Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:04
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820
Simulation Timestamp: 2023-10-16 09:04:27
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:27
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 33375.49 | 720.54 | 720.54 |
Net Site Energy | 33375.49 | 720.54 | 720.54 |
Total Source Energy | 104496.57 | 2255.95 | 2255.95 |
Net Source Energy | 104496.57 | 2255.95 | 2255.95 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 18.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 6499.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 2741.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 447.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 15213.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1914.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2647.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1289.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 1962.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18423.02 |
Humidification | 82.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.74 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 559.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 32797.66 | 577.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20733.93 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 18.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 6499.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 2741.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 447.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5871.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 59.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 1848.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 5.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 2647.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 1289.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 1962.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18423.02 |
Humidification | General | 82.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.74 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Water Heater | 0.00 | 559.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 18.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 6499.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 2741.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 447.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 15213.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 1914.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 2647.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 1289.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 1962.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18423.02 |
Humidification | Unassigned | 82.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.74 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 559.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 68.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 269.44 | 12.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.45 |
Other | 369.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 708.06 | 12.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.45 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 68.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 269.44 | 12.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.45 |
Other | 369.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 708.06 | 12.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.45 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 32797.665 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 32797.665 | 100.00 |
Total On-Site and Utility Electric Sources | 32797.665 | 100.00 |
Total Electricity End Uses | 32797.665 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 20733.93 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 20733.93 | 100.00 |
Total Water End Uses | 20733.93 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 1100.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5943.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY IND_DELHI_NEWDELHI
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| HEATSYS1 BOILER | CENTRAL BOILER |DXReportMonthly
| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |FanReportMonthly
| CAV_BAS FAN | VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:27
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:04 |
RunPeriod | RUNPERIOD 1 |
Weather File | New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 |
Latitude [deg] | 28.58 |
Longitude [deg] | 77.20 |
Elevation [m] | 216.00 |
Time Zone | 5.50 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 3476.85 | 1043.06 | 695.37 | 1043.06 | 695.37 |
Gross Window-Wall Ratio [%] | 28.54 | 28.54 | 28.54 | 28.54 | 28.54 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 3476.85 | 1043.06 | 695.37 | 1043.06 | 695.37 |
Gross Window-Wall Ratio [%] | 28.54 | 28.54 | 28.54 | 28.54 | 28.54 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 7.6202 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.6202 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.6202 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.6202 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 7.6202 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 7.6202 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 7.6202 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 7.6202 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 86.92 | 86.92 | 7.6202 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 57.95 | 57.95 | 7.6202 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 86.92 | 86.92 | 7.6202 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 57.95 | 57.95 | 7.6202 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 7.6202 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 7.6202 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 7.6202 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 7.6202 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.5114 | 18.58 | 215.2992 |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.5114 | 18.58 | 215.2992 |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.5114 | 18.58 | 215.2992 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 7.6202 | 18.58 | 484.4232 |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 3476.85 | 3476.85 | 7.6661 | 18.58 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 3476.85 | 3476.85 | 7.6661 | 18.58 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 2779.43 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 7.6202 | 18.58 | 4.8418 | |
CORE_BOTTOM | 2496.12 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 7.6202 | 18.58 | 8.0697 | |
CORE_MID | 2496.12 | Yes | Yes | 10.00 | CORE_MID | GENERAL | CORE_MID | 7.6202 | 18.58 | 8.0696 | |
CORE_TOP | 2496.12 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 7.6202 | 18.58 | 8.0696 | |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 7.6202 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 7.6202 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 7.6202 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 7.6202 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 7.6202 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 7.6202 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 7.6202 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 7.6202 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 7.6202 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 7.6202 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 7.6202 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 7.6202 | 18.58 | 8.0699 | |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | GROUNDFLOOR_PLENUM | GENERAL | GROUNDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 10.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_BOT_ZN_6 | GENERAL | DATACENTER_BOT_ZN_6 | 12.5114 | 18.58 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 10.00 | DATACENTER_MID_ZN_6 | GENERAL | DATACENTER_MID_ZN_6 | 12.5114 | 18.58 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_TOP_ZN_6 | GENERAL | DATACENTER_TOP_ZN_6 | 12.5114 | 18.58 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1.00 | DATACENTER_BASEMENT_ZN_6 | GENERAL | DATACENTER_BASEMENT_ZN_6 | 7.6202 | 18.58 | 484.4232 | |
Total | 46320.38 | 7.6661 | 9.29 | 17.8789 | |||||||
Conditioned Total | 46320.38 | 7.6661 | 9.29 | 17.8789 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 42757.27 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 46320.38 | 46320.38 | 0.00 | 42757.27 | 2.3561 | 60.38 | 10.8345 |
Total | 46320.38 | 46320.38 | 0.00 | 42757.27 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:27
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 07-AUG-15:09 | 02-JAN-06:19 | - | - | - | - | - | - | - | - | - | - | 19-APR-15:09 |
Heating | 0.00 | 217619.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 559423.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 234435.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 794004.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 83146.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 212155.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 67734.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 91812.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 26548.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 2042710.94 | 244167.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 217619.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 559423.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 234435.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 320838.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 3711.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 79171.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 263.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 212155.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 67734.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 91812.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 26548.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:27
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 19.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 20582.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 8683.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 1416.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 48180.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 6062.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 8384.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 4083.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 6213.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 261.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 606.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 103870.20 | 626.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 444.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 187.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 30.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1040.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 130.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 181.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 88.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 134.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 5.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 13.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2242.43 | 13.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 444.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 187.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 30.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1040.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 130.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 181.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 88.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 134.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 5.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 13.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2242.43 | 13.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:27
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
BASEMENT DIRECT AIR | 5.57 |
DATACENTER_BOT_ZN_6 DIRECT AIR | 0.482956 |
DATACENTER_MID_ZN_6 DIRECT AIR | 4.60 |
DATACENTER_TOP_ZN_6 DIRECT AIR | 0.463312 |
DATACENTER_BASEMENT_ZN_6 DIRECT AIR | 21.90 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 5.95 | 0.319862 | 0.326000 | 1.94 | 0.852965 | 0.500000 | 0.001191 | 0.000166 | 1.94 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 56.33 | 0.337662 | 0.339000 | 19.10 | 0.900432 | 0.500000 | 0.001128 | 0.003077 | 19.10 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 5.86 | 0.324791 | 0.338000 | 1.98 | 0.866109 | 0.500000 | 0.001173 | 0.000547 | 1.98 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 1.17 | 0.203374 | 0.208000 | 0.244253 | 0.542330 | 0.500000 | 0.001873 | 0.000036 | 0.244253 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.920155 | 0.167260 | 0.200000 | 0.184031 | 0.446026 | 0.500000 | 0.002278 | 0.000028 | 0.184031 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.20 | 0.199785 | 0.204000 | 0.243864 | 0.532760 | 0.500000 | 0.001907 | 0.000052 | 0.243864 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 1.21 | 0.127613 | 0.200000 | 0.241205 | 0.340302 | 0.500000 | 0.002986 | 0.000022 | 0.241205 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 11.40 | 0.209451 | 0.210000 | 2.39 | 0.558536 | 0.500000 | 0.001819 | 0.001070 | 3.74 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 9.53 | 0.161524 | 0.200000 | 1.91 | 0.430731 | 0.500000 | 0.002359 | 0.000713 | 2.49 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 11.50 | 0.207593 | 0.209000 | 2.40 | 0.553580 | 0.500000 | 0.001835 | 0.001070 | 3.74 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 10.21 | 0.150804 | 0.200000 | 2.04 | 0.402144 | 0.500000 | 0.002526 | 0.000617 | 2.15 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 1.34 | 0.177999 | 0.200000 | 0.268339 | 0.474664 | 0.500000 | 0.002140 | 0.000155 | 0.540259 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.02 | 0.150733 | 0.200000 | 0.204209 | 0.401954 | 0.500000 | 0.002528 | 0.000102 | 0.355715 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.34 | 0.177655 | 0.200000 | 0.268864 | 0.473748 | 0.500000 | 0.002145 | 0.000155 | 0.540265 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.15 | 0.133392 | 0.200000 | 0.230757 | 0.355711 | 0.500000 | 0.002856 | 0.000094 | 0.329853 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 19026.36 | 0.000166 | 383.56 |
CORE_MID VAV BOX REHEAT COIL | 351752.39 | 0.003077 | 7765.61 |
CORE_TOP VAV BOX REHEAT COIL | 62504.34 | 0.000547 | 1623.56 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 4066.49 | 0.000036 | 88.03 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 3242.83 | 0.000028 | 70.96 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 5927.70 | 0.000052 | 140.17 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 2512.97 | 0.000022 | 50.97 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 122321.44 | 0.001070 | 3228.47 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 81481.53 | 0.000713 | 2150.45 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 122322.11 | 0.001070 | 3228.48 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 70505.88 | 0.000617 | 1861.23 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 17668.25 | 0.000155 | 466.11 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 11632.41 | 0.000102 | 306.87 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 17668.43 | 0.000155 | 466.11 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 10788.67 | 0.000094 | 284.63 |
VAV_BOT WITH REHEAT HEATING COIL | 22570.87 | 0.000197 | 394.69 |
VAV_MID WITH REHEAT HEATING COIL | 171567.88 | 0.001501 | 3027.85 |
VAV_TOP WITH REHEAT HEATING COIL | 13282.34 | 0.000116 | 237.36 |
CAV_BAS HEATING COIL | 253780.16 | 0.002220 | 5777.81 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT | 5.22 | 2.85 | 10.44 | 2.85 | 9.81 | 9.81 | 0.300000 | 0.290745 | 9.81 |
VAV_MID WITH REHEAT | 49.49 | 27.84 | 98.97 | 27.84 | 92.79 | 92.79 | 0.300000 | 0.300057 | 92.79 |
VAV_TOP WITH REHEAT | 5.36 | 2.95 | 10.72 | 3.64 | 10.59 | 10.59 | 0.300000 | 0.343589 | 10.59 |
CAV_BAS | 5.57 | 5.57 | 5.57 | 5.57 | 5.57 | 5.57 | 1.00 | 1.00 | 5.57 |
AIRLOOP DATACENTER BASEMENT | 21.90 | 21.90 | 21.90 | 21.90 | 21.90 | 21.90 | 1.00 | 0.999988 | 21.90 |
AIRLOOP DATACENTER BOT | 0.482956 | 0.482956 | 0.482956 | 0.482956 | 0.482956 | 0.482956 | 1.00 | 1.00 | 0.482956 |
AIRLOOP DATACENTER MID | 4.60 | 4.60 | 4.60 | 4.60 | 4.60 | 4.60 | 1.00 | 1.00 | 4.60 |
AIRLOOP DATACENTER TOP | 0.463312 | 0.463312 | 0.463312 | 0.463312 | 0.463312 | 0.463312 | 1.00 | 1.00 | 0.463312 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 9.81 | |
VAV_MID WITH REHEAT_OA_CONTROLLER | 92.79 | |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 10.59 | |
CAV_BAS_OA_CONTROLLER | 5.57 | 1.20 |
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | 21.90 | 0.338393 |
AIRLOOP DATACENTER BOT_OA_CONTROLLER | 0.482956 | 0.015632 |
AIRLOOP DATACENTER MID_OA_CONTROLLER | 4.60 | 0.156323 |
AIRLOOP DATACENTER TOP_OA_CONTROLLER | 0.463312 | 0.015632 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT COOLING COIL | 28.81 | 6.67 | 10.99 | 0.007833 | 0.007000 | 233283.98 | 0.009924 | 9.81 |
VAV_MID WITH REHEAT COOLING COIL | 29.27 | 6.67 | 10.99 | 0.007914 | 0.007000 | 2280072.41 | 0.097000 | 92.79 |
VAV_TOP WITH REHEAT COOLING COIL | 28.32 | 6.67 | 11.00 | 0.007772 | 0.007000 | 243601.62 | 0.010363 | 10.59 |
CAV_BAS COOLING COIL | 27.70 | 6.67 | 11.38 | 0.007883 | 0.007000 | 123307.64 | 0.005246 | 5.57 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 9.81 |
VAV_MID WITH REHEAT FAN | 92.79 |
VAV_TOP WITH REHEAT FAN | 10.59 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.009924 | 0.000048 |
VAV_BOT WITH REHEAT_HEATC_CONTROLLER | 0.000197 | |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.097000 | 0.000005 |
VAV_MID WITH REHEAT_HEATC_CONTROLLER | 0.001501 | |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.010363 | 0.000046 |
VAV_TOP WITH REHEAT_HEATC_CONTROLLER | 0.000116 | |
CAV_BAS_COOLC_CONTROLLER | 0.005246 | 0.000091 |
CAV_BAS_HEATC_CONTROLLER | 0.002220 |
Design Size Maximum Flow Rate [m3/s] | |
CAV_BAS FAN | 5.57 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Total Cooling Capacity [W] | Design Size Rated Sensible Cooling Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | 21.90 | 451109.56 | 280919.89 | 0.011048 |
AIRLOOP DATACENTER BOT COOLING COIL | 0.482956 | 9672.22 | 6096.44 | 0.000237 |
AIRLOOP DATACENTER MID COOLING COIL | 4.60 | 92221.08 | 58100.27 | 0.002258 |
AIRLOOP DATACENTER TOP COOLING COIL | 0.463312 | 9540.07 | 5930.05 | 0.000234 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | 21.90 | 21.90 | 21.90 | 21.90 | 451109.56 | 451109.56 | 13450.69 | 1.00 |
AIRLOOP DATACENTER BOT DXAC HEAT PUMP | 0.482956 | 0.482956 | 0.482956 | 0.482956 | 9672.22 | 9672.22 | 621.37 | 1.00 |
AIRLOOP DATACENTER MID DXAC HEAT PUMP | 4.60 | 4.60 | 4.60 | 4.60 | 92221.08 | 92221.08 | 6213.66 | 1.00 |
AIRLOOP DATACENTER TOP DXAC HEAT PUMP | 0.463312 | 0.463312 | 0.463312 | 0.463312 | 9540.07 | 9540.07 | 621.37 | 1.00 |
Design Size Maximum Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | 21.90 |
AIRLOOP DATACENTER BOT SUPPLY FAN | 0.482956 |
AIRLOOP DATACENTER MID SUPPLY FAN | 4.60 |
AIRLOOP DATACENTER TOP SUPPLY FAN | 0.463312 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Heating Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | 21.90 | 451109.56 | 0.011048 |
AIRLOOP DATACENTER BOT HEATING COIL | 0.482956 | 9672.22 | 0.000237 |
AIRLOOP DATACENTER MID HEATING COIL | 4.60 | 92221.08 | 0.002258 |
AIRLOOP DATACENTER TOP HEATING COIL | 0.463312 | 9540.07 | 0.000234 |
Design Size Nominal Capacity [W] | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | 13450.69 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | 621.37 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | 6213.66 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | 621.37 |
Design Size Nominal Capacity Volume [m3/s] | User-Specified Nominal Capacity Volume [m3/s] | Design Size Rated Power [W] | User-Specified Rated Power [W] | |
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | 0.000048 | 0.000037 | 96450.70 | 100000.00 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.122533 | 25249.54 | |
HEATSYS1 PUMP | 0.011938 | 3595.30 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.122533 | 14.70 |
HEATSYS1 | 0.011938 | 1.43 |
COOLSYS1_SUPPLY | 0.122533 | 14.70 |
SINGLE WATER PLANT LOOP | 0.013777 | 1.65 |
SWHSYS1 | 0.000440 | 0.052800 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.122533 | 0.122533 | 514333.15 | 5.60 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 1364623.04 | 1364623.04 | 0.011938 |
CENTRAL BOILER | 567479.46 | 556467.27 | 0.013777 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP | 0.122533 | 17481.11 |
PLANT CIRC PUMP | 0.013777 | 3513.73 |
SWHSYS1 PUMP | 0.000440 | 5.96 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Water Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.122533 | 0.061850 | 1457418.04 | 1464382.66 | 0.072467 |
COOLSYS1 CHILLER2 | 0.122533 | 0.061850 | 1457418.04 | 1464382.66 | 0.072467 |
Design Water Flow Rate [m3/s] | Air Flow Rate at High Fan Speed [m3/s] | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | Air Flow Rate at Low Fan Speed [m3/s] | Fan Power at Low Fan Speed [W] | U-factor Times Area Value at Low Fan Speed [W/C] | |
CENTRAL TOWER | 0.013777 | 139666.47 | 57485.43 | 69833.23 | 7879.72 | 21233.18 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000440 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.144934 | 17.39 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.144934 | 43650.89 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 57.46 | 1737449.05 | 11.49 | 217181.13 |
TOWERWATERSYS COOLTOWER 2 | 57.46 | 1737449.05 | 11.49 | 217181.13 |
Design Water Flow Rate [m3/s] Equipment # 47 | |
WSHPPLANT OPERATION SCHEME | 0.075270 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:27
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:27
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:27
VersionVersion ID | |
1 | 22.1.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 25.10 | 19.60 | 14.50 | 13.40 | 17.00 | 22.40 | 29.10 | 33.00 | 33.60 | 31.70 | 30.00 | 28.70 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 | 28.58 | 77.20 | 5.50 | 216.00 | 98757 | 1.1738 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 24.84 | 20.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 105.88 | 86.92 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 71.89 | 57.95 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 105.88 | 86.92 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 71.89 | 57.95 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 7.620 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 12.462 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 12.511 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 227.811 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 12.511 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 227.811 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 12.511 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 227.811 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 18.579 | 5.382E-002 | 7.620 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 492.043 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DATACENTER_BOT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | DATACENTER_MID_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | DATACENTER_TOP_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | DATACENTER_BASEMENT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 42.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 42 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_OFFICE | BASEMENT | 2779.43 | 149.6 | 21179.739 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 21179.739 |
2 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 2496.12 | 134.4 | 19020.895 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 19020.895 |
3 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 2496.12 | 134.4 | 19020.895 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 19020.895 |
4 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 2496.12 | 134.4 | 19020.895 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 19020.895 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2388.263 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2388.263 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1539.088 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1539.088 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2388.315 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2388.315 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1539.088 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1539.088 |
9 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2388.263 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2388.263 |
10 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1539.088 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1539.088 |
11 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2388.315 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2388.315 |
12 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1539.088 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1539.088 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2388.263 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2388.263 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1539.088 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1539.088 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2388.315 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2388.315 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1539.088 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1539.088 |
17 | DATACENTER_BASEMENT_LIGHTS | LTG_SCH_OFFICE | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 5971.780 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5971.780 |
18 | DATACENTER_BOT_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 452.948 | 12.511 | 232.447 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 452.948 |
19 | DATACENTER_MID_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 452.948 | 12.511 | 232.447 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 452.948 |
20 | DATACENTER_TOP_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 452.948 | 12.511 | 232.447 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 452.948 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 379632.522 | 484.423 | 9000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.464 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2832 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
9 | NONRES_EXT_WALL_GRD | 20 | 3 | 9 | 0.167 | 1.743 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | NONRES_EXT_WALL_MID | 21 | 3 | 9 | 0.167 | 1.656 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | NONRES_EXT_WALL_TOP | 22 | 3 | 9 | 0.167 | 2.135 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | BASEMENT_WALL_EAST_CFACTOR | 39 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_SOUTH_CFACTOR | 40 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BASEMENT_WALL_NORTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 42 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 43 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 44 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2887 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.472 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4064 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4365 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3009 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
32 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
33 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
34 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
35 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.4637404 | 3.4637404 | 3.4637404 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.61927053E-06 | 0.12767249E-08 | -0.37968499E-05 | 0.16832131E-17 |
47 | 2 | 0.77611055 | 0.17315568E-02 | 1.0534842 | -0.72792597E-06 |
48 | 1 | -21.915918 | 0.11588205 | -6.3286394 | 0.20197014 |
49 | 0 | 21.365777 | 0.10835518 | 5.5011278 | |
50 | 9 | 0.76055735E-15 | 0.55973061E-16 | -0.11090261E-09 | -0.43371185E-17 |
51 | 8 | 0.16390423E-07 | 0.22068143E-12 | 0.31740643E-03 | -0.18636477E-09 |
52 | 7 | -0.10429999E-01 | 0.12271718E-07 | -0.20474149E-01 | 0.11859286E-03 |
53 | 6 | 0.35611320 | 0.43955117E-05 | 0.42991281 | -0.41673803E-02 |
54 | 5 | -4.7098961 | 0.16827687E-03 | -4.1162358 | 0.57223947E-01 |
55 | 4 | 30.875684 | 0.14076848E-02 | 20.167480 | -0.39388153 |
56 | 3 | -106.69740 | 0.31291265E-02 | -53.106522 | 1.4497707 |
57 | 2 | 192.63914 | 0.17911574E-02 | 75.570394 | -2.8293896 |
58 | 1 | -169.50392 | 0.19431750E-03 | -54.592911 | 2.7164834 |
59 | 0 | 57.057407 | 0.11257899E-05 | 15.674734 | |
60 | 9 | 0.11474244E-14 | 0.54197419E-16 | -0.11508650E-09 | -0.49945851E-17 |
61 | 8 | 0.16984416E-07 | 0.21156325E-12 | 0.32425024E-03 | -0.19311866E-09 |
62 | 7 | -0.10636353E-01 | 0.11664670E-07 | -0.20772028E-01 | 0.12093918E-03 |
63 | 6 | 0.36172330 | 0.41637772E-05 | 0.43474562 | -0.42335086E-02 |
64 | 5 | -4.7646824 | 0.15893927E-03 | -4.1535939 | 0.57903236E-01 |
65 | 4 | 31.118254 | 0.13261305E-02 | 20.314042 | -0.39710182 |
66 | 3 | -107.21418 | 0.29411649E-02 | -53.396504 | 1.4572354 |
67 | 2 | 193.15212 | 0.16802168E-02 | 75.835339 | -2.8375342 |
68 | 1 | -169.69371 | 0.18194848E-03 | -54.668081 | 2.7198097 |
69 | 0 | 57.057407 | 0.10520719E-05 | 15.660794 | |
70 | 9 | 0.66246833E-15 | 0.57738042E-16 | -0.92036509E-10 | -0.27018983E-17 |
71 | 8 | 0.13701644E-07 | 0.25726543E-12 | 0.28527343E-03 | -0.15579243E-09 |
72 | 7 | -0.94571194E-02 | 0.14940887E-07 | -0.19068097E-01 | 0.10753086E-03 |
73 | 6 | 0.32965778 | 0.54453531E-05 | 0.40701455 | -0.38555430E-02 |
74 | 5 | -4.4514676 | 0.21157254E-03 | -3.9387765 | 0.54019785E-01 |
75 | 4 | 29.731016 | 0.17930056E-02 | 19.470280 | -0.37868589 |
76 | 3 | -104.25747 | 0.40308508E-02 | -51.726693 | 1.4145289 |
77 | 2 | 190.21562 | 0.23301583E-02 | 74.311741 | -2.7909129 |
78 | 1 | -168.60668 | 0.25508611E-03 | -54.239505 | 2.7007581 |
79 | 0 | 57.057407 | 0.14924561E-05 | 15.743350 | |
80 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
81 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
82 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
83 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
84 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
85 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
86 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
87 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
88 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
89 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
90 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
91 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
92 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
93 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
94 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
95 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
96 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
97 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
98 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
99 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
100 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
101 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
102 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
103 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
104 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
105 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
106 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
107 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
108 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
109 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
110 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
111 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
112 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
113 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
114 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
115 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
116 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
117 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
118 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
119 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
120 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
121 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
122 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
123 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
124 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
125 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
126 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
127 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.5047_SHGC_EAST_0.25 | 35 | 1 | VerySmooth | 2.869 | 2.869 | 1.000 | 0.251 | ||
2 | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | 36 | 1 | VerySmooth | 2.869 | 2.869 | 1.000 | 0.251 | ||
3 | WINDOW_U_0.5047_SHGC_WEST_0.25 | 37 | 1 | VerySmooth | 2.869 | 2.869 | 1.000 | 0.251 | ||
4 | WINDOW_U_0.5047_SHGC_NORTH_0.25 | 38 | 1 | VerySmooth | 2.869 | 2.869 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 1.90891E-002 | 0.16139 | 0.61055 | 0.61055 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.10708 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 1.90891E-002 | 0.16139 | 0.61055 | 0.61055 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.10708 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 1.90891E-002 | 0.16139 | 0.61055 | 0.61055 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.10708 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 1.90891E-002 | 0.16139 | 0.61055 | 0.61055 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.10708 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_BOT_ZN_3 | 5 | 0 |
2 | PERIMETER_BOT_ZN_2 | 3 | 0 |
3 | PERIMETER_BOT_ZN_1 | 5 | 0 |
4 | PERIMETER_BOT_ZN_4 | 3 | 0 |
5 | PERIMETER_MID_ZN_3 | 1 | 0 |
6 | PERIMETER_MID_ZN_2 | 1 | 0 |
7 | PERIMETER_MID_ZN_1 | 1 | 0 |
8 | PERIMETER_MID_ZN_4 | 1 | 0 |
9 | PERIMETER_TOP_ZN_3 | 1 | 0 |
10 | PERIMETER_TOP_ZN_2 | 1 | 0 |
11 | PERIMETER_TOP_ZN_1 | 1 | 0 |
12 | PERIMETER_TOP_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_BOT_ZN_3 | 0 | |
2 | PERIMETER_BOT_ZN_2 | 0 | |
3 | PERIMETER_BOT_ZN_1 | 0 | |
4 | PERIMETER_BOT_ZN_4 | 0 | |
5 | PERIMETER_MID_ZN_3 | 0 | |
6 | PERIMETER_MID_ZN_2 | 0 | |
7 | PERIMETER_MID_ZN_1 | 0 | |
8 | PERIMETER_MID_ZN_4 | 0 | |
9 | PERIMETER_TOP_ZN_3 | 0 | |
10 | PERIMETER_TOP_ZN_2 | 0 | |
11 | PERIMETER_TOP_ZN_1 | 0 | |
12 | PERIMETER_TOP_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 1.1356 | 87921.3 | 0.496 | 7.5104E-002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 4.384E-005 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.6556E-003 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.6567E-003 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.8034E-003 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.8043E-003 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.1458E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.1465E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.2447E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.2452E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.6818E-003 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.7553E-003 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.8248E-003 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.8865E-003 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.1628E-003 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.2127E-003 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.2574E-003 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.2891E-003 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.3694E-002 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.0906E-002 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.1712E-002 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.2798E-002 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.0286E-002 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.2382E-002 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.6042E-002 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 9.1095E-003 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.6871E-003 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.7813E-003 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.8306E-003 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.9145E-003 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.1681E-003 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.2329E-003 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.2577E-003 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.2900E-003 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.6555E-003 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.6568E-003 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.8033E-003 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.8044E-003 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.1458E-003 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.1467E-003 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.2447E-003 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.2451E-003 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.7734E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.9022E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.6487E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.7820E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.5073E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.5748E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.1302E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.1521E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.2792E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.5967E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.1179E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.4553E-002 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.3343E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.3602E-002 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.6787E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 9.9865E-003 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.7433E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.7949E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.6113E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.6492E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.4871E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.5031E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.1303E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.1525E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.2193E-003 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2205E-003 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.0482E-003 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.0492E-003 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 9.2927E-004 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 9.2997E-004 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.2447E-003 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2452E-003 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.2462E-003 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3126E-003 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.0702E-003 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1232E-003 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 9.4683E-004 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 9.8505E-004 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.2577E-003 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2900E-003 |
81 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.8970E-002 |
82 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.0736E-002 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.4831E-002 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 8.2182E-003 |
85 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.4618E-002 |
86 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 5.7927E-003 |
87 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.6042E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 9.1067E-003 |
89 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.2442E-003 |
90 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3101E-003 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.0678E-003 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1184E-003 |
93 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 9.4273E-004 |
94 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 9.7257E-004 |
95 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.2574E-003 |
96 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2891E-003 |
97 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.2192E-003 |
98 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2203E-003 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.0481E-003 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.0490E-003 |
101 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 9.2918E-004 |
102 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 9.2973E-004 |
103 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.2447E-003 |
104 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2451E-003 |
105 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.3719E-003 |
106 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.4257E-003 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.1617E-003 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.2007E-003 |
109 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.1392E-003 |
110 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.1537E-003 |
111 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.1303E-003 |
112 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.1525E-003 |
113 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.5554E-002 |
114 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.3237E-002 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.2515E-002 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.1301E-002 |
117 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.6176E-002 |
118 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.0860E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.6787E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 9.9865E-003 |
121 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.3958E-003 |
122 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.4967E-003 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.1920E-003 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.2913E-003 |
125 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.1581E-003 |
126 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.2174E-003 |
127 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.1302E-003 |
128 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.1521E-003 |
129 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 7.2526E-002 |
130 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 4.2005E-002 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 7.8513E-002 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 4.4500E-002 |
133 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 6.3253E-002 |
134 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 3.1602E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 3.0133E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 1.4574E-002 |
137 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.7645E-002 |
138 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.2088E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.5896E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.0428E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.7878E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.9148E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.0820E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.4729E-002 |
145 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.2887E-002 |
146 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.5929E-002 |
147 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 1.8364E-002 |
148 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.2718E-002 |
149 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 1.8071E-002 |
150 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 9.9091E-003 |
151 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.0133E-002 |
152 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.4571E-002 |
153 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 2.9784E-002 |
154 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.8510E-002 |
155 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 2.6470E-002 |
156 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.6146E-002 |
157 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.0155E-002 |
158 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.5644E-002 |
159 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.0820E-002 |
160 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.4729E-002 |
161 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 7.2523E-002 |
162 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 4.2071E-002 |
163 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 7.8524E-002 |
164 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 4.4578E-002 |
165 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 6.3293E-002 |
166 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 3.1668E-002 |
167 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 3.0168E-002 |
168 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 1.4602E-002 |
169 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.7636E-002 |
170 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.2110E-002 |
171 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.5896E-002 |
172 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.0450E-002 |
173 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.7898E-002 |
174 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.9182E-002 |
175 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.0854E-002 |
176 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.4757E-002 |
177 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.2861E-002 |
178 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.5936E-002 |
179 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 1.8346E-002 |
180 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.2724E-002 |
181 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 1.8081E-002 |
182 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 9.9234E-003 |
183 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.0168E-002 |
184 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.4599E-002 |
185 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 2.9768E-002 |
186 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.8524E-002 |
187 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 2.6462E-002 |
188 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.6160E-002 |
189 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.0169E-002 |
190 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.5670E-002 |
191 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.0854E-002 |
192 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.4757E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 75181.81742 | 75181.81742 | 5.56805 | 5.56805 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 34.82200 | 9.14597E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20016 | 00:10:00 | 6.30000 | 6.07234E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 | |
3 | CORE_BOTTOM | Cooling | 80291.25723 | 80291.25723 | 5.94646 | 5.94646 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 34.82200 | 9.14597E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
4 | CORE_BOTTOM | Heating | 0.00000 | 0.00000 | 0.00000 | 1.07782 | 00:10:00 | 6.30000 | 6.07234E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 | |
5 | CORE_MID | Cooling | 760763.86913 | 760763.86913 | 56.32982 | 56.32982 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 34.82200 | 9.14597E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
6 | CORE_MID | Heating | 164331.48709 | 164331.48709 | 7.04256 | 10.77825 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
7 | CORE_TOP | Cooling | 78353.55371 | 78353.55371 | 5.85621 | 5.85621 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:50:00 | 42.00000 | 9.15790E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
8 | CORE_TOP | Heating | 43076.99797 | 43076.99797 | 1.87236 | 1.87236 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 15711.61378 | 15711.61378 | 1.17429 | 1.17429 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:20:00 | 41.80600 | 9.15758E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 1670.32548 | 1670.32548 | 7.25146E-002 | 0.13533 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 12311.34991 | 12311.34991 | 0.92016 | 0.92016 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 10:10:00 | 38.55650 | 9.15215E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 1437.36817 | 1437.36817 | 6.21895E-002 | 8.72129E-002 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 15994.18128 | 15994.18128 | 1.19541 | 1.19541 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | 42.00000 | 9.15790E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 3534.94656 | 3534.94656 | 0.15294 | 0.15294 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 16136.28664 | 16136.28664 | 1.20603 | 1.20603 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:20:00 | 41.15933 | 9.15650E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 149.21061 | 149.21061 | 6.54944E-003 | 8.72129E-002 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
17 | PERIMETER_MID_ZN_3 | Cooling | 152555.09452 | 152555.09452 | 11.40222 | 11.40222 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:30:00 | 41.70900 | 9.15741E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 85655.61543 | 85655.61543 | 3.73659 | 3.73659 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 127483.44478 | 127483.44478 | 9.52830 | 9.52830 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 10:20:00 | 38.79900 | 9.15255E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 57054.55283 | 57054.55283 | 2.48932 | 2.48932 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 153924.07964 | 153924.07964 | 11.50455 | 11.50455 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:10:00 | 42.00000 | 9.15790E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 85656.08753 | 85656.08753 | 3.73661 | 3.73661 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 136545.97971 | 136545.97971 | 10.20564 | 10.20564 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:30:00 | 41.03000 | 9.15628E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 49381.77448 | 49381.77448 | 2.15288 | 2.15288 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 17951.06011 | 17951.06011 | 1.34170 | 1.34170 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:40:00 | 41.61200 | 9.15725E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 12366.35462 | 12366.35462 | 0.54026 | 0.54026 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 13660.96349 | 13660.96349 | 1.02105 | 1.02105 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 10:40:00 | 39.28400 | 9.15337E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 8141.55349 | 8141.55349 | 0.35572 | 0.35572 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 17986.16464 | 17986.16464 | 1.34432 | 1.34432 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:40:00 | 42.00000 | 9.15790E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 12366.47583 | 12366.47583 | 0.54026 | 0.54026 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 15436.93151 | 15436.93151 | 1.15378 | 1.15378 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:20:00 | 41.15933 | 9.15650E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 7551.69961 | 7551.69961 | 0.32985 | 0.32985 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30000 | 6.07234E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 8193.50212 | 8193.50212 | 0.48296 | 0.48296 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:20:00 | 32.36467 | 9.14193E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | 00:10:00 | 6.30000 | 6.07234E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 | |
35 | DATACENTER_MID_ZN_6 | Cooling | 78050.85023 | 78050.85023 | 4.60061 | 4.60061 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:20:00 | 32.36467 | 9.14193E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15632 | 00:10:00 | 6.30000 | 6.07234E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 | |
37 | DATACENTER_TOP_ZN_6 | Cooling | 7859.30186 | 7859.30186 | 0.46331 | 0.46331 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:40:00 | 40.90067 | 9.15606E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | 00:10:00 | 6.30000 | 6.07234E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 | |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 371509.00917 | 371509.00917 | 21.90024 | 21.90024 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 07:00:00 | 33.17300 | 9.14325E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33839 | 00:10:00 | 6.30000 | 6.07234E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV_BOT WITH REHEAT | Cooling | Sensible | 179307.50 | 9.80894 | 9.80894 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 00:00:00 |
2 | VAV_BOT WITH REHEAT | Heating | Sensible | 11810.70 | 1.54052 | 1.54052 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
3 | VAV_MID WITH REHEAT | Cooling | Sensible | 1684130.86 | 92.78733 | 92.78733 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 00:00:00 |
4 | VAV_MID WITH REHEAT | Heating | Sensible | 175518.16 | 22.89365 | 22.89365 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
5 | VAV_TOP WITH REHEAT | Cooling | Sensible | 193487.50 | 10.58956 | 10.58956 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 00:00:00 |
6 | VAV_TOP WITH REHEAT | Heating | Sensible | 19399.83 | 3.63846 | 3.63846 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 |
7 | CAV_BAS | Cooling | Sensible | 89805.36 | 5.56805 | 5.56805 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
8 | CAV_BAS | Heating | Sensible | 47704.73 | 1.20016 | 1.20016 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
9 | AIRLOOP DATACENTER BASEMENT | Cooling | Sensible | 372287.85 | 21.90051 | 21.90051 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
10 | AIRLOOP DATACENTER BASEMENT | Heating | Sensible | 13450.69 | 0.33839 | 0.33839 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
11 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 8187.82 | 0.48296 | 0.48296 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
12 | AIRLOOP DATACENTER BOT | Heating | Sensible | 621.37 | 1.56323E-002 | 1.56323E-002 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
13 | AIRLOOP DATACENTER MID | Cooling | Sensible | 78043.59 | 4.60061 | 4.60061 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
14 | AIRLOOP DATACENTER MID | Heating | Sensible | 6213.66 | 0.15632 | 0.15632 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
15 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 8019.11 | 0.46331 | 0.46331 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:00:00 |
16 | AIRLOOP DATACENTER TOP | Heating | Sensible | 621.37 | 1.56323E-002 | 1.56323E-002 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | BASEMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 5.56805 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.94646 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.31986 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.32600 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.93854 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.85296 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.19114E-003 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.66451E-004 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.93854 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
13 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 19026.36169 |
14 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.66451E-004 |
15 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 383.55652 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 56.32982 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.33766 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.33900 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 19.09581 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.90043 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.12835E-003 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.07728E-003 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 19.09581 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
27 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 351752.38731 |
28 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.07728E-003 |
29 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 7765.61402 |
30 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.85621 |
31 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.32479 |
32 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.33800 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.97940 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.86611 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.17306E-003 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.46815E-004 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.97940 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
40 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
41 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 62504.33746 |
42 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.46815E-004 |
43 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1623.56270 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.17429 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20337 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20800 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.24425 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.54233 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.87340E-003 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.55754E-005 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.24425 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
55 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 4066.49209 |
56 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.55754E-005 |
57 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 88.03434 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.92016 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16726 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.18403 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.44603 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.27789E-003 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.83697E-005 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.18403 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
69 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 3242.82773 |
70 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.83697E-005 |
71 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 70.95758 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.19541 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19979 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20400 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.24386 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.53276 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.90705E-003 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.18581E-005 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.24386 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
83 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 5927.69989 |
84 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.18581E-005 |
85 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 140.16754 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.20603 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12761 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.24121 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.34030 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.98558E-003 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.19845E-005 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.24121 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
97 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 2512.96726 |
98 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.19845E-005 |
99 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 50.96716 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 11.40222 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20945 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.21000 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.39447 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.55854 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.81904E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.07012E-003 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.73659 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 122321.44301 |
112 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.07012E-003 |
113 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 3228.46535 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 9.52830 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16152 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.90566 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.43073 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.35878E-003 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.12836E-004 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.48932 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
124 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
125 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 81481.53457 |
126 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.12836E-004 |
127 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2150.45456 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 11.50455 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20759 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20900 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.40445 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.55358 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.83533E-003 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.07013E-003 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.73661 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
138 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
139 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 122322.11399 |
140 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.07013E-003 |
141 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 3228.48315 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 10.20564 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15080 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.04113 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.40214 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.52646E-003 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.16816E-004 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.15288 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
152 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
153 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 70505.87724 |
154 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.16816E-004 |
155 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1861.23416 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.34170 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17800 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.26834 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.47466 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.14046E-003 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.54570E-004 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.54026 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
166 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
167 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 17668.25253 |
168 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.54570E-004 |
169 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 466.10897 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.02105 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15073 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20421 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.40195 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.52765E-003 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.01765E-004 |
178 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.35572 |
179 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
180 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
181 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11632.41214 |
182 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.01765E-004 |
183 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 306.86877 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.34432 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17766 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.26886 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.47375 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.14460E-003 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.54571E-004 |
192 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.54026 |
193 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
194 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
195 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 17668.42545 |
196 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.54571E-004 |
197 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 466.11354 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.15378 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13339 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.23076 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.35571 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.85625E-003 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.43840E-005 |
206 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.32985 |
207 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
208 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
209 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10788.66831 |
210 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.43840E-005 |
211 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 284.63449 |
212 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BOT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.48296 |
213 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_MID_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.60061 |
214 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_TOP_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.46331 |
215 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BASEMENT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 21.90024 |
216 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.22117 |
217 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.85190 |
218 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 10.44235 |
219 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 2.85190 |
220 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 9.80894 |
221 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 9.80894 |
222 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
223 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.29074 |
224 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 49.48527 |
225 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 27.84151 |
226 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 98.97053 |
227 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 27.84151 |
228 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 92.78733 |
229 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 92.78733 |
230 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
231 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.30006 |
232 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.35853 |
233 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.95157 |
234 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 10.71706 |
235 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 3.63846 |
236 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 10.58956 |
237 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 10.58956 |
238 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
239 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.34359 |
240 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.56805 |
241 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 5.56805 |
242 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.56805 |
243 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 5.56805 |
244 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.56805 |
245 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 5.56805 |
246 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
247 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
248 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 21.90024 |
249 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 21.90024 |
250 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 21.90024 |
251 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Heating Design Air Flow Rate [m3/s] | 21.90024 |
252 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Cooling Design Air Flow Rate [m3/s] | 21.90051 |
253 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Main Design Air Flow Rate [m3/s] | 21.90051 |
254 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | User Heating Air Flow Ratio [] | 1.00000 |
255 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Calculated Heating Air Flow Ratio [] | 0.99999 |
256 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.48296 |
257 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.48296 |
258 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.48296 |
259 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.48296 |
260 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.48296 |
261 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.48296 |
262 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
263 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
264 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.60061 |
265 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.60061 |
266 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.60061 |
267 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 4.60061 |
268 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.60061 |
269 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.60061 |
270 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
271 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
272 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.46331 |
273 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.46331 |
274 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.46331 |
275 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.46331 |
276 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.46331 |
277 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.46331 |
278 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
279 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
280 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 9.80894 |
281 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 92.78733 |
282 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 10.58956 |
283 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 5.56805 |
284 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Design Supply Air Flow Rate [m3/s] | 21.90051 |
285 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.48296 |
286 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 4.60061 |
287 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.46331 |
288 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 9.80894 |
289 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 28.81087 |
290 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
291 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.99403 |
292 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.83253E-003 |
293 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
294 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 233283.97957 |
295 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 9.92444E-003 |
296 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 9.80894 |
297 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 22570.86522 |
298 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.97460E-004 |
299 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 394.68947 |
300 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 9.80894 |
301 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 9.92444E-003 |
302 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 4.79816E-005 |
303 | Controller:WaterCoil | VAV_BOT WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.97460E-004 |
304 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 92.78733 |
305 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 29.26856 |
306 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
307 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.99430 |
308 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.91354E-003 |
309 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
310 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 2280072.41273 |
311 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 9.69996E-002 |
312 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 92.78733 |
313 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 171567.88298 |
314 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.50095E-003 |
315 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 3027.84644 |
316 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 92.78733 |
317 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 9.69996E-002 |
318 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 4.90920E-006 |
319 | Controller:WaterCoil | VAV_MID WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.50095E-003 |
320 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 10.58956 |
321 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 28.32196 |
322 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
323 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.00343 |
324 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.77160E-003 |
325 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
326 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 243601.61716 |
327 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.03634E-002 |
328 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 10.58956 |
329 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 13282.33747 |
330 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.16200E-004 |
331 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 237.35583 |
332 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 10.58956 |
333 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.03634E-002 |
334 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 4.59494E-005 |
335 | Controller:WaterCoil | VAV_TOP WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.16200E-004 |
336 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.56805 |
337 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.20016 |
338 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 27.70339 |
339 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
340 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.38302 |
341 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.88349E-003 |
342 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
343 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Coil Load [W] | 123307.64462 |
344 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 5.24579E-003 |
345 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 5.56805 |
346 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Rated Capacity [W] | 253780.15715 |
347 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.22018E-003 |
348 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 5777.80691 |
349 | Fan:ConstantVolume | CAV_BAS FAN | Design Size Maximum Flow Rate [m3/s] | 5.56805 |
350 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.24579E-003 |
351 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 9.07757E-005 |
352 | Controller:WaterCoil | CAV_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.22018E-003 |
353 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 21.90051 |
354 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.33839 |
355 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 21.90051 |
356 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 451109.56477 |
357 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 280919.89260 |
358 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.10476E-002 |
359 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 21.90051 |
360 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 21.90051 |
361 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 21.90051 |
362 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 21.90051 |
363 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 451109.56477 |
364 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 451109.56477 |
365 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 13450.69260 |
366 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
367 | Fan:OnOff | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 21.90051 |
368 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 21.90051 |
369 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Heating Capacity [W] | 451109.56477 |
370 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.10476E-002 |
371 | Coil:Heating:Electric | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 13450.69260 |
372 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Nominal Capacity Volume [m3/s] | 4.78176E-005 |
373 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Nominal Capacity Volume [m3/s] | 3.72000E-005 |
374 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Rated Power [W] | 96450.69782 |
375 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Rated Power [W] | 100000.00000 |
376 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.48296 |
377 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
378 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.48296 |
379 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9672.21752 |
380 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6096.44376 |
381 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.36872E-004 |
382 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.48296 |
383 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.48296 |
384 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.48296 |
385 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.48296 |
386 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9672.21752 |
387 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9672.21752 |
388 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 621.36627 |
389 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
390 | Fan:OnOff | AIRLOOP DATACENTER BOT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.48296 |
391 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.48296 |
392 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Heating Capacity [W] | 9672.21752 |
393 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.36872E-004 |
394 | Coil:Heating:Electric | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 621.36627 |
395 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.60061 |
396 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.15632 |
397 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.60061 |
398 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 92221.07590 |
399 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 58100.26718 |
400 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.25849E-003 |
401 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 4.60061 |
402 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 4.60061 |
403 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 4.60061 |
404 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 4.60061 |
405 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Heating Capacity [W] | 92221.07590 |
406 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 92221.07590 |
407 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 6213.66275 |
408 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
409 | Fan:OnOff | AIRLOOP DATACENTER MID SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 4.60061 |
410 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.60061 |
411 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Heating Capacity [W] | 92221.07590 |
412 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.25849E-003 |
413 | Coil:Heating:Electric | AIRLOOP DATACENTER MID_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 6213.66275 |
414 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.46331 |
415 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
416 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.46331 |
417 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9540.06689 |
418 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 5930.05476 |
419 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.33636E-004 |
420 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.46331 |
421 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.46331 |
422 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.46331 |
423 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.46331 |
424 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9540.06689 |
425 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9540.06689 |
426 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 621.36627 |
427 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
428 | Fan:OnOff | AIRLOOP DATACENTER TOP SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.46331 |
429 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.46331 |
430 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Heating Capacity [W] | 9540.06689 |
431 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.33636E-004 |
432 | Coil:Heating:Electric | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 621.36627 |
433 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 0.12253 |
434 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 25249.54261 |
435 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 0.12253 |
436 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 14.70398 |
437 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 0.12253 |
438 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 0.12253 |
439 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 514333.15251 |
440 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 5.60000 |
441 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 1.19383E-002 |
442 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 1.43260 |
443 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 1.19383E-002 |
444 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 3595.29702 |
445 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
446 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 1364623.04349 |
447 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 1364623.04000 |
448 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 1.19383E-002 |
449 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 0.12253 |
450 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 14.70398 |
451 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 0.12253 |
452 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 17481.11008 |
453 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 0.12253 |
454 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 6.18500E-002 |
455 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1457418.04140 |
456 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1464382.66000 |
457 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Water Flow Rate [m3/s] | 7.24669E-002 |
458 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 0.12253 |
459 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 6.18500E-002 |
460 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 1457418.04140 |
461 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 1464382.66000 |
462 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Water Flow Rate [m3/s] | 7.24669E-002 |
463 | PlantLoop | SINGLE WATER PLANT LOOP | Maximum Loop Flow Rate [m3/s] | 1.37766E-002 |
464 | PlantLoop | SINGLE WATER PLANT LOOP | Plant Loop Volume [m3] | 1.65320 |
465 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Flow Rate [m3/s] | 1.37766E-002 |
466 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Power Consumption [W] | 3513.73214 |
467 | FluidCooler:TwoSpeed | CENTRAL TOWER | Design Water Flow Rate [m3/s] | 1.37766E-002 |
468 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at High Fan Speed [m3/s] | 139666.46671 |
469 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | 57485.42595 |
470 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at Low Fan Speed [m3/s] | 69833.23335 |
471 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fan Power at Low Fan Speed [W] | 7879.72339 |
472 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at Low Fan Speed [W/C] | 21233.17685 |
473 | Boiler:HotWater | CENTRAL BOILER | Design Size Nominal Capacity [W] | 567479.46138 |
474 | Boiler:HotWater | CENTRAL BOILER | User-Specified Nominal Capacity [W] | 556467.27000 |
475 | Boiler:HotWater | CENTRAL BOILER | Design Size Design Water Flow Rate [m3/s] | 1.37766E-002 |
476 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
477 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
478 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
479 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 5.95776 |
480 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
481 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 0.14493 |
482 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 17.39205 |
483 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 0.14493 |
484 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 43650.88847 |
485 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 57.46141 |
486 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 1737449.04667 |
487 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 11.49228 |
488 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 217181.13083 |
489 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 57.46141 |
490 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 1737449.04667 |
491 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 11.49228 |
492 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 217181.13083 |
493 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 7.52700E-002 |
494 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 7.52700E-002 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 18041.04 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 333375.69 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 59191.66 |
4 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 3854.39 |
5 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 3073.53 |
6 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 5616.00 |
7 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 2382.76 |
8 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 115913.30 |
9 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 77212.16 |
10 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 115913.94 |
11 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 66814.59 |
12 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 16741.22 |
13 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 11022.02 |
14 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 16741.38 |
15 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 10222.71 |
16 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | 19567.51 |
17 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | 151298.88 |
18 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | 11984.64 |
19 | Coil:Heating:Water | CAV_BAS HEATING COIL | 206608.38 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | 286360.91 | 187954.71 | 98406.20 | 0.66 | 37797.31 | 383.36 |
2 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | 2734121.12 | 1788934.72 | 945186.40 | 0.65 | 358896.74 | 3640.13 |
3 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | 306011.31 | 201548.59 | 104462.72 | 0.66 | 40588.76 | 411.67 |
4 | Coil:Cooling:Water | CAV_BAS COOLING COIL | 156896.37 | 104134.33 | 52762.05 | 0.66 | 20260.24 | 205.49 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | 6.84 | 23.33 |
2 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | 6.84 | 23.33 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.743 | 1.382 | 105.88 | 200.61 | 105.88 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_NORTH_0.25 | N/A | 2.869 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_NORTH_0.25 | N/A | 2.869 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_NORTH_0.25 | N/A | 2.869 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_NORTH_0.25 | N/A | 2.869 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_NORTH_0.25 | N/A | 2.869 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.743 | 1.382 | 71.89 | 133.74 | 71.89 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_EAST_0.25 | N/A | 2.869 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_EAST_0.25 | N/A | 2.869 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_EAST_0.25 | N/A | 2.869 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.743 | 1.382 | 105.88 | 200.61 | 105.88 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | N/A | 2.869 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | N/A | 2.869 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | N/A | 2.869 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | N/A | 2.869 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | N/A | 2.869 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.743 | 1.382 | 71.89 | 133.74 | 71.89 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_WEST_0.25 | N/A | 2.869 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_WEST_0.25 | N/A | 2.869 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_WEST_0.25 | N/A | 2.869 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.656 | 1.327 | 113.68 | 200.61 | 113.68 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_NORTH_0.25 | N/A | 2.869 | No | 86.92 | 86.92 | 86.92 | 0.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.656 | 1.327 | 75.79 | 133.74 | 75.79 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_EAST_0.25 | N/A | 2.869 | No | 57.95 | 57.95 | 57.95 | 90.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.656 | 1.327 | 113.68 | 200.61 | 113.68 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | N/A | 2.869 | No | 86.92 | 86.92 | 86.92 | 180.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.656 | 1.327 | 75.79 | 133.74 | 75.79 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_WEST_0.25 | N/A | 2.869 | No | 57.95 | 57.95 | 57.95 | 270.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 2.135 | 1.618 | 113.68 | 200.61 | 113.68 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_NORTH_0.25 | N/A | 2.869 | No | 86.92 | 86.92 | 86.92 | 0.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 2.135 | 1.618 | 75.79 | 133.74 | 75.79 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_EAST_0.25 | N/A | 2.869 | No | 57.95 | 57.95 | 57.95 | 90.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 2.135 | 1.618 | 113.68 | 200.61 | 113.68 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | N/A | 2.869 | No | 86.92 | 86.92 | 86.92 | 180.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 2.135 | 1.618 | 75.79 | 133.74 | 75.79 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_WEST_0.25 | N/A | 2.869 | No | 57.95 | 57.95 | 57.95 | 270.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.743 | 1.382 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.743 | 1.382 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.743 | 1.382 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.743 | 1.382 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.656 | 1.327 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.656 | 1.327 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.656 | 1.327 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.656 | 1.327 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 2.135 | 1.618 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 2.135 | 1.618 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 2.135 | 1.618 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 2.135 | 1.618 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 0.4179534797 | 0.1445237306 | Pass | Pass | 0.5008472136 | 0.5178642309 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 2.7446870709E-003 | 2.0120071568E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 2.7342699512E-003 | 2.0212730289E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 2.1180242897E-002 | 1.2650471983E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 2.1500402697E-002 | 1.5074042896E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 2.9237037027E-002 | 3.3273024400E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 5.0217232847E-002 | 3.8130257264E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 3.4792914852E-002 | 3.0897086410E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 2.3029508803E-002 | 1.5121523883E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 3.1558747997E-002 | 3.1684784284E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 5.6812544635E-002 | 4.0990599032E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 3.7265566514E-002 | 3.1595908015E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 3.5490799815E-002 | 2.1293420539E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 4.3241650306E-002 | 2.8593610416E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 6.8159748067E-002 | 4.4137563676E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 5.0607760608E-002 | 3.6493446292E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 3.8024927934E-003 | 3.0692091663E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 3.9408484231E-003 | 3.3329043996E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 6.3676620974E-002 | 4.8015434543E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 4.7575454740E-005 | 7.2306833616E-005 | Pass | Pass | 2.3826871028E-003 | 1.4102690012E-003 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 3.2030136358E-005 | 4.7417908433E-005 | Pass | Pass | 8.2655504681E-003 | 4.2404389886E-003 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 3.6167558266E-002 | 1.8060830871E-002 | Pass | Pass | 1.1174275852E-002 | 8.7583286461E-003 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 2.1093864744E-004 | 2.0347591614E-004 | Pass | Pass | 6.3483675957E-005 | 1.0377116494E-004 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:27
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 4683.87 | -42.2 | 0.00 | -5171.6 | 40559.66 | 40029.74 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:27
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 6.30 | 0.00 | 6.30 | Wetbulb [C] | 0.50 | 270.00 |
NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 42.00 | 9.70 | 22.20 | Wetbulb [C] | 3.20 | 320.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.60 | 4 | |||
Feb | 21.40 | 43 | |||
Mar | 12.00 | 35 | |||
Apr | 29.10 | 12 | |||
May | 29.10 | 57 | |||
Jun | 197.10 | 59 | |||
Jul | 47.90 | 83 | |||
Aug | 0.00 | 0 | |||
Sep | 171.60 | 106 | |||
Oct | 4.80 | 31 | |||
Nov | 1.20 | 7 | |||
Dec | 33.00 | 13 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:27
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.845 | 0.940 | 118.87 | 118.87 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 139.09 | 139.09 | 180.00 | 90.00 | S |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 139.09 | 139.09 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.382 | 1.743 | 200.61 | 105.88 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.382 | 1.743 | 133.74 | 71.89 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.382 | 1.743 | 200.61 | 105.88 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.382 | 1.743 | 133.74 | 71.89 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.327 | 1.656 | 2006.06 | 1136.85 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 1.327 | 1.656 | 1337.37 | 757.90 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.327 | 1.656 | 2006.06 | 1136.85 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 1.327 | 1.656 | 1337.37 | 757.90 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.618 | 2.135 | 200.61 | 113.68 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.618 | 2.135 | 133.74 | 75.79 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.618 | 2.135 | 200.61 | 113.68 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.618 | 2.135 | 133.74 | 75.79 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.382 | 1.743 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.382 | 1.743 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.382 | 1.743 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.382 | 1.743 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.327 | 1.656 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 1.327 | 1.656 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.327 | 1.656 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 1.327 | 1.656 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.618 | 2.135 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.618 | 2.135 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.618 | 2.135 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.618 | 2.135 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 39.22 | 39.22 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 39.22 | 39.22 | 180.00 | 90.00 | S |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.845 | 0.940 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 270.00 | 90.00 | W |
BASEMENT_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 2779.43 | 2779.43 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 2076.77 | 2076.77 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 419.30 | 419.30 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 2076.82 | 2076.82 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 0.00 | 180.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.35 | 250.35 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 225.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 135.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.41 | 313.41 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
INT-PER3S-NE-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
INT-PER3S-NE | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.42 | 313.42 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
GROUNDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
iz-DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 0.00 | 180.00 | |
MIDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 35631.06 | 35631.06 | 180.00 | 0.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_BOT_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_BOT_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_MID_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
DATACENTER_MID_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
DATACENTER_MID_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 362.03 | 362.03 | 0.00 | 180.00 | |
DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 180.00 | 0.00 | |
DATACENTER_TOP_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_TOP_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_TOP_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 783.68 | 783.68 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 419.35 | 419.35 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 135.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.08 | 63.08 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 180.00 | 0.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 7126.21 | 0.00 | 90.00 | N | ||
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 50646.53 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.26 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.50 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.35 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.48 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.5047_SHGC_NORTH_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.5047_SHGC_NORTH_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.5047_SHGC_NORTH_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.5047_SHGC_NORTH_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.5047_SHGC_NORTH_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.5047_SHGC_EAST_0.25 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.5047_SHGC_EAST_0.25 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.5047_SHGC_EAST_0.25 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.5047_SHGC_WEST_0.25 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.5047_SHGC_WEST_0.25 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.5047_SHGC_WEST_0.25 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.5047_SHGC_NORTH_0.25 | 86.92 | 0.00 | 0.00 | 86.92 | 869.21 | 2.869 | 0.251 | 0.251 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.5047_SHGC_EAST_0.25 | 57.95 | 0.00 | 0.00 | 57.95 | 579.48 | 2.869 | 0.251 | 0.251 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | 86.92 | 0.00 | 0.00 | 86.92 | 869.21 | 2.869 | 0.251 | 0.251 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.5047_SHGC_WEST_0.25 | 57.95 | 0.00 | 0.00 | 57.95 | 579.48 | 2.869 | 0.251 | 0.251 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.5047_SHGC_NORTH_0.25 | 86.92 | 0.00 | 0.00 | 86.92 | 86.92 | 2.869 | 0.251 | 0.251 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.5047_SHGC_EAST_0.25 | 57.95 | 0.00 | 0.00 | 57.95 | 57.95 | 2.869 | 0.251 | 0.251 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | 86.92 | 0.00 | 0.00 | 86.92 | 86.92 | 2.869 | 0.251 | 0.251 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.5047_SHGC_WEST_0.25 | 57.95 | 0.00 | 0.00 | 57.95 | 57.95 | 2.869 | 0.251 | 0.251 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 3476.85 | 2.869 | 0.251 | 0.251 | |||||||||||||||||
North Total or Average | 1043.06 | 2.869 | 0.251 | 0.251 | |||||||||||||||||
Non-North Total or Average | 2433.80 | 2.869 | 0.251 | 0.251 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:27
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:27
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 7.6202 | 2779.43 | 21179.74 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 44.71 | 0.0000 | Y | 177.74 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 7.6202 | 2496.12 | 19020.89 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 44.71 | 0.0000 | Y | 159.62 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 7.6202 | 24961.20 | 190208.95 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 44.71 | 0.0000 | Y | 1596.24 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 7.6202 | 2496.12 | 19020.89 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 44.71 | 0.0000 | Y | 159.62 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 7.6202 | 313.41 | 2388.26 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 30.73 | 0.0000 | Y | 13.78 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 7.6202 | 201.98 | 1539.09 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 30.70 | 0.0000 | Y | 8.87 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 7.6202 | 313.42 | 2388.32 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 30.55 | 0.0000 | Y | 13.70 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 7.6202 | 201.98 | 1539.09 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 30.68 | 0.0000 | Y | 8.86 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 7.6202 | 3134.13 | 23882.63 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 30.76 | 0.0000 | Y | 137.90 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 7.6202 | 2019.75 | 15390.88 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 30.71 | 0.0000 | Y | 88.73 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 7.6202 | 3134.20 | 23883.15 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 30.57 | 0.0000 | Y | 137.06 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 7.6202 | 2019.75 | 15390.88 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 30.69 | 0.0000 | Y | 88.66 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 7.6202 | 313.41 | 2388.26 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 30.76 | 0.0000 | Y | 13.79 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 7.6202 | 201.98 | 1539.09 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 30.71 | 0.0000 | Y | 8.87 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 7.6202 | 313.42 | 2388.32 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 30.57 | 0.0000 | Y | 13.71 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 7.6202 | 201.98 | 1539.09 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 30.69 | 0.0000 | Y | 8.87 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GENERAL | 7.6202 | 783.68 | 5971.78 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 44.71 | 0.0000 | Y | 50.12 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | DATACENTER_BOT_ZN_6 | GENERAL | 12.5114 | 36.20 | 452.95 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 4.64 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | DATACENTER_MID_ZN_6 | GENERAL | 12.5114 | 362.03 | 4529.48 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 46.40 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | DATACENTER_TOP_ZN_6 | GENERAL | 12.5114 | 36.20 | 452.95 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 4.64 |
Interior Lighting Total | 7.6661 | 46320.38 | 355094.67 | 856.32 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2388.32 | 921.17 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 2388.32 | 0.00 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1539.09 | 593.63 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1539.09 | 0.00 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2388.26 | 921.15 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 2388.26 | 0.00 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1539.09 | 593.63 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1539.09 | 0.00 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2388.32 | 921.17 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 2388.32 | 0.00 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1539.09 | 593.63 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1539.09 | 0.00 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2388.26 | 921.15 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 2388.26 | 0.00 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1539.09 | 593.63 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1539.09 | 0.00 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2388.32 | 921.17 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 2388.32 | 0.00 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1539.09 | 593.63 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1539.09 | 0.00 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2388.26 | 921.15 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 2388.26 | 0.00 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1539.09 | 593.63 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1539.09 | 0.00 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 9973.05 | AstronomicalClock | - | 41.75 | 41.75 | 78.17 | |
EXTERIOR_LIGHTS_B | 27638.03 | AstronomicalClock | - | 83.75 | 71.15 | 369.15 | |
Exterior Lighting Total | 37611.08 | 447.32 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:27
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 2873641.89 | |||||
HEATSYS1 BOILER | Boiler:HotWater | 1364623.04 | 0.81 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:ReformulatedEIR | 1464382.66 | 6.28 | 1401597.32 | 5.98 | 6.84 | 23.33 |
COOLSYS1 CHILLER2 | Chiller:Electric:ReformulatedEIR | 1464382.66 | 6.28 | 1401597.32 | 5.98 | 6.84 | 23.33 |
CENTRAL TOWER | FluidCooler:TwoSpeed | 582060.00 | |||||
CENTRAL BOILER | Boiler:HotWater | 556467.27 | 0.80 | ||||
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 1737449.05 | |||||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 1737449.05 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | 233283.98 | 286360.91 | 187954.71 | 98406.20 | 0.66 | - | 37797.31 | 383.36 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | 2280072.41 | 2734121.12 | 1788934.72 | 945186.40 | 0.65 | - | 358896.74 | 3640.13 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | 243601.62 | 306011.31 | 201548.59 | 104462.72 | 0.66 | - | 40588.76 | 411.67 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | 123307.64 | 156896.37 | 104134.33 | 52762.05 | 0.66 | - | 20260.24 | 205.49 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 451109.56 | 280919.89 | 170189.67 | 0.62 | 0.00 | |||
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9672.22 | 6096.44 | 3575.77 | 0.63 | 0.00 | |||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 92221.08 | 58100.27 | 34120.81 | 0.63 | 0.00 | |||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9540.07 | 5930.05 | 3610.01 | 0.62 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 19026.36 | 18041.04 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 351752.39 | 333375.69 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 62504.34 | 59191.66 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 4066.49 | 3854.39 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 3242.83 | 3073.53 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 5927.70 | 5616.00 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 2512.97 | 2382.76 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 122321.44 | 115913.30 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 81481.53 | 77212.16 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 122322.11 | 115913.94 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 70505.88 | 66814.59 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 17668.25 | 16741.22 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 11632.41 | 11022.02 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 17668.43 | 16741.38 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 10788.67 | 10222.71 | - |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | 22570.87 | 19567.51 | - |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | 171567.88 | 151298.88 | - |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | 13282.34 | 11984.64 | - |
CAV_BAS HEATING COIL | Coil:Heating:Water | 253780.16 | 206608.38 | - |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 451109.56 | 0.00 | |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9672.22 | 0.00 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 92221.08 | 0.00 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9540.07 | 0.00 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | 13450.69 | 1.00 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | 621.37 | 1.00 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | 6213.66 | 1.00 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | 621.37 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 9.81 | 21196.60 | 2160.95 | 1.00 | 1.12 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 92.79 | 200508.47 | 2160.95 | 1.00 | 1.08 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 10.59 | 22761.89 | 2149.46 | 1.00 | 1.12 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:30:00 |
CAV_BAS FAN | Fan:ConstantVolume | 0.60 | 1018.41 | 5.57 | 9441.50 | 1695.65 | 1.00 | 1.16 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 0.62 | 1018.41 | 21.90 | 36119.35 | 1649.25 | 1.00 | 1.14 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 07:10:00 |
AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.48 | 540.96 | 1120.11 | 1.00 | 1.62 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 4.60 | 5153.18 | 1120.11 | 1.00 | 1.16 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.46 | 518.96 | 1120.11 | 1.00 | 1.64 | General | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 133527.72 | 0.122533 | 25249.54 | 206062.94 | 0.90 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.011938 | 3595.30 | 301156.09 | 0.90 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 92445.74 | 0.122533 | 17481.11 | 142664.32 | 0.90 | General |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.013777 | 3513.73 | 255050.01 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 3168.45 | 0.000440 | 5.96 | 13540.37 | 0.30 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 180718.98 | 0.144934 | 43650.89 | 301178.23 | 0.90 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.50 | 0.08 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:27
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 75181.82 | 75181.82 | 27.05 | 5.568 | 5.568 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 24.00 | 24.00 | 0.00746 | 34.82 | 0.00915 | 1.200 | 0.00 |
CORE_BOTTOM | 80291.26 | 80291.26 | 32.17 | 5.946 | 5.946 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 24.00 | 24.00 | 0.00739 | 34.82 | 0.00915 | 1.078 | 0.00 |
CORE_MID | 760763.87 | 760763.87 | 304.78 | 56.330 | 56.330 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 24.00 | 24.00 | 0.00741 | 34.82 | 0.00915 | 10.778 | 0.00 |
CORE_TOP | 78353.55 | 78353.55 | 31.39 | 5.856 | 5.856 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:50:00 | 24.00 | 24.00 | 0.00739 | 42.00 | 0.00916 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 15711.61 | 15711.61 | 50.13 | 1.174 | 1.174 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:20:00 | 24.00 | 24.00 | 0.00727 | 41.81 | 0.00916 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 12311.35 | 12311.35 | 60.95 | 0.920 | 0.920 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 10:10:00 | 24.00 | 24.00 | 0.00722 | 38.56 | 0.00915 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 15994.18 | 15994.18 | 51.03 | 1.195 | 1.195 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | 24.00 | 24.00 | 0.00727 | 42.00 | 0.00916 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 16136.29 | 16136.29 | 79.89 | 1.206 | 1.206 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:20:00 | 24.00 | 24.00 | 0.00717 | 41.16 | 0.00916 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 152555.09 | 152555.09 | 486.75 | 11.402 | 11.402 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:30:00 | 24.00 | 24.00 | 0.00732 | 41.71 | 0.00916 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 127483.44 | 127483.44 | 631.18 | 9.528 | 9.528 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 10:20:00 | 24.00 | 24.00 | 0.00725 | 38.80 | 0.00915 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 153924.08 | 153924.08 | 491.11 | 11.505 | 11.505 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:10:00 | 24.00 | 24.00 | 0.00731 | 42.00 | 0.00916 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 136545.98 | 136545.98 | 676.05 | 10.206 | 10.206 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:30:00 | 24.00 | 24.00 | 0.00723 | 41.03 | 0.00916 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 17951.06 | 17951.06 | 57.28 | 1.342 | 1.342 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:40:00 | 24.00 | 24.00 | 0.00728 | 41.61 | 0.00916 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 13660.96 | 13660.96 | 67.64 | 1.021 | 1.021 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 10:40:00 | 24.00 | 24.00 | 0.00724 | 39.28 | 0.00915 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 17986.16 | 17986.16 | 57.39 | 1.344 | 1.344 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:40:00 | 24.00 | 24.00 | 0.00728 | 42.00 | 0.00916 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 15436.93 | 15436.93 | 76.43 | 1.154 | 1.154 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:20:00 | 24.00 | 24.00 | 0.00722 | 41.16 | 0.00916 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 8193.50 | 8193.50 | 226.32 | 0.483 | 0.483 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:20:00 | 27.00 | 27.00 | 0.00700 | 32.36 | 0.00914 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 78050.85 | 78050.85 | 2155.94 | 4.601 | 4.601 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:20:00 | 27.00 | 27.00 | 0.00700 | 32.36 | 0.00914 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 7859.30 | 7859.30 | 217.09 | 0.463 | 0.463 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:40:00 | 27.00 | 27.00 | 0.00709 | 40.90 | 0.00916 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 371509.01 | 371509.01 | 474.06 | 21.900 | 21.900 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 07:00:00 | 27.00 | 27.00 | 0.00704 | 33.17 | 0.00914 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | 00:10:00 | 15.60 | 25.81 | 0.00607 | 6.30 | 0.00607 | 1.200 | 0.00 | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.000 | 1.078 | 00:10:00 | 15.60 | 23.39 | 0.00607 | 6.30 | 0.00607 | 1.078 | 0.00 | |
CORE_MID | 164331.49 | 164331.49 | 65.83 | 7.043 | 10.778 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 6.30 | 0.00607 | 10.778 | 0.00 |
CORE_TOP | 43077.00 | 43077.00 | 17.26 | 1.872 | 1.872 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 6.30 | 0.00607 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 1670.33 | 1670.33 | 5.33 | 0.073 | 0.135 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00775 | 6.30 | 0.00607 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 1437.37 | 1437.37 | 7.12 | 0.062 | 0.087 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00778 | 6.30 | 0.00607 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 3534.95 | 3534.95 | 11.28 | 0.153 | 0.153 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00785 | 6.30 | 0.00607 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 149.21 | 149.21 | 0.74 | 0.007 | 0.087 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00717 | 6.30 | 0.00607 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 85655.62 | 85655.62 | 273.30 | 3.737 | 3.737 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00790 | 6.30 | 0.00607 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 57054.55 | 57054.55 | 282.48 | 2.489 | 2.489 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00790 | 6.30 | 0.00607 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 85656.09 | 85656.09 | 273.30 | 3.737 | 3.737 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00790 | 6.30 | 0.00607 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 49381.77 | 49381.77 | 244.49 | 2.153 | 2.153 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00787 | 6.30 | 0.00607 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 12366.35 | 12366.35 | 39.46 | 0.540 | 0.540 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00795 | 6.30 | 0.00607 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 8141.55 | 8141.55 | 40.31 | 0.356 | 0.356 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00795 | 6.30 | 0.00607 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 12366.48 | 12366.48 | 39.46 | 0.540 | 0.540 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00795 | 6.30 | 0.00607 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 7551.70 | 7551.70 | 37.39 | 0.330 | 0.330 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00794 | 6.30 | 0.00607 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | 00:10:00 | 18.00 | 27.00 | 0.00700 | 6.30 | 0.00607 | 0.016 | 0.00 | |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | 00:10:00 | 18.00 | 25.16 | 0.00698 | 6.30 | 0.00607 | 0.156 | 0.00 | |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | 00:10:00 | 18.00 | 24.11 | 0.00620 | 6.30 | 0.00607 | 0.016 | 0.00 | |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | 00:10:00 | 18.00 | 27.00 | 0.00700 | 6.30 | 0.00607 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV_BOT WITH REHEAT | 9.81 | 9.81 | 1.54 | 1.54 | 9.8089 | 2.8519 | 9.8089 | 0.2907 | 0.3000 |
VAV_MID WITH REHEAT | 92.79 | 92.79 | 22.89 | 22.89 | 92.7873 | 27.8415 | 92.7873 | 0.3001 | 0.3000 |
VAV_TOP WITH REHEAT | 10.59 | 10.59 | 3.64 | 3.64 | 10.5896 | 3.6385 | 10.5896 | 0.3436 | 0.3000 |
CAV_BAS | 5.57 | 5.57 | 1.20 | 1.20 | 5.5681 | 5.5681 | 5.5681 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.90 | 21.90 | 0.34 | 0.34 | 21.9005 | 21.9002 | 21.9005 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.48 | 0.48 | 0.02 | 0.02 | 0.4830 | 0.4830 | 0.4830 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 4.60 | 4.60 | 0.16 | 0.16 | 4.6006 | 4.6006 | 4.6006 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.46 | 0.46 | 0.02 | 0.02 | 0.4633 | 0.4633 | 0.4633 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 19026.362 | 19026.362 | 1.938545 | 0.00016645 | 383.557 | 1/21 00:10:00 | 1/21 00:10:00 | 19026.36 | 19026.36 | 1.938545 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00800000 | 50.4125 | 0.00 | 0.00 | 19096.52 | 19096.52 | ||
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 351752.387 | 351752.387 | 19.095809 | 0.00307728 | 7765.614 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 351752.39 | 351752.39 | 19.095809 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00800000 | 50.4125 | 164331.49 | 0.00 | 352965.50 | 352965.50 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 62504.337 | 62504.337 | 1.979399 | 0.00054682 | 1623.563 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 62504.34 | 62504.34 | 1.979399 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00800000 | 50.4125 | 43077.00 | 0.00 | 62695.71 | 62695.71 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 4066.492 | 4066.492 | 0.244253 | 0.00003558 | 88.034 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4066.49 | 4066.49 | 0.244253 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00775217 | 48.8704 | 1670.33 | 0.00 | 4080.67 | 4080.67 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 3242.828 | 3242.828 | 0.184031 | 0.00002837 | 70.958 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 3242.83 | 3242.83 | 0.184031 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00777922 | 49.0390 | 1437.37 | 0.00 | 3254.06 | 3254.06 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 5927.700 | 5927.700 | 0.243864 | 0.00005186 | 140.168 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 5927.70 | 5927.70 | 0.243864 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00784759 | 49.4646 | 3534.95 | 0.00 | 5947.06 | 5947.06 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 2512.967 | 2512.967 | 0.241205 | 0.00002198 | 50.967 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 2512.97 | 2512.97 | 0.241205 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00716599 | 45.2170 | 149.21 | 0.00 | 2522.20 | 2522.20 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 122321.443 | 122321.443 | 3.736591 | 0.00107012 | 3228.465 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 122321.44 | 122321.44 | 3.736591 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00790031 | 49.7931 | 85655.62 | 0.00 | 122740.94 | 122740.94 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 81481.535 | 81481.535 | 2.489322 | 0.00071284 | 2150.455 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 81481.53 | 81481.53 | 2.489322 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00790358 | 49.8134 | 57054.55 | 0.00 | 81760.17 | 81760.17 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 122322.114 | 122322.114 | 3.736611 | 0.00107013 | 3228.483 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 122322.11 | 122322.11 | 3.736611 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00790031 | 49.7931 | 85656.09 | 0.00 | 122741.61 | 122741.61 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 70505.877 | 70505.877 | 2.152877 | 0.00061682 | 1861.234 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 70505.88 | 70505.88 | 2.152877 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00786997 | 49.6044 | 49381.77 | 0.00 | 70750.20 | 70750.20 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 17668.253 | 17668.253 | 0.540259 | 0.00015457 | 466.109 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 17668.25 | 17668.25 | 0.540259 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00794874 | 50.0942 | 12366.35 | 0.00 | 17727.30 | 17727.30 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 11632.412 | 11632.412 | 0.355715 | 0.00010177 | 306.869 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 11632.41 | 11632.41 | 0.355715 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00794965 | 50.0999 | 8141.55 | 0.00 | 11671.23 | 11671.23 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 17668.425 | 17668.425 | 0.540265 | 0.00015457 | 466.114 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 17668.43 | 17668.43 | 0.540265 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00794874 | 50.0942 | 12366.48 | 0.00 | 17727.48 | 17727.48 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 10788.668 | 10788.668 | 0.329853 | 0.00009438 | 284.634 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 10788.67 | 10788.67 | 0.329853 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 0.0000 | 21.00 | 0.00793757 | 50.0248 | 7551.70 | 0.00 | 10824.85 | 10824.85 |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 233283.980 | -999.000 | 9.808941 | 0.00992444 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 233283.98 | 211663.82 | 9.808941 | 28.81 | 17.23 | 0.00783253 | 10.99 | 9.55 | 0.00700000 | 42.00 | 0.00915790 | 22.26 | 25.8763 | 24.00 | 0.00734896 | 38.6354 | 127037.73 | 0.00 | 237639.92 | 223761.68 |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 22570.865 | 22570.865 | 2.942682 | 0.00019746 | 394.689 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 22570.87 | 22570.87 | 2.942682 | 6.30 | 6.30 | 0.00613865 | 12.80 | 11.37 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 86.2543 | 22.54 | 0.00665833 | 38.2686 | 6791.85 | 0.00 | 23690.11 | 23690.11 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 2280072.413 | -999.000 | 92.787326 | 0.09699955 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 2280072.41 | 2054737.19 | 92.787326 | 29.27 | 17.45 | 0.00791354 | 10.99 | 9.55 | 0.00700000 | 42.00 | 0.00915790 | 22.26 | 27.3550 | 24.00 | 0.00739846 | 38.8928 | 1160020.42 | 0.00 | 2321039.26 | 2167672.23 |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 171567.883 | 171567.883 | 27.836198 | 0.00150095 | 3027.846 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 171567.88 | 171567.88 | 27.836198 | 7.57 | 7.11 | 0.00623743 | 12.80 | 11.37 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 91.1833 | 21.00 | 0.00793397 | 50.0022 | 442079.52 | 0.00 | 183176.43 | 183176.43 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 243601.617 | -999.000 | 10.589565 | 0.01036338 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:30:00 | 243601.62 | 222071.32 | 10.589565 | 28.32 | 17.01 | 0.00777160 | 11.00 | 9.55 | 0.00700000 | 42.00 | 0.00915790 | 22.26 | 23.9688 | 24.00 | 0.00733343 | 38.5549 | 141400.81 | 0.00 | 248248.49 | 235266.64 |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 13282.337 | 13282.337 | 3.176869 | 0.00011620 | 237.356 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 13282.34 | 13282.34 | 3.176869 | 9.26 | 8.16 | 0.00645544 | 12.80 | 11.37 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 79.8959 | 21.00 | 0.00797793 | 50.2754 | 57545.58 | 0.00 | 14509.80 | 14509.80 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 123307.645 | -999.000 | 5.568055 | 0.00524579 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 11:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | 123307.64 | 110638.64 | 5.568055 | 27.70 | 16.89 | 0.00788349 | 11.38 | 9.72 | 0.00700000 | 39.77 | 0.00915417 | 21.63 | 21.5543 | 24.00 | 0.00749333 | 39.3855 | 68353.97 | 0.00 | 125668.08 | 118261.45 |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | CAV_BAS | 253780.157 | 253780.157 | 5.568055 | 0.00222018 | 5777.807 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 253780.16 | 253780.16 | 5.568055 | 1.36 | 1.36 | 0.00607234 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 21.5543 | 25.81 | 0.00607234 | 28.7199 | 0.00 | 0.00 | 218646.00 | 218646.00 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 451109.565 | 280919.893 | 21.900509 | 0.01104764 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 07:10:00 | 405188.86 | 401471.72 | -999.0 | 28.66 | 16.55 | 0.00707492 | 12.80 | 10.34 | 0.00700000 | 42.00 | 0.00915790 | 22.26 | -999.0000 | 27.00 | 0.00704219 | 30.9981 | 371036.55 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9672.218 | 6096.444 | 0.482956 | 0.00023687 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:20:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:20:00 | 8642.49 | 8567.20 | -999.0 | 28.14 | 16.36 | 0.00706933 | 12.80 | 10.34 | 0.00700000 | 32.36 | 0.00914193 | 19.41 | -999.0000 | 27.00 | 0.00700000 | 30.8097 | 8144.83 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 92221.076 | 58100.267 | 4.600613 | 0.00225849 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:20:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:20:00 | 82416.93 | 81663.87 | -999.0 | 28.15 | 16.37 | 0.00707278 | 12.80 | 10.34 | 0.00700000 | 32.36 | 0.00914193 | 19.41 | -999.0000 | 27.00 | 0.00700000 | 30.8097 | 77687.88 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9540.067 | 5930.055 | 0.463312 | 0.00023364 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:40:00 | 8569.33 | 8399.76 | -999.0 | 28.45 | 16.55 | 0.00716170 | 12.80 | 10.34 | 0.00700000 | 41.29 | 0.00915671 | 22.06 | -999.0000 | 27.00 | 0.00709201 | 31.2132 | 7855.92 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 451109.565 | 451109.565 | 21.900509 | 0.01104764 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 451109.56 | 451109.56 | 21.900509 | 6.30 | 6.30 | 0.00607234 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 1.5451 | 27.00 | 0.00700000 | 30.8097 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9672.218 | 9672.218 | 0.482956 | 0.00023687 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9672.22 | 9672.22 | 0.482956 | 6.30 | 6.30 | 0.00607234 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 3.2368 | 27.00 | 0.00700000 | 30.8097 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 92221.076 | 92221.076 | 4.600613 | 0.00225849 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 92221.08 | 92221.08 | 4.600613 | 6.30 | 6.30 | 0.00607234 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 3.3979 | 25.16 | 0.00698209 | 34.2539 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9540.067 | 9540.067 | 0.463312 | 0.00023364 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9540.07 | 9540.07 | 0.463312 | 6.30 | 6.30 | 0.00607234 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 3.3740 | 24.11 | 0.00620124 | 32.4414 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 13450.693 | 13450.693 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 13450.69 | 13450.69 | 21.900509 | 0.10 | 0.10 | 0.00698567 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 1.5451 | 27.00 | 0.00700000 | 30.8097 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BOT | 621.366 | 621.366 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 621.37 | 621.37 | 0.482956 | 0.20 | 0.20 | 0.00696997 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 3.2368 | 27.00 | 0.00700000 | 30.8097 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER MID | 6213.663 | 6213.663 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 6213.66 | 6213.66 | 4.600613 | 0.21 | 0.21 | 0.00695118 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 3.3979 | 25.16 | 0.00698209 | 34.2539 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER TOP | 621.366 | 621.366 | -999.0 | -999.0 | -999.000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 621.37 | 621.37 | 0.463312 | 0.21 | 0.21 | 0.00619689 | 40.00 | 20.89 | 0.00800000 | 6.30 | 0.00607234 | 6.30 | 3.3740 | 24.11 | 0.00620124 | 32.4414 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 09:04:27
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 19026.362 | 19026.362 | 1.938545 | 0.00016645 | 383.557 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 11.93709985 | 54.44 | 82.22 | 27.78 | 1392086.62 | 1.3668 | 1.394258 | 1/21 00:10:00 | unknown | unknown | 1/21 00:10:00 | Sensible | 19026.36 | 19026.36 | 1.0000 | 2.27543554 | 1.938545 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.16643393 | 60.00 | 32.22 | 27.78 | 0.000 | 19026.36 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 50.4125 | 0.00 | 0.00 | 19096.52 | 19096.52 | 2.27543554 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 21.03 | 14.86 | 0.00800000 | 41452.3 | |||
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 351752.387 | 351752.387 | 19.095809 | 0.00307728 | 7765.614 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 11.93709985 | 54.44 | 82.22 | 27.78 | 1392086.62 | 25.2680 | 25.776524 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 351752.39 | 351752.39 | 1.0000 | 22.41438330 | 19.095809 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 3.07696942 | 60.00 | 32.22 | 27.78 | 0.000 | 351752.39 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.58 | 0.00800000 | 21.00 | 0.00800000 | 50.4125 | 164331.49 | 0.00 | 352965.50 | 352965.50 | 22.41438330 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 28.24 | 17.44 | 0.00800000 | 48807.1 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 62504.337 | 62504.337 | 1.979399 | 0.00054682 | 1623.563 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 11.93709985 | 54.44 | 82.22 | 27.78 | 1392086.62 | 4.4900 | 4.580337 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 62504.34 | 62504.34 | 1.0000 | 2.32339001 | 1.979399 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.54675943 | 60.00 | 32.22 | 27.78 | 0.000 | 62504.34 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.86 | 0.00800000 | 21.00 | 0.00800000 | 50.4125 | 43077.00 | 0.00 | 62695.71 | 62695.71 | 2.32339001 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 39.26 | 20.96 | 0.00800000 | 60044.4 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4066.492 | 4066.492 | 0.244253 | 0.00003558 | 88.034 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 11.93709985 | 54.44 | 82.22 | 27.78 | 1392086.62 | 0.2921 | 0.297994 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 4066.49 | 4066.49 | 1.0000 | 0.28670089 | 0.244253 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.03557182 | 60.00 | 32.22 | 27.78 | 0.000 | 4066.49 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.91 | 0.00775217 | 21.00 | 0.00775217 | 48.8704 | 1670.33 | 0.00 | 4080.67 | 4080.67 | 0.28670089 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 26.76 | 16.93 | 0.00800000 | 47293.0 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3242.828 | 3242.828 | 0.184031 | 0.00002837 | 70.958 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 11.93709985 | 54.44 | 82.22 | 27.78 | 1392086.62 | 0.2329 | 0.237635 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 3242.83 | 3242.83 | 1.0000 | 0.21601293 | 0.184031 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.02836678 | 60.00 | 32.22 | 27.78 | 0.000 | 3242.83 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.87 | 0.00777922 | 21.00 | 0.00777922 | 49.0390 | 1437.37 | 0.00 | 3254.06 | 3254.06 | 0.21601293 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 27.57 | 17.21 | 0.00800000 | 48124.0 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5927.700 | 5927.700 | 0.243864 | 0.00005186 | 140.168 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 11.93709985 | 54.44 | 82.22 | 27.78 | 1392086.62 | 0.4258 | 0.434384 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 5927.70 | 5927.70 | 1.0000 | 0.28624446 | 0.243864 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.05185281 | 60.00 | 32.22 | 27.78 | 0.000 | 5927.70 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.87 | 0.00784759 | 21.00 | 0.00784759 | 49.4646 | 3534.95 | 0.00 | 5947.06 | 5947.06 | 0.28624446 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 33.17 | 19.08 | 0.00800000 | 53836.0 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2512.967 | 2512.967 | 0.241205 | 0.00002198 | 50.967 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 11.93709985 | 54.44 | 82.22 | 27.78 | 1392086.62 | 0.1805 | 0.184151 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 2512.97 | 2512.97 | 1.0000 | 0.28312332 | 0.241205 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.02198229 | 60.00 | 32.22 | 27.78 | 0.000 | 2512.97 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.99 | 0.00716599 | 21.00 | 0.00716599 | 45.2170 | 149.21 | 0.00 | 2522.20 | 2522.20 | 0.28312332 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 21.54 | 15.05 | 0.00800000 | 41968.3 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 122321.443 | 122321.443 | 3.736591 | 0.00107012 | 3228.465 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 11.93709985 | 54.44 | 82.22 | 27.78 | 1392086.62 | 8.7869 | 8.963753 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 122321.44 | 122321.44 | 1.0000 | 4.38595607 | 3.736591 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 1.07001218 | 60.00 | 32.22 | 27.78 | 0.000 | 122321.44 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.91 | 0.00790031 | 21.00 | 0.00790031 | 49.7931 | 85655.62 | 0.00 | 122740.94 | 122740.94 | 4.38595607 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.24 | 21.25 | 0.00800000 | 61044.8 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 81481.535 | 81481.535 | 2.489322 | 0.00071284 | 2150.455 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 11.93709985 | 54.44 | 82.22 | 27.78 | 1392086.62 | 5.8532 | 5.970992 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 81481.53 | 81481.53 | 1.0000 | 2.92193049 | 2.489322 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.71276329 | 60.00 | 32.22 | 27.78 | 0.000 | 81481.53 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.91 | 0.00790358 | 21.00 | 0.00790358 | 49.8134 | 57054.55 | 0.00 | 81760.17 | 81760.17 | 2.92193049 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.24 | 21.25 | 0.00800000 | 61041.4 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 122322.114 | 122322.114 | 3.736611 | 0.00107013 | 3228.483 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 11.93709985 | 54.44 | 82.22 | 27.78 | 1392086.62 | 8.7870 | 8.963802 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 122322.11 | 122322.11 | 1.0000 | 4.38597986 | 3.736611 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 1.07001805 | 60.00 | 32.22 | 27.78 | 0.000 | 122322.11 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.91 | 0.00790031 | 21.00 | 0.00790031 | 49.7931 | 85656.09 | 0.00 | 122741.61 | 122741.61 | 4.38597986 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.24 | 21.25 | 0.00800000 | 61044.8 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 70505.877 | 70505.877 | 2.152877 | 0.00061682 | 1861.234 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 11.93709985 | 54.44 | 82.22 | 27.78 | 1392086.62 | 5.0648 | 5.166693 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 70505.88 | 70505.88 | 1.0000 | 2.52701524 | 2.152877 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.61675325 | 60.00 | 32.22 | 27.78 | 0.000 | 70505.88 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.91 | 0.00786997 | 21.00 | 0.00786997 | 49.6044 | 49381.77 | 0.00 | 70750.20 | 70750.20 | 2.52701524 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.26 | 21.26 | 0.00800000 | 61057.4 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 17668.253 | 17668.253 | 0.540259 | 0.00015457 | 466.109 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 11.93709985 | 54.44 | 82.22 | 27.78 | 1392086.62 | 1.2692 | 1.294735 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 17668.25 | 17668.25 | 1.0000 | 0.63414873 | 0.540259 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.15455381 | 60.00 | 32.22 | 27.78 | 0.000 | 17668.25 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00794874 | 21.00 | 0.00794874 | 50.0942 | 12366.35 | 0.00 | 17727.30 | 17727.30 | 0.63414873 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.21 | 21.25 | 0.00800000 | 61014.3 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11632.412 | 11632.412 | 0.355715 | 0.00010177 | 306.869 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 11.93709985 | 54.44 | 82.22 | 27.78 | 1392086.62 | 0.8356 | 0.852427 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 11632.41 | 11632.41 | 1.0000 | 0.41753340 | 0.355715 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.10175503 | 60.00 | 32.22 | 27.78 | 0.000 | 11632.41 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00794965 | 21.00 | 0.00794965 | 50.0999 | 8141.55 | 0.00 | 11671.23 | 11671.23 | 0.41753340 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.21 | 21.25 | 0.00800000 | 61012.6 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 17668.425 | 17668.425 | 0.540265 | 0.00015457 | 466.114 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 11.93709985 | 54.44 | 82.22 | 27.78 | 1392086.62 | 1.2692 | 1.294748 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 17668.43 | 17668.43 | 1.0000 | 0.63415491 | 0.540265 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.15455533 | 60.00 | 32.22 | 27.78 | 0.000 | 17668.43 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00794874 | 21.00 | 0.00794874 | 50.0942 | 12366.48 | 0.00 | 17727.48 | 17727.48 | 0.63415491 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.21 | 21.25 | 0.00800000 | 61014.3 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10788.668 | 10788.668 | 0.329853 | 0.00009438 | 284.634 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 11.93709985 | 54.44 | 82.22 | 27.78 | 1392086.62 | 0.7750 | 0.790597 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 10788.67 | 10788.67 | 1.0000 | 0.38717649 | 0.329853 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.09437435 | 60.00 | 32.22 | 27.78 | 0.000 | 10788.67 | 6.30 | 0.00607234 | 6.30 | 0.00000000 | 0.0000 | 20.95 | 0.00793757 | 21.00 | 0.00793757 | 50.0248 | 7551.70 | 0.00 | 10824.85 | 10824.85 | 0.38717649 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.22 | 21.25 | 0.00800000 | 61018.3 | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 233283.980 | -999.000 | 9.808941 | 0.00992444 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.4003 | 1004.8586 | 1.1738 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 9.808941 | 11.51359212 | 4197.9300 | 999.8980 | 122.52065959 | 12.27 | 6.67 | 5.60 | 2880265.65 | 8.0994 | 8.099391 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | Sensible | 233283.98 | 211663.82 | 1.0000 | 11.51359212 | 9.808941 | 28.81 | 17.23 | 0.00783253 | 48958.5 | 10.99 | 9.55 | 0.00700000 | 28696.9 | 9.92342738 | 6.67 | 12.27 | 5.60 | 21196.599 | 212087.38 | 42.00 | 0.00915790 | 22.26 | 2.53819000 | 25.8763 | 24.00 | 0.00734896 | 24.00 | 0.00734896 | 38.6354 | 127037.73 | 0.00 | 237639.92 | 223761.68 | 11.51359212 | 28.81 | 17.50 | 0.00783253 | 48958.5 | 9.75 | 9.59 | 0.00735403 | 28318.6 | |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 22570.865 | 22570.865 | 2.942682 | 0.00019746 | 394.689 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 9.808941 | 11.51359212 | 4197.9300 | 999.8980 | 11.93709985 | 54.44 | 82.22 | 27.78 | 1392086.62 | 1.6214 | 1.654000 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 22570.87 | 22570.87 | 1.0000 | 3.45407764 | 2.942682 | 6.30 | 6.30 | 0.00613865 | 21751.8 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 0.19743963 | 60.00 | 32.22 | 27.78 | 0.000 | 22570.87 | 6.30 | 0.00607234 | 6.30 | 2.53819000 | 86.2543 | 6.28 | 0.00655470 | 22.54 | 0.00665833 | 38.2686 | 6791.85 | 0.00 | 23690.11 | 23690.11 | 3.45407764 | 2.80 | 2.80 | 0.00613865 | 18197.9 | 9.55 | 8.14 | 0.00613865 | 25056.5 | |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 2280072.413 | -999.000 | 92.787326 | 0.09699955 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.5509 | 1004.8586 | 1.1738 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 92.787326 | 108.91241465 | 4197.9300 | 999.8980 | 122.52065959 | 12.27 | 6.67 | 5.60 | 2880265.65 | 79.1619 | 79.161879 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | Sensible | 2280072.41 | 2054737.19 | 1.0000 | 108.91241465 | 92.787326 | 29.27 | 17.45 | 0.00791354 | 49632.1 | 10.99 | 9.55 | 0.00700000 | 28697.2 | 96.98965633 | 6.67 | 12.27 | 5.60 | 200508.471 | 2079563.94 | 42.00 | 0.00915790 | 22.26 | 25.38195000 | 27.3550 | 24.00 | 0.00739846 | 24.00 | 0.00739846 | 38.8928 | 1160020.42 | 0.00 | 2321039.26 | 2167672.23 | 108.91241465 | 29.27 | 17.72 | 0.00791354 | 49632.1 | 9.75 | 9.59 | 0.00735453 | 28321.0 | |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 171567.883 | 171567.883 | 27.836198 | 0.00150095 | 3027.846 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 92.787326 | 108.91241465 | 4197.9300 | 999.8980 | 11.93709985 | 54.44 | 82.22 | 27.78 | 1392086.62 | 12.3245 | 12.572548 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 171567.88 | 171567.88 | 1.0000 | 32.67372439 | 27.836198 | 7.57 | 7.11 | 0.00623743 | 23298.4 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 1.50079757 | 60.00 | 32.22 | 27.78 | 0.000 | 171567.88 | 6.30 | 0.00607234 | 6.30 | 25.38195000 | 91.1833 | 20.75 | 0.00794474 | 21.00 | 0.00793397 | 50.0022 | 442079.52 | 0.00 | 183176.43 | 183176.43 | 32.67372439 | 2.80 | 2.80 | 0.00623743 | 18445.4 | 8.32 | 7.66 | 0.00623743 | 24051.7 | |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 243601.617 | -999.000 | 10.589565 | 0.01036338 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.2870 | 1004.8586 | 1.1738 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 10.589565 | 12.42987736 | 4197.9300 | 999.8980 | 122.52065959 | 12.27 | 6.67 | 5.60 | 2880265.65 | 8.4576 | 8.457609 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:30:00 | Sensible | 243601.62 | 222071.32 | 1.0000 | 12.42987736 | 10.589565 | 28.32 | 17.01 | 0.00777160 | 48304.5 | 11.00 | 9.55 | 0.00700000 | 28706.4 | 10.36231876 | 6.67 | 12.27 | 5.60 | 22761.895 | 220839.72 | 42.00 | 0.00915790 | 22.26 | 2.53819000 | 23.9688 | 24.00 | 0.00733343 | 24.00 | 0.00733343 | 38.5549 | 141400.81 | 0.00 | 248248.49 | 235266.64 | 12.42987736 | 28.32 | 17.28 | 0.00777160 | 48304.5 | 9.75 | 9.59 | 0.00735700 | 28332.6 | |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 13282.337 | 13282.337 | 3.176869 | 0.00011620 | 237.356 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 10.589565 | 12.42987736 | 4197.9300 | 999.8980 | 11.93709985 | 54.44 | 82.22 | 27.78 | 1392086.62 | 0.9541 | 0.973334 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 12:00:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 13282.34 | 13282.34 | 1.0000 | 3.72896321 | 3.176869 | 9.26 | 8.16 | 0.00645544 | 25555.8 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 0.11618783 | 60.00 | 32.22 | 27.78 | 0.000 | 13282.34 | 6.30 | 0.00607234 | 6.30 | 2.53819000 | 79.8959 | 21.00 | 0.00797793 | 21.00 | 0.00797793 | 50.2754 | 57545.58 | 0.00 | 14509.80 | 14509.80 | 3.72896321 | 2.80 | 2.80 | 0.00645544 | 18991.8 | 6.63 | 6.63 | 0.00645544 | 22882.9 | |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 123307.645 | -999.000 | 5.568055 | 0.00524579 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.4950 | 1004.8586 | 1.1738 | CAV_BAS FAN | Fan:ConstantVolume | 5.568055 | 6.53570200 | 4197.9300 | 999.8980 | 122.52065959 | 12.27 | 6.67 | 5.60 | 2880265.65 | 4.2811 | 4.281121 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 11:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 11:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 08:00:00 | Sensible | 123307.64 | 110638.64 | 1.0000 | 6.53570200 | 5.568055 | 27.70 | 16.89 | 0.00788349 | 47959.6 | 11.38 | 9.72 | 0.00700000 | 29092.8 | 5.24525713 | 6.67 | 12.27 | 5.60 | 9441.497 | 113866.15 | 39.77 | 0.00915417 | 21.63 | 1.20015641 | 21.5543 | 24.00 | 0.00749333 | 24.00 | 0.00749333 | 39.3855 | 68353.97 | 0.00 | 125668.08 | 118261.45 | 6.53570200 | 27.70 | 17.16 | 0.00788349 | 47959.6 | 9.95 | 9.77 | 0.00743368 | 28731.7 | |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 253780.157 | 253780.157 | 5.568055 | 0.00222018 | 5777.807 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | CAV_BAS FAN | Fan:ConstantVolume | 5.568055 | 6.53570200 | 4197.9300 | 999.8980 | 11.93709985 | 54.44 | 82.22 | 27.78 | 1392086.62 | 18.2302 | 18.597089 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 253780.16 | 253780.16 | 1.0000 | 6.53570200 | 5.568055 | 1.36 | 1.36 | 0.00607234 | 16566.4 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 2.21995304 | 60.00 | 32.22 | 27.78 | 0.000 | 253780.16 | 6.30 | 0.00607234 | 6.30 | 1.20015641 | 21.5543 | 0.00 | 0.00607234 | 25.81 | 0.00607234 | 28.7199 | 0.00 | 0.00 | 218646.00 | 218646.00 | 6.53570200 | 12.80 | 9.56 | 0.00607234 | 28193.0 | 45.72 | 21.48 | 0.00607234 | 61647.1 | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 451109.565 | 280919.893 | 21.900509 | 0.01104764 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1017.9919 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:00:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 07:10:00 | Sensible | 405188.86 | 401471.72 | 0.8982 | -999.0 | -999.0 | 28.66 | 16.55 | 0.00707492 | 46869.4 | 12.80 | 10.34 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 405188.86 | 42.00 | 0.00915790 | 22.26 | 0.33839277 | -999.0000 | 27.00 | 0.00704219 | 27.00 | 0.00704219 | 30.9981 | 371036.55 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9672.218 | 6096.444 | 0.482956 | 0.00023687 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1017.9815 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:20:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 06:40:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:20:00 | Sensible | 8642.49 | 8567.20 | 0.8935 | -999.0 | -999.0 | 28.14 | 16.36 | 0.00706933 | 46331.0 | 12.80 | 10.34 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8642.49 | 32.36 | 0.00914193 | 19.41 | 0.01563234 | -999.0000 | 27.00 | 0.00700000 | 27.00 | 0.00700000 | 30.8097 | 8144.83 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 92221.076 | 58100.267 | 4.600613 | 0.00225849 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1017.9879 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:20:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 06:40:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 05:20:00 | Sensible | 82416.93 | 81663.87 | 0.8937 | -999.0 | -999.0 | 28.15 | 16.37 | 0.00707278 | 46348.6 | 12.80 | 10.34 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 82416.93 | 32.36 | 0.00914193 | 19.41 | 0.15632344 | -999.0000 | 27.00 | 0.00700000 | 27.00 | 0.00700000 | 30.8097 | 77687.88 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9540.067 | 5930.055 | 0.463312 | 0.00023364 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1018.1532 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:10:00 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:40:00 | Sensible | 8569.33 | 8399.76 | 0.8982 | -999.0 | -999.0 | 28.45 | 16.55 | 0.00716170 | 46880.4 | 12.80 | 10.34 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8569.33 | 41.29 | 0.00915671 | 22.06 | 0.01563234 | -999.0000 | 27.00 | 0.00709201 | 27.00 | 0.00709201 | 31.2132 | 7855.92 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 451109.565 | 451109.565 | 21.900509 | 0.01104764 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 451109.56 | 451109.56 | 1.0000 | 25.70649850 | 21.900509 | 6.30 | 6.30 | 0.00607234 | 21588.2 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 451109.56 | 6.30 | 0.00607234 | 6.30 | 0.33839277 | 1.5451 | 0.00 | 0.00700000 | 27.00 | 0.00700000 | 30.8097 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9672.218 | 9672.218 | 0.482956 | 0.00023687 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 9672.22 | 9672.22 | 1.0000 | 0.56688676 | 0.482956 | 6.30 | 6.30 | 0.00607234 | 21588.2 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9672.22 | 6.30 | 0.00607234 | 6.30 | 0.01563234 | 3.2368 | 0.00 | 0.00700000 | 27.00 | 0.00700000 | 30.8097 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 92221.076 | 92221.076 | 4.600613 | 0.00225849 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 92221.08 | 92221.08 | 1.0000 | 5.40013208 | 4.600613 | 6.30 | 6.30 | 0.00607234 | 21588.2 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 92221.08 | 6.30 | 0.00607234 | 6.30 | 0.15632344 | 3.3979 | 0.00 | 0.00698209 | 25.16 | 0.00698209 | 34.2539 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9540.067 | 9540.067 | 0.463312 | 0.00023364 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1738 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 9540.07 | 9540.07 | 1.0000 | 0.54382862 | 0.463312 | 6.30 | 6.30 | 0.00607234 | 21588.2 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9540.07 | 6.30 | 0.00607234 | 6.30 | 0.01563234 | 3.3740 | 0.00 | 0.00620124 | 24.11 | 0.00620124 | 32.4414 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 13450.693 | 13450.693 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 21.900509 | 25.70649850 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 13450.69 | 13450.69 | 1.0000 | 25.70649850 | 21.900509 | 0.10 | 0.10 | 0.00698567 | 17569.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13450.69 | 6.30 | 0.00607234 | 6.30 | 0.33839277 | 1.5451 | 0.00 | 0.00700000 | 27.00 | 0.00700000 | 30.8097 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 621.366 | 621.366 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.482956 | 0.56688676 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 621.37 | 621.37 | 1.0000 | 0.56688676 | 0.482956 | 0.20 | 0.20 | 0.00696997 | 17639.0 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 621.37 | 6.30 | 0.00607234 | 6.30 | 0.01563234 | 3.2368 | 0.00 | 0.00700000 | 27.00 | 0.00700000 | 30.8097 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 6213.663 | 6213.663 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 4.600613 | 5.40013208 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 6213.66 | 6213.66 | 1.0000 | 5.40013208 | 4.600613 | 0.21 | 0.21 | 0.00695118 | 17602.4 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6213.66 | 6.30 | 0.00607234 | 6.30 | 0.15632344 | 3.3979 | 0.00 | 0.00698209 | 25.16 | 0.00698209 | 34.2539 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 621.366 | 621.366 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1738 | AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.463312 | 0.54382862 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 621.37 | 621.37 | 1.0000 | 0.54382862 | 0.463312 | 0.21 | 0.21 | 0.00619689 | 15714.1 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 621.37 | 6.30 | 0.00607234 | 6.30 | 0.01563234 | 3.3740 | 0.00 | 0.00620124 | 24.11 | 0.00620124 | 32.4414 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:27
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 5309.50 | 1653.33 | 1653.00 |
CORE_BOTTOM | 5343.83 | 23.00 | 13.33 |
CORE_MID | 4638.00 | 307.50 | 23.00 |
CORE_TOP | 4222.00 | 1123.33 | 26.83 |
PERIMETER_BOT_ZN_3 | 4603.50 | 797.83 | 173.67 |
PERIMETER_BOT_ZN_2 | 4744.83 | 816.00 | 241.33 |
PERIMETER_BOT_ZN_1 | 5218.50 | 621.67 | 333.33 |
PERIMETER_BOT_ZN_4 | 5479.33 | 758.50 | 623.33 |
PERIMETER_MID_ZN_3 | 3991.83 | 1679.83 | 273.00 |
PERIMETER_MID_ZN_2 | 3606.00 | 1316.00 | 379.17 |
PERIMETER_MID_ZN_1 | 4996.17 | 892.17 | 427.17 |
PERIMETER_MID_ZN_4 | 4475.67 | 1399.00 | 404.33 |
PERIMETER_TOP_ZN_3 | 3964.00 | 2093.33 | 460.83 |
PERIMETER_TOP_ZN_2 | 4238.67 | 1813.67 | 480.00 |
PERIMETER_TOP_ZN_1 | 4743.67 | 1260.33 | 472.00 |
PERIMETER_TOP_ZN_4 | 4282.83 | 1802.00 | 491.00 |
DATACENTER_BOT_ZN_6 | 5943.00 | 1410.17 | 1410.17 |
DATACENTER_MID_ZN_6 | 5943.00 | 493.83 | 493.83 |
DATACENTER_TOP_ZN_6 | 5907.17 | 659.00 | 646.17 |
DATACENTER_BASEMENT_ZN_6 | 5943.00 | 5943.00 | 5943.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5943.00 | 5943.00 | 5943.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 89.17 | 0.00 | 7.50 |
CORE_BOTTOM | 0.00 | 7.83 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.17 | 0.00 | 0.00 |
CORE_TOP | 0.17 | 0.50 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 71.00 | 0.00 | 26.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 77.67 | 0.00 | 47.50 |
PERIMETER_BOT_ZN_1 | 0.00 | 136.67 | 0.00 | 75.17 |
PERIMETER_BOT_ZN_4 | 0.00 | 358.00 | 0.00 | 106.17 |
PERIMETER_MID_ZN_3 | 0.00 | 49.83 | 0.00 | 18.67 |
PERIMETER_MID_ZN_2 | 0.00 | 85.33 | 0.00 | 52.17 |
PERIMETER_MID_ZN_1 | 0.00 | 110.50 | 0.00 | 64.67 |
PERIMETER_MID_ZN_4 | 0.00 | 130.33 | 0.00 | 43.33 |
PERIMETER_TOP_ZN_3 | 0.67 | 91.17 | 0.00 | 35.50 |
PERIMETER_TOP_ZN_2 | 0.33 | 127.50 | 0.00 | 63.67 |
PERIMETER_TOP_ZN_1 | 0.33 | 142.00 | 0.00 | 69.17 |
PERIMETER_TOP_ZN_4 | 0.33 | 154.67 | 0.00 | 52.50 |
DATACENTER_BOT_ZN_6 | 0.00 | 660.17 | 0.00 | 517.00 |
DATACENTER_MID_ZN_6 | 0.00 | 537.50 | 0.00 | 453.83 |
DATACENTER_TOP_ZN_6 | 0.00 | 368.83 | 0.00 | 321.33 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 1290.33 | 0.00 | 923.33 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.67 | 1747.67 | 0.00 | 1100.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:27
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.75 | 149.60 | 6779.02 | 0.533 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 56.35 | 134.35 | 6849.35 | 0.487 | 0.000 | 0.000 | 0.000 |
CORE_MID | 56.35 | 134.35 | 6849.35 | 0.468 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 56.35 | 134.35 | 6849.35 | 0.450 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 7.08 | 16.87 | 860.00 | 0.593 | 0.017 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.56 | 10.87 | 554.22 | 0.690 | 0.017 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 7.08 | 16.87 | 860.02 | 0.770 | 0.017 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.56 | 10.87 | 554.22 | 1.069 | 0.017 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 7.08 | 16.87 | 860.00 | 0.611 | 0.039 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.99 | 10.87 | 554.22 | 0.757 | 0.042 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 7.08 | 16.87 | 860.02 | 0.853 | 0.039 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.56 | 10.87 | 554.22 | 0.861 | 0.041 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 7.08 | 16.87 | 860.00 | 0.612 | 0.049 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.56 | 10.87 | 554.22 | 0.784 | 0.051 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 7.08 | 16.87 | 860.02 | 0.821 | 0.049 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.56 | 10.87 | 554.22 | 0.844 | 0.051 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.82 | 1.95 | 99.34 | 0.590 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.82 | 1.95 | 99.34 | 0.590 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.82 | 1.95 | 99.34 | 0.590 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.69 | 42.18 | 1911.37 | 0.665 | 0.000 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.75 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 56.35 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 56.35 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 56.35 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 7.08 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.56 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 7.08 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.56 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 7.08 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.99 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 7.08 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.56 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 7.08 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.56 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 7.08 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.56 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.82 | 1.95 | 99.34 | 0.545 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.82 | 1.95 | 99.34 | 0.545 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.82 | 1.95 | 99.34 | 0.545 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.69 | 42.18 | 1911.37 | 0.613 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 09:04:27
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | CAV_BAS | 62.75 | 149.60 | 6779.02 | 2779.43 | 1.2002 | 1.200 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 56.35 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
CORE_MID | VAV_MID WITH REHEAT | 56.35 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 10.778 |
CORE_TOP | VAV_TOP WITH REHEAT | 56.35 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 7.08 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 4.56 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 7.08 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 4.56 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 7.08 | 16.87 | 860.00 | 313.41 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 3.99 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 7.08 | 16.87 | 860.02 | 313.42 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 4.56 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 7.08 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 4.56 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 7.08 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 4.56 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.82 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.82 | 1.95 | 99.34 | 36.20 | 0.1563 | 0.156 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.82 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 17.69 | 42.18 | 1911.37 | 783.68 | 0.3384 | 0.338 |
Total Facility | 1040.03 | 2493.19 | 126016.35 | 46320.38 | 1.7261 | 158.471 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 23821144.57 | 0.00 | 23821144.57 | 0.00 | 23821144.57 | 37848132.68 | 3246.56 | 5513.44 | 0.00 | 719.50 |
CORE_BOTTOM | 24247717.05 | 0.00 | 24247717.05 | 0.00 | 24247717.05 | 33990283.35 | 7580.00 | 88.46 | 1091.54 | 1349.10 |
CORE_MID | 0.21E+09 | 0.00 | 0.21E+09 | 0.00 | 0.21E+09 | 0.34E+09 | 7620.43 | 317.86 | 821.71 | 807.06 |
CORE_TOP | 20714760.06 | 0.00 | 20714760.06 | 0.00 | 20714760.06 | 33990283.35 | 8409.18 | 52.14 | 298.69 | 811.90 |
PERIMETER_BOT_ZN_3 | 3583031.23 | 0.00 | 3583031.23 | 135485.55 | 3718516.78 | 4267819.30 | 5740.40 | 123.17 | 2896.43 | 1349.10 |
PERIMETER_BOT_ZN_2 | 2677702.40 | 0.00 | 2677702.40 | 90323.64 | 2768026.04 | 2750345.05 | 2962.12 | 151.68 | 5646.20 | 1349.10 |
PERIMETER_BOT_ZN_1 | 4474710.85 | 0.00 | 4474710.85 | 135485.55 | 4610196.40 | 4267912.63 | 4298.69 | 49.38 | 4411.93 | 1349.10 |
PERIMETER_BOT_ZN_4 | 4161878.82 | 0.00 | 4161878.82 | 90323.64 | 4252202.46 | 2750345.05 | 2143.78 | 0.34 | 6615.88 | 1349.10 |
PERIMETER_MID_ZN_3 | 34114116.90 | 0.00 | 34114116.90 | 317743.67 | 34431860.57 | 42678193.03 | 5768.10 | 217.84 | 2774.06 | 807.06 |
PERIMETER_MID_ZN_2 | 28205769.50 | 0.00 | 28205769.50 | 211828.97 | 28417598.47 | 27503450.52 | 3071.05 | 50.45 | 5638.49 | 1716.06 |
PERIMETER_MID_ZN_1 | 46280118.34 | 0.00 | 46280118.34 | 317743.67 | 46597862.01 | 42679126.28 | 4044.61 | 421.12 | 4294.26 | 807.06 |
PERIMETER_MID_ZN_4 | 31051984.02 | 0.00 | 31051984.02 | 211828.97 | 31263812.99 | 27503450.52 | 2971.06 | 60.46 | 5728.48 | 807.06 |
PERIMETER_TOP_ZN_3 | 3461917.59 | 0.00 | 3461917.59 | 394502.81 | 3856420.40 | 4267819.30 | 3750.08 | 132.57 | 4877.34 | 811.90 |
PERIMETER_TOP_ZN_2 | 2827254.86 | 0.00 | 2827254.86 | 263001.69 | 3090256.55 | 2750345.05 | 2951.60 | 19.85 | 5788.55 | 811.90 |
PERIMETER_TOP_ZN_1 | 4511837.64 | 0.00 | 4511837.64 | 394502.81 | 4906340.45 | 4267912.63 | 2918.25 | 16.92 | 5824.83 | 811.90 |
PERIMETER_TOP_ZN_4 | 3086712.71 | 0.00 | 3086712.71 | 263001.69 | 3349714.40 | 2750345.05 | 2884.05 | 5.43 | 5870.52 | 811.90 |
DATACENTER_BOT_ZN_6 | 492981.60 | 0.00 | 492981.60 | 0.00 | 492981.60 | 492981.60 | 0.00 | 8760.00 | 0.00 | 2817.00 |
DATACENTER_MID_ZN_6 | 4929815.99 | 0.00 | 4929815.99 | 0.00 | 4929815.99 | 4929815.99 | 0.00 | 8760.00 | 0.00 | 2817.00 |
DATACENTER_TOP_ZN_6 | 492981.60 | 0.00 | 492981.60 | 0.00 | 492981.60 | 492981.60 | 0.00 | 8760.00 | 0.00 | 2817.00 |
DATACENTER_BASEMENT_ZN_6 | 10671554.30 | 0.00 | 10671554.30 | 0.00 | 10671554.30 | 10671554.30 | 0.00 | 8760.00 | 0.00 | 2817.00 |
Total Facility | 0.37E+10 | 0.00 | 0.37E+10 | 12358080.11 | 0.37E+10 | 0.50E+10 | 8759.86 | 8760.00 | 6999.59 | 3726.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 0.9681 | 0.0000 | 0.9681 | 0.0000 | 0.9681 | 1.2002 | 1149.06 | 4793.94 | 0.00 |
CORE_BOTTOM | 0.8957 | 0.0000 | 0.8957 | 0.0000 | 0.8957 | 1.0778 | 4787.61 | 86.74 | 1068.66 |
CORE_MID | 8.6059 | 0.0000 | 8.6059 | 0.0000 | 8.6059 | 10.7782 | 4821.45 | 310.23 | 811.32 |
CORE_TOP | 0.8280 | 0.0000 | 0.8280 | 0.0000 | 0.8280 | 1.0778 | 5595.55 | 51.48 | 295.97 |
PERIMETER_BOT_ZN_3 | 0.1365 | 0.0000 | 0.1365 | 0.0039 | 0.1404 | 0.1353 | 3044.60 | 94.95 | 2803.45 |
PERIMETER_BOT_ZN_2 | 0.1024 | 0.0000 | 0.1024 | 0.0026 | 0.1050 | 0.0872 | 1468.08 | 147.11 | 4327.81 |
PERIMETER_BOT_ZN_1 | 0.1778 | 0.0000 | 0.1778 | 0.0039 | 0.1817 | 0.1353 | 1616.82 | 35.40 | 4290.78 |
PERIMETER_BOT_ZN_4 | 0.1588 | 0.0000 | 0.1588 | 0.0026 | 0.1614 | 0.0872 | 674.45 | 0.07 | 5268.49 |
PERIMETER_MID_ZN_3 | 1.4072 | 0.0000 | 1.4072 | 0.0091 | 1.4163 | 1.3533 | 3017.87 | 212.06 | 2713.08 |
PERIMETER_MID_ZN_2 | 1.1247 | 0.0000 | 1.1247 | 0.0062 | 1.1310 | 0.8721 | 958.25 | 30.64 | 4045.10 |
PERIMETER_MID_ZN_1 | 1.9697 | 0.0000 | 1.9697 | 0.0091 | 1.9788 | 1.3533 | 1363.90 | 378.38 | 4200.72 |
PERIMETER_MID_ZN_4 | 1.2790 | 0.0000 | 1.2790 | 0.0060 | 1.2851 | 0.8721 | 956.69 | 60.11 | 4926.20 |
PERIMETER_TOP_ZN_3 | 0.1412 | 0.0000 | 0.1412 | 0.0113 | 0.1524 | 0.1353 | 1734.61 | 124.43 | 4083.96 |
PERIMETER_TOP_ZN_2 | 0.1166 | 0.0000 | 0.1166 | 0.0075 | 0.1241 | 0.0872 | 944.97 | 19.64 | 4978.39 |
PERIMETER_TOP_ZN_1 | 0.1896 | 0.0000 | 0.1896 | 0.0113 | 0.2008 | 0.1353 | 911.48 | 14.68 | 5016.84 |
PERIMETER_TOP_ZN_4 | 0.1254 | 0.0000 | 0.1254 | 0.0075 | 0.1329 | 0.0872 | 878.65 | 5.40 | 5058.95 |
DATACENTER_BOT_ZN_6 | 0.0156 | 0.0000 | 0.0156 | 0.0000 | 0.0156 | 0.0156 | 0.00 | 5943.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.1563 | 0.0000 | 0.1563 | 0.0000 | 0.1563 | 0.1563 | 0.00 | 5943.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.0156 | 0.0000 | 0.0156 | 0.0000 | 0.0156 | 0.0156 | 0.00 | 5943.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.3384 | 0.0000 | 0.3384 | 0.0000 | 0.3384 | 0.3384 | 0.00 | 5943.00 | 0.00 |
Total Facility | 149.6397 | 0.0000 | 149.6397 | 0.3545 | 149.9943 | 158.4706 | 5942.86 | 5943.00 | 5401.74 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV_BOT WITH REHEAT | 53932977.31 | 0.00 | 53932977.31 | 48026705.38 | 2139.79 | 0.00 | 6620.21 | 1349.10 |
VAV_MID WITH REHEAT | 0.49E+09 | 0.00 | 0.49E+09 | 0.48E+09 | 2871.73 | 0.00 | 5888.27 | 807.06 |
VAV_TOP WITH REHEAT | 47674343.62 | 0.00 | 47674343.62 | 48026705.38 | 2877.93 | 0.00 | 5882.07 | 811.90 |
CAV_BAS | 32820113.29 | 0.00 | 32820113.29 | 37848132.68 | 3246.56 | 0.00 | 5513.44 | 719.50 |
AIRLOOP DATACENTER BASEMENT | 14702971.99 | 0.00 | 14702971.99 | 10671554.30 | 0.00 | 0.00 | 8760.00 | 2817.00 |
AIRLOOP DATACENTER BOT | 679216.39 | 0.00 | 679216.39 | 492981.60 | 0.00 | 0.00 | 8760.00 | 2817.00 |
AIRLOOP DATACENTER MID | 6792163.95 | 0.00 | 6792163.95 | 4929815.99 | 0.00 | 0.00 | 8760.00 | 2817.00 |
AIRLOOP DATACENTER TOP | 679216.39 | 0.00 | 679216.39 | 492981.60 | 0.00 | 0.00 | 8760.00 | 2817.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV_BOT WITH REHEAT | 2.0271 | 0.0000 | 2.0271 | 1.5229 | 671.89 | 0.00 | 5271.11 |
VAV_MID WITH REHEAT | 19.8857 | 0.0000 | 19.8857 | 15.2292 | 861.79 | 0.00 | 5081.21 |
VAV_TOP WITH REHEAT | 1.9298 | 0.0000 | 1.9298 | 1.5229 | 872.82 | 0.00 | 5070.18 |
CAV_BAS | 1.3338 | 0.0000 | 1.3338 | 1.2002 | 1149.06 | 0.00 | 4793.94 |
AIRLOOP DATACENTER BASEMENT | 0.4662 | 0.0000 | 0.4662 | 0.3384 | 0.00 | 0.00 | 5943.00 |
AIRLOOP DATACENTER BOT | 0.0215 | 0.0000 | 0.0215 | 0.0156 | 0.00 | 0.00 | 5943.00 |
AIRLOOP DATACENTER MID | 0.2154 | 0.0000 | 0.2154 | 0.1563 | 0.00 | 0.00 | 5943.00 |
AIRLOOP DATACENTER TOP | 0.0215 | 0.0000 | 0.0215 | 0.0156 | 0.00 | 0.00 | 5943.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV_BOT WITH REHEAT | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6620.21 | 0.00 | 0.00 | 0.00 |
VAV_MID WITH REHEAT | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5888.27 | 0.00 | 0.00 | 0.00 |
VAV_TOP WITH REHEAT | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5882.07 | 0.00 | 0.00 | 0.00 |
CAV_BAS | 0.00 | 5513.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV_BOT WITH REHEAT | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 2.2855 | 0.0000 | 0.0000 | 0.0000 |
VAV_MID WITH REHEAT | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 23.2594 | 0.0000 | 0.0000 | 0.0000 |
VAV_TOP WITH REHEAT | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 2.2621 | 0.0000 | 0.0000 | 0.0000 |
CAV_BAS | 0.0000 | 1.6539 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BASEMENT | 0.0000 | 0.4662 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BOT | 0.0000 | 0.0215 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER MID | 0.0000 | 0.2154 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER TOP | 0.0000 | 0.0215 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:27
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 8 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1380 |
Defaulted Fields | 1179 |
Fields with Defaults | 3862 |
Autosized Fields | 330 |
Autosizable Fields | 409 |
Autocalculated Fields | 226 |
Autocalculatable Fields | 473 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 09:04:27
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 32797.66 | 375599.35 | 01-JAN-10:30 | 2042710.94 | 07-AUG-15:10 |
Electricity:Building | 17955.23 | 247233.96 | 01-JAN-08:50 | 1047565.99 | 29-DEC-17:00 |
Electricity:Zone:BASEMENT | 602.14 | 14319.77 | 01-JAN-00:10 | 28977.00 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 17955.23 | 247233.96 | 01-JAN-08:50 | 1047565.99 | 29-DEC-17:00 |
InteriorLights:Electricity | 2741.82 | 13024.70 | 01-JAN-08:50 | 254941.81 | 11-OCT-07:10 |
InteriorLights:Electricity:Zone:BASEMENT | 177.74 | 862.23 | 01-JAN-00:10 | 15519.45 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 2741.82 | 13024.70 | 01-JAN-08:50 | 254941.81 | 11-OCT-07:10 |
LightsWired:InteriorLights:Electricity | 2741.82 | 13024.70 | 01-JAN-08:50 | 254941.81 | 11-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 177.74 | 862.23 | 01-JAN-00:10 | 15519.45 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 2741.82 | 13024.70 | 01-JAN-08:50 | 254941.81 | 11-OCT-07:10 |
Electricity:Zone:CORE_BOTTOM | 480.91 | 6817.20 | 01-JAN-00:10 | 32066.15 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 159.62 | 774.34 | 01-JAN-00:10 | 13937.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 159.62 | 774.34 | 01-JAN-00:10 | 13937.56 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 4809.09 | 68171.81 | 01-JAN-00:10 | 320660.81 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 1596.25 | 7743.41 | 01-JAN-00:10 | 139375.61 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 1596.25 | 7743.41 | 01-JAN-00:10 | 139375.61 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 480.91 | 6817.18 | 01-JAN-00:10 | 32066.08 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 159.62 | 774.34 | 01-JAN-00:10 | 13937.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 159.62 | 774.34 | 01-JAN-00:10 | 13937.56 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 54.12 | 818.50 | 01-JAN-08:40 | 3871.91 | 11-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 13.78 | 59.73 | 01-JAN-08:40 | 1595.59 | 11-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 13.78 | 59.73 | 01-JAN-08:40 | 1595.59 | 11-OCT-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 34.87 | 527.47 | 01-JAN-07:50 | 2496.53 | 27-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 8.87 | 38.49 | 01-JAN-07:50 | 1029.58 | 27-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 8.87 | 38.49 | 01-JAN-07:50 | 1029.58 | 27-NOV-17:00 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 54.04 | 818.51 | 01-JAN-07:50 | 3865.66 | 11-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 13.70 | 59.73 | 01-JAN-07:50 | 1589.31 | 11-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 13.70 | 59.73 | 01-JAN-07:50 | 1589.31 | 11-OCT-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 34.86 | 527.47 | 01-JAN-08:50 | 2499.72 | 11-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 8.86 | 38.49 | 01-JAN-08:50 | 1032.79 | 11-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 8.86 | 38.49 | 01-JAN-08:50 | 1032.79 | 11-OCT-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 541.32 | 8184.99 | 01-JAN-08:40 | 38764.25 | 11-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 137.90 | 597.26 | 01-JAN-08:40 | 16001.07 | 11-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 137.90 | 597.26 | 01-JAN-08:40 | 16001.07 | 11-OCT-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 348.71 | 5274.72 | 01-JAN-07:50 | 24974.07 | 27-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 88.73 | 384.90 | 01-JAN-07:50 | 10304.61 | 27-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 88.73 | 384.90 | 01-JAN-07:50 | 10304.61 | 27-NOV-17:00 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 540.49 | 8185.12 | 01-JAN-08:00 | 38704.41 | 11-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 137.06 | 597.27 | 01-JAN-08:00 | 15940.89 | 11-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 137.06 | 597.27 | 01-JAN-08:00 | 15940.89 | 11-OCT-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 348.64 | 5274.69 | 01-JAN-08:50 | 25004.27 | 11-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 88.66 | 384.90 | 01-JAN-08:50 | 10334.90 | 11-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 88.66 | 384.90 | 01-JAN-08:50 | 10334.90 | 11-OCT-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 54.13 | 818.50 | 01-JAN-08:40 | 3876.27 | 11-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 13.79 | 59.73 | 01-JAN-08:40 | 1599.95 | 11-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 13.79 | 59.73 | 01-JAN-08:40 | 1599.95 | 11-OCT-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 34.87 | 527.47 | 01-JAN-07:50 | 2497.35 | 27-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 8.87 | 38.49 | 01-JAN-07:50 | 1030.41 | 27-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 8.87 | 38.49 | 01-JAN-07:50 | 1030.41 | 27-NOV-17:00 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 54.05 | 818.51 | 01-JAN-08:00 | 3870.29 | 11-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 13.71 | 59.73 | 01-JAN-08:00 | 1593.94 | 11-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 13.71 | 59.73 | 01-JAN-08:00 | 1593.94 | 11-OCT-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 34.86 | 527.47 | 01-JAN-08:50 | 2500.33 | 11-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 8.87 | 38.49 | 01-JAN-08:50 | 1033.39 | 11-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 8.87 | 38.49 | 01-JAN-08:50 | 1033.39 | 11-OCT-07:10 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7544.97 | 95151.24 | 01-JAN-00:10 | 384008.34 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 50.12 | 243.11 | 01-JAN-00:10 | 4375.82 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 50.12 | 243.11 | 01-JAN-00:10 | 4375.82 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 158.52 | 1971.11 | 01-JAN-00:10 | 8199.53 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 4.64 | 22.51 | 01-JAN-00:10 | 405.10 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 4.64 | 22.51 | 01-JAN-00:10 | 405.10 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1585.20 | 19711.13 | 01-JAN-00:10 | 81995.25 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 46.40 | 225.07 | 01-JAN-00:10 | 4051.03 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 46.40 | 225.07 | 01-JAN-00:10 | 4051.03 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 158.52 | 1971.11 | 01-JAN-00:10 | 8199.53 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 4.64 | 22.51 | 01-JAN-00:10 | 405.10 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 4.64 | 22.51 | 01-JAN-00:10 | 405.10 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 15213.41 | 234209.26 | 01-JAN-00:10 | 794004.08 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 15213.41 | 234209.26 | 01-JAN-00:10 | 794004.08 | 03-APR-07:10 |
MiscPlug:InteriorEquipment:Electricity | 5871.99 | 115917.86 | 01-JAN-00:10 | 320838.49 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 5871.99 | 115917.86 | 01-JAN-00:10 | 320838.49 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 321.29 | 6042.86 | 01-JAN-00:10 | 18128.59 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 321.29 | 6042.86 | 01-JAN-00:10 | 18128.59 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 3212.85 | 60428.40 | 01-JAN-00:10 | 181285.20 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 3212.85 | 60428.40 | 01-JAN-00:10 | 181285.20 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 321.28 | 6042.84 | 01-JAN-00:10 | 18128.52 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 321.28 | 6042.84 | 01-JAN-00:10 | 18128.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 40.34 | 758.77 | 01-JAN-00:10 | 2276.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 40.34 | 758.77 | 01-JAN-00:10 | 2276.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.95 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.95 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 40.34 | 758.78 | 01-JAN-00:10 | 2276.35 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 40.34 | 758.78 | 01-JAN-00:10 | 2276.35 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.94 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.94 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 403.42 | 7587.73 | 01-JAN-00:10 | 22763.18 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 403.42 | 7587.73 | 01-JAN-00:10 | 22763.18 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 259.98 | 4889.82 | 01-JAN-00:10 | 14669.46 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 259.98 | 4889.82 | 01-JAN-00:10 | 14669.46 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 403.43 | 7587.84 | 01-JAN-00:10 | 22763.53 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 403.43 | 7587.84 | 01-JAN-00:10 | 22763.53 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 259.98 | 4889.79 | 01-JAN-00:10 | 14669.36 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 259.98 | 4889.79 | 01-JAN-00:10 | 14669.36 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 40.34 | 758.77 | 01-JAN-00:10 | 2276.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 40.34 | 758.77 | 01-JAN-00:10 | 2276.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.95 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.95 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 40.34 | 758.78 | 01-JAN-00:10 | 2276.35 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 40.34 | 758.78 | 01-JAN-00:10 | 2276.35 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.94 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.94 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
Electricity:Plant | 6333.66 | 8268.15 | 05-JAN-05:40 | 548558.64 | 22-JUN-15:40 |
HeatRejection:Electricity | 1962.04 | 4579.22 | 05-JAN-07:00 | 91812.10 | 06-MAR-14:30 |
General:HeatRejection:Electricity | 1962.04 | 4579.22 | 05-JAN-07:00 | 91812.10 | 06-MAR-14:30 |
Electricity:HVAC | 6206.84 | 81819.38 | 16-JAN-04:40 | 423977.76 | 07-JUL-14:50 |
ExteriorEquipment:Electricity | 1914.38 | 28294.68 | 01-JAN-00:10 | 117201.23 | 11-OCT-07:20 |
Transformer:ExteriorEquipment:Electricity | 59.77 | 1112.61 | 01-JAN-00:10 | 3723.27 | 11-OCT-07:20 |
ElectricityPurchased:Facility | 32797.66 | 375599.35 | 01-JAN-10:30 | 2042710.94 | 07-AUG-15:10 |
ElectricityPurchased:Plant | 32797.66 | 375599.35 | 01-JAN-10:30 | 2042710.94 | 07-AUG-15:10 |
Cogeneration:ElectricityPurchased | 32797.66 | 375599.35 | 01-JAN-10:30 | 2042710.94 | 07-AUG-15:10 |
General:Cogeneration:ElectricityPurchased | 32797.66 | 375599.35 | 01-JAN-10:30 | 2042710.94 | 07-AUG-15:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 32797.66 | 375599.35 | 01-JAN-10:30 | 2042710.94 | 07-AUG-15:10 |
ElectricityNet:Plant | 32797.66 | 375599.35 | 01-JAN-10:30 | 2042710.94 | 07-AUG-15:10 |
Cogeneration:ElectricityNet | 32797.66 | 375599.35 | 01-JAN-10:30 | 2042710.94 | 07-AUG-15:10 |
General:Cogeneration:ElectricityNet | 32797.66 | 375599.35 | 01-JAN-10:30 | 2042710.94 | 07-AUG-15:10 |
Fans:Electricity | 2647.39 | 42332.45 | 05-JAN-23:40 | 229329.06 | 07-JUN-14:00 |
General:Fans:Electricity | 2647.39 | 42332.45 | 05-JAN-23:40 | 229329.06 | 07-JUN-14:00 |
ExteriorLights:Electricity | 447.32 | 0.00 | 01-JAN-07:20 | 37611.08 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 447.32 | 0.00 | 01-JAN-07:20 | 37611.08 | 01-JAN-06:10 |
ElevatorLift:ExteriorEquipment:Electricity | 1848.78 | 27144.47 | 01-JAN-00:10 | 113101.96 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 5.83 | 37.60 | 01-JAN-00:10 | 376.00 | 01-JAN-07:10 |
Cooling:Electricity | 6499.17 | 33609.71 | 01-JAN-06:00 | 571270.01 | 28-AUG-14:50 |
General:Cooling:Electricity | 6499.17 | 33609.71 | 01-JAN-06:00 | 571270.01 | 28-AUG-14:50 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Humidifier:Electricity | 82.64 | 0.00 | 12-JAN-13:10 | 28639.67 | 22-DEC-06:00 |
General:Humidifier:Electricity | 82.64 | 0.00 | 12-JAN-13:10 | 28639.67 | 22-DEC-06:00 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Pumps:Electricity | 1289.49 | 3513.73 | 01-JAN-00:10 | 70858.56 | 29-AUG-05:10 |
General:Pumps:Electricity | 1289.49 | 3513.73 | 01-JAN-00:10 | 70858.56 | 29-AUG-05:10 |
WIRED_LTG_ELECTRICITY | 77.05 | 0.00 | 01-JAN-00:10 | 7163.86 | 11-OCT-07:20 |
WIRED_INT_EQUIP | 5871.99 | 115917.86 | 04-MAR-00:10 | 320838.49 | 03-APR-07:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 577.83 | 5695.87 | 16-APR-15:40 | 244167.48 | 02-JAN-06:20 |
NaturalGas:Plant | 577.83 | 5695.87 | 16-APR-15:40 | 244167.48 | 02-JAN-06:20 |
Heating:NaturalGas | 18.27 | 0.00 | 01-JAN-00:10 | 217619.02 | 02-JAN-06:20 |
Boiler:Heating:NaturalGas | 18.27 | 0.00 | 01-JAN-00:10 | 217619.02 | 02-JAN-06:20 |
WaterSystems:NaturalGas | 559.56 | 5695.87 | 16-APR-15:40 | 72823.30 | 10-JAN-12:50 |
Water Heater:WaterSystems:NaturalGas | 559.56 | 5695.87 | 16-APR-15:40 | 72823.30 | 10-JAN-12:50 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 35429.36 | 165767.50 | 01-JAN-06:00 | 3103772.09 | 28-AUG-14:40 |
PlantLoopCoolingDemand:HVAC | 35429.36 | 165767.50 | 01-JAN-06:00 | 3103772.09 | 28-AUG-14:40 |
CoolingCoils:PlantLoopCoolingDemand | 35429.36 | 165767.50 | 01-JAN-06:00 | 3103772.09 | 28-AUG-14:40 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 20733.93 | 0.00 | 11-MAR-00:10 | 0.00 | 19-APR-15:10 |
Water:HVAC | 30.74 | 0.00 | 12-JAN-13:10 | 0.00 | 22-DEC-06:00 |
Humidifier:Water | 30.74 | 0.00 | 12-JAN-13:10 | 0.00 | 22-DEC-06:00 |
General:Humidifier:Water | 30.74 | 0.00 | 12-JAN-13:10 | 0.00 | 22-DEC-06:00 |
MainsWater:Facility | 20733.93 | 0.00 | 11-MAR-00:10 | 0.00 | 19-APR-15:10 |
MainsWater:HVAC | 30.74 | 0.00 | 12-JAN-13:10 | 0.00 | 22-DEC-06:00 |
Humidifier:MainsWater | 30.74 | 0.00 | 12-JAN-13:10 | 0.00 | 22-DEC-06:00 |
General:Humidifier:MainsWater | 30.74 | 0.00 | 12-JAN-13:10 | 0.00 | 22-DEC-06:00 |
Water:Plant | 20703.19 | 0.00 | 01-JAN-00:10 | 0.00 | 19-APR-15:10 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 20703.19 | 0.00 | 01-JAN-00:10 | 0.00 | 19-APR-15:10 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatRejection:Water | 18423.02 | 0.00 | 01-JAN-00:10 | 0.00 | 19-APR-15:00 |
General:HeatRejection:Water | 18423.02 | 0.00 | 01-JAN-00:10 | 0.00 | 19-APR-15:00 |
HeatRejection:MainsWater | 18423.02 | 0.00 | 01-JAN-00:10 | 0.00 | 19-APR-15:00 |
General:HeatRejection:MainsWater | 18423.02 | 0.00 | 01-JAN-00:10 | 0.00 | 19-APR-15:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 120612.32 | 229336.65 | 01-JAN-05:30 | 12057260.73 | 28-AUG-14:40 |
EnergyTransfer:Building | 22802.23 | 96830.74 | 01-JAN-07:50 | 1632312.71 | 27-APR-15:30 |
EnergyTransfer:Zone:BASEMENT | 748.53 | 0.00 | 01-JAN-00:40 | 73749.36 | 26-DEC-06:10 |
Heating:EnergyTransfer | 18.72 | 0.00 | 02-JAN-17:20 | 98312.78 | 02-JAN-06:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 4.49 | 0.00 | 01-JAN-00:10 | 33282.46 | 10-JUN-16:10 |
General:Heating:EnergyTransfer | 18.72 | 0.00 | 02-JAN-17:20 | 98312.78 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 4.49 | 0.00 | 01-JAN-00:10 | 33282.46 | 10-JUN-16:10 |
Cooling:EnergyTransfer | 22783.51 | 96603.22 | 01-JAN-07:50 | 1632312.71 | 27-APR-15:30 |
Cooling:EnergyTransfer:Zone:BASEMENT | 744.05 | 0.00 | 01-JAN-00:40 | 73749.36 | 26-DEC-06:10 |
General:Cooling:EnergyTransfer | 22783.51 | 96603.22 | 01-JAN-07:50 | 1632312.71 | 27-APR-15:30 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 744.05 | 0.00 | 01-JAN-00:40 | 73749.36 | 26-DEC-06:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 763.72 | 0.00 | 01-JAN-00:10 | 58546.97 | 07-AUG-07:20 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 763.72 | 0.00 | 01-JAN-00:10 | 58546.97 | 07-AUG-07:20 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 763.72 | 0.00 | 01-JAN-00:10 | 58546.97 | 07-AUG-07:20 |
EnergyTransfer:Zone:CORE_MID | 5794.37 | 0.00 | 01-JAN-00:10 | 433177.84 | 05-SEP-09:20 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 5794.37 | 0.00 | 01-JAN-00:10 | 433177.84 | 05-SEP-09:20 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 5794.37 | 0.00 | 01-JAN-00:10 | 433177.84 | 05-SEP-09:20 |
EnergyTransfer:Zone:CORE_TOP | 596.44 | 0.00 | 01-JAN-00:10 | 55989.00 | 12-JUN-14:00 |
Heating:EnergyTransfer:Zone:CORE_TOP | 0.24 | 0.00 | 01-JAN-00:10 | 38510.49 | 02-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 0.24 | 0.00 | 01-JAN-00:10 | 38510.49 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 596.19 | 0.00 | 01-JAN-00:10 | 55989.00 | 12-JUN-14:00 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 596.19 | 0.00 | 01-JAN-00:10 | 55989.00 | 12-JUN-14:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 120.58 | 0.00 | 01-JAN-00:10 | 12797.57 | 12-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 120.58 | 0.00 | 01-JAN-00:10 | 12797.57 | 12-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 120.58 | 0.00 | 01-JAN-00:10 | 12797.57 | 12-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 90.00 | 0.00 | 01-JAN-00:10 | 12364.21 | 12-JUN-09:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 90.00 | 0.00 | 01-JAN-00:10 | 12364.21 | 12-JUN-09:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 90.00 | 0.00 | 01-JAN-00:10 | 12364.21 | 12-JUN-09:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 154.07 | 0.00 | 01-JAN-00:10 | 16568.23 | 02-OCT-13:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 154.07 | 0.00 | 01-JAN-00:10 | 16568.23 | 02-OCT-13:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 154.07 | 0.00 | 01-JAN-00:10 | 16568.23 | 02-OCT-13:20 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 139.69 | 0.00 | 01-JAN-00:10 | 16373.84 | 27-APR-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 139.69 | 0.00 | 01-JAN-00:10 | 16373.84 | 27-APR-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 139.69 | 0.00 | 01-JAN-00:10 | 16373.84 | 27-APR-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 977.68 | 0.00 | 01-JAN-00:10 | 120463.05 | 12-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.02 | 0.00 | 01-JAN-00:10 | 7205.96 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.02 | 0.00 | 01-JAN-00:10 | 7205.96 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 977.67 | 0.00 | 01-JAN-00:10 | 120463.05 | 12-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 977.67 | 0.00 | 01-JAN-00:10 | 120463.05 | 12-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 818.81 | 0.00 | 01-JAN-00:10 | 122773.51 | 03-MAY-09:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 1147.80 | 03-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 1147.80 | 03-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 818.81 | 0.00 | 01-JAN-00:10 | 122773.51 | 03-MAY-09:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 818.81 | 0.00 | 01-JAN-00:10 | 122773.51 | 03-MAY-09:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1352.36 | 0.00 | 01-JAN-00:10 | 161065.58 | 02-OCT-13:40 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1352.36 | 0.00 | 01-JAN-00:10 | 161065.58 | 02-OCT-13:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1352.36 | 0.00 | 01-JAN-00:10 | 161065.58 | 02-OCT-13:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 893.29 | 0.00 | 01-JAN-00:10 | 135111.42 | 06-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 893.29 | 0.00 | 01-JAN-00:10 | 135111.42 | 06-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 893.29 | 0.00 | 01-JAN-00:10 | 135111.42 | 06-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 105.91 | 0.00 | 01-JAN-00:10 | 14153.28 | 12-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 0.83 | 0.00 | 01-JAN-00:10 | 11536.76 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 0.83 | 0.00 | 01-JAN-00:10 | 11536.76 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 105.09 | 0.00 | 01-JAN-00:10 | 14153.28 | 12-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 105.09 | 0.00 | 01-JAN-00:10 | 14153.28 | 12-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 88.22 | 0.00 | 01-JAN-00:10 | 13460.91 | 12-JUN-09:40 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.30 | 0.00 | 01-JAN-00:10 | 7203.88 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.30 | 0.00 | 01-JAN-00:10 | 7203.88 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 87.92 | 0.00 | 01-JAN-00:10 | 13460.91 | 12-JUN-09:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 87.92 | 0.00 | 01-JAN-00:10 | 13460.91 | 12-JUN-09:40 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 140.89 | 0.00 | 01-JAN-00:10 | 18275.35 | 02-OCT-13:40 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.19 | 0.00 | 01-JAN-00:10 | 8843.13 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.19 | 0.00 | 01-JAN-00:10 | 8843.13 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 140.70 | 0.00 | 01-JAN-00:10 | 18275.35 | 02-OCT-13:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 140.70 | 0.00 | 01-JAN-00:10 | 18275.35 | 02-OCT-13:40 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 94.91 | 0.00 | 01-JAN-00:10 | 14931.82 | 06-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.18 | 0.00 | 01-JAN-00:10 | 5550.30 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.18 | 0.00 | 01-JAN-00:10 | 5550.30 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 94.73 | 0.00 | 01-JAN-00:10 | 14931.82 | 06-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 94.73 | 0.00 | 01-JAN-00:10 | 14931.82 | 06-JUN-16:00 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 115.27 | 0.00 | 01-JAN-00:10 | 14968.19 | 07-AUG-05:20 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 0.84 | 0.00 | 01-JAN-00:10 | 3632.26 | 24-DEC-11:00 |
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 0.84 | 0.00 | 01-JAN-00:10 | 3632.26 | 24-DEC-11:00 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 114.43 | 0.00 | 01-JAN-00:10 | 14968.19 | 07-AUG-05:20 |
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 114.43 | 0.00 | 01-JAN-00:10 | 14968.19 | 07-AUG-05:20 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 872.87 | 0.00 | 01-JAN-00:10 | 96427.67 | 05-JUL-12:10 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 5.36 | 0.00 | 01-JAN-00:10 | 20984.97 | 24-DEC-11:30 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 5.36 | 0.00 | 01-JAN-00:10 | 20984.97 | 24-DEC-11:30 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 867.51 | 0.00 | 01-JAN-00:10 | 96427.67 | 05-JUL-12:10 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 867.51 | 0.00 | 01-JAN-00:10 | 96427.67 | 05-JUL-12:10 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 159.71 | 0.00 | 01-JAN-00:10 | 30910.08 | 12-JUN-13:50 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 6.21 | 0.00 | 01-JAN-00:10 | 14931.28 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 6.21 | 0.00 | 01-JAN-00:10 | 14931.28 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 153.49 | 0.00 | 01-JAN-00:10 | 30910.08 | 12-JUN-13:50 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 153.49 | 0.00 | 01-JAN-00:10 | 30910.08 | 12-JUN-13:50 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 142.87 | 1159.82 | 07-JAN-08:00 | 7744.34 | 17-APR-02:00 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 142.87 | 1159.82 | 07-JAN-08:00 | 7744.34 | 17-APR-02:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 142.87 | 1159.82 | 07-JAN-08:00 | 7744.34 | 17-APR-02:00 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1326.17 | 5632.01 | 01-JAN-07:50 | 72442.37 | 12-APR-16:00 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1326.17 | 5632.01 | 01-JAN-07:50 | 72442.37 | 12-APR-16:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1326.17 | 5632.01 | 01-JAN-07:50 | 72442.37 | 12-APR-16:00 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 129.71 | 0.04 | 04-JAN-03:40 | 7449.43 | 16-APR-21:20 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.07 | 0.00 | 02-JAN-11:40 | 324.86 | 01-JAN-14:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.07 | 0.00 | 02-JAN-11:40 | 324.86 | 01-JAN-14:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 129.64 | 0.00 | 01-JAN-00:10 | 7449.43 | 16-APR-21:20 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 129.64 | 0.00 | 01-JAN-00:10 | 7449.43 | 16-APR-21:20 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7176.17 | 88468.31 | 14-MAY-02:10 | 369494.56 | 15-AUG-24:00 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7176.17 | 88468.31 | 14-MAY-02:10 | 369494.56 | 15-AUG-24:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7176.17 | 88468.31 | 14-MAY-02:10 | 369494.56 | 15-AUG-24:00 |
PlantLoopHeatingDemand:Facility | 305.42 | 0.00 | 01-JAN-00:10 | 181284.13 | 02-JAN-06:20 |
PlantLoopHeatingDemand:Plant | 293.17 | 0.00 | 01-JAN-00:10 | 40154.54 | 17-JAN-12:10 |
WaterSystems:PlantLoopHeatingDemand | 293.17 | 0.00 | 01-JAN-00:10 | 40154.54 | 17-JAN-12:10 |
General:WaterSystems:PlantLoopHeatingDemand | 293.17 | 0.00 | 01-JAN-00:10 | 40154.54 | 17-JAN-12:10 |
EnergyTransfer:HVAC | 32024.57 | 132157.79 | 01-JAN-06:00 | 2907161.80 | 28-AUG-14:40 |
HeatingCoils:EnergyTransfer | 12.25 | 0.00 | 01-JAN-00:10 | 176369.99 | 02-JAN-06:20 |
PlantLoopHeatingDemand:HVAC | 12.25 | 0.00 | 01-JAN-00:10 | 176369.99 | 02-JAN-06:20 |
HeatingCoils:PlantLoopHeatingDemand | 12.25 | 0.00 | 01-JAN-00:10 | 176369.99 | 02-JAN-06:20 |
CoolingCoils:EnergyTransfer | 32012.32 | 132157.79 | 01-JAN-06:00 | 2907161.80 | 28-AUG-14:40 |
EnergyTransfer:Plant | 65785.52 | 0.00 | 01-JAN-00:10 | 7857828.05 | 22-JUN-15:40 |
LoopToLoop:EnergyTransfer | 22277.76 | 0.00 | 01-JAN-00:10 | 2476003.81 | 22-JUN-15:30 |
WaterSystems:EnergyTransfer | 293.17 | 0.00 | 01-JAN-00:10 | 40154.54 | 17-JAN-12:10 |
WaterUse:WaterSystems:EnergyTransfer | 293.17 | 0.00 | 01-JAN-00:10 | 40154.54 | 17-JAN-12:10 |
Boilers:EnergyTransfer | 11.98 | 0.00 | 01-JAN-00:10 | 165341.44 | 02-JAN-06:20 |
Chillers:EnergyTransfer | 20060.24 | 0.00 | 01-JAN-00:10 | 2487285.50 | 22-JUN-15:40 |
HeatRejection:EnergyTransfer | 23142.37 | 0.00 | 01-JAN-00:10 | 2875638.92 | 22-JUN-15:40 |
General:HeatRejection:EnergyTransfer | 23142.37 | 0.00 | 01-JAN-00:10 | 2875638.92 | 22-JUN-15:40 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:27
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 4.486 | -744.041 | 0.000 | 0.000 | 92.664 | 177.742 | 424.397 | 0.000 | 0.000 | 0.000 | 44.753 | 0.000 | 0.000 | 0.000 | 0.000 | -0.001 |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -763.720 | 0.000 | 0.000 | 83.423 | 159.625 | 321.286 | 0.000 | 0.000 | 0.000 | 199.387 | 0.000 | 0.000 | 0.000 | 0.000 | -0.002 |
CORE_MID | 0.000 | 0.000 | 0.000 | -5794.361 | 0.000 | 0.000 | 835.553 | 1596.246 | 3212.845 | 0.000 | 0.000 | 0.000 | 149.717 | 0.000 | 0.000 | 0.000 | 0.000 | -0.030 |
CORE_TOP | 0.000 | 0.000 | 0.244 | -596.192 | 0.000 | 0.000 | 84.309 | 159.625 | 321.285 | 0.000 | 0.000 | 0.000 | 30.731 | 0.000 | 0.000 | 0.000 | 0.000 | -0.001 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.000 | -120.582 | 0.000 | 0.000 | 10.500 | 13.776 | 40.342 | 42.201 | 0.000 | 0.626 | 34.779 | 0.000 | -21.277 | 0.000 | -0.365 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.000 | -90.000 | 0.000 | 0.000 | 6.762 | 8.870 | 25.998 | 50.214 | 0.000 | 0.422 | 10.918 | 0.000 | -12.942 | 0.000 | -0.242 | 0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 0.000 | -154.066 | 0.000 | 0.000 | 10.473 | 13.696 | 40.343 | 90.148 | 0.000 | 0.614 | 19.795 | 0.000 | -20.611 | 0.000 | -0.393 | -0.002 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.000 | -139.687 | 0.000 | 0.000 | 6.740 | 8.863 | 25.998 | 48.850 | 0.000 | 0.391 | 65.419 | 0.000 | -16.286 | 0.000 | -0.289 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 0.015 | -977.656 | 0.000 | 0.000 | 106.160 | 137.901 | 403.423 | 432.376 | 0.000 | 14.280 | 87.534 | 0.000 | -196.338 | 0.000 | -7.695 | 0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 0.001 | -818.803 | 0.000 | 0.000 | 49.929 | 88.733 | 259.981 | 501.648 | 0.000 | 9.329 | 40.798 | 0.000 | -126.123 | 0.000 | -5.492 | -0.013 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 0.000 | -1352.350 | 0.000 | 0.000 | 104.873 | 137.061 | 403.429 | 902.696 | 0.000 | 13.897 | 3.918 | 0.000 | -204.315 | 0.000 | -9.209 | -0.001 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 0.000 | -893.280 | 0.000 | 0.000 | 68.136 | 88.661 | 259.979 | 503.628 | 0.000 | 9.151 | 109.870 | 0.000 | -140.414 | 0.000 | -5.730 | -0.003 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 0.826 | -105.087 | 0.000 | 0.000 | 10.783 | 13.790 | 40.342 | 43.061 | 0.000 | 1.733 | 13.405 | 0.000 | -18.011 | 0.000 | -0.842 | -0.000 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 0.300 | -87.915 | 0.000 | 0.000 | 6.863 | 8.873 | 25.998 | 50.058 | 0.000 | 1.129 | 7.110 | 0.000 | -11.799 | 0.000 | -0.618 | -0.001 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 0.189 | -140.695 | 0.000 | 0.000 | 10.560 | 13.706 | 40.343 | 89.920 | 0.000 | 1.682 | 4.662 | 0.000 | -19.302 | 0.000 | -1.064 | -0.000 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 0.177 | -94.732 | 0.000 | 0.000 | 6.898 | 8.866 | 25.998 | 50.178 | 0.000 | 1.119 | 15.324 | 0.000 | -13.174 | 0.000 | -0.654 | -0.001 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.000 | -142.865 | 0.000 | 0.000 | 0.936 | 4.640 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -16.591 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 0.000 | -1326.176 | 0.000 | 0.000 | 9.380 | 46.396 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -268.406 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 0.067 | -129.645 | 0.000 | 0.000 | 0.942 | 4.640 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -29.884 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | 0.000 | 0.000 | -7176.183 | 0.000 | 0.000 | 19.434 | 50.116 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -388.223 |
GROUNDFLOOR_PLENUM | 0.843 | -114.428 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.176 | 113.216 | 0.000 | 0.000 | 0.000 | -0.808 | -0.000 |
MIDFLOOR_PLENUM | 5.361 | -867.503 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 21.362 | 854.615 | 0.000 | 0.000 | 0.000 | -13.834 | -0.000 |
TOPFLOOR_PLENUM | 6.212 | -153.491 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 2.197 | 146.456 | 0.000 | 0.000 | 0.000 | -1.375 | -0.001 |
Total Facility | 12.416 | -1135.422 | 6.305 | -21648.036 | 0.000 | 0.000 | 1525.316 | 2741.824 | 15213.411 | 2804.978 | 0.000 | 79.107 | 1952.407 | 0.000 | -800.592 | 0.000 | -48.611 | -703.160 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 06-FEB-04:03 | 0.00 | 0.00 | 0.00 | -100510.50 | 0.00 | 0.00 | 0.00 | 862.23 | 13457.54 | 0.00 | 0.00 | 0.00 | 86190.73 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 02-JAN-04:02 | 0.00 | 0.00 | 0.00 | -94134.29 | 0.00 | 0.00 | 0.00 | 774.34 | 8057.15 | 0.00 | 0.00 | 0.00 | 85302.80 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 27-FEB-04:02 | 0.00 | 0.00 | 0.00 | -845701.94 | 0.00 | 0.00 | 0.00 | 7743.41 | 80571.20 | 0.00 | 0.00 | 0.00 | 757387.34 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 12-JUN-05:02 | 0.00 | 0.00 | 0.00 | -86985.00 | 0.00 | 0.00 | 808.43 | 1548.68 | 8057.12 | 0.00 | 0.00 | 0.00 | 76570.77 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 02-JUL-17:01 | 0.00 | 0.00 | 0.00 | -20860.56 | 0.00 | 0.00 | 0.00 | 59.73 | 758.77 | 5112.85 | 0.00 | 163.31 | 14765.90 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 07-MAY-09:11 | 0.00 | 0.00 | 0.00 | -16989.09 | 0.00 | 0.00 | 22.40 | 38.49 | 488.98 | 11040.75 | 0.00 | 97.54 | 5300.93 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 01-OCT-13:11 | 0.00 | 0.00 | 0.00 | -22454.51 | 0.00 | 0.00 | 34.11 | 59.73 | 758.78 | 14693.55 | 0.00 | 67.11 | 6841.22 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 02-JUL-16:21 | 0.00 | 0.00 | 0.00 | -24089.81 | 0.00 | 0.00 | 17.84 | 38.49 | 488.98 | 10400.03 | 0.00 | 96.50 | 13047.98 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 28-MAY-16:41 | 0.00 | 0.00 | 0.00 | -194137.11 | 0.00 | 0.00 | 388.21 | 597.26 | 7587.73 | 51511.90 | 0.00 | 11688.26 | 122363.75 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 28-MAY-09:21 | 0.00 | 0.00 | 0.00 | -179963.44 | 0.00 | 0.00 | 213.14 | 384.90 | 4889.82 | 111412.28 | 0.00 | 1957.19 | 61106.11 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 01-OCT-13:11 | 0.00 | 0.00 | 0.00 | -220219.11 | 0.00 | 0.00 | 330.54 | 597.27 | 7587.84 | 146026.92 | 0.00 | 1489.61 | 64186.92 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 28-MAY-16:01 | 0.00 | 0.00 | 0.00 | -189865.75 | 0.00 | 0.00 | 177.88 | 384.90 | 4889.79 | 124372.39 | 0.00 | 7654.55 | 52386.25 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 28-MAY-16:11 | 0.00 | 0.00 | 0.00 | -23072.64 | 0.00 | 0.00 | 35.40 | 59.73 | 758.77 | 5028.54 | 0.00 | 1514.13 | 15676.07 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 07-MAY-09:51 | 0.00 | 0.00 | 0.00 | -19383.99 | 0.00 | 0.00 | 20.26 | 38.49 | 488.98 | 9600.21 | 0.00 | 278.65 | 8957.40 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 22-OCT-13:52 | 0.00 | 0.00 | 0.00 | -25032.96 | 0.00 | 0.00 | 34.33 | 59.73 | 758.78 | 12764.41 | 0.00 | 59.32 | 11356.39 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 28-MAY-16:11 | 0.00 | 0.00 | 0.00 | -21507.90 | 0.00 | 0.00 | 15.54 | 38.49 | 488.98 | 12141.13 | 0.00 | 925.03 | 7898.72 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 17-APR-01:55 | 0.00 | 0.00 | 0.00 | -7748.03 | 0.00 | 0.00 | 0.00 | 22.51 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -68.90 |
DATACENTER_MID_ZN_6 | 12-APR-16:00 | 0.00 | 0.00 | 0.00 | -72437.66 | 0.00 | 0.00 | 985.53 | 4051.03 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -10543.13 |
DATACENTER_TOP_ZN_6 | 16-APR-21:32 | 0.00 | 0.00 | 0.00 | -7463.58 | 0.00 | 0.00 | 0.00 | 22.51 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -353.35 |
DATACENTER_BASEMENT_ZN_6 | 15-AUG-23:53 | 0.00 | 0.00 | 0.00 | -369673.07 | 0.00 | 0.00 | 0.00 | 243.11 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -10202.57 |
GROUNDFLOOR_PLENUM | 05-JUL-05:15 | 0.00 | -18069.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.49 | 18013.96 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 05-SEP-05:15 | 0.00 | -115675.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.81 | 115632.95 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 12-JUN-13:50 | 0.00 | -30910.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 367.34 | 30543.33 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 17-APR-05:02 | 0.00 | -77674.29 | 0.00 | -2073908.18 | 0.00 | 0.00 | 15633.57 | 29009.37 | 623236.89 | 0.00 | 0.00 | 0.00 | 1516786.30 | 0.00 | -33078.85 | 0.00 | -4.82 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 10-JUN-16:01 | 0.00 | 0.00 | 35206.82 | 0.00 | 0.00 | 0.00 | 520.12 | 862.23 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -50046.71 |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 02-JAN-05:01 | 0.00 | 0.00 | 61366.80 | 0.00 | 0.00 | 0.00 | 0.00 | 1548.68 | 8057.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -70972.61 |
PERIMETER_BOT_ZN_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 02-JAN-06:01 | 0.00 | 0.00 | 37218.17 | 0.00 | 0.00 | 0.00 | 1405.93 | 1944.52 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -31742.49 | 0.00 | 0.00 | -18943.11 |
PERIMETER_MID_ZN_2 | 03-JAN-06:05 | 0.00 | 0.00 | 4590.90 | 0.00 | 0.00 | 0.00 | 889.30 | 1253.13 | 6519.76 | 0.00 | 0.00 | 0.00 | 9916.65 | 0.00 | -23056.35 | 0.00 | -113.39 | 0.00 |
PERIMETER_MID_ZN_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 02-JAN-04:02 | 0.00 | 0.00 | 16865.17 | 0.00 | 0.00 | 0.00 | 0.00 | 97.23 | 1011.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2262.07 | 0.00 | 0.00 | -15712.03 |
PERIMETER_TOP_ZN_2 | 02-JAN-04:02 | 0.00 | 0.00 | 11587.32 | 0.00 | 0.00 | 0.00 | 0.00 | 62.66 | 651.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1547.40 | 0.00 | 0.00 | -10754.56 |
PERIMETER_TOP_ZN_1 | 02-JAN-05:01 | 0.00 | 0.00 | 16202.83 | 0.00 | 0.00 | 0.00 | 0.00 | 194.46 | 1011.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2545.23 | 0.00 | 0.00 | -14863.77 |
PERIMETER_TOP_ZN_4 | 02-JAN-05:01 | 0.00 | 0.00 | 11193.67 | 0.00 | 0.00 | 0.00 | 0.00 | 125.31 | 651.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1705.48 | 0.00 | 0.00 | -10265.48 |
DATACENTER_BOT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 01-JAN-14:00 | 0.00 | 0.00 | 331.77 | 0.00 | 0.00 | 0.00 | 6.24 | 22.51 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2309.12 |
DATACENTER_BASEMENT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 11-DEC-04:02 | 11259.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -11259.34 |
MIDFLOOR_PLENUM | 11-SEP-03:02 | 91186.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -91186.58 |
TOPFLOOR_PLENUM | 02-JAN-06:13 | 19540.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -19540.64 |
Total Facility | 02-JAN-06:01 | -1003619.82 | 1087924.83 | 145399.07 | -1087924.83 | 0.00 | 0.00 | 17732.50 | 29009.37 | 268362.69 | 0.00 | 0.00 | 0.00 | 672716.04 | 0.00 | -129599.85 | 0.00 | 0.00 | 0.00 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:27
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 10.4423 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 9.8089 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 98.9705 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 92.7873 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 10.7171 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 10.5896 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 5.5681 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 5.5681 | 0.2155 | 1.0000 | Not calculated | 1.2002 | 0.2155 | ||
AIRLOOP DATACENTER BASEMENT | 21.9002 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 21.9005 | 0.0155 | 1.0000 | Not calculated | 0.3384 | 0.0155 | ||
AIRLOOP DATACENTER BOT | 0.4830 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4830 | 0.0324 | 1.0000 | Not calculated | 0.0156 | 0.0324 | ||
AIRLOOP DATACENTER MID | 4.6006 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.6006 | 0.0340 | 1.0000 | Not calculated | 0.1563 | 0.0340 | ||
AIRLOOP DATACENTER TOP | 0.4633 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4633 | 0.0337 | 1.0000 | Not calculated | 0.0156 | 0.0337 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 5.2212 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.8519 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 49.4853 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 27.8415 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 5.3585 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.9516 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 5.5681 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 5.5681 | 1.0000 | 1.0000 | Not calculated | 1.2002 | 0.2155 | ||
AIRLOOP DATACENTER BASEMENT | 21.9002 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 21.9002 | 1.0000 | 1.0000 | Not calculated | 0.3384 | 0.0155 | ||
AIRLOOP DATACENTER BOT | 0.4830 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4830 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0324 | ||
AIRLOOP DATACENTER MID | 4.6006 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.6006 | 1.0000 | 1.0000 | Not calculated | 0.1563 | 0.0340 | ||
AIRLOOP DATACENTER TOP | 0.4633 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4633 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0337 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.000000 | 149.6021 | 0.000432 | 2779.43 | 1.2002 | 1.0000 | 1.2002 | 1.000 | 1.2002 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.000000 | 19.4861 | 0.000432 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.1814 | 0.000432 | 783.68 | 0.3384 | 1.0000 | 0.3384 | 1.000 | 0.3384 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
CAV_BAS | 0.000000 | 149.60 | 0.000432 | 2779.4266 | 1.2002 | 1.2002 | 1.2002 |
AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.18 | 0.000432 | 783.6794 | 0.3384 | 0.3384 | 0.3384 |
AIRLOOP DATACENTER BOT | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AIRLOOP DATACENTER MID | 0.000000 | 19.49 | 0.000432 | 362.0274 | 0.1563 | 0.1563 | 0.1563 |
AIRLOOP DATACENTER TOP | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.5681 | 5.5681 | 5.5681 | No | 1.2002 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.9465 | 5.9465 | 1.9385 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 56.3298 | 56.3298 | 19.0958 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.8562 | 5.8562 | 1.9794 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1743 | 1.1743 | 0.2443 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9202 | 0.9202 | 0.1840 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1954 | 1.1954 | 0.2439 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2060 | 1.2060 | 0.2412 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 11.4022 | 11.4022 | 2.3945 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 9.5283 | 9.5283 | 1.9057 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 11.5045 | 11.5045 | 2.4045 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 10.2056 | 10.2056 | 2.0411 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3417 | 1.3417 | 0.2683 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0210 | 1.0210 | 0.2042 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3443 | 1.3443 | 0.2689 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1538 | 1.1538 | 0.2308 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4830 | 0.4830 | 0.4830 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.6006 | 4.6006 | 4.6006 | No | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4633 | 0.4633 | 0.4633 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 21.9002 | 21.9002 | 21.9002 | No | 0.3384 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 10.4423 | 9.8089 | 10.4423 | 2.8519 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 98.9705 | 92.7873 | 98.9705 | 27.8415 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 10.7171 | 10.5896 | 10.7171 | 2.9516 | 0.0000 | 1.0000 |
CAV_BAS | 5.5681 | 5.5681 | 5.5681 | 5.5681 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.9002 | 21.9005 | 21.9002 | 21.9002 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4830 | 0.4830 | 0.4830 | 0.4830 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.6006 | 4.6006 | 4.6006 | 4.6006 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4633 | 0.4633 | 0.4633 | 0.4633 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.5681 | 5.5681 | 5.5681 | No | 1.2002 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.9732 | 2.9732 | 1.9385 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 28.1649 | 28.1649 | 19.0958 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.9281 | 2.9281 | 1.9794 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5871 | 0.5871 | 0.2443 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4601 | 0.4601 | 0.1840 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5977 | 0.5977 | 0.2439 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6030 | 0.6030 | 0.2412 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.7011 | 5.7011 | 2.3945 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.7642 | 4.7642 | 1.9057 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.7523 | 5.7523 | 2.4045 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.1028 | 5.1028 | 2.0411 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6708 | 0.6708 | 0.2683 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5105 | 0.5105 | 0.2042 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6722 | 0.6722 | 0.2689 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5769 | 0.5769 | 0.2308 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4830 | 0.4830 | 0.4830 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.6006 | 4.6006 | 4.6006 | No | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4633 | 0.4633 | 0.4633 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 21.9002 | 21.9002 | 21.9002 | No | 0.3384 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 5.2212 | 2.8519 | 2.8519 | 2.8519 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 49.4853 | 27.8415 | 27.8415 | 27.8415 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 5.3585 | 2.9516 | 2.9516 | 2.9516 | 0.0000 | 1.0000 |
CAV_BAS | 5.5681 | 5.5681 | 5.5681 | 5.5681 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.9002 | 21.9002 | 21.9002 | 21.9002 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4830 | 0.4830 | 0.4830 | 0.4830 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.6006 | 4.6006 | 4.6006 | 4.6006 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4633 | 0.4633 | 0.4633 | 0.4633 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:27
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 113.98 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 1100.00 |
Number of hours not met | 1100.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 18.27 | 217619.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 6499.17 | 571270.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 2741.82 | 254941.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 447.32 | 37611.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5871.99 | 320838.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 59.77 | 3723.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 1848.78 | 113101.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 5.83 | 376.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 2647.39 | 229329.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 1289.49 | 70858.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 1962.04 | 91812.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- General | 82.64 | 28639.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 559.56 | 72823.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 15213.41 | 32797.66 |
Natural Gas | 0.00 | 577.83 |
Additional | 0.00 | 0.00 |
Total | 15213.41 | 33375.49 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 59.19 |
Space Heating | 0.00 |
Space Cooling | 140.31 |
Fans (All) | 57.15 |
Service Water Heating | 0.00 |
Receptacle Equipment | 328.44 |
Miscellaneous (All) | 708.06 |
Subtotal | 708.06 |
Natural Gas [MJ/m2] | |
Space Heating | 0.39 |
Service Water Heating | 12.08 |
Miscellaneous (All) | 12.47 |
Subtotal | 12.47 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 8.22 |
Space Heating | 0.05 |
Space Cooling | 19.47 |
Fans (All) | 7.93 |
Service Water Heating | 1.68 |
Receptacle Equipment | 45.58 |
Miscellaneous | 17.07 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2393. | 8760. |
LTG_SCH_DATACENTER | 2921. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4487. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 1565. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:27
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 7493.50 | 1266.50 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8676.00 | 84.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8756.83 | 3.17 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8751.00 | 9.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8605.00 | 155.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8586.83 | 173.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8466.50 | 293.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 7576.67 | 1183.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8472.50 | 287.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8319.67 | 440.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8134.67 | 625.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 7893.33 | 866.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8379.33 | 380.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8251.67 | 508.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8095.83 | 664.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 7948.00 | 812.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 6102.67 | 2657.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 6085.50 | 2674.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 6708.67 | 2051.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 7279.67 | 1480.33 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8731.83 | 28.17 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8272.33 | 487.67 | 0.00 | 0.00 | 0.00 |
Min | 6085.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 2674.50 | 0.00 | 0.00 | 0.00 |
Average | 8015.13 | 744.87 | 0.00 | 0.00 | 0.00 |
Sum | 184348.00 | 17132.00 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 365235.00 | 3381.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330646.00 | 167.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330794.00 | 19.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330788.00 | 25.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 1347.67 | 920.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 1332.00 | 936.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 1488.00 | 780.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 81926.33 | 21468.67 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 365235.00 | 21468.67 | 0.00 | 0.00 | 0.00 |
Average | 79130.70 | 1204.22 | 0.00 | 0.00 | 0.00 |
Sum | 1820006.00 | 27697.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 5403.33 | 3356.67 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 7456.17 | 1303.83 | 0.00 | 0.00 | 0.00 |
CORE_MID | 7539.17 | 1220.83 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 7516.17 | 1243.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 6849.17 | 1910.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 7028.00 | 1732.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 6596.17 | 2163.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 6271.00 | 2489.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 6842.67 | 1917.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 6734.50 | 2025.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 6549.33 | 2210.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 6618.67 | 2141.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 6867.17 | 1892.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 6751.00 | 2009.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 6584.83 | 2175.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 6668.00 | 2092.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 7056.83 | 1703.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 7059.50 | 1700.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 7476.67 | 1283.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 7542.50 | 1217.50 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 6172.50 | 2587.50 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 5738.00 | 3022.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 4744.17 | 4015.83 | 0.00 | 0.00 | 0.00 |
Min | 4744.17 | 1217.50 | 0.00 | 0.00 | 0.00 |
Max | 7542.50 | 4015.83 | 0.00 | 0.00 | 0.00 |
Average | 6698.50 | 2061.50 | 0.00 | 0.00 | 0.00 |
Sum | 154065.50 | 47414.50 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 333368.00 | 35248.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 328306.83 | 2506.17 | 0.00 | 0.00 | 0.00 |
CORE_MID | 328578.17 | 2234.83 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 328356.17 | 2456.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38921.67 | 3.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18352.33 | 1.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38921.83 | 3.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24907.83 | 1.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38920.83 | 4.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24906.83 | 2.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38920.83 | 4.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24907.67 | 1.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 1640.00 | 628.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 1627.83 | 640.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 1771.00 | 497.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 87353.83 | 16041.17 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 333368.00 | 35248.00 | 0.00 | 0.00 | 0.00 |
Average | 77714.33 | 2620.58 | 0.00 | 0.00 | 0.00 |
Sum | 1787429.67 | 60273.33 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:27
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:27
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 4570.43 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 18354.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 38925.00 | 0.00 |
Average | 0.00 | 0.00 | 16367.35 | 0.00 |
Sum | 0.00 | 0.00 | 376449.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018
For: Environment
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Environment
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1B
For: Environment
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY IND_DELHI_NEWDELHI
For: Environment
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.392 |
February | 16.974 |
March | 22.368 |
April | 29.134 |
May | 32.978 |
June | 33.595 |
July | 31.671 |
August | 30.033 |
September | 28.750 |
October | 25.087 |
November | 19.629 |
December | 14.516 |
Annual Sum or Average | 24.876 |
Minimum of Months | 13.392 |
Maximum of Months | 33.595 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.576987E+11 | 97223.56 | 02-JAN-04:02 | 6.67 | 6.44 | 0.566885E+10 | 7499.04 | 04-JAN-10:20 | 13.03 | 10.49 |
February | 0.510626E+11 | 100508.93 | 06-FEB-04:03 | 10.55 | 9.45 | 0.514165E+10 | 7499.07 | 02-FEB-10:09 | 10.55 | 9.45 |
March | 0.585353E+11 | 95460.67 | 06-MAR-04:02 | 15.67 | 14.63 | 0.613458E+10 | 7499.00 | 16-MAR-09:00 | 19.90 | 15.14 |
April | 0.553139E+11 | 95547.30 | 28-APR-03:02 | 28.85 | 17.10 | 0.545167E+10 | 7499.02 | 04-APR-09:09 | 28.85 | 17.10 |
May | 0.585835E+11 | 94628.54 | 29-MAY-17:30 | 40.55 | 21.29 | 0.590305E+10 | 7498.86 | 04-MAY-13:20 | 40.55 | 21.29 |
June | 0.614247E+11 | 91765.23 | 05-JUN-03:02 | 30.82 | 20.05 | 0.588419E+10 | 7498.87 | 07-JUN-09:09 | 37.65 | 20.59 |
July | 0.657858E+11 | 85621.88 | 04-JUL-19:50 | 40.00 | 24.33 | 0.547682E+10 | 7498.76 | 28-JUL-09:20 | 28.17 | 25.73 |
August | 0.754103E+11 | 83004.63 | 22-AUG-03:02 | 25.88 | 25.10 | 0.614011E+10 | 7498.72 | 24-AUG-09:20 | 29.43 | 26.79 |
September | 0.651251E+11 | 84697.23 | 26-SEP-03:02 | 25.65 | 21.91 | 0.545546E+10 | 7498.75 | 15-SEP-13:20 | 25.65 | 21.91 |
October | 0.674804E+11 | 94666.66 | 29-OCT-13:32 | 29.23 | 17.90 | 0.567432E+10 | 7498.91 | 17-OCT-09:30 | 29.23 | 17.90 |
November | 0.649829E+11 | 99215.18 | 12-NOV-13:52 | 28.20 | 15.95 | 0.561814E+10 | 7498.95 | 09-NOV-10:09 | 28.20 | 15.95 |
December | 0.626420E+11 | 96467.72 | 26-DEC-04:03 | 10.20 | 8.99 | 0.547479E+10 | 7498.95 | 13-DEC-10:09 | 10.20 | 8.99 |
Annual Sum or Average | 0.744045E+12 | 0.680236E+11 | ||||||||
Minimum of Months | 0.510626E+11 | 83004.63 | 6.67 | 6.44 | 0.514165E+10 | 7498.72 | 10.20 | 8.99 | ||
Maximum of Months | 0.754103E+11 | 100508.93 | 40.55 | 25.10 | 0.614011E+10 | 7499.07 | 40.55 | 26.79 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.454920E+11 | 94247.69 | 02-JAN-04:02 | 6.67 | 6.44 | 0.508059E+10 | 6734.74 | 04-JAN-10:00 | 15.50 | 12.02 |
February | 0.474129E+11 | 93630.41 | 21-FEB-04:02 | 12.42 | 11.05 | 0.460628E+10 | 6734.76 | 02-FEB-10:09 | 12.42 | 11.05 |
March | 0.650079E+11 | 89662.57 | 21-MAR-03:02 | 14.88 | 11.76 | 0.549823E+10 | 6734.75 | 27-MAR-09:09 | 23.33 | 16.01 |
April | 0.720154E+11 | 86826.26 | 17-APR-05:05 | 24.22 | 18.83 | 0.487623E+10 | 6734.74 | 04-APR-09:09 | 24.22 | 18.83 |
May | 0.676663E+11 | 85761.14 | 01-MAY-05:02 | 32.45 | 19.07 | 0.528054E+10 | 6734.55 | 08-MAY-13:09 | 38.60 | 20.90 |
June | 0.691610E+11 | 85216.57 | 12-JUN-05:02 | 34.12 | 19.12 | 0.526504E+10 | 6734.56 | 12-JUN-13:09 | 43.40 | 22.40 |
July | 0.727014E+11 | 85751.65 | 10-JUL-05:05 | 30.80 | 25.35 | 0.489285E+10 | 6734.53 | 17-JUL-13:00 | 33.90 | 27.72 |
August | 0.813583E+11 | 84674.83 | 07-AUG-05:01 | 29.53 | 24.79 | 0.549482E+10 | 6734.54 | 07-AUG-09:09 | 32.20 | 25.23 |
September | 0.616902E+11 | 82935.09 | 11-SEP-03:02 | 26.07 | 25.28 | 0.488007E+10 | 6734.54 | 05-SEP-09:09 | 26.07 | 25.28 |
October | 0.649114E+11 | 90591.37 | 31-OCT-03:02 | 16.50 | 14.83 | 0.507705E+10 | 6734.66 | 24-OCT-09:09 | 16.50 | 14.83 |
November | 0.601806E+11 | 93854.23 | 24-NOV-04:02 | 11.00 | 9.68 | 0.503088E+10 | 6734.70 | 16-NOV-10:09 | 11.00 | 9.68 |
December | 0.561220E+11 | 93980.08 | 04-DEC-04:02 | 8.72 | 8.07 | 0.490322E+10 | 6734.72 | 18-DEC-10:00 | 21.70 | 14.67 |
Annual Sum or Average | 0.763719E+12 | 0.608858E+11 | ||||||||
Minimum of Months | 0.454920E+11 | 82935.09 | 6.67 | 6.44 | 0.460628E+10 | 6734.53 | 11.00 | 9.68 | ||
Maximum of Months | 0.813583E+11 | 94247.69 | 34.12 | 25.35 | 0.549823E+10 | 6734.76 | 43.40 | 27.72 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.348087E+11 | 80680.75 | 17-JAN-06:02 | 10.70 | 10.27 | 0.504312E+10 | 6734.71 | 04-JAN-10:00 | 10.70 | 10.27 |
February | 0.362009E+11 | 84600.87 | 27-FEB-04:02 | 11.72 | 10.91 | 0.458687E+10 | 6734.74 | 02-FEB-10:09 | 11.72 | 10.91 |
March | 0.491260E+11 | 81591.21 | 23-MAR-04:03 | 16.62 | 14.35 | 0.549288E+10 | 6734.75 | 27-MAR-09:09 | 23.33 | 16.01 |
April | 0.521247E+11 | 79594.66 | 13-APR-03:02 | 24.18 | 17.44 | 0.487335E+10 | 6734.74 | 04-APR-09:09 | 24.18 | 17.44 |
May | 0.581295E+11 | 75644.68 | 25-MAY-03:02 | 26.60 | 23.78 | 0.527550E+10 | 6734.60 | 01-MAY-09:20 | 26.60 | 23.78 |
June | 0.562357E+11 | 77374.93 | 21-JUN-03:02 | 28.25 | 23.92 | 0.526173E+10 | 6734.64 | 05-JUN-13:09 | 28.25 | 23.92 |
July | 0.549864E+11 | 77726.46 | 28-JUL-03:02 | 27.00 | 25.79 | 0.488690E+10 | 6734.56 | 18-JUL-13:09 | 27.00 | 25.79 |
August | 0.562502E+11 | 78401.83 | 17-AUG-03:02 | 27.35 | 25.43 | 0.549215E+10 | 6734.56 | 21-AUG-13:09 | 29.57 | 27.56 |
September | 0.501359E+11 | 80308.33 | 06-SEP-03:02 | 25.57 | 24.55 | 0.487896E+10 | 6734.56 | 11-SEP-13:09 | 31.10 | 27.02 |
October | 0.504335E+11 | 82936.58 | 24-OCT-03:02 | 18.57 | 14.45 | 0.507321E+10 | 6734.65 | 24-OCT-09:09 | 23.63 | 15.90 |
November | 0.439093E+11 | 81772.99 | 17-NOV-05:03 | 13.97 | 13.14 | 0.501878E+10 | 6734.70 | 06-NOV-10:09 | 13.97 | 13.14 |
December | 0.370963E+11 | 80223.21 | 27-DEC-06:02 | 10.88 | 9.54 | 0.486971E+10 | 6734.67 | 18-DEC-10:00 | 10.88 | 9.54 |
Annual Sum or Average | 0.579437E+12 | 0.607532E+11 | ||||||||
Minimum of Months | 0.348087E+11 | 75644.68 | 10.70 | 9.54 | 0.458687E+10 | 6734.56 | 10.70 | 9.54 | ||
Maximum of Months | 0.581295E+11 | 84600.87 | 28.25 | 25.79 | 0.549288E+10 | 6734.75 | 31.10 | 27.56 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.252649E+11 | 34277.53 | 26-JAN-16:20 | 19.67 | 13.02 | 0.467447E+10 | 6734.53 | 13-JAN-14:09 | 19.67 | 13.02 |
February | 0.300087E+11 | 79357.48 | 23-FEB-06:03 | 15.05 | 13.57 | 0.447724E+10 | 6734.62 | 15-FEB-10:09 | 15.05 | 13.57 |
March | 0.478751E+11 | 83715.24 | 15-MAR-04:03 | 18.62 | 15.11 | 0.547284E+10 | 6734.74 | 27-MAR-09:09 | 23.33 | 16.01 |
April | 0.582517E+11 | 83283.83 | 17-APR-05:03 | 24.22 | 18.83 | 0.487457E+10 | 6734.73 | 04-APR-09:09 | 24.22 | 18.83 |
May | 0.686688E+11 | 82830.27 | 25-MAY-03:02 | 26.60 | 23.78 | 0.528191E+10 | 6734.56 | 08-MAY-13:09 | 26.60 | 23.78 |
June | 0.672001E+11 | 86993.69 | 12-JUN-05:02 | 34.12 | 19.12 | 0.526712E+10 | 6734.62 | 12-JUN-13:09 | 43.40 | 22.40 |
July | 0.640474E+11 | 83995.34 | 28-JUL-03:02 | 27.00 | 25.79 | 0.489393E+10 | 6734.52 | 17-JUL-13:00 | 27.00 | 25.79 |
August | 0.637269E+11 | 84138.26 | 17-AUG-03:02 | 27.35 | 25.43 | 0.549580E+10 | 6734.53 | 21-AUG-13:00 | 28.90 | 27.65 |
September | 0.549793E+11 | 85558.99 | 11-SEP-03:02 | 26.07 | 25.28 | 0.488032E+10 | 6734.54 | 08-SEP-13:00 | 26.07 | 25.28 |
October | 0.505445E+11 | 84715.45 | 11-OCT-03:02 | 24.45 | 20.86 | 0.506305E+10 | 6734.64 | 17-OCT-09:20 | 26.63 | 18.34 |
November | 0.380705E+11 | 81204.55 | 09-NOV-06:02 | 17.53 | 15.94 | 0.496320E+10 | 6734.66 | 06-NOV-10:09 | 17.53 | 15.94 |
December | 0.275569E+11 | 69665.87 | 29-DEC-06:02 | 16.53 | 12.55 | 0.465534E+10 | 6734.59 | 29-DEC-10:09 | 18.00 | 13.36 |
Annual Sum or Average | 0.596195E+12 | 0.599998E+11 | ||||||||
Minimum of Months | 0.252649E+11 | 34277.53 | 15.05 | 12.55 | 0.447724E+10 | 6734.52 | 15.05 | 13.02 | ||
Maximum of Months | 0.686688E+11 | 86993.69 | 34.12 | 25.79 | 0.549580E+10 | 6734.74 | 43.40 | 27.65 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.392791E+10 | 4968.19 | 26-JAN-14:10 | 22.35 | 13.84 | 0.619610E+09 | 845.62 | 17-JAN-10:00 | 22.35 | 13.84 |
February | 0.491946E+10 | 6682.53 | 23-FEB-14:30 | 26.10 | 14.00 | 0.571659E+09 | 845.62 | 02-FEB-10:00 | 26.10 | 14.00 |
March | 0.881413E+10 | 13821.38 | 14-MAR-05:02 | 20.70 | 16.42 | 0.689502E+09 | 845.63 | 30-MAR-13:50 | 32.05 | 19.26 |
April | 0.124979E+11 | 19444.80 | 16-APR-15:41 | 39.37 | 22.61 | 0.613636E+09 | 845.63 | 04-APR-09:09 | 39.37 | 22.61 |
May | 0.140021E+11 | 19446.64 | 07-MAY-16:31 | 41.77 | 21.63 | 0.665359E+09 | 845.61 | 08-MAY-13:09 | 38.60 | 20.90 |
June | 0.146556E+11 | 19512.69 | 11-JUN-17:02 | 42.88 | 23.08 | 0.662950E+09 | 845.61 | 07-JUN-13:09 | 42.88 | 23.08 |
July | 0.144747E+11 | 20867.56 | 02-JUL-17:01 | 40.18 | 26.57 | 0.616784E+09 | 845.60 | 10-JUL-09:09 | 32.98 | 26.50 |
August | 0.150573E+11 | 18961.79 | 06-AUG-15:42 | 36.30 | 26.24 | 0.691492E+09 | 845.61 | 07-AUG-09:09 | 32.20 | 25.23 |
September | 0.107885E+11 | 19212.21 | 24-SEP-14:42 | 35.10 | 24.80 | 0.613973E+09 | 845.61 | 08-SEP-13:30 | 35.10 | 24.80 |
October | 0.953957E+10 | 17364.69 | 01-OCT-15:51 | 35.50 | 20.15 | 0.637691E+09 | 845.62 | 10-OCT-13:00 | 31.70 | 20.64 |
November | 0.680923E+10 | 8997.97 | 06-NOV-06:02 | 14.70 | 13.68 | 0.629307E+09 | 845.63 | 06-NOV-14:50 | 28.48 | 18.19 |
December | 0.509637E+10 | 5933.59 | 26-DEC-14:10 | 22.68 | 14.39 | 0.607185E+09 | 845.62 | 18-DEC-10:00 | 22.68 | 14.39 |
Annual Sum or Average | 0.120583E+12 | 0.761915E+10 | ||||||||
Minimum of Months | 0.392791E+10 | 4968.19 | 14.70 | 13.68 | 0.571659E+09 | 845.60 | 22.35 | 13.84 | ||
Maximum of Months | 0.150573E+11 | 20867.56 | 42.88 | 26.57 | 0.691492E+09 | 845.63 | 42.88 | 26.50 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.328112E+10 | 4453.37 | 26-JAN-10:20 | 18.10 | 12.94 | 0.404086E+09 | 544.95 | 04-JAN-10:00 | 18.10 | 12.94 |
February | 0.408230E+10 | 7146.13 | 21-FEB-09:40 | 18.10 | 12.98 | 0.369167E+09 | 544.95 | 02-FEB-10:09 | 18.10 | 12.98 |
March | 0.709092E+10 | 13235.84 | 12-MAR-09:53 | 25.90 | 17.17 | 0.444348E+09 | 544.96 | 27-MAR-09:20 | 23.77 | 16.23 |
April | 0.981976E+10 | 16685.30 | 16-APR-09:02 | 33.08 | 21.25 | 0.395522E+09 | 545.35 | 28-APR-09:50 | 33.47 | 18.33 |
May | 0.113152E+11 | 16990.34 | 07-MAY-09:11 | 34.60 | 20.48 | 0.429003E+09 | 545.24 | 26-MAY-09:00 | 35.60 | 21.80 |
June | 0.106140E+11 | 15610.86 | 11-JUN-09:42 | 36.22 | 25.04 | 0.427165E+09 | 545.32 | 12-JUN-09:39 | 39.50 | 22.03 |
July | 0.975500E+10 | 16213.54 | 02-JUL-15:41 | 40.33 | 26.36 | 0.397258E+09 | 545.08 | 07-JUL-09:00 | 36.90 | 24.55 |
August | 0.950138E+10 | 12964.53 | 07-AUG-05:01 | 29.53 | 24.79 | 0.445222E+09 | 545.02 | 07-AUG-09:00 | 33.20 | 25.77 |
September | 0.797521E+10 | 15173.92 | 24-SEP-14:42 | 35.10 | 24.80 | 0.395627E+09 | 544.94 | 08-SEP-13:30 | 35.10 | 24.80 |
October | 0.746545E+10 | 15922.26 | 01-OCT-09:52 | 29.70 | 19.34 | 0.411170E+09 | 545.26 | 02-OCT-09:20 | 30.57 | 20.21 |
November | 0.531285E+10 | 6736.27 | 13-NOV-09:40 | 21.37 | 14.10 | 0.405448E+09 | 544.96 | 06-NOV-14:50 | 21.37 | 14.10 |
December | 0.378736E+10 | 4963.54 | 01-DEC-09:40 | 17.67 | 11.19 | 0.390993E+09 | 544.95 | 18-DEC-10:00 | 21.70 | 14.67 |
Annual Sum or Average | 0.900005E+11 | 0.491501E+10 | ||||||||
Minimum of Months | 0.328112E+10 | 4453.37 | 17.67 | 11.19 | 0.369167E+09 | 544.94 | 18.10 | 12.94 | ||
Maximum of Months | 0.113152E+11 | 16990.34 | 40.33 | 26.36 | 0.445222E+09 | 545.35 | 39.50 | 25.77 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.753033E+10 | 14671.94 | 08-JAN-14:23 | 22.60 | 13.48 | 0.629081E+09 | 845.88 | 12-JAN-14:20 | 23.40 | 14.05 |
February | 0.854754E+10 | 20491.31 | 19-FEB-14:13 | 25.47 | 14.26 | 0.575339E+09 | 846.09 | 07-FEB-14:50 | 25.47 | 14.26 |
March | 0.129485E+11 | 21190.03 | 12-MAR-13:12 | 30.87 | 19.14 | 0.690972E+09 | 846.05 | 08-MAR-14:00 | 30.87 | 19.14 |
April | 0.150210E+11 | 20457.00 | 16-APR-15:01 | 39.63 | 22.37 | 0.614291E+09 | 845.96 | 12-APR-13:00 | 39.63 | 22.37 |
May | 0.146427E+11 | 19971.29 | 07-MAY-15:11 | 42.37 | 21.49 | 0.665528E+09 | 846.01 | 30-MAY-13:20 | 39.27 | 24.02 |
June | 0.146094E+11 | 19798.19 | 11-JUN-16:22 | 43.25 | 23.12 | 0.662976E+09 | 845.93 | 12-JUN-13:20 | 43.50 | 22.39 |
July | 0.145409E+11 | 21177.55 | 02-JUL-16:21 | 40.35 | 26.46 | 0.616812E+09 | 845.89 | 05-JUL-13:20 | 37.90 | 25.56 |
August | 0.156042E+11 | 20003.67 | 06-AUG-14:22 | 36.10 | 26.31 | 0.691632E+09 | 846.24 | 09-AUG-13:20 | 34.53 | 26.23 |
September | 0.129914E+11 | 21061.96 | 24-SEP-14:42 | 35.10 | 24.80 | 0.614469E+09 | 846.00 | 19-SEP-13:00 | 35.10 | 24.80 |
October | 0.150391E+11 | 22454.27 | 01-OCT-13:11 | 35.43 | 19.93 | 0.639986E+09 | 874.22 | 02-OCT-13:30 | 36.30 | 21.12 |
November | 0.131785E+11 | 21450.98 | 23-NOV-12:52 | 25.80 | 14.32 | 0.632641E+09 | 851.20 | 27-NOV-14:09 | 26.35 | 13.94 |
December | 0.941301E+10 | 20837.28 | 03-DEC-12:43 | 23.78 | 14.19 | 0.612585E+09 | 846.18 | 04-DEC-14:00 | 23.20 | 14.27 |
Annual Sum or Average | 0.154067E+12 | 0.764631E+10 | ||||||||
Minimum of Months | 0.753033E+10 | 14671.94 | 22.60 | 13.48 | 0.575339E+09 | 845.88 | 23.20 | 13.94 | ||
Maximum of Months | 0.156042E+11 | 22454.27 | 43.25 | 26.46 | 0.691632E+09 | 874.22 | 43.50 | 26.23 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.473417E+10 | 8480.49 | 14-JAN-06:02 | 14.50 | 12.49 | 0.405205E+09 | 544.95 | 17-JAN-10:00 | 14.40 | 13.62 |
February | 0.627337E+10 | 17406.44 | 19-FEB-16:12 | 25.17 | 13.60 | 0.372553E+09 | 544.95 | 02-FEB-10:09 | 25.17 | 13.60 |
March | 0.115387E+11 | 21070.60 | 26-MAR-14:42 | 30.37 | 16.76 | 0.446184E+09 | 544.97 | 30-MAR-13:50 | 32.05 | 19.26 |
April | 0.168288E+11 | 22159.83 | 30-APR-16:21 | 37.45 | 18.00 | 0.396833E+09 | 544.96 | 04-APR-09:09 | 37.45 | 18.00 |
May | 0.139290E+11 | 21518.67 | 07-MAY-15:51 | 42.30 | 21.45 | 0.429333E+09 | 544.94 | 05-MAY-09:00 | 42.30 | 21.45 |
June | 0.149745E+11 | 21554.30 | 04-JUN-15:51 | 42.30 | 22.20 | 0.427837E+09 | 544.95 | 07-JUN-13:09 | 43.15 | 21.81 |
July | 0.149320E+11 | 24103.34 | 02-JUL-16:21 | 40.35 | 26.46 | 0.398216E+09 | 544.94 | 10-JUL-09:09 | 32.98 | 26.50 |
August | 0.178526E+11 | 21609.99 | 06-AUG-15:42 | 36.30 | 26.24 | 0.446629E+09 | 544.95 | 07-AUG-09:09 | 32.20 | 25.23 |
September | 0.106089E+11 | 21299.59 | 24-SEP-14:42 | 35.10 | 24.80 | 0.396230E+09 | 544.94 | 08-SEP-13:30 | 35.10 | 24.80 |
October | 0.109045E+11 | 22307.67 | 01-OCT-15:11 | 35.83 | 20.00 | 0.412306E+09 | 544.95 | 10-OCT-13:00 | 31.70 | 20.64 |
November | 0.922537E+10 | 20184.25 | 23-NOV-14:12 | 25.47 | 14.21 | 0.408170E+09 | 544.97 | 06-NOV-14:50 | 25.47 | 14.21 |
December | 0.788505E+10 | 18231.40 | 24-DEC-15:32 | 23.13 | 13.76 | 0.397499E+09 | 544.95 | 18-DEC-10:00 | 23.13 | 13.76 |
Annual Sum or Average | 0.139687E+12 | 0.493699E+10 | ||||||||
Minimum of Months | 0.473417E+10 | 8480.49 | 14.50 | 12.49 | 0.372553E+09 | 544.94 | 14.40 | 13.60 | ||
Maximum of Months | 0.178526E+11 | 24103.34 | 42.30 | 26.46 | 0.446629E+09 | 544.97 | 43.15 | 26.50 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.282036E+10 | 3666.53 | 26-JAN-14:30 | 22.05 | 13.77 | 0.573456E+09 | 845.61 | 13-JAN-14:09 | 22.05 | 13.77 |
February | 0.349790E+10 | 5606.67 | 24-FEB-15:00 | 26.40 | 17.38 | 0.552553E+09 | 845.61 | 09-FEB-14:09 | 26.40 | 17.38 |
March | 0.653020E+10 | 13820.12 | 14-MAR-05:02 | 20.70 | 16.42 | 0.685644E+09 | 845.63 | 30-MAR-13:50 | 32.05 | 19.26 |
April | 0.982985E+10 | 14864.95 | 28-APR-05:02 | 27.22 | 17.16 | 0.613600E+09 | 845.63 | 04-APR-09:09 | 27.22 | 17.16 |
May | 0.132016E+11 | 19413.51 | 28-MAY-16:41 | 41.80 | 19.54 | 0.665498E+09 | 845.61 | 01-MAY-09:20 | 41.80 | 19.54 |
June | 0.132471E+11 | 18920.92 | 11-JUN-17:02 | 42.88 | 23.08 | 0.663130E+09 | 845.70 | 12-JUN-13:00 | 43.90 | 22.36 |
July | 0.122250E+11 | 18880.01 | 02-JUL-16:32 | 40.33 | 26.50 | 0.617010E+09 | 845.60 | 06-JUL-09:20 | 35.40 | 25.87 |
August | 0.117068E+11 | 17268.53 | 02-AUG-03:02 | 28.98 | 24.83 | 0.691692E+09 | 845.60 | 28-AUG-09:09 | 30.88 | 27.50 |
September | 0.934946E+10 | 18740.12 | 24-SEP-14:42 | 35.10 | 24.80 | 0.614223E+09 | 845.60 | 08-SEP-13:30 | 35.10 | 24.80 |
October | 0.753789E+10 | 14289.53 | 12-OCT-05:02 | 21.05 | 20.47 | 0.636564E+09 | 845.61 | 16-OCT-09:09 | 26.53 | 17.36 |
November | 0.471232E+10 | 5931.09 | 09-NOV-14:30 | 29.30 | 17.79 | 0.619969E+09 | 845.62 | 06-NOV-14:00 | 29.30 | 17.79 |
December | 0.310804E+10 | 3555.20 | 28-DEC-15:00 | 24.50 | 15.39 | 0.570008E+09 | 845.61 | 29-DEC-14:09 | 19.75 | 14.80 |
Annual Sum or Average | 0.977666E+11 | 0.750334E+10 | ||||||||
Minimum of Months | 0.282036E+10 | 3555.20 | 20.70 | 13.77 | 0.552553E+09 | 845.60 | 19.75 | 13.77 | ||
Maximum of Months | 0.132471E+11 | 19413.51 | 42.88 | 26.50 | 0.691692E+09 | 845.70 | 43.90 | 27.50 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.251318E+10 | 3524.92 | 26-JAN-10:00 | 17.30 | 12.76 | 0.283747E+09 | 521.20 | 13-JAN-11:20 | 17.30 | 12.76 |
February | 0.335076E+10 | 6241.44 | 22-FEB-10:00 | 20.60 | 13.92 | 0.266365E+09 | 521.21 | 15-FEB-11:20 | 20.60 | 13.92 |
March | 0.626307E+10 | 11230.52 | 12-MAR-09:23 | 24.75 | 16.87 | 0.325742E+09 | 521.22 | 16-MAR-10:20 | 20.53 | 15.55 |
April | 0.922490E+10 | 16467.59 | 16-APR-09:52 | 35.00 | 21.64 | 0.291845E+09 | 521.78 | 14-APR-10:50 | 35.00 | 21.64 |
May | 0.113648E+11 | 17994.83 | 28-MAY-09:21 | 35.35 | 19.88 | 0.316031E+09 | 521.74 | 19-MAY-10:00 | 35.35 | 19.88 |
June | 0.103295E+11 | 16318.97 | 04-JUN-10:43 | 36.87 | 21.80 | 0.314328E+09 | 521.68 | 12-JUN-10:00 | 41.40 | 22.35 |
July | 0.903128E+10 | 16232.01 | 04-JUL-10:02 | 35.40 | 25.09 | 0.293436E+09 | 521.60 | 06-JUL-10:00 | 37.80 | 25.49 |
August | 0.853623E+10 | 13615.72 | 07-AUG-05:03 | 29.53 | 24.79 | 0.327718E+09 | 521.20 | 21-AUG-12:09 | 30.20 | 27.51 |
September | 0.739941E+10 | 15903.65 | 24-SEP-14:42 | 35.10 | 24.80 | 0.291682E+09 | 521.20 | 29-SEP-14:20 | 33.83 | 22.63 |
October | 0.672127E+10 | 16716.65 | 01-OCT-09:52 | 29.70 | 19.34 | 0.302912E+09 | 521.22 | 10-OCT-14:20 | 31.63 | 20.81 |
November | 0.440326E+10 | 6198.50 | 09-NOV-10:00 | 24.50 | 17.90 | 0.296308E+09 | 521.21 | 06-NOV-15:20 | 24.50 | 17.90 |
December | 0.274320E+10 | 4156.04 | 01-DEC-10:00 | 18.30 | 11.37 | 0.278697E+09 | 521.21 | 18-DEC-11:20 | 22.00 | 14.81 |
Annual Sum or Average | 0.818809E+11 | 0.358881E+10 | ||||||||
Minimum of Months | 0.251318E+10 | 3524.92 | 17.30 | 11.37 | 0.266365E+09 | 521.20 | 17.30 | 12.76 | ||
Maximum of Months | 0.113648E+11 | 17994.83 | 36.87 | 25.09 | 0.327718E+09 | 521.78 | 41.40 | 27.51 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.701979E+10 | 17581.65 | 08-JAN-14:23 | 22.60 | 13.48 | 0.623528E+09 | 845.85 | 12-JAN-14:00 | 23.60 | 14.20 |
February | 0.759379E+10 | 20020.60 | 20-FEB-12:23 | 25.20 | 13.29 | 0.571308E+09 | 845.99 | 07-FEB-14:00 | 25.20 | 13.29 |
March | 0.111652E+11 | 19973.64 | 26-MAR-13:32 | 30.07 | 16.56 | 0.690064E+09 | 848.37 | 30-MAR-13:50 | 32.05 | 19.26 |
April | 0.125445E+11 | 20027.83 | 16-APR-12:32 | 38.80 | 21.93 | 0.614559E+09 | 845.85 | 21-APR-13:00 | 35.00 | 19.79 |
May | 0.138023E+11 | 19632.98 | 28-MAY-16:01 | 42.20 | 19.49 | 0.665635E+09 | 845.82 | 04-MAY-13:00 | 42.20 | 19.49 |
June | 0.131387E+11 | 18963.11 | 11-JUN-16:22 | 43.25 | 23.12 | 0.663119E+09 | 845.77 | 12-JUN-13:50 | 43.80 | 22.37 |
July | 0.123127E+11 | 18985.98 | 02-JUL-16:32 | 40.33 | 26.50 | 0.617026E+09 | 845.62 | 06-JUL-09:20 | 35.40 | 25.87 |
August | 0.123971E+11 | 19151.91 | 27-AUG-14:43 | 35.52 | 29.13 | 0.691875E+09 | 845.77 | 07-AUG-13:00 | 35.52 | 29.13 |
September | 0.117728E+11 | 20511.29 | 24-SEP-14:42 | 35.10 | 24.80 | 0.614858E+09 | 854.89 | 28-SEP-13:39 | 35.37 | 22.75 |
October | 0.137838E+11 | 22021.59 | 01-OCT-13:11 | 35.43 | 19.93 | 0.640763E+09 | 883.82 | 02-OCT-13:50 | 36.37 | 21.07 |
November | 0.118912E+11 | 21614.61 | 12-NOV-13:12 | 27.87 | 16.14 | 0.631966E+09 | 861.96 | 01-NOV-13:39 | 27.87 | 16.14 |
December | 0.781449E+10 | 20107.48 | 03-DEC-13:02 | 24.08 | 14.17 | 0.607762E+09 | 845.92 | 06-DEC-14:50 | 21.82 | 13.16 |
Annual Sum or Average | 0.135236E+12 | 0.763246E+10 | ||||||||
Minimum of Months | 0.701979E+10 | 17581.65 | 22.60 | 13.29 | 0.571308E+09 | 845.62 | 21.82 | 13.16 | ||
Maximum of Months | 0.138023E+11 | 22021.59 | 43.25 | 29.13 | 0.691875E+09 | 883.82 | 43.80 | 29.13 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.292566E+10 | 5187.61 | 31-JAN-16:00 | 21.10 | 11.23 | 0.378028E+09 | 544.94 | 25-JAN-14:00 | 21.10 | 11.23 |
February | 0.357677E+10 | 10246.83 | 20-FEB-15:43 | 25.72 | 14.13 | 0.359289E+09 | 544.95 | 09-FEB-14:09 | 25.72 | 14.13 |
March | 0.675453E+10 | 16661.43 | 12-MAR-17:23 | 29.85 | 19.55 | 0.443575E+09 | 544.96 | 30-MAR-13:50 | 32.05 | 19.26 |
April | 0.100248E+11 | 18114.90 | 30-APR-16:02 | 37.68 | 18.13 | 0.396262E+09 | 544.95 | 04-APR-09:09 | 37.68 | 18.13 |
May | 0.118434E+11 | 18986.17 | 28-MAY-16:01 | 42.20 | 19.49 | 0.429292E+09 | 544.95 | 03-MAY-09:20 | 42.20 | 19.49 |
June | 0.114785E+11 | 18241.39 | 11-JUN-16:22 | 43.25 | 23.12 | 0.427687E+09 | 544.95 | 07-JUN-09:20 | 43.25 | 23.12 |
July | 0.981968E+10 | 18095.36 | 02-JUL-16:32 | 40.33 | 26.50 | 0.397885E+09 | 544.94 | 06-JUL-09:20 | 35.40 | 25.87 |
August | 0.955318E+10 | 17610.66 | 06-AUG-16:22 | 36.15 | 26.34 | 0.446078E+09 | 544.94 | 28-AUG-09:09 | 30.88 | 27.50 |
September | 0.799230E+10 | 18098.27 | 24-SEP-14:42 | 35.10 | 24.80 | 0.396206E+09 | 544.94 | 08-SEP-13:30 | 35.10 | 24.80 |
October | 0.718103E+10 | 18856.78 | 01-OCT-15:51 | 35.50 | 20.15 | 0.411274E+09 | 544.95 | 16-OCT-09:09 | 26.53 | 17.36 |
November | 0.493452E+10 | 14342.84 | 12-NOV-15:12 | 27.97 | 15.72 | 0.402572E+09 | 544.96 | 06-NOV-14:00 | 27.97 | 15.72 |
December | 0.324451E+10 | 5662.30 | 01-DEC-15:30 | 22.85 | 13.56 | 0.375109E+09 | 544.95 | 29-DEC-14:09 | 19.75 | 14.80 |
Annual Sum or Average | 0.893289E+11 | 0.486326E+10 | ||||||||
Minimum of Months | 0.292566E+10 | 5187.61 | 21.10 | 11.23 | 0.359289E+09 | 544.94 | 19.75 | 11.23 | ||
Maximum of Months | 0.118434E+11 | 18986.17 | 43.25 | 26.50 | 0.446078E+09 | 544.96 | 43.25 | 27.50 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.215562E+10 | 3129.44 | 26-JAN-15:00 | 21.60 | 13.66 | 0.519460E+09 | 845.60 | 26-JAN-14:30 | 21.60 | 13.66 |
February | 0.311071E+10 | 5757.36 | 23-FEB-14:50 | 25.90 | 14.07 | 0.521636E+09 | 845.61 | 24-FEB-14:20 | 26.07 | 17.12 |
March | 0.656816E+10 | 13558.29 | 14-MAR-05:02 | 20.70 | 16.42 | 0.676585E+09 | 845.63 | 30-MAR-13:50 | 32.05 | 19.26 |
April | 0.109786E+11 | 22425.99 | 16-APR-15:41 | 39.37 | 22.61 | 0.613294E+09 | 845.63 | 04-APR-09:09 | 39.37 | 22.61 |
May | 0.152080E+11 | 23072.30 | 28-MAY-16:11 | 42.10 | 19.51 | 0.665667E+09 | 845.61 | 08-MAY-13:09 | 42.10 | 19.51 |
June | 0.153121E+11 | 22971.45 | 04-JUN-16:31 | 41.97 | 22.48 | 0.663299E+09 | 845.62 | 12-JUN-13:09 | 43.40 | 22.40 |
July | 0.139347E+11 | 22741.27 | 02-JUL-16:32 | 40.33 | 26.50 | 0.617226E+09 | 845.60 | 10-JUL-09:09 | 32.98 | 26.50 |
August | 0.130612E+11 | 21402.19 | 06-AUG-15:42 | 36.30 | 26.24 | 0.691825E+09 | 845.60 | 28-AUG-09:09 | 30.88 | 27.50 |
September | 0.102135E+11 | 22620.07 | 17-SEP-14:52 | 34.20 | 26.01 | 0.614194E+09 | 845.60 | 08-SEP-13:39 | 34.20 | 26.01 |
October | 0.775445E+10 | 15286.49 | 04-OCT-05:02 | 25.07 | 21.35 | 0.633299E+09 | 845.61 | 16-OCT-09:20 | 26.87 | 17.49 |
November | 0.433489E+10 | 6421.82 | 09-NOV-14:40 | 29.27 | 17.76 | 0.599860E+09 | 845.62 | 06-NOV-14:50 | 29.27 | 17.76 |
December | 0.245637E+10 | 2982.71 | 28-DEC-15:50 | 23.92 | 15.23 | 0.520424E+09 | 845.61 | 28-DEC-14:00 | 23.92 | 15.23 |
Annual Sum or Average | 0.105088E+12 | 0.733677E+10 | ||||||||
Minimum of Months | 0.215562E+10 | 2982.71 | 20.70 | 13.66 | 0.519460E+09 | 845.60 | 21.60 | 13.66 | ||
Maximum of Months | 0.153121E+11 | 23072.30 | 42.10 | 26.50 | 0.691825E+09 | 845.63 | 43.40 | 27.50 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.202946E+10 | 3024.32 | 26-JAN-14:30 | 22.05 | 13.77 | 0.357817E+09 | 544.94 | 13-JAN-14:39 | 22.05 | 13.77 |
February | 0.299243E+10 | 5702.31 | 23-FEB-10:40 | 22.80 | 14.32 | 0.353544E+09 | 544.95 | 15-FEB-10:50 | 22.80 | 14.32 |
March | 0.639082E+10 | 16454.10 | 12-MAR-16:22 | 30.95 | 19.85 | 0.441945E+09 | 544.96 | 27-MAR-09:20 | 23.77 | 16.23 |
April | 0.102694E+11 | 18984.57 | 16-APR-09:02 | 33.08 | 21.25 | 0.396088E+09 | 545.23 | 28-APR-09:50 | 33.47 | 18.33 |
May | 0.129502E+11 | 19384.98 | 07-MAY-09:51 | 36.20 | 20.86 | 0.429301E+09 | 545.23 | 12-MAY-09:20 | 33.00 | 23.15 |
June | 0.119045E+11 | 17604.11 | 11-JUN-10:22 | 37.75 | 25.19 | 0.427605E+09 | 545.10 | 02-JUN-09:20 | 37.75 | 25.19 |
July | 0.103108E+11 | 17464.38 | 04-JUL-10:02 | 35.40 | 25.09 | 0.397861E+09 | 545.05 | 07-JUL-09:00 | 36.90 | 24.55 |
August | 0.961047E+10 | 16901.28 | 06-AUG-15:02 | 36.30 | 26.24 | 0.445926E+09 | 544.94 | 28-AUG-09:09 | 30.88 | 27.50 |
September | 0.815214E+10 | 17470.79 | 17-SEP-14:52 | 34.20 | 26.01 | 0.395916E+09 | 544.94 | 08-SEP-13:39 | 34.20 | 26.01 |
October | 0.698097E+10 | 11882.51 | 01-OCT-10:02 | 30.08 | 19.42 | 0.410064E+09 | 544.95 | 17-OCT-09:20 | 26.63 | 18.34 |
November | 0.411598E+10 | 5906.63 | 09-NOV-10:20 | 25.33 | 18.04 | 0.398582E+09 | 544.95 | 06-NOV-14:50 | 25.33 | 18.04 |
December | 0.220834E+10 | 3089.37 | 01-DEC-14:50 | 23.42 | 13.31 | 0.359198E+09 | 544.94 | 28-DEC-14:09 | 24.58 | 15.31 |
Annual Sum or Average | 0.879155E+11 | 0.481385E+10 | ||||||||
Minimum of Months | 0.202946E+10 | 3024.32 | 22.05 | 13.31 | 0.353544E+09 | 544.94 | 22.05 | 13.77 | ||
Maximum of Months | 0.129502E+11 | 19384.98 | 37.75 | 26.24 | 0.445926E+09 | 545.23 | 37.75 | 27.50 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.544418E+10 | 11874.19 | 12-JAN-14:20 | 23.40 | 14.05 | 0.595185E+09 | 845.64 | 25-JAN-14:00 | 23.00 | 13.41 |
February | 0.678222E+10 | 22961.50 | 20-FEB-15:43 | 25.72 | 14.13 | 0.556517E+09 | 845.93 | 21-FEB-14:00 | 26.30 | 15.42 |
March | 0.112417E+11 | 24195.88 | 12-MAR-13:42 | 31.12 | 19.32 | 0.686371E+09 | 846.00 | 09-MAR-14:00 | 31.12 | 19.32 |
April | 0.139152E+11 | 23332.65 | 16-APR-15:01 | 39.63 | 22.37 | 0.614460E+09 | 846.06 | 21-APR-13:20 | 34.67 | 19.93 |
May | 0.158691E+11 | 23269.98 | 07-MAY-15:11 | 42.37 | 21.49 | 0.665789E+09 | 845.99 | 01-MAY-13:20 | 42.37 | 21.49 |
June | 0.151917E+11 | 22933.34 | 04-JUN-15:51 | 42.30 | 22.20 | 0.663295E+09 | 846.06 | 12-JUN-13:20 | 43.50 | 22.39 |
July | 0.140226E+11 | 22730.01 | 02-JUL-16:32 | 40.33 | 26.50 | 0.617241E+09 | 845.62 | 10-JUL-13:09 | 39.20 | 26.78 |
August | 0.138060E+11 | 22519.96 | 06-AUG-14:22 | 36.10 | 26.31 | 0.692009E+09 | 845.62 | 28-AUG-09:09 | 30.88 | 27.50 |
September | 0.127692E+11 | 24219.07 | 17-SEP-14:52 | 34.20 | 26.01 | 0.614799E+09 | 845.82 | 26-SEP-13:00 | 35.70 | 22.91 |
October | 0.140824E+11 | 25030.65 | 22-OCT-13:52 | 30.80 | 17.95 | 0.638952E+09 | 857.06 | 02-OCT-13:50 | 30.80 | 17.95 |
November | 0.112476E+11 | 25001.93 | 05-NOV-13:42 | 29.32 | 17.20 | 0.626735E+09 | 846.06 | 21-NOV-14:00 | 26.70 | 14.93 |
December | 0.632462E+10 | 21256.23 | 03-DEC-13:32 | 24.33 | 14.17 | 0.588887E+09 | 845.64 | 04-DEC-14:50 | 23.20 | 14.19 |
Annual Sum or Average | 0.140697E+12 | 0.756024E+10 | ||||||||
Minimum of Months | 0.544418E+10 | 11874.19 | 23.40 | 14.05 | 0.556517E+09 | 845.62 | 23.00 | 13.41 | ||
Maximum of Months | 0.158691E+11 | 25030.65 | 42.37 | 26.50 | 0.692009E+09 | 857.06 | 43.50 | 27.50 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.239876E+10 | 4674.48 | 12-JAN-15:50 | 23.35 | 14.44 | 0.351200E+09 | 544.94 | 25-JAN-14:00 | 23.00 | 13.41 |
February | 0.330481E+10 | 8499.11 | 20-FEB-15:43 | 25.72 | 14.13 | 0.342644E+09 | 544.95 | 24-FEB-14:20 | 26.07 | 17.12 |
March | 0.681778E+10 | 20539.15 | 12-MAR-16:22 | 30.95 | 19.85 | 0.438973E+09 | 544.96 | 30-MAR-13:50 | 32.05 | 19.26 |
April | 0.109537E+11 | 20700.95 | 30-APR-16:02 | 37.68 | 18.13 | 0.396164E+09 | 544.96 | 04-APR-09:09 | 37.68 | 18.13 |
May | 0.133107E+11 | 21507.39 | 28-MAY-16:11 | 42.10 | 19.51 | 0.429306E+09 | 544.95 | 05-MAY-09:00 | 42.10 | 19.51 |
June | 0.129839E+11 | 21212.49 | 04-JUN-16:31 | 41.97 | 22.48 | 0.427698E+09 | 544.95 | 12-JUN-13:09 | 43.40 | 22.40 |
July | 0.110148E+11 | 20820.03 | 02-JUL-16:32 | 40.33 | 26.50 | 0.397940E+09 | 544.94 | 10-JUL-09:09 | 32.98 | 26.50 |
August | 0.104770E+11 | 20041.98 | 06-AUG-16:22 | 36.15 | 26.34 | 0.446081E+09 | 544.94 | 28-AUG-09:09 | 30.88 | 27.50 |
September | 0.867027E+10 | 20695.12 | 17-SEP-14:52 | 34.20 | 26.01 | 0.396071E+09 | 544.94 | 08-SEP-13:39 | 34.20 | 26.01 |
October | 0.736970E+10 | 20076.81 | 22-OCT-15:52 | 30.40 | 17.68 | 0.409609E+09 | 544.95 | 16-OCT-09:20 | 30.40 | 17.68 |
November | 0.468770E+10 | 15036.99 | 05-NOV-15:42 | 28.08 | 17.72 | 0.392332E+09 | 544.96 | 06-NOV-14:50 | 28.48 | 18.19 |
December | 0.274416E+10 | 5295.54 | 28-DEC-15:40 | 24.03 | 15.27 | 0.351081E+09 | 544.95 | 29-DEC-14:50 | 19.55 | 14.90 |
Annual Sum or Average | 0.947333E+11 | 0.477910E+10 | ||||||||
Minimum of Months | 0.239876E+10 | 4674.48 | 23.35 | 14.13 | 0.342644E+09 | 544.94 | 19.55 | 13.41 | ||
Maximum of Months | 0.133107E+11 | 21507.39 | 42.10 | 26.50 | 0.446081E+09 | 544.96 | 43.40 | 27.50 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.369702E+10 | 6991.68 | 17-JAN-06:13 | 10.70 | 10.27 | 0.00 | 0.00 | 01-JAN-00:10 | 10.70 | 10.27 |
February | 0.496714E+10 | 10225.49 | 21-FEB-06:15 | 11.70 | 10.89 | 0.00 | 0.00 | 01-FEB-00:10 | 11.70 | 10.89 |
March | 0.869111E+10 | 10811.52 | 06-MAR-06:13 | 15.77 | 13.93 | 0.00 | 0.00 | 01-MAR-00:10 | 15.77 | 13.93 |
April | 0.119360E+11 | 16257.10 | 17-APR-05:15 | 24.33 | 18.88 | 0.00 | 0.00 | 01-APR-00:10 | 24.33 | 18.88 |
May | 0.129241E+11 | 17755.84 | 30-MAY-05:15 | 30.30 | 21.64 | 0.00 | 0.00 | 01-MAY-00:10 | 30.30 | 21.64 |
June | 0.129059E+11 | 17355.93 | 12-JUN-05:15 | 34.23 | 19.16 | 0.00 | 0.00 | 01-JUN-00:10 | 34.23 | 19.16 |
July | 0.126902E+11 | 18071.93 | 05-JUL-05:15 | 32.63 | 24.69 | 0.00 | 0.00 | 01-JUL-00:10 | 32.63 | 24.69 |
August | 0.138079E+11 | 17631.53 | 07-AUG-05:13 | 29.57 | 24.74 | 0.00 | 0.00 | 01-AUG-00:10 | 29.57 | 24.74 |
September | 0.994747E+10 | 13175.73 | 05-SEP-05:15 | 26.20 | 25.15 | 0.00 | 0.00 | 01-SEP-00:10 | 26.20 | 25.15 |
October | 0.975623E+10 | 11566.60 | 10-OCT-05:10 | 19.80 | 18.03 | 0.00 | 0.00 | 01-OCT-00:10 | 19.80 | 18.03 |
November | 0.767231E+10 | 11739.03 | 06-NOV-06:13 | 14.80 | 13.74 | 0.00 | 0.00 | 01-NOV-00:10 | 14.80 | 13.74 |
December | 0.543259E+10 | 9077.87 | 26-DEC-06:13 | 10.23 | 8.49 | 0.00 | 0.00 | 01-DEC-00:10 | 10.23 | 8.49 |
Annual Sum or Average | 0.114428E+12 | 0.00 | ||||||||
Minimum of Months | 0.369702E+10 | 6991.68 | 10.23 | 8.49 | 0.00 | 0.00 | 10.23 | 8.49 | ||
Maximum of Months | 0.138079E+11 | 18071.93 | 34.23 | 25.15 | 0.00 | 0.00 | 34.23 | 25.15 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.191019E+10 | 3840.52 | 20-JAN-06:10 | 7.47 | 6.75 | 0.00 | 0.00 | 01-JAN-00:10 | 7.47 | 6.75 |
February | 0.311325E+10 | 4968.25 | 21-FEB-06:15 | 11.70 | 10.89 | 0.00 | 0.00 | 01-FEB-00:10 | 11.70 | 10.89 |
March | 0.644008E+10 | 7305.32 | 13-MAR-16:00 | 32.50 | 18.65 | 0.00 | 0.00 | 01-MAR-00:10 | 32.50 | 18.65 |
April | 0.917772E+10 | 8362.01 | 17-APR-15:10 | 34.65 | 21.60 | 0.00 | 0.00 | 01-APR-00:10 | 34.65 | 21.60 |
May | 0.112479E+11 | 11081.53 | 31-MAY-05:03 | 31.72 | 21.12 | 0.00 | 0.00 | 01-MAY-00:10 | 31.72 | 21.12 |
June | 0.108545E+11 | 10939.00 | 10-JUN-05:03 | 29.67 | 22.80 | 0.00 | 0.00 | 01-JUN-00:10 | 29.67 | 22.80 |
July | 0.100836E+11 | 10485.90 | 07-JUL-05:03 | 31.52 | 25.91 | 0.00 | 0.00 | 01-JUL-00:10 | 31.52 | 25.91 |
August | 0.988290E+10 | 11036.50 | 08-AUG-05:02 | 30.10 | 25.30 | 0.00 | 0.00 | 01-AUG-00:10 | 30.10 | 25.30 |
September | 0.846099E+10 | 11569.19 | 05-SEP-05:15 | 26.20 | 25.15 | 0.00 | 0.00 | 01-SEP-00:10 | 26.20 | 25.15 |
October | 0.775420E+10 | 9077.00 | 16-OCT-05:13 | 20.50 | 15.01 | 0.00 | 0.00 | 01-OCT-00:10 | 20.50 | 15.01 |
November | 0.513158E+10 | 6956.99 | 06-NOV-06:13 | 14.80 | 13.74 | 0.00 | 0.00 | 01-NOV-00:10 | 14.80 | 13.74 |
December | 0.269388E+10 | 4197.97 | 20-DEC-06:10 | 6.40 | 4.05 | 0.00 | 0.00 | 01-DEC-00:10 | 6.40 | 4.05 |
Annual Sum or Average | 0.867508E+11 | 0.00 | ||||||||
Minimum of Months | 0.191019E+10 | 3840.52 | 6.40 | 4.05 | 0.00 | 0.00 | 6.40 | 4.05 | ||
Maximum of Months | 0.112479E+11 | 11569.19 | 34.65 | 25.91 | 0.00 | 0.00 | 34.65 | 25.91 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.165985E+10 | 6448.44 | 12-JAN-15:00 | 23.60 | 14.20 | 0.00 | 0.00 | 01-JAN-00:10 | 23.60 | 14.20 |
February | 0.388441E+10 | 13210.73 | 22-FEB-14:50 | 27.08 | 16.22 | 0.00 | 0.00 | 01-FEB-00:10 | 27.08 | 16.22 |
March | 0.103755E+11 | 20925.33 | 28-MAR-15:20 | 35.57 | 18.58 | 0.00 | 0.00 | 01-MAR-00:10 | 35.57 | 18.58 |
April | 0.182599E+11 | 25800.19 | 26-APR-14:50 | 39.22 | 22.03 | 0.00 | 0.00 | 01-APR-00:10 | 39.22 | 22.03 |
May | 0.238305E+11 | 29385.58 | 01-MAY-14:20 | 43.93 | 22.01 | 0.00 | 0.00 | 01-MAY-00:10 | 43.93 | 22.01 |
June | 0.237444E+11 | 30910.08 | 12-JUN-13:50 | 43.80 | 22.37 | 0.00 | 0.00 | 01-JUN-00:10 | 43.80 | 22.37 |
July | 0.194390E+11 | 27485.09 | 07-JUL-14:00 | 40.30 | 24.54 | 0.00 | 0.00 | 01-JUL-00:10 | 40.30 | 24.54 |
August | 0.178762E+11 | 24488.57 | 07-AUG-14:00 | 37.20 | 26.26 | 0.00 | 0.00 | 01-AUG-00:10 | 37.20 | 26.26 |
September | 0.140258E+11 | 21333.92 | 26-SEP-14:40 | 35.97 | 22.76 | 0.00 | 0.00 | 01-SEP-00:10 | 35.97 | 22.76 |
October | 0.118977E+11 | 20275.13 | 02-OCT-14:00 | 36.40 | 21.05 | 0.00 | 0.00 | 01-OCT-00:10 | 36.40 | 21.05 |
November | 0.639852E+10 | 14160.35 | 09-NOV-14:10 | 29.37 | 17.83 | 0.00 | 0.00 | 01-NOV-00:10 | 29.37 | 17.83 |
December | 0.210124E+10 | 7952.38 | 01-DEC-14:30 | 23.45 | 13.21 | 0.00 | 0.00 | 01-DEC-00:10 | 23.45 | 13.21 |
Annual Sum or Average | 0.153493E+12 | 0.00 | ||||||||
Minimum of Months | 0.165985E+10 | 6448.44 | 23.45 | 13.21 | 0.00 | 0.00 | 23.45 | 13.21 | ||
Maximum of Months | 0.238305E+11 | 30910.08 | 43.93 | 26.26 | 0.00 | 0.00 | 43.93 | 26.26 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.404960E+10 | 1887.21 | 30-JAN-17:00 | 19.20 | 10.80 | 95236668.02 | 126.85 | 17-JAN-14:50 | 19.20 | 10.80 |
February | 0.848571E+10 | 3915.09 | 20-FEB-17:15 | 24.07 | 14.47 | 86404015.41 | 126.84 | 09-FEB-14:00 | 24.07 | 14.47 |
March | 0.146372E+11 | 7201.51 | 31-MAR-23:53 | 23.70 | 16.75 | 0.103242E+09 | 126.84 | 23-MAR-09:09 | 23.70 | 16.75 |
April | 0.191087E+11 | 7748.08 | 17-APR-01:55 | 26.00 | 19.96 | 95633468.81 | 146.09 | 27-APR-13:00 | 39.60 | 19.54 |
May | 0.476590E+10 | 3494.18 | 31-MAY-24:00 | 28.10 | 22.60 | 99240598.27 | 126.85 | 10-MAY-13:39 | 28.10 | 22.60 |
June | 0.948324E+10 | 5404.43 | 30-JUN-24:00 | 33.10 | 24.67 | 98979850.43 | 126.88 | 27-JUN-09:00 | 33.10 | 24.67 |
July | 0.148525E+11 | 7250.20 | 31-JUL-24:00 | 29.40 | 26.34 | 91893539.13 | 126.85 | 27-JUL-09:09 | 29.40 | 26.34 |
August | 0.195281E+11 | 7547.82 | 16-AUG-00:50 | 23.73 | 23.24 | 0.113266E+09 | 152.21 | 07-AUG-13:00 | 23.73 | 23.24 |
September | 0.454382E+10 | 3486.88 | 30-SEP-24:00 | 26.60 | 21.92 | 91606574.04 | 126.85 | 29-SEP-13:09 | 26.60 | 21.92 |
October | 0.970926E+10 | 5386.65 | 31-OCT-24:00 | 17.80 | 15.13 | 95244984.43 | 126.86 | 06-OCT-09:20 | 17.80 | 15.13 |
November | 0.141846E+11 | 5798.22 | 12-NOV-16:23 | 26.95 | 15.49 | 94304960.06 | 126.83 | 09-NOV-10:09 | 26.95 | 15.49 |
December | 0.195166E+11 | 7603.79 | 28-DEC-17:00 | 22.80 | 14.91 | 91882180.85 | 126.83 | 11-DEC-10:09 | 22.80 | 14.91 |
Annual Sum or Average | 0.142865E+12 | 0.115693E+10 | ||||||||
Minimum of Months | 0.404960E+10 | 1887.21 | 17.80 | 10.80 | 86404015.41 | 126.83 | 17.80 | 10.80 | ||
Maximum of Months | 0.195281E+11 | 7748.08 | 33.10 | 26.34 | 0.113266E+09 | 152.21 | 39.60 | 26.34 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.292516E+10 | 1735.60 | 12-JAN-17:00 | 22.30 | 14.53 | 95235189.93 | 126.84 | 13-JAN-14:00 | 21.50 | 15.25 |
February | 0.754953E+10 | 3622.26 | 21-FEB-17:00 | 25.40 | 15.70 | 86403534.57 | 126.84 | 09-FEB-14:00 | 25.40 | 15.70 |
March | 0.138240E+11 | 6949.20 | 31-MAR-23:53 | 23.70 | 16.75 | 0.103241E+09 | 126.83 | 29-MAR-09:09 | 23.70 | 16.75 |
April | 0.180921E+11 | 7244.24 | 12-APR-16:00 | 28.10 | 17.52 | 95365586.80 | 144.51 | 26-APR-13:00 | 38.80 | 22.02 |
May | 0.443053E+10 | 3365.50 | 31-MAY-24:00 | 28.10 | 22.60 | 99238204.75 | 126.85 | 30-MAY-13:00 | 28.10 | 22.60 |
June | 0.897229E+10 | 5201.09 | 30-JUN-24:00 | 33.10 | 24.67 | 98979214.62 | 126.87 | 27-JUN-09:50 | 33.10 | 24.67 |
July | 0.140757E+11 | 6927.47 | 31-JUL-23:43 | 29.40 | 26.34 | 91894354.97 | 126.85 | 18-JUL-09:00 | 29.40 | 26.34 |
August | 0.184226E+11 | 7130.42 | 16-AUG-09:40 | 25.23 | 24.59 | 0.111575E+09 | 147.90 | 07-AUG-13:00 | 25.23 | 24.59 |
September | 0.419038E+10 | 3369.15 | 30-SEP-24:00 | 26.60 | 21.92 | 91605401.01 | 126.84 | 27-SEP-13:20 | 26.60 | 21.92 |
October | 0.911447E+10 | 5084.85 | 31-OCT-24:00 | 17.80 | 15.13 | 95244111.18 | 126.86 | 06-OCT-09:00 | 17.80 | 15.13 |
November | 0.131789E+11 | 5445.65 | 08-NOV-16:40 | 28.33 | 18.82 | 94304883.95 | 126.83 | 09-NOV-10:09 | 24.92 | 17.98 |
December | 0.178417E+11 | 7195.50 | 01-DEC-17:00 | 21.20 | 14.26 | 91882297.01 | 126.83 | 11-DEC-10:00 | 10.00 | 9.32 |
Annual Sum or Average | 0.132617E+12 | 0.115497E+10 | ||||||||
Minimum of Months | 0.292516E+10 | 1735.60 | 17.80 | 14.26 | 86403534.57 | 126.83 | 10.00 | 9.32 | ||
Maximum of Months | 0.184226E+11 | 7244.24 | 33.10 | 26.34 | 0.111575E+09 | 147.90 | 38.80 | 26.34 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.148960E+10 | 1731.45 | 12-JAN-17:00 | 22.30 | 14.53 | 95015606.26 | 126.84 | 13-JAN-14:00 | 21.50 | 15.25 |
February | 0.682727E+10 | 3656.86 | 22-FEB-17:00 | 25.70 | 15.75 | 86404196.42 | 126.84 | 15-FEB-14:00 | 25.70 | 15.75 |
March | 0.136453E+11 | 6899.61 | 31-MAR-23:53 | 23.70 | 16.75 | 0.103242E+09 | 126.84 | 29-MAR-09:09 | 23.70 | 16.75 |
April | 0.182540E+11 | 7463.63 | 16-APR-21:32 | 28.07 | 20.03 | 94223769.91 | 143.03 | 26-APR-13:00 | 38.80 | 22.02 |
May | 0.466363E+10 | 3341.38 | 31-MAY-24:00 | 28.10 | 22.60 | 99239146.83 | 126.85 | 30-MAY-13:09 | 28.10 | 22.60 |
June | 0.919537E+10 | 5250.79 | 30-JUN-24:00 | 33.10 | 24.67 | 98981027.70 | 126.88 | 28-JUN-13:09 | 33.10 | 24.67 |
July | 0.142874E+11 | 7047.25 | 31-JUL-23:57 | 29.40 | 26.34 | 91896111.45 | 126.85 | 12-JUL-13:09 | 29.40 | 26.34 |
August | 0.187458E+11 | 7296.00 | 20-AUG-17:33 | 26.43 | 25.55 | 0.109009E+09 | 146.65 | 07-AUG-13:00 | 26.43 | 25.55 |
September | 0.426521E+10 | 3356.05 | 30-SEP-23:17 | 26.60 | 22.12 | 91605459.11 | 126.84 | 27-SEP-13:20 | 26.60 | 22.12 |
October | 0.902218E+10 | 4941.58 | 31-OCT-24:00 | 17.80 | 15.13 | 95245389.23 | 126.86 | 06-OCT-09:00 | 17.80 | 15.13 |
November | 0.126558E+11 | 5493.45 | 08-NOV-16:30 | 28.55 | 18.76 | 94305607.26 | 126.83 | 09-NOV-10:09 | 24.92 | 17.98 |
December | 0.165930E+11 | 7190.26 | 28-DEC-17:00 | 22.80 | 14.91 | 91882912.38 | 126.83 | 11-DEC-10:50 | 22.80 | 14.91 |
Annual Sum or Average | 0.129645E+12 | 0.115105E+10 | ||||||||
Minimum of Months | 0.148960E+10 | 1731.45 | 17.80 | 14.53 | 86404196.42 | 126.83 | 17.80 | 14.91 | ||
Maximum of Months | 0.187458E+11 | 7463.63 | 33.10 | 26.34 | 0.109009E+09 | 146.65 | 38.80 | 26.34 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.241088E+12 | 92473.16 | 12-JAN-17:00 | 22.30 | 14.53 | 0.206242E+10 | 2748.28 | 26-JAN-10:09 | 17.70 | 12.86 |
February | 0.437544E+12 | 183895.03 | 21-FEB-17:00 | 25.40 | 15.70 | 0.187106E+10 | 2749.09 | 09-FEB-14:09 | 25.40 | 15.70 |
March | 0.729233E+12 | 358642.06 | 31-MAR-23:57 | 23.70 | 16.75 | 0.223526E+10 | 2749.78 | 21-MAR-09:09 | 23.70 | 16.75 |
April | 0.934111E+12 | 368779.80 | 30-APR-04:53 | 22.70 | 16.37 | 0.240827E+10 | 4040.51 | 28-APR-13:00 | 22.70 | 16.37 |
May | 0.241964E+12 | 176019.30 | 31-MAY-24:00 | 28.10 | 22.60 | 0.214885E+10 | 2747.25 | 24-MAY-09:00 | 28.10 | 22.60 |
June | 0.471565E+12 | 268193.27 | 30-JUN-24:00 | 33.10 | 24.67 | 0.214278E+10 | 2746.96 | 27-JUN-09:00 | 33.10 | 24.67 |
July | 0.734787E+12 | 356261.78 | 31-JUL-23:20 | 29.40 | 26.34 | 0.198927E+10 | 2746.02 | 18-JUL-09:00 | 29.40 | 26.34 |
August | 0.966883E+12 | 369681.22 | 15-AUG-23:53 | 23.40 | 22.91 | 0.293726E+10 | 4087.37 | 07-AUG-13:00 | 23.40 | 22.91 |
September | 0.239065E+12 | 177491.45 | 30-SEP-24:00 | 26.60 | 21.92 | 0.198368E+10 | 2747.27 | 01-SEP-09:30 | 26.60 | 21.92 |
October | 0.490165E+12 | 269346.88 | 31-OCT-24:00 | 17.80 | 15.13 | 0.206191E+10 | 2746.43 | 13-OCT-09:09 | 17.80 | 15.13 |
November | 0.710886E+12 | 277030.05 | 13-NOV-17:00 | 26.40 | 16.65 | 0.204192E+10 | 2749.74 | 28-NOV-10:30 | 18.60 | 13.96 |
December | 0.978876E+12 | 368383.94 | 04-DEC-17:00 | 20.10 | 14.52 | 0.199056E+10 | 2818.56 | 28-DEC-14:00 | 24.50 | 15.39 |
Annual Sum or Average | 0.717617E+13 | 0.258733E+11 | ||||||||
Minimum of Months | 0.239065E+12 | 92473.16 | 17.80 | 14.52 | 0.187106E+10 | 2746.02 | 17.70 | 12.86 | ||
Maximum of Months | 0.978876E+12 | 369681.22 | 33.10 | 26.34 | 0.293726E+10 | 4087.37 | 33.10 | 26.34 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3575357.53 | 2409.09 | 14-JAN-17:03 | 20.55 |
February | 52403877.96 | 9294.00 | 20-FEB-14:05 | 26.38 |
March | 0.133021E+09 | 15691.62 | 11-MAR-17:02 | 29.70 |
April | 0.442592E+09 | 30037.96 | 15-APR-16:01 | 39.58 |
May | 0.610702E+09 | 33373.02 | 27-MAY-16:01 | 42.00 |
June | 0.600621E+09 | 35206.26 | 10-JUN-16:01 | 43.12 |
July | 0.804879E+09 | 29444.50 | 02-JUL-16:28 | 40.35 |
August | 0.517245E+09 | 24458.33 | 05-AUG-16:01 | 35.70 |
September | 0.651407E+09 | 22520.28 | 30-SEP-16:02 | 34.78 |
October | 0.484766E+09 | 22951.17 | 01-OCT-15:43 | 35.58 |
November | 0.169209E+09 | 14552.55 | 05-NOV-13:50 | 29.32 |
December | 15443225.38 | 9125.93 | 03-DEC-13:43 | 24.42 |
Annual Sum or Average | 0.448586E+10 | |||
Minimum of Months | 3575357.53 | 2409.09 | 20.55 | |
Maximum of Months | 0.804879E+09 | 35206.26 | 43.12 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:03 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.83 | |
Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:03 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.83 | |
Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.243611E+09 | 61371.01 | 02-JAN-05:01 | 6.48 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:03 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 0.243611E+09 | |||
Minimum of Months | 0.00 | 0.00 | 6.48 | |
Maximum of Months | 0.243611E+09 | 61371.01 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:03 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.83 | |
Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:03 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.83 | |
Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:03 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.83 | |
Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:03 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.83 | |
Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1509235.62 | 3722.00 | 02-JAN-06:01 | 6.45 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:03 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 2510.44 | 16.74 | 23-DEC-06:08 | 5.43 |
Annual Sum or Average | 1511746.06 | |||
Minimum of Months | 0.00 | 0.00 | 5.43 | |
Maximum of Months | 1509235.62 | 3722.00 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 100048.35 | 459.12 | 03-JAN-06:05 | 5.57 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:03 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 100048.35 | |||
Minimum of Months | 0.00 | 0.00 | 5.57 | |
Maximum of Months | 100048.35 | 459.12 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:03 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.83 | |
Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:03 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.83 | |
Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.576556E+09 | 16867.79 | 02-JAN-04:02 | 6.67 |
February | 67492235.15 | 14467.92 | 11-FEB-06:02 | 9.30 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:03 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.58 |
November | 40864.27 | 261.57 | 27-NOV-06:05 | 9.55 |
December | 0.182358E+09 | 14460.12 | 20-DEC-06:02 | 6.40 |
Annual Sum or Average | 0.826447E+09 | |||
Minimum of Months | 0.00 | 0.00 | 6.40 | |
Maximum of Months | 0.576556E+09 | 16867.79 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.229675E+09 | 11589.49 | 02-JAN-04:02 | 6.67 |
February | 17113153.93 | 10039.96 | 11-FEB-06:02 | 9.30 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:03 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 53356422.83 | 9816.20 | 21-DEC-06:02 | 5.27 |
Annual Sum or Average | 0.300144E+09 | |||
Minimum of Months | 0.00 | 0.00 | 5.27 | |
Maximum of Months | 0.229675E+09 | 11589.49 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.153375E+09 | 16202.45 | 02-JAN-05:01 | 6.48 |
February | 14807071.10 | 14456.42 | 11-FEB-06:02 | 9.30 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:03 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 20930135.83 | 13235.45 | 23-DEC-06:03 | 5.43 |
Annual Sum or Average | 0.189113E+09 | |||
Minimum of Months | 0.00 | 0.00 | 5.43 | |
Maximum of Months | 0.153375E+09 | 16202.45 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.143728E+09 | 11193.19 | 02-JAN-05:01 | 6.48 |
February | 8356197.91 | 9459.04 | 11-FEB-06:02 | 9.30 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:03 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 25091763.76 | 8836.50 | 23-DEC-06:03 | 5.43 |
Annual Sum or Average | 0.177176E+09 | |||
Minimum of Months | 0.00 | 0.00 | 5.43 | |
Maximum of Months | 0.143728E+09 | 11193.19 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 67962756.48 | 9320.49 | 17-JAN-04:02 | 11.75 |
February | 82086192.63 | 8834.08 | 13-FEB-04:03 | 11.62 |
March | 77798583.06 | 7993.51 | 21-MAR-03:02 | 14.88 |
April | 55949950.79 | 7131.99 | 16-APR-15:01 | 39.63 |
May | 33960403.90 | 6023.99 | 07-MAY-15:11 | 42.37 |
June | 39705313.17 | 7542.96 | 04-JUN-15:51 | 42.30 |
July | 62084144.98 | 6044.11 | 30-JUL-14:22 | 34.60 |
August | 63584765.11 | 6389.49 | 27-AUG-15:02 | 35.43 |
September | 55321580.88 | 6504.26 | 09-SEP-03:02 | 24.35 |
October | 79625654.36 | 7183.57 | 27-OCT-03:02 | 17.72 |
November | 97521060.12 | 8737.46 | 24-NOV-04:02 | 11.00 |
December | 0.127876E+09 | 11258.94 | 11-DEC-04:02 | 10.80 |
Annual Sum or Average | 0.843476E+09 | |||
Minimum of Months | 33960403.90 | 6023.99 | 10.80 | |
Maximum of Months | 0.127876E+09 | 11258.94 | 42.37 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 60178767.45 | 7235.63 | 02-JAN-06:01 | 6.45 |
February | 45483901.88 | 6513.99 | 27-FEB-04:02 | 11.72 |
March | 44014133.11 | 6094.82 | 29-MAR-03:02 | 21.75 |
April | 35403566.26 | 6513.59 | 13-APR-03:02 | 24.18 |
May | 37478530.62 | 7758.71 | 24-MAY-03:02 | 26.12 |
June | 27525410.40 | 7123.71 | 21-JUN-03:02 | 28.25 |
July | 46363501.00 | 7471.39 | 27-JUL-03:02 | 27.18 |
August | 38504486.15 | 7222.02 | 17-AUG-03:02 | 27.35 |
September | 51003888.36 | 9118.75 | 11-SEP-03:02 | 26.07 |
October | 51469004.63 | 5693.94 | 11-OCT-03:02 | 24.45 |
November | 48514052.91 | 5537.47 | 28-NOV-05:03 | 15.20 |
December | 50128433.23 | 6898.62 | 22-DEC-06:03 | 12.42 |
Annual Sum or Average | 0.536068E+09 | |||
Minimum of Months | 27525410.40 | 5537.47 | 6.45 | |
Maximum of Months | 60178767.45 | 9118.75 | 28.25 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.217587E+10 | 19541.47 | 02-JAN-06:13 | 6.50 |
February | 0.984266E+09 | 18117.52 | 27-FEB-06:03 | 10.82 |
March | 0.383634E+09 | 17791.18 | 01-MAR-06:02 | 13.67 |
April | 82798449.74 | 13668.28 | 10-APR-05:02 | 18.28 |
May | 18747756.06 | 8868.96 | 25-MAY-03:02 | 26.60 |
June | 10367076.70 | 8237.15 | 28-JUN-03:02 | 26.40 |
July | 10745772.45 | 6617.71 | 27-JUL-03:02 | 27.18 |
August | 17287372.68 | 7495.90 | 24-AUG-03:02 | 25.58 |
September | 42961569.23 | 11064.57 | 11-SEP-03:02 | 26.07 |
October | 0.217483E+09 | 16183.94 | 27-OCT-05:02 | 16.90 |
November | 0.661675E+09 | 18226.89 | 06-NOV-06:02 | 14.70 |
December | 0.160618E+10 | 14692.14 | 29-DEC-06:02 | 16.53 |
Annual Sum or Average | 0.621202E+10 | |||
Minimum of Months | 10367076.70 | 6617.71 | 6.50 | |
Maximum of Months | 0.217587E+10 | 19541.47 | 27.18 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:03 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.83 | |
Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:03 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.83 | |
Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 66865428.96 | 331.75 | 01-JAN-14:00 | 16.20 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:03 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 66865428.96 | |||
Minimum of Months | 0.00 | 0.00 | 9.73 | |
Maximum of Months | 66865428.96 | 331.75 | 32.95 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 9.73 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15.55 |
April | 0.00 | 0.00 | 01-APR-00:03 | 23.70 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 30.53 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 28.05 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 32.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.32 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 28.43 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.58 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.72 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12.50 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.83 | |
Maximum of Months | 0.00 | 0.00 | 32.95 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.148304E+11 | 15519.45 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.134523E+11 | 15519.45 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.159851E+11 | 15519.45 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.142779E+11 | 15519.45 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.154078E+11 | 15519.45 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.153333E+11 | 15519.45 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.143524E+11 | 15519.45 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.159851E+11 | 15519.45 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.142779E+11 | 15519.45 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.148304E+11 | 15519.45 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.146566E+11 | 15519.45 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.143524E+11 | 15519.45 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.177742E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.134523E+11 | 15519.45 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.159851E+11 | 15519.45 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.133188E+11 | 13937.56 | 02-JAN-08:09 | 0.270551E+11 | 18128.59 | 02-JAN-08:09 |
February | 0.120811E+11 | 13937.56 | 01-FEB-08:09 | 0.244881E+11 | 18128.59 | 01-FEB-08:09 |
March | 0.143557E+11 | 13937.56 | 01-MAR-08:09 | 0.280558E+11 | 18128.59 | 01-MAR-08:09 |
April | 0.128226E+11 | 13937.56 | 03-APR-07:10 | 0.261305E+11 | 18128.59 | 03-APR-07:10 |
May | 0.138373E+11 | 13937.56 | 01-MAY-07:10 | 0.275555E+11 | 18128.59 | 01-MAY-07:10 |
June | 0.137704E+11 | 13937.56 | 01-JUN-07:10 | 0.270261E+11 | 18128.59 | 01-JUN-07:10 |
July | 0.128895E+11 | 13937.56 | 03-JUL-07:10 | 0.266527E+11 | 18128.59 | 03-JUL-07:10 |
August | 0.143557E+11 | 13937.56 | 01-AUG-07:10 | 0.280558E+11 | 18128.59 | 01-AUG-07:10 |
September | 0.128226E+11 | 13937.56 | 01-SEP-07:10 | 0.261160E+11 | 18128.59 | 01-SEP-07:10 |
October | 0.133188E+11 | 13937.56 | 02-OCT-07:10 | 0.270624E+11 | 18128.59 | 02-OCT-07:10 |
November | 0.131627E+11 | 13937.56 | 01-NOV-07:10 | 0.264424E+11 | 18128.59 | 01-NOV-07:10 |
December | 0.128895E+11 | 13937.56 | 01-DEC-08:09 | 0.266454E+11 | 18128.59 | 01-DEC-08:09 |
Annual Sum or Average | 0.159625E+12 | 0.321286E+12 | ||||
Minimum of Months | 0.120811E+11 | 13937.56 | 0.244881E+11 | 18128.59 | ||
Maximum of Months | 0.143557E+11 | 13937.56 | 0.280558E+11 | 18128.59 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.133188E+11 | 13937.56 | 02-JAN-08:09 | 0.270550E+11 | 18128.52 | 02-JAN-08:09 |
February | 0.120811E+11 | 13937.56 | 01-FEB-08:09 | 0.244880E+11 | 18128.52 | 01-FEB-08:09 |
March | 0.143557E+11 | 13937.56 | 01-MAR-08:09 | 0.280557E+11 | 18128.52 | 01-MAR-08:09 |
April | 0.128226E+11 | 13937.56 | 03-APR-07:10 | 0.261304E+11 | 18128.52 | 03-APR-07:10 |
May | 0.138373E+11 | 13937.56 | 01-MAY-07:10 | 0.275554E+11 | 18128.52 | 01-MAY-07:10 |
June | 0.137704E+11 | 13937.56 | 01-JUN-07:10 | 0.270260E+11 | 18128.52 | 01-JUN-07:10 |
July | 0.128895E+11 | 13937.56 | 03-JUL-07:10 | 0.266526E+11 | 18128.52 | 03-JUL-07:10 |
August | 0.143557E+11 | 13937.56 | 01-AUG-07:10 | 0.280557E+11 | 18128.52 | 01-AUG-07:10 |
September | 0.128226E+11 | 13937.56 | 01-SEP-07:10 | 0.261159E+11 | 18128.52 | 01-SEP-07:10 |
October | 0.133188E+11 | 13937.56 | 02-OCT-07:10 | 0.270623E+11 | 18128.52 | 02-OCT-07:10 |
November | 0.131627E+11 | 13937.56 | 01-NOV-07:10 | 0.264423E+11 | 18128.52 | 01-NOV-07:10 |
December | 0.128895E+11 | 13937.56 | 01-DEC-08:09 | 0.266453E+11 | 18128.52 | 01-DEC-08:09 |
Annual Sum or Average | 0.159625E+12 | 0.321285E+12 | ||||
Minimum of Months | 0.120811E+11 | 13937.56 | 0.244880E+11 | 18128.52 | ||
Maximum of Months | 0.143557E+11 | 13937.56 | 0.280557E+11 | 18128.52 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.133188E+11 | 13937.56 | 02-JAN-08:09 | 0.270550E+11 | 18128.52 | 02-JAN-08:09 |
February | 0.120811E+11 | 13937.56 | 01-FEB-08:09 | 0.244880E+11 | 18128.52 | 01-FEB-08:09 |
March | 0.143557E+11 | 13937.56 | 01-MAR-08:09 | 0.280557E+11 | 18128.52 | 01-MAR-08:09 |
April | 0.128226E+11 | 13937.56 | 03-APR-07:10 | 0.261304E+11 | 18128.52 | 03-APR-07:10 |
May | 0.138373E+11 | 13937.56 | 01-MAY-07:10 | 0.275554E+11 | 18128.52 | 01-MAY-07:10 |
June | 0.137704E+11 | 13937.56 | 01-JUN-07:10 | 0.270260E+11 | 18128.52 | 01-JUN-07:10 |
July | 0.128895E+11 | 13937.56 | 03-JUL-07:10 | 0.266526E+11 | 18128.52 | 03-JUL-07:10 |
August | 0.143557E+11 | 13937.56 | 01-AUG-07:10 | 0.280557E+11 | 18128.52 | 01-AUG-07:10 |
September | 0.128226E+11 | 13937.56 | 01-SEP-07:10 | 0.261159E+11 | 18128.52 | 01-SEP-07:10 |
October | 0.133188E+11 | 13937.56 | 02-OCT-07:10 | 0.270623E+11 | 18128.52 | 02-OCT-07:10 |
November | 0.131627E+11 | 13937.56 | 01-NOV-07:10 | 0.264423E+11 | 18128.52 | 01-NOV-07:10 |
December | 0.128895E+11 | 13937.56 | 01-DEC-08:09 | 0.266453E+11 | 18128.52 | 01-DEC-08:09 |
Annual Sum or Average | 0.159625E+12 | 0.321285E+12 | ||||
Minimum of Months | 0.120811E+11 | 13937.56 | 0.244880E+11 | 18128.52 | ||
Maximum of Months | 0.143557E+11 | 13937.56 | 0.280557E+11 | 18128.52 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.119284E+10 | 1518.11 | 18-JAN-08:09 | 0.339718E+10 | 2276.32 | 02-JAN-08:09 |
February | 0.106120E+10 | 1493.71 | 10-FEB-08:09 | 0.307485E+10 | 2276.32 | 01-FEB-08:09 |
March | 0.122685E+10 | 1506.04 | 14-MAR-07:10 | 0.352283E+10 | 2276.32 | 01-MAR-08:09 |
April | 0.108392E+10 | 1075.02 | 03-APR-07:10 | 0.328108E+10 | 2276.32 | 03-APR-07:10 |
May | 0.115420E+10 | 1249.63 | 24-MAY-07:10 | 0.346000E+10 | 2276.32 | 01-MAY-07:10 |
June | 0.114798E+10 | 1240.40 | 23-JUN-07:10 | 0.339353E+10 | 2276.32 | 01-JUN-07:10 |
July | 0.108862E+10 | 1459.75 | 26-JUL-07:10 | 0.334664E+10 | 2276.32 | 03-JUL-07:10 |
August | 0.121752E+10 | 1495.67 | 16-AUG-07:10 | 0.352283E+10 | 2276.32 | 01-AUG-07:10 |
September | 0.110108E+10 | 1531.62 | 08-SEP-07:10 | 0.327926E+10 | 2276.32 | 01-SEP-07:10 |
October | 0.116174E+10 | 1595.59 | 11-OCT-07:10 | 0.339809E+10 | 2276.32 | 02-OCT-07:10 |
November | 0.117402E+10 | 1570.33 | 27-NOV-16:00 | 0.332024E+10 | 2276.32 | 01-NOV-07:10 |
December | 0.116591E+10 | 1578.40 | 29-DEC-16:00 | 0.334573E+10 | 2276.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.137759E+11 | 0.403423E+11 | ||||
Minimum of Months | 0.106120E+10 | 1075.02 | 0.307485E+10 | 2276.32 | ||
Maximum of Months | 0.122685E+10 | 1595.59 | 0.352283E+10 | 2276.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.764375E+09 | 973.30 | 17-JAN-16:00 | 0.218927E+10 | 1466.95 | 02-JAN-08:09 |
February | 0.682979E+09 | 967.62 | 09-FEB-16:00 | 0.198155E+10 | 1466.95 | 01-FEB-08:09 |
March | 0.789745E+09 | 909.26 | 14-MAR-07:10 | 0.227025E+10 | 1466.95 | 01-MAR-08:09 |
April | 0.699325E+09 | 692.79 | 03-APR-07:10 | 0.211446E+10 | 1466.95 | 03-APR-07:10 |
May | 0.746469E+09 | 692.79 | 01-MAY-07:10 | 0.222976E+10 | 1466.95 | 01-MAY-07:10 |
June | 0.742294E+09 | 692.79 | 01-JUN-07:10 | 0.218692E+10 | 1466.95 | 01-JUN-07:10 |
July | 0.702323E+09 | 917.91 | 26-JUL-07:10 | 0.215670E+10 | 1466.95 | 03-JUL-07:10 |
August | 0.784517E+09 | 943.58 | 16-AUG-07:10 | 0.227025E+10 | 1466.95 | 01-AUG-07:10 |
September | 0.709467E+09 | 968.41 | 07-SEP-07:10 | 0.211328E+10 | 1466.95 | 01-SEP-07:10 |
October | 0.745665E+09 | 1016.67 | 11-OCT-07:10 | 0.218986E+10 | 1466.95 | 02-OCT-07:10 |
November | 0.755439E+09 | 1029.58 | 27-NOV-16:00 | 0.213969E+10 | 1466.95 | 01-NOV-07:10 |
December | 0.747625E+09 | 1023.86 | 29-DEC-16:00 | 0.215612E+10 | 1466.95 | 01-DEC-08:09 |
Annual Sum or Average | 0.887022E+10 | 0.259981E+11 | ||||
Minimum of Months | 0.682979E+09 | 692.79 | 0.198155E+10 | 1466.95 | ||
Maximum of Months | 0.789745E+09 | 1029.58 | 0.227025E+10 | 1466.95 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.116785E+10 | 1473.40 | 18-JAN-08:09 | 0.339723E+10 | 2276.35 | 02-JAN-08:09 |
February | 0.104951E+10 | 1456.78 | 10-FEB-08:09 | 0.307490E+10 | 2276.35 | 01-FEB-08:09 |
March | 0.122283E+10 | 1492.56 | 14-MAR-07:10 | 0.352288E+10 | 2276.35 | 01-MAR-08:09 |
April | 0.108531E+10 | 1075.05 | 03-APR-07:10 | 0.328113E+10 | 2276.35 | 03-APR-07:10 |
May | 0.115978E+10 | 1287.72 | 24-MAY-07:10 | 0.346006E+10 | 2276.35 | 01-MAY-07:10 |
June | 0.115290E+10 | 1296.72 | 23-JUN-07:10 | 0.339359E+10 | 2276.35 | 01-JUN-07:10 |
July | 0.109261E+10 | 1476.24 | 26-JUL-07:10 | 0.334669E+10 | 2276.35 | 03-JUL-07:10 |
August | 0.121960E+10 | 1502.97 | 16-AUG-07:10 | 0.352288E+10 | 2276.35 | 01-AUG-07:10 |
September | 0.110006E+10 | 1529.49 | 08-SEP-07:10 | 0.327931E+10 | 2276.35 | 01-SEP-07:10 |
October | 0.115302E+10 | 1589.31 | 11-OCT-07:10 | 0.339814E+10 | 2276.35 | 02-OCT-07:10 |
November | 0.115440E+10 | 1476.84 | 27-NOV-16:00 | 0.332029E+10 | 2276.35 | 01-NOV-07:10 |
December | 0.113822E+10 | 1537.17 | 29-DEC-16:00 | 0.334578E+10 | 2276.35 | 01-DEC-08:09 |
Annual Sum or Average | 0.136961E+11 | 0.403429E+11 | ||||
Minimum of Months | 0.104951E+10 | 1075.05 | 0.307490E+10 | 2276.35 | ||
Maximum of Months | 0.122283E+10 | 1589.31 | 0.352288E+10 | 2276.35 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.761171E+09 | 985.07 | 18-JAN-08:09 | 0.218926E+10 | 1466.94 | 02-JAN-08:09 |
February | 0.679755E+09 | 972.30 | 10-FEB-08:09 | 0.198154E+10 | 1466.94 | 01-FEB-08:09 |
March | 0.791821E+09 | 995.66 | 14-MAR-07:10 | 0.227023E+10 | 1466.94 | 01-MAR-08:09 |
April | 0.699843E+09 | 858.71 | 03-APR-07:10 | 0.211444E+10 | 1466.94 | 03-APR-07:10 |
May | 0.747200E+09 | 866.74 | 24-MAY-07:10 | 0.222974E+10 | 1466.94 | 01-MAY-07:10 |
June | 0.742235E+09 | 868.08 | 23-JUN-07:10 | 0.218691E+10 | 1466.94 | 01-JUN-07:10 |
July | 0.704269E+09 | 961.95 | 26-JUL-07:10 | 0.215669E+10 | 1466.94 | 03-JUL-07:10 |
August | 0.787792E+09 | 979.52 | 16-AUG-07:10 | 0.227023E+10 | 1466.94 | 01-AUG-07:10 |
September | 0.711323E+09 | 997.33 | 08-SEP-07:10 | 0.211327E+10 | 1466.94 | 01-SEP-07:10 |
October | 0.750330E+09 | 1032.79 | 11-OCT-07:10 | 0.218984E+10 | 1466.94 | 02-OCT-07:10 |
November | 0.747485E+09 | 959.54 | 03-NOV-07:10 | 0.213967E+10 | 1466.94 | 01-NOV-07:10 |
December | 0.739528E+09 | 977.42 | 29-DEC-16:00 | 0.215610E+10 | 1466.94 | 01-DEC-08:09 |
Annual Sum or Average | 0.886275E+10 | 0.259979E+11 | ||||
Minimum of Months | 0.679755E+09 | 858.71 | 0.198154E+10 | 1466.94 | ||
Maximum of Months | 0.791821E+09 | 1032.79 | 0.227023E+10 | 1466.94 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.119505E+10 | 1524.72 | 18-JAN-08:09 | 0.339718E+10 | 2276.32 | 02-JAN-08:09 |
February | 0.106222E+10 | 1501.05 | 10-FEB-08:09 | 0.307485E+10 | 2276.32 | 01-FEB-08:09 |
March | 0.122769E+10 | 1513.20 | 14-MAR-07:10 | 0.352283E+10 | 2276.32 | 01-MAR-08:09 |
April | 0.108421E+10 | 1075.02 | 03-APR-07:10 | 0.328108E+10 | 2276.32 | 03-APR-07:10 |
May | 0.115539E+10 | 1264.06 | 24-MAY-07:10 | 0.346000E+10 | 2276.32 | 01-MAY-07:10 |
June | 0.114884E+10 | 1255.10 | 23-JUN-07:10 | 0.339353E+10 | 2276.32 | 01-JUN-07:10 |
July | 0.108930E+10 | 1468.23 | 26-JUL-07:10 | 0.334664E+10 | 2276.32 | 03-JUL-07:10 |
August | 0.121857E+10 | 1503.11 | 16-AUG-07:10 | 0.352283E+10 | 2276.32 | 01-AUG-07:10 |
September | 0.110214E+10 | 1538.01 | 08-SEP-07:10 | 0.327926E+10 | 2276.32 | 01-SEP-07:10 |
October | 0.116304E+10 | 1600.11 | 11-OCT-07:10 | 0.339809E+10 | 2276.32 | 02-OCT-07:10 |
November | 0.117563E+10 | 1575.52 | 27-NOV-16:00 | 0.332024E+10 | 2276.32 | 01-NOV-07:10 |
December | 0.116805E+10 | 1583.38 | 29-DEC-16:00 | 0.334573E+10 | 2276.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.137901E+11 | 0.403423E+11 | ||||
Minimum of Months | 0.106222E+10 | 1075.02 | 0.307485E+10 | 2276.32 | ||
Maximum of Months | 0.122769E+10 | 1600.11 | 0.352283E+10 | 2276.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.764789E+09 | 974.56 | 17-JAN-16:00 | 0.218927E+10 | 1466.95 | 02-JAN-08:09 |
February | 0.683231E+09 | 968.84 | 09-FEB-16:00 | 0.198155E+10 | 1466.95 | 01-FEB-08:09 |
March | 0.790057E+09 | 911.74 | 14-MAR-07:10 | 0.227025E+10 | 1466.95 | 01-MAR-08:09 |
April | 0.699478E+09 | 692.79 | 03-APR-07:10 | 0.211446E+10 | 1466.95 | 03-APR-07:10 |
May | 0.746630E+09 | 692.79 | 01-MAY-07:10 | 0.222976E+10 | 1466.95 | 01-MAY-07:10 |
June | 0.742404E+09 | 692.79 | 01-JUN-07:10 | 0.218692E+10 | 1466.95 | 01-JUN-07:10 |
July | 0.702580E+09 | 921.23 | 26-JUL-07:10 | 0.215670E+10 | 1466.95 | 03-JUL-07:10 |
August | 0.784739E+09 | 945.96 | 16-AUG-07:10 | 0.227025E+10 | 1466.95 | 01-AUG-07:10 |
September | 0.709644E+09 | 970.43 | 08-SEP-07:10 | 0.211328E+10 | 1466.95 | 01-SEP-07:10 |
October | 0.745801E+09 | 1017.83 | 11-OCT-07:10 | 0.218986E+10 | 1466.95 | 02-OCT-07:10 |
November | 0.755814E+09 | 1030.46 | 27-NOV-16:00 | 0.213969E+10 | 1466.95 | 01-NOV-07:10 |
December | 0.748082E+09 | 1024.69 | 29-DEC-16:00 | 0.215612E+10 | 1466.95 | 01-DEC-08:09 |
Annual Sum or Average | 0.887325E+10 | 0.259981E+11 | ||||
Minimum of Months | 0.683231E+09 | 692.79 | 0.198155E+10 | 1466.95 | ||
Maximum of Months | 0.790057E+09 | 1030.46 | 0.227025E+10 | 1466.95 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.117096E+10 | 1483.05 | 18-JAN-08:09 | 0.339723E+10 | 2276.35 | 02-JAN-08:09 |
February | 0.104998E+10 | 1465.43 | 10-FEB-08:09 | 0.307490E+10 | 2276.35 | 01-FEB-08:09 |
March | 0.122342E+10 | 1500.25 | 14-MAR-07:10 | 0.352288E+10 | 2276.35 | 01-MAR-08:09 |
April | 0.108567E+10 | 1075.05 | 03-APR-07:10 | 0.328113E+10 | 2276.35 | 03-APR-07:10 |
May | 0.116037E+10 | 1300.75 | 24-MAY-07:10 | 0.346006E+10 | 2276.35 | 01-MAY-07:10 |
June | 0.115367E+10 | 1309.39 | 23-JUN-07:10 | 0.339359E+10 | 2276.35 | 01-JUN-07:10 |
July | 0.109362E+10 | 1484.11 | 26-JUL-07:10 | 0.334669E+10 | 2276.35 | 03-JUL-07:10 |
August | 0.122041E+10 | 1510.13 | 16-AUG-07:10 | 0.352288E+10 | 2276.35 | 01-AUG-07:10 |
September | 0.110069E+10 | 1535.96 | 08-SEP-07:10 | 0.327931E+10 | 2276.35 | 01-SEP-07:10 |
October | 0.115247E+10 | 1594.09 | 11-OCT-07:10 | 0.339814E+10 | 2276.35 | 02-OCT-07:10 |
November | 0.115511E+10 | 1485.33 | 27-NOV-16:00 | 0.332029E+10 | 2276.35 | 01-NOV-07:10 |
December | 0.113972E+10 | 1543.67 | 29-DEC-16:00 | 0.334578E+10 | 2276.35 | 01-DEC-08:09 |
Annual Sum or Average | 0.137061E+11 | 0.403429E+11 | ||||
Minimum of Months | 0.104998E+10 | 1075.05 | 0.307490E+10 | 2276.35 | ||
Maximum of Months | 0.122342E+10 | 1594.09 | 0.352288E+10 | 2276.35 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.761629E+09 | 986.19 | 18-JAN-08:09 | 0.218926E+10 | 1466.94 | 02-JAN-08:09 |
February | 0.680120E+09 | 973.47 | 10-FEB-08:09 | 0.198154E+10 | 1466.94 | 01-FEB-08:09 |
March | 0.792152E+09 | 996.62 | 14-MAR-07:10 | 0.227023E+10 | 1466.94 | 01-MAR-08:09 |
April | 0.700030E+09 | 861.42 | 03-APR-07:10 | 0.211444E+10 | 1466.94 | 03-APR-07:10 |
May | 0.747333E+09 | 868.65 | 24-MAY-07:10 | 0.222974E+10 | 1466.94 | 01-MAY-07:10 |
June | 0.742337E+09 | 869.98 | 23-JUN-07:10 | 0.218691E+10 | 1466.94 | 01-JUN-07:10 |
July | 0.704619E+09 | 963.17 | 26-JUL-07:10 | 0.215669E+10 | 1466.94 | 03-JUL-07:10 |
August | 0.788011E+09 | 980.60 | 16-AUG-07:10 | 0.227023E+10 | 1466.94 | 01-AUG-07:10 |
September | 0.711551E+09 | 998.29 | 08-SEP-07:10 | 0.211327E+10 | 1466.94 | 01-SEP-07:10 |
October | 0.750650E+09 | 1033.49 | 11-OCT-07:10 | 0.218984E+10 | 1466.94 | 02-OCT-07:10 |
November | 0.747778E+09 | 961.41 | 03-NOV-07:10 | 0.213967E+10 | 1466.94 | 01-NOV-07:10 |
December | 0.739903E+09 | 979.00 | 29-DEC-16:00 | 0.215610E+10 | 1466.94 | 01-DEC-08:09 |
Annual Sum or Average | 0.886611E+10 | 0.259979E+11 | ||||
Minimum of Months | 0.680120E+09 | 861.42 | 0.198154E+10 | 1466.94 | ||
Maximum of Months | 0.792152E+09 | 1033.49 | 0.227023E+10 | 1466.94 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.119506E+10 | 1524.51 | 18-JAN-08:09 | 0.339718E+10 | 2276.32 | 02-JAN-08:09 |
February | 0.106222E+10 | 1500.81 | 10-FEB-08:09 | 0.307485E+10 | 2276.32 | 01-FEB-08:09 |
March | 0.122769E+10 | 1513.02 | 14-MAR-07:10 | 0.352283E+10 | 2276.32 | 01-MAR-08:09 |
April | 0.108422E+10 | 1075.02 | 03-APR-07:10 | 0.328108E+10 | 2276.32 | 03-APR-07:10 |
May | 0.115539E+10 | 1263.67 | 24-MAY-07:10 | 0.346000E+10 | 2276.32 | 01-MAY-07:10 |
June | 0.114881E+10 | 1254.71 | 23-JUN-07:10 | 0.339353E+10 | 2276.32 | 01-JUN-07:10 |
July | 0.108928E+10 | 1467.96 | 26-JUL-07:10 | 0.334664E+10 | 2276.32 | 03-JUL-07:10 |
August | 0.121849E+10 | 1502.87 | 16-AUG-07:10 | 0.352283E+10 | 2276.32 | 01-AUG-07:10 |
September | 0.110213E+10 | 1537.80 | 08-SEP-07:10 | 0.327926E+10 | 2276.32 | 01-SEP-07:10 |
October | 0.116303E+10 | 1599.95 | 11-OCT-07:10 | 0.339809E+10 | 2276.32 | 02-OCT-07:10 |
November | 0.117563E+10 | 1575.44 | 27-NOV-16:00 | 0.332024E+10 | 2276.32 | 01-NOV-07:10 |
December | 0.116806E+10 | 1583.24 | 29-DEC-16:00 | 0.334573E+10 | 2276.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.137900E+11 | 0.403423E+11 | ||||
Minimum of Months | 0.106222E+10 | 1075.02 | 0.307485E+10 | 2276.32 | ||
Maximum of Months | 0.122769E+10 | 1599.95 | 0.352283E+10 | 2276.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.764799E+09 | 974.44 | 17-JAN-16:00 | 0.218927E+10 | 1466.95 | 02-JAN-08:09 |
February | 0.683233E+09 | 968.69 | 09-FEB-16:00 | 0.198155E+10 | 1466.95 | 01-FEB-08:09 |
March | 0.790061E+09 | 911.68 | 14-MAR-07:10 | 0.227025E+10 | 1466.95 | 01-MAR-08:09 |
April | 0.699481E+09 | 692.79 | 03-APR-07:10 | 0.211446E+10 | 1466.95 | 03-APR-07:10 |
May | 0.746628E+09 | 692.79 | 01-MAY-07:10 | 0.222976E+10 | 1466.95 | 01-MAY-07:10 |
June | 0.742399E+09 | 692.79 | 01-JUN-07:10 | 0.218692E+10 | 1466.95 | 01-JUN-07:10 |
July | 0.702572E+09 | 921.10 | 26-JUL-07:10 | 0.215670E+10 | 1466.95 | 03-JUL-07:10 |
August | 0.784732E+09 | 945.84 | 16-AUG-07:10 | 0.227025E+10 | 1466.95 | 01-AUG-07:10 |
September | 0.709641E+09 | 970.32 | 08-SEP-07:10 | 0.211328E+10 | 1466.95 | 01-SEP-07:10 |
October | 0.745800E+09 | 1017.75 | 11-OCT-07:10 | 0.218986E+10 | 1466.95 | 02-OCT-07:10 |
November | 0.755818E+09 | 1030.41 | 27-NOV-16:00 | 0.213969E+10 | 1466.95 | 01-NOV-07:10 |
December | 0.748091E+09 | 1024.60 | 29-DEC-16:00 | 0.215612E+10 | 1466.95 | 01-DEC-08:09 |
Annual Sum or Average | 0.887325E+10 | 0.259981E+11 | ||||
Minimum of Months | 0.683233E+09 | 692.79 | 0.198155E+10 | 1466.95 | ||
Maximum of Months | 0.790061E+09 | 1030.41 | 0.227025E+10 | 1466.95 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.117097E+10 | 1482.85 | 18-JAN-08:09 | 0.339723E+10 | 2276.35 | 02-JAN-08:09 |
February | 0.104998E+10 | 1465.20 | 10-FEB-08:09 | 0.307490E+10 | 2276.35 | 01-FEB-08:09 |
March | 0.122342E+10 | 1500.08 | 14-MAR-07:10 | 0.352288E+10 | 2276.35 | 01-MAR-08:09 |
April | 0.108567E+10 | 1075.05 | 03-APR-07:10 | 0.328113E+10 | 2276.35 | 03-APR-07:10 |
May | 0.116036E+10 | 1300.36 | 24-MAY-07:10 | 0.346006E+10 | 2276.35 | 01-MAY-07:10 |
June | 0.115365E+10 | 1309.00 | 23-JUN-07:10 | 0.339359E+10 | 2276.35 | 01-JUN-07:10 |
July | 0.109360E+10 | 1483.84 | 26-JUL-07:10 | 0.334669E+10 | 2276.35 | 03-JUL-07:10 |
August | 0.122039E+10 | 1509.89 | 16-AUG-07:10 | 0.352288E+10 | 2276.35 | 01-AUG-07:10 |
September | 0.110068E+10 | 1535.75 | 08-SEP-07:10 | 0.327931E+10 | 2276.35 | 01-SEP-07:10 |
October | 0.115247E+10 | 1593.94 | 11-OCT-07:10 | 0.339814E+10 | 2276.35 | 02-OCT-07:10 |
November | 0.115512E+10 | 1485.29 | 27-NOV-16:00 | 0.332029E+10 | 2276.35 | 01-NOV-07:10 |
December | 0.113975E+10 | 1543.55 | 29-DEC-16:00 | 0.334578E+10 | 2276.35 | 01-DEC-08:09 |
Annual Sum or Average | 0.137061E+11 | 0.403429E+11 | ||||
Minimum of Months | 0.104998E+10 | 1075.05 | 0.307490E+10 | 2276.35 | ||
Maximum of Months | 0.122342E+10 | 1593.94 | 0.352288E+10 | 2276.35 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.761640E+09 | 986.06 | 18-JAN-08:09 | 0.218926E+10 | 1466.94 | 02-JAN-08:09 |
February | 0.680124E+09 | 973.33 | 10-FEB-08:09 | 0.198154E+10 | 1466.94 | 01-FEB-08:09 |
March | 0.792177E+09 | 996.51 | 14-MAR-07:10 | 0.227023E+10 | 1466.94 | 01-MAR-08:09 |
April | 0.700034E+09 | 861.42 | 03-APR-07:10 | 0.211444E+10 | 1466.94 | 03-APR-07:10 |
May | 0.747331E+09 | 868.41 | 24-MAY-07:10 | 0.222974E+10 | 1466.94 | 01-MAY-07:10 |
June | 0.742331E+09 | 869.75 | 23-JUN-07:10 | 0.218691E+10 | 1466.94 | 01-JUN-07:10 |
July | 0.704606E+09 | 963.00 | 26-JUL-07:10 | 0.215669E+10 | 1466.94 | 03-JUL-07:10 |
August | 0.787999E+09 | 980.46 | 16-AUG-07:10 | 0.227023E+10 | 1466.94 | 01-AUG-07:10 |
September | 0.711546E+09 | 998.16 | 08-SEP-07:10 | 0.211327E+10 | 1466.94 | 01-SEP-07:10 |
October | 0.750648E+09 | 1033.39 | 11-OCT-07:10 | 0.218984E+10 | 1466.94 | 02-OCT-07:10 |
November | 0.747830E+09 | 961.38 | 03-NOV-07:10 | 0.213967E+10 | 1466.94 | 01-NOV-07:10 |
December | 0.739913E+09 | 978.95 | 29-DEC-16:00 | 0.215610E+10 | 1466.94 | 01-DEC-08:09 |
Annual Sum or Average | 0.886618E+10 | 0.259979E+11 | ||||
Minimum of Months | 0.680124E+09 | 861.42 | 0.198154E+10 | 1466.94 | ||
Maximum of Months | 0.792177E+09 | 1033.39 | 0.227023E+10 | 1466.94 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.387117E+09 | 405.10 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.351144E+09 | 405.10 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.417256E+09 | 405.10 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.372695E+09 | 405.10 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.402187E+09 | 405.10 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.400242E+09 | 405.10 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.374640E+09 | 405.10 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.417256E+09 | 405.10 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.372695E+09 | 405.10 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.387117E+09 | 405.10 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.382580E+09 | 405.10 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.374640E+09 | 405.10 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.463957E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.351144E+09 | 405.10 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.417256E+09 | 405.10 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.387117E+09 | 405.10 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.351144E+09 | 405.10 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.417256E+09 | 405.10 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.372695E+09 | 405.10 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.402187E+09 | 405.10 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.400242E+09 | 405.10 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.374640E+09 | 405.10 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.417256E+09 | 405.10 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.372695E+09 | 405.10 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.387117E+09 | 405.10 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.382580E+09 | 405.10 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.374640E+09 | 405.10 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.463957E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.351144E+09 | 405.10 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.417256E+09 | 405.10 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.387117E+09 | 405.10 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.351144E+09 | 405.10 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.417256E+09 | 405.10 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.372695E+09 | 405.10 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.402187E+09 | 405.10 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.400242E+09 | 405.10 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.374640E+09 | 405.10 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.417256E+09 | 405.10 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.372695E+09 | 405.10 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.387117E+09 | 405.10 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.382580E+09 | 405.10 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.374640E+09 | 405.10 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.463957E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.351144E+09 | 405.10 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.417256E+09 | 405.10 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.418155E+10 | 4375.82 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.379298E+10 | 4375.82 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.450711E+10 | 4375.82 | 01-MAR-08:09 | 0.762947E+12 | 379632.52 | 31-MAR-23:10 |
April | 0.402577E+10 | 4375.82 | 03-APR-07:10 | 0.982982E+12 | 379632.52 | 01-APR-00:10 |
May | 0.434433E+10 | 4375.82 | 01-MAY-07:10 | 0.254544E+12 | 189816.26 | 31-MAY-23:10 |
June | 0.432333E+10 | 4375.82 | 01-JUN-07:10 | 0.492345E+12 | 284724.39 | 30-JUN-23:10 |
July | 0.404678E+10 | 4375.82 | 03-JUL-07:10 | 0.762947E+12 | 379632.52 | 31-JUL-23:10 |
August | 0.450711E+10 | 4375.82 | 01-AUG-07:10 | 0.101578E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.402577E+10 | 4375.82 | 01-SEP-07:10 | 0.246344E+12 | 189816.26 | 30-SEP-23:10 |
October | 0.418155E+10 | 4375.82 | 02-OCT-07:10 | 0.508746E+12 | 284724.39 | 31-OCT-23:10 |
November | 0.413254E+10 | 4375.82 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.404678E+10 | 4375.82 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.501156E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.379298E+10 | 4375.82 | 0.246344E+12 | 94908.13 | ||
Maximum of Months | 0.450711E+10 | 4375.82 | 0.101681E+13 | 379632.52 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.148304E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.134523E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.159851E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.142779E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.154078E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.153333E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.143524E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.159851E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.142779E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.148304E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.146566E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.143524E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.177742E+12 | 0.424397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121482E+11 | 0.134523E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.159851E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.133188E+11 | 0.270551E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.120811E+11 | 0.244881E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.143557E+11 | 0.280558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.128226E+11 | 0.261305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.138373E+11 | 0.275555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.137704E+11 | 0.270261E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.128895E+11 | 0.266527E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.143557E+11 | 0.280558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.128226E+11 | 0.261160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.133188E+11 | 0.270624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.131627E+11 | 0.264424E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.128895E+11 | 0.266454E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.159625E+12 | 0.321286E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.120811E+11 | 0.244881E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.143557E+11 | 0.280558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.133188E+11 | 0.270550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.120811E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.143557E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.128226E+11 | 0.261304E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.138373E+11 | 0.275554E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.137704E+11 | 0.270260E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.128895E+11 | 0.266526E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.143557E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.128226E+11 | 0.261159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.133188E+11 | 0.270623E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.131627E+11 | 0.264423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.128895E+11 | 0.266453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.159625E+12 | 0.321285E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.120811E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.143557E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.133188E+11 | 0.270550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.120811E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.143557E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.128226E+11 | 0.261304E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.138373E+11 | 0.275554E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.137704E+11 | 0.270260E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.128895E+11 | 0.266526E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.143557E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.128226E+11 | 0.261159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.133188E+11 | 0.270623E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.131627E+11 | 0.264423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.128895E+11 | 0.266453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.159625E+12 | 0.321285E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.120811E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.143557E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.119284E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92835788.06 |
February | 0.136985E+10 | 0.106120E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1173983.16 | 97095714.94 |
March | 0.163685E+10 | 0.122685E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17765040.71 | 57889427.47 |
April | 0.145243E+10 | 0.108392E+10 | 0.328108E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70487126.86 | 3598592.31 |
May | 0.157338E+10 | 0.115420E+10 | 0.346000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153891E+09 | 1225959.64 |
June | 0.156900E+10 | 0.114798E+10 | 0.339353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104434E+09 | 651768.59 |
July | 0.145680E+10 | 0.108862E+10 | 0.334664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131907E+09 | 242510.18 |
August | 0.163685E+10 | 0.121752E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 74750431.20 | 439329.29 |
September | 0.145243E+10 | 0.110108E+10 | 0.327926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43627017.24 | 1280876.24 |
October | 0.150991E+10 | 0.116174E+10 | 0.339809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22813638.11 | 4725393.63 |
November | 0.149516E+10 | 0.117402E+10 | 0.332024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4774899.18 | 20436125.63 |
December | 0.145680E+10 | 0.116591E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39168.28 | 84273795.94 |
Annual Sum or Average | 0.181194E+11 | 0.137759E+11 | 0.403423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.625663E+09 | 0.364695E+09 |
Minimum of Months | 0.136985E+10 | 0.106120E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 242510.18 |
Maximum of Months | 0.163685E+10 | 0.122685E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153891E+09 | 97095714.94 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.764375E+09 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62357929.06 |
February | 0.882782E+09 | 0.682979E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 679772.72 | 65367332.69 |
March | 0.105485E+10 | 0.789745E+09 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11313142.89 | 37738667.49 |
April | 0.936002E+09 | 0.699325E+09 | 0.211446E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46728044.69 | 2094645.24 |
May | 0.101394E+10 | 0.746469E+09 | 0.222976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102033E+09 | 781939.55 |
June | 0.101113E+10 | 0.742294E+09 | 0.218692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70645429.58 | 343269.84 |
July | 0.938820E+09 | 0.702323E+09 | 0.215670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 90864726.77 | 99525.03 |
August | 0.105485E+10 | 0.784517E+09 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52645602.01 | 165381.96 |
September | 0.936002E+09 | 0.709467E+09 | 0.211328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29486653.19 | 668692.46 |
October | 0.973041E+09 | 0.745665E+09 | 0.218986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14644309.56 | 3164567.21 |
November | 0.963541E+09 | 0.755439E+09 | 0.213969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3066434.55 | 13789076.44 |
December | 0.938820E+09 | 0.747625E+09 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19983.27 | 55392655.17 |
Annual Sum or Average | 0.116768E+11 | 0.887022E+10 | 0.259981E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.422127E+09 | 0.241964E+09 |
Minimum of Months | 0.882782E+09 | 0.682979E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99525.03 |
Maximum of Months | 0.105485E+10 | 0.789745E+09 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102033E+09 | 65367332.69 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.116785E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97227386.92 |
February | 0.136988E+10 | 0.104951E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 871414.26 | 0.105252E+09 |
March | 0.163688E+10 | 0.122283E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15487704.85 | 63427324.05 |
April | 0.145246E+10 | 0.108531E+10 | 0.328113E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68014243.69 | 4105131.54 |
May | 0.157341E+10 | 0.115978E+10 | 0.346006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152745E+09 | 1247682.33 |
June | 0.156904E+10 | 0.115290E+10 | 0.339359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104280E+09 | 665340.99 |
July | 0.145684E+10 | 0.109261E+10 | 0.334669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131691E+09 | 238637.37 |
August | 0.163688E+10 | 0.121960E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 74291341.26 | 465240.21 |
September | 0.145246E+10 | 0.110006E+10 | 0.327931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42328186.67 | 1257065.64 |
October | 0.150994E+10 | 0.115302E+10 | 0.339814E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20576022.53 | 5331997.09 |
November | 0.149520E+10 | 0.115440E+10 | 0.332029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3755160.17 | 23123237.61 |
December | 0.145684E+10 | 0.113822E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17138.20 | 91077700.38 |
Annual Sum or Average | 0.181198E+11 | 0.136961E+11 | 0.403429E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.614057E+09 | 0.393419E+09 |
Minimum of Months | 0.136988E+10 | 0.104951E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 238637.37 |
Maximum of Months | 0.163688E+10 | 0.122283E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152745E+09 | 0.105252E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.761171E+09 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67811360.14 |
February | 0.882782E+09 | 0.679755E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 585498.94 | 75310118.86 |
March | 0.105485E+10 | 0.791821E+09 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10199523.63 | 49538751.56 |
April | 0.936002E+09 | 0.699843E+09 | 0.211444E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43347318.29 | 4908433.61 |
May | 0.101394E+10 | 0.747200E+09 | 0.222974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 99123460.64 | 1212720.45 |
June | 0.101113E+10 | 0.742235E+09 | 0.218691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66611335.74 | 771423.28 |
July | 0.938820E+09 | 0.704269E+09 | 0.215669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 82227989.62 | 325538.85 |
August | 0.105485E+10 | 0.787792E+09 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44874927.94 | 767315.92 |
September | 0.936002E+09 | 0.711323E+09 | 0.211327E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27650875.25 | 1593750.49 |
October | 0.973041E+09 | 0.750330E+09 | 0.218984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14034263.67 | 3987784.29 |
November | 0.963541E+09 | 0.747485E+09 | 0.213967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2579012.42 | 16260982.54 |
December | 0.938820E+09 | 0.739528E+09 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11544.94 | 66096259.93 |
Annual Sum or Average | 0.116768E+11 | 0.886275E+10 | 0.259979E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.391246E+09 | 0.288584E+09 |
Minimum of Months | 0.882782E+09 | 0.679755E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 325538.85 |
Maximum of Months | 0.105485E+10 | 0.791821E+09 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 99123460.64 | 75310118.86 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.119505E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64820.85 | 0.187772E+09 |
February | 0.136985E+10 | 0.106222E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4814185.63 | 0.202243E+09 |
March | 0.163685E+10 | 0.122769E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42569536.46 | 0.132834E+09 |
April | 0.145243E+10 | 0.108421E+10 | 0.328108E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164833E+09 | 12021827.71 |
May | 0.157338E+10 | 0.115539E+10 | 0.346000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.350731E+09 | 3152443.47 |
June | 0.156900E+10 | 0.114884E+10 | 0.339353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237715E+09 | 2330402.12 |
July | 0.145680E+10 | 0.108930E+10 | 0.334664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293630E+09 | 962929.58 |
August | 0.163685E+10 | 0.121857E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168299E+09 | 1870671.64 |
September | 0.145243E+10 | 0.110214E+10 | 0.327926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 97662164.75 | 3507269.47 |
October | 0.150991E+10 | 0.116304E+10 | 0.339809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53480617.31 | 11415300.31 |
November | 0.149516E+10 | 0.117563E+10 | 0.332024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13037993.32 | 42697834.67 |
December | 0.145680E+10 | 0.116805E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1202253.11 | 0.168719E+09 |
Annual Sum or Average | 0.181194E+11 | 0.137901E+11 | 0.403423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142804E+10 | 0.769527E+09 |
Minimum of Months | 0.136985E+10 | 0.106222E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64820.85 | 962929.58 |
Maximum of Months | 0.163685E+10 | 0.122769E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.350731E+09 | 0.202243E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.764789E+09 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132286E+09 |
February | 0.649041E+09 | 0.683231E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1692514.49 | 0.144641E+09 |
March | 0.773965E+09 | 0.790057E+09 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24857394.98 | 95375393.19 |
April | 0.688021E+09 | 0.699478E+09 | 0.211446E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104755E+09 | 9487095.13 |
May | 0.744847E+09 | 0.746630E+09 | 0.222976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230735E+09 | 2272397.77 |
June | 0.742030E+09 | 0.742404E+09 | 0.218692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158132E+09 | 1608367.46 |
July | 0.690839E+09 | 0.702580E+09 | 0.215670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195903E+09 | 648804.78 |
August | 0.773965E+09 | 0.784739E+09 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111739E+09 | 1283508.47 |
September | 0.688021E+09 | 0.709644E+09 | 0.211328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64468074.79 | 2310273.56 |
October | 0.715730E+09 | 0.745801E+09 | 0.218986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33218077.06 | 8377805.06 |
November | 0.708685E+09 | 0.755814E+09 | 0.213969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7107490.61 | 31086896.67 |
December | 0.690839E+09 | 0.748082E+09 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 277786.04 | 0.119800E+09 |
Annual Sum or Average | 0.858171E+10 | 0.887325E+10 | 0.259981E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.932885E+09 | 0.549177E+09 |
Minimum of Months | 0.649041E+09 | 0.683231E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 648804.78 |
Maximum of Months | 0.773965E+09 | 0.790057E+09 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230735E+09 | 0.144641E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.117096E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222136E+09 |
February | 0.136988E+10 | 0.104998E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1853761.76 | 0.242305E+09 |
March | 0.163688E+10 | 0.122342E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34625541.47 | 0.153790E+09 |
April | 0.145246E+10 | 0.108567E+10 | 0.328113E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157081E+09 | 14095750.48 |
May | 0.157341E+10 | 0.116037E+10 | 0.346006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.348908E+09 | 3264974.59 |
June | 0.156904E+10 | 0.115367E+10 | 0.339359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237967E+09 | 2283710.29 |
July | 0.145684E+10 | 0.109362E+10 | 0.334669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293546E+09 | 966210.90 |
August | 0.163688E+10 | 0.122041E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166349E+09 | 1957324.97 |
September | 0.145246E+10 | 0.110069E+10 | 0.327931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 94238383.17 | 3823270.13 |
October | 0.150994E+10 | 0.115247E+10 | 0.339814E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46767086.28 | 13610759.89 |
November | 0.149520E+10 | 0.115511E+10 | 0.332029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8332042.23 | 54160856.27 |
December | 0.145684E+10 | 0.113972E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29183.99 | 0.208520E+09 |
Annual Sum or Average | 0.181198E+11 | 0.137061E+11 | 0.403429E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138970E+10 | 0.920913E+09 |
Minimum of Months | 0.136988E+10 | 0.104998E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 966210.90 |
Maximum of Months | 0.163688E+10 | 0.122342E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.348908E+09 | 0.242305E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.761629E+09 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135883E+09 |
February | 0.882782E+09 | 0.680120E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1506527.16 | 0.149110E+09 |
March | 0.105485E+10 | 0.792152E+09 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24658184.96 | 0.103311E+09 |
April | 0.936002E+09 | 0.700030E+09 | 0.211444E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103708E+09 | 10961728.85 |
May | 0.101394E+10 | 0.747333E+09 | 0.222974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227791E+09 | 2878043.79 |
June | 0.101113E+10 | 0.742337E+09 | 0.218691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154865E+09 | 2059451.44 |
July | 0.938820E+09 | 0.704619E+09 | 0.215669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191205E+09 | 841195.52 |
August | 0.105485E+10 | 0.788011E+09 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108301E+09 | 1639994.88 |
September | 0.936002E+09 | 0.711551E+09 | 0.211327E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62798007.48 | 3063546.41 |
October | 0.973041E+09 | 0.750650E+09 | 0.218984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33237166.21 | 8497395.76 |
November | 0.963541E+09 | 0.747778E+09 | 0.213967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6883757.07 | 31416263.78 |
December | 0.938820E+09 | 0.739903E+09 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 109025.09 | 0.123379E+09 |
Annual Sum or Average | 0.116768E+11 | 0.886611E+10 | 0.259979E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.915064E+09 | 0.573041E+09 |
Minimum of Months | 0.882782E+09 | 0.680120E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 841195.52 |
Maximum of Months | 0.105485E+10 | 0.792152E+09 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227791E+09 | 0.149110E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.119506E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 352890.87 | 0.192789E+09 |
February | 0.136985E+10 | 0.106222E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7891049.19 | 0.221903E+09 |
March | 0.163685E+10 | 0.122769E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51205953.38 | 0.158233E+09 |
April | 0.145243E+10 | 0.108422E+10 | 0.328108E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197552E+09 | 15029560.82 |
May | 0.157338E+10 | 0.115539E+10 | 0.346000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.425611E+09 | 4120380.71 |
June | 0.156900E+10 | 0.114881E+10 | 0.339353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288062E+09 | 3197554.43 |
July | 0.145680E+10 | 0.108928E+10 | 0.334664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.355286E+09 | 1237690.49 |
August | 0.163685E+10 | 0.121849E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202648E+09 | 2676586.84 |
September | 0.145243E+10 | 0.110213E+10 | 0.327926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118105E+09 | 4598113.20 |
October | 0.150991E+10 | 0.116303E+10 | 0.339809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65516618.78 | 13720548.06 |
November | 0.149516E+10 | 0.117563E+10 | 0.332024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17400867.44 | 47243361.42 |
December | 0.145680E+10 | 0.116806E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3029373.38 | 0.177291E+09 |
Annual Sum or Average | 0.181194E+11 | 0.137900E+11 | 0.403423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173266E+10 | 0.842040E+09 |
Minimum of Months | 0.136985E+10 | 0.106222E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 352890.87 | 1237690.49 |
Maximum of Months | 0.163685E+10 | 0.122769E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.425611E+09 | 0.221903E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.764799E+09 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47033.31 | 0.139881E+09 |
February | 0.882782E+09 | 0.683233E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2489018.56 | 0.163635E+09 |
March | 0.105485E+10 | 0.790061E+09 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29466452.15 | 0.115963E+09 |
April | 0.936002E+09 | 0.699481E+09 | 0.211446E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126171E+09 | 12213615.60 |
May | 0.101394E+10 | 0.746628E+09 | 0.222976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.279740E+09 | 2962637.08 |
June | 0.101113E+10 | 0.742399E+09 | 0.218692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191368E+09 | 2204359.90 |
July | 0.938820E+09 | 0.702572E+09 | 0.215670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236839E+09 | 834132.99 |
August | 0.105485E+10 | 0.784732E+09 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134363E+09 | 1836922.35 |
September | 0.936002E+09 | 0.709641E+09 | 0.211328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77964091.80 | 3046843.24 |
October | 0.973041E+09 | 0.745800E+09 | 0.218986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40238524.50 | 10241344.06 |
November | 0.963541E+09 | 0.755818E+09 | 0.213969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8937024.37 | 35585548.90 |
December | 0.938820E+09 | 0.748091E+09 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 928052.16 | 0.129814E+09 |
Annual Sum or Average | 0.116768E+11 | 0.887325E+10 | 0.259981E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112855E+10 | 0.618219E+09 |
Minimum of Months | 0.882782E+09 | 0.683233E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47033.31 | 834132.99 |
Maximum of Months | 0.105485E+10 | 0.790061E+09 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.279740E+09 | 0.163635E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.117097E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246102E+09 |
February | 0.136988E+10 | 0.104998E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2076426.25 | 0.280279E+09 |
March | 0.163688E+10 | 0.122342E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41550320.50 | 0.187673E+09 |
April | 0.145246E+10 | 0.108567E+10 | 0.328113E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189893E+09 | 18035218.08 |
May | 0.157341E+10 | 0.116036E+10 | 0.346006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.423484E+09 | 4274836.71 |
June | 0.156904E+10 | 0.115365E+10 | 0.339359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288202E+09 | 3151178.91 |
July | 0.145684E+10 | 0.109360E+10 | 0.334669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.355187E+09 | 1241659.69 |
August | 0.163688E+10 | 0.122039E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200356E+09 | 2796595.73 |
September | 0.145246E+10 | 0.110068E+10 | 0.327931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114175E+09 | 5087786.03 |
October | 0.150994E+10 | 0.115247E+10 | 0.339814E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56957241.41 | 16803839.49 |
November | 0.149520E+10 | 0.115512E+10 | 0.332029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9928568.14 | 64086049.78 |
December | 0.145684E+10 | 0.113975E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24857.92 | 0.234898E+09 |
Annual Sum or Average | 0.181198E+11 | 0.137061E+11 | 0.403429E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168183E+10 | 0.106443E+10 |
Minimum of Months | 0.136988E+10 | 0.104998E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1241659.69 |
Maximum of Months | 0.163688E+10 | 0.122342E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.423484E+09 | 0.280279E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.761640E+09 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1950.73 | 0.148301E+09 |
February | 0.882782E+09 | 0.680124E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2092498.26 | 0.169680E+09 |
March | 0.105485E+10 | 0.792177E+09 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30019679.38 | 0.125416E+09 |
April | 0.936002E+09 | 0.700034E+09 | 0.211444E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126162E+09 | 13843424.73 |
May | 0.101394E+10 | 0.747331E+09 | 0.222974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.278594E+09 | 3559189.85 |
June | 0.101113E+10 | 0.742331E+09 | 0.218691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189321E+09 | 2630509.08 |
July | 0.938820E+09 | 0.704606E+09 | 0.215669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233676E+09 | 1076535.44 |
August | 0.105485E+10 | 0.787999E+09 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131958E+09 | 2262143.05 |
September | 0.936002E+09 | 0.711546E+09 | 0.211327E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76842513.09 | 3900138.61 |
October | 0.973041E+09 | 0.750648E+09 | 0.218984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41060801.47 | 10366299.94 |
November | 0.963541E+09 | 0.747830E+09 | 0.213967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8800913.87 | 36000785.83 |
December | 0.938820E+09 | 0.739913E+09 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 488928.74 | 0.136529E+09 |
Annual Sum or Average | 0.116768E+11 | 0.886618E+10 | 0.259979E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111902E+10 | 0.653565E+09 |
Minimum of Months | 0.882782E+09 | 0.680124E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1950.73 | 1076535.44 |
Maximum of Months | 0.105485E+10 | 0.792177E+09 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.278594E+09 | 0.169680E+09 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.387117E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.351144E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.417256E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.372695E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.402187E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.400242E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.374640E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.417256E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.372695E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.387117E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.382580E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.374640E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.463957E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.351144E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.417256E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.387117E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.351144E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.417256E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.372695E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.402187E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.400242E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.374640E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.417256E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.372695E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.387117E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.382580E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.374640E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.463957E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.351144E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.417256E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.387117E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.351144E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.417256E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.372695E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.402187E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.400242E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.374640E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.417256E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.372695E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.387117E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.382580E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.374640E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.463957E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.351144E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.417256E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.377547E+10 | 0.418155E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.342526E+10 | 0.379298E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409289E+10 | 0.450711E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363176E+10 | 0.402577E+10 | 0.982982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.393418E+10 | 0.434433E+10 | 0.254544E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.392325E+10 | 0.432333E+10 | 0.492345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.364269E+10 | 0.404678E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.409289E+10 | 0.450711E+10 | 0.101578E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.363176E+10 | 0.402577E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.377547E+10 | 0.418155E+10 | 0.508746E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373861E+10 | 0.413254E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364269E+10 | 0.404678E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453069E+11 | 0.501156E+11 | 0.749486E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.342526E+10 | 0.379298E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.409289E+10 | 0.450711E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201667E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 979256.55 | 0.213759E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29532153.53 | 0.130767E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131917E+09 | 10073041.13 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.295989E+09 | 2768015.02 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200185E+09 | 1465080.19 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251755E+09 | 691646.62 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138041E+09 | 1099160.83 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80334148.40 | 1933099.43 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40694974.18 | 11178440.71 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6779283.58 | 46359161.63 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186135E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117621E+10 | 0.807896E+09 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 691646.62 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.295989E+09 | 0.213759E+09 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.342726E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2589018.24 | 0.365281E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54664202.73 | 0.230371E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241981E+09 | 19473278.86 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.535562E+09 | 4837159.51 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.360953E+09 | 2747210.98 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.457157E+09 | 1298781.76 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.252634E+09 | 2127542.90 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143723E+09 | 3396975.03 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73444009.63 | 20155926.12 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13351511.20 | 79058423.84 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147916.91 | 0.311961E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213621E+10 | 0.138344E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1298781.76 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.535562E+09 | 0.365281E+09 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.328292E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 553077.92 | 0.370562E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44501090.97 | 0.243500E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237085E+09 | 19344084.34 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.566315E+09 | 5523435.51 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.385388E+09 | 3468897.93 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.476027E+09 | 1352881.78 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261675E+09 | 3588642.47 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145602E+09 | 4392406.02 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69805158.59 | 19783849.20 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9677902.89 | 77401775.42 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 428371.18 | 0.297752E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219706E+10 | 0.137496E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1352881.78 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.566315E+09 | 0.370562E+09 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 15519.45 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 15519.45 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 15519.45 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 15519.45 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 15519.45 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 15519.45 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 15519.45 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 15519.45 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 15519.45 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 15519.45 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 15519.45 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 15519.45 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 17832.21 | 15519.45 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 15519.45 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 13937.56 | 02-JAN-08:09 | 18128.59 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 13937.56 | 01-FEB-08:09 | 18128.59 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 13937.56 | 01-MAR-08:09 | 18128.59 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 13937.56 | 03-APR-07:10 | 18128.59 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 13937.56 | 01-MAY-07:10 | 18128.59 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 13937.56 | 01-JUN-07:10 | 18128.59 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 13937.56 | 03-JUL-07:10 | 18128.59 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 13937.56 | 01-AUG-07:10 | 18128.59 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 13937.56 | 01-SEP-07:10 | 18128.59 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 13937.56 | 02-OCT-07:10 | 18128.59 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 13937.56 | 01-NOV-07:10 | 18128.59 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 13937.56 | 01-DEC-08:09 | 18128.59 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 13937.56 | 18128.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 13937.56 | 18128.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 13937.56 | 02-JAN-08:09 | 18128.52 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 13937.56 | 01-FEB-08:09 | 18128.52 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 13937.56 | 01-MAR-08:09 | 18128.52 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 13937.56 | 03-APR-07:10 | 18128.52 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 13937.56 | 01-MAY-07:10 | 18128.52 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 13937.56 | 01-JUN-07:10 | 18128.52 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 13937.56 | 03-JUL-07:10 | 18128.52 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 13937.56 | 01-AUG-07:10 | 18128.52 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 13937.56 | 01-SEP-07:10 | 18128.52 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 13937.56 | 02-OCT-07:10 | 18128.52 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 13937.56 | 01-NOV-07:10 | 18128.52 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 13937.56 | 01-DEC-08:09 | 18128.52 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 13937.56 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 13937.56 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 13937.56 | 02-JAN-08:09 | 18128.52 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 13937.56 | 01-FEB-08:09 | 18128.52 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 13937.56 | 01-MAR-08:09 | 18128.52 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 13937.56 | 03-APR-07:10 | 18128.52 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 13937.56 | 01-MAY-07:10 | 18128.52 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 13937.56 | 01-JUN-07:10 | 18128.52 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 13937.56 | 03-JUL-07:10 | 18128.52 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 13937.56 | 01-AUG-07:10 | 18128.52 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 13937.56 | 01-SEP-07:10 | 18128.52 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 13937.56 | 02-OCT-07:10 | 18128.52 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 13937.56 | 01-NOV-07:10 | 18128.52 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 13937.56 | 01-DEC-08:09 | 18128.52 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 13937.56 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 13937.56 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1518.11 | 18-JAN-08:09 | 2276.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 237.11 | 15-JAN-17:00 |
February | 2010.79 | 01-FEB-10:09 | 1493.71 | 10-FEB-08:09 | 2276.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 38.43 | 19-FEB-15:00 | 317.06 | 09-FEB-22:10 |
March | 2010.79 | 01-MAR-10:09 | 1506.04 | 14-MAR-07:10 | 2276.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 183.94 | 26-MAR-14:10 | 681.74 | 24-MAR-24:00 |
April | 2010.79 | 03-APR-09:09 | 1075.02 | 03-APR-07:10 | 2276.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 343.34 | 15-APR-17:02 | 102.10 | 22-APR-18:07 |
May | 2010.79 | 01-MAY-09:09 | 1249.63 | 24-MAY-07:10 | 2276.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 612.56 | 28-MAY-14:55 | 49.14 | 15-MAY-02:47 |
June | 2010.79 | 01-JUN-09:09 | 1240.40 | 23-JUN-07:10 | 2276.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 282.12 | 03-JUN-17:02 | 50.10 | 18-JUN-04:30 |
July | 2010.79 | 03-JUL-09:09 | 1459.75 | 26-JUL-07:10 | 2276.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 298.30 | 02-JUL-11:45 | 38.93 | 19-JUL-02:20 |
August | 2010.79 | 01-AUG-09:09 | 1495.67 | 16-AUG-07:10 | 2276.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 194.48 | 06-AUG-14:25 | 45.48 | 15-AUG-23:50 |
September | 2010.79 | 01-SEP-09:09 | 1531.62 | 08-SEP-07:10 | 2276.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 170.10 | 24-SEP-14:45 | 27.27 | 08-SEP-22:10 |
October | 2010.79 | 02-OCT-09:09 | 1595.59 | 11-OCT-07:10 | 2276.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 194.16 | 15-OCT-12:40 | 96.62 | 12-OCT-02:30 |
November | 2010.79 | 01-NOV-09:09 | 1570.33 | 27-NOV-16:00 | 2276.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 62.34 | 12-NOV-14:10 | 158.89 | 28-NOV-05:20 |
December | 2010.79 | 01-DEC-10:09 | 1578.40 | 29-DEC-16:00 | 2276.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8.55 | 24-DEC-14:23 | 367.40 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.27 | |||||
Maximum of Months | 2010.79 | 1595.59 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 612.56 | 681.74 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 973.30 | 17-JAN-16:00 | 1466.95 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 154.78 | 15-JAN-17:00 |
February | 1295.83 | 01-FEB-10:09 | 967.62 | 09-FEB-16:00 | 1466.95 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 19.37 | 19-FEB-15:00 | 202.69 | 09-FEB-22:10 |
March | 1295.83 | 01-MAR-10:09 | 909.26 | 14-MAR-07:10 | 1466.95 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 116.34 | 26-MAR-14:50 | 449.46 | 24-MAR-24:00 |
April | 1295.83 | 03-APR-09:09 | 692.79 | 03-APR-07:10 | 1466.95 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 229.62 | 15-APR-17:02 | 62.79 | 22-APR-18:07 |
May | 1295.83 | 01-MAY-09:09 | 692.79 | 01-MAY-07:10 | 1466.95 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 409.44 | 28-MAY-14:53 | 33.89 | 15-MAY-02:47 |
June | 1295.83 | 01-JUN-09:09 | 692.79 | 01-JUN-07:10 | 1466.95 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 193.13 | 17-JUN-20:50 | 29.48 | 18-JUN-04:30 |
July | 1295.83 | 03-JUL-09:09 | 917.91 | 26-JUL-07:10 | 1466.95 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 199.64 | 02-JUL-11:45 | 21.21 | 19-JUL-02:20 |
August | 1295.83 | 01-AUG-09:09 | 943.58 | 16-AUG-07:10 | 1466.95 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 131.22 | 06-AUG-14:00 | 24.23 | 15-AUG-23:50 |
September | 1295.83 | 01-SEP-09:09 | 968.41 | 07-SEP-07:10 | 1466.95 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 114.21 | 24-SEP-14:45 | 16.11 | 08-SEP-22:20 |
October | 1295.83 | 02-OCT-09:09 | 1016.67 | 11-OCT-07:10 | 1466.95 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 122.27 | 15-OCT-13:10 | 60.85 | 12-OCT-02:30 |
November | 1295.83 | 01-NOV-09:09 | 1029.58 | 27-NOV-16:00 | 1466.95 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.56 | 12-NOV-14:10 | 102.53 | 28-NOV-05:20 |
December | 1295.83 | 01-DEC-10:09 | 1023.86 | 29-DEC-16:00 | 1466.95 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4.19 | 24-DEC-14:23 | 231.12 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.11 | |||||
Maximum of Months | 1295.83 | 1029.58 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 409.44 | 449.46 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1473.40 | 18-JAN-08:09 | 2276.35 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 243.74 | 22-JAN-14:43 |
February | 2010.83 | 01-FEB-10:09 | 1456.78 | 10-FEB-08:09 | 2276.35 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 12.62 | 21-FEB-15:00 | 313.14 | 09-FEB-22:10 |
March | 2010.83 | 01-MAR-10:09 | 1492.56 | 14-MAR-07:10 | 2276.35 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 148.99 | 26-MAR-15:24 | 739.52 | 24-MAR-24:00 |
April | 2010.83 | 03-APR-09:09 | 1075.05 | 03-APR-07:10 | 2276.35 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 338.69 | 15-APR-17:08 | 107.75 | 22-APR-18:07 |
May | 2010.83 | 01-MAY-09:09 | 1287.72 | 24-MAY-07:10 | 2276.35 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 610.63 | 28-MAY-14:53 | 53.36 | 15-MAY-02:47 |
June | 2010.83 | 01-JUN-09:09 | 1296.72 | 23-JUN-07:10 | 2276.35 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 284.13 | 03-JUN-17:02 | 50.88 | 18-JUN-04:30 |
July | 2010.83 | 03-JUL-09:09 | 1476.24 | 26-JUL-07:10 | 2276.35 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 297.66 | 02-JUL-11:45 | 38.66 | 19-JUL-02:20 |
August | 2010.83 | 01-AUG-09:09 | 1502.97 | 16-AUG-07:10 | 2276.35 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 193.59 | 06-AUG-13:44 | 46.93 | 15-AUG-23:50 |
September | 2010.83 | 01-SEP-09:09 | 1529.49 | 08-SEP-07:10 | 2276.35 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 162.24 | 24-SEP-14:45 | 26.51 | 08-SEP-22:10 |
October | 2010.83 | 02-OCT-09:09 | 1589.31 | 11-OCT-07:10 | 2276.35 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 164.10 | 15-OCT-12:50 | 96.66 | 12-OCT-02:30 |
November | 2010.83 | 01-NOV-09:09 | 1476.84 | 27-NOV-16:00 | 2276.35 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.57 | 12-NOV-14:45 | 169.51 | 29-NOV-24:00 |
December | 2010.83 | 01-DEC-10:09 | 1537.17 | 29-DEC-16:00 | 2276.35 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2.91 | 28-DEC-14:00 | 405.70 | 31-DEC-14:50 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1075.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.51 | |||||
Maximum of Months | 2010.83 | 1589.31 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 610.63 | 739.52 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 985.07 | 18-JAN-08:09 | 1466.94 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 170.69 | 15-JAN-17:00 |
February | 1295.83 | 01-FEB-10:09 | 972.30 | 10-FEB-08:09 | 1466.94 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8.43 | 21-FEB-15:00 | 233.37 | 09-FEB-22:20 |
March | 1295.83 | 01-MAR-10:09 | 995.66 | 14-MAR-07:10 | 1466.94 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 100.10 | 26-MAR-13:28 | 611.67 | 24-MAR-24:00 |
April | 1295.83 | 03-APR-09:09 | 858.71 | 03-APR-07:10 | 1466.94 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 220.39 | 15-APR-17:10 | 115.32 | 22-APR-18:07 |
May | 1295.83 | 01-MAY-09:09 | 866.74 | 24-MAY-07:10 | 1466.94 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 402.95 | 28-MAY-14:14 | 48.50 | 15-MAY-02:47 |
June | 1295.83 | 01-JUN-09:09 | 868.08 | 23-JUN-07:10 | 1466.94 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 190.14 | 17-JUN-20:30 | 49.00 | 18-JUN-04:30 |
July | 1295.83 | 03-JUL-09:09 | 961.95 | 26-JUL-07:10 | 1466.94 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 201.66 | 02-JUL-11:45 | 39.33 | 19-JUL-02:20 |
August | 1295.83 | 01-AUG-09:09 | 979.52 | 16-AUG-07:10 | 1466.94 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 126.06 | 06-AUG-13:44 | 51.80 | 15-AUG-23:50 |
September | 1295.83 | 01-SEP-09:09 | 997.33 | 08-SEP-07:10 | 1466.94 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 110.47 | 24-SEP-14:05 | 26.38 | 08-SEP-22:20 |
October | 1295.83 | 02-OCT-09:09 | 1032.79 | 11-OCT-07:10 | 1466.94 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 120.22 | 15-OCT-12:40 | 79.49 | 12-OCT-02:30 |
November | 1295.83 | 01-NOV-09:09 | 959.54 | 03-NOV-07:10 | 1466.94 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.40 | 12-NOV-14:05 | 127.51 | 29-NOV-24:00 |
December | 1295.83 | 01-DEC-10:09 | 977.42 | 29-DEC-16:00 | 1466.94 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1.95 | 28-DEC-14:00 | 292.60 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 858.71 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.38 | |||||
Maximum of Months | 1295.83 | 1032.79 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 402.95 | 611.67 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1524.72 | 18-JAN-08:09 | 2276.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 17.78 | 08-JAN-14:50 | 478.18 | 15-JAN-17:00 |
February | 2010.79 | 01-FEB-10:09 | 1501.05 | 10-FEB-08:09 | 2276.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 162.37 | 19-FEB-14:53 | 676.13 | 09-FEB-22:10 |
March | 2010.79 | 01-MAR-10:09 | 1513.20 | 14-MAR-07:10 | 2276.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 484.65 | 26-MAR-14:32 | 1334.55 | 24-MAR-24:00 |
April | 2010.79 | 03-APR-09:09 | 1075.02 | 03-APR-07:10 | 2276.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 821.08 | 15-APR-17:02 | 217.07 | 22-APR-18:03 |
May | 2010.79 | 01-MAY-09:09 | 1264.06 | 24-MAY-07:10 | 2276.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1401.00 | 28-MAY-14:43 | 126.85 | 15-MAY-03:00 |
June | 2010.79 | 01-JUN-09:09 | 1255.10 | 23-JUN-07:10 | 2276.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 660.26 | 03-JUN-17:02 | 120.31 | 18-JUN-04:55 |
July | 2010.79 | 03-JUL-09:09 | 1468.23 | 26-JUL-07:10 | 2276.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 688.81 | 02-JUL-11:56 | 105.36 | 19-JUL-02:53 |
August | 2010.79 | 01-AUG-09:09 | 1503.11 | 16-AUG-07:10 | 2276.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 456.61 | 06-AUG-14:00 | 123.16 | 15-AUG-24:00 |
September | 2010.79 | 01-SEP-09:09 | 1538.01 | 08-SEP-07:10 | 2276.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 391.39 | 24-SEP-14:45 | 54.10 | 08-SEP-22:10 |
October | 2010.79 | 02-OCT-09:09 | 1600.11 | 11-OCT-07:10 | 2276.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 454.56 | 15-OCT-12:00 | 211.02 | 12-OCT-02:55 |
November | 2010.79 | 01-NOV-09:09 | 1575.52 | 27-NOV-16:00 | 2276.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 177.06 | 12-NOV-14:00 | 340.37 | 28-NOV-04:55 |
December | 2010.79 | 01-DEC-10:09 | 1583.38 | 29-DEC-16:00 | 2276.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 111.12 | 24-DEC-14:10 | 731.97 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 17.78 | 54.10 | |||||
Maximum of Months | 2010.79 | 1600.11 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 1401.00 | 1334.55 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 974.56 | 17-JAN-16:00 | 1466.95 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 318.19 | 15-JAN-17:00 |
February | 1239.33 | 01-FEB-08:09 | 968.84 | 09-FEB-16:00 | 1466.95 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 60.08 | 19-FEB-14:55 | 438.69 | 09-FEB-22:10 |
March | 1239.33 | 01-MAR-08:09 | 911.74 | 14-MAR-07:10 | 1466.95 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 268.87 | 26-MAR-15:00 | 948.50 | 24-MAR-24:00 |
April | 1239.33 | 03-APR-07:10 | 692.79 | 03-APR-07:10 | 1466.95 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 530.81 | 15-APR-17:02 | 164.91 | 22-APR-18:03 |
May | 1239.33 | 01-MAY-07:10 | 692.79 | 01-MAY-07:10 | 1466.95 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 936.48 | 28-MAY-14:43 | 94.28 | 15-MAY-03:00 |
June | 1239.33 | 01-JUN-07:10 | 692.79 | 01-JUN-07:10 | 1466.95 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 439.16 | 03-JUN-17:02 | 80.78 | 18-JUN-04:55 |
July | 1239.33 | 03-JUL-07:10 | 921.23 | 26-JUL-07:10 | 1466.95 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 461.65 | 02-JUL-11:56 | 69.72 | 19-JUL-02:53 |
August | 1239.33 | 01-AUG-07:10 | 945.96 | 16-AUG-07:10 | 1466.95 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 303.69 | 06-AUG-14:25 | 84.76 | 15-AUG-24:00 |
September | 1239.33 | 01-SEP-07:10 | 970.43 | 08-SEP-07:10 | 1466.95 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 261.39 | 24-SEP-14:45 | 35.03 | 08-SEP-22:20 |
October | 1239.33 | 02-OCT-07:10 | 1017.83 | 11-OCT-07:10 | 1466.95 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 290.82 | 15-OCT-12:55 | 141.45 | 12-OCT-02:55 |
November | 1239.33 | 01-NOV-07:10 | 1030.46 | 27-NOV-16:00 | 1466.95 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 91.30 | 12-NOV-14:40 | 234.70 | 28-NOV-04:55 |
December | 1239.33 | 01-DEC-08:09 | 1024.69 | 29-DEC-16:00 | 1466.95 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 42.20 | 24-DEC-14:10 | 483.34 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1239.33 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.03 | |||||
Maximum of Months | 1239.33 | 1030.46 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 936.48 | 948.50 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1483.05 | 18-JAN-08:09 | 2276.35 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 584.00 | 22-JAN-14:00 |
February | 2010.83 | 01-FEB-10:09 | 1465.43 | 10-FEB-08:09 | 2276.35 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 28.20 | 21-FEB-15:00 | 686.86 | 09-FEB-22:10 |
March | 2010.83 | 01-MAR-10:09 | 1500.25 | 14-MAR-07:10 | 2276.35 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 346.27 | 26-MAR-14:55 | 1517.57 | 24-MAR-24:00 |
April | 2010.83 | 03-APR-09:09 | 1075.05 | 03-APR-07:10 | 2276.35 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 779.22 | 15-APR-17:10 | 243.00 | 22-APR-18:03 |
May | 2010.83 | 01-MAY-09:09 | 1300.75 | 24-MAY-07:10 | 2276.35 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1404.11 | 28-MAY-14:43 | 135.64 | 15-MAY-03:00 |
June | 2010.83 | 01-JUN-09:09 | 1309.39 | 23-JUN-07:10 | 2276.35 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 666.93 | 03-JUN-17:02 | 119.23 | 18-JUN-04:55 |
July | 2010.83 | 03-JUL-09:09 | 1484.11 | 26-JUL-07:10 | 2276.35 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 687.64 | 02-JUL-11:56 | 105.06 | 19-JUL-02:53 |
August | 2010.83 | 01-AUG-09:09 | 1510.13 | 16-AUG-07:10 | 2276.35 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 449.19 | 06-AUG-14:25 | 126.44 | 15-AUG-24:00 |
September | 2010.83 | 01-SEP-09:09 | 1535.96 | 08-SEP-07:10 | 2276.35 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 377.33 | 24-SEP-14:45 | 54.73 | 08-SEP-22:10 |
October | 2010.83 | 02-OCT-09:09 | 1594.09 | 11-OCT-07:10 | 2276.35 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 379.45 | 15-OCT-13:00 | 217.61 | 12-OCT-02:55 |
November | 2010.83 | 01-NOV-09:09 | 1485.33 | 27-NOV-16:00 | 2276.35 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.74 | 13-NOV-14:00 | 387.58 | 28-NOV-04:55 |
December | 2010.83 | 01-DEC-10:09 | 1543.67 | 29-DEC-16:00 | 2276.35 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5.58 | 28-DEC-14:00 | 943.65 | 31-DEC-14:25 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1075.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.73 | |||||
Maximum of Months | 2010.83 | 1594.09 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 1404.11 | 1517.57 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 986.19 | 18-JAN-08:09 | 1466.94 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 332.45 | 15-JAN-17:00 |
February | 1295.83 | 01-FEB-10:09 | 973.47 | 10-FEB-08:09 | 1466.94 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 32.12 | 19-FEB-14:13 | 456.48 | 09-FEB-22:10 |
March | 1295.83 | 01-MAR-10:09 | 996.62 | 14-MAR-07:10 | 1466.94 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 267.60 | 26-MAR-13:00 | 1035.64 | 24-MAR-24:00 |
April | 1295.83 | 03-APR-09:09 | 861.42 | 03-APR-07:10 | 1466.94 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 522.04 | 15-APR-17:07 | 171.38 | 22-APR-18:00 |
May | 1295.83 | 01-MAY-09:09 | 868.65 | 24-MAY-07:10 | 1466.94 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 933.25 | 28-MAY-14:43 | 117.88 | 15-MAY-03:00 |
June | 1295.83 | 01-JUN-09:09 | 869.98 | 23-JUN-07:10 | 1466.94 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 433.73 | 17-JUN-20:30 | 95.58 | 18-JUN-03:55 |
July | 1295.83 | 03-JUL-09:09 | 963.17 | 26-JUL-07:10 | 1466.94 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 464.21 | 02-JUL-11:56 | 75.34 | 19-JUL-02:53 |
August | 1295.83 | 01-AUG-09:09 | 980.60 | 16-AUG-07:10 | 1466.94 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 299.77 | 06-AUG-13:46 | 92.57 | 15-AUG-24:00 |
September | 1295.83 | 01-SEP-09:09 | 998.29 | 08-SEP-07:10 | 1466.94 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 255.31 | 24-SEP-14:05 | 39.79 | 08-SEP-22:20 |
October | 1295.83 | 02-OCT-09:09 | 1033.49 | 11-OCT-07:10 | 1466.94 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 297.02 | 15-OCT-12:00 | 147.75 | 12-OCT-02:55 |
November | 1295.83 | 01-NOV-09:09 | 961.41 | 03-NOV-07:10 | 1466.94 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 81.91 | 12-NOV-13:00 | 245.13 | 28-NOV-04:55 |
December | 1295.83 | 01-DEC-10:09 | 979.00 | 29-DEC-16:00 | 1466.94 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 24.78 | 24-DEC-13:53 | 505.53 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 861.42 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.79 | |||||
Maximum of Months | 1295.83 | 1033.49 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 933.25 | 1035.64 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1524.51 | 18-JAN-08:09 | 2276.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 57.95 | 08-JAN-14:50 | 503.36 | 15-JAN-17:00 |
February | 2010.79 | 01-FEB-10:09 | 1500.81 | 10-FEB-08:09 | 2276.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 219.93 | 19-FEB-15:10 | 761.15 | 09-FEB-22:10 |
March | 2010.79 | 01-MAR-10:09 | 1513.02 | 14-MAR-07:10 | 2276.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 578.40 | 26-MAR-14:32 | 1544.29 | 24-MAR-24:00 |
April | 2010.79 | 03-APR-09:09 | 1075.02 | 03-APR-07:10 | 2276.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 970.02 | 15-APR-17:02 | 253.26 | 22-APR-18:03 |
May | 2010.79 | 01-MAY-09:09 | 1263.67 | 24-MAY-07:10 | 2276.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1720.61 | 28-MAY-14:58 | 159.96 | 15-MAY-02:30 |
June | 2010.79 | 01-JUN-09:09 | 1254.71 | 23-JUN-07:10 | 2276.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 783.55 | 17-JUN-20:30 | 162.68 | 18-JUN-03:55 |
July | 2010.79 | 03-JUL-09:09 | 1467.96 | 26-JUL-07:10 | 2276.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 853.72 | 02-JUL-11:56 | 129.90 | 19-JUL-02:53 |
August | 2010.79 | 01-AUG-09:09 | 1502.87 | 16-AUG-07:10 | 2276.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 558.98 | 06-AUG-14:25 | 169.16 | 15-AUG-24:00 |
September | 2010.79 | 01-SEP-09:09 | 1537.80 | 08-SEP-07:10 | 2276.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 470.81 | 24-SEP-14:56 | 64.54 | 08-SEP-22:10 |
October | 2010.79 | 02-OCT-09:09 | 1599.95 | 11-OCT-07:10 | 2276.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 565.66 | 15-OCT-12:00 | 248.70 | 12-OCT-02:55 |
November | 2010.79 | 01-NOV-09:09 | 1575.44 | 27-NOV-16:00 | 2276.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 227.32 | 12-NOV-14:00 | 370.67 | 28-NOV-04:55 |
December | 2010.79 | 01-DEC-10:09 | 1583.24 | 29-DEC-16:00 | 2276.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 226.60 | 24-DEC-14:00 | 809.52 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 57.95 | 64.54 | |||||
Maximum of Months | 2010.79 | 1599.95 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 1720.61 | 1544.29 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 974.44 | 17-JAN-16:00 | 1466.95 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 17.31 | 08-JAN-14:50 | 335.39 | 15-JAN-17:00 |
February | 1295.83 | 01-FEB-10:09 | 968.69 | 09-FEB-16:00 | 1466.95 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 91.66 | 19-FEB-15:10 | 497.32 | 09-FEB-22:10 |
March | 1295.83 | 01-MAR-10:09 | 911.68 | 14-MAR-07:10 | 1466.95 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 310.13 | 26-MAR-15:00 | 1113.00 | 24-MAR-24:00 |
April | 1295.83 | 03-APR-09:09 | 692.79 | 03-APR-07:10 | 1466.95 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 646.75 | 15-APR-17:08 | 196.19 | 22-APR-18:03 |
May | 1295.83 | 01-MAY-09:09 | 692.79 | 01-MAY-07:10 | 1466.95 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1147.18 | 28-MAY-14:55 | 117.89 | 15-MAY-02:30 |
June | 1295.83 | 01-JUN-09:09 | 692.79 | 01-JUN-07:10 | 1466.95 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 529.05 | 17-JUN-20:30 | 109.86 | 18-JUN-03:55 |
July | 1295.83 | 03-JUL-09:09 | 921.10 | 26-JUL-07:10 | 1466.95 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 572.13 | 02-JUL-11:56 | 85.96 | 19-JUL-02:53 |
August | 1295.83 | 01-AUG-09:09 | 945.84 | 16-AUG-07:10 | 1466.95 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 376.40 | 06-AUG-14:25 | 116.49 | 15-AUG-24:00 |
September | 1295.83 | 01-SEP-09:09 | 970.32 | 08-SEP-07:10 | 1466.95 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 317.87 | 24-SEP-14:56 | 41.62 | 08-SEP-22:20 |
October | 1295.83 | 02-OCT-09:09 | 1017.75 | 11-OCT-07:10 | 1466.95 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 338.07 | 15-OCT-12:40 | 166.83 | 12-OCT-02:55 |
November | 1295.83 | 01-NOV-09:09 | 1030.41 | 27-NOV-16:00 | 1466.95 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 120.20 | 12-NOV-14:40 | 260.45 | 28-NOV-04:55 |
December | 1295.83 | 01-DEC-10:09 | 1024.60 | 29-DEC-16:00 | 1466.95 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 106.65 | 24-DEC-14:00 | 536.98 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 17.31 | 41.62 | |||||
Maximum of Months | 1295.83 | 1030.41 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 1147.18 | 1113.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1482.85 | 18-JAN-08:09 | 2276.35 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 661.28 | 22-JAN-14:50 |
February | 2010.83 | 01-FEB-10:09 | 1465.20 | 10-FEB-08:09 | 2276.35 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 33.26 | 21-FEB-15:00 | 779.59 | 09-FEB-22:10 |
March | 2010.83 | 01-MAR-10:09 | 1500.08 | 14-MAR-07:10 | 2276.35 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 421.21 | 26-MAR-14:55 | 1796.50 | 24-MAR-24:00 |
April | 2010.83 | 03-APR-09:09 | 1075.05 | 03-APR-07:10 | 2276.35 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 967.21 | 15-APR-17:08 | 286.71 | 22-APR-18:03 |
May | 2010.83 | 01-MAY-09:09 | 1300.36 | 24-MAY-07:10 | 2276.35 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1720.61 | 28-MAY-14:57 | 169.88 | 15-MAY-02:30 |
June | 2010.83 | 01-JUN-09:09 | 1309.00 | 23-JUN-07:10 | 2276.35 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 790.96 | 03-JUN-17:02 | 161.58 | 18-JUN-04:43 |
July | 2010.83 | 03-JUL-09:09 | 1483.84 | 26-JUL-07:10 | 2276.35 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 851.99 | 02-JUL-11:56 | 129.51 | 19-JUL-02:53 |
August | 2010.83 | 01-AUG-09:09 | 1509.89 | 16-AUG-07:10 | 2276.35 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 552.82 | 06-AUG-13:46 | 173.56 | 15-AUG-24:00 |
September | 2010.83 | 01-SEP-09:09 | 1535.75 | 08-SEP-07:10 | 2276.35 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 461.14 | 24-SEP-14:15 | 65.50 | 08-SEP-22:10 |
October | 2010.83 | 02-OCT-09:09 | 1593.94 | 11-OCT-07:10 | 2276.35 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 460.17 | 15-OCT-12:50 | 257.81 | 12-OCT-02:55 |
November | 2010.83 | 01-NOV-09:09 | 1485.29 | 27-NOV-16:00 | 2276.35 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.84 | 12-NOV-13:55 | 440.10 | 28-NOV-04:55 |
December | 2010.83 | 01-DEC-10:09 | 1543.55 | 29-DEC-16:00 | 2276.35 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5.41 | 28-DEC-14:00 | 1073.97 | 31-DEC-14:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1075.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.50 | |||||
Maximum of Months | 2010.83 | 1593.94 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 1720.61 | 1796.50 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 986.06 | 18-JAN-08:09 | 1466.94 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2.27 | 08-JAN-14:10 | 364.15 | 15-JAN-17:00 |
February | 1295.83 | 01-FEB-10:09 | 973.33 | 10-FEB-08:09 | 1466.94 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 59.96 | 19-FEB-14:02 | 518.08 | 09-FEB-22:10 |
March | 1295.83 | 01-MAR-10:09 | 996.51 | 14-MAR-07:10 | 1466.94 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 331.98 | 26-MAR-13:00 | 1224.17 | 24-MAR-24:00 |
April | 1295.83 | 03-APR-09:09 | 861.42 | 03-APR-07:10 | 1466.94 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 642.52 | 15-APR-17:07 | 201.02 | 22-APR-18:00 |
May | 1295.83 | 01-MAY-09:09 | 868.41 | 24-MAY-07:10 | 1466.94 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1147.95 | 28-MAY-14:55 | 139.43 | 15-MAY-02:30 |
June | 1295.83 | 01-JUN-09:09 | 869.75 | 23-JUN-07:10 | 1466.94 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 537.67 | 17-JUN-20:30 | 125.42 | 18-JUN-03:55 |
July | 1295.83 | 03-JUL-09:09 | 963.00 | 26-JUL-07:10 | 1466.94 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 577.20 | 02-JUL-11:56 | 92.91 | 19-JUL-02:53 |
August | 1295.83 | 01-AUG-09:09 | 980.46 | 16-AUG-07:10 | 1466.94 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 373.23 | 06-AUG-13:46 | 125.33 | 15-AUG-24:00 |
September | 1295.83 | 01-SEP-09:09 | 998.16 | 08-SEP-07:10 | 1466.94 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 312.79 | 24-SEP-14:54 | 46.89 | 08-SEP-22:20 |
October | 1295.83 | 02-OCT-09:09 | 1033.39 | 11-OCT-07:10 | 1466.94 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 373.44 | 15-OCT-11:50 | 175.17 | 12-OCT-02:55 |
November | 1295.83 | 01-NOV-09:09 | 961.38 | 03-NOV-07:10 | 1466.94 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 112.53 | 12-NOV-13:00 | 276.18 | 28-NOV-04:55 |
December | 1295.83 | 01-DEC-10:09 | 978.95 | 29-DEC-16:00 | 1466.94 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 74.39 | 24-DEC-14:00 | 568.10 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 861.42 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 2.27 | 46.89 | |||||
Maximum of Months | 1295.83 | 1033.39 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 1147.95 | 1224.17 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 405.10 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 405.10 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 405.10 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 405.10 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 405.10 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 405.10 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 405.10 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 405.10 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 405.10 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 405.10 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 405.10 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 405.10 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 405.10 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 405.10 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 405.10 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 405.10 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 405.10 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 405.10 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 405.10 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 405.10 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 405.10 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 405.10 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 405.10 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 405.10 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 405.10 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 405.10 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 405.10 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 405.10 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 405.10 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 405.10 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 405.10 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 405.10 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 405.10 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 405.10 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 405.10 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 405.10 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 405.10 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 405.10 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 405.10 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 405.10 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 405.10 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 405.10 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5027.92 | 02-JAN-10:09 | 4375.82 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5027.92 | 01-FEB-10:09 | 4375.82 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5027.92 | 01-MAR-10:09 | 4375.82 | 01-MAR-08:09 | 379632.52 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5027.92 | 03-APR-09:09 | 4375.82 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5027.92 | 01-MAY-09:09 | 4375.82 | 01-MAY-07:10 | 189816.26 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5027.92 | 01-JUN-09:09 | 4375.82 | 01-JUN-07:10 | 284724.39 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5027.92 | 03-JUL-09:09 | 4375.82 | 03-JUL-07:10 | 379632.52 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5027.92 | 01-AUG-09:09 | 4375.82 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5027.92 | 01-SEP-09:09 | 4375.82 | 01-SEP-07:10 | 189816.26 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5027.92 | 02-OCT-09:09 | 4375.82 | 02-OCT-07:10 | 284724.39 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5027.92 | 01-NOV-09:09 | 4375.82 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5027.92 | 01-DEC-10:09 | 4375.82 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5027.92 | 4375.82 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 5027.92 | 4375.82 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 490.85 | 15-JAN-17:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.68 | 19-FEB-14:53 | 699.93 | 09-FEB-22:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 350.27 | 26-MAR-15:00 | 1444.24 | 24-MAR-24:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 710.40 | 15-APR-17:02 | 204.39 | 22-APR-18:13 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1226.35 | 28-MAY-14:41 | 85.76 | 13-MAY-03:04 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 573.04 | 03-JUN-17:02 | 92.92 | 18-JUN-04:35 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 596.45 | 02-JUL-12:00 | 75.85 | 19-JUL-03:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 385.55 | 06-AUG-14:10 | 80.97 | 15-AUG-23:57 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 335.42 | 24-SEP-13:52 | 38.09 | 19-SEP-05:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 374.86 | 15-OCT-12:50 | 186.52 | 12-OCT-02:38 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.54 | 12-NOV-13:52 | 354.31 | 28-NOV-04:55 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 774.49 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.09 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1226.35 | 1444.24 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 828.72 | 15-JAN-17:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.79 | 19-FEB-15:00 | 1223.23 | 09-FEB-22:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 689.47 | 26-MAR-14:42 | 2459.77 | 24-MAR-24:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1306.21 | 15-APR-17:02 | 354.95 | 22-APR-18:20 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2218.51 | 28-MAY-15:00 | 151.91 | 13-MAY-03:04 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1041.10 | 03-JUN-17:02 | 164.76 | 18-JUN-04:55 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1113.62 | 02-JUL-11:40 | 141.39 | 19-JUL-03:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 739.68 | 06-AUG-14:10 | 150.04 | 15-AUG-24:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 608.99 | 24-SEP-13:52 | 67.64 | 19-SEP-05:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 674.31 | 15-OCT-12:40 | 324.99 | 12-OCT-03:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182.91 | 12-NOV-14:20 | 609.93 | 28-NOV-05:07 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.67 | 24-DEC-14:30 | 1320.04 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.64 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2218.51 | 2459.77 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 808.05 | 15-JAN-17:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.24 | 19-FEB-14:53 | 1249.57 | 09-FEB-22:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 496.26 | 26-MAR-14:40 | 2424.89 | 24-MAR-24:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1323.38 | 15-APR-17:02 | 308.27 | 22-APR-18:40 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2149.93 | 28-MAY-15:00 | 174.14 | 13-MAY-03:06 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1092.70 | 03-JUN-17:10 | 200.68 | 18-JUN-04:55 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1040.16 | 02-JUL-10:52 | 153.70 | 19-JUL-02:53 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 709.87 | 06-AUG-08:52 | 222.44 | 15-AUG-24:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 538.04 | 24-SEP-14:00 | 67.12 | 19-SEP-05:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 606.70 | 15-OCT-12:02 | 347.36 | 12-OCT-02:55 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.95 | 12-NOV-14:20 | 565.77 | 28-NOV-04:55 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.59 | 24-DEC-14:10 | 1263.55 | 29-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.12 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2149.93 | 2424.89 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 97223.56 | 02-JAN-04:02 | 0.00 | 4311.14 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 100508.93 | 06-FEB-04:03 | 0.00 | 3448.91 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 95460.67 | 06-MAR-04:02 | 0.00 | 4311.14 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 95547.30 | 28-APR-03:02 | 0.00 | 5173.36 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 94628.54 | 29-MAY-17:30 | 0.00 | 7760.04 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 91765.23 | 05-JUN-03:02 | 0.00 | 5173.36 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 85621.88 | 04-JUL-19:50 | 0.00 | 5173.36 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 83004.63 | 22-AUG-03:02 | 0.00 | 3448.91 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 84697.23 | 26-SEP-03:02 | 0.00 | 4311.14 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 94666.66 | 29-OCT-13:32 | 5385.68 | 5173.36 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 99215.18 | 12-NOV-13:52 | 5385.68 | 5173.36 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 96467.72 | 26-DEC-04:03 | 0.00 | 3448.91 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 83004.63 | 0.00 | 3448.91 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 100508.93 | 5385.68 | 7760.04 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 94247.69 | 02-JAN-04:02 | 0.00 | 3871.70 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 93630.41 | 21-FEB-04:02 | 0.00 | 3871.70 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 89662.57 | 21-MAR-03:02 | 0.00 | 3871.70 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 86826.26 | 17-APR-05:05 | 9673.43 | 9292.09 | 48342.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 85761.14 | 01-MAY-05:02 | 9673.43 | 9292.09 | 48342.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 85216.57 | 12-JUN-05:02 | 9673.43 | 9292.09 | 48342.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 85751.65 | 10-JUL-05:05 | 9673.43 | 9292.09 | 48342.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 84674.83 | 07-AUG-05:01 | 11285.67 | 10840.77 | 56400.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 82935.09 | 11-SEP-03:02 | 0.00 | 4646.04 | 48342.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 90591.37 | 31-OCT-03:02 | 0.00 | 3871.70 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 93854.23 | 24-NOV-04:02 | 0.00 | 3871.70 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 93980.08 | 04-DEC-04:02 | 0.00 | 3871.70 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 82935.09 | 0.00 | 3871.70 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 94247.69 | 11285.67 | 10840.77 | 56400.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 80680.75 | 17-JAN-06:02 | 8061.19 | 7743.41 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 84600.87 | 27-FEB-04:02 | 0.00 | 3871.70 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 81591.21 | 23-MAR-04:03 | 0.00 | 6194.72 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 79594.66 | 13-APR-03:02 | 0.00 | 3871.70 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 75644.68 | 25-MAY-03:02 | 0.00 | 3871.70 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 77374.93 | 21-JUN-03:02 | 0.00 | 3871.70 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 77726.46 | 28-JUL-03:02 | 0.00 | 3871.70 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 78401.83 | 17-AUG-03:02 | 0.00 | 3871.70 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 80308.33 | 06-SEP-03:02 | 0.00 | 3871.70 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 82936.58 | 24-OCT-03:02 | 0.00 | 3871.70 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 81772.99 | 17-NOV-05:03 | 0.00 | 6194.72 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 80223.21 | 27-DEC-06:02 | 8061.19 | 7743.41 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 75644.68 | 0.00 | 3871.70 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 84600.87 | 8061.19 | 7743.41 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 34277.53 | 26-JAN-16:20 | 15316.26 | 13937.56 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 79357.48 | 23-FEB-06:03 | 6448.95 | 6194.72 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 83715.24 | 15-MAR-04:03 | 0.00 | 6194.72 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 83283.83 | 17-APR-05:03 | 9673.43 | 9292.09 | 48342.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 82830.27 | 25-MAY-03:02 | 0.00 | 3871.70 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 86993.69 | 12-JUN-05:02 | 9673.43 | 9292.09 | 48342.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 83995.34 | 28-JUL-03:02 | 0.00 | 3871.70 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 84138.26 | 17-AUG-03:02 | 0.00 | 3871.70 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 85558.99 | 11-SEP-03:02 | 0.00 | 4646.04 | 48342.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 84715.45 | 11-OCT-03:02 | 0.00 | 3871.70 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 81204.55 | 09-NOV-06:02 | 8061.19 | 7743.41 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 69665.87 | 29-DEC-06:02 | 8061.19 | 7743.41 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 34277.53 | 0.00 | 3871.70 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 86993.69 | 15316.26 | 13937.56 | 48342.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4968.19 | 26-JAN-14:10 | 2010.79 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 |
February | 6682.53 | 23-FEB-14:30 | 2010.79 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 5.79 | 0.00 |
March | 13821.38 | 14-MAR-05:02 | 1012.16 | 972.26 | 5058.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.61 |
April | 19444.80 | 16-APR-15:41 | 708.51 | 418.08 | 5311.41 | 0.00 | 0.00 | 0.00 | 0.00 | 45.09 | 0.00 |
May | 19446.64 | 07-MAY-16:31 | 809.73 | 477.81 | 6070.18 | 0.00 | 0.00 | 0.00 | 0.00 | 217.26 | 0.00 |
June | 19512.69 | 11-JUN-17:02 | 0.00 | 358.36 | 4552.64 | 0.00 | 0.00 | 0.00 | 0.00 | 99.01 | 0.00 |
July | 20867.56 | 02-JUL-17:01 | 0.00 | 537.53 | 6828.95 | 0.00 | 0.00 | 0.00 | 0.00 | 163.31 | 0.00 |
August | 18961.79 | 06-AUG-15:42 | 607.30 | 358.36 | 4552.64 | 0.00 | 0.00 | 0.00 | 0.00 | 166.87 | 0.00 |
September | 19212.21 | 24-SEP-14:42 | 607.30 | 358.36 | 4552.64 | 0.00 | 0.00 | 0.00 | 0.00 | 156.15 | 0.00 |
October | 17364.69 | 01-OCT-15:51 | 708.51 | 418.08 | 5311.41 | 0.00 | 0.00 | 0.00 | 0.00 | 58.48 | 0.00 |
November | 8997.97 | 06-NOV-06:02 | 1012.16 | 972.26 | 5058.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5933.59 | 26-DEC-14:10 | 2010.79 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.11 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4968.19 | 0.00 | 358.36 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20867.56 | 2010.79 | 1075.02 | 6828.95 | 0.00 | 0.00 | 0.00 | 0.00 | 217.26 | 9.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4453.37 | 26-JAN-10:20 | 1295.83 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.32 |
February | 7146.13 | 21-FEB-09:40 | 1239.33 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.43 |
March | 13235.84 | 12-MAR-09:53 | 260.91 | 153.96 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.14 |
April | 16685.30 | 16-APR-09:02 | 391.37 | 230.94 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 0.00 |
May | 16990.34 | 07-MAY-09:11 | 456.59 | 269.43 | 3422.87 | 0.00 | 0.00 | 0.00 | 0.00 | 97.54 | 0.00 |
June | 15610.86 | 11-JUN-09:42 | 326.14 | 192.45 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 51.43 | 0.00 |
July | 16213.54 | 02-JUL-15:41 | 587.05 | 346.41 | 4400.84 | 0.00 | 0.00 | 0.00 | 0.00 | 114.14 | 0.00 |
August | 12964.53 | 07-AUG-05:01 | 913.19 | 877.19 | 4563.83 | 0.00 | 0.00 | 0.00 | 0.00 | 5.82 | 0.00 |
September | 15173.92 | 24-SEP-14:42 | 391.37 | 230.94 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 102.72 | 0.00 |
October | 15922.26 | 01-OCT-09:52 | 326.14 | 192.45 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 10.92 | 0.00 |
November | 6736.27 | 13-NOV-09:40 | 1239.33 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 |
December | 4963.54 | 01-DEC-09:40 | 1239.33 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.48 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4453.37 | 260.91 | 153.96 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16990.34 | 1295.83 | 877.19 | 4563.83 | 0.00 | 0.00 | 0.00 | 0.00 | 114.14 | 15.32 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 14671.94 | 08-JAN-14:23 | 303.66 | 179.18 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.61 |
February | 20491.31 | 19-FEB-14:13 | 404.87 | 238.91 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.56 |
March | 21190.03 | 12-MAR-13:12 | 506.09 | 298.64 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 15.85 | 0.00 |
April | 20457.00 | 16-APR-15:01 | 708.53 | 418.09 | 5311.49 | 0.00 | 0.00 | 0.00 | 0.00 | 60.51 | 0.00 |
May | 19971.29 | 07-MAY-15:11 | 809.75 | 477.82 | 6070.27 | 0.00 | 0.00 | 0.00 | 0.00 | 243.82 | 0.00 |
June | 19798.19 | 11-JUN-16:22 | 607.31 | 358.36 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 110.31 | 0.00 |
July | 21177.55 | 02-JUL-16:21 | 910.97 | 537.55 | 6829.06 | 0.00 | 0.00 | 0.00 | 0.00 | 170.31 | 0.00 |
August | 20003.67 | 06-AUG-14:22 | 607.31 | 358.36 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 181.51 | 0.00 |
September | 21061.96 | 24-SEP-14:42 | 607.31 | 358.36 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 136.57 | 0.00 |
October | 22454.27 | 01-OCT-13:11 | 708.53 | 418.09 | 5311.49 | 0.00 | 0.00 | 0.00 | 0.00 | 67.11 | 0.00 |
November | 21450.98 | 23-NOV-12:52 | 506.09 | 298.64 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.11 |
December | 20837.28 | 03-DEC-12:43 | 404.87 | 238.91 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.80 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 14671.94 | 303.66 | 179.18 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22454.27 | 910.97 | 537.55 | 6829.06 | 0.00 | 0.00 | 0.00 | 0.00 | 243.82 | 49.56 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8480.49 | 14-JAN-06:02 | 652.28 | 626.56 | 3259.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.66 |
February | 17406.44 | 19-FEB-16:12 | 260.91 | 153.96 | 1955.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.88 |
March | 21070.60 | 26-MAR-14:42 | 326.14 | 192.45 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 72.59 | 0.00 |
April | 22159.83 | 30-APR-16:21 | 456.59 | 269.43 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 153.78 | 0.00 |
May | 21518.67 | 07-MAY-15:51 | 521.82 | 307.92 | 3911.83 | 0.00 | 0.00 | 0.00 | 0.00 | 147.69 | 0.00 |
June | 21554.30 | 04-JUN-15:51 | 521.82 | 307.92 | 3911.83 | 0.00 | 0.00 | 0.00 | 0.00 | 147.81 | 0.00 |
July | 24103.34 | 02-JUL-16:21 | 587.05 | 346.41 | 4400.81 | 0.00 | 0.00 | 0.00 | 0.00 | 96.50 | 0.00 |
August | 21609.99 | 06-AUG-15:42 | 391.37 | 230.94 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 97.55 | 0.00 |
September | 21299.59 | 24-SEP-14:42 | 391.37 | 230.94 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 90.61 | 0.00 |
October | 22307.67 | 01-OCT-15:11 | 456.59 | 269.43 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 38.94 | 0.00 |
November | 20184.25 | 23-NOV-14:12 | 326.14 | 192.45 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.34 |
December | 18231.40 | 24-DEC-15:32 | 260.91 | 153.96 | 1955.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.36 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8480.49 | 260.91 | 153.96 | 1955.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24103.34 | 652.28 | 626.56 | 4400.81 | 0.00 | 0.00 | 0.00 | 0.00 | 153.78 | 42.36 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3666.53 | 26-JAN-14:30 | 2010.79 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.25 |
February | 5606.67 | 24-FEB-15:00 | 2010.79 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 24.00 | 0.00 |
March | 13820.12 | 14-MAR-05:02 | 1012.16 | 972.26 | 5058.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.94 |
April | 14864.95 | 28-APR-05:02 | 1214.60 | 1166.71 | 6070.18 | 0.00 | 0.00 | 0.00 | 0.00 | 1.03 | 0.00 |
May | 19413.51 | 28-MAY-16:41 | 1012.16 | 597.26 | 7587.73 | 0.00 | 0.00 | 0.00 | 0.00 | 1168.83 | 0.00 |
June | 18920.92 | 11-JUN-17:02 | 0.00 | 358.36 | 4552.64 | 0.00 | 0.00 | 0.00 | 0.00 | 230.87 | 0.00 |
July | 18880.01 | 02-JUL-16:32 | 607.30 | 358.36 | 4552.64 | 0.00 | 0.00 | 0.00 | 0.00 | 426.10 | 0.00 |
August | 17268.53 | 02-AUG-03:02 | 0.00 | 486.13 | 5058.48 | 0.00 | 0.00 | 0.00 | 0.00 | 94.43 | 0.00 |
September | 18740.12 | 24-SEP-14:42 | 607.30 | 358.36 | 4552.64 | 0.00 | 0.00 | 0.00 | 0.00 | 359.47 | 0.00 |
October | 14289.53 | 12-OCT-05:02 | 1012.16 | 972.26 | 5058.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.59 |
November | 5931.09 | 09-NOV-14:30 | 2010.79 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 17.61 | 0.00 |
December | 3555.20 | 28-DEC-15:00 | 2010.79 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3555.20 | 0.00 | 358.36 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19413.51 | 2010.79 | 1166.71 | 7587.73 | 0.00 | 0.00 | 0.00 | 0.00 | 1168.83 | 25.25 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3524.92 | 26-JAN-10:00 | 1239.33 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.02 |
February | 6241.44 | 22-FEB-10:00 | 1239.33 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.52 |
March | 11230.52 | 12-MAR-09:23 | 195.68 | 115.47 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.48 |
April | 16467.59 | 16-APR-09:52 | 326.14 | 192.45 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 40.03 | 0.00 |
May | 17994.83 | 28-MAY-09:21 | 456.59 | 269.43 | 3422.87 | 0.00 | 0.00 | 0.00 | 0.00 | 195.72 | 0.00 |
June | 16318.97 | 04-JUN-10:43 | 260.91 | 153.96 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 204.54 | 0.00 |
July | 16232.01 | 04-JUL-10:02 | 326.14 | 192.45 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 177.26 | 0.00 |
August | 13615.72 | 07-AUG-05:03 | 913.19 | 877.19 | 4563.83 | 0.00 | 0.00 | 0.00 | 0.00 | 19.22 | 0.00 |
September | 15903.65 | 24-SEP-14:42 | 391.37 | 230.94 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 233.26 | 0.00 |
October | 16716.65 | 01-OCT-09:52 | 326.14 | 192.45 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 22.55 | 0.00 |
November | 6198.50 | 09-NOV-10:00 | 1239.33 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.53 | 0.00 |
December | 4156.04 | 01-DEC-10:00 | 1239.33 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3524.92 | 195.68 | 115.47 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17994.83 | 1239.33 | 877.19 | 4563.83 | 0.00 | 0.00 | 0.00 | 0.00 | 233.26 | 34.02 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 17581.65 | 08-JAN-14:23 | 303.66 | 179.18 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.79 |
February | 20020.60 | 20-FEB-12:23 | 404.87 | 238.91 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.28 |
March | 19973.64 | 26-MAR-13:32 | 404.87 | 238.91 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 222.65 | 0.00 |
April | 20027.83 | 16-APR-12:32 | 404.87 | 238.91 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 172.34 | 0.00 |
May | 19632.98 | 28-MAY-16:01 | 1012.19 | 597.27 | 7587.84 | 0.00 | 0.00 | 0.00 | 0.00 | 1258.14 | 0.00 |
June | 18963.11 | 11-JUN-16:22 | 607.31 | 358.36 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 257.95 | 0.00 |
July | 18985.98 | 02-JUL-16:32 | 607.31 | 358.36 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 427.54 | 0.00 |
August | 19151.91 | 27-AUG-14:43 | 404.87 | 238.91 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 186.66 | 0.00 |
September | 20511.29 | 24-SEP-14:42 | 607.31 | 358.36 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 308.45 | 0.00 |
October | 22021.59 | 01-OCT-13:11 | 708.53 | 418.09 | 5311.49 | 0.00 | 0.00 | 0.00 | 0.00 | 148.96 | 0.00 |
November | 21614.61 | 12-NOV-13:12 | 607.31 | 358.36 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.78 |
December | 20107.48 | 03-DEC-13:02 | 404.87 | 238.91 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 17581.65 | 303.66 | 179.18 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22021.59 | 1012.19 | 597.27 | 7587.84 | 0.00 | 0.00 | 0.00 | 0.00 | 1258.14 | 95.79 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5187.61 | 31-JAN-16:00 | 1239.33 | 692.79 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.89 |
February | 10246.83 | 20-FEB-15:43 | 260.91 | 153.96 | 1955.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.49 |
March | 16661.43 | 12-MAR-17:23 | 0.00 | 153.96 | 1955.92 | 0.00 | 0.00 | 0.00 | 0.00 | 83.98 | 0.00 |
April | 18114.90 | 30-APR-16:02 | 391.37 | 230.94 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 381.80 | 0.00 |
May | 18986.17 | 28-MAY-16:01 | 652.28 | 384.90 | 4889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 765.46 | 0.00 |
June | 18241.39 | 11-JUN-16:22 | 391.37 | 230.94 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 159.83 | 0.00 |
July | 18095.36 | 02-JUL-16:32 | 391.37 | 230.94 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 263.38 | 0.00 |
August | 17610.66 | 06-AUG-16:22 | 391.37 | 230.94 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 220.00 | 0.00 |
September | 18098.27 | 24-SEP-14:42 | 391.37 | 230.94 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 207.98 | 0.00 |
October | 18856.78 | 01-OCT-15:51 | 456.59 | 269.43 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 72.02 | 0.00 |
November | 14342.84 | 12-NOV-15:12 | 326.14 | 192.45 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 29.71 | 0.00 |
December | 5662.30 | 01-DEC-15:30 | 1239.33 | 692.79 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.43 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5187.61 | 0.00 | 153.96 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18986.17 | 1239.33 | 692.79 | 4889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 765.46 | 19.89 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3129.44 | 26-JAN-15:00 | 2010.79 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.24 |
February | 5757.36 | 23-FEB-14:50 | 2010.79 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 14.07 | 0.00 |
March | 13558.29 | 14-MAR-05:02 | 1012.16 | 972.26 | 5058.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.25 |
April | 22425.99 | 16-APR-15:41 | 708.51 | 418.08 | 5311.41 | 0.00 | 0.00 | 0.00 | 0.00 | 127.63 | 0.00 |
May | 23072.30 | 28-MAY-16:11 | 708.51 | 418.08 | 5311.41 | 0.00 | 0.00 | 0.00 | 0.00 | 1514.13 | 0.00 |
June | 22971.45 | 04-JUN-16:31 | 809.73 | 477.81 | 6070.18 | 0.00 | 0.00 | 0.00 | 0.00 | 616.04 | 0.00 |
July | 22741.27 | 02-JUL-16:32 | 607.30 | 358.36 | 4552.64 | 0.00 | 0.00 | 0.00 | 0.00 | 513.12 | 0.00 |
August | 21402.19 | 06-AUG-15:42 | 607.30 | 358.36 | 4552.64 | 0.00 | 0.00 | 0.00 | 0.00 | 473.74 | 0.00 |
September | 22620.07 | 17-SEP-14:52 | 607.30 | 358.36 | 4552.64 | 0.00 | 0.00 | 0.00 | 0.00 | 372.64 | 0.00 |
October | 15286.49 | 04-OCT-05:02 | 1012.16 | 972.26 | 5058.48 | 0.00 | 0.00 | 0.00 | 0.00 | 1.74 | 0.00 |
November | 6421.82 | 09-NOV-14:40 | 2010.79 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 20.84 | 0.00 |
December | 2982.71 | 28-DEC-15:50 | 1923.11 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.13 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2982.71 | 607.30 | 358.36 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23072.30 | 2010.79 | 1075.02 | 6070.18 | 0.00 | 0.00 | 0.00 | 0.00 | 1514.13 | 37.24 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3024.32 | 26-JAN-14:30 | 1295.83 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.01 |
February | 5702.31 | 23-FEB-10:40 | 1295.83 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.55 |
March | 16454.10 | 12-MAR-16:22 | 391.37 | 230.94 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 117.07 | 0.00 |
April | 18984.57 | 16-APR-09:02 | 391.37 | 230.94 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 14.75 | 0.00 |
May | 19384.98 | 07-MAY-09:51 | 456.59 | 269.43 | 3422.87 | 0.00 | 0.00 | 0.00 | 0.00 | 278.65 | 0.00 |
June | 17604.11 | 11-JUN-10:22 | 326.14 | 192.45 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 176.63 | 0.00 |
July | 17464.38 | 04-JUL-10:02 | 326.14 | 192.45 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 215.05 | 0.00 |
August | 16901.28 | 06-AUG-15:02 | 391.37 | 230.94 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 337.97 | 0.00 |
September | 17470.79 | 17-SEP-14:52 | 391.37 | 230.94 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 240.70 | 0.00 |
October | 11882.51 | 01-OCT-10:02 | 260.91 | 153.96 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 41.89 | 0.00 |
November | 5906.63 | 09-NOV-10:20 | 1295.83 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 1.87 | 0.00 |
December | 3089.37 | 01-DEC-14:50 | 1295.83 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.70 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3024.32 | 260.91 | 153.96 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19384.98 | 1295.83 | 692.79 | 3422.87 | 0.00 | 0.00 | 0.00 | 0.00 | 337.97 | 22.01 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 11874.19 | 12-JAN-14:20 | 2010.83 | 1075.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.02 |
February | 22961.50 | 20-FEB-15:43 | 404.87 | 238.91 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.90 |
March | 24195.88 | 12-MAR-13:42 | 506.09 | 298.64 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 37.28 | 0.00 |
April | 23332.65 | 16-APR-15:01 | 708.53 | 418.09 | 5311.49 | 0.00 | 0.00 | 0.00 | 0.00 | 170.13 | 0.00 |
May | 23269.98 | 07-MAY-15:11 | 809.75 | 477.82 | 6070.27 | 0.00 | 0.00 | 0.00 | 0.00 | 680.00 | 0.00 |
June | 22933.34 | 04-JUN-15:51 | 809.75 | 477.82 | 6070.27 | 0.00 | 0.00 | 0.00 | 0.00 | 668.87 | 0.00 |
July | 22730.01 | 02-JUL-16:32 | 607.31 | 358.36 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 514.47 | 0.00 |
August | 22519.96 | 06-AUG-14:22 | 607.31 | 358.36 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 513.54 | 0.00 |
September | 24219.07 | 17-SEP-14:52 | 607.31 | 358.36 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 320.16 | 0.00 |
October | 25030.65 | 22-OCT-13:52 | 607.31 | 358.36 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 59.32 | 0.00 |
November | 25001.93 | 05-NOV-13:42 | 607.31 | 358.36 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 9.48 | 0.00 |
December | 21256.23 | 03-DEC-13:32 | 404.87 | 238.91 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.93 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 11874.19 | 404.87 | 238.91 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25030.65 | 2010.83 | 1075.05 | 6070.27 | 0.00 | 0.00 | 0.00 | 0.00 | 680.00 | 31.90 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4674.48 | 12-JAN-15:50 | 1239.33 | 692.79 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.42 |
February | 8499.11 | 20-FEB-15:43 | 260.91 | 153.96 | 1955.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.38 |
March | 20539.15 | 12-MAR-16:22 | 391.37 | 230.94 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 84.97 | 0.00 |
April | 20700.95 | 30-APR-16:02 | 391.37 | 230.94 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 459.23 | 0.00 |
May | 21507.39 | 28-MAY-16:11 | 456.59 | 269.43 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 925.03 | 0.00 |
June | 21212.49 | 04-JUN-16:31 | 521.82 | 307.92 | 3911.83 | 0.00 | 0.00 | 0.00 | 0.00 | 380.76 | 0.00 |
July | 20820.03 | 02-JUL-16:32 | 391.37 | 230.94 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 318.12 | 0.00 |
August | 20041.98 | 06-AUG-16:22 | 391.37 | 230.94 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 264.42 | 0.00 |
September | 20695.12 | 17-SEP-14:52 | 391.37 | 230.94 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 215.84 | 0.00 |
October | 20076.81 | 22-OCT-15:52 | 326.14 | 192.45 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 46.93 | 0.00 |
November | 15036.99 | 05-NOV-15:42 | 326.14 | 192.45 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 4.59 | 0.00 |
December | 5295.54 | 28-DEC-15:40 | 1239.33 | 692.79 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.32 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4674.48 | 260.91 | 153.96 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21507.39 | 1239.33 | 692.79 | 3911.83 | 0.00 | 0.00 | 0.00 | 0.00 | 925.03 | 15.38 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6991.68 | 17-JAN-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 10225.49 | 21-FEB-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.15 |
March | 10811.52 | 06-MAR-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.69 |
April | 16257.10 | 17-APR-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
May | 17755.84 | 30-MAY-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.22 | 0.00 |
June | 17355.93 | 12-JUN-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.00 | 0.00 |
July | 18071.93 | 05-JUL-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.49 | 0.00 |
August | 17631.53 | 07-AUG-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.24 | 0.00 |
September | 13175.73 | 05-SEP-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.75 | 0.00 |
October | 11566.60 | 10-OCT-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11739.03 | 06-NOV-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 9077.87 | 26-DEC-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 6991.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18071.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.00 | 15.69 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3840.52 | 20-JAN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.87 |
February | 4968.25 | 21-FEB-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.35 |
March | 7305.32 | 13-MAR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.30 | 0.00 |
April | 8362.01 | 17-APR-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 322.79 | 0.00 |
May | 11081.53 | 31-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.39 | 0.00 |
June | 10939.00 | 10-JUN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.67 | 0.00 |
July | 10485.90 | 07-JUL-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.30 | 0.00 |
August | 11036.50 | 08-AUG-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.21 | 0.00 |
September | 11569.19 | 05-SEP-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.28 | 0.00 |
October | 9077.00 | 16-OCT-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.41 |
November | 6956.99 | 06-NOV-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 4197.97 | 20-DEC-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 3840.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11569.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 322.79 | 105.03 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6448.44 | 12-JAN-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.79 |
February | 13210.73 | 22-FEB-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.04 | 0.00 |
March | 20925.33 | 28-MAR-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 25800.19 | 26-APR-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.41 | 0.00 |
May | 29385.58 | 01-MAY-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 335.29 | 0.00 |
June | 30910.08 | 12-JUN-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 367.34 | 0.00 |
July | 27485.09 | 07-JUL-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 254.03 | 0.00 |
August | 24488.57 | 07-AUG-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 242.59 | 0.00 |
September | 21333.92 | 26-SEP-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.48 | 0.00 |
October | 20275.13 | 02-OCT-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.38 | 0.00 |
November | 14160.35 | 09-NOV-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.02 | 0.00 |
December | 7952.38 | 01-DEC-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.74 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 6448.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 30910.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 367.34 | 47.79 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1887.21 | 30-JAN-17:00 | 222.14 | 405.10 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3915.09 | 20-FEB-17:15 | 46.77 | 90.03 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7201.51 | 31-MAR-23:53 | 0.00 | 67.52 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7748.08 | 17-APR-01:55 | 0.00 | 45.01 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3494.18 | 31-MAY-24:00 | 0.00 | 22.51 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5404.43 | 30-JUN-24:00 | 0.00 | 45.01 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7250.20 | 31-JUL-24:00 | 0.00 | 67.52 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7547.82 | 16-AUG-00:50 | 0.00 | 45.01 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3486.88 | 30-SEP-24:00 | 0.00 | 45.01 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5386.65 | 31-OCT-24:00 | 0.00 | 22.51 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5798.22 | 12-NOV-16:23 | 35.07 | 67.52 | 17537.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7603.79 | 28-DEC-17:00 | 222.14 | 405.10 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1887.21 | 0.00 | 22.51 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7748.08 | 222.14 | 405.10 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1735.60 | 12-JAN-17:00 | 222.14 | 405.10 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3622.26 | 21-FEB-17:00 | 222.14 | 405.10 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6949.20 | 31-MAR-23:53 | 0.00 | 67.52 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7244.24 | 12-APR-16:00 | 222.14 | 405.10 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3365.50 | 31-MAY-24:00 | 0.00 | 22.51 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5201.09 | 30-JUN-24:00 | 0.00 | 45.01 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6927.47 | 31-JUL-23:43 | 0.00 | 67.52 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7130.42 | 16-AUG-09:40 | 232.27 | 405.10 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3369.15 | 30-SEP-24:00 | 0.00 | 45.01 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5084.85 | 31-OCT-24:00 | 0.00 | 22.51 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5445.65 | 08-NOV-16:40 | 222.14 | 405.10 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7195.50 | 01-DEC-17:00 | 222.14 | 405.10 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1735.60 | 0.00 | 22.51 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7244.24 | 232.27 | 405.10 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1731.45 | 12-JAN-17:00 | 222.14 | 405.10 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3656.86 | 22-FEB-17:00 | 222.14 | 405.10 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6899.61 | 31-MAR-23:53 | 0.00 | 67.52 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7463.63 | 16-APR-21:32 | 0.00 | 112.53 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3341.38 | 31-MAY-24:00 | 0.00 | 22.51 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5250.79 | 30-JUN-24:00 | 0.00 | 45.01 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7047.25 | 31-JUL-23:57 | 0.00 | 67.52 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7296.00 | 20-AUG-17:33 | 0.00 | 90.03 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3356.05 | 30-SEP-23:17 | 0.00 | 67.52 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4941.58 | 31-OCT-24:00 | 0.00 | 22.51 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5493.45 | 08-NOV-16:30 | 222.14 | 405.10 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7190.26 | 28-DEC-17:00 | 222.14 | 405.10 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1731.45 | 0.00 | 22.51 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7463.63 | 222.14 | 405.10 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 92473.16 | 12-JAN-17:00 | 4808.68 | 4375.82 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 183895.03 | 21-FEB-17:00 | 4808.68 | 4375.82 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 358642.06 | 31-MAR-23:57 | 0.00 | 729.33 | 1138897.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 368779.80 | 30-APR-04:53 | 0.00 | 729.33 | 1138897.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 176019.30 | 31-MAY-24:00 | 0.00 | 243.11 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 268193.27 | 30-JUN-24:00 | 0.00 | 486.22 | 569448.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 356261.78 | 31-JUL-23:20 | 0.00 | 486.22 | 759265.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 369681.22 | 15-AUG-23:53 | 0.00 | 729.33 | 1138897.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 177491.45 | 30-SEP-24:00 | 0.00 | 486.22 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 269346.88 | 31-OCT-24:00 | 0.00 | 243.11 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 277030.05 | 13-NOV-17:00 | 4808.68 | 4375.82 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 368383.94 | 04-DEC-17:00 | 4808.68 | 4375.82 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 92473.16 | 0.00 | 243.11 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 369681.22 | 4808.68 | 4375.82 | 1138897.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.174873E+13 | 1115941.33 | 12-JAN-16:30 | 0.675158E+11 | 244167.48 | 02-JAN-06:19 |
February | 0.203008E+13 | 1323472.18 | 24-FEB-16:40 | 0.496620E+11 | 86230.74 | 02-FEB-06:00 |
March | 0.284100E+13 | 1703269.47 | 29-MAR-15:50 | 0.533201E+11 | 70054.48 | 02-MAR-12:50 |
April | 0.333074E+13 | 1942589.44 | 18-APR-15:09 | 0.459380E+11 | 65297.38 | 07-APR-11:50 |
May | 0.238200E+13 | 1509528.89 | 09-MAY-15:00 | 0.447716E+11 | 60254.53 | 01-MAY-11:30 |
June | 0.284464E+13 | 1753558.74 | 22-JUN-15:09 | 0.410891E+11 | 53093.97 | 01-JUN-11:00 |
July | 0.336823E+13 | 1916426.92 | 05-JUL-15:00 | 0.392773E+11 | 47766.69 | 03-JUL-11:39 |
August | 0.381333E+13 | 2042710.94 | 07-AUG-15:09 | 0.423262E+11 | 52019.59 | 31-AUG-11:50 |
September | 0.225795E+13 | 1532602.57 | 14-SEP-15:20 | 0.419045E+11 | 58164.39 | 27-SEP-11:30 |
October | 0.250838E+13 | 1557910.99 | 03-OCT-15:09 | 0.467968E+11 | 64548.95 | 27-OCT-11:20 |
November | 0.265396E+13 | 1576264.58 | 06-NOV-14:39 | 0.492601E+11 | 69710.62 | 27-NOV-12:00 |
December | 0.301861E+13 | 1614177.22 | 28-DEC-16:19 | 0.559683E+11 | 148250.85 | 23-DEC-06:40 |
Annual Sum or Average | 0.327977E+14 | 0.577830E+12 | ||||
Minimum of Months | 0.174873E+13 | 1115941.33 | 0.392773E+11 | 47766.69 | ||
Maximum of Months | 0.381333E+13 | 2042710.94 | 0.675158E+11 | 244167.48 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.230186E+12 | 0.445929E+11 | 0.811612E+12 | 0.162549E+12 | 0.174550E+12 | 0.694902E+11 | 0.00 | 0.177321E+12 | 0.664469E+11 | 0.119804E+11 | 0.00 | 0.00 | 0.00 |
February | 0.208137E+12 | 0.381264E+11 | 0.102011E+13 | 0.146826E+12 | 0.169544E+12 | 0.699399E+11 | 0.00 | 0.262453E+12 | 0.101830E+12 | 0.131189E+11 | 0.00 | 0.00 | 0.00 |
March | 0.246166E+12 | 0.387256E+11 | 0.146267E+13 | 0.162740E+12 | 0.218542E+12 | 0.963901E+11 | 0.00 | 0.468352E+12 | 0.140572E+12 | 0.684805E+10 | 0.00 | 0.00 | 0.00 |
April | 0.219479E+12 | 0.340652E+11 | 0.170311E+13 | 0.157288E+12 | 0.239060E+12 | 0.118137E+12 | 0.00 | 0.700569E+12 | 0.158074E+12 | 0.962645E+09 | 0.00 | 0.00 | 0.00 |
May | 0.236340E+12 | 0.322038E+11 | 0.820521E+12 | 0.162644E+12 | 0.260963E+12 | 0.130779E+12 | 0.00 | 0.537055E+12 | 0.201476E+12 | 15072026.57 | 0.00 | 0.00 | 0.00 |
June | 0.235149E+12 | 0.295519E+11 | 0.110677E+13 | 0.157466E+12 | 0.256441E+12 | 0.132255E+12 | 0.00 | 0.713786E+12 | 0.213221E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.220648E+12 | 0.314140E+11 | 0.143888E+13 | 0.162466E+12 | 0.249420E+12 | 0.142614E+12 | 0.00 | 0.890456E+12 | 0.232336E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.245906E+12 | 0.338286E+11 | 0.177780E+13 | 0.162740E+12 | 0.256965E+12 | 0.143520E+12 | 0.00 | 0.963564E+12 | 0.229008E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.220133E+12 | 0.360059E+11 | 0.784732E+12 | 0.157287E+12 | 0.227862E+12 | 0.119141E+12 | 0.00 | 0.506897E+12 | 0.205892E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.229225E+12 | 0.407566E+11 | 0.112899E+13 | 0.162550E+12 | 0.219540E+12 | 0.105862E+12 | 0.00 | 0.457904E+12 | 0.162218E+12 | 0.133582E+10 | 0.00 | 0.00 | 0.00 |
November | 0.227341E+12 | 0.423923E+11 | 0.140306E+13 | 0.157361E+12 | 0.193489E+12 | 0.841051E+11 | 0.00 | 0.403866E+12 | 0.128602E+12 | 0.137471E+11 | 0.00 | 0.00 | 0.00 |
December | 0.223114E+12 | 0.456536E+11 | 0.175516E+13 | 0.162465E+12 | 0.181015E+12 | 0.772607E+11 | 0.00 | 0.416941E+12 | 0.122362E+12 | 0.346349E+11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.274182E+13 | 0.447317E+12 | 0.152134E+14 | 0.191438E+13 | 0.264739E+13 | 0.128949E+13 | 0.00 | 0.649917E+13 | 0.196204E+13 | 0.826428E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.208137E+12 | 0.295519E+11 | 0.784732E+12 | 0.146826E+12 | 0.169544E+12 | 0.694902E+11 | 0.00 | 0.177321E+12 | 0.664469E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.246166E+12 | 0.456536E+11 | 0.177780E+13 | 0.162740E+12 | 0.260963E+12 | 0.143520E+12 | 0.00 | 0.963564E+12 | 0.232336E+12 | 0.346349E+11 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.133055E+11 | 0.00 | 0.542103E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.120457E+10 | 0.00 | 0.484574E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.533201E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.459380E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.447716E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.410891E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.392773E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.423262E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 7305.64 | 0.00 | 0.419045E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.467968E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 43671473.35 | 0.00 | 0.492164E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.371727E+10 | 0.00 | 0.522511E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.182710E+11 | 0.00 | 0.559559E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.392773E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.133055E+11 | 0.00 | 0.542103E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 251205.37 | 18-JAN-08:09 | 37611.08 | 01-JAN-06:10 | 439129.89 | 02-JAN-08:09 | 117199.11 | 18-JAN-08:20 | 119443.29 | 12-JAN-15:09 | 65670.73 | 12-JAN-14:09 | 0.00 | 01-JAN-00:10 |
February | 250359.64 | 10-FEB-08:09 | 37611.08 | 01-FEB-06:10 | 557421.28 | 01-FEB-08:09 | 117198.62 | 10-FEB-08:20 | 152599.68 | 21-FEB-16:10 | 66204.05 | 16-FEB-16:40 | 0.00 | 01-FEB-00:10 |
March | 251050.18 | 14-MAR-07:10 | 37611.08 | 01-MAR-06:10 | 675712.68 | 01-MAR-08:09 | 117199.02 | 14-MAR-07:19 | 185321.15 | 13-MAR-15:00 | 66728.74 | 28-MAR-14:20 | 0.00 | 01-MAR-00:10 |
April | 236455.86 | 03-APR-07:10 | 37611.08 | 01-APR-05:10 | 794004.08 | 03-APR-07:10 | 117190.71 | 03-APR-07:19 | 201830.84 | 17-APR-15:09 | 68512.20 | 19-APR-16:10 | 0.00 | 01-APR-00:10 |
May | 241491.81 | 24-MAY-07:10 | 37611.08 | 01-MAY-05:10 | 439129.89 | 01-MAY-07:10 | 117193.58 | 24-MAY-07:19 | 225642.14 | 30-MAY-14:09 | 68157.02 | 03-MAY-15:50 | 0.00 | 01-MAY-00:10 |
June | 241504.02 | 23-JUN-07:10 | 37611.08 | 01-JUN-05:10 | 557421.28 | 01-JUN-07:10 | 117193.58 | 23-JUN-07:19 | 229329.06 | 07-JUN-13:00 | 68426.35 | 22-JUN-15:00 | 0.00 | 01-JUN-00:10 |
July | 250026.35 | 26-JUL-07:10 | 37611.08 | 01-JUL-05:10 | 675712.68 | 03-JUL-07:10 | 117198.43 | 26-JUL-07:19 | 227382.65 | 05-JUL-15:20 | 70744.01 | 18-JUL-05:10 | 0.00 | 01-JUL-00:10 |
August | 251266.09 | 16-AUG-07:10 | 37611.08 | 01-AUG-05:10 | 794004.08 | 01-AUG-07:10 | 117199.14 | 16-AUG-07:19 | 212273.56 | 07-AUG-14:50 | 70858.56 | 29-AUG-05:10 | 0.00 | 01-AUG-00:10 |
September | 252502.98 | 08-SEP-07:10 | 37611.08 | 01-SEP-05:10 | 439129.89 | 01-SEP-07:10 | 117199.84 | 08-SEP-07:19 | 201694.50 | 27-SEP-15:00 | 67555.12 | 28-SEP-14:30 | 0.00 | 01-SEP-00:10 |
October | 254941.81 | 11-OCT-07:10 | 37611.08 | 01-OCT-05:10 | 557421.28 | 02-OCT-07:10 | 117201.23 | 11-OCT-07:19 | 183825.22 | 04-OCT-15:00 | 67594.60 | 03-OCT-14:39 | 0.00 | 01-OCT-00:10 |
November | 252112.79 | 27-NOV-16:00 | 37611.08 | 01-NOV-05:10 | 675712.68 | 01-NOV-07:10 | 117194.98 | 03-NOV-07:19 | 159990.45 | 13-NOV-16:10 | 67054.99 | 13-NOV-13:00 | 0.00 | 01-NOV-00:10 |
December | 253561.92 | 29-DEC-16:00 | 37611.08 | 01-DEC-06:10 | 794004.08 | 01-DEC-08:09 | 117193.45 | 29-DEC-08:20 | 131789.64 | 01-DEC-15:39 | 65898.16 | 01-DEC-16:30 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 236455.86 | 37611.08 | 439129.89 | 117190.71 | 119443.29 | 65670.73 | 0.00 | |||||||
Maximum of Months | 254941.81 | 37611.08 | 794004.08 | 117201.23 | 229329.06 | 70858.56 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum} [W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY {Maximum} [W] | HUMIDIFIER:ELECTRICITY {TIMESTAMP} | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 150965.65 | 12-JAN-14:09 | 50450.41 | 13-JAN-14:00 | 7518.01 | 21-JAN-17:40 | 0.00 | 0.00 | 0.00 |
February | 200879.52 | 24-FEB-16:40 | 53127.49 | 24-FEB-15:30 | 11142.13 | 04-FEB-05:00 | 0.00 | 0.00 | 0.00 |
March | 392847.42 | 28-MAR-13:30 | 91812.10 | 06-MAR-14:30 | 13984.28 | 01-MAR-05:00 | 0.00 | 0.00 | 0.00 |
April | 483888.37 | 18-APR-15:39 | 91812.10 | 03-APR-09:09 | 7692.98 | 11-APR-04:00 | 0.00 | 0.00 | 0.00 |
May | 417622.23 | 17-MAY-15:30 | 91812.10 | 01-MAY-07:10 | 2037.96 | 28-MAY-14:00 | 0.00 | 0.00 | 0.00 |
June | 528597.55 | 22-JUN-15:39 | 91812.10 | 01-JUN-06:40 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 539407.01 | 10-JUL-13:00 | 91812.10 | 01-JUL-03:39 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 571270.01 | 28-AUG-14:50 | 91812.10 | 01-AUG-01:10 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 427468.59 | 14-SEP-15:30 | 91812.10 | 01-SEP-00:20 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 386627.81 | 04-OCT-12:09 | 91812.10 | 02-OCT-08:09 | 7240.60 | 31-OCT-04:00 | 0.00 | 0.00 | 0.00 |
November | 359511.14 | 06-NOV-13:09 | 91812.10 | 06-NOV-11:20 | 15174.12 | 30-NOV-22:00 | 0.00 | 0.00 | 0.00 |
December | 262312.87 | 01-DEC-14:30 | 50764.07 | 28-DEC-14:00 | 28639.67 | 22-DEC-05:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 150965.65 | 50450.41 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 571270.01 | 91812.10 | 28639.67 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 1115941.33 | 12-JAN-16:30 | 237063.17 | 439129.89 | 0.00 | 83146.61 | 113284.16 | 43655.31 | 0.00 | 149433.25 | 50228.95 |
February | 1323472.18 | 24-FEB-16:40 | 234435.00 | 557421.28 | 0.00 | 83146.17 | 130051.76 | 65018.72 | 0.00 | 200879.52 | 52519.72 |
March | 1703269.47 | 29-MAR-15:50 | 234435.00 | 675712.68 | 0.00 | 83146.17 | 175452.16 | 66089.92 | 0.00 | 376621.42 | 91812.10 |
April | 1942589.44 | 18-APR-15:09 | 234435.00 | 794004.08 | 0.00 | 83146.17 | 191844.31 | 66756.00 | 0.00 | 480591.77 | 91812.10 |
May | 1509528.89 | 09-MAY-15:00 | 234435.00 | 439129.89 | 0.00 | 83146.17 | 202737.54 | 66978.63 | 0.00 | 391289.55 | 91812.10 |
June | 1753558.74 | 22-JUN-15:09 | 234435.00 | 557421.28 | 0.00 | 83146.17 | 196490.91 | 68081.54 | 0.00 | 522171.72 | 91812.10 |
July | 1916426.92 | 05-JUL-15:00 | 234435.00 | 675712.68 | 0.00 | 83146.17 | 224961.07 | 67718.55 | 0.00 | 538641.34 | 91812.10 |
August | 2042710.94 | 07-AUG-15:09 | 234435.00 | 794004.08 | 0.00 | 83146.17 | 212155.95 | 67734.36 | 0.00 | 559423.27 | 91812.10 |
September | 1532602.57 | 14-SEP-15:20 | 234435.00 | 439129.89 | 0.00 | 83146.17 | 189715.44 | 67426.71 | 0.00 | 426937.25 | 91812.10 |
October | 1557910.99 | 03-OCT-15:09 | 234435.00 | 557421.28 | 0.00 | 83146.17 | 139324.01 | 67511.73 | 0.00 | 384260.68 | 91812.10 |
November | 1576264.58 | 06-NOV-14:39 | 234435.00 | 675712.68 | 0.00 | 37754.99 | 122702.75 | 66089.97 | 0.00 | 347757.08 | 91812.10 |
December | 1614177.22 | 28-DEC-16:19 | 236798.20 | 794004.08 | 0.00 | 83146.17 | 123015.79 | 65298.54 | 0.00 | 261238.60 | 50675.84 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1115941.33 | 234435.00 | 439129.89 | 0.00 | 37754.99 | 113284.16 | 43655.31 | 0.00 | 149433.25 | 50228.95 | |
Maximum of Months | 2042710.94 | 237063.17 | 794004.08 | 0.00 | 83146.61 | 224961.07 | 68081.54 | 0.00 | 559423.27 | 91812.10 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 217619.02 | 02-JAN-06:19 | 0.00 | 72823.30 | 10-JAN-12:50 | 0.00 |
February | 0.00 | 0.00 | 60286.66 | 02-FEB-06:00 | 0.00 | 72220.76 | 10-FEB-12:39 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 70054.48 | 02-MAR-12:50 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 65297.38 | 07-APR-11:50 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 60254.53 | 01-MAY-11:30 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 53093.97 | 01-JUN-11:00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 47766.69 | 03-JUL-11:39 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 52019.59 | 31-AUG-11:50 | 0.00 |
September | 0.00 | 0.00 | 12.18 | 25-SEP-10:20 | 0.00 | 58164.39 | 27-SEP-11:30 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 64548.95 | 27-OCT-11:20 | 0.00 |
November | 0.00 | 0.00 | 3692.60 | 27-NOV-06:00 | 0.00 | 69710.62 | 27-NOV-12:00 | 0.00 |
December | 0.00 | 0.00 | 122984.77 | 23-DEC-06:49 | 0.00 | 72384.62 | 28-DEC-12:39 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 47766.69 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 217619.02 | 0.00 | 72823.30 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 26.60 | 2.33 | 26.75 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 26.26 | 0.33 | 26.34 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 25.87 | 0.00 | 25.87 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 26.28 | 0.17 | 26.20 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 26.29 | 0.17 | 26.33 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 26.62 | 0.00 | 26.62 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 26.23 | 1.00 | 26.29 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 26.00 | 0.67 | 26.08 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 26.28 | 1.50 | 26.41 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 26.03 | 0.17 | 26.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 | 26.43 | 1.00 | 26.50 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 26.46 | 0.17 | 26.47 |
Annual Sum or Average | 0.00 | 0.00 | 89.17 | 26.30 | 7.50 | 26.36 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 25.87 | 0.00 | 25.87 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 | 26.62 | 2.33 | 26.75 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 25.75 | 0.00 | 25.75 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 25.63 | 0.00 | 25.63 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.67 | 0.00 | 25.67 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.57 | 0.00 | 25.57 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 25.64 | 0.00 | 25.64 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 25.69 | 0.00 | 25.69 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.60 | 0.00 | 25.60 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.63 | 0.00 | 25.63 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 25.59 | 0.00 | 25.59 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 25.77 | 0.00 | 25.77 |
Annual Sum or Average | 0.00 | 0.00 | 7.83 | 25.68 | 0.00 | 25.68 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 25.77 | 0.00 | 25.77 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.56 | 0.00 | 25.56 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.17 | 25.56 | 0.00 | 25.56 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.56 | 0.00 | 25.56 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 19.11 | 0.00 | 19.11 | 0.00 | 19.11 | 0.00 | 19.11 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.64 | 0.00 | 25.64 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.57 | 0.00 | 25.57 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.57 | 0.00 | 25.57 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | 19.11 | 0.00 | 19.11 | 0.50 | 23.97 | 0.00 | 23.97 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 19.11 | 0.00 | 19.11 | 0.17 | 25.64 | 0.00 | 25.64 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 26.83 | 2.83 | 27.04 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 11.83 | 26.94 | 4.83 | 27.12 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 12.83 | 26.69 | 3.00 | 26.86 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 22.00 | 27.12 | 9.33 | 27.24 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 16.50 | 26.82 | 5.83 | 27.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 25.99 | 0.17 | 26.11 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 71.00 | 26.89 | 26.00 | 27.07 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 22.00 | 27.12 | 9.33 | 27.24 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.33 | 0.17 | 27.33 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.46 | 1.67 | 27.46 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 27.57 | 6.50 | 27.67 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 16.83 | 27.42 | 9.83 | 27.61 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 12.33 | 26.95 | 4.67 | 27.17 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 20.00 | 27.29 | 10.50 | 27.43 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 26.99 | 5.67 | 27.20 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.15 | 3.67 | 27.29 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.52 | 4.83 | 27.52 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 77.67 | 27.27 | 47.50 | 27.43 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 20.00 | 27.57 | 10.50 | 27.67 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.35 | 1.17 | 27.35 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.67 | 4.67 | 27.67 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 27.59 | 5.67 | 27.62 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 14.17 | 27.21 | 7.67 | 27.39 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 16.17 | 27.04 | 7.33 | 27.21 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 13.67 | 26.72 | 3.17 | 26.88 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 22.67 | 27.12 | 9.50 | 27.25 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 19.33 | 26.91 | 6.50 | 27.10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 26.96 | 3.67 | 27.21 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 15.50 | 27.67 | 11.33 | 27.82 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 27.87 | 10.17 | 27.87 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.58 | 4.33 | 27.58 |
Annual Sum or Average | 0.00 | 0.00 | 136.67 | 27.21 | 75.17 | 27.40 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 26.72 | 1.17 | 26.88 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 22.67 | 27.87 | 11.33 | 27.87 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.73 | 2.50 | 27.73 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 19.67 | 26.87 | 5.33 | 27.10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 67.67 | 27.71 | 18.67 | 27.79 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 35.00 | 27.35 | 10.00 | 27.52 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 42.17 | 27.42 | 10.50 | 27.52 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 59.00 | 27.62 | 18.00 | 27.72 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 74.50 | 27.74 | 19.17 | 27.79 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 17.83 | 26.88 | 4.00 | 27.05 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 23.33 | 27.10 | 8.33 | 27.33 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 26.99 | 6.00 | 27.29 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.07 | 3.67 | 27.28 |
Annual Sum or Average | 0.00 | 0.00 | 358.00 | 27.47 | 106.17 | 27.59 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 74.50 | 27.74 | 19.17 | 27.79 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 26.89 | 1.33 | 27.07 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 12.67 | 26.90 | 5.17 | 27.11 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 26.56 | 2.67 | 26.76 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 16.50 | 26.87 | 6.50 | 27.04 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 26.42 | 2.67 | 26.68 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 26.20 | 0.33 | 26.47 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 49.83 | 26.74 | 18.67 | 26.94 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 16.50 | 26.90 | 6.50 | 27.11 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.51 | 1.83 | 27.51 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 27.59 | 7.83 | 27.70 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 19.67 | 27.39 | 10.67 | 27.63 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 | 26.96 | 5.00 | 27.21 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 19.83 | 27.20 | 10.33 | 27.39 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 26.91 | 6.00 | 27.16 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.28 | 4.33 | 27.41 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 27.56 | 6.17 | 27.56 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 85.33 | 27.26 | 52.17 | 27.45 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 19.83 | 27.59 | 10.67 | 27.70 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.48 | 1.00 | 27.48 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.73 | 4.00 | 27.73 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.67 | 4.83 | 27.69 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 27.24 | 5.50 | 27.42 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 15.83 | 26.94 | 7.17 | 27.16 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 26.57 | 2.83 | 26.77 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 17.00 | 26.90 | 7.33 | 27.09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 26.64 | 4.67 | 26.92 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 26.80 | 3.50 | 27.09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 15.33 | 27.77 | 11.00 | 27.93 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 27.91 | 9.67 | 27.92 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.60 | 3.17 | 27.60 |
Annual Sum or Average | 0.00 | 0.00 | 110.50 | 27.17 | 64.67 | 27.39 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 26.57 | 1.00 | 26.77 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 17.00 | 27.91 | 11.00 | 27.93 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.31 | 0.33 | 27.31 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.62 | 2.17 | 27.68 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 16.50 | 27.22 | 5.67 | 27.45 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 29.00 | 27.32 | 8.50 | 27.52 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 22.83 | 27.13 | 5.33 | 27.32 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 25.50 | 27.27 | 8.50 | 27.43 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 16.67 | 26.91 | 5.00 | 27.12 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 26.76 | 2.17 | 27.04 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 27.64 | 5.00 | 27.76 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.41 | 0.67 | 27.41 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 130.33 | 27.20 | 43.33 | 27.40 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 29.00 | 27.64 | 8.50 | 27.76 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.67 | 18.36 | 0.00 | 18.36 | 0.00 | 18.36 | 0.00 | 18.36 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 27.46 | 3.67 | 27.54 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 22.83 | 27.34 | 9.00 | 27.48 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 20.17 | 27.03 | 5.50 | 27.19 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 25.17 | 27.24 | 9.50 | 27.37 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 12.67 | 26.85 | 5.00 | 27.07 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.10 | 2.33 | 27.27 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.35 | 0.50 | 27.35 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.67 | 18.36 | 0.00 | 18.36 | 91.17 | 27.11 | 35.50 | 27.28 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.67 | 18.36 | 0.00 | 18.36 | 25.17 | 27.46 | 9.50 | 27.54 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 18.51 | 0.00 | 18.51 | 0.00 | 18.51 | 0.00 | 18.51 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.49 | 2.17 | 27.49 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 14.83 | 27.69 | 10.17 | 27.79 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 29.50 | 27.61 | 12.33 | 27.82 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 23.17 | 27.23 | 8.33 | 27.42 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 27.33 | 27.45 | 11.67 | 27.62 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 15.33 | 27.06 | 7.00 | 27.30 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27.41 | 4.33 | 27.56 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 27.58 | 7.67 | 27.59 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.33 | 18.51 | 0.00 | 18.51 | 127.50 | 27.41 | 63.67 | 27.59 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 18.51 | 0.00 | 18.51 | 29.50 | 27.69 | 12.33 | 27.82 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 18.86 | 0.00 | 18.86 | 0.00 | 18.86 | 0.00 | 18.86 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.71 | 2.67 | 27.71 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.82 | 4.33 | 27.84 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 13.50 | 27.43 | 7.17 | 27.61 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 24.50 | 27.36 | 9.17 | 27.52 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 20.17 | 27.02 | 5.67 | 27.19 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 25.67 | 27.24 | 9.83 | 27.39 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 15.67 | 26.96 | 6.00 | 27.18 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 27.11 | 4.33 | 27.36 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 15.33 | 27.96 | 10.83 | 28.09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 27.89 | 8.50 | 27.89 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.51 | 0.67 | 27.51 |
Annual Sum or Average | 0.33 | 18.86 | 0.00 | 18.86 | 142.00 | 27.33 | 69.17 | 27.53 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.86 | 0.00 | 18.86 |
Maximum of Months | 0.33 | 18.86 | 0.00 | 18.86 | 25.67 | 27.96 | 10.83 | 28.09 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 18.89 | 0.00 | 18.89 | 0.00 | 18.89 | 0.00 | 18.89 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.83 | 2.33 | 27.86 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 19.67 | 27.50 | 6.83 | 27.70 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 33.33 | 27.59 | 9.83 | 27.79 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 28.00 | 27.39 | 7.00 | 27.57 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 32.17 | 27.50 | 10.50 | 27.65 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 21.83 | 27.14 | 7.17 | 27.33 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 27.16 | 3.33 | 27.40 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 27.99 | 5.00 | 28.04 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.38 | 0.50 | 27.38 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.33 | 18.89 | 0.00 | 18.89 | 154.67 | 27.44 | 52.50 | 27.62 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 18.89 | 0.00 | 18.89 | 33.33 | 27.99 | 10.50 | 28.04 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 181.00 | 28.27 | 156.83 | 28.28 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 479.17 | 28.28 | 360.17 | 28.30 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 660.17 | 28.28 | 517.00 | 28.29 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 479.17 | 28.28 | 360.17 | 28.30 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 163.67 | 28.19 | 148.83 | 28.19 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 373.83 | 28.16 | 305.00 | 28.18 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 537.50 | 28.17 | 453.83 | 28.18 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 373.83 | 28.19 | 305.00 | 28.19 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 119.17 | 28.24 | 105.67 | 28.23 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 249.67 | 28.14 | 215.67 | 28.14 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 368.83 | 28.17 | 321.33 | 28.17 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 249.67 | 28.24 | 215.67 | 28.23 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 546.17 | 29.51 | 409.33 | 29.61 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 28.29 | 0.00 | 28.29 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 743.17 | 30.27 | 514.00 | 30.35 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 1290.33 | 29.94 | 923.33 | 30.03 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 743.17 | 30.27 | 514.00 | 30.35 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.17 | 26.74 | 294.33 | 24.96 | 1.83 | 24.98 |
February | 12.17 | 26.72 | 352.67 | 24.76 | 12.17 | 24.82 |
March | 35.00 | 25.07 | 431.67 | 24.56 | 35.00 | 24.59 |
April | 32.50 | 24.21 | 411.33 | 24.59 | 32.50 | 24.57 |
May | 287.33 | 24.46 | 489.83 | 24.51 | 287.33 | 24.49 |
June | 345.33 | 24.55 | 496.00 | 24.51 | 345.33 | 24.52 |
July | 298.50 | 25.07 | 497.00 | 24.80 | 298.50 | 24.88 |
August | 253.17 | 25.02 | 514.00 | 24.67 | 253.17 | 24.76 |
September | 279.67 | 25.01 | 485.00 | 24.74 | 279.67 | 24.81 |
October | 107.33 | 25.16 | 502.00 | 24.72 | 107.33 | 24.79 |
November | 0.17 | 27.21 | 465.17 | 24.66 | 0.17 | 24.66 |
December | 0.00 | 0.00 | 370.50 | 24.82 | 0.00 | 24.82 |
Annual Sum or Average | 1653.33 | 24.84 | 5309.50 | 24.67 | 1653.00 | 24.70 |
Minimum of Months | 0.00 | 0.00 | 294.33 | 24.51 | 0.00 | 24.49 |
Maximum of Months | 345.33 | 27.21 | 514.00 | 24.96 | 345.33 | 24.98 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 20.33 | 25.53 | 266.00 | 24.81 | 12.17 | 24.89 |
February | 2.00 | 25.35 | 359.67 | 24.43 | 1.17 | 24.44 |
March | 0.00 | 0.00 | 457.83 | 24.29 | 0.00 | 24.29 |
April | 0.00 | 0.00 | 443.00 | 24.21 | 0.00 | 24.21 |
May | 0.00 | 0.00 | 492.83 | 24.18 | 0.00 | 24.18 |
June | 0.00 | 0.00 | 496.00 | 24.17 | 0.00 | 24.17 |
July | 0.00 | 0.00 | 497.00 | 24.23 | 0.00 | 24.23 |
August | 0.00 | 0.00 | 514.00 | 24.19 | 0.00 | 24.19 |
September | 0.00 | 0.00 | 485.00 | 24.27 | 0.00 | 24.27 |
October | 0.00 | 0.00 | 502.00 | 24.33 | 0.00 | 24.33 |
November | 0.00 | 0.00 | 466.50 | 24.41 | 0.00 | 24.41 |
December | 0.67 | 23.97 | 364.00 | 24.54 | 0.00 | 24.54 |
Annual Sum or Average | 23.00 | 25.47 | 5343.83 | 24.31 | 13.33 | 24.32 |
Minimum of Months | 0.00 | 0.00 | 266.00 | 24.17 | 0.00 | 24.17 |
Maximum of Months | 20.33 | 25.53 | 514.00 | 24.81 | 12.17 | 24.89 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 136.17 | 23.59 | 124.83 | 24.02 | 13.00 | 24.04 |
February | 61.67 | 23.82 | 249.17 | 24.23 | 8.17 | 24.27 |
March | 8.17 | 23.75 | 398.17 | 24.24 | 0.50 | 24.24 |
April | 3.33 | 23.78 | 382.50 | 24.19 | 0.00 | 24.19 |
May | 0.00 | 0.00 | 474.17 | 24.12 | 0.00 | 24.12 |
June | 0.00 | 0.00 | 495.83 | 24.12 | 0.00 | 24.12 |
July | 0.00 | 0.00 | 497.00 | 24.14 | 0.00 | 24.14 |
August | 0.00 | 0.00 | 514.00 | 24.17 | 0.00 | 24.17 |
September | 1.33 | 26.10 | 484.50 | 24.26 | 1.33 | 24.27 |
October | 0.00 | 0.00 | 489.00 | 24.29 | 0.00 | 24.29 |
November | 10.50 | 23.56 | 382.00 | 24.27 | 0.00 | 24.27 |
December | 86.33 | 23.50 | 146.83 | 24.07 | 0.00 | 24.07 |
Annual Sum or Average | 307.50 | 23.63 | 4638.00 | 24.18 | 23.00 | 24.19 |
Minimum of Months | 0.00 | 0.00 | 124.83 | 24.02 | 0.00 | 24.04 |
Maximum of Months | 136.17 | 26.10 | 514.00 | 24.29 | 13.00 | 24.29 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 410.17 | 22.51 | 39.50 | 22.50 | 15.83 | 22.41 |
February | 207.00 | 23.06 | 145.00 | 23.51 | 8.00 | 23.54 |
March | 45.33 | 23.53 | 359.33 | 24.12 | 2.00 | 24.13 |
April | 0.00 | 0.00 | 416.00 | 24.24 | 0.00 | 24.24 |
May | 0.00 | 0.00 | 501.33 | 24.21 | 0.00 | 24.21 |
June | 0.00 | 0.00 | 495.83 | 24.21 | 0.00 | 24.21 |
July | 0.00 | 0.00 | 497.00 | 24.25 | 0.00 | 24.25 |
August | 0.00 | 0.00 | 514.00 | 24.22 | 0.00 | 24.22 |
September | 1.00 | 26.22 | 481.67 | 24.29 | 1.00 | 24.30 |
October | 0.17 | 23.26 | 472.67 | 24.24 | 0.00 | 24.24 |
November | 111.50 | 23.18 | 256.67 | 23.85 | 0.00 | 23.85 |
December | 348.17 | 22.74 | 43.00 | 22.88 | 0.00 | 22.88 |
Annual Sum or Average | 1123.33 | 22.79 | 4222.00 | 23.91 | 26.83 | 23.90 |
Minimum of Months | 0.00 | 0.00 | 39.50 | 22.50 | 0.00 | 22.41 |
Maximum of Months | 410.17 | 26.22 | 514.00 | 24.29 | 15.83 | 24.30 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 290.00 | 23.15 | 67.33 | 23.38 | 0.00 | 23.38 |
February | 120.83 | 23.34 | 198.33 | 23.88 | 0.00 | 23.88 |
March | 15.50 | 23.57 | 407.67 | 24.25 | 0.00 | 24.25 |
April | 11.50 | 26.88 | 454.17 | 24.46 | 11.50 | 24.52 |
May | 25.50 | 26.81 | 508.00 | 24.58 | 25.50 | 24.68 |
June | 27.83 | 26.57 | 496.00 | 24.52 | 27.83 | 24.62 |
July | 49.83 | 26.78 | 497.00 | 24.74 | 49.83 | 24.91 |
August | 30.83 | 26.76 | 514.00 | 24.52 | 30.83 | 24.64 |
September | 26.17 | 26.37 | 485.00 | 24.53 | 26.17 | 24.62 |
October | 2.00 | 26.91 | 498.33 | 24.38 | 2.00 | 24.39 |
November | 22.67 | 23.56 | 366.33 | 24.24 | 0.00 | 24.24 |
December | 175.17 | 23.37 | 111.33 | 23.69 | 0.00 | 23.69 |
Annual Sum or Average | 797.83 | 24.02 | 4603.50 | 24.33 | 173.67 | 24.41 |
Minimum of Months | 2.00 | 23.15 | 67.33 | 23.38 | 0.00 | 23.38 |
Maximum of Months | 290.00 | 26.91 | 514.00 | 24.74 | 49.83 | 24.91 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 220.67 | 23.09 | 98.67 | 23.48 | 0.00 | 23.48 |
February | 97.67 | 23.15 | 245.00 | 24.00 | 0.00 | 24.00 |
March | 23.50 | 24.06 | 425.67 | 24.31 | 4.67 | 24.33 |
April | 30.83 | 26.88 | 457.83 | 24.57 | 30.83 | 24.71 |
May | 47.50 | 26.91 | 508.00 | 24.71 | 47.50 | 24.88 |
June | 29.00 | 26.67 | 496.00 | 24.52 | 29.00 | 24.63 |
July | 47.17 | 26.81 | 497.00 | 24.69 | 47.17 | 24.86 |
August | 27.33 | 26.73 | 514.00 | 24.43 | 27.33 | 24.54 |
September | 28.83 | 26.45 | 485.00 | 24.54 | 28.83 | 24.64 |
October | 25.50 | 26.79 | 492.83 | 24.56 | 25.50 | 24.66 |
November | 41.83 | 23.42 | 375.33 | 24.26 | 0.50 | 24.26 |
December | 196.17 | 23.16 | 149.50 | 23.66 | 0.00 | 23.66 |
Annual Sum or Average | 816.00 | 24.22 | 4744.83 | 24.37 | 241.33 | 24.47 |
Minimum of Months | 23.50 | 23.09 | 98.67 | 23.48 | 0.00 | 23.48 |
Maximum of Months | 220.67 | 26.91 | 514.00 | 24.71 | 47.50 | 24.88 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 138.50 | 23.16 | 221.67 | 23.90 | 0.67 | 23.90 |
February | 72.00 | 23.74 | 319.33 | 24.34 | 10.17 | 24.41 |
March | 26.83 | 26.33 | 455.83 | 24.51 | 22.00 | 24.62 |
April | 28.33 | 26.97 | 468.67 | 24.61 | 28.33 | 24.74 |
May | 32.33 | 26.85 | 508.00 | 24.62 | 32.33 | 24.75 |
June | 28.83 | 26.58 | 496.00 | 24.53 | 28.83 | 24.63 |
July | 49.00 | 26.80 | 497.00 | 24.74 | 49.00 | 24.91 |
August | 32.00 | 26.83 | 514.00 | 24.54 | 32.00 | 24.67 |
September | 35.50 | 26.57 | 485.00 | 24.63 | 35.50 | 24.75 |
October | 48.50 | 27.02 | 502.00 | 24.79 | 48.50 | 24.97 |
November | 44.33 | 26.58 | 443.83 | 24.75 | 38.67 | 24.92 |
December | 85.50 | 23.68 | 307.17 | 24.34 | 7.33 | 24.39 |
Annual Sum or Average | 621.67 | 25.17 | 5218.50 | 24.55 | 333.33 | 24.68 |
Minimum of Months | 26.83 | 23.16 | 221.67 | 23.90 | 0.67 | 23.90 |
Maximum of Months | 138.50 | 27.02 | 514.00 | 24.79 | 49.00 | 24.97 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 119.50 | 23.25 | 212.83 | 24.03 | 0.00 | 24.03 |
February | 24.67 | 24.84 | 377.33 | 24.55 | 10.17 | 24.61 |
March | 30.00 | 26.98 | 507.67 | 24.64 | 30.00 | 24.76 |
April | 87.33 | 26.94 | 485.00 | 24.99 | 87.33 | 25.25 |
May | 66.83 | 26.88 | 508.00 | 24.83 | 66.83 | 25.05 |
June | 75.17 | 26.78 | 496.00 | 24.82 | 75.17 | 25.04 |
July | 105.83 | 26.84 | 497.00 | 25.05 | 105.83 | 25.32 |
August | 95.33 | 26.88 | 514.00 | 24.93 | 95.33 | 25.19 |
September | 56.67 | 26.76 | 485.00 | 24.77 | 56.67 | 24.96 |
October | 54.33 | 26.95 | 502.00 | 24.84 | 54.33 | 25.03 |
November | 29.67 | 26.96 | 479.17 | 24.75 | 29.67 | 24.88 |
December | 13.17 | 26.66 | 415.33 | 24.73 | 12.00 | 24.79 |
Annual Sum or Average | 758.50 | 26.23 | 5479.33 | 24.78 | 623.33 | 24.97 |
Minimum of Months | 13.17 | 23.25 | 212.83 | 24.03 | 0.00 | 24.03 |
Maximum of Months | 119.50 | 26.98 | 514.00 | 25.05 | 105.83 | 25.32 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 467.50 | 22.41 | 8.17 | 22.44 | 0.33 | 22.44 |
February | 275.83 | 22.84 | 82.83 | 23.13 | 0.00 | 23.13 |
March | 70.67 | 23.35 | 316.33 | 24.05 | 0.00 | 24.05 |
April | 4.83 | 26.64 | 428.67 | 24.46 | 4.67 | 24.48 |
May | 28.83 | 26.77 | 508.00 | 24.61 | 28.83 | 24.72 |
June | 39.83 | 26.38 | 496.00 | 24.57 | 39.83 | 24.70 |
July | 90.17 | 26.37 | 497.00 | 24.85 | 90.17 | 25.05 |
August | 57.67 | 26.36 | 514.00 | 24.62 | 57.67 | 24.78 |
September | 51.50 | 26.27 | 485.00 | 24.64 | 51.50 | 24.78 |
October | 8.17 | 23.32 | 473.17 | 24.32 | 0.00 | 24.32 |
November | 157.83 | 23.14 | 179.17 | 23.65 | 0.00 | 23.65 |
December | 427.00 | 22.57 | 3.50 | 22.58 | 0.00 | 22.58 |
Annual Sum or Average | 1679.83 | 23.28 | 3991.83 | 24.07 | 273.00 | 24.18 |
Minimum of Months | 4.83 | 22.41 | 3.50 | 22.44 | 0.00 | 22.44 |
Maximum of Months | 467.50 | 26.77 | 514.00 | 24.85 | 90.17 | 25.05 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 349.00 | 22.64 | 6.50 | 22.67 | 0.00 | 22.67 |
February | 165.17 | 22.88 | 126.17 | 23.53 | 0.00 | 23.53 |
March | 43.33 | 23.90 | 318.00 | 24.38 | 8.17 | 24.43 |
April | 36.00 | 26.91 | 377.83 | 24.86 | 36.00 | 25.02 |
May | 51.50 | 26.95 | 430.00 | 24.88 | 51.50 | 25.08 |
June | 45.83 | 26.63 | 418.00 | 24.75 | 45.83 | 24.91 |
July | 90.83 | 26.51 | 422.00 | 25.01 | 90.83 | 25.24 |
August | 57.50 | 26.49 | 433.00 | 24.75 | 57.50 | 24.93 |
September | 60.83 | 26.37 | 410.00 | 24.81 | 60.83 | 24.99 |
October | 32.00 | 26.43 | 408.00 | 24.71 | 28.33 | 24.84 |
November | 86.00 | 23.12 | 241.50 | 24.06 | 0.17 | 24.06 |
December | 298.00 | 22.73 | 15.00 | 22.82 | 0.00 | 22.82 |
Annual Sum or Average | 1316.00 | 23.89 | 3606.00 | 24.38 | 379.17 | 24.54 |
Minimum of Months | 32.00 | 22.64 | 6.50 | 22.67 | 0.00 | 22.67 |
Maximum of Months | 349.00 | 26.95 | 433.00 | 25.01 | 90.83 | 25.24 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 202.50 | 23.05 | 193.83 | 23.69 | 1.00 | 23.70 |
February | 99.00 | 23.34 | 277.00 | 24.19 | 10.17 | 24.27 |
March | 41.83 | 25.11 | 422.83 | 24.48 | 19.83 | 24.58 |
April | 23.83 | 26.92 | 450.83 | 24.65 | 23.83 | 24.76 |
May | 35.67 | 26.80 | 508.00 | 24.65 | 35.67 | 24.78 |
June | 38.67 | 26.39 | 496.00 | 24.57 | 38.67 | 24.69 |
July | 89.17 | 26.38 | 497.00 | 24.84 | 89.17 | 25.05 |
August | 57.33 | 26.47 | 514.00 | 24.64 | 57.33 | 24.81 |
September | 57.83 | 26.46 | 485.00 | 24.73 | 57.83 | 24.90 |
October | 48.17 | 27.07 | 500.83 | 24.82 | 48.17 | 25.00 |
November | 58.17 | 25.82 | 415.83 | 24.73 | 38.83 | 24.90 |
December | 140.00 | 23.24 | 235.00 | 24.08 | 6.67 | 24.14 |
Annual Sum or Average | 892.17 | 24.78 | 4996.17 | 24.55 | 427.17 | 24.69 |
Minimum of Months | 23.83 | 23.05 | 193.83 | 23.69 | 1.00 | 23.70 |
Maximum of Months | 202.50 | 27.07 | 514.00 | 24.84 | 89.17 | 25.05 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 383.33 | 22.64 | 36.17 | 22.77 | 0.00 | 22.77 |
February | 180.50 | 22.87 | 170.50 | 23.58 | 0.83 | 23.59 |
March | 38.50 | 24.10 | 403.83 | 24.34 | 8.50 | 24.39 |
April | 29.83 | 26.98 | 473.33 | 24.69 | 29.83 | 24.82 |
May | 53.67 | 26.96 | 508.00 | 24.79 | 53.67 | 24.98 |
June | 62.50 | 26.68 | 496.00 | 24.74 | 62.50 | 24.93 |
July | 97.67 | 26.61 | 497.00 | 24.95 | 97.67 | 25.18 |
August | 63.83 | 26.68 | 514.00 | 24.72 | 63.83 | 24.92 |
September | 64.33 | 26.55 | 485.00 | 24.77 | 64.33 | 24.96 |
October | 21.67 | 26.96 | 489.17 | 24.60 | 21.67 | 24.70 |
November | 78.67 | 23.26 | 327.00 | 24.12 | 1.50 | 24.13 |
December | 324.50 | 22.86 | 75.67 | 23.11 | 0.00 | 23.11 |
Annual Sum or Average | 1399.00 | 23.94 | 4475.67 | 24.36 | 404.33 | 24.51 |
Minimum of Months | 21.67 | 22.64 | 36.17 | 22.77 | 0.00 | 22.77 |
Maximum of Months | 383.33 | 26.98 | 514.00 | 24.95 | 97.67 | 25.18 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 494.17 | 21.38 | 78.33 | 21.17 | 78.33 | 21.01 |
February | 352.83 | 22.25 | 57.67 | 22.41 | 9.33 | 22.36 |
March | 131.67 | 23.04 | 289.83 | 23.83 | 0.00 | 23.83 |
April | 21.17 | 25.90 | 429.67 | 24.52 | 15.17 | 24.59 |
May | 43.50 | 26.82 | 508.00 | 24.69 | 43.50 | 24.84 |
June | 48.50 | 26.53 | 496.00 | 24.64 | 48.50 | 24.79 |
July | 96.83 | 26.45 | 497.00 | 24.89 | 96.83 | 25.11 |
August | 59.17 | 26.41 | 514.00 | 24.64 | 59.17 | 24.80 |
September | 55.67 | 26.26 | 485.00 | 24.65 | 55.67 | 24.80 |
October | 35.17 | 23.40 | 432.67 | 24.24 | 3.50 | 24.26 |
November | 269.67 | 22.66 | 127.17 | 23.09 | 2.17 | 23.07 |
December | 485.00 | 21.72 | 48.67 | 21.55 | 48.67 | 21.41 |
Annual Sum or Average | 2093.33 | 22.69 | 3964.00 | 23.72 | 460.83 | 23.78 |
Minimum of Months | 21.17 | 21.38 | 48.67 | 21.17 | 0.00 | 21.01 |
Maximum of Months | 494.17 | 26.82 | 514.00 | 24.89 | 96.83 | 25.11 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 472.83 | 21.85 | 45.50 | 21.71 | 39.50 | 21.57 |
February | 250.33 | 22.48 | 126.83 | 23.01 | 3.00 | 22.98 |
March | 74.83 | 23.43 | 376.00 | 24.19 | 8.67 | 24.24 |
April | 43.67 | 26.80 | 456.50 | 24.75 | 41.67 | 24.92 |
May | 59.00 | 26.98 | 508.00 | 24.81 | 59.00 | 25.01 |
June | 54.00 | 26.72 | 496.00 | 24.70 | 54.00 | 24.88 |
July | 98.67 | 26.54 | 497.00 | 24.93 | 98.67 | 25.16 |
August | 58.50 | 26.55 | 514.00 | 24.66 | 58.50 | 24.84 |
September | 63.00 | 26.35 | 485.00 | 24.70 | 63.00 | 24.87 |
October | 51.83 | 25.45 | 462.33 | 24.57 | 34.17 | 24.71 |
November | 153.67 | 22.76 | 246.17 | 23.66 | 0.00 | 23.66 |
December | 433.33 | 22.17 | 25.33 | 22.10 | 19.83 | 22.02 |
Annual Sum or Average | 1813.67 | 23.25 | 4238.67 | 24.06 | 480.00 | 24.18 |
Minimum of Months | 43.67 | 21.85 | 25.33 | 21.71 | 0.00 | 21.57 |
Maximum of Months | 472.83 | 26.98 | 514.00 | 24.93 | 98.67 | 25.16 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 297.00 | 22.14 | 143.83 | 22.65 | 19.33 | 22.53 |
February | 162.33 | 22.62 | 220.50 | 23.67 | 6.50 | 23.73 |
March | 74.17 | 24.14 | 395.00 | 24.36 | 19.67 | 24.46 |
April | 31.17 | 26.75 | 451.33 | 24.67 | 29.17 | 24.80 |
May | 44.17 | 26.86 | 508.00 | 24.70 | 44.17 | 24.86 |
June | 47.83 | 26.54 | 496.00 | 24.63 | 47.83 | 24.79 |
July | 95.83 | 26.45 | 497.00 | 24.89 | 95.83 | 25.11 |
August | 60.33 | 26.49 | 514.00 | 24.67 | 60.33 | 24.84 |
September | 63.50 | 26.44 | 485.00 | 24.75 | 63.50 | 24.93 |
October | 51.17 | 26.73 | 484.83 | 24.79 | 46.83 | 24.97 |
November | 96.67 | 24.25 | 368.17 | 24.46 | 31.83 | 24.63 |
December | 236.17 | 22.44 | 180.00 | 23.26 | 7.00 | 23.22 |
Annual Sum or Average | 1260.33 | 23.92 | 4743.67 | 24.36 | 472.00 | 24.50 |
Minimum of Months | 31.17 | 22.14 | 143.83 | 22.65 | 6.50 | 22.53 |
Maximum of Months | 297.00 | 26.86 | 514.00 | 24.89 | 95.83 | 25.11 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 436.33 | 21.79 | 49.17 | 21.73 | 31.83 | 21.60 |
February | 265.33 | 22.37 | 122.33 | 22.98 | 0.00 | 22.98 |
March | 86.00 | 23.48 | 367.00 | 24.18 | 9.67 | 24.24 |
April | 35.83 | 26.97 | 467.00 | 24.72 | 35.67 | 24.87 |
May | 63.67 | 26.95 | 508.00 | 24.83 | 63.67 | 25.04 |
June | 70.33 | 26.67 | 496.00 | 24.77 | 70.33 | 24.98 |
July | 103.83 | 26.61 | 497.00 | 24.97 | 103.83 | 25.21 |
August | 66.33 | 26.66 | 514.00 | 24.73 | 66.33 | 24.93 |
September | 69.67 | 26.50 | 485.00 | 24.77 | 69.67 | 24.96 |
October | 38.33 | 25.30 | 466.33 | 24.52 | 22.33 | 24.62 |
November | 167.17 | 22.84 | 248.67 | 23.69 | 1.33 | 23.70 |
December | 399.17 | 22.10 | 62.33 | 22.23 | 16.33 | 22.16 |
Annual Sum or Average | 1802.00 | 23.31 | 4282.83 | 24.10 | 491.00 | 24.24 |
Minimum of Months | 35.83 | 21.79 | 49.17 | 21.73 | 0.00 | 21.60 |
Maximum of Months | 436.33 | 26.97 | 514.00 | 24.97 | 103.83 | 25.21 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 502.00 | 27.00 | 0.00 | 27.00 |
February | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
March | 43.50 | 27.00 | 514.00 | 27.00 | 43.50 | 27.00 |
April | 358.67 | 27.64 | 485.00 | 27.54 | 358.67 | 27.57 |
May | 20.50 | 27.00 | 508.00 | 27.00 | 20.50 | 27.00 |
June | 122.50 | 27.00 | 496.00 | 27.00 | 122.50 | 27.00 |
July | 260.50 | 27.00 | 497.00 | 27.00 | 260.50 | 27.00 |
August | 498.17 | 28.02 | 514.00 | 28.00 | 498.17 | 28.01 |
September | 17.83 | 27.00 | 485.00 | 27.00 | 17.83 | 27.00 |
October | 21.00 | 27.00 | 502.00 | 27.00 | 21.00 | 27.00 |
November | 36.00 | 27.00 | 489.00 | 27.00 | 36.00 | 27.00 |
December | 31.50 | 27.00 | 497.00 | 27.00 | 31.50 | 27.00 |
Annual Sum or Average | 1410.17 | 27.52 | 5943.00 | 27.20 | 1410.17 | 27.25 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 498.17 | 28.02 | 514.00 | 28.00 | 498.17 | 28.01 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 502.00 | 27.00 | 0.00 | 27.00 |
February | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
March | 0.00 | 0.00 | 514.00 | 27.00 | 0.00 | 27.00 |
April | 170.33 | 28.09 | 485.00 | 27.59 | 170.33 | 27.69 |
May | 0.00 | 0.00 | 508.00 | 27.00 | 0.00 | 27.00 |
June | 1.33 | 27.00 | 496.00 | 27.00 | 1.33 | 27.00 |
July | 5.33 | 27.00 | 497.00 | 27.00 | 5.33 | 27.00 |
August | 316.50 | 28.17 | 514.00 | 27.93 | 316.50 | 28.00 |
September | 0.00 | 0.00 | 485.00 | 27.00 | 0.00 | 27.00 |
October | 0.33 | 27.00 | 502.00 | 27.00 | 0.33 | 27.00 |
November | 0.00 | 0.00 | 489.00 | 27.00 | 0.00 | 27.00 |
December | 0.00 | 0.00 | 497.00 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 493.83 | 28.13 | 5943.00 | 27.18 | 493.83 | 27.25 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 316.50 | 28.17 | 514.00 | 27.93 | 316.50 | 28.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 12.83 | 24.51 | 466.17 | 26.93 | 0.00 | 26.93 |
February | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
March | 2.50 | 27.00 | 514.00 | 27.00 | 2.50 | 27.00 |
April | 156.67 | 27.92 | 485.00 | 27.46 | 156.67 | 27.55 |
May | 53.17 | 27.00 | 508.00 | 27.00 | 53.17 | 27.00 |
June | 87.33 | 27.00 | 496.00 | 27.00 | 87.33 | 27.00 |
July | 76.33 | 27.00 | 497.00 | 27.00 | 76.33 | 27.00 |
August | 252.33 | 28.04 | 514.00 | 27.70 | 252.33 | 27.79 |
September | 10.33 | 27.00 | 485.00 | 27.00 | 10.33 | 27.00 |
October | 7.50 | 27.00 | 502.00 | 27.00 | 7.50 | 27.00 |
November | 0.00 | 0.00 | 489.00 | 27.00 | 0.00 | 27.00 |
December | 0.00 | 0.00 | 497.00 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 659.00 | 27.57 | 5907.17 | 27.12 | 646.17 | 27.17 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 26.93 | 0.00 | 26.93 |
Maximum of Months | 252.33 | 28.04 | 514.00 | 27.70 | 252.33 | 27.79 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 27.01 | 502.00 | 27.01 | 502.00 | 27.01 |
February | 454.00 | 27.01 | 454.00 | 27.01 | 454.00 | 27.01 |
March | 514.00 | 27.00 | 514.00 | 27.00 | 514.00 | 27.00 |
April | 485.00 | 29.34 | 485.00 | 29.34 | 485.00 | 29.34 |
May | 508.00 | 27.00 | 508.00 | 27.00 | 508.00 | 27.00 |
June | 496.00 | 27.00 | 496.00 | 27.00 | 496.00 | 27.00 |
July | 497.00 | 27.00 | 497.00 | 27.00 | 497.00 | 27.00 |
August | 514.00 | 30.47 | 514.00 | 30.47 | 514.00 | 30.47 |
September | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
October | 502.00 | 27.00 | 502.00 | 27.00 | 502.00 | 27.00 |
November | 489.00 | 27.00 | 489.00 | 27.00 | 489.00 | 27.00 |
December | 497.00 | 27.01 | 497.00 | 27.01 | 497.00 | 27.01 |
Annual Sum or Average | 5943.00 | 27.49 | 5943.00 | 27.49 | 5943.00 | 27.49 |
Minimum of Months | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
Maximum of Months | 514.00 | 30.47 | 514.00 | 30.47 | 514.00 | 30.47 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00071 | 29.14523 | 0.85891 | 20.60436 |
February | 454.00000 | 27.00090 | 29.61821 | 0.91217 | 22.60259 |
March | 514.00000 | 27.00055 | 31.21559 | 0.97568 | 25.13376 |
April | 485.00000 | 27.47113 | 32.47454 | 1.12894 | 32.13452 |
May | 508.00000 | 27.00072 | 37.44610 | 0.32767 | 7.27559 |
June | 496.00000 | 27.00241 | 37.19085 | 0.37233 | 7.92388 |
July | 497.00000 | 27.00154 | 36.36942 | 0.40781 | 8.50720 |
August | 514.00000 | 27.98913 | 34.65545 | 0.70489 | 16.26947 |
September | 485.00000 | 27.00012 | 40.25516 | 0.33925 | 7.42640 |
October | 502.00000 | 27.00162 | 33.22764 | 0.97223 | 24.99002 |
November | 489.00000 | 27.00059 | 30.46599 | 0.97067 | 24.93045 |
December | 497.00000 | 27.00016 | 28.23959 | 0.96354 | 24.64247 |
Annual Sum or Average | 5943.00000 | 27.12477 | 33.37831 | 0.74316 | 18.49417 |
Minimum of Months | 454.00000 | 27.00012 | 28.23959 | 0.32767 | 7.27559 |
Maximum of Months | 514.00000 | 27.98913 | 40.25516 | 1.12894 | 32.13452 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00052 | 29.43100 | 0.78678 | 18.10675 |
February | 454.00000 | 27.00085 | 29.69843 | 0.83489 | 19.75984 |
March | 514.00000 | 27.00053 | 31.23166 | 0.90293 | 22.25339 |
April | 485.00000 | 27.41949 | 32.53262 | 1.03025 | 27.70143 |
May | 508.00000 | 27.00049 | 37.66225 | 0.28148 | 6.68868 |
June | 496.00000 | 27.00234 | 37.34897 | 0.30128 | 6.92508 |
July | 497.00000 | 27.00157 | 36.50456 | 0.30876 | 7.01712 |
August | 514.00000 | 27.78429 | 34.89705 | 0.50722 | 11.08048 |
September | 485.00000 | 27.00003 | 40.75350 | 0.29071 | 6.78778 |
October | 502.00000 | 27.00154 | 33.33068 | 0.91644 | 22.76591 |
November | 489.00000 | 27.00057 | 30.48908 | 0.88201 | 21.46573 |
December | 497.00000 | 27.00017 | 28.23392 | 0.83331 | 19.71360 |
Annual Sum or Average | 5943.00000 | 27.10278 | 33.52937 | 0.65470 | 15.81096 |
Minimum of Months | 454.00000 | 27.00003 | 28.23392 | 0.28148 | 6.68868 |
Maximum of Months | 514.00000 | 27.78429 | 40.75350 | 1.03025 | 27.70143 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.90952 | 29.93574 | 0.69573 | 15.63781 |
February | 454.00000 | 27.00092 | 29.19086 | 0.79022 | 18.30249 |
March | 514.00000 | 27.00061 | 30.59049 | 0.89239 | 21.90271 |
April | 485.00000 | 27.30877 | 32.04150 | 1.02255 | 27.40309 |
May | 508.00000 | 27.00058 | 36.98708 | 0.31333 | 7.14368 |
June | 496.00000 | 27.00254 | 36.65729 | 0.33437 | 7.42264 |
July | 497.00000 | 27.00178 | 35.80986 | 0.33588 | 7.43201 |
August | 514.00000 | 27.54028 | 34.33191 | 0.46534 | 10.31167 |
September | 485.00000 | 27.00004 | 40.06620 | 0.30103 | 6.95129 |
October | 502.00000 | 27.00168 | 32.70772 | 0.91099 | 22.59196 |
November | 489.00000 | 27.00066 | 29.86278 | 0.84932 | 20.33492 |
December | 497.00000 | 27.00024 | 27.68206 | 0.76249 | 17.41330 |
Annual Sum or Average | 5943.00000 | 27.06504 | 33.00889 | 0.63796 | 15.19826 |
Minimum of Months | 454.00000 | 26.90952 | 27.68206 | 0.30103 | 6.95129 |
Maximum of Months | 514.00000 | 27.54028 | 40.06620 | 1.02255 | 27.40309 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00515 | 30.03360 | 1.08599 | 29.88112 |
February | 454.00000 | 27.00599 | 30.19470 | 1.23106 | 36.78350 |
March | 514.00000 | 27.00312 | 31.01669 | 1.37177 | 44.01639 |
April | 485.00000 | 29.33892 | 31.10883 | 1.98122 | 74.23090 |
May | 508.00000 | 27.00353 | 34.96380 | 0.54657 | 11.32201 |
June | 496.00000 | 27.00323 | 35.08717 | 0.77472 | 17.66594 |
July | 497.00000 | 27.00174 | 34.48866 | 0.99034 | 25.72824 |
August | 514.00000 | 30.46736 | 31.89435 | 2.19856 | 83.28766 |
September | 485.00000 | 27.00421 | 35.51047 | 0.62243 | 13.19020 |
October | 502.00000 | 27.00277 | 31.99604 | 1.29172 | 39.84832 |
November | 489.00000 | 27.00429 | 30.63887 | 1.41227 | 46.16871 |
December | 497.00000 | 27.00672 | 30.05060 | 1.52564 | 52.29513 |
Annual Sum or Average | 5943.00000 | 27.49413 | 32.25933 | 1.25415 | 39.61053 |
Minimum of Months | 454.00000 | 27.00174 | 30.03360 | 0.54657 | 11.32201 |
Maximum of Months | 514.00000 | 30.46736 | 35.51047 | 2.19856 | 83.28766 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.56104 | 39.70734 | 0.50775 | 11.02737 |
February | 454.00000 | 24.53484 | 44.36356 | 0.53310 | 11.50062 |
March | 514.00000 | 24.43228 | 48.18276 | 0.53824 | 11.53423 |
April | 485.00000 | 24.53135 | 47.49188 | 0.55586 | 12.02171 |
May | 508.00000 | 24.51168 | 58.39214 | -0.2188 | 6.99585 |
June | 496.00000 | 24.48341 | 62.02988 | -0.1886 | 6.94378 |
July | 497.00000 | 24.64271 | 62.63469 | -0.1199 | 7.20800 |
August | 514.00000 | 24.50093 | 61.51795 | -0.1526 | 7.08997 |
September | 485.00000 | 24.57967 | 62.85375 | -0.1348 | 7.20303 |
October | 502.00000 | 24.62638 | 55.71494 | 0.65778 | 14.81207 |
November | 489.00000 | 24.62904 | 46.95179 | 0.59337 | 13.07229 |
December | 497.00000 | 24.61367 | 39.80588 | 0.53125 | 11.56758 |
Annual Sum or Average | 5943.00000 | 24.55345 | 52.54068 | 0.25567 | 10.06417 |
Minimum of Months | 454.00000 | 24.43228 | 39.70734 | -0.2188 | 6.94378 |
Maximum of Months | 514.00000 | 24.64271 | 62.85375 | 0.65778 | 14.81207 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.40147 | 42.10830 | 0.48460 | 10.59898 |
February | 454.00000 | 24.34062 | 45.31433 | 0.50908 | 10.72450 |
March | 514.00000 | 24.25515 | 48.88469 | 0.53132 | 11.12009 |
April | 485.00000 | 24.19359 | 48.66040 | 0.53335 | 11.09114 |
May | 508.00000 | 24.17568 | 54.41140 | -0.3120 | 7.19319 |
June | 496.00000 | 24.16517 | 56.19610 | -0.2938 | 6.93491 |
July | 497.00000 | 24.22666 | 56.39696 | -0.2654 | 6.66719 |
August | 514.00000 | 24.19352 | 56.09823 | -0.2566 | 6.55849 |
September | 485.00000 | 24.26647 | 56.79420 | -0.2704 | 6.86619 |
October | 502.00000 | 24.33186 | 54.08615 | 0.58923 | 12.52038 |
November | 489.00000 | 24.39059 | 47.87201 | 0.55757 | 11.83030 |
December | 497.00000 | 24.40183 | 40.71229 | 0.49985 | 10.58248 |
Annual Sum or Average | 5943.00000 | 24.27781 | 50.67407 | 0.18911 | 9.37622 |
Minimum of Months | 454.00000 | 24.16517 | 40.71229 | -0.3120 | 6.55849 |
Maximum of Months | 514.00000 | 24.40183 | 56.79420 | 0.58923 | 12.52038 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.02710 | 43.11083 | 0.37218 | 8.21850 |
February | 454.00000 | 24.11577 | 45.73816 | 0.42764 | 9.13580 |
March | 514.00000 | 24.18708 | 48.98921 | 0.48760 | 10.18152 |
April | 485.00000 | 24.15363 | 48.98100 | 0.48744 | 10.12498 |
May | 508.00000 | 24.10381 | 54.81589 | -0.3627 | 7.91011 |
June | 496.00000 | 24.11934 | 56.86771 | -0.3431 | 7.63393 |
July | 497.00000 | 24.13863 | 57.58313 | -0.3363 | 7.56042 |
August | 514.00000 | 24.16708 | 57.63722 | -0.3240 | 7.41248 |
September | 485.00000 | 24.25468 | 57.15718 | -0.3038 | 7.32054 |
October | 502.00000 | 24.27808 | 54.45433 | 0.55210 | 11.60014 |
November | 489.00000 | 24.20822 | 48.24068 | 0.48207 | 10.08765 |
December | 497.00000 | 24.03104 | 41.71322 | 0.37256 | 8.13141 |
Annual Sum or Average | 5943.00000 | 24.14873 | 51.32402 | 0.12292 | 8.77292 |
Minimum of Months | 454.00000 | 24.02710 | 41.71322 | -0.3627 | 7.32054 |
Maximum of Months | 514.00000 | 24.27808 | 57.63722 | 0.55210 | 11.60014 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.77742 | 46.88115 | 0.05209 | 6.52087 |
February | 454.00000 | 23.56888 | 47.76877 | 0.28673 | 7.58404 |
March | 514.00000 | 24.08143 | 49.69578 | 0.46588 | 9.81152 |
April | 485.00000 | 24.20482 | 49.11951 | 0.51898 | 10.82835 |
May | 508.00000 | 24.20911 | 54.36190 | -0.2899 | 7.01823 |
June | 496.00000 | 24.20856 | 56.28439 | -0.2737 | 6.86705 |
July | 497.00000 | 24.24719 | 57.05150 | -0.2688 | 6.79954 |
August | 514.00000 | 24.21900 | 57.40377 | -0.2797 | 6.90075 |
September | 485.00000 | 24.28357 | 57.28199 | -0.2750 | 7.03080 |
October | 502.00000 | 24.20678 | 55.37613 | 0.54425 | 11.37517 |
November | 489.00000 | 23.85915 | 50.04552 | 0.39343 | 8.65155 |
December | 497.00000 | 23.10844 | 44.90609 | 0.13586 | 6.52033 |
Annual Sum or Average | 5943.00000 | 23.91691 | 52.22146 | 0.08192 | 7.99271 |
Minimum of Months | 454.00000 | 22.77742 | 44.90609 | -0.2899 | 6.52033 |
Maximum of Months | 514.00000 | 24.28357 | 57.40377 | 0.54425 | 11.37517 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.55093 | 42.88036 | 0.23768 | 6.79758 |
February | 454.00000 | 23.92665 | 45.75302 | 0.37560 | 8.38070 |
March | 514.00000 | 24.20636 | 48.21460 | 0.50564 | 10.60005 |
April | 485.00000 | 24.37755 | 47.23442 | 0.59876 | 12.98254 |
May | 508.00000 | 24.46712 | 52.60502 | -0.1413 | 6.39463 |
June | 496.00000 | 24.40631 | 54.63001 | -0.1286 | 6.18948 |
July | 497.00000 | 24.53331 | 55.08557 | -0.0922 | 6.53482 |
August | 514.00000 | 24.38506 | 55.03714 | -0.1352 | 6.31543 |
September | 485.00000 | 24.43021 | 55.91536 | -0.1782 | 6.56361 |
October | 502.00000 | 24.36893 | 53.19700 | 0.59445 | 12.73781 |
November | 489.00000 | 24.18271 | 47.85865 | 0.47429 | 9.92002 |
December | 497.00000 | 23.83517 | 41.67535 | 0.31702 | 7.46896 |
Annual Sum or Average | 5943.00000 | 24.22439 | 50.04453 | 0.20037 | 8.39900 |
Minimum of Months | 454.00000 | 23.55093 | 41.67535 | -0.1782 | 6.18948 |
Maximum of Months | 514.00000 | 24.53331 | 55.91536 | 0.59876 | 12.98254 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.67624 | 42.18539 | 0.28556 | 7.33282 |
February | 454.00000 | 23.99037 | 45.35738 | 0.41550 | 9.21731 |
March | 514.00000 | 24.23289 | 47.93772 | 0.54202 | 11.64247 |
April | 485.00000 | 24.39047 | 47.01640 | 0.63795 | 14.22262 |
May | 508.00000 | 24.49962 | 52.33623 | -0.0699 | 6.47138 |
June | 496.00000 | 24.38931 | 54.56145 | -0.1049 | 6.17311 |
July | 497.00000 | 24.48551 | 55.19830 | -0.0986 | 6.61749 |
August | 514.00000 | 24.30886 | 55.31797 | -0.1668 | 6.43092 |
September | 485.00000 | 24.42276 | 55.78896 | -0.1532 | 6.44323 |
October | 502.00000 | 24.42610 | 52.79207 | 0.63380 | 14.01826 |
November | 489.00000 | 24.19666 | 47.59011 | 0.50027 | 10.69409 |
December | 497.00000 | 23.75871 | 41.67510 | 0.31508 | 7.66457 |
Annual Sum or Average | 5943.00000 | 24.23293 | 49.85224 | 0.22594 | 8.89996 |
Minimum of Months | 454.00000 | 23.67624 | 41.67510 | -0.1668 | 6.17311 |
Maximum of Months | 514.00000 | 24.49962 | 55.78896 | 0.63795 | 14.22262 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.93579 | 41.29494 | 0.37853 | 8.89064 |
February | 454.00000 | 24.22990 | 44.55587 | 0.50353 | 11.19994 |
March | 514.00000 | 24.34952 | 47.48049 | 0.59521 | 13.02734 |
April | 485.00000 | 24.45193 | 46.87551 | 0.64985 | 14.51946 |
May | 508.00000 | 24.48287 | 52.52282 | -0.1246 | 6.41412 |
June | 496.00000 | 24.40709 | 54.62688 | -0.1292 | 6.22575 |
July | 497.00000 | 24.53415 | 55.07765 | -0.0907 | 6.56067 |
August | 514.00000 | 24.39690 | 54.95805 | -0.1216 | 6.33864 |
September | 485.00000 | 24.48572 | 55.58024 | -0.1169 | 6.46789 |
October | 502.00000 | 24.57569 | 52.15848 | 0.71599 | 16.65329 |
November | 489.00000 | 24.51010 | 46.34825 | 0.64127 | 14.52075 |
December | 497.00000 | 24.23486 | 40.19154 | 0.47305 | 10.58929 |
Annual Sum or Average | 5943.00000 | 24.38338 | 49.34815 | 0.27867 | 10.09782 |
Minimum of Months | 454.00000 | 23.93579 | 40.19154 | -0.1292 | 6.22575 |
Maximum of Months | 514.00000 | 24.57569 | 55.58024 | 0.71599 | 16.65329 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.04019 | 40.87680 | 0.39812 | 8.93999 |
February | 454.00000 | 24.40602 | 43.90695 | 0.55918 | 12.19112 |
March | 514.00000 | 24.49517 | 46.95651 | 0.68343 | 15.52322 |
April | 485.00000 | 24.63601 | 46.17971 | 0.80978 | 19.77065 |
May | 508.00000 | 24.56470 | 52.07667 | 0.00839 | 6.61723 |
June | 496.00000 | 24.51933 | 53.98877 | 0.04193 | 6.54263 |
July | 497.00000 | 24.66754 | 54.27609 | 0.08078 | 7.24744 |
August | 514.00000 | 24.56207 | 54.06422 | 0.10491 | 7.05860 |
September | 485.00000 | 24.53963 | 55.18608 | -0.0458 | 6.41114 |
October | 502.00000 | 24.61133 | 52.04635 | 0.73978 | 17.32306 |
November | 489.00000 | 24.60484 | 46.08279 | 0.67173 | 15.25144 |
December | 497.00000 | 24.55449 | 39.18633 | 0.57854 | 12.71004 |
Annual Sum or Average | 5943.00000 | 24.51701 | 48.77788 | 0.38399 | 11.27504 |
Minimum of Months | 454.00000 | 24.04019 | 39.18633 | -0.0458 | 6.41114 |
Maximum of Months | 514.00000 | 24.66754 | 55.18608 | 0.80978 | 19.77065 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.51378 | 45.18269 | -0.0201 | 6.00647 |
February | 454.00000 | 23.29610 | 47.11971 | 0.20538 | 6.85928 |
March | 514.00000 | 24.04139 | 48.45849 | 0.43988 | 9.40873 |
April | 485.00000 | 24.38201 | 47.20870 | 0.56644 | 12.14264 |
May | 508.00000 | 24.48532 | 52.79450 | -0.1516 | 6.54155 |
June | 496.00000 | 24.42860 | 55.42917 | -0.1407 | 6.34723 |
July | 497.00000 | 24.56928 | 56.83642 | -0.1047 | 6.74439 |
August | 514.00000 | 24.42077 | 56.95916 | -0.1662 | 6.59198 |
September | 485.00000 | 24.46220 | 57.08208 | -0.1839 | 6.86098 |
October | 502.00000 | 24.29964 | 53.52107 | 0.55503 | 11.75865 |
November | 489.00000 | 23.73196 | 48.95492 | 0.34164 | 7.87886 |
December | 497.00000 | 22.76568 | 44.16325 | 0.04215 | 6.04426 |
Annual Sum or Average | 5943.00000 | 23.95445 | 51.17880 | 0.11395 | 7.76601 |
Minimum of Months | 454.00000 | 22.51378 | 44.16325 | -0.1839 | 6.00647 |
Maximum of Months | 514.00000 | 24.56928 | 57.08208 | 0.56644 | 12.14264 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 22.88600 | 43.32844 | 0.07921 | 6.02386 |
February | 385.00000 | 23.63114 | 45.31012 | 0.30387 | 7.93321 |
March | 433.00000 | 24.26368 | 46.95669 | 0.52106 | 11.41537 |
April | 410.00000 | 24.60802 | 45.80578 | 0.66003 | 15.08356 |
May | 430.00000 | 24.63535 | 52.07312 | -0.0469 | 6.86410 |
June | 418.00000 | 24.53872 | 54.94180 | -0.0759 | 6.48730 |
July | 422.00000 | 24.68821 | 56.40809 | -0.0509 | 7.07319 |
August | 433.00000 | 24.51752 | 56.55582 | -0.1238 | 6.70445 |
September | 410.00000 | 24.58086 | 56.68080 | -0.1217 | 6.85315 |
October | 427.00000 | 24.53311 | 52.48502 | 0.63532 | 14.28307 |
November | 417.00000 | 24.01623 | 47.43757 | 0.43092 | 9.55837 |
December | 422.00000 | 23.12464 | 42.48607 | 0.14014 | 6.37523 |
Annual Sum or Average | 5034.00000 | 24.17120 | 50.07332 | 0.19473 | 8.71864 |
Minimum of Months | 385.00000 | 22.88600 | 42.48607 | -0.1238 | 6.02386 |
Maximum of Months | 433.00000 | 24.68821 | 56.68080 | 0.66003 | 15.08356 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.75404 | 41.25971 | 0.32923 | 8.45034 |
February | 454.00000 | 24.09124 | 44.38437 | 0.45577 | 10.55675 |
March | 514.00000 | 24.31467 | 47.22131 | 0.56800 | 12.45449 |
April | 485.00000 | 24.49105 | 46.71987 | 0.63014 | 14.00551 |
May | 508.00000 | 24.49796 | 52.71432 | -0.1365 | 6.53250 |
June | 496.00000 | 24.42500 | 55.44246 | -0.1440 | 6.36562 |
July | 497.00000 | 24.56907 | 56.81794 | -0.1030 | 6.75462 |
August | 514.00000 | 24.43954 | 56.79718 | -0.1472 | 6.59644 |
September | 485.00000 | 24.52870 | 56.60612 | -0.1147 | 6.75979 |
October | 502.00000 | 24.60609 | 52.05846 | 0.71075 | 16.59531 |
November | 489.00000 | 24.45484 | 45.99618 | 0.61240 | 13.89717 |
December | 497.00000 | 24.03083 | 40.23667 | 0.40470 | 9.74738 |
Annual Sum or Average | 5943.00000 | 24.35147 | 49.73607 | 0.25306 | 9.87752 |
Minimum of Months | 454.00000 | 23.75404 | 40.23667 | -0.1472 | 6.36562 |
Maximum of Months | 514.00000 | 24.60609 | 56.81794 | 0.71075 | 16.59531 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.96793 | 43.33847 | 0.11136 | 6.32834 |
February | 454.00000 | 23.65406 | 45.65170 | 0.32209 | 8.27236 |
March | 514.00000 | 24.23564 | 47.54137 | 0.53910 | 11.68457 |
April | 485.00000 | 24.53641 | 46.58593 | 0.67596 | 15.40776 |
May | 508.00000 | 24.56050 | 52.37380 | -0.0453 | 6.72655 |
June | 496.00000 | 24.49229 | 54.99258 | -0.0451 | 6.48738 |
July | 497.00000 | 24.61881 | 56.30901 | -0.0416 | 6.97627 |
August | 514.00000 | 24.48123 | 56.40628 | -0.0954 | 6.59810 |
September | 485.00000 | 24.53784 | 56.46562 | -0.1047 | 6.77787 |
October | 502.00000 | 24.47228 | 52.70118 | 0.64311 | 14.35447 |
November | 489.00000 | 24.06673 | 47.45414 | 0.46255 | 10.06637 |
December | 497.00000 | 23.27338 | 42.21103 | 0.18895 | 6.74524 |
Annual Sum or Average | 5943.00000 | 24.16143 | 50.21010 | 0.21608 | 8.86297 |
Minimum of Months | 454.00000 | 22.96793 | 42.21103 | -0.1047 | 6.32834 |
Maximum of Months | 514.00000 | 24.61881 | 56.46562 | 0.67596 | 15.40776 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.42057 | 47.92334 | -0.3020 | 8.86892 |
February | 454.00000 | 22.62401 | 49.00561 | 0.04024 | 6.88321 |
March | 514.00000 | 23.85289 | 49.27673 | 0.40039 | 9.13037 |
April | 485.00000 | 24.38216 | 47.61673 | 0.58733 | 12.82406 |
May | 508.00000 | 24.50504 | 52.74094 | -0.1058 | 6.58010 |
June | 496.00000 | 24.45174 | 55.26447 | -0.0935 | 6.38113 |
July | 497.00000 | 24.59057 | 56.75548 | -0.0637 | 6.90170 |
August | 514.00000 | 24.43307 | 56.97925 | -0.1343 | 6.57420 |
September | 485.00000 | 24.46228 | 57.34780 | -0.1641 | 6.84501 |
October | 502.00000 | 24.18366 | 54.58180 | 0.53834 | 11.53088 |
November | 489.00000 | 23.24821 | 50.88118 | 0.22737 | 7.24608 |
December | 497.00000 | 21.76944 | 46.66681 | -0.2077 | 7.71288 |
Annual Sum or Average | 5943.00000 | 23.66803 | 52.11423 | 0.05976 | 8.12583 |
Minimum of Months | 454.00000 | 21.42057 | 46.66681 | -0.3020 | 6.38113 |
Maximum of Months | 514.00000 | 24.59057 | 57.34780 | 0.58733 | 12.82406 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.97123 | 46.25283 | -0.1522 | 7.44662 |
February | 454.00000 | 23.18655 | 47.12652 | 0.19889 | 7.50000 |
March | 514.00000 | 24.11810 | 48.13744 | 0.50911 | 11.32785 |
April | 485.00000 | 24.51461 | 46.98742 | 0.68359 | 15.73128 |
May | 508.00000 | 24.55605 | 52.36984 | -0.0074 | 6.84165 |
June | 496.00000 | 24.47514 | 54.98271 | -0.0343 | 6.46438 |
July | 497.00000 | 24.60552 | 56.47619 | -0.0260 | 7.10284 |
August | 514.00000 | 24.44907 | 56.70153 | -0.1001 | 6.59093 |
September | 485.00000 | 24.49094 | 56.94990 | -0.1108 | 6.73508 |
October | 502.00000 | 24.38373 | 53.59605 | 0.62706 | 14.05982 |
November | 489.00000 | 23.70160 | 49.05988 | 0.36435 | 8.85216 |
December | 497.00000 | 22.38727 | 44.83489 | -0.0452 | 6.82473 |
Annual Sum or Average | 5943.00000 | 23.90842 | 51.15827 | 0.15795 | 8.79022 |
Minimum of Months | 454.00000 | 21.97123 | 44.83489 | -0.1522 | 6.46438 |
Maximum of Months | 514.00000 | 24.60552 | 56.94990 | 0.68359 | 15.73128 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.96873 | 43.48811 | 0.11481 | 8.17877 |
February | 454.00000 | 23.67934 | 45.67733 | 0.34596 | 9.70050 |
March | 514.00000 | 24.20951 | 47.84662 | 0.54805 | 12.30400 |
April | 485.00000 | 24.48932 | 47.16929 | 0.65255 | 14.75504 |
May | 508.00000 | 24.51635 | 52.67579 | -0.0907 | 6.60483 |
June | 496.00000 | 24.44903 | 55.27642 | -0.0965 | 6.39883 |
July | 497.00000 | 24.59014 | 56.74451 | -0.0621 | 6.91692 |
August | 514.00000 | 24.45165 | 56.83239 | -0.1149 | 6.61261 |
September | 485.00000 | 24.52982 | 56.89106 | -0.0928 | 6.83532 |
October | 502.00000 | 24.55203 | 52.95640 | 0.70998 | 16.66961 |
November | 489.00000 | 24.24762 | 47.19070 | 0.55823 | 13.04137 |
December | 497.00000 | 23.42871 | 41.98496 | 0.23918 | 8.71649 |
Annual Sum or Average | 5943.00000 | 24.17894 | 50.43718 | 0.22416 | 9.71706 |
Minimum of Months | 454.00000 | 22.96873 | 41.98496 | -0.1149 | 6.39883 |
Maximum of Months | 514.00000 | 24.59014 | 56.89106 | 0.70998 | 16.66961 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.08048 | 45.65236 | -0.1169 | 7.48439 |
February | 454.00000 | 23.10424 | 47.22398 | 0.18768 | 7.73896 |
March | 514.00000 | 24.08872 | 48.24952 | 0.51039 | 11.42908 |
April | 485.00000 | 24.52639 | 47.05557 | 0.69544 | 16.10305 |
May | 508.00000 | 24.56391 | 52.40388 | -0.0050 | 6.95680 |
June | 496.00000 | 24.49686 | 54.91719 | -0.0038 | 6.66703 |
July | 497.00000 | 24.62219 | 56.31954 | -0.0070 | 7.18750 |
August | 514.00000 | 24.47744 | 56.51300 | -0.0703 | 6.64415 |
September | 485.00000 | 24.52255 | 56.79154 | -0.0887 | 6.82919 |
October | 502.00000 | 24.37213 | 53.71143 | 0.63165 | 14.16144 |
November | 489.00000 | 23.69307 | 49.03510 | 0.37511 | 9.16423 |
December | 497.00000 | 22.47465 | 44.29750 | -0.0115 | 6.98787 |
Annual Sum or Average | 5943.00000 | 23.92432 | 51.04813 | 0.17398 | 8.94478 |
Minimum of Months | 454.00000 | 22.08048 | 44.29750 | -0.1169 | 6.64415 |
Maximum of Months | 514.00000 | 24.62219 | 56.79154 | 0.69544 | 16.10305 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.779983E+11 | 102601.76 | 12-JAN-14:10 | 423.63 | 0.457442E+12 | 0.00 | 0.535441E+12 | 3.08 | 7.25 | 25-JAN-15:30 | 0.00 | 0.00 |
February | 0.934064E+11 | 109042.94 | 24-FEB-16:40 | 424.89 | 0.575441E+12 | 0.00 | 0.668847E+12 | 3.64 | 7.42 | 25-FEB-06:03 | 0.00 | 0.00 |
March | 0.146362E+12 | 142048.25 | 14-MAR-05:02 | 579.64 | 0.955352E+12 | 0.00 | 0.110171E+13 | 4.75 | 7.67 | 14-MAR-05:02 | 0.00 | 0.00 |
April | 0.189547E+12 | 194431.18 | 17-APR-05:03 | 671.62 | 0.125994E+13 | 0.00 | 0.144949E+13 | 5.81 | 7.71 | 24-APR-05:03 | 0.00 | 0.00 |
May | 0.242892E+12 | 207213.35 | 25-MAY-05:03 | 687.74 | 0.161286E+13 | 0.00 | 0.185575E+13 | 5.96 | 7.58 | 13-MAY-05:03 | 0.00 | 0.00 |
June | 0.260873E+12 | 228724.68 | 27-JUN-05:04 | 666.68 | 0.169905E+13 | 0.00 | 0.195992E+13 | 5.85 | 7.50 | 02-JUN-05:02 | 0.00 | 0.00 |
July | 0.285848E+12 | 229671.88 | 18-JUL-05:04 | 710.24 | 0.181050E+13 | 0.00 | 0.209635E+13 | 5.79 | 7.02 | 01-JUL-05:03 | 0.00 | 0.00 |
August | 0.281490E+12 | 226767.02 | 14-AUG-05:03 | 706.66 | 0.178552E+13 | 0.00 | 0.206701E+13 | 5.71 | 7.25 | 16-AUG-03:02 | 0.00 | 0.00 |
September | 0.221318E+12 | 218466.06 | 13-SEP-05:03 | 607.69 | 0.142774E+13 | 0.00 | 0.164906E+13 | 5.18 | 7.49 | 27-SEP-05:02 | 0.00 | 0.00 |
October | 0.169379E+12 | 197763.29 | 04-OCT-05:02 | 594.51 | 0.113038E+13 | 0.00 | 0.129975E+13 | 5.02 | 7.80 | 19-OCT-05:02 | 0.00 | 0.00 |
November | 0.123512E+12 | 119908.57 | 10-NOV-06:04 | 515.72 | 0.786963E+12 | 0.00 | 0.910475E+12 | 4.27 | 7.71 | 10-NOV-06:04 | 0.00 | 0.00 |
December | 0.914255E+11 | 107996.48 | 01-DEC-14:30 | 475.59 | 0.549056E+12 | 0.00 | 0.640482E+12 | 3.52 | 7.38 | 07-DEC-15:50 | 0.00 | 0.00 |
Annual Sum or Average | 0.218405E+13 | 7064.62 | 0.140503E+14 | 0.00 | 0.162343E+14 | 4.89 | 0.00 | 0.00 | ||||
Minimum of Months | 0.779983E+11 | 102601.76 | 423.63 | 0.457442E+12 | 0.00 | 0.535441E+12 | 3.08 | 7.02 | 0.00 | 0.00 | ||
Maximum of Months | 0.285848E+12 | 229671.88 | 710.24 | 0.181050E+13 | 0.00 | 0.209635E+13 | 5.96 | 7.80 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.129122E+11 | 142048.25 | 14-MAR-05:02 | 33.52 | 0.918345E+11 | 0.00 | 0.104747E+12 | 0.32 | 7.67 | 14-MAR-05:02 | 0.00 | 0.00 |
April | 0.568678E+11 | 194431.18 | 17-APR-05:03 | 141.06 | 0.402128E+12 | 0.00 | 0.458996E+12 | 1.39 | 7.71 | 24-APR-05:03 | 0.00 | 0.00 |
May | 0.113365E+12 | 207213.35 | 25-MAY-05:03 | 255.73 | 0.779370E+12 | 0.00 | 0.892735E+12 | 2.36 | 7.58 | 13-MAY-05:03 | 0.00 | 0.00 |
June | 0.152057E+12 | 228724.68 | 27-JUN-05:04 | 316.05 | 0.101475E+13 | 0.00 | 0.116681E+13 | 2.93 | 7.50 | 02-JUN-05:02 | 0.00 | 0.00 |
July | 0.187984E+12 | 229671.88 | 18-JUL-05:04 | 379.18 | 0.122876E+13 | 0.00 | 0.141675E+13 | 3.33 | 7.02 | 01-JUL-05:03 | 0.00 | 0.00 |
August | 0.198938E+12 | 226767.02 | 14-AUG-05:03 | 396.15 | 0.129893E+13 | 0.00 | 0.149787E+13 | 3.48 | 7.25 | 16-AUG-03:02 | 0.00 | 0.00 |
September | 0.125038E+12 | 218466.06 | 13-SEP-05:03 | 268.60 | 0.834807E+12 | 0.00 | 0.959845E+12 | 2.49 | 7.49 | 27-SEP-05:02 | 0.00 | 0.00 |
October | 0.485135E+11 | 197763.29 | 04-OCT-05:02 | 121.03 | 0.342262E+12 | 0.00 | 0.390776E+12 | 1.15 | 7.80 | 19-OCT-05:02 | 0.00 | 0.00 |
November | 0.239966E+10 | 119908.57 | 10-NOV-06:04 | 6.33 | 0.171441E+11 | 0.00 | 0.195437E+11 | 0.06 | 7.71 | 10-NOV-06:04 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.898076E+12 | 1917.64 | 0.600999E+13 | 0.00 | 0.690806E+13 | 1.47 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.198938E+12 | 229671.88 | 396.15 | 0.129893E+13 | 0.00 | 0.149787E+13 | 3.48 | 7.80 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: CENTRAL TOWER
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.661162E+11 | 744.00 | 49248.27 | 02-JAN-13:30 | 213681.58 | 12-JAN-17:00 | 22.67 | 19.06 | 14.67 |
February | 0.101046E+12 | 672.00 | 49248.27 | 01-FEB-10:20 | 377518.32 | 24-FEB-16:10 | 28.02 | 21.40 | 14.67 |
March | 0.131866E+12 | 744.00 | 49248.27 | 01-MAR-00:10 | 649395.19 | 31-MAR-24:00 | 36.93 | 27.16 | 14.67 |
April | 0.127652E+12 | 720.00 | 49248.27 | 01-APR-00:03 | 720260.12 | 16-APR-17:31 | 48.57 | 35.61 | 14.67 |
May | 0.131907E+12 | 744.00 | 49248.27 | 01-MAY-00:05 | 379848.41 | 31-MAY-23:20 | 39.84 | 35.25 | 14.67 |
June | 0.127652E+12 | 720.00 | 49248.27 | 01-JUN-00:10 | 557927.11 | 30-JUN-23:25 | 45.33 | 37.49 | 14.67 |
July | 0.131907E+12 | 744.00 | 49248.27 | 01-JUL-00:05 | 688331.62 | 31-JUL-24:00 | 48.00 | 37.11 | 14.67 |
August | 0.131907E+12 | 744.00 | 49248.27 | 01-AUG-00:03 | 720865.23 | 25-AUG-14:30 | 50.10 | 36.73 | 14.67 |
September | 0.127652E+12 | 720.00 | 49248.27 | 01-SEP-00:03 | 376069.05 | 30-SEP-23:17 | 35.69 | 31.03 | 14.67 |
October | 0.131907E+12 | 744.00 | 49248.27 | 01-OCT-00:03 | 487035.78 | 31-OCT-23:40 | 35.78 | 28.60 | 14.67 |
November | 0.125489E+12 | 720.00 | 49248.27 | 01-NOV-00:10 | 548808.77 | 08-NOV-16:10 | 34.17 | 24.51 | 14.67 |
December | 0.121918E+12 | 744.00 | 49248.27 | 01-DEC-07:00 | 669230.44 | 28-DEC-16:30 | 33.56 | 21.41 | 14.67 |
Annual Sum or Average | 0.145702E+13 | 8760.00 | 38.28 | 29.65 | 14.67 | ||||
Minimum of Months | 0.661162E+11 | 672.00 | 49248.27 | 213681.58 | 22.67 | 19.06 | 14.67 | ||
Maximum of Months | 0.131907E+12 | 744.00 | 49248.27 | 720865.23 | 50.10 | 37.49 | 14.67 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.330686E+09 | 298.79 | 1202.13 | 13-JAN-15:00 | 1084391.75 | 25-JAN-16:10 | 21.94 | 21.24 | 35.69 |
February | 0.784495E+09 | 354.47 | 3879.22 | 24-FEB-15:30 | 1223385.09 | 22-FEB-15:30 | 22.39 | 21.36 | 42.86 |
March | 0.719269E+10 | 511.22 | 21281.92 | 06-MAR-13:00 | 1347195.03 | 08-MAR-14:40 | 22.90 | 21.29 | 54.31 |
April | 0.226450E+11 | 618.99 | 21281.92 | 01-APR-09:10 | 1366496.07 | 10-APR-15:30 | 23.68 | 21.60 | 66.06 |
May | 0.471156E+11 | 686.93 | 21281.92 | 01-MAY-04:04 | 1367652.61 | 18-MAY-05:04 | 26.16 | 23.78 | 65.61 |
June | 0.508582E+11 | 666.68 | 21281.92 | 01-JUN-00:23 | 1505420.71 | 27-JUN-05:04 | 28.38 | 25.78 | 60.95 |
July | 0.544152E+11 | 710.24 | 21281.92 | 01-JUL-00:05 | 1498658.13 | 18-JUL-05:04 | 30.10 | 27.38 | 58.42 |
August | 0.541408E+11 | 706.66 | 21281.92 | 01-AUG-00:13 | 1428457.20 | 09-AUG-05:03 | 29.94 | 27.26 | 60.79 |
September | 0.464812E+11 | 607.69 | 21281.92 | 01-SEP-00:03 | 1453080.91 | 06-SEP-05:04 | 28.32 | 26.10 | 54.21 |
October | 0.228882E+11 | 572.24 | 21281.92 | 01-OCT-00:53 | 1400116.52 | 20-OCT-05:04 | 23.51 | 21.75 | 57.48 |
November | 0.301350E+10 | 443.43 | 21281.92 | 06-NOV-10:40 | 1337284.10 | 01-NOV-15:20 | 22.73 | 21.30 | 49.00 |
December | 0.444101E+09 | 339.29 | 1515.80 | 28-DEC-15:00 | 1128014.71 | 01-DEC-16:00 | 22.07 | 21.22 | 41.10 |
Annual Sum or Average | 0.310310E+12 | 6516.64 | 25.19 | 23.35 | 53.92 | ||||
Minimum of Months | 0.330686E+09 | 298.79 | 1202.13 | 1084391.75 | 21.94 | 21.22 | 35.69 | ||
Maximum of Months | 0.544152E+11 | 710.24 | 21281.92 | 1505420.71 | 30.10 | 27.38 | 66.06 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 21.94 | 21.94 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 22.39 | 22.39 | 0.00 |
March | 0.151322E+10 | 20.40 | 21281.92 | 06-MAR-14:30 | 1337175.98 | 14-MAR-05:04 | 22.90 | 22.80 | 1.98 |
April | 0.777715E+10 | 105.05 | 21281.92 | 03-APR-05:03 | 1366496.07 | 10-APR-15:30 | 23.68 | 23.20 | 10.53 |
May | 0.224537E+11 | 293.10 | 21281.92 | 01-MAY-05:03 | 1367652.61 | 18-MAY-05:04 | 26.16 | 24.90 | 27.27 |
June | 0.347117E+11 | 453.07 | 21281.92 | 01-JUN-04:03 | 1505420.71 | 27-JUN-05:04 | 28.38 | 26.35 | 39.53 |
July | 0.460146E+11 | 600.60 | 21281.92 | 01-JUL-00:10 | 1498658.13 | 18-JUL-05:04 | 30.10 | 27.54 | 47.78 |
August | 0.429609E+11 | 560.74 | 21281.92 | 01-AUG-00:57 | 1428457.20 | 09-AUG-05:03 | 29.94 | 27.45 | 46.64 |
September | 0.317588E+11 | 414.53 | 21281.92 | 01-SEP-00:07 | 1453080.91 | 06-SEP-05:04 | 28.32 | 26.51 | 34.84 |
October | 0.742346E+10 | 97.13 | 21281.92 | 02-OCT-08:70 | 1400116.52 | 20-OCT-05:04 | 23.51 | 23.10 | 9.42 |
November | 98731013.26 | 2.53 | 21281.92 | 06-NOV-11:20 | 1321576.11 | 01-NOV-14:40 | 22.73 | 22.71 | 0.25 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 22.07 | 22.07 | 0.00 |
Annual Sum or Average | 0.194712E+12 | 2547.14 | 25.19 | 24.26 | 18.30 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 21.94 | 21.94 | 0.00 | ||
Maximum of Months | 0.460146E+11 | 600.60 | 21281.92 | 1505420.71 | 30.10 | 27.54 | 47.78 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.880845E+10 | 0.00 | 146.56 | 207559.90 | 02-JAN-06:13 | 0.00 | 30.50 | 40.21 | 0.02 | 0.00 | 0.00 | 0.15 | 02-JAN-06:13 |
February | 0.763173E+09 | 0.00 | 39.57 | 113461.85 | 11-FEB-06:02 | 0.00 | 25.57 | 28.68 | 0.00 | 0.00 | 0.00 | 0.08 | 11-FEB-06:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 24.47 | 24.47 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 24.47 | 24.47 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:03 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 24.47 | 24.47 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 24.47 | 24.47 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 24.47 | 24.47 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 24.47 | 24.47 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 5935.83 | 0.00 | 0.17 | 9.89 | 25-SEP-10:20 | 0.00 | 24.47 | 24.48 | 0.00 | 0.00 | 0.00 | 0.00 | 25-SEP-10:20 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 24.47 | 24.47 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 27612496.95 | 0.00 | 7.04 | 2741.34 | 27-NOV-06:05 | 0.00 | 24.34 | 24.88 | 0.00 | 0.00 | 0.00 | 0.00 | 27-NOV-06:05 |
December | 0.237810E+10 | 0.00 | 95.28 | 99383.19 | 23-DEC-06:03 | 0.00 | 25.60 | 32.32 | 0.00 | 0.00 | 0.00 | 0.07 | 23-DEC-06:03 |
Annual Sum or Average | 0.119773E+11 | 0.00 | 288.61 | 0.00 | 25.15 | 26.83 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.34 | 24.47 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.880845E+10 | 0.00 | 146.56 | 207559.90 | 0.00 | 30.50 | 40.21 | 0.02 | 0.00 | 0.00 | 0.15 |
Report: BoilerReportMonthly
For: CENTRAL BOILER
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 22.67 | 22.67 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 28.02 | 28.02 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 36.93 | 36.93 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 48.57 | 48.57 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 39.84 | 39.84 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 45.33 | 45.33 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 48.00 | 48.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 50.10 | 50.10 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 35.69 | 35.69 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 35.78 | 35.78 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 34.17 | 34.17 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 33.56 | 33.56 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 38.28 | 38.28 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.67 | 22.67 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.10 | 50.10 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.453706E+11 | 0.00 | 394.26 | 0.452951E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 86484.70 | 18-JAN-06:03 | 81305.58 | 14-JAN-06:02 | 0.00 | 0.00 | 0.00 |
February | 0.643314E+11 | 0.00 | 410.32 | 0.642073E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 103576.57 | 21-FEB-16:00 | 103576.57 | 21-FEB-16:00 | 0.00 | 0.00 | 0.00 |
March | 0.120624E+12 | 0.00 | 558.15 | 0.118666E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 200178.88 | 29-MAR-05:03 | 149364.99 | 28-MAR-05:02 | 0.00 | 0.00 | 0.00 |
April | 0.177620E+12 | 0.00 | 628.83 | 0.170685E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 249997.83 | 17-APR-05:03 | 177804.91 | 28-APR-05:03 | 0.00 | 0.00 | 0.00 |
May | 0.217423E+12 | 0.00 | 625.36 | 0.184253E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 277208.69 | 22-MAY-05:02 | 192132.13 | 01-MAY-05:03 | 0.00 | 0.00 | 0.00 |
June | 0.256762E+12 | 0.00 | 619.61 | 0.189662E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 287729.18 | 26-JUN-05:02 | 196605.67 | 12-JUN-05:03 | 0.00 | 0.00 | 0.00 |
July | 0.297209E+12 | 0.00 | 645.49 | 0.183584E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 299718.20 | 31-JUL-05:03 | 188075.24 | 05-JUL-05:02 | 0.00 | 0.00 | 0.00 |
August | 0.318655E+12 | 0.00 | 659.77 | 0.194049E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 315682.45 | 28-AUG-05:04 | 184718.35 | 07-AUG-05:03 | 0.00 | 0.00 | 0.00 |
September | 0.221857E+12 | 0.00 | 554.60 | 0.141278E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 283436.53 | 05-SEP-05:02 | 171401.17 | 18-SEP-05:02 | 0.00 | 0.00 | 0.00 |
October | 0.148554E+12 | 0.00 | 557.07 | 0.131722E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 253426.05 | 04-OCT-05:02 | 165376.78 | 04-OCT-05:02 | 0.00 | 0.00 | 0.00 |
November | 0.990074E+11 | 0.00 | 485.97 | 0.977505E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 170716.22 | 10-NOV-06:02 | 132002.40 | 06-NOV-06:02 | 0.00 | 0.00 | 0.00 |
December | 0.660829E+11 | 0.00 | 455.09 | 0.660829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 101627.38 | 29-DEC-06:02 | 101627.38 | 29-DEC-06:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.203350E+13 | 0.00 | 6594.52 | 0.158723E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.453706E+11 | 0.00 | 394.26 | 0.452951E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 86484.70 | 81305.58 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.318655E+12 | 0.00 | 659.77 | 0.194049E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 315682.45 | 196605.67 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.316074E+12 | 0.00 | 364.15 | 0.315985E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 826637.85 | 18-JAN-06:03 | 691505.87 | 14-JAN-06:02 | 0.00 | 0.00 | 0.00 |
February | 0.466977E+12 | 0.00 | 376.96 | 0.465988E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1273675.58 | 25-FEB-06:03 | 863622.00 | 25-FEB-06:03 | 0.00 | 0.00 | 0.00 |
March | 0.922597E+12 | 0.00 | 474.76 | 0.908900E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1917600.85 | 14-MAR-05:02 | 1458699.03 | 29-MAR-05:03 | 0.00 | 0.00 | 0.00 |
April | 0.137792E+13 | 0.00 | 527.95 | 0.132672E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2302218.55 | 26-APR-05:02 | 1563709.22 | 28-APR-05:02 | 0.00 | 0.00 | 0.00 |
May | 0.199934E+13 | 0.00 | 599.75 | 0.168166E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2723695.48 | 24-MAY-03:02 | 1645073.61 | 05-MAY-05:02 | 0.00 | 0.00 | 0.00 |
June | 0.227613E+13 | 0.00 | 575.02 | 0.165161E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2847278.10 | 26-JUN-05:02 | 1737234.01 | 12-JUN-05:02 | 0.00 | 0.00 | 0.00 |
July | 0.250696E+13 | 0.00 | 572.18 | 0.147927E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2980871.43 | 27-JUL-03:02 | 1638125.55 | 06-JUL-05:02 | 0.00 | 0.00 | 0.00 |
August | 0.247813E+13 | 0.00 | 554.50 | 0.141234E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2892133.00 | 10-AUG-05:02 | 1628675.43 | 02-AUG-05:02 | 0.00 | 0.00 | 0.00 |
September | 0.192020E+13 | 0.00 | 487.17 | 0.120040E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2862700.79 | 09-SEP-05:03 | 1597641.34 | 05-SEP-05:02 | 0.00 | 0.00 | 0.00 |
October | 0.121278E+13 | 0.00 | 482.72 | 0.106898E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2437777.84 | 12-OCT-05:02 | 1566354.03 | 04-OCT-05:02 | 0.00 | 0.00 | 0.00 |
November | 0.725332E+12 | 0.00 | 430.63 | 0.716076E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1662271.15 | 09-NOV-06:02 | 1130449.78 | 09-NOV-06:02 | 0.00 | 0.00 | 0.00 |
December | 0.384513E+12 | 0.00 | 401.98 | 0.384513E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 736826.41 | 29-DEC-06:02 | 736826.41 | 29-DEC-06:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.165870E+14 | 0.00 | 5847.78 | 0.126124E+14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.316074E+12 | 0.00 | 364.15 | 0.315985E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 736826.41 | 691505.87 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.250696E+13 | 0.00 | 599.75 | 0.168166E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2980871.43 | 1737234.01 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.232183E+11 | 0.00 | 330.84 | 0.232183E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 59605.80 | 12-JAN-15:00 | 59605.80 | 12-JAN-15:00 | 0.00 | 0.00 | 0.00 |
February | 0.412320E+11 | 0.00 | 352.04 | 0.411399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 111329.74 | 25-FEB-06:03 | 95680.46 | 22-FEB-15:00 | 0.00 | 0.00 | 0.00 |
March | 0.949783E+11 | 0.00 | 459.81 | 0.936886E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 198865.85 | 14-MAR-05:02 | 148160.20 | 14-MAR-05:02 | 0.00 | 0.00 | 0.00 |
April | 0.156239E+12 | 0.00 | 533.79 | 0.150929E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 248592.61 | 17-APR-05:02 | 173491.03 | 28-APR-05:02 | 0.00 | 0.00 | 0.00 |
May | 0.229640E+12 | 0.00 | 612.59 | 0.196709E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 294419.81 | 24-MAY-05:02 | 192890.04 | 30-MAY-04:12 | 0.00 | 0.00 | 0.00 |
June | 0.258883E+12 | 0.00 | 585.68 | 0.194715E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 307109.39 | 22-JUN-05:02 | 212859.37 | 12-JUN-05:03 | 0.00 | 0.00 | 0.00 |
July | 0.276720E+12 | 0.00 | 587.70 | 0.170914E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 342673.02 | 25-JUL-03:02 | 202166.31 | 05-JUL-04:02 | 0.00 | 0.00 | 0.00 |
August | 0.269569E+12 | 0.00 | 568.08 | 0.160250E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 322552.24 | 10-AUG-05:02 | 190612.73 | 07-AUG-05:03 | 0.00 | 0.00 | 0.00 |
September | 0.207122E+12 | 0.00 | 502.94 | 0.132844E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 313339.76 | 08-SEP-05:02 | 179529.59 | 05-SEP-05:02 | 0.00 | 0.00 | 0.00 |
October | 0.125099E+12 | 0.00 | 476.93 | 0.111623E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 249817.80 | 04-OCT-05:02 | 163803.78 | 04-OCT-05:02 | 0.00 | 0.00 | 0.00 |
November | 0.673464E+11 | 0.00 | 406.88 | 0.669089E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 152748.17 | 09-NOV-06:02 | 107643.09 | 09-NOV-14:50 | 0.00 | 0.00 | 0.00 |
December | 0.288834E+11 | 0.00 | 365.13 | 0.288834E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 67394.81 | 01-DEC-15:00 | 67394.81 | 01-DEC-15:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.177893E+13 | 0.00 | 5782.40 | 0.137182E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.232183E+11 | 0.00 | 330.84 | 0.232183E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 59605.80 | 59605.80 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.276720E+12 | 0.00 | 612.59 | 0.196709E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 342673.02 | 212859.37 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.508292E+11 | 0.00 | 400.75 | 0.507519E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 98805.55 | 17-JAN-04:02 | 85660.86 | 17-JAN-04:02 | 0.00 | 0.00 | 0.00 |
February | 0.523339E+11 | 0.00 | 372.33 | 0.522820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 116353.47 | 27-FEB-04:02 | 92250.81 | 06-FEB-04:03 | 0.00 | 0.00 | 0.00 |
March | 0.727924E+11 | 0.00 | 442.59 | 0.725662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 135638.78 | 13-MAR-03:02 | 94169.09 | 13-MAR-03:02 | 0.00 | 0.00 | 0.00 |
April | 0.849268E+11 | 0.00 | 417.45 | 0.829803E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 158468.71 | 27-APR-03:02 | 112826.30 | 28-APR-03:02 | 0.00 | 0.00 | 0.00 |
May | 0.109000E+12 | 0.00 | 448.09 | 0.968889E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 184999.95 | 22-MAY-03:02 | 125322.27 | 29-MAY-16:09 | 0.00 | 0.00 | 0.00 |
June | 0.128552E+12 | 0.00 | 450.82 | 0.100906E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 213420.58 | 26-JUN-03:02 | 119657.49 | 04-JUN-18:30 | 0.00 | 0.00 | 0.00 |
July | 0.150085E+12 | 0.00 | 463.53 | 0.100371E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 224035.41 | 30-JUL-19:40 | 116198.71 | 04-JUL-19:50 | 0.00 | 0.00 | 0.00 |
August | 0.168700E+12 | 0.00 | 500.84 | 0.109043E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 240745.28 | 27-AUG-14:59 | 105262.05 | 06-AUG-16:17 | 0.00 | 0.00 | 0.00 |
September | 0.132492E+12 | 0.00 | 461.39 | 0.931082E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 217368.28 | 17-SEP-20:17 | 103850.85 | 24-SEP-12:42 | 0.00 | 0.00 | 0.00 |
October | 0.951481E+11 | 0.00 | 471.64 | 0.883773E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 166534.52 | 04-OCT-03:02 | 115586.04 | 01-OCT-15:41 | 0.00 | 0.00 | 0.00 |
November | 0.728296E+11 | 0.00 | 434.41 | 0.725483E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 121054.96 | 09-NOV-06:02 | 113349.96 | 05-NOV-13:48 | 0.00 | 0.00 | 0.00 |
December | 0.582386E+11 | 0.00 | 410.56 | 0.582313E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 92460.77 | 29-DEC-04:02 | 88388.53 | 29-DEC-04:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.117593E+13 | 0.00 | 5274.39 | 0.978054E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.508292E+11 | 0.00 | 372.33 | 0.507519E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 92460.77 | 85660.86 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.168700E+12 | 0.00 | 500.84 | 0.109043E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 240745.28 | 125322.27 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.337411E+12 | 0.874060E+11 | 744.00 | 0.323791E+12 | 0.136203E+11 | 0.00 | 0.35 | 12-JAN-16:00 | 0.32 | 22-JAN-06:00 | 131369.15 | 17-JAN-15:00 | 127093.53 | 12-JAN-15:00 | 6384.37 | 17-JAN-15:00 | 41117.70 | 12-JAN-15:00 | 0.00 |
February | 0.532790E+12 | 0.141624E+12 | 672.00 | 0.515874E+12 | 0.169161E+11 | 0.00 | 0.60 | 22-FEB-15:00 | 0.53 | 01-FEB-00:10 | 225101.03 | 24-FEB-17:00 | 219749.13 | 22-FEB-15:00 | 10336.41 | 27-FEB-09:40 | 77474.54 | 22-FEB-15:00 | 0.00 |
March | 0.835439E+12 | 0.253971E+12 | 744.00 | 0.821376E+12 | 0.140632E+11 | 0.00 | 0.98 | 31-MAR-24:00 | 0.74 | 01-MAR-02:00 | 395738.57 | 31-MAR-24:00 | 393445.91 | 31-MAR-23:53 | 13903.23 | 05-MAR-06:00 | 136174.48 | 28-MAR-15:30 | 0.00 |
April | 0.103387E+13 | 0.368918E+12 | 720.00 | 0.102764E+13 | 0.623054E+10 | 0.00 | 1.00 | 01-APR-08:70 | 0.42 | 30-APR-23:17 | 409642.52 | 22-APR-17:00 | 403753.64 | 30-APR-04:53 | 8847.56 | 11-APR-05:00 | 173337.68 | 15-APR-15:00 | 0.00 |
May | 0.362309E+12 | 0.148435E+12 | 744.00 | 0.345365E+12 | 0.169447E+11 | 0.00 | 0.60 | 31-MAY-23:15 | 0.35 | 28-MAY-05:00 | 226062.27 | 31-MAY-23:03 | 212657.17 | 31-MAY-24:00 | 15171.85 | 22-MAY-23:10 | 79009.18 | 31-MAY-23:15 | 0.00 |
June | 0.598264E+12 | 0.245268E+12 | 720.00 | 0.572403E+12 | 0.258618E+11 | 0.00 | 0.85 | 30-JUN-24:00 | 0.58 | 18-JUN-04:55 | 318207.61 | 30-JUN-23:03 | 306905.83 | 30-JUN-24:00 | 18586.69 | 28-JUN-13:30 | 127495.20 | 30-JUN-23:20 | 0.00 |
July | 0.873669E+12 | 0.339011E+12 | 744.00 | 0.837004E+12 | 0.366650E+11 | 0.00 | 1.00 | 31-JUL-23:03 | 0.80 | 19-JUL-03:00 | 401295.33 | 31-JUL-24:00 | 389769.04 | 31-JUL-24:00 | 19562.60 | 18-JUL-08:30 | 157203.28 | 07-JUL-15:00 | 0.00 |
August | 0.109901E+13 | 0.390764E+12 | 744.00 | 0.106349E+13 | 0.355186E+11 | 0.00 | 1.00 | 01-AUG-00:03 | 0.45 | 31-AUG-23:17 | 421246.85 | 10-AUG-14:00 | 404479.86 | 15-AUG-23:57 | 20793.96 | 25-AUG-16:00 | 166009.77 | 07-AUG-15:00 | 0.00 |
September | 0.366104E+12 | 0.132071E+12 | 720.00 | 0.334825E+12 | 0.312789E+11 | 0.00 | 0.59 | 30-SEP-23:03 | 0.36 | 27-SEP-05:00 | 227388.26 | 30-SEP-23:03 | 213521.24 | 30-SEP-24:00 | 18092.20 | 12-SEP-16:00 | 76147.96 | 30-SEP-23:13 | 0.00 |
October | 0.601447E+12 | 0.197519E+12 | 744.00 | 0.585009E+12 | 0.164374E+11 | 0.00 | 0.76 | 31-OCT-23:30 | 0.55 | 31-OCT-05:00 | 310615.61 | 31-OCT-24:00 | 302108.06 | 31-OCT-24:00 | 11505.56 | 13-OCT-08:30 | 101578.67 | 02-OCT-15:00 | 0.00 |
November | 0.817191E+12 | 0.229491E+12 | 720.00 | 0.797581E+12 | 0.196103E+11 | 0.00 | 0.84 | 08-NOV-15:00 | 0.75 | 26-NOV-06:00 | 321426.53 | 24-NOV-08:15 | 313962.50 | 08-NOV-15:00 | 14617.17 | 23-NOV-08:00 | 118404.11 | 08-NOV-15:00 | 0.00 |
December | 0.109883E+13 | 0.269807E+12 | 744.00 | 0.106407E+13 | 0.347623E+11 | 0.00 | 1.00 | 03-DEC-13:43 | 0.93 | 01-DEC-00:10 | 421933.43 | 22-DEC-06:03 | 403434.75 | 28-DEC-17:00 | 25655.78 | 22-DEC-06:03 | 130068.41 | 28-DEC-14:10 | 0.00 |
Annual Sum or Average | 0.855633E+13 | 0.280428E+13 | 8760.00 | 0.828842E+13 | 0.267909E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.337411E+12 | 0.874060E+11 | 672.00 | 0.323791E+12 | 0.623054E+10 | 0.00 | 0.35 | 0.32 | 131369.15 | 127093.53 | 6384.37 | 41117.70 | 0.00 | ||||||
Maximum of Months | 0.109901E+13 | 0.390764E+12 | 744.00 | 0.106407E+13 | 0.366650E+11 | 0.00 | 1.00 | 0.93 | 421933.43 | 404479.86 | 25655.78 | 173337.68 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.496405E+10 | 0.129302E+10 | 744.00 | 0.481944E+10 | 0.144612E+09 | 0.00 | 0.31 | 12-JAN-17:00 | 0.17 | 07-JAN-08:00 | 2461.85 | 12-JAN-17:00 | 2332.68 | 12-JAN-17:00 | 242.12 | 17-JAN-16:20 | 735.21 | 12-JAN-16:00 | 0.00 |
February | 0.956863E+10 | 0.252289E+10 | 672.00 | 0.934264E+10 | 0.225990E+09 | 0.00 | 0.56 | 20-FEB-17:03 | 0.41 | 02-FEB-07:00 | 4507.57 | 21-FEB-17:00 | 4401.49 | 20-FEB-17:15 | 262.69 | 15-FEB-17:10 | 1488.42 | 22-FEB-15:00 | 0.00 |
March | 0.161863E+11 | 0.482578E+10 | 744.00 | 0.158562E+11 | 0.330177E+09 | 0.00 | 0.91 | 31-MAR-24:00 | 0.64 | 01-MAR-07:00 | 7782.42 | 31-MAR-24:00 | 7681.68 | 31-MAR-23:53 | 335.36 | 10-MAR-17:10 | 2714.53 | 28-MAR-16:00 | 0.00 |
April | 0.209044E+11 | 0.743386E+10 | 720.00 | 0.205976E+11 | 0.306832E+09 | 0.00 | 1.00 | 01-APR-13:50 | 0.39 | 30-APR-23:05 | 8531.71 | 17-APR-01:55 | 8274.66 | 17-APR-01:55 | 382.96 | 26-APR-08:00 | 3558.27 | 15-APR-15:00 | 0.00 |
May | 0.718480E+10 | 0.283565E+10 | 744.00 | 0.652195E+10 | 0.662852E+09 | 0.00 | 0.57 | 31-MAY-23:03 | 0.29 | 13-MAY-07:00 | 4655.66 | 31-MAY-23:03 | 4059.13 | 31-MAY-24:00 | 642.66 | 22-MAY-23:10 | 1588.38 | 01-MAY-15:40 | 0.00 |
June | 0.123015E+11 | 0.483594E+10 | 720.00 | 0.112179E+11 | 0.108358E+10 | 0.00 | 0.81 | 30-JUN-23:25 | 0.54 | 18-JUN-03:55 | 6544.35 | 30-JUN-23:03 | 6064.99 | 30-JUN-24:00 | 811.24 | 28-JUN-13:30 | 2530.51 | 08-JUN-16:00 | 0.00 |
July | 0.181648E+11 | 0.675365E+10 | 744.00 | 0.165539E+11 | 0.161083E+10 | 0.00 | 1.00 | 31-JUL-23:03 | 0.75 | 19-JUL-03:00 | 8536.99 | 31-JUL-23:03 | 7838.72 | 31-JUL-24:00 | 844.79 | 18-JUL-08:20 | 3270.86 | 02-JUL-16:50 | 0.00 |
August | 0.227886E+11 | 0.803399E+10 | 744.00 | 0.210995E+11 | 0.168917E+10 | 0.00 | 1.00 | 01-AUG-00:03 | 0.38 | 31-AUG-23:05 | 8774.97 | 10-AUG-14:10 | 8063.92 | 29-AUG-03:35 | 862.19 | 21-AUG-14:00 | 3414.04 | 07-AUG-15:00 | 0.00 |
September | 0.731155E+10 | 0.250726E+10 | 720.00 | 0.604316E+10 | 0.126840E+10 | 0.00 | 0.56 | 30-SEP-23:03 | 0.30 | 27-SEP-06:00 | 4619.85 | 30-SEP-23:03 | 4023.56 | 30-SEP-24:00 | 731.12 | 12-SEP-16:00 | 1470.29 | 30-SEP-23:13 | 0.00 |
October | 0.116850E+11 | 0.373155E+10 | 744.00 | 0.110668E+11 | 0.618249E+09 | 0.00 | 0.69 | 31-OCT-23:20 | 0.47 | 31-OCT-06:00 | 5960.59 | 31-OCT-23:10 | 5756.59 | 31-OCT-24:00 | 493.68 | 06-OCT-09:50 | 2030.82 | 02-OCT-15:00 | 0.00 |
November | 0.155412E+11 | 0.430270E+10 | 720.00 | 0.152313E+11 | 0.309876E+09 | 0.00 | 0.80 | 08-NOV-16:20 | 0.64 | 25-NOV-08:00 | 6553.50 | 08-NOV-16:40 | 6338.54 | 12-NOV-16:20 | 282.78 | 08-NOV-20:00 | 2318.84 | 08-NOV-15:00 | 0.00 |
December | 0.205124E+11 | 0.502349E+10 | 744.00 | 0.203422E+11 | 0.170145E+09 | 0.00 | 0.96 | 25-DEC-14:13 | 0.81 | 23-DEC-08:00 | 8226.95 | 28-DEC-17:00 | 8066.52 | 28-DEC-17:00 | 252.92 | 29-DEC-17:10 | 2561.58 | 25-DEC-14:00 | 0.00 |
Annual Sum or Average | 0.167113E+12 | 0.540998E+11 | 8760.00 | 0.158693E+12 | 0.842071E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.496405E+10 | 0.129302E+10 | 672.00 | 0.481944E+10 | 0.144612E+09 | 0.00 | 0.31 | 0.17 | 2461.85 | 2332.68 | 242.12 | 735.21 | 0.00 | ||||||
Maximum of Months | 0.227886E+11 | 0.803399E+10 | 744.00 | 0.210995E+11 | 0.168917E+10 | 0.00 | 1.00 | 0.81 | 8774.97 | 8274.66 | 862.19 | 3558.27 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.376245E+11 | 0.999568E+10 | 744.00 | 0.362624E+11 | 0.136201E+10 | 0.00 | 0.31 | 12-JAN-17:00 | 0.10 | 01-JAN-06:55 | 22908.01 | 12-JAN-17:00 | 21638.91 | 12-JAN-17:00 | 2378.01 | 17-JAN-16:20 | 6800.40 | 12-JAN-16:50 | 0.00 |
February | 0.856789E+11 | 0.227712E+11 | 672.00 | 0.834441E+11 | 0.223480E+10 | 0.00 | 0.56 | 22-FEB-17:00 | 0.35 | 11-FEB-08:00 | 42571.53 | 22-FEB-17:00 | 41083.14 | 21-FEB-17:00 | 2602.39 | 15-FEB-17:10 | 14104.48 | 22-FEB-15:00 | 0.00 |
March | 0.153034E+12 | 0.457082E+11 | 744.00 | 0.149743E+12 | 0.329083E+10 | 0.00 | 0.92 | 31-MAR-24:00 | 0.62 | 01-MAR-07:00 | 75049.05 | 31-MAR-24:00 | 74037.22 | 31-MAR-23:53 | 3336.43 | 10-MAR-17:10 | 25898.19 | 28-MAR-16:00 | 0.00 |
April | 0.198255E+12 | 0.706109E+11 | 720.00 | 0.195176E+12 | 0.307970E+10 | 0.00 | 1.00 | 01-APR-13:30 | 0.33 | 30-APR-24:00 | 80291.95 | 12-APR-16:00 | 78037.86 | 12-APR-16:10 | 3831.10 | 26-APR-08:00 | 33920.29 | 15-APR-15:00 | 0.00 |
May | 0.677233E+11 | 0.267355E+11 | 744.00 | 0.611764E+11 | 0.654694E+10 | 0.00 | 0.57 | 31-MAY-23:15 | 0.28 | 13-MAY-07:00 | 44631.54 | 31-MAY-23:03 | 39048.59 | 31-MAY-24:00 | 6283.20 | 22-MAY-23:20 | 14805.77 | 31-MAY-23:15 | 0.00 |
June | 0.117176E+12 | 0.460233E+11 | 720.00 | 0.106404E+12 | 0.107720E+11 | 0.00 | 0.82 | 30-JUN-23:15 | 0.53 | 24-JUN-13:40 | 63260.26 | 30-JUN-23:03 | 58359.92 | 30-JUN-24:00 | 8087.89 | 28-JUN-13:30 | 24241.94 | 30-JUN-23:15 | 0.00 |
July | 0.173140E+12 | 0.642970E+11 | 744.00 | 0.157083E+12 | 0.160575E+11 | 0.00 | 1.00 | 31-JUL-23:03 | 0.76 | 19-JUL-03:00 | 81503.66 | 31-JUL-23:03 | 74853.49 | 31-JUL-23:50 | 8424.40 | 18-JUL-08:20 | 30709.35 | 02-JUL-16:51 | 0.00 |
August | 0.216311E+12 | 0.764863E+11 | 744.00 | 0.199372E+12 | 0.169391E+11 | 0.00 | 1.00 | 01-AUG-00:03 | 0.34 | 31-AUG-23:05 | 83476.87 | 10-AUG-14:10 | 76173.71 | 16-AUG-09:40 | 8599.85 | 21-AUG-14:00 | 32540.05 | 07-AUG-15:00 | 0.00 |
September | 0.687551E+11 | 0.235570E+11 | 720.00 | 0.562298E+11 | 0.125253E+11 | 0.00 | 0.57 | 30-SEP-23:03 | 0.29 | 08-SEP-21:20 | 44822.67 | 30-SEP-23:03 | 38802.02 | 30-SEP-24:00 | 7229.46 | 12-SEP-16:00 | 14192.19 | 30-SEP-23:13 | 0.00 |
October | 0.110166E+12 | 0.352266E+11 | 744.00 | 0.104033E+12 | 0.613356E+10 | 0.00 | 0.68 | 31-OCT-23:20 | 0.45 | 31-OCT-06:00 | 56366.39 | 31-OCT-23:10 | 54291.33 | 31-OCT-24:00 | 4921.84 | 06-OCT-09:50 | 19313.76 | 02-OCT-15:00 | 0.00 |
November | 0.144678E+12 | 0.402210E+11 | 720.00 | 0.141592E+12 | 0.308659E+10 | 0.00 | 0.80 | 08-NOV-16:20 | 0.60 | 25-NOV-08:00 | 62400.34 | 08-NOV-16:50 | 59910.59 | 08-NOV-16:30 | 2790.36 | 08-NOV-20:00 | 22054.10 | 08-NOV-15:00 | 0.00 |
December | 0.187690E+12 | 0.462811E+11 | 744.00 | 0.185987E+12 | 0.170305E+10 | 0.00 | 0.95 | 28-DEC-16:40 | 0.76 | 23-DEC-08:00 | 77874.40 | 28-DEC-17:00 | 76278.70 | 28-DEC-17:00 | 2521.47 | 29-DEC-17:10 | 24193.82 | 28-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.156023E+13 | 0.507914E+12 | 8760.00 | 0.147650E+13 | 0.837314E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.376245E+11 | 0.999568E+10 | 672.00 | 0.362624E+11 | 0.136201E+10 | 0.00 | 0.31 | 0.10 | 22908.01 | 21638.91 | 2378.01 | 6800.40 | 0.00 | ||||||
Maximum of Months | 0.216311E+12 | 0.764863E+11 | 744.00 | 0.199372E+12 | 0.169391E+11 | 0.00 | 1.00 | 0.76 | 83476.87 | 78037.86 | 8599.85 | 33920.29 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.226246E+10 | 0.628486E+09 | 660.92 | 0.213883E+10 | 0.123629E+09 | 0.00 | 0.30 | 12-JAN-17:00 | 0.00 | 01-JAN-00:10 | 2298.72 | 12-JAN-17:00 | 2163.49 | 12-JAN-17:00 | 250.75 | 17-JAN-15:20 | 686.03 | 12-JAN-16:50 | 0.00 |
February | 0.786748E+10 | 0.212871E+10 | 672.00 | 0.763117E+10 | 0.236311E+09 | 0.00 | 0.55 | 22-FEB-17:00 | 0.26 | 11-FEB-06:00 | 4312.75 | 22-FEB-17:00 | 4152.27 | 22-FEB-17:00 | 267.83 | 15-FEB-17:10 | 1437.73 | 22-FEB-15:00 | 0.00 |
March | 0.151537E+11 | 0.457270E+10 | 744.00 | 0.148056E+11 | 0.348082E+09 | 0.00 | 0.90 | 31-MAR-24:00 | 0.56 | 01-MAR-08:00 | 7466.29 | 31-MAR-24:00 | 7357.89 | 31-MAR-23:53 | 341.44 | 10-MAR-17:10 | 2660.05 | 28-MAR-16:00 | 0.00 |
April | 0.200188E+11 | 0.719157E+10 | 720.00 | 0.196932E+11 | 0.325613E+09 | 0.00 | 1.00 | 01-APR-15:00 | 0.34 | 30-APR-24:00 | 8283.88 | 16-APR-20:54 | 8012.65 | 16-APR-21:32 | 390.24 | 26-APR-08:00 | 3508.65 | 15-APR-15:00 | 0.00 |
May | 0.703734E+10 | 0.279211E+10 | 744.00 | 0.636088E+10 | 0.676457E+09 | 0.00 | 0.55 | 31-MAY-23:15 | 0.26 | 13-MAY-07:00 | 4452.01 | 31-MAY-23:03 | 3884.53 | 31-MAY-24:00 | 640.87 | 31-MAY-23:03 | 1616.12 | 28-MAY-16:31 | 0.00 |
June | 0.119715E+11 | 0.472930E+10 | 720.00 | 0.108733E+11 | 0.109817E+10 | 0.00 | 0.81 | 30-JUN-23:15 | 0.51 | 24-JUN-13:50 | 6391.36 | 30-JUN-23:03 | 5889.48 | 30-JUN-24:00 | 818.99 | 28-JUN-13:30 | 2564.20 | 11-JUN-16:10 | 0.00 |
July | 0.175570E+11 | 0.656192E+10 | 744.00 | 0.159304E+11 | 0.162657E+10 | 0.00 | 1.00 | 31-JUL-23:03 | 0.73 | 19-JUL-03:00 | 8395.53 | 31-JUL-23:03 | 7618.14 | 31-JUL-23:57 | 849.73 | 18-JUL-08:20 | 3282.92 | 02-JUL-16:51 | 0.00 |
August | 0.220047E+11 | 0.785259E+10 | 744.00 | 0.202827E+11 | 0.172192E+10 | 0.00 | 1.00 | 01-AUG-08:30 | 0.34 | 31-AUG-23:13 | 8537.75 | 10-AUG-14:10 | 7817.29 | 20-AUG-17:25 | 871.50 | 21-AUG-14:00 | 3365.16 | 07-AUG-15:00 | 0.00 |
September | 0.698050E+10 | 0.240576E+10 | 720.00 | 0.570770E+10 | 0.127279E+10 | 0.00 | 0.55 | 30-SEP-23:03 | 0.27 | 09-SEP-17:13 | 4501.53 | 30-SEP-23:03 | 3871.73 | 30-SEP-23:17 | 730.00 | 12-SEP-16:00 | 1437.24 | 30-SEP-23:13 | 0.00 |
October | 0.109526E+11 | 0.353440E+10 | 744.00 | 0.103210E+11 | 0.631566E+09 | 0.00 | 0.65 | 31-OCT-23:20 | 0.41 | 28-OCT-07:00 | 5524.99 | 31-OCT-23:10 | 5289.64 | 31-OCT-24:00 | 501.43 | 06-OCT-09:50 | 1988.65 | 02-OCT-15:10 | 0.00 |
November | 0.139720E+11 | 0.393913E+10 | 720.00 | 0.136458E+11 | 0.326139E+09 | 0.00 | 0.79 | 08-NOV-16:20 | 0.50 | 26-NOV-07:40 | 6296.21 | 08-NOV-16:40 | 6042.89 | 08-NOV-16:30 | 286.18 | 08-NOV-20:00 | 2241.86 | 08-NOV-15:00 | 0.00 |
December | 0.175460E+11 | 0.440401E+10 | 744.00 | 0.173600E+11 | 0.185941E+09 | 0.00 | 0.93 | 28-DEC-16:40 | 0.62 | 31-DEC-08:70 | 7798.23 | 28-DEC-17:00 | 7631.12 | 28-DEC-17:00 | 258.84 | 29-DEC-17:10 | 2439.28 | 28-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.153324E+12 | 0.507407E+11 | 8676.92 | 0.144751E+12 | 0.857319E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.226246E+10 | 0.628486E+09 | 660.92 | 0.213883E+10 | 0.123629E+09 | 0.00 | 0.30 | 0.00 | 2298.72 | 2163.49 | 250.75 | 686.03 | 0.00 | ||||||
Maximum of Months | 0.220047E+11 | 0.785259E+10 | 744.00 | 0.202827E+11 | 0.172192E+10 | 0.00 | 1.00 | 0.73 | 8537.75 | 8012.65 | 871.50 | 3508.65 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 91.15 | 0.00 | 91.15 | 47.39 | 367.50 | 0.00 | 0.00 | 0.00 |
February | 108.09 | 0.00 | 108.09 | 100.03 | 279.60 | 0.00 | 0.00 | 0.00 |
March | 130.25 | 0.00 | 130.25 | 197.35 | 159.38 | 0.00 | 0.00 | 0.00 |
April | 141.33 | 0.48 | 140.85 | 339.19 | 52.61 | 0.00 | 0.00 | 0.00 |
May | 156.58 | 4.39 | 152.19 | 474.79 | 8.04 | 0.00 | 0.00 | 0.00 |
June | 162.09 | 6.00 | 156.08 | 514.42 | 6.03 | 0.00 | 0.00 | 0.00 |
July | 159.85 | 2.53 | 157.32 | 456.97 | 1.33 | 0.00 | 0.00 | 0.00 |
August | 146.75 | 0.46 | 146.29 | 382.02 | 5.29 | 0.00 | 0.00 | 0.00 |
September | 130.76 | 0.01 | 130.75 | 302.25 | 20.81 | 0.00 | 0.00 | 0.00 |
October | 113.28 | 0.00 | 113.28 | 218.66 | 120.85 | 0.00 | 0.00 | 0.00 |
November | 95.95 | 0.00 | 95.95 | 116.48 | 246.22 | 0.00 | 0.00 | 0.00 |
December | 88.92 | 0.00 | 88.92 | 52.45 | 358.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 127.18 | 1.16 | 126.02 | 267.64 | 134.94 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 88.92 | 0.00 | 88.92 | 47.39 | 1.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 162.09 | 6.00 | 157.32 | 514.42 | 367.50 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 91.15 | 0.00 | 91.15 | 47.38 | 367.50 | 0.00 | 0.00 | 0.00 |
February | 108.09 | 0.00 | 108.09 | 100.03 | 279.60 | 0.00 | 0.00 | 0.00 |
March | 130.24 | 0.00 | 130.24 | 197.35 | 159.38 | 0.00 | 0.00 | 0.00 |
April | 141.33 | 0.48 | 140.85 | 339.19 | 52.61 | 0.00 | 0.00 | 0.00 |
May | 156.58 | 4.39 | 152.18 | 474.79 | 8.04 | 0.00 | 0.00 | 0.00 |
June | 162.08 | 6.00 | 156.08 | 514.42 | 6.03 | 0.00 | 0.00 | 0.00 |
July | 159.85 | 2.53 | 157.32 | 456.97 | 1.33 | 0.00 | 0.00 | 0.00 |
August | 146.75 | 0.46 | 146.29 | 382.02 | 5.29 | 0.00 | 0.00 | 0.00 |
September | 130.76 | 0.01 | 130.75 | 302.25 | 20.81 | 0.00 | 0.00 | 0.00 |
October | 113.28 | 0.00 | 113.28 | 218.66 | 120.85 | 0.00 | 0.00 | 0.00 |
November | 95.95 | 0.00 | 95.95 | 116.48 | 246.21 | 0.00 | 0.00 | 0.00 |
December | 88.92 | 0.00 | 88.92 | 52.45 | 358.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 127.18 | 1.16 | 126.02 | 267.64 | 134.94 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 88.92 | 0.00 | 88.92 | 47.38 | 1.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 162.08 | 6.00 | 157.32 | 514.42 | 367.50 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 91.15 | 0.00 | 91.15 | 47.38 | 367.50 | 0.00 | 0.00 | 0.00 |
February | 108.09 | 0.00 | 108.09 | 100.03 | 279.60 | 0.00 | 0.00 | 0.00 |
March | 130.24 | 0.00 | 130.24 | 197.35 | 159.38 | 0.00 | 0.00 | 0.00 |
April | 141.33 | 0.48 | 140.85 | 339.19 | 52.61 | 0.00 | 0.00 | 0.00 |
May | 156.58 | 4.39 | 152.19 | 474.79 | 8.04 | 0.00 | 0.00 | 0.00 |
June | 162.08 | 6.00 | 156.08 | 514.42 | 6.03 | 0.00 | 0.00 | 0.00 |
July | 159.85 | 2.53 | 157.32 | 456.97 | 1.33 | 0.00 | 0.00 | 0.00 |
August | 146.75 | 0.46 | 146.29 | 382.02 | 5.29 | 0.00 | 0.00 | 0.00 |
September | 130.76 | 0.01 | 130.75 | 302.25 | 20.81 | 0.00 | 0.00 | 0.00 |
October | 113.28 | 0.00 | 113.28 | 218.66 | 120.85 | 0.00 | 0.00 | 0.00 |
November | 95.95 | 0.00 | 95.95 | 116.48 | 246.21 | 0.00 | 0.00 | 0.00 |
December | 88.92 | 0.00 | 88.92 | 52.45 | 358.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 127.18 | 1.16 | 126.02 | 267.64 | 134.94 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 88.92 | 0.00 | 88.92 | 47.38 | 1.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 162.08 | 6.00 | 157.32 | 514.42 | 367.50 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 91.15 | 0.00 | 91.15 | 47.38 | 367.50 | 0.00 | 0.00 | 0.00 |
February | 108.09 | 0.00 | 108.09 | 100.03 | 279.60 | 0.00 | 0.00 | 0.00 |
March | 130.24 | 0.00 | 130.24 | 197.35 | 159.38 | 0.00 | 0.00 | 0.00 |
April | 141.33 | 0.48 | 140.85 | 339.19 | 52.61 | 0.00 | 0.00 | 0.00 |
May | 156.58 | 4.39 | 152.18 | 474.79 | 8.04 | 0.00 | 0.00 | 0.00 |
June | 162.08 | 6.00 | 156.08 | 514.42 | 6.03 | 0.00 | 0.00 | 0.00 |
July | 159.85 | 2.53 | 157.32 | 456.97 | 1.33 | 0.00 | 0.00 | 0.00 |
August | 146.75 | 0.46 | 146.29 | 382.02 | 5.29 | 0.00 | 0.00 | 0.00 |
September | 130.76 | 0.01 | 130.75 | 302.25 | 20.81 | 0.00 | 0.00 | 0.00 |
October | 113.28 | 0.00 | 113.28 | 218.66 | 120.85 | 0.00 | 0.00 | 0.00 |
November | 95.95 | 0.00 | 95.95 | 116.48 | 246.21 | 0.00 | 0.00 | 0.00 |
December | 88.92 | 0.00 | 88.92 | 52.45 | 358.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 127.18 | 1.16 | 126.02 | 267.64 | 134.94 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 88.92 | 0.00 | 88.92 | 47.38 | 1.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 162.08 | 6.00 | 157.32 | 514.42 | 367.50 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 91.14 | 0.00 | 91.14 | 47.38 | 367.48 | 0.00 | 0.00 | 0.00 |
February | 108.08 | 0.00 | 108.08 | 100.03 | 279.59 | 0.00 | 0.00 | 0.00 |
March | 130.24 | 0.00 | 130.24 | 197.34 | 159.38 | 0.00 | 0.00 | 0.00 |
April | 141.32 | 0.48 | 140.84 | 339.17 | 52.61 | 0.00 | 0.00 | 0.00 |
May | 156.57 | 4.39 | 152.18 | 474.77 | 8.04 | 0.00 | 0.00 | 0.00 |
June | 162.08 | 6.00 | 156.07 | 514.40 | 6.03 | 0.00 | 0.00 | 0.00 |
July | 159.84 | 2.53 | 157.31 | 456.95 | 1.33 | 0.00 | 0.00 | 0.00 |
August | 146.74 | 0.46 | 146.28 | 382.00 | 5.29 | 0.00 | 0.00 | 0.00 |
September | 130.75 | 0.01 | 130.74 | 302.24 | 20.81 | 0.00 | 0.00 | 0.00 |
October | 113.27 | 0.00 | 113.27 | 218.65 | 120.84 | 0.00 | 0.00 | 0.00 |
November | 95.94 | 0.00 | 95.94 | 116.47 | 246.20 | 0.00 | 0.00 | 0.00 |
December | 88.91 | 0.00 | 88.91 | 52.45 | 358.71 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 127.17 | 1.16 | 126.01 | 267.63 | 134.93 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 88.91 | 0.00 | 88.91 | 47.38 | 1.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 162.08 | 6.00 | 157.31 | 514.40 | 367.48 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 216.96 | 87.08 | 129.87 | 217.25 | 369.31 | 0.00 | 0.00 | 0.00 |
February | 263.57 | 108.82 | 154.76 | 339.19 | 284.17 | 0.00 | 0.00 | 0.00 |
March | 321.53 | 132.72 | 188.81 | 522.97 | 163.71 | 0.00 | 0.00 | 0.00 |
April | 382.54 | 178.36 | 204.18 | 778.42 | 53.77 | 0.00 | 0.00 | 0.00 |
May | 376.52 | 166.93 | 209.59 | 883.61 | 8.45 | 0.00 | 0.00 | 0.00 |
June | 306.44 | 101.68 | 204.76 | 799.63 | 5.84 | 0.00 | 0.00 | 0.00 |
July | 257.56 | 54.39 | 203.17 | 658.63 | 0.91 | 0.00 | 0.00 | 0.00 |
August | 232.07 | 40.39 | 191.68 | 558.60 | 3.63 | 0.00 | 0.00 | 0.00 |
September | 247.94 | 69.14 | 178.79 | 519.09 | 21.38 | 0.00 | 0.00 | 0.00 |
October | 271.22 | 109.55 | 161.66 | 500.61 | 127.88 | 0.00 | 0.00 | 0.00 |
November | 240.47 | 103.22 | 137.25 | 354.58 | 251.21 | 0.00 | 0.00 | 0.00 |
December | 209.68 | 83.08 | 126.60 | 228.68 | 358.67 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 277.13 | 102.79 | 174.35 | 530.77 | 136.80 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 209.68 | 40.39 | 126.60 | 217.25 | 0.91 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 382.54 | 178.36 | 209.59 | 883.61 | 369.31 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 216.96 | 87.08 | 129.87 | 217.25 | 369.31 | 0.00 | 0.00 | 0.00 |
February | 263.57 | 108.82 | 154.76 | 339.19 | 284.17 | 0.00 | 0.00 | 0.00 |
March | 321.53 | 132.72 | 188.81 | 522.97 | 163.71 | 0.00 | 0.00 | 0.00 |
April | 382.54 | 178.36 | 204.18 | 778.42 | 53.77 | 0.00 | 0.00 | 0.00 |
May | 376.52 | 166.93 | 209.59 | 883.61 | 8.45 | 0.00 | 0.00 | 0.00 |
June | 306.44 | 101.68 | 204.76 | 799.63 | 5.84 | 0.00 | 0.00 | 0.00 |
July | 257.56 | 54.39 | 203.17 | 658.63 | 0.91 | 0.00 | 0.00 | 0.00 |
August | 232.07 | 40.39 | 191.68 | 558.60 | 3.63 | 0.00 | 0.00 | 0.00 |
September | 247.94 | 69.14 | 178.79 | 519.09 | 21.38 | 0.00 | 0.00 | 0.00 |
October | 271.22 | 109.55 | 161.66 | 500.61 | 127.88 | 0.00 | 0.00 | 0.00 |
November | 240.47 | 103.22 | 137.25 | 354.58 | 251.21 | 0.00 | 0.00 | 0.00 |
December | 209.68 | 83.08 | 126.60 | 228.68 | 358.67 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 277.13 | 102.79 | 174.35 | 530.77 | 136.80 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 209.68 | 40.39 | 126.60 | 217.25 | 0.91 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 382.54 | 178.36 | 209.59 | 883.61 | 369.31 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 216.95 | 87.08 | 129.87 | 217.24 | 369.30 | 0.00 | 0.00 | 0.00 |
February | 263.57 | 108.81 | 154.75 | 339.18 | 284.16 | 0.00 | 0.00 | 0.00 |
March | 321.53 | 132.71 | 188.81 | 522.96 | 163.70 | 0.00 | 0.00 | 0.00 |
April | 382.53 | 178.36 | 204.18 | 778.40 | 53.77 | 0.00 | 0.00 | 0.00 |
May | 376.52 | 166.93 | 209.59 | 883.60 | 8.45 | 0.00 | 0.00 | 0.00 |
June | 306.43 | 101.67 | 204.76 | 799.61 | 5.84 | 0.00 | 0.00 | 0.00 |
July | 257.55 | 54.39 | 203.16 | 658.62 | 0.91 | 0.00 | 0.00 | 0.00 |
August | 232.06 | 40.38 | 191.68 | 558.59 | 3.63 | 0.00 | 0.00 | 0.00 |
September | 247.93 | 69.14 | 178.79 | 519.08 | 21.38 | 0.00 | 0.00 | 0.00 |
October | 271.21 | 109.55 | 161.66 | 500.60 | 127.88 | 0.00 | 0.00 | 0.00 |
November | 240.47 | 103.22 | 137.25 | 354.57 | 251.20 | 0.00 | 0.00 | 0.00 |
December | 209.68 | 83.08 | 126.60 | 228.68 | 358.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 277.13 | 102.78 | 174.34 | 530.76 | 136.80 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 209.68 | 40.38 | 126.60 | 217.24 | 0.91 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 382.53 | 178.36 | 209.59 | 883.60 | 369.30 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 414.54 | 251.88 | 162.65 | 567.57 | 334.31 | 0.00 | 0.00 | 0.00 |
February | 394.17 | 218.93 | 175.24 | 587.79 | 269.34 | 0.00 | 0.00 | 0.00 |
March | 337.02 | 148.86 | 188.16 | 588.49 | 163.46 | 0.00 | 0.00 | 0.00 |
April | 236.73 | 66.81 | 169.92 | 547.33 | 57.35 | 0.00 | 0.00 | 0.00 |
May | 170.24 | 12.60 | 157.64 | 508.44 | 8.22 | 0.00 | 0.00 | 0.00 |
June | 155.72 | 2.66 | 153.07 | 501.87 | 6.09 | 0.00 | 0.00 | 0.00 |
July | 162.43 | 2.23 | 160.20 | 463.91 | 1.25 | 0.00 | 0.00 | 0.00 |
August | 172.31 | 9.20 | 163.11 | 434.75 | 5.54 | 0.00 | 0.00 | 0.00 |
September | 230.99 | 59.95 | 171.04 | 495.80 | 23.45 | 0.00 | 0.00 | 0.00 |
October | 397.40 | 221.90 | 175.49 | 735.82 | 128.50 | 0.00 | 0.00 | 0.00 |
November | 496.37 | 328.09 | 168.28 | 803.81 | 245.35 | 0.00 | 0.00 | 0.00 |
December | 443.00 | 277.59 | 165.40 | 628.63 | 332.96 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 300.37 | 132.90 | 167.47 | 571.72 | 130.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 155.72 | 2.23 | 153.07 | 434.75 | 1.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 496.37 | 328.09 | 188.16 | 803.81 | 334.31 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 414.53 | 251.88 | 162.65 | 567.57 | 334.31 | 0.00 | 0.00 | 0.00 |
February | 394.16 | 218.93 | 175.23 | 587.79 | 269.34 | 0.00 | 0.00 | 0.00 |
March | 337.02 | 148.86 | 188.16 | 588.49 | 163.46 | 0.00 | 0.00 | 0.00 |
April | 236.72 | 66.81 | 169.91 | 547.33 | 57.35 | 0.00 | 0.00 | 0.00 |
May | 170.24 | 12.60 | 157.64 | 508.44 | 8.22 | 0.00 | 0.00 | 0.00 |
June | 155.72 | 2.66 | 153.07 | 501.87 | 6.09 | 0.00 | 0.00 | 0.00 |
July | 162.43 | 2.23 | 160.20 | 463.90 | 1.25 | 0.00 | 0.00 | 0.00 |
August | 172.31 | 9.20 | 163.10 | 434.75 | 5.54 | 0.00 | 0.00 | 0.00 |
September | 230.99 | 59.95 | 171.04 | 495.80 | 23.45 | 0.00 | 0.00 | 0.00 |
October | 397.39 | 221.90 | 175.49 | 735.82 | 128.50 | 0.00 | 0.00 | 0.00 |
November | 496.37 | 328.09 | 168.28 | 803.81 | 245.35 | 0.00 | 0.00 | 0.00 |
December | 442.99 | 277.59 | 165.40 | 628.62 | 332.96 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 300.37 | 132.90 | 167.47 | 571.72 | 130.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 155.72 | 2.23 | 153.07 | 434.75 | 1.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 496.37 | 328.09 | 188.16 | 803.81 | 334.31 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 414.54 | 251.88 | 162.65 | 567.57 | 334.31 | 0.00 | 0.00 | 0.00 |
February | 394.17 | 218.93 | 175.24 | 587.79 | 269.34 | 0.00 | 0.00 | 0.00 |
March | 337.02 | 148.86 | 188.16 | 588.49 | 163.46 | 0.00 | 0.00 | 0.00 |
April | 236.73 | 66.81 | 169.92 | 547.33 | 57.35 | 0.00 | 0.00 | 0.00 |
May | 170.24 | 12.60 | 157.64 | 508.44 | 8.22 | 0.00 | 0.00 | 0.00 |
June | 155.72 | 2.66 | 153.07 | 501.87 | 6.09 | 0.00 | 0.00 | 0.00 |
July | 162.43 | 2.23 | 160.20 | 463.91 | 1.25 | 0.00 | 0.00 | 0.00 |
August | 172.31 | 9.20 | 163.11 | 434.75 | 5.54 | 0.00 | 0.00 | 0.00 |
September | 230.99 | 59.95 | 171.04 | 495.80 | 23.45 | 0.00 | 0.00 | 0.00 |
October | 397.40 | 221.90 | 175.49 | 735.82 | 128.50 | 0.00 | 0.00 | 0.00 |
November | 496.37 | 328.09 | 168.28 | 803.81 | 245.35 | 0.00 | 0.00 | 0.00 |
December | 443.00 | 277.59 | 165.40 | 628.63 | 332.96 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 300.37 | 132.90 | 167.47 | 571.72 | 130.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 155.72 | 2.23 | 153.07 | 434.75 | 1.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 496.37 | 328.09 | 188.16 | 803.81 | 334.31 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 414.53 | 251.88 | 162.65 | 567.57 | 334.31 | 0.00 | 0.00 | 0.00 |
February | 394.16 | 218.93 | 175.23 | 587.79 | 269.34 | 0.00 | 0.00 | 0.00 |
March | 337.02 | 148.86 | 188.16 | 588.49 | 163.46 | 0.00 | 0.00 | 0.00 |
April | 236.72 | 66.81 | 169.91 | 547.33 | 57.35 | 0.00 | 0.00 | 0.00 |
May | 170.24 | 12.60 | 157.64 | 508.44 | 8.22 | 0.00 | 0.00 | 0.00 |
June | 155.72 | 2.66 | 153.07 | 501.87 | 6.09 | 0.00 | 0.00 | 0.00 |
July | 162.43 | 2.23 | 160.20 | 463.90 | 1.25 | 0.00 | 0.00 | 0.00 |
August | 172.31 | 9.20 | 163.10 | 434.75 | 5.54 | 0.00 | 0.00 | 0.00 |
September | 230.99 | 59.95 | 171.04 | 495.80 | 23.45 | 0.00 | 0.00 | 0.00 |
October | 397.39 | 221.90 | 175.49 | 735.82 | 128.50 | 0.00 | 0.00 | 0.00 |
November | 496.37 | 328.09 | 168.28 | 803.81 | 245.35 | 0.00 | 0.00 | 0.00 |
December | 442.99 | 277.59 | 165.40 | 628.62 | 332.96 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 300.37 | 132.90 | 167.47 | 571.72 | 130.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 155.72 | 2.23 | 153.07 | 434.75 | 1.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 496.37 | 328.09 | 188.16 | 803.81 | 334.31 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 414.52 | 251.87 | 162.65 | 567.55 | 334.30 | 0.00 | 0.00 | 0.00 |
February | 394.15 | 218.92 | 175.23 | 587.77 | 269.33 | 0.00 | 0.00 | 0.00 |
March | 337.01 | 148.85 | 188.15 | 588.47 | 163.46 | 0.00 | 0.00 | 0.00 |
April | 236.72 | 66.81 | 169.91 | 547.31 | 57.34 | 0.00 | 0.00 | 0.00 |
May | 170.23 | 12.60 | 157.63 | 508.42 | 8.22 | 0.00 | 0.00 | 0.00 |
June | 155.72 | 2.66 | 153.06 | 501.85 | 6.09 | 0.00 | 0.00 | 0.00 |
July | 162.43 | 2.23 | 160.19 | 463.89 | 1.25 | 0.00 | 0.00 | 0.00 |
August | 172.30 | 9.20 | 163.10 | 434.74 | 5.54 | 0.00 | 0.00 | 0.00 |
September | 230.98 | 59.95 | 171.03 | 495.78 | 23.45 | 0.00 | 0.00 | 0.00 |
October | 397.38 | 221.89 | 175.49 | 735.79 | 128.50 | 0.00 | 0.00 | 0.00 |
November | 496.35 | 328.07 | 168.27 | 803.78 | 245.34 | 0.00 | 0.00 | 0.00 |
December | 442.98 | 277.58 | 165.40 | 628.60 | 332.95 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 300.36 | 132.89 | 167.47 | 571.70 | 130.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 155.72 | 2.23 | 153.06 | 434.74 | 1.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 496.35 | 328.07 | 188.15 | 803.78 | 334.30 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 212.26 | 82.60 | 129.65 | 233.49 | 428.03 | 0.00 | 0.00 | 0.00 |
February | 242.72 | 89.45 | 153.27 | 315.20 | 343.34 | 0.00 | 0.00 | 0.00 |
March | 314.75 | 125.82 | 188.93 | 506.22 | 211.29 | 0.00 | 0.00 | 0.00 |
April | 382.57 | 179.41 | 203.16 | 752.30 | 89.44 | 0.00 | 0.00 | 0.00 |
May | 362.26 | 153.66 | 208.60 | 843.49 | 15.14 | 0.00 | 0.00 | 0.00 |
June | 340.26 | 132.17 | 208.09 | 830.60 | 11.83 | 0.00 | 0.00 | 0.00 |
July | 252.49 | 49.11 | 203.38 | 607.75 | 5.29 | 0.00 | 0.00 | 0.00 |
August | 231.88 | 41.21 | 190.67 | 511.02 | 20.27 | 0.00 | 0.00 | 0.00 |
September | 254.90 | 74.83 | 180.07 | 519.35 | 35.66 | 0.00 | 0.00 | 0.00 |
October | 265.31 | 105.65 | 159.67 | 485.90 | 159.89 | 0.00 | 0.00 | 0.00 |
November | 240.02 | 102.29 | 137.72 | 359.56 | 311.12 | 0.00 | 0.00 | 0.00 |
December | 205.39 | 78.32 | 127.07 | 224.56 | 443.18 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 275.35 | 101.08 | 174.27 | 516.34 | 172.14 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 205.39 | 41.21 | 127.07 | 224.56 | 5.29 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 382.57 | 179.41 | 208.60 | 843.49 | 443.18 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 212.26 | 82.60 | 129.65 | 233.49 | 428.03 | 0.00 | 0.00 | 0.00 |
February | 242.72 | 89.45 | 153.27 | 315.20 | 343.34 | 0.00 | 0.00 | 0.00 |
March | 314.75 | 125.82 | 188.93 | 506.22 | 211.29 | 0.00 | 0.00 | 0.00 |
April | 382.57 | 179.41 | 203.16 | 752.30 | 89.44 | 0.00 | 0.00 | 0.00 |
May | 362.26 | 153.66 | 208.60 | 843.49 | 15.14 | 0.00 | 0.00 | 0.00 |
June | 340.26 | 132.17 | 208.09 | 830.60 | 11.83 | 0.00 | 0.00 | 0.00 |
July | 252.49 | 49.11 | 203.38 | 607.75 | 5.29 | 0.00 | 0.00 | 0.00 |
August | 231.88 | 41.21 | 190.67 | 511.02 | 20.27 | 0.00 | 0.00 | 0.00 |
September | 254.90 | 74.83 | 180.07 | 519.35 | 35.66 | 0.00 | 0.00 | 0.00 |
October | 265.31 | 105.65 | 159.67 | 485.90 | 159.89 | 0.00 | 0.00 | 0.00 |
November | 240.02 | 102.29 | 137.72 | 359.56 | 311.12 | 0.00 | 0.00 | 0.00 |
December | 205.39 | 78.32 | 127.07 | 224.56 | 443.18 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 275.35 | 101.08 | 174.27 | 516.34 | 172.14 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 205.39 | 41.21 | 127.07 | 224.56 | 5.29 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 382.57 | 179.41 | 208.60 | 843.49 | 443.18 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 212.25 | 82.60 | 129.65 | 233.48 | 428.03 | 0.00 | 0.00 | 0.00 |
February | 242.72 | 89.45 | 153.27 | 315.19 | 343.33 | 0.00 | 0.00 | 0.00 |
March | 314.74 | 125.81 | 188.93 | 506.21 | 211.28 | 0.00 | 0.00 | 0.00 |
April | 382.56 | 179.41 | 203.16 | 752.29 | 89.44 | 0.00 | 0.00 | 0.00 |
May | 362.25 | 153.66 | 208.59 | 843.47 | 15.14 | 0.00 | 0.00 | 0.00 |
June | 340.25 | 132.16 | 208.09 | 830.58 | 11.83 | 0.00 | 0.00 | 0.00 |
July | 252.48 | 49.11 | 203.38 | 607.74 | 5.28 | 0.00 | 0.00 | 0.00 |
August | 231.88 | 41.21 | 190.67 | 511.01 | 20.27 | 0.00 | 0.00 | 0.00 |
September | 254.90 | 74.83 | 180.07 | 519.34 | 35.65 | 0.00 | 0.00 | 0.00 |
October | 265.31 | 105.65 | 159.66 | 485.89 | 159.89 | 0.00 | 0.00 | 0.00 |
November | 240.02 | 102.29 | 137.72 | 359.55 | 311.11 | 0.00 | 0.00 | 0.00 |
December | 205.38 | 78.32 | 127.07 | 224.56 | 443.17 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 275.35 | 101.08 | 174.27 | 516.33 | 172.13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 205.38 | 41.21 | 127.07 | 224.56 | 5.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 382.56 | 179.41 | 208.59 | 843.47 | 443.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 455.75 | 0.00 | 455.75 | 282.51 | 1658.77 | 0.00 | 0.00 | 0.00 |
February | 540.44 | 0.00 | 540.44 | 538.41 | 1282.23 | 0.00 | 0.00 | 0.00 |
March | 651.23 | 0.00 | 651.23 | 1008.91 | 761.47 | 0.00 | 0.00 | 0.00 |
April | 706.64 | 2.40 | 704.24 | 1737.17 | 256.13 | 0.00 | 0.00 | 0.00 |
May | 782.90 | 21.97 | 760.93 | 2397.84 | 41.53 | 0.00 | 0.00 | 0.00 |
June | 810.43 | 30.02 | 780.41 | 2597.81 | 32.69 | 0.00 | 0.00 | 0.00 |
July | 799.27 | 12.66 | 786.61 | 2312.28 | 8.60 | 0.00 | 0.00 | 0.00 |
August | 733.75 | 2.29 | 731.46 | 1953.70 | 27.83 | 0.00 | 0.00 | 0.00 |
September | 653.79 | 0.05 | 653.75 | 1522.75 | 108.63 | 0.00 | 0.00 | 0.00 |
October | 566.40 | 0.00 | 566.40 | 1114.90 | 588.65 | 0.00 | 0.00 | 0.00 |
November | 479.74 | 0.00 | 479.74 | 618.77 | 1141.57 | 0.00 | 0.00 | 0.00 |
December | 444.59 | 0.00 | 444.59 | 319.03 | 1596.03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 635.89 | 5.80 | 630.09 | 1371.05 | 622.58 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 444.59 | 0.00 | 444.59 | 282.51 | 8.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 810.43 | 30.02 | 786.61 | 2597.81 | 1658.77 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 650.86 | 261.25 | 389.61 | 676.13 | 1032.49 | 0.00 | 0.00 | 0.00 |
February | 790.71 | 326.44 | 464.27 | 1025.52 | 815.37 | 0.00 | 0.00 | 0.00 |
March | 964.58 | 398.15 | 566.44 | 1561.14 | 497.94 | 0.00 | 0.00 | 0.00 |
April | 1147.61 | 535.07 | 612.53 | 2323.43 | 180.58 | 0.00 | 0.00 | 0.00 |
May | 1129.56 | 500.78 | 628.77 | 2641.81 | 29.05 | 0.00 | 0.00 | 0.00 |
June | 919.31 | 305.03 | 614.29 | 2388.54 | 22.33 | 0.00 | 0.00 | 0.00 |
July | 772.66 | 163.16 | 609.49 | 1962.01 | 5.08 | 0.00 | 0.00 | 0.00 |
August | 696.20 | 121.15 | 575.04 | 1661.76 | 19.06 | 0.00 | 0.00 | 0.00 |
September | 743.81 | 207.43 | 536.38 | 1548.74 | 76.29 | 0.00 | 0.00 | 0.00 |
October | 813.64 | 328.66 | 484.98 | 1496.77 | 394.38 | 0.00 | 0.00 | 0.00 |
November | 721.41 | 309.66 | 411.75 | 1069.33 | 734.90 | 0.00 | 0.00 | 0.00 |
December | 629.04 | 249.23 | 379.81 | 709.89 | 1013.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 831.39 | 308.36 | 523.03 | 1590.71 | 399.93 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 629.04 | 121.15 | 379.81 | 676.13 | 5.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1147.61 | 535.07 | 628.77 | 2641.81 | 1032.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2072.73 | 1259.44 | 813.28 | 2819.13 | 1650.06 | 0.00 | 0.00 | 0.00 |
February | 1970.86 | 1094.67 | 876.19 | 2921.52 | 1324.64 | 0.00 | 0.00 | 0.00 |
March | 1685.13 | 744.31 | 940.82 | 2932.20 | 814.22 | 0.00 | 0.00 | 0.00 |
April | 1183.64 | 334.06 | 849.58 | 2751.91 | 288.58 | 0.00 | 0.00 | 0.00 |
May | 851.20 | 63.01 | 788.18 | 2564.76 | 41.62 | 0.00 | 0.00 | 0.00 |
June | 778.63 | 13.29 | 765.34 | 2537.45 | 32.27 | 0.00 | 0.00 | 0.00 |
July | 812.18 | 11.17 | 801.01 | 2348.72 | 7.59 | 0.00 | 0.00 | 0.00 |
August | 861.55 | 46.01 | 815.54 | 2208.98 | 29.14 | 0.00 | 0.00 | 0.00 |
September | 1154.98 | 299.78 | 855.20 | 2475.08 | 126.38 | 0.00 | 0.00 | 0.00 |
October | 1987.02 | 1109.54 | 877.48 | 3665.47 | 653.74 | 0.00 | 0.00 | 0.00 |
November | 2481.90 | 1640.48 | 841.42 | 4001.99 | 1218.94 | 0.00 | 0.00 | 0.00 |
December | 2215.03 | 1388.00 | 827.03 | 3137.88 | 1623.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1501.89 | 664.51 | 837.38 | 2862.43 | 647.88 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 778.63 | 11.17 | 765.34 | 2208.98 | 7.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2481.90 | 1640.48 | 940.82 | 4001.99 | 1650.06 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 636.76 | 247.80 | 388.96 | 734.66 | 1142.62 | 0.00 | 0.00 | 0.00 |
February | 728.15 | 268.34 | 459.81 | 981.58 | 904.24 | 0.00 | 0.00 | 0.00 |
March | 944.23 | 377.44 | 566.79 | 1550.54 | 558.32 | 0.00 | 0.00 | 0.00 |
April | 1147.70 | 538.23 | 609.47 | 2317.11 | 211.51 | 0.00 | 0.00 | 0.00 |
May | 1086.77 | 460.98 | 625.78 | 2559.20 | 39.11 | 0.00 | 0.00 | 0.00 |
June | 1020.76 | 396.49 | 624.27 | 2544.53 | 28.70 | 0.00 | 0.00 | 0.00 |
July | 757.46 | 147.33 | 610.13 | 1900.60 | 8.36 | 0.00 | 0.00 | 0.00 |
August | 695.65 | 123.64 | 572.01 | 1636.70 | 25.16 | 0.00 | 0.00 | 0.00 |
September | 764.70 | 224.49 | 540.20 | 1577.66 | 92.11 | 0.00 | 0.00 | 0.00 |
October | 795.93 | 316.94 | 478.99 | 1482.88 | 434.29 | 0.00 | 0.00 | 0.00 |
November | 720.05 | 306.88 | 413.17 | 1119.48 | 815.85 | 0.00 | 0.00 | 0.00 |
December | 616.15 | 234.95 | 381.20 | 737.20 | 1106.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 826.04 | 303.23 | 522.82 | 1596.99 | 445.25 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 616.15 | 123.64 | 381.20 | 734.66 | 8.36 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1147.70 | 538.23 | 625.78 | 2559.20 | 1142.62 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 455.75 | 0.00 | 455.75 | 345.73 | 1440.50 | 0.00 | 0.00 | 0.00 |
February | 540.44 | 0.00 | 540.44 | 577.59 | 1167.14 | 0.00 | 0.00 | 0.00 |
March | 651.23 | 0.00 | 651.23 | 1008.60 | 731.89 | 0.00 | 0.00 | 0.00 |
April | 706.64 | 2.40 | 704.24 | 1707.49 | 258.86 | 0.00 | 0.00 | 0.00 |
May | 782.90 | 21.97 | 760.93 | 2350.60 | 46.78 | 0.00 | 0.00 | 0.00 |
June | 810.43 | 30.02 | 780.41 | 2545.76 | 36.73 | 0.00 | 0.00 | 0.00 |
July | 799.27 | 12.66 | 786.61 | 2260.62 | 9.57 | 0.00 | 0.00 | 0.00 |
August | 733.75 | 2.29 | 731.46 | 1913.09 | 31.39 | 0.00 | 0.00 | 0.00 |
September | 653.79 | 0.05 | 653.75 | 1498.61 | 113.16 | 0.00 | 0.00 | 0.00 |
October | 566.40 | 0.00 | 566.40 | 1108.21 | 573.17 | 0.00 | 0.00 | 0.00 |
November | 479.74 | 0.00 | 479.74 | 644.29 | 1059.80 | 0.00 | 0.00 | 0.00 |
December | 444.59 | 0.00 | 444.59 | 378.69 | 1415.83 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 635.89 | 5.80 | 630.09 | 1365.45 | 571.12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 444.59 | 0.00 | 444.59 | 345.73 | 9.57 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 810.43 | 30.02 | 786.61 | 2545.76 | 1440.50 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 650.86 | 261.25 | 389.61 | 733.79 | 911.31 | 0.00 | 0.00 | 0.00 |
February | 790.71 | 326.44 | 464.27 | 1051.76 | 758.59 | 0.00 | 0.00 | 0.00 |
March | 964.58 | 398.15 | 566.44 | 1557.73 | 486.74 | 0.00 | 0.00 | 0.00 |
April | 1147.61 | 535.07 | 612.53 | 2300.98 | 184.81 | 0.00 | 0.00 | 0.00 |
May | 1129.56 | 500.78 | 628.77 | 2607.29 | 33.06 | 0.00 | 0.00 | 0.00 |
June | 919.31 | 305.03 | 614.29 | 2351.21 | 25.31 | 0.00 | 0.00 | 0.00 |
July | 772.66 | 163.16 | 609.49 | 1925.64 | 5.61 | 0.00 | 0.00 | 0.00 |
August | 696.20 | 121.15 | 575.04 | 1633.20 | 21.58 | 0.00 | 0.00 | 0.00 |
September | 743.81 | 207.43 | 536.38 | 1531.19 | 79.87 | 0.00 | 0.00 | 0.00 |
October | 813.64 | 328.66 | 484.98 | 1490.12 | 389.30 | 0.00 | 0.00 | 0.00 |
November | 721.41 | 309.66 | 411.75 | 1084.67 | 696.32 | 0.00 | 0.00 | 0.00 |
December | 629.04 | 249.23 | 379.81 | 758.30 | 917.98 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 831.39 | 308.36 | 523.03 | 1587.34 | 374.14 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 629.04 | 121.15 | 379.81 | 733.79 | 5.61 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1147.61 | 535.07 | 628.77 | 2607.29 | 917.98 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2072.73 | 1259.44 | 813.28 | 2881.95 | 1479.87 | 0.00 | 0.00 | 0.00 |
February | 1970.86 | 1094.67 | 876.19 | 2945.42 | 1240.41 | 0.00 | 0.00 | 0.00 |
March | 1685.13 | 744.31 | 940.82 | 2922.43 | 795.65 | 0.00 | 0.00 | 0.00 |
April | 1183.64 | 334.06 | 849.58 | 2719.84 | 294.19 | 0.00 | 0.00 | 0.00 |
May | 851.20 | 63.01 | 788.18 | 2517.18 | 46.89 | 0.00 | 0.00 | 0.00 |
June | 778.63 | 13.29 | 765.34 | 2484.96 | 36.51 | 0.00 | 0.00 | 0.00 |
July | 812.18 | 11.17 | 801.01 | 2296.68 | 8.39 | 0.00 | 0.00 | 0.00 |
August | 861.55 | 46.01 | 815.54 | 2167.75 | 32.95 | 0.00 | 0.00 | 0.00 |
September | 1154.98 | 299.78 | 855.20 | 2448.54 | 132.82 | 0.00 | 0.00 | 0.00 |
October | 1987.02 | 1109.54 | 877.48 | 3650.78 | 648.72 | 0.00 | 0.00 | 0.00 |
November | 2481.90 | 1640.48 | 841.42 | 4009.02 | 1168.05 | 0.00 | 0.00 | 0.00 |
December | 2215.03 | 1388.00 | 827.03 | 3189.09 | 1494.91 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1501.89 | 664.51 | 837.38 | 2851.35 | 612.07 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 778.63 | 11.17 | 765.34 | 2167.75 | 8.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2481.90 | 1640.48 | 940.82 | 4009.02 | 1494.91 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 636.76 | 247.80 | 388.96 | 767.86 | 1024.66 | 0.00 | 0.00 | 0.00 |
February | 728.15 | 268.34 | 459.81 | 998.69 | 841.67 | 0.00 | 0.00 | 0.00 |
March | 944.23 | 377.44 | 566.79 | 1545.39 | 543.44 | 0.00 | 0.00 | 0.00 |
April | 1147.70 | 538.23 | 609.47 | 2297.10 | 213.61 | 0.00 | 0.00 | 0.00 |
May | 1086.77 | 460.98 | 625.78 | 2530.62 | 42.12 | 0.00 | 0.00 | 0.00 |
June | 1020.76 | 396.49 | 624.27 | 2513.05 | 30.80 | 0.00 | 0.00 | 0.00 |
July | 757.46 | 147.33 | 610.13 | 1870.54 | 8.96 | 0.00 | 0.00 | 0.00 |
August | 695.65 | 123.64 | 572.01 | 1613.97 | 27.30 | 0.00 | 0.00 | 0.00 |
September | 764.70 | 224.49 | 540.20 | 1562.43 | 94.60 | 0.00 | 0.00 | 0.00 |
October | 795.93 | 316.94 | 478.99 | 1476.19 | 426.58 | 0.00 | 0.00 | 0.00 |
November | 720.05 | 306.88 | 413.17 | 1129.02 | 772.57 | 0.00 | 0.00 | 0.00 |
December | 616.15 | 234.95 | 381.20 | 768.01 | 1009.62 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 826.04 | 303.23 | 522.82 | 1591.13 | 417.75 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 616.15 | 123.64 | 381.20 | 767.86 | 8.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1147.70 | 538.23 | 625.78 | 2530.62 | 1024.66 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.244134E+09 | 0.00 | 0.244134E+09 | 0.126918E+09 | 0.984302E+09 |
February | 0.261485E+09 | 0.00 | 0.261485E+09 | 0.242004E+09 | 0.676404E+09 |
March | 0.348851E+09 | 0.00 | 0.348851E+09 | 0.528592E+09 | 0.426896E+09 |
April | 0.366321E+09 | 1242306.39 | 0.365078E+09 | 0.879178E+09 | 0.136363E+09 |
May | 0.419386E+09 | 11768647.88 | 0.407617E+09 | 0.127169E+10 | 21523355.43 |
June | 0.420126E+09 | 15561451.75 | 0.404565E+09 | 0.133338E+10 | 15642383.50 |
July | 0.428151E+09 | 6779998.49 | 0.421371E+09 | 0.122396E+10 | 3574180.66 |
August | 0.393055E+09 | 1224970.50 | 0.391830E+09 | 0.102320E+10 | 14170130.01 |
September | 0.338926E+09 | 23798.53 | 0.338902E+09 | 0.783434E+09 | 53934588.87 |
October | 0.303407E+09 | 0.00 | 0.303407E+09 | 0.585655E+09 | 0.323675E+09 |
November | 0.248699E+09 | 0.00 | 0.248699E+09 | 0.301912E+09 | 0.638189E+09 |
December | 0.238157E+09 | 0.00 | 0.238157E+09 | 0.140482E+09 | 0.960799E+09 |
Annual Sum or Average | 0.401070E+10 | 36601173.55 | 0.397410E+10 | 0.844040E+10 | 0.425547E+10 |
Minimum of Months | 0.238157E+09 | 0.00 | 0.238157E+09 | 0.126918E+09 | 3574180.66 |
Maximum of Months | 0.428151E+09 | 15561451.75 | 0.421371E+09 | 0.133338E+10 | 0.984302E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.244130E+09 | 0.00 | 0.244130E+09 | 0.126915E+09 | 0.984299E+09 |
February | 0.261481E+09 | 0.00 | 0.261481E+09 | 0.242000E+09 | 0.676402E+09 |
March | 0.348846E+09 | 0.00 | 0.348846E+09 | 0.528587E+09 | 0.426893E+09 |
April | 0.366316E+09 | 1242279.08 | 0.365074E+09 | 0.879174E+09 | 0.136360E+09 |
May | 0.419380E+09 | 11768389.16 | 0.407612E+09 | 0.127168E+10 | 21522604.71 |
June | 0.420121E+09 | 15561109.65 | 0.404560E+09 | 0.133338E+10 | 15642116.53 |
July | 0.428145E+09 | 6779849.44 | 0.421365E+09 | 0.122395E+10 | 3574029.43 |
August | 0.393049E+09 | 1224943.57 | 0.391824E+09 | 0.102319E+10 | 14169717.70 |
September | 0.338921E+09 | 23798.01 | 0.338897E+09 | 0.783428E+09 | 53933215.64 |
October | 0.303403E+09 | 0.00 | 0.303403E+09 | 0.585651E+09 | 0.323672E+09 |
November | 0.248696E+09 | 0.00 | 0.248696E+09 | 0.301909E+09 | 0.638186E+09 |
December | 0.238154E+09 | 0.00 | 0.238154E+09 | 0.140479E+09 | 0.960796E+09 |
Annual Sum or Average | 0.401064E+10 | 36600368.92 | 0.397404E+10 | 0.844034E+10 | 0.425545E+10 |
Minimum of Months | 0.238154E+09 | 0.00 | 0.238154E+09 | 0.126915E+09 | 3574029.43 |
Maximum of Months | 0.428145E+09 | 15561109.65 | 0.421365E+09 | 0.133338E+10 | 0.984299E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.244132E+09 | 0.00 | 0.244132E+09 | 0.126916E+09 | 0.984300E+09 |
February | 0.261483E+09 | 0.00 | 0.261483E+09 | 0.242001E+09 | 0.676403E+09 |
March | 0.348848E+09 | 0.00 | 0.348848E+09 | 0.528588E+09 | 0.426894E+09 |
April | 0.366318E+09 | 1242288.19 | 0.365075E+09 | 0.879175E+09 | 0.136361E+09 |
May | 0.419382E+09 | 11768475.40 | 0.407614E+09 | 0.127168E+10 | 21522854.95 |
June | 0.420122E+09 | 15561223.69 | 0.404561E+09 | 0.133338E+10 | 15642205.52 |
July | 0.428147E+09 | 6779899.12 | 0.421367E+09 | 0.122395E+10 | 3574079.84 |
August | 0.393051E+09 | 1224952.55 | 0.391826E+09 | 0.102319E+10 | 14169855.14 |
September | 0.338923E+09 | 23798.18 | 0.338899E+09 | 0.783430E+09 | 53933673.38 |
October | 0.303405E+09 | 0.00 | 0.303405E+09 | 0.585652E+09 | 0.323673E+09 |
November | 0.248697E+09 | 0.00 | 0.248697E+09 | 0.301910E+09 | 0.638187E+09 |
December | 0.238155E+09 | 0.00 | 0.238155E+09 | 0.140480E+09 | 0.960797E+09 |
Annual Sum or Average | 0.401066E+10 | 36600637.13 | 0.397406E+10 | 0.844036E+10 | 0.425546E+10 |
Minimum of Months | 0.238155E+09 | 0.00 | 0.238155E+09 | 0.126916E+09 | 3574079.84 |
Maximum of Months | 0.428147E+09 | 15561223.69 | 0.421367E+09 | 0.133338E+10 | 0.984300E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.244130E+09 | 0.00 | 0.244130E+09 | 0.126915E+09 | 0.984299E+09 |
February | 0.261481E+09 | 0.00 | 0.261481E+09 | 0.242000E+09 | 0.676402E+09 |
March | 0.348846E+09 | 0.00 | 0.348846E+09 | 0.528587E+09 | 0.426893E+09 |
April | 0.366316E+09 | 1242279.08 | 0.365074E+09 | 0.879174E+09 | 0.136360E+09 |
May | 0.419380E+09 | 11768389.16 | 0.407612E+09 | 0.127168E+10 | 21522604.71 |
June | 0.420121E+09 | 15561109.65 | 0.404560E+09 | 0.133338E+10 | 15642116.53 |
July | 0.428145E+09 | 6779849.44 | 0.421365E+09 | 0.122395E+10 | 3574029.43 |
August | 0.393049E+09 | 1224943.57 | 0.391824E+09 | 0.102319E+10 | 14169717.70 |
September | 0.338921E+09 | 23798.01 | 0.338897E+09 | 0.783428E+09 | 53933215.64 |
October | 0.303403E+09 | 0.00 | 0.303403E+09 | 0.585651E+09 | 0.323672E+09 |
November | 0.248696E+09 | 0.00 | 0.248696E+09 | 0.301909E+09 | 0.638186E+09 |
December | 0.238154E+09 | 0.00 | 0.238154E+09 | 0.140479E+09 | 0.960796E+09 |
Annual Sum or Average | 0.401064E+10 | 36600368.92 | 0.397404E+10 | 0.844034E+10 | 0.425545E+10 |
Minimum of Months | 0.238154E+09 | 0.00 | 0.238154E+09 | 0.126915E+09 | 3574029.43 |
Maximum of Months | 0.428145E+09 | 15561109.65 | 0.421365E+09 | 0.133338E+10 | 0.984299E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.244121E+09 | 0.00 | 0.244121E+09 | 0.126910E+09 | 0.984260E+09 |
February | 0.261472E+09 | 0.00 | 0.261472E+09 | 0.241991E+09 | 0.676375E+09 |
March | 0.348833E+09 | 0.00 | 0.348833E+09 | 0.528566E+09 | 0.426876E+09 |
April | 0.366302E+09 | 1242233.56 | 0.365060E+09 | 0.879139E+09 | 0.136355E+09 |
May | 0.419364E+09 | 11767957.96 | 0.407596E+09 | 0.127163E+10 | 21521862.37 |
June | 0.420105E+09 | 15560539.49 | 0.404544E+09 | 0.133332E+10 | 15641530.58 |
July | 0.428128E+09 | 6779601.02 | 0.421349E+09 | 0.122390E+10 | 3573910.58 |
August | 0.393034E+09 | 1224898.69 | 0.391809E+09 | 0.102315E+10 | 14169215.31 |
September | 0.338908E+09 | 23797.13 | 0.338884E+09 | 0.783397E+09 | 53931270.75 |
October | 0.303392E+09 | 0.00 | 0.303392E+09 | 0.585628E+09 | 0.323660E+09 |
November | 0.248686E+09 | 0.00 | 0.248686E+09 | 0.301897E+09 | 0.638161E+09 |
December | 0.238145E+09 | 0.00 | 0.238145E+09 | 0.140474E+09 | 0.960758E+09 |
Annual Sum or Average | 0.401049E+10 | 36599027.86 | 0.397389E+10 | 0.844001E+10 | 0.425528E+10 |
Minimum of Months | 0.238145E+09 | 0.00 | 0.238145E+09 | 0.126910E+09 | 3573910.58 |
Maximum of Months | 0.428128E+09 | 15560539.49 | 0.421349E+09 | 0.133332E+10 | 0.984260E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.581093E+09 | 0.233243E+09 | 0.347850E+09 | 0.581877E+09 | 0.989151E+09 |
February | 0.637636E+09 | 0.263246E+09 | 0.374390E+09 | 0.820570E+09 | 0.687455E+09 |
March | 0.861189E+09 | 0.355469E+09 | 0.505720E+09 | 0.140071E+10 | 0.438469E+09 |
April | 0.991541E+09 | 0.462307E+09 | 0.529234E+09 | 0.201766E+10 | 0.139374E+09 |
May | 0.100848E+10 | 0.447105E+09 | 0.561375E+09 | 0.236666E+10 | 22640970.60 |
June | 0.794294E+09 | 0.263546E+09 | 0.530748E+09 | 0.207264E+10 | 15132845.67 |
July | 0.689836E+09 | 0.145675E+09 | 0.544161E+09 | 0.176408E+10 | 2436678.38 |
August | 0.621571E+09 | 0.108168E+09 | 0.513403E+09 | 0.149615E+10 | 9732023.79 |
September | 0.642656E+09 | 0.179221E+09 | 0.463435E+09 | 0.134548E+10 | 55427648.53 |
October | 0.726423E+09 | 0.293427E+09 | 0.432996E+09 | 0.134084E+10 | 0.342519E+09 |
November | 0.623303E+09 | 0.267550E+09 | 0.355753E+09 | 0.919061E+09 | 0.651130E+09 |
December | 0.561610E+09 | 0.222513E+09 | 0.339097E+09 | 0.612496E+09 | 0.960659E+09 |
Annual Sum or Average | 0.873963E+10 | 0.324147E+10 | 0.549816E+10 | 0.167382E+11 | 0.431413E+10 |
Minimum of Months | 0.561610E+09 | 0.108168E+09 | 0.339097E+09 | 0.581877E+09 | 2436678.38 |
Maximum of Months | 0.100848E+10 | 0.462307E+09 | 0.561375E+09 | 0.236666E+10 | 0.989151E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.581093E+09 | 0.233243E+09 | 0.347850E+09 | 0.581877E+09 | 0.989151E+09 |
February | 0.637636E+09 | 0.263246E+09 | 0.374390E+09 | 0.820570E+09 | 0.687455E+09 |
March | 0.861189E+09 | 0.355469E+09 | 0.505720E+09 | 0.140071E+10 | 0.438469E+09 |
April | 0.991541E+09 | 0.462307E+09 | 0.529234E+09 | 0.201766E+10 | 0.139374E+09 |
May | 0.100848E+10 | 0.447105E+09 | 0.561375E+09 | 0.236666E+10 | 22640970.60 |
June | 0.794294E+09 | 0.263546E+09 | 0.530748E+09 | 0.207264E+10 | 15132845.67 |
July | 0.689836E+09 | 0.145675E+09 | 0.544161E+09 | 0.176408E+10 | 2436678.38 |
August | 0.621571E+09 | 0.108168E+09 | 0.513403E+09 | 0.149615E+10 | 9732023.79 |
September | 0.642656E+09 | 0.179221E+09 | 0.463435E+09 | 0.134548E+10 | 55427648.53 |
October | 0.726423E+09 | 0.293427E+09 | 0.432996E+09 | 0.134084E+10 | 0.342519E+09 |
November | 0.623303E+09 | 0.267550E+09 | 0.355753E+09 | 0.919061E+09 | 0.651130E+09 |
December | 0.561610E+09 | 0.222513E+09 | 0.339097E+09 | 0.612496E+09 | 0.960659E+09 |
Annual Sum or Average | 0.873963E+10 | 0.324147E+10 | 0.549816E+10 | 0.167382E+11 | 0.431413E+10 |
Minimum of Months | 0.561610E+09 | 0.108168E+09 | 0.339097E+09 | 0.581877E+09 | 2436678.38 |
Maximum of Months | 0.100848E+10 | 0.462307E+09 | 0.561375E+09 | 0.236666E+10 | 0.989151E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.581082E+09 | 0.233238E+09 | 0.347844E+09 | 0.581866E+09 | 0.989133E+09 |
February | 0.637624E+09 | 0.263241E+09 | 0.374383E+09 | 0.820555E+09 | 0.687442E+09 |
March | 0.861174E+09 | 0.355463E+09 | 0.505711E+09 | 0.140069E+10 | 0.438461E+09 |
April | 0.991523E+09 | 0.462299E+09 | 0.529224E+09 | 0.201762E+10 | 0.139372E+09 |
May | 0.100846E+10 | 0.447097E+09 | 0.561365E+09 | 0.236662E+10 | 22640556.90 |
June | 0.794279E+09 | 0.263541E+09 | 0.530738E+09 | 0.207260E+10 | 15132569.16 |
July | 0.689824E+09 | 0.145672E+09 | 0.544151E+09 | 0.176405E+10 | 2436633.85 |
August | 0.621560E+09 | 0.108166E+09 | 0.513394E+09 | 0.149612E+10 | 9731845.97 |
September | 0.642644E+09 | 0.179218E+09 | 0.463427E+09 | 0.134546E+10 | 55426635.74 |
October | 0.726410E+09 | 0.293422E+09 | 0.432988E+09 | 0.134082E+10 | 0.342513E+09 |
November | 0.623291E+09 | 0.267545E+09 | 0.355746E+09 | 0.919044E+09 | 0.651118E+09 |
December | 0.561600E+09 | 0.222509E+09 | 0.339091E+09 | 0.612485E+09 | 0.960642E+09 |
Annual Sum or Average | 0.873947E+10 | 0.324141E+10 | 0.549806E+10 | 0.167379E+11 | 0.431405E+10 |
Minimum of Months | 0.561600E+09 | 0.108166E+09 | 0.339091E+09 | 0.581866E+09 | 2436633.85 |
Maximum of Months | 0.100846E+10 | 0.462299E+09 | 0.561365E+09 | 0.236662E+10 | 0.989133E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.111030E+10 | 0.674644E+09 | 0.435654E+09 | 0.152019E+10 | 0.895426E+09 |
February | 0.953565E+09 | 0.529635E+09 | 0.423930E+09 | 0.142199E+10 | 0.651581E+09 |
March | 0.902678E+09 | 0.398704E+09 | 0.503975E+09 | 0.157621E+10 | 0.437818E+09 |
April | 0.613594E+09 | 0.173173E+09 | 0.440420E+09 | 0.141869E+10 | 0.148644E+09 |
May | 0.455965E+09 | 33753370.59 | 0.422212E+09 | 0.136180E+10 | 22011699.92 |
June | 0.403636E+09 | 6887849.73 | 0.396748E+09 | 0.130084E+10 | 15788643.85 |
July | 0.435064E+09 | 5983889.20 | 0.429080E+09 | 0.124253E+10 | 3348161.86 |
August | 0.461510E+09 | 24647909.05 | 0.436862E+09 | 0.116444E+10 | 14848119.75 |
September | 0.598732E+09 | 0.155401E+09 | 0.443331E+09 | 0.128512E+10 | 60778256.41 |
October | 0.106439E+10 | 0.594348E+09 | 0.470041E+09 | 0.197082E+10 | 0.344178E+09 |
November | 0.128659E+10 | 0.850407E+09 | 0.436184E+09 | 0.208348E+10 | 0.635948E+09 |
December | 0.118652E+10 | 0.743507E+09 | 0.443017E+09 | 0.168372E+10 | 0.891811E+09 |
Annual Sum or Average | 0.947255E+10 | 0.419109E+10 | 0.528145E+10 | 0.180298E+11 | 0.412218E+10 |
Minimum of Months | 0.403636E+09 | 5983889.20 | 0.396748E+09 | 0.116444E+10 | 3348161.86 |
Maximum of Months | 0.128659E+10 | 0.850407E+09 | 0.503975E+09 | 0.208348E+10 | 0.895426E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.111029E+10 | 0.674639E+09 | 0.435651E+09 | 0.152018E+10 | 0.895425E+09 |
February | 0.953558E+09 | 0.529631E+09 | 0.423927E+09 | 0.142198E+10 | 0.651581E+09 |
March | 0.902673E+09 | 0.398701E+09 | 0.503972E+09 | 0.157620E+10 | 0.437817E+09 |
April | 0.613590E+09 | 0.173172E+09 | 0.440418E+09 | 0.141868E+10 | 0.148644E+09 |
May | 0.455963E+09 | 33753123.25 | 0.422210E+09 | 0.136179E+10 | 22011446.13 |
June | 0.403635E+09 | 6887799.25 | 0.396747E+09 | 0.130084E+10 | 15788559.17 |
July | 0.435061E+09 | 5983845.35 | 0.429078E+09 | 0.124252E+10 | 3348117.42 |
August | 0.461507E+09 | 24647728.43 | 0.436859E+09 | 0.116444E+10 | 14847981.59 |
September | 0.598729E+09 | 0.155400E+09 | 0.443328E+09 | 0.128511E+10 | 60777770.87 |
October | 0.106438E+10 | 0.594344E+09 | 0.470039E+09 | 0.197081E+10 | 0.344177E+09 |
November | 0.128658E+10 | 0.850401E+09 | 0.436181E+09 | 0.208347E+10 | 0.635946E+09 |
December | 0.118652E+10 | 0.743502E+09 | 0.443014E+09 | 0.168371E+10 | 0.891810E+09 |
Annual Sum or Average | 0.947249E+10 | 0.419106E+10 | 0.528143E+10 | 0.180297E+11 | 0.412217E+10 |
Minimum of Months | 0.403635E+09 | 5983845.35 | 0.396747E+09 | 0.116444E+10 | 3348117.42 |
Maximum of Months | 0.128658E+10 | 0.850401E+09 | 0.503972E+09 | 0.208347E+10 | 0.895425E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.111030E+10 | 0.674644E+09 | 0.435654E+09 | 0.152019E+10 | 0.895426E+09 |
February | 0.953565E+09 | 0.529635E+09 | 0.423930E+09 | 0.142199E+10 | 0.651581E+09 |
March | 0.902678E+09 | 0.398704E+09 | 0.503975E+09 | 0.157621E+10 | 0.437818E+09 |
April | 0.613594E+09 | 0.173173E+09 | 0.440420E+09 | 0.141869E+10 | 0.148644E+09 |
May | 0.455965E+09 | 33753370.59 | 0.422212E+09 | 0.136180E+10 | 22011699.92 |
June | 0.403636E+09 | 6887849.73 | 0.396748E+09 | 0.130084E+10 | 15788643.85 |
July | 0.435064E+09 | 5983889.20 | 0.429080E+09 | 0.124253E+10 | 3348161.86 |
August | 0.461510E+09 | 24647909.05 | 0.436862E+09 | 0.116444E+10 | 14848119.75 |
September | 0.598732E+09 | 0.155401E+09 | 0.443331E+09 | 0.128512E+10 | 60778256.41 |
October | 0.106439E+10 | 0.594348E+09 | 0.470041E+09 | 0.197082E+10 | 0.344178E+09 |
November | 0.128659E+10 | 0.850407E+09 | 0.436184E+09 | 0.208348E+10 | 0.635948E+09 |
December | 0.118652E+10 | 0.743507E+09 | 0.443017E+09 | 0.168372E+10 | 0.891811E+09 |
Annual Sum or Average | 0.947255E+10 | 0.419109E+10 | 0.528145E+10 | 0.180298E+11 | 0.412218E+10 |
Minimum of Months | 0.403636E+09 | 5983889.20 | 0.396748E+09 | 0.116444E+10 | 3348161.86 |
Maximum of Months | 0.128659E+10 | 0.850407E+09 | 0.503975E+09 | 0.208348E+10 | 0.895426E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.111029E+10 | 0.674639E+09 | 0.435651E+09 | 0.152018E+10 | 0.895425E+09 |
February | 0.953558E+09 | 0.529631E+09 | 0.423927E+09 | 0.142198E+10 | 0.651581E+09 |
March | 0.902673E+09 | 0.398701E+09 | 0.503972E+09 | 0.157620E+10 | 0.437817E+09 |
April | 0.613590E+09 | 0.173172E+09 | 0.440418E+09 | 0.141868E+10 | 0.148644E+09 |
May | 0.455963E+09 | 33753123.25 | 0.422210E+09 | 0.136179E+10 | 22011446.13 |
June | 0.403635E+09 | 6887799.25 | 0.396747E+09 | 0.130084E+10 | 15788559.17 |
July | 0.435061E+09 | 5983845.35 | 0.429078E+09 | 0.124252E+10 | 3348117.42 |
August | 0.461507E+09 | 24647728.43 | 0.436859E+09 | 0.116444E+10 | 14847981.59 |
September | 0.598729E+09 | 0.155400E+09 | 0.443328E+09 | 0.128511E+10 | 60777770.87 |
October | 0.106438E+10 | 0.594344E+09 | 0.470039E+09 | 0.197081E+10 | 0.344177E+09 |
November | 0.128658E+10 | 0.850401E+09 | 0.436181E+09 | 0.208347E+10 | 0.635946E+09 |
December | 0.118652E+10 | 0.743502E+09 | 0.443014E+09 | 0.168371E+10 | 0.891810E+09 |
Annual Sum or Average | 0.947249E+10 | 0.419106E+10 | 0.528143E+10 | 0.180297E+11 | 0.412217E+10 |
Minimum of Months | 0.403635E+09 | 5983845.35 | 0.396747E+09 | 0.116444E+10 | 3348117.42 |
Maximum of Months | 0.128658E+10 | 0.850401E+09 | 0.503972E+09 | 0.208347E+10 | 0.895425E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.111025E+10 | 0.674614E+09 | 0.435635E+09 | 0.152012E+10 | 0.895389E+09 |
February | 0.953523E+09 | 0.529612E+09 | 0.423911E+09 | 0.142192E+10 | 0.651555E+09 |
March | 0.902639E+09 | 0.398686E+09 | 0.503953E+09 | 0.157615E+10 | 0.437800E+09 |
April | 0.613567E+09 | 0.173166E+09 | 0.440401E+09 | 0.141863E+10 | 0.148638E+09 |
May | 0.455946E+09 | 33751886.52 | 0.422194E+09 | 0.136174E+10 | 22010685.86 |
June | 0.403619E+09 | 6887546.88 | 0.396732E+09 | 0.130079E+10 | 15787965.16 |
July | 0.435045E+09 | 5983626.10 | 0.429061E+09 | 0.124247E+10 | 3348004.70 |
August | 0.461490E+09 | 24646825.33 | 0.436843E+09 | 0.116439E+10 | 14847452.23 |
September | 0.598706E+09 | 0.155394E+09 | 0.443312E+09 | 0.128506E+10 | 60775564.02 |
October | 0.106434E+10 | 0.594322E+09 | 0.470021E+09 | 0.197073E+10 | 0.344164E+09 |
November | 0.128653E+10 | 0.850370E+09 | 0.436165E+09 | 0.208339E+10 | 0.635921E+09 |
December | 0.118647E+10 | 0.743475E+09 | 0.442998E+09 | 0.168365E+10 | 0.891775E+09 |
Annual Sum or Average | 0.947214E+10 | 0.419091E+10 | 0.528123E+10 | 0.180291E+11 | 0.412201E+10 |
Minimum of Months | 0.403619E+09 | 5983626.10 | 0.396732E+09 | 0.116439E+10 | 3348004.70 |
Maximum of Months | 0.128653E+10 | 0.850370E+09 | 0.503953E+09 | 0.208339E+10 | 0.895389E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.568506E+09 | 0.221241E+09 | 0.347265E+09 | 0.625375E+09 | 0.114644E+10 |
February | 0.587189E+09 | 0.216395E+09 | 0.370794E+09 | 0.762529E+09 | 0.830604E+09 |
March | 0.843016E+09 | 0.336983E+09 | 0.506033E+09 | 0.135585E+10 | 0.565909E+09 |
April | 0.991624E+09 | 0.465034E+09 | 0.526590E+09 | 0.194996E+10 | 0.231836E+09 |
May | 0.970274E+09 | 0.411570E+09 | 0.558703E+09 | 0.225920E+10 | 40541581.02 |
June | 0.881948E+09 | 0.342572E+09 | 0.539376E+09 | 0.215291E+10 | 30673409.98 |
July | 0.676266E+09 | 0.131534E+09 | 0.544732E+09 | 0.162780E+10 | 14155394.26 |
August | 0.621079E+09 | 0.110385E+09 | 0.510694E+09 | 0.136872E+10 | 54286970.82 |
September | 0.660705E+09 | 0.193964E+09 | 0.466741E+09 | 0.134616E+10 | 92417919.92 |
October | 0.710616E+09 | 0.282966E+09 | 0.427650E+09 | 0.130142E+10 | 0.428254E+09 |
November | 0.622131E+09 | 0.265149E+09 | 0.356983E+09 | 0.931977E+09 | 0.806416E+09 |
December | 0.550107E+09 | 0.209768E+09 | 0.340339E+09 | 0.601462E+09 | 0.118701E+10 |
Annual Sum or Average | 0.868346E+10 | 0.318756E+10 | 0.549590E+10 | 0.162834E+11 | 0.542855E+10 |
Minimum of Months | 0.550107E+09 | 0.110385E+09 | 0.340339E+09 | 0.601462E+09 | 14155394.26 |
Maximum of Months | 0.991624E+09 | 0.465034E+09 | 0.558703E+09 | 0.225920E+10 | 0.118701E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.568506E+09 | 0.221241E+09 | 0.347265E+09 | 0.625375E+09 | 0.114644E+10 |
February | 0.587189E+09 | 0.216395E+09 | 0.370794E+09 | 0.762529E+09 | 0.830604E+09 |
March | 0.843016E+09 | 0.336983E+09 | 0.506033E+09 | 0.135585E+10 | 0.565909E+09 |
April | 0.991624E+09 | 0.465034E+09 | 0.526590E+09 | 0.194996E+10 | 0.231836E+09 |
May | 0.970274E+09 | 0.411570E+09 | 0.558703E+09 | 0.225920E+10 | 40541581.02 |
June | 0.881948E+09 | 0.342572E+09 | 0.539376E+09 | 0.215291E+10 | 30673409.98 |
July | 0.676266E+09 | 0.131534E+09 | 0.544732E+09 | 0.162780E+10 | 14155394.26 |
August | 0.621079E+09 | 0.110385E+09 | 0.510694E+09 | 0.136872E+10 | 54286970.82 |
September | 0.660705E+09 | 0.193964E+09 | 0.466741E+09 | 0.134616E+10 | 92417919.92 |
October | 0.710616E+09 | 0.282966E+09 | 0.427650E+09 | 0.130142E+10 | 0.428254E+09 |
November | 0.622131E+09 | 0.265149E+09 | 0.356983E+09 | 0.931977E+09 | 0.806416E+09 |
December | 0.550107E+09 | 0.209768E+09 | 0.340339E+09 | 0.601462E+09 | 0.118701E+10 |
Annual Sum or Average | 0.868346E+10 | 0.318756E+10 | 0.549590E+10 | 0.162834E+11 | 0.542855E+10 |
Minimum of Months | 0.550107E+09 | 0.110385E+09 | 0.340339E+09 | 0.601462E+09 | 14155394.26 |
Maximum of Months | 0.991624E+09 | 0.465034E+09 | 0.558703E+09 | 0.225920E+10 | 0.118701E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.568496E+09 | 0.221237E+09 | 0.347259E+09 | 0.625364E+09 | 0.114642E+10 |
February | 0.587178E+09 | 0.216391E+09 | 0.370787E+09 | 0.762515E+09 | 0.830589E+09 |
March | 0.843001E+09 | 0.336977E+09 | 0.506024E+09 | 0.135583E+10 | 0.565898E+09 |
April | 0.991605E+09 | 0.465025E+09 | 0.526580E+09 | 0.194993E+10 | 0.231831E+09 |
May | 0.970256E+09 | 0.411563E+09 | 0.558693E+09 | 0.225916E+10 | 40540840.23 |
June | 0.881932E+09 | 0.342566E+09 | 0.539366E+09 | 0.215287E+10 | 30672849.51 |
July | 0.676253E+09 | 0.131532E+09 | 0.544722E+09 | 0.162777E+10 | 14155135.61 |
August | 0.621068E+09 | 0.110383E+09 | 0.510685E+09 | 0.136870E+10 | 54285978.88 |
September | 0.660693E+09 | 0.193961E+09 | 0.466732E+09 | 0.134614E+10 | 92416231.25 |
October | 0.710603E+09 | 0.282961E+09 | 0.427642E+09 | 0.130140E+10 | 0.428246E+09 |
November | 0.622120E+09 | 0.265144E+09 | 0.356976E+09 | 0.931960E+09 | 0.806401E+09 |
December | 0.550097E+09 | 0.209764E+09 | 0.340333E+09 | 0.601451E+09 | 0.118699E+10 |
Annual Sum or Average | 0.868330E+10 | 0.318750E+10 | 0.549580E+10 | 0.162831E+11 | 0.542845E+10 |
Minimum of Months | 0.550097E+09 | 0.110383E+09 | 0.340333E+09 | 0.601451E+09 | 14155135.61 |
Maximum of Months | 0.991605E+09 | 0.465025E+09 | 0.558693E+09 | 0.225916E+10 | 0.118699E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.122067E+10 | 0.00 | 0.122067E+10 | 0.756676E+09 | 0.444286E+10 |
February | 0.130743E+10 | 0.00 | 0.130743E+10 | 0.130253E+10 | 0.310198E+10 |
March | 0.174425E+10 | 0.00 | 0.174425E+10 | 0.270227E+10 | 0.203953E+10 |
April | 0.183160E+10 | 6211571.55 | 0.182539E+10 | 0.450275E+10 | 0.663896E+09 |
May | 0.209692E+10 | 58843614.39 | 0.203808E+10 | 0.642238E+10 | 0.111234E+09 |
June | 0.210063E+10 | 77807754.61 | 0.202282E+10 | 0.673352E+10 | 84736153.23 |
July | 0.214076E+10 | 33900208.49 | 0.210686E+10 | 0.619321E+10 | 23045251.77 |
August | 0.196528E+10 | 6124891.54 | 0.195915E+10 | 0.523278E+10 | 74549790.00 |
September | 0.169463E+10 | 118993.41 | 0.169451E+10 | 0.394696E+10 | 0.281557E+09 |
October | 0.151703E+10 | 0.00 | 0.151703E+10 | 0.298614E+10 | 0.157665E+10 |
November | 0.124349E+10 | 0.00 | 0.124349E+10 | 0.160385E+10 | 0.295894E+10 |
December | 0.119078E+10 | 0.00 | 0.119078E+10 | 0.854502E+09 | 0.427481E+10 |
Annual Sum or Average | 0.200535E+11 | 0.183007E+09 | 0.198705E+11 | 0.432376E+11 | 0.196338E+11 |
Minimum of Months | 0.119078E+10 | 0.00 | 0.119078E+10 | 0.756676E+09 | 23045251.77 |
Maximum of Months | 0.214076E+10 | 77807754.61 | 0.210686E+10 | 0.673352E+10 | 0.444286E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.174326E+10 | 0.699721E+09 | 0.104354E+10 | 0.181095E+10 | 0.276542E+10 |
February | 0.191289E+10 | 0.789730E+09 | 0.112316E+10 | 0.248095E+10 | 0.197255E+10 |
March | 0.258354E+10 | 0.106640E+10 | 0.151715E+10 | 0.418135E+10 | 0.133369E+10 |
April | 0.297459E+10 | 0.138691E+10 | 0.158769E+10 | 0.602233E+10 | 0.468072E+09 |
May | 0.302541E+10 | 0.134130E+10 | 0.168411E+10 | 0.707583E+10 | 77815196.25 |
June | 0.238286E+10 | 0.790630E+09 | 0.159223E+10 | 0.619111E+10 | 57878419.62 |
July | 0.206949E+10 | 0.437021E+09 | 0.163247E+10 | 0.525505E+10 | 13610752.54 |
August | 0.186469E+10 | 0.324501E+09 | 0.154019E+10 | 0.445086E+10 | 51037486.80 |
September | 0.192795E+10 | 0.537657E+09 | 0.139029E+10 | 0.401435E+10 | 0.197736E+09 |
October | 0.217925E+10 | 0.880272E+09 | 0.129897E+10 | 0.400895E+10 | 0.105631E+10 |
November | 0.186989E+10 | 0.802641E+09 | 0.106725E+10 | 0.277171E+10 | 0.190486E+10 |
December | 0.168481E+10 | 0.667533E+09 | 0.101728E+10 | 0.190136E+10 | 0.271335E+10 |
Annual Sum or Average | 0.262186E+11 | 0.972431E+10 | 0.164943E+11 | 0.501648E+11 | 0.126123E+11 |
Minimum of Months | 0.168481E+10 | 0.324501E+09 | 0.101728E+10 | 0.181095E+10 | 13610752.54 |
Maximum of Months | 0.302541E+10 | 0.138691E+10 | 0.168411E+10 | 0.707583E+10 | 0.276542E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.555159E+10 | 0.337329E+10 | 0.217830E+10 | 0.755077E+10 | 0.441953E+10 |
February | 0.476791E+10 | 0.264823E+10 | 0.211968E+10 | 0.706774E+10 | 0.320457E+10 |
March | 0.451346E+10 | 0.199356E+10 | 0.251990E+10 | 0.785360E+10 | 0.218080E+10 |
April | 0.306800E+10 | 0.865885E+09 | 0.220212E+10 | 0.713294E+10 | 0.748010E+09 |
May | 0.227984E+10 | 0.168770E+09 | 0.211107E+10 | 0.686946E+10 | 0.111473E+09 |
June | 0.201820E+10 | 34439972.86 | 0.198376E+10 | 0.657707E+10 | 83646886.49 |
July | 0.217534E+10 | 29920075.17 | 0.214542E+10 | 0.629082E+10 | 20327321.27 |
August | 0.230758E+10 | 0.123242E+09 | 0.218434E+10 | 0.591654E+10 | 78061325.72 |
September | 0.299371E+10 | 0.777023E+09 | 0.221668E+10 | 0.641542E+10 | 0.327571E+09 |
October | 0.532204E+10 | 0.297180E+10 | 0.235023E+10 | 0.981759E+10 | 0.175096E+10 |
November | 0.643307E+10 | 0.425213E+10 | 0.218095E+10 | 0.103731E+11 | 0.315949E+10 |
December | 0.593273E+10 | 0.371762E+10 | 0.221512E+10 | 0.840450E+10 | 0.434705E+10 |
Annual Sum or Average | 0.473635E+11 | 0.209559E+11 | 0.264076E+11 | 0.902696E+11 | 0.204315E+11 |
Minimum of Months | 0.201820E+10 | 29920075.17 | 0.198376E+10 | 0.591654E+10 | 20327321.27 |
Maximum of Months | 0.643307E+10 | 0.425213E+10 | 0.251990E+10 | 0.103731E+11 | 0.441953E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.170550E+10 | 0.663716E+09 | 0.104178E+10 | 0.196771E+10 | 0.306039E+10 |
February | 0.176155E+10 | 0.649178E+09 | 0.111237E+10 | 0.237465E+10 | 0.218753E+10 |
March | 0.252902E+10 | 0.101094E+10 | 0.151808E+10 | 0.415297E+10 | 0.149540E+10 |
April | 0.297484E+10 | 0.139509E+10 | 0.157975E+10 | 0.600594E+10 | 0.548230E+09 |
May | 0.291079E+10 | 0.123470E+10 | 0.167609E+10 | 0.685456E+10 | 0.104761E+09 |
June | 0.264582E+10 | 0.102771E+10 | 0.161811E+10 | 0.659542E+10 | 74392060.00 |
July | 0.202878E+10 | 0.394598E+09 | 0.163418E+10 | 0.509057E+10 | 22386456.82 |
August | 0.186322E+10 | 0.331151E+09 | 0.153207E+10 | 0.438375E+10 | 67393117.14 |
September | 0.198210E+10 | 0.581887E+09 | 0.140021E+10 | 0.408930E+10 | 0.238757E+09 |
October | 0.213182E+10 | 0.848889E+09 | 0.128294E+10 | 0.397174E+10 | 0.116320E+10 |
November | 0.186638E+10 | 0.795438E+09 | 0.107094E+10 | 0.290168E+10 | 0.211469E+10 |
December | 0.165030E+10 | 0.629299E+09 | 0.102101E+10 | 0.197452E+10 | 0.296428E+10 |
Annual Sum or Average | 0.260501E+11 | 0.956259E+10 | 0.164875E+11 | 0.503628E+11 | 0.140414E+11 |
Minimum of Months | 0.165030E+10 | 0.331151E+09 | 0.102101E+10 | 0.196771E+10 | 22386456.82 |
Maximum of Months | 0.297484E+10 | 0.139509E+10 | 0.167609E+10 | 0.685456E+10 | 0.306039E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.122067E+10 | 0.00 | 0.122067E+10 | 0.926004E+09 | 0.385822E+10 |
February | 0.130743E+10 | 0.00 | 0.130743E+10 | 0.139731E+10 | 0.282356E+10 |
March | 0.174425E+10 | 0.00 | 0.174425E+10 | 0.270144E+10 | 0.196029E+10 |
April | 0.183160E+10 | 6211571.55 | 0.182539E+10 | 0.442581E+10 | 0.670970E+09 |
May | 0.209692E+10 | 58843614.39 | 0.203808E+10 | 0.629584E+10 | 0.125302E+09 |
June | 0.210063E+10 | 77807754.61 | 0.202282E+10 | 0.659860E+10 | 95200721.54 |
July | 0.214076E+10 | 33900208.49 | 0.210686E+10 | 0.605485E+10 | 25632722.24 |
August | 0.196528E+10 | 6124891.54 | 0.195915E+10 | 0.512401E+10 | 84073321.09 |
September | 0.169463E+10 | 118993.41 | 0.169451E+10 | 0.388441E+10 | 0.293305E+09 |
October | 0.151703E+10 | 0.00 | 0.151703E+10 | 0.296822E+10 | 0.153517E+10 |
November | 0.124349E+10 | 0.00 | 0.124349E+10 | 0.167001E+10 | 0.274700E+10 |
December | 0.119078E+10 | 0.00 | 0.119078E+10 | 0.101430E+10 | 0.379217E+10 |
Annual Sum or Average | 0.200535E+11 | 0.183007E+09 | 0.198705E+11 | 0.430608E+11 | 0.180109E+11 |
Minimum of Months | 0.119078E+10 | 0.00 | 0.119078E+10 | 0.926004E+09 | 25632722.24 |
Maximum of Months | 0.214076E+10 | 77807754.61 | 0.210686E+10 | 0.659860E+10 | 0.385822E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.174326E+10 | 0.699721E+09 | 0.104354E+10 | 0.196537E+10 | 0.244085E+10 |
February | 0.191289E+10 | 0.789730E+09 | 0.112316E+10 | 0.254442E+10 | 0.183518E+10 |
March | 0.258354E+10 | 0.106640E+10 | 0.151715E+10 | 0.417223E+10 | 0.130370E+10 |
April | 0.297459E+10 | 0.138691E+10 | 0.158769E+10 | 0.596414E+10 | 0.479036E+09 |
May | 0.302541E+10 | 0.134130E+10 | 0.168411E+10 | 0.698338E+10 | 88544188.33 |
June | 0.238286E+10 | 0.790630E+09 | 0.159223E+10 | 0.609433E+10 | 65594359.36 |
July | 0.206949E+10 | 0.437021E+09 | 0.163247E+10 | 0.515764E+10 | 15020457.82 |
August | 0.186469E+10 | 0.324501E+09 | 0.154019E+10 | 0.437436E+10 | 57794006.36 |
September | 0.192795E+10 | 0.537657E+09 | 0.139029E+10 | 0.396885E+10 | 0.207012E+09 |
October | 0.217925E+10 | 0.880272E+09 | 0.129897E+10 | 0.399114E+10 | 0.104270E+10 |
November | 0.186989E+10 | 0.802641E+09 | 0.106725E+10 | 0.281147E+10 | 0.180485E+10 |
December | 0.168481E+10 | 0.667533E+09 | 0.101728E+10 | 0.203102E+10 | 0.245871E+10 |
Annual Sum or Average | 0.262186E+11 | 0.972431E+10 | 0.164943E+11 | 0.500584E+11 | 0.117990E+11 |
Minimum of Months | 0.168481E+10 | 0.324501E+09 | 0.101728E+10 | 0.196537E+10 | 15020457.82 |
Maximum of Months | 0.302541E+10 | 0.138691E+10 | 0.168411E+10 | 0.698338E+10 | 0.245871E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.555159E+10 | 0.337329E+10 | 0.217830E+10 | 0.771902E+10 | 0.396369E+10 |
February | 0.476791E+10 | 0.264823E+10 | 0.211968E+10 | 0.712555E+10 | 0.300079E+10 |
March | 0.451346E+10 | 0.199356E+10 | 0.251990E+10 | 0.782744E+10 | 0.213106E+10 |
April | 0.306800E+10 | 0.865885E+09 | 0.220212E+10 | 0.704982E+10 | 0.762537E+09 |
May | 0.227984E+10 | 0.168770E+09 | 0.211107E+10 | 0.674202E+10 | 0.125578E+09 |
June | 0.201820E+10 | 34439972.86 | 0.198376E+10 | 0.644101E+10 | 94630488.00 |
July | 0.217534E+10 | 29920075.17 | 0.214542E+10 | 0.615142E+10 | 22469016.34 |
August | 0.230758E+10 | 0.123242E+09 | 0.218434E+10 | 0.580611E+10 | 88243698.41 |
September | 0.299371E+10 | 0.777023E+09 | 0.221668E+10 | 0.634662E+10 | 0.344265E+09 |
October | 0.532204E+10 | 0.297180E+10 | 0.235023E+10 | 0.977826E+10 | 0.173753E+10 |
November | 0.643307E+10 | 0.425213E+10 | 0.218095E+10 | 0.103914E+11 | 0.302760E+10 |
December | 0.593273E+10 | 0.371762E+10 | 0.221512E+10 | 0.854166E+10 | 0.400397E+10 |
Annual Sum or Average | 0.473635E+11 | 0.209559E+11 | 0.264076E+11 | 0.899203E+11 | 0.193024E+11 |
Minimum of Months | 0.201820E+10 | 29920075.17 | 0.198376E+10 | 0.580611E+10 | 22469016.34 |
Maximum of Months | 0.643307E+10 | 0.425213E+10 | 0.251990E+10 | 0.103914E+11 | 0.400397E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.170550E+10 | 0.663716E+09 | 0.104178E+10 | 0.205664E+10 | 0.274444E+10 |
February | 0.176155E+10 | 0.649178E+09 | 0.111237E+10 | 0.241604E+10 | 0.203617E+10 |
March | 0.252902E+10 | 0.101094E+10 | 0.151808E+10 | 0.413917E+10 | 0.145554E+10 |
April | 0.297484E+10 | 0.139509E+10 | 0.157975E+10 | 0.595408E+10 | 0.553672E+09 |
May | 0.291079E+10 | 0.123470E+10 | 0.167609E+10 | 0.677802E+10 | 0.112825E+09 |
June | 0.264582E+10 | 0.102771E+10 | 0.161811E+10 | 0.651382E+10 | 79833431.80 |
July | 0.202878E+10 | 0.394598E+09 | 0.163418E+10 | 0.501006E+10 | 24005839.07 |
August | 0.186322E+10 | 0.331151E+09 | 0.153207E+10 | 0.432287E+10 | 73117717.19 |
September | 0.198210E+10 | 0.581887E+09 | 0.140021E+10 | 0.404981E+10 | 0.245201E+09 |
October | 0.213182E+10 | 0.848889E+09 | 0.128294E+10 | 0.395383E+10 | 0.114256E+10 |
November | 0.186638E+10 | 0.795438E+09 | 0.107094E+10 | 0.292642E+10 | 0.200251E+10 |
December | 0.165030E+10 | 0.629299E+09 | 0.102101E+10 | 0.205705E+10 | 0.270416E+10 |
Annual Sum or Average | 0.260501E+11 | 0.956259E+10 | 0.164875E+11 | 0.501778E+11 | 0.131740E+11 |
Minimum of Months | 0.165030E+10 | 0.331151E+09 | 0.102101E+10 | 0.205664E+10 | 24005839.07 |
Maximum of Months | 0.297484E+10 | 0.139509E+10 | 0.167609E+10 | 0.677802E+10 | 0.274444E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 236.92 | 1837.46 | 455.74 | 0.00 | 455.74 | 0.00 | 0.00 |
February | 500.16 | 1397.98 | 540.43 | 0.00 | 540.43 | 0.00 | 0.00 |
March | 986.75 | 796.91 | 651.22 | 0.00 | 651.22 | 0.00 | 0.00 |
April | 1695.93 | 263.04 | 706.63 | 2.40 | 704.23 | 0.00 | 0.00 |
May | 2373.94 | 40.18 | 782.89 | 21.97 | 760.92 | 0.00 | 0.00 |
June | 2572.08 | 30.17 | 810.41 | 30.02 | 780.40 | 0.00 | 0.00 |
July | 2284.84 | 6.67 | 799.25 | 12.66 | 786.60 | 0.00 | 0.00 |
August | 1910.07 | 26.45 | 733.74 | 2.29 | 731.45 | 0.00 | 0.00 |
September | 1511.23 | 104.04 | 653.78 | 0.05 | 653.73 | 0.00 | 0.00 |
October | 1093.28 | 604.22 | 566.39 | 0.00 | 566.39 | 0.00 | 0.00 |
November | 582.38 | 1231.06 | 479.74 | 0.00 | 479.74 | 0.00 | 0.00 |
December | 262.24 | 1793.59 | 444.58 | 0.00 | 444.58 | 0.00 | 0.00 |
Annual Sum or Average | 1338.20 | 674.69 | 635.88 | 5.80 | 630.08 | 0.00 | 0.00 |
Minimum of Months | 236.92 | 6.67 | 444.58 | 0.00 | 444.58 | 0.00 | 0.00 |
Maximum of Months | 2572.08 | 1837.46 | 810.41 | 30.02 | 786.60 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 651.74 | 1107.91 | 650.86 | 261.25 | 389.61 | 0.00 | 0.00 |
February | 1017.57 | 852.49 | 790.71 | 326.44 | 464.27 | 0.00 | 0.00 |
March | 1568.89 | 491.11 | 964.59 | 398.15 | 566.44 | 0.00 | 0.00 |
April | 2335.24 | 161.31 | 1147.61 | 535.07 | 612.54 | 0.00 | 0.00 |
May | 2650.82 | 25.36 | 1129.56 | 500.79 | 628.78 | 0.00 | 0.00 |
June | 2398.87 | 17.51 | 919.32 | 305.03 | 614.29 | 0.00 | 0.00 |
July | 1975.89 | 2.73 | 772.66 | 163.17 | 609.50 | 0.00 | 0.00 |
August | 1675.78 | 10.90 | 696.20 | 121.16 | 575.04 | 0.00 | 0.00 |
September | 1557.26 | 64.15 | 743.81 | 207.43 | 536.38 | 0.00 | 0.00 |
October | 1501.83 | 383.64 | 813.64 | 328.66 | 484.98 | 0.00 | 0.00 |
November | 1063.72 | 753.62 | 721.41 | 309.66 | 411.75 | 0.00 | 0.00 |
December | 686.04 | 1076.00 | 629.04 | 249.23 | 379.81 | 0.00 | 0.00 |
Annual Sum or Average | 1592.29 | 410.40 | 831.39 | 308.36 | 523.03 | 0.00 | 0.00 |
Minimum of Months | 651.74 | 2.73 | 629.04 | 121.16 | 379.81 | 0.00 | 0.00 |
Maximum of Months | 2650.82 | 1107.91 | 1147.61 | 535.07 | 628.78 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2837.84 | 1671.55 | 2072.66 | 1259.40 | 813.26 | 0.00 | 0.00 |
February | 2938.93 | 1346.68 | 1970.80 | 1094.64 | 876.17 | 0.00 | 0.00 |
March | 2942.42 | 817.30 | 1685.09 | 744.29 | 940.80 | 0.00 | 0.00 |
April | 2736.64 | 286.73 | 1183.62 | 334.05 | 849.57 | 0.00 | 0.00 |
May | 2542.16 | 41.09 | 851.18 | 63.01 | 788.17 | 0.00 | 0.00 |
June | 2509.31 | 30.46 | 778.61 | 13.29 | 765.32 | 0.00 | 0.00 |
July | 2319.51 | 6.25 | 812.16 | 11.17 | 800.99 | 0.00 | 0.00 |
August | 2173.75 | 27.72 | 861.53 | 46.01 | 815.52 | 0.00 | 0.00 |
September | 2478.98 | 117.24 | 1154.95 | 299.77 | 855.18 | 0.00 | 0.00 |
October | 3679.06 | 642.50 | 1986.97 | 1109.51 | 877.46 | 0.00 | 0.00 |
November | 4019.01 | 1226.74 | 2481.82 | 1640.43 | 841.39 | 0.00 | 0.00 |
December | 3143.11 | 1664.81 | 2214.96 | 1387.95 | 827.01 | 0.00 | 0.00 |
Annual Sum or Average | 2858.58 | 653.56 | 1501.85 | 664.49 | 837.36 | 0.00 | 0.00 |
Minimum of Months | 2173.75 | 6.25 | 778.61 | 11.17 | 765.32 | 0.00 | 0.00 |
Maximum of Months | 4019.01 | 1671.55 | 2481.82 | 1640.43 | 940.80 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 700.46 | 1284.09 | 636.76 | 247.80 | 388.96 | 0.00 | 0.00 |
February | 945.59 | 1030.01 | 728.16 | 268.35 | 459.81 | 0.00 | 0.00 |
March | 1518.64 | 633.85 | 944.23 | 377.44 | 566.79 | 0.00 | 0.00 |
April | 2256.89 | 268.33 | 1147.71 | 538.23 | 609.48 | 0.00 | 0.00 |
May | 2530.45 | 45.41 | 1086.77 | 460.99 | 625.78 | 0.00 | 0.00 |
June | 2491.78 | 35.50 | 1020.77 | 396.49 | 624.27 | 0.00 | 0.00 |
July | 1823.24 | 15.85 | 757.46 | 147.33 | 610.13 | 0.00 | 0.00 |
August | 1533.06 | 60.80 | 695.65 | 123.64 | 572.01 | 0.00 | 0.00 |
September | 1558.05 | 106.96 | 764.70 | 224.49 | 540.21 | 0.00 | 0.00 |
October | 1457.68 | 479.67 | 795.94 | 316.94 | 479.00 | 0.00 | 0.00 |
November | 1078.67 | 933.35 | 720.06 | 306.88 | 413.17 | 0.00 | 0.00 |
December | 673.68 | 1329.53 | 616.16 | 234.95 | 381.20 | 0.00 | 0.00 |
Annual Sum or Average | 1549.02 | 516.41 | 826.05 | 303.23 | 522.82 | 0.00 | 0.00 |
Minimum of Months | 673.68 | 15.85 | 616.16 | 123.64 | 381.20 | 0.00 | 0.00 |
Maximum of Months | 2530.45 | 1329.53 | 1147.71 | 538.23 | 625.78 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 282.51 | 1658.77 | 455.75 | 0.00 | 455.75 | 0.00 | 0.00 |
February | 538.41 | 1282.23 | 540.44 | 0.00 | 540.44 | 0.00 | 0.00 |
March | 1008.91 | 761.47 | 651.23 | 0.00 | 651.23 | 0.00 | 0.00 |
April | 1737.17 | 256.13 | 706.64 | 2.40 | 704.24 | 0.00 | 0.00 |
May | 2397.84 | 41.53 | 782.90 | 21.97 | 760.93 | 0.00 | 0.00 |
June | 2597.81 | 32.69 | 810.43 | 30.02 | 780.41 | 0.00 | 0.00 |
July | 2312.28 | 8.60 | 799.27 | 12.66 | 786.61 | 0.00 | 0.00 |
August | 1953.70 | 27.83 | 733.75 | 2.29 | 731.46 | 0.00 | 0.00 |
September | 1522.75 | 108.63 | 653.79 | 0.05 | 653.75 | 0.00 | 0.00 |
October | 1114.90 | 588.65 | 566.40 | 0.00 | 566.40 | 0.00 | 0.00 |
November | 618.77 | 1141.57 | 479.74 | 0.00 | 479.74 | 0.00 | 0.00 |
December | 319.03 | 1596.03 | 444.59 | 0.00 | 444.59 | 0.00 | 0.00 |
Annual Sum or Average | 1371.05 | 622.58 | 635.89 | 5.80 | 630.09 | 0.00 | 0.00 |
Minimum of Months | 282.51 | 8.60 | 444.59 | 0.00 | 444.59 | 0.00 | 0.00 |
Maximum of Months | 2597.81 | 1658.77 | 810.43 | 30.02 | 786.61 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 676.13 | 1032.49 | 650.86 | 261.25 | 389.61 | 0.00 | 0.00 |
February | 1025.52 | 815.37 | 790.71 | 326.44 | 464.27 | 0.00 | 0.00 |
March | 1561.14 | 497.94 | 964.58 | 398.15 | 566.44 | 0.00 | 0.00 |
April | 2323.43 | 180.58 | 1147.61 | 535.07 | 612.53 | 0.00 | 0.00 |
May | 2641.81 | 29.05 | 1129.56 | 500.78 | 628.77 | 0.00 | 0.00 |
June | 2388.54 | 22.33 | 919.31 | 305.03 | 614.29 | 0.00 | 0.00 |
July | 1962.01 | 5.08 | 772.66 | 163.16 | 609.49 | 0.00 | 0.00 |
August | 1661.76 | 19.06 | 696.20 | 121.15 | 575.04 | 0.00 | 0.00 |
September | 1548.74 | 76.29 | 743.81 | 207.43 | 536.38 | 0.00 | 0.00 |
October | 1496.77 | 394.38 | 813.64 | 328.66 | 484.98 | 0.00 | 0.00 |
November | 1069.33 | 734.90 | 721.41 | 309.66 | 411.75 | 0.00 | 0.00 |
December | 709.89 | 1013.05 | 629.04 | 249.23 | 379.81 | 0.00 | 0.00 |
Annual Sum or Average | 1590.71 | 399.93 | 831.39 | 308.36 | 523.03 | 0.00 | 0.00 |
Minimum of Months | 676.13 | 5.08 | 629.04 | 121.15 | 379.81 | 0.00 | 0.00 |
Maximum of Months | 2641.81 | 1032.49 | 1147.61 | 535.07 | 628.77 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2819.13 | 1650.06 | 2072.73 | 1259.44 | 813.28 | 0.00 | 0.00 |
February | 2921.52 | 1324.64 | 1970.86 | 1094.67 | 876.19 | 0.00 | 0.00 |
March | 2932.20 | 814.22 | 1685.13 | 744.31 | 940.82 | 0.00 | 0.00 |
April | 2751.91 | 288.58 | 1183.64 | 334.06 | 849.58 | 0.00 | 0.00 |
May | 2564.76 | 41.62 | 851.20 | 63.01 | 788.18 | 0.00 | 0.00 |
June | 2537.45 | 32.27 | 778.63 | 13.29 | 765.34 | 0.00 | 0.00 |
July | 2348.72 | 7.59 | 812.18 | 11.17 | 801.01 | 0.00 | 0.00 |
August | 2208.98 | 29.14 | 861.55 | 46.01 | 815.54 | 0.00 | 0.00 |
September | 2475.08 | 126.38 | 1154.98 | 299.78 | 855.20 | 0.00 | 0.00 |
October | 3665.47 | 653.74 | 1987.02 | 1109.54 | 877.48 | 0.00 | 0.00 |
November | 4001.99 | 1218.94 | 2481.90 | 1640.48 | 841.42 | 0.00 | 0.00 |
December | 3137.88 | 1623.00 | 2215.03 | 1388.00 | 827.03 | 0.00 | 0.00 |
Annual Sum or Average | 2862.43 | 647.88 | 1501.89 | 664.51 | 837.38 | 0.00 | 0.00 |
Minimum of Months | 2208.98 | 7.59 | 778.63 | 11.17 | 765.34 | 0.00 | 0.00 |
Maximum of Months | 4001.99 | 1650.06 | 2481.90 | 1640.48 | 940.82 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 734.66 | 1142.62 | 636.76 | 247.80 | 388.96 | 0.00 | 0.00 |
February | 981.58 | 904.24 | 728.15 | 268.34 | 459.81 | 0.00 | 0.00 |
March | 1550.54 | 558.32 | 944.23 | 377.44 | 566.79 | 0.00 | 0.00 |
April | 2317.11 | 211.51 | 1147.70 | 538.23 | 609.47 | 0.00 | 0.00 |
May | 2559.20 | 39.11 | 1086.77 | 460.98 | 625.78 | 0.00 | 0.00 |
June | 2544.53 | 28.70 | 1020.76 | 396.49 | 624.27 | 0.00 | 0.00 |
July | 1900.60 | 8.36 | 757.46 | 147.33 | 610.13 | 0.00 | 0.00 |
August | 1636.70 | 25.16 | 695.65 | 123.64 | 572.01 | 0.00 | 0.00 |
September | 1577.66 | 92.11 | 764.70 | 224.49 | 540.20 | 0.00 | 0.00 |
October | 1482.88 | 434.29 | 795.93 | 316.94 | 478.99 | 0.00 | 0.00 |
November | 1119.48 | 815.85 | 720.05 | 306.88 | 413.17 | 0.00 | 0.00 |
December | 737.20 | 1106.73 | 616.15 | 234.95 | 381.20 | 0.00 | 0.00 |
Annual Sum or Average | 1596.99 | 445.25 | 826.04 | 303.23 | 522.82 | 0.00 | 0.00 |
Minimum of Months | 734.66 | 8.36 | 616.15 | 123.64 | 381.20 | 0.00 | 0.00 |
Maximum of Months | 2559.20 | 1142.62 | 1147.70 | 538.23 | 625.78 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 345.73 | 1440.50 | 455.75 | 0.00 | 455.75 | 0.00 | 0.00 |
February | 577.59 | 1167.14 | 540.44 | 0.00 | 540.44 | 0.00 | 0.00 |
March | 1008.60 | 731.89 | 651.23 | 0.00 | 651.23 | 0.00 | 0.00 |
April | 1707.49 | 258.86 | 706.64 | 2.40 | 704.24 | 0.00 | 0.00 |
May | 2350.60 | 46.78 | 782.90 | 21.97 | 760.93 | 0.00 | 0.00 |
June | 2545.76 | 36.73 | 810.43 | 30.02 | 780.41 | 0.00 | 0.00 |
July | 2260.62 | 9.57 | 799.27 | 12.66 | 786.61 | 0.00 | 0.00 |
August | 1913.09 | 31.39 | 733.75 | 2.29 | 731.46 | 0.00 | 0.00 |
September | 1498.61 | 113.16 | 653.79 | 0.05 | 653.75 | 0.00 | 0.00 |
October | 1108.21 | 573.17 | 566.40 | 0.00 | 566.40 | 0.00 | 0.00 |
November | 644.29 | 1059.80 | 479.74 | 0.00 | 479.74 | 0.00 | 0.00 |
December | 378.69 | 1415.83 | 444.59 | 0.00 | 444.59 | 0.00 | 0.00 |
Annual Sum or Average | 1365.45 | 571.12 | 635.89 | 5.80 | 630.09 | 0.00 | 0.00 |
Minimum of Months | 345.73 | 9.57 | 444.59 | 0.00 | 444.59 | 0.00 | 0.00 |
Maximum of Months | 2545.76 | 1440.50 | 810.43 | 30.02 | 786.61 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 733.79 | 911.31 | 650.86 | 261.25 | 389.61 | 0.00 | 0.00 |
February | 1051.76 | 758.59 | 790.71 | 326.44 | 464.27 | 0.00 | 0.00 |
March | 1557.73 | 486.74 | 964.58 | 398.15 | 566.44 | 0.00 | 0.00 |
April | 2300.98 | 184.81 | 1147.61 | 535.07 | 612.53 | 0.00 | 0.00 |
May | 2607.29 | 33.06 | 1129.56 | 500.78 | 628.77 | 0.00 | 0.00 |
June | 2351.21 | 25.31 | 919.31 | 305.03 | 614.29 | 0.00 | 0.00 |
July | 1925.64 | 5.61 | 772.66 | 163.16 | 609.49 | 0.00 | 0.00 |
August | 1633.20 | 21.58 | 696.20 | 121.15 | 575.04 | 0.00 | 0.00 |
September | 1531.19 | 79.87 | 743.81 | 207.43 | 536.38 | 0.00 | 0.00 |
October | 1490.12 | 389.30 | 813.64 | 328.66 | 484.98 | 0.00 | 0.00 |
November | 1084.67 | 696.32 | 721.41 | 309.66 | 411.75 | 0.00 | 0.00 |
December | 758.30 | 917.98 | 629.04 | 249.23 | 379.81 | 0.00 | 0.00 |
Annual Sum or Average | 1587.34 | 374.14 | 831.39 | 308.36 | 523.03 | 0.00 | 0.00 |
Minimum of Months | 733.79 | 5.61 | 629.04 | 121.15 | 379.81 | 0.00 | 0.00 |
Maximum of Months | 2607.29 | 917.98 | 1147.61 | 535.07 | 628.77 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2881.95 | 1479.87 | 2072.73 | 1259.44 | 813.28 | 0.00 | 0.00 |
February | 2945.42 | 1240.41 | 1970.86 | 1094.67 | 876.19 | 0.00 | 0.00 |
March | 2922.43 | 795.65 | 1685.13 | 744.31 | 940.82 | 0.00 | 0.00 |
April | 2719.84 | 294.19 | 1183.64 | 334.06 | 849.58 | 0.00 | 0.00 |
May | 2517.18 | 46.89 | 851.20 | 63.01 | 788.18 | 0.00 | 0.00 |
June | 2484.96 | 36.51 | 778.63 | 13.29 | 765.34 | 0.00 | 0.00 |
July | 2296.68 | 8.39 | 812.18 | 11.17 | 801.01 | 0.00 | 0.00 |
August | 2167.75 | 32.95 | 861.55 | 46.01 | 815.54 | 0.00 | 0.00 |
September | 2448.54 | 132.82 | 1154.98 | 299.78 | 855.20 | 0.00 | 0.00 |
October | 3650.78 | 648.72 | 1987.02 | 1109.54 | 877.48 | 0.00 | 0.00 |
November | 4009.02 | 1168.05 | 2481.90 | 1640.48 | 841.42 | 0.00 | 0.00 |
December | 3189.09 | 1494.91 | 2215.03 | 1388.00 | 827.03 | 0.00 | 0.00 |
Annual Sum or Average | 2851.35 | 612.07 | 1501.89 | 664.51 | 837.38 | 0.00 | 0.00 |
Minimum of Months | 2167.75 | 8.39 | 778.63 | 11.17 | 765.34 | 0.00 | 0.00 |
Maximum of Months | 4009.02 | 1494.91 | 2481.90 | 1640.48 | 940.82 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 767.86 | 1024.66 | 636.76 | 247.80 | 388.96 | 0.00 | 0.00 |
February | 998.69 | 841.67 | 728.15 | 268.34 | 459.81 | 0.00 | 0.00 |
March | 1545.39 | 543.44 | 944.23 | 377.44 | 566.79 | 0.00 | 0.00 |
April | 2297.10 | 213.61 | 1147.70 | 538.23 | 609.47 | 0.00 | 0.00 |
May | 2530.62 | 42.12 | 1086.77 | 460.98 | 625.78 | 0.00 | 0.00 |
June | 2513.05 | 30.80 | 1020.76 | 396.49 | 624.27 | 0.00 | 0.00 |
July | 1870.54 | 8.96 | 757.46 | 147.33 | 610.13 | 0.00 | 0.00 |
August | 1613.97 | 27.30 | 695.65 | 123.64 | 572.01 | 0.00 | 0.00 |
September | 1562.43 | 94.60 | 764.70 | 224.49 | 540.20 | 0.00 | 0.00 |
October | 1476.19 | 426.58 | 795.93 | 316.94 | 478.99 | 0.00 | 0.00 |
November | 1129.02 | 772.57 | 720.05 | 306.88 | 413.17 | 0.00 | 0.00 |
December | 768.01 | 1009.62 | 616.15 | 234.95 | 381.20 | 0.00 | 0.00 |
Annual Sum or Average | 1591.13 | 417.75 | 826.04 | 303.23 | 522.82 | 0.00 | 0.00 |
Minimum of Months | 767.86 | 8.96 | 616.15 | 123.64 | 381.20 | 0.00 | 0.00 |
Maximum of Months | 2530.62 | 1024.66 | 1147.70 | 538.23 | 625.78 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.634572E+09 | 0.492146E+10 | 0.122065E+10 | 0.00 | 0.122065E+10 | 0.00 | 0.00 |
February | 0.121000E+10 | 0.338199E+10 | 0.130740E+10 | 0.00 | 0.130740E+10 | 0.00 | 0.00 |
March | 0.264292E+10 | 0.213445E+10 | 0.174422E+10 | 0.00 | 0.174422E+10 | 0.00 | 0.00 |
April | 0.439584E+10 | 0.681800E+09 | 0.183157E+10 | 6211386.31 | 0.182536E+10 | 0.00 | 0.00 |
May | 0.635836E+10 | 0.107613E+09 | 0.209689E+10 | 58841859.56 | 0.203805E+10 | 0.00 | 0.00 |
June | 0.666683E+10 | 78210352.67 | 0.210059E+10 | 77805434.24 | 0.202279E+10 | 0.00 | 0.00 |
July | 0.611972E+10 | 17870229.94 | 0.214072E+10 | 33899197.52 | 0.210682E+10 | 0.00 | 0.00 |
August | 0.511592E+10 | 70848635.86 | 0.196524E+10 | 6124708.88 | 0.195911E+10 | 0.00 | 0.00 |
September | 0.391712E+10 | 0.269666E+09 | 0.169460E+10 | 118989.86 | 0.169448E+10 | 0.00 | 0.00 |
October | 0.292824E+10 | 0.161835E+10 | 0.151701E+10 | 0.00 | 0.151701E+10 | 0.00 | 0.00 |
November | 0.150954E+10 | 0.319091E+10 | 0.124347E+10 | 0.00 | 0.124347E+10 | 0.00 | 0.00 |
December | 0.702394E+09 | 0.480395E+10 | 0.119076E+10 | 0.00 | 0.119076E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.422014E+11 | 0.212771E+11 | 0.200531E+11 | 0.183002E+09 | 0.198701E+11 | 0.00 | 0.00 |
Minimum of Months | 0.634572E+09 | 17870229.94 | 0.119076E+10 | 0.00 | 0.119076E+10 | 0.00 | 0.00 |
Maximum of Months | 0.666683E+10 | 0.492146E+10 | 0.214072E+10 | 77805434.24 | 0.210682E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.174562E+10 | 0.296743E+10 | 0.174327E+10 | 0.699724E+09 | 0.104354E+10 | 0.00 | 0.00 |
February | 0.246170E+10 | 0.206235E+10 | 0.191290E+10 | 0.789733E+09 | 0.112316E+10 | 0.00 | 0.00 |
March | 0.420211E+10 | 0.131540E+10 | 0.258355E+10 | 0.106640E+10 | 0.151715E+10 | 0.00 | 0.00 |
April | 0.605293E+10 | 0.418120E+09 | 0.297461E+10 | 0.138691E+10 | 0.158769E+10 | 0.00 | 0.00 |
May | 0.709995E+10 | 67922498.09 | 0.302542E+10 | 0.134131E+10 | 0.168411E+10 | 0.00 | 0.00 |
June | 0.621787E+10 | 45398260.51 | 0.238287E+10 | 0.790633E+09 | 0.159223E+10 | 0.00 | 0.00 |
July | 0.529222E+10 | 7309990.61 | 0.206950E+10 | 0.437022E+09 | 0.163247E+10 | 0.00 | 0.00 |
August | 0.448842E+10 | 29195893.56 | 0.186470E+10 | 0.324502E+09 | 0.154020E+10 | 0.00 | 0.00 |
September | 0.403643E+10 | 0.166282E+09 | 0.192796E+10 | 0.537659E+09 | 0.139030E+10 | 0.00 | 0.00 |
October | 0.402250E+10 | 0.102755E+10 | 0.217926E+10 | 0.880276E+09 | 0.129898E+10 | 0.00 | 0.00 |
November | 0.275717E+10 | 0.195338E+10 | 0.186990E+10 | 0.802644E+09 | 0.106725E+10 | 0.00 | 0.00 |
December | 0.183748E+10 | 0.288196E+10 | 0.168482E+10 | 0.667536E+09 | 0.101729E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.502144E+11 | 0.129423E+11 | 0.262187E+11 | 0.972435E+10 | 0.164944E+11 | 0.00 | 0.00 |
Minimum of Months | 0.174562E+10 | 7309990.61 | 0.168482E+10 | 0.324502E+09 | 0.101729E+10 | 0.00 | 0.00 |
Maximum of Months | 0.709995E+10 | 0.296743E+10 | 0.302542E+10 | 0.138691E+10 | 0.168411E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.760087E+10 | 0.447709E+10 | 0.555142E+10 | 0.337318E+10 | 0.217825E+10 | 0.00 | 0.00 |
February | 0.710985E+10 | 0.325788E+10 | 0.476777E+10 | 0.264814E+10 | 0.211962E+10 | 0.00 | 0.00 |
March | 0.788098E+10 | 0.218907E+10 | 0.451334E+10 | 0.199349E+10 | 0.251985E+10 | 0.00 | 0.00 |
April | 0.709338E+10 | 0.743213E+09 | 0.306794E+10 | 0.865857E+09 | 0.220208E+10 | 0.00 | 0.00 |
May | 0.680892E+10 | 0.110057E+09 | 0.227980E+10 | 0.168765E+09 | 0.211104E+10 | 0.00 | 0.00 |
June | 0.650414E+10 | 78942371.21 | 0.201816E+10 | 34438844.85 | 0.198372E+10 | 0.00 | 0.00 |
July | 0.621257E+10 | 16740563.26 | 0.217530E+10 | 29919095.19 | 0.214538E+10 | 0.00 | 0.00 |
August | 0.582216E+10 | 74239654.92 | 0.230752E+10 | 0.123238E+09 | 0.218429E+10 | 0.00 | 0.00 |
September | 0.642552E+10 | 0.303888E+09 | 0.299363E+10 | 0.776997E+09 | 0.221663E+10 | 0.00 | 0.00 |
October | 0.985399E+10 | 0.172087E+10 | 0.532189E+10 | 0.297171E+10 | 0.235018E+10 | 0.00 | 0.00 |
November | 0.104173E+11 | 0.317971E+10 | 0.643288E+10 | 0.425199E+10 | 0.218090E+10 | 0.00 | 0.00 |
December | 0.841850E+10 | 0.445902E+10 | 0.593256E+10 | 0.371749E+10 | 0.221506E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.901482E+11 | 0.206107E+11 | 0.473622E+11 | 0.209552E+11 | 0.264070E+11 | 0.00 | 0.00 |
Minimum of Months | 0.582216E+10 | 16740563.26 | 0.201816E+10 | 29919095.19 | 0.198372E+10 | 0.00 | 0.00 |
Maximum of Months | 0.104173E+11 | 0.447709E+10 | 0.643288E+10 | 0.425199E+10 | 0.251985E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.187611E+10 | 0.343931E+10 | 0.170551E+10 | 0.663719E+09 | 0.104179E+10 | 0.00 | 0.00 |
February | 0.228757E+10 | 0.249180E+10 | 0.176155E+10 | 0.649181E+09 | 0.111237E+10 | 0.00 | 0.00 |
March | 0.406753E+10 | 0.169772E+10 | 0.252903E+10 | 0.101094E+10 | 0.151809E+10 | 0.00 | 0.00 |
April | 0.584985E+10 | 0.695503E+09 | 0.297485E+10 | 0.139509E+10 | 0.157976E+10 | 0.00 | 0.00 |
May | 0.677756E+10 | 0.121624E+09 | 0.291080E+10 | 0.123470E+10 | 0.167610E+10 | 0.00 | 0.00 |
June | 0.645868E+10 | 92019669.47 | 0.264583E+10 | 0.102771E+10 | 0.161812E+10 | 0.00 | 0.00 |
July | 0.488337E+10 | 42465924.12 | 0.202878E+10 | 0.394599E+09 | 0.163419E+10 | 0.00 | 0.00 |
August | 0.410614E+10 | 0.162860E+09 | 0.186323E+10 | 0.331152E+09 | 0.153207E+10 | 0.00 | 0.00 |
September | 0.403846E+10 | 0.277252E+09 | 0.198210E+10 | 0.581889E+09 | 0.140021E+10 | 0.00 | 0.00 |
October | 0.390425E+10 | 0.128476E+10 | 0.213183E+10 | 0.848893E+09 | 0.128294E+10 | 0.00 | 0.00 |
November | 0.279592E+10 | 0.241923E+10 | 0.186638E+10 | 0.795441E+09 | 0.107094E+10 | 0.00 | 0.00 |
December | 0.180438E+10 | 0.356101E+10 | 0.165031E+10 | 0.629301E+09 | 0.102101E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.488498E+11 | 0.162855E+11 | 0.260502E+11 | 0.956263E+10 | 0.164876E+11 | 0.00 | 0.00 |
Minimum of Months | 0.180438E+10 | 42465924.12 | 0.165031E+10 | 0.331152E+09 | 0.102101E+10 | 0.00 | 0.00 |
Maximum of Months | 0.677756E+10 | 0.356101E+10 | 0.297485E+10 | 0.139509E+10 | 0.167610E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.756676E+09 | 0.444286E+10 | 0.122067E+10 | 0.00 | 0.122067E+10 | 0.00 | 0.00 |
February | 0.130253E+10 | 0.310198E+10 | 0.130743E+10 | 0.00 | 0.130743E+10 | 0.00 | 0.00 |
March | 0.270227E+10 | 0.203953E+10 | 0.174425E+10 | 0.00 | 0.174425E+10 | 0.00 | 0.00 |
April | 0.450275E+10 | 0.663896E+09 | 0.183160E+10 | 6211571.55 | 0.182539E+10 | 0.00 | 0.00 |
May | 0.642238E+10 | 0.111234E+09 | 0.209692E+10 | 58843614.39 | 0.203808E+10 | 0.00 | 0.00 |
June | 0.673352E+10 | 84736153.23 | 0.210063E+10 | 77807754.61 | 0.202282E+10 | 0.00 | 0.00 |
July | 0.619321E+10 | 23045251.77 | 0.214076E+10 | 33900208.49 | 0.210686E+10 | 0.00 | 0.00 |
August | 0.523278E+10 | 74549790.00 | 0.196528E+10 | 6124891.54 | 0.195915E+10 | 0.00 | 0.00 |
September | 0.394696E+10 | 0.281557E+09 | 0.169463E+10 | 118993.41 | 0.169451E+10 | 0.00 | 0.00 |
October | 0.298614E+10 | 0.157665E+10 | 0.151703E+10 | 0.00 | 0.151703E+10 | 0.00 | 0.00 |
November | 0.160385E+10 | 0.295894E+10 | 0.124349E+10 | 0.00 | 0.124349E+10 | 0.00 | 0.00 |
December | 0.854502E+09 | 0.427481E+10 | 0.119078E+10 | 0.00 | 0.119078E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.432376E+11 | 0.196338E+11 | 0.200535E+11 | 0.183007E+09 | 0.198705E+11 | 0.00 | 0.00 |
Minimum of Months | 0.756676E+09 | 23045251.77 | 0.119078E+10 | 0.00 | 0.119078E+10 | 0.00 | 0.00 |
Maximum of Months | 0.673352E+10 | 0.444286E+10 | 0.214076E+10 | 77807754.61 | 0.210686E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.181095E+10 | 0.276542E+10 | 0.174326E+10 | 0.699721E+09 | 0.104354E+10 | 0.00 | 0.00 |
February | 0.248095E+10 | 0.197255E+10 | 0.191289E+10 | 0.789730E+09 | 0.112316E+10 | 0.00 | 0.00 |
March | 0.418135E+10 | 0.133369E+10 | 0.258354E+10 | 0.106640E+10 | 0.151715E+10 | 0.00 | 0.00 |
April | 0.602233E+10 | 0.468072E+09 | 0.297459E+10 | 0.138691E+10 | 0.158769E+10 | 0.00 | 0.00 |
May | 0.707583E+10 | 77815196.25 | 0.302541E+10 | 0.134130E+10 | 0.168411E+10 | 0.00 | 0.00 |
June | 0.619111E+10 | 57878419.62 | 0.238286E+10 | 0.790630E+09 | 0.159223E+10 | 0.00 | 0.00 |
July | 0.525505E+10 | 13610752.54 | 0.206949E+10 | 0.437021E+09 | 0.163247E+10 | 0.00 | 0.00 |
August | 0.445086E+10 | 51037486.80 | 0.186469E+10 | 0.324501E+09 | 0.154019E+10 | 0.00 | 0.00 |
September | 0.401435E+10 | 0.197736E+09 | 0.192795E+10 | 0.537657E+09 | 0.139029E+10 | 0.00 | 0.00 |
October | 0.400895E+10 | 0.105631E+10 | 0.217925E+10 | 0.880272E+09 | 0.129897E+10 | 0.00 | 0.00 |
November | 0.277171E+10 | 0.190486E+10 | 0.186989E+10 | 0.802641E+09 | 0.106725E+10 | 0.00 | 0.00 |
December | 0.190136E+10 | 0.271335E+10 | 0.168481E+10 | 0.667533E+09 | 0.101728E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.501648E+11 | 0.126123E+11 | 0.262186E+11 | 0.972431E+10 | 0.164943E+11 | 0.00 | 0.00 |
Minimum of Months | 0.181095E+10 | 13610752.54 | 0.168481E+10 | 0.324501E+09 | 0.101728E+10 | 0.00 | 0.00 |
Maximum of Months | 0.707583E+10 | 0.276542E+10 | 0.302541E+10 | 0.138691E+10 | 0.168411E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.755077E+10 | 0.441953E+10 | 0.555159E+10 | 0.337329E+10 | 0.217830E+10 | 0.00 | 0.00 |
February | 0.706774E+10 | 0.320457E+10 | 0.476791E+10 | 0.264823E+10 | 0.211968E+10 | 0.00 | 0.00 |
March | 0.785360E+10 | 0.218080E+10 | 0.451346E+10 | 0.199356E+10 | 0.251990E+10 | 0.00 | 0.00 |
April | 0.713294E+10 | 0.748010E+09 | 0.306800E+10 | 0.865885E+09 | 0.220212E+10 | 0.00 | 0.00 |
May | 0.686946E+10 | 0.111473E+09 | 0.227984E+10 | 0.168770E+09 | 0.211107E+10 | 0.00 | 0.00 |
June | 0.657707E+10 | 83646886.49 | 0.201820E+10 | 34439972.86 | 0.198376E+10 | 0.00 | 0.00 |
July | 0.629082E+10 | 20327321.27 | 0.217534E+10 | 29920075.17 | 0.214542E+10 | 0.00 | 0.00 |
August | 0.591654E+10 | 78061325.72 | 0.230758E+10 | 0.123242E+09 | 0.218434E+10 | 0.00 | 0.00 |
September | 0.641542E+10 | 0.327571E+09 | 0.299371E+10 | 0.777023E+09 | 0.221668E+10 | 0.00 | 0.00 |
October | 0.981759E+10 | 0.175096E+10 | 0.532204E+10 | 0.297180E+10 | 0.235023E+10 | 0.00 | 0.00 |
November | 0.103731E+11 | 0.315949E+10 | 0.643307E+10 | 0.425213E+10 | 0.218095E+10 | 0.00 | 0.00 |
December | 0.840450E+10 | 0.434705E+10 | 0.593273E+10 | 0.371762E+10 | 0.221512E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.902696E+11 | 0.204315E+11 | 0.473635E+11 | 0.209559E+11 | 0.264076E+11 | 0.00 | 0.00 |
Minimum of Months | 0.591654E+10 | 20327321.27 | 0.201820E+10 | 29920075.17 | 0.198376E+10 | 0.00 | 0.00 |
Maximum of Months | 0.103731E+11 | 0.441953E+10 | 0.643307E+10 | 0.425213E+10 | 0.251990E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.196771E+10 | 0.306039E+10 | 0.170550E+10 | 0.663716E+09 | 0.104178E+10 | 0.00 | 0.00 |
February | 0.237465E+10 | 0.218753E+10 | 0.176155E+10 | 0.649178E+09 | 0.111237E+10 | 0.00 | 0.00 |
March | 0.415297E+10 | 0.149540E+10 | 0.252902E+10 | 0.101094E+10 | 0.151808E+10 | 0.00 | 0.00 |
April | 0.600594E+10 | 0.548230E+09 | 0.297484E+10 | 0.139509E+10 | 0.157975E+10 | 0.00 | 0.00 |
May | 0.685456E+10 | 0.104761E+09 | 0.291079E+10 | 0.123470E+10 | 0.167609E+10 | 0.00 | 0.00 |
June | 0.659542E+10 | 74392060.00 | 0.264582E+10 | 0.102771E+10 | 0.161811E+10 | 0.00 | 0.00 |
July | 0.509057E+10 | 22386456.82 | 0.202878E+10 | 0.394598E+09 | 0.163418E+10 | 0.00 | 0.00 |
August | 0.438375E+10 | 67393117.14 | 0.186322E+10 | 0.331151E+09 | 0.153207E+10 | 0.00 | 0.00 |
September | 0.408930E+10 | 0.238757E+09 | 0.198210E+10 | 0.581887E+09 | 0.140021E+10 | 0.00 | 0.00 |
October | 0.397174E+10 | 0.116320E+10 | 0.213182E+10 | 0.848889E+09 | 0.128294E+10 | 0.00 | 0.00 |
November | 0.290168E+10 | 0.211469E+10 | 0.186638E+10 | 0.795438E+09 | 0.107094E+10 | 0.00 | 0.00 |
December | 0.197452E+10 | 0.296428E+10 | 0.165030E+10 | 0.629299E+09 | 0.102101E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.503628E+11 | 0.140414E+11 | 0.260501E+11 | 0.956259E+10 | 0.164875E+11 | 0.00 | 0.00 |
Minimum of Months | 0.196771E+10 | 22386456.82 | 0.165030E+10 | 0.331151E+09 | 0.102101E+10 | 0.00 | 0.00 |
Maximum of Months | 0.685456E+10 | 0.306039E+10 | 0.297484E+10 | 0.139509E+10 | 0.167609E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.926004E+09 | 0.385822E+10 | 0.122067E+10 | 0.00 | 0.122067E+10 | 0.00 | 0.00 |
February | 0.139731E+10 | 0.282356E+10 | 0.130743E+10 | 0.00 | 0.130743E+10 | 0.00 | 0.00 |
March | 0.270144E+10 | 0.196029E+10 | 0.174425E+10 | 0.00 | 0.174425E+10 | 0.00 | 0.00 |
April | 0.442581E+10 | 0.670970E+09 | 0.183160E+10 | 6211571.55 | 0.182539E+10 | 0.00 | 0.00 |
May | 0.629584E+10 | 0.125302E+09 | 0.209692E+10 | 58843614.39 | 0.203808E+10 | 0.00 | 0.00 |
June | 0.659860E+10 | 95200721.54 | 0.210063E+10 | 77807754.61 | 0.202282E+10 | 0.00 | 0.00 |
July | 0.605485E+10 | 25632722.24 | 0.214076E+10 | 33900208.49 | 0.210686E+10 | 0.00 | 0.00 |
August | 0.512401E+10 | 84073321.09 | 0.196528E+10 | 6124891.54 | 0.195915E+10 | 0.00 | 0.00 |
September | 0.388441E+10 | 0.293305E+09 | 0.169463E+10 | 118993.41 | 0.169451E+10 | 0.00 | 0.00 |
October | 0.296822E+10 | 0.153517E+10 | 0.151703E+10 | 0.00 | 0.151703E+10 | 0.00 | 0.00 |
November | 0.167001E+10 | 0.274700E+10 | 0.124349E+10 | 0.00 | 0.124349E+10 | 0.00 | 0.00 |
December | 0.101430E+10 | 0.379217E+10 | 0.119078E+10 | 0.00 | 0.119078E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.430608E+11 | 0.180109E+11 | 0.200535E+11 | 0.183007E+09 | 0.198705E+11 | 0.00 | 0.00 |
Minimum of Months | 0.926004E+09 | 25632722.24 | 0.119078E+10 | 0.00 | 0.119078E+10 | 0.00 | 0.00 |
Maximum of Months | 0.659860E+10 | 0.385822E+10 | 0.214076E+10 | 77807754.61 | 0.210686E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.196537E+10 | 0.244085E+10 | 0.174326E+10 | 0.699721E+09 | 0.104354E+10 | 0.00 | 0.00 |
February | 0.254442E+10 | 0.183518E+10 | 0.191289E+10 | 0.789730E+09 | 0.112316E+10 | 0.00 | 0.00 |
March | 0.417223E+10 | 0.130370E+10 | 0.258354E+10 | 0.106640E+10 | 0.151715E+10 | 0.00 | 0.00 |
April | 0.596414E+10 | 0.479036E+09 | 0.297459E+10 | 0.138691E+10 | 0.158769E+10 | 0.00 | 0.00 |
May | 0.698338E+10 | 88544188.33 | 0.302541E+10 | 0.134130E+10 | 0.168411E+10 | 0.00 | 0.00 |
June | 0.609433E+10 | 65594359.36 | 0.238286E+10 | 0.790630E+09 | 0.159223E+10 | 0.00 | 0.00 |
July | 0.515764E+10 | 15020457.82 | 0.206949E+10 | 0.437021E+09 | 0.163247E+10 | 0.00 | 0.00 |
August | 0.437436E+10 | 57794006.36 | 0.186469E+10 | 0.324501E+09 | 0.154019E+10 | 0.00 | 0.00 |
September | 0.396885E+10 | 0.207012E+09 | 0.192795E+10 | 0.537657E+09 | 0.139029E+10 | 0.00 | 0.00 |
October | 0.399114E+10 | 0.104270E+10 | 0.217925E+10 | 0.880272E+09 | 0.129897E+10 | 0.00 | 0.00 |
November | 0.281147E+10 | 0.180485E+10 | 0.186989E+10 | 0.802641E+09 | 0.106725E+10 | 0.00 | 0.00 |
December | 0.203102E+10 | 0.245871E+10 | 0.168481E+10 | 0.667533E+09 | 0.101728E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.500584E+11 | 0.117990E+11 | 0.262186E+11 | 0.972431E+10 | 0.164943E+11 | 0.00 | 0.00 |
Minimum of Months | 0.196537E+10 | 15020457.82 | 0.168481E+10 | 0.324501E+09 | 0.101728E+10 | 0.00 | 0.00 |
Maximum of Months | 0.698338E+10 | 0.245871E+10 | 0.302541E+10 | 0.138691E+10 | 0.168411E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.771902E+10 | 0.396369E+10 | 0.555159E+10 | 0.337329E+10 | 0.217830E+10 | 0.00 | 0.00 |
February | 0.712555E+10 | 0.300079E+10 | 0.476791E+10 | 0.264823E+10 | 0.211968E+10 | 0.00 | 0.00 |
March | 0.782744E+10 | 0.213106E+10 | 0.451346E+10 | 0.199356E+10 | 0.251990E+10 | 0.00 | 0.00 |
April | 0.704982E+10 | 0.762537E+09 | 0.306800E+10 | 0.865885E+09 | 0.220212E+10 | 0.00 | 0.00 |
May | 0.674202E+10 | 0.125578E+09 | 0.227984E+10 | 0.168770E+09 | 0.211107E+10 | 0.00 | 0.00 |
June | 0.644101E+10 | 94630488.00 | 0.201820E+10 | 34439972.86 | 0.198376E+10 | 0.00 | 0.00 |
July | 0.615142E+10 | 22469016.34 | 0.217534E+10 | 29920075.17 | 0.214542E+10 | 0.00 | 0.00 |
August | 0.580611E+10 | 88243698.41 | 0.230758E+10 | 0.123242E+09 | 0.218434E+10 | 0.00 | 0.00 |
September | 0.634662E+10 | 0.344265E+09 | 0.299371E+10 | 0.777023E+09 | 0.221668E+10 | 0.00 | 0.00 |
October | 0.977826E+10 | 0.173753E+10 | 0.532204E+10 | 0.297180E+10 | 0.235023E+10 | 0.00 | 0.00 |
November | 0.103914E+11 | 0.302760E+10 | 0.643307E+10 | 0.425213E+10 | 0.218095E+10 | 0.00 | 0.00 |
December | 0.854166E+10 | 0.400397E+10 | 0.593273E+10 | 0.371762E+10 | 0.221512E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.899203E+11 | 0.193024E+11 | 0.473635E+11 | 0.209559E+11 | 0.264076E+11 | 0.00 | 0.00 |
Minimum of Months | 0.580611E+10 | 22469016.34 | 0.201820E+10 | 29920075.17 | 0.198376E+10 | 0.00 | 0.00 |
Maximum of Months | 0.103914E+11 | 0.400397E+10 | 0.643307E+10 | 0.425213E+10 | 0.251990E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.205664E+10 | 0.274444E+10 | 0.170550E+10 | 0.663716E+09 | 0.104178E+10 | 0.00 | 0.00 |
February | 0.241604E+10 | 0.203617E+10 | 0.176155E+10 | 0.649178E+09 | 0.111237E+10 | 0.00 | 0.00 |
March | 0.413917E+10 | 0.145554E+10 | 0.252902E+10 | 0.101094E+10 | 0.151808E+10 | 0.00 | 0.00 |
April | 0.595408E+10 | 0.553672E+09 | 0.297484E+10 | 0.139509E+10 | 0.157975E+10 | 0.00 | 0.00 |
May | 0.677802E+10 | 0.112825E+09 | 0.291079E+10 | 0.123470E+10 | 0.167609E+10 | 0.00 | 0.00 |
June | 0.651382E+10 | 79833431.80 | 0.264582E+10 | 0.102771E+10 | 0.161811E+10 | 0.00 | 0.00 |
July | 0.501006E+10 | 24005839.07 | 0.202878E+10 | 0.394598E+09 | 0.163418E+10 | 0.00 | 0.00 |
August | 0.432287E+10 | 73117717.19 | 0.186322E+10 | 0.331151E+09 | 0.153207E+10 | 0.00 | 0.00 |
September | 0.404981E+10 | 0.245201E+09 | 0.198210E+10 | 0.581887E+09 | 0.140021E+10 | 0.00 | 0.00 |
October | 0.395383E+10 | 0.114256E+10 | 0.213182E+10 | 0.848889E+09 | 0.128294E+10 | 0.00 | 0.00 |
November | 0.292642E+10 | 0.200251E+10 | 0.186638E+10 | 0.795438E+09 | 0.107094E+10 | 0.00 | 0.00 |
December | 0.205705E+10 | 0.270416E+10 | 0.165030E+10 | 0.629299E+09 | 0.102101E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.501778E+11 | 0.131740E+11 | 0.260501E+11 | 0.956259E+10 | 0.164875E+11 | 0.00 | 0.00 |
Minimum of Months | 0.205664E+10 | 24005839.07 | 0.165030E+10 | 0.331151E+09 | 0.102101E+10 | 0.00 | 0.00 |
Maximum of Months | 0.677802E+10 | 0.274444E+10 | 0.297484E+10 | 0.139509E+10 | 0.167609E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 13.39 | 10.38 | 7.87 | 1.20 | 0.38 | 63.33 | 149.51 | 0.00 |
February | 16.97 | 12.78 | 9.69 | 1.81 | 4.63 | 75.94 | 163.32 | 0.01 |
March | 22.37 | 15.60 | 11.23 | 1.86 | 10.07 | 92.70 | 193.23 | 0.00 |
April | 29.13 | 18.33 | 11.93 | 1.64 | 16.17 | 89.20 | 259.84 | 0.01 |
May | 32.98 | 21.97 | 16.72 | 2.17 | 21.14 | 97.31 | 248.85 | 0.02 |
June | 33.59 | 24.39 | 20.62 | 1.55 | 23.45 | 107.22 | 203.36 | 0.06 |
July | 31.67 | 26.29 | 24.51 | 2.27 | 24.88 | 132.35 | 83.14 | 0.02 |
August | 30.03 | 26.31 | 25.11 | 1.75 | 23.81 | 127.44 | 60.46 | 0.00 |
September | 28.75 | 24.70 | 23.21 | 1.33 | 20.22 | 105.62 | 105.60 | 0.08 |
October | 25.09 | 18.74 | 15.36 | 0.77 | 12.83 | 75.09 | 190.08 | 0.00 |
November | 19.63 | 14.46 | 10.99 | 0.66 | 5.78 | 58.54 | 201.10 | 0.00 |
December | 14.52 | 10.88 | 7.89 | 0.97 | 0.94 | 60.91 | 153.60 | 0.01 |
Annual Sum or Average | 24.88 | 18.77 | 15.46 | 1.50 | 13.74 | 90.59 | 167.44 | 0.02 |
Minimum of Months | 13.39 | 10.38 | 7.87 | 0.66 | 0.38 | 58.54 | 60.46 | 0.00 |
Maximum of Months | 33.59 | 26.31 | 25.11 | 2.27 | 24.88 | 132.35 | 259.84 | 0.08 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 23.60 | 12-JAN-14:00 | 14.20 | 7.40 | 3.80 | 8.15 | 163.00 | 476.00 |
February | 27.10 | 22-FEB-14:00 | 16.20 | 9.10 | 1.50 | 15.39 | 225.00 | 451.00 |
March | 35.60 | 28-MAR-14:00 | 18.50 | 7.70 | 0.00 | 19.52 | 182.00 | 699.00 |
April | 40.30 | 15-APR-14:00 | 20.67 | 10.00 | 6.70 | 28.43 | 201.00 | 649.50 |
May | 44.50 | 03-MAY-14:00 | 20.64 | 5.30 | 2.80 | 28.91 | 150.00 | 809.00 |
June | 44.60 | 07-JUN-15:00 | 21.53 | 9.10 | 3.10 | 28.43 | 167.00 | 640.50 |
July | 40.40 | 02-JUL-15:00 | 26.36 | 21.60 | 2.10 | 29.87 | 200.00 | 545.50 |
August | 37.30 | 07-AUG-14:00 | 26.58 | 22.90 | 3.00 | 29.87 | 311.00 | 370.00 |
September | 37.50 | 17-SEP-19:00 | 27.68 | 24.60 | 0.20 | 28.59 | 0.00 | 0.00 |
October | 36.40 | 02-OCT-14:20 | 21.05 | 13.00 | 1.80 | 21.61 | 187.33 | 678.83 |
November | 30.30 | 04-NOV-13:00 | 17.17 | 8.90 | 1.10 | 14.84 | 155.00 | 710.00 |
December | 24.60 | 28-DEC-13:00 | 15.30 | 8.90 | 2.80 | 10.88 | 181.50 | 535.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 23.60 | 14.20 | 5.30 | 0.00 | 8.15 | 0.00 | 0.00 | |
Maximum of Months | 44.60 | 27.68 | 24.60 | 6.70 | 29.87 | 311.00 | 809.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 4.80 | 05-JAN-06:00 | 4.73 | 4.60 | 0.00 | -10.2 | 0.00 | 0.00 |
February | 6.90 | 02-FEB-05:00 | 6.67 | 6.50 | 0.00 | -7.8 | 0.00 | 0.00 |
March | 13.30 | 01-MAR-03:00 | 10.56 | 8.30 | 0.80 | -1.4 | 0.00 | 0.00 |
April | 17.40 | 11-APR-04:00 | 13.58 | 10.90 | 0.00 | 3.06 | 0.00 | 0.00 |
May | 22.70 | 13-MAY-04:00 | 20.32 | 19.30 | 2.10 | 20.40 | 0.00 | 0.00 |
June | 23.30 | 18-JUN-04:00 | 21.80 | 21.20 | 2.70 | 17.75 | 0.00 | 0.00 |
July | 23.20 | 19-JUL-02:00 | 23.20 | 23.20 | 2.30 | 15.39 | 0.00 | 0.00 |
August | 23.40 | 15-AUG-23:00 | 22.91 | 22.80 | 2.40 | 21.78 | 0.00 | 0.00 |
September | 23.00 | 27-SEP-04:00 | 20.74 | 19.70 | 0.00 | 10.30 | 0.00 | 0.00 |
October | 15.50 | 31-OCT-04:00 | 14.07 | 13.20 | 0.00 | 1.80 | 0.00 | 0.00 |
November | 9.50 | 27-NOV-05:00 | 8.75 | 8.10 | 0.00 | -5.0 | 0.00 | 0.00 |
December | 5.00 | 21-DEC-04:00 | 4.08 | 3.00 | 0.00 | -10.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 4.80 | 4.08 | 3.00 | 0.00 | -10.5 | 0.00 | 0.00 | |
Maximum of Months | 23.40 | 23.20 | 23.20 | 2.70 | 21.78 | 0.00 | 0.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 15.62 | 17-JAN-14:00 | 18.20 | 14.10 | 1.00 | 11.07 | 198.00 | 56.50 |
February | 18.14 | 25-FEB-16:00 | 21.20 | 16.60 | 5.90 | 10.88 | 107.50 | 156.50 |
March | 21.38 | 10-MAR-18:49 | 29.25 | 17.73 | 2.10 | 21.44 | 0.00 | 0.00 |
April | 23.42 | 18-APR-13:00 | 37.10 | 17.80 | 5.70 | 23.49 | 233.50 | 671.50 |
May | 27.40 | 22-MAY-22:00 | 29.40 | 26.80 | 0.00 | 20.40 | 0.00 | 0.00 |
June | 28.92 | 28-JUN-12:00 | 34.40 | 27.50 | 1.00 | 25.49 | 332.50 | 501.50 |
July | 29.18 | 01-JUL-16:00 | 37.20 | 26.80 | 2.30 | 25.66 | 196.00 | 196.00 |
August | 29.17 | 27-AUG-15:00 | 35.10 | 27.40 | 1.30 | 29.55 | 256.00 | 129.00 |
September | 28.10 | 14-SEP-16:00 | 33.70 | 26.40 | 1.40 | 26.48 | 122.50 | 108.50 |
October | 23.06 | 06-OCT-10:00 | 28.60 | 20.80 | 1.30 | 20.22 | 327.00 | 348.50 |
November | 18.93 | 08-NOV-17:10 | 27.55 | 14.47 | 0.17 | 16.67 | 28.00 | 65.33 |
December | 15.64 | 29-DEC-19:00 | 16.80 | 14.90 | 4.80 | 13.54 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.62 | 16.80 | 14.10 | 0.00 | 10.88 | 0.00 | 0.00 | |
Maximum of Months | 29.18 | 37.20 | 27.50 | 5.90 | 29.55 | 332.50 | 671.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.10 | 17-JAN-13:00 | 17.80 | 15.48 | 0.90 | 9.72 | 260.50 | 81.50 |
February | 16.60 | 25-FEB-16:00 | 21.20 | 18.14 | 5.90 | 10.88 | 107.50 | 156.50 |
March | 18.30 | 10-MAR-19:00 | 27.70 | 21.26 | 2.10 | 21.44 | 0.00 | 0.00 |
April | 19.30 | 26-APR-23:10 | 28.53 | 22.04 | 0.00 | 15.61 | 0.00 | 0.00 |
May | 26.80 | 22-MAY-22:00 | 29.40 | 27.40 | 0.00 | 20.40 | 0.00 | 0.00 |
June | 27.50 | 28-JUN-12:00 | 34.40 | 28.92 | 1.00 | 25.49 | 332.50 | 501.50 |
July | 27.30 | 18-JUL-06:19 | 29.10 | 27.70 | 1.17 | 26.48 | 20.00 | 0.00 |
August | 28.80 | 12-AUG-07:00 | 29.10 | 28.83 | 2.90 | 26.81 | 113.00 | 6.50 |
September | 26.50 | 12-SEP-14:00 | 30.50 | 27.38 | 0.90 | 25.99 | 260.00 | 20.00 |
October | 21.10 | 06-OCT-08:00 | 25.50 | 22.41 | 0.30 | 17.21 | 239.00 | 159.00 |
November | 16.30 | 08-NOV-21:19 | 20.10 | 17.59 | 0.00 | 10.95 | 0.00 | 0.00 |
December | 14.90 | 29-DEC-20:10 | 16.72 | 15.59 | 4.73 | 13.13 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 14.10 | 16.72 | 15.48 | 0.00 | 9.72 | 0.00 | 0.00 | |
Maximum of Months | 28.80 | 34.40 | 28.92 | 5.90 | 26.81 | 332.50 | 501.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 20.92 | 27.26 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 21.74 | 33.91 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 24.21 | 44.04 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 27.79 | 55.91 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 31.48 | 58.43 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 34.27 | 54.82 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 35.42 | 39.75 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 34.60 | 34.68 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 32.04 | 35.55 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 28.44 | 39.44 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 24.77 | 33.85 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 22.02 | 26.79 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 28.18 | 40.37 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 20.92 | 26.79 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 35.42 | 58.43 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.313250E+11 | -0.303039E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102106E+10 | 58.97 | 0.00 | 0.00 |
February | 0.278785E+11 | -0.269554E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -923077069.9 | 58.97 | 0.00 | 0.00 |
March | 0.306002E+11 | -0.295746E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102561E+10 | 58.98 | 0.00 | 0.00 |
April | 0.250571E+11 | -0.240683E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -988770070.4 | 58.97 | 0.00 | 0.00 |
May | 0.237303E+11 | -0.227078E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102248E+10 | 58.97 | 0.00 | 0.00 |
June | 0.211633E+11 | -0.201733E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -989972621.0 | 58.96 | 0.00 | 0.00 |
July | 0.193085E+11 | -0.182913E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101724E+10 | 58.96 | 0.00 | 0.00 |
August | 0.217636E+11 | -0.207422E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102138E+10 | 58.97 | 0.00 | 0.00 |
September | 0.218160E+11 | -0.208298E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -986124291.4 | 58.96 | 0.00 | 0.00 |
October | 0.253571E+11 | -0.243390E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101803E+10 | 58.97 | 0.00 | 0.00 |
November | 0.277046E+11 | -0.267189E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -985611251.0 | 58.97 | 0.00 | 0.00 |
December | 0.297410E+11 | -0.287222E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101880E+10 | 58.97 | 0.00 | 0.00 |
Annual Sum or Average | 0.305445E+12 | -0.293427E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.120182E+11 | 58.97 | 0.00 | 0.00 |
Minimum of Months | 0.193085E+11 | -0.303039E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.102561E+10 | 58.96 | 0.00 | 0.00 |
Maximum of Months | 0.313250E+11 | -0.182913E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -923077069.9 | 58.98 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.64 | 0.61 | 01-JAN-07:49 | 5229.40 | 34.80 | 297.00 | 284.33 | 1049.42 | 24.95 | 250.50 | 263.50 |
February | 303.83 | 0.64 | 0.61 | 01-FEB-07:49 | 3042.78 | 28.08 | 195.67 | 268.33 | 918.85 | 20.43 | 147.00 | 236.00 |
March | 364.50 | 0.64 | 0.61 | 01-MAR-07:40 | 1477.59 | 17.65 | 7.50 | 315.00 | 789.00 | 20.23 | 129.17 | 279.83 |
April | 379.83 | 0.65 | 0.61 | 01-APR-07:10 | 982.72 | 16.01 | 0.00 | 322.67 | 578.92 | 18.84 | 10.17 | 280.50 |
May | 406.00 | 0.65 | 0.61 | 01-MAY-06:49 | 833.18 | 15.69 | 0.00 | 340.50 | 488.09 | 18.64 | 0.67 | 292.67 |
June | 386.67 | 0.65 | 0.61 | 01-JUN-06:00 | 829.12 | 15.40 | 0.00 | 326.00 | 473.29 | 18.30 | 0.00 | 274.67 |
July | 379.83 | 0.64 | 0.61 | 01-JUL-06:40 | 948.58 | 15.96 | 0.00 | 324.17 | 486.34 | 18.75 | 3.33 | 260.67 |
August | 372.50 | 0.65 | 0.61 | 01-AUG-06:49 | 1073.85 | 16.05 | 0.00 | 313.50 | 530.54 | 18.80 | 51.17 | 252.33 |
September | 344.33 | 0.64 | 0.61 | 01-SEP-06:00 | 1299.80 | 16.77 | 0.00 | 294.33 | 664.41 | 19.62 | 123.67 | 248.67 |
October | 347.33 | 0.65 | 0.61 | 01-OCT-06:00 | 2269.30 | 18.78 | 39.33 | 300.17 | 883.15 | 19.96 | 131.00 | 269.67 |
November | 317.83 | 0.64 | 0.61 | 01-NOV-07:19 | 7147.17 | 34.42 | 292.17 | 279.00 | 1080.60 | 22.63 | 172.83 | 259.17 |
December | 315.50 | 0.64 | 0.61 | 01-DEC-07:30 | 5499.61 | 34.82 | 293.00 | 280.17 | 1253.63 | 27.25 | 275.83 | 276.00 |
Annual Sum or Average | 4237.50 | 0.64 | 2399.52 | 21.42 | 1124.67 | 3648.17 | 745.67 | 20.52 | 1295.33 | 3193.67 | ||
Minimum of Months | 303.83 | 0.64 | 0.61 | 829.12 | 15.40 | 0.00 | 268.33 | 473.29 | 18.30 | 0.00 | 236.00 | |
Maximum of Months | 406.00 | 0.65 | 0.61 | 7147.17 | 34.82 | 297.00 | 340.50 | 1253.63 | 27.25 | 275.83 | 292.67 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.66 | 0.61 | 01-JAN-07:49 | 1408.41 | 17.63 | 83.67 | 252.17 | 757.96 | 18.92 | 74.33 | 200.50 |
February | 303.83 | 0.65 | 0.61 | 01-FEB-07:49 | 1747.84 | 17.40 | 75.00 | 246.17 | 948.69 | 18.63 | 69.50 | 199.00 |
March | 364.50 | 0.64 | 0.61 | 01-MAR-07:40 | 1690.85 | 15.45 | 57.83 | 305.67 | 849.32 | 14.19 | 2.67 | 264.67 |
April | 379.83 | 0.65 | 0.61 | 01-APR-06:49 | 2045.00 | 11.68 | 0.00 | 316.00 | 1092.67 | 13.06 | 0.00 | 279.50 |
May | 406.00 | 0.64 | 0.61 | 01-MAY-06:10 | 2207.47 | 11.81 | 0.00 | 344.83 | 801.02 | 13.00 | 0.00 | 301.00 |
June | 386.67 | 0.65 | 0.61 | 01-JUN-06:40 | 1740.72 | 11.88 | 0.00 | 329.00 | 689.86 | 12.82 | 0.00 | 278.83 |
July | 379.83 | 0.64 | 0.61 | 01-JUL-06:10 | 1427.28 | 12.51 | 0.00 | 328.33 | 612.22 | 13.14 | 0.00 | 260.00 |
August | 372.50 | 0.65 | 0.61 | 01-AUG-06:19 | 1286.70 | 12.44 | 0.00 | 311.50 | 583.45 | 13.09 | 0.00 | 246.83 |
September | 344.33 | 0.65 | 0.61 | 01-SEP-06:49 | 1436.76 | 13.06 | 8.50 | 289.17 | 722.50 | 13.86 | 5.50 | 230.67 |
October | 347.33 | 0.65 | 0.61 | 01-OCT-06:49 | 1588.53 | 17.03 | 85.83 | 283.83 | 776.70 | 16.43 | 55.00 | 240.67 |
November | 317.83 | 0.65 | 0.61 | 01-NOV-07:10 | 1431.06 | 17.88 | 82.50 | 254.67 | 711.90 | 17.54 | 56.17 | 210.67 |
December | 315.50 | 0.65 | 0.61 | 01-DEC-07:40 | 1471.06 | 18.19 | 87.83 | 247.67 | 805.64 | 19.64 | 79.67 | 206.17 |
Annual Sum or Average | 4237.50 | 0.65 | 1635.41 | 14.54 | 481.17 | 3509.00 | 777.75 | 15.15 | 342.83 | 2918.50 | ||
Minimum of Months | 303.83 | 0.64 | 0.61 | 1286.70 | 11.68 | 0.00 | 246.17 | 583.45 | 12.82 | 0.00 | 199.00 | |
Maximum of Months | 406.00 | 0.66 | 0.61 | 2207.47 | 18.19 | 87.83 | 344.83 | 1092.67 | 19.64 | 79.67 | 301.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.67 | 0.61 | 01-JAN-08:39 | 450.37 | 0.00 | 0.00 | 225.50 | 281.20 | 0.00 | 0.00 | 101.67 |
February | 303.83 | 0.66 | 0.61 | 01-FEB-08:20 | 520.95 | 0.00 | 0.00 | 237.00 | 323.35 | 0.00 | 0.00 | 146.67 |
March | 364.50 | 0.64 | 0.61 | 01-MAR-07:00 | 616.84 | 0.00 | 0.00 | 302.83 | 381.62 | 0.00 | 0.00 | 236.67 |
April | 379.83 | 0.65 | 0.61 | 01-APR-07:10 | 664.67 | 0.00 | 0.00 | 325.67 | 417.80 | 0.00 | 0.00 | 278.67 |
May | 406.00 | 0.64 | 0.61 | 01-MAY-06:19 | 802.65 | 0.00 | 0.00 | 360.00 | 471.90 | 0.00 | 0.00 | 322.83 |
June | 386.67 | 0.64 | 0.61 | 01-JUN-06:49 | 896.14 | 0.00 | 0.00 | 342.50 | 498.79 | 0.00 | 0.00 | 300.17 |
July | 379.83 | 0.63 | 0.61 | 01-JUL-06:19 | 922.74 | 0.00 | 0.00 | 336.83 | 477.54 | 0.00 | 0.00 | 278.83 |
August | 372.50 | 0.64 | 0.61 | 01-AUG-06:40 | 827.49 | 0.00 | 0.00 | 317.17 | 427.45 | 0.00 | 0.00 | 249.33 |
September | 344.33 | 0.64 | 0.61 | 01-SEP-06:00 | 710.28 | 0.00 | 0.00 | 290.67 | 393.92 | 0.00 | 0.00 | 216.67 |
October | 347.33 | 0.66 | 0.61 | 01-OCT-07:10 | 543.29 | 0.00 | 0.00 | 279.17 | 345.60 | 0.00 | 0.00 | 198.00 |
November | 317.83 | 0.66 | 0.61 | 01-NOV-07:40 | 456.83 | 0.00 | 0.00 | 235.17 | 304.39 | 0.00 | 0.00 | 132.33 |
December | 315.50 | 0.67 | 0.61 | 01-DEC-08:20 | 442.31 | 0.00 | 0.00 | 223.17 | 279.49 | 0.00 | 0.00 | 89.33 |
Annual Sum or Average | 4237.50 | 0.65 | 667.50 | 0.00 | 0.00 | 3475.67 | 389.74 | 0.00 | 0.00 | 2551.17 | ||
Minimum of Months | 303.83 | 0.63 | 0.61 | 442.31 | 0.00 | 0.00 | 223.17 | 279.49 | 0.00 | 0.00 | 89.33 | |
Maximum of Months | 406.00 | 0.67 | 0.61 | 922.74 | 0.00 | 0.00 | 360.00 | 498.79 | 0.00 | 0.00 | 322.83 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.66 | 0.61 | 01-JAN-08:50 | 1413.08 | 17.63 | 82.50 | 250.33 | 745.72 | 18.67 | 71.50 | 201.67 |
February | 303.83 | 0.65 | 0.61 | 01-FEB-08:39 | 1662.73 | 17.31 | 77.00 | 247.67 | 663.34 | 16.83 | 44.00 | 201.83 |
March | 364.50 | 0.64 | 0.61 | 01-MAR-08:09 | 1645.38 | 15.39 | 57.33 | 306.00 | 822.80 | 14.13 | 1.83 | 264.50 |
April | 379.83 | 0.65 | 0.61 | 01-APR-07:30 | 1881.74 | 11.68 | 0.00 | 319.50 | 978.65 | 13.07 | 0.00 | 282.83 |
May | 406.00 | 0.64 | 0.61 | 01-MAY-07:10 | 1807.33 | 11.79 | 0.00 | 342.00 | 934.99 | 12.97 | 0.00 | 301.67 |
June | 386.67 | 0.65 | 0.61 | 01-JUN-07:10 | 1804.63 | 11.96 | 0.00 | 329.83 | 716.76 | 12.90 | 0.00 | 284.17 |
July | 379.83 | 0.64 | 0.61 | 01-JUL-06:00 | 1378.71 | 12.53 | 0.00 | 325.67 | 605.46 | 13.16 | 0.00 | 263.17 |
August | 372.50 | 0.65 | 0.61 | 01-AUG-07:10 | 1272.69 | 12.41 | 0.00 | 311.33 | 626.22 | 13.05 | 0.00 | 248.17 |
September | 344.33 | 0.64 | 0.61 | 01-SEP-07:30 | 1410.50 | 13.13 | 8.50 | 290.00 | 698.44 | 13.92 | 5.50 | 236.00 |
October | 347.33 | 0.65 | 0.61 | 01-OCT-07:30 | 1689.01 | 16.96 | 84.83 | 281.00 | 848.39 | 16.34 | 54.00 | 242.00 |
November | 317.83 | 0.65 | 0.61 | 01-NOV-07:00 | 1480.96 | 17.90 | 84.83 | 257.67 | 720.42 | 17.28 | 55.00 | 211.83 |
December | 315.50 | 0.65 | 0.61 | 01-DEC-08:20 | 1293.14 | 18.30 | 87.33 | 252.17 | 650.84 | 17.73 | 56.33 | 204.50 |
Annual Sum or Average | 4237.50 | 0.65 | 1569.62 | 14.54 | 482.33 | 3513.17 | 755.35 | 14.83 | 288.17 | 2942.33 | ||
Minimum of Months | 303.83 | 0.64 | 0.61 | 1272.69 | 11.68 | 0.00 | 247.67 | 605.46 | 12.90 | 0.00 | 201.67 | |
Maximum of Months | 406.00 | 0.66 | 0.61 | 1881.74 | 18.30 | 87.33 | 342.00 | 978.65 | 18.67 | 71.50 | 301.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.64 | 0.61 | 01-JAN-07:00 | 5130.05 | 30.67 | 258.67 | 276.50 | 1080.85 | 20.87 | 85.17 | 263.83 |
February | 303.83 | 0.64 | 0.61 | 01-FEB-07:49 | 3016.51 | 25.57 | 194.00 | 267.83 | 950.11 | 15.67 | 0.00 | 237.17 |
March | 364.50 | 0.64 | 0.61 | 01-MAR-07:40 | 1455.73 | 11.86 | 7.50 | 313.67 | 815.73 | 16.26 | 0.00 | 281.83 |
April | 379.83 | 0.65 | 0.61 | 01-APR-07:10 | 970.59 | 10.73 | 0.00 | 320.17 | 598.55 | 15.38 | 0.00 | 283.17 |
May | 406.00 | 0.65 | 0.61 | 01-MAY-06:49 | 820.23 | 10.24 | 0.00 | 338.33 | 503.19 | 14.95 | 0.00 | 296.17 |
June | 386.67 | 0.65 | 0.61 | 01-JUN-06:00 | 814.68 | 9.84 | 0.00 | 325.33 | 487.37 | 14.45 | 0.00 | 277.50 |
July | 379.83 | 0.64 | 0.61 | 01-JUL-06:40 | 926.96 | 9.83 | 0.00 | 322.50 | 499.91 | 14.41 | 0.00 | 264.33 |
August | 372.50 | 0.65 | 0.61 | 01-AUG-06:49 | 1046.53 | 9.89 | 0.00 | 312.00 | 544.67 | 14.35 | 0.00 | 254.50 |
September | 344.33 | 0.64 | 0.61 | 01-SEP-06:00 | 1270.45 | 10.66 | 0.00 | 294.00 | 683.06 | 15.30 | 0.00 | 250.67 |
October | 347.33 | 0.65 | 0.61 | 01-OCT-06:00 | 2255.69 | 13.22 | 39.33 | 301.83 | 915.79 | 15.53 | 5.33 | 271.67 |
November | 317.83 | 0.64 | 0.61 | 01-NOV-07:19 | 7119.93 | 33.41 | 288.33 | 277.83 | 1123.69 | 18.15 | 45.17 | 263.67 |
December | 315.50 | 0.64 | 0.61 | 01-DEC-07:40 | 5415.75 | 32.21 | 273.33 | 276.17 | 1276.95 | 22.72 | 113.50 | 272.50 |
Annual Sum or Average | 4237.50 | 0.64 | 2368.49 | 16.61 | 1061.17 | 3626.17 | 768.69 | 16.35 | 249.17 | 3217.00 | ||
Minimum of Months | 303.83 | 0.64 | 0.61 | 814.68 | 9.83 | 0.00 | 267.83 | 487.37 | 14.35 | 0.00 | 237.17 | |
Maximum of Months | 406.00 | 0.65 | 0.61 | 7119.93 | 33.41 | 288.33 | 338.33 | 1276.95 | 22.72 | 113.50 | 296.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.66 | 0.61 | 01-JAN-07:49 | 1401.92 | 15.60 | 84.33 | 251.83 | 733.15 | 15.14 | 55.17 | 201.00 |
February | 303.83 | 0.65 | 0.61 | 01-FEB-07:49 | 1742.61 | 15.21 | 75.33 | 245.67 | 968.45 | 16.85 | 70.00 | 201.83 |
March | 364.50 | 0.64 | 0.61 | 01-MAR-07:40 | 1697.60 | 12.81 | 57.83 | 304.83 | 872.79 | 11.71 | 2.83 | 267.33 |
April | 379.83 | 0.65 | 0.61 | 01-APR-06:49 | 2033.91 | 8.42 | 0.00 | 314.83 | 1117.79 | 10.77 | 0.00 | 282.50 |
May | 406.00 | 0.64 | 0.61 | 01-MAY-06:10 | 2100.19 | 8.45 | 0.00 | 344.33 | 827.26 | 10.77 | 0.00 | 305.17 |
June | 386.67 | 0.65 | 0.61 | 01-JUN-06:40 | 1728.87 | 8.66 | 0.00 | 328.33 | 712.17 | 10.73 | 0.00 | 283.50 |
July | 379.83 | 0.64 | 0.61 | 01-JUL-06:10 | 1389.78 | 9.10 | 0.00 | 327.17 | 635.10 | 10.93 | 0.00 | 264.00 |
August | 372.50 | 0.65 | 0.61 | 01-AUG-06:19 | 1272.50 | 9.07 | 0.00 | 311.00 | 658.83 | 10.81 | 0.00 | 251.17 |
September | 344.33 | 0.65 | 0.61 | 01-SEP-06:49 | 1432.36 | 9.82 | 8.50 | 288.17 | 740.98 | 11.49 | 5.50 | 237.00 |
October | 347.33 | 0.65 | 0.61 | 01-OCT-06:49 | 1572.48 | 14.64 | 81.83 | 283.50 | 797.34 | 14.52 | 55.50 | 244.17 |
November | 317.83 | 0.65 | 0.61 | 01-NOV-07:10 | 1329.36 | 13.75 | 59.00 | 253.67 | 731.65 | 15.56 | 56.50 | 214.67 |
December | 315.50 | 0.66 | 0.61 | 01-DEC-07:40 | 1464.61 | 16.15 | 87.83 | 247.33 | 822.19 | 17.81 | 79.83 | 210.17 |
Annual Sum or Average | 4237.50 | 0.65 | 1608.38 | 11.57 | 454.67 | 3500.67 | 800.71 | 12.88 | 325.33 | 2962.50 | ||
Minimum of Months | 303.83 | 0.64 | 0.61 | 1272.50 | 8.42 | 0.00 | 245.67 | 635.10 | 10.73 | 0.00 | 201.00 | |
Maximum of Months | 406.00 | 0.66 | 0.61 | 2100.19 | 16.15 | 87.83 | 344.33 | 1117.79 | 17.81 | 79.83 | 305.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.67 | 0.61 | 01-JAN-08:39 | 441.09 | 0.00 | 0.00 | 221.50 | 288.57 | 0.00 | 0.00 | 116.67 |
February | 303.83 | 0.66 | 0.61 | 01-FEB-08:20 | 511.05 | 0.00 | 0.00 | 234.33 | 332.25 | 0.00 | 0.00 | 152.83 |
March | 364.50 | 0.64 | 0.61 | 01-MAR-07:00 | 606.20 | 0.00 | 0.00 | 300.33 | 392.55 | 0.00 | 0.00 | 241.00 |
April | 379.83 | 0.65 | 0.61 | 01-APR-07:10 | 655.23 | 0.00 | 0.00 | 324.83 | 430.59 | 0.00 | 0.00 | 282.33 |
May | 406.00 | 0.64 | 0.61 | 01-MAY-06:30 | 787.27 | 0.00 | 0.00 | 356.17 | 486.43 | 0.00 | 0.00 | 325.00 |
June | 386.67 | 0.64 | 0.61 | 01-JUN-06:49 | 879.81 | 0.00 | 0.00 | 340.50 | 515.22 | 0.00 | 0.00 | 304.33 |
July | 379.83 | 0.64 | 0.61 | 01-JUL-06:19 | 903.51 | 0.00 | 0.00 | 334.17 | 490.83 | 0.00 | 0.00 | 281.33 |
August | 372.50 | 0.64 | 0.61 | 01-AUG-06:40 | 809.72 | 0.00 | 0.00 | 315.33 | 439.36 | 0.00 | 0.00 | 253.50 |
September | 344.33 | 0.65 | 0.61 | 01-SEP-06:00 | 695.82 | 0.00 | 0.00 | 289.00 | 404.84 | 0.00 | 0.00 | 220.83 |
October | 347.33 | 0.66 | 0.61 | 01-OCT-07:19 | 533.66 | 0.00 | 0.00 | 276.50 | 355.31 | 0.00 | 0.00 | 205.67 |
November | 317.83 | 0.66 | 0.61 | 01-NOV-07:49 | 448.06 | 0.00 | 0.00 | 233.00 | 312.52 | 0.00 | 0.00 | 144.17 |
December | 315.50 | 0.67 | 0.61 | 01-DEC-08:20 | 432.98 | 0.00 | 0.00 | 219.33 | 286.65 | 0.00 | 0.00 | 103.33 |
Annual Sum or Average | 4237.50 | 0.65 | 654.76 | 0.00 | 0.00 | 3445.00 | 400.97 | 0.00 | 0.00 | 2631.00 | ||
Minimum of Months | 303.83 | 0.64 | 0.61 | 432.98 | 0.00 | 0.00 | 219.33 | 286.65 | 0.00 | 0.00 | 103.33 | |
Maximum of Months | 406.00 | 0.67 | 0.61 | 903.51 | 0.00 | 0.00 | 356.17 | 515.22 | 0.00 | 0.00 | 325.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.66 | 0.61 | 01-JAN-08:50 | 1406.70 | 15.58 | 82.83 | 249.50 | 761.98 | 16.83 | 72.00 | 204.17 |
February | 303.83 | 0.65 | 0.61 | 01-FEB-08:39 | 1656.77 | 15.12 | 77.00 | 246.67 | 681.65 | 14.81 | 44.33 | 205.50 |
March | 364.50 | 0.64 | 0.61 | 01-MAR-08:09 | 1651.00 | 12.76 | 57.33 | 305.50 | 845.71 | 11.66 | 1.83 | 268.50 |
April | 379.83 | 0.65 | 0.61 | 01-APR-07:30 | 1870.60 | 8.42 | 0.00 | 318.83 | 964.50 | 10.78 | 0.00 | 283.17 |
May | 406.00 | 0.65 | 0.61 | 01-MAY-07:10 | 1792.11 | 8.45 | 0.00 | 341.17 | 960.72 | 10.75 | 0.00 | 304.50 |
June | 386.67 | 0.65 | 0.61 | 01-JUN-07:10 | 1794.68 | 8.64 | 0.00 | 329.67 | 741.16 | 10.74 | 0.00 | 288.33 |
July | 379.83 | 0.64 | 0.61 | 01-JUL-06:00 | 1347.38 | 9.13 | 0.00 | 324.50 | 623.83 | 10.95 | 0.00 | 268.17 |
August | 372.50 | 0.65 | 0.61 | 01-AUG-07:10 | 1258.54 | 9.05 | 0.00 | 310.17 | 643.06 | 10.78 | 0.00 | 252.83 |
September | 344.33 | 0.64 | 0.61 | 01-SEP-07:30 | 1405.39 | 9.87 | 8.50 | 290.00 | 717.02 | 11.55 | 5.50 | 240.33 |
October | 347.33 | 0.65 | 0.61 | 01-OCT-07:30 | 1689.90 | 14.87 | 85.00 | 280.33 | 868.71 | 14.44 | 54.17 | 246.00 |
November | 317.83 | 0.65 | 0.61 | 01-NOV-07:00 | 1476.23 | 15.84 | 85.00 | 256.83 | 739.90 | 15.26 | 55.00 | 216.67 |
December | 315.50 | 0.65 | 0.61 | 01-DEC-08:20 | 1287.98 | 16.29 | 87.33 | 251.67 | 667.01 | 15.64 | 56.33 | 208.50 |
Annual Sum or Average | 4237.50 | 0.65 | 1560.70 | 11.74 | 483.00 | 3504.83 | 772.25 | 12.67 | 289.17 | 2986.67 | ||
Minimum of Months | 303.83 | 0.64 | 0.61 | 1258.54 | 8.42 | 0.00 | 246.67 | 623.83 | 10.74 | 0.00 | 204.17 | |
Maximum of Months | 406.00 | 0.66 | 0.61 | 1870.60 | 16.29 | 87.33 | 341.17 | 964.50 | 16.83 | 72.00 | 304.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.64 | 0.61 | 01-JAN-07:00 | 5129.79 | 30.66 | 258.67 | 276.50 | 1082.07 | 20.86 | 85.17 | 263.83 |
February | 303.83 | 0.64 | 0.61 | 01-FEB-07:49 | 3017.09 | 25.55 | 194.00 | 267.83 | 951.25 | 15.65 | 0.00 | 237.33 |
March | 364.50 | 0.64 | 0.61 | 01-MAR-07:40 | 1456.41 | 11.82 | 7.50 | 313.67 | 816.67 | 16.24 | 0.00 | 281.83 |
April | 379.83 | 0.65 | 0.61 | 01-APR-07:10 | 970.87 | 10.69 | 0.00 | 320.17 | 599.12 | 15.37 | 0.00 | 283.33 |
May | 406.00 | 0.65 | 0.61 | 01-MAY-06:49 | 820.44 | 10.20 | 0.00 | 338.33 | 503.68 | 14.93 | 0.00 | 296.17 |
June | 386.67 | 0.65 | 0.61 | 01-JUN-06:00 | 814.96 | 9.80 | 0.00 | 325.33 | 487.88 | 14.43 | 0.00 | 277.67 |
July | 379.83 | 0.64 | 0.61 | 01-JUL-06:40 | 927.68 | 9.80 | 0.00 | 322.50 | 500.61 | 14.39 | 0.00 | 265.00 |
August | 372.50 | 0.65 | 0.61 | 01-AUG-06:49 | 1047.44 | 9.85 | 0.00 | 312.00 | 545.51 | 14.34 | 0.00 | 254.67 |
September | 344.33 | 0.64 | 0.61 | 01-SEP-06:00 | 1271.35 | 10.62 | 0.00 | 294.00 | 684.03 | 15.28 | 0.00 | 250.67 |
October | 347.33 | 0.65 | 0.61 | 01-OCT-06:00 | 2256.24 | 13.18 | 39.33 | 301.83 | 916.80 | 15.52 | 5.33 | 271.67 |
November | 317.83 | 0.64 | 0.61 | 01-NOV-07:19 | 7119.82 | 33.40 | 288.33 | 277.83 | 1124.81 | 18.13 | 45.17 | 263.67 |
December | 315.50 | 0.64 | 0.61 | 01-DEC-07:40 | 5415.31 | 32.19 | 273.33 | 276.17 | 1278.23 | 22.71 | 113.50 | 272.50 |
Annual Sum or Average | 4237.50 | 0.64 | 2368.86 | 16.58 | 1061.17 | 3626.17 | 769.57 | 16.33 | 249.17 | 3218.33 | ||
Minimum of Months | 303.83 | 0.64 | 0.61 | 814.96 | 9.80 | 0.00 | 267.83 | 487.88 | 14.34 | 0.00 | 237.33 | |
Maximum of Months | 406.00 | 0.65 | 0.61 | 7119.82 | 33.40 | 288.33 | 338.33 | 1278.23 | 22.71 | 113.50 | 296.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.66 | 0.61 | 01-JAN-07:49 | 1401.67 | 15.59 | 84.33 | 251.83 | 733.67 | 15.13 | 55.17 | 201.33 |
February | 303.83 | 0.65 | 0.61 | 01-FEB-07:49 | 1742.37 | 15.20 | 75.33 | 245.50 | 969.07 | 16.85 | 70.00 | 201.83 |
March | 364.50 | 0.64 | 0.61 | 01-MAR-07:40 | 1697.34 | 12.79 | 57.83 | 304.83 | 873.48 | 11.70 | 2.83 | 267.33 |
April | 379.83 | 0.65 | 0.61 | 01-APR-06:49 | 2033.75 | 8.41 | 0.00 | 314.83 | 1118.43 | 10.76 | 0.00 | 282.67 |
May | 406.00 | 0.64 | 0.61 | 01-MAY-06:10 | 2100.13 | 8.44 | 0.00 | 344.33 | 827.95 | 10.76 | 0.00 | 305.17 |
June | 386.67 | 0.65 | 0.61 | 01-JUN-06:40 | 1729.09 | 8.64 | 0.00 | 328.33 | 712.90 | 10.72 | 0.00 | 283.67 |
July | 379.83 | 0.64 | 0.61 | 01-JUL-06:10 | 1390.42 | 9.09 | 0.00 | 327.17 | 635.96 | 10.92 | 0.00 | 264.33 |
August | 372.50 | 0.65 | 0.61 | 01-AUG-06:19 | 1273.19 | 9.06 | 0.00 | 311.00 | 659.70 | 10.81 | 0.00 | 251.17 |
September | 344.33 | 0.65 | 0.61 | 01-SEP-06:49 | 1432.68 | 9.81 | 8.50 | 288.17 | 741.81 | 11.48 | 5.50 | 237.17 |
October | 347.33 | 0.65 | 0.61 | 01-OCT-06:49 | 1572.17 | 14.63 | 81.83 | 283.50 | 797.95 | 14.51 | 55.50 | 244.17 |
November | 317.83 | 0.65 | 0.61 | 01-NOV-07:10 | 1329.00 | 13.74 | 59.00 | 253.67 | 732.15 | 15.55 | 56.50 | 214.67 |
December | 315.50 | 0.66 | 0.61 | 01-DEC-07:40 | 1464.34 | 16.14 | 87.83 | 247.33 | 822.71 | 17.80 | 79.83 | 210.17 |
Annual Sum or Average | 4237.50 | 0.65 | 1608.39 | 11.55 | 454.67 | 3500.50 | 801.39 | 12.87 | 325.33 | 2963.67 | ||
Minimum of Months | 303.83 | 0.64 | 0.61 | 1273.19 | 8.41 | 0.00 | 245.50 | 635.96 | 10.72 | 0.00 | 201.33 | |
Maximum of Months | 406.00 | 0.66 | 0.61 | 2100.13 | 16.14 | 87.83 | 344.33 | 1118.43 | 17.80 | 79.83 | 305.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.67 | 0.61 | 01-JAN-08:39 | 440.97 | 0.00 | 0.00 | 221.50 | 288.80 | 0.00 | 0.00 | 117.17 |
February | 303.83 | 0.66 | 0.61 | 01-FEB-08:20 | 510.95 | 0.00 | 0.00 | 234.33 | 332.51 | 0.00 | 0.00 | 153.33 |
March | 364.50 | 0.64 | 0.61 | 01-MAR-07:00 | 606.11 | 0.00 | 0.00 | 300.33 | 392.86 | 0.00 | 0.00 | 241.00 |
April | 379.83 | 0.65 | 0.61 | 01-APR-07:10 | 655.12 | 0.00 | 0.00 | 324.83 | 430.92 | 0.00 | 0.00 | 282.33 |
May | 406.00 | 0.64 | 0.61 | 01-MAY-06:30 | 787.31 | 0.00 | 0.00 | 356.17 | 486.87 | 0.00 | 0.00 | 325.00 |
June | 386.67 | 0.64 | 0.61 | 01-JUN-06:49 | 880.04 | 0.00 | 0.00 | 340.50 | 515.77 | 0.00 | 0.00 | 304.50 |
July | 379.83 | 0.64 | 0.61 | 01-JUL-06:19 | 904.08 | 0.00 | 0.00 | 334.17 | 491.50 | 0.00 | 0.00 | 281.67 |
August | 372.50 | 0.64 | 0.61 | 01-AUG-06:40 | 810.24 | 0.00 | 0.00 | 315.33 | 439.99 | 0.00 | 0.00 | 253.50 |
September | 344.33 | 0.65 | 0.61 | 01-SEP-06:00 | 696.04 | 0.00 | 0.00 | 289.00 | 405.31 | 0.00 | 0.00 | 221.00 |
October | 347.33 | 0.66 | 0.61 | 01-OCT-07:19 | 533.51 | 0.00 | 0.00 | 276.50 | 355.57 | 0.00 | 0.00 | 206.00 |
November | 317.83 | 0.66 | 0.61 | 01-NOV-07:49 | 447.82 | 0.00 | 0.00 | 233.00 | 312.70 | 0.00 | 0.00 | 144.33 |
December | 315.50 | 0.67 | 0.61 | 01-DEC-08:20 | 432.83 | 0.00 | 0.00 | 219.33 | 286.86 | 0.00 | 0.00 | 103.50 |
Annual Sum or Average | 4237.50 | 0.65 | 654.83 | 0.00 | 0.00 | 3445.00 | 401.36 | 0.00 | 0.00 | 2633.33 | ||
Minimum of Months | 303.83 | 0.64 | 0.61 | 432.83 | 0.00 | 0.00 | 219.33 | 286.86 | 0.00 | 0.00 | 103.50 | |
Maximum of Months | 406.00 | 0.67 | 0.61 | 904.08 | 0.00 | 0.00 | 356.17 | 515.77 | 0.00 | 0.00 | 325.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 319.33 | 0.66 | 0.61 | 01-JAN-08:50 | 1406.46 | 15.57 | 82.83 | 249.33 | 762.50 | 16.83 | 72.00 | 204.17 |
February | 303.83 | 0.65 | 0.61 | 01-FEB-08:39 | 1656.59 | 15.11 | 77.00 | 246.67 | 682.26 | 14.81 | 44.33 | 205.67 |
March | 364.50 | 0.64 | 0.61 | 01-MAR-08:09 | 1650.77 | 12.75 | 57.33 | 305.33 | 846.40 | 11.65 | 1.83 | 268.50 |
April | 379.83 | 0.65 | 0.61 | 01-APR-07:30 | 1870.45 | 8.41 | 0.00 | 318.83 | 965.12 | 10.77 | 0.00 | 283.17 |
May | 406.00 | 0.65 | 0.61 | 01-MAY-07:10 | 1792.07 | 8.44 | 0.00 | 341.17 | 961.41 | 10.74 | 0.00 | 304.83 |
June | 386.67 | 0.65 | 0.61 | 01-JUN-07:10 | 1794.84 | 8.62 | 0.00 | 329.67 | 741.91 | 10.73 | 0.00 | 288.33 |
July | 379.83 | 0.64 | 0.61 | 01-JUL-06:00 | 1348.05 | 9.11 | 0.00 | 324.50 | 624.69 | 10.94 | 0.00 | 268.33 |
August | 372.50 | 0.65 | 0.61 | 01-AUG-07:10 | 1259.24 | 9.04 | 0.00 | 310.17 | 643.93 | 10.77 | 0.00 | 253.00 |
September | 344.33 | 0.64 | 0.61 | 01-SEP-07:30 | 1405.74 | 9.86 | 8.50 | 290.00 | 717.85 | 11.54 | 5.50 | 240.50 |
October | 347.33 | 0.65 | 0.61 | 01-OCT-07:30 | 1689.70 | 14.86 | 85.00 | 280.33 | 869.31 | 14.44 | 54.17 | 246.00 |
November | 317.83 | 0.65 | 0.61 | 01-NOV-07:00 | 1475.88 | 15.83 | 85.00 | 256.83 | 740.39 | 15.25 | 55.00 | 216.83 |
December | 315.50 | 0.65 | 0.61 | 01-DEC-08:20 | 1287.74 | 16.28 | 87.33 | 251.33 | 667.52 | 15.64 | 56.33 | 208.50 |
Annual Sum or Average | 4237.50 | 0.65 | 1560.73 | 11.73 | 483.00 | 3504.17 | 772.92 | 12.66 | 289.17 | 2987.83 | ||
Minimum of Months | 303.83 | 0.64 | 0.61 | 1259.24 | 8.41 | 0.00 | 246.67 | 624.69 | 10.73 | 0.00 | 204.17 | |
Maximum of Months | 406.00 | 0.66 | 0.61 | 1870.45 | 16.28 | 87.33 | 341.17 | 965.12 | 16.83 | 72.00 | 304.83 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.163125E+09 | 5300.56 | 05-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 807832.26 | 869.18 | 02-FEB-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 35436036.95 | 4113.58 | 23-DEC-05:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.199369E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.163125E+09 | 5300.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.342266E+10 | 67608.38 | 05-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.137570E+09 | 22992.67 | 02-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 7053.43 | 11.76 | 25-SEP-10:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.716610E+09 | 50791.97 | 23-DEC-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.427685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.342266E+10 | 67608.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.589766E+09 | 59170.07 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3257951.78 | 1112.19 | 11-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.104670E+09 | 15584.92 | 23-DEC-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.697694E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.589766E+09 | 59170.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.164769E+09 | 17992.14 | 03-JAN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 14417895.39 | 8183.39 | 11-FEB-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 25818644.69 | 8808.39 | 23-DEC-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.205005E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.164769E+09 | 17992.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 91243135.80 | 10268.80 | 03-JAN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4218789.12 | 1116.78 | 11-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 9240750.83 | 2229.30 | 23-DEC-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.104703E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 91243135.80 | 10268.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.143374E+10 | 13444.84 | 02-JAN-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.153654E+09 | 7484.63 | 02-FEB-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1339827.82 | 1020.22 | 27-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.376860E+09 | 12397.55 | 23-DEC-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.196559E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.143374E+10 | 13444.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.602584E+09 | 71048.76 | 02-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 600876.17 | 714.08 | 23-DEC-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.603185E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.602584E+09 | 71048.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.119920E+10 | 18539.34 | 02-JAN-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.225155E+09 | 18336.85 | 11-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 24347687.63 | 1992.46 | 27-NOV-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.594157E+09 | 18433.71 | 23-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.204286E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.119920E+10 | 18539.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.501868E+09 | 13091.14 | 02-JAN-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 90289200.33 | 12946.53 | 11-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 4152964.94 | 660.58 | 27-NOV-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.238042E+09 | 12990.88 | 21-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.834353E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.501868E+09 | 13091.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.397139E+09 | 18501.20 | 02-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 70122257.02 | 18354.92 | 11-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.103610E+09 | 16915.67 | 23-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.570872E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.397139E+09 | 18501.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.475303E+09 | 13197.94 | 02-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 86090789.85 | 13092.95 | 11-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 382650.66 | 110.12 | 25-NOV-07:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.191731E+09 | 11577.89 | 23-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.753507E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.475303E+09 | 13197.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS HEATING COIL
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT HEATING COIL
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT HEATING COIL
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID HEATING COIL
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP HEATING COIL
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID_SUPPHEATCOIL
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.453706E+11 | 0.452951E+11 | 86484.70 | 18-JAN-06:03 | 72576.05 | 0.30 |
February | 0.00 | 0.00 | 0.643314E+11 | 0.642073E+11 | 103576.57 | 21-FEB-16:00 | 103576.57 | 0.48 |
March | 0.00 | 0.00 | 0.120624E+12 | 0.118666E+12 | 200178.88 | 29-MAR-05:03 | 143935.68 | 0.68 |
April | 0.00 | 0.00 | 0.177620E+12 | 0.170685E+12 | 249997.83 | 17-APR-05:03 | 175997.34 | 0.81 |
May | 0.00 | 0.00 | 0.217423E+12 | 0.184253E+12 | 277208.69 | 22-MAY-05:02 | 174612.19 | 0.83 |
June | 0.00 | 0.00 | 0.256762E+12 | 0.189662E+12 | 287729.18 | 26-JUN-05:02 | 169747.02 | 0.86 |
July | 0.00 | 0.00 | 0.297209E+12 | 0.183584E+12 | 299718.20 | 31-JUL-05:03 | 176172.27 | 0.87 |
August | 0.00 | 0.00 | 0.318655E+12 | 0.194049E+12 | 315682.45 | 28-AUG-05:04 | 175311.42 | 0.89 |
September | 0.00 | 0.00 | 0.221857E+12 | 0.141278E+12 | 283436.53 | 05-SEP-05:02 | 169863.16 | 0.77 |
October | 0.00 | 0.00 | 0.148554E+12 | 0.131722E+12 | 253426.05 | 04-OCT-05:02 | 165376.78 | 0.75 |
November | 0.00 | 0.00 | 0.990074E+11 | 0.977505E+11 | 170716.22 | 10-NOV-06:02 | 122619.00 | 0.63 |
December | 0.00 | 0.00 | 0.660829E+11 | 0.660829E+11 | 101627.38 | 29-DEC-06:02 | 101627.38 | 0.40 |
Annual Sum or Average | 0.00 | 0.00 | 0.203350E+13 | 0.158723E+13 | 0.69 | |||
Minimum of Months | 0.00 | 0.00 | 0.453706E+11 | 0.452951E+11 | 86484.70 | 72576.05 | 0.30 | |
Maximum of Months | 0.00 | 0.00 | 0.318655E+12 | 0.194049E+12 | 315682.45 | 176172.27 | 0.89 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.316074E+12 | 0.315985E+12 | 826637.85 | 18-JAN-06:03 | 652604.61 | 0.27 |
February | 0.00 | 0.00 | 0.466977E+12 | 0.465988E+12 | 1273675.58 | 25-FEB-06:03 | 863622.00 | 0.43 |
March | 0.00 | 0.00 | 0.922597E+12 | 0.908900E+12 | 1917600.85 | 14-MAR-05:02 | 1439676.49 | 0.57 |
April | 0.00 | 0.00 | 0.137792E+13 | 0.132672E+13 | 2302218.55 | 26-APR-05:02 | 1523340.26 | 0.67 |
May | 0.00 | 0.00 | 0.199934E+13 | 0.168166E+13 | 2723695.48 | 24-MAY-03:02 | 1536009.70 | 0.80 |
June | 0.00 | 0.00 | 0.227613E+13 | 0.165161E+13 | 2847278.10 | 26-JUN-05:02 | 1578548.39 | 0.80 |
July | 0.00 | 0.00 | 0.250696E+13 | 0.147927E+13 | 2980871.43 | 27-JUL-03:02 | 1552684.26 | 0.77 |
August | 0.00 | 0.00 | 0.247813E+13 | 0.141234E+13 | 2892133.00 | 10-AUG-05:02 | 1597063.45 | 0.75 |
September | 0.00 | 0.00 | 0.192020E+13 | 0.120040E+13 | 2862700.79 | 09-SEP-05:03 | 1491498.15 | 0.68 |
October | 0.00 | 0.00 | 0.121278E+13 | 0.106898E+13 | 2437777.84 | 12-OCT-05:02 | 1448482.13 | 0.65 |
November | 0.00 | 0.00 | 0.725332E+12 | 0.716076E+12 | 1662271.15 | 09-NOV-06:02 | 1130449.78 | 0.55 |
December | 0.00 | 0.00 | 0.384513E+12 | 0.384513E+12 | 736826.41 | 29-DEC-06:02 | 736826.41 | 0.33 |
Annual Sum or Average | 0.00 | 0.00 | 0.165870E+14 | 0.126124E+14 | 0.61 | |||
Minimum of Months | 0.00 | 0.00 | 0.316074E+12 | 0.315985E+12 | 736826.41 | 652604.61 | 0.27 | |
Maximum of Months | 0.00 | 0.00 | 0.250696E+13 | 0.168166E+13 | 2980871.43 | 1597063.45 | 0.80 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.232183E+11 | 0.232183E+11 | 59605.80 | 12-JAN-15:00 | 59605.80 | 0.26 |
February | 0.00 | 0.00 | 0.412320E+11 | 0.411399E+11 | 111329.74 | 25-FEB-06:03 | 74963.49 | 0.41 |
March | 0.00 | 0.00 | 0.949783E+11 | 0.936886E+11 | 198865.85 | 14-MAR-05:02 | 148160.20 | 0.56 |
April | 0.00 | 0.00 | 0.156239E+12 | 0.150929E+12 | 248592.61 | 17-APR-05:02 | 172595.31 | 0.69 |
May | 0.00 | 0.00 | 0.229640E+12 | 0.196709E+12 | 294419.81 | 24-MAY-05:02 | 173170.27 | 0.82 |
June | 0.00 | 0.00 | 0.258883E+12 | 0.194715E+12 | 307109.39 | 22-JUN-05:02 | 187091.32 | 0.81 |
July | 0.00 | 0.00 | 0.276720E+12 | 0.170914E+12 | 342673.02 | 25-JUL-03:02 | 181778.09 | 0.79 |
August | 0.00 | 0.00 | 0.269569E+12 | 0.160250E+12 | 322552.24 | 10-AUG-05:02 | 180795.29 | 0.76 |
September | 0.00 | 0.00 | 0.207122E+12 | 0.132844E+12 | 313339.76 | 08-SEP-05:02 | 169863.66 | 0.70 |
October | 0.00 | 0.00 | 0.125099E+12 | 0.111623E+12 | 249817.80 | 04-OCT-05:02 | 163803.78 | 0.64 |
November | 0.00 | 0.00 | 0.673464E+11 | 0.669089E+11 | 152748.17 | 09-NOV-06:02 | 99836.80 | 0.53 |
December | 0.00 | 0.00 | 0.288834E+11 | 0.288834E+11 | 67394.81 | 01-DEC-15:00 | 67394.81 | 0.32 |
Annual Sum or Average | 0.00 | 0.00 | 0.177893E+13 | 0.137182E+13 | 0.61 | |||
Minimum of Months | 0.00 | 0.00 | 0.232183E+11 | 0.232183E+11 | 59605.80 | 59605.80 | 0.26 | |
Maximum of Months | 0.00 | 0.00 | 0.276720E+12 | 0.196709E+12 | 342673.02 | 187091.32 | 0.82 |
Report: CoilReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.508292E+11 | 0.507519E+11 | 98805.55 | 17-JAN-04:02 | 85660.86 | 0.31 |
February | 0.00 | 0.00 | 0.523339E+11 | 0.522820E+11 | 116353.47 | 27-FEB-04:02 | 84736.77 | 0.45 |
March | 0.00 | 0.00 | 0.727924E+11 | 0.725662E+11 | 135638.78 | 13-MAR-03:02 | 94169.09 | 0.54 |
April | 0.00 | 0.00 | 0.849268E+11 | 0.829803E+11 | 158468.71 | 27-APR-03:02 | 96542.15 | 0.52 |
May | 0.00 | 0.00 | 0.109000E+12 | 0.968889E+11 | 184999.95 | 22-MAY-03:02 | 91230.48 | 0.60 |
June | 0.00 | 0.00 | 0.128552E+12 | 0.100906E+12 | 213420.58 | 26-JUN-03:02 | 86799.52 | 0.63 |
July | 0.00 | 0.00 | 0.150085E+12 | 0.100371E+12 | 224035.41 | 30-JUL-19:40 | 91119.37 | 0.62 |
August | 0.00 | 0.00 | 0.168700E+12 | 0.109043E+12 | 240745.28 | 27-AUG-14:59 | 97063.34 | 0.67 |
September | 0.00 | 0.00 | 0.132492E+12 | 0.931082E+11 | 217368.28 | 17-SEP-20:17 | 102940.02 | 0.64 |
October | 0.00 | 0.00 | 0.951481E+11 | 0.883773E+11 | 166534.52 | 04-OCT-03:02 | 94188.97 | 0.63 |
November | 0.00 | 0.00 | 0.728296E+11 | 0.725483E+11 | 121054.96 | 09-NOV-06:02 | 80524.94 | 0.57 |
December | 0.00 | 0.00 | 0.582386E+11 | 0.582313E+11 | 92460.77 | 29-DEC-04:02 | 88388.53 | 0.38 |
Annual Sum or Average | 0.00 | 0.00 | 0.117593E+13 | 0.978054E+12 | 0.55 | |||
Minimum of Months | 0.00 | 0.00 | 0.508292E+11 | 0.507519E+11 | 92460.77 | 80524.94 | 0.31 | |
Maximum of Months | 0.00 | 0.00 | 0.168700E+12 | 0.109043E+12 | 240745.28 | 102940.02 | 0.67 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.337411E+12 | 0.323791E+12 | 131369.15 | 17-JAN-15:00 | 124984.78 | 0.00 |
February | 0.00 | 0.00 | 0.532790E+12 | 0.515874E+12 | 225101.03 | 24-FEB-17:00 | 219076.15 | 0.00 |
March | 0.00 | 0.00 | 0.835439E+12 | 0.821376E+12 | 395738.57 | 31-MAR-24:00 | 393445.81 | 0.00 |
April | 0.00 | 0.00 | 0.103387E+13 | 0.102764E+13 | 409642.52 | 22-APR-17:00 | 401408.45 | 0.00 |
May | 0.00 | 0.00 | 0.362309E+12 | 0.345365E+12 | 226062.27 | 31-MAY-23:03 | 212107.23 | 0.00 |
June | 0.00 | 0.00 | 0.598264E+12 | 0.572403E+12 | 318207.61 | 30-JUN-23:03 | 306257.71 | 0.00 |
July | 0.00 | 0.00 | 0.873669E+12 | 0.837004E+12 | 401295.33 | 31-JUL-24:00 | 389769.04 | 0.00 |
August | 0.00 | 0.00 | 0.109901E+13 | 0.106349E+13 | 421246.85 | 10-AUG-14:00 | 401433.81 | 0.00 |
September | 0.00 | 0.00 | 0.366104E+12 | 0.334825E+12 | 227388.26 | 30-SEP-23:03 | 212883.38 | 0.00 |
October | 0.00 | 0.00 | 0.601447E+12 | 0.585009E+12 | 310615.61 | 31-OCT-24:00 | 302108.06 | 0.00 |
November | 0.00 | 0.00 | 0.817191E+12 | 0.797581E+12 | 321426.53 | 24-NOV-08:15 | 307251.90 | 0.00 |
December | 0.00 | 0.00 | 0.109883E+13 | 0.106407E+13 | 421933.43 | 22-DEC-06:03 | 396277.65 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.855633E+13 | 0.828842E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.337411E+12 | 0.323791E+12 | 131369.15 | 124984.78 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.109901E+13 | 0.106407E+13 | 421933.43 | 401433.81 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.496405E+10 | 0.481944E+10 | 2461.85 | 12-JAN-17:00 | 2332.68 | 0.00 |
February | 0.00 | 0.00 | 0.956863E+10 | 0.934264E+10 | 4507.57 | 21-FEB-17:00 | 4358.35 | 0.00 |
March | 0.00 | 0.00 | 0.161863E+11 | 0.158562E+11 | 7782.42 | 31-MAR-24:00 | 7681.64 | 0.00 |
April | 0.00 | 0.00 | 0.209044E+11 | 0.205976E+11 | 8531.71 | 17-APR-01:55 | 8274.66 | 0.00 |
May | 0.00 | 0.00 | 0.718480E+10 | 0.652195E+10 | 4655.66 | 31-MAY-23:03 | 4042.65 | 0.00 |
June | 0.00 | 0.00 | 0.123015E+11 | 0.112179E+11 | 6544.35 | 30-JUN-23:03 | 6031.78 | 0.00 |
July | 0.00 | 0.00 | 0.181648E+11 | 0.165539E+11 | 8536.99 | 31-JUL-23:03 | 7741.65 | 0.00 |
August | 0.00 | 0.00 | 0.227886E+11 | 0.210995E+11 | 8774.97 | 10-AUG-14:10 | 7955.55 | 0.00 |
September | 0.00 | 0.00 | 0.731155E+10 | 0.604316E+10 | 4619.85 | 30-SEP-23:03 | 3997.36 | 0.00 |
October | 0.00 | 0.00 | 0.116850E+11 | 0.110668E+11 | 5960.59 | 31-OCT-23:10 | 5711.11 | 0.00 |
November | 0.00 | 0.00 | 0.155412E+11 | 0.152313E+11 | 6553.50 | 08-NOV-16:40 | 6300.45 | 0.00 |
December | 0.00 | 0.00 | 0.205124E+11 | 0.203422E+11 | 8226.95 | 28-DEC-17:00 | 8066.52 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.167113E+12 | 0.158693E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.496405E+10 | 0.481944E+10 | 2461.85 | 2332.68 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.227886E+11 | 0.210995E+11 | 8774.97 | 8274.66 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.376245E+11 | 0.362624E+11 | 22908.01 | 12-JAN-17:00 | 21638.91 | 0.00 |
February | 0.00 | 0.00 | 0.856789E+11 | 0.834441E+11 | 42571.53 | 22-FEB-17:00 | 41046.36 | 0.00 |
March | 0.00 | 0.00 | 0.153034E+12 | 0.149743E+12 | 75049.05 | 31-MAR-24:00 | 74036.85 | 0.00 |
April | 0.00 | 0.00 | 0.198255E+12 | 0.195176E+12 | 80291.95 | 12-APR-16:00 | 78025.38 | 0.00 |
May | 0.00 | 0.00 | 0.677233E+11 | 0.611764E+11 | 44631.54 | 31-MAY-23:03 | 38359.29 | 0.00 |
June | 0.00 | 0.00 | 0.117176E+12 | 0.106404E+12 | 63260.26 | 30-JUN-23:03 | 58093.40 | 0.00 |
July | 0.00 | 0.00 | 0.173140E+12 | 0.157083E+12 | 81503.66 | 31-JUL-23:03 | 73553.17 | 0.00 |
August | 0.00 | 0.00 | 0.216311E+12 | 0.199372E+12 | 83476.87 | 10-AUG-14:10 | 75342.21 | 0.00 |
September | 0.00 | 0.00 | 0.687551E+11 | 0.562298E+11 | 44822.67 | 30-SEP-23:03 | 38474.61 | 0.00 |
October | 0.00 | 0.00 | 0.110166E+12 | 0.104033E+12 | 56366.39 | 31-OCT-23:10 | 53807.87 | 0.00 |
November | 0.00 | 0.00 | 0.144678E+12 | 0.141592E+12 | 62400.34 | 08-NOV-16:50 | 59802.51 | 0.00 |
December | 0.00 | 0.00 | 0.187690E+12 | 0.185987E+12 | 77874.40 | 28-DEC-17:00 | 76278.70 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.156023E+13 | 0.147650E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.376245E+11 | 0.362624E+11 | 22908.01 | 21638.91 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.216311E+12 | 0.199372E+12 | 83476.87 | 78025.38 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.226246E+10 | 0.213883E+10 | 2298.72 | 12-JAN-17:00 | 2163.49 | 0.00 |
February | 0.00 | 0.00 | 0.786748E+10 | 0.763117E+10 | 4312.75 | 22-FEB-17:00 | 4152.27 | 0.00 |
March | 0.00 | 0.00 | 0.151537E+11 | 0.148056E+11 | 7466.29 | 31-MAR-24:00 | 7357.83 | 0.00 |
April | 0.00 | 0.00 | 0.200188E+11 | 0.196932E+11 | 8283.88 | 16-APR-20:54 | 8000.82 | 0.00 |
May | 0.00 | 0.00 | 0.703734E+10 | 0.636088E+10 | 4452.01 | 31-MAY-23:03 | 3811.14 | 0.00 |
June | 0.00 | 0.00 | 0.119715E+11 | 0.108733E+11 | 6391.36 | 30-JUN-23:03 | 5866.14 | 0.00 |
July | 0.00 | 0.00 | 0.175570E+11 | 0.159304E+11 | 8395.53 | 31-JUL-23:03 | 7573.77 | 0.00 |
August | 0.00 | 0.00 | 0.220047E+11 | 0.202827E+11 | 8537.75 | 10-AUG-14:10 | 7709.19 | 0.00 |
September | 0.00 | 0.00 | 0.698050E+10 | 0.570770E+10 | 4501.53 | 30-SEP-23:03 | 3858.03 | 0.00 |
October | 0.00 | 0.00 | 0.109526E+11 | 0.103210E+11 | 5524.99 | 31-OCT-23:10 | 5257.24 | 0.00 |
November | 0.00 | 0.00 | 0.139720E+11 | 0.136458E+11 | 6296.21 | 08-NOV-16:40 | 6037.44 | 0.00 |
December | 0.00 | 0.00 | 0.175460E+11 | 0.173600E+11 | 7798.23 | 28-DEC-17:00 | 7631.12 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.153324E+12 | 0.144751E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.226246E+10 | 0.213883E+10 | 2298.72 | 2163.49 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.220047E+11 | 0.202827E+11 | 8537.75 | 8000.82 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 3288.70 | 207559.90 | 02-JAN-06:13 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 315.46 | 113461.85 | 11-FEB-06:02 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 01-APR-00:03 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 9.89 | 25-SEP-10:20 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.65 | 2741.34 | 27-NOV-06:05 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 887.88 | 99383.19 | 23-DEC-06:03 |
Annual Sum or Average | 0.00 | 379.80 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 3288.70 | 207559.90 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 338362.96 | 1484294.89 | 12-JAN-14:10 | 4.37 | 58557.25 | 09-JAN-04:03 |
February | 471508.37 | 1590596.31 | 17-FEB-16:10 | 145.26 | 244744.87 | 20-FEB-01:40 |
March | 707682.66 | 2178349.57 | 14-MAR-05:02 | 1.20 | 16737.73 | 04-MAR-22:33 |
April | 966365.79 | 3078479.26 | 17-APR-05:03 | 0.00 | 0.00 | 01-APR-00:03 |
May | 1199020.52 | 3202931.04 | 18-MAY-05:02 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 1306546.33 | 3517870.50 | 27-JUN-05:02 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 1348206.12 | 3502432.09 | 06-JUL-05:02 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 1330200.70 | 3703129.11 | 07-AUG-05:03 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 1097778.47 | 3578453.37 | 05-SEP-05:04 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 838961.74 | 3189625.69 | 04-OCT-05:02 | 10.69 | 69135.39 | 28-OCT-19:33 |
November | 601816.48 | 1849670.02 | 10-NOV-06:04 | 10.56 | 74720.81 | 19-NOV-08:13 |
December | 406212.99 | 1581393.77 | 01-DEC-14:30 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 886590.48 | 13.39 | ||||
Minimum of Months | 338362.96 | 1484294.89 | 0.00 | 0.00 | ||
Maximum of Months | 1348206.12 | 3703129.11 | 145.26 | 244744.87 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 211418.16 | 1659882.23 | 18-JAN-06:03 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 322634.06 | 2536869.36 | 25-FEB-06:03 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 530950.49 | 3593536.10 | 14-MAR-05:02 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 761685.85 | 4120582.58 | 17-APR-05:02 | 0.00 | 0.00 | 01-APR-00:03 |
May | 1006300.65 | 4842933.64 | 24-MAY-05:02 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 1172891.89 | 5117348.16 | 27-JUN-05:02 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 1245830.12 | 5127218.35 | 18-JUL-05:02 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 1243429.77 | 5066309.31 | 09-AUG-05:02 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 1004343.59 | 5005870.77 | 06-SEP-05:02 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 657864.09 | 4702443.16 | 04-OCT-05:02 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 452532.23 | 3225268.09 | 09-NOV-06:02 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 261652.31 | 1665391.87 | 13-DEC-06:03 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 741529.24 | 0.00 | ||||
Minimum of Months | 211418.16 | 1659882.23 | 0.00 | 0.00 | ||
Maximum of Months | 1245830.12 | 5127218.35 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 221478.88 | 581796.75 | 12-JAN-15:00 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 497445.86 | 1014514.91 | 22-FEB-15:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 963295.28 | 1757316.38 | 28-MAR-15:20 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 1582935.43 | 2218641.77 | 15-APR-15:00 | 0.00 | 0.00 | 01-APR-00:03 |
May | 1117280.36 | 1775093.23 | 01-MAY-15:00 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 1409231.00 | 2060731.80 | 08-JUN-16:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 1551733.28 | 2083446.05 | 07-JUL-15:00 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 1664286.44 | 2080587.03 | 07-AUG-15:00 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 897172.92 | 1393224.69 | 17-SEP-20:00 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 902837.86 | 1572825.95 | 02-OCT-15:00 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 818829.36 | 1420749.50 | 08-NOV-15:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 785993.58 | 1320185.87 | 28-DEC-14:20 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 1037226.36 | 0.00 | ||||
Minimum of Months | 221478.88 | 581796.75 | 0.00 | 0.00 | ||
Maximum of Months | 1664286.44 | 2218641.77 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 12736.51 | 41939.93 | 18-JAN-12:50 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 12564.27 | 41692.37 | 01-FEB-12:40 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 12460.74 | 39951.39 | 01-MAR-12:40 |
April | 0.00 | 0.00 | 01-APR-00:03 | 10710.40 | 36287.29 | 03-APR-11:40 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 9907.20 | 32621.48 | 01-MAY-12:00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9217.51 | 29011.23 | 01-JUN-11:50 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 8270.58 | 26824.63 | 03-JUL-11:30 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 9179.52 | 28583.78 | 31-AUG-11:40 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 9467.79 | 31745.88 | 29-SEP-11:50 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 10514.71 | 35938.15 | 31-OCT-11:20 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 11730.58 | 39428.93 | 30-NOV-12:30 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12147.66 | 41507.46 | 29-DEC-13:00 |
Annual Sum or Average | 0.00 | 10732.36 | ||||
Minimum of Months | 0.00 | 0.00 | 8270.58 | 26824.63 | ||
Maximum of Months | 0.00 | 0.00 | 12736.51 | 41939.93 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 198837.52 | 1084391.75 | 25-JAN-16:10 | 2946.31 | 144923.88 | 04-JAN-07:00 |
February | 309851.23 | 1223385.09 | 22-FEB-15:30 | 1249.39 | 132853.29 | 01-FEB-06:50 |
March | 561243.25 | 3213183.62 | 10-MAR-17:00 | 329.85 | 67291.58 | 02-MAR-04:30 |
April | 1047093.08 | 4907954.29 | 18-APR-14:00 | 173.94 | 40475.78 | 10-APR-01:15 |
May | 2208387.84 | 6628981.06 | 17-MAY-15:30 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 3317457.73 | 7696082.91 | 27-JUN-05:04 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 4206224.90 | 7783576.19 | 18-JUL-05:04 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 4236997.61 | 7525760.18 | 28-AUG-14:40 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 2941726.81 | 7293616.55 | 14-SEP-15:30 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 928113.33 | 4676191.28 | 04-OCT-05:04 | 33.74 | 23605.04 | 09-OCT-04:30 |
November | 443314.24 | 2660791.00 | 09-NOV-11:20 | 577.35 | 75347.51 | 27-NOV-05:45 |
December | 242173.05 | 1128014.71 | 01-DEC-16:00 | 1922.03 | 149588.97 | 30-DEC-05:30 |
Annual Sum or Average | 1729328.47 | 601.95 | ||||
Minimum of Months | 198837.52 | 1084391.75 | 0.00 | 0.00 | ||
Maximum of Months | 4236997.61 | 7783576.19 | 2946.31 | 149588.97 |
Report: FanReportMonthly
For: CAV_BAS FAN
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.153726E+11 | 0.86 | 9441.50 | 01-JAN-00:10 | 1.42 |
February | 0.136259E+11 | 0.84 | 9441.50 | 01-FEB-04:05 | 1.42 |
March | 0.154623E+11 | 0.86 | 9441.50 | 01-MAR-04:03 | 1.42 |
April | 0.144630E+11 | 0.84 | 9441.50 | 01-APR-03:03 | 1.42 |
May | 0.154308E+11 | 0.86 | 9441.50 | 01-MAY-00:05 | 1.42 |
June | 0.155245E+11 | 0.89 | 9441.50 | 01-JUN-03:02 | 1.41 |
July | 0.160111E+11 | 0.89 | 9441.50 | 01-JUL-03:02 | 1.41 |
August | 0.172150E+11 | 0.96 | 9441.50 | 01-AUG-03:02 | 1.41 |
September | 0.160500E+11 | 0.92 | 9441.50 | 01-SEP-03:02 | 1.41 |
October | 0.165709E+11 | 0.92 | 9441.50 | 01-OCT-10:43 | 1.40 |
November | 0.159158E+11 | 0.92 | 9441.50 | 01-NOV-03:02 | 1.41 |
December | 0.157564E+11 | 0.88 | 9441.50 | 01-DEC-04:03 | 1.42 |
Annual Sum or Average | 0.187398E+12 | 0.89 | |||
Minimum of Months | 0.136259E+11 | 0.84 | 9441.50 | 1.40 | |
Maximum of Months | 0.172150E+11 | 0.96 | 9441.50 | 1.42 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.537995E+10 | 0.36 | 9543.90 | 14-JAN-06:02 | 1.09 |
February | 0.646967E+10 | 0.43 | 12382.88 | 21-FEB-16:00 | 1.29 |
March | 0.103858E+11 | 0.57 | 21044.18 | 14-MAR-05:02 | 1.79 |
April | 0.132675E+11 | 0.71 | 21188.12 | 03-APR-05:02 | 1.80 |
May | 0.125789E+11 | 0.66 | 21188.12 | 01-MAY-04:22 | 1.80 |
June | 0.133987E+11 | 0.71 | 21188.12 | 01-JUN-05:02 | 1.80 |
July | 0.137139E+11 | 0.70 | 21188.12 | 03-JUL-04:22 | 1.80 |
August | 0.168514E+11 | 0.79 | 21188.12 | 01-AUG-05:02 | 1.80 |
September | 0.102823E+11 | 0.58 | 21188.12 | 01-SEP-05:02 | 1.80 |
October | 0.988408E+10 | 0.56 | 21188.12 | 02-OCT-05:02 | 1.80 |
November | 0.858474E+10 | 0.50 | 18155.98 | 06-NOV-06:02 | 1.63 |
December | 0.769572E+10 | 0.45 | 12016.50 | 29-DEC-06:02 | 1.26 |
Annual Sum or Average | 0.128493E+12 | 0.59 | |||
Minimum of Months | 0.537995E+10 | 0.36 | 9543.90 | 1.09 | |
Maximum of Months | 0.168514E+11 | 0.79 | 21188.12 | 1.80 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.375350E+11 | 0.31 | 78641.93 | 02-JAN-06:01 | 1.01 |
February | 0.435581E+11 | 0.36 | 100676.55 | 21-FEB-06:03 | 1.17 |
March | 0.725011E+11 | 0.45 | 200428.27 | 14-MAR-05:02 | 1.80 |
April | 0.914074E+11 | 0.55 | 200428.27 | 01-APR-05:02 | 1.80 |
May | 0.106880E+12 | 0.62 | 200428.27 | 05-MAY-05:02 | 1.80 |
June | 0.105107E+12 | 0.62 | 200428.27 | 01-JUN-05:02 | 1.80 |
July | 0.954552E+11 | 0.57 | 200428.27 | 06-JUL-05:02 | 1.80 |
August | 0.987994E+11 | 0.57 | 200428.27 | 01-AUG-05:02 | 1.80 |
September | 0.830838E+11 | 0.51 | 200428.27 | 01-SEP-05:02 | 1.80 |
October | 0.724875E+11 | 0.46 | 200428.27 | 02-OCT-05:02 | 1.80 |
November | 0.545110E+11 | 0.39 | 144790.05 | 09-NOV-06:02 | 1.47 |
December | 0.411517E+11 | 0.33 | 78641.93 | 01-DEC-05:03 | 1.01 |
Annual Sum or Average | 0.902478E+12 | 0.48 | |||
Minimum of Months | 0.375350E+11 | 0.31 | 78641.93 | 1.01 | |
Maximum of Months | 0.106880E+12 | 0.62 | 200428.27 | 1.80 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.287959E+10 | 0.28 | 4300.58 | 02-JAN-05:01 | 0.67 |
February | 0.347957E+10 | 0.31 | 8001.85 | 22-FEB-15:00 | 0.94 |
March | 0.680978E+10 | 0.41 | 20395.72 | 14-MAR-05:02 | 1.67 |
April | 0.101960E+11 | 0.55 | 22752.79 | 17-APR-05:02 | 1.79 |
May | 0.126904E+11 | 0.63 | 22752.79 | 01-MAY-05:02 | 1.79 |
June | 0.126853E+11 | 0.64 | 22752.79 | 02-JUN-05:02 | 1.79 |
July | 0.108561E+11 | 0.57 | 22752.79 | 03-JUL-05:02 | 1.79 |
August | 0.107163E+11 | 0.56 | 22752.79 | 01-AUG-05:02 | 1.79 |
September | 0.872038E+10 | 0.49 | 22752.79 | 01-SEP-05:02 | 1.79 |
October | 0.721443E+10 | 0.43 | 21496.52 | 04-OCT-05:02 | 1.73 |
November | 0.475144E+10 | 0.34 | 12175.41 | 09-NOV-06:02 | 1.21 |
December | 0.302798E+10 | 0.28 | 7289.53 | 29-DEC-06:02 | 0.89 |
Annual Sum or Average | 0.940273E+11 | 0.46 | |||
Minimum of Months | 0.287959E+10 | 0.28 | 4300.58 | 0.67 | |
Maximum of Months | 0.126904E+11 | 0.64 | 22752.79 | 1.79 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BASEMENT SUPPLY FAN
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.967421E+11 | 1.38 | 36119.35 | 01-JAN-00:10 | 1.38 |
February | 0.873799E+11 | 1.38 | 36119.35 | 01-FEB-00:10 | 1.38 |
March | 0.967421E+11 | 1.38 | 36119.35 | 01-MAR-00:10 | 1.38 |
April | 0.936213E+11 | 1.38 | 36119.35 | 01-APR-00:03 | 1.38 |
May | 0.967421E+11 | 1.38 | 36119.35 | 01-MAY-00:05 | 1.38 |
June | 0.936213E+11 | 1.38 | 36119.35 | 01-JUN-00:10 | 1.38 |
July | 0.967421E+11 | 1.38 | 36119.35 | 01-JUL-00:05 | 1.38 |
August | 0.967421E+11 | 1.38 | 36119.35 | 01-AUG-00:03 | 1.38 |
September | 0.936213E+11 | 1.38 | 36119.35 | 01-SEP-00:03 | 1.38 |
October | 0.967421E+11 | 1.38 | 36119.35 | 01-OCT-00:03 | 1.38 |
November | 0.936213E+11 | 1.38 | 36119.35 | 01-NOV-00:10 | 1.38 |
December | 0.967421E+11 | 1.38 | 36119.35 | 01-DEC-00:10 | 1.38 |
Annual Sum or Average | 0.113906E+13 | 1.38 | |||
Minimum of Months | 0.873799E+11 | 1.38 | 36119.35 | 1.38 | |
Maximum of Months | 0.967421E+11 | 1.38 | 36119.35 | 1.38 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BOT SUPPLY FAN
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.144892E+10 | 0.94 | 540.96 | 01-JAN-00:10 | 0.94 |
February | 0.130870E+10 | 0.94 | 540.96 | 01-FEB-00:10 | 0.94 |
March | 0.144892E+10 | 0.94 | 540.96 | 01-MAR-00:10 | 0.94 |
April | 0.140218E+10 | 0.94 | 540.96 | 01-APR-00:03 | 0.94 |
May | 0.144892E+10 | 0.93 | 540.96 | 01-MAY-00:05 | 0.94 |
June | 0.140218E+10 | 0.93 | 540.96 | 01-JUN-00:10 | 0.94 |
July | 0.144892E+10 | 0.93 | 540.96 | 01-JUL-00:05 | 0.93 |
August | 0.144892E+10 | 0.93 | 540.96 | 01-AUG-00:03 | 0.93 |
September | 0.140218E+10 | 0.93 | 540.96 | 01-SEP-00:03 | 0.93 |
October | 0.144892E+10 | 0.94 | 540.96 | 01-OCT-00:03 | 0.94 |
November | 0.140218E+10 | 0.94 | 540.96 | 01-NOV-00:10 | 0.94 |
December | 0.144892E+10 | 0.94 | 540.96 | 01-DEC-00:10 | 0.94 |
Annual Sum or Average | 0.170598E+11 | 0.94 | |||
Minimum of Months | 0.130870E+10 | 0.93 | 540.96 | 0.93 | |
Maximum of Months | 0.144892E+10 | 0.94 | 540.96 | 0.94 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER MID SUPPLY FAN
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.138023E+11 | 0.94 | 5153.18 | 01-JAN-00:10 | 0.94 |
February | 0.124666E+11 | 0.94 | 5153.18 | 01-FEB-00:10 | 0.94 |
March | 0.138023E+11 | 0.94 | 5153.18 | 01-MAR-00:10 | 0.94 |
April | 0.133570E+11 | 0.94 | 5153.18 | 01-APR-00:03 | 0.94 |
May | 0.138023E+11 | 0.93 | 5153.18 | 01-MAY-00:05 | 0.94 |
June | 0.133570E+11 | 0.93 | 5153.18 | 01-JUN-00:10 | 0.93 |
July | 0.138023E+11 | 0.93 | 5153.18 | 01-JUL-00:05 | 0.93 |
August | 0.138023E+11 | 0.93 | 5153.18 | 01-AUG-00:03 | 0.93 |
September | 0.133570E+11 | 0.93 | 5153.18 | 01-SEP-00:03 | 0.93 |
October | 0.138023E+11 | 0.94 | 5153.18 | 01-OCT-00:03 | 0.94 |
November | 0.133570E+11 | 0.94 | 5153.18 | 01-NOV-00:10 | 0.94 |
December | 0.138023E+11 | 0.94 | 5153.18 | 01-DEC-00:10 | 0.94 |
Annual Sum or Average | 0.162511E+12 | 0.94 | |||
Minimum of Months | 0.124666E+11 | 0.93 | 5153.18 | 0.93 | |
Maximum of Months | 0.138023E+11 | 0.94 | 5153.18 | 0.94 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER TOP SUPPLY FAN
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.138998E+10 | 0.94 | 518.96 | 01-JAN-00:10 | 0.94 |
February | 0.125547E+10 | 0.94 | 518.96 | 01-FEB-00:10 | 0.94 |
March | 0.138998E+10 | 0.94 | 518.96 | 01-MAR-00:10 | 0.94 |
April | 0.134514E+10 | 0.94 | 518.96 | 01-APR-00:03 | 0.94 |
May | 0.138998E+10 | 0.93 | 518.96 | 01-MAY-00:05 | 0.94 |
June | 0.134514E+10 | 0.93 | 518.96 | 01-JUN-00:10 | 0.94 |
July | 0.138998E+10 | 0.93 | 518.96 | 01-JUL-00:05 | 0.94 |
August | 0.138998E+10 | 0.93 | 518.96 | 01-AUG-00:03 | 0.94 |
September | 0.134514E+10 | 0.93 | 518.96 | 01-SEP-00:03 | 0.93 |
October | 0.138998E+10 | 0.94 | 518.96 | 01-OCT-00:03 | 0.94 |
November | 0.134514E+10 | 0.94 | 518.96 | 01-NOV-00:10 | 0.94 |
December | 0.138998E+10 | 0.94 | 518.96 | 01-DEC-00:10 | 0.94 |
Annual Sum or Average | 0.163659E+11 | 0.94 | |||
Minimum of Months | 0.125547E+10 | 0.93 | 518.96 | 0.93 | |
Maximum of Months | 0.138998E+10 | 0.94 | 518.96 | 0.94 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 43478407.91 | 39130567.12 | 1226.44 | 02-JAN-06:01 | 1103.80 | 1103.80 | 48.19 | 1.50 |
February | 3434638.42 | 3091174.58 | 466.06 | 11-FEB-06:02 | 419.46 | 419.46 | 25.81 | 0.51 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 24.47 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 24.47 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 24.47 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 24.47 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 24.47 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 24.47 | 0.00 |
September | 25.37 | 22.83 | 0.04 | 25-SEP-10:20 | 0.04 | 0.04 | 24.47 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 24.47 | 0.00 |
November | 116959.72 | 105263.75 | 11.58 | 27-NOV-06:05 | 10.42 | 10.42 | 23.98 | 0.01 |
December | 11099087.74 | 9989178.97 | 520.32 | 23-DEC-06:03 | 468.29 | 468.29 | 38.20 | 0.57 |
Annual Sum or Average | 58129119.16 | 52316207.25 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.98 | 0.00 | |
Maximum of Months | 43478407.91 | 39130567.12 | 1226.44 | 1103.80 | 1103.80 | 48.19 | 1.50 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.267171E+09 | 0.240454E+09 | 2866.15 | 28-JAN-06:02 | 2579.53 | 2579.53 | 8.62 | 49.56 |
February | 0.492713E+09 | 0.443441E+09 | 5748.39 | 25-FEB-06:03 | 5173.55 | 5173.55 | 8.33 | 66.96 |
March | 0.997944E+09 | 0.898150E+09 | 14525.48 | 27-MAR-05:03 | 13072.93 | 13072.93 | 7.98 | 98.13 |
April | 0.158003E+10 | 0.142203E+10 | 21618.04 | 11-APR-05:03 | 19456.23 | 19456.23 | 8.37 | 114.98 |
May | 0.203343E+10 | 0.183009E+10 | 24944.71 | 24-MAY-05:02 | 22450.24 | 22450.24 | 7.45 | 121.65 |
June | 0.236270E+10 | 0.212643E+10 | 25398.51 | 27-JUN-05:02 | 22858.66 | 22858.66 | 7.98 | 122.52 |
July | 0.261432E+10 | 0.235289E+10 | 25398.51 | 06-JUL-05:02 | 22858.66 | 22858.66 | 7.98 | 122.52 |
August | 0.275158E+10 | 0.247642E+10 | 25398.51 | 10-AUG-05:02 | 22858.66 | 22858.66 | 7.37 | 122.52 |
September | 0.198680E+10 | 0.178812E+10 | 25398.51 | 05-SEP-05:02 | 22858.66 | 22858.66 | 7.41 | 122.52 |
October | 0.131607E+10 | 0.118447E+10 | 24658.18 | 04-OCT-05:02 | 22192.36 | 22192.36 | 7.99 | 121.09 |
November | 0.975519E+09 | 0.877967E+09 | 9995.47 | 09-NOV-06:02 | 8995.92 | 8995.92 | 8.36 | 84.31 |
December | 0.394752E+09 | 0.355277E+09 | 4001.16 | 13-DEC-06:03 | 3601.04 | 3601.04 | 8.75 | 57.34 |
Annual Sum or Average | 0.177730E+11 | 0.159957E+11 | ||||||
Minimum of Months | 0.267171E+09 | 0.240454E+09 | 2866.15 | 2579.53 | 2579.53 | 7.37 | 49.56 | |
Maximum of Months | 0.275158E+10 | 0.247642E+10 | 25398.51 | 22858.66 | 22858.66 | 8.75 | 122.52 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.266635E+11 | 0.239971E+11 | 17481.11 | 01-JAN-00:15 | 15733.00 | 15733.00 | 8.46 | 122.52 |
February | 0.267811E+11 | 0.241030E+11 | 17481.11 | 01-FEB-04:05 | 15733.00 | 15733.00 | 8.60 | 122.52 |
March | 0.364840E+11 | 0.328356E+11 | 17481.11 | 01-MAR-04:03 | 15733.00 | 15733.00 | 8.97 | 122.52 |
April | 0.422666E+11 | 0.380399E+11 | 17481.11 | 01-APR-00:10 | 15733.00 | 15733.00 | 7.33 | 122.52 |
May | 0.432807E+11 | 0.389527E+11 | 17481.11 | 01-MAY-00:05 | 15733.00 | 15733.00 | 8.24 | 122.52 |
June | 0.419553E+11 | 0.377598E+11 | 17481.11 | 01-JUN-00:23 | 15733.00 | 15733.00 | 7.02 | 122.52 |
July | 0.446970E+11 | 0.402273E+11 | 17481.11 | 01-JUL-00:05 | 15733.00 | 15733.00 | 8.93 | 122.52 |
August | 0.444716E+11 | 0.400245E+11 | 17481.11 | 01-AUG-00:13 | 15733.00 | 15733.00 | 7.41 | 122.52 |
September | 0.382434E+11 | 0.344191E+11 | 17481.11 | 01-SEP-00:03 | 15733.00 | 15733.00 | 8.91 | 122.52 |
October | 0.374306E+11 | 0.336875E+11 | 17481.11 | 01-OCT-00:53 | 15733.00 | 15733.00 | 7.01 | 122.52 |
November | 0.324677E+11 | 0.292209E+11 | 17481.11 | 01-NOV-03:02 | 15733.00 | 15733.00 | 10.17 | 122.52 |
December | 0.299296E+11 | 0.269366E+11 | 17481.11 | 01-DEC-04:03 | 15733.00 | 15733.00 | 9.01 | 122.52 |
Annual Sum or Average | 0.444671E+12 | 0.400204E+12 | ||||||
Minimum of Months | 0.266635E+11 | 0.239971E+11 | 17481.11 | 15733.00 | 15733.00 | 7.01 | 122.52 | |
Maximum of Months | 0.446970E+11 | 0.402273E+11 | 17481.11 | 15733.00 | 15733.00 | 10.17 | 122.52 |
Report: PumpReportMonthly
For: PLANT CIRC PUMP
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.941118E+10 | 0.847006E+10 | 3513.73 | 01-JAN-00:10 | 3162.36 | 3162.36 | 21.71 | 14.67 |
February | 0.850042E+10 | 0.765038E+10 | 3513.73 | 01-FEB-00:10 | 3162.36 | 3162.36 | 24.25 | 14.67 |
March | 0.941118E+10 | 0.847006E+10 | 3513.73 | 01-MAR-00:10 | 3162.36 | 3162.36 | 28.58 | 14.67 |
April | 0.910759E+10 | 0.819683E+10 | 3513.73 | 01-APR-00:03 | 3162.36 | 3162.36 | 42.38 | 14.67 |
May | 0.941118E+10 | 0.847006E+10 | 3513.73 | 01-MAY-00:05 | 3162.36 | 3162.36 | 37.79 | 14.67 |
June | 0.910759E+10 | 0.819683E+10 | 3513.73 | 01-JUN-00:10 | 3162.36 | 3162.36 | 38.95 | 14.67 |
July | 0.941118E+10 | 0.847006E+10 | 3513.73 | 01-JUL-00:05 | 3162.36 | 3162.36 | 49.00 | 14.67 |
August | 0.941118E+10 | 0.847006E+10 | 3513.73 | 01-AUG-00:03 | 3162.36 | 3162.36 | 49.11 | 14.67 |
September | 0.910759E+10 | 0.819683E+10 | 3513.73 | 01-SEP-00:03 | 3162.36 | 3162.36 | 36.30 | 14.67 |
October | 0.941118E+10 | 0.847006E+10 | 3513.73 | 01-OCT-00:03 | 3162.36 | 3162.36 | 37.33 | 14.67 |
November | 0.910759E+10 | 0.819683E+10 | 3513.73 | 01-NOV-00:10 | 3162.36 | 3162.36 | 31.79 | 14.67 |
December | 0.941118E+10 | 0.847006E+10 | 3513.73 | 01-DEC-00:10 | 3162.36 | 3162.36 | 29.94 | 14.67 |
Annual Sum or Average | 0.110809E+12 | 0.997282E+11 | ||||||
Minimum of Months | 0.850042E+10 | 0.765038E+10 | 3513.73 | 3162.36 | 3162.36 | 21.71 | 14.67 | |
Maximum of Months | 0.941118E+10 | 0.847006E+10 | 3513.73 | 3162.36 | 3162.36 | 49.11 | 14.67 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 11967951.72 | 3590385.52 | 5.96 | 01-JAN-06:05 | 1.79 | 1.79 | 55.98 | 0.44 |
February | 10809762.85 | 3242928.85 | 5.96 | 01-FEB-06:02 | 1.79 | 1.79 | 56.12 | 0.44 |
March | 11967951.72 | 3590385.52 | 5.96 | 01-MAR-06:02 | 1.79 | 1.79 | 56.20 | 0.44 |
April | 11581888.76 | 3474566.63 | 5.96 | 01-APR-05:02 | 1.79 | 1.79 | 56.70 | 0.44 |
May | 11967951.72 | 3590385.52 | 5.96 | 01-MAY-05:02 | 1.79 | 1.79 | 58.03 | 0.44 |
June | 11581888.76 | 3474566.63 | 5.96 | 01-JUN-05:02 | 1.79 | 1.79 | 57.70 | 0.44 |
July | 11967951.72 | 3590385.52 | 5.96 | 01-JUL-05:03 | 1.79 | 1.79 | 57.83 | 0.44 |
August | 11967951.72 | 3590385.52 | 5.96 | 01-AUG-05:02 | 1.79 | 1.79 | 57.70 | 0.44 |
September | 11581888.76 | 3474566.63 | 5.96 | 01-SEP-05:02 | 1.79 | 1.79 | 58.01 | 0.44 |
October | 11967951.72 | 3590385.52 | 5.96 | 01-OCT-05:05 | 1.79 | 1.79 | 56.41 | 0.44 |
November | 11581888.76 | 3474566.63 | 5.96 | 01-NOV-05:03 | 1.79 | 1.79 | 56.26 | 0.44 |
December | 11967951.72 | 3590385.52 | 5.96 | 01-DEC-06:03 | 1.79 | 1.79 | 56.19 | 0.44 |
Annual Sum or Average | 0.140913E+09 | 42273893.99 | ||||||
Minimum of Months | 10809762.85 | 3242928.85 | 5.96 | 1.79 | 1.79 | 55.98 | 0.44 | |
Maximum of Months | 11967951.72 | 3590385.52 | 5.96 | 1.79 | 1.79 | 58.03 | 0.44 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.330930E+11 | 0.297837E+11 | 43378.03 | 12-JAN-14:10 | 39040.23 | 39040.23 | 22.67 | 144.34 |
February | 0.341514E+11 | 0.307363E+11 | 43383.77 | 21-FEB-11:40 | 39045.39 | 39045.39 | 22.85 | 144.34 |
March | 0.494851E+11 | 0.445365E+11 | 43502.73 | 10-MAR-17:00 | 39152.45 | 39152.45 | 26.43 | 144.34 |
April | 0.651710E+11 | 0.586539E+11 | 43589.78 | 18-APR-12:30 | 39230.80 | 39230.80 | 28.84 | 144.34 |
May | 0.760417E+11 | 0.684376E+11 | 43589.78 | 09-MAY-13:10 | 39230.80 | 39230.80 | 28.84 | 144.34 |
June | 0.788177E+11 | 0.709359E+11 | 43589.78 | 05-JUN-15:00 | 39230.80 | 39230.80 | 28.87 | 144.34 |
July | 0.858796E+11 | 0.772916E+11 | 43589.78 | 01-JUL-05:03 | 39230.80 | 39230.80 | 29.05 | 144.34 |
August | 0.868735E+11 | 0.781861E+11 | 43589.78 | 01-AUG-03:02 | 39230.80 | 39230.80 | 28.88 | 144.34 |
September | 0.697920E+11 | 0.628128E+11 | 43589.78 | 01-SEP-03:04 | 39230.80 | 39230.80 | 29.52 | 144.34 |
October | 0.576923E+11 | 0.519231E+11 | 43589.78 | 04-OCT-05:04 | 39230.80 | 39230.80 | 28.85 | 144.34 |
November | 0.415426E+11 | 0.373883E+11 | 43469.35 | 09-NOV-11:20 | 39122.41 | 39122.41 | 25.51 | 144.34 |
December | 0.375021E+11 | 0.337519E+11 | 43381.74 | 01-DEC-14:20 | 39043.56 | 39043.56 | 22.78 | 144.34 |
Annual Sum or Average | 0.716042E+12 | 0.644438E+12 | ||||||
Minimum of Months | 0.330930E+11 | 0.297837E+11 | 43378.03 | 39040.23 | 39040.23 | 22.67 | 144.34 | |
Maximum of Months | 0.868735E+11 | 0.781861E+11 | 43589.78 | 39230.80 | 39230.80 | 29.52 | 144.34 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 79.76 | 79.76 | 3288.70 | 207559.90 | 02-JAN-06:13 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 29.26 | 29.26 | 315.46 | 113461.85 | 11-FEB-06:02 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 24.47 | 24.47 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 0.00 | 0.00 | 01-APR-00:03 | 24.47 | 24.47 | 0.00 | 0.00 | 01-APR-00:03 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 24.47 | 24.47 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.47 | 24.47 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 24.47 | 24.47 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 24.47 | 24.47 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 24.47 | 24.47 | 0.00 | 9.89 | 25-SEP-10:20 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 24.47 | 24.47 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 24.47 | 24.47 | 10.65 | 2741.34 | 27-NOV-06:05 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.69 | 23.69 | 887.88 | 99383.19 | 23-DEC-06:03 |
Annual Sum or Average | 0.00 | 379.80 | ||||||
Minimum of Months | 0.00 | 0.00 | 23.69 | 23.69 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 79.76 | 79.76 | 3288.70 | 207559.90 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 338362.96 | 1484294.89 | 12-JAN-14:10 | 10.09 | 8.63 | 4.37 | 58557.25 | 09-JAN-04:03 |
February | 471508.37 | 1590596.31 | 17-FEB-16:10 | 10.36 | 8.68 | 145.26 | 244744.87 | 20-FEB-01:40 |
March | 707682.66 | 2178349.57 | 14-MAR-05:02 | 11.85 | 7.60 | 1.20 | 16737.73 | 04-MAR-22:33 |
April | 966365.79 | 3078479.26 | 17-APR-05:03 | 13.07 | 7.37 | 0.00 | 0.00 | 01-APR-00:03 |
May | 1199020.52 | 3202931.04 | 18-MAY-05:02 | 12.94 | 7.23 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 1306546.33 | 3517870.50 | 27-JUN-05:02 | 13.56 | 7.85 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 1348206.12 | 3502432.09 | 06-JUL-05:02 | 13.53 | 7.82 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 1330200.70 | 3703129.11 | 07-AUG-05:03 | 13.92 | 8.21 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 1097778.47 | 3578453.37 | 05-SEP-05:04 | 13.75 | 8.04 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 838961.74 | 3189625.69 | 04-OCT-05:02 | 13.16 | 7.45 | 10.69 | 69135.39 | 28-OCT-19:33 |
November | 601816.48 | 1849670.02 | 10-NOV-06:04 | 11.76 | 8.16 | 10.56 | 74720.81 | 19-NOV-08:13 |
December | 406212.99 | 1581393.77 | 01-DEC-14:30 | 10.27 | 8.61 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 886590.48 | 13.39 | ||||||
Minimum of Months | 338362.96 | 1484294.89 | 10.09 | 7.23 | 0.00 | 0.00 | ||
Maximum of Months | 1348206.12 | 3703129.11 | 13.92 | 8.68 | 145.26 | 244744.87 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 211418.16 | 1659882.23 | 18-JAN-06:03 | 15.05 | 9.01 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 322634.06 | 2536869.36 | 25-FEB-06:03 | 15.75 | 8.92 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 530950.49 | 3593536.10 | 14-MAR-05:02 | 15.57 | 7.94 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 761685.85 | 4120582.58 | 17-APR-05:02 | 16.28 | 7.56 | 0.00 | 0.00 | 01-APR-00:03 |
May | 1006300.65 | 4842933.64 | 24-MAY-05:02 | 16.22 | 7.01 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 1172891.89 | 5117348.16 | 27-JUN-05:02 | 16.68 | 7.93 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 1245830.12 | 5127218.35 | 18-JUL-05:02 | 16.70 | 7.87 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 1243429.77 | 5066309.31 | 09-AUG-05:02 | 16.81 | 7.70 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 1004343.59 | 5005870.77 | 06-SEP-05:02 | 16.47 | 7.78 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 657864.09 | 4702443.16 | 04-OCT-05:02 | 15.98 | 7.81 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 452532.23 | 3225268.09 | 09-NOV-06:02 | 15.84 | 8.12 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 261652.31 | 1665391.87 | 13-DEC-06:03 | 13.64 | 8.96 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 741529.24 | 0.00 | ||||||
Minimum of Months | 211418.16 | 1659882.23 | 13.64 | 7.01 | 0.00 | 0.00 | ||
Maximum of Months | 1245830.12 | 5127218.35 | 16.81 | 9.01 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 221478.88 | 581796.75 | 12-JAN-15:00 | 29.65 | 25.58 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 497445.86 | 1014514.91 | 22-FEB-15:00 | 37.93 | 30.67 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 963295.28 | 1757316.38 | 28-MAR-15:20 | 51.83 | 41.00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 1582935.43 | 2218641.77 | 15-APR-15:00 | 60.29 | 47.04 | 0.00 | 0.00 | 01-APR-00:03 |
May | 1117280.36 | 1775093.23 | 01-MAY-15:00 | 52.16 | 46.86 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 1409231.00 | 2060731.80 | 08-JUN-16:00 | 57.41 | 48.91 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 1551733.28 | 2083446.05 | 07-JUL-15:00 | 57.83 | 46.26 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 1664286.44 | 2080587.03 | 07-AUG-15:00 | 57.77 | 44.19 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 897172.92 | 1393224.69 | 17-SEP-20:00 | 45.06 | 40.01 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 902837.86 | 1572825.95 | 02-OCT-15:00 | 48.41 | 40.40 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 818829.36 | 1420749.50 | 08-NOV-15:00 | 45.57 | 35.11 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 785993.58 | 1320185.87 | 28-DEC-14:20 | 43.69 | 30.91 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 1037226.36 | 0.00 | ||||||
Minimum of Months | 221478.88 | 581796.75 | 29.65 | 25.58 | 0.00 | 0.00 | ||
Maximum of Months | 1664286.44 | 2218641.77 | 60.29 | 48.91 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 57.15 | 57.15 | 12736.51 | 41939.93 | 18-JAN-12:50 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 56.57 | 56.57 | 12564.27 | 41692.37 | 01-FEB-12:40 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 56.63 | 56.63 | 12460.74 | 39951.39 | 01-MAR-12:40 |
April | 0.00 | 0.00 | 01-APR-00:03 | 57.05 | 57.05 | 10710.40 | 36287.29 | 03-APR-11:40 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 58.45 | 58.45 | 9907.20 | 32621.48 | 01-MAY-12:00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 57.95 | 57.95 | 9217.51 | 29011.23 | 01-JUN-11:50 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 58.08 | 58.08 | 8270.58 | 26824.63 | 03-JUL-11:30 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 58.38 | 58.38 | 9179.52 | 28583.78 | 31-AUG-11:40 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 58.26 | 58.26 | 9467.79 | 31745.88 | 29-SEP-11:50 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 56.81 | 56.81 | 10514.71 | 35938.15 | 31-OCT-11:20 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 56.69 | 56.69 | 11730.58 | 39428.93 | 30-NOV-12:30 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 56.67 | 56.67 | 12147.66 | 41507.46 | 29-DEC-13:00 |
Annual Sum or Average | 0.00 | 10732.36 | ||||||
Minimum of Months | 0.00 | 0.00 | 56.57 | 56.57 | 8270.58 | 26824.63 | ||
Maximum of Months | 0.00 | 0.00 | 58.45 | 58.45 | 12736.51 | 41939.93 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 198837.52 | 1084391.75 | 25-JAN-16:10 | 24.70 | 21.10 | 2946.31 | 144923.88 | 04-JAN-07:00 |
February | 309851.23 | 1223385.09 | 22-FEB-15:30 | 25.16 | 21.10 | 1249.39 | 132853.29 | 01-FEB-06:50 |
March | 561243.25 | 3213183.62 | 10-MAR-17:00 | 26.43 | 23.32 | 329.85 | 67291.58 | 02-MAR-04:30 |
April | 1047093.08 | 4907954.29 | 18-APR-14:00 | 29.23 | 25.57 | 173.94 | 40475.78 | 10-APR-01:15 |
May | 2208387.84 | 6628981.06 | 17-MAY-15:30 | 32.09 | 27.83 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 3317457.73 | 7696082.91 | 27-JUN-05:04 | 33.86 | 28.87 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 4206224.90 | 7783576.19 | 18-JUL-05:04 | 34.00 | 29.03 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 4236997.61 | 7525760.18 | 28-AUG-14:40 | 33.57 | 28.90 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 2941726.81 | 7293616.55 | 14-SEP-15:30 | 33.19 | 28.77 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 928113.33 | 4676191.28 | 04-OCT-05:04 | 28.85 | 24.37 | 33.74 | 23605.04 | 09-OCT-04:30 |
November | 443314.24 | 2660791.00 | 09-NOV-11:20 | 25.51 | 21.51 | 577.35 | 75347.51 | 27-NOV-05:45 |
December | 242173.05 | 1128014.71 | 01-DEC-16:00 | 24.84 | 21.10 | 1922.03 | 149588.97 | 30-DEC-05:30 |
Annual Sum or Average | 1729328.47 | 601.95 | ||||||
Minimum of Months | 198837.52 | 1084391.75 | 24.70 | 21.10 | 0.00 | 0.00 | ||
Maximum of Months | 4236997.61 | 7783576.19 | 34.00 | 29.03 | 2946.31 | 149588.97 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.163125E+09 | 0.00 | 0.453706E+11 | 0.537995E+10 | 0.00 | 0.00 |
February | 807832.26 | 0.00 | 0.643314E+11 | 0.646967E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.120624E+12 | 0.103858E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.177620E+12 | 0.132675E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.217423E+12 | 0.125789E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.256762E+12 | 0.133987E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.297209E+12 | 0.137139E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.318655E+12 | 0.168514E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.221857E+12 | 0.102823E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.148554E+12 | 0.988408E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.990074E+11 | 0.858474E+10 | 0.00 | 0.00 |
December | 35436036.95 | 0.00 | 0.660829E+11 | 0.769572E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.199369E+09 | 0.00 | 0.203350E+13 | 0.128493E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.453706E+11 | 0.537995E+10 | 0.00 | 0.00 |
Maximum of Months | 0.163125E+09 | 0.00 | 0.318655E+12 | 0.168514E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.426844E+10 | 0.00 | 0.316074E+12 | 0.375350E+11 | 0.00 | 0.00 |
February | 0.159464E+09 | 0.00 | 0.466977E+12 | 0.435581E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.922597E+12 | 0.725011E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.137792E+13 | 0.914074E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.199934E+13 | 0.106880E+12 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.227613E+13 | 0.105107E+12 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.250696E+13 | 0.954552E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.247813E+13 | 0.987994E+11 | 0.00 | 0.00 |
September | 7053.43 | 0.00 | 0.192020E+13 | 0.830838E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.121278E+13 | 0.724875E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.725332E+12 | 0.545110E+11 | 0.00 | 0.00 |
December | 0.856340E+09 | 0.00 | 0.384513E+12 | 0.411517E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.528425E+10 | 0.00 | 0.165870E+14 | 0.902478E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.316074E+12 | 0.375350E+11 | 0.00 | 0.00 |
Maximum of Months | 0.426844E+10 | 0.00 | 0.250696E+13 | 0.106880E+12 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.460983E+10 | 0.00 | 0.232183E+11 | 0.287959E+10 | 0.00 | 0.00 |
February | 0.625311E+09 | 0.00 | 0.412320E+11 | 0.347957E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.949783E+11 | 0.680978E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.156239E+12 | 0.101960E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.229640E+12 | 0.126904E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.258883E+12 | 0.126853E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.276720E+12 | 0.108561E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.269569E+12 | 0.107163E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.207122E+12 | 0.872038E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.125099E+12 | 0.721443E+10 | 0.00 | 0.00 |
November | 30223131.05 | 0.00 | 0.673464E+11 | 0.475144E+10 | 0.00 | 0.00 |
December | 0.150500E+10 | 0.00 | 0.288834E+11 | 0.302798E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.677037E+10 | 0.00 | 0.177893E+13 | 0.940273E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.232183E+11 | 0.287959E+10 | 0.00 | 0.00 |
Maximum of Months | 0.460983E+10 | 0.00 | 0.276720E+12 | 0.126904E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.508292E+11 | 0.153726E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.523339E+11 | 0.136259E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.727924E+11 | 0.154623E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.849268E+11 | 0.144630E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.109000E+12 | 0.154308E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.128552E+12 | 0.155245E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.150085E+12 | 0.160111E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.168700E+12 | 0.172150E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.132492E+12 | 0.160500E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.951481E+11 | 0.165709E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.728296E+11 | 0.159158E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.582386E+11 | 0.157564E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.117593E+13 | 0.187398E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.508292E+11 | 0.136259E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.168700E+12 | 0.172150E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.424817E+12 | 0.196128E+12 | 0.00 | 4.46 |
February | 0.00 | 0.00 | 0.674414E+12 | 0.242123E+12 | 0.00 | 4.88 |
March | 0.00 | 0.00 | 0.108941E+13 | 0.357561E+12 | 0.00 | 2.55 |
April | 0.00 | 0.00 | 0.140279E+13 | 0.463502E+12 | 0.00 | 0.36 |
May | 0.00 | 0.00 | 0.510744E+12 | 0.245192E+12 | 0.00 | 0.01 |
June | 0.00 | 0.00 | 0.843532E+12 | 0.338889E+12 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.121268E+13 | 0.435753E+12 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.148977E+13 | 0.487506E+12 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.498175E+12 | 0.225692E+12 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.798965E+12 | 0.295596E+12 | 0.00 | 0.50 |
November | 0.00 | 0.00 | 0.104668E+13 | 0.336859E+12 | 0.00 | 5.11 |
December | 0.00 | 0.00 | 0.136864E+13 | 0.401184E+12 | 0.00 | 12.88 |
Annual Sum or Average | 0.00 | 0.00 | 0.113606E+14 | 0.402599E+13 | 0.00 | 30.74 |
Minimum of Months | 0.00 | 0.00 | 0.424817E+12 | 0.196128E+12 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.148977E+13 | 0.487506E+12 | 0.00 | 12.88 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.625706E+10 | 0.274193E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.120915E+11 | 0.383159E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.210121E+11 | 0.627470E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.283383E+11 | 0.883603E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.100204E+11 | 0.428456E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.171374E+11 | 0.623811E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.249184E+11 | 0.820256E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.308226E+11 | 0.948291E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.981881E+10 | 0.390943E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.154166E+11 | 0.518047E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.198439E+11 | 0.570488E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.255358E+11 | 0.647240E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.221213E+12 | 0.711596E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.625706E+10 | 0.274193E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.308226E+11 | 0.948291E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.476201E+11 | 0.237980E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.108450E+12 | 0.352378E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.198742E+12 | 0.595105E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.268866E+12 | 0.839679E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.944588E+11 | 0.405377E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.163199E+12 | 0.593804E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.237437E+12 | 0.780993E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.292797E+12 | 0.902886E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.923121E+11 | 0.369140E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.145393E+12 | 0.490289E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.184899E+12 | 0.535781E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.233971E+12 | 0.600834E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.206815E+13 | 0.670425E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.476201E+11 | 0.237980E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.292797E+12 | 0.902886E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.289094E+10 | 0.201847E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.999620E+10 | 0.338418E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.197264E+11 | 0.596268E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.272103E+11 | 0.853671E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.982945E+10 | 0.418209E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.167008E+11 | 0.607444E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.241189E+11 | 0.795190E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.298572E+11 | 0.924257E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.938625E+10 | 0.375090E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.144870E+11 | 0.492438E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.179111E+11 | 0.528427E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.219500E+11 | 0.579399E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.204065E+12 | 0.671066E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.289094E+10 | 0.201847E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.298572E+11 | 0.924257E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.537995E+10 | 0.453706E+11 | 0.163125E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.646967E+10 | 0.643314E+11 | 807832.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.103858E+11 | 0.120624E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.132675E+11 | 0.177620E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125789E+11 | 0.217423E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.133987E+11 | 0.256762E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.137139E+11 | 0.297209E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.168514E+11 | 0.318655E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.102823E+11 | 0.221857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.988408E+10 | 0.148554E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.858474E+10 | 0.990074E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.769572E+10 | 0.660829E+11 | 35436036.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.128493E+12 | 0.203350E+13 | 0.199369E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.537995E+10 | 0.453706E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.168514E+11 | 0.318655E+12 | 0.163125E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.375350E+11 | 0.316074E+12 | 0.426844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.435581E+11 | 0.466977E+12 | 0.159464E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.725011E+11 | 0.922597E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.914074E+11 | 0.137792E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.106880E+12 | 0.199934E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.105107E+12 | 0.227613E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.954552E+11 | 0.250696E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.987994E+11 | 0.247813E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.830838E+11 | 0.192020E+13 | 7053.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.724875E+11 | 0.121278E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.545110E+11 | 0.725332E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.411517E+11 | 0.384513E+12 | 0.856340E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.902478E+12 | 0.165870E+14 | 0.528425E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.375350E+11 | 0.316074E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.106880E+12 | 0.250696E+13 | 0.426844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.287959E+10 | 0.232183E+11 | 0.460983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.347957E+10 | 0.412320E+11 | 0.625311E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.680978E+10 | 0.949783E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.101960E+11 | 0.156239E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.126904E+11 | 0.229640E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.126853E+11 | 0.258883E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.108561E+11 | 0.276720E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.107163E+11 | 0.269569E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.872038E+10 | 0.207122E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.721443E+10 | 0.125099E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.475144E+10 | 0.673464E+11 | 30223131.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.302798E+10 | 0.288834E+11 | 0.150500E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.940273E+11 | 0.177893E+13 | 0.677037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.287959E+10 | 0.232183E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.126904E+11 | 0.276720E+12 | 0.460983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.153726E+11 | 0.508292E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.136259E+11 | 0.523339E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.154623E+11 | 0.727924E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.144630E+11 | 0.849268E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.154308E+11 | 0.109000E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.155245E+11 | 0.128552E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.160111E+11 | 0.150085E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.172150E+11 | 0.168700E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.160500E+11 | 0.132492E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.165709E+11 | 0.951481E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.159158E+11 | 0.728296E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.157564E+11 | 0.582386E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.187398E+12 | 0.117593E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.136259E+11 | 0.508292E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.172150E+11 | 0.168700E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.967421E+11 | 0.337411E+12 | 0.00 | 0.00 | 0.00 | 0.119267E+11 | 0.00 | 0.00 |
February | 0.873799E+11 | 0.532790E+12 | 0.00 | 0.00 | 0.00 | 0.130601E+11 | 0.00 | 0.00 |
March | 0.967421E+11 | 0.835439E+12 | 0.00 | 0.00 | 0.00 | 0.681737E+10 | 0.00 | 0.00 |
April | 0.936213E+11 | 0.103387E+13 | 0.00 | 0.00 | 0.00 | 0.958331E+09 | 0.00 | 0.00 |
May | 0.967421E+11 | 0.362309E+12 | 0.00 | 0.00 | 0.00 | 15004485.30 | 0.00 | 0.00 |
June | 0.936213E+11 | 0.598264E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.967421E+11 | 0.873669E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.967421E+11 | 0.109901E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.936213E+11 | 0.366104E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.967421E+11 | 0.601447E+12 | 0.00 | 0.00 | 0.00 | 0.132983E+10 | 0.00 | 0.00 |
November | 0.936213E+11 | 0.817191E+12 | 0.00 | 0.00 | 0.00 | 0.136855E+11 | 0.00 | 0.00 |
December | 0.967421E+11 | 0.109883E+13 | 0.00 | 0.00 | 0.00 | 0.344797E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.113906E+13 | 0.855633E+13 | 0.00 | 0.00 | 0.00 | 0.822725E+11 | 0.00 | 0.00 |
Minimum of Months | 0.873799E+11 | 0.337411E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.967421E+11 | 0.109901E+13 | 0.00 | 0.00 | 0.00 | 0.344797E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.144892E+10 | 0.496405E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.130870E+10 | 0.956863E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.144892E+10 | 0.161863E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.140218E+10 | 0.209044E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.144892E+10 | 0.718480E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.140218E+10 | 0.123015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.144892E+10 | 0.181648E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.144892E+10 | 0.227886E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.140218E+10 | 0.731155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.144892E+10 | 0.116850E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.140218E+10 | 0.155412E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.144892E+10 | 0.205124E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.170598E+11 | 0.167113E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.130870E+10 | 0.496405E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.144892E+10 | 0.227886E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.138023E+11 | 0.376245E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.124666E+11 | 0.856789E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.138023E+11 | 0.153034E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.133570E+11 | 0.198255E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.138023E+11 | 0.677233E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.133570E+11 | 0.117176E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.138023E+11 | 0.173140E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.138023E+11 | 0.216311E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.133570E+11 | 0.687551E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.138023E+11 | 0.110166E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.133570E+11 | 0.144678E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.138023E+11 | 0.187690E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.162511E+12 | 0.156023E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.124666E+11 | 0.376245E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.138023E+11 | 0.216311E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.138998E+10 | 0.226246E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.125547E+10 | 0.786748E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.138998E+10 | 0.151537E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.134514E+10 | 0.200188E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.138998E+10 | 0.703734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.134514E+10 | 0.119715E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.138998E+10 | 0.175570E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.138998E+10 | 0.220047E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.134514E+10 | 0.698050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.138998E+10 | 0.109526E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.134514E+10 | 0.139720E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.138998E+10 | 0.175460E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.163659E+11 | 0.153324E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.125547E+10 | 0.226246E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.138998E+10 | 0.220047E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.537995E+10 | 0.163125E+09 | 0.453706E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.646967E+10 | 807832.26 | 0.643314E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.103858E+11 | 0.00 | 0.120624E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.132675E+11 | 0.00 | 0.177620E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125789E+11 | 0.00 | 0.217423E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.133987E+11 | 0.00 | 0.256762E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.137139E+11 | 0.00 | 0.297209E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.168514E+11 | 0.00 | 0.318655E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.102823E+11 | 0.00 | 0.221857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.988408E+10 | 0.00 | 0.148554E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.858474E+10 | 0.00 | 0.990074E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.769572E+10 | 35436036.95 | 0.660829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.128493E+12 | 0.199369E+09 | 0.203350E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.537995E+10 | 0.00 | 0.453706E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.168514E+11 | 0.163125E+09 | 0.318655E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.375350E+11 | 0.426844E+10 | 0.316074E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.435581E+11 | 0.159464E+09 | 0.466977E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.725011E+11 | 0.00 | 0.922597E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.914074E+11 | 0.00 | 0.137792E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.106880E+12 | 0.00 | 0.199934E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.105107E+12 | 0.00 | 0.227613E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.954552E+11 | 0.00 | 0.250696E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.987994E+11 | 0.00 | 0.247813E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.830838E+11 | 7053.43 | 0.192020E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.724875E+11 | 0.00 | 0.121278E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.545110E+11 | 0.00 | 0.725332E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.411517E+11 | 0.856340E+09 | 0.384513E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.902478E+12 | 0.528425E+10 | 0.165870E+14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.375350E+11 | 0.00 | 0.316074E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.106880E+12 | 0.426844E+10 | 0.250696E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.287959E+10 | 0.460983E+10 | 0.232183E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.347957E+10 | 0.625311E+09 | 0.412320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.680978E+10 | 0.00 | 0.949783E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.101960E+11 | 0.00 | 0.156239E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.126904E+11 | 0.00 | 0.229640E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.126853E+11 | 0.00 | 0.258883E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.108561E+11 | 0.00 | 0.276720E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.107163E+11 | 0.00 | 0.269569E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.872038E+10 | 0.00 | 0.207122E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.721443E+10 | 0.00 | 0.125099E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.475144E+10 | 30223131.05 | 0.673464E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.302798E+10 | 0.150500E+10 | 0.288834E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.940273E+11 | 0.677037E+10 | 0.177893E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.287959E+10 | 0.00 | 0.232183E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.126904E+11 | 0.460983E+10 | 0.276720E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.153726E+11 | 0.00 | 0.508292E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.136259E+11 | 0.00 | 0.523339E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.154623E+11 | 0.00 | 0.727924E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.144630E+11 | 0.00 | 0.849268E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.154308E+11 | 0.00 | 0.109000E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.155245E+11 | 0.00 | 0.128552E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.160111E+11 | 0.00 | 0.150085E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.172150E+11 | 0.00 | 0.168700E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.160500E+11 | 0.00 | 0.132492E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.165709E+11 | 0.00 | 0.951481E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.159158E+11 | 0.00 | 0.728296E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.157564E+11 | 0.00 | 0.582386E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.187398E+12 | 0.00 | 0.117593E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.136259E+11 | 0.00 | 0.508292E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.172150E+11 | 0.00 | 0.168700E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.967421E+11 | 0.00 | 0.424817E+12 | 0.00 | 0.874060E+11 | 0.00 | 0.00 | 0.00 | 0.119804E+11 | 0.00 | 0.00 | 0.00 |
February | 0.873799E+11 | 0.00 | 0.674414E+12 | 0.00 | 0.141624E+12 | 0.00 | 0.00 | 0.00 | 0.131189E+11 | 0.00 | 0.00 | 0.00 |
March | 0.967421E+11 | 0.00 | 0.108941E+13 | 0.00 | 0.253971E+12 | 0.00 | 0.00 | 0.00 | 0.684805E+10 | 0.00 | 0.00 | 0.00 |
April | 0.936213E+11 | 0.00 | 0.140279E+13 | 0.00 | 0.368918E+12 | 0.00 | 0.00 | 0.00 | 0.962645E+09 | 0.00 | 0.00 | 0.00 |
May | 0.967421E+11 | 0.00 | 0.510744E+12 | 0.00 | 0.148435E+12 | 0.00 | 0.00 | 0.00 | 15072026.57 | 0.00 | 0.00 | 0.00 |
June | 0.936213E+11 | 0.00 | 0.843532E+12 | 0.00 | 0.245268E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.967421E+11 | 0.00 | 0.121268E+13 | 0.00 | 0.339011E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.967421E+11 | 0.00 | 0.148977E+13 | 0.00 | 0.390764E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.936213E+11 | 0.00 | 0.498175E+12 | 0.00 | 0.132071E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.967421E+11 | 0.00 | 0.798965E+12 | 0.00 | 0.197519E+12 | 0.00 | 0.00 | 0.00 | 0.133582E+10 | 0.00 | 0.00 | 0.00 |
November | 0.936213E+11 | 0.00 | 0.104668E+13 | 0.00 | 0.229491E+12 | 0.00 | 0.00 | 0.00 | 0.137471E+11 | 0.00 | 0.00 | 0.00 |
December | 0.967421E+11 | 0.00 | 0.136864E+13 | 0.00 | 0.269807E+12 | 0.00 | 0.00 | 0.00 | 0.346349E+11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.113906E+13 | 0.00 | 0.113606E+14 | 0.00 | 0.280428E+13 | 0.00 | 0.00 | 0.00 | 0.826428E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.873799E+11 | 0.00 | 0.424817E+12 | 0.00 | 0.874060E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.967421E+11 | 0.00 | 0.148977E+13 | 0.00 | 0.390764E+12 | 0.00 | 0.00 | 0.00 | 0.346349E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.144892E+10 | 0.00 | 0.625706E+10 | 0.00 | 0.129302E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.130870E+10 | 0.00 | 0.120915E+11 | 0.00 | 0.252289E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.144892E+10 | 0.00 | 0.210121E+11 | 0.00 | 0.482578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.140218E+10 | 0.00 | 0.283383E+11 | 0.00 | 0.743386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.144892E+10 | 0.00 | 0.100204E+11 | 0.00 | 0.283565E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.140218E+10 | 0.00 | 0.171374E+11 | 0.00 | 0.483594E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.144892E+10 | 0.00 | 0.249184E+11 | 0.00 | 0.675365E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.144892E+10 | 0.00 | 0.308226E+11 | 0.00 | 0.803399E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.140218E+10 | 0.00 | 0.981881E+10 | 0.00 | 0.250726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.144892E+10 | 0.00 | 0.154166E+11 | 0.00 | 0.373155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.140218E+10 | 0.00 | 0.198439E+11 | 0.00 | 0.430270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.144892E+10 | 0.00 | 0.255358E+11 | 0.00 | 0.502349E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.170598E+11 | 0.00 | 0.221213E+12 | 0.00 | 0.540998E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.130870E+10 | 0.00 | 0.625706E+10 | 0.00 | 0.129302E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.144892E+10 | 0.00 | 0.308226E+11 | 0.00 | 0.803399E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.138023E+11 | 0.00 | 0.476201E+11 | 0.00 | 0.999568E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.124666E+11 | 0.00 | 0.108450E+12 | 0.00 | 0.227712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.138023E+11 | 0.00 | 0.198742E+12 | 0.00 | 0.457082E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.133570E+11 | 0.00 | 0.268866E+12 | 0.00 | 0.706109E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.138023E+11 | 0.00 | 0.944588E+11 | 0.00 | 0.267355E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.133570E+11 | 0.00 | 0.163199E+12 | 0.00 | 0.460233E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.138023E+11 | 0.00 | 0.237437E+12 | 0.00 | 0.642970E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.138023E+11 | 0.00 | 0.292797E+12 | 0.00 | 0.764863E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.133570E+11 | 0.00 | 0.923121E+11 | 0.00 | 0.235570E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.138023E+11 | 0.00 | 0.145393E+12 | 0.00 | 0.352266E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.133570E+11 | 0.00 | 0.184899E+12 | 0.00 | 0.402210E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.138023E+11 | 0.00 | 0.233971E+12 | 0.00 | 0.462811E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.162511E+12 | 0.00 | 0.206815E+13 | 0.00 | 0.507914E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.124666E+11 | 0.00 | 0.476201E+11 | 0.00 | 0.999568E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.138023E+11 | 0.00 | 0.292797E+12 | 0.00 | 0.764863E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.138998E+10 | 0.00 | 0.289094E+10 | 0.00 | 0.628486E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.125547E+10 | 0.00 | 0.999620E+10 | 0.00 | 0.212871E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.138998E+10 | 0.00 | 0.197264E+11 | 0.00 | 0.457270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.134514E+10 | 0.00 | 0.272103E+11 | 0.00 | 0.719157E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.138998E+10 | 0.00 | 0.982945E+10 | 0.00 | 0.279211E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.134514E+10 | 0.00 | 0.167008E+11 | 0.00 | 0.472930E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.138998E+10 | 0.00 | 0.241189E+11 | 0.00 | 0.656192E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.138998E+10 | 0.00 | 0.298572E+11 | 0.00 | 0.785259E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.134514E+10 | 0.00 | 0.938625E+10 | 0.00 | 0.240576E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.138998E+10 | 0.00 | 0.144870E+11 | 0.00 | 0.353440E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.134514E+10 | 0.00 | 0.179111E+11 | 0.00 | 0.393913E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.138998E+10 | 0.00 | 0.219500E+11 | 0.00 | 0.440401E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.163659E+11 | 0.00 | 0.204065E+12 | 0.00 | 0.507407E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.125547E+10 | 0.00 | 0.289094E+10 | 0.00 | 0.628486E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.138998E+10 | 0.00 | 0.298572E+11 | 0.00 | 0.785259E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.254336E+10 | 0.00 | 0.00 | 0.113700E+09 | 0.00 | 0.00 | 0.257122E+11 | 0.00 | 0.40 |
February | 0.992914E+09 | 0.00 | 0.00 | 0.101515E+09 | 0.00 | 0.00 | 0.165293E+11 | 0.00 | 0.39 |
March | 0.342322E+09 | 0.152966E+10 | 0.00 | 92139731.23 | 27747493.12 | 0.00 | 0.846132E+10 | 0.00 | 0.40 |
April | 22318292.49 | 0.106819E+11 | 0.00 | 21368182.66 | 0.281402E+09 | 0.00 | 0.548877E+09 | 0.00 | 0.39 |
May | 5171939.13 | 0.297736E+11 | 0.00 | 3174802.06 | 0.474510E+09 | 0.00 | 48846417.74 | 0.00 | 0.41 |
June | 0.00 | 0.462440E+11 | 0.00 | 477049.84 | 0.780366E+09 | 0.00 | 879911.21 | 0.00 | 0.42 |
July | 0.00 | 0.634032E+11 | 0.00 | 0.00 | 0.155379E+10 | 0.00 | 0.00 | 0.00 | 0.42 |
August | 0.00 | 0.709591E+11 | 0.00 | 0.00 | 0.114476E+10 | 0.00 | 0.00 | 0.00 | 0.45 |
September | 0.00 | 0.465107E+11 | 0.00 | 0.00 | 0.982365E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
October | 0.174253E+09 | 0.881618E+10 | 0.00 | 57322702.82 | 0.127534E+09 | 0.00 | 0.292506E+10 | 0.00 | 0.43 |
November | 0.103723E+10 | 0.242869E+09 | 0.00 | 0.129809E+09 | 23533402.98 | 0.00 | 0.131761E+11 | 0.00 | 0.43 |
December | 0.205880E+10 | 0.00 | 0.00 | 0.124693E+09 | 0.00 | 0.00 | 0.239784E+11 | 0.00 | 0.41 |
Annual Sum or Average | 0.717637E+10 | 0.278161E+12 | 0.00 | 0.644200E+09 | 0.539601E+10 | 0.00 | 0.913809E+11 | 0.00 | 0.42 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.39 |
Maximum of Months | 0.254336E+10 | 0.709591E+11 | 0.00 | 0.129809E+09 | 0.155379E+10 | 0.00 | 0.257122E+11 | 0.00 | 0.45 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.181627E+10 | 0.00 | 0.00 | 80627018.17 | 0.00 | 0.00 | 0.251113E+11 | 0.00 | 0.36 |
February | 0.193492E+10 | 0.00 | 0.00 | 80556225.63 | 1269930.79 | 0.00 | 0.161996E+11 | 0.00 | 0.37 |
March | 0.264154E+10 | 0.115678E+10 | 0.00 | 79603992.65 | 0.389747E+09 | 0.00 | 0.818757E+10 | 0.00 | 0.42 |
April | 0.697253E+09 | 0.702076E+10 | 0.00 | 22976466.19 | 0.398967E+10 | 0.00 | 0.762090E+09 | 0.00 | 0.46 |
May | 15245814.15 | 0.233713E+11 | 0.00 | 575614.89 | 0.109513E+11 | 0.00 | 9032324.21 | 0.00 | 0.43 |
June | 0.00 | 0.354032E+11 | 0.00 | 0.00 | 0.197564E+11 | 0.00 | 0.00 | 0.00 | 0.44 |
July | 0.00 | 0.453139E+11 | 0.00 | 0.00 | 0.332166E+11 | 0.00 | 0.00 | 0.00 | 0.46 |
August | 0.00 | 0.518099E+11 | 0.00 | 0.00 | 0.298537E+11 | 0.00 | 0.00 | 0.00 | 0.47 |
September | 0.00 | 0.353174E+11 | 0.00 | 0.00 | 0.174936E+11 | 0.00 | 0.00 | 0.00 | 0.41 |
October | 0.920007E+09 | 0.756738E+10 | 0.00 | 29481093.71 | 0.199217E+10 | 0.00 | 0.227417E+10 | 0.00 | 0.41 |
November | 0.282989E+10 | 0.179127E+09 | 0.00 | 91429624.69 | 90469793.95 | 0.00 | 0.118673E+11 | 0.00 | 0.39 |
December | 0.326570E+10 | 0.00 | 0.00 | 94596271.42 | 0.00 | 0.00 | 0.232962E+11 | 0.00 | 0.40 |
Annual Sum or Average | 0.141208E+11 | 0.207140E+12 | 0.00 | 0.479846E+09 | 0.117735E+12 | 0.00 | 0.877073E+11 | 0.00 | 0.42 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
Maximum of Months | 0.326570E+10 | 0.518099E+11 | 0.00 | 94596271.42 | 0.332166E+11 | 0.00 | 0.251113E+11 | 0.00 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.371798E+11 | 0.00 | 0.00 | 0.479933E+09 | 0.00 | 0.00 | 0.192150E+12 | 0.00 | 0.34 |
February | 0.140003E+11 | 0.00 | 0.00 | 0.556050E+09 | 61395997.46 | 0.00 | 0.140244E+12 | 0.00 | 0.35 |
March | 0.103017E+11 | 0.116670E+11 | 0.00 | 0.661797E+09 | 0.344429E+10 | 0.00 | 0.776552E+11 | 0.00 | 0.36 |
April | 0.245065E+10 | 0.675510E+11 | 0.00 | 0.166465E+09 | 0.350433E+11 | 0.00 | 0.611550E+10 | 0.00 | 0.38 |
May | 0.109484E+09 | 0.229432E+12 | 0.00 | 3023522.05 | 0.979931E+11 | 0.00 | 82578280.25 | 0.00 | 0.41 |
June | 0.00 | 0.344950E+12 | 0.00 | 0.00 | 0.159725E+12 | 0.00 | 0.00 | 0.00 | 0.41 |
July | 0.00 | 0.434220E+12 | 0.00 | 0.00 | 0.249861E+12 | 0.00 | 0.00 | 0.00 | 0.40 |
August | 0.00 | 0.493094E+12 | 0.00 | 0.00 | 0.183353E+12 | 0.00 | 0.00 | 0.00 | 0.39 |
September | 0.00 | 0.347307E+12 | 0.00 | 0.00 | 0.110338E+12 | 0.00 | 0.00 | 0.00 | 0.36 |
October | 0.516759E+10 | 0.746917E+11 | 0.00 | 0.241343E+09 | 0.136734E+11 | 0.00 | 0.203205E+11 | 0.00 | 0.35 |
November | 0.143580E+11 | 0.184454E+10 | 0.00 | 0.667282E+09 | 0.111708E+10 | 0.00 | 0.101324E+12 | 0.00 | 0.35 |
December | 0.237548E+11 | 0.00 | 0.00 | 0.527245E+09 | 10469191.04 | 0.00 | 0.187326E+12 | 0.00 | 0.35 |
Annual Sum or Average | 0.107322E+12 | 0.200476E+13 | 0.00 | 0.330314E+10 | 0.854620E+12 | 0.00 | 0.725219E+12 | 0.00 | 0.37 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.34 |
Maximum of Months | 0.371798E+11 | 0.493094E+12 | 0.00 | 0.667282E+09 | 0.249861E+12 | 0.00 | 0.192150E+12 | 0.00 | 0.41 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.126112E+11 | 0.00 | 0.00 | 13477625.28 | 0.00 | 0.263789E+09 | 0.541169E+10 | 0.00 | 0.30 |
February | 0.535084E+10 | 0.00 | 0.00 | 31343975.79 | 909367.88 | 0.00 | 0.724985E+10 | 0.00 | 0.31 |
March | 0.125555E+10 | 0.828932E+09 | 0.00 | 56512772.94 | 0.238064E+09 | 0.00 | 0.653755E+10 | 0.00 | 0.34 |
April | 0.221615E+09 | 0.587080E+10 | 0.00 | 21410369.15 | 0.313042E+10 | 0.00 | 0.701964E+09 | 0.00 | 0.38 |
May | 10302283.83 | 0.220988E+11 | 0.00 | 269459.82 | 0.936761E+10 | 0.00 | 6854031.95 | 0.00 | 0.42 |
June | 0.00 | 0.338251E+11 | 0.00 | 0.00 | 0.157946E+11 | 0.00 | 0.00 | 0.00 | 0.41 |
July | 0.00 | 0.429470E+11 | 0.00 | 0.00 | 0.253007E+11 | 0.00 | 0.00 | 0.00 | 0.41 |
August | 0.00 | 0.486186E+11 | 0.00 | 0.00 | 0.191134E+11 | 0.00 | 0.00 | 0.00 | 0.40 |
September | 0.00 | 0.336002E+11 | 0.00 | 0.00 | 0.124890E+11 | 0.00 | 0.00 | 0.00 | 0.37 |
October | 0.493387E+09 | 0.652683E+10 | 0.00 | 21177554.95 | 0.123437E+10 | 0.00 | 0.156997E+10 | 0.00 | 0.34 |
November | 0.318368E+10 | 46712861.34 | 0.00 | 46870062.41 | 80064191.60 | 0.00 | 0.624812E+10 | 0.00 | 0.31 |
December | 0.990485E+10 | 0.00 | 0.00 | 20270042.92 | 159115.22 | 0.00 | 0.648424E+10 | 0.00 | 0.30 |
Annual Sum or Average | 0.330314E+11 | 0.194363E+12 | 0.00 | 0.211332E+09 | 0.867494E+11 | 0.263789E+09 | 0.342102E+11 | 0.00 | 0.36 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.126112E+11 | 0.486186E+11 | 0.00 | 56512772.94 | 0.253007E+11 | 0.263789E+09 | 0.724985E+10 | 0.00 | 0.42 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.164376E+10 | 0.00 | 0.00 | 3364269.78 | 0.00 | 0.00 | 0.902376E+09 | 0.00 | 0.28 |
February | 0.837591E+09 | 0.00 | 0.00 | 5848885.01 | 160009.05 | 0.00 | 0.994037E+09 | 0.00 | 0.32 |
March | 0.419932E+09 | 0.207051E+09 | 0.00 | 8999503.39 | 48950918.76 | 0.00 | 0.857221E+09 | 0.00 | 0.44 |
April | 91089633.41 | 0.154502E+10 | 0.00 | 3556546.01 | 0.425417E+09 | 0.00 | 0.103374E+09 | 0.00 | 0.58 |
May | 1300643.41 | 0.576168E+10 | 0.00 | 213579.16 | 0.104987E+10 | 0.00 | 2761838.72 | 0.00 | 0.66 |
June | 0.00 | 0.889836E+10 | 0.00 | 0.00 | 0.194909E+10 | 0.00 | 0.00 | 0.00 | 0.69 |
July | 0.00 | 0.113680E+11 | 0.00 | 0.00 | 0.312958E+10 | 0.00 | 0.00 | 0.00 | 0.66 |
August | 0.00 | 0.112637E+11 | 0.00 | 0.00 | 0.295811E+10 | 0.00 | 0.00 | 0.00 | 0.64 |
September | 0.00 | 0.687572E+10 | 0.00 | 0.00 | 0.198651E+10 | 0.00 | 0.00 | 0.00 | 0.54 |
October | 0.147949E+09 | 0.128025E+10 | 0.00 | 3085415.48 | 0.243289E+09 | 0.00 | 0.211949E+09 | 0.00 | 0.46 |
November | 0.600247E+09 | 26855402.62 | 0.00 | 8174632.00 | 11399035.53 | 0.00 | 0.916464E+09 | 0.00 | 0.35 |
December | 0.135640E+10 | 0.00 | 0.00 | 5329741.87 | 0.00 | 0.00 | 0.111331E+10 | 0.00 | 0.30 |
Annual Sum or Average | 0.509827E+10 | 0.472266E+11 | 0.00 | 38572572.69 | 0.118024E+11 | 0.00 | 0.510149E+10 | 0.00 | 0.49 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.164376E+10 | 0.113680E+11 | 0.00 | 8999503.39 | 0.312958E+10 | 0.00 | 0.111331E+10 | 0.00 | 0.69 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.107847E+10 | 0.00 | 0.00 | 3481870.33 | 0.00 | 0.00 | 0.100881E+10 | 0.00 | 0.35 |
February | 0.585072E+09 | 0.00 | 0.00 | 5245147.83 | 120557.79 | 0.00 | 0.935126E+09 | 0.00 | 0.40 |
March | 0.346703E+09 | 0.151079E+09 | 0.00 | 7528159.78 | 35697052.54 | 0.00 | 0.691927E+09 | 0.00 | 0.54 |
April | 64939513.66 | 0.118710E+10 | 0.00 | 3070100.25 | 0.322547E+09 | 0.00 | 91593379.86 | 0.00 | 0.71 |
May | 1115852.89 | 0.458939E+10 | 0.00 | 130118.23 | 0.748615E+09 | 0.00 | 1754088.46 | 0.00 | 0.81 |
June | 0.00 | 0.618792E+10 | 0.00 | 0.00 | 0.155117E+10 | 0.00 | 0.00 | 0.00 | 0.77 |
July | 0.00 | 0.725530E+10 | 0.00 | 0.00 | 0.260783E+10 | 0.00 | 0.00 | 0.00 | 0.70 |
August | 0.00 | 0.653961E+10 | 0.00 | 0.00 | 0.258738E+10 | 0.00 | 0.00 | 0.00 | 0.64 |
September | 0.00 | 0.491657E+10 | 0.00 | 0.00 | 0.150737E+10 | 0.00 | 0.00 | 0.00 | 0.62 |
October | 0.111871E+09 | 0.958625E+09 | 0.00 | 2720908.85 | 0.171228E+09 | 0.00 | 0.181307E+09 | 0.00 | 0.55 |
November | 0.522907E+09 | 18825614.48 | 0.00 | 6358287.64 | 8588529.70 | 0.00 | 0.685932E+09 | 0.00 | 0.42 |
December | 0.110619E+10 | 0.00 | 0.00 | 3891537.61 | 0.00 | 0.00 | 0.784608E+09 | 0.00 | 0.35 |
Annual Sum or Average | 0.381726E+10 | 0.318044E+11 | 0.00 | 32426130.53 | 0.954055E+10 | 0.00 | 0.438105E+10 | 0.00 | 0.57 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
Maximum of Months | 0.110619E+10 | 0.725530E+10 | 0.00 | 7528159.78 | 0.260783E+10 | 0.00 | 0.100881E+10 | 0.00 | 0.81 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.102379E+10 | 0.00 | 0.00 | 10937428.52 | 0.00 | 0.00 | 0.287742E+10 | 0.00 | 0.47 |
February | 0.643379E+09 | 184296.83 | 0.00 | 13881165.01 | 29734.74 | 0.00 | 0.201047E+10 | 0.00 | 0.50 |
March | 0.364091E+09 | 0.354053E+09 | 0.00 | 14450346.55 | 24870329.33 | 0.00 | 0.129602E+10 | 0.00 | 0.60 |
April | 84712245.22 | 0.201712E+10 | 0.00 | 4615877.26 | 0.347383E+09 | 0.00 | 0.126747E+09 | 0.00 | 0.68 |
May | 1258189.28 | 0.613121E+10 | 0.00 | 228197.16 | 0.971528E+09 | 0.00 | 2849975.11 | 0.00 | 0.68 |
June | 0.00 | 0.889258E+10 | 0.00 | 0.00 | 0.192764E+10 | 0.00 | 0.00 | 0.00 | 0.68 |
July | 0.00 | 0.114586E+11 | 0.00 | 0.00 | 0.310125E+10 | 0.00 | 0.00 | 0.00 | 0.67 |
August | 0.00 | 0.117889E+11 | 0.00 | 0.00 | 0.289436E+10 | 0.00 | 0.00 | 0.00 | 0.66 |
September | 0.00 | 0.860055E+10 | 0.00 | 0.00 | 0.169729E+10 | 0.00 | 0.00 | 0.00 | 0.64 |
October | 0.117647E+09 | 0.216078E+10 | 0.00 | 6695841.17 | 0.145805E+09 | 0.00 | 0.339776E+09 | 0.00 | 0.68 |
November | 0.450294E+09 | 68999458.88 | 0.00 | 21464189.62 | 6155373.62 | 0.00 | 0.189199E+10 | 0.00 | 0.62 |
December | 0.950508E+09 | 0.00 | 0.00 | 14711094.98 | 0.00 | 0.00 | 0.276228E+10 | 0.00 | 0.50 |
Annual Sum or Average | 0.363568E+10 | 0.514730E+11 | 0.00 | 86984140.27 | 0.111163E+11 | 0.00 | 0.113075E+11 | 0.00 | 0.62 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.47 |
Maximum of Months | 0.102379E+10 | 0.117889E+11 | 0.00 | 21464189.62 | 0.310125E+10 | 0.00 | 0.287742E+10 | 0.00 | 0.68 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.950174E+09 | 0.00 | 0.00 | 5855404.15 | 0.00 | 0.00 | 0.181618E+10 | 0.00 | 0.48 |
February | 0.357717E+09 | 209731.30 | 0.00 | 10116592.93 | 20066.38 | 0.00 | 0.178609E+10 | 0.00 | 0.60 |
March | 0.204468E+09 | 0.323506E+09 | 0.00 | 15052978.60 | 15622349.60 | 0.00 | 0.143955E+10 | 0.00 | 0.88 |
April | 14744598.91 | 0.264871E+10 | 0.00 | 7292567.42 | 46830892.60 | 0.00 | 0.232725E+09 | 0.00 | 1.22 |
May | 955848.56 | 0.621215E+10 | 0.00 | 271798.92 | 0.647733E+09 | 0.00 | 3119990.07 | 0.00 | 1.03 |
June | 0.00 | 0.101945E+11 | 0.00 | 0.00 | 0.101192E+10 | 0.00 | 0.00 | 0.00 | 1.11 |
July | 0.00 | 0.139211E+11 | 0.00 | 0.00 | 0.130042E+10 | 0.00 | 0.00 | 0.00 | 1.08 |
August | 0.00 | 0.168723E+11 | 0.00 | 0.00 | 0.306943E+09 | 0.00 | 0.00 | 0.00 | 1.20 |
September | 0.00 | 0.738073E+10 | 0.00 | 0.00 | 0.141685E+10 | 0.00 | 0.00 | 0.00 | 0.84 |
October | 81554924.28 | 0.157905E+10 | 0.00 | 4964363.50 | 0.131113E+09 | 0.00 | 0.330340E+09 | 0.00 | 0.81 |
November | 0.281537E+09 | 48989549.84 | 0.00 | 14596395.74 | 4112351.29 | 0.00 | 0.168415E+10 | 0.00 | 0.72 |
December | 0.363089E+09 | 0.00 | 0.00 | 13445331.56 | 0.00 | 0.00 | 0.310610E+10 | 0.00 | 0.68 |
Annual Sum or Average | 0.225424E+10 | 0.591813E+11 | 0.00 | 71595432.83 | 0.488157E+10 | 0.00 | 0.103982E+11 | 0.00 | 0.89 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.48 |
Maximum of Months | 0.950174E+09 | 0.168723E+11 | 0.00 | 15052978.60 | 0.141685E+10 | 0.00 | 0.310610E+10 | 0.00 | 1.22 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.206306E+11 | 0.00 | 0.00 | 6677382.98 | 0.00 | 0.291003E+09 | 0.265946E+10 | 0.00 | 0.27 |
February | 0.108097E+11 | 0.00 | 0.00 | 27872753.38 | 7698584.10 | 0.00 | 0.504214E+10 | 0.00 | 0.29 |
March | 0.365583E+10 | 0.214086E+10 | 0.00 | 62268435.42 | 0.432283E+09 | 0.00 | 0.638309E+10 | 0.00 | 0.37 |
April | 0.310605E+09 | 0.160216E+11 | 0.00 | 25308259.16 | 0.398950E+10 | 0.00 | 0.843259E+09 | 0.00 | 0.54 |
May | 8565343.50 | 0.627631E+11 | 0.00 | 1626772.16 | 0.840655E+10 | 0.00 | 28381591.01 | 0.00 | 0.68 |
June | 0.00 | 0.964665E+11 | 0.00 | 0.00 | 0.143988E+11 | 0.00 | 0.00 | 0.00 | 0.71 |
July | 0.00 | 0.121168E+12 | 0.00 | 0.00 | 0.209328E+11 | 0.00 | 0.00 | 0.00 | 0.66 |
August | 0.00 | 0.117743E+12 | 0.00 | 0.00 | 0.173615E+11 | 0.00 | 0.00 | 0.00 | 0.61 |
September | 0.00 | 0.712336E+11 | 0.00 | 0.00 | 0.116347E+11 | 0.00 | 0.00 | 0.00 | 0.51 |
October | 0.135966E+10 | 0.128493E+11 | 0.00 | 20840755.99 | 0.167136E+10 | 0.00 | 0.144817E+10 | 0.00 | 0.40 |
November | 0.762331E+10 | 0.245614E+09 | 0.00 | 43306555.62 | 0.141293E+09 | 0.00 | 0.451178E+10 | 0.00 | 0.31 |
December | 0.181422E+11 | 0.00 | 0.00 | 12548632.90 | 1312755.73 | 5330559.89 | 0.328280E+10 | 0.00 | 0.28 |
Annual Sum or Average | 0.625404E+11 | 0.500632E+12 | 0.00 | 0.200450E+09 | 0.789778E+11 | 0.296333E+09 | 0.241991E+11 | 0.00 | 0.47 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.206306E+11 | 0.121168E+12 | 0.00 | 62268435.42 | 0.209328E+11 | 0.291003E+09 | 0.638309E+10 | 0.00 | 0.71 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.134053E+11 | 0.00 | 0.00 | 15401855.26 | 0.00 | 30639242.32 | 0.581039E+10 | 0.00 | 0.35 |
February | 0.680206E+10 | 0.00 | 0.00 | 37695339.44 | 6126994.91 | 0.00 | 0.763558E+10 | 0.00 | 0.41 |
March | 0.225499E+10 | 0.184235E+10 | 0.00 | 69777525.40 | 0.307973E+09 | 0.00 | 0.747320E+10 | 0.00 | 0.54 |
April | 0.182693E+09 | 0.153731E+11 | 0.00 | 29063321.89 | 0.249721E+10 | 0.00 | 0.988056E+09 | 0.00 | 0.77 |
May | 5768815.36 | 0.534363E+11 | 0.00 | 1151191.51 | 0.577564E+10 | 0.00 | 21657727.85 | 0.00 | 0.90 |
June | 0.00 | 0.739138E+11 | 0.00 | 0.00 | 0.109328E+11 | 0.00 | 0.00 | 0.00 | 0.85 |
July | 0.00 | 0.889856E+11 | 0.00 | 0.00 | 0.161958E+11 | 0.00 | 0.00 | 0.00 | 0.75 |
August | 0.00 | 0.847564E+11 | 0.00 | 0.00 | 0.133455E+11 | 0.00 | 0.00 | 0.00 | 0.69 |
September | 0.00 | 0.556301E+11 | 0.00 | 0.00 | 0.846175E+10 | 0.00 | 0.00 | 0.00 | 0.62 |
October | 0.873071E+09 | 0.109237E+11 | 0.00 | 25116561.27 | 0.107962E+10 | 0.00 | 0.180748E+10 | 0.00 | 0.55 |
November | 0.490935E+10 | 0.211934E+09 | 0.00 | 50004680.00 | 0.111479E+09 | 0.00 | 0.624211E+10 | 0.00 | 0.43 |
December | 0.117494E+11 | 0.00 | 0.00 | 20991828.76 | 1044769.74 | 0.00 | 0.590263E+10 | 0.00 | 0.36 |
Annual Sum or Average | 0.401826E+11 | 0.385073E+12 | 0.00 | 0.249202E+09 | 0.587148E+11 | 30639242.32 | 0.358811E+11 | 0.00 | 0.60 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
Maximum of Months | 0.134053E+11 | 0.889856E+11 | 0.00 | 69777525.40 | 0.161958E+11 | 30639242.32 | 0.763558E+10 | 0.00 | 0.90 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.103993E+11 | 0.00 | 0.00 | 0.100790E+09 | 0.00 | 0.00 | 0.299594E+11 | 0.00 | 0.53 |
February | 0.606225E+10 | 10743700.23 | 0.00 | 0.123625E+09 | 910544.31 | 0.00 | 0.200349E+11 | 0.00 | 0.54 |
March | 0.236366E+10 | 0.409666E+10 | 0.00 | 0.127070E+09 | 0.133652E+09 | 0.00 | 0.126607E+11 | 0.00 | 0.60 |
April | 0.268988E+09 | 0.221791E+11 | 0.00 | 35295791.81 | 0.297269E+10 | 0.00 | 0.109857E+10 | 0.00 | 0.67 |
May | 8462833.35 | 0.663510E+11 | 0.00 | 1788380.96 | 0.783001E+10 | 0.00 | 29110166.35 | 0.00 | 0.71 |
June | 0.00 | 0.953543E+11 | 0.00 | 0.00 | 0.147352E+11 | 0.00 | 0.00 | 0.00 | 0.70 |
July | 0.00 | 0.122381E+12 | 0.00 | 0.00 | 0.206970E+11 | 0.00 | 0.00 | 0.00 | 0.66 |
August | 0.00 | 0.126847E+12 | 0.00 | 0.00 | 0.156877E+11 | 0.00 | 0.00 | 0.00 | 0.64 |
September | 0.00 | 0.922818E+11 | 0.00 | 0.00 | 0.866419E+10 | 0.00 | 0.00 | 0.00 | 0.63 |
October | 0.511533E+09 | 0.241580E+11 | 0.00 | 55218960.03 | 0.633694E+09 | 0.00 | 0.362298E+10 | 0.00 | 0.70 |
November | 0.283571E+10 | 0.911685E+09 | 0.00 | 0.197008E+09 | 51240223.88 | 0.00 | 0.197624E+11 | 0.00 | 0.68 |
December | 0.855549E+10 | 1271717.44 | 0.00 | 0.121118E+09 | 219638.67 | 0.00 | 0.290130E+11 | 0.00 | 0.56 |
Annual Sum or Average | 0.310054E+11 | 0.554572E+12 | 0.00 | 0.761914E+09 | 0.714064E+11 | 0.00 | 0.116181E+12 | 0.00 | 0.64 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.53 |
Maximum of Months | 0.103993E+11 | 0.126847E+12 | 0.00 | 0.197008E+09 | 0.206970E+11 | 0.00 | 0.299594E+11 | 0.00 | 0.71 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.157805E+11 | 0.00 | 0.00 | 19256465.45 | 0.00 | 0.00 | 0.567940E+10 | 0.00 | 0.40 |
February | 0.766417E+10 | 4404850.53 | 0.00 | 38258717.23 | 2953658.63 | 0.00 | 0.687801E+10 | 0.00 | 0.44 |
March | 0.220725E+10 | 0.261694E+10 | 0.00 | 71826149.77 | 0.190974E+09 | 0.00 | 0.747002E+10 | 0.00 | 0.59 |
April | 0.196533E+09 | 0.190479E+11 | 0.00 | 26836867.46 | 0.185901E+10 | 0.00 | 0.852026E+09 | 0.00 | 0.85 |
May | 5171245.83 | 0.601119E+11 | 0.00 | 1686767.37 | 0.456985E+10 | 0.00 | 25478285.51 | 0.00 | 0.96 |
June | 0.00 | 0.878944E+11 | 0.00 | 0.00 | 0.845737E+10 | 0.00 | 0.00 | 0.00 | 0.96 |
July | 0.00 | 0.102207E+12 | 0.00 | 0.00 | 0.132335E+11 | 0.00 | 0.00 | 0.00 | 0.83 |
August | 0.00 | 0.101264E+12 | 0.00 | 0.00 | 0.106081E+11 | 0.00 | 0.00 | 0.00 | 0.78 |
September | 0.00 | 0.636458E+11 | 0.00 | 0.00 | 0.747840E+10 | 0.00 | 0.00 | 0.00 | 0.68 |
October | 0.682292E+09 | 0.128084E+11 | 0.00 | 22468423.76 | 0.976961E+09 | 0.00 | 0.177939E+10 | 0.00 | 0.59 |
November | 0.466406E+10 | 0.366907E+09 | 0.00 | 55607197.49 | 94479411.46 | 0.00 | 0.636708E+10 | 0.00 | 0.47 |
December | 0.131550E+11 | 0.00 | 0.00 | 25258709.31 | 1119038.87 | 0.00 | 0.646627E+10 | 0.00 | 0.41 |
Annual Sum or Average | 0.443550E+11 | 0.449968E+12 | 0.00 | 0.261199E+09 | 0.474727E+11 | 0.00 | 0.355177E+11 | 0.00 | 0.66 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.40 |
Maximum of Months | 0.157805E+11 | 0.102207E+12 | 0.00 | 71826149.77 | 0.132335E+11 | 0.00 | 0.747002E+10 | 0.00 | 0.96 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.176513E+10 | 0.00 | 0.00 | 122318.77 | 0.00 | 0.608606E+09 | 44635658.41 | 0.00 | 0.31 |
February | 0.112965E+10 | 0.00 | 0.00 | 1703876.16 | 123279.45 | 0.122688E+09 | 0.304670E+09 | 0.00 | 0.30 |
March | 0.377663E+09 | 0.149077E+09 | 0.00 | 5853352.91 | 31626317.66 | 0.00 | 0.598698E+09 | 0.00 | 0.37 |
April | 33327033.54 | 0.137398E+10 | 0.00 | 3450449.82 | 0.353292E+09 | 0.00 | 0.107762E+09 | 0.00 | 0.54 |
May | 755346.48 | 0.587905E+10 | 0.00 | 149155.55 | 0.756689E+09 | 0.00 | 2638389.54 | 0.00 | 0.68 |
June | 0.00 | 0.923120E+10 | 0.00 | 0.00 | 0.132900E+10 | 0.00 | 0.00 | 0.00 | 0.70 |
July | 0.00 | 0.119894E+11 | 0.00 | 0.00 | 0.194849E+10 | 0.00 | 0.00 | 0.00 | 0.66 |
August | 0.00 | 0.115674E+11 | 0.00 | 0.00 | 0.175792E+10 | 0.00 | 0.00 | 0.00 | 0.62 |
September | 0.00 | 0.693361E+10 | 0.00 | 0.00 | 0.131927E+10 | 0.00 | 0.00 | 0.00 | 0.52 |
October | 0.150932E+09 | 0.108994E+10 | 0.00 | 2166753.87 | 0.178015E+09 | 0.00 | 0.109736E+09 | 0.00 | 0.40 |
November | 0.808961E+09 | 6670726.14 | 0.00 | 3586606.28 | 10380601.08 | 279085.20 | 0.338805E+09 | 0.00 | 0.31 |
December | 0.164980E+10 | 0.00 | 0.00 | 208781.96 | 21570.63 | 0.354948E+09 | 89368981.46 | 0.00 | 0.30 |
Annual Sum or Average | 0.591622E+10 | 0.482203E+11 | 0.00 | 17241295.31 | 0.768483E+10 | 0.108652E+10 | 0.159631E+10 | 0.00 | 0.48 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.176513E+10 | 0.119894E+11 | 0.00 | 5853352.91 | 0.194849E+10 | 0.608606E+09 | 0.598698E+09 | 0.00 | 0.70 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.129925E+10 | 0.00 | 0.00 | 484964.63 | 0.00 | 0.310987E+09 | 0.230640E+09 | 0.00 | 0.37 |
February | 0.655858E+09 | 0.00 | 0.00 | 2922073.85 | 93817.00 | 49030531.19 | 0.615568E+09 | 0.00 | 0.40 |
March | 0.191612E+09 | 0.131532E+09 | 0.00 | 7148972.37 | 19323570.04 | 0.00 | 0.758342E+09 | 0.00 | 0.54 |
April | 16249880.53 | 0.132894E+10 | 0.00 | 3938968.21 | 0.217600E+09 | 0.00 | 0.123924E+09 | 0.00 | 0.77 |
May | 589140.71 | 0.496817E+10 | 0.00 | 114214.58 | 0.513284E+09 | 0.00 | 1908422.62 | 0.00 | 0.89 |
June | 0.00 | 0.707521E+10 | 0.00 | 0.00 | 0.974690E+09 | 0.00 | 0.00 | 0.00 | 0.83 |
July | 0.00 | 0.882689E+10 | 0.00 | 0.00 | 0.144463E+10 | 0.00 | 0.00 | 0.00 | 0.76 |
August | 0.00 | 0.843740E+10 | 0.00 | 0.00 | 0.128853E+10 | 0.00 | 0.00 | 0.00 | 0.70 |
September | 0.00 | 0.550552E+10 | 0.00 | 0.00 | 0.918189E+09 | 0.00 | 0.00 | 0.00 | 0.64 |
October | 85843134.93 | 0.956240E+09 | 0.00 | 2822338.09 | 0.107121E+09 | 0.00 | 0.163247E+09 | 0.00 | 0.55 |
November | 0.450620E+09 | 6886652.05 | 0.00 | 4740938.04 | 7617120.16 | 0.00 | 0.559868E+09 | 0.00 | 0.42 |
December | 0.116902E+10 | 0.00 | 0.00 | 847292.56 | 16415.48 | 0.124719E+09 | 0.308142E+09 | 0.00 | 0.36 |
Annual Sum or Average | 0.386904E+10 | 0.372368E+11 | 0.00 | 23019762.33 | 0.549110E+10 | 0.484736E+09 | 0.276164E+10 | 0.00 | 0.60 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
Maximum of Months | 0.129925E+10 | 0.882689E+10 | 0.00 | 7148972.37 | 0.144463E+10 | 0.310987E+09 | 0.758342E+09 | 0.00 | 0.89 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.110496E+10 | 0.00 | 0.00 | 6854850.44 | 0.00 | 0.272553E+09 | 0.213333E+10 | 0.00 | 0.48 |
February | 0.685329E+09 | 149362.47 | 0.00 | 10303757.76 | 18179.04 | 28512688.66 | 0.176212E+10 | 0.00 | 0.52 |
March | 0.223719E+09 | 0.270874E+09 | 0.00 | 12926694.59 | 12863483.38 | 0.00 | 0.128894E+10 | 0.00 | 0.58 |
April | 27702561.82 | 0.185728E+10 | 0.00 | 5036651.44 | 0.267124E+09 | 0.00 | 0.146639E+09 | 0.00 | 0.66 |
May | 733649.18 | 0.616575E+10 | 0.00 | 162018.64 | 0.719701E+09 | 0.00 | 2734601.24 | 0.00 | 0.71 |
June | 0.00 | 0.913284E+10 | 0.00 | 0.00 | 0.135049E+10 | 0.00 | 0.00 | 0.00 | 0.69 |
July | 0.00 | 0.120708E+11 | 0.00 | 0.00 | 0.194183E+10 | 0.00 | 0.00 | 0.00 | 0.67 |
August | 0.00 | 0.124090E+11 | 0.00 | 0.00 | 0.160225E+10 | 0.00 | 0.00 | 0.00 | 0.65 |
September | 0.00 | 0.886647E+10 | 0.00 | 0.00 | 0.101456E+10 | 0.00 | 0.00 | 0.00 | 0.63 |
October | 61065092.67 | 0.199638E+10 | 0.00 | 8180029.53 | 63541196.72 | 0.00 | 0.343007E+09 | 0.00 | 0.69 |
November | 0.316716E+09 | 33380484.69 | 0.00 | 19497478.96 | 5436384.21 | 0.00 | 0.191790E+10 | 0.00 | 0.66 |
December | 0.984631E+09 | 19330.07 | 0.00 | 8555902.11 | 9873.64 | 72087590.79 | 0.221758E+10 | 0.00 | 0.50 |
Annual Sum or Average | 0.340486E+10 | 0.528029E+11 | 0.00 | 71517383.47 | 0.697782E+10 | 0.373153E+09 | 0.981226E+10 | 0.00 | 0.62 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.48 |
Maximum of Months | 0.110496E+10 | 0.124090E+11 | 0.00 | 19497478.96 | 0.194183E+10 | 0.272553E+09 | 0.221758E+10 | 0.00 | 0.71 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.143016E+10 | 0.00 | 0.00 | 1135196.25 | 0.00 | 0.317566E+09 | 0.382666E+09 | 0.00 | 0.43 |
February | 0.881769E+09 | 26195.33 | 0.00 | 2906526.46 | 89612.73 | 32712940.69 | 0.528500E+09 | 0.00 | 0.45 |
March | 0.245816E+09 | 0.177898E+09 | 0.00 | 7021478.95 | 15021485.56 | 0.00 | 0.710364E+09 | 0.00 | 0.57 |
April | 20710544.62 | 0.153889E+10 | 0.00 | 3889084.81 | 0.185806E+09 | 0.00 | 0.108685E+09 | 0.00 | 0.83 |
May | 555900.20 | 0.532205E+10 | 0.00 | 150012.58 | 0.505811E+09 | 0.00 | 2287211.57 | 0.00 | 0.93 |
June | 0.00 | 0.807930E+10 | 0.00 | 0.00 | 0.874691E+09 | 0.00 | 0.00 | 0.00 | 0.93 |
July | 0.00 | 0.967862E+10 | 0.00 | 0.00 | 0.146991E+10 | 0.00 | 0.00 | 0.00 | 0.82 |
August | 0.00 | 0.954499E+10 | 0.00 | 0.00 | 0.128460E+10 | 0.00 | 0.00 | 0.00 | 0.78 |
September | 0.00 | 0.606867E+10 | 0.00 | 0.00 | 0.928031E+09 | 0.00 | 0.00 | 0.00 | 0.69 |
October | 95687524.28 | 0.106491E+10 | 0.00 | 2779265.01 | 0.108833E+09 | 0.00 | 0.134746E+09 | 0.00 | 0.59 |
November | 0.535918E+09 | 12838305.88 | 0.00 | 5132698.76 | 7735093.57 | 0.00 | 0.538585E+09 | 0.00 | 0.47 |
December | 0.138645E+10 | 0.00 | 0.00 | 1510442.89 | 18549.51 | 73740720.47 | 0.422417E+09 | 0.00 | 0.42 |
Annual Sum or Average | 0.459707E+10 | 0.414882E+11 | 0.00 | 24524705.72 | 0.538054E+10 | 0.424019E+09 | 0.282825E+10 | 0.00 | 0.66 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 0.143016E+10 | 0.967862E+10 | 0.00 | 7021478.95 | 0.146991E+10 | 0.317566E+09 | 0.710364E+09 | 0.00 | 0.93 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 8277676.64 | 0.00 | 0.00 | 0.623625E+09 | 0.00 | 0.58 |
February | 0.00 | 5583522.31 | 0.00 | 17166665.48 | 0.00 | 0.00 | 0.308232E+09 | 0.00 | 0.59 |
March | 0.00 | 0.106507E+09 | 0.00 | 18260078.41 | 0.00 | 0.00 | 0.107853E+09 | 0.00 | 0.59 |
April | 0.00 | 0.319097E+09 | 0.00 | 8226666.84 | 0.00 | 0.00 | 9821507.77 | 0.00 | 0.59 |
May | 0.00 | 0.839330E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
June | 0.00 | 0.127934E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
July | 0.00 | 0.174962E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
August | 0.00 | 0.170409E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
September | 0.00 | 0.124668E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
October | 0.00 | 0.404176E+09 | 0.00 | 2014555.10 | 0.00 | 0.00 | 6002295.50 | 0.00 | 0.59 |
November | 0.00 | 37314741.76 | 0.00 | 24870823.00 | 0.00 | 0.00 | 0.164301E+09 | 0.00 | 0.59 |
December | 0.00 | 5444.04 | 0.00 | 44140209.25 | 0.00 | 0.00 | 0.503795E+09 | 0.00 | 0.58 |
Annual Sum or Average | 0.00 | 0.769175E+10 | 0.00 | 0.122957E+09 | 0.00 | 0.00 | 0.172363E+10 | 0.00 | 0.59 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
Maximum of Months | 0.00 | 0.174962E+10 | 0.00 | 44140209.25 | 0.00 | 0.00 | 0.623625E+09 | 0.00 | 0.60 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 58477410.63 | 0.00 | 0.00 | 0.634441E+10 | 0.00 | 0.58 |
February | 0.00 | 53515577.94 | 0.00 | 0.152550E+09 | 0.00 | 0.00 | 0.311977E+10 | 0.00 | 0.59 |
March | 0.00 | 0.106168E+10 | 0.00 | 0.172435E+09 | 0.00 | 0.00 | 0.108912E+10 | 0.00 | 0.59 |
April | 0.00 | 0.322798E+10 | 0.00 | 79171958.13 | 0.00 | 0.00 | 0.100340E+09 | 0.00 | 0.59 |
May | 0.00 | 0.833106E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
June | 0.00 | 0.127480E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
July | 0.00 | 0.174559E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
August | 0.00 | 0.172214E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
September | 0.00 | 0.123252E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
October | 0.00 | 0.401447E+10 | 0.00 | 19051042.41 | 0.00 | 0.00 | 63350957.73 | 0.00 | 0.59 |
November | 0.00 | 0.370582E+09 | 0.00 | 0.230406E+09 | 0.00 | 0.00 | 0.166512E+10 | 0.00 | 0.59 |
December | 0.00 | 47319.91 | 0.00 | 0.402426E+09 | 0.00 | 0.00 | 0.507382E+10 | 0.00 | 0.58 |
Annual Sum or Average | 0.00 | 0.768099E+11 | 0.00 | 0.111452E+10 | 0.00 | 0.00 | 0.174559E+11 | 0.00 | 0.59 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
Maximum of Months | 0.00 | 0.174559E+11 | 0.00 | 0.402426E+09 | 0.00 | 0.00 | 0.634441E+10 | 0.00 | 0.60 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.146546E+09 | 0.00 | 0.00 | 2735518.43 | 0.00 | 0.00 | 0.498316E+09 | 0.00 | 0.58 |
February | 0.00 | 6486852.39 | 0.00 | 13443359.08 | 0.00 | 0.00 | 0.302186E+09 | 0.00 | 0.59 |
March | 0.00 | 0.115142E+09 | 0.00 | 16017010.79 | 0.00 | 0.00 | 0.100648E+09 | 0.00 | 0.59 |
April | 0.00 | 0.343070E+09 | 0.00 | 6961564.01 | 0.00 | 0.00 | 8398197.94 | 0.00 | 0.59 |
May | 0.00 | 0.852862E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
June | 0.00 | 0.129459E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
July | 0.00 | 0.176619E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
August | 0.00 | 0.176461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
September | 0.00 | 0.125191E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
October | 0.00 | 0.417986E+09 | 0.00 | 1636525.09 | 0.00 | 0.00 | 5286332.08 | 0.00 | 0.59 |
November | 0.00 | 42183528.20 | 0.00 | 21151082.31 | 0.00 | 0.00 | 0.156119E+09 | 0.00 | 0.59 |
December | 0.00 | 36936.53 | 0.00 | 37161559.10 | 0.00 | 0.00 | 0.494528E+09 | 0.00 | 0.58 |
Annual Sum or Average | 0.146546E+09 | 0.785506E+10 | 0.00 | 99106618.80 | 0.00 | 0.00 | 0.156548E+10 | 0.00 | 0.59 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
Maximum of Months | 0.146546E+09 | 0.176619E+10 | 0.00 | 37161559.10 | 0.00 | 0.00 | 0.498316E+09 | 0.00 | 0.60 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.495043E+09 | 0.00 | 0.00 | 0.139978E+11 | 0.00 | 0.66 |
February | 0.00 | 0.162045E+09 | 0.00 | 0.865791E+09 | 0.00 | 0.00 | 0.675921E+10 | 0.00 | 0.66 |
March | 0.00 | 0.247280E+10 | 0.00 | 0.832162E+09 | 0.00 | 0.00 | 0.206915E+10 | 0.00 | 0.66 |
April | 0.00 | 0.462598E+10 | 0.00 | 0.614061E+09 | 0.00 | 0.00 | 0.392536E+09 | 0.00 | 0.67 |
May | 0.00 | 0.196920E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 |
June | 0.00 | 0.289772E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 |
July | 0.00 | 0.390392E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 |
August | 0.00 | 0.329510E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.68 |
September | 0.00 | 0.298996E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 |
October | 0.00 | 0.949475E+10 | 0.00 | 84764945.42 | 0.00 | 0.00 | 92306919.23 | 0.00 | 0.66 |
November | 0.00 | 0.893764E+09 | 0.00 | 0.117770E+10 | 0.00 | 0.00 | 0.331140E+10 | 0.00 | 0.66 |
December | 0.00 | 0.00 | 0.00 | 0.217203E+10 | 0.00 | 0.00 | 0.110815E+11 | 0.00 | 0.66 |
Annual Sum or Average | 0.00 | 0.168208E+12 | 0.00 | 0.624156E+10 | 0.00 | 0.00 | 0.377039E+11 | 0.00 | 0.66 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 |
Maximum of Months | 0.00 | 0.390392E+11 | 0.00 | 0.217203E+10 | 0.00 | 0.00 | 0.139978E+11 | 0.00 | 0.68 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 09:04:27
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.290993E+12 | 0.300579E+10 | 0.00 | 0.851044E+12 | 0.113000E+13 |
February | 0.336876E+12 | 0.351694E+10 | 0.00 | 0.551517E+12 | 0.166947E+13 |
March | 0.457104E+12 | 0.207383E+10 | 0.00 | 0.252033E+12 | 0.287539E+13 |
April | 0.496583E+12 | -0.156170E+10 | 0.00 | -0.266823E+12 | 0.392212E+13 |
May | 0.541000E+12 | -0.725241E+10 | 0.00 | -0.912719E+12 | 0.370818E+13 |
June | 0.505040E+12 | -0.823236E+10 | 0.00 | -0.141686E+13 | 0.453443E+13 |
July | 0.410830E+12 | -0.175677E+11 | 0.00 | -0.193869E+13 | 0.540333E+13 |
August | 0.344035E+12 | -0.123155E+11 | 0.00 | -0.195118E+13 | 0.579819E+13 |
September | 0.371864E+12 | -0.709814E+10 | 0.00 | -0.142099E+13 | 0.356651E+13 |
October | 0.354735E+12 | -617010426.0 | 0.00 | -0.151604E+12 | 0.291445E+13 |
November | 0.307931E+12 | 0.876516E+09 | 0.00 | 0.438560E+12 | 0.255380E+13 |
December | 0.266882E+12 | 0.298765E+10 | 0.00 | 0.793843E+12 | 0.248370E+13 |
Annual Sum or Average | 0.468387E+13 | -0.421841E+11 | 0.00 | -0.517187E+13 | 0.405596E+14 |
Minimum of Months | 0.266882E+12 | -0.175677E+11 | 0.00 | -0.195118E+13 | 0.113000E+13 |
Maximum of Months | 0.541000E+12 | 0.351694E+10 | 0.00 | 0.851044E+12 | 0.579819E+13 |