Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:04
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** Albuquerque Intl Sunport NM USA TMY3 WMO#=723650
Simulation Timestamp: 2023-10-16 09:04:19
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:19
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 31452.69 | 679.02 | 679.02 |
Net Site Energy | 31452.69 | 679.02 | 679.02 |
Total Source Energy | 96648.65 | 2086.53 | 2086.53 |
Net Source Energy | 96648.65 | 2086.53 | 2086.53 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 729.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 3998.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 2740.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 447.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 15213.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1914.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2824.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 586.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 1150.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6369.97 |
Humidification | 1154.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 429.52 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 692.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 30030.69 | 1421.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9079.66 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 729.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 3998.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 2740.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 447.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5871.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 59.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 1848.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 5.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 2824.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 586.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 1150.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6369.97 |
Humidification | General | 1154.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 429.52 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Water Heater | 0.00 | 692.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 729.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 3998.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 2740.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 447.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 15213.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 1914.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 2824.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 586.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 1150.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6369.97 |
Humidification | Unassigned | 1154.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 429.52 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 692.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 68.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 209.73 | 30.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.20 |
Other | 369.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 648.33 | 30.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.20 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 68.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 209.73 | 30.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.20 |
Other | 369.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 648.33 | 30.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.20 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 30030.695 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 30030.695 | 100.00 |
Total On-Site and Utility Electric Sources | 30030.695 | 100.00 |
Total Electricity End Uses | 30030.695 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 9079.66 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 9079.66 | 100.00 |
Total Water End Uses | 9079.66 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 12.33 |
Time Setpoint Not Met During Occupied Cooling | 1629.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5943.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NM_ALBUQUERQUE
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| HEATSYS1 BOILER | CENTRAL BOILER |DXReportMonthly
| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |FanReportMonthly
| CAV_BAS FAN | VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:19
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:04 |
RunPeriod | RUNPERIOD 1 |
Weather File | Albuquerque Intl Sunport NM USA TMY3 WMO#=723650 |
Latitude [deg] | 35.04 |
Longitude [deg] | -106.6 |
Elevation [m] | 1619.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 3476.85 | 1043.06 | 695.37 | 1043.06 | 695.37 |
Gross Window-Wall Ratio [%] | 28.54 | 28.54 | 28.54 | 28.54 | 28.54 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 3476.85 | 1043.06 | 695.37 | 1043.06 | 695.37 |
Gross Window-Wall Ratio [%] | 28.54 | 28.54 | 28.54 | 28.54 | 28.54 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 7.6202 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.6202 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.6202 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.6202 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 7.6202 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 7.6202 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 7.6202 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 7.6202 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 86.92 | 86.92 | 7.6202 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 57.95 | 57.95 | 7.6202 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 86.92 | 86.92 | 7.6202 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 57.95 | 57.95 | 7.6202 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 7.6202 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 7.6202 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 7.6202 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 7.6202 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.5114 | 18.58 | 215.2992 |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.5114 | 18.58 | 215.2992 |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.5114 | 18.58 | 215.2992 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 7.6202 | 18.58 | 484.4232 |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 3476.85 | 3476.85 | 7.6661 | 18.58 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 3476.85 | 3476.85 | 7.6661 | 18.58 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 2779.43 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 7.6202 | 18.58 | 4.8418 | |
CORE_BOTTOM | 2496.12 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 7.6202 | 18.58 | 8.0697 | |
CORE_MID | 2496.12 | Yes | Yes | 10.00 | CORE_MID | GENERAL | CORE_MID | 7.6202 | 18.58 | 8.0696 | |
CORE_TOP | 2496.12 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 7.6202 | 18.58 | 8.0696 | |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 7.6202 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 7.6202 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 7.6202 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 7.6202 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 7.6202 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 7.6202 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 7.6202 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 7.6202 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 7.6202 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 7.6202 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 7.6202 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 7.6202 | 18.58 | 8.0699 | |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | GROUNDFLOOR_PLENUM | GENERAL | GROUNDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 10.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_BOT_ZN_6 | GENERAL | DATACENTER_BOT_ZN_6 | 12.5114 | 18.58 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 10.00 | DATACENTER_MID_ZN_6 | GENERAL | DATACENTER_MID_ZN_6 | 12.5114 | 18.58 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_TOP_ZN_6 | GENERAL | DATACENTER_TOP_ZN_6 | 12.5114 | 18.58 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1.00 | DATACENTER_BASEMENT_ZN_6 | GENERAL | DATACENTER_BASEMENT_ZN_6 | 7.6202 | 18.58 | 484.4232 | |
Total | 46320.38 | 7.6661 | 9.29 | 17.8789 | |||||||
Conditioned Total | 46320.38 | 7.6661 | 9.29 | 17.8789 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 42757.27 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 46320.38 | 46320.38 | 0.00 | 42757.27 | 2.3561 | 60.38 | 10.8345 |
Total | 46320.38 | 46320.38 | 0.00 | 42757.27 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:19
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 02-AUG-15:30 | 06-FEB-07:10 | - | - | - | - | - | - | - | - | - | - | 28-JUN-16:19 |
Heating | 0.00 | 741511.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 413953.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 234435.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 794004.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 83146.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 273286.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 54199.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 81203.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 35144.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 29502.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1969373.19 | 771014.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 741511.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 413953.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 234435.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 320838.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 3711.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 79171.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 263.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 273286.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 54199.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 81203.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 35144.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 29502.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:19
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 790.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 12662.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 8679.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 1416.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 48180.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 6062.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 8946.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1857.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 3644.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 3656.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 751.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 95107.21 | 1541.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 17.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 273.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 187.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 30.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1040.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 130.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 193.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 40.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 78.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 78.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 16.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2053.25 | 33.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 17.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 273.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 187.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 30.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1040.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 130.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 193.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 40.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 78.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 78.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 16.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2053.25 | 33.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:19
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
BASEMENT DIRECT AIR | 6.47 |
DATACENTER_BOT_ZN_6 DIRECT AIR | 0.580616 |
DATACENTER_MID_ZN_6 DIRECT AIR | 5.54 |
DATACENTER_TOP_ZN_6 DIRECT AIR | 0.566403 |
DATACENTER_BASEMENT_ZN_6 DIRECT AIR | 25.97 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 6.82 | 0.278791 | 0.294000 | 2.01 | 0.743442 | 0.500000 | 0.001367 | 0.000145 | 2.01 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 64.01 | 0.297137 | 0.307000 | 19.65 | 0.792365 | 0.500000 | 0.001282 | 0.003639 | 19.65 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 6.39 | 0.297652 | 0.316000 | 2.02 | 0.793738 | 0.500000 | 0.001280 | 0.000719 | 2.97 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 1.15 | 0.207637 | 0.219000 | 0.251890 | 0.553699 | 0.500000 | 0.001835 | 0.000093 | 0.387034 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 1.30 | 0.118747 | 0.200000 | 0.259216 | 0.316657 | 0.500000 | 0.003209 | 0.000066 | 0.274138 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.39 | 0.171322 | 0.200000 | 0.278803 | 0.456859 | 0.500000 | 0.002224 | 0.000113 | 0.465923 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 1.66 | 0.092882 | 0.200000 | 0.331398 | 0.300000 | 0.500000 | 0.004102 | 0.000056 | 0.331398 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 10.84 | 0.220406 | 0.228000 | 2.47 | 0.587750 | 0.500000 | 0.001729 | 0.001788 | 7.41 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 13.59 | 0.113223 | 0.200000 | 2.72 | 0.301929 | 0.500000 | 0.003365 | 0.001186 | 4.92 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 13.35 | 0.178939 | 0.200000 | 2.67 | 0.477171 | 0.500000 | 0.002129 | 0.001772 | 7.35 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 14.67 | 0.104930 | 0.200000 | 2.93 | 0.300000 | 0.500000 | 0.003631 | 0.001121 | 4.65 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 1.26 | 0.190085 | 0.202000 | 0.253791 | 0.506892 | 0.500000 | 0.002004 | 0.000234 | 0.972598 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.38 | 0.111379 | 0.200000 | 0.276364 | 0.300000 | 0.500000 | 0.003421 | 0.000155 | 0.641794 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.49 | 0.159845 | 0.200000 | 0.298822 | 0.426252 | 0.500000 | 0.002384 | 0.000233 | 0.964580 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.58 | 0.097139 | 0.200000 | 0.316876 | 0.300000 | 0.500000 | 0.003922 | 0.000150 | 0.620724 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 16610.99 | 0.000145 | 334.86 |
CORE_MID VAV BOX REHEAT COIL | 415981.64 | 0.003639 | 9930.94 |
CORE_TOP VAV BOX REHEAT COIL | 82180.72 | 0.000719 | 2169.11 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 10686.45 | 0.000093 | 282.00 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 7567.42 | 0.000066 | 199.67 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 12859.68 | 0.000113 | 339.29 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 6415.63 | 0.000056 | 149.23 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 204364.43 | 0.001788 | 5389.10 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 135620.65 | 0.001186 | 3576.23 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 202605.99 | 0.001772 | 5342.77 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 128157.40 | 0.001121 | 3379.57 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 26802.04 | 0.000234 | 706.64 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 17685.41 | 0.000155 | 466.27 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 26581.38 | 0.000233 | 700.82 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 17105.40 | 0.000150 | 450.98 |
VAV_BOT WITH REHEAT HEATING COIL | 53316.13 | 0.000466 | 877.63 |
VAV_MID WITH REHEAT HEATING COIL | 487107.32 | 0.004261 | 8029.20 |
VAV_TOP WITH REHEAT HEATING COIL | 45106.13 | 0.000395 | 754.78 |
CAV_BAS HEATING COIL | 266817.07 | 0.002334 | 5910.31 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT | 6.16 | 3.13 | 12.32 | 3.13 | 11.12 | 11.12 | 0.300000 | 0.281268 | 11.12 |
VAV_MID WITH REHEAT | 58.23 | 30.44 | 116.46 | 37.33 | 103.19 | 103.19 | 0.300000 | 0.361744 | 103.19 |
VAV_TOP WITH REHEAT | 6.05 | 3.17 | 12.11 | 6.17 | 11.40 | 11.40 | 0.300000 | 0.541867 | 11.40 |
CAV_BAS | 6.47 | 6.47 | 6.47 | 6.47 | 6.47 | 6.47 | 1.00 | 1.00 | 6.47 |
AIRLOOP DATACENTER BASEMENT | 25.97 | 25.97 | 25.97 | 25.97 | 25.97 | 25.97 | 1.00 | 0.999986 | 25.97 |
AIRLOOP DATACENTER BOT | 0.580616 | 0.580616 | 0.580616 | 0.580616 | 0.580616 | 0.580616 | 1.00 | 1.00 | 0.580616 |
AIRLOOP DATACENTER MID | 5.54 | 5.54 | 5.54 | 5.54 | 5.54 | 5.54 | 1.00 | 1.00 | 5.54 |
AIRLOOP DATACENTER TOP | 0.566403 | 0.566403 | 0.566403 | 0.566403 | 0.566403 | 0.566403 | 1.00 | 1.00 | 0.566403 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 11.12 | |
VAV_MID WITH REHEAT_OA_CONTROLLER | 103.19 | |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 11.40 | |
CAV_BAS_OA_CONTROLLER | 6.47 | 1.20 |
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | 25.97 | 0.338393 |
AIRLOOP DATACENTER BOT_OA_CONTROLLER | 0.580616 | 0.015632 |
AIRLOOP DATACENTER MID_OA_CONTROLLER | 5.54 | 0.156323 |
AIRLOOP DATACENTER TOP_OA_CONTROLLER | 0.566403 | 0.015632 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT COOLING COIL | 26.64 | 6.67 | 10.67 | 0.006952 | 0.006952 | 179053.87 | 0.007617 | 11.12 |
VAV_MID WITH REHEAT COOLING COIL | 26.94 | 6.67 | 10.67 | 0.006925 | 0.006925 | 1692065.48 | 0.071984 | 103.19 |
VAV_TOP WITH REHEAT COOLING COIL | 26.48 | 6.67 | 10.67 | 0.006945 | 0.006945 | 181618.43 | 0.007726 | 11.40 |
CAV_BAS COOLING COIL | 26.19 | 6.67 | 11.12 | 0.007140 | 0.007140 | 98239.40 | 0.004179 | 6.47 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 11.12 |
VAV_MID WITH REHEAT FAN | 103.19 |
VAV_TOP WITH REHEAT FAN | 11.40 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.007617 | 0.000063 |
VAV_BOT WITH REHEAT_HEATC_CONTROLLER | 0.000466 | |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.071984 | 0.000007 |
VAV_MID WITH REHEAT_HEATC_CONTROLLER | 0.004261 | |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.007726 | 0.000062 |
VAV_TOP WITH REHEAT_HEATC_CONTROLLER | 0.000395 | |
CAV_BAS_COOLC_CONTROLLER | 0.004179 | 0.000114 |
CAV_BAS_HEATC_CONTROLLER | 0.002334 |
Design Size Maximum Flow Rate [m3/s] | |
CAV_BAS FAN | 6.47 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Total Cooling Capacity [W] | Design Size Rated Sensible Cooling Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | 25.97 | 475527.81 | 252201.15 | 0.011646 |
AIRLOOP DATACENTER BOT COOLING COIL | 0.580616 | 10356.64 | 5543.42 | 0.000254 |
AIRLOOP DATACENTER MID COOLING COIL | 5.54 | 98913.37 | 52928.84 | 0.002422 |
AIRLOOP DATACENTER TOP COOLING COIL | 0.566403 | 10106.03 | 5408.44 | 0.000247 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | 25.97 | 25.97 | 25.97 | 25.97 | 475527.81 | 475527.81 | 16131.55 | 1.00 |
AIRLOOP DATACENTER BOT DXAC HEAT PUMP | 0.580616 | 0.580616 | 0.580616 | 0.580616 | 10356.64 | 10356.64 | 745.21 | 1.00 |
AIRLOOP DATACENTER MID DXAC HEAT PUMP | 5.54 | 5.54 | 5.54 | 5.54 | 98913.37 | 98913.37 | 7452.11 | 1.00 |
AIRLOOP DATACENTER TOP DXAC HEAT PUMP | 0.566403 | 0.566403 | 0.566403 | 0.566403 | 10106.03 | 10106.03 | 745.21 | 1.00 |
Design Size Maximum Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | 25.97 |
AIRLOOP DATACENTER BOT SUPPLY FAN | 0.580616 |
AIRLOOP DATACENTER MID SUPPLY FAN | 5.54 |
AIRLOOP DATACENTER TOP SUPPLY FAN | 0.566403 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Heating Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | 25.97 | 475527.81 | 0.011646 |
AIRLOOP DATACENTER BOT HEATING COIL | 0.580616 | 10356.64 | 0.000254 |
AIRLOOP DATACENTER MID HEATING COIL | 5.54 | 98913.37 | 0.002422 |
AIRLOOP DATACENTER TOP HEATING COIL | 0.566403 | 10106.03 | 0.000247 |
Design Size Nominal Capacity [W] | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | 16131.55 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | 745.21 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | 7452.11 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | 745.21 |
Design Size Nominal Capacity Volume [m3/s] | User-Specified Nominal Capacity Volume [m3/s] | Design Size Rated Power [W] | User-Specified Rated Power [W] | |
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | 0.000140 | 0.000037 | 96450.70 | 100000.00 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.091508 | 18856.31 | |
HEATSYS1 PUMP | 0.018928 | 5700.24 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.091508 | 10.98 |
HEATSYS1 | 0.018928 | 2.27 |
COOLSYS1_SUPPLY | 0.091508 | 10.98 |
SINGLE WATER PLANT LOOP | 0.014569 | 1.75 |
SWHSYS1 | 0.000440 | 0.052800 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.091508 | 0.091508 | 384103.07 | 5.60 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 2163571.87 | 2163571.87 | 0.018928 |
CENTRAL BOILER | 600124.37 | 586379.63 | 0.014569 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP | 0.091508 | 13054.86 |
PLANT CIRC PUMP | 0.014569 | 3715.86 |
SWHSYS1 PUMP | 0.000440 | 5.96 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Water Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.091508 | 0.046437 | 1094231.11 | 1099421.64 | 0.054406 |
COOLSYS1 CHILLER2 | 0.091508 | 0.046437 | 1094231.11 | 1099421.64 | 0.054406 |
Design Water Flow Rate [m3/s] | Air Flow Rate at High Fan Speed [m3/s] | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | Air Flow Rate at Low Fan Speed [m3/s] | Fan Power at Low Fan Speed [W] | U-factor Times Area Value at Low Fan Speed [W/C] | |
CENTRAL TOWER | 0.014569 | 139666.47 | 55090.86 | 69833.23 | 7879.72 | 20969.37 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000440 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.108813 | 13.06 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.108813 | 32771.99 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 51.13 | 1306047.12 | 10.23 | 163255.89 |
TOWERWATERSYS COOLTOWER 2 | 51.13 | 1306047.12 | 10.23 | 163255.89 |
Design Water Flow Rate [m3/s] Equipment # 47 | |
WSHPPLANT OPERATION SCHEME | 0.056510 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:19
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:19
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:19
VersionVersion ID | |
1 | 22.1.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.70 | 7.00 | 2.10 | 2.60 | 4.30 | 8.80 | 13.90 | 17.80 | 23.20 | 25.60 | 24.10 | 20.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Albuquerque Intl Sunport NM USA TMY3 WMO#=723650 | 35.04 | -106.62 | -7.00 | 1619.00 | 83328 | 0.9904 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 13.63 | 23.50 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 105.88 | 86.92 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 71.89 | 57.95 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 105.88 | 86.92 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 71.89 | 57.95 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 7.620 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 12.462 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 12.511 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 227.811 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 12.511 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 227.811 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 12.511 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 227.811 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 18.579 | 5.382E-002 | 7.620 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 492.043 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DATACENTER_BOT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | DATACENTER_MID_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | DATACENTER_TOP_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | DATACENTER_BASEMENT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 42.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 42 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_OFFICE | BASEMENT | 2779.43 | 149.6 | 21179.739 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 21179.739 |
2 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 2496.12 | 134.4 | 19020.895 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 19020.895 |
3 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 2496.12 | 134.4 | 19020.895 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 19020.895 |
4 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 2496.12 | 134.4 | 19020.895 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 19020.895 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2388.263 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2388.263 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1539.088 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1539.088 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2388.315 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2388.315 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1539.088 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1539.088 |
9 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2388.263 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2388.263 |
10 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1539.088 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1539.088 |
11 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2388.315 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2388.315 |
12 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1539.088 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1539.088 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2388.263 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2388.263 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1539.088 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1539.088 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2388.315 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2388.315 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1539.088 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1539.088 |
17 | DATACENTER_BASEMENT_LIGHTS | LTG_SCH_OFFICE | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 5971.780 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5971.780 |
18 | DATACENTER_BOT_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 452.948 | 12.511 | 232.447 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 452.948 |
19 | DATACENTER_MID_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 452.948 | 12.511 | 232.447 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 452.948 |
20 | DATACENTER_TOP_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 452.948 | 12.511 | 232.447 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 452.948 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 379632.522 | 484.423 | 9000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.464 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
9 | NONRES_EXT_WALL_GRD | 20 | 3 | 9 | 0.167 | 1.339 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | NONRES_EXT_WALL_MID | 21 | 3 | 9 | 0.167 | 1.260 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | NONRES_EXT_WALL_TOP | 22 | 3 | 9 | 0.167 | 1.694 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | BASEMENT_WALL_EAST_CFACTOR | 39 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_SOUTH_CFACTOR | 40 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BASEMENT_WALL_NORTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 42 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 43 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 44 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2887 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5795 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6262 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4230 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
32 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
33 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
34 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
35 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.4637404 | 3.4637404 | 3.4637404 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
47 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
48 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
49 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
50 | 9 | 0.13684007E-14 | 0.43769670E-16 | -0.13032795E-09 | -0.34517937E-17 |
51 | 8 | 0.19139952E-07 | 0.17580734E-12 | 0.34842432E-03 | -0.21762784E-09 |
52 | 7 | -0.11363040E-01 | 0.94207812E-08 | -0.21820187E-01 | 0.12920189E-03 |
53 | 6 | 0.38147639 | 0.33245073E-05 | 0.45170425 | -0.44663469E-02 |
54 | 5 | -4.9575440 | 0.12566514E-03 | -4.2844407 | 0.60294545E-01 |
55 | 4 | 31.971915 | 0.10393916E-02 | 20.826829 | -0.40843520 |
56 | 3 | -109.03212 | 0.22875987E-02 | -54.410870 | 1.4834967 |
57 | 2 | 194.95586 | 0.12980373E-02 | 76.763178 | -2.8661744 |
58 | 1 | -170.36074 | 0.13969006E-03 | -54.933270 | 2.7315001 |
59 | 0 | 57.057407 | 0.80219562E-06 | 15.613236 | |
60 | 9 | 0.17296484E-14 | 0.42300129E-16 | -0.13408130E-09 | -0.44058463E-17 |
61 | 8 | 0.19671007E-07 | 0.16641005E-12 | 0.35423406E-03 | -0.22366611E-09 |
62 | 7 | -0.11537194E-01 | 0.88593938E-08 | -0.22071206E-01 | 0.13118209E-03 |
63 | 6 | 0.38620962 | 0.31182457E-05 | 0.45575528 | -0.45221398E-02 |
64 | 5 | -5.0037487 | 0.11760487E-03 | -4.3156427 | 0.60867449E-01 |
65 | 4 | 32.176377 | 0.97077592E-03 | 20.948989 | -0.41114975 |
66 | 3 | -109.46738 | 0.21328008E-02 | -54.652468 | 1.4897847 |
67 | 2 | 195.38754 | 0.12083052E-02 | 76.984396 | -2.8730290 |
68 | 1 | -170.52030 | 0.12984550E-03 | -54.996922 | 2.7342967 |
69 | 0 | 57.057407 | 0.74448799E-06 | 15.602172 | |
70 | 9 | 0.10997584E-14 | 0.53843923E-16 | -0.11326114E-09 | -0.28570046E-17 |
71 | 8 | 0.16725364E-07 | 0.21557791E-12 | 0.32127585E-03 | -0.19017314E-09 |
72 | 7 | -0.10546704E-01 | 0.11930081E-07 | -0.20642631E-01 | 0.11991984E-03 |
73 | 6 | 0.35928609 | 0.42648229E-05 | 0.43264702 | -0.42047803E-02 |
74 | 5 | -4.7408821 | 0.16300219E-03 | -4.1373754 | 0.57608138E-01 |
75 | 4 | 31.012880 | 0.13615538E-02 | 20.250423 | -0.39570291 |
76 | 3 | -106.98970 | 0.30226891E-02 | -53.270634 | 1.4539929 |
77 | 2 | 192.92930 | 0.17282771E-02 | 75.720319 | -2.8339965 |
78 | 1 | -169.61128 | 0.18730106E-03 | -54.635416 | 2.7183650 |
79 | 0 | 57.057407 | 0.10839563E-05 | 15.666826 | |
80 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
81 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
82 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
83 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
84 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
85 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
86 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
87 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
88 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
89 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
90 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
91 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
92 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
93 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
94 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
95 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
96 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
97 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
98 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
99 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
100 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
101 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
102 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
103 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
104 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
105 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
106 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
107 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
108 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
109 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
110 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
111 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
112 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
113 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
114 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
115 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
116 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
117 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
118 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
119 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
120 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
121 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
122 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
123 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
124 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
125 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
126 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
127 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.3822_SHGC_EAST_0.36 | 35 | 1 | VerySmooth | 2.171 | 2.171 | 1.000 | 0.361 | ||
2 | WINDOW_U_0.3822_SHGC_SOUTH_0.36 | 36 | 1 | VerySmooth | 2.171 | 2.171 | 1.000 | 0.361 | ||
3 | WINDOW_U_0.3822_SHGC_WEST_0.36 | 37 | 1 | VerySmooth | 2.171 | 2.171 | 1.000 | 0.361 | ||
4 | WINDOW_U_0.3822_SHGC_NORTH_0.36 | 38 | 1 | VerySmooth | 2.171 | 2.171 | 1.000 | 0.361 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 3.43662E-002 | 0.27318 | 0.51756 | 0.51756 | 0.36000 | 0.14234 | 0.19141 | 0.00000 | 0.84000 | 0.84000 | 0.11924 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 3.43662E-002 | 0.27318 | 0.51756 | 0.51756 | 0.36000 | 0.14234 | 0.19141 | 0.00000 | 0.84000 | 0.84000 | 0.11924 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 3.43662E-002 | 0.27318 | 0.51756 | 0.51756 | 0.36000 | 0.14234 | 0.19141 | 0.00000 | 0.84000 | 0.84000 | 0.11924 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 3.43662E-002 | 0.27318 | 0.51756 | 0.51756 | 0.36000 | 0.14234 | 0.19141 | 0.00000 | 0.84000 | 0.84000 | 0.11924 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_BOT_ZN_3 | 5 | 0 |
2 | PERIMETER_BOT_ZN_2 | 3 | 0 |
3 | PERIMETER_BOT_ZN_1 | 5 | 0 |
4 | PERIMETER_BOT_ZN_4 | 3 | 0 |
5 | PERIMETER_MID_ZN_3 | 1 | 0 |
6 | PERIMETER_MID_ZN_2 | 1 | 0 |
7 | PERIMETER_MID_ZN_1 | 1 | 0 |
8 | PERIMETER_MID_ZN_4 | 1 | 0 |
9 | PERIMETER_TOP_ZN_3 | 1 | 0 |
10 | PERIMETER_TOP_ZN_2 | 1 | 0 |
11 | PERIMETER_TOP_ZN_1 | 1 | 0 |
12 | PERIMETER_TOP_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_BOT_ZN_3 | 0 | |
2 | PERIMETER_BOT_ZN_2 | 0 | |
3 | PERIMETER_BOT_ZN_1 | 0 | |
4 | PERIMETER_BOT_ZN_4 | 0 | |
5 | PERIMETER_MID_ZN_3 | 0 | |
6 | PERIMETER_MID_ZN_2 | 0 | |
7 | PERIMETER_MID_ZN_1 | 0 | |
8 | PERIMETER_MID_ZN_4 | 0 | |
9 | PERIMETER_TOP_ZN_3 | 0 | |
10 | PERIMETER_TOP_ZN_2 | 0 | |
11 | PERIMETER_TOP_ZN_1 | 0 | |
12 | PERIMETER_TOP_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 1.1356 | 87921.3 | 0.496 | 7.5104E-002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 4.384E-005 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.3860E-003 |
2 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.3877E-003 |
3 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.7646E-003 |
4 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.7661E-003 |
5 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.2096E-003 |
6 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.2108E-003 |
7 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.7698E-003 |
8 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.7704E-003 |
9 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.4263E-003 |
10 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.5465E-003 |
11 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.7986E-003 |
12 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.9037E-003 |
13 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.2388E-003 |
14 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.3257E-003 |
15 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.7873E-003 |
16 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.8319E-003 |
17 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1196 |
18 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.8845E-002 |
19 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1355 |
20 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.5656E-002 |
21 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 9.0371E-002 |
22 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.6353E-002 |
23 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.7170E-002 |
24 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.3047E-002 |
25 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.4280E-003 |
26 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.5543E-003 |
27 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.8003E-003 |
28 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.9115E-003 |
29 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.2403E-003 |
30 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.3313E-003 |
31 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.7877E-003 |
32 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.8332E-003 |
33 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.3858E-003 |
34 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.3876E-003 |
35 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.7644E-003 |
36 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.7659E-003 |
37 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.2095E-003 |
38 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.2107E-003 |
39 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.7697E-003 |
40 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.7704E-003 |
41 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.8299E-003 |
42 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.0528E-003 |
43 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.6131E-003 |
44 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.8530E-003 |
45 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.4827E-003 |
46 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.5867E-003 |
47 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.0284E-003 |
48 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.0591E-003 |
49 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.3479E-002 |
50 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.2194E-002 |
51 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.0362E-002 |
52 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.9896E-002 |
53 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.5737E-002 |
54 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.9221E-002 |
55 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.8227E-002 |
56 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.4292E-002 |
57 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.7647E-003 |
58 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.8465E-003 |
59 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.5292E-003 |
60 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.5885E-003 |
61 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.4496E-003 |
62 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.4728E-003 |
63 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.0285E-003 |
64 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.0596E-003 |
65 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.8157E-003 |
66 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8174E-003 |
67 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5441E-003 |
68 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5454E-003 |
69 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.3660E-003 |
70 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3669E-003 |
71 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7698E-003 |
72 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7704E-003 |
73 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.8531E-003 |
74 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.9507E-003 |
75 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5744E-003 |
76 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.6511E-003 |
77 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.3903E-003 |
78 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.4442E-003 |
79 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7878E-003 |
80 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8333E-003 |
81 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.8930E-002 |
82 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.6752E-002 |
83 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.2371E-002 |
84 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2695E-002 |
85 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.2483E-002 |
86 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 8.9379E-003 |
87 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.7170E-002 |
88 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3043E-002 |
89 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.8521E-003 |
90 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.9483E-003 |
91 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5734E-003 |
92 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.6487E-003 |
93 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.3891E-003 |
94 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.4408E-003 |
95 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7873E-003 |
96 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8320E-003 |
97 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.8156E-003 |
98 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8172E-003 |
99 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5440E-003 |
100 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5453E-003 |
101 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.3659E-003 |
102 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3668E-003 |
103 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7697E-003 |
104 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7704E-003 |
105 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.6979E-003 |
106 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.7802E-003 |
107 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.4464E-003 |
108 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.5059E-003 |
109 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.3938E-003 |
110 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.4166E-003 |
111 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.0286E-003 |
112 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.0596E-003 |
113 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.2184E-002 |
114 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.1678E-002 |
115 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.8773E-002 |
116 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.9263E-002 |
117 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.4581E-002 |
118 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.8756E-002 |
119 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.8227E-002 |
120 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.4292E-002 |
121 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.7608E-003 |
122 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.9745E-003 |
123 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.5274E-003 |
124 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.7558E-003 |
125 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.4264E-003 |
126 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.5287E-003 |
127 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.0283E-003 |
128 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.0590E-003 |
129 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1090 |
130 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 7.5388E-002 |
131 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1192 |
132 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 8.3241E-002 |
133 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 9.3368E-002 |
134 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 4.9843E-002 |
135 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 4.2949E-002 |
136 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 2.0811E-002 |
137 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.0110E-002 |
138 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.0676E-002 |
139 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.6719E-002 |
140 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.7948E-002 |
141 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.1972E-002 |
142 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.6919E-002 |
143 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.3948E-002 |
144 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.1031E-002 |
145 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.4588E-002 |
146 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.4431E-002 |
147 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.7447E-002 |
148 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.9285E-002 |
149 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.7506E-002 |
150 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.4992E-002 |
151 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.2949E-002 |
152 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.0807E-002 |
153 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 4.8707E-002 |
154 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.0000E-002 |
155 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 4.4993E-002 |
156 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.7115E-002 |
157 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.0730E-002 |
158 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.6331E-002 |
159 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 4.3948E-002 |
160 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.1031E-002 |
161 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1089 |
162 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 7.5496E-002 |
163 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1191 |
164 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 8.3371E-002 |
165 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 9.3388E-002 |
166 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 4.9944E-002 |
167 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 4.2998E-002 |
168 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 2.0851E-002 |
169 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.0082E-002 |
170 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.0702E-002 |
171 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.6703E-002 |
172 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.7974E-002 |
173 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.1989E-002 |
174 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.6965E-002 |
175 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.3994E-002 |
176 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.1071E-002 |
177 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.4543E-002 |
178 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.4440E-002 |
179 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.7416E-002 |
180 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.9293E-002 |
181 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.7519E-002 |
182 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.5014E-002 |
183 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.2998E-002 |
184 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.0847E-002 |
185 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 4.8678E-002 |
186 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.0025E-002 |
187 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 4.4975E-002 |
188 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.7140E-002 |
189 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.0746E-002 |
190 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.6376E-002 |
191 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 4.3994E-002 |
192 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.1071E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 73618.21668 | 73618.21668 | 6.46543 | 6.46543 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 25.11000 | 5.68410E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20016 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:10:00 | -7.90000 | 2.34317E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
3 | CORE_BOTTOM | Cooling | 77690.56451 | 77690.56451 | 6.82248 | 6.82248 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 25.11000 | 5.68410E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
4 | CORE_BOTTOM | Heating | 0.00000 | 0.00000 | 0.00000 | 1.07782 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:20:00 | -7.90000 | 2.34317E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
5 | CORE_MID | Cooling | 729106.46231 | 729106.46231 | 64.01238 | 64.01238 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 25.11000 | 5.68410E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
6 | CORE_MID | Heating | 253236.48383 | 253236.48383 | 12.99806 | 12.99806 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
7 | CORE_TOP | Cooling | 72139.69664 | 72139.69664 | 6.39016 | 6.39016 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 35.10000 | 5.69938E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
8 | CORE_TOP | Heating | 57544.02644 | 57544.02644 | 2.97493 | 2.97493 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 12984.99773 | 12984.99773 | 1.15018 | 1.15018 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 35.10000 | 5.69938E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 7484.89292 | 7484.89292 | 0.38703 | 0.38703 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 14632.23749 | 14632.23749 | 1.29608 | 1.29608 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 27.67500 | 5.68796E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 5299.36933 | 5299.36933 | 0.27414 | 0.27414 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 15737.78161 | 15737.78161 | 1.39401 | 1.39401 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 34.65000 | 5.69869E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 9004.20583 | 9004.20583 | 0.46592 | 0.46592 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 18706.82028 | 18706.82028 | 1.65699 | 1.65699 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 33.39000 | 5.69673E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 3676.39126 | 3676.39126 | 0.18977 | 0.18977 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
17 | PERIMETER_MID_ZN_3 | Cooling | 122329.06721 | 122329.06721 | 10.83547 | 10.83547 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 35.10000 | 5.69938E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 143027.24814 | 143027.24814 | 7.41290 | 7.41290 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 153462.58776 | 153462.58776 | 13.59305 | 13.59305 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 28.44000 | 5.68912E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 94913.89501 | 94913.89501 | 4.91963 | 4.91963 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 150680.89525 | 150680.89525 | 13.34675 | 13.34675 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 34.76250 | 5.69886E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 141797.90161 | 141797.90161 | 7.34901 | 7.34901 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 165592.07635 | 165592.07635 | 14.66744 | 14.66744 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 33.21000 | 5.69645E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 89695.96167 | 89695.96167 | 4.64849 | 4.64849 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 14184.37004 | 14184.37004 | 1.25639 | 1.25639 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 35.10000 | 5.69938E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 18754.26281 | 18754.26281 | 0.97260 | 0.97260 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 15600.53627 | 15600.53627 | 1.38182 | 1.38182 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 29.20500 | 5.69029E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 12374.92766 | 12374.92766 | 0.64179 | 0.64179 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 16868.21667 | 16868.21667 | 1.49411 | 1.49411 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 34.98750 | 5.69921E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 18599.98441 | 18599.98441 | 0.96458 | 0.96458 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 17887.43751 | 17887.43751 | 1.58438 | 1.58438 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 33.21000 | 5.69645E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 11969.36882 | 11969.36882 | 0.62072 | 0.62072 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90000 | 2.34317E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 8310.44868 | 8310.44868 | 0.58062 | 0.58062 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 30.51000 | 5.69229E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:30:00 | -7.90000 | 2.34317E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
35 | DATACENTER_MID_ZN_6 | Cooling | 79328.68976 | 79328.68976 | 5.54240 | 5.54240 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 30.17250 | 5.69177E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15632 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | -7.90000 | 2.34317E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
37 | DATACENTER_TOP_ZN_6 | Cooling | 8106.99375 | 8106.99375 | 0.56640 | 0.56640 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 30.51000 | 5.69229E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | -7.90000 | 2.34317E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 371690.88721 | 371690.88721 | 25.96802 | 25.96802 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 22.81500 | 5.68069E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33839 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:40:00 | -7.90000 | 2.34317E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV_BOT WITH REHEAT | Cooling | Sensible | 146727.99 | 11.11792 | 11.11792 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV_BOT WITH REHEAT | Heating | Sensible | 49333.16 | 2.39469 | 2.39469 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 |
3 | VAV_MID WITH REHEAT | Cooling | Sensible | 1349665.02 | 103.18914 | 103.18914 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | VAV_MID WITH REHEAT | Heating | Sensible | 519288.82 | 37.32809 | 37.32809 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:30:00 |
5 | VAV_TOP WITH REHEAT | Cooling | Sensible | 154636.02 | 11.39510 | 11.39510 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | VAV_TOP WITH REHEAT | Heating | Sensible | 52128.29 | 6.17463 | 6.17463 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 22:20:00 |
7 | CAV_BAS | Cooling | Sensible | 76174.85 | 6.46543 | 6.46543 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | CAV_BAS | Heating | Sensible | 57212.75 | 1.20016 | 1.20016 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
9 | AIRLOOP DATACENTER BASEMENT | Cooling | Sensible | 369211.21 | 25.96838 | 25.96838 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | AIRLOOP DATACENTER BASEMENT | Heating | Sensible | 16131.55 | 0.33839 | 0.33839 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
11 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 8258.99 | 0.58062 | 0.58062 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | AIRLOOP DATACENTER BOT | Heating | Sensible | 745.21 | 1.56323E-002 | 1.56323E-002 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
13 | AIRLOOP DATACENTER MID | Cooling | Sensible | 78859.70 | 5.54240 | 5.54240 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | AIRLOOP DATACENTER MID | Heating | Sensible | 7452.11 | 0.15632 | 0.15632 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
15 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 8058.13 | 0.56640 | 0.56640 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
16 | AIRLOOP DATACENTER TOP | Heating | Sensible | 745.21 | 1.56323E-002 | 1.56323E-002 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | BASEMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.46543 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 6.82248 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.27879 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.29400 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.00581 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.74344 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.36662E-003 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.45320E-004 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.00581 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
13 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 16610.98594 |
14 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.45320E-004 |
15 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 334.86444 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 64.01238 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.29714 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30700 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 19.65180 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.79237 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.28224E-003 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.63919E-003 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 19.65180 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
27 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 415981.63634 |
28 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.63919E-003 |
29 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 9930.93611 |
30 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 6.39016 |
31 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.29765 |
32 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.31600 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.01929 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.79374 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.28002E-003 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.18953E-004 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.97493 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
40 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
41 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 82180.71875 |
42 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.18953E-004 |
43 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2169.11215 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.15018 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20764 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.21900 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.25189 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.55370 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.83493E-003 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.34897E-005 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.38703 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
55 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10686.44982 |
56 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.34897E-005 |
57 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 282.00025 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.29608 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11875 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.25922 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.31666 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.20851E-003 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.62031E-005 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.27414 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
69 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7567.42442 |
70 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.62031E-005 |
71 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 199.67143 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.39401 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17132 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.27880 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.45686 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.22388E-003 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.12502E-004 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.46592 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
83 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12859.68370 |
84 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.12502E-004 |
85 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 339.28895 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.65699 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.28823E-002 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.33140 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.10197E-003 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.61267E-005 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.33140 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
97 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6415.62565 |
98 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.61267E-005 |
99 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 149.22830 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 10.83547 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22041 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.22800 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.47049 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.58775 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.72863E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.78787E-003 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 7.41290 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 204364.43267 |
112 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.78787E-003 |
113 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 5389.10003 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 13.59305 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11322 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.71861 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30193 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.36503E-003 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.18647E-003 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 4.91963 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
124 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
125 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 135620.64917 |
126 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.18647E-003 |
127 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 3576.23398 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 13.34675 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17894 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.66935 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.47717 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.12921E-003 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.77249E-003 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 7.34901 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
138 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
139 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 202605.98994 |
140 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.77249E-003 |
141 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 5342.76670 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 14.66744 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10493 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.93349 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.63100E-003 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.12118E-003 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 4.64849 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
152 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
153 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 128157.39720 |
154 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.12118E-003 |
155 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 3379.56929 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.25639 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19008 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20200 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.25379 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.50689 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.00437E-003 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.34476E-004 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.97260 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
166 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
167 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 26802.04320 |
168 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.34476E-004 |
169 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 706.63553 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.38182 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11138 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.27636 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.42077E-003 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.54720E-004 |
178 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.64179 |
179 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
180 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
181 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 17685.40706 |
182 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.54720E-004 |
183 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 466.26805 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.49411 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15984 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.29882 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.42625 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.38357E-003 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.32546E-004 |
192 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.96458 |
193 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
194 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
195 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 26581.38231 |
196 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.32546E-004 |
197 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 700.82123 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.58438 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.71389E-002 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.31688 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.92222E-003 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.49645E-004 |
206 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.62072 |
207 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
208 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
209 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 17105.39638 |
210 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.49645E-004 |
211 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 450.98339 |
212 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BOT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.58062 |
213 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_MID_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 5.54240 |
214 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_TOP_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.56640 |
215 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BASEMENT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 25.96802 |
216 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 6.15987 |
217 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.12712 |
218 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 12.31975 |
219 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 3.12712 |
220 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 11.11792 |
221 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 11.11792 |
222 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
223 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.28127 |
224 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 58.22754 |
225 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 30.44373 |
226 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 116.45509 |
227 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 37.32809 |
228 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 103.18914 |
229 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 103.18914 |
230 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
231 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.36174 |
232 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 6.05343 |
233 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.16515 |
234 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 12.10687 |
235 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 6.17463 |
236 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 11.39510 |
237 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 11.39510 |
238 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
239 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.54187 |
240 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 6.46543 |
241 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 6.46543 |
242 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 6.46543 |
243 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 6.46543 |
244 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 6.46543 |
245 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 6.46543 |
246 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
247 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
248 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 25.96802 |
249 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 25.96802 |
250 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 25.96802 |
251 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Heating Design Air Flow Rate [m3/s] | 25.96802 |
252 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Cooling Design Air Flow Rate [m3/s] | 25.96838 |
253 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Main Design Air Flow Rate [m3/s] | 25.96838 |
254 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | User Heating Air Flow Ratio [] | 1.00000 |
255 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Calculated Heating Air Flow Ratio [] | 0.99999 |
256 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.58062 |
257 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.58062 |
258 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.58062 |
259 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.58062 |
260 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.58062 |
261 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.58062 |
262 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
263 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
264 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.54240 |
265 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 5.54240 |
266 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.54240 |
267 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 5.54240 |
268 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.54240 |
269 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 5.54240 |
270 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
271 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
272 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.56640 |
273 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.56640 |
274 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.56640 |
275 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.56640 |
276 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.56640 |
277 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.56640 |
278 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
279 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
280 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 11.11792 |
281 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 103.18914 |
282 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 11.39510 |
283 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 6.46543 |
284 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Design Supply Air Flow Rate [m3/s] | 25.96838 |
285 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.58062 |
286 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 5.54240 |
287 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.56640 |
288 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 11.11792 |
289 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.64472 |
290 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
291 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.66760 |
292 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 6.95250E-003 |
293 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 6.95250E-003 |
294 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 179053.87080 |
295 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 7.61737E-003 |
296 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 11.11792 |
297 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 53316.12834 |
298 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.66433E-004 |
299 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 877.63180 |
300 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 11.11792 |
301 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 7.61737E-003 |
302 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 6.25138E-005 |
303 | Controller:WaterCoil | VAV_BOT WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.66433E-004 |
304 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 103.18914 |
305 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.93584 |
306 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
307 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.66749 |
308 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 6.92461E-003 |
309 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 6.92461E-003 |
310 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 1692065.48002 |
311 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 7.19844E-002 |
312 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 103.18914 |
313 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 487107.31805 |
314 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.26143E-003 |
315 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 8029.19748 |
316 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 103.18914 |
317 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 7.19844E-002 |
318 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 6.61519E-006 |
319 | Controller:WaterCoil | VAV_MID WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.26143E-003 |
320 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 11.39510 |
321 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.47954 |
322 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
323 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.66757 |
324 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 6.94504E-003 |
325 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 6.94504E-003 |
326 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 181618.42894 |
327 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 7.72647E-003 |
328 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 11.39510 |
329 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 45106.12882 |
330 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.94608E-004 |
331 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 754.78106 |
332 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 11.39510 |
333 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 7.72647E-003 |
334 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 6.16311E-005 |
335 | Controller:WaterCoil | VAV_TOP WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.94608E-004 |
336 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 6.46543 |
337 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.20016 |
338 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.18716 |
339 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
340 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.11838 |
341 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.13998E-003 |
342 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.13998E-003 |
343 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Coil Load [W] | 98239.40048 |
344 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.17933E-003 |
345 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 6.46543 |
346 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Rated Capacity [W] | 266817.06793 |
347 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.33423E-003 |
348 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 5910.30602 |
349 | Fan:ConstantVolume | CAV_BAS FAN | Design Size Maximum Flow Rate [m3/s] | 6.46543 |
350 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.17933E-003 |
351 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.13939E-004 |
352 | Controller:WaterCoil | CAV_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.33423E-003 |
353 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 25.96838 |
354 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.33839 |
355 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 25.96838 |
356 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 475527.80780 |
357 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 252201.14688 |
358 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.16456E-002 |
359 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 25.96838 |
360 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 25.96838 |
361 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 25.96838 |
362 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 25.96838 |
363 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 475527.80780 |
364 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 475527.80780 |
365 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 16131.54879 |
366 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
367 | Fan:OnOff | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 25.96838 |
368 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 25.96838 |
369 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Heating Capacity [W] | 475527.80780 |
370 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.16456E-002 |
371 | Coil:Heating:Electric | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 16131.54879 |
372 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Nominal Capacity Volume [m3/s] | 1.40446E-004 |
373 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Nominal Capacity Volume [m3/s] | 3.72000E-005 |
374 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Rated Power [W] | 96450.69782 |
375 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Rated Power [W] | 100000.00000 |
376 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.58062 |
377 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
378 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.58062 |
379 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 10356.63653 |
380 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 5543.42048 |
381 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.53633E-004 |
382 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.58062 |
383 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.58062 |
384 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.58062 |
385 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.58062 |
386 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 10356.63653 |
387 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 10356.63653 |
388 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 745.21073 |
389 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
390 | Fan:OnOff | AIRLOOP DATACENTER BOT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.58062 |
391 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.58062 |
392 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Heating Capacity [W] | 10356.63653 |
393 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.53633E-004 |
394 | Coil:Heating:Electric | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 745.21073 |
395 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.54240 |
396 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.15632 |
397 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 5.54240 |
398 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 98913.37173 |
399 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 52928.83834 |
400 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.42238E-003 |
401 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 5.54240 |
402 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 5.54240 |
403 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 5.54240 |
404 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 5.54240 |
405 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Heating Capacity [W] | 98913.37173 |
406 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 98913.37173 |
407 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 7452.10725 |
408 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
409 | Fan:OnOff | AIRLOOP DATACENTER MID SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 5.54240 |
410 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 5.54240 |
411 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Heating Capacity [W] | 98913.37173 |
412 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.42238E-003 |
413 | Coil:Heating:Electric | AIRLOOP DATACENTER MID_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 7452.10725 |
414 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.56640 |
415 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
416 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.56640 |
417 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 10106.03285 |
418 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 5408.44460 |
419 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.47496E-004 |
420 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.56640 |
421 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.56640 |
422 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.56640 |
423 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.56640 |
424 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Heating Capacity [W] | 10106.03285 |
425 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 10106.03285 |
426 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 745.21073 |
427 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
428 | Fan:OnOff | AIRLOOP DATACENTER TOP SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.56640 |
429 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.56640 |
430 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Heating Capacity [W] | 10106.03285 |
431 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.47496E-004 |
432 | Coil:Heating:Electric | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 745.21073 |
433 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 9.15075E-002 |
434 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 18856.31275 |
435 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 9.15075E-002 |
436 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 10.98090 |
437 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 9.15075E-002 |
438 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 9.15075E-002 |
439 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 384103.06790 |
440 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 5.60000 |
441 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 1.89279E-002 |
442 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 2.27134 |
443 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 1.89279E-002 |
444 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 5700.24338 |
445 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
446 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 2163571.86569 |
447 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 2163571.87000 |
448 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 1.89279E-002 |
449 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 9.15075E-002 |
450 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 10.98090 |
451 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 9.15075E-002 |
452 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 13054.86138 |
453 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 9.15075E-002 |
454 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 4.64371E-002 |
455 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1094231.11495 |
456 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1099421.64000 |
457 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Water Flow Rate [m3/s] | 5.44063E-002 |
458 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 9.15075E-002 |
459 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 4.64371E-002 |
460 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 1094231.11495 |
461 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 1099421.64000 |
462 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Water Flow Rate [m3/s] | 5.44063E-002 |
463 | PlantLoop | SINGLE WATER PLANT LOOP | Maximum Loop Flow Rate [m3/s] | 1.45692E-002 |
464 | PlantLoop | SINGLE WATER PLANT LOOP | Plant Loop Volume [m3] | 1.74830 |
465 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Flow Rate [m3/s] | 1.45692E-002 |
466 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Power Consumption [W] | 3715.86359 |
467 | FluidCooler:TwoSpeed | CENTRAL TOWER | Design Water Flow Rate [m3/s] | 1.45692E-002 |
468 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at High Fan Speed [m3/s] | 139666.46671 |
469 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | 55090.86339 |
470 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at Low Fan Speed [m3/s] | 69833.23335 |
471 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fan Power at Low Fan Speed [W] | 7879.72339 |
472 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at Low Fan Speed [W/C] | 20969.37107 |
473 | Boiler:HotWater | CENTRAL BOILER | Design Size Nominal Capacity [W] | 600124.36510 |
474 | Boiler:HotWater | CENTRAL BOILER | User-Specified Nominal Capacity [W] | 586379.63000 |
475 | Boiler:HotWater | CENTRAL BOILER | Design Size Design Water Flow Rate [m3/s] | 1.45692E-002 |
476 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
477 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
478 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
479 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 5.95776 |
480 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
481 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 0.10881 |
482 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 13.05751 |
483 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 0.10881 |
484 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 32771.98829 |
485 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 51.12741 |
486 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 1306047.12035 |
487 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 10.22548 |
488 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 163255.89004 |
489 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 51.12741 |
490 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 1306047.12035 |
491 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 10.22548 |
492 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 163255.89004 |
493 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 5.65100E-002 |
494 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 5.65100E-002 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 15753.04 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 394248.70 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 77903.99 |
4 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 10129.90 |
5 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 7173.16 |
6 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 12189.55 |
7 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 6080.89 |
8 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 193695.53 |
9 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 128539.93 |
10 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 192029.14 |
11 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 121467.26 |
12 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 25401.92 |
13 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 16761.48 |
14 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 25192.81 |
15 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 16211.82 |
16 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | 41063.42 |
17 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | 376248.26 |
18 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | 35914.78 |
19 | Coil:Heating:Water | CAV_BAS HEATING COIL | 210327.33 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | 239894.09 | 152164.94 | 87729.16 | 0.63 | 24516.32 | 248.66 |
2 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | 2244186.17 | 1419184.21 | 825001.96 | 0.63 | 228688.00 | 2319.48 |
3 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | 244744.70 | 155517.77 | 89226.93 | 0.64 | 25054.68 | 254.12 |
4 | Coil:Cooling:Water | CAV_BAS COOLING COIL | 132559.15 | 85359.71 | 47199.43 | 0.64 | 13074.81 | 132.61 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | 6.84 | 23.33 |
2 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | 6.84 | 23.33 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.419 | 0.394 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.339 | 1.115 | 105.88 | 200.61 | 105.88 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.36 | N/A | 2.171 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.36 | N/A | 2.171 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.36 | N/A | 2.171 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.36 | N/A | 2.171 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.36 | N/A | 2.171 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.339 | 1.115 | 71.89 | 133.74 | 71.89 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_EAST_0.36 | N/A | 2.171 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_EAST_0.36 | N/A | 2.171 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_EAST_0.36 | N/A | 2.171 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.339 | 1.115 | 105.88 | 200.61 | 105.88 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.36 | N/A | 2.171 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.36 | N/A | 2.171 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.36 | N/A | 2.171 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.36 | N/A | 2.171 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.36 | N/A | 2.171 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.339 | 1.115 | 71.89 | 133.74 | 71.89 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_WEST_0.36 | N/A | 2.171 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_WEST_0.36 | N/A | 2.171 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_WEST_0.36 | N/A | 2.171 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.260 | 1.060 | 113.68 | 200.61 | 113.68 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.36 | N/A | 2.171 | No | 86.92 | 86.92 | 86.92 | 0.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.260 | 1.060 | 75.79 | 133.74 | 75.79 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_EAST_0.36 | N/A | 2.171 | No | 57.95 | 57.95 | 57.95 | 90.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.260 | 1.060 | 113.68 | 200.61 | 113.68 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.36 | N/A | 2.171 | No | 86.92 | 86.92 | 86.92 | 180.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.260 | 1.060 | 75.79 | 133.74 | 75.79 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_WEST_0.36 | N/A | 2.171 | No | 57.95 | 57.95 | 57.95 | 270.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.694 | 1.351 | 113.68 | 200.61 | 113.68 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.36 | N/A | 2.171 | No | 86.92 | 86.92 | 86.92 | 0.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.694 | 1.351 | 75.79 | 133.74 | 75.79 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_EAST_0.36 | N/A | 2.171 | No | 57.95 | 57.95 | 57.95 | 90.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.694 | 1.351 | 113.68 | 200.61 | 113.68 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.36 | N/A | 2.171 | No | 86.92 | 86.92 | 86.92 | 180.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.694 | 1.351 | 75.79 | 133.74 | 75.79 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_WEST_0.36 | N/A | 2.171 | No | 57.95 | 57.95 | 57.95 | 270.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.339 | 1.115 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.339 | 1.115 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.339 | 1.115 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.339 | 1.115 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.260 | 1.060 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.260 | 1.060 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.260 | 1.060 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.260 | 1.060 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.694 | 1.351 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.694 | 1.351 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.694 | 1.351 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.694 | 1.351 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.419 | 0.394 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 0.2788375137 | 0.2405333009 | Pass | Pass | 1.3305410724 | 3.0920403239 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 0.1122257707 | 0.1864808097 | Pass | Pass | 0.1539149177 | 0.3601646601 | Pass | Pass |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 5.7712429129E-002 | 0.1149175249 | Pass | Pass | 0.1193918792 | 0.3235098550 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 6.8520715871E-002 | 5.8012409946E-002 | Pass | Pass | 0.2287461586 | 0.4170708359 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 8.3080498773E-002 | 0.1204159551 | Pass | Pass | 0.1532230408 | 0.3586688221 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1843473329 | 0.2447560169 | Pass | Pass | 0.1556100668 | 0.3626591713 | Pass | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2505645133 | 0.4069998268 | Pass | Pass | 0.1640116322 | 0.3811300176 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1768983714 | 0.2936845503 | Pass | Pass | 0.1528904627 | 0.3543871744 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 5.2174321015E-002 | 5.4382544735E-002 | Pass | Pass | 0.1184592418 | 0.3210913785 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1345213650 | 0.1751689252 | Pass | Pass | 0.1214235950 | 0.3277043935 | Pass | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2602299208 | 0.4209914714 | Pass | Pass | 0.1402009021 | 0.3686685863 | Pass | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1256803016 | 0.1765094103 | Pass | Pass | 0.1165067445 | 0.3138936289 | Pass | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1198255967 | 0.1761605436 | Pass | Pass | 14.4502509860 | 64.4323556204 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1143849620 | 0.1300799291 | Pass | Pass | 6.8858997023 | 43.9599156836 | Pass | Pass |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1954624846 | 0.1762337674 | Pass | Pass | 0.2306456451 | 0.4177452508 | Pass | Pass |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1100697521 | 0.1331491083 | Pass | Pass | 0.4944125399 | 3.1393113221 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 2.2261563352E-002 | 3.1503738693E-002 | Pass | Pass | 0.6563445044 | 2.4579442188 | Pass | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 2.7840331855E-002 | 3.6947323649E-002 | Pass | Pass | 0.2131685781 | 0.6547909699 | Pass | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 9.2065853736E-002 | 7.4100654021E-002 | Pass | Pass | 0.2336049781 | 0.4131398714 | Pass | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 4.8674554605E-006 | 6.3221251937E-006 | Pass | Pass | 6.6488289991E-003 | 8.8539315995E-003 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 4.7069251792E-006 | 6.6821637719E-006 | Pass | Pass | 0.1848087554 | 0.5870691614 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 3.8656973797E-002 | 2.8985729543E-002 | Pass | Pass | 0.1216677570 | 0.5875247203 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 8.0348893147E-006 | 2.3315974540E-005 | Pass | Pass | 6.2255994780E-005 | 1.0808903765E-004 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:19
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 8875.81 | 143.83 | 0.00 | 17270.05 | 24212.77 | 50502.46 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:19
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | -7.90 | 0.00 | -7.90 | Wetbulb [C] | 3.20 | 0.00 |
ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 35.10 | 13.50 | 15.70 | Wetbulb [C] | 4.40 | 220.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 9.00 | 6 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 5.00 | 4 | |||
Nov | 9.00 | 7 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:19
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.399 | 0.419 | 118.87 | 118.87 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.399 | 0.419 | 139.09 | 139.09 | 180.00 | 90.00 | S |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.399 | 0.419 | 139.09 | 139.09 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.115 | 1.339 | 200.61 | 105.88 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.115 | 1.339 | 133.74 | 71.89 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.115 | 1.339 | 200.61 | 105.88 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.115 | 1.339 | 133.74 | 71.89 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.060 | 1.260 | 2006.06 | 1136.85 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 1.060 | 1.260 | 1337.37 | 757.90 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.060 | 1.260 | 2006.06 | 1136.85 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 1.060 | 1.260 | 1337.37 | 757.90 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.351 | 1.694 | 200.61 | 113.68 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.351 | 1.694 | 133.74 | 75.79 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.351 | 1.694 | 200.61 | 113.68 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.351 | 1.694 | 133.74 | 75.79 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.115 | 1.339 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.115 | 1.339 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.115 | 1.339 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.115 | 1.339 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.060 | 1.260 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 1.060 | 1.260 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.060 | 1.260 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 1.060 | 1.260 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.351 | 1.694 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.351 | 1.694 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.351 | 1.694 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.351 | 1.694 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.182 | 0.186 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.399 | 0.419 | 39.22 | 39.22 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.399 | 0.419 | 39.22 | 39.22 | 180.00 | 90.00 | S |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.399 | 0.419 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 270.00 | 90.00 | W |
BASEMENT_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 2779.43 | 2779.43 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 2076.77 | 2076.77 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 419.30 | 419.30 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 2076.82 | 2076.82 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 0.00 | 180.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.35 | 250.35 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 225.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 135.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.41 | 313.41 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
INT-PER3S-NE-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
INT-PER3S-NE | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.42 | 313.42 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
GROUNDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
iz-DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 0.00 | 180.00 | |
MIDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 35631.06 | 35631.06 | 180.00 | 0.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_BOT_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_BOT_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_MID_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
DATACENTER_MID_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
DATACENTER_MID_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 362.03 | 362.03 | 0.00 | 180.00 | |
DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 180.00 | 0.00 | |
DATACENTER_TOP_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_TOP_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_TOP_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 783.68 | 783.68 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 419.35 | 419.35 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 135.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.08 | 63.08 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 180.00 | 0.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 7126.21 | 0.00 | 90.00 | N | ||
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 50646.53 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.26 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.50 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.35 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.48 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.3822_SHGC_NORTH_0.36 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.171 | 0.361 | 0.361 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.3822_SHGC_NORTH_0.36 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.171 | 0.361 | 0.361 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.3822_SHGC_NORTH_0.36 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.171 | 0.361 | 0.361 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.3822_SHGC_NORTH_0.36 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.171 | 0.361 | 0.361 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.3822_SHGC_NORTH_0.36 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.171 | 0.361 | 0.361 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.3822_SHGC_EAST_0.36 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.171 | 0.361 | 0.361 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.3822_SHGC_EAST_0.36 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.171 | 0.361 | 0.361 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.3822_SHGC_EAST_0.36 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.171 | 0.361 | 0.361 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.3822_SHGC_SOUTH_0.36 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.171 | 0.361 | 0.361 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.3822_SHGC_SOUTH_0.36 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.171 | 0.361 | 0.361 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.3822_SHGC_SOUTH_0.36 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.171 | 0.361 | 0.361 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.3822_SHGC_SOUTH_0.36 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.171 | 0.361 | 0.361 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.3822_SHGC_SOUTH_0.36 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.171 | 0.361 | 0.361 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.3822_SHGC_WEST_0.36 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.171 | 0.361 | 0.361 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.3822_SHGC_WEST_0.36 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.171 | 0.361 | 0.361 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.3822_SHGC_WEST_0.36 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.171 | 0.361 | 0.361 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.3822_SHGC_NORTH_0.36 | 86.92 | 0.00 | 0.00 | 86.92 | 869.21 | 2.171 | 0.361 | 0.361 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.3822_SHGC_EAST_0.36 | 57.95 | 0.00 | 0.00 | 57.95 | 579.48 | 2.171 | 0.361 | 0.361 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.3822_SHGC_SOUTH_0.36 | 86.92 | 0.00 | 0.00 | 86.92 | 869.21 | 2.171 | 0.361 | 0.361 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.3822_SHGC_WEST_0.36 | 57.95 | 0.00 | 0.00 | 57.95 | 579.48 | 2.171 | 0.361 | 0.361 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.3822_SHGC_NORTH_0.36 | 86.92 | 0.00 | 0.00 | 86.92 | 86.92 | 2.171 | 0.361 | 0.361 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.3822_SHGC_EAST_0.36 | 57.95 | 0.00 | 0.00 | 57.95 | 57.95 | 2.171 | 0.361 | 0.361 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.3822_SHGC_SOUTH_0.36 | 86.92 | 0.00 | 0.00 | 86.92 | 86.92 | 2.171 | 0.361 | 0.361 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.3822_SHGC_WEST_0.36 | 57.95 | 0.00 | 0.00 | 57.95 | 57.95 | 2.171 | 0.361 | 0.361 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 3476.85 | 2.171 | 0.361 | 0.361 | |||||||||||||||||
North Total or Average | 1043.06 | 2.171 | 0.361 | 0.361 | |||||||||||||||||
Non-North Total or Average | 2433.80 | 2.171 | 0.361 | 0.361 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:19
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:19
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 7.6202 | 2779.43 | 21179.74 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 44.71 | 0.0000 | Y | 177.74 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 7.6202 | 2496.12 | 19020.89 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 44.71 | 0.0000 | Y | 159.62 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 7.6202 | 24961.20 | 190208.95 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 44.71 | 0.0000 | Y | 1596.24 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 7.6202 | 2496.12 | 19020.89 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 44.71 | 0.0000 | Y | 159.62 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 7.6202 | 313.41 | 2388.26 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 30.71 | 0.0000 | Y | 13.77 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 7.6202 | 201.98 | 1539.09 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 30.67 | 0.0000 | Y | 8.86 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 7.6202 | 313.42 | 2388.32 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 30.48 | 0.0000 | Y | 13.66 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 7.6202 | 201.98 | 1539.09 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 30.53 | 0.0000 | Y | 8.82 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 7.6202 | 3134.13 | 23882.63 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 30.73 | 0.0000 | Y | 137.78 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 7.6202 | 2019.75 | 15390.88 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 30.68 | 0.0000 | Y | 88.64 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 7.6202 | 3134.20 | 23883.15 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 30.49 | 0.0000 | Y | 136.69 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 7.6202 | 2019.75 | 15390.88 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 30.53 | 0.0000 | Y | 88.22 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 7.6202 | 313.41 | 2388.26 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 30.73 | 0.0000 | Y | 13.78 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 7.6202 | 201.98 | 1539.09 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 30.68 | 0.0000 | Y | 8.86 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 7.6202 | 313.42 | 2388.32 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 30.49 | 0.0000 | Y | 13.67 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 7.6202 | 201.98 | 1539.09 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 30.53 | 0.0000 | Y | 8.82 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GENERAL | 7.6202 | 783.68 | 5971.78 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 44.71 | 0.0000 | Y | 50.12 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | DATACENTER_BOT_ZN_6 | GENERAL | 12.5114 | 36.20 | 452.95 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 4.64 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | DATACENTER_MID_ZN_6 | GENERAL | 12.5114 | 362.03 | 4529.48 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 46.40 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | DATACENTER_TOP_ZN_6 | GENERAL | 12.5114 | 36.20 | 452.95 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 4.64 |
Interior Lighting Total | 7.6661 | 46320.38 | 355094.67 | 856.03 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2388.32 | 921.17 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 2388.32 | 0.00 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1539.09 | 593.63 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1539.09 | 0.00 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2388.26 | 921.15 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 2388.26 | 0.00 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1539.09 | 593.63 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1539.09 | 0.00 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2388.32 | 921.17 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 2388.32 | 0.00 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1539.09 | 593.63 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1539.09 | 0.00 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2388.26 | 921.15 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 2388.26 | 0.00 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1539.09 | 593.63 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1539.09 | 0.00 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2388.32 | 921.17 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 2388.32 | 0.00 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1539.09 | 593.63 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1539.09 | 0.00 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2388.26 | 921.15 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 2388.26 | 0.00 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1539.09 | 593.63 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1539.09 | 0.00 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 9973.05 | AstronomicalClock | - | 41.81 | 41.81 | 78.28 | |
EXTERIOR_LIGHTS_B | 27638.03 | AstronomicalClock | - | 83.71 | 71.14 | 369.07 | |
Exterior Lighting Total | 37611.08 | 447.35 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:19
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 2146030.57 | |||||
HEATSYS1 BOILER | Boiler:HotWater | 2163571.87 | 0.81 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:ReformulatedEIR | 1099421.64 | 6.28 | 1052290.50 | 5.98 | 6.84 | 23.33 |
COOLSYS1 CHILLER2 | Chiller:Electric:ReformulatedEIR | 1099421.64 | 6.28 | 1052290.50 | 5.98 | 6.84 | 23.33 |
CENTRAL TOWER | FluidCooler:TwoSpeed | 582060.00 | |||||
CENTRAL BOILER | Boiler:HotWater | 586379.63 | 0.80 | ||||
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 1306047.12 | |||||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 1306047.12 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | 179053.87 | 239894.09 | 152164.94 | 87729.16 | 0.63 | - | 24516.32 | 248.66 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | 1692065.48 | 2244186.17 | 1419184.21 | 825001.96 | 0.63 | - | 228688.00 | 2319.48 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | 181618.43 | 244744.70 | 155517.77 | 89226.93 | 0.64 | - | 25054.68 | 254.12 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | 98239.40 | 132559.15 | 85359.71 | 47199.43 | 0.64 | - | 13074.81 | 132.61 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 475527.81 | 252201.15 | 223326.66 | 0.53 | 0.00 | |||
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 10356.64 | 5543.42 | 4813.22 | 0.54 | 0.00 | |||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 98913.37 | 52928.84 | 45984.53 | 0.54 | 0.00 | |||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 10106.03 | 5408.44 | 4697.59 | 0.54 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 16610.99 | 15753.04 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 415981.64 | 394248.70 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 82180.72 | 77903.99 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 10686.45 | 10129.90 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 7567.42 | 7173.16 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 12859.68 | 12189.55 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 6415.63 | 6080.89 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 204364.43 | 193695.53 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 135620.65 | 128539.93 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 202605.99 | 192029.14 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 128157.40 | 121467.26 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 26802.04 | 25401.92 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 17685.41 | 16761.48 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 26581.38 | 25192.81 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 17105.40 | 16211.82 | - |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | 53316.13 | 41063.42 | - |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | 487107.32 | 376248.26 | - |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | 45106.13 | 35914.78 | - |
CAV_BAS HEATING COIL | Coil:Heating:Water | 266817.07 | 210327.33 | - |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 475527.81 | 0.00 | |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 10356.64 | 0.00 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 98913.37 | 0.00 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 10106.03 | 0.00 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | 16131.55 | 1.00 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | 745.21 | 1.00 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | 7452.11 | 1.00 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | 745.21 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 11.12 | 23897.57 | 2149.46 | 1.00 | 1.12 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 103.19 | 221801.41 | 2149.46 | 1.00 | 1.08 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 11.40 | 24493.37 | 2149.46 | 1.00 | 1.12 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 |
CAV_BAS FAN | Fan:ConstantVolume | 0.60 | 1018.41 | 6.47 | 10963.13 | 1695.65 | 1.00 | 1.15 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 0.62 | 1018.41 | 25.97 | 42828.27 | 1649.25 | 1.00 | 1.14 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 |
AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.58 | 650.35 | 1120.11 | 1.00 | 1.54 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 5.54 | 6208.08 | 1120.11 | 1.00 | 1.15 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.57 | 634.43 | 1120.11 | 1.00 | 1.55 | General | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 133527.72 | 0.091508 | 18856.31 | 206062.94 | 0.90 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.018928 | 5700.24 | 301156.09 | 0.90 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 92445.74 | 0.091508 | 13054.86 | 142664.32 | 0.90 | General |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.014569 | 3715.86 | 255050.01 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 3168.45 | 0.000440 | 5.96 | 13540.37 | 0.30 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 180718.98 | 0.108813 | 32771.99 | 301178.23 | 0.90 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.50 | 0.08 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:19
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 73618.22 | 73618.22 | 26.49 | 6.465 | 6.465 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00747 | 25.11 | 0.00568 | 1.200 | 0.00 |
CORE_BOTTOM | 77690.56 | 77690.56 | 31.12 | 6.822 | 6.822 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00740 | 25.11 | 0.00568 | 1.078 | 0.00 |
CORE_MID | 729106.46 | 729106.46 | 292.10 | 64.012 | 64.012 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00743 | 25.11 | 0.00568 | 10.778 | 0.00 |
CORE_TOP | 72139.70 | 72139.70 | 28.90 | 6.390 | 6.390 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 24.00 | 0.00742 | 35.10 | 0.00570 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 12985.00 | 12985.00 | 41.43 | 1.150 | 1.150 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 24.00 | 0.00726 | 35.10 | 0.00570 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 14632.24 | 14632.24 | 72.45 | 1.296 | 1.296 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 24.00 | 24.00 | 0.00715 | 27.68 | 0.00569 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 15737.78 | 15737.78 | 50.21 | 1.394 | 1.394 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 24.00 | 24.00 | 0.00722 | 34.65 | 0.00570 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 18706.82 | 18706.82 | 92.62 | 1.657 | 1.657 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 24.00 | 24.00 | 0.00712 | 33.39 | 0.00570 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 122329.07 | 122329.07 | 390.31 | 10.835 | 10.835 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 24.00 | 0.00723 | 35.10 | 0.00570 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 153462.59 | 153462.59 | 759.81 | 13.593 | 13.593 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 24.00 | 24.00 | 0.00712 | 28.44 | 0.00569 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 150680.90 | 150680.90 | 480.76 | 13.347 | 13.347 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 24.00 | 24.00 | 0.00719 | 34.76 | 0.00570 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 165592.08 | 165592.08 | 819.86 | 14.667 | 14.667 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 24.00 | 24.00 | 0.00711 | 33.21 | 0.00570 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 14184.37 | 14184.37 | 45.26 | 1.256 | 1.256 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 24.00 | 0.00718 | 35.10 | 0.00570 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 15600.54 | 15600.54 | 77.24 | 1.382 | 1.382 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 24.00 | 24.00 | 0.00711 | 29.21 | 0.00569 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 16868.22 | 16868.22 | 53.82 | 1.494 | 1.494 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 24.00 | 24.00 | 0.00716 | 34.99 | 0.00570 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 17887.44 | 17887.44 | 88.56 | 1.584 | 1.584 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 24.00 | 24.00 | 0.00709 | 33.21 | 0.00570 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 8310.45 | 8310.45 | 229.55 | 0.581 | 0.581 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 27.00 | 27.00 | 0.00709 | 30.51 | 0.00569 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 79328.69 | 79328.69 | 2191.23 | 5.542 | 5.542 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 27.00 | 27.00 | 0.00709 | 30.17 | 0.00569 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 8106.99 | 8106.99 | 223.93 | 0.566 | 0.566 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 27.00 | 27.00 | 0.00709 | 30.51 | 0.00569 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 371690.89 | 371690.89 | 474.29 | 25.968 | 25.968 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 27.00 | 27.00 | 0.00704 | 22.82 | 0.00568 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:10:00 | 21.00 | 24.28 | 0.00234 | -7.90 | 0.00234 | 1.200 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.000 | 1.078 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:20:00 | 19.60 | 21.69 | 0.00234 | -7.90 | 0.00234 | 1.078 | 0.00 |
CORE_MID | 253236.48 | 253236.48 | 101.45 | 12.998 | 12.998 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -7.90 | 0.00234 | 10.778 | 0.00 |
CORE_TOP | 57544.03 | 57544.03 | 23.05 | 2.975 | 2.975 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -7.90 | 0.00234 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 7484.89 | 7484.89 | 23.88 | 0.387 | 0.387 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00748 | -7.90 | 0.00234 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 5299.37 | 5299.37 | 26.24 | 0.274 | 0.274 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00756 | -7.90 | 0.00234 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 9004.21 | 9004.21 | 28.73 | 0.466 | 0.466 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00765 | -7.90 | 0.00234 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 3676.39 | 3676.39 | 18.20 | 0.190 | 0.190 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00709 | -7.90 | 0.00234 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 143027.25 | 143027.25 | 456.35 | 7.413 | 7.413 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00764 | -7.90 | 0.00234 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 94913.90 | 94913.90 | 469.93 | 4.920 | 4.920 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00764 | -7.90 | 0.00234 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 141797.90 | 141797.90 | 452.42 | 7.349 | 7.349 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00763 | -7.90 | 0.00234 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 89695.96 | 89695.96 | 444.09 | 4.648 | 4.648 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00761 | -7.90 | 0.00234 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 18754.26 | 18754.26 | 59.84 | 0.973 | 0.973 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00766 | -7.90 | 0.00234 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 12374.93 | 12374.93 | 61.27 | 0.642 | 0.642 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00766 | -7.90 | 0.00234 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 18599.98 | 18599.98 | 59.35 | 0.965 | 0.965 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00766 | -7.90 | 0.00234 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 11969.37 | 11969.37 | 59.26 | 0.621 | 0.621 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00765 | -7.90 | 0.00234 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:30:00 | 18.00 | 26.10 | 0.00700 | -7.90 | 0.00234 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | 18.00 | 23.08 | 0.00393 | -7.90 | 0.00234 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | 18.00 | 21.23 | 0.00284 | -7.90 | 0.00234 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:40:00 | 18.00 | 27.00 | 0.00700 | -7.90 | 0.00234 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV_BOT WITH REHEAT | 11.12 | 11.12 | 2.39 | 2.39 | 11.1179 | 3.1271 | 11.1179 | 0.2813 | 0.3000 |
VAV_MID WITH REHEAT | 103.19 | 103.19 | 37.33 | 37.33 | 103.1891 | 37.3281 | 103.1891 | 0.3617 | 0.3000 |
VAV_TOP WITH REHEAT | 11.40 | 11.40 | 6.17 | 6.17 | 11.3951 | 6.1746 | 11.3951 | 0.5419 | 0.3000 |
CAV_BAS | 6.47 | 6.47 | 1.20 | 1.20 | 6.4654 | 6.4654 | 6.4654 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 25.97 | 25.97 | 0.34 | 0.34 | 25.9684 | 25.9680 | 25.9684 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.58 | 0.58 | 0.02 | 0.02 | 0.5806 | 0.5806 | 0.5806 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 5.54 | 5.54 | 0.16 | 0.16 | 5.5424 | 5.5424 | 5.5424 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.57 | 0.57 | 0.02 | 0.02 | 0.5664 | 0.5664 | 0.5664 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 16610.986 | 16610.986 | 2.005809 | 0.00014532 | 334.864 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:20:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:20:00 | 16610.99 | 16610.99 | 2.005809 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00800000 | 42.5367 | 0.00 | 0.00 | 16672.23 | 16672.23 |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 415981.636 | 415981.636 | 19.651799 | 0.00363919 | 9930.936 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 415981.64 | 415981.64 | 19.651799 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00800000 | 42.5367 | 253236.48 | 0.00 | 417334.13 | 417334.13 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 82180.719 | 82180.719 | 2.974929 | 0.00071895 | 2169.112 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 82180.72 | 82180.72 | 2.974929 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00800000 | 42.5367 | 57544.03 | 0.00 | 82463.22 | 82463.22 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 10686.450 | 10686.450 | 0.387034 | 0.00009349 | 282.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 10686.45 | 10686.45 | 0.387034 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00747723 | 39.7938 | 7484.89 | 0.00 | 10722.74 | 10722.74 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 7567.424 | 7567.424 | 0.274138 | 0.00006620 | 199.671 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 7567.42 | 7567.42 | 0.274138 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00755928 | 40.2249 | 5299.37 | 0.00 | 7592.96 | 7592.96 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 12859.684 | 12859.684 | 0.465923 | 0.00011250 | 339.289 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 12859.68 | 12859.68 | 0.465923 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00764653 | 40.6830 | 9004.21 | 0.00 | 12902.92 | 12902.92 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 6415.626 | 6415.626 | 0.331398 | 0.00005613 | 149.228 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 6415.63 | 6415.63 | 0.331398 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00708987 | 37.7567 | 3676.39 | 0.00 | 6436.77 | 6436.77 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 204364.433 | 204364.433 | 7.412901 | 0.00178787 | 5389.100 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 204364.43 | 204364.43 | 7.412901 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00763715 | 40.6347 | 143027.25 | 0.00 | 205031.11 | 205031.11 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 135620.649 | 135620.649 | 4.919630 | 0.00118647 | 3576.234 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 135620.65 | 135620.65 | 4.919630 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00763697 | 40.6339 | 94913.90 | 0.00 | 136062.43 | 136062.43 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 202605.990 | 202605.990 | 7.349007 | 0.00177249 | 5342.767 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 202605.99 | 202605.99 | 7.349007 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00763375 | 40.6169 | 141797.90 | 0.00 | 203267.20 | 203267.20 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 128157.397 | 128157.397 | 4.648489 | 0.00112118 | 3379.569 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 128157.40 | 128157.40 | 4.648489 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00761398 | 40.5131 | 89695.96 | 0.00 | 128575.85 | 128575.85 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 26802.043 | 26802.043 | 0.972598 | 0.00023448 | 706.636 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 26802.04 | 26802.04 | 0.972598 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00766122 | 40.7618 | 18754.26 | 0.00 | 26888.50 | 26888.50 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 17685.407 | 17685.407 | 0.641794 | 0.00015472 | 466.268 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 17685.41 | 17685.41 | 0.641794 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00765799 | 40.7450 | 12374.93 | 0.00 | 17742.40 | 17742.40 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 26581.382 | 26581.382 | 0.964580 | 0.00023255 | 700.821 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 26581.38 | 26581.38 | 0.964580 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00765855 | 40.7478 | 18599.98 | 0.00 | 26667.15 | 26667.15 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 17105.396 | 17105.396 | 0.620724 | 0.00014965 | 450.983 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 17105.40 | 17105.40 | 0.620724 | 12.80 | 9.86 | 0.00800000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 0.0000 | 21.00 | 0.00764708 | 40.6876 | 11969.37 | 0.00 | 17160.57 | 17160.57 |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 179053.871 | -999.000 | 11.117917 | 0.00761737 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 179053.87 | 179053.87 | 11.117917 | 26.64 | 14.00 | 0.00695250 | 10.67 | 7.93 | 0.00695250 | 35.10 | 0.00569938 | 15.77 | 22.8297 | 24.00 | 0.00734464 | 32.5806 | 120220.29 | 0.00 | 160830.34 | 160830.34 |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 53316.128 | 53316.128 | 3.335375 | 0.00046643 | 877.632 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 53316.13 | 53316.13 | 3.335375 | -3.26 | -4.00 | 0.00302074 | 12.80 | 9.86 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 76.0991 | 21.24 | 0.00583839 | 30.7000 | 25464.86 | 0.00 | 49668.81 | 49668.81 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 1692065.480 | -999.000 | 103.189145 | 0.07198438 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 1692065.48 | 1692065.48 | 103.189145 | 26.94 | 14.08 | 0.00692461 | 10.67 | 7.90 | 0.00692461 | 35.10 | 0.00569938 | 15.77 | 24.5975 | 24.00 | 0.00736538 | 32.6714 | 1083068.18 | 0.00 | 1518102.18 | 1518102.18 |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 487107.318 | 487107.318 | 30.956743 | 0.00426143 | 8029.197 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:30:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 487107.32 | 487107.32 | 30.956743 | -3.01 | -3.45 | 0.00328587 | 12.80 | 9.86 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 81.9917 | 19.63 | 0.00734639 | 42.5655 | 349375.77 | 0.00 | 455128.88 | 455128.88 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 181618.429 | -999.000 | 11.395102 | 0.00772647 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 181618.43 | 181618.43 | 11.395102 | 26.48 | 13.94 | 0.00694504 | 10.67 | 7.93 | 0.00694504 | 35.10 | 0.00569938 | 15.77 | 22.2744 | 24.00 | 0.00730350 | 32.4000 | 128230.86 | 0.00 | 162867.45 | 162867.45 |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 45106.129 | 45106.129 | 3.418531 | 0.00039461 | 754.781 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 22:20:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 45106.13 | 45106.13 | 3.418531 | -0.46 | -1.47 | 0.00370126 | 12.80 | 9.86 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 74.2480 | 18.55 | 0.00760000 | 47.0620 | 46505.13 | 0.00 | 43453.26 | 43453.26 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 98239.400 | -999.000 | 6.465428 | 0.00417933 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 98239.40 | 98239.40 | 6.465428 | 26.19 | 14.01 | 0.00713998 | 11.12 | 8.32 | 0.00713998 | 34.43 | 0.00569833 | 15.56 | 18.5627 | 24.00 | 0.00752300 | 33.3628 | 65830.74 | 0.00 | 88960.26 | 88960.26 |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | CAV_BAS | 266817.068 | 266817.068 | 6.465428 | 0.00233423 | 5910.306 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 266817.07 | 266817.07 | 6.465428 | -1.47 | -4.06 | 0.00234317 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 18.5627 | 24.35 | 0.00234317 | 10.2573 | 0.00 | 0.00 | 222068.80 | 222068.80 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 475527.808 | 252201.147 | 25.968380 | 0.01164565 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 | 405880.75 | 404788.42 | -999.0 | 28.80 | 14.79 | 0.00702464 | 12.80 | 8.87 | 0.00700000 | 35.10 | 0.00569938 | 15.77 | -999.0000 | 27.00 | 0.00704216 | 26.1557 | 371221.42 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 10356.637 | 5543.420 | 0.580616 | 0.00025363 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 8796.81 | 8748.52 | -999.0 | 28.24 | 14.62 | 0.00704921 | 12.80 | 8.87 | 0.00700000 | 30.51 | 0.00569229 | 14.27 | -999.0000 | 27.00 | 0.00708676 | 26.3176 | 8310.45 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 98913.372 | 52928.838 | 5.542398 | 0.00242238 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 84024.11 | 83542.33 | -999.0 | 28.25 | 14.63 | 0.00705142 | 12.80 | 8.87 | 0.00700000 | 30.51 | 0.00569229 | 14.27 | -999.0000 | 27.00 | 0.00709087 | 26.3328 | 79326.03 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 10106.033 | 5408.445 | 0.566403 | 0.00024750 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 8584.41 | 8536.10 | -999.0 | 28.25 | 14.62 | 0.00705047 | 12.80 | 8.87 | 0.00700000 | 30.51 | 0.00569229 | 14.27 | -999.0000 | 27.00 | 0.00708901 | 26.3259 | 8106.99 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 475527.808 | 475527.808 | 25.968380 | 0.01164565 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 475527.81 | 475527.81 | 25.968380 | -7.90 | -7.90 | 0.00234317 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 1.3031 | 27.00 | 0.00700000 | 25.9964 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 10356.637 | 10356.637 | 0.580616 | 0.00025363 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 10356.64 | 10356.64 | 0.580616 | -7.90 | -7.90 | 0.00234317 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 2.6924 | 26.52 | 0.00699525 | 26.7217 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 98913.372 | 98913.372 | 5.542398 | 0.00242238 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 98913.37 | 98913.37 | 5.542398 | -7.90 | -7.90 | 0.00234317 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 2.8205 | 24.27 | 0.00392913 | 17.2447 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 10106.033 | 10106.033 | 0.566403 | 0.00024750 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 10106.03 | 10106.03 | 0.566403 | -7.90 | -7.90 | 0.00234317 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 2.7599 | 23.09 | 0.00283710 | 13.3873 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 16131.549 | 16131.549 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 16131.55 | 16131.55 | 25.968380 | -0.10 | -0.10 | 0.00693932 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 1.3031 | 27.00 | 0.00700000 | 25.9964 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BOT | 745.211 | 745.211 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 745.21 | 745.21 | 0.580616 | -0.21 | -0.21 | 0.00687000 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 2.6924 | 26.52 | 0.00699525 | 26.7217 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER MID | 7452.107 | 7452.107 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 7452.11 | 7452.11 | 5.542398 | -0.22 | -1.09 | 0.00388440 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 2.8205 | 24.27 | 0.00392913 | 17.2447 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER TOP | 745.211 | 745.211 | -999.0 | -999.0 | -999.000 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 745.21 | 745.21 | 0.566403 | -0.22 | -2.63 | 0.00282347 | 40.00 | 18.92 | 0.00800000 | -7.90 | 0.00234317 | -7.90 | 2.7599 | 23.09 | 0.00283710 | 13.3873 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 09:04:19
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 16610.986 | 16610.986 | 2.005809 | 0.00014532 | 334.864 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 18.92593968 | 54.44 | 82.22 | 27.78 | 2207114.61 | 0.7526 | 0.767758 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:20:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:20:00 | Sensible | 16610.99 | 16610.99 | 1.0000 | 1.98657149 | 2.005809 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.14530533 | 60.00 | 32.22 | 27.78 | 0.000 | 16610.99 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 42.5367 | 0.00 | 0.00 | 16672.23 | 16672.23 | 1.98657149 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 21.03 | 14.86 | 0.00800000 | 41452.3 | |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 415981.636 | 415981.636 | 19.651799 | 0.00363919 | 9930.936 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 18.92593968 | 54.44 | 82.22 | 27.78 | 2207114.61 | 18.8473 | 19.226615 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 415981.64 | 415981.64 | 1.0000 | 19.46331670 | 19.651799 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 3.63881759 | 60.00 | 32.22 | 27.78 | 0.000 | 415981.64 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.87 | 0.00800000 | 21.00 | 0.00800000 | 42.5367 | 253236.48 | 0.00 | 417334.13 | 417334.13 | 19.46331670 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 33.83 | 19.29 | 0.00800000 | 54501.9 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 82180.719 | 82180.719 | 2.974929 | 0.00071895 | 2169.112 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 18.92593968 | 54.44 | 82.22 | 27.78 | 2207114.61 | 3.7234 | 3.798382 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 82180.72 | 82180.72 | 1.0000 | 2.94639648 | 2.974929 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.71887944 | 60.00 | 32.22 | 27.78 | 0.000 | 82180.72 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.91 | 0.00800000 | 21.00 | 0.00800000 | 42.5367 | 57544.03 | 0.00 | 82463.22 | 82463.22 | 2.94639648 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.25 | 21.26 | 0.00800000 | 61047.6 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10686.450 | 10686.450 | 0.387034 | 0.00009349 | 282.000 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 18.92593968 | 54.44 | 82.22 | 27.78 | 2207114.61 | 0.4842 | 0.493926 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 10686.45 | 10686.45 | 1.0000 | 0.38332240 | 0.387034 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.09348019 | 60.00 | 32.22 | 27.78 | 0.000 | 10686.45 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.91 | 0.00747723 | 21.00 | 0.00747723 | 39.7938 | 7484.89 | 0.00 | 10722.74 | 10722.74 | 0.38332240 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.23 | 21.25 | 0.00800000 | 61033.0 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7567.424 | 7567.424 | 0.274138 | 0.00006620 | 199.671 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 18.92593968 | 54.44 | 82.22 | 27.78 | 2207114.61 | 0.3429 | 0.349765 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 7567.42 | 7567.42 | 1.0000 | 0.27150889 | 0.274138 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.06619638 | 60.00 | 32.22 | 27.78 | 0.000 | 7567.42 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.91 | 0.00755928 | 21.00 | 0.00755928 | 40.2249 | 5299.37 | 0.00 | 7592.96 | 7592.96 | 0.27150889 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.23 | 21.25 | 0.00800000 | 61025.6 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12859.684 | 12859.684 | 0.465923 | 0.00011250 | 339.289 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 18.92593968 | 54.44 | 82.22 | 27.78 | 2207114.61 | 0.5826 | 0.594373 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 12859.68 | 12859.68 | 1.0000 | 0.46145386 | 0.465923 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.11249065 | 60.00 | 32.22 | 27.78 | 0.000 | 12859.68 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.95 | 0.00764653 | 21.00 | 0.00764653 | 40.6830 | 9004.21 | 0.00 | 12902.92 | 12902.92 | 0.46145386 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.22 | 21.25 | 0.00800000 | 61021.3 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6415.626 | 6415.626 | 0.331398 | 0.00005613 | 149.228 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 18.92593968 | 54.44 | 82.22 | 27.78 | 2207114.61 | 0.2907 | 0.296529 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 6415.63 | 6415.63 | 1.0000 | 0.32821973 | 0.331398 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.05612097 | 60.00 | 32.22 | 27.78 | 0.000 | 6415.63 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.91 | 0.00708987 | 21.00 | 0.00708987 | 37.7567 | 3676.39 | 0.00 | 6436.77 | 6436.77 | 0.32821973 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.03 | 18.71 | 0.00800000 | 52671.0 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 204364.433 | 204364.433 | 7.412901 | 0.00178787 | 5389.100 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 18.92593968 | 54.44 | 82.22 | 27.78 | 2207114.61 | 9.2593 | 9.445697 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 204364.43 | 204364.43 | 1.0000 | 7.34180351 | 7.412901 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 1.78768683 | 60.00 | 32.22 | 27.78 | 0.000 | 204364.43 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.95 | 0.00763715 | 21.00 | 0.00763715 | 40.6347 | 143027.25 | 0.00 | 205031.11 | 205031.11 | 7.34180351 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60986.4 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 135620.649 | 135620.649 | 4.919630 | 0.00118647 | 3576.234 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 18.92593968 | 54.44 | 82.22 | 27.78 | 2207114.61 | 6.1447 | 6.268368 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 135620.65 | 135620.65 | 1.0000 | 4.87244499 | 4.919630 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 1.18634757 | 60.00 | 32.22 | 27.78 | 0.000 | 135620.65 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.95 | 0.00763697 | 21.00 | 0.00763697 | 40.6339 | 94913.90 | 0.00 | 136062.43 | 136062.43 | 4.87244499 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60984.7 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 202605.990 | 202605.990 | 7.349007 | 0.00177249 | 5342.767 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 18.92593968 | 54.44 | 82.22 | 27.78 | 2207114.61 | 9.1797 | 9.364422 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 202605.99 | 202605.99 | 1.0000 | 7.27852141 | 7.349007 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 1.77230477 | 60.00 | 32.22 | 27.78 | 0.000 | 202605.99 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.95 | 0.00763375 | 21.00 | 0.00763375 | 40.6169 | 141797.90 | 0.00 | 203267.20 | 203267.20 | 7.27852141 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60986.8 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 128157.397 | 128157.397 | 4.648489 | 0.00112118 | 3379.569 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 18.92593968 | 54.44 | 82.22 | 27.78 | 2207114.61 | 5.8066 | 5.923418 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 128157.40 | 128157.40 | 1.0000 | 4.60390514 | 4.648489 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 1.12106245 | 60.00 | 32.22 | 27.78 | 0.000 | 128157.40 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.95 | 0.00761398 | 21.00 | 0.00761398 | 40.5131 | 89695.96 | 0.00 | 128575.85 | 128575.85 | 4.60390514 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60987.4 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 26802.043 | 26802.043 | 0.972598 | 0.00023448 | 706.636 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 18.92593968 | 54.44 | 82.22 | 27.78 | 2207114.61 | 1.2143 | 1.238787 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 26802.04 | 26802.04 | 1.0000 | 0.96326945 | 0.972598 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.23445205 | 60.00 | 32.22 | 27.78 | 0.000 | 26802.04 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.95 | 0.00766122 | 21.00 | 0.00766122 | 40.7618 | 18754.26 | 0.00 | 26888.50 | 26888.50 | 0.96326945 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60973.6 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 17685.407 | 17685.407 | 0.641794 | 0.00015472 | 466.268 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 18.92593968 | 54.44 | 82.22 | 27.78 | 2207114.61 | 0.8013 | 0.817417 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 17685.41 | 17685.41 | 1.0000 | 0.63563850 | 0.641794 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.15470387 | 60.00 | 32.22 | 27.78 | 0.000 | 17685.41 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.95 | 0.00765799 | 21.00 | 0.00765799 | 40.7450 | 12374.93 | 0.00 | 17742.40 | 17742.40 | 0.63563850 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60972.6 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 26581.382 | 26581.382 | 0.964580 | 0.00023255 | 700.821 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 18.92593968 | 54.44 | 82.22 | 27.78 | 2207114.61 | 1.2043 | 1.228588 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 26581.38 | 26581.38 | 1.0000 | 0.95532866 | 0.964580 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.23252181 | 60.00 | 32.22 | 27.78 | 0.000 | 26581.38 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.95 | 0.00765855 | 21.00 | 0.00765855 | 40.7478 | 18599.98 | 0.00 | 26667.15 | 26667.15 | 0.95532866 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60973.9 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 17105.396 | 17105.396 | 0.620724 | 0.00014965 | 450.983 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 18.92593968 | 54.44 | 82.22 | 27.78 | 2207114.61 | 0.7750 | 0.790609 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 17105.40 | 17105.40 | 1.0000 | 0.61477101 | 0.620724 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 0.14963020 | 60.00 | 32.22 | 27.78 | 0.000 | 17105.40 | -7.90 | 0.00234317 | -7.90 | 0.00000000 | 0.0000 | 20.95 | 0.00764708 | 21.00 | 0.00764708 | 40.6876 | 11969.37 | 0.00 | 17160.57 | 17160.57 | 0.61477101 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60973.6 | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 179053.871 | -999.000 | 11.117917 | 0.00761737 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.7643 | 1004.8586 | 0.9904 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 11.117917 | 11.01128430 | 4197.9300 | 999.8980 | 91.49820695 | 12.27 | 6.67 | 5.60 | 2150977.18 | 8.3243 | 8.324304 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 179053.87 | 179053.87 | 1.0000 | 11.01128430 | 11.117917 | 26.64 | 14.00 | 0.00695250 | 44505.8 | 10.67 | 7.93 | 0.00695250 | 28244.9 | 7.61658853 | 6.67 | 12.27 | 5.60 | 23897.570 | 155156.30 | 35.10 | 0.00569938 | 15.77 | 2.53819000 | 22.8297 | 24.00 | 0.00734464 | 24.00 | 0.00734464 | 32.5806 | 120220.29 | 0.00 | 160830.34 | 160830.34 | 11.01128430 | 26.64 | 15.99 | 0.00695250 | 44505.8 | 12.29 | 10.28 | 0.00695250 | 29899.9 | |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 53316.128 | 53316.128 | 3.335375 | 0.00046643 | 877.632 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 11.117917 | 11.01128430 | 4197.9300 | 999.8980 | 18.92593968 | 54.44 | 82.22 | 27.78 | 2207114.61 | 2.4156 | 2.464264 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 53316.13 | 53316.13 | 1.0000 | 3.30338529 | 3.335375 | -3.26 | -4.00 | 0.00302074 | 4258.8 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 0.46638517 | 60.00 | 32.22 | 27.78 | 0.000 | 53316.13 | -7.90 | 0.00234317 | -7.90 | 2.53819000 | 76.0991 | 11.51 | 0.00517808 | 21.24 | 0.00583839 | 30.7000 | 25464.86 | 0.00 | 49668.81 | 49668.81 | 3.30338529 | 2.80 | 0.55 | 0.00302074 | 10384.0 | 17.68 | 8.36 | 0.00302074 | 25419.7 | |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 1692065.480 | -999.000 | 103.189145 | 0.07198438 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.7125 | 1004.8586 | 0.9904 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 103.189145 | 102.19944648 | 4197.9300 | 999.8980 | 91.49820695 | 12.27 | 6.67 | 5.60 | 2150977.18 | 78.6650 | 78.664967 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 1692065.48 | 1692065.48 | 1.0000 | 102.19944648 | 103.189145 | 26.94 | 14.08 | 0.00692461 | 44731.0 | 10.67 | 7.90 | 0.00692461 | 28174.5 | 71.97703392 | 6.67 | 12.27 | 5.60 | 221801.409 | 1470264.07 | 35.10 | 0.00569938 | 15.77 | 25.38195000 | 24.5975 | 24.00 | 0.00736538 | 24.00 | 0.00736538 | 32.6714 | 1083068.18 | 0.00 | 1518102.18 | 1518102.18 | 102.19944648 | 26.94 | 16.07 | 0.00692461 | 44731.0 | 12.34 | 10.28 | 0.00692461 | 29876.7 | |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 487107.318 | 487107.318 | 30.956743 | 0.00426143 | 8029.197 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 103.189145 | 102.19944648 | 4197.9300 | 999.8980 | 18.92593968 | 54.44 | 82.22 | 27.78 | 2207114.61 | 22.0699 | 22.514035 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:30:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 487107.32 | 487107.32 | 1.0000 | 30.65983394 | 30.956743 | -3.01 | -3.45 | 0.00328587 | 5174.1 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 4.26099260 | 60.00 | 32.22 | 27.78 | 0.000 | 487107.32 | -7.90 | 0.00234317 | -7.90 | 25.38195000 | 81.9917 | 19.25 | 0.00757796 | 19.63 | 0.00734639 | 42.5655 | 349375.77 | 0.00 | 455128.88 | 455128.88 | 30.65983394 | 2.80 | 0.94 | 0.00328587 | 11048.4 | 17.48 | 8.57 | 0.00328587 | 25892.9 | |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 181618.429 | -999.000 | 11.395102 | 0.00772647 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.7505 | 1004.8586 | 0.9904 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 11.395102 | 11.28581048 | 4197.9300 | 999.8980 | 91.49820695 | 12.27 | 6.67 | 5.60 | 2150977.18 | 8.4435 | 8.443531 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | Sensible | 181618.43 | 181618.43 | 1.0000 | 11.28581048 | 11.395102 | 26.48 | 13.94 | 0.00694504 | 44318.7 | 10.67 | 7.93 | 0.00694504 | 28226.1 | 7.72567964 | 6.67 | 12.27 | 5.60 | 24493.368 | 157125.06 | 35.10 | 0.00569938 | 15.77 | 2.53819000 | 22.2744 | 24.00 | 0.00730350 | 24.00 | 0.00730350 | 32.4000 | 128230.86 | 0.00 | 162867.45 | 162867.45 | 11.28581048 | 26.48 | 15.92 | 0.00694504 | 44318.7 | 12.30 | 10.28 | 0.00694504 | 29887.5 | |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 45106.129 | 45106.129 | 3.418531 | 0.00039461 | 754.781 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 11.395102 | 11.28581048 | 4197.9300 | 999.8980 | 18.92593968 | 54.44 | 82.22 | 27.78 | 2207114.61 | 2.0437 | 2.084799 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 22:20:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 45106.13 | 45106.13 | 1.0000 | 3.38574314 | 3.418531 | -0.46 | -1.47 | 0.00370126 | 8793.3 | 12.80 | 9.86 | 0.00800000 | 33059.8 | 0.39456784 | 60.00 | 32.22 | 27.78 | 0.000 | 45106.13 | -7.90 | 0.00234317 | -7.90 | 2.53819000 | 74.2480 | 21.00 | 0.00761691 | 18.55 | 0.00760000 | 47.0620 | 46505.13 | 0.00 | 43453.26 | 43453.26 | 3.38574314 | 2.80 | 1.53 | 0.00370126 | 12089.5 | 15.49 | 8.12 | 0.00370126 | 24923.6 | |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 98239.400 | -999.000 | 6.465428 | 0.00417933 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.1129 | 1004.8586 | 0.9904 | CAV_BAS FAN | Fan:ConstantVolume | 6.465428 | 6.40341703 | 4197.9300 | 999.8980 | 91.49820695 | 12.27 | 6.67 | 5.60 | 2150977.18 | 4.5672 | 4.567199 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 98239.40 | 98239.40 | 1.0000 | 6.40341703 | 6.465428 | 26.19 | 14.01 | 0.00713998 | 44518.2 | 11.12 | 8.32 | 0.00713998 | 29176.4 | 4.17890486 | 6.67 | 12.27 | 5.60 | 10963.130 | 87276.27 | 34.43 | 0.00569833 | 15.56 | 1.20015641 | 18.5627 | 24.00 | 0.00752300 | 24.00 | 0.00752300 | 33.3628 | 65830.74 | 0.00 | 88960.26 | 88960.26 | 6.40341703 | 26.19 | 15.99 | 0.00713998 | 44518.2 | 12.54 | 10.59 | 0.00713998 | 30625.5 | |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 266817.068 | 266817.068 | 6.465428 | 0.00233423 | 5910.306 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | CAV_BAS FAN | Fan:ConstantVolume | 6.465428 | 6.40341703 | 4197.9300 | 999.8980 | 18.92593968 | 54.44 | 82.22 | 27.78 | 2207114.61 | 12.0890 | 12.332249 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 266817.07 | 266817.07 | 1.0000 | 6.40341703 | 6.465428 | -1.47 | -4.06 | 0.00234317 | 4380.2 | 40.00 | 18.92 | 0.00800000 | 60796.0 | 2.33399399 | 60.00 | 32.22 | 27.78 | 0.000 | 266817.07 | -7.90 | 0.00234317 | -7.90 | 1.20015641 | 18.5627 | 0.00 | 0.00234317 | 24.35 | 0.00234317 | 10.2573 | 0.00 | 0.00 | 222068.80 | 222068.80 | 6.40341703 | 12.80 | 5.14 | 0.00234317 | 18777.8 | 47.16 | 19.11 | 0.00234317 | 53457.6 | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 475527.808 | 252201.147 | 25.968380 | 0.01164565 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1017.8985 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 | Sensible | 405880.75 | 404788.42 | 0.8535 | -999.0 | -999.0 | 28.80 | 14.79 | 0.00702464 | 46880.9 | 12.80 | 8.87 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 405880.75 | 35.10 | 0.00569938 | 15.77 | 0.33839277 | -999.0000 | 27.00 | 0.00704216 | 27.00 | 0.00704216 | 26.1557 | 371221.42 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 10356.637 | 5543.420 | 0.580616 | 0.00025363 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1017.9441 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | Sensible | 8796.81 | 8748.52 | 0.8494 | -999.0 | -999.0 | 28.24 | 14.62 | 0.00704921 | 46380.1 | 12.80 | 8.87 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8796.81 | 30.51 | 0.00569229 | 14.27 | 0.01563234 | -999.0000 | 27.00 | 0.00708676 | 27.00 | 0.00708676 | 26.3176 | 8310.45 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 98913.372 | 52928.838 | 5.542398 | 0.00242238 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1017.9482 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | Sensible | 84024.11 | 83542.33 | 0.8495 | -999.0 | -999.0 | 28.25 | 14.63 | 0.00705142 | 46390.2 | 12.80 | 8.87 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 84024.11 | 30.51 | 0.00569229 | 14.27 | 0.15632344 | -999.0000 | 27.00 | 0.00709087 | 27.00 | 0.00709087 | 26.3328 | 79326.03 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 10106.033 | 5408.445 | 0.566403 | 0.00024750 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1017.9465 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | Sensible | 8584.41 | 8536.10 | 0.8494 | -999.0 | -999.0 | 28.25 | 14.62 | 0.00705047 | 46385.7 | 12.80 | 8.87 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8584.41 | 30.51 | 0.00569229 | 14.27 | 0.01563234 | -999.0000 | 27.00 | 0.00708901 | 27.00 | 0.00708901 | 26.3259 | 8106.99 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 475527.808 | 475527.808 | 25.968380 | 0.01164565 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 475527.81 | 475527.81 | 1.0000 | 25.71931490 | 25.968380 | -7.90 | -7.90 | 0.00234317 | -2112.5 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 475527.81 | -7.90 | 0.00234317 | -7.90 | 0.33839277 | 1.3031 | 0.00 | 0.00700000 | 27.00 | 0.00700000 | 25.9964 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 10356.637 | 10356.637 | 0.580616 | 0.00025363 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 10356.64 | 10356.64 | 1.0000 | 0.57504712 | 0.580616 | -7.90 | -7.90 | 0.00234317 | -2112.5 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10356.64 | -7.90 | 0.00234317 | -7.90 | 0.01563234 | 2.6924 | 0.00 | 0.00699525 | 26.52 | 0.00699525 | 26.7217 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 98913.372 | 98913.372 | 5.542398 | 0.00242238 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 98913.37 | 98913.37 | 1.0000 | 5.48923999 | 5.542398 | -7.90 | -7.90 | 0.00234317 | -2112.5 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 98913.37 | -7.90 | 0.00234317 | -7.90 | 0.15632344 | 2.8205 | 0.00 | 0.00392913 | 24.27 | 0.00392913 | 17.2447 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 10106.033 | 10106.033 | 0.566403 | 0.00024750 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 0.9904 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 10106.03 | 10106.03 | 1.0000 | 0.56097060 | 0.566403 | -7.90 | -7.90 | 0.00234317 | -2112.5 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10106.03 | -7.90 | 0.00234317 | -7.90 | 0.01563234 | 2.7599 | 0.00 | 0.00283710 | 23.09 | 0.00283710 | 13.3873 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 16131.549 | 16131.549 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 25.968380 | 25.71931490 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 16131.55 | 16131.55 | 1.0000 | 25.71931490 | 25.968380 | -0.10 | -0.10 | 0.00693932 | 17250.0 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16131.55 | -7.90 | 0.00234317 | -7.90 | 0.33839277 | 1.3031 | 0.00 | 0.00700000 | 27.00 | 0.00700000 | 25.9964 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 745.211 | 745.211 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.580616 | 0.57504712 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 745.21 | 745.21 | 1.0000 | 0.57504712 | 0.580616 | -0.21 | -0.21 | 0.00687000 | 16965.0 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 745.21 | -7.90 | 0.00234317 | -7.90 | 0.01563234 | 2.6924 | 0.00 | 0.00699525 | 26.52 | 0.00699525 | 26.7217 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 7452.107 | 7452.107 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 5.542398 | 5.48923999 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 7452.11 | 7452.11 | 1.0000 | 5.48923999 | 5.542398 | -0.22 | -1.09 | 0.00388440 | 9489.1 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7452.11 | -7.90 | 0.00234317 | -7.90 | 0.15632344 | 2.8205 | 0.00 | 0.00392913 | 24.27 | 0.00392913 | 17.2447 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 745.211 | 745.211 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9904 | AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.566403 | 0.56097060 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 745.21 | 745.21 | 1.0000 | 0.56097060 | 0.566403 | -0.22 | -2.63 | 0.00282347 | 6841.1 | 40.00 | 18.92 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 745.21 | -7.90 | 0.00234317 | -7.90 | 0.01563234 | 2.7599 | 0.00 | 0.00283710 | 23.09 | 0.00283710 | 13.3873 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:19
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 11.12 | - | |||
VAV_MID WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 103.19 | - | |||
VAV_TOP WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 11.40 | - | |||
CAV_BAS_OA_CONTROLLER | DifferentialDryBulb | 1.20 | 6.47 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 2386.83 | 1579.33 | 216.50 |
CORE_BOTTOM | 2158.17 | 1511.67 | 230.33 |
CORE_MID | 1695.50 | 3258.50 | 278.67 |
CORE_TOP | 2126.67 | 3574.50 | 695.00 |
PERIMETER_BOT_ZN_3 | 1934.00 | 3352.00 | 227.33 |
PERIMETER_BOT_ZN_2 | 2344.50 | 2868.67 | 328.83 |
PERIMETER_BOT_ZN_1 | 2606.67 | 2139.17 | 332.17 |
PERIMETER_BOT_ZN_4 | 2923.83 | 1761.17 | 368.83 |
PERIMETER_MID_ZN_3 | 2765.50 | 3809.67 | 1323.33 |
PERIMETER_MID_ZN_2 | 2365.17 | 2868.33 | 861.67 |
PERIMETER_MID_ZN_1 | 2628.83 | 2495.17 | 538.50 |
PERIMETER_MID_ZN_4 | 2650.50 | 3268.83 | 809.50 |
PERIMETER_TOP_ZN_3 | 3482.00 | 3948.33 | 2083.33 |
PERIMETER_TOP_ZN_2 | 3321.17 | 3439.67 | 1532.50 |
PERIMETER_TOP_ZN_1 | 2841.33 | 2833.33 | 936.50 |
PERIMETER_TOP_ZN_4 | 3197.50 | 3501.50 | 1429.83 |
DATACENTER_BOT_ZN_6 | 5943.00 | 711.50 | 711.50 |
DATACENTER_MID_ZN_6 | 5834.33 | 119.50 | 119.50 |
DATACENTER_TOP_ZN_6 | 5277.33 | 334.17 | 215.67 |
DATACENTER_BASEMENT_ZN_6 | 5943.00 | 5943.00 | 5943.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5943.00 | 5943.00 | 5943.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 85.50 | 0.00 | 3.83 |
CORE_BOTTOM | 0.00 | 9.67 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.50 | 0.00 | 0.00 |
CORE_TOP | 2.00 | 0.17 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 9.83 | 0.00 | 5.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 46.83 | 0.00 | 46.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 86.50 | 0.00 | 79.33 |
PERIMETER_BOT_ZN_4 | 0.00 | 171.00 | 0.00 | 60.67 |
PERIMETER_MID_ZN_3 | 7.67 | 3.67 | 0.33 | 2.33 |
PERIMETER_MID_ZN_2 | 5.83 | 50.33 | 0.00 | 48.17 |
PERIMETER_MID_ZN_1 | 1.67 | 131.00 | 0.00 | 128.00 |
PERIMETER_MID_ZN_4 | 2.17 | 42.17 | 0.00 | 23.83 |
PERIMETER_TOP_ZN_3 | 63.00 | 14.67 | 12.33 | 9.50 |
PERIMETER_TOP_ZN_2 | 41.33 | 58.33 | 1.83 | 51.83 |
PERIMETER_TOP_ZN_1 | 28.17 | 69.00 | 0.67 | 62.00 |
PERIMETER_TOP_ZN_4 | 26.67 | 47.00 | 0.00 | 26.33 |
DATACENTER_BOT_ZN_6 | 0.00 | 126.00 | 0.00 | 106.33 |
DATACENTER_MID_ZN_6 | 0.00 | 63.33 | 0.00 | 53.83 |
DATACENTER_TOP_ZN_6 | 0.00 | 43.33 | 0.00 | 33.33 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 2076.33 | 0.00 | 1376.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 69.33 | 2449.50 | 12.33 | 1629.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:19
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.11 | 149.60 | 6779.02 | 1.481 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.78 | 134.35 | 6849.35 | 1.099 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.78 | 134.35 | 6849.35 | 0.826 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.78 | 134.35 | 6849.35 | 0.787 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 7.00 | 16.87 | 860.00 | 1.000 | 0.043 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.51 | 10.87 | 554.22 | 1.680 | 0.045 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 7.00 | 16.87 | 860.02 | 1.690 | 0.043 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.51 | 10.87 | 554.22 | 2.293 | 0.045 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 7.00 | 16.87 | 860.00 | 0.808 | 0.100 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.94 | 10.87 | 554.22 | 1.518 | 0.112 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 7.00 | 16.87 | 860.02 | 1.517 | 0.101 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.51 | 10.87 | 554.22 | 1.520 | 0.104 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 7.00 | 16.87 | 860.00 | 0.815 | 0.125 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.51 | 10.87 | 554.22 | 1.631 | 0.129 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 7.00 | 16.87 | 860.02 | 1.479 | 0.125 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.51 | 10.87 | 554.22 | 1.559 | 0.129 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.425 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.425 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.425 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.51 | 42.18 | 1911.37 | 0.481 | 0.000 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.11 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.78 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.78 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.78 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 7.00 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 7.00 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 7.00 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.94 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 7.00 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 7.00 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 7.00 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.51 | 42.18 | 1911.37 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 09:04:19
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | CAV_BAS | 62.11 | 149.60 | 6779.02 | 2779.43 | 1.2002 | 1.200 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 55.78 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
CORE_MID | VAV_MID WITH REHEAT | 55.78 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 10.778 |
CORE_TOP | VAV_TOP WITH REHEAT | 55.78 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 7.00 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 7.00 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 7.00 | 16.87 | 860.00 | 313.41 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 3.94 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 7.00 | 16.87 | 860.02 | 313.42 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 7.00 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 7.00 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.81 | 1.95 | 99.34 | 36.20 | 0.1563 | 0.156 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 17.51 | 42.18 | 1911.37 | 783.68 | 0.3384 | 0.338 |
Total Facility | 1029.47 | 2493.19 | 126016.35 | 46320.38 | 1.7261 | 158.471 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 63750506.41 | 0.00 | 63750506.41 | 0.00 | 63750506.41 | 37848132.68 | 3732.84 | 1154.63 | 3872.53 | 520.59 |
CORE_BOTTOM | 49017229.17 | 0.00 | 49017229.17 | 0.00 | 49017229.17 | 33990283.35 | 4323.81 | 31.06 | 4405.13 | 750.08 |
CORE_MID | 0.35E+09 | 0.00 | 0.35E+09 | 0.00 | 0.35E+09 | 0.34E+09 | 5583.19 | 36.85 | 3139.96 | 267.01 |
CORE_TOP | 33115474.70 | 0.00 | 33115474.70 | 0.00 | 33115474.70 | 33990283.35 | 5953.66 | 33.17 | 2773.17 | 367.00 |
PERIMETER_BOT_ZN_3 | 5627628.71 | 0.00 | 5627628.71 | 435989.32 | 6063618.03 | 4267819.30 | 4204.34 | 67.09 | 4488.57 | 750.08 |
PERIMETER_BOT_ZN_2 | 6062800.35 | 0.00 | 6062800.35 | 290659.35 | 6353459.70 | 2750345.05 | 3053.66 | 9.99 | 5696.35 | 750.08 |
PERIMETER_BOT_ZN_1 | 9175193.88 | 0.00 | 9175193.88 | 435989.32 | 9611183.20 | 4267912.63 | 3504.62 | 59.89 | 5195.49 | 750.08 |
PERIMETER_BOT_ZN_4 | 8306859.38 | 0.00 | 8306859.38 | 290659.35 | 8597518.72 | 2750345.05 | 2998.00 | 0.17 | 5761.83 | 750.08 |
PERIMETER_MID_ZN_3 | 42726860.25 | 0.00 | 42726860.25 | 1022509.09 | 43749369.33 | 42678193.03 | 4957.35 | 64.31 | 3738.33 | 267.01 |
PERIMETER_MID_ZN_2 | 55015360.03 | 0.00 | 55015360.03 | 681672.26 | 55697032.29 | 27503450.52 | 3712.59 | 5.27 | 5042.14 | 1176.01 |
PERIMETER_MID_ZN_1 | 78541682.66 | 0.00 | 78541682.66 | 1022509.09 | 79564191.74 | 42679126.28 | 3893.27 | 28.84 | 4837.89 | 267.01 |
PERIMETER_MID_ZN_4 | 51806030.92 | 0.00 | 51806030.92 | 681672.26 | 52487703.18 | 27503450.52 | 3687.14 | 8.91 | 5063.95 | 267.01 |
PERIMETER_TOP_ZN_3 | 4307100.91 | 0.00 | 4307100.91 | 1269544.06 | 5576644.98 | 4267819.30 | 5025.15 | 47.36 | 3687.49 | 367.00 |
PERIMETER_TOP_ZN_2 | 5503111.07 | 0.00 | 5503111.07 | 846362.13 | 6349473.20 | 2750345.05 | 3844.56 | 1.70 | 4913.74 | 367.00 |
PERIMETER_TOP_ZN_1 | 7677636.05 | 0.00 | 7677636.05 | 1269544.06 | 8947180.11 | 4267912.63 | 3889.23 | 5.67 | 4865.10 | 367.00 |
PERIMETER_TOP_ZN_4 | 5314989.22 | 0.00 | 5314989.22 | 846362.13 | 6161351.34 | 2750345.05 | 3823.17 | 3.89 | 4932.94 | 367.00 |
DATACENTER_BOT_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2442960.18 | 0.00 | 2442960.18 | 0.00 | 2442960.18 | 4929815.99 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 5288266.81 | 0.00 | 5288266.81 | 0.00 | 5288266.81 | 10671554.30 | 4419.00 | 4341.00 | 0.00 | 0.00 |
Total Facility | 0.60E+10 | 0.00 | 0.60E+10 | 39768736.56 | 0.60E+10 | 0.50E+10 | 6575.66 | 4405.88 | 6018.81 | 1985.09 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 2.7465 | 0.0000 | 2.7465 | 0.0000 | 2.7465 | 1.2002 | 1281.36 | 1150.54 | 3511.10 |
CORE_BOTTOM | 2.0587 | 0.0000 | 2.0587 | 0.0000 | 2.0587 | 1.0778 | 2162.83 | 28.41 | 3751.76 |
CORE_MID | 15.4786 | 0.0000 | 15.4786 | 0.0000 | 15.4786 | 10.7782 | 2976.42 | 36.05 | 2930.53 |
CORE_TOP | 1.4742 | 0.0000 | 1.4742 | 0.0000 | 1.4742 | 1.0778 | 3314.62 | 33.17 | 2595.21 |
PERIMETER_BOT_ZN_3 | 0.2351 | 0.0000 | 0.2351 | 0.0101 | 0.2452 | 0.1353 | 2033.08 | 64.24 | 3845.68 |
PERIMETER_BOT_ZN_2 | 0.2549 | 0.0000 | 0.2549 | 0.0067 | 0.2616 | 0.0872 | 973.34 | 7.36 | 4962.30 |
PERIMETER_BOT_ZN_1 | 0.3978 | 0.0000 | 0.3978 | 0.0101 | 0.4080 | 0.1353 | 1349.93 | 55.40 | 4537.67 |
PERIMETER_BOT_ZN_4 | 0.3476 | 0.0000 | 0.3476 | 0.0067 | 0.3544 | 0.0872 | 931.03 | 0.17 | 5011.81 |
PERIMETER_MID_ZN_3 | 1.9044 | 0.0000 | 1.9044 | 0.0237 | 1.9282 | 1.3533 | 2353.51 | 62.85 | 3526.64 |
PERIMETER_MID_ZN_2 | 2.3034 | 0.0000 | 2.3034 | 0.0170 | 2.3204 | 0.8721 | 1122.04 | 3.00 | 3908.95 |
PERIMETER_MID_ZN_1 | 3.5705 | 0.0000 | 3.5705 | 0.0237 | 3.5943 | 1.3533 | 1289.42 | 28.37 | 4625.21 |
PERIMETER_MID_ZN_4 | 2.3073 | 0.0000 | 2.3073 | 0.0158 | 2.3232 | 0.8721 | 1103.52 | 7.00 | 4832.48 |
PERIMETER_TOP_ZN_3 | 0.1922 | 0.0000 | 0.1922 | 0.0295 | 0.2217 | 0.1353 | 2388.60 | 47.02 | 3507.38 |
PERIMETER_TOP_ZN_2 | 0.2475 | 0.0000 | 0.2475 | 0.0197 | 0.2672 | 0.0872 | 1217.11 | 0.86 | 4725.02 |
PERIMETER_TOP_ZN_1 | 0.3482 | 0.0000 | 0.3482 | 0.0295 | 0.3777 | 0.1353 | 1251.50 | 5.51 | 4685.99 |
PERIMETER_TOP_ZN_4 | 0.2368 | 0.0000 | 0.2368 | 0.0197 | 0.2565 | 0.0872 | 1203.62 | 1.97 | 4737.41 |
DATACENTER_BOT_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.1142 | 0.0000 | 0.1142 | 0.0000 | 0.1142 | 0.1563 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.2472 | 0.0000 | 0.2472 | 0.0000 | 0.2472 | 0.3384 | 1602.00 | 4341.00 | 0.00 |
Total Facility | 265.5942 | 0.0000 | 265.5942 | 0.9354 | 266.5297 | 158.4706 | 3758.66 | 4382.84 | 5113.43 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV_BOT WITH REHEAT | 76697113.29 | 0.00 | 76697113.29 | 48026705.38 | 3172.06 | 13.80 | 5574.14 | 750.08 |
VAV_MID WITH REHEAT | 0.57E+09 | 0.00 | 0.57E+09 | 0.48E+09 | 3807.46 | 7.77 | 4944.77 | 267.01 |
VAV_TOP WITH REHEAT | 54850807.30 | 0.00 | 54850807.30 | 48026705.38 | 3895.55 | 7.92 | 4856.54 | 367.00 |
CAV_BAS | 62533495.03 | 0.00 | 62533495.03 | 37848132.68 | 4887.42 | 6.14 | 3866.44 | 520.59 |
AIRLOOP DATACENTER BASEMENT | 5187312.62 | 0.00 | 5187312.62 | 10671554.30 | 8760.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 239632.35 | 0.00 | 239632.35 | 492981.60 | 8760.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 2396323.53 | 0.00 | 2396323.53 | 4929815.99 | 8760.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 239632.35 | 0.00 | 239632.35 | 492981.60 | 8760.00 | 0.00 | 0.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV_BOT WITH REHEAT | 3.2312 | 0.0000 | 3.2312 | 1.5229 | 1020.70 | 11.67 | 4910.63 |
VAV_MID WITH REHEAT | 25.2402 | 0.0000 | 25.2402 | 15.2292 | 1202.87 | 7.69 | 4732.44 |
VAV_TOP WITH REHEAT | 2.4513 | 0.0000 | 2.4513 | 1.5229 | 1256.88 | 7.92 | 4678.21 |
CAV_BAS | 2.6941 | 0.0000 | 2.6941 | 1.2002 | 2431.90 | 3.17 | 3507.93 |
AIRLOOP DATACENTER BASEMENT | 0.2425 | 0.0000 | 0.2425 | 0.3384 | 5943.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 0.0112 | 0.0000 | 0.0112 | 0.0156 | 5943.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.1120 | 0.0000 | 0.1120 | 0.1563 | 5943.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.0112 | 0.0000 | 0.0112 | 0.0156 | 5943.00 | 0.00 | 0.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV_BOT WITH REHEAT | 0.00 | 0.03 | 4415.02 | 0.00 | 0.00 | 0.00 | 1347.33 | 0.00 | 0.00 | 0.00 |
VAV_MID WITH REHEAT | 0.00 | 0.17 | 3602.17 | 0.00 | 0.00 | 0.00 | 1541.91 | 0.00 | 0.00 | 0.00 |
VAV_TOP WITH REHEAT | 0.00 | 0.03 | 3314.78 | 0.00 | 0.00 | 0.00 | 1928.75 | 0.00 | 0.00 | 0.00 |
CAV_BAS | 0.00 | 1148.83 | 4057.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV_BOT WITH REHEAT | 0.0000 | 0.0000 | 4.6416 | 0.0000 | 0.0000 | 0.0000 | 1.6301 | 0.0000 | 0.0000 | 0.0000 |
VAV_MID WITH REHEAT | 0.0000 | 0.0000 | 37.4040 | 0.0000 | 0.0000 | 0.0000 | 16.3829 | 0.0000 | 0.0000 | 0.0000 |
VAV_TOP WITH REHEAT | 0.0000 | 0.0000 | 3.8889 | 0.0000 | 0.0000 | 0.0000 | 1.6116 | 0.0000 | 0.0000 | 0.0000 |
CAV_BAS | 0.0000 | 1.1781 | 4.1455 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BASEMENT | 0.0000 | 0.3320 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BOT | 0.0000 | 0.0153 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER MID | 0.0000 | 0.1534 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER TOP | 0.0000 | 0.0153 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:19
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 8 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1380 |
Defaulted Fields | 1179 |
Fields with Defaults | 3862 |
Autosized Fields | 330 |
Autosizable Fields | 409 |
Autocalculated Fields | 226 |
Autocalculatable Fields | 473 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 09:04:19
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 30030.69 | 400769.78 | 22-JAN-10:10 | 1969373.19 | 02-AUG-15:30 |
Electricity:Building | 17954.02 | 247233.96 | 01-JAN-09:00 | 1055078.17 | 01-DEC-17:00 |
Electricity:Zone:BASEMENT | 602.14 | 14319.77 | 01-JAN-00:10 | 28977.00 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 17954.02 | 247233.96 | 01-JAN-09:00 | 1055078.17 | 01-DEC-17:00 |
InteriorLights:Electricity | 2740.61 | 13024.70 | 01-JAN-09:00 | 261074.09 | 13-NOV-17:00 |
InteriorLights:Electricity:Zone:BASEMENT | 177.74 | 862.23 | 01-JAN-00:10 | 15519.45 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 2740.61 | 13024.70 | 01-JAN-09:00 | 261074.09 | 13-NOV-17:00 |
LightsWired:InteriorLights:Electricity | 2740.61 | 13024.70 | 01-JAN-09:00 | 261074.09 | 13-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 177.74 | 862.23 | 01-JAN-00:10 | 15519.45 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 2740.61 | 13024.70 | 01-JAN-09:00 | 261074.09 | 13-NOV-17:00 |
Electricity:Zone:CORE_BOTTOM | 480.91 | 6817.20 | 01-JAN-00:10 | 32066.15 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 159.62 | 774.34 | 01-JAN-00:10 | 13937.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 159.62 | 774.34 | 01-JAN-00:10 | 13937.56 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 4809.09 | 68171.81 | 01-JAN-00:10 | 320660.81 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 1596.25 | 7743.41 | 01-JAN-00:10 | 139375.61 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 1596.25 | 7743.41 | 01-JAN-00:10 | 139375.61 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 480.91 | 6817.18 | 01-JAN-00:10 | 32066.08 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 159.62 | 774.34 | 01-JAN-00:10 | 13937.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 159.62 | 774.34 | 01-JAN-00:10 | 13937.56 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 54.11 | 818.50 | 01-JAN-09:00 | 4026.32 | 13-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 13.77 | 59.73 | 01-JAN-09:00 | 1750.00 | 13-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 13.77 | 59.73 | 01-JAN-09:00 | 1750.00 | 13-NOV-17:00 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 34.86 | 527.47 | 01-JAN-07:50 | 2594.71 | 13-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 8.86 | 38.49 | 01-JAN-07:50 | 1127.77 | 13-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 8.86 | 38.49 | 01-JAN-07:50 | 1127.77 | 13-NOV-17:00 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 54.01 | 818.51 | 01-JAN-07:50 | 4026.39 | 13-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 13.66 | 59.73 | 01-JAN-07:50 | 1750.04 | 13-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 13.66 | 59.73 | 01-JAN-07:50 | 1750.04 | 13-NOV-17:00 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 34.82 | 527.47 | 01-JAN-09:00 | 2594.70 | 13-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 8.82 | 38.49 | 01-JAN-09:00 | 1127.77 | 13-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 8.82 | 38.49 | 01-JAN-09:00 | 1127.77 | 13-NOV-17:00 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 541.20 | 8184.99 | 01-JAN-09:00 | 40263.18 | 13-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 137.78 | 597.26 | 01-JAN-09:00 | 17500.00 | 13-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 137.78 | 597.26 | 01-JAN-09:00 | 17500.00 | 13-NOV-17:00 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 348.63 | 5274.72 | 01-JAN-07:50 | 25947.12 | 13-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 88.65 | 384.90 | 01-JAN-07:50 | 11277.66 | 13-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 88.65 | 384.90 | 01-JAN-07:50 | 11277.66 | 13-NOV-17:00 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 540.12 | 8185.12 | 01-JAN-07:50 | 40263.91 | 13-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 136.69 | 597.27 | 01-JAN-07:50 | 17500.38 | 13-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 136.69 | 597.27 | 01-JAN-07:50 | 17500.38 | 13-NOV-17:00 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 348.19 | 5274.69 | 01-JAN-09:00 | 25947.03 | 13-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 88.22 | 384.90 | 01-JAN-09:00 | 11277.66 | 13-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 88.22 | 384.90 | 01-JAN-09:00 | 11277.66 | 13-NOV-17:00 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 54.12 | 818.50 | 01-JAN-09:00 | 4026.32 | 13-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 13.78 | 59.73 | 01-JAN-09:00 | 1750.00 | 13-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 13.78 | 59.73 | 01-JAN-09:00 | 1750.00 | 13-NOV-17:00 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 34.86 | 527.47 | 01-JAN-07:50 | 2594.71 | 13-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 8.86 | 38.49 | 01-JAN-07:50 | 1127.77 | 13-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 8.86 | 38.49 | 01-JAN-07:50 | 1127.77 | 13-NOV-17:00 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 54.01 | 818.51 | 01-JAN-07:50 | 4026.39 | 13-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 13.67 | 59.73 | 01-JAN-07:50 | 1750.04 | 13-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 13.67 | 59.73 | 01-JAN-07:50 | 1750.04 | 13-NOV-17:00 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 34.82 | 527.47 | 01-JAN-09:00 | 2594.70 | 13-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 8.82 | 38.49 | 01-JAN-09:00 | 1127.77 | 13-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 8.82 | 38.49 | 01-JAN-09:00 | 1127.77 | 13-NOV-17:00 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7544.97 | 95151.24 | 01-JAN-00:10 | 384008.34 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 50.12 | 243.11 | 01-JAN-00:10 | 4375.82 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 50.12 | 243.11 | 01-JAN-00:10 | 4375.82 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 158.52 | 1971.11 | 01-JAN-00:10 | 8199.53 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 4.64 | 22.51 | 01-JAN-00:10 | 405.10 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 4.64 | 22.51 | 01-JAN-00:10 | 405.10 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1585.20 | 19711.13 | 01-JAN-00:10 | 81995.25 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 46.40 | 225.07 | 01-JAN-00:10 | 4051.03 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 46.40 | 225.07 | 01-JAN-00:10 | 4051.03 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 158.52 | 1971.11 | 01-JAN-00:10 | 8199.53 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 4.64 | 22.51 | 01-JAN-00:10 | 405.10 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 4.64 | 22.51 | 01-JAN-00:10 | 405.10 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 15213.41 | 234209.26 | 01-JAN-00:10 | 794004.08 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 15213.41 | 234209.26 | 01-JAN-00:10 | 794004.08 | 03-APR-07:10 |
MiscPlug:InteriorEquipment:Electricity | 5871.99 | 115917.86 | 01-JAN-00:10 | 320838.49 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 5871.99 | 115917.86 | 01-JAN-00:10 | 320838.49 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 321.29 | 6042.86 | 01-JAN-00:10 | 18128.59 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 321.29 | 6042.86 | 01-JAN-00:10 | 18128.59 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 3212.85 | 60428.40 | 01-JAN-00:10 | 181285.20 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 3212.85 | 60428.40 | 01-JAN-00:10 | 181285.20 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 321.28 | 6042.84 | 01-JAN-00:10 | 18128.52 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 321.28 | 6042.84 | 01-JAN-00:10 | 18128.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 40.34 | 758.77 | 01-JAN-00:10 | 2276.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 40.34 | 758.77 | 01-JAN-00:10 | 2276.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.95 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.95 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 40.34 | 758.78 | 01-JAN-00:10 | 2276.35 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 40.34 | 758.78 | 01-JAN-00:10 | 2276.35 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.94 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.94 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 403.42 | 7587.73 | 01-JAN-00:10 | 22763.18 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 403.42 | 7587.73 | 01-JAN-00:10 | 22763.18 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 259.98 | 4889.82 | 01-JAN-00:10 | 14669.46 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 259.98 | 4889.82 | 01-JAN-00:10 | 14669.46 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 403.43 | 7587.84 | 01-JAN-00:10 | 22763.53 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 403.43 | 7587.84 | 01-JAN-00:10 | 22763.53 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 259.98 | 4889.79 | 01-JAN-00:10 | 14669.36 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 259.98 | 4889.79 | 01-JAN-00:10 | 14669.36 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 40.34 | 758.77 | 01-JAN-00:10 | 2276.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 40.34 | 758.77 | 01-JAN-00:10 | 2276.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.95 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.95 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 40.34 | 758.78 | 01-JAN-00:10 | 2276.35 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 40.34 | 758.78 | 01-JAN-00:10 | 2276.35 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.94 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.94 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
Electricity:Plant | 2661.92 | 6761.08 | 20-JAN-02:00 | 386989.65 | 05-SEP-13:10 |
HeatRejection:Electricity | 1150.78 | 2812.04 | 21-JAN-07:10 | 81203.66 | 06-JUN-13:00 |
General:HeatRejection:Electricity | 1150.78 | 2812.04 | 21-JAN-07:10 | 81203.66 | 06-JUN-13:00 |
Electricity:HVAC | 7112.79 | 110883.97 | 22-JAN-07:30 | 527435.34 | 07-AUG-15:40 |
ExteriorEquipment:Electricity | 1914.38 | 28294.68 | 01-JAN-00:10 | 117200.69 | 02-NOV-07:20 |
Transformer:ExteriorEquipment:Electricity | 59.77 | 1112.61 | 01-JAN-00:10 | 3726.76 | 05-DEC-17:00 |
ElectricityPurchased:Facility | 30030.69 | 400769.78 | 22-JAN-10:10 | 1969373.19 | 02-AUG-15:30 |
ElectricityPurchased:Plant | 30030.69 | 400769.78 | 22-JAN-10:10 | 1969373.19 | 02-AUG-15:30 |
Cogeneration:ElectricityPurchased | 30030.69 | 400769.78 | 22-JAN-10:10 | 1969373.19 | 02-AUG-15:30 |
General:Cogeneration:ElectricityPurchased | 30030.69 | 400769.78 | 22-JAN-10:10 | 1969373.19 | 02-AUG-15:30 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 30030.69 | 400769.78 | 22-JAN-10:10 | 1969373.19 | 02-AUG-15:30 |
ElectricityNet:Plant | 30030.69 | 400769.78 | 22-JAN-10:10 | 1969373.19 | 02-AUG-15:30 |
Cogeneration:ElectricityNet | 30030.69 | 400769.78 | 22-JAN-10:10 | 1969373.19 | 02-AUG-15:30 |
General:Cogeneration:ElectricityNet | 30030.69 | 400769.78 | 22-JAN-10:10 | 1969373.19 | 02-AUG-15:30 |
Fans:Electricity | 2824.89 | 50321.14 | 02-JAN-22:10 | 280561.00 | 07-AUG-15:40 |
General:Fans:Electricity | 2824.89 | 50321.14 | 02-JAN-22:10 | 280561.00 | 07-AUG-15:40 |
ExteriorLights:Electricity | 447.35 | 0.00 | 01-JAN-07:20 | 37611.08 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 447.35 | 0.00 | 01-JAN-07:20 | 37611.08 | 01-JAN-06:10 |
ElevatorLift:ExteriorEquipment:Electricity | 1848.78 | 27144.47 | 01-JAN-00:10 | 113101.96 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 5.83 | 37.60 | 01-JAN-00:10 | 376.00 | 01-JAN-07:10 |
Cooling:Electricity | 3998.22 | 35955.30 | 17-JAN-08:00 | 419477.62 | 01-AUG-15:10 |
General:Cooling:Electricity | 3998.22 | 35955.30 | 17-JAN-08:00 | 419477.62 | 01-AUG-15:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Humidifier:Electricity | 1154.63 | 0.00 | 06-JUL-15:50 | 75857.24 | 23-DEC-07:30 |
General:Humidifier:Electricity | 1154.63 | 0.00 | 06-JUL-15:50 | 75857.24 | 23-DEC-07:30 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Pumps:Electricity | 586.42 | 3715.86 | 01-JAN-00:10 | 66759.28 | 21-JUL-16:00 |
General:Pumps:Electricity | 586.42 | 3715.86 | 01-JAN-00:10 | 66759.28 | 21-JUL-16:00 |
WIRED_LTG_ELECTRICITY | 77.01 | 0.00 | 01-JAN-00:10 | 7336.18 | 13-NOV-17:10 |
WIRED_INT_EQUIP | 5871.99 | 115917.86 | 04-MAR-00:10 | 320838.49 | 03-APR-07:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 1421.99 | 5695.87 | 06-FEB-06:00 | 771014.08 | 06-FEB-07:10 |
NaturalGas:Plant | 1421.99 | 5695.87 | 06-FEB-06:00 | 771014.08 | 06-FEB-07:10 |
Heating:NaturalGas | 729.01 | 0.00 | 01-JAN-00:10 | 744684.27 | 06-FEB-07:20 |
Boiler:Heating:NaturalGas | 729.01 | 0.00 | 01-JAN-00:10 | 744684.27 | 06-FEB-07:20 |
WaterSystems:NaturalGas | 692.99 | 5695.87 | 03-JAN-05:10 | 81629.56 | 07-FEB-13:00 |
Water Heater:WaterSystems:NaturalGas | 692.99 | 5695.87 | 03-JAN-05:10 | 81629.56 | 07-FEB-13:00 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 20857.91 | 176460.08 | 21-JAN-07:10 | 2311250.62 | 07-AUG-15:40 |
PlantLoopCoolingDemand:HVAC | 20857.91 | 176460.08 | 21-JAN-07:10 | 2311250.62 | 07-AUG-15:40 |
CoolingCoils:PlantLoopCoolingDemand | 20857.91 | 176460.08 | 21-JAN-07:10 | 2311250.62 | 07-AUG-15:40 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 9079.66 | 0.00 | 31-AUG-23:10 | 0.00 | 28-JUN-16:20 |
Water:HVAC | 429.52 | 0.00 | 06-JUL-15:50 | 0.00 | 23-DEC-07:30 |
Humidifier:Water | 429.52 | 0.00 | 06-JUL-15:50 | 0.00 | 23-DEC-07:30 |
General:Humidifier:Water | 429.52 | 0.00 | 06-JUL-15:50 | 0.00 | 23-DEC-07:30 |
MainsWater:Facility | 9079.66 | 0.00 | 31-AUG-23:10 | 0.00 | 28-JUN-16:20 |
MainsWater:HVAC | 429.52 | 0.00 | 06-JUL-15:50 | 0.00 | 23-DEC-07:30 |
Humidifier:MainsWater | 429.52 | 0.00 | 06-JUL-15:50 | 0.00 | 23-DEC-07:30 |
General:Humidifier:MainsWater | 429.52 | 0.00 | 06-JUL-15:50 | 0.00 | 23-DEC-07:30 |
Water:Plant | 8650.14 | 0.00 | 01-JAN-00:10 | 0.00 | 28-JUN-16:20 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 8650.14 | 0.00 | 01-JAN-00:10 | 0.00 | 28-JUN-16:20 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatRejection:Water | 6369.97 | 0.00 | 01-JAN-00:10 | 0.00 | 28-JUN-16:20 |
General:HeatRejection:Water | 6369.97 | 0.00 | 01-JAN-00:10 | 0.00 | 28-JUN-16:20 |
HeatRejection:MainsWater | 6369.97 | 0.00 | 01-JAN-00:10 | 0.00 | 28-JUN-16:20 |
General:HeatRejection:MainsWater | 6369.97 | 0.00 | 01-JAN-00:10 | 0.00 | 28-JUN-16:20 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 59045.74 | 246406.49 | 22-JAN-05:30 | 8892381.94 | 05-SEP-13:00 |
EnergyTransfer:Building | 19499.82 | 88947.44 | 29-JAN-08:40 | 1618588.19 | 07-AUG-15:30 |
EnergyTransfer:Zone:BASEMENT | 681.35 | 0.00 | 01-JAN-00:10 | 69590.19 | 13-NOV-06:10 |
Heating:EnergyTransfer | 186.05 | 0.00 | 01-JAN-17:20 | 469125.86 | 17-JAN-05:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 3.93 | 0.00 | 01-JAN-00:10 | 22163.15 | 22-JUL-16:10 |
General:Heating:EnergyTransfer | 186.05 | 0.00 | 01-JAN-17:20 | 469125.86 | 17-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 3.93 | 0.00 | 01-JAN-00:10 | 22163.15 | 22-JUL-16:10 |
Cooling:EnergyTransfer | 19313.77 | 88018.02 | 22-JAN-08:10 | 1618588.19 | 07-AUG-15:30 |
Cooling:EnergyTransfer:Zone:BASEMENT | 677.42 | 0.00 | 01-JAN-00:10 | 69590.19 | 13-NOV-06:10 |
General:Cooling:EnergyTransfer | 19313.77 | 88018.02 | 22-JAN-08:10 | 1618588.19 | 07-AUG-15:30 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 677.42 | 0.00 | 01-JAN-00:10 | 69590.19 | 13-NOV-06:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 655.08 | 0.00 | 01-JAN-00:10 | 61398.91 | 21-AUG-07:20 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 655.08 | 0.00 | 01-JAN-00:10 | 61398.91 | 21-AUG-07:20 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 655.08 | 0.00 | 01-JAN-00:10 | 61398.91 | 21-AUG-07:20 |
EnergyTransfer:Zone:CORE_MID | 4623.44 | 0.00 | 01-JAN-00:10 | 427937.35 | 05-SEP-10:00 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 4623.44 | 0.00 | 01-JAN-00:10 | 427937.35 | 05-SEP-10:00 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 4623.44 | 0.00 | 01-JAN-00:10 | 427937.35 | 05-SEP-10:00 |
EnergyTransfer:Zone:CORE_TOP | 432.06 | 0.00 | 01-JAN-00:10 | 54723.90 | 17-JAN-06:10 |
Heating:EnergyTransfer:Zone:CORE_TOP | 3.60 | 0.00 | 01-JAN-00:10 | 54723.90 | 17-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 3.60 | 0.00 | 01-JAN-00:10 | 54723.90 | 17-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 428.45 | 0.00 | 01-JAN-00:10 | 50872.65 | 07-AUG-14:00 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 428.45 | 0.00 | 01-JAN-00:10 | 50872.65 | 07-AUG-14:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 77.08 | 0.00 | 01-JAN-00:10 | 11010.04 | 07-AUG-14:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 1067.81 | 06-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 1067.81 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 77.08 | 0.00 | 01-JAN-00:10 | 11010.04 | 07-AUG-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 77.08 | 0.00 | 01-JAN-00:10 | 11010.04 | 07-AUG-14:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 78.93 | 0.00 | 01-JAN-00:10 | 13463.12 | 05-JUL-07:40 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.02 | 0.00 | 01-JAN-00:10 | 1269.41 | 21-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.02 | 0.00 | 01-JAN-00:10 | 1269.41 | 21-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 78.92 | 0.00 | 01-JAN-00:10 | 13463.12 | 05-JUL-07:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 78.92 | 0.00 | 01-JAN-00:10 | 13463.12 | 05-JUL-07:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 126.05 | 0.00 | 01-JAN-00:10 | 17050.27 | 28-SEP-13:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.05 | 0.00 | 01-JAN-00:10 | 4115.29 | 17-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.05 | 0.00 | 01-JAN-00:10 | 4115.29 | 17-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 126.00 | 0.00 | 01-JAN-00:10 | 17050.27 | 28-SEP-13:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 126.00 | 0.00 | 01-JAN-00:10 | 17050.27 | 28-SEP-13:20 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 116.69 | 0.00 | 01-JAN-00:10 | 18792.75 | 21-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 116.69 | 0.00 | 01-JAN-00:10 | 18792.75 | 21-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 116.69 | 0.00 | 01-JAN-00:10 | 18792.75 | 21-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 576.13 | 0.00 | 01-JAN-00:10 | 105267.01 | 06-FEB-05:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 33.06 | 0.00 | 01-JAN-00:10 | 105267.01 | 06-FEB-05:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 33.06 | 0.00 | 01-JAN-00:10 | 105267.01 | 06-FEB-05:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 543.07 | 0.00 | 01-JAN-00:10 | 100098.09 | 29-JUN-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 543.07 | 0.00 | 01-JAN-00:10 | 100098.09 | 29-JUN-15:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 705.65 | 0.00 | 01-JAN-00:10 | 138583.63 | 05-JUL-08:40 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 14.26 | 0.00 | 01-JAN-00:10 | 70682.21 | 06-FEB-05:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 14.26 | 0.00 | 01-JAN-00:10 | 70682.21 | 06-FEB-05:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 691.39 | 0.00 | 01-JAN-00:10 | 138583.63 | 05-JUL-08:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 691.39 | 0.00 | 01-JAN-00:10 | 138583.63 | 05-JUL-08:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1096.06 | 0.00 | 01-JAN-00:10 | 171776.37 | 28-SEP-13:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 8.29 | 0.00 | 01-JAN-00:10 | 90644.63 | 17-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 8.29 | 0.00 | 01-JAN-00:10 | 90644.63 | 17-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1087.77 | 0.00 | 01-JAN-00:10 | 171776.37 | 28-SEP-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1087.77 | 0.00 | 01-JAN-00:10 | 171776.37 | 28-SEP-13:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 706.81 | 0.00 | 01-JAN-00:10 | 153359.73 | 28-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 9.12 | 0.00 | 01-JAN-00:10 | 63044.54 | 06-FEB-05:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 9.12 | 0.00 | 01-JAN-00:10 | 63044.54 | 06-FEB-05:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 697.69 | 0.00 | 01-JAN-00:10 | 153359.73 | 28-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 697.69 | 0.00 | 01-JAN-00:10 | 153359.73 | 28-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 66.70 | 0.00 | 01-JAN-00:10 | 14479.80 | 17-JAN-04:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 14.94 | 0.00 | 01-JAN-00:10 | 14479.80 | 17-JAN-04:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 14.94 | 0.00 | 01-JAN-00:10 | 14479.80 | 17-JAN-04:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 51.76 | 0.00 | 01-JAN-00:10 | 11407.76 | 29-JUN-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 51.76 | 0.00 | 01-JAN-00:10 | 11407.76 | 29-JUN-15:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 73.01 | 0.00 | 01-JAN-00:10 | 14175.10 | 05-JUL-08:50 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 6.36 | 0.00 | 01-JAN-00:10 | 13776.79 | 17-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 6.36 | 0.00 | 01-JAN-00:10 | 13776.79 | 17-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 66.65 | 0.00 | 01-JAN-00:10 | 14175.10 | 05-JUL-08:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 66.65 | 0.00 | 01-JAN-00:10 | 14175.10 | 05-JUL-08:50 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 107.64 | 0.00 | 01-JAN-00:10 | 18665.80 | 28-SEP-13:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 5.75 | 0.00 | 01-JAN-00:10 | 15952.20 | 17-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 5.75 | 0.00 | 01-JAN-00:10 | 15952.20 | 17-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 101.89 | 0.00 | 01-JAN-00:10 | 18665.80 | 28-SEP-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 101.89 | 0.00 | 01-JAN-00:10 | 18665.80 | 28-SEP-13:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 72.11 | 0.00 | 01-JAN-00:10 | 16303.62 | 28-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 4.82 | 0.00 | 01-JAN-00:10 | 12657.45 | 17-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 4.82 | 0.00 | 01-JAN-00:10 | 12657.45 | 17-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 67.29 | 0.00 | 01-JAN-00:10 | 16303.62 | 28-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 67.29 | 0.00 | 01-JAN-00:10 | 16303.62 | 28-JUN-16:00 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 68.50 | 0.00 | 01-JAN-00:10 | 11857.28 | 21-AUG-07:10 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 1.76 | 0.00 | 01-JAN-00:10 | 4185.24 | 24-DEC-10:30 |
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 1.76 | 0.00 | 01-JAN-00:10 | 4185.24 | 24-DEC-10:30 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 66.74 | 0.00 | 01-JAN-00:10 | 11857.28 | 21-AUG-07:10 |
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 66.74 | 0.00 | 01-JAN-00:10 | 11857.28 | 21-AUG-07:10 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 478.89 | 0.00 | 01-JAN-00:10 | 80584.90 | 05-JUL-15:00 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 53.91 | 0.00 | 01-JAN-00:10 | 48216.51 | 06-FEB-15:20 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 53.91 | 0.00 | 01-JAN-00:10 | 48216.51 | 06-FEB-15:20 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 424.98 | 0.00 | 01-JAN-00:10 | 80584.90 | 05-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 424.98 | 0.00 | 01-JAN-00:10 | 80584.90 | 05-JUL-15:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 103.47 | 0.00 | 01-JAN-00:10 | 23285.87 | 28-JUN-13:30 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 25.15 | 0.00 | 01-JAN-00:10 | 21004.75 | 06-FEB-06:20 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 25.15 | 0.00 | 01-JAN-00:10 | 21004.75 | 06-FEB-06:20 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 78.32 | 0.00 | 01-JAN-00:10 | 23285.87 | 28-JUN-13:30 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 78.32 | 0.00 | 01-JAN-00:10 | 23285.87 | 28-JUN-13:30 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 141.14 | 773.90 | 21-JAN-08:00 | 8155.20 | 15-APR-18:00 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 141.14 | 773.90 | 21-JAN-08:00 | 8155.20 | 15-APR-18:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 141.14 | 773.90 | 21-JAN-08:00 | 8155.20 | 15-APR-18:00 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1248.07 | 5.88 | 19-JAN-01:20 | 76454.80 | 24-APR-18:00 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.30 | 0.00 | 01-JAN-00:10 | 4980.24 | 17-JAN-05:00 |
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.30 | 0.00 | 01-JAN-00:10 | 4980.24 | 17-JAN-05:00 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1247.77 | 0.00 | 01-JAN-04:30 | 76454.80 | 24-APR-18:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1247.77 | 0.00 | 01-JAN-04:30 | 76454.80 | 24-APR-18:00 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 117.13 | 0.51 | 07-JAN-16:50 | 7750.97 | 16-APR-18:00 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.72 | 0.00 | 01-JAN-16:10 | 674.30 | 18-JAN-01:30 |
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.72 | 0.00 | 01-JAN-16:10 | 674.30 | 18-JAN-01:30 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 116.41 | 0.00 | 01-JAN-00:10 | 7750.97 | 16-APR-18:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 116.41 | 0.00 | 01-JAN-00:10 | 7750.97 | 16-APR-18:00 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7147.83 | 87167.51 | 22-JAN-09:20 | 366750.82 | 18-APR-07:20 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7147.83 | 87167.51 | 22-JAN-09:20 | 366750.82 | 18-APR-07:20 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7147.83 | 87167.51 | 22-JAN-09:20 | 366750.82 | 18-APR-07:20 |
PlantLoopHeatingDemand:Facility | 931.57 | 0.00 | 01-JAN-00:10 | 666548.51 | 06-FEB-07:10 |
PlantLoopHeatingDemand:Plant | 400.27 | 0.00 | 01-JAN-00:10 | 50687.87 | 06-FEB-12:40 |
WaterSystems:PlantLoopHeatingDemand | 400.27 | 0.00 | 01-JAN-00:10 | 50687.87 | 06-FEB-12:40 |
General:WaterSystems:PlantLoopHeatingDemand | 400.27 | 0.00 | 01-JAN-00:10 | 50687.87 | 06-FEB-12:40 |
EnergyTransfer:HVAC | 18315.70 | 153658.44 | 17-JAN-03:30 | 2132805.18 | 23-AUG-16:00 |
HeatingCoils:EnergyTransfer | 531.29 | 0.00 | 01-JAN-00:10 | 649745.41 | 06-FEB-07:10 |
PlantLoopHeatingDemand:HVAC | 531.29 | 0.00 | 01-JAN-00:10 | 649745.41 | 06-FEB-07:10 |
HeatingCoils:PlantLoopHeatingDemand | 531.29 | 0.00 | 01-JAN-00:10 | 649745.41 | 06-FEB-07:10 |
CoolingCoils:EnergyTransfer | 17784.40 | 140338.46 | 21-JAN-07:10 | 2132805.18 | 23-AUG-16:00 |
EnergyTransfer:Plant | 21230.23 | 0.00 | 01-JAN-00:10 | 5724597.06 | 05-SEP-13:00 |
LoopToLoop:EnergyTransfer | 6781.56 | 0.00 | 01-JAN-00:10 | 1808943.26 | 05-SEP-13:00 |
WaterSystems:EnergyTransfer | 400.27 | 0.00 | 01-JAN-00:10 | 50687.87 | 06-FEB-12:40 |
WaterUse:WaterSystems:EnergyTransfer | 400.27 | 0.00 | 01-JAN-00:10 | 50687.87 | 06-FEB-12:40 |
Boilers:EnergyTransfer | 526.52 | 0.00 | 01-JAN-00:10 | 620176.37 | 06-FEB-07:20 |
Chillers:EnergyTransfer | 6298.58 | 0.00 | 01-JAN-00:10 | 1818485.64 | 05-SEP-13:10 |
HeatRejection:EnergyTransfer | 7223.29 | 0.00 | 01-JAN-00:10 | 2064023.10 | 05-SEP-13:10 |
General:HeatRejection:EnergyTransfer | 7223.29 | 0.00 | 01-JAN-00:10 | 2064023.10 | 05-SEP-13:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:19
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 3.932 | -677.411 | 0.000 | 0.000 | 92.693 | 177.742 | 424.397 | 0.000 | 0.000 | 0.000 | 0.005 | 0.000 | 0.000 | 0.000 | 0.000 | -21.353 |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -655.073 | 0.000 | 0.000 | 83.423 | 159.625 | 321.286 | 0.000 | 0.000 | 0.000 | 90.739 | 0.000 | 0.000 | 0.000 | 0.000 | -0.000 |
CORE_MID | 0.000 | 0.000 | 0.000 | -4623.405 | 0.000 | 0.000 | 839.219 | 1596.246 | 3212.845 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -1024.905 |
CORE_TOP | 0.000 | 0.000 | 3.605 | -428.449 | 0.000 | 0.000 | 86.166 | 159.625 | 321.285 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -142.231 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.005 | -77.076 | 0.000 | 0.000 | 10.699 | 13.767 | 40.342 | 28.784 | 0.000 | 0.188 | 33.530 | 0.000 | -45.394 | 0.000 | -4.846 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.017 | -78.915 | 0.000 | 0.000 | 6.875 | 8.862 | 25.998 | 69.593 | 0.000 | 0.129 | 0.001 | 0.000 | -27.725 | 0.000 | -3.214 | -1.620 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 0.051 | -126.002 | 0.000 | 0.000 | 10.552 | 13.664 | 40.343 | 124.545 | 0.000 | 0.185 | 0.004 | 0.000 | -42.617 | 0.000 | -5.011 | -15.710 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.000 | -116.686 | 0.000 | 0.000 | 6.803 | 8.819 | 25.998 | 63.327 | 0.000 | 0.115 | 48.021 | 0.000 | -32.809 | 0.000 | -3.589 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 33.059 | -543.064 | 0.000 | 0.000 | 111.568 | 137.779 | 403.423 | 298.824 | 0.000 | 4.391 | 69.075 | 0.000 | -413.126 | 0.000 | -101.928 | 0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 14.263 | -691.385 | 0.000 | 0.000 | 51.862 | 88.645 | 259.981 | 696.710 | 0.000 | 2.835 | 0.039 | 0.000 | -263.101 | 0.000 | -71.044 | -88.767 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 8.290 | -1087.747 | 0.000 | 0.000 | 106.240 | 136.695 | 403.429 | 1242.365 | 0.000 | 4.193 | 0.004 | 0.000 | -415.491 | 0.000 | -113.452 | -284.521 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 9.119 | -697.673 | 0.000 | 0.000 | 71.169 | 88.216 | 259.979 | 644.662 | 0.000 | 2.731 | 0.002 | 0.000 | -288.928 | 0.000 | -73.490 | -15.785 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 14.940 | -51.760 | 0.000 | 0.000 | 11.341 | 13.778 | 40.342 | 30.297 | 0.000 | 0.511 | 0.005 | 0.000 | -38.738 | 0.000 | -11.799 | -8.914 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 6.358 | -66.649 | 0.000 | 0.000 | 7.147 | 8.865 | 25.998 | 70.015 | 0.000 | 0.333 | 0.002 | 0.000 | -24.903 | 0.000 | -8.295 | -18.869 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 5.748 | -101.886 | 0.000 | 0.000 | 10.800 | 13.670 | 40.343 | 124.721 | 0.000 | 0.498 | 0.003 | 0.000 | -39.312 | 0.000 | -13.228 | -41.355 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 4.822 | -67.285 | 0.000 | 0.000 | 7.223 | 8.822 | 25.998 | 64.612 | 0.000 | 0.327 | 0.000 | 0.000 | -27.441 | 0.000 | -8.614 | -8.462 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.000 | -141.144 | 0.000 | 0.000 | 0.948 | 4.640 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -18.324 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 0.304 | -1247.770 | 0.000 | 0.000 | 9.491 | 46.396 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -347.227 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 0.722 | -116.410 | 0.000 | 0.000 | 0.951 | 4.640 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -43.783 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | 0.000 | 0.000 | -7147.844 | 0.000 | 0.000 | 19.115 | 50.116 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -416.244 |
GROUNDFLOOR_PLENUM | 1.764 | -66.736 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.345 | 75.034 | 0.000 | 0.000 | 0.000 | -10.407 | 0.000 |
MIDFLOOR_PLENUM | 53.907 | -424.978 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 6.332 | 542.867 | 0.000 | 0.000 | 0.000 | -178.128 | -0.001 |
TOPFLOOR_PLENUM | 25.150 | -78.313 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.528 | 71.468 | 0.000 | 0.000 | 0.000 | -18.833 | -0.005 |
Total Facility | 80.821 | -570.027 | 105.234 | -18743.634 | 0.000 | 0.000 | 1544.286 | 2740.610 | 15213.411 | 3458.455 | 0.000 | 23.641 | 930.800 | 0.000 | -1659.583 | 0.000 | -625.878 | -2498.077 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 11-DEC-04:01 | 0.00 | 0.00 | 0.00 | -106944.91 | 0.00 | 0.00 | 0.00 | 862.23 | 13457.54 | 0.00 | 0.00 | 0.00 | 92625.14 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 10-OCT-03:02 | 0.00 | 0.00 | 0.00 | -88892.34 | 0.00 | 0.00 | 0.00 | 774.34 | 8057.15 | 0.00 | 0.00 | 0.00 | 80060.85 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 05-SEP-03:02 | 0.00 | 0.00 | 0.00 | -803897.20 | 0.00 | 0.00 | 0.00 | 7743.41 | 80571.20 | 0.00 | 0.00 | 0.00 | 715582.60 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 10-JUL-03:02 | 0.00 | 0.00 | 0.00 | -82000.77 | 0.00 | 0.00 | 0.00 | 774.34 | 8057.12 | 0.00 | 0.00 | 0.00 | 73169.31 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 18-JUN-18:11 | 0.00 | 0.00 | 0.00 | -16427.66 | 0.00 | 0.00 | 0.00 | 59.73 | 758.77 | 5930.82 | 0.00 | 129.69 | 9548.65 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 30-JUL-08:41 | 0.00 | 0.00 | 0.00 | -20677.55 | 0.00 | 0.00 | 20.96 | 38.49 | 488.98 | 15102.26 | 0.00 | 0.00 | 5046.11 | 0.00 | -0.00 | 0.00 | -19.25 | 0.00 |
PERIMETER_BOT_ZN_1 | 01-OCT-14:51 | 0.00 | 0.00 | 0.00 | -22001.63 | 0.00 | 0.00 | 33.84 | 59.73 | 758.78 | 12639.52 | 0.00 | 0.00 | 8512.32 | 0.00 | -0.00 | 0.00 | -2.56 | 0.00 |
PERIMETER_BOT_ZN_4 | 30-JUL-16:01 | 0.00 | 0.00 | 0.00 | -28212.96 | 0.00 | 0.00 | 15.74 | 38.49 | 488.98 | 16356.43 | 0.00 | 60.87 | 11252.45 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 04-JUL-17:01 | 0.00 | 0.00 | 0.00 | -158541.75 | 0.00 | 0.00 | 0.00 | 597.26 | 7587.73 | 47756.10 | 0.00 | 8896.76 | 93703.91 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 04-JUL-08:21 | 0.00 | 0.00 | 0.00 | -226042.86 | 0.00 | 0.00 | 188.26 | 384.90 | 4889.82 | 161215.78 | 0.00 | 0.00 | 60515.81 | 0.00 | -0.00 | 0.00 | -1151.71 | 0.00 |
PERIMETER_MID_ZN_1 | 03-SEP-12:21 | 0.00 | 0.00 | 0.00 | -214581.99 | 0.00 | 0.00 | 331.88 | 597.27 | 7587.84 | 173841.16 | 0.00 | 741.33 | 31482.50 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 04-JUL-17:01 | 0.00 | 0.00 | 0.00 | -256172.82 | 0.00 | 0.00 | 0.00 | 384.90 | 4889.79 | 170693.12 | 0.00 | 3846.82 | 76358.19 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 04-JUL-16:21 | 0.00 | 0.00 | 0.00 | -18846.86 | 0.00 | 0.00 | 38.46 | 59.73 | 758.77 | 3986.10 | 0.00 | 973.54 | 13030.26 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 04-JUL-08:21 | 0.00 | 0.00 | 0.00 | -22963.53 | 0.00 | 0.00 | 18.81 | 38.49 | 488.98 | 16091.46 | 0.00 | 0.00 | 6472.29 | 0.00 | -0.00 | 0.00 | -146.51 | 0.00 |
PERIMETER_TOP_ZN_1 | 01-OCT-11:21 | 0.00 | 0.00 | 0.00 | -24367.76 | 0.00 | 0.00 | 31.55 | 59.73 | 758.78 | 22714.44 | 0.00 | 0.00 | 919.90 | 0.00 | -0.00 | 0.00 | -116.64 | 0.00 |
PERIMETER_TOP_ZN_4 | 04-JUL-16:21 | 0.00 | 0.00 | 0.00 | -27990.76 | 0.00 | 0.00 | 13.83 | 38.49 | 488.98 | 17394.26 | 0.00 | 425.52 | 9629.69 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 15-APR-18:00 | 0.00 | 0.00 | 0.00 | -8155.25 | 0.00 | 0.00 | 5.31 | 22.51 | 7794.42 | 0.00 | 0.00 | 0.00 | 333.01 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 24-APR-18:00 | 0.00 | 0.00 | 0.00 | -76448.16 | 0.00 | 0.00 | 106.16 | 1350.33 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2952.55 |
DATACENTER_TOP_ZN_6 | 16-APR-18:00 | 0.00 | 0.00 | 0.00 | -7753.32 | 0.00 | 0.00 | 0.00 | 22.51 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -63.61 |
DATACENTER_BASEMENT_ZN_6 | 18-APR-07:15 | 0.00 | 0.00 | 0.00 | -366755.92 | 0.00 | 0.00 | 1976.78 | 4375.82 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -19229.20 |
GROUNDFLOOR_PLENUM | 07-AUG-05:15 | 0.00 | -14072.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14134.76 | 0.00 | -0.00 | 0.00 | -62.39 | 0.00 |
MIDFLOOR_PLENUM | 05-JUL-05:15 | 0.00 | -83617.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84727.08 | 0.00 | -0.00 | 0.00 | -1109.51 | 0.00 |
TOPFLOOR_PLENUM | 28-JUN-13:30 | 0.00 | -23280.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 199.27 | 23080.95 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 07-AUG-05:02 | 0.00 | -42162.91 | 0.00 | -1972692.01 | 0.00 | 0.00 | 15367.15 | 29009.37 | 623236.89 | 0.00 | 0.00 | 0.00 | 1409037.30 | 0.00 | -58257.77 | 0.00 | -3538.03 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 22-JUL-16:01 | 0.00 | 0.00 | 23471.31 | 0.00 | 0.00 | 0.00 | 520.13 | 862.23 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -38311.21 |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 17-JAN-04:11 | 0.00 | 0.00 | 72705.16 | 0.00 | 0.00 | 0.00 | 0.00 | 774.34 | 8057.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -81536.62 |
PERIMETER_BOT_ZN_3 | 06-FEB-06:01 | 0.00 | 0.00 | 8648.89 | 0.00 | 0.00 | 0.00 | 142.44 | 194.45 | 1011.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4373.07 | 0.00 | -231.39 | -5393.02 |
PERIMETER_BOT_ZN_2 | 22-DEC-06:01 | 0.00 | 0.00 | 6388.34 | 0.00 | 0.00 | 0.00 | 94.07 | 125.31 | 651.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3010.42 | 0.00 | -110.56 | -4138.71 |
PERIMETER_BOT_ZN_1 | 06-FEB-06:01 | 0.00 | 0.00 | 11004.85 | 0.00 | 0.00 | 0.00 | 148.43 | 194.46 | 1011.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4117.10 | 0.00 | -223.75 | -8018.60 |
PERIMETER_BOT_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 06-FEB-04:01 | 0.00 | 0.00 | 128258.50 | 0.00 | 0.00 | 0.00 | 0.00 | 972.26 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -37086.17 | 0.00 | -20034.53 | -82227.03 |
PERIMETER_MID_ZN_2 | 17-JAN-04:01 | 0.00 | 0.00 | 144795.75 | 0.00 | 0.00 | 0.00 | 0.00 | 626.56 | 6519.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -22657.78 | 0.00 | -17867.00 | -111417.30 |
PERIMETER_MID_ZN_1 | 17-JAN-04:01 | 0.00 | 0.00 | 150359.94 | 0.00 | 0.00 | 0.00 | 0.00 | 972.28 | 10117.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -34362.65 | 0.00 | -27614.45 | -99472.25 |
PERIMETER_MID_ZN_4 | 06-FEB-04:01 | 0.00 | 0.00 | 139523.72 | 0.00 | 0.00 | 0.00 | 0.00 | 626.56 | 6519.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -25980.23 | 0.00 | -14238.15 | -106451.62 |
PERIMETER_TOP_ZN_3 | 16-JAN-23:33 | 0.00 | 0.00 | 15928.11 | 0.00 | 0.00 | 0.00 | 0.00 | 97.23 | 758.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2866.74 | 0.00 | -3061.13 | -10856.24 |
PERIMETER_TOP_ZN_2 | 17-JAN-04:11 | 0.00 | 0.00 | 17240.20 | 0.00 | 0.00 | 0.00 | 0.00 | 62.66 | 651.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1988.94 | 0.00 | -1989.90 | -13975.99 |
PERIMETER_TOP_ZN_1 | 17-JAN-04:11 | 0.00 | 0.00 | 18681.99 | 0.00 | 0.00 | 0.00 | 0.00 | 97.23 | 1011.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2931.28 | 0.00 | -2974.69 | -13884.97 |
PERIMETER_TOP_ZN_4 | 17-JAN-04:11 | 0.00 | 0.00 | 18801.09 | 0.00 | 0.00 | 0.00 | 0.00 | 62.66 | 651.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1973.81 | 0.00 | -2030.83 | -15511.07 |
DATACENTER_BOT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 17-JAN-04:52 | 0.00 | 0.00 | 4980.24 | 0.00 | 0.00 | 0.00 | 0.00 | 225.07 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -24691.37 |
DATACENTER_TOP_ZN_6 | 18-JAN-01:30 | 0.00 | 0.00 | 674.30 | 0.00 | 0.00 | 0.00 | 0.00 | 22.51 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2645.42 |
DATACENTER_BASEMENT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 26-DEC-04:01 | 13772.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -802.18 | -12969.94 |
MIDFLOOR_PLENUM | 30-JUL-16:01 | 88092.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6845.68 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -94937.96 |
TOPFLOOR_PLENUM | 06-FEB-06:12 | 24527.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -836.14 | -23691.23 |
Total Facility | 17-JAN-05:01 | -395734.72 | 381841.91 | 674883.04 | -381841.91 | 0.00 | 0.00 | 0.00 | 29009.37 | 268362.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -141400.08 | 0.00 | -150372.60 | -284747.71 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:19
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 12.3197 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 11.1179 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 116.4551 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 103.1891 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 12.1069 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 11.3951 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 6.4654 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 6.4654 | 0.1856 | 1.0000 | Not calculated | 1.2002 | 0.1856 | ||
AIRLOOP DATACENTER BASEMENT | 25.9680 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 25.9684 | 0.0130 | 1.0000 | Not calculated | 0.3384 | 0.0130 | ||
AIRLOOP DATACENTER BOT | 0.5806 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5806 | 0.0269 | 1.0000 | Not calculated | 0.0156 | 0.0269 | ||
AIRLOOP DATACENTER MID | 5.5424 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 5.5424 | 0.0282 | 1.0000 | Not calculated | 0.1563 | 0.0282 | ||
AIRLOOP DATACENTER TOP | 0.5664 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5664 | 0.0276 | 1.0000 | Not calculated | 0.0156 | 0.0276 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 6.1599 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 3.1271 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 58.2275 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 30.4437 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 6.0534 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 3.1651 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 6.4654 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 6.4654 | 1.0000 | 1.0000 | Not calculated | 1.2002 | 0.1856 | ||
AIRLOOP DATACENTER BASEMENT | 25.9680 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 25.9680 | 1.0000 | 1.0000 | Not calculated | 0.3384 | 0.0130 | ||
AIRLOOP DATACENTER BOT | 0.5806 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5806 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0269 | ||
AIRLOOP DATACENTER MID | 5.5424 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 5.5424 | 1.0000 | 1.0000 | Not calculated | 0.1563 | 0.0282 | ||
AIRLOOP DATACENTER TOP | 0.5664 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5664 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0276 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.000000 | 149.6021 | 0.000432 | 2779.43 | 1.2002 | 1.0000 | 1.2002 | 1.000 | 1.2002 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.000000 | 19.4861 | 0.000432 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.1814 | 0.000432 | 783.68 | 0.3384 | 1.0000 | 0.3384 | 1.000 | 0.3384 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
CAV_BAS | 0.000000 | 149.60 | 0.000432 | 2779.4266 | 1.2002 | 1.2002 | 1.2002 |
AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.18 | 0.000432 | 783.6794 | 0.3384 | 0.3384 | 0.3384 |
AIRLOOP DATACENTER BOT | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AIRLOOP DATACENTER MID | 0.000000 | 19.49 | 0.000432 | 362.0274 | 0.1563 | 0.1563 | 0.1563 |
AIRLOOP DATACENTER TOP | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 6.4654 | 6.4654 | 6.4654 | No | 1.2002 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.8225 | 6.8225 | 2.0058 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 64.0124 | 64.0124 | 19.6518 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.3902 | 6.3902 | 2.0193 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1502 | 1.1502 | 0.2519 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2961 | 1.2961 | 0.2592 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3940 | 1.3940 | 0.2788 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6570 | 1.6570 | 0.3314 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 10.8355 | 10.8355 | 2.4705 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 13.5931 | 13.5931 | 2.7186 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 13.3468 | 13.3468 | 2.6694 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 14.6674 | 14.6674 | 2.9335 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2564 | 1.2564 | 0.2538 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3818 | 1.3818 | 0.2764 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4941 | 1.4941 | 0.2988 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5844 | 1.5844 | 0.3169 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5806 | 0.5806 | 0.5806 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.5424 | 5.5424 | 5.5424 | No | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5664 | 0.5664 | 0.5664 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 25.9680 | 25.9680 | 25.9680 | No | 0.3384 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 12.3197 | 11.1179 | 12.3197 | 3.1271 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 116.4551 | 103.1891 | 116.4551 | 30.4437 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 12.1069 | 11.3951 | 12.1069 | 3.1651 | 0.0000 | 1.0000 |
CAV_BAS | 6.4654 | 6.4654 | 6.4654 | 6.4654 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 25.9680 | 25.9684 | 25.9680 | 25.9680 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.5806 | 0.5806 | 0.5806 | 0.5806 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 5.5424 | 5.5424 | 5.5424 | 5.5424 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.5664 | 0.5664 | 0.5664 | 0.5664 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 6.4654 | 6.4654 | 6.4654 | No | 1.2002 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.4112 | 3.4112 | 2.0058 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 32.0062 | 32.0062 | 19.6518 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.1951 | 3.1951 | 2.0193 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5751 | 0.5751 | 0.2519 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6480 | 0.6480 | 0.2592 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6970 | 0.6970 | 0.2788 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8285 | 0.8285 | 0.3314 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.4177 | 5.4177 | 2.4705 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.7965 | 6.7965 | 2.7186 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.6734 | 6.6734 | 2.6694 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 7.3337 | 7.3337 | 2.9335 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6282 | 0.6282 | 0.2538 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6909 | 0.6909 | 0.2764 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7471 | 0.7471 | 0.2988 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7922 | 0.7922 | 0.3169 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5806 | 0.5806 | 0.5806 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.5424 | 5.5424 | 5.5424 | No | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5664 | 0.5664 | 0.5664 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 25.9680 | 25.9680 | 25.9680 | No | 0.3384 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 6.1599 | 3.1271 | 3.1271 | 3.1271 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 58.2275 | 30.4437 | 30.4437 | 30.4437 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 6.0534 | 3.1651 | 3.1651 | 3.1651 | 0.0000 | 1.0000 |
CAV_BAS | 6.4654 | 6.4654 | 6.4654 | 6.4654 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 25.9680 | 25.9680 | 25.9680 | 25.9680 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.5806 | 0.5806 | 0.5806 | 0.5806 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 5.5424 | 5.5424 | 5.5424 | 5.5424 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.5664 | 0.5664 | 0.5664 | 0.5664 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:19
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Albuquerque Intl Sunport NM USA TMY3 WMO#=723650 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 113.98 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 12.33 |
Number of hours cooling loads not met | 1629.00 |
Number of hours not met | 1637.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 729.01 | 744684.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 3998.22 | 419477.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 2740.61 | 261074.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 447.35 | 37611.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5871.99 | 320838.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 59.77 | 3726.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 1848.78 | 113101.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 5.83 | 376.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 2824.89 | 280561.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 586.42 | 66759.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 1150.78 | 81203.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- General | 1154.63 | 75857.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 692.99 | 81629.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 15213.41 | 30030.69 |
Natural Gas | 0.00 | 1421.99 |
Additional | 0.00 | 0.00 |
Total | 15213.41 | 31452.69 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 59.17 |
Space Heating | 0.00 |
Space Cooling | 86.32 |
Fans (All) | 60.99 |
Service Water Heating | 0.00 |
Receptacle Equipment | 328.44 |
Miscellaneous (All) | 648.33 |
Subtotal | 648.33 |
Natural Gas [MJ/m2] | |
Space Heating | 15.74 |
Service Water Heating | 14.96 |
Miscellaneous (All) | 30.70 |
Subtotal | 30.70 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 8.71 |
Space Heating | 2.32 |
Space Cooling | 12.71 |
Fans (All) | 8.98 |
Service Water Heating | 2.20 |
Receptacle Equipment | 48.37 |
Miscellaneous | 16.70 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2393. | 8760. |
LTG_SCH_DATACENTER | 2921. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4487. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 1565. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:19
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8607.67 | 152.33 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8755.00 | 5.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8759.00 | 1.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8754.00 | 6.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8743.67 | 16.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8697.83 | 62.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8713.17 | 46.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8544.33 | 215.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8754.83 | 5.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8680.00 | 80.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8716.50 | 43.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8678.50 | 81.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8740.83 | 19.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8671.50 | 88.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8712.00 | 48.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8673.67 | 86.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 8650.33 | 109.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 8699.83 | 60.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 8717.33 | 42.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 6601.83 | 2069.00 | 89.17 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8641.17 | 118.83 | 0.00 | 0.00 | 0.00 |
Min | 6601.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 2069.00 | 89.17 | 0.00 | 0.00 |
Average | 8610.13 | 145.99 | 3.88 | 0.00 | 0.00 |
Sum | 198033.00 | 3357.83 | 89.17 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 368058.33 | 557.67 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330804.00 | 9.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 2222.33 | 45.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2244.33 | 23.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 2253.00 | 15.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 77856.67 | 24248.83 | 1289.50 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 368058.33 | 24248.83 | 1289.50 | 0.00 | 0.00 |
Average | 79196.25 | 1082.60 | 56.07 | 0.00 | 0.00 |
Sum | 1821513.67 | 24899.83 | 1289.50 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8500.83 | 259.17 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8670.83 | 89.17 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8655.17 | 104.83 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8656.00 | 104.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8648.00 | 112.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8657.33 | 102.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8634.83 | 125.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8471.17 | 288.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8667.67 | 92.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8594.83 | 165.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8624.50 | 135.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8580.33 | 179.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8650.17 | 109.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8595.33 | 164.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8626.50 | 133.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8578.83 | 181.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 8756.00 | 4.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 8759.33 | 0.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 8758.33 | 1.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 7430.67 | 1329.33 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8609.00 | 151.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8682.83 | 77.17 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8526.67 | 233.33 | 0.00 | 0.00 | 0.00 |
Min | 7430.67 | 0.67 | 0.00 | 0.00 | 0.00 |
Max | 8759.33 | 1329.33 | 0.00 | 0.00 | 0.00 |
Average | 8579.79 | 180.21 | 0.00 | 0.00 | 0.00 |
Sum | 197335.17 | 4144.83 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 367763.50 | 852.50 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330640.00 | 173.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330690.00 | 123.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330693.00 | 120.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 2267.50 | 0.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2268.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 2268.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 88216.67 | 15178.33 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 367763.50 | 15178.33 | 0.00 | 0.00 | 0.00 |
Average | 79619.81 | 715.10 | 0.00 | 0.00 | 0.00 |
Sum | 1831255.67 | 16447.33 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:19
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:19
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 4570.43 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 18354.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 38925.00 | 0.00 |
Average | 0.00 | 0.00 | 16367.35 | 0.00 |
Sum | 0.00 | 0.00 | 376449.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018
For: Environment
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Environment
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4B
For: Environment
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NM_ALBUQUERQUE
For: Environment
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 2.601 |
February | 4.285 |
March | 8.765 |
April | 13.905 |
May | 17.822 |
June | 23.208 |
July | 25.626 |
August | 24.075 |
September | 20.490 |
October | 13.707 |
November | 6.961 |
December | 2.072 |
Annual Sum or Average | 13.676 |
Minimum of Months | 2.072 |
Maximum of Months | 25.626 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.490228E+11 | 106203.28 | 02-JAN-04:11 | -1.9 | -3.6 | 0.566371E+10 | 7499.08 | 13-JAN-10:09 | 4.27 | 1.21 |
February | 0.448018E+11 | 103093.82 | 27-FEB-04:02 | 1.20 | -0.5 | 0.513759E+10 | 7499.07 | 01-FEB-10:00 | 1.20 | -0.5 |
March | 0.549036E+11 | 103234.03 | 27-MAR-03:02 | 5.50 | 0.89 | 0.613213E+10 | 7499.00 | 02-MAR-14:09 | 5.50 | 0.89 |
April | 0.538574E+11 | 104528.05 | 10-APR-03:02 | 7.88 | 0.48 | 0.545010E+10 | 7499.01 | 26-APR-13:20 | 24.80 | 9.90 |
May | 0.556707E+11 | 101365.48 | 01-MAY-03:02 | 11.85 | 8.24 | 0.590135E+10 | 7532.48 | 22-MAY-09:50 | 24.13 | 14.54 |
June | 0.576311E+11 | 97807.71 | 19-JUN-03:02 | 14.13 | 6.21 | 0.588226E+10 | 7499.15 | 30-JUN-13:00 | 26.70 | 17.72 |
July | 0.594828E+11 | 89899.36 | 31-JUL-03:02 | 19.40 | 14.43 | 0.547487E+10 | 7499.02 | 28-JUL-09:09 | 19.40 | 14.43 |
August | 0.690432E+11 | 88404.66 | 07-AUG-01:40 | 22.03 | 14.51 | 0.614037E+10 | 7540.96 | 28-AUG-13:09 | 23.30 | 15.11 |
September | 0.594726E+11 | 94864.97 | 25-SEP-04:33 | 11.50 | 9.68 | 0.545421E+10 | 7577.09 | 11-SEP-09:00 | 11.50 | 9.68 |
October | 0.613258E+11 | 105920.20 | 23-OCT-03:02 | 8.22 | 7.00 | 0.567248E+10 | 7521.89 | 10-OCT-09:00 | 8.22 | 7.00 |
November | 0.573924E+11 | 104450.06 | 06-NOV-04:02 | 2.62 | -1.0 | 0.561452E+10 | 7498.90 | 08-NOV-10:30 | 13.60 | 6.17 |
December | 0.548116E+11 | 106949.18 | 11-DEC-04:01 | 2.12 | -2.0 | 0.547071E+10 | 7498.99 | 20-DEC-10:09 | 1.10 | -3.7 |
Annual Sum or Average | 0.677416E+12 | 0.679943E+11 | ||||||||
Minimum of Months | 0.448018E+11 | 88404.66 | -1.9 | -3.6 | 0.513759E+10 | 7498.90 | 1.10 | -3.7 | ||
Maximum of Months | 0.690432E+11 | 106949.18 | 22.03 | 14.51 | 0.614037E+10 | 7577.09 | 26.70 | 17.72 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.382483E+11 | 82822.57 | 03-JAN-05:01 | -0.8 | -2.3 | 0.506547E+10 | 6734.71 | 13-JAN-10:09 | 4.27 | 1.21 |
February | 0.382012E+11 | 83167.14 | 22-FEB-05:01 | 0.60 | 0.08 | 0.460239E+10 | 6734.74 | 15-FEB-10:09 | 0.60 | 0.08 |
March | 0.526339E+11 | 84868.49 | 27-MAR-03:02 | 5.50 | 0.89 | 0.549899E+10 | 6734.69 | 28-MAR-13:09 | 16.42 | 7.54 |
April | 0.606297E+11 | 88575.75 | 24-APR-03:02 | 5.18 | 2.43 | 0.488147E+10 | 6734.77 | 17-APR-13:00 | 5.18 | 2.43 |
May | 0.537857E+11 | 87219.83 | 30-MAY-03:02 | 14.82 | 11.26 | 0.528558E+10 | 6734.99 | 11-MAY-09:09 | 14.82 | 11.26 |
June | 0.613724E+11 | 88647.66 | 05-JUN-03:02 | 15.00 | 13.28 | 0.526812E+10 | 6734.83 | 30-JUN-13:00 | 26.70 | 17.72 |
July | 0.667348E+11 | 78974.88 | 10-JUL-04:03 | 20.00 | 15.66 | 0.489434E+10 | 6734.77 | 18-JUL-09:39 | 25.37 | 17.15 |
August | 0.790634E+11 | 85594.25 | 28-AUG-05:03 | 16.52 | 13.53 | 0.549673E+10 | 6787.78 | 21-AUG-09:00 | 16.52 | 13.53 |
September | 0.540675E+11 | 88399.89 | 18-SEP-03:02 | 14.90 | 11.31 | 0.488440E+10 | 6734.81 | 27-SEP-09:09 | 18.77 | 10.94 |
October | 0.538674E+11 | 88882.08 | 10-OCT-03:02 | 14.82 | 11.26 | 0.507894E+10 | 6734.81 | 24-OCT-13:39 | 10.53 | 5.31 |
November | 0.494320E+11 | 87015.84 | 13-NOV-04:02 | 0.00 | -1.8 | 0.502753E+10 | 6734.69 | 27-NOV-10:09 | 1.28 | -3.1 |
December | 0.470402E+11 | 87879.63 | 26-DEC-04:01 | 0.32 | -0.9 | 0.490119E+10 | 6734.74 | 26-DEC-10:09 | 2.38 | 0.81 |
Annual Sum or Average | 0.655077E+12 | 0.608851E+11 | ||||||||
Minimum of Months | 0.382012E+11 | 78974.88 | -0.8 | -2.3 | 0.460239E+10 | 6734.69 | 0.60 | -3.1 | ||
Maximum of Months | 0.790634E+11 | 88882.08 | 20.00 | 15.66 | 0.549899E+10 | 6787.78 | 26.70 | 17.72 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.263055E+11 | 45541.27 | 05-JAN-06:02 | 1.83 | -0.7 | 0.491469E+10 | 6734.71 | 13-JAN-10:09 | 4.27 | 1.21 |
February | 0.255638E+11 | 72008.22 | 16-FEB-06:03 | 1.70 | -0.5 | 0.451925E+10 | 6734.69 | 01-FEB-10:00 | 1.70 | -0.5 |
March | 0.351519E+11 | 73420.66 | 31-MAR-05:02 | 1.97 | -0.3 | 0.546172E+10 | 6734.68 | 01-MAR-10:09 | 1.97 | -0.3 |
April | 0.380012E+11 | 75816.43 | 28-APR-04:03 | 11.78 | 3.96 | 0.486946E+10 | 6734.72 | 17-APR-13:00 | 11.78 | 3.96 |
May | 0.443808E+11 | 76738.77 | 23-MAY-04:03 | 14.90 | 9.82 | 0.527796E+10 | 6734.96 | 11-MAY-09:09 | 14.90 | 9.82 |
June | 0.487348E+11 | 76733.78 | 06-JUN-04:03 | 12.20 | 10.56 | 0.526511E+10 | 6734.83 | 30-JUN-13:00 | 26.70 | 17.72 |
July | 0.499064E+11 | 79384.50 | 10-JUL-03:02 | 20.00 | 15.66 | 0.489316E+10 | 6734.77 | 18-JUL-09:39 | 25.37 | 17.15 |
August | 0.523216E+11 | 79016.30 | 08-AUG-03:02 | 20.40 | 14.86 | 0.549503E+10 | 6735.81 | 28-AUG-13:50 | 23.30 | 17.44 |
September | 0.446851E+11 | 80393.99 | 05-SEP-03:02 | 17.80 | 15.22 | 0.487847E+10 | 6734.79 | 27-SEP-09:09 | 18.77 | 10.94 |
October | 0.398041E+11 | 76651.80 | 11-OCT-04:03 | 17.30 | 13.69 | 0.505858E+10 | 6734.75 | 24-OCT-13:39 | 10.53 | 5.31 |
November | 0.311826E+11 | 72714.14 | 02-NOV-05:03 | 7.12 | 4.64 | 0.498009E+10 | 6734.63 | 08-NOV-10:30 | 13.60 | 6.17 |
December | 0.263057E+11 | 68986.30 | 01-DEC-06:03 | 3.90 | -0.5 | 0.477307E+10 | 6734.71 | 20-DEC-10:09 | 1.10 | -3.7 |
Annual Sum or Average | 0.462344E+12 | 0.603866E+11 | ||||||||
Minimum of Months | 0.255638E+11 | 45541.27 | 1.70 | -0.7 | 0.451925E+10 | 6734.63 | 1.10 | -3.7 | ||
Maximum of Months | 0.523216E+11 | 80393.99 | 20.40 | 15.66 | 0.549503E+10 | 6735.81 | 26.70 | 17.72 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.188796E+11 | 21827.53 | 05-JAN-17:00 | 13.30 | 5.53 | 0.435151E+10 | 6733.58 | 27-JAN-14:00 | 11.70 | 2.33 |
February | 0.190713E+11 | 33505.17 | 15-FEB-16:40 | 16.87 | 6.07 | 0.412001E+10 | 6734.46 | 15-FEB-10:50 | 16.87 | 6.07 |
March | 0.280483E+11 | 35414.28 | 08-MAR-17:00 | 22.20 | 8.27 | 0.524854E+10 | 6734.58 | 02-MAR-14:09 | 22.20 | 8.27 |
April | 0.345352E+11 | 73646.76 | 28-APR-05:02 | 11.93 | 4.35 | 0.481563E+10 | 6734.75 | 17-APR-13:00 | 11.93 | 4.35 |
May | 0.434793E+11 | 74931.95 | 23-MAY-05:02 | 14.40 | 9.66 | 0.525796E+10 | 6734.90 | 11-MAY-09:09 | 14.40 | 9.66 |
June | 0.522463E+11 | 78173.26 | 26-JUN-03:02 | 18.90 | 11.70 | 0.526242E+10 | 6764.44 | 28-JUN-13:50 | 37.70 | 14.07 |
July | 0.556538E+11 | 82015.33 | 10-JUL-03:02 | 20.00 | 15.66 | 0.489613E+10 | 6734.75 | 18-JUL-09:50 | 25.73 | 17.29 |
August | 0.568258E+11 | 81089.72 | 28-AUG-03:02 | 17.80 | 14.22 | 0.549717E+10 | 6735.87 | 28-AUG-13:50 | 23.30 | 17.44 |
September | 0.444533E+11 | 81259.56 | 05-SEP-03:02 | 17.80 | 15.22 | 0.487219E+10 | 6734.75 | 27-SEP-09:09 | 18.77 | 10.94 |
October | 0.338076E+11 | 75726.46 | 11-OCT-05:02 | 17.80 | 13.88 | 0.495151E+10 | 6734.69 | 24-OCT-13:50 | 8.87 | 4.55 |
November | 0.230810E+11 | 40492.15 | 01-NOV-05:03 | 7.70 | 5.59 | 0.465788E+10 | 6734.60 | 01-NOV-09:09 | 10.47 | 6.68 |
December | 0.183723E+11 | 22513.61 | 01-DEC-17:00 | 12.20 | 4.22 | 0.421167E+10 | 6734.32 | 01-DEC-14:00 | 12.20 | 4.22 |
Annual Sum or Average | 0.428454E+12 | 0.581426E+11 | ||||||||
Minimum of Months | 0.183723E+11 | 21827.53 | 7.70 | 4.22 | 0.412001E+10 | 6733.58 | 8.87 | 2.33 | ||
Maximum of Months | 0.568258E+11 | 82015.33 | 22.20 | 15.66 | 0.549717E+10 | 6764.44 | 37.70 | 17.44 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.255039E+10 | 2766.15 | 02-JAN-14:40 | 14.23 | 5.61 | 0.564511E+09 | 845.58 | 24-JAN-14:00 | 16.10 | 4.97 |
February | 0.264471E+10 | 4051.15 | 15-FEB-15:00 | 17.20 | 6.67 | 0.534315E+09 | 845.61 | 15-FEB-10:09 | 17.20 | 6.67 |
March | 0.438551E+10 | 6090.37 | 27-MAR-14:30 | 18.05 | 6.97 | 0.674188E+09 | 845.63 | 28-MAR-13:09 | 16.42 | 7.54 |
April | 0.674530E+10 | 8008.97 | 14-APR-14:00 | 23.30 | 10.26 | 0.609178E+09 | 845.63 | 17-APR-13:00 | 24.40 | 9.80 |
May | 0.708709E+10 | 12679.88 | 22-MAY-05:02 | 16.78 | 12.20 | 0.662002E+09 | 845.65 | 11-MAY-09:09 | 16.78 | 12.20 |
June | 0.104459E+11 | 16428.66 | 18-JUN-18:11 | 29.43 | 10.52 | 0.662070E+09 | 845.80 | 29-JUN-13:00 | 36.70 | 15.89 |
July | 0.117000E+11 | 16154.24 | 04-JUL-18:31 | 32.77 | 13.53 | 0.615936E+09 | 846.07 | 17-JUL-13:20 | 28.30 | 17.53 |
August | 0.126401E+11 | 16018.39 | 20-AUG-17:41 | 34.40 | 15.36 | 0.690881E+09 | 853.22 | 21-AUG-09:00 | 26.70 | 17.15 |
September | 0.724294E+10 | 12718.76 | 05-SEP-05:03 | 15.92 | 14.88 | 0.612600E+09 | 845.63 | 27-SEP-09:09 | 18.77 | 10.94 |
October | 0.526640E+10 | 12576.67 | 02-OCT-05:02 | 17.12 | 12.75 | 0.626150E+09 | 845.63 | 24-OCT-13:39 | 10.53 | 5.31 |
November | 0.353830E+10 | 4537.00 | 09-NOV-14:10 | 19.22 | 9.76 | 0.608335E+09 | 845.61 | 21-NOV-14:09 | 15.18 | 5.79 |
December | 0.283045E+10 | 3292.69 | 01-DEC-14:10 | 11.78 | 4.41 | 0.559811E+09 | 845.61 | 01-DEC-10:39 | 11.78 | 4.41 |
Annual Sum or Average | 0.770772E+11 | 0.741998E+10 | ||||||||
Minimum of Months | 0.255039E+10 | 2766.15 | 11.78 | 4.41 | 0.534315E+09 | 845.58 | 10.53 | 4.41 | ||
Maximum of Months | 0.126401E+11 | 16428.66 | 34.40 | 15.36 | 0.690881E+09 | 853.22 | 36.70 | 17.53 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.280440E+10 | 5871.16 | 02-JAN-09:25 | 2.75 | -0.6 | 0.371706E+09 | 544.95 | 02-JAN-10:09 | 4.97 | 0.87 |
February | 0.301166E+10 | 8028.06 | 14-FEB-09:10 | 7.25 | 1.90 | 0.350841E+09 | 544.96 | 15-FEB-10:09 | 11.38 | 5.33 |
March | 0.498300E+10 | 13595.67 | 12-MAR-09:13 | 8.50 | 1.40 | 0.435463E+09 | 544.95 | 28-MAR-13:09 | 16.42 | 7.54 |
April | 0.754726E+10 | 17533.25 | 30-APR-08:62 | 15.10 | 5.14 | 0.393148E+09 | 546.15 | 28-APR-09:50 | 15.10 | 5.14 |
May | 0.795274E+10 | 19626.82 | 14-MAY-07:32 | 18.17 | 8.24 | 0.427358E+09 | 545.84 | 15-MAY-09:20 | 20.37 | 9.24 |
June | 0.103206E+11 | 19363.06 | 18-JUN-08:11 | 23.73 | 11.69 | 0.426807E+09 | 546.05 | 19-JUN-09:00 | 21.10 | 8.29 |
July | 0.109109E+11 | 20681.83 | 30-JUL-08:41 | 25.32 | 16.68 | 0.397221E+09 | 546.32 | 06-JUL-09:20 | 25.32 | 16.68 |
August | 0.111300E+11 | 19165.21 | 20-AUG-08:22 | 25.25 | 15.06 | 0.445025E+09 | 552.85 | 21-AUG-09:00 | 26.70 | 17.15 |
September | 0.770095E+10 | 20446.31 | 03-SEP-08:21 | 24.45 | 14.44 | 0.394806E+09 | 545.97 | 11-SEP-09:09 | 21.47 | 13.47 |
October | 0.581461E+10 | 19315.56 | 01-OCT-08:52 | 17.80 | 11.25 | 0.404468E+09 | 544.97 | 18-OCT-09:09 | 12.35 | 5.73 |
November | 0.382456E+10 | 8353.39 | 01-NOV-08:50 | 9.63 | 6.30 | 0.392670E+09 | 544.95 | 27-NOV-10:09 | 1.28 | -3.1 |
December | 0.291511E+10 | 5379.50 | 29-DEC-09:15 | 1.67 | -0.9 | 0.362274E+09 | 544.95 | 26-DEC-10:09 | 1.67 | -0.9 |
Annual Sum or Average | 0.789157E+11 | 0.480179E+10 | ||||||||
Minimum of Months | 0.280440E+10 | 5379.50 | 1.67 | -0.9 | 0.350841E+09 | 544.95 | 1.28 | -3.1 | ||
Maximum of Months | 0.111300E+11 | 20681.83 | 25.32 | 16.68 | 0.445025E+09 | 552.85 | 26.70 | 17.15 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.751057E+10 | 21324.71 | 01-JAN-14:02 | 15.68 | 5.68 | 0.607063E+09 | 861.56 | 23-JAN-14:09 | 14.60 | 4.35 |
February | 0.772385E+10 | 19770.65 | 12-FEB-15:13 | 18.30 | 6.40 | 0.562414E+09 | 890.34 | 14-FEB-14:09 | 20.78 | 7.02 |
March | 0.882940E+10 | 20474.22 | 12-MAR-13:12 | 17.07 | 5.60 | 0.679100E+09 | 847.24 | 20-MAR-13:00 | 18.30 | 8.36 |
April | 0.100269E+11 | 15478.79 | 30-APR-14:42 | 22.12 | 7.83 | 0.609420E+09 | 847.42 | 17-APR-13:00 | 22.12 | 7.83 |
May | 0.829408E+10 | 14345.42 | 22-MAY-05:02 | 16.78 | 12.20 | 0.660863E+09 | 845.67 | 09-MAY-13:20 | 16.78 | 12.20 |
June | 0.105635E+11 | 18904.32 | 18-JUN-16:11 | 32.03 | 11.80 | 0.661474E+09 | 845.67 | 30-JUN-13:00 | 26.70 | 17.72 |
July | 0.127650E+11 | 20459.19 | 30-JUL-15:21 | 33.60 | 17.71 | 0.616001E+09 | 846.43 | 25-JUL-13:39 | 33.60 | 17.71 |
August | 0.158492E+11 | 19996.56 | 20-AUG-14:21 | 34.70 | 16.30 | 0.691418E+09 | 854.64 | 21-AUG-09:00 | 26.70 | 17.15 |
September | 0.126758E+11 | 21950.93 | 03-SEP-12:21 | 30.85 | 16.81 | 0.615367E+09 | 917.49 | 28-SEP-13:39 | 29.63 | 15.09 |
October | 0.125243E+11 | 22001.67 | 01-OCT-14:51 | 28.30 | 12.89 | 0.638234E+09 | 919.23 | 31-OCT-13:30 | 21.40 | 8.63 |
November | 0.100524E+11 | 21548.35 | 23-NOV-12:02 | 12.48 | 4.07 | 0.626884E+09 | 917.37 | 01-NOV-13:09 | 12.48 | 4.07 |
December | 0.918931E+10 | 20730.28 | 24-DEC-13:02 | 10.87 | 2.48 | 0.599136E+09 | 875.50 | 29-DEC-14:09 | 10.68 | 3.53 |
Annual Sum or Average | 0.126004E+12 | 0.756737E+10 | ||||||||
Minimum of Months | 0.751057E+10 | 14345.42 | 10.87 | 2.48 | 0.562414E+09 | 845.67 | 10.68 | 3.53 | ||
Maximum of Months | 0.158492E+11 | 22001.67 | 34.70 | 17.71 | 0.691418E+09 | 919.23 | 33.60 | 17.72 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.425436E+10 | 8371.25 | 26-JAN-16:30 | 10.30 | 1.40 | 0.375333E+09 | 544.93 | 04-JAN-14:50 | 10.30 | 1.40 |
February | 0.507816E+10 | 13271.36 | 12-FEB-15:13 | 18.30 | 6.40 | 0.358845E+09 | 544.95 | 15-FEB-10:09 | 11.38 | 5.33 |
March | 0.801491E+10 | 23522.64 | 12-MAR-15:52 | 19.40 | 6.09 | 0.443127E+09 | 544.96 | 28-MAR-13:09 | 16.42 | 7.54 |
April | 0.124358E+11 | 25298.95 | 16-APR-16:31 | 20.20 | 8.02 | 0.396290E+09 | 544.97 | 17-APR-13:00 | 24.40 | 9.80 |
May | 0.925632E+10 | 26183.51 | 14-MAY-16:11 | 28.30 | 10.92 | 0.427350E+09 | 544.98 | 11-MAY-09:09 | 28.30 | 10.92 |
June | 0.128431E+11 | 27872.09 | 18-JUN-16:51 | 31.70 | 11.85 | 0.427491E+09 | 544.97 | 30-JUN-13:00 | 26.70 | 17.72 |
July | 0.148126E+11 | 28214.36 | 30-JUL-16:01 | 33.62 | 17.43 | 0.397810E+09 | 544.97 | 18-JUL-09:39 | 33.62 | 17.43 |
August | 0.192289E+11 | 26653.64 | 20-AUG-15:41 | 35.00 | 15.92 | 0.446636E+09 | 552.38 | 21-AUG-09:00 | 26.70 | 17.15 |
September | 0.951095E+10 | 25363.07 | 24-SEP-15:41 | 25.60 | 15.63 | 0.395902E+09 | 544.96 | 19-SEP-13:09 | 25.60 | 15.63 |
October | 0.852704E+10 | 25220.44 | 01-OCT-14:51 | 28.30 | 12.89 | 0.408527E+09 | 544.97 | 24-OCT-13:39 | 10.53 | 5.31 |
November | 0.661710E+10 | 21723.04 | 12-NOV-15:12 | 9.40 | 2.60 | 0.404293E+09 | 544.95 | 21-NOV-14:09 | 15.18 | 5.79 |
December | 0.610890E+10 | 15538.83 | 17-DEC-15:32 | 11.70 | 3.53 | 0.392328E+09 | 544.95 | 26-DEC-10:09 | 2.38 | 0.81 |
Annual Sum or Average | 0.116688E+12 | 0.487393E+10 | ||||||||
Minimum of Months | 0.425436E+10 | 8371.25 | 9.40 | 1.40 | 0.358845E+09 | 544.93 | 2.38 | 0.81 | ||
Maximum of Months | 0.192289E+11 | 28214.36 | 35.00 | 17.43 | 0.446636E+09 | 552.38 | 33.62 | 17.72 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.115384E+10 | 2358.00 | 05-JAN-15:20 | 16.10 | 6.84 | 0.485909E+09 | 730.88 | 04-JAN-14:00 | 16.10 | 6.84 |
February | 0.142105E+10 | 2682.77 | 15-FEB-16:00 | 17.20 | 6.50 | 0.459016E+09 | 814.00 | 15-FEB-14:00 | 17.20 | 6.50 |
March | 0.255709E+10 | 3533.00 | 27-MAR-14:50 | 18.22 | 7.02 | 0.613107E+09 | 845.62 | 28-MAR-13:09 | 16.42 | 7.54 |
April | 0.383756E+10 | 6571.37 | 14-APR-14:30 | 23.60 | 10.45 | 0.589724E+09 | 845.63 | 17-APR-13:00 | 24.40 | 9.80 |
May | 0.565566E+10 | 10123.52 | 22-MAY-05:02 | 16.78 | 12.20 | 0.655880E+09 | 845.64 | 11-MAY-09:09 | 16.78 | 12.20 |
June | 0.873540E+10 | 15464.39 | 25-JUN-17:21 | 33.05 | 15.18 | 0.661207E+09 | 845.65 | 30-JUN-13:00 | 26.70 | 17.72 |
July | 0.949948E+10 | 15857.85 | 04-JUL-17:01 | 35.73 | 14.63 | 0.615870E+09 | 845.88 | 31-JUL-13:30 | 30.00 | 18.38 |
August | 0.885408E+10 | 14112.88 | 06-AUG-16:51 | 30.60 | 16.14 | 0.690282E+09 | 845.78 | 28-AUG-13:50 | 23.30 | 17.44 |
September | 0.584089E+10 | 9147.69 | 01-SEP-05:03 | 18.80 | 12.73 | 0.609737E+09 | 845.62 | 27-SEP-09:09 | 18.77 | 10.94 |
October | 0.366481E+10 | 6745.02 | 02-OCT-13:40 | 26.33 | 15.37 | 0.592644E+09 | 845.62 | 04-OCT-13:50 | 25.32 | 13.57 |
November | 0.208555E+10 | 2697.03 | 02-NOV-15:30 | 16.95 | 9.55 | 0.527791E+09 | 845.60 | 09-NOV-14:00 | 18.30 | 9.49 |
December | 0.100180E+10 | 2223.80 | 29-DEC-15:30 | 11.40 | 3.91 | 0.461427E+09 | 775.13 | 01-DEC-14:00 | 11.40 | 3.91 |
Annual Sum or Average | 0.543072E+11 | 0.696259E+10 | ||||||||
Minimum of Months | 0.100180E+10 | 2223.80 | 11.40 | 3.91 | 0.459016E+09 | 730.88 | 11.40 | 3.91 | ||
Maximum of Months | 0.949948E+10 | 15857.85 | 35.73 | 16.14 | 0.690282E+09 | 845.88 | 30.00 | 18.38 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.174629E+10 | 3302.15 | 27-JAN-10:00 | 2.80 | -2.5 | 0.244000E+09 | 521.19 | 27-JAN-09:39 | 2.80 | -2.5 |
February | 0.211793E+10 | 6377.87 | 14-FEB-09:40 | 8.90 | 2.72 | 0.232968E+09 | 521.20 | 09-FEB-11:09 | 8.90 | 2.72 |
March | 0.388368E+10 | 8522.94 | 26-MAR-10:23 | 14.70 | 5.58 | 0.304971E+09 | 521.22 | 17-MAR-15:30 | 14.70 | 5.58 |
April | 0.629556E+10 | 20423.47 | 30-APR-09:42 | 16.52 | 5.13 | 0.287456E+09 | 521.65 | 27-APR-08:00 | 16.52 | 5.13 |
May | 0.760551E+10 | 21443.30 | 29-MAY-08:51 | 18.30 | 12.78 | 0.313097E+09 | 521.42 | 19-MAY-08:50 | 18.30 | 12.78 |
June | 0.100394E+11 | 22134.39 | 18-JUN-08:21 | 24.20 | 11.76 | 0.313515E+09 | 529.21 | 29-JUN-07:19 | 27.93 | 17.35 |
July | 0.104651E+11 | 22618.84 | 04-JUL-08:21 | 25.55 | 18.35 | 0.293467E+09 | 528.27 | 05-JUL-07:19 | 24.80 | 15.16 |
August | 0.101428E+11 | 21578.73 | 06-AUG-08:51 | 25.00 | 15.05 | 0.327375E+09 | 522.89 | 02-AUG-10:30 | 25.00 | 15.05 |
September | 0.732968E+10 | 21544.40 | 03-SEP-09:01 | 25.97 | 15.10 | 0.289481E+09 | 521.45 | 01-SEP-08:50 | 25.97 | 15.10 |
October | 0.499648E+10 | 12859.06 | 01-OCT-09:02 | 18.35 | 11.47 | 0.289689E+09 | 521.22 | 02-OCT-12:20 | 25.20 | 14.93 |
November | 0.280138E+10 | 7334.40 | 01-NOV-09:00 | 10.00 | 6.46 | 0.266613E+09 | 521.19 | 09-NOV-08:20 | 13.33 | 8.67 |
December | 0.171510E+10 | 3052.36 | 29-DEC-09:30 | 1.95 | -0.8 | 0.232882E+09 | 521.19 | 29-DEC-09:30 | 1.95 | -0.8 |
Annual Sum or Average | 0.691389E+11 | 0.339551E+10 | ||||||||
Minimum of Months | 0.171510E+10 | 3052.36 | 1.95 | -2.5 | 0.232882E+09 | 521.19 | 1.95 | -2.5 | ||
Maximum of Months | 0.104651E+11 | 22618.84 | 25.97 | 18.35 | 0.327375E+09 | 529.21 | 27.93 | 17.35 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.700429E+10 | 19417.63 | 08-JAN-12:43 | 11.42 | 3.94 | 0.594288E+09 | 908.54 | 26-JAN-14:20 | 10.20 | 1.54 |
February | 0.707750E+10 | 20141.51 | 19-FEB-12:32 | 14.27 | 5.93 | 0.551315E+09 | 936.09 | 14-FEB-14:20 | 14.27 | 5.93 |
March | 0.745301E+10 | 19299.65 | 26-MAR-13:02 | 18.17 | 6.87 | 0.662951E+09 | 849.90 | 13-MAR-13:50 | 18.17 | 6.87 |
April | 0.747792E+10 | 18267.11 | 30-APR-13:43 | 21.52 | 7.52 | 0.601317E+09 | 846.76 | 17-APR-13:00 | 21.52 | 7.52 |
May | 0.717098E+10 | 13343.03 | 22-MAY-05:02 | 16.78 | 12.20 | 0.656589E+09 | 845.67 | 09-MAY-13:20 | 16.78 | 12.20 |
June | 0.892776E+10 | 18708.52 | 25-JUN-16:41 | 33.68 | 14.48 | 0.660132E+09 | 845.67 | 30-JUN-13:39 | 29.47 | 17.83 |
July | 0.105779E+11 | 19715.18 | 30-JUL-14:41 | 33.12 | 17.91 | 0.616104E+09 | 845.94 | 25-JUL-13:39 | 33.12 | 17.91 |
August | 0.123693E+11 | 19369.41 | 06-AUG-11:32 | 28.33 | 15.73 | 0.691328E+09 | 858.17 | 31-AUG-13:09 | 29.50 | 15.73 |
September | 0.120320E+11 | 21458.02 | 03-SEP-12:21 | 30.85 | 16.81 | 0.617046E+09 | 970.23 | 28-SEP-13:39 | 29.63 | 15.09 |
October | 0.117553E+11 | 20760.45 | 01-OCT-13:02 | 27.38 | 14.05 | 0.638263E+09 | 966.47 | 31-OCT-13:00 | 22.80 | 8.86 |
November | 0.907293E+10 | 19940.05 | 05-NOV-12:32 | 11.13 | 2.84 | 0.621236E+09 | 959.13 | 01-NOV-13:30 | 11.13 | 2.84 |
December | 0.785817E+10 | 19934.87 | 31-DEC-14:12 | 10.37 | 1.81 | 0.585195E+09 | 903.04 | 29-DEC-14:09 | 10.37 | 1.81 |
Annual Sum or Average | 0.108777E+12 | 0.749576E+10 | ||||||||
Minimum of Months | 0.700429E+10 | 13343.03 | 10.37 | 1.81 | 0.551315E+09 | 845.67 | 10.20 | 1.54 | ||
Maximum of Months | 0.123693E+11 | 21458.02 | 33.68 | 17.91 | 0.691328E+09 | 970.23 | 33.12 | 17.91 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.215810E+10 | 6216.48 | 26-JAN-16:30 | 10.30 | 1.40 | 0.331817E+09 | 544.18 | 05-JAN-14:00 | 10.30 | 1.40 |
February | 0.268034E+10 | 10010.55 | 15-FEB-16:30 | 16.95 | 6.18 | 0.312421E+09 | 544.92 | 09-FEB-14:00 | 16.95 | 6.18 |
March | 0.417547E+10 | 10948.99 | 12-MAR-16:42 | 20.40 | 6.33 | 0.397006E+09 | 544.94 | 17-MAR-13:00 | 16.10 | 5.42 |
April | 0.595535E+10 | 20757.37 | 30-APR-15:42 | 21.78 | 7.81 | 0.380231E+09 | 544.96 | 17-APR-13:00 | 21.78 | 7.81 |
May | 0.710177E+10 | 22094.91 | 14-MAY-16:21 | 28.30 | 10.87 | 0.419744E+09 | 544.97 | 16-MAY-13:00 | 25.00 | 9.24 |
June | 0.945045E+10 | 25054.68 | 25-JUN-16:41 | 33.68 | 14.48 | 0.424935E+09 | 544.97 | 30-JUN-13:50 | 28.08 | 17.83 |
July | 0.998059E+10 | 25623.11 | 04-JUL-17:01 | 35.73 | 14.63 | 0.397042E+09 | 544.96 | 18-JUL-09:39 | 25.37 | 17.15 |
August | 0.100141E+11 | 22425.90 | 20-AUG-16:01 | 34.90 | 15.92 | 0.445221E+09 | 545.07 | 28-AUG-13:50 | 23.30 | 17.44 |
September | 0.731286E+10 | 22470.24 | 04-SEP-17:01 | 26.52 | 16.05 | 0.392729E+09 | 544.97 | 18-SEP-13:00 | 25.00 | 14.88 |
October | 0.550546E+10 | 16442.05 | 01-OCT-15:42 | 28.80 | 13.20 | 0.383152E+09 | 544.96 | 04-OCT-13:50 | 25.32 | 13.57 |
November | 0.330353E+10 | 8723.68 | 02-NOV-16:00 | 16.70 | 9.78 | 0.354864E+09 | 544.93 | 03-NOV-13:50 | 12.12 | 2.35 |
December | 0.213121E+10 | 5309.17 | 29-DEC-16:00 | 11.70 | 3.88 | 0.320729E+09 | 543.94 | 29-DEC-14:00 | 11.70 | 3.88 |
Annual Sum or Average | 0.697693E+11 | 0.455989E+10 | ||||||||
Minimum of Months | 0.213121E+10 | 5309.17 | 10.30 | 1.40 | 0.312421E+09 | 543.94 | 10.30 | 1.40 | ||
Maximum of Months | 0.100141E+11 | 25623.11 | 35.73 | 16.05 | 0.445221E+09 | 545.07 | 28.08 | 17.83 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.475314E+09 | 1980.75 | 05-JAN-14:30 | 16.10 | 6.84 | 0.469686E+09 | 685.14 | 24-JAN-14:00 | 16.10 | 4.97 |
February | 0.753354E+09 | 2662.28 | 15-FEB-15:00 | 17.20 | 6.67 | 0.436418E+09 | 786.63 | 15-FEB-14:00 | 17.20 | 6.67 |
March | 0.194697E+10 | 2714.50 | 27-MAR-16:00 | 18.90 | 7.43 | 0.573944E+09 | 845.60 | 17-MAR-13:00 | 18.90 | 7.43 |
April | 0.347108E+10 | 6966.38 | 28-APR-15:30 | 25.00 | 10.42 | 0.569369E+09 | 845.63 | 17-APR-13:00 | 25.00 | 10.42 |
May | 0.553166E+10 | 8183.57 | 31-MAY-15:30 | 27.75 | 11.03 | 0.646457E+09 | 845.64 | 31-MAY-13:20 | 27.75 | 11.03 |
June | 0.927412E+10 | 18606.83 | 25-JUN-17:21 | 33.05 | 15.18 | 0.659516E+09 | 858.95 | 28-JUN-13:50 | 37.70 | 14.07 |
July | 0.103797E+11 | 18851.35 | 04-JUL-16:21 | 35.85 | 14.32 | 0.615970E+09 | 845.64 | 18-JUL-09:50 | 25.73 | 17.29 |
August | 0.947179E+10 | 17396.61 | 06-AUG-16:51 | 30.60 | 16.14 | 0.689989E+09 | 845.79 | 28-AUG-13:50 | 23.30 | 17.44 |
September | 0.582013E+10 | 8310.42 | 03-SEP-14:32 | 31.33 | 16.36 | 0.605660E+09 | 845.65 | 13-SEP-13:30 | 26.40 | 14.44 |
October | 0.309849E+10 | 7204.18 | 02-OCT-13:40 | 26.33 | 15.37 | 0.567506E+09 | 845.63 | 02-OCT-13:20 | 26.33 | 15.37 |
November | 0.124202E+10 | 2669.90 | 01-NOV-15:00 | 12.80 | 7.53 | 0.493493E+09 | 806.93 | 09-NOV-14:00 | 18.30 | 9.49 |
December | 0.295950E+09 | 1963.61 | 29-DEC-14:10 | 10.68 | 3.53 | 0.449914E+09 | 710.54 | 01-DEC-14:00 | 10.68 | 3.53 |
Annual Sum or Average | 0.517606E+11 | 0.677792E+10 | ||||||||
Minimum of Months | 0.295950E+09 | 1963.61 | 10.68 | 3.53 | 0.436418E+09 | 685.14 | 10.68 | 3.53 | ||
Maximum of Months | 0.103797E+11 | 18851.35 | 35.85 | 16.36 | 0.689989E+09 | 858.95 | 37.70 | 17.44 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.105804E+10 | 2341.38 | 26-JAN-14:10 | 10.10 | 1.50 | 0.314731E+09 | 507.01 | 27-JAN-10:30 | 4.45 | -1.6 |
February | 0.146986E+10 | 4418.44 | 14-FEB-10:10 | 10.83 | 3.59 | 0.302446E+09 | 544.94 | 10-FEB-10:09 | 10.83 | 3.59 |
March | 0.313426E+10 | 6461.58 | 08-MAR-09:50 | 13.43 | 6.40 | 0.405195E+09 | 544.95 | 10-MAR-10:09 | 6.97 | 1.35 |
April | 0.587499E+10 | 20428.88 | 30-APR-09:12 | 15.97 | 4.95 | 0.389406E+09 | 545.77 | 28-APR-09:00 | 15.97 | 4.95 |
May | 0.753435E+10 | 18690.99 | 29-MAY-09:02 | 18.68 | 12.90 | 0.425072E+09 | 545.77 | 19-MAY-09:00 | 18.68 | 12.90 |
June | 0.105954E+11 | 21870.02 | 25-JUN-08:61 | 24.37 | 15.49 | 0.426375E+09 | 547.98 | 28-JUN-13:50 | 37.70 | 14.07 |
July | 0.112966E+11 | 22978.03 | 04-JUL-08:21 | 25.55 | 18.35 | 0.397752E+09 | 546.02 | 06-JUL-09:39 | 28.67 | 16.27 |
August | 0.108377E+11 | 21977.13 | 06-AUG-08:51 | 25.00 | 15.05 | 0.445407E+09 | 545.77 | 16-AUG-09:00 | 27.20 | 18.11 |
September | 0.742776E+10 | 20267.72 | 03-SEP-09:12 | 26.33 | 15.30 | 0.392637E+09 | 544.99 | 13-SEP-13:30 | 26.40 | 14.44 |
October | 0.442460E+10 | 19805.50 | 01-OCT-09:22 | 19.45 | 11.90 | 0.388542E+09 | 544.97 | 02-OCT-13:20 | 25.97 | 15.23 |
November | 0.200661E+10 | 6181.79 | 01-NOV-09:10 | 10.47 | 6.68 | 0.344807E+09 | 544.95 | 01-NOV-09:09 | 10.47 | 6.68 |
December | 0.989476E+09 | 2375.44 | 29-DEC-13:40 | 10.03 | 3.18 | 0.297682E+09 | 500.89 | 29-DEC-10:09 | 10.03 | 3.18 |
Annual Sum or Average | 0.666497E+11 | 0.453005E+10 | ||||||||
Minimum of Months | 0.989476E+09 | 2341.38 | 10.03 | 1.50 | 0.297682E+09 | 500.89 | 4.45 | -1.6 | ||
Maximum of Months | 0.112966E+11 | 22978.03 | 26.33 | 18.35 | 0.445407E+09 | 547.98 | 37.70 | 18.11 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.526278E+10 | 16645.34 | 15-JAN-13:52 | 11.70 | 3.37 | 0.569806E+09 | 845.62 | 19-JAN-14:00 | 5.00 | 1.80 |
February | 0.562826E+10 | 20909.08 | 12-FEB-14:12 | 17.57 | 5.95 | 0.526948E+09 | 878.97 | 14-FEB-14:30 | 21.15 | 7.16 |
March | 0.621520E+10 | 21374.54 | 12-MAR-13:52 | 17.80 | 6.05 | 0.635722E+09 | 846.35 | 16-MAR-13:00 | 20.60 | 8.86 |
April | 0.699637E+10 | 18178.98 | 30-APR-14:31 | 22.03 | 7.78 | 0.587030E+09 | 846.90 | 27-APR-13:00 | 22.03 | 7.78 |
May | 0.714343E+10 | 11350.26 | 19-MAY-13:10 | 28.90 | 12.73 | 0.647025E+09 | 845.67 | 08-MAY-13:30 | 28.90 | 12.73 |
June | 0.956030E+10 | 21775.28 | 25-JUN-16:41 | 33.68 | 14.48 | 0.657356E+09 | 856.59 | 28-JUN-13:50 | 37.70 | 14.07 |
July | 0.115763E+11 | 22482.64 | 04-JUL-15:41 | 35.60 | 13.89 | 0.615910E+09 | 845.66 | 18-JUL-09:50 | 25.73 | 17.29 |
August | 0.132057E+11 | 21816.89 | 06-AUG-11:32 | 28.33 | 15.73 | 0.690748E+09 | 846.69 | 25-AUG-13:00 | 28.90 | 17.11 |
September | 0.121749E+11 | 22879.61 | 03-SEP-13:12 | 31.67 | 16.75 | 0.612331E+09 | 939.30 | 28-SEP-13:39 | 29.63 | 15.09 |
October | 0.109475E+11 | 24369.95 | 01-OCT-11:21 | 24.75 | 14.09 | 0.618577E+09 | 932.32 | 05-OCT-13:50 | 26.52 | 12.57 |
November | 0.726592E+10 | 22063.49 | 19-NOV-13:42 | 12.93 | 3.20 | 0.598180E+09 | 905.86 | 01-NOV-13:30 | 12.93 | 3.20 |
December | 0.591152E+10 | 21581.76 | 31-DEC-14:01 | 10.18 | 1.71 | 0.559743E+09 | 845.63 | 20-DEC-14:00 | 10.18 | 1.71 |
Annual Sum or Average | 0.101888E+12 | 0.731938E+10 | ||||||||
Minimum of Months | 0.526278E+10 | 11350.26 | 10.18 | 1.71 | 0.526948E+09 | 845.62 | 5.00 | 1.71 | ||
Maximum of Months | 0.132057E+11 | 24369.95 | 35.60 | 16.75 | 0.690748E+09 | 939.30 | 37.70 | 17.29 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.139523E+10 | 5415.54 | 26-JAN-16:30 | 10.30 | 1.40 | 0.322413E+09 | 532.82 | 05-JAN-14:00 | 10.30 | 1.40 |
February | 0.201940E+10 | 9749.21 | 15-FEB-16:30 | 16.95 | 6.18 | 0.301314E+09 | 544.91 | 15-FEB-14:00 | 16.95 | 6.18 |
March | 0.356489E+10 | 11932.70 | 12-MAR-16:32 | 20.20 | 6.28 | 0.376590E+09 | 544.93 | 09-MAR-14:09 | 20.20 | 6.28 |
April | 0.566250E+10 | 23384.35 | 16-APR-17:01 | 20.40 | 8.05 | 0.367961E+09 | 544.97 | 17-APR-13:00 | 24.40 | 9.80 |
May | 0.711229E+10 | 23078.45 | 14-MAY-16:32 | 28.30 | 10.81 | 0.411822E+09 | 544.97 | 08-MAY-13:30 | 28.30 | 10.81 |
June | 0.994200E+10 | 27713.30 | 25-JUN-16:41 | 33.68 | 14.48 | 0.422835E+09 | 560.56 | 27-JUN-15:00 | 37.80 | 15.32 |
July | 0.106964E+11 | 27998.98 | 04-JUL-16:21 | 35.85 | 14.32 | 0.396749E+09 | 544.96 | 18-JUL-09:50 | 25.73 | 17.29 |
August | 0.105796E+11 | 24264.12 | 20-AUG-16:01 | 34.90 | 15.92 | 0.444599E+09 | 545.07 | 28-AUG-13:50 | 23.30 | 17.44 |
September | 0.739421E+10 | 23259.44 | 10-SEP-15:22 | 27.25 | 14.47 | 0.388944E+09 | 544.99 | 13-SEP-13:30 | 26.40 | 14.44 |
October | 0.503427E+10 | 23912.24 | 01-OCT-15:21 | 28.60 | 13.08 | 0.370167E+09 | 544.96 | 02-OCT-13:20 | 25.97 | 15.23 |
November | 0.257371E+10 | 8219.36 | 02-NOV-16:00 | 16.70 | 9.78 | 0.337764E+09 | 544.93 | 14-NOV-14:00 | 12.20 | 4.12 |
December | 0.131278E+10 | 4568.82 | 29-DEC-16:00 | 11.70 | 3.88 | 0.312374E+09 | 531.19 | 20-DEC-14:00 | 11.70 | 3.88 |
Annual Sum or Average | 0.672872E+11 | 0.445353E+10 | ||||||||
Minimum of Months | 0.131278E+10 | 4568.82 | 10.30 | 1.40 | 0.301314E+09 | 531.19 | 10.30 | 1.40 | ||
Maximum of Months | 0.106964E+11 | 27998.98 | 35.85 | 15.92 | 0.444599E+09 | 560.56 | 37.80 | 17.44 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.113643E+10 | 4177.83 | 02-JAN-06:10 | -4.2 | -5.0 | 0.00 | 0.00 | 01-JAN-00:10 | -4.2 | -5.0 |
February | 0.151109E+10 | 3858.44 | 15-FEB-16:40 | 16.87 | 6.07 | 0.00 | 0.00 | 01-FEB-00:10 | 16.87 | 6.07 |
March | 0.349451E+10 | 5448.19 | 27-MAR-05:15 | 5.40 | 0.66 | 0.00 | 0.00 | 01-MAR-00:10 | 5.40 | 0.66 |
April | 0.582100E+10 | 6709.73 | 17-APR-05:15 | 9.43 | 2.64 | 0.00 | 0.00 | 01-APR-00:10 | 9.43 | 2.64 |
May | 0.623855E+10 | 9643.38 | 30-MAY-05:15 | 14.43 | 10.90 | 0.00 | 0.00 | 01-MAY-00:10 | 14.43 | 10.90 |
June | 0.876798E+10 | 9778.67 | 05-JUN-05:15 | 15.00 | 12.60 | 0.00 | 0.00 | 01-JUN-00:10 | 15.00 | 12.60 |
July | 0.102024E+11 | 12825.33 | 05-JUL-05:15 | 22.20 | 13.64 | 0.00 | 0.00 | 01-JUL-00:10 | 22.20 | 13.64 |
August | 0.117174E+11 | 14072.21 | 07-AUG-05:15 | 18.90 | 13.62 | 0.00 | 0.00 | 01-AUG-00:10 | 18.90 | 13.62 |
September | 0.738413E+10 | 10064.42 | 05-SEP-05:25 | 15.55 | 14.64 | 0.00 | 0.00 | 01-SEP-00:10 | 15.55 | 14.64 |
October | 0.549890E+10 | 11398.37 | 02-OCT-05:15 | 17.03 | 12.72 | 0.00 | 0.00 | 01-OCT-00:10 | 17.03 | 12.72 |
November | 0.320092E+10 | 5100.28 | 13-NOV-06:07 | 0.10 | -1.5 | 0.00 | 0.00 | 01-NOV-00:10 | 0.10 | -1.5 |
December | 0.176279E+10 | 3645.11 | 02-DEC-06:08 | 1.70 | -3.0 | 0.00 | 0.00 | 01-DEC-00:10 | 1.70 | -3.0 |
Annual Sum or Average | 0.667361E+11 | 0.00 | ||||||||
Minimum of Months | 0.113643E+10 | 3645.11 | -4.2 | -5.0 | 0.00 | 0.00 | -4.2 | -5.0 | ||
Maximum of Months | 0.117174E+11 | 14072.21 | 22.20 | 14.64 | 0.00 | 0.00 | 22.20 | 14.64 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.330740E+09 | 6537.91 | 17-JAN-04:01 | -3.3 | -5.0 | 0.00 | 0.00 | 01-JAN-00:10 | -3.3 | -5.0 |
February | 0.461057E+09 | 5874.53 | 06-FEB-04:01 | -4.4 | -7.0 | 0.00 | 0.00 | 01-FEB-00:10 | -4.4 | -7.0 |
March | 0.108876E+10 | 4756.56 | 04-MAR-06:01 | -1.7 | -4.4 | 0.00 | 0.00 | 01-MAR-00:10 | -1.7 | -4.4 |
April | 0.288411E+10 | 4851.14 | 28-APR-15:00 | 25.00 | 10.42 | 0.00 | 0.00 | 01-APR-00:10 | 25.00 | 10.42 |
May | 0.445989E+10 | 6050.98 | 22-MAY-05:15 | 16.87 | 12.18 | 0.00 | 0.00 | 01-MAY-00:10 | 16.87 | 12.18 |
June | 0.689475E+10 | 7490.02 | 26-JUN-15:30 | 35.55 | 15.63 | 0.00 | 0.00 | 01-JUN-00:10 | 35.55 | 15.63 |
July | 0.807362E+10 | 8362.43 | 05-JUL-05:15 | 22.20 | 13.64 | 0.00 | 0.00 | 01-JUL-00:10 | 22.20 | 13.64 |
August | 0.807984E+10 | 7924.64 | 07-AUG-15:40 | 33.13 | 16.01 | 0.00 | 0.00 | 01-AUG-00:10 | 33.13 | 16.01 |
September | 0.563694E+10 | 7094.54 | 05-SEP-15:00 | 24.40 | 17.62 | 0.00 | 0.00 | 01-SEP-00:10 | 24.40 | 17.62 |
October | 0.326760E+10 | 6150.01 | 02-OCT-16:00 | 23.90 | 14.76 | 0.00 | 0.00 | 01-OCT-00:10 | 23.90 | 14.76 |
November | 0.998795E+09 | 5486.86 | 25-NOV-06:01 | 1.10 | -1.4 | 0.00 | 0.00 | 01-NOV-00:10 | 1.10 | -1.4 |
December | 0.322059E+09 | 5278.31 | 23-DEC-05:01 | -5.1 | -7.6 | 0.00 | 0.00 | 01-DEC-00:10 | -5.1 | -7.6 |
Annual Sum or Average | 0.424982E+11 | 0.00 | ||||||||
Minimum of Months | 0.322059E+09 | 4756.56 | -5.1 | -7.6 | 0.00 | 0.00 | -5.1 | -7.6 | ||
Maximum of Months | 0.807984E+10 | 8362.43 | 35.55 | 17.62 | 0.00 | 0.00 | 35.55 | 17.62 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.149307E+09 | 1996.16 | 01-JAN-14:38 | 15.93 | 5.77 | 0.00 | 0.00 | 01-JAN-00:10 | 15.93 | 5.77 |
February | 0.687642E+09 | 6376.84 | 15-FEB-15:20 | 17.20 | 6.61 | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 | 6.61 |
March | 0.232581E+10 | 9183.30 | 08-MAR-15:00 | 22.20 | 9.10 | 0.00 | 0.00 | 01-MAR-00:10 | 22.20 | 9.10 |
April | 0.609087E+10 | 15545.01 | 28-APR-14:20 | 24.60 | 10.33 | 0.00 | 0.00 | 01-APR-00:10 | 24.60 | 10.33 |
May | 0.881058E+10 | 18059.25 | 30-MAY-14:30 | 27.20 | 12.25 | 0.00 | 0.00 | 01-MAY-00:10 | 27.20 | 12.25 |
June | 0.139804E+11 | 23285.87 | 28-JUN-13:30 | 37.50 | 13.98 | 0.00 | 0.00 | 01-JUN-00:10 | 37.50 | 13.98 |
July | 0.160535E+11 | 22359.80 | 21-JUL-14:00 | 37.80 | 15.31 | 0.00 | 0.00 | 01-JUL-00:10 | 37.80 | 15.31 |
August | 0.152319E+11 | 21046.79 | 07-AUG-14:20 | 33.13 | 15.81 | 0.00 | 0.00 | 01-AUG-00:10 | 33.13 | 15.81 |
September | 0.960793E+10 | 16408.58 | 01-SEP-15:00 | 28.90 | 16.64 | 0.00 | 0.00 | 01-SEP-00:10 | 28.90 | 16.64 |
October | 0.454154E+10 | 12747.82 | 02-OCT-13:30 | 26.15 | 15.30 | 0.00 | 0.00 | 01-OCT-00:10 | 26.15 | 15.30 |
November | 0.778767E+09 | 5500.79 | 02-NOV-14:40 | 16.67 | 9.19 | 0.00 | 0.00 | 01-NOV-00:10 | 16.67 | 9.19 |
December | 57239673.05 | 2289.00 | 31-DEC-15:25 | 10.55 | 1.85 | 0.00 | 0.00 | 01-DEC-00:10 | 10.55 | 1.85 |
Annual Sum or Average | 0.783155E+11 | 0.00 | ||||||||
Minimum of Months | 57239673.05 | 1996.16 | 10.55 | 1.85 | 0.00 | 0.00 | 10.55 | 1.85 | ||
Maximum of Months | 0.160535E+11 | 23285.87 | 37.80 | 16.64 | 0.00 | 0.00 | 37.80 | 16.64 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.336334E+10 | 2300.64 | 26-JAN-17:00 | 10.00 | 1.21 | 95230027.76 | 126.82 | 20-JAN-14:00 | 10.00 | 1.21 |
February | 0.801116E+10 | 4333.04 | 15-FEB-17:00 | 16.70 | 5.85 | 86396716.66 | 126.83 | 17-FEB-10:00 | 7.20 | 4.72 |
March | 0.143664E+11 | 7113.90 | 31-MAR-24:00 | 6.90 | 3.36 | 0.103236E+09 | 126.83 | 21-MAR-13:30 | 6.90 | 3.36 |
April | 0.191614E+11 | 8155.20 | 15-APR-18:00 | 7.20 | 4.16 | 91744178.89 | 128.57 | 13-APR-13:00 | 7.20 | 4.16 |
May | 0.452963E+10 | 3508.54 | 31-MAY-24:00 | 18.60 | 7.93 | 99235494.44 | 126.85 | 24-MAY-13:30 | 18.60 | 7.93 |
June | 0.943707E+10 | 5342.32 | 30-JUN-24:00 | 22.10 | 13.89 | 98962056.80 | 126.86 | 08-JUN-13:00 | 22.10 | 13.89 |
July | 0.148262E+11 | 7248.62 | 31-JUL-23:53 | 21.00 | 17.53 | 91885852.16 | 126.84 | 17-JUL-09:09 | 21.00 | 17.53 |
August | 0.202607E+11 | 8014.12 | 27-AUG-18:52 | 23.30 | 14.85 | 0.105320E+09 | 137.90 | 17-AUG-13:00 | 23.30 | 14.85 |
September | 0.453063E+10 | 3512.39 | 30-SEP-24:00 | 17.40 | 10.77 | 91613309.86 | 126.86 | 07-SEP-13:09 | 17.40 | 10.77 |
October | 0.953837E+10 | 5309.33 | 31-OCT-24:00 | 13.00 | 4.55 | 95233229.29 | 126.85 | 11-OCT-09:50 | 13.00 | 4.55 |
November | 0.138567E+11 | 6200.52 | 06-NOV-16:40 | 14.40 | 4.29 | 94300839.31 | 126.83 | 02-NOV-09:00 | 14.40 | 4.29 |
December | 0.192623E+11 | 8017.19 | 26-DEC-16:30 | 8.05 | 3.32 | 91880719.76 | 126.82 | 08-DEC-14:09 | 8.05 | 3.32 |
Annual Sum or Average | 0.141144E+12 | 0.114504E+10 | ||||||||
Minimum of Months | 0.336334E+10 | 2300.64 | 6.90 | 1.21 | 86396716.66 | 126.82 | 6.90 | 1.21 | ||
Maximum of Months | 0.202607E+11 | 8155.20 | 23.30 | 17.53 | 0.105320E+09 | 137.90 | 23.30 | 17.53 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.152361E+10 | 2076.52 | 26-JAN-17:00 | 10.00 | 1.21 | 95229211.46 | 126.82 | 20-JAN-14:00 | 10.00 | 1.21 |
February | 0.629352E+10 | 4059.68 | 15-FEB-17:00 | 16.70 | 5.85 | 86396719.40 | 126.83 | 17-FEB-10:00 | 7.20 | 4.72 |
March | 0.127037E+11 | 6539.49 | 31-MAR-23:50 | 6.80 | 3.32 | 0.103236E+09 | 126.83 | 15-MAR-09:00 | 6.80 | 3.32 |
April | 0.177093E+11 | 7645.48 | 24-APR-18:00 | 20.60 | 8.33 | 91648980.74 | 126.82 | 20-APR-09:39 | 20.60 | 8.33 |
May | 0.395531E+10 | 3318.92 | 31-MAY-24:00 | 18.60 | 7.93 | 99235136.86 | 126.84 | 24-MAY-09:00 | 18.60 | 7.93 |
June | 0.886555E+10 | 5174.67 | 30-JUN-24:00 | 22.10 | 13.89 | 98961736.21 | 126.85 | 08-JUN-13:00 | 22.10 | 13.89 |
July | 0.141205E+11 | 6992.63 | 31-JUL-23:57 | 21.00 | 17.53 | 91886227.51 | 126.84 | 17-JUL-09:09 | 21.00 | 17.53 |
August | 0.188645E+11 | 7449.35 | 23-AUG-18:00 | 23.90 | 15.31 | 0.104248E+09 | 134.16 | 17-AUG-13:00 | 23.90 | 15.31 |
September | 0.402816E+10 | 3318.24 | 30-SEP-24:00 | 17.40 | 10.77 | 91612247.61 | 126.85 | 06-SEP-13:00 | 17.40 | 10.77 |
October | 0.841243E+10 | 4842.77 | 31-OCT-24:00 | 13.00 | 4.55 | 95232999.81 | 126.84 | 11-OCT-09:00 | 13.00 | 4.55 |
November | 0.119400E+11 | 5751.42 | 02-NOV-16:40 | 16.30 | 9.65 | 94300797.06 | 126.83 | 02-NOV-09:00 | 16.30 | 9.65 |
December | 0.163605E+11 | 7382.90 | 29-DEC-16:50 | 10.28 | 3.14 | 91880788.95 | 126.82 | 08-DEC-14:09 | 10.28 | 3.14 |
Annual Sum or Average | 0.124777E+12 | 0.114387E+10 | ||||||||
Minimum of Months | 0.152361E+10 | 2076.52 | 6.80 | 1.21 | 86396719.40 | 126.82 | 6.80 | 1.21 | ||
Maximum of Months | 0.188645E+11 | 7645.48 | 23.90 | 17.53 | 0.104248E+09 | 134.16 | 23.90 | 17.53 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.610961E+09 | 1969.21 | 26-JAN-17:00 | 10.00 | 1.21 | 94103796.61 | 129.17 | 09-JAN-10:00 | 10.00 | 1.21 |
February | 0.478168E+10 | 4068.82 | 15-FEB-17:00 | 16.70 | 5.85 | 86396719.15 | 126.83 | 17-FEB-10:00 | 7.20 | 4.72 |
March | 0.116167E+11 | 6161.13 | 31-MAR-23:20 | 6.50 | 3.19 | 0.103236E+09 | 126.83 | 29-MAR-09:39 | 6.50 | 3.19 |
April | 0.172373E+11 | 7753.32 | 16-APR-18:00 | 19.40 | 7.60 | 91627767.84 | 126.82 | 20-APR-09:39 | 11.47 | 5.64 |
May | 0.373181E+10 | 3266.06 | 31-MAY-24:00 | 18.60 | 7.93 | 99234984.28 | 126.84 | 23-MAY-13:00 | 18.60 | 7.93 |
June | 0.887552E+10 | 5178.52 | 30-JUN-24:00 | 22.10 | 13.89 | 98961866.81 | 126.85 | 08-JUN-13:00 | 22.10 | 13.89 |
July | 0.142302E+11 | 6971.80 | 31-JUL-23:57 | 21.00 | 17.53 | 91886370.30 | 126.84 | 17-JUL-09:09 | 21.00 | 17.53 |
August | 0.189436E+11 | 7579.68 | 30-AUG-17:30 | 28.60 | 14.79 | 0.103947E+09 | 132.53 | 17-AUG-13:00 | 28.60 | 14.79 |
September | 0.391877E+10 | 3300.51 | 30-SEP-24:00 | 17.40 | 10.77 | 91612220.43 | 126.85 | 06-SEP-13:00 | 17.40 | 10.77 |
October | 0.771776E+10 | 4606.32 | 31-OCT-23:50 | 13.17 | 4.73 | 95233026.09 | 126.84 | 11-OCT-09:00 | 13.17 | 4.73 |
November | 0.104168E+11 | 5729.76 | 02-NOV-16:40 | 16.30 | 9.65 | 94300815.98 | 126.83 | 02-NOV-09:00 | 16.30 | 9.65 |
December | 0.143288E+11 | 7292.97 | 29-DEC-16:50 | 10.28 | 3.14 | 91880809.60 | 126.82 | 08-DEC-14:09 | 10.28 | 3.14 |
Annual Sum or Average | 0.116410E+12 | 0.114242E+10 | ||||||||
Minimum of Months | 0.610961E+09 | 1969.21 | 6.50 | 1.21 | 86396719.15 | 126.82 | 6.50 | 1.21 | ||
Maximum of Months | 0.189436E+11 | 7753.32 | 28.60 | 17.53 | 0.103947E+09 | 132.53 | 28.60 | 17.53 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.238107E+12 | 92009.88 | 02-JAN-17:00 | 11.10 | 4.18 | 0.206145E+10 | 2745.73 | 05-JAN-14:00 | 16.10 | 6.84 |
February | 0.435664E+12 | 183463.75 | 15-FEB-17:00 | 16.70 | 5.85 | 0.187264E+10 | 2749.46 | 01-FEB-10:50 | 16.70 | 5.85 |
March | 0.729037E+12 | 358557.24 | 31-MAR-24:00 | 6.90 | 3.36 | 0.223667E+10 | 2748.26 | 01-MAR-14:09 | 6.90 | 3.36 |
April | 0.935482E+12 | 366754.19 | 18-APR-07:15 | 7.23 | 1.32 | 0.230033E+10 | 3623.46 | 28-APR-13:00 | 24.40 | 10.28 |
May | 0.241281E+12 | 176011.75 | 31-MAY-24:00 | 18.60 | 7.93 | 0.214866E+10 | 2747.84 | 08-MAY-13:00 | 18.60 | 7.93 |
June | 0.470563E+12 | 267808.51 | 30-JUN-23:55 | 22.10 | 13.89 | 0.214399E+10 | 2749.57 | 09-JUN-09:00 | 22.10 | 13.89 |
July | 0.732687E+12 | 356451.47 | 31-JUL-23:13 | 21.13 | 17.19 | 0.198992E+10 | 2749.66 | 19-JUL-13:00 | 21.13 | 17.19 |
August | 0.958220E+12 | 364744.51 | 31-AUG-06:05 | 13.63 | 11.20 | 0.323835E+10 | 4417.52 | 17-AUG-13:00 | 13.63 | 11.20 |
September | 0.236999E+12 | 176538.64 | 30-SEP-24:00 | 17.40 | 10.77 | 0.198380E+10 | 2748.05 | 15-SEP-13:30 | 17.40 | 10.77 |
October | 0.488176E+12 | 268672.67 | 31-OCT-24:00 | 13.00 | 4.55 | 0.206392E+10 | 2749.61 | 16-OCT-09:30 | 13.00 | 4.55 |
November | 0.708632E+12 | 276418.53 | 24-NOV-17:00 | 13.90 | 4.33 | 0.204308E+10 | 2748.25 | 01-NOV-13:50 | 13.90 | 4.33 |
December | 0.972985E+12 | 366518.05 | 13-DEC-16:55 | 7.20 | 0.17 | 0.210889E+10 | 3028.77 | 26-DEC-14:00 | 10.00 | 3.84 |
Annual Sum or Average | 0.714783E+13 | 0.261917E+11 | ||||||||
Minimum of Months | 0.236999E+12 | 92009.88 | 6.90 | 0.17 | 0.187264E+10 | 2745.73 | 6.90 | 3.36 | ||
Maximum of Months | 0.972985E+12 | 366754.19 | 22.10 | 17.19 | 0.323835E+10 | 4417.52 | 24.40 | 17.19 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.228035E+09 | 14509.65 | 01-JAN-09:43 | 4.53 |
February | 0.169171E+09 | 12937.39 | 13-FEB-04:05 | 1.10 |
March | 0.152653E+09 | 12945.54 | 13-MAR-03:05 | 1.20 |
April | 0.257400E+09 | 12654.66 | 05-APR-04:05 | 4.32 |
May | 0.337004E+09 | 14047.42 | 29-MAY-17:43 | 22.85 |
June | 0.392574E+09 | 20419.29 | 17-JUN-16:01 | 33.43 |
July | 0.559608E+09 | 23471.37 | 22-JUL-16:01 | 36.05 |
August | 0.383431E+09 | 18514.23 | 05-AUG-16:01 | 31.52 |
September | 0.463733E+09 | 17922.13 | 02-SEP-16:01 | 31.10 |
October | 0.391541E+09 | 14290.63 | 01-OCT-23:43 | 18.48 |
November | 0.348986E+09 | 12742.31 | 20-NOV-04:05 | 3.22 |
December | 0.248373E+09 | 12523.41 | 11-DEC-04:45 | 1.78 |
Annual Sum or Average | 0.393251E+10 | |||
Minimum of Months | 0.152653E+09 | 12523.41 | 1.10 | |
Maximum of Months | 0.559608E+09 | 23471.37 | 36.05 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 2.30 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -3.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -3.2 | |
Maximum of Months | 0.00 | 0.00 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 2.30 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -3.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -3.2 | |
Maximum of Months | 0.00 | 0.00 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.150546E+10 | 72705.32 | 17-JAN-04:11 | -3.3 |
February | 0.580859E+09 | 71867.33 | 06-FEB-04:01 | -4.4 |
March | 22838143.64 | 62102.84 | 06-MAR-06:01 | -2.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.88 |
October | 2101912.07 | 17515.93 | 26-OCT-05:02 | -2.5 |
November | 0.294079E+09 | 67431.97 | 27-NOV-05:11 | -4.1 |
December | 0.119966E+10 | 72158.29 | 26-DEC-04:01 | 0.32 |
Annual Sum or Average | 0.360499E+10 | |||
Minimum of Months | 0.00 | 0.00 | -4.4 | |
Maximum of Months | 0.150546E+10 | 72705.32 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 2587926.84 | 6391.40 | 17-JAN-06:01 | -3.4 |
February | 2054688.88 | 8648.92 | 06-FEB-06:01 | -4.6 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 |
Annual Sum or Average | 4642615.73 | |||
Minimum of Months | 0.00 | 0.00 | -4.6 | |
Maximum of Months | 2587926.84 | 8648.92 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 8037029.00 | 6176.36 | 21-JAN-06:01 | -6.5 |
February | 3275917.49 | 6277.69 | 06-FEB-06:01 | -4.6 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
December | 5800478.14 | 6388.37 | 22-DEC-06:01 | -6.1 |
Annual Sum or Average | 17113424.63 | |||
Minimum of Months | 0.00 | 0.00 | -6.5 | |
Maximum of Months | 8037029.00 | 6388.37 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 34349931.31 | 10881.53 | 17-JAN-06:01 | -3.4 |
February | 10961224.08 | 11004.90 | 06-FEB-06:01 | -4.6 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
December | 5253210.58 | 10566.97 | 22-DEC-06:01 | -6.1 |
Annual Sum or Average | 50564365.98 | |||
Minimum of Months | 0.00 | 0.00 | -6.1 | |
Maximum of Months | 34349931.31 | 11004.90 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 2.30 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -3.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -3.2 | |
Maximum of Months | 0.00 | 0.00 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.115410E+10 | 12822.62 | 17-JAN-04:01 | -3.3 |
February | 0.672903E+09 | 12825.86 | 06-FEB-04:01 | -4.4 |
March | 88390659.05 | 11152.15 | 06-MAR-05:01 | -0.5 |
April | 2641144.49 | 8719.02 | 08-APR-05:03 | 2.62 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.88 |
October | 24495060.47 | 10559.35 | 26-OCT-05:02 | -2.5 |
November | 0.217587E+09 | 11681.42 | 27-NOV-05:01 | -4.0 |
December | 0.114575E+10 | 11839.36 | 23-DEC-05:01 | -5.1 |
Annual Sum or Average | 0.330586E+10 | |||
Minimum of Months | 0.00 | 0.00 | -5.1 | |
Maximum of Months | 0.115410E+10 | 12825.86 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.560834E+09 | 14479.40 | 17-JAN-04:01 | -3.3 |
February | 0.268180E+09 | 14445.29 | 06-FEB-04:01 | -4.4 |
March | 23819823.62 | 12269.32 | 04-MAR-05:01 | -1.2 |
April | 923394.29 | 4011.85 | 08-APR-05:03 | 2.62 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.88 |
October | 12680141.67 | 10842.50 | 26-OCT-05:02 | -2.5 |
November | 67873715.67 | 12702.34 | 27-NOV-05:01 | -4.0 |
December | 0.491988E+09 | 13226.29 | 26-DEC-05:01 | -1.0 |
Annual Sum or Average | 0.142630E+10 | |||
Minimum of Months | 0.00 | 0.00 | -4.4 | |
Maximum of Months | 0.560834E+09 | 14479.40 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.342378E+09 | 15035.88 | 17-JAN-04:01 | -3.3 |
February | 0.177081E+09 | 14401.29 | 06-FEB-05:21 | -4.4 |
March | 17588649.24 | 12915.81 | 04-MAR-06:01 | -1.7 |
April | 400946.40 | 2642.73 | 08-APR-05:03 | 2.62 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.88 |
October | 8498855.05 | 12783.83 | 26-OCT-05:02 | -2.5 |
November | 13762250.00 | 12899.59 | 28-NOV-06:01 | -2.1 |
December | 0.269261E+09 | 14043.24 | 26-DEC-05:01 | -1.0 |
Annual Sum or Average | 0.828971E+09 | |||
Minimum of Months | 0.00 | 0.00 | -4.4 | |
Maximum of Months | 0.342378E+09 | 15035.88 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.362537E+09 | 13945.24 | 17-JAN-04:01 | -3.3 |
February | 0.195576E+09 | 13952.38 | 06-FEB-04:01 | -4.4 |
March | 15685646.24 | 11495.66 | 04-MAR-06:01 | -1.7 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.88 |
October | 6688612.23 | 9390.34 | 26-OCT-05:02 | -2.5 |
November | 30063296.36 | 11506.46 | 28-NOV-06:01 | -2.1 |
December | 0.301306E+09 | 12575.71 | 23-DEC-05:01 | -5.1 |
Annual Sum or Average | 0.911857E+09 | |||
Minimum of Months | 0.00 | 0.00 | -5.1 | |
Maximum of Months | 0.362537E+09 | 13952.38 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.448039E+10 | 15928.30 | 16-JAN-23:33 | -2.2 |
February | 0.285563E+10 | 15894.31 | 06-FEB-02:62 | -5.0 |
March | 0.940061E+09 | 14271.73 | 06-MAR-04:02 | 0.50 |
April | 0.122182E+09 | 13169.68 | 08-APR-04:02 | 2.80 |
May | 11536704.72 | 12156.32 | 05-MAY-05:02 | 5.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.88 |
October | 0.360618E+09 | 13613.52 | 26-OCT-04:01 | -2.8 |
November | 0.160439E+10 | 14969.59 | 27-NOV-04:01 | -3.9 |
December | 0.456531E+10 | 15426.53 | 26-DEC-04:01 | 0.32 |
Annual Sum or Average | 0.149401E+11 | |||
Minimum of Months | 0.00 | 0.00 | -5.0 | |
Maximum of Months | 0.456531E+10 | 15928.30 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.205483E+10 | 17240.10 | 17-JAN-04:11 | -3.3 |
February | 0.120805E+10 | 17109.71 | 06-FEB-04:01 | -4.4 |
March | 0.348686E+09 | 14678.81 | 04-MAR-05:01 | -1.2 |
April | 30529209.20 | 13917.71 | 08-APR-04:02 | 2.80 |
May | 3641697.87 | 6783.04 | 05-MAY-05:02 | 5.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.88 |
October | 0.156101E+09 | 14672.71 | 26-OCT-04:01 | -2.8 |
November | 0.588552E+09 | 16097.54 | 27-NOV-04:01 | -3.9 |
December | 0.196806E+10 | 16720.09 | 26-DEC-04:01 | 0.32 |
Annual Sum or Average | 0.635845E+10 | |||
Minimum of Months | 0.00 | 0.00 | -4.4 | |
Maximum of Months | 0.205483E+10 | 17240.10 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.188387E+10 | 18681.91 | 17-JAN-04:11 | -3.3 |
February | 0.115092E+10 | 18506.65 | 06-FEB-04:01 | -4.4 |
March | 0.413884E+09 | 16081.10 | 04-MAR-05:01 | -1.2 |
April | 60979393.53 | 15086.84 | 08-APR-04:02 | 2.80 |
May | 12694373.83 | 13752.69 | 05-MAY-05:02 | 5.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.88 |
October | 0.157926E+09 | 16092.94 | 26-OCT-04:01 | -2.8 |
November | 0.401752E+09 | 17016.14 | 27-NOV-04:01 | -3.9 |
December | 0.166615E+10 | 18180.30 | 26-DEC-04:01 | 0.32 |
Annual Sum or Average | 0.574819E+10 | |||
Minimum of Months | 0.00 | 0.00 | -4.4 | |
Maximum of Months | 0.188387E+10 | 18681.91 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.160546E+10 | 18800.98 | 17-JAN-04:11 | -3.3 |
February | 0.956350E+09 | 18615.43 | 06-FEB-04:01 | -4.4 |
March | 0.271114E+09 | 15757.31 | 04-MAR-05:01 | -1.2 |
April | 17034302.48 | 8030.13 | 06-APR-05:02 | 2.12 |
May | 3660656.84 | 8320.53 | 05-MAY-05:02 | 5.68 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.88 |
October | 0.108403E+09 | 15645.65 | 26-OCT-04:01 | -2.8 |
November | 0.424019E+09 | 16908.03 | 27-NOV-04:01 | -3.9 |
December | 0.143549E+10 | 17763.89 | 26-DEC-04:01 | 0.32 |
Annual Sum or Average | 0.482153E+10 | |||
Minimum of Months | 0.00 | 0.00 | -4.4 | |
Maximum of Months | 0.160546E+10 | 18800.98 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.301067E+09 | 12045.57 | 17-JAN-05:01 | -3.3 |
February | 0.180865E+09 | 11991.26 | 07-FEB-06:01 | -3.9 |
March | 0.137417E+09 | 11292.25 | 20-MAR-03:02 | 11.32 |
April | 0.182879E+09 | 11351.18 | 24-APR-03:02 | 5.18 |
May | 90736253.08 | 8928.38 | 01-MAY-03:02 | 11.85 |
June | 82328553.60 | 8817.67 | 05-JUN-03:02 | 15.00 |
July | 96289018.10 | 9877.20 | 30-JUL-15:21 | 33.60 |
August | 0.109478E+09 | 10275.71 | 20-AUG-15:41 | 35.00 |
September | 78796643.70 | 7928.36 | 18-SEP-03:02 | 14.90 |
October | 0.119875E+09 | 9747.59 | 23-OCT-03:02 | 8.22 |
November | 0.187485E+09 | 11595.94 | 27-NOV-04:01 | -3.9 |
December | 0.196322E+09 | 13771.30 | 26-DEC-04:01 | 0.32 |
Annual Sum or Average | 0.176354E+10 | |||
Minimum of Months | 78796643.70 | 7928.36 | -3.9 | |
Maximum of Months | 0.301067E+09 | 13771.30 | 35.00 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.167758E+10 | 7521.52 | 01-JAN-14:12 | 15.77 |
February | 0.109940E+10 | 7253.57 | 15-FEB-06:03 | 6.93 |
March | 0.254375E+09 | 8248.68 | 14-MAR-05:03 | 6.02 |
April | 60197315.60 | 6722.22 | 06-APR-05:02 | 2.12 |
May | 67871093.90 | 7030.85 | 05-MAY-05:02 | 5.68 |
June | 61437502.81 | 8668.17 | 25-JUN-16:41 | 33.68 |
July | 76589484.42 | 8809.23 | 30-JUL-16:01 | 33.62 |
August | 56650458.52 | 7731.75 | 20-AUG-15:21 | 35.00 |
September | 67675180.76 | 7472.81 | 03-SEP-13:41 | 32.52 |
October | 0.113771E+09 | 6918.01 | 15-OCT-15:22 | 20.85 |
November | 0.417814E+09 | 7792.42 | 08-NOV-06:02 | 11.52 |
December | 0.143728E+10 | 7178.42 | 17-DEC-14:32 | 11.50 |
Annual Sum or Average | 0.539063E+10 | |||
Minimum of Months | 56650458.52 | 6722.22 | 2.12 | |
Maximum of Months | 0.167758E+10 | 8809.23 | 35.00 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.634094E+10 | 23147.96 | 17-JAN-05:12 | -3.3 |
February | 0.408741E+10 | 24527.35 | 06-FEB-06:12 | -4.8 |
March | 0.229264E+10 | 11085.53 | 06-MAR-06:01 | -2.9 |
April | 0.826779E+09 | 16710.04 | 18-APR-05:02 | 7.12 |
May | 0.424349E+09 | 15202.71 | 03-MAY-05:02 | 8.40 |
June | 0.167961E+09 | 13900.18 | 10-JUN-05:03 | 12.30 |
July | 84629988.76 | 9427.07 | 31-JUL-03:02 | 19.40 |
August | 90393949.47 | 11065.98 | 29-AUG-04:02 | 16.02 |
September | 0.216322E+09 | 13619.87 | 27-SEP-05:03 | 11.60 |
October | 0.131708E+10 | 17676.68 | 12-OCT-05:03 | 6.70 |
November | 0.290510E+10 | 19234.77 | 27-NOV-06:03 | -4.4 |
December | 0.639614E+10 | 21208.93 | 26-DEC-06:13 | -1.0 |
Annual Sum or Average | 0.251497E+11 | |||
Minimum of Months | 84629988.76 | 9427.07 | -4.8 | |
Maximum of Months | 0.639614E+10 | 24527.35 | 19.40 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 2.30 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -3.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -3.2 | |
Maximum of Months | 0.00 | 0.00 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 30375051.29 | 498.02 | 17-JAN-04:52 | -3.3 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -3.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 |
Annual Sum or Average | 30375051.29 | |||
Minimum of Months | 0.00 | 0.00 | -3.3 | |
Maximum of Months | 30375051.29 | 498.02 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.715505E+09 | 674.30 | 18-JAN-01:30 | -2.2 |
February | 6437668.55 | 392.14 | 06-FEB-04:17 | -4.4 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 |
Annual Sum or Average | 0.721943E+09 | |||
Minimum of Months | 0.00 | 0.00 | -4.4 | |
Maximum of Months | 0.715505E+09 | 674.30 | 21.95 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 2.30 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -3.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2.47 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 14.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.42 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.95 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 20.95 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.88 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 17.33 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12.83 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.13 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -3.2 | |
Maximum of Months | 0.00 | 0.00 | 21.95 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.148304E+11 | 15519.45 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.134523E+11 | 15519.45 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.159851E+11 | 15519.45 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.142779E+11 | 15519.45 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.154078E+11 | 15519.45 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.153333E+11 | 15519.45 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.143524E+11 | 15519.45 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.159851E+11 | 15519.45 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.142779E+11 | 15519.45 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.148304E+11 | 15519.45 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.146566E+11 | 15519.45 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.143524E+11 | 15519.45 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.177742E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.134523E+11 | 15519.45 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.159851E+11 | 15519.45 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.133188E+11 | 13937.56 | 02-JAN-08:09 | 0.270551E+11 | 18128.59 | 02-JAN-08:09 |
February | 0.120811E+11 | 13937.56 | 01-FEB-08:09 | 0.244881E+11 | 18128.59 | 01-FEB-08:09 |
March | 0.143557E+11 | 13937.56 | 01-MAR-08:09 | 0.280558E+11 | 18128.59 | 01-MAR-08:09 |
April | 0.128226E+11 | 13937.56 | 03-APR-07:10 | 0.261305E+11 | 18128.59 | 03-APR-07:10 |
May | 0.138373E+11 | 13937.56 | 01-MAY-07:10 | 0.275555E+11 | 18128.59 | 01-MAY-07:10 |
June | 0.137704E+11 | 13937.56 | 01-JUN-07:10 | 0.270261E+11 | 18128.59 | 01-JUN-07:10 |
July | 0.128895E+11 | 13937.56 | 03-JUL-07:10 | 0.266527E+11 | 18128.59 | 03-JUL-07:10 |
August | 0.143557E+11 | 13937.56 | 01-AUG-07:10 | 0.280558E+11 | 18128.59 | 01-AUG-07:10 |
September | 0.128226E+11 | 13937.56 | 01-SEP-07:10 | 0.261160E+11 | 18128.59 | 01-SEP-07:10 |
October | 0.133188E+11 | 13937.56 | 02-OCT-07:10 | 0.270624E+11 | 18128.59 | 02-OCT-07:10 |
November | 0.131627E+11 | 13937.56 | 01-NOV-07:10 | 0.264424E+11 | 18128.59 | 01-NOV-07:10 |
December | 0.128895E+11 | 13937.56 | 01-DEC-08:09 | 0.266454E+11 | 18128.59 | 01-DEC-08:09 |
Annual Sum or Average | 0.159625E+12 | 0.321286E+12 | ||||
Minimum of Months | 0.120811E+11 | 13937.56 | 0.244881E+11 | 18128.59 | ||
Maximum of Months | 0.143557E+11 | 13937.56 | 0.280558E+11 | 18128.59 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.133188E+11 | 13937.56 | 02-JAN-08:09 | 0.270550E+11 | 18128.52 | 02-JAN-08:09 |
February | 0.120811E+11 | 13937.56 | 01-FEB-08:09 | 0.244880E+11 | 18128.52 | 01-FEB-08:09 |
March | 0.143557E+11 | 13937.56 | 01-MAR-08:09 | 0.280557E+11 | 18128.52 | 01-MAR-08:09 |
April | 0.128226E+11 | 13937.56 | 03-APR-07:10 | 0.261304E+11 | 18128.52 | 03-APR-07:10 |
May | 0.138373E+11 | 13937.56 | 01-MAY-07:10 | 0.275554E+11 | 18128.52 | 01-MAY-07:10 |
June | 0.137704E+11 | 13937.56 | 01-JUN-07:10 | 0.270260E+11 | 18128.52 | 01-JUN-07:10 |
July | 0.128895E+11 | 13937.56 | 03-JUL-07:10 | 0.266526E+11 | 18128.52 | 03-JUL-07:10 |
August | 0.143557E+11 | 13937.56 | 01-AUG-07:10 | 0.280557E+11 | 18128.52 | 01-AUG-07:10 |
September | 0.128226E+11 | 13937.56 | 01-SEP-07:10 | 0.261159E+11 | 18128.52 | 01-SEP-07:10 |
October | 0.133188E+11 | 13937.56 | 02-OCT-07:10 | 0.270623E+11 | 18128.52 | 02-OCT-07:10 |
November | 0.131627E+11 | 13937.56 | 01-NOV-07:10 | 0.264423E+11 | 18128.52 | 01-NOV-07:10 |
December | 0.128895E+11 | 13937.56 | 01-DEC-08:09 | 0.266453E+11 | 18128.52 | 01-DEC-08:09 |
Annual Sum or Average | 0.159625E+12 | 0.321285E+12 | ||||
Minimum of Months | 0.120811E+11 | 13937.56 | 0.244880E+11 | 18128.52 | ||
Maximum of Months | 0.143557E+11 | 13937.56 | 0.280557E+11 | 18128.52 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.133188E+11 | 13937.56 | 02-JAN-08:09 | 0.270550E+11 | 18128.52 | 02-JAN-08:09 |
February | 0.120811E+11 | 13937.56 | 01-FEB-08:09 | 0.244880E+11 | 18128.52 | 01-FEB-08:09 |
March | 0.143557E+11 | 13937.56 | 01-MAR-08:09 | 0.280557E+11 | 18128.52 | 01-MAR-08:09 |
April | 0.128226E+11 | 13937.56 | 03-APR-07:10 | 0.261304E+11 | 18128.52 | 03-APR-07:10 |
May | 0.138373E+11 | 13937.56 | 01-MAY-07:10 | 0.275554E+11 | 18128.52 | 01-MAY-07:10 |
June | 0.137704E+11 | 13937.56 | 01-JUN-07:10 | 0.270260E+11 | 18128.52 | 01-JUN-07:10 |
July | 0.128895E+11 | 13937.56 | 03-JUL-07:10 | 0.266526E+11 | 18128.52 | 03-JUL-07:10 |
August | 0.143557E+11 | 13937.56 | 01-AUG-07:10 | 0.280557E+11 | 18128.52 | 01-AUG-07:10 |
September | 0.128226E+11 | 13937.56 | 01-SEP-07:10 | 0.261159E+11 | 18128.52 | 01-SEP-07:10 |
October | 0.133188E+11 | 13937.56 | 02-OCT-07:10 | 0.270623E+11 | 18128.52 | 02-OCT-07:10 |
November | 0.131627E+11 | 13937.56 | 01-NOV-07:10 | 0.264423E+11 | 18128.52 | 01-NOV-07:10 |
December | 0.128895E+11 | 13937.56 | 01-DEC-08:09 | 0.266453E+11 | 18128.52 | 01-DEC-08:09 |
Annual Sum or Average | 0.159625E+12 | 0.321285E+12 | ||||
Minimum of Months | 0.120811E+11 | 13937.56 | 0.244880E+11 | 18128.52 | ||
Maximum of Months | 0.143557E+11 | 13937.56 | 0.280557E+11 | 18128.52 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.120889E+10 | 1619.54 | 09-JAN-16:00 | 0.339718E+10 | 2276.32 | 02-JAN-08:09 |
February | 0.106786E+10 | 1478.68 | 16-FEB-08:09 | 0.307485E+10 | 2276.32 | 01-FEB-08:09 |
March | 0.122772E+10 | 1341.29 | 20-MAR-07:10 | 0.352283E+10 | 2276.32 | 01-MAR-08:09 |
April | 0.107233E+10 | 1075.02 | 03-APR-07:10 | 0.328108E+10 | 2276.32 | 03-APR-07:10 |
May | 0.114790E+10 | 1075.02 | 01-MAY-07:10 | 0.346000E+10 | 2276.32 | 01-MAY-07:10 |
June | 0.113152E+10 | 1075.02 | 01-JUN-07:10 | 0.339353E+10 | 2276.32 | 01-JUN-07:10 |
July | 0.106733E+10 | 1075.02 | 03-JUL-07:10 | 0.334664E+10 | 2276.32 | 03-JUL-07:10 |
August | 0.119245E+10 | 1075.02 | 01-AUG-07:10 | 0.352283E+10 | 2276.32 | 01-AUG-07:10 |
September | 0.108805E+10 | 1458.04 | 08-SEP-07:10 | 0.327926E+10 | 2276.32 | 01-SEP-07:10 |
October | 0.116468E+10 | 1458.66 | 25-OCT-07:10 | 0.339809E+10 | 2276.32 | 02-OCT-07:10 |
November | 0.119329E+10 | 1750.00 | 13-NOV-16:00 | 0.332024E+10 | 2276.32 | 01-NOV-07:10 |
December | 0.120531E+10 | 1750.00 | 01-DEC-16:00 | 0.334573E+10 | 2276.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.137673E+11 | 0.403423E+11 | ||||
Minimum of Months | 0.106733E+10 | 1075.02 | 0.307485E+10 | 2276.32 | ||
Maximum of Months | 0.122772E+10 | 1750.00 | 0.352283E+10 | 2276.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.772310E+09 | 1044.15 | 09-JAN-16:00 | 0.218927E+10 | 1466.95 | 02-JAN-08:09 |
February | 0.685736E+09 | 941.83 | 16-FEB-08:09 | 0.198155E+10 | 1466.95 | 01-FEB-08:09 |
March | 0.790154E+09 | 820.15 | 14-MAR-15:00 | 0.227025E+10 | 1466.95 | 01-MAR-08:09 |
April | 0.693167E+09 | 692.79 | 03-APR-07:10 | 0.211446E+10 | 1466.95 | 03-APR-07:10 |
May | 0.743861E+09 | 692.79 | 01-MAY-07:10 | 0.222976E+10 | 1466.95 | 01-MAY-07:10 |
June | 0.732967E+09 | 692.79 | 01-JUN-07:10 | 0.218692E+10 | 1466.95 | 01-JUN-07:10 |
July | 0.690510E+09 | 692.79 | 03-JUL-07:10 | 0.215670E+10 | 1466.95 | 03-JUL-07:10 |
August | 0.770333E+09 | 692.79 | 01-AUG-07:10 | 0.227025E+10 | 1466.95 | 01-AUG-07:10 |
September | 0.701018E+09 | 930.85 | 08-SEP-07:10 | 0.211328E+10 | 1466.95 | 01-SEP-07:10 |
October | 0.744595E+09 | 902.28 | 25-OCT-07:10 | 0.218986E+10 | 1466.95 | 02-OCT-07:10 |
November | 0.767369E+09 | 1127.77 | 13-NOV-16:00 | 0.213969E+10 | 1466.95 | 01-NOV-07:10 |
December | 0.770224E+09 | 1127.77 | 01-DEC-16:00 | 0.215612E+10 | 1466.95 | 01-DEC-08:09 |
Annual Sum or Average | 0.886224E+10 | 0.259981E+11 | ||||
Minimum of Months | 0.685736E+09 | 692.79 | 0.198155E+10 | 1466.95 | ||
Maximum of Months | 0.790154E+09 | 1127.77 | 0.227025E+10 | 1466.95 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.117794E+10 | 1542.62 | 04-JAN-16:00 | 0.339723E+10 | 2276.35 | 02-JAN-08:09 |
February | 0.105316E+10 | 1468.05 | 16-FEB-08:09 | 0.307490E+10 | 2276.35 | 01-FEB-08:09 |
March | 0.122228E+10 | 1320.24 | 20-MAR-07:10 | 0.352288E+10 | 2276.35 | 01-MAR-08:09 |
April | 0.107489E+10 | 1075.05 | 03-APR-07:10 | 0.328113E+10 | 2276.35 | 03-APR-07:10 |
May | 0.115381E+10 | 1075.05 | 01-MAY-07:10 | 0.346006E+10 | 2276.35 | 01-MAY-07:10 |
June | 0.113885E+10 | 1075.05 | 01-JUN-07:10 | 0.339359E+10 | 2276.35 | 01-JUN-07:10 |
July | 0.107248E+10 | 1075.05 | 03-JUL-07:10 | 0.334669E+10 | 2276.35 | 03-JUL-07:10 |
August | 0.119536E+10 | 1075.05 | 01-AUG-07:10 | 0.352288E+10 | 2276.35 | 01-AUG-07:10 |
September | 0.108694E+10 | 1455.86 | 08-SEP-07:10 | 0.327931E+10 | 2276.35 | 01-SEP-07:10 |
October | 0.114680E+10 | 1434.14 | 25-OCT-07:10 | 0.339814E+10 | 2276.35 | 02-OCT-07:10 |
November | 0.116997E+10 | 1750.04 | 13-NOV-16:00 | 0.332029E+10 | 2276.35 | 01-NOV-07:10 |
December | 0.117186E+10 | 1750.04 | 01-DEC-16:00 | 0.334578E+10 | 2276.35 | 01-DEC-08:09 |
Annual Sum or Average | 0.136644E+11 | 0.403429E+11 | ||||
Minimum of Months | 0.105316E+10 | 1075.05 | 0.307490E+10 | 2276.35 | ||
Maximum of Months | 0.122228E+10 | 1750.04 | 0.352288E+10 | 2276.35 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.766024E+09 | 976.97 | 04-JAN-16:00 | 0.218926E+10 | 1466.94 | 02-JAN-08:09 |
February | 0.681967E+09 | 955.18 | 16-FEB-08:09 | 0.198154E+10 | 1466.94 | 01-FEB-08:09 |
March | 0.789160E+09 | 912.47 | 22-MAR-07:10 | 0.227023E+10 | 1466.94 | 01-MAR-08:09 |
April | 0.690699E+09 | 692.79 | 03-APR-07:10 | 0.211444E+10 | 1466.94 | 03-APR-07:10 |
May | 0.740033E+09 | 692.79 | 01-MAY-07:10 | 0.222974E+10 | 1466.94 | 01-MAY-07:10 |
June | 0.730925E+09 | 821.54 | 08-JUN-07:10 | 0.218691E+10 | 1466.94 | 01-JUN-07:10 |
July | 0.689212E+09 | 692.79 | 03-JUL-07:10 | 0.215669E+10 | 1466.94 | 03-JUL-07:10 |
August | 0.769192E+09 | 692.79 | 01-AUG-07:10 | 0.227023E+10 | 1466.94 | 01-AUG-07:10 |
September | 0.700258E+09 | 943.72 | 08-SEP-07:10 | 0.211327E+10 | 1466.94 | 01-SEP-07:10 |
October | 0.745412E+09 | 952.72 | 25-OCT-07:10 | 0.218984E+10 | 1466.94 | 02-OCT-07:10 |
November | 0.755448E+09 | 1127.77 | 13-NOV-16:00 | 0.213967E+10 | 1466.94 | 01-NOV-07:10 |
December | 0.760917E+09 | 1127.77 | 01-DEC-16:00 | 0.215610E+10 | 1466.94 | 01-DEC-08:09 |
Annual Sum or Average | 0.881925E+10 | 0.259979E+11 | ||||
Minimum of Months | 0.681967E+09 | 692.79 | 0.198154E+10 | 1466.94 | ||
Maximum of Months | 0.789160E+09 | 1127.77 | 0.227023E+10 | 1466.94 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.121095E+10 | 1624.66 | 09-JAN-16:00 | 0.339718E+10 | 2276.32 | 02-JAN-08:09 |
February | 0.106920E+10 | 1486.80 | 16-FEB-08:09 | 0.307485E+10 | 2276.32 | 01-FEB-08:09 |
March | 0.122875E+10 | 1353.52 | 20-MAR-07:10 | 0.352283E+10 | 2276.32 | 01-MAR-08:09 |
April | 0.107250E+10 | 1075.02 | 03-APR-07:10 | 0.328108E+10 | 2276.32 | 03-APR-07:10 |
May | 0.114808E+10 | 1075.02 | 01-MAY-07:10 | 0.346000E+10 | 2276.32 | 01-MAY-07:10 |
June | 0.113200E+10 | 1181.89 | 08-JUN-15:00 | 0.339353E+10 | 2276.32 | 01-JUN-07:10 |
July | 0.106754E+10 | 1075.02 | 03-JUL-07:10 | 0.334664E+10 | 2276.32 | 03-JUL-07:10 |
August | 0.119246E+10 | 1075.02 | 01-AUG-07:10 | 0.352283E+10 | 2276.32 | 01-AUG-07:10 |
September | 0.108860E+10 | 1466.81 | 08-SEP-07:10 | 0.327926E+10 | 2276.32 | 01-SEP-07:10 |
October | 0.116588E+10 | 1467.31 | 25-OCT-07:10 | 0.339809E+10 | 2276.32 | 02-OCT-07:10 |
November | 0.119476E+10 | 1750.00 | 13-NOV-16:00 | 0.332024E+10 | 2276.32 | 01-NOV-07:10 |
December | 0.120723E+10 | 1750.00 | 01-DEC-16:00 | 0.334573E+10 | 2276.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.137779E+11 | 0.403423E+11 | ||||
Minimum of Months | 0.106754E+10 | 1075.02 | 0.307485E+10 | 2276.32 | ||
Maximum of Months | 0.122875E+10 | 1750.00 | 0.352283E+10 | 2276.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.772521E+09 | 1046.38 | 09-JAN-16:00 | 0.218927E+10 | 1466.95 | 02-JAN-08:09 |
February | 0.686059E+09 | 943.53 | 16-FEB-08:09 | 0.198155E+10 | 1466.95 | 01-FEB-08:09 |
March | 0.790455E+09 | 822.32 | 14-MAR-15:00 | 0.227025E+10 | 1466.95 | 01-MAR-08:09 |
April | 0.693254E+09 | 692.79 | 03-APR-07:10 | 0.211446E+10 | 1466.95 | 03-APR-07:10 |
May | 0.743954E+09 | 692.79 | 01-MAY-07:10 | 0.222976E+10 | 1466.95 | 01-MAY-07:10 |
June | 0.733162E+09 | 760.79 | 08-JUN-15:00 | 0.218692E+10 | 1466.95 | 01-JUN-07:10 |
July | 0.690661E+09 | 692.79 | 03-JUL-07:10 | 0.215670E+10 | 1466.95 | 03-JUL-07:10 |
August | 0.770406E+09 | 692.79 | 01-AUG-07:10 | 0.227025E+10 | 1466.95 | 01-AUG-07:10 |
September | 0.701198E+09 | 932.71 | 08-SEP-07:10 | 0.211328E+10 | 1466.95 | 01-SEP-07:10 |
October | 0.744734E+09 | 905.08 | 25-OCT-07:10 | 0.218986E+10 | 1466.95 | 02-OCT-07:10 |
November | 0.767665E+09 | 1127.77 | 13-NOV-16:00 | 0.213969E+10 | 1466.95 | 01-NOV-07:10 |
December | 0.770454E+09 | 1127.77 | 01-DEC-16:00 | 0.215612E+10 | 1466.95 | 01-DEC-08:09 |
Annual Sum or Average | 0.886452E+10 | 0.259981E+11 | ||||
Minimum of Months | 0.686059E+09 | 692.79 | 0.198155E+10 | 1466.95 | ||
Maximum of Months | 0.790455E+09 | 1127.77 | 0.227025E+10 | 1466.95 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.117858E+10 | 1549.95 | 04-JAN-16:00 | 0.339723E+10 | 2276.35 | 02-JAN-08:09 |
February | 0.105357E+10 | 1476.62 | 16-FEB-08:09 | 0.307490E+10 | 2276.35 | 01-FEB-08:09 |
March | 0.122292E+10 | 1333.36 | 20-MAR-07:10 | 0.352288E+10 | 2276.35 | 01-MAR-08:09 |
April | 0.107527E+10 | 1075.05 | 03-APR-07:10 | 0.328113E+10 | 2276.35 | 03-APR-07:10 |
May | 0.115415E+10 | 1075.05 | 01-MAY-07:10 | 0.346006E+10 | 2276.35 | 01-MAY-07:10 |
June | 0.113959E+10 | 1183.56 | 08-JUN-15:00 | 0.339359E+10 | 2276.35 | 01-JUN-07:10 |
July | 0.107299E+10 | 1075.05 | 03-JUL-07:10 | 0.334669E+10 | 2276.35 | 03-JUL-07:10 |
August | 0.119575E+10 | 1075.05 | 01-AUG-07:10 | 0.352288E+10 | 2276.35 | 01-AUG-07:10 |
September | 0.108735E+10 | 1464.71 | 08-SEP-07:10 | 0.327931E+10 | 2276.35 | 01-SEP-07:10 |
October | 0.114550E+10 | 1443.83 | 25-OCT-07:10 | 0.339814E+10 | 2276.35 | 02-OCT-07:10 |
November | 0.117067E+10 | 1750.04 | 13-NOV-16:00 | 0.332029E+10 | 2276.35 | 01-NOV-07:10 |
December | 0.117314E+10 | 1750.04 | 01-DEC-16:00 | 0.334578E+10 | 2276.35 | 01-DEC-08:09 |
Annual Sum or Average | 0.136695E+11 | 0.403429E+11 | ||||
Minimum of Months | 0.105357E+10 | 1075.05 | 0.307490E+10 | 2276.35 | ||
Maximum of Months | 0.122292E+10 | 1750.04 | 0.352288E+10 | 2276.35 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.766288E+09 | 979.60 | 04-JAN-16:00 | 0.218926E+10 | 1466.94 | 02-JAN-08:09 |
February | 0.682192E+09 | 956.50 | 16-FEB-08:09 | 0.198154E+10 | 1466.94 | 01-FEB-08:09 |
March | 0.789462E+09 | 914.03 | 22-MAR-07:10 | 0.227023E+10 | 1466.94 | 01-MAR-08:09 |
April | 0.690850E+09 | 692.79 | 03-APR-07:10 | 0.211444E+10 | 1466.94 | 03-APR-07:10 |
May | 0.740148E+09 | 692.79 | 01-MAY-07:10 | 0.222974E+10 | 1466.94 | 01-MAY-07:10 |
June | 0.731036E+09 | 823.62 | 08-JUN-07:10 | 0.218691E+10 | 1466.94 | 01-JUN-07:10 |
July | 0.689338E+09 | 692.79 | 03-JUL-07:10 | 0.215669E+10 | 1466.94 | 03-JUL-07:10 |
August | 0.769371E+09 | 692.79 | 01-AUG-07:10 | 0.227023E+10 | 1466.94 | 01-AUG-07:10 |
September | 0.700434E+09 | 945.12 | 08-SEP-07:10 | 0.211327E+10 | 1466.94 | 01-SEP-07:10 |
October | 0.745569E+09 | 954.08 | 25-OCT-07:10 | 0.218984E+10 | 1466.94 | 02-OCT-07:10 |
November | 0.755768E+09 | 1127.77 | 13-NOV-16:00 | 0.213967E+10 | 1466.94 | 01-NOV-07:10 |
December | 0.761116E+09 | 1127.77 | 01-DEC-16:00 | 0.215610E+10 | 1466.94 | 01-DEC-08:09 |
Annual Sum or Average | 0.882157E+10 | 0.259979E+11 | ||||
Minimum of Months | 0.682192E+09 | 692.79 | 0.198154E+10 | 1466.94 | ||
Maximum of Months | 0.789462E+09 | 1127.77 | 0.227023E+10 | 1466.94 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.121098E+10 | 1624.81 | 09-JAN-16:00 | 0.339718E+10 | 2276.32 | 02-JAN-08:09 |
February | 0.106916E+10 | 1486.51 | 16-FEB-08:09 | 0.307485E+10 | 2276.32 | 01-FEB-08:09 |
March | 0.122881E+10 | 1353.17 | 20-MAR-07:10 | 0.352283E+10 | 2276.32 | 01-MAR-08:09 |
April | 0.107250E+10 | 1075.02 | 03-APR-07:10 | 0.328108E+10 | 2276.32 | 03-APR-07:10 |
May | 0.114808E+10 | 1075.02 | 01-MAY-07:10 | 0.346000E+10 | 2276.32 | 01-MAY-07:10 |
June | 0.113200E+10 | 1181.26 | 08-JUN-15:00 | 0.339353E+10 | 2276.32 | 01-JUN-07:10 |
July | 0.106754E+10 | 1075.02 | 03-JUL-07:10 | 0.334664E+10 | 2276.32 | 03-JUL-07:10 |
August | 0.119246E+10 | 1075.02 | 01-AUG-07:10 | 0.352283E+10 | 2276.32 | 01-AUG-07:10 |
September | 0.108860E+10 | 1466.50 | 08-SEP-07:10 | 0.327926E+10 | 2276.32 | 01-SEP-07:10 |
October | 0.116590E+10 | 1467.05 | 25-OCT-07:10 | 0.339809E+10 | 2276.32 | 02-OCT-07:10 |
November | 0.119478E+10 | 1750.00 | 13-NOV-16:00 | 0.332024E+10 | 2276.32 | 01-NOV-07:10 |
December | 0.120727E+10 | 1750.00 | 01-DEC-16:00 | 0.334573E+10 | 2276.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.137781E+11 | 0.403423E+11 | ||||
Minimum of Months | 0.106754E+10 | 1075.02 | 0.307485E+10 | 2276.32 | ||
Maximum of Months | 0.122881E+10 | 1750.00 | 0.352283E+10 | 2276.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.772539E+09 | 1046.50 | 09-JAN-16:00 | 0.218927E+10 | 1466.95 | 02-JAN-08:09 |
February | 0.686071E+09 | 943.36 | 16-FEB-08:09 | 0.198155E+10 | 1466.95 | 01-FEB-08:09 |
March | 0.790460E+09 | 822.08 | 14-MAR-15:00 | 0.227025E+10 | 1466.95 | 01-MAR-08:09 |
April | 0.693257E+09 | 692.79 | 03-APR-07:10 | 0.211446E+10 | 1466.95 | 03-APR-07:10 |
May | 0.743955E+09 | 692.79 | 01-MAY-07:10 | 0.222976E+10 | 1466.95 | 01-MAY-07:10 |
June | 0.733166E+09 | 760.41 | 08-JUN-15:00 | 0.218692E+10 | 1466.95 | 01-JUN-07:10 |
July | 0.690661E+09 | 692.79 | 03-JUL-07:10 | 0.215670E+10 | 1466.95 | 03-JUL-07:10 |
August | 0.770421E+09 | 692.79 | 01-AUG-07:10 | 0.227025E+10 | 1466.95 | 01-AUG-07:10 |
September | 0.701204E+09 | 932.53 | 08-SEP-07:10 | 0.211328E+10 | 1466.95 | 01-SEP-07:10 |
October | 0.744749E+09 | 904.96 | 25-OCT-07:10 | 0.218986E+10 | 1466.95 | 02-OCT-07:10 |
November | 0.767689E+09 | 1127.77 | 13-NOV-16:00 | 0.213969E+10 | 1466.95 | 01-NOV-07:10 |
December | 0.770513E+09 | 1127.77 | 01-DEC-16:00 | 0.215612E+10 | 1466.95 | 01-DEC-08:09 |
Annual Sum or Average | 0.886469E+10 | 0.259981E+11 | ||||
Minimum of Months | 0.686071E+09 | 692.79 | 0.198155E+10 | 1466.95 | ||
Maximum of Months | 0.790460E+09 | 1127.77 | 0.227025E+10 | 1466.95 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.117859E+10 | 1549.88 | 04-JAN-16:00 | 0.339723E+10 | 2276.35 | 02-JAN-08:09 |
February | 0.105356E+10 | 1476.34 | 16-FEB-08:09 | 0.307490E+10 | 2276.35 | 01-FEB-08:09 |
March | 0.122292E+10 | 1333.01 | 20-MAR-07:10 | 0.352288E+10 | 2276.35 | 01-MAR-08:09 |
April | 0.107527E+10 | 1075.05 | 03-APR-07:10 | 0.328113E+10 | 2276.35 | 03-APR-07:10 |
May | 0.115416E+10 | 1075.05 | 01-MAY-07:10 | 0.346006E+10 | 2276.35 | 01-MAY-07:10 |
June | 0.113960E+10 | 1182.92 | 08-JUN-15:00 | 0.339359E+10 | 2276.35 | 01-JUN-07:10 |
July | 0.107299E+10 | 1075.05 | 03-JUL-07:10 | 0.334669E+10 | 2276.35 | 03-JUL-07:10 |
August | 0.119575E+10 | 1075.05 | 01-AUG-07:10 | 0.352288E+10 | 2276.35 | 01-AUG-07:10 |
September | 0.108736E+10 | 1464.40 | 08-SEP-07:10 | 0.327931E+10 | 2276.35 | 01-SEP-07:10 |
October | 0.114549E+10 | 1443.57 | 25-OCT-07:10 | 0.339814E+10 | 2276.35 | 02-OCT-07:10 |
November | 0.117068E+10 | 1750.04 | 13-NOV-16:00 | 0.332029E+10 | 2276.35 | 01-NOV-07:10 |
December | 0.117316E+10 | 1750.04 | 01-DEC-16:00 | 0.334578E+10 | 2276.35 | 01-DEC-08:09 |
Annual Sum or Average | 0.136695E+11 | 0.403429E+11 | ||||
Minimum of Months | 0.105356E+10 | 1075.05 | 0.307490E+10 | 2276.35 | ||
Maximum of Months | 0.122292E+10 | 1750.04 | 0.352288E+10 | 2276.35 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.766307E+09 | 979.59 | 04-JAN-16:00 | 0.218926E+10 | 1466.94 | 02-JAN-08:09 |
February | 0.682199E+09 | 956.33 | 16-FEB-08:09 | 0.198154E+10 | 1466.94 | 01-FEB-08:09 |
March | 0.789471E+09 | 913.93 | 22-MAR-07:10 | 0.227023E+10 | 1466.94 | 01-MAR-08:09 |
April | 0.690856E+09 | 692.79 | 03-APR-07:10 | 0.211444E+10 | 1466.94 | 03-APR-07:10 |
May | 0.740153E+09 | 692.79 | 01-MAY-07:10 | 0.222974E+10 | 1466.94 | 01-MAY-07:10 |
June | 0.731039E+09 | 823.38 | 08-JUN-07:10 | 0.218691E+10 | 1466.94 | 01-JUN-07:10 |
July | 0.689339E+09 | 692.79 | 03-JUL-07:10 | 0.215669E+10 | 1466.94 | 03-JUL-07:10 |
August | 0.769376E+09 | 692.79 | 01-AUG-07:10 | 0.227023E+10 | 1466.94 | 01-AUG-07:10 |
September | 0.700481E+09 | 944.93 | 08-SEP-07:10 | 0.211327E+10 | 1466.94 | 01-SEP-07:10 |
October | 0.745584E+09 | 953.92 | 25-OCT-07:10 | 0.218984E+10 | 1466.94 | 02-OCT-07:10 |
November | 0.755780E+09 | 1127.77 | 13-NOV-16:00 | 0.213967E+10 | 1466.94 | 01-NOV-07:10 |
December | 0.761132E+09 | 1127.77 | 01-DEC-16:00 | 0.215610E+10 | 1466.94 | 01-DEC-08:09 |
Annual Sum or Average | 0.882172E+10 | 0.259979E+11 | ||||
Minimum of Months | 0.682199E+09 | 692.79 | 0.198154E+10 | 1466.94 | ||
Maximum of Months | 0.789471E+09 | 1127.77 | 0.227023E+10 | 1466.94 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.387117E+09 | 405.10 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.351144E+09 | 405.10 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.417256E+09 | 405.10 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.372695E+09 | 405.10 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.402187E+09 | 405.10 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.400242E+09 | 405.10 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.374640E+09 | 405.10 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.417256E+09 | 405.10 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.372695E+09 | 405.10 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.387117E+09 | 405.10 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.382580E+09 | 405.10 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.374640E+09 | 405.10 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.463957E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.351144E+09 | 405.10 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.417256E+09 | 405.10 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.387117E+09 | 405.10 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.351144E+09 | 405.10 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.417256E+09 | 405.10 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.372695E+09 | 405.10 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.402187E+09 | 405.10 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.400242E+09 | 405.10 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.374640E+09 | 405.10 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.417256E+09 | 405.10 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.372695E+09 | 405.10 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.387117E+09 | 405.10 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.382580E+09 | 405.10 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.374640E+09 | 405.10 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.463957E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.351144E+09 | 405.10 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.417256E+09 | 405.10 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.387117E+09 | 405.10 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.351144E+09 | 405.10 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.417256E+09 | 405.10 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.372695E+09 | 405.10 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.402187E+09 | 405.10 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.400242E+09 | 405.10 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.374640E+09 | 405.10 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.417256E+09 | 405.10 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.372695E+09 | 405.10 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.387117E+09 | 405.10 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.382580E+09 | 405.10 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.374640E+09 | 405.10 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.463957E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.351144E+09 | 405.10 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.417256E+09 | 405.10 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.418155E+10 | 4375.82 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.379298E+10 | 4375.82 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.450711E+10 | 4375.82 | 01-MAR-08:09 | 0.762947E+12 | 379632.52 | 31-MAR-23:10 |
April | 0.402577E+10 | 4375.82 | 03-APR-07:10 | 0.982982E+12 | 379632.52 | 01-APR-00:10 |
May | 0.434433E+10 | 4375.82 | 01-MAY-07:10 | 0.254544E+12 | 189816.26 | 31-MAY-23:10 |
June | 0.432333E+10 | 4375.82 | 01-JUN-07:10 | 0.492345E+12 | 284724.39 | 30-JUN-23:10 |
July | 0.404678E+10 | 4375.82 | 03-JUL-07:10 | 0.762947E+12 | 379632.52 | 31-JUL-23:10 |
August | 0.450711E+10 | 4375.82 | 01-AUG-07:10 | 0.101578E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.402577E+10 | 4375.82 | 01-SEP-07:10 | 0.246344E+12 | 189816.26 | 30-SEP-23:10 |
October | 0.418155E+10 | 4375.82 | 02-OCT-07:10 | 0.508746E+12 | 284724.39 | 31-OCT-23:10 |
November | 0.413254E+10 | 4375.82 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.404678E+10 | 4375.82 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.501156E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.379298E+10 | 4375.82 | 0.246344E+12 | 94908.13 | ||
Maximum of Months | 0.450711E+10 | 4375.82 | 0.101681E+13 | 379632.52 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.148304E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.134523E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.159851E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.142779E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.154078E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.153333E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.143524E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.159851E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.142779E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.148304E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.146566E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.143524E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.177742E+12 | 0.424397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121482E+11 | 0.134523E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.159851E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.133188E+11 | 0.270551E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.120811E+11 | 0.244881E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.143557E+11 | 0.280558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.128226E+11 | 0.261305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.138373E+11 | 0.275555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.137704E+11 | 0.270261E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.128895E+11 | 0.266527E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.143557E+11 | 0.280558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.128226E+11 | 0.261160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.133188E+11 | 0.270624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.131627E+11 | 0.264424E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.128895E+11 | 0.266454E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.159625E+12 | 0.321286E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.120811E+11 | 0.244881E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.143557E+11 | 0.280558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.133188E+11 | 0.270550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.120811E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.143557E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.128226E+11 | 0.261304E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.138373E+11 | 0.275554E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.137704E+11 | 0.270260E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.128895E+11 | 0.266526E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.143557E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.128226E+11 | 0.261159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.133188E+11 | 0.270623E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.131627E+11 | 0.264423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.128895E+11 | 0.266453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.159625E+12 | 0.321285E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.120811E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.143557E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.133188E+11 | 0.270550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.120811E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.143557E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.128226E+11 | 0.261304E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.138373E+11 | 0.275554E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.137704E+11 | 0.270260E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.128895E+11 | 0.266526E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.143557E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.128226E+11 | 0.261159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.133188E+11 | 0.270623E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.131627E+11 | 0.264423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.128895E+11 | 0.266453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.159625E+12 | 0.321285E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.120811E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.143557E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.120889E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.696878E+09 |
February | 0.136985E+10 | 0.106786E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.647388E+09 |
March | 0.163685E+10 | 0.122772E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.637650E+09 |
April | 0.145243E+10 | 0.107233E+10 | 0.328108E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1086923.37 | 0.451211E+09 |
May | 0.157338E+10 | 0.114790E+10 | 0.346000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10812871.06 | 0.307733E+09 |
June | 0.156900E+10 | 0.113152E+10 | 0.339353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51351047.06 | 0.160069E+09 |
July | 0.145680E+10 | 0.106733E+10 | 0.334664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72996688.66 | 82139133.66 |
August | 0.163685E+10 | 0.119245E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36376924.66 | 0.113013E+09 |
September | 0.145243E+10 | 0.108805E+10 | 0.327926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12544714.42 | 0.184798E+09 |
October | 0.150991E+10 | 0.116468E+10 | 0.339809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3012389.58 | 0.345657E+09 |
November | 0.149516E+10 | 0.119329E+10 | 0.332024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.565078E+09 |
December | 0.145680E+10 | 0.120531E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.654163E+09 |
Annual Sum or Average | 0.181194E+11 | 0.137673E+11 | 0.403423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188182E+09 | 0.484578E+10 |
Minimum of Months | 0.136985E+10 | 0.106733E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82139133.66 |
Maximum of Months | 0.163685E+10 | 0.122772E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72996688.66 | 0.696878E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.772310E+09 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.469739E+09 |
February | 0.882782E+09 | 0.685736E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.433090E+09 |
March | 0.105485E+10 | 0.790154E+09 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.423634E+09 |
April | 0.936002E+09 | 0.693167E+09 | 0.211446E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 752288.74 | 0.298239E+09 |
May | 0.101394E+10 | 0.743861E+09 | 0.222976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6873556.83 | 0.209153E+09 |
June | 0.101113E+10 | 0.732967E+09 | 0.218692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35306931.41 | 0.102733E+09 |
July | 0.938820E+09 | 0.690510E+09 | 0.215670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50217552.34 | 49733605.11 |
August | 0.105485E+10 | 0.770333E+09 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25588163.98 | 64697282.91 |
September | 0.936002E+09 | 0.701018E+09 | 0.211328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8273769.46 | 0.123762E+09 |
October | 0.973041E+09 | 0.744595E+09 | 0.218986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1963806.71 | 0.232101E+09 |
November | 0.963541E+09 | 0.767369E+09 | 0.213969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.376226E+09 |
December | 0.938820E+09 | 0.770224E+09 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.430783E+09 |
Annual Sum or Average | 0.116768E+11 | 0.886224E+10 | 0.259981E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128976E+09 | 0.321389E+10 |
Minimum of Months | 0.882782E+09 | 0.685736E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49733605.11 |
Maximum of Months | 0.105485E+10 | 0.790154E+09 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50217552.34 | 0.469739E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.117794E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.724852E+09 |
February | 0.136988E+10 | 0.105316E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.673205E+09 |
March | 0.163688E+10 | 0.122228E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.651739E+09 |
April | 0.145246E+10 | 0.107489E+10 | 0.328113E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1061427.83 | 0.460114E+09 |
May | 0.157341E+10 | 0.115381E+10 | 0.346006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9812407.29 | 0.308777E+09 |
June | 0.156904E+10 | 0.113885E+10 | 0.339359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52257810.32 | 0.156449E+09 |
July | 0.145684E+10 | 0.107248E+10 | 0.334669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72313901.54 | 81617109.05 |
August | 0.163688E+10 | 0.119536E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35546947.82 | 0.116124E+09 |
September | 0.145246E+10 | 0.108694E+10 | 0.327931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11271214.35 | 0.197534E+09 |
October | 0.150994E+10 | 0.114680E+10 | 0.339814E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2551257.72 | 0.367474E+09 |
November | 0.149520E+10 | 0.116997E+10 | 0.332029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.595009E+09 |
December | 0.145684E+10 | 0.117186E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.678527E+09 |
Annual Sum or Average | 0.181198E+11 | 0.136644E+11 | 0.403429E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184815E+09 | 0.501142E+10 |
Minimum of Months | 0.136988E+10 | 0.105316E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81617109.05 |
Maximum of Months | 0.163688E+10 | 0.122228E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72313901.54 | 0.724852E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.766024E+09 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.491400E+09 |
February | 0.882782E+09 | 0.681967E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.467146E+09 |
March | 0.105485E+10 | 0.789160E+09 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.469550E+09 |
April | 0.936002E+09 | 0.690699E+09 | 0.211444E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 702771.29 | 0.347001E+09 |
May | 0.101394E+10 | 0.740033E+09 | 0.222974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6001596.69 | 0.226516E+09 |
June | 0.101113E+10 | 0.730925E+09 | 0.218691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31726274.89 | 0.121471E+09 |
July | 0.938820E+09 | 0.689212E+09 | 0.215669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44831015.21 | 66878223.40 |
August | 0.105485E+10 | 0.769192E+09 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22580720.05 | 97026712.47 |
September | 0.936002E+09 | 0.700258E+09 | 0.211327E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7792589.48 | 0.139441E+09 |
October | 0.973041E+09 | 0.745412E+09 | 0.218984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1824430.91 | 0.256284E+09 |
November | 0.963541E+09 | 0.755448E+09 | 0.213967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.417346E+09 |
December | 0.938820E+09 | 0.760917E+09 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.489272E+09 |
Annual Sum or Average | 0.116768E+11 | 0.881925E+10 | 0.259979E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115459E+09 | 0.358933E+10 |
Minimum of Months | 0.882782E+09 | 0.681967E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66878223.40 |
Maximum of Months | 0.105485E+10 | 0.789160E+09 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44831015.21 | 0.491400E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.121095E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142847E+10 |
February | 0.136985E+10 | 0.106920E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133907E+10 |
March | 0.163685E+10 | 0.122875E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132825E+10 |
April | 0.145243E+10 | 0.107250E+10 | 0.328108E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2724439.01 | 0.965992E+09 |
May | 0.157338E+10 | 0.114808E+10 | 0.346000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26564939.50 | 0.678916E+09 |
June | 0.156900E+10 | 0.113200E+10 | 0.339353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117418E+09 | 0.370136E+09 |
July | 0.145680E+10 | 0.106754E+10 | 0.334664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168054E+09 | 0.212825E+09 |
August | 0.163685E+10 | 0.119246E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 87444979.19 | 0.275995E+09 |
September | 0.145243E+10 | 0.108860E+10 | 0.327926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29657000.78 | 0.407291E+09 |
October | 0.150991E+10 | 0.116588E+10 | 0.339809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7220559.86 | 0.728435E+09 |
November | 0.149516E+10 | 0.119476E+10 | 0.332024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114808E+10 |
December | 0.145680E+10 | 0.120723E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130935E+10 |
Annual Sum or Average | 0.181194E+11 | 0.137779E+11 | 0.403423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.439084E+09 | 0.101928E+11 |
Minimum of Months | 0.136985E+10 | 0.106754E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212825E+09 |
Maximum of Months | 0.163685E+10 | 0.122875E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168054E+09 | 0.142847E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.772521E+09 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.984907E+09 |
February | 0.649041E+09 | 0.686059E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.923683E+09 |
March | 0.773965E+09 | 0.790455E+09 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.923735E+09 |
April | 0.688021E+09 | 0.693254E+09 | 0.211446E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1593258.32 | 0.696172E+09 |
May | 0.744847E+09 | 0.743954E+09 | 0.222976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14990031.96 | 0.479471E+09 |
June | 0.742030E+09 | 0.733162E+09 | 0.218692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77810554.09 | 0.251505E+09 |
July | 0.690839E+09 | 0.690661E+09 | 0.215670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109725E+09 | 0.151730E+09 |
August | 0.773965E+09 | 0.770406E+09 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56462101.75 | 0.196192E+09 |
September | 0.688021E+09 | 0.701198E+09 | 0.211328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18634861.59 | 0.285182E+09 |
October | 0.715730E+09 | 0.744734E+09 | 0.218986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4325660.64 | 0.514707E+09 |
November | 0.708685E+09 | 0.767665E+09 | 0.213969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.798876E+09 |
December | 0.690839E+09 | 0.770454E+09 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.898250E+09 |
Annual Sum or Average | 0.858171E+10 | 0.886452E+10 | 0.259981E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.283541E+09 | 0.710441E+10 |
Minimum of Months | 0.649041E+09 | 0.686059E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151730E+09 |
Maximum of Months | 0.773965E+09 | 0.790455E+09 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109725E+09 | 0.984907E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.117858E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162667E+10 |
February | 0.136988E+10 | 0.105357E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151458E+10 |
March | 0.163688E+10 | 0.122292E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145616E+10 |
April | 0.145246E+10 | 0.107527E+10 | 0.328113E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2195548.81 | 0.104001E+10 |
May | 0.157341E+10 | 0.115415E+10 | 0.346006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21825533.59 | 0.698158E+09 |
June | 0.156904E+10 | 0.113959E+10 | 0.339359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118841E+09 | 0.365340E+09 |
July | 0.145684E+10 | 0.107299E+10 | 0.334669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164560E+09 | 0.215924E+09 |
August | 0.163688E+10 | 0.119575E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 81940937.36 | 0.295548E+09 |
September | 0.145246E+10 | 0.108735E+10 | 0.327931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24730648.06 | 0.456660E+09 |
October | 0.150994E+10 | 0.114550E+10 | 0.339814E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5200321.17 | 0.840208E+09 |
November | 0.149520E+10 | 0.117067E+10 | 0.332029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133415E+10 |
December | 0.145684E+10 | 0.117314E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150179E+10 |
Annual Sum or Average | 0.181198E+11 | 0.136695E+11 | 0.403429E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.419294E+09 | 0.113452E+11 |
Minimum of Months | 0.136988E+10 | 0.105357E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215924E+09 |
Maximum of Months | 0.163688E+10 | 0.122292E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164560E+09 | 0.162667E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.766288E+09 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101058E+10 |
February | 0.882782E+09 | 0.682192E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.953315E+09 |
March | 0.105485E+10 | 0.789462E+09 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.949919E+09 |
April | 0.936002E+09 | 0.690850E+09 | 0.211444E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1450114.19 | 0.716272E+09 |
May | 0.101394E+10 | 0.740148E+09 | 0.222974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13890418.40 | 0.491365E+09 |
June | 0.101113E+10 | 0.731036E+09 | 0.218691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73905583.69 | 0.269648E+09 |
July | 0.938820E+09 | 0.689338E+09 | 0.215669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107365E+09 | 0.159716E+09 |
August | 0.105485E+10 | 0.769371E+09 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54428517.05 | 0.210675E+09 |
September | 0.936002E+09 | 0.700434E+09 | 0.211327E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17899362.66 | 0.302476E+09 |
October | 0.973041E+09 | 0.745569E+09 | 0.218984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4161374.20 | 0.530923E+09 |
November | 0.963541E+09 | 0.755768E+09 | 0.213967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.822371E+09 |
December | 0.938820E+09 | 0.761116E+09 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.931728E+09 |
Annual Sum or Average | 0.116768E+11 | 0.882157E+10 | 0.259979E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273100E+09 | 0.734899E+10 |
Minimum of Months | 0.882782E+09 | 0.682192E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159716E+09 |
Maximum of Months | 0.105485E+10 | 0.789462E+09 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107365E+09 | 0.101058E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.121098E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162500E+10 |
February | 0.136985E+10 | 0.106916E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153802E+10 |
March | 0.163685E+10 | 0.122881E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151841E+10 |
April | 0.145243E+10 | 0.107250E+10 | 0.328108E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3055896.81 | 0.113198E+10 |
May | 0.157338E+10 | 0.114808E+10 | 0.346000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28805739.16 | 0.814673E+09 |
June | 0.156900E+10 | 0.113200E+10 | 0.339353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138433E+09 | 0.456466E+09 |
July | 0.145680E+10 | 0.106754E+10 | 0.334664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197171E+09 | 0.271619E+09 |
August | 0.163685E+10 | 0.119246E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100685E+09 | 0.348522E+09 |
September | 0.145243E+10 | 0.108860E+10 | 0.327926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34242298.31 | 0.496810E+09 |
October | 0.150991E+10 | 0.116590E+10 | 0.339809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8115209.76 | 0.841307E+09 |
November | 0.149516E+10 | 0.119478E+10 | 0.332024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128073E+10 |
December | 0.145680E+10 | 0.120727E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147523E+10 |
Annual Sum or Average | 0.181194E+11 | 0.137781E+11 | 0.403423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.510509E+09 | 0.117988E+11 |
Minimum of Months | 0.136985E+10 | 0.106754E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.271619E+09 |
Maximum of Months | 0.163685E+10 | 0.122881E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197171E+09 | 0.162500E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.772539E+09 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111753E+10 |
February | 0.882782E+09 | 0.686071E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106197E+10 |
March | 0.105485E+10 | 0.790460E+09 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107251E+10 |
April | 0.936002E+09 | 0.693257E+09 | 0.211446E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1663845.42 | 0.834172E+09 |
May | 0.101394E+10 | 0.743955E+09 | 0.222976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16561152.82 | 0.585417E+09 |
June | 0.101113E+10 | 0.733166E+09 | 0.218692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 91791554.35 | 0.312801E+09 |
July | 0.938820E+09 | 0.690661E+09 | 0.215670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129994E+09 | 0.193294E+09 |
August | 0.105485E+10 | 0.770421E+09 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66166132.84 | 0.248634E+09 |
September | 0.936002E+09 | 0.701204E+09 | 0.211328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21724461.19 | 0.351244E+09 |
October | 0.973041E+09 | 0.744749E+09 | 0.218986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4924541.09 | 0.607443E+09 |
November | 0.963541E+09 | 0.767689E+09 | 0.213969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.899135E+09 |
December | 0.938820E+09 | 0.770513E+09 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101095E+10 |
Annual Sum or Average | 0.116768E+11 | 0.886469E+10 | 0.259981E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.332826E+09 | 0.829510E+10 |
Minimum of Months | 0.882782E+09 | 0.686071E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193294E+09 |
Maximum of Months | 0.105485E+10 | 0.790460E+09 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129994E+09 | 0.111753E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.117859E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184906E+10 |
February | 0.136988E+10 | 0.105356E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174514E+10 |
March | 0.163688E+10 | 0.122292E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169226E+10 |
April | 0.145246E+10 | 0.107527E+10 | 0.328113E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2365356.48 | 0.123107E+10 |
May | 0.157341E+10 | 0.115416E+10 | 0.346006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24710240.79 | 0.838612E+09 |
June | 0.156904E+10 | 0.113960E+10 | 0.339359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141080E+09 | 0.447772E+09 |
July | 0.145684E+10 | 0.107299E+10 | 0.334669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196163E+09 | 0.273162E+09 |
August | 0.163688E+10 | 0.119575E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 97285112.92 | 0.372125E+09 |
September | 0.145246E+10 | 0.108736E+10 | 0.327931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29821168.25 | 0.559969E+09 |
October | 0.150994E+10 | 0.114549E+10 | 0.339814E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6542931.92 | 0.994699E+09 |
November | 0.149520E+10 | 0.117068E+10 | 0.332029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152153E+10 |
December | 0.145684E+10 | 0.117316E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170223E+10 |
Annual Sum or Average | 0.181198E+11 | 0.136695E+11 | 0.403429E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.497968E+09 | 0.132276E+11 |
Minimum of Months | 0.136988E+10 | 0.105356E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273162E+09 |
Maximum of Months | 0.163688E+10 | 0.122292E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196163E+09 | 0.184906E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.766307E+09 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115618E+10 |
February | 0.882782E+09 | 0.682199E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110683E+10 |
March | 0.105485E+10 | 0.789471E+09 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110842E+10 |
April | 0.936002E+09 | 0.690856E+09 | 0.211444E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1565830.47 | 0.854214E+09 |
May | 0.101394E+10 | 0.740153E+09 | 0.222974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16365372.23 | 0.593352E+09 |
June | 0.101113E+10 | 0.731039E+09 | 0.218691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 89170547.12 | 0.332544E+09 |
July | 0.938820E+09 | 0.689339E+09 | 0.215669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128817E+09 | 0.200139E+09 |
August | 0.105485E+10 | 0.769376E+09 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64970890.61 | 0.264053E+09 |
September | 0.936002E+09 | 0.700481E+09 | 0.211327E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21441691.21 | 0.370439E+09 |
October | 0.973041E+09 | 0.745584E+09 | 0.218984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4845589.37 | 0.628188E+09 |
November | 0.963541E+09 | 0.755780E+09 | 0.213967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.937632E+09 |
December | 0.938820E+09 | 0.761132E+09 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106249E+10 |
Annual Sum or Average | 0.116768E+11 | 0.882172E+10 | 0.259979E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.327177E+09 | 0.861448E+10 |
Minimum of Months | 0.882782E+09 | 0.682199E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200139E+09 |
Maximum of Months | 0.105485E+10 | 0.789471E+09 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128817E+09 | 0.115618E+10 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.387117E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.351144E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.417256E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.372695E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.402187E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.400242E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.374640E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.417256E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.372695E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.387117E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.382580E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.374640E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.463957E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.351144E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.417256E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.387117E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.351144E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.417256E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.372695E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.402187E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.400242E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.374640E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.417256E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.372695E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.387117E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.382580E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.374640E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.463957E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.351144E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.417256E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.387117E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.351144E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.417256E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.372695E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.402187E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.400242E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.374640E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.417256E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.372695E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.387117E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.382580E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.374640E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.463957E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.351144E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.417256E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.377547E+10 | 0.418155E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.342526E+10 | 0.379298E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409289E+10 | 0.450711E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363176E+10 | 0.402577E+10 | 0.982982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.393418E+10 | 0.434433E+10 | 0.254544E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.392325E+10 | 0.432333E+10 | 0.492345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.364269E+10 | 0.404678E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.409289E+10 | 0.450711E+10 | 0.101578E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.363176E+10 | 0.402577E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.377547E+10 | 0.418155E+10 | 0.508746E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373861E+10 | 0.413254E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364269E+10 | 0.404678E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453069E+11 | 0.501156E+11 | 0.749486E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.342526E+10 | 0.379298E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.409289E+10 | 0.450711E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151112E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139387E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135798E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 824441.19 | 0.962872E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18279982.42 | 0.646984E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96696087.57 | 0.337514E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140218E+09 | 0.180435E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65219142.73 | 0.253007E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20311888.40 | 0.390758E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3793375.23 | 0.744057E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121922E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140937E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.345343E+09 | 0.104072E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180435E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140218E+09 | 0.151112E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254554E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237280E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.232593E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1681591.73 | 0.166032E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34902315.09 | 0.113608E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174505E+09 | 0.598681E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254706E+09 | 0.329051E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122817E+09 | 0.449015E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37312730.56 | 0.685492E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7247126.51 | 0.128708E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207285E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234993E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.633172E+09 | 0.178128E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.329051E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254706E+09 | 0.254554E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254968E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.244608E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246659E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62491.97 | 0.185513E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18222798.30 | 0.128815E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154718E+09 | 0.686143E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222353E+09 | 0.399810E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103310E+09 | 0.535277E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25549832.60 | 0.786398E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3602566.06 | 0.137604E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210481E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233877E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.527819E+09 | 0.188329E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.399810E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222353E+09 | 0.254968E+10 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 15519.45 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 15519.45 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 15519.45 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 15519.45 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 15519.45 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 15519.45 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 15519.45 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 15519.45 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 15519.45 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 15519.45 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 15519.45 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 15519.45 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 17832.21 | 15519.45 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 15519.45 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 13937.56 | 02-JAN-08:09 | 18128.59 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 13937.56 | 01-FEB-08:09 | 18128.59 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 13937.56 | 01-MAR-08:09 | 18128.59 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 13937.56 | 03-APR-07:10 | 18128.59 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 13937.56 | 01-MAY-07:10 | 18128.59 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 13937.56 | 01-JUN-07:10 | 18128.59 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 13937.56 | 03-JUL-07:10 | 18128.59 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 13937.56 | 01-AUG-07:10 | 18128.59 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 13937.56 | 01-SEP-07:10 | 18128.59 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 13937.56 | 02-OCT-07:10 | 18128.59 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 13937.56 | 01-NOV-07:10 | 18128.59 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 13937.56 | 01-DEC-08:09 | 18128.59 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 13937.56 | 18128.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 13937.56 | 18128.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 13937.56 | 02-JAN-08:09 | 18128.52 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 13937.56 | 01-FEB-08:09 | 18128.52 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 13937.56 | 01-MAR-08:09 | 18128.52 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 13937.56 | 03-APR-07:10 | 18128.52 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 13937.56 | 01-MAY-07:10 | 18128.52 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 13937.56 | 01-JUN-07:10 | 18128.52 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 13937.56 | 03-JUL-07:10 | 18128.52 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 13937.56 | 01-AUG-07:10 | 18128.52 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 13937.56 | 01-SEP-07:10 | 18128.52 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 13937.56 | 02-OCT-07:10 | 18128.52 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 13937.56 | 01-NOV-07:10 | 18128.52 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 13937.56 | 01-DEC-08:09 | 18128.52 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 13937.56 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 13937.56 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 13937.56 | 02-JAN-08:09 | 18128.52 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 13937.56 | 01-FEB-08:09 | 18128.52 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 13937.56 | 01-MAR-08:09 | 18128.52 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 13937.56 | 03-APR-07:10 | 18128.52 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 13937.56 | 01-MAY-07:10 | 18128.52 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 13937.56 | 01-JUN-07:10 | 18128.52 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 13937.56 | 03-JUL-07:10 | 18128.52 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 13937.56 | 01-AUG-07:10 | 18128.52 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 13937.56 | 01-SEP-07:10 | 18128.52 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 13937.56 | 02-OCT-07:10 | 18128.52 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 13937.56 | 01-NOV-07:10 | 18128.52 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 13937.56 | 01-DEC-08:09 | 18128.52 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 13937.56 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 13937.56 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1619.54 | 09-JAN-16:00 | 2276.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1994.36 | 16-JAN-18:00 |
February | 2010.79 | 01-FEB-10:09 | 1478.68 | 16-FEB-08:09 | 2276.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1506.37 | 05-FEB-01:00 |
March | 2010.79 | 01-MAR-10:09 | 1341.29 | 20-MAR-07:10 | 2276.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1354.91 | 14-MAR-03:00 |
April | 2010.79 | 03-APR-09:09 | 1075.02 | 03-APR-07:10 | 2276.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.39 | 29-APR-16:00 | 1475.75 | 07-APR-22:00 |
May | 2010.79 | 01-MAY-09:09 | 1075.02 | 01-MAY-07:10 | 2276.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 149.01 | 14-MAY-17:00 | 913.18 | 03-MAY-22:00 |
June | 2010.79 | 01-JUN-09:09 | 1075.02 | 01-JUN-07:10 | 2276.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 377.16 | 18-JUN-15:51 | 704.16 | 10-JUN-01:00 |
July | 2010.79 | 03-JUL-09:09 | 1075.02 | 03-JUL-07:10 | 2276.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 510.91 | 04-JUL-14:51 | 305.96 | 15-JUL-19:00 |
August | 2010.79 | 01-AUG-09:09 | 1075.02 | 01-AUG-07:10 | 2276.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 245.98 | 20-AUG-16:51 | 369.60 | 22-AUG-21:50 |
September | 2010.79 | 01-SEP-09:09 | 1458.04 | 08-SEP-07:10 | 2276.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 165.60 | 03-SEP-14:27 | 529.91 | 18-SEP-00:55 |
October | 2010.79 | 02-OCT-09:09 | 1458.66 | 25-OCT-07:10 | 2276.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.05 | 01-OCT-16:00 | 842.11 | 11-OCT-23:00 |
November | 2010.79 | 01-NOV-09:09 | 1750.00 | 13-NOV-16:00 | 2276.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1519.90 | 26-NOV-06:00 |
December | 2010.79 | 01-DEC-10:09 | 1750.00 | 01-DEC-16:00 | 2276.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2132.12 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 305.96 | |||||
Maximum of Months | 2010.79 | 1750.00 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 510.91 | 2132.12 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1044.15 | 09-JAN-16:00 | 1466.95 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1334.64 | 16-JAN-18:00 |
February | 1295.83 | 01-FEB-10:09 | 941.83 | 16-FEB-08:09 | 1466.95 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1010.49 | 05-FEB-01:00 |
March | 1295.83 | 01-MAR-10:09 | 820.15 | 14-MAR-15:00 | 1466.95 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 899.14 | 14-MAR-03:00 |
April | 1295.83 | 03-APR-09:09 | 692.79 | 03-APR-07:10 | 1466.95 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.59 | 29-APR-16:00 | 969.94 | 07-APR-22:00 |
May | 1295.83 | 01-MAY-09:09 | 692.79 | 01-MAY-07:10 | 1466.95 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 104.17 | 14-MAY-17:00 | 599.83 | 03-MAY-22:00 |
June | 1295.83 | 01-JUN-09:09 | 692.79 | 01-JUN-07:10 | 1466.95 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 269.91 | 18-JUN-16:20 | 461.96 | 10-JUN-01:00 |
July | 1295.83 | 03-JUL-09:09 | 692.79 | 03-JUL-07:10 | 1466.95 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 350.30 | 04-JUL-14:51 | 194.54 | 15-JUL-18:43 |
August | 1295.83 | 01-AUG-09:09 | 692.79 | 01-AUG-07:10 | 1466.95 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 185.69 | 05-AUG-17:10 | 281.02 | 27-AUG-07:40 |
September | 1295.83 | 01-SEP-09:09 | 930.85 | 08-SEP-07:10 | 1466.95 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 119.10 | 03-SEP-14:25 | 363.76 | 18-SEP-00:55 |
October | 1295.83 | 02-OCT-09:09 | 902.28 | 25-OCT-07:10 | 1466.95 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.74 | 01-OCT-16:20 | 556.59 | 11-OCT-23:00 |
November | 1295.83 | 01-NOV-09:09 | 1127.77 | 13-NOV-16:00 | 1466.95 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 997.18 | 26-NOV-06:00 |
December | 1295.83 | 01-DEC-10:09 | 1127.77 | 01-DEC-16:00 | 1466.95 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1396.08 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 194.54 | |||||
Maximum of Months | 1295.83 | 1127.77 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 350.30 | 1396.08 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1542.62 | 04-JAN-16:00 | 2276.35 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1972.35 | 16-JAN-18:00 |
February | 2010.83 | 01-FEB-10:09 | 1468.05 | 16-FEB-08:09 | 2276.35 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1565.26 | 05-FEB-01:00 |
March | 2010.83 | 01-MAR-10:09 | 1320.24 | 20-MAR-07:10 | 2276.35 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1376.27 | 14-MAR-03:00 |
April | 2010.83 | 03-APR-09:09 | 1075.05 | 03-APR-07:10 | 2276.35 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.39 | 29-APR-16:00 | 1490.47 | 07-APR-22:00 |
May | 2010.83 | 01-MAY-09:09 | 1075.05 | 01-MAY-07:10 | 2276.35 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 136.65 | 14-MAY-17:00 | 898.52 | 03-MAY-22:00 |
June | 2010.83 | 01-JUN-09:09 | 1075.05 | 01-JUN-07:10 | 2276.35 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 380.51 | 18-JUN-16:14 | 689.14 | 10-JUN-01:00 |
July | 2010.83 | 03-JUL-09:09 | 1075.05 | 03-JUL-07:10 | 2276.35 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 501.52 | 04-JUL-14:51 | 309.76 | 15-JUL-19:00 |
August | 2010.83 | 01-AUG-09:09 | 1075.05 | 01-AUG-07:10 | 2276.35 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 244.31 | 20-AUG-16:51 | 382.99 | 22-AUG-21:50 |
September | 2010.83 | 01-SEP-09:09 | 1455.86 | 08-SEP-07:10 | 2276.35 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 157.75 | 03-SEP-14:25 | 568.47 | 18-SEP-00:55 |
October | 2010.83 | 02-OCT-09:09 | 1434.14 | 25-OCT-07:10 | 2276.35 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.89 | 11-OCT-14:00 | 868.70 | 11-OCT-23:00 |
November | 2010.83 | 01-NOV-09:09 | 1750.04 | 13-NOV-16:00 | 2276.35 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1530.46 | 03-NOV-24:00 |
December | 2010.83 | 01-DEC-10:09 | 1750.04 | 01-DEC-16:00 | 2276.35 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2170.37 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1075.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 309.76 | |||||
Maximum of Months | 2010.83 | 1750.04 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 501.52 | 2170.37 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 976.97 | 04-JAN-16:00 | 1466.94 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1397.65 | 16-JAN-18:00 |
February | 1295.83 | 01-FEB-10:09 | 955.18 | 16-FEB-08:09 | 1466.94 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1103.87 | 05-FEB-01:00 |
March | 1295.83 | 01-MAR-10:09 | 912.47 | 22-MAR-07:10 | 1466.94 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1011.32 | 14-MAR-03:00 |
April | 1295.83 | 03-APR-09:09 | 692.79 | 03-APR-07:10 | 1466.94 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.59 | 29-APR-16:00 | 1119.11 | 07-APR-22:00 |
May | 1295.83 | 01-MAY-09:09 | 692.79 | 01-MAY-07:10 | 1466.94 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 85.32 | 14-MAY-16:55 | 666.72 | 18-MAY-02:50 |
June | 1295.83 | 01-JUN-09:09 | 821.54 | 08-JUN-07:10 | 1466.94 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 235.40 | 18-JUN-16:00 | 554.55 | 10-JUN-01:00 |
July | 1295.83 | 03-JUL-09:09 | 692.79 | 03-JUL-07:10 | 1466.94 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 329.94 | 04-JUL-15:00 | 239.86 | 15-JUL-18:43 |
August | 1295.83 | 01-AUG-09:09 | 692.79 | 01-AUG-07:10 | 1466.94 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 156.23 | 20-AUG-16:46 | 349.61 | 22-AUG-21:50 |
September | 1295.83 | 01-SEP-09:09 | 943.72 | 08-SEP-07:10 | 1466.94 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 124.14 | 03-SEP-15:08 | 404.64 | 18-SEP-00:55 |
October | 1295.83 | 02-OCT-09:09 | 952.72 | 25-OCT-07:10 | 1466.94 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.12 | 11-OCT-13:00 | 619.26 | 11-OCT-23:00 |
November | 1295.83 | 01-NOV-09:09 | 1127.77 | 13-NOV-16:00 | 1466.94 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1115.73 | 03-NOV-24:00 |
December | 1295.83 | 01-DEC-10:09 | 1127.77 | 01-DEC-16:00 | 1466.94 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1588.70 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 692.79 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 239.86 | |||||
Maximum of Months | 1295.83 | 1127.77 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 329.94 | 1588.70 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1624.66 | 09-JAN-16:00 | 2276.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3786.32 | 16-JAN-18:00 |
February | 2010.79 | 01-FEB-10:09 | 1486.80 | 16-FEB-08:09 | 2276.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3006.83 | 05-FEB-01:00 |
March | 2010.79 | 01-MAR-10:09 | 1353.52 | 20-MAR-07:10 | 2276.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2678.24 | 14-MAR-03:00 |
April | 2010.79 | 03-APR-09:09 | 1075.02 | 03-APR-07:10 | 2276.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 110.61 | 01-APR-17:01 | 3090.74 | 07-APR-22:00 |
May | 2010.79 | 01-MAY-09:09 | 1075.02 | 01-MAY-07:10 | 2276.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 355.25 | 14-MAY-16:50 | 1975.52 | 03-MAY-22:00 |
June | 2010.79 | 01-JUN-09:09 | 1181.89 | 08-JUN-15:00 | 2276.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 847.24 | 18-JUN-15:53 | 1486.72 | 10-JUN-01:00 |
July | 2010.79 | 03-JUL-09:09 | 1075.02 | 03-JUL-07:10 | 2276.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1127.35 | 04-JUL-14:51 | 831.33 | 15-JUL-18:53 |
August | 2010.79 | 01-AUG-09:09 | 1075.02 | 01-AUG-07:10 | 2276.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 622.52 | 05-AUG-17:01 | 801.44 | 08-AUG-00:52 |
September | 2010.79 | 01-SEP-09:09 | 1466.81 | 08-SEP-07:10 | 2276.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 395.48 | 03-SEP-14:50 | 1094.16 | 07-SEP-22:00 |
October | 2010.79 | 02-OCT-09:09 | 1467.31 | 25-OCT-07:10 | 2276.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 213.62 | 01-OCT-16:10 | 1835.60 | 11-OCT-23:00 |
November | 2010.79 | 01-NOV-09:09 | 1750.00 | 13-NOV-16:00 | 2276.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3127.10 | 03-NOV-21:03 |
December | 2010.79 | 01-DEC-10:09 | 1750.00 | 01-DEC-16:00 | 2276.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4155.92 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 801.44 | |||||
Maximum of Months | 2010.79 | 1750.00 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 1127.35 | 4155.92 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 1046.38 | 09-JAN-16:00 | 1466.95 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2581.33 | 16-JAN-18:00 |
February | 1239.33 | 01-FEB-08:09 | 943.53 | 16-FEB-08:09 | 1466.95 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2062.79 | 05-FEB-01:00 |
March | 1239.33 | 01-MAR-08:09 | 822.32 | 14-MAR-15:00 | 1466.95 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1854.04 | 14-MAR-03:00 |
April | 1239.33 | 03-APR-07:10 | 692.79 | 03-APR-07:10 | 1466.95 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.45 | 29-APR-16:00 | 2105.53 | 23-APR-09:10 |
May | 1239.33 | 01-MAY-07:10 | 692.79 | 01-MAY-07:10 | 1466.95 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 217.70 | 14-MAY-17:10 | 1307.11 | 03-MAY-22:00 |
June | 1239.33 | 01-JUN-07:10 | 760.79 | 08-JUN-15:00 | 1466.95 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 606.48 | 18-JUN-15:44 | 1012.64 | 04-JUN-16:53 |
July | 1239.33 | 03-JUL-07:10 | 692.79 | 03-JUL-07:10 | 1466.95 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 758.20 | 04-JUL-15:03 | 598.66 | 15-JUL-18:53 |
August | 1239.33 | 01-AUG-07:10 | 692.79 | 01-AUG-07:10 | 1466.95 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 417.26 | 05-AUG-17:01 | 666.89 | 27-AUG-07:40 |
September | 1239.33 | 01-SEP-07:10 | 932.71 | 08-SEP-07:10 | 1466.95 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 282.95 | 03-SEP-14:25 | 777.77 | 18-SEP-00:55 |
October | 1239.33 | 02-OCT-07:10 | 905.08 | 25-OCT-07:10 | 1466.95 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 114.46 | 01-OCT-16:10 | 1231.68 | 11-OCT-23:00 |
November | 1239.33 | 01-NOV-07:10 | 1127.77 | 13-NOV-16:00 | 1466.95 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2069.26 | 03-NOV-21:03 |
December | 1239.33 | 01-DEC-08:09 | 1127.77 | 01-DEC-16:00 | 1466.95 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2809.10 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1239.33 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 598.66 | |||||
Maximum of Months | 1239.33 | 1127.77 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 758.20 | 2809.10 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1549.95 | 04-JAN-16:00 | 2276.35 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 4220.99 | 16-JAN-18:00 |
February | 2010.83 | 01-FEB-10:09 | 1476.62 | 16-FEB-08:09 | 2276.35 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3393.21 | 05-FEB-01:00 |
March | 2010.83 | 01-MAR-10:09 | 1333.36 | 20-MAR-07:10 | 2276.35 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2900.65 | 14-MAR-03:00 |
April | 2010.83 | 03-APR-09:09 | 1075.05 | 03-APR-07:10 | 2276.35 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.68 | 29-APR-16:00 | 3215.77 | 07-APR-22:00 |
May | 2010.83 | 01-MAY-09:09 | 1075.05 | 01-MAY-07:10 | 2276.35 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 281.28 | 14-MAY-17:10 | 1961.37 | 03-MAY-22:00 |
June | 2010.83 | 01-JUN-09:09 | 1183.56 | 08-JUN-15:00 | 2276.35 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 854.18 | 18-JUN-15:44 | 1474.84 | 10-JUN-01:00 |
July | 2010.83 | 03-JUL-09:09 | 1075.05 | 03-JUL-07:10 | 2276.35 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1121.04 | 04-JUL-14:51 | 858.37 | 15-JUL-18:53 |
August | 2010.83 | 01-AUG-09:09 | 1075.05 | 01-AUG-07:10 | 2276.35 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 580.17 | 20-AUG-16:51 | 842.81 | 08-AUG-00:52 |
September | 2010.83 | 01-SEP-09:09 | 1464.71 | 08-SEP-07:10 | 2276.35 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 364.60 | 03-SEP-14:25 | 1273.56 | 17-SEP-20:00 |
October | 2010.83 | 02-OCT-09:09 | 1443.83 | 25-OCT-07:10 | 2276.35 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 135.40 | 11-OCT-14:30 | 1928.26 | 11-OCT-23:00 |
November | 2010.83 | 01-NOV-09:09 | 1750.04 | 13-NOV-16:00 | 2276.35 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3393.86 | 03-NOV-21:03 |
December | 2010.83 | 01-DEC-10:09 | 1750.04 | 01-DEC-16:00 | 2276.35 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4537.46 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1075.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 842.81 | |||||
Maximum of Months | 2010.83 | 1750.04 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 1121.04 | 4537.46 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 979.60 | 04-JAN-16:00 | 1466.94 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2694.58 | 16-JAN-18:00 |
February | 1295.83 | 01-FEB-10:09 | 956.50 | 16-FEB-08:09 | 1466.94 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2177.43 | 05-FEB-01:00 |
March | 1295.83 | 01-MAR-10:09 | 914.03 | 22-MAR-07:10 | 1466.94 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1884.28 | 14-MAR-03:00 |
April | 1295.83 | 03-APR-09:09 | 692.79 | 03-APR-07:10 | 1466.94 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.45 | 29-APR-16:00 | 2332.17 | 15-APR-17:07 |
May | 1295.83 | 01-MAY-09:09 | 692.79 | 01-MAY-07:10 | 1466.94 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 145.50 | 14-MAY-17:05 | 1372.14 | 18-MAY-02:00 |
June | 1295.83 | 01-JUN-09:09 | 823.62 | 08-JUN-07:10 | 1466.94 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 541.11 | 18-JUN-16:00 | 1098.48 | 10-JUN-01:00 |
July | 1295.83 | 03-JUL-09:09 | 692.79 | 03-JUL-07:10 | 1466.94 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 743.71 | 04-JUL-15:03 | 625.16 | 15-JUL-18:53 |
August | 1295.83 | 01-AUG-09:09 | 692.79 | 01-AUG-07:10 | 1466.94 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 386.03 | 20-AUG-17:00 | 629.93 | 08-AUG-00:52 |
September | 1295.83 | 01-SEP-09:09 | 945.12 | 08-SEP-07:10 | 1466.94 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 272.41 | 03-SEP-14:25 | 865.89 | 17-SEP-20:00 |
October | 1295.83 | 02-OCT-09:09 | 954.08 | 25-OCT-07:10 | 1466.94 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 99.31 | 11-OCT-13:00 | 1286.41 | 11-OCT-23:00 |
November | 1295.83 | 01-NOV-09:09 | 1127.77 | 13-NOV-16:00 | 1466.94 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2177.91 | 03-NOV-21:10 |
December | 1295.83 | 01-DEC-10:09 | 1127.77 | 01-DEC-16:00 | 1466.94 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2905.93 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 692.79 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 625.16 | |||||
Maximum of Months | 1295.83 | 1127.77 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 743.71 | 2905.93 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1624.81 | 09-JAN-16:00 | 2276.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 4431.66 | 16-JAN-18:00 |
February | 2010.79 | 01-FEB-10:09 | 1486.51 | 16-FEB-08:09 | 2276.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3498.20 | 05-FEB-01:27 |
March | 2010.79 | 01-MAR-10:09 | 1353.17 | 20-MAR-07:10 | 2276.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3216.44 | 14-MAR-05:00 |
April | 2010.79 | 03-APR-09:09 | 1075.02 | 03-APR-07:10 | 2276.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 147.97 | 01-APR-17:01 | 3598.18 | 07-APR-22:00 |
May | 2010.79 | 01-MAY-09:09 | 1075.02 | 01-MAY-07:10 | 2276.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 338.43 | 14-MAY-17:00 | 2314.52 | 03-MAY-22:00 |
June | 2010.79 | 01-JUN-09:09 | 1181.26 | 08-JUN-15:00 | 2276.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1065.59 | 18-JUN-15:54 | 1799.44 | 04-JUN-16:53 |
July | 2010.79 | 03-JUL-09:09 | 1075.02 | 03-JUL-07:10 | 2276.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1367.89 | 04-JUL-14:51 | 1063.78 | 15-JUL-18:53 |
August | 2010.79 | 01-AUG-09:09 | 1075.02 | 01-AUG-07:10 | 2276.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 708.73 | 20-AUG-16:51 | 1001.00 | 08-AUG-00:52 |
September | 2010.79 | 01-SEP-09:09 | 1466.50 | 08-SEP-07:10 | 2276.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 467.06 | 03-SEP-14:50 | 1301.91 | 07-SEP-22:00 |
October | 2010.79 | 02-OCT-09:09 | 1467.05 | 25-OCT-07:10 | 2276.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 216.30 | 01-OCT-16:10 | 2206.25 | 11-OCT-23:00 |
November | 2010.79 | 01-NOV-09:09 | 1750.00 | 13-NOV-16:00 | 2276.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3755.18 | 03-NOV-21:03 |
December | 2010.79 | 01-DEC-10:09 | 1750.00 | 01-DEC-16:00 | 2276.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4974.68 | 14-DEC-04:08 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1001.00 | |||||
Maximum of Months | 2010.79 | 1750.00 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 1367.89 | 4974.68 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1046.50 | 09-JAN-16:00 | 1466.95 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2953.89 | 16-JAN-18:00 |
February | 1295.83 | 01-FEB-10:09 | 943.36 | 16-FEB-08:09 | 1466.95 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2325.56 | 05-FEB-01:00 |
March | 1295.83 | 01-MAR-10:09 | 822.08 | 14-MAR-15:00 | 1466.95 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2144.12 | 14-MAR-04:57 |
April | 1295.83 | 03-APR-09:09 | 692.79 | 03-APR-07:10 | 1466.95 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.25 | 29-APR-16:00 | 2545.49 | 23-APR-09:00 |
May | 1295.83 | 01-MAY-09:09 | 692.79 | 01-MAY-07:10 | 1466.95 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 237.73 | 14-MAY-16:40 | 1538.98 | 03-MAY-22:00 |
June | 1295.83 | 01-JUN-09:09 | 760.41 | 08-JUN-15:00 | 1466.95 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 755.29 | 18-JUN-15:54 | 1261.69 | 04-JUN-16:53 |
July | 1295.83 | 03-JUL-09:09 | 692.79 | 03-JUL-07:10 | 1466.95 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 909.03 | 04-JUL-15:03 | 764.80 | 15-JUL-18:53 |
August | 1295.83 | 01-AUG-09:09 | 692.79 | 01-AUG-07:10 | 1466.95 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 491.02 | 20-AUG-16:51 | 814.55 | 27-AUG-07:40 |
September | 1295.83 | 01-SEP-09:09 | 932.53 | 08-SEP-07:10 | 1466.95 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 338.08 | 03-SEP-14:38 | 960.90 | 17-SEP-20:00 |
October | 1295.83 | 02-OCT-09:09 | 904.96 | 25-OCT-07:10 | 1466.95 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 146.15 | 01-OCT-16:10 | 1484.48 | 11-OCT-23:00 |
November | 1295.83 | 01-NOV-09:09 | 1127.77 | 13-NOV-16:00 | 1466.95 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2516.15 | 03-NOV-21:03 |
December | 1295.83 | 01-DEC-10:09 | 1127.77 | 01-DEC-16:00 | 1466.95 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3346.23 | 14-DEC-04:04 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 764.80 | |||||
Maximum of Months | 1295.83 | 1127.77 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 909.03 | 3346.23 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1549.88 | 04-JAN-16:00 | 2276.35 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 4431.80 | 16-JAN-18:00 |
February | 2010.83 | 01-FEB-10:09 | 1476.34 | 16-FEB-08:09 | 2276.35 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3737.63 | 05-FEB-00:45 |
March | 2010.83 | 01-MAR-10:09 | 1333.01 | 20-MAR-07:10 | 2276.35 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3313.11 | 14-MAR-03:00 |
April | 2010.83 | 03-APR-09:09 | 1075.05 | 03-APR-07:10 | 2276.35 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.38 | 29-APR-16:00 | 3784.08 | 07-APR-22:00 |
May | 2010.83 | 01-MAY-09:09 | 1075.05 | 01-MAY-07:10 | 2276.35 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 315.37 | 14-MAY-16:40 | 2289.38 | 03-MAY-22:00 |
June | 2010.83 | 01-JUN-09:09 | 1182.92 | 08-JUN-15:00 | 2276.35 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1083.97 | 18-JUN-15:54 | 1800.18 | 04-JUN-16:53 |
July | 2010.83 | 03-JUL-09:09 | 1075.05 | 03-JUL-07:10 | 2276.35 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1366.30 | 04-JUL-15:03 | 1096.02 | 15-JUL-18:53 |
August | 2010.83 | 01-AUG-09:09 | 1075.05 | 01-AUG-07:10 | 2276.35 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 708.63 | 20-AUG-16:51 | 1056.31 | 08-AUG-00:52 |
September | 2010.83 | 01-SEP-09:09 | 1464.40 | 08-SEP-07:10 | 2276.35 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 424.98 | 03-SEP-14:34 | 1584.42 | 17-SEP-20:00 |
October | 2010.83 | 02-OCT-09:09 | 1443.57 | 25-OCT-07:10 | 2276.35 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 176.67 | 11-OCT-13:50 | 2330.36 | 11-OCT-23:00 |
November | 2010.83 | 01-NOV-09:09 | 1750.04 | 13-NOV-16:00 | 2276.35 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 4042.67 | 03-NOV-21:03 |
December | 2010.83 | 01-DEC-10:09 | 1750.04 | 01-DEC-16:00 | 2276.35 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 5029.53 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1075.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1056.31 | |||||
Maximum of Months | 2010.83 | 1750.04 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 1366.30 | 5029.53 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 979.59 | 04-JAN-16:00 | 1466.94 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2954.18 | 16-JAN-18:00 |
February | 1295.83 | 01-FEB-10:09 | 956.33 | 16-FEB-08:09 | 1466.94 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2410.68 | 05-FEB-01:00 |
March | 1295.83 | 01-MAR-10:09 | 913.93 | 22-MAR-07:10 | 1466.94 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2149.87 | 14-MAR-03:00 |
April | 1295.83 | 03-APR-09:09 | 692.79 | 03-APR-07:10 | 1466.94 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.25 | 29-APR-16:00 | 2823.50 | 15-APR-17:10 |
May | 1295.83 | 01-MAY-09:09 | 692.79 | 01-MAY-07:10 | 1466.94 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 177.70 | 21-MAY-16:30 | 1638.93 | 18-MAY-02:00 |
June | 1295.83 | 01-JUN-09:09 | 823.38 | 08-JUN-07:10 | 1466.94 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 658.24 | 18-JUN-16:00 | 1300.99 | 10-JUN-01:00 |
July | 1295.83 | 03-JUL-09:09 | 692.79 | 03-JUL-07:10 | 1466.94 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 907.36 | 04-JUL-15:03 | 788.27 | 15-JUL-18:53 |
August | 1295.83 | 01-AUG-09:09 | 692.79 | 01-AUG-07:10 | 1466.94 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 472.41 | 20-AUG-17:00 | 789.76 | 08-AUG-00:52 |
September | 1295.83 | 01-SEP-09:09 | 944.93 | 08-SEP-07:10 | 1466.94 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 325.92 | 03-SEP-14:36 | 1070.68 | 17-SEP-20:00 |
October | 1295.83 | 02-OCT-09:09 | 953.92 | 25-OCT-07:10 | 1466.94 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 118.11 | 11-OCT-13:00 | 1554.51 | 11-OCT-23:00 |
November | 1295.83 | 01-NOV-09:09 | 1127.77 | 13-NOV-16:00 | 1466.94 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2584.06 | 03-NOV-21:03 |
December | 1295.83 | 01-DEC-10:09 | 1127.77 | 01-DEC-16:00 | 1466.94 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3322.48 | 14-DEC-04:02 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 692.79 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 788.27 | |||||
Maximum of Months | 1295.83 | 1127.77 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 907.36 | 3322.48 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 405.10 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 405.10 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 405.10 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 405.10 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 405.10 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 405.10 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 405.10 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 405.10 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 405.10 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 405.10 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 405.10 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 405.10 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 405.10 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 405.10 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 405.10 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 405.10 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 405.10 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 405.10 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 405.10 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 405.10 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 405.10 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 405.10 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 405.10 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 405.10 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 405.10 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 405.10 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 405.10 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 405.10 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 405.10 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 405.10 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 405.10 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 405.10 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 405.10 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 405.10 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 405.10 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 405.10 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 405.10 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 405.10 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 405.10 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 405.10 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 405.10 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 405.10 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5027.92 | 02-JAN-10:09 | 4375.82 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5027.92 | 01-FEB-10:09 | 4375.82 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5027.92 | 01-MAR-10:09 | 4375.82 | 01-MAR-08:09 | 379632.52 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5027.92 | 03-APR-09:09 | 4375.82 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5027.92 | 01-MAY-09:09 | 4375.82 | 01-MAY-07:10 | 189816.26 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5027.92 | 01-JUN-09:09 | 4375.82 | 01-JUN-07:10 | 284724.39 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5027.92 | 03-JUL-09:09 | 4375.82 | 03-JUL-07:10 | 379632.52 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5027.92 | 01-AUG-09:09 | 4375.82 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5027.92 | 01-SEP-09:09 | 4375.82 | 01-SEP-07:10 | 189816.26 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5027.92 | 02-OCT-09:09 | 4375.82 | 02-OCT-07:10 | 284724.39 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5027.92 | 01-NOV-09:09 | 4375.82 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5027.92 | 01-DEC-10:09 | 4375.82 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5027.92 | 4375.82 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 5027.92 | 4375.82 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 4311.78 | 16-JAN-18:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3347.74 | 05-FEB-01:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2907.18 | 14-MAR-03:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.30 | 26-APR-15:00 | 3121.45 | 07-APR-22:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 291.51 | 14-MAY-17:00 | 1906.36 | 03-MAY-22:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 790.89 | 18-JUN-16:00 | 1475.81 | 10-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1038.53 | 04-JUL-15:00 | 684.08 | 15-JUL-18:53 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 523.41 | 05-AUG-17:01 | 754.62 | 22-AUG-22:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 349.64 | 03-SEP-14:50 | 1091.53 | 18-SEP-00:55 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.16 | 01-OCT-16:00 | 1755.08 | 11-OCT-23:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3346.59 | 26-NOV-06:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4669.83 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 684.08 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1038.53 | 4669.83 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 7112.70 | 16-JAN-18:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 5683.70 | 05-FEB-01:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4895.29 | 14-MAR-03:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.75 | 17-APR-15:00 | 5420.33 | 07-APR-22:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 574.65 | 14-MAY-16:52 | 3350.63 | 03-MAY-22:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1448.56 | 18-JUN-16:00 | 2565.15 | 10-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1875.21 | 04-JUL-14:51 | 1255.33 | 15-JUL-18:53 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 998.65 | 05-AUG-17:01 | 1275.51 | 22-AUG-22:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 650.31 | 03-SEP-14:52 | 1864.07 | 18-SEP-00:55 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 269.57 | 01-OCT-16:00 | 3071.66 | 11-OCT-23:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 5610.73 | 26-NOV-06:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 7847.42 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1255.33 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1875.21 | 7847.42 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 6731.45 | 16-JAN-18:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 5599.82 | 05-FEB-01:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4993.95 | 14-MAR-03:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.63 | 13-APR-17:00 | 5810.90 | 07-APR-22:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 238.87 | 19-MAY-15:00 | 3567.99 | 03-MAY-22:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1102.33 | 18-JUN-16:00 | 2769.19 | 04-JUN-16:53 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1601.25 | 04-JUL-16:51 | 1662.10 | 15-JUL-18:53 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 835.69 | 20-AUG-17:00 | 1492.90 | 08-AUG-00:52 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 437.74 | 03-SEP-14:20 | 2070.00 | 18-SEP-00:55 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.90 | 01-OCT-15:52 | 3411.17 | 11-OCT-23:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 6050.31 | 03-NOV-21:03 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 7668.35 | 14-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1492.90 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1601.25 | 7668.35 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 106203.28 | 02-JAN-04:11 | 0.00 | 6897.82 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 103093.82 | 27-FEB-04:02 | 0.00 | 5173.36 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 103234.03 | 27-MAR-03:02 | 0.00 | 3448.91 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 104528.05 | 10-APR-03:02 | 0.00 | 4311.14 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 101365.48 | 01-MAY-03:02 | 0.00 | 4311.14 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 97807.71 | 19-JUN-03:02 | 0.00 | 4311.14 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 89899.36 | 31-JUL-03:02 | 0.00 | 5173.36 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 88404.66 | 07-AUG-01:40 | 0.00 | 4311.14 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 94864.97 | 25-SEP-04:33 | 0.00 | 6897.82 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 105920.20 | 23-OCT-03:02 | 0.00 | 4311.14 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 104450.06 | 06-NOV-04:02 | 0.00 | 4311.14 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 106949.18 | 11-DEC-04:01 | 0.00 | 7760.04 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 88404.66 | 0.00 | 3448.91 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 106949.18 | 0.00 | 7760.04 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 82822.57 | 03-JAN-05:01 | 0.00 | 13938.13 | 72514.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 83167.14 | 22-FEB-05:01 | 0.00 | 12389.45 | 64457.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 84868.49 | 27-MAR-03:02 | 0.00 | 3097.36 | 32228.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 88575.75 | 24-APR-03:02 | 0.00 | 3871.70 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 87219.83 | 30-MAY-03:02 | 0.00 | 3871.70 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 88647.66 | 05-JUN-03:02 | 0.00 | 3871.70 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 78974.88 | 10-JUL-04:03 | 0.00 | 6194.72 | 32228.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 85594.25 | 28-AUG-05:03 | 9673.43 | 9292.09 | 48342.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 88399.89 | 18-SEP-03:02 | 0.00 | 3871.70 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 88882.08 | 10-OCT-03:02 | 0.00 | 3871.70 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 87015.84 | 13-NOV-04:02 | 0.00 | 3871.70 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 87879.63 | 26-DEC-04:01 | 0.00 | 6969.07 | 72514.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 78974.88 | 0.00 | 3097.36 | 32228.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 88882.08 | 9673.43 | 13938.13 | 72514.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 45541.27 | 05-JAN-06:02 | 8061.19 | 7743.41 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 72008.22 | 16-FEB-06:03 | 6448.95 | 6194.72 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 73420.66 | 31-MAR-05:02 | 8061.19 | 7743.41 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 75816.43 | 28-APR-04:03 | 0.00 | 6194.72 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 76738.77 | 23-MAY-04:03 | 0.00 | 6194.72 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 76733.78 | 06-JUN-04:03 | 0.00 | 6194.72 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 79384.50 | 10-JUL-03:02 | 0.00 | 3097.36 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 79016.30 | 08-AUG-03:02 | 0.00 | 4646.04 | 48342.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 80393.99 | 05-SEP-03:02 | 0.00 | 3097.36 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 76651.80 | 11-OCT-04:03 | 0.00 | 6194.72 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 72714.14 | 02-NOV-05:03 | 6448.95 | 6194.72 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 68986.30 | 01-DEC-06:03 | 6448.95 | 6194.72 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 45541.27 | 0.00 | 3097.36 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 80393.99 | 8061.19 | 7743.41 | 48342.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 21827.53 | 05-JAN-17:00 | 15316.26 | 13937.56 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 33505.17 | 15-FEB-16:40 | 15316.26 | 13937.56 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 35414.28 | 08-MAR-17:00 | 15316.26 | 13937.56 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 73646.76 | 28-APR-05:02 | 8061.19 | 7743.41 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 74931.95 | 23-MAY-05:02 | 8061.19 | 7743.41 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 78173.26 | 26-JUN-03:02 | 0.00 | 3871.70 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 82015.33 | 10-JUL-03:02 | 0.00 | 3097.36 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 81089.72 | 28-AUG-03:02 | 0.00 | 3871.70 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 81259.56 | 05-SEP-03:02 | 0.00 | 3097.36 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 75726.46 | 11-OCT-05:02 | 8061.19 | 7743.41 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 40492.15 | 01-NOV-05:03 | 6448.95 | 6194.72 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 22513.61 | 01-DEC-17:00 | 15316.26 | 13937.56 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 21827.53 | 0.00 | 3097.36 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 82015.33 | 15316.26 | 13937.56 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2766.15 | 02-JAN-14:40 | 2010.79 | 1246.19 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.35 |
February | 4051.15 | 15-FEB-15:00 | 2010.79 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.48 |
March | 6090.37 | 27-MAR-14:30 | 1923.11 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.65 |
April | 8008.97 | 14-APR-14:00 | 2010.79 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.76 |
May | 12679.88 | 22-MAY-05:02 | 1012.16 | 972.26 | 5058.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.82 |
June | 16428.66 | 18-JUN-18:11 | 0.00 | 537.53 | 6828.95 | 0.00 | 0.00 | 0.00 | 0.00 | 129.69 | 0.00 |
July | 16154.24 | 04-JUL-18:31 | 0.00 | 418.08 | 5311.41 | 0.00 | 0.00 | 0.00 | 0.00 | 203.67 | 0.00 |
August | 16018.39 | 20-AUG-17:41 | 0.00 | 477.81 | 6070.18 | 0.00 | 0.00 | 0.00 | 0.00 | 151.47 | 0.00 |
September | 12718.76 | 05-SEP-05:03 | 809.73 | 777.81 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.05 |
October | 12576.67 | 02-OCT-05:02 | 1012.16 | 972.26 | 5058.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.49 |
November | 4537.00 | 09-NOV-14:10 | 2010.79 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.83 |
December | 3292.69 | 01-DEC-14:10 | 2010.79 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.14 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2766.15 | 0.00 | 418.08 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16428.66 | 2010.79 | 1246.19 | 6828.95 | 0.00 | 0.00 | 0.00 | 0.00 | 203.67 | 108.14 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5871.16 | 02-JAN-09:25 | 2478.65 | 1385.57 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.22 |
February | 8028.06 | 14-FEB-09:10 | 1239.33 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.10 |
March | 13595.67 | 12-MAR-09:13 | 260.91 | 153.96 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 210.80 |
April | 17533.25 | 30-APR-08:62 | 326.14 | 192.45 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 323.42 |
May | 19626.82 | 14-MAY-07:32 | 391.37 | 230.94 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.85 |
June | 19363.06 | 18-JUN-08:11 | 521.82 | 307.92 | 3911.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.33 |
July | 20681.83 | 30-JUL-08:41 | 521.82 | 307.92 | 3911.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.25 |
August | 19165.21 | 20-AUG-08:22 | 391.37 | 230.94 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.48 |
September | 20446.31 | 03-SEP-08:21 | 456.59 | 269.43 | 3422.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.52 |
October | 19315.56 | 01-OCT-08:52 | 391.37 | 230.94 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.86 |
November | 8353.39 | 01-NOV-08:50 | 1239.33 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.34 |
December | 5379.50 | 29-DEC-09:15 | 2478.65 | 1385.57 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.85 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5379.50 | 260.91 | 153.96 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.48 | |
Maximum of Months | 20681.83 | 2478.65 | 1385.57 | 3911.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 323.42 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 21324.71 | 01-JAN-14:02 | 607.31 | 358.36 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 261.41 |
February | 19770.65 | 12-FEB-15:13 | 404.87 | 238.91 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.83 |
March | 20474.22 | 12-MAR-13:12 | 506.09 | 298.64 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182.73 |
April | 15478.79 | 30-APR-14:42 | 607.31 | 358.36 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 241.20 |
May | 14345.42 | 22-MAY-05:02 | 1012.19 | 972.28 | 5058.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.30 |
June | 18904.32 | 18-JUN-16:11 | 1012.19 | 597.27 | 7587.84 | 0.00 | 0.00 | 0.00 | 0.00 | 336.49 | 0.00 |
July | 20459.19 | 30-JUL-15:21 | 1012.19 | 597.27 | 7587.84 | 0.00 | 0.00 | 0.00 | 0.00 | 121.03 | 0.00 |
August | 19996.56 | 20-AUG-14:21 | 708.53 | 418.09 | 5311.49 | 0.00 | 0.00 | 0.00 | 0.00 | 88.93 | 0.00 |
September | 21950.93 | 03-SEP-12:21 | 708.53 | 418.09 | 5311.49 | 0.00 | 0.00 | 0.00 | 0.00 | 38.14 | 0.00 |
October | 22001.67 | 01-OCT-14:51 | 708.53 | 418.09 | 5311.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.56 |
November | 21548.35 | 23-NOV-12:02 | 607.31 | 358.36 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.10 |
December | 20730.28 | 24-DEC-13:02 | 506.09 | 298.64 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 397.54 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 14345.42 | 404.87 | 238.91 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22001.67 | 1012.19 | 972.28 | 7587.84 | 0.00 | 0.00 | 0.00 | 0.00 | 336.49 | 397.54 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8371.25 | 26-JAN-16:30 | 1239.33 | 692.79 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.38 |
February | 13271.36 | 12-FEB-15:13 | 260.91 | 153.96 | 1955.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.11 |
March | 23522.64 | 12-MAR-15:52 | 391.37 | 230.94 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.47 |
April | 25298.95 | 16-APR-16:31 | 456.59 | 269.43 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.97 |
May | 26183.51 | 14-MAY-16:11 | 521.82 | 307.92 | 3911.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.54 |
June | 27872.09 | 18-JUN-16:51 | 652.28 | 384.90 | 4889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 72.07 | 0.00 |
July | 28214.36 | 30-JUL-16:01 | 652.28 | 384.90 | 4889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 60.87 | 0.00 |
August | 26653.64 | 20-AUG-15:41 | 521.82 | 307.92 | 3911.83 | 0.00 | 0.00 | 0.00 | 0.00 | 65.07 | 0.00 |
September | 25363.07 | 24-SEP-15:41 | 456.59 | 269.43 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.44 |
October | 25220.44 | 01-OCT-14:51 | 456.59 | 269.43 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 1.53 | 0.00 |
November | 21723.04 | 12-NOV-15:12 | 326.14 | 192.45 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.55 |
December | 15538.83 | 17-DEC-15:32 | 260.91 | 153.96 | 1955.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 473.11 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8371.25 | 260.91 | 153.96 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 28214.36 | 1239.33 | 692.79 | 4889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 72.07 | 473.11 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2358.00 | 05-JAN-15:20 | 1923.11 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.55 |
February | 2682.77 | 15-FEB-16:00 | 1923.11 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.41 |
March | 3533.00 | 27-MAR-14:50 | 1923.11 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.30 |
April | 6571.37 | 14-APR-14:30 | 1923.11 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.51 |
May | 10123.52 | 22-MAY-05:02 | 1012.16 | 972.26 | 5058.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.16 |
June | 15464.39 | 25-JUN-17:21 | 0.00 | 597.26 | 7587.73 | 0.00 | 0.00 | 0.00 | 0.00 | 480.17 | 0.00 |
July | 15857.85 | 04-JUL-17:01 | 0.00 | 597.26 | 7587.73 | 0.00 | 0.00 | 0.00 | 0.00 | 889.68 | 0.00 |
August | 14112.88 | 06-AUG-16:51 | 1012.16 | 597.26 | 7587.73 | 0.00 | 0.00 | 0.00 | 0.00 | 341.80 | 0.00 |
September | 9147.69 | 01-SEP-05:03 | 809.73 | 777.81 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.83 |
October | 6745.02 | 02-OCT-13:40 | 2010.79 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 18.56 | 0.00 |
November | 2697.03 | 02-NOV-15:30 | 1923.11 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.63 |
December | 2223.80 | 29-DEC-15:30 | 1923.11 | 1237.68 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.22 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2223.80 | 0.00 | 597.26 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15857.85 | 2010.79 | 1237.68 | 7587.73 | 0.00 | 0.00 | 0.00 | 0.00 | 889.68 | 112.30 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3302.15 | 27-JAN-10:00 | 1239.33 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6377.87 | 14-FEB-09:40 | 1239.33 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.24 |
March | 8522.94 | 26-MAR-10:23 | 195.68 | 115.47 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 444.76 |
April | 20423.47 | 30-APR-09:42 | 391.37 | 230.94 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 596.98 |
May | 21443.30 | 29-MAY-08:51 | 456.59 | 269.43 | 3422.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 144.74 |
June | 22134.39 | 18-JUN-08:21 | 521.82 | 307.92 | 3911.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 185.87 |
July | 22618.84 | 04-JUL-08:21 | 521.82 | 307.92 | 3911.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.17 |
August | 21578.73 | 06-AUG-08:51 | 456.59 | 269.43 | 3422.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.62 |
September | 21544.40 | 03-SEP-09:01 | 456.59 | 269.43 | 3422.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.69 |
October | 12859.06 | 01-OCT-09:02 | 260.91 | 153.96 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 240.06 |
November | 7334.40 | 01-NOV-09:00 | 1239.33 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.07 |
December | 3052.36 | 29-DEC-09:30 | 1239.33 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.34 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3052.36 | 195.68 | 115.47 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22618.84 | 1239.33 | 692.79 | 3911.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 596.98 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 19417.63 | 08-JAN-12:43 | 404.87 | 238.91 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 967.02 |
February | 20141.51 | 19-FEB-12:32 | 506.09 | 298.64 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1140.30 |
March | 19299.65 | 26-MAR-13:02 | 404.87 | 238.91 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 519.76 |
April | 18267.11 | 30-APR-13:43 | 404.87 | 238.91 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 631.57 |
May | 13343.03 | 22-MAY-05:02 | 1012.19 | 972.28 | 5058.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.54 |
June | 18708.52 | 25-JUN-16:41 | 1012.19 | 597.27 | 7587.84 | 0.00 | 0.00 | 0.00 | 0.00 | 591.74 | 0.00 |
July | 19715.18 | 30-JUL-14:41 | 809.75 | 477.82 | 6070.27 | 0.00 | 0.00 | 0.00 | 0.00 | 250.58 | 0.00 |
August | 19369.41 | 06-AUG-11:32 | 607.31 | 358.36 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 21.91 | 0.00 |
September | 21458.02 | 03-SEP-12:21 | 708.53 | 418.09 | 5311.49 | 0.00 | 0.00 | 0.00 | 0.00 | 74.13 | 0.00 |
October | 20760.45 | 01-OCT-13:02 | 607.31 | 358.36 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.31 |
November | 19940.05 | 05-NOV-12:32 | 506.09 | 298.64 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1658.65 |
December | 19934.87 | 31-DEC-14:12 | 506.09 | 298.64 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 13343.03 | 404.87 | 238.91 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21458.02 | 1012.19 | 972.28 | 7587.84 | 0.00 | 0.00 | 0.00 | 0.00 | 591.74 | 1658.65 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6216.48 | 26-JAN-16:30 | 1239.33 | 692.79 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.55 |
February | 10010.55 | 15-FEB-16:30 | 1239.33 | 692.79 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.59 |
March | 10948.99 | 12-MAR-16:42 | 260.91 | 153.96 | 1955.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 310.79 |
April | 20757.37 | 30-APR-15:42 | 326.14 | 192.45 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 414.31 |
May | 22094.91 | 14-MAY-16:21 | 587.05 | 346.41 | 4400.81 | 0.00 | 0.00 | 0.00 | 0.00 | 26.84 | 0.00 |
June | 25054.68 | 25-JUN-16:41 | 652.28 | 384.90 | 4889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 209.05 | 0.00 |
July | 25623.11 | 04-JUL-17:01 | 0.00 | 384.90 | 4889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 384.68 | 0.00 |
August | 22425.90 | 20-AUG-16:01 | 456.59 | 269.43 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 207.08 | 0.00 |
September | 22470.24 | 04-SEP-17:01 | 0.00 | 269.43 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.11 |
October | 16442.05 | 01-OCT-15:42 | 326.14 | 192.45 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 59.86 | 0.00 |
November | 8723.68 | 02-NOV-16:00 | 1239.33 | 692.79 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.56 |
December | 5309.17 | 29-DEC-16:00 | 1239.33 | 692.79 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5309.17 | 0.00 | 153.96 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25623.11 | 1239.33 | 692.79 | 4889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 384.68 | 414.31 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1980.75 | 05-JAN-14:30 | 2010.79 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.75 |
February | 2662.28 | 15-FEB-15:00 | 2010.79 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.82 |
March | 2714.50 | 27-MAR-16:00 | 1923.11 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.24 |
April | 6966.38 | 28-APR-15:30 | 1923.11 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 25.78 | 0.00 |
May | 8183.57 | 31-MAY-15:30 | 1923.11 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 131.32 | 0.00 |
June | 18606.83 | 25-JUN-17:21 | 0.00 | 597.26 | 7587.73 | 0.00 | 0.00 | 0.00 | 0.00 | 532.28 | 0.00 |
July | 18851.35 | 04-JUL-16:21 | 1012.16 | 597.26 | 7587.73 | 0.00 | 0.00 | 0.00 | 0.00 | 973.54 | 0.00 |
August | 17396.61 | 06-AUG-16:51 | 1012.16 | 597.26 | 7587.73 | 0.00 | 0.00 | 0.00 | 0.00 | 384.71 | 0.00 |
September | 8310.42 | 03-SEP-14:32 | 506.08 | 298.63 | 3793.86 | 0.00 | 0.00 | 0.00 | 0.00 | 416.48 | 0.00 |
October | 7204.18 | 02-OCT-13:40 | 2010.79 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 21.91 | 0.00 |
November | 2669.90 | 01-NOV-15:00 | 1923.11 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 590.02 |
December | 1963.61 | 29-DEC-14:10 | 2010.79 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.83 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1963.61 | 0.00 | 298.63 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18851.35 | 2010.79 | 1075.02 | 7587.73 | 0.00 | 0.00 | 0.00 | 0.00 | 973.54 | 590.02 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2341.38 | 26-JAN-14:10 | 1295.83 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.36 |
February | 4418.44 | 14-FEB-10:10 | 1295.83 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.95 |
March | 6461.58 | 08-MAR-09:50 | 1239.33 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.80 |
April | 20428.88 | 30-APR-09:12 | 391.37 | 230.94 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 907.62 |
May | 18690.99 | 29-MAY-09:02 | 326.14 | 192.45 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 175.35 |
June | 21870.02 | 25-JUN-08:61 | 456.59 | 269.43 | 3422.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.55 |
July | 22978.03 | 04-JUL-08:21 | 521.82 | 307.92 | 3911.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.51 |
August | 21977.13 | 06-AUG-08:51 | 456.59 | 269.43 | 3422.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.07 |
September | 20267.72 | 03-SEP-09:12 | 391.37 | 230.94 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.73 |
October | 19805.50 | 01-OCT-09:22 | 326.14 | 192.45 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 239.99 |
November | 6181.79 | 01-NOV-09:10 | 1295.83 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.43 |
December | 2375.44 | 29-DEC-13:40 | 1239.33 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.98 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2341.38 | 326.14 | 192.45 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.73 | |
Maximum of Months | 22978.03 | 1295.83 | 692.79 | 3911.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 907.62 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 16645.34 | 15-JAN-13:52 | 506.09 | 298.64 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 572.26 |
February | 20909.08 | 12-FEB-14:12 | 607.31 | 358.36 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 378.68 |
March | 21374.54 | 12-MAR-13:52 | 506.09 | 298.64 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 250.91 |
April | 18178.98 | 30-APR-14:31 | 809.75 | 477.82 | 6070.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 748.10 |
May | 11350.26 | 19-MAY-13:10 | 2010.83 | 1075.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 135.93 | 0.00 |
June | 21775.28 | 25-JUN-16:41 | 1012.19 | 597.27 | 7587.84 | 0.00 | 0.00 | 0.00 | 0.00 | 667.14 | 0.00 |
July | 22482.64 | 04-JUL-15:41 | 1012.19 | 597.27 | 7587.84 | 0.00 | 0.00 | 0.00 | 0.00 | 871.90 | 0.00 |
August | 21816.89 | 06-AUG-11:32 | 607.31 | 358.36 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 19.39 | 0.00 |
September | 22879.61 | 03-SEP-13:12 | 607.31 | 358.36 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 207.04 | 0.00 |
October | 24369.95 | 01-OCT-11:21 | 708.53 | 418.09 | 5311.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.64 |
November | 22063.49 | 19-NOV-13:42 | 607.31 | 358.36 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 831.63 |
December | 21581.76 | 31-DEC-14:01 | 708.53 | 418.09 | 5311.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 11350.26 | 506.09 | 298.64 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24369.95 | 2010.83 | 1075.05 | 7587.84 | 0.00 | 0.00 | 0.00 | 0.00 | 871.90 | 831.63 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5415.54 | 26-JAN-16:30 | 1239.33 | 692.79 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.34 |
February | 9749.21 | 15-FEB-16:30 | 1239.33 | 692.79 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.37 |
March | 11932.70 | 12-MAR-16:32 | 391.37 | 230.94 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 353.71 |
April | 23384.35 | 16-APR-17:01 | 0.00 | 384.90 | 4889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.73 |
May | 23078.45 | 14-MAY-16:32 | 391.37 | 230.94 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 67.31 | 0.00 |
June | 27713.30 | 25-JUN-16:41 | 652.28 | 384.90 | 4889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 225.50 | 0.00 |
July | 27998.98 | 04-JUL-16:21 | 652.28 | 384.90 | 4889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 425.52 | 0.00 |
August | 24264.12 | 20-AUG-16:01 | 456.59 | 269.43 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 243.34 | 0.00 |
September | 23259.44 | 10-SEP-15:22 | 391.37 | 230.94 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.38 |
October | 23912.24 | 01-OCT-15:21 | 456.59 | 269.43 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 13.76 | 0.00 |
November | 8219.36 | 02-NOV-16:00 | 1239.33 | 692.79 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.49 |
December | 4568.82 | 29-DEC-16:00 | 1239.33 | 692.79 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4568.82 | 0.00 | 230.94 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 27998.98 | 1239.33 | 692.79 | 4889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 425.52 | 353.71 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4177.83 | 02-JAN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 195.11 |
February | 3858.44 | 15-FEB-16:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.63 |
March | 5448.19 | 27-MAR-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.76 |
April | 6709.73 | 17-APR-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.71 |
May | 9643.38 | 30-MAY-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.29 |
June | 9778.67 | 05-JUN-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.49 |
July | 12825.33 | 05-JUL-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.53 |
August | 14072.21 | 07-AUG-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.39 |
September | 10064.42 | 05-SEP-05:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.96 |
October | 11398.37 | 02-OCT-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.58 |
November | 5100.28 | 13-NOV-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.35 |
December | 3645.11 | 02-DEC-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.84 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 3645.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.35 | |
Maximum of Months | 14072.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 195.11 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6537.91 | 17-JAN-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4843.06 |
February | 5874.53 | 06-FEB-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3709.42 |
March | 4756.56 | 04-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 789.62 |
April | 4851.14 | 28-APR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.67 | 0.00 |
May | 6050.98 | 22-MAY-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.16 |
June | 7490.02 | 26-JUN-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 324.17 | 0.00 |
July | 8362.43 | 05-JUL-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.95 |
August | 7924.64 | 07-AUG-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 196.44 | 0.00 |
September | 7094.54 | 05-SEP-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.03 |
October | 6150.01 | 02-OCT-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.19 |
November | 5486.86 | 25-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1112.02 |
December | 5278.31 | 23-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3288.60 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 4756.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8362.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 324.17 | 4843.06 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1996.16 | 01-JAN-14:38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 557.21 |
February | 6376.84 | 15-FEB-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.71 |
March | 9183.30 | 08-MAR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.10 |
April | 15545.01 | 28-APR-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.61 |
May | 18059.25 | 30-MAY-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.91 | 0.00 |
June | 23285.87 | 28-JUN-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 199.27 | 0.00 |
July | 22359.80 | 21-JUL-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 371.02 | 0.00 |
August | 21046.79 | 07-AUG-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.17 | 0.00 |
September | 16408.58 | 01-SEP-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.98 | 0.00 |
October | 12747.82 | 02-OCT-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.42 | 0.00 |
November | 5500.79 | 02-NOV-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 191.96 |
December | 2289.00 | 31-DEC-15:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1996.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23285.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 371.02 | 557.21 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 2300.64 | 26-JAN-17:00 | 222.14 | 405.10 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4333.04 | 15-FEB-17:00 | 222.14 | 405.10 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7113.90 | 31-MAR-24:00 | 0.00 | 22.51 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8155.20 | 15-APR-18:00 | 23.38 | 45.01 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3508.54 | 31-MAY-24:00 | 0.00 | 22.51 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5342.32 | 30-JUN-24:00 | 0.00 | 45.01 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7248.62 | 31-JUL-23:53 | 0.00 | 67.52 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8014.12 | 27-AUG-18:52 | 0.00 | 112.53 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3512.39 | 30-SEP-24:00 | 0.00 | 22.51 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5309.33 | 31-OCT-24:00 | 0.00 | 22.51 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6200.52 | 06-NOV-16:40 | 222.14 | 405.10 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 8017.19 | 26-DEC-16:30 | 222.14 | 405.10 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 2300.64 | 0.00 | 22.51 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8155.20 | 222.14 | 405.10 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 2076.52 | 26-JAN-17:00 | 222.14 | 405.10 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4059.68 | 15-FEB-17:00 | 222.14 | 405.10 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6539.49 | 31-MAR-23:50 | 0.00 | 22.51 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7645.48 | 24-APR-18:00 | 23.38 | 135.03 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3318.92 | 31-MAY-24:00 | 0.00 | 22.51 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5174.67 | 30-JUN-24:00 | 0.00 | 45.01 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6992.63 | 31-JUL-23:57 | 0.00 | 67.52 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7449.35 | 23-AUG-18:00 | 23.38 | 135.03 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3318.24 | 30-SEP-24:00 | 0.00 | 22.51 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4842.77 | 31-OCT-24:00 | 0.00 | 22.51 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5751.42 | 02-NOV-16:40 | 70.15 | 225.06 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7382.90 | 29-DEC-16:50 | 222.14 | 405.10 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 2076.52 | 0.00 | 22.51 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7645.48 | 222.14 | 405.10 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1969.21 | 26-JAN-17:00 | 222.14 | 405.10 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4068.82 | 15-FEB-17:00 | 222.14 | 405.10 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6161.13 | 31-MAR-23:20 | 0.00 | 22.51 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7753.32 | 16-APR-18:00 | 0.00 | 135.04 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3266.06 | 31-MAY-24:00 | 0.00 | 22.51 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5178.52 | 30-JUN-24:00 | 0.00 | 45.01 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6971.80 | 31-JUL-23:57 | 0.00 | 67.52 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7579.68 | 30-AUG-17:30 | 23.38 | 135.03 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3300.51 | 30-SEP-24:00 | 0.00 | 22.51 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4606.32 | 31-OCT-23:50 | 0.00 | 22.51 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5729.76 | 02-NOV-16:40 | 70.15 | 225.06 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7292.97 | 29-DEC-16:50 | 222.14 | 405.10 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1969.21 | 0.00 | 22.51 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7753.32 | 222.14 | 405.10 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 92009.88 | 02-JAN-17:00 | 4808.68 | 4375.82 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 183463.75 | 15-FEB-17:00 | 4808.68 | 4375.82 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 358557.24 | 31-MAR-24:00 | 0.00 | 243.11 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 366754.19 | 18-APR-07:15 | 9617.36 | 8751.64 | 759265.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 176011.75 | 31-MAY-24:00 | 0.00 | 243.11 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 267808.51 | 30-JUN-23:55 | 0.00 | 486.22 | 569448.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 356451.47 | 31-JUL-23:13 | 0.00 | 729.33 | 1138897.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 364744.51 | 31-AUG-06:05 | 2024.71 | 2917.21 | 759265.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 176538.64 | 30-SEP-24:00 | 0.00 | 243.11 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 268672.67 | 31-OCT-24:00 | 0.00 | 243.11 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 276418.53 | 24-NOV-17:00 | 4808.68 | 4375.82 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 366518.05 | 13-DEC-16:55 | 9617.36 | 8751.64 | 759265.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 92009.88 | 0.00 | 243.11 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 366754.19 | 9617.36 | 8751.64 | 1138897.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.165132E+13 | 1047540.59 | 05-JAN-16:10 | 0.301410E+12 | 762200.74 | 17-JAN-07:10 |
February | 0.190988E+13 | 1293655.30 | 14-FEB-16:00 | 0.199261E+12 | 771014.08 | 06-FEB-07:10 |
March | 0.264792E+13 | 1493518.89 | 08-MAR-16:40 | 0.103167E+12 | 386814.27 | 04-MAR-07:19 |
April | 0.307083E+13 | 1818661.73 | 13-APR-15:09 | 0.635575E+11 | 229529.44 | 08-APR-06:30 |
May | 0.192613E+13 | 1349823.18 | 19-MAY-15:20 | 0.593854E+11 | 81507.15 | 06-MAY-06:10 |
June | 0.248809E+13 | 1602559.15 | 26-JUN-15:30 | 0.549725E+11 | 74434.46 | 01-JUN-11:30 |
July | 0.305038E+13 | 1804090.61 | 31-JUL-15:09 | 0.516832E+11 | 71520.50 | 03-JUL-11:39 |
August | 0.356806E+13 | 1969373.19 | 02-AUG-15:30 | 0.546256E+11 | 70750.60 | 30-AUG-11:20 |
September | 0.194368E+13 | 1365196.25 | 05-SEP-15:09 | 0.517320E+11 | 72276.18 | 22-SEP-11:50 |
October | 0.228446E+13 | 1475690.36 | 02-OCT-15:00 | 0.755195E+11 | 431588.99 | 26-OCT-06:19 |
November | 0.251199E+13 | 1424219.08 | 02-NOV-15:00 | 0.115497E+12 | 559075.98 | 27-NOV-07:10 |
December | 0.297796E+13 | 1548471.98 | 27-DEC-16:00 | 0.291184E+12 | 676862.18 | 15-DEC-07:10 |
Annual Sum or Average | 0.300307E+14 | 0.142199E+13 | ||||
Minimum of Months | 0.165132E+13 | 1047540.59 | 0.516832E+11 | 70750.60 | ||
Maximum of Months | 0.356806E+13 | 1969373.19 | 0.301410E+12 | 771014.08 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.230620E+12 | 0.466691E+11 | 0.811612E+12 | 0.162550E+12 | 0.195268E+12 | 0.181929E+11 | 0.00 | 0.112217E+12 | 0.177786E+11 | 0.564088E+11 | 0.00 | 0.00 | 0.00 |
February | 0.208322E+12 | 0.391193E+11 | 0.102011E+13 | 0.146826E+12 | 0.179889E+12 | 0.200946E+11 | 0.00 | 0.176683E+12 | 0.354512E+11 | 0.833842E+11 | 0.00 | 0.00 | 0.00 |
March | 0.246145E+12 | 0.389287E+11 | 0.146267E+13 | 0.162740E+12 | 0.213374E+12 | 0.265459E+11 | 0.00 | 0.287603E+12 | 0.852775E+11 | 0.124640E+12 | 0.00 | 0.00 | 0.00 |
April | 0.219029E+12 | 0.331851E+11 | 0.170311E+13 | 0.157288E+12 | 0.231242E+12 | 0.435798E+11 | 0.00 | 0.410389E+12 | 0.116923E+12 | 0.156083E+12 | 0.00 | 0.00 | 0.00 |
May | 0.236061E+12 | 0.305101E+11 | 0.820521E+12 | 0.162644E+12 | 0.251221E+12 | 0.538280E+11 | 0.00 | 0.220262E+12 | 0.103115E+12 | 0.479670E+11 | 0.00 | 0.00 | 0.00 |
June | 0.234532E+12 | 0.277819E+11 | 0.110677E+13 | 0.157466E+12 | 0.280506E+12 | 0.794405E+11 | 0.00 | 0.414828E+12 | 0.130233E+12 | 0.565294E+11 | 0.00 | 0.00 | 0.00 |
July | 0.219814E+12 | 0.294282E+11 | 0.143888E+13 | 0.162465E+12 | 0.298650E+12 | 0.945987E+11 | 0.00 | 0.591573E+12 | 0.154244E+12 | 0.607317E+11 | 0.00 | 0.00 | 0.00 |
August | 0.244903E+12 | 0.325649E+11 | 0.177780E+13 | 0.162739E+12 | 0.304445E+12 | 0.971572E+11 | 0.00 | 0.659783E+12 | 0.149512E+12 | 0.139161E+12 | 0.00 | 0.00 | 0.00 |
September | 0.219577E+12 | 0.357803E+11 | 0.784732E+12 | 0.157286E+12 | 0.247146E+12 | 0.683250E+11 | 0.00 | 0.265658E+12 | 0.123976E+12 | 0.411955E+11 | 0.00 | 0.00 | 0.00 |
October | 0.229103E+12 | 0.415239E+11 | 0.112899E+13 | 0.162550E+12 | 0.226352E+12 | 0.451473E+11 | 0.00 | 0.270375E+12 | 0.968864E+11 | 0.835324E+11 | 0.00 | 0.00 | 0.00 |
November | 0.227996E+12 | 0.441074E+11 | 0.140306E+13 | 0.157361E+12 | 0.199486E+12 | 0.193972E+11 | 0.00 | 0.261598E+12 | 0.726385E+11 | 0.126341E+12 | 0.00 | 0.00 | 0.00 |
December | 0.224509E+12 | 0.477523E+11 | 0.175516E+13 | 0.162466E+12 | 0.197306E+12 | 0.201170E+11 | 0.00 | 0.327254E+12 | 0.647445E+11 | 0.178657E+12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.274061E+13 | 0.447351E+12 | 0.152134E+14 | 0.191438E+13 | 0.282489E+13 | 0.586424E+12 | 0.00 | 0.399822E+13 | 0.115078E+13 | 0.115463E+13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.208322E+12 | 0.277819E+11 | 0.784732E+12 | 0.146826E+12 | 0.179889E+12 | 0.181929E+11 | 0.00 | 0.112217E+12 | 0.177786E+11 | 0.411955E+11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.246145E+12 | 0.477523E+11 | 0.177780E+13 | 0.162740E+12 | 0.304445E+12 | 0.971572E+11 | 0.00 | 0.659783E+12 | 0.154244E+12 | 0.178657E+12 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.237635E+12 | 0.00 | 0.637744E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.141053E+12 | 0.00 | 0.582083E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.369930E+11 | 0.00 | 0.661741E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.493672E+10 | 0.00 | 0.586208E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.519335E+09 | 0.00 | 0.588661E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 7522668.72 | 0.00 | 0.549649E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.516832E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.546256E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.517320E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.196142E+11 | 0.00 | 0.559053E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.578376E+11 | 0.00 | 0.576592E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.230409E+12 | 0.00 | 0.607756E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.729005E+12 | 0.00 | 0.692989E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.516832E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.237635E+12 | 0.00 | 0.661741E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 253986.56 | 04-JAN-16:00 | 37611.08 | 01-JAN-06:10 | 439129.89 | 02-JAN-08:09 | 117193.84 | 03-JAN-08:20 | 125571.26 | 26-JAN-16:49 | 35783.64 | 17-JAN-06:10 | 0.00 | 01-JAN-00:10 |
February | 250348.04 | 16-FEB-08:09 | 37611.08 | 01-FEB-06:10 | 557421.28 | 01-FEB-08:09 | 117198.62 | 16-FEB-08:20 | 157381.70 | 15-FEB-16:00 | 50262.37 | 14-FEB-14:20 | 0.00 | 01-FEB-00:10 |
March | 244683.94 | 20-MAR-07:10 | 37611.08 | 01-MAR-06:10 | 675712.68 | 01-MAR-08:09 | 117195.39 | 20-MAR-07:19 | 165093.21 | 24-MAR-15:00 | 50255.02 | 13-MAR-14:09 | 0.00 | 01-MAR-00:10 |
April | 234435.00 | 03-APR-07:10 | 37611.08 | 01-APR-05:10 | 794004.08 | 03-APR-07:10 | 117189.56 | 03-APR-07:19 | 224748.46 | 28-APR-14:00 | 51185.36 | 28-APR-13:30 | 0.00 | 01-APR-00:10 |
May | 234435.00 | 01-MAY-07:10 | 37611.08 | 01-MAY-05:10 | 439129.89 | 01-MAY-07:10 | 117189.56 | 01-MAY-07:19 | 233639.73 | 15-MAY-15:20 | 56598.78 | 23-MAY-12:09 | 0.00 | 01-MAY-00:10 |
June | 237550.56 | 08-JUN-15:00 | 37611.08 | 01-JUN-19:10 | 557421.28 | 01-JUN-07:10 | 117190.45 | 08-JUN-07:19 | 273381.36 | 28-JUN-14:50 | 64645.63 | 27-JUN-15:20 | 0.00 | 01-JUN-00:10 |
July | 234435.00 | 03-JUL-07:10 | 37611.08 | 01-JUL-19:19 | 675712.68 | 03-JUL-07:10 | 117189.56 | 03-JUL-07:19 | 274231.25 | 31-JUL-15:09 | 66759.28 | 21-JUL-15:00 | 0.00 | 01-JUL-00:10 |
August | 234435.00 | 01-AUG-07:10 | 37611.08 | 01-AUG-05:10 | 794004.08 | 01-AUG-07:10 | 117189.56 | 01-AUG-07:19 | 280561.00 | 07-AUG-15:39 | 58978.32 | 02-AUG-07:49 | 0.00 | 01-AUG-00:10 |
September | 249697.59 | 08-SEP-07:10 | 37611.08 | 01-SEP-05:10 | 439129.89 | 01-SEP-07:10 | 117198.25 | 08-SEP-07:19 | 232544.77 | 06-SEP-15:50 | 65073.33 | 21-SEP-14:30 | 0.00 | 01-SEP-00:10 |
October | 249227.62 | 25-OCT-07:10 | 37611.08 | 01-OCT-05:10 | 557421.28 | 02-OCT-07:10 | 117197.98 | 25-OCT-07:19 | 201175.86 | 02-OCT-08:00 | 62416.02 | 02-OCT-11:50 | 0.00 | 01-OCT-00:10 |
November | 261074.09 | 13-NOV-16:00 | 37611.08 | 01-NOV-05:10 | 675712.68 | 01-NOV-07:10 | 117200.69 | 02-NOV-07:19 | 161091.18 | 03-NOV-15:00 | 34250.96 | 27-NOV-06:40 | 0.00 | 01-NOV-00:10 |
December | 261074.09 | 01-DEC-16:00 | 37611.08 | 01-DEC-06:10 | 794004.08 | 01-DEC-08:09 | 117196.62 | 08-DEC-08:20 | 128139.15 | 29-DEC-16:30 | 34640.47 | 14-DEC-05:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 234435.00 | 37611.08 | 439129.89 | 117189.56 | 125571.26 | 34250.96 | 0.00 | |||||||
Maximum of Months | 261074.09 | 37611.08 | 794004.08 | 117200.69 | 280561.00 | 66759.28 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum} [W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY {Maximum} [W] | HUMIDIFIER:ELECTRICITY {TIMESTAMP} | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 87532.66 | 05-JAN-15:30 | 49248.27 | 05-JAN-13:00 | 24477.41 | 27-JAN-18:10 | 0.00 | 0.00 | 0.00 |
February | 168610.18 | 14-FEB-16:40 | 49714.83 | 14-FEB-16:00 | 38907.14 | 24-FEB-19:00 | 0.00 | 0.00 | 0.00 |
March | 213258.91 | 08-MAR-16:40 | 49936.00 | 08-MAR-15:00 | 59845.64 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 |
April | 345386.91 | 26-APR-13:30 | 50493.59 | 28-APR-14:09 | 73638.42 | 05-APR-19:10 | 0.00 | 0.00 | 0.00 |
May | 252512.42 | 22-MAY-13:50 | 54308.00 | 23-MAY-10:30 | 27482.40 | 31-MAY-23:00 | 0.00 | 0.00 | 0.00 |
June | 355515.47 | 28-JUN-14:50 | 81203.66 | 06-JUN-12:00 | 36458.62 | 19-JUN-06:10 | 0.00 | 0.00 | 0.00 |
July | 408623.06 | 21-JUL-14:50 | 81203.66 | 03-JUL-08:00 | 47044.92 | 31-JUL-23:00 | 0.00 | 0.00 | 0.00 |
August | 419477.62 | 01-AUG-15:09 | 81203.66 | 01-AUG-09:30 | 71630.12 | 25-AUG-20:19 | 0.00 | 0.00 | 0.00 |
September | 305135.24 | 05-SEP-13:09 | 81203.66 | 01-SEP-10:30 | 29566.58 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 |
October | 296111.60 | 02-OCT-11:50 | 81203.66 | 11-OCT-10:39 | 46352.40 | 31-OCT-23:00 | 0.00 | 0.00 | 0.00 |
November | 171748.73 | 09-NOV-13:00 | 49467.61 | 02-NOV-15:09 | 53679.80 | 18-NOV-17:00 | 0.00 | 0.00 | 0.00 |
December | 131134.08 | 24-DEC-14:39 | 49248.27 | 01-DEC-12:39 | 75857.24 | 23-DEC-07:30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 87532.66 | 49248.27 | 24477.41 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 419477.62 | 81203.66 | 75857.24 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 1047540.59 | 05-JAN-16:10 | 238394.56 | 439129.89 | 0.00 | 83147.77 | 122807.02 | 33065.58 | 0.00 | 65282.92 | 45259.34 |
February | 1293655.30 | 14-FEB-16:00 | 236770.23 | 557421.28 | 0.00 | 83146.17 | 142477.65 | 33538.81 | 0.00 | 164564.19 | 49714.83 |
March | 1493518.89 | 08-MAR-16:40 | 234435.00 | 675712.68 | 0.00 | 83146.17 | 158316.13 | 49888.53 | 0.00 | 213258.91 | 49550.43 |
April | 1818661.73 | 13-APR-15:09 | 234435.00 | 794004.08 | 0.00 | 83146.17 | 223314.48 | 50548.04 | 0.00 | 338339.29 | 50010.07 |
May | 1349823.18 | 19-MAY-15:20 | 234435.00 | 439129.89 | 0.00 | 83146.17 | 233111.84 | 50768.58 | 0.00 | 248335.28 | 51432.93 |
June | 1602559.15 | 26-JUN-15:30 | 234435.00 | 557421.28 | 0.00 | 83146.17 | 270360.17 | 58692.27 | 0.00 | 342473.86 | 51921.69 |
July | 1804090.61 | 31-JUL-15:09 | 234435.00 | 675712.68 | 0.00 | 83146.17 | 274231.25 | 53113.16 | 0.00 | 396944.24 | 81203.66 |
August | 1969373.19 | 02-AUG-15:30 | 234435.00 | 794004.08 | 0.00 | 83146.17 | 273286.02 | 54199.49 | 0.00 | 413953.98 | 81203.66 |
September | 1365196.25 | 05-SEP-15:09 | 234435.00 | 439129.89 | 0.00 | 83146.17 | 223612.70 | 51788.21 | 0.00 | 244159.06 | 81203.66 |
October | 1475690.36 | 02-OCT-15:00 | 234435.00 | 557421.28 | 0.00 | 83146.17 | 197481.49 | 56556.01 | 0.00 | 277656.72 | 51074.96 |
November | 1424219.08 | 02-NOV-15:00 | 237749.46 | 675712.68 | 0.00 | 83147.54 | 145658.26 | 33205.12 | 0.00 | 159676.31 | 49408.70 |
December | 1548471.98 | 27-DEC-16:00 | 261074.09 | 794004.08 | 37611.08 | 83160.48 | 102008.29 | 33039.88 | 0.00 | 126266.48 | 41347.46 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1047540.59 | 234435.00 | 439129.89 | 0.00 | 83146.17 | 102008.29 | 33039.88 | 0.00 | 65282.92 | 41347.46 | |
Maximum of Months | 1969373.19 | 261074.09 | 794004.08 | 37611.08 | 83160.48 | 274231.25 | 58692.27 | 0.00 | 413953.98 | 81203.66 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 732774.58 | 17-JAN-07:10 | 0.00 | 81566.36 | 30-JAN-12:39 | 0.00 |
February | 0.00 | 0.00 | 744684.27 | 06-FEB-07:19 | 0.00 | 81629.56 | 07-FEB-12:00 | 0.00 |
March | 0.00 | 0.00 | 376833.91 | 04-MAR-07:10 | 0.00 | 81301.67 | 01-MAR-12:30 | 0.00 |
April | 0.00 | 0.00 | 211548.97 | 08-APR-06:10 | 0.00 | 79701.17 | 03-APR-11:00 | 0.00 |
May | 0.00 | 0.00 | 54341.75 | 06-MAY-06:10 | 0.00 | 77469.67 | 01-MAY-11:39 | 0.00 |
June | 0.00 | 0.00 | 1539.36 | 09-JUN-05:40 | 0.00 | 74434.46 | 01-JUN-11:30 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 71520.50 | 03-JUL-11:39 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 70750.60 | 30-AUG-11:20 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 72276.18 | 22-SEP-11:50 | 0.00 |
October | 0.00 | 0.00 | 402547.00 | 26-OCT-06:19 | 0.00 | 75543.85 | 26-OCT-11:39 | 0.00 |
November | 0.00 | 0.00 | 533506.19 | 27-NOV-07:10 | 0.00 | 78730.37 | 30-NOV-12:50 | 0.00 |
December | 0.00 | 0.00 | 647666.98 | 15-DEC-07:10 | 0.00 | 80645.02 | 29-DEC-12:20 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 70750.60 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 744684.27 | 0.00 | 81629.56 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 26.83 | 0.67 | 26.89 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 26.40 | 0.00 | 26.40 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 25.83 | 0.00 | 25.83 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 26.10 | 0.00 | 26.10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 26.08 | 0.17 | 26.13 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 26.14 | 0.00 | 26.14 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 26.35 | 0.00 | 26.35 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 25.87 | 0.00 | 25.87 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 26.34 | 0.33 | 26.39 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 26.37 | 0.50 | 26.41 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 12.00 | 26.43 | 1.00 | 26.50 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 26.35 | 1.17 | 26.47 |
Annual Sum or Average | 0.00 | 0.00 | 85.50 | 26.29 | 3.83 | 26.33 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 25.83 | 0.00 | 25.83 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 12.00 | 26.83 | 1.17 | 26.89 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.57 | 0.00 | 25.57 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.66 | 0.00 | 25.66 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 25.71 | 0.00 | 25.71 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.64 | 0.00 | 25.64 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 25.62 | 0.00 | 25.62 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 25.72 | 0.00 | 25.72 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 25.63 | 0.00 | 25.63 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 25.78 | 0.00 | 25.78 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.91 | 0.00 | 25.91 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.59 | 0.00 | 25.59 |
Annual Sum or Average | 0.00 | 0.00 | 9.67 | 25.71 | 0.00 | 25.71 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 25.91 | 0.00 | 25.91 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.58 | 0.00 | 25.58 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.57 | 0.00 | 25.57 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.56 | 0.00 | 25.56 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.50 | 25.57 | 0.00 | 25.57 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.58 | 0.00 | 25.58 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.00 | 18.69 | 0.00 | 18.69 | 0.00 | 18.69 | 0.00 | 18.69 |
February | 0.33 | 18.89 | 0.00 | 18.89 | 0.00 | 18.89 | 0.00 | 18.89 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.56 | 0.00 | 25.56 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 18.60 | 0.00 | 18.60 | 0.00 | 18.60 | 0.00 | 18.60 |
December | 0.50 | 18.89 | 0.00 | 18.89 | 0.00 | 18.89 | 0.00 | 18.89 |
Annual Sum or Average | 2.00 | 18.76 | 0.00 | 18.76 | 0.17 | 19.29 | 0.00 | 19.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.00 | 18.89 | 0.00 | 18.89 | 0.17 | 25.56 | 0.00 | 25.56 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.40 | 0.17 | 27.39 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.28 | 2.17 | 27.32 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 26.91 | 2.67 | 27.10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 9.83 | 27.09 | 5.00 | 27.21 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.40 | 2.67 | 27.39 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.74 | 1.33 | 27.74 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.84 | 3.33 | 27.84 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 28.03 | 6.67 | 28.03 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 27.97 | 6.67 | 27.97 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 13.83 | 28.05 | 13.33 | 28.06 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 28.01 | 7.67 | 28.04 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.94 | 4.00 | 27.94 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.79 | 3.00 | 27.79 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 46.83 | 27.98 | 46.00 | 27.99 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 13.83 | 28.05 | 13.33 | 28.06 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.79 | 6.00 | 27.79 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.17 | 4.00 | 27.17 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.71 | 3.50 | 27.71 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.54 | 2.00 | 27.54 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.31 | 0.50 | 27.31 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.36 | 0.83 | 27.36 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 27.47 | 6.83 | 27.54 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 12.00 | 27.35 | 7.33 | 27.55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 | 26.85 | 12.33 | 26.85 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 22.33 | 26.08 | 21.67 | 26.08 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 27.02 | 9.33 | 27.02 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.95 | 5.00 | 27.95 |
Annual Sum or Average | 0.00 | 0.00 | 86.50 | 27.00 | 79.33 | 27.02 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 26.08 | 0.50 | 26.08 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 22.33 | 27.95 | 21.67 | 27.95 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.66 | 1.00 | 27.66 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 28.31 | 2.83 | 28.33 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 20.00 | 27.38 | 5.83 | 27.61 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 27.91 | 3.83 | 28.07 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 21.00 | 27.39 | 5.67 | 27.61 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 33.83 | 27.48 | 9.83 | 27.69 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 67.50 | 27.79 | 18.33 | 27.88 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 27.91 | 4.83 | 28.03 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.94 | 3.83 | 28.15 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.78 | 2.83 | 27.78 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.88 | 1.83 | 27.88 |
Annual Sum or Average | 0.00 | 0.00 | 171.00 | 27.66 | 60.67 | 27.82 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 67.50 | 28.31 | 18.33 | 28.33 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.83 | 19.02 | 0.17 | 19.09 | 0.00 | 19.09 | 0.00 | 19.09 |
February | 1.83 | 18.89 | 0.17 | 19.01 | 0.00 | 19.01 | 0.00 | 19.01 |
March | 0.17 | 19.42 | 0.00 | 19.42 | 0.00 | 19.42 | 0.00 | 19.42 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.38 | 0.33 | 27.37 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.49 | 2.00 | 27.48 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.50 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 |
December | 2.33 | 19.23 | 0.00 | 19.23 | 0.00 | 19.23 | 0.00 | 19.23 |
Annual Sum or Average | 7.67 | 19.08 | 0.33 | 19.13 | 3.67 | 21.75 | 2.33 | 22.70 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.83 | 19.42 | 0.17 | 19.42 | 2.50 | 27.49 | 2.00 | 27.48 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.33 | 18.93 | 0.00 | 18.93 | 0.00 | 18.93 | 0.00 | 18.93 |
February | 1.17 | 18.61 | 0.00 | 18.61 | 0.00 | 18.61 | 0.00 | 18.61 |
March | 0.17 | 19.36 | 0.00 | 19.36 | 0.50 | 25.47 | 0.50 | 26.34 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 28.13 | 1.50 | 28.13 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 28.02 | 7.17 | 28.02 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 28.13 | 7.67 | 28.15 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 17.17 | 28.19 | 16.00 | 28.22 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 28.14 | 9.67 | 28.16 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 28.03 | 4.00 | 28.03 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.81 | 1.67 | 27.81 |
November | 0.17 | 19.23 | 0.00 | 19.23 | 0.00 | 19.23 | 0.00 | 19.23 |
December | 2.00 | 19.24 | 0.00 | 19.24 | 0.00 | 19.24 | 0.00 | 19.24 |
Annual Sum or Average | 5.83 | 18.99 | 0.00 | 18.99 | 50.33 | 27.17 | 48.17 | 27.62 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.61 | 0.00 | 18.61 |
Maximum of Months | 2.33 | 19.36 | 0.00 | 19.36 | 17.17 | 28.19 | 16.00 | 28.22 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.67 | 18.86 | 0.00 | 18.86 | 11.83 | 25.92 | 11.83 | 26.11 |
February | 0.33 | 18.65 | 0.00 | 18.65 | 11.17 | 25.46 | 11.17 | 25.56 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.76 | 3.00 | 27.76 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.54 | 0.83 | 27.54 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.31 | 0.17 | 27.31 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.34 | 1.17 | 27.34 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 27.56 | 6.17 | 27.59 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27.72 | 6.17 | 27.74 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 15.83 | 26.56 | 15.83 | 26.56 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 42.33 | 25.63 | 41.67 | 25.61 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 24.00 | 25.69 | 24.00 | 25.69 |
December | 0.67 | 19.36 | 0.00 | 19.36 | 6.00 | 26.37 | 6.00 | 26.74 |
Annual Sum or Average | 1.67 | 19.02 | 0.00 | 19.02 | 131.00 | 26.10 | 128.00 | 26.13 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.46 | 0.17 | 25.56 |
Maximum of Months | 0.67 | 19.36 | 0.00 | 19.36 | 42.33 | 27.76 | 41.67 | 27.76 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.67 | 18.30 | 0.00 | 18.30 | 0.00 | 18.30 | 0.00 | 18.30 |
February | 0.83 | 18.56 | 0.00 | 18.56 | 0.00 | 18.56 | 0.00 | 18.56 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.86 | 0.50 | 27.85 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 28.08 | 2.33 | 28.09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 28.15 | 2.67 | 28.22 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 28.59 | 3.33 | 28.66 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 11.33 | 28.06 | 5.50 | 28.23 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 28.03 | 3.50 | 28.18 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 28.13 | 3.50 | 28.18 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 28.00 | 2.50 | 28.04 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.67 | 19.32 | 0.00 | 19.32 | 0.00 | 19.32 | 0.00 | 19.32 |
Annual Sum or Average | 2.17 | 18.71 | 0.00 | 18.71 | 42.17 | 27.70 | 23.83 | 27.95 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.83 | 19.32 | 0.00 | 19.32 | 11.33 | 28.59 | 5.50 | 28.66 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 20.33 | 17.30 | 4.50 | 17.45 | 0.00 | 17.45 | 0.00 | 17.45 |
February | 15.00 | 17.07 | 3.00 | 17.20 | 0.00 | 17.20 | 0.00 | 17.20 |
March | 2.50 | 18.74 | 0.00 | 18.74 | 0.00 | 18.74 | 0.00 | 18.74 |
April | 0.17 | 19.22 | 0.00 | 19.22 | 0.00 | 19.22 | 0.00 | 19.22 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.57 | 1.83 | 27.55 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 27.52 | 5.33 | 27.56 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.56 | 2.17 | 27.57 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.27 | 0.17 | 27.27 |
October | 0.50 | 19.09 | 0.00 | 19.09 | 0.00 | 19.09 | 0.00 | 19.09 |
November | 5.33 | 18.47 | 0.50 | 18.46 | 0.00 | 18.46 | 0.00 | 18.46 |
December | 19.17 | 17.45 | 4.33 | 17.56 | 0.00 | 17.56 | 0.00 | 17.56 |
Annual Sum or Average | 63.00 | 17.47 | 12.33 | 17.56 | 14.67 | 19.19 | 9.50 | 19.99 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 20.33 | 19.22 | 4.50 | 19.22 | 7.83 | 27.57 | 5.33 | 27.57 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 12.83 | 16.93 | 0.67 | 16.83 | 0.00 | 16.83 | 0.00 | 16.83 |
February | 10.33 | 17.01 | 0.83 | 16.93 | 0.00 | 16.93 | 0.00 | 16.93 |
March | 1.50 | 18.70 | 0.00 | 18.70 | 0.00 | 18.70 | 0.00 | 18.70 |
April | 0.17 | 19.28 | 0.00 | 19.28 | 1.17 | 27.00 | 1.17 | 27.51 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 27.82 | 9.67 | 27.83 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 28.08 | 9.33 | 28.10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 19.50 | 28.29 | 16.33 | 28.35 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 12.33 | 28.23 | 10.50 | 28.27 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 28.05 | 3.83 | 28.07 |
October | 0.67 | 18.65 | 0.00 | 18.65 | 1.00 | 24.22 | 1.00 | 25.62 |
November | 3.67 | 18.59 | 0.00 | 18.59 | 0.00 | 18.59 | 0.00 | 18.59 |
December | 12.17 | 17.18 | 0.33 | 17.12 | 0.00 | 17.12 | 0.00 | 17.12 |
Annual Sum or Average | 41.33 | 17.27 | 1.83 | 17.19 | 58.33 | 23.48 | 51.83 | 25.08 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.83 | 0.00 | 16.83 |
Maximum of Months | 12.83 | 19.28 | 0.83 | 19.28 | 19.50 | 28.29 | 16.33 | 28.35 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 9.83 | 17.69 | 0.17 | 17.74 | 1.17 | 18.74 | 1.17 | 19.56 |
February | 6.83 | 17.99 | 0.33 | 18.09 | 1.50 | 19.75 | 1.50 | 20.91 |
March | 0.83 | 18.87 | 0.00 | 18.87 | 1.83 | 24.91 | 1.83 | 26.03 |
April | 0.17 | 19.40 | 0.00 | 19.40 | 0.83 | 26.15 | 0.83 | 26.76 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.35 | 1.83 | 27.35 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.60 | 2.33 | 27.62 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 27.69 | 8.67 | 27.74 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 27.86 | 6.67 | 27.92 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 13.83 | 26.80 | 13.17 | 26.79 |
October | 0.33 | 19.12 | 0.00 | 19.12 | 18.83 | 26.02 | 18.33 | 26.06 |
November | 1.50 | 18.49 | 0.00 | 18.49 | 4.67 | 24.55 | 4.67 | 25.39 |
December | 8.67 | 18.16 | 0.17 | 18.20 | 1.00 | 19.19 | 1.00 | 19.99 |
Annual Sum or Average | 28.17 | 18.01 | 0.67 | 18.07 | 69.00 | 24.38 | 62.00 | 25.38 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 18.74 | 0.83 | 19.56 |
Maximum of Months | 9.83 | 19.40 | 0.33 | 19.40 | 18.83 | 27.86 | 18.33 | 27.92 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 10.00 | 17.52 | 0.00 | 17.52 | 0.00 | 17.52 | 0.00 | 17.52 |
February | 6.33 | 17.98 | 0.00 | 17.98 | 0.00 | 17.98 | 0.00 | 17.98 |
March | 0.67 | 18.88 | 0.00 | 18.88 | 0.33 | 21.84 | 0.17 | 22.69 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 28.05 | 2.17 | 28.07 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 28.20 | 2.83 | 28.26 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 28.40 | 4.00 | 28.38 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 13.00 | 28.28 | 6.33 | 28.43 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 28.37 | 4.33 | 28.45 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 28.10 | 4.00 | 28.12 |
October | 0.33 | 19.21 | 0.00 | 19.21 | 2.67 | 27.00 | 2.50 | 27.45 |
November | 1.67 | 18.48 | 0.00 | 18.48 | 0.00 | 18.48 | 0.00 | 18.48 |
December | 7.67 | 18.36 | 0.00 | 18.36 | 0.00 | 18.36 | 0.00 | 18.36 |
Annual Sum or Average | 26.67 | 17.99 | 0.00 | 17.99 | 47.00 | 24.54 | 26.33 | 25.55 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.52 | 0.00 | 17.52 |
Maximum of Months | 10.00 | 19.21 | 0.00 | 19.21 | 13.00 | 28.40 | 6.33 | 28.45 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 21.50 | 27.93 | 13.33 | 27.91 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 104.50 | 28.07 | 93.00 | 28.03 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 126.00 | 28.04 | 106.33 | 28.02 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 104.50 | 28.07 | 93.00 | 28.03 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 27.91 | 7.00 | 27.88 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 53.83 | 27.86 | 46.83 | 27.83 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 63.33 | 27.87 | 53.83 | 27.84 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 53.83 | 27.91 | 46.83 | 27.88 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.91 | 3.00 | 27.88 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 38.67 | 27.97 | 30.33 | 27.90 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 43.33 | 27.96 | 33.33 | 27.90 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 38.67 | 27.97 | 30.33 | 27.90 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 708.50 | 28.91 | 479.33 | 28.94 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 28.31 | 0.00 | 28.31 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 743.17 | 31.88 | 514.00 | 31.95 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 623.67 | 27.93 | 382.67 | 27.91 |
Annual Sum or Average | 0.00 | 0.00 | 2076.33 | 29.68 | 1376.00 | 29.74 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 743.17 | 31.88 | 514.00 | 31.95 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 244.17 | 24.01 | 68.17 | 24.51 | 0.00 | 24.51 |
February | 218.17 | 24.00 | 63.50 | 24.53 | 0.00 | 24.53 |
March | 191.50 | 24.00 | 62.17 | 24.55 | 0.00 | 24.55 |
April | 177.67 | 24.00 | 76.83 | 24.75 | 0.00 | 24.75 |
May | 124.83 | 24.00 | 136.17 | 24.76 | 0.67 | 24.75 |
June | 9.00 | 24.00 | 279.33 | 24.77 | 0.00 | 24.77 |
July | 118.50 | 24.42 | 470.50 | 24.60 | 118.50 | 24.57 |
August | 83.00 | 24.31 | 492.17 | 24.48 | 83.00 | 24.46 |
September | 14.33 | 24.84 | 366.67 | 24.74 | 14.33 | 24.75 |
October | 71.50 | 24.00 | 185.17 | 25.10 | 0.00 | 25.10 |
November | 99.33 | 24.00 | 101.33 | 25.27 | 0.00 | 25.27 |
December | 227.33 | 24.01 | 84.83 | 24.70 | 0.00 | 24.70 |
Annual Sum or Average | 1579.33 | 24.06 | 2386.83 | 24.69 | 216.50 | 24.67 |
Minimum of Months | 9.00 | 24.00 | 62.17 | 24.48 | 0.00 | 24.46 |
Maximum of Months | 244.17 | 24.84 | 492.17 | 25.27 | 118.50 | 25.27 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 310.50 | 23.95 | 9.17 | 24.00 | 0.00 | 24.00 |
February | 192.00 | 23.98 | 22.67 | 24.18 | 0.00 | 24.18 |
March | 153.17 | 24.00 | 40.33 | 24.42 | 0.00 | 24.42 |
April | 119.17 | 24.01 | 29.50 | 24.40 | 0.00 | 24.40 |
May | 103.33 | 24.01 | 124.17 | 24.43 | 1.17 | 24.43 |
June | 3.67 | 24.04 | 295.83 | 24.31 | 0.00 | 24.31 |
July | 153.00 | 24.36 | 475.67 | 24.28 | 153.00 | 24.30 |
August | 57.33 | 24.29 | 512.67 | 24.22 | 57.33 | 24.23 |
September | 18.83 | 24.34 | 374.50 | 24.43 | 18.83 | 24.43 |
October | 76.17 | 24.00 | 167.50 | 24.59 | 0.00 | 24.59 |
November | 119.83 | 24.00 | 60.33 | 24.61 | 0.00 | 24.61 |
December | 204.67 | 24.00 | 45.83 | 24.40 | 0.00 | 24.40 |
Annual Sum or Average | 1511.67 | 24.04 | 2158.17 | 24.33 | 230.33 | 24.33 |
Minimum of Months | 3.67 | 23.95 | 9.17 | 24.00 | 0.00 | 24.00 |
Maximum of Months | 310.50 | 24.36 | 512.67 | 24.61 | 153.00 | 24.61 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 23.37 | 0.00 | 23.37 | 0.00 | 23.37 |
February | 424.83 | 23.61 | 0.00 | 23.61 | 0.00 | 23.61 |
March | 419.50 | 23.84 | 0.67 | 23.84 | 0.00 | 23.84 |
April | 309.67 | 23.94 | 2.50 | 23.96 | 0.00 | 23.96 |
May | 179.33 | 23.96 | 86.00 | 24.13 | 1.33 | 24.13 |
June | 27.17 | 23.90 | 239.67 | 24.27 | 0.00 | 24.27 |
July | 154.50 | 24.18 | 463.00 | 24.23 | 154.50 | 24.22 |
August | 102.50 | 24.17 | 476.67 | 24.21 | 102.50 | 24.20 |
September | 23.67 | 24.27 | 327.33 | 24.35 | 19.83 | 24.35 |
October | 211.50 | 23.86 | 98.67 | 24.06 | 0.50 | 24.06 |
November | 407.33 | 23.77 | 1.00 | 23.78 | 0.00 | 23.78 |
December | 496.50 | 23.46 | 0.00 | 23.46 | 0.00 | 23.46 |
Annual Sum or Average | 3258.50 | 23.72 | 1695.50 | 23.92 | 278.67 | 23.93 |
Minimum of Months | 23.67 | 23.37 | 0.00 | 23.37 | 0.00 | 23.37 |
Maximum of Months | 502.00 | 24.27 | 476.67 | 24.35 | 154.50 | 24.35 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.74 | 147.00 | 21.39 | 147.00 | 21.17 |
February | 452.17 | 22.29 | 66.83 | 22.06 | 66.83 | 21.89 |
March | 498.33 | 23.17 | 10.83 | 23.11 | 10.83 | 23.07 |
April | 355.67 | 23.71 | 1.17 | 23.71 | 0.00 | 23.71 |
May | 185.50 | 23.74 | 77.33 | 23.94 | 1.50 | 23.94 |
June | 29.17 | 23.76 | 264.33 | 24.24 | 0.00 | 24.24 |
July | 146.83 | 24.24 | 472.33 | 24.28 | 146.83 | 24.28 |
August | 96.67 | 24.20 | 490.50 | 24.25 | 96.67 | 24.24 |
September | 44.33 | 23.96 | 313.67 | 24.28 | 22.83 | 24.27 |
October | 302.33 | 23.35 | 82.17 | 23.55 | 2.00 | 23.55 |
November | 464.50 | 22.63 | 41.50 | 22.47 | 41.50 | 22.33 |
December | 497.00 | 21.77 | 159.00 | 21.44 | 159.00 | 21.24 |
Annual Sum or Average | 3574.50 | 22.78 | 2126.67 | 23.05 | 695.00 | 22.92 |
Minimum of Months | 29.17 | 21.74 | 1.17 | 21.39 | 0.00 | 21.17 |
Maximum of Months | 502.00 | 24.24 | 490.50 | 24.28 | 159.00 | 24.28 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 22.25 | 24.17 | 22.19 | 24.17 | 22.14 |
February | 452.00 | 22.74 | 13.00 | 22.69 | 13.00 | 22.64 |
March | 476.83 | 23.45 | 0.00 | 23.45 | 0.00 | 23.45 |
April | 297.33 | 23.86 | 6.00 | 23.89 | 0.00 | 23.89 |
May | 154.50 | 23.83 | 104.17 | 24.17 | 0.83 | 24.17 |
June | 4.50 | 24.32 | 349.50 | 24.41 | 0.67 | 24.41 |
July | 109.67 | 25.12 | 489.83 | 24.56 | 109.67 | 24.65 |
August | 56.33 | 24.89 | 509.67 | 24.37 | 56.33 | 24.42 |
September | 38.67 | 24.03 | 331.00 | 24.37 | 14.50 | 24.37 |
October | 299.50 | 23.53 | 98.50 | 23.73 | 0.00 | 23.73 |
November | 463.67 | 23.22 | 0.00 | 23.22 | 0.00 | 23.22 |
December | 497.00 | 22.62 | 8.17 | 22.59 | 8.17 | 22.57 |
Annual Sum or Average | 3352.00 | 23.17 | 1934.00 | 23.59 | 227.33 | 23.62 |
Minimum of Months | 4.50 | 22.25 | 0.00 | 22.19 | 0.00 | 22.14 |
Maximum of Months | 502.00 | 25.12 | 509.67 | 24.56 | 109.67 | 24.65 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 467.83 | 22.34 | 29.50 | 22.31 | 24.17 | 22.25 |
February | 400.50 | 22.70 | 15.67 | 22.73 | 7.50 | 22.70 |
March | 333.17 | 23.14 | 33.83 | 23.32 | 0.50 | 23.32 |
April | 188.00 | 23.67 | 90.83 | 24.08 | 4.50 | 24.13 |
May | 123.17 | 24.19 | 207.83 | 24.54 | 20.83 | 24.69 |
June | 30.67 | 25.87 | 384.83 | 24.53 | 21.00 | 24.65 |
July | 120.33 | 25.60 | 486.33 | 24.71 | 120.33 | 24.85 |
August | 73.50 | 25.40 | 497.33 | 24.43 | 71.33 | 24.55 |
September | 52.17 | 24.80 | 391.83 | 24.49 | 30.17 | 24.57 |
October | 208.50 | 23.30 | 164.33 | 23.92 | 5.33 | 23.96 |
November | 398.17 | 23.00 | 18.33 | 23.11 | 0.67 | 23.10 |
December | 472.67 | 22.41 | 23.83 | 22.36 | 22.50 | 22.30 |
Annual Sum or Average | 2868.67 | 23.12 | 2344.50 | 23.71 | 328.83 | 23.79 |
Minimum of Months | 30.67 | 22.34 | 15.67 | 22.31 | 0.50 | 22.25 |
Maximum of Months | 472.67 | 25.87 | 497.33 | 24.71 | 120.33 | 24.85 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 326.83 | 22.68 | 102.17 | 23.05 | 30.67 | 22.97 |
February | 258.33 | 22.99 | 83.33 | 23.37 | 13.17 | 23.35 |
March | 275.50 | 23.41 | 52.67 | 23.68 | 2.17 | 23.70 |
April | 184.67 | 23.74 | 53.00 | 24.08 | 0.50 | 24.09 |
May | 154.00 | 23.72 | 133.50 | 24.18 | 2.00 | 24.19 |
June | 28.00 | 24.12 | 315.33 | 24.37 | 3.50 | 24.40 |
July | 116.17 | 25.24 | 485.50 | 24.60 | 116.17 | 24.70 |
August | 67.17 | 25.40 | 512.67 | 24.47 | 67.17 | 24.57 |
September | 55.00 | 25.84 | 399.33 | 24.73 | 45.67 | 24.87 |
October | 139.67 | 24.00 | 248.00 | 24.53 | 23.00 | 24.68 |
November | 237.67 | 23.53 | 124.00 | 24.06 | 9.67 | 24.13 |
December | 296.17 | 23.00 | 97.17 | 23.38 | 18.50 | 23.37 |
Annual Sum or Average | 2139.17 | 23.53 | 2606.67 | 24.09 | 332.17 | 24.15 |
Minimum of Months | 28.00 | 22.68 | 52.67 | 23.05 | 0.50 | 22.97 |
Maximum of Months | 326.83 | 25.84 | 512.67 | 24.73 | 116.17 | 24.87 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 418.67 | 22.63 | 11.67 | 22.72 | 0.00 | 22.72 |
February | 284.67 | 23.24 | 47.50 | 23.48 | 0.67 | 23.49 |
March | 128.00 | 23.80 | 108.17 | 24.42 | 7.50 | 24.50 |
April | 34.17 | 25.84 | 229.50 | 25.23 | 20.17 | 25.37 |
May | 66.00 | 24.33 | 268.17 | 24.63 | 13.67 | 24.72 |
June | 25.67 | 26.80 | 446.50 | 24.64 | 23.67 | 24.75 |
July | 126.00 | 25.65 | 497.00 | 24.81 | 126.00 | 24.95 |
August | 124.83 | 25.95 | 514.00 | 24.82 | 124.83 | 25.01 |
September | 34.83 | 26.00 | 427.00 | 24.68 | 34.83 | 24.77 |
October | 107.83 | 23.98 | 239.00 | 24.53 | 14.00 | 24.64 |
November | 164.83 | 23.71 | 77.50 | 24.18 | 2.00 | 24.21 |
December | 245.67 | 23.71 | 57.83 | 24.04 | 1.50 | 24.06 |
Annual Sum or Average | 1761.17 | 23.85 | 2923.83 | 24.38 | 368.83 | 24.51 |
Minimum of Months | 25.67 | 22.63 | 11.67 | 22.72 | 0.00 | 22.72 |
Maximum of Months | 418.67 | 26.80 | 514.00 | 25.23 | 126.00 | 25.37 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.74 | 329.33 | 20.58 | 329.33 | 20.52 |
February | 454.00 | 21.17 | 197.83 | 20.96 | 197.83 | 20.85 |
March | 514.00 | 22.24 | 66.50 | 22.06 | 66.50 | 21.92 |
April | 435.50 | 23.24 | 3.50 | 23.22 | 3.50 | 23.21 |
May | 250.00 | 23.57 | 66.33 | 23.77 | 1.00 | 23.77 |
June | 28.67 | 23.63 | 290.83 | 24.35 | 0.17 | 24.35 |
July | 110.17 | 24.60 | 486.33 | 24.47 | 110.17 | 24.49 |
August | 71.67 | 24.26 | 485.50 | 24.29 | 70.33 | 24.28 |
September | 78.00 | 23.59 | 256.50 | 24.13 | 14.17 | 24.12 |
October | 379.67 | 22.60 | 76.00 | 22.69 | 23.50 | 22.60 |
November | 489.00 | 21.58 | 139.00 | 21.34 | 139.00 | 21.19 |
December | 497.00 | 20.67 | 367.83 | 20.56 | 367.83 | 20.52 |
Annual Sum or Average | 3809.67 | 22.01 | 2765.50 | 22.33 | 1323.33 | 22.11 |
Minimum of Months | 28.67 | 20.67 | 3.50 | 20.56 | 0.17 | 20.52 |
Maximum of Months | 514.00 | 24.60 | 486.33 | 24.47 | 367.83 | 24.49 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 21.22 | 197.33 | 21.00 | 197.33 | 20.89 |
February | 371.00 | 21.59 | 99.00 | 21.36 | 97.33 | 21.20 |
March | 365.83 | 22.48 | 28.17 | 22.51 | 16.00 | 22.44 |
April | 198.67 | 23.31 | 74.50 | 23.84 | 4.17 | 23.87 |
May | 144.33 | 23.92 | 155.33 | 24.46 | 22.67 | 24.64 |
June | 46.83 | 25.28 | 306.67 | 24.71 | 24.67 | 24.86 |
July | 113.83 | 25.85 | 411.17 | 24.96 | 113.83 | 25.12 |
August | 76.67 | 25.58 | 416.00 | 24.67 | 74.17 | 24.80 |
September | 73.00 | 24.24 | 287.50 | 24.46 | 28.83 | 24.56 |
October | 239.83 | 22.76 | 118.67 | 23.30 | 15.67 | 23.27 |
November | 389.33 | 21.97 | 49.00 | 21.85 | 45.17 | 21.74 |
December | 422.00 | 21.08 | 221.83 | 20.87 | 221.83 | 20.76 |
Annual Sum or Average | 2868.33 | 22.36 | 2365.17 | 22.94 | 861.67 | 22.84 |
Minimum of Months | 46.83 | 21.08 | 28.17 | 20.87 | 4.17 | 20.76 |
Maximum of Months | 427.00 | 25.85 | 416.00 | 24.96 | 221.83 | 25.12 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 341.67 | 22.22 | 168.67 | 22.45 | 96.00 | 22.24 |
February | 278.33 | 22.45 | 109.33 | 22.79 | 41.17 | 22.66 |
March | 332.00 | 22.91 | 52.00 | 23.13 | 8.50 | 23.11 |
April | 255.00 | 23.35 | 34.17 | 23.63 | 0.00 | 23.63 |
May | 199.83 | 23.51 | 99.83 | 23.91 | 1.17 | 23.92 |
June | 56.50 | 23.61 | 280.67 | 24.28 | 1.67 | 24.29 |
July | 118.67 | 25.04 | 479.50 | 24.58 | 118.67 | 24.66 |
August | 77.17 | 25.08 | 497.33 | 24.48 | 77.17 | 24.55 |
September | 71.50 | 25.35 | 377.83 | 24.69 | 50.00 | 24.83 |
October | 173.83 | 23.67 | 240.00 | 24.36 | 30.00 | 24.51 |
November | 270.00 | 22.97 | 128.33 | 23.55 | 21.67 | 23.56 |
December | 320.67 | 22.29 | 161.17 | 22.43 | 92.50 | 22.22 |
Annual Sum or Average | 2495.17 | 23.09 | 2628.83 | 23.71 | 538.50 | 23.69 |
Minimum of Months | 56.50 | 22.22 | 34.17 | 22.43 | 0.00 | 22.22 |
Maximum of Months | 341.67 | 25.35 | 497.33 | 24.69 | 118.67 | 24.83 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 484.33 | 21.31 | 185.17 | 21.09 | 185.17 | 20.96 |
February | 403.17 | 21.66 | 92.67 | 21.48 | 90.00 | 21.35 |
March | 424.33 | 22.37 | 40.83 | 22.47 | 15.83 | 22.42 |
April | 275.67 | 23.22 | 68.33 | 23.57 | 5.33 | 23.63 |
May | 161.50 | 23.40 | 169.67 | 24.02 | 10.00 | 24.10 |
June | 51.83 | 24.38 | 363.17 | 24.48 | 16.67 | 24.58 |
July | 121.00 | 24.89 | 495.17 | 24.56 | 121.00 | 24.61 |
August | 75.83 | 24.82 | 508.17 | 24.43 | 75.83 | 24.48 |
September | 73.33 | 24.21 | 349.00 | 24.42 | 30.83 | 24.51 |
October | 281.83 | 22.70 | 123.17 | 23.23 | 10.17 | 23.27 |
November | 433.00 | 21.99 | 53.67 | 21.88 | 47.17 | 21.76 |
December | 483.00 | 21.35 | 201.50 | 21.12 | 201.50 | 21.00 |
Annual Sum or Average | 3268.83 | 22.30 | 2650.50 | 22.92 | 809.50 | 22.82 |
Minimum of Months | 51.83 | 21.31 | 40.83 | 21.09 | 5.33 | 20.96 |
Maximum of Months | 484.33 | 24.89 | 508.17 | 24.56 | 201.50 | 24.61 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.13 | 440.33 | 20.05 | 440.33 | 20.03 |
February | 454.00 | 20.52 | 323.17 | 20.36 | 323.17 | 20.29 |
March | 514.00 | 21.54 | 184.33 | 21.25 | 184.33 | 21.08 |
April | 433.50 | 22.77 | 50.17 | 22.55 | 50.17 | 22.37 |
May | 268.33 | 23.22 | 70.83 | 23.40 | 11.00 | 23.34 |
June | 52.67 | 23.56 | 304.33 | 24.29 | 4.17 | 24.32 |
July | 121.83 | 24.99 | 487.00 | 24.56 | 121.83 | 24.63 |
August | 78.17 | 24.50 | 482.17 | 24.33 | 73.67 | 24.36 |
September | 130.17 | 23.41 | 236.83 | 23.97 | 17.67 | 23.97 |
October | 407.67 | 22.07 | 136.83 | 22.01 | 91.00 | 21.82 |
November | 489.00 | 20.76 | 293.00 | 20.50 | 293.00 | 20.38 |
December | 497.00 | 20.08 | 473.00 | 20.05 | 473.00 | 20.04 |
Annual Sum or Average | 3948.33 | 21.52 | 3482.00 | 21.79 | 2083.33 | 21.53 |
Minimum of Months | 52.67 | 20.08 | 50.17 | 20.05 | 4.17 | 20.03 |
Maximum of Months | 514.00 | 24.99 | 487.00 | 24.56 | 473.00 | 24.63 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.58 | 344.00 | 20.38 | 344.00 | 20.30 |
February | 452.17 | 21.10 | 203.50 | 20.79 | 203.50 | 20.63 |
March | 450.33 | 22.17 | 86.17 | 21.96 | 81.83 | 21.78 |
April | 220.50 | 23.04 | 81.33 | 23.38 | 16.33 | 23.30 |
May | 170.33 | 23.79 | 197.17 | 24.30 | 31.00 | 24.47 |
June | 58.17 | 25.12 | 386.83 | 24.58 | 30.50 | 24.74 |
July | 128.50 | 25.65 | 488.17 | 24.82 | 128.50 | 24.96 |
August | 88.33 | 25.41 | 495.67 | 24.58 | 84.17 | 24.70 |
September | 94.67 | 23.92 | 353.83 | 24.29 | 33.67 | 24.38 |
October | 296.83 | 22.52 | 146.83 | 22.84 | 43.50 | 22.71 |
November | 480.83 | 21.43 | 175.50 | 21.13 | 173.33 | 20.94 |
December | 497.00 | 20.40 | 362.17 | 20.24 | 362.17 | 20.18 |
Annual Sum or Average | 3439.67 | 21.91 | 3321.17 | 22.41 | 1532.50 | 22.21 |
Minimum of Months | 58.17 | 20.40 | 81.33 | 20.24 | 16.33 | 20.18 |
Maximum of Months | 502.00 | 25.65 | 495.67 | 24.82 | 362.17 | 24.96 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 376.67 | 21.43 | 214.67 | 21.33 | 172.67 | 21.07 |
February | 314.50 | 21.69 | 160.50 | 21.63 | 115.33 | 21.36 |
March | 370.83 | 22.28 | 113.00 | 22.22 | 78.17 | 22.01 |
April | 278.17 | 22.84 | 64.50 | 22.91 | 29.50 | 22.74 |
May | 233.17 | 23.14 | 106.33 | 23.54 | 11.00 | 23.48 |
June | 76.67 | 23.41 | 285.33 | 24.20 | 5.83 | 24.24 |
July | 122.00 | 25.07 | 479.00 | 24.59 | 122.00 | 24.67 |
August | 81.00 | 25.03 | 493.83 | 24.47 | 77.50 | 24.54 |
September | 98.17 | 24.56 | 353.17 | 24.53 | 47.33 | 24.68 |
October | 208.00 | 23.00 | 239.83 | 23.70 | 48.33 | 23.68 |
November | 316.83 | 22.16 | 145.67 | 22.33 | 71.33 | 22.07 |
December | 357.33 | 21.40 | 185.50 | 21.18 | 157.50 | 20.90 |
Annual Sum or Average | 2833.33 | 22.46 | 2841.33 | 23.01 | 936.50 | 22.84 |
Minimum of Months | 76.67 | 21.40 | 64.50 | 21.18 | 5.83 | 20.90 |
Maximum of Months | 376.67 | 25.07 | 493.83 | 24.59 | 172.67 | 24.68 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 494.17 | 20.76 | 317.50 | 20.51 | 317.50 | 20.40 |
February | 416.50 | 21.13 | 194.83 | 20.86 | 193.00 | 20.72 |
March | 436.83 | 21.78 | 118.17 | 21.71 | 97.67 | 21.55 |
April | 298.00 | 22.74 | 88.67 | 23.03 | 26.33 | 22.98 |
May | 210.00 | 23.06 | 163.33 | 23.69 | 15.00 | 23.74 |
June | 73.50 | 23.90 | 360.67 | 24.39 | 18.67 | 24.50 |
July | 120.00 | 24.92 | 493.00 | 24.55 | 120.00 | 24.61 |
August | 76.17 | 24.81 | 499.00 | 24.43 | 73.17 | 24.48 |
September | 114.67 | 23.70 | 319.83 | 24.25 | 33.33 | 24.34 |
October | 314.17 | 22.25 | 151.67 | 22.65 | 49.83 | 22.55 |
November | 454.00 | 21.36 | 158.50 | 21.10 | 153.00 | 20.92 |
December | 493.50 | 20.81 | 332.33 | 20.56 | 332.33 | 20.45 |
Annual Sum or Average | 3501.50 | 21.85 | 3197.50 | 22.37 | 1429.83 | 22.17 |
Minimum of Months | 73.50 | 20.76 | 88.67 | 20.51 | 15.00 | 20.40 |
Maximum of Months | 494.17 | 24.92 | 499.00 | 24.55 | 332.33 | 24.61 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 502.00 | 27.00 | 0.00 | 27.00 |
February | 2.67 | 27.00 | 454.00 | 27.00 | 2.67 | 27.00 |
March | 13.33 | 27.00 | 514.00 | 27.00 | 13.33 | 27.00 |
April | 54.67 | 27.31 | 485.00 | 27.07 | 54.67 | 27.09 |
May | 0.50 | 27.00 | 508.00 | 27.00 | 0.50 | 27.00 |
June | 21.50 | 27.00 | 496.00 | 27.00 | 21.50 | 27.00 |
July | 134.83 | 27.00 | 497.00 | 27.00 | 134.83 | 27.00 |
August | 420.00 | 27.28 | 514.00 | 27.25 | 420.00 | 27.26 |
September | 11.00 | 27.00 | 485.00 | 27.00 | 11.00 | 27.00 |
October | 22.17 | 27.00 | 502.00 | 27.00 | 22.17 | 27.00 |
November | 14.67 | 27.00 | 489.00 | 27.00 | 14.67 | 27.00 |
December | 16.17 | 27.00 | 497.00 | 27.00 | 16.17 | 27.00 |
Annual Sum or Average | 711.50 | 27.19 | 5943.00 | 27.04 | 711.50 | 27.06 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 420.00 | 27.31 | 514.00 | 27.25 | 420.00 | 27.26 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 449.17 | 27.00 | 0.00 | 27.00 |
February | 0.00 | 0.00 | 437.83 | 27.00 | 0.00 | 27.00 |
March | 0.00 | 0.00 | 514.00 | 27.00 | 0.00 | 27.00 |
April | 9.67 | 27.67 | 485.00 | 27.03 | 9.67 | 27.04 |
May | 0.00 | 0.00 | 508.00 | 27.00 | 0.00 | 27.00 |
June | 4.17 | 27.00 | 496.00 | 27.00 | 4.17 | 27.00 |
July | 9.50 | 27.00 | 497.00 | 27.00 | 9.50 | 27.00 |
August | 88.33 | 27.58 | 514.00 | 27.18 | 88.33 | 27.23 |
September | 1.67 | 27.00 | 485.00 | 27.00 | 1.67 | 27.00 |
October | 6.00 | 27.00 | 502.00 | 27.00 | 6.00 | 27.00 |
November | 0.17 | 27.00 | 489.00 | 27.00 | 0.17 | 27.00 |
December | 0.00 | 0.00 | 457.33 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 119.50 | 27.48 | 5834.33 | 27.02 | 119.50 | 27.03 |
Minimum of Months | 0.00 | 0.00 | 437.83 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 88.33 | 27.67 | 514.00 | 27.18 | 88.33 | 27.23 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 83.00 | 25.34 | 268.83 | 26.61 | 0.00 | 26.61 |
February | 11.67 | 27.00 | 331.33 | 27.00 | 0.00 | 27.00 |
March | 0.00 | 0.00 | 475.17 | 27.00 | 0.00 | 27.00 |
April | 10.17 | 27.44 | 483.00 | 27.02 | 10.17 | 27.03 |
May | 0.00 | 0.00 | 502.67 | 27.00 | 0.00 | 27.00 |
June | 13.50 | 27.00 | 496.00 | 27.00 | 13.50 | 27.00 |
July | 70.00 | 27.00 | 497.00 | 27.00 | 70.00 | 27.00 |
August | 106.67 | 27.41 | 514.00 | 27.14 | 106.67 | 27.18 |
September | 7.33 | 27.00 | 485.00 | 27.00 | 7.33 | 27.00 |
October | 8.00 | 27.00 | 488.33 | 27.00 | 8.00 | 27.00 |
November | 0.00 | 0.00 | 422.50 | 27.00 | 0.00 | 27.00 |
December | 23.83 | 27.00 | 313.50 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 334.17 | 26.73 | 5277.33 | 26.99 | 215.67 | 27.00 |
Minimum of Months | 0.00 | 0.00 | 268.83 | 26.61 | 0.00 | 26.61 |
Maximum of Months | 106.67 | 27.44 | 514.00 | 27.14 | 106.67 | 27.18 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 27.00 | 502.00 | 27.00 | 502.00 | 27.00 |
February | 454.00 | 27.02 | 454.00 | 27.02 | 454.00 | 27.02 |
March | 514.00 | 27.01 | 514.00 | 27.01 | 514.00 | 27.01 |
April | 485.00 | 28.96 | 485.00 | 28.96 | 485.00 | 28.96 |
May | 508.00 | 27.00 | 508.00 | 27.00 | 508.00 | 27.00 |
June | 496.00 | 27.01 | 496.00 | 27.01 | 496.00 | 27.01 |
July | 497.00 | 27.01 | 497.00 | 27.01 | 497.00 | 27.01 |
August | 514.00 | 32.05 | 514.00 | 32.05 | 514.00 | 32.05 |
September | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
October | 502.00 | 27.01 | 502.00 | 27.01 | 502.00 | 27.01 |
November | 489.00 | 27.01 | 489.00 | 27.01 | 489.00 | 27.01 |
December | 497.00 | 27.77 | 497.00 | 27.77 | 497.00 | 27.77 |
Annual Sum or Average | 5943.00 | 27.67 | 5943.00 | 27.67 | 5943.00 | 27.67 |
Minimum of Months | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
Maximum of Months | 514.00 | 32.05 | 514.00 | 32.05 | 514.00 | 32.05 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00000 | 16.97076 | 0.71913 | 15.97613 |
February | 454.00000 | 27.00002 | 17.42148 | 0.77993 | 17.91448 |
March | 514.00000 | 27.00001 | 18.11163 | 0.84102 | 19.99254 |
April | 485.00000 | 27.04047 | 16.85234 | 0.90599 | 22.42323 |
May | 508.00000 | 27.00019 | 20.18005 | 0.15441 | 5.60306 |
June | 496.00000 | 27.00040 | 24.53797 | 0.25762 | 6.46027 |
July | 497.00000 | 27.00049 | 27.17158 | 0.33216 | 7.36083 |
August | 514.00000 | 27.22892 | 26.96717 | 0.47724 | 10.19688 |
September | 485.00000 | 27.00077 | 25.65006 | 0.21747 | 6.06894 |
October | 502.00000 | 27.00025 | 21.07679 | 0.85580 | 20.55876 |
November | 489.00000 | 27.00004 | 18.27587 | 0.83992 | 19.95984 |
December | 497.00000 | 26.99999 | 14.79871 | 0.82945 | 19.59338 |
Annual Sum or Average | 5943.00000 | 27.02328 | 20.69861 | 0.59926 | 14.30540 |
Minimum of Months | 454.00000 | 26.99999 | 14.79871 | 0.15441 | 5.60306 |
Maximum of Months | 514.00000 | 27.22892 | 27.17158 | 0.90599 | 22.42323 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.99996 | 16.95211 | 0.61324 | 13.02507 |
February | 454.00000 | 27.00002 | 17.40245 | 0.66143 | 14.35953 |
March | 514.00000 | 27.00001 | 18.08529 | 0.72366 | 16.14952 |
April | 485.00000 | 27.01888 | 16.83959 | 0.78036 | 17.96509 |
May | 508.00000 | 27.00017 | 20.18895 | 0.08790 | 5.31466 |
June | 496.00000 | 27.00038 | 24.54556 | 0.18012 | 5.78649 |
July | 497.00000 | 27.00051 | 27.18942 | 0.23829 | 6.25963 |
August | 514.00000 | 27.10903 | 27.08680 | 0.28465 | 6.94711 |
September | 485.00000 | 27.00069 | 25.75037 | 0.15420 | 5.60555 |
October | 502.00000 | 27.00024 | 21.07425 | 0.77173 | 17.71648 |
November | 489.00000 | 27.00004 | 18.25818 | 0.70659 | 15.63837 |
December | 497.00000 | 26.99999 | 14.77541 | 0.64152 | 13.79893 |
Annual Sum or Average | 5943.00000 | 27.01114 | 20.71006 | 0.48525 | 11.51626 |
Minimum of Months | 454.00000 | 26.99996 | 14.77541 | 0.08790 | 5.31466 |
Maximum of Months | 514.00000 | 27.10903 | 27.18942 | 0.78036 | 17.96509 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.69216 | 17.23528 | 0.47317 | 10.63392 |
February | 454.00000 | 27.00002 | 17.41791 | 0.58914 | 12.59344 |
March | 514.00000 | 27.00001 | 18.10106 | 0.67216 | 14.75447 |
April | 485.00000 | 27.01180 | 16.85756 | 0.75712 | 17.31273 |
May | 508.00000 | 27.00015 | 20.21104 | 0.07906 | 5.42203 |
June | 496.00000 | 27.00039 | 24.55562 | 0.19330 | 5.98637 |
July | 497.00000 | 27.00052 | 27.19224 | 0.26061 | 6.56027 |
August | 514.00000 | 27.08694 | 27.10120 | 0.29685 | 7.16772 |
September | 485.00000 | 27.00068 | 25.76614 | 0.15278 | 5.69354 |
October | 502.00000 | 27.00024 | 21.09445 | 0.73849 | 16.79156 |
November | 489.00000 | 27.00004 | 18.27167 | 0.63424 | 13.71636 |
December | 497.00000 | 27.00000 | 14.78651 | 0.55274 | 11.69570 |
Annual Sum or Average | 5943.00000 | 26.98265 | 20.74723 | 0.44851 | 10.67057 |
Minimum of Months | 454.00000 | 26.69216 | 14.78651 | 0.07906 | 5.42203 |
Maximum of Months | 514.00000 | 27.08694 | 27.19224 | 0.75712 | 17.31273 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00003 | 29.99810 | 1.04848 | 28.21368 |
February | 454.00000 | 27.01523 | 29.99850 | 1.21144 | 35.81510 |
March | 514.00000 | 27.00991 | 29.99796 | 1.36165 | 43.48166 |
April | 485.00000 | 28.96476 | 29.90681 | 1.91685 | 72.17543 |
May | 508.00000 | 27.00297 | 29.99980 | 0.49291 | 10.14341 |
June | 496.00000 | 27.00973 | 29.99761 | 0.72113 | 15.95409 |
July | 497.00000 | 27.00513 | 29.99789 | 0.93225 | 23.36713 |
August | 514.00000 | 32.05408 | 29.87690 | 2.63780 | 94.32896 |
September | 485.00000 | 27.00415 | 29.99798 | 0.54863 | 11.37586 |
October | 502.00000 | 27.01378 | 29.99706 | 1.26071 | 38.26971 |
November | 489.00000 | 27.00971 | 29.99981 | 1.38921 | 44.93941 |
December | 497.00000 | 27.77339 | 30.01374 | 1.67719 | 60.50780 |
Annual Sum or Average | 5943.00000 | 27.66796 | 29.98162 | 1.26956 | 39.99984 |
Minimum of Months | 454.00000 | 27.00003 | 29.87690 | 0.49291 | 10.14341 |
Maximum of Months | 514.00000 | 32.05408 | 30.01374 | 2.63780 | 94.32896 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.48222 | 14.49070 | 0.29247 | 7.21879 |
February | 454.00000 | 24.47148 | 15.59468 | 0.29927 | 7.28667 |
March | 514.00000 | 24.39812 | 15.44469 | 0.29040 | 7.05107 |
April | 485.00000 | 24.50752 | 13.80617 | 0.30799 | 7.44909 |
May | 508.00000 | 24.48494 | 21.28920 | -0.5001 | 11.27750 |
June | 496.00000 | 24.45476 | 31.95482 | -0.4238 | 9.61175 |
July | 497.00000 | 24.61482 | 45.73465 | -0.2716 | 7.75021 |
August | 514.00000 | 24.48862 | 45.32732 | -0.2932 | 7.79017 |
September | 485.00000 | 24.55973 | 37.53078 | -0.3413 | 8.75505 |
October | 502.00000 | 24.60277 | 22.74518 | 0.40374 | 9.18403 |
November | 489.00000 | 24.57722 | 16.02890 | 0.34570 | 8.09774 |
December | 497.00000 | 24.55589 | 12.37912 | 0.30753 | 7.52341 |
Annual Sum or Average | 5943.00000 | 24.51626 | 24.44772 | 0.03203 | 8.25794 |
Minimum of Months | 454.00000 | 24.39812 | 12.37912 | -0.5001 | 7.05107 |
Maximum of Months | 514.00000 | 24.61482 | 45.73465 | 0.40374 | 11.27750 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.19034 | 16.29905 | 0.23214 | 6.28602 |
February | 454.00000 | 24.27561 | 17.05902 | 0.26766 | 6.67378 |
March | 514.00000 | 24.27719 | 16.43190 | 0.28509 | 6.88107 |
April | 485.00000 | 24.28228 | 14.30786 | 0.29259 | 6.96131 |
May | 508.00000 | 24.26410 | 22.63025 | -0.5336 | 11.44575 |
June | 496.00000 | 24.21448 | 33.56923 | -0.4512 | 9.54372 |
July | 497.00000 | 24.24911 | 47.87908 | -0.3274 | 7.52978 |
August | 514.00000 | 24.21717 | 45.95728 | -0.3242 | 7.41559 |
September | 485.00000 | 24.33987 | 38.73274 | -0.3860 | 8.71992 |
October | 502.00000 | 24.36227 | 23.68631 | 0.36454 | 8.17429 |
November | 489.00000 | 24.34724 | 16.97104 | 0.30471 | 7.17785 |
December | 497.00000 | 24.37361 | 13.73358 | 0.27837 | 6.89525 |
Annual Sum or Average | 5943.00000 | 24.28239 | 25.69022 | -0.0025 | 7.81932 |
Minimum of Months | 454.00000 | 24.19034 | 13.73358 | -0.5336 | 6.28602 |
Maximum of Months | 514.00000 | 24.37361 | 47.87908 | 0.36454 | 11.44575 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.37036 | 18.07532 | 0.01017 | 5.51639 |
February | 454.00000 | 23.64197 | 18.79835 | 0.08764 | 5.54451 |
March | 514.00000 | 23.93481 | 17.65604 | 0.17076 | 5.81316 |
April | 485.00000 | 24.13864 | 15.09424 | 0.21662 | 6.12822 |
May | 508.00000 | 24.15943 | 23.01638 | -0.5968 | 12.86107 |
June | 496.00000 | 24.17198 | 33.62075 | -0.5012 | 10.53113 |
July | 497.00000 | 24.23456 | 47.60962 | -0.3769 | 8.24246 |
August | 514.00000 | 24.20628 | 46.67196 | -0.3912 | 8.43523 |
September | 485.00000 | 24.24707 | 39.14428 | -0.4453 | 9.55572 |
October | 502.00000 | 24.11446 | 24.51684 | 0.27880 | 6.99803 |
November | 489.00000 | 23.87339 | 18.71791 | 0.15665 | 5.77225 |
December | 497.00000 | 23.46017 | 16.17281 | 0.02099 | 5.44708 |
Annual Sum or Average | 5943.00000 | 23.96485 | 26.67123 | -0.1163 | 7.59095 |
Minimum of Months | 454.00000 | 23.37036 | 15.09424 | -0.5968 | 5.44708 |
Maximum of Months | 514.00000 | 24.24707 | 47.60962 | 0.27880 | 12.86107 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.74010 | 19.79042 | -0.4004 | 10.57215 |
February | 454.00000 | 22.29838 | 20.64893 | -0.2502 | 8.15750 |
March | 514.00000 | 23.19073 | 18.99471 | -0.0230 | 6.10806 |
April | 485.00000 | 23.85184 | 15.41151 | 0.14182 | 5.88757 |
May | 508.00000 | 24.05358 | 22.85045 | -0.6316 | 14.07875 |
June | 496.00000 | 24.17423 | 33.60437 | -0.4822 | 10.21305 |
July | 497.00000 | 24.28692 | 47.54942 | -0.3340 | 7.72944 |
August | 514.00000 | 24.24679 | 46.53870 | -0.3587 | 8.00754 |
September | 485.00000 | 24.20380 | 38.88172 | -0.4575 | 9.79103 |
October | 502.00000 | 23.67494 | 25.28631 | 0.16047 | 6.61793 |
November | 489.00000 | 22.70058 | 20.75745 | -0.1426 | 7.07964 |
December | 497.00000 | 21.77023 | 18.00567 | -0.4039 | 10.36941 |
Annual Sum or Average | 5943.00000 | 23.35728 | 27.43170 | -0.2658 | 8.72745 |
Minimum of Months | 454.00000 | 21.74010 | 15.41151 | -0.6316 | 5.88757 |
Maximum of Months | 514.00000 | 24.28692 | 47.54942 | 0.16047 | 14.07875 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.25477 | 17.66025 | -0.2558 | 7.16935 |
February | 454.00000 | 22.74807 | 18.31270 | -0.1297 | 6.30798 |
March | 514.00000 | 23.50055 | 16.98947 | 0.05801 | 5.61866 |
April | 485.00000 | 24.00167 | 14.13088 | 0.19489 | 6.05540 |
May | 508.00000 | 24.15847 | 22.25216 | -0.5818 | 12.90706 |
June | 496.00000 | 24.30189 | 32.59058 | -0.3906 | 8.78397 |
July | 497.00000 | 24.43346 | 46.52001 | -0.2276 | 6.97975 |
August | 514.00000 | 24.30877 | 45.01186 | -0.2740 | 7.21197 |
September | 485.00000 | 24.28771 | 38.08582 | -0.4192 | 9.40800 |
October | 502.00000 | 23.81482 | 23.92316 | 0.19639 | 6.67687 |
November | 489.00000 | 23.25757 | 17.90165 | -0.0036 | 5.57389 |
December | 497.00000 | 22.61852 | 15.13303 | -0.1831 | 6.37134 |
Annual Sum or Average | 5943.00000 | 23.64680 | 25.78615 | -0.1689 | 7.43464 |
Minimum of Months | 454.00000 | 22.25477 | 14.13088 | -0.5818 | 5.57389 |
Maximum of Months | 514.00000 | 24.43346 | 46.52001 | 0.19639 | 12.90706 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.49654 | 16.60255 | -0.1742 | 7.09994 |
February | 454.00000 | 22.89633 | 17.38208 | -0.0609 | 6.57246 |
March | 514.00000 | 23.53446 | 16.37600 | 0.11804 | 6.44487 |
April | 485.00000 | 24.04953 | 13.66710 | 0.28152 | 7.61086 |
May | 508.00000 | 24.28576 | 21.64918 | -0.4340 | 11.28256 |
June | 496.00000 | 24.32717 | 32.35764 | -0.2791 | 8.12964 |
July | 497.00000 | 24.47409 | 46.24812 | -0.1203 | 7.45005 |
August | 514.00000 | 24.26777 | 44.94407 | -0.2058 | 7.42579 |
September | 485.00000 | 24.33293 | 37.67980 | -0.3068 | 8.51709 |
October | 502.00000 | 23.92580 | 23.25390 | 0.27863 | 8.32625 |
November | 489.00000 | 23.25233 | 17.20376 | 0.03380 | 6.18107 |
December | 497.00000 | 22.51138 | 14.38961 | -0.1811 | 6.95029 |
Annual Sum or Average | 5943.00000 | 23.70190 | 25.22597 | -0.0883 | 7.67672 |
Minimum of Months | 454.00000 | 22.49654 | 13.66710 | -0.4340 | 6.18107 |
Maximum of Months | 514.00000 | 24.47409 | 46.24812 | 0.28152 | 11.28256 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.33401 | 15.61979 | 0.06031 | 8.20187 |
February | 454.00000 | 23.58242 | 16.32955 | 0.14111 | 7.71167 |
March | 514.00000 | 23.81139 | 15.98913 | 0.19310 | 7.00086 |
April | 485.00000 | 24.10486 | 13.69352 | 0.26835 | 7.20768 |
May | 508.00000 | 24.16330 | 22.10369 | -0.5559 | 12.88727 |
June | 496.00000 | 24.25688 | 32.64886 | -0.4061 | 9.22141 |
July | 497.00000 | 24.43455 | 46.46905 | -0.2079 | 7.08133 |
August | 514.00000 | 24.35182 | 44.73818 | -0.2008 | 6.91866 |
September | 485.00000 | 24.46566 | 37.27546 | -0.2469 | 8.08500 |
October | 502.00000 | 24.31074 | 22.55390 | 0.41465 | 10.51915 |
November | 489.00000 | 24.00786 | 16.04703 | 0.26413 | 8.25473 |
December | 497.00000 | 23.55698 | 13.22180 | 0.12275 | 7.87768 |
Annual Sum or Average | 5943.00000 | 24.03410 | 24.81011 | -0.0148 | 8.42376 |
Minimum of Months | 454.00000 | 23.33401 | 13.22180 | -0.5559 | 6.91866 |
Maximum of Months | 514.00000 | 24.46566 | 46.46905 | 0.41465 | 12.88727 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.91452 | 15.82276 | -0.0474 | 6.31145 |
February | 454.00000 | 23.66620 | 16.21560 | 0.16094 | 6.68314 |
March | 514.00000 | 24.22573 | 15.38474 | 0.33127 | 8.02955 |
April | 485.00000 | 24.54212 | 13.10390 | 0.47921 | 10.73521 |
May | 508.00000 | 24.35129 | 21.61125 | -0.3822 | 9.75356 |
June | 496.00000 | 24.45835 | 32.07288 | -0.1804 | 7.30788 |
July | 497.00000 | 24.59063 | 45.88850 | 0.00398 | 6.84390 |
August | 514.00000 | 24.55104 | 44.07451 | 0.06091 | 6.88383 |
September | 485.00000 | 24.49873 | 37.21421 | -0.2050 | 7.60006 |
October | 502.00000 | 24.32595 | 22.56027 | 0.42100 | 9.93624 |
November | 489.00000 | 24.18038 | 15.81537 | 0.30126 | 7.54553 |
December | 497.00000 | 24.13027 | 12.65380 | 0.24993 | 7.00785 |
Annual Sum or Average | 5943.00000 | 24.20588 | 24.45102 | 0.09844 | 7.89200 |
Minimum of Months | 454.00000 | 22.91452 | 12.65380 | -0.3822 | 6.31145 |
Maximum of Months | 514.00000 | 24.59063 | 45.88850 | 0.47921 | 10.73521 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.74147 | 18.93098 | -0.6472 | 14.96515 |
February | 454.00000 | 21.16691 | 20.06222 | -0.5234 | 11.99332 |
March | 514.00000 | 22.24152 | 18.85486 | -0.2509 | 7.64695 |
April | 485.00000 | 23.33542 | 15.32860 | 0.01187 | 6.01132 |
May | 508.00000 | 23.89106 | 22.82468 | -0.6938 | 16.35641 |
June | 496.00000 | 24.24166 | 32.50010 | -0.4421 | 9.75504 |
July | 497.00000 | 24.43254 | 46.17890 | -0.2656 | 7.27544 |
August | 514.00000 | 24.27010 | 45.48128 | -0.3447 | 7.95846 |
September | 485.00000 | 24.10077 | 38.60842 | -0.5074 | 11.10796 |
October | 502.00000 | 22.96094 | 25.31976 | -0.0178 | 6.99323 |
November | 489.00000 | 21.58065 | 19.80091 | -0.4091 | 9.93657 |
December | 497.00000 | 20.66880 | 17.09356 | -0.6770 | 15.60060 |
Annual Sum or Average | 5943.00000 | 22.81520 | 26.82053 | -0.3968 | 10.46072 |
Minimum of Months | 454.00000 | 20.66880 | 15.32860 | -0.6938 | 6.01132 |
Maximum of Months | 514.00000 | 24.43254 | 46.17890 | 0.01187 | 16.35641 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 21.22183 | 17.16011 | -0.5112 | 11.88011 |
February | 385.00000 | 21.69378 | 18.15491 | -0.3691 | 9.86377 |
March | 433.00000 | 22.77925 | 16.93289 | -0.0792 | 7.06203 |
April | 410.00000 | 23.90682 | 13.70992 | 0.22209 | 7.63799 |
May | 430.00000 | 24.21169 | 21.74849 | -0.4792 | 13.23352 |
June | 418.00000 | 24.41454 | 31.46793 | -0.2766 | 8.78684 |
July | 422.00000 | 24.68861 | 44.72448 | -0.0798 | 8.05387 |
August | 433.00000 | 24.47055 | 44.13656 | -0.1759 | 7.74343 |
September | 410.00000 | 24.28199 | 37.32221 | -0.3535 | 9.70771 |
October | 427.00000 | 23.48150 | 23.33502 | 0.15267 | 8.14266 |
November | 417.00000 | 22.12910 | 18.01844 | -0.2472 | 7.97907 |
December | 422.00000 | 21.08441 | 15.49468 | -0.5516 | 12.71723 |
Annual Sum or Average | 5034.00000 | 23.20567 | 25.24413 | -0.2286 | 9.40122 |
Minimum of Months | 385.00000 | 21.08441 | 13.70992 | -0.5516 | 7.06203 |
Maximum of Months | 433.00000 | 24.68861 | 44.72448 | 0.22209 | 13.23352 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.97548 | 16.00973 | -0.0299 | 9.56974 |
February | 454.00000 | 23.20261 | 16.97942 | 0.04879 | 8.65231 |
March | 514.00000 | 23.39216 | 16.72528 | 0.08769 | 7.24576 |
April | 485.00000 | 23.81800 | 14.18481 | 0.18047 | 6.91064 |
May | 508.00000 | 23.99601 | 22.45408 | -0.6270 | 15.00711 |
June | 496.00000 | 24.19911 | 32.53622 | -0.4538 | 10.25589 |
July | 497.00000 | 24.45519 | 46.05656 | -0.2368 | 7.33959 |
August | 514.00000 | 24.36715 | 45.00196 | -0.2437 | 7.34776 |
September | 485.00000 | 24.42336 | 37.29477 | -0.2704 | 8.63512 |
October | 502.00000 | 24.17346 | 22.79605 | 0.37831 | 10.68578 |
November | 489.00000 | 23.65683 | 16.62027 | 0.17875 | 8.72468 |
December | 497.00000 | 23.03170 | 14.21829 | -0.0111 | 9.23528 |
Annual Sum or Average | 5943.00000 | 23.81121 | 25.15785 | -0.0852 | 9.14552 |
Minimum of Months | 454.00000 | 22.97548 | 14.18481 | -0.6270 | 6.91064 |
Maximum of Months | 514.00000 | 24.45519 | 46.05656 | 0.37831 | 15.00711 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.40871 | 17.39703 | -0.4472 | 11.14859 |
February | 454.00000 | 21.93367 | 18.35428 | -0.2916 | 9.16015 |
March | 514.00000 | 22.71369 | 17.41892 | -0.0819 | 7.12324 |
April | 485.00000 | 23.71410 | 14.27529 | 0.18072 | 7.32542 |
May | 508.00000 | 23.98570 | 22.33768 | -0.5562 | 14.03467 |
June | 496.00000 | 24.28280 | 32.28787 | -0.3233 | 9.17395 |
July | 497.00000 | 24.47232 | 45.95922 | -0.1471 | 7.03218 |
August | 514.00000 | 24.36459 | 45.00504 | -0.1938 | 7.08193 |
September | 485.00000 | 24.23917 | 37.86321 | -0.3487 | 9.43865 |
October | 502.00000 | 23.36320 | 23.98047 | 0.14690 | 8.03298 |
November | 489.00000 | 22.23712 | 18.16979 | -0.2048 | 7.79821 |
December | 497.00000 | 21.42153 | 15.54354 | -0.4531 | 11.17929 |
Annual Sum or Average | 5943.00000 | 23.18714 | 25.79365 | -0.2268 | 9.04664 |
Minimum of Months | 454.00000 | 21.40871 | 14.27529 | -0.5562 | 7.03218 |
Maximum of Months | 514.00000 | 24.47232 | 45.95922 | 0.18072 | 14.03467 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.13334 | 19.72712 | -0.8493 | 22.61179 |
February | 454.00000 | 20.52272 | 20.87286 | -0.7215 | 18.04551 |
March | 514.00000 | 21.54318 | 19.60636 | -0.4380 | 11.09648 |
April | 485.00000 | 22.90581 | 15.60739 | -0.0950 | 7.13499 |
May | 508.00000 | 23.68355 | 22.89118 | -0.7623 | 19.47105 |
June | 496.00000 | 24.20193 | 32.70855 | -0.4388 | 10.18738 |
July | 497.00000 | 24.44609 | 46.34452 | -0.2372 | 7.25523 |
August | 514.00000 | 24.27416 | 45.54956 | -0.3269 | 8.00848 |
September | 485.00000 | 23.97670 | 38.59625 | -0.5471 | 12.53271 |
October | 502.00000 | 22.44907 | 25.90023 | -0.1532 | 8.67189 |
November | 489.00000 | 20.76449 | 20.87363 | -0.6372 | 16.04740 |
December | 497.00000 | 20.08019 | 17.84493 | -0.8794 | 23.58381 |
Annual Sum or Average | 5943.00000 | 22.42985 | 27.27943 | -0.5059 | 13.69246 |
Minimum of Months | 454.00000 | 20.08019 | 15.60739 | -0.8794 | 7.13499 |
Maximum of Months | 514.00000 | 24.44609 | 46.34452 | -0.0950 | 23.58381 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.57796 | 18.55091 | -0.7040 | 17.53965 |
February | 454.00000 | 21.11196 | 19.53520 | -0.5358 | 13.78626 |
March | 514.00000 | 22.42271 | 17.88385 | -0.1803 | 8.30044 |
April | 485.00000 | 23.72647 | 13.93954 | 0.18526 | 7.58368 |
May | 508.00000 | 24.09825 | 21.63861 | -0.4983 | 13.82257 |
June | 496.00000 | 24.33637 | 32.18181 | -0.2573 | 8.59889 |
July | 497.00000 | 24.58579 | 45.74437 | -0.0567 | 7.73001 |
August | 514.00000 | 24.39355 | 44.91600 | -0.1504 | 7.48347 |
September | 485.00000 | 24.16561 | 37.62091 | -0.3615 | 9.91369 |
October | 502.00000 | 23.21838 | 24.13645 | 0.08545 | 8.41054 |
November | 489.00000 | 21.47058 | 19.39477 | -0.4289 | 11.24129 |
December | 497.00000 | 20.40153 | 16.83767 | -0.7548 | 19.20235 |
Annual Sum or Average | 5943.00000 | 22.88951 | 26.10229 | -0.3034 | 11.11466 |
Minimum of Months | 454.00000 | 20.40153 | 13.93954 | -0.7548 | 7.48347 |
Maximum of Months | 514.00000 | 24.58579 | 45.74437 | 0.18526 | 19.20235 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.19794 | 16.99528 | -0.2604 | 12.55423 |
February | 454.00000 | 22.48904 | 17.95176 | -0.1569 | 10.89181 |
March | 514.00000 | 22.84189 | 17.47988 | -0.0661 | 8.53539 |
April | 485.00000 | 23.46157 | 14.43604 | 0.09090 | 7.41443 |
May | 508.00000 | 23.77113 | 22.53645 | -0.6986 | 18.14961 |
June | 496.00000 | 24.12343 | 32.81449 | -0.4604 | 11.03878 |
July | 497.00000 | 24.44314 | 46.30838 | -0.2152 | 7.39816 |
August | 514.00000 | 24.34958 | 45.15120 | -0.2299 | 7.50037 |
September | 485.00000 | 24.30442 | 37.27625 | -0.3045 | 9.60069 |
October | 502.00000 | 23.79685 | 23.24639 | 0.27462 | 10.46837 |
November | 489.00000 | 22.97016 | 17.66744 | -0.0174 | 9.51072 |
December | 497.00000 | 22.22239 | 15.21113 | -0.2490 | 12.83532 |
Annual Sum or Average | 5943.00000 | 23.42057 | 25.67110 | -0.1922 | 10.49957 |
Minimum of Months | 454.00000 | 22.19794 | 14.43604 | -0.6986 | 7.39816 |
Maximum of Months | 514.00000 | 24.44314 | 46.30838 | 0.27462 | 18.14961 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.81381 | 18.18832 | -0.6346 | 16.77742 |
February | 454.00000 | 21.37127 | 19.07716 | -0.4609 | 12.91146 |
March | 514.00000 | 22.16257 | 18.05058 | -0.2321 | 9.04384 |
April | 485.00000 | 23.35025 | 14.46472 | 0.09125 | 7.79328 |
May | 508.00000 | 23.76003 | 22.39430 | -0.6262 | 16.99018 |
June | 496.00000 | 24.20701 | 32.57043 | -0.3284 | 9.97116 |
July | 497.00000 | 24.45233 | 46.24865 | -0.1284 | 7.25651 |
August | 514.00000 | 24.34186 | 45.17044 | -0.1822 | 7.31668 |
September | 485.00000 | 24.09639 | 37.90368 | -0.3892 | 10.71445 |
October | 502.00000 | 22.97410 | 24.41961 | 0.04212 | 8.73160 |
November | 489.00000 | 21.54641 | 19.12353 | -0.3963 | 11.29141 |
December | 497.00000 | 20.83141 | 16.29228 | -0.6410 | 16.79685 |
Annual Sum or Average | 5943.00000 | 22.83661 | 26.23422 | -0.3233 | 11.29154 |
Minimum of Months | 454.00000 | 20.81381 | 14.46472 | -0.6410 | 7.25651 |
Maximum of Months | 514.00000 | 24.45233 | 46.24865 | 0.09125 | 16.99018 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.256742E+10 | 43096.50 | 05-JAN-15:00 | 70.59 | 0.118686E+11 | 0.00 | 0.144360E+11 | 0.43 | 5.41 | 05-JAN-15:00 | 0.00 | 0.00 |
February | 0.540749E+10 | 75956.60 | 13-FEB-15:10 | 100.38 | 0.319579E+11 | 0.00 | 0.373654E+11 | 0.73 | 7.33 | 13-FEB-15:00 | 0.00 | 0.00 |
March | 0.163477E+11 | 80632.94 | 08-MAR-16:40 | 154.87 | 0.903925E+11 | 0.00 | 0.106740E+12 | 1.05 | 7.38 | 08-MAR-16:40 | 0.00 | 0.00 |
April | 0.441745E+11 | 85959.26 | 28-APR-13:30 | 301.91 | 0.282206E+12 | 0.00 | 0.326380E+12 | 2.38 | 7.42 | 28-APR-10:30 | 0.00 | 0.00 |
May | 0.717374E+11 | 93579.23 | 23-MAY-12:10 | 374.55 | 0.470283E+12 | 0.00 | 0.542020E+12 | 3.07 | 7.42 | 30-MAY-08:50 | 0.00 | 0.00 |
June | 0.114729E+12 | 112180.00 | 29-JUN-05:02 | 543.20 | 0.778200E+12 | 0.00 | 0.892929E+12 | 4.72 | 7.64 | 29-JUN-05:02 | 0.00 | 0.00 |
July | 0.138442E+12 | 114149.43 | 31-JUL-15:00 | 655.40 | 0.939645E+12 | 0.00 | 0.107809E+13 | 5.47 | 7.76 | 01-JUL-05:02 | 0.00 | 0.00 |
August | 0.133529E+12 | 128261.37 | 14-AUG-05:03 | 679.32 | 0.909303E+12 | 0.00 | 0.104283E+13 | 5.58 | 7.81 | 14-AUG-05:03 | 0.00 | 0.00 |
September | 0.932699E+11 | 122768.73 | 05-SEP-13:10 | 462.14 | 0.624283E+12 | 0.00 | 0.717553E+12 | 3.97 | 7.57 | 05-SEP-12:10 | 0.00 | 0.00 |
October | 0.489648E+11 | 97968.47 | 02-OCT-11:50 | 301.81 | 0.315117E+12 | 0.00 | 0.364081E+12 | 2.35 | 7.51 | 02-OCT-11:00 | 0.00 | 0.00 |
November | 0.508388E+10 | 56883.27 | 02-NOV-15:00 | 90.65 | 0.246863E+11 | 0.00 | 0.297702E+11 | 0.59 | 6.78 | 02-NOV-15:00 | 0.00 | 0.00 |
December | 0.829437E+09 | 5394.38 | 01-DEC-06:05 | 89.21 | 0.377817E+10 | 0.00 | 0.460761E+10 | 0.55 | 4.56 | 20-DEC-11:30 | 0.00 | 0.00 |
Annual Sum or Average | 0.675083E+12 | 3824.03 | 0.448172E+13 | 0.00 | 0.515680E+13 | 2.58 | 0.00 | 0.00 | ||||
Minimum of Months | 0.829437E+09 | 5394.38 | 70.59 | 0.377817E+10 | 0.00 | 0.460761E+10 | 0.43 | 4.56 | 0.00 | 0.00 | ||
Maximum of Months | 0.138442E+12 | 128261.37 | 679.32 | 0.939645E+12 | 0.00 | 0.107809E+13 | 5.58 | 7.81 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.666671E+10 | 85959.26 | 28-APR-13:30 | 23.33 | 0.481837E+11 | 0.00 | 0.548504E+11 | 0.23 | 7.32 | 28-APR-14:00 | 0.00 | 0.00 |
May | 0.146503E+11 | 93579.23 | 23-MAY-12:10 | 50.00 | 0.105726E+12 | 0.00 | 0.120377E+12 | 0.48 | 7.41 | 23-MAY-12:20 | 0.00 | 0.00 |
June | 0.503569E+11 | 112180.00 | 29-JUN-05:02 | 160.33 | 0.367036E+12 | 0.00 | 0.417393E+12 | 1.62 | 7.64 | 29-JUN-05:02 | 0.00 | 0.00 |
July | 0.671998E+11 | 114149.43 | 31-JUL-15:00 | 208.69 | 0.489396E+12 | 0.00 | 0.556595E+12 | 2.04 | 7.76 | 01-JUL-05:02 | 0.00 | 0.00 |
August | 0.651472E+11 | 128261.37 | 14-AUG-05:03 | 205.09 | 0.475183E+12 | 0.00 | 0.540331E+12 | 2.01 | 7.81 | 14-AUG-05:03 | 0.00 | 0.00 |
September | 0.349417E+11 | 122768.73 | 05-SEP-13:10 | 114.75 | 0.253918E+12 | 0.00 | 0.288859E+12 | 1.16 | 7.57 | 05-SEP-12:10 | 0.00 | 0.00 |
October | 0.106715E+11 | 97968.47 | 02-OCT-11:50 | 36.25 | 0.774131E+11 | 0.00 | 0.880846E+11 | 0.35 | 7.51 | 02-OCT-11:00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.249634E+12 | 798.45 | 0.181686E+13 | 0.00 | 0.206649E+13 | 0.66 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.671998E+11 | 128261.37 | 208.69 | 0.489396E+12 | 0.00 | 0.556595E+12 | 2.04 | 7.81 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: CENTRAL TOWER
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.177786E+11 | 744.00 | 49248.27 | 05-JAN-14:00 | 226902.82 | 05-JAN-16:00 | 22.13 | 18.33 | 15.52 |
February | 0.354414E+11 | 672.00 | 49248.27 | 10-FEB-15:30 | 411258.08 | 13-FEB-17:05 | 25.26 | 18.49 | 15.52 |
March | 0.852423E+11 | 744.00 | 49248.27 | 01-MAR-13:10 | 681005.20 | 31-MAR-24:00 | 29.03 | 19.26 | 15.52 |
April | 0.116742E+12 | 720.00 | 49248.27 | 01-APR-08:00 | 736503.28 | 29-APR-18:11 | 35.32 | 22.52 | 15.52 |
May | 0.102539E+12 | 744.00 | 49248.27 | 02-MAY-10:40 | 386748.66 | 31-MAY-24:00 | 26.02 | 21.79 | 15.52 |
June | 0.125013E+12 | 720.00 | 49248.27 | 01-JUN-00:10 | 552753.68 | 30-JUN-23:23 | 34.89 | 27.57 | 15.52 |
July | 0.131907E+12 | 744.00 | 49248.27 | 01-JUL-00:10 | 699258.88 | 31-JUL-24:00 | 41.91 | 31.60 | 15.52 |
August | 0.131907E+12 | 744.00 | 49248.27 | 01-AUG-00:03 | 776209.42 | 20-AUG-18:11 | 45.02 | 31.79 | 15.52 |
September | 0.120104E+12 | 720.00 | 49248.27 | 01-SEP-00:05 | 384894.76 | 30-SEP-24:00 | 27.62 | 23.27 | 15.52 |
October | 0.961243E+11 | 744.00 | 49248.27 | 01-OCT-00:10 | 535914.94 | 31-OCT-23:50 | 27.87 | 20.79 | 15.52 |
November | 0.726336E+11 | 720.00 | 49248.27 | 01-NOV-00:10 | 557146.60 | 02-NOV-16:00 | 28.31 | 18.56 | 15.52 |
December | 0.647445E+11 | 744.00 | 49248.27 | 01-DEC-12:40 | 705116.06 | 24-DEC-16:12 | 30.84 | 18.35 | 15.52 |
Annual Sum or Average | 0.110018E+13 | 8760.00 | 31.23 | 22.73 | 15.52 | ||||
Minimum of Months | 0.177786E+11 | 672.00 | 49248.27 | 226902.82 | 22.13 | 18.33 | 15.52 | ||
Maximum of Months | 0.131907E+12 | 744.00 | 49248.27 | 776209.42 | 45.02 | 31.79 | 15.52 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 290712.95 | 05-JAN-15:00 | 21.03 | 21.00 | 1.84 |
February | 9806206.96 | 16.25 | 466.55 | 14-FEB-17:00 | 827606.99 | 14-FEB-16:30 | 21.04 | 20.96 | 2.97 |
March | 35202866.79 | 76.10 | 687.73 | 08-MAR-16:00 | 843601.34 | 08-MAR-16:00 | 21.14 | 20.94 | 8.32 |
April | 0.163689E+09 | 185.45 | 966.59 | 14-APR-16:10 | 1009990.58 | 14-APR-13:30 | 21.63 | 20.99 | 17.69 |
May | 0.498747E+09 | 316.05 | 2529.86 | 23-MAY-10:30 | 1106034.66 | 19-MAY-15:20 | 22.31 | 21.26 | 25.68 |
June | 0.328837E+10 | 461.35 | 15977.69 | 06-JUN-13:00 | 1129197.73 | 15-JUN-13:10 | 23.05 | 21.17 | 38.62 |
July | 0.139146E+11 | 561.38 | 15977.69 | 01-JUL-05:04 | 1084001.01 | 21-JUL-16:50 | 23.30 | 21.27 | 46.54 |
August | 0.106140E+11 | 527.06 | 15977.69 | 01-AUG-09:30 | 1091215.64 | 31-AUG-14:10 | 23.22 | 21.18 | 46.29 |
September | 0.257265E+10 | 398.13 | 15977.69 | 01-SEP-10:30 | 1126370.30 | 21-SEP-16:00 | 22.85 | 21.35 | 33.17 |
October | 0.539053E+09 | 217.05 | 15977.69 | 11-OCT-10:30 | 1066557.85 | 03-OCT-12:10 | 21.89 | 21.15 | 18.87 |
November | 4947095.87 | 19.92 | 219.34 | 02-NOV-15:10 | 454043.06 | 02-NOV-15:10 | 21.07 | 21.01 | 3.67 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 215339.18 | 22-DEC-16:20 | 20.98 | 20.97 | 0.81 |
Annual Sum or Average | 0.316411E+11 | 2778.73 | 21.96 | 21.11 | 20.48 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 215339.18 | 20.98 | 20.94 | 0.81 | ||
Maximum of Months | 0.139146E+11 | 561.38 | 15977.69 | 1129197.73 | 23.30 | 21.35 | 46.54 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 21.03 | 21.03 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 21.04 | 21.04 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 21.14 | 21.14 | 0.00 |
April | 16851267.79 | 10.33 | 622.66 | 28-APR-14:10 | 999448.88 | 26-APR-12:50 | 21.63 | 21.57 | 0.78 |
May | 77446262.97 | 26.00 | 2529.86 | 23-MAY-10:30 | 1106034.66 | 19-MAY-15:20 | 22.31 | 22.16 | 1.89 |
June | 0.193123E+10 | 134.57 | 15977.69 | 06-JUN-13:00 | 1129197.73 | 15-JUN-13:10 | 23.05 | 22.25 | 10.13 |
July | 0.842310E+10 | 171.73 | 15977.69 | 01-JUL-05:04 | 1084001.01 | 21-JUL-16:50 | 23.30 | 22.43 | 12.51 |
August | 0.699141E+10 | 167.18 | 15977.69 | 01-AUG-09:30 | 1091215.64 | 31-AUG-14:10 | 23.22 | 22.34 | 12.18 |
September | 0.129938E+10 | 87.83 | 15977.69 | 01-SEP-10:30 | 1126370.30 | 21-SEP-16:00 | 22.85 | 22.32 | 6.61 |
October | 0.223102E+09 | 31.67 | 15977.69 | 11-OCT-10:40 | 1066557.85 | 03-OCT-12:10 | 21.89 | 21.70 | 2.31 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 21.07 | 21.07 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 20.98 | 20.98 | 0.00 |
Annual Sum or Average | 0.189625E+11 | 629.31 | 21.96 | 21.67 | 3.89 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 20.98 | 20.98 | 0.00 | ||
Maximum of Months | 0.842310E+10 | 171.73 | 15977.69 | 1129197.73 | 23.30 | 22.43 | 12.51 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.175572E+12 | 0.00 | 415.39 | 1093392.98 | 10-JAN-06:01 | 0.00 | 28.23 | 56.93 | 0.33 | 0.00 | 0.03 | 0.51 | 10-JAN-06:01 |
February | 0.101407E+12 | 0.00 | 303.47 | 1098001.93 | 27-FEB-06:01 | 0.00 | 26.98 | 50.48 | 0.20 | 0.00 | 0.02 | 0.51 | 27-FEB-06:01 |
March | 0.250672E+11 | 0.00 | 179.07 | 1108390.62 | 06-MAR-06:01 | 0.00 | 25.82 | 38.77 | 0.04 | 0.00 | 0.00 | 0.51 | 06-MAR-06:01 |
April | 0.320452E+10 | 0.00 | 44.46 | 409213.80 | 08-APR-05:03 | 0.00 | 24.82 | 28.19 | 0.01 | 0.00 | 0.00 | 0.19 | 08-APR-05:03 |
May | 0.332739E+09 | 0.00 | 11.30 | 94295.97 | 05-MAY-05:02 | 0.00 | 24.00 | 24.84 | 0.00 | 0.00 | 0.00 | 0.04 | 05-MAY-05:02 |
June | 4819791.27 | 0.00 | 1.96 | 1283.05 | 09-JUN-05:20 | 0.00 | 23.77 | 23.92 | 0.00 | 0.00 | 0.00 | 0.00 | 09-JUN-05:20 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 23.74 | 23.74 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 23.74 | 23.74 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 23.74 | 23.74 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 0.133135E+11 | 0.00 | 90.67 | 1052037.29 | 26-OCT-05:02 | 0.00 | 24.45 | 31.05 | 0.02 | 0.00 | 0.00 | 0.49 | 26-OCT-05:02 |
November | 0.397042E+11 | 0.00 | 239.48 | 1052445.09 | 28-NOV-06:01 | 0.00 | 25.55 | 43.31 | 0.07 | 0.00 | 0.01 | 0.49 | 28-NOV-06:01 |
December | 0.167912E+12 | 0.00 | 433.44 | 1141531.72 | 04-DEC-05:01 | 0.00 | 27.64 | 58.01 | 0.31 | 0.00 | 0.03 | 0.53 | 04-DEC-05:01 |
Annual Sum or Average | 0.526519E+12 | 0.00 | 1719.24 | 0.00 | 25.20 | 35.50 | 0.08 | 0.00 | 0.01 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.74 | 23.74 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.175572E+12 | 0.00 | 433.44 | 1141531.72 | 0.00 | 28.23 | 58.01 | 0.33 | 0.00 | 0.03 | 0.53 |
Report: BoilerReportMonthly
For: CENTRAL BOILER
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 22.13 | 22.13 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 25.26 | 25.26 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 29.03 | 29.03 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 35.32 | 35.32 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 26.02 | 26.02 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 34.89 | 34.89 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 41.91 | 41.91 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 45.02 | 45.02 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 27.62 | 27.62 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 27.87 | 27.87 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 28.31 | 28.31 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 30.84 | 30.84 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 31.23 | 31.23 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.13 | 22.13 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.02 | 45.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.888480E+09 | 0.00 | 24.99 | 0.888480E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21959.34 | 05-JAN-14:10 | 21959.34 | 05-JAN-14:10 | 0.00 | 0.00 | 0.00 |
February | 0.303259E+10 | 0.00 | 36.00 | 0.303259E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69498.26 | 14-FEB-16:00 | 69498.26 | 14-FEB-16:00 | 0.00 | 0.00 | 0.00 |
March | 0.962673E+10 | 0.00 | 127.08 | 0.962673E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75933.74 | 08-MAR-16:00 | 75933.74 | 08-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.372508E+11 | 0.00 | 285.11 | 0.372508E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 111205.87 | 28-APR-14:50 | 111205.87 | 28-APR-14:50 | 0.00 | 0.00 | 0.00 |
May | 0.551812E+11 | 0.00 | 353.89 | 0.551812E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 112035.50 | 30-MAY-14:30 | 112035.50 | 30-MAY-14:30 | 0.00 | 0.00 | 0.00 |
June | 0.108359E+12 | 0.00 | 519.67 | 0.108356E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 153547.36 | 29-JUN-05:02 | 141574.91 | 29-JUN-05:02 | 0.00 | 0.00 | 0.00 |
July | 0.139648E+12 | 0.00 | 616.07 | 0.135936E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 152451.87 | 01-JUL-05:02 | 137097.93 | 05-JUL-14:50 | 0.00 | 0.00 | 0.00 |
August | 0.149756E+12 | 0.00 | 656.37 | 0.145025E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 162084.80 | 23-AUG-16:00 | 147678.17 | 07-AUG-15:10 | 0.00 | 0.00 | 0.00 |
September | 0.796856E+11 | 0.00 | 439.43 | 0.786256E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 159002.77 | 05-SEP-13:10 | 114148.06 | 01-SEP-15:50 | 0.00 | 0.00 | 0.00 |
October | 0.380108E+11 | 0.00 | 268.15 | 0.379890E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 111108.18 | 10-OCT-16:00 | 111108.18 | 10-OCT-16:00 | 0.00 | 0.00 | 0.00 |
November | 0.236245E+10 | 0.00 | 57.92 | 0.236245E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36778.65 | 02-NOV-15:00 | 36778.65 | 02-NOV-15:00 | 0.00 | 0.00 | 0.00 |
December | 334315.88 | 0.00 | 0.93 | 334315.88 | 0.00 | 0.00 | 0.00 | 0.00 | 2778.26 | 24-DEC-14:22 | 2778.26 | 24-DEC-14:22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.623803E+12 | 0.00 | 3385.59 | 0.614275E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 334315.88 | 0.00 | 0.93 | 334315.88 | 0.00 | 0.00 | 0.00 | 0.00 | 2778.26 | 2778.26 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.149756E+12 | 0.00 | 656.37 | 0.145025E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 162084.80 | 147678.17 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.757867E+10 | 0.00 | 68.91 | 0.757867E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 191057.64 | 05-JAN-15:20 | 191057.64 | 05-JAN-15:20 | 0.00 | 0.00 | 0.00 |
February | 0.242953E+11 | 0.00 | 97.95 | 0.242953E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 560842.86 | 14-FEB-16:00 | 560842.86 | 14-FEB-16:00 | 0.00 | 0.00 | 0.00 |
March | 0.692741E+11 | 0.00 | 145.15 | 0.692741E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 581327.61 | 08-MAR-16:00 | 581327.61 | 08-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.261490E+12 | 0.00 | 244.54 | 0.261490E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 902042.46 | 13-APR-15:20 | 902042.46 | 13-APR-15:20 | 0.00 | 0.00 | 0.00 |
May | 0.476331E+12 | 0.00 | 345.78 | 0.476331E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1019118.74 | 19-MAY-15:20 | 1019118.74 | 19-MAY-15:20 | 0.00 | 0.00 | 0.00 |
June | 0.926766E+12 | 0.00 | 460.93 | 0.926723E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1435347.13 | 29-JUN-05:02 | 1318385.25 | 29-JUN-05:02 | 0.00 | 0.00 | 0.00 |
July | 0.112765E+13 | 0.00 | 499.97 | 0.110337E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 1393813.00 | 01-JUL-05:02 | 1244594.05 | 21-JUL-14:50 | 0.00 | 0.00 | 0.00 |
August | 0.106652E+13 | 0.00 | 504.63 | 0.104455E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 1420620.07 | 14-AUG-05:02 | 1209472.10 | 07-AUG-15:40 | 0.00 | 0.00 | 0.00 |
September | 0.692859E+12 | 0.00 | 418.09 | 0.683600E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1393804.32 | 05-SEP-13:00 | 1032124.15 | 21-SEP-16:00 | 0.00 | 0.00 | 0.00 |
October | 0.312349E+12 | 0.00 | 272.76 | 0.312194E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 963742.65 | 06-OCT-15:30 | 963742.65 | 06-OCT-15:30 | 0.00 | 0.00 | 0.00 |
November | 0.167196E+11 | 0.00 | 87.11 | 0.167196E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 299589.49 | 02-NOV-15:00 | 299589.49 | 02-NOV-15:00 | 0.00 | 0.00 | 0.00 |
December | 550465.02 | 0.00 | 88.60 | 550465.02 | 0.00 | 0.00 | 0.00 | 0.00 | 2336.16 | 24-DEC-13:53 | 2336.16 | 24-DEC-13:53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.498184E+13 | 0.00 | 3234.42 | 0.492612E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 550465.02 | 0.00 | 68.91 | 550465.02 | 0.00 | 0.00 | 0.00 | 0.00 | 2336.16 | 2336.16 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.112765E+13 | 0.00 | 504.63 | 0.110337E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 1435347.13 | 1318385.25 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.308942E+09 | 0.00 | 18.71 | 0.308942E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12268.69 | 05-JAN-14:20 | 12268.69 | 05-JAN-14:20 | 0.00 | 0.00 | 0.00 |
February | 0.197302E+10 | 0.00 | 30.15 | 0.197302E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52697.47 | 14-FEB-16:00 | 52697.47 | 14-FEB-16:00 | 0.00 | 0.00 | 0.00 |
March | 0.588773E+10 | 0.00 | 114.22 | 0.588773E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60148.27 | 08-MAR-16:00 | 60148.27 | 08-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.275848E+11 | 0.00 | 228.60 | 0.275848E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 109539.40 | 26-APR-14:50 | 109539.40 | 26-APR-14:50 | 0.00 | 0.00 | 0.00 |
May | 0.523500E+11 | 0.00 | 340.10 | 0.523500E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 124975.45 | 19-MAY-15:20 | 124975.45 | 19-MAY-15:20 | 0.00 | 0.00 | 0.00 |
June | 0.106331E+12 | 0.00 | 457.79 | 0.106328E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 156804.16 | 28-JUN-14:50 | 156804.16 | 28-JUN-14:50 | 0.00 | 0.00 | 0.00 |
July | 0.130452E+12 | 0.00 | 506.20 | 0.127745E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 167423.49 | 16-JUL-14:51 | 155248.21 | 21-JUL-14:50 | 0.00 | 0.00 | 0.00 |
August | 0.121634E+12 | 0.00 | 504.41 | 0.119335E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 154990.60 | 14-AUG-05:02 | 148127.30 | 07-AUG-15:40 | 0.00 | 0.00 | 0.00 |
September | 0.753027E+11 | 0.00 | 408.98 | 0.745847E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 147800.76 | 05-SEP-13:30 | 123801.35 | 21-SEP-15:50 | 0.00 | 0.00 | 0.00 |
October | 0.312635E+11 | 0.00 | 242.52 | 0.312635E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 110927.30 | 06-OCT-15:20 | 110927.30 | 06-OCT-15:20 | 0.00 | 0.00 | 0.00 |
November | 0.104216E+10 | 0.00 | 46.29 | 0.104216E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25371.88 | 02-NOV-15:00 | 25371.88 | 02-NOV-15:00 | 0.00 | 0.00 | 0.00 |
December | 285.62 | 0.00 | 0.29 | 285.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 | 16-DEC-14:20 | 0.30 | 16-DEC-14:20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.554130E+12 | 0.00 | 2898.26 | 0.548403E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 285.62 | 0.00 | 0.29 | 285.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 | 0.30 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.130452E+12 | 0.00 | 506.20 | 0.127745E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 167423.49 | 156804.16 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 1944765.30 | 0.00 | 1.17 | 1944765.30 | 0.00 | 0.00 | 0.00 | 0.00 | 1039.11 | 02-JAN-15:00 | 1039.11 | 02-JAN-15:00 | 0.00 | 0.00 | 0.00 |
February | 0.126643E+10 | 0.00 | 16.00 | 0.126643E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41489.85 | 13-FEB-16:00 | 41489.85 | 13-FEB-16:00 | 0.00 | 0.00 | 0.00 |
March | 0.341756E+10 | 0.00 | 64.41 | 0.341756E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43396.92 | 08-MAR-16:00 | 43396.92 | 08-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.189055E+11 | 0.00 | 178.05 | 0.189055E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 62024.19 | 17-APR-15:00 | 62024.19 | 17-APR-15:00 | 0.00 | 0.00 | 0.00 |
May | 0.329603E+11 | 0.00 | 260.85 | 0.329583E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 96894.53 | 29-MAY-16:20 | 96894.53 | 29-MAY-16:20 | 0.00 | 0.00 | 0.00 |
June | 0.609459E+11 | 0.00 | 365.04 | 0.609323E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 87075.33 | 29-JUN-05:04 | 80693.54 | 29-JUN-05:04 | 0.00 | 0.00 | 0.00 |
July | 0.741519E+11 | 0.00 | 400.10 | 0.730896E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 132244.41 | 02-JUL-19:00 | 100407.31 | 04-JUL-17:47 | 0.00 | 0.00 | 0.00 |
August | 0.772154E+11 | 0.00 | 437.46 | 0.759345E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 108083.52 | 27-AUG-14:20 | 91187.50 | 13-AUG-19:00 | 0.00 | 0.00 | 0.00 |
September | 0.495564E+11 | 0.00 | 342.48 | 0.488051E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 102011.51 | 05-SEP-13:00 | 78435.52 | 17-SEP-16:18 | 0.00 | 0.00 | 0.00 |
October | 0.226805E+11 | 0.00 | 195.14 | 0.226771E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 98022.33 | 01-OCT-14:56 | 98022.33 | 01-OCT-14:56 | 0.00 | 0.00 | 0.00 |
November | 0.505839E+09 | 0.00 | 23.41 | 0.505839E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 23884.18 | 09-NOV-14:00 | 23884.18 | 09-NOV-14:00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.341608E+12 | 0.00 | 2284.10 | 0.338494E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.772154E+11 | 0.00 | 437.46 | 0.759345E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 132244.41 | 100407.31 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.395471E+12 | 0.100221E+12 | 744.00 | 0.346223E+12 | 0.492486E+11 | 0.00 | 0.38 | 03-JAN-22:03 | 0.35 | 21-JAN-07:10 | 152161.14 | 01-JAN-18:00 | 133154.39 | 02-JAN-22:07 | 19287.34 | 11-JAN-22:03 | 38379.75 | 03-JAN-22:03 | 0.00 |
February | 0.610891E+12 | 0.147688E+12 | 672.00 | 0.535683E+12 | 0.752074E+11 | 0.00 | 0.62 | 14-FEB-16:00 | 0.57 | 01-FEB-08:00 | 257548.52 | 24-FEB-22:03 | 225790.37 | 14-FEB-16:00 | 32788.34 | 25-FEB-01:00 | 77023.94 | 14-FEB-16:00 | 0.00 |
March | 0.956854E+12 | 0.227831E+12 | 744.00 | 0.843246E+12 | 0.113607E+12 | 0.00 | 1.00 | 31-MAR-23:10 | 0.79 | 01-MAR-07:05 | 460589.85 | 31-MAR-24:00 | 404561.06 | 31-MAR-24:00 | 56217.62 | 31-MAR-23:10 | 109816.65 | 08-MAR-16:00 | 0.00 |
April | 0.119141E+13 | 0.295847E+12 | 720.00 | 0.104932E+13 | 0.142088E+12 | 0.00 | 1.00 | 01-APR-00:10 | 0.43 | 30-APR-24:00 | 478633.84 | 29-APR-02:45 | 412420.75 | 29-APR-02:45 | 66562.23 | 29-APR-02:42 | 145517.79 | 13-APR-17:00 | 0.00 |
May | 0.398284E+12 | 0.113595E+12 | 744.00 | 0.355289E+12 | 0.429949E+11 | 0.00 | 0.60 | 31-MAY-23:30 | 0.36 | 04-MAY-06:05 | 246158.57 | 31-MAY-24:00 | 220347.55 | 31-MAY-24:00 | 25811.02 | 31-MAY-24:00 | 69551.48 | 31-MAY-23:20 | 0.00 |
June | 0.637742E+12 | 0.207029E+12 | 720.00 | 0.584394E+12 | 0.533480E+11 | 0.00 | 0.83 | 30-JUN-23:23 | 0.59 | 01-JUN-06:10 | 340747.25 | 30-JUN-24:00 | 312310.63 | 30-JUN-24:00 | 32964.19 | 10-JUN-05:55 | 115515.26 | 28-JUN-16:00 | 0.00 |
July | 0.912110E+12 | 0.317887E+12 | 744.00 | 0.851363E+12 | 0.607470E+11 | 0.00 | 1.00 | 31-JUL-23:03 | 0.82 | 01-JUL-06:10 | 437468.65 | 31-JUL-24:00 | 397177.19 | 31-JUL-23:43 | 40888.08 | 31-JUL-24:00 | 156968.94 | 22-JUL-15:00 | 0.00 |
August | 0.120949E+13 | 0.375943E+12 | 744.00 | 0.107715E+13 | 0.132346E+12 | 0.00 | 1.00 | 01-AUG-00:03 | 0.45 | 31-AUG-24:00 | 477540.35 | 31-AUG-05:55 | 411195.58 | 31-AUG-06:00 | 73630.81 | 25-AUG-20:30 | 171877.30 | 20-AUG-16:00 | 0.00 |
September | 0.389014E+12 | 0.116253E+12 | 720.00 | 0.348503E+12 | 0.405105E+11 | 0.00 | 0.60 | 30-SEP-24:00 | 0.37 | 09-SEP-06:10 | 248565.40 | 30-SEP-24:00 | 220982.78 | 30-SEP-24:00 | 27802.33 | 30-SEP-23:10 | 66661.29 | 30-SEP-23:30 | 0.00 |
October | 0.679505E+12 | 0.177692E+12 | 744.00 | 0.602541E+12 | 0.769638E+11 | 0.00 | 0.81 | 31-OCT-23:30 | 0.58 | 26-OCT-07:00 | 357743.79 | 31-OCT-24:00 | 314102.88 | 31-OCT-24:00 | 43640.91 | 31-OCT-24:00 | 90459.40 | 01-OCT-16:00 | 0.00 |
November | 0.934649E+12 | 0.216804E+12 | 720.00 | 0.819018E+12 | 0.115631E+12 | 0.00 | 0.83 | 09-NOV-14:00 | 0.80 | 27-NOV-07:10 | 365091.62 | 12-NOV-15:42 | 318934.12 | 02-NOV-21:03 | 46916.44 | 12-NOV-05:00 | 100826.51 | 09-NOV-14:00 | 0.00 |
December | 0.125057E+13 | 0.274456E+12 | 744.00 | 0.108715E+13 | 0.163415E+12 | 0.00 | 1.00 | 01-DEC-00:10 | 1.00 | 01-DEC-00:10 | 474053.44 | 24-DEC-16:50 | 409197.07 | 31-DEC-23:53 | 68709.01 | 26-DEC-07:30 | 108702.75 | 24-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.956599E+13 | 0.257125E+13 | 8760.00 | 0.849988E+13 | 0.106611E+13 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.389014E+12 | 0.100221E+12 | 672.00 | 0.346223E+12 | 0.405105E+11 | 0.00 | 0.38 | 0.35 | 152161.14 | 133154.39 | 19287.34 | 38379.75 | 0.00 | ||||||
Maximum of Months | 0.125057E+13 | 0.375943E+12 | 744.00 | 0.108715E+13 | 0.163415E+12 | 0.00 | 1.00 | 1.00 | 478633.84 | 412420.75 | 73630.81 | 171877.30 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.465683E+10 | 0.128825E+10 | 744.00 | 0.465626E+10 | 565560.60 | 0.00 | 0.34 | 26-JAN-17:00 | 0.13 | 21-JAN-07:40 | 2739.57 | 01-JAN-16:45 | 2732.77 | 01-JAN-16:50 | 27.26 | 20-JAN-17:00 | 724.66 | 26-JAN-17:00 | 0.00 |
February | 0.920797E+10 | 0.239455E+10 | 672.00 | 0.920510E+10 | 2871256.60 | 0.00 | 0.60 | 14-FEB-17:00 | 0.37 | 04-FEB-07:55 | 4821.74 | 15-FEB-17:00 | 4821.74 | 15-FEB-17:00 | 80.83 | 17-FEB-11:10 | 1511.36 | 14-FEB-17:00 | 0.00 |
March | 0.157697E+11 | 0.401316E+10 | 744.00 | 0.157656E+11 | 4159528.94 | 0.00 | 0.87 | 12-MAR-17:23 | 0.60 | 04-MAR-07:05 | 7764.25 | 31-MAR-24:00 | 7764.25 | 31-MAR-24:00 | 101.21 | 20-MAR-16:05 | 2224.86 | 12-MAR-17:01 | 0.00 |
April | 0.206312E+11 | 0.566874E+10 | 720.00 | 0.206310E+11 | 150507.51 | 0.00 | 1.00 | 01-APR-14:50 | 0.34 | 30-APR-23:53 | 8805.55 | 15-APR-18:00 | 8805.55 | 15-APR-18:00 | 46.05 | 20-APR-09:30 | 3018.22 | 13-APR-17:00 | 0.00 |
May | 0.615226E+10 | 0.186098E+10 | 744.00 | 0.611664E+10 | 35619393.78 | 0.00 | 0.51 | 31-MAY-23:50 | 0.20 | 05-MAY-06:05 | 4158.90 | 31-MAY-24:00 | 4158.90 | 31-MAY-24:00 | 273.37 | 24-MAY-15:50 | 1233.81 | 31-MAY-23:20 | 0.00 |
June | 0.111856E+11 | 0.374561E+10 | 720.00 | 0.111089E+11 | 76635713.32 | 0.00 | 0.71 | 30-JUN-23:15 | 0.44 | 09-JUN-06:10 | 6000.69 | 30-JUN-23:55 | 5992.71 | 30-JUN-24:00 | 313.24 | 30-JUN-14:00 | 2384.25 | 28-JUN-16:00 | 0.00 |
July | 0.167929E+11 | 0.591802E+10 | 744.00 | 0.165970E+11 | 0.195915E+09 | 0.00 | 0.92 | 04-JUL-18:11 | 0.68 | 08-JUL-06:05 | 7898.97 | 31-JUL-24:00 | 7898.97 | 31-JUL-24:00 | 430.32 | 07-JUL-17:00 | 3156.25 | 21-JUL-17:00 | 0.00 |
August | 0.221938E+11 | 0.751443E+10 | 744.00 | 0.219816E+11 | 0.212271E+09 | 0.00 | 1.00 | 01-AUG-12:00 | 0.35 | 31-AUG-24:00 | 8839.76 | 23-AUG-16:00 | 8688.18 | 27-AUG-18:52 | 418.27 | 23-AUG-14:00 | 3567.57 | 20-AUG-16:00 | 0.00 |
September | 0.626699E+10 | 0.191976E+10 | 720.00 | 0.613363E+10 | 0.133359E+09 | 0.00 | 0.49 | 30-SEP-24:00 | 0.23 | 09-SEP-06:05 | 4162.74 | 30-SEP-24:00 | 4162.74 | 30-SEP-24:00 | 300.07 | 05-SEP-14:40 | 1197.99 | 02-SEP-17:31 | 0.00 |
October | 0.110983E+11 | 0.304610E+10 | 744.00 | 0.110504E+11 | 47913064.21 | 0.00 | 0.69 | 31-OCT-23:30 | 0.39 | 26-OCT-06:55 | 5959.68 | 31-OCT-24:00 | 5959.68 | 31-OCT-24:00 | 256.85 | 02-OCT-17:00 | 1787.90 | 01-OCT-16:02 | 0.00 |
November | 0.151993E+11 | 0.375381E+10 | 720.00 | 0.151895E+11 | 9862134.69 | 0.00 | 0.80 | 19-NOV-16:35 | 0.62 | 10-NOV-07:50 | 6764.14 | 05-NOV-16:35 | 6764.14 | 05-NOV-16:35 | 131.87 | 02-NOV-11:10 | 1782.93 | 02-NOV-16:00 | 0.00 |
December | 0.205332E+11 | 0.496868E+10 | 744.00 | 0.205331E+11 | 106636.12 | 0.00 | 0.99 | 17-DEC-16:25 | 0.79 | 09-DEC-07:20 | 8647.90 | 31-DEC-16:35 | 8647.90 | 31-DEC-16:35 | 24.57 | 27-DEC-17:03 | 2129.65 | 24-DEC-15:55 | 0.00 |
Annual Sum or Average | 0.159688E+12 | 0.460921E+11 | 8760.00 | 0.158969E+12 | 0.719428E+09 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.465683E+10 | 0.128825E+10 | 672.00 | 0.465626E+10 | 106636.12 | 0.00 | 0.34 | 0.13 | 2739.57 | 2732.77 | 24.57 | 724.66 | 0.00 | ||||||
Maximum of Months | 0.221938E+11 | 0.751443E+10 | 744.00 | 0.219816E+11 | 0.212271E+09 | 0.00 | 1.00 | 0.79 | 8839.76 | 8805.55 | 430.32 | 3567.57 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.270774E+11 | 0.779763E+10 | 742.67 | 0.270715E+11 | 5964847.16 | 0.00 | 0.33 | 26-JAN-17:00 | 0.00 | 02-JAN-06:25 | 24318.51 | 26-JAN-17:00 | 24318.51 | 26-JAN-17:00 | 267.36 | 20-JAN-17:00 | 6592.74 | 26-JAN-17:00 | 0.00 |
February | 0.741894E+11 | 0.195964E+11 | 672.00 | 0.741603E+11 | 29090191.62 | 0.00 | 0.58 | 14-FEB-17:00 | 0.24 | 06-FEB-07:10 | 45188.43 | 15-FEB-17:00 | 45188.43 | 15-FEB-17:00 | 777.78 | 17-FEB-11:10 | 14110.60 | 14-FEB-17:00 | 0.00 |
March | 0.140280E+12 | 0.360363E+11 | 744.00 | 0.140237E+12 | 42665895.66 | 0.00 | 0.84 | 31-MAR-23:50 | 0.53 | 04-MAR-07:05 | 71602.95 | 31-MAR-23:50 | 71602.95 | 31-MAR-23:50 | 1001.37 | 20-MAR-16:05 | 20350.29 | 12-MAR-17:01 | 0.00 |
April | 0.191030E+12 | 0.528250E+11 | 720.00 | 0.191028E+12 | 2037609.10 | 0.00 | 1.00 | 01-APR-15:40 | 0.30 | 30-APR-23:55 | 82578.83 | 16-APR-18:23 | 82578.83 | 16-APR-18:23 | 488.57 | 20-APR-09:30 | 28820.10 | 13-APR-17:00 | 0.00 |
May | 0.549846E+11 | 0.167804E+11 | 744.00 | 0.546319E+11 | 0.352636E+09 | 0.00 | 0.51 | 31-MAY-23:40 | 0.16 | 05-MAY-06:15 | 39397.27 | 31-MAY-24:00 | 39397.27 | 31-MAY-24:00 | 2681.46 | 24-MAY-15:50 | 11712.98 | 31-MAY-23:20 | 0.00 |
June | 0.105373E+12 | 0.353960E+11 | 720.00 | 0.104608E+12 | 0.765012E+09 | 0.00 | 0.72 | 30-JUN-23:55 | 0.40 | 09-JUN-06:10 | 58044.68 | 30-JUN-23:55 | 57955.22 | 30-JUN-24:00 | 3075.30 | 30-JUN-14:00 | 22781.36 | 28-JUN-16:00 | 0.00 |
July | 0.160079E+12 | 0.564180E+11 | 744.00 | 0.158121E+12 | 0.195723E+10 | 0.00 | 0.92 | 04-JUL-18:31 | 0.67 | 08-JUL-06:05 | 76134.38 | 31-JUL-23:57 | 76134.38 | 31-JUL-23:57 | 4220.21 | 07-JUL-17:00 | 30212.07 | 21-JUL-18:10 | 0.00 |
August | 0.207220E+12 | 0.705323E+11 | 744.00 | 0.205091E+12 | 0.212904E+10 | 0.00 | 1.00 | 01-AUG-12:10 | 0.30 | 31-AUG-24:00 | 82636.76 | 23-AUG-16:00 | 80959.26 | 30-AUG-18:10 | 4139.48 | 23-AUG-14:00 | 34047.52 | 20-AUG-16:00 | 0.00 |
September | 0.568634E+11 | 0.175305E+11 | 720.00 | 0.555457E+11 | 0.131764E+10 | 0.00 | 0.49 | 30-SEP-24:00 | 0.20 | 09-SEP-06:15 | 39390.54 | 30-SEP-24:00 | 39390.54 | 30-SEP-24:00 | 2980.46 | 05-SEP-14:40 | 11336.14 | 02-SEP-17:31 | 0.00 |
October | 0.989303E+11 | 0.274099E+11 | 744.00 | 0.984531E+11 | 0.477161E+09 | 0.00 | 0.67 | 31-OCT-23:30 | 0.32 | 26-OCT-06:10 | 54635.74 | 31-OCT-24:00 | 54635.74 | 31-OCT-24:00 | 2539.22 | 02-OCT-17:00 | 16749.34 | 05-OCT-17:00 | 0.00 |
November | 0.132061E+12 | 0.329857E+11 | 720.00 | 0.131962E+12 | 98874215.58 | 0.00 | 0.74 | 02-NOV-16:40 | 0.51 | 27-NOV-07:10 | 62693.33 | 02-NOV-16:40 | 62040.32 | 02-NOV-16:40 | 1316.33 | 02-NOV-11:10 | 16771.94 | 02-NOV-16:00 | 0.00 |
December | 0.175523E+12 | 0.431146E+11 | 744.00 | 0.175522E+12 | 1329688.03 | 0.00 | 0.90 | 15-DEC-16:30 | 0.70 | 27-DEC-07:10 | 77432.00 | 29-DEC-16:40 | 77432.00 | 29-DEC-16:40 | 247.05 | 27-DEC-17:03 | 18460.98 | 01-DEC-16:10 | 0.00 |
Annual Sum or Average | 0.142361E+13 | 0.416423E+12 | 8758.67 | 0.141643E+13 | 0.717869E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.270774E+11 | 0.779763E+10 | 672.00 | 0.270715E+11 | 1329688.03 | 0.00 | 0.33 | 0.00 | 24318.51 | 24318.51 | 247.05 | 6592.74 | 0.00 | ||||||
Maximum of Months | 0.207220E+12 | 0.705323E+11 | 744.00 | 0.205091E+12 | 0.212904E+10 | 0.00 | 1.00 | 0.70 | 82636.76 | 82578.83 | 4220.21 | 34047.52 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.115165E+10 | 0.343399E+09 | 469.27 | 0.115116E+10 | 484069.41 | 0.00 | 0.31 | 26-JAN-17:00 | 0.00 | 01-JAN-00:05 | 2338.19 | 26-JAN-17:00 | 2338.19 | 26-JAN-17:00 | 33.06 | 01-JAN-16:45 | 637.21 | 26-JAN-17:00 | 0.00 |
February | 0.593354E+10 | 0.159592E+10 | 672.00 | 0.593075E+10 | 2789586.37 | 0.00 | 0.57 | 14-FEB-17:00 | 0.04 | 06-FEB-04:12 | 4541.62 | 15-FEB-17:00 | 4541.62 | 15-FEB-17:00 | 74.97 | 17-FEB-11:30 | 1418.73 | 14-FEB-17:00 | 0.00 |
March | 0.129775E+11 | 0.337431E+10 | 744.00 | 0.129733E+11 | 4156565.17 | 0.00 | 0.80 | 12-MAR-17:23 | 0.42 | 04-MAR-07:05 | 6795.57 | 31-MAR-23:20 | 6795.57 | 31-MAR-23:20 | 98.92 | 20-MAR-16:05 | 2014.66 | 08-MAR-17:00 | 0.00 |
April | 0.186663E+11 | 0.520652E+10 | 720.00 | 0.186662E+11 | 173621.51 | 0.00 | 1.00 | 01-APR-16:40 | 0.27 | 30-APR-23:53 | 8397.80 | 16-APR-18:04 | 8397.80 | 16-APR-18:04 | 45.94 | 20-APR-09:30 | 2944.00 | 13-APR-17:00 | 0.00 |
May | 0.531123E+10 | 0.163824E+10 | 744.00 | 0.527619E+10 | 35045541.92 | 0.00 | 0.49 | 31-MAY-23:30 | 0.08 | 05-MAY-06:05 | 3900.50 | 31-MAY-24:00 | 3900.50 | 31-MAY-24:00 | 266.52 | 24-MAY-15:50 | 1165.56 | 31-MAY-23:20 | 0.00 |
June | 0.105825E+11 | 0.357209E+10 | 720.00 | 0.105061E+11 | 76355110.54 | 0.00 | 0.73 | 18-JUN-18:11 | 0.34 | 09-JUN-06:10 | 5822.09 | 30-JUN-23:55 | 5812.99 | 30-JUN-24:00 | 310.07 | 30-JUN-14:00 | 2347.41 | 28-JUN-16:00 | 0.00 |
July | 0.161539E+11 | 0.570855E+10 | 744.00 | 0.159583E+11 | 0.195596E+09 | 0.00 | 0.95 | 04-JUL-18:11 | 0.64 | 08-JUL-06:05 | 7606.23 | 31-JUL-23:57 | 7606.23 | 31-JUL-23:57 | 424.62 | 07-JUL-17:00 | 3130.61 | 04-JUL-17:51 | 0.00 |
August | 0.208385E+11 | 0.711697E+10 | 744.00 | 0.206255E+11 | 0.212999E+09 | 0.00 | 1.00 | 01-AUG-12:40 | 0.30 | 31-AUG-24:00 | 8352.67 | 23-AUG-16:00 | 8243.71 | 13-AUG-19:55 | 414.51 | 23-AUG-14:00 | 3479.87 | 20-AUG-16:00 | 0.00 |
September | 0.561212E+10 | 0.174323E+10 | 720.00 | 0.548049E+10 | 0.131628E+09 | 0.00 | 0.48 | 30-SEP-23:40 | 0.15 | 09-SEP-06:45 | 3934.94 | 30-SEP-24:00 | 3934.94 | 30-SEP-24:00 | 300.29 | 05-SEP-14:30 | 1183.18 | 02-SEP-17:31 | 0.00 |
October | 0.923469E+10 | 0.259035E+10 | 744.00 | 0.918716E+10 | 47530270.12 | 0.00 | 0.63 | 31-OCT-23:20 | 0.21 | 26-OCT-06:10 | 5240.75 | 31-OCT-23:50 | 5240.75 | 31-OCT-23:50 | 254.33 | 02-OCT-17:00 | 1731.00 | 01-OCT-16:02 | 0.00 |
November | 0.117182E+11 | 0.297034E+10 | 720.00 | 0.117084E+11 | 9798696.10 | 0.00 | 0.73 | 02-NOV-16:40 | 0.35 | 27-NOV-04:15 | 6261.63 | 02-NOV-16:40 | 6196.01 | 02-NOV-16:40 | 131.77 | 02-NOV-11:10 | 1679.37 | 02-NOV-16:00 | 0.00 |
December | 0.155572E+11 | 0.388500E+10 | 744.00 | 0.155570E+11 | 117571.59 | 0.00 | 0.87 | 13-DEC-16:40 | 0.52 | 26-DEC-04:01 | 7665.17 | 29-DEC-16:40 | 7665.17 | 29-DEC-16:40 | 24.33 | 27-DEC-17:03 | 1828.44 | 01-DEC-16:10 | 0.00 |
Annual Sum or Average | 0.133737E+12 | 0.397449E+11 | 8485.27 | 0.133021E+12 | 0.716673E+09 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.115165E+10 | 0.343399E+09 | 469.27 | 0.115116E+10 | 117571.59 | 0.00 | 0.31 | 0.00 | 2338.19 | 2338.19 | 24.33 | 637.21 | 0.00 | ||||||
Maximum of Months | 0.208385E+11 | 0.711697E+10 | 744.00 | 0.206255E+11 | 0.212999E+09 | 0.00 | 1.00 | 0.64 | 8397.80 | 8397.80 | 424.62 | 3479.87 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 120.17 | 0.00 | 120.17 | 16.67 | 517.31 | 0.00 | 0.00 | 0.00 |
February | 150.20 | 0.00 | 150.20 | 43.02 | 467.77 | 0.00 | 0.00 | 0.00 |
March | 189.46 | 0.00 | 189.46 | 106.89 | 367.45 | 0.00 | 0.00 | 0.00 |
April | 240.36 | 2.06 | 238.30 | 184.55 | 243.06 | 0.00 | 0.00 | 0.00 |
May | 261.27 | 16.85 | 244.43 | 266.54 | 171.02 | 0.00 | 0.00 | 0.00 |
June | 296.88 | 48.58 | 248.29 | 420.84 | 111.47 | 0.00 | 0.00 | 0.00 |
July | 272.49 | 22.68 | 249.81 | 419.95 | 74.43 | 0.00 | 0.00 | 0.00 |
August | 252.78 | 5.66 | 247.12 | 351.97 | 87.33 | 0.00 | 0.00 | 0.00 |
September | 202.14 | 0.05 | 202.09 | 238.60 | 155.59 | 0.00 | 0.00 | 0.00 |
October | 150.84 | 0.00 | 150.84 | 102.18 | 286.23 | 0.00 | 0.00 | 0.00 |
November | 128.10 | 0.00 | 128.10 | 27.53 | 421.59 | 0.00 | 0.00 | 0.00 |
December | 102.29 | 0.00 | 102.29 | 2.94 | 561.75 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 197.42 | 8.00 | 189.42 | 182.55 | 287.89 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 102.29 | 0.00 | 102.29 | 2.94 | 74.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 296.88 | 48.58 | 249.81 | 420.84 | 561.75 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 120.17 | 0.00 | 120.17 | 16.67 | 517.31 | 0.00 | 0.00 | 0.00 |
February | 150.20 | 0.00 | 150.20 | 43.02 | 467.77 | 0.00 | 0.00 | 0.00 |
March | 189.45 | 0.00 | 189.45 | 106.89 | 367.45 | 0.00 | 0.00 | 0.00 |
April | 240.36 | 2.06 | 238.30 | 184.55 | 243.06 | 0.00 | 0.00 | 0.00 |
May | 261.27 | 16.84 | 244.43 | 266.53 | 171.02 | 0.00 | 0.00 | 0.00 |
June | 296.87 | 48.58 | 248.29 | 420.84 | 111.47 | 0.00 | 0.00 | 0.00 |
July | 272.48 | 22.68 | 249.81 | 419.94 | 74.43 | 0.00 | 0.00 | 0.00 |
August | 252.77 | 5.66 | 247.12 | 351.97 | 87.33 | 0.00 | 0.00 | 0.00 |
September | 202.14 | 0.05 | 202.09 | 238.59 | 155.59 | 0.00 | 0.00 | 0.00 |
October | 150.84 | 0.00 | 150.84 | 102.18 | 286.23 | 0.00 | 0.00 | 0.00 |
November | 128.10 | 0.00 | 128.10 | 27.53 | 421.59 | 0.00 | 0.00 | 0.00 |
December | 102.29 | 0.00 | 102.29 | 2.94 | 561.75 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 197.42 | 8.00 | 189.41 | 182.55 | 287.89 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 102.29 | 0.00 | 102.29 | 2.94 | 74.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 296.87 | 48.58 | 249.81 | 420.84 | 561.75 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 120.17 | 0.00 | 120.17 | 16.67 | 517.31 | 0.00 | 0.00 | 0.00 |
February | 150.20 | 0.00 | 150.20 | 43.02 | 467.77 | 0.00 | 0.00 | 0.00 |
March | 189.45 | 0.00 | 189.45 | 106.89 | 367.45 | 0.00 | 0.00 | 0.00 |
April | 240.36 | 2.06 | 238.30 | 184.55 | 243.06 | 0.00 | 0.00 | 0.00 |
May | 261.27 | 16.84 | 244.43 | 266.53 | 171.02 | 0.00 | 0.00 | 0.00 |
June | 296.87 | 48.58 | 248.29 | 420.84 | 111.47 | 0.00 | 0.00 | 0.00 |
July | 272.48 | 22.68 | 249.81 | 419.94 | 74.43 | 0.00 | 0.00 | 0.00 |
August | 252.78 | 5.66 | 247.12 | 351.97 | 87.33 | 0.00 | 0.00 | 0.00 |
September | 202.14 | 0.05 | 202.09 | 238.59 | 155.59 | 0.00 | 0.00 | 0.00 |
October | 150.84 | 0.00 | 150.84 | 102.18 | 286.23 | 0.00 | 0.00 | 0.00 |
November | 128.10 | 0.00 | 128.10 | 27.53 | 421.59 | 0.00 | 0.00 | 0.00 |
December | 102.29 | 0.00 | 102.29 | 2.94 | 561.75 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 197.42 | 8.00 | 189.41 | 182.55 | 287.89 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 102.29 | 0.00 | 102.29 | 2.94 | 74.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 296.87 | 48.58 | 249.81 | 420.84 | 561.75 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 120.17 | 0.00 | 120.17 | 16.67 | 517.31 | 0.00 | 0.00 | 0.00 |
February | 150.20 | 0.00 | 150.20 | 43.02 | 467.77 | 0.00 | 0.00 | 0.00 |
March | 189.45 | 0.00 | 189.45 | 106.89 | 367.45 | 0.00 | 0.00 | 0.00 |
April | 240.36 | 2.06 | 238.30 | 184.55 | 243.06 | 0.00 | 0.00 | 0.00 |
May | 261.27 | 16.84 | 244.43 | 266.53 | 171.02 | 0.00 | 0.00 | 0.00 |
June | 296.87 | 48.58 | 248.29 | 420.84 | 111.47 | 0.00 | 0.00 | 0.00 |
July | 272.48 | 22.68 | 249.81 | 419.94 | 74.43 | 0.00 | 0.00 | 0.00 |
August | 252.77 | 5.66 | 247.12 | 351.97 | 87.33 | 0.00 | 0.00 | 0.00 |
September | 202.14 | 0.05 | 202.09 | 238.59 | 155.59 | 0.00 | 0.00 | 0.00 |
October | 150.84 | 0.00 | 150.84 | 102.18 | 286.23 | 0.00 | 0.00 | 0.00 |
November | 128.10 | 0.00 | 128.10 | 27.53 | 421.59 | 0.00 | 0.00 | 0.00 |
December | 102.29 | 0.00 | 102.29 | 2.94 | 561.75 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 197.42 | 8.00 | 189.41 | 182.55 | 287.89 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 102.29 | 0.00 | 102.29 | 2.94 | 74.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 296.87 | 48.58 | 249.81 | 420.84 | 561.75 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 120.17 | 0.00 | 120.17 | 16.67 | 517.29 | 0.00 | 0.00 | 0.00 |
February | 150.19 | 0.00 | 150.19 | 43.02 | 467.75 | 0.00 | 0.00 | 0.00 |
March | 189.45 | 0.00 | 189.45 | 106.89 | 367.44 | 0.00 | 0.00 | 0.00 |
April | 240.35 | 2.06 | 238.29 | 184.54 | 243.05 | 0.00 | 0.00 | 0.00 |
May | 261.26 | 16.84 | 244.42 | 266.52 | 171.01 | 0.00 | 0.00 | 0.00 |
June | 296.86 | 48.58 | 248.28 | 420.82 | 111.46 | 0.00 | 0.00 | 0.00 |
July | 272.47 | 22.68 | 249.80 | 419.93 | 74.43 | 0.00 | 0.00 | 0.00 |
August | 252.76 | 5.66 | 247.11 | 351.95 | 87.32 | 0.00 | 0.00 | 0.00 |
September | 202.13 | 0.05 | 202.08 | 238.58 | 155.58 | 0.00 | 0.00 | 0.00 |
October | 150.83 | 0.00 | 150.83 | 102.18 | 286.22 | 0.00 | 0.00 | 0.00 |
November | 128.09 | 0.00 | 128.09 | 27.53 | 421.58 | 0.00 | 0.00 | 0.00 |
December | 102.28 | 0.00 | 102.28 | 2.94 | 561.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 197.41 | 8.00 | 189.41 | 182.54 | 287.88 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 102.28 | 0.00 | 102.28 | 2.94 | 74.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 296.86 | 48.58 | 249.80 | 420.82 | 561.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 369.79 | 206.75 | 163.04 | 303.74 | 519.66 | 0.00 | 0.00 | 0.00 |
February | 449.29 | 242.22 | 207.07 | 411.18 | 472.59 | 0.00 | 0.00 | 0.00 |
March | 592.68 | 336.93 | 255.75 | 626.91 | 371.54 | 0.00 | 0.00 | 0.00 |
April | 809.73 | 461.30 | 348.43 | 956.51 | 250.96 | 0.00 | 0.00 | 0.00 |
May | 772.65 | 440.33 | 332.32 | 970.73 | 192.55 | 0.00 | 0.00 | 0.00 |
June | 832.98 | 513.15 | 319.82 | 1161.28 | 120.24 | 0.00 | 0.00 | 0.00 |
July | 770.77 | 440.76 | 330.01 | 1124.24 | 78.19 | 0.00 | 0.00 | 0.00 |
August | 762.73 | 420.51 | 342.22 | 1077.16 | 88.05 | 0.00 | 0.00 | 0.00 |
September | 634.84 | 355.20 | 279.64 | 842.13 | 164.38 | 0.00 | 0.00 | 0.00 |
October | 552.12 | 350.30 | 201.82 | 635.32 | 290.01 | 0.00 | 0.00 | 0.00 |
November | 431.51 | 253.68 | 177.83 | 408.21 | 424.04 | 0.00 | 0.00 | 0.00 |
December | 349.64 | 212.79 | 136.85 | 292.08 | 554.90 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 611.32 | 353.26 | 258.06 | 735.60 | 293.05 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 349.64 | 206.75 | 136.85 | 292.08 | 78.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 832.98 | 513.15 | 348.43 | 1161.28 | 554.90 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 369.79 | 206.75 | 163.04 | 303.74 | 519.66 | 0.00 | 0.00 | 0.00 |
February | 449.29 | 242.22 | 207.07 | 411.18 | 472.59 | 0.00 | 0.00 | 0.00 |
March | 592.68 | 336.93 | 255.75 | 626.91 | 371.54 | 0.00 | 0.00 | 0.00 |
April | 809.73 | 461.30 | 348.43 | 956.51 | 250.96 | 0.00 | 0.00 | 0.00 |
May | 772.65 | 440.33 | 332.32 | 970.73 | 192.55 | 0.00 | 0.00 | 0.00 |
June | 832.98 | 513.15 | 319.82 | 1161.28 | 120.24 | 0.00 | 0.00 | 0.00 |
July | 770.77 | 440.76 | 330.01 | 1124.24 | 78.19 | 0.00 | 0.00 | 0.00 |
August | 762.73 | 420.51 | 342.22 | 1077.16 | 88.05 | 0.00 | 0.00 | 0.00 |
September | 634.84 | 355.20 | 279.64 | 842.13 | 164.38 | 0.00 | 0.00 | 0.00 |
October | 552.12 | 350.30 | 201.82 | 635.32 | 290.01 | 0.00 | 0.00 | 0.00 |
November | 431.51 | 253.68 | 177.83 | 408.21 | 424.04 | 0.00 | 0.00 | 0.00 |
December | 349.64 | 212.79 | 136.85 | 292.08 | 554.90 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 611.32 | 353.26 | 258.06 | 735.60 | 293.05 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 349.64 | 206.75 | 136.85 | 292.08 | 78.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 832.98 | 513.15 | 348.43 | 1161.28 | 554.90 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 369.79 | 206.75 | 163.04 | 303.74 | 519.65 | 0.00 | 0.00 | 0.00 |
February | 449.28 | 242.21 | 207.07 | 411.17 | 472.58 | 0.00 | 0.00 | 0.00 |
March | 592.67 | 336.92 | 255.75 | 626.90 | 371.54 | 0.00 | 0.00 | 0.00 |
April | 809.71 | 461.29 | 348.42 | 956.49 | 250.95 | 0.00 | 0.00 | 0.00 |
May | 772.64 | 440.32 | 332.32 | 970.71 | 192.54 | 0.00 | 0.00 | 0.00 |
June | 832.96 | 513.14 | 319.82 | 1161.26 | 120.24 | 0.00 | 0.00 | 0.00 |
July | 770.75 | 440.75 | 330.01 | 1124.22 | 78.19 | 0.00 | 0.00 | 0.00 |
August | 762.71 | 420.50 | 342.21 | 1077.14 | 88.05 | 0.00 | 0.00 | 0.00 |
September | 634.83 | 355.19 | 279.64 | 842.11 | 164.37 | 0.00 | 0.00 | 0.00 |
October | 552.11 | 350.29 | 201.82 | 635.31 | 290.00 | 0.00 | 0.00 | 0.00 |
November | 431.50 | 253.68 | 177.82 | 408.20 | 424.03 | 0.00 | 0.00 | 0.00 |
December | 349.64 | 212.79 | 136.85 | 292.07 | 554.89 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 611.31 | 353.26 | 258.06 | 735.58 | 293.04 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 349.64 | 206.75 | 136.85 | 292.07 | 78.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 832.96 | 513.14 | 348.42 | 1161.26 | 554.89 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 888.44 | 691.32 | 197.11 | 1015.83 | 459.17 | 0.00 | 0.00 | 0.00 |
February | 869.46 | 635.11 | 234.35 | 1016.96 | 427.25 | 0.00 | 0.00 | 0.00 |
March | 640.70 | 387.34 | 253.36 | 764.97 | 350.65 | 0.00 | 0.00 | 0.00 |
April | 499.67 | 205.10 | 294.56 | 620.19 | 251.75 | 0.00 | 0.00 | 0.00 |
May | 333.24 | 73.31 | 259.93 | 417.79 | 182.59 | 0.00 | 0.00 | 0.00 |
June | 281.89 | 34.74 | 247.15 | 421.16 | 119.12 | 0.00 | 0.00 | 0.00 |
July | 311.93 | 49.81 | 262.12 | 506.02 | 78.35 | 0.00 | 0.00 | 0.00 |
August | 428.92 | 139.42 | 289.50 | 662.90 | 93.69 | 0.00 | 0.00 | 0.00 |
September | 593.10 | 330.73 | 262.37 | 850.01 | 161.18 | 0.00 | 0.00 | 0.00 |
October | 811.43 | 597.62 | 213.82 | 1041.67 | 270.97 | 0.00 | 0.00 | 0.00 |
November | 903.78 | 693.65 | 210.13 | 1066.93 | 378.52 | 0.00 | 0.00 | 0.00 |
December | 963.93 | 795.14 | 168.79 | 1109.51 | 479.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 625.85 | 384.83 | 241.02 | 789.87 | 270.28 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 281.89 | 34.74 | 168.79 | 417.79 | 78.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 963.93 | 795.14 | 294.56 | 1109.51 | 479.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 888.43 | 691.32 | 197.11 | 1015.83 | 459.17 | 0.00 | 0.00 | 0.00 |
February | 869.45 | 635.10 | 234.35 | 1016.95 | 427.25 | 0.00 | 0.00 | 0.00 |
March | 640.70 | 387.34 | 253.36 | 764.96 | 350.65 | 0.00 | 0.00 | 0.00 |
April | 499.66 | 205.10 | 294.56 | 620.19 | 251.75 | 0.00 | 0.00 | 0.00 |
May | 333.24 | 73.30 | 259.93 | 417.78 | 182.59 | 0.00 | 0.00 | 0.00 |
June | 281.89 | 34.74 | 247.15 | 421.16 | 119.12 | 0.00 | 0.00 | 0.00 |
July | 311.93 | 49.81 | 262.11 | 506.01 | 78.35 | 0.00 | 0.00 | 0.00 |
August | 428.92 | 139.42 | 289.50 | 662.90 | 93.69 | 0.00 | 0.00 | 0.00 |
September | 593.10 | 330.73 | 262.37 | 850.00 | 161.18 | 0.00 | 0.00 | 0.00 |
October | 811.43 | 597.61 | 213.82 | 1041.66 | 270.97 | 0.00 | 0.00 | 0.00 |
November | 903.78 | 693.64 | 210.13 | 1066.92 | 378.52 | 0.00 | 0.00 | 0.00 |
December | 963.92 | 795.13 | 168.79 | 1109.50 | 479.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 625.84 | 384.83 | 241.02 | 789.87 | 270.28 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 281.89 | 34.74 | 168.79 | 417.78 | 78.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 963.92 | 795.13 | 294.56 | 1109.50 | 479.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 888.44 | 691.32 | 197.11 | 1015.83 | 459.17 | 0.00 | 0.00 | 0.00 |
February | 869.46 | 635.11 | 234.35 | 1016.96 | 427.25 | 0.00 | 0.00 | 0.00 |
March | 640.70 | 387.34 | 253.36 | 764.97 | 350.65 | 0.00 | 0.00 | 0.00 |
April | 499.67 | 205.10 | 294.56 | 620.19 | 251.75 | 0.00 | 0.00 | 0.00 |
May | 333.24 | 73.31 | 259.93 | 417.79 | 182.59 | 0.00 | 0.00 | 0.00 |
June | 281.89 | 34.74 | 247.15 | 421.16 | 119.12 | 0.00 | 0.00 | 0.00 |
July | 311.93 | 49.81 | 262.12 | 506.02 | 78.35 | 0.00 | 0.00 | 0.00 |
August | 428.92 | 139.42 | 289.50 | 662.90 | 93.69 | 0.00 | 0.00 | 0.00 |
September | 593.10 | 330.73 | 262.37 | 850.01 | 161.18 | 0.00 | 0.00 | 0.00 |
October | 811.43 | 597.62 | 213.82 | 1041.67 | 270.97 | 0.00 | 0.00 | 0.00 |
November | 903.78 | 693.65 | 210.13 | 1066.93 | 378.52 | 0.00 | 0.00 | 0.00 |
December | 963.93 | 795.14 | 168.79 | 1109.51 | 479.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 625.85 | 384.83 | 241.02 | 789.87 | 270.28 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 281.89 | 34.74 | 168.79 | 417.79 | 78.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 963.93 | 795.14 | 294.56 | 1109.51 | 479.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 888.43 | 691.32 | 197.11 | 1015.83 | 459.17 | 0.00 | 0.00 | 0.00 |
February | 869.45 | 635.10 | 234.35 | 1016.95 | 427.25 | 0.00 | 0.00 | 0.00 |
March | 640.70 | 387.34 | 253.36 | 764.96 | 350.65 | 0.00 | 0.00 | 0.00 |
April | 499.66 | 205.10 | 294.56 | 620.19 | 251.75 | 0.00 | 0.00 | 0.00 |
May | 333.24 | 73.30 | 259.93 | 417.78 | 182.59 | 0.00 | 0.00 | 0.00 |
June | 281.89 | 34.74 | 247.15 | 421.16 | 119.12 | 0.00 | 0.00 | 0.00 |
July | 311.93 | 49.81 | 262.11 | 506.01 | 78.35 | 0.00 | 0.00 | 0.00 |
August | 428.92 | 139.42 | 289.50 | 662.90 | 93.69 | 0.00 | 0.00 | 0.00 |
September | 593.10 | 330.73 | 262.37 | 850.00 | 161.18 | 0.00 | 0.00 | 0.00 |
October | 811.43 | 597.61 | 213.82 | 1041.66 | 270.97 | 0.00 | 0.00 | 0.00 |
November | 903.78 | 693.64 | 210.13 | 1066.92 | 378.52 | 0.00 | 0.00 | 0.00 |
December | 963.92 | 795.13 | 168.79 | 1109.50 | 479.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 625.84 | 384.83 | 241.02 | 789.87 | 270.28 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 281.89 | 34.74 | 168.79 | 417.78 | 78.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 963.92 | 795.13 | 294.56 | 1109.50 | 479.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 888.40 | 691.29 | 197.10 | 1015.79 | 459.15 | 0.00 | 0.00 | 0.00 |
February | 869.42 | 635.08 | 234.34 | 1016.92 | 427.23 | 0.00 | 0.00 | 0.00 |
March | 640.67 | 387.32 | 253.35 | 764.93 | 350.64 | 0.00 | 0.00 | 0.00 |
April | 499.64 | 205.09 | 294.55 | 620.16 | 251.74 | 0.00 | 0.00 | 0.00 |
May | 333.22 | 73.30 | 259.92 | 417.77 | 182.58 | 0.00 | 0.00 | 0.00 |
June | 281.88 | 34.74 | 247.14 | 421.15 | 119.12 | 0.00 | 0.00 | 0.00 |
July | 311.91 | 49.81 | 262.10 | 505.99 | 78.34 | 0.00 | 0.00 | 0.00 |
August | 428.90 | 139.41 | 289.49 | 662.88 | 93.68 | 0.00 | 0.00 | 0.00 |
September | 593.08 | 330.72 | 262.36 | 849.97 | 161.17 | 0.00 | 0.00 | 0.00 |
October | 811.40 | 597.59 | 213.81 | 1041.62 | 270.96 | 0.00 | 0.00 | 0.00 |
November | 903.74 | 693.62 | 210.12 | 1066.88 | 378.51 | 0.00 | 0.00 | 0.00 |
December | 963.88 | 795.10 | 168.78 | 1109.46 | 479.77 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 625.82 | 384.81 | 241.01 | 789.84 | 270.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 281.88 | 34.74 | 168.78 | 417.77 | 78.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 963.88 | 795.10 | 294.55 | 1109.46 | 479.77 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 381.43 | 217.52 | 163.91 | 348.77 | 579.41 | 0.00 | 0.00 | 0.00 |
February | 491.02 | 283.65 | 207.37 | 483.80 | 541.64 | 0.00 | 0.00 | 0.00 |
March | 548.42 | 291.93 | 256.48 | 574.66 | 440.76 | 0.00 | 0.00 | 0.00 |
April | 699.95 | 372.52 | 327.43 | 797.81 | 313.87 | 0.00 | 0.00 | 0.00 |
May | 663.65 | 341.96 | 321.69 | 819.40 | 219.10 | 0.00 | 0.00 | 0.00 |
June | 711.43 | 396.97 | 314.46 | 992.92 | 154.26 | 0.00 | 0.00 | 0.00 |
July | 641.69 | 314.03 | 327.66 | 934.82 | 106.67 | 0.00 | 0.00 | 0.00 |
August | 655.69 | 303.29 | 352.41 | 914.33 | 134.09 | 0.00 | 0.00 | 0.00 |
September | 592.25 | 311.91 | 280.33 | 788.67 | 193.25 | 0.00 | 0.00 | 0.00 |
October | 541.82 | 336.76 | 205.06 | 634.68 | 344.46 | 0.00 | 0.00 | 0.00 |
November | 425.33 | 250.23 | 175.10 | 410.00 | 493.61 | 0.00 | 0.00 | 0.00 |
December | 367.82 | 230.66 | 137.16 | 324.66 | 651.68 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 560.09 | 304.14 | 255.95 | 669.37 | 346.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 367.82 | 217.52 | 137.16 | 324.66 | 106.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 711.43 | 396.97 | 352.41 | 992.92 | 651.68 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 381.43 | 217.52 | 163.91 | 348.77 | 579.41 | 0.00 | 0.00 | 0.00 |
February | 491.02 | 283.65 | 207.37 | 483.80 | 541.64 | 0.00 | 0.00 | 0.00 |
March | 548.42 | 291.93 | 256.48 | 574.66 | 440.76 | 0.00 | 0.00 | 0.00 |
April | 699.95 | 372.52 | 327.43 | 797.81 | 313.87 | 0.00 | 0.00 | 0.00 |
May | 663.65 | 341.96 | 321.69 | 819.40 | 219.10 | 0.00 | 0.00 | 0.00 |
June | 711.43 | 396.97 | 314.46 | 992.92 | 154.26 | 0.00 | 0.00 | 0.00 |
July | 641.69 | 314.03 | 327.66 | 934.82 | 106.67 | 0.00 | 0.00 | 0.00 |
August | 655.69 | 303.29 | 352.41 | 914.33 | 134.09 | 0.00 | 0.00 | 0.00 |
September | 592.25 | 311.91 | 280.33 | 788.67 | 193.25 | 0.00 | 0.00 | 0.00 |
October | 541.82 | 336.76 | 205.06 | 634.68 | 344.46 | 0.00 | 0.00 | 0.00 |
November | 425.33 | 250.23 | 175.10 | 410.00 | 493.61 | 0.00 | 0.00 | 0.00 |
December | 367.82 | 230.66 | 137.16 | 324.66 | 651.68 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 560.09 | 304.14 | 255.95 | 669.37 | 346.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 367.82 | 217.52 | 137.16 | 324.66 | 106.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 711.43 | 396.97 | 352.41 | 992.92 | 651.68 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 381.42 | 217.51 | 163.91 | 348.76 | 579.40 | 0.00 | 0.00 | 0.00 |
February | 491.02 | 283.65 | 207.37 | 483.79 | 541.63 | 0.00 | 0.00 | 0.00 |
March | 548.41 | 291.93 | 256.48 | 574.65 | 440.75 | 0.00 | 0.00 | 0.00 |
April | 699.93 | 372.51 | 327.43 | 797.80 | 313.86 | 0.00 | 0.00 | 0.00 |
May | 663.64 | 341.95 | 321.69 | 819.38 | 219.10 | 0.00 | 0.00 | 0.00 |
June | 711.42 | 396.96 | 314.45 | 992.90 | 154.26 | 0.00 | 0.00 | 0.00 |
July | 641.68 | 314.03 | 327.65 | 934.80 | 106.67 | 0.00 | 0.00 | 0.00 |
August | 655.68 | 303.28 | 352.40 | 914.31 | 134.09 | 0.00 | 0.00 | 0.00 |
September | 592.23 | 311.91 | 280.33 | 788.66 | 193.25 | 0.00 | 0.00 | 0.00 |
October | 541.81 | 336.76 | 205.06 | 634.67 | 344.46 | 0.00 | 0.00 | 0.00 |
November | 425.32 | 250.23 | 175.10 | 410.00 | 493.60 | 0.00 | 0.00 | 0.00 |
December | 367.82 | 230.66 | 137.16 | 324.65 | 651.67 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 560.08 | 304.14 | 255.95 | 669.36 | 346.78 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 367.82 | 217.51 | 137.16 | 324.65 | 106.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 711.42 | 396.96 | 352.40 | 992.90 | 651.67 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 600.87 | 0.00 | 600.87 | 130.76 | 2337.11 | 0.00 | 0.00 | 0.00 |
February | 750.99 | 0.00 | 750.99 | 277.59 | 2115.37 | 0.00 | 0.00 | 0.00 |
March | 947.28 | 0.00 | 947.28 | 594.94 | 1672.51 | 0.00 | 0.00 | 0.00 |
April | 1201.80 | 10.29 | 1191.51 | 968.51 | 1119.94 | 0.00 | 0.00 | 0.00 |
May | 1306.37 | 84.23 | 1222.14 | 1352.90 | 817.43 | 0.00 | 0.00 | 0.00 |
June | 1484.38 | 242.92 | 1241.47 | 2117.87 | 544.90 | 0.00 | 0.00 | 0.00 |
July | 1362.43 | 113.40 | 1249.04 | 2114.06 | 369.90 | 0.00 | 0.00 | 0.00 |
August | 1263.88 | 28.30 | 1235.59 | 1786.86 | 417.04 | 0.00 | 0.00 | 0.00 |
September | 1010.72 | 0.26 | 1010.46 | 1208.70 | 743.05 | 0.00 | 0.00 | 0.00 |
October | 754.20 | 0.00 | 754.20 | 549.34 | 1310.68 | 0.00 | 0.00 | 0.00 |
November | 640.49 | 0.00 | 640.49 | 187.04 | 1863.55 | 0.00 | 0.00 | 0.00 |
December | 511.43 | 0.00 | 511.43 | 39.69 | 2455.37 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 987.10 | 40.02 | 947.07 | 947.56 | 1310.01 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 511.43 | 0.00 | 511.43 | 39.69 | 369.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1484.38 | 242.92 | 1249.04 | 2117.87 | 2455.37 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1109.37 | 620.24 | 489.13 | 944.65 | 1441.34 | 0.00 | 0.00 | 0.00 |
February | 1347.86 | 726.64 | 621.22 | 1262.27 | 1319.67 | 0.00 | 0.00 | 0.00 |
March | 1778.03 | 1010.78 | 767.25 | 1889.98 | 1056.24 | 0.00 | 0.00 | 0.00 |
April | 2429.15 | 1383.87 | 1045.28 | 2858.31 | 739.38 | 0.00 | 0.00 | 0.00 |
May | 2317.93 | 1320.97 | 996.96 | 2897.44 | 565.55 | 0.00 | 0.00 | 0.00 |
June | 2498.90 | 1539.44 | 959.46 | 3467.24 | 365.54 | 0.00 | 0.00 | 0.00 |
July | 2312.28 | 1322.25 | 990.02 | 3354.63 | 254.03 | 0.00 | 0.00 | 0.00 |
August | 2288.15 | 1261.50 | 1026.65 | 3213.46 | 284.98 | 0.00 | 0.00 | 0.00 |
September | 1904.50 | 1065.59 | 838.92 | 2516.91 | 484.28 | 0.00 | 0.00 | 0.00 |
October | 1656.33 | 1050.88 | 605.45 | 1908.72 | 830.42 | 0.00 | 0.00 | 0.00 |
November | 1294.51 | 761.03 | 533.48 | 1244.46 | 1177.05 | 0.00 | 0.00 | 0.00 |
December | 1048.92 | 638.36 | 410.56 | 901.65 | 1521.51 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1833.95 | 1059.78 | 774.18 | 2209.25 | 834.29 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1048.92 | 620.24 | 410.56 | 901.65 | 254.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2498.90 | 1539.44 | 1045.28 | 3467.24 | 1521.51 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 4442.26 | 3456.69 | 985.57 | 5058.29 | 2251.45 | 0.00 | 0.00 | 0.00 |
February | 4347.36 | 3175.60 | 1171.76 | 5063.11 | 2086.62 | 0.00 | 0.00 | 0.00 |
March | 3203.56 | 1936.75 | 1266.81 | 3812.43 | 1700.20 | 0.00 | 0.00 | 0.00 |
April | 2498.36 | 1025.53 | 1472.83 | 3097.20 | 1213.92 | 0.00 | 0.00 | 0.00 |
May | 1666.20 | 366.53 | 1299.67 | 2086.71 | 888.53 | 0.00 | 0.00 | 0.00 |
June | 1409.47 | 173.70 | 1235.77 | 2117.30 | 583.22 | 0.00 | 0.00 | 0.00 |
July | 1559.65 | 249.06 | 1310.59 | 2536.88 | 392.71 | 0.00 | 0.00 | 0.00 |
August | 2144.63 | 697.11 | 1447.52 | 3318.71 | 458.93 | 0.00 | 0.00 | 0.00 |
September | 2965.56 | 1653.69 | 1311.88 | 4226.80 | 796.09 | 0.00 | 0.00 | 0.00 |
October | 4057.25 | 2988.14 | 1069.11 | 5181.25 | 1332.25 | 0.00 | 0.00 | 0.00 |
November | 4519.00 | 3468.32 | 1050.68 | 5315.17 | 1842.70 | 0.00 | 0.00 | 0.00 |
December | 4819.72 | 3975.77 | 843.96 | 5536.72 | 2311.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3129.29 | 1924.18 | 1205.11 | 3939.51 | 1317.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1409.47 | 173.70 | 843.96 | 2086.71 | 392.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4819.72 | 3975.77 | 1472.83 | 5536.72 | 2311.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1144.27 | 652.54 | 491.73 | 1083.69 | 1572.44 | 0.00 | 0.00 | 0.00 |
February | 1473.06 | 850.94 | 622.12 | 1498.76 | 1444.87 | 0.00 | 0.00 | 0.00 |
March | 1645.24 | 875.79 | 769.45 | 1775.04 | 1161.42 | 0.00 | 0.00 | 0.00 |
April | 2099.82 | 1117.53 | 982.28 | 2443.19 | 823.26 | 0.00 | 0.00 | 0.00 |
May | 1990.93 | 1025.87 | 965.06 | 2469.82 | 614.37 | 0.00 | 0.00 | 0.00 |
June | 2134.28 | 1190.90 | 943.37 | 2998.11 | 429.60 | 0.00 | 0.00 | 0.00 |
July | 1925.05 | 942.09 | 982.96 | 2832.02 | 288.71 | 0.00 | 0.00 | 0.00 |
August | 1967.06 | 909.85 | 1057.21 | 2792.58 | 331.45 | 0.00 | 0.00 | 0.00 |
September | 1776.72 | 935.73 | 840.99 | 2376.37 | 540.73 | 0.00 | 0.00 | 0.00 |
October | 1625.46 | 1010.28 | 615.18 | 1934.01 | 925.05 | 0.00 | 0.00 | 0.00 |
November | 1275.98 | 750.69 | 525.29 | 1280.43 | 1267.30 | 0.00 | 0.00 | 0.00 |
December | 1103.46 | 691.99 | 411.47 | 1023.41 | 1626.67 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1680.26 | 912.42 | 767.84 | 2044.21 | 916.18 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1103.46 | 652.54 | 411.47 | 1023.41 | 288.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2134.28 | 1190.90 | 1057.21 | 2998.11 | 1626.67 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 600.87 | 0.00 | 600.87 | 163.58 | 2160.35 | 0.00 | 0.00 | 0.00 |
February | 750.99 | 0.00 | 750.99 | 315.69 | 1962.45 | 0.00 | 0.00 | 0.00 |
March | 947.28 | 0.00 | 947.28 | 635.70 | 1555.94 | 0.00 | 0.00 | 0.00 |
April | 1201.80 | 10.29 | 1191.51 | 990.09 | 1060.34 | 0.00 | 0.00 | 0.00 |
May | 1306.37 | 84.23 | 1222.14 | 1358.10 | 794.11 | 0.00 | 0.00 | 0.00 |
June | 1484.38 | 242.92 | 1241.47 | 2104.38 | 544.01 | 0.00 | 0.00 | 0.00 |
July | 1362.43 | 113.40 | 1249.04 | 2092.20 | 377.69 | 0.00 | 0.00 | 0.00 |
August | 1263.88 | 28.30 | 1235.59 | 1768.86 | 422.09 | 0.00 | 0.00 | 0.00 |
September | 1010.72 | 0.26 | 1010.46 | 1204.92 | 727.75 | 0.00 | 0.00 | 0.00 |
October | 754.20 | 0.00 | 754.20 | 570.79 | 1225.13 | 0.00 | 0.00 | 0.00 |
November | 640.49 | 0.00 | 640.49 | 225.95 | 1693.93 | 0.00 | 0.00 | 0.00 |
December | 511.43 | 0.00 | 511.43 | 57.90 | 2258.92 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 987.10 | 40.02 | 947.07 | 960.71 | 1228.36 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 511.43 | 0.00 | 511.43 | 57.90 | 377.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1484.38 | 242.92 | 1249.04 | 2104.38 | 2258.92 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1109.37 | 620.24 | 489.13 | 986.54 | 1337.14 | 0.00 | 0.00 | 0.00 |
February | 1347.86 | 726.64 | 621.22 | 1299.87 | 1230.36 | 0.00 | 0.00 | 0.00 |
March | 1778.03 | 1010.78 | 767.25 | 1914.45 | 995.76 | 0.00 | 0.00 | 0.00 |
April | 2429.15 | 1383.87 | 1045.28 | 2863.54 | 713.29 | 0.00 | 0.00 | 0.00 |
May | 2317.93 | 1320.97 | 996.96 | 2891.58 | 554.84 | 0.00 | 0.00 | 0.00 |
June | 2498.90 | 1539.44 | 959.46 | 3453.37 | 366.51 | 0.00 | 0.00 | 0.00 |
July | 2312.28 | 1322.25 | 990.02 | 3337.99 | 259.74 | 0.00 | 0.00 | 0.00 |
August | 2288.15 | 1261.50 | 1026.65 | 3198.56 | 289.76 | 0.00 | 0.00 | 0.00 |
September | 1904.50 | 1065.59 | 838.92 | 2510.63 | 479.33 | 0.00 | 0.00 | 0.00 |
October | 1656.33 | 1050.88 | 605.45 | 1920.54 | 791.12 | 0.00 | 0.00 | 0.00 |
November | 1294.51 | 761.03 | 533.48 | 1281.95 | 1083.11 | 0.00 | 0.00 | 0.00 |
December | 1048.92 | 638.36 | 410.56 | 933.58 | 1401.16 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1833.95 | 1059.78 | 774.18 | 2220.17 | 789.68 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1048.92 | 620.24 | 410.56 | 933.58 | 259.74 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2498.90 | 1539.44 | 1045.28 | 3453.37 | 1401.16 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 4442.26 | 3456.69 | 985.57 | 5114.76 | 2091.62 | 0.00 | 0.00 | 0.00 |
February | 4347.36 | 3175.60 | 1171.76 | 5107.93 | 1945.71 | 0.00 | 0.00 | 0.00 |
March | 3203.56 | 1936.75 | 1266.81 | 3843.46 | 1601.85 | 0.00 | 0.00 | 0.00 |
April | 2498.36 | 1025.53 | 1472.83 | 3107.10 | 1159.32 | 0.00 | 0.00 | 0.00 |
May | 1666.20 | 366.53 | 1299.67 | 2086.12 | 861.74 | 0.00 | 0.00 | 0.00 |
June | 1409.47 | 173.70 | 1235.77 | 2104.08 | 578.44 | 0.00 | 0.00 | 0.00 |
July | 1559.65 | 249.06 | 1310.59 | 2515.66 | 399.09 | 0.00 | 0.00 | 0.00 |
August | 2144.63 | 697.11 | 1447.52 | 3298.49 | 463.83 | 0.00 | 0.00 | 0.00 |
September | 2965.56 | 1653.69 | 1311.88 | 4216.63 | 785.14 | 0.00 | 0.00 | 0.00 |
October | 4057.25 | 2988.14 | 1069.11 | 5196.98 | 1271.34 | 0.00 | 0.00 | 0.00 |
November | 4519.00 | 3468.32 | 1050.68 | 5363.15 | 1709.70 | 0.00 | 0.00 | 0.00 |
December | 4819.72 | 3975.77 | 843.96 | 5582.67 | 2134.30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3129.29 | 1924.18 | 1205.11 | 3954.88 | 1246.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1409.47 | 173.70 | 843.96 | 2086.12 | 399.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4819.72 | 3975.77 | 1472.83 | 5582.67 | 2134.30 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1144.27 | 652.54 | 491.73 | 1104.19 | 1469.49 | 0.00 | 0.00 | 0.00 |
February | 1473.06 | 850.94 | 622.12 | 1517.38 | 1358.03 | 0.00 | 0.00 | 0.00 |
March | 1645.24 | 875.79 | 769.45 | 1792.02 | 1097.41 | 0.00 | 0.00 | 0.00 |
April | 2099.82 | 1117.53 | 982.28 | 2448.60 | 790.31 | 0.00 | 0.00 | 0.00 |
May | 1990.93 | 1025.87 | 965.06 | 2467.58 | 598.70 | 0.00 | 0.00 | 0.00 |
June | 2134.28 | 1190.90 | 943.37 | 2987.07 | 427.63 | 0.00 | 0.00 | 0.00 |
July | 1925.05 | 942.09 | 982.96 | 2817.06 | 291.98 | 0.00 | 0.00 | 0.00 |
August | 1967.06 | 909.85 | 1057.21 | 2779.41 | 334.18 | 0.00 | 0.00 | 0.00 |
September | 1776.72 | 935.73 | 840.99 | 2371.24 | 533.06 | 0.00 | 0.00 | 0.00 |
October | 1625.46 | 1010.28 | 615.18 | 1940.73 | 880.77 | 0.00 | 0.00 | 0.00 |
November | 1275.98 | 750.69 | 525.29 | 1301.01 | 1174.23 | 0.00 | 0.00 | 0.00 |
December | 1103.46 | 691.99 | 411.47 | 1037.60 | 1515.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1680.26 | 912.42 | 767.84 | 2048.82 | 870.16 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1103.46 | 652.54 | 411.47 | 1037.60 | 291.98 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2134.28 | 1190.90 | 1057.21 | 2987.07 | 1515.38 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.321876E+09 | 0.00 | 0.321876E+09 | 44655205.31 | 0.138557E+10 |
February | 0.363359E+09 | 0.00 | 0.363359E+09 | 0.104085E+09 | 0.113163E+10 |
March | 0.507438E+09 | 0.00 | 0.507438E+09 | 0.286301E+09 | 0.984186E+09 |
April | 0.623014E+09 | 5333940.93 | 0.617681E+09 | 0.478356E+09 | 0.630011E+09 |
May | 0.699796E+09 | 45117755.73 | 0.654678E+09 | 0.713892E+09 | 0.458059E+09 |
June | 0.769506E+09 | 0.125927E+09 | 0.643579E+09 | 0.109083E+10 | 0.288920E+09 |
July | 0.729829E+09 | 60743208.74 | 0.669086E+09 | 0.112478E+10 | 0.199351E+09 |
August | 0.677038E+09 | 15157315.94 | 0.661881E+09 | 0.942717E+09 | 0.233896E+09 |
September | 0.523956E+09 | 134472.84 | 0.523822E+09 | 0.618440E+09 | 0.403280E+09 |
October | 0.404009E+09 | 0.00 | 0.404009E+09 | 0.273688E+09 | 0.766635E+09 |
November | 0.332032E+09 | 0.00 | 0.332032E+09 | 71357625.05 | 0.109277E+10 |
December | 0.273965E+09 | 0.00 | 0.273965E+09 | 7868591.66 | 0.150459E+10 |
Annual Sum or Average | 0.622582E+10 | 0.252414E+09 | 0.597340E+10 | 0.575697E+10 | 0.907890E+10 |
Minimum of Months | 0.273965E+09 | 0.00 | 0.273965E+09 | 7868591.66 | 0.199351E+09 |
Maximum of Months | 0.769506E+09 | 0.125927E+09 | 0.669086E+09 | 0.112478E+10 | 0.150459E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.321871E+09 | 0.00 | 0.321871E+09 | 44652949.07 | 0.138557E+10 |
February | 0.363355E+09 | 0.00 | 0.363355E+09 | 0.104082E+09 | 0.113163E+10 |
March | 0.507432E+09 | 0.00 | 0.507432E+09 | 0.286294E+09 | 0.984185E+09 |
April | 0.623007E+09 | 5333823.67 | 0.617673E+09 | 0.478348E+09 | 0.630010E+09 |
May | 0.699787E+09 | 45116763.87 | 0.654671E+09 | 0.713882E+09 | 0.458057E+09 |
June | 0.769496E+09 | 0.125925E+09 | 0.643572E+09 | 0.109082E+10 | 0.288918E+09 |
July | 0.729820E+09 | 60741873.38 | 0.669078E+09 | 0.112477E+10 | 0.199349E+09 |
August | 0.677030E+09 | 15156982.73 | 0.661873E+09 | 0.942707E+09 | 0.233894E+09 |
September | 0.523950E+09 | 134469.88 | 0.523815E+09 | 0.618433E+09 | 0.403278E+09 |
October | 0.404004E+09 | 0.00 | 0.404004E+09 | 0.273685E+09 | 0.766634E+09 |
November | 0.332027E+09 | 0.00 | 0.332027E+09 | 71354852.90 | 0.109277E+10 |
December | 0.273961E+09 | 0.00 | 0.273961E+09 | 7867868.29 | 0.150459E+10 |
Annual Sum or Average | 0.622574E+10 | 0.252408E+09 | 0.597333E+10 | 0.575689E+10 | 0.907889E+10 |
Minimum of Months | 0.273961E+09 | 0.00 | 0.273961E+09 | 7867868.29 | 0.199349E+09 |
Maximum of Months | 0.769496E+09 | 0.125925E+09 | 0.669078E+09 | 0.112477E+10 | 0.150459E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.321873E+09 | 0.00 | 0.321873E+09 | 44653701.15 | 0.138557E+10 |
February | 0.363356E+09 | 0.00 | 0.363356E+09 | 0.104083E+09 | 0.113163E+10 |
March | 0.507434E+09 | 0.00 | 0.507434E+09 | 0.286297E+09 | 0.984185E+09 |
April | 0.623010E+09 | 5333862.76 | 0.617676E+09 | 0.478351E+09 | 0.630010E+09 |
May | 0.699790E+09 | 45117094.49 | 0.654673E+09 | 0.713886E+09 | 0.458058E+09 |
June | 0.769499E+09 | 0.125925E+09 | 0.643574E+09 | 0.109082E+10 | 0.288919E+09 |
July | 0.729823E+09 | 60742318.50 | 0.669081E+09 | 0.112478E+10 | 0.199350E+09 |
August | 0.677033E+09 | 15157093.80 | 0.661876E+09 | 0.942710E+09 | 0.233895E+09 |
September | 0.523952E+09 | 134470.87 | 0.523817E+09 | 0.618435E+09 | 0.403279E+09 |
October | 0.404006E+09 | 0.00 | 0.404006E+09 | 0.273686E+09 | 0.766634E+09 |
November | 0.332029E+09 | 0.00 | 0.332029E+09 | 71355776.95 | 0.109277E+10 |
December | 0.273963E+09 | 0.00 | 0.273963E+09 | 7868109.41 | 0.150459E+10 |
Annual Sum or Average | 0.622577E+10 | 0.252410E+09 | 0.597336E+10 | 0.575692E+10 | 0.907889E+10 |
Minimum of Months | 0.273963E+09 | 0.00 | 0.273963E+09 | 7868109.41 | 0.199350E+09 |
Maximum of Months | 0.769499E+09 | 0.125925E+09 | 0.669081E+09 | 0.112478E+10 | 0.150459E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.321871E+09 | 0.00 | 0.321871E+09 | 44652949.07 | 0.138557E+10 |
February | 0.363355E+09 | 0.00 | 0.363355E+09 | 0.104082E+09 | 0.113163E+10 |
March | 0.507432E+09 | 0.00 | 0.507432E+09 | 0.286294E+09 | 0.984185E+09 |
April | 0.623007E+09 | 5333823.67 | 0.617673E+09 | 0.478348E+09 | 0.630010E+09 |
May | 0.699787E+09 | 45116763.87 | 0.654671E+09 | 0.713882E+09 | 0.458057E+09 |
June | 0.769496E+09 | 0.125925E+09 | 0.643572E+09 | 0.109082E+10 | 0.288918E+09 |
July | 0.729820E+09 | 60741873.38 | 0.669078E+09 | 0.112477E+10 | 0.199349E+09 |
August | 0.677030E+09 | 15156982.73 | 0.661873E+09 | 0.942707E+09 | 0.233894E+09 |
September | 0.523950E+09 | 134469.88 | 0.523815E+09 | 0.618433E+09 | 0.403278E+09 |
October | 0.404004E+09 | 0.00 | 0.404004E+09 | 0.273685E+09 | 0.766634E+09 |
November | 0.332027E+09 | 0.00 | 0.332027E+09 | 71354852.90 | 0.109277E+10 |
December | 0.273961E+09 | 0.00 | 0.273961E+09 | 7867868.29 | 0.150459E+10 |
Annual Sum or Average | 0.622574E+10 | 0.252408E+09 | 0.597333E+10 | 0.575689E+10 | 0.907889E+10 |
Minimum of Months | 0.273961E+09 | 0.00 | 0.273961E+09 | 7867868.29 | 0.199349E+09 |
Maximum of Months | 0.769496E+09 | 0.125925E+09 | 0.669078E+09 | 0.112477E+10 | 0.150459E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.321859E+09 | 0.00 | 0.321859E+09 | 44651525.38 | 0.138552E+10 |
February | 0.363341E+09 | 0.00 | 0.363341E+09 | 0.104078E+09 | 0.113158E+10 |
March | 0.507413E+09 | 0.00 | 0.507413E+09 | 0.286284E+09 | 0.984146E+09 |
April | 0.622983E+09 | 5333628.24 | 0.617650E+09 | 0.478330E+09 | 0.629985E+09 |
May | 0.699761E+09 | 45115110.77 | 0.654645E+09 | 0.713855E+09 | 0.458039E+09 |
June | 0.769467E+09 | 0.125920E+09 | 0.643547E+09 | 0.109077E+10 | 0.288907E+09 |
July | 0.729792E+09 | 60739647.76 | 0.669053E+09 | 0.112473E+10 | 0.199341E+09 |
August | 0.677004E+09 | 15156427.37 | 0.661848E+09 | 0.942670E+09 | 0.233885E+09 |
September | 0.523930E+09 | 134464.96 | 0.523795E+09 | 0.618409E+09 | 0.403262E+09 |
October | 0.403989E+09 | 0.00 | 0.403989E+09 | 0.273674E+09 | 0.766603E+09 |
November | 0.332015E+09 | 0.00 | 0.332015E+09 | 71352438.99 | 0.109273E+10 |
December | 0.273951E+09 | 0.00 | 0.273951E+09 | 7867671.73 | 0.150453E+10 |
Annual Sum or Average | 0.622550E+10 | 0.252399E+09 | 0.597310E+10 | 0.575667E+10 | 0.907852E+10 |
Minimum of Months | 0.273951E+09 | 0.00 | 0.273951E+09 | 7867671.73 | 0.199341E+09 |
Maximum of Months | 0.769467E+09 | 0.125920E+09 | 0.669053E+09 | 0.112473E+10 | 0.150453E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.990453E+09 | 0.553757E+09 | 0.436696E+09 | 0.813539E+09 | 0.139187E+10 |
February | 0.108692E+10 | 0.585969E+09 | 0.500955E+09 | 0.994732E+09 | 0.114329E+10 |
March | 0.158744E+10 | 0.902431E+09 | 0.685010E+09 | 0.167912E+10 | 0.995143E+09 |
April | 0.209881E+10 | 0.119568E+10 | 0.903127E+09 | 0.247928E+10 | 0.650483E+09 |
May | 0.206946E+10 | 0.117937E+10 | 0.890094E+09 | 0.260000E+10 | 0.515722E+09 |
June | 0.215907E+10 | 0.133009E+10 | 0.828980E+09 | 0.301005E+10 | 0.311671E+09 |
July | 0.206442E+10 | 0.118052E+10 | 0.883902E+09 | 0.301118E+10 | 0.209422E+09 |
August | 0.204288E+10 | 0.112628E+10 | 0.916604E+09 | 0.288507E+10 | 0.235825E+09 |
September | 0.164551E+10 | 0.920676E+09 | 0.724832E+09 | 0.218279E+10 | 0.426065E+09 |
October | 0.147879E+10 | 0.938234E+09 | 0.540555E+09 | 0.170164E+10 | 0.776753E+09 |
November | 0.111847E+10 | 0.657538E+09 | 0.460928E+09 | 0.105808E+10 | 0.109910E+10 |
December | 0.936483E+09 | 0.569936E+09 | 0.366548E+09 | 0.782295E+09 | 0.148625E+10 |
Annual Sum or Average | 0.192787E+11 | 0.111405E+11 | 0.813823E+10 | 0.231978E+11 | 0.924160E+10 |
Minimum of Months | 0.936483E+09 | 0.553757E+09 | 0.366548E+09 | 0.782295E+09 | 0.209422E+09 |
Maximum of Months | 0.215907E+10 | 0.133009E+10 | 0.916604E+09 | 0.301118E+10 | 0.148625E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.990453E+09 | 0.553757E+09 | 0.436696E+09 | 0.813539E+09 | 0.139187E+10 |
February | 0.108692E+10 | 0.585969E+09 | 0.500955E+09 | 0.994732E+09 | 0.114329E+10 |
March | 0.158744E+10 | 0.902431E+09 | 0.685010E+09 | 0.167912E+10 | 0.995143E+09 |
April | 0.209881E+10 | 0.119568E+10 | 0.903127E+09 | 0.247928E+10 | 0.650483E+09 |
May | 0.206946E+10 | 0.117937E+10 | 0.890094E+09 | 0.260000E+10 | 0.515722E+09 |
June | 0.215907E+10 | 0.133009E+10 | 0.828980E+09 | 0.301005E+10 | 0.311671E+09 |
July | 0.206442E+10 | 0.118052E+10 | 0.883902E+09 | 0.301118E+10 | 0.209422E+09 |
August | 0.204288E+10 | 0.112628E+10 | 0.916604E+09 | 0.288507E+10 | 0.235825E+09 |
September | 0.164551E+10 | 0.920676E+09 | 0.724832E+09 | 0.218279E+10 | 0.426065E+09 |
October | 0.147879E+10 | 0.938234E+09 | 0.540555E+09 | 0.170164E+10 | 0.776753E+09 |
November | 0.111847E+10 | 0.657538E+09 | 0.460928E+09 | 0.105808E+10 | 0.109910E+10 |
December | 0.936483E+09 | 0.569936E+09 | 0.366548E+09 | 0.782295E+09 | 0.148625E+10 |
Annual Sum or Average | 0.192787E+11 | 0.111405E+11 | 0.813823E+10 | 0.231978E+11 | 0.924160E+10 |
Minimum of Months | 0.936483E+09 | 0.553757E+09 | 0.366548E+09 | 0.782295E+09 | 0.209422E+09 |
Maximum of Months | 0.215907E+10 | 0.133009E+10 | 0.916604E+09 | 0.301118E+10 | 0.148625E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.990434E+09 | 0.553747E+09 | 0.436688E+09 | 0.813524E+09 | 0.139184E+10 |
February | 0.108690E+10 | 0.585958E+09 | 0.500946E+09 | 0.994714E+09 | 0.114327E+10 |
March | 0.158741E+10 | 0.902415E+09 | 0.684997E+09 | 0.167909E+10 | 0.995125E+09 |
April | 0.209877E+10 | 0.119566E+10 | 0.903111E+09 | 0.247923E+10 | 0.650471E+09 |
May | 0.206943E+10 | 0.117935E+10 | 0.890078E+09 | 0.259995E+10 | 0.515712E+09 |
June | 0.215903E+10 | 0.133007E+10 | 0.828965E+09 | 0.300999E+10 | 0.311665E+09 |
July | 0.206438E+10 | 0.118050E+10 | 0.883886E+09 | 0.301112E+10 | 0.209418E+09 |
August | 0.204285E+10 | 0.112626E+10 | 0.916587E+09 | 0.288501E+10 | 0.235820E+09 |
September | 0.164548E+10 | 0.920659E+09 | 0.724819E+09 | 0.218275E+10 | 0.426057E+09 |
October | 0.147876E+10 | 0.938217E+09 | 0.540545E+09 | 0.170161E+10 | 0.776739E+09 |
November | 0.111845E+10 | 0.657526E+09 | 0.460919E+09 | 0.105806E+10 | 0.109908E+10 |
December | 0.936466E+09 | 0.569926E+09 | 0.366541E+09 | 0.782281E+09 | 0.148623E+10 |
Annual Sum or Average | 0.192784E+11 | 0.111403E+11 | 0.813808E+10 | 0.231973E+11 | 0.924143E+10 |
Minimum of Months | 0.936466E+09 | 0.553747E+09 | 0.366541E+09 | 0.782281E+09 | 0.209418E+09 |
Maximum of Months | 0.215903E+10 | 0.133007E+10 | 0.916587E+09 | 0.301112E+10 | 0.148623E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.237958E+10 | 0.185164E+10 | 0.527943E+09 | 0.272081E+10 | 0.122983E+10 |
February | 0.210339E+10 | 0.153645E+10 | 0.566938E+09 | 0.246023E+10 | 0.103361E+10 |
March | 0.171605E+10 | 0.103745E+10 | 0.678598E+09 | 0.204889E+10 | 0.939188E+09 |
April | 0.129513E+10 | 0.531625E+09 | 0.763509E+09 | 0.160753E+10 | 0.652532E+09 |
May | 0.892543E+09 | 0.196341E+09 | 0.696202E+09 | 0.111900E+10 | 0.489051E+09 |
June | 0.730663E+09 | 90045041.91 | 0.640618E+09 | 0.109166E+10 | 0.308762E+09 |
July | 0.835464E+09 | 0.133414E+09 | 0.702050E+09 | 0.135531E+10 | 0.209843E+09 |
August | 0.114882E+10 | 0.373422E+09 | 0.775399E+09 | 0.177552E+10 | 0.250929E+09 |
September | 0.153732E+10 | 0.857252E+09 | 0.680071E+09 | 0.220322E+10 | 0.417772E+09 |
October | 0.217335E+10 | 0.160065E+10 | 0.572693E+09 | 0.279001E+10 | 0.725776E+09 |
November | 0.234261E+10 | 0.179794E+10 | 0.544666E+09 | 0.276547E+10 | 0.981128E+09 |
December | 0.258178E+10 | 0.212969E+10 | 0.452085E+09 | 0.297172E+10 | 0.128508E+10 |
Annual Sum or Average | 0.197367E+11 | 0.121359E+11 | 0.760077E+10 | 0.249094E+11 | 0.852350E+10 |
Minimum of Months | 0.730663E+09 | 90045041.91 | 0.452085E+09 | 0.109166E+10 | 0.209843E+09 |
Maximum of Months | 0.258178E+10 | 0.212969E+10 | 0.775399E+09 | 0.297172E+10 | 0.128508E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.237957E+10 | 0.185163E+10 | 0.527940E+09 | 0.272079E+10 | 0.122983E+10 |
February | 0.210337E+10 | 0.153644E+10 | 0.566935E+09 | 0.246021E+10 | 0.103361E+10 |
March | 0.171604E+10 | 0.103745E+10 | 0.678594E+09 | 0.204887E+10 | 0.939188E+09 |
April | 0.129513E+10 | 0.531621E+09 | 0.763506E+09 | 0.160752E+10 | 0.652532E+09 |
May | 0.892539E+09 | 0.196339E+09 | 0.696200E+09 | 0.111899E+10 | 0.489050E+09 |
June | 0.730660E+09 | 90044382.05 | 0.640616E+09 | 0.109165E+10 | 0.308762E+09 |
July | 0.835461E+09 | 0.133413E+09 | 0.702047E+09 | 0.135531E+10 | 0.209842E+09 |
August | 0.114882E+10 | 0.373420E+09 | 0.775396E+09 | 0.177551E+10 | 0.250929E+09 |
September | 0.153731E+10 | 0.857246E+09 | 0.680068E+09 | 0.220321E+10 | 0.417771E+09 |
October | 0.217333E+10 | 0.160064E+10 | 0.572690E+09 | 0.278998E+10 | 0.725775E+09 |
November | 0.234259E+10 | 0.179793E+10 | 0.544664E+09 | 0.276545E+10 | 0.981127E+09 |
December | 0.258176E+10 | 0.212968E+10 | 0.452082E+09 | 0.297170E+10 | 0.128507E+10 |
Annual Sum or Average | 0.197366E+11 | 0.121358E+11 | 0.760074E+10 | 0.249092E+11 | 0.852349E+10 |
Minimum of Months | 0.730660E+09 | 90044382.05 | 0.452082E+09 | 0.109165E+10 | 0.209842E+09 |
Maximum of Months | 0.258176E+10 | 0.212968E+10 | 0.775396E+09 | 0.297170E+10 | 0.128507E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.237958E+10 | 0.185164E+10 | 0.527943E+09 | 0.272081E+10 | 0.122983E+10 |
February | 0.210339E+10 | 0.153645E+10 | 0.566938E+09 | 0.246023E+10 | 0.103361E+10 |
March | 0.171605E+10 | 0.103745E+10 | 0.678598E+09 | 0.204889E+10 | 0.939188E+09 |
April | 0.129513E+10 | 0.531625E+09 | 0.763509E+09 | 0.160753E+10 | 0.652532E+09 |
May | 0.892543E+09 | 0.196341E+09 | 0.696202E+09 | 0.111900E+10 | 0.489051E+09 |
June | 0.730663E+09 | 90045041.91 | 0.640618E+09 | 0.109166E+10 | 0.308762E+09 |
July | 0.835464E+09 | 0.133414E+09 | 0.702050E+09 | 0.135531E+10 | 0.209843E+09 |
August | 0.114882E+10 | 0.373422E+09 | 0.775399E+09 | 0.177552E+10 | 0.250929E+09 |
September | 0.153732E+10 | 0.857252E+09 | 0.680071E+09 | 0.220322E+10 | 0.417772E+09 |
October | 0.217335E+10 | 0.160065E+10 | 0.572693E+09 | 0.279001E+10 | 0.725776E+09 |
November | 0.234261E+10 | 0.179794E+10 | 0.544666E+09 | 0.276547E+10 | 0.981128E+09 |
December | 0.258178E+10 | 0.212969E+10 | 0.452085E+09 | 0.297172E+10 | 0.128508E+10 |
Annual Sum or Average | 0.197367E+11 | 0.121359E+11 | 0.760077E+10 | 0.249094E+11 | 0.852350E+10 |
Minimum of Months | 0.730663E+09 | 90045041.91 | 0.452085E+09 | 0.109166E+10 | 0.209843E+09 |
Maximum of Months | 0.258178E+10 | 0.212969E+10 | 0.775399E+09 | 0.297172E+10 | 0.128508E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.237957E+10 | 0.185163E+10 | 0.527940E+09 | 0.272079E+10 | 0.122983E+10 |
February | 0.210337E+10 | 0.153644E+10 | 0.566935E+09 | 0.246021E+10 | 0.103361E+10 |
March | 0.171604E+10 | 0.103745E+10 | 0.678594E+09 | 0.204887E+10 | 0.939188E+09 |
April | 0.129513E+10 | 0.531621E+09 | 0.763506E+09 | 0.160752E+10 | 0.652532E+09 |
May | 0.892539E+09 | 0.196339E+09 | 0.696200E+09 | 0.111899E+10 | 0.489050E+09 |
June | 0.730660E+09 | 90044382.05 | 0.640616E+09 | 0.109165E+10 | 0.308762E+09 |
July | 0.835461E+09 | 0.133413E+09 | 0.702047E+09 | 0.135531E+10 | 0.209842E+09 |
August | 0.114882E+10 | 0.373420E+09 | 0.775396E+09 | 0.177551E+10 | 0.250929E+09 |
September | 0.153731E+10 | 0.857246E+09 | 0.680068E+09 | 0.220321E+10 | 0.417771E+09 |
October | 0.217333E+10 | 0.160064E+10 | 0.572690E+09 | 0.278998E+10 | 0.725775E+09 |
November | 0.234259E+10 | 0.179793E+10 | 0.544664E+09 | 0.276545E+10 | 0.981127E+09 |
December | 0.258176E+10 | 0.212968E+10 | 0.452082E+09 | 0.297170E+10 | 0.128507E+10 |
Annual Sum or Average | 0.197366E+11 | 0.121358E+11 | 0.760074E+10 | 0.249092E+11 | 0.852349E+10 |
Minimum of Months | 0.730660E+09 | 90044382.05 | 0.452082E+09 | 0.109165E+10 | 0.209842E+09 |
Maximum of Months | 0.258176E+10 | 0.212968E+10 | 0.775396E+09 | 0.297170E+10 | 0.128507E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.237948E+10 | 0.185156E+10 | 0.527920E+09 | 0.272069E+10 | 0.122978E+10 |
February | 0.210329E+10 | 0.153638E+10 | 0.566914E+09 | 0.246012E+10 | 0.103356E+10 |
March | 0.171598E+10 | 0.103741E+10 | 0.678569E+09 | 0.204880E+10 | 0.939150E+09 |
April | 0.129508E+10 | 0.531602E+09 | 0.763477E+09 | 0.160746E+10 | 0.652506E+09 |
May | 0.892505E+09 | 0.196332E+09 | 0.696173E+09 | 0.111895E+10 | 0.489031E+09 |
June | 0.730632E+09 | 90041082.78 | 0.640591E+09 | 0.109161E+10 | 0.308749E+09 |
July | 0.835429E+09 | 0.133408E+09 | 0.702020E+09 | 0.135526E+10 | 0.209834E+09 |
August | 0.114877E+10 | 0.373406E+09 | 0.775366E+09 | 0.177545E+10 | 0.250919E+09 |
September | 0.153726E+10 | 0.857215E+09 | 0.680042E+09 | 0.220312E+10 | 0.417755E+09 |
October | 0.217325E+10 | 0.160058E+10 | 0.572668E+09 | 0.278988E+10 | 0.725746E+09 |
November | 0.234250E+10 | 0.179786E+10 | 0.544643E+09 | 0.276535E+10 | 0.981088E+09 |
December | 0.258167E+10 | 0.212960E+10 | 0.452065E+09 | 0.297159E+10 | 0.128502E+10 |
Annual Sum or Average | 0.197358E+11 | 0.121354E+11 | 0.760045E+10 | 0.249083E+11 | 0.852315E+10 |
Minimum of Months | 0.730632E+09 | 90041082.78 | 0.452065E+09 | 0.109161E+10 | 0.209834E+09 |
Maximum of Months | 0.258167E+10 | 0.212960E+10 | 0.775366E+09 | 0.297159E+10 | 0.128502E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.102161E+10 | 0.582595E+09 | 0.439020E+09 | 0.934137E+09 | 0.155190E+10 |
February | 0.118789E+10 | 0.686207E+09 | 0.501680E+09 | 0.117041E+10 | 0.131033E+10 |
March | 0.146888E+10 | 0.781916E+09 | 0.686968E+09 | 0.153917E+10 | 0.118053E+10 |
April | 0.181426E+10 | 0.965559E+09 | 0.848703E+09 | 0.206793E+10 | 0.813547E+09 |
May | 0.177752E+10 | 0.915905E+09 | 0.861619E+09 | 0.219468E+10 | 0.586835E+09 |
June | 0.184403E+10 | 0.102895E+10 | 0.815082E+09 | 0.257365E+10 | 0.399854E+09 |
July | 0.171870E+10 | 0.841111E+09 | 0.877592E+09 | 0.250383E+10 | 0.285707E+09 |
August | 0.175621E+10 | 0.812319E+09 | 0.943891E+09 | 0.244893E+10 | 0.359147E+09 |
September | 0.153510E+10 | 0.808475E+09 | 0.726624E+09 | 0.204424E+10 | 0.500914E+09 |
October | 0.145122E+10 | 0.901987E+09 | 0.549234E+09 | 0.169992E+10 | 0.922609E+09 |
November | 0.110245E+10 | 0.648599E+09 | 0.453856E+09 | 0.106273E+10 | 0.127945E+10 |
December | 0.985179E+09 | 0.617812E+09 | 0.367366E+09 | 0.869559E+09 | 0.174546E+10 |
Annual Sum or Average | 0.176631E+11 | 0.959144E+10 | 0.807163E+10 | 0.211092E+11 | 0.109363E+11 |
Minimum of Months | 0.985179E+09 | 0.582595E+09 | 0.367366E+09 | 0.869559E+09 | 0.285707E+09 |
Maximum of Months | 0.184403E+10 | 0.102895E+10 | 0.943891E+09 | 0.257365E+10 | 0.174546E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.102161E+10 | 0.582595E+09 | 0.439020E+09 | 0.934137E+09 | 0.155190E+10 |
February | 0.118789E+10 | 0.686207E+09 | 0.501680E+09 | 0.117041E+10 | 0.131033E+10 |
March | 0.146888E+10 | 0.781916E+09 | 0.686968E+09 | 0.153917E+10 | 0.118053E+10 |
April | 0.181426E+10 | 0.965559E+09 | 0.848703E+09 | 0.206793E+10 | 0.813547E+09 |
May | 0.177752E+10 | 0.915905E+09 | 0.861619E+09 | 0.219468E+10 | 0.586835E+09 |
June | 0.184403E+10 | 0.102895E+10 | 0.815082E+09 | 0.257365E+10 | 0.399854E+09 |
July | 0.171870E+10 | 0.841111E+09 | 0.877592E+09 | 0.250383E+10 | 0.285707E+09 |
August | 0.175621E+10 | 0.812319E+09 | 0.943891E+09 | 0.244893E+10 | 0.359147E+09 |
September | 0.153510E+10 | 0.808475E+09 | 0.726624E+09 | 0.204424E+10 | 0.500914E+09 |
October | 0.145122E+10 | 0.901987E+09 | 0.549234E+09 | 0.169992E+10 | 0.922609E+09 |
November | 0.110245E+10 | 0.648599E+09 | 0.453856E+09 | 0.106273E+10 | 0.127945E+10 |
December | 0.985179E+09 | 0.617812E+09 | 0.367366E+09 | 0.869559E+09 | 0.174546E+10 |
Annual Sum or Average | 0.176631E+11 | 0.959144E+10 | 0.807163E+10 | 0.211092E+11 | 0.109363E+11 |
Minimum of Months | 0.985179E+09 | 0.582595E+09 | 0.367366E+09 | 0.869559E+09 | 0.285707E+09 |
Maximum of Months | 0.184403E+10 | 0.102895E+10 | 0.943891E+09 | 0.257365E+10 | 0.174546E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.102160E+10 | 0.582584E+09 | 0.439012E+09 | 0.934120E+09 | 0.155188E+10 |
February | 0.118787E+10 | 0.686194E+09 | 0.501671E+09 | 0.117039E+10 | 0.131030E+10 |
March | 0.146886E+10 | 0.781902E+09 | 0.686956E+09 | 0.153914E+10 | 0.118051E+10 |
April | 0.181423E+10 | 0.965541E+09 | 0.848687E+09 | 0.206789E+10 | 0.813532E+09 |
May | 0.177749E+10 | 0.915888E+09 | 0.861603E+09 | 0.219464E+10 | 0.586824E+09 |
June | 0.184400E+10 | 0.102893E+10 | 0.815067E+09 | 0.257361E+10 | 0.399846E+09 |
July | 0.171867E+10 | 0.841095E+09 | 0.877576E+09 | 0.250378E+10 | 0.285702E+09 |
August | 0.175618E+10 | 0.812304E+09 | 0.943873E+09 | 0.244889E+10 | 0.359140E+09 |
September | 0.153507E+10 | 0.808460E+09 | 0.726611E+09 | 0.204420E+10 | 0.500904E+09 |
October | 0.145120E+10 | 0.901971E+09 | 0.549224E+09 | 0.169989E+10 | 0.922592E+09 |
November | 0.110243E+10 | 0.648587E+09 | 0.453848E+09 | 0.106271E+10 | 0.127942E+10 |
December | 0.985161E+09 | 0.617801E+09 | 0.367360E+09 | 0.869543E+09 | 0.174543E+10 |
Annual Sum or Average | 0.176627E+11 | 0.959126E+10 | 0.807149E+10 | 0.211088E+11 | 0.109361E+11 |
Minimum of Months | 0.985161E+09 | 0.582584E+09 | 0.367360E+09 | 0.869543E+09 | 0.285702E+09 |
Maximum of Months | 0.184400E+10 | 0.102893E+10 | 0.943873E+09 | 0.257361E+10 | 0.174543E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.160938E+10 | 0.00 | 0.160938E+10 | 0.350217E+09 | 0.625971E+10 |
February | 0.181679E+10 | 0.00 | 0.181679E+10 | 0.671540E+09 | 0.511751E+10 |
March | 0.253719E+10 | 0.00 | 0.253719E+10 | 0.159349E+10 | 0.447966E+10 |
April | 0.311507E+10 | 26669874.63 | 0.308840E+10 | 0.251037E+10 | 0.290289E+10 |
May | 0.349897E+10 | 0.225590E+09 | 0.327338E+10 | 0.362360E+10 | 0.218941E+10 |
June | 0.384753E+10 | 0.629640E+09 | 0.321789E+10 | 0.548952E+10 | 0.141238E+10 |
July | 0.364914E+10 | 0.303718E+09 | 0.334542E+10 | 0.566230E+10 | 0.990741E+09 |
August | 0.338519E+10 | 75787062.69 | 0.330940E+10 | 0.478592E+10 | 0.111700E+10 |
September | 0.261977E+10 | 672368.48 | 0.261910E+10 | 0.313294E+10 | 0.192600E+10 |
October | 0.202004E+10 | 0.00 | 0.202004E+10 | 0.147136E+10 | 0.351054E+10 |
November | 0.166015E+10 | 0.00 | 0.166015E+10 | 0.484807E+09 | 0.483032E+10 |
December | 0.136982E+10 | 0.00 | 0.136982E+10 | 0.106301E+09 | 0.657647E+10 |
Annual Sum or Average | 0.311290E+11 | 0.126208E+10 | 0.298670E+11 | 0.298824E+11 | 0.413126E+11 |
Minimum of Months | 0.136982E+10 | 0.00 | 0.136982E+10 | 0.106301E+09 | 0.990741E+09 |
Maximum of Months | 0.384753E+10 | 0.629640E+09 | 0.334542E+10 | 0.566230E+10 | 0.657647E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.297133E+10 | 0.166125E+10 | 0.131007E+10 | 0.253016E+10 | 0.386048E+10 |
February | 0.326074E+10 | 0.175789E+10 | 0.150285E+10 | 0.305369E+10 | 0.319255E+10 |
March | 0.476227E+10 | 0.270727E+10 | 0.205501E+10 | 0.506213E+10 | 0.282902E+10 |
April | 0.629636E+10 | 0.358700E+10 | 0.270935E+10 | 0.740874E+10 | 0.191646E+10 |
May | 0.620833E+10 | 0.353808E+10 | 0.267025E+10 | 0.776050E+10 | 0.151478E+10 |
June | 0.647715E+10 | 0.399023E+10 | 0.248692E+10 | 0.898709E+10 | 0.947475E+09 |
July | 0.619320E+10 | 0.354153E+10 | 0.265168E+10 | 0.898504E+10 | 0.680395E+09 |
August | 0.612859E+10 | 0.337881E+10 | 0.274978E+10 | 0.860692E+10 | 0.763289E+09 |
September | 0.493647E+10 | 0.276200E+10 | 0.217447E+10 | 0.652382E+10 | 0.125526E+10 |
October | 0.443632E+10 | 0.281467E+10 | 0.162165E+10 | 0.511231E+10 | 0.222420E+10 |
November | 0.335536E+10 | 0.197259E+10 | 0.138277E+10 | 0.322565E+10 | 0.305092E+10 |
December | 0.280942E+10 | 0.170979E+10 | 0.109963E+10 | 0.241497E+10 | 0.407522E+10 |
Annual Sum or Average | 0.578356E+11 | 0.334211E+11 | 0.244144E+11 | 0.696710E+11 | 0.263101E+11 |
Minimum of Months | 0.280942E+10 | 0.166125E+10 | 0.109963E+10 | 0.241497E+10 | 0.680395E+09 |
Maximum of Months | 0.647715E+10 | 0.399023E+10 | 0.274978E+10 | 0.898709E+10 | 0.407522E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.118982E+11 | 0.925840E+10 | 0.263975E+10 | 0.135481E+11 | 0.603029E+10 |
February | 0.105171E+11 | 0.768240E+10 | 0.283472E+10 | 0.122487E+11 | 0.504796E+10 |
March | 0.858041E+10 | 0.518738E+10 | 0.339302E+10 | 0.102112E+11 | 0.455382E+10 |
April | 0.647576E+10 | 0.265818E+10 | 0.381758E+10 | 0.802794E+10 | 0.314649E+10 |
May | 0.446276E+10 | 0.981725E+09 | 0.348103E+10 | 0.558905E+10 | 0.237984E+10 |
June | 0.365334E+10 | 0.450235E+09 | 0.320310E+10 | 0.548804E+10 | 0.151170E+10 |
July | 0.417736E+10 | 0.667085E+09 | 0.351027E+10 | 0.679477E+10 | 0.105184E+10 |
August | 0.574418E+10 | 0.186715E+10 | 0.387703E+10 | 0.888885E+10 | 0.122920E+10 |
September | 0.768674E+10 | 0.428635E+10 | 0.340039E+10 | 0.109559E+11 | 0.206347E+10 |
October | 0.108669E+11 | 0.800344E+10 | 0.286349E+10 | 0.138774E+11 | 0.356829E+10 |
November | 0.117133E+11 | 0.898989E+10 | 0.272337E+10 | 0.137769E+11 | 0.477627E+10 |
December | 0.129091E+11 | 0.106487E+11 | 0.226045E+10 | 0.148295E+11 | 0.618992E+10 |
Annual Sum or Average | 0.986851E+11 | 0.606809E+11 | 0.380042E+11 | 0.124236E+12 | 0.415491E+11 |
Minimum of Months | 0.365334E+10 | 0.450235E+09 | 0.226045E+10 | 0.548804E+10 | 0.105184E+10 |
Maximum of Months | 0.129091E+11 | 0.106487E+11 | 0.387703E+10 | 0.148295E+11 | 0.618992E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.306481E+10 | 0.174777E+10 | 0.131705E+10 | 0.290256E+10 | 0.421163E+10 |
February | 0.356362E+10 | 0.205860E+10 | 0.150502E+10 | 0.362580E+10 | 0.349543E+10 |
March | 0.440661E+10 | 0.234573E+10 | 0.206088E+10 | 0.475427E+10 | 0.311074E+10 |
April | 0.544273E+10 | 0.289665E+10 | 0.254608E+10 | 0.633275E+10 | 0.213389E+10 |
May | 0.533252E+10 | 0.274769E+10 | 0.258483E+10 | 0.661515E+10 | 0.164554E+10 |
June | 0.553204E+10 | 0.308682E+10 | 0.244522E+10 | 0.777110E+10 | 0.111352E+10 |
July | 0.515606E+10 | 0.252331E+10 | 0.263275E+10 | 0.758528E+10 | 0.773276E+09 |
August | 0.526857E+10 | 0.243693E+10 | 0.283164E+10 | 0.747966E+10 | 0.887761E+09 |
September | 0.460525E+10 | 0.242540E+10 | 0.217985E+10 | 0.615955E+10 | 0.140158E+10 |
October | 0.435362E+10 | 0.270593E+10 | 0.164769E+10 | 0.518004E+10 | 0.247766E+10 |
November | 0.330733E+10 | 0.194578E+10 | 0.136155E+10 | 0.331888E+10 | 0.328484E+10 |
December | 0.295551E+10 | 0.185342E+10 | 0.110209E+10 | 0.274111E+10 | 0.435688E+10 |
Annual Sum or Average | 0.529887E+11 | 0.287740E+11 | 0.242147E+11 | 0.644662E+11 | 0.288928E+11 |
Minimum of Months | 0.295551E+10 | 0.174777E+10 | 0.110209E+10 | 0.274111E+10 | 0.773276E+09 |
Maximum of Months | 0.553204E+10 | 0.308682E+10 | 0.283164E+10 | 0.777110E+10 | 0.435688E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.160938E+10 | 0.00 | 0.160938E+10 | 0.438132E+09 | 0.578629E+10 |
February | 0.181679E+10 | 0.00 | 0.181679E+10 | 0.763707E+09 | 0.474756E+10 |
March | 0.253719E+10 | 0.00 | 0.253719E+10 | 0.170265E+10 | 0.416744E+10 |
April | 0.311507E+10 | 26669874.63 | 0.308840E+10 | 0.256630E+10 | 0.274840E+10 |
May | 0.349897E+10 | 0.225590E+09 | 0.327338E+10 | 0.363753E+10 | 0.212693E+10 |
June | 0.384753E+10 | 0.629640E+09 | 0.321789E+10 | 0.545455E+10 | 0.141008E+10 |
July | 0.364914E+10 | 0.303718E+09 | 0.334542E+10 | 0.560376E+10 | 0.101159E+10 |
August | 0.338519E+10 | 75787062.69 | 0.330940E+10 | 0.473771E+10 | 0.113052E+10 |
September | 0.261977E+10 | 672368.48 | 0.261910E+10 | 0.312315E+10 | 0.188632E+10 |
October | 0.202004E+10 | 0.00 | 0.202004E+10 | 0.152880E+10 | 0.328138E+10 |
November | 0.166015E+10 | 0.00 | 0.166015E+10 | 0.585665E+09 | 0.439068E+10 |
December | 0.136982E+10 | 0.00 | 0.136982E+10 | 0.155069E+09 | 0.605029E+10 |
Annual Sum or Average | 0.311290E+11 | 0.126208E+10 | 0.298670E+11 | 0.302970E+11 | 0.387375E+11 |
Minimum of Months | 0.136982E+10 | 0.00 | 0.136982E+10 | 0.155069E+09 | 0.101159E+10 |
Maximum of Months | 0.384753E+10 | 0.629640E+09 | 0.334542E+10 | 0.560376E+10 | 0.605029E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.297133E+10 | 0.166125E+10 | 0.131007E+10 | 0.264234E+10 | 0.358141E+10 |
February | 0.326074E+10 | 0.175789E+10 | 0.150285E+10 | 0.314466E+10 | 0.297649E+10 |
March | 0.476227E+10 | 0.270727E+10 | 0.205501E+10 | 0.512766E+10 | 0.266703E+10 |
April | 0.629636E+10 | 0.358700E+10 | 0.270935E+10 | 0.742230E+10 | 0.184884E+10 |
May | 0.620833E+10 | 0.353808E+10 | 0.267025E+10 | 0.774482E+10 | 0.148608E+10 |
June | 0.647715E+10 | 0.399023E+10 | 0.248692E+10 | 0.895114E+10 | 0.950001E+09 |
July | 0.619320E+10 | 0.354153E+10 | 0.265168E+10 | 0.894048E+10 | 0.695675E+09 |
August | 0.612859E+10 | 0.337881E+10 | 0.274978E+10 | 0.856702E+10 | 0.776092E+09 |
September | 0.493647E+10 | 0.276200E+10 | 0.217447E+10 | 0.650755E+10 | 0.124241E+10 |
October | 0.443632E+10 | 0.281467E+10 | 0.162165E+10 | 0.514397E+10 | 0.211894E+10 |
November | 0.335536E+10 | 0.197259E+10 | 0.138277E+10 | 0.332281E+10 | 0.280741E+10 |
December | 0.280942E+10 | 0.170979E+10 | 0.109963E+10 | 0.250051E+10 | 0.375287E+10 |
Annual Sum or Average | 0.578356E+11 | 0.334211E+11 | 0.244144E+11 | 0.700152E+11 | 0.249033E+11 |
Minimum of Months | 0.280942E+10 | 0.166125E+10 | 0.109963E+10 | 0.250051E+10 | 0.695675E+09 |
Maximum of Months | 0.647715E+10 | 0.399023E+10 | 0.274978E+10 | 0.895114E+10 | 0.375287E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.118982E+11 | 0.925840E+10 | 0.263975E+10 | 0.136994E+11 | 0.560219E+10 |
February | 0.105171E+11 | 0.768240E+10 | 0.283472E+10 | 0.123571E+11 | 0.470706E+10 |
March | 0.858041E+10 | 0.518738E+10 | 0.339302E+10 | 0.102943E+11 | 0.429041E+10 |
April | 0.647576E+10 | 0.265818E+10 | 0.381758E+10 | 0.805360E+10 | 0.300497E+10 |
May | 0.446276E+10 | 0.981725E+09 | 0.348103E+10 | 0.558747E+10 | 0.230808E+10 |
June | 0.365334E+10 | 0.450235E+09 | 0.320310E+10 | 0.545377E+10 | 0.149931E+10 |
July | 0.417736E+10 | 0.667085E+09 | 0.351027E+10 | 0.673794E+10 | 0.106893E+10 |
August | 0.574418E+10 | 0.186715E+10 | 0.387703E+10 | 0.883467E+10 | 0.124232E+10 |
September | 0.768674E+10 | 0.428635E+10 | 0.340039E+10 | 0.109295E+11 | 0.203508E+10 |
October | 0.108669E+11 | 0.800344E+10 | 0.286349E+10 | 0.139196E+11 | 0.340517E+10 |
November | 0.117133E+11 | 0.898989E+10 | 0.272337E+10 | 0.139013E+11 | 0.443155E+10 |
December | 0.129091E+11 | 0.106487E+11 | 0.226045E+10 | 0.149526E+11 | 0.571650E+10 |
Annual Sum or Average | 0.986851E+11 | 0.606809E+11 | 0.380042E+11 | 0.124721E+12 | 0.393116E+11 |
Minimum of Months | 0.365334E+10 | 0.450235E+09 | 0.226045E+10 | 0.545377E+10 | 0.106893E+10 |
Maximum of Months | 0.129091E+11 | 0.106487E+11 | 0.387703E+10 | 0.149526E+11 | 0.571650E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.306481E+10 | 0.174777E+10 | 0.131705E+10 | 0.295746E+10 | 0.393589E+10 |
February | 0.356362E+10 | 0.205860E+10 | 0.150502E+10 | 0.367085E+10 | 0.328534E+10 |
March | 0.440661E+10 | 0.234573E+10 | 0.206088E+10 | 0.479974E+10 | 0.293929E+10 |
April | 0.544273E+10 | 0.289665E+10 | 0.254608E+10 | 0.634678E+10 | 0.204847E+10 |
May | 0.533252E+10 | 0.274769E+10 | 0.258483E+10 | 0.660918E+10 | 0.160357E+10 |
June | 0.553204E+10 | 0.308682E+10 | 0.244522E+10 | 0.774249E+10 | 0.110842E+10 |
July | 0.515606E+10 | 0.252331E+10 | 0.263275E+10 | 0.754522E+10 | 0.782041E+09 |
August | 0.526857E+10 | 0.243693E+10 | 0.283164E+10 | 0.744437E+10 | 0.895063E+09 |
September | 0.460525E+10 | 0.242540E+10 | 0.217985E+10 | 0.614624E+10 | 0.138168E+10 |
October | 0.435362E+10 | 0.270593E+10 | 0.164769E+10 | 0.519804E+10 | 0.235906E+10 |
November | 0.330733E+10 | 0.194578E+10 | 0.136155E+10 | 0.337221E+10 | 0.304361E+10 |
December | 0.295551E+10 | 0.185342E+10 | 0.110209E+10 | 0.277910E+10 | 0.405880E+10 |
Annual Sum or Average | 0.529887E+11 | 0.287740E+11 | 0.242147E+11 | 0.646117E+11 | 0.274412E+11 |
Minimum of Months | 0.295551E+10 | 0.174777E+10 | 0.110209E+10 | 0.277910E+10 | 0.782041E+09 |
Maximum of Months | 0.553204E+10 | 0.308682E+10 | 0.283164E+10 | 0.774249E+10 | 0.405880E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 83.36 | 2586.54 | 600.86 | 0.00 | 600.86 | 0.00 | 0.00 |
February | 215.12 | 2338.83 | 750.98 | 0.00 | 750.98 | 0.00 | 0.00 |
March | 534.45 | 1837.25 | 947.26 | 0.00 | 947.26 | 0.00 | 0.00 |
April | 922.74 | 1215.29 | 1201.78 | 10.29 | 1191.49 | 0.00 | 0.00 |
May | 1332.66 | 855.09 | 1306.35 | 84.22 | 1222.12 | 0.00 | 0.00 |
June | 2104.19 | 557.32 | 1484.36 | 242.91 | 1241.45 | 0.00 | 0.00 |
July | 2099.70 | 372.14 | 1362.41 | 113.39 | 1249.02 | 0.00 | 0.00 |
August | 1759.82 | 436.63 | 1263.86 | 28.29 | 1235.57 | 0.00 | 0.00 |
September | 1192.96 | 777.92 | 1010.70 | 0.26 | 1010.44 | 0.00 | 0.00 |
October | 510.91 | 1431.13 | 754.19 | 0.00 | 754.19 | 0.00 | 0.00 |
November | 137.64 | 2107.95 | 640.48 | 0.00 | 640.48 | 0.00 | 0.00 |
December | 14.69 | 2808.72 | 511.43 | 0.00 | 511.43 | 0.00 | 0.00 |
Annual Sum or Average | 912.75 | 1439.44 | 987.08 | 40.02 | 947.06 | 0.00 | 0.00 |
Minimum of Months | 14.69 | 372.14 | 511.43 | 0.00 | 511.43 | 0.00 | 0.00 |
Maximum of Months | 2104.19 | 2808.72 | 1484.36 | 242.91 | 1249.02 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 911.22 | 1558.98 | 1109.37 | 620.24 | 489.13 | 0.00 | 0.00 |
February | 1233.54 | 1417.76 | 1347.86 | 726.64 | 621.22 | 0.00 | 0.00 |
March | 1880.72 | 1114.63 | 1778.04 | 1010.78 | 767.26 | 0.00 | 0.00 |
April | 2869.52 | 752.87 | 2429.16 | 1383.88 | 1045.28 | 0.00 | 0.00 |
May | 2912.17 | 577.64 | 2317.93 | 1320.97 | 996.96 | 0.00 | 0.00 |
June | 3483.83 | 360.73 | 2498.91 | 1539.45 | 959.46 | 0.00 | 0.00 |
July | 3372.71 | 234.57 | 2312.29 | 1322.26 | 990.03 | 0.00 | 0.00 |
August | 3231.46 | 264.14 | 2288.16 | 1261.51 | 1026.66 | 0.00 | 0.00 |
September | 2526.37 | 493.13 | 1904.51 | 1065.59 | 838.92 | 0.00 | 0.00 |
October | 1905.95 | 870.01 | 1656.34 | 1050.88 | 605.46 | 0.00 | 0.00 |
November | 1224.63 | 1272.10 | 1294.51 | 761.03 | 533.48 | 0.00 | 0.00 |
December | 876.22 | 1664.70 | 1048.92 | 638.37 | 410.56 | 0.00 | 0.00 |
Annual Sum or Average | 2206.78 | 879.14 | 1833.96 | 1059.78 | 774.18 | 0.00 | 0.00 |
Minimum of Months | 876.22 | 234.57 | 1048.92 | 620.24 | 410.56 | 0.00 | 0.00 |
Maximum of Months | 3483.83 | 1664.70 | 2498.91 | 1539.45 | 1045.28 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 5079.11 | 2295.82 | 4442.12 | 3456.58 | 985.55 | 0.00 | 0.00 |
February | 5084.75 | 2136.24 | 4347.23 | 3175.49 | 1171.73 | 0.00 | 0.00 |
March | 3824.79 | 1753.25 | 3203.47 | 1936.68 | 1266.78 | 0.00 | 0.00 |
April | 3100.92 | 1258.73 | 2498.30 | 1025.50 | 1472.80 | 0.00 | 0.00 |
May | 2088.90 | 912.95 | 1666.17 | 366.52 | 1299.65 | 0.00 | 0.00 |
June | 2105.80 | 595.60 | 1409.44 | 173.70 | 1235.75 | 0.00 | 0.00 |
July | 2530.05 | 391.73 | 1559.62 | 249.05 | 1310.56 | 0.00 | 0.00 |
August | 3314.48 | 468.43 | 2144.58 | 697.09 | 1447.49 | 0.00 | 0.00 |
September | 4249.99 | 805.88 | 2965.48 | 1653.63 | 1311.85 | 0.00 | 0.00 |
October | 5208.28 | 1354.86 | 4057.13 | 2988.04 | 1069.08 | 0.00 | 0.00 |
November | 5334.56 | 1892.59 | 4518.86 | 3468.21 | 1050.66 | 0.00 | 0.00 |
December | 5547.50 | 2398.94 | 4819.57 | 3975.64 | 843.94 | 0.00 | 0.00 |
Annual Sum or Average | 3949.31 | 1351.38 | 3129.20 | 1924.12 | 1205.08 | 0.00 | 0.00 |
Minimum of Months | 2088.90 | 391.73 | 1409.44 | 173.70 | 843.94 | 0.00 | 0.00 |
Maximum of Months | 5547.50 | 2398.94 | 4819.57 | 3975.64 | 1472.80 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1046.29 | 1738.23 | 1144.27 | 652.54 | 491.73 | 0.00 | 0.00 |
February | 1451.39 | 1624.90 | 1473.07 | 850.95 | 622.12 | 0.00 | 0.00 |
March | 1723.97 | 1322.27 | 1645.25 | 875.80 | 769.45 | 0.00 | 0.00 |
April | 2393.43 | 941.60 | 2099.83 | 1117.54 | 982.29 | 0.00 | 0.00 |
May | 2458.18 | 657.29 | 1990.94 | 1025.87 | 965.07 | 0.00 | 0.00 |
June | 2978.75 | 462.79 | 2134.28 | 1190.91 | 943.38 | 0.00 | 0.00 |
July | 2804.45 | 320.01 | 1925.06 | 942.10 | 982.96 | 0.00 | 0.00 |
August | 2742.97 | 402.27 | 1967.07 | 909.85 | 1057.22 | 0.00 | 0.00 |
September | 2366.00 | 579.76 | 1776.72 | 935.73 | 841.00 | 0.00 | 0.00 |
October | 1904.03 | 1033.38 | 1625.46 | 1010.28 | 615.18 | 0.00 | 0.00 |
November | 1230.00 | 1480.83 | 1275.98 | 750.69 | 525.29 | 0.00 | 0.00 |
December | 973.96 | 1955.03 | 1103.46 | 691.99 | 411.47 | 0.00 | 0.00 |
Annual Sum or Average | 2008.09 | 1040.36 | 1680.27 | 912.42 | 767.84 | 0.00 | 0.00 |
Minimum of Months | 973.96 | 320.01 | 1103.46 | 652.54 | 411.47 | 0.00 | 0.00 |
Maximum of Months | 2978.75 | 1955.03 | 2134.28 | 1190.91 | 1057.22 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 130.76 | 2337.11 | 600.87 | 0.00 | 600.87 | 0.00 | 0.00 |
February | 277.59 | 2115.37 | 750.99 | 0.00 | 750.99 | 0.00 | 0.00 |
March | 594.94 | 1672.51 | 947.28 | 0.00 | 947.28 | 0.00 | 0.00 |
April | 968.51 | 1119.94 | 1201.80 | 10.29 | 1191.51 | 0.00 | 0.00 |
May | 1352.90 | 817.43 | 1306.37 | 84.23 | 1222.14 | 0.00 | 0.00 |
June | 2117.87 | 544.90 | 1484.38 | 242.92 | 1241.47 | 0.00 | 0.00 |
July | 2114.06 | 369.90 | 1362.43 | 113.40 | 1249.04 | 0.00 | 0.00 |
August | 1786.86 | 417.04 | 1263.88 | 28.30 | 1235.59 | 0.00 | 0.00 |
September | 1208.70 | 743.05 | 1010.72 | 0.26 | 1010.46 | 0.00 | 0.00 |
October | 549.34 | 1310.68 | 754.20 | 0.00 | 754.20 | 0.00 | 0.00 |
November | 187.04 | 1863.55 | 640.49 | 0.00 | 640.49 | 0.00 | 0.00 |
December | 39.69 | 2455.37 | 511.43 | 0.00 | 511.43 | 0.00 | 0.00 |
Annual Sum or Average | 947.56 | 1310.01 | 987.10 | 40.02 | 947.07 | 0.00 | 0.00 |
Minimum of Months | 39.69 | 369.90 | 511.43 | 0.00 | 511.43 | 0.00 | 0.00 |
Maximum of Months | 2117.87 | 2455.37 | 1484.38 | 242.92 | 1249.04 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 944.65 | 1441.34 | 1109.37 | 620.24 | 489.13 | 0.00 | 0.00 |
February | 1262.27 | 1319.67 | 1347.86 | 726.64 | 621.22 | 0.00 | 0.00 |
March | 1889.98 | 1056.24 | 1778.03 | 1010.78 | 767.25 | 0.00 | 0.00 |
April | 2858.31 | 739.38 | 2429.15 | 1383.87 | 1045.28 | 0.00 | 0.00 |
May | 2897.44 | 565.55 | 2317.93 | 1320.97 | 996.96 | 0.00 | 0.00 |
June | 3467.24 | 365.54 | 2498.90 | 1539.44 | 959.46 | 0.00 | 0.00 |
July | 3354.63 | 254.03 | 2312.28 | 1322.25 | 990.02 | 0.00 | 0.00 |
August | 3213.46 | 284.98 | 2288.15 | 1261.50 | 1026.65 | 0.00 | 0.00 |
September | 2516.91 | 484.28 | 1904.50 | 1065.59 | 838.92 | 0.00 | 0.00 |
October | 1908.72 | 830.42 | 1656.33 | 1050.88 | 605.45 | 0.00 | 0.00 |
November | 1244.46 | 1177.05 | 1294.51 | 761.03 | 533.48 | 0.00 | 0.00 |
December | 901.65 | 1521.51 | 1048.92 | 638.36 | 410.56 | 0.00 | 0.00 |
Annual Sum or Average | 2209.25 | 834.29 | 1833.95 | 1059.78 | 774.18 | 0.00 | 0.00 |
Minimum of Months | 901.65 | 254.03 | 1048.92 | 620.24 | 410.56 | 0.00 | 0.00 |
Maximum of Months | 3467.24 | 1521.51 | 2498.90 | 1539.44 | 1045.28 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 5058.29 | 2251.45 | 4442.26 | 3456.69 | 985.57 | 0.00 | 0.00 |
February | 5063.11 | 2086.62 | 4347.36 | 3175.60 | 1171.76 | 0.00 | 0.00 |
March | 3812.43 | 1700.20 | 3203.56 | 1936.75 | 1266.81 | 0.00 | 0.00 |
April | 3097.20 | 1213.92 | 2498.36 | 1025.53 | 1472.83 | 0.00 | 0.00 |
May | 2086.71 | 888.53 | 1666.20 | 366.53 | 1299.67 | 0.00 | 0.00 |
June | 2117.30 | 583.22 | 1409.47 | 173.70 | 1235.77 | 0.00 | 0.00 |
July | 2536.88 | 392.71 | 1559.65 | 249.06 | 1310.59 | 0.00 | 0.00 |
August | 3318.71 | 458.93 | 2144.63 | 697.11 | 1447.52 | 0.00 | 0.00 |
September | 4226.80 | 796.09 | 2965.56 | 1653.69 | 1311.88 | 0.00 | 0.00 |
October | 5181.25 | 1332.25 | 4057.25 | 2988.14 | 1069.11 | 0.00 | 0.00 |
November | 5315.17 | 1842.70 | 4519.00 | 3468.32 | 1050.68 | 0.00 | 0.00 |
December | 5536.72 | 2311.05 | 4819.72 | 3975.77 | 843.96 | 0.00 | 0.00 |
Annual Sum or Average | 3939.51 | 1317.51 | 3129.29 | 1924.18 | 1205.11 | 0.00 | 0.00 |
Minimum of Months | 2086.71 | 392.71 | 1409.47 | 173.70 | 843.96 | 0.00 | 0.00 |
Maximum of Months | 5536.72 | 2311.05 | 4819.72 | 3975.77 | 1472.83 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1083.69 | 1572.44 | 1144.27 | 652.54 | 491.73 | 0.00 | 0.00 |
February | 1498.76 | 1444.87 | 1473.06 | 850.94 | 622.12 | 0.00 | 0.00 |
March | 1775.04 | 1161.42 | 1645.24 | 875.79 | 769.45 | 0.00 | 0.00 |
April | 2443.19 | 823.26 | 2099.82 | 1117.53 | 982.28 | 0.00 | 0.00 |
May | 2469.82 | 614.37 | 1990.93 | 1025.87 | 965.06 | 0.00 | 0.00 |
June | 2998.11 | 429.60 | 2134.28 | 1190.90 | 943.37 | 0.00 | 0.00 |
July | 2832.02 | 288.71 | 1925.05 | 942.09 | 982.96 | 0.00 | 0.00 |
August | 2792.58 | 331.45 | 1967.06 | 909.85 | 1057.21 | 0.00 | 0.00 |
September | 2376.37 | 540.73 | 1776.72 | 935.73 | 840.99 | 0.00 | 0.00 |
October | 1934.01 | 925.05 | 1625.46 | 1010.28 | 615.18 | 0.00 | 0.00 |
November | 1280.43 | 1267.30 | 1275.98 | 750.69 | 525.29 | 0.00 | 0.00 |
December | 1023.41 | 1626.67 | 1103.46 | 691.99 | 411.47 | 0.00 | 0.00 |
Annual Sum or Average | 2044.21 | 916.18 | 1680.26 | 912.42 | 767.84 | 0.00 | 0.00 |
Minimum of Months | 1023.41 | 288.71 | 1103.46 | 652.54 | 411.47 | 0.00 | 0.00 |
Maximum of Months | 2998.11 | 1626.67 | 2134.28 | 1190.90 | 1057.21 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 163.58 | 2160.35 | 600.87 | 0.00 | 600.87 | 0.00 | 0.00 |
February | 315.69 | 1962.45 | 750.99 | 0.00 | 750.99 | 0.00 | 0.00 |
March | 635.70 | 1555.94 | 947.28 | 0.00 | 947.28 | 0.00 | 0.00 |
April | 990.09 | 1060.34 | 1201.80 | 10.29 | 1191.51 | 0.00 | 0.00 |
May | 1358.10 | 794.11 | 1306.37 | 84.23 | 1222.14 | 0.00 | 0.00 |
June | 2104.38 | 544.01 | 1484.38 | 242.92 | 1241.47 | 0.00 | 0.00 |
July | 2092.20 | 377.69 | 1362.43 | 113.40 | 1249.04 | 0.00 | 0.00 |
August | 1768.86 | 422.09 | 1263.88 | 28.30 | 1235.59 | 0.00 | 0.00 |
September | 1204.92 | 727.75 | 1010.72 | 0.26 | 1010.46 | 0.00 | 0.00 |
October | 570.79 | 1225.13 | 754.20 | 0.00 | 754.20 | 0.00 | 0.00 |
November | 225.95 | 1693.93 | 640.49 | 0.00 | 640.49 | 0.00 | 0.00 |
December | 57.90 | 2258.92 | 511.43 | 0.00 | 511.43 | 0.00 | 0.00 |
Annual Sum or Average | 960.71 | 1228.36 | 987.10 | 40.02 | 947.07 | 0.00 | 0.00 |
Minimum of Months | 57.90 | 377.69 | 511.43 | 0.00 | 511.43 | 0.00 | 0.00 |
Maximum of Months | 2104.38 | 2258.92 | 1484.38 | 242.92 | 1249.04 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 986.54 | 1337.14 | 1109.37 | 620.24 | 489.13 | 0.00 | 0.00 |
February | 1299.87 | 1230.36 | 1347.86 | 726.64 | 621.22 | 0.00 | 0.00 |
March | 1914.45 | 995.76 | 1778.03 | 1010.78 | 767.25 | 0.00 | 0.00 |
April | 2863.54 | 713.29 | 2429.15 | 1383.87 | 1045.28 | 0.00 | 0.00 |
May | 2891.58 | 554.84 | 2317.93 | 1320.97 | 996.96 | 0.00 | 0.00 |
June | 3453.37 | 366.51 | 2498.90 | 1539.44 | 959.46 | 0.00 | 0.00 |
July | 3337.99 | 259.74 | 2312.28 | 1322.25 | 990.02 | 0.00 | 0.00 |
August | 3198.56 | 289.76 | 2288.15 | 1261.50 | 1026.65 | 0.00 | 0.00 |
September | 2510.63 | 479.33 | 1904.50 | 1065.59 | 838.92 | 0.00 | 0.00 |
October | 1920.54 | 791.12 | 1656.33 | 1050.88 | 605.45 | 0.00 | 0.00 |
November | 1281.95 | 1083.11 | 1294.51 | 761.03 | 533.48 | 0.00 | 0.00 |
December | 933.58 | 1401.16 | 1048.92 | 638.36 | 410.56 | 0.00 | 0.00 |
Annual Sum or Average | 2220.17 | 789.68 | 1833.95 | 1059.78 | 774.18 | 0.00 | 0.00 |
Minimum of Months | 933.58 | 259.74 | 1048.92 | 620.24 | 410.56 | 0.00 | 0.00 |
Maximum of Months | 3453.37 | 1401.16 | 2498.90 | 1539.44 | 1045.28 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 5114.76 | 2091.62 | 4442.26 | 3456.69 | 985.57 | 0.00 | 0.00 |
February | 5107.93 | 1945.71 | 4347.36 | 3175.60 | 1171.76 | 0.00 | 0.00 |
March | 3843.46 | 1601.85 | 3203.56 | 1936.75 | 1266.81 | 0.00 | 0.00 |
April | 3107.10 | 1159.32 | 2498.36 | 1025.53 | 1472.83 | 0.00 | 0.00 |
May | 2086.12 | 861.74 | 1666.20 | 366.53 | 1299.67 | 0.00 | 0.00 |
June | 2104.08 | 578.44 | 1409.47 | 173.70 | 1235.77 | 0.00 | 0.00 |
July | 2515.66 | 399.09 | 1559.65 | 249.06 | 1310.59 | 0.00 | 0.00 |
August | 3298.49 | 463.83 | 2144.63 | 697.11 | 1447.52 | 0.00 | 0.00 |
September | 4216.63 | 785.14 | 2965.56 | 1653.69 | 1311.88 | 0.00 | 0.00 |
October | 5196.98 | 1271.34 | 4057.25 | 2988.14 | 1069.11 | 0.00 | 0.00 |
November | 5363.15 | 1709.70 | 4519.00 | 3468.32 | 1050.68 | 0.00 | 0.00 |
December | 5582.67 | 2134.30 | 4819.72 | 3975.77 | 843.96 | 0.00 | 0.00 |
Annual Sum or Average | 3954.88 | 1246.56 | 3129.29 | 1924.18 | 1205.11 | 0.00 | 0.00 |
Minimum of Months | 2086.12 | 399.09 | 1409.47 | 173.70 | 843.96 | 0.00 | 0.00 |
Maximum of Months | 5582.67 | 2134.30 | 4819.72 | 3975.77 | 1472.83 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1104.19 | 1469.49 | 1144.27 | 652.54 | 491.73 | 0.00 | 0.00 |
February | 1517.38 | 1358.03 | 1473.06 | 850.94 | 622.12 | 0.00 | 0.00 |
March | 1792.02 | 1097.41 | 1645.24 | 875.79 | 769.45 | 0.00 | 0.00 |
April | 2448.60 | 790.31 | 2099.82 | 1117.53 | 982.28 | 0.00 | 0.00 |
May | 2467.58 | 598.70 | 1990.93 | 1025.87 | 965.06 | 0.00 | 0.00 |
June | 2987.07 | 427.63 | 2134.28 | 1190.90 | 943.37 | 0.00 | 0.00 |
July | 2817.06 | 291.98 | 1925.05 | 942.09 | 982.96 | 0.00 | 0.00 |
August | 2779.41 | 334.18 | 1967.06 | 909.85 | 1057.21 | 0.00 | 0.00 |
September | 2371.24 | 533.06 | 1776.72 | 935.73 | 840.99 | 0.00 | 0.00 |
October | 1940.73 | 880.77 | 1625.46 | 1010.28 | 615.18 | 0.00 | 0.00 |
November | 1301.01 | 1174.23 | 1275.98 | 750.69 | 525.29 | 0.00 | 0.00 |
December | 1037.60 | 1515.38 | 1103.46 | 691.99 | 411.47 | 0.00 | 0.00 |
Annual Sum or Average | 2048.82 | 870.16 | 1680.26 | 912.42 | 767.84 | 0.00 | 0.00 |
Minimum of Months | 1037.60 | 291.98 | 1103.46 | 652.54 | 411.47 | 0.00 | 0.00 |
Maximum of Months | 2987.07 | 1515.38 | 2134.28 | 1190.90 | 1057.21 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.223266E+09 | 0.692780E+10 | 0.160935E+10 | 0.00 | 0.160935E+10 | 0.00 | 0.00 |
February | 0.520408E+09 | 0.565810E+10 | 0.181676E+10 | 0.00 | 0.181676E+10 | 0.00 | 0.00 |
March | 0.143147E+10 | 0.492089E+10 | 0.253715E+10 | 0.00 | 0.253715E+10 | 0.00 | 0.00 |
April | 0.239173E+10 | 0.315003E+10 | 0.311502E+10 | 26669079.28 | 0.308835E+10 | 0.00 | 0.00 |
May | 0.356940E+10 | 0.229027E+10 | 0.349892E+10 | 0.225583E+09 | 0.327334E+10 | 0.00 | 0.00 |
June | 0.545405E+10 | 0.144458E+10 | 0.384746E+10 | 0.629622E+09 | 0.321784E+10 | 0.00 | 0.00 |
July | 0.562383E+10 | 0.996740E+09 | 0.364909E+10 | 0.303709E+09 | 0.334538E+10 | 0.00 | 0.00 |
August | 0.471351E+10 | 0.116946E+10 | 0.338514E+10 | 75784802.57 | 0.330935E+10 | 0.00 | 0.00 |
September | 0.309215E+10 | 0.201638E+10 | 0.261974E+10 | 672348.43 | 0.261907E+10 | 0.00 | 0.00 |
October | 0.136842E+10 | 0.383314E+10 | 0.202001E+10 | 0.00 | 0.202001E+10 | 0.00 | 0.00 |
November | 0.356776E+09 | 0.546382E+10 | 0.166013E+10 | 0.00 | 0.166013E+10 | 0.00 | 0.00 |
December | 39340109.37 | 0.752288E+10 | 0.136980E+10 | 0.00 | 0.136980E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.287844E+11 | 0.453941E+11 | 0.311286E+11 | 0.126204E+10 | 0.298665E+11 | 0.00 | 0.00 |
Minimum of Months | 39340109.37 | 0.996740E+09 | 0.136980E+10 | 0.00 | 0.136980E+10 | 0.00 | 0.00 |
Maximum of Months | 0.562383E+10 | 0.752288E+10 | 0.384746E+10 | 0.629622E+09 | 0.334538E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.244060E+10 | 0.417558E+10 | 0.297134E+10 | 0.166126E+10 | 0.131008E+10 | 0.00 | 0.00 |
February | 0.298418E+10 | 0.342985E+10 | 0.326075E+10 | 0.175790E+10 | 0.150286E+10 | 0.00 | 0.00 |
March | 0.503732E+10 | 0.298541E+10 | 0.476229E+10 | 0.270728E+10 | 0.205502E+10 | 0.00 | 0.00 |
April | 0.743779E+10 | 0.195144E+10 | 0.629638E+10 | 0.358702E+10 | 0.270937E+10 | 0.00 | 0.00 |
May | 0.779996E+10 | 0.154716E+10 | 0.620836E+10 | 0.353809E+10 | 0.267027E+10 | 0.00 | 0.00 |
June | 0.903009E+10 | 0.935006E+09 | 0.647718E+10 | 0.399025E+10 | 0.248693E+10 | 0.00 | 0.00 |
July | 0.903347E+10 | 0.628262E+09 | 0.619323E+10 | 0.354154E+10 | 0.265169E+10 | 0.00 | 0.00 |
August | 0.865515E+10 | 0.707470E+09 | 0.612862E+10 | 0.337882E+10 | 0.274979E+10 | 0.00 | 0.00 |
September | 0.654834E+10 | 0.127819E+10 | 0.493649E+10 | 0.276201E+10 | 0.217448E+10 | 0.00 | 0.00 |
October | 0.510489E+10 | 0.233025E+10 | 0.443634E+10 | 0.281469E+10 | 0.162166E+10 | 0.00 | 0.00 |
November | 0.317423E+10 | 0.329728E+10 | 0.335538E+10 | 0.197260E+10 | 0.138278E+10 | 0.00 | 0.00 |
December | 0.234687E+10 | 0.445874E+10 | 0.280943E+10 | 0.170980E+10 | 0.109964E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.695929E+11 | 0.277246E+11 | 0.578358E+11 | 0.334213E+11 | 0.244145E+11 | 0.00 | 0.00 |
Minimum of Months | 0.234687E+10 | 0.628262E+09 | 0.280943E+10 | 0.166126E+10 | 0.109964E+10 | 0.00 | 0.00 |
Maximum of Months | 0.903347E+10 | 0.445874E+10 | 0.647718E+10 | 0.399025E+10 | 0.274979E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.136039E+11 | 0.614912E+10 | 0.118978E+11 | 0.925810E+10 | 0.263969E+10 | 0.00 | 0.00 |
February | 0.123010E+11 | 0.516799E+10 | 0.105168E+11 | 0.768215E+10 | 0.283466E+10 | 0.00 | 0.00 |
March | 0.102443E+11 | 0.469590E+10 | 0.858016E+10 | 0.518721E+10 | 0.339295E+10 | 0.00 | 0.00 |
April | 0.803758E+10 | 0.326263E+10 | 0.647560E+10 | 0.265810E+10 | 0.381751E+10 | 0.00 | 0.00 |
May | 0.559492E+10 | 0.244523E+10 | 0.446267E+10 | 0.981693E+09 | 0.348098E+10 | 0.00 | 0.00 |
June | 0.545823E+10 | 0.154380E+10 | 0.365328E+10 | 0.450220E+09 | 0.320306E+10 | 0.00 | 0.00 |
July | 0.677649E+10 | 0.104920E+10 | 0.417728E+10 | 0.667063E+09 | 0.351022E+10 | 0.00 | 0.00 |
August | 0.887752E+10 | 0.125463E+10 | 0.574405E+10 | 0.186709E+10 | 0.387696E+10 | 0.00 | 0.00 |
September | 0.110160E+11 | 0.208884E+10 | 0.768653E+10 | 0.428621E+10 | 0.340032E+10 | 0.00 | 0.00 |
October | 0.139499E+11 | 0.362885E+10 | 0.108666E+11 | 0.800317E+10 | 0.286343E+10 | 0.00 | 0.00 |
November | 0.138272E+11 | 0.490560E+10 | 0.117129E+11 | 0.898959E+10 | 0.272330E+10 | 0.00 | 0.00 |
December | 0.148584E+11 | 0.642532E+10 | 0.129087E+11 | 0.106483E+11 | 0.226040E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.124545E+12 | 0.426171E+11 | 0.986824E+11 | 0.606790E+11 | 0.380035E+11 | 0.00 | 0.00 |
Minimum of Months | 0.545823E+10 | 0.104920E+10 | 0.365328E+10 | 0.450220E+09 | 0.226040E+10 | 0.00 | 0.00 |
Maximum of Months | 0.148584E+11 | 0.642532E+10 | 0.129087E+11 | 0.106483E+11 | 0.387696E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.280239E+10 | 0.465568E+10 | 0.306482E+10 | 0.174777E+10 | 0.131705E+10 | 0.00 | 0.00 |
February | 0.351121E+10 | 0.393096E+10 | 0.356364E+10 | 0.205861E+10 | 0.150503E+10 | 0.00 | 0.00 |
March | 0.461747E+10 | 0.354156E+10 | 0.440663E+10 | 0.234573E+10 | 0.206089E+10 | 0.00 | 0.00 |
April | 0.620376E+10 | 0.244063E+10 | 0.544275E+10 | 0.289666E+10 | 0.254609E+10 | 0.00 | 0.00 |
May | 0.658400E+10 | 0.176049E+10 | 0.533254E+10 | 0.274770E+10 | 0.258484E+10 | 0.00 | 0.00 |
June | 0.772091E+10 | 0.119955E+10 | 0.553207E+10 | 0.308684E+10 | 0.244523E+10 | 0.00 | 0.00 |
July | 0.751144E+10 | 0.857117E+09 | 0.515608E+10 | 0.252332E+10 | 0.263276E+10 | 0.00 | 0.00 |
August | 0.734676E+10 | 0.107743E+10 | 0.526860E+10 | 0.243694E+10 | 0.283165E+10 | 0.00 | 0.00 |
September | 0.613267E+10 | 0.150273E+10 | 0.460527E+10 | 0.242541E+10 | 0.217986E+10 | 0.00 | 0.00 |
October | 0.509974E+10 | 0.276781E+10 | 0.435364E+10 | 0.270594E+10 | 0.164769E+10 | 0.00 | 0.00 |
November | 0.318817E+10 | 0.383831E+10 | 0.330734E+10 | 0.194579E+10 | 0.136156E+10 | 0.00 | 0.00 |
December | 0.260866E+10 | 0.523636E+10 | 0.295552E+10 | 0.185343E+10 | 0.110209E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.633272E+11 | 0.328086E+11 | 0.529889E+11 | 0.287741E+11 | 0.242148E+11 | 0.00 | 0.00 |
Minimum of Months | 0.260866E+10 | 0.857117E+09 | 0.295552E+10 | 0.174777E+10 | 0.110209E+10 | 0.00 | 0.00 |
Maximum of Months | 0.772091E+10 | 0.523636E+10 | 0.553207E+10 | 0.308684E+10 | 0.283165E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.350217E+09 | 0.625971E+10 | 0.160938E+10 | 0.00 | 0.160938E+10 | 0.00 | 0.00 |
February | 0.671540E+09 | 0.511751E+10 | 0.181679E+10 | 0.00 | 0.181679E+10 | 0.00 | 0.00 |
March | 0.159349E+10 | 0.447966E+10 | 0.253719E+10 | 0.00 | 0.253719E+10 | 0.00 | 0.00 |
April | 0.251037E+10 | 0.290289E+10 | 0.311507E+10 | 26669874.63 | 0.308840E+10 | 0.00 | 0.00 |
May | 0.362360E+10 | 0.218941E+10 | 0.349897E+10 | 0.225590E+09 | 0.327338E+10 | 0.00 | 0.00 |
June | 0.548952E+10 | 0.141238E+10 | 0.384753E+10 | 0.629640E+09 | 0.321789E+10 | 0.00 | 0.00 |
July | 0.566230E+10 | 0.990741E+09 | 0.364914E+10 | 0.303718E+09 | 0.334542E+10 | 0.00 | 0.00 |
August | 0.478592E+10 | 0.111700E+10 | 0.338519E+10 | 75787062.69 | 0.330940E+10 | 0.00 | 0.00 |
September | 0.313294E+10 | 0.192600E+10 | 0.261977E+10 | 672368.48 | 0.261910E+10 | 0.00 | 0.00 |
October | 0.147136E+10 | 0.351054E+10 | 0.202004E+10 | 0.00 | 0.202004E+10 | 0.00 | 0.00 |
November | 0.484807E+09 | 0.483032E+10 | 0.166015E+10 | 0.00 | 0.166015E+10 | 0.00 | 0.00 |
December | 0.106301E+09 | 0.657647E+10 | 0.136982E+10 | 0.00 | 0.136982E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.298824E+11 | 0.413126E+11 | 0.311290E+11 | 0.126208E+10 | 0.298670E+11 | 0.00 | 0.00 |
Minimum of Months | 0.106301E+09 | 0.990741E+09 | 0.136982E+10 | 0.00 | 0.136982E+10 | 0.00 | 0.00 |
Maximum of Months | 0.566230E+10 | 0.657647E+10 | 0.384753E+10 | 0.629640E+09 | 0.334542E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.253016E+10 | 0.386048E+10 | 0.297133E+10 | 0.166125E+10 | 0.131007E+10 | 0.00 | 0.00 |
February | 0.305369E+10 | 0.319255E+10 | 0.326074E+10 | 0.175789E+10 | 0.150285E+10 | 0.00 | 0.00 |
March | 0.506213E+10 | 0.282902E+10 | 0.476227E+10 | 0.270727E+10 | 0.205501E+10 | 0.00 | 0.00 |
April | 0.740874E+10 | 0.191646E+10 | 0.629636E+10 | 0.358700E+10 | 0.270935E+10 | 0.00 | 0.00 |
May | 0.776050E+10 | 0.151478E+10 | 0.620833E+10 | 0.353808E+10 | 0.267025E+10 | 0.00 | 0.00 |
June | 0.898709E+10 | 0.947475E+09 | 0.647715E+10 | 0.399023E+10 | 0.248692E+10 | 0.00 | 0.00 |
July | 0.898504E+10 | 0.680395E+09 | 0.619320E+10 | 0.354153E+10 | 0.265168E+10 | 0.00 | 0.00 |
August | 0.860692E+10 | 0.763289E+09 | 0.612859E+10 | 0.337881E+10 | 0.274978E+10 | 0.00 | 0.00 |
September | 0.652382E+10 | 0.125526E+10 | 0.493647E+10 | 0.276200E+10 | 0.217447E+10 | 0.00 | 0.00 |
October | 0.511231E+10 | 0.222420E+10 | 0.443632E+10 | 0.281467E+10 | 0.162165E+10 | 0.00 | 0.00 |
November | 0.322565E+10 | 0.305092E+10 | 0.335536E+10 | 0.197259E+10 | 0.138277E+10 | 0.00 | 0.00 |
December | 0.241497E+10 | 0.407522E+10 | 0.280942E+10 | 0.170979E+10 | 0.109963E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.696710E+11 | 0.263101E+11 | 0.578356E+11 | 0.334211E+11 | 0.244144E+11 | 0.00 | 0.00 |
Minimum of Months | 0.241497E+10 | 0.680395E+09 | 0.280942E+10 | 0.166125E+10 | 0.109963E+10 | 0.00 | 0.00 |
Maximum of Months | 0.898709E+10 | 0.407522E+10 | 0.647715E+10 | 0.399023E+10 | 0.274978E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.135481E+11 | 0.603029E+10 | 0.118982E+11 | 0.925840E+10 | 0.263975E+10 | 0.00 | 0.00 |
February | 0.122487E+11 | 0.504796E+10 | 0.105171E+11 | 0.768240E+10 | 0.283472E+10 | 0.00 | 0.00 |
March | 0.102112E+11 | 0.455382E+10 | 0.858041E+10 | 0.518738E+10 | 0.339302E+10 | 0.00 | 0.00 |
April | 0.802794E+10 | 0.314649E+10 | 0.647576E+10 | 0.265818E+10 | 0.381758E+10 | 0.00 | 0.00 |
May | 0.558905E+10 | 0.237984E+10 | 0.446276E+10 | 0.981725E+09 | 0.348103E+10 | 0.00 | 0.00 |
June | 0.548804E+10 | 0.151170E+10 | 0.365334E+10 | 0.450235E+09 | 0.320310E+10 | 0.00 | 0.00 |
July | 0.679477E+10 | 0.105184E+10 | 0.417736E+10 | 0.667085E+09 | 0.351027E+10 | 0.00 | 0.00 |
August | 0.888885E+10 | 0.122920E+10 | 0.574418E+10 | 0.186715E+10 | 0.387703E+10 | 0.00 | 0.00 |
September | 0.109559E+11 | 0.206347E+10 | 0.768674E+10 | 0.428635E+10 | 0.340039E+10 | 0.00 | 0.00 |
October | 0.138774E+11 | 0.356829E+10 | 0.108669E+11 | 0.800344E+10 | 0.286349E+10 | 0.00 | 0.00 |
November | 0.137769E+11 | 0.477627E+10 | 0.117133E+11 | 0.898989E+10 | 0.272337E+10 | 0.00 | 0.00 |
December | 0.148295E+11 | 0.618992E+10 | 0.129091E+11 | 0.106487E+11 | 0.226045E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.124236E+12 | 0.415491E+11 | 0.986851E+11 | 0.606809E+11 | 0.380042E+11 | 0.00 | 0.00 |
Minimum of Months | 0.548804E+10 | 0.105184E+10 | 0.365334E+10 | 0.450235E+09 | 0.226045E+10 | 0.00 | 0.00 |
Maximum of Months | 0.148295E+11 | 0.618992E+10 | 0.129091E+11 | 0.106487E+11 | 0.387703E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.290256E+10 | 0.421163E+10 | 0.306481E+10 | 0.174777E+10 | 0.131705E+10 | 0.00 | 0.00 |
February | 0.362580E+10 | 0.349543E+10 | 0.356362E+10 | 0.205860E+10 | 0.150502E+10 | 0.00 | 0.00 |
March | 0.475427E+10 | 0.311074E+10 | 0.440661E+10 | 0.234573E+10 | 0.206088E+10 | 0.00 | 0.00 |
April | 0.633275E+10 | 0.213389E+10 | 0.544273E+10 | 0.289665E+10 | 0.254608E+10 | 0.00 | 0.00 |
May | 0.661515E+10 | 0.164554E+10 | 0.533252E+10 | 0.274769E+10 | 0.258483E+10 | 0.00 | 0.00 |
June | 0.777110E+10 | 0.111352E+10 | 0.553204E+10 | 0.308682E+10 | 0.244522E+10 | 0.00 | 0.00 |
July | 0.758528E+10 | 0.773276E+09 | 0.515606E+10 | 0.252331E+10 | 0.263275E+10 | 0.00 | 0.00 |
August | 0.747966E+10 | 0.887761E+09 | 0.526857E+10 | 0.243693E+10 | 0.283164E+10 | 0.00 | 0.00 |
September | 0.615955E+10 | 0.140158E+10 | 0.460525E+10 | 0.242540E+10 | 0.217985E+10 | 0.00 | 0.00 |
October | 0.518004E+10 | 0.247766E+10 | 0.435362E+10 | 0.270593E+10 | 0.164769E+10 | 0.00 | 0.00 |
November | 0.331888E+10 | 0.328484E+10 | 0.330733E+10 | 0.194578E+10 | 0.136155E+10 | 0.00 | 0.00 |
December | 0.274111E+10 | 0.435688E+10 | 0.295551E+10 | 0.185342E+10 | 0.110209E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.644662E+11 | 0.288928E+11 | 0.529887E+11 | 0.287740E+11 | 0.242147E+11 | 0.00 | 0.00 |
Minimum of Months | 0.274111E+10 | 0.773276E+09 | 0.295551E+10 | 0.174777E+10 | 0.110209E+10 | 0.00 | 0.00 |
Maximum of Months | 0.777110E+10 | 0.435688E+10 | 0.553204E+10 | 0.308682E+10 | 0.283164E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.438132E+09 | 0.578629E+10 | 0.160938E+10 | 0.00 | 0.160938E+10 | 0.00 | 0.00 |
February | 0.763707E+09 | 0.474756E+10 | 0.181679E+10 | 0.00 | 0.181679E+10 | 0.00 | 0.00 |
March | 0.170265E+10 | 0.416744E+10 | 0.253719E+10 | 0.00 | 0.253719E+10 | 0.00 | 0.00 |
April | 0.256630E+10 | 0.274840E+10 | 0.311507E+10 | 26669874.63 | 0.308840E+10 | 0.00 | 0.00 |
May | 0.363753E+10 | 0.212693E+10 | 0.349897E+10 | 0.225590E+09 | 0.327338E+10 | 0.00 | 0.00 |
June | 0.545455E+10 | 0.141008E+10 | 0.384753E+10 | 0.629640E+09 | 0.321789E+10 | 0.00 | 0.00 |
July | 0.560376E+10 | 0.101159E+10 | 0.364914E+10 | 0.303718E+09 | 0.334542E+10 | 0.00 | 0.00 |
August | 0.473771E+10 | 0.113052E+10 | 0.338519E+10 | 75787062.69 | 0.330940E+10 | 0.00 | 0.00 |
September | 0.312315E+10 | 0.188632E+10 | 0.261977E+10 | 672368.48 | 0.261910E+10 | 0.00 | 0.00 |
October | 0.152880E+10 | 0.328138E+10 | 0.202004E+10 | 0.00 | 0.202004E+10 | 0.00 | 0.00 |
November | 0.585665E+09 | 0.439068E+10 | 0.166015E+10 | 0.00 | 0.166015E+10 | 0.00 | 0.00 |
December | 0.155069E+09 | 0.605029E+10 | 0.136982E+10 | 0.00 | 0.136982E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.302970E+11 | 0.387375E+11 | 0.311290E+11 | 0.126208E+10 | 0.298670E+11 | 0.00 | 0.00 |
Minimum of Months | 0.155069E+09 | 0.101159E+10 | 0.136982E+10 | 0.00 | 0.136982E+10 | 0.00 | 0.00 |
Maximum of Months | 0.560376E+10 | 0.605029E+10 | 0.384753E+10 | 0.629640E+09 | 0.334542E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.264234E+10 | 0.358141E+10 | 0.297133E+10 | 0.166125E+10 | 0.131007E+10 | 0.00 | 0.00 |
February | 0.314466E+10 | 0.297649E+10 | 0.326074E+10 | 0.175789E+10 | 0.150285E+10 | 0.00 | 0.00 |
March | 0.512766E+10 | 0.266703E+10 | 0.476227E+10 | 0.270727E+10 | 0.205501E+10 | 0.00 | 0.00 |
April | 0.742230E+10 | 0.184884E+10 | 0.629636E+10 | 0.358700E+10 | 0.270935E+10 | 0.00 | 0.00 |
May | 0.774482E+10 | 0.148608E+10 | 0.620833E+10 | 0.353808E+10 | 0.267025E+10 | 0.00 | 0.00 |
June | 0.895114E+10 | 0.950001E+09 | 0.647715E+10 | 0.399023E+10 | 0.248692E+10 | 0.00 | 0.00 |
July | 0.894048E+10 | 0.695675E+09 | 0.619320E+10 | 0.354153E+10 | 0.265168E+10 | 0.00 | 0.00 |
August | 0.856702E+10 | 0.776092E+09 | 0.612859E+10 | 0.337881E+10 | 0.274978E+10 | 0.00 | 0.00 |
September | 0.650755E+10 | 0.124241E+10 | 0.493647E+10 | 0.276200E+10 | 0.217447E+10 | 0.00 | 0.00 |
October | 0.514397E+10 | 0.211894E+10 | 0.443632E+10 | 0.281467E+10 | 0.162165E+10 | 0.00 | 0.00 |
November | 0.332281E+10 | 0.280741E+10 | 0.335536E+10 | 0.197259E+10 | 0.138277E+10 | 0.00 | 0.00 |
December | 0.250051E+10 | 0.375287E+10 | 0.280942E+10 | 0.170979E+10 | 0.109963E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.700152E+11 | 0.249033E+11 | 0.578356E+11 | 0.334211E+11 | 0.244144E+11 | 0.00 | 0.00 |
Minimum of Months | 0.250051E+10 | 0.695675E+09 | 0.280942E+10 | 0.166125E+10 | 0.109963E+10 | 0.00 | 0.00 |
Maximum of Months | 0.895114E+10 | 0.375287E+10 | 0.647715E+10 | 0.399023E+10 | 0.274978E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.136994E+11 | 0.560219E+10 | 0.118982E+11 | 0.925840E+10 | 0.263975E+10 | 0.00 | 0.00 |
February | 0.123571E+11 | 0.470706E+10 | 0.105171E+11 | 0.768240E+10 | 0.283472E+10 | 0.00 | 0.00 |
March | 0.102943E+11 | 0.429041E+10 | 0.858041E+10 | 0.518738E+10 | 0.339302E+10 | 0.00 | 0.00 |
April | 0.805360E+10 | 0.300497E+10 | 0.647576E+10 | 0.265818E+10 | 0.381758E+10 | 0.00 | 0.00 |
May | 0.558747E+10 | 0.230808E+10 | 0.446276E+10 | 0.981725E+09 | 0.348103E+10 | 0.00 | 0.00 |
June | 0.545377E+10 | 0.149931E+10 | 0.365334E+10 | 0.450235E+09 | 0.320310E+10 | 0.00 | 0.00 |
July | 0.673794E+10 | 0.106893E+10 | 0.417736E+10 | 0.667085E+09 | 0.351027E+10 | 0.00 | 0.00 |
August | 0.883467E+10 | 0.124232E+10 | 0.574418E+10 | 0.186715E+10 | 0.387703E+10 | 0.00 | 0.00 |
September | 0.109295E+11 | 0.203508E+10 | 0.768674E+10 | 0.428635E+10 | 0.340039E+10 | 0.00 | 0.00 |
October | 0.139196E+11 | 0.340517E+10 | 0.108669E+11 | 0.800344E+10 | 0.286349E+10 | 0.00 | 0.00 |
November | 0.139013E+11 | 0.443155E+10 | 0.117133E+11 | 0.898989E+10 | 0.272337E+10 | 0.00 | 0.00 |
December | 0.149526E+11 | 0.571650E+10 | 0.129091E+11 | 0.106487E+11 | 0.226045E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.124721E+12 | 0.393116E+11 | 0.986851E+11 | 0.606809E+11 | 0.380042E+11 | 0.00 | 0.00 |
Minimum of Months | 0.545377E+10 | 0.106893E+10 | 0.365334E+10 | 0.450235E+09 | 0.226045E+10 | 0.00 | 0.00 |
Maximum of Months | 0.149526E+11 | 0.571650E+10 | 0.129091E+11 | 0.106487E+11 | 0.387703E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.295746E+10 | 0.393589E+10 | 0.306481E+10 | 0.174777E+10 | 0.131705E+10 | 0.00 | 0.00 |
February | 0.367085E+10 | 0.328534E+10 | 0.356362E+10 | 0.205860E+10 | 0.150502E+10 | 0.00 | 0.00 |
March | 0.479974E+10 | 0.293929E+10 | 0.440661E+10 | 0.234573E+10 | 0.206088E+10 | 0.00 | 0.00 |
April | 0.634678E+10 | 0.204847E+10 | 0.544273E+10 | 0.289665E+10 | 0.254608E+10 | 0.00 | 0.00 |
May | 0.660918E+10 | 0.160357E+10 | 0.533252E+10 | 0.274769E+10 | 0.258483E+10 | 0.00 | 0.00 |
June | 0.774249E+10 | 0.110842E+10 | 0.553204E+10 | 0.308682E+10 | 0.244522E+10 | 0.00 | 0.00 |
July | 0.754522E+10 | 0.782041E+09 | 0.515606E+10 | 0.252331E+10 | 0.263275E+10 | 0.00 | 0.00 |
August | 0.744437E+10 | 0.895063E+09 | 0.526857E+10 | 0.243693E+10 | 0.283164E+10 | 0.00 | 0.00 |
September | 0.614624E+10 | 0.138168E+10 | 0.460525E+10 | 0.242540E+10 | 0.217985E+10 | 0.00 | 0.00 |
October | 0.519804E+10 | 0.235906E+10 | 0.435362E+10 | 0.270593E+10 | 0.164769E+10 | 0.00 | 0.00 |
November | 0.337221E+10 | 0.304361E+10 | 0.330733E+10 | 0.194578E+10 | 0.136155E+10 | 0.00 | 0.00 |
December | 0.277910E+10 | 0.405880E+10 | 0.295551E+10 | 0.185342E+10 | 0.110209E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.646117E+11 | 0.274412E+11 | 0.529887E+11 | 0.287740E+11 | 0.242147E+11 | 0.00 | 0.00 |
Minimum of Months | 0.277910E+10 | 0.782041E+09 | 0.295551E+10 | 0.174777E+10 | 0.110209E+10 | 0.00 | 0.00 |
Maximum of Months | 0.774249E+10 | 0.405880E+10 | 0.553204E+10 | 0.308682E+10 | 0.283164E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 2.60 | -1.3 | -7.5 | 3.29 | -12.5 | 38.91 | 220.14 | 0.00 |
February | 4.28 | 0.13 | -5.8 | 3.80 | -10.7 | 48.21 | 247.44 | 0.00 |
March | 8.76 | 2.64 | -5.5 | 4.72 | -6.0 | 66.36 | 249.43 | 0.00 |
April | 13.90 | 4.70 | -6.4 | 4.61 | -1.8 | 81.54 | 308.98 | 0.00 |
May | 17.82 | 8.42 | -1.1 | 4.68 | 3.61 | 77.67 | 310.50 | 0.00 |
June | 23.21 | 12.42 | 4.15 | 4.28 | 9.16 | 70.88 | 348.57 | 0.00 |
July | 25.63 | 16.13 | 10.74 | 4.00 | 14.07 | 80.74 | 308.61 | 0.00 |
August | 24.08 | 15.39 | 10.38 | 3.96 | 13.00 | 86.20 | 290.42 | 0.00 |
September | 20.49 | 12.87 | 7.70 | 3.48 | 8.22 | 67.00 | 274.65 | 0.00 |
October | 13.71 | 6.72 | -0.1 | 3.54 | -0.8 | 42.11 | 283.53 | 0.00 |
November | 6.96 | 1.72 | -4.9 | 3.43 | -7.6 | 39.44 | 239.51 | 0.01 |
December | 2.07 | -2.2 | -8.9 | 2.95 | -13.5 | 27.44 | 240.96 | 0.00 |
Annual Sum or Average | 13.68 | 6.50 | -0.6 | 3.90 | -0.3 | 60.60 | 276.96 | 0.00 |
Minimum of Months | 2.07 | -2.2 | -8.9 | 2.95 | -13.5 | 27.44 | 220.14 | 0.00 |
Maximum of Months | 25.63 | 16.13 | 10.74 | 4.72 | 14.07 | 86.20 | 348.57 | 0.01 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.10 | 01-JAN-14:00 | 5.83 | -6.7 | 5.20 | -2.3 | 27.00 | 880.00 |
February | 22.20 | 14-FEB-15:00 | 7.86 | -10.0 | 4.60 | 4.72 | 61.50 | 778.50 |
March | 22.80 | 08-MAR-13:00 | 9.68 | -2.8 | 3.60 | 4.92 | 122.50 | 851.50 |
April | 26.10 | 13-APR-16:00 | 10.32 | -4.4 | 5.20 | 7.55 | 95.00 | 507.00 |
May | 30.00 | 19-MAY-15:20 | 12.71 | -1.5 | 8.93 | 13.35 | 108.33 | 887.00 |
June | 38.90 | 28-JUN-15:00 | 14.16 | -8.9 | 3.10 | 20.75 | 70.00 | 888.00 |
July | 38.30 | 22-JUL-14:00 | 16.71 | 3.30 | 5.20 | 24.16 | 99.00 | 907.50 |
August | 35.00 | 01-AUG-14:00 | 16.30 | 4.40 | 2.60 | 19.52 | 113.00 | 840.50 |
September | 32.80 | 03-SEP-13:00 | 16.76 | 7.80 | 3.60 | 21.78 | 263.50 | 532.50 |
October | 28.90 | 01-OCT-15:00 | 13.26 | 1.70 | 4.10 | 15.94 | 85.00 | 435.00 |
November | 19.40 | 09-NOV-13:00 | 9.81 | 1.70 | 10.80 | 8.35 | 157.50 | 0.00 |
December | 13.30 | 24-DEC-14:00 | 4.02 | -8.3 | 8.20 | -2.5 | 40.50 | 792.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.30 | 4.02 | -10.0 | 2.60 | -2.5 | 27.00 | 0.00 | |
Maximum of Months | 38.90 | 16.76 | 7.80 | 10.80 | 24.16 | 263.50 | 907.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -8.3 | 20-JAN-01:00 | -8.3 | -8.3 | 2.10 | -25.6 | 0.00 | 0.00 |
February | -6.7 | 04-FEB-06:10 | -8.2 | -11.7 | 5.10 | -25.0 | 0.00 | 0.00 |
March | -3.9 | 05-MAR-06:00 | -5.7 | -9.4 | 1.50 | -21.6 | 17.00 | 434.50 |
April | 1.70 | 06-APR-05:00 | -2.4 | -8.3 | 2.60 | -12.9 | 28.00 | 215.00 |
May | 4.40 | 07-MAY-04:00 | -1.0 | -8.3 | 1.50 | -13.7 | 0.00 | 0.00 |
June | 7.80 | 09-JUN-04:40 | 5.54 | 3.30 | 4.83 | -7.8 | 0.00 | 0.00 |
July | 16.10 | 08-JUL-02:00 | 14.67 | 13.90 | 0.00 | 4.72 | 0.00 | 0.00 |
August | 12.80 | 31-AUG-05:00 | 10.77 | 9.40 | 3.10 | -1.7 | 24.50 | 228.50 |
September | 10.60 | 09-SEP-05:00 | 9.95 | 9.40 | 2.10 | -2.5 | 15.50 | 177.00 |
October | -2.8 | 26-OCT-04:10 | -4.1 | -6.1 | 2.42 | -17.7 | 0.00 | 0.00 |
November | -4.4 | 27-NOV-05:00 | -6.9 | -11.7 | 2.60 | -22.7 | 0.00 | 0.00 |
December | -9.4 | 15-DEC-04:00 | -12.1 | -21.7 | 0.00 | -29.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -9.4 | -12.1 | -21.7 | 0.00 | -29.7 | 0.00 | 0.00 | |
Maximum of Months | 16.10 | 14.67 | 13.90 | 5.10 | 4.72 | 28.00 | 434.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 6.84 | 05-JAN-13:00 | 16.10 | -2.8 | 3.10 | -0.1 | 62.00 | 873.00 |
February | 7.86 | 14-FEB-15:00 | 22.20 | -10.0 | 4.60 | 4.72 | 61.50 | 778.50 |
March | 9.68 | 08-MAR-13:00 | 22.80 | -2.8 | 3.60 | 4.92 | 122.50 | 851.50 |
April | 10.95 | 14-APR-15:00 | 24.40 | -0.6 | 8.20 | 17.21 | 237.00 | 154.00 |
May | 15.08 | 22-MAY-12:30 | 28.60 | 6.40 | 5.15 | 16.76 | 167.00 | 0.00 |
June | 18.19 | 24-JUN-13:00 | 31.70 | 11.70 | 2.60 | 19.17 | 130.00 | 891.50 |
July | 19.21 | 31-JUL-14:00 | 32.80 | 12.80 | 6.20 | 22.98 | 264.50 | 624.50 |
August | 19.18 | 26-AUG-12:00 | 27.80 | 15.60 | 3.60 | 17.03 | 289.00 | 426.50 |
September | 18.19 | 05-SEP-12:00 | 23.90 | 15.60 | 3.10 | 13.35 | 196.50 | 796.00 |
October | 16.16 | 11-OCT-10:00 | 23.90 | 12.20 | 13.40 | 13.73 | 219.50 | 450.00 |
November | 9.81 | 09-NOV-13:00 | 19.40 | 1.70 | 10.80 | 8.35 | 157.50 | 0.00 |
December | 4.92 | 01-DEC-15:00 | 12.80 | -3.9 | 2.10 | 1.58 | 50.00 | 276.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 4.92 | 12.80 | -10.0 | 2.10 | -0.1 | 50.00 | 0.00 | |
Maximum of Months | 19.21 | 32.80 | 15.60 | 13.40 | 22.98 | 289.00 | 891.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -0.6 | 28-JAN-17:00 | 6.10 | 3.01 | 4.60 | -5.0 | 0.00 | 0.00 |
February | 2.20 | 17-FEB-10:00 | 7.20 | 4.72 | 3.10 | -4.1 | 212.50 | 561.00 |
March | 5.60 | 28-MAR-17:10 | 8.80 | 7.05 | 4.60 | 3.37 | 35.00 | 0.67 |
April | 7.20 | 15-APR-06:00 | 13.30 | 9.79 | 7.20 | 6.35 | 116.00 | 422.00 |
May | 13.90 | 24-MAY-14:00 | 16.70 | 14.90 | 4.60 | 11.07 | 128.00 | 0.00 |
June | 13.30 | 30-JUN-13:00 | 26.70 | 17.72 | 6.70 | 20.75 | 170.00 | 126.50 |
July | 17.80 | 01-JUL-13:00 | 22.20 | 19.05 | 3.60 | 13.91 | 361.00 | 125.00 |
August | 17.20 | 26-AUG-09:00 | 21.70 | 18.59 | 2.60 | 11.65 | 243.50 | 681.50 |
September | 15.60 | 05-SEP-11:00 | 22.20 | 17.61 | 3.10 | 12.79 | 231.00 | 705.00 |
October | 13.90 | 02-OCT-16:00 | 20.60 | 16.04 | 6.20 | 13.54 | 38.50 | 65.00 |
November | 6.10 | 09-NOV-21:00 | 8.90 | 7.38 | 11.80 | 3.69 | 0.00 | 0.00 |
December | 1.10 | 25-DEC-08:00 | 2.20 | 1.65 | 2.10 | -4.1 | 54.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -0.6 | 2.20 | 1.65 | 2.10 | -5.0 | 0.00 | 0.00 | |
Maximum of Months | 17.80 | 26.70 | 19.05 | 11.80 | 20.75 | 361.00 | 705.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 11.28 | 25.87 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 10.91 | 34.17 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 12.10 | 41.92 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 14.59 | 56.24 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 17.73 | 59.47 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 20.66 | 62.98 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 22.59 | 61.22 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 23.01 | 57.83 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 21.78 | 48.11 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 19.25 | 37.89 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 16.11 | 28.37 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 13.20 | 24.17 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 16.97 | 44.90 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 10.91 | 24.17 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 23.01 | 62.98 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.390135E+11 | -0.379882E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102531E+10 | 58.98 | 0.00 | 0.00 |
February | 0.357132E+11 | -0.347868E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -926400893.1 | 58.98 | 0.00 | 0.00 |
March | 0.409312E+11 | -0.399039E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102730E+10 | 58.97 | 0.00 | 0.00 |
April | 0.352575E+11 | -0.342679E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -989600284.8 | 58.97 | 0.00 | 0.00 |
May | 0.350672E+11 | -0.340430E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102425E+10 | 58.98 | 0.00 | 0.00 |
June | 0.323113E+11 | -0.313200E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -991353894.2 | 58.97 | 0.00 | 0.00 |
July | 0.292917E+11 | -0.282728E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101895E+10 | 58.97 | 0.00 | 0.00 |
August | 0.316447E+11 | -0.306219E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102282E+10 | 58.97 | 0.00 | 0.00 |
September | 0.297261E+11 | -0.287383E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -987799215.9 | 58.97 | 0.00 | 0.00 |
October | 0.326764E+11 | -0.316566E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101981E+10 | 58.98 | 0.00 | 0.00 |
November | 0.344807E+11 | -0.334933E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -987422487.5 | 58.97 | 0.00 | 0.00 |
December | 0.366000E+11 | -0.355787E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102129E+10 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.412714E+12 | -0.400671E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.120423E+11 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.292917E+11 | -0.399039E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.102730E+10 | 58.97 | 0.00 | 0.00 |
Maximum of Months | 0.409312E+11 | -0.282728E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -926400893.1 | 58.98 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.63 | 0.61 | 01-JAN-07:49 | 8985.82 | 35.41 | 269.50 | 278.33 | 2171.50 | 27.32 | 198.17 | 270.67 |
February | 282.00 | 0.63 | 0.61 | 01-FEB-07:30 | 11231.19 | 37.05 | 271.33 | 270.17 | 1467.45 | 22.34 | 139.67 | 251.33 |
March | 351.33 | 0.63 | 0.61 | 01-MAR-06:00 | 1834.68 | 17.25 | 10.67 | 321.17 | 1051.67 | 19.94 | 119.50 | 285.00 |
April | 381.83 | 0.64 | 0.61 | 01-APR-06:19 | 1466.51 | 17.26 | 0.00 | 342.83 | 882.96 | 20.23 | 120.50 | 309.83 |
May | 378.00 | 0.64 | 0.61 | 01-MAY-06:10 | 1125.58 | 16.51 | 0.00 | 358.83 | 695.22 | 19.54 | 56.67 | 314.17 |
June | 412.83 | 0.64 | 0.61 | 01-JUN-05:49 | 897.35 | 15.49 | 0.00 | 348.33 | 560.80 | 18.61 | 44.83 | 290.17 |
July | 395.33 | 0.63 | 0.61 | 01-JUL-06:30 | 1089.52 | 16.32 | 0.00 | 359.33 | 665.36 | 19.40 | 72.33 | 310.83 |
August | 408.83 | 0.64 | 0.61 | 01-AUG-05:00 | 1364.71 | 17.00 | 0.00 | 360.67 | 812.53 | 20.00 | 138.50 | 323.17 |
September | 359.33 | 0.63 | 0.61 | 01-SEP-06:19 | 1811.84 | 17.67 | 16.50 | 317.83 | 981.21 | 19.92 | 110.17 | 286.33 |
October | 329.00 | 0.63 | 0.61 | 01-OCT-06:40 | 5298.94 | 27.15 | 181.17 | 310.67 | 1319.51 | 20.17 | 87.00 | 294.33 |
November | 284.17 | 0.63 | 0.61 | 01-NOV-06:00 | 10214.51 | 36.78 | 266.00 | 276.17 | 2122.10 | 26.92 | 165.50 | 267.50 |
December | 265.67 | 0.64 | 0.61 | 01-DEC-07:49 | 10069.08 | 35.63 | 227.83 | 257.33 | 3247.09 | 30.79 | 173.83 | 255.33 |
Annual Sum or Average | 4149.83 | 0.63 | 4057.42 | 22.89 | 1243.00 | 3801.67 | 1233.08 | 21.64 | 1426.67 | 3458.67 | ||
Minimum of Months | 265.67 | 0.63 | 0.61 | 897.35 | 15.49 | 0.00 | 257.33 | 560.80 | 18.61 | 44.83 | 251.33 | |
Maximum of Months | 412.83 | 0.64 | 0.61 | 11231.19 | 37.05 | 271.33 | 360.67 | 3247.09 | 30.79 | 198.17 | 323.17 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.64 | 0.61 | 01-JAN-07:49 | 2112.05 | 18.59 | 85.33 | 241.33 | 1230.70 | 19.51 | 74.17 | 203.33 |
February | 282.00 | 0.64 | 0.61 | 01-FEB-07:19 | 2663.75 | 18.38 | 73.17 | 247.83 | 1568.35 | 19.30 | 67.83 | 211.00 |
March | 351.33 | 0.63 | 0.61 | 01-MAR-06:49 | 2753.19 | 15.56 | 55.17 | 308.00 | 1390.53 | 13.90 | 2.83 | 269.33 |
April | 381.83 | 0.63 | 0.61 | 01-APR-05:00 | 4065.75 | 15.54 | 54.83 | 345.33 | 1493.73 | 14.25 | 0.00 | 321.00 |
May | 378.00 | 0.64 | 0.61 | 01-MAY-05:00 | 3113.12 | 12.17 | 0.00 | 363.00 | 1766.49 | 13.72 | 0.00 | 326.50 |
June | 412.83 | 0.63 | 0.61 | 01-JUN-05:19 | 2945.49 | 11.21 | 0.00 | 368.67 | 1737.33 | 12.78 | 0.00 | 329.83 |
July | 395.33 | 0.63 | 0.61 | 01-JUL-06:19 | 2999.00 | 12.03 | 0.00 | 369.17 | 1600.20 | 13.57 | 0.00 | 334.33 |
August | 408.83 | 0.63 | 0.61 | 01-AUG-05:40 | 3738.42 | 12.82 | 5.50 | 370.00 | 1417.40 | 14.10 | 0.00 | 340.17 |
September | 359.33 | 0.63 | 0.61 | 01-SEP-05:00 | 3015.48 | 15.52 | 54.50 | 316.50 | 1771.16 | 14.22 | 5.50 | 287.67 |
October | 329.00 | 0.64 | 0.61 | 01-OCT-06:40 | 2795.36 | 17.55 | 82.67 | 280.83 | 1585.46 | 16.82 | 53.83 | 251.83 |
November | 284.17 | 0.64 | 0.61 | 01-NOV-06:49 | 2292.93 | 18.88 | 76.67 | 245.67 | 1205.26 | 18.41 | 52.67 | 214.17 |
December | 265.67 | 0.65 | 0.61 | 01-DEC-07:49 | 2452.65 | 19.11 | 80.33 | 223.17 | 1511.15 | 19.79 | 67.50 | 179.33 |
Annual Sum or Average | 4149.83 | 0.64 | 2968.99 | 15.23 | 568.17 | 3679.50 | 1535.31 | 15.51 | 324.33 | 3268.50 | ||
Minimum of Months | 265.67 | 0.63 | 0.61 | 2112.05 | 11.21 | 0.00 | 223.17 | 1205.26 | 12.78 | 0.00 | 179.33 | |
Maximum of Months | 412.83 | 0.65 | 0.61 | 4065.75 | 19.11 | 85.33 | 370.00 | 1771.16 | 19.79 | 74.17 | 340.17 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.66 | 0.61 | 01-JAN-08:00 | 499.04 | 0.00 | 0.00 | 205.83 | 323.19 | 0.00 | 0.00 | 119.00 |
February | 282.00 | 0.64 | 0.61 | 01-FEB-07:49 | 584.26 | 0.00 | 0.00 | 227.83 | 390.35 | 0.00 | 0.00 | 159.67 |
March | 351.33 | 0.64 | 0.61 | 01-MAR-07:10 | 703.73 | 0.00 | 0.00 | 296.50 | 442.59 | 0.00 | 0.00 | 228.50 |
April | 381.83 | 0.63 | 0.61 | 01-APR-06:10 | 881.33 | 0.00 | 0.00 | 355.33 | 564.97 | 0.00 | 0.00 | 324.00 |
May | 378.00 | 0.63 | 0.61 | 01-MAY-05:00 | 1039.53 | 0.00 | 0.00 | 383.33 | 598.72 | 0.00 | 0.00 | 337.67 |
June | 412.83 | 0.62 | 0.61 | 01-JUN-05:30 | 1079.03 | 0.00 | 0.00 | 393.33 | 566.53 | 0.00 | 0.00 | 359.50 |
July | 395.33 | 0.62 | 0.61 | 01-JUL-06:30 | 1056.35 | 0.00 | 0.00 | 386.83 | 606.33 | 0.00 | 0.00 | 358.50 |
August | 408.83 | 0.63 | 0.61 | 01-AUG-05:00 | 934.46 | 0.00 | 0.00 | 375.67 | 598.15 | 0.00 | 0.00 | 352.00 |
September | 359.33 | 0.63 | 0.61 | 01-SEP-06:19 | 740.59 | 0.00 | 0.00 | 311.17 | 477.91 | 0.00 | 0.00 | 255.50 |
October | 329.00 | 0.66 | 0.61 | 01-OCT-07:10 | 531.36 | 0.00 | 0.00 | 254.17 | 368.75 | 0.00 | 0.00 | 183.33 |
November | 284.17 | 0.65 | 0.61 | 01-NOV-07:19 | 523.40 | 0.00 | 0.00 | 224.17 | 354.08 | 0.00 | 0.00 | 149.17 |
December | 265.67 | 0.67 | 0.61 | 01-DEC-08:09 | 431.78 | 0.00 | 0.00 | 189.83 | 304.63 | 0.00 | 0.00 | 86.17 |
Annual Sum or Average | 4149.83 | 0.64 | 781.09 | 0.00 | 0.00 | 3604.00 | 481.41 | 0.00 | 0.00 | 2913.00 | ||
Minimum of Months | 265.67 | 0.62 | 0.61 | 431.78 | 0.00 | 0.00 | 189.83 | 304.63 | 0.00 | 0.00 | 86.17 | |
Maximum of Months | 412.83 | 0.67 | 0.61 | 1079.03 | 0.00 | 0.00 | 393.33 | 606.33 | 0.00 | 0.00 | 359.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.64 | 0.61 | 01-JAN-08:00 | 1614.22 | 16.60 | 56.83 | 245.83 | 927.85 | 17.85 | 54.17 | 204.83 |
February | 282.00 | 0.63 | 0.61 | 01-FEB-08:09 | 2678.64 | 18.65 | 74.33 | 246.50 | 1522.08 | 19.47 | 64.67 | 209.00 |
March | 351.33 | 0.63 | 0.61 | 01-MAR-07:19 | 2759.27 | 17.10 | 77.83 | 308.33 | 1073.40 | 13.98 | 2.67 | 268.50 |
April | 381.83 | 0.63 | 0.61 | 01-APR-06:40 | 3636.38 | 15.31 | 53.67 | 345.83 | 1368.67 | 14.28 | 0.00 | 319.17 |
May | 378.00 | 0.63 | 0.61 | 01-MAY-06:19 | 2557.22 | 12.29 | 0.00 | 374.17 | 1467.61 | 13.89 | 0.00 | 342.00 |
June | 412.83 | 0.63 | 0.61 | 01-JUN-05:00 | 2661.07 | 11.23 | 0.00 | 363.50 | 1612.50 | 12.80 | 0.00 | 327.83 |
July | 395.33 | 0.63 | 0.61 | 01-JUL-06:40 | 2602.57 | 12.16 | 0.00 | 369.67 | 1462.10 | 13.66 | 0.00 | 335.83 |
August | 408.83 | 0.63 | 0.61 | 01-AUG-06:19 | 2597.03 | 12.97 | 5.50 | 360.00 | 1373.24 | 14.24 | 0.00 | 332.17 |
September | 359.33 | 0.63 | 0.61 | 01-SEP-06:40 | 2898.36 | 15.49 | 56.50 | 317.50 | 1125.94 | 14.18 | 5.00 | 288.00 |
October | 329.00 | 0.64 | 0.61 | 01-OCT-07:19 | 2667.92 | 17.46 | 81.83 | 282.50 | 1406.09 | 16.99 | 56.00 | 246.83 |
November | 284.17 | 0.63 | 0.61 | 01-NOV-07:19 | 2518.10 | 19.09 | 78.50 | 254.17 | 1603.20 | 20.63 | 76.50 | 217.00 |
December | 265.67 | 0.65 | 0.61 | 01-DEC-08:09 | 2323.66 | 19.12 | 80.00 | 229.50 | 1492.96 | 21.00 | 78.33 | 188.17 |
Annual Sum or Average | 4149.83 | 0.64 | 2652.62 | 15.26 | 565.00 | 3697.50 | 1370.65 | 15.69 | 337.33 | 3279.33 | ||
Minimum of Months | 265.67 | 0.63 | 0.61 | 1614.22 | 11.23 | 0.00 | 229.50 | 927.85 | 12.80 | 0.00 | 188.17 | |
Maximum of Months | 412.83 | 0.65 | 0.61 | 3636.38 | 19.12 | 81.83 | 374.17 | 1612.50 | 21.00 | 78.33 | 342.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.63 | 0.61 | 01-JAN-07:49 | 8977.98 | 34.50 | 269.17 | 277.67 | 2236.05 | 23.58 | 126.83 | 271.33 |
February | 282.00 | 0.63 | 0.61 | 01-FEB-07:30 | 11228.38 | 36.67 | 270.50 | 269.67 | 1668.69 | 20.43 | 78.83 | 257.50 |
March | 351.33 | 0.63 | 0.61 | 01-MAR-06:00 | 1822.05 | 11.00 | 10.67 | 320.33 | 1099.42 | 15.62 | 3.50 | 286.83 |
April | 381.83 | 0.64 | 0.61 | 01-APR-06:19 | 1452.18 | 11.76 | 0.00 | 341.50 | 916.65 | 16.64 | 0.00 | 311.83 |
May | 378.00 | 0.64 | 0.61 | 01-MAY-06:10 | 1114.10 | 11.15 | 0.00 | 356.50 | 720.27 | 16.03 | 0.00 | 317.17 |
June | 412.83 | 0.64 | 0.61 | 01-JUN-05:49 | 888.96 | 9.92 | 0.00 | 345.83 | 581.38 | 14.96 | 0.00 | 295.00 |
July | 395.33 | 0.63 | 0.61 | 01-JUL-06:40 | 1076.70 | 10.81 | 0.00 | 357.50 | 688.67 | 15.76 | 0.00 | 314.33 |
August | 408.83 | 0.64 | 0.61 | 01-AUG-06:10 | 1348.65 | 11.49 | 0.00 | 358.83 | 841.52 | 16.34 | 0.00 | 325.67 |
September | 359.33 | 0.63 | 0.61 | 01-SEP-06:19 | 1804.93 | 11.85 | 16.50 | 317.00 | 1022.86 | 15.81 | 0.00 | 288.33 |
October | 329.00 | 0.63 | 0.61 | 01-OCT-06:40 | 5339.90 | 23.75 | 181.00 | 314.83 | 1380.17 | 15.56 | 14.67 | 295.67 |
November | 284.17 | 0.63 | 0.61 | 01-NOV-06:00 | 10208.80 | 36.16 | 265.83 | 275.50 | 2189.36 | 22.93 | 105.67 | 268.00 |
December | 265.67 | 0.64 | 0.61 | 01-DEC-07:49 | 10029.43 | 33.90 | 222.67 | 255.17 | 3324.66 | 27.49 | 146.67 | 255.33 |
Annual Sum or Average | 4149.83 | 0.63 | 4049.30 | 18.73 | 1236.33 | 3790.33 | 1285.98 | 17.95 | 476.17 | 3487.00 | ||
Minimum of Months | 265.67 | 0.63 | 0.61 | 888.96 | 9.92 | 0.00 | 255.17 | 581.38 | 14.96 | 0.00 | 255.33 | |
Maximum of Months | 412.83 | 0.64 | 0.61 | 11228.38 | 36.67 | 270.50 | 358.83 | 3324.66 | 27.49 | 146.67 | 325.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.64 | 0.61 | 01-JAN-07:49 | 2116.69 | 16.48 | 85.33 | 241.50 | 1125.71 | 15.81 | 55.33 | 205.50 |
February | 282.00 | 0.64 | 0.61 | 01-FEB-07:19 | 2669.23 | 16.20 | 73.17 | 247.83 | 1598.83 | 17.56 | 68.00 | 215.33 |
March | 351.33 | 0.63 | 0.61 | 01-MAR-06:49 | 2768.32 | 12.73 | 55.33 | 308.00 | 1428.74 | 11.24 | 2.83 | 273.17 |
April | 381.83 | 0.63 | 0.61 | 01-APR-05:00 | 3708.33 | 12.66 | 54.83 | 344.17 | 1538.89 | 11.68 | 0.00 | 323.17 |
May | 378.00 | 0.64 | 0.61 | 01-MAY-05:00 | 3104.93 | 8.60 | 0.00 | 362.67 | 1814.63 | 11.27 | 0.00 | 329.67 |
June | 412.83 | 0.63 | 0.61 | 01-JUN-05:19 | 2955.35 | 7.49 | 0.00 | 368.33 | 1782.37 | 10.28 | 0.00 | 333.33 |
July | 395.33 | 0.63 | 0.61 | 01-JUL-06:19 | 3000.95 | 8.39 | 0.00 | 367.83 | 1646.66 | 11.07 | 0.00 | 337.17 |
August | 408.83 | 0.63 | 0.61 | 01-AUG-05:40 | 3734.74 | 9.34 | 5.50 | 369.50 | 1459.95 | 11.60 | 0.00 | 342.00 |
September | 359.33 | 0.63 | 0.61 | 01-SEP-05:00 | 3028.44 | 12.69 | 54.50 | 316.17 | 1809.01 | 11.69 | 5.50 | 290.33 |
October | 329.00 | 0.64 | 0.61 | 01-OCT-06:40 | 2730.54 | 14.88 | 78.67 | 281.00 | 1623.22 | 14.80 | 53.83 | 256.83 |
November | 284.17 | 0.64 | 0.61 | 01-NOV-06:49 | 1970.91 | 14.43 | 54.50 | 246.00 | 1236.97 | 16.39 | 53.00 | 217.00 |
December | 265.67 | 0.65 | 0.61 | 01-DEC-07:49 | 2462.58 | 17.26 | 80.33 | 223.17 | 1498.87 | 17.62 | 63.67 | 185.00 |
Annual Sum or Average | 4149.83 | 0.64 | 2912.72 | 12.16 | 542.17 | 3676.17 | 1562.29 | 13.05 | 302.17 | 3308.50 | ||
Minimum of Months | 265.67 | 0.63 | 0.61 | 1970.91 | 7.49 | 0.00 | 223.17 | 1125.71 | 10.28 | 0.00 | 185.00 | |
Maximum of Months | 412.83 | 0.65 | 0.61 | 3734.74 | 17.26 | 85.33 | 369.50 | 1814.63 | 17.62 | 68.00 | 342.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.66 | 0.61 | 01-JAN-08:00 | 490.79 | 0.00 | 0.00 | 203.33 | 332.83 | 0.00 | 0.00 | 132.00 |
February | 282.00 | 0.65 | 0.61 | 01-FEB-07:00 | 576.03 | 0.00 | 0.00 | 226.17 | 402.45 | 0.00 | 0.00 | 167.67 |
March | 351.33 | 0.64 | 0.61 | 01-MAR-07:10 | 694.50 | 0.00 | 0.00 | 293.67 | 457.14 | 0.00 | 0.00 | 236.50 |
April | 381.83 | 0.63 | 0.61 | 01-APR-06:10 | 870.46 | 0.00 | 0.00 | 355.33 | 582.78 | 0.00 | 0.00 | 326.17 |
May | 378.00 | 0.63 | 0.61 | 01-MAY-05:00 | 1029.57 | 0.00 | 0.00 | 382.83 | 619.23 | 0.00 | 0.00 | 340.50 |
June | 412.83 | 0.62 | 0.61 | 01-JUN-05:30 | 1072.90 | 0.00 | 0.00 | 392.17 | 587.95 | 0.00 | 0.00 | 361.67 |
July | 395.33 | 0.62 | 0.61 | 01-JUL-06:30 | 1049.19 | 0.00 | 0.00 | 386.00 | 627.46 | 0.00 | 0.00 | 360.00 |
August | 408.83 | 0.63 | 0.61 | 01-AUG-05:49 | 941.60 | 0.00 | 0.00 | 377.50 | 616.60 | 0.00 | 0.00 | 354.67 |
September | 359.33 | 0.63 | 0.61 | 01-SEP-06:19 | 731.57 | 0.00 | 0.00 | 308.83 | 493.59 | 0.00 | 0.00 | 261.00 |
October | 329.00 | 0.66 | 0.61 | 01-OCT-07:10 | 526.13 | 0.00 | 0.00 | 252.33 | 381.13 | 0.00 | 0.00 | 192.33 |
November | 284.17 | 0.65 | 0.61 | 01-NOV-07:19 | 514.64 | 0.00 | 0.00 | 221.83 | 364.32 | 0.00 | 0.00 | 157.33 |
December | 265.67 | 0.67 | 0.61 | 01-DEC-08:09 | 424.89 | 0.00 | 0.00 | 186.33 | 313.53 | 0.00 | 0.00 | 102.00 |
Annual Sum or Average | 4149.83 | 0.64 | 774.42 | 0.00 | 0.00 | 3586.33 | 497.25 | 0.00 | 0.00 | 2991.83 | ||
Minimum of Months | 265.67 | 0.62 | 0.61 | 424.89 | 0.00 | 0.00 | 186.33 | 313.53 | 0.00 | 0.00 | 102.00 | |
Maximum of Months | 412.83 | 0.67 | 0.61 | 1072.90 | 0.00 | 0.00 | 392.17 | 627.46 | 0.00 | 0.00 | 361.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.64 | 0.61 | 01-JAN-08:00 | 1618.15 | 14.10 | 57.00 | 245.17 | 951.69 | 15.77 | 53.67 | 210.67 |
February | 282.00 | 0.64 | 0.61 | 01-FEB-08:09 | 2686.50 | 16.40 | 74.33 | 246.17 | 1404.13 | 15.79 | 48.00 | 212.17 |
March | 351.33 | 0.63 | 0.61 | 01-MAR-07:19 | 2770.45 | 14.67 | 78.00 | 307.50 | 1105.07 | 11.33 | 1.83 | 272.17 |
April | 381.83 | 0.63 | 0.61 | 01-APR-06:40 | 3642.18 | 12.47 | 53.67 | 344.33 | 1408.44 | 11.74 | 0.00 | 321.33 |
May | 378.00 | 0.63 | 0.61 | 01-MAY-06:19 | 2552.87 | 8.83 | 0.00 | 373.83 | 1508.07 | 11.46 | 0.00 | 344.83 |
June | 412.83 | 0.63 | 0.61 | 01-JUN-05:00 | 2668.58 | 7.58 | 0.00 | 363.50 | 1653.94 | 10.34 | 0.00 | 333.00 |
July | 395.33 | 0.63 | 0.61 | 01-JUL-06:40 | 2598.14 | 8.65 | 0.00 | 368.83 | 1501.86 | 11.26 | 0.00 | 338.50 |
August | 408.83 | 0.64 | 0.61 | 01-AUG-06:19 | 2584.46 | 9.59 | 5.50 | 359.00 | 1409.42 | 11.81 | 0.00 | 334.67 |
September | 359.33 | 0.63 | 0.61 | 01-SEP-06:40 | 2910.84 | 12.66 | 56.50 | 317.33 | 1163.53 | 11.64 | 5.00 | 292.00 |
October | 329.00 | 0.64 | 0.61 | 01-OCT-07:19 | 2683.67 | 15.24 | 81.83 | 282.33 | 1443.10 | 15.04 | 56.00 | 252.33 |
November | 284.17 | 0.63 | 0.61 | 01-NOV-07:19 | 2522.94 | 16.94 | 78.50 | 253.83 | 1632.78 | 18.92 | 76.67 | 220.83 |
December | 265.67 | 0.65 | 0.61 | 01-DEC-08:09 | 2333.81 | 17.25 | 80.00 | 229.33 | 1520.77 | 19.40 | 78.67 | 194.33 |
Annual Sum or Average | 4149.83 | 0.64 | 2656.92 | 12.42 | 565.33 | 3691.17 | 1395.87 | 13.31 | 319.83 | 3326.83 | ||
Minimum of Months | 265.67 | 0.63 | 0.61 | 1618.15 | 7.58 | 0.00 | 229.33 | 951.69 | 10.34 | 0.00 | 194.33 | |
Maximum of Months | 412.83 | 0.65 | 0.61 | 3642.18 | 17.25 | 81.83 | 373.83 | 1653.94 | 19.40 | 78.67 | 344.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.63 | 0.61 | 01-JAN-07:49 | 8977.10 | 34.48 | 269.17 | 277.67 | 2237.17 | 23.57 | 126.83 | 271.33 |
February | 282.00 | 0.63 | 0.61 | 01-FEB-07:30 | 11228.14 | 36.66 | 270.50 | 269.67 | 1669.91 | 20.42 | 78.83 | 257.50 |
March | 351.33 | 0.63 | 0.61 | 01-MAR-06:00 | 1822.70 | 10.96 | 10.67 | 320.17 | 1100.49 | 15.60 | 3.50 | 287.00 |
April | 381.83 | 0.64 | 0.61 | 01-APR-06:19 | 1452.62 | 11.72 | 0.00 | 341.50 | 917.48 | 16.62 | 0.00 | 312.00 |
May | 378.00 | 0.64 | 0.61 | 01-MAY-06:10 | 1114.29 | 11.11 | 0.00 | 356.50 | 720.87 | 16.01 | 0.00 | 317.17 |
June | 412.83 | 0.64 | 0.61 | 01-JUN-05:49 | 889.13 | 9.88 | 0.00 | 345.67 | 581.84 | 14.94 | 0.00 | 295.33 |
July | 395.33 | 0.63 | 0.61 | 01-JUL-06:40 | 1076.95 | 10.77 | 0.00 | 357.33 | 689.26 | 15.74 | 0.00 | 314.33 |
August | 408.83 | 0.64 | 0.61 | 01-AUG-06:10 | 1349.05 | 11.45 | 0.00 | 358.83 | 842.30 | 16.32 | 0.00 | 325.83 |
September | 359.33 | 0.63 | 0.61 | 01-SEP-06:19 | 1805.44 | 11.81 | 16.50 | 317.00 | 1023.78 | 15.79 | 0.00 | 288.33 |
October | 329.00 | 0.63 | 0.61 | 01-OCT-06:40 | 5340.02 | 23.72 | 181.00 | 314.83 | 1381.06 | 15.54 | 14.67 | 295.67 |
November | 284.17 | 0.63 | 0.61 | 01-NOV-06:00 | 10207.93 | 36.14 | 265.83 | 275.50 | 2190.51 | 22.92 | 105.67 | 268.00 |
December | 265.67 | 0.64 | 0.61 | 01-DEC-07:49 | 10028.15 | 33.88 | 222.67 | 255.17 | 3325.62 | 27.48 | 146.67 | 255.33 |
Annual Sum or Average | 4149.83 | 0.63 | 4049.33 | 18.70 | 1236.33 | 3789.83 | 1286.83 | 17.93 | 476.17 | 3487.83 | ||
Minimum of Months | 265.67 | 0.63 | 0.61 | 889.13 | 9.88 | 0.00 | 255.17 | 581.84 | 14.94 | 0.00 | 255.33 | |
Maximum of Months | 412.83 | 0.64 | 0.61 | 11228.14 | 36.66 | 270.50 | 358.83 | 3325.62 | 27.48 | 146.67 | 325.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.64 | 0.61 | 01-JAN-07:49 | 2116.38 | 16.47 | 85.33 | 241.33 | 1126.18 | 15.80 | 55.33 | 205.50 |
February | 282.00 | 0.64 | 0.61 | 01-FEB-07:19 | 2668.79 | 16.19 | 73.17 | 247.83 | 1599.40 | 17.55 | 68.00 | 215.33 |
March | 351.33 | 0.63 | 0.61 | 01-MAR-06:49 | 2768.04 | 12.72 | 55.33 | 308.00 | 1429.44 | 11.23 | 2.83 | 273.17 |
April | 381.83 | 0.63 | 0.61 | 01-APR-05:00 | 3707.81 | 12.65 | 54.83 | 344.17 | 1539.70 | 11.67 | 0.00 | 323.17 |
May | 378.00 | 0.64 | 0.61 | 01-MAY-05:00 | 3104.45 | 8.58 | 0.00 | 362.67 | 1815.36 | 11.26 | 0.00 | 329.67 |
June | 412.83 | 0.63 | 0.61 | 01-JUN-05:19 | 2955.02 | 7.47 | 0.00 | 368.33 | 1782.96 | 10.27 | 0.00 | 333.17 |
July | 395.33 | 0.63 | 0.61 | 01-JUL-06:19 | 2973.17 | 8.37 | 0.00 | 367.83 | 1647.34 | 11.06 | 0.00 | 337.33 |
August | 408.83 | 0.63 | 0.61 | 01-AUG-05:40 | 3425.20 | 9.32 | 5.50 | 369.33 | 1460.71 | 11.59 | 0.00 | 342.17 |
September | 359.33 | 0.63 | 0.61 | 01-SEP-05:00 | 3028.06 | 12.67 | 54.50 | 316.17 | 1809.70 | 11.68 | 5.50 | 290.33 |
October | 329.00 | 0.64 | 0.61 | 01-OCT-06:40 | 2730.05 | 14.87 | 78.67 | 281.00 | 1623.66 | 14.79 | 53.83 | 257.00 |
November | 284.17 | 0.64 | 0.61 | 01-NOV-06:49 | 1970.34 | 14.42 | 54.50 | 246.00 | 1237.43 | 16.38 | 53.00 | 217.00 |
December | 265.67 | 0.65 | 0.61 | 01-DEC-07:49 | 2462.11 | 17.25 | 80.33 | 223.17 | 1499.22 | 17.61 | 63.67 | 185.00 |
Annual Sum or Average | 4149.83 | 0.64 | 2879.24 | 12.15 | 542.17 | 3675.83 | 1562.91 | 13.04 | 302.17 | 3308.83 | ||
Minimum of Months | 265.67 | 0.63 | 0.61 | 1970.34 | 7.47 | 0.00 | 223.17 | 1126.18 | 10.27 | 0.00 | 185.00 | |
Maximum of Months | 412.83 | 0.65 | 0.61 | 3707.81 | 17.25 | 85.33 | 369.33 | 1815.36 | 17.61 | 68.00 | 342.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.66 | 0.61 | 01-JAN-08:00 | 490.65 | 0.00 | 0.00 | 203.00 | 333.06 | 0.00 | 0.00 | 132.00 |
February | 282.00 | 0.65 | 0.61 | 01-FEB-07:00 | 575.81 | 0.00 | 0.00 | 226.17 | 402.69 | 0.00 | 0.00 | 167.83 |
March | 351.33 | 0.64 | 0.61 | 01-MAR-07:10 | 694.46 | 0.00 | 0.00 | 293.67 | 457.50 | 0.00 | 0.00 | 236.67 |
April | 381.83 | 0.63 | 0.61 | 01-APR-06:10 | 870.26 | 0.00 | 0.00 | 355.33 | 583.18 | 0.00 | 0.00 | 326.33 |
May | 378.00 | 0.63 | 0.61 | 01-MAY-05:00 | 1029.43 | 0.00 | 0.00 | 382.83 | 619.68 | 0.00 | 0.00 | 340.67 |
June | 412.83 | 0.62 | 0.61 | 01-JUN-05:30 | 1072.84 | 0.00 | 0.00 | 392.17 | 588.38 | 0.00 | 0.00 | 361.83 |
July | 395.33 | 0.62 | 0.61 | 01-JUL-06:30 | 1049.11 | 0.00 | 0.00 | 386.00 | 627.92 | 0.00 | 0.00 | 360.17 |
August | 408.83 | 0.63 | 0.61 | 01-AUG-05:49 | 941.45 | 0.00 | 0.00 | 377.50 | 617.06 | 0.00 | 0.00 | 354.67 |
September | 359.33 | 0.63 | 0.61 | 01-SEP-06:19 | 731.43 | 0.00 | 0.00 | 308.67 | 493.94 | 0.00 | 0.00 | 261.00 |
October | 329.00 | 0.66 | 0.61 | 01-OCT-07:10 | 525.89 | 0.00 | 0.00 | 252.17 | 381.32 | 0.00 | 0.00 | 192.50 |
November | 284.17 | 0.65 | 0.61 | 01-NOV-07:19 | 514.37 | 0.00 | 0.00 | 221.83 | 364.52 | 0.00 | 0.00 | 157.83 |
December | 265.67 | 0.67 | 0.61 | 01-DEC-08:09 | 424.60 | 0.00 | 0.00 | 186.33 | 313.66 | 0.00 | 0.00 | 102.17 |
Annual Sum or Average | 4149.83 | 0.64 | 774.27 | 0.00 | 0.00 | 3585.67 | 497.59 | 0.00 | 0.00 | 2993.67 | ||
Minimum of Months | 265.67 | 0.62 | 0.61 | 424.60 | 0.00 | 0.00 | 186.33 | 313.66 | 0.00 | 0.00 | 102.17 | |
Maximum of Months | 412.83 | 0.67 | 0.61 | 1072.84 | 0.00 | 0.00 | 392.17 | 627.92 | 0.00 | 0.00 | 361.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 301.50 | 0.64 | 0.61 | 01-JAN-08:00 | 1617.80 | 14.09 | 57.00 | 245.17 | 952.17 | 15.76 | 53.67 | 210.67 |
February | 282.00 | 0.64 | 0.61 | 01-FEB-08:09 | 2686.01 | 16.39 | 74.33 | 246.17 | 1404.69 | 15.79 | 48.00 | 212.33 |
March | 351.33 | 0.63 | 0.61 | 01-MAR-07:19 | 2770.28 | 14.65 | 78.00 | 307.50 | 1105.77 | 11.32 | 1.83 | 272.33 |
April | 381.83 | 0.63 | 0.61 | 01-APR-06:40 | 3641.92 | 12.45 | 53.67 | 344.33 | 1409.17 | 11.73 | 0.00 | 321.33 |
May | 378.00 | 0.63 | 0.61 | 01-MAY-06:19 | 2552.60 | 8.82 | 0.00 | 373.83 | 1508.77 | 11.45 | 0.00 | 344.83 |
June | 412.83 | 0.63 | 0.61 | 01-JUN-05:00 | 2668.37 | 7.56 | 0.00 | 363.50 | 1654.56 | 10.33 | 0.00 | 333.17 |
July | 395.33 | 0.63 | 0.61 | 01-JUL-06:40 | 2597.97 | 8.63 | 0.00 | 368.83 | 1502.62 | 11.25 | 0.00 | 338.67 |
August | 408.83 | 0.64 | 0.61 | 01-AUG-06:19 | 2584.27 | 9.57 | 5.50 | 359.00 | 1410.30 | 11.80 | 0.00 | 335.00 |
September | 359.33 | 0.63 | 0.61 | 01-SEP-06:40 | 2910.54 | 12.65 | 56.50 | 317.33 | 1164.26 | 11.63 | 5.00 | 292.00 |
October | 329.00 | 0.64 | 0.61 | 01-OCT-07:19 | 2683.15 | 15.23 | 81.83 | 282.33 | 1443.56 | 15.03 | 56.00 | 252.33 |
November | 284.17 | 0.63 | 0.61 | 01-NOV-07:19 | 2522.44 | 16.93 | 78.50 | 253.17 | 1633.24 | 18.91 | 76.67 | 220.83 |
December | 265.67 | 0.65 | 0.61 | 01-DEC-08:09 | 2333.37 | 17.23 | 80.00 | 229.33 | 1521.10 | 19.40 | 78.67 | 194.50 |
Annual Sum or Average | 4149.83 | 0.64 | 2656.61 | 12.41 | 565.33 | 3690.50 | 1396.50 | 13.30 | 319.83 | 3328.00 | ||
Minimum of Months | 265.67 | 0.63 | 0.61 | 1617.80 | 7.56 | 0.00 | 229.33 | 952.17 | 10.33 | 0.00 | 194.50 | |
Maximum of Months | 412.83 | 0.65 | 0.61 | 3641.92 | 17.23 | 81.83 | 373.83 | 1654.56 | 19.40 | 78.67 | 344.83 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.525521E+10 | 24950.72 | 21-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.267017E+10 | 22408.06 | 04-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.429437E+09 | 12979.14 | 04-MAR-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 18439097.88 | 4801.67 | 08-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 154134.71 | 259.27 | 06-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.294605E+09 | 15370.35 | 26-OCT-06:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.507675E+09 | 15192.51 | 27-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.322473E+10 | 23821.64 | 15-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.124004E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.525521E+10 | 24950.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 64411148.64 | 8915.81 | 17-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 26720675.79 | 12892.49 | 06-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 8658897.70 | 1076.11 | 23-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 99790722.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 64411148.64 | 12892.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.141834E+09 | 11035.54 | 21-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 45563519.74 | 11081.17 | 04-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1098372.03 | 1873.45 | 04-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 2603787.76 | 1214.20 | 26-OCT-05:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 2764031.88 | 763.61 | 28-NOV-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 92244793.74 | 11045.49 | 15-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.286108E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.141834E+09 | 11081.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.119914E+09 | 15532.00 | 19-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 41514541.51 | 15741.65 | 06-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1130875.68 | 1557.13 | 04-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3002444.34 | 1157.91 | 26-OCT-05:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 52545.18 | 45.67 | 27-NOV-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 38873783.49 | 15596.89 | 22-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.204489E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.119914E+09 | 15741.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 7260207.09 | 1230.43 | 17-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 7260207.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7260207.09 | 1230.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.870987E+11 | 272117.50 | 21-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.508052E+11 | 245301.30 | 04-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.119999E+11 | 154157.05 | 04-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.181584E+10 | 95202.88 | 08-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.129472E+09 | 25066.62 | 06-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.735494E+10 | 175572.13 | 26-OCT-06:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.190909E+11 | 210669.14 | 27-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.846007E+11 | 269423.88 | 15-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.262896E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.870987E+11 | 272117.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.219332E+11 | 132959.99 | 20-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.130470E+11 | 133345.06 | 13-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.284343E+10 | 143834.99 | 11-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.119172E+09 | 121828.03 | 08-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.876912E+09 | 144064.47 | 27-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.521685E+10 | 140960.44 | 30-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.226782E+11 | 132975.21 | 09-DEC-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.667148E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.226782E+11 | 144064.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.138919E+11 | 154171.02 | 21-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.701375E+10 | 154468.50 | 04-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.144528E+10 | 152246.24 | 04-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 61250540.94 | 60743.80 | 08-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.761022E+09 | 155593.87 | 26-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.269737E+10 | 152420.99 | 28-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.127293E+11 | 154296.61 | 15-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.385999E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.138919E+11 | 155593.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.694183E+10 | 163440.81 | 19-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.362041E+10 | 163154.44 | 06-FEB-05:24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.604282E+09 | 162279.76 | 06-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 52030234.39 | 46718.41 | 08-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.293797E+09 | 175113.58 | 26-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.436401E+09 | 162495.70 | 25-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.558558E+10 | 163673.66 | 04-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.175343E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.694183E+10 | 175113.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.113517E+11 | 154836.70 | 21-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.632984E+10 | 155142.88 | 04-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.149346E+10 | 152898.43 | 04-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 29749795.43 | 7111.63 | 24-APR-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2116007.09 | 1684.57 | 05-MAY-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.568992E+09 | 130070.26 | 26-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.223314E+10 | 153073.67 | 28-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.104046E+11 | 154977.85 | 15-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.324136E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.113517E+11 | 155142.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.113667E+11 | 32703.15 | 21-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.723979E+10 | 30446.16 | 04-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.236312E+10 | 20647.82 | 04-MAR-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.506443E+09 | 13915.08 | 08-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 64549006.57 | 6041.55 | 06-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.152823E+10 | 22845.15 | 26-OCT-06:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.353847E+10 | 26790.22 | 27-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.118593E+11 | 33492.92 | 15-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.384666E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.118593E+11 | 33492.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.352264E+10 | 78318.35 | 19-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.161439E+10 | 78052.31 | 06-FEB-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.136684E+09 | 77356.83 | 06-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 33413310.90 | 28299.39 | 26-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.721824E+09 | 78008.83 | 27-NOV-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.319297E+10 | 78498.32 | 26-DEC-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.922192E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.352264E+10 | 78498.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.628647E+10 | 15501.87 | 02-JAN-05:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.417760E+10 | 15504.42 | 02-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.155843E+10 | 15471.74 | 06-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.253052E+09 | 15345.46 | 08-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 40980923.74 | 15349.48 | 05-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.662222E+09 | 15484.44 | 23-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.258162E+10 | 15488.00 | 06-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.650886E+10 | 15493.50 | 04-DEC-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.220692E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.650886E+10 | 15504.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.338935E+10 | 17005.70 | 19-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.206656E+10 | 16998.09 | 08-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.753070E+09 | 16895.37 | 04-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 86273474.09 | 16851.37 | 08-APR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 15235949.70 | 8691.15 | 05-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.362431E+09 | 16849.26 | 25-OCT-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.118383E+10 | 16872.53 | 22-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.327374E+10 | 17020.06 | 27-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.111305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.338935E+10 | 17020.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.269683E+10 | 18417.96 | 19-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.168775E+10 | 18424.47 | 27-FEB-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.816695E+09 | 18386.79 | 06-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.171386E+09 | 18188.37 | 08-APR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 53532045.17 | 17612.96 | 05-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1069327.09 | 540.93 | 09-JUN-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.312294E+09 | 18267.23 | 26-OCT-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.758788E+09 | 18388.97 | 28-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.231947E+10 | 18426.16 | 04-DEC-05:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.881781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.269683E+10 | 18426.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.309084E+10 | 18684.08 | 30-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.196670E+10 | 18808.53 | 04-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.843466E+09 | 18488.67 | 04-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.117715E+09 | 10277.25 | 06-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 36587766.43 | 10654.77 | 05-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4357457.86 | 1058.61 | 09-JUN-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.368819E+09 | 18262.56 | 26-OCT-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.109250E+10 | 18598.00 | 27-NOV-05:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.291137E+10 | 18763.69 | 22-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.104324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.309084E+10 | 18808.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS HEATING COIL
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT HEATING COIL
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT HEATING COIL
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID HEATING COIL
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP HEATING COIL
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID_SUPPHEATCOIL
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.888480E+09 | 0.888480E+09 | 21959.34 | 05-JAN-14:10 | 21959.34 | 0.00 |
February | 0.00 | 0.00 | 0.303259E+10 | 0.303259E+10 | 69498.26 | 14-FEB-16:00 | 69498.26 | 0.00 |
March | 0.00 | 0.00 | 0.962673E+10 | 0.962673E+10 | 75933.74 | 08-MAR-16:00 | 75933.74 | 0.00 |
April | 0.00 | 0.00 | 0.372508E+11 | 0.372508E+11 | 111205.87 | 28-APR-14:50 | 111205.87 | 0.00 |
May | 0.00 | 0.00 | 0.551812E+11 | 0.551812E+11 | 112035.50 | 30-MAY-14:30 | 112035.50 | 0.05 |
June | 0.00 | 0.00 | 0.108359E+12 | 0.108356E+12 | 153547.36 | 29-JUN-05:02 | 141574.91 | 0.27 |
July | 0.00 | 0.00 | 0.139648E+12 | 0.135936E+12 | 152451.87 | 01-JUL-05:02 | 66861.84 | 0.77 |
August | 0.00 | 0.00 | 0.149756E+12 | 0.145025E+12 | 162084.80 | 23-AUG-16:00 | 97318.93 | 0.82 |
September | 0.00 | 0.00 | 0.796856E+11 | 0.786256E+11 | 159002.77 | 05-SEP-13:10 | 96730.60 | 0.39 |
October | 0.00 | 0.00 | 0.380108E+11 | 0.379890E+11 | 111108.18 | 10-OCT-16:00 | 111108.18 | 0.09 |
November | 0.00 | 0.00 | 0.236245E+10 | 0.236245E+10 | 36778.65 | 02-NOV-15:00 | 36778.65 | 0.00 |
December | 0.00 | 0.00 | 334315.88 | 334315.88 | 2778.26 | 24-DEC-14:22 | 2778.26 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.623803E+12 | 0.614275E+12 | 0.20 | |||
Minimum of Months | 0.00 | 0.00 | 334315.88 | 334315.88 | 2778.26 | 2778.26 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.149756E+12 | 0.145025E+12 | 162084.80 | 141574.91 | 0.82 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.757867E+10 | 0.757867E+10 | 191057.64 | 05-JAN-15:20 | 191057.64 | 0.00 |
February | 0.00 | 0.00 | 0.242953E+11 | 0.242953E+11 | 560842.86 | 14-FEB-16:00 | 560842.86 | 0.00 |
March | 0.00 | 0.00 | 0.692741E+11 | 0.692741E+11 | 581327.61 | 08-MAR-16:00 | 581327.61 | 0.00 |
April | 0.00 | 0.00 | 0.261490E+12 | 0.261490E+12 | 902042.46 | 13-APR-15:20 | 902042.46 | 0.00 |
May | 0.00 | 0.00 | 0.476331E+12 | 0.476331E+12 | 1019118.74 | 19-MAY-15:20 | 1019118.74 | 0.06 |
June | 0.00 | 0.00 | 0.926766E+12 | 0.926723E+12 | 1435347.13 | 29-JUN-05:02 | 1318385.25 | 0.25 |
July | 0.00 | 0.00 | 0.112765E+13 | 0.110337E+13 | 1393813.00 | 01-JUL-05:02 | 608254.82 | 0.62 |
August | 0.00 | 0.00 | 0.106652E+13 | 0.104455E+13 | 1420620.07 | 14-AUG-05:02 | 693164.28 | 0.64 |
September | 0.00 | 0.00 | 0.692859E+12 | 0.683600E+12 | 1393804.32 | 05-SEP-13:00 | 832682.13 | 0.37 |
October | 0.00 | 0.00 | 0.312349E+12 | 0.312194E+12 | 963742.65 | 06-OCT-15:30 | 963742.65 | 0.08 |
November | 0.00 | 0.00 | 0.167196E+11 | 0.167196E+11 | 299589.49 | 02-NOV-15:00 | 299589.49 | 0.00 |
December | 0.00 | 0.00 | 550465.02 | 550465.02 | 2336.16 | 24-DEC-13:53 | 2336.16 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.498184E+13 | 0.492612E+13 | 0.17 | |||
Minimum of Months | 0.00 | 0.00 | 550465.02 | 550465.02 | 2336.16 | 2336.16 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.112765E+13 | 0.110337E+13 | 1435347.13 | 1318385.25 | 0.64 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.308942E+09 | 0.308942E+09 | 12268.69 | 05-JAN-14:20 | 12268.69 | 0.00 |
February | 0.00 | 0.00 | 0.197302E+10 | 0.197302E+10 | 52697.47 | 14-FEB-16:00 | 52697.47 | 0.00 |
March | 0.00 | 0.00 | 0.588773E+10 | 0.588773E+10 | 60148.27 | 08-MAR-16:00 | 60148.27 | 0.00 |
April | 0.00 | 0.00 | 0.275848E+11 | 0.275848E+11 | 109539.40 | 26-APR-14:50 | 109539.40 | 0.00 |
May | 0.00 | 0.00 | 0.523500E+11 | 0.523500E+11 | 124975.45 | 19-MAY-15:20 | 124975.45 | 0.05 |
June | 0.00 | 0.00 | 0.106331E+12 | 0.106328E+12 | 156804.16 | 28-JUN-14:50 | 156804.16 | 0.25 |
July | 0.00 | 0.00 | 0.130452E+12 | 0.127745E+12 | 167423.49 | 16-JUL-14:51 | 130778.56 | 0.63 |
August | 0.00 | 0.00 | 0.121634E+12 | 0.119335E+12 | 154990.60 | 14-AUG-05:02 | 75832.02 | 0.64 |
September | 0.00 | 0.00 | 0.753027E+11 | 0.745847E+11 | 147800.76 | 05-SEP-13:30 | 95159.80 | 0.35 |
October | 0.00 | 0.00 | 0.312635E+11 | 0.312635E+11 | 110927.30 | 06-OCT-15:20 | 110927.30 | 0.08 |
November | 0.00 | 0.00 | 0.104216E+10 | 0.104216E+10 | 25371.88 | 02-NOV-15:00 | 25371.88 | 0.00 |
December | 0.00 | 0.00 | 285.62 | 285.62 | 0.30 | 16-DEC-14:20 | 0.30 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.554130E+12 | 0.548403E+12 | 0.17 | |||
Minimum of Months | 0.00 | 0.00 | 285.62 | 285.62 | 0.30 | 0.30 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.130452E+12 | 0.127745E+12 | 167423.49 | 156804.16 | 0.64 |
Report: CoilReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 1944765.30 | 1944765.30 | 1039.11 | 02-JAN-15:00 | 1039.11 | 0.00 |
February | 0.00 | 0.00 | 0.126643E+10 | 0.126643E+10 | 41489.85 | 13-FEB-16:00 | 41489.85 | 0.00 |
March | 0.00 | 0.00 | 0.341756E+10 | 0.341756E+10 | 43396.92 | 08-MAR-16:00 | 43396.92 | 0.00 |
April | 0.00 | 0.00 | 0.189055E+11 | 0.189055E+11 | 62024.19 | 17-APR-15:00 | 62024.19 | 0.00 |
May | 0.00 | 0.00 | 0.329603E+11 | 0.329583E+11 | 96894.53 | 29-MAY-16:20 | 96894.53 | 0.03 |
June | 0.00 | 0.00 | 0.609459E+11 | 0.609323E+11 | 87075.33 | 29-JUN-05:04 | 80693.54 | 0.20 |
July | 0.00 | 0.00 | 0.741519E+11 | 0.730896E+11 | 132244.41 | 02-JUL-19:00 | 83472.72 | 0.50 |
August | 0.00 | 0.00 | 0.772154E+11 | 0.759345E+11 | 108083.52 | 27-AUG-14:20 | 90726.51 | 0.55 |
September | 0.00 | 0.00 | 0.495564E+11 | 0.488051E+11 | 102011.51 | 05-SEP-13:00 | 67421.89 | 0.29 |
October | 0.00 | 0.00 | 0.226805E+11 | 0.226771E+11 | 98022.33 | 01-OCT-14:56 | 98022.33 | 0.08 |
November | 0.00 | 0.00 | 0.505839E+09 | 0.505839E+09 | 23884.18 | 09-NOV-14:00 | 23884.18 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.341608E+12 | 0.338494E+12 | 0.14 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.772154E+11 | 0.759345E+11 | 132244.41 | 98022.33 | 0.55 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.395471E+12 | 0.346223E+12 | 152161.14 | 01-JAN-18:00 | 133027.03 | 0.00 |
February | 0.00 | 0.00 | 0.610891E+12 | 0.535683E+12 | 257548.52 | 24-FEB-22:03 | 224946.40 | 0.00 |
March | 0.00 | 0.00 | 0.956854E+12 | 0.843246E+12 | 460589.85 | 31-MAR-24:00 | 404561.06 | 0.00 |
April | 0.00 | 0.00 | 0.119141E+13 | 0.104932E+13 | 478633.84 | 29-APR-02:45 | 412420.75 | 0.00 |
May | 0.00 | 0.00 | 0.398284E+12 | 0.355289E+12 | 246158.57 | 31-MAY-24:00 | 220347.55 | 0.00 |
June | 0.00 | 0.00 | 0.637742E+12 | 0.584394E+12 | 340747.25 | 30-JUN-24:00 | 312310.63 | 0.00 |
July | 0.00 | 0.00 | 0.912110E+12 | 0.851363E+12 | 437468.65 | 31-JUL-24:00 | 396580.57 | 0.00 |
August | 0.00 | 0.00 | 0.120949E+13 | 0.107715E+13 | 477540.35 | 31-AUG-05:55 | 411047.36 | 0.00 |
September | 0.00 | 0.00 | 0.389014E+12 | 0.348503E+12 | 248565.40 | 30-SEP-24:00 | 220982.78 | 0.00 |
October | 0.00 | 0.00 | 0.679505E+12 | 0.602541E+12 | 357743.79 | 31-OCT-24:00 | 314102.88 | 0.00 |
November | 0.00 | 0.00 | 0.934649E+12 | 0.819018E+12 | 365091.62 | 12-NOV-15:42 | 318567.97 | 0.00 |
December | 0.00 | 0.00 | 0.125057E+13 | 0.108715E+13 | 474053.44 | 24-DEC-16:50 | 408340.28 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.956599E+13 | 0.849988E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.389014E+12 | 0.346223E+12 | 152161.14 | 133027.03 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.125057E+13 | 0.108715E+13 | 478633.84 | 412420.75 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.465683E+10 | 0.465626E+10 | 2739.57 | 01-JAN-16:45 | 2732.76 | 0.00 |
February | 0.00 | 0.00 | 0.920797E+10 | 0.920510E+10 | 4821.74 | 15-FEB-17:00 | 4821.74 | 0.00 |
March | 0.00 | 0.00 | 0.157697E+11 | 0.157656E+11 | 7764.25 | 31-MAR-24:00 | 7764.25 | 0.00 |
April | 0.00 | 0.00 | 0.206312E+11 | 0.206310E+11 | 8805.55 | 15-APR-18:00 | 8805.55 | 0.00 |
May | 0.00 | 0.00 | 0.615226E+10 | 0.611664E+10 | 4158.90 | 31-MAY-24:00 | 4158.90 | 0.00 |
June | 0.00 | 0.00 | 0.111856E+11 | 0.111089E+11 | 6000.69 | 30-JUN-23:55 | 5992.67 | 0.00 |
July | 0.00 | 0.00 | 0.167929E+11 | 0.165970E+11 | 7898.97 | 31-JUL-24:00 | 7898.97 | 0.00 |
August | 0.00 | 0.00 | 0.221938E+11 | 0.219816E+11 | 8839.76 | 23-AUG-16:00 | 8447.69 | 0.00 |
September | 0.00 | 0.00 | 0.626699E+10 | 0.613363E+10 | 4162.74 | 30-SEP-24:00 | 4162.74 | 0.00 |
October | 0.00 | 0.00 | 0.110983E+11 | 0.110504E+11 | 5959.68 | 31-OCT-24:00 | 5959.68 | 0.00 |
November | 0.00 | 0.00 | 0.151993E+11 | 0.151895E+11 | 6764.14 | 05-NOV-16:35 | 6764.14 | 0.00 |
December | 0.00 | 0.00 | 0.205332E+11 | 0.205331E+11 | 8647.90 | 31-DEC-16:35 | 8647.90 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.159688E+12 | 0.158969E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.465683E+10 | 0.465626E+10 | 2739.57 | 2732.76 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.221938E+11 | 0.219816E+11 | 8839.76 | 8805.55 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.270774E+11 | 0.270715E+11 | 24318.51 | 26-JAN-17:00 | 24318.51 | 0.00 |
February | 0.00 | 0.00 | 0.741894E+11 | 0.741603E+11 | 45188.43 | 15-FEB-17:00 | 45188.43 | 0.00 |
March | 0.00 | 0.00 | 0.140280E+12 | 0.140237E+12 | 71602.95 | 31-MAR-23:50 | 71602.95 | 0.00 |
April | 0.00 | 0.00 | 0.191030E+12 | 0.191028E+12 | 82578.83 | 16-APR-18:23 | 82578.83 | 0.00 |
May | 0.00 | 0.00 | 0.549846E+11 | 0.546319E+11 | 39397.27 | 31-MAY-24:00 | 39397.27 | 0.00 |
June | 0.00 | 0.00 | 0.105373E+12 | 0.104608E+12 | 58044.68 | 30-JUN-23:55 | 57954.79 | 0.00 |
July | 0.00 | 0.00 | 0.160079E+12 | 0.158121E+12 | 76134.38 | 31-JUL-23:57 | 76134.38 | 0.00 |
August | 0.00 | 0.00 | 0.207220E+12 | 0.205091E+12 | 82636.76 | 23-AUG-16:00 | 78720.40 | 0.00 |
September | 0.00 | 0.00 | 0.568634E+11 | 0.555457E+11 | 39390.54 | 30-SEP-24:00 | 39390.54 | 0.00 |
October | 0.00 | 0.00 | 0.989303E+11 | 0.984531E+11 | 54635.74 | 31-OCT-24:00 | 54635.74 | 0.00 |
November | 0.00 | 0.00 | 0.132061E+12 | 0.131962E+12 | 62693.33 | 02-NOV-16:40 | 62040.32 | 0.00 |
December | 0.00 | 0.00 | 0.175523E+12 | 0.175522E+12 | 77432.00 | 29-DEC-16:40 | 77432.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.142361E+13 | 0.141643E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.270774E+11 | 0.270715E+11 | 24318.51 | 24318.51 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.207220E+12 | 0.205091E+12 | 82636.76 | 82578.83 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.115165E+10 | 0.115116E+10 | 2338.19 | 26-JAN-17:00 | 2338.19 | 0.00 |
February | 0.00 | 0.00 | 0.593354E+10 | 0.593075E+10 | 4541.62 | 15-FEB-17:00 | 4541.62 | 0.00 |
March | 0.00 | 0.00 | 0.129775E+11 | 0.129733E+11 | 6795.57 | 31-MAR-23:20 | 6795.57 | 0.00 |
April | 0.00 | 0.00 | 0.186663E+11 | 0.186662E+11 | 8397.80 | 16-APR-18:04 | 8397.80 | 0.00 |
May | 0.00 | 0.00 | 0.531123E+10 | 0.527619E+10 | 3900.50 | 31-MAY-24:00 | 3900.50 | 0.00 |
June | 0.00 | 0.00 | 0.105825E+11 | 0.105061E+11 | 5822.09 | 30-JUN-23:55 | 5812.95 | 0.00 |
July | 0.00 | 0.00 | 0.161539E+11 | 0.159583E+11 | 7606.23 | 31-JUL-23:57 | 7606.23 | 0.00 |
August | 0.00 | 0.00 | 0.208385E+11 | 0.206255E+11 | 8352.67 | 23-AUG-16:00 | 7960.83 | 0.00 |
September | 0.00 | 0.00 | 0.561212E+10 | 0.548049E+10 | 3934.94 | 30-SEP-24:00 | 3934.94 | 0.00 |
October | 0.00 | 0.00 | 0.923469E+10 | 0.918716E+10 | 5240.75 | 31-OCT-23:50 | 5240.75 | 0.00 |
November | 0.00 | 0.00 | 0.117182E+11 | 0.117084E+11 | 6261.63 | 02-NOV-16:40 | 6196.01 | 0.00 |
December | 0.00 | 0.00 | 0.155572E+11 | 0.155570E+11 | 7665.17 | 29-DEC-16:40 | 7665.17 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.133737E+12 | 0.133021E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.115165E+10 | 0.115116E+10 | 2338.19 | 2338.19 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.208385E+11 | 0.206255E+11 | 8397.80 | 8397.80 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 65551.16 | 1093392.98 | 10-JAN-06:01 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 41917.67 | 1098001.93 | 27-FEB-06:01 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 9359.02 | 1108390.62 | 06-MAR-06:01 |
April | 0.00 | 0.00 | 01-APR-00:10 | 1236.31 | 409213.80 | 08-APR-05:03 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 124.23 | 94295.97 | 05-MAY-05:02 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 1.86 | 1283.05 | 09-JUN-05:20 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 4970.68 | 1052037.29 | 26-OCT-05:02 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 15317.98 | 1052445.09 | 28-NOV-06:01 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 62691.28 | 1141531.72 | 04-DEC-05:01 |
Annual Sum or Average | 0.00 | 16695.80 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 65551.16 | 1141531.72 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 8732.04 | 459552.12 | 05-JAN-15:00 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 26039.58 | 1113155.98 | 13-FEB-15:10 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 66530.78 | 1190065.70 | 08-MAR-16:40 | 0.01 | 102.37 | 26-MAR-18:47 |
April | 215252.78 | 1241636.09 | 28-APR-13:30 | 8.66 | 40838.41 | 01-APR-21:13 |
May | 347443.85 | 1367962.76 | 23-MAY-12:10 | 375.17 | 408135.48 | 28-MAY-07:12 |
June | 596036.63 | 1713931.34 | 29-JUN-05:02 | 127.02 | 125592.95 | 14-JUN-02:23 |
July | 696919.09 | 1654866.43 | 31-JUL-15:00 | 1.60 | 14743.08 | 13-JUL-01:53 |
August | 674408.59 | 2003551.79 | 14-AUG-05:03 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 477751.82 | 1818485.64 | 05-SEP-13:10 | 115.68 | 291071.49 | 17-SEP-07:23 |
October | 232769.54 | 1446761.73 | 02-OCT-11:50 | 161.35 | 426458.17 | 01-OCT-07:03 |
November | 18767.77 | 759613.50 | 02-NOV-15:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 2779.70 | 48340.47 | 01-DEC-06:05 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 281864.30 | 66.36 | ||||
Minimum of Months | 2779.70 | 48340.47 | 0.00 | 0.00 | ||
Maximum of Months | 696919.09 | 2003551.79 | 375.17 | 426458.17 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 4635.41 | 320549.47 | 05-JAN-15:00 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 17216.11 | 948162.18 | 14-FEB-16:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 41768.63 | 950693.60 | 08-MAR-14:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 157704.53 | 1289246.32 | 28-APR-13:30 | 0.00 | 0.00 | 01-APR-00:10 |
May | 266315.09 | 1475946.85 | 22-MAY-05:02 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 507001.51 | 2589773.87 | 29-JUN-05:02 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 598045.64 | 2925142.63 | 01-JUL-05:02 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 590144.76 | 2940998.78 | 14-AUG-05:02 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 402362.71 | 2266066.11 | 05-SEP-05:03 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 186434.42 | 1591619.91 | 02-OCT-10:50 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 11143.26 | 581793.87 | 02-NOV-15:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 0.53 | 4470.82 | 24-DEC-14:22 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 233249.56 | 0.00 | ||||
Minimum of Months | 0.53 | 4470.82 | 0.00 | 0.00 | ||
Maximum of Months | 598045.64 | 2940998.78 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 204985.63 | 234384.22 | 05-JAN-16:00 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 374707.59 | 834828.90 | 14-FEB-16:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 581272.87 | 1121798.36 | 08-MAR-16:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 929211.09 | 1570011.02 | 13-APR-17:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 416944.58 | 1034574.41 | 19-MAY-16:00 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 906215.09 | 1834405.70 | 28-JUN-16:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 1297648.93 | 2054973.02 | 22-JUL-15:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 1472841.60 | 2122606.83 | 20-AUG-16:00 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 504530.88 | 1178906.84 | 03-SEP-14:00 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 518286.50 | 1223305.11 | 01-OCT-16:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 541747.97 | 918713.71 | 09-NOV-14:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 680137.31 | 808520.33 | 24-DEC-15:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 704872.89 | 0.00 | ||||
Minimum of Months | 204985.63 | 234384.22 | 0.00 | 0.00 | ||
Maximum of Months | 1472841.60 | 2122606.83 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15593.41 | 52438.63 | 31-JAN-12:25 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 15792.33 | 52467.82 | 02-FEB-12:10 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 16304.79 | 51979.09 | 01-MAR-12:50 |
April | 0.00 | 0.00 | 01-APR-00:10 | 14628.61 | 49717.74 | 03-APR-11:30 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 14122.54 | 46849.34 | 01-MAY-12:00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13496.07 | 43470.63 | 01-JUN-11:50 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11972.12 | 40727.90 | 03-JUL-12:00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 12848.02 | 40024.65 | 31-AUG-11:40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 12507.10 | 41939.13 | 29-SEP-11:40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 13236.11 | 45164.90 | 31-OCT-12:00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14335.47 | 48447.44 | 30-NOV-12:20 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14697.56 | 51017.89 | 29-DEC-12:40 |
Annual Sum or Average | 0.00 | 14118.39 | ||||
Minimum of Months | 0.00 | 0.00 | 11972.12 | 40024.65 | ||
Maximum of Months | 0.00 | 0.00 | 16304.79 | 52467.82 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 3083.76 | 290712.95 | 05-JAN-15:00 | 1706.18 | 135988.31 | 31-JAN-16:10 |
February | 13893.93 | 827606.99 | 14-FEB-16:30 | 3214.89 | 131383.28 | 03-FEB-12:40 |
March | 38726.95 | 843601.34 | 08-MAR-16:00 | 1981.16 | 128715.01 | 18-MAR-05:30 |
April | 167116.00 | 1998897.77 | 26-APR-12:50 | 2699.50 | 115770.97 | 15-APR-13:40 |
May | 298262.48 | 2212069.32 | 19-MAY-15:20 | 698.48 | 97779.35 | 16-MAY-07:00 |
June | 634413.34 | 2266464.81 | 29-JUN-11:40 | 712.06 | 87193.43 | 19-JUN-06:30 |
July | 752647.48 | 3019272.83 | 31-JUL-15:00 | 124.90 | 26405.43 | 19-JUL-01:40 |
August | 728932.64 | 2551712.95 | 21-AUG-14:00 | 535.45 | 37913.69 | 06-AUG-05:20 |
September | 495645.50 | 3042284.10 | 05-SEP-13:10 | 447.31 | 66205.60 | 30-SEP-06:00 |
October | 208789.32 | 2133115.70 | 03-OCT-12:10 | 1430.13 | 115756.34 | 12-OCT-10:40 |
November | 8588.77 | 454043.06 | 02-NOV-15:10 | 1835.71 | 133966.13 | 16-NOV-10:20 |
December | 134.44 | 25383.40 | 06-DEC-13:20 | 3144.64 | 136140.95 | 14-DEC-13:20 |
Annual Sum or Average | 280848.84 | 1531.79 | ||||
Minimum of Months | 134.44 | 25383.40 | 124.90 | 26405.43 | ||
Maximum of Months | 752647.48 | 3042284.10 | 3214.89 | 136140.95 |
Report: FanReportMonthly
For: CAV_BAS FAN
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.169051E+11 | 0.98 | 10963.13 | 01-JAN-00:15 | 1.69 |
February | 0.151006E+11 | 0.96 | 10963.13 | 01-FEB-05:01 | 1.70 |
March | 0.175783E+11 | 1.01 | 10963.13 | 01-MAR-05:02 | 1.69 |
April | 0.164611E+11 | 0.98 | 10963.13 | 01-APR-04:03 | 1.70 |
May | 0.176231E+11 | 1.01 | 10963.13 | 01-MAY-00:05 | 1.69 |
June | 0.174829E+11 | 1.03 | 10963.13 | 01-JUN-03:02 | 1.68 |
July | 0.176319E+11 | 1.00 | 10963.13 | 01-JUL-03:02 | 1.67 |
August | 0.195268E+11 | 1.11 | 10963.13 | 01-AUG-03:02 | 1.68 |
September | 0.180434E+11 | 1.07 | 10963.13 | 01-SEP-03:02 | 1.67 |
October | 0.183923E+11 | 1.06 | 10963.13 | 01-OCT-13:58 | 1.68 |
November | 0.168934E+11 | 1.01 | 10963.13 | 01-NOV-03:02 | 1.69 |
December | 0.168947E+11 | 0.98 | 10963.13 | 01-DEC-04:10 | 1.69 |
Annual Sum or Average | 0.208534E+12 | 1.02 | |||
Minimum of Months | 0.151006E+11 | 0.96 | 10963.13 | 1.67 | |
Maximum of Months | 0.195268E+11 | 1.11 | 10963.13 | 1.70 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.499857E+10 | 0.40 | 12863.16 | 17-JAN-06:01 | 1.46 |
February | 0.540338E+10 | 0.43 | 13791.66 | 06-FEB-06:01 | 1.52 |
March | 0.848712E+10 | 0.54 | 13230.48 | 13-MAR-15:10 | 1.48 |
April | 0.122390E+11 | 0.71 | 18714.98 | 28-APR-14:50 | 1.84 |
May | 0.102765E+11 | 0.60 | 23276.84 | 22-MAY-05:02 | 2.09 |
June | 0.135754E+11 | 0.75 | 23888.01 | 15-JUN-05:02 | 2.13 |
July | 0.156465E+11 | 0.82 | 23888.01 | 01-JUL-05:02 | 2.12 |
August | 0.191869E+11 | 0.94 | 23888.01 | 07-AUG-05:02 | 2.12 |
September | 0.103064E+11 | 0.60 | 23510.96 | 05-SEP-05:03 | 2.10 |
October | 0.883804E+10 | 0.54 | 23888.01 | 02-OCT-05:02 | 2.12 |
November | 0.734022E+10 | 0.49 | 13338.08 | 24-NOV-16:00 | 1.49 |
December | 0.677635E+10 | 0.46 | 12547.71 | 22-DEC-06:01 | 1.43 |
Annual Sum or Average | 0.123074E+12 | 0.61 | |||
Minimum of Months | 0.499857E+10 | 0.40 | 12547.71 | 1.43 | |
Maximum of Months | 0.191869E+11 | 0.94 | 23888.01 | 2.13 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.349659E+11 | 0.37 | 99368.04 | 06-JAN-06:02 | 1.30 |
February | 0.344365E+11 | 0.37 | 131544.57 | 22-FEB-06:02 | 1.54 |
March | 0.485237E+11 | 0.42 | 105085.31 | 11-MAR-06:03 | 1.35 |
April | 0.662192E+11 | 0.48 | 132884.69 | 13-APR-15:10 | 1.55 |
May | 0.807920E+11 | 0.54 | 221712.69 | 22-MAY-05:02 | 2.12 |
June | 0.107385E+12 | 0.65 | 221712.69 | 15-JUN-05:02 | 2.13 |
July | 0.117470E+12 | 0.66 | 221712.69 | 03-JUL-05:02 | 2.13 |
August | 0.118053E+12 | 0.67 | 221712.69 | 03-AUG-05:02 | 2.12 |
September | 0.803422E+11 | 0.54 | 213839.25 | 01-SEP-05:03 | 2.08 |
October | 0.592281E+11 | 0.45 | 151228.25 | 02-OCT-05:02 | 1.67 |
November | 0.413387E+11 | 0.38 | 106706.43 | 30-NOV-06:03 | 1.36 |
December | 0.352912E+11 | 0.36 | 98962.46 | 02-DEC-06:02 | 1.30 |
Annual Sum or Average | 0.824046E+12 | 0.49 | |||
Minimum of Months | 0.344365E+11 | 0.36 | 98962.46 | 1.30 | |
Maximum of Months | 0.118053E+12 | 0.67 | 221712.69 | 2.13 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.361846E+10 | 0.39 | 5105.69 | 02-JAN-05:01 | 0.84 |
February | 0.321160E+10 | 0.37 | 7279.77 | 15-FEB-16:40 | 1.02 |
March | 0.400427E+10 | 0.39 | 7723.54 | 08-MAR-16:20 | 1.06 |
April | 0.589053E+10 | 0.43 | 15380.14 | 28-APR-14:40 | 1.60 |
May | 0.774934E+10 | 0.50 | 16968.41 | 19-MAY-15:20 | 1.69 |
June | 0.116310E+11 | 0.64 | 24483.57 | 27-JUN-15:50 | 2.13 |
July | 0.131206E+11 | 0.67 | 24483.09 | 01-JUL-05:02 | 2.12 |
August | 0.128980E+11 | 0.66 | 24483.57 | 07-AUG-05:02 | 2.12 |
September | 0.802188E+10 | 0.51 | 16760.61 | 12-SEP-16:00 | 1.67 |
October | 0.511379E+10 | 0.40 | 15623.24 | 02-OCT-05:02 | 1.60 |
November | 0.348096E+10 | 0.36 | 7074.47 | 01-NOV-15:50 | 1.00 |
December | 0.356330E+10 | 0.38 | 5105.69 | 04-DEC-05:01 | 0.84 |
Annual Sum or Average | 0.823037E+11 | 0.48 | |||
Minimum of Months | 0.321160E+10 | 0.36 | 5105.69 | 0.84 | |
Maximum of Months | 0.131206E+11 | 0.67 | 24483.57 | 2.13 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BASEMENT SUPPLY FAN
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.114711E+12 | 1.63 | 42828.27 | 01-JAN-00:10 | 1.63 |
February | 0.103610E+12 | 1.63 | 42828.27 | 01-FEB-00:10 | 1.63 |
March | 0.114711E+12 | 1.63 | 42828.27 | 01-MAR-00:10 | 1.63 |
April | 0.111011E+12 | 1.63 | 42828.27 | 01-APR-00:10 | 1.63 |
May | 0.114711E+12 | 1.63 | 42828.27 | 01-MAY-00:05 | 1.63 |
June | 0.111011E+12 | 1.63 | 42828.27 | 01-JUN-00:10 | 1.63 |
July | 0.114711E+12 | 1.63 | 42828.27 | 01-JUL-00:10 | 1.63 |
August | 0.114711E+12 | 1.63 | 42828.27 | 01-AUG-00:03 | 1.63 |
September | 0.111011E+12 | 1.63 | 42828.27 | 01-SEP-00:10 | 1.63 |
October | 0.114711E+12 | 1.63 | 42828.27 | 01-OCT-00:10 | 1.63 |
November | 0.111011E+12 | 1.63 | 42828.27 | 01-NOV-00:10 | 1.63 |
December | 0.114711E+12 | 1.63 | 42828.27 | 01-DEC-00:10 | 1.63 |
Annual Sum or Average | 0.135063E+13 | 1.63 | |||
Minimum of Months | 0.103610E+12 | 1.63 | 42828.27 | 1.63 | |
Maximum of Months | 0.114711E+12 | 1.63 | 42828.27 | 1.63 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BOT SUPPLY FAN
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.174190E+10 | 1.12 | 650.35 | 01-JAN-00:05 | 1.11 |
February | 0.157333E+10 | 1.12 | 650.35 | 01-FEB-00:10 | 1.12 |
March | 0.174190E+10 | 1.12 | 650.35 | 01-MAR-00:10 | 1.12 |
April | 0.168571E+10 | 1.12 | 650.35 | 01-APR-00:10 | 1.12 |
May | 0.174190E+10 | 1.11 | 650.35 | 01-MAY-00:05 | 1.12 |
June | 0.168571E+10 | 1.11 | 650.35 | 01-JUN-00:10 | 1.12 |
July | 0.174190E+10 | 1.11 | 650.35 | 01-JUL-00:10 | 1.11 |
August | 0.174190E+10 | 1.11 | 650.35 | 01-AUG-00:03 | 1.11 |
September | 0.168571E+10 | 1.11 | 650.35 | 01-SEP-00:05 | 1.11 |
October | 0.174190E+10 | 1.11 | 650.35 | 01-OCT-00:10 | 1.11 |
November | 0.168571E+10 | 1.12 | 650.35 | 01-NOV-00:10 | 1.12 |
December | 0.174190E+10 | 1.12 | 650.35 | 01-DEC-00:10 | 1.12 |
Annual Sum or Average | 0.205095E+11 | 1.11 | |||
Minimum of Months | 0.157333E+10 | 1.11 | 650.35 | 1.11 | |
Maximum of Months | 0.174190E+10 | 1.12 | 650.35 | 1.12 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER MID SUPPLY FAN
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.166277E+11 | 1.12 | 6208.08 | 01-JAN-00:05 | 1.11 |
February | 0.150186E+11 | 1.12 | 6208.08 | 01-FEB-00:20 | 1.12 |
March | 0.166277E+11 | 1.12 | 6208.08 | 01-MAR-00:10 | 1.12 |
April | 0.160914E+11 | 1.12 | 6208.08 | 01-APR-00:10 | 1.12 |
May | 0.166277E+11 | 1.11 | 6208.08 | 01-MAY-00:05 | 1.12 |
June | 0.160914E+11 | 1.11 | 6208.08 | 01-JUN-00:10 | 1.12 |
July | 0.166277E+11 | 1.11 | 6208.08 | 01-JUL-00:10 | 1.11 |
August | 0.166277E+11 | 1.11 | 6208.08 | 01-AUG-00:03 | 1.11 |
September | 0.160914E+11 | 1.11 | 6208.08 | 01-SEP-00:05 | 1.11 |
October | 0.166277E+11 | 1.11 | 6208.08 | 01-OCT-00:10 | 1.11 |
November | 0.160914E+11 | 1.12 | 6208.08 | 01-NOV-00:10 | 1.12 |
December | 0.166277E+11 | 1.12 | 6208.08 | 01-DEC-00:10 | 1.12 |
Annual Sum or Average | 0.195778E+12 | 1.11 | |||
Minimum of Months | 0.150186E+11 | 1.11 | 6208.08 | 1.11 | |
Maximum of Months | 0.166277E+11 | 1.12 | 6208.08 | 1.12 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER TOP SUPPLY FAN
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.169926E+10 | 1.12 | 634.43 | 01-JAN-00:05 | 1.11 |
February | 0.153482E+10 | 1.12 | 634.43 | 01-FEB-00:10 | 1.12 |
March | 0.169926E+10 | 1.12 | 634.43 | 01-MAR-00:10 | 1.12 |
April | 0.164445E+10 | 1.12 | 634.43 | 01-APR-00:10 | 1.12 |
May | 0.169926E+10 | 1.11 | 634.43 | 01-MAY-00:05 | 1.12 |
June | 0.164445E+10 | 1.11 | 634.43 | 01-JUN-00:10 | 1.12 |
July | 0.169926E+10 | 1.11 | 634.43 | 01-JUL-00:10 | 1.11 |
August | 0.169926E+10 | 1.11 | 634.43 | 01-AUG-00:03 | 1.11 |
September | 0.164445E+10 | 1.11 | 634.43 | 01-SEP-00:05 | 1.11 |
October | 0.169926E+10 | 1.11 | 634.43 | 01-OCT-00:10 | 1.11 |
November | 0.164445E+10 | 1.12 | 634.43 | 01-NOV-00:10 | 1.12 |
December | 0.169926E+10 | 1.12 | 634.43 | 01-DEC-00:10 | 1.12 |
Annual Sum or Average | 0.200075E+11 | 1.11 | |||
Minimum of Months | 0.153482E+10 | 1.11 | 634.43 | 1.11 | |
Maximum of Months | 0.169926E+10 | 1.12 | 634.43 | 1.12 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.772301E+09 | 0.695071E+09 | 3625.86 | 17-JAN-06:01 | 3263.27 | 3263.27 | 47.79 | 5.98 |
February | 0.444717E+09 | 0.400245E+09 | 3622.25 | 06-FEB-06:01 | 3260.02 | 3260.02 | 46.70 | 5.97 |
March | 0.107189E+09 | 96470271.35 | 3554.65 | 06-MAR-06:01 | 3199.19 | 3199.19 | 35.68 | 5.78 |
April | 13614457.48 | 12253011.73 | 1652.53 | 08-APR-05:03 | 1487.28 | 1487.28 | 30.78 | 1.96 |
May | 1399801.52 | 1259821.37 | 386.22 | 05-MAY-05:02 | 347.60 | 347.60 | 24.59 | 0.41 |
June | 20271.03 | 18243.93 | 5.39 | 09-JUN-05:20 | 4.85 | 4.85 | 23.83 | 0.01 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 23.74 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 23.74 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 23.74 | 0.00 |
October | 56610274.81 | 50949247.33 | 3487.40 | 26-OCT-05:02 | 3138.66 | 3138.66 | 36.33 | 5.57 |
November | 0.172367E+09 | 0.155130E+09 | 3544.28 | 28-NOV-06:01 | 3189.85 | 3189.85 | 37.59 | 5.74 |
December | 0.736260E+09 | 0.662634E+09 | 3597.40 | 26-DEC-06:01 | 3237.66 | 3237.66 | 42.25 | 5.90 |
Annual Sum or Average | 0.230448E+10 | 0.207403E+10 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.74 | 0.00 | |
Maximum of Months | 0.772301E+09 | 0.695071E+09 | 3625.86 | 3263.27 | 3263.27 | 47.79 | 5.98 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 4592804.92 | 4133524.43 | 173.55 | 05-JAN-15:00 | 156.19 | 156.19 | 8.90 | 10.88 |
February | 33691759.71 | 30322583.74 | 1288.98 | 14-FEB-15:40 | 1160.08 | 1160.08 | 7.91 | 29.46 |
March | 51177626.56 | 46059863.90 | 1214.89 | 08-MAR-14:00 | 1093.40 | 1093.40 | 7.82 | 28.68 |
April | 0.245034E+09 | 0.220530E+09 | 1800.49 | 28-APR-13:30 | 1620.45 | 1620.45 | 7.37 | 34.27 |
May | 0.536086E+09 | 0.482478E+09 | 10501.82 | 22-MAY-05:02 | 9451.63 | 9451.63 | 8.54 | 72.33 |
June | 0.229111E+10 | 0.206200E+10 | 18967.56 | 29-JUN-05:02 | 17070.81 | 17070.81 | 7.70 | 91.50 |
July | 0.256061E+10 | 0.230455E+10 | 18967.56 | 01-JUL-05:02 | 17070.81 | 17070.81 | 8.31 | 91.50 |
August | 0.289460E+10 | 0.260514E+10 | 18967.56 | 14-AUG-05:02 | 17070.81 | 17070.81 | 8.26 | 91.50 |
September | 0.244061E+10 | 0.219655E+10 | 18518.12 | 01-SEP-05:03 | 16666.30 | 16666.30 | 8.52 | 90.63 |
October | 0.876307E+09 | 0.788676E+09 | 13022.70 | 02-OCT-11:50 | 11720.43 | 11720.43 | 7.17 | 78.85 |
November | 12227572.78 | 11004815.50 | 595.70 | 02-NOV-15:00 | 536.13 | 536.13 | 9.12 | 20.48 |
December | 222.49 | 200.24 | 0.71 | 24-DEC-14:22 | 0.64 | 0.64 | 8.56 | 0.16 |
Annual Sum or Average | 0.119460E+11 | 0.107514E+11 | ||||||
Minimum of Months | 222.49 | 200.24 | 0.71 | 0.64 | 0.64 | 7.17 | 0.16 | |
Maximum of Months | 0.289460E+10 | 0.260514E+10 | 18967.56 | 17070.81 | 17070.81 | 9.12 | 91.50 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.331773E+10 | 0.298596E+10 | 13054.86 | 01-JAN-09:00 | 11749.38 | 11749.38 | 8.47 | 91.50 |
February | 0.471750E+10 | 0.424575E+10 | 13054.86 | 01-FEB-12:40 | 11749.38 | 11749.38 | 8.43 | 91.50 |
March | 0.728116E+10 | 0.655305E+10 | 13054.86 | 01-MAR-16:30 | 11749.38 | 11749.38 | 8.47 | 91.50 |
April | 0.142113E+11 | 0.127901E+11 | 13054.86 | 01-APR-05:02 | 11749.38 | 11749.38 | 8.44 | 91.50 |
May | 0.176936E+11 | 0.159242E+11 | 13054.86 | 01-MAY-03:02 | 11749.38 | 11749.38 | 8.70 | 91.50 |
June | 0.256302E+11 | 0.230672E+11 | 13054.86 | 01-JUN-03:02 | 11749.38 | 11749.38 | 8.75 | 91.50 |
July | 0.308081E+11 | 0.277273E+11 | 13054.86 | 01-JUL-00:12 | 11749.38 | 11749.38 | 7.50 | 91.50 |
August | 0.319262E+11 | 0.287336E+11 | 13054.86 | 01-AUG-00:03 | 11749.38 | 11749.38 | 7.74 | 91.50 |
September | 0.217504E+11 | 0.195753E+11 | 13054.86 | 01-SEP-00:05 | 11749.38 | 11749.38 | 7.61 | 91.50 |
October | 0.142194E+11 | 0.127974E+11 | 13054.86 | 01-OCT-07:03 | 11749.38 | 11749.38 | 7.26 | 91.50 |
November | 0.426045E+10 | 0.383441E+10 | 13054.86 | 01-NOV-09:50 | 11749.38 | 11749.38 | 8.57 | 91.50 |
December | 0.419281E+10 | 0.377353E+10 | 13054.86 | 01-DEC-06:05 | 11749.38 | 11749.38 | 8.50 | 91.50 |
Annual Sum or Average | 0.180009E+12 | 0.162008E+12 | ||||||
Minimum of Months | 0.331773E+10 | 0.298596E+10 | 13054.86 | 11749.38 | 11749.38 | 7.26 | 91.50 | |
Maximum of Months | 0.319262E+11 | 0.287336E+11 | 13054.86 | 11749.38 | 11749.38 | 8.75 | 91.50 |
Report: PumpReportMonthly
For: PLANT CIRC PUMP
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.995257E+10 | 0.895731E+10 | 3715.86 | 01-JAN-00:05 | 3344.28 | 3344.28 | 22.18 | 15.52 |
February | 0.898942E+10 | 0.809048E+10 | 3715.86 | 01-FEB-00:10 | 3344.28 | 3344.28 | 24.66 | 15.52 |
March | 0.995257E+10 | 0.895731E+10 | 3715.86 | 01-MAR-00:10 | 3344.28 | 3344.28 | 27.64 | 15.52 |
April | 0.963152E+10 | 0.866837E+10 | 3715.86 | 01-APR-00:10 | 3344.28 | 3344.28 | 30.85 | 15.52 |
May | 0.995257E+10 | 0.895731E+10 | 3715.86 | 01-MAY-00:05 | 3344.28 | 3344.28 | 23.09 | 15.52 |
June | 0.963152E+10 | 0.866837E+10 | 3715.86 | 01-JUN-00:10 | 3344.28 | 3344.28 | 29.60 | 15.52 |
July | 0.995257E+10 | 0.895731E+10 | 3715.86 | 01-JUL-00:10 | 3344.28 | 3344.28 | 37.83 | 15.52 |
August | 0.995257E+10 | 0.895731E+10 | 3715.86 | 01-AUG-00:03 | 3344.28 | 3344.28 | 41.10 | 15.52 |
September | 0.963152E+10 | 0.866837E+10 | 3715.86 | 01-SEP-00:05 | 3344.28 | 3344.28 | 29.83 | 15.52 |
October | 0.995257E+10 | 0.895731E+10 | 3715.86 | 01-OCT-00:10 | 3344.28 | 3344.28 | 28.47 | 15.52 |
November | 0.963152E+10 | 0.866837E+10 | 3715.86 | 01-NOV-00:10 | 3344.28 | 3344.28 | 28.32 | 15.52 |
December | 0.995257E+10 | 0.895731E+10 | 3715.86 | 01-DEC-00:10 | 3344.28 | 3344.28 | 30.50 | 15.52 |
Annual Sum or Average | 0.117183E+12 | 0.105465E+12 | ||||||
Minimum of Months | 0.898942E+10 | 0.809048E+10 | 3715.86 | 3344.28 | 3344.28 | 22.18 | 15.52 | |
Maximum of Months | 0.995257E+10 | 0.895731E+10 | 3715.86 | 3344.28 | 3344.28 | 41.10 | 15.52 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 11967951.72 | 3590385.52 | 5.96 | 01-JAN-06:05 | 1.79 | 1.79 | 55.69 | 0.44 |
February | 10809762.85 | 3242928.85 | 5.96 | 01-FEB-06:01 | 1.79 | 1.79 | 55.73 | 0.44 |
March | 11967951.72 | 3590385.52 | 5.96 | 01-MAR-06:03 | 1.79 | 1.79 | 56.35 | 0.44 |
April | 11581888.76 | 3474566.63 | 5.96 | 01-APR-05:02 | 1.79 | 1.79 | 55.66 | 0.44 |
May | 11967951.72 | 3590385.52 | 5.96 | 01-MAY-05:02 | 1.79 | 1.79 | 56.00 | 0.44 |
June | 11581888.76 | 3474566.63 | 5.96 | 01-JUN-05:03 | 1.79 | 1.79 | 56.36 | 0.44 |
July | 11967951.72 | 3590385.52 | 5.96 | 01-JUL-05:02 | 1.79 | 1.79 | 56.13 | 0.44 |
August | 11967951.72 | 3590385.52 | 5.96 | 01-AUG-05:03 | 1.79 | 1.79 | 56.66 | 0.44 |
September | 11581888.76 | 3474566.63 | 5.96 | 01-SEP-05:03 | 1.79 | 1.79 | 56.00 | 0.44 |
October | 11967951.72 | 3590385.52 | 5.96 | 01-OCT-05:10 | 1.79 | 1.79 | 56.05 | 0.44 |
November | 11581888.76 | 3474566.63 | 5.96 | 01-NOV-05:03 | 1.79 | 1.79 | 56.76 | 0.44 |
December | 11967951.72 | 3590385.52 | 5.96 | 01-DEC-06:03 | 1.79 | 1.79 | 56.49 | 0.44 |
Annual Sum or Average | 0.140913E+09 | 42273893.99 | ||||||
Minimum of Months | 10809762.85 | 3242928.85 | 5.96 | 1.79 | 1.79 | 55.66 | 0.44 | |
Maximum of Months | 11967951.72 | 3590385.52 | 5.96 | 1.79 | 1.79 | 56.76 | 0.44 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.413377E+10 | 0.372039E+10 | 16280.14 | 05-JAN-15:00 | 14652.12 | 14652.12 | 22.38 | 54.19 |
February | 0.589842E+10 | 0.530858E+10 | 32567.28 | 13-FEB-15:10 | 29310.55 | 29310.55 | 22.67 | 108.37 |
March | 0.914179E+10 | 0.822761E+10 | 32571.15 | 08-MAR-15:30 | 29314.04 | 29314.04 | 22.84 | 108.37 |
April | 0.194668E+11 | 0.175201E+11 | 32635.77 | 26-APR-12:50 | 29372.19 | 29372.19 | 25.51 | 108.37 |
May | 0.256324E+11 | 0.230692E+11 | 32648.64 | 19-MAY-15:20 | 29383.78 | 29383.78 | 25.98 | 108.37 |
June | 0.418760E+11 | 0.376884E+11 | 32651.93 | 29-JUN-11:40 | 29386.74 | 29386.74 | 26.10 | 108.37 |
July | 0.512655E+11 | 0.461389E+11 | 32697.49 | 31-JUL-15:00 | 29427.74 | 29427.74 | 27.77 | 108.37 |
August | 0.523719E+11 | 0.471347E+11 | 32669.18 | 21-AUG-14:00 | 29402.26 | 29402.26 | 26.73 | 108.37 |
September | 0.344910E+11 | 0.310419E+11 | 32698.88 | 05-SEP-13:10 | 29428.99 | 29428.99 | 27.82 | 108.37 |
October | 0.200305E+11 | 0.180275E+11 | 32643.87 | 03-OCT-12:10 | 29379.49 | 29379.49 | 25.81 | 108.37 |
November | 0.530903E+10 | 0.477812E+10 | 16288.58 | 02-NOV-15:10 | 14659.73 | 14659.73 | 23.10 | 54.19 |
December | 0.522343E+10 | 0.470108E+10 | 16266.43 | 06-DEC-13:20 | 14639.79 | 14639.79 | 21.21 | 54.19 |
Annual Sum or Average | 0.274840E+12 | 0.247356E+12 | ||||||
Minimum of Months | 0.413377E+10 | 0.372039E+10 | 16266.43 | 14639.79 | 14639.79 | 21.21 | 54.19 | |
Maximum of Months | 0.523719E+11 | 0.471347E+11 | 32698.88 | 29428.99 | 29428.99 | 27.82 | 108.37 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 33.88 | 33.88 | 65551.16 | 1093392.98 | 10-JAN-06:01 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 31.46 | 31.46 | 41917.67 | 1098001.93 | 27-FEB-06:01 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 24.79 | 24.79 | 9359.02 | 1108390.62 | 06-MAR-06:01 |
April | 0.00 | 0.00 | 01-APR-00:10 | 24.67 | 24.67 | 1236.31 | 409213.80 | 08-APR-05:03 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 25.24 | 25.24 | 124.23 | 94295.97 | 05-MAY-05:02 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 23.85 | 23.85 | 1.86 | 1283.05 | 09-JUN-05:20 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 23.74 | 23.74 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 23.74 | 23.74 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 23.74 | 23.74 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 23.74 | 23.74 | 4970.68 | 1052037.29 | 26-OCT-05:02 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.14 | 25.14 | 15317.98 | 1052445.09 | 28-NOV-06:01 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 24.14 | 24.14 | 62691.28 | 1141531.72 | 04-DEC-05:01 |
Annual Sum or Average | 0.00 | 16695.80 | ||||||
Minimum of Months | 0.00 | 0.00 | 23.74 | 23.74 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 33.88 | 33.88 | 65551.16 | 1141531.72 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 8732.04 | 459552.12 | 05-JAN-15:00 | 9.49 | 8.88 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 26039.58 | 1113155.98 | 13-FEB-15:10 | 10.43 | 8.96 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 66530.78 | 1190065.70 | 08-MAR-16:40 | 10.45 | 8.78 | 0.01 | 102.37 | 26-MAR-18:47 |
April | 215252.78 | 1241636.09 | 28-APR-13:30 | 10.28 | 7.05 | 8.66 | 40838.41 | 01-APR-21:13 |
May | 347443.85 | 1367962.76 | 23-MAY-12:10 | 10.54 | 6.97 | 375.17 | 408135.48 | 28-MAY-07:12 |
June | 596036.63 | 1713931.34 | 29-JUN-05:02 | 11.52 | 7.05 | 127.02 | 125592.95 | 14-JUN-02:23 |
July | 696919.09 | 1654866.43 | 31-JUL-15:00 | 11.02 | 6.70 | 1.60 | 14743.08 | 13-JUL-01:53 |
August | 674408.59 | 2003551.79 | 14-AUG-05:03 | 13.10 | 7.87 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 477751.82 | 1818485.64 | 05-SEP-13:10 | 11.85 | 7.11 | 115.68 | 291071.49 | 17-SEP-07:23 |
October | 232769.54 | 1446761.73 | 02-OCT-11:50 | 10.76 | 6.98 | 161.35 | 426458.17 | 01-OCT-07:03 |
November | 18767.77 | 759613.50 | 02-NOV-15:00 | 10.11 | 9.10 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 2779.70 | 48340.47 | 01-DEC-06:05 | 8.50 | 8.43 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 281864.30 | 66.36 | ||||||
Minimum of Months | 2779.70 | 48340.47 | 8.50 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 696919.09 | 2003551.79 | 13.10 | 9.10 | 375.17 | 426458.17 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 4635.41 | 320549.47 | 05-JAN-15:00 | 13.74 | 8.89 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 17216.11 | 948162.18 | 14-FEB-16:00 | 14.43 | 8.44 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 41768.63 | 950693.60 | 08-MAR-14:00 | 14.62 | 8.37 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 157704.53 | 1289246.32 | 28-APR-13:30 | 15.69 | 7.05 | 0.00 | 0.00 | 01-APR-00:10 |
May | 266315.09 | 1475946.85 | 22-MAY-05:02 | 11.57 | 8.66 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 507001.51 | 2589773.87 | 29-JUN-05:02 | 13.46 | 7.45 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 598045.64 | 2925142.63 | 01-JUL-05:02 | 14.34 | 8.17 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 590144.76 | 2940998.78 | 14-AUG-05:02 | 14.38 | 8.05 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 402362.71 | 2266066.11 | 05-SEP-05:03 | 12.99 | 8.36 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 186434.42 | 1591619.91 | 02-OCT-10:50 | 11.54 | 7.17 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 11143.26 | 581793.87 | 02-NOV-15:00 | 13.49 | 9.12 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 0.53 | 4470.82 | 24-DEC-14:22 | 13.30 | 8.40 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 233249.56 | 0.00 | ||||||
Minimum of Months | 0.53 | 4470.82 | 11.54 | 7.05 | 0.00 | 0.00 | ||
Maximum of Months | 598045.64 | 2940998.78 | 15.69 | 9.12 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 204985.63 | 234384.22 | 05-JAN-16:00 | 22.67 | 18.47 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 374707.59 | 834828.90 | 14-FEB-16:00 | 33.64 | 26.37 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 581272.87 | 1121798.36 | 08-MAR-16:00 | 38.80 | 28.66 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 929211.09 | 1570011.02 | 13-APR-17:00 | 46.76 | 33.72 | 0.00 | 0.00 | 01-APR-00:10 |
May | 416944.58 | 1034574.41 | 19-MAY-16:00 | 37.24 | 32.65 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 906215.09 | 1834405.70 | 28-JUN-16:00 | 51.41 | 43.53 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 1297648.93 | 2054973.02 | 22-JUL-15:00 | 55.26 | 44.60 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 1472841.60 | 2122606.83 | 20-AUG-16:00 | 56.43 | 42.97 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 504530.88 | 1178906.84 | 03-SEP-14:00 | 39.82 | 35.37 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 518286.50 | 1223305.11 | 01-OCT-16:00 | 40.62 | 33.20 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 541747.97 | 918713.71 | 09-NOV-14:00 | 35.16 | 25.15 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 680137.31 | 808520.33 | 24-DEC-15:00 | 33.16 | 20.53 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 704872.89 | 0.00 | ||||||
Minimum of Months | 204985.63 | 234384.22 | 22.67 | 18.47 | 0.00 | 0.00 | ||
Maximum of Months | 1472841.60 | 2122606.83 | 56.43 | 44.60 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 57.69 | 57.69 | 15593.41 | 52438.63 | 31-JAN-12:25 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 56.18 | 56.18 | 15792.33 | 52467.82 | 02-FEB-12:10 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 56.96 | 56.96 | 16304.79 | 51979.09 | 01-MAR-12:50 |
April | 0.00 | 0.00 | 01-APR-00:10 | 56.22 | 56.22 | 14628.61 | 49717.74 | 03-APR-11:30 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 56.70 | 56.70 | 14122.54 | 46849.34 | 01-MAY-12:00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 56.90 | 56.90 | 13496.07 | 43470.63 | 01-JUN-11:50 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 56.52 | 56.52 | 11972.12 | 40727.90 | 03-JUL-12:00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 57.08 | 57.08 | 12848.02 | 40024.65 | 31-AUG-11:40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 56.47 | 56.47 | 12507.10 | 41939.13 | 29-SEP-11:40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 56.97 | 56.97 | 13236.11 | 45164.90 | 31-OCT-12:00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 57.28 | 57.28 | 14335.47 | 48447.44 | 30-NOV-12:20 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 56.67 | 56.67 | 14697.56 | 51017.89 | 29-DEC-12:40 |
Annual Sum or Average | 0.00 | 14118.39 | ||||||
Minimum of Months | 0.00 | 0.00 | 56.18 | 56.18 | 11972.12 | 40024.65 | ||
Maximum of Months | 0.00 | 0.00 | 57.69 | 57.69 | 16304.79 | 52467.82 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 3083.76 | 290712.95 | 05-JAN-15:00 | 22.38 | 21.10 | 1706.18 | 135988.31 | 31-JAN-16:10 |
February | 13893.93 | 827606.99 | 14-FEB-16:30 | 24.75 | 21.10 | 3214.89 | 131383.28 | 03-FEB-12:40 |
March | 38726.95 | 843601.34 | 08-MAR-16:00 | 24.83 | 21.10 | 1981.16 | 128715.01 | 18-MAR-05:30 |
April | 167116.00 | 1998897.77 | 26-APR-12:50 | 25.51 | 21.10 | 2699.50 | 115770.97 | 15-APR-13:40 |
May | 298262.48 | 2212069.32 | 19-MAY-15:20 | 25.98 | 21.10 | 698.48 | 97779.35 | 16-MAY-07:00 |
June | 634413.34 | 2266464.81 | 29-JUN-11:40 | 26.10 | 21.86 | 712.06 | 87193.43 | 19-JUN-06:30 |
July | 752647.48 | 3019272.83 | 31-JUL-15:00 | 27.77 | 23.56 | 124.90 | 26405.43 | 19-JUL-01:40 |
August | 728932.64 | 2551712.95 | 21-AUG-14:00 | 26.73 | 22.80 | 535.45 | 37913.69 | 06-AUG-05:20 |
September | 495645.50 | 3042284.10 | 05-SEP-13:10 | 27.82 | 23.17 | 447.31 | 66205.60 | 30-SEP-06:00 |
October | 208789.32 | 2133115.70 | 03-OCT-12:10 | 25.81 | 21.10 | 1430.13 | 115756.34 | 12-OCT-10:40 |
November | 8588.77 | 454043.06 | 02-NOV-15:10 | 23.10 | 21.10 | 1835.71 | 133966.13 | 16-NOV-10:20 |
December | 134.44 | 25383.40 | 06-DEC-13:20 | 21.21 | 20.30 | 3144.64 | 136140.95 | 14-DEC-13:20 |
Annual Sum or Average | 280848.84 | 1531.79 | ||||||
Minimum of Months | 134.44 | 25383.40 | 21.21 | 20.30 | 124.90 | 26405.43 | ||
Maximum of Months | 752647.48 | 3042284.10 | 27.82 | 23.56 | 3214.89 | 136140.95 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.558863E+10 | 0.00 | 0.888480E+09 | 0.499857E+10 | 0.00 | 0.00 |
February | 0.278397E+10 | 0.00 | 0.303259E+10 | 0.540338E+10 | 0.00 | 0.00 |
March | 0.431666E+09 | 0.00 | 0.962673E+10 | 0.848712E+10 | 0.00 | 0.00 |
April | 18439097.88 | 0.00 | 0.372508E+11 | 0.122390E+11 | 0.00 | 0.00 |
May | 154134.71 | 0.00 | 0.551812E+11 | 0.102765E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.108359E+12 | 0.135754E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.139648E+12 | 0.156465E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.149756E+12 | 0.191869E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.796856E+11 | 0.103064E+11 | 0.00 | 0.00 |
October | 0.300212E+09 | 0.00 | 0.380108E+11 | 0.883804E+10 | 0.00 | 0.00 |
November | 0.510492E+09 | 0.00 | 0.236245E+10 | 0.734022E+10 | 0.00 | 0.00 |
December | 0.336451E+10 | 0.00 | 334315.88 | 0.677635E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.129981E+11 | 0.00 | 0.623803E+12 | 0.123074E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 334315.88 | 0.499857E+10 | 0.00 | 0.00 |
Maximum of Months | 0.558863E+10 | 0.00 | 0.149756E+12 | 0.191869E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.141217E+12 | 0.00 | 0.757867E+10 | 0.349659E+11 | 0.00 | 0.00 |
February | 0.808161E+11 | 0.00 | 0.242953E+11 | 0.344365E+11 | 0.00 | 0.00 |
March | 0.183864E+11 | 0.00 | 0.692741E+11 | 0.485237E+11 | 0.00 | 0.00 |
April | 0.207805E+10 | 0.00 | 0.261490E+12 | 0.662192E+11 | 0.00 | 0.00 |
May | 0.131588E+09 | 0.00 | 0.476331E+12 | 0.807920E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.926766E+12 | 0.107385E+12 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.112765E+13 | 0.117470E+12 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.106652E+13 | 0.118053E+12 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.692859E+12 | 0.803422E+11 | 0.00 | 0.00 |
October | 0.985567E+10 | 0.00 | 0.312349E+12 | 0.592281E+11 | 0.00 | 0.00 |
November | 0.296747E+11 | 0.00 | 0.167196E+11 | 0.413387E+11 | 0.00 | 0.00 |
December | 0.135998E+12 | 0.00 | 550465.02 | 0.352912E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.418158E+12 | 0.00 | 0.498184E+13 | 0.824046E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 550465.02 | 0.344365E+11 | 0.00 | 0.00 |
Maximum of Months | 0.141217E+12 | 0.00 | 0.112765E+13 | 0.118053E+12 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.303529E+11 | 0.00 | 0.308942E+09 | 0.361846E+10 | 0.00 | 0.00 |
February | 0.187528E+11 | 0.00 | 0.197302E+10 | 0.321160E+10 | 0.00 | 0.00 |
March | 0.647147E+10 | 0.00 | 0.588773E+10 | 0.400427E+10 | 0.00 | 0.00 |
April | 0.113487E+10 | 0.00 | 0.275848E+11 | 0.589053E+10 | 0.00 | 0.00 |
May | 0.210886E+09 | 0.00 | 0.523500E+11 | 0.774934E+10 | 0.00 | 0.00 |
June | 5426784.95 | 0.00 | 0.106331E+12 | 0.116310E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.130452E+12 | 0.131206E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.121634E+12 | 0.128980E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.753027E+11 | 0.802188E+10 | 0.00 | 0.00 |
October | 0.326741E+10 | 0.00 | 0.312635E+11 | 0.511379E+10 | 0.00 | 0.00 |
November | 0.987703E+10 | 0.00 | 0.104216E+10 | 0.348096E+10 | 0.00 | 0.00 |
December | 0.300657E+11 | 0.00 | 285.62 | 0.356330E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.100138E+12 | 0.00 | 0.554130E+12 | 0.823037E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 285.62 | 0.321160E+10 | 0.00 | 0.00 |
Maximum of Months | 0.303529E+11 | 0.00 | 0.130452E+12 | 0.131206E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 1944765.30 | 0.169051E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.126643E+10 | 0.151006E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.341756E+10 | 0.175783E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.189055E+11 | 0.164611E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.329603E+11 | 0.176231E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.609459E+11 | 0.174829E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.741519E+11 | 0.176319E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.772154E+11 | 0.195268E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.495564E+11 | 0.180434E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.226805E+11 | 0.183923E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.505839E+09 | 0.168934E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.168947E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.341608E+12 | 0.208534E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.151006E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.772154E+11 | 0.195268E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.495692E+12 | 0.271341E+12 | 0.00 | 20.98 |
February | 0.00 | 0.00 | 0.758579E+12 | 0.334682E+12 | 0.00 | 31.02 |
March | 0.00 | 0.00 | 0.118468E+13 | 0.467182E+12 | 0.00 | 46.37 |
April | 0.00 | 0.00 | 0.148726E+13 | 0.562941E+12 | 0.00 | 58.06 |
May | 0.00 | 0.00 | 0.511879E+12 | 0.276273E+12 | 0.00 | 17.84 |
June | 0.00 | 0.00 | 0.844771E+12 | 0.374569E+12 | 0.00 | 21.03 |
July | 0.00 | 0.00 | 0.123000E+13 | 0.493330E+12 | 0.00 | 22.59 |
August | 0.00 | 0.00 | 0.158544E+13 | 0.629815E+12 | 0.00 | 51.77 |
September | 0.00 | 0.00 | 0.505267E+12 | 0.268459E+12 | 0.00 | 15.32 |
October | 0.00 | 0.00 | 0.857197E+12 | 0.375936E+12 | 0.00 | 31.07 |
November | 0.00 | 0.00 | 0.115145E+13 | 0.454156E+12 | 0.00 | 47.00 |
December | 0.00 | 0.00 | 0.152502E+13 | 0.567824E+12 | 0.00 | 66.46 |
Annual Sum or Average | 0.00 | 0.00 | 0.121372E+14 | 0.507651E+13 | 0.00 | 429.52 |
Minimum of Months | 0.00 | 0.00 | 0.495692E+12 | 0.268459E+12 | 0.00 | 15.32 |
Maximum of Months | 0.00 | 0.00 | 0.158544E+13 | 0.629815E+12 | 0.00 | 66.46 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.594508E+10 | 0.303016E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.116025E+11 | 0.396789E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.197829E+11 | 0.575506E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.262999E+11 | 0.735446E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.801324E+10 | 0.360289E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.149312E+11 | 0.543133E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.227109E+11 | 0.765992E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.297083E+11 | 0.925634E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.818675E+10 | 0.360548E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.141444E+11 | 0.478801E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.189531E+11 | 0.543953E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.255019E+11 | 0.671058E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.205780E+12 | 0.666016E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.594508E+10 | 0.303016E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.297083E+11 | 0.925634E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.348751E+11 | 0.244254E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.937858E+11 | 0.346150E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.176316E+12 | 0.526640E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.243855E+12 | 0.689163E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.717650E+11 | 0.334081E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.140769E+12 | 0.514873E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.216497E+12 | 0.730457E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.277752E+12 | 0.871600E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.743938E+11 | 0.336218E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.126340E+12 | 0.440376E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.165046E+12 | 0.490771E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.218638E+12 | 0.597424E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.184003E+13 | 0.612201E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.348751E+11 | 0.244254E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.277752E+12 | 0.871600E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.149505E+10 | 0.204266E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.752946E+10 | 0.313074E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.163518E+11 | 0.507358E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.238729E+11 | 0.685096E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.694947E+10 | 0.333750E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.141546E+11 | 0.521654E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.218625E+11 | 0.740781E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.279555E+11 | 0.881623E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.735534E+10 | 0.338767E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.118250E+11 | 0.428961E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.146885E+11 | 0.461479E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.194422E+11 | 0.558427E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.173482E+12 | 0.597524E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.149505E+10 | 0.204266E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.279555E+11 | 0.881623E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.499857E+10 | 0.888480E+09 | 0.558863E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.540338E+10 | 0.303259E+10 | 0.278397E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.848712E+10 | 0.962673E+10 | 0.431666E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.122390E+11 | 0.372508E+11 | 18439097.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.102765E+11 | 0.551812E+11 | 154134.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.135754E+11 | 0.108359E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.156465E+11 | 0.139648E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.191869E+11 | 0.149756E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.103064E+11 | 0.796856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.883804E+10 | 0.380108E+11 | 0.300212E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.734022E+10 | 0.236245E+10 | 0.510492E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.677635E+10 | 334315.88 | 0.336451E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.123074E+12 | 0.623803E+12 | 0.129981E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.499857E+10 | 334315.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.191869E+11 | 0.149756E+12 | 0.558863E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.349659E+11 | 0.757867E+10 | 0.141217E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.344365E+11 | 0.242953E+11 | 0.808161E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.485237E+11 | 0.692741E+11 | 0.183864E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.662192E+11 | 0.261490E+12 | 0.207805E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.807920E+11 | 0.476331E+12 | 0.131588E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.107385E+12 | 0.926766E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.117470E+12 | 0.112765E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.118053E+12 | 0.106652E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.803422E+11 | 0.692859E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.592281E+11 | 0.312349E+12 | 0.985567E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.413387E+11 | 0.167196E+11 | 0.296747E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.352912E+11 | 550465.02 | 0.135998E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.824046E+12 | 0.498184E+13 | 0.418158E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.344365E+11 | 550465.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.118053E+12 | 0.112765E+13 | 0.141217E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.361846E+10 | 0.308942E+09 | 0.303529E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.321160E+10 | 0.197302E+10 | 0.187528E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.400427E+10 | 0.588773E+10 | 0.647147E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.589053E+10 | 0.275848E+11 | 0.113487E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.774934E+10 | 0.523500E+11 | 0.210886E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.116310E+11 | 0.106331E+12 | 5426784.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.131206E+11 | 0.130452E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.128980E+11 | 0.121634E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.802188E+10 | 0.753027E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.511379E+10 | 0.312635E+11 | 0.326741E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.348096E+10 | 0.104216E+10 | 0.987703E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.356330E+10 | 285.62 | 0.300657E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.823037E+11 | 0.554130E+12 | 0.100138E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.321160E+10 | 285.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.131206E+11 | 0.130452E+12 | 0.303529E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.169051E+11 | 1944765.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.151006E+11 | 0.126643E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.175783E+11 | 0.341756E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.164611E+11 | 0.189055E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.176231E+11 | 0.329603E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.174829E+11 | 0.609459E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.176319E+11 | 0.741519E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.195268E+11 | 0.772154E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.180434E+11 | 0.495564E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.183923E+11 | 0.226805E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.168934E+11 | 0.505839E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168947E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.208534E+12 | 0.341608E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.151006E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.195268E+11 | 0.772154E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.114711E+12 | 0.395471E+12 | 0.00 | 0.00 | 0.00 | 0.561560E+11 | 0.00 | 0.00 |
February | 0.103610E+12 | 0.610891E+12 | 0.00 | 0.00 | 0.00 | 0.830105E+11 | 0.00 | 0.00 |
March | 0.114711E+12 | 0.956854E+12 | 0.00 | 0.00 | 0.00 | 0.124081E+12 | 0.00 | 0.00 |
April | 0.111011E+12 | 0.119141E+13 | 0.00 | 0.00 | 0.00 | 0.155384E+12 | 0.00 | 0.00 |
May | 0.114711E+12 | 0.398284E+12 | 0.00 | 0.00 | 0.00 | 0.477521E+11 | 0.00 | 0.00 |
June | 0.111011E+12 | 0.637742E+12 | 0.00 | 0.00 | 0.00 | 0.562761E+11 | 0.00 | 0.00 |
July | 0.114711E+12 | 0.912110E+12 | 0.00 | 0.00 | 0.00 | 0.604595E+11 | 0.00 | 0.00 |
August | 0.114711E+12 | 0.120949E+13 | 0.00 | 0.00 | 0.00 | 0.138537E+12 | 0.00 | 0.00 |
September | 0.111011E+12 | 0.389014E+12 | 0.00 | 0.00 | 0.00 | 0.410109E+11 | 0.00 | 0.00 |
October | 0.114711E+12 | 0.679505E+12 | 0.00 | 0.00 | 0.00 | 0.831581E+11 | 0.00 | 0.00 |
November | 0.111011E+12 | 0.934649E+12 | 0.00 | 0.00 | 0.00 | 0.125774E+12 | 0.00 | 0.00 |
December | 0.114711E+12 | 0.125057E+13 | 0.00 | 0.00 | 0.00 | 0.177856E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.135063E+13 | 0.956599E+13 | 0.00 | 0.00 | 0.00 | 0.114946E+13 | 0.00 | 0.00 |
Minimum of Months | 0.103610E+12 | 0.389014E+12 | 0.00 | 0.00 | 0.00 | 0.410109E+11 | 0.00 | 0.00 |
Maximum of Months | 0.114711E+12 | 0.125057E+13 | 0.00 | 0.00 | 0.00 | 0.177856E+12 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.174190E+10 | 0.465683E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.157333E+10 | 0.920797E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.174190E+10 | 0.157697E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.168571E+10 | 0.206312E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.174190E+10 | 0.615226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.168571E+10 | 0.111856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.174190E+10 | 0.167929E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.174190E+10 | 0.221938E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.168571E+10 | 0.626699E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174190E+10 | 0.110983E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.168571E+10 | 0.151993E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.174190E+10 | 0.205332E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.205095E+11 | 0.159688E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.157333E+10 | 0.465683E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.174190E+10 | 0.221938E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.166277E+11 | 0.270774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.150186E+11 | 0.741894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.166277E+11 | 0.140280E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.160914E+11 | 0.191030E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.166277E+11 | 0.549846E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.160914E+11 | 0.105373E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.166277E+11 | 0.160079E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.166277E+11 | 0.207220E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.160914E+11 | 0.568634E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.166277E+11 | 0.989303E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.160914E+11 | 0.132061E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.166277E+11 | 0.175523E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.195778E+12 | 0.142361E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.150186E+11 | 0.270774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.166277E+11 | 0.207220E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.169926E+10 | 0.115165E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.153482E+10 | 0.593354E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.169926E+10 | 0.129775E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.164445E+10 | 0.186663E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.169926E+10 | 0.531123E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.164445E+10 | 0.105825E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.169926E+10 | 0.161539E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.169926E+10 | 0.208385E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.164445E+10 | 0.561212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.169926E+10 | 0.923469E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.164445E+10 | 0.117182E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.169926E+10 | 0.155572E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.200075E+11 | 0.133737E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.153482E+10 | 0.115165E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.169926E+10 | 0.208385E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.499857E+10 | 0.558863E+10 | 0.888480E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.540338E+10 | 0.278397E+10 | 0.303259E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.848712E+10 | 0.431666E+09 | 0.962673E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.122390E+11 | 18439097.88 | 0.372508E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.102765E+11 | 154134.71 | 0.551812E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.135754E+11 | 0.00 | 0.108359E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.156465E+11 | 0.00 | 0.139648E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.191869E+11 | 0.00 | 0.149756E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.103064E+11 | 0.00 | 0.796856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.883804E+10 | 0.300212E+09 | 0.380108E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.734022E+10 | 0.510492E+09 | 0.236245E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.677635E+10 | 0.336451E+10 | 334315.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.123074E+12 | 0.129981E+11 | 0.623803E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.499857E+10 | 0.00 | 334315.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.191869E+11 | 0.558863E+10 | 0.149756E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.349659E+11 | 0.141217E+12 | 0.757867E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.344365E+11 | 0.808161E+11 | 0.242953E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.485237E+11 | 0.183864E+11 | 0.692741E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.662192E+11 | 0.207805E+10 | 0.261490E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.807920E+11 | 0.131588E+09 | 0.476331E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.107385E+12 | 0.00 | 0.926766E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.117470E+12 | 0.00 | 0.112765E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.118053E+12 | 0.00 | 0.106652E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.803422E+11 | 0.00 | 0.692859E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.592281E+11 | 0.985567E+10 | 0.312349E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.413387E+11 | 0.296747E+11 | 0.167196E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.352912E+11 | 0.135998E+12 | 550465.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.824046E+12 | 0.418158E+12 | 0.498184E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.344365E+11 | 0.00 | 550465.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.118053E+12 | 0.141217E+12 | 0.112765E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.361846E+10 | 0.303529E+11 | 0.308942E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.321160E+10 | 0.187528E+11 | 0.197302E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.400427E+10 | 0.647147E+10 | 0.588773E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.589053E+10 | 0.113487E+10 | 0.275848E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.774934E+10 | 0.210886E+09 | 0.523500E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.116310E+11 | 5426784.95 | 0.106331E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.131206E+11 | 0.00 | 0.130452E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.128980E+11 | 0.00 | 0.121634E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.802188E+10 | 0.00 | 0.753027E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.511379E+10 | 0.326741E+10 | 0.312635E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.348096E+10 | 0.987703E+10 | 0.104216E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.356330E+10 | 0.300657E+11 | 285.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.823037E+11 | 0.100138E+12 | 0.554130E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.321160E+10 | 0.00 | 285.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.131206E+11 | 0.303529E+11 | 0.130452E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.169051E+11 | 0.00 | 1944765.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.151006E+11 | 0.00 | 0.126643E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.175783E+11 | 0.00 | 0.341756E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.164611E+11 | 0.00 | 0.189055E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.176231E+11 | 0.00 | 0.329603E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.174829E+11 | 0.00 | 0.609459E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.176319E+11 | 0.00 | 0.741519E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.195268E+11 | 0.00 | 0.772154E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.180434E+11 | 0.00 | 0.495564E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.183923E+11 | 0.00 | 0.226805E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.168934E+11 | 0.00 | 0.505839E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168947E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.208534E+12 | 0.00 | 0.341608E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.151006E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.195268E+11 | 0.00 | 0.772154E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.114711E+12 | 0.00 | 0.495692E+12 | 0.00 | 0.100221E+12 | 0.00 | 0.00 | 0.00 | 0.564088E+11 | 0.00 | 0.00 | 0.00 |
February | 0.103610E+12 | 0.00 | 0.758579E+12 | 0.00 | 0.147688E+12 | 0.00 | 0.00 | 0.00 | 0.833842E+11 | 0.00 | 0.00 | 0.00 |
March | 0.114711E+12 | 0.00 | 0.118468E+13 | 0.00 | 0.227831E+12 | 0.00 | 0.00 | 0.00 | 0.124640E+12 | 0.00 | 0.00 | 0.00 |
April | 0.111011E+12 | 0.00 | 0.148726E+13 | 0.00 | 0.295847E+12 | 0.00 | 0.00 | 0.00 | 0.156083E+12 | 0.00 | 0.00 | 0.00 |
May | 0.114711E+12 | 0.00 | 0.511879E+12 | 0.00 | 0.113595E+12 | 0.00 | 0.00 | 0.00 | 0.479670E+11 | 0.00 | 0.00 | 0.00 |
June | 0.111011E+12 | 0.00 | 0.844771E+12 | 0.00 | 0.207029E+12 | 0.00 | 0.00 | 0.00 | 0.565294E+11 | 0.00 | 0.00 | 0.00 |
July | 0.114711E+12 | 0.00 | 0.123000E+13 | 0.00 | 0.317887E+12 | 0.00 | 0.00 | 0.00 | 0.607317E+11 | 0.00 | 0.00 | 0.00 |
August | 0.114711E+12 | 0.00 | 0.158544E+13 | 0.00 | 0.375943E+12 | 0.00 | 0.00 | 0.00 | 0.139161E+12 | 0.00 | 0.00 | 0.00 |
September | 0.111011E+12 | 0.00 | 0.505267E+12 | 0.00 | 0.116253E+12 | 0.00 | 0.00 | 0.00 | 0.411955E+11 | 0.00 | 0.00 | 0.00 |
October | 0.114711E+12 | 0.00 | 0.857197E+12 | 0.00 | 0.177692E+12 | 0.00 | 0.00 | 0.00 | 0.835324E+11 | 0.00 | 0.00 | 0.00 |
November | 0.111011E+12 | 0.00 | 0.115145E+13 | 0.00 | 0.216804E+12 | 0.00 | 0.00 | 0.00 | 0.126341E+12 | 0.00 | 0.00 | 0.00 |
December | 0.114711E+12 | 0.00 | 0.152502E+13 | 0.00 | 0.274456E+12 | 0.00 | 0.00 | 0.00 | 0.178657E+12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.135063E+13 | 0.00 | 0.121372E+14 | 0.00 | 0.257125E+13 | 0.00 | 0.00 | 0.00 | 0.115463E+13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.103610E+12 | 0.00 | 0.495692E+12 | 0.00 | 0.100221E+12 | 0.00 | 0.00 | 0.00 | 0.411955E+11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.114711E+12 | 0.00 | 0.158544E+13 | 0.00 | 0.375943E+12 | 0.00 | 0.00 | 0.00 | 0.178657E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.174190E+10 | 0.00 | 0.594508E+10 | 0.00 | 0.128825E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.157333E+10 | 0.00 | 0.116025E+11 | 0.00 | 0.239455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.174190E+10 | 0.00 | 0.197829E+11 | 0.00 | 0.401316E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.168571E+10 | 0.00 | 0.262999E+11 | 0.00 | 0.566874E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.174190E+10 | 0.00 | 0.801324E+10 | 0.00 | 0.186098E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.168571E+10 | 0.00 | 0.149312E+11 | 0.00 | 0.374561E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.174190E+10 | 0.00 | 0.227109E+11 | 0.00 | 0.591802E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.174190E+10 | 0.00 | 0.297083E+11 | 0.00 | 0.751443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.168571E+10 | 0.00 | 0.818675E+10 | 0.00 | 0.191976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174190E+10 | 0.00 | 0.141444E+11 | 0.00 | 0.304610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.168571E+10 | 0.00 | 0.189531E+11 | 0.00 | 0.375381E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.174190E+10 | 0.00 | 0.255019E+11 | 0.00 | 0.496868E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.205095E+11 | 0.00 | 0.205780E+12 | 0.00 | 0.460921E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.157333E+10 | 0.00 | 0.594508E+10 | 0.00 | 0.128825E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.174190E+10 | 0.00 | 0.297083E+11 | 0.00 | 0.751443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.166277E+11 | 0.00 | 0.348751E+11 | 0.00 | 0.779763E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.150186E+11 | 0.00 | 0.937858E+11 | 0.00 | 0.195964E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.166277E+11 | 0.00 | 0.176316E+12 | 0.00 | 0.360363E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.160914E+11 | 0.00 | 0.243855E+12 | 0.00 | 0.528250E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.166277E+11 | 0.00 | 0.717650E+11 | 0.00 | 0.167804E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.160914E+11 | 0.00 | 0.140769E+12 | 0.00 | 0.353960E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.166277E+11 | 0.00 | 0.216497E+12 | 0.00 | 0.564180E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.166277E+11 | 0.00 | 0.277752E+12 | 0.00 | 0.705323E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.160914E+11 | 0.00 | 0.743938E+11 | 0.00 | 0.175305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.166277E+11 | 0.00 | 0.126340E+12 | 0.00 | 0.274099E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.160914E+11 | 0.00 | 0.165046E+12 | 0.00 | 0.329857E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.166277E+11 | 0.00 | 0.218638E+12 | 0.00 | 0.431146E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.195778E+12 | 0.00 | 0.184003E+13 | 0.00 | 0.416423E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.150186E+11 | 0.00 | 0.348751E+11 | 0.00 | 0.779763E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.166277E+11 | 0.00 | 0.277752E+12 | 0.00 | 0.705323E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.169926E+10 | 0.00 | 0.149505E+10 | 0.00 | 0.343399E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.153482E+10 | 0.00 | 0.752946E+10 | 0.00 | 0.159592E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.169926E+10 | 0.00 | 0.163518E+11 | 0.00 | 0.337431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.164445E+10 | 0.00 | 0.238729E+11 | 0.00 | 0.520652E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.169926E+10 | 0.00 | 0.694947E+10 | 0.00 | 0.163824E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.164445E+10 | 0.00 | 0.141546E+11 | 0.00 | 0.357209E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.169926E+10 | 0.00 | 0.218625E+11 | 0.00 | 0.570855E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.169926E+10 | 0.00 | 0.279555E+11 | 0.00 | 0.711697E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.164445E+10 | 0.00 | 0.735534E+10 | 0.00 | 0.174323E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.169926E+10 | 0.00 | 0.118250E+11 | 0.00 | 0.259035E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.164445E+10 | 0.00 | 0.146885E+11 | 0.00 | 0.297034E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.169926E+10 | 0.00 | 0.194422E+11 | 0.00 | 0.388500E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.200075E+11 | 0.00 | 0.173482E+12 | 0.00 | 0.397449E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.153482E+10 | 0.00 | 0.149505E+10 | 0.00 | 0.343399E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.169926E+10 | 0.00 | 0.279555E+11 | 0.00 | 0.711697E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.483529E+09 | 0.00 | 0.00 | 0.115737E+09 | 0.00 | 0.00 | 0.709215E+11 | 0.00 | 0.74 |
February | 0.340634E+09 | 0.00 | 0.00 | 0.102296E+09 | 0.00 | 0.00 | 0.632705E+11 | 0.00 | 0.81 |
March | 0.225767E+09 | 0.00 | 0.00 | 0.114341E+09 | 0.00 | 0.00 | 0.748219E+11 | 0.00 | 1.21 |
April | 0.181586E+09 | 12009327.24 | 0.00 | 0.109936E+09 | 98401.67 | 0.00 | 0.564242E+11 | 0.00 | 1.36 |
May | 0.112802E+09 | 0.121431E+09 | 0.00 | 0.109191E+09 | 10686396.65 | 0.00 | 0.459163E+11 | 0.00 | 1.34 |
June | 66907594.14 | 0.247671E+10 | 0.00 | 71877595.97 | 25202942.54 | 0.00 | 0.219160E+11 | 0.00 | 1.04 |
July | 84626522.76 | 0.293278E+10 | 0.00 | 68027007.50 | 61387199.66 | 0.00 | 0.104954E+11 | 0.00 | 0.90 |
August | 96660720.92 | 0.181876E+10 | 0.00 | 0.106638E+09 | 42973184.46 | 0.00 | 0.188838E+11 | 0.00 | 1.16 |
September | 0.143086E+09 | 0.329918E+09 | 0.00 | 0.114805E+09 | 11527640.41 | 0.00 | 0.331905E+11 | 0.00 | 1.36 |
October | 0.281280E+09 | 12687777.85 | 0.00 | 0.133286E+09 | 141659.57 | 0.00 | 0.622105E+11 | 0.00 | 1.39 |
November | 0.408064E+09 | 0.00 | 0.00 | 0.128915E+09 | 0.00 | 0.00 | 0.786546E+11 | 0.00 | 1.06 |
December | 0.517389E+09 | 0.00 | 0.00 | 0.134260E+09 | 0.00 | 0.00 | 0.764926E+11 | 0.00 | 0.71 |
Annual Sum or Average | 0.294233E+10 | 0.770429E+10 | 0.00 | 0.130931E+10 | 0.152017E+09 | 0.00 | 0.613198E+12 | 0.00 | 1.09 |
Minimum of Months | 66907594.14 | 0.00 | 0.00 | 68027007.50 | 0.00 | 0.00 | 0.104954E+11 | 0.00 | 0.71 |
Maximum of Months | 0.517389E+09 | 0.293278E+10 | 0.00 | 0.134260E+09 | 61387199.66 | 0.00 | 0.786546E+11 | 0.00 | 1.39 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.283961E+10 | 0.00 | 0.00 | 72524031.24 | 0.00 | 0.00 | 0.466504E+11 | 0.00 | 0.50 |
February | 0.213460E+10 | 0.00 | 0.00 | 76555900.19 | 0.00 | 0.00 | 0.448902E+11 | 0.00 | 0.58 |
March | 0.330816E+10 | 0.00 | 0.00 | 97936572.28 | 0.00 | 0.00 | 0.575248E+11 | 0.00 | 0.92 |
April | 0.943403E+10 | 2745573.67 | 0.00 | 96041503.53 | 0.00 | 0.00 | 0.459975E+11 | 0.00 | 1.21 |
May | 0.300830E+10 | 49722413.03 | 0.00 | 89412420.13 | 19843927.45 | 0.00 | 0.341676E+11 | 0.00 | 0.99 |
June | 0.438756E+10 | 0.990122E+09 | 0.00 | 62836358.33 | 0.126406E+09 | 0.00 | 0.152127E+11 | 0.00 | 0.83 |
July | 0.411700E+10 | 0.141273E+10 | 0.00 | 48542885.93 | 0.375117E+09 | 0.00 | 0.520854E+10 | 0.00 | 0.74 |
August | 0.624607E+10 | 0.110425E+10 | 0.00 | 86189352.01 | 0.130444E+09 | 0.00 | 0.132107E+11 | 0.00 | 1.05 |
September | 0.282722E+10 | 0.277952E+09 | 0.00 | 84071767.64 | 16450111.04 | 0.00 | 0.218976E+11 | 0.00 | 0.90 |
October | 0.421596E+10 | 1459598.25 | 0.00 | 96103794.75 | 1732343.51 | 0.00 | 0.423505E+11 | 0.00 | 0.92 |
November | 0.425689E+10 | 0.00 | 0.00 | 94983481.78 | 0.00 | 0.00 | 0.561110E+11 | 0.00 | 0.78 |
December | 0.311643E+10 | 0.00 | 0.00 | 0.100805E+09 | 0.00 | 0.00 | 0.565839E+11 | 0.00 | 0.54 |
Annual Sum or Average | 0.498918E+11 | 0.383898E+10 | 0.00 | 0.100600E+10 | 0.669993E+09 | 0.00 | 0.439805E+12 | 0.00 | 0.83 |
Minimum of Months | 0.213460E+10 | 0.00 | 0.00 | 48542885.93 | 0.00 | 0.00 | 0.520854E+10 | 0.00 | 0.50 |
Maximum of Months | 0.943403E+10 | 0.141273E+10 | 0.00 | 0.100805E+09 | 0.375117E+09 | 0.00 | 0.575248E+11 | 0.00 | 1.21 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.178534E+12 | 0.00 | 0.00 | 0.225752E+09 | 0.00 | 0.00 | 0.184080E+12 | 0.00 | 0.37 |
February | 0.119374E+12 | 0.00 | 0.00 | 0.292061E+09 | 0.00 | 0.00 | 0.206096E+12 | 0.00 | 0.41 |
March | 0.544137E+11 | 0.00 | 0.00 | 0.511411E+09 | 0.00 | 0.00 | 0.349815E+12 | 0.00 | 0.63 |
April | 0.310008E+11 | 20864120.94 | 0.00 | 0.623505E+09 | 9549419.92 | 0.00 | 0.307966E+12 | 0.00 | 0.77 |
May | 0.222331E+11 | 0.516460E+09 | 0.00 | 0.723616E+09 | 0.158792E+09 | 0.00 | 0.276658E+12 | 0.00 | 0.81 |
June | 0.187104E+11 | 0.111173E+11 | 0.00 | 0.516352E+09 | 0.567148E+09 | 0.00 | 0.121270E+12 | 0.00 | 0.64 |
July | 0.130449E+11 | 0.139015E+11 | 0.00 | 0.401274E+09 | 0.238019E+10 | 0.00 | 0.409656E+11 | 0.00 | 0.52 |
August | 0.153078E+11 | 0.796019E+10 | 0.00 | 0.650120E+09 | 0.104749E+10 | 0.00 | 0.978959E+11 | 0.00 | 0.66 |
September | 0.183934E+11 | 0.256351E+10 | 0.00 | 0.692446E+09 | 0.262949E+09 | 0.00 | 0.175476E+12 | 0.00 | 0.74 |
October | 0.418340E+11 | 7639589.48 | 0.00 | 0.643710E+09 | 80869860.84 | 0.00 | 0.290995E+12 | 0.00 | 0.69 |
November | 0.737628E+11 | 0.00 | 0.00 | 0.433747E+09 | 0.00 | 0.00 | 0.308983E+12 | 0.00 | 0.51 |
December | 0.166308E+12 | 0.00 | 0.00 | 0.252164E+09 | 0.00 | 0.00 | 0.198171E+12 | 0.00 | 0.33 |
Annual Sum or Average | 0.752918E+12 | 0.360874E+11 | 0.00 | 0.596616E+10 | 0.450700E+10 | 0.00 | 0.255837E+13 | 0.00 | 0.59 |
Minimum of Months | 0.130449E+11 | 0.00 | 0.00 | 0.225752E+09 | 0.00 | 0.00 | 0.409656E+11 | 0.00 | 0.33 |
Maximum of Months | 0.178534E+12 | 0.139015E+11 | 0.00 | 0.723616E+09 | 0.238019E+10 | 0.00 | 0.349815E+12 | 0.00 | 0.81 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.249209E+11 | 0.00 | 0.00 | 2922042.00 | 0.00 | 0.113124E+10 | 0.367406E+10 | 0.00 | 0.32 |
February | 0.190818E+11 | 0.00 | 0.00 | 6938040.24 | 0.00 | 0.438439E+09 | 0.710637E+10 | 0.00 | 0.35 |
March | 0.129559E+11 | 0.00 | 0.00 | 24076179.23 | 0.00 | 33783280.18 | 0.201220E+11 | 0.00 | 0.53 |
April | 0.515519E+10 | 0.00 | 0.00 | 47139607.63 | 0.00 | 0.00 | 0.251671E+11 | 0.00 | 0.75 |
May | 0.361329E+10 | 20969615.50 | 0.00 | 63498460.28 | 17685199.15 | 0.00 | 0.243912E+11 | 0.00 | 0.83 |
June | 0.202443E+10 | 0.721475E+09 | 0.00 | 58626910.02 | 53418344.94 | 0.00 | 0.112659E+11 | 0.00 | 0.65 |
July | 0.143202E+10 | 0.905719E+09 | 0.00 | 51849454.50 | 0.250940E+09 | 0.00 | 0.398027E+10 | 0.00 | 0.54 |
August | 0.142095E+10 | 0.513229E+09 | 0.00 | 75528566.11 | 0.109673E+09 | 0.00 | 0.979040E+10 | 0.00 | 0.70 |
September | 0.167351E+10 | 0.126423E+09 | 0.00 | 66356648.70 | 6616857.69 | 0.00 | 0.156749E+11 | 0.00 | 0.74 |
October | 0.816274E+10 | 1126883.84 | 0.00 | 42581357.87 | 550216.97 | 927367.32 | 0.186528E+11 | 0.00 | 0.61 |
November | 0.159717E+11 | 0.00 | 0.00 | 14168773.05 | 0.00 | 0.303949E+09 | 0.131943E+11 | 0.00 | 0.41 |
December | 0.250021E+11 | 0.00 | 0.00 | 2410104.07 | 0.00 | 0.117784E+10 | 0.331969E+10 | 0.00 | 0.28 |
Annual Sum or Average | 0.121415E+12 | 0.228894E+10 | 0.00 | 0.456096E+09 | 0.438883E+09 | 0.308617E+10 | 0.156339E+12 | 0.00 | 0.56 |
Minimum of Months | 0.142095E+10 | 0.00 | 0.00 | 2410104.07 | 0.00 | 0.00 | 0.331969E+10 | 0.00 | 0.28 |
Maximum of Months | 0.250021E+11 | 0.905719E+09 | 0.00 | 75528566.11 | 0.250940E+09 | 0.117784E+10 | 0.251671E+11 | 0.00 | 0.83 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.379445E+10 | 0.00 | 0.00 | 224295.52 | 0.00 | 26481229.77 | 0.412193E+09 | 0.00 | 0.33 |
February | 0.282802E+10 | 0.00 | 0.00 | 1086499.56 | 0.00 | 8767496.71 | 0.976740E+09 | 0.00 | 0.38 |
March | 0.204926E+10 | 0.00 | 0.00 | 4477679.37 | 0.00 | 0.00 | 0.325628E+10 | 0.00 | 0.66 |
April | 0.169935E+10 | 512099.02 | 0.00 | 8502292.88 | 0.00 | 0.00 | 0.414539E+10 | 0.00 | 1.11 |
May | 0.719978E+09 | 10935917.48 | 0.00 | 9951095.66 | 2492004.52 | 0.00 | 0.358248E+10 | 0.00 | 1.01 |
June | 0.614881E+09 | 0.217661E+09 | 0.00 | 9509026.92 | 15421060.59 | 0.00 | 0.202265E+10 | 0.00 | 1.01 |
July | 0.528335E+09 | 0.307195E+09 | 0.00 | 7984811.88 | 47107215.02 | 0.00 | 0.787581E+09 | 0.00 | 0.94 |
August | 0.841441E+09 | 0.208857E+09 | 0.00 | 12588800.05 | 15571174.03 | 0.00 | 0.176016E+10 | 0.00 | 1.22 |
September | 0.528825E+09 | 46109698.95 | 0.00 | 9740275.28 | 2050568.32 | 0.00 | 0.230171E+10 | 0.00 | 0.90 |
October | 0.155634E+10 | 250294.85 | 0.00 | 6302429.26 | 217548.06 | 0.00 | 0.266585E+10 | 0.00 | 0.74 |
November | 0.240759E+10 | 0.00 | 0.00 | 2717858.07 | 0.00 | 0.00 | 0.229697E+10 | 0.00 | 0.49 |
December | 0.363454E+10 | 0.00 | 0.00 | 497246.02 | 0.00 | 0.00 | 0.677763E+09 | 0.00 | 0.31 |
Annual Sum or Average | 0.212030E+11 | 0.791521E+09 | 0.00 | 73582310.48 | 82859570.54 | 35248726.48 | 0.248858E+11 | 0.00 | 0.76 |
Minimum of Months | 0.528335E+09 | 0.00 | 0.00 | 224295.52 | 0.00 | 0.00 | 0.412193E+09 | 0.00 | 0.31 |
Maximum of Months | 0.379445E+10 | 0.307195E+09 | 0.00 | 12588800.05 | 47107215.02 | 26481229.77 | 0.414539E+10 | 0.00 | 1.22 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.316322E+10 | 0.00 | 0.00 | 1741063.08 | 0.00 | 56030881.97 | 0.138467E+10 | 0.00 | 0.56 |
February | 0.236922E+10 | 0.00 | 0.00 | 2721015.22 | 0.00 | 18105650.89 | 0.188896E+10 | 0.00 | 0.64 |
March | 0.185266E+10 | 0.00 | 0.00 | 6634594.14 | 0.00 | 0.00 | 0.430130E+10 | 0.00 | 1.11 |
April | 0.166981E+10 | 407329.92 | 0.00 | 11023095.10 | 0.00 | 0.00 | 0.565468E+10 | 0.00 | 1.93 |
May | 0.667334E+09 | 9785189.08 | 0.00 | 13537215.00 | 2564483.55 | 0.00 | 0.494235E+10 | 0.00 | 1.84 |
June | 0.678702E+09 | 0.163706E+09 | 0.00 | 11170785.40 | 16752171.46 | 0.00 | 0.220297E+10 | 0.00 | 1.66 |
July | 0.556484E+09 | 0.255685E+09 | 0.00 | 8792912.03 | 46533871.74 | 0.00 | 0.731140E+09 | 0.00 | 1.43 |
August | 0.937759E+09 | 0.162450E+09 | 0.00 | 11122469.75 | 16458712.75 | 0.00 | 0.161248E+10 | 0.00 | 1.81 |
September | 0.583433E+09 | 34369745.81 | 0.00 | 11196885.65 | 2117890.29 | 0.00 | 0.282297E+10 | 0.00 | 1.63 |
October | 0.142936E+10 | 174173.26 | 0.00 | 8419134.31 | 218965.45 | 0.00 | 0.371124E+10 | 0.00 | 1.29 |
November | 0.229225E+10 | 0.00 | 0.00 | 4086417.82 | 0.00 | 0.00 | 0.284702E+10 | 0.00 | 0.79 |
December | 0.330341E+10 | 0.00 | 0.00 | 1686089.14 | 0.00 | 47161282.53 | 0.126514E+10 | 0.00 | 0.51 |
Annual Sum or Average | 0.195036E+11 | 0.626577E+09 | 0.00 | 92131676.65 | 84646095.24 | 0.121298E+09 | 0.333649E+11 | 0.00 | 1.27 |
Minimum of Months | 0.556484E+09 | 0.00 | 0.00 | 1686089.14 | 0.00 | 0.00 | 0.731140E+09 | 0.00 | 0.51 |
Maximum of Months | 0.330341E+10 | 0.255685E+09 | 0.00 | 13537215.00 | 46533871.74 | 56030881.97 | 0.565468E+10 | 0.00 | 1.93 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.212801E+10 | 0.00 | 0.00 | 13300511.74 | 0.00 | 0.100773E+09 | 0.771692E+10 | 0.00 | 0.90 |
February | 0.158312E+10 | 0.00 | 0.00 | 13162620.90 | 0.00 | 23725230.04 | 0.798840E+10 | 0.00 | 1.04 |
March | 0.152629E+10 | 0.00 | 0.00 | 13833299.72 | 0.00 | 0.00 | 0.857963E+10 | 0.00 | 1.36 |
April | 0.181038E+10 | 744056.06 | 0.00 | 14157383.92 | 0.00 | 0.00 | 0.658661E+10 | 0.00 | 1.67 |
May | 0.925701E+09 | 15965094.67 | 0.00 | 11367236.26 | 2758261.23 | 0.00 | 0.393904E+10 | 0.00 | 1.17 |
June | 0.766408E+09 | 0.221720E+09 | 0.00 | 8915121.28 | 17163333.32 | 0.00 | 0.175174E+10 | 0.00 | 0.99 |
July | 0.587334E+09 | 0.348863E+09 | 0.00 | 8162757.09 | 52140356.80 | 0.00 | 0.745092E+09 | 0.00 | 0.97 |
August | 0.907631E+09 | 0.278403E+09 | 0.00 | 15478309.13 | 14946276.20 | 0.00 | 0.196262E+10 | 0.00 | 1.41 |
September | 0.469330E+09 | 88499276.46 | 0.00 | 19188025.67 | 1672238.32 | 0.00 | 0.356490E+10 | 0.00 | 1.43 |
October | 0.106474E+10 | 1297400.44 | 0.00 | 23930772.76 | 0.00 | 0.00 | 0.830975E+10 | 0.00 | 1.69 |
November | 0.123061E+10 | 0.00 | 0.00 | 19163082.52 | 0.00 | 0.00 | 0.112047E+11 | 0.00 | 1.31 |
December | 0.177226E+10 | 0.00 | 0.00 | 16499327.48 | 0.00 | 26647047.41 | 0.101232E+11 | 0.00 | 0.90 |
Annual Sum or Average | 0.147718E+11 | 0.955492E+09 | 0.00 | 0.177158E+09 | 88680465.86 | 0.151146E+09 | 0.724726E+11 | 0.00 | 1.24 |
Minimum of Months | 0.469330E+09 | 0.00 | 0.00 | 8162757.09 | 0.00 | 0.00 | 0.745092E+09 | 0.00 | 0.90 |
Maximum of Months | 0.212801E+10 | 0.348863E+09 | 0.00 | 23930772.76 | 52140356.80 | 0.100773E+09 | 0.112047E+11 | 0.00 | 1.69 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.392534E+10 | 0.00 | 0.00 | 2724960.85 | 0.00 | 0.00 | 0.238304E+10 | 0.00 | 0.81 |
February | 0.201347E+10 | 0.00 | 0.00 | 6007764.66 | 0.00 | 0.00 | 0.447956E+10 | 0.00 | 1.07 |
March | 0.933271E+09 | 0.00 | 0.00 | 13218184.11 | 0.00 | 0.00 | 0.805586E+10 | 0.00 | 1.84 |
April | 0.100956E+10 | 815416.25 | 0.00 | 24034829.96 | 0.00 | 0.00 | 0.906585E+10 | 0.00 | 3.05 |
May | 0.658619E+09 | 22393940.72 | 0.00 | 13898764.89 | 1411364.96 | 0.00 | 0.459505E+10 | 0.00 | 1.96 |
June | 0.557461E+09 | 0.290773E+09 | 0.00 | 12438329.59 | 15770275.24 | 0.00 | 0.238076E+10 | 0.00 | 1.82 |
July | 0.429291E+09 | 0.409048E+09 | 0.00 | 11851189.18 | 41781005.12 | 0.00 | 0.119909E+10 | 0.00 | 1.75 |
August | 0.213107E+09 | 0.334045E+09 | 0.00 | 26442472.07 | 2820473.57 | 0.00 | 0.363852E+10 | 0.00 | 2.76 |
September | 0.487460E+09 | 58225755.80 | 0.00 | 14697693.94 | 633665.66 | 0.00 | 0.290743E+10 | 0.00 | 1.69 |
October | 0.102596E+10 | 342713.55 | 0.00 | 14194344.89 | 286216.39 | 0.00 | 0.545629E+10 | 0.00 | 1.80 |
November | 0.106079E+10 | 0.00 | 0.00 | 10133414.50 | 0.00 | 0.00 | 0.709989E+10 | 0.00 | 1.36 |
December | 0.130736E+10 | 0.00 | 0.00 | 9126141.25 | 0.00 | 0.00 | 0.660123E+10 | 0.00 | 0.92 |
Annual Sum or Average | 0.136217E+11 | 0.111564E+10 | 0.00 | 0.158768E+09 | 62703000.94 | 0.00 | 0.578625E+11 | 0.00 | 1.74 |
Minimum of Months | 0.213107E+09 | 0.00 | 0.00 | 2724960.85 | 0.00 | 0.00 | 0.119909E+10 | 0.00 | 0.81 |
Maximum of Months | 0.392534E+10 | 0.409048E+09 | 0.00 | 26442472.07 | 41781005.12 | 0.00 | 0.906585E+10 | 0.00 | 3.05 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.263595E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160635E+11 | 0.00 | 0.00 | 0.34 |
February | 0.255295E+11 | 0.00 | 0.00 | 213959.98 | 0.00 | 0.968009E+10 | 0.417277E+09 | 0.00 | 0.35 |
March | 0.300289E+11 | 0.00 | 0.00 | 6570778.09 | 0.00 | 0.194712E+10 | 0.591086E+10 | 0.00 | 0.46 |
April | 0.157252E+11 | 4205646.33 | 0.00 | 39164920.14 | 1200486.45 | 66537782.73 | 0.170400E+11 | 0.00 | 0.65 |
May | 0.896911E+10 | 0.113896E+09 | 0.00 | 73040373.55 | 19962242.00 | 0.00 | 0.236052E+11 | 0.00 | 0.80 |
June | 0.361872E+10 | 0.272375E+10 | 0.00 | 74645226.63 | 61403799.41 | 0.00 | 0.147609E+11 | 0.00 | 0.82 |
July | 0.170716E+10 | 0.340249E+10 | 0.00 | 65702557.84 | 0.299557E+09 | 0.00 | 0.615748E+10 | 0.00 | 0.72 |
August | 0.234932E+10 | 0.174465E+10 | 0.00 | 94895608.79 | 0.131684E+09 | 0.00 | 0.124652E+11 | 0.00 | 0.80 |
September | 0.599276E+10 | 0.437614E+09 | 0.00 | 71680152.70 | 32802563.63 | 0.00 | 0.154433E+11 | 0.00 | 0.71 |
October | 0.206967E+11 | 1285849.36 | 0.00 | 30368244.67 | 10166394.73 | 0.770651E+09 | 0.100966E+11 | 0.00 | 0.55 |
November | 0.318027E+11 | 0.00 | 0.00 | 1448172.07 | 0.00 | 0.413946E+10 | 0.208967E+10 | 0.00 | 0.39 |
December | 0.230302E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190329E+11 | 0.00 | 0.00 | 0.30 |
Annual Sum or Average | 0.195810E+12 | 0.842789E+10 | 0.00 | 0.457730E+09 | 0.556776E+09 | 0.517002E+11 | 0.107986E+12 | 0.00 | 0.58 |
Minimum of Months | 0.170716E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.318027E+11 | 0.340249E+10 | 0.00 | 94895608.79 | 0.299557E+09 | 0.190329E+11 | 0.236052E+11 | 0.00 | 0.82 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.334856E+11 | 0.00 | 0.00 | 2092652.09 | 0.00 | 0.110166E+11 | 0.196608E+10 | 0.00 | 0.58 |
February | 0.289502E+11 | 0.00 | 0.00 | 8711420.31 | 0.00 | 0.504560E+10 | 0.627690E+10 | 0.00 | 0.61 |
March | 0.219635E+11 | 0.00 | 0.00 | 39732630.22 | 0.00 | 0.736091E+09 | 0.279515E+11 | 0.00 | 0.94 |
April | 0.924159E+10 | 6112611.04 | 0.00 | 96838308.19 | 113452.75 | 28603786.69 | 0.493643E+11 | 0.00 | 1.60 |
May | 0.645549E+10 | 0.122879E+09 | 0.00 | 0.131007E+09 | 21967149.11 | 0.00 | 0.454437E+11 | 0.00 | 1.75 |
June | 0.383600E+10 | 0.229525E+10 | 0.00 | 0.105512E+09 | 62360362.72 | 0.00 | 0.205429E+11 | 0.00 | 1.57 |
July | 0.175101E+10 | 0.355752E+10 | 0.00 | 90326177.77 | 0.194170E+09 | 0.00 | 0.732631E+10 | 0.00 | 1.28 |
August | 0.243256E+10 | 0.169632E+10 | 0.00 | 0.121394E+09 | 0.144404E+09 | 0.00 | 0.171127E+11 | 0.00 | 1.55 |
September | 0.556783E+10 | 0.362214E+09 | 0.00 | 0.103898E+09 | 32184651.76 | 0.00 | 0.250992E+11 | 0.00 | 1.53 |
October | 0.159328E+11 | 1505392.53 | 0.00 | 63773440.86 | 10847227.35 | 0.532531E+09 | 0.276052E+11 | 0.00 | 1.14 |
November | 0.311941E+11 | 0.00 | 0.00 | 13475083.08 | 0.00 | 0.183596E+10 | 0.108168E+11 | 0.00 | 0.70 |
December | 0.341005E+11 | 0.00 | 0.00 | 823711.55 | 0.00 | 0.109839E+11 | 0.106342E+10 | 0.00 | 0.51 |
Annual Sum or Average | 0.194911E+12 | 0.804180E+10 | 0.00 | 0.777584E+09 | 0.466047E+09 | 0.301793E+11 | 0.240569E+12 | 0.00 | 1.15 |
Minimum of Months | 0.175101E+10 | 0.00 | 0.00 | 823711.55 | 0.00 | 0.00 | 0.106342E+10 | 0.00 | 0.51 |
Maximum of Months | 0.341005E+11 | 0.355752E+10 | 0.00 | 0.131007E+09 | 0.194170E+09 | 0.110166E+11 | 0.493643E+11 | 0.00 | 1.75 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.195807E+11 | 0.00 | 0.00 | 0.129201E+09 | 0.00 | 0.548830E+10 | 0.684017E+11 | 0.00 | 0.88 |
February | 0.151255E+11 | 0.00 | 0.00 | 0.124960E+09 | 0.00 | 0.267221E+10 | 0.696944E+11 | 0.00 | 0.98 |
March | 0.158913E+11 | 0.00 | 0.00 | 0.115637E+09 | 0.00 | 0.282224E+09 | 0.677030E+11 | 0.00 | 1.17 |
April | 0.108124E+11 | 10836197.22 | 0.00 | 0.108595E+09 | 111397.02 | 7881980.49 | 0.486223E+11 | 0.00 | 1.25 |
May | 0.921884E+10 | 0.185312E+09 | 0.00 | 95338501.92 | 21569111.26 | 0.00 | 0.307810E+11 | 0.00 | 1.00 |
June | 0.482168E+10 | 0.276590E+10 | 0.00 | 71239884.83 | 68426566.38 | 0.00 | 0.132144E+11 | 0.00 | 0.80 |
July | 0.182386E+10 | 0.392231E+10 | 0.00 | 69278418.04 | 0.323657E+09 | 0.00 | 0.601986E+10 | 0.00 | 0.75 |
August | 0.222955E+10 | 0.255694E+10 | 0.00 | 0.133253E+09 | 0.137537E+09 | 0.00 | 0.157466E+11 | 0.00 | 1.04 |
September | 0.385030E+10 | 0.981316E+09 | 0.00 | 0.180684E+09 | 15262702.94 | 0.00 | 0.306053E+11 | 0.00 | 1.31 |
October | 0.900760E+10 | 32686518.71 | 0.00 | 0.233244E+09 | 717987.70 | 0.234073E+09 | 0.736046E+11 | 0.00 | 1.55 |
November | 0.127560E+11 | 0.00 | 0.00 | 0.176620E+09 | 0.00 | 0.250759E+09 | 0.964479E+11 | 0.00 | 1.17 |
December | 0.170582E+11 | 0.00 | 0.00 | 0.139242E+09 | 0.00 | 0.462171E+10 | 0.831901E+11 | 0.00 | 0.80 |
Annual Sum or Average | 0.122176E+12 | 0.104553E+11 | 0.00 | 0.157729E+10 | 0.567282E+09 | 0.135572E+11 | 0.604031E+12 | 0.00 | 1.06 |
Minimum of Months | 0.182386E+10 | 0.00 | 0.00 | 69278418.04 | 0.00 | 0.00 | 0.601986E+10 | 0.00 | 0.75 |
Maximum of Months | 0.195807E+11 | 0.392231E+10 | 0.00 | 0.233244E+09 | 0.323657E+09 | 0.548830E+10 | 0.964479E+11 | 0.00 | 1.55 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.344414E+11 | 0.00 | 0.00 | 8616184.36 | 0.00 | 0.990550E+10 | 0.714633E+10 | 0.00 | 0.65 |
February | 0.288858E+11 | 0.00 | 0.00 | 18942409.23 | 0.00 | 0.513007E+10 | 0.128269E+11 | 0.00 | 0.75 |
March | 0.301622E+11 | 0.00 | 0.00 | 35947664.75 | 0.00 | 0.503282E+09 | 0.229817E+11 | 0.00 | 1.09 |
April | 0.146900E+11 | 9310352.38 | 0.00 | 88983728.40 | 69733.78 | 0.00 | 0.317660E+11 | 0.00 | 1.51 |
May | 0.103655E+11 | 0.233758E+09 | 0.00 | 90373150.46 | 6162942.22 | 0.00 | 0.271569E+11 | 0.00 | 1.48 |
June | 0.521820E+10 | 0.335871E+10 | 0.00 | 71311078.77 | 47662268.23 | 0.00 | 0.119253E+11 | 0.00 | 1.26 |
July | 0.181094E+10 | 0.386562E+10 | 0.00 | 61122103.55 | 0.308809E+09 | 0.00 | 0.539884E+10 | 0.00 | 1.07 |
August | 0.231507E+10 | 0.206898E+10 | 0.00 | 0.103769E+09 | 0.108966E+09 | 0.00 | 0.126998E+11 | 0.00 | 1.31 |
September | 0.619460E+10 | 0.550989E+09 | 0.00 | 97304504.85 | 24449147.32 | 0.00 | 0.176023E+11 | 0.00 | 1.24 |
October | 0.202682E+11 | 17450819.39 | 0.00 | 65206172.25 | 1841215.03 | 0.282807E+09 | 0.223473E+11 | 0.00 | 1.20 |
November | 0.336089E+11 | 0.00 | 0.00 | 19965501.31 | 0.00 | 0.866413E+09 | 0.158734E+11 | 0.00 | 0.83 |
December | 0.347823E+11 | 0.00 | 0.00 | 8514389.83 | 0.00 | 0.895023E+10 | 0.731148E+10 | 0.00 | 0.57 |
Annual Sum or Average | 0.222743E+12 | 0.101048E+11 | 0.00 | 0.670056E+09 | 0.497960E+09 | 0.256383E+11 | 0.195036E+12 | 0.00 | 1.08 |
Minimum of Months | 0.181094E+10 | 0.00 | 0.00 | 8514389.83 | 0.00 | 0.00 | 0.539884E+10 | 0.00 | 0.57 |
Maximum of Months | 0.347823E+11 | 0.386562E+10 | 0.00 | 0.103769E+09 | 0.308809E+09 | 0.990550E+10 | 0.317660E+11 | 0.00 | 1.51 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.117676E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.282356E+10 | 0.00 | 0.00 | 0.34 |
February | 0.151782E+10 | 0.00 | 0.00 | 3388.99 | 0.00 | 0.190509E+10 | 12461408.81 | 0.00 | 0.35 |
March | 0.271961E+10 | 0.00 | 0.00 | 244303.61 | 0.00 | 0.698662E+09 | 0.250667E+09 | 0.00 | 0.45 |
April | 0.160565E+10 | 0.00 | 0.00 | 3370454.97 | 0.00 | 0.144954E+09 | 0.138668E+10 | 0.00 | 0.67 |
May | 0.100862E+10 | 4459655.67 | 0.00 | 6877337.76 | 2222731.62 | 17766662.41 | 0.213188E+10 | 0.00 | 0.82 |
June | 0.423020E+09 | 0.169000E+09 | 0.00 | 9091222.97 | 4760222.71 | 0.00 | 0.135290E+10 | 0.00 | 0.81 |
July | 0.188367E+09 | 0.206263E+09 | 0.00 | 8855806.52 | 30791727.28 | 0.00 | 0.609010E+09 | 0.00 | 0.73 |
August | 0.269138E+09 | 0.103472E+09 | 0.00 | 11226633.16 | 13738915.44 | 0.00 | 0.124824E+10 | 0.00 | 0.83 |
September | 0.622587E+09 | 20556192.56 | 0.00 | 7230901.82 | 831627.55 | 0.00 | 0.140911E+10 | 0.00 | 0.73 |
October | 0.186561E+10 | 147849.94 | 0.00 | 2465367.08 | 69153.00 | 0.335983E+09 | 0.689889E+09 | 0.00 | 0.53 |
November | 0.231794E+10 | 0.00 | 0.00 | 119.84 | 0.00 | 0.119330E+10 | 3717531.66 | 0.00 | 0.38 |
December | 0.837511E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.314651E+10 | 0.00 | 0.00 | 0.30 |
Annual Sum or Average | 0.145526E+11 | 0.503899E+09 | 0.00 | 49365536.72 | 52414377.60 | 0.102658E+11 | 0.909456E+10 | 0.00 | 0.58 |
Minimum of Months | 0.188367E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.271961E+10 | 0.206263E+09 | 0.00 | 11226633.16 | 30791727.28 | 0.314651E+10 | 0.213188E+10 | 0.00 | 0.83 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.216526E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192240E+10 | 0.00 | 0.00 | 0.54 |
February | 0.230953E+10 | 0.00 | 0.00 | 335685.79 | 0.00 | 0.100820E+10 | 0.296985E+09 | 0.00 | 0.58 |
March | 0.213858E+10 | 0.00 | 0.00 | 2641378.61 | 0.00 | 0.370597E+09 | 0.199354E+10 | 0.00 | 0.86 |
April | 0.806156E+09 | 0.00 | 0.00 | 8887091.19 | 0.00 | 41428100.32 | 0.459029E+10 | 0.00 | 1.60 |
May | 0.555976E+09 | 4731735.15 | 0.00 | 12732657.11 | 2311214.11 | 5036381.04 | 0.447242E+10 | 0.00 | 1.81 |
June | 0.345532E+09 | 0.142761E+09 | 0.00 | 12897436.38 | 4835401.49 | 0.00 | 0.204129E+10 | 0.00 | 1.59 |
July | 0.181060E+09 | 0.236228E+09 | 0.00 | 11574248.46 | 20017324.38 | 0.00 | 0.756101E+09 | 0.00 | 1.33 |
August | 0.222901E+09 | 0.103934E+09 | 0.00 | 14598937.88 | 14247682.65 | 0.00 | 0.179559E+10 | 0.00 | 1.64 |
September | 0.513920E+09 | 17054339.60 | 0.00 | 10742806.28 | 771226.26 | 0.00 | 0.243183E+10 | 0.00 | 1.61 |
October | 0.137892E+10 | 134897.96 | 0.00 | 5458995.95 | 75303.67 | 0.213983E+09 | 0.227243E+10 | 0.00 | 1.09 |
November | 0.283017E+10 | 0.00 | 0.00 | 410041.69 | 0.00 | 0.545754E+09 | 0.432341E+09 | 0.00 | 0.64 |
December | 0.227515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178472E+10 | 0.00 | 0.00 | 0.48 |
Annual Sum or Average | 0.157232E+11 | 0.504844E+09 | 0.00 | 80279279.34 | 42258152.56 | 0.589211E+10 | 0.210828E+11 | 0.00 | 1.15 |
Minimum of Months | 0.181060E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.48 |
Maximum of Months | 0.283017E+10 | 0.236228E+09 | 0.00 | 14598937.88 | 20017324.38 | 0.192240E+10 | 0.459029E+10 | 0.00 | 1.81 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.169937E+10 | 0.00 | 0.00 | 7373643.58 | 0.00 | 0.114720E+10 | 0.494832E+10 | 0.00 | 0.76 |
February | 0.148934E+10 | 0.00 | 0.00 | 8602411.29 | 0.00 | 0.614307E+09 | 0.545157E+10 | 0.00 | 0.87 |
March | 0.159604E+10 | 0.00 | 0.00 | 8821930.46 | 0.00 | 0.431318E+09 | 0.586255E+10 | 0.00 | 1.07 |
April | 0.116952E+10 | 0.00 | 0.00 | 9927951.95 | 0.00 | 87829569.52 | 0.465671E+10 | 0.00 | 1.28 |
May | 0.108164E+10 | 6647295.34 | 0.00 | 9329393.97 | 2617123.51 | 34859097.47 | 0.297774E+10 | 0.00 | 1.07 |
June | 0.581787E+09 | 0.166582E+09 | 0.00 | 8905758.91 | 6508178.51 | 0.00 | 0.127788E+10 | 0.00 | 0.82 |
July | 0.224857E+09 | 0.230816E+09 | 0.00 | 9536787.68 | 36302954.15 | 0.00 | 0.611863E+09 | 0.00 | 0.78 |
August | 0.287144E+09 | 0.146315E+09 | 0.00 | 16093415.44 | 14961052.70 | 0.00 | 0.165428E+10 | 0.00 | 1.09 |
September | 0.460997E+09 | 43247564.70 | 0.00 | 19401959.05 | 480062.18 | 0.00 | 0.311185E+10 | 0.00 | 1.42 |
October | 0.862262E+09 | 505766.63 | 0.00 | 21294919.64 | 0.00 | 0.194685E+09 | 0.691378E+10 | 0.00 | 1.56 |
November | 0.129048E+10 | 0.00 | 0.00 | 11753974.21 | 0.00 | 0.379454E+09 | 0.772200E+10 | 0.00 | 1.03 |
December | 0.177707E+10 | 0.00 | 0.00 | 8634696.10 | 0.00 | 0.830976E+09 | 0.576787E+10 | 0.00 | 0.66 |
Annual Sum or Average | 0.125205E+11 | 0.594113E+09 | 0.00 | 0.139677E+09 | 60869371.05 | 0.372063E+10 | 0.509564E+11 | 0.00 | 1.03 |
Minimum of Months | 0.224857E+09 | 0.00 | 0.00 | 7373643.58 | 0.00 | 0.00 | 0.611863E+09 | 0.00 | 0.66 |
Maximum of Months | 0.177707E+10 | 0.230816E+09 | 0.00 | 21294919.64 | 36302954.15 | 0.114720E+10 | 0.772200E+10 | 0.00 | 1.56 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.235710E+10 | 0.00 | 0.00 | 520043.37 | 0.00 | 0.187086E+10 | 0.510612E+09 | 0.00 | 0.63 |
February | 0.232194E+10 | 0.00 | 0.00 | 1441611.07 | 0.00 | 0.110481E+10 | 0.104881E+10 | 0.00 | 0.74 |
March | 0.290800E+10 | 0.00 | 0.00 | 2845633.06 | 0.00 | 0.489901E+09 | 0.197388E+10 | 0.00 | 1.09 |
April | 0.163266E+10 | 0.00 | 0.00 | 8417607.38 | 0.00 | 42129700.77 | 0.302384E+10 | 0.00 | 1.61 |
May | 0.120286E+10 | 8762754.39 | 0.00 | 9403534.91 | 2086470.37 | 16140845.80 | 0.266755E+10 | 0.00 | 1.59 |
June | 0.564226E+09 | 0.194290E+09 | 0.00 | 9237240.90 | 4527465.61 | 0.00 | 0.121078E+10 | 0.00 | 1.28 |
July | 0.222001E+09 | 0.223445E+09 | 0.00 | 8514997.23 | 31562896.14 | 0.00 | 0.551526E+09 | 0.00 | 1.09 |
August | 0.289567E+09 | 0.116780E+09 | 0.00 | 12355070.05 | 12808418.47 | 0.00 | 0.130034E+10 | 0.00 | 1.36 |
September | 0.725964E+09 | 25366301.25 | 0.00 | 10527377.42 | 235644.45 | 0.00 | 0.163516E+10 | 0.00 | 1.34 |
October | 0.194170E+10 | 334625.05 | 0.00 | 5813690.95 | 0.00 | 0.234848E+09 | 0.196273E+10 | 0.00 | 1.21 |
November | 0.283211E+10 | 0.00 | 0.00 | 1423532.39 | 0.00 | 0.623375E+09 | 0.123500E+10 | 0.00 | 0.80 |
December | 0.232999E+10 | 0.00 | 0.00 | 444319.31 | 0.00 | 0.183597E+10 | 0.495025E+09 | 0.00 | 0.55 |
Annual Sum or Average | 0.193281E+11 | 0.568980E+09 | 0.00 | 70944658.05 | 51220895.05 | 0.621804E+10 | 0.176153E+11 | 0.00 | 1.11 |
Minimum of Months | 0.222001E+09 | 0.00 | 0.00 | 444319.31 | 0.00 | 0.00 | 0.495025E+09 | 0.00 | 0.55 |
Maximum of Months | 0.290800E+10 | 0.223445E+09 | 0.00 | 12355070.05 | 31562896.14 | 0.187086E+10 | 0.302384E+10 | 0.00 | 1.61 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 3441443.20 | 0.00 | 0.00 | 0.544226E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 7943392.35 | 0.00 | 0.00 | 0.454620E+09 | 0.00 | 0.28 |
March | 0.00 | 0.00 | 0.00 | 14178550.42 | 0.00 | 0.00 | 0.428774E+09 | 0.00 | 0.30 |
April | 0.00 | 0.00 | 0.00 | 17329017.85 | 0.00 | 0.00 | 0.291368E+09 | 0.00 | 0.29 |
May | 0.00 | 470287.07 | 0.00 | 4011528.18 | 0.00 | 0.00 | 0.215487E+09 | 0.00 | 0.29 |
June | 0.00 | 23929120.09 | 0.00 | 5225026.89 | 0.00 | 0.00 | 51587848.22 | 0.00 | 0.30 |
July | 0.00 | 0.136641E+09 | 0.00 | 362787.12 | 0.00 | 0.00 | 366831.62 | 0.00 | 0.28 |
August | 0.00 | 95242143.30 | 0.00 | 2264594.74 | 0.00 | 0.00 | 2616006.99 | 0.00 | 0.30 |
September | 0.00 | 17942941.88 | 0.00 | 2685142.72 | 0.00 | 0.00 | 56885090.59 | 0.00 | 0.29 |
October | 0.00 | 3688036.97 | 0.00 | 7786053.92 | 0.00 | 0.00 | 0.276349E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 12836189.38 | 0.00 | 0.00 | 0.425145E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 18648317.41 | 0.00 | 0.00 | 0.547246E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.00 | 0.277913E+09 | 0.00 | 96712044.17 | 0.00 | 0.00 | 0.329467E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 362787.12 | 0.00 | 0.00 | 366831.62 | 0.00 | 0.28 |
Maximum of Months | 0.00 | 0.136641E+09 | 0.00 | 18648317.41 | 0.00 | 0.00 | 0.547246E+09 | 0.00 | 0.30 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 53467073.62 | 0.00 | 0.00 | 20705389.05 | 0.00 | 0.00 | 0.540133E+10 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 65908426.15 | 0.00 | 0.00 | 0.455955E+10 | 0.00 | 0.28 |
March | 0.00 | 0.00 | 0.00 | 0.127613E+09 | 0.00 | 0.00 | 0.430064E+10 | 0.00 | 0.30 |
April | 0.00 | 0.00 | 0.00 | 0.161030E+09 | 0.00 | 0.00 | 0.292046E+10 | 0.00 | 0.29 |
May | 0.00 | 4280667.64 | 0.00 | 35827421.49 | 0.00 | 0.00 | 0.216282E+10 | 0.00 | 0.29 |
June | 0.00 | 0.237598E+09 | 0.00 | 49236351.65 | 0.00 | 0.00 | 0.520003E+09 | 0.00 | 0.30 |
July | 0.00 | 0.136227E+10 | 0.00 | 3444934.10 | 0.00 | 0.00 | 3579032.08 | 0.00 | 0.28 |
August | 0.00 | 0.986497E+09 | 0.00 | 18764545.43 | 0.00 | 0.00 | 22790332.01 | 0.00 | 0.30 |
September | 0.00 | 0.170495E+09 | 0.00 | 24596827.50 | 0.00 | 0.00 | 0.579386E+09 | 0.00 | 0.29 |
October | 0.00 | 35723286.38 | 0.00 | 69582982.71 | 0.00 | 0.00 | 0.277215E+10 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 0.113838E+09 | 0.00 | 0.00 | 0.426525E+10 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 0.163391E+09 | 0.00 | 0.00 | 0.549467E+10 | 0.00 | 0.28 |
Annual Sum or Average | 53467073.62 | 0.279686E+10 | 0.00 | 0.853940E+09 | 0.00 | 0.00 | 0.330026E+11 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 3444934.10 | 0.00 | 0.00 | 3579032.08 | 0.00 | 0.28 |
Maximum of Months | 53467073.62 | 0.136227E+10 | 0.00 | 0.163391E+09 | 0.00 | 0.00 | 0.549467E+10 | 0.00 | 0.30 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.172029E+09 | 0.00 | 0.00 | 1089432.11 | 0.00 | 0.00 | 0.371128E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 5613255.69 | 0.00 | 0.00 | 0.457046E+09 | 0.00 | 0.28 |
March | 0.00 | 0.00 | 0.00 | 11993448.06 | 0.00 | 0.00 | 0.430953E+09 | 0.00 | 0.30 |
April | 0.00 | 0.00 | 0.00 | 15816437.38 | 0.00 | 0.00 | 0.292212E+09 | 0.00 | 0.29 |
May | 0.00 | 432774.98 | 0.00 | 3468346.50 | 0.00 | 0.00 | 0.216638E+09 | 0.00 | 0.29 |
June | 0.00 | 23789555.61 | 0.00 | 4928447.50 | 0.00 | 0.00 | 52113720.69 | 0.00 | 0.30 |
July | 0.00 | 0.136230E+09 | 0.00 | 350459.60 | 0.00 | 0.00 | 365567.91 | 0.00 | 0.28 |
August | 0.00 | 99778993.88 | 0.00 | 1774671.73 | 0.00 | 0.00 | 2152694.46 | 0.00 | 0.30 |
September | 0.00 | 17045183.32 | 0.00 | 2406336.94 | 0.00 | 0.00 | 58164041.85 | 0.00 | 0.29 |
October | 0.00 | 3556358.58 | 0.00 | 6485729.03 | 0.00 | 0.00 | 0.277912E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 10446293.67 | 0.00 | 0.00 | 0.427577E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 15047733.97 | 0.00 | 0.00 | 0.550804E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.172029E+09 | 0.280833E+09 | 0.00 | 79420592.17 | 0.00 | 0.00 | 0.313707E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 350459.60 | 0.00 | 0.00 | 365567.91 | 0.00 | 0.28 |
Maximum of Months | 0.172029E+09 | 0.136230E+09 | 0.00 | 15816437.38 | 0.00 | 0.00 | 0.550804E+09 | 0.00 | 0.30 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.226225E+09 | 0.00 | 0.00 | 0.153244E+11 | 0.00 | 0.32 |
February | 0.00 | 0.00 | 0.00 | 0.422611E+09 | 0.00 | 0.00 | 0.128168E+11 | 0.00 | 0.32 |
March | 0.00 | 0.00 | 0.00 | 0.716594E+09 | 0.00 | 0.00 | 0.124513E+11 | 0.00 | 0.34 |
April | 0.00 | 0.00 | 0.00 | 0.891160E+09 | 0.00 | 0.00 | 0.113997E+11 | 0.00 | 0.33 |
May | 0.00 | 0.00 | 0.00 | 0.215825E+09 | 0.00 | 0.00 | 0.738124E+10 | 0.00 | 0.33 |
June | 0.00 | 0.306221E+09 | 0.00 | 0.320841E+09 | 0.00 | 0.00 | 0.221160E+10 | 0.00 | 0.34 |
July | 0.00 | 0.242510E+10 | 0.00 | 50496553.76 | 0.00 | 0.00 | 48566936.75 | 0.00 | 0.31 |
August | 0.00 | 12325170.79 | 0.00 | 0.946334E+09 | 0.00 | 0.00 | 0.342866E+10 | 0.00 | 0.35 |
September | 0.00 | 0.234153E+09 | 0.00 | 0.165043E+09 | 0.00 | 0.00 | 0.204991E+10 | 0.00 | 0.32 |
October | 0.00 | 24346499.02 | 0.00 | 0.418743E+09 | 0.00 | 0.00 | 0.818268E+10 | 0.00 | 0.32 |
November | 0.00 | 0.00 | 0.00 | 0.652150E+09 | 0.00 | 0.00 | 0.121119E+11 | 0.00 | 0.32 |
December | 0.00 | 0.00 | 0.00 | 0.958900E+09 | 0.00 | 0.00 | 0.161639E+11 | 0.00 | 0.31 |
Annual Sum or Average | 0.00 | 0.300215E+10 | 0.00 | 0.598492E+10 | 0.00 | 0.00 | 0.103571E+12 | 0.00 | 0.33 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 50496553.76 | 0.00 | 0.00 | 48566936.75 | 0.00 | 0.31 |
Maximum of Months | 0.00 | 0.242510E+10 | 0.00 | 0.958900E+09 | 0.00 | 0.00 | 0.161639E+11 | 0.00 | 0.35 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 09:04:19
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.484293E+12 | 0.208610E+11 | 0.00 | 0.177328E+13 | 0.646484E+12 |
February | 0.587784E+12 | 0.194462E+11 | 0.00 | 0.166421E+13 | 0.100335E+13 |
March | 0.756570E+12 | 0.189472E+11 | 0.00 | 0.191834E+13 | 0.163486E+13 |
April | 0.925082E+12 | 0.137697E+11 | 0.00 | 0.181261E+13 | 0.234332E+13 |
May | 0.981977E+12 | 0.908520E+10 | 0.00 | 0.148864E+13 | 0.145129E+13 |
June | 0.917513E+12 | 0.427105E+10 | 0.00 | 0.804678E+12 | 0.273417E+13 |
July | 0.941902E+12 | 0.166941E+10 | 0.00 | 0.305850E+12 | 0.343993E+13 |
August | 0.925801E+12 | 0.333951E+10 | 0.00 | 0.642940E+12 | 0.388249E+13 |
September | 0.758255E+12 | 0.574176E+10 | 0.00 | 0.123847E+13 | 0.193491E+13 |
October | 0.629292E+12 | 0.106450E+11 | 0.00 | 0.181513E+13 | 0.168846E+13 |
November | 0.512680E+12 | 0.169923E+11 | 0.00 | 0.195810E+13 | 0.149854E+13 |
December | 0.454664E+12 | 0.190580E+11 | 0.00 | 0.184759E+13 | 0.195489E+13 |
Annual Sum or Average | 0.887581E+13 | 0.143826E+12 | 0.00 | 0.172698E+14 | 0.242127E+14 |
Minimum of Months | 0.454664E+12 | 0.166941E+10 | 0.00 | 0.305850E+12 | 0.646484E+12 |
Maximum of Months | 0.981977E+12 | 0.208610E+11 | 0.00 | 0.195810E+13 | 0.388249E+13 |