Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:04
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** Great Falls Intl Arpt MT USA TMY3 WMO#=727750
Simulation Timestamp: 2023-10-16 09:04:16
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:16
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 32336.76 | 698.11 | 698.11 |
Net Site Energy | 32336.76 | 698.11 | 698.11 |
Total Source Energy | 93525.24 | 2019.09 | 2019.09 |
Net Source Energy | 93525.24 | 2019.09 | 2019.09 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 3494.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 3166.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 2746.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 447.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 15213.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1914.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2550.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 381.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 809.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3020.59 |
Humidification | 841.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 312.97 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 771.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 28071.14 | 4265.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5613.73 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 3494.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 3166.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 2746.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 447.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5871.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 59.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 1848.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 5.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 2550.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 381.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 809.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3020.59 |
Humidification | General | 841.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 312.97 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Water Heater | 0.00 | 771.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 3494.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 3166.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 2746.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 447.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 15213.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 1914.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 2550.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 381.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 809.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3020.59 |
Humidification | Unassigned | 841.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 312.97 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 771.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 68.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 167.30 | 92.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.12 |
Other | 369.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 606.02 | 92.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.12 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 68.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 167.30 | 92.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.12 |
Other | 369.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 606.02 | 92.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.12 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 28071.145 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 28071.145 | 100.00 |
Total On-Site and Utility Electric Sources | 28071.145 | 100.00 |
Total Electricity End Uses | 28071.145 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 5613.73 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 5613.73 | 100.00 |
Total Water End Uses | 5613.73 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 121.67 |
Time Setpoint Not Met During Occupied Cooling | 514.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5943.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MT_GREATFALLS
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| HEATSYS1 BOILER | CENTRAL BOILER |DXReportMonthly
| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |FanReportMonthly
| CAV_BAS FAN | VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:16
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:04 |
RunPeriod | RUNPERIOD 1 |
Weather File | Great Falls Intl Arpt MT USA TMY3 WMO#=727750 |
Latitude [deg] | 47.47 |
Longitude [deg] | -111.4 |
Elevation [m] | 1117.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 3476.85 | 1043.06 | 695.37 | 1043.06 | 695.37 |
Gross Window-Wall Ratio [%] | 28.54 | 28.54 | 28.54 | 28.54 | 28.54 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 3476.85 | 1043.06 | 695.37 | 1043.06 | 695.37 |
Gross Window-Wall Ratio [%] | 28.54 | 28.54 | 28.54 | 28.54 | 28.54 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 7.6202 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.6202 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.6202 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.6202 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 7.6202 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 7.6202 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 7.6202 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 7.6202 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 86.92 | 86.92 | 7.6202 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 57.95 | 57.95 | 7.6202 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 86.92 | 86.92 | 7.6202 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 57.95 | 57.95 | 7.6202 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 7.6202 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 7.6202 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 7.6202 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 7.6202 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.5114 | 18.58 | 215.2992 |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.5114 | 18.58 | 215.2992 |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.5114 | 18.58 | 215.2992 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 7.6202 | 18.58 | 484.4232 |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 3476.85 | 3476.85 | 7.6661 | 18.58 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 3476.85 | 3476.85 | 7.6661 | 18.58 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 2779.43 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 7.6202 | 18.58 | 4.8418 | |
CORE_BOTTOM | 2496.12 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 7.6202 | 18.58 | 8.0697 | |
CORE_MID | 2496.12 | Yes | Yes | 10.00 | CORE_MID | GENERAL | CORE_MID | 7.6202 | 18.58 | 8.0696 | |
CORE_TOP | 2496.12 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 7.6202 | 18.58 | 8.0696 | |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 7.6202 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 7.6202 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 7.6202 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 7.6202 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 7.6202 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 7.6202 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 7.6202 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 7.6202 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 7.6202 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 7.6202 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 7.6202 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 7.6202 | 18.58 | 8.0699 | |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | GROUNDFLOOR_PLENUM | GENERAL | GROUNDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 10.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_BOT_ZN_6 | GENERAL | DATACENTER_BOT_ZN_6 | 12.5114 | 18.58 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 10.00 | DATACENTER_MID_ZN_6 | GENERAL | DATACENTER_MID_ZN_6 | 12.5114 | 18.58 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_TOP_ZN_6 | GENERAL | DATACENTER_TOP_ZN_6 | 12.5114 | 18.58 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1.00 | DATACENTER_BASEMENT_ZN_6 | GENERAL | DATACENTER_BASEMENT_ZN_6 | 7.6202 | 18.58 | 484.4232 | |
Total | 46320.38 | 7.6661 | 9.29 | 17.8789 | |||||||
Conditioned Total | 46320.38 | 7.6661 | 9.29 | 17.8789 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 42757.27 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 46320.38 | 46320.38 | 0.00 | 42757.27 | 2.3561 | 60.38 | 10.8345 |
Total | 46320.38 | 46320.38 | 0.00 | 42757.27 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:16
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 07-AUG-15:39 | 09-JAN-07:10 | - | - | - | - | - | - | - | - | - | - | 17-JUL-15:00 |
Heating | 0.00 | 2355196.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 414367.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 234435.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 794004.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 83146.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 283819.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 52664.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 80284.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 16886.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 20143.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1959607.51 | 2375340.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 2355196.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 414367.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 234435.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 320838.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 3711.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 79171.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 263.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 283819.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 52664.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 80284.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 16886.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 20143.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:16
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 3787.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 10028.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 8696.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 1418.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 48180.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 6062.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 8077.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1209.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 2562.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 2664.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 836.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 88901.32 | 4623.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 81.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 216.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 187.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 30.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1040.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 130.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 174.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 26.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 55.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 57.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 18.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1919.27 | 99.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 81.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 216.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 187.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 30.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1040.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 130.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 174.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 26.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 55.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 57.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 18.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1919.27 | 99.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:16
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
BASEMENT DIRECT AIR | 5.98 |
DATACENTER_BOT_ZN_6 DIRECT AIR | 0.562174 |
DATACENTER_MID_ZN_6 DIRECT AIR | 5.38 |
DATACENTER_TOP_ZN_6 DIRECT AIR | 0.548359 |
DATACENTER_BASEMENT_ZN_6 DIRECT AIR | 24.39 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 6.39 | 0.297693 | 0.308000 | 1.97 | 0.793849 | 0.500000 | 0.001280 | 0.000232 | 1.97 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 59.93 | 0.317358 | 0.322000 | 19.30 | 0.846289 | 0.500000 | 0.001201 | 0.004573 | 19.30 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 5.87 | 0.324303 | 0.340000 | 1.99 | 0.864807 | 0.500000 | 0.001175 | 0.001001 | 3.90 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 1.03 | 0.231235 | 0.239000 | 0.246841 | 0.616625 | 0.500000 | 0.001648 | 0.000175 | 0.682446 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 1.30 | 0.117935 | 0.200000 | 0.260999 | 0.314494 | 0.500000 | 0.003231 | 0.000120 | 0.468499 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.65 | 0.145165 | 0.200000 | 0.329041 | 0.387106 | 0.500000 | 0.002625 | 0.000192 | 0.750352 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 1.64 | 0.094022 | 0.200000 | 0.327382 | 0.300000 | 0.500000 | 0.004052 | 0.000100 | 0.389269 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 9.77 | 0.244508 | 0.249000 | 2.43 | 0.652020 | 0.500000 | 0.001558 | 0.002504 | 9.77 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 13.77 | 0.111757 | 0.200000 | 2.75 | 0.300000 | 0.500000 | 0.003409 | 0.001661 | 6.48 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 16.58 | 0.144025 | 0.200000 | 3.32 | 0.384067 | 0.500000 | 0.002645 | 0.002534 | 9.89 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 14.84 | 0.103707 | 0.200000 | 2.97 | 0.300000 | 0.500000 | 0.003674 | 0.001628 | 6.35 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 1.29 | 0.185614 | 0.225000 | 0.289496 | 0.494972 | 0.500000 | 0.002053 | 0.000330 | 1.29 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.38 | 0.111413 | 0.200000 | 0.276279 | 0.300000 | 0.500000 | 0.003420 | 0.000218 | 0.848943 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.79 | 0.133137 | 0.200000 | 0.358768 | 0.355031 | 0.500000 | 0.002862 | 0.000333 | 1.30 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.58 | 0.097242 | 0.200000 | 0.316540 | 0.300000 | 0.500000 | 0.003918 | 0.000217 | 0.846961 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 26556.58 | 0.000232 | 565.02 |
CORE_MID VAV BOX REHEAT COIL | 522716.38 | 0.004573 | 13324.09 |
CORE_TOP VAV BOX REHEAT COIL | 114474.95 | 0.001001 | 3020.42 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 20010.40 | 0.000175 | 527.73 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 13735.44 | 0.000120 | 362.22 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 21997.98 | 0.000192 | 580.11 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 11416.89 | 0.000100 | 301.13 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 286203.60 | 0.002504 | 7545.67 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 189849.57 | 0.001661 | 5005.23 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 289677.87 | 0.002534 | 7637.22 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 186046.86 | 0.001628 | 4905.02 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 37689.39 | 0.000330 | 993.53 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 24867.16 | 0.000218 | 655.51 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 38120.11 | 0.000333 | 1004.88 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 24809.04 | 0.000217 | 653.98 |
VAV_BOT WITH REHEAT HEATING COIL | 103606.04 | 0.000906 | 1555.48 |
VAV_MID WITH REHEAT HEATING COIL | 1064885.03 | 0.009316 | 15542.29 |
VAV_TOP WITH REHEAT HEATING COIL | 104739.21 | 0.000916 | 1585.46 |
CAV_BAS HEATING COIL | 288343.86 | 0.002523 | 6142.17 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT | 6.00 | 3.13 | 12.01 | 3.37 | 10.35 | 10.35 | 0.300000 | 0.325541 | 10.35 |
VAV_MID WITH REHEAT | 57.45 | 30.77 | 114.89 | 49.56 | 95.65 | 95.65 | 0.300000 | 0.518201 | 95.65 |
VAV_TOP WITH REHEAT | 5.95 | 3.24 | 11.91 | 8.18 | 10.80 | 10.80 | 0.300000 | 0.757893 | 10.80 |
CAV_BAS | 5.98 | 5.98 | 5.98 | 5.98 | 5.98 | 5.98 | 1.00 | 1.00 | 5.98 |
AIRLOOP DATACENTER BASEMENT | 24.39 | 24.39 | 24.39 | 24.39 | 24.39 | 24.39 | 1.00 | 0.999990 | 24.39 |
AIRLOOP DATACENTER BOT | 0.562174 | 0.562174 | 0.562174 | 0.562174 | 0.562174 | 0.562174 | 1.00 | 1.00 | 0.562174 |
AIRLOOP DATACENTER MID | 5.38 | 5.38 | 5.38 | 5.38 | 5.38 | 5.38 | 1.00 | 1.00 | 5.38 |
AIRLOOP DATACENTER TOP | 0.548359 | 0.548359 | 0.548359 | 0.548359 | 0.548359 | 0.548359 | 1.00 | 1.00 | 0.548359 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 10.35 | |
VAV_MID WITH REHEAT_OA_CONTROLLER | 95.65 | |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 10.80 | |
CAV_BAS_OA_CONTROLLER | 5.98 | 1.20 |
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | 24.39 | 0.338393 |
AIRLOOP DATACENTER BOT_OA_CONTROLLER | 0.562174 | 0.015632 |
AIRLOOP DATACENTER MID_OA_CONTROLLER | 5.38 | 0.156323 |
AIRLOOP DATACENTER TOP_OA_CONTROLLER | 0.548359 | 0.015632 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT COOLING COIL | 26.34 | 6.67 | 10.68 | 0.007084 | 0.007000 | 176035.57 | 0.007489 | 10.35 |
VAV_MID WITH REHEAT COOLING COIL | 26.57 | 6.67 | 10.68 | 0.007075 | 0.007000 | 1648180.26 | 0.070117 | 95.65 |
VAV_TOP WITH REHEAT COOLING COIL | 26.22 | 6.67 | 10.68 | 0.007074 | 0.007000 | 181969.89 | 0.007741 | 10.80 |
CAV_BAS COOLING COIL | 25.95 | 6.67 | 11.22 | 0.007253 | 0.007000 | 98522.43 | 0.004191 | 5.98 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 10.35 |
VAV_MID WITH REHEAT FAN | 95.65 |
VAV_TOP WITH REHEAT FAN | 10.80 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.007489 | 0.000064 |
VAV_BOT WITH REHEAT_HEATC_CONTROLLER | 0.000906 | |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.070117 | 0.000007 |
VAV_MID WITH REHEAT_HEATC_CONTROLLER | 0.009316 | |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.007741 | 0.000062 |
VAV_TOP WITH REHEAT_HEATC_CONTROLLER | 0.000916 | |
CAV_BAS_COOLC_CONTROLLER | 0.004191 | 0.000114 |
CAV_BAS_HEATC_CONTROLLER | 0.002523 |
Design Size Maximum Flow Rate [m3/s] | |
CAV_BAS FAN | 5.98 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Total Cooling Capacity [W] | Design Size Rated Sensible Cooling Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | 24.39 | 463695.08 | 260952.55 | 0.011356 |
AIRLOOP DATACENTER BOT COOLING COIL | 0.562174 | 10386.00 | 5906.25 | 0.000254 |
AIRLOOP DATACENTER MID COOLING COIL | 5.38 | 99506.15 | 56574.76 | 0.002437 |
AIRLOOP DATACENTER TOP COOLING COIL | 0.548359 | 10132.77 | 5761.53 | 0.000248 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | 24.39 | 24.39 | 24.39 | 24.39 | 463695.08 | 463695.08 | 24207.99 | 1.00 |
AIRLOOP DATACENTER BOT DXAC HEAT PUMP | 0.562174 | 0.562174 | 0.562174 | 0.562174 | 10386.00 | 10386.00 | 1118.31 | 1.00 |
AIRLOOP DATACENTER MID DXAC HEAT PUMP | 5.38 | 5.38 | 5.38 | 5.38 | 99506.15 | 99506.15 | 11183.09 | 1.00 |
AIRLOOP DATACENTER TOP DXAC HEAT PUMP | 0.548359 | 0.548359 | 0.548359 | 0.548359 | 10132.77 | 10132.77 | 1118.31 | 1.00 |
Design Size Maximum Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | 24.39 |
AIRLOOP DATACENTER BOT SUPPLY FAN | 0.562174 |
AIRLOOP DATACENTER MID SUPPLY FAN | 5.38 |
AIRLOOP DATACENTER TOP SUPPLY FAN | 0.548359 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Heating Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | 24.39 | 463695.08 | 0.011356 |
AIRLOOP DATACENTER BOT HEATING COIL | 0.562174 | 10386.00 | 0.000254 |
AIRLOOP DATACENTER MID HEATING COIL | 5.38 | 99506.15 | 0.002437 |
AIRLOOP DATACENTER TOP HEATING COIL | 0.548359 | 10132.77 | 0.000248 |
Design Size Nominal Capacity [W] | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | 24207.99 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | 1118.31 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | 11183.09 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | 1118.31 |
Design Size Nominal Capacity Volume [m3/s] | User-Specified Nominal Capacity Volume [m3/s] | Design Size Rated Power [W] | User-Specified Rated Power [W] | |
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | 0.000190 | 0.000037 | 96450.70 | 100000.00 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.089539 | 18450.70 | |
HEATSYS1 PUMP | 0.029480 | 8878.08 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.089539 | 10.74 |
HEATSYS1 | 0.029480 | 3.54 |
COOLSYS1_SUPPLY | 0.089539 | 10.74 |
SINGLE WATER PLANT LOOP | 0.014295 | 1.72 |
SWHSYS1 | 0.000440 | 0.052800 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.089539 | 0.089539 | 375840.74 | 5.60 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 3369746.34 | 3369746.34 | 0.029480 |
CENTRAL BOILER | 588842.37 | 576151.43 | 0.014295 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP | 0.089539 | 12774.04 |
PLANT CIRC PUMP | 0.014295 | 3646.01 |
SWHSYS1 PUMP | 0.000440 | 5.96 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Water Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.089539 | 0.045101 | 1062739.34 | 1067780.64 | 0.052841 |
COOLSYS1 CHILLER2 | 0.089539 | 0.045101 | 1062739.34 | 1067780.64 | 0.052841 |
Design Water Flow Rate [m3/s] | Air Flow Rate at High Fan Speed [m3/s] | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | Air Flow Rate at Low Fan Speed [m3/s] | Fan Power at Low Fan Speed [W] | U-factor Times Area Value at Low Fan Speed [W/C] | |
CENTRAL TOWER | 0.014295 | 139666.47 | 55853.20 | 69833.23 | 7879.72 | 21056.18 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000440 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.105681 | 12.68 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.105681 | 31828.82 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 46.70 | 1268490.47 | 9.34 | 158561.31 |
TOWERWATERSYS COOLTOWER 2 | 46.70 | 1268490.47 | 9.34 | 158561.31 |
Design Water Flow Rate [m3/s] Equipment # 47 | |
WSHPPLANT OPERATION SCHEME | 0.054885 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:16
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:16
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:16
VersionVersion ID | |
1 | 22.1.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 8.60 | 2.80 | -4.10 | -8.80 | -2.20 | 0.30 | 6.70 | 10.10 | 16.50 | 20.60 | 19.20 | 14.70 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Great Falls Intl Arpt MT USA TMY3 WMO#=727750 | 47.47 | -111.38 | -7.00 | 1117.00 | 88606 | 1.0531 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 7.03 | 29.40 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 105.88 | 86.92 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 71.89 | 57.95 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 105.88 | 86.92 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 71.89 | 57.95 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 7.620 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 12.462 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 12.511 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 227.811 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 12.511 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 227.811 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 12.511 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 227.811 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 18.579 | 5.382E-002 | 7.620 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 492.043 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DATACENTER_BOT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | DATACENTER_MID_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | DATACENTER_TOP_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | DATACENTER_BASEMENT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 42.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 42 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_OFFICE | BASEMENT | 2779.43 | 149.6 | 21179.739 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 21179.739 |
2 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 2496.12 | 134.4 | 19020.895 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 19020.895 |
3 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 2496.12 | 134.4 | 19020.895 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 19020.895 |
4 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 2496.12 | 134.4 | 19020.895 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 19020.895 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2388.263 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2388.263 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1539.088 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1539.088 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2388.315 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2388.315 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1539.088 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1539.088 |
9 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2388.263 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2388.263 |
10 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1539.088 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1539.088 |
11 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2388.315 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2388.315 |
12 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1539.088 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1539.088 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2388.263 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2388.263 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1539.088 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1539.088 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2388.315 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2388.315 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1539.088 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1539.088 |
17 | DATACENTER_BASEMENT_LIGHTS | LTG_SCH_OFFICE | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 5971.780 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5971.780 |
18 | DATACENTER_BOT_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 452.948 | 12.511 | 232.447 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 452.948 |
19 | DATACENTER_MID_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 452.948 | 12.511 | 232.447 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 452.948 |
20 | DATACENTER_TOP_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 452.948 | 12.511 | 232.447 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 452.948 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 379632.522 | 484.423 | 9000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
9 | NONRES_EXT_WALL_GRD | 20 | 3 | 9 | 0.167 | 1.147 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | NONRES_EXT_WALL_MID | 21 | 3 | 9 | 0.167 | 1.072 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | NONRES_EXT_WALL_TOP | 22 | 3 | 9 | 0.167 | 1.485 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | BASEMENT_WALL_EAST_CFACTOR | 39 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_SOUTH_CFACTOR | 40 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BASEMENT_WALL_NORTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 42 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 43 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 44 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7043 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7653 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5060 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
32 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
33 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
34 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
35 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
47 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
48 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
49 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
50 | 9 | 0.18777991E-14 | 0.39318316E-16 | -0.13945218E-09 | -0.53504997E-17 |
51 | 8 | 0.20428582E-07 | 0.15263370E-12 | 0.36243033E-03 | -0.23227999E-09 |
52 | 7 | -0.11782580E-01 | 0.80534805E-08 | -0.22424787E-01 | 0.13397222E-03 |
53 | 6 | 0.39287835 | 0.28244099E-05 | 0.46145507 | -0.46007477E-02 |
54 | 5 | -5.0688419 | 0.10619431E-03 | -4.3595097 | 0.61674563E-01 |
55 | 4 | 32.464389 | 0.87416084E-03 | 21.120657 | -0.41497362 |
56 | 3 | -110.08041 | 0.19158287E-02 | -54.991947 | 1.4986409 |
57 | 2 | 195.99541 | 0.10830235E-02 | 77.295382 | -2.8826816 |
58 | 1 | -170.74495 | 0.11614893E-03 | -55.086664 | 2.7382339 |
59 | 0 | 57.057407 | 0.66454694E-06 | 15.586789 | |
60 | 9 | -0.35772101E-15 | 0.35300796E-16 | -0.14299885E-09 | 0.43432634E-17 |
61 | 8 | 0.20929462E-07 | 0.14329262E-12 | 0.36779278E-03 | -0.23797519E-09 |
62 | 7 | -0.11942934E-01 | 0.75175974E-08 | -0.22655780E-01 | 0.13579551E-03 |
63 | 6 | 0.39723595 | 0.26304111E-05 | 0.46517473 | -0.46521131E-02 |
64 | 5 | -5.1113728 | 0.98704798E-04 | -4.3881162 | 0.62201922E-01 |
65 | 4 | 32.652551 | 0.81106559E-03 | 21.232557 | -0.41747184 |
66 | 3 | -110.48086 | 0.17747443E-02 | -55.213214 | 1.5044261 |
67 | 2 | 196.39242 | 0.10018625E-02 | 77.498162 | -2.8889858 |
68 | 1 | -170.89164 | 0.10730575E-03 | -55.145342 | 2.7408049 |
69 | 0 | 57.057407 | 0.61309336E-06 | 15.576862 | |
70 | 9 | 0.62620750E-15 | 0.53459335E-16 | -0.12331227E-09 | -0.46720721E-17 |
71 | 8 | 0.18149323E-07 | 0.19273772E-12 | 0.33743729E-03 | -0.20636407E-09 |
72 | 7 | -0.11033179E-01 | 0.10459398E-07 | -0.21344557E-01 | 0.12545125E-03 |
73 | 6 | 0.37251059 | 0.37098382E-05 | 0.44401761 | -0.43606628E-02 |
74 | 5 | -4.8700128 | 0.14084247E-03 | -4.2251796 | 0.59209231E-01 |
75 | 4 | 31.584523 | 0.11694623E-02 | 20.594689 | -0.40329204 |
76 | 3 | -108.20727 | 0.25827026E-02 | -53.951706 | 1.4715810 |
77 | 2 | 194.13760 | 0.14699268E-02 | 76.342983 | -2.8531817 |
78 | 1 | -170.05820 | 0.15862972E-03 | -54.812808 | 2.7261979 |
79 | 0 | 57.057407 | 0.91374417E-06 | 15.634538 | |
80 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
81 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
82 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
83 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
84 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
85 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
86 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
87 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
88 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
89 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
90 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
91 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
92 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
93 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
94 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
95 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
96 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
97 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
98 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
99 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
100 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
101 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
102 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
103 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
104 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
105 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
106 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
107 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
108 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
109 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
110 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
111 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
112 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
113 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
114 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
115 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
116 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
117 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
118 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
119 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
120 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
121 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
122 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
123 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
124 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
125 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
126 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
127 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.3622_SHGC_EAST_0.4 | 35 | 1 | VerySmooth | 2.058 | 2.058 | 1.000 | 0.401 | ||
2 | WINDOW_U_0.3622_SHGC_SOUTH_0.4 | 36 | 1 | VerySmooth | 2.058 | 2.058 | 1.000 | 0.401 | ||
3 | WINDOW_U_0.3622_SHGC_WEST_0.4 | 37 | 1 | VerySmooth | 2.058 | 2.058 | 1.000 | 0.401 | ||
4 | WINDOW_U_0.3622_SHGC_NORTH_0.4 | 38 | 1 | VerySmooth | 2.058 | 2.058 | 1.000 | 0.401 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 3.63487E-002 | 0.31435 | 0.48131 | 0.48131 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11603 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 3.63487E-002 | 0.31435 | 0.48131 | 0.48131 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11603 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 3.63487E-002 | 0.31435 | 0.48131 | 0.48131 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11603 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 3.63487E-002 | 0.31435 | 0.48131 | 0.48131 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11603 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_BOT_ZN_3 | 5 | 0 |
2 | PERIMETER_BOT_ZN_2 | 3 | 0 |
3 | PERIMETER_BOT_ZN_1 | 5 | 0 |
4 | PERIMETER_BOT_ZN_4 | 3 | 0 |
5 | PERIMETER_MID_ZN_3 | 1 | 0 |
6 | PERIMETER_MID_ZN_2 | 1 | 0 |
7 | PERIMETER_MID_ZN_1 | 1 | 0 |
8 | PERIMETER_MID_ZN_4 | 1 | 0 |
9 | PERIMETER_TOP_ZN_3 | 1 | 0 |
10 | PERIMETER_TOP_ZN_2 | 1 | 0 |
11 | PERIMETER_TOP_ZN_1 | 1 | 0 |
12 | PERIMETER_TOP_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_BOT_ZN_3 | 0 | |
2 | PERIMETER_BOT_ZN_2 | 0 | |
3 | PERIMETER_BOT_ZN_1 | 0 | |
4 | PERIMETER_BOT_ZN_4 | 0 | |
5 | PERIMETER_MID_ZN_3 | 0 | |
6 | PERIMETER_MID_ZN_2 | 0 | |
7 | PERIMETER_MID_ZN_1 | 0 | |
8 | PERIMETER_MID_ZN_4 | 0 | |
9 | PERIMETER_TOP_ZN_3 | 0 | |
10 | PERIMETER_TOP_ZN_2 | 0 | |
11 | PERIMETER_TOP_ZN_1 | 0 | |
12 | PERIMETER_TOP_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 1.1356 | 87921.3 | 0.496 | 7.5104E-002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 4.384E-005 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.4803E-003 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.4823E-003 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.1356E-003 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.1372E-003 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.5287E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.5299E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.9650E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.9658E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.5256E-003 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.6567E-003 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.1737E-003 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.2878E-003 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.5607E-003 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.6550E-003 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.9845E-003 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.0341E-003 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1338 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.1635E-002 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1537 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 9.5149E-002 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 9.5460E-002 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.1244E-002 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.1298E-002 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.4495E-002 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.5360E-003 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.7125E-003 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.1852E-003 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.3502E-003 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.5692E-003 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.6882E-003 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.9850E-003 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.0355E-003 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.4802E-003 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.4826E-003 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.1354E-003 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.1375E-003 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.5286E-003 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.5302E-003 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.9650E-003 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.9657E-003 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.9356E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.3574E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.8593E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.3554E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.2341E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.3671E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.3625E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.3966E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.9134E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.0176E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.8337E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.8818E-002 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.8114E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.4776E-002 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.2472E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.5878E-002 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.8013E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.9010E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.6817E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.7553E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.1933E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.2235E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.3626E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.3972E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1610E-003 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1631E-003 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.8300E-003 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8318E-003 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.6002E-003 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.6015E-003 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.9651E-003 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.9658E-003 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.2071E-003 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.3238E-003 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.8688E-003 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.9639E-003 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.6326E-003 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7051E-003 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.9850E-003 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.0356E-003 |
81 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.5928E-002 |
82 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.0905E-002 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7862E-002 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5915E-002 |
85 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7858E-002 |
86 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1027E-002 |
87 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.1298E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.4491E-002 |
89 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.2047E-003 |
90 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.3243E-003 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.8651E-003 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.9584E-003 |
93 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.6259E-003 |
94 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.6839E-003 |
95 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.9846E-003 |
96 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.0341E-003 |
97 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1609E-003 |
98 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1629E-003 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.8299E-003 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8315E-003 |
101 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.6000E-003 |
102 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.6011E-003 |
103 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.9650E-003 |
104 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.9657E-003 |
105 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.0671E-003 |
106 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.1729E-003 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.7366E-003 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.8133E-003 |
109 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.6833E-003 |
110 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.7100E-003 |
111 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.3627E-003 |
112 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.3972E-003 |
113 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.5138E-002 |
114 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.4180E-002 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.0462E-002 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.1137E-002 |
117 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.7632E-002 |
118 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.0352E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.2472E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.5878E-002 |
121 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.1557E-003 |
122 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.4083E-003 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.8546E-003 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.1297E-003 |
125 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.7200E-003 |
126 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.8324E-003 |
127 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.3624E-003 |
128 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.3966E-003 |
129 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1307 |
130 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1040 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1464 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1201 |
133 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1017 |
134 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 5.6289E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 4.7714E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 2.3115E-002 |
137 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 6.7452E-002 |
138 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 4.1233E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 6.6590E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.9809E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 6.5532E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.4116E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.8823E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.3360E-002 |
145 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.2473E-002 |
146 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 3.0013E-002 |
147 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.3722E-002 |
148 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.3702E-002 |
149 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.3677E-002 |
150 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.8123E-002 |
151 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.7714E-002 |
152 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.3111E-002 |
153 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.2277E-002 |
154 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.3362E-002 |
155 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 4.7188E-002 |
156 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.9703E-002 |
157 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.4291E-002 |
158 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.8571E-002 |
159 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 4.8823E-002 |
160 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.3360E-002 |
161 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1305 |
162 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1041 |
163 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1462 |
164 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1202 |
165 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1017 |
166 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 5.6394E-002 |
167 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 4.7768E-002 |
168 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 2.3160E-002 |
169 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 6.7405E-002 |
170 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 4.1270E-002 |
171 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 6.6553E-002 |
172 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.9849E-002 |
173 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 6.5544E-002 |
174 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.4174E-002 |
175 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.8875E-002 |
176 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.3404E-002 |
177 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.2416E-002 |
178 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 3.0024E-002 |
179 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.3682E-002 |
180 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.3712E-002 |
181 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.3694E-002 |
182 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.8151E-002 |
183 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.7768E-002 |
184 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.3156E-002 |
185 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.2232E-002 |
186 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.3386E-002 |
187 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 4.7155E-002 |
188 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.9726E-002 |
189 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.4304E-002 |
190 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.8618E-002 |
191 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 4.8875E-002 |
192 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.3404E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 72467.57236 | 72467.57236 | 5.98366 | 5.98366 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 21.56000 | 6.28881E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20016 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
3 | CORE_BOTTOM | Cooling | 77382.85800 | 77382.85800 | 6.38927 | 6.38927 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 21.56000 | 6.28881E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
4 | CORE_BOTTOM | Heating | 9227.34779 | 9227.34779 | 0.44638 | 1.07782 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
5 | CORE_MID | Cooling | 726059.13540 | 726059.13540 | 59.93363 | 59.93363 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 21.56000 | 6.28881E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
6 | CORE_MID | Heating | 352773.19363 | 352773.19363 | 17.08187 | 17.08187 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
7 | CORE_TOP | Cooling | 70405.34942 | 70405.34942 | 5.86503 | 5.86503 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 33.08000 | 6.30633E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
8 | CORE_TOP | Heating | 80130.06328 | 80130.06328 | 3.90018 | 3.90018 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 12398.39183 | 12398.39183 | 1.03281 | 1.03281 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 33.40000 | 6.30683E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 14004.02258 | 14004.02258 | 0.68245 | 0.68245 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 15666.04728 | 15666.04728 | 1.30500 | 1.30500 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:50:00 | 24.09333 | 6.29258E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 9611.96117 | 9611.96117 | 0.46850 | 0.46850 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 19750.08708 | 19750.08708 | 1.64521 | 1.64521 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 33.13333 | 6.30642E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 15393.54707 | 15393.54707 | 0.75035 | 0.75035 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 19650.58511 | 19650.58511 | 1.63691 | 1.63691 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 30.36000 | 6.30211E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 7991.39497 | 7991.39497 | 0.38927 | 0.38927 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
17 | PERIMETER_MID_ZN_3 | Cooling | 116727.74467 | 116727.74467 | 9.72351 | 9.72351 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 33.40000 | 6.30683E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 200265.88498 | 200265.88498 | 9.76741 | 9.76741 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 165322.36306 | 165322.36306 | 13.77135 | 13.77135 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 25.96000 | 6.29539E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 132841.97254 | 132841.97254 | 6.47935 | 6.47935 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 199065.55384 | 199065.55384 | 16.58224 | 16.58224 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 33.26667 | 6.30663E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 202694.95481 | 202694.95481 | 9.88613 | 9.88613 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 178155.44661 | 178155.44661 | 14.84036 | 14.84036 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 30.36000 | 6.30211E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 130183.00372 | 130183.00372 | 6.34945 | 6.34945 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 13373.88723 | 13373.88723 | 1.11405 | 1.11405 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 33.08000 | 6.30633E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 26368.98672 | 26368.98672 | 1.28665 | 1.28665 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 16583.45271 | 16583.45271 | 1.38140 | 1.38140 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 26.41333 | 6.29608E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 17397.95006 | 17397.95006 | 0.84894 | 0.84894 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 21534.71606 | 21534.71606 | 1.79384 | 1.79384 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 33.40000 | 6.30683E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 26670.13923 | 26670.13923 | 1.30137 | 1.30137 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 19000.04970 | 19000.04970 | 1.58270 | 1.58270 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 30.36000 | 6.30211E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 17357.27514 | 17357.27514 | 0.84696 | 0.84696 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 8556.18890 | 8556.18890 | 0.56217 | 0.56217 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | 26.28000 | 6.29588E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | -27.60000 | 3.41898E-004 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
35 | DATACENTER_MID_ZN_6 | Cooling | 81947.67577 | 81947.67577 | 5.38430 | 5.38430 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | 26.28000 | 6.29588E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15632 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | -27.60000 | 3.41898E-004 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
37 | DATACENTER_TOP_ZN_6 | Cooling | 8345.90462 | 8345.90462 | 0.54836 | 0.54836 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | 26.57333 | 6.29632E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | -27.60000 | 3.41898E-004 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 371264.36442 | 371264.36442 | 24.39313 | 24.39313 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 18.84000 | 6.28481E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33839 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:50:00 | -27.60000 | 3.41898E-004 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV_BOT WITH REHEAT | Cooling | Sensible | 145952.73 | 10.34707 | 10.34707 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV_BOT WITH REHEAT | Heating | Sensible | 108514.25 | 3.36839 | 3.36839 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 |
3 | VAV_MID WITH REHEAT | Cooling | Sensible | 1352455.44 | 95.64675 | 95.64675 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | VAV_MID WITH REHEAT | Heating | Sensible | 1083253.27 | 49.56421 | 49.56421 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 |
5 | VAV_TOP WITH REHEAT | Cooling | Sensible | 152729.72 | 10.79849 | 10.79849 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | VAV_TOP WITH REHEAT | Heating | Sensible | 108507.10 | 8.18410 | 8.18410 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 02:30:00 |
7 | CAV_BAS | Cooling | Sensible | 73759.58 | 5.98366 | 5.98366 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | CAV_BAS | Heating | Sensible | 85856.97 | 1.20016 | 1.20016 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
9 | AIRLOOP DATACENTER BASEMENT | Cooling | Sensible | 368358.21 | 24.39337 | 24.39337 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | AIRLOOP DATACENTER BASEMENT | Heating | Sensible | 24207.99 | 0.33839 | 0.33839 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
11 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 8435.21 | 0.56217 | 0.56217 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | AIRLOOP DATACENTER BOT | Heating | Sensible | 1118.31 | 1.56323E-002 | 1.56323E-002 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
13 | AIRLOOP DATACENTER MID | Cooling | Sensible | 80782.92 | 5.38430 | 5.38430 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | AIRLOOP DATACENTER MID | Heating | Sensible | 11183.09 | 0.15632 | 0.15632 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
15 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 8232.33 | 0.54836 | 0.54836 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
16 | AIRLOOP DATACENTER TOP | Heating | Sensible | 1118.31 | 1.56323E-002 | 1.56323E-002 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | BASEMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 5.98366 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 6.38927 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.29769 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30800 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.96790 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.79385 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.27984E-003 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.32329E-004 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.96790 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
13 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 26556.58483 |
14 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.32329E-004 |
15 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 565.01840 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 59.93363 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.31736 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.32200 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 19.29863 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.84629 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.20054E-003 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.57295E-003 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 19.29863 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
27 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 522716.37820 |
28 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.57295E-003 |
29 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 13324.09308 |
30 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.86503 |
31 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.32430 |
32 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.34000 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.99411 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.86481 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.17483E-003 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.00148E-003 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.90018 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
40 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
41 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 114474.94732 |
42 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.00148E-003 |
43 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 3020.41839 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.03281 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.23123 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.23900 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.24684 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.61663 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.64768E-003 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.75060E-004 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.68245 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
55 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 20010.39903 |
56 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.75060E-004 |
57 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 527.73014 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.30500 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11794 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.26100 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.31449 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.23059E-003 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.20164E-004 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.46850 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
69 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 13735.43802 |
70 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.20164E-004 |
71 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 362.22142 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.64521 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14516 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.32904 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.38711 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.62461E-003 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.92448E-004 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.75035 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
83 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 21997.97573 |
84 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.92448E-004 |
85 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 580.10556 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.63691 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.40218E-002 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.32738 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.05225E-003 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.98799E-005 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.38927 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
97 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11416.88660 |
98 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.98799E-005 |
99 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 301.13023 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 9.76741 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.24451 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.24900 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.43208 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.65202 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.55823E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.50383E-003 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 9.76741 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 286203.60007 |
112 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.50383E-003 |
113 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 7545.67122 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 13.77135 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11176 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.75427 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.40917E-003 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.66089E-003 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 6.47935 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
124 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
125 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 189849.56718 |
126 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.66089E-003 |
127 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 5005.23300 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 16.58224 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14403 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 3.31645 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.38407 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.64537E-003 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.53423E-003 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 9.88613 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
138 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
139 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 289677.86801 |
140 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.53423E-003 |
141 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 7637.21666 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 14.84036 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10371 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.96807 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.67381E-003 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.62762E-003 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 6.34945 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
152 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
153 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 186046.86375 |
154 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.62762E-003 |
155 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 4905.01990 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.28665 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18561 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.22500 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.28950 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.49497 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.05264E-003 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.29723E-004 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.28665 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
166 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
167 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 37689.39131 |
168 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.29723E-004 |
169 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 993.52682 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.38140 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11141 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.27628 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.41972E-003 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.17549E-004 |
178 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.84894 |
179 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
180 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
181 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 24867.16385 |
182 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.17549E-004 |
183 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 655.51333 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.79384 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13314 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.35877 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.35503 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.86172E-003 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.33491E-004 |
192 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.30137 |
193 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
194 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
195 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 38120.10621 |
196 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.33491E-004 |
197 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1004.87616 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.58270 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.72422E-002 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.31654 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.91805E-003 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.17040E-004 |
206 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.84696 |
207 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
208 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
209 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 24809.03901 |
210 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.17040E-004 |
211 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 653.98018 |
212 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BOT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.56217 |
213 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_MID_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 5.38430 |
214 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_TOP_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.54836 |
215 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BASEMENT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 24.39313 |
216 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 6.00459 |
217 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.13216 |
218 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 12.00919 |
219 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 3.36839 |
220 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 10.34707 |
221 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 10.34707 |
222 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
223 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.32554 |
224 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 57.44749 |
225 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 30.76950 |
226 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 114.89499 |
227 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 49.56421 |
228 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 95.64675 |
229 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 95.64675 |
230 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
231 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.51820 |
232 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.95481 |
233 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.23519 |
234 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 11.90961 |
235 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 8.18410 |
236 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 10.79849 |
237 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 10.79849 |
238 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
239 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.75789 |
240 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.98366 |
241 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 5.98366 |
242 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.98366 |
243 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 5.98366 |
244 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.98366 |
245 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 5.98366 |
246 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
247 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
248 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 24.39313 |
249 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 24.39313 |
250 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 24.39313 |
251 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Heating Design Air Flow Rate [m3/s] | 24.39313 |
252 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Cooling Design Air Flow Rate [m3/s] | 24.39337 |
253 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Main Design Air Flow Rate [m3/s] | 24.39337 |
254 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | User Heating Air Flow Ratio [] | 1.00000 |
255 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Calculated Heating Air Flow Ratio [] | 0.99999 |
256 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.56217 |
257 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.56217 |
258 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.56217 |
259 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.56217 |
260 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.56217 |
261 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.56217 |
262 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
263 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
264 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.38430 |
265 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 5.38430 |
266 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.38430 |
267 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 5.38430 |
268 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.38430 |
269 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 5.38430 |
270 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
271 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
272 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.54836 |
273 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.54836 |
274 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.54836 |
275 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.54836 |
276 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.54836 |
277 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.54836 |
278 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
279 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
280 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 10.34707 |
281 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 95.64675 |
282 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 10.79849 |
283 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 5.98366 |
284 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Design Supply Air Flow Rate [m3/s] | 24.39337 |
285 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.56217 |
286 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 5.38430 |
287 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.54836 |
288 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 10.34707 |
289 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.34171 |
290 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
291 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.68119 |
292 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.08413E-003 |
293 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
294 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 176035.56890 |
295 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 7.48896E-003 |
296 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 10.34707 |
297 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 103606.03766 |
298 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.06391E-004 |
299 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1555.48180 |
300 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 10.34707 |
301 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 7.48896E-003 |
302 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 6.35857E-005 |
303 | Controller:WaterCoil | VAV_BOT WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 9.06391E-004 |
304 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 95.64675 |
305 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.56982 |
306 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
307 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.68115 |
308 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.07455E-003 |
309 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
310 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 1648180.25833 |
311 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 7.01174E-002 |
312 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 95.64675 |
313 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 1064885.02778 |
314 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.31608E-003 |
315 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 15542.29489 |
316 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 95.64675 |
317 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 7.01174E-002 |
318 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 6.79133E-006 |
319 | Controller:WaterCoil | VAV_MID WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 9.31608E-003 |
320 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 10.79849 |
321 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.21722 |
322 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
323 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.68115 |
324 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.07361E-003 |
325 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
326 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 181969.89268 |
327 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 7.74142E-003 |
328 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 10.79849 |
329 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 104739.20566 |
330 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.16304E-004 |
331 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1585.46466 |
332 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 10.79849 |
333 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 7.74142E-003 |
334 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 6.15120E-005 |
335 | Controller:WaterCoil | VAV_TOP WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 9.16304E-004 |
336 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.98366 |
337 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.20016 |
338 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.94555 |
339 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
340 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.21888 |
341 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.25297E-003 |
342 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
343 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Coil Load [W] | 98522.43271 |
344 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.19137E-003 |
345 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 5.98366 |
346 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Rated Capacity [W] | 288343.85804 |
347 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.52256E-003 |
348 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 6142.16875 |
349 | Fan:ConstantVolume | CAV_BAS FAN | Design Size Maximum Flow Rate [m3/s] | 5.98366 |
350 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.19137E-003 |
351 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.13612E-004 |
352 | Controller:WaterCoil | CAV_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.52256E-003 |
353 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 24.39337 |
354 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.33839 |
355 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 24.39337 |
356 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 463695.07683 |
357 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 260952.55372 |
358 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.13559E-002 |
359 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 24.39337 |
360 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 24.39337 |
361 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 24.39337 |
362 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 24.39337 |
363 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 463695.07683 |
364 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 463695.07683 |
365 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 24207.99248 |
366 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
367 | Fan:OnOff | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 24.39337 |
368 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 24.39337 |
369 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Heating Capacity [W] | 463695.07683 |
370 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.13559E-002 |
371 | Coil:Heating:Electric | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 24207.99248 |
372 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Nominal Capacity Volume [m3/s] | 1.89945E-004 |
373 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Nominal Capacity Volume [m3/s] | 3.72000E-005 |
374 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Rated Power [W] | 96450.69782 |
375 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Rated Power [W] | 100000.00000 |
376 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.56217 |
377 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
378 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.56217 |
379 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 10385.99877 |
380 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 5906.25331 |
381 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.54352E-004 |
382 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.56217 |
383 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.56217 |
384 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.56217 |
385 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.56217 |
386 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 10385.99877 |
387 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 10385.99877 |
388 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 1118.30896 |
389 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
390 | Fan:OnOff | AIRLOOP DATACENTER BOT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.56217 |
391 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.56217 |
392 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Heating Capacity [W] | 10385.99877 |
393 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.54352E-004 |
394 | Coil:Heating:Electric | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 1118.30896 |
395 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.38430 |
396 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.15632 |
397 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 5.38430 |
398 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 99506.15099 |
399 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 56574.75557 |
400 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.43690E-003 |
401 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 5.38430 |
402 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 5.38430 |
403 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 5.38430 |
404 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 5.38430 |
405 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Heating Capacity [W] | 99506.15099 |
406 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 99506.15099 |
407 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 11183.08965 |
408 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
409 | Fan:OnOff | AIRLOOP DATACENTER MID SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 5.38430 |
410 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 5.38430 |
411 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Heating Capacity [W] | 99506.15099 |
412 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.43690E-003 |
413 | Coil:Heating:Electric | AIRLOOP DATACENTER MID_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 11183.08965 |
414 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.54836 |
415 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
416 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.54836 |
417 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 10132.76636 |
418 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 5761.52753 |
419 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.48151E-004 |
420 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.54836 |
421 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.54836 |
422 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.54836 |
423 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.54836 |
424 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Heating Capacity [W] | 10132.76636 |
425 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 10132.76636 |
426 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 1118.30896 |
427 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
428 | Fan:OnOff | AIRLOOP DATACENTER TOP SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.54836 |
429 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.54836 |
430 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Heating Capacity [W] | 10132.76636 |
431 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.48151E-004 |
432 | Coil:Heating:Electric | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 1118.30896 |
433 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 8.95391E-002 |
434 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 18450.70023 |
435 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 8.95391E-002 |
436 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 10.74470 |
437 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 8.95391E-002 |
438 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 8.95391E-002 |
439 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 375840.74154 |
440 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 5.60000 |
441 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 2.94800E-002 |
442 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 3.53760 |
443 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 2.94800E-002 |
444 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 8878.08470 |
445 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
446 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 3369746.33825 |
447 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 3369746.34000 |
448 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 2.94800E-002 |
449 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 8.95391E-002 |
450 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 10.74470 |
451 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 8.95391E-002 |
452 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 12774.04216 |
453 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 8.95391E-002 |
454 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 4.51006E-002 |
455 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1062739.33901 |
456 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1067780.64000 |
457 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Water Flow Rate [m3/s] | 5.28405E-002 |
458 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 8.95391E-002 |
459 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 4.51006E-002 |
460 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 1062739.33901 |
461 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 1067780.64000 |
462 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Water Flow Rate [m3/s] | 5.28405E-002 |
463 | PlantLoop | SINGLE WATER PLANT LOOP | Maximum Loop Flow Rate [m3/s] | 1.42953E-002 |
464 | PlantLoop | SINGLE WATER PLANT LOOP | Plant Loop Volume [m3] | 1.71543 |
465 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Flow Rate [m3/s] | 1.42953E-002 |
466 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Power Consumption [W] | 3646.00746 |
467 | FluidCooler:TwoSpeed | CENTRAL TOWER | Design Water Flow Rate [m3/s] | 1.42953E-002 |
468 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at High Fan Speed [m3/s] | 139666.46671 |
469 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | 55853.19967 |
470 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at Low Fan Speed [m3/s] | 69833.23335 |
471 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fan Power at Low Fan Speed [W] | 7879.72339 |
472 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at Low Fan Speed [W/C] | 21056.17605 |
473 | Boiler:HotWater | CENTRAL BOILER | Design Size Nominal Capacity [W] | 588842.36639 |
474 | Boiler:HotWater | CENTRAL BOILER | User-Specified Nominal Capacity [W] | 576151.43000 |
475 | Boiler:HotWater | CENTRAL BOILER | Design Size Design Water Flow Rate [m3/s] | 1.42953E-002 |
476 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
477 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
478 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
479 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 5.95776 |
480 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
481 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 0.10568 |
482 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 12.68172 |
483 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 0.10568 |
484 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 31828.82104 |
485 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 46.69933 |
486 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 1268490.46541 |
487 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 9.33987 |
488 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 158561.30818 |
489 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 46.69933 |
490 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 1268490.46541 |
491 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 9.33987 |
492 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 158561.30818 |
493 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 5.48850E-002 |
494 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 5.48850E-002 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 25177.03 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 495197.91 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 108495.51 |
4 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 18963.54 |
5 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 13016.72 |
6 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 20846.85 |
7 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 10819.84 |
8 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 271215.01 |
9 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 179906.44 |
10 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 274506.98 |
11 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 176303.19 |
12 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 35714.62 |
13 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 23564.17 |
14 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 36122.74 |
15 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 23509.09 |
16 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | 67617.69 |
17 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | 671567.32 |
18 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | 69029.89 |
19 | Coil:Heating:Water | CAV_BAS HEATING COIL | 216931.80 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | 292769.23 | 179584.97 | 113184.26 | 0.61 | 57583.83 | 584.05 |
2 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | 2715285.91 | 1663600.25 | 1051685.66 | 0.61 | 527926.86 | 5354.53 |
3 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | 304704.73 | 187088.42 | 117616.31 | 0.61 | 60394.03 | 612.55 |
4 | Coil:Cooling:Water | CAV_BAS COOLING COIL | 163434.66 | 101471.40 | 61963.26 | 0.62 | 29551.75 | 299.73 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | 6.84 | 23.33 |
2 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | 6.84 | 23.33 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.419 | 0.394 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.147 | 0.979 | 105.88 | 200.61 | 105.88 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_NORTH_0.4 | N/A | 2.058 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_NORTH_0.4 | N/A | 2.058 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_NORTH_0.4 | N/A | 2.058 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_NORTH_0.4 | N/A | 2.058 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_NORTH_0.4 | N/A | 2.058 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.147 | 0.979 | 71.89 | 133.74 | 71.89 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_EAST_0.4 | N/A | 2.058 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_EAST_0.4 | N/A | 2.058 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_EAST_0.4 | N/A | 2.058 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.147 | 0.979 | 105.88 | 200.61 | 105.88 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_SOUTH_0.4 | N/A | 2.058 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_SOUTH_0.4 | N/A | 2.058 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_SOUTH_0.4 | N/A | 2.058 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_SOUTH_0.4 | N/A | 2.058 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_SOUTH_0.4 | N/A | 2.058 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.147 | 0.979 | 71.89 | 133.74 | 71.89 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_WEST_0.4 | N/A | 2.058 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_WEST_0.4 | N/A | 2.058 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_WEST_0.4 | N/A | 2.058 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.072 | 0.924 | 113.68 | 200.61 | 113.68 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_NORTH_0.4 | N/A | 2.058 | No | 86.92 | 86.92 | 86.92 | 0.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.072 | 0.924 | 75.79 | 133.74 | 75.79 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_EAST_0.4 | N/A | 2.058 | No | 57.95 | 57.95 | 57.95 | 90.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.072 | 0.924 | 113.68 | 200.61 | 113.68 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_SOUTH_0.4 | N/A | 2.058 | No | 86.92 | 86.92 | 86.92 | 180.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.072 | 0.924 | 75.79 | 133.74 | 75.79 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_WEST_0.4 | N/A | 2.058 | No | 57.95 | 57.95 | 57.95 | 270.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.485 | 1.215 | 113.68 | 200.61 | 113.68 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_NORTH_0.4 | N/A | 2.058 | No | 86.92 | 86.92 | 86.92 | 0.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.485 | 1.215 | 75.79 | 133.74 | 75.79 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_EAST_0.4 | N/A | 2.058 | No | 57.95 | 57.95 | 57.95 | 90.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.485 | 1.215 | 113.68 | 200.61 | 113.68 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_SOUTH_0.4 | N/A | 2.058 | No | 86.92 | 86.92 | 86.92 | 180.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.485 | 1.215 | 75.79 | 133.74 | 75.79 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3622_SHGC_WEST_0.4 | N/A | 2.058 | No | 57.95 | 57.95 | 57.95 | 270.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.147 | 0.979 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.147 | 0.979 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.147 | 0.979 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.147 | 0.979 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.072 | 0.924 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.072 | 0.924 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.072 | 0.924 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.072 | 0.924 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.485 | 1.215 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.485 | 1.215 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.485 | 1.215 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.485 | 1.215 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.419 | 0.394 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 0.2323501594 | 0.1864510138 | Pass | Pass | 3.6217065662 | 12.1691048627 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 4.4366687418E-002 | 0.1257878105 | Pass | Pass | 4.9741394267E-002 | 0.2168434658 | Pass | Pass |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 6.1102902986E-003 | 4.4675264252E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 3.2941136702E-002 | 2.4169220570E-002 | Pass | Pass | 0.5063551498 | 0.4880665300 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 3.8473803346E-002 | 7.1551460581E-002 | Pass | Pass | 4.9391244265E-002 | 0.2158417788 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 8.0860487427E-002 | 0.1378427247 | Pass | Pass | 4.9541586831E-002 | 0.2167984417 | Pass | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1338005575 | 0.1743047671 | Pass | Pass | 5.1319240551E-002 | 0.2201902864 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 7.3366919302E-002 | 0.1632306656 | Pass | Pass | 4.8477501317E-002 | 0.2112916444 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 2.4579361007E-002 | 2.4514174589E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 4.7803794426E-002 | 7.0394780610E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1258598923 | 0.1204635890 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 4.9625357954E-002 | 5.1859054925E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.3520759942 | 0.3624864675 | Pass | Pass | 10.5483044006 | 27.1596109308 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2438493126 | 0.3379625819 | Pass | Pass | 10.6226075577 | 37.8440055611 | Pass | Pass |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2176936095 | 0.2252274649 | Pass | Pass | 0.8608073957 | 1.4708307481 | Pass | Pass |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.2062084214 | 0.2691349769 | Pass | Pass | 5.6577634101 | 20.3268917777 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 1.3480463098E-002 | 2.3327643452E-002 | Pass | Pass | 0.5927776569 | 3.3996042908 | Pass | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 1.0695273159E-002 | 1.2124948602E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.1069425759 | 8.0110566903E-002 | Pass | Pass | 0.5193593403 | 0.4794744129 | Pass | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 4.1490769063E-006 | 5.4181779687E-006 | Pass | Pass | 4.0722348811E-003 | 3.5114154512E-003 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 8.2192990403E-003 | 9.2227496590E-003 | Pass | Pass | 2.2941758645E-002 | 4.6213804872E-002 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 2.5538242264E-002 | 2.0148134258E-002 | Pass | Pass | 5.2402421466E-003 | 5.5795061799E-003 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 9.4295215342E-005 | 7.8825295710E-005 | Pass | Pass | 4.6954805094E-005 | 1.0470435471E-004 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:16
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 7019.65 | 306.83 | 0.00 | 19739.56 | 19361.13 | 46427.16 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:16
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | -27.60 | 0.00 | -27.60 | Wetbulb [C] | 2.70 | 230.00 |
GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 33.40 | 16.00 | 16.30 | Wetbulb [C] | 4.90 | 240.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 11.00 | 18 | |||
May | 24.00 | 14 | |||
Jun | 29.00 | 21 | |||
Jul | 6.00 | 9 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:16
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.399 | 0.419 | 118.87 | 118.87 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.399 | 0.419 | 139.09 | 139.09 | 180.00 | 90.00 | S |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.399 | 0.419 | 139.09 | 139.09 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.979 | 1.147 | 200.61 | 105.88 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.979 | 1.147 | 133.74 | 71.89 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.979 | 1.147 | 200.61 | 105.88 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.979 | 1.147 | 133.74 | 71.89 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.924 | 1.072 | 2006.06 | 1136.85 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.924 | 1.072 | 1337.37 | 757.90 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.924 | 1.072 | 2006.06 | 1136.85 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.924 | 1.072 | 1337.37 | 757.90 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.215 | 1.485 | 200.61 | 113.68 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.215 | 1.485 | 133.74 | 75.79 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.215 | 1.485 | 200.61 | 113.68 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.215 | 1.485 | 133.74 | 75.79 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.979 | 1.147 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.979 | 1.147 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.979 | 1.147 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.979 | 1.147 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.924 | 1.072 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.924 | 1.072 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.924 | 1.072 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.924 | 1.072 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.215 | 1.485 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.215 | 1.485 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.215 | 1.485 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.215 | 1.485 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.182 | 0.186 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.399 | 0.419 | 39.22 | 39.22 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.399 | 0.419 | 39.22 | 39.22 | 180.00 | 90.00 | S |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.399 | 0.419 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 270.00 | 90.00 | W |
BASEMENT_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 2779.43 | 2779.43 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 2076.77 | 2076.77 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 419.30 | 419.30 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 2076.82 | 2076.82 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 0.00 | 180.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.35 | 250.35 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 225.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 135.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.41 | 313.41 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
INT-PER3S-NE-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
INT-PER3S-NE | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.42 | 313.42 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
GROUNDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
iz-DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 0.00 | 180.00 | |
MIDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 35631.06 | 35631.06 | 180.00 | 0.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_BOT_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_BOT_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_MID_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
DATACENTER_MID_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
DATACENTER_MID_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 362.03 | 362.03 | 0.00 | 180.00 | |
DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 180.00 | 0.00 | |
DATACENTER_TOP_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_TOP_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_TOP_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 783.68 | 783.68 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 419.35 | 419.35 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 135.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.08 | 63.08 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 180.00 | 0.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 7126.21 | 0.00 | 90.00 | N | ||
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 50646.53 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.26 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.50 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.35 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.48 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.3622_SHGC_NORTH_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.058 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.3622_SHGC_NORTH_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.058 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.3622_SHGC_NORTH_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.058 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.3622_SHGC_NORTH_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.058 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.3622_SHGC_NORTH_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.058 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.3622_SHGC_EAST_0.4 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.058 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.3622_SHGC_EAST_0.4 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.058 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.3622_SHGC_EAST_0.4 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.058 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.3622_SHGC_SOUTH_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.058 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.3622_SHGC_SOUTH_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.058 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.3622_SHGC_SOUTH_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.058 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.3622_SHGC_SOUTH_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.058 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.3622_SHGC_SOUTH_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.058 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.3622_SHGC_WEST_0.4 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.058 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.3622_SHGC_WEST_0.4 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.058 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.3622_SHGC_WEST_0.4 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.058 | 0.401 | 0.402 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.3622_SHGC_NORTH_0.4 | 86.92 | 0.00 | 0.00 | 86.92 | 869.21 | 2.058 | 0.401 | 0.402 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.3622_SHGC_EAST_0.4 | 57.95 | 0.00 | 0.00 | 57.95 | 579.48 | 2.058 | 0.401 | 0.402 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.3622_SHGC_SOUTH_0.4 | 86.92 | 0.00 | 0.00 | 86.92 | 869.21 | 2.058 | 0.401 | 0.402 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.3622_SHGC_WEST_0.4 | 57.95 | 0.00 | 0.00 | 57.95 | 579.48 | 2.058 | 0.401 | 0.402 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.3622_SHGC_NORTH_0.4 | 86.92 | 0.00 | 0.00 | 86.92 | 86.92 | 2.058 | 0.401 | 0.402 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.3622_SHGC_EAST_0.4 | 57.95 | 0.00 | 0.00 | 57.95 | 57.95 | 2.058 | 0.401 | 0.402 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.3622_SHGC_SOUTH_0.4 | 86.92 | 0.00 | 0.00 | 86.92 | 86.92 | 2.058 | 0.401 | 0.402 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.3622_SHGC_WEST_0.4 | 57.95 | 0.00 | 0.00 | 57.95 | 57.95 | 2.058 | 0.401 | 0.402 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 3476.85 | 2.058 | 0.401 | 0.402 | |||||||||||||||||
North Total or Average | 1043.06 | 2.058 | 0.401 | 0.402 | |||||||||||||||||
Non-North Total or Average | 2433.80 | 2.058 | 0.401 | 0.402 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:16
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:16
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 7.6202 | 2779.43 | 21179.74 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 44.71 | 0.0000 | Y | 177.74 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 7.6202 | 2496.12 | 19020.89 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 44.71 | 0.0000 | Y | 159.62 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 7.6202 | 24961.20 | 190208.95 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 44.71 | 0.0000 | Y | 1596.24 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 7.6202 | 2496.12 | 19020.89 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 44.71 | 0.0000 | Y | 159.62 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 7.6202 | 313.41 | 2388.26 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 31.05 | 0.0000 | Y | 13.92 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 7.6202 | 201.98 | 1539.09 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 30.88 | 0.0000 | Y | 8.92 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 7.6202 | 313.42 | 2388.32 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 30.75 | 0.0000 | Y | 13.78 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 7.6202 | 201.98 | 1539.09 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 30.93 | 0.0000 | Y | 8.94 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 7.6202 | 3134.13 | 23882.63 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 31.08 | 0.0000 | Y | 139.36 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 7.6202 | 2019.75 | 15390.88 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 30.89 | 0.0000 | Y | 89.25 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 7.6202 | 3134.20 | 23883.15 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 30.76 | 0.0000 | Y | 137.92 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 7.6202 | 2019.75 | 15390.88 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 30.94 | 0.0000 | Y | 89.40 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 7.6202 | 313.41 | 2388.26 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 31.08 | 0.0000 | Y | 13.94 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 7.6202 | 201.98 | 1539.09 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 30.89 | 0.0000 | Y | 8.93 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 7.6202 | 313.42 | 2388.32 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 30.76 | 0.0000 | Y | 13.79 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 7.6202 | 201.98 | 1539.09 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 30.94 | 0.0000 | Y | 8.94 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GENERAL | 7.6202 | 783.68 | 5971.78 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 44.71 | 0.0000 | Y | 50.12 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | DATACENTER_BOT_ZN_6 | GENERAL | 12.5114 | 36.20 | 452.95 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 4.64 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | DATACENTER_MID_ZN_6 | GENERAL | 12.5114 | 362.03 | 4529.48 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 46.40 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | DATACENTER_TOP_ZN_6 | GENERAL | 12.5114 | 36.20 | 452.95 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 4.64 |
Interior Lighting Total | 7.6661 | 46320.38 | 355094.67 | 857.40 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2388.32 | 921.17 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 2388.32 | 0.00 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1539.09 | 593.63 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1539.09 | 0.00 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2388.26 | 921.15 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 2388.26 | 0.00 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1539.09 | 593.63 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1539.09 | 0.00 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2388.32 | 921.17 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 2388.32 | 0.00 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1539.09 | 593.63 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1539.09 | 0.00 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2388.26 | 921.15 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 2388.26 | 0.00 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1539.09 | 593.63 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1539.09 | 0.00 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2388.32 | 921.17 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 2388.32 | 0.00 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1539.09 | 593.63 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1539.09 | 0.00 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2388.26 | 921.15 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 2388.26 | 0.00 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1539.09 | 593.63 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1539.09 | 0.00 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 9973.05 | AstronomicalClock | - | 42.11 | 42.11 | 78.82 | |
EXTERIOR_LIGHTS_B | 27638.03 | AstronomicalClock | - | 83.57 | 71.13 | 369.02 | |
Exterior Lighting Total | 37611.08 | 447.85 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:16
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 2099867.95 | |||||
HEATSYS1 BOILER | Boiler:HotWater | 3369746.34 | 0.81 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:ReformulatedEIR | 1067780.64 | 6.28 | 1022005.89 | 5.98 | 6.84 | 23.33 |
COOLSYS1 CHILLER2 | Chiller:Electric:ReformulatedEIR | 1067780.64 | 6.28 | 1022005.89 | 5.98 | 6.84 | 23.33 |
CENTRAL TOWER | FluidCooler:TwoSpeed | 582060.00 | |||||
CENTRAL BOILER | Boiler:HotWater | 576151.43 | 0.80 | ||||
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 1268490.47 | |||||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 1268490.47 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | 176035.57 | 292769.23 | 179584.97 | 113184.26 | 0.61 | - | 57583.83 | 584.05 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | 1648180.26 | 2715285.91 | 1663600.25 | 1051685.66 | 0.61 | - | 527926.86 | 5354.53 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | 181969.89 | 304704.73 | 187088.42 | 117616.31 | 0.61 | - | 60394.03 | 612.55 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | 98522.43 | 163434.66 | 101471.40 | 61963.26 | 0.62 | - | 29551.75 | 299.73 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 463695.08 | 260952.55 | 202742.52 | 0.56 | 0.00 | |||
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 10386.00 | 5906.25 | 4479.75 | 0.57 | 0.00 | |||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 99506.15 | 56574.76 | 42931.40 | 0.57 | 0.00 | |||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 10132.77 | 5761.53 | 4371.24 | 0.57 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 26556.58 | 25177.03 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 522716.38 | 495197.91 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 114474.95 | 108495.51 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 20010.40 | 18963.54 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 13735.44 | 13016.72 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 21997.98 | 20846.85 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 11416.89 | 10819.84 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 286203.60 | 271215.01 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 189849.57 | 179906.44 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 289677.87 | 274506.98 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 186046.86 | 176303.19 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 37689.39 | 35714.62 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 24867.16 | 23564.17 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 38120.11 | 36122.74 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 24809.04 | 23509.09 | - |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | 103606.04 | 67617.69 | - |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | 1064885.03 | 671567.32 | - |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | 104739.21 | 69029.89 | - |
CAV_BAS HEATING COIL | Coil:Heating:Water | 288343.86 | 216931.80 | - |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 463695.08 | 0.00 | |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 10386.00 | 0.00 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 99506.15 | 0.00 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 10132.77 | 0.00 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | 24207.99 | 1.00 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | 1118.31 | 1.00 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | 11183.09 | 1.00 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | 1118.31 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 10.35 | 23504.32 | 2271.59 | 1.00 | 1.12 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 95.65 | 217270.51 | 2271.59 | 1.00 | 1.08 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 10.80 | 24529.79 | 2271.59 | 1.00 | 1.12 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 |
CAV_BAS FAN | Fan:ConstantVolume | 0.60 | 1018.41 | 5.98 | 10146.22 | 1695.65 | 1.00 | 1.15 | General | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 0.62 | 1018.41 | 24.39 | 40230.69 | 1649.25 | 1.00 | 1.14 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 |
AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.56 | 629.70 | 1120.11 | 1.00 | 1.56 | General | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 5.38 | 6031.00 | 1120.11 | 1.00 | 1.15 | General | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.55 | 614.22 | 1120.11 | 1.00 | 1.57 | General | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 133527.72 | 0.089539 | 18450.70 | 206062.94 | 0.90 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.029480 | 8878.08 | 301156.09 | 0.90 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 92445.74 | 0.089539 | 12774.04 | 142664.32 | 0.90 | General |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.014295 | 3646.01 | 255050.01 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 3168.45 | 0.000440 | 5.96 | 13540.37 | 0.30 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 180718.98 | 0.105681 | 31828.82 | 301178.23 | 0.90 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.50 | 0.08 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:16
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 72467.57 | 72467.57 | 26.07 | 5.984 | 5.984 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00748 | 21.56 | 0.00629 | 1.200 | 0.00 |
CORE_BOTTOM | 77382.86 | 77382.86 | 31.00 | 6.389 | 6.389 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00740 | 21.56 | 0.00629 | 1.078 | 0.00 |
CORE_MID | 726059.14 | 726059.14 | 290.88 | 59.934 | 59.934 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00743 | 21.56 | 0.00629 | 10.778 | 0.00 |
CORE_TOP | 70405.35 | 70405.35 | 28.21 | 5.865 | 5.865 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 24.00 | 24.00 | 0.00743 | 33.08 | 0.00631 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 12398.39 | 12398.39 | 39.56 | 1.033 | 1.033 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 24.00 | 0.00728 | 33.40 | 0.00631 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 15666.05 | 15666.05 | 77.56 | 1.305 | 1.305 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:50:00 | 24.00 | 24.00 | 0.00714 | 24.09 | 0.00629 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 19750.09 | 19750.09 | 63.01 | 1.645 | 1.645 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 24.00 | 24.00 | 0.00718 | 33.13 | 0.00631 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 19650.59 | 19650.59 | 97.29 | 1.637 | 1.637 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 24.00 | 24.00 | 0.00712 | 30.36 | 0.00630 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 116727.74 | 116727.74 | 372.44 | 9.724 | 9.724 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 24.00 | 0.00726 | 33.40 | 0.00631 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 165322.36 | 165322.36 | 818.53 | 13.771 | 13.771 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 24.00 | 24.00 | 0.00712 | 25.96 | 0.00630 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 199065.55 | 199065.55 | 635.14 | 16.582 | 16.582 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 24.00 | 24.00 | 0.00716 | 33.27 | 0.00631 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 178155.45 | 178155.45 | 882.07 | 14.840 | 14.840 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 24.00 | 24.00 | 0.00711 | 30.36 | 0.00630 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 13373.89 | 13373.89 | 42.67 | 1.114 | 1.114 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 24.00 | 24.00 | 0.00722 | 33.08 | 0.00631 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 16583.45 | 16583.45 | 82.11 | 1.381 | 1.381 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 24.00 | 24.00 | 0.00712 | 26.41 | 0.00630 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 21534.72 | 21534.72 | 68.71 | 1.794 | 1.794 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 24.00 | 24.00 | 0.00714 | 33.40 | 0.00631 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 19000.05 | 19000.05 | 94.07 | 1.583 | 1.583 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 24.00 | 24.00 | 0.00710 | 30.36 | 0.00630 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 8556.19 | 8556.19 | 236.34 | 0.562 | 0.562 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | 27.00 | 27.00 | 0.00708 | 26.28 | 0.00630 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 81947.68 | 81947.68 | 2263.58 | 5.384 | 5.384 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | 27.00 | 27.00 | 0.00709 | 26.28 | 0.00630 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 8345.90 | 8345.90 | 230.53 | 0.548 | 0.548 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | 27.00 | 27.00 | 0.00709 | 26.57 | 0.00630 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 371264.36 | 371264.36 | 473.75 | 24.393 | 24.393 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 27.00 | 27.00 | 0.00704 | 18.84 | 0.00628 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 22.70 | 0.00034 | -27.60 | 0.00034 | 1.200 | 0.00 |
CORE_BOTTOM | 9227.35 | 9227.35 | 3.70 | 0.446 | 1.078 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -27.60 | 0.00034 | 1.078 | 0.00 |
CORE_MID | 352773.19 | 352773.19 | 141.33 | 17.082 | 17.082 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -27.60 | 0.00034 | 10.778 | 0.00 |
CORE_TOP | 80130.06 | 80130.06 | 32.10 | 3.900 | 3.900 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -27.60 | 0.00034 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 14004.02 | 14004.02 | 44.68 | 0.682 | 0.682 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00777 | -27.60 | 0.00034 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 9611.96 | 9611.96 | 47.59 | 0.468 | 0.468 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00778 | -27.60 | 0.00034 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 15393.55 | 15393.55 | 49.11 | 0.750 | 0.750 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00780 | -27.60 | 0.00034 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 7991.39 | 7991.39 | 39.57 | 0.389 | 0.389 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00770 | -27.60 | 0.00034 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 200265.88 | 200265.88 | 638.98 | 9.767 | 9.767 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00766 | -27.60 | 0.00034 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 132841.97 | 132841.97 | 657.71 | 6.479 | 6.479 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00766 | -27.60 | 0.00034 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 202694.95 | 202694.95 | 646.72 | 9.886 | 9.886 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00766 | -27.60 | 0.00034 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 130183.00 | 130183.00 | 644.55 | 6.349 | 6.349 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00765 | -27.60 | 0.00034 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 26368.99 | 26368.99 | 84.13 | 1.287 | 1.287 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00768 | -27.60 | 0.00034 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 17397.95 | 17397.95 | 86.14 | 0.849 | 0.849 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00767 | -27.60 | 0.00034 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 26670.14 | 26670.14 | 85.09 | 1.301 | 1.301 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00768 | -27.60 | 0.00034 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 17357.28 | 17357.28 | 85.94 | 0.847 | 0.847 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00767 | -27.60 | 0.00034 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | 18.00 | 24.21 | 0.00098 | -27.60 | 0.00034 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | 18.00 | 22.23 | 0.00098 | -27.60 | 0.00034 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | 18.00 | 19.68 | 0.00098 | -27.60 | 0.00034 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:50:00 | 18.00 | 27.00 | 0.00700 | -27.60 | 0.00034 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV_BOT WITH REHEAT | 10.35 | 10.35 | 3.37 | 3.37 | 10.3471 | 3.3684 | 10.3471 | 0.3255 | 0.3000 |
VAV_MID WITH REHEAT | 95.65 | 95.65 | 49.56 | 49.56 | 95.6468 | 49.5642 | 95.6468 | 0.5182 | 0.3000 |
VAV_TOP WITH REHEAT | 10.80 | 10.80 | 8.18 | 8.18 | 10.7985 | 8.1841 | 10.7985 | 0.7579 | 0.3000 |
CAV_BAS | 5.98 | 5.98 | 1.20 | 1.20 | 5.9837 | 5.9837 | 5.9837 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 24.39 | 24.39 | 0.34 | 0.34 | 24.3934 | 24.3931 | 24.3934 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.56 | 0.56 | 0.02 | 0.02 | 0.5622 | 0.5622 | 0.5622 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 5.38 | 5.38 | 0.16 | 0.16 | 5.3843 | 5.3843 | 5.3843 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.55 | 0.55 | 0.02 | 0.02 | 0.5484 | 0.5484 | 0.5484 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 26556.585 | 26556.585 | 1.967896 | 0.00023233 | 565.018 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 26556.58 | 26556.58 | 1.967896 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00799999 | 45.2309 | 9227.35 | 0.00 | 26650.12 | 26650.12 |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 522716.378 | 522716.378 | 19.298630 | 0.00457295 | 13324.093 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 522716.38 | 522716.38 | 19.298630 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00800000 | 45.2310 | 352773.19 | 0.00 | 524329.70 | 524329.70 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 114474.947 | 114474.947 | 3.900181 | 0.00100148 | 3020.418 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 114474.95 | 114474.95 | 3.900181 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00800000 | 45.2310 | 80130.06 | 0.00 | 114860.69 | 114860.69 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 20010.399 | 20010.399 | 0.682446 | 0.00017506 | 527.730 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 20010.40 | 20010.40 | 0.682446 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00777257 | 43.9637 | 14004.02 | 0.00 | 20076.07 | 20076.07 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 13735.438 | 13735.438 | 0.468499 | 0.00012016 | 362.221 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 13735.44 | 13735.44 | 0.468499 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00778445 | 44.0300 | 9611.96 | 0.00 | 13780.37 | 13780.37 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 21997.976 | 21997.976 | 0.750352 | 0.00019245 | 580.106 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21997.98 | 21997.98 | 0.750352 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00780023 | 44.1180 | 15393.55 | 0.00 | 22069.87 | 22069.87 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 11416.887 | 11416.887 | 0.389269 | 0.00009988 | 301.130 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 11416.89 | 11416.89 | 0.389269 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00770102 | 43.5646 | 7991.39 | 0.00 | 11454.61 | 11454.61 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 286203.600 | 286203.600 | 9.767409 | 0.00250383 | 7545.671 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 286203.60 | 285306.53 | 9.767409 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00765732 | 43.3222 | 200265.88 | 0.00 | 287126.21 | 287126.21 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 189849.567 | 189849.567 | 6.479353 | 0.00166089 | 5005.233 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 189849.57 | 189849.57 | 6.479353 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00765595 | 43.3146 | 132841.97 | 0.00 | 190460.89 | 190460.89 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 289677.868 | 289677.868 | 9.886126 | 0.00253423 | 7637.217 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 289677.87 | 289677.87 | 9.886126 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00766138 | 43.3448 | 202694.95 | 0.00 | 290611.30 | 290611.30 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 186046.864 | 186046.864 | 6.349451 | 0.00162762 | 4905.020 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 186046.86 | 186046.86 | 6.349451 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00764910 | 43.2764 | 130183.00 | 0.00 | 186646.25 | 186646.25 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 37689.391 | 37689.391 | 1.286648 | 0.00032972 | 993.527 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 37689.39 | 37583.07 | 1.286648 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00767644 | 43.4299 | 26368.99 | 0.00 | 37809.86 | 37809.86 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 24867.164 | 24867.164 | 0.848943 | 0.00021755 | 655.513 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 24867.16 | 24867.16 | 0.848943 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00767313 | 43.4115 | 17397.95 | 0.00 | 24946.59 | 24946.59 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 38120.106 | 38120.106 | 1.301366 | 0.00033349 | 1004.876 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 38120.11 | 38120.11 | 1.301366 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00767993 | 43.4494 | 26670.14 | 0.00 | 38241.92 | 38241.92 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 24809.039 | 24809.039 | 0.846961 | 0.00021704 | 653.980 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 24809.04 | 24809.04 | 0.846961 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00767261 | 43.4087 | 17357.28 | 0.00 | 24888.27 | 24888.27 |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 176035.569 | -999.000 | 10.347066 | 0.00748896 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 176035.57 | 174160.21 | 10.347066 | 26.34 | 14.64 | 0.00708413 | 10.68 | 8.51 | 0.00700000 | 33.40 | 0.00630683 | 16.37 | 24.5305 | 24.00 | 0.00734215 | 34.6326 | 122261.29 | 0.00 | 198291.93 | 195430.57 |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 103606.038 | 103606.038 | 3.104120 | 0.00090639 | 1555.482 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 103606.04 | 103606.04 | 3.104120 | -18.74 | -18.74 | 0.00170554 | 12.80 | 10.41 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 81.7684 | 19.41 | 0.00772660 | 48.2177 | 33826.76 | 0.00 | 81761.81 | 81761.81 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 1648180.258 | -999.000 | 95.646752 | 0.07011740 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 1648180.26 | 1632778.46 | 95.646752 | 26.57 | 14.71 | 0.00707455 | 10.68 | 8.51 | 0.00700000 | 33.40 | 0.00630683 | 16.37 | 26.5372 | 24.00 | 0.00736353 | 34.7321 | 1114157.20 | 0.00 | 1854349.07 | 1830011.82 |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 1064885.028 | 1064885.028 | 28.694026 | 0.00931608 | 15542.295 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 1064885.03 | 1064885.03 | 28.694026 | -22.27 | -22.27 | 0.00117628 | 12.80 | 10.41 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 88.4573 | 17.82 | 0.00755555 | 52.0890 | 368953.52 | 0.00 | 811795.04 | 811795.04 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 181969.893 | -999.000 | 10.798494 | 0.00774142 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 181969.89 | 180260.93 | 10.798494 | 26.22 | 14.59 | 0.00707361 | 10.68 | 8.51 | 0.00700000 | 33.40 | 0.00630683 | 16.37 | 23.5050 | 24.00 | 0.00731043 | 34.4845 | 129126.13 | 0.00 | 205157.41 | 202498.70 |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 104739.206 | 104739.206 | 3.239548 | 0.00091630 | 1585.465 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 02:30:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 104739.21 | 104739.21 | 3.239548 | -17.75 | -17.75 | 0.00188992 | 12.80 | 10.41 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 78.3501 | 15.76 | 0.00758378 | 59.5988 | 38318.26 | 0.00 | 83476.95 | 83476.95 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 98522.433 | -999.000 | 5.983658 | 0.00419137 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 98522.43 | 95371.75 | 5.983658 | 25.95 | 14.64 | 0.00725297 | 11.22 | 8.74 | 0.00700000 | 32.60 | 0.00630558 | 16.10 | 20.0572 | 24.00 | 0.00753016 | 35.5092 | 63647.68 | 0.00 | 111060.65 | 108708.53 |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | CAV_BAS | 288343.858 | 288343.858 | 5.983658 | 0.00252256 | 6142.169 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 288343.86 | 288343.86 | 5.983658 | -5.54 | -9.81 | 0.00034190 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 20.0572 | 22.82 | 0.00034190 | 1.7515 | 0.00 | 0.00 | 228809.94 | 228809.94 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 463695.077 | 260952.554 | 24.393372 | 0.01135586 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 | 402924.02 | 401452.92 | -999.0 | 28.68 | 15.39 | 0.00703200 | 12.80 | 9.41 | 0.00700000 | 33.40 | 0.00630683 | 16.37 | -999.0000 | 27.00 | 0.00704221 | 27.8124 | 370798.99 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 10385.999 | 5906.253 | 0.562174 | 0.00025435 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | 8977.03 | 8911.64 | -999.0 | 28.07 | 15.21 | 0.00706232 | 12.80 | 9.41 | 0.00700000 | 26.57 | 0.00629632 | 14.04 | -999.0000 | 27.00 | 0.00708424 | 27.9745 | 8556.19 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 99506.151 | 56574.756 | 5.384300 | 0.00243690 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | 86012.11 | 85359.20 | -999.0 | 28.07 | 15.21 | 0.00706495 | 12.80 | 9.41 | 0.00700000 | 26.57 | 0.00629632 | 14.04 | -999.0000 | 27.00 | 0.00708795 | 27.9891 | 81947.68 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 10132.766 | 5761.528 | 0.548359 | 0.00024815 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | 8758.46 | 8693.07 | -999.0 | 28.07 | 15.21 | 0.00706387 | 12.80 | 9.41 | 0.00700000 | 26.57 | 0.00629632 | 14.04 | -999.0000 | 27.00 | 0.00708640 | 27.9830 | 8345.90 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 463695.077 | 463695.077 | 24.393372 | 0.01135586 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 463695.08 | 463695.08 | 24.393372 | -27.60 | -27.60 | 0.00034190 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 1.3872 | 27.00 | 0.00700000 | 27.6430 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 10385.999 | 10385.999 | 0.562174 | 0.00025435 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 10386.00 | 10386.00 | 0.562174 | -27.60 | -27.60 | 0.00034190 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 2.7807 | 25.05 | 0.00098406 | 4.4026 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 99506.151 | 99506.151 | 5.384300 | 0.00243690 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 99506.15 | 99506.15 | 5.384300 | -27.60 | -27.60 | 0.00034190 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 2.9033 | 23.48 | 0.00098407 | 4.8367 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 10132.766 | 10132.766 | 0.548359 | 0.00024815 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 10132.77 | 10132.77 | 0.548359 | -27.60 | -27.60 | 0.00034190 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 2.8507 | 21.93 | 0.00098348 | 5.3126 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 24207.992 | 24207.992 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 24207.99 | 24207.99 | 24.393372 | -0.38 | -0.38 | 0.00690764 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 1.3872 | 27.00 | 0.00700000 | 27.6430 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BOT | 1118.309 | 1118.309 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 1118.31 | 1118.31 | 0.562174 | -0.77 | -5.61 | 0.00096620 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 2.7807 | 25.05 | 0.00098406 | 4.4026 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER MID | 11183.090 | 11183.090 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 11183.09 | 11183.09 | 5.384300 | -0.80 | -5.63 | 0.00096543 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 2.9033 | 23.48 | 0.00098407 | 4.8367 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER TOP | 1118.309 | 1118.309 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 1118.31 | 1118.31 | 0.548359 | -0.79 | -5.62 | 0.00096519 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 2.8507 | 21.93 | 0.00098348 | 5.3126 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 09:04:16
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 26556.585 | 26556.585 | 1.967896 | 0.00023233 | 565.018 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 29.47700371 | 54.44 | 82.22 | 27.78 | 3437563.82 | 0.7725 | 0.788089 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 26556.58 | 26556.58 | 1.0000 | 2.07246980 | 1.967896 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.23230489 | 60.00 | 32.22 | 27.78 | 0.000 | 26556.58 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.76 | 0.00799999 | 21.00 | 0.00799999 | 45.2309 | 9227.35 | 0.00 | 26650.12 | 26650.12 | 2.07246980 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 25.41 | 16.46 | 0.00800000 | 45918.9 | |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 522716.378 | 522716.378 | 19.298630 | 0.00457295 | 13324.093 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 29.47700371 | 54.44 | 82.22 | 27.78 | 3437563.82 | 15.2060 | 15.512039 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 522716.38 | 522716.38 | 1.0000 | 20.32415695 | 19.298630 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 4.57248442 | 60.00 | 32.22 | 27.78 | 0.000 | 522716.38 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.86 | 0.00800000 | 21.00 | 0.00800000 | 45.2310 | 352773.19 | 0.00 | 524329.70 | 524329.70 | 20.32415695 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 38.10 | 20.61 | 0.00800000 | 58858.2 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 114474.947 | 114474.947 | 3.900181 | 0.00100148 | 3020.418 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 29.47700371 | 54.44 | 82.22 | 27.78 | 3437563.82 | 3.3301 | 3.397138 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 114474.95 | 114474.95 | 1.0000 | 4.10743635 | 3.900181 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 1.00137462 | 60.00 | 32.22 | 27.78 | 0.000 | 114474.95 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00800000 | 21.00 | 0.00800000 | 45.2310 | 80130.06 | 0.00 | 114860.69 | 114860.69 | 4.10743635 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.22 | 21.25 | 0.00800000 | 61023.9 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 20010.399 | 20010.399 | 0.682446 | 0.00017506 | 527.730 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 29.47700371 | 54.44 | 82.22 | 27.78 | 3437563.82 | 0.5821 | 0.593825 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 20010.40 | 20010.40 | 1.0000 | 0.71871098 | 0.682446 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.17504184 | 60.00 | 32.22 | 27.78 | 0.000 | 20010.40 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00777257 | 21.00 | 0.00777257 | 43.9637 | 14004.02 | 0.00 | 20076.07 | 20076.07 | 0.71871098 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60993.3 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13735.438 | 13735.438 | 0.468499 | 0.00012016 | 362.221 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 29.47700371 | 54.44 | 82.22 | 27.78 | 3437563.82 | 0.3996 | 0.407610 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 13735.44 | 13735.44 | 1.0000 | 0.49339496 | 0.468499 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.12015135 | 60.00 | 32.22 | 27.78 | 0.000 | 13735.44 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00778445 | 21.00 | 0.00778445 | 44.0300 | 9611.96 | 0.00 | 13780.37 | 13780.37 | 0.49339496 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60989.5 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 21997.976 | 21997.976 | 0.750352 | 0.00019245 | 580.106 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 29.47700371 | 54.44 | 82.22 | 27.78 | 3437563.82 | 0.6399 | 0.652808 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 21997.98 | 21997.98 | 1.0000 | 0.79022525 | 0.750352 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.19242826 | 60.00 | 32.22 | 27.78 | 0.000 | 21997.98 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00780023 | 21.00 | 0.00780023 | 44.1180 | 15393.55 | 0.00 | 22069.87 | 22069.87 | 0.79022525 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60988.4 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11416.887 | 11416.887 | 0.389269 | 0.00009988 | 301.130 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 29.47700371 | 54.44 | 82.22 | 27.78 | 3437563.82 | 0.3321 | 0.338806 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 11416.89 | 11416.89 | 1.0000 | 0.40995459 | 0.389269 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.09986972 | 60.00 | 32.22 | 27.78 | 0.000 | 11416.89 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00770102 | 21.00 | 0.00770102 | 43.5646 | 7991.39 | 0.00 | 11454.61 | 11454.61 | 0.40995459 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 61001.0 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 286203.600 | 286203.600 | 9.767409 | 0.00250383 | 7545.671 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 29.47700371 | 54.44 | 82.22 | 27.78 | 3437563.82 | 8.3258 | 8.493328 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 286203.60 | 285306.53 | 1.0000 | 10.28644820 | 9.767409 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 2.50357853 | 60.00 | 32.22 | 27.78 | 0.000 | 286203.60 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00765732 | 21.00 | 0.00765732 | 43.3222 | 200265.88 | 0.00 | 287126.21 | 287126.21 | 10.28644820 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60972.9 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 189849.567 | 189849.567 | 6.479353 | 0.00166089 | 5005.233 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 29.47700371 | 54.44 | 82.22 | 27.78 | 3437563.82 | 5.5228 | 5.633942 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 189849.57 | 189849.57 | 1.0000 | 6.82366491 | 6.479353 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 1.66071741 | 60.00 | 32.22 | 27.78 | 0.000 | 189849.57 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00765595 | 21.00 | 0.00765595 | 43.3146 | 132841.97 | 0.00 | 190460.89 | 190460.89 | 6.82366491 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60971.6 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 289677.868 | 289677.868 | 9.886126 | 0.00253423 | 7637.217 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 29.47700371 | 54.44 | 82.22 | 27.78 | 3437563.82 | 8.4268 | 8.596429 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 289677.87 | 289677.87 | 1.0000 | 10.41147385 | 9.886126 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 2.53396984 | 60.00 | 32.22 | 27.78 | 0.000 | 289677.87 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00766138 | 21.00 | 0.00766138 | 43.3448 | 202694.95 | 0.00 | 290611.30 | 290611.30 | 10.41147385 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60972.4 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 186046.864 | 186046.864 | 6.349451 | 0.00162762 | 4905.020 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 29.47700371 | 54.44 | 82.22 | 27.78 | 3437563.82 | 5.4122 | 5.521094 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 186046.86 | 186046.86 | 1.0000 | 6.68686049 | 6.349451 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 1.62745309 | 60.00 | 32.22 | 27.78 | 0.000 | 186046.86 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00764910 | 21.00 | 0.00764910 | 43.2764 | 130183.00 | 0.00 | 186646.25 | 186646.25 | 6.68686049 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60972.2 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 37689.391 | 37689.391 | 1.286648 | 0.00032972 | 993.527 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 29.47700371 | 54.44 | 82.22 | 27.78 | 3437563.82 | 1.0964 | 1.118464 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 37689.39 | 37583.07 | 1.0000 | 1.35502071 | 1.286648 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.32968960 | 60.00 | 32.22 | 27.78 | 0.000 | 37689.39 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00767644 | 21.00 | 0.00767644 | 43.4299 | 26368.99 | 0.00 | 37809.86 | 37809.86 | 1.35502071 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.16 | 21.23 | 0.00800000 | 60963.4 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 24867.164 | 24867.164 | 0.848943 | 0.00021755 | 655.513 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 29.47700371 | 54.44 | 82.22 | 27.78 | 3437563.82 | 0.7234 | 0.737954 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 24867.16 | 24867.16 | 1.0000 | 0.89405546 | 0.848943 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.21752661 | 60.00 | 32.22 | 27.78 | 0.000 | 24867.16 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00767313 | 21.00 | 0.00767313 | 43.4115 | 17397.95 | 0.00 | 24946.59 | 24946.59 | 0.89405546 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.16 | 21.23 | 0.00800000 | 60962.6 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 38120.106 | 38120.106 | 1.301366 | 0.00033349 | 1004.876 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 29.47700371 | 54.44 | 82.22 | 27.78 | 3437563.82 | 1.1089 | 1.131246 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 38120.11 | 38120.11 | 1.0000 | 1.37051994 | 1.301366 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.33345730 | 60.00 | 32.22 | 27.78 | 0.000 | 38120.11 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00767993 | 21.00 | 0.00767993 | 43.4494 | 26670.14 | 0.00 | 38241.92 | 38241.92 | 1.37051994 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.16 | 21.23 | 0.00800000 | 60963.0 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 24809.039 | 24809.039 | 0.846961 | 0.00021704 | 653.980 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 29.47700371 | 54.44 | 82.22 | 27.78 | 3437563.82 | 0.7217 | 0.736229 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 24809.04 | 24809.04 | 1.0000 | 0.89196849 | 0.846961 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.21701816 | 60.00 | 32.22 | 27.78 | 0.000 | 24809.04 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00767261 | 21.00 | 0.00767261 | 43.4087 | 17357.28 | 0.00 | 24888.27 | 24888.27 | 0.89196849 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.16 | 21.23 | 0.00800000 | 60962.5 | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 176035.569 | -999.000 | 10.347066 | 0.00748896 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.0091 | 1004.8586 | 1.0531 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 10.347066 | 10.89690757 | 4197.9300 | 999.8980 | 89.53001635 | 12.27 | 6.67 | 5.60 | 2104708.15 | 8.3639 | 8.363894 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 176035.57 | 174160.21 | 1.0000 | 10.89690757 | 10.347066 | 26.34 | 14.64 | 0.00708413 | 44533.1 | 10.68 | 8.51 | 0.00700000 | 28378.5 | 7.48819609 | 6.67 | 12.27 | 5.60 | 23504.324 | 152531.24 | 33.40 | 0.00630683 | 16.37 | 2.53819000 | 24.5305 | 24.00 | 0.00734215 | 24.00 | 0.00734215 | 34.6326 | 122261.29 | 0.00 | 198291.93 | 195430.57 | 10.89690757 | 26.34 | 16.00 | 0.00708413 | 44533.1 | 8.72 | 8.71 | 0.00697982 | 26336.0 | |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 103606.038 | 103606.038 | 3.104120 | 0.00090639 | 1555.482 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 10.347066 | 10.89690757 | 4197.9300 | 999.8980 | 29.47700371 | 54.44 | 82.22 | 27.78 | 3437563.82 | 3.0139 | 3.074595 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 103606.04 | 103606.04 | 1.0000 | 3.26907227 | 3.104120 | -18.74 | -18.74 | 0.00170554 | -14624.2 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 0.90629835 | 60.00 | 32.22 | 27.78 | 0.000 | 103606.04 | -27.60 | 0.00034190 | -27.60 | 2.53819000 | 81.7684 | 21.00 | 0.00782146 | 19.41 | 0.00772660 | 48.2177 | 33826.76 | 0.00 | 81761.81 | 81761.81 | 3.26907227 | 2.80 | -1.65 | 0.00170554 | 7087.9 | 27.61 | 11.33 | 0.00170554 | 32098.6 | |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 1648180.258 | -999.000 | 95.646752 | 0.07011740 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.9912 | 1004.8586 | 1.0531 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 95.646752 | 100.72940890 | 4197.9300 | 999.8980 | 89.53001635 | 12.27 | 6.67 | 5.60 | 2104708.15 | 78.3092 | 78.309207 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 1648180.26 | 1632778.46 | 1.0000 | 100.72940890 | 95.646752 | 26.57 | 14.71 | 0.00707455 | 44740.9 | 10.68 | 8.51 | 0.00700000 | 28378.4 | 70.11024559 | 6.67 | 12.27 | 5.60 | 217270.514 | 1430909.74 | 33.40 | 0.00630683 | 16.37 | 25.38195000 | 26.5372 | 24.00 | 0.00736353 | 24.00 | 0.00736353 | 34.7321 | 1114157.20 | 0.00 | 1854349.07 | 1830011.82 | 100.72940890 | 26.57 | 16.07 | 0.00707455 | 44740.9 | 8.72 | 8.71 | 0.00697856 | 26331.7 | |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 1064885.028 | 1064885.028 | 28.694026 | 0.00931608 | 15542.295 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 95.646752 | 100.72940890 | 4197.9300 | 999.8980 | 29.47700371 | 54.44 | 82.22 | 27.78 | 3437563.82 | 30.9779 | 31.601341 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 1064885.03 | 1064885.03 | 1.0000 | 30.21882267 | 28.694026 | -22.27 | -22.27 | 0.00117628 | -19483.4 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 9.31512843 | 60.00 | 32.22 | 27.78 | 0.000 | 1064885.03 | -27.60 | 0.00034190 | -27.60 | 25.38195000 | 88.4573 | 18.59 | 0.00757052 | 17.82 | 0.00755555 | 52.0890 | 368953.52 | 0.00 | 811795.04 | 811795.04 | 30.21882267 | 2.80 | -2.50 | 0.00117628 | 5761.5 | 29.48 | 11.56 | 0.00117628 | 32625.4 | |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 181969.893 | -999.000 | 10.798494 | 0.00774142 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.9895 | 1004.8586 | 1.0531 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 10.798494 | 11.37232517 | 4197.9300 | 999.8980 | 89.53001635 | 12.27 | 6.67 | 5.60 | 2104708.15 | 8.6458 | 8.645849 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | Sensible | 181969.89 | 180260.93 | 1.0000 | 11.37232517 | 10.798494 | 26.22 | 14.59 | 0.00707361 | 44379.5 | 10.68 | 8.51 | 0.00700000 | 28378.4 | 7.74063019 | 6.67 | 12.27 | 5.60 | 24529.787 | 157440.11 | 33.40 | 0.00630683 | 16.37 | 2.53819000 | 23.5050 | 24.00 | 0.00731043 | 24.00 | 0.00731043 | 34.4845 | 129126.13 | 0.00 | 205157.41 | 202498.70 | 11.37232517 | 26.22 | 15.94 | 0.00707361 | 44379.5 | 8.73 | 8.71 | 0.00698073 | 26339.5 | |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 104739.206 | 104739.206 | 3.239548 | 0.00091630 | 1585.465 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 10.798494 | 11.37232517 | 4197.9300 | 999.8980 | 29.47700371 | 54.44 | 82.22 | 27.78 | 3437563.82 | 3.0469 | 3.108222 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 02:30:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 104739.21 | 104739.21 | 1.0000 | 3.41169755 | 3.239548 | -17.75 | -17.75 | 0.00188992 | -13173.3 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 0.91621079 | 60.00 | 32.22 | 27.78 | 0.000 | 104739.21 | -27.60 | 0.00034190 | -27.60 | 2.53819000 | 78.3501 | 17.89 | 0.00749217 | 15.76 | 0.00758378 | 59.5988 | 38318.26 | 0.00 | 83476.95 | 83476.95 | 3.41169755 | 2.80 | -1.35 | 0.00188992 | 7550.0 | 27.07 | 11.29 | 0.00188992 | 32017.8 | |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 98522.433 | -999.000 | 5.983658 | 0.00419137 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.3229 | 1004.8586 | 1.0531 | CAV_BAS FAN | Fan:ConstantVolume | 5.983658 | 6.30162870 | 4197.9300 | 999.8980 | 89.53001635 | 12.27 | 6.67 | 5.60 | 2104708.15 | 4.6810 | 4.681050 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 98522.43 | 95371.75 | 1.0000 | 6.30162870 | 5.983658 | 25.95 | 14.64 | 0.00725297 | 44560.2 | 11.22 | 8.74 | 0.00700000 | 28925.7 | 4.19094448 | 6.67 | 12.27 | 5.60 | 10146.215 | 88376.22 | 32.60 | 0.00630558 | 16.10 | 1.20015641 | 20.0572 | 24.00 | 0.00753016 | 24.00 | 0.00753016 | 35.5092 | 63647.68 | 0.00 | 111060.65 | 108708.53 | 6.30162870 | 25.95 | 16.00 | 0.00725297 | 44560.2 | 9.01 | 8.98 | 0.00710471 | 26936.1 | |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 288343.858 | 288343.858 | 5.983658 | 0.00252256 | 6142.169 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | CAV_BAS FAN | Fan:ConstantVolume | 5.983658 | 6.30162870 | 4197.9300 | 999.8980 | 29.47700371 | 54.44 | 82.22 | 27.78 | 3437563.82 | 8.3880 | 8.556842 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 288343.86 | 288343.86 | 1.0000 | 6.30162870 | 5.983658 | -5.54 | -9.81 | 0.00034190 | -4711.0 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 2.52230053 | 60.00 | 32.22 | 27.78 | 0.000 | 288343.86 | -27.60 | 0.00034190 | -27.60 | 1.20015641 | 20.0572 | 0.00 | 0.00034190 | 22.82 | 0.00034190 | 1.7515 | 0.00 | 0.00 | 228809.94 | 228809.94 | 6.30162870 | 12.80 | 2.46 | 0.00034190 | 13725.2 | 48.91 | 18.05 | 0.00034190 | 50034.8 | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 463695.077 | 260952.554 | 24.393372 | 0.01135586 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1017.9121 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 | Sensible | 402924.02 | 401452.92 | 0.8689 | -999.0 | -999.0 | 28.68 | 15.39 | 0.00703200 | 46779.9 | 12.80 | 9.41 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 402924.02 | 33.40 | 0.00630683 | 16.37 | 0.33839277 | -999.0000 | 27.00 | 0.00704221 | 27.00 | 0.00704221 | 27.8124 | 370798.99 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 10385.999 | 5906.253 | 0.562174 | 0.00025435 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1017.9685 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | Sensible | 8977.03 | 8911.64 | 0.8643 | -999.0 | -999.0 | 28.07 | 15.21 | 0.00706232 | 46235.2 | 12.80 | 9.41 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8977.03 | 26.57 | 0.00629632 | 14.04 | 0.01563234 | -999.0000 | 27.00 | 0.00708424 | 27.00 | 0.00708424 | 27.9745 | 8556.19 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 99506.151 | 56574.756 | 5.384300 | 0.00243690 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1017.9734 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | Sensible | 86012.11 | 85359.20 | 0.8644 | -999.0 | -999.0 | 28.07 | 15.21 | 0.00706495 | 46241.3 | 12.80 | 9.41 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 86012.11 | 26.57 | 0.00629632 | 14.04 | 0.15632344 | -999.0000 | 27.00 | 0.00708795 | 27.00 | 0.00708795 | 27.9891 | 81947.68 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 10132.766 | 5761.528 | 0.548359 | 0.00024815 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1017.9714 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | Sensible | 8758.46 | 8693.07 | 0.8644 | -999.0 | -999.0 | 28.07 | 15.21 | 0.00706387 | 46238.8 | 12.80 | 9.41 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8758.46 | 26.57 | 0.00629632 | 14.04 | 0.01563234 | -999.0000 | 27.00 | 0.00708640 | 27.00 | 0.00708640 | 27.9830 | 8345.90 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 463695.077 | 463695.077 | 24.393372 | 0.01135586 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 463695.08 | 463695.08 | 1.0000 | 25.68963282 | 24.393372 | -27.60 | -27.60 | 0.00034190 | -26896.1 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 463695.08 | -27.60 | 0.00034190 | -27.60 | 0.33839277 | 1.3872 | 0.00 | 0.00700000 | 27.00 | 0.00700000 | 27.6430 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 10385.999 | 10385.999 | 0.562174 | 0.00025435 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 10386.00 | 10386.00 | 1.0000 | 0.59204747 | 0.562174 | -27.60 | -27.60 | 0.00034190 | -26896.1 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10386.00 | -27.60 | 0.00034190 | -27.60 | 0.01563234 | 2.7807 | 0.00 | 0.00098406 | 25.05 | 0.00098406 | 4.4026 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 99506.151 | 99506.151 | 5.384300 | 0.00243690 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 99506.15 | 99506.15 | 1.0000 | 5.67042080 | 5.384300 | -27.60 | -27.60 | 0.00034190 | -26896.1 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 99506.15 | -27.60 | 0.00034190 | -27.60 | 0.15632344 | 2.9033 | 0.00 | 0.00098407 | 23.48 | 0.00098407 | 4.8367 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 10132.766 | 10132.766 | 0.548359 | 0.00024815 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 10132.77 | 10132.77 | 1.0000 | 0.57749876 | 0.548359 | -27.60 | -27.60 | 0.00034190 | -26896.1 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10132.77 | -27.60 | 0.00034190 | -27.60 | 0.01563234 | 2.8507 | 0.00 | 0.00098348 | 21.93 | 0.00098348 | 5.3126 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 24207.992 | 24207.992 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 24.393372 | 25.68963282 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 24207.99 | 24207.99 | 1.0000 | 25.68963282 | 24.393372 | -0.38 | -0.38 | 0.00690764 | 16885.9 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 24207.99 | -27.60 | 0.00034190 | -27.60 | 0.33839277 | 1.3872 | 0.00 | 0.00700000 | 27.00 | 0.00700000 | 27.6430 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 1118.309 | 1118.309 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.562174 | 0.59204747 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 1118.31 | 1118.31 | 1.0000 | 0.59204747 | 0.562174 | -0.77 | -5.61 | 0.00096620 | 1643.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 1118.31 | -27.60 | 0.00034190 | -27.60 | 0.01563234 | 2.7807 | 0.00 | 0.00098406 | 25.05 | 0.00098406 | 4.4026 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 11183.090 | 11183.090 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 5.384300 | 5.67042080 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 11183.09 | 11183.09 | 1.0000 | 5.67042080 | 5.384300 | -0.80 | -5.63 | 0.00096543 | 1607.9 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11183.09 | -27.60 | 0.00034190 | -27.60 | 0.15632344 | 2.9033 | 0.00 | 0.00098407 | 23.48 | 0.00098407 | 4.8367 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 1118.309 | 1118.309 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.548359 | 0.57749876 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 1118.31 | 1118.31 | 1.0000 | 0.57749876 | 0.548359 | -0.79 | -5.62 | 0.00096519 | 1621.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 1118.31 | -27.60 | 0.00034190 | -27.60 | 0.01563234 | 2.8507 | 0.00 | 0.00098348 | 21.93 | 0.00098348 | 5.3126 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:16
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 10.35 | - | |||
VAV_MID WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 95.65 | - | |||
VAV_TOP WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 10.80 | - | |||
CAV_BAS_OA_CONTROLLER | DifferentialDryBulb | 1.20 | 5.98 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 1413.33 | 1953.00 | 36.50 |
CORE_BOTTOM | 1298.00 | 1910.67 | 27.17 |
CORE_MID | 977.83 | 3691.50 | 294.83 |
CORE_TOP | 2009.17 | 4258.50 | 1337.50 |
PERIMETER_BOT_ZN_3 | 1653.67 | 3933.50 | 720.17 |
PERIMETER_BOT_ZN_2 | 2100.50 | 3698.33 | 859.33 |
PERIMETER_BOT_ZN_1 | 2213.33 | 3192.67 | 730.17 |
PERIMETER_BOT_ZN_4 | 2421.50 | 2612.67 | 476.50 |
PERIMETER_MID_ZN_3 | 2750.00 | 4480.83 | 2132.67 |
PERIMETER_MID_ZN_2 | 2579.33 | 3585.83 | 1713.83 |
PERIMETER_MID_ZN_1 | 2608.83 | 3627.83 | 1319.67 |
PERIMETER_MID_ZN_4 | 2835.33 | 4124.17 | 1732.17 |
PERIMETER_TOP_ZN_3 | 3439.17 | 4721.67 | 2858.50 |
PERIMETER_TOP_ZN_2 | 3547.67 | 4274.50 | 2504.67 |
PERIMETER_TOP_ZN_1 | 3084.67 | 3997.33 | 1963.00 |
PERIMETER_TOP_ZN_4 | 3363.50 | 4375.83 | 2346.00 |
DATACENTER_BOT_ZN_6 | 5777.67 | 338.17 | 337.00 |
DATACENTER_MID_ZN_6 | 5143.17 | 217.67 | 56.67 |
DATACENTER_TOP_ZN_6 | 4393.67 | 580.50 | 129.33 |
DATACENTER_BASEMENT_ZN_6 | 5943.00 | 5574.67 | 5574.67 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5943.00 | 5943.00 | 5943.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 49.83 | 0.00 | 1.67 |
CORE_BOTTOM | 0.00 | 3.00 | 0.00 | 0.00 |
CORE_MID | 0.17 | 0.17 | 0.00 | 0.00 |
CORE_TOP | 19.83 | 0.00 | 4.67 | 0.00 |
PERIMETER_BOT_ZN_3 | 7.50 | 2.50 | 1.33 | 1.33 |
PERIMETER_BOT_ZN_2 | 6.67 | 21.33 | 0.50 | 21.17 |
PERIMETER_BOT_ZN_1 | 7.67 | 33.67 | 0.50 | 30.17 |
PERIMETER_BOT_ZN_4 | 3.00 | 86.00 | 0.00 | 30.50 |
PERIMETER_MID_ZN_3 | 133.17 | 0.33 | 49.50 | 0.17 |
PERIMETER_MID_ZN_2 | 72.67 | 22.83 | 10.67 | 22.00 |
PERIMETER_MID_ZN_1 | 51.83 | 29.00 | 6.50 | 26.67 |
PERIMETER_MID_ZN_4 | 55.67 | 26.83 | 8.33 | 12.33 |
PERIMETER_TOP_ZN_3 | 321.67 | 3.67 | 113.83 | 2.50 |
PERIMETER_TOP_ZN_2 | 200.67 | 24.67 | 39.67 | 22.00 |
PERIMETER_TOP_ZN_1 | 164.17 | 23.67 | 28.17 | 19.50 |
PERIMETER_TOP_ZN_4 | 154.83 | 26.83 | 30.50 | 12.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 22.33 | 0.00 | 16.83 |
DATACENTER_MID_ZN_6 | 0.00 | 8.83 | 0.00 | 5.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 9.33 | 0.00 | 5.17 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 547.83 | 0.00 | 415.83 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 362.33 | 741.17 | 121.67 | 514.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:16
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.80 | 149.60 | 6779.02 | 1.232 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.50 | 134.35 | 6849.35 | 0.945 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.50 | 134.35 | 6849.35 | 0.714 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.50 | 134.35 | 6849.35 | 0.666 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.97 | 16.87 | 860.00 | 0.841 | 0.059 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.49 | 10.87 | 554.22 | 1.407 | 0.061 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.97 | 16.87 | 860.02 | 1.418 | 0.059 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.49 | 10.87 | 554.22 | 1.895 | 0.061 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.97 | 16.87 | 860.00 | 0.696 | 0.137 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.92 | 10.87 | 554.22 | 1.257 | 0.151 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.97 | 16.87 | 860.02 | 1.314 | 0.138 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.49 | 10.87 | 554.22 | 1.344 | 0.142 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.97 | 16.87 | 860.00 | 0.764 | 0.170 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.49 | 10.87 | 554.22 | 1.342 | 0.176 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.97 | 16.87 | 860.02 | 1.274 | 0.171 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.49 | 10.87 | 554.22 | 1.365 | 0.176 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.426 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.426 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.426 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.43 | 42.18 | 1911.37 | 0.481 | 0.000 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.80 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.50 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.50 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.50 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.97 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.49 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.97 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.49 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.97 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.92 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.97 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.49 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.97 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.49 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.97 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.49 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.43 | 42.18 | 1911.37 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 09:04:16
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | CAV_BAS | 61.80 | 149.60 | 6779.02 | 2779.43 | 1.2002 | 1.200 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 55.50 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
CORE_MID | VAV_MID WITH REHEAT | 55.50 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 10.778 |
CORE_TOP | VAV_TOP WITH REHEAT | 55.50 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 6.97 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 4.49 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 6.97 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 4.49 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 6.97 | 16.87 | 860.00 | 313.41 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 3.92 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 6.97 | 16.87 | 860.02 | 313.42 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 4.49 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 6.97 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 4.49 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 6.97 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 4.49 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.81 | 1.95 | 99.34 | 36.20 | 0.1563 | 0.156 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 17.43 | 42.18 | 1911.37 | 783.68 | 0.3384 | 0.338 |
Total Facility | 1024.28 | 2493.19 | 126016.35 | 46320.38 | 1.7261 | 158.471 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 51010889.82 | 0.00 | 51010889.82 | 0.00 | 51010889.82 | 37848132.68 | 3969.19 | 1051.40 | 3739.41 | 356.00 |
CORE_BOTTOM | 40717170.54 | 0.00 | 40717170.54 | 0.00 | 40717170.54 | 33990283.35 | 4656.03 | 48.09 | 4055.88 | 525.38 |
CORE_MID | 0.30E+09 | 0.00 | 0.30E+09 | 0.00 | 0.30E+09 | 0.34E+09 | 6129.01 | 34.43 | 2596.56 | 391.63 |
CORE_TOP | 27660189.33 | 0.00 | 27660189.33 | 0.00 | 27660189.33 | 33990283.35 | 6553.99 | 35.12 | 2170.89 | 442.67 |
PERIMETER_BOT_ZN_3 | 4579370.59 | 0.00 | 4579370.59 | 591585.02 | 5170955.60 | 4267819.30 | 5506.48 | 54.14 | 3199.39 | 525.38 |
PERIMETER_BOT_ZN_2 | 4931660.48 | 0.00 | 4931660.48 | 394389.74 | 5326050.22 | 2750345.05 | 3470.53 | 5.18 | 5284.29 | 525.38 |
PERIMETER_BOT_ZN_1 | 7593949.48 | 0.00 | 7593949.48 | 591585.02 | 8185534.50 | 4267912.63 | 3711.82 | 49.08 | 4999.10 | 525.38 |
PERIMETER_BOT_ZN_4 | 6647250.39 | 0.00 | 6647250.39 | 394389.74 | 7041640.13 | 2750345.05 | 3426.36 | 2.96 | 5330.68 | 525.38 |
PERIMETER_MID_ZN_3 | 36525268.15 | 0.00 | 36525268.15 | 1387434.57 | 37912702.72 | 42678193.03 | 5867.54 | 55.41 | 2837.05 | 391.63 |
PERIMETER_MID_ZN_2 | 46089190.77 | 0.00 | 46089190.77 | 924955.75 | 47014146.51 | 27503450.52 | 3932.20 | 4.51 | 4823.29 | 1300.63 |
PERIMETER_MID_ZN_1 | 67969330.55 | 0.00 | 67969330.55 | 1387434.57 | 69356765.12 | 42679126.28 | 4002.92 | 5.21 | 4751.87 | 391.63 |
PERIMETER_MID_ZN_4 | 45458704.15 | 0.00 | 45458704.15 | 924955.75 | 46383659.90 | 27503450.52 | 3902.22 | 10.44 | 4847.34 | 391.63 |
PERIMETER_TOP_ZN_3 | 3998120.48 | 0.00 | 3998120.48 | 1722650.34 | 5720770.82 | 4267819.30 | 4159.00 | 26.81 | 4574.19 | 442.67 |
PERIMETER_TOP_ZN_2 | 4492034.32 | 0.00 | 4492034.32 | 1148432.78 | 5640467.09 | 2750345.05 | 4047.03 | 3.88 | 4709.09 | 442.67 |
PERIMETER_TOP_ZN_1 | 6588084.35 | 0.00 | 6588084.35 | 1722650.34 | 8310734.69 | 4267912.63 | 4074.95 | 3.70 | 4681.35 | 442.67 |
PERIMETER_TOP_ZN_4 | 4602897.13 | 0.00 | 4602897.13 | 1148432.78 | 5751329.90 | 2750345.05 | 4026.12 | 3.96 | 4729.93 | 442.67 |
DATACENTER_BOT_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2442960.18 | 0.00 | 2442960.18 | 0.00 | 2442960.18 | 4929815.99 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 5288266.81 | 0.00 | 5288266.81 | 0.00 | 5288266.81 | 10671554.30 | 4419.00 | 4341.00 | 0.00 | 0.00 |
Total Facility | 0.51E+10 | 0.00 | 0.51E+10 | 53961922.12 | 0.52E+10 | 0.50E+10 | 6921.08 | 4409.92 | 5489.31 | 1985.14 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 2.2764 | 0.0000 | 2.2764 | 0.0000 | 2.2764 | 1.2002 | 1350.99 | 1047.43 | 3544.58 |
CORE_BOTTOM | 1.7643 | 0.0000 | 1.7643 | 0.0000 | 1.7643 | 1.0778 | 2236.57 | 46.55 | 3659.88 |
CORE_MID | 13.3434 | 0.0000 | 13.3434 | 0.0000 | 13.3434 | 10.7782 | 3435.37 | 34.07 | 2473.56 |
CORE_TOP | 1.2463 | 0.0000 | 1.2463 | 0.0000 | 1.2463 | 1.0778 | 3838.43 | 34.28 | 2070.29 |
PERIMETER_BOT_ZN_3 | 0.1974 | 0.0000 | 0.1974 | 0.0139 | 0.2113 | 0.1353 | 3079.71 | 52.05 | 2811.24 |
PERIMETER_BOT_ZN_2 | 0.2130 | 0.0000 | 0.2130 | 0.0092 | 0.2222 | 0.0872 | 1130.51 | 3.37 | 4809.12 |
PERIMETER_BOT_ZN_1 | 0.3328 | 0.0000 | 0.3328 | 0.0139 | 0.3466 | 0.1353 | 1339.49 | 43.72 | 4559.78 |
PERIMETER_BOT_ZN_4 | 0.2866 | 0.0000 | 0.2866 | 0.0092 | 0.2958 | 0.0872 | 1095.97 | 2.02 | 4845.01 |
PERIMETER_MID_ZN_3 | 1.6385 | 0.0000 | 1.6385 | 0.0325 | 1.6710 | 1.3533 | 3178.96 | 54.22 | 2709.82 |
PERIMETER_MID_ZN_2 | 1.9054 | 0.0000 | 1.9054 | 0.0230 | 1.9284 | 0.8721 | 1269.21 | 2.90 | 3761.89 |
PERIMETER_MID_ZN_1 | 3.0858 | 0.0000 | 3.0858 | 0.0325 | 3.1183 | 1.3533 | 1323.57 | 4.15 | 4615.28 |
PERIMETER_MID_ZN_4 | 2.0374 | 0.0000 | 2.0374 | 0.0217 | 2.0591 | 0.8721 | 1249.50 | 5.63 | 4687.87 |
PERIMETER_TOP_ZN_3 | 0.1799 | 0.0000 | 0.1799 | 0.0404 | 0.2203 | 0.1353 | 1449.25 | 26.01 | 4467.74 |
PERIMETER_TOP_ZN_2 | 0.2035 | 0.0000 | 0.2035 | 0.0269 | 0.2304 | 0.0872 | 1350.06 | 2.13 | 4590.81 |
PERIMETER_TOP_ZN_1 | 0.2995 | 0.0000 | 0.2995 | 0.0404 | 0.3399 | 0.1353 | 1371.55 | 2.12 | 4569.33 |
PERIMETER_TOP_ZN_4 | 0.2071 | 0.0000 | 0.2071 | 0.0269 | 0.2340 | 0.0872 | 1337.38 | 2.31 | 4603.31 |
DATACENTER_BOT_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.1142 | 0.0000 | 0.1142 | 0.0000 | 0.1142 | 0.1563 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.2472 | 0.0000 | 0.2472 | 0.0000 | 0.2472 | 0.3384 | 1602.00 | 4341.00 | 0.00 |
Total Facility | 228.7228 | 0.0000 | 228.7228 | 1.2778 | 230.0006 | 158.4706 | 4104.08 | 4382.23 | 4890.14 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV_BOT WITH REHEAT | 71503310.04 | 0.00 | 71503310.04 | 48026705.38 | 3565.47 | 7.56 | 5186.97 | 525.38 |
VAV_MID WITH REHEAT | 0.55E+09 | 0.00 | 0.55E+09 | 0.48E+09 | 4033.18 | 4.61 | 4722.21 | 391.63 |
VAV_TOP WITH REHEAT | 52506430.71 | 0.00 | 52506430.71 | 48026705.38 | 4096.02 | 0.96 | 4663.02 | 442.54 |
CAV_BAS | 56576361.89 | 0.00 | 56576361.89 | 37848132.68 | 3937.97 | 5.45 | 4816.57 | 356.00 |
AIRLOOP DATACENTER BASEMENT | 5865235.79 | 0.00 | 5865235.79 | 10671554.30 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER BOT | 270949.60 | 0.00 | 270949.60 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER MID | 2709495.95 | 0.00 | 2709495.95 | 4929815.99 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER TOP | 270949.60 | 0.00 | 270949.60 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV_BOT WITH REHEAT | 3.0988 | 0.0000 | 3.0988 | 1.5229 | 1182.07 | 4.69 | 4756.25 |
VAV_MID WITH REHEAT | 24.6044 | 0.0000 | 24.6044 | 15.2292 | 1346.58 | 2.88 | 4593.54 |
VAV_TOP WITH REHEAT | 2.3694 | 0.0000 | 2.3694 | 1.5229 | 1383.65 | 0.92 | 4558.44 |
CAV_BAS | 2.5247 | 0.0000 | 2.5247 | 1.2002 | 1339.31 | 1.50 | 4602.18 |
AIRLOOP DATACENTER BASEMENT | 0.2741 | 0.0000 | 0.2741 | 0.3384 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER BOT | 0.0127 | 0.0000 | 0.0127 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER MID | 0.1266 | 0.0000 | 0.1266 | 0.1563 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER TOP | 0.0127 | 0.0000 | 0.0127 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV_BOT WITH REHEAT | 0.00 | 0.26 | 3822.68 | 0.00 | 0.00 | 0.00 | 1587.42 | 0.00 | 0.00 | 0.00 |
VAV_MID WITH REHEAT | 0.00 | 0.00 | 3642.77 | 0.00 | 0.00 | 0.00 | 1575.33 | 0.00 | 0.00 | 0.00 |
VAV_TOP WITH REHEAT | 0.00 | 0.00 | 2942.13 | 0.00 | 0.00 | 0.00 | 2315.36 | 0.00 | 0.00 | 0.00 |
CAV_BAS | 0.00 | 1036.14 | 3972.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV_BOT WITH REHEAT | 0.0000 | 0.0000 | 4.6630 | 0.0000 | 0.0000 | 0.0000 | 1.9154 | 0.0000 | 0.0000 | 0.0000 |
VAV_MID WITH REHEAT | 0.0000 | 0.0000 | 35.9590 | 0.0000 | 0.0000 | 0.0000 | 18.6168 | 0.0000 | 0.0000 | 0.0000 |
VAV_TOP WITH REHEAT | 0.0000 | 0.0000 | 3.9235 | 0.0000 | 0.0000 | 0.0000 | 1.8473 | 0.0000 | 0.0000 | 0.0000 |
CAV_BAS | 0.0000 | 1.3313 | 3.7681 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BASEMENT | 0.0000 | 0.3754 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BOT | 0.0000 | 0.0173 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER MID | 0.0000 | 0.1734 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER TOP | 0.0000 | 0.0173 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:16
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 8 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1380 |
Defaulted Fields | 1179 |
Fields with Defaults | 3862 |
Autosized Fields | 330 |
Autosizable Fields | 409 |
Autocalculated Fields | 226 |
Autocalculatable Fields | 473 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 09:04:16
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 28071.14 | 383095.38 | 29-JAN-10:40 | 1959607.51 | 07-AUG-15:40 |
Electricity:Building | 17959.53 | 247233.96 | 01-JAN-09:50 | 1055078.17 | 01-DEC-16:40 |
Electricity:Zone:BASEMENT | 602.14 | 14319.77 | 01-JAN-00:10 | 28977.00 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 17959.53 | 247233.96 | 01-JAN-09:50 | 1055078.17 | 01-DEC-16:40 |
InteriorLights:Electricity | 2746.12 | 13024.70 | 01-JAN-09:50 | 261074.09 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:BASEMENT | 177.74 | 862.23 | 01-JAN-00:10 | 15519.45 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 2746.12 | 13024.70 | 01-JAN-09:50 | 261074.09 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 2746.12 | 13024.70 | 01-JAN-09:50 | 261074.09 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 177.74 | 862.23 | 01-JAN-00:10 | 15519.45 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 2746.12 | 13024.70 | 01-JAN-09:50 | 261074.09 | 02-JAN-08:10 |
Electricity:Zone:CORE_BOTTOM | 480.91 | 6817.20 | 01-JAN-00:10 | 32066.15 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 159.62 | 774.34 | 01-JAN-00:10 | 13937.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 159.62 | 774.34 | 01-JAN-00:10 | 13937.56 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 4809.09 | 68171.81 | 01-JAN-00:10 | 320660.81 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 1596.25 | 7743.41 | 01-JAN-00:10 | 139375.61 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 1596.25 | 7743.41 | 01-JAN-00:10 | 139375.61 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 480.91 | 6817.18 | 01-JAN-00:10 | 32066.08 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 159.62 | 774.34 | 01-JAN-00:10 | 13937.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 159.62 | 774.34 | 01-JAN-00:10 | 13937.56 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 54.26 | 818.50 | 01-JAN-09:40 | 4026.32 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 13.92 | 59.73 | 01-JAN-09:40 | 1750.00 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 13.92 | 59.73 | 01-JAN-09:40 | 1750.00 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 34.92 | 527.47 | 01-JAN-08:50 | 2594.71 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 8.92 | 38.49 | 01-JAN-08:50 | 1127.77 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 8.92 | 38.49 | 01-JAN-08:50 | 1127.77 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 54.13 | 818.51 | 01-JAN-08:50 | 4026.39 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 13.78 | 59.73 | 01-JAN-08:50 | 1750.04 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 13.78 | 59.73 | 01-JAN-08:50 | 1750.04 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 34.93 | 527.47 | 01-JAN-09:40 | 2594.70 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 8.94 | 38.49 | 01-JAN-09:40 | 1127.77 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 8.94 | 38.49 | 01-JAN-09:40 | 1127.77 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 542.78 | 8184.99 | 01-JAN-09:50 | 40263.18 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 139.36 | 597.26 | 01-JAN-09:50 | 17500.00 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 139.36 | 597.26 | 01-JAN-09:50 | 17500.00 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 349.24 | 5274.72 | 01-JAN-08:50 | 25947.12 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 89.26 | 384.90 | 01-JAN-08:50 | 11277.66 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 89.26 | 384.90 | 01-JAN-08:50 | 11277.66 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 541.35 | 8185.12 | 01-JAN-08:50 | 40263.91 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 137.92 | 597.27 | 01-JAN-08:50 | 17500.38 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 137.92 | 597.27 | 01-JAN-08:50 | 17500.38 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 349.38 | 5274.69 | 01-JAN-09:50 | 25947.03 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 89.40 | 384.90 | 01-JAN-09:50 | 11277.66 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 89.40 | 384.90 | 01-JAN-09:50 | 11277.66 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 54.28 | 818.50 | 01-JAN-09:50 | 4026.32 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 13.94 | 59.73 | 01-JAN-09:50 | 1750.00 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 13.94 | 59.73 | 01-JAN-09:50 | 1750.00 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 34.92 | 527.47 | 01-JAN-08:50 | 2594.71 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 8.93 | 38.49 | 01-JAN-08:50 | 1127.77 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 8.93 | 38.49 | 01-JAN-08:50 | 1127.77 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 54.14 | 818.51 | 01-JAN-08:50 | 4026.39 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 13.79 | 59.73 | 01-JAN-08:50 | 1750.04 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 13.79 | 59.73 | 01-JAN-08:50 | 1750.04 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 34.94 | 527.47 | 01-JAN-09:50 | 2594.70 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 8.94 | 38.49 | 01-JAN-09:50 | 1127.77 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 8.94 | 38.49 | 01-JAN-09:50 | 1127.77 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7544.97 | 95151.24 | 01-JAN-00:10 | 384008.34 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 50.12 | 243.11 | 01-JAN-00:10 | 4375.82 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 50.12 | 243.11 | 01-JAN-00:10 | 4375.82 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 158.52 | 1971.11 | 01-JAN-00:10 | 8199.53 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 4.64 | 22.51 | 01-JAN-00:10 | 405.10 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 4.64 | 22.51 | 01-JAN-00:10 | 405.10 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1585.20 | 19711.13 | 01-JAN-00:10 | 81995.25 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 46.40 | 225.07 | 01-JAN-00:10 | 4051.03 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 46.40 | 225.07 | 01-JAN-00:10 | 4051.03 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 158.52 | 1971.11 | 01-JAN-00:10 | 8199.53 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 4.64 | 22.51 | 01-JAN-00:10 | 405.10 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 4.64 | 22.51 | 01-JAN-00:10 | 405.10 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 15213.41 | 234209.26 | 01-JAN-00:10 | 794004.08 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 15213.41 | 234209.26 | 01-JAN-00:10 | 794004.08 | 03-APR-07:10 |
MiscPlug:InteriorEquipment:Electricity | 5871.99 | 115917.86 | 01-JAN-00:10 | 320838.49 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 5871.99 | 115917.86 | 01-JAN-00:10 | 320838.49 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 321.29 | 6042.86 | 01-JAN-00:10 | 18128.59 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 321.29 | 6042.86 | 01-JAN-00:10 | 18128.59 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 3212.85 | 60428.40 | 01-JAN-00:10 | 181285.20 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 3212.85 | 60428.40 | 01-JAN-00:10 | 181285.20 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 321.28 | 6042.84 | 01-JAN-00:10 | 18128.52 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 321.28 | 6042.84 | 01-JAN-00:10 | 18128.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 40.34 | 758.77 | 01-JAN-00:10 | 2276.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 40.34 | 758.77 | 01-JAN-00:10 | 2276.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.95 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.95 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 40.34 | 758.78 | 01-JAN-00:10 | 2276.35 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 40.34 | 758.78 | 01-JAN-00:10 | 2276.35 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.94 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.94 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 403.42 | 7587.73 | 01-JAN-00:10 | 22763.18 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 403.42 | 7587.73 | 01-JAN-00:10 | 22763.18 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 259.98 | 4889.82 | 01-JAN-00:10 | 14669.46 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 259.98 | 4889.82 | 01-JAN-00:10 | 14669.46 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 403.43 | 7587.84 | 01-JAN-00:10 | 22763.53 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 403.43 | 7587.84 | 01-JAN-00:10 | 22763.53 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 259.98 | 4889.79 | 01-JAN-00:10 | 14669.36 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 259.98 | 4889.79 | 01-JAN-00:10 | 14669.36 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 40.34 | 758.77 | 01-JAN-00:10 | 2276.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 40.34 | 758.77 | 01-JAN-00:10 | 2276.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.95 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.95 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 40.34 | 758.78 | 01-JAN-00:10 | 2276.35 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 40.34 | 758.78 | 01-JAN-00:10 | 2276.35 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.94 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.94 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
Electricity:Plant | 1656.51 | 5083.83 | 10-JAN-22:10 | 432377.14 | 07-SEP-15:00 |
HeatRejection:Electricity | 809.21 | 1238.62 | 10-JAN-22:00 | 80284.75 | 06-JUN-14:50 |
General:HeatRejection:Electricity | 809.21 | 1238.62 | 10-JAN-22:00 | 80284.75 | 06-JUN-14:50 |
Electricity:HVAC | 6152.64 | 95621.60 | 09-JAN-24:00 | 507265.50 | 11-AUG-15:30 |
ExteriorEquipment:Electricity | 1914.38 | 28294.68 | 01-JAN-00:10 | 117204.73 | 02-JAN-08:20 |
Transformer:ExteriorEquipment:Electricity | 59.77 | 1112.61 | 01-JAN-00:10 | 3726.76 | 01-DEC-16:50 |
ElectricityPurchased:Facility | 28071.14 | 383095.38 | 29-JAN-10:40 | 1959607.51 | 07-AUG-15:40 |
ElectricityPurchased:Plant | 28071.14 | 383095.38 | 29-JAN-10:40 | 1959607.51 | 07-AUG-15:40 |
Cogeneration:ElectricityPurchased | 28071.14 | 383095.38 | 29-JAN-10:40 | 1959607.51 | 07-AUG-15:40 |
General:Cogeneration:ElectricityPurchased | 28071.14 | 383095.38 | 29-JAN-10:40 | 1959607.51 | 07-AUG-15:40 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 28071.14 | 383095.38 | 29-JAN-10:40 | 1959607.51 | 07-AUG-15:40 |
ElectricityNet:Plant | 28071.14 | 383095.38 | 29-JAN-10:40 | 1959607.51 | 07-AUG-15:40 |
Cogeneration:ElectricityNet | 28071.14 | 383095.38 | 29-JAN-10:40 | 1959607.51 | 07-AUG-15:40 |
General:Cogeneration:ElectricityNet | 28071.14 | 383095.38 | 29-JAN-10:40 | 1959607.51 | 07-AUG-15:40 |
Fans:Electricity | 2550.45 | 47505.61 | 01-JAN-00:10 | 308014.36 | 17-JUL-15:10 |
General:Fans:Electricity | 2550.45 | 47505.61 | 01-JAN-00:10 | 308014.36 | 17-JUL-15:10 |
ExteriorLights:Electricity | 447.85 | 0.00 | 01-JAN-08:20 | 37611.08 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 447.85 | 0.00 | 01-JAN-08:20 | 37611.08 | 01-JAN-06:10 |
ElevatorLift:ExteriorEquipment:Electricity | 1848.78 | 27144.47 | 01-JAN-00:10 | 113101.96 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 5.83 | 37.60 | 01-JAN-00:10 | 376.00 | 01-JAN-07:10 |
Cooling:Electricity | 3166.61 | 30101.61 | 09-JAN-07:10 | 414820.51 | 17-JUL-15:30 |
General:Cooling:Electricity | 3166.61 | 30101.61 | 09-JAN-07:10 | 414820.51 | 17-JUL-15:30 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Humidifier:Electricity | 841.32 | 0.00 | 13-JUL-15:20 | 51932.06 | 28-DEC-19:00 |
General:Humidifier:Electricity | 841.32 | 0.00 | 13-JUL-15:20 | 51932.06 | 28-DEC-19:00 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Pumps:Electricity | 381.79 | 3646.01 | 01-JAN-00:10 | 54235.53 | 05-SEP-12:30 |
General:Pumps:Electricity | 381.79 | 3646.01 | 01-JAN-00:10 | 54235.53 | 05-SEP-12:30 |
WIRED_LTG_ELECTRICITY | 77.17 | 0.00 | 01-JAN-00:10 | 7336.18 | 02-JAN-08:20 |
WIRED_INT_EQUIP | 5871.99 | 115917.86 | 04-MAR-00:10 | 320838.49 | 03-APR-07:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 4265.61 | 5695.87 | 05-JAN-22:20 | 2375340.32 | 09-JAN-07:10 |
NaturalGas:Plant | 4265.61 | 5695.87 | 05-JAN-22:20 | 2375340.32 | 09-JAN-07:10 |
Heating:NaturalGas | 3494.03 | 0.00 | 01-JAN-00:10 | 2355196.33 | 09-JAN-07:10 |
Boiler:Heating:NaturalGas | 3494.03 | 0.00 | 01-JAN-00:10 | 2355196.33 | 09-JAN-07:10 |
WaterSystems:NaturalGas | 771.58 | 5695.87 | 05-JAN-22:20 | 85533.81 | 16-FEB-12:40 |
Water Heater:WaterSystems:NaturalGas | 771.58 | 5695.87 | 05-JAN-22:20 | 85533.81 | 16-FEB-12:40 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 16683.15 | 146491.17 | 09-JAN-08:00 | 2363057.10 | 07-SEP-15:00 |
PlantLoopCoolingDemand:HVAC | 16683.15 | 146491.17 | 09-JAN-08:00 | 2363057.10 | 07-SEP-15:00 |
CoolingCoils:PlantLoopCoolingDemand | 16683.15 | 146491.17 | 09-JAN-08:00 | 2363057.10 | 07-SEP-15:00 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 5613.73 | 0.00 | 03-SEP-24:00 | 0.00 | 17-JUL-16:00 |
Water:HVAC | 312.97 | 0.00 | 13-JUL-15:20 | 0.00 | 28-DEC-19:00 |
Humidifier:Water | 312.97 | 0.00 | 13-JUL-15:20 | 0.00 | 28-DEC-19:00 |
General:Humidifier:Water | 312.97 | 0.00 | 13-JUL-15:20 | 0.00 | 28-DEC-19:00 |
MainsWater:Facility | 5613.73 | 0.00 | 03-SEP-24:00 | 0.00 | 17-JUL-16:00 |
MainsWater:HVAC | 312.97 | 0.00 | 13-JUL-15:20 | 0.00 | 28-DEC-19:00 |
Humidifier:MainsWater | 312.97 | 0.00 | 13-JUL-15:20 | 0.00 | 28-DEC-19:00 |
General:Humidifier:MainsWater | 312.97 | 0.00 | 13-JUL-15:20 | 0.00 | 28-DEC-19:00 |
Water:Plant | 5300.76 | 0.00 | 01-JAN-00:10 | 0.00 | 17-JUL-16:00 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 5300.76 | 0.00 | 01-JAN-00:10 | 0.00 | 17-JUL-16:00 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatRejection:Water | 3020.59 | 0.00 | 01-JAN-00:10 | 0.00 | 17-JUL-16:00 |
General:HeatRejection:Water | 3020.59 | 0.00 | 01-JAN-00:10 | 0.00 | 17-JUL-16:00 |
HeatRejection:MainsWater | 3020.59 | 0.00 | 01-JAN-00:10 | 0.00 | 17-JUL-16:00 |
General:HeatRejection:MainsWater | 3020.59 | 0.00 | 01-JAN-00:10 | 0.00 | 17-JUL-16:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 47891.39 | 227585.06 | 30-JAN-06:00 | 10156531.75 | 07-SEP-15:00 |
EnergyTransfer:Building | 17918.11 | 87625.13 | 12-JAN-22:10 | 1664660.42 | 07-AUG-15:20 |
EnergyTransfer:Zone:BASEMENT | 619.99 | 0.00 | 01-JAN-00:10 | 68155.92 | 05-SEP-05:10 |
Heating:EnergyTransfer | 1012.97 | 0.00 | 01-FEB-00:40 | 1308936.12 | 09-JAN-06:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 2.95 | 0.00 | 01-JAN-00:10 | 21625.22 | 05-AUG-16:10 |
General:Heating:EnergyTransfer | 1012.97 | 0.00 | 01-FEB-00:40 | 1308936.12 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 2.95 | 0.00 | 01-JAN-00:10 | 21625.22 | 05-AUG-16:10 |
Cooling:EnergyTransfer | 16905.14 | 82850.23 | 09-JAN-05:50 | 1664660.42 | 07-AUG-15:20 |
Cooling:EnergyTransfer:Zone:BASEMENT | 617.04 | 0.00 | 01-JAN-00:10 | 68155.92 | 05-SEP-05:10 |
General:Cooling:EnergyTransfer | 16905.14 | 82850.23 | 09-JAN-05:50 | 1664660.42 | 07-AUG-15:20 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 617.04 | 0.00 | 01-JAN-00:10 | 68155.92 | 05-SEP-05:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 564.11 | 0.00 | 01-JAN-00:10 | 55774.90 | 07-AUG-07:20 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 564.11 | 0.00 | 01-JAN-00:10 | 55774.90 | 07-AUG-07:20 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 564.11 | 0.00 | 01-JAN-00:10 | 55774.90 | 07-AUG-07:20 |
EnergyTransfer:Zone:CORE_MID | 3929.82 | 0.00 | 01-JAN-00:10 | 419804.15 | 05-SEP-13:10 |
Heating:EnergyTransfer:Zone:CORE_MID | 9.14 | 0.00 | 01-JAN-00:10 | 375849.59 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 9.14 | 0.00 | 01-JAN-00:10 | 375849.59 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 3920.68 | 0.00 | 01-JAN-00:10 | 419804.15 | 05-SEP-13:10 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 3920.68 | 0.00 | 01-JAN-00:10 | 419804.15 | 05-SEP-13:10 |
EnergyTransfer:Zone:CORE_TOP | 351.92 | 0.00 | 01-JAN-00:10 | 67582.89 | 06-MAR-05:10 |
Heating:EnergyTransfer:Zone:CORE_TOP | 23.62 | 0.00 | 01-JAN-00:10 | 67582.89 | 06-MAR-05:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 23.62 | 0.00 | 01-JAN-00:10 | 67582.89 | 06-MAR-05:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 328.30 | 0.00 | 01-JAN-00:10 | 50152.94 | 17-JUL-15:30 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 328.30 | 0.00 | 01-JAN-00:10 | 50152.94 | 17-JUL-15:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 60.11 | 0.00 | 01-JAN-00:10 | 11662.58 | 09-JAN-05:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 3.49 | 0.00 | 01-JAN-00:10 | 11662.58 | 09-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 3.49 | 0.00 | 01-JAN-00:10 | 11662.58 | 09-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 56.62 | 0.00 | 01-JAN-00:10 | 9961.26 | 09-AUG-14:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 56.62 | 0.00 | 01-JAN-00:10 | 9961.26 | 09-AUG-14:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 60.69 | 0.00 | 01-JAN-00:10 | 14384.75 | 07-AUG-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 2.54 | 0.00 | 01-JAN-00:10 | 9684.18 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 2.54 | 0.00 | 01-JAN-00:10 | 9684.18 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 58.14 | 0.00 | 01-JAN-00:10 | 14384.75 | 07-AUG-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 58.14 | 0.00 | 01-JAN-00:10 | 14384.75 | 07-AUG-08:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 100.67 | 0.00 | 01-JAN-00:10 | 19912.19 | 18-OCT-13:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 3.51 | 0.00 | 01-JAN-00:10 | 15952.30 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 3.51 | 0.00 | 01-JAN-00:10 | 15952.30 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 97.16 | 0.00 | 01-JAN-00:10 | 19912.19 | 18-OCT-13:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 97.16 | 0.00 | 01-JAN-00:10 | 19912.19 | 18-OCT-13:20 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 88.90 | 0.00 | 01-JAN-00:10 | 18099.02 | 07-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.74 | 0.00 | 01-JAN-00:10 | 7163.56 | 09-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.74 | 0.00 | 01-JAN-00:10 | 7163.56 | 09-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 88.16 | 0.00 | 01-JAN-00:10 | 18099.02 | 07-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 88.16 | 0.00 | 01-JAN-00:10 | 18099.02 | 07-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 570.02 | 0.00 | 01-JAN-00:10 | 126669.65 | 30-JAN-04:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 212.83 | 0.00 | 01-JAN-00:10 | 126669.65 | 30-JAN-04:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 212.83 | 0.00 | 01-JAN-00:10 | 126669.65 | 30-JAN-04:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 357.19 | 0.00 | 01-JAN-00:10 | 91082.35 | 17-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 357.19 | 0.00 | 01-JAN-00:10 | 91082.35 | 17-JUL-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 592.16 | 0.00 | 01-JAN-00:10 | 147626.83 | 09-JAN-05:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 125.87 | 0.00 | 01-JAN-00:10 | 147626.83 | 09-JAN-05:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 125.87 | 0.00 | 01-JAN-00:10 | 147626.83 | 09-JAN-05:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 466.30 | 0.00 | 01-JAN-00:10 | 146550.70 | 07-AUG-09:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 466.30 | 0.00 | 01-JAN-00:10 | 146550.70 | 07-AUG-09:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 941.39 | 0.00 | 01-JAN-00:10 | 206549.70 | 18-OCT-13:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 124.94 | 0.00 | 01-JAN-00:10 | 189493.24 | 09-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 124.94 | 0.00 | 01-JAN-00:10 | 189493.24 | 09-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 816.45 | 0.00 | 01-JAN-00:10 | 206549.70 | 18-OCT-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 816.45 | 0.00 | 01-JAN-00:10 | 206549.70 | 18-OCT-13:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 584.60 | 0.00 | 01-JAN-00:10 | 153567.46 | 17-JUL-17:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 99.98 | 0.00 | 01-JAN-00:10 | 142968.53 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 99.98 | 0.00 | 01-JAN-00:10 | 142968.53 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 484.63 | 0.00 | 01-JAN-00:10 | 153567.46 | 17-JUL-17:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 484.63 | 0.00 | 01-JAN-00:10 | 153567.46 | 17-JUL-17:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 83.22 | 0.00 | 01-JAN-00:10 | 17313.03 | 09-JAN-02:50 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 50.87 | 0.00 | 01-JAN-00:10 | 17313.03 | 09-JAN-02:50 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 50.87 | 0.00 | 01-JAN-00:10 | 17313.03 | 09-JAN-02:50 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 32.35 | 0.00 | 01-JAN-00:10 | 10379.17 | 17-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 32.35 | 0.00 | 01-JAN-00:10 | 10379.17 | 17-JUL-16:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 71.49 | 0.00 | 01-JAN-00:10 | 16549.76 | 09-JAN-04:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 29.21 | 0.00 | 01-JAN-00:10 | 16549.76 | 09-JAN-04:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 29.21 | 0.00 | 01-JAN-00:10 | 16549.76 | 09-JAN-04:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 42.28 | 0.00 | 01-JAN-00:10 | 14879.48 | 07-AUG-09:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 42.28 | 0.00 | 01-JAN-00:10 | 14879.48 | 07-AUG-09:20 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 105.87 | 0.00 | 01-JAN-00:10 | 21963.10 | 09-JAN-04:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 33.39 | 0.00 | 01-JAN-00:10 | 21963.10 | 09-JAN-04:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 33.39 | 0.00 | 01-JAN-00:10 | 21963.10 | 09-JAN-04:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 72.48 | 0.00 | 01-JAN-00:10 | 21768.07 | 01-SEP-13:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 72.48 | 0.00 | 01-JAN-00:10 | 21768.07 | 01-SEP-13:40 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 68.55 | 0.00 | 01-JAN-00:10 | 17569.36 | 30-JAN-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 24.31 | 0.00 | 01-JAN-00:10 | 17569.36 | 30-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 24.31 | 0.00 | 01-JAN-00:10 | 17569.36 | 30-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 44.24 | 0.00 | 01-JAN-00:10 | 16258.27 | 17-JUL-17:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 44.24 | 0.00 | 01-JAN-00:10 | 16258.27 | 17-JUL-17:00 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 49.59 | 0.00 | 01-JAN-00:10 | 10303.53 | 07-AUG-07:10 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 6.53 | 0.00 | 01-JAN-00:10 | 6750.32 | 30-JAN-13:40 |
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 6.53 | 0.00 | 01-JAN-00:10 | 6750.32 | 30-JAN-13:40 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 43.06 | 0.00 | 01-JAN-00:10 | 10303.53 | 07-AUG-07:10 |
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 43.06 | 0.00 | 01-JAN-00:10 | 10303.53 | 07-AUG-07:10 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 437.69 | 0.00 | 01-JAN-00:10 | 122323.57 | 09-JAN-06:10 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 178.29 | 0.00 | 01-JAN-00:10 | 122323.57 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 178.29 | 0.00 | 01-JAN-00:10 | 122323.57 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 259.40 | 0.00 | 01-JAN-00:10 | 78346.75 | 17-JUL-15:30 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 259.40 | 0.00 | 01-JAN-00:10 | 78346.75 | 17-JUL-15:30 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 115.23 | 0.00 | 01-JAN-00:10 | 32432.28 | 09-JAN-05:10 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 73.03 | 0.00 | 01-JAN-00:10 | 32432.28 | 09-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 73.03 | 0.00 | 01-JAN-00:10 | 32432.28 | 09-JAN-05:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 42.20 | 0.00 | 01-JAN-00:10 | 22087.46 | 17-JUL-15:10 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 42.20 | 0.00 | 01-JAN-00:10 | 22087.46 | 17-JUL-15:10 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 135.05 | 4.90 | 07-JAN-21:40 | 8240.94 | 22-APR-18:10 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.09 | 0.00 | 01-JAN-00:10 | 631.45 | 09-JAN-03:40 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.09 | 0.00 | 01-JAN-00:10 | 631.45 | 09-JAN-03:40 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 134.96 | 0.00 | 07-JAN-22:40 | 8240.94 | 22-APR-18:10 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 134.96 | 0.00 | 07-JAN-22:40 | 8240.94 | 22-APR-18:10 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1145.12 | 5.94 | 05-JAN-00:50 | 78143.70 | 03-AUG-18:50 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 6.49 | 0.00 | 02-JAN-09:20 | 6652.62 | 29-JAN-17:50 |
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 6.49 | 0.00 | 02-JAN-09:20 | 6652.62 | 29-JAN-17:50 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1138.64 | 0.00 | 01-JAN-00:10 | 78143.70 | 03-AUG-18:50 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1138.64 | 0.00 | 01-JAN-00:10 | 78143.70 | 03-AUG-18:50 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 102.75 | 0.36 | 31-JAN-09:10 | 7928.49 | 03-AUG-18:40 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 1.16 | 0.00 | 02-JAN-13:40 | 769.38 | 30-APR-23:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 1.16 | 0.00 | 02-JAN-13:40 | 769.38 | 30-APR-23:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 101.59 | 0.00 | 01-JAN-00:10 | 7928.49 | 03-AUG-18:40 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 101.59 | 0.00 | 01-JAN-00:10 | 7928.49 | 03-AUG-18:40 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7139.16 | 82830.98 | 09-JAN-05:00 | 368974.89 | 22-AUG-07:10 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7139.16 | 82830.98 | 09-JAN-05:00 | 368974.89 | 22-AUG-07:10 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7139.16 | 82830.98 | 09-JAN-05:00 | 368974.89 | 22-AUG-07:10 |
PlantLoopHeatingDemand:Facility | 3166.19 | 0.00 | 01-JAN-00:10 | 2013918.74 | 09-JAN-07:10 |
PlantLoopHeatingDemand:Plant | 463.31 | 0.00 | 01-JAN-00:10 | 57401.28 | 16-FEB-12:20 |
WaterSystems:PlantLoopHeatingDemand | 463.31 | 0.00 | 01-JAN-00:10 | 57401.28 | 16-FEB-12:20 |
General:WaterSystems:PlantLoopHeatingDemand | 463.31 | 0.00 | 01-JAN-00:10 | 57401.28 | 16-FEB-12:20 |
EnergyTransfer:HVAC | 16684.93 | 137190.00 | 09-JAN-24:00 | 2306350.52 | 07-SEP-15:00 |
HeatingCoils:EnergyTransfer | 2702.88 | 0.00 | 01-JAN-00:10 | 1995333.15 | 09-JAN-07:10 |
PlantLoopHeatingDemand:HVAC | 2702.88 | 0.00 | 01-JAN-00:10 | 1995333.15 | 09-JAN-07:10 |
HeatingCoils:PlantLoopHeatingDemand | 2702.88 | 0.00 | 01-JAN-00:10 | 1995333.15 | 09-JAN-07:10 |
CoolingCoils:EnergyTransfer | 13982.05 | 116388.28 | 09-JAN-08:00 | 2306350.52 | 07-SEP-15:00 |
EnergyTransfer:Plant | 13288.34 | 0.00 | 01-JAN-00:10 | 6738888.41 | 07-SEP-15:00 |
LoopToLoop:EnergyTransfer | 3401.26 | -2293.24 | 25-FEB-14:00 | 2141281.34 | 07-SEP-15:00 |
WaterSystems:EnergyTransfer | 463.31 | 0.00 | 01-JAN-00:10 | 57401.28 | 16-FEB-12:20 |
WaterUse:WaterSystems:EnergyTransfer | 463.31 | 0.00 | 01-JAN-00:10 | 57401.28 | 16-FEB-12:20 |
Boilers:EnergyTransfer | 2688.98 | 0.00 | 01-JAN-00:10 | 1957865.55 | 09-JAN-07:10 |
Chillers:EnergyTransfer | 3134.64 | 0.00 | 01-JAN-00:10 | 2135561.28 | 07-SEP-15:00 |
HeatRejection:EnergyTransfer | 3600.15 | 0.00 | 01-JAN-00:10 | 2435965.83 | 07-SEP-15:00 |
General:HeatRejection:EnergyTransfer | 3600.15 | 0.00 | 01-JAN-00:10 | 2435965.83 | 07-SEP-15:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:16
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 2.950 | -617.041 | 0.000 | 0.000 | 93.445 | 177.742 | 424.397 | 0.000 | 0.000 | 0.000 | 0.003 | 0.000 | 0.000 | 0.000 | 0.000 | -81.493 |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -564.110 | 0.000 | 0.000 | 83.659 | 159.625 | 321.286 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -0.459 |
CORE_MID | 0.000 | 0.000 | 9.144 | -3920.662 | 0.000 | 0.000 | 856.335 | 1596.246 | 3212.845 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -1753.908 |
CORE_TOP | 0.000 | 0.000 | 23.621 | -328.297 | 0.000 | 0.000 | 89.363 | 159.625 | 321.285 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -265.597 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 3.489 | -56.621 | 0.000 | 0.000 | 10.996 | 13.922 | 40.342 | 22.543 | 0.000 | 0.087 | 37.848 | 0.000 | -62.258 | 0.000 | -10.349 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 2.544 | -58.143 | 0.000 | 0.000 | 7.132 | 8.923 | 25.998 | 52.391 | 0.000 | 0.058 | 6.115 | 0.000 | -38.193 | 0.000 | -6.826 | -0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 3.506 | -97.164 | 0.000 | 0.000 | 10.907 | 13.785 | 40.343 | 113.654 | 0.000 | 0.083 | 0.002 | 0.000 | -56.680 | 0.000 | -10.425 | -18.008 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.745 | -88.156 | 0.000 | 0.000 | 6.964 | 8.937 | 25.998 | 49.010 | 0.000 | 0.054 | 47.573 | 0.000 | -43.673 | 0.000 | -7.452 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 212.832 | -357.189 | 0.000 | 0.000 | 115.452 | 139.357 | 403.423 | 236.587 | 0.000 | 2.069 | 31.657 | 0.000 | -569.092 | 0.000 | -215.096 | -0.005 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 125.866 | -466.299 | 0.000 | 0.000 | 54.257 | 89.255 | 259.981 | 527.305 | 0.000 | 1.310 | 0.002 | 0.000 | -358.946 | 0.000 | -146.473 | -86.257 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 124.938 | -816.444 | 0.000 | 0.000 | 111.442 | 137.924 | 403.429 | 1135.255 | 0.000 | 1.876 | 0.011 | 0.000 | -547.512 | 0.000 | -230.428 | -320.480 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 99.977 | -484.618 | 0.000 | 0.000 | 74.241 | 89.398 | 259.979 | 502.558 | 0.000 | 1.296 | 0.021 | 0.000 | -386.298 | 0.000 | -150.131 | -6.403 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 50.871 | -32.347 | 0.000 | 0.000 | 11.790 | 13.936 | 40.342 | 24.391 | 0.000 | 0.254 | 0.000 | 0.000 | -53.780 | 0.000 | -25.108 | -30.348 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 29.207 | -42.284 | 0.000 | 0.000 | 7.463 | 8.926 | 25.998 | 53.214 | 0.000 | 0.155 | 0.001 | 0.000 | -34.113 | 0.000 | -17.186 | -31.381 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 33.390 | -72.480 | 0.000 | 0.000 | 11.381 | 13.793 | 40.343 | 114.370 | 0.000 | 0.225 | 0.002 | 0.000 | -51.748 | 0.000 | -26.808 | -62.465 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 24.307 | -44.244 | 0.000 | 0.000 | 7.546 | 8.940 | 25.998 | 50.603 | 0.000 | 0.157 | 0.000 | 0.000 | -36.823 | 0.000 | -17.659 | -18.825 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.089 | -134.956 | 0.000 | 0.000 | 0.950 | 4.640 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -24.603 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 6.489 | -1138.634 | 0.000 | 0.000 | 9.525 | 46.396 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -462.582 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 1.157 | -101.588 | 0.000 | 0.000 | 0.958 | 4.640 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -59.048 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | 0.000 | 0.000 | -7139.168 | 0.000 | 0.000 | 20.222 | 50.116 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -426.027 |
GROUNDFLOOR_PLENUM | 6.528 | -43.064 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.159 | 58.358 | 0.000 | 0.000 | 0.000 | -21.981 | 0.000 |
MIDFLOOR_PLENUM | 178.294 | -259.399 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 2.937 | 447.306 | 0.000 | 0.000 | 0.000 | -369.136 | -0.025 |
TOPFLOOR_PLENUM | 73.033 | -42.195 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.256 | 7.462 | 0.000 | 0.000 | 0.000 | -38.556 | -0.007 |
Total Facility | 257.855 | -344.658 | 755.124 | -16560.443 | 0.000 | 0.000 | 1584.029 | 2746.123 | 15213.411 | 2881.881 | 0.000 | 10.976 | 636.362 | 0.000 | -2239.115 | 0.000 | -1293.614 | -3647.925 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 10-OCT-03:01 | 0.00 | 0.00 | 0.00 | -106472.31 | 0.00 | 0.00 | 0.00 | 862.23 | 13457.54 | 0.00 | 0.00 | 0.00 | 92152.54 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 11-SEP-03:02 | 0.00 | 0.00 | 0.00 | -89355.27 | 0.00 | 0.00 | 0.00 | 774.34 | 8057.15 | 0.00 | 0.00 | 0.00 | 80523.78 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 14-AUG-03:02 | 0.00 | 0.00 | 0.00 | -802895.53 | 0.00 | 0.00 | 0.00 | 7743.41 | 80571.20 | 0.00 | 0.00 | 0.00 | 714580.93 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 21-JUN-03:02 | 0.00 | 0.00 | 0.00 | -77783.19 | 0.00 | 0.00 | 0.00 | 774.34 | 8057.12 | 0.00 | 0.00 | 0.00 | 68951.73 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 16-JUL-18:31 | 0.00 | 0.00 | 0.00 | -15275.74 | 0.00 | 0.00 | 0.00 | 59.73 | 758.77 | 5908.21 | 0.00 | 95.68 | 8453.35 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 25-JUN-07:52 | 0.00 | 0.00 | 0.00 | -20891.22 | 0.00 | 0.00 | 22.56 | 38.49 | 488.98 | 15849.15 | 0.00 | 0.00 | 4628.53 | 0.00 | -0.00 | 0.00 | -136.49 | 0.00 |
PERIMETER_BOT_ZN_1 | 15-OCT-12:31 | 0.00 | 0.00 | 0.00 | -27766.68 | 0.00 | 0.00 | 33.00 | 59.73 | 758.78 | 29217.46 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -421.92 | -1880.37 |
PERIMETER_BOT_ZN_4 | 28-MAY-17:41 | 0.00 | 0.00 | 0.00 | -27672.91 | 0.00 | 0.00 | 0.00 | 38.49 | 488.98 | 17718.99 | 0.00 | 0.00 | 9762.99 | 0.00 | -0.00 | 0.00 | -336.54 | 0.00 |
PERIMETER_MID_ZN_3 | 16-JUL-19:01 | 0.00 | 0.00 | 0.00 | -144686.90 | 0.00 | 0.00 | 0.00 | 597.26 | 7587.73 | 32537.67 | 0.00 | 1918.69 | 102045.55 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 06-AUG-09:21 | 0.00 | 0.00 | 0.00 | -245581.92 | 0.00 | 0.00 | 179.42 | 384.90 | 4889.82 | 164004.72 | 0.00 | 0.00 | 76560.64 | 0.00 | -0.00 | 0.00 | -437.56 | 0.00 |
PERIMETER_MID_ZN_1 | 03-SEP-14:11 | 0.00 | 0.00 | 0.00 | -281274.47 | 0.00 | 0.00 | 305.32 | 597.27 | 7587.84 | 125486.28 | 0.00 | 3545.65 | 143752.10 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 16-JUL-17:01 | 0.00 | 0.00 | 0.00 | -269482.22 | 0.00 | 0.00 | 0.00 | 384.90 | 4889.79 | 186860.18 | 0.00 | 677.04 | 76670.30 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 06-AUG-16:11 | 0.00 | 0.00 | 0.00 | -19642.64 | 0.00 | 0.00 | 40.55 | 59.73 | 758.77 | 3760.06 | 0.00 | 718.01 | 14305.52 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 06-AUG-08:11 | 0.00 | 0.00 | 0.00 | -23935.42 | 0.00 | 0.00 | 19.39 | 38.49 | 488.98 | 18989.48 | 0.00 | 0.00 | 4554.31 | 0.00 | -0.00 | 0.00 | -155.24 | 0.00 |
PERIMETER_TOP_ZN_1 | 04-SEP-15:01 | 0.00 | 0.00 | 0.00 | -30694.47 | 0.00 | 0.00 | 29.64 | 59.73 | 758.78 | 16209.04 | 0.00 | 193.90 | 13443.37 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 06-AUG-16:11 | 0.00 | 0.00 | 0.00 | -28386.51 | 0.00 | 0.00 | 15.97 | 38.49 | 488.98 | 16838.36 | 0.00 | 322.28 | 10682.43 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 22-APR-18:10 | 0.00 | 0.00 | 0.00 | -8240.93 | 0.00 | 0.00 | 0.00 | 22.51 | 7794.42 | 0.00 | 0.00 | 0.00 | 424.00 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 03-AUG-18:50 | 0.00 | 0.00 | 0.00 | -78140.73 | 0.00 | 0.00 | 105.15 | 1350.33 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1258.97 |
DATACENTER_TOP_ZN_6 | 03-AUG-18:40 | 0.00 | 0.00 | 0.00 | -7928.17 | 0.00 | 0.00 | 10.62 | 135.03 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -11.90 |
DATACENTER_BASEMENT_ZN_6 | 22-AUG-07:20 | 0.00 | 0.00 | 0.00 | -368996.85 | 0.00 | 0.00 | 2177.29 | 4375.82 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -17188.78 |
GROUNDFLOOR_PLENUM | 07-AUG-05:15 | 0.00 | -12936.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13029.27 | 0.00 | -0.00 | 0.00 | -93.25 | 0.00 |
MIDFLOOR_PLENUM | 04-MAR-04:01 | 0.00 | -110232.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141775.85 | 0.00 | -0.00 | 0.00 | -31542.95 | 0.00 |
TOPFLOOR_PLENUM | 17-JUL-15:10 | 0.00 | -22086.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.62 | 22035.11 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 07-AUG-05:02 | 0.00 | -46909.11 | 0.00 | -1899154.73 | 0.00 | 0.00 | 15748.74 | 29009.37 | 623236.89 | 0.00 | 0.00 | 0.00 | 1347036.95 | 0.00 | -63161.24 | 0.00 | -5806.86 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 05-AUG-16:01 | 0.00 | 0.00 | 23062.75 | 0.00 | 0.00 | 0.00 | 520.12 | 862.23 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -37902.65 |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 09-JAN-05:11 | 0.00 | 0.00 | 535766.83 | 0.00 | 0.00 | 0.00 | 0.00 | 15486.81 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -631824.84 |
CORE_TOP | 09-JAN-04:01 | 0.00 | 0.00 | 76166.79 | 0.00 | 0.00 | 0.00 | 0.00 | 774.34 | 8057.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -84998.25 |
PERIMETER_BOT_ZN_3 | 30-JAN-04:01 | 0.00 | 0.00 | 13205.08 | 0.00 | 0.00 | 0.00 | 0.00 | 97.23 | 1011.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5254.84 | 0.00 | -1412.17 | -7646.99 |
PERIMETER_BOT_ZN_2 | 30-JAN-04:01 | 0.00 | 0.00 | 15385.94 | 0.00 | 0.00 | 0.00 | 0.00 | 62.66 | 651.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3499.42 | 0.00 | -948.96 | -11652.19 |
PERIMETER_BOT_ZN_1 | 11-JAN-04:01 | 0.00 | 0.00 | 20950.23 | 0.00 | 0.00 | 0.00 | 0.00 | 97.23 | 1011.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -6898.67 | 0.00 | -959.94 | -14200.56 |
PERIMETER_BOT_ZN_4 | 09-JAN-04:01 | 0.00 | 0.00 | 14297.75 | 0.00 | 0.00 | 0.00 | 0.00 | 62.66 | 651.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4375.04 | 0.00 | -575.90 | -10061.44 |
PERIMETER_MID_ZN_3 | 09-JAN-05:51 | 0.00 | 0.00 | 134038.39 | 0.00 | 0.00 | 0.00 | 0.00 | 1944.52 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -63813.11 | 0.00 | -18860.95 | -63425.83 |
PERIMETER_MID_ZN_2 | 09-JAN-02:31 | 0.00 | 0.00 | 185504.38 | 0.00 | 0.00 | 0.00 | 0.00 | 626.56 | 6519.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -42086.54 | 0.00 | -17689.06 | -132875.09 |
PERIMETER_MID_ZN_1 | 09-JAN-02:31 | 0.00 | 0.00 | 223413.55 | 0.00 | 0.00 | 0.00 | 0.00 | 972.28 | 10117.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -61506.89 | 0.00 | -26527.03 | -146469.04 |
PERIMETER_MID_ZN_4 | 09-JAN-02:31 | 0.00 | 0.00 | 197293.15 | 0.00 | 0.00 | 0.00 | 0.00 | 626.56 | 6519.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -41101.76 | 0.00 | -17807.51 | -145530.16 |
PERIMETER_TOP_ZN_3 | 30-JAN-06:01 | 0.00 | 0.00 | 18844.80 | 0.00 | 0.00 | 0.00 | 186.96 | 194.45 | 1011.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4547.22 | 0.00 | -965.84 | -14724.86 |
PERIMETER_TOP_ZN_2 | 11-JAN-04:11 | 0.00 | 0.00 | 19728.83 | 0.00 | 0.00 | 0.00 | 0.00 | 62.66 | 651.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4400.30 | 0.00 | -1587.98 | -14455.18 |
PERIMETER_TOP_ZN_1 | 11-JAN-04:11 | 0.00 | 0.00 | 25571.73 | 0.00 | 0.00 | 0.00 | 0.00 | 97.23 | 1011.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -6620.97 | 0.00 | -2381.92 | -17677.78 |
PERIMETER_TOP_ZN_4 | 11-JAN-04:11 | 0.00 | 0.00 | 22328.66 | 0.00 | 0.00 | 0.00 | 0.00 | 62.66 | 651.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4300.16 | 0.00 | -1600.75 | -17142.39 |
DATACENTER_BOT_ZN_6 | 09-JAN-03:03 | 0.00 | 0.00 | 632.16 | 0.00 | 0.00 | 0.00 | 0.00 | 22.51 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2603.27 |
DATACENTER_MID_ZN_6 | 29-JAN-17:50 | 0.00 | 0.00 | 6652.65 | 0.00 | 0.00 | 0.00 | 54.26 | 225.07 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -26418.04 |
DATACENTER_TOP_ZN_6 | 30-APR-23:05 | 0.00 | 0.00 | 778.87 | 0.00 | 0.00 | 0.00 | 0.00 | 22.51 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2749.99 |
DATACENTER_BASEMENT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 19-DEC-06:01 | 14687.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -421.30 | -14266.20 |
MIDFLOOR_PLENUM | 09-JAN-06:12 | 144801.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -8379.71 | -136421.85 |
TOPFLOOR_PLENUM | 11-JAN-05:11 | 34216.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1468.82 | -32747.52 |
Total Facility | 30-JAN-06:01 | -1207.09 | 96550.60 | 1425254.33 | -96550.60 | 0.00 | 0.00 | 22512.57 | 29009.37 | 268362.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -203806.35 | 0.00 | -49765.64 | -1490359.87 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:16
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 12.0092 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 10.3471 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 114.8950 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 95.6468 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 11.9096 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 10.7985 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 5.9837 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 5.9837 | 0.2006 | 1.0000 | Not calculated | 1.2002 | 0.2006 | ||
AIRLOOP DATACENTER BASEMENT | 24.3931 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 24.3934 | 0.0139 | 1.0000 | Not calculated | 0.3384 | 0.0139 | ||
AIRLOOP DATACENTER BOT | 0.5622 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5622 | 0.0278 | 1.0000 | Not calculated | 0.0156 | 0.0278 | ||
AIRLOOP DATACENTER MID | 5.3843 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 5.3843 | 0.0290 | 1.0000 | Not calculated | 0.1563 | 0.0290 | ||
AIRLOOP DATACENTER TOP | 0.5484 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5484 | 0.0285 | 1.0000 | Not calculated | 0.0156 | 0.0285 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 6.0046 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 3.1322 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 57.4475 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 30.7695 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 5.9548 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 3.2352 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 5.9837 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 5.9837 | 1.0000 | 1.0000 | Not calculated | 1.2002 | 0.2006 | ||
AIRLOOP DATACENTER BASEMENT | 24.3931 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 24.3931 | 1.0000 | 1.0000 | Not calculated | 0.3384 | 0.0139 | ||
AIRLOOP DATACENTER BOT | 0.5622 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5622 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0278 | ||
AIRLOOP DATACENTER MID | 5.3843 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 5.3843 | 1.0000 | 1.0000 | Not calculated | 0.1563 | 0.0290 | ||
AIRLOOP DATACENTER TOP | 0.5484 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5484 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0285 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.000000 | 149.6021 | 0.000432 | 2779.43 | 1.2002 | 1.0000 | 1.2002 | 1.000 | 1.2002 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.000000 | 19.4861 | 0.000432 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.1814 | 0.000432 | 783.68 | 0.3384 | 1.0000 | 0.3384 | 1.000 | 0.3384 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
CAV_BAS | 0.000000 | 149.60 | 0.000432 | 2779.4266 | 1.2002 | 1.2002 | 1.2002 |
AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.18 | 0.000432 | 783.6794 | 0.3384 | 0.3384 | 0.3384 |
AIRLOOP DATACENTER BOT | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AIRLOOP DATACENTER MID | 0.000000 | 19.49 | 0.000432 | 362.0274 | 0.1563 | 0.1563 | 0.1563 |
AIRLOOP DATACENTER TOP | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.9837 | 5.9837 | 5.9837 | No | 1.2002 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.3893 | 6.3893 | 1.9679 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 59.9336 | 59.9336 | 19.2986 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.8650 | 5.8650 | 1.9941 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0328 | 1.0328 | 0.2468 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3050 | 1.3050 | 0.2610 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6452 | 1.6452 | 0.3290 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6369 | 1.6369 | 0.3274 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 9.7674 | 9.7674 | 2.4321 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 13.7713 | 13.7713 | 2.7543 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 16.5822 | 16.5822 | 3.3164 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 14.8404 | 14.8404 | 2.9681 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2866 | 1.2866 | 0.2895 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3814 | 1.3814 | 0.2763 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7938 | 1.7938 | 0.3588 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5827 | 1.5827 | 0.3165 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5622 | 0.5622 | 0.5622 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.3843 | 5.3843 | 5.3843 | No | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5484 | 0.5484 | 0.5484 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 24.3931 | 24.3931 | 24.3931 | No | 0.3384 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 12.0092 | 10.3471 | 12.0092 | 3.1322 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 114.8950 | 95.6468 | 114.8950 | 30.7695 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 11.9096 | 10.7985 | 11.9096 | 3.2352 | 0.0000 | 1.0000 |
CAV_BAS | 5.9837 | 5.9837 | 5.9837 | 5.9837 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 24.3931 | 24.3934 | 24.3931 | 24.3931 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.5622 | 0.5622 | 0.5622 | 0.5622 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 5.3843 | 5.3843 | 5.3843 | 5.3843 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.5484 | 0.5484 | 0.5484 | 0.5484 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.9837 | 5.9837 | 5.9837 | No | 1.2002 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.1946 | 3.1946 | 1.9679 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 29.9668 | 29.9668 | 19.2986 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.9325 | 2.9325 | 1.9941 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5164 | 0.5164 | 0.2468 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6525 | 0.6525 | 0.2610 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8226 | 0.8226 | 0.3290 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8185 | 0.8185 | 0.3274 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.8837 | 4.8837 | 2.4321 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.8857 | 6.8857 | 2.7543 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 8.2911 | 8.2911 | 3.3164 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 7.4202 | 7.4202 | 2.9681 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6433 | 0.6433 | 0.2895 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6907 | 0.6907 | 0.2763 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8969 | 0.8969 | 0.3588 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7913 | 0.7913 | 0.3165 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5622 | 0.5622 | 0.5622 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.3843 | 5.3843 | 5.3843 | No | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5484 | 0.5484 | 0.5484 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 24.3931 | 24.3931 | 24.3931 | No | 0.3384 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 6.0046 | 3.1322 | 3.1322 | 3.1322 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 57.4475 | 30.7695 | 30.7695 | 30.7695 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 5.9548 | 3.2352 | 3.2352 | 3.2352 | 0.0000 | 1.0000 |
CAV_BAS | 5.9837 | 5.9837 | 5.9837 | 5.9837 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 24.3931 | 24.3931 | 24.3931 | 24.3931 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.5622 | 0.5622 | 0.5622 | 0.5622 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 5.3843 | 5.3843 | 5.3843 | 5.3843 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.5484 | 0.5484 | 0.5484 | 0.5484 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:16
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Great Falls Intl Arpt MT USA TMY3 WMO#=727750 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 113.98 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 121.67 |
Number of hours cooling loads not met | 514.00 |
Number of hours not met | 635.67 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 3494.03 | 2355196.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 3166.61 | 414820.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 2746.12 | 261074.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 447.85 | 37611.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5871.99 | 320838.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 59.77 | 3726.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 1848.78 | 113101.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 5.83 | 376.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 2550.45 | 308014.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 381.79 | 54235.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 809.21 | 80284.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- General | 841.32 | 51932.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 771.58 | 85533.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 15213.41 | 28071.14 |
Natural Gas | 0.00 | 4265.61 |
Additional | 0.00 | 0.00 |
Total | 15213.41 | 32336.76 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 59.29 |
Space Heating | 0.00 |
Space Cooling | 68.36 |
Fans (All) | 55.06 |
Service Water Heating | 0.00 |
Receptacle Equipment | 328.44 |
Miscellaneous (All) | 606.02 |
Subtotal | 606.02 |
Natural Gas [MJ/m2] | |
Space Heating | 75.43 |
Service Water Heating | 16.66 |
Miscellaneous (All) | 92.09 |
Subtotal | 92.09 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 8.49 |
Space Heating | 10.81 |
Space Cooling | 9.79 |
Fans (All) | 7.89 |
Service Water Heating | 2.39 |
Receptacle Equipment | 47.05 |
Miscellaneous | 13.59 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2393. | 8760. |
LTG_SCH_DATACENTER | 2921. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4487. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 1565. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:16
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8716.67 | 43.33 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8756.33 | 3.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8758.50 | 1.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8742.17 | 17.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8741.50 | 18.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8689.67 | 70.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8758.83 | 1.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8737.83 | 22.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8740.83 | 19.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8736.00 | 24.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8758.33 | 1.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8738.83 | 21.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8742.67 | 17.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8736.33 | 23.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 8740.00 | 20.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 8752.67 | 7.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 8752.33 | 7.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 8173.17 | 586.83 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8735.83 | 24.17 | 0.00 | 0.00 | 0.00 |
Min | 8173.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 586.83 | 0.00 | 0.00 | 0.00 |
Average | 8719.50 | 40.50 | 0.00 | 0.00 | 0.00 |
Sum | 200548.50 | 931.50 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 368466.67 | 149.33 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330796.00 | 17.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 2264.17 | 3.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2268.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 2268.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 95325.17 | 8069.83 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 368466.67 | 8069.83 | 0.00 | 0.00 | 0.00 |
Average | 79976.65 | 358.26 | 0.00 | 0.00 | 0.00 |
Sum | 1839463.00 | 8240.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8681.00 | 79.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8727.83 | 32.17 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8690.83 | 69.17 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8736.00 | 24.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8747.67 | 12.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8746.00 | 14.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8740.67 | 19.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8703.67 | 56.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8751.17 | 8.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8739.50 | 20.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8739.83 | 20.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8732.50 | 27.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8750.83 | 9.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8740.17 | 19.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8741.00 | 19.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8733.50 | 26.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 8370.33 | 389.67 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8745.00 | 15.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8752.67 | 7.33 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8720.33 | 39.67 | 0.00 | 0.00 | 0.00 |
Min | 8370.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 389.67 | 0.00 | 0.00 | 0.00 |
Average | 8720.46 | 39.54 | 0.00 | 0.00 | 0.00 |
Sum | 200570.50 | 909.50 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 368338.17 | 277.83 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330740.00 | 73.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330638.00 | 175.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330759.00 | 54.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 2268.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2268.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 2268.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 97856.33 | 5538.67 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 368338.17 | 5538.67 | 0.00 | 0.00 | 0.00 |
Average | 80068.89 | 266.02 | 0.00 | 0.00 | 0.00 |
Sum | 1841584.50 | 6118.50 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:16
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:16
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 4570.43 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 18354.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 38925.00 | 0.00 |
Average | 0.00 | 0.00 | 16367.35 | 0.00 |
Sum | 0.00 | 0.00 | 376449.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018
For: Environment
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Environment
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6B
For: Environment
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MT_GREATFALLS
For: Environment
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.450503E+11 | 101597.79 | 02-JAN-04:03 | -0.5 | -3.0 | 0.523325E+10 | 7499.18 | 13-JAN-14:20 | 8.53 | 4.10 |
February | 0.397503E+11 | 103033.50 | 21-FEB-04:01 | 6.88 | 1.33 | 0.495847E+10 | 7499.19 | 07-FEB-10:20 | 6.88 | 1.33 |
March | 0.489255E+11 | 101112.59 | 20-MAR-03:01 | -1.6 | -3.4 | 0.610505E+10 | 7499.15 | 07-MAR-10:09 | -1.6 | -3.4 |
April | 0.472725E+11 | 100898.03 | 10-APR-03:02 | 4.40 | 0.24 | 0.544436E+10 | 7499.13 | 04-APR-09:09 | 4.40 | 0.24 |
May | 0.498323E+11 | 103694.71 | 30-MAY-03:02 | 15.60 | 10.52 | 0.589859E+10 | 7499.76 | 02-MAY-13:20 | 15.60 | 10.52 |
June | 0.543058E+11 | 103066.51 | 05-JUN-03:02 | 8.62 | 5.44 | 0.587987E+10 | 7499.13 | 20-JUN-13:20 | 27.77 | 18.21 |
July | 0.568174E+11 | 102303.48 | 05-JUL-03:02 | 9.90 | 9.28 | 0.547254E+10 | 7499.21 | 03-JUL-13:09 | 9.90 | 9.28 |
August | 0.635000E+11 | 102341.04 | 07-AUG-03:02 | 20.60 | 11.11 | 0.613715E+10 | 7499.05 | 01-AUG-13:20 | 20.60 | 11.11 |
September | 0.546222E+11 | 102833.74 | 25-SEP-03:02 | 13.22 | 9.31 | 0.545136E+10 | 7499.34 | 07-SEP-09:00 | 13.22 | 9.31 |
October | 0.559646E+11 | 106478.99 | 10-OCT-03:01 | -4.1 | -4.8 | 0.566914E+10 | 7499.08 | 06-OCT-09:00 | -4.1 | -4.8 |
November | 0.514179E+11 | 104856.08 | 13-NOV-04:01 | -6.2 | -8.4 | 0.561113E+10 | 7499.05 | 03-NOV-09:09 | -6.2 | -8.4 |
December | 0.495842E+11 | 102150.21 | 04-DEC-04:01 | 1.70 | -1.2 | 0.538130E+10 | 7499.12 | 07-DEC-10:09 | 3.35 | 1.22 |
Annual Sum or Average | 0.617043E+12 | 0.672422E+11 | ||||||||
Minimum of Months | 0.397503E+11 | 100898.03 | -6.2 | -8.4 | 0.495847E+10 | 7499.05 | -6.2 | -8.4 | ||
Maximum of Months | 0.635000E+11 | 106478.99 | 20.60 | 11.11 | 0.613715E+10 | 7499.76 | 27.77 | 18.21 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.287600E+11 | 83711.95 | 02-JAN-05:01 | -0.2 | -2.7 | 0.490078E+10 | 6734.76 | 02-JAN-10:09 | 2.48 | -0.4 |
February | 0.305111E+11 | 82088.25 | 27-FEB-05:01 | 3.98 | -0.3 | 0.455350E+10 | 6734.74 | 28-FEB-10:09 | 1.57 | -0.3 |
March | 0.438750E+11 | 82835.67 | 29-MAR-04:01 | -0.1 | -2.6 | 0.548910E+10 | 6734.77 | 01-MAR-10:09 | -0.1 | -2.6 |
April | 0.488748E+11 | 85312.37 | 10-APR-03:02 | 4.40 | 0.24 | 0.488305E+10 | 6734.78 | 04-APR-09:09 | 4.40 | 0.24 |
May | 0.455545E+11 | 88221.82 | 30-MAY-03:02 | 15.60 | 10.52 | 0.528852E+10 | 6735.16 | 02-MAY-13:09 | 15.60 | 10.52 |
June | 0.565639E+11 | 86301.76 | 12-JUN-03:02 | 12.12 | 11.21 | 0.526905E+10 | 6734.78 | 20-JUN-13:09 | 27.48 | 18.05 |
July | 0.632733E+11 | 89041.91 | 05-JUL-03:02 | 9.90 | 9.28 | 0.489687E+10 | 6734.96 | 03-JUL-13:09 | 9.90 | 9.28 |
August | 0.709891E+11 | 84984.61 | 02-AUG-03:02 | 8.90 | 6.89 | 0.549673E+10 | 6734.78 | 22-AUG-09:09 | 16.88 | 12.48 |
September | 0.489262E+11 | 89355.18 | 11-SEP-03:02 | 11.10 | 10.41 | 0.488174E+10 | 6735.10 | 07-SEP-09:50 | 11.10 | 10.41 |
October | 0.466645E+11 | 84774.97 | 02-OCT-03:02 | 5.00 | 2.94 | 0.507901E+10 | 6734.74 | 27-OCT-09:09 | 7.67 | 3.31 |
November | 0.420311E+11 | 85415.90 | 06-NOV-04:03 | -2.8 | -3.9 | 0.502682E+10 | 6734.74 | 03-NOV-09:09 | -2.8 | -3.9 |
December | 0.380874E+11 | 82253.97 | 07-DEC-05:01 | -1.6 | -2.7 | 0.488421E+10 | 6734.77 | 07-DEC-10:09 | 3.35 | 1.22 |
Annual Sum or Average | 0.564111E+12 | 0.606494E+11 | ||||||||
Minimum of Months | 0.287600E+11 | 82088.25 | -2.8 | -3.9 | 0.455350E+10 | 6734.74 | -2.8 | -3.9 | ||
Maximum of Months | 0.709891E+11 | 89355.18 | 15.60 | 11.21 | 0.549673E+10 | 6735.16 | 27.48 | 18.05 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.208758E+11 | 16910.38 | 05-JAN-17:00 | -20.0 | -20.5 | 0.436077E+10 | 6554.14 | 05-JAN-14:00 | -20.0 | -20.5 |
February | 0.206998E+11 | 28933.85 | 28-FEB-17:00 | 10.00 | 4.31 | 0.419000E+10 | 6734.74 | 28-FEB-10:09 | 10.00 | 4.31 |
March | 0.281437E+11 | 67068.68 | 30-MAR-05:02 | 0.00 | -2.1 | 0.527613E+10 | 6734.76 | 01-MAR-10:09 | 0.00 | -2.1 |
April | 0.304275E+11 | 74704.58 | 07-APR-05:02 | 12.20 | 5.15 | 0.482493E+10 | 6734.76 | 04-APR-09:09 | 12.20 | 5.15 |
May | 0.345326E+11 | 75262.41 | 26-MAY-05:02 | 9.50 | 7.94 | 0.524209E+10 | 6735.18 | 02-MAY-13:09 | 9.50 | 7.94 |
June | 0.441459E+11 | 76814.21 | 13-JUN-05:02 | 13.30 | 12.25 | 0.525954E+10 | 6734.81 | 20-JUN-13:09 | 27.48 | 18.05 |
July | 0.465548E+11 | 76546.02 | 13-JUL-04:03 | 12.02 | 8.52 | 0.489244E+10 | 6734.95 | 03-JUL-13:09 | 12.02 | 8.52 |
August | 0.482273E+11 | 80284.65 | 14-AUG-03:02 | 12.20 | 10.20 | 0.549461E+10 | 6734.78 | 01-AUG-13:09 | 12.20 | 10.20 |
September | 0.385719E+11 | 79490.17 | 11-SEP-03:02 | 11.10 | 10.41 | 0.486361E+10 | 6735.12 | 07-SEP-09:00 | 11.10 | 10.41 |
October | 0.316208E+11 | 73185.96 | 17-OCT-05:02 | 3.90 | 1.71 | 0.502494E+10 | 6734.74 | 27-OCT-09:09 | 7.67 | 3.31 |
November | 0.255470E+11 | 68100.19 | 04-NOV-05:02 | 9.43 | 5.60 | 0.481512E+10 | 6734.75 | 03-NOV-09:09 | 9.43 | 5.60 |
December | 0.227207E+11 | 23661.17 | 07-DEC-16:30 | 5.55 | 1.71 | 0.443078E+10 | 6734.49 | 14-DEC-14:09 | 3.40 | -0.7 |
Annual Sum or Average | 0.392068E+12 | 0.586750E+11 | ||||||||
Minimum of Months | 0.206998E+11 | 16910.38 | -20.0 | -20.5 | 0.419000E+10 | 6554.14 | -20.0 | -20.5 | ||
Maximum of Months | 0.482273E+11 | 80284.65 | 13.30 | 12.25 | 0.549461E+10 | 6735.18 | 27.48 | 18.05 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.118848E+11 | 16120.89 | 13-JAN-17:00 | 7.80 | 3.93 | 0.387690E+10 | 5994.68 | 13-JAN-14:00 | 7.80 | 3.93 |
February | 0.144758E+11 | 20388.65 | 28-FEB-17:00 | 10.00 | 4.31 | 0.370994E+10 | 6596.35 | 28-FEB-14:00 | 10.00 | 4.31 |
March | 0.204160E+11 | 23589.59 | 23-MAR-16:00 | 7.20 | 0.71 | 0.473387E+10 | 6734.35 | 23-MAR-13:00 | 7.20 | 0.71 |
April | 0.237550E+11 | 43394.79 | 07-APR-05:02 | 12.20 | 5.15 | 0.451710E+10 | 6734.59 | 13-APR-13:00 | 13.30 | 7.60 |
May | 0.301490E+11 | 73104.27 | 20-MAY-05:02 | 11.47 | 8.41 | 0.501148E+10 | 6735.18 | 02-MAY-13:09 | 11.47 | 8.41 |
June | 0.432464E+11 | 77817.29 | 21-JUN-03:02 | 19.22 | 13.03 | 0.523083E+10 | 6734.76 | 20-JUN-13:09 | 19.22 | 13.03 |
July | 0.480746E+11 | 76100.91 | 20-JUL-04:03 | 20.40 | 14.09 | 0.488341E+10 | 6734.95 | 03-JUL-13:09 | 20.40 | 14.09 |
August | 0.473033E+11 | 75519.85 | 07-AUG-03:02 | 20.60 | 11.11 | 0.547622E+10 | 6734.77 | 01-AUG-13:09 | 20.60 | 11.11 |
September | 0.337182E+11 | 77170.41 | 05-SEP-03:02 | 18.30 | 12.34 | 0.473328E+10 | 6735.07 | 07-SEP-09:00 | 16.70 | 15.61 |
October | 0.235241E+11 | 38021.07 | 19-OCT-05:03 | 12.20 | 5.54 | 0.466670E+10 | 6734.69 | 20-OCT-09:39 | 8.53 | 4.35 |
November | 0.178082E+11 | 21702.67 | 03-NOV-16:00 | 14.30 | 7.69 | 0.422924E+10 | 6724.90 | 08-NOV-14:00 | 13.20 | 7.65 |
December | 0.139444E+11 | 17190.00 | 06-DEC-17:00 | 6.70 | 2.38 | 0.387613E+10 | 6403.24 | 07-DEC-14:00 | 8.30 | 2.55 |
Annual Sum or Average | 0.328300E+12 | 0.549451E+11 | ||||||||
Minimum of Months | 0.118848E+11 | 16120.89 | 6.70 | 0.71 | 0.370994E+10 | 5994.68 | 7.20 | 0.71 | ||
Maximum of Months | 0.480746E+11 | 77817.29 | 20.60 | 14.09 | 0.547622E+10 | 6735.18 | 20.60 | 15.61 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.107131E+10 | 2443.81 | 02-JAN-05:01 | -0.2 | -2.7 | 0.492170E+09 | 801.07 | 02-JAN-14:50 | 6.20 | 1.19 |
February | 0.170314E+10 | 3744.49 | 27-FEB-16:00 | 18.90 | 7.06 | 0.481060E+09 | 845.60 | 21-FEB-14:00 | 18.90 | 7.06 |
March | 0.299095E+10 | 4159.15 | 27-MAR-14:40 | 9.63 | 2.75 | 0.633059E+09 | 845.61 | 21-MAR-13:00 | 9.63 | 2.75 |
April | 0.424968E+10 | 6570.48 | 07-APR-14:30 | 22.50 | 9.29 | 0.594926E+09 | 845.62 | 13-APR-13:00 | 13.30 | 7.60 |
May | 0.490369E+10 | 11031.87 | 30-MAY-05:03 | 15.60 | 11.34 | 0.647882E+09 | 845.68 | 02-MAY-13:09 | 15.60 | 11.34 |
June | 0.816655E+10 | 12304.40 | 26-JUN-05:02 | 9.87 | 8.82 | 0.660045E+09 | 845.64 | 20-JUN-13:09 | 9.87 | 8.82 |
July | 0.994237E+10 | 15276.03 | 16-JUL-18:31 | 32.40 | 17.11 | 0.615200E+09 | 846.51 | 18-JUL-13:20 | 33.17 | 17.33 |
August | 0.983364E+10 | 15075.48 | 06-AUG-15:41 | 35.40 | 16.19 | 0.689722E+09 | 845.64 | 01-AUG-13:09 | 35.40 | 16.19 |
September | 0.530737E+10 | 11971.78 | 05-SEP-05:02 | 18.40 | 11.40 | 0.603894E+09 | 845.67 | 07-SEP-09:50 | 16.52 | 15.26 |
October | 0.379329E+10 | 5461.61 | 19-OCT-14:30 | 21.40 | 10.24 | 0.615119E+09 | 845.62 | 18-OCT-13:30 | 21.40 | 10.24 |
November | 0.271468E+10 | 3744.19 | 24-NOV-14:30 | 14.90 | 6.43 | 0.572541E+09 | 845.62 | 16-NOV-14:09 | 14.90 | 6.43 |
December | 0.194428E+10 | 2448.33 | 06-DEC-05:01 | 7.20 | 4.06 | 0.517951E+09 | 845.60 | 06-DEC-14:00 | 11.10 | 5.34 |
Annual Sum or Average | 0.566209E+11 | 0.712357E+10 | ||||||||
Minimum of Months | 0.107131E+10 | 2443.81 | -0.2 | -2.7 | 0.481060E+09 | 801.07 | 6.20 | 1.19 | ||
Maximum of Months | 0.994237E+10 | 15276.03 | 35.40 | 17.11 | 0.689722E+09 | 846.51 | 35.40 | 17.33 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.105770E+10 | 2569.45 | 02-JAN-05:01 | -0.2 | -2.7 | 0.316895E+09 | 541.07 | 17-JAN-10:39 | 5.53 | 1.42 |
February | 0.182061E+10 | 6341.40 | 27-FEB-09:55 | 11.70 | 4.23 | 0.312633E+09 | 544.95 | 28-FEB-10:09 | 1.57 | -0.3 |
March | 0.329423E+10 | 8912.60 | 28-MAR-09:15 | 5.73 | 0.86 | 0.402593E+09 | 544.95 | 06-MAR-10:20 | 5.73 | 0.86 |
April | 0.464659E+10 | 16620.57 | 16-APR-08:43 | 11.83 | 5.16 | 0.374042E+09 | 544.95 | 25-APR-09:09 | 9.87 | 4.86 |
May | 0.550067E+10 | 11398.95 | 19-MAY-08:30 | 16.95 | 11.09 | 0.415135E+09 | 544.99 | 02-MAY-13:09 | 16.95 | 11.09 |
June | 0.832253E+10 | 20898.80 | 25-JUN-07:52 | 15.60 | 11.35 | 0.424111E+09 | 546.27 | 23-JUN-09:50 | 15.60 | 11.35 |
July | 0.101177E+11 | 20438.38 | 02-JUL-08:32 | 21.67 | 15.15 | 0.396407E+09 | 546.32 | 03-JUL-09:00 | 23.30 | 14.49 |
August | 0.961162E+10 | 20548.08 | 06-AUG-08:22 | 25.25 | 14.09 | 0.442935E+09 | 546.19 | 01-AUG-09:09 | 25.25 | 14.09 |
September | 0.564518E+10 | 18422.35 | 04-SEP-08:32 | 26.33 | 14.69 | 0.387513E+09 | 544.98 | 07-SEP-09:50 | 16.52 | 15.26 |
October | 0.392951E+10 | 8558.68 | 18-OCT-09:20 | 18.13 | 8.00 | 0.393220E+09 | 544.95 | 18-OCT-13:30 | 24.70 | 11.11 |
November | 0.255460E+10 | 5857.14 | 06-NOV-09:35 | 1.20 | -1.1 | 0.358527E+09 | 544.95 | 03-NOV-09:09 | 1.20 | -1.1 |
December | 0.164154E+10 | 2423.92 | 20-DEC-10:20 | 3.67 | -0.4 | 0.321149E+09 | 544.93 | 20-DEC-10:30 | 3.85 | -0.4 |
Annual Sum or Average | 0.581425E+11 | 0.454516E+10 | ||||||||
Minimum of Months | 0.105770E+10 | 2423.92 | -0.2 | -2.7 | 0.312633E+09 | 541.07 | 1.20 | -1.1 | ||
Maximum of Months | 0.101177E+11 | 20898.80 | 26.33 | 15.15 | 0.442935E+09 | 546.32 | 25.25 | 15.26 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.253283E+10 | 11207.84 | 02-JAN-13:30 | 6.70 | 1.68 | 0.527267E+09 | 845.64 | 13-JAN-14:20 | 8.53 | 4.10 |
February | 0.464096E+10 | 25036.28 | 26-FEB-13:32 | 15.40 | 5.68 | 0.520984E+09 | 847.26 | 27-FEB-14:39 | 18.70 | 7.17 |
March | 0.670303E+10 | 18390.37 | 01-MAR-13:40 | 6.33 | 2.52 | 0.638179E+09 | 847.96 | 23-MAR-13:00 | 10.00 | 2.51 |
April | 0.725245E+10 | 24636.24 | 16-APR-13:23 | 18.85 | 8.05 | 0.582970E+09 | 846.34 | 24-APR-13:00 | 17.80 | 9.82 |
May | 0.731695E+10 | 14564.14 | 19-MAY-13:30 | 26.65 | 14.96 | 0.635361E+09 | 845.71 | 02-MAY-13:09 | 26.65 | 14.96 |
June | 0.103564E+11 | 18960.04 | 25-JUN-13:13 | 23.33 | 13.15 | 0.656621E+09 | 845.69 | 19-JUN-13:39 | 23.33 | 13.15 |
July | 0.133632E+11 | 24404.07 | 16-JUL-15:12 | 33.13 | 18.76 | 0.614991E+09 | 846.63 | 14-JUL-13:20 | 33.13 | 18.76 |
August | 0.154209E+11 | 25128.83 | 06-AUG-13:42 | 34.32 | 15.27 | 0.689071E+09 | 849.03 | 30-AUG-13:39 | 26.33 | 14.35 |
September | 0.107651E+11 | 26395.25 | 03-SEP-12:32 | 33.13 | 15.93 | 0.602007E+09 | 849.26 | 01-SEP-13:30 | 33.13 | 15.93 |
October | 0.888222E+10 | 27762.99 | 15-OCT-12:31 | 21.83 | 10.70 | 0.617538E+09 | 858.27 | 18-OCT-13:30 | 24.70 | 11.11 |
November | 0.599537E+10 | 23862.64 | 12-NOV-13:32 | -0.6 | -3.6 | 0.585362E+09 | 847.02 | 06-NOV-14:39 | -0.6 | -3.6 |
December | 0.393540E+10 | 12858.84 | 12-DEC-12:30 | -2.8 | -5.7 | 0.542302E+09 | 845.64 | 19-DEC-14:09 | 10.97 | 6.81 |
Annual Sum or Average | 0.971648E+11 | 0.721265E+10 | ||||||||
Minimum of Months | 0.253283E+10 | 11207.84 | -2.8 | -5.7 | 0.520984E+09 | 845.64 | -0.6 | -3.6 | ||
Maximum of Months | 0.154209E+11 | 27762.99 | 34.32 | 18.76 | 0.689071E+09 | 858.27 | 33.13 | 18.76 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.189157E+10 | 4176.10 | 13-JAN-15:40 | 9.27 | 4.85 | 0.323726E+09 | 544.93 | 02-JAN-14:00 | 9.27 | 4.85 |
February | 0.334030E+10 | 15273.08 | 26-FEB-17:33 | 12.60 | 4.72 | 0.329469E+09 | 544.95 | 27-FEB-10:09 | 12.15 | 4.44 |
March | 0.559006E+10 | 14471.91 | 12-MAR-16:23 | 5.55 | -0.9 | 0.428699E+09 | 544.95 | 21-MAR-13:50 | 2.25 | 0.50 |
April | 0.805338E+10 | 25603.26 | 16-APR-17:22 | 19.70 | 8.86 | 0.394115E+09 | 544.96 | 13-APR-13:00 | 19.70 | 8.86 |
May | 0.729374E+10 | 27673.15 | 28-MAY-17:41 | 20.18 | 10.35 | 0.417637E+09 | 544.99 | 02-MAY-13:09 | 20.18 | 10.35 |
June | 0.108317E+11 | 25710.59 | 25-JUN-17:52 | 23.30 | 14.13 | 0.426626E+09 | 544.98 | 19-JUN-13:39 | 23.30 | 14.13 |
July | 0.138072E+11 | 27209.43 | 16-JUL-17:11 | 33.13 | 17.22 | 0.397808E+09 | 544.98 | 13-JUL-09:00 | 33.13 | 17.22 |
August | 0.153197E+11 | 27063.21 | 06-AUG-16:21 | 35.30 | 16.02 | 0.446159E+09 | 544.97 | 15-AUG-13:30 | 25.00 | 13.67 |
September | 0.737168E+10 | 25400.31 | 04-SEP-15:52 | 32.80 | 16.49 | 0.389128E+09 | 544.99 | 07-SEP-09:50 | 16.52 | 15.26 |
October | 0.595908E+10 | 24293.32 | 15-OCT-14:31 | 22.97 | 11.08 | 0.402739E+09 | 544.96 | 18-OCT-13:30 | 24.70 | 11.11 |
November | 0.477277E+10 | 9250.18 | 03-NOV-15:40 | 14.40 | 7.69 | 0.389029E+09 | 544.96 | 16-NOV-14:09 | 10.63 | 6.46 |
December | 0.392596E+10 | 8432.48 | 06-DEC-15:30 | 10.25 | 4.94 | 0.367343E+09 | 544.95 | 07-DEC-10:20 | 3.90 | 1.50 |
Annual Sum or Average | 0.881571E+11 | 0.471248E+10 | ||||||||
Minimum of Months | 0.189157E+10 | 4176.10 | 5.55 | -0.9 | 0.323726E+09 | 544.93 | 2.25 | 0.50 | ||
Maximum of Months | 0.153197E+11 | 27673.15 | 35.30 | 17.22 | 0.446159E+09 | 544.99 | 33.13 | 17.22 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 57657188.11 | 1332.92 | 14-JAN-17:03 | 8.90 | 4.06 | 0.461812E+09 | 626.02 | 09-JAN-14:39 | 8.90 | 4.06 |
February | 0.468321E+09 | 2364.02 | 27-FEB-13:30 | 17.75 | 6.76 | 0.428083E+09 | 741.20 | 27-FEB-14:00 | 18.90 | 7.23 |
March | 0.135771E+10 | 2299.44 | 23-MAR-13:30 | 9.70 | 2.18 | 0.537005E+09 | 783.41 | 29-MAR-13:00 | 12.80 | 4.50 |
April | 0.224309E+10 | 4714.69 | 07-APR-14:30 | 22.50 | 9.29 | 0.530802E+09 | 845.61 | 13-APR-13:00 | 13.30 | 7.60 |
May | 0.342311E+10 | 6761.33 | 19-MAY-16:00 | 27.80 | 14.54 | 0.604483E+09 | 845.62 | 25-MAY-13:09 | 17.20 | 8.78 |
June | 0.631841E+10 | 8615.82 | 21-JUN-05:03 | 15.87 | 11.84 | 0.653473E+09 | 845.64 | 27-JUN-13:00 | 25.00 | 13.11 |
July | 0.761123E+10 | 14469.02 | 16-JUL-19:01 | 31.37 | 17.17 | 0.613424E+09 | 846.48 | 18-JUL-13:20 | 33.17 | 17.33 |
August | 0.662454E+10 | 14382.13 | 06-AUG-16:41 | 35.10 | 15.80 | 0.683726E+09 | 845.64 | 01-AUG-13:09 | 35.10 | 15.80 |
September | 0.395012E+10 | 14215.20 | 04-SEP-15:01 | 32.30 | 16.64 | 0.575239E+09 | 845.67 | 07-SEP-09:00 | 16.70 | 15.61 |
October | 0.228735E+10 | 3995.06 | 19-OCT-14:40 | 21.50 | 10.24 | 0.549664E+09 | 845.61 | 19-OCT-13:09 | 21.50 | 10.24 |
November | 0.111922E+10 | 2308.24 | 03-NOV-13:30 | 14.35 | 7.74 | 0.487095E+09 | 783.38 | 08-NOV-14:00 | 13.20 | 7.65 |
December | 0.258338E+09 | 1571.04 | 06-DEC-16:20 | 8.50 | 3.80 | 0.449374E+09 | 665.63 | 06-DEC-14:00 | 8.50 | 3.80 |
Annual Sum or Average | 0.357191E+11 | 0.657418E+10 | ||||||||
Minimum of Months | 57657188.11 | 1332.92 | 8.50 | 2.18 | 0.428083E+09 | 626.02 | 8.50 | 3.80 | ||
Maximum of Months | 0.761123E+10 | 14469.02 | 35.10 | 17.17 | 0.683726E+09 | 846.48 | 35.10 | 17.33 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.167050E+09 | 1685.81 | 20-JAN-10:00 | -3.3 | -5.9 | 0.219555E+09 | 396.80 | 20-JAN-09:00 | -3.3 | -5.9 |
February | 0.848023E+09 | 3825.08 | 28-FEB-09:55 | 1.10 | -0.5 | 0.208551E+09 | 521.20 | 28-FEB-11:20 | 4.83 | 1.71 |
March | 0.198210E+10 | 6737.60 | 28-MAR-10:10 | 7.38 | 1.58 | 0.265819E+09 | 521.20 | 22-MAR-10:09 | 7.38 | 1.58 |
April | 0.341498E+10 | 10321.90 | 25-APR-09:00 | 9.40 | 4.65 | 0.257910E+09 | 521.21 | 13-APR-14:09 | 9.40 | 4.65 |
May | 0.464794E+10 | 11857.47 | 19-MAY-08:50 | 17.52 | 11.29 | 0.292652E+09 | 521.26 | 02-MAY-12:20 | 17.52 | 11.29 |
June | 0.783077E+10 | 21042.65 | 04-JUN-07:42 | 15.63 | 13.07 | 0.309184E+09 | 522.16 | 30-JUN-10:30 | 21.95 | 13.70 |
July | 0.956508E+10 | 24045.00 | 16-JUL-09:01 | 22.38 | 16.15 | 0.291646E+09 | 523.00 | 03-JUL-10:30 | 22.38 | 16.15 |
August | 0.859665E+10 | 24557.99 | 06-AUG-09:21 | 28.60 | 14.63 | 0.323635E+09 | 523.19 | 07-AUG-10:50 | 30.60 | 14.99 |
September | 0.498618E+10 | 21859.73 | 04-SEP-08:22 | 26.15 | 14.59 | 0.274424E+09 | 521.22 | 07-SEP-10:09 | 16.88 | 15.79 |
October | 0.285988E+10 | 7085.01 | 18-OCT-10:10 | 20.28 | 8.90 | 0.266801E+09 | 521.20 | 19-OCT-10:09 | 19.18 | 9.33 |
November | 0.136025E+10 | 3429.25 | 03-NOV-10:10 | 9.10 | 5.57 | 0.233209E+09 | 521.20 | 03-NOV-10:20 | 9.50 | 5.81 |
December | 0.370884E+09 | 1845.23 | 07-DEC-11:20 | 6.67 | 2.71 | 0.212598E+09 | 423.73 | 07-DEC-11:30 | 6.95 | 2.80 |
Annual Sum or Average | 0.466298E+11 | 0.315598E+10 | ||||||||
Minimum of Months | 0.167050E+09 | 1685.81 | -3.3 | -5.9 | 0.208551E+09 | 396.80 | -3.3 | -5.9 | ||
Maximum of Months | 0.956508E+10 | 24557.99 | 28.60 | 16.15 | 0.323635E+09 | 523.19 | 30.60 | 16.15 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.165117E+10 | 10271.35 | 19-JAN-14:00 | -5.6 | -7.5 | 0.505223E+09 | 845.64 | 13-JAN-14:39 | -5.6 | -7.5 |
February | 0.378313E+10 | 26768.16 | 26-FEB-12:42 | 14.72 | 5.41 | 0.498956E+09 | 845.96 | 27-FEB-14:20 | 18.50 | 7.10 |
March | 0.541531E+10 | 19695.28 | 01-MAR-13:50 | 6.52 | 2.64 | 0.601353E+09 | 846.43 | 23-MAR-13:00 | 10.00 | 2.51 |
April | 0.560766E+10 | 23121.63 | 16-APR-13:13 | 18.67 | 7.93 | 0.553139E+09 | 846.03 | 24-APR-13:00 | 17.80 | 9.82 |
May | 0.633317E+10 | 15080.46 | 14-MAY-13:43 | 16.52 | 6.74 | 0.615081E+09 | 846.08 | 19-MAY-13:39 | 26.83 | 14.98 |
June | 0.900586E+10 | 14704.71 | 30-JUN-13:30 | 28.05 | 13.89 | 0.648885E+09 | 845.68 | 19-JUN-13:09 | 28.05 | 13.89 |
July | 0.114905E+11 | 26719.84 | 16-JUL-13:02 | 29.78 | 18.22 | 0.612938E+09 | 846.25 | 19-JUL-13:50 | 29.68 | 17.39 |
August | 0.129329E+11 | 27236.13 | 06-AUG-12:41 | 33.72 | 14.74 | 0.684024E+09 | 862.20 | 30-AUG-13:39 | 26.33 | 14.35 |
September | 0.103513E+11 | 28127.80 | 03-SEP-14:11 | 33.33 | 16.05 | 0.590398E+09 | 873.22 | 01-SEP-13:50 | 33.33 | 16.05 |
October | 0.805617E+10 | 26595.87 | 15-OCT-13:22 | 22.75 | 10.91 | 0.600576E+09 | 884.61 | 18-OCT-13:50 | 24.90 | 11.31 |
November | 0.468428E+10 | 24690.01 | 12-NOV-13:43 | -0.3 | -3.4 | 0.558960E+09 | 846.15 | 06-NOV-14:50 | -0.3 | -3.4 |
December | 0.233376E+10 | 10729.65 | 12-DEC-14:30 | -2.2 | -5.4 | 0.506051E+09 | 845.63 | 14-DEC-14:20 | 3.50 | -0.7 |
Annual Sum or Average | 0.816451E+11 | 0.697559E+10 | ||||||||
Minimum of Months | 0.165117E+10 | 10271.35 | -5.6 | -7.5 | 0.498956E+09 | 845.63 | -5.6 | -7.5 | ||
Maximum of Months | 0.129329E+11 | 28127.80 | 33.72 | 18.22 | 0.684024E+09 | 884.61 | 33.33 | 17.39 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.305037E+09 | 2386.10 | 13-JAN-15:50 | 9.08 | 4.76 | 0.301866E+09 | 479.34 | 13-JAN-15:00 | 8.90 | 4.67 |
February | 0.108275E+10 | 6724.16 | 28-FEB-16:40 | 10.37 | 4.49 | 0.285239E+09 | 544.13 | 27-FEB-14:00 | 10.37 | 4.49 |
March | 0.226467E+10 | 8366.90 | 28-MAR-17:00 | 10.60 | 2.97 | 0.353282E+09 | 544.94 | 02-MAR-14:39 | 10.60 | 2.97 |
April | 0.364656E+10 | 22665.17 | 16-APR-17:11 | 19.80 | 8.90 | 0.341126E+09 | 544.94 | 07-APR-13:09 | 19.80 | 8.90 |
May | 0.514554E+10 | 22790.05 | 28-MAY-17:52 | 20.00 | 10.33 | 0.385956E+09 | 544.96 | 25-MAY-13:09 | 20.00 | 10.33 |
June | 0.757907E+10 | 25249.96 | 18-JUN-17:21 | 25.30 | 14.49 | 0.416289E+09 | 544.97 | 27-JUN-13:00 | 25.00 | 13.11 |
July | 0.910797E+10 | 26950.18 | 16-JUL-17:01 | 33.22 | 17.33 | 0.394674E+09 | 544.97 | 03-JUL-13:09 | 33.22 | 17.33 |
August | 0.835700E+10 | 26091.73 | 06-AUG-16:41 | 35.10 | 15.80 | 0.437935E+09 | 544.96 | 01-AUG-13:09 | 35.10 | 15.80 |
September | 0.532204E+10 | 25370.58 | 04-SEP-15:41 | 32.70 | 16.52 | 0.364588E+09 | 544.98 | 07-SEP-09:00 | 16.70 | 15.61 |
October | 0.329267E+10 | 9863.86 | 16-OCT-16:00 | 19.40 | 8.07 | 0.352753E+09 | 544.94 | 19-OCT-13:09 | 21.10 | 10.07 |
November | 0.172146E+10 | 5231.32 | 03-NOV-15:50 | 14.35 | 7.69 | 0.323608E+09 | 544.92 | 09-NOV-14:00 | 9.00 | 3.82 |
December | 0.637755E+09 | 2616.28 | 06-DEC-15:50 | 9.68 | 4.65 | 0.295358E+09 | 513.75 | 06-DEC-15:00 | 9.40 | 4.51 |
Annual Sum or Average | 0.484625E+11 | 0.425267E+10 | ||||||||
Minimum of Months | 0.305037E+09 | 2386.10 | 9.08 | 2.97 | 0.285239E+09 | 479.34 | 8.90 | 2.97 | ||
Maximum of Months | 0.910797E+10 | 26950.18 | 35.10 | 17.33 | 0.437935E+09 | 544.98 | 35.10 | 17.33 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 17541607.81 | 1550.14 | 14-JAN-17:03 | 8.90 | 4.06 | 0.458341E+09 | 626.07 | 10-JAN-14:20 | 8.90 | 4.06 |
February | 0.152147E+09 | 2026.66 | 27-FEB-16:10 | 17.78 | 6.92 | 0.421975E+09 | 682.42 | 27-FEB-14:00 | 17.78 | 6.92 |
March | 0.671869E+09 | 2167.16 | 29-MAR-16:00 | 12.20 | 4.07 | 0.512399E+09 | 711.66 | 29-MAR-13:00 | 12.20 | 4.07 |
April | 0.167775E+10 | 4278.52 | 07-APR-14:30 | 22.50 | 9.29 | 0.489976E+09 | 845.60 | 07-APR-13:09 | 22.50 | 9.29 |
May | 0.312169E+10 | 7452.95 | 19-MAY-16:00 | 27.80 | 14.54 | 0.570367E+09 | 845.63 | 19-MAY-13:09 | 27.80 | 14.54 |
June | 0.629061E+10 | 9223.32 | 29-JUN-15:10 | 32.02 | 14.63 | 0.639145E+09 | 845.63 | 21-JUN-13:09 | 32.02 | 14.63 |
July | 0.792380E+10 | 18798.35 | 16-JUL-18:31 | 32.40 | 17.11 | 0.609273E+09 | 845.65 | 03-JUL-13:09 | 32.40 | 17.11 |
August | 0.668375E+10 | 19643.54 | 06-AUG-16:11 | 35.40 | 16.13 | 0.670615E+09 | 845.64 | 01-AUG-13:09 | 35.40 | 16.13 |
September | 0.365664E+10 | 19121.07 | 04-SEP-15:41 | 32.70 | 16.52 | 0.544175E+09 | 845.66 | 07-SEP-09:00 | 16.70 | 15.61 |
October | 0.160188E+10 | 3257.93 | 19-OCT-15:00 | 21.70 | 10.26 | 0.503167E+09 | 845.60 | 19-OCT-13:50 | 21.70 | 10.26 |
November | 0.476969E+09 | 2023.36 | 17-NOV-17:00 | 17.20 | 8.89 | 0.464002E+09 | 700.13 | 08-NOV-14:00 | 17.20 | 8.89 |
December | 72590499.53 | 1594.32 | 06-DEC-16:20 | 8.50 | 3.80 | 0.446389E+09 | 626.01 | 29-DEC-10:09 | -23.5 | -23.9 |
Annual Sum or Average | 0.323472E+11 | 0.632983E+10 | ||||||||
Minimum of Months | 17541607.81 | 1550.14 | 8.50 | 3.80 | 0.421975E+09 | 626.01 | -23.5 | -23.9 | ||
Maximum of Months | 0.792380E+10 | 19643.54 | 35.40 | 17.11 | 0.670615E+09 | 845.66 | 35.40 | 17.11 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 40544927.54 | 1646.82 | 13-JAN-06:04 | 0.50 | -2.4 | 0.298611E+09 | 403.45 | 09-JAN-10:50 | 0.50 | -2.4 |
February | 0.493399E+09 | 2321.63 | 28-FEB-10:30 | 2.50 | 0.37 | 0.277444E+09 | 518.89 | 28-FEB-10:39 | 2.97 | 0.62 |
March | 0.131051E+10 | 4966.15 | 23-MAR-10:30 | 8.60 | 1.66 | 0.350453E+09 | 544.95 | 22-MAR-09:00 | 8.60 | 1.66 |
April | 0.262049E+10 | 9251.10 | 25-APR-09:40 | 11.27 | 5.45 | 0.340970E+09 | 544.95 | 25-APR-09:09 | 11.27 | 5.45 |
May | 0.414030E+10 | 11380.57 | 19-MAY-09:20 | 18.53 | 11.74 | 0.391212E+09 | 544.99 | 02-MAY-13:09 | 18.53 | 11.74 |
June | 0.772813E+10 | 22265.57 | 25-JUN-09:02 | 17.15 | 11.95 | 0.418527E+09 | 546.01 | 23-JUN-09:00 | 17.15 | 11.95 |
July | 0.982132E+10 | 21941.44 | 16-JUL-09:12 | 22.57 | 16.22 | 0.394699E+09 | 545.76 | 03-JUL-09:00 | 22.57 | 16.22 |
August | 0.864118E+10 | 23936.56 | 06-AUG-08:11 | 24.60 | 14.01 | 0.438759E+09 | 546.05 | 11-AUG-09:00 | 27.80 | 12.62 |
September | 0.449366E+10 | 21937.99 | 04-SEP-09:02 | 26.88 | 14.90 | 0.365686E+09 | 544.98 | 07-SEP-09:00 | 16.70 | 15.61 |
October | 0.210933E+10 | 5872.13 | 18-OCT-10:00 | 20.00 | 8.80 | 0.345857E+09 | 544.95 | 12-OCT-09:20 | 20.00 | 8.80 |
November | 0.740136E+09 | 2260.89 | 03-NOV-10:00 | 8.70 | 5.33 | 0.303414E+09 | 505.77 | 03-NOV-09:00 | 8.70 | 5.33 |
December | 0.145228E+09 | 1670.38 | 09-DEC-06:04 | -5.1 | -5.7 | 0.288245E+09 | 413.06 | 06-DEC-10:50 | -5.1 | -5.7 |
Annual Sum or Average | 0.422842E+11 | 0.421388E+10 | ||||||||
Minimum of Months | 40544927.54 | 1646.82 | -5.1 | -5.7 | 0.277444E+09 | 403.45 | -5.1 | -5.7 | ||
Maximum of Months | 0.982132E+10 | 23936.56 | 26.88 | 16.22 | 0.438759E+09 | 546.05 | 27.80 | 16.22 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.108269E+10 | 8601.33 | 31-JAN-13:40 | -0.8 | -4.5 | 0.489870E+09 | 845.63 | 31-JAN-14:00 | -1.1 | -4.4 |
February | 0.279393E+10 | 26877.68 | 26-FEB-14:31 | 16.33 | 6.24 | 0.477774E+09 | 845.63 | 06-FEB-14:00 | 16.33 | 6.24 |
March | 0.405957E+10 | 17432.78 | 01-MAR-14:10 | 6.97 | 2.89 | 0.575614E+09 | 845.99 | 23-MAR-13:50 | 9.90 | 2.40 |
April | 0.442778E+10 | 16726.38 | 25-APR-13:40 | 16.30 | 6.98 | 0.526635E+09 | 846.12 | 24-APR-13:00 | 16.30 | 6.98 |
May | 0.567801E+10 | 15530.60 | 19-MAY-13:50 | 27.02 | 15.00 | 0.593480E+09 | 845.71 | 02-MAY-13:09 | 27.02 | 15.00 |
June | 0.888060E+10 | 22337.32 | 25-JUN-14:22 | 24.70 | 13.38 | 0.636477E+09 | 845.66 | 21-JUN-13:09 | 24.70 | 13.38 |
July | 0.118260E+11 | 27339.55 | 16-JUL-13:52 | 31.70 | 18.44 | 0.608265E+09 | 846.37 | 18-JUL-13:00 | 31.70 | 17.43 |
August | 0.129805E+11 | 30333.83 | 06-AUG-14:11 | 34.40 | 15.37 | 0.674735E+09 | 846.52 | 31-AUG-13:39 | 25.37 | 13.99 |
September | 0.957656E+10 | 30694.41 | 04-SEP-15:01 | 32.30 | 16.64 | 0.570748E+09 | 854.90 | 01-SEP-13:50 | 32.30 | 16.64 |
October | 0.636062E+10 | 28821.48 | 15-OCT-15:02 | 22.70 | 11.00 | 0.571513E+09 | 847.54 | 18-OCT-13:50 | 24.90 | 11.31 |
November | 0.331288E+10 | 16784.58 | 03-NOV-13:30 | 14.35 | 7.74 | 0.528929E+09 | 845.63 | 10-NOV-14:00 | 5.50 | 0.83 |
December | 0.150156E+10 | 8120.88 | 06-DEC-14:40 | 11.30 | 5.42 | 0.485081E+09 | 845.63 | 01-DEC-14:00 | 11.30 | 5.42 |
Annual Sum or Average | 0.724807E+11 | 0.673912E+10 | ||||||||
Minimum of Months | 0.108269E+10 | 8120.88 | -0.8 | -4.5 | 0.477774E+09 | 845.63 | -1.1 | -4.4 | ||
Maximum of Months | 0.129805E+11 | 30694.41 | 34.40 | 18.44 | 0.674735E+09 | 854.90 | 32.30 | 17.43 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.175090E+09 | 2387.21 | 13-JAN-15:50 | 9.08 | 4.76 | 0.299570E+09 | 458.08 | 13-JAN-15:00 | 8.90 | 4.67 |
February | 0.716358E+09 | 5972.87 | 28-FEB-16:40 | 10.37 | 4.49 | 0.280068E+09 | 524.73 | 27-FEB-14:00 | 10.37 | 4.49 |
March | 0.154821E+10 | 7801.50 | 28-MAR-17:00 | 10.60 | 2.97 | 0.342489E+09 | 544.89 | 02-MAR-14:00 | 10.60 | 2.97 |
April | 0.298321E+10 | 21608.46 | 16-APR-17:42 | 19.50 | 8.78 | 0.323384E+09 | 544.94 | 07-APR-13:20 | 19.50 | 8.78 |
May | 0.472690E+10 | 24067.47 | 28-MAY-17:52 | 20.00 | 10.33 | 0.370939E+09 | 544.96 | 19-MAY-13:09 | 20.00 | 10.33 |
June | 0.751985E+10 | 26901.85 | 18-JUN-17:11 | 25.40 | 14.50 | 0.407358E+09 | 544.96 | 29-JUN-09:30 | 25.55 | 12.82 |
July | 0.933868E+10 | 27621.06 | 09-JUL-17:21 | 28.05 | 13.07 | 0.391285E+09 | 544.97 | 03-JUL-13:09 | 28.05 | 13.07 |
August | 0.837458E+10 | 28387.72 | 06-AUG-16:11 | 35.40 | 16.13 | 0.430406E+09 | 544.96 | 01-AUG-13:09 | 35.40 | 16.13 |
September | 0.492987E+10 | 27460.37 | 04-SEP-15:41 | 32.70 | 16.52 | 0.350449E+09 | 544.95 | 05-SEP-09:09 | 17.20 | 11.96 |
October | 0.250978E+10 | 9572.51 | 18-OCT-16:00 | 24.40 | 11.02 | 0.333445E+09 | 544.85 | 13-OCT-13:00 | 24.40 | 11.02 |
November | 0.107502E+10 | 4333.93 | 03-NOV-15:50 | 14.35 | 7.69 | 0.310691E+09 | 522.23 | 09-NOV-14:00 | 9.00 | 3.82 |
December | 0.347233E+09 | 2606.63 | 06-DEC-15:50 | 9.68 | 4.65 | 0.290827E+09 | 488.15 | 06-DEC-15:00 | 9.40 | 4.51 |
Annual Sum or Average | 0.442448E+11 | 0.413091E+10 | ||||||||
Minimum of Months | 0.175090E+09 | 2387.21 | 9.08 | 2.97 | 0.280068E+09 | 458.08 | 8.90 | 2.97 | ||
Maximum of Months | 0.933868E+10 | 28387.72 | 35.40 | 16.52 | 0.430406E+09 | 544.97 | 35.40 | 16.13 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.259304E+09 | 7887.51 | 06-JAN-05:01 | -24.5 | -24.9 | 0.00 | 0.00 | 01-JAN-00:10 | -24.5 | -24.9 |
February | 0.485349E+09 | 5711.05 | 04-FEB-05:01 | -20.4 | -20.8 | 0.00 | 0.00 | 01-FEB-00:10 | -20.4 | -20.8 |
March | 0.143189E+10 | 5243.63 | 04-MAR-06:01 | -20.1 | -20.7 | 0.00 | 0.00 | 01-MAR-00:10 | -20.1 | -20.7 |
April | 0.315354E+10 | 5262.81 | 25-APR-15:40 | 17.53 | 7.62 | 0.00 | 0.00 | 01-APR-00:10 | 17.53 | 7.62 |
May | 0.322285E+10 | 8798.00 | 30-MAY-05:15 | 15.60 | 11.34 | 0.00 | 0.00 | 01-MAY-00:10 | 15.60 | 11.34 |
June | 0.667258E+10 | 8254.42 | 26-JUN-05:15 | 10.33 | 9.12 | 0.00 | 0.00 | 01-JUN-00:10 | 10.33 | 9.12 |
July | 0.869661E+10 | 10385.62 | 03-JUL-05:15 | 11.30 | 9.70 | 0.00 | 0.00 | 01-JUL-00:10 | 11.30 | 9.70 |
August | 0.903811E+10 | 12935.74 | 07-AUG-05:15 | 17.77 | 10.09 | 0.00 | 0.00 | 01-AUG-00:10 | 17.77 | 10.09 |
September | 0.489896E+10 | 10381.62 | 05-SEP-05:25 | 18.60 | 12.09 | 0.00 | 0.00 | 01-SEP-00:10 | 18.60 | 12.09 |
October | 0.318880E+10 | 5120.53 | 16-OCT-15:50 | 19.68 | 8.22 | 0.00 | 0.00 | 01-OCT-00:10 | 19.68 | 8.22 |
November | 0.154083E+10 | 4417.77 | 06-NOV-06:07 | -3.5 | -4.3 | 0.00 | 0.00 | 01-NOV-00:10 | -3.5 | -4.3 |
December | 0.475563E+09 | 3381.48 | 29-DEC-05:01 | -25.0 | -25.3 | 0.00 | 0.00 | 01-DEC-00:10 | -25.0 | -25.3 |
Annual Sum or Average | 0.430644E+11 | 0.00 | ||||||||
Minimum of Months | 0.259304E+09 | 3381.48 | -25.0 | -25.3 | 0.00 | 0.00 | -25.0 | -25.3 | ||
Maximum of Months | 0.903811E+10 | 12935.74 | 19.68 | 12.09 | 0.00 | 0.00 | 19.68 | 12.09 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.189458E+09 | 9857.17 | 06-JAN-04:01 | -24.4 | -24.9 | 0.00 | 0.00 | 01-JAN-00:10 | -24.4 | -24.9 |
February | 0.125911E+09 | 7836.47 | 04-FEB-04:01 | -21.9 | -22.2 | 0.00 | 0.00 | 01-FEB-00:10 | -21.9 | -22.2 |
March | 0.480642E+09 | 11023.31 | 04-MAR-04:01 | -18.4 | -18.9 | 0.00 | 0.00 | 01-MAR-00:10 | -18.4 | -18.9 |
April | 0.941203E+09 | 6309.79 | 29-APR-04:01 | -7.8 | -8.7 | 0.00 | 0.00 | 01-APR-00:10 | -7.8 | -8.7 |
May | 0.165040E+10 | 6729.87 | 08-MAY-04:01 | -2.3 | -2.7 | 0.00 | 0.00 | 01-MAY-00:10 | -2.3 | -2.7 |
June | 0.463686E+10 | 6192.73 | 23-JUN-15:30 | 27.50 | 14.33 | 0.00 | 0.00 | 01-JUN-00:10 | 27.50 | 14.33 |
July | 0.642490E+10 | 7834.67 | 17-JUL-15:30 | 36.65 | 17.14 | 0.00 | 0.00 | 01-JUL-00:10 | 36.65 | 17.14 |
August | 0.615704E+10 | 7720.71 | 07-AUG-15:40 | 32.40 | 16.10 | 0.00 | 0.00 | 01-AUG-00:10 | 32.40 | 16.10 |
September | 0.331661E+10 | 7412.87 | 05-SEP-14:40 | 24.40 | 14.90 | 0.00 | 0.00 | 01-SEP-00:10 | 24.40 | 14.90 |
October | 0.125307E+10 | 5831.23 | 10-OCT-04:01 | -5.2 | -5.7 | 0.00 | 0.00 | 01-OCT-00:10 | -5.2 | -5.7 |
November | 0.510734E+09 | 6662.69 | 13-NOV-05:01 | -5.6 | -8.1 | 0.00 | 0.00 | 01-NOV-00:10 | -5.6 | -8.1 |
December | 0.253214E+09 | 8048.81 | 23-DEC-04:01 | -11.7 | -12.5 | 0.00 | 0.00 | 01-DEC-00:10 | -11.7 | -12.5 |
Annual Sum or Average | 0.259400E+11 | 0.00 | ||||||||
Minimum of Months | 0.125911E+09 | 5831.23 | -24.4 | -24.9 | 0.00 | 0.00 | -24.4 | -24.9 | ||
Maximum of Months | 0.642490E+10 | 11023.31 | 36.65 | 17.14 | 0.00 | 0.00 | 36.65 | 17.14 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 1.38 | -1.3 | 0.00 | 0.00 | 01-JAN-00:10 | 1.38 | -1.3 |
February | 46678605.86 | 2470.12 | 26-FEB-14:34 | 16.33 | 6.24 | 0.00 | 0.00 | 01-FEB-00:10 | 16.33 | 6.24 |
March | 0.302862E+09 | 2884.67 | 23-MAR-13:50 | 9.90 | 2.40 | 0.00 | 0.00 | 01-MAR-00:10 | 9.90 | 2.40 |
April | 0.165922E+10 | 10041.20 | 25-APR-15:00 | 17.00 | 7.46 | 0.00 | 0.00 | 01-APR-00:10 | 17.00 | 7.46 |
May | 0.389495E+10 | 15686.27 | 19-MAY-15:00 | 28.30 | 14.88 | 0.00 | 0.00 | 01-MAY-00:10 | 28.30 | 14.88 |
June | 0.879971E+10 | 18467.55 | 23-JUN-13:30 | 31.40 | 15.21 | 0.00 | 0.00 | 01-JUN-00:10 | 31.40 | 15.21 |
July | 0.119967E+11 | 22087.46 | 17-JUL-15:10 | 36.28 | 17.05 | 0.00 | 0.00 | 01-JUL-00:10 | 36.28 | 17.05 |
August | 0.101024E+11 | 19648.04 | 07-AUG-15:40 | 32.40 | 16.10 | 0.00 | 0.00 | 01-AUG-00:10 | 32.40 | 16.10 |
September | 0.445406E+10 | 14253.15 | 05-SEP-14:40 | 24.40 | 14.90 | 0.00 | 0.00 | 01-SEP-00:10 | 24.40 | 14.90 |
October | 0.913066E+09 | 7767.08 | 18-OCT-15:20 | 24.80 | 11.42 | 0.00 | 0.00 | 01-OCT-00:10 | 24.80 | 11.42 |
November | 25794058.52 | 1136.51 | 04-NOV-16:15 | 15.93 | 7.46 | 0.00 | 0.00 | 01-NOV-00:10 | 15.93 | 7.46 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -2.1 | -4.2 | 0.00 | 0.00 | 01-DEC-00:10 | -2.1 | -4.2 |
Annual Sum or Average | 0.421955E+11 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -2.1 | -4.2 | 0.00 | 0.00 | -2.1 | -4.2 | ||
Maximum of Months | 0.119967E+11 | 22087.46 | 36.28 | 17.05 | 0.00 | 0.00 | 36.28 | 17.05 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.188992E+10 | 1953.66 | 19-JAN-16:50 | -6.4 | -8.0 | 95144403.34 | 126.82 | 20-JAN-14:09 | 0.50 | -3.2 |
February | 0.714484E+10 | 4275.73 | 28-FEB-17:00 | 10.00 | 4.31 | 86396452.40 | 126.82 | 23-FEB-14:09 | 10.00 | 4.31 |
March | 0.137689E+11 | 6830.55 | 31-MAR-24:00 | 2.50 | 0.99 | 0.103236E+09 | 126.82 | 15-MAR-13:09 | 2.50 | 0.99 |
April | 0.187360E+11 | 8240.94 | 22-APR-18:10 | 15.63 | 8.19 | 91605262.09 | 126.82 | 20-APR-13:00 | 15.63 | 8.19 |
May | 0.420256E+10 | 3488.15 | 31-MAY-24:00 | 15.50 | 10.27 | 99234972.22 | 126.84 | 30-MAY-09:30 | 15.50 | 10.27 |
June | 0.931573E+10 | 5349.61 | 30-JUN-23:55 | 19.60 | 12.23 | 98962637.52 | 126.85 | 01-JUN-13:00 | 19.60 | 12.23 |
July | 0.148144E+11 | 7248.02 | 31-JUL-23:40 | 19.77 | 11.91 | 91883848.14 | 126.84 | 03-JUL-13:09 | 19.77 | 11.91 |
August | 0.198926E+11 | 8185.51 | 29-AUG-17:50 | 23.90 | 12.71 | 0.103516E+09 | 133.32 | 11-AUG-13:00 | 23.90 | 12.71 |
September | 0.421255E+10 | 3319.70 | 30-SEP-24:00 | 11.80 | 6.26 | 91610830.02 | 126.85 | 06-SEP-13:00 | 11.80 | 6.26 |
October | 0.917093E+10 | 4969.47 | 31-OCT-24:00 | 4.70 | 1.47 | 95230913.41 | 126.83 | 25-OCT-09:00 | 4.70 | 1.47 |
November | 0.134201E+11 | 6039.07 | 13-NOV-16:20 | 3.27 | -2.5 | 94300335.07 | 126.83 | 08-NOV-14:00 | 3.27 | -2.5 |
December | 0.183878E+11 | 7808.91 | 06-DEC-16:10 | 8.95 | 4.16 | 91880805.96 | 126.82 | 01-DEC-14:09 | 8.95 | 4.16 |
Annual Sum or Average | 0.134956E+12 | 0.114300E+10 | ||||||||
Minimum of Months | 0.188992E+10 | 1953.66 | -6.4 | -8.0 | 86396452.40 | 126.82 | 0.50 | -3.2 | ||
Maximum of Months | 0.198926E+11 | 8240.94 | 23.90 | 12.71 | 0.103516E+09 | 133.32 | 23.90 | 12.71 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.377899E+09 | 1529.37 | 19-JAN-16:50 | -6.4 | -8.0 | 92772484.21 | 126.82 | 20-JAN-14:09 | 0.50 | -3.2 |
February | 0.476908E+10 | 3909.82 | 28-FEB-17:00 | 10.00 | 4.31 | 86396466.57 | 126.82 | 23-FEB-14:09 | 10.00 | 4.31 |
March | 0.112215E+11 | 5858.91 | 31-MAR-23:30 | 2.00 | 0.53 | 0.103236E+09 | 126.82 | 15-MAR-13:09 | 2.00 | 0.53 |
April | 0.167383E+11 | 7778.08 | 25-APR-18:10 | 16.73 | 7.64 | 91605290.86 | 126.82 | 24-APR-09:09 | 16.73 | 7.64 |
May | 0.319301E+10 | 3299.15 | 31-MAY-24:00 | 15.50 | 10.27 | 99234867.31 | 126.84 | 30-MAY-09:30 | 15.50 | 10.27 |
June | 0.854984E+10 | 5228.27 | 30-JUN-23:55 | 19.60 | 12.23 | 98962327.31 | 126.85 | 01-JUN-13:00 | 19.60 | 12.23 |
July | 0.140032E+11 | 7055.04 | 31-JUL-23:55 | 19.20 | 11.32 | 91883929.86 | 126.84 | 03-JUL-13:09 | 19.20 | 11.32 |
August | 0.187011E+11 | 7814.37 | 03-AUG-18:50 | 24.60 | 12.54 | 0.103351E+09 | 131.12 | 11-AUG-13:00 | 32.20 | 13.16 |
September | 0.340050E+10 | 2897.38 | 30-SEP-23:40 | 12.27 | 6.64 | 91609813.32 | 126.84 | 11-SEP-13:00 | 12.27 | 6.64 |
October | 0.746858E+10 | 4119.24 | 31-OCT-24:00 | 4.70 | 1.47 | 95230856.44 | 126.83 | 25-OCT-09:00 | 4.70 | 1.47 |
November | 0.108252E+11 | 5529.96 | 03-NOV-16:00 | 14.30 | 7.69 | 94300353.67 | 126.83 | 08-NOV-14:00 | 13.20 | 7.65 |
December | 0.146153E+11 | 7087.40 | 06-DEC-16:20 | 8.50 | 3.80 | 91880835.29 | 126.82 | 01-DEC-14:09 | 8.50 | 3.80 |
Annual Sum or Average | 0.113864E+12 | 0.114046E+10 | ||||||||
Minimum of Months | 0.377899E+09 | 1529.37 | -6.4 | -8.0 | 86396466.57 | 126.82 | 0.50 | -3.2 | ||
Maximum of Months | 0.187011E+11 | 7814.37 | 24.60 | 12.54 | 0.103351E+09 | 131.12 | 32.20 | 13.16 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.154559E+09 | 1288.58 | 13-JAN-16:30 | 8.35 | 4.30 | 87317359.99 | 128.08 | 24-JAN-10:20 | 0.60 | -0.9 |
February | 0.319410E+10 | 3818.57 | 28-FEB-17:00 | 10.00 | 4.31 | 86389831.01 | 126.82 | 23-FEB-14:09 | 10.00 | 4.31 |
March | 0.944719E+10 | 5772.28 | 28-MAR-17:50 | 9.18 | 2.32 | 0.103236E+09 | 126.82 | 15-MAR-13:09 | 9.18 | 2.32 |
April | 0.154275E+11 | 7829.18 | 25-APR-18:10 | 16.73 | 7.64 | 91605323.18 | 126.82 | 21-APR-09:00 | 16.73 | 7.64 |
May | 0.256263E+10 | 3216.29 | 31-MAY-24:00 | 15.50 | 10.27 | 98882097.14 | 127.04 | 08-MAY-13:09 | 15.50 | 10.27 |
June | 0.829237E+10 | 5228.10 | 30-JUN-23:55 | 19.60 | 12.23 | 98962442.79 | 126.85 | 01-JUN-13:00 | 19.60 | 12.23 |
July | 0.139166E+11 | 7051.37 | 31-JUL-23:55 | 19.20 | 11.32 | 91884019.27 | 126.84 | 03-JUL-13:09 | 19.20 | 11.32 |
August | 0.185277E+11 | 7928.49 | 03-AUG-18:40 | 24.80 | 12.58 | 0.103314E+09 | 129.22 | 11-AUG-13:00 | 32.20 | 13.16 |
September | 0.279900E+10 | 2812.41 | 04-SEP-17:37 | 32.07 | 16.48 | 91604977.96 | 126.84 | 05-SEP-09:00 | 17.20 | 11.96 |
October | 0.590781E+10 | 4001.07 | 18-OCT-17:00 | 21.70 | 10.27 | 95230835.04 | 126.83 | 25-OCT-09:00 | 13.30 | 8.54 |
November | 0.878014E+10 | 5414.91 | 03-NOV-16:00 | 14.30 | 7.69 | 94300359.10 | 126.83 | 08-NOV-14:00 | 13.20 | 7.65 |
December | 0.125780E+11 | 6957.56 | 06-DEC-16:20 | 8.50 | 3.80 | 91880843.27 | 126.82 | 01-DEC-14:09 | 8.50 | 3.80 |
Annual Sum or Average | 0.101588E+12 | 0.113461E+10 | ||||||||
Minimum of Months | 0.154559E+09 | 1288.58 | 8.35 | 2.32 | 86389831.01 | 126.82 | 0.60 | -0.9 | ||
Maximum of Months | 0.185277E+11 | 7928.49 | 32.07 | 16.48 | 0.103314E+09 | 129.22 | 32.20 | 13.16 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.232822E+12 | 91021.31 | 02-JAN-17:00 | 2.20 | -1.7 | 0.206142E+10 | 2745.29 | 02-JAN-14:00 | 2.20 | -1.7 |
February | 0.431961E+12 | 182796.29 | 28-FEB-17:00 | 10.00 | 4.31 | 0.187198E+10 | 2748.46 | 10-FEB-10:09 | 10.00 | 4.31 |
March | 0.725727E+12 | 357269.11 | 31-MAR-24:00 | 2.50 | 0.99 | 0.223626E+10 | 2747.51 | 03-MAR-10:00 | 2.50 | 0.99 |
April | 0.939909E+12 | 366101.27 | 26-APR-16:00 | 9.40 | 4.24 | 0.199629E+10 | 3013.33 | 07-APR-13:00 | 9.40 | 4.24 |
May | 0.238951E+12 | 175652.77 | 31-MAY-24:00 | 15.50 | 10.27 | 0.214840E+10 | 2747.87 | 02-MAY-13:39 | 15.50 | 10.27 |
June | 0.468819E+12 | 267561.85 | 30-JUN-24:00 | 19.60 | 12.23 | 0.214399E+10 | 2748.99 | 22-JUN-13:09 | 19.60 | 12.23 |
July | 0.731435E+12 | 358472.58 | 31-JUL-23:53 | 19.20 | 11.32 | 0.198987E+10 | 2750.16 | 18-JUL-09:00 | 19.20 | 11.32 |
August | 0.970554E+12 | 368999.03 | 22-AUG-07:20 | 12.77 | 9.84 | 0.255767E+10 | 3886.39 | 07-AUG-13:00 | 12.77 | 9.84 |
September | 0.234681E+12 | 175610.11 | 30-SEP-24:00 | 11.80 | 6.26 | 0.198353E+10 | 2748.16 | 06-SEP-13:39 | 11.80 | 6.26 |
October | 0.485879E+12 | 267421.69 | 31-OCT-24:00 | 4.70 | 1.47 | 0.206335E+10 | 2748.50 | 24-OCT-13:09 | 4.70 | 1.47 |
November | 0.706030E+12 | 275866.55 | 06-NOV-16:55 | 6.70 | 2.26 | 0.204274E+10 | 2747.58 | 08-NOV-14:00 | 13.20 | 7.65 |
December | 0.972396E+12 | 366922.97 | 07-DEC-17:00 | 4.40 | 1.14 | 0.198911E+10 | 2745.69 | 29-DEC-10:09 | -23.5 | -23.9 |
Annual Sum or Average | 0.713916E+13 | 0.250846E+11 | ||||||||
Minimum of Months | 0.232822E+12 | 91021.31 | 2.20 | -1.7 | 0.187198E+10 | 2745.29 | -23.5 | -23.9 | ||
Maximum of Months | 0.972396E+12 | 368999.03 | 19.60 | 12.23 | 0.255767E+10 | 3886.39 | 19.60 | 12.23 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.298161E+09 | 11753.91 | 26-JAN-06:05 | -22.2 |
February | 82743847.52 | 11591.05 | 15-FEB-05:03 | 5.40 |
March | 85319750.46 | 11786.37 | 13-MAR-04:35 | 0.93 |
April | 0.115409E+09 | 12121.60 | 10-APR-03:05 | 4.40 |
May | 0.258031E+09 | 15243.05 | 20-MAY-16:03 | 29.82 |
June | 0.231054E+09 | 14246.20 | 24-JUN-16:01 | 28.22 |
July | 0.404987E+09 | 20124.12 | 15-JUL-16:01 | 32.80 |
August | 0.410068E+09 | 23062.80 | 05-AUG-16:01 | 35.22 |
September | 0.437239E+09 | 21150.67 | 02-SEP-16:01 | 33.98 |
October | 0.320978E+09 | 11978.89 | 30-OCT-03:05 | 5.82 |
November | 0.234488E+09 | 12100.82 | 20-NOV-04:07 | -1.7 |
December | 72006845.62 | 12091.75 | 11-DEC-04:05 | -2.6 |
Annual Sum or Average | 0.295049E+10 | |||
Minimum of Months | 72006845.62 | 11591.05 | -22.2 | |
Maximum of Months | 0.437239E+09 | 23062.80 | 35.22 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 1.38 |
February | 0.00 | 0.00 | 01-FEB-00:05 | -12.4 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -3.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2.68 |
May | 0.00 | 0.00 | 01-MAY-00:05 | -1.1 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 18.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 4.98 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -2.1 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -12.4 | |
Maximum of Months | 0.00 | 0.00 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.535457E+09 | 53576.75 | 09-JAN-05:11 | -27.2 |
February | 0.166936E+09 | 51495.91 | 06-FEB-05:01 | -0.4 |
March | 43591199.23 | 48311.78 | 06-MAR-06:01 | -16.3 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2.68 |
May | 0.00 | 0.00 | 01-MAY-00:05 | -1.1 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 18.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 |
November | 17201561.82 | 47884.73 | 27-NOV-06:02 | -14.5 |
December | 0.151188E+09 | 51311.59 | 26-DEC-05:01 | -7.3 |
Annual Sum or Average | 0.914374E+09 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.535457E+09 | 53576.75 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.966339E+10 | 76166.89 | 09-JAN-04:01 | -27.2 |
February | 0.350574E+10 | 75050.09 | 06-FEB-04:01 | -0.6 |
March | 0.201225E+10 | 74575.82 | 06-MAR-04:01 | -18.4 |
April | 80591321.46 | 61031.96 | 10-APR-05:01 | 3.90 |
May | 0.581788E+09 | 68083.58 | 08-MAY-04:01 | -2.3 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 18.43 |
October | 0.310454E+09 | 68290.13 | 10-OCT-04:11 | -5.4 |
November | 0.235061E+10 | 74474.88 | 27-NOV-04:01 | -15.8 |
December | 0.511637E+10 | 74770.45 | 26-DEC-04:01 | -6.3 |
Annual Sum or Average | 0.236212E+11 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.966339E+10 | 76166.89 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.238669E+10 | 13205.04 | 30-JAN-04:01 | -17.7 |
February | 0.620850E+09 | 11869.75 | 04-FEB-05:01 | -20.4 |
March | 93796969.44 | 11908.74 | 06-MAR-05:01 | -18.4 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2.68 |
May | 0.00 | 0.00 | 01-MAY-00:05 | -1.1 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 18.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 |
November | 34065063.36 | 11238.22 | 27-NOV-05:01 | -15.4 |
December | 0.353876E+09 | 11695.33 | 30-DEC-05:01 | -20.6 |
Annual Sum or Average | 0.348928E+10 | |||
Minimum of Months | 0.00 | 0.00 | -20.6 | |
Maximum of Months | 0.238669E+10 | 13205.04 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.156143E+10 | 15385.86 | 30-JAN-04:01 | -17.7 |
February | 0.462808E+09 | 13640.70 | 04-FEB-05:01 | -20.4 |
March | 82899190.75 | 13751.07 | 06-MAR-05:01 | -18.4 |
April | 878913.82 | 7608.08 | 29-APR-05:01 | -7.7 |
May | 499459.26 | 5347.69 | 22-MAY-05:01 | -0.6 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 18.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 |
November | 50287919.90 | 13449.33 | 27-NOV-05:01 | -15.4 |
December | 0.385098E+09 | 13897.72 | 30-DEC-05:01 | -20.6 |
Annual Sum or Average | 0.254390E+10 | |||
Minimum of Months | 0.00 | 0.00 | -20.6 | |
Maximum of Months | 0.156143E+10 | 15385.86 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.217294E+10 | 20950.05 | 11-JAN-04:01 | -28.9 |
February | 0.535626E+09 | 18971.57 | 06-FEB-05:01 | -0.4 |
March | 0.151216E+09 | 19525.96 | 06-MAR-04:01 | -18.4 |
April | 2844575.24 | 16377.86 | 29-APR-05:01 | -7.7 |
May | 16077218.24 | 16558.22 | 08-MAY-05:01 | -2.8 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 18.43 |
October | 3853121.57 | 13051.09 | 10-OCT-05:02 | -6.1 |
November | 0.113410E+09 | 18920.55 | 27-NOV-05:01 | -15.4 |
December | 0.510382E+09 | 19028.04 | 30-DEC-05:01 | -20.6 |
Annual Sum or Average | 0.350635E+10 | |||
Minimum of Months | 0.00 | 0.00 | -28.9 | |
Maximum of Months | 0.217294E+10 | 20950.05 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.691335E+09 | 14297.74 | 09-JAN-04:01 | -27.2 |
February | 43002063.04 | 11897.59 | 04-FEB-05:01 | -20.4 |
March | 4926329.09 | 11123.62 | 04-MAR-06:01 | -20.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2.68 |
May | 0.00 | 0.00 | 01-MAY-00:05 | -1.1 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 18.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 |
November | 1421029.14 | 9676.60 | 27-NOV-06:02 | -14.5 |
December | 4199405.16 | 11115.41 | 30-DEC-06:01 | -20.5 |
Annual Sum or Average | 0.744884E+09 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.691335E+09 | 14297.74 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.843855E+10 | 13403.90 | 09-JAN-05:51 | -27.2 |
February | 0.392368E+10 | 13198.66 | 05-FEB-17:22 | -17.8 |
March | 0.169308E+10 | 12845.87 | 06-MAR-03:53 | -18.3 |
April | 0.165154E+09 | 10979.29 | 29-APR-04:01 | -7.8 |
May | 0.184484E+09 | 11314.59 | 08-MAY-04:01 | -2.3 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.90 |
September | 19435348.38 | 10203.35 | 19-SEP-05:02 | 2.20 |
October | 0.152210E+09 | 11254.39 | 10-OCT-04:01 | -5.2 |
November | 0.167117E+10 | 12967.01 | 26-NOV-18:32 | -13.9 |
December | 0.503539E+10 | 13245.39 | 31-DEC-08:61 | -27.6 |
Annual Sum or Average | 0.212832E+11 | |||
Minimum of Months | 0.00 | 0.00 | -27.6 | |
Maximum of Months | 0.843855E+10 | 13403.90 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.511521E+10 | 18550.39 | 09-JAN-02:31 | -27.2 |
February | 0.219175E+10 | 18076.37 | 05-FEB-04:42 | -20.0 |
March | 0.919676E+09 | 17762.43 | 06-MAR-05:11 | -17.8 |
April | 91640205.67 | 15139.04 | 29-APR-04:01 | -7.8 |
May | 0.117450E+09 | 15550.50 | 08-MAY-04:01 | -2.3 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.90 |
September | 10482144.40 | 12752.30 | 19-SEP-05:02 | 2.20 |
October | 81418474.48 | 15458.66 | 10-OCT-04:01 | -5.2 |
November | 0.102611E+10 | 17739.60 | 27-NOV-05:11 | -15.3 |
December | 0.303292E+10 | 18345.35 | 31-DEC-08:61 | -27.6 |
Annual Sum or Average | 0.125867E+11 | |||
Minimum of Months | 0.00 | 0.00 | -27.6 | |
Maximum of Months | 0.511521E+10 | 18550.39 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.536749E+10 | 22341.31 | 09-JAN-02:31 | -27.2 |
February | 0.195632E+10 | 21843.36 | 05-FEB-04:42 | -20.0 |
March | 0.951747E+09 | 21288.74 | 06-MAR-05:11 | -17.8 |
April | 0.123235E+09 | 18222.84 | 29-APR-04:01 | -7.8 |
May | 0.180249E+09 | 18882.64 | 08-MAY-04:01 | -2.3 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.90 |
September | 9072886.15 | 13819.64 | 19-SEP-05:02 | 2.20 |
October | 68216714.78 | 18534.16 | 10-OCT-04:01 | -5.2 |
November | 0.949085E+09 | 21241.77 | 27-NOV-05:11 | -15.3 |
December | 0.288837E+10 | 22175.53 | 31-DEC-08:61 | -27.6 |
Annual Sum or Average | 0.124938E+11 | |||
Minimum of Months | 0.00 | 0.00 | -27.6 | |
Maximum of Months | 0.536749E+10 | 22341.31 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.450262E+10 | 19729.26 | 09-JAN-02:31 | -27.2 |
February | 0.166563E+10 | 18994.56 | 06-FEB-04:01 | -0.6 |
March | 0.700432E+09 | 18751.04 | 06-MAR-05:11 | -17.8 |
April | 51608025.03 | 15033.22 | 29-APR-05:01 | -7.7 |
May | 83690026.49 | 16622.17 | 08-MAY-04:01 | -2.3 |
June | 37582.91 | 250.55 | 17-JUN-05:05 | 2.35 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.90 |
September | 6386597.09 | 10643.19 | 19-SEP-05:02 | 2.20 |
October | 53137985.51 | 16103.03 | 10-OCT-04:01 | -5.2 |
November | 0.705350E+09 | 18825.06 | 27-NOV-05:11 | -15.3 |
December | 0.222883E+10 | 19443.30 | 31-DEC-08:61 | -27.6 |
Annual Sum or Average | 0.999772E+10 | |||
Minimum of Months | 0.00 | 0.00 | -27.6 | |
Maximum of Months | 0.450262E+10 | 19729.26 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.158330E+11 | 18845.14 | 30-JAN-06:01 | -15.9 |
February | 0.832876E+10 | 18133.27 | 05-FEB-09:22 | -20.0 |
March | 0.524986E+10 | 18299.68 | 06-MAR-05:01 | -18.4 |
April | 0.141077E+10 | 16037.26 | 29-APR-03:01 | -6.9 |
May | 0.109285E+10 | 16859.09 | 08-MAY-03:11 | -2.6 |
June | 22846370.82 | 14100.34 | 17-JUN-04:02 | 2.12 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 19.45 |
August | 16536726.00 | 12447.17 | 18-AUG-05:03 | 7.30 |
September | 0.347950E+09 | 15031.69 | 20-SEP-04:01 | 3.30 |
October | 0.137687E+10 | 16349.75 | 10-OCT-03:01 | -4.1 |
November | 0.556793E+10 | 18299.42 | 27-NOV-05:11 | -15.3 |
December | 0.116232E+11 | 18143.88 | 31-DEC-00:52 | -17.8 |
Annual Sum or Average | 0.508705E+11 | |||
Minimum of Months | 0.00 | 0.00 | -20.0 | |
Maximum of Months | 0.158330E+11 | 18845.14 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.958404E+10 | 19729.13 | 11-JAN-04:11 | -28.9 |
February | 0.459594E+10 | 19051.89 | 05-FEB-04:42 | -20.0 |
March | 0.279587E+10 | 19002.08 | 06-MAR-05:01 | -18.4 |
April | 0.677935E+09 | 16848.66 | 29-APR-03:01 | -6.9 |
May | 0.598176E+09 | 17784.79 | 08-MAY-03:11 | -2.6 |
June | 11261648.01 | 14890.01 | 17-JUN-04:02 | 2.12 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 19.45 |
August | 8636711.49 | 8057.23 | 18-AUG-05:03 | 7.30 |
September | 0.167745E+09 | 15757.19 | 20-SEP-04:01 | 3.30 |
October | 0.675575E+09 | 17185.14 | 10-OCT-03:01 | -4.1 |
November | 0.311625E+10 | 18964.37 | 27-NOV-05:11 | -15.3 |
December | 0.697585E+10 | 19094.56 | 31-DEC-00:52 | -17.8 |
Annual Sum or Average | 0.292073E+11 | |||
Minimum of Months | 0.00 | 0.00 | -28.9 | |
Maximum of Months | 0.958404E+10 | 19729.13 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.110637E+11 | 25572.09 | 11-JAN-04:11 | -28.9 |
February | 0.488601E+10 | 24789.58 | 05-FEB-04:42 | -20.0 |
March | 0.345328E+10 | 24730.47 | 05-MAR-01:02 | -22.2 |
April | 0.104322E+10 | 21889.71 | 29-APR-03:01 | -6.9 |
May | 0.101645E+10 | 23205.92 | 08-MAY-03:11 | -2.6 |
June | 35654317.37 | 19437.84 | 17-JUN-04:02 | 2.12 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 19.45 |
August | 20549064.76 | 12463.80 | 18-AUG-05:03 | 7.30 |
September | 0.215067E+09 | 20396.91 | 19-SEP-04:01 | 2.20 |
October | 0.706102E+09 | 22488.37 | 10-OCT-03:01 | -4.1 |
November | 0.328792E+10 | 24604.64 | 27-NOV-05:11 | -15.3 |
December | 0.766151E+10 | 24796.71 | 31-DEC-00:52 | -17.8 |
Annual Sum or Average | 0.333895E+11 | |||
Minimum of Months | 0.00 | 0.00 | -28.9 | |
Maximum of Months | 0.110637E+11 | 25572.09 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.887934E+10 | 22328.99 | 11-JAN-04:11 | -28.9 |
February | 0.374786E+10 | 21229.35 | 05-FEB-08:62 | -20.1 |
March | 0.228333E+10 | 21321.72 | 06-MAR-05:01 | -18.4 |
April | 0.488445E+09 | 17738.07 | 29-APR-04:01 | -7.8 |
May | 0.459550E+09 | 20083.63 | 08-MAY-03:11 | -2.6 |
June | 14396827.80 | 10249.71 | 17-JUN-04:02 | 2.12 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 19.45 |
August | 9307587.90 | 7849.06 | 18-AUG-05:03 | 7.30 |
September | 0.122837E+09 | 17715.26 | 19-SEP-04:01 | 2.20 |
October | 0.474790E+09 | 19445.54 | 10-OCT-03:01 | -4.1 |
November | 0.233056E+10 | 21341.60 | 27-NOV-05:11 | -15.3 |
December | 0.549653E+10 | 21266.56 | 31-DEC-08:11 | -27.4 |
Annual Sum or Average | 0.243070E+11 | |||
Minimum of Months | 0.00 | 0.00 | -28.9 | |
Maximum of Months | 0.887934E+10 | 22328.99 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.267024E+10 | 13157.17 | 24-JAN-06:01 | 8.22 |
February | 0.138478E+10 | 13081.90 | 21-FEB-05:01 | 7.62 |
March | 0.493284E+09 | 13473.01 | 09-MAR-06:01 | 2.30 |
April | 0.174618E+09 | 12135.45 | 03-APR-04:01 | 2.52 |
May | 0.109412E+09 | 11461.41 | 01-MAY-04:01 | -0.6 |
June | 0.108231E+09 | 8823.68 | 12-JUN-03:02 | 12.12 |
July | 0.125560E+09 | 9950.62 | 05-JUL-03:02 | 9.90 |
August | 0.127011E+09 | 11254.69 | 06-AUG-15:41 | 35.40 |
September | 94361772.32 | 9755.57 | 20-SEP-04:01 | 3.30 |
October | 0.113361E+09 | 11313.65 | 10-OCT-03:01 | -4.1 |
November | 0.359222E+09 | 12941.37 | 30-NOV-06:01 | 1.10 |
December | 0.768216E+09 | 14687.01 | 19-DEC-06:01 | 3.80 |
Annual Sum or Average | 0.652829E+10 | |||
Minimum of Months | 94361772.32 | 8823.68 | -4.1 | |
Maximum of Months | 0.267024E+10 | 14687.01 | 35.40 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.562583E+10 | 14480.15 | 09-JAN-06:12 | -27.2 |
February | 0.335539E+10 | 13516.91 | 06-FEB-06:12 | 0.60 |
March | 0.198310E+10 | 8386.90 | 06-MAR-06:03 | -16.3 |
April | 0.322602E+09 | 11300.01 | 16-APR-15:51 | 20.00 |
May | 0.573574E+09 | 8846.07 | 03-MAY-05:03 | 0.92 |
June | 74118330.37 | 7320.41 | 18-JUN-15:21 | 24.70 |
July | 82716426.88 | 10271.02 | 16-JUL-16:21 | 33.05 |
August | 63558907.57 | 11393.63 | 06-AUG-16:01 | 35.50 |
September | 0.135825E+09 | 10418.47 | 03-SEP-15:31 | 33.67 |
October | 0.402941E+09 | 8188.61 | 13-OCT-05:03 | 14.03 |
November | 0.170030E+10 | 8547.84 | 12-NOV-13:43 | -0.3 |
December | 0.350911E+10 | 8058.38 | 26-DEC-06:15 | -8.0 |
Annual Sum or Average | 0.178291E+11 | |||
Minimum of Months | 63558907.57 | 7320.41 | -27.2 | |
Maximum of Months | 0.562583E+10 | 14480.15 | 35.50 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.202776E+11 | 34216.34 | 11-JAN-05:11 | -30.2 |
February | 0.109664E+11 | 29231.22 | 04-FEB-06:12 | -19.6 |
March | 0.774569E+10 | 33834.58 | 06-MAR-05:12 | -17.8 |
April | 0.301240E+10 | 16198.56 | 29-APR-05:13 | -7.6 |
May | 0.227903E+10 | 20839.79 | 08-MAY-04:15 | -2.4 |
June | 0.483827E+09 | 16257.98 | 05-JUN-05:03 | 10.97 |
July | 0.201323E+09 | 15892.92 | 12-JUL-05:03 | 6.85 |
August | 0.384304E+09 | 15964.41 | 03-AUG-05:02 | 8.12 |
September | 0.121759E+10 | 16836.84 | 28-SEP-05:03 | 8.90 |
October | 0.303841E+10 | 21721.08 | 10-OCT-04:23 | -5.5 |
November | 0.816969E+10 | 31193.05 | 27-NOV-05:20 | -15.3 |
December | 0.152564E+11 | 31731.39 | 29-DEC-05:12 | -25.0 |
Annual Sum or Average | 0.730327E+11 | |||
Minimum of Months | 0.201323E+09 | 15892.92 | -30.2 | |
Maximum of Months | 0.202776E+11 | 34216.34 | 10.97 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 89261759.14 | 632.16 | 09-JAN-03:03 | -27.2 |
February | 0.00 | 0.00 | 01-FEB-00:05 | -12.4 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -3.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2.68 |
May | 0.00 | 0.00 | 01-MAY-00:05 | -1.1 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 18.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 4.98 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -2.1 |
Annual Sum or Average | 89261759.14 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 89261759.14 | 632.16 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.645560E+09 | 665.26 | 29-JAN-17:50 | -21.9 |
February | 0.00 | 0.00 | 01-FEB-00:05 | -12.4 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -3.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2.68 |
May | 3291479.89 | 186.34 | 08-MAY-04:15 | -2.4 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 18.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 4.98 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -2.1 |
Annual Sum or Average | 0.648851E+09 | |||
Minimum of Months | 0.00 | 0.00 | -21.9 | |
Maximum of Months | 0.645560E+09 | 665.26 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.909480E+09 | 690.45 | 29-JAN-17:50 | -21.9 |
February | 73692083.90 | 639.34 | 05-FEB-18:30 | -18.3 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -3.0 |
April | 2489202.73 | 778.87 | 30-APR-23:05 | -1.3 |
May | 0.133157E+09 | 664.30 | 01-MAY-00:05 | -1.1 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.90 |
September | 38141590.55 | 589.43 | 19-SEP-04:24 | 2.20 |
October | 465121.89 | 428.93 | 10-OCT-02:30 | -3.6 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 4.98 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -2.1 |
Annual Sum or Average | 0.115743E+10 | |||
Minimum of Months | 0.00 | 0.00 | -21.9 | |
Maximum of Months | 0.909480E+09 | 778.87 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 1.38 |
February | 0.00 | 0.00 | 01-FEB-00:05 | -12.4 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -3.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2.68 |
May | 0.00 | 0.00 | 01-MAY-00:05 | -1.1 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 18.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 4.98 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -2.1 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -12.4 | |
Maximum of Months | 0.00 | 0.00 | 19.45 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.148304E+11 | 15519.45 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.134523E+11 | 15519.45 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.159851E+11 | 15519.45 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.142779E+11 | 15519.45 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.154078E+11 | 15519.45 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.153333E+11 | 15519.45 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.143524E+11 | 15519.45 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.159851E+11 | 15519.45 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.142779E+11 | 15519.45 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.148304E+11 | 15519.45 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.146566E+11 | 15519.45 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.143524E+11 | 15519.45 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.177742E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.134523E+11 | 15519.45 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.159851E+11 | 15519.45 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.133188E+11 | 13937.56 | 02-JAN-08:09 | 0.270551E+11 | 18128.59 | 02-JAN-08:09 |
February | 0.120811E+11 | 13937.56 | 01-FEB-08:09 | 0.244881E+11 | 18128.59 | 01-FEB-08:09 |
March | 0.143557E+11 | 13937.56 | 01-MAR-08:09 | 0.280558E+11 | 18128.59 | 01-MAR-08:09 |
April | 0.128226E+11 | 13937.56 | 03-APR-07:10 | 0.261305E+11 | 18128.59 | 03-APR-07:10 |
May | 0.138373E+11 | 13937.56 | 01-MAY-07:10 | 0.275555E+11 | 18128.59 | 01-MAY-07:10 |
June | 0.137704E+11 | 13937.56 | 01-JUN-07:10 | 0.270261E+11 | 18128.59 | 01-JUN-07:10 |
July | 0.128895E+11 | 13937.56 | 03-JUL-07:10 | 0.266527E+11 | 18128.59 | 03-JUL-07:10 |
August | 0.143557E+11 | 13937.56 | 01-AUG-07:10 | 0.280558E+11 | 18128.59 | 01-AUG-07:10 |
September | 0.128226E+11 | 13937.56 | 01-SEP-07:10 | 0.261160E+11 | 18128.59 | 01-SEP-07:10 |
October | 0.133188E+11 | 13937.56 | 02-OCT-07:10 | 0.270624E+11 | 18128.59 | 02-OCT-07:10 |
November | 0.131627E+11 | 13937.56 | 01-NOV-07:10 | 0.264424E+11 | 18128.59 | 01-NOV-07:10 |
December | 0.128895E+11 | 13937.56 | 01-DEC-08:09 | 0.266454E+11 | 18128.59 | 01-DEC-08:09 |
Annual Sum or Average | 0.159625E+12 | 0.321286E+12 | ||||
Minimum of Months | 0.120811E+11 | 13937.56 | 0.244881E+11 | 18128.59 | ||
Maximum of Months | 0.143557E+11 | 13937.56 | 0.280558E+11 | 18128.59 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.133188E+11 | 13937.56 | 02-JAN-08:09 | 0.270550E+11 | 18128.52 | 02-JAN-08:09 |
February | 0.120811E+11 | 13937.56 | 01-FEB-08:09 | 0.244880E+11 | 18128.52 | 01-FEB-08:09 |
March | 0.143557E+11 | 13937.56 | 01-MAR-08:09 | 0.280557E+11 | 18128.52 | 01-MAR-08:09 |
April | 0.128226E+11 | 13937.56 | 03-APR-07:10 | 0.261304E+11 | 18128.52 | 03-APR-07:10 |
May | 0.138373E+11 | 13937.56 | 01-MAY-07:10 | 0.275554E+11 | 18128.52 | 01-MAY-07:10 |
June | 0.137704E+11 | 13937.56 | 01-JUN-07:10 | 0.270260E+11 | 18128.52 | 01-JUN-07:10 |
July | 0.128895E+11 | 13937.56 | 03-JUL-07:10 | 0.266526E+11 | 18128.52 | 03-JUL-07:10 |
August | 0.143557E+11 | 13937.56 | 01-AUG-07:10 | 0.280557E+11 | 18128.52 | 01-AUG-07:10 |
September | 0.128226E+11 | 13937.56 | 01-SEP-07:10 | 0.261159E+11 | 18128.52 | 01-SEP-07:10 |
October | 0.133188E+11 | 13937.56 | 02-OCT-07:10 | 0.270623E+11 | 18128.52 | 02-OCT-07:10 |
November | 0.131627E+11 | 13937.56 | 01-NOV-07:10 | 0.264423E+11 | 18128.52 | 01-NOV-07:10 |
December | 0.128895E+11 | 13937.56 | 01-DEC-08:09 | 0.266453E+11 | 18128.52 | 01-DEC-08:09 |
Annual Sum or Average | 0.159625E+12 | 0.321285E+12 | ||||
Minimum of Months | 0.120811E+11 | 13937.56 | 0.244880E+11 | 18128.52 | ||
Maximum of Months | 0.143557E+11 | 13937.56 | 0.280557E+11 | 18128.52 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.133188E+11 | 13937.56 | 02-JAN-08:09 | 0.270550E+11 | 18128.52 | 02-JAN-08:09 |
February | 0.120811E+11 | 13937.56 | 01-FEB-08:09 | 0.244880E+11 | 18128.52 | 01-FEB-08:09 |
March | 0.143557E+11 | 13937.56 | 01-MAR-08:09 | 0.280557E+11 | 18128.52 | 01-MAR-08:09 |
April | 0.128226E+11 | 13937.56 | 03-APR-07:10 | 0.261304E+11 | 18128.52 | 03-APR-07:10 |
May | 0.138373E+11 | 13937.56 | 01-MAY-07:10 | 0.275554E+11 | 18128.52 | 01-MAY-07:10 |
June | 0.137704E+11 | 13937.56 | 01-JUN-07:10 | 0.270260E+11 | 18128.52 | 01-JUN-07:10 |
July | 0.128895E+11 | 13937.56 | 03-JUL-07:10 | 0.266526E+11 | 18128.52 | 03-JUL-07:10 |
August | 0.143557E+11 | 13937.56 | 01-AUG-07:10 | 0.280557E+11 | 18128.52 | 01-AUG-07:10 |
September | 0.128226E+11 | 13937.56 | 01-SEP-07:10 | 0.261159E+11 | 18128.52 | 01-SEP-07:10 |
October | 0.133188E+11 | 13937.56 | 02-OCT-07:10 | 0.270623E+11 | 18128.52 | 02-OCT-07:10 |
November | 0.131627E+11 | 13937.56 | 01-NOV-07:10 | 0.264423E+11 | 18128.52 | 01-NOV-07:10 |
December | 0.128895E+11 | 13937.56 | 01-DEC-08:09 | 0.266453E+11 | 18128.52 | 01-DEC-08:09 |
Annual Sum or Average | 0.159625E+12 | 0.321285E+12 | ||||
Minimum of Months | 0.120811E+11 | 13937.56 | 0.244880E+11 | 18128.52 | ||
Maximum of Months | 0.143557E+11 | 13937.56 | 0.280557E+11 | 18128.52 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.128837E+10 | 1750.00 | 02-JAN-08:09 | 0.339718E+10 | 2276.32 | 02-JAN-08:09 |
February | 0.108359E+10 | 1574.71 | 01-FEB-08:09 | 0.307485E+10 | 2276.32 | 01-FEB-08:09 |
March | 0.123553E+10 | 1683.15 | 17-MAR-07:10 | 0.352283E+10 | 2276.32 | 01-MAR-08:09 |
April | 0.107314E+10 | 1382.47 | 14-APR-07:10 | 0.328108E+10 | 2276.32 | 03-APR-07:10 |
May | 0.113392E+10 | 1232.40 | 03-MAY-07:10 | 0.346000E+10 | 2276.32 | 01-MAY-07:10 |
June | 0.111338E+10 | 1075.02 | 01-JUN-07:10 | 0.339353E+10 | 2276.32 | 01-JUN-07:10 |
July | 0.105617E+10 | 1075.02 | 03-JUL-07:10 | 0.334664E+10 | 2276.32 | 03-JUL-07:10 |
August | 0.118089E+10 | 1075.02 | 01-AUG-07:10 | 0.352283E+10 | 2276.32 | 01-AUG-07:10 |
September | 0.108936E+10 | 1407.20 | 11-SEP-07:10 | 0.327926E+10 | 2276.32 | 01-SEP-07:10 |
October | 0.117754E+10 | 1750.00 | 30-OCT-07:10 | 0.339809E+10 | 2276.32 | 02-OCT-07:10 |
November | 0.123558E+10 | 1750.00 | 01-NOV-07:10 | 0.332024E+10 | 2276.32 | 01-NOV-07:10 |
December | 0.125473E+10 | 1750.00 | 01-DEC-16:40 | 0.334573E+10 | 2276.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.139222E+11 | 0.403423E+11 | ||||
Minimum of Months | 0.105617E+10 | 1075.02 | 0.307485E+10 | 2276.32 | ||
Maximum of Months | 0.128837E+10 | 1750.00 | 0.352283E+10 | 2276.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.815941E+09 | 1127.77 | 02-JAN-08:09 | 0.218927E+10 | 1466.95 | 02-JAN-08:09 |
February | 0.692587E+09 | 980.15 | 01-FEB-16:00 | 0.198155E+10 | 1466.95 | 01-FEB-08:09 |
March | 0.792080E+09 | 1084.69 | 17-MAR-07:10 | 0.227025E+10 | 1466.95 | 01-MAR-08:09 |
April | 0.690691E+09 | 863.77 | 14-APR-07:10 | 0.211446E+10 | 1466.95 | 03-APR-07:10 |
May | 0.732124E+09 | 692.79 | 01-MAY-07:10 | 0.222976E+10 | 1466.95 | 01-MAY-07:10 |
June | 0.720965E+09 | 692.79 | 01-JUN-07:10 | 0.218692E+10 | 1466.95 | 01-JUN-07:10 |
July | 0.681934E+09 | 692.79 | 03-JUL-07:10 | 0.215670E+10 | 1466.95 | 03-JUL-07:10 |
August | 0.763096E+09 | 692.79 | 01-AUG-07:10 | 0.227025E+10 | 1466.95 | 01-AUG-07:10 |
September | 0.701094E+09 | 823.04 | 13-SEP-07:10 | 0.211328E+10 | 1466.95 | 01-SEP-07:10 |
October | 0.750543E+09 | 1127.77 | 30-OCT-07:10 | 0.218986E+10 | 1466.95 | 02-OCT-07:10 |
November | 0.786262E+09 | 1127.77 | 01-NOV-07:10 | 0.213969E+10 | 1466.95 | 01-NOV-07:10 |
December | 0.795198E+09 | 1127.77 | 01-DEC-16:40 | 0.215612E+10 | 1466.95 | 01-DEC-08:09 |
Annual Sum or Average | 0.892252E+10 | 0.259981E+11 | ||||
Minimum of Months | 0.681934E+09 | 692.79 | 0.198155E+10 | 1466.95 | ||
Maximum of Months | 0.815941E+09 | 1127.77 | 0.227025E+10 | 1466.95 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.125350E+10 | 1750.04 | 02-JAN-08:09 | 0.339723E+10 | 2276.35 | 02-JAN-08:09 |
February | 0.106460E+10 | 1430.76 | 02-FEB-08:09 | 0.307490E+10 | 2276.35 | 01-FEB-08:09 |
March | 0.122723E+10 | 1683.19 | 17-MAR-07:10 | 0.352288E+10 | 2276.35 | 01-MAR-08:09 |
April | 0.107432E+10 | 1380.38 | 14-APR-07:10 | 0.328113E+10 | 2276.35 | 03-APR-07:10 |
May | 0.113748E+10 | 1240.79 | 03-MAY-07:10 | 0.346006E+10 | 2276.35 | 01-MAY-07:10 |
June | 0.111929E+10 | 1075.05 | 01-JUN-07:10 | 0.339359E+10 | 2276.35 | 01-JUN-07:10 |
July | 0.106017E+10 | 1075.05 | 03-JUL-07:10 | 0.334669E+10 | 2276.35 | 03-JUL-07:10 |
August | 0.118500E+10 | 1075.05 | 01-AUG-07:10 | 0.352288E+10 | 2276.35 | 01-AUG-07:10 |
September | 0.108777E+10 | 1379.90 | 11-SEP-07:10 | 0.327931E+10 | 2276.35 | 01-SEP-07:10 |
October | 0.115836E+10 | 1750.04 | 30-OCT-07:10 | 0.339814E+10 | 2276.35 | 02-OCT-07:10 |
November | 0.120257E+10 | 1750.04 | 01-NOV-07:10 | 0.332029E+10 | 2276.35 | 01-NOV-07:10 |
December | 0.121426E+10 | 1750.04 | 01-DEC-16:40 | 0.334578E+10 | 2276.35 | 01-DEC-08:09 |
Annual Sum or Average | 0.137846E+11 | 0.403429E+11 | ||||
Minimum of Months | 0.106017E+10 | 1075.05 | 0.307490E+10 | 2276.35 | ||
Maximum of Months | 0.125350E+10 | 1750.04 | 0.352288E+10 | 2276.35 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.821407E+09 | 1127.77 | 02-JAN-08:09 | 0.218926E+10 | 1466.94 | 02-JAN-08:09 |
February | 0.692838E+09 | 1019.45 | 02-FEB-08:09 | 0.198154E+10 | 1466.94 | 01-FEB-08:09 |
March | 0.795438E+09 | 1084.69 | 17-MAR-07:10 | 0.227023E+10 | 1466.94 | 01-MAR-08:09 |
April | 0.693037E+09 | 906.34 | 14-APR-07:10 | 0.211444E+10 | 1466.94 | 03-APR-07:10 |
May | 0.732076E+09 | 824.48 | 03-MAY-07:10 | 0.222974E+10 | 1466.94 | 01-MAY-07:10 |
June | 0.718797E+09 | 692.79 | 01-JUN-07:10 | 0.218691E+10 | 1466.94 | 01-JUN-07:10 |
July | 0.682370E+09 | 692.79 | 03-JUL-07:10 | 0.215669E+10 | 1466.94 | 03-JUL-07:10 |
August | 0.762666E+09 | 794.12 | 17-AUG-07:10 | 0.227023E+10 | 1466.94 | 01-AUG-07:10 |
September | 0.702495E+09 | 959.61 | 11-SEP-07:10 | 0.211327E+10 | 1466.94 | 01-SEP-07:10 |
October | 0.756099E+09 | 1127.77 | 30-OCT-07:10 | 0.218984E+10 | 1466.94 | 02-OCT-07:10 |
November | 0.784537E+09 | 1127.77 | 01-NOV-07:10 | 0.213967E+10 | 1466.94 | 01-NOV-07:10 |
December | 0.795013E+09 | 1127.77 | 01-DEC-16:40 | 0.215610E+10 | 1466.94 | 01-DEC-08:09 |
Annual Sum or Average | 0.893677E+10 | 0.259979E+11 | ||||
Minimum of Months | 0.682370E+09 | 692.79 | 0.198154E+10 | 1466.94 | ||
Maximum of Months | 0.821407E+09 | 1127.77 | 0.227023E+10 | 1466.94 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.129037E+10 | 1750.00 | 02-JAN-08:09 | 0.339718E+10 | 2276.32 | 02-JAN-08:09 |
February | 0.108521E+10 | 1581.11 | 01-FEB-08:09 | 0.307485E+10 | 2276.32 | 01-FEB-08:09 |
March | 0.123644E+10 | 1685.17 | 17-MAR-07:10 | 0.352283E+10 | 2276.32 | 01-MAR-08:09 |
April | 0.107368E+10 | 1393.49 | 14-APR-07:10 | 0.328108E+10 | 2276.32 | 03-APR-07:10 |
May | 0.113419E+10 | 1247.76 | 03-MAY-07:10 | 0.346000E+10 | 2276.32 | 01-MAY-07:10 |
June | 0.111364E+10 | 1075.02 | 01-JUN-07:10 | 0.339353E+10 | 2276.32 | 01-JUN-07:10 |
July | 0.105637E+10 | 1075.02 | 03-JUL-07:10 | 0.334664E+10 | 2276.32 | 03-JUL-07:10 |
August | 0.118116E+10 | 1075.02 | 01-AUG-07:10 | 0.352283E+10 | 2276.32 | 01-AUG-07:10 |
September | 0.109006E+10 | 1417.27 | 11-SEP-07:10 | 0.327926E+10 | 2276.32 | 01-SEP-07:10 |
October | 0.117892E+10 | 1750.00 | 30-OCT-07:10 | 0.339809E+10 | 2276.32 | 02-OCT-07:10 |
November | 0.123782E+10 | 1750.00 | 01-NOV-07:10 | 0.332024E+10 | 2276.32 | 01-NOV-07:10 |
December | 0.125786E+10 | 1750.00 | 01-DEC-16:40 | 0.334573E+10 | 2276.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.139357E+11 | 0.403423E+11 | ||||
Minimum of Months | 0.105637E+10 | 1075.02 | 0.307485E+10 | 2276.32 | ||
Maximum of Months | 0.129037E+10 | 1750.00 | 0.352283E+10 | 2276.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.816324E+09 | 1127.77 | 02-JAN-08:09 | 0.218927E+10 | 1466.95 | 02-JAN-08:09 |
February | 0.692878E+09 | 983.59 | 01-FEB-16:00 | 0.198155E+10 | 1466.95 | 01-FEB-08:09 |
March | 0.792288E+09 | 1085.02 | 17-MAR-07:10 | 0.227025E+10 | 1466.95 | 01-MAR-08:09 |
April | 0.690808E+09 | 867.06 | 14-APR-07:10 | 0.211446E+10 | 1466.95 | 03-APR-07:10 |
May | 0.732233E+09 | 692.79 | 01-MAY-07:10 | 0.222976E+10 | 1466.95 | 01-MAY-07:10 |
June | 0.721102E+09 | 692.79 | 01-JUN-07:10 | 0.218692E+10 | 1466.95 | 01-JUN-07:10 |
July | 0.682030E+09 | 692.79 | 03-JUL-07:10 | 0.215670E+10 | 1466.95 | 03-JUL-07:10 |
August | 0.763248E+09 | 692.79 | 01-AUG-07:10 | 0.227025E+10 | 1466.95 | 01-AUG-07:10 |
September | 0.701263E+09 | 827.35 | 13-SEP-07:10 | 0.211328E+10 | 1466.95 | 01-SEP-07:10 |
October | 0.750944E+09 | 1127.77 | 30-OCT-07:10 | 0.218986E+10 | 1466.95 | 02-OCT-07:10 |
November | 0.786660E+09 | 1127.77 | 01-NOV-07:10 | 0.213969E+10 | 1466.95 | 01-NOV-07:10 |
December | 0.795752E+09 | 1127.77 | 01-DEC-16:40 | 0.215612E+10 | 1466.95 | 01-DEC-08:09 |
Annual Sum or Average | 0.892553E+10 | 0.259981E+11 | ||||
Minimum of Months | 0.682030E+09 | 692.79 | 0.198155E+10 | 1466.95 | ||
Maximum of Months | 0.816324E+09 | 1127.77 | 0.227025E+10 | 1466.95 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.125433E+10 | 1750.04 | 02-JAN-08:09 | 0.339723E+10 | 2276.35 | 02-JAN-08:09 |
February | 0.106529E+10 | 1441.85 | 02-FEB-08:09 | 0.307490E+10 | 2276.35 | 01-FEB-08:09 |
March | 0.122799E+10 | 1685.21 | 17-MAR-07:10 | 0.352288E+10 | 2276.35 | 01-MAR-08:09 |
April | 0.107483E+10 | 1391.48 | 14-APR-07:10 | 0.328113E+10 | 2276.35 | 03-APR-07:10 |
May | 0.113793E+10 | 1255.83 | 03-MAY-07:10 | 0.346006E+10 | 2276.35 | 01-MAY-07:10 |
June | 0.111977E+10 | 1075.05 | 01-JUN-07:10 | 0.339359E+10 | 2276.35 | 01-JUN-07:10 |
July | 0.106051E+10 | 1075.05 | 03-JUL-07:10 | 0.334669E+10 | 2276.35 | 03-JUL-07:10 |
August | 0.118553E+10 | 1178.04 | 17-AUG-07:10 | 0.352288E+10 | 2276.35 | 01-AUG-07:10 |
September | 0.108819E+10 | 1391.00 | 11-SEP-07:10 | 0.327931E+10 | 2276.35 | 01-SEP-07:10 |
October | 0.115918E+10 | 1750.04 | 30-OCT-07:10 | 0.339814E+10 | 2276.35 | 02-OCT-07:10 |
November | 0.120358E+10 | 1750.04 | 01-NOV-07:10 | 0.332029E+10 | 2276.35 | 01-NOV-07:10 |
December | 0.121530E+10 | 1750.04 | 01-DEC-16:40 | 0.334578E+10 | 2276.35 | 01-DEC-08:09 |
Annual Sum or Average | 0.137924E+11 | 0.403429E+11 | ||||
Minimum of Months | 0.106051E+10 | 1075.05 | 0.307490E+10 | 2276.35 | ||
Maximum of Months | 0.125433E+10 | 1750.04 | 0.352288E+10 | 2276.35 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.821729E+09 | 1127.77 | 02-JAN-08:09 | 0.218926E+10 | 1466.94 | 02-JAN-08:09 |
February | 0.693153E+09 | 1020.75 | 02-FEB-08:09 | 0.198154E+10 | 1466.94 | 01-FEB-08:09 |
March | 0.795570E+09 | 1085.02 | 17-MAR-07:10 | 0.227023E+10 | 1466.94 | 01-MAR-08:09 |
April | 0.693186E+09 | 908.02 | 14-APR-07:10 | 0.211444E+10 | 1466.94 | 03-APR-07:10 |
May | 0.732164E+09 | 826.78 | 03-MAY-07:10 | 0.222974E+10 | 1466.94 | 01-MAY-07:10 |
June | 0.718932E+09 | 692.79 | 01-JUN-07:10 | 0.218691E+10 | 1466.94 | 01-JUN-07:10 |
July | 0.682445E+09 | 692.79 | 03-JUL-07:10 | 0.215669E+10 | 1466.94 | 03-JUL-07:10 |
August | 0.762817E+09 | 796.65 | 17-AUG-07:10 | 0.227023E+10 | 1466.94 | 01-AUG-07:10 |
September | 0.702771E+09 | 960.86 | 11-SEP-07:10 | 0.211327E+10 | 1466.94 | 01-SEP-07:10 |
October | 0.756535E+09 | 1127.77 | 30-OCT-07:10 | 0.218984E+10 | 1466.94 | 02-OCT-07:10 |
November | 0.784997E+09 | 1127.77 | 01-NOV-07:10 | 0.213967E+10 | 1466.94 | 01-NOV-07:10 |
December | 0.795514E+09 | 1127.77 | 01-DEC-16:40 | 0.215610E+10 | 1466.94 | 01-DEC-08:09 |
Annual Sum or Average | 0.893981E+10 | 0.259979E+11 | ||||
Minimum of Months | 0.682445E+09 | 692.79 | 0.198154E+10 | 1466.94 | ||
Maximum of Months | 0.821729E+09 | 1127.77 | 0.227023E+10 | 1466.94 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.129037E+10 | 1750.00 | 02-JAN-08:09 | 0.339718E+10 | 2276.32 | 02-JAN-08:09 |
February | 0.108522E+10 | 1581.30 | 01-FEB-08:09 | 0.307485E+10 | 2276.32 | 01-FEB-08:09 |
March | 0.123644E+10 | 1685.09 | 17-MAR-07:10 | 0.352283E+10 | 2276.32 | 01-MAR-08:09 |
April | 0.107368E+10 | 1393.14 | 14-APR-07:10 | 0.328108E+10 | 2276.32 | 03-APR-07:10 |
May | 0.113419E+10 | 1247.27 | 03-MAY-07:10 | 0.346000E+10 | 2276.32 | 01-MAY-07:10 |
June | 0.111364E+10 | 1075.02 | 01-JUN-07:10 | 0.339353E+10 | 2276.32 | 01-JUN-07:10 |
July | 0.105637E+10 | 1075.02 | 03-JUL-07:10 | 0.334664E+10 | 2276.32 | 03-JUL-07:10 |
August | 0.118115E+10 | 1075.02 | 01-AUG-07:10 | 0.352283E+10 | 2276.32 | 01-AUG-07:10 |
September | 0.109006E+10 | 1417.09 | 11-SEP-07:10 | 0.327926E+10 | 2276.32 | 01-SEP-07:10 |
October | 0.117894E+10 | 1750.00 | 30-OCT-07:10 | 0.339809E+10 | 2276.32 | 02-OCT-07:10 |
November | 0.123784E+10 | 1750.00 | 01-NOV-07:10 | 0.332024E+10 | 2276.32 | 01-NOV-07:10 |
December | 0.125790E+10 | 1750.00 | 01-DEC-16:40 | 0.334573E+10 | 2276.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.139358E+11 | 0.403423E+11 | ||||
Minimum of Months | 0.105637E+10 | 1075.02 | 0.307485E+10 | 2276.32 | ||
Maximum of Months | 0.129037E+10 | 1750.00 | 0.352283E+10 | 2276.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.816325E+09 | 1127.77 | 02-JAN-08:09 | 0.218927E+10 | 1466.95 | 02-JAN-08:09 |
February | 0.692886E+09 | 983.79 | 01-FEB-16:00 | 0.198155E+10 | 1466.95 | 01-FEB-08:09 |
March | 0.792246E+09 | 1084.97 | 17-MAR-07:10 | 0.227025E+10 | 1466.95 | 01-MAR-08:09 |
April | 0.690808E+09 | 866.88 | 14-APR-07:10 | 0.211446E+10 | 1466.95 | 03-APR-07:10 |
May | 0.732236E+09 | 692.79 | 01-MAY-07:10 | 0.222976E+10 | 1466.95 | 01-MAY-07:10 |
June | 0.721105E+09 | 692.79 | 01-JUN-07:10 | 0.218692E+10 | 1466.95 | 01-JUN-07:10 |
July | 0.682032E+09 | 692.79 | 03-JUL-07:10 | 0.215670E+10 | 1466.95 | 03-JUL-07:10 |
August | 0.763250E+09 | 692.79 | 01-AUG-07:10 | 0.227025E+10 | 1466.95 | 01-AUG-07:10 |
September | 0.701265E+09 | 827.19 | 13-SEP-07:10 | 0.211328E+10 | 1466.95 | 01-SEP-07:10 |
October | 0.750953E+09 | 1127.77 | 30-OCT-07:10 | 0.218986E+10 | 1466.95 | 02-OCT-07:10 |
November | 0.786829E+09 | 1127.77 | 01-NOV-07:10 | 0.213969E+10 | 1466.95 | 01-NOV-07:10 |
December | 0.795767E+09 | 1127.77 | 01-DEC-16:40 | 0.215612E+10 | 1466.95 | 01-DEC-08:09 |
Annual Sum or Average | 0.892570E+10 | 0.259981E+11 | ||||
Minimum of Months | 0.682032E+09 | 692.79 | 0.198155E+10 | 1466.95 | ||
Maximum of Months | 0.816325E+09 | 1127.77 | 0.227025E+10 | 1466.95 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.125434E+10 | 1750.04 | 02-JAN-08:09 | 0.339723E+10 | 2276.35 | 02-JAN-08:09 |
February | 0.106529E+10 | 1441.95 | 02-FEB-08:09 | 0.307490E+10 | 2276.35 | 01-FEB-08:09 |
March | 0.122799E+10 | 1685.13 | 17-MAR-07:10 | 0.352288E+10 | 2276.35 | 01-MAR-08:09 |
April | 0.107483E+10 | 1391.13 | 14-APR-07:10 | 0.328113E+10 | 2276.35 | 03-APR-07:10 |
May | 0.113793E+10 | 1255.34 | 03-MAY-07:10 | 0.346006E+10 | 2276.35 | 01-MAY-07:10 |
June | 0.111977E+10 | 1075.05 | 01-JUN-07:10 | 0.339359E+10 | 2276.35 | 01-JUN-07:10 |
July | 0.106051E+10 | 1075.05 | 03-JUL-07:10 | 0.334669E+10 | 2276.35 | 03-JUL-07:10 |
August | 0.118551E+10 | 1177.54 | 17-AUG-07:10 | 0.352288E+10 | 2276.35 | 01-AUG-07:10 |
September | 0.108819E+10 | 1390.83 | 11-SEP-07:10 | 0.327931E+10 | 2276.35 | 01-SEP-07:10 |
October | 0.115927E+10 | 1750.04 | 30-OCT-07:10 | 0.339814E+10 | 2276.35 | 02-OCT-07:10 |
November | 0.120360E+10 | 1750.04 | 01-NOV-07:10 | 0.332029E+10 | 2276.35 | 01-NOV-07:10 |
December | 0.121532E+10 | 1750.04 | 01-DEC-16:40 | 0.334578E+10 | 2276.35 | 01-DEC-08:09 |
Annual Sum or Average | 0.137925E+11 | 0.403429E+11 | ||||
Minimum of Months | 0.106051E+10 | 1075.05 | 0.307490E+10 | 2276.35 | ||
Maximum of Months | 0.125434E+10 | 1750.04 | 0.352288E+10 | 2276.35 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.821734E+09 | 1127.77 | 02-JAN-08:09 | 0.218926E+10 | 1466.94 | 02-JAN-08:09 |
February | 0.693159E+09 | 1020.73 | 02-FEB-08:09 | 0.198154E+10 | 1466.94 | 01-FEB-08:09 |
March | 0.795573E+09 | 1084.97 | 17-MAR-07:10 | 0.227023E+10 | 1466.94 | 01-MAR-08:09 |
April | 0.693194E+09 | 907.81 | 14-APR-07:10 | 0.211444E+10 | 1466.94 | 03-APR-07:10 |
May | 0.732165E+09 | 826.48 | 03-MAY-07:10 | 0.222974E+10 | 1466.94 | 01-MAY-07:10 |
June | 0.718936E+09 | 692.79 | 01-JUN-07:10 | 0.218691E+10 | 1466.94 | 01-JUN-07:10 |
July | 0.682446E+09 | 692.79 | 03-JUL-07:10 | 0.215669E+10 | 1466.94 | 03-JUL-07:10 |
August | 0.762821E+09 | 796.34 | 17-AUG-07:10 | 0.227023E+10 | 1466.94 | 01-AUG-07:10 |
September | 0.702773E+09 | 960.74 | 11-SEP-07:10 | 0.211327E+10 | 1466.94 | 01-SEP-07:10 |
October | 0.756547E+09 | 1127.77 | 30-OCT-07:10 | 0.218984E+10 | 1466.94 | 02-OCT-07:10 |
November | 0.785014E+09 | 1127.77 | 01-NOV-07:10 | 0.213967E+10 | 1466.94 | 01-NOV-07:10 |
December | 0.795526E+09 | 1127.77 | 01-DEC-16:40 | 0.215610E+10 | 1466.94 | 01-DEC-08:09 |
Annual Sum or Average | 0.893989E+10 | 0.259979E+11 | ||||
Minimum of Months | 0.682446E+09 | 692.79 | 0.198154E+10 | 1466.94 | ||
Maximum of Months | 0.821734E+09 | 1127.77 | 0.227023E+10 | 1466.94 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.387117E+09 | 405.10 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.351144E+09 | 405.10 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.417256E+09 | 405.10 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.372695E+09 | 405.10 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.402187E+09 | 405.10 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.400242E+09 | 405.10 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.374640E+09 | 405.10 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.417256E+09 | 405.10 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.372695E+09 | 405.10 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.387117E+09 | 405.10 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.382580E+09 | 405.10 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.374640E+09 | 405.10 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.463957E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.351144E+09 | 405.10 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.417256E+09 | 405.10 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.387117E+09 | 405.10 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.351144E+09 | 405.10 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.417256E+09 | 405.10 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.372695E+09 | 405.10 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.402187E+09 | 405.10 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.400242E+09 | 405.10 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.374640E+09 | 405.10 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.417256E+09 | 405.10 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.372695E+09 | 405.10 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.387117E+09 | 405.10 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.382580E+09 | 405.10 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.374640E+09 | 405.10 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.463957E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.351144E+09 | 405.10 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.417256E+09 | 405.10 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.387117E+09 | 405.10 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.351144E+09 | 405.10 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.417256E+09 | 405.10 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.372695E+09 | 405.10 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.402187E+09 | 405.10 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.400242E+09 | 405.10 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.374640E+09 | 405.10 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.417256E+09 | 405.10 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.372695E+09 | 405.10 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.387117E+09 | 405.10 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.382580E+09 | 405.10 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.374640E+09 | 405.10 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.463957E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.351144E+09 | 405.10 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.417256E+09 | 405.10 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.418155E+10 | 4375.82 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.379298E+10 | 4375.82 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.450711E+10 | 4375.82 | 01-MAR-08:09 | 0.762947E+12 | 379632.52 | 31-MAR-23:10 |
April | 0.402577E+10 | 4375.82 | 03-APR-07:10 | 0.982982E+12 | 379632.52 | 01-APR-00:10 |
May | 0.434433E+10 | 4375.82 | 01-MAY-07:10 | 0.254544E+12 | 189816.26 | 31-MAY-23:10 |
June | 0.432333E+10 | 4375.82 | 01-JUN-07:10 | 0.492345E+12 | 284724.39 | 30-JUN-23:10 |
July | 0.404678E+10 | 4375.82 | 03-JUL-07:10 | 0.762947E+12 | 379632.52 | 31-JUL-23:10 |
August | 0.450711E+10 | 4375.82 | 01-AUG-07:10 | 0.101578E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.402577E+10 | 4375.82 | 01-SEP-07:10 | 0.246344E+12 | 189816.26 | 30-SEP-23:10 |
October | 0.418155E+10 | 4375.82 | 02-OCT-07:10 | 0.508746E+12 | 284724.39 | 31-OCT-23:10 |
November | 0.413254E+10 | 4375.82 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.404678E+10 | 4375.82 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.501156E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.379298E+10 | 4375.82 | 0.246344E+12 | 94908.13 | ||
Maximum of Months | 0.450711E+10 | 4375.82 | 0.101681E+13 | 379632.52 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.148304E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.134523E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.159851E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.142779E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.154078E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.153333E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.143524E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.159851E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.142779E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.148304E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.146566E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.143524E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.177742E+12 | 0.424397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121482E+11 | 0.134523E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.159851E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.133188E+11 | 0.270551E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.120811E+11 | 0.244881E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.143557E+11 | 0.280558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.128226E+11 | 0.261305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.138373E+11 | 0.275555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.137704E+11 | 0.270261E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.128895E+11 | 0.266527E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.143557E+11 | 0.280558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.128226E+11 | 0.261160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.133188E+11 | 0.270624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.131627E+11 | 0.264424E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.128895E+11 | 0.266454E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.159625E+12 | 0.321286E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.120811E+11 | 0.244881E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.143557E+11 | 0.280558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.133188E+11 | 0.270550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.120811E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.143557E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.128226E+11 | 0.261304E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.138373E+11 | 0.275554E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.137704E+11 | 0.270260E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.128895E+11 | 0.266526E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.143557E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.128226E+11 | 0.261159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.133188E+11 | 0.270623E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.131627E+11 | 0.264423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.128895E+11 | 0.266453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.159625E+12 | 0.321285E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.120811E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.143557E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.133188E+11 | 0.270550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.120811E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.143557E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.128226E+11 | 0.261304E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.138373E+11 | 0.275554E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.137704E+11 | 0.270260E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.128895E+11 | 0.266526E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.143557E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.128226E+11 | 0.261159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.133188E+11 | 0.270623E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.131627E+11 | 0.264423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.128895E+11 | 0.266453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.159625E+12 | 0.321285E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.120811E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.143557E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.128837E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153365E+10 |
February | 0.136985E+10 | 0.108359E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122899E+10 |
March | 0.163685E+10 | 0.123553E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112668E+10 |
April | 0.145243E+10 | 0.107314E+10 | 0.328108E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.820381E+09 |
May | 0.157338E+10 | 0.113392E+10 | 0.346000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1840213.32 | 0.803442E+09 |
June | 0.156900E+10 | 0.111338E+10 | 0.339353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9306854.36 | 0.397971E+09 |
July | 0.145680E+10 | 0.105617E+10 | 0.334664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31639090.11 | 0.261549E+09 |
August | 0.163685E+10 | 0.118089E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26854855.83 | 0.287437E+09 |
September | 0.145243E+10 | 0.108936E+10 | 0.327926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17172057.84 | 0.530038E+09 |
October | 0.150991E+10 | 0.117754E+10 | 0.339809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 108356.43 | 0.799017E+09 |
November | 0.149516E+10 | 0.123558E+10 | 0.332024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112904E+10 |
December | 0.145680E+10 | 0.125473E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143077E+10 |
Annual Sum or Average | 0.181194E+11 | 0.139222E+11 | 0.403423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 86921427.89 | 0.103490E+11 |
Minimum of Months | 0.136985E+10 | 0.105617E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261549E+09 |
Maximum of Months | 0.163685E+10 | 0.128837E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31639090.11 | 0.153365E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.815941E+09 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102159E+10 |
February | 0.882782E+09 | 0.692587E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.820872E+09 |
March | 0.105485E+10 | 0.792080E+09 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.744646E+09 |
April | 0.936002E+09 | 0.690691E+09 | 0.211446E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.539164E+09 |
May | 0.101394E+10 | 0.732124E+09 | 0.222976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1275312.73 | 0.529223E+09 |
June | 0.101113E+10 | 0.720965E+09 | 0.218692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6331573.35 | 0.262037E+09 |
July | 0.938820E+09 | 0.681934E+09 | 0.215670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21189086.65 | 0.168416E+09 |
August | 0.105485E+10 | 0.763096E+09 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18132602.57 | 0.180974E+09 |
September | 0.936002E+09 | 0.701094E+09 | 0.211328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11191352.30 | 0.353602E+09 |
October | 0.973041E+09 | 0.750543E+09 | 0.218986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72233.52 | 0.530887E+09 |
November | 0.963541E+09 | 0.786262E+09 | 0.213969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.738436E+09 |
December | 0.938820E+09 | 0.795198E+09 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.935741E+09 |
Annual Sum or Average | 0.116768E+11 | 0.892252E+10 | 0.259981E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 58192161.12 | 0.682559E+10 |
Minimum of Months | 0.882782E+09 | 0.681934E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168416E+09 |
Maximum of Months | 0.105485E+10 | 0.815941E+09 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21189086.65 | 0.102159E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.125350E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154628E+10 |
February | 0.136988E+10 | 0.106460E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126291E+10 |
March | 0.163688E+10 | 0.122723E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113355E+10 |
April | 0.145246E+10 | 0.107432E+10 | 0.328113E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.818874E+09 |
May | 0.157341E+10 | 0.113748E+10 | 0.346006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1829842.15 | 0.793011E+09 |
June | 0.156904E+10 | 0.111929E+10 | 0.339359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9276971.78 | 0.395181E+09 |
July | 0.145684E+10 | 0.106017E+10 | 0.334669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30132911.59 | 0.260806E+09 |
August | 0.163688E+10 | 0.118500E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26243183.89 | 0.288981E+09 |
September | 0.145246E+10 | 0.108777E+10 | 0.327931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14980450.82 | 0.540720E+09 |
October | 0.150994E+10 | 0.115836E+10 | 0.339814E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 99273.26 | 0.818545E+09 |
November | 0.149520E+10 | 0.120257E+10 | 0.332029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113232E+10 |
December | 0.145684E+10 | 0.121426E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143391E+10 |
Annual Sum or Average | 0.181198E+11 | 0.137846E+11 | 0.403429E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 82562633.50 | 0.104251E+11 |
Minimum of Months | 0.136988E+10 | 0.106017E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260806E+09 |
Maximum of Months | 0.163688E+10 | 0.125350E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30132911.59 | 0.154628E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.821407E+09 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105532E+10 |
February | 0.882782E+09 | 0.692838E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.882181E+09 |
March | 0.105485E+10 | 0.795438E+09 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.809873E+09 |
April | 0.936002E+09 | 0.693037E+09 | 0.211444E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.610206E+09 |
May | 0.101394E+10 | 0.732076E+09 | 0.222974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1174720.29 | 0.571160E+09 |
June | 0.101113E+10 | 0.718797E+09 | 0.218691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6007221.20 | 0.289608E+09 |
July | 0.938820E+09 | 0.682370E+09 | 0.215669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19166033.94 | 0.199493E+09 |
August | 0.105485E+10 | 0.762666E+09 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17009009.44 | 0.217392E+09 |
September | 0.936002E+09 | 0.702495E+09 | 0.211327E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10751914.18 | 0.376907E+09 |
October | 0.973041E+09 | 0.756099E+09 | 0.218984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72237.03 | 0.578870E+09 |
November | 0.963541E+09 | 0.784537E+09 | 0.213967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.817398E+09 |
December | 0.938820E+09 | 0.795013E+09 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104359E+10 |
Annual Sum or Average | 0.116768E+11 | 0.893677E+10 | 0.259979E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 54181136.07 | 0.745200E+10 |
Minimum of Months | 0.882782E+09 | 0.682370E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199493E+09 |
Maximum of Months | 0.105485E+10 | 0.821407E+09 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19166033.94 | 0.105532E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.129037E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.326703E+10 |
February | 0.136985E+10 | 0.108521E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250862E+10 |
March | 0.163685E+10 | 0.123644E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233553E+10 |
April | 0.145243E+10 | 0.107368E+10 | 0.328108E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168280E+10 |
May | 0.157338E+10 | 0.113419E+10 | 0.346000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4070461.18 | 0.171005E+10 |
June | 0.156900E+10 | 0.111364E+10 | 0.339353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21716426.72 | 0.884710E+09 |
July | 0.145680E+10 | 0.105637E+10 | 0.334664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75956947.01 | 0.598080E+09 |
August | 0.163685E+10 | 0.118116E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62928089.05 | 0.651416E+09 |
September | 0.145243E+10 | 0.109006E+10 | 0.327926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40618442.81 | 0.113365E+10 |
October | 0.150991E+10 | 0.117892E+10 | 0.339809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1597365.09 | 0.160636E+10 |
November | 0.149516E+10 | 0.123782E+10 | 0.332024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226902E+10 |
December | 0.145680E+10 | 0.125786E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.286228E+10 |
Annual Sum or Average | 0.181194E+11 | 0.139357E+11 | 0.403423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206888E+09 | 0.215096E+11 |
Minimum of Months | 0.136985E+10 | 0.105637E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.598080E+09 |
Maximum of Months | 0.163685E+10 | 0.129037E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75956947.01 | 0.326703E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.816324E+09 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220108E+10 |
February | 0.649041E+09 | 0.692878E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171827E+10 |
March | 0.773965E+09 | 0.792288E+09 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159617E+10 |
April | 0.688021E+09 | 0.690808E+09 | 0.211446E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116640E+10 |
May | 0.744847E+09 | 0.732233E+09 | 0.222976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2832649.28 | 0.115078E+10 |
June | 0.742030E+09 | 0.721102E+09 | 0.218692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14318290.47 | 0.604436E+09 |
July | 0.690839E+09 | 0.682030E+09 | 0.215670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47346012.69 | 0.415473E+09 |
August | 0.773965E+09 | 0.763248E+09 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41093284.19 | 0.445021E+09 |
September | 0.688021E+09 | 0.701263E+09 | 0.211328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25228626.60 | 0.780895E+09 |
October | 0.715730E+09 | 0.750944E+09 | 0.218986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 159206.50 | 0.111321E+10 |
November | 0.708685E+09 | 0.786660E+09 | 0.213969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153048E+10 |
December | 0.690839E+09 | 0.795752E+09 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192507E+10 |
Annual Sum or Average | 0.858171E+10 | 0.892553E+10 | 0.259981E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130978E+09 | 0.146473E+11 |
Minimum of Months | 0.649041E+09 | 0.682030E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.415473E+09 |
Maximum of Months | 0.773965E+09 | 0.816324E+09 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47346012.69 | 0.220108E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.125433E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.343633E+10 |
February | 0.136988E+10 | 0.106529E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.277596E+10 |
March | 0.163688E+10 | 0.122799E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250714E+10 |
April | 0.145246E+10 | 0.107483E+10 | 0.328113E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180683E+10 |
May | 0.157341E+10 | 0.113793E+10 | 0.346006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3991025.38 | 0.176011E+10 |
June | 0.156904E+10 | 0.111977E+10 | 0.339359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21040184.68 | 0.898920E+09 |
July | 0.145684E+10 | 0.106051E+10 | 0.334669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68748916.11 | 0.619490E+09 |
August | 0.163688E+10 | 0.118553E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60194790.13 | 0.684315E+09 |
September | 0.145246E+10 | 0.108819E+10 | 0.327931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33468348.97 | 0.122160E+10 |
October | 0.150994E+10 | 0.115918E+10 | 0.339814E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 134473.86 | 0.181502E+10 |
November | 0.149520E+10 | 0.120358E+10 | 0.332029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246224E+10 |
December | 0.145684E+10 | 0.121530E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.305483E+10 |
Annual Sum or Average | 0.181198E+11 | 0.137924E+11 | 0.403429E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187578E+09 | 0.230428E+11 |
Minimum of Months | 0.136988E+10 | 0.106051E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.619490E+09 |
Maximum of Months | 0.163688E+10 | 0.125433E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68748916.11 | 0.343633E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.821729E+09 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222552E+10 |
February | 0.882782E+09 | 0.693153E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175542E+10 |
March | 0.105485E+10 | 0.795570E+09 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162381E+10 |
April | 0.936002E+09 | 0.693186E+09 | 0.211444E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120600E+10 |
May | 0.101394E+10 | 0.732164E+09 | 0.222974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2617137.94 | 0.121173E+10 |
June | 0.101113E+10 | 0.718932E+09 | 0.218691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13806802.91 | 0.624987E+09 |
July | 0.938820E+09 | 0.682445E+09 | 0.215669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46875911.66 | 0.441253E+09 |
August | 0.105485E+10 | 0.762817E+09 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40596190.44 | 0.463812E+09 |
September | 0.936002E+09 | 0.702771E+09 | 0.211327E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25517166.06 | 0.794837E+09 |
October | 0.973041E+09 | 0.756535E+09 | 0.218984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 220793.16 | 0.113353E+10 |
November | 0.963541E+09 | 0.784997E+09 | 0.213967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156946E+10 |
December | 0.938820E+09 | 0.795514E+09 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196278E+10 |
Annual Sum or Average | 0.116768E+11 | 0.893981E+10 | 0.259979E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129634E+09 | 0.150131E+11 |
Minimum of Months | 0.882782E+09 | 0.682445E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.441253E+09 |
Maximum of Months | 0.105485E+10 | 0.821729E+09 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46875911.66 | 0.222552E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.129037E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.395457E+10 |
February | 0.136985E+10 | 0.108522E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.292092E+10 |
March | 0.163685E+10 | 0.123644E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.272289E+10 |
April | 0.145243E+10 | 0.107368E+10 | 0.328108E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189976E+10 |
May | 0.157338E+10 | 0.113419E+10 | 0.346000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4884995.42 | 0.198372E+10 |
June | 0.156900E+10 | 0.111364E+10 | 0.339353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26052390.13 | 0.105890E+10 |
July | 0.145680E+10 | 0.105637E+10 | 0.334664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 92288695.30 | 0.721036E+09 |
August | 0.163685E+10 | 0.118115E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75856839.78 | 0.776013E+09 |
September | 0.145243E+10 | 0.109006E+10 | 0.327926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49148558.88 | 0.129941E+10 |
October | 0.150991E+10 | 0.117894E+10 | 0.339809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6039202.46 | 0.174803E+10 |
November | 0.149516E+10 | 0.123784E+10 | 0.332024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.259270E+10 |
December | 0.145680E+10 | 0.125790E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.343048E+10 |
Annual Sum or Average | 0.181194E+11 | 0.139358E+11 | 0.403423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254271E+09 | 0.251084E+11 |
Minimum of Months | 0.136985E+10 | 0.105637E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.721036E+09 |
Maximum of Months | 0.163685E+10 | 0.129037E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 92288695.30 | 0.395457E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.816325E+09 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.265614E+10 |
February | 0.882782E+09 | 0.692886E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199067E+10 |
March | 0.105485E+10 | 0.792246E+09 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186407E+10 |
April | 0.936002E+09 | 0.690808E+09 | 0.211446E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133799E+10 |
May | 0.101394E+10 | 0.732236E+09 | 0.222976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3277290.30 | 0.135214E+10 |
June | 0.101113E+10 | 0.721105E+09 | 0.218692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16922002.21 | 0.736921E+09 |
July | 0.938820E+09 | 0.682032E+09 | 0.215670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55811344.16 | 0.510936E+09 |
August | 0.105485E+10 | 0.763250E+09 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49109842.99 | 0.541612E+09 |
September | 0.936002E+09 | 0.701265E+09 | 0.211328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29246139.40 | 0.916576E+09 |
October | 0.973041E+09 | 0.750953E+09 | 0.218986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 754404.43 | 0.123056E+10 |
November | 0.963541E+09 | 0.786829E+09 | 0.213969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174926E+10 |
December | 0.938820E+09 | 0.795767E+09 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229864E+10 |
Annual Sum or Average | 0.116768E+11 | 0.892570E+10 | 0.259981E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155121E+09 | 0.171855E+11 |
Minimum of Months | 0.882782E+09 | 0.682032E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.510936E+09 |
Maximum of Months | 0.105485E+10 | 0.816325E+09 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55811344.16 | 0.265614E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.125434E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.407916E+10 |
February | 0.136988E+10 | 0.106529E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.319381E+10 |
March | 0.163688E+10 | 0.122799E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.292130E+10 |
April | 0.145246E+10 | 0.107483E+10 | 0.328113E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206882E+10 |
May | 0.157341E+10 | 0.113793E+10 | 0.346006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4695790.64 | 0.205817E+10 |
June | 0.156904E+10 | 0.111977E+10 | 0.339359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25147621.18 | 0.108354E+10 |
July | 0.145684E+10 | 0.106051E+10 | 0.334669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 82541530.67 | 0.752874E+09 |
August | 0.163688E+10 | 0.118551E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72575009.49 | 0.827453E+09 |
September | 0.145246E+10 | 0.108819E+10 | 0.327931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40038017.21 | 0.143075E+10 |
October | 0.150994E+10 | 0.115927E+10 | 0.339814E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 219857.25 | 0.203333E+10 |
November | 0.149520E+10 | 0.120360E+10 | 0.332029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.278824E+10 |
December | 0.145684E+10 | 0.121532E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.357034E+10 |
Annual Sum or Average | 0.181198E+11 | 0.137925E+11 | 0.403429E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225218E+09 | 0.268078E+11 |
Minimum of Months | 0.136988E+10 | 0.106051E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.752874E+09 |
Maximum of Months | 0.163688E+10 | 0.125434E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 82541530.67 | 0.407916E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.821734E+09 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.267467E+10 |
February | 0.882782E+09 | 0.693159E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204693E+10 |
March | 0.105485E+10 | 0.795573E+09 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190956E+10 |
April | 0.936002E+09 | 0.693194E+09 | 0.211444E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139271E+10 |
May | 0.101394E+10 | 0.732165E+09 | 0.222974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3090408.01 | 0.142490E+10 |
June | 0.101113E+10 | 0.718936E+09 | 0.218691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16653086.75 | 0.756960E+09 |
July | 0.938820E+09 | 0.682446E+09 | 0.215669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56784188.99 | 0.538445E+09 |
August | 0.105485E+10 | 0.762821E+09 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49170485.27 | 0.561668E+09 |
September | 0.936002E+09 | 0.702773E+09 | 0.211327E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30637155.01 | 0.931535E+09 |
October | 0.973041E+09 | 0.756547E+09 | 0.218984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 910226.57 | 0.127577E+10 |
November | 0.963541E+09 | 0.785014E+09 | 0.213967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180904E+10 |
December | 0.938820E+09 | 0.795526E+09 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233702E+10 |
Annual Sum or Average | 0.116768E+11 | 0.893989E+10 | 0.259979E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157246E+09 | 0.176592E+11 |
Minimum of Months | 0.882782E+09 | 0.682446E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.538445E+09 |
Maximum of Months | 0.105485E+10 | 0.821734E+09 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56784188.99 | 0.267467E+10 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.387117E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.351144E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.417256E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.372695E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.402187E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.400242E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.374640E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.417256E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.372695E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.387117E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.382580E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.374640E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.463957E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.351144E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.417256E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.387117E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.351144E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.417256E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.372695E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.402187E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.400242E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.374640E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.417256E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.372695E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.387117E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.382580E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.374640E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.463957E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.351144E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.417256E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.387117E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.351144E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.417256E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.372695E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.402187E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.400242E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.374640E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.417256E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.372695E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.387117E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.382580E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.374640E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.463957E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.351144E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.417256E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.377547E+10 | 0.418155E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.342526E+10 | 0.379298E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409289E+10 | 0.450711E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363176E+10 | 0.402577E+10 | 0.982982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.393418E+10 | 0.434433E+10 | 0.254544E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.392325E+10 | 0.432333E+10 | 0.492345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.364269E+10 | 0.404678E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.409289E+10 | 0.450711E+10 | 0.101578E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.363176E+10 | 0.402577E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.377547E+10 | 0.418155E+10 | 0.508746E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373861E+10 | 0.413254E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364269E+10 | 0.404678E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453069E+11 | 0.501156E+11 | 0.749486E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.342526E+10 | 0.379298E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.409289E+10 | 0.450711E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.326632E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.262818E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238389E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172691E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2902900.25 | 0.167927E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15225703.17 | 0.828687E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58345797.77 | 0.552646E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49562374.94 | 0.614126E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32941417.44 | 0.112659E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68894.38 | 0.169930E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241132E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.306389E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159047E+09 | 0.219811E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.552646E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58345797.77 | 0.326632E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.545443E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.433600E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.401305E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291990E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5465409.36 | 0.289304E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27958651.58 | 0.145312E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108498E+09 | 0.976986E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90573807.45 | 0.108561E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60996046.72 | 0.196257E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167153.46 | 0.286116E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.399437E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.496339E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293659E+09 | 0.369136E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.976986E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108498E+09 | 0.545443E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.575320E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.445620E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.420411E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.304553E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3319317.10 | 0.313090E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22927947.34 | 0.165604E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93321815.95 | 0.112410E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84474552.66 | 0.122167E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51486393.81 | 0.208873E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.284359E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.397199E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.506011E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.255530E+09 | 0.385562E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112410E+10 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93321815.95 | 0.575320E+10 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 15519.45 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 15519.45 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 15519.45 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 15519.45 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 15519.45 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 15519.45 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 15519.45 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 15519.45 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 15519.45 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 15519.45 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 15519.45 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 15519.45 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 17832.21 | 15519.45 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 15519.45 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 13937.56 | 02-JAN-08:09 | 18128.59 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 13937.56 | 01-FEB-08:09 | 18128.59 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 13937.56 | 01-MAR-08:09 | 18128.59 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 13937.56 | 03-APR-07:10 | 18128.59 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 13937.56 | 01-MAY-07:10 | 18128.59 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 13937.56 | 01-JUN-07:10 | 18128.59 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 13937.56 | 03-JUL-07:10 | 18128.59 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 13937.56 | 01-AUG-07:10 | 18128.59 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 13937.56 | 01-SEP-07:10 | 18128.59 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 13937.56 | 02-OCT-07:10 | 18128.59 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 13937.56 | 01-NOV-07:10 | 18128.59 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 13937.56 | 01-DEC-08:09 | 18128.59 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 13937.56 | 18128.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 13937.56 | 18128.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 13937.56 | 02-JAN-08:09 | 18128.52 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 13937.56 | 01-FEB-08:09 | 18128.52 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 13937.56 | 01-MAR-08:09 | 18128.52 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 13937.56 | 03-APR-07:10 | 18128.52 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 13937.56 | 01-MAY-07:10 | 18128.52 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 13937.56 | 01-JUN-07:10 | 18128.52 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 13937.56 | 03-JUL-07:10 | 18128.52 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 13937.56 | 01-AUG-07:10 | 18128.52 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 13937.56 | 01-SEP-07:10 | 18128.52 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 13937.56 | 02-OCT-07:10 | 18128.52 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 13937.56 | 01-NOV-07:10 | 18128.52 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 13937.56 | 01-DEC-08:09 | 18128.52 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 13937.56 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 13937.56 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 13937.56 | 02-JAN-08:09 | 18128.52 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 13937.56 | 01-FEB-08:09 | 18128.52 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 13937.56 | 01-MAR-08:09 | 18128.52 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 13937.56 | 03-APR-07:10 | 18128.52 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 13937.56 | 01-MAY-07:10 | 18128.52 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 13937.56 | 01-JUN-07:10 | 18128.52 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 13937.56 | 03-JUL-07:10 | 18128.52 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 13937.56 | 01-AUG-07:10 | 18128.52 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 13937.56 | 01-SEP-07:10 | 18128.52 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 13937.56 | 02-OCT-07:10 | 18128.52 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 13937.56 | 01-NOV-07:10 | 18128.52 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 13937.56 | 01-DEC-08:09 | 18128.52 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 13937.56 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 13937.56 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1750.00 | 02-JAN-08:09 | 2276.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2513.01 | 05-JAN-22:01 |
February | 2010.79 | 01-FEB-10:09 | 1574.71 | 01-FEB-08:09 | 2276.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 1584.86 | 17-FEB-03:55 |
March | 2010.79 | 01-MAR-10:09 | 1683.15 | 17-MAR-07:10 | 2276.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1929.87 | 02-MAR-23:00 |
April | 2010.79 | 03-APR-09:09 | 1382.47 | 14-APR-07:10 | 2276.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1383.72 | 27-APR-02:00 |
May | 2010.79 | 01-MAY-09:09 | 1232.40 | 03-MAY-07:10 | 2276.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 103.62 | 20-MAY-17:03 | 2614.44 | 22-MAY-03:55 |
June | 2010.79 | 01-JUN-09:09 | 1075.02 | 01-JUN-07:10 | 2276.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 127.69 | 29-JUN-15:00 | 1108.24 | 14-JUN-02:00 |
July | 2010.79 | 03-JUL-09:09 | 1075.02 | 03-JUL-07:10 | 2276.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 261.23 | 30-JUL-12:00 | 667.30 | 05-JUL-00:53 |
August | 2010.79 | 01-AUG-09:09 | 1075.02 | 01-AUG-07:10 | 2276.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 326.31 | 06-AUG-17:45 | 854.79 | 23-AUG-03:00 |
September | 2010.79 | 01-SEP-09:09 | 1407.20 | 11-SEP-07:10 | 2276.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 388.93 | 03-SEP-13:00 | 1478.01 | 12-SEP-03:00 |
October | 2010.79 | 02-OCT-09:09 | 1750.00 | 30-OCT-07:10 | 2276.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.99 | 18-OCT-14:00 | 1263.51 | 30-OCT-22:00 |
November | 2010.79 | 01-NOV-09:09 | 1750.00 | 01-NOV-07:10 | 2276.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1505.87 | 28-NOV-05:51 |
December | 2010.79 | 01-DEC-10:09 | 1750.00 | 01-DEC-16:40 | 2276.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2342.04 | 01-DEC-04:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 667.30 | |||||
Maximum of Months | 2010.79 | 1750.00 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 388.93 | 2614.44 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1127.77 | 02-JAN-08:09 | 1466.95 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1674.83 | 05-JAN-22:01 |
February | 1295.83 | 01-FEB-10:09 | 980.15 | 01-FEB-16:00 | 1466.95 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 1038.09 | 17-FEB-03:55 |
March | 1295.83 | 01-MAR-10:09 | 1084.69 | 17-MAR-07:10 | 1466.95 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1264.06 | 02-MAR-23:00 |
April | 1295.83 | 03-APR-09:09 | 863.77 | 14-APR-07:10 | 1466.95 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 905.98 | 27-APR-02:00 |
May | 1295.83 | 01-MAY-09:09 | 692.79 | 01-MAY-07:10 | 1466.95 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.58 | 20-MAY-17:03 | 1718.97 | 22-MAY-04:30 |
June | 1295.83 | 01-JUN-09:09 | 692.79 | 01-JUN-07:10 | 1466.95 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 85.13 | 29-JUN-15:00 | 720.73 | 14-JUN-02:00 |
July | 1295.83 | 03-JUL-09:09 | 692.79 | 03-JUL-07:10 | 1466.95 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 173.14 | 30-JUL-14:20 | 431.16 | 05-JUL-00:53 |
August | 1295.83 | 01-AUG-09:09 | 692.79 | 01-AUG-07:10 | 1466.95 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 227.77 | 06-AUG-17:50 | 550.70 | 23-AUG-03:00 |
September | 1295.83 | 01-SEP-09:09 | 823.04 | 13-SEP-07:10 | 1466.95 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 251.85 | 03-SEP-13:00 | 970.60 | 12-SEP-03:00 |
October | 1295.83 | 02-OCT-09:09 | 1127.77 | 30-OCT-07:10 | 1466.95 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.99 | 18-OCT-14:00 | 828.56 | 30-OCT-22:00 |
November | 1295.83 | 01-NOV-09:09 | 1127.77 | 01-NOV-07:10 | 1466.95 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1003.92 | 28-NOV-06:00 |
December | 1295.83 | 01-DEC-10:09 | 1127.77 | 01-DEC-16:40 | 1466.95 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1511.39 | 01-DEC-04:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 431.16 | |||||
Maximum of Months | 1295.83 | 1127.77 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 251.85 | 1718.97 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1750.04 | 02-JAN-08:09 | 2276.35 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2511.94 | 05-JAN-22:01 |
February | 2010.83 | 01-FEB-10:09 | 1430.76 | 02-FEB-08:09 | 2276.35 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 1558.51 | 17-FEB-03:55 |
March | 2010.83 | 01-MAR-10:09 | 1683.19 | 17-MAR-07:10 | 2276.35 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1959.41 | 02-MAR-23:00 |
April | 2010.83 | 03-APR-09:09 | 1380.38 | 14-APR-07:10 | 2276.35 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1369.01 | 27-APR-02:00 |
May | 2010.83 | 01-MAY-09:09 | 1240.79 | 03-MAY-07:10 | 2276.35 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 100.54 | 20-MAY-17:03 | 2532.33 | 22-MAY-04:30 |
June | 2010.83 | 01-JUN-09:09 | 1075.05 | 01-JUN-07:10 | 2276.35 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 127.69 | 29-JUN-15:00 | 1089.13 | 14-JUN-02:00 |
July | 2010.83 | 03-JUL-09:09 | 1075.05 | 03-JUL-07:10 | 2276.35 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 240.41 | 30-JUL-14:18 | 654.62 | 05-JUL-00:53 |
August | 2010.83 | 01-AUG-09:09 | 1075.05 | 01-AUG-07:10 | 2276.35 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 331.58 | 06-AUG-17:45 | 852.96 | 23-AUG-03:00 |
September | 2010.83 | 01-SEP-09:09 | 1379.90 | 11-SEP-07:10 | 2276.35 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 351.25 | 03-SEP-12:53 | 1437.19 | 12-SEP-03:00 |
October | 2010.83 | 02-OCT-09:09 | 1750.04 | 30-OCT-07:10 | 2276.35 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.89 | 18-OCT-14:30 | 1283.93 | 30-OCT-22:00 |
November | 2010.83 | 01-NOV-09:09 | 1750.04 | 01-NOV-07:10 | 2276.35 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1505.87 | 28-NOV-05:59 |
December | 2010.83 | 01-DEC-10:09 | 1750.04 | 01-DEC-16:40 | 2276.35 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2257.31 | 01-DEC-04:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1075.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 654.62 | |||||
Maximum of Months | 2010.83 | 1750.04 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 351.25 | 2532.33 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1127.77 | 02-JAN-08:09 | 1466.94 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1677.05 | 05-JAN-22:01 |
February | 1295.83 | 01-FEB-10:09 | 1019.45 | 02-FEB-08:09 | 1466.94 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 1130.81 | 17-FEB-03:55 |
March | 1295.83 | 01-MAR-10:09 | 1084.69 | 17-MAR-07:10 | 1466.94 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1378.91 | 02-MAR-23:00 |
April | 1295.83 | 03-APR-09:09 | 906.34 | 14-APR-07:10 | 1466.94 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1011.08 | 27-APR-02:00 |
May | 1295.83 | 01-MAY-09:09 | 824.48 | 03-MAY-07:10 | 1466.94 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.23 | 20-MAY-17:03 | 1771.21 | 22-MAY-04:30 |
June | 1295.83 | 01-JUN-09:09 | 692.79 | 01-JUN-07:10 | 1466.94 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 85.13 | 29-JUN-15:00 | 804.02 | 14-JUN-02:00 |
July | 1295.83 | 03-JUL-09:09 | 692.79 | 03-JUL-07:10 | 1466.94 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 164.01 | 30-JUL-12:00 | 501.25 | 05-JUL-00:53 |
August | 1295.83 | 01-AUG-09:09 | 794.12 | 17-AUG-07:10 | 1466.94 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 217.44 | 06-AUG-17:43 | 666.54 | 23-AUG-03:00 |
September | 1295.83 | 01-SEP-09:09 | 959.61 | 11-SEP-07:10 | 1466.94 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 260.92 | 03-SEP-12:51 | 1021.20 | 12-SEP-03:00 |
October | 1295.83 | 02-OCT-09:09 | 1127.77 | 30-OCT-07:10 | 1466.94 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.99 | 18-OCT-14:00 | 903.26 | 30-OCT-22:10 |
November | 1295.83 | 01-NOV-09:09 | 1127.77 | 01-NOV-07:10 | 1466.94 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1067.17 | 26-NOV-19:52 |
December | 1295.83 | 01-DEC-10:09 | 1127.77 | 01-DEC-16:40 | 1466.94 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1714.31 | 01-DEC-04:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 692.79 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 501.25 | |||||
Maximum of Months | 1295.83 | 1127.77 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 260.92 | 1771.21 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1750.00 | 02-JAN-08:09 | 2276.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 5880.36 | 05-JAN-22:01 |
February | 2010.79 | 01-FEB-10:09 | 1581.11 | 01-FEB-08:09 | 2276.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 3239.74 | 08-FEB-22:01 |
March | 2010.79 | 01-MAR-10:09 | 1685.17 | 17-MAR-07:10 | 2276.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4104.03 | 02-MAR-23:00 |
April | 2010.79 | 03-APR-09:09 | 1393.49 | 14-APR-07:10 | 2276.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2912.21 | 27-APR-02:00 |
May | 2010.79 | 01-MAY-09:09 | 1247.76 | 03-MAY-07:10 | 2276.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 247.60 | 20-MAY-17:03 | 5691.64 | 22-MAY-04:57 |
June | 2010.79 | 01-JUN-09:09 | 1075.02 | 01-JUN-07:10 | 2276.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 295.49 | 29-JUN-15:00 | 2337.56 | 14-JUN-02:00 |
July | 2010.79 | 03-JUL-09:09 | 1075.02 | 03-JUL-07:10 | 2276.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 649.82 | 30-JUL-12:00 | 1402.51 | 05-JUL-00:53 |
August | 2010.79 | 01-AUG-09:09 | 1075.02 | 01-AUG-07:10 | 2276.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 734.47 | 06-AUG-17:31 | 1736.18 | 23-AUG-03:00 |
September | 2010.79 | 01-SEP-09:09 | 1417.27 | 11-SEP-07:10 | 2276.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 903.80 | 03-SEP-13:00 | 3040.34 | 12-SEP-03:00 |
October | 2010.79 | 02-OCT-09:09 | 1750.00 | 30-OCT-07:10 | 2276.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 200.85 | 15-OCT-13:51 | 2575.91 | 30-OCT-22:00 |
November | 2010.79 | 01-NOV-09:09 | 1750.00 | 01-NOV-07:10 | 2276.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3518.78 | 28-NOV-05:50 |
December | 2010.79 | 01-DEC-10:09 | 1750.00 | 01-DEC-16:40 | 2276.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 5043.25 | 01-DEC-05:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1402.51 | |||||
Maximum of Months | 2010.79 | 1750.00 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 903.80 | 5880.36 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 1127.77 | 02-JAN-08:09 | 1466.95 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3919.59 | 05-JAN-22:01 |
February | 1239.33 | 01-FEB-08:09 | 983.59 | 01-FEB-16:00 | 1466.95 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 2159.34 | 08-FEB-22:01 |
March | 1239.33 | 01-MAR-08:09 | 1085.02 | 17-MAR-07:10 | 1466.95 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2733.23 | 02-MAR-23:00 |
April | 1239.33 | 03-APR-07:10 | 867.06 | 14-APR-07:10 | 1466.95 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1952.42 | 27-APR-02:00 |
May | 1239.33 | 01-MAY-07:10 | 692.79 | 01-MAY-07:10 | 1466.95 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 182.71 | 20-MAY-17:03 | 3794.47 | 22-MAY-05:00 |
June | 1239.33 | 01-JUN-07:10 | 692.79 | 01-JUN-07:10 | 1466.95 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 196.99 | 29-JUN-15:00 | 1536.80 | 14-JUN-02:00 |
July | 1239.33 | 03-JUL-07:10 | 692.79 | 03-JUL-07:10 | 1466.95 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 397.14 | 30-JUL-15:00 | 935.99 | 05-JUL-00:53 |
August | 1239.33 | 01-AUG-07:10 | 692.79 | 01-AUG-07:10 | 1466.95 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 516.88 | 06-AUG-17:31 | 1162.31 | 23-AUG-03:00 |
September | 1239.33 | 01-SEP-07:10 | 827.35 | 13-SEP-07:10 | 1466.95 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 605.00 | 03-SEP-12:54 | 1997.82 | 12-SEP-03:00 |
October | 1239.33 | 02-OCT-07:10 | 1127.77 | 30-OCT-07:10 | 1466.95 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.25 | 15-OCT-14:10 | 1726.00 | 30-OCT-22:00 |
November | 1239.33 | 01-NOV-07:10 | 1127.77 | 01-NOV-07:10 | 1466.95 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2352.78 | 28-NOV-05:47 |
December | 1239.33 | 01-DEC-08:09 | 1127.77 | 01-DEC-16:40 | 1466.95 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3362.18 | 01-DEC-05:06 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1239.33 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 935.99 | |||||
Maximum of Months | 1239.33 | 1127.77 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 605.00 | 3919.59 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1750.04 | 02-JAN-08:09 | 2276.35 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 5882.55 | 05-JAN-22:01 |
February | 2010.83 | 01-FEB-10:09 | 1441.85 | 02-FEB-08:09 | 2276.35 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 3360.64 | 19-FEB-13:00 |
March | 2010.83 | 01-MAR-10:09 | 1685.21 | 17-MAR-07:10 | 2276.35 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4309.33 | 02-MAR-23:00 |
April | 2010.83 | 03-APR-09:09 | 1391.48 | 14-APR-07:10 | 2276.35 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2956.66 | 27-APR-02:00 |
May | 2010.83 | 01-MAY-09:09 | 1255.83 | 03-MAY-07:10 | 2276.35 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 232.14 | 20-MAY-17:03 | 5695.47 | 22-MAY-04:47 |
June | 2010.83 | 01-JUN-09:09 | 1075.05 | 01-JUN-07:10 | 2276.35 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 295.49 | 29-JUN-15:00 | 2328.15 | 14-JUN-02:00 |
July | 2010.83 | 03-JUL-09:09 | 1075.05 | 03-JUL-07:10 | 2276.35 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 543.94 | 30-JUL-14:18 | 1420.90 | 05-JUL-00:53 |
August | 2010.83 | 01-AUG-09:09 | 1178.04 | 17-AUG-07:10 | 2276.35 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 745.02 | 06-AUG-17:24 | 1790.26 | 23-AUG-03:00 |
September | 2010.83 | 01-SEP-09:09 | 1391.00 | 11-SEP-07:10 | 2276.35 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 810.14 | 03-SEP-12:58 | 3040.47 | 12-SEP-03:00 |
October | 2010.83 | 02-OCT-09:09 | 1750.04 | 30-OCT-07:10 | 2276.35 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.96 | 18-OCT-15:00 | 2781.80 | 30-OCT-22:00 |
November | 2010.83 | 01-NOV-09:09 | 1750.04 | 01-NOV-07:10 | 2276.35 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3529.02 | 28-NOV-05:50 |
December | 2010.83 | 01-DEC-10:09 | 1750.04 | 01-DEC-16:40 | 2276.35 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 5043.22 | 01-DEC-05:07 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1075.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1420.90 | |||||
Maximum of Months | 2010.83 | 1750.04 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 810.14 | 5882.55 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1127.77 | 02-JAN-08:09 | 1466.94 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3920.36 | 05-JAN-22:01 |
February | 1295.83 | 01-FEB-10:09 | 1020.75 | 02-FEB-08:09 | 1466.94 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 2173.57 | 17-FEB-05:45 |
March | 1295.83 | 01-MAR-10:09 | 1085.02 | 17-MAR-07:10 | 1466.94 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2834.41 | 02-MAR-23:00 |
April | 1295.83 | 03-APR-09:09 | 908.02 | 14-APR-07:10 | 1466.94 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1987.33 | 27-APR-02:00 |
May | 1295.83 | 01-MAY-09:09 | 826.78 | 03-MAY-07:10 | 1466.94 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 152.55 | 20-MAY-17:03 | 3794.47 | 22-MAY-04:53 |
June | 1295.83 | 01-JUN-09:09 | 692.79 | 01-JUN-07:10 | 1466.94 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 196.99 | 29-JUN-15:00 | 1593.84 | 14-JUN-02:00 |
July | 1295.83 | 03-JUL-09:09 | 692.79 | 03-JUL-07:10 | 1466.94 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 479.55 | 30-JUL-12:00 | 1005.74 | 05-JUL-00:53 |
August | 1295.83 | 01-AUG-09:09 | 796.65 | 17-AUG-07:10 | 1466.94 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 484.60 | 06-AUG-12:10 | 1207.00 | 23-AUG-03:00 |
September | 1295.83 | 01-SEP-09:09 | 960.86 | 11-SEP-07:10 | 1466.94 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 634.25 | 03-SEP-13:00 | 2005.68 | 12-SEP-03:00 |
October | 1295.83 | 02-OCT-09:09 | 1127.77 | 30-OCT-07:10 | 1466.94 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.89 | 15-OCT-12:50 | 1778.65 | 30-OCT-22:00 |
November | 1295.83 | 01-NOV-09:09 | 1127.77 | 01-NOV-07:10 | 1466.94 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2352.74 | 28-NOV-05:50 |
December | 1295.83 | 01-DEC-10:09 | 1127.77 | 01-DEC-16:40 | 1466.94 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3362.17 | 01-DEC-05:09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 692.79 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1005.74 | |||||
Maximum of Months | 1295.83 | 1127.77 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 634.25 | 3920.36 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1750.00 | 02-JAN-08:09 | 2276.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 7290.47 | 05-JAN-22:01 |
February | 2010.79 | 01-FEB-10:09 | 1581.30 | 01-FEB-08:09 | 2276.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 4020.08 | 08-FEB-22:01 |
March | 2010.79 | 01-MAR-10:09 | 1685.09 | 17-MAR-07:10 | 2276.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4958.03 | 17-MAR-04:47 |
April | 2010.79 | 03-APR-09:09 | 1393.14 | 14-APR-07:10 | 2276.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 3319.21 | 27-APR-02:00 |
May | 2010.79 | 01-MAY-09:09 | 1247.27 | 03-MAY-07:10 | 2276.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 291.80 | 20-MAY-17:03 | 7101.99 | 22-MAY-04:47 |
June | 2010.79 | 01-JUN-09:09 | 1075.02 | 01-JUN-07:10 | 2276.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 361.93 | 29-JUN-15:00 | 2692.95 | 14-JUN-02:00 |
July | 2010.79 | 03-JUL-09:09 | 1075.02 | 03-JUL-07:10 | 2276.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 810.08 | 30-JUL-12:00 | 1605.80 | 05-JUL-00:53 |
August | 2010.79 | 01-AUG-09:09 | 1075.02 | 01-AUG-07:10 | 2276.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 901.79 | 06-AUG-17:35 | 2013.07 | 22-AUG-21:10 |
September | 2010.79 | 01-SEP-09:09 | 1417.09 | 11-SEP-07:10 | 2276.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1095.08 | 03-SEP-12:51 | 3306.41 | 12-SEP-03:00 |
October | 2010.79 | 02-OCT-09:09 | 1750.00 | 30-OCT-07:10 | 2276.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 464.87 | 15-OCT-13:53 | 3154.66 | 30-OCT-21:03 |
November | 2010.79 | 01-NOV-09:09 | 1750.00 | 01-NOV-07:10 | 2276.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 4304.26 | 28-NOV-06:00 |
December | 2010.79 | 01-DEC-10:09 | 1750.00 | 01-DEC-16:40 | 2276.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 5964.80 | 01-DEC-05:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1605.80 | |||||
Maximum of Months | 2010.79 | 1750.00 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 1095.08 | 7290.47 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1127.77 | 02-JAN-08:09 | 1466.95 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 4860.54 | 05-JAN-22:01 |
February | 1295.83 | 01-FEB-10:09 | 983.79 | 01-FEB-16:00 | 1466.95 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 2679.40 | 08-FEB-22:01 |
March | 1295.83 | 01-MAR-10:09 | 1084.97 | 17-MAR-07:10 | 1466.95 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3305.45 | 17-MAR-04:45 |
April | 1295.83 | 03-APR-09:09 | 866.88 | 14-APR-07:10 | 1466.95 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2246.70 | 27-APR-02:00 |
May | 1295.83 | 01-MAY-09:09 | 692.79 | 01-MAY-07:10 | 1466.95 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 204.32 | 20-MAY-17:03 | 4734.91 | 22-MAY-04:50 |
June | 1295.83 | 01-JUN-09:09 | 692.79 | 01-JUN-07:10 | 1466.95 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 241.28 | 29-JUN-15:00 | 1900.75 | 04-JUN-13:53 |
July | 1295.83 | 03-JUL-09:09 | 692.79 | 03-JUL-07:10 | 1466.95 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 495.51 | 30-JUL-12:00 | 1077.05 | 05-JUL-00:53 |
August | 1295.83 | 01-AUG-09:09 | 692.79 | 01-AUG-07:10 | 1466.95 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 615.65 | 06-AUG-17:40 | 1348.17 | 22-AUG-21:10 |
September | 1295.83 | 01-SEP-09:09 | 827.19 | 13-SEP-07:10 | 1466.95 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 701.69 | 03-SEP-13:04 | 2186.13 | 12-SEP-03:00 |
October | 1295.83 | 02-OCT-09:09 | 1127.77 | 30-OCT-07:10 | 1466.95 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 123.90 | 15-OCT-13:50 | 2106.89 | 30-OCT-21:03 |
November | 1295.83 | 01-NOV-09:09 | 1127.77 | 01-NOV-07:10 | 1466.95 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2948.74 | 28-NOV-06:00 |
December | 1295.83 | 01-DEC-10:09 | 1127.77 | 01-DEC-16:40 | 1466.95 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4198.50 | 01-DEC-05:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1077.05 | |||||
Maximum of Months | 1295.83 | 1127.77 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 701.69 | 4860.54 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1750.04 | 02-JAN-08:09 | 2276.35 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 7294.07 | 05-JAN-22:01 |
February | 2010.83 | 01-FEB-10:09 | 1441.95 | 02-FEB-08:09 | 2276.35 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 4033.42 | 08-FEB-22:01 |
March | 2010.83 | 01-MAR-10:09 | 1685.13 | 17-MAR-07:10 | 2276.35 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 5070.86 | 02-MAR-23:00 |
April | 2010.83 | 03-APR-09:09 | 1391.13 | 14-APR-07:10 | 2276.35 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 3398.09 | 27-APR-02:00 |
May | 2010.83 | 01-MAY-09:09 | 1255.34 | 03-MAY-07:10 | 2276.35 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 262.52 | 20-MAY-17:03 | 7101.86 | 22-MAY-04:50 |
June | 2010.83 | 01-JUN-09:09 | 1075.05 | 01-JUN-07:10 | 2276.35 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 361.92 | 29-JUN-15:00 | 2680.50 | 14-JUN-02:00 |
July | 2010.83 | 03-JUL-09:09 | 1075.05 | 03-JUL-07:10 | 2276.35 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 701.31 | 30-JUL-12:00 | 1633.70 | 05-JUL-00:53 |
August | 2010.83 | 01-AUG-09:09 | 1177.54 | 17-AUG-07:10 | 2276.35 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 919.68 | 06-AUG-17:35 | 2102.60 | 22-AUG-21:10 |
September | 2010.83 | 01-SEP-09:09 | 1390.83 | 11-SEP-07:10 | 2276.35 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 935.66 | 03-SEP-13:10 | 3313.38 | 12-SEP-03:00 |
October | 2010.83 | 02-OCT-09:09 | 1750.04 | 30-OCT-07:10 | 2276.35 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.16 | 18-OCT-14:10 | 3211.80 | 30-OCT-21:03 |
November | 2010.83 | 01-NOV-09:09 | 1750.04 | 01-NOV-07:10 | 2276.35 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 4423.28 | 28-NOV-05:59 |
December | 2010.83 | 01-DEC-10:09 | 1750.04 | 01-DEC-16:40 | 2276.35 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 6297.82 | 01-DEC-05:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1075.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1633.70 | |||||
Maximum of Months | 2010.83 | 1750.04 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 935.66 | 7294.07 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1127.77 | 02-JAN-08:09 | 1466.94 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 4861.75 | 05-JAN-22:01 |
February | 1295.83 | 01-FEB-10:09 | 1020.73 | 02-FEB-08:09 | 1466.94 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 2685.89 | 08-FEB-22:01 |
March | 1295.83 | 01-MAR-10:09 | 1084.97 | 17-MAR-07:10 | 1466.94 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3355.28 | 02-MAR-23:00 |
April | 1295.83 | 03-APR-09:09 | 907.81 | 14-APR-07:10 | 1466.94 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2287.56 | 27-APR-02:00 |
May | 1295.83 | 01-MAY-09:09 | 826.48 | 03-MAY-07:10 | 1466.94 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 174.13 | 20-MAY-17:03 | 4734.71 | 22-MAY-04:43 |
June | 1295.83 | 01-JUN-09:09 | 692.79 | 01-JUN-07:10 | 1466.94 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 241.28 | 29-JUN-15:00 | 1847.19 | 14-JUN-02:00 |
July | 1295.83 | 03-JUL-09:09 | 692.79 | 03-JUL-07:10 | 1466.94 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 616.06 | 30-JUL-12:00 | 1170.12 | 05-JUL-00:53 |
August | 1295.83 | 01-AUG-09:09 | 796.34 | 17-AUG-07:10 | 1466.94 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 615.68 | 06-AUG-17:34 | 1413.22 | 22-AUG-21:10 |
September | 1295.83 | 01-SEP-09:09 | 960.74 | 11-SEP-07:10 | 1466.94 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 742.64 | 03-SEP-12:51 | 2211.06 | 12-SEP-03:00 |
October | 1295.83 | 02-OCT-09:09 | 1127.77 | 30-OCT-07:10 | 1466.94 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 134.19 | 15-OCT-12:42 | 2122.57 | 30-OCT-21:03 |
November | 1295.83 | 01-NOV-09:09 | 1127.77 | 01-NOV-07:10 | 1466.94 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2948.83 | 28-NOV-05:56 |
December | 1295.83 | 01-DEC-10:09 | 1127.77 | 01-DEC-16:40 | 1466.94 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4198.71 | 01-DEC-05:06 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 692.79 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1170.12 | |||||
Maximum of Months | 1295.83 | 1127.77 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 742.64 | 4861.75 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 405.10 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 405.10 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 405.10 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 405.10 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 405.10 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 405.10 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 405.10 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 405.10 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 405.10 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 405.10 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 405.10 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 405.10 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 405.10 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 405.10 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 405.10 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 405.10 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 405.10 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 405.10 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 405.10 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 405.10 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 405.10 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 405.10 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 405.10 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 405.10 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 405.10 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 405.10 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 405.10 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 405.10 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 405.10 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 405.10 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 405.10 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 405.10 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 405.10 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 405.10 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 405.10 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 405.10 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 405.10 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 405.10 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 405.10 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 405.10 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 405.10 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 405.10 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5027.92 | 02-JAN-10:09 | 4375.82 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5027.92 | 01-FEB-10:09 | 4375.82 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5027.92 | 01-MAR-10:09 | 4375.82 | 01-MAR-08:09 | 379632.52 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5027.92 | 03-APR-09:09 | 4375.82 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5027.92 | 01-MAY-09:09 | 4375.82 | 01-MAY-07:10 | 189816.26 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5027.92 | 01-JUN-09:09 | 4375.82 | 01-JUN-07:10 | 284724.39 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5027.92 | 03-JUL-09:09 | 4375.82 | 03-JUL-07:10 | 379632.52 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5027.92 | 01-AUG-09:09 | 4375.82 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5027.92 | 01-SEP-09:09 | 4375.82 | 01-SEP-07:10 | 189816.26 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5027.92 | 02-OCT-09:09 | 4375.82 | 02-OCT-07:10 | 284724.39 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5027.92 | 01-NOV-09:09 | 4375.82 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5027.92 | 01-DEC-10:09 | 4375.82 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5027.92 | 4375.82 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 5027.92 | 4375.82 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 5184.64 | 05-JAN-22:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 3455.34 | 17-FEB-03:55 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4103.79 | 02-MAR-23:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2925.32 | 27-APR-02:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 217.64 | 20-MAY-17:03 | 5807.04 | 22-MAY-04:01 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 232.50 | 29-JUN-15:00 | 2322.82 | 14-JUN-02:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 580.18 | 30-JUL-12:00 | 1365.54 | 05-JUL-00:53 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 657.02 | 06-AUG-18:00 | 1780.90 | 23-AUG-03:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 780.79 | 03-SEP-13:00 | 3185.04 | 12-SEP-03:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.96 | 18-OCT-15:00 | 2694.05 | 30-OCT-23:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3278.68 | 26-NOV-19:52 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 5120.02 | 01-DEC-04:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1365.54 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 780.79 | 5807.04 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 9104.87 | 05-JAN-22:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 5783.31 | 17-FEB-03:55 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 7126.79 | 02-MAR-23:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 5089.75 | 27-APR-02:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 410.52 | 20-MAY-17:03 | 10043.75 | 22-MAY-04:01 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 416.07 | 29-JUN-15:00 | 4045.26 | 14-JUN-02:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1095.46 | 30-JUL-12:00 | 2369.32 | 05-JUL-00:53 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1240.31 | 06-AUG-17:52 | 3065.62 | 23-AUG-03:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1421.29 | 03-SEP-13:00 | 5539.89 | 12-SEP-03:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.44 | 18-OCT-15:00 | 4581.51 | 30-OCT-22:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 5397.99 | 26-NOV-19:52 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 8210.09 | 01-DEC-04:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2369.32 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1421.29 | 10043.75 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 10234.26 | 05-JAN-22:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 5717.31 | 08-FEB-22:01 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 7682.58 | 02-MAR-23:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 5312.73 | 27-APR-02:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 358.59 | 20-MAY-17:03 | 10095.78 | 22-MAY-04:10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 429.66 | 29-JUN-15:00 | 4179.72 | 14-JUN-02:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 993.28 | 30-JUL-12:00 | 2505.86 | 05-JUL-00:53 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1117.69 | 06-AUG-18:00 | 3211.36 | 22-AUG-21:03 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1303.56 | 03-SEP-12:51 | 5408.09 | 12-SEP-03:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 4795.78 | 30-OCT-21:03 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 5738.59 | 28-NOV-06:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 8143.50 | 01-DEC-04:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2505.86 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1303.56 | 10234.26 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 101597.79 | 02-JAN-04:03 | 0.00 | 2586.68 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 103033.50 | 21-FEB-04:01 | 0.00 | 6035.59 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 101112.59 | 20-MAR-03:01 | 0.00 | 6035.59 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 100898.03 | 10-APR-03:02 | 0.00 | 3448.91 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 103694.71 | 30-MAY-03:02 | 0.00 | 4311.14 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 103066.51 | 05-JUN-03:02 | 0.00 | 3448.91 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 102303.48 | 05-JUL-03:02 | 0.00 | 4311.14 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 102341.04 | 07-AUG-03:02 | 0.00 | 5173.36 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 102833.74 | 25-SEP-03:02 | 0.00 | 3448.91 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 106478.99 | 10-OCT-03:01 | 0.00 | 6035.59 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 104856.08 | 13-NOV-04:01 | 0.00 | 6035.59 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 102150.21 | 04-DEC-04:01 | 0.00 | 6035.59 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 100898.03 | 0.00 | 2586.68 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 106478.99 | 0.00 | 6035.59 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 83711.95 | 02-JAN-05:01 | 0.00 | 12389.45 | 64457.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 82088.25 | 27-FEB-05:01 | 0.00 | 10840.77 | 56400.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 82835.67 | 29-MAR-04:01 | 0.00 | 12389.45 | 64457.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 85312.37 | 10-APR-03:02 | 0.00 | 3097.36 | 32228.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 88221.82 | 30-MAY-03:02 | 0.00 | 3871.70 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 86301.76 | 12-JUN-03:02 | 0.00 | 3871.70 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 89041.91 | 05-JUL-03:02 | 0.00 | 3871.70 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 84984.61 | 02-AUG-03:02 | 0.00 | 3871.70 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 89355.18 | 11-SEP-03:02 | 0.00 | 3871.70 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 84774.97 | 02-OCT-03:02 | 0.00 | 3097.36 | 32228.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 85415.90 | 06-NOV-04:03 | 0.00 | 3097.36 | 32228.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 82253.97 | 07-DEC-05:01 | 0.00 | 10840.77 | 56400.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 82088.25 | 0.00 | 3097.36 | 32228.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 89355.18 | 0.00 | 12389.45 | 64457.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16910.38 | 05-JAN-17:00 | 15316.26 | 13937.56 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 28933.85 | 28-FEB-17:00 | 15316.26 | 13937.56 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 67068.68 | 30-MAR-05:02 | 8061.19 | 7743.41 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 74704.58 | 07-APR-05:02 | 8061.19 | 7743.41 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 75262.41 | 26-MAY-05:02 | 8061.19 | 7743.41 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 76814.21 | 13-JUN-05:02 | 8061.19 | 7743.41 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 76546.02 | 13-JUL-04:03 | 0.00 | 6194.72 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 80284.65 | 14-AUG-03:02 | 0.00 | 3097.36 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 79490.17 | 11-SEP-03:02 | 0.00 | 3871.70 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 73185.96 | 17-OCT-05:02 | 8061.19 | 7743.41 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 68100.19 | 04-NOV-05:02 | 8061.19 | 7743.41 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 23661.17 | 07-DEC-16:30 | 30632.53 | 27875.12 | 36257.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 16910.38 | 0.00 | 3097.36 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 80284.65 | 30632.53 | 27875.12 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16120.89 | 13-JAN-17:00 | 15316.26 | 13937.56 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 20388.65 | 28-FEB-17:00 | 15316.26 | 13937.56 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 23589.59 | 23-MAR-16:00 | 15316.26 | 13937.56 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 43394.79 | 07-APR-05:02 | 8061.19 | 7743.41 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 73104.27 | 20-MAY-05:02 | 8061.19 | 7743.41 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 77817.29 | 21-JUN-03:02 | 0.00 | 3871.70 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 76100.91 | 20-JUL-04:03 | 0.00 | 6194.72 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 75519.85 | 07-AUG-03:02 | 0.00 | 4646.04 | 48342.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 77170.41 | 05-SEP-03:02 | 0.00 | 3871.70 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 38021.07 | 19-OCT-05:03 | 6448.95 | 6194.72 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 21702.67 | 03-NOV-16:00 | 15316.26 | 13937.56 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17190.00 | 06-DEC-17:00 | 15316.26 | 13937.56 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 16120.89 | 0.00 | 3871.70 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 77817.29 | 15316.26 | 13937.56 | 48342.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2443.81 | 02-JAN-05:01 | 0.00 | 1555.62 | 8093.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.66 |
February | 3744.49 | 27-FEB-16:00 | 1923.11 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.22 |
March | 4159.15 | 27-MAR-14:40 | 1923.11 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.41 |
April | 6570.48 | 07-APR-14:30 | 1923.11 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.97 |
May | 11031.87 | 30-MAY-05:03 | 809.73 | 742.20 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.54 |
June | 12304.40 | 26-JUN-05:02 | 1012.16 | 597.26 | 5058.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.03 |
July | 15276.03 | 16-JUL-18:31 | 0.00 | 418.08 | 5311.41 | 0.00 | 0.00 | 0.00 | 0.00 | 95.68 | 0.00 |
August | 15075.48 | 06-AUG-15:41 | 708.51 | 418.08 | 5311.41 | 0.00 | 0.00 | 0.00 | 0.00 | 260.16 | 0.00 |
September | 11971.78 | 05-SEP-05:02 | 1012.16 | 972.26 | 5058.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.62 |
October | 5461.61 | 19-OCT-14:30 | 1923.11 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.32 |
November | 3744.19 | 24-NOV-14:30 | 2010.79 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.86 |
December | 2448.33 | 06-DEC-05:01 | 0.00 | 1555.62 | 8093.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 830.32 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2443.81 | 0.00 | 418.08 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15276.03 | 2010.79 | 1555.62 | 8093.57 | 0.00 | 0.00 | 0.00 | 0.00 | 260.16 | 830.32 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2569.45 | 02-JAN-05:01 | 0.00 | 1002.50 | 5215.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.36 |
February | 6341.40 | 27-FEB-09:55 | 2478.65 | 1385.57 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.07 |
March | 8912.60 | 28-MAR-09:15 | 2591.66 | 1385.57 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.10 |
April | 16620.57 | 16-APR-08:43 | 260.91 | 153.96 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 482.92 |
May | 11398.95 | 19-MAY-08:30 | 1239.33 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.73 |
June | 20898.80 | 25-JUN-07:52 | 391.37 | 230.94 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.49 |
July | 20438.38 | 02-JUL-08:32 | 391.37 | 230.94 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.71 |
August | 20548.08 | 06-AUG-08:22 | 391.37 | 230.94 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.49 |
September | 18422.35 | 04-SEP-08:32 | 326.14 | 192.45 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.87 |
October | 8558.68 | 18-OCT-09:20 | 1295.83 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.01 |
November | 5857.14 | 06-NOV-09:35 | 2478.65 | 1385.57 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.71 |
December | 2423.92 | 20-DEC-10:20 | 1295.83 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.11 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2423.92 | 0.00 | 153.96 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.87 | |
Maximum of Months | 20898.80 | 2591.66 | 1385.57 | 5215.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 482.92 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 11207.84 | 02-JAN-13:30 | 1923.15 | 1075.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 221.46 |
February | 25036.28 | 26-FEB-13:32 | 506.09 | 298.64 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 470.14 |
March | 18390.37 | 01-MAR-13:40 | 1923.15 | 1075.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.45 |
April | 24636.24 | 16-APR-13:23 | 404.87 | 238.91 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 370.40 |
May | 14564.14 | 19-MAY-13:30 | 2010.83 | 1075.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 33.90 | 0.00 |
June | 18960.04 | 25-JUN-13:13 | 404.87 | 238.91 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.26 |
July | 24404.07 | 16-JUL-15:12 | 607.31 | 358.36 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 132.53 | 0.00 |
August | 25128.83 | 06-AUG-13:42 | 506.09 | 298.64 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 221.80 | 0.00 |
September | 26395.25 | 03-SEP-12:32 | 607.31 | 358.36 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 232.95 | 0.00 |
October | 27762.99 | 15-OCT-12:31 | 708.53 | 418.09 | 5311.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 421.92 |
November | 23862.64 | 12-NOV-13:32 | 404.87 | 238.91 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 475.94 |
December | 12858.84 | 12-DEC-12:30 | 1058.33 | 1075.05 | 2023.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.02 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 11207.84 | 404.87 | 238.91 | 2023.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 27762.99 | 2010.83 | 1075.05 | 5311.49 | 0.00 | 0.00 | 0.00 | 0.00 | 232.95 | 475.94 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4176.10 | 13-JAN-15:40 | 1239.33 | 692.79 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160.07 |
February | 15273.08 | 26-FEB-17:33 | 260.91 | 210.09 | 1955.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 264.48 |
March | 14471.91 | 12-MAR-16:23 | 260.91 | 153.96 | 1955.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 897.04 |
April | 25603.26 | 16-APR-17:22 | 0.00 | 230.94 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.81 |
May | 27673.15 | 28-MAY-17:41 | 0.00 | 307.92 | 3911.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 336.54 |
June | 25710.59 | 25-JUN-17:52 | 0.00 | 230.94 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.01 |
July | 27209.43 | 16-JUL-17:11 | 0.00 | 269.43 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 47.06 | 0.00 |
August | 27063.21 | 06-AUG-16:21 | 456.59 | 269.43 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 146.69 | 0.00 |
September | 25400.31 | 04-SEP-15:52 | 391.37 | 230.94 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 66.27 | 0.00 |
October | 24293.32 | 15-OCT-14:31 | 456.59 | 269.43 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.87 |
November | 9250.18 | 03-NOV-15:40 | 1239.33 | 692.79 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.93 |
December | 8432.48 | 06-DEC-15:30 | 1239.33 | 692.79 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 214.22 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4176.10 | 0.00 | 153.96 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 27673.15 | 1239.33 | 692.79 | 3911.83 | 0.00 | 0.00 | 0.00 | 0.00 | 146.69 | 897.04 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1332.92 | 14-JAN-17:03 | 303.65 | 291.68 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 361.86 |
February | 2364.02 | 27-FEB-13:30 | 1923.11 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.29 |
March | 2299.44 | 23-MAR-13:30 | 2010.79 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 547.14 |
April | 4714.69 | 07-APR-14:30 | 1923.11 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.30 |
May | 6761.33 | 19-MAY-16:00 | 1923.11 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 178.84 | 0.00 |
June | 8615.82 | 21-JUN-05:03 | 809.73 | 477.81 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.73 |
July | 14469.02 | 16-JUL-19:01 | 0.00 | 537.53 | 6828.95 | 0.00 | 0.00 | 0.00 | 0.00 | 191.87 | 0.00 |
August | 14382.13 | 06-AUG-16:41 | 1012.16 | 597.26 | 7587.73 | 0.00 | 0.00 | 0.00 | 0.00 | 622.59 | 0.00 |
September | 14215.20 | 04-SEP-15:01 | 809.73 | 477.81 | 6070.18 | 0.00 | 0.00 | 0.00 | 0.00 | 292.88 | 0.00 |
October | 3995.06 | 19-OCT-14:40 | 1923.11 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.97 |
November | 2308.24 | 03-NOV-13:30 | 2010.79 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 189.44 |
December | 1571.04 | 06-DEC-16:20 | 1923.11 | 1620.35 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 531.72 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1332.92 | 0.00 | 291.68 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14469.02 | 2010.79 | 1620.35 | 7587.73 | 0.00 | 0.00 | 0.00 | 0.00 | 622.59 | 547.14 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1685.81 | 20-JAN-10:00 | 2478.65 | 1385.57 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 623.91 |
February | 3825.08 | 28-FEB-09:55 | 2478.65 | 1385.57 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.69 |
March | 6737.60 | 28-MAR-10:10 | 1239.33 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 214.50 |
April | 10321.90 | 25-APR-09:00 | 1239.33 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.65 |
May | 11857.47 | 19-MAY-08:50 | 1239.33 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.37 |
June | 21042.65 | 04-JUN-07:42 | 326.14 | 192.45 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 319.45 |
July | 24045.00 | 16-JUL-09:01 | 521.82 | 307.92 | 3911.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 302.53 |
August | 24557.99 | 06-AUG-09:21 | 587.05 | 346.41 | 4400.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.76 |
September | 21859.73 | 04-SEP-08:22 | 391.37 | 230.94 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.57 |
October | 7085.01 | 18-OCT-10:10 | 1239.33 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.83 |
November | 3429.25 | 03-NOV-10:10 | 1239.33 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 226.46 |
December | 1845.23 | 07-DEC-11:20 | 1239.33 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.89 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1685.81 | 326.14 | 192.45 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.76 | |
Maximum of Months | 24557.99 | 2478.65 | 1385.57 | 4400.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 623.91 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 10271.35 | 19-JAN-14:00 | 1923.15 | 1075.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 501.93 |
February | 26768.16 | 26-FEB-12:42 | 607.31 | 358.36 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1297.86 |
March | 19695.28 | 01-MAR-13:50 | 1923.15 | 1075.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 287.03 |
April | 23121.63 | 16-APR-13:13 | 404.87 | 238.91 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 890.26 |
May | 15080.46 | 14-MAY-13:43 | 404.87 | 238.91 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1675.18 |
June | 14704.71 | 30-JUN-13:30 | 2010.83 | 1075.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 40.55 | 0.00 |
July | 26719.84 | 16-JUL-13:02 | 607.31 | 358.36 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 54.09 | 0.00 |
August | 27236.13 | 06-AUG-12:41 | 708.53 | 418.09 | 5311.49 | 0.00 | 0.00 | 0.00 | 0.00 | 398.80 | 0.00 |
September | 28127.80 | 03-SEP-14:11 | 809.75 | 477.82 | 6070.27 | 0.00 | 0.00 | 0.00 | 0.00 | 354.56 | 0.00 |
October | 26595.87 | 15-OCT-13:22 | 607.31 | 358.36 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 734.04 |
November | 24690.01 | 12-NOV-13:43 | 404.87 | 238.91 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1124.66 |
December | 10729.65 | 12-DEC-14:30 | 2010.83 | 1075.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 465.20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 10271.35 | 404.87 | 238.91 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 28127.80 | 2010.83 | 1075.05 | 6070.27 | 0.00 | 0.00 | 0.00 | 0.00 | 398.80 | 1675.18 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2386.10 | 13-JAN-15:50 | 1239.33 | 692.79 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 372.53 |
February | 6724.16 | 28-FEB-16:40 | 1239.33 | 692.79 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.78 |
March | 8366.90 | 28-MAR-17:00 | 391.37 | 384.88 | 814.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 356.46 |
April | 22665.17 | 16-APR-17:11 | 0.00 | 346.41 | 4400.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 372.24 |
May | 22790.05 | 28-MAY-17:52 | 0.00 | 230.94 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 676.31 |
June | 25249.96 | 18-JUN-17:21 | 0.00 | 307.92 | 3911.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.87 |
July | 26950.18 | 16-JUL-17:01 | 0.00 | 384.90 | 4889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 67.70 | 0.00 |
August | 26091.73 | 06-AUG-16:41 | 652.28 | 384.90 | 4889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 273.88 | 0.00 |
September | 25370.58 | 04-SEP-15:41 | 587.05 | 346.41 | 4400.81 | 0.00 | 0.00 | 0.00 | 0.00 | 101.19 | 0.00 |
October | 9863.86 | 16-OCT-16:00 | 1239.33 | 692.79 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.46 |
November | 5231.32 | 03-NOV-15:50 | 1239.33 | 692.79 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.24 |
December | 2616.28 | 06-DEC-15:50 | 1239.33 | 692.79 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 473.46 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2386.10 | 0.00 | 230.94 | 814.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26950.18 | 1239.33 | 692.79 | 4889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 273.88 | 676.31 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1550.14 | 14-JAN-17:03 | 303.65 | 291.68 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 448.95 |
February | 2026.66 | 27-FEB-16:10 | 1923.11 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.21 |
March | 2167.16 | 29-MAR-16:00 | 1923.11 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 645.85 |
April | 4278.52 | 07-APR-14:30 | 1923.11 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.94 |
May | 7452.95 | 19-MAY-16:00 | 1923.11 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 215.48 | 0.00 |
June | 9223.32 | 29-JUN-15:10 | 1923.11 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 350.96 | 0.00 |
July | 18798.35 | 16-JUL-18:31 | 0.00 | 418.08 | 5311.41 | 0.00 | 0.00 | 0.00 | 0.00 | 266.06 | 0.00 |
August | 19643.54 | 06-AUG-16:11 | 1012.16 | 597.26 | 7587.73 | 0.00 | 0.00 | 0.00 | 0.00 | 718.01 | 0.00 |
September | 19121.07 | 04-SEP-15:41 | 910.95 | 537.53 | 6828.95 | 0.00 | 0.00 | 0.00 | 0.00 | 305.16 | 0.00 |
October | 3257.93 | 19-OCT-15:00 | 1923.11 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.58 |
November | 2023.36 | 17-NOV-17:00 | 1923.11 | 1750.00 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 269.19 |
December | 1594.32 | 06-DEC-16:20 | 1923.11 | 1620.50 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 633.71 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1550.14 | 0.00 | 291.68 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19643.54 | 1923.11 | 1750.00 | 7587.73 | 0.00 | 0.00 | 0.00 | 0.00 | 718.01 | 645.85 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1646.82 | 13-JAN-06:04 | 913.19 | 877.19 | 4563.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 220.77 |
February | 2321.63 | 28-FEB-10:30 | 1295.83 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 199.21 |
March | 4966.15 | 23-MAR-10:30 | 1239.33 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 675.21 |
April | 9251.10 | 25-APR-09:40 | 1295.83 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.71 |
May | 11380.57 | 19-MAY-09:20 | 1295.83 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.00 |
June | 22265.57 | 25-JUN-09:02 | 391.37 | 230.94 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 297.69 |
July | 21941.44 | 16-JUL-09:12 | 391.37 | 230.94 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 283.94 |
August | 23936.56 | 06-AUG-08:11 | 521.82 | 307.92 | 3911.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.24 |
September | 21937.99 | 04-SEP-09:02 | 391.37 | 230.94 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.53 |
October | 5872.13 | 18-OCT-10:00 | 1295.83 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.46 |
November | 2260.89 | 03-NOV-10:00 | 1295.83 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 273.20 |
December | 1670.38 | 09-DEC-06:04 | 913.19 | 877.19 | 4563.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1646.82 | 391.37 | 230.94 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23936.56 | 1295.83 | 877.19 | 4563.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 675.21 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8601.33 | 31-JAN-13:40 | 1923.15 | 1075.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 853.90 |
February | 26877.68 | 26-FEB-14:31 | 708.53 | 418.09 | 5311.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1123.30 |
March | 17432.78 | 01-MAR-14:10 | 2010.83 | 1075.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 348.85 |
April | 16726.38 | 25-APR-13:40 | 2010.83 | 1075.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.47 |
May | 15530.60 | 19-MAY-13:50 | 2010.83 | 1075.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 112.92 | 0.00 |
June | 22337.32 | 25-JUN-14:22 | 506.09 | 298.64 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.16 |
July | 27339.55 | 16-JUL-13:52 | 506.09 | 298.64 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 206.23 | 0.00 |
August | 30333.83 | 06-AUG-14:11 | 809.75 | 477.82 | 6070.27 | 0.00 | 0.00 | 0.00 | 0.00 | 428.79 | 0.00 |
September | 30694.41 | 04-SEP-15:01 | 809.75 | 477.82 | 6070.27 | 0.00 | 0.00 | 0.00 | 0.00 | 193.90 | 0.00 |
October | 28821.48 | 15-OCT-15:02 | 607.31 | 358.36 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 943.11 |
November | 16784.58 | 03-NOV-13:30 | 2010.83 | 1075.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 290.99 |
December | 8120.88 | 06-DEC-14:40 | 2010.83 | 1075.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1018.71 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8120.88 | 506.09 | 298.64 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 30694.41 | 2010.83 | 1075.05 | 6070.27 | 0.00 | 0.00 | 0.00 | 0.00 | 428.79 | 1123.30 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2387.21 | 13-JAN-15:50 | 1239.33 | 692.79 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 451.00 |
February | 5972.87 | 28-FEB-16:40 | 1239.33 | 692.79 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 196.20 |
March | 7801.50 | 28-MAR-17:00 | 391.37 | 384.88 | 814.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 446.15 |
April | 21608.46 | 16-APR-17:42 | 0.00 | 192.45 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 370.63 |
May | 24067.47 | 28-MAY-17:52 | 0.00 | 230.94 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 835.04 |
June | 26901.85 | 18-JUN-17:11 | 0.00 | 307.92 | 3911.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.91 |
July | 27621.06 | 09-JUL-17:21 | 0.00 | 346.41 | 4400.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.90 |
August | 28387.72 | 06-AUG-16:11 | 652.28 | 384.90 | 4889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 322.28 | 0.00 |
September | 27460.37 | 04-SEP-15:41 | 587.05 | 346.41 | 4400.81 | 0.00 | 0.00 | 0.00 | 0.00 | 114.34 | 0.00 |
October | 9572.51 | 18-OCT-16:00 | 1239.33 | 692.79 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 4.27 | 0.00 |
November | 4333.93 | 03-NOV-15:50 | 1239.33 | 692.79 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 184.86 |
December | 2606.63 | 06-DEC-15:50 | 1239.33 | 692.79 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 570.17 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2387.21 | 0.00 | 192.45 | 814.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 28387.72 | 1239.33 | 692.79 | 4889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 322.28 | 835.04 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7887.51 | 06-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2596.64 |
February | 5711.05 | 04-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1710.12 |
March | 5243.63 | 04-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 457.84 |
April | 5262.81 | 25-APR-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.86 |
May | 8798.00 | 30-MAY-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.18 |
June | 8254.42 | 26-JUN-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 148.01 |
July | 10385.62 | 03-JUL-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.46 |
August | 12935.74 | 07-AUG-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.25 |
September | 10381.62 | 05-SEP-05:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.02 |
October | 5120.53 | 16-OCT-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.39 |
November | 4417.77 | 06-NOV-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 230.53 |
December | 3381.48 | 29-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 3381.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12935.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2596.64 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9857.17 | 06-JAN-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6370.06 |
February | 7836.47 | 04-FEB-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2913.40 |
March | 11023.31 | 04-MAR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3154.30 |
April | 6309.79 | 29-APR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3263.91 |
May | 6729.87 | 08-MAY-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4195.21 |
June | 6192.73 | 23-JUN-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.07 | 0.00 |
July | 7834.67 | 17-JUL-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.50 | 0.00 |
August | 7720.71 | 07-AUG-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.20 | 0.00 |
September | 7412.87 | 05-SEP-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.04 |
October | 5831.23 | 10-OCT-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2697.77 |
November | 6662.69 | 13-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3075.28 |
December | 8048.81 | 23-DEC-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3940.29 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 5831.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11023.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.50 | 6370.06 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 862.26 |
February | 2470.12 | 26-FEB-14:34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 868.83 |
March | 2884.67 | 23-MAR-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1175.33 |
April | 10041.20 | 25-APR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 185.12 |
May | 15686.27 | 19-MAY-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 181.12 | 0.00 |
June | 18467.55 | 23-JUN-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.74 | 0.00 |
July | 22087.46 | 17-JUL-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.62 | 0.00 |
August | 19648.04 | 07-AUG-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.06 | 0.00 |
September | 14253.15 | 05-SEP-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.47 |
October | 7767.08 | 18-OCT-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.18 |
November | 1136.51 | 04-NOV-16:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 448.54 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5069.53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22087.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 181.12 | 5069.53 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1953.66 | 19-JAN-16:50 | 222.14 | 405.10 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4275.73 | 28-FEB-17:00 | 222.14 | 405.10 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6830.55 | 31-MAR-24:00 | 0.00 | 22.51 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8240.94 | 22-APR-18:10 | 0.00 | 22.51 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3488.15 | 31-MAY-24:00 | 0.00 | 22.51 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5349.61 | 30-JUN-23:55 | 0.00 | 45.01 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7248.02 | 31-JUL-23:40 | 0.00 | 22.51 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8185.51 | 29-AUG-17:50 | 23.38 | 135.03 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3319.70 | 30-SEP-24:00 | 0.00 | 22.51 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4969.47 | 31-OCT-24:00 | 0.00 | 22.51 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6039.07 | 13-NOV-16:20 | 222.14 | 405.10 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7808.91 | 06-DEC-16:10 | 222.14 | 405.10 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1953.66 | 0.00 | 22.51 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8240.94 | 222.14 | 405.10 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1529.37 | 19-JAN-16:50 | 222.14 | 405.10 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3909.82 | 28-FEB-17:00 | 222.14 | 405.10 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5858.91 | 31-MAR-23:30 | 0.00 | 22.51 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7778.08 | 25-APR-18:10 | 23.38 | 135.03 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3299.15 | 31-MAY-24:00 | 0.00 | 22.51 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5228.27 | 30-JUN-23:55 | 0.00 | 45.01 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7055.04 | 31-JUL-23:55 | 0.00 | 90.03 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7814.37 | 03-AUG-18:50 | 23.38 | 135.03 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2897.38 | 30-SEP-23:40 | 0.00 | 22.51 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4119.24 | 31-OCT-24:00 | 0.00 | 22.51 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5529.96 | 03-NOV-16:00 | 222.14 | 405.10 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7087.40 | 06-DEC-16:20 | 222.14 | 405.10 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1529.37 | 0.00 | 22.51 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7814.37 | 222.14 | 405.10 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1288.58 | 13-JAN-16:30 | 222.14 | 405.10 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3818.57 | 28-FEB-17:00 | 222.14 | 405.10 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5772.28 | 28-MAR-17:50 | 23.38 | 135.03 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7829.18 | 25-APR-18:10 | 23.38 | 135.03 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3216.29 | 31-MAY-24:00 | 0.00 | 22.51 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5228.10 | 30-JUN-23:55 | 0.00 | 45.01 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7051.37 | 31-JUL-23:55 | 0.00 | 90.03 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7928.49 | 03-AUG-18:40 | 23.38 | 135.03 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2812.41 | 04-SEP-17:37 | 0.00 | 202.56 | 17537.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4001.07 | 18-OCT-17:00 | 70.15 | 225.06 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5414.91 | 03-NOV-16:00 | 222.14 | 405.10 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6957.56 | 06-DEC-16:20 | 222.14 | 405.10 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1288.58 | 0.00 | 22.51 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7928.49 | 222.14 | 405.10 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 91021.31 | 02-JAN-17:00 | 4808.68 | 4375.82 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 182796.29 | 28-FEB-17:00 | 4808.68 | 4375.82 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 357269.11 | 31-MAR-24:00 | 0.00 | 243.11 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 366101.27 | 26-APR-16:00 | 4808.68 | 4375.82 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 175652.77 | 31-MAY-24:00 | 0.00 | 243.11 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 267561.85 | 30-JUN-24:00 | 0.00 | 486.22 | 569448.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 358472.58 | 31-JUL-23:53 | 0.00 | 972.44 | 1518530.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 368999.03 | 22-AUG-07:20 | 9617.36 | 8751.64 | 759265.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 175610.11 | 30-SEP-24:00 | 0.00 | 243.11 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 267421.69 | 31-OCT-24:00 | 0.00 | 243.11 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 275866.55 | 06-NOV-16:55 | 9617.36 | 8751.64 | 569448.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 366922.97 | 07-DEC-17:00 | 4808.68 | 4375.82 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 91021.31 | 0.00 | 243.11 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 368999.03 | 9617.36 | 8751.64 | 1518530.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.160332E+13 | 999002.68 | 09-JAN-08:09 | 0.121882E+13 | 2375340.32 | 09-JAN-07:10 |
February | 0.183942E+13 | 1214569.68 | 27-FEB-16:10 | 0.681862E+12 | 1589376.33 | 01-FEB-07:10 |
March | 0.249861E+13 | 1316537.11 | 16-MAR-15:30 | 0.455095E+12 | 1671783.90 | 06-MAR-07:10 |
April | 0.284356E+13 | 1621541.38 | 25-APR-15:00 | 0.170036E+12 | 629359.11 | 29-APR-06:10 |
May | 0.171646E+13 | 1334721.67 | 19-MAY-15:30 | 0.136689E+12 | 748002.32 | 08-MAY-04:10 |
June | 0.226714E+13 | 1546712.39 | 29-JUN-15:09 | 0.646890E+11 | 212225.70 | 16-JUN-06:00 |
July | 0.285186E+13 | 1844548.40 | 17-JUL-15:09 | 0.588038E+11 | 78913.68 | 03-JUL-11:30 |
August | 0.330022E+13 | 1959607.51 | 07-AUG-15:39 | 0.620959E+11 | 77549.27 | 02-AUG-11:20 |
September | 0.174252E+13 | 1421563.82 | 07-SEP-14:00 | 0.741954E+11 | 386306.56 | 19-SEP-05:10 |
October | 0.211548E+13 | 1416204.92 | 18-OCT-15:00 | 0.138532E+12 | 747600.19 | 10-OCT-06:30 |
November | 0.242458E+13 | 1401255.10 | 17-NOV-16:00 | 0.376580E+12 | 1430899.65 | 27-NOV-07:19 |
December | 0.286799E+13 | 1499232.41 | 06-DEC-16:30 | 0.828215E+12 | 1717123.64 | 29-DEC-07:00 |
Annual Sum or Average | 0.280711E+14 | 0.426561E+13 | ||||
Minimum of Months | 0.160332E+13 | 999002.68 | 0.588038E+11 | 77549.27 | ||
Maximum of Months | 0.330022E+13 | 1959607.51 | 0.121882E+13 | 2375340.32 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.233672E+12 | 0.517691E+11 | 0.811612E+12 | 0.162551E+12 | 0.188884E+12 | 0.112126E+11 | 0.00 | 0.943177E+11 | 0.843533E+10 | 0.408632E+11 | 0.00 | 0.00 | 0.00 |
February | 0.208868E+12 | 0.418273E+11 | 0.102011E+13 | 0.146826E+12 | 0.169050E+12 | 0.124185E+11 | 0.00 | 0.157752E+12 | 0.213315E+11 | 0.612392E+11 | 0.00 | 0.00 | 0.00 |
March | 0.246393E+12 | 0.394026E+11 | 0.146267E+13 | 0.162740E+12 | 0.193829E+12 | 0.153679E+11 | 0.00 | 0.247243E+12 | 0.385604E+11 | 0.924050E+11 | 0.00 | 0.00 | 0.00 |
April | 0.219036E+12 | 0.311541E+11 | 0.170311E+13 | 0.157288E+12 | 0.193840E+12 | 0.219111E+11 | 0.00 | 0.323101E+12 | 0.827871E+11 | 0.111339E+12 | 0.00 | 0.00 | 0.00 |
May | 0.235463E+12 | 0.263597E+11 | 0.820521E+12 | 0.162644E+12 | 0.209512E+12 | 0.311448E+11 | 0.00 | 0.140930E+12 | 0.529867E+11 | 0.368947E+11 | 0.00 | 0.00 | 0.00 |
June | 0.233784E+12 | 0.229106E+11 | 0.110677E+13 | 0.157466E+12 | 0.249583E+12 | 0.528908E+11 | 0.00 | 0.288220E+12 | 0.106196E+12 | 0.493128E+11 | 0.00 | 0.00 | 0.00 |
July | 0.219344E+12 | 0.246407E+11 | 0.143888E+13 | 0.162465E+12 | 0.279213E+12 | 0.719042E+11 | 0.00 | 0.466486E+12 | 0.134003E+12 | 0.549227E+11 | 0.00 | 0.00 | 0.00 |
August | 0.244480E+12 | 0.294056E+11 | 0.177780E+13 | 0.162739E+12 | 0.277441E+12 | 0.688219E+11 | 0.00 | 0.520269E+12 | 0.131881E+12 | 0.873835E+11 | 0.00 | 0.00 | 0.00 |
September | 0.219633E+12 | 0.350807E+11 | 0.784732E+12 | 0.157287E+12 | 0.218260E+12 | 0.431207E+11 | 0.00 | 0.175614E+12 | 0.773517E+11 | 0.314383E+11 | 0.00 | 0.00 | 0.00 |
October | 0.229627E+12 | 0.434195E+11 | 0.112899E+13 | 0.162550E+12 | 0.199509E+12 | 0.252671E+11 | 0.00 | 0.200811E+12 | 0.610490E+11 | 0.642552E+11 | 0.00 | 0.00 | 0.00 |
November | 0.229485E+12 | 0.483273E+11 | 0.140306E+13 | 0.157362E+12 | 0.183910E+12 | 0.159294E+11 | 0.00 | 0.242409E+12 | 0.524452E+11 | 0.916485E+11 | 0.00 | 0.00 | 0.00 |
December | 0.226337E+12 | 0.535519E+11 | 0.175516E+13 | 0.162467E+12 | 0.187419E+12 | 0.117981E+11 | 0.00 | 0.309456E+12 | 0.421852E+11 | 0.119619E+12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.274612E+13 | 0.447849E+12 | 0.152134E+14 | 0.191438E+13 | 0.255045E+13 | 0.381787E+12 | 0.00 | 0.316661E+13 | 0.809213E+12 | 0.841321E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.208868E+12 | 0.229106E+11 | 0.784732E+12 | 0.146826E+12 | 0.169050E+12 | 0.112126E+11 | 0.00 | 0.943177E+11 | 0.843533E+10 | 0.314383E+11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.246393E+12 | 0.535519E+11 | 0.177780E+13 | 0.162740E+12 | 0.279213E+12 | 0.719042E+11 | 0.00 | 0.520269E+12 | 0.134003E+12 | 0.119619E+12 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.114919E+13 | 0.00 | 0.696328E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.617830E+12 | 0.00 | 0.640315E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.381424E+12 | 0.00 | 0.736709E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.104133E+12 | 0.00 | 0.659034E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.697801E+11 | 0.00 | 0.669094E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.184718E+10 | 0.00 | 0.628418E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 2039915.85 | 0.00 | 0.588017E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.316160E+09 | 0.00 | 0.617798E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.165986E+11 | 0.00 | 0.575968E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.770694E+11 | 0.00 | 0.614629E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.313707E+12 | 0.00 | 0.628725E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.762140E+12 | 0.00 | 0.660756E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.349403E+13 | 0.00 | 0.771579E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 2039915.85 | 0.00 | 0.575968E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.114919E+13 | 0.00 | 0.736709E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 261074.09 | 02-JAN-08:09 | 37611.08 | 01-JAN-06:10 | 439129.89 | 02-JAN-08:09 | 117204.73 | 02-JAN-08:20 | 114899.67 | 09-JAN-06:10 | 32537.35 | 23-JAN-06:10 | 0.00 | 01-JAN-00:10 |
February | 250680.24 | 02-FEB-08:09 | 37611.08 | 01-FEB-06:10 | 557421.28 | 01-FEB-08:09 | 117198.81 | 02-FEB-08:20 | 135082.29 | 28-FEB-15:00 | 32426.42 | 01-FEB-06:10 | 0.00 | 01-FEB-00:10 |
March | 258487.19 | 17-MAR-07:10 | 37611.08 | 01-MAR-06:10 | 675712.68 | 01-MAR-08:09 | 117203.25 | 17-MAR-07:19 | 143213.88 | 28-MAR-15:39 | 32370.34 | 04-MAR-06:10 | 0.00 | 01-MAR-00:10 |
April | 246699.75 | 14-APR-07:10 | 37611.08 | 01-APR-05:10 | 794004.08 | 03-APR-07:10 | 117196.54 | 14-APR-07:19 | 199229.48 | 25-APR-15:39 | 48343.98 | 06-APR-14:50 | 0.00 | 01-APR-00:10 |
May | 240251.06 | 03-MAY-07:10 | 37611.08 | 01-MAY-05:10 | 439129.89 | 01-MAY-07:10 | 117192.87 | 03-MAY-07:19 | 234749.49 | 19-MAY-15:30 | 50237.68 | 19-MAY-11:00 | 0.00 | 01-MAY-00:10 |
June | 234435.00 | 01-JUN-07:10 | 37611.08 | 01-JUN-20:10 | 557421.28 | 01-JUN-07:10 | 117189.56 | 01-JUN-07:19 | 264631.51 | 29-JUN-14:30 | 51605.05 | 30-JUN-15:00 | 0.00 | 01-JUN-00:10 |
July | 234435.00 | 03-JUL-07:10 | 37611.08 | 01-JUL-20:30 | 675712.68 | 03-JUL-07:10 | 117189.56 | 03-JUL-07:19 | 308014.36 | 17-JUL-15:09 | 52938.94 | 31-JUL-15:39 | 0.00 | 01-JUL-00:10 |
August | 236810.93 | 17-AUG-07:10 | 37611.08 | 01-AUG-19:00 | 794004.08 | 01-AUG-07:10 | 117190.91 | 17-AUG-07:19 | 296388.80 | 11-AUG-15:30 | 53341.66 | 07-AUG-12:00 | 0.00 | 01-AUG-00:10 |
September | 246493.73 | 11-SEP-07:10 | 37611.08 | 01-SEP-05:10 | 439129.89 | 01-SEP-07:10 | 117196.42 | 11-SEP-07:19 | 248755.41 | 05-SEP-14:50 | 54235.53 | 05-SEP-12:30 | 0.00 | 01-SEP-00:10 |
October | 261074.09 | 30-OCT-07:10 | 37611.08 | 01-OCT-05:10 | 557421.28 | 02-OCT-07:10 | 117204.73 | 30-OCT-07:19 | 177505.44 | 18-OCT-15:00 | 48779.55 | 18-OCT-14:00 | 0.00 | 01-OCT-00:10 |
November | 261074.09 | 01-NOV-07:10 | 37611.08 | 01-NOV-05:10 | 675712.68 | 01-NOV-07:10 | 117204.73 | 01-NOV-07:19 | 141467.77 | 03-NOV-15:09 | 32496.28 | 27-NOV-07:00 | 0.00 | 01-NOV-00:10 |
December | 261074.09 | 01-DEC-16:40 | 37611.08 | 01-DEC-06:10 | 794004.08 | 01-DEC-08:09 | 117204.73 | 13-DEC-08:20 | 103605.49 | 07-DEC-14:09 | 32303.36 | 11-DEC-05:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 234435.00 | 37611.08 | 439129.89 | 117189.56 | 103605.49 | 32303.36 | 0.00 | |||||||
Maximum of Months | 261074.09 | 37611.08 | 794004.08 | 117204.73 | 308014.36 | 54235.53 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum} [W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY {Maximum} [W] | HUMIDIFIER:ELECTRICITY {TIMESTAMP} | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 41434.05 | 19-JAN-16:00 | 7364.57 | 14-JAN-14:00 | 20023.70 | 18-JAN-20:00 | 0.00 | 0.00 | 0.00 |
February | 132163.44 | 27-FEB-15:30 | 49248.27 | 20-FEB-15:39 | 31400.88 | 04-FEB-07:30 | 0.00 | 0.00 | 0.00 |
March | 116157.44 | 31-MAR-23:00 | 49248.27 | 14-MAR-11:20 | 43034.05 | 31-MAR-23:00 | 0.00 | 0.00 | 0.00 |
April | 236824.74 | 07-APR-13:09 | 50137.75 | 06-APR-15:50 | 50178.55 | 29-APR-06:10 | 0.00 | 0.00 | 0.00 |
May | 236607.71 | 19-MAY-15:30 | 52688.46 | 19-MAY-12:39 | 21878.42 | 31-MAY-23:00 | 0.00 | 0.00 | 0.00 |
June | 311119.66 | 29-JUN-14:00 | 80284.75 | 06-JUN-14:50 | 26992.18 | 08-JUN-20:00 | 0.00 | 0.00 | 0.00 |
July | 414820.51 | 17-JUL-15:30 | 80284.75 | 13-JUL-13:09 | 36625.63 | 12-JUL-06:10 | 0.00 | 0.00 | 0.00 |
August | 414367.56 | 07-AUG-15:39 | 80284.75 | 05-AUG-12:39 | 49578.98 | 01-AUG-20:00 | 0.00 | 0.00 | 0.00 |
September | 357111.14 | 07-SEP-14:00 | 80284.75 | 02-SEP-10:39 | 22822.71 | 30-SEP-23:00 | 0.00 | 0.00 | 0.00 |
October | 256310.42 | 18-OCT-14:00 | 50241.34 | 18-OCT-12:00 | 33005.13 | 31-OCT-23:00 | 0.00 | 0.00 | 0.00 |
November | 139356.54 | 17-NOV-16:00 | 49288.48 | 17-NOV-16:00 | 41251.30 | 20-NOV-21:00 | 0.00 | 0.00 | 0.00 |
December | 124536.55 | 10-DEC-01:00 | 49248.27 | 05-DEC-13:09 | 51932.06 | 28-DEC-18:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 41434.05 | 7364.57 | 20023.70 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 414820.51 | 80284.75 | 51932.06 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 999002.68 | 09-JAN-08:09 | 261074.09 | 439129.89 | 37611.08 | 117106.55 | 91179.35 | 4417.60 | 0.00 | 30506.97 | 1428.05 |
February | 1214569.68 | 27-FEB-16:10 | 234435.00 | 557421.28 | 0.00 | 83146.17 | 115070.96 | 32300.81 | 0.00 | 121609.89 | 49248.27 |
March | 1316537.11 | 16-MAR-15:30 | 234435.00 | 675712.68 | 0.00 | 83146.17 | 137984.42 | 32221.36 | 0.00 | 96915.76 | 19415.28 |
April | 1621541.38 | 25-APR-15:00 | 234435.00 | 794004.08 | 0.00 | 83146.17 | 196895.54 | 32416.43 | 0.00 | 198280.02 | 49416.23 |
May | 1334721.67 | 19-MAY-15:30 | 234435.00 | 439129.89 | 0.00 | 83146.17 | 234749.49 | 50176.11 | 0.00 | 236607.71 | 52688.46 |
June | 1546712.39 | 29-JUN-15:09 | 234435.00 | 557421.28 | 0.00 | 83146.17 | 260939.16 | 48826.00 | 0.00 | 309937.09 | 51185.79 |
July | 1844548.40 | 17-JUL-15:09 | 234435.00 | 675712.68 | 0.00 | 83146.17 | 308014.36 | 52131.46 | 0.00 | 410823.98 | 80284.75 |
August | 1959607.51 | 07-AUG-15:39 | 234435.00 | 794004.08 | 0.00 | 83146.17 | 283819.75 | 52664.13 | 0.00 | 414367.56 | 80284.75 |
September | 1421563.82 | 07-SEP-14:00 | 234435.00 | 439129.89 | 0.00 | 37754.99 | 221160.22 | 51687.83 | 0.00 | 357111.14 | 80284.75 |
October | 1416204.92 | 18-OCT-15:00 | 237415.79 | 557421.28 | 0.00 | 83147.46 | 177505.44 | 48619.11 | 0.00 | 250110.54 | 49923.71 |
November | 1401255.10 | 17-NOV-16:00 | 261074.09 | 675712.68 | 37611.08 | 83161.34 | 96889.44 | 32261.86 | 0.00 | 139356.54 | 49288.48 |
December | 1499232.41 | 06-DEC-16:30 | 261074.09 | 794004.08 | 37611.08 | 83155.90 | 90410.25 | 32221.39 | 0.00 | 121281.55 | 36170.55 |
Annual Sum or Average | |||||||||||
Minimum of Months | 999002.68 | 234435.00 | 439129.89 | 0.00 | 37754.99 | 90410.25 | 4417.60 | 0.00 | 30506.97 | 1428.05 | |
Maximum of Months | 1959607.51 | 261074.09 | 794004.08 | 37611.08 | 117106.55 | 308014.36 | 52664.13 | 0.00 | 414367.56 | 80284.75 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 2355196.33 | 09-JAN-07:10 | 0.00 | 85381.17 | 31-JAN-12:30 | 0.00 |
February | 0.00 | 0.00 | 1558607.42 | 01-FEB-07:10 | 0.00 | 85533.81 | 16-FEB-12:39 | 0.00 |
March | 0.00 | 0.00 | 1641151.20 | 06-MAR-07:10 | 0.00 | 85512.84 | 02-MAR-12:39 | 0.00 |
April | 0.00 | 0.00 | 601531.61 | 29-APR-06:10 | 0.00 | 84640.18 | 03-APR-11:50 | 0.00 |
May | 0.00 | 0.00 | 742306.45 | 08-MAY-04:10 | 0.00 | 83216.38 | 01-MAY-11:50 | 0.00 |
June | 0.00 | 0.00 | 182623.95 | 16-JUN-06:00 | 0.00 | 81109.27 | 01-JUN-11:00 | 0.00 |
July | 0.00 | 0.00 | 505.63 | 08-JUL-05:30 | 0.00 | 78913.68 | 03-JUL-11:30 | 0.00 |
August | 0.00 | 0.00 | 67560.14 | 18-AUG-05:10 | 0.00 | 77549.27 | 02-AUG-11:20 | 0.00 |
September | 0.00 | 0.00 | 375752.84 | 19-SEP-05:10 | 0.00 | 78451.87 | 29-SEP-11:00 | 0.00 |
October | 0.00 | 0.00 | 718132.13 | 10-OCT-06:30 | 0.00 | 80545.95 | 31-OCT-11:39 | 0.00 |
November | 0.00 | 0.00 | 1408187.71 | 27-NOV-07:19 | 0.00 | 82619.04 | 30-NOV-12:39 | 0.00 |
December | 0.00 | 0.00 | 1686788.37 | 29-DEC-07:00 | 0.00 | 84267.28 | 29-DEC-12:50 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 505.63 | 0.00 | 77549.27 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 2355196.33 | 0.00 | 85533.81 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.05 | 0.67 | 27.09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 25.78 | 0.00 | 25.78 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 25.69 | 0.00 | 25.69 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 25.74 | 0.00 | 25.74 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 25.97 | 0.00 | 25.97 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 25.89 | 0.00 | 25.89 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 26.35 | 0.00 | 26.35 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 26.28 | 0.00 | 26.28 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 26.48 | 0.17 | 26.50 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 26.54 | 0.83 | 26.61 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 26.37 | 0.00 | 26.37 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 25.77 | 0.00 | 25.77 |
Annual Sum or Average | 0.00 | 0.00 | 49.83 | 26.34 | 1.67 | 26.37 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 25.69 | 0.00 | 25.69 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 27.05 | 0.83 | 27.09 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.17 | 0.00 | 26.17 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.56 | 0.00 | 25.56 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.60 | 0.00 | 25.60 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 25.63 | 0.00 | 25.63 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 25.59 | 0.00 | 25.59 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.59 | 0.00 | 25.59 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 3.00 | 25.63 | 0.00 | 25.63 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 26.17 | 0.00 | 26.17 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 18.35 | 0.00 | 18.35 | 0.00 | 18.35 | 0.00 | 18.35 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.56 | 0.00 | 25.56 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | 18.35 | 0.00 | 18.35 | 0.17 | 21.96 | 0.00 | 21.96 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 18.35 | 0.00 | 18.35 | 0.17 | 25.56 | 0.00 | 25.56 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 9.83 | 18.87 | 2.83 | 19.08 | 0.00 | 19.08 | 0.00 | 19.08 |
February | 2.33 | 18.86 | 0.50 | 19.05 | 0.00 | 19.05 | 0.00 | 19.05 |
March | 1.67 | 18.68 | 0.50 | 19.04 | 0.00 | 19.04 | 0.00 | 19.04 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.17 | 19.30 | 0.00 | 19.30 | 0.00 | 19.30 | 0.00 | 19.30 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.33 | 18.65 | 0.00 | 18.65 | 0.00 | 18.65 | 0.00 | 18.65 |
November | 2.17 | 18.82 | 0.50 | 19.07 | 0.00 | 19.07 | 0.00 | 19.07 |
December | 3.33 | 18.78 | 0.33 | 18.93 | 0.00 | 18.93 | 0.00 | 18.93 |
Annual Sum or Average | 19.83 | 18.83 | 4.67 | 19.04 | 0.00 | 19.04 | 0.00 | 19.04 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 9.83 | 19.30 | 2.83 | 19.30 | 0.00 | 19.30 | 0.00 | 19.30 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 6.17 | 18.63 | 1.33 | 18.88 | 0.00 | 18.88 | 0.00 | 18.88 |
February | 0.67 | 19.22 | 0.00 | 19.22 | 0.00 | 19.22 | 0.00 | 19.22 |
March | 0.33 | 19.09 | 0.00 | 19.09 | 0.00 | 19.09 | 0.00 | 19.09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.38 | 0.00 | 27.38 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.12 | 1.17 | 27.23 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.34 | 0.17 | 27.34 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.33 | 19.32 | 0.00 | 19.32 | 0.00 | 19.32 | 0.00 | 19.32 |
Annual Sum or Average | 7.50 | 18.73 | 1.33 | 18.93 | 2.50 | 20.75 | 1.33 | 21.45 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 6.17 | 19.32 | 1.33 | 19.32 | 2.00 | 27.38 | 1.17 | 27.38 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.50 | 18.24 | 0.50 | 18.46 | 0.00 | 18.46 | 0.00 | 18.46 |
February | 1.00 | 19.17 | 0.00 | 19.17 | 0.00 | 19.17 | 0.00 | 19.17 |
March | 0.50 | 19.06 | 0.00 | 19.06 | 0.00 | 19.06 | 0.00 | 19.06 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.73 | 0.83 | 27.73 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.42 | 0.17 | 27.42 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.97 | 4.83 | 27.97 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 28.02 | 7.67 | 28.02 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 28.05 | 3.00 | 28.07 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.82 | 4.50 | 27.82 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.28 | 0.17 | 27.28 |
November | 0.17 | 19.42 | 0.00 | 19.42 | 0.00 | 19.42 | 0.00 | 19.42 |
December | 0.50 | 19.06 | 0.00 | 19.06 | 0.00 | 19.06 | 0.00 | 19.06 |
Annual Sum or Average | 6.67 | 18.53 | 0.50 | 18.66 | 21.33 | 25.61 | 21.17 | 26.61 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.46 | 0.00 | 18.46 |
Maximum of Months | 4.50 | 19.42 | 0.50 | 19.42 | 7.67 | 28.05 | 7.67 | 28.07 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 5.67 | 17.98 | 0.50 | 18.17 | 0.50 | 18.86 | 0.50 | 19.45 |
February | 0.83 | 19.12 | 0.00 | 19.12 | 1.83 | 25.22 | 1.83 | 26.36 |
March | 0.50 | 18.86 | 0.00 | 18.86 | 0.67 | 23.80 | 0.67 | 25.15 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.59 | 1.83 | 27.59 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.42 | 1.00 | 27.42 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.52 | 2.50 | 27.52 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 27.73 | 6.67 | 27.76 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.78 | 4.33 | 27.86 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 27.93 | 6.33 | 28.01 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 28.08 | 3.00 | 28.08 |
November | 0.17 | 19.04 | 0.00 | 19.04 | 1.50 | 26.80 | 1.50 | 27.20 |
December | 0.50 | 18.99 | 0.00 | 18.99 | 0.00 | 18.99 | 0.00 | 18.99 |
Annual Sum or Average | 7.67 | 18.25 | 0.50 | 18.38 | 33.67 | 25.95 | 30.17 | 26.75 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.86 | 0.00 | 18.99 |
Maximum of Months | 5.67 | 19.12 | 0.50 | 19.12 | 7.83 | 28.08 | 6.67 | 28.08 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.00 | 18.71 | 0.00 | 18.71 | 0.00 | 18.71 | 0.00 | 18.71 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.77 | 0.83 | 27.77 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.51 | 0.67 | 27.52 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.80 | 3.17 | 27.86 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 28.13 | 1.83 | 28.13 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 27.82 | 3.67 | 27.89 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 26.33 | 27.61 | 8.17 | 27.79 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 30.67 | 27.36 | 7.83 | 27.52 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 27.87 | 3.17 | 27.98 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 28.07 | 1.00 | 28.05 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.28 | 0.17 | 27.28 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3.00 | 18.71 | 0.00 | 18.71 | 86.00 | 27.31 | 30.50 | 27.53 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.00 | 18.71 | 0.00 | 18.71 | 30.67 | 28.13 | 8.17 | 28.13 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 64.00 | 17.21 | 28.83 | 17.57 | 0.00 | 17.57 | 0.00 | 17.57 |
February | 22.00 | 17.36 | 7.33 | 17.48 | 0.00 | 17.48 | 0.00 | 17.48 |
March | 9.67 | 17.42 | 2.33 | 17.85 | 0.00 | 17.85 | 0.00 | 17.85 |
April | 0.33 | 19.23 | 0.00 | 19.23 | 0.00 | 19.23 | 0.00 | 19.23 |
May | 0.83 | 18.97 | 0.00 | 18.97 | 0.00 | 18.97 | 0.00 | 18.97 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.31 | 0.00 | 27.31 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.26 | 0.17 | 27.26 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.33 | 19.20 | 0.00 | 19.20 | 0.00 | 19.20 | 0.00 | 19.20 |
November | 9.67 | 17.53 | 2.50 | 17.95 | 0.00 | 17.95 | 0.00 | 17.95 |
December | 26.33 | 17.27 | 8.50 | 17.44 | 0.00 | 17.44 | 0.00 | 17.44 |
Annual Sum or Average | 133.17 | 17.31 | 49.50 | 17.59 | 0.33 | 17.60 | 0.17 | 17.61 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 64.00 | 19.23 | 28.83 | 19.23 | 0.17 | 27.31 | 0.17 | 27.31 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 29.67 | 15.63 | 5.33 | 15.55 | 0.00 | 15.55 | 0.00 | 15.55 |
February | 13.00 | 16.57 | 1.50 | 16.52 | 0.00 | 16.52 | 0.00 | 16.52 |
March | 6.67 | 16.50 | 0.33 | 16.56 | 0.00 | 16.56 | 0.00 | 16.56 |
April | 0.33 | 19.14 | 0.00 | 19.14 | 0.00 | 19.14 | 0.00 | 19.14 |
May | 0.83 | 18.96 | 0.00 | 18.96 | 0.00 | 18.96 | 0.00 | 18.96 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 28.05 | 4.83 | 28.05 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 28.13 | 9.00 | 28.14 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 28.22 | 3.17 | 28.27 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.85 | 5.00 | 27.85 |
October | 0.33 | 19.23 | 0.00 | 19.23 | 0.00 | 19.23 | 0.00 | 19.23 |
November | 5.67 | 16.59 | 0.00 | 16.59 | 0.00 | 16.59 | 0.00 | 16.59 |
December | 16.17 | 16.11 | 3.50 | 15.83 | 0.00 | 15.83 | 0.00 | 15.83 |
Annual Sum or Average | 72.67 | 16.13 | 10.67 | 16.00 | 22.83 | 18.60 | 22.00 | 20.23 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.55 | 0.00 | 15.55 |
Maximum of Months | 29.67 | 19.23 | 5.33 | 19.23 | 9.33 | 28.22 | 9.00 | 28.27 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 23.67 | 16.15 | 3.50 | 16.15 | 0.00 | 16.15 | 0.00 | 16.15 |
February | 8.50 | 17.17 | 0.83 | 17.15 | 1.50 | 18.68 | 1.50 | 19.84 |
March | 4.00 | 17.23 | 0.17 | 17.35 | 0.50 | 18.44 | 0.50 | 19.31 |
April | 0.17 | 19.14 | 0.00 | 19.14 | 1.00 | 26.46 | 1.00 | 27.02 |
May | 0.67 | 18.96 | 0.00 | 18.96 | 0.33 | 21.76 | 0.33 | 23.17 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.46 | 1.83 | 27.46 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 27.77 | 6.33 | 27.78 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.94 | 3.83 | 27.96 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 28.14 | 6.83 | 28.18 |
October | 0.17 | 19.19 | 0.00 | 19.19 | 3.00 | 27.72 | 3.00 | 27.95 |
November | 3.33 | 17.30 | 0.00 | 17.30 | 1.50 | 20.51 | 1.50 | 22.21 |
December | 11.33 | 16.54 | 2.00 | 16.23 | 0.00 | 16.23 | 0.00 | 16.23 |
Annual Sum or Average | 51.83 | 16.61 | 6.50 | 16.53 | 29.00 | 20.31 | 26.67 | 22.10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.15 | 0.00 | 16.15 |
Maximum of Months | 23.67 | 19.19 | 3.50 | 19.19 | 7.83 | 28.14 | 6.83 | 28.18 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 25.67 | 15.68 | 4.33 | 15.56 | 0.00 | 15.56 | 0.00 | 15.56 |
February | 9.17 | 16.96 | 1.17 | 16.82 | 0.00 | 16.82 | 0.00 | 16.82 |
March | 3.83 | 17.10 | 0.00 | 17.10 | 0.00 | 17.10 | 0.00 | 17.10 |
April | 0.17 | 19.42 | 0.00 | 19.42 | 1.00 | 26.84 | 0.50 | 27.19 |
May | 0.50 | 18.93 | 0.00 | 18.93 | 3.33 | 26.87 | 1.17 | 27.14 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 28.19 | 1.33 | 28.24 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 28.36 | 4.67 | 28.36 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 28.26 | 2.00 | 28.28 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 28.26 | 2.33 | 28.34 |
October | 0.17 | 19.24 | 0.00 | 19.24 | 0.33 | 24.79 | 0.33 | 25.90 |
November | 3.83 | 17.27 | 0.00 | 17.27 | 0.00 | 17.27 | 0.00 | 17.27 |
December | 12.33 | 16.47 | 2.83 | 16.12 | 0.00 | 16.12 | 0.00 | 16.12 |
Annual Sum or Average | 55.67 | 16.32 | 8.33 | 16.14 | 26.83 | 19.71 | 12.33 | 20.74 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.56 | 0.00 | 15.56 |
Maximum of Months | 25.67 | 19.42 | 4.33 | 19.42 | 9.83 | 28.36 | 4.67 | 28.36 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 118.00 | 16.32 | 49.67 | 16.72 | 0.00 | 16.72 | 0.00 | 16.72 |
February | 47.50 | 16.73 | 15.50 | 16.97 | 0.00 | 16.97 | 0.00 | 16.97 |
March | 27.67 | 16.72 | 7.83 | 16.88 | 0.00 | 16.88 | 0.00 | 16.88 |
April | 4.67 | 18.36 | 0.17 | 18.43 | 0.00 | 18.43 | 0.00 | 18.43 |
May | 6.67 | 17.29 | 1.17 | 17.40 | 0.00 | 17.40 | 0.00 | 17.40 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.49 | 0.17 | 27.46 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.56 | 0.83 | 27.56 |
September | 1.00 | 19.04 | 0.00 | 19.04 | 1.50 | 24.05 | 1.50 | 25.30 |
October | 4.33 | 18.02 | 0.33 | 18.17 | 0.00 | 18.17 | 0.00 | 18.17 |
November | 34.33 | 16.27 | 11.00 | 16.37 | 0.00 | 16.37 | 0.00 | 16.37 |
December | 77.50 | 16.09 | 28.17 | 16.25 | 0.00 | 16.25 | 0.00 | 16.25 |
Annual Sum or Average | 321.67 | 16.43 | 113.83 | 16.67 | 3.67 | 16.76 | 2.50 | 16.82 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 118.00 | 19.04 | 49.67 | 19.04 | 1.50 | 27.56 | 1.50 | 27.56 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 64.17 | 15.20 | 14.33 | 15.22 | 0.00 | 15.22 | 0.00 | 15.22 |
February | 28.50 | 15.63 | 4.67 | 15.53 | 0.00 | 15.53 | 0.00 | 15.53 |
March | 19.67 | 16.09 | 3.50 | 15.94 | 0.00 | 15.94 | 0.00 | 15.94 |
April | 3.50 | 18.40 | 0.00 | 18.40 | 0.00 | 18.40 | 0.00 | 18.40 |
May | 4.50 | 16.74 | 0.00 | 16.74 | 0.00 | 16.74 | 0.00 | 16.74 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.85 | 4.67 | 27.85 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 11.33 | 28.03 | 9.83 | 28.06 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 28.43 | 2.83 | 28.49 |
September | 0.83 | 19.03 | 0.00 | 19.03 | 5.17 | 26.72 | 4.67 | 27.28 |
October | 3.33 | 17.84 | 0.00 | 17.84 | 0.00 | 17.84 | 0.00 | 17.84 |
November | 21.83 | 15.69 | 3.67 | 15.54 | 0.00 | 15.54 | 0.00 | 15.54 |
December | 54.33 | 15.10 | 13.50 | 14.97 | 0.00 | 14.97 | 0.00 | 14.97 |
Annual Sum or Average | 200.67 | 15.52 | 39.67 | 15.42 | 24.67 | 16.59 | 22.00 | 17.47 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.97 | 0.00 | 14.97 |
Maximum of Months | 64.17 | 19.03 | 14.33 | 19.03 | 11.33 | 28.43 | 9.83 | 28.49 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 58.00 | 15.82 | 14.00 | 16.00 | 0.00 | 16.00 | 0.00 | 16.00 |
February | 21.67 | 16.28 | 2.00 | 16.28 | 0.83 | 16.67 | 0.83 | 17.04 |
March | 16.83 | 16.42 | 2.00 | 16.40 | 0.00 | 16.40 | 0.00 | 16.40 |
April | 3.00 | 18.48 | 0.00 | 18.48 | 0.00 | 18.48 | 0.00 | 18.48 |
May | 4.17 | 16.78 | 0.00 | 16.78 | 0.00 | 16.78 | 0.00 | 16.78 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.45 | 1.33 | 27.45 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 27.84 | 6.17 | 27.87 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 28.04 | 3.67 | 28.08 |
September | 0.83 | 19.11 | 0.00 | 19.11 | 7.17 | 27.27 | 5.83 | 27.72 |
October | 2.33 | 18.19 | 0.00 | 18.19 | 1.67 | 22.29 | 1.67 | 23.98 |
November | 16.00 | 16.33 | 2.33 | 16.25 | 0.00 | 16.25 | 0.00 | 16.25 |
December | 41.33 | 15.42 | 7.83 | 15.25 | 0.00 | 15.25 | 0.00 | 15.25 |
Annual Sum or Average | 164.17 | 16.01 | 28.17 | 16.00 | 23.67 | 17.31 | 19.50 | 18.20 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.25 | 0.00 | 15.25 |
Maximum of Months | 58.00 | 19.11 | 14.00 | 19.11 | 8.00 | 28.04 | 6.17 | 28.08 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 52.67 | 15.08 | 11.83 | 15.04 | 0.00 | 15.04 | 0.00 | 15.04 |
February | 21.50 | 15.97 | 3.17 | 15.85 | 0.00 | 15.85 | 0.00 | 15.85 |
March | 15.50 | 16.29 | 2.00 | 16.14 | 0.00 | 16.14 | 0.00 | 16.14 |
April | 2.33 | 18.62 | 0.00 | 18.62 | 0.83 | 21.06 | 0.50 | 22.00 |
May | 2.67 | 17.39 | 0.00 | 17.39 | 3.17 | 23.17 | 1.17 | 23.96 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 28.29 | 1.50 | 28.31 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 28.47 | 4.17 | 28.46 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 28.39 | 2.00 | 28.43 |
September | 0.83 | 19.19 | 0.00 | 19.19 | 4.50 | 26.88 | 2.67 | 27.42 |
October | 2.00 | 18.46 | 0.00 | 18.46 | 0.00 | 18.46 | 0.00 | 18.46 |
November | 16.17 | 15.93 | 3.17 | 15.71 | 0.00 | 15.71 | 0.00 | 15.71 |
December | 41.17 | 15.34 | 10.33 | 15.18 | 0.00 | 15.18 | 0.00 | 15.18 |
Annual Sum or Average | 154.83 | 15.64 | 30.50 | 15.49 | 26.83 | 17.12 | 12.00 | 17.72 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.04 | 0.00 | 15.04 |
Maximum of Months | 52.67 | 19.19 | 11.83 | 19.19 | 10.00 | 28.47 | 4.17 | 28.46 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.75 | 0.00 | 27.75 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 21.50 | 27.99 | 16.83 | 27.94 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 22.33 | 27.98 | 16.83 | 27.94 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 21.50 | 27.99 | 16.83 | 27.94 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 27.96 | 5.00 | 27.95 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 8.83 | 27.96 | 5.00 | 27.95 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 27.96 | 5.00 | 27.95 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 28.06 | 5.17 | 28.02 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 9.33 | 28.06 | 5.17 | 28.02 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 28.06 | 5.17 | 28.02 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 28.17 | 27.89 | 26.00 | 27.89 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 519.67 | 29.10 | 389.83 | 29.15 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 547.83 | 29.04 | 415.83 | 29.08 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 519.67 | 29.10 | 389.83 | 29.15 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 412.33 | 23.10 | 31.50 | 23.31 | 2.00 | 23.29 |
February | 349.83 | 23.55 | 28.17 | 23.75 | 0.00 | 23.75 |
March | 336.00 | 23.94 | 28.17 | 24.10 | 0.00 | 24.10 |
April | 152.67 | 24.00 | 67.17 | 24.64 | 0.00 | 24.64 |
May | 129.50 | 24.00 | 89.33 | 24.82 | 0.00 | 24.82 |
June | 26.50 | 24.13 | 209.50 | 24.87 | 8.67 | 24.86 |
July | 9.50 | 24.76 | 320.00 | 24.90 | 9.33 | 24.89 |
August | 0.33 | 24.00 | 200.33 | 25.18 | 0.00 | 25.18 |
September | 26.33 | 24.00 | 201.33 | 25.09 | 16.50 | 25.02 |
October | 26.00 | 24.00 | 107.83 | 25.96 | 0.00 | 25.96 |
November | 162.83 | 24.00 | 88.33 | 24.85 | 0.00 | 24.85 |
December | 321.17 | 23.75 | 41.67 | 24.03 | 0.00 | 24.03 |
Annual Sum or Average | 1953.00 | 23.68 | 1413.33 | 24.42 | 36.50 | 24.42 |
Minimum of Months | 0.33 | 23.10 | 28.17 | 23.31 | 0.00 | 23.29 |
Maximum of Months | 412.33 | 24.76 | 320.00 | 25.96 | 16.50 | 25.96 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 458.83 | 23.39 | 11.83 | 23.43 | 2.00 | 23.42 |
February | 367.83 | 23.72 | 3.83 | 23.74 | 0.00 | 23.74 |
March | 275.67 | 23.94 | 15.33 | 24.04 | 0.00 | 24.04 |
April | 82.00 | 23.98 | 53.17 | 24.76 | 0.00 | 24.76 |
May | 121.33 | 23.97 | 78.17 | 24.56 | 0.00 | 24.56 |
June | 9.17 | 24.21 | 213.83 | 24.50 | 5.83 | 24.49 |
July | 3.83 | 24.67 | 345.67 | 24.40 | 3.83 | 24.41 |
August | 0.00 | 0.00 | 240.00 | 24.45 | 0.00 | 24.45 |
September | 39.17 | 24.04 | 188.00 | 24.57 | 15.50 | 24.55 |
October | 60.50 | 23.98 | 79.50 | 25.08 | 0.00 | 25.08 |
November | 191.17 | 23.97 | 49.17 | 24.38 | 0.00 | 24.38 |
December | 301.17 | 23.90 | 19.50 | 24.01 | 0.00 | 24.01 |
Annual Sum or Average | 1910.67 | 23.77 | 1298.00 | 24.19 | 27.17 | 24.19 |
Minimum of Months | 0.00 | 0.00 | 3.83 | 23.43 | 0.00 | 23.42 |
Maximum of Months | 458.83 | 24.67 | 345.67 | 25.08 | 15.50 | 25.08 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.95 | 130.33 | 21.70 | 130.33 | 21.54 |
February | 454.00 | 22.57 | 40.00 | 22.41 | 40.00 | 22.26 |
March | 513.83 | 23.26 | 17.67 | 23.18 | 17.67 | 23.11 |
April | 381.00 | 23.65 | 0.00 | 23.65 | 0.00 | 23.65 |
May | 267.33 | 23.70 | 52.50 | 23.97 | 0.00 | 23.97 |
June | 80.33 | 23.80 | 141.67 | 24.16 | 7.83 | 24.16 |
July | 34.67 | 24.16 | 242.83 | 24.39 | 8.67 | 24.41 |
August | 19.33 | 23.78 | 141.50 | 24.57 | 0.00 | 24.57 |
September | 148.33 | 23.77 | 132.33 | 24.15 | 16.17 | 24.15 |
October | 328.00 | 23.69 | 4.83 | 23.71 | 0.00 | 23.71 |
November | 465.67 | 23.33 | 6.33 | 23.30 | 6.33 | 23.27 |
December | 497.00 | 22.39 | 67.83 | 22.15 | 67.83 | 21.97 |
Annual Sum or Average | 3691.50 | 23.04 | 977.83 | 23.14 | 294.83 | 23.02 |
Minimum of Months | 19.33 | 21.95 | 0.00 | 21.70 | 0.00 | 21.54 |
Maximum of Months | 513.83 | 24.16 | 242.83 | 24.57 | 130.33 | 24.57 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.57 | 368.17 | 20.39 | 368.17 | 20.32 |
February | 454.00 | 21.17 | 229.00 | 20.89 | 229.00 | 20.75 |
March | 514.00 | 21.87 | 136.83 | 21.54 | 136.83 | 21.32 |
April | 455.33 | 22.63 | 53.83 | 22.42 | 53.83 | 22.26 |
May | 346.67 | 23.00 | 62.17 | 23.03 | 24.67 | 22.89 |
June | 137.83 | 23.48 | 143.83 | 23.90 | 6.17 | 23.91 |
July | 53.50 | 23.75 | 267.00 | 24.24 | 10.17 | 24.26 |
August | 77.17 | 23.59 | 144.17 | 24.18 | 0.00 | 24.18 |
September | 258.33 | 23.14 | 113.50 | 23.55 | 18.00 | 23.58 |
October | 473.67 | 22.60 | 27.17 | 22.47 | 27.17 | 22.35 |
November | 489.00 | 21.63 | 160.17 | 21.30 | 160.17 | 21.10 |
December | 497.00 | 20.83 | 303.33 | 20.55 | 303.33 | 20.43 |
Annual Sum or Average | 4258.50 | 21.93 | 2009.17 | 21.86 | 1337.50 | 21.59 |
Minimum of Months | 53.50 | 20.57 | 27.17 | 20.39 | 0.00 | 20.32 |
Maximum of Months | 514.00 | 23.75 | 368.17 | 24.24 | 368.17 | 24.26 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.93 | 304.00 | 20.72 | 304.00 | 20.62 |
February | 454.00 | 21.69 | 149.17 | 21.41 | 149.17 | 21.24 |
March | 514.00 | 22.63 | 49.67 | 22.44 | 49.67 | 22.29 |
April | 424.50 | 23.40 | 0.50 | 23.40 | 0.00 | 23.40 |
May | 303.33 | 23.38 | 55.17 | 23.63 | 0.00 | 23.63 |
June | 62.33 | 23.78 | 210.83 | 24.23 | 4.17 | 24.24 |
July | 8.50 | 24.50 | 345.67 | 24.47 | 3.00 | 24.47 |
August | 31.17 | 23.86 | 207.50 | 24.37 | 0.83 | 24.38 |
September | 219.83 | 23.40 | 128.33 | 23.86 | 10.83 | 23.87 |
October | 435.33 | 23.31 | 4.33 | 23.33 | 0.00 | 23.33 |
November | 481.50 | 22.59 | 36.00 | 22.46 | 36.00 | 22.34 |
December | 497.00 | 21.68 | 162.50 | 21.39 | 162.50 | 21.22 |
Annual Sum or Average | 3933.50 | 22.47 | 1653.67 | 22.57 | 720.17 | 22.34 |
Minimum of Months | 8.50 | 20.93 | 0.50 | 20.72 | 0.00 | 20.62 |
Maximum of Months | 514.00 | 24.50 | 345.67 | 24.47 | 304.00 | 24.47 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 500.33 | 20.95 | 303.33 | 20.74 | 303.33 | 20.65 |
February | 433.00 | 21.64 | 153.00 | 21.39 | 150.67 | 21.23 |
March | 468.83 | 22.25 | 60.33 | 22.11 | 54.50 | 21.96 |
April | 328.33 | 22.77 | 47.83 | 23.01 | 1.33 | 23.01 |
May | 232.67 | 22.93 | 99.83 | 23.43 | 0.00 | 23.43 |
June | 95.50 | 24.04 | 279.83 | 24.35 | 21.83 | 24.46 |
July | 46.50 | 25.59 | 394.00 | 24.59 | 29.33 | 24.73 |
August | 71.33 | 23.75 | 293.17 | 24.19 | 9.17 | 24.26 |
September | 199.67 | 23.32 | 189.67 | 23.97 | 24.00 | 24.07 |
October | 352.00 | 22.86 | 14.33 | 22.96 | 0.00 | 22.96 |
November | 473.17 | 22.23 | 61.83 | 22.06 | 61.83 | 21.93 |
December | 497.00 | 21.33 | 203.33 | 21.10 | 203.33 | 20.98 |
Annual Sum or Average | 3698.33 | 22.20 | 2100.50 | 22.50 | 859.33 | 22.32 |
Minimum of Months | 46.50 | 20.95 | 14.33 | 20.74 | 0.00 | 20.65 |
Maximum of Months | 500.33 | 25.59 | 394.00 | 24.59 | 303.33 | 24.73 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 463.17 | 21.30 | 266.00 | 21.05 | 256.67 | 20.89 |
February | 360.00 | 21.95 | 156.50 | 21.89 | 123.17 | 21.68 |
March | 394.00 | 22.34 | 95.33 | 22.34 | 52.00 | 22.17 |
April | 305.33 | 22.85 | 57.33 | 23.13 | 4.50 | 23.12 |
May | 251.67 | 22.81 | 104.50 | 23.28 | 10.33 | 23.23 |
June | 106.67 | 23.61 | 229.17 | 24.17 | 10.17 | 24.22 |
July | 45.83 | 25.11 | 373.00 | 24.56 | 22.00 | 24.67 |
August | 51.67 | 24.36 | 318.00 | 24.40 | 13.33 | 24.50 |
September | 166.67 | 23.54 | 237.00 | 24.21 | 28.17 | 24.34 |
October | 264.67 | 23.06 | 109.00 | 23.50 | 9.00 | 23.56 |
November | 354.83 | 22.42 | 100.00 | 22.53 | 48.67 | 22.36 |
December | 428.17 | 21.70 | 167.50 | 21.46 | 152.17 | 21.24 |
Annual Sum or Average | 3192.67 | 22.39 | 2213.33 | 22.80 | 730.17 | 22.62 |
Minimum of Months | 45.83 | 21.30 | 57.33 | 21.05 | 4.50 | 20.89 |
Maximum of Months | 463.17 | 25.11 | 373.00 | 24.56 | 256.67 | 24.67 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 497.83 | 21.32 | 221.33 | 21.08 | 221.33 | 20.96 |
February | 392.17 | 22.28 | 89.83 | 22.15 | 76.00 | 21.97 |
March | 316.17 | 23.11 | 48.17 | 23.19 | 13.00 | 23.12 |
April | 83.67 | 23.84 | 145.83 | 24.68 | 6.67 | 24.75 |
May | 161.83 | 23.25 | 178.50 | 24.09 | 6.50 | 24.15 |
June | 39.17 | 24.92 | 369.67 | 24.58 | 19.17 | 24.66 |
July | 39.33 | 26.96 | 473.83 | 24.80 | 39.33 | 24.96 |
August | 26.67 | 26.98 | 475.83 | 24.65 | 26.67 | 24.77 |
September | 139.83 | 23.56 | 233.00 | 24.27 | 20.67 | 24.35 |
October | 199.83 | 23.41 | 91.17 | 23.92 | 2.83 | 23.95 |
November | 302.17 | 23.07 | 45.17 | 23.36 | 2.00 | 23.35 |
December | 414.00 | 22.75 | 49.17 | 22.61 | 42.33 | 22.46 |
Annual Sum or Average | 2612.67 | 22.79 | 2421.50 | 23.42 | 476.50 | 23.32 |
Minimum of Months | 26.67 | 21.32 | 45.17 | 21.08 | 2.00 | 20.96 |
Maximum of Months | 497.83 | 26.98 | 475.83 | 24.80 | 221.33 | 24.96 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.92 | 494.67 | 19.91 | 494.67 | 19.91 |
February | 454.00 | 20.38 | 391.00 | 20.30 | 391.00 | 20.28 |
March | 514.00 | 20.90 | 279.00 | 20.68 | 279.00 | 20.57 |
April | 482.83 | 21.97 | 87.83 | 21.74 | 87.83 | 21.56 |
May | 394.33 | 22.54 | 61.50 | 22.47 | 36.67 | 22.29 |
June | 163.33 | 23.38 | 140.33 | 23.78 | 4.67 | 23.79 |
July | 42.33 | 23.66 | 257.67 | 24.30 | 2.67 | 24.31 |
August | 126.50 | 23.41 | 129.33 | 23.95 | 0.00 | 23.95 |
September | 314.17 | 22.64 | 94.67 | 23.01 | 22.17 | 22.98 |
October | 501.33 | 21.96 | 71.50 | 21.76 | 71.50 | 21.61 |
November | 489.00 | 20.78 | 282.33 | 20.55 | 282.33 | 20.44 |
December | 497.00 | 20.04 | 460.17 | 19.99 | 460.17 | 19.98 |
Annual Sum or Average | 4480.83 | 21.32 | 2750.00 | 21.23 | 2132.67 | 20.98 |
Minimum of Months | 42.33 | 19.92 | 61.50 | 19.91 | 0.00 | 19.91 |
Maximum of Months | 514.00 | 23.66 | 494.67 | 24.30 | 494.67 | 24.31 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 19.95 | 408.67 | 19.93 | 408.67 | 19.92 |
February | 384.33 | 20.61 | 281.50 | 20.44 | 281.50 | 20.37 |
March | 423.67 | 21.12 | 197.83 | 20.85 | 197.83 | 20.71 |
April | 338.67 | 21.92 | 71.83 | 21.85 | 53.83 | 21.69 |
May | 265.50 | 22.25 | 87.00 | 22.45 | 29.50 | 22.26 |
June | 127.33 | 23.63 | 212.33 | 24.25 | 23.17 | 24.39 |
July | 61.83 | 25.29 | 312.17 | 24.78 | 34.83 | 24.96 |
August | 91.50 | 23.51 | 225.50 | 24.28 | 11.67 | 24.38 |
September | 232.83 | 22.75 | 132.83 | 23.48 | 26.83 | 23.60 |
October | 395.17 | 21.99 | 45.33 | 21.87 | 41.67 | 21.74 |
November | 416.00 | 20.88 | 223.17 | 20.66 | 223.17 | 20.55 |
December | 422.00 | 19.98 | 381.17 | 19.92 | 381.17 | 19.90 |
Annual Sum or Average | 3585.83 | 21.35 | 2579.33 | 21.53 | 1713.83 | 21.29 |
Minimum of Months | 61.83 | 19.95 | 45.33 | 19.92 | 11.67 | 19.90 |
Maximum of Months | 427.00 | 25.29 | 408.67 | 24.78 | 408.67 | 24.96 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 479.33 | 20.78 | 348.83 | 20.56 | 343.50 | 20.44 |
February | 380.00 | 21.38 | 229.17 | 21.23 | 201.50 | 21.03 |
March | 413.17 | 21.53 | 192.33 | 21.43 | 152.00 | 21.22 |
April | 350.50 | 22.09 | 99.50 | 22.20 | 55.33 | 22.03 |
May | 302.50 | 22.36 | 108.17 | 22.58 | 37.00 | 22.39 |
June | 159.17 | 23.15 | 200.83 | 23.87 | 8.50 | 23.91 |
July | 68.17 | 24.33 | 332.33 | 24.48 | 21.17 | 24.60 |
August | 101.33 | 23.60 | 286.67 | 24.26 | 11.17 | 24.34 |
September | 199.50 | 23.08 | 221.67 | 23.93 | 32.00 | 24.07 |
October | 318.50 | 22.53 | 122.00 | 22.90 | 30.83 | 22.87 |
November | 396.00 | 21.75 | 176.83 | 21.64 | 136.50 | 21.41 |
December | 459.67 | 20.82 | 290.50 | 20.51 | 290.17 | 20.37 |
Annual Sum or Average | 3627.83 | 21.83 | 2608.83 | 22.12 | 1319.67 | 21.86 |
Minimum of Months | 68.17 | 20.78 | 99.50 | 20.51 | 8.50 | 20.37 |
Maximum of Months | 479.33 | 24.33 | 348.83 | 24.48 | 343.50 | 24.60 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.20 | 461.33 | 20.15 | 461.33 | 20.13 |
February | 443.67 | 20.76 | 298.00 | 20.57 | 297.00 | 20.49 |
March | 487.00 | 21.17 | 199.50 | 20.94 | 197.50 | 20.81 |
April | 401.83 | 22.03 | 75.00 | 22.06 | 47.83 | 21.96 |
May | 300.17 | 22.36 | 122.83 | 22.74 | 32.83 | 22.62 |
June | 144.50 | 23.17 | 239.33 | 23.94 | 12.33 | 24.00 |
July | 65.00 | 24.49 | 364.50 | 24.50 | 23.33 | 24.62 |
August | 103.83 | 23.32 | 267.50 | 24.19 | 8.00 | 24.25 |
September | 267.33 | 22.54 | 161.00 | 23.34 | 20.83 | 23.42 |
October | 434.67 | 21.96 | 52.83 | 21.93 | 37.67 | 21.83 |
November | 477.17 | 21.12 | 205.33 | 20.86 | 205.33 | 20.72 |
December | 497.00 | 20.29 | 388.17 | 20.16 | 388.17 | 20.11 |
Annual Sum or Average | 4124.17 | 21.41 | 2835.33 | 21.65 | 1732.17 | 21.40 |
Minimum of Months | 65.00 | 20.20 | 52.83 | 20.15 | 8.00 | 20.11 |
Maximum of Months | 502.00 | 24.49 | 461.33 | 24.50 | 461.33 | 24.62 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.63 | 500.17 | 19.63 | 500.17 | 19.63 |
February | 454.00 | 19.98 | 438.50 | 19.95 | 438.50 | 19.95 |
March | 514.00 | 20.35 | 404.83 | 20.23 | 404.83 | 20.18 |
April | 483.83 | 21.12 | 220.33 | 20.79 | 220.33 | 20.62 |
May | 429.00 | 21.95 | 130.17 | 21.73 | 106.17 | 21.49 |
June | 210.50 | 22.83 | 137.00 | 23.36 | 6.00 | 23.37 |
July | 97.17 | 23.31 | 243.83 | 24.07 | 5.17 | 24.09 |
August | 181.00 | 22.97 | 127.83 | 23.54 | 2.17 | 23.54 |
September | 362.17 | 22.06 | 123.67 | 22.29 | 62.33 | 22.16 |
October | 502.00 | 20.98 | 224.83 | 20.69 | 224.83 | 20.54 |
November | 489.00 | 20.11 | 401.83 | 20.00 | 401.83 | 19.96 |
December | 497.00 | 19.80 | 486.17 | 19.78 | 486.17 | 19.78 |
Annual Sum or Average | 4721.67 | 20.85 | 3439.17 | 20.78 | 2858.50 | 20.56 |
Minimum of Months | 97.17 | 19.63 | 123.67 | 19.63 | 2.17 | 19.63 |
Maximum of Months | 514.00 | 23.31 | 500.17 | 24.07 | 500.17 | 24.09 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.81 | 492.83 | 19.80 | 492.83 | 19.79 |
February | 454.00 | 20.25 | 384.67 | 20.13 | 384.67 | 20.09 |
March | 507.83 | 20.73 | 319.33 | 20.48 | 319.33 | 20.36 |
April | 402.83 | 21.39 | 153.67 | 21.08 | 145.17 | 20.87 |
May | 325.00 | 21.93 | 133.50 | 21.97 | 70.17 | 21.69 |
June | 143.17 | 23.17 | 259.67 | 24.02 | 22.33 | 24.12 |
July | 78.17 | 24.80 | 376.33 | 24.57 | 36.00 | 24.74 |
August | 114.67 | 23.16 | 294.67 | 24.06 | 11.83 | 24.13 |
September | 280.00 | 22.41 | 162.67 | 23.02 | 52.00 | 23.06 |
October | 480.83 | 21.40 | 139.83 | 21.08 | 139.83 | 20.87 |
November | 489.00 | 20.29 | 356.33 | 20.13 | 356.33 | 20.06 |
December | 497.00 | 19.86 | 474.17 | 19.84 | 474.17 | 19.83 |
Annual Sum or Average | 4274.50 | 20.98 | 3547.67 | 21.17 | 2504.67 | 20.92 |
Minimum of Months | 78.17 | 19.81 | 133.50 | 19.80 | 11.83 | 19.79 |
Maximum of Months | 507.83 | 24.80 | 492.83 | 24.57 | 492.83 | 24.74 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 493.00 | 20.30 | 402.33 | 20.09 | 402.33 | 20.01 |
February | 409.17 | 20.88 | 274.83 | 20.63 | 261.50 | 20.47 |
March | 440.17 | 20.95 | 272.17 | 20.74 | 251.33 | 20.56 |
April | 385.00 | 21.45 | 175.67 | 21.29 | 142.50 | 21.04 |
May | 338.33 | 21.89 | 151.33 | 21.96 | 85.00 | 21.68 |
June | 189.50 | 22.67 | 195.67 | 23.53 | 10.83 | 23.54 |
July | 101.83 | 23.75 | 310.50 | 24.30 | 23.17 | 24.43 |
August | 136.17 | 23.12 | 280.33 | 24.01 | 13.00 | 24.07 |
September | 237.00 | 22.49 | 225.00 | 23.33 | 55.50 | 23.33 |
October | 359.33 | 21.66 | 171.50 | 21.72 | 106.83 | 21.48 |
November | 430.17 | 20.97 | 254.00 | 20.72 | 239.67 | 20.55 |
December | 477.67 | 20.31 | 371.33 | 20.09 | 371.33 | 20.00 |
Annual Sum or Average | 3997.33 | 21.30 | 3084.67 | 21.49 | 1963.00 | 21.21 |
Minimum of Months | 101.83 | 20.30 | 151.33 | 20.09 | 10.83 | 20.00 |
Maximum of Months | 493.00 | 23.75 | 402.33 | 24.30 | 402.33 | 24.43 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.87 | 475.33 | 19.83 | 475.33 | 19.82 |
February | 448.33 | 20.37 | 359.83 | 20.23 | 359.83 | 20.17 |
March | 494.33 | 20.71 | 303.67 | 20.50 | 303.67 | 20.40 |
April | 420.83 | 21.40 | 160.67 | 21.23 | 138.83 | 21.05 |
May | 348.17 | 22.00 | 152.17 | 22.19 | 72.50 | 21.98 |
June | 185.83 | 22.75 | 231.00 | 23.65 | 13.50 | 23.71 |
July | 92.33 | 23.82 | 338.17 | 24.34 | 23.67 | 24.47 |
August | 141.00 | 22.92 | 260.33 | 23.92 | 9.50 | 23.98 |
September | 304.67 | 22.12 | 171.83 | 22.78 | 49.83 | 22.76 |
October | 455.67 | 21.29 | 147.50 | 21.08 | 136.33 | 20.90 |
November | 485.67 | 20.54 | 320.17 | 20.32 | 320.17 | 20.23 |
December | 497.00 | 19.99 | 442.83 | 19.91 | 442.83 | 19.89 |
Annual Sum or Average | 4375.83 | 21.03 | 3363.50 | 21.21 | 2346.00 | 20.97 |
Minimum of Months | 92.33 | 19.87 | 147.50 | 19.83 | 9.50 | 19.82 |
Maximum of Months | 502.00 | 23.82 | 475.33 | 24.34 | 475.33 | 24.47 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.17 | 26.18 | 370.17 | 27.00 | 0.00 | 27.00 |
February | 1.17 | 27.00 | 427.17 | 27.00 | 1.17 | 27.00 |
March | 4.50 | 27.00 | 511.00 | 27.00 | 4.50 | 27.00 |
April | 17.00 | 27.00 | 485.00 | 27.00 | 17.00 | 27.00 |
May | 1.17 | 27.00 | 508.00 | 27.00 | 1.17 | 27.00 |
June | 10.83 | 27.00 | 496.00 | 27.00 | 10.83 | 27.00 |
July | 83.17 | 27.00 | 497.00 | 27.00 | 83.17 | 27.00 |
August | 199.33 | 27.12 | 514.00 | 27.07 | 199.33 | 27.08 |
September | 6.50 | 27.00 | 485.00 | 27.00 | 6.50 | 27.00 |
October | 7.17 | 27.00 | 502.00 | 27.00 | 7.17 | 27.00 |
November | 3.83 | 27.00 | 489.00 | 27.00 | 3.83 | 27.00 |
December | 2.33 | 27.00 | 493.33 | 27.00 | 2.33 | 27.00 |
Annual Sum or Average | 338.17 | 27.07 | 5777.67 | 27.01 | 337.00 | 27.01 |
Minimum of Months | 1.17 | 26.18 | 370.17 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 199.33 | 27.12 | 514.00 | 27.07 | 199.33 | 27.08 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 125.00 | 25.55 | 174.50 | 26.40 | 0.00 | 26.40 |
February | 13.33 | 27.00 | 279.67 | 27.00 | 0.00 | 27.00 |
March | 7.17 | 27.00 | 454.00 | 27.00 | 0.00 | 27.00 |
April | 2.83 | 27.00 | 479.67 | 27.00 | 2.83 | 27.00 |
May | 0.50 | 27.00 | 498.17 | 27.00 | 0.50 | 27.00 |
June | 6.33 | 27.00 | 496.00 | 27.00 | 6.33 | 27.00 |
July | 12.83 | 27.00 | 497.00 | 27.00 | 12.83 | 27.00 |
August | 30.50 | 27.28 | 514.00 | 27.04 | 30.50 | 27.05 |
September | 3.67 | 27.00 | 485.00 | 27.00 | 3.67 | 27.00 |
October | 0.00 | 0.00 | 502.00 | 27.00 | 0.00 | 27.00 |
November | 0.00 | 0.00 | 446.17 | 27.00 | 0.00 | 27.00 |
December | 15.50 | 27.00 | 317.00 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 217.67 | 26.21 | 5143.17 | 26.97 | 56.67 | 26.97 |
Minimum of Months | 0.00 | 0.00 | 174.50 | 26.40 | 0.00 | 26.40 |
Maximum of Months | 125.00 | 27.28 | 514.00 | 27.04 | 30.50 | 27.05 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 295.50 | 24.60 | 102.17 | 24.81 | 31.17 | 24.58 |
February | 50.33 | 26.93 | 163.00 | 26.98 | 0.00 | 26.98 |
March | 22.67 | 27.00 | 338.17 | 27.00 | 0.00 | 27.00 |
April | 3.67 | 27.00 | 416.83 | 27.00 | 3.67 | 27.00 |
May | 23.50 | 25.68 | 469.83 | 26.94 | 1.33 | 26.94 |
June | 8.33 | 27.00 | 496.00 | 27.00 | 8.33 | 27.00 |
July | 32.17 | 27.00 | 497.00 | 27.00 | 32.17 | 27.00 |
August | 47.00 | 27.18 | 514.00 | 27.03 | 47.00 | 27.04 |
September | 5.67 | 27.00 | 472.33 | 27.00 | 5.67 | 27.00 |
October | 0.00 | 0.00 | 450.00 | 27.00 | 0.00 | 27.00 |
November | 23.17 | 27.00 | 295.67 | 27.00 | 0.00 | 27.00 |
December | 68.50 | 27.00 | 178.67 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 580.50 | 25.73 | 4393.67 | 26.82 | 129.33 | 26.80 |
Minimum of Months | 0.00 | 0.00 | 102.17 | 24.81 | 0.00 | 24.58 |
Maximum of Months | 295.50 | 27.18 | 514.00 | 27.03 | 47.00 | 27.04 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 154.83 | 27.00 | 502.00 | 27.00 | 154.83 | 27.00 |
February | 454.00 | 27.01 | 454.00 | 27.01 | 454.00 | 27.01 |
March | 514.00 | 27.01 | 514.00 | 27.01 | 514.00 | 27.01 |
April | 485.00 | 27.07 | 485.00 | 27.07 | 485.00 | 27.07 |
May | 486.83 | 27.00 | 508.00 | 27.00 | 486.83 | 27.00 |
June | 496.00 | 27.01 | 496.00 | 27.01 | 496.00 | 27.01 |
July | 497.00 | 27.01 | 497.00 | 27.01 | 497.00 | 27.01 |
August | 514.00 | 28.72 | 514.00 | 28.72 | 514.00 | 28.72 |
September | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
October | 502.00 | 27.01 | 502.00 | 27.01 | 502.00 | 27.01 |
November | 489.00 | 27.01 | 489.00 | 27.01 | 489.00 | 27.01 |
December | 497.00 | 27.00 | 497.00 | 27.00 | 497.00 | 27.00 |
Annual Sum or Average | 5574.67 | 27.17 | 5943.00 | 27.16 | 5574.67 | 27.17 |
Minimum of Months | 154.83 | 27.00 | 454.00 | 27.00 | 154.83 | 27.00 |
Maximum of Months | 514.00 | 28.72 | 514.00 | 28.72 | 514.00 | 28.72 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.98897 | 13.63439 | 0.60063 | 12.80489 |
February | 454.00000 | 27.00000 | 14.89739 | 0.69975 | 15.48453 |
March | 514.00000 | 26.99999 | 16.86936 | 0.78863 | 18.23421 |
April | 485.00000 | 27.00002 | 19.99205 | 0.88360 | 21.55804 |
May | 508.00000 | 27.00015 | 22.20505 | 0.13867 | 5.55579 |
June | 496.00000 | 27.00044 | 25.69010 | 0.25104 | 6.39516 |
July | 497.00000 | 27.00026 | 26.87196 | 0.32494 | 7.27462 |
August | 514.00000 | 27.04589 | 26.40022 | 0.38082 | 8.20908 |
September | 485.00000 | 27.00049 | 25.35208 | 0.17681 | 5.79225 |
October | 502.00000 | 27.00006 | 22.37516 | 0.83704 | 19.84100 |
November | 489.00000 | 27.00000 | 18.48603 | 0.80734 | 18.84521 |
December | 497.00000 | 26.99999 | 14.82094 | 0.76685 | 17.54905 |
Annual Sum or Average | 5943.00000 | 27.00315 | 20.67242 | 0.55312 | 13.09473 |
Minimum of Months | 454.00000 | 26.98897 | 13.63439 | 0.13867 | 5.55579 |
Maximum of Months | 514.00000 | 27.04589 | 26.87196 | 0.88360 | 21.55804 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.59906 | 13.70522 | 0.40618 | 9.40843 |
February | 454.00000 | 27.00000 | 14.88885 | 0.55575 | 11.69536 |
March | 514.00000 | 26.99999 | 16.85232 | 0.63390 | 13.65222 |
April | 485.00000 | 27.00002 | 19.96182 | 0.73539 | 16.55200 |
May | 508.00000 | 27.00014 | 22.22080 | 0.03963 | 5.33441 |
June | 496.00000 | 27.00042 | 25.70157 | 0.15714 | 5.67016 |
July | 497.00000 | 27.00027 | 26.87174 | 0.21965 | 6.12594 |
August | 514.00000 | 27.02138 | 26.42053 | 0.23301 | 6.32112 |
September | 485.00000 | 27.00042 | 25.44936 | 0.08803 | 5.40256 |
October | 502.00000 | 27.00006 | 22.35726 | 0.72523 | 16.18475 |
November | 489.00000 | 27.00000 | 18.46007 | 0.64428 | 13.90827 |
December | 497.00000 | 27.00000 | 14.79446 | 0.55565 | 11.70667 |
Annual Sum or Average | 5943.00000 | 26.96809 | 20.67992 | 0.41455 | 10.13932 |
Minimum of Months | 454.00000 | 26.59906 | 13.70522 | 0.03963 | 5.33441 |
Maximum of Months | 514.00000 | 27.02138 | 26.87174 | 0.73539 | 16.55200 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 25.53675 | 14.20309 | 0.13668 | 8.51379 |
February | 454.00000 | 26.99224 | 14.89059 | 0.48255 | 10.20312 |
March | 514.00000 | 27.00000 | 16.85954 | 0.55981 | 11.90903 |
April | 485.00000 | 27.00002 | 19.97835 | 0.66981 | 14.77024 |
May | 508.00000 | 26.93454 | 22.28677 | -0.0315 | 6.11694 |
June | 496.00000 | 27.00043 | 25.71547 | 0.14311 | 5.75359 |
July | 497.00000 | 27.00027 | 26.88083 | 0.22026 | 6.25462 |
August | 514.00000 | 27.01817 | 26.43212 | 0.22237 | 6.36914 |
September | 485.00000 | 26.99991 | 25.55010 | 0.04246 | 5.54107 |
October | 502.00000 | 27.00006 | 22.38327 | 0.65210 | 14.17897 |
November | 489.00000 | 27.00001 | 18.47252 | 0.55384 | 11.72103 |
December | 497.00000 | 27.00000 | 14.80600 | 0.47626 | 10.07916 |
Annual Sum or Average | 5943.00000 | 26.87184 | 20.74505 | 0.34234 | 9.26815 |
Minimum of Months | 454.00000 | 25.53675 | 14.20309 | -0.0315 | 5.54107 |
Maximum of Months | 514.00000 | 27.01817 | 26.88083 | 0.66981 | 14.77024 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.99980 | 30.00055 | 0.97589 | 25.15709 |
February | 454.00000 | 27.01062 | 29.99982 | 1.16880 | 33.76188 |
March | 514.00000 | 27.00786 | 29.99987 | 1.33286 | 41.97758 |
April | 485.00000 | 27.07347 | 29.99883 | 1.49169 | 50.45207 |
May | 508.00000 | 27.00179 | 30.00194 | 0.45167 | 9.29905 |
June | 496.00000 | 27.00957 | 29.99936 | 0.69806 | 15.26053 |
July | 497.00000 | 27.00538 | 30.02706 | 0.91850 | 22.82826 |
August | 514.00000 | 28.71708 | 29.87953 | 1.60532 | 55.79462 |
September | 485.00000 | 27.00302 | 30.00204 | 0.51111 | 10.52268 |
October | 502.00000 | 27.01098 | 29.99906 | 1.23923 | 37.19146 |
November | 489.00000 | 27.00792 | 29.99861 | 1.36541 | 43.68085 |
December | 497.00000 | 27.00091 | 30.00032 | 1.47342 | 49.46156 |
Annual Sum or Average | 5943.00000 | 27.15928 | 29.99188 | 1.10321 | 32.98597 |
Minimum of Months | 454.00000 | 26.99980 | 29.87953 | 0.45167 | 9.29905 |
Maximum of Months | 514.00000 | 28.71708 | 30.02706 | 1.60532 | 55.79462 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.50127 | 12.64057 | 0.04024 | 6.86967 |
February | 454.00000 | 23.94289 | 14.41213 | 0.15415 | 6.45092 |
March | 514.00000 | 24.23480 | 15.38839 | 0.23934 | 6.51600 |
April | 485.00000 | 24.42467 | 18.87525 | 0.31016 | 7.32574 |
May | 508.00000 | 24.44985 | 22.55057 | -0.5208 | 11.63479 |
June | 496.00000 | 24.42209 | 31.20408 | -0.4497 | 9.99596 |
July | 497.00000 | 24.58546 | 35.62400 | -0.3588 | 8.94712 |
August | 514.00000 | 24.46500 | 30.75910 | -0.4194 | 9.60090 |
September | 485.00000 | 24.52450 | 30.36671 | -0.4186 | 9.78865 |
October | 502.00000 | 24.55889 | 21.01180 | 0.37142 | 8.45045 |
November | 489.00000 | 24.53096 | 16.53006 | 0.32522 | 7.70500 |
December | 497.00000 | 24.20942 | 13.66545 | 0.22590 | 6.75759 |
Annual Sum or Average | 5943.00000 | 24.32255 | 21.96731 | -0.0443 | 8.35360 |
Minimum of Months | 454.00000 | 23.50127 | 12.64057 | -0.5208 | 6.45092 |
Maximum of Months | 514.00000 | 24.58546 | 35.62400 | 0.37142 | 11.63479 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.52028 | 14.45540 | 0.02581 | 6.05894 |
February | 454.00000 | 23.90343 | 16.00294 | 0.14503 | 5.95652 |
March | 514.00000 | 24.18080 | 16.65687 | 0.24055 | 6.43500 |
April | 485.00000 | 24.32035 | 19.90334 | 0.31550 | 7.32604 |
May | 508.00000 | 24.32052 | 23.86512 | -0.5390 | 11.73920 |
June | 496.00000 | 24.23492 | 32.52524 | -0.4650 | 9.87419 |
July | 497.00000 | 24.28900 | 36.53991 | -0.4034 | 8.83294 |
August | 514.00000 | 24.22617 | 31.91454 | -0.4430 | 9.37106 |
September | 485.00000 | 24.29437 | 31.65399 | -0.4707 | 10.19399 |
October | 502.00000 | 24.36946 | 22.65653 | 0.33996 | 7.71123 |
November | 489.00000 | 24.35163 | 18.03320 | 0.29093 | 7.03952 |
December | 497.00000 | 24.18297 | 15.18563 | 0.21769 | 6.32966 |
Annual Sum or Average | 5943.00000 | 24.18408 | 23.32969 | -0.0647 | 8.08980 |
Minimum of Months | 454.00000 | 23.52028 | 14.45540 | -0.5390 | 5.95652 |
Maximum of Months | 514.00000 | 24.36946 | 36.53991 | 0.33996 | 11.73920 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.94538 | 17.74308 | -0.3613 | 9.11854 |
February | 454.00000 | 22.57328 | 17.92095 | -0.1979 | 7.19000 |
March | 514.00000 | 23.26116 | 18.69347 | -0.0115 | 6.01006 |
April | 485.00000 | 23.78830 | 21.68714 | 0.15515 | 5.87211 |
May | 508.00000 | 24.03527 | 24.86976 | -0.6705 | 15.38184 |
June | 496.00000 | 24.11329 | 33.10609 | -0.5402 | 11.46662 |
July | 497.00000 | 24.22214 | 37.01077 | -0.4672 | 10.00465 |
August | 514.00000 | 24.20667 | 32.24317 | -0.5063 | 10.68368 |
September | 485.00000 | 24.11451 | 32.40206 | -0.5638 | 12.28494 |
October | 502.00000 | 23.89454 | 24.39912 | 0.19910 | 6.06627 |
November | 489.00000 | 23.36441 | 20.19547 | 0.02069 | 5.89825 |
December | 497.00000 | 22.39148 | 17.38110 | -0.2449 | 7.95956 |
Annual Sum or Average | 5943.00000 | 23.49882 | 24.84755 | -0.2672 | 9.01694 |
Minimum of Months | 454.00000 | 21.94538 | 17.38110 | -0.6705 | 5.87211 |
Maximum of Months | 514.00000 | 24.22214 | 37.01077 | 0.19910 | 15.38184 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.56856 | 15.97649 | -0.7432 | 19.19506 |
February | 454.00000 | 21.17089 | 18.56823 | -0.5616 | 13.85624 |
March | 514.00000 | 21.86975 | 20.20182 | -0.3653 | 10.25571 |
April | 485.00000 | 22.72085 | 23.46932 | -0.1150 | 7.11972 |
May | 508.00000 | 23.43250 | 25.86319 | -0.8897 | 24.47280 |
June | 496.00000 | 23.96145 | 33.29917 | -0.5907 | 13.20022 |
July | 497.00000 | 24.15919 | 36.99053 | -0.4786 | 10.29016 |
August | 514.00000 | 24.12140 | 32.36775 | -0.5354 | 11.53922 |
September | 485.00000 | 23.67399 | 33.51488 | -0.7283 | 18.37982 |
October | 502.00000 | 22.67717 | 26.81790 | -0.1094 | 6.83615 |
November | 489.00000 | 21.63490 | 21.98027 | -0.4167 | 11.17225 |
December | 497.00000 | 20.83203 | 18.16659 | -0.6516 | 16.99754 |
Annual Sum or Average | 5943.00000 | 22.57960 | 25.64146 | -0.5158 | 13.61820 |
Minimum of Months | 454.00000 | 20.56856 | 15.97649 | -0.8897 | 6.83615 |
Maximum of Months | 514.00000 | 24.15919 | 36.99053 | -0.1094 | 24.47280 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.92891 | 14.31080 | -0.6378 | 15.78610 |
February | 454.00000 | 21.69150 | 16.58721 | -0.4103 | 10.55346 |
March | 514.00000 | 22.62902 | 17.39625 | -0.1612 | 7.07130 |
April | 485.00000 | 23.48733 | 20.38649 | 0.08221 | 5.77324 |
May | 508.00000 | 23.77575 | 24.06345 | -0.7447 | 18.52869 |
June | 496.00000 | 24.16126 | 31.92532 | -0.4873 | 10.58133 |
July | 497.00000 | 24.34395 | 35.57854 | -0.3693 | 8.54923 |
August | 514.00000 | 24.20524 | 31.30227 | -0.4613 | 10.01505 |
September | 485.00000 | 23.91303 | 31.84031 | -0.6344 | 15.30220 |
October | 502.00000 | 23.41910 | 23.34571 | 0.07664 | 5.70320 |
November | 489.00000 | 22.61263 | 18.96336 | -0.1568 | 6.89480 |
December | 497.00000 | 21.67511 | 15.91415 | -0.4095 | 10.35514 |
Annual Sum or Average | 5943.00000 | 23.07988 | 23.50990 | -0.3600 | 10.43426 |
Minimum of Months | 454.00000 | 20.92891 | 14.31080 | -0.7447 | 5.70320 |
Maximum of Months | 514.00000 | 24.34395 | 35.57854 | 0.08221 | 18.52869 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.96773 | 13.53916 | -0.6221 | 15.51971 |
February | 454.00000 | 21.77176 | 15.73539 | -0.3751 | 10.60073 |
March | 514.00000 | 22.42358 | 16.73798 | -0.1767 | 7.80943 |
April | 485.00000 | 23.24193 | 20.10946 | 0.07346 | 6.76592 |
May | 508.00000 | 23.65002 | 23.58995 | -0.7081 | 18.37073 |
June | 496.00000 | 24.16745 | 31.63004 | -0.3908 | 10.34476 |
July | 497.00000 | 24.36718 | 35.30888 | -0.2552 | 8.23284 |
August | 514.00000 | 24.09385 | 31.21573 | -0.4039 | 9.96156 |
September | 485.00000 | 23.89737 | 31.43334 | -0.5625 | 14.79323 |
October | 502.00000 | 23.26327 | 22.90799 | 0.07731 | 6.34003 |
November | 489.00000 | 22.29511 | 18.52858 | -0.2113 | 7.53340 |
December | 497.00000 | 21.33393 | 15.44164 | -0.4832 | 11.59744 |
Annual Sum or Average | 5943.00000 | 22.96448 | 23.05948 | -0.3371 | 10.66458 |
Minimum of Months | 454.00000 | 20.96773 | 13.53916 | -0.7081 | 6.34003 |
Maximum of Months | 514.00000 | 24.36718 | 35.30888 | 0.07731 | 18.37073 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.55678 | 13.31973 | -0.4694 | 14.03670 |
February | 454.00000 | 22.47360 | 15.12984 | -0.1845 | 10.17709 |
March | 514.00000 | 22.78130 | 16.34584 | -0.0776 | 8.17363 |
April | 485.00000 | 23.38264 | 19.99018 | 0.10168 | 7.12508 |
May | 508.00000 | 23.57838 | 23.79766 | -0.7594 | 20.78569 |
June | 496.00000 | 24.09369 | 31.84401 | -0.4676 | 11.32357 |
July | 497.00000 | 24.35489 | 35.37914 | -0.3028 | 8.40866 |
August | 514.00000 | 24.22650 | 30.93775 | -0.3527 | 9.13459 |
September | 485.00000 | 24.05822 | 31.04945 | -0.4712 | 13.59843 |
October | 502.00000 | 23.63038 | 22.22078 | 0.19788 | 7.77939 |
November | 489.00000 | 22.97301 | 17.73589 | -0.0286 | 8.09830 |
December | 497.00000 | 22.06871 | 14.84698 | -0.2950 | 10.83501 |
Annual Sum or Average | 5943.00000 | 23.26980 | 22.76415 | -0.2607 | 10.80585 |
Minimum of Months | 454.00000 | 21.55678 | 13.31973 | -0.7594 | 7.12508 |
Maximum of Months | 514.00000 | 24.35489 | 35.37914 | 0.19788 | 20.78569 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.34274 | 13.02494 | -0.4975 | 12.23465 |
February | 454.00000 | 22.57841 | 14.70987 | -0.1435 | 8.05251 |
March | 514.00000 | 23.55706 | 15.38021 | 0.12698 | 6.75817 |
April | 485.00000 | 24.34122 | 18.54846 | 0.38907 | 8.99812 |
May | 508.00000 | 24.05035 | 22.94712 | -0.5306 | 13.81375 |
June | 496.00000 | 24.37809 | 31.15200 | -0.2613 | 7.98993 |
July | 497.00000 | 24.59403 | 34.77484 | -0.0994 | 7.17243 |
August | 514.00000 | 24.48336 | 30.30269 | -0.1468 | 7.12104 |
September | 485.00000 | 24.14199 | 30.80279 | -0.4364 | 11.81331 |
October | 502.00000 | 23.99887 | 21.62031 | 0.28467 | 7.53031 |
November | 489.00000 | 23.60773 | 16.82590 | 0.13530 | 6.74909 |
December | 497.00000 | 23.01332 | 13.74045 | -0.0445 | 6.87861 |
Annual Sum or Average | 5943.00000 | 23.68052 | 22.03181 | -0.1026 | 8.76146 |
Minimum of Months | 454.00000 | 21.34274 | 13.02494 | -0.5306 | 6.74909 |
Maximum of Months | 514.00000 | 24.59403 | 34.77484 | 0.38907 | 13.81375 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.91760 | 14.47799 | -0.9657 | 26.89056 |
February | 454.00000 | 20.37997 | 17.38590 | -0.7875 | 19.82083 |
March | 514.00000 | 20.90316 | 18.94683 | -0.5999 | 14.44260 |
April | 485.00000 | 21.98357 | 22.70643 | -0.2854 | 8.51865 |
May | 508.00000 | 22.92271 | 25.53080 | -1.0477 | 31.13625 |
June | 496.00000 | 23.88572 | 32.63841 | -0.6073 | 13.89615 |
July | 497.00000 | 24.20417 | 35.76365 | -0.4524 | 10.01116 |
August | 514.00000 | 24.01436 | 31.73771 | -0.5738 | 12.89029 |
September | 485.00000 | 23.24736 | 33.17398 | -0.8742 | 24.75376 |
October | 502.00000 | 21.96100 | 25.65847 | -0.2758 | 8.11022 |
November | 489.00000 | 20.77962 | 20.62977 | -0.6251 | 15.44943 |
December | 497.00000 | 20.03829 | 17.04200 | -0.8824 | 23.85789 |
Annual Sum or Average | 5943.00000 | 22.03297 | 24.68218 | -0.6645 | 17.47479 |
Minimum of Months | 454.00000 | 19.91760 | 14.47799 | -1.0477 | 8.11022 |
Maximum of Months | 514.00000 | 24.20417 | 35.76365 | -0.2758 | 31.13625 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 19.95133 | 13.36786 | -0.9424 | 25.86349 |
February | 385.00000 | 20.61672 | 16.01297 | -0.7084 | 17.98587 |
March | 433.00000 | 21.17852 | 17.33763 | -0.5111 | 13.18280 |
April | 410.00000 | 22.33356 | 21.02681 | -0.1630 | 8.46268 |
May | 430.00000 | 23.02210 | 24.29964 | -0.9441 | 28.10880 |
June | 418.00000 | 24.06914 | 31.55430 | -0.4468 | 12.64977 |
July | 422.00000 | 24.45320 | 34.70274 | -0.2552 | 9.09107 |
August | 433.00000 | 24.14198 | 30.58937 | -0.4262 | 11.41520 |
September | 410.00000 | 23.45999 | 31.97778 | -0.7317 | 21.77415 |
October | 427.00000 | 22.16141 | 24.10014 | -0.1997 | 7.69974 |
November | 417.00000 | 20.88629 | 19.15810 | -0.5863 | 14.26834 |
December | 422.00000 | 19.97800 | 15.81107 | -0.8847 | 23.93359 |
Annual Sum or Average | 5034.00000 | 22.19679 | 23.35963 | -0.5664 | 16.20278 |
Minimum of Months | 385.00000 | 19.95133 | 13.36786 | -0.9441 | 7.69974 |
Maximum of Months | 433.00000 | 24.45320 | 34.70274 | -0.1630 | 28.10880 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.95853 | 13.33581 | -0.6503 | 18.52462 |
February | 454.00000 | 21.86920 | 15.42796 | -0.3501 | 13.22558 |
March | 514.00000 | 22.05471 | 17.06601 | -0.2621 | 10.86532 |
April | 485.00000 | 22.70984 | 21.03526 | -0.0645 | 8.33512 |
May | 508.00000 | 23.14588 | 24.51919 | -0.9108 | 27.05907 |
June | 496.00000 | 23.88398 | 32.29851 | -0.5520 | 13.96866 |
July | 497.00000 | 24.27752 | 35.39236 | -0.3511 | 9.51631 |
August | 514.00000 | 24.14446 | 30.96018 | -0.4083 | 10.78951 |
September | 485.00000 | 23.81344 | 31.49998 | -0.5518 | 17.07673 |
October | 502.00000 | 23.14525 | 23.05234 | 0.08523 | 8.35858 |
November | 489.00000 | 22.25062 | 18.42250 | -0.2157 | 10.66059 |
December | 497.00000 | 21.06372 | 15.60164 | -0.5735 | 16.81336 |
Annual Sum or Average | 5943.00000 | 22.78287 | 23.26512 | -0.4017 | 13.78571 |
Minimum of Months | 454.00000 | 20.95853 | 13.33581 | -0.9108 | 8.33512 |
Maximum of Months | 514.00000 | 24.27752 | 35.39236 | 0.08523 | 27.05907 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.19643 | 13.61622 | -0.8705 | 23.12034 |
February | 454.00000 | 20.83553 | 16.13733 | -0.6359 | 16.23095 |
March | 514.00000 | 21.31980 | 17.66680 | -0.4605 | 12.13042 |
April | 485.00000 | 22.40851 | 21.31321 | -0.1320 | 7.93979 |
May | 508.00000 | 23.15241 | 24.43074 | -0.8765 | 26.31653 |
June | 496.00000 | 23.89712 | 32.25752 | -0.4970 | 13.06660 |
July | 497.00000 | 24.29307 | 35.39506 | -0.3054 | 9.07515 |
August | 514.00000 | 24.08864 | 31.14108 | -0.4295 | 11.16868 |
September | 485.00000 | 23.35838 | 32.30897 | -0.7444 | 22.16957 |
October | 502.00000 | 22.25902 | 24.27875 | -0.1611 | 7.60327 |
November | 489.00000 | 21.19090 | 19.36246 | -0.4938 | 12.64462 |
December | 497.00000 | 20.29366 | 16.04699 | -0.7864 | 20.59425 |
Annual Sum or Average | 5943.00000 | 22.28592 | 23.70673 | -0.5325 | 15.16904 |
Minimum of Months | 454.00000 | 20.19643 | 13.61622 | -0.8765 | 7.60327 |
Maximum of Months | 514.00000 | 24.29307 | 35.39506 | -0.1320 | 26.31653 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.63467 | 14.26707 | -1.1054 | 32.96683 |
February | 454.00000 | 19.97783 | 17.44940 | -0.9442 | 26.12491 |
March | 514.00000 | 20.34619 | 19.25935 | -0.7880 | 20.48139 |
April | 485.00000 | 21.12504 | 23.55219 | -0.5169 | 13.56936 |
May | 508.00000 | 22.30651 | 26.22416 | -1.2713 | 40.45144 |
June | 496.00000 | 23.57400 | 33.12288 | -0.7077 | 18.15136 |
July | 497.00000 | 24.04068 | 36.03448 | -0.4966 | 11.62565 |
August | 514.00000 | 23.75775 | 32.17300 | -0.6545 | 16.10983 |
September | 485.00000 | 22.65499 | 34.16128 | -1.0831 | 34.19559 |
October | 502.00000 | 20.98156 | 26.91193 | -0.5382 | 13.51798 |
November | 489.00000 | 20.10701 | 21.28134 | -0.8475 | 22.87883 |
December | 497.00000 | 19.79629 | 16.90183 | -1.0189 | 29.34100 |
Annual Sum or Average | 5943.00000 | 21.53891 | 25.15361 | -0.8305 | 23.26612 |
Minimum of Months | 454.00000 | 19.63467 | 14.26707 | -1.2713 | 11.62565 |
Maximum of Months | 514.00000 | 24.04068 | 36.03448 | -0.4966 | 40.45144 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.80794 | 13.94441 | -1.0422 | 30.19273 |
February | 454.00000 | 20.24626 | 16.78820 | -0.8437 | 22.66390 |
March | 514.00000 | 20.77297 | 18.38526 | -0.6484 | 17.23375 |
April | 485.00000 | 21.84929 | 22.03422 | -0.3023 | 11.42994 |
May | 508.00000 | 22.74440 | 25.01100 | -1.0494 | 31.86694 |
June | 496.00000 | 23.92523 | 31.94078 | -0.4757 | 13.83944 |
July | 497.00000 | 24.31609 | 35.12758 | -0.2628 | 9.23958 |
August | 514.00000 | 24.00554 | 31.13798 | -0.4404 | 12.20358 |
September | 485.00000 | 23.18263 | 32.81399 | -0.8311 | 25.83803 |
October | 502.00000 | 21.50654 | 25.66085 | -0.3800 | 11.00080 |
November | 489.00000 | 20.29010 | 20.62330 | -0.7778 | 20.43542 |
December | 497.00000 | 19.86292 | 16.49291 | -0.9833 | 27.92809 |
Annual Sum or Average | 5943.00000 | 21.88932 | 24.20468 | -0.6689 | 19.46699 |
Minimum of Months | 454.00000 | 19.80794 | 13.94441 | -1.0494 | 9.23958 |
Maximum of Months | 514.00000 | 24.31609 | 35.12758 | -0.2628 | 31.86694 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.36422 | 13.62123 | -0.8501 | 24.61601 |
February | 454.00000 | 21.21712 | 15.96183 | -0.5530 | 17.53780 |
March | 514.00000 | 21.39838 | 17.73375 | -0.4649 | 15.21264 |
April | 485.00000 | 22.03747 | 21.91475 | -0.2562 | 11.58680 |
May | 508.00000 | 22.69292 | 25.18706 | -1.0871 | 34.02751 |
June | 496.00000 | 23.63553 | 32.68260 | -0.6339 | 17.52387 |
July | 497.00000 | 24.12947 | 35.63936 | -0.3890 | 11.03065 |
August | 514.00000 | 23.96728 | 31.27950 | -0.4635 | 13.09440 |
September | 485.00000 | 23.43445 | 32.26965 | -0.6983 | 23.15972 |
October | 502.00000 | 22.38275 | 24.29534 | -0.1288 | 10.52543 |
November | 489.00000 | 21.34090 | 19.48578 | -0.4787 | 15.05388 |
December | 497.00000 | 20.45757 | 16.04153 | -0.7785 | 22.64093 |
Annual Sum or Average | 5943.00000 | 22.26318 | 23.88904 | -0.5660 | 18.01766 |
Minimum of Months | 454.00000 | 20.36422 | 13.62123 | -1.0871 | 10.52543 |
Maximum of Months | 514.00000 | 24.12947 | 35.63936 | -0.1288 | 34.02751 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.86638 | 13.79799 | -1.0141 | 29.15888 |
February | 454.00000 | 20.42138 | 16.49166 | -0.7832 | 21.13863 |
March | 514.00000 | 20.83962 | 18.15050 | -0.6207 | 16.54163 |
April | 485.00000 | 21.76747 | 22.10030 | -0.3106 | 10.98614 |
May | 508.00000 | 22.71695 | 25.03039 | -1.0425 | 32.93555 |
June | 496.00000 | 23.65308 | 32.60050 | -0.5762 | 16.45715 |
July | 497.00000 | 24.14765 | 35.63112 | -0.3424 | 10.47238 |
August | 514.00000 | 23.89710 | 31.47820 | -0.4891 | 13.54957 |
September | 485.00000 | 22.95492 | 33.08046 | -0.8943 | 28.82685 |
October | 502.00000 | 21.55163 | 25.39525 | -0.3580 | 10.80979 |
November | 489.00000 | 20.56106 | 20.18322 | -0.6922 | 18.22134 |
December | 497.00000 | 19.98811 | 16.25286 | -0.9225 | 25.71403 |
Annual Sum or Average | 5943.00000 | 21.87618 | 24.22602 | -0.6700 | 19.55684 |
Minimum of Months | 454.00000 | 19.86638 | 13.79799 | -1.0425 | 10.47238 |
Maximum of Months | 514.00000 | 24.14765 | 35.63112 | -0.3106 | 32.93555 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.111757E+09 | 2527.43 | 18-JAN-04:18 | 12.30 | 0.508937E+09 | 0.00 | 0.620694E+09 | 0.08 | 4.56 | 17-JAN-06:40 | 0.00 | 0.00 |
February | 0.112444E+10 | 52835.20 | 27-FEB-15:30 | 34.31 | 0.619249E+10 | 0.00 | 0.731693E+10 | 0.24 | 6.53 | 27-FEB-13:40 | 0.00 | 0.00 |
March | 0.514738E+09 | 7570.37 | 14-MAR-13:30 | 54.13 | 0.234419E+10 | 0.00 | 0.285892E+10 | 0.33 | 4.56 | 10-MAR-06:50 | 0.00 | 0.00 |
April | 0.954570E+10 | 77868.44 | 07-APR-13:10 | 120.25 | 0.543460E+11 | 0.00 | 0.638917E+11 | 0.83 | 7.37 | 07-APR-13:10 | 0.00 | 0.00 |
May | 0.262949E+11 | 87346.43 | 19-MAY-15:30 | 200.13 | 0.162653E+12 | 0.00 | 0.188948E+12 | 1.48 | 7.39 | 30-MAY-14:50 | 0.00 | 0.00 |
June | 0.659687E+11 | 98246.31 | 29-JUN-14:50 | 375.43 | 0.431326E+12 | 0.00 | 0.497295E+12 | 3.10 | 7.60 | 30-JUN-10:10 | 0.00 | 0.00 |
July | 0.100781E+12 | 116740.22 | 17-JUL-15:30 | 512.27 | 0.682296E+12 | 0.00 | 0.783077E+12 | 4.26 | 7.54 | 25-JUL-15:20 | 0.00 | 0.00 |
August | 0.886349E+11 | 108298.91 | 07-AUG-15:40 | 496.69 | 0.596761E+12 | 0.00 | 0.685396E+12 | 4.02 | 7.53 | 10-AUG-15:40 | 0.00 | 0.00 |
September | 0.485952E+11 | 150202.28 | 07-SEP-15:00 | 300.52 | 0.315353E+12 | 0.00 | 0.363948E+12 | 2.43 | 7.51 | 07-SEP-14:10 | 0.00 | 0.00 |
October | 0.145972E+11 | 80382.25 | 18-OCT-15:00 | 146.74 | 0.886554E+11 | 0.00 | 0.103253E+12 | 1.03 | 7.43 | 16-OCT-14:50 | 0.00 | 0.00 |
November | 0.151830E+10 | 31679.58 | 17-NOV-17:00 | 62.69 | 0.687817E+10 | 0.00 | 0.839647E+10 | 0.40 | 4.56 | 13-NOV-14:00 | 0.00 | 0.00 |
December | 0.172171E+09 | 2560.62 | 11-DEC-04:52 | 18.94 | 0.783965E+09 | 0.00 | 0.956136E+09 | 0.12 | 4.56 | 11-DEC-06:50 | 0.00 | 0.00 |
Annual Sum or Average | 0.357859E+12 | 2334.39 | 0.234810E+13 | 0.00 | 0.270596E+13 | 1.53 | 0.00 | 0.00 | ||||
Minimum of Months | 0.111757E+09 | 2527.43 | 12.30 | 0.508937E+09 | 0.00 | 0.620694E+09 | 0.08 | 4.56 | 0.00 | 0.00 | ||
Maximum of Months | 0.100781E+12 | 150202.28 | 512.27 | 0.682296E+12 | 0.00 | 0.783077E+12 | 4.26 | 7.60 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
May | 0.178522E+10 | 87346.43 | 19-MAY-15:30 | 6.17 | 0.129395E+11 | 0.00 | 0.147247E+11 | 0.06 | 7.35 | 19-MAY-15:30 | 0.00 | 0.00 |
June | 0.194309E+11 | 98246.31 | 29-JUN-14:50 | 64.83 | 0.141263E+12 | 0.00 | 0.160694E+12 | 0.65 | 7.48 | 26-JUN-09:50 | 0.00 | 0.00 |
July | 0.415105E+11 | 116740.22 | 17-JUL-15:30 | 133.26 | 0.303661E+12 | 0.00 | 0.345171E+12 | 1.31 | 7.54 | 25-JUL-15:20 | 0.00 | 0.00 |
August | 0.340399E+11 | 108298.91 | 07-AUG-15:40 | 109.94 | 0.249780E+12 | 0.00 | 0.283819E+12 | 1.08 | 7.53 | 10-AUG-15:40 | 0.00 | 0.00 |
September | 0.100987E+11 | 150202.28 | 07-SEP-15:00 | 33.70 | 0.732398E+11 | 0.00 | 0.833385E+11 | 0.34 | 7.51 | 07-SEP-14:10 | 0.00 | 0.00 |
October | 0.785820E+09 | 80382.25 | 18-OCT-15:00 | 2.83 | 0.565962E+10 | 0.00 | 0.644544E+10 | 0.03 | 7.24 | 18-OCT-15:30 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.107651E+12 | 350.73 | 0.786543E+12 | 0.00 | 0.894194E+12 | 0.29 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.415105E+11 | 150202.28 | 133.26 | 0.303661E+12 | 0.00 | 0.345171E+12 | 1.31 | 7.54 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: CENTRAL TOWER
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.843533E+10 | 744.00 | 7364.57 | 14-JAN-15:00 | 199897.32 | 13-JAN-16:30 | 21.67 | 18.33 | 15.23 |
February | 0.213315E+11 | 672.00 | 49248.27 | 20-FEB-15:40 | 385581.79 | 26-FEB-17:03 | 24.69 | 18.36 | 15.23 |
March | 0.385604E+11 | 744.00 | 49248.27 | 14-MAR-11:20 | 644974.42 | 31-MAR-24:00 | 27.63 | 18.34 | 15.23 |
April | 0.827600E+11 | 720.00 | 49248.27 | 01-APR-11:00 | 703792.97 | 16-APR-18:02 | 31.47 | 19.18 | 15.23 |
May | 0.527754E+11 | 744.00 | 49248.27 | 02-MAY-10:20 | 364849.72 | 31-MAY-24:00 | 23.15 | 19.25 | 15.23 |
June | 0.103150E+12 | 720.00 | 49248.27 | 01-JUN-00:10 | 526673.40 | 30-JUN-23:33 | 29.07 | 22.12 | 15.23 |
July | 0.127740E+12 | 744.00 | 49248.27 | 01-JUL-00:05 | 684145.34 | 31-JUL-23:42 | 36.32 | 26.36 | 15.23 |
August | 0.129341E+12 | 744.00 | 49248.27 | 01-AUG-00:05 | 757465.69 | 05-AUG-19:32 | 39.14 | 26.41 | 15.23 |
September | 0.752936E+11 | 720.00 | 49248.27 | 01-SEP-00:03 | 353766.49 | 30-SEP-24:00 | 24.69 | 20.67 | 15.23 |
October | 0.609917E+11 | 744.00 | 49248.27 | 02-OCT-13:20 | 497549.51 | 31-OCT-24:00 | 25.60 | 18.89 | 15.23 |
November | 0.524449E+11 | 720.00 | 49248.27 | 01-NOV-10:55 | 527092.56 | 03-NOV-16:00 | 27.82 | 18.44 | 15.23 |
December | 0.421852E+11 | 744.00 | 49248.27 | 05-DEC-13:10 | 662557.64 | 06-DEC-16:10 | 30.30 | 18.34 | 15.23 |
Annual Sum or Average | 0.795009E+12 | 8760.00 | 28.50 | 20.41 | 15.23 | ||||
Minimum of Months | 0.843533E+10 | 672.00 | 7364.57 | 199897.32 | 21.67 | 18.33 | 15.23 | ||
Maximum of Months | 0.129341E+12 | 744.00 | 49248.27 | 757465.69 | 39.14 | 26.41 | 15.23 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 208849.10 | 18-JAN-04:02 | 20.97 | 20.97 | 0.08 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 410832.06 | 27-FEB-15:30 | 21.00 | 20.98 | 0.72 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 209075.78 | 31-MAR-06:00 | 20.98 | 20.97 | 0.60 |
April | 27096339.42 | 40.68 | 889.48 | 06-APR-15:50 | 816823.01 | 07-APR-14:00 | 21.11 | 20.99 | 5.08 |
May | 0.186008E+09 | 128.26 | 2131.22 | 20-MAY-15:50 | 1078483.55 | 19-MAY-15:30 | 21.39 | 21.03 | 11.25 |
June | 0.200991E+10 | 297.23 | 15518.24 | 06-JUN-14:50 | 1097568.77 | 28-JUN-13:40 | 22.14 | 21.11 | 24.98 |
July | 0.392592E+10 | 419.24 | 15518.24 | 01-JUL-13:20 | 1097282.85 | 20-JUL-15:20 | 22.73 | 21.15 | 33.70 |
August | 0.168124E+10 | 366.99 | 15518.24 | 05-AUG-11:30 | 1097807.29 | 11-AUG-12:20 | 22.50 | 21.08 | 30.63 |
September | 0.140948E+10 | 222.23 | 15518.24 | 02-SEP-10:40 | 1212323.70 | 07-SEP-15:00 | 21.90 | 21.17 | 19.27 |
October | 57029348.08 | 66.37 | 971.27 | 18-OCT-16:10 | 960110.07 | 18-OCT-12:40 | 21.28 | 21.08 | 7.01 |
November | 208561.91 | 3.50 | 40.21 | 17-NOV-17:00 | 208562.18 | 29-NOV-05:00 | 21.02 | 21.00 | 1.31 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 208497.15 | 15-DEC-06:50 | 21.02 | 21.02 | 0.14 |
Annual Sum or Average | 0.929688E+10 | 1544.51 | 21.51 | 21.05 | 11.30 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 208497.15 | 20.97 | 20.97 | 0.08 | ||
Maximum of Months | 0.392592E+10 | 419.24 | 15518.24 | 1212323.70 | 22.73 | 21.17 | 33.70 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 20.97 | 20.97 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 21.00 | 21.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 20.98 | 20.98 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 21.11 | 21.11 | 0.00 |
May | 25295218.02 | 4.50 | 1720.10 | 19-MAY-12:40 | 1078483.55 | 19-MAY-15:30 | 21.39 | 21.36 | 0.32 |
June | 0.103644E+10 | 50.00 | 15518.24 | 06-JUN-14:50 | 1097568.77 | 28-JUN-13:40 | 22.14 | 21.86 | 3.65 |
July | 0.233712E+10 | 109.50 | 15518.24 | 13-JUL-13:10 | 1097282.85 | 20-JUL-15:20 | 22.73 | 22.12 | 7.75 |
August | 0.859009E+09 | 91.67 | 15518.24 | 05-AUG-12:40 | 1097807.29 | 11-AUG-12:20 | 22.50 | 21.97 | 6.48 |
September | 0.648673E+09 | 27.67 | 15518.24 | 02-SEP-10:40 | 1212323.70 | 07-SEP-15:00 | 21.90 | 21.74 | 2.02 |
October | 297921.25 | 0.17 | 496.54 | 18-OCT-13:00 | 927815.58 | 18-OCT-13:00 | 21.28 | 21.27 | 0.01 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 21.02 | 21.02 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 21.02 | 21.02 | 0.00 |
Annual Sum or Average | 0.490684E+10 | 283.50 | 21.51 | 21.37 | 1.70 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 20.97 | 20.97 | 0.00 | ||
Maximum of Months | 0.233712E+10 | 109.50 | 15518.24 | 1212323.70 | 22.73 | 22.12 | 7.75 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.918926E+12 | 0.00 | 611.48 | 1978568.98 | 09-JAN-07:10 | 0.00 | 34.12 | 72.35 | 1.92 | 0.00 | 0.10 | 0.59 | 09-JAN-07:10 |
February | 0.480337E+12 | 0.00 | 461.78 | 1810107.54 | 07-FEB-06:01 | 0.00 | 29.92 | 64.28 | 1.03 | 0.00 | 0.06 | 0.54 | 07-FEB-06:01 |
March | 0.280095E+12 | 0.00 | 449.68 | 1656832.32 | 06-MAR-06:01 | 0.00 | 26.87 | 58.77 | 0.51 | 0.00 | 0.03 | 0.49 | 06-MAR-06:01 |
April | 0.703365E+11 | 0.00 | 237.17 | 1264749.54 | 19-APR-05:02 | 0.00 | 23.96 | 42.22 | 0.12 | 0.00 | 0.01 | 0.38 | 19-APR-05:02 |
May | 0.483196E+11 | 0.00 | 155.62 | 1482123.24 | 22-MAY-04:01 | 0.00 | 24.24 | 35.70 | 0.08 | 0.00 | 0.01 | 0.44 | 22-MAY-04:01 |
June | 0.119917E+10 | 0.00 | 28.17 | 127675.22 | 17-JUN-04:02 | 0.00 | 23.26 | 25.47 | 0.00 | 0.00 | 0.00 | 0.04 | 17-JUN-04:02 |
July | 1324291.66 | 0.00 | 1.83 | 599.67 | 08-JUL-05:20 | 0.00 | 23.07 | 23.21 | 0.00 | 0.00 | 0.00 | 0.00 | 08-JUL-05:20 |
August | 0.205248E+09 | 0.00 | 9.25 | 96432.44 | 18-AUG-05:03 | 0.00 | 23.23 | 23.93 | 0.00 | 0.00 | 0.00 | 0.03 | 18-AUG-05:03 |
September | 0.109112E+11 | 0.00 | 96.37 | 1235412.06 | 19-SEP-05:02 | 0.00 | 23.19 | 30.72 | 0.02 | 0.00 | 0.00 | 0.37 | 19-SEP-05:02 |
October | 0.526768E+11 | 0.00 | 239.42 | 1231242.84 | 11-OCT-05:01 | 0.00 | 23.74 | 41.62 | 0.09 | 0.00 | 0.01 | 0.37 | 11-OCT-05:01 |
November | 0.233224E+12 | 0.00 | 427.00 | 1634490.46 | 27-NOV-06:02 | 0.00 | 26.78 | 58.09 | 0.44 | 0.00 | 0.03 | 0.49 | 27-NOV-06:02 |
December | 0.592750E+12 | 0.00 | 570.27 | 1877892.63 | 26-DEC-05:01 | 0.00 | 31.22 | 69.16 | 1.15 | 0.00 | 0.07 | 0.56 | 26-DEC-05:01 |
Annual Sum or Average | 0.268898E+13 | 0.00 | 3288.04 | 0.00 | 26.12 | 45.37 | 0.44 | 0.00 | 0.03 | ||||
Minimum of Months | 1324291.66 | 0.00 | 1.83 | 599.67 | 0.00 | 23.07 | 23.21 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.918926E+12 | 0.00 | 611.48 | 1978568.98 | 0.00 | 34.12 | 72.35 | 1.92 | 0.00 | 0.10 | 0.59 |
Report: BoilerReportMonthly
For: CENTRAL BOILER
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 21.67 | 21.67 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 24.69 | 24.69 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 27.63 | 27.63 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 31.47 | 31.47 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 23.15 | 23.15 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 29.07 | 29.07 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 36.32 | 36.32 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 39.14 | 39.14 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 24.69 | 24.69 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 25.60 | 25.60 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 27.82 | 27.82 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 30.30 | 30.30 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 28.50 | 28.50 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.67 | 21.67 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.14 | 39.14 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 |
February | 0.585539E+09 | 0.00 | 11.00 | 0.585539E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39637.15 | 27-FEB-15:30 | 39637.15 | 27-FEB-15:30 | 0.00 | 0.00 | 0.00 |
March | 31058141.34 | 0.00 | 4.37 | 31058141.34 | 0.00 | 0.00 | 0.00 | 0.00 | 6585.09 | 14-MAR-13:30 | 6585.09 | 14-MAR-13:30 | 0.00 | 0.00 | 0.00 |
April | 0.618598E+10 | 0.00 | 78.27 | 0.618598E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 79355.46 | 07-APR-14:00 | 79355.46 | 07-APR-14:00 | 0.00 | 0.00 | 0.00 |
May | 0.169802E+11 | 0.00 | 170.39 | 0.169802E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 105058.47 | 19-MAY-15:20 | 105058.47 | 19-MAY-15:20 | 0.00 | 0.00 | 0.00 |
June | 0.565611E+11 | 0.00 | 353.33 | 0.565080E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 121375.46 | 29-JUN-14:50 | 121375.46 | 29-JUN-14:50 | 0.00 | 0.00 | 0.00 |
July | 0.975288E+11 | 0.00 | 489.79 | 0.973455E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 147725.16 | 17-JUL-15:20 | 147725.16 | 17-JUL-15:20 | 0.00 | 0.00 | 0.00 |
August | 0.904464E+11 | 0.00 | 476.35 | 0.904464E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 149489.42 | 07-AUG-15:20 | 149489.42 | 07-AUG-15:20 | 0.00 | 0.00 | 0.00 |
September | 0.365519E+11 | 0.00 | 262.23 | 0.353562E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 184789.40 | 07-SEP-15:00 | 118995.92 | 01-SEP-16:00 | 0.00 | 0.00 | 0.00 |
October | 0.981394E+10 | 0.00 | 109.20 | 0.981394E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 97079.12 | 18-OCT-15:50 | 97079.12 | 18-OCT-15:50 | 0.00 | 0.00 | 0.00 |
November | 0.496941E+09 | 0.00 | 22.45 | 0.496941E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16582.30 | 17-NOV-17:00 | 16582.30 | 17-NOV-17:00 | 0.00 | 0.00 | 0.00 |
December | 222.89 | 0.00 | 0.17 | 222.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 | 06-DEC-08:00 | 0.37 | 06-DEC-08:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.315182E+12 | 0.00 | 1977.55 | 0.313750E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.975288E+11 | 0.00 | 489.79 | 0.973455E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 184789.40 | 149489.42 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 19694.50 | 0.00 | 10.67 | 19694.50 | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 23-JAN-06:03 | 5.00 | 23-JAN-06:03 | 0.00 | 0.00 | 0.00 |
February | 0.391301E+10 | 0.00 | 31.37 | 0.391301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 260343.98 | 27-FEB-13:40 | 260343.98 | 27-FEB-13:40 | 0.00 | 0.00 | 0.00 |
March | 48397356.45 | 0.00 | 53.38 | 48397356.45 | 0.00 | 0.00 | 0.00 | 0.00 | 11665.00 | 14-MAR-13:40 | 11665.00 | 14-MAR-13:40 | 0.00 | 0.00 | 0.00 |
April | 0.421678E+11 | 0.00 | 109.32 | 0.421678E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 590995.09 | 06-APR-16:00 | 590995.09 | 06-APR-16:00 | 0.00 | 0.00 | 0.00 |
May | 0.142546E+12 | 0.00 | 184.02 | 0.142546E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 995840.49 | 19-MAY-15:30 | 995840.49 | 19-MAY-15:30 | 0.00 | 0.00 | 0.00 |
June | 0.478291E+12 | 0.00 | 334.88 | 0.477854E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1145978.91 | 29-JUN-14:50 | 1145978.91 | 29-JUN-14:50 | 0.00 | 0.00 | 0.00 |
July | 0.807487E+12 | 0.00 | 421.54 | 0.806461E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1338274.28 | 17-JUL-15:30 | 1338274.28 | 17-JUL-15:30 | 0.00 | 0.00 | 0.00 |
August | 0.700062E+12 | 0.00 | 390.71 | 0.700062E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1256519.71 | 10-AUG-15:40 | 1256519.71 | 10-AUG-15:40 | 0.00 | 0.00 | 0.00 |
September | 0.318686E+12 | 0.00 | 271.26 | 0.307948E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1711545.18 | 07-SEP-15:00 | 1128161.65 | 04-SEP-15:41 | 0.00 | 0.00 | 0.00 |
October | 0.744339E+11 | 0.00 | 133.05 | 0.744339E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 798022.48 | 18-OCT-15:20 | 798022.48 | 18-OCT-15:20 | 0.00 | 0.00 | 0.00 |
November | 0.339142E+10 | 0.00 | 58.00 | 0.339142E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 115588.23 | 03-NOV-14:00 | 115588.23 | 03-NOV-14:00 | 0.00 | 0.00 | 0.00 |
December | 28959.19 | 0.00 | 17.78 | 28959.19 | 0.00 | 0.00 | 0.00 | 0.00 | 1.34 | 20-DEC-06:01 | 1.34 | 20-DEC-06:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.257103E+13 | 0.00 | 2015.98 | 0.255883E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 19694.50 | 0.00 | 10.67 | 19694.50 | 0.00 | 0.00 | 0.00 | 0.00 | 1.34 | 1.34 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.807487E+12 | 0.00 | 421.54 | 0.806461E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1711545.18 | 1338274.28 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 1220.61 | 0.00 | 1.10 | 1220.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.74 | 06-JAN-06:01 | 0.74 | 06-JAN-06:01 | 0.00 | 0.00 | 0.00 |
February | 0.288330E+09 | 0.00 | 12.40 | 0.288330E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20707.13 | 26-FEB-14:31 | 20707.13 | 26-FEB-14:31 | 0.00 | 0.00 | 0.00 |
March | 1270391.95 | 0.00 | 1.64 | 1270391.95 | 0.00 | 0.00 | 0.00 | 0.00 | 1268.25 | 04-MAR-06:01 | 1268.25 | 04-MAR-06:01 | 0.00 | 0.00 | 0.00 |
April | 0.382489E+10 | 0.00 | 65.11 | 0.382489E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58522.14 | 06-APR-16:00 | 58522.14 | 06-APR-16:00 | 0.00 | 0.00 | 0.00 |
May | 0.147627E+11 | 0.00 | 154.28 | 0.147627E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 119736.54 | 19-MAY-15:30 | 119736.54 | 19-MAY-15:30 | 0.00 | 0.00 | 0.00 |
June | 0.525532E+11 | 0.00 | 321.72 | 0.524987E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 136614.94 | 29-JUN-15:00 | 136614.94 | 29-JUN-15:00 | 0.00 | 0.00 | 0.00 |
July | 0.892413E+11 | 0.00 | 421.58 | 0.891506E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 163854.81 | 17-JUL-15:30 | 163854.81 | 17-JUL-15:30 | 0.00 | 0.00 | 0.00 |
August | 0.751464E+11 | 0.00 | 382.86 | 0.751464E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 150928.45 | 07-AUG-15:40 | 150928.45 | 07-AUG-15:40 | 0.00 | 0.00 | 0.00 |
September | 0.324631E+11 | 0.00 | 243.72 | 0.314012E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 174294.92 | 07-SEP-15:20 | 139630.22 | 04-SEP-15:41 | 0.00 | 0.00 | 0.00 |
October | 0.625453E+10 | 0.00 | 93.84 | 0.625453E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 81165.67 | 18-OCT-15:00 | 81165.67 | 18-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.248191E+09 | 0.00 | 16.61 | 0.248191E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9292.84 | 04-NOV-14:00 | 9292.84 | 04-NOV-14:00 | 0.00 | 0.00 | 0.00 |
December | 63355.11 | 0.00 | 1.03 | 63355.11 | 0.00 | 0.00 | 0.00 | 0.00 | 518.69 | 11-DEC-04:52 | 518.69 | 11-DEC-04:52 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.274784E+12 | 0.00 | 1715.90 | 0.273577E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1220.61 | 0.00 | 1.03 | 1220.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.74 | 0.74 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.892413E+11 | 0.00 | 421.58 | 0.891506E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 174294.92 | 163854.81 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 109714.94 | 0.00 | 0.52 | 109714.94 | 0.00 | 0.00 | 0.00 | 0.00 | 681.13 | 24-JAN-05:01 | 681.13 | 24-JAN-05:01 | 0.00 | 0.00 | 0.00 |
February | 0.239590E+09 | 0.00 | 5.17 | 0.239590E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21759.88 | 27-FEB-15:00 | 21759.88 | 27-FEB-15:00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 |
April | 0.207821E+10 | 0.00 | 36.78 | 0.207821E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45040.95 | 07-APR-14:00 | 45040.95 | 07-APR-14:00 | 0.00 | 0.00 | 0.00 |
May | 0.809844E+10 | 0.00 | 103.76 | 0.809844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55269.49 | 29-MAY-14:13 | 55269.49 | 29-MAY-14:13 | 0.00 | 0.00 | 0.00 |
June | 0.288063E+11 | 0.00 | 229.28 | 0.287938E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 63606.65 | 26-JUN-11:00 | 63606.65 | 26-JUN-11:00 | 0.00 | 0.00 | 0.00 |
July | 0.495170E+11 | 0.00 | 322.92 | 0.494983E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 99715.52 | 19-JUL-05:03 | 79093.87 | 25-JUL-05:02 | 0.00 | 0.00 | 0.00 |
August | 0.460405E+11 | 0.00 | 318.65 | 0.460405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 99323.84 | 06-AUG-16:56 | 99323.84 | 06-AUG-16:56 | 0.00 | 0.00 | 0.00 |
September | 0.188259E+11 | 0.00 | 181.74 | 0.184981E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 86263.91 | 07-SEP-14:50 | 73705.82 | 03-SEP-18:12 | 0.00 | 0.00 | 0.00 |
October | 0.532649E+10 | 0.00 | 60.75 | 0.532649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54826.08 | 18-OCT-14:00 | 54826.08 | 18-OCT-14:00 | 0.00 | 0.00 | 0.00 |
November | 60763290.06 | 0.00 | 4.11 | 60763290.06 | 0.00 | 0.00 | 0.00 | 0.00 | 23487.69 | 17-NOV-06:02 | 23487.69 | 17-NOV-06:02 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.158993E+12 | 0.00 | 1263.67 | 0.158634E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.495170E+11 | 0.00 | 322.92 | 0.494983E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 99715.52 | 99323.84 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.360020E+12 | 0.914325E+11 | 744.00 | 0.326531E+12 | 0.334887E+11 | 0.00 | 0.36 | 02-JAN-06:08 | 0.30 | 09-JAN-07:02 | 142257.39 | 02-JAN-06:08 | 129348.57 | 02-JAN-22:03 | 13907.80 | 18-JAN-22:01 | 35850.31 | 02-JAN-06:08 | 0.00 |
February | 0.573981E+12 | 0.138103E+12 | 672.00 | 0.520370E+12 | 0.536106E+11 | 0.00 | 0.59 | 27-FEB-16:00 | 0.54 | 01-FEB-07:04 | 244851.71 | 27-FEB-22:03 | 221626.09 | 28-FEB-22:03 | 23825.93 | 05-FEB-00:32 | 66161.18 | 27-FEB-16:00 | 0.00 |
March | 0.908998E+12 | 0.209521E+12 | 744.00 | 0.826277E+12 | 0.827202E+11 | 0.00 | 0.98 | 31-MAR-24:00 | 0.76 | 06-MAR-07:07 | 440370.69 | 31-MAR-24:00 | 399931.55 | 31-MAR-24:00 | 40439.14 | 31-MAR-24:00 | 97635.35 | 31-MAR-24:00 | 0.00 |
April | 0.114382E+13 | 0.261097E+12 | 720.00 | 0.104186E+13 | 0.101954E+12 | 0.00 | 1.00 | 06-APR-09:50 | 0.39 | 30-APR-23:55 | 449292.35 | 24-APR-21:02 | 408158.75 | 16-APR-19:55 | 44664.77 | 24-APR-19:50 | 131876.83 | 07-APR-14:00 | 0.00 |
May | 0.374342E+12 | 0.978285E+11 | 744.00 | 0.341479E+12 | 0.328633E+11 | 0.00 | 0.58 | 31-MAY-23:40 | 0.33 | 08-MAY-06:10 | 237560.68 | 31-MAY-24:00 | 217091.81 | 31-MAY-24:00 | 20468.87 | 31-MAY-24:00 | 59394.93 | 31-MAY-23:20 | 0.00 |
June | 0.618878E+12 | 0.168977E+12 | 720.00 | 0.571988E+12 | 0.468902E+11 | 0.00 | 0.80 | 30-JUN-23:13 | 0.57 | 01-JUN-06:10 | 329651.37 | 30-JUN-24:00 | 309014.46 | 30-JUN-24:00 | 23463.47 | 01-JUN-19:00 | 95573.94 | 30-JUN-23:13 | 0.00 |
July | 0.893602E+12 | 0.266935E+12 | 744.00 | 0.840780E+12 | 0.528228E+11 | 0.00 | 1.00 | 31-JUL-23:03 | 0.78 | 08-JUL-06:10 | 426325.66 | 31-JUL-24:00 | 399986.67 | 31-JUL-23:55 | 34280.41 | 05-JUL-09:00 | 149359.80 | 17-JUL-16:00 | 0.00 |
August | 0.116066E+13 | 0.325711E+12 | 744.00 | 0.107929E+13 | 0.813726E+11 | 0.00 | 1.00 | 01-AUG-00:05 | 0.41 | 31-AUG-24:00 | 456969.36 | 04-AUG-00:03 | 411733.59 | 12-AUG-04:55 | 47520.61 | 01-AUG-21:00 | 167170.17 | 06-AUG-16:00 | 0.00 |
September | 0.365621E+12 | 0.100278E+12 | 720.00 | 0.335552E+12 | 0.300690E+11 | 0.00 | 0.57 | 30-SEP-24:00 | 0.34 | 18-SEP-07:00 | 238502.81 | 30-SEP-24:00 | 217102.12 | 30-SEP-24:00 | 21400.69 | 30-SEP-24:00 | 58999.94 | 02-SEP-17:00 | 0.00 |
October | 0.647772E+12 | 0.158355E+12 | 744.00 | 0.589409E+12 | 0.583637E+11 | 0.00 | 0.78 | 31-OCT-24:00 | 0.56 | 10-OCT-06:10 | 340513.03 | 31-OCT-24:00 | 309509.21 | 31-OCT-24:00 | 31003.82 | 31-OCT-24:00 | 78665.91 | 18-OCT-15:00 | 0.00 |
November | 0.888341E+12 | 0.205032E+12 | 720.00 | 0.805395E+12 | 0.829459E+11 | 0.00 | 0.81 | 17-NOV-17:00 | 0.77 | 27-NOV-07:10 | 348467.43 | 06-NOV-22:03 | 315034.95 | 06-NOV-22:03 | 34388.11 | 03-NOV-08:00 | 89393.50 | 17-NOV-17:00 | 0.00 |
December | 0.118105E+13 | 0.262556E+12 | 744.00 | 0.107302E+13 | 0.108029E+12 | 0.00 | 0.99 | 07-DEC-24:00 | 0.96 | 30-DEC-07:10 | 448111.69 | 07-DEC-24:00 | 406504.91 | 07-DEC-22:03 | 43485.83 | 16-DEC-17:00 | 104720.61 | 10-DEC-02:00 | 0.00 |
Annual Sum or Average | 0.911709E+13 | 0.228583E+13 | 8760.00 | 0.835196E+13 | 0.765130E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.360020E+12 | 0.914325E+11 | 672.00 | 0.326531E+12 | 0.300690E+11 | 0.00 | 0.36 | 0.30 | 142257.39 | 129348.57 | 13907.80 | 35850.31 | 0.00 | ||||||
Maximum of Months | 0.118105E+13 | 0.325711E+12 | 744.00 | 0.107929E+13 | 0.108029E+12 | 0.00 | 1.00 | 0.96 | 456969.36 | 411733.59 | 47520.61 | 167170.17 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.273551E+10 | 0.787621E+09 | 718.86 | 0.273519E+10 | 319869.43 | 0.00 | 0.26 | 19-JAN-16:40 | 0.00 | 07-JAN-17:55 | 2121.47 | 01-JAN-16:05 | 2121.28 | 13-JAN-16:20 | 13.01 | 02-JAN-07:10 | 558.20 | 19-JAN-16:40 | 0.00 |
February | 0.810072E+10 | 0.213204E+10 | 672.00 | 0.810072E+10 | -0.0 | 0.00 | 0.59 | 26-FEB-17:03 | 0.26 | 01-FEB-07:02 | 4895.59 | 26-FEB-17:20 | 4895.59 | 26-FEB-17:20 | 0.00 | 07-FEB-23:30 | 1280.84 | 26-FEB-16:53 | 0.00 |
March | 0.148854E+11 | 0.368388E+10 | 744.00 | 0.148854E+11 | -0.0 | 0.00 | 0.82 | 31-MAR-24:00 | 0.52 | 06-MAR-07:03 | 7460.24 | 31-MAR-24:00 | 7460.24 | 31-MAR-24:00 | 0.00 | 13-MAR-06:20 | 1755.36 | 31-MAR-24:00 | 0.00 |
April | 0.199822E+11 | 0.481113E+10 | 720.00 | 0.199747E+11 | 7524014.51 | 0.00 | 1.00 | 16-APR-16:52 | 0.30 | 30-APR-23:55 | 8870.63 | 22-APR-18:10 | 8870.63 | 22-APR-18:10 | 128.49 | 17-APR-16:10 | 2673.26 | 07-APR-14:00 | 0.00 |
May | 0.557500E+10 | 0.152167E+10 | 744.00 | 0.555338E+10 | 21619872.62 | 0.00 | 0.48 | 31-MAY-24:00 | 0.14 | 08-MAY-06:50 | 4117.84 | 31-MAY-24:00 | 4117.84 | 31-MAY-24:00 | 136.99 | 30-MAY-09:10 | 1065.61 | 31-MAY-23:30 | 0.00 |
June | 0.108501E+11 | 0.302276E+10 | 720.00 | 0.107701E+11 | 79990287.19 | 0.00 | 0.68 | 30-JUN-23:23 | 0.40 | 17-JUN-06:30 | 5979.31 | 30-JUN-23:55 | 5979.31 | 30-JUN-23:55 | 304.81 | 06-JUN-16:50 | 1853.62 | 29-JUN-15:00 | 0.00 |
July | 0.165225E+11 | 0.500630E+10 | 744.00 | 0.164333E+11 | 89212074.01 | 0.00 | 0.89 | 16-JUL-18:45 | 0.62 | 08-JUL-06:10 | 7877.72 | 31-JUL-23:40 | 7877.72 | 31-JUL-23:40 | 312.70 | 03-JUL-17:00 | 3030.41 | 17-JUL-16:00 | 0.00 |
August | 0.215187E+11 | 0.631081E+10 | 744.00 | 0.214556E+11 | 63151685.09 | 0.00 | 1.00 | 03-AUG-18:10 | 0.32 | 31-AUG-24:00 | 8817.72 | 05-AUG-20:12 | 8817.72 | 05-AUG-20:12 | 367.81 | 22-AUG-16:00 | 3577.62 | 06-AUG-16:00 | 0.00 |
September | 0.568889E+10 | 0.160934E+10 | 720.00 | 0.560670E+10 | 82191213.13 | 0.00 | 0.46 | 30-SEP-24:00 | 0.17 | 19-SEP-07:00 | 3949.39 | 30-SEP-24:00 | 3949.39 | 30-SEP-24:00 | 343.31 | 07-SEP-15:30 | 1355.93 | 04-SEP-17:31 | 0.00 |
October | 0.105085E+11 | 0.266977E+10 | 744.00 | 0.104978E+11 | 10752960.28 | 0.00 | 0.65 | 31-OCT-24:00 | 0.37 | 10-OCT-06:10 | 5599.16 | 31-OCT-24:00 | 5599.16 | 31-OCT-24:00 | 111.21 | 25-OCT-11:00 | 1571.65 | 15-OCT-16:43 | 0.00 |
November | 0.145912E+11 | 0.357888E+10 | 720.00 | 0.145895E+11 | 1705179.94 | 0.00 | 0.72 | 12-NOV-16:23 | 0.54 | 27-NOV-07:10 | 6471.71 | 12-NOV-16:25 | 6471.71 | 12-NOV-16:25 | 83.35 | 08-NOV-15:10 | 1636.84 | 17-NOV-16:50 | 0.00 |
December | 0.194362E+11 | 0.470683E+10 | 744.00 | 0.194359E+11 | 238807.04 | 0.00 | 0.91 | 10-DEC-15:53 | 0.74 | 29-DEC-07:03 | 8265.84 | 10-DEC-16:10 | 8265.84 | 10-DEC-16:10 | 49.61 | 19-DEC-17:05 | 1973.31 | 10-DEC-02:00 | 0.00 |
Annual Sum or Average | 0.150395E+12 | 0.398410E+11 | 8734.86 | 0.150038E+12 | 0.356706E+09 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.273551E+10 | 0.787621E+09 | 672.00 | 0.273519E+10 | -0.0 | 0.00 | 0.26 | 0.00 | 2121.47 | 2121.28 | 0.00 | 558.20 | 0.00 | ||||||
Maximum of Months | 0.215187E+11 | 0.631081E+10 | 744.00 | 0.214556E+11 | 89212074.01 | 0.00 | 1.00 | 0.74 | 8870.63 | 8870.63 | 367.81 | 3577.62 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.602116E+10 | 0.193365E+10 | 415.59 | 0.601880E+10 | 2365056.20 | 0.00 | 0.22 | 13-JAN-16:30 | 0.00 | 01-JAN-01:05 | 16872.55 | 13-JAN-16:30 | 16872.55 | 13-JAN-16:30 | 181.25 | 01-JAN-15:45 | 4491.90 | 13-JAN-16:30 | 0.00 |
February | 0.566069E+11 | 0.152782E+11 | 672.00 | 0.566069E+11 | 0.00 | 0.00 | 0.52 | 26-FEB-17:23 | 0.12 | 06-FEB-04:01 | 42293.97 | 28-FEB-17:00 | 42293.97 | 28-FEB-17:00 | 0.00 | 12-FEB-15:10 | 11356.52 | 27-FEB-16:00 | 0.00 |
March | 0.122668E+12 | 0.308391E+11 | 744.00 | 0.122668E+12 | 0.00 | 0.00 | 0.75 | 31-MAR-23:30 | 0.37 | 06-MAR-07:03 | 64620.06 | 31-MAR-23:30 | 64620.06 | 31-MAR-23:30 | 0.00 | 06-MAR-02:50 | 15410.40 | 31-MAR-23:30 | 0.00 |
April | 0.179156E+12 | 0.435535E+11 | 720.00 | 0.179079E+12 | 77055582.78 | 0.00 | 1.00 | 16-APR-17:42 | 0.14 | 30-APR-24:00 | 82177.38 | 22-APR-18:10 | 82177.38 | 22-APR-18:10 | 1282.53 | 17-APR-16:10 | 25381.52 | 07-APR-14:00 | 0.00 |
May | 0.449057E+11 | 0.124441E+11 | 744.00 | 0.446933E+11 | 0.212459E+09 | 0.00 | 0.48 | 31-MAY-24:00 | 0.02 | 08-MAY-06:10 | 39022.52 | 31-MAY-24:00 | 39022.52 | 31-MAY-24:00 | 1329.45 | 30-MAY-09:10 | 10125.95 | 31-MAY-23:30 | 0.00 |
June | 0.100151E+12 | 0.280584E+11 | 720.00 | 0.993533E+11 | 0.797458E+09 | 0.00 | 0.69 | 30-JUN-23:13 | 0.34 | 17-JUN-06:30 | 58313.68 | 30-JUN-23:55 | 58313.68 | 30-JUN-23:55 | 2986.02 | 06-JUN-16:50 | 17679.93 | 29-JUN-15:00 | 0.00 |
July | 0.156401E+12 | 0.474965E+11 | 744.00 | 0.155509E+12 | 0.892353E+09 | 0.00 | 0.90 | 31-JUL-23:15 | 0.59 | 08-JUL-06:10 | 76581.41 | 31-JUL-23:55 | 76581.41 | 31-JUL-23:55 | 3067.96 | 03-JUL-17:00 | 28865.33 | 17-JUL-16:00 | 0.00 |
August | 0.202567E+12 | 0.596195E+11 | 744.00 | 0.201934E+12 | 0.633107E+09 | 0.00 | 1.00 | 03-AUG-18:20 | 0.27 | 31-AUG-24:00 | 83842.69 | 03-AUG-19:00 | 83842.69 | 03-AUG-19:00 | 3613.51 | 22-AUG-16:00 | 34257.45 | 06-AUG-16:00 | 0.00 |
September | 0.480619E+11 | 0.138016E+11 | 720.00 | 0.472573E+11 | 0.804649E+09 | 0.00 | 0.43 | 04-SEP-17:31 | 0.09 | 19-SEP-06:10 | 35004.81 | 30-SEP-23:40 | 35004.81 | 30-SEP-23:40 | 3425.09 | 07-SEP-15:30 | 12823.82 | 04-SEP-17:25 | 0.00 |
October | 0.873500E+11 | 0.225115E+11 | 744.00 | 0.872425E+11 | 0.107492E+09 | 0.00 | 0.58 | 31-OCT-24:00 | 0.25 | 10-OCT-06:10 | 47223.43 | 31-OCT-24:00 | 47223.43 | 31-OCT-24:00 | 1092.74 | 25-OCT-11:00 | 14401.62 | 18-OCT-16:00 | 0.00 |
November | 0.119276E+12 | 0.297604E+11 | 720.00 | 0.119258E+12 | 17772891.25 | 0.00 | 0.69 | 03-NOV-16:00 | 0.37 | 27-NOV-07:10 | 59758.21 | 03-NOV-16:00 | 59209.11 | 03-NOV-16:00 | 830.69 | 08-NOV-15:10 | 15170.24 | 17-NOV-17:00 | 0.00 |
December | 0.155926E+12 | 0.386023E+11 | 744.00 | 0.155923E+12 | 3211122.60 | 0.00 | 0.83 | 12-DEC-16:00 | 0.56 | 31-DEC-23:45 | 74146.89 | 06-DEC-16:10 | 73845.83 | 06-DEC-16:10 | 522.43 | 19-DEC-17:05 | 16906.14 | 06-DEC-16:10 | 0.00 |
Annual Sum or Average | 0.127909E+13 | 0.343899E+12 | 8431.59 | 0.127554E+13 | 0.354792E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.602116E+10 | 0.193365E+10 | 415.59 | 0.601880E+10 | 0.00 | 0.00 | 0.22 | 0.00 | 16872.55 | 16872.55 | 0.00 | 4491.90 | 0.00 | ||||||
Maximum of Months | 0.202567E+12 | 0.596195E+11 | 744.00 | 0.201934E+12 | 0.892353E+09 | 0.00 | 1.00 | 0.59 | 83842.69 | 83842.69 | 3613.51 | 34257.45 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.158707E+09 | 52180105.68 | 127.92 | 0.158707E+09 | 0.00 | 0.00 | 0.20 | 13-JAN-16:30 | 0.00 | 01-JAN-00:05 | 1591.69 | 13-JAN-16:30 | 1591.69 | 13-JAN-16:30 | 0.00 | 24-JAN-22:50 | 426.63 | 13-JAN-16:30 | 0.00 |
February | 0.403903E+10 | 0.111350E+10 | 648.45 | 0.403903E+10 | 0.00 | 0.00 | 0.49 | 28-FEB-17:00 | 0.00 | 03-FEB-03:53 | 4149.29 | 28-FEB-17:00 | 4149.29 | 28-FEB-17:00 | 0.00 | 12-FEB-23:30 | 1103.78 | 27-FEB-16:00 | 0.00 |
March | 0.105223E+11 | 0.268437E+10 | 744.00 | 0.105223E+11 | -0.0 | 0.00 | 0.71 | 28-MAR-17:50 | 0.19 | 06-MAR-04:07 | 6089.86 | 28-MAR-17:50 | 6089.86 | 28-MAR-17:50 | 0.00 | 11-MAR-01:40 | 1476.77 | 28-MAR-17:50 | 0.00 |
April | 0.166314E+11 | 0.409306E+10 | 719.00 | 0.166238E+11 | 7563282.15 | 0.00 | 0.97 | 16-APR-17:51 | 0.00 | 30-APR-23:05 | 8275.47 | 25-APR-18:00 | 8275.47 | 25-APR-18:00 | 126.92 | 17-APR-16:10 | 2549.31 | 07-APR-14:00 | 0.00 |
May | 0.376036E+10 | 0.105561E+10 | 684.92 | 0.373952E+10 | 20835961.65 | 0.00 | 0.46 | 31-MAY-23:40 | 0.00 | 01-MAY-00:05 | 3830.51 | 31-MAY-24:00 | 3830.51 | 31-MAY-24:00 | 128.36 | 30-MAY-09:20 | 999.71 | 31-MAY-23:20 | 0.00 |
June | 0.978624E+10 | 0.276211E+10 | 720.00 | 0.970669E+10 | 79548979.84 | 0.00 | 0.68 | 30-JUN-23:13 | 0.25 | 17-JUN-06:10 | 5842.32 | 30-JUN-23:55 | 5842.32 | 30-JUN-23:55 | 300.85 | 06-JUN-16:50 | 1806.66 | 29-JUN-15:00 | 0.00 |
July | 0.155832E+11 | 0.475603E+10 | 744.00 | 0.154941E+11 | 89074314.95 | 0.00 | 0.91 | 16-JUL-18:45 | 0.54 | 08-JUL-06:30 | 7665.59 | 31-JUL-23:55 | 7665.59 | 31-JUL-23:55 | 307.65 | 03-JUL-17:00 | 2951.56 | 17-JUL-16:00 | 0.00 |
August | 0.201131E+11 | 0.595267E+10 | 744.00 | 0.200499E+11 | 63158319.83 | 0.00 | 1.00 | 04-AUG-17:20 | 0.26 | 31-AUG-24:00 | 8542.39 | 05-AUG-20:00 | 8542.39 | 05-AUG-20:00 | 362.60 | 22-AUG-16:00 | 3489.37 | 06-AUG-16:00 | 0.00 |
September | 0.419403E+10 | 0.123067E+10 | 717.22 | 0.411506E+10 | 78968458.85 | 0.00 | 0.46 | 04-SEP-17:25 | 0.00 | 12-SEP-06:10 | 3426.63 | 04-SEP-17:33 | 3426.63 | 04-SEP-17:37 | 344.95 | 07-SEP-15:30 | 1386.93 | 04-SEP-17:25 | 0.00 |
October | 0.720339E+10 | 0.189170E+10 | 743.83 | 0.719291E+10 | 10476132.94 | 0.00 | 0.56 | 18-OCT-16:50 | 0.00 | 10-OCT-02:65 | 4530.26 | 18-OCT-16:50 | 4530.26 | 18-OCT-16:50 | 108.22 | 25-OCT-11:00 | 1450.23 | 18-OCT-16:00 | 0.00 |
November | 0.991135E+10 | 0.251919E+10 | 720.00 | 0.990963E+10 | 1723916.54 | 0.00 | 0.66 | 03-NOV-16:00 | 0.19 | 27-NOV-04:10 | 5871.86 | 03-NOV-16:00 | 5817.01 | 03-NOV-16:00 | 81.62 | 08-NOV-15:10 | 1477.87 | 17-NOV-17:00 | 0.00 |
December | 0.135852E+11 | 0.341860E+10 | 744.00 | 0.135849E+11 | 279945.32 | 0.00 | 0.80 | 06-DEC-16:10 | 0.40 | 31-DEC-23:50 | 7293.12 | 06-DEC-16:10 | 7264.54 | 06-DEC-16:10 | 49.26 | 19-DEC-17:05 | 1670.42 | 06-DEC-16:10 | 0.00 |
Annual Sum or Average | 0.115488E+12 | 0.315297E+11 | 8057.34 | 0.115137E+12 | 0.351629E+09 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.158707E+09 | 52180105.68 | 127.92 | 0.158707E+09 | -0.0 | 0.00 | 0.20 | 0.00 | 1591.69 | 1591.69 | 0.00 | 426.63 | 0.00 | ||||||
Maximum of Months | 0.201131E+11 | 0.595267E+10 | 744.00 | 0.200499E+11 | 89074314.95 | 0.00 | 1.00 | 0.54 | 8542.39 | 8542.39 | 362.60 | 3489.37 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 90.40 | 0.00 | 90.40 | 1.55 | 790.49 | 0.00 | 0.00 | 0.00 |
February | 127.65 | 0.00 | 127.65 | 15.53 | 595.82 | 0.00 | 0.00 | 0.00 |
March | 207.35 | 0.00 | 207.35 | 61.94 | 487.97 | 0.00 | 0.00 | 0.00 |
April | 236.43 | 1.38 | 235.05 | 114.83 | 351.22 | 0.00 | 0.00 | 0.00 |
May | 310.49 | 18.40 | 292.09 | 224.68 | 253.26 | 0.00 | 0.00 | 0.00 |
June | 361.54 | 41.56 | 319.99 | 365.90 | 158.52 | 0.00 | 0.00 | 0.00 |
July | 330.29 | 30.94 | 299.35 | 397.61 | 130.75 | 0.00 | 0.00 | 0.00 |
August | 264.66 | 7.09 | 257.57 | 287.63 | 151.62 | 0.00 | 0.00 | 0.00 |
September | 198.21 | 0.07 | 198.14 | 166.71 | 235.63 | 0.00 | 0.00 | 0.00 |
October | 144.59 | 0.00 | 144.59 | 57.92 | 361.40 | 0.00 | 0.00 | 0.00 |
November | 98.29 | 0.00 | 98.29 | 11.34 | 523.08 | 0.00 | 0.00 | 0.00 |
December | 75.81 | 0.00 | 75.81 | 0.46 | 707.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 204.22 | 8.33 | 195.89 | 142.97 | 394.84 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 75.81 | 0.00 | 75.81 | 0.46 | 130.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 361.54 | 41.56 | 319.99 | 397.61 | 790.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 90.40 | 0.00 | 90.40 | 1.55 | 790.49 | 0.00 | 0.00 | 0.00 |
February | 127.64 | 0.00 | 127.64 | 15.53 | 595.82 | 0.00 | 0.00 | 0.00 |
March | 207.35 | 0.00 | 207.35 | 61.94 | 487.97 | 0.00 | 0.00 | 0.00 |
April | 236.42 | 1.38 | 235.04 | 114.83 | 351.22 | 0.00 | 0.00 | 0.00 |
May | 310.48 | 18.40 | 292.08 | 224.68 | 253.26 | 0.00 | 0.00 | 0.00 |
June | 361.54 | 41.56 | 319.98 | 365.90 | 158.52 | 0.00 | 0.00 | 0.00 |
July | 330.29 | 30.93 | 299.35 | 397.61 | 130.75 | 0.00 | 0.00 | 0.00 |
August | 264.66 | 7.09 | 257.57 | 287.63 | 151.62 | 0.00 | 0.00 | 0.00 |
September | 198.21 | 0.07 | 198.14 | 166.71 | 235.63 | 0.00 | 0.00 | 0.00 |
October | 144.58 | 0.00 | 144.58 | 57.92 | 361.40 | 0.00 | 0.00 | 0.00 |
November | 98.29 | 0.00 | 98.29 | 11.34 | 523.08 | 0.00 | 0.00 | 0.00 |
December | 75.81 | 0.00 | 75.81 | 0.46 | 707.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 204.22 | 8.33 | 195.89 | 142.97 | 394.84 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 75.81 | 0.00 | 75.81 | 0.46 | 130.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 361.54 | 41.56 | 319.98 | 397.61 | 790.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 90.40 | 0.00 | 90.40 | 1.55 | 790.49 | 0.00 | 0.00 | 0.00 |
February | 127.64 | 0.00 | 127.64 | 15.53 | 595.82 | 0.00 | 0.00 | 0.00 |
March | 207.35 | 0.00 | 207.35 | 61.94 | 487.97 | 0.00 | 0.00 | 0.00 |
April | 236.43 | 1.38 | 235.05 | 114.83 | 351.22 | 0.00 | 0.00 | 0.00 |
May | 310.48 | 18.40 | 292.08 | 224.68 | 253.26 | 0.00 | 0.00 | 0.00 |
June | 361.54 | 41.56 | 319.98 | 365.90 | 158.52 | 0.00 | 0.00 | 0.00 |
July | 330.29 | 30.93 | 299.35 | 397.61 | 130.75 | 0.00 | 0.00 | 0.00 |
August | 264.66 | 7.09 | 257.57 | 287.63 | 151.62 | 0.00 | 0.00 | 0.00 |
September | 198.21 | 0.07 | 198.14 | 166.71 | 235.63 | 0.00 | 0.00 | 0.00 |
October | 144.58 | 0.00 | 144.58 | 57.92 | 361.40 | 0.00 | 0.00 | 0.00 |
November | 98.29 | 0.00 | 98.29 | 11.34 | 523.08 | 0.00 | 0.00 | 0.00 |
December | 75.81 | 0.00 | 75.81 | 0.46 | 707.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 204.22 | 8.33 | 195.89 | 142.97 | 394.84 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 75.81 | 0.00 | 75.81 | 0.46 | 130.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 361.54 | 41.56 | 319.98 | 397.61 | 790.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 90.40 | 0.00 | 90.40 | 1.55 | 790.49 | 0.00 | 0.00 | 0.00 |
February | 127.64 | 0.00 | 127.64 | 15.53 | 595.82 | 0.00 | 0.00 | 0.00 |
March | 207.35 | 0.00 | 207.35 | 61.94 | 487.97 | 0.00 | 0.00 | 0.00 |
April | 236.42 | 1.38 | 235.04 | 114.83 | 351.22 | 0.00 | 0.00 | 0.00 |
May | 310.48 | 18.40 | 292.08 | 224.68 | 253.26 | 0.00 | 0.00 | 0.00 |
June | 361.54 | 41.56 | 319.98 | 365.90 | 158.52 | 0.00 | 0.00 | 0.00 |
July | 330.29 | 30.93 | 299.35 | 397.61 | 130.75 | 0.00 | 0.00 | 0.00 |
August | 264.66 | 7.09 | 257.57 | 287.63 | 151.62 | 0.00 | 0.00 | 0.00 |
September | 198.21 | 0.07 | 198.14 | 166.71 | 235.63 | 0.00 | 0.00 | 0.00 |
October | 144.58 | 0.00 | 144.58 | 57.92 | 361.40 | 0.00 | 0.00 | 0.00 |
November | 98.29 | 0.00 | 98.29 | 11.34 | 523.08 | 0.00 | 0.00 | 0.00 |
December | 75.81 | 0.00 | 75.81 | 0.46 | 707.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 204.22 | 8.33 | 195.89 | 142.97 | 394.84 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 75.81 | 0.00 | 75.81 | 0.46 | 130.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 361.54 | 41.56 | 319.98 | 397.61 | 790.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 90.40 | 0.00 | 90.40 | 1.55 | 790.46 | 0.00 | 0.00 | 0.00 |
February | 127.64 | 0.00 | 127.64 | 15.53 | 595.80 | 0.00 | 0.00 | 0.00 |
March | 207.34 | 0.00 | 207.34 | 61.93 | 487.95 | 0.00 | 0.00 | 0.00 |
April | 236.41 | 1.38 | 235.04 | 114.83 | 351.21 | 0.00 | 0.00 | 0.00 |
May | 310.47 | 18.40 | 292.07 | 224.67 | 253.25 | 0.00 | 0.00 | 0.00 |
June | 361.52 | 41.55 | 319.97 | 365.88 | 158.51 | 0.00 | 0.00 | 0.00 |
July | 330.27 | 30.93 | 299.34 | 397.59 | 130.74 | 0.00 | 0.00 | 0.00 |
August | 264.65 | 7.09 | 257.56 | 287.61 | 151.61 | 0.00 | 0.00 | 0.00 |
September | 198.20 | 0.07 | 198.13 | 166.70 | 235.62 | 0.00 | 0.00 | 0.00 |
October | 144.58 | 0.00 | 144.58 | 57.92 | 361.39 | 0.00 | 0.00 | 0.00 |
November | 98.29 | 0.00 | 98.29 | 11.34 | 523.06 | 0.00 | 0.00 | 0.00 |
December | 75.80 | 0.00 | 75.80 | 0.46 | 707.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 204.21 | 8.33 | 195.88 | 142.96 | 394.82 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 75.80 | 0.00 | 75.80 | 0.46 | 130.74 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 361.52 | 41.55 | 319.97 | 397.59 | 790.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 230.66 | 105.75 | 124.91 | 118.55 | 802.11 | 0.00 | 0.00 | 0.00 |
February | 360.77 | 179.11 | 181.66 | 263.15 | 599.99 | 0.00 | 0.00 | 0.00 |
March | 485.09 | 200.72 | 284.37 | 387.39 | 499.01 | 0.00 | 0.00 | 0.00 |
April | 618.92 | 306.73 | 312.19 | 592.43 | 360.59 | 0.00 | 0.00 | 0.00 |
May | 683.68 | 304.20 | 379.49 | 705.62 | 280.35 | 0.00 | 0.00 | 0.00 |
June | 884.94 | 455.39 | 429.55 | 1055.47 | 177.83 | 0.00 | 0.00 | 0.00 |
July | 928.77 | 525.06 | 403.71 | 1195.67 | 141.33 | 0.00 | 0.00 | 0.00 |
August | 807.14 | 449.71 | 357.43 | 1014.89 | 158.76 | 0.00 | 0.00 | 0.00 |
September | 570.97 | 294.73 | 276.24 | 648.48 | 243.74 | 0.00 | 0.00 | 0.00 |
October | 409.64 | 208.01 | 201.63 | 381.05 | 368.34 | 0.00 | 0.00 | 0.00 |
November | 259.62 | 121.21 | 138.41 | 172.30 | 516.27 | 0.00 | 0.00 | 0.00 |
December | 191.49 | 82.24 | 109.24 | 90.38 | 704.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 536.89 | 269.87 | 267.02 | 553.78 | 403.70 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 191.49 | 82.24 | 109.24 | 90.38 | 141.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 928.77 | 525.06 | 429.55 | 1195.67 | 802.11 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 230.66 | 105.75 | 124.91 | 118.55 | 802.11 | 0.00 | 0.00 | 0.00 |
February | 360.77 | 179.11 | 181.66 | 263.15 | 599.99 | 0.00 | 0.00 | 0.00 |
March | 485.09 | 200.72 | 284.37 | 387.39 | 499.01 | 0.00 | 0.00 | 0.00 |
April | 618.92 | 306.73 | 312.19 | 592.43 | 360.59 | 0.00 | 0.00 | 0.00 |
May | 683.68 | 304.20 | 379.49 | 705.62 | 280.35 | 0.00 | 0.00 | 0.00 |
June | 884.94 | 455.39 | 429.55 | 1055.47 | 177.83 | 0.00 | 0.00 | 0.00 |
July | 928.77 | 525.06 | 403.71 | 1195.67 | 141.33 | 0.00 | 0.00 | 0.00 |
August | 807.14 | 449.71 | 357.43 | 1014.89 | 158.76 | 0.00 | 0.00 | 0.00 |
September | 570.97 | 294.73 | 276.24 | 648.48 | 243.74 | 0.00 | 0.00 | 0.00 |
October | 409.64 | 208.01 | 201.63 | 381.05 | 368.34 | 0.00 | 0.00 | 0.00 |
November | 259.62 | 121.21 | 138.41 | 172.30 | 516.27 | 0.00 | 0.00 | 0.00 |
December | 191.49 | 82.24 | 109.24 | 90.38 | 704.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 536.89 | 269.87 | 267.02 | 553.78 | 403.70 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 191.49 | 82.24 | 109.24 | 90.38 | 141.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 928.77 | 525.06 | 429.55 | 1195.67 | 802.11 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 230.65 | 105.75 | 124.91 | 118.54 | 802.10 | 0.00 | 0.00 | 0.00 |
February | 360.76 | 179.11 | 181.65 | 263.15 | 599.98 | 0.00 | 0.00 | 0.00 |
March | 485.08 | 200.71 | 284.37 | 387.38 | 499.00 | 0.00 | 0.00 | 0.00 |
April | 618.91 | 306.73 | 312.18 | 592.42 | 360.58 | 0.00 | 0.00 | 0.00 |
May | 683.67 | 304.19 | 379.48 | 705.61 | 280.34 | 0.00 | 0.00 | 0.00 |
June | 884.92 | 455.38 | 429.54 | 1055.45 | 177.82 | 0.00 | 0.00 | 0.00 |
July | 928.75 | 525.05 | 403.70 | 1195.65 | 141.33 | 0.00 | 0.00 | 0.00 |
August | 807.13 | 449.71 | 357.42 | 1014.87 | 158.76 | 0.00 | 0.00 | 0.00 |
September | 570.96 | 294.73 | 276.23 | 648.47 | 243.74 | 0.00 | 0.00 | 0.00 |
October | 409.64 | 208.01 | 201.63 | 381.04 | 368.33 | 0.00 | 0.00 | 0.00 |
November | 259.62 | 121.21 | 138.41 | 172.30 | 516.26 | 0.00 | 0.00 | 0.00 |
December | 191.48 | 82.24 | 109.24 | 90.38 | 704.84 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 536.88 | 269.87 | 267.02 | 553.77 | 403.69 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 191.48 | 82.24 | 109.24 | 90.38 | 141.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 928.75 | 525.05 | 429.54 | 1195.65 | 802.10 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 637.24 | 455.13 | 182.11 | 591.36 | 664.39 | 0.00 | 0.00 | 0.00 |
February | 811.51 | 583.67 | 227.84 | 828.47 | 507.47 | 0.00 | 0.00 | 0.00 |
March | 725.39 | 407.34 | 318.04 | 737.14 | 458.00 | 0.00 | 0.00 | 0.00 |
April | 583.09 | 278.89 | 304.20 | 614.42 | 346.08 | 0.00 | 0.00 | 0.00 |
May | 518.06 | 172.06 | 346.00 | 557.61 | 268.09 | 0.00 | 0.00 | 0.00 |
June | 514.75 | 150.12 | 364.62 | 633.25 | 181.74 | 0.00 | 0.00 | 0.00 |
July | 554.95 | 204.99 | 349.95 | 761.77 | 143.46 | 0.00 | 0.00 | 0.00 |
August | 659.52 | 332.52 | 327.00 | 878.33 | 162.83 | 0.00 | 0.00 | 0.00 |
September | 731.48 | 448.20 | 283.28 | 904.38 | 234.72 | 0.00 | 0.00 | 0.00 |
October | 764.73 | 528.80 | 235.93 | 865.18 | 335.72 | 0.00 | 0.00 | 0.00 |
November | 697.20 | 505.03 | 192.18 | 716.20 | 435.58 | 0.00 | 0.00 | 0.00 |
December | 605.98 | 437.58 | 168.40 | 571.39 | 582.08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 649.20 | 373.97 | 275.23 | 720.80 | 359.47 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 514.75 | 150.12 | 168.40 | 557.61 | 143.46 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 811.51 | 583.67 | 364.62 | 904.38 | 664.39 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 637.23 | 455.12 | 182.11 | 591.35 | 664.39 | 0.00 | 0.00 | 0.00 |
February | 811.51 | 583.66 | 227.84 | 828.46 | 507.47 | 0.00 | 0.00 | 0.00 |
March | 725.38 | 407.34 | 318.04 | 737.13 | 458.00 | 0.00 | 0.00 | 0.00 |
April | 583.09 | 278.89 | 304.19 | 614.41 | 346.08 | 0.00 | 0.00 | 0.00 |
May | 518.06 | 172.06 | 346.00 | 557.60 | 268.09 | 0.00 | 0.00 | 0.00 |
June | 514.74 | 150.12 | 364.62 | 633.25 | 181.74 | 0.00 | 0.00 | 0.00 |
July | 554.95 | 204.99 | 349.95 | 761.77 | 143.46 | 0.00 | 0.00 | 0.00 |
August | 659.51 | 332.51 | 327.00 | 878.33 | 162.83 | 0.00 | 0.00 | 0.00 |
September | 731.48 | 448.20 | 283.28 | 904.37 | 234.72 | 0.00 | 0.00 | 0.00 |
October | 764.72 | 528.79 | 235.93 | 865.17 | 335.72 | 0.00 | 0.00 | 0.00 |
November | 697.20 | 505.02 | 192.18 | 716.19 | 435.58 | 0.00 | 0.00 | 0.00 |
December | 605.97 | 437.57 | 168.40 | 571.38 | 582.08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 649.20 | 373.97 | 275.23 | 720.79 | 359.46 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 514.74 | 150.12 | 168.40 | 557.60 | 143.46 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 811.51 | 583.66 | 364.62 | 904.37 | 664.39 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 637.24 | 455.13 | 182.11 | 591.36 | 664.39 | 0.00 | 0.00 | 0.00 |
February | 811.51 | 583.67 | 227.84 | 828.47 | 507.47 | 0.00 | 0.00 | 0.00 |
March | 725.39 | 407.34 | 318.04 | 737.14 | 458.00 | 0.00 | 0.00 | 0.00 |
April | 583.09 | 278.89 | 304.20 | 614.42 | 346.08 | 0.00 | 0.00 | 0.00 |
May | 518.06 | 172.06 | 346.00 | 557.61 | 268.09 | 0.00 | 0.00 | 0.00 |
June | 514.75 | 150.12 | 364.62 | 633.25 | 181.74 | 0.00 | 0.00 | 0.00 |
July | 554.95 | 204.99 | 349.95 | 761.77 | 143.46 | 0.00 | 0.00 | 0.00 |
August | 659.52 | 332.52 | 327.00 | 878.33 | 162.83 | 0.00 | 0.00 | 0.00 |
September | 731.48 | 448.20 | 283.28 | 904.38 | 234.72 | 0.00 | 0.00 | 0.00 |
October | 764.73 | 528.80 | 235.93 | 865.18 | 335.72 | 0.00 | 0.00 | 0.00 |
November | 697.20 | 505.03 | 192.18 | 716.20 | 435.58 | 0.00 | 0.00 | 0.00 |
December | 605.98 | 437.58 | 168.40 | 571.39 | 582.08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 649.20 | 373.97 | 275.23 | 720.80 | 359.47 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 514.75 | 150.12 | 168.40 | 557.61 | 143.46 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 811.51 | 583.67 | 364.62 | 904.38 | 664.39 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 637.23 | 455.12 | 182.11 | 591.35 | 664.39 | 0.00 | 0.00 | 0.00 |
February | 811.51 | 583.66 | 227.84 | 828.46 | 507.47 | 0.00 | 0.00 | 0.00 |
March | 725.38 | 407.34 | 318.04 | 737.13 | 458.00 | 0.00 | 0.00 | 0.00 |
April | 583.09 | 278.89 | 304.19 | 614.41 | 346.08 | 0.00 | 0.00 | 0.00 |
May | 518.06 | 172.06 | 346.00 | 557.60 | 268.09 | 0.00 | 0.00 | 0.00 |
June | 514.74 | 150.12 | 364.62 | 633.25 | 181.74 | 0.00 | 0.00 | 0.00 |
July | 554.95 | 204.99 | 349.95 | 761.77 | 143.46 | 0.00 | 0.00 | 0.00 |
August | 659.51 | 332.51 | 327.00 | 878.33 | 162.83 | 0.00 | 0.00 | 0.00 |
September | 731.48 | 448.20 | 283.28 | 904.37 | 234.72 | 0.00 | 0.00 | 0.00 |
October | 764.72 | 528.79 | 235.93 | 865.17 | 335.72 | 0.00 | 0.00 | 0.00 |
November | 697.20 | 505.02 | 192.18 | 716.19 | 435.58 | 0.00 | 0.00 | 0.00 |
December | 605.97 | 437.57 | 168.40 | 571.38 | 582.08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 649.20 | 373.97 | 275.23 | 720.79 | 359.46 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 514.74 | 150.12 | 168.40 | 557.60 | 143.46 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 811.51 | 583.66 | 364.62 | 904.37 | 664.39 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 637.21 | 455.11 | 182.10 | 591.33 | 664.36 | 0.00 | 0.00 | 0.00 |
February | 811.48 | 583.64 | 227.83 | 828.43 | 507.45 | 0.00 | 0.00 | 0.00 |
March | 725.35 | 407.32 | 318.03 | 737.11 | 457.98 | 0.00 | 0.00 | 0.00 |
April | 583.06 | 278.88 | 304.18 | 614.39 | 346.07 | 0.00 | 0.00 | 0.00 |
May | 518.04 | 172.05 | 345.99 | 557.58 | 268.08 | 0.00 | 0.00 | 0.00 |
June | 514.72 | 150.12 | 364.61 | 633.22 | 181.73 | 0.00 | 0.00 | 0.00 |
July | 554.92 | 204.99 | 349.94 | 761.74 | 143.45 | 0.00 | 0.00 | 0.00 |
August | 659.49 | 332.50 | 326.99 | 878.30 | 162.82 | 0.00 | 0.00 | 0.00 |
September | 731.45 | 448.18 | 283.27 | 904.34 | 234.71 | 0.00 | 0.00 | 0.00 |
October | 764.69 | 528.77 | 235.92 | 865.14 | 335.71 | 0.00 | 0.00 | 0.00 |
November | 697.17 | 505.00 | 192.17 | 716.17 | 435.56 | 0.00 | 0.00 | 0.00 |
December | 605.95 | 437.56 | 168.39 | 571.36 | 582.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 649.18 | 373.96 | 275.22 | 720.76 | 359.45 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 514.72 | 150.12 | 168.39 | 557.58 | 143.45 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 811.48 | 583.64 | 364.61 | 904.34 | 664.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 208.93 | 84.20 | 124.73 | 101.92 | 864.20 | 0.00 | 0.00 | 0.00 |
February | 356.61 | 175.29 | 181.32 | 257.91 | 658.53 | 0.00 | 0.00 | 0.00 |
March | 456.37 | 167.22 | 289.15 | 342.66 | 570.83 | 0.00 | 0.00 | 0.00 |
April | 595.79 | 263.96 | 331.83 | 556.08 | 433.00 | 0.00 | 0.00 | 0.00 |
May | 736.96 | 336.09 | 400.86 | 774.98 | 316.10 | 0.00 | 0.00 | 0.00 |
June | 801.78 | 368.29 | 433.49 | 944.79 | 217.24 | 0.00 | 0.00 | 0.00 |
July | 821.33 | 415.03 | 406.30 | 1050.89 | 182.89 | 0.00 | 0.00 | 0.00 |
August | 697.42 | 342.28 | 355.14 | 861.61 | 206.77 | 0.00 | 0.00 | 0.00 |
September | 561.03 | 283.64 | 277.40 | 639.92 | 279.77 | 0.00 | 0.00 | 0.00 |
October | 400.98 | 199.23 | 201.76 | 372.55 | 423.35 | 0.00 | 0.00 | 0.00 |
November | 283.86 | 140.82 | 143.04 | 206.28 | 592.39 | 0.00 | 0.00 | 0.00 |
December | 190.81 | 80.53 | 110.27 | 90.50 | 802.97 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 510.02 | 238.28 | 271.74 | 518.03 | 461.62 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 190.81 | 80.53 | 110.27 | 90.50 | 182.89 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 821.33 | 415.03 | 433.49 | 1050.89 | 864.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 208.93 | 84.20 | 124.73 | 101.92 | 864.20 | 0.00 | 0.00 | 0.00 |
February | 356.61 | 175.29 | 181.32 | 257.91 | 658.53 | 0.00 | 0.00 | 0.00 |
March | 456.37 | 167.22 | 289.15 | 342.66 | 570.83 | 0.00 | 0.00 | 0.00 |
April | 595.79 | 263.96 | 331.83 | 556.08 | 433.00 | 0.00 | 0.00 | 0.00 |
May | 736.96 | 336.09 | 400.86 | 774.98 | 316.10 | 0.00 | 0.00 | 0.00 |
June | 801.78 | 368.29 | 433.49 | 944.79 | 217.24 | 0.00 | 0.00 | 0.00 |
July | 821.33 | 415.03 | 406.30 | 1050.89 | 182.89 | 0.00 | 0.00 | 0.00 |
August | 697.42 | 342.28 | 355.14 | 861.61 | 206.77 | 0.00 | 0.00 | 0.00 |
September | 561.03 | 283.64 | 277.40 | 639.92 | 279.77 | 0.00 | 0.00 | 0.00 |
October | 400.98 | 199.23 | 201.76 | 372.55 | 423.35 | 0.00 | 0.00 | 0.00 |
November | 283.86 | 140.82 | 143.04 | 206.28 | 592.39 | 0.00 | 0.00 | 0.00 |
December | 190.81 | 80.53 | 110.27 | 90.50 | 802.97 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 510.02 | 238.28 | 271.74 | 518.03 | 461.62 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 190.81 | 80.53 | 110.27 | 90.50 | 182.89 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 821.33 | 415.03 | 433.49 | 1050.89 | 864.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 208.92 | 84.20 | 124.73 | 101.92 | 864.18 | 0.00 | 0.00 | 0.00 |
February | 356.60 | 175.29 | 181.31 | 257.91 | 658.51 | 0.00 | 0.00 | 0.00 |
March | 456.36 | 167.22 | 289.14 | 342.65 | 570.82 | 0.00 | 0.00 | 0.00 |
April | 595.78 | 263.96 | 331.82 | 556.07 | 432.99 | 0.00 | 0.00 | 0.00 |
May | 736.94 | 336.09 | 400.86 | 774.96 | 316.09 | 0.00 | 0.00 | 0.00 |
June | 801.76 | 368.28 | 433.48 | 944.77 | 217.24 | 0.00 | 0.00 | 0.00 |
July | 821.32 | 415.02 | 406.29 | 1050.87 | 182.89 | 0.00 | 0.00 | 0.00 |
August | 697.41 | 342.27 | 355.14 | 861.59 | 206.76 | 0.00 | 0.00 | 0.00 |
September | 561.02 | 283.63 | 277.39 | 639.91 | 279.77 | 0.00 | 0.00 | 0.00 |
October | 400.98 | 199.22 | 201.75 | 372.54 | 423.35 | 0.00 | 0.00 | 0.00 |
November | 283.85 | 140.82 | 143.04 | 206.27 | 592.37 | 0.00 | 0.00 | 0.00 |
December | 190.80 | 80.53 | 110.27 | 90.50 | 802.96 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 510.01 | 238.27 | 271.73 | 518.02 | 461.61 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 190.80 | 80.53 | 110.27 | 90.50 | 182.89 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 821.32 | 415.02 | 433.48 | 1050.87 | 864.18 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 452.02 | 0.00 | 452.02 | 16.43 | 3710.44 | 0.00 | 0.00 | 0.00 |
February | 638.23 | 0.00 | 638.23 | 120.82 | 2735.38 | 0.00 | 0.00 | 0.00 |
March | 1036.77 | 0.00 | 1036.77 | 381.39 | 2206.96 | 0.00 | 0.00 | 0.00 |
April | 1182.14 | 6.90 | 1175.24 | 643.56 | 1571.62 | 0.00 | 0.00 | 0.00 |
May | 1552.43 | 91.99 | 1460.44 | 1168.27 | 1173.16 | 0.00 | 0.00 | 0.00 |
June | 1807.72 | 207.78 | 1599.93 | 1852.44 | 760.39 | 0.00 | 0.00 | 0.00 |
July | 1651.45 | 154.68 | 1496.77 | 2009.22 | 634.97 | 0.00 | 0.00 | 0.00 |
August | 1323.31 | 35.47 | 1287.84 | 1463.00 | 726.28 | 0.00 | 0.00 | 0.00 |
September | 991.07 | 0.36 | 990.71 | 863.01 | 1096.76 | 0.00 | 0.00 | 0.00 |
October | 722.93 | 0.00 | 722.93 | 343.15 | 1615.64 | 0.00 | 0.00 | 0.00 |
November | 491.45 | 0.00 | 491.45 | 85.96 | 2301.91 | 0.00 | 0.00 | 0.00 |
December | 379.05 | 0.00 | 379.05 | 8.70 | 3163.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1021.09 | 41.64 | 979.45 | 750.21 | 1804.58 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 379.05 | 0.00 | 379.05 | 8.70 | 634.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1807.72 | 207.78 | 1599.93 | 2009.22 | 3710.44 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 691.97 | 317.24 | 374.73 | 373.35 | 2282.20 | 0.00 | 0.00 | 0.00 |
February | 1082.30 | 537.34 | 544.96 | 819.40 | 1685.01 | 0.00 | 0.00 | 0.00 |
March | 1455.25 | 602.14 | 853.11 | 1193.36 | 1395.63 | 0.00 | 0.00 | 0.00 |
April | 1856.76 | 920.19 | 936.56 | 1793.65 | 1012.40 | 0.00 | 0.00 | 0.00 |
May | 2051.03 | 912.58 | 1138.45 | 2122.39 | 792.72 | 0.00 | 0.00 | 0.00 |
June | 2654.79 | 1366.15 | 1288.64 | 3153.61 | 524.85 | 0.00 | 0.00 | 0.00 |
July | 2786.28 | 1575.16 | 1211.12 | 3570.06 | 430.82 | 0.00 | 0.00 | 0.00 |
August | 2421.40 | 1349.13 | 1072.27 | 3029.26 | 485.67 | 0.00 | 0.00 | 0.00 |
September | 1712.90 | 884.19 | 828.71 | 1945.88 | 698.33 | 0.00 | 0.00 | 0.00 |
October | 1228.92 | 624.03 | 604.89 | 1165.67 | 1021.63 | 0.00 | 0.00 | 0.00 |
November | 778.86 | 363.63 | 415.24 | 546.03 | 1410.87 | 0.00 | 0.00 | 0.00 |
December | 574.46 | 246.73 | 327.73 | 293.93 | 1942.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1610.66 | 809.61 | 801.05 | 1672.07 | 1138.21 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 574.46 | 246.73 | 327.73 | 293.93 | 430.82 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2786.28 | 1575.16 | 1288.64 | 3570.06 | 2282.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 3186.24 | 2275.68 | 910.56 | 2956.95 | 3240.93 | 0.00 | 0.00 | 0.00 |
February | 4057.63 | 2918.40 | 1139.23 | 4135.42 | 2454.75 | 0.00 | 0.00 | 0.00 |
March | 3627.00 | 2036.75 | 1590.24 | 3682.65 | 2203.70 | 0.00 | 0.00 | 0.00 |
April | 2915.50 | 1394.50 | 1521.00 | 3074.24 | 1650.48 | 0.00 | 0.00 | 0.00 |
May | 2590.34 | 860.32 | 1730.02 | 2783.42 | 1293.35 | 0.00 | 0.00 | 0.00 |
June | 2573.77 | 750.63 | 1823.13 | 3159.72 | 888.19 | 0.00 | 0.00 | 0.00 |
July | 2774.78 | 1025.00 | 1749.79 | 3801.96 | 711.06 | 0.00 | 0.00 | 0.00 |
August | 3297.64 | 1662.61 | 1635.03 | 4378.80 | 805.92 | 0.00 | 0.00 | 0.00 |
September | 3657.48 | 2241.06 | 1416.43 | 4493.63 | 1150.23 | 0.00 | 0.00 | 0.00 |
October | 3823.70 | 2644.04 | 1179.66 | 4308.71 | 1625.05 | 0.00 | 0.00 | 0.00 |
November | 3486.08 | 2525.18 | 960.91 | 3586.88 | 2084.47 | 0.00 | 0.00 | 0.00 |
December | 3029.94 | 2187.92 | 842.02 | 2885.12 | 2757.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3246.08 | 1869.91 | 1376.16 | 3599.87 | 1736.15 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 2573.77 | 750.63 | 842.02 | 2783.42 | 711.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4057.63 | 2918.40 | 1823.13 | 4493.63 | 3240.93 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 626.78 | 252.60 | 374.18 | 322.58 | 2411.95 | 0.00 | 0.00 | 0.00 |
February | 1069.81 | 525.87 | 543.95 | 821.78 | 1766.16 | 0.00 | 0.00 | 0.00 |
March | 1369.10 | 501.66 | 867.44 | 1094.26 | 1490.22 | 0.00 | 0.00 | 0.00 |
April | 1787.37 | 791.89 | 995.48 | 1735.30 | 1106.39 | 0.00 | 0.00 | 0.00 |
May | 2210.84 | 1008.26 | 1202.58 | 2350.64 | 870.35 | 0.00 | 0.00 | 0.00 |
June | 2405.31 | 1104.85 | 1300.46 | 2859.27 | 601.48 | 0.00 | 0.00 | 0.00 |
July | 2463.98 | 1245.08 | 1218.89 | 3180.72 | 506.45 | 0.00 | 0.00 | 0.00 |
August | 2092.25 | 1026.83 | 1065.42 | 2625.71 | 548.40 | 0.00 | 0.00 | 0.00 |
September | 1683.08 | 850.90 | 832.18 | 1940.98 | 768.62 | 0.00 | 0.00 | 0.00 |
October | 1202.94 | 597.68 | 605.26 | 1167.25 | 1104.50 | 0.00 | 0.00 | 0.00 |
November | 851.57 | 422.45 | 429.12 | 667.71 | 1504.89 | 0.00 | 0.00 | 0.00 |
December | 572.41 | 241.60 | 330.81 | 309.06 | 2042.68 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1530.03 | 714.83 | 815.21 | 1593.60 | 1224.94 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 572.41 | 241.60 | 330.81 | 309.06 | 506.45 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2463.98 | 1245.08 | 1300.46 | 3180.72 | 2411.95 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 452.02 | 0.00 | 452.02 | 22.33 | 3590.54 | 0.00 | 0.00 | 0.00 |
February | 638.23 | 0.00 | 638.23 | 142.29 | 2609.77 | 0.00 | 0.00 | 0.00 |
March | 1036.77 | 0.00 | 1036.77 | 418.55 | 2072.44 | 0.00 | 0.00 | 0.00 |
April | 1182.14 | 6.90 | 1175.24 | 696.71 | 1442.64 | 0.00 | 0.00 | 0.00 |
May | 1552.43 | 91.99 | 1460.44 | 1206.12 | 1095.71 | 0.00 | 0.00 | 0.00 |
June | 1807.72 | 207.78 | 1599.93 | 1867.20 | 735.42 | 0.00 | 0.00 | 0.00 |
July | 1651.45 | 154.68 | 1496.77 | 2009.72 | 624.01 | 0.00 | 0.00 | 0.00 |
August | 1323.31 | 35.47 | 1287.84 | 1469.58 | 702.82 | 0.00 | 0.00 | 0.00 |
September | 991.07 | 0.36 | 990.71 | 889.55 | 1024.12 | 0.00 | 0.00 | 0.00 |
October | 722.93 | 0.00 | 722.93 | 394.76 | 1458.51 | 0.00 | 0.00 | 0.00 |
November | 491.45 | 0.00 | 491.45 | 107.42 | 2119.51 | 0.00 | 0.00 | 0.00 |
December | 379.05 | 0.00 | 379.05 | 11.08 | 3027.97 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1021.09 | 41.64 | 979.45 | 773.44 | 1705.36 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 379.05 | 0.00 | 379.05 | 11.08 | 624.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1807.72 | 207.78 | 1599.93 | 2009.72 | 3590.54 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 691.97 | 317.24 | 374.73 | 384.48 | 2207.87 | 0.00 | 0.00 | 0.00 |
February | 1082.30 | 537.34 | 544.96 | 844.59 | 1607.66 | 0.00 | 0.00 | 0.00 |
March | 1455.25 | 602.14 | 853.11 | 1224.31 | 1314.50 | 0.00 | 0.00 | 0.00 |
April | 1856.76 | 920.19 | 936.56 | 1823.62 | 942.01 | 0.00 | 0.00 | 0.00 |
May | 2051.03 | 912.58 | 1138.45 | 2136.29 | 749.63 | 0.00 | 0.00 | 0.00 |
June | 2654.79 | 1366.15 | 1288.64 | 3152.01 | 514.60 | 0.00 | 0.00 | 0.00 |
July | 2786.28 | 1575.16 | 1211.12 | 3562.26 | 427.71 | 0.00 | 0.00 | 0.00 |
August | 2421.40 | 1349.13 | 1072.27 | 3025.26 | 477.29 | 0.00 | 0.00 | 0.00 |
September | 1712.90 | 884.19 | 828.71 | 1956.45 | 665.35 | 0.00 | 0.00 | 0.00 |
October | 1228.92 | 624.03 | 604.89 | 1202.85 | 934.57 | 0.00 | 0.00 | 0.00 |
November | 778.86 | 363.63 | 415.24 | 575.00 | 1302.37 | 0.00 | 0.00 | 0.00 |
December | 574.46 | 246.73 | 327.73 | 304.63 | 1858.70 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1610.66 | 809.61 | 801.05 | 1687.41 | 1081.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 574.46 | 246.73 | 327.73 | 304.63 | 427.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2786.28 | 1575.16 | 1288.64 | 3562.26 | 2207.87 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 3186.24 | 2275.68 | 910.56 | 2992.27 | 3108.37 | 0.00 | 0.00 | 0.00 |
February | 4057.63 | 2918.40 | 1139.23 | 4178.29 | 2324.39 | 0.00 | 0.00 | 0.00 |
March | 3627.00 | 2036.75 | 1590.24 | 3723.78 | 2069.25 | 0.00 | 0.00 | 0.00 |
April | 2915.50 | 1394.50 | 1521.00 | 3113.36 | 1531.40 | 0.00 | 0.00 | 0.00 |
May | 2590.34 | 860.32 | 1730.02 | 2803.79 | 1217.96 | 0.00 | 0.00 | 0.00 |
June | 2573.77 | 750.63 | 1823.13 | 3161.31 | 861.85 | 0.00 | 0.00 | 0.00 |
July | 2774.78 | 1025.00 | 1749.79 | 3794.18 | 700.25 | 0.00 | 0.00 | 0.00 |
August | 3297.64 | 1662.61 | 1635.03 | 4372.77 | 787.22 | 0.00 | 0.00 | 0.00 |
September | 3657.48 | 2241.06 | 1416.43 | 4503.49 | 1092.44 | 0.00 | 0.00 | 0.00 |
October | 3823.70 | 2644.04 | 1179.66 | 4352.53 | 1491.18 | 0.00 | 0.00 | 0.00 |
November | 3486.08 | 2525.18 | 960.91 | 3649.16 | 1916.87 | 0.00 | 0.00 | 0.00 |
December | 3029.94 | 2187.92 | 842.02 | 2925.62 | 2618.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3246.08 | 1869.91 | 1376.16 | 3626.64 | 1640.91 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 2573.77 | 750.63 | 842.02 | 2803.79 | 700.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4057.63 | 2918.40 | 1823.13 | 4503.49 | 3108.37 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 626.78 | 252.60 | 374.18 | 330.64 | 2332.49 | 0.00 | 0.00 | 0.00 |
February | 1069.81 | 525.87 | 543.95 | 836.81 | 1689.87 | 0.00 | 0.00 | 0.00 |
March | 1369.10 | 501.66 | 867.44 | 1113.36 | 1412.34 | 0.00 | 0.00 | 0.00 |
April | 1787.37 | 791.89 | 995.48 | 1759.74 | 1035.62 | 0.00 | 0.00 | 0.00 |
May | 2210.84 | 1008.26 | 1202.58 | 2362.50 | 824.51 | 0.00 | 0.00 | 0.00 |
June | 2405.31 | 1104.85 | 1300.46 | 2859.31 | 585.96 | 0.00 | 0.00 | 0.00 |
July | 2463.98 | 1245.08 | 1218.89 | 3175.37 | 499.81 | 0.00 | 0.00 | 0.00 |
August | 2092.25 | 1026.83 | 1065.42 | 2623.83 | 536.45 | 0.00 | 0.00 | 0.00 |
September | 1683.08 | 850.90 | 832.18 | 1950.01 | 731.32 | 0.00 | 0.00 | 0.00 |
October | 1202.94 | 597.68 | 605.26 | 1192.70 | 1020.91 | 0.00 | 0.00 | 0.00 |
November | 851.57 | 422.45 | 429.12 | 687.52 | 1402.32 | 0.00 | 0.00 | 0.00 |
December | 572.41 | 241.60 | 330.81 | 316.43 | 1961.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1530.03 | 714.83 | 815.21 | 1604.62 | 1167.64 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 572.41 | 241.60 | 330.81 | 316.43 | 499.81 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2463.98 | 1245.08 | 1300.46 | 3175.37 | 2332.49 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.242139E+09 | 0.00 | 0.242139E+09 | 4144356.69 | 0.211726E+10 |
February | 0.308799E+09 | 0.00 | 0.308799E+09 | 37567572.19 | 0.144141E+10 |
March | 0.555376E+09 | 0.00 | 0.555376E+09 | 0.165897E+09 | 0.130699E+10 |
April | 0.612820E+09 | 3576254.47 | 0.609243E+09 | 0.297649E+09 | 0.910373E+09 |
May | 0.831604E+09 | 49277394.08 | 0.782327E+09 | 0.601795E+09 | 0.678341E+09 |
June | 0.937120E+09 | 0.107713E+09 | 0.829407E+09 | 0.948421E+09 | 0.410883E+09 |
July | 0.884648E+09 | 82857303.69 | 0.801791E+09 | 0.106496E+10 | 0.350192E+09 |
August | 0.708873E+09 | 19000970.75 | 0.689872E+09 | 0.770386E+09 | 0.406100E+09 |
September | 0.513771E+09 | 184367.60 | 0.513587E+09 | 0.432120E+09 | 0.610751E+09 |
October | 0.387258E+09 | 0.00 | 0.387258E+09 | 0.155137E+09 | 0.967981E+09 |
November | 0.254769E+09 | 0.00 | 0.254769E+09 | 29393412.55 | 0.135582E+10 |
December | 0.203047E+09 | 0.00 | 0.203047E+09 | 1225117.95 | 0.189556E+10 |
Annual Sum or Average | 0.644022E+10 | 0.262610E+09 | 0.617761E+10 | 0.450870E+10 | 0.124517E+11 |
Minimum of Months | 0.203047E+09 | 0.00 | 0.203047E+09 | 1225117.95 | 0.350192E+09 |
Maximum of Months | 0.937120E+09 | 0.107713E+09 | 0.829407E+09 | 0.106496E+10 | 0.211726E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.242135E+09 | 0.00 | 0.242135E+09 | 4143972.50 | 0.211726E+10 |
February | 0.308795E+09 | 0.00 | 0.308795E+09 | 37565757.63 | 0.144141E+10 |
March | 0.555368E+09 | 0.00 | 0.555368E+09 | 0.165891E+09 | 0.130699E+10 |
April | 0.612811E+09 | 3576175.85 | 0.609235E+09 | 0.297642E+09 | 0.910374E+09 |
May | 0.831592E+09 | 49276310.77 | 0.782316E+09 | 0.601782E+09 | 0.678341E+09 |
June | 0.937106E+09 | 0.107711E+09 | 0.829396E+09 | 0.948405E+09 | 0.410882E+09 |
July | 0.884636E+09 | 82855482.17 | 0.801781E+09 | 0.106495E+10 | 0.350190E+09 |
August | 0.708864E+09 | 19000553.03 | 0.689863E+09 | 0.770376E+09 | 0.406098E+09 |
September | 0.513764E+09 | 184363.55 | 0.513580E+09 | 0.432113E+09 | 0.610750E+09 |
October | 0.387253E+09 | 0.00 | 0.387253E+09 | 0.155133E+09 | 0.967980E+09 |
November | 0.254766E+09 | 0.00 | 0.254766E+09 | 29391901.29 | 0.135582E+10 |
December | 0.203044E+09 | 0.00 | 0.203044E+09 | 1224965.04 | 0.189556E+10 |
Annual Sum or Average | 0.644013E+10 | 0.262604E+09 | 0.617753E+10 | 0.450862E+10 | 0.124517E+11 |
Minimum of Months | 0.203044E+09 | 0.00 | 0.203044E+09 | 1224965.04 | 0.350190E+09 |
Maximum of Months | 0.937106E+09 | 0.107711E+09 | 0.829396E+09 | 0.106495E+10 | 0.211726E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.242136E+09 | 0.00 | 0.242136E+09 | 4144100.56 | 0.211726E+10 |
February | 0.308796E+09 | 0.00 | 0.308796E+09 | 37566362.49 | 0.144141E+10 |
March | 0.555371E+09 | 0.00 | 0.555371E+09 | 0.165893E+09 | 0.130699E+10 |
April | 0.612814E+09 | 3576202.05 | 0.609237E+09 | 0.297644E+09 | 0.910373E+09 |
May | 0.831596E+09 | 49276671.88 | 0.782319E+09 | 0.601786E+09 | 0.678341E+09 |
June | 0.937111E+09 | 0.107712E+09 | 0.829399E+09 | 0.948410E+09 | 0.410882E+09 |
July | 0.884640E+09 | 82856089.35 | 0.801784E+09 | 0.106495E+10 | 0.350191E+09 |
August | 0.708867E+09 | 19000692.27 | 0.689866E+09 | 0.770379E+09 | 0.406099E+09 |
September | 0.513767E+09 | 184364.90 | 0.513582E+09 | 0.432115E+09 | 0.610750E+09 |
October | 0.387254E+09 | 0.00 | 0.387254E+09 | 0.155134E+09 | 0.967980E+09 |
November | 0.254767E+09 | 0.00 | 0.254767E+09 | 29392405.04 | 0.135582E+10 |
December | 0.203045E+09 | 0.00 | 0.203045E+09 | 1225016.01 | 0.189556E+10 |
Annual Sum or Average | 0.644016E+10 | 0.262606E+09 | 0.617756E+10 | 0.450864E+10 | 0.124517E+11 |
Minimum of Months | 0.203045E+09 | 0.00 | 0.203045E+09 | 1225016.01 | 0.350191E+09 |
Maximum of Months | 0.937111E+09 | 0.107712E+09 | 0.829399E+09 | 0.106495E+10 | 0.211726E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.242135E+09 | 0.00 | 0.242135E+09 | 4143972.50 | 0.211726E+10 |
February | 0.308795E+09 | 0.00 | 0.308795E+09 | 37565757.63 | 0.144141E+10 |
March | 0.555368E+09 | 0.00 | 0.555368E+09 | 0.165891E+09 | 0.130699E+10 |
April | 0.612811E+09 | 3576175.85 | 0.609235E+09 | 0.297642E+09 | 0.910374E+09 |
May | 0.831592E+09 | 49276310.77 | 0.782316E+09 | 0.601782E+09 | 0.678341E+09 |
June | 0.937106E+09 | 0.107711E+09 | 0.829396E+09 | 0.948405E+09 | 0.410882E+09 |
July | 0.884636E+09 | 82855482.17 | 0.801781E+09 | 0.106495E+10 | 0.350190E+09 |
August | 0.708864E+09 | 19000553.03 | 0.689863E+09 | 0.770376E+09 | 0.406098E+09 |
September | 0.513764E+09 | 184363.55 | 0.513580E+09 | 0.432113E+09 | 0.610750E+09 |
October | 0.387253E+09 | 0.00 | 0.387253E+09 | 0.155133E+09 | 0.967980E+09 |
November | 0.254766E+09 | 0.00 | 0.254766E+09 | 29391901.29 | 0.135582E+10 |
December | 0.203044E+09 | 0.00 | 0.203044E+09 | 1224965.04 | 0.189556E+10 |
Annual Sum or Average | 0.644013E+10 | 0.262604E+09 | 0.617753E+10 | 0.450862E+10 | 0.124517E+11 |
Minimum of Months | 0.203044E+09 | 0.00 | 0.203044E+09 | 1224965.04 | 0.350190E+09 |
Maximum of Months | 0.937106E+09 | 0.107711E+09 | 0.829396E+09 | 0.106495E+10 | 0.211726E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.242126E+09 | 0.00 | 0.242126E+09 | 4143869.51 | 0.211717E+10 |
February | 0.308783E+09 | 0.00 | 0.308783E+09 | 37564545.98 | 0.144135E+10 |
March | 0.555347E+09 | 0.00 | 0.555347E+09 | 0.165885E+09 | 0.130694E+10 |
April | 0.612788E+09 | 3576044.81 | 0.609211E+09 | 0.297631E+09 | 0.910337E+09 |
May | 0.831561E+09 | 49274505.26 | 0.782286E+09 | 0.601760E+09 | 0.678314E+09 |
June | 0.937071E+09 | 0.107707E+09 | 0.829364E+09 | 0.948369E+09 | 0.410866E+09 |
July | 0.884602E+09 | 82852446.31 | 0.801750E+09 | 0.106491E+10 | 0.350176E+09 |
August | 0.708837E+09 | 18999856.84 | 0.689837E+09 | 0.770347E+09 | 0.406082E+09 |
September | 0.513745E+09 | 184356.80 | 0.513560E+09 | 0.432097E+09 | 0.610725E+09 |
October | 0.387238E+09 | 0.00 | 0.387238E+09 | 0.155127E+09 | 0.967941E+09 |
November | 0.254756E+09 | 0.00 | 0.254756E+09 | 29390968.53 | 0.135576E+10 |
December | 0.203036E+09 | 0.00 | 0.203036E+09 | 1224941.15 | 0.189548E+10 |
Annual Sum or Average | 0.643989E+10 | 0.262594E+09 | 0.617729E+10 | 0.450845E+10 | 0.124512E+11 |
Minimum of Months | 0.203036E+09 | 0.00 | 0.203036E+09 | 1224941.15 | 0.350176E+09 |
Maximum of Months | 0.937071E+09 | 0.107707E+09 | 0.829364E+09 | 0.106491E+10 | 0.211717E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.617795E+09 | 0.283234E+09 | 0.334561E+09 | 0.317516E+09 | 0.214838E+10 |
February | 0.872775E+09 | 0.433312E+09 | 0.439463E+09 | 0.636620E+09 | 0.145150E+10 |
March | 0.129926E+10 | 0.537598E+09 | 0.761663E+09 | 0.103758E+10 | 0.133654E+10 |
April | 0.160425E+10 | 0.795056E+09 | 0.809197E+09 | 0.153558E+10 | 0.934642E+09 |
May | 0.183118E+10 | 0.814759E+09 | 0.101642E+10 | 0.188994E+10 | 0.750881E+09 |
June | 0.229376E+10 | 0.118037E+10 | 0.111339E+10 | 0.273577E+10 | 0.460925E+09 |
July | 0.248761E+10 | 0.140631E+10 | 0.108130E+10 | 0.320249E+10 | 0.378550E+09 |
August | 0.216185E+10 | 0.120451E+10 | 0.957333E+09 | 0.271828E+10 | 0.425225E+09 |
September | 0.147996E+10 | 0.763951E+09 | 0.716011E+09 | 0.168086E+10 | 0.631778E+09 |
October | 0.109719E+10 | 0.557135E+09 | 0.540053E+09 | 0.102060E+10 | 0.986565E+09 |
November | 0.672946E+09 | 0.314177E+09 | 0.358768E+09 | 0.446597E+09 | 0.133817E+10 |
December | 0.512881E+09 | 0.220284E+09 | 0.292597E+09 | 0.242078E+09 | 0.188789E+10 |
Annual Sum or Average | 0.169315E+11 | 0.851070E+10 | 0.842076E+10 | 0.174639E+11 | 0.127310E+11 |
Minimum of Months | 0.512881E+09 | 0.220284E+09 | 0.292597E+09 | 0.242078E+09 | 0.378550E+09 |
Maximum of Months | 0.248761E+10 | 0.140631E+10 | 0.111339E+10 | 0.320249E+10 | 0.214838E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.617795E+09 | 0.283234E+09 | 0.334561E+09 | 0.317516E+09 | 0.214838E+10 |
February | 0.872775E+09 | 0.433312E+09 | 0.439463E+09 | 0.636620E+09 | 0.145150E+10 |
March | 0.129926E+10 | 0.537598E+09 | 0.761663E+09 | 0.103758E+10 | 0.133654E+10 |
April | 0.160425E+10 | 0.795056E+09 | 0.809197E+09 | 0.153558E+10 | 0.934642E+09 |
May | 0.183118E+10 | 0.814759E+09 | 0.101642E+10 | 0.188994E+10 | 0.750881E+09 |
June | 0.229376E+10 | 0.118037E+10 | 0.111339E+10 | 0.273577E+10 | 0.460925E+09 |
July | 0.248761E+10 | 0.140631E+10 | 0.108130E+10 | 0.320249E+10 | 0.378550E+09 |
August | 0.216185E+10 | 0.120451E+10 | 0.957333E+09 | 0.271828E+10 | 0.425225E+09 |
September | 0.147996E+10 | 0.763951E+09 | 0.716011E+09 | 0.168086E+10 | 0.631778E+09 |
October | 0.109719E+10 | 0.557135E+09 | 0.540053E+09 | 0.102060E+10 | 0.986565E+09 |
November | 0.672946E+09 | 0.314177E+09 | 0.358768E+09 | 0.446597E+09 | 0.133817E+10 |
December | 0.512881E+09 | 0.220284E+09 | 0.292597E+09 | 0.242078E+09 | 0.188789E+10 |
Annual Sum or Average | 0.169315E+11 | 0.851070E+10 | 0.842076E+10 | 0.174639E+11 | 0.127310E+11 |
Minimum of Months | 0.512881E+09 | 0.220284E+09 | 0.292597E+09 | 0.242078E+09 | 0.378550E+09 |
Maximum of Months | 0.248761E+10 | 0.140631E+10 | 0.111339E+10 | 0.320249E+10 | 0.214838E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.617784E+09 | 0.283229E+09 | 0.334555E+09 | 0.317510E+09 | 0.214834E+10 |
February | 0.872759E+09 | 0.433304E+09 | 0.439455E+09 | 0.636609E+09 | 0.145147E+10 |
March | 0.129924E+10 | 0.537588E+09 | 0.761649E+09 | 0.103757E+10 | 0.133651E+10 |
April | 0.160422E+10 | 0.795042E+09 | 0.809182E+09 | 0.153556E+10 | 0.934625E+09 |
May | 0.183114E+10 | 0.814744E+09 | 0.101640E+10 | 0.188990E+10 | 0.750868E+09 |
June | 0.229372E+10 | 0.118035E+10 | 0.111337E+10 | 0.273572E+10 | 0.460916E+09 |
July | 0.248757E+10 | 0.140629E+10 | 0.108128E+10 | 0.320243E+10 | 0.378543E+09 |
August | 0.216181E+10 | 0.120449E+10 | 0.957315E+09 | 0.271824E+10 | 0.425217E+09 |
September | 0.147994E+10 | 0.763937E+09 | 0.715998E+09 | 0.168083E+10 | 0.631767E+09 |
October | 0.109717E+10 | 0.557125E+09 | 0.540043E+09 | 0.102058E+10 | 0.986546E+09 |
November | 0.672933E+09 | 0.314171E+09 | 0.358762E+09 | 0.446589E+09 | 0.133814E+10 |
December | 0.512872E+09 | 0.220279E+09 | 0.292592E+09 | 0.242074E+09 | 0.188785E+10 |
Annual Sum or Average | 0.169312E+11 | 0.851055E+10 | 0.842060E+10 | 0.174636E+11 | 0.127308E+11 |
Minimum of Months | 0.512872E+09 | 0.220279E+09 | 0.292592E+09 | 0.242074E+09 | 0.378543E+09 |
Maximum of Months | 0.248757E+10 | 0.140629E+10 | 0.111337E+10 | 0.320243E+10 | 0.214834E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.170677E+10 | 0.121901E+10 | 0.487764E+09 | 0.158389E+10 | 0.177950E+10 |
February | 0.196321E+10 | 0.141201E+10 | 0.551198E+09 | 0.200422E+10 | 0.122768E+10 |
March | 0.194287E+10 | 0.109103E+10 | 0.851849E+09 | 0.197436E+10 | 0.122671E+10 |
April | 0.151137E+10 | 0.722894E+09 | 0.788475E+09 | 0.159257E+10 | 0.897040E+09 |
May | 0.138758E+10 | 0.460849E+09 | 0.926727E+09 | 0.149349E+10 | 0.718061E+09 |
June | 0.133422E+10 | 0.389120E+09 | 0.945104E+09 | 0.164139E+10 | 0.471074E+09 |
July | 0.148637E+10 | 0.549058E+09 | 0.937317E+09 | 0.204033E+10 | 0.384238E+09 |
August | 0.176645E+10 | 0.890610E+09 | 0.875845E+09 | 0.235253E+10 | 0.436123E+09 |
September | 0.189601E+10 | 0.116174E+10 | 0.734266E+09 | 0.234416E+10 | 0.608406E+09 |
October | 0.204824E+10 | 0.141633E+10 | 0.631912E+09 | 0.231729E+10 | 0.899202E+09 |
November | 0.180715E+10 | 0.130903E+10 | 0.498126E+09 | 0.185639E+10 | 0.112902E+10 |
December | 0.162305E+10 | 0.117200E+10 | 0.451044E+09 | 0.153040E+10 | 0.155904E+10 |
Annual Sum or Average | 0.204733E+11 | 0.117937E+11 | 0.867963E+10 | 0.227310E+11 | 0.113361E+11 |
Minimum of Months | 0.133422E+10 | 0.389120E+09 | 0.451044E+09 | 0.149349E+10 | 0.384238E+09 |
Maximum of Months | 0.204824E+10 | 0.141633E+10 | 0.945104E+09 | 0.235253E+10 | 0.177950E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.170676E+10 | 0.121900E+10 | 0.487761E+09 | 0.158388E+10 | 0.177950E+10 |
February | 0.196319E+10 | 0.141200E+10 | 0.551195E+09 | 0.200421E+10 | 0.122768E+10 |
March | 0.194286E+10 | 0.109102E+10 | 0.851844E+09 | 0.197434E+10 | 0.122671E+10 |
April | 0.151136E+10 | 0.722889E+09 | 0.788471E+09 | 0.159256E+10 | 0.897040E+09 |
May | 0.138757E+10 | 0.460846E+09 | 0.926722E+09 | 0.149348E+10 | 0.718061E+09 |
June | 0.133422E+10 | 0.389117E+09 | 0.945099E+09 | 0.164138E+10 | 0.471074E+09 |
July | 0.148637E+10 | 0.549054E+09 | 0.937312E+09 | 0.204032E+10 | 0.384237E+09 |
August | 0.176644E+10 | 0.890603E+09 | 0.875840E+09 | 0.235252E+10 | 0.436122E+09 |
September | 0.189599E+10 | 0.116173E+10 | 0.734262E+09 | 0.234414E+10 | 0.608406E+09 |
October | 0.204823E+10 | 0.141632E+10 | 0.631909E+09 | 0.231727E+10 | 0.899201E+09 |
November | 0.180714E+10 | 0.130902E+10 | 0.498123E+09 | 0.185638E+10 | 0.112902E+10 |
December | 0.162303E+10 | 0.117199E+10 | 0.451041E+09 | 0.153039E+10 | 0.155904E+10 |
Annual Sum or Average | 0.204732E+11 | 0.117936E+11 | 0.867958E+10 | 0.227309E+11 | 0.113361E+11 |
Minimum of Months | 0.133422E+10 | 0.389117E+09 | 0.451041E+09 | 0.149348E+10 | 0.384237E+09 |
Maximum of Months | 0.204823E+10 | 0.141632E+10 | 0.945099E+09 | 0.235252E+10 | 0.177950E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.170677E+10 | 0.121901E+10 | 0.487764E+09 | 0.158389E+10 | 0.177950E+10 |
February | 0.196321E+10 | 0.141201E+10 | 0.551198E+09 | 0.200422E+10 | 0.122768E+10 |
March | 0.194287E+10 | 0.109103E+10 | 0.851849E+09 | 0.197436E+10 | 0.122671E+10 |
April | 0.151137E+10 | 0.722894E+09 | 0.788475E+09 | 0.159257E+10 | 0.897040E+09 |
May | 0.138758E+10 | 0.460849E+09 | 0.926727E+09 | 0.149349E+10 | 0.718061E+09 |
June | 0.133422E+10 | 0.389120E+09 | 0.945104E+09 | 0.164139E+10 | 0.471074E+09 |
July | 0.148637E+10 | 0.549058E+09 | 0.937317E+09 | 0.204033E+10 | 0.384238E+09 |
August | 0.176645E+10 | 0.890610E+09 | 0.875845E+09 | 0.235253E+10 | 0.436123E+09 |
September | 0.189601E+10 | 0.116174E+10 | 0.734266E+09 | 0.234416E+10 | 0.608406E+09 |
October | 0.204824E+10 | 0.141633E+10 | 0.631912E+09 | 0.231729E+10 | 0.899202E+09 |
November | 0.180715E+10 | 0.130903E+10 | 0.498126E+09 | 0.185639E+10 | 0.112902E+10 |
December | 0.162305E+10 | 0.117200E+10 | 0.451044E+09 | 0.153040E+10 | 0.155904E+10 |
Annual Sum or Average | 0.204733E+11 | 0.117937E+11 | 0.867963E+10 | 0.227310E+11 | 0.113361E+11 |
Minimum of Months | 0.133422E+10 | 0.389120E+09 | 0.451044E+09 | 0.149349E+10 | 0.384238E+09 |
Maximum of Months | 0.204824E+10 | 0.141633E+10 | 0.945104E+09 | 0.235253E+10 | 0.177950E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.170676E+10 | 0.121900E+10 | 0.487761E+09 | 0.158388E+10 | 0.177950E+10 |
February | 0.196319E+10 | 0.141200E+10 | 0.551195E+09 | 0.200421E+10 | 0.122768E+10 |
March | 0.194286E+10 | 0.109102E+10 | 0.851844E+09 | 0.197434E+10 | 0.122671E+10 |
April | 0.151136E+10 | 0.722889E+09 | 0.788471E+09 | 0.159256E+10 | 0.897040E+09 |
May | 0.138757E+10 | 0.460846E+09 | 0.926722E+09 | 0.149348E+10 | 0.718061E+09 |
June | 0.133422E+10 | 0.389117E+09 | 0.945099E+09 | 0.164138E+10 | 0.471074E+09 |
July | 0.148637E+10 | 0.549054E+09 | 0.937312E+09 | 0.204032E+10 | 0.384237E+09 |
August | 0.176644E+10 | 0.890603E+09 | 0.875840E+09 | 0.235252E+10 | 0.436122E+09 |
September | 0.189599E+10 | 0.116173E+10 | 0.734262E+09 | 0.234414E+10 | 0.608406E+09 |
October | 0.204823E+10 | 0.141632E+10 | 0.631909E+09 | 0.231727E+10 | 0.899201E+09 |
November | 0.180714E+10 | 0.130902E+10 | 0.498123E+09 | 0.185638E+10 | 0.112902E+10 |
December | 0.162303E+10 | 0.117199E+10 | 0.451041E+09 | 0.153039E+10 | 0.155904E+10 |
Annual Sum or Average | 0.204732E+11 | 0.117936E+11 | 0.867958E+10 | 0.227309E+11 | 0.113361E+11 |
Minimum of Months | 0.133422E+10 | 0.389117E+09 | 0.451041E+09 | 0.149348E+10 | 0.384237E+09 |
Maximum of Months | 0.204823E+10 | 0.141632E+10 | 0.945099E+09 | 0.235252E+10 | 0.177950E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.170670E+10 | 0.121896E+10 | 0.487742E+09 | 0.158382E+10 | 0.177943E+10 |
February | 0.196312E+10 | 0.141195E+10 | 0.551174E+09 | 0.200413E+10 | 0.122763E+10 |
March | 0.194279E+10 | 0.109098E+10 | 0.851812E+09 | 0.197427E+10 | 0.122666E+10 |
April | 0.151130E+10 | 0.722862E+09 | 0.788441E+09 | 0.159250E+10 | 0.897004E+09 |
May | 0.138752E+10 | 0.460829E+09 | 0.926687E+09 | 0.149343E+10 | 0.718032E+09 |
June | 0.133417E+10 | 0.389103E+09 | 0.945063E+09 | 0.164132E+10 | 0.471055E+09 |
July | 0.148631E+10 | 0.549034E+09 | 0.937277E+09 | 0.204024E+10 | 0.384222E+09 |
August | 0.176638E+10 | 0.890571E+09 | 0.875807E+09 | 0.235243E+10 | 0.436105E+09 |
September | 0.189592E+10 | 0.116169E+10 | 0.734234E+09 | 0.234405E+10 | 0.608381E+09 |
October | 0.204815E+10 | 0.141627E+10 | 0.631885E+09 | 0.231719E+10 | 0.899165E+09 |
November | 0.180707E+10 | 0.130897E+10 | 0.498104E+09 | 0.185631E+10 | 0.112897E+10 |
December | 0.162297E+10 | 0.117195E+10 | 0.451025E+09 | 0.153034E+10 | 0.155897E+10 |
Annual Sum or Average | 0.204724E+11 | 0.117932E+11 | 0.867925E+10 | 0.227300E+11 | 0.113356E+11 |
Minimum of Months | 0.133417E+10 | 0.389103E+09 | 0.451025E+09 | 0.149343E+10 | 0.384222E+09 |
Maximum of Months | 0.204815E+10 | 0.141627E+10 | 0.945063E+09 | 0.235243E+10 | 0.177943E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.559591E+09 | 0.225519E+09 | 0.334072E+09 | 0.272988E+09 | 0.231467E+10 |
February | 0.862705E+09 | 0.424063E+09 | 0.438642E+09 | 0.623945E+09 | 0.159311E+10 |
March | 0.122234E+10 | 0.447885E+09 | 0.774459E+09 | 0.917784E+09 | 0.152891E+10 |
April | 0.154430E+10 | 0.684197E+09 | 0.860104E+09 | 0.144137E+10 | 0.112232E+10 |
May | 0.197386E+10 | 0.900187E+09 | 0.107368E+10 | 0.207570E+10 | 0.846642E+09 |
June | 0.207821E+10 | 0.954601E+09 | 0.112361E+10 | 0.244888E+10 | 0.563098E+09 |
July | 0.219986E+10 | 0.111162E+10 | 0.108824E+10 | 0.281470E+10 | 0.489863E+09 |
August | 0.186798E+10 | 0.916764E+09 | 0.951214E+09 | 0.230772E+10 | 0.553807E+09 |
September | 0.145420E+10 | 0.735184E+09 | 0.719015E+09 | 0.165867E+10 | 0.725175E+09 |
October | 0.107400E+10 | 0.533611E+09 | 0.540386E+09 | 0.997838E+09 | 0.113391E+10 |
November | 0.735763E+09 | 0.365001E+09 | 0.370762E+09 | 0.534674E+09 | 0.153546E+10 |
December | 0.511052E+09 | 0.215701E+09 | 0.295352E+09 | 0.242407E+09 | 0.215069E+10 |
Annual Sum or Average | 0.160839E+11 | 0.751434E+10 | 0.856953E+10 | 0.163367E+11 | 0.145577E+11 |
Minimum of Months | 0.511052E+09 | 0.215701E+09 | 0.295352E+09 | 0.242407E+09 | 0.489863E+09 |
Maximum of Months | 0.219986E+10 | 0.111162E+10 | 0.112361E+10 | 0.281470E+10 | 0.231467E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.559591E+09 | 0.225519E+09 | 0.334072E+09 | 0.272988E+09 | 0.231467E+10 |
February | 0.862705E+09 | 0.424063E+09 | 0.438642E+09 | 0.623945E+09 | 0.159311E+10 |
March | 0.122234E+10 | 0.447885E+09 | 0.774459E+09 | 0.917784E+09 | 0.152891E+10 |
April | 0.154430E+10 | 0.684197E+09 | 0.860104E+09 | 0.144137E+10 | 0.112232E+10 |
May | 0.197386E+10 | 0.900187E+09 | 0.107368E+10 | 0.207570E+10 | 0.846642E+09 |
June | 0.207821E+10 | 0.954601E+09 | 0.112361E+10 | 0.244888E+10 | 0.563098E+09 |
July | 0.219986E+10 | 0.111162E+10 | 0.108824E+10 | 0.281470E+10 | 0.489863E+09 |
August | 0.186798E+10 | 0.916764E+09 | 0.951214E+09 | 0.230772E+10 | 0.553807E+09 |
September | 0.145420E+10 | 0.735184E+09 | 0.719015E+09 | 0.165867E+10 | 0.725175E+09 |
October | 0.107400E+10 | 0.533611E+09 | 0.540386E+09 | 0.997838E+09 | 0.113391E+10 |
November | 0.735763E+09 | 0.365001E+09 | 0.370762E+09 | 0.534674E+09 | 0.153546E+10 |
December | 0.511052E+09 | 0.215701E+09 | 0.295352E+09 | 0.242407E+09 | 0.215069E+10 |
Annual Sum or Average | 0.160839E+11 | 0.751434E+10 | 0.856953E+10 | 0.163367E+11 | 0.145577E+11 |
Minimum of Months | 0.511052E+09 | 0.215701E+09 | 0.295352E+09 | 0.242407E+09 | 0.489863E+09 |
Maximum of Months | 0.219986E+10 | 0.111162E+10 | 0.112361E+10 | 0.281470E+10 | 0.231467E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.559581E+09 | 0.225515E+09 | 0.334066E+09 | 0.272983E+09 | 0.231463E+10 |
February | 0.862689E+09 | 0.424056E+09 | 0.438634E+09 | 0.623933E+09 | 0.159308E+10 |
March | 0.122232E+10 | 0.447877E+09 | 0.774445E+09 | 0.917767E+09 | 0.152889E+10 |
April | 0.154427E+10 | 0.684184E+09 | 0.860088E+09 | 0.144134E+10 | 0.112230E+10 |
May | 0.197383E+10 | 0.900170E+09 | 0.107366E+10 | 0.207566E+10 | 0.846627E+09 |
June | 0.207817E+10 | 0.954583E+09 | 0.112359E+10 | 0.244884E+10 | 0.563088E+09 |
July | 0.219982E+10 | 0.111160E+10 | 0.108822E+10 | 0.281465E+10 | 0.489854E+09 |
August | 0.186794E+10 | 0.916748E+09 | 0.951197E+09 | 0.230768E+10 | 0.553797E+09 |
September | 0.145417E+10 | 0.735170E+09 | 0.719002E+09 | 0.165864E+10 | 0.725162E+09 |
October | 0.107398E+10 | 0.533602E+09 | 0.540376E+09 | 0.997820E+09 | 0.113389E+10 |
November | 0.735749E+09 | 0.364994E+09 | 0.370755E+09 | 0.534664E+09 | 0.153543E+10 |
December | 0.511043E+09 | 0.215697E+09 | 0.295346E+09 | 0.242403E+09 | 0.215065E+10 |
Annual Sum or Average | 0.160836E+11 | 0.751420E+10 | 0.856937E+10 | 0.163364E+11 | 0.145574E+11 |
Minimum of Months | 0.511043E+09 | 0.215697E+09 | 0.295346E+09 | 0.242403E+09 | 0.489854E+09 |
Maximum of Months | 0.219982E+10 | 0.111160E+10 | 0.112359E+10 | 0.281465E+10 | 0.231463E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.121069E+10 | 0.00 | 0.121069E+10 | 44006795.58 | 0.993806E+10 |
February | 0.154399E+10 | 0.00 | 0.154399E+10 | 0.292293E+09 | 0.661744E+10 |
March | 0.277688E+10 | 0.00 | 0.277688E+10 | 0.102152E+10 | 0.591112E+10 |
April | 0.306410E+10 | 17881386.28 | 0.304622E+10 | 0.166810E+10 | 0.407364E+10 |
May | 0.415802E+10 | 0.246389E+09 | 0.391163E+10 | 0.312909E+10 | 0.314220E+10 |
June | 0.468560E+10 | 0.538570E+09 | 0.414703E+10 | 0.480153E+10 | 0.197094E+10 |
July | 0.442324E+10 | 0.414289E+09 | 0.400895E+10 | 0.538150E+10 | 0.170071E+10 |
August | 0.354436E+10 | 95005459.17 | 0.344936E+10 | 0.391850E+10 | 0.194526E+10 |
September | 0.256885E+10 | 921843.89 | 0.256793E+10 | 0.223693E+10 | 0.284281E+10 |
October | 0.193629E+10 | 0.00 | 0.193629E+10 | 0.919081E+09 | 0.432733E+10 |
November | 0.127385E+10 | 0.00 | 0.127385E+10 | 0.222805E+09 | 0.596655E+10 |
December | 0.101523E+10 | 0.00 | 0.101523E+10 | 23303430.79 | 0.847319E+10 |
Annual Sum or Average | 0.322011E+11 | 0.131306E+10 | 0.308881E+11 | 0.236587E+11 | 0.569092E+11 |
Minimum of Months | 0.101523E+10 | 0.00 | 0.101523E+10 | 23303430.79 | 0.170071E+10 |
Maximum of Months | 0.468560E+10 | 0.538570E+09 | 0.414703E+10 | 0.538150E+10 | 0.993806E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.185337E+10 | 0.849694E+09 | 0.100367E+10 | 0.999969E+09 | 0.611264E+10 |
February | 0.261830E+10 | 0.129992E+10 | 0.131838E+10 | 0.198228E+10 | 0.407638E+10 |
March | 0.389774E+10 | 0.161278E+10 | 0.228496E+10 | 0.319630E+10 | 0.373806E+10 |
April | 0.481271E+10 | 0.238514E+10 | 0.242757E+10 | 0.464914E+10 | 0.262414E+10 |
May | 0.549347E+10 | 0.244425E+10 | 0.304922E+10 | 0.568462E+10 | 0.212322E+10 |
June | 0.688122E+10 | 0.354107E+10 | 0.334015E+10 | 0.817417E+10 | 0.136040E+10 |
July | 0.746276E+10 | 0.421890E+10 | 0.324386E+10 | 0.956204E+10 | 0.115392E+10 |
August | 0.648547E+10 | 0.361351E+10 | 0.287197E+10 | 0.811357E+10 | 0.130083E+10 |
September | 0.443984E+10 | 0.229183E+10 | 0.214801E+10 | 0.504372E+10 | 0.181006E+10 |
October | 0.329153E+10 | 0.167139E+10 | 0.162014E+10 | 0.312213E+10 | 0.273634E+10 |
November | 0.201882E+10 | 0.942522E+09 | 0.107629E+10 | 0.141532E+10 | 0.365697E+10 |
December | 0.153863E+10 | 0.660844E+09 | 0.877783E+09 | 0.787250E+09 | 0.520162E+10 |
Annual Sum or Average | 0.507939E+11 | 0.255318E+11 | 0.252620E+11 | 0.527305E+11 | 0.358946E+11 |
Minimum of Months | 0.153863E+10 | 0.660844E+09 | 0.877783E+09 | 0.787250E+09 | 0.115392E+10 |
Maximum of Months | 0.746276E+10 | 0.421890E+10 | 0.334015E+10 | 0.956204E+10 | 0.611264E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.853404E+10 | 0.609518E+10 | 0.243886E+10 | 0.791991E+10 | 0.868051E+10 |
February | 0.981623E+10 | 0.706020E+10 | 0.275603E+10 | 0.100044E+11 | 0.593853E+10 |
March | 0.971455E+10 | 0.545524E+10 | 0.425930E+10 | 0.986362E+10 | 0.590239E+10 |
April | 0.755697E+10 | 0.361455E+10 | 0.394242E+10 | 0.796844E+10 | 0.427805E+10 |
May | 0.693798E+10 | 0.230429E+10 | 0.463369E+10 | 0.745512E+10 | 0.346410E+10 |
June | 0.667121E+10 | 0.194564E+10 | 0.472556E+10 | 0.819000E+10 | 0.230219E+10 |
July | 0.743197E+10 | 0.274535E+10 | 0.468662E+10 | 0.101832E+11 | 0.190451E+10 |
August | 0.883241E+10 | 0.445314E+10 | 0.437927E+10 | 0.117282E+11 | 0.215857E+10 |
September | 0.948020E+10 | 0.580882E+10 | 0.367137E+10 | 0.116475E+11 | 0.298139E+10 |
October | 0.102414E+11 | 0.708180E+10 | 0.315960E+10 | 0.115404E+11 | 0.435254E+10 |
November | 0.903593E+10 | 0.654527E+10 | 0.249067E+10 | 0.929720E+10 | 0.540294E+10 |
December | 0.811539E+10 | 0.586013E+10 | 0.225526E+10 | 0.772751E+10 | 0.738546E+10 |
Annual Sum or Average | 0.102368E+12 | 0.589696E+11 | 0.433987E+11 | 0.113525E+12 | 0.547512E+11 |
Minimum of Months | 0.667121E+10 | 0.194564E+10 | 0.225526E+10 | 0.745512E+10 | 0.190451E+10 |
Maximum of Months | 0.102414E+11 | 0.708180E+10 | 0.472556E+10 | 0.117282E+11 | 0.868051E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.167876E+10 | 0.676552E+09 | 0.100221E+10 | 0.863987E+09 | 0.646017E+10 |
February | 0.258809E+10 | 0.127218E+10 | 0.131591E+10 | 0.198805E+10 | 0.427270E+10 |
March | 0.366700E+10 | 0.134364E+10 | 0.232335E+10 | 0.293086E+10 | 0.399140E+10 |
April | 0.463285E+10 | 0.205257E+10 | 0.258029E+10 | 0.449790E+10 | 0.286776E+10 |
May | 0.592153E+10 | 0.270053E+10 | 0.322099E+10 | 0.629595E+10 | 0.233114E+10 |
June | 0.623457E+10 | 0.286377E+10 | 0.337080E+10 | 0.741123E+10 | 0.155903E+10 |
July | 0.659951E+10 | 0.333483E+10 | 0.326468E+10 | 0.851923E+10 | 0.135646E+10 |
August | 0.560388E+10 | 0.275026E+10 | 0.285361E+10 | 0.703271E+10 | 0.146883E+10 |
September | 0.436255E+10 | 0.220553E+10 | 0.215702E+10 | 0.503102E+10 | 0.199226E+10 |
October | 0.322196E+10 | 0.160082E+10 | 0.162114E+10 | 0.312636E+10 | 0.295828E+10 |
November | 0.220727E+10 | 0.109499E+10 | 0.111227E+10 | 0.173070E+10 | 0.390067E+10 |
December | 0.153314E+10 | 0.647096E+09 | 0.886046E+09 | 0.827775E+09 | 0.547111E+10 |
Annual Sum or Average | 0.482511E+11 | 0.225428E+11 | 0.257083E+11 | 0.502558E+11 | 0.386298E+11 |
Minimum of Months | 0.153314E+10 | 0.647096E+09 | 0.886046E+09 | 0.827775E+09 | 0.135646E+10 |
Maximum of Months | 0.659951E+10 | 0.333483E+10 | 0.337080E+10 | 0.851923E+10 | 0.646017E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.121069E+10 | 0.00 | 0.121069E+10 | 59807850.24 | 0.961691E+10 |
February | 0.154399E+10 | 0.00 | 0.154399E+10 | 0.344225E+09 | 0.631355E+10 |
March | 0.277688E+10 | 0.00 | 0.277688E+10 | 0.112105E+10 | 0.555083E+10 |
April | 0.306410E+10 | 17881386.28 | 0.304622E+10 | 0.180587E+10 | 0.373932E+10 |
May | 0.415802E+10 | 0.246389E+09 | 0.391163E+10 | 0.323046E+10 | 0.293475E+10 |
June | 0.468560E+10 | 0.538570E+09 | 0.414703E+10 | 0.483978E+10 | 0.190622E+10 |
July | 0.442324E+10 | 0.414289E+09 | 0.400895E+10 | 0.538284E+10 | 0.167135E+10 |
August | 0.354436E+10 | 95005459.17 | 0.344936E+10 | 0.393612E+10 | 0.188242E+10 |
September | 0.256885E+10 | 921843.89 | 0.256793E+10 | 0.230570E+10 | 0.265451E+10 |
October | 0.193629E+10 | 0.00 | 0.193629E+10 | 0.105733E+10 | 0.390647E+10 |
November | 0.127385E+10 | 0.00 | 0.127385E+10 | 0.278439E+09 | 0.549377E+10 |
December | 0.101523E+10 | 0.00 | 0.101523E+10 | 29675764.09 | 0.811011E+10 |
Annual Sum or Average | 0.322011E+11 | 0.131306E+10 | 0.308881E+11 | 0.243913E+11 | 0.537802E+11 |
Minimum of Months | 0.101523E+10 | 0.00 | 0.101523E+10 | 29675764.09 | 0.167135E+10 |
Maximum of Months | 0.468560E+10 | 0.538570E+09 | 0.414703E+10 | 0.538284E+10 | 0.961691E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.185337E+10 | 0.849694E+09 | 0.100367E+10 | 0.102978E+10 | 0.591356E+10 |
February | 0.261830E+10 | 0.129992E+10 | 0.131838E+10 | 0.204324E+10 | 0.388924E+10 |
March | 0.389774E+10 | 0.161278E+10 | 0.228496E+10 | 0.327920E+10 | 0.352077E+10 |
April | 0.481271E+10 | 0.238514E+10 | 0.242757E+10 | 0.472681E+10 | 0.244168E+10 |
May | 0.549347E+10 | 0.244425E+10 | 0.304922E+10 | 0.572184E+10 | 0.200782E+10 |
June | 0.688122E+10 | 0.354107E+10 | 0.334015E+10 | 0.817000E+10 | 0.133385E+10 |
July | 0.746276E+10 | 0.421890E+10 | 0.324386E+10 | 0.954117E+10 | 0.114557E+10 |
August | 0.648547E+10 | 0.361351E+10 | 0.287197E+10 | 0.810287E+10 | 0.127838E+10 |
September | 0.443984E+10 | 0.229183E+10 | 0.214801E+10 | 0.507112E+10 | 0.172458E+10 |
October | 0.329153E+10 | 0.167139E+10 | 0.162014E+10 | 0.322172E+10 | 0.250315E+10 |
November | 0.201882E+10 | 0.942522E+09 | 0.107629E+10 | 0.149041E+10 | 0.337574E+10 |
December | 0.153863E+10 | 0.660844E+09 | 0.877783E+09 | 0.815930E+09 | 0.497834E+10 |
Annual Sum or Average | 0.507939E+11 | 0.255318E+11 | 0.252620E+11 | 0.532141E+11 | 0.341127E+11 |
Minimum of Months | 0.153863E+10 | 0.660844E+09 | 0.877783E+09 | 0.815930E+09 | 0.114557E+10 |
Maximum of Months | 0.746276E+10 | 0.421890E+10 | 0.334015E+10 | 0.954117E+10 | 0.591356E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.853404E+10 | 0.609518E+10 | 0.243886E+10 | 0.801449E+10 | 0.832546E+10 |
February | 0.981623E+10 | 0.706020E+10 | 0.275603E+10 | 0.101081E+11 | 0.562316E+10 |
March | 0.971455E+10 | 0.545524E+10 | 0.425930E+10 | 0.997378E+10 | 0.554228E+10 |
April | 0.755697E+10 | 0.361455E+10 | 0.394242E+10 | 0.806982E+10 | 0.396940E+10 |
May | 0.693798E+10 | 0.230429E+10 | 0.463369E+10 | 0.750967E+10 | 0.326218E+10 |
June | 0.667121E+10 | 0.194564E+10 | 0.472556E+10 | 0.819412E+10 | 0.223391E+10 |
July | 0.743197E+10 | 0.274535E+10 | 0.468662E+10 | 0.101623E+11 | 0.187555E+10 |
August | 0.883241E+10 | 0.445314E+10 | 0.437927E+10 | 0.117120E+11 | 0.210850E+10 |
September | 0.948020E+10 | 0.580882E+10 | 0.367137E+10 | 0.116731E+11 | 0.283160E+10 |
October | 0.102414E+11 | 0.708180E+10 | 0.315960E+10 | 0.116578E+11 | 0.399398E+10 |
November | 0.903593E+10 | 0.654527E+10 | 0.249067E+10 | 0.945863E+10 | 0.496852E+10 |
December | 0.811539E+10 | 0.586013E+10 | 0.225526E+10 | 0.783597E+10 | 0.701313E+10 |
Annual Sum or Average | 0.102368E+12 | 0.589696E+11 | 0.433987E+11 | 0.114370E+12 | 0.517477E+11 |
Minimum of Months | 0.667121E+10 | 0.194564E+10 | 0.225526E+10 | 0.750967E+10 | 0.187555E+10 |
Maximum of Months | 0.102414E+11 | 0.708180E+10 | 0.472556E+10 | 0.117120E+11 | 0.832546E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.167876E+10 | 0.676552E+09 | 0.100221E+10 | 0.885594E+09 | 0.624734E+10 |
February | 0.258809E+10 | 0.127218E+10 | 0.131591E+10 | 0.202440E+10 | 0.408813E+10 |
March | 0.366700E+10 | 0.134364E+10 | 0.232335E+10 | 0.298203E+10 | 0.378282E+10 |
April | 0.463285E+10 | 0.205257E+10 | 0.258029E+10 | 0.456123E+10 | 0.268434E+10 |
May | 0.592153E+10 | 0.270053E+10 | 0.322099E+10 | 0.632771E+10 | 0.220837E+10 |
June | 0.623457E+10 | 0.286377E+10 | 0.337080E+10 | 0.741133E+10 | 0.151881E+10 |
July | 0.659951E+10 | 0.333483E+10 | 0.326468E+10 | 0.850492E+10 | 0.133869E+10 |
August | 0.560388E+10 | 0.275026E+10 | 0.285361E+10 | 0.702768E+10 | 0.143684E+10 |
September | 0.436255E+10 | 0.220553E+10 | 0.215702E+10 | 0.505442E+10 | 0.189557E+10 |
October | 0.322196E+10 | 0.160082E+10 | 0.162114E+10 | 0.319454E+10 | 0.273440E+10 |
November | 0.220727E+10 | 0.109499E+10 | 0.111227E+10 | 0.178205E+10 | 0.363481E+10 |
December | 0.153314E+10 | 0.647096E+09 | 0.886046E+09 | 0.847531E+09 | 0.525258E+10 |
Annual Sum or Average | 0.482511E+11 | 0.225428E+11 | 0.257083E+11 | 0.506034E+11 | 0.368227E+11 |
Minimum of Months | 0.153314E+10 | 0.647096E+09 | 0.886046E+09 | 0.847531E+09 | 0.133869E+10 |
Maximum of Months | 0.659951E+10 | 0.333483E+10 | 0.337080E+10 | 0.850492E+10 | 0.624734E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 7.74 | 3952.44 | 452.01 | 0.00 | 452.01 | 0.00 | 0.00 |
February | 77.64 | 2979.08 | 638.21 | 0.00 | 638.21 | 0.00 | 0.00 |
March | 309.68 | 2439.85 | 1036.75 | 0.00 | 1036.75 | 0.00 | 0.00 |
April | 574.15 | 1756.11 | 1182.12 | 6.90 | 1175.22 | 0.00 | 0.00 |
May | 1123.40 | 1266.31 | 1552.40 | 91.99 | 1460.41 | 0.00 | 0.00 |
June | 1829.48 | 792.59 | 1807.68 | 207.78 | 1599.91 | 0.00 | 0.00 |
July | 1988.02 | 653.73 | 1651.42 | 154.67 | 1496.75 | 0.00 | 0.00 |
August | 1438.12 | 758.09 | 1323.29 | 35.47 | 1287.82 | 0.00 | 0.00 |
September | 833.55 | 1178.13 | 991.05 | 0.36 | 990.70 | 0.00 | 0.00 |
October | 289.60 | 1807.00 | 722.92 | 0.00 | 722.92 | 0.00 | 0.00 |
November | 56.70 | 2615.37 | 491.44 | 0.00 | 491.44 | 0.00 | 0.00 |
December | 2.29 | 3538.58 | 379.04 | 0.00 | 379.04 | 0.00 | 0.00 |
Annual Sum or Average | 714.83 | 1974.18 | 1021.07 | 41.64 | 979.44 | 0.00 | 0.00 |
Minimum of Months | 2.29 | 653.73 | 379.04 | 0.00 | 379.04 | 0.00 | 0.00 |
Maximum of Months | 1988.02 | 3952.44 | 1807.68 | 207.78 | 1599.91 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 355.64 | 2406.33 | 691.97 | 317.24 | 374.73 | 0.00 | 0.00 |
February | 789.45 | 1799.96 | 1082.30 | 537.34 | 544.97 | 0.00 | 0.00 |
March | 1162.16 | 1497.01 | 1455.26 | 602.14 | 853.11 | 0.00 | 0.00 |
April | 1777.28 | 1081.75 | 1856.76 | 920.20 | 936.56 | 0.00 | 0.00 |
May | 2116.85 | 841.04 | 2051.04 | 912.58 | 1138.45 | 0.00 | 0.00 |
June | 3166.38 | 533.47 | 2654.80 | 1366.16 | 1288.64 | 0.00 | 0.00 |
July | 3586.99 | 424.00 | 2786.29 | 1575.16 | 1211.13 | 0.00 | 0.00 |
August | 3044.66 | 476.28 | 2421.41 | 1349.13 | 1072.27 | 0.00 | 0.00 |
September | 1945.43 | 731.22 | 1712.91 | 884.20 | 828.71 | 0.00 | 0.00 |
October | 1143.13 | 1105.02 | 1228.92 | 624.03 | 604.89 | 0.00 | 0.00 |
November | 516.89 | 1548.79 | 778.87 | 363.63 | 415.24 | 0.00 | 0.00 |
December | 271.14 | 2114.55 | 574.46 | 246.73 | 327.73 | 0.00 | 0.00 |
Annual Sum or Average | 1661.32 | 1211.09 | 1610.67 | 809.61 | 801.06 | 0.00 | 0.00 |
Minimum of Months | 271.14 | 424.00 | 574.46 | 246.73 | 327.73 | 0.00 | 0.00 |
Maximum of Months | 3586.99 | 2406.33 | 2786.29 | 1575.16 | 1288.64 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2956.75 | 3321.92 | 3186.14 | 2275.60 | 910.54 | 0.00 | 0.00 |
February | 4142.28 | 2537.35 | 4057.51 | 2918.31 | 1139.20 | 0.00 | 0.00 |
March | 3685.66 | 2289.98 | 3626.89 | 2036.69 | 1590.20 | 0.00 | 0.00 |
April | 3072.05 | 1730.39 | 2915.42 | 1394.46 | 1520.96 | 0.00 | 0.00 |
May | 2788.00 | 1340.46 | 2590.28 | 860.30 | 1729.98 | 0.00 | 0.00 |
June | 3166.22 | 908.70 | 2573.71 | 750.61 | 1823.10 | 0.00 | 0.00 |
July | 3808.82 | 717.28 | 2774.71 | 1024.96 | 1749.75 | 0.00 | 0.00 |
August | 4391.62 | 814.14 | 3297.56 | 1662.56 | 1635.00 | 0.00 | 0.00 |
September | 4521.85 | 1173.61 | 3657.38 | 2240.99 | 1416.39 | 0.00 | 0.00 |
October | 4325.84 | 1678.60 | 3823.59 | 2643.96 | 1179.63 | 0.00 | 0.00 |
November | 3580.96 | 2177.87 | 3485.98 | 2525.10 | 960.88 | 0.00 | 0.00 |
December | 2856.90 | 2910.37 | 3029.84 | 2187.85 | 841.99 | 0.00 | 0.00 |
Annual Sum or Average | 3603.94 | 1797.31 | 3245.98 | 1869.85 | 1376.13 | 0.00 | 0.00 |
Minimum of Months | 2788.00 | 717.28 | 2573.71 | 750.61 | 841.99 | 0.00 | 0.00 |
Maximum of Months | 4521.85 | 3321.92 | 4057.51 | 2918.31 | 1823.10 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 305.76 | 2592.58 | 626.78 | 252.60 | 374.18 | 0.00 | 0.00 |
February | 773.74 | 1975.57 | 1069.82 | 525.87 | 543.95 | 0.00 | 0.00 |
March | 1027.98 | 1712.48 | 1369.10 | 501.66 | 867.44 | 0.00 | 0.00 |
April | 1668.24 | 1298.98 | 1787.37 | 791.89 | 995.48 | 0.00 | 0.00 |
May | 2324.92 | 948.29 | 2210.85 | 1008.27 | 1202.59 | 0.00 | 0.00 |
June | 2834.34 | 651.73 | 2405.32 | 1104.86 | 1300.47 | 0.00 | 0.00 |
July | 3152.65 | 548.68 | 2463.99 | 1245.09 | 1218.90 | 0.00 | 0.00 |
August | 2584.80 | 620.30 | 2092.26 | 1026.84 | 1065.42 | 0.00 | 0.00 |
September | 1919.75 | 839.32 | 1683.09 | 850.90 | 832.19 | 0.00 | 0.00 |
October | 1117.64 | 1270.05 | 1202.95 | 597.68 | 605.27 | 0.00 | 0.00 |
November | 618.83 | 1777.14 | 851.57 | 422.45 | 429.12 | 0.00 | 0.00 |
December | 271.51 | 2408.91 | 572.41 | 241.60 | 330.81 | 0.00 | 0.00 |
Annual Sum or Average | 1554.09 | 1384.85 | 1530.04 | 714.83 | 815.21 | 0.00 | 0.00 |
Minimum of Months | 271.51 | 548.68 | 572.41 | 241.60 | 330.81 | 0.00 | 0.00 |
Maximum of Months | 3152.65 | 2592.58 | 2463.99 | 1245.09 | 1300.47 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 16.43 | 3710.44 | 452.02 | 0.00 | 452.02 | 0.00 | 0.00 |
February | 120.82 | 2735.38 | 638.23 | 0.00 | 638.23 | 0.00 | 0.00 |
March | 381.39 | 2206.96 | 1036.77 | 0.00 | 1036.77 | 0.00 | 0.00 |
April | 643.56 | 1571.62 | 1182.14 | 6.90 | 1175.24 | 0.00 | 0.00 |
May | 1168.27 | 1173.16 | 1552.43 | 91.99 | 1460.44 | 0.00 | 0.00 |
June | 1852.44 | 760.39 | 1807.72 | 207.78 | 1599.93 | 0.00 | 0.00 |
July | 2009.22 | 634.97 | 1651.45 | 154.68 | 1496.77 | 0.00 | 0.00 |
August | 1463.00 | 726.28 | 1323.31 | 35.47 | 1287.84 | 0.00 | 0.00 |
September | 863.01 | 1096.76 | 991.07 | 0.36 | 990.71 | 0.00 | 0.00 |
October | 343.15 | 1615.64 | 722.93 | 0.00 | 722.93 | 0.00 | 0.00 |
November | 85.96 | 2301.91 | 491.45 | 0.00 | 491.45 | 0.00 | 0.00 |
December | 8.70 | 3163.53 | 379.05 | 0.00 | 379.05 | 0.00 | 0.00 |
Annual Sum or Average | 750.21 | 1804.58 | 1021.09 | 41.64 | 979.45 | 0.00 | 0.00 |
Minimum of Months | 8.70 | 634.97 | 379.05 | 0.00 | 379.05 | 0.00 | 0.00 |
Maximum of Months | 2009.22 | 3710.44 | 1807.72 | 207.78 | 1599.93 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 373.35 | 2282.20 | 691.97 | 317.24 | 374.73 | 0.00 | 0.00 |
February | 819.40 | 1685.01 | 1082.30 | 537.34 | 544.96 | 0.00 | 0.00 |
March | 1193.36 | 1395.63 | 1455.25 | 602.14 | 853.11 | 0.00 | 0.00 |
April | 1793.65 | 1012.40 | 1856.76 | 920.19 | 936.56 | 0.00 | 0.00 |
May | 2122.39 | 792.72 | 2051.03 | 912.58 | 1138.45 | 0.00 | 0.00 |
June | 3153.61 | 524.85 | 2654.79 | 1366.15 | 1288.64 | 0.00 | 0.00 |
July | 3570.06 | 430.82 | 2786.28 | 1575.16 | 1211.12 | 0.00 | 0.00 |
August | 3029.26 | 485.67 | 2421.40 | 1349.13 | 1072.27 | 0.00 | 0.00 |
September | 1945.88 | 698.33 | 1712.90 | 884.19 | 828.71 | 0.00 | 0.00 |
October | 1165.67 | 1021.63 | 1228.92 | 624.03 | 604.89 | 0.00 | 0.00 |
November | 546.03 | 1410.87 | 778.86 | 363.63 | 415.24 | 0.00 | 0.00 |
December | 293.93 | 1942.06 | 574.46 | 246.73 | 327.73 | 0.00 | 0.00 |
Annual Sum or Average | 1672.07 | 1138.21 | 1610.66 | 809.61 | 801.05 | 0.00 | 0.00 |
Minimum of Months | 293.93 | 430.82 | 574.46 | 246.73 | 327.73 | 0.00 | 0.00 |
Maximum of Months | 3570.06 | 2282.20 | 2786.28 | 1575.16 | 1288.64 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2956.95 | 3240.93 | 3186.24 | 2275.68 | 910.56 | 0.00 | 0.00 |
February | 4135.42 | 2454.75 | 4057.63 | 2918.40 | 1139.23 | 0.00 | 0.00 |
March | 3682.65 | 2203.70 | 3627.00 | 2036.75 | 1590.24 | 0.00 | 0.00 |
April | 3074.24 | 1650.48 | 2915.50 | 1394.50 | 1521.00 | 0.00 | 0.00 |
May | 2783.42 | 1293.35 | 2590.34 | 860.32 | 1730.02 | 0.00 | 0.00 |
June | 3159.72 | 888.19 | 2573.77 | 750.63 | 1823.13 | 0.00 | 0.00 |
July | 3801.96 | 711.06 | 2774.78 | 1025.00 | 1749.79 | 0.00 | 0.00 |
August | 4378.80 | 805.92 | 3297.64 | 1662.61 | 1635.03 | 0.00 | 0.00 |
September | 4493.63 | 1150.23 | 3657.48 | 2241.06 | 1416.43 | 0.00 | 0.00 |
October | 4308.71 | 1625.05 | 3823.70 | 2644.04 | 1179.66 | 0.00 | 0.00 |
November | 3586.88 | 2084.47 | 3486.08 | 2525.18 | 960.91 | 0.00 | 0.00 |
December | 2885.12 | 2757.42 | 3029.94 | 2187.92 | 842.02 | 0.00 | 0.00 |
Annual Sum or Average | 3599.87 | 1736.15 | 3246.08 | 1869.91 | 1376.16 | 0.00 | 0.00 |
Minimum of Months | 2783.42 | 711.06 | 2573.77 | 750.63 | 842.02 | 0.00 | 0.00 |
Maximum of Months | 4493.63 | 3240.93 | 4057.63 | 2918.40 | 1823.13 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 322.58 | 2411.95 | 626.78 | 252.60 | 374.18 | 0.00 | 0.00 |
February | 821.78 | 1766.16 | 1069.81 | 525.87 | 543.95 | 0.00 | 0.00 |
March | 1094.26 | 1490.22 | 1369.10 | 501.66 | 867.44 | 0.00 | 0.00 |
April | 1735.30 | 1106.39 | 1787.37 | 791.89 | 995.48 | 0.00 | 0.00 |
May | 2350.64 | 870.35 | 2210.84 | 1008.26 | 1202.58 | 0.00 | 0.00 |
June | 2859.27 | 601.48 | 2405.31 | 1104.85 | 1300.46 | 0.00 | 0.00 |
July | 3180.72 | 506.45 | 2463.98 | 1245.08 | 1218.89 | 0.00 | 0.00 |
August | 2625.71 | 548.40 | 2092.25 | 1026.83 | 1065.42 | 0.00 | 0.00 |
September | 1940.98 | 768.62 | 1683.08 | 850.90 | 832.18 | 0.00 | 0.00 |
October | 1167.25 | 1104.50 | 1202.94 | 597.68 | 605.26 | 0.00 | 0.00 |
November | 667.71 | 1504.89 | 851.57 | 422.45 | 429.12 | 0.00 | 0.00 |
December | 309.06 | 2042.68 | 572.41 | 241.60 | 330.81 | 0.00 | 0.00 |
Annual Sum or Average | 1593.60 | 1224.94 | 1530.03 | 714.83 | 815.21 | 0.00 | 0.00 |
Minimum of Months | 309.06 | 506.45 | 572.41 | 241.60 | 330.81 | 0.00 | 0.00 |
Maximum of Months | 3180.72 | 2411.95 | 2463.98 | 1245.08 | 1300.46 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 22.33 | 3590.54 | 452.02 | 0.00 | 452.02 | 0.00 | 0.00 |
February | 142.29 | 2609.77 | 638.23 | 0.00 | 638.23 | 0.00 | 0.00 |
March | 418.55 | 2072.44 | 1036.77 | 0.00 | 1036.77 | 0.00 | 0.00 |
April | 696.71 | 1442.64 | 1182.14 | 6.90 | 1175.24 | 0.00 | 0.00 |
May | 1206.12 | 1095.71 | 1552.43 | 91.99 | 1460.44 | 0.00 | 0.00 |
June | 1867.20 | 735.42 | 1807.72 | 207.78 | 1599.93 | 0.00 | 0.00 |
July | 2009.72 | 624.01 | 1651.45 | 154.68 | 1496.77 | 0.00 | 0.00 |
August | 1469.58 | 702.82 | 1323.31 | 35.47 | 1287.84 | 0.00 | 0.00 |
September | 889.55 | 1024.12 | 991.07 | 0.36 | 990.71 | 0.00 | 0.00 |
October | 394.76 | 1458.51 | 722.93 | 0.00 | 722.93 | 0.00 | 0.00 |
November | 107.42 | 2119.51 | 491.45 | 0.00 | 491.45 | 0.00 | 0.00 |
December | 11.08 | 3027.97 | 379.05 | 0.00 | 379.05 | 0.00 | 0.00 |
Annual Sum or Average | 773.44 | 1705.36 | 1021.09 | 41.64 | 979.45 | 0.00 | 0.00 |
Minimum of Months | 11.08 | 624.01 | 379.05 | 0.00 | 379.05 | 0.00 | 0.00 |
Maximum of Months | 2009.72 | 3590.54 | 1807.72 | 207.78 | 1599.93 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 384.48 | 2207.87 | 691.97 | 317.24 | 374.73 | 0.00 | 0.00 |
February | 844.59 | 1607.66 | 1082.30 | 537.34 | 544.96 | 0.00 | 0.00 |
March | 1224.31 | 1314.50 | 1455.25 | 602.14 | 853.11 | 0.00 | 0.00 |
April | 1823.62 | 942.01 | 1856.76 | 920.19 | 936.56 | 0.00 | 0.00 |
May | 2136.29 | 749.63 | 2051.03 | 912.58 | 1138.45 | 0.00 | 0.00 |
June | 3152.01 | 514.60 | 2654.79 | 1366.15 | 1288.64 | 0.00 | 0.00 |
July | 3562.26 | 427.71 | 2786.28 | 1575.16 | 1211.12 | 0.00 | 0.00 |
August | 3025.26 | 477.29 | 2421.40 | 1349.13 | 1072.27 | 0.00 | 0.00 |
September | 1956.45 | 665.35 | 1712.90 | 884.19 | 828.71 | 0.00 | 0.00 |
October | 1202.85 | 934.57 | 1228.92 | 624.03 | 604.89 | 0.00 | 0.00 |
November | 575.00 | 1302.37 | 778.86 | 363.63 | 415.24 | 0.00 | 0.00 |
December | 304.63 | 1858.70 | 574.46 | 246.73 | 327.73 | 0.00 | 0.00 |
Annual Sum or Average | 1687.41 | 1081.71 | 1610.66 | 809.61 | 801.05 | 0.00 | 0.00 |
Minimum of Months | 304.63 | 427.71 | 574.46 | 246.73 | 327.73 | 0.00 | 0.00 |
Maximum of Months | 3562.26 | 2207.87 | 2786.28 | 1575.16 | 1288.64 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2992.27 | 3108.37 | 3186.24 | 2275.68 | 910.56 | 0.00 | 0.00 |
February | 4178.29 | 2324.39 | 4057.63 | 2918.40 | 1139.23 | 0.00 | 0.00 |
March | 3723.78 | 2069.25 | 3627.00 | 2036.75 | 1590.24 | 0.00 | 0.00 |
April | 3113.36 | 1531.40 | 2915.50 | 1394.50 | 1521.00 | 0.00 | 0.00 |
May | 2803.79 | 1217.96 | 2590.34 | 860.32 | 1730.02 | 0.00 | 0.00 |
June | 3161.31 | 861.85 | 2573.77 | 750.63 | 1823.13 | 0.00 | 0.00 |
July | 3794.18 | 700.25 | 2774.78 | 1025.00 | 1749.79 | 0.00 | 0.00 |
August | 4372.77 | 787.22 | 3297.64 | 1662.61 | 1635.03 | 0.00 | 0.00 |
September | 4503.49 | 1092.44 | 3657.48 | 2241.06 | 1416.43 | 0.00 | 0.00 |
October | 4352.53 | 1491.18 | 3823.70 | 2644.04 | 1179.66 | 0.00 | 0.00 |
November | 3649.16 | 1916.87 | 3486.08 | 2525.18 | 960.91 | 0.00 | 0.00 |
December | 2925.62 | 2618.40 | 3029.94 | 2187.92 | 842.02 | 0.00 | 0.00 |
Annual Sum or Average | 3626.64 | 1640.91 | 3246.08 | 1869.91 | 1376.16 | 0.00 | 0.00 |
Minimum of Months | 2803.79 | 700.25 | 2573.77 | 750.63 | 842.02 | 0.00 | 0.00 |
Maximum of Months | 4503.49 | 3108.37 | 4057.63 | 2918.40 | 1823.13 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 330.64 | 2332.49 | 626.78 | 252.60 | 374.18 | 0.00 | 0.00 |
February | 836.81 | 1689.87 | 1069.81 | 525.87 | 543.95 | 0.00 | 0.00 |
March | 1113.36 | 1412.34 | 1369.10 | 501.66 | 867.44 | 0.00 | 0.00 |
April | 1759.74 | 1035.62 | 1787.37 | 791.89 | 995.48 | 0.00 | 0.00 |
May | 2362.50 | 824.51 | 2210.84 | 1008.26 | 1202.58 | 0.00 | 0.00 |
June | 2859.31 | 585.96 | 2405.31 | 1104.85 | 1300.46 | 0.00 | 0.00 |
July | 3175.37 | 499.81 | 2463.98 | 1245.08 | 1218.89 | 0.00 | 0.00 |
August | 2623.83 | 536.45 | 2092.25 | 1026.83 | 1065.42 | 0.00 | 0.00 |
September | 1950.01 | 731.32 | 1683.08 | 850.90 | 832.18 | 0.00 | 0.00 |
October | 1192.70 | 1020.91 | 1202.94 | 597.68 | 605.26 | 0.00 | 0.00 |
November | 687.52 | 1402.32 | 851.57 | 422.45 | 429.12 | 0.00 | 0.00 |
December | 316.43 | 1961.09 | 572.41 | 241.60 | 330.81 | 0.00 | 0.00 |
Annual Sum or Average | 1604.62 | 1167.64 | 1530.03 | 714.83 | 815.21 | 0.00 | 0.00 |
Minimum of Months | 316.43 | 499.81 | 572.41 | 241.60 | 330.81 | 0.00 | 0.00 |
Maximum of Months | 3175.37 | 2332.49 | 2463.98 | 1245.08 | 1300.46 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 20720271.77 | 0.105862E+11 | 0.121067E+10 | 0.00 | 0.121067E+10 | 0.00 | 0.00 |
February | 0.187830E+09 | 0.720700E+10 | 0.154397E+10 | 0.00 | 0.154397E+10 | 0.00 | 0.00 |
March | 0.829457E+09 | 0.653490E+10 | 0.277683E+10 | 0.00 | 0.277683E+10 | 0.00 | 0.00 |
April | 0.148821E+10 | 0.455183E+10 | 0.306404E+10 | 17880853.02 | 0.304616E+10 | 0.00 | 0.00 |
May | 0.300890E+10 | 0.339168E+10 | 0.415795E+10 | 0.246381E+09 | 0.391156E+10 | 0.00 | 0.00 |
June | 0.474201E+10 | 0.205439E+10 | 0.468551E+10 | 0.538554E+09 | 0.414696E+10 | 0.00 | 0.00 |
July | 0.532472E+10 | 0.175094E+10 | 0.442316E+10 | 0.414277E+09 | 0.400889E+10 | 0.00 | 0.00 |
August | 0.385186E+10 | 0.203048E+10 | 0.354431E+10 | 95002625.92 | 0.344930E+10 | 0.00 | 0.00 |
September | 0.216056E+10 | 0.305372E+10 | 0.256881E+10 | 921816.40 | 0.256789E+10 | 0.00 | 0.00 |
October | 0.775664E+09 | 0.483986E+10 | 0.193626E+10 | 0.00 | 0.193626E+10 | 0.00 | 0.00 |
November | 0.146961E+09 | 0.677903E+10 | 0.127382E+10 | 0.00 | 0.127382E+10 | 0.00 | 0.00 |
December | 6125005.20 | 0.947773E+10 | 0.101522E+10 | 0.00 | 0.101522E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.225430E+11 | 0.622578E+11 | 0.322005E+11 | 0.131302E+10 | 0.308875E+11 | 0.00 | 0.00 |
Minimum of Months | 6125005.20 | 0.175094E+10 | 0.101522E+10 | 0.00 | 0.101522E+10 | 0.00 | 0.00 |
Maximum of Months | 0.532472E+10 | 0.105862E+11 | 0.468551E+10 | 0.538554E+09 | 0.414696E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.952542E+09 | 0.644511E+10 | 0.185337E+10 | 0.849697E+09 | 0.100368E+10 | 0.00 | 0.00 |
February | 0.190985E+10 | 0.435446E+10 | 0.261831E+10 | 0.129993E+10 | 0.131838E+10 | 0.00 | 0.00 |
March | 0.311274E+10 | 0.400959E+10 | 0.389776E+10 | 0.161278E+10 | 0.228497E+10 | 0.00 | 0.00 |
April | 0.460672E+10 | 0.280391E+10 | 0.481273E+10 | 0.238515E+10 | 0.242758E+10 | 0.00 | 0.00 |
May | 0.566978E+10 | 0.225263E+10 | 0.549350E+10 | 0.244426E+10 | 0.304924E+10 | 0.00 | 0.00 |
June | 0.820726E+10 | 0.138277E+10 | 0.688124E+10 | 0.354108E+10 | 0.334016E+10 | 0.00 | 0.00 |
July | 0.960740E+10 | 0.113564E+10 | 0.746279E+10 | 0.421892E+10 | 0.324388E+10 | 0.00 | 0.00 |
August | 0.815480E+10 | 0.127567E+10 | 0.648550E+10 | 0.361352E+10 | 0.287198E+10 | 0.00 | 0.00 |
September | 0.504256E+10 | 0.189532E+10 | 0.443986E+10 | 0.229184E+10 | 0.214802E+10 | 0.00 | 0.00 |
October | 0.306177E+10 | 0.295968E+10 | 0.329155E+10 | 0.167140E+10 | 0.162015E+10 | 0.00 | 0.00 |
November | 0.133978E+10 | 0.401447E+10 | 0.201882E+10 | 0.942526E+09 | 0.107630E+10 | 0.00 | 0.00 |
December | 0.726230E+09 | 0.566362E+10 | 0.153863E+10 | 0.660846E+09 | 0.877787E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.523914E+11 | 0.381929E+11 | 0.507941E+11 | 0.255320E+11 | 0.252621E+11 | 0.00 | 0.00 |
Minimum of Months | 0.726230E+09 | 0.113564E+10 | 0.153863E+10 | 0.660846E+09 | 0.877787E+09 | 0.00 | 0.00 |
Maximum of Months | 0.960740E+10 | 0.644511E+10 | 0.746279E+10 | 0.421892E+10 | 0.334016E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.791936E+10 | 0.889744E+10 | 0.853377E+10 | 0.609498E+10 | 0.243879E+10 | 0.00 | 0.00 |
February | 0.100210E+11 | 0.613835E+10 | 0.981593E+10 | 0.705997E+10 | 0.275596E+10 | 0.00 | 0.00 |
March | 0.987167E+10 | 0.613349E+10 | 0.971426E+10 | 0.545506E+10 | 0.425920E+10 | 0.00 | 0.00 |
April | 0.796275E+10 | 0.448517E+10 | 0.755676E+10 | 0.361443E+10 | 0.394233E+10 | 0.00 | 0.00 |
May | 0.746737E+10 | 0.359028E+10 | 0.693780E+10 | 0.230422E+10 | 0.463359E+10 | 0.00 | 0.00 |
June | 0.820686E+10 | 0.235535E+10 | 0.667105E+10 | 0.194558E+10 | 0.472547E+10 | 0.00 | 0.00 |
July | 0.102015E+11 | 0.192117E+10 | 0.743179E+10 | 0.274526E+10 | 0.468653E+10 | 0.00 | 0.00 |
August | 0.117625E+11 | 0.218059E+10 | 0.883217E+10 | 0.445300E+10 | 0.437918E+10 | 0.00 | 0.00 |
September | 0.117206E+11 | 0.304200E+10 | 0.947992E+10 | 0.580863E+10 | 0.367129E+10 | 0.00 | 0.00 |
October | 0.115863E+11 | 0.449597E+10 | 0.102411E+11 | 0.708157E+10 | 0.315953E+10 | 0.00 | 0.00 |
November | 0.928185E+10 | 0.564505E+10 | 0.903565E+10 | 0.654505E+10 | 0.249060E+10 | 0.00 | 0.00 |
December | 0.765192E+10 | 0.779512E+10 | 0.811513E+10 | 0.585994E+10 | 0.225520E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.113654E+12 | 0.566800E+11 | 0.102365E+12 | 0.589677E+11 | 0.433977E+11 | 0.00 | 0.00 |
Minimum of Months | 0.746737E+10 | 0.192117E+10 | 0.667105E+10 | 0.194558E+10 | 0.225520E+10 | 0.00 | 0.00 |
Maximum of Months | 0.117625E+11 | 0.889744E+10 | 0.102411E+11 | 0.708157E+10 | 0.472547E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.818960E+09 | 0.694398E+10 | 0.167876E+10 | 0.676554E+09 | 0.100221E+10 | 0.00 | 0.00 |
February | 0.187182E+10 | 0.477929E+10 | 0.258810E+10 | 0.127218E+10 | 0.131592E+10 | 0.00 | 0.00 |
March | 0.275333E+10 | 0.458672E+10 | 0.366701E+10 | 0.134365E+10 | 0.232336E+10 | 0.00 | 0.00 |
April | 0.432408E+10 | 0.336695E+10 | 0.463287E+10 | 0.205258E+10 | 0.258030E+10 | 0.00 | 0.00 |
May | 0.622706E+10 | 0.253991E+10 | 0.592155E+10 | 0.270054E+10 | 0.322101E+10 | 0.00 | 0.00 |
June | 0.734661E+10 | 0.168928E+10 | 0.623460E+10 | 0.286378E+10 | 0.337081E+10 | 0.00 | 0.00 |
July | 0.844405E+10 | 0.146958E+10 | 0.659954E+10 | 0.333485E+10 | 0.326470E+10 | 0.00 | 0.00 |
August | 0.692313E+10 | 0.166141E+10 | 0.560390E+10 | 0.275028E+10 | 0.285362E+10 | 0.00 | 0.00 |
September | 0.497599E+10 | 0.217551E+10 | 0.436257E+10 | 0.220554E+10 | 0.215703E+10 | 0.00 | 0.00 |
October | 0.299350E+10 | 0.340170E+10 | 0.322197E+10 | 0.160082E+10 | 0.162115E+10 | 0.00 | 0.00 |
November | 0.160401E+10 | 0.460636E+10 | 0.220727E+10 | 0.109500E+10 | 0.111228E+10 | 0.00 | 0.00 |
December | 0.727217E+09 | 0.645203E+10 | 0.153315E+10 | 0.647098E+09 | 0.886049E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.490098E+11 | 0.436727E+11 | 0.482513E+11 | 0.225429E+11 | 0.257084E+11 | 0.00 | 0.00 |
Minimum of Months | 0.727217E+09 | 0.146958E+10 | 0.153315E+10 | 0.647098E+09 | 0.886049E+09 | 0.00 | 0.00 |
Maximum of Months | 0.844405E+10 | 0.694398E+10 | 0.659954E+10 | 0.333485E+10 | 0.337081E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 44006795.58 | 0.993806E+10 | 0.121069E+10 | 0.00 | 0.121069E+10 | 0.00 | 0.00 |
February | 0.292293E+09 | 0.661744E+10 | 0.154399E+10 | 0.00 | 0.154399E+10 | 0.00 | 0.00 |
March | 0.102152E+10 | 0.591112E+10 | 0.277688E+10 | 0.00 | 0.277688E+10 | 0.00 | 0.00 |
April | 0.166810E+10 | 0.407364E+10 | 0.306410E+10 | 17881386.28 | 0.304622E+10 | 0.00 | 0.00 |
May | 0.312909E+10 | 0.314220E+10 | 0.415802E+10 | 0.246389E+09 | 0.391163E+10 | 0.00 | 0.00 |
June | 0.480153E+10 | 0.197094E+10 | 0.468560E+10 | 0.538570E+09 | 0.414703E+10 | 0.00 | 0.00 |
July | 0.538150E+10 | 0.170071E+10 | 0.442324E+10 | 0.414289E+09 | 0.400895E+10 | 0.00 | 0.00 |
August | 0.391850E+10 | 0.194526E+10 | 0.354436E+10 | 95005459.17 | 0.344936E+10 | 0.00 | 0.00 |
September | 0.223693E+10 | 0.284281E+10 | 0.256885E+10 | 921843.89 | 0.256793E+10 | 0.00 | 0.00 |
October | 0.919081E+09 | 0.432733E+10 | 0.193629E+10 | 0.00 | 0.193629E+10 | 0.00 | 0.00 |
November | 0.222805E+09 | 0.596655E+10 | 0.127385E+10 | 0.00 | 0.127385E+10 | 0.00 | 0.00 |
December | 23303430.79 | 0.847319E+10 | 0.101523E+10 | 0.00 | 0.101523E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.236587E+11 | 0.569092E+11 | 0.322011E+11 | 0.131306E+10 | 0.308881E+11 | 0.00 | 0.00 |
Minimum of Months | 23303430.79 | 0.170071E+10 | 0.101523E+10 | 0.00 | 0.101523E+10 | 0.00 | 0.00 |
Maximum of Months | 0.538150E+10 | 0.993806E+10 | 0.468560E+10 | 0.538570E+09 | 0.414703E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.999969E+09 | 0.611264E+10 | 0.185337E+10 | 0.849694E+09 | 0.100367E+10 | 0.00 | 0.00 |
February | 0.198228E+10 | 0.407638E+10 | 0.261830E+10 | 0.129992E+10 | 0.131838E+10 | 0.00 | 0.00 |
March | 0.319630E+10 | 0.373806E+10 | 0.389774E+10 | 0.161278E+10 | 0.228496E+10 | 0.00 | 0.00 |
April | 0.464914E+10 | 0.262414E+10 | 0.481271E+10 | 0.238514E+10 | 0.242757E+10 | 0.00 | 0.00 |
May | 0.568462E+10 | 0.212322E+10 | 0.549347E+10 | 0.244425E+10 | 0.304922E+10 | 0.00 | 0.00 |
June | 0.817417E+10 | 0.136040E+10 | 0.688122E+10 | 0.354107E+10 | 0.334015E+10 | 0.00 | 0.00 |
July | 0.956204E+10 | 0.115392E+10 | 0.746276E+10 | 0.421890E+10 | 0.324386E+10 | 0.00 | 0.00 |
August | 0.811357E+10 | 0.130083E+10 | 0.648547E+10 | 0.361351E+10 | 0.287197E+10 | 0.00 | 0.00 |
September | 0.504372E+10 | 0.181006E+10 | 0.443984E+10 | 0.229183E+10 | 0.214801E+10 | 0.00 | 0.00 |
October | 0.312213E+10 | 0.273634E+10 | 0.329153E+10 | 0.167139E+10 | 0.162014E+10 | 0.00 | 0.00 |
November | 0.141532E+10 | 0.365697E+10 | 0.201882E+10 | 0.942522E+09 | 0.107629E+10 | 0.00 | 0.00 |
December | 0.787250E+09 | 0.520162E+10 | 0.153863E+10 | 0.660844E+09 | 0.877783E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.527305E+11 | 0.358946E+11 | 0.507939E+11 | 0.255318E+11 | 0.252620E+11 | 0.00 | 0.00 |
Minimum of Months | 0.787250E+09 | 0.115392E+10 | 0.153863E+10 | 0.660844E+09 | 0.877783E+09 | 0.00 | 0.00 |
Maximum of Months | 0.956204E+10 | 0.611264E+10 | 0.746276E+10 | 0.421890E+10 | 0.334015E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.791991E+10 | 0.868051E+10 | 0.853404E+10 | 0.609518E+10 | 0.243886E+10 | 0.00 | 0.00 |
February | 0.100044E+11 | 0.593853E+10 | 0.981623E+10 | 0.706020E+10 | 0.275603E+10 | 0.00 | 0.00 |
March | 0.986362E+10 | 0.590239E+10 | 0.971455E+10 | 0.545524E+10 | 0.425930E+10 | 0.00 | 0.00 |
April | 0.796844E+10 | 0.427805E+10 | 0.755697E+10 | 0.361455E+10 | 0.394242E+10 | 0.00 | 0.00 |
May | 0.745512E+10 | 0.346410E+10 | 0.693798E+10 | 0.230429E+10 | 0.463369E+10 | 0.00 | 0.00 |
June | 0.819000E+10 | 0.230219E+10 | 0.667121E+10 | 0.194564E+10 | 0.472556E+10 | 0.00 | 0.00 |
July | 0.101832E+11 | 0.190451E+10 | 0.743197E+10 | 0.274535E+10 | 0.468662E+10 | 0.00 | 0.00 |
August | 0.117282E+11 | 0.215857E+10 | 0.883241E+10 | 0.445314E+10 | 0.437927E+10 | 0.00 | 0.00 |
September | 0.116475E+11 | 0.298139E+10 | 0.948020E+10 | 0.580882E+10 | 0.367137E+10 | 0.00 | 0.00 |
October | 0.115404E+11 | 0.435254E+10 | 0.102414E+11 | 0.708180E+10 | 0.315960E+10 | 0.00 | 0.00 |
November | 0.929720E+10 | 0.540294E+10 | 0.903593E+10 | 0.654527E+10 | 0.249067E+10 | 0.00 | 0.00 |
December | 0.772751E+10 | 0.738546E+10 | 0.811539E+10 | 0.586013E+10 | 0.225526E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.113525E+12 | 0.547512E+11 | 0.102368E+12 | 0.589696E+11 | 0.433987E+11 | 0.00 | 0.00 |
Minimum of Months | 0.745512E+10 | 0.190451E+10 | 0.667121E+10 | 0.194564E+10 | 0.225526E+10 | 0.00 | 0.00 |
Maximum of Months | 0.117282E+11 | 0.868051E+10 | 0.102414E+11 | 0.708180E+10 | 0.472556E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.863987E+09 | 0.646017E+10 | 0.167876E+10 | 0.676552E+09 | 0.100221E+10 | 0.00 | 0.00 |
February | 0.198805E+10 | 0.427270E+10 | 0.258809E+10 | 0.127218E+10 | 0.131591E+10 | 0.00 | 0.00 |
March | 0.293086E+10 | 0.399140E+10 | 0.366700E+10 | 0.134364E+10 | 0.232335E+10 | 0.00 | 0.00 |
April | 0.449790E+10 | 0.286776E+10 | 0.463285E+10 | 0.205257E+10 | 0.258029E+10 | 0.00 | 0.00 |
May | 0.629595E+10 | 0.233114E+10 | 0.592153E+10 | 0.270053E+10 | 0.322099E+10 | 0.00 | 0.00 |
June | 0.741123E+10 | 0.155903E+10 | 0.623457E+10 | 0.286377E+10 | 0.337080E+10 | 0.00 | 0.00 |
July | 0.851923E+10 | 0.135646E+10 | 0.659951E+10 | 0.333483E+10 | 0.326468E+10 | 0.00 | 0.00 |
August | 0.703271E+10 | 0.146883E+10 | 0.560388E+10 | 0.275026E+10 | 0.285361E+10 | 0.00 | 0.00 |
September | 0.503102E+10 | 0.199226E+10 | 0.436255E+10 | 0.220553E+10 | 0.215702E+10 | 0.00 | 0.00 |
October | 0.312636E+10 | 0.295828E+10 | 0.322196E+10 | 0.160082E+10 | 0.162114E+10 | 0.00 | 0.00 |
November | 0.173070E+10 | 0.390067E+10 | 0.220727E+10 | 0.109499E+10 | 0.111227E+10 | 0.00 | 0.00 |
December | 0.827775E+09 | 0.547111E+10 | 0.153314E+10 | 0.647096E+09 | 0.886046E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.502558E+11 | 0.386298E+11 | 0.482511E+11 | 0.225428E+11 | 0.257083E+11 | 0.00 | 0.00 |
Minimum of Months | 0.827775E+09 | 0.135646E+10 | 0.153314E+10 | 0.647096E+09 | 0.886046E+09 | 0.00 | 0.00 |
Maximum of Months | 0.851923E+10 | 0.646017E+10 | 0.659951E+10 | 0.333483E+10 | 0.337080E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 59807850.24 | 0.961691E+10 | 0.121069E+10 | 0.00 | 0.121069E+10 | 0.00 | 0.00 |
February | 0.344225E+09 | 0.631355E+10 | 0.154399E+10 | 0.00 | 0.154399E+10 | 0.00 | 0.00 |
March | 0.112105E+10 | 0.555083E+10 | 0.277688E+10 | 0.00 | 0.277688E+10 | 0.00 | 0.00 |
April | 0.180587E+10 | 0.373932E+10 | 0.306410E+10 | 17881386.28 | 0.304622E+10 | 0.00 | 0.00 |
May | 0.323046E+10 | 0.293475E+10 | 0.415802E+10 | 0.246389E+09 | 0.391163E+10 | 0.00 | 0.00 |
June | 0.483978E+10 | 0.190622E+10 | 0.468560E+10 | 0.538570E+09 | 0.414703E+10 | 0.00 | 0.00 |
July | 0.538284E+10 | 0.167135E+10 | 0.442324E+10 | 0.414289E+09 | 0.400895E+10 | 0.00 | 0.00 |
August | 0.393612E+10 | 0.188242E+10 | 0.354436E+10 | 95005459.17 | 0.344936E+10 | 0.00 | 0.00 |
September | 0.230570E+10 | 0.265451E+10 | 0.256885E+10 | 921843.89 | 0.256793E+10 | 0.00 | 0.00 |
October | 0.105733E+10 | 0.390647E+10 | 0.193629E+10 | 0.00 | 0.193629E+10 | 0.00 | 0.00 |
November | 0.278439E+09 | 0.549377E+10 | 0.127385E+10 | 0.00 | 0.127385E+10 | 0.00 | 0.00 |
December | 29675764.09 | 0.811011E+10 | 0.101523E+10 | 0.00 | 0.101523E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.243913E+11 | 0.537802E+11 | 0.322011E+11 | 0.131306E+10 | 0.308881E+11 | 0.00 | 0.00 |
Minimum of Months | 29675764.09 | 0.167135E+10 | 0.101523E+10 | 0.00 | 0.101523E+10 | 0.00 | 0.00 |
Maximum of Months | 0.538284E+10 | 0.961691E+10 | 0.468560E+10 | 0.538570E+09 | 0.414703E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.102978E+10 | 0.591356E+10 | 0.185337E+10 | 0.849694E+09 | 0.100367E+10 | 0.00 | 0.00 |
February | 0.204324E+10 | 0.388924E+10 | 0.261830E+10 | 0.129992E+10 | 0.131838E+10 | 0.00 | 0.00 |
March | 0.327920E+10 | 0.352077E+10 | 0.389774E+10 | 0.161278E+10 | 0.228496E+10 | 0.00 | 0.00 |
April | 0.472681E+10 | 0.244168E+10 | 0.481271E+10 | 0.238514E+10 | 0.242757E+10 | 0.00 | 0.00 |
May | 0.572184E+10 | 0.200782E+10 | 0.549347E+10 | 0.244425E+10 | 0.304922E+10 | 0.00 | 0.00 |
June | 0.817000E+10 | 0.133385E+10 | 0.688122E+10 | 0.354107E+10 | 0.334015E+10 | 0.00 | 0.00 |
July | 0.954117E+10 | 0.114557E+10 | 0.746276E+10 | 0.421890E+10 | 0.324386E+10 | 0.00 | 0.00 |
August | 0.810287E+10 | 0.127838E+10 | 0.648547E+10 | 0.361351E+10 | 0.287197E+10 | 0.00 | 0.00 |
September | 0.507112E+10 | 0.172458E+10 | 0.443984E+10 | 0.229183E+10 | 0.214801E+10 | 0.00 | 0.00 |
October | 0.322172E+10 | 0.250315E+10 | 0.329153E+10 | 0.167139E+10 | 0.162014E+10 | 0.00 | 0.00 |
November | 0.149041E+10 | 0.337574E+10 | 0.201882E+10 | 0.942522E+09 | 0.107629E+10 | 0.00 | 0.00 |
December | 0.815930E+09 | 0.497834E+10 | 0.153863E+10 | 0.660844E+09 | 0.877783E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.532141E+11 | 0.341127E+11 | 0.507939E+11 | 0.255318E+11 | 0.252620E+11 | 0.00 | 0.00 |
Minimum of Months | 0.815930E+09 | 0.114557E+10 | 0.153863E+10 | 0.660844E+09 | 0.877783E+09 | 0.00 | 0.00 |
Maximum of Months | 0.954117E+10 | 0.591356E+10 | 0.746276E+10 | 0.421890E+10 | 0.334015E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.801449E+10 | 0.832546E+10 | 0.853404E+10 | 0.609518E+10 | 0.243886E+10 | 0.00 | 0.00 |
February | 0.101081E+11 | 0.562316E+10 | 0.981623E+10 | 0.706020E+10 | 0.275603E+10 | 0.00 | 0.00 |
March | 0.997378E+10 | 0.554228E+10 | 0.971455E+10 | 0.545524E+10 | 0.425930E+10 | 0.00 | 0.00 |
April | 0.806982E+10 | 0.396940E+10 | 0.755697E+10 | 0.361455E+10 | 0.394242E+10 | 0.00 | 0.00 |
May | 0.750967E+10 | 0.326218E+10 | 0.693798E+10 | 0.230429E+10 | 0.463369E+10 | 0.00 | 0.00 |
June | 0.819412E+10 | 0.223391E+10 | 0.667121E+10 | 0.194564E+10 | 0.472556E+10 | 0.00 | 0.00 |
July | 0.101623E+11 | 0.187555E+10 | 0.743197E+10 | 0.274535E+10 | 0.468662E+10 | 0.00 | 0.00 |
August | 0.117120E+11 | 0.210850E+10 | 0.883241E+10 | 0.445314E+10 | 0.437927E+10 | 0.00 | 0.00 |
September | 0.116731E+11 | 0.283160E+10 | 0.948020E+10 | 0.580882E+10 | 0.367137E+10 | 0.00 | 0.00 |
October | 0.116578E+11 | 0.399398E+10 | 0.102414E+11 | 0.708180E+10 | 0.315960E+10 | 0.00 | 0.00 |
November | 0.945863E+10 | 0.496852E+10 | 0.903593E+10 | 0.654527E+10 | 0.249067E+10 | 0.00 | 0.00 |
December | 0.783597E+10 | 0.701313E+10 | 0.811539E+10 | 0.586013E+10 | 0.225526E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.114370E+12 | 0.517477E+11 | 0.102368E+12 | 0.589696E+11 | 0.433987E+11 | 0.00 | 0.00 |
Minimum of Months | 0.750967E+10 | 0.187555E+10 | 0.667121E+10 | 0.194564E+10 | 0.225526E+10 | 0.00 | 0.00 |
Maximum of Months | 0.117120E+11 | 0.832546E+10 | 0.102414E+11 | 0.708180E+10 | 0.472556E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.885594E+09 | 0.624734E+10 | 0.167876E+10 | 0.676552E+09 | 0.100221E+10 | 0.00 | 0.00 |
February | 0.202440E+10 | 0.408813E+10 | 0.258809E+10 | 0.127218E+10 | 0.131591E+10 | 0.00 | 0.00 |
March | 0.298203E+10 | 0.378282E+10 | 0.366700E+10 | 0.134364E+10 | 0.232335E+10 | 0.00 | 0.00 |
April | 0.456123E+10 | 0.268434E+10 | 0.463285E+10 | 0.205257E+10 | 0.258029E+10 | 0.00 | 0.00 |
May | 0.632771E+10 | 0.220837E+10 | 0.592153E+10 | 0.270053E+10 | 0.322099E+10 | 0.00 | 0.00 |
June | 0.741133E+10 | 0.151881E+10 | 0.623457E+10 | 0.286377E+10 | 0.337080E+10 | 0.00 | 0.00 |
July | 0.850492E+10 | 0.133869E+10 | 0.659951E+10 | 0.333483E+10 | 0.326468E+10 | 0.00 | 0.00 |
August | 0.702768E+10 | 0.143684E+10 | 0.560388E+10 | 0.275026E+10 | 0.285361E+10 | 0.00 | 0.00 |
September | 0.505442E+10 | 0.189557E+10 | 0.436255E+10 | 0.220553E+10 | 0.215702E+10 | 0.00 | 0.00 |
October | 0.319454E+10 | 0.273440E+10 | 0.322196E+10 | 0.160082E+10 | 0.162114E+10 | 0.00 | 0.00 |
November | 0.178205E+10 | 0.363481E+10 | 0.220727E+10 | 0.109499E+10 | 0.111227E+10 | 0.00 | 0.00 |
December | 0.847531E+09 | 0.525258E+10 | 0.153314E+10 | 0.647096E+09 | 0.886046E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.506034E+11 | 0.368227E+11 | 0.482511E+11 | 0.225428E+11 | 0.257083E+11 | 0.00 | 0.00 |
Minimum of Months | 0.847531E+09 | 0.133869E+10 | 0.153314E+10 | 0.647096E+09 | 0.886046E+09 | 0.00 | 0.00 |
Maximum of Months | 0.850492E+10 | 0.624734E+10 | 0.659951E+10 | 0.333483E+10 | 0.337080E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -8.8 | -10.9 | -16.1 | 5.70 | -23.3 | 32.48 | 106.19 | 0.00 |
February | -2.2 | -5.0 | -9.9 | 6.21 | -16.1 | 41.31 | 158.25 | 0.00 |
March | 0.30 | -2.9 | -8.4 | 5.38 | -12.8 | 78.62 | 145.02 | 0.00 |
April | 6.67 | 2.34 | -2.9 | 4.89 | -6.2 | 82.10 | 182.32 | 0.01 |
May | 10.10 | 5.18 | 0.22 | 5.28 | -1.1 | 102.67 | 205.47 | 0.01 |
June | 16.46 | 10.06 | 4.91 | 4.56 | 5.05 | 103.05 | 264.47 | 0.02 |
July | 20.57 | 12.46 | 6.56 | 4.24 | 8.00 | 89.47 | 301.47 | 0.00 |
August | 19.17 | 11.04 | 4.61 | 4.29 | 7.19 | 78.96 | 261.05 | 0.00 |
September | 14.69 | 9.08 | 4.37 | 5.43 | 3.42 | 63.03 | 204.21 | 0.00 |
October | 8.64 | 4.13 | -1.0 | 5.38 | -4.2 | 47.64 | 162.42 | 0.00 |
November | 2.84 | -0.9 | -6.9 | 5.91 | -11.0 | 33.00 | 125.52 | 0.00 |
December | -4.1 | -6.5 | -11.1 | 5.64 | -18.2 | 26.54 | 97.81 | 0.00 |
Annual Sum or Average | 7.07 | 2.37 | -2.9 | 5.23 | -5.7 | 65.04 | 184.63 | 0.00 |
Minimum of Months | -8.8 | -10.9 | -16.1 | 4.24 | -23.3 | 26.54 | 97.81 | 0.00 |
Maximum of Months | 20.57 | 12.46 | 6.56 | 6.21 | 8.00 | 103.05 | 301.47 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.60 | 14-JAN-12:00 | 5.16 | -1.1 | 8.20 | -2.3 | 105.00 | 464.50 |
February | 18.90 | 27-FEB-14:00 | 7.23 | -7.8 | 5.20 | 1.37 | 76.00 | 634.50 |
March | 15.00 | 14-MAR-13:20 | 6.67 | -2.4 | 9.30 | 1.23 | 201.67 | 711.67 |
April | 23.30 | 07-APR-13:00 | 9.68 | -4.4 | 9.30 | 4.92 | 314.50 | 110.00 |
May | 30.00 | 20-MAY-15:00 | 15.22 | 5.60 | 6.70 | 20.57 | 215.50 | 18.50 |
June | 32.20 | 29-JUN-12:00 | 14.40 | 0.60 | 9.30 | 17.03 | 187.00 | 729.00 |
July | 37.20 | 17-JUL-15:00 | 17.28 | 4.40 | 4.60 | 20.22 | 119.50 | 797.00 |
August | 35.60 | 05-AUG-15:00 | 17.65 | 6.70 | 5.20 | 22.47 | 136.50 | 625.50 |
September | 34.40 | 02-SEP-14:00 | 16.28 | 4.40 | 7.70 | 20.75 | 95.50 | 789.50 |
October | 25.00 | 18-OCT-13:00 | 11.40 | -1.1 | 7.70 | 7.35 | 48.00 | 913.00 |
November | 17.20 | 04-NOV-13:00 | 8.18 | -1.1 | 11.30 | 2.22 | 81.00 | 689.50 |
December | 13.90 | 10-DEC-01:00 | 5.50 | -5.0 | 13.90 | 5.74 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.60 | 5.16 | -7.8 | 4.60 | -2.3 | 0.00 | 0.00 | |
Maximum of Months | 37.20 | 17.65 | 6.70 | 13.90 | 22.47 | 314.50 | 913.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -33.9 | 10-JAN-21:00 | -34.1 | -37.8 | 3.10 | -54.3 | 0.00 | 0.00 |
February | -25.0 | 01-FEB-03:00 | -25.2 | -27.8 | 2.10 | -45.6 | 0.00 | 0.00 |
March | -23.3 | 04-MAR-23:00 | -23.8 | -28.9 | 3.60 | -44.5 | 0.00 | 0.00 |
April | -7.8 | 29-APR-03:00 | -8.7 | -10.6 | 4.10 | -25.6 | 0.00 | 0.00 |
May | -2.8 | 08-MAY-00:10 | -3.3 | -3.9 | 6.18 | -10.2 | 0.00 | 0.00 |
June | 0.60 | 15-JUN-03:00 | -0.5 | -1.7 | 2.60 | -15.7 | 0.00 | 0.00 |
July | 5.60 | 08-JUL-03:00 | 2.99 | 0.00 | 4.10 | -9.2 | 0.00 | 0.00 |
August | 6.70 | 17-AUG-00:00 | 4.32 | 1.70 | 2.60 | -7.1 | 0.00 | 0.00 |
September | 0.00 | 17-SEP-02:00 | -1.6 | -3.9 | 4.10 | -16.8 | 0.00 | 0.00 |
October | -6.1 | 10-OCT-05:19 | -6.6 | -7.8 | 3.77 | -20.6 | 0.00 | 0.00 |
November | -16.7 | 26-NOV-07:00 | -17.3 | -20.6 | 4.60 | -33.8 | 19.50 | 94.00 |
December | -28.3 | 29-DEC-08:00 | -28.6 | -32.2 | 2.10 | -48.7 | 69.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -33.9 | -34.1 | -37.8 | 2.10 | -54.3 | 0.00 | 0.00 | |
Maximum of Months | 6.70 | 4.32 | 1.70 | 6.18 | -7.1 | 69.50 | 94.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.18 | 13-JAN-14:00 | 10.00 | 0.00 | 8.80 | -3.0 | 40.00 | 694.00 |
February | 7.23 | 27-FEB-14:00 | 18.90 | -7.8 | 5.20 | 1.37 | 76.00 | 634.50 |
March | 6.94 | 14-MAR-13:00 | 15.00 | -1.7 | 10.30 | 1.80 | 241.00 | 538.00 |
April | 11.02 | 06-APR-15:00 | 22.20 | 1.10 | 3.60 | 5.33 | 110.00 | 779.00 |
May | 15.22 | 20-MAY-15:00 | 30.00 | 5.60 | 6.70 | 20.57 | 215.50 | 18.50 |
June | 19.20 | 20-JUN-14:00 | 29.40 | 14.40 | 2.60 | 18.28 | 204.00 | 614.00 |
July | 19.21 | 19-JUL-11:00 | 29.40 | 14.40 | 8.80 | 19.52 | 306.50 | 563.50 |
August | 17.65 | 05-AUG-15:00 | 35.60 | 6.70 | 5.20 | 22.47 | 136.50 | 625.50 |
September | 20.12 | 07-SEP-15:20 | 25.17 | 17.93 | 4.10 | 15.88 | 127.67 | 652.00 |
October | 11.61 | 18-OCT-14:00 | 25.00 | -0.6 | 7.70 | 7.55 | 40.50 | 852.00 |
November | 8.89 | 17-NOV-16:00 | 17.20 | 1.10 | 11.30 | 4.10 | 0.00 | 0.00 |
December | 7.62 | 19-DEC-14:00 | 12.80 | 2.80 | 8.20 | 1.37 | 74.00 | 138.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 5.18 | 10.00 | -7.8 | 2.60 | -3.0 | 0.00 | 0.00 | |
Maximum of Months | 20.12 | 35.60 | 17.93 | 11.30 | 22.47 | 306.50 | 852.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.70 | 12-JAN-14:00 | 7.20 | 4.48 | 5.20 | -1.0 | 107.00 | 61.00 |
February | -0.6 | 11-FEB-08:00 | 4.40 | 2.16 | 10.80 | -5.7 | 69.50 | 50.50 |
March | -0.6 | 10-MAR-12:00 | 8.90 | 4.51 | 10.30 | -2.3 | 253.00 | 140.50 |
April | 6.10 | 17-APR-16:19 | 7.97 | 6.96 | 4.50 | 0.87 | 201.50 | 117.50 |
May | 12.20 | 02-MAY-12:00 | 18.90 | 14.61 | 12.90 | 14.84 | 108.50 | 934.50 |
June | 15.60 | 20-JUN-19:00 | 25.60 | 18.76 | 3.60 | 20.22 | 17.50 | 17.00 |
July | 16.70 | 18-JUL-21:00 | 19.40 | 17.51 | 4.10 | 16.49 | 0.00 | 0.00 |
August | 11.10 | 08-AUG-11:00 | 26.70 | 16.75 | 2.60 | 12.03 | 134.50 | 869.00 |
September | 18.30 | 07-SEP-14:00 | 24.40 | 20.10 | 4.10 | 15.57 | 111.00 | 720.00 |
October | 6.70 | 01-OCT-14:09 | 9.08 | 7.78 | 2.10 | 4.07 | 260.33 | 0.33 |
November | 3.30 | 16-NOV-19:00 | 10.60 | 6.88 | 9.80 | -1.7 | 0.00 | 0.00 |
December | 2.80 | 19-DEC-14:09 | 10.97 | 6.81 | 10.78 | -1.0 | 95.00 | 292.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -0.6 | 4.40 | 2.16 | 2.10 | -5.7 | 0.00 | 0.00 | |
Maximum of Months | 18.30 | 26.70 | 20.10 | 12.90 | 20.22 | 260.33 | 934.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 5.41 | 12.59 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 4.46 | 20.37 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 5.03 | 30.19 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 7.01 | 37.07 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 9.90 | 46.35 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 12.91 | 55.45 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 15.24 | 57.38 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 16.26 | 48.01 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 15.67 | 34.51 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 13.64 | 22.84 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 10.74 | 14.52 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 7.74 | 10.24 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 10.37 | 32.53 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 4.46 | 10.24 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 16.26 | 57.38 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.437237E+11 | -0.426678E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.105587E+10 | 58.98 | 0.00 | 0.00 |
February | 0.403949E+11 | -0.394525E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -942399995.9 | 58.98 | 0.00 | 0.00 |
March | 0.469627E+11 | -0.459286E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.103411E+10 | 58.97 | 0.00 | 0.00 |
April | 0.411168E+11 | -0.401230E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -993830825.0 | 58.97 | 0.00 | 0.00 |
May | 0.415216E+11 | -0.404951E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102648E+10 | 58.98 | 0.00 | 0.00 |
June | 0.386516E+11 | -0.376585E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -993177832.1 | 58.98 | 0.00 | 0.00 |
July | 0.350107E+11 | -0.339906E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102007E+10 | 58.98 | 0.00 | 0.00 |
August | 0.373972E+11 | -0.363730E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102417E+10 | 58.98 | 0.00 | 0.00 |
September | 0.344388E+11 | -0.334495E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -989274031.5 | 58.97 | 0.00 | 0.00 |
October | 0.371418E+11 | -0.361205E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102133E+10 | 58.98 | 0.00 | 0.00 |
November | 0.386811E+11 | -0.376911E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -990020606.9 | 58.98 | 0.00 | 0.00 |
December | 0.408582E+11 | -0.398248E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.103337E+10 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.475899E+12 | -0.463775E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.121241E+11 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.344388E+11 | -0.459286E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.105587E+10 | 58.97 | 0.00 | 0.00 |
Maximum of Months | 0.469627E+11 | -0.334495E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -942399995.9 | 58.98 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.64 | 0.61 | 01-JAN-08:50 | 5097.18 | 32.67 | 186.00 | 222.00 | 4508.42 | 37.63 | 218.67 | 207.17 |
February | 275.00 | 0.63 | 0.61 | 01-FEB-08:20 | 7187.51 | 34.27 | 240.83 | 249.83 | 3012.65 | 31.09 | 228.67 | 239.83 |
March | 304.00 | 0.63 | 0.61 | 01-MAR-07:49 | 8536.88 | 32.08 | 253.50 | 316.17 | 1586.52 | 22.09 | 194.67 | 285.17 |
April | 325.17 | 0.63 | 0.61 | 01-APR-08:39 | 1939.33 | 18.00 | 0.00 | 339.83 | 1094.23 | 21.03 | 159.17 | 297.33 |
May | 385.83 | 0.63 | 0.61 | 01-MAY-06:10 | 1718.33 | 17.69 | 0.00 | 385.83 | 953.00 | 20.69 | 170.50 | 336.33 |
June | 434.17 | 0.64 | 0.61 | 01-JUN-13:39 | 1461.07 | 17.04 | 0.00 | 394.17 | 842.21 | 20.09 | 183.17 | 341.67 |
July | 417.33 | 0.63 | 0.61 | 01-JUL-06:40 | 1565.82 | 17.48 | 0.00 | 393.33 | 928.13 | 20.55 | 142.50 | 350.17 |
August | 421.33 | 0.64 | 0.61 | 01-AUG-06:19 | 1676.86 | 17.06 | 0.00 | 370.83 | 991.36 | 20.07 | 147.00 | 328.17 |
September | 352.17 | 0.64 | 0.61 | 01-SEP-06:49 | 2439.00 | 18.71 | 29.50 | 318.67 | 1163.65 | 20.35 | 140.67 | 285.50 |
October | 317.67 | 0.63 | 0.61 | 01-OCT-07:40 | 7376.52 | 33.51 | 276.67 | 294.67 | 1885.38 | 23.09 | 168.33 | 272.50 |
November | 269.50 | 0.63 | 0.61 | 01-NOV-07:49 | 5291.25 | 33.17 | 223.50 | 240.67 | 4880.05 | 38.16 | 261.50 | 236.17 |
December | 236.83 | 0.64 | 0.61 | 01-DEC-08:50 | 3827.25 | 30.55 | 166.50 | 221.83 | 3680.55 | 37.33 | 224.50 | 210.67 |
Annual Sum or Average | 3965.83 | 0.63 | 3668.97 | 23.84 | 1376.50 | 3747.83 | 1871.79 | 24.71 | 2239.33 | 3390.67 | ||
Minimum of Months | 226.83 | 0.63 | 0.61 | 1461.07 | 17.04 | 0.00 | 221.83 | 842.21 | 20.07 | 140.67 | 207.17 | |
Maximum of Months | 434.17 | 0.64 | 0.61 | 8536.88 | 34.27 | 276.67 | 394.17 | 4880.05 | 38.16 | 261.50 | 350.17 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.65 | 0.61 | 01-JAN-08:50 | 1515.70 | 19.87 | 73.83 | 201.50 | 909.48 | 20.73 | 61.50 | 159.33 |
February | 275.00 | 0.64 | 0.61 | 01-FEB-08:09 | 1512.39 | 16.70 | 48.83 | 232.00 | 897.48 | 18.14 | 46.17 | 192.50 |
March | 304.00 | 0.63 | 0.61 | 01-MAR-07:40 | 2643.32 | 18.73 | 70.33 | 309.50 | 1543.82 | 18.41 | 44.83 | 270.67 |
April | 325.17 | 0.63 | 0.61 | 01-APR-08:39 | 2661.32 | 16.14 | 42.50 | 346.83 | 1551.95 | 15.15 | 0.00 | 297.33 |
May | 385.83 | 0.63 | 0.61 | 01-MAY-05:40 | 3060.56 | 13.63 | 0.00 | 394.67 | 1315.48 | 15.00 | 0.00 | 347.00 |
June | 434.17 | 0.63 | 0.61 | 01-JUN-13:39 | 3714.72 | 13.03 | 0.00 | 406.33 | 1589.50 | 14.54 | 0.00 | 369.50 |
July | 417.33 | 0.62 | 0.61 | 01-JUL-06:40 | 4046.93 | 13.47 | 3.67 | 409.33 | 1706.80 | 14.95 | 0.00 | 377.67 |
August | 421.33 | 0.63 | 0.61 | 01-AUG-05:40 | 3022.20 | 15.49 | 55.83 | 378.50 | 1838.33 | 14.30 | 0.00 | 338.50 |
September | 352.17 | 0.64 | 0.61 | 01-SEP-06:30 | 2350.16 | 15.89 | 52.50 | 313.00 | 1343.76 | 14.94 | 8.50 | 274.00 |
October | 317.67 | 0.64 | 0.61 | 01-OCT-07:40 | 2076.98 | 18.31 | 80.17 | 273.17 | 1248.14 | 19.32 | 73.33 | 229.83 |
November | 269.50 | 0.65 | 0.61 | 01-NOV-07:49 | 1373.22 | 18.88 | 81.33 | 215.00 | 727.59 | 18.22 | 53.83 | 170.83 |
December | 236.83 | 0.65 | 0.61 | 01-DEC-08:50 | 1174.43 | 19.62 | 80.33 | 190.00 | 738.18 | 20.91 | 72.50 | 142.17 |
Annual Sum or Average | 3965.83 | 0.64 | 2602.30 | 16.20 | 589.33 | 3669.83 | 1349.58 | 16.60 | 360.67 | 3169.33 | ||
Minimum of Months | 226.83 | 0.62 | 0.61 | 1174.43 | 13.03 | 0.00 | 190.00 | 727.59 | 14.30 | 0.00 | 142.17 | |
Maximum of Months | 434.17 | 0.65 | 0.61 | 4046.93 | 19.87 | 81.33 | 409.33 | 1838.33 | 20.91 | 73.33 | 377.67 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.67 | 0.61 | 01-JAN-09:39 | 494.54 | 0.00 | 0.00 | 170.83 | 293.92 | 0.00 | 0.00 | 68.67 |
February | 275.00 | 0.65 | 0.61 | 01-FEB-10:20 | 538.64 | 0.00 | 0.00 | 209.83 | 334.67 | 0.00 | 0.00 | 129.00 |
March | 304.00 | 0.63 | 0.61 | 01-MAR-07:00 | 858.79 | 0.00 | 0.00 | 299.67 | 505.19 | 0.00 | 0.00 | 245.67 |
April | 325.17 | 0.63 | 0.61 | 01-APR-08:39 | 892.96 | 0.00 | 0.00 | 342.50 | 533.87 | 0.00 | 0.00 | 281.00 |
May | 385.83 | 0.62 | 0.61 | 01-MAY-05:49 | 1114.37 | 0.00 | 0.00 | 404.17 | 651.57 | 0.00 | 0.00 | 363.00 |
June | 434.17 | 0.63 | 0.61 | 01-JUN-13:39 | 1155.10 | 0.00 | 0.00 | 432.33 | 637.69 | 0.00 | 0.00 | 395.83 |
July | 417.33 | 0.62 | 0.61 | 01-JUL-06:40 | 1129.94 | 0.00 | 0.00 | 419.17 | 646.37 | 0.00 | 0.00 | 386.00 |
August | 421.33 | 0.63 | 0.61 | 01-AUG-05:40 | 869.82 | 0.00 | 0.00 | 391.67 | 558.50 | 0.00 | 0.00 | 357.67 |
September | 352.17 | 0.64 | 0.61 | 01-SEP-06:49 | 707.70 | 0.00 | 0.00 | 310.67 | 442.60 | 0.00 | 0.00 | 241.50 |
October | 317.67 | 0.65 | 0.61 | 01-OCT-07:49 | 584.73 | 0.00 | 0.00 | 249.83 | 358.91 | 0.00 | 0.00 | 166.50 |
November | 269.50 | 0.66 | 0.61 | 01-NOV-08:09 | 462.77 | 0.00 | 0.00 | 181.17 | 280.42 | 0.00 | 0.00 | 61.17 |
December | 236.83 | 0.67 | 0.61 | 01-DEC-09:09 | 401.05 | 0.00 | 0.00 | 148.67 | 242.56 | 0.00 | 0.00 | 15.83 |
Annual Sum or Average | 3965.83 | 0.64 | 815.95 | 0.00 | 0.00 | 3560.50 | 484.67 | 0.00 | 0.00 | 2711.83 | ||
Minimum of Months | 226.83 | 0.62 | 0.61 | 401.05 | 0.00 | 0.00 | 148.67 | 242.56 | 0.00 | 0.00 | 15.83 | |
Maximum of Months | 434.17 | 0.67 | 0.61 | 1155.10 | 0.00 | 0.00 | 432.33 | 651.57 | 0.00 | 0.00 | 395.83 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.66 | 0.61 | 01-JAN-09:39 | 1396.40 | 18.96 | 69.17 | 194.83 | 866.64 | 19.81 | 58.83 | 148.83 |
February | 275.00 | 0.64 | 0.61 | 01-FEB-10:20 | 1854.80 | 19.00 | 76.33 | 229.83 | 955.29 | 18.25 | 48.83 | 192.67 |
March | 304.00 | 0.63 | 0.61 | 01-MAR-07:00 | 2492.22 | 18.53 | 69.00 | 305.00 | 1412.19 | 19.45 | 62.00 | 268.33 |
April | 325.17 | 0.63 | 0.61 | 01-APR-08:39 | 2604.19 | 16.34 | 48.50 | 335.17 | 1512.15 | 15.24 | 0.00 | 295.50 |
May | 385.83 | 0.63 | 0.61 | 01-MAY-06:19 | 3076.06 | 13.72 | 0.00 | 389.50 | 1774.73 | 15.20 | 1.33 | 348.00 |
June | 434.17 | 0.63 | 0.61 | 01-JUN-13:39 | 3145.79 | 13.15 | 0.00 | 409.50 | 1403.52 | 16.71 | 47.50 | 369.67 |
July | 417.33 | 0.63 | 0.61 | 01-JUL-06:40 | 3662.35 | 13.44 | 3.67 | 397.50 | 1634.67 | 16.31 | 31.50 | 360.67 |
August | 421.33 | 0.63 | 0.61 | 01-AUG-06:30 | 2705.64 | 15.41 | 56.83 | 374.00 | 1540.18 | 14.36 | 0.00 | 337.00 |
September | 352.17 | 0.64 | 0.61 | 01-SEP-06:00 | 2876.75 | 17.35 | 75.33 | 314.50 | 1113.30 | 14.77 | 5.50 | 274.50 |
October | 317.67 | 0.64 | 0.61 | 01-OCT-07:00 | 1853.40 | 18.27 | 77.67 | 270.83 | 991.50 | 18.09 | 53.33 | 228.50 |
November | 269.50 | 0.65 | 0.61 | 01-NOV-08:20 | 1582.40 | 19.14 | 82.33 | 212.17 | 941.30 | 20.18 | 71.83 | 169.83 |
December | 236.83 | 0.65 | 0.61 | 01-DEC-09:09 | 1122.44 | 19.52 | 79.17 | 194.00 | 608.57 | 18.53 | 49.83 | 139.83 |
Annual Sum or Average | 3965.83 | 0.64 | 2508.03 | 16.46 | 638.00 | 3626.83 | 1288.60 | 16.93 | 430.50 | 3133.33 | ||
Minimum of Months | 226.83 | 0.63 | 0.61 | 1122.44 | 13.15 | 0.00 | 194.00 | 608.57 | 14.36 | 0.00 | 139.83 | |
Maximum of Months | 434.17 | 0.66 | 0.61 | 3662.35 | 19.52 | 82.33 | 409.50 | 1774.73 | 20.18 | 71.83 | 369.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.64 | 0.61 | 01-JAN-08:50 | 4462.85 | 25.63 | 138.83 | 220.83 | 4554.30 | 37.18 | 214.33 | 207.67 |
February | 275.00 | 0.63 | 0.61 | 01-FEB-08:20 | 7152.76 | 33.30 | 239.33 | 249.17 | 3067.03 | 28.60 | 169.67 | 240.17 |
March | 304.00 | 0.63 | 0.61 | 01-MAR-07:49 | 8490.01 | 31.08 | 250.17 | 314.33 | 1637.51 | 17.40 | 6.67 | 286.83 |
April | 325.17 | 0.63 | 0.61 | 01-APR-08:39 | 1908.40 | 12.00 | 0.00 | 338.17 | 1134.03 | 16.87 | 0.00 | 299.17 |
May | 385.83 | 0.63 | 0.61 | 01-MAY-06:10 | 1687.13 | 11.93 | 0.00 | 384.83 | 984.97 | 16.71 | 0.00 | 339.83 |
June | 434.17 | 0.64 | 0.61 | 01-JUN-13:39 | 1437.92 | 11.48 | 0.00 | 392.17 | 870.55 | 16.33 | 0.00 | 345.00 |
July | 417.33 | 0.63 | 0.61 | 01-JUL-06:40 | 1545.48 | 11.87 | 0.00 | 391.17 | 961.96 | 16.80 | 0.00 | 352.33 |
August | 421.33 | 0.64 | 0.61 | 01-AUG-06:19 | 1659.43 | 11.18 | 0.00 | 368.33 | 1030.17 | 16.05 | 0.00 | 330.83 |
September | 352.17 | 0.64 | 0.61 | 01-SEP-06:49 | 2418.58 | 12.96 | 29.50 | 317.50 | 1225.17 | 16.21 | 5.50 | 287.17 |
October | 317.67 | 0.63 | 0.61 | 01-OCT-07:40 | 7290.95 | 32.29 | 270.17 | 293.83 | 2020.28 | 20.65 | 76.17 | 278.50 |
November | 269.50 | 0.64 | 0.61 | 01-NOV-07:49 | 5031.46 | 28.74 | 191.00 | 240.17 | 4886.22 | 36.56 | 248.83 | 233.00 |
December | 236.83 | 0.64 | 0.61 | 01-DEC-08:50 | 3085.67 | 21.26 | 108.67 | 220.67 | 3717.67 | 36.67 | 218.00 | 211.50 |
Annual Sum or Average | 3965.83 | 0.63 | 3543.98 | 18.96 | 1227.67 | 3731.17 | 1918.16 | 21.48 | 939.17 | 3412.00 | ||
Minimum of Months | 226.83 | 0.63 | 0.61 | 1437.92 | 11.18 | 0.00 | 220.67 | 870.55 | 16.05 | 0.00 | 207.67 | |
Maximum of Months | 434.17 | 0.64 | 0.61 | 8490.01 | 33.30 | 270.17 | 392.17 | 4886.22 | 37.18 | 248.83 | 352.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.65 | 0.61 | 01-JAN-08:50 | 1511.97 | 18.02 | 74.00 | 200.67 | 843.63 | 16.72 | 46.17 | 160.00 |
February | 275.00 | 0.64 | 0.61 | 01-FEB-08:09 | 1512.87 | 14.14 | 48.83 | 231.00 | 922.21 | 15.98 | 46.50 | 194.67 |
March | 304.00 | 0.63 | 0.61 | 01-MAR-07:40 | 2640.82 | 16.41 | 70.33 | 308.50 | 1578.00 | 16.18 | 44.50 | 272.67 |
April | 325.17 | 0.63 | 0.61 | 01-APR-08:39 | 2666.43 | 13.26 | 42.50 | 345.67 | 1588.35 | 12.52 | 0.00 | 300.83 |
May | 385.83 | 0.63 | 0.61 | 01-MAY-05:40 | 3058.86 | 10.22 | 0.00 | 394.33 | 1352.32 | 12.53 | 0.00 | 350.50 |
June | 434.17 | 0.63 | 0.61 | 01-JUN-13:39 | 3705.48 | 9.52 | 0.00 | 405.83 | 1632.30 | 12.07 | 0.00 | 372.33 |
July | 417.33 | 0.62 | 0.61 | 01-JUL-06:40 | 4046.95 | 9.92 | 3.67 | 408.33 | 1754.47 | 12.39 | 0.00 | 380.17 |
August | 421.33 | 0.63 | 0.61 | 01-AUG-05:40 | 3030.38 | 12.59 | 55.83 | 378.50 | 1879.80 | 11.71 | 0.00 | 341.83 |
September | 352.17 | 0.64 | 0.61 | 01-SEP-06:30 | 2353.22 | 13.22 | 52.50 | 312.33 | 1375.63 | 12.40 | 8.50 | 277.50 |
October | 317.67 | 0.64 | 0.61 | 01-OCT-07:40 | 2022.78 | 15.71 | 76.50 | 272.67 | 1272.19 | 17.45 | 73.67 | 233.67 |
November | 269.50 | 0.65 | 0.61 | 01-NOV-07:49 | 1167.73 | 14.33 | 56.67 | 214.67 | 745.98 | 16.16 | 53.67 | 174.33 |
December | 236.83 | 0.66 | 0.61 | 01-DEC-08:50 | 1169.49 | 17.76 | 80.33 | 188.67 | 752.12 | 19.15 | 72.67 | 144.50 |
Annual Sum or Average | 3965.83 | 0.64 | 2583.71 | 13.24 | 561.17 | 3661.17 | 1377.67 | 14.16 | 345.67 | 3203.00 | ||
Minimum of Months | 226.83 | 0.62 | 0.61 | 1167.73 | 9.52 | 0.00 | 188.67 | 745.98 | 11.71 | 0.00 | 144.50 | |
Maximum of Months | 434.17 | 0.66 | 0.61 | 4046.95 | 18.02 | 80.33 | 408.33 | 1879.80 | 19.15 | 73.67 | 380.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.67 | 0.61 | 01-JAN-09:50 | 482.82 | 0.00 | 0.00 | 168.17 | 301.22 | 0.00 | 0.00 | 75.83 |
February | 275.00 | 0.65 | 0.61 | 01-FEB-10:20 | 527.36 | 0.00 | 0.00 | 207.67 | 343.55 | 0.00 | 0.00 | 137.67 |
March | 304.00 | 0.63 | 0.61 | 01-MAR-07:00 | 841.75 | 0.00 | 0.00 | 297.50 | 519.31 | 0.00 | 0.00 | 249.50 |
April | 325.17 | 0.63 | 0.61 | 01-APR-08:39 | 877.01 | 0.00 | 0.00 | 340.50 | 549.67 | 0.00 | 0.00 | 286.00 |
May | 385.83 | 0.62 | 0.61 | 01-MAY-05:49 | 1096.75 | 0.00 | 0.00 | 403.00 | 670.62 | 0.00 | 0.00 | 366.50 |
June | 434.17 | 0.63 | 0.61 | 01-JUN-13:39 | 1139.92 | 0.00 | 0.00 | 431.00 | 657.69 | 0.00 | 0.00 | 397.00 |
July | 417.33 | 0.62 | 0.61 | 01-JUL-06:40 | 1116.82 | 0.00 | 0.00 | 418.50 | 667.34 | 0.00 | 0.00 | 387.83 |
August | 421.33 | 0.63 | 0.61 | 01-AUG-05:40 | 857.49 | 0.00 | 0.00 | 390.17 | 575.05 | 0.00 | 0.00 | 361.17 |
September | 352.17 | 0.64 | 0.61 | 01-SEP-06:49 | 695.45 | 0.00 | 0.00 | 307.67 | 455.59 | 0.00 | 0.00 | 248.00 |
October | 317.67 | 0.65 | 0.61 | 01-OCT-07:49 | 572.75 | 0.00 | 0.00 | 247.50 | 368.69 | 0.00 | 0.00 | 174.67 |
November | 269.50 | 0.67 | 0.61 | 01-NOV-08:09 | 452.19 | 0.00 | 0.00 | 178.67 | 287.50 | 0.00 | 0.00 | 72.33 |
December | 236.83 | 0.68 | 0.61 | 01-DEC-09:09 | 390.42 | 0.00 | 0.00 | 144.83 | 247.99 | 0.00 | 0.00 | 20.67 |
Annual Sum or Average | 3965.83 | 0.64 | 802.42 | 0.00 | 0.00 | 3535.17 | 498.83 | 0.00 | 0.00 | 2777.17 | ||
Minimum of Months | 226.83 | 0.62 | 0.61 | 390.42 | 0.00 | 0.00 | 144.83 | 247.99 | 0.00 | 0.00 | 20.67 | |
Maximum of Months | 434.17 | 0.68 | 0.61 | 1139.92 | 0.00 | 0.00 | 431.00 | 670.62 | 0.00 | 0.00 | 397.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.66 | 0.61 | 01-JAN-09:50 | 1391.45 | 17.13 | 69.17 | 194.50 | 883.82 | 17.99 | 58.17 | 151.83 |
February | 275.00 | 0.64 | 0.61 | 01-FEB-10:20 | 1853.11 | 16.87 | 76.50 | 229.00 | 979.31 | 16.09 | 48.67 | 196.00 |
March | 304.00 | 0.63 | 0.61 | 01-MAR-07:00 | 2486.70 | 16.15 | 68.83 | 304.50 | 1442.85 | 17.44 | 62.17 | 270.50 |
April | 325.17 | 0.63 | 0.61 | 01-APR-08:39 | 2604.96 | 13.56 | 48.50 | 334.00 | 1547.88 | 12.66 | 0.00 | 297.83 |
May | 385.83 | 0.63 | 0.61 | 01-MAY-06:19 | 2823.08 | 10.24 | 0.00 | 388.33 | 1813.43 | 12.69 | 1.33 | 350.00 |
June | 434.17 | 0.63 | 0.61 | 01-JUN-13:39 | 3133.75 | 9.71 | 0.00 | 408.17 | 1440.99 | 14.66 | 47.83 | 372.50 |
July | 417.33 | 0.63 | 0.61 | 01-JUL-06:40 | 3655.10 | 10.00 | 3.67 | 396.67 | 1678.84 | 14.09 | 31.50 | 364.17 |
August | 421.33 | 0.64 | 0.61 | 01-AUG-06:30 | 2672.63 | 12.61 | 56.83 | 373.00 | 1577.08 | 11.85 | 0.00 | 339.83 |
September | 352.17 | 0.64 | 0.61 | 01-SEP-06:00 | 2626.87 | 14.72 | 72.33 | 314.00 | 1145.72 | 12.21 | 5.50 | 277.17 |
October | 317.67 | 0.64 | 0.61 | 01-OCT-07:00 | 1611.16 | 13.92 | 53.67 | 270.33 | 1000.05 | 15.62 | 49.33 | 231.17 |
November | 269.50 | 0.65 | 0.61 | 01-NOV-08:20 | 1570.29 | 16.79 | 78.83 | 211.67 | 866.97 | 16.21 | 52.50 | 170.33 |
December | 236.83 | 0.66 | 0.61 | 01-DEC-09:09 | 953.39 | 14.75 | 54.00 | 192.83 | 622.98 | 16.45 | 49.83 | 145.00 |
Annual Sum or Average | 3965.83 | 0.64 | 2424.56 | 13.39 | 582.33 | 3617.00 | 1312.34 | 14.52 | 406.83 | 3166.33 | ||
Minimum of Months | 226.83 | 0.63 | 0.61 | 953.39 | 9.71 | 0.00 | 192.83 | 622.98 | 11.85 | 0.00 | 145.00 | |
Maximum of Months | 434.17 | 0.66 | 0.61 | 3655.10 | 17.13 | 78.83 | 408.17 | 1813.43 | 17.99 | 62.17 | 372.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.64 | 0.61 | 01-JAN-08:50 | 4461.26 | 25.61 | 138.83 | 220.83 | 4555.28 | 37.17 | 214.33 | 207.83 |
February | 275.00 | 0.63 | 0.61 | 01-FEB-08:20 | 7151.54 | 33.28 | 239.33 | 249.17 | 3068.36 | 28.59 | 169.67 | 240.17 |
March | 304.00 | 0.63 | 0.61 | 01-MAR-07:49 | 8490.16 | 31.07 | 250.17 | 314.33 | 1639.37 | 17.38 | 6.67 | 287.00 |
April | 325.17 | 0.63 | 0.61 | 01-APR-08:39 | 1909.27 | 11.96 | 0.00 | 338.17 | 1135.34 | 16.85 | 0.00 | 299.17 |
May | 385.83 | 0.63 | 0.61 | 01-MAY-06:10 | 1688.03 | 11.89 | 0.00 | 384.67 | 986.12 | 16.70 | 0.00 | 340.00 |
June | 434.17 | 0.64 | 0.61 | 01-JUN-13:39 | 1438.50 | 11.44 | 0.00 | 392.17 | 871.44 | 16.31 | 0.00 | 345.00 |
July | 417.33 | 0.63 | 0.61 | 01-JUL-06:40 | 1546.04 | 11.83 | 0.00 | 391.17 | 962.87 | 16.78 | 0.00 | 352.50 |
August | 421.33 | 0.64 | 0.61 | 01-AUG-06:19 | 1660.07 | 11.14 | 0.00 | 368.33 | 1031.19 | 16.03 | 0.00 | 330.83 |
September | 352.17 | 0.64 | 0.61 | 01-SEP-06:49 | 2419.04 | 12.92 | 29.50 | 317.50 | 1226.41 | 16.19 | 5.50 | 287.17 |
October | 317.67 | 0.63 | 0.61 | 01-OCT-07:40 | 7290.12 | 32.27 | 270.17 | 293.83 | 2021.62 | 20.63 | 76.17 | 278.50 |
November | 269.50 | 0.64 | 0.61 | 01-NOV-07:49 | 5029.92 | 28.72 | 191.00 | 240.17 | 4887.26 | 36.55 | 248.83 | 233.00 |
December | 236.83 | 0.64 | 0.61 | 01-DEC-08:50 | 3083.93 | 21.23 | 108.67 | 220.67 | 3718.34 | 36.67 | 218.00 | 211.50 |
Annual Sum or Average | 3965.83 | 0.63 | 3543.93 | 18.92 | 1227.67 | 3731.00 | 1919.30 | 21.47 | 939.17 | 3412.67 | ||
Minimum of Months | 226.83 | 0.63 | 0.61 | 1438.50 | 11.14 | 0.00 | 220.67 | 871.44 | 16.03 | 0.00 | 207.83 | |
Maximum of Months | 434.17 | 0.64 | 0.61 | 8490.16 | 33.28 | 270.17 | 392.17 | 4887.26 | 37.17 | 248.83 | 352.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.65 | 0.61 | 01-JAN-08:50 | 1511.69 | 18.01 | 74.00 | 200.67 | 844.16 | 16.71 | 46.17 | 160.00 |
February | 275.00 | 0.64 | 0.61 | 01-FEB-08:09 | 1512.44 | 14.12 | 48.83 | 231.00 | 922.76 | 15.97 | 46.50 | 194.67 |
March | 304.00 | 0.63 | 0.61 | 01-MAR-07:40 | 2640.59 | 16.40 | 70.33 | 308.50 | 1579.01 | 16.17 | 44.50 | 272.83 |
April | 325.17 | 0.63 | 0.61 | 01-APR-08:39 | 2666.21 | 13.25 | 42.50 | 345.67 | 1589.22 | 12.51 | 0.00 | 300.67 |
May | 385.83 | 0.63 | 0.61 | 01-MAY-05:40 | 3058.92 | 10.20 | 0.00 | 394.33 | 1353.32 | 12.52 | 0.00 | 350.67 |
June | 434.17 | 0.63 | 0.61 | 01-JUN-13:39 | 3705.14 | 9.51 | 0.00 | 405.67 | 1633.17 | 12.06 | 0.00 | 372.50 |
July | 417.33 | 0.62 | 0.61 | 01-JUL-06:40 | 4046.53 | 9.91 | 3.67 | 408.17 | 1755.30 | 12.38 | 0.00 | 380.00 |
August | 421.33 | 0.63 | 0.61 | 01-AUG-05:40 | 3030.04 | 12.58 | 55.83 | 378.33 | 1880.61 | 11.70 | 0.00 | 341.83 |
September | 352.17 | 0.64 | 0.61 | 01-SEP-06:30 | 2352.79 | 13.21 | 52.50 | 312.33 | 1376.37 | 12.40 | 8.50 | 277.67 |
October | 317.67 | 0.64 | 0.61 | 01-OCT-07:40 | 2022.38 | 15.69 | 76.50 | 272.67 | 1272.81 | 17.45 | 73.67 | 233.67 |
November | 269.50 | 0.65 | 0.61 | 01-NOV-07:49 | 1167.42 | 14.32 | 56.67 | 214.50 | 746.46 | 16.15 | 53.67 | 174.33 |
December | 236.83 | 0.66 | 0.61 | 01-DEC-08:50 | 1169.18 | 17.75 | 80.33 | 188.67 | 752.52 | 19.15 | 72.67 | 144.67 |
Annual Sum or Average | 3965.83 | 0.64 | 2583.41 | 13.23 | 561.17 | 3660.50 | 1378.42 | 14.15 | 345.67 | 3203.50 | ||
Minimum of Months | 226.83 | 0.62 | 0.61 | 1167.42 | 9.51 | 0.00 | 188.67 | 746.46 | 11.70 | 0.00 | 144.67 | |
Maximum of Months | 434.17 | 0.66 | 0.61 | 4046.53 | 18.01 | 80.33 | 408.17 | 1880.61 | 19.15 | 73.67 | 380.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.67 | 0.61 | 01-JAN-09:50 | 482.76 | 0.00 | 0.00 | 168.17 | 301.50 | 0.00 | 0.00 | 76.00 |
February | 275.00 | 0.65 | 0.61 | 01-FEB-10:20 | 527.23 | 0.00 | 0.00 | 207.67 | 343.83 | 0.00 | 0.00 | 137.83 |
March | 304.00 | 0.63 | 0.61 | 01-MAR-07:00 | 841.78 | 0.00 | 0.00 | 297.50 | 519.84 | 0.00 | 0.00 | 249.50 |
April | 325.17 | 0.63 | 0.61 | 01-APR-08:39 | 877.01 | 0.00 | 0.00 | 340.67 | 550.19 | 0.00 | 0.00 | 286.00 |
May | 385.83 | 0.62 | 0.61 | 01-MAY-05:49 | 1096.79 | 0.00 | 0.00 | 403.00 | 671.24 | 0.00 | 0.00 | 366.50 |
June | 434.17 | 0.63 | 0.61 | 01-JUN-13:39 | 1139.75 | 0.00 | 0.00 | 431.00 | 658.23 | 0.00 | 0.00 | 397.00 |
July | 417.33 | 0.62 | 0.61 | 01-JUL-06:40 | 1116.59 | 0.00 | 0.00 | 418.50 | 667.83 | 0.00 | 0.00 | 387.83 |
August | 421.33 | 0.63 | 0.61 | 01-AUG-05:40 | 857.34 | 0.00 | 0.00 | 390.17 | 575.47 | 0.00 | 0.00 | 361.17 |
September | 352.17 | 0.64 | 0.61 | 01-SEP-06:49 | 695.32 | 0.00 | 0.00 | 307.67 | 455.96 | 0.00 | 0.00 | 248.33 |
October | 317.67 | 0.65 | 0.61 | 01-OCT-07:49 | 572.65 | 0.00 | 0.00 | 247.17 | 369.00 | 0.00 | 0.00 | 175.17 |
November | 269.50 | 0.67 | 0.61 | 01-NOV-08:09 | 452.11 | 0.00 | 0.00 | 178.67 | 287.75 | 0.00 | 0.00 | 72.67 |
December | 236.83 | 0.68 | 0.61 | 01-DEC-09:09 | 390.32 | 0.00 | 0.00 | 144.33 | 248.21 | 0.00 | 0.00 | 20.67 |
Annual Sum or Average | 3965.83 | 0.64 | 802.32 | 0.00 | 0.00 | 3534.50 | 499.25 | 0.00 | 0.00 | 2778.67 | ||
Minimum of Months | 226.83 | 0.62 | 0.61 | 390.32 | 0.00 | 0.00 | 144.33 | 248.21 | 0.00 | 0.00 | 20.67 | |
Maximum of Months | 434.17 | 0.68 | 0.61 | 1139.75 | 0.00 | 0.00 | 431.00 | 671.24 | 0.00 | 0.00 | 397.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.66 | 0.61 | 01-JAN-09:50 | 1391.20 | 17.12 | 69.17 | 194.67 | 884.35 | 17.98 | 58.17 | 152.17 |
February | 275.00 | 0.64 | 0.61 | 01-FEB-10:20 | 1852.71 | 16.86 | 76.50 | 229.00 | 979.87 | 16.08 | 48.67 | 196.00 |
March | 304.00 | 0.63 | 0.61 | 01-MAR-07:00 | 2486.49 | 16.14 | 68.83 | 304.50 | 1443.87 | 17.43 | 62.17 | 270.67 |
April | 325.17 | 0.63 | 0.61 | 01-APR-08:39 | 2604.61 | 13.55 | 48.50 | 333.83 | 1548.87 | 12.65 | 0.00 | 297.83 |
May | 385.83 | 0.63 | 0.61 | 01-MAY-06:19 | 2822.92 | 10.23 | 0.00 | 388.33 | 1814.51 | 12.68 | 1.33 | 350.33 |
June | 434.17 | 0.63 | 0.61 | 01-JUN-13:39 | 3133.54 | 9.69 | 0.00 | 408.17 | 1441.93 | 14.65 | 47.83 | 372.50 |
July | 417.33 | 0.63 | 0.61 | 01-JUL-06:40 | 3654.71 | 9.99 | 3.67 | 396.67 | 1679.75 | 14.08 | 31.50 | 364.17 |
August | 421.33 | 0.64 | 0.61 | 01-AUG-06:30 | 2672.36 | 12.59 | 56.83 | 372.83 | 1577.92 | 11.84 | 0.00 | 339.83 |
September | 352.17 | 0.64 | 0.61 | 01-SEP-06:00 | 2626.42 | 14.71 | 72.33 | 314.00 | 1146.45 | 12.21 | 5.50 | 277.17 |
October | 317.67 | 0.64 | 0.61 | 01-OCT-07:00 | 1610.76 | 13.91 | 53.67 | 270.33 | 1000.67 | 15.61 | 49.33 | 231.33 |
November | 269.50 | 0.65 | 0.61 | 01-NOV-08:20 | 1569.91 | 16.78 | 78.83 | 211.67 | 867.46 | 16.20 | 52.50 | 170.67 |
December | 236.83 | 0.66 | 0.61 | 01-DEC-09:09 | 953.07 | 14.74 | 54.00 | 192.67 | 623.38 | 16.44 | 49.83 | 145.50 |
Annual Sum or Average | 3965.83 | 0.64 | 2424.25 | 13.38 | 582.33 | 3616.67 | 1313.13 | 14.51 | 406.83 | 3168.17 | ||
Minimum of Months | 226.83 | 0.63 | 0.61 | 953.07 | 9.69 | 0.00 | 192.67 | 623.38 | 11.84 | 0.00 | 145.50 | |
Maximum of Months | 434.17 | 0.66 | 0.61 | 3654.71 | 17.12 | 78.83 | 408.17 | 1814.51 | 17.98 | 62.17 | 372.50 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.359462E+11 | 77223.19 | 10-JAN-22:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.191448E+11 | 59099.27 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.928950E+10 | 49472.09 | 04-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.155121E+10 | 24545.25 | 29-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.101916E+10 | 17862.57 | 08-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17241311.64 | 5359.79 | 16-JUN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.181539E+09 | 8158.74 | 19-SEP-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.114771E+10 | 21721.24 | 10-OCT-06:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.632012E+10 | 37788.62 | 27-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.204446E+11 | 64617.50 | 29-DEC-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.950620E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.359462E+11 | 77223.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.355283E+10 | 13893.53 | 18-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.114880E+10 | 13432.91 | 06-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.225372E+09 | 13428.52 | 04-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 908773.90 | 1011.62 | 08-MAY-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.109191E+09 | 13349.68 | 28-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.765228E+09 | 14428.36 | 16-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.580233E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.355283E+10 | 14428.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.279642E+10 | 15927.17 | 18-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109597E+10 | 15715.20 | 09-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.284991E+09 | 15732.72 | 06-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 9710538.77 | 10631.88 | 29-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 10426692.84 | 7501.96 | 22-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5079564.11 | 1059.42 | 05-OCT-05:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.245383E+09 | 15928.05 | 29-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.108031E+10 | 16124.03 | 16-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.552830E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.279642E+10 | 16124.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.344161E+10 | 22815.00 | 05-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.110092E+10 | 22987.32 | 23-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.364155E+09 | 21293.77 | 06-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 29962773.53 | 22944.12 | 29-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 66971979.07 | 22745.38 | 08-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 20148431.67 | 18223.04 | 10-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.323494E+09 | 22854.77 | 13-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.109585E+10 | 22989.16 | 27-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.644312E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.344161E+10 | 22989.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.177689E+10 | 15548.51 | 07-JAN-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.315249E+09 | 15526.46 | 04-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 33267138.28 | 15523.06 | 04-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 36351.49 | 47.09 | 08-MAY-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11896250.85 | 12437.06 | 27-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 88647649.50 | 15523.55 | 29-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.222598E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.177689E+10 | 15548.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.412139E+12 | 821922.10 | 10-JAN-22:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.237518E+12 | 642437.80 | 01-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.146071E+12 | 554469.74 | 06-MAR-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.397552E+11 | 268341.84 | 29-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.245571E+11 | 208587.81 | 08-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.516293E+09 | 89724.25 | 16-JUN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.472621E+10 | 105370.27 | 19-SEP-06:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.277848E+11 | 268431.33 | 10-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.105955E+12 | 442590.34 | 27-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.276158E+12 | 702129.38 | 29-DEC-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.127518E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.412139E+12 | 821922.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.177225E+11 | 627186.60 | 10-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.539129E+10 | 623583.44 | 04-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.164207E+10 | 626609.21 | 06-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.117716E+10 | 623703.48 | 27-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.686895E+10 | 626365.54 | 26-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.328020E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.177225E+11 | 627186.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.107897E+12 | 128333.13 | 23-JAN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.549464E+11 | 128046.24 | 06-FEB-06:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.270857E+11 | 136863.81 | 30-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.444982E+10 | 137481.71 | 11-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.332893E+10 | 135536.67 | 22-MAY-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.693012E+09 | 136461.57 | 19-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.390158E+10 | 138178.25 | 04-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.265248E+11 | 137642.64 | 09-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.694302E+11 | 128136.69 | 18-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.298257E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.107897E+12 | 138178.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.736487E+11 | 180557.99 | 12-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.363315E+11 | 179899.67 | 06-FEB-05:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189988E+11 | 179389.85 | 09-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.388159E+10 | 187587.26 | 19-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.292338E+10 | 188641.90 | 22-MAY-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16768493.07 | 12686.83 | 17-JUN-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11258142.49 | 12508.47 | 18-AUG-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.780973E+09 | 175141.47 | 19-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.346639E+10 | 190238.36 | 05-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.205103E+11 | 188471.66 | 06-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.497829E+11 | 180081.16 | 18-DEC-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.210352E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.736487E+11 | 190238.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.739304E+11 | 217066.84 | 12-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.307112E+11 | 217640.43 | 07-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.176579E+11 | 216674.30 | 06-MAR-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.403658E+10 | 231135.29 | 19-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.412429E+10 | 230210.68 | 22-MAY-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 66429610.49 | 18725.11 | 17-JUN-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11135599.32 | 8067.71 | 18-AUG-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.558798E+09 | 190099.44 | 19-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195904E+10 | 214779.99 | 10-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.171427E+11 | 216064.83 | 27-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.435537E+11 | 216661.63 | 27-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.193752E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.739304E+11 | 231135.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.677935E+11 | 193279.31 | 10-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.310957E+11 | 192684.61 | 07-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.167459E+11 | 192203.54 | 04-MAR-05:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.302197E+10 | 191186.67 | 29-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.251494E+10 | 194938.25 | 22-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 54473562.65 | 21834.79 | 17-JUN-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 24534753.36 | 8083.96 | 18-AUG-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.664311E+09 | 146259.65 | 19-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.276904E+10 | 190579.48 | 10-OCT-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.165645E+11 | 192269.91 | 28-NOV-05:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.410642E+11 | 193979.15 | 27-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.182313E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.677935E+11 | 194938.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.475822E+11 | 89291.25 | 10-JAN-22:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.266925E+11 | 71775.06 | 01-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.179112E+11 | 63371.74 | 04-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.608711E+10 | 33144.29 | 29-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.359370E+10 | 25658.61 | 08-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.217530E+09 | 11729.91 | 16-JUN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6636875.60 | 2834.85 | 18-AUG-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.120954E+10 | 15289.35 | 19-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.456502E+10 | 32470.60 | 10-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.135043E+11 | 46870.61 | 27-NOV-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.325771E+11 | 78193.18 | 29-DEC-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.153947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.475822E+11 | 89291.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.177617E+11 | 76617.28 | 02-JAN-05:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.792566E+10 | 76746.28 | 21-FEB-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.446522E+10 | 76522.11 | 20-MAR-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.705685E+09 | 75591.69 | 10-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.108856E+10 | 76549.39 | 01-MAY-04:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 25912539.90 | 6247.06 | 19-SEP-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.734007E+09 | 76680.94 | 10-OCT-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.493974E+10 | 76413.69 | 20-NOV-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.113185E+11 | 76493.73 | 26-DEC-04:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.489649E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.177617E+11 | 76746.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.189921E+11 | 16898.60 | 14-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.107953E+11 | 16882.30 | 13-FEB-05:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.741120E+10 | 16875.57 | 20-MAR-04:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.246519E+10 | 16869.23 | 10-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.169420E+10 | 16848.13 | 09-MAY-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 65153692.39 | 16703.70 | 17-JUN-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 38009849.06 | 15932.93 | 18-AUG-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.715598E+09 | 16867.36 | 19-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.246800E+10 | 16896.49 | 10-OCT-04:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.761212E+10 | 16893.94 | 24-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.144193E+11 | 16882.61 | 08-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.666761E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.189921E+11 | 16898.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.121892E+11 | 18046.58 | 05-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.641270E+10 | 18067.01 | 17-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.427926E+10 | 18087.61 | 22-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.142984E+10 | 18048.03 | 19-APR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.101221E+10 | 18054.97 | 08-MAY-04:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 48257316.41 | 17942.87 | 17-JUN-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 159125.72 | 157.51 | 05-JUL-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 26524074.57 | 10311.68 | 18-AUG-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.435229E+09 | 17927.89 | 19-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.138058E+10 | 18059.61 | 11-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.473079E+10 | 18049.61 | 30-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.928495E+10 | 18077.91 | 20-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.412297E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 159125.72 | 157.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.121892E+11 | 18087.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.138820E+11 | 23496.26 | 13-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.657913E+10 | 23532.50 | 15-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.504531E+10 | 23510.79 | 10-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.199440E+10 | 23435.57 | 29-APR-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.166235E+10 | 23472.79 | 09-MAY-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.134810E+09 | 23326.23 | 17-JUN-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1344682.52 | 671.62 | 08-JUL-05:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 49993049.84 | 15949.98 | 18-AUG-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.523839E+09 | 23366.77 | 12-SEP-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.137462E+10 | 23530.31 | 10-OCT-04:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.470665E+10 | 23490.22 | 06-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.993846E+10 | 23502.42 | 20-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.458929E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1344682.52 | 671.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.138820E+11 | 23532.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.116090E+11 | 20627.60 | 25-JAN-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.567579E+10 | 20626.95 | 09-FEB-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.401396E+10 | 20635.64 | 08-MAR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.130538E+10 | 20551.32 | 29-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.966751E+09 | 20603.16 | 22-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 73113707.56 | 12437.52 | 17-JUN-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 36788153.72 | 10047.98 | 18-AUG-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.458428E+09 | 20551.60 | 19-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.132745E+10 | 20601.63 | 10-OCT-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.400698E+10 | 20644.60 | 28-NOV-05:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.786631E+10 | 20641.73 | 01-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.373400E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.116090E+11 | 20644.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS HEATING COIL
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.111315E+10 | 31747.01 | 10-JAN-22:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 708736.03 | 698.84 | 04-FEB-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.111386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.111315E+10 | 31747.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT HEATING COIL
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT HEATING COIL
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID HEATING COIL
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP HEATING COIL
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID_SUPPHEATCOIL
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.585539E+09 | 0.585539E+09 | 39637.15 | 27-FEB-15:30 | 39637.15 | 0.00 |
March | 0.00 | 0.00 | 31058141.34 | 31058141.34 | 6585.09 | 14-MAR-13:30 | 6585.09 | 0.00 |
April | 0.00 | 0.00 | 0.618598E+10 | 0.618598E+10 | 79355.46 | 07-APR-14:00 | 79355.46 | 0.00 |
May | 0.00 | 0.00 | 0.169802E+11 | 0.169802E+11 | 105058.47 | 19-MAY-15:20 | 105058.47 | 0.02 |
June | 0.00 | 0.00 | 0.565611E+11 | 0.565080E+11 | 121375.46 | 29-JUN-14:50 | 121375.46 | 0.17 |
July | 0.00 | 0.00 | 0.975288E+11 | 0.973455E+11 | 147725.16 | 17-JUL-15:20 | 147725.16 | 0.31 |
August | 0.00 | 0.00 | 0.904464E+11 | 0.904464E+11 | 149489.42 | 07-AUG-15:20 | 149489.42 | 0.14 |
September | 0.00 | 0.00 | 0.365519E+11 | 0.353562E+11 | 184789.40 | 07-SEP-15:00 | 98110.00 | 0.10 |
October | 0.00 | 0.00 | 0.981394E+10 | 0.981394E+10 | 97079.12 | 18-OCT-15:50 | 97079.12 | 0.00 |
November | 0.00 | 0.00 | 0.496941E+09 | 0.496941E+09 | 16582.30 | 17-NOV-17:00 | 16582.30 | 0.00 |
December | 0.00 | 0.00 | 222.89 | 222.89 | 0.37 | 06-DEC-08:00 | 0.37 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.315182E+12 | 0.313750E+12 | 0.06 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.975288E+11 | 0.973455E+11 | 184789.40 | 149489.42 | 0.31 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 19694.50 | 19694.50 | 5.00 | 23-JAN-06:03 | 5.00 | 0.00 |
February | 0.00 | 0.00 | 0.391301E+10 | 0.391301E+10 | 260343.98 | 27-FEB-13:40 | 260343.98 | 0.00 |
March | 0.00 | 0.00 | 48397356.45 | 48397356.45 | 11665.00 | 14-MAR-13:40 | 11665.00 | 0.00 |
April | 0.00 | 0.00 | 0.421678E+11 | 0.421678E+11 | 590995.09 | 06-APR-16:00 | 590995.09 | 0.00 |
May | 0.00 | 0.00 | 0.142546E+12 | 0.142546E+12 | 995840.49 | 19-MAY-15:30 | 995840.49 | 0.02 |
June | 0.00 | 0.00 | 0.478291E+12 | 0.477854E+12 | 1145978.91 | 29-JUN-14:50 | 1145978.91 | 0.16 |
July | 0.00 | 0.00 | 0.807487E+12 | 0.806461E+12 | 1338274.28 | 17-JUL-15:30 | 1338274.28 | 0.27 |
August | 0.00 | 0.00 | 0.700062E+12 | 0.700062E+12 | 1256519.71 | 10-AUG-15:40 | 1256519.71 | 0.12 |
September | 0.00 | 0.00 | 0.318686E+12 | 0.307948E+12 | 1711545.18 | 07-SEP-15:00 | 908775.70 | 0.09 |
October | 0.00 | 0.00 | 0.744339E+11 | 0.744339E+11 | 798022.48 | 18-OCT-15:20 | 798022.48 | 0.00 |
November | 0.00 | 0.00 | 0.339142E+10 | 0.339142E+10 | 115588.23 | 03-NOV-14:00 | 115588.23 | 0.00 |
December | 0.00 | 0.00 | 28959.19 | 28959.19 | 1.34 | 20-DEC-06:01 | 1.34 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.257103E+13 | 0.255883E+13 | 0.06 | |||
Minimum of Months | 0.00 | 0.00 | 19694.50 | 19694.50 | 1.34 | 1.34 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.807487E+12 | 0.806461E+12 | 1711545.18 | 1338274.28 | 0.27 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 1220.61 | 1220.61 | 0.74 | 06-JAN-06:01 | 0.74 | 0.00 |
February | 0.00 | 0.00 | 0.288330E+09 | 0.288330E+09 | 20707.13 | 26-FEB-14:31 | 20707.13 | 0.00 |
March | 0.00 | 0.00 | 1270391.95 | 1270391.95 | 1268.25 | 04-MAR-06:01 | 1268.25 | 0.00 |
April | 0.00 | 0.00 | 0.382489E+10 | 0.382489E+10 | 58522.14 | 06-APR-16:00 | 58522.14 | 0.00 |
May | 0.00 | 0.00 | 0.147627E+11 | 0.147627E+11 | 119736.54 | 19-MAY-15:30 | 119736.54 | 0.02 |
June | 0.00 | 0.00 | 0.525532E+11 | 0.524987E+11 | 136614.94 | 29-JUN-15:00 | 136614.94 | 0.15 |
July | 0.00 | 0.00 | 0.892413E+11 | 0.891506E+11 | 163854.81 | 17-JUL-15:30 | 163854.81 | 0.27 |
August | 0.00 | 0.00 | 0.751464E+11 | 0.751464E+11 | 150928.45 | 07-AUG-15:40 | 150928.45 | 0.12 |
September | 0.00 | 0.00 | 0.324631E+11 | 0.314012E+11 | 174294.92 | 07-SEP-15:20 | 100232.75 | 0.09 |
October | 0.00 | 0.00 | 0.625453E+10 | 0.625453E+10 | 81165.67 | 18-OCT-15:00 | 81165.67 | 0.00 |
November | 0.00 | 0.00 | 0.248191E+09 | 0.248191E+09 | 9292.84 | 04-NOV-14:00 | 9292.84 | 0.00 |
December | 0.00 | 0.00 | 63355.11 | 63355.11 | 518.69 | 11-DEC-04:52 | 518.69 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.274784E+12 | 0.273577E+12 | 0.05 | |||
Minimum of Months | 0.00 | 0.00 | 1220.61 | 1220.61 | 0.74 | 0.74 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.892413E+11 | 0.891506E+11 | 174294.92 | 163854.81 | 0.27 |
Report: CoilReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 109714.94 | 109714.94 | 681.13 | 24-JAN-05:01 | 681.13 | 0.00 |
February | 0.00 | 0.00 | 0.239590E+09 | 0.239590E+09 | 21759.88 | 27-FEB-15:00 | 21759.88 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.207821E+10 | 0.207821E+10 | 45040.95 | 07-APR-14:00 | 45040.95 | 0.00 |
May | 0.00 | 0.00 | 0.809844E+10 | 0.809844E+10 | 55269.49 | 29-MAY-14:13 | 55269.49 | 0.02 |
June | 0.00 | 0.00 | 0.288063E+11 | 0.287938E+11 | 63606.65 | 26-JUN-11:00 | 63606.65 | 0.12 |
July | 0.00 | 0.00 | 0.495170E+11 | 0.494983E+11 | 99715.52 | 19-JUL-05:03 | 57581.33 | 0.22 |
August | 0.00 | 0.00 | 0.460405E+11 | 0.460405E+11 | 99323.84 | 06-AUG-16:56 | 99323.84 | 0.12 |
September | 0.00 | 0.00 | 0.188259E+11 | 0.184981E+11 | 86263.91 | 07-SEP-14:50 | 52031.77 | 0.08 |
October | 0.00 | 0.00 | 0.532649E+10 | 0.532649E+10 | 54826.08 | 18-OCT-14:00 | 54826.08 | 0.00 |
November | 0.00 | 0.00 | 60763290.06 | 60763290.06 | 23487.69 | 17-NOV-06:02 | 23487.69 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.158993E+12 | 0.158634E+12 | 0.05 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.495170E+11 | 0.494983E+11 | 99715.52 | 99323.84 | 0.22 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.360020E+12 | 0.326531E+12 | 142257.39 | 02-JAN-06:08 | 128993.82 | 0.00 |
February | 0.00 | 0.00 | 0.573981E+12 | 0.520370E+12 | 244851.71 | 27-FEB-22:03 | 221601.24 | 0.00 |
March | 0.00 | 0.00 | 0.908998E+12 | 0.826277E+12 | 440370.69 | 31-MAR-24:00 | 399931.55 | 0.00 |
April | 0.00 | 0.00 | 0.114382E+13 | 0.104186E+13 | 449292.35 | 24-APR-21:02 | 406917.88 | 0.00 |
May | 0.00 | 0.00 | 0.374342E+12 | 0.341479E+12 | 237560.68 | 31-MAY-24:00 | 217091.81 | 0.00 |
June | 0.00 | 0.00 | 0.618878E+12 | 0.571988E+12 | 329651.37 | 30-JUN-24:00 | 309014.46 | 0.00 |
July | 0.00 | 0.00 | 0.893602E+12 | 0.840780E+12 | 426325.66 | 31-JUL-24:00 | 399973.90 | 0.00 |
August | 0.00 | 0.00 | 0.116066E+13 | 0.107929E+13 | 456969.36 | 04-AUG-00:03 | 410781.16 | 0.00 |
September | 0.00 | 0.00 | 0.365621E+12 | 0.335552E+12 | 238502.81 | 30-SEP-24:00 | 217102.12 | 0.00 |
October | 0.00 | 0.00 | 0.647772E+12 | 0.589409E+12 | 340513.03 | 31-OCT-24:00 | 309509.21 | 0.00 |
November | 0.00 | 0.00 | 0.888341E+12 | 0.805395E+12 | 348467.43 | 06-NOV-22:03 | 315034.95 | 0.00 |
December | 0.00 | 0.00 | 0.118105E+13 | 0.107302E+13 | 448111.69 | 07-DEC-24:00 | 406313.88 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.911709E+13 | 0.835196E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.360020E+12 | 0.326531E+12 | 142257.39 | 128993.82 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.118105E+13 | 0.107929E+13 | 456969.36 | 410781.16 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.273551E+10 | 0.273519E+10 | 2121.47 | 01-JAN-16:05 | 2114.85 | 0.00 |
February | 0.00 | 0.00 | 0.810072E+10 | 0.810072E+10 | 4895.59 | 26-FEB-17:20 | 4895.59 | 0.00 |
March | 0.00 | 0.00 | 0.148854E+11 | 0.148854E+11 | 7460.24 | 31-MAR-24:00 | 7460.24 | 0.00 |
April | 0.00 | 0.00 | 0.199822E+11 | 0.199747E+11 | 8870.63 | 22-APR-18:10 | 8870.63 | 0.00 |
May | 0.00 | 0.00 | 0.557500E+10 | 0.555338E+10 | 4117.84 | 31-MAY-24:00 | 4117.84 | 0.00 |
June | 0.00 | 0.00 | 0.108501E+11 | 0.107701E+11 | 5979.31 | 30-JUN-23:55 | 5979.31 | 0.00 |
July | 0.00 | 0.00 | 0.165225E+11 | 0.164333E+11 | 7877.72 | 31-JUL-23:40 | 7877.72 | 0.00 |
August | 0.00 | 0.00 | 0.215187E+11 | 0.214556E+11 | 8817.72 | 05-AUG-20:12 | 8817.72 | 0.00 |
September | 0.00 | 0.00 | 0.568889E+10 | 0.560670E+10 | 3949.39 | 30-SEP-24:00 | 3949.39 | 0.00 |
October | 0.00 | 0.00 | 0.105085E+11 | 0.104978E+11 | 5599.16 | 31-OCT-24:00 | 5599.16 | 0.00 |
November | 0.00 | 0.00 | 0.145912E+11 | 0.145895E+11 | 6471.71 | 12-NOV-16:25 | 6471.71 | 0.00 |
December | 0.00 | 0.00 | 0.194362E+11 | 0.194359E+11 | 8265.84 | 10-DEC-16:10 | 8265.84 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.150395E+12 | 0.150038E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.273551E+10 | 0.273519E+10 | 2121.47 | 2114.85 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.215187E+11 | 0.214556E+11 | 8870.63 | 8870.63 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.602116E+10 | 0.601880E+10 | 16872.55 | 13-JAN-16:30 | 16872.55 | 0.00 |
February | 0.00 | 0.00 | 0.566069E+11 | 0.566069E+11 | 42293.97 | 28-FEB-17:00 | 42293.97 | 0.00 |
March | 0.00 | 0.00 | 0.122668E+12 | 0.122668E+12 | 64620.06 | 31-MAR-23:30 | 64620.06 | 0.00 |
April | 0.00 | 0.00 | 0.179156E+12 | 0.179079E+12 | 82177.38 | 22-APR-18:10 | 82177.38 | 0.00 |
May | 0.00 | 0.00 | 0.449057E+11 | 0.446933E+11 | 39022.52 | 31-MAY-24:00 | 39022.52 | 0.00 |
June | 0.00 | 0.00 | 0.100151E+12 | 0.993533E+11 | 58313.68 | 30-JUN-23:55 | 58313.68 | 0.00 |
July | 0.00 | 0.00 | 0.156401E+12 | 0.155509E+12 | 76581.41 | 31-JUL-23:55 | 76581.41 | 0.00 |
August | 0.00 | 0.00 | 0.202567E+12 | 0.201934E+12 | 83842.69 | 03-AUG-19:00 | 83842.69 | 0.00 |
September | 0.00 | 0.00 | 0.480619E+11 | 0.472573E+11 | 35004.81 | 30-SEP-23:40 | 35004.81 | 0.00 |
October | 0.00 | 0.00 | 0.873500E+11 | 0.872425E+11 | 47223.43 | 31-OCT-24:00 | 47223.43 | 0.00 |
November | 0.00 | 0.00 | 0.119276E+12 | 0.119258E+12 | 59758.21 | 03-NOV-16:00 | 59209.11 | 0.00 |
December | 0.00 | 0.00 | 0.155926E+12 | 0.155923E+12 | 74146.89 | 06-DEC-16:10 | 73845.83 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.127909E+13 | 0.127554E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.602116E+10 | 0.601880E+10 | 16872.55 | 16872.55 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.202567E+12 | 0.201934E+12 | 83842.69 | 83842.69 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.158707E+09 | 0.158707E+09 | 1591.69 | 13-JAN-16:30 | 1591.69 | 0.00 |
February | 0.00 | 0.00 | 0.403903E+10 | 0.403903E+10 | 4149.29 | 28-FEB-17:00 | 4149.29 | 0.00 |
March | 0.00 | 0.00 | 0.105223E+11 | 0.105223E+11 | 6089.86 | 28-MAR-17:50 | 6089.86 | 0.00 |
April | 0.00 | 0.00 | 0.166314E+11 | 0.166238E+11 | 8275.47 | 25-APR-18:00 | 8275.47 | 0.00 |
May | 0.00 | 0.00 | 0.376036E+10 | 0.373952E+10 | 3830.51 | 31-MAY-24:00 | 3830.51 | 0.00 |
June | 0.00 | 0.00 | 0.978624E+10 | 0.970669E+10 | 5842.32 | 30-JUN-23:55 | 5842.32 | 0.00 |
July | 0.00 | 0.00 | 0.155832E+11 | 0.154941E+11 | 7665.59 | 31-JUL-23:55 | 7665.59 | 0.00 |
August | 0.00 | 0.00 | 0.201131E+11 | 0.200499E+11 | 8542.39 | 05-AUG-20:00 | 8542.39 | 0.00 |
September | 0.00 | 0.00 | 0.419403E+10 | 0.411506E+10 | 3426.63 | 04-SEP-17:33 | 3426.63 | 0.00 |
October | 0.00 | 0.00 | 0.720339E+10 | 0.719291E+10 | 4530.26 | 18-OCT-16:50 | 4530.26 | 0.00 |
November | 0.00 | 0.00 | 0.991135E+10 | 0.990963E+10 | 5871.86 | 03-NOV-16:00 | 5817.01 | 0.00 |
December | 0.00 | 0.00 | 0.135852E+11 | 0.135849E+11 | 7293.12 | 06-DEC-16:10 | 7264.54 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.115488E+12 | 0.115137E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.158707E+09 | 0.158707E+09 | 1591.69 | 1591.69 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.201131E+11 | 0.200499E+11 | 8542.39 | 8542.39 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 343087.60 | 1978568.98 | 09-JAN-07:10 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 198552.18 | 1810107.54 | 07-FEB-06:01 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 104575.63 | 1656832.32 | 06-MAR-06:01 |
April | 0.00 | 0.00 | 01-APR-00:10 | 27136.01 | 1264749.54 | 19-APR-05:02 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 18040.48 | 1482123.24 | 22-MAY-04:01 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 462.64 | 127675.22 | 17-JUN-04:02 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.49 | 599.67 | 08-JUL-05:20 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 76.63 | 96432.44 | 18-AUG-05:03 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 4209.59 | 1235412.06 | 19-SEP-05:02 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 19667.28 | 1231242.84 | 11-OCT-05:01 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 89978.26 | 1634490.46 | 27-NOV-06:02 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 221307.46 | 1877892.63 | 26-DEC-05:01 |
Annual Sum or Average | 0.00 | 85267.07 | ||||
Minimum of Months | 0.00 | 0.00 | 0.49 | 599.67 | ||
Maximum of Months | 0.00 | 0.00 | 343087.60 | 1978568.98 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 377.24 | 22824.41 | 07-JAN-03:00 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 5081.88 | 684129.01 | 27-FEB-15:30 | 0.00 | 0.00 | 01-FEB-00:05 |
March | 1737.59 | 68508.81 | 14-MAR-13:30 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 41636.97 | 1147816.12 | 07-APR-13:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 120689.98 | 1284008.00 | 19-MAY-15:30 | 171.97 | 281830.03 | 22-MAY-03:10 |
June | 331289.84 | 1469148.71 | 29-JUN-14:50 | 44.71 | 139991.23 | 11-JUN-19:42 |
July | 507544.63 | 1733625.68 | 17-JUL-15:30 | 61.30 | 106501.76 | 26-JUL-23:53 |
August | 443842.27 | 1630310.94 | 07-AUG-15:40 | 20.12 | 48820.56 | 20-AUG-20:25 |
September | 242082.44 | 2275676.93 | 07-SEP-15:00 | 46.06 | 160713.38 | 24-SEP-08:53 |
October | 65782.19 | 1157586.76 | 16-OCT-14:50 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 5268.28 | 282016.57 | 17-NOV-17:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 581.10 | 23132.41 | 11-DEC-04:52 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 148240.61 | 28.98 | ||||
Minimum of Months | 377.24 | 22824.41 | 0.00 | 0.00 | ||
Maximum of Months | 507544.63 | 2275676.93 | 171.97 | 281830.03 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 1.21 | 24-JAN-05:01 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 2463.08 | 427062.11 | 27-FEB-13:30 | 0.00 | 0.00 | 01-FEB-00:05 |
March | 47.10 | 28152.75 | 14-MAR-13:30 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 25088.59 | 878243.98 | 06-APR-16:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 78390.61 | 1274039.30 | 19-MAY-15:30 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 264754.12 | 1459678.07 | 29-JUN-14:50 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 423177.48 | 2180299.88 | 19-JUL-05:03 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 369916.03 | 1622263.73 | 07-AUG-15:40 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 176655.44 | 2280015.20 | 07-SEP-15:00 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 42469.84 | 1161411.97 | 18-OCT-15:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 2047.64 | 183992.95 | 01-NOV-04:01 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 0.04 | 588.74 | 11-DEC-04:52 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 116327.05 | 0.00 | ||||
Minimum of Months | 0.00 | 1.21 | 0.00 | 0.00 | ||
Maximum of Months | 423177.48 | 2280015.20 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 176767.77 | 199897.32 | 13-JAN-16:30 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 337425.94 | 604470.58 | 27-FEB-16:00 | 0.00 | 0.00 | 01-FEB-00:05 |
March | 494873.97 | 644974.42 | 31-MAR-24:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 702091.86 | 1321310.43 | 07-APR-14:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 255793.62 | 971082.33 | 20-MAY-16:00 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 573482.42 | 1370645.00 | 29-JUN-15:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 966949.97 | 1947680.29 | 17-JUL-16:00 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 1121157.93 | 2066020.76 | 06-AUG-16:00 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 338382.19 | 1240861.18 | 02-SEP-17:00 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 385968.62 | 955868.82 | 18-OCT-15:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 504985.36 | 745592.46 | 17-NOV-17:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 638348.30 | 764174.98 | 10-DEC-02:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 543155.74 | 0.00 | ||||
Minimum of Months | 176767.77 | 199897.32 | 0.00 | 0.00 | ||
Maximum of Months | 1121157.93 | 2066020.76 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 17330.27 | 58846.21 | 31-JAN-13:00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 17709.67 | 59172.20 | 23-FEB-12:10 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 18546.04 | 59076.16 | 02-MAR-12:40 |
April | 0.00 | 0.00 | 01-APR-00:10 | 16883.78 | 57455.33 | 03-APR-11:50 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 16525.59 | 54969.25 | 01-MAY-11:20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15932.57 | 51686.41 | 01-JUN-11:30 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 14099.46 | 48654.43 | 03-JUL-11:50 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 14986.23 | 46968.27 | 01-AUG-12:00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 14316.35 | 48076.88 | 29-SEP-11:30 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14900.79 | 50878.85 | 31-OCT-12:00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 15950.96 | 54068.60 | 30-NOV-13:00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 16274.40 | 56867.58 | 29-DEC-12:40 |
Annual Sum or Average | 0.00 | 16112.13 | ||||
Minimum of Months | 0.00 | 0.00 | 14099.46 | 46968.27 | ||
Maximum of Months | 0.00 | 0.00 | 18546.04 | 59172.20 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 6.17 | 18559.79 | 18-JAN-04:02 | 403.21 | 82933.45 | 17-JAN-06:40 |
February | 2259.34 | 410832.06 | 27-FEB-15:30 | 929.94 | 113180.55 | 24-FEB-06:30 |
March | 85.57 | 22922.24 | 31-MAR-06:00 | 1966.67 | 132296.99 | 16-MAR-13:30 |
April | 24455.21 | 816823.01 | 07-APR-14:00 | 2242.68 | 116130.94 | 14-APR-13:30 |
May | 84322.46 | 2156967.09 | 19-MAY-15:30 | 1753.42 | 125290.83 | 03-MAY-15:50 |
June | 309844.26 | 2426608.04 | 20-JUN-15:40 | 1139.20 | 96526.46 | 17-JUN-05:30 |
July | 517346.26 | 2510037.86 | 17-JUL-15:30 | 745.26 | 55829.00 | 08-JUL-08:20 |
August | 445223.47 | 2198347.53 | 07-AUG-16:20 | 1633.54 | 79360.13 | 12-AUG-03:00 |
September | 210788.06 | 4295686.58 | 07-SEP-15:00 | 1530.70 | 111702.61 | 18-SEP-15:40 |
October | 42383.40 | 1855631.16 | 18-OCT-13:00 | 2007.13 | 131090.49 | 21-OCT-05:30 |
November | 1467.82 | 186962.36 | 17-NOV-17:00 | 2027.66 | 131507.52 | 09-NOV-07:00 |
December | 19.66 | 20931.89 | 07-DEC-15:20 | 783.71 | 130123.25 | 20-DEC-06:30 |
Annual Sum or Average | 137618.95 | 1431.03 | ||||
Minimum of Months | 6.17 | 18559.79 | 403.21 | 55829.00 | ||
Maximum of Months | 517346.26 | 4295686.58 | 2242.68 | 132296.99 |
Report: FanReportMonthly
For: CAV_BAS FAN
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.148648E+11 | 0.87 | 10146.22 | 01-JAN-00:20 | 1.59 |
February | 0.133007E+11 | 0.86 | 10146.22 | 01-FEB-06:02 | 1.60 |
March | 0.159412E+11 | 0.93 | 10146.22 | 01-MAR-05:01 | 1.59 |
April | 0.147896E+11 | 0.89 | 10146.22 | 01-APR-04:01 | 1.60 |
May | 0.158012E+11 | 0.92 | 10146.22 | 01-MAY-03:01 | 1.59 |
June | 0.157987E+11 | 0.95 | 10146.22 | 01-JUN-03:02 | 1.58 |
July | 0.157068E+11 | 0.91 | 10146.22 | 01-JUL-03:02 | 1.57 |
August | 0.172691E+11 | 1.01 | 10146.22 | 01-AUG-03:02 | 1.58 |
September | 0.161121E+11 | 0.97 | 10146.22 | 01-SEP-03:10 | 1.58 |
October | 0.157591E+11 | 0.92 | 10146.22 | 02-OCT-02:70 | 1.58 |
November | 0.150687E+11 | 0.91 | 10146.22 | 01-NOV-03:10 | 1.60 |
December | 0.147026E+11 | 0.86 | 10146.22 | 01-DEC-05:01 | 1.60 |
Annual Sum or Average | 0.185115E+12 | 0.92 | |||
Minimum of Months | 0.133007E+11 | 0.86 | 10146.22 | 1.57 | |
Maximum of Months | 0.172691E+11 | 1.01 | 10146.22 | 1.60 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.367808E+10 | 0.36 | 14708.45 | 18-JAN-06:01 | 1.59 |
February | 0.410923E+10 | 0.38 | 12546.37 | 23-FEB-06:01 | 1.44 |
March | 0.634041E+10 | 0.45 | 12866.36 | 08-MAR-06:01 | 1.46 |
April | 0.823325E+10 | 0.53 | 17909.52 | 24-APR-14:50 | 1.79 |
May | 0.746795E+10 | 0.49 | 15160.64 | 30-MAY-05:03 | 1.60 |
June | 0.119786E+11 | 0.67 | 20214.56 | 26-JUN-05:02 | 1.92 |
July | 0.150143E+11 | 0.77 | 23494.92 | 18-JUL-05:02 | 2.12 |
August | 0.164373E+11 | 0.84 | 23494.92 | 07-AUG-04:22 | 2.12 |
September | 0.852528E+10 | 0.54 | 23494.92 | 05-SEP-05:02 | 2.12 |
October | 0.737476E+10 | 0.47 | 16166.06 | 16-OCT-15:50 | 1.68 |
November | 0.595377E+10 | 0.43 | 13538.26 | 29-NOV-06:01 | 1.51 |
December | 0.493990E+10 | 0.38 | 14708.45 | 16-DEC-06:01 | 1.59 |
Annual Sum or Average | 0.100053E+12 | 0.53 | |||
Minimum of Months | 0.367808E+10 | 0.36 | 12546.37 | 1.44 | |
Maximum of Months | 0.164373E+11 | 0.84 | 23494.92 | 2.12 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.380767E+11 | 0.42 | 59060.55 | 09-JAN-05:11 | 0.97 |
February | 0.328571E+11 | 0.39 | 63708.03 | 28-FEB-16:00 | 1.01 |
March | 0.402777E+11 | 0.40 | 125618.36 | 30-MAR-05:02 | 1.51 |
April | 0.439482E+11 | 0.39 | 157210.95 | 19-APR-05:02 | 1.73 |
May | 0.541579E+11 | 0.43 | 169629.65 | 22-MAY-04:01 | 1.82 |
June | 0.902401E+11 | 0.58 | 188462.18 | 26-JUN-05:02 | 1.93 |
July | 0.110468E+12 | 0.63 | 217183.61 | 25-JUL-05:02 | 2.12 |
August | 0.106653E+12 | 0.62 | 217183.61 | 07-AUG-03:02 | 2.12 |
September | 0.649686E+11 | 0.48 | 217183.61 | 05-SEP-05:02 | 2.12 |
October | 0.454802E+11 | 0.38 | 135288.02 | 31-OCT-05:02 | 1.58 |
November | 0.360074E+11 | 0.37 | 153168.18 | 06-NOV-06:01 | 1.71 |
December | 0.360271E+11 | 0.40 | 59060.55 | 18-DEC-05:01 | 0.97 |
Annual Sum or Average | 0.699161E+12 | 0.46 | |||
Minimum of Months | 0.328571E+11 | 0.37 | 59060.55 | 0.97 | |
Maximum of Months | 0.110468E+12 | 0.63 | 217183.61 | 2.12 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.502493E+10 | 0.50 | 5529.26 | 12-JAN-05:01 | 0.87 |
February | 0.385781E+10 | 0.44 | 5529.26 | 01-FEB-06:02 | 0.87 |
March | 0.403028E+10 | 0.41 | 5529.26 | 04-MAR-06:12 | 0.88 |
April | 0.373414E+10 | 0.36 | 10661.51 | 25-APR-16:00 | 1.27 |
May | 0.484592E+10 | 0.40 | 16173.13 | 19-MAY-15:30 | 1.62 |
June | 0.843109E+10 | 0.52 | 19047.66 | 29-JUN-14:50 | 1.81 |
July | 0.107852E+11 | 0.58 | 24519.98 | 17-JUL-15:10 | 2.11 |
August | 0.984313E+10 | 0.56 | 22333.81 | 10-AUG-15:50 | 2.00 |
September | 0.551921E+10 | 0.43 | 17812.50 | 05-SEP-05:02 | 1.73 |
October | 0.365548E+10 | 0.35 | 9304.28 | 18-OCT-16:00 | 1.17 |
November | 0.374569E+10 | 0.40 | 5529.26 | 06-NOV-06:01 | 0.87 |
December | 0.451017E+10 | 0.46 | 5529.26 | 20-DEC-06:01 | 0.87 |
Annual Sum or Average | 0.679831E+11 | 0.45 | |||
Minimum of Months | 0.365548E+10 | 0.35 | 5529.26 | 0.87 | |
Maximum of Months | 0.107852E+11 | 0.58 | 24519.98 | 2.11 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BASEMENT SUPPLY FAN
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.107754E+12 | 1.54 | 40230.69 | 01-JAN-00:05 | 1.54 |
February | 0.973261E+11 | 1.54 | 40230.69 | 01-FEB-00:05 | 1.54 |
March | 0.107754E+12 | 1.54 | 40230.69 | 01-MAR-00:10 | 1.54 |
April | 0.104278E+12 | 1.54 | 40230.69 | 01-APR-00:10 | 1.54 |
May | 0.107754E+12 | 1.54 | 40230.69 | 01-MAY-00:05 | 1.54 |
June | 0.104278E+12 | 1.54 | 40230.69 | 01-JUN-00:10 | 1.54 |
July | 0.107754E+12 | 1.54 | 40230.69 | 01-JUL-00:10 | 1.54 |
August | 0.107754E+12 | 1.54 | 40230.69 | 01-AUG-00:05 | 1.54 |
September | 0.104278E+12 | 1.54 | 40230.69 | 01-SEP-00:03 | 1.54 |
October | 0.107754E+12 | 1.54 | 40230.69 | 01-OCT-00:10 | 1.54 |
November | 0.104278E+12 | 1.54 | 40230.69 | 01-NOV-00:10 | 1.54 |
December | 0.107754E+12 | 1.54 | 40230.69 | 01-DEC-00:10 | 1.54 |
Annual Sum or Average | 0.126872E+13 | 1.54 | |||
Minimum of Months | 0.973261E+11 | 1.54 | 40230.69 | 1.54 | |
Maximum of Months | 0.107754E+12 | 1.54 | 40230.69 | 1.54 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BOT SUPPLY FAN
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.168658E+10 | 1.05 | 629.70 | 01-JAN-00:05 | 1.05 |
February | 0.152336E+10 | 1.05 | 629.70 | 01-FEB-00:05 | 1.05 |
March | 0.168658E+10 | 1.05 | 629.70 | 01-MAR-00:10 | 1.05 |
April | 0.163217E+10 | 1.05 | 629.70 | 01-APR-00:10 | 1.05 |
May | 0.168658E+10 | 1.05 | 629.70 | 01-MAY-00:05 | 1.05 |
June | 0.163217E+10 | 1.05 | 629.70 | 01-JUN-00:10 | 1.05 |
July | 0.168658E+10 | 1.05 | 629.70 | 01-JUL-00:05 | 1.05 |
August | 0.168658E+10 | 1.05 | 629.70 | 01-AUG-00:05 | 1.05 |
September | 0.163217E+10 | 1.05 | 629.70 | 01-SEP-00:03 | 1.05 |
October | 0.168658E+10 | 1.05 | 629.70 | 01-OCT-00:10 | 1.05 |
November | 0.163217E+10 | 1.05 | 629.70 | 01-NOV-00:10 | 1.05 |
December | 0.168658E+10 | 1.05 | 629.70 | 01-DEC-00:10 | 1.05 |
Annual Sum or Average | 0.198581E+11 | 1.05 | |||
Minimum of Months | 0.152336E+10 | 1.05 | 629.70 | 1.05 | |
Maximum of Months | 0.168658E+10 | 1.05 | 629.70 | 1.05 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER MID SUPPLY FAN
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.161534E+11 | 1.05 | 6031.00 | 01-JAN-00:05 | 1.05 |
February | 0.145902E+11 | 1.05 | 6031.00 | 01-FEB-00:05 | 1.05 |
March | 0.161534E+11 | 1.05 | 6031.00 | 01-MAR-00:10 | 1.05 |
April | 0.156323E+11 | 1.05 | 6031.00 | 01-APR-00:10 | 1.05 |
May | 0.161534E+11 | 1.05 | 6031.00 | 01-MAY-00:05 | 1.05 |
June | 0.156323E+11 | 1.05 | 6031.00 | 01-JUN-00:10 | 1.05 |
July | 0.161534E+11 | 1.05 | 6031.00 | 01-JUL-00:05 | 1.05 |
August | 0.161534E+11 | 1.05 | 6031.00 | 01-AUG-00:05 | 1.05 |
September | 0.156323E+11 | 1.05 | 6031.00 | 01-SEP-00:03 | 1.05 |
October | 0.161534E+11 | 1.05 | 6031.00 | 01-OCT-00:10 | 1.05 |
November | 0.156323E+11 | 1.05 | 6031.00 | 01-NOV-00:10 | 1.05 |
December | 0.161534E+11 | 1.05 | 6031.00 | 01-DEC-00:10 | 1.05 |
Annual Sum or Average | 0.190194E+12 | 1.05 | |||
Minimum of Months | 0.145902E+11 | 1.05 | 6031.00 | 1.05 | |
Maximum of Months | 0.161534E+11 | 1.05 | 6031.00 | 1.05 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER TOP SUPPLY FAN
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.164513E+10 | 1.05 | 614.22 | 01-JAN-00:05 | 1.05 |
February | 0.148592E+10 | 1.05 | 614.22 | 01-FEB-00:05 | 1.05 |
March | 0.164513E+10 | 1.05 | 614.22 | 01-MAR-00:10 | 1.05 |
April | 0.159206E+10 | 1.05 | 614.22 | 01-APR-00:10 | 1.05 |
May | 0.164513E+10 | 1.05 | 614.22 | 01-MAY-00:05 | 1.05 |
June | 0.159206E+10 | 1.05 | 614.22 | 01-JUN-00:10 | 1.05 |
July | 0.164513E+10 | 1.05 | 614.22 | 01-JUL-00:05 | 1.05 |
August | 0.164513E+10 | 1.05 | 614.22 | 01-AUG-00:05 | 1.05 |
September | 0.159206E+10 | 1.05 | 614.22 | 01-SEP-00:03 | 1.05 |
October | 0.164513E+10 | 1.05 | 614.22 | 01-OCT-00:10 | 1.05 |
November | 0.159206E+10 | 1.05 | 614.22 | 01-NOV-00:10 | 1.05 |
December | 0.164513E+10 | 1.05 | 614.22 | 01-DEC-00:10 | 1.05 |
Annual Sum or Average | 0.193701E+11 | 1.05 | |||
Minimum of Months | 0.148592E+10 | 1.05 | 614.22 | 1.05 | |
Maximum of Months | 0.164513E+10 | 1.05 | 614.22 | 1.05 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.170182E+09 | 0.153164E+09 | 1239.68 | 09-JAN-07:02 | 1115.71 | 1115.71 | 46.82 | 12.92 |
February | 56688046.76 | 51019242.08 | 1021.51 | 06-FEB-06:01 | 919.36 | 919.36 | 45.97 | 11.88 |
March | 23565056.12 | 21208550.50 | 951.87 | 06-MAR-06:01 | 856.69 | 856.69 | 47.74 | 11.50 |
April | 3156132.95 | 2840519.66 | 301.03 | 29-APR-05:01 | 270.93 | 270.93 | 38.53 | 6.78 |
May | 2613513.11 | 2352161.80 | 316.64 | 08-MAY-05:01 | 284.97 | 284.97 | 42.88 | 6.93 |
June | 36609.14 | 32948.23 | 4.54 | 17-JUN-04:02 | 4.09 | 4.09 | 23.59 | 0.53 |
July | 34.67 | 31.20 | 0.02 | 08-JUL-05:20 | 0.01 | 0.01 | 23.08 | 0.00 |
August | 5777.88 | 5200.10 | 3.28 | 18-AUG-05:03 | 2.95 | 2.95 | 23.84 | 0.41 |
September | 406992.90 | 366293.61 | 227.15 | 19-SEP-05:02 | 204.44 | 204.44 | 30.82 | 5.92 |
October | 2484758.82 | 2236282.93 | 279.90 | 11-OCT-05:01 | 251.91 | 251.91 | 36.19 | 6.55 |
November | 18691442.63 | 16822298.36 | 953.28 | 27-NOV-06:02 | 857.95 | 857.95 | 48.22 | 11.51 |
December | 72538347.51 | 65284512.76 | 963.76 | 18-DEC-06:02 | 867.38 | 867.38 | 47.22 | 11.57 |
Annual Sum or Average | 0.350369E+09 | 0.315332E+09 | ||||||
Minimum of Months | 34.67 | 31.20 | 0.02 | 0.01 | 0.01 | 23.08 | 0.00 | |
Maximum of Months | 0.170182E+09 | 0.153164E+09 | 1239.68 | 1115.71 | 1115.71 | 48.22 | 12.92 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 30.84 | 27.76 | 0.28 | 24-JAN-05:01 | 0.25 | 0.25 | 6.70 | 0.06 |
February | 1657236.15 | 1491512.54 | 164.75 | 27-FEB-13:30 | 148.27 | 148.27 | 8.88 | 10.47 |
March | 14512.03 | 13060.82 | 3.33 | 14-MAR-13:30 | 2.99 | 2.99 | 8.63 | 0.68 |
April | 17470087.78 | 15723079.00 | 346.08 | 06-APR-16:00 | 311.47 | 311.47 | 7.97 | 15.47 |
May | 90673039.90 | 81605735.91 | 2118.38 | 19-MAY-12:00 | 1906.54 | 1906.54 | 7.49 | 36.40 |
June | 0.460388E+09 | 0.414349E+09 | 3500.05 | 30-JUN-16:00 | 3150.04 | 3150.04 | 6.72 | 45.28 |
July | 0.100964E+10 | 0.908676E+09 | 6331.79 | 19-JUL-05:03 | 5698.61 | 5698.61 | 8.02 | 58.09 |
August | 0.907414E+09 | 0.816673E+09 | 5232.66 | 07-AUG-13:00 | 4709.40 | 4709.40 | 6.72 | 53.67 |
September | 0.325695E+09 | 0.293126E+09 | 6134.13 | 05-SEP-12:30 | 5520.72 | 5520.72 | 7.51 | 57.33 |
October | 38230873.78 | 34407786.40 | 686.86 | 18-OCT-15:00 | 618.18 | 618.18 | 7.44 | 21.69 |
November | 956781.05 | 861102.95 | 47.56 | 03-NOV-14:00 | 42.80 | 42.80 | 8.70 | 5.07 |
December | 14.26 | 12.84 | 0.08 | 11-DEC-04:52 | 0.07 | 0.07 | 8.48 | 0.02 |
Annual Sum or Average | 0.285214E+10 | 0.256693E+10 | ||||||
Minimum of Months | 14.26 | 12.84 | 0.08 | 0.07 | 0.07 | 6.70 | 0.02 | |
Maximum of Months | 0.100964E+10 | 0.908676E+09 | 6331.79 | 5698.61 | 5698.61 | 8.88 | 58.09 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.565601E+09 | 0.509041E+09 | 12774.04 | 01-JAN-13:20 | 11496.64 | 11496.64 | 8.43 | 89.53 |
February | 0.157768E+10 | 0.141991E+10 | 12774.04 | 01-FEB-03:13 | 11496.64 | 11496.64 | 8.43 | 89.53 |
March | 0.248905E+10 | 0.224014E+10 | 12774.04 | 01-MAR-05:01 | 11496.64 | 11496.64 | 8.43 | 89.53 |
April | 0.552996E+10 | 0.497697E+10 | 12774.04 | 01-APR-12:15 | 11496.64 | 11496.64 | 8.43 | 89.53 |
May | 0.924623E+10 | 0.832161E+10 | 12774.04 | 01-MAY-12:40 | 11496.64 | 11496.64 | 8.43 | 89.53 |
June | 0.173016E+11 | 0.155714E+11 | 12774.04 | 01-JUN-03:02 | 11496.64 | 11496.64 | 8.64 | 89.53 |
July | 0.236106E+11 | 0.212496E+11 | 12774.04 | 01-JUL-00:10 | 11496.64 | 11496.64 | 7.94 | 89.53 |
August | 0.228786E+11 | 0.205908E+11 | 12774.04 | 01-AUG-00:05 | 11496.64 | 11496.64 | 8.00 | 89.53 |
September | 0.138459E+11 | 0.124613E+11 | 12774.04 | 01-SEP-00:03 | 11496.64 | 11496.64 | 8.05 | 89.53 |
October | 0.674789E+10 | 0.607310E+10 | 12774.04 | 02-OCT-05:08 | 11496.64 | 11496.64 | 8.61 | 89.53 |
November | 0.288280E+10 | 0.259452E+10 | 12774.04 | 01-NOV-04:01 | 11496.64 | 11496.64 | 8.62 | 89.53 |
December | 0.871062E+09 | 0.783956E+09 | 12774.04 | 01-DEC-05:41 | 11496.64 | 11496.64 | 8.43 | 89.53 |
Annual Sum or Average | 0.107547E+12 | 0.967923E+11 | ||||||
Minimum of Months | 0.565601E+09 | 0.509041E+09 | 12774.04 | 11496.64 | 11496.64 | 7.94 | 89.53 | |
Maximum of Months | 0.236106E+11 | 0.212496E+11 | 12774.04 | 11496.64 | 11496.64 | 8.64 | 89.53 |
Report: PumpReportMonthly
For: PLANT CIRC PUMP
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.976547E+10 | 0.878892E+10 | 3646.01 | 01-JAN-00:05 | 3281.41 | 3281.41 | 21.82 | 15.23 |
February | 0.882042E+10 | 0.793838E+10 | 3646.01 | 01-FEB-00:05 | 3281.41 | 3281.41 | 23.94 | 15.23 |
March | 0.976547E+10 | 0.878892E+10 | 3646.01 | 01-MAR-00:10 | 3281.41 | 3281.41 | 27.44 | 15.23 |
April | 0.945045E+10 | 0.850541E+10 | 3646.01 | 01-APR-00:10 | 3281.41 | 3281.41 | 30.42 | 15.23 |
May | 0.976547E+10 | 0.878892E+10 | 3646.01 | 01-MAY-00:05 | 3281.41 | 3281.41 | 22.36 | 15.23 |
June | 0.945045E+10 | 0.850541E+10 | 3646.01 | 01-JUN-00:10 | 3281.41 | 3281.41 | 25.97 | 15.23 |
July | 0.976547E+10 | 0.878892E+10 | 3646.01 | 01-JUL-00:05 | 3281.41 | 3281.41 | 34.62 | 15.23 |
August | 0.976547E+10 | 0.878892E+10 | 3646.01 | 01-AUG-00:05 | 3281.41 | 3281.41 | 38.54 | 15.23 |
September | 0.945045E+10 | 0.850541E+10 | 3646.01 | 01-SEP-00:03 | 3281.41 | 3281.41 | 25.52 | 15.23 |
October | 0.976547E+10 | 0.878892E+10 | 3646.01 | 01-OCT-00:10 | 3281.41 | 3281.41 | 25.00 | 15.23 |
November | 0.945045E+10 | 0.850541E+10 | 3646.01 | 01-NOV-00:10 | 3281.41 | 3281.41 | 27.68 | 15.23 |
December | 0.976547E+10 | 0.878892E+10 | 3646.01 | 01-DEC-00:10 | 3281.41 | 3281.41 | 30.06 | 15.23 |
Annual Sum or Average | 0.114980E+12 | 0.103482E+12 | ||||||
Minimum of Months | 0.882042E+10 | 0.793838E+10 | 3646.01 | 3281.41 | 3281.41 | 21.82 | 15.23 | |
Maximum of Months | 0.976547E+10 | 0.878892E+10 | 3646.01 | 3281.41 | 3281.41 | 38.54 | 15.23 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 11967951.72 | 3590385.52 | 5.96 | 01-JAN-06:03 | 1.79 | 1.79 | 55.22 | 0.44 |
February | 10809762.85 | 3242928.85 | 5.96 | 01-FEB-06:01 | 1.79 | 1.79 | 55.46 | 0.44 |
March | 11967951.72 | 3590385.52 | 5.96 | 01-MAR-06:02 | 1.79 | 1.79 | 56.13 | 0.44 |
April | 11581888.76 | 3474566.63 | 5.96 | 01-APR-05:01 | 1.79 | 1.79 | 56.36 | 0.44 |
May | 11967951.72 | 3590385.52 | 5.96 | 01-MAY-05:03 | 1.79 | 1.79 | 55.70 | 0.44 |
June | 11581888.76 | 3474566.63 | 5.96 | 01-JUN-05:03 | 1.79 | 1.79 | 56.56 | 0.44 |
July | 11967951.72 | 3590385.52 | 5.96 | 01-JUL-05:03 | 1.79 | 1.79 | 56.68 | 0.44 |
August | 11967951.72 | 3590385.52 | 5.96 | 01-AUG-05:02 | 1.79 | 1.79 | 56.37 | 0.44 |
September | 11581888.76 | 3474566.63 | 5.96 | 01-SEP-05:03 | 1.79 | 1.79 | 56.30 | 0.44 |
October | 11967951.72 | 3590385.52 | 5.96 | 01-OCT-05:10 | 1.79 | 1.79 | 55.89 | 0.44 |
November | 11581888.76 | 3474566.63 | 5.96 | 01-NOV-05:03 | 1.79 | 1.79 | 55.37 | 0.44 |
December | 11967951.72 | 3590385.52 | 5.96 | 01-DEC-06:01 | 1.79 | 1.79 | 55.98 | 0.44 |
Annual Sum or Average | 0.140913E+09 | 42273893.99 | ||||||
Minimum of Months | 10809762.85 | 3242928.85 | 5.96 | 1.79 | 1.79 | 55.22 | 0.44 | |
Maximum of Months | 11967951.72 | 3590385.52 | 5.96 | 1.79 | 1.79 | 56.68 | 0.44 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.699396E+09 | 0.629456E+09 | 15797.97 | 18-JAN-04:02 | 14218.18 | 14218.18 | 21.18 | 52.63 |
February | 0.195120E+10 | 0.175608E+10 | 15818.24 | 27-FEB-15:30 | 14236.42 | 14236.42 | 22.97 | 52.63 |
March | 0.307782E+10 | 0.277004E+10 | 15798.20 | 31-MAR-06:00 | 14218.38 | 14218.38 | 21.20 | 52.63 |
April | 0.689847E+10 | 0.620863E+10 | 31633.45 | 07-APR-13:10 | 28470.11 | 28470.11 | 22.82 | 105.25 |
May | 0.120279E+11 | 0.108251E+11 | 31709.54 | 19-MAY-15:30 | 28538.59 | 28538.59 | 26.00 | 105.25 |
June | 0.256668E+11 | 0.231001E+11 | 31725.85 | 20-JUN-15:40 | 28553.26 | 28553.26 | 26.62 | 105.25 |
July | 0.375065E+11 | 0.337558E+11 | 31730.89 | 17-JUL-15:30 | 28557.80 | 28557.80 | 26.81 | 105.25 |
August | 0.352585E+11 | 0.317326E+11 | 31712.05 | 07-AUG-16:20 | 28540.84 | 28540.84 | 26.10 | 105.25 |
September | 0.194867E+11 | 0.175380E+11 | 31784.26 | 07-SEP-14:40 | 28605.83 | 28605.83 | 29.37 | 105.25 |
October | 0.870106E+10 | 0.783096E+10 | 31691.35 | 18-OCT-13:00 | 28522.21 | 28522.21 | 25.32 | 105.25 |
November | 0.356494E+10 | 0.320845E+10 | 15806.67 | 17-NOV-17:00 | 14226.00 | 14226.00 | 21.95 | 52.63 |
December | 0.107709E+10 | 0.969384E+09 | 15798.10 | 07-DEC-15:20 | 14218.29 | 14218.29 | 21.20 | 52.63 |
Annual Sum or Average | 0.155916E+12 | 0.140325E+12 | ||||||
Minimum of Months | 0.699396E+09 | 0.629456E+09 | 15797.97 | 14218.18 | 14218.18 | 21.18 | 52.63 | |
Maximum of Months | 0.375065E+11 | 0.337558E+11 | 31784.26 | 28605.83 | 28605.83 | 29.37 | 105.25 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 38.76 | 38.76 | 343087.60 | 1978568.98 | 09-JAN-07:10 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 32.91 | 82.20 | 198552.18 | 1810107.54 | 07-FEB-06:01 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.59 | 25.59 | 104575.63 | 1656832.32 | 06-MAR-06:01 |
April | 0.00 | 0.00 | 01-APR-00:10 | 26.48 | 26.48 | 27136.01 | 1264749.54 | 19-APR-05:02 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 23.43 | 81.26 | 18040.48 | 1482123.24 | 22-MAY-04:01 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 23.66 | 23.66 | 462.64 | 127675.22 | 17-JUN-04:02 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 23.08 | 23.08 | 0.49 | 599.67 | 08-JUL-05:20 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.06 | 23.06 | 76.63 | 96432.44 | 18-AUG-05:03 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.45 | 23.45 | 4209.59 | 1235412.06 | 19-SEP-05:02 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.53 | 22.53 | 19667.28 | 1231242.84 | 11-OCT-05:01 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 26.59 | 26.59 | 89978.26 | 1634490.46 | 27-NOV-06:02 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 30.14 | 30.14 | 221307.46 | 1877892.63 | 26-DEC-05:01 |
Annual Sum or Average | 0.00 | 85267.07 | ||||||
Minimum of Months | 0.00 | 0.00 | 22.53 | 22.53 | 0.49 | 599.67 | ||
Maximum of Months | 0.00 | 0.00 | 38.76 | 82.20 | 343087.60 | 1978568.98 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 377.24 | 22824.41 | 07-JAN-03:00 | 8.43 | 8.40 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 5081.88 | 684129.01 | 27-FEB-15:30 | 9.70 | 8.78 | 0.00 | 0.00 | 01-FEB-00:05 |
March | 1737.59 | 68508.81 | 14-MAR-13:30 | 8.55 | 8.46 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 41636.97 | 1147816.12 | 07-APR-13:10 | 10.41 | 8.75 | 0.00 | 0.00 | 01-APR-00:10 |
May | 120689.98 | 1284008.00 | 19-MAY-15:30 | 10.12 | 6.70 | 171.97 | 281830.03 | 22-MAY-03:10 |
June | 331289.84 | 1469148.71 | 29-JUN-14:50 | 10.62 | 6.70 | 44.71 | 139991.23 | 11-JUN-19:42 |
July | 507544.63 | 1733625.68 | 17-JUL-15:30 | 11.32 | 6.70 | 61.30 | 106501.76 | 26-JUL-23:53 |
August | 443842.27 | 1630310.94 | 07-AUG-15:40 | 11.05 | 6.70 | 20.12 | 48820.56 | 20-AUG-20:25 |
September | 242082.44 | 2275676.93 | 07-SEP-15:00 | 13.12 | 7.42 | 46.06 | 160713.38 | 24-SEP-08:53 |
October | 65782.19 | 1157586.76 | 16-OCT-14:50 | 10.63 | 8.96 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 5268.28 | 282016.57 | 17-NOV-17:00 | 8.88 | 8.50 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 581.10 | 23132.41 | 11-DEC-04:52 | 8.43 | 8.40 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 148240.61 | 28.98 | ||||||
Minimum of Months | 377.24 | 22824.41 | 8.43 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 507544.63 | 2275676.93 | 13.12 | 8.96 | 171.97 | 281830.03 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 1.21 | 24-JAN-05:01 | 6.70 | 8.40 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 2463.08 | 427062.11 | 27-FEB-13:30 | 16.45 | 8.93 | 0.00 | 0.00 | 01-FEB-00:05 |
March | 47.10 | 28152.75 | 14-MAR-13:30 | 16.57 | 8.46 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 25088.59 | 878243.98 | 06-APR-16:00 | 20.28 | 8.49 | 0.00 | 0.00 | 01-APR-00:10 |
May | 78390.61 | 1274039.30 | 19-MAY-15:30 | 15.20 | 6.70 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 264754.12 | 1459678.07 | 29-JUN-14:50 | 22.35 | 6.70 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 423177.48 | 2180299.88 | 19-JUL-05:03 | 15.67 | 7.82 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 369916.03 | 1622263.73 | 07-AUG-15:40 | 14.36 | 6.70 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 176655.44 | 2280015.20 | 07-SEP-15:00 | 18.77 | 7.54 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 42469.84 | 1161411.97 | 18-OCT-15:00 | 19.51 | 6.96 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 2047.64 | 183992.95 | 01-NOV-04:01 | 17.19 | 8.44 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 0.04 | 588.74 | 11-DEC-04:52 | 14.20 | 8.40 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 116327.05 | 0.00 | ||||||
Minimum of Months | 0.00 | 1.21 | 6.70 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 423177.48 | 2280015.20 | 22.35 | 8.93 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 176767.77 | 199897.32 | 13-JAN-16:30 | 22.11 | 18.33 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 337425.94 | 604470.58 | 27-FEB-16:00 | 29.67 | 22.68 | 0.00 | 0.00 | 01-FEB-00:05 |
March | 494873.97 | 644974.42 | 31-MAR-24:00 | 30.42 | 18.33 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 702091.86 | 1321310.43 | 07-APR-14:00 | 42.81 | 30.23 | 0.00 | 0.00 | 01-APR-00:10 |
May | 255793.62 | 971082.33 | 20-MAY-16:00 | 36.43 | 32.27 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 573482.42 | 1370645.00 | 29-JUN-15:00 | 43.70 | 36.29 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 966949.97 | 1947680.29 | 17-JUL-16:00 | 54.04 | 43.25 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 1121157.93 | 2066020.76 | 06-AUG-16:00 | 56.14 | 42.99 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 338382.19 | 1240861.18 | 02-SEP-17:00 | 41.35 | 36.87 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 385968.62 | 955868.82 | 18-OCT-15:00 | 36.15 | 28.94 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 504985.36 | 745592.46 | 17-NOV-17:00 | 32.28 | 22.50 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 638348.30 | 764174.98 | 10-DEC-02:00 | 32.63 | 20.49 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 543155.74 | 0.00 | ||||||
Minimum of Months | 176767.77 | 199897.32 | 22.11 | 18.33 | 0.00 | 0.00 | ||
Maximum of Months | 1121157.93 | 2066020.76 | 56.14 | 43.25 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 56.25 | 56.25 | 17330.27 | 58846.21 | 31-JAN-13:00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 55.93 | 55.93 | 17709.67 | 59172.20 | 23-FEB-12:10 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 56.68 | 56.68 | 18546.04 | 59076.16 | 02-MAR-12:40 |
April | 0.00 | 0.00 | 01-APR-00:10 | 56.82 | 56.82 | 16883.78 | 57455.33 | 03-APR-11:50 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 56.70 | 56.70 | 16525.59 | 54969.25 | 01-MAY-11:20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 57.13 | 57.13 | 15932.57 | 51686.41 | 01-JUN-11:30 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 57.24 | 57.24 | 14099.46 | 48654.43 | 03-JUL-11:50 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 56.89 | 56.89 | 14986.23 | 46968.27 | 01-AUG-12:00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 57.21 | 57.21 | 14316.35 | 48076.88 | 29-SEP-11:30 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 56.99 | 56.99 | 14900.79 | 50878.85 | 31-OCT-12:00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 56.02 | 56.02 | 15950.96 | 54068.60 | 30-NOV-13:00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 56.49 | 56.49 | 16274.40 | 56867.58 | 29-DEC-12:40 |
Annual Sum or Average | 0.00 | 16112.13 | ||||||
Minimum of Months | 0.00 | 0.00 | 55.93 | 55.93 | 14099.46 | 46968.27 | ||
Maximum of Months | 0.00 | 0.00 | 57.24 | 57.24 | 18546.04 | 59172.20 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 6.17 | 18559.79 | 18-JAN-04:02 | 21.18 | 20.24 | 403.21 | 82933.45 | 17-JAN-06:40 |
February | 2259.34 | 410832.06 | 27-FEB-15:30 | 22.97 | 21.10 | 929.94 | 113180.55 | 24-FEB-06:30 |
March | 85.57 | 22922.24 | 31-MAR-06:00 | 21.20 | 20.25 | 1966.67 | 132296.99 | 16-MAR-13:30 |
April | 24455.21 | 816823.01 | 07-APR-14:00 | 24.81 | 21.10 | 2242.68 | 116130.94 | 14-APR-13:30 |
May | 84322.46 | 2156967.09 | 19-MAY-15:30 | 26.00 | 21.10 | 1753.42 | 125290.83 | 03-MAY-15:50 |
June | 309844.26 | 2426608.04 | 20-JUN-15:40 | 26.62 | 22.95 | 1139.20 | 96526.46 | 17-JUN-05:30 |
July | 517346.26 | 2510037.86 | 17-JUL-15:30 | 26.81 | 22.28 | 745.26 | 55829.00 | 08-JUL-08:20 |
August | 445223.47 | 2198347.53 | 07-AUG-16:20 | 26.10 | 21.53 | 1633.54 | 79360.13 | 12-AUG-03:00 |
September | 210788.06 | 4295686.58 | 07-SEP-15:00 | 30.86 | 25.35 | 1530.70 | 111702.61 | 18-SEP-15:40 |
October | 42383.40 | 1855631.16 | 18-OCT-13:00 | 25.32 | 21.10 | 2007.13 | 131090.49 | 21-OCT-05:30 |
November | 1467.82 | 186962.36 | 17-NOV-17:00 | 21.95 | 21.10 | 2027.66 | 131507.52 | 09-NOV-07:00 |
December | 19.66 | 20931.89 | 07-DEC-15:20 | 21.20 | 20.36 | 783.71 | 130123.25 | 20-DEC-06:30 |
Annual Sum or Average | 137618.95 | 1431.03 | ||||||
Minimum of Months | 6.17 | 18559.79 | 21.18 | 20.24 | 403.21 | 55829.00 | ||
Maximum of Months | 517346.26 | 4295686.58 | 30.86 | 25.35 | 2242.68 | 132296.99 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.475139E+11 | 0.00 | 0.00 | 0.367808E+10 | 0.00 | 0.00 |
February | 0.228057E+11 | 0.00 | 0.585539E+09 | 0.410923E+10 | 0.00 | 0.00 |
March | 0.101973E+11 | 0.00 | 31058141.34 | 0.634041E+10 | 0.00 | 0.00 |
April | 0.159089E+10 | 0.00 | 0.618598E+10 | 0.823325E+10 | 0.00 | 0.00 |
May | 0.109750E+10 | 0.00 | 0.169802E+11 | 0.746795E+10 | 0.00 | 0.00 |
June | 17241311.64 | 0.00 | 0.565611E+11 | 0.119786E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.975288E+11 | 0.150143E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.904464E+11 | 0.164373E+11 | 0.00 | 0.00 |
September | 0.181539E+09 | 0.00 | 0.365519E+11 | 0.852528E+10 | 0.00 | 0.00 |
October | 0.117293E+10 | 0.00 | 0.981394E+10 | 0.737476E+10 | 0.00 | 0.00 |
November | 0.701009E+10 | 0.00 | 0.496941E+09 | 0.595377E+10 | 0.00 | 0.00 |
December | 0.234746E+11 | 0.00 | 222.89 | 0.493990E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.115062E+12 | 0.00 | 0.315182E+12 | 0.100053E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.367808E+10 | 0.00 | 0.00 |
Maximum of Months | 0.475139E+11 | 0.00 | 0.975288E+11 | 0.164373E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.753131E+12 | 0.00 | 19694.50 | 0.380767E+11 | 0.00 | 0.00 |
February | 0.395994E+12 | 0.00 | 0.391301E+10 | 0.328571E+11 | 0.00 | 0.00 |
March | 0.228202E+12 | 0.00 | 48397356.45 | 0.402777E+11 | 0.00 | 0.00 |
April | 0.551451E+11 | 0.00 | 0.421678E+11 | 0.439482E+11 | 0.00 | 0.00 |
May | 0.374487E+11 | 0.00 | 0.142546E+12 | 0.541579E+11 | 0.00 | 0.00 |
June | 0.653964E+09 | 0.00 | 0.478291E+12 | 0.902401E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.807487E+12 | 0.110468E+12 | 0.00 | 0.00 |
August | 46928495.17 | 0.00 | 0.700062E+12 | 0.106653E+12 | 0.00 | 0.00 |
September | 0.742331E+10 | 0.00 | 0.318686E+12 | 0.649686E+11 | 0.00 | 0.00 |
October | 0.398809E+11 | 0.00 | 0.744339E+11 | 0.454802E+11 | 0.00 | 0.00 |
November | 0.187875E+12 | 0.00 | 0.339142E+10 | 0.360074E+11 | 0.00 | 0.00 |
December | 0.486857E+12 | 0.00 | 28959.19 | 0.360271E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.219266E+13 | 0.00 | 0.257103E+13 | 0.699161E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 19694.50 | 0.328571E+11 | 0.00 | 0.00 |
Maximum of Months | 0.753131E+12 | 0.00 | 0.807487E+12 | 0.110468E+12 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.122016E+12 | 0.00 | 1220.61 | 0.502493E+10 | 0.00 | 0.00 |
February | 0.640811E+11 | 0.00 | 0.288330E+09 | 0.385781E+10 | 0.00 | 0.00 |
March | 0.431262E+11 | 0.00 | 1270391.95 | 0.403028E+10 | 0.00 | 0.00 |
April | 0.139876E+11 | 0.00 | 0.382489E+10 | 0.373414E+10 | 0.00 | 0.00 |
May | 0.100178E+11 | 0.00 | 0.147627E+11 | 0.484592E+10 | 0.00 | 0.00 |
June | 0.538865E+09 | 0.00 | 0.525532E+11 | 0.843109E+10 | 0.00 | 0.00 |
July | 1503808.24 | 0.00 | 0.892413E+11 | 0.107852E+11 | 0.00 | 0.00 |
August | 0.157952E+09 | 0.00 | 0.751464E+11 | 0.984313E+10 | 0.00 | 0.00 |
September | 0.336855E+10 | 0.00 | 0.324631E+11 | 0.551921E+10 | 0.00 | 0.00 |
October | 0.118497E+11 | 0.00 | 0.625453E+10 | 0.365548E+10 | 0.00 | 0.00 |
November | 0.395005E+11 | 0.00 | 0.248191E+09 | 0.374569E+10 | 0.00 | 0.00 |
December | 0.854046E+11 | 0.00 | 63355.11 | 0.451017E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.394050E+12 | 0.00 | 0.274784E+12 | 0.679831E+11 | 0.00 | 0.00 |
Minimum of Months | 1503808.24 | 0.00 | 1220.61 | 0.365548E+10 | 0.00 | 0.00 |
Maximum of Months | 0.122016E+12 | 0.00 | 0.892413E+11 | 0.107852E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.111315E+10 | 0.00 | 109714.94 | 0.148648E+11 | 0.00 | 0.00 |
February | 708736.03 | 0.00 | 0.239590E+09 | 0.133007E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.159412E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.207821E+10 | 0.147896E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.809844E+10 | 0.158012E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.288063E+11 | 0.157987E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.495170E+11 | 0.157068E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.460405E+11 | 0.172691E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.188259E+11 | 0.161121E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.532649E+10 | 0.157591E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 60763290.06 | 0.150687E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.147026E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.111386E+10 | 0.00 | 0.158993E+12 | 0.185115E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.133007E+11 | 0.00 | 0.00 |
Maximum of Months | 0.111315E+10 | 0.00 | 0.495170E+11 | 0.172691E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.451452E+12 | 0.240050E+12 | 0.00 | 15.20 |
February | 0.00 | 0.00 | 0.712084E+12 | 0.296669E+12 | 0.00 | 22.78 |
March | 0.00 | 0.00 | 0.111852E+13 | 0.409679E+12 | 0.00 | 34.37 |
April | 0.00 | 0.00 | 0.140492E+13 | 0.476714E+12 | 0.00 | 41.42 |
May | 0.00 | 0.00 | 0.472170E+12 | 0.242477E+12 | 0.00 | 13.72 |
June | 0.00 | 0.00 | 0.787856E+12 | 0.322568E+12 | 0.00 | 18.34 |
July | 0.00 | 0.00 | 0.116054E+13 | 0.429612E+12 | 0.00 | 20.43 |
August | 0.00 | 0.00 | 0.148638E+13 | 0.520849E+12 | 0.00 | 32.51 |
September | 0.00 | 0.00 | 0.465899E+12 | 0.235994E+12 | 0.00 | 11.70 |
October | 0.00 | 0.00 | 0.806128E+12 | 0.330364E+12 | 0.00 | 23.90 |
November | 0.00 | 0.00 | 0.109337E+13 | 0.400958E+12 | 0.00 | 34.09 |
December | 0.00 | 0.00 | 0.144361E+13 | 0.489929E+12 | 0.00 | 44.50 |
Annual Sum or Average | 0.00 | 0.00 | 0.114029E+14 | 0.439586E+13 | 0.00 | 312.97 |
Minimum of Months | 0.00 | 0.00 | 0.451452E+12 | 0.235994E+12 | 0.00 | 11.70 |
Maximum of Months | 0.00 | 0.00 | 0.148638E+13 | 0.520849E+12 | 0.00 | 44.50 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.352313E+10 | 0.247420E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.102328E+11 | 0.365540E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.185693E+11 | 0.537046E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.247933E+11 | 0.644330E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.709667E+10 | 0.320825E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.138729E+11 | 0.465493E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.215288E+11 | 0.669288E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.278295E+11 | 0.799739E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.729823E+10 | 0.324151E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.131783E+11 | 0.435635E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.181701E+11 | 0.521105E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.241430E+11 | 0.639340E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.190236E+12 | 0.596991E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.352313E+10 | 0.247420E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.278295E+11 | 0.799739E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.795481E+10 | 0.180871E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.718851E+11 | 0.298684E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.153507E+12 | 0.469925E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.222710E+12 | 0.591859E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.573498E+11 | 0.285975E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.128209E+12 | 0.436908E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.203898E+12 | 0.636499E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.262187E+12 | 0.757730E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.618635E+11 | 0.294340E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.109862E+12 | 0.386650E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.149036E+12 | 0.453927E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.194528E+12 | 0.547557E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.162299E+13 | 0.534092E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.795481E+10 | 0.180871E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.262187E+12 | 0.757730E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.210887E+09 | 0.169731E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.515254E+10 | 0.259943E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.132067E+11 | 0.432950E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.207245E+11 | 0.568512E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.481597E+10 | 0.270074E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.125483E+11 | 0.435417E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.203392E+11 | 0.640116E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.260658E+11 | 0.759780E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.542469E+10 | 0.282273E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.909510E+10 | 0.353684E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.124305E+11 | 0.411125E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.170038E+11 | 0.506373E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.147018E+12 | 0.508998E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.210887E+09 | 0.169731E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.260658E+11 | 0.759780E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.367808E+10 | 0.00 | 0.475139E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.410923E+10 | 0.585539E+09 | 0.228057E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.634041E+10 | 31058141.34 | 0.101973E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.823325E+10 | 0.618598E+10 | 0.159089E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.746795E+10 | 0.169802E+11 | 0.109750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.119786E+11 | 0.565611E+11 | 17241311.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.150143E+11 | 0.975288E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.164373E+11 | 0.904464E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.852528E+10 | 0.365519E+11 | 0.181539E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.737476E+10 | 0.981394E+10 | 0.117293E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.595377E+10 | 0.496941E+09 | 0.701009E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.493990E+10 | 222.89 | 0.234746E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.100053E+12 | 0.315182E+12 | 0.115062E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.367808E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.164373E+11 | 0.975288E+11 | 0.475139E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.380767E+11 | 19694.50 | 0.753131E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.328571E+11 | 0.391301E+10 | 0.395994E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.402777E+11 | 48397356.45 | 0.228202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.439482E+11 | 0.421678E+11 | 0.551451E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.541579E+11 | 0.142546E+12 | 0.374487E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.902401E+11 | 0.478291E+12 | 0.653964E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.110468E+12 | 0.807487E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.106653E+12 | 0.700062E+12 | 46928495.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.649686E+11 | 0.318686E+12 | 0.742331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.454802E+11 | 0.744339E+11 | 0.398809E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.360074E+11 | 0.339142E+10 | 0.187875E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.360271E+11 | 28959.19 | 0.486857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.699161E+12 | 0.257103E+13 | 0.219266E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.328571E+11 | 19694.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.110468E+12 | 0.807487E+12 | 0.753131E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.502493E+10 | 1220.61 | 0.122016E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.385781E+10 | 0.288330E+09 | 0.640811E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.403028E+10 | 1270391.95 | 0.431262E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.373414E+10 | 0.382489E+10 | 0.139876E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.484592E+10 | 0.147627E+11 | 0.100178E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.843109E+10 | 0.525532E+11 | 0.538865E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.107852E+11 | 0.892413E+11 | 1503808.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.984313E+10 | 0.751464E+11 | 0.157952E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.551921E+10 | 0.324631E+11 | 0.336855E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.365548E+10 | 0.625453E+10 | 0.118497E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.374569E+10 | 0.248191E+09 | 0.395005E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.451017E+10 | 63355.11 | 0.854046E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.679831E+11 | 0.274784E+12 | 0.394050E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.365548E+10 | 1220.61 | 1503808.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.107852E+11 | 0.892413E+11 | 0.122016E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.148648E+11 | 109714.94 | 0.111315E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.133007E+11 | 0.239590E+09 | 708736.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.159412E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.147896E+11 | 0.207821E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.158012E+11 | 0.809844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.157987E+11 | 0.288063E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.157068E+11 | 0.495170E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.172691E+11 | 0.460405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.161121E+11 | 0.188259E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.157591E+11 | 0.532649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.150687E+11 | 60763290.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.147026E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.185115E+12 | 0.158993E+12 | 0.111386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.133007E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.172691E+11 | 0.495170E+11 | 0.111315E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.107754E+12 | 0.360020E+12 | 0.00 | 0.00 | 0.00 | 0.406801E+11 | 0.00 | 0.00 |
February | 0.973261E+11 | 0.573981E+12 | 0.00 | 0.00 | 0.00 | 0.609648E+11 | 0.00 | 0.00 |
March | 0.107754E+12 | 0.908998E+12 | 0.00 | 0.00 | 0.00 | 0.919909E+11 | 0.00 | 0.00 |
April | 0.104278E+12 | 0.114382E+13 | 0.00 | 0.00 | 0.00 | 0.110840E+12 | 0.00 | 0.00 |
May | 0.107754E+12 | 0.374342E+12 | 0.00 | 0.00 | 0.00 | 0.367293E+11 | 0.00 | 0.00 |
June | 0.104278E+12 | 0.618878E+12 | 0.00 | 0.00 | 0.00 | 0.490918E+11 | 0.00 | 0.00 |
July | 0.107754E+12 | 0.893602E+12 | 0.00 | 0.00 | 0.00 | 0.546766E+11 | 0.00 | 0.00 |
August | 0.107754E+12 | 0.116066E+13 | 0.00 | 0.00 | 0.00 | 0.869919E+11 | 0.00 | 0.00 |
September | 0.104278E+12 | 0.365621E+12 | 0.00 | 0.00 | 0.00 | 0.312974E+11 | 0.00 | 0.00 |
October | 0.107754E+12 | 0.647772E+12 | 0.00 | 0.00 | 0.00 | 0.639672E+11 | 0.00 | 0.00 |
November | 0.104278E+12 | 0.888341E+12 | 0.00 | 0.00 | 0.00 | 0.912378E+11 | 0.00 | 0.00 |
December | 0.107754E+12 | 0.118105E+13 | 0.00 | 0.00 | 0.00 | 0.119083E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.126872E+13 | 0.911709E+13 | 0.00 | 0.00 | 0.00 | 0.837551E+12 | 0.00 | 0.00 |
Minimum of Months | 0.973261E+11 | 0.360020E+12 | 0.00 | 0.00 | 0.00 | 0.312974E+11 | 0.00 | 0.00 |
Maximum of Months | 0.107754E+12 | 0.118105E+13 | 0.00 | 0.00 | 0.00 | 0.119083E+12 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.168658E+10 | 0.273551E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.152336E+10 | 0.810072E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.168658E+10 | 0.148854E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.163217E+10 | 0.199822E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.168658E+10 | 0.557500E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.163217E+10 | 0.108501E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168658E+10 | 0.165225E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.168658E+10 | 0.215187E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.163217E+10 | 0.568889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.168658E+10 | 0.105085E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.163217E+10 | 0.145912E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168658E+10 | 0.194362E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.198581E+11 | 0.150395E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.152336E+10 | 0.273551E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.168658E+10 | 0.215187E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.161534E+11 | 0.602116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.145902E+11 | 0.566069E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.161534E+11 | 0.122668E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.156323E+11 | 0.179156E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.161534E+11 | 0.449057E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.156323E+11 | 0.100151E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.161534E+11 | 0.156401E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.161534E+11 | 0.202567E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.156323E+11 | 0.480619E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.161534E+11 | 0.873500E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.156323E+11 | 0.119276E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.161534E+11 | 0.155926E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.190194E+12 | 0.127909E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.145902E+11 | 0.602116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.161534E+11 | 0.202567E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.164513E+10 | 0.158707E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.148592E+10 | 0.403903E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.164513E+10 | 0.105223E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.159206E+10 | 0.166314E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.164513E+10 | 0.376036E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.159206E+10 | 0.978624E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.164513E+10 | 0.155832E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.164513E+10 | 0.201131E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.159206E+10 | 0.419403E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.164513E+10 | 0.720339E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.159206E+10 | 0.991135E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.164513E+10 | 0.135852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.193701E+11 | 0.115488E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.148592E+10 | 0.158707E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.164513E+10 | 0.201131E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.367808E+10 | 0.475139E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.410923E+10 | 0.228057E+11 | 0.585539E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.634041E+10 | 0.101973E+11 | 31058141.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.823325E+10 | 0.159089E+10 | 0.618598E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.746795E+10 | 0.109750E+10 | 0.169802E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.119786E+11 | 17241311.64 | 0.565611E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.150143E+11 | 0.00 | 0.975288E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.164373E+11 | 0.00 | 0.904464E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.852528E+10 | 0.181539E+09 | 0.365519E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.737476E+10 | 0.117293E+10 | 0.981394E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.595377E+10 | 0.701009E+10 | 0.496941E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.493990E+10 | 0.234746E+11 | 222.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.100053E+12 | 0.115062E+12 | 0.315182E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.367808E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.164373E+11 | 0.475139E+11 | 0.975288E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.380767E+11 | 0.753131E+12 | 19694.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.328571E+11 | 0.395994E+12 | 0.391301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.402777E+11 | 0.228202E+12 | 48397356.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.439482E+11 | 0.551451E+11 | 0.421678E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.541579E+11 | 0.374487E+11 | 0.142546E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.902401E+11 | 0.653964E+09 | 0.478291E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.110468E+12 | 0.00 | 0.807487E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.106653E+12 | 46928495.17 | 0.700062E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.649686E+11 | 0.742331E+10 | 0.318686E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.454802E+11 | 0.398809E+11 | 0.744339E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.360074E+11 | 0.187875E+12 | 0.339142E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.360271E+11 | 0.486857E+12 | 28959.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.699161E+12 | 0.219266E+13 | 0.257103E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.328571E+11 | 0.00 | 19694.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.110468E+12 | 0.753131E+12 | 0.807487E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.502493E+10 | 0.122016E+12 | 1220.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.385781E+10 | 0.640811E+11 | 0.288330E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.403028E+10 | 0.431262E+11 | 1270391.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.373414E+10 | 0.139876E+11 | 0.382489E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.484592E+10 | 0.100178E+11 | 0.147627E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.843109E+10 | 0.538865E+09 | 0.525532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.107852E+11 | 1503808.24 | 0.892413E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.984313E+10 | 0.157952E+09 | 0.751464E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.551921E+10 | 0.336855E+10 | 0.324631E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.365548E+10 | 0.118497E+11 | 0.625453E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.374569E+10 | 0.395005E+11 | 0.248191E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.451017E+10 | 0.854046E+11 | 63355.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.679831E+11 | 0.394050E+12 | 0.274784E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.365548E+10 | 1503808.24 | 1220.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.107852E+11 | 0.122016E+12 | 0.892413E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.148648E+11 | 0.111315E+10 | 109714.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.133007E+11 | 708736.03 | 0.239590E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.159412E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.147896E+11 | 0.00 | 0.207821E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.158012E+11 | 0.00 | 0.809844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.157987E+11 | 0.00 | 0.288063E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.157068E+11 | 0.00 | 0.495170E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.172691E+11 | 0.00 | 0.460405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.161121E+11 | 0.00 | 0.188259E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.157591E+11 | 0.00 | 0.532649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.150687E+11 | 0.00 | 60763290.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.147026E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.185115E+12 | 0.111386E+10 | 0.158993E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.133007E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.172691E+11 | 0.111315E+10 | 0.495170E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.107754E+12 | 0.00 | 0.451452E+12 | 0.00 | 0.914325E+11 | 0.00 | 0.00 | 0.00 | 0.408632E+11 | 0.00 | 0.00 | 0.00 |
February | 0.973261E+11 | 0.00 | 0.712084E+12 | 0.00 | 0.138103E+12 | 0.00 | 0.00 | 0.00 | 0.612392E+11 | 0.00 | 0.00 | 0.00 |
March | 0.107754E+12 | 0.00 | 0.111852E+13 | 0.00 | 0.209521E+12 | 0.00 | 0.00 | 0.00 | 0.924050E+11 | 0.00 | 0.00 | 0.00 |
April | 0.104278E+12 | 0.00 | 0.140492E+13 | 0.00 | 0.261097E+12 | 0.00 | 0.00 | 0.00 | 0.111339E+12 | 0.00 | 0.00 | 0.00 |
May | 0.107754E+12 | 0.00 | 0.472170E+12 | 0.00 | 0.978285E+11 | 0.00 | 0.00 | 0.00 | 0.368947E+11 | 0.00 | 0.00 | 0.00 |
June | 0.104278E+12 | 0.00 | 0.787856E+12 | 0.00 | 0.168977E+12 | 0.00 | 0.00 | 0.00 | 0.493128E+11 | 0.00 | 0.00 | 0.00 |
July | 0.107754E+12 | 0.00 | 0.116054E+13 | 0.00 | 0.266935E+12 | 0.00 | 0.00 | 0.00 | 0.549227E+11 | 0.00 | 0.00 | 0.00 |
August | 0.107754E+12 | 0.00 | 0.148638E+13 | 0.00 | 0.325711E+12 | 0.00 | 0.00 | 0.00 | 0.873835E+11 | 0.00 | 0.00 | 0.00 |
September | 0.104278E+12 | 0.00 | 0.465899E+12 | 0.00 | 0.100278E+12 | 0.00 | 0.00 | 0.00 | 0.314383E+11 | 0.00 | 0.00 | 0.00 |
October | 0.107754E+12 | 0.00 | 0.806128E+12 | 0.00 | 0.158355E+12 | 0.00 | 0.00 | 0.00 | 0.642552E+11 | 0.00 | 0.00 | 0.00 |
November | 0.104278E+12 | 0.00 | 0.109337E+13 | 0.00 | 0.205032E+12 | 0.00 | 0.00 | 0.00 | 0.916485E+11 | 0.00 | 0.00 | 0.00 |
December | 0.107754E+12 | 0.00 | 0.144361E+13 | 0.00 | 0.262556E+12 | 0.00 | 0.00 | 0.00 | 0.119619E+12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.126872E+13 | 0.00 | 0.114029E+14 | 0.00 | 0.228583E+13 | 0.00 | 0.00 | 0.00 | 0.841321E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.973261E+11 | 0.00 | 0.451452E+12 | 0.00 | 0.914325E+11 | 0.00 | 0.00 | 0.00 | 0.314383E+11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.107754E+12 | 0.00 | 0.148638E+13 | 0.00 | 0.325711E+12 | 0.00 | 0.00 | 0.00 | 0.119619E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.168658E+10 | 0.00 | 0.352313E+10 | 0.00 | 0.787621E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.152336E+10 | 0.00 | 0.102328E+11 | 0.00 | 0.213204E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.168658E+10 | 0.00 | 0.185693E+11 | 0.00 | 0.368388E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.163217E+10 | 0.00 | 0.247933E+11 | 0.00 | 0.481113E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.168658E+10 | 0.00 | 0.709667E+10 | 0.00 | 0.152167E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.163217E+10 | 0.00 | 0.138729E+11 | 0.00 | 0.302276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168658E+10 | 0.00 | 0.215288E+11 | 0.00 | 0.500630E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.168658E+10 | 0.00 | 0.278295E+11 | 0.00 | 0.631081E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.163217E+10 | 0.00 | 0.729823E+10 | 0.00 | 0.160934E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.168658E+10 | 0.00 | 0.131783E+11 | 0.00 | 0.266977E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.163217E+10 | 0.00 | 0.181701E+11 | 0.00 | 0.357888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168658E+10 | 0.00 | 0.241430E+11 | 0.00 | 0.470683E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.198581E+11 | 0.00 | 0.190236E+12 | 0.00 | 0.398410E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.152336E+10 | 0.00 | 0.352313E+10 | 0.00 | 0.787621E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.168658E+10 | 0.00 | 0.278295E+11 | 0.00 | 0.631081E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.161534E+11 | 0.00 | 0.795481E+10 | 0.00 | 0.193365E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.145902E+11 | 0.00 | 0.718851E+11 | 0.00 | 0.152782E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.161534E+11 | 0.00 | 0.153507E+12 | 0.00 | 0.308391E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.156323E+11 | 0.00 | 0.222710E+12 | 0.00 | 0.435535E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.161534E+11 | 0.00 | 0.573498E+11 | 0.00 | 0.124441E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.156323E+11 | 0.00 | 0.128209E+12 | 0.00 | 0.280584E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.161534E+11 | 0.00 | 0.203898E+12 | 0.00 | 0.474965E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.161534E+11 | 0.00 | 0.262187E+12 | 0.00 | 0.596195E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.156323E+11 | 0.00 | 0.618635E+11 | 0.00 | 0.138016E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.161534E+11 | 0.00 | 0.109862E+12 | 0.00 | 0.225115E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.156323E+11 | 0.00 | 0.149036E+12 | 0.00 | 0.297604E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.161534E+11 | 0.00 | 0.194528E+12 | 0.00 | 0.386023E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.190194E+12 | 0.00 | 0.162299E+13 | 0.00 | 0.343899E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.145902E+11 | 0.00 | 0.795481E+10 | 0.00 | 0.193365E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.161534E+11 | 0.00 | 0.262187E+12 | 0.00 | 0.596195E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.164513E+10 | 0.00 | 0.210887E+09 | 0.00 | 52180105.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.148592E+10 | 0.00 | 0.515254E+10 | 0.00 | 0.111350E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.164513E+10 | 0.00 | 0.132067E+11 | 0.00 | 0.268437E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.159206E+10 | 0.00 | 0.207245E+11 | 0.00 | 0.409306E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.164513E+10 | 0.00 | 0.481597E+10 | 0.00 | 0.105561E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.159206E+10 | 0.00 | 0.125483E+11 | 0.00 | 0.276211E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.164513E+10 | 0.00 | 0.203392E+11 | 0.00 | 0.475603E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.164513E+10 | 0.00 | 0.260658E+11 | 0.00 | 0.595267E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.159206E+10 | 0.00 | 0.542469E+10 | 0.00 | 0.123067E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.164513E+10 | 0.00 | 0.909510E+10 | 0.00 | 0.189170E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.159206E+10 | 0.00 | 0.124305E+11 | 0.00 | 0.251919E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.164513E+10 | 0.00 | 0.170038E+11 | 0.00 | 0.341860E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.193701E+11 | 0.00 | 0.147018E+12 | 0.00 | 0.315297E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.148592E+10 | 0.00 | 0.210887E+09 | 0.00 | 52180105.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.164513E+10 | 0.00 | 0.260658E+11 | 0.00 | 0.595267E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.311621E+11 | 0.00 | 0.00 | 48167793.40 | 0.00 | 0.00 | 0.349437E+11 | 0.00 | 0.39 |
February | 0.160393E+11 | 0.00 | 0.00 | 60786063.85 | 0.00 | 0.00 | 0.416624E+11 | 0.00 | 0.50 |
March | 0.314828E+10 | 0.00 | 0.00 | 0.102973E+09 | 0.00 | 0.00 | 0.677778E+11 | 0.00 | 0.62 |
April | 0.314722E+09 | 0.00 | 0.00 | 98775507.61 | 0.00 | 0.00 | 0.650821E+11 | 0.00 | 0.86 |
May | 0.147571E+09 | 41648468.26 | 0.00 | 0.102876E+09 | 6946804.94 | 0.00 | 0.631126E+11 | 0.00 | 1.04 |
June | 0.100395E+09 | 0.372625E+09 | 0.00 | 96141372.07 | 308204.83 | 0.00 | 0.471373E+11 | 0.00 | 1.24 |
July | 0.134799E+09 | 0.132524E+10 | 0.00 | 92570628.80 | 31222884.34 | 0.00 | 0.293300E+11 | 0.00 | 1.05 |
August | 0.132236E+09 | 0.928987E+09 | 0.00 | 0.109481E+09 | 51168691.54 | 0.00 | 0.413332E+11 | 0.00 | 1.27 |
September | 0.190240E+09 | 0.344031E+09 | 0.00 | 0.108264E+09 | 38666545.45 | 0.00 | 0.572008E+11 | 0.00 | 1.24 |
October | 0.365044E+09 | 0.00 | 0.00 | 0.121776E+09 | 0.00 | 0.00 | 0.715411E+11 | 0.00 | 1.03 |
November | 0.372463E+09 | 0.00 | 0.00 | 0.115943E+09 | 0.00 | 0.00 | 0.714582E+11 | 0.00 | 0.75 |
December | 0.774073E+10 | 0.00 | 0.00 | 94702523.66 | 0.00 | 0.00 | 0.619316E+11 | 0.00 | 0.50 |
Annual Sum or Average | 0.598478E+11 | 0.301253E+10 | 0.00 | 0.115246E+10 | 0.128313E+09 | 0.00 | 0.652511E+12 | 0.00 | 0.88 |
Minimum of Months | 0.100395E+09 | 0.00 | 0.00 | 48167793.40 | 0.00 | 0.00 | 0.293300E+11 | 0.00 | 0.39 |
Maximum of Months | 0.311621E+11 | 0.132524E+10 | 0.00 | 0.121776E+09 | 51168691.54 | 0.00 | 0.715411E+11 | 0.00 | 1.27 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.256947E+11 | 0.00 | 0.00 | 29965704.90 | 0.00 | 0.00 | 0.298681E+11 | 0.00 | 0.32 |
February | 0.105294E+11 | 0.00 | 0.00 | 48600779.88 | 0.00 | 0.00 | 0.374779E+11 | 0.00 | 0.40 |
March | 0.362464E+10 | 0.00 | 0.00 | 86847635.98 | 0.00 | 0.00 | 0.560351E+11 | 0.00 | 0.50 |
April | 0.413866E+10 | 0.00 | 0.00 | 89366227.44 | 0.00 | 0.00 | 0.545206E+11 | 0.00 | 0.74 |
May | 0.240423E+10 | 17260513.84 | 0.00 | 81542099.26 | 8127094.74 | 0.00 | 0.463731E+11 | 0.00 | 0.74 |
June | 0.509235E+10 | 0.209518E+09 | 0.00 | 84076347.00 | 11665009.72 | 0.00 | 0.366787E+11 | 0.00 | 0.99 |
July | 0.786939E+10 | 0.574742E+09 | 0.00 | 74051134.39 | 73232590.03 | 0.00 | 0.209895E+11 | 0.00 | 0.92 |
August | 0.998841E+10 | 0.411051E+09 | 0.00 | 91925711.72 | 51668322.91 | 0.00 | 0.320995E+11 | 0.00 | 1.13 |
September | 0.299013E+10 | 0.363967E+09 | 0.00 | 79747832.85 | 38417514.09 | 0.00 | 0.394025E+11 | 0.00 | 0.84 |
October | 0.266652E+10 | 0.00 | 0.00 | 89685250.15 | 0.00 | 0.00 | 0.511829E+11 | 0.00 | 0.74 |
November | 0.207000E+10 | 0.00 | 0.00 | 81601718.51 | 0.00 | 0.00 | 0.533072E+11 | 0.00 | 0.56 |
December | 0.450285E+10 | 0.00 | 0.00 | 70985385.87 | 0.00 | 0.00 | 0.543356E+11 | 0.00 | 0.40 |
Annual Sum or Average | 0.815713E+11 | 0.157654E+10 | 0.00 | 0.908396E+09 | 0.183111E+09 | 0.00 | 0.512271E+12 | 0.00 | 0.69 |
Minimum of Months | 0.207000E+10 | 0.00 | 0.00 | 29965704.90 | 0.00 | 0.00 | 0.209895E+11 | 0.00 | 0.32 |
Maximum of Months | 0.256947E+11 | 0.574742E+09 | 0.00 | 91925711.72 | 73232590.03 | 0.00 | 0.560351E+11 | 0.00 | 1.13 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.447278E+12 | 0.00 | 0.00 | 7118962.37 | 0.00 | 0.800834E+10 | 0.281972E+11 | 0.00 | 0.28 |
February | 0.302014E+12 | 0.00 | 0.00 | 71218469.88 | 0.00 | 0.111160E+10 | 0.770498E+11 | 0.00 | 0.31 |
March | 0.210514E+12 | 0.00 | 0.00 | 0.246748E+09 | 0.00 | 0.174160E+10 | 0.208617E+12 | 0.00 | 0.35 |
April | 0.861400E+11 | 0.00 | 0.00 | 0.398924E+09 | 0.00 | 0.00 | 0.289030E+12 | 0.00 | 0.48 |
May | 0.593925E+11 | 0.212542E+09 | 0.00 | 0.485130E+09 | 92709371.99 | 0.00 | 0.309334E+12 | 0.00 | 0.58 |
June | 0.278240E+11 | 0.224142E+10 | 0.00 | 0.654645E+09 | 0.132421E+09 | 0.00 | 0.286874E+12 | 0.00 | 0.77 |
July | 0.276080E+11 | 0.635647E+10 | 0.00 | 0.598692E+09 | 0.391135E+09 | 0.00 | 0.160476E+12 | 0.00 | 0.66 |
August | 0.240395E+11 | 0.442805E+10 | 0.00 | 0.694154E+09 | 0.505649E+09 | 0.00 | 0.239310E+12 | 0.00 | 0.76 |
September | 0.331535E+11 | 0.353985E+10 | 0.00 | 0.557377E+09 | 0.399625E+09 | 0.00 | 0.289591E+12 | 0.00 | 0.66 |
October | 0.701921E+11 | 0.00 | 0.00 | 0.440899E+09 | 0.00 | 0.00 | 0.295924E+12 | 0.00 | 0.51 |
November | 0.181929E+12 | 0.00 | 0.00 | 0.232189E+09 | 0.00 | 0.260939E+09 | 0.182485E+12 | 0.00 | 0.37 |
December | 0.334740E+12 | 0.00 | 0.00 | 70208556.84 | 0.00 | 0.222733E+10 | 0.893654E+11 | 0.00 | 0.29 |
Annual Sum or Average | 0.180482E+13 | 0.167783E+11 | 0.00 | 0.445730E+10 | 0.152154E+10 | 0.133498E+11 | 0.245625E+13 | 0.00 | 0.50 |
Minimum of Months | 0.240395E+11 | 0.00 | 0.00 | 7118962.37 | 0.00 | 0.00 | 0.281972E+11 | 0.00 | 0.28 |
Maximum of Months | 0.447278E+12 | 0.635647E+10 | 0.00 | 0.694154E+09 | 0.505649E+09 | 0.800834E+10 | 0.309334E+12 | 0.00 | 0.77 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.279884E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128829E+11 | 0.00 | 0.00 | 0.26 |
February | 0.283496E+11 | 0.00 | 0.00 | 422906.74 | 0.00 | 0.425743E+10 | 0.529180E+09 | 0.00 | 0.30 |
March | 0.284010E+11 | 0.00 | 0.00 | 3331245.76 | 0.00 | 0.248578E+10 | 0.399019E+10 | 0.00 | 0.31 |
April | 0.177433E+11 | 0.00 | 0.00 | 14807413.74 | 0.00 | 0.163632E+09 | 0.128224E+11 | 0.00 | 0.41 |
May | 0.123568E+11 | 10295807.91 | 0.00 | 28959690.94 | 5867295.50 | 0.334946E+09 | 0.199857E+11 | 0.00 | 0.54 |
June | 0.466792E+10 | 0.127572E+09 | 0.00 | 57813384.42 | 15050676.76 | 0.00 | 0.244345E+11 | 0.00 | 0.78 |
July | 0.333685E+10 | 0.411795E+09 | 0.00 | 58351878.77 | 33426000.13 | 0.00 | 0.143009E+11 | 0.00 | 0.68 |
August | 0.347178E+10 | 0.273927E+09 | 0.00 | 63775947.57 | 40355343.58 | 0.00 | 0.197349E+11 | 0.00 | 0.74 |
September | 0.862329E+10 | 0.308038E+09 | 0.00 | 34758594.54 | 31190147.18 | 0.00 | 0.177081E+11 | 0.00 | 0.60 |
October | 0.171939E+11 | 0.00 | 0.00 | 13206571.56 | 930536.24 | 0.281571E+09 | 0.104408E+11 | 0.00 | 0.42 |
November | 0.241025E+11 | 0.00 | 0.00 | 2190357.74 | 0.00 | 0.213373E+10 | 0.255669E+10 | 0.00 | 0.32 |
December | 0.277894E+11 | 0.00 | 0.00 | 97066.48 | 0.00 | 0.758103E+10 | 0.309845E+09 | 0.00 | 0.27 |
Annual Sum or Average | 0.204025E+12 | 0.113163E+10 | 0.00 | 0.277715E+09 | 0.126820E+09 | 0.301210E+11 | 0.126813E+12 | 0.00 | 0.47 |
Minimum of Months | 0.333685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.26 |
Maximum of Months | 0.284010E+11 | 0.411795E+09 | 0.00 | 63775947.57 | 40355343.58 | 0.128829E+11 | 0.244345E+11 | 0.00 | 0.78 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.256509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.367513E+10 | 0.00 | 0.00 | 0.27 |
February | 0.317128E+10 | 0.00 | 0.00 | 270449.84 | 0.00 | 0.133499E+10 | 0.216966E+09 | 0.00 | 0.30 |
March | 0.344503E+10 | 0.00 | 0.00 | 1429389.60 | 0.00 | 0.248544E+09 | 0.135032E+10 | 0.00 | 0.34 |
April | 0.217207E+10 | 0.00 | 0.00 | 4246670.45 | 0.00 | 0.00 | 0.314498E+10 | 0.00 | 0.57 |
May | 0.148912E+10 | 4803163.34 | 0.00 | 5875501.28 | 1019412.90 | 0.00 | 0.352887E+10 | 0.00 | 0.68 |
June | 0.876396E+09 | 39040296.55 | 0.00 | 10744828.26 | 1444578.11 | 0.00 | 0.444450E+10 | 0.00 | 1.11 |
July | 0.108883E+10 | 0.124355E+09 | 0.00 | 10689599.74 | 9185846.72 | 0.00 | 0.274962E+10 | 0.00 | 1.08 |
August | 0.145106E+10 | 85878537.50 | 0.00 | 10973477.52 | 6480957.38 | 0.00 | 0.354938E+10 | 0.00 | 1.19 |
September | 0.133590E+10 | 64085303.46 | 0.00 | 5753364.09 | 4818857.23 | 0.00 | 0.282798E+10 | 0.00 | 0.73 |
October | 0.230117E+10 | 0.00 | 0.00 | 3340968.75 | 0.00 | 0.00 | 0.229162E+10 | 0.00 | 0.52 |
November | 0.325077E+10 | 0.00 | 0.00 | 1062619.63 | 0.00 | 0.116301E+09 | 0.101124E+10 | 0.00 | 0.35 |
December | 0.381110E+10 | 0.00 | 0.00 | 135014.46 | 0.00 | 0.987606E+09 | 0.193053E+09 | 0.00 | 0.26 |
Annual Sum or Average | 0.269578E+11 | 0.318162E+09 | 0.00 | 54521883.62 | 22949652.34 | 0.636257E+10 | 0.253085E+11 | 0.00 | 0.62 |
Minimum of Months | 0.876396E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.26 |
Maximum of Months | 0.381110E+10 | 0.124355E+09 | 0.00 | 10973477.52 | 9185846.72 | 0.367513E+10 | 0.444450E+10 | 0.00 | 1.19 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.300621E+10 | 0.00 | 0.00 | 23459.02 | 0.00 | 0.337847E+10 | 32923327.69 | 0.00 | 0.44 |
February | 0.321314E+10 | 0.00 | 0.00 | 983550.31 | 0.00 | 0.126994E+10 | 0.636700E+09 | 0.00 | 0.51 |
March | 0.339017E+10 | 0.00 | 0.00 | 2813976.36 | 0.00 | 0.389850E+09 | 0.195259E+10 | 0.00 | 0.59 |
April | 0.256299E+10 | 0.00 | 0.00 | 5184527.85 | 0.00 | 3419238.72 | 0.352567E+10 | 0.00 | 0.97 |
May | 0.156400E+10 | 3345017.64 | 0.00 | 7324394.21 | 1077884.67 | 797479.58 | 0.442476E+10 | 0.00 | 1.18 |
June | 0.103383E+10 | 32741342.64 | 0.00 | 12351233.61 | 1527436.63 | 0.00 | 0.474039E+10 | 0.00 | 1.83 |
July | 0.118923E+10 | 93783376.71 | 0.00 | 12985822.98 | 9712731.12 | 0.00 | 0.327148E+10 | 0.00 | 1.86 |
August | 0.178944E+10 | 71038043.45 | 0.00 | 10459434.26 | 6660052.17 | 0.00 | 0.368337E+10 | 0.00 | 1.92 |
September | 0.148297E+10 | 51729354.64 | 0.00 | 6587528.45 | 5049457.00 | 0.00 | 0.324152E+10 | 0.00 | 1.24 |
October | 0.237696E+10 | 0.00 | 0.00 | 4167104.23 | 0.00 | 0.00 | 0.255790E+10 | 0.00 | 0.85 |
November | 0.333951E+10 | 0.00 | 0.00 | 1030681.04 | 0.00 | 0.236417E+09 | 0.101304E+10 | 0.00 | 0.55 |
December | 0.374868E+10 | 0.00 | 0.00 | 82928.92 | 0.00 | 0.143440E+10 | 94728673.62 | 0.00 | 0.43 |
Annual Sum or Average | 0.286971E+11 | 0.252637E+09 | 0.00 | 63994641.24 | 24027561.59 | 0.671329E+10 | 0.291751E+11 | 0.00 | 1.03 |
Minimum of Months | 0.103383E+10 | 0.00 | 0.00 | 23459.02 | 0.00 | 0.00 | 32923327.69 | 0.00 | 0.43 |
Maximum of Months | 0.374868E+10 | 93783376.71 | 0.00 | 12985822.98 | 9712731.12 | 0.337847E+10 | 0.474039E+10 | 0.00 | 1.92 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.349832E+10 | 0.00 | 0.00 | 2300579.85 | 0.00 | 0.350428E+10 | 0.213008E+10 | 0.00 | 0.41 |
February | 0.315446E+10 | 0.00 | 0.00 | 6830351.66 | 0.00 | 0.126130E+10 | 0.430856E+10 | 0.00 | 0.65 |
March | 0.367755E+10 | 0.00 | 0.00 | 8716363.09 | 0.00 | 0.362688E+09 | 0.621749E+10 | 0.00 | 0.75 |
April | 0.294302E+10 | 0.00 | 0.00 | 9124176.66 | 0.00 | 12480174.03 | 0.603837E+10 | 0.00 | 1.02 |
May | 0.219444E+10 | 6806606.66 | 0.00 | 9126725.11 | 1358887.68 | 50475333.38 | 0.527295E+10 | 0.00 | 1.05 |
June | 0.150145E+10 | 57059918.21 | 0.00 | 12899046.22 | 1923964.70 | 0.00 | 0.488208E+10 | 0.00 | 1.38 |
July | 0.153517E+10 | 0.179647E+09 | 0.00 | 13848464.98 | 12244826.43 | 0.00 | 0.312249E+10 | 0.00 | 1.38 |
August | 0.201579E+10 | 0.161395E+09 | 0.00 | 17270335.35 | 7018404.37 | 0.00 | 0.486713E+10 | 0.00 | 1.77 |
September | 0.158374E+10 | 0.165412E+09 | 0.00 | 13623682.41 | 3157880.34 | 0.00 | 0.596785E+10 | 0.00 | 1.46 |
October | 0.215001E+10 | 0.00 | 0.00 | 14534711.28 | 0.00 | 26502873.91 | 0.770733E+10 | 0.00 | 1.23 |
November | 0.302829E+10 | 0.00 | 0.00 | 7836982.77 | 0.00 | 0.345710E+09 | 0.552586E+10 | 0.00 | 0.73 |
December | 0.381649E+10 | 0.00 | 0.00 | 3937177.45 | 0.00 | 0.139070E+10 | 0.305306E+10 | 0.00 | 0.46 |
Annual Sum or Average | 0.310987E+11 | 0.570321E+09 | 0.00 | 0.120049E+09 | 25703963.53 | 0.695413E+10 | 0.590932E+11 | 0.00 | 1.03 |
Minimum of Months | 0.150145E+10 | 0.00 | 0.00 | 2300579.85 | 0.00 | 0.00 | 0.213008E+10 | 0.00 | 0.41 |
Maximum of Months | 0.381649E+10 | 0.179647E+09 | 0.00 | 17270335.35 | 12244826.43 | 0.350428E+10 | 0.770733E+10 | 0.00 | 1.77 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.479498E+10 | 0.00 | 0.00 | 203157.34 | 0.00 | 0.302026E+10 | 0.217699E+09 | 0.00 | 0.55 |
February | 0.448704E+10 | 0.00 | 0.00 | 2301634.71 | 0.00 | 0.284288E+09 | 0.193644E+10 | 0.00 | 0.70 |
March | 0.260056E+10 | 0.00 | 0.00 | 6771635.51 | 0.00 | 36779888.97 | 0.546355E+10 | 0.00 | 0.88 |
April | 0.761795E+09 | 0.00 | 0.00 | 14034889.45 | 0.00 | 0.00 | 0.857061E+10 | 0.00 | 1.62 |
May | 0.138575E+10 | 5489504.80 | 0.00 | 11117009.10 | 1352033.25 | 0.00 | 0.589413E+10 | 0.00 | 1.53 |
June | 0.800932E+09 | 55143813.79 | 0.00 | 16623720.41 | 547637.51 | 0.00 | 0.589067E+10 | 0.00 | 2.22 |
July | 0.901014E+09 | 0.197604E+09 | 0.00 | 18482266.18 | 7202434.36 | 0.00 | 0.413184E+10 | 0.00 | 2.22 |
August | 0.937326E+09 | 0.142120E+09 | 0.00 | 22680678.57 | 2003916.58 | 0.00 | 0.647546E+10 | 0.00 | 2.74 |
September | 0.120574E+10 | 0.108652E+09 | 0.00 | 8698122.26 | 1010785.56 | 0.00 | 0.429549E+10 | 0.00 | 1.54 |
October | 0.150932E+10 | 0.00 | 0.00 | 7983212.10 | 0.00 | 0.00 | 0.532145E+10 | 0.00 | 1.24 |
November | 0.248781E+10 | 0.00 | 0.00 | 5081957.21 | 0.00 | 1483915.10 | 0.426588E+10 | 0.00 | 0.86 |
December | 0.438145E+10 | 0.00 | 0.00 | 2881546.89 | 0.00 | 25839775.57 | 0.272106E+10 | 0.00 | 0.60 |
Annual Sum or Average | 0.262537E+11 | 0.509010E+09 | 0.00 | 0.116860E+09 | 12116807.26 | 0.336865E+10 | 0.551843E+11 | 0.00 | 1.39 |
Minimum of Months | 0.761795E+09 | 0.00 | 0.00 | 203157.34 | 0.00 | 0.00 | 0.217699E+09 | 0.00 | 0.55 |
Maximum of Months | 0.479498E+10 | 0.197604E+09 | 0.00 | 22680678.57 | 7202434.36 | 0.302026E+10 | 0.857061E+10 | 0.00 | 2.74 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.287085E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.738697E+11 | 0.00 | 0.00 | 0.34 |
February | 0.122395E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.385529E+11 | 0.00 | 0.00 | 0.32 |
March | 0.296143E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195749E+11 | 0.00 | 0.00 | 0.32 |
April | 0.286198E+11 | 0.00 | 0.00 | 6525089.35 | 0.00 | 0.364115E+10 | 0.530694E+10 | 0.00 | 0.38 |
May | 0.216866E+11 | 50536156.62 | 0.00 | 28191299.44 | 14229835.45 | 0.207191E+10 | 0.152594E+11 | 0.00 | 0.52 |
June | 0.883349E+10 | 0.441756E+09 | 0.00 | 76628827.61 | 16688131.80 | 0.00 | 0.293455E+11 | 0.00 | 0.85 |
July | 0.503578E+10 | 0.152404E+10 | 0.00 | 80497514.84 | 50568127.67 | 0.00 | 0.190537E+11 | 0.00 | 0.78 |
August | 0.884449E+10 | 0.103833E+10 | 0.00 | 68167224.92 | 63723755.09 | 0.00 | 0.201757E+11 | 0.00 | 0.77 |
September | 0.193630E+11 | 0.600963E+09 | 0.00 | 29783194.62 | 50362278.09 | 0.475623E+09 | 0.123297E+11 | 0.00 | 0.57 |
October | 0.296268E+11 | 0.00 | 0.00 | 5272371.27 | 0.00 | 0.301393E+10 | 0.361503E+10 | 0.00 | 0.40 |
November | 0.226677E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195306E+11 | 0.00 | 0.00 | 0.33 |
December | 0.874629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.491876E+11 | 0.00 | 0.00 | 0.31 |
Annual Sum or Average | 0.198149E+12 | 0.365563E+10 | 0.00 | 0.295066E+09 | 0.195572E+09 | 0.209918E+12 | 0.105086E+12 | 0.00 | 0.49 |
Minimum of Months | 0.287085E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
Maximum of Months | 0.296268E+11 | 0.152404E+10 | 0.00 | 80497514.84 | 63723755.09 | 0.738697E+11 | 0.293455E+11 | 0.00 | 0.85 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.915208E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.622906E+11 | 0.00 | 0.00 | 0.51 |
February | 0.182530E+11 | 0.00 | 0.00 | 1541802.68 | 0.00 | 0.347466E+11 | 0.111339E+10 | 0.00 | 0.55 |
March | 0.314203E+11 | 0.00 | 0.00 | 10479686.06 | 0.00 | 0.173064E+11 | 0.787462E+10 | 0.00 | 0.58 |
April | 0.246025E+11 | 0.00 | 0.00 | 33439205.14 | 0.00 | 0.284023E+10 | 0.240021E+11 | 0.00 | 0.82 |
May | 0.184932E+11 | 43515753.55 | 0.00 | 54750969.75 | 13231332.81 | 0.221271E+10 | 0.327392E+11 | 0.00 | 1.08 |
June | 0.873716E+10 | 0.424969E+09 | 0.00 | 0.117682E+09 | 18654657.31 | 0.00 | 0.425759E+11 | 0.00 | 1.71 |
July | 0.500341E+10 | 0.131966E+10 | 0.00 | 0.135741E+09 | 57267019.14 | 0.00 | 0.317585E+11 | 0.00 | 1.70 |
August | 0.889780E+10 | 0.107336E+10 | 0.00 | 0.100899E+09 | 71746552.04 | 0.00 | 0.341926E+11 | 0.00 | 1.65 |
September | 0.187561E+11 | 0.582662E+09 | 0.00 | 49365732.20 | 56744405.90 | 0.324117E+09 | 0.225799E+11 | 0.00 | 1.11 |
October | 0.295461E+11 | 0.00 | 0.00 | 17086317.78 | 0.00 | 0.198372E+10 | 0.112036E+11 | 0.00 | 0.74 |
November | 0.276952E+11 | 0.00 | 0.00 | 1088820.04 | 0.00 | 0.183774E+11 | 0.910202E+09 | 0.00 | 0.57 |
December | 0.149966E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.458095E+11 | 0.00 | 0.00 | 0.51 |
Annual Sum or Average | 0.215553E+12 | 0.344417E+10 | 0.00 | 0.522074E+09 | 0.217644E+09 | 0.185891E+12 | 0.208950E+12 | 0.00 | 0.96 |
Minimum of Months | 0.500341E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.51 |
Maximum of Months | 0.314203E+11 | 0.131966E+10 | 0.00 | 0.135741E+09 | 71746552.04 | 0.622906E+11 | 0.425759E+11 | 0.00 | 1.71 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.226229E+11 | 0.00 | 0.00 | 13795598.12 | 0.00 | 0.566538E+11 | 0.148221E+11 | 0.00 | 0.44 |
February | 0.258790E+11 | 0.00 | 0.00 | 57665024.75 | 0.00 | 0.255198E+11 | 0.341434E+11 | 0.00 | 0.65 |
March | 0.341628E+11 | 0.00 | 0.00 | 69138548.23 | 0.00 | 0.148831E+11 | 0.480962E+11 | 0.00 | 0.71 |
April | 0.279984E+11 | 0.00 | 0.00 | 69211913.93 | 0.00 | 0.295003E+10 | 0.438102E+11 | 0.00 | 0.86 |
May | 0.236038E+11 | 91300192.74 | 0.00 | 74841384.36 | 15931997.26 | 0.274709E+10 | 0.409806E+11 | 0.00 | 0.95 |
June | 0.144745E+11 | 0.708271E+09 | 0.00 | 0.105720E+09 | 14132438.07 | 0.00 | 0.377156E+11 | 0.00 | 1.18 |
July | 0.827621E+10 | 0.238815E+10 | 0.00 | 0.119098E+09 | 68955864.43 | 0.00 | 0.249088E+11 | 0.00 | 1.13 |
August | 0.110027E+11 | 0.229951E+10 | 0.00 | 0.147791E+09 | 68452862.83 | 0.00 | 0.380381E+11 | 0.00 | 1.43 |
September | 0.167572E+11 | 0.193271E+10 | 0.00 | 0.126112E+09 | 23258874.06 | 0.447139E+09 | 0.512436E+11 | 0.00 | 1.38 |
October | 0.221912E+11 | 0.00 | 0.00 | 0.130632E+09 | 0.00 | 0.160923E+10 | 0.647898E+11 | 0.00 | 1.14 |
November | 0.268699E+11 | 0.00 | 0.00 | 60290968.26 | 0.00 | 0.131842E+11 | 0.415632E+11 | 0.00 | 0.67 |
December | 0.294413E+11 | 0.00 | 0.00 | 20467991.48 | 0.00 | 0.349059E+11 | 0.174587E+11 | 0.00 | 0.46 |
Annual Sum or Average | 0.263280E+12 | 0.741994E+10 | 0.00 | 0.994765E+09 | 0.190732E+09 | 0.152900E+12 | 0.457570E+12 | 0.00 | 0.92 |
Minimum of Months | 0.827621E+10 | 0.00 | 0.00 | 13795598.12 | 0.00 | 0.00 | 0.148221E+11 | 0.00 | 0.44 |
Maximum of Months | 0.341628E+11 | 0.238815E+10 | 0.00 | 0.147791E+09 | 68955864.43 | 0.566538E+11 | 0.647898E+11 | 0.00 | 1.43 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.140506E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.616714E+11 | 0.00 | 0.00 | 0.54 |
February | 0.233837E+11 | 0.00 | 0.00 | 3731912.66 | 0.00 | 0.325090E+11 | 0.273912E+10 | 0.00 | 0.60 |
March | 0.377039E+11 | 0.00 | 0.00 | 10683762.41 | 0.00 | 0.157230E+11 | 0.859161E+10 | 0.00 | 0.65 |
April | 0.310020E+11 | 0.00 | 0.00 | 32755489.01 | 0.00 | 0.203209E+10 | 0.199293E+11 | 0.00 | 0.91 |
May | 0.219488E+11 | 51997868.22 | 0.00 | 64766360.38 | 17365833.30 | 0.191655E+10 | 0.312254E+11 | 0.00 | 1.17 |
June | 0.111095E+11 | 0.577225E+09 | 0.00 | 93385822.90 | 13403911.31 | 5285621.19 | 0.324094E+11 | 0.00 | 1.53 |
July | 0.636396E+10 | 0.222982E+10 | 0.00 | 0.101460E+09 | 22753026.94 | 0.00 | 0.202345E+11 | 0.00 | 1.38 |
August | 0.101529E+11 | 0.140138E+10 | 0.00 | 90295213.39 | 37679187.97 | 0.00 | 0.237145E+11 | 0.00 | 1.45 |
September | 0.219352E+11 | 0.101335E+10 | 0.00 | 43757734.68 | 9058105.41 | 0.340136E+09 | 0.186832E+11 | 0.00 | 1.15 |
October | 0.335850E+11 | 0.00 | 0.00 | 19081596.85 | 0.00 | 0.194331E+10 | 0.118578E+11 | 0.00 | 0.84 |
November | 0.313212E+11 | 0.00 | 0.00 | 4421792.44 | 0.00 | 0.155861E+11 | 0.410847E+10 | 0.00 | 0.62 |
December | 0.219126E+11 | 0.00 | 0.00 | 140952.08 | 0.00 | 0.429219E+11 | 0.265134E+09 | 0.00 | 0.55 |
Annual Sum or Average | 0.264469E+12 | 0.527378E+10 | 0.00 | 0.464481E+09 | 0.100260E+09 | 0.174649E+12 | 0.173758E+12 | 0.00 | 0.95 |
Minimum of Months | 0.636396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.54 |
Maximum of Months | 0.377039E+11 | 0.222982E+10 | 0.00 | 0.101460E+09 | 37679187.97 | 0.616714E+11 | 0.324094E+11 | 0.00 | 1.53 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 94716552.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.847262E+10 | 0.00 | 0.00 | 0.41 |
February | 0.497020E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.514221E+10 | 0.00 | 0.00 | 0.38 |
March | 0.183067E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.351853E+10 | 0.00 | 0.00 | 0.37 |
April | 0.266214E+10 | 0.00 | 0.00 | 256529.82 | 0.00 | 0.132877E+10 | 0.196898E+09 | 0.00 | 0.43 |
May | 0.249659E+10 | 2885959.20 | 0.00 | 1982459.68 | 851787.52 | 0.772939E+09 | 0.103534E+10 | 0.00 | 0.57 |
June | 0.123107E+10 | 23410952.35 | 0.00 | 7149800.83 | 2184989.43 | 39074235.30 | 0.252858E+10 | 0.00 | 0.88 |
July | 0.750793E+09 | 91934445.03 | 0.00 | 8011655.19 | 5020695.83 | 0.00 | 0.166679E+10 | 0.00 | 0.82 |
August | 0.114953E+10 | 61921602.89 | 0.00 | 6739530.28 | 5858606.94 | 18509884.23 | 0.172387E+10 | 0.00 | 0.78 |
September | 0.209253E+10 | 51036689.04 | 0.00 | 2185453.96 | 4801914.52 | 0.388843E+09 | 0.836676E+09 | 0.00 | 0.60 |
October | 0.247313E+10 | 0.00 | 0.00 | 102020.62 | 135091.06 | 0.135666E+10 | 70237411.97 | 0.00 | 0.45 |
November | 0.117986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.324816E+10 | 0.00 | 0.00 | 0.38 |
December | 0.301013E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.599456E+10 | 0.00 | 0.00 | 0.36 |
Annual Sum or Average | 0.167591E+11 | 0.231190E+09 | 0.00 | 26427450.40 | 18853085.30 | 0.302809E+11 | 0.805839E+10 | 0.00 | 0.54 |
Minimum of Months | 94716552.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
Maximum of Months | 0.266214E+10 | 91934445.03 | 0.00 | 8011655.19 | 5858606.94 | 0.847262E+10 | 0.252858E+10 | 0.00 | 0.88 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.256155E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.601491E+10 | 0.00 | 0.00 | 0.48 |
February | 0.121909E+10 | 0.00 | 0.00 | 5828.11 | 0.00 | 0.348791E+10 | 21867311.14 | 0.00 | 0.52 |
March | 0.235588E+10 | 0.00 | 0.00 | 393096.76 | 0.00 | 0.224498E+10 | 0.298751E+09 | 0.00 | 0.54 |
April | 0.199390E+10 | 0.00 | 0.00 | 2424225.38 | 0.00 | 0.860243E+09 | 0.175450E+10 | 0.00 | 0.76 |
May | 0.163525E+10 | 2222614.25 | 0.00 | 4645734.88 | 812899.61 | 0.516776E+09 | 0.283658E+10 | 0.00 | 1.04 |
June | 0.807204E+09 | 22685393.69 | 0.00 | 11675618.05 | 2085234.88 | 24997325.03 | 0.405766E+10 | 0.00 | 1.72 |
July | 0.468615E+09 | 79320381.64 | 0.00 | 14033818.17 | 4791478.57 | 0.00 | 0.312492E+10 | 0.00 | 1.75 |
August | 0.784056E+09 | 66252210.84 | 0.00 | 10593882.10 | 5493682.18 | 8530638.72 | 0.326444E+10 | 0.00 | 1.65 |
September | 0.155916E+10 | 51272065.32 | 0.00 | 4219048.04 | 4321319.48 | 0.241211E+09 | 0.189378E+10 | 0.00 | 1.06 |
October | 0.241007E+10 | 0.00 | 0.00 | 834097.25 | 128923.55 | 0.823149E+09 | 0.520416E+09 | 0.00 | 0.69 |
November | 0.163598E+10 | 0.00 | 0.00 | 291.41 | 0.00 | 0.239146E+10 | 2631221.85 | 0.00 | 0.55 |
December | 0.567018E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.460090E+10 | 0.00 | 0.00 | 0.47 |
Annual Sum or Average | 0.156924E+11 | 0.221753E+09 | 0.00 | 48825640.16 | 17633538.26 | 0.212151E+11 | 0.177755E+11 | 0.00 | 0.94 |
Minimum of Months | 0.256155E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.47 |
Maximum of Months | 0.241007E+10 | 79320381.64 | 0.00 | 14033818.17 | 5493682.18 | 0.601491E+10 | 0.405766E+10 | 0.00 | 1.75 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.147537E+10 | 0.00 | 0.00 | 587160.34 | 0.00 | 0.638546E+10 | 0.616576E+09 | 0.00 | 0.42 |
February | 0.197005E+10 | 0.00 | 0.00 | 3578758.40 | 0.00 | 0.320321E+10 | 0.219419E+10 | 0.00 | 0.58 |
March | 0.247219E+10 | 0.00 | 0.00 | 4923007.63 | 0.00 | 0.246933E+10 | 0.362924E+10 | 0.00 | 0.64 |
April | 0.228042E+10 | 0.00 | 0.00 | 5029119.48 | 0.00 | 0.112820E+10 | 0.363742E+10 | 0.00 | 0.80 |
May | 0.217673E+10 | 4344627.68 | 0.00 | 6450182.23 | 1055608.41 | 0.831242E+09 | 0.369630E+10 | 0.00 | 0.95 |
June | 0.155968E+10 | 36010935.73 | 0.00 | 10738437.29 | 2707826.96 | 47910794.59 | 0.363179E+10 | 0.00 | 1.23 |
July | 0.911438E+09 | 0.138417E+09 | 0.00 | 12988793.50 | 5011927.90 | 0.00 | 0.254457E+10 | 0.00 | 1.19 |
August | 0.116870E+10 | 0.134667E+09 | 0.00 | 15773827.72 | 5131121.31 | 22969265.04 | 0.378209E+10 | 0.00 | 1.46 |
September | 0.167314E+10 | 0.159290E+09 | 0.00 | 11124827.53 | 1500273.83 | 0.306136E+09 | 0.452158E+10 | 0.00 | 1.34 |
October | 0.222017E+10 | 250820.50 | 0.00 | 9203987.98 | 24083.15 | 0.687351E+09 | 0.465165E+10 | 0.00 | 1.03 |
November | 0.214805E+10 | 0.00 | 0.00 | 3307944.72 | 0.00 | 0.208146E+10 | 0.238745E+10 | 0.00 | 0.59 |
December | 0.188379E+10 | 0.00 | 0.00 | 1040972.04 | 0.00 | 0.436598E+10 | 0.853822E+09 | 0.00 | 0.42 |
Annual Sum or Average | 0.219397E+11 | 0.472981E+09 | 0.00 | 84747018.85 | 15430841.56 | 0.215292E+11 | 0.361467E+11 | 0.00 | 0.89 |
Minimum of Months | 0.911438E+09 | 0.00 | 0.00 | 587160.34 | 0.00 | 0.00 | 0.616576E+09 | 0.00 | 0.42 |
Maximum of Months | 0.247219E+10 | 0.159290E+09 | 0.00 | 15773827.72 | 5131121.31 | 0.638546E+10 | 0.465165E+10 | 0.00 | 1.46 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.541771E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.630333E+10 | 0.00 | 0.00 | 0.54 |
February | 0.145404E+10 | 0.00 | 0.00 | 222686.08 | 0.00 | 0.369524E+10 | 0.190144E+09 | 0.00 | 0.59 |
March | 0.260905E+10 | 0.00 | 0.00 | 756704.96 | 0.00 | 0.249718E+10 | 0.641625E+09 | 0.00 | 0.64 |
April | 0.287577E+10 | 0.00 | 0.00 | 2499470.57 | 0.00 | 0.767544E+09 | 0.158566E+10 | 0.00 | 0.90 |
May | 0.219187E+10 | 2870892.98 | 0.00 | 5783018.80 | 931358.49 | 0.565242E+09 | 0.282025E+10 | 0.00 | 1.20 |
June | 0.133591E+10 | 31185150.05 | 0.00 | 10474110.10 | 371996.91 | 23523490.53 | 0.303588E+10 | 0.00 | 1.61 |
July | 0.729054E+09 | 0.128122E+09 | 0.00 | 10860005.57 | 2196040.34 | 0.00 | 0.197989E+10 | 0.00 | 1.44 |
August | 0.109178E+10 | 79590626.09 | 0.00 | 9532534.00 | 3029348.87 | 20075760.07 | 0.223810E+10 | 0.00 | 1.46 |
September | 0.207956E+10 | 85250450.16 | 0.00 | 3868052.26 | 1002130.45 | 0.258613E+09 | 0.163628E+10 | 0.00 | 1.16 |
October | 0.282702E+10 | 0.00 | 0.00 | 1312420.76 | 147710.79 | 0.780928E+09 | 0.839565E+09 | 0.00 | 0.84 |
November | 0.207669E+10 | 0.00 | 0.00 | 145135.46 | 0.00 | 0.232085E+10 | 0.189936E+09 | 0.00 | 0.62 |
December | 0.104576E+10 | 0.00 | 0.00 | 1016.91 | 0.00 | 0.466884E+10 | 6033388.77 | 0.00 | 0.53 |
Annual Sum or Average | 0.208583E+11 | 0.327019E+09 | 0.00 | 45455155.47 | 7678585.83 | 0.219014E+11 | 0.151634E+11 | 0.00 | 0.96 |
Minimum of Months | 0.541771E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.53 |
Maximum of Months | 0.287577E+10 | 0.128122E+09 | 0.00 | 10860005.57 | 3029348.87 | 0.630333E+10 | 0.303588E+10 | 0.00 | 1.61 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 30247231.46 | 0.00 | 0.00 | 2103977.05 | 0.00 | 0.00 | 0.819559E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 7092035.63 | 0.00 | 0.00 | 0.645632E+09 | 0.00 | 0.28 |
March | 0.00 | 0.00 | 0.00 | 14016199.27 | 0.00 | 0.00 | 0.661413E+09 | 0.00 | 0.31 |
April | 0.00 | 0.00 | 0.00 | 17297123.72 | 0.00 | 0.00 | 0.462734E+09 | 0.00 | 0.29 |
May | 0.00 | 142422.41 | 0.00 | 3880166.77 | 0.00 | 0.00 | 0.407987E+09 | 0.00 | 0.29 |
June | 0.00 | 13405094.87 | 0.00 | 7380950.17 | 0.00 | 0.00 | 0.201136E+09 | 0.00 | 0.30 |
July | 0.00 | 21366682.38 | 0.00 | 8937191.91 | 0.00 | 0.00 | 81780477.87 | 0.00 | 0.28 |
August | 0.00 | 5608430.11 | 0.00 | 16200042.20 | 0.00 | 0.00 | 0.152330E+09 | 0.00 | 0.31 |
September | 0.00 | 11330887.37 | 0.00 | 3463155.27 | 0.00 | 0.00 | 0.257557E+09 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 8410369.61 | 0.00 | 0.00 | 0.439872E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 12151068.50 | 0.00 | 0.00 | 0.543898E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 16748579.99 | 0.00 | 0.00 | 0.716643E+09 | 0.00 | 0.28 |
Annual Sum or Average | 30247231.46 | 51853517.13 | 0.00 | 0.117681E+09 | 0.00 | 0.00 | 0.539054E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 2103977.05 | 0.00 | 0.00 | 81780477.87 | 0.00 | 0.28 |
Maximum of Months | 30247231.46 | 21366682.38 | 0.00 | 17297123.72 | 0.00 | 0.00 | 0.819559E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.366157E+10 | 0.00 | 0.00 | 5801847.72 | 0.00 | 0.00 | 0.476066E+10 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 53087169.12 | 0.00 | 0.00 | 0.647435E+10 | 0.00 | 0.28 |
March | 0.00 | 0.00 | 0.00 | 0.119170E+09 | 0.00 | 0.00 | 0.663464E+10 | 0.00 | 0.31 |
April | 0.00 | 0.00 | 0.00 | 0.157297E+09 | 0.00 | 0.00 | 0.464048E+10 | 0.00 | 0.29 |
May | 6215256.53 | 1352550.20 | 0.00 | 30710564.59 | 0.00 | 0.00 | 0.408636E+10 | 0.00 | 0.29 |
June | 0.00 | 0.132788E+09 | 0.00 | 68392617.15 | 0.00 | 0.00 | 0.201861E+10 | 0.00 | 0.30 |
July | 0.00 | 0.212789E+09 | 0.00 | 84797296.30 | 0.00 | 0.00 | 0.822445E+09 | 0.00 | 0.28 |
August | 0.00 | 58806518.12 | 0.00 | 0.152103E+09 | 0.00 | 0.00 | 0.152807E+10 | 0.00 | 0.31 |
September | 0.00 | 0.110737E+09 | 0.00 | 28247006.26 | 0.00 | 0.00 | 0.259683E+10 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 71409843.52 | 0.00 | 0.00 | 0.441078E+10 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 0.102809E+09 | 0.00 | 0.00 | 0.545669E+10 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 0.141139E+09 | 0.00 | 0.00 | 0.719055E+10 | 0.00 | 0.28 |
Annual Sum or Average | 0.366778E+10 | 0.516473E+09 | 0.00 | 0.101496E+10 | 0.00 | 0.00 | 0.506205E+11 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 5801847.72 | 0.00 | 0.00 | 0.822445E+09 | 0.00 | 0.28 |
Maximum of Months | 0.366157E+10 | 0.212789E+09 | 0.00 | 0.157297E+09 | 0.00 | 0.00 | 0.719055E+10 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.678280E+09 | 0.00 | 0.00 | 157823.59 | 0.00 | 0.00 | 0.144110E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 4301647.90 | 0.00 | 0.00 | 0.648375E+09 | 0.00 | 0.28 |
March | 0.00 | 0.00 | 0.00 | 10746576.06 | 0.00 | 0.00 | 0.664655E+09 | 0.00 | 0.31 |
April | 0.00 | 0.00 | 0.00 | 14877702.80 | 0.00 | 0.00 | 0.465073E+09 | 0.00 | 0.29 |
May | 34896180.25 | 137443.70 | 0.00 | 2555465.24 | 0.00 | 0.00 | 0.374084E+09 | 0.00 | 0.29 |
June | 0.00 | 13320347.55 | 0.00 | 6675836.68 | 0.00 | 0.00 | 0.202246E+09 | 0.00 | 0.30 |
July | 0.00 | 21285254.78 | 0.00 | 8448024.72 | 0.00 | 0.00 | 82393997.85 | 0.00 | 0.28 |
August | 0.00 | 5923640.35 | 0.00 | 15058217.28 | 0.00 | 0.00 | 0.152939E+09 | 0.00 | 0.31 |
September | 8714029.05 | 11065324.73 | 0.00 | 2344273.76 | 0.00 | 0.00 | 0.253011E+09 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 6146004.39 | 0.00 | 0.00 | 0.442384E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 9090155.01 | 0.00 | 0.00 | 0.546925E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 12962597.74 | 0.00 | 0.00 | 0.720307E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.721890E+09 | 51732011.11 | 0.00 | 93364325.16 | 0.00 | 0.00 | 0.469650E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 157823.59 | 0.00 | 0.00 | 82393997.85 | 0.00 | 0.28 |
Maximum of Months | 0.678280E+09 | 21285254.78 | 0.00 | 15058217.28 | 0.00 | 0.00 | 0.720307E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.218419E+09 | 0.00 | 0.00 | 0.230686E+11 | 0.00 | 0.32 |
February | 0.00 | 0.00 | 0.00 | 0.412609E+09 | 0.00 | 0.00 | 0.176873E+11 | 0.00 | 0.32 |
March | 0.00 | 0.00 | 0.00 | 0.727127E+09 | 0.00 | 0.00 | 0.179450E+11 | 0.00 | 0.35 |
April | 0.00 | 0.00 | 0.00 | 0.867158E+09 | 0.00 | 0.00 | 0.123150E+11 | 0.00 | 0.32 |
May | 0.00 | 0.00 | 0.00 | 0.218148E+09 | 0.00 | 0.00 | 0.110032E+11 | 0.00 | 0.33 |
June | 0.00 | 0.269504E+09 | 0.00 | 0.375646E+09 | 0.00 | 0.00 | 0.532263E+10 | 0.00 | 0.34 |
July | 0.00 | 0.422087E+09 | 0.00 | 0.455601E+09 | 0.00 | 0.00 | 0.221469E+10 | 0.00 | 0.31 |
August | 0.00 | 0.00 | 0.00 | 0.923505E+09 | 0.00 | 0.00 | 0.556270E+10 | 0.00 | 0.35 |
September | 0.00 | 0.251382E+09 | 0.00 | 0.194292E+09 | 0.00 | 0.00 | 0.667172E+10 | 0.00 | 0.32 |
October | 0.00 | 0.00 | 0.00 | 0.440954E+09 | 0.00 | 0.00 | 0.114136E+11 | 0.00 | 0.32 |
November | 0.00 | 0.00 | 0.00 | 0.631724E+09 | 0.00 | 0.00 | 0.145819E+11 | 0.00 | 0.32 |
December | 0.00 | 0.00 | 0.00 | 0.873332E+09 | 0.00 | 0.00 | 0.192692E+11 | 0.00 | 0.32 |
Annual Sum or Average | 0.00 | 0.942973E+09 | 0.00 | 0.633851E+10 | 0.00 | 0.00 | 0.147056E+12 | 0.00 | 0.33 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.194292E+09 | 0.00 | 0.00 | 0.221469E+10 | 0.00 | 0.31 |
Maximum of Months | 0.00 | 0.422087E+09 | 0.00 | 0.923505E+09 | 0.00 | 0.00 | 0.230686E+11 | 0.00 | 0.35 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 09:04:16
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.278697E+12 | 0.462086E+11 | 0.00 | 0.156850E+13 | 0.712895E+12 |
February | 0.370989E+12 | 0.359822E+11 | 0.00 | 0.146403E+13 | 0.979545E+12 |
March | 0.634067E+12 | 0.337901E+11 | 0.00 | 0.176609E+13 | 0.147019E+13 |
April | 0.679298E+12 | 0.241966E+11 | 0.00 | 0.188876E+13 | 0.189056E+13 |
May | 0.893533E+12 | 0.239761E+11 | 0.00 | 0.184771E+13 | 0.854507E+12 |
June | 0.976867E+12 | 0.124638E+11 | 0.00 | 0.158002E+13 | 0.181704E+13 |
July | 0.967421E+12 | 0.819149E+10 | 0.00 | 0.127517E+13 | 0.286145E+13 |
August | 0.805540E+12 | 0.889510E+10 | 0.00 | 0.143801E+13 | 0.311509E+13 |
September | 0.607817E+12 | 0.160225E+11 | 0.00 | 0.163654E+13 | 0.114635E+13 |
October | 0.400836E+12 | 0.232776E+11 | 0.00 | 0.197528E+13 | 0.115589E+13 |
November | 0.221335E+12 | 0.325591E+11 | 0.00 | 0.173945E+13 | 0.143687E+13 |
December | 0.183253E+12 | 0.412661E+11 | 0.00 | 0.155986E+13 | 0.192068E+13 |
Annual Sum or Average | 0.701965E+13 | 0.306829E+12 | 0.00 | 0.197394E+14 | 0.193611E+14 |
Minimum of Months | 0.183253E+12 | 0.819149E+10 | 0.00 | 0.127517E+13 | 0.712895E+12 |
Maximum of Months | 0.976867E+12 | 0.462086E+11 | 0.00 | 0.197528E+13 | 0.311509E+13 |