Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:04
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860
Simulation Timestamp: 2023-10-16 09:04:39
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:39
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 29722.06 | 641.66 | 641.66 |
Net Site Energy | 29722.06 | 641.66 | 641.66 |
Total Source Energy | 90321.17 | 1949.92 | 1949.92 |
Net Source Energy | 90321.17 | 1949.92 | 1949.92 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1121.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 3472.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 2745.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 449.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 15213.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1914.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2283.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 620.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 1130.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4966.52 |
Humidification | 14.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.29 |
Heat Recovery | 48.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 706.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 27893.64 | 1828.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7251.98 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 1121.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 3472.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 2745.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 449.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5871.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 59.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 1848.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 5.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 2283.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 620.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 1130.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4966.52 |
Humidification | General | 14.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.29 |
Heat Recovery | General | 48.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Water Heater | 0.00 | 706.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 1121.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 3472.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 2745.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 449.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 15213.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 1914.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 2283.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 620.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 1130.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4966.52 |
Humidification | Unassigned | 14.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.29 |
Heat Recovery | Unassigned | 48.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 706.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 68.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 162.39 | 39.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.16 |
Other | 370.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 602.19 | 39.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.16 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 68.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 162.39 | 39.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.16 |
Other | 370.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 602.19 | 39.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.16 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 27893.641 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 27893.641 | 100.00 |
Total On-Site and Utility Electric Sources | 27893.641 | 100.00 |
Total Electricity End Uses | 27893.641 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 470.49 | 33.91 |
Air to Air Heat Recovery for Heating | 916.94 | 66.09 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 1387.43 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 7251.98 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 7251.98 | 100.00 |
Total Water End Uses | 7251.98 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 56.00 |
Time Setpoint Not Met During Occupied Cooling | 405.67 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5939.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_NEWYORK
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| HEATSYS1 BOILER | CENTRAL BOILER |DXReportMonthly
| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |FanReportMonthly
| CAV_BAS FAN | VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:39
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:04 |
RunPeriod | RUNPERIOD 1 |
Weather File | New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 |
Latitude [deg] | 40.65 |
Longitude [deg] | -73.8 |
Elevation [m] | 5.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 3476.85 | 1043.06 | 695.37 | 1043.06 | 695.37 |
Gross Window-Wall Ratio [%] | 28.54 | 28.54 | 28.54 | 28.54 | 28.54 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 3476.85 | 1043.06 | 695.37 | 1043.06 | 695.37 |
Gross Window-Wall Ratio [%] | 28.54 | 28.54 | 28.54 | 28.54 | 28.54 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 7.6202 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.6202 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.6202 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.6202 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 7.6202 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 7.6202 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 7.6202 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 7.6202 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 86.92 | 86.92 | 7.6202 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 57.95 | 57.95 | 7.6202 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 86.92 | 86.92 | 7.6202 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 57.95 | 57.95 | 7.6202 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 7.6202 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 7.6202 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 7.6202 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 7.6202 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.5114 | 18.58 | 215.2992 |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.5114 | 18.58 | 215.2992 |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.5114 | 18.58 | 215.2992 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 7.6202 | 18.58 | 484.4232 |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 3476.85 | 3476.85 | 7.6661 | 18.58 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 3476.85 | 3476.85 | 7.6661 | 18.58 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 2779.43 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 7.6202 | 18.58 | 4.8418 | |
CORE_BOTTOM | 2496.12 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 7.6202 | 18.58 | 8.0697 | |
CORE_MID | 2496.12 | Yes | Yes | 10.00 | CORE_MID | GENERAL | CORE_MID | 7.6202 | 18.58 | 8.0696 | |
CORE_TOP | 2496.12 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 7.6202 | 18.58 | 8.0696 | |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 7.6202 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 7.6202 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 7.6202 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 7.6202 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 7.6202 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 7.6202 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 7.6202 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 7.6202 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 7.6202 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 7.6202 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 7.6202 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 7.6202 | 18.58 | 8.0699 | |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | GROUNDFLOOR_PLENUM | GENERAL | GROUNDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 10.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_BOT_ZN_6 | GENERAL | DATACENTER_BOT_ZN_6 | 12.5114 | 18.58 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 10.00 | DATACENTER_MID_ZN_6 | GENERAL | DATACENTER_MID_ZN_6 | 12.5114 | 18.58 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_TOP_ZN_6 | GENERAL | DATACENTER_TOP_ZN_6 | 12.5114 | 18.58 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1.00 | DATACENTER_BASEMENT_ZN_6 | GENERAL | DATACENTER_BASEMENT_ZN_6 | 7.6202 | 18.58 | 484.4232 | |
Total | 46320.38 | 7.6661 | 9.29 | 17.8789 | |||||||
Conditioned Total | 46320.38 | 7.6661 | 9.29 | 17.8789 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 42757.27 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 46320.38 | 46320.38 | 0.00 | 42757.27 | 2.3561 | 60.38 | 10.8345 |
Total | 46320.38 | 46320.38 | 0.00 | 42757.27 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:39
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 22-AUG-14:39 | 02-JAN-05:10 | - | - | - | - | - | - | - | - | - | - | 30-AUG-15:50 |
Heating | 0.00 | 1746492.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 445167.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 234435.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 794004.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 37754.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 283348.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 70698.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 90459.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 3742.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 5695.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1959609.74 | 1752188.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 1746492.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 445167.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 234435.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 320838.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 3711.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 33930.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 112.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 283348.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 70698.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 90459.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 3742.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 5695.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:39
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1215.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 10998.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 8695.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 1422.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 48180.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 6062.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 7232.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1965.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 3580.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 45.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 154.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 766.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 88339.16 | 1982.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 26.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 237.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 187.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 30.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1040.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 130.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 156.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 42.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 77.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 3.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 16.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1907.13 | 42.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 26.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 237.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 187.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 30.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1040.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 130.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 156.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 42.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 77.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 3.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 16.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1907.13 | 42.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:39
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
BASEMENT DIRECT AIR | 5.28 |
DATACENTER_BOT_ZN_6 DIRECT AIR | 0.472311 |
DATACENTER_MID_ZN_6 DIRECT AIR | 4.51 |
DATACENTER_TOP_ZN_6 DIRECT AIR | 0.459345 |
DATACENTER_BASEMENT_ZN_6 DIRECT AIR | 21.30 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 5.61 | 0.338841 | 0.340000 | 1.91 | 0.903576 | 0.500000 | 0.001124 | 0.000176 | 1.91 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 52.76 | 0.360524 | 0.355000 | 18.73 | 0.961399 | 0.500000 | 0.001057 | 0.004447 | 18.73 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 5.37 | 0.354089 | 0.356000 | 1.91 | 0.944237 | 0.500000 | 0.001076 | 0.000811 | 2.76 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.934792 | 0.255480 | 0.256000 | 0.239307 | 0.681279 | 0.500000 | 0.001491 | 0.000141 | 0.479133 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 1.04 | 0.147752 | 0.200000 | 0.208329 | 0.394006 | 0.500000 | 0.002579 | 0.000096 | 0.327529 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.26 | 0.188908 | 0.200000 | 0.252849 | 0.503754 | 0.500000 | 0.002017 | 0.000155 | 0.528177 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 1.30 | 0.118174 | 0.200000 | 0.260472 | 0.315131 | 0.500000 | 0.003224 | 0.000076 | 0.260472 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 8.84 | 0.270076 | 0.266000 | 2.35 | 0.720203 | 0.500000 | 0.001411 | 0.002378 | 8.12 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 10.94 | 0.140644 | 0.200000 | 2.19 | 0.375050 | 0.500000 | 0.002709 | 0.001562 | 5.33 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 12.32 | 0.193852 | 0.200000 | 2.46 | 0.516938 | 0.500000 | 0.001965 | 0.002355 | 8.04 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 11.42 | 0.134737 | 0.200000 | 2.28 | 0.359298 | 0.500000 | 0.002828 | 0.001517 | 5.18 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 1.04 | 0.229537 | 0.236000 | 0.245545 | 0.612099 | 0.500000 | 0.001660 | 0.000305 | 1.04 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.12 | 0.137150 | 0.200000 | 0.224433 | 0.365734 | 0.500000 | 0.002778 | 0.000199 | 0.681083 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.36 | 0.175922 | 0.200000 | 0.271513 | 0.469125 | 0.500000 | 0.002166 | 0.000302 | 1.03 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.23 | 0.124926 | 0.200000 | 0.246394 | 0.333135 | 0.500000 | 0.003050 | 0.000197 | 0.672064 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 20089.51 | 0.000176 | 406.82 |
CORE_MID VAV BOX REHEAT COIL | 508268.08 | 0.004447 | 12344.87 |
CORE_TOP VAV BOX REHEAT COIL | 92710.99 | 0.000811 | 2447.39 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 16065.01 | 0.000141 | 423.79 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 10980.27 | 0.000096 | 289.64 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 17706.24 | 0.000155 | 467.04 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 8694.95 | 0.000076 | 228.91 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 271829.17 | 0.002378 | 7166.71 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 178600.17 | 0.001562 | 4708.67 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 269201.03 | 0.002355 | 7097.46 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 173446.66 | 0.001517 | 4572.86 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 34830.21 | 0.000305 | 918.14 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 22799.52 | 0.000199 | 601.00 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 34513.29 | 0.000302 | 909.79 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 22497.72 | 0.000197 | 593.04 |
VAV_BOT WITH REHEAT HEATING COIL | 69798.50 | 0.000611 | 1119.89 |
VAV_MID WITH REHEAT HEATING COIL | 717380.55 | 0.006276 | 11389.18 |
VAV_TOP WITH REHEAT HEATING COIL | 70617.11 | 0.000618 | 1132.48 |
CAV_BAS HEATING COIL | 270970.20 | 0.002371 | 5947.01 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT | 5.08 | 2.87 | 10.16 | 2.87 | 9.25 | 9.25 | 0.300000 | 0.310289 | 9.25 |
VAV_MID WITH REHEAT | 48.14 | 28.02 | 96.29 | 40.18 | 86.39 | 86.39 | 0.300000 | 0.465108 | 86.39 |
VAV_TOP WITH REHEAT | 5.06 | 2.90 | 10.12 | 6.19 | 9.32 | 9.32 | 0.300000 | 0.663446 | 9.32 |
CAV_BAS | 5.28 | 5.28 | 5.28 | 5.28 | 5.28 | 5.28 | 1.00 | 1.00 | 5.28 |
AIRLOOP DATACENTER BASEMENT | 21.30 | 21.30 | 21.30 | 21.30 | 21.30 | 21.30 | 1.00 | 0.999988 | 21.30 |
AIRLOOP DATACENTER BOT | 0.472311 | 0.472311 | 0.472311 | 0.472311 | 0.472311 | 0.472311 | 1.00 | 1.00 | 0.472311 |
AIRLOOP DATACENTER MID | 4.51 | 4.51 | 4.51 | 4.51 | 4.51 | 4.51 | 1.00 | 1.00 | 4.51 |
AIRLOOP DATACENTER TOP | 0.459345 | 0.459345 | 0.459345 | 0.459345 | 0.459345 | 0.459345 | 1.00 | 1.00 | 0.459345 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 9.25 | |
VAV_MID WITH REHEAT_OA_CONTROLLER | 86.39 | |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 9.32 | |
CAV_BAS_OA_CONTROLLER | 5.28 | 1.20 |
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | 21.30 | 0.338393 |
AIRLOOP DATACENTER BOT_OA_CONTROLLER | 0.472311 | 0.015632 |
AIRLOOP DATACENTER MID_OA_CONTROLLER | 4.51 | 0.156323 |
AIRLOOP DATACENTER TOP_OA_CONTROLLER | 0.459345 | 0.015632 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT OA HEAT RECOVERY | 2.54 |
VAV_MID WITH REHEAT OA HEAT RECOVERY | 25.38 |
VAV_TOP WITH REHEAT OA HEAT RECOVERY | 2.54 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT COOLING COIL | 26.33 | 6.67 | 10.95 | 0.010417 | 0.008500 | 229200.72 | 0.009751 | 9.25 |
VAV_MID WITH REHEAT COOLING COIL | 26.58 | 6.67 | 10.95 | 0.010661 | 0.008500 | 2231858.92 | 0.094948 | 86.39 |
VAV_TOP WITH REHEAT COOLING COIL | 26.20 | 6.67 | 10.95 | 0.010393 | 0.008500 | 228877.65 | 0.009737 | 9.32 |
CAV_BAS COOLING COIL | 24.70 | 6.67 | 11.42 | 0.010148 | 0.008500 | 112810.89 | 0.004799 | 5.28 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 9.25 |
VAV_MID WITH REHEAT FAN | 86.39 |
VAV_TOP WITH REHEAT FAN | 9.32 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.009751 | 0.000049 |
VAV_BOT WITH REHEAT_HEATC_CONTROLLER | 0.000611 | |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.094948 | 0.000005 |
VAV_MID WITH REHEAT_HEATC_CONTROLLER | 0.006276 | |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.009737 | 0.000049 |
VAV_TOP WITH REHEAT_HEATC_CONTROLLER | 0.000618 | |
CAV_BAS_COOLC_CONTROLLER | 0.004799 | 0.000099 |
CAV_BAS_HEATC_CONTROLLER | 0.002371 |
Design Size Maximum Flow Rate [m3/s] | |
CAV_BAS FAN | 5.28 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Total Cooling Capacity [W] | Design Size Rated Sensible Cooling Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | 21.30 | 430959.38 | 311115.05 | 0.010554 |
AIRLOOP DATACENTER BOT COOLING COIL | 0.472311 | 9507.01 | 6877.70 | 0.000233 |
AIRLOOP DATACENTER MID COOLING COIL | 4.51 | 90854.16 | 65670.26 | 0.002225 |
AIRLOOP DATACENTER TOP COOLING COIL | 0.459345 | 9256.47 | 6692.41 | 0.000227 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | 21.30 | 21.30 | 21.30 | 21.30 | 430959.38 | 430959.38 | 20749.82 | 1.00 |
AIRLOOP DATACENTER BOT DXAC HEAT PUMP | 0.472311 | 0.472311 | 0.472311 | 0.472311 | 9507.01 | 9507.01 | 958.56 | 1.00 |
AIRLOOP DATACENTER MID DXAC HEAT PUMP | 4.51 | 4.51 | 4.51 | 4.51 | 90854.16 | 90854.16 | 9585.56 | 1.00 |
AIRLOOP DATACENTER TOP DXAC HEAT PUMP | 0.459345 | 0.459345 | 0.459345 | 0.459345 | 9256.47 | 9256.47 | 958.56 | 1.00 |
Design Size Maximum Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | 21.30 |
AIRLOOP DATACENTER BOT SUPPLY FAN | 0.472311 |
AIRLOOP DATACENTER MID SUPPLY FAN | 4.51 |
AIRLOOP DATACENTER TOP SUPPLY FAN | 0.459345 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Heating Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | 21.30 | 430959.38 | 0.010554 |
AIRLOOP DATACENTER BOT HEATING COIL | 0.472311 | 9507.01 | 0.000233 |
AIRLOOP DATACENTER MID HEATING COIL | 4.51 | 90854.16 | 0.002225 |
AIRLOOP DATACENTER TOP HEATING COIL | 0.459345 | 9256.47 | 0.000227 |
Design Size Nominal Capacity [W] | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | 20749.82 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | 958.56 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | 9585.56 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | 958.56 |
Design Size Nominal Capacity Volume [m3/s] | User-Specified Nominal Capacity Volume [m3/s] | Design Size Rated Power [W] | User-Specified Rated Power [W] | |
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | 0.000173 | 0.000037 | 96450.70 | 100000.00 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.119235 | 24569.99 | |
HEATSYS1 PUMP | 0.024592 | 7405.98 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.119235 | 14.31 |
HEATSYS1 | 0.024592 | 2.95 |
COOLSYS1_SUPPLY | 0.119235 | 14.31 |
SINGLE WATER PLANT LOOP | 0.013239 | 1.59 |
SWHSYS1 | 0.000440 | 0.052800 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.119235 | 0.119235 | 500490.75 | 5.60 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 2810999.16 | 2810999.16 | 0.024592 |
CENTRAL BOILER | 545320.80 | 534724.26 | 0.013239 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP | 0.119235 | 17010.64 |
PLANT CIRC PUMP | 0.013239 | 3376.53 |
SWHSYS1 PUMP | 0.000440 | 5.96 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Water Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.119235 | 0.059885 | 1411115.27 | 1417827.83 | 0.070163 |
COOLSYS1 CHILLER2 | 0.119235 | 0.059885 | 1411115.27 | 1417827.83 | 0.070163 |
Design Water Flow Rate [m3/s] | Air Flow Rate at High Fan Speed [m3/s] | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | Air Flow Rate at Low Fan Speed [m3/s] | Fan Power at Low Fan Speed [W] | U-factor Times Area Value at Low Fan Speed [W/C] | |
CENTRAL TOWER | 0.013239 | 139666.47 | 59495.76 | 69833.23 | 7879.72 | 21436.87 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000440 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.140326 | 16.84 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.140326 | 42263.16 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 54.26 | 1682223.24 | 10.85 | 210277.90 |
TOWERWATERSYS COOLTOWER 2 | 54.26 | 1682223.24 | 10.85 | 210277.90 |
Design Water Flow Rate [m3/s] Equipment # 47 | |
WSHPPLANT OPERATION SCHEME | 0.072877 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:39
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:39
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:39
VersionVersion ID | |
1 | 22.1.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 14.00 | 7.30 | 3.30 | 1.20 | -0.20 | 5.60 | 10.90 | 16.10 | 21.70 | 25.00 | 24.80 | 19.90 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 | 40.65 | -73.80 | -5.00 | 5.00 | 101265 | 1.2036 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 12.47 | 25.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 105.88 | 86.92 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 71.89 | 57.95 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 105.88 | 86.92 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 71.89 | 57.95 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 7.620 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 12.462 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 12.511 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 227.811 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 12.511 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 227.811 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 12.511 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 227.811 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 18.579 | 5.382E-002 | 7.620 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 492.043 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DATACENTER_BOT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | DATACENTER_MID_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | DATACENTER_TOP_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | DATACENTER_BASEMENT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 42.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 42 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_OFFICE | BASEMENT | 2779.43 | 149.6 | 21179.739 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 21179.739 |
2 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 2496.12 | 134.4 | 19020.895 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 19020.895 |
3 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 2496.12 | 134.4 | 19020.895 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 19020.895 |
4 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 2496.12 | 134.4 | 19020.895 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 19020.895 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2388.263 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2388.263 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1539.088 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1539.088 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2388.315 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2388.315 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1539.088 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1539.088 |
9 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2388.263 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2388.263 |
10 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1539.088 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1539.088 |
11 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2388.315 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2388.315 |
12 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1539.088 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1539.088 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2388.263 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2388.263 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1539.088 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1539.088 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2388.315 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2388.315 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1539.088 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1539.088 |
17 | DATACENTER_BASEMENT_LIGHTS | LTG_SCH_OFFICE | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 5971.780 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5971.780 |
18 | DATACENTER_BOT_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 452.948 | 12.511 | 232.447 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 452.948 |
19 | DATACENTER_MID_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 452.948 | 12.511 | 232.447 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 452.948 |
20 | DATACENTER_TOP_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 452.948 | 12.511 | 232.447 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 452.948 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 379632.522 | 484.423 | 9000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.464 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
9 | NONRES_EXT_WALL_GRD | 20 | 3 | 9 | 0.167 | 1.339 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | NONRES_EXT_WALL_MID | 21 | 3 | 9 | 0.167 | 1.260 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | NONRES_EXT_WALL_TOP | 22 | 3 | 9 | 0.167 | 1.694 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | BASEMENT_WALL_EAST_CFACTOR | 39 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_SOUTH_CFACTOR | 40 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BASEMENT_WALL_NORTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 42 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 43 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 44 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2887 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5795 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6262 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4230 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
32 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
33 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
34 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
35 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.4637404 | 3.4637404 | 3.4637404 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
47 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
48 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
49 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
50 | 9 | 0.13684007E-14 | 0.43769670E-16 | -0.13032795E-09 | -0.34517937E-17 |
51 | 8 | 0.19139952E-07 | 0.17580734E-12 | 0.34842432E-03 | -0.21762784E-09 |
52 | 7 | -0.11363040E-01 | 0.94207812E-08 | -0.21820187E-01 | 0.12920189E-03 |
53 | 6 | 0.38147639 | 0.33245073E-05 | 0.45170425 | -0.44663469E-02 |
54 | 5 | -4.9575440 | 0.12566514E-03 | -4.2844407 | 0.60294545E-01 |
55 | 4 | 31.971915 | 0.10393916E-02 | 20.826829 | -0.40843520 |
56 | 3 | -109.03212 | 0.22875987E-02 | -54.410870 | 1.4834967 |
57 | 2 | 194.95586 | 0.12980373E-02 | 76.763178 | -2.8661744 |
58 | 1 | -170.36074 | 0.13969006E-03 | -54.933270 | 2.7315001 |
59 | 0 | 57.057407 | 0.80219562E-06 | 15.613236 | |
60 | 9 | 0.17296484E-14 | 0.42300129E-16 | -0.13408130E-09 | -0.44058463E-17 |
61 | 8 | 0.19671007E-07 | 0.16641005E-12 | 0.35423406E-03 | -0.22366611E-09 |
62 | 7 | -0.11537194E-01 | 0.88593938E-08 | -0.22071206E-01 | 0.13118209E-03 |
63 | 6 | 0.38620962 | 0.31182457E-05 | 0.45575528 | -0.45221398E-02 |
64 | 5 | -5.0037487 | 0.11760487E-03 | -4.3156427 | 0.60867449E-01 |
65 | 4 | 32.176377 | 0.97077592E-03 | 20.948989 | -0.41114975 |
66 | 3 | -109.46738 | 0.21328008E-02 | -54.652468 | 1.4897847 |
67 | 2 | 195.38754 | 0.12083052E-02 | 76.984396 | -2.8730290 |
68 | 1 | -170.52030 | 0.12984550E-03 | -54.996922 | 2.7342967 |
69 | 0 | 57.057407 | 0.74448799E-06 | 15.602172 | |
70 | 9 | 0.10997584E-14 | 0.53843923E-16 | -0.11326114E-09 | -0.28570046E-17 |
71 | 8 | 0.16725364E-07 | 0.21557791E-12 | 0.32127585E-03 | -0.19017314E-09 |
72 | 7 | -0.10546704E-01 | 0.11930081E-07 | -0.20642631E-01 | 0.11991984E-03 |
73 | 6 | 0.35928609 | 0.42648229E-05 | 0.43264702 | -0.42047803E-02 |
74 | 5 | -4.7408821 | 0.16300219E-03 | -4.1373754 | 0.57608138E-01 |
75 | 4 | 31.012880 | 0.13615538E-02 | 20.250423 | -0.39570291 |
76 | 3 | -106.98970 | 0.30226891E-02 | -53.270634 | 1.4539929 |
77 | 2 | 192.92930 | 0.17282771E-02 | 75.720319 | -2.8339965 |
78 | 1 | -169.61128 | 0.18730106E-03 | -54.635416 | 2.7183650 |
79 | 0 | 57.057407 | 0.10839563E-05 | 15.666826 | |
80 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
81 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
82 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
83 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
84 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
85 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
86 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
87 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
88 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
89 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
90 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
91 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
92 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
93 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
94 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
95 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
96 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
97 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
98 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
99 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
100 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
101 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
102 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
103 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
104 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
105 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
106 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
107 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
108 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
109 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
110 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
111 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
112 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
113 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
114 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
115 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
116 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
117 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
118 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
119 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
120 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
121 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
122 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
123 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
124 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
125 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
126 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
127 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.3822_SHGC_EAST_0.36 | 35 | 1 | VerySmooth | 2.171 | 2.171 | 1.000 | 0.361 | ||
2 | WINDOW_U_0.3822_SHGC_SOUTH_0.36 | 36 | 1 | VerySmooth | 2.171 | 2.171 | 1.000 | 0.361 | ||
3 | WINDOW_U_0.3822_SHGC_WEST_0.36 | 37 | 1 | VerySmooth | 2.171 | 2.171 | 1.000 | 0.361 | ||
4 | WINDOW_U_0.3822_SHGC_NORTH_0.36 | 38 | 1 | VerySmooth | 2.171 | 2.171 | 1.000 | 0.361 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 3.43662E-002 | 0.27318 | 0.51756 | 0.51756 | 0.36000 | 0.14234 | 0.19141 | 0.00000 | 0.84000 | 0.84000 | 0.11924 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 3.43662E-002 | 0.27318 | 0.51756 | 0.51756 | 0.36000 | 0.14234 | 0.19141 | 0.00000 | 0.84000 | 0.84000 | 0.11924 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 3.43662E-002 | 0.27318 | 0.51756 | 0.51756 | 0.36000 | 0.14234 | 0.19141 | 0.00000 | 0.84000 | 0.84000 | 0.11924 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 3.43662E-002 | 0.27318 | 0.51756 | 0.51756 | 0.36000 | 0.14234 | 0.19141 | 0.00000 | 0.84000 | 0.84000 | 0.11924 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_BOT_ZN_3 | 5 | 0 |
2 | PERIMETER_BOT_ZN_2 | 3 | 0 |
3 | PERIMETER_BOT_ZN_1 | 5 | 0 |
4 | PERIMETER_BOT_ZN_4 | 3 | 0 |
5 | PERIMETER_MID_ZN_3 | 1 | 0 |
6 | PERIMETER_MID_ZN_2 | 1 | 0 |
7 | PERIMETER_MID_ZN_1 | 1 | 0 |
8 | PERIMETER_MID_ZN_4 | 1 | 0 |
9 | PERIMETER_TOP_ZN_3 | 1 | 0 |
10 | PERIMETER_TOP_ZN_2 | 1 | 0 |
11 | PERIMETER_TOP_ZN_1 | 1 | 0 |
12 | PERIMETER_TOP_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_BOT_ZN_3 | 0 | |
2 | PERIMETER_BOT_ZN_2 | 0 | |
3 | PERIMETER_BOT_ZN_1 | 0 | |
4 | PERIMETER_BOT_ZN_4 | 0 | |
5 | PERIMETER_MID_ZN_3 | 0 | |
6 | PERIMETER_MID_ZN_2 | 0 | |
7 | PERIMETER_MID_ZN_1 | 0 | |
8 | PERIMETER_MID_ZN_4 | 0 | |
9 | PERIMETER_TOP_ZN_3 | 0 | |
10 | PERIMETER_TOP_ZN_2 | 0 | |
11 | PERIMETER_TOP_ZN_1 | 0 | |
12 | PERIMETER_TOP_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 1.1356 | 87921.3 | 0.496 | 7.5104E-002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 4.384E-005 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.5291E-003 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.5308E-003 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.9532E-003 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.9547E-003 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.2216E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.2228E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.7698E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.7704E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.5696E-003 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.6906E-003 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.9875E-003 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.0934E-003 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.2512E-003 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.3391E-003 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.7873E-003 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.8319E-003 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1208 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.2531E-002 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1373 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.0500E-002 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 9.0010E-002 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.6925E-002 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.7170E-002 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.3047E-002 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.5718E-003 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.7013E-003 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.9898E-003 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.1044E-003 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.2532E-003 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.3467E-003 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.7877E-003 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.8332E-003 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.5289E-003 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.5307E-003 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.9531E-003 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.9546E-003 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.2215E-003 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.2227E-003 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.7697E-003 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.7704E-003 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.8941E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.1365E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.6887E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.9537E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.5298E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.6368E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.0284E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.0591E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.4374E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.2710E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.1421E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.0485E-002 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.6660E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.9684E-002 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.8227E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.4292E-002 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.8199E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.9036E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.5929E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.6535E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.4957E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.5194E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.0285E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.0596E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.8382E-003 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8399E-003 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5600E-003 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5614E-003 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.3805E-003 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3815E-003 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7698E-003 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7704E-003 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.8761E-003 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.9749E-003 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5908E-003 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.6687E-003 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.4056E-003 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.4612E-003 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7878E-003 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8333E-003 |
81 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9500E-002 |
82 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7124E-002 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.2773E-002 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2960E-002 |
85 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.2994E-002 |
86 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 9.1344E-003 |
87 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.7170E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3043E-002 |
89 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.8751E-003 |
90 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.9726E-003 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5897E-003 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.6661E-003 |
93 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.4040E-003 |
94 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.4566E-003 |
95 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7873E-003 |
96 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8320E-003 |
97 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.8381E-003 |
98 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8398E-003 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5600E-003 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5613E-003 |
101 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.3805E-003 |
102 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3814E-003 |
103 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7697E-003 |
104 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7704E-003 |
105 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.7111E-003 |
106 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.7955E-003 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.4569E-003 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.5179E-003 |
109 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.4078E-003 |
110 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.4310E-003 |
111 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.0286E-003 |
112 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.0596E-003 |
113 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.2274E-002 |
114 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.1860E-002 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.8824E-002 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.9434E-002 |
117 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.4842E-002 |
118 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.8944E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.8227E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.4292E-002 |
121 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.7808E-003 |
122 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.0062E-003 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.5472E-003 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.7906E-003 |
125 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.4412E-003 |
126 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.5452E-003 |
127 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.0283E-003 |
128 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.0590E-003 |
129 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1103 |
130 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 7.9013E-002 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1210 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 8.8006E-002 |
133 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 9.3366E-002 |
134 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 5.0391E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 4.2949E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 2.0811E-002 |
137 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.1091E-002 |
138 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.1347E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.7879E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.8721E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.2954E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.7483E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.3948E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.1031E-002 |
145 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.5192E-002 |
146 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.4890E-002 |
147 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.7875E-002 |
148 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.9612E-002 |
149 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.8060E-002 |
150 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.5254E-002 |
151 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.2949E-002 |
152 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.0807E-002 |
153 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 4.8814E-002 |
154 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.0233E-002 |
155 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 4.5059E-002 |
156 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.7338E-002 |
157 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.1002E-002 |
158 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.6550E-002 |
159 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 4.3948E-002 |
160 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.1031E-002 |
161 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1102 |
162 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 7.9120E-002 |
163 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1208 |
164 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 8.8135E-002 |
165 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 9.3379E-002 |
166 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 5.0492E-002 |
167 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 4.2998E-002 |
168 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 2.0851E-002 |
169 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.1061E-002 |
170 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.1374E-002 |
171 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.7860E-002 |
172 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.8749E-002 |
173 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.2970E-002 |
174 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.7529E-002 |
175 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.3994E-002 |
176 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.1071E-002 |
177 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.5146E-002 |
178 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.4900E-002 |
179 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.7844E-002 |
180 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.9621E-002 |
181 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.8074E-002 |
182 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.5277E-002 |
183 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.2998E-002 |
184 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.0847E-002 |
185 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 4.8782E-002 |
186 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.0258E-002 |
187 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 4.5038E-002 |
188 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.7363E-002 |
189 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.1017E-002 |
190 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.6595E-002 |
191 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 4.3994E-002 |
192 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.1071E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 73318.86467 | 73318.86467 | 5.28010 | 5.28010 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 26.62400 | 1.41098E-002 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20016 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -10.70000 | 1.50390E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
3 | CORE_BOTTOM | Cooling | 77948.18478 | 77948.18478 | 5.61338 | 5.61338 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 26.62400 | 1.41098E-002 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
4 | CORE_BOTTOM | Heating | 1101.61439 | 1101.61439 | 4.70658E-002 | 1.07782 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
5 | CORE_MID | Cooling | 732804.18102 | 732804.18102 | 52.75769 | 52.75769 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 26.62400 | 1.41098E-002 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
6 | CORE_MID | Heating | 319779.23227 | 319779.23227 | 13.51351 | 13.51351 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
7 | CORE_TOP | Cooling | 74603.57039 | 74603.57039 | 5.37166 | 5.37166 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 26.62400 | 1.41098E-002 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
8 | CORE_TOP | Heating | 64925.78402 | 64925.78402 | 2.76084 | 2.76084 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 12859.32364 | 12859.32364 | 0.93479 | 0.93479 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 32.10000 | 1.41196E-002 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 11251.76827 | 11251.76827 | 0.47913 | 0.47913 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 14329.30653 | 14329.30653 | 1.04164 | 1.04164 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:50:00 | 27.79567 | 1.41119E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 7689.61278 | 7689.61278 | 0.32753 | 0.32753 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 17391.45837 | 17391.45837 | 1.26425 | 1.26425 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 31.73000 | 1.41190E-002 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 12398.78676 | 12398.78676 | 0.52818 | 0.52818 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 17915.91563 | 17915.91563 | 1.30236 | 1.30236 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 31.26133 | 1.41181E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 6079.89807 | 6079.89807 | 0.25870 | 0.25870 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
17 | PERIMETER_MID_ZN_3 | Cooling | 121634.60486 | 121634.60486 | 8.84271 | 8.84271 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 32.10000 | 1.41196E-002 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 190303.58515 | 190303.58515 | 8.11716 | 8.11716 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 150524.29801 | 150524.29801 | 10.94289 | 10.94289 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 28.23967 | 1.41127E-002 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 125034.84725 | 125034.84725 | 5.33343 | 5.33343 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 169466.74063 | 169466.74063 | 12.32001 | 12.32001 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 | 31.79167 | 1.41191E-002 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 188465.86832 | 188465.86832 | 8.03858 | 8.03858 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 157123.95550 | 157123.95550 | 11.42266 | 11.42266 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 31.16267 | 1.41180E-002 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 121431.04503 | 121431.04503 | 5.17937 | 5.17937 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 14002.82321 | 14002.82321 | 1.01802 | 1.01802 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 32.10000 | 1.41196E-002 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 24380.82272 | 24380.82272 | 1.04044 | 1.04044 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 15435.41838 | 15435.41838 | 1.12216 | 1.12216 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 28.44933 | 1.41131E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 15959.51643 | 15959.51643 | 0.68108 | 0.68108 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 18673.39240 | 18673.39240 | 1.35757 | 1.35757 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 31.91500 | 1.41193E-002 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 24159.19478 | 24159.19478 | 1.03097 | 1.03097 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 16945.87606 | 16945.87606 | 1.23197 | 1.23197 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 31.26133 | 1.41181E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 15748.43641 | 15748.43641 | 0.67206 | 0.67206 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 8237.99884 | 8237.99884 | 0.47231 | 0.47231 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 29.58400 | 1.41151E-002 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | -10.70000 | 1.50390E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
35 | DATACENTER_MID_ZN_6 | Cooling | 78598.84137 | 78598.84137 | 4.50636 | 4.50636 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 29.58400 | 1.41151E-002 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15632 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | -10.70000 | 1.50390E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
37 | DATACENTER_TOP_ZN_6 | Cooling | 8011.81532 | 8011.81532 | 0.45935 | 0.45935 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 29.76900 | 1.41154E-002 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | -10.70000 | 1.50390E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 371512.58824 | 371512.58824 | 21.29966 | 21.29966 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 25.36600 | 1.41076E-002 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33839 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 03:50:00 | -10.70000 | 1.50390E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV_BOT WITH REHEAT | Cooling | Sensible | 144101.03 | 9.24784 | 9.24784 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV_BOT WITH REHEAT | Heating | Sensible | 72120.43 | 2.67136 | 2.67136 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 |
3 | VAV_MID WITH REHEAT | Cooling | Sensible | 1328271.32 | 86.39302 | 86.39302 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | VAV_MID WITH REHEAT | Heating | Sensible | 720953.29 | 40.18205 | 40.18205 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:10:00 |
5 | VAV_TOP WITH REHEAT | Cooling | Sensible | 151138.33 | 9.32315 | 9.32315 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | VAV_TOP WITH REHEAT | Heating | Sensible | 72077.12 | 6.18540 | 6.18540 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:20:00 |
7 | CAV_BAS | Cooling | Sensible | 75760.41 | 5.28010 | 5.28010 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | CAV_BAS | Heating | Sensible | 73592.09 | 1.20016 | 1.20016 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
9 | AIRLOOP DATACENTER BASEMENT | Cooling | Sensible | 367420.18 | 21.29992 | 21.29992 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | AIRLOOP DATACENTER BASEMENT | Heating | Sensible | 20749.82 | 0.33839 | 0.33839 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
11 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 8160.05 | 0.47231 | 0.47231 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | AIRLOOP DATACENTER BOT | Heating | Sensible | 958.56 | 1.56323E-002 | 1.56323E-002 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
13 | AIRLOOP DATACENTER MID | Cooling | Sensible | 77872.30 | 4.50636 | 4.50636 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | AIRLOOP DATACENTER MID | Heating | Sensible | 9585.56 | 0.15632 | 0.15632 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
15 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 7940.31 | 0.45935 | 0.45935 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
16 | AIRLOOP DATACENTER TOP | Heating | Sensible | 958.56 | 1.56323E-002 | 1.56323E-002 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | BASEMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 5.28010 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.61338 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.33884 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.34000 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.90855 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.90358 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.12442E-003 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.75752E-004 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.90855 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
13 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 20089.50992 |
14 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.75752E-004 |
15 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 406.82197 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 52.75769 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.36052 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.35500 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 18.72898 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.96140 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.05679E-003 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.44655E-003 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 18.72898 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
27 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 508268.08469 |
28 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.44655E-003 |
29 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 12344.87102 |
30 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.37166 |
31 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.35409 |
32 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.35600 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.91231 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.94424 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.07600E-003 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.11076E-004 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.76084 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
40 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
41 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 92710.98843 |
42 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.11076E-004 |
43 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2447.38867 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.93479 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.25548 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.25600 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.23931 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.68128 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.49131E-003 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.40544E-004 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.47913 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
55 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 16065.00510 |
56 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.40544E-004 |
57 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 423.78769 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.04164 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14775 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20833 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.39401 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.57864E-003 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.60602E-005 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.32753 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
69 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10980.27029 |
70 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.60602E-005 |
71 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 289.63586 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.26425 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18891 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.25285 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.50375 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.01686E-003 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.54902E-004 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.52818 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
83 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 17706.23583 |
84 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.54902E-004 |
85 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 467.04402 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.30236 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11817 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.26047 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.31513 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.22406E-003 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.60672E-005 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.26047 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
97 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 8694.95004 |
98 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.60672E-005 |
99 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 228.90717 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 8.84271 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.27008 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.26600 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.35216 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.72020 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.41071E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.37808E-003 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 8.11716 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 271829.16870 |
112 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.37808E-003 |
113 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 7166.70630 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 10.94289 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14064 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.18858 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.37505 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.70897E-003 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.56247E-003 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 5.33343 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
124 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
125 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 178600.16647 |
126 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.56247E-003 |
127 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 4708.66536 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 12.32001 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19385 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.46400 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.51694 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.96542E-003 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.35509E-003 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 8.03858 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
138 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
139 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 269201.02998 |
140 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.35509E-003 |
141 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 7097.45928 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 11.42266 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13474 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.28453 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.35930 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.82774E-003 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.51739E-003 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 5.17937 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
152 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
153 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 173446.65596 |
154 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.51739E-003 |
155 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 4572.86341 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.04044 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22954 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.23600 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.24554 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.61210 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.65986E-003 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.04710E-004 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.04044 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
166 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
167 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 34830.21446 |
168 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.04710E-004 |
169 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 918.14073 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.12216 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13715 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.22443 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.36573 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.77797E-003 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.99460E-004 |
178 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.68108 |
179 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
180 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
181 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 22799.51513 |
182 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.99460E-004 |
183 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 600.99820 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.35757 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17592 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.27151 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.46913 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.16573E-003 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.01937E-004 |
192 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.03097 |
193 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
194 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
195 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 34513.28767 |
196 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.01937E-004 |
197 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 909.79017 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.23197 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12493 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.24639 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.33314 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.04981E-003 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.96820E-004 |
206 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.67206 |
207 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
208 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
209 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 22497.71516 |
210 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.96820E-004 |
211 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 593.04446 |
212 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BOT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.47231 |
213 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_MID_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.50636 |
214 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_TOP_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.45935 |
215 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BASEMENT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 21.29966 |
216 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.07821 |
217 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.86951 |
218 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 10.15642 |
219 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 2.86951 |
220 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 9.24784 |
221 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 9.24784 |
222 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
223 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.31029 |
224 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 48.14298 |
225 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 28.01825 |
226 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 96.28596 |
227 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 40.18205 |
228 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 86.39302 |
229 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 86.39302 |
230 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
231 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.46511 |
232 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.06190 |
233 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.90019 |
234 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 10.12380 |
235 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 6.18540 |
236 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 9.32315 |
237 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 9.32315 |
238 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
239 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.66345 |
240 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.28010 |
241 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 5.28010 |
242 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.28010 |
243 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 5.28010 |
244 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.28010 |
245 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 5.28010 |
246 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
247 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
248 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 21.29966 |
249 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 21.29966 |
250 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 21.29966 |
251 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Heating Design Air Flow Rate [m3/s] | 21.29966 |
252 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Cooling Design Air Flow Rate [m3/s] | 21.29992 |
253 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Main Design Air Flow Rate [m3/s] | 21.29992 |
254 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | User Heating Air Flow Ratio [] | 1.00000 |
255 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Calculated Heating Air Flow Ratio [] | 0.99999 |
256 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.47231 |
257 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.47231 |
258 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.47231 |
259 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.47231 |
260 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.47231 |
261 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.47231 |
262 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
263 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
264 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.50636 |
265 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.50636 |
266 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.50636 |
267 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 4.50636 |
268 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.50636 |
269 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.50636 |
270 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
271 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
272 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.45935 |
273 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.45935 |
274 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.45935 |
275 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.45935 |
276 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.45935 |
277 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.45935 |
278 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
279 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
280 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 9.24784 |
281 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 86.39302 |
282 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 9.32315 |
283 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 5.28010 |
284 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Design Supply Air Flow Rate [m3/s] | 21.29992 |
285 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.47231 |
286 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 4.50636 |
287 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.45935 |
288 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 9.24784 |
289 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_BOT WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.53819 |
290 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.33437 |
291 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
292 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.94742 |
293 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.04167E-002 |
294 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
295 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 229200.72335 |
296 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 9.75073E-003 |
297 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 9.24784 |
298 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 69798.50194 |
299 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.10628E-004 |
300 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1119.88615 |
301 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 9.24784 |
302 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 9.75073E-003 |
303 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 4.88364E-005 |
304 | Controller:WaterCoil | VAV_BOT WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.10628E-004 |
305 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 86.39302 |
306 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_MID WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 25.38195 |
307 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.57797 |
308 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
309 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.94824 |
310 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.06611E-002 |
311 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
312 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 2231858.92395 |
313 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 9.49484E-002 |
314 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 86.39302 |
315 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 717380.54921 |
316 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.27596E-003 |
317 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 11389.17724 |
318 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 86.39302 |
319 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 9.49484E-002 |
320 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 5.01525E-006 |
321 | Controller:WaterCoil | VAV_MID WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.27596E-003 |
322 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 9.32315 |
323 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_TOP WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.53819 |
324 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.20376 |
325 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
326 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.94734 |
327 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.03926E-002 |
328 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
329 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 228877.65226 |
330 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 9.73698E-003 |
331 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 9.32315 |
332 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 70617.11296 |
333 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.17789E-004 |
334 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1132.48301 |
335 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 9.32315 |
336 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 9.73698E-003 |
337 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 4.89053E-005 |
338 | Controller:WaterCoil | VAV_TOP WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.17789E-004 |
339 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.28010 |
340 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.20016 |
341 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 24.70431 |
342 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
343 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.42380 |
344 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.01478E-002 |
345 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
346 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Coil Load [W] | 112810.89057 |
347 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.79924E-003 |
348 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 5.28010 |
349 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Rated Capacity [W] | 270970.19768 |
350 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.37057E-003 |
351 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 5947.01436 |
352 | Fan:ConstantVolume | CAV_BAS FAN | Design Size Maximum Flow Rate [m3/s] | 5.28010 |
353 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.79924E-003 |
354 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 9.92221E-005 |
355 | Controller:WaterCoil | CAV_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.37057E-003 |
356 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 21.29992 |
357 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.33839 |
358 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 21.29992 |
359 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 430959.38432 |
360 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 311115.04699 |
361 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.05542E-002 |
362 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 21.29992 |
363 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 21.29992 |
364 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 21.29992 |
365 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 21.29992 |
366 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 430959.38432 |
367 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 430959.38432 |
368 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 20749.82071 |
369 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
370 | Fan:OnOff | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 21.29992 |
371 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 21.29992 |
372 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Heating Capacity [W] | 430959.38432 |
373 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.05542E-002 |
374 | Coil:Heating:Electric | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 20749.82071 |
375 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Nominal Capacity Volume [m3/s] | 1.72692E-004 |
376 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Nominal Capacity Volume [m3/s] | 3.72000E-005 |
377 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Rated Power [W] | 96450.69782 |
378 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Rated Power [W] | 100000.00000 |
379 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.47231 |
380 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
381 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.47231 |
382 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9507.00802 |
383 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6877.69865 |
384 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.32826E-004 |
385 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.47231 |
386 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.47231 |
387 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.47231 |
388 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.47231 |
389 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9507.00802 |
390 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9507.00802 |
391 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 958.55576 |
392 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
393 | Fan:OnOff | AIRLOOP DATACENTER BOT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.47231 |
394 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.47231 |
395 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Heating Capacity [W] | 9507.00802 |
396 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.32826E-004 |
397 | Coil:Heating:Electric | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 958.55576 |
398 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.50636 |
399 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.15632 |
400 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.50636 |
401 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 90854.15736 |
402 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 65670.26171 |
403 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.22501E-003 |
404 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 4.50636 |
405 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 4.50636 |
406 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 4.50636 |
407 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 4.50636 |
408 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Heating Capacity [W] | 90854.15736 |
409 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 90854.15736 |
410 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 9585.55755 |
411 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
412 | Fan:OnOff | AIRLOOP DATACENTER MID SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 4.50636 |
413 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.50636 |
414 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Heating Capacity [W] | 90854.15736 |
415 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.22501E-003 |
416 | Coil:Heating:Electric | AIRLOOP DATACENTER MID_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 9585.55755 |
417 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.45935 |
418 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
419 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.45935 |
420 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9256.46997 |
421 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6692.40897 |
422 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.26690E-004 |
423 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.45935 |
424 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.45935 |
425 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.45935 |
426 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.45935 |
427 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9256.46997 |
428 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9256.46997 |
429 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 958.55576 |
430 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
431 | Fan:OnOff | AIRLOOP DATACENTER TOP SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.45935 |
432 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.45935 |
433 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Heating Capacity [W] | 9256.46997 |
434 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.26690E-004 |
435 | Coil:Heating:Electric | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 958.55576 |
436 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 0.11924 |
437 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 24569.99400 |
438 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 0.11924 |
439 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 14.30825 |
440 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 0.11924 |
441 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 0.11924 |
442 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 500490.74824 |
443 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 5.60000 |
444 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 2.45918E-002 |
445 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 2.95102 |
446 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 2.45918E-002 |
447 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 7405.98434 |
448 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
449 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 2810999.15962 |
450 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 2810999.16000 |
451 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 2.45918E-002 |
452 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 0.11924 |
453 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 14.30825 |
454 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 0.11924 |
455 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 17010.63565 |
456 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 0.11924 |
457 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 5.98850E-002 |
458 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1411115.26935 |
459 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1417827.83500 |
460 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Water Flow Rate [m3/s] | 7.01630E-002 |
461 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 0.11924 |
462 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 5.98850E-002 |
463 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 1411115.26935 |
464 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 1417827.83500 |
465 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Water Flow Rate [m3/s] | 7.01630E-002 |
466 | PlantLoop | SINGLE WATER PLANT LOOP | Maximum Loop Flow Rate [m3/s] | 1.32387E-002 |
467 | PlantLoop | SINGLE WATER PLANT LOOP | Plant Loop Volume [m3] | 1.58864 |
468 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Flow Rate [m3/s] | 1.32387E-002 |
469 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Power Consumption [W] | 3376.52962 |
470 | FluidCooler:TwoSpeed | CENTRAL TOWER | Design Water Flow Rate [m3/s] | 1.32387E-002 |
471 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at High Fan Speed [m3/s] | 139666.46671 |
472 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | 59495.75544 |
473 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at Low Fan Speed [m3/s] | 69833.23335 |
474 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fan Power at Low Fan Speed [W] | 7879.72339 |
475 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at Low Fan Speed [W/C] | 21436.86697 |
476 | Boiler:HotWater | CENTRAL BOILER | Design Size Nominal Capacity [W] | 545320.79648 |
477 | Boiler:HotWater | CENTRAL BOILER | User-Specified Nominal Capacity [W] | 534724.26000 |
478 | Boiler:HotWater | CENTRAL BOILER | Design Size Design Water Flow Rate [m3/s] | 1.32387E-002 |
479 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
480 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
481 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
482 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 5.95776 |
483 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
484 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 0.14033 |
485 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 16.83913 |
486 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 0.14033 |
487 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 42263.16412 |
488 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 54.25705 |
489 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 1682223.23500 |
490 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 10.85141 |
491 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 210277.90438 |
492 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 54.25705 |
493 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 1682223.23500 |
494 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 10.85141 |
495 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 210277.90438 |
496 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 7.28775E-002 |
497 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 7.28775E-002 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 19048.34 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 481462.57 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 87852.81 |
4 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 15221.19 |
5 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 10403.40 |
6 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 16775.96 |
7 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 8235.14 |
8 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 257524.30 |
9 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 169200.88 |
10 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 255034.76 |
11 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 164319.03 |
12 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 32996.29 |
13 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 21599.00 |
14 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 32696.08 |
15 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 21313.10 |
16 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | 50927.45 |
17 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | 511629.54 |
18 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | 51479.24 |
19 | Coil:Heating:Water | CAV_BAS HEATING COIL | 211120.40 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | 244431.25 | 166932.50 | 77498.75 | 0.68 | 25391.95 | 257.54 |
2 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | 2321644.02 | 1577540.74 | 744103.28 | 0.68 | 241744.39 | 2451.91 |
3 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | 245551.89 | 167886.16 | 77665.73 | 0.68 | 25510.38 | 258.74 |
4 | Coil:Cooling:Water | CAV_BAS COOLING COIL | 129663.06 | 90516.25 | 39146.82 | 0.70 | 13187.83 | 133.76 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | 6.84 | 23.33 |
2 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | 6.84 | 23.33 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.419 | 0.394 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.339 | 1.115 | 105.88 | 200.61 | 105.88 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.36 | N/A | 2.171 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.36 | N/A | 2.171 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.36 | N/A | 2.171 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.36 | N/A | 2.171 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.36 | N/A | 2.171 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.339 | 1.115 | 71.89 | 133.74 | 71.89 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_EAST_0.36 | N/A | 2.171 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_EAST_0.36 | N/A | 2.171 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_EAST_0.36 | N/A | 2.171 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.339 | 1.115 | 105.88 | 200.61 | 105.88 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.36 | N/A | 2.171 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.36 | N/A | 2.171 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.36 | N/A | 2.171 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.36 | N/A | 2.171 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.36 | N/A | 2.171 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.339 | 1.115 | 71.89 | 133.74 | 71.89 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_WEST_0.36 | N/A | 2.171 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_WEST_0.36 | N/A | 2.171 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_WEST_0.36 | N/A | 2.171 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.260 | 1.060 | 113.68 | 200.61 | 113.68 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.36 | N/A | 2.171 | No | 86.92 | 86.92 | 86.92 | 0.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.260 | 1.060 | 75.79 | 133.74 | 75.79 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_EAST_0.36 | N/A | 2.171 | No | 57.95 | 57.95 | 57.95 | 90.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.260 | 1.060 | 113.68 | 200.61 | 113.68 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.36 | N/A | 2.171 | No | 86.92 | 86.92 | 86.92 | 180.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.260 | 1.060 | 75.79 | 133.74 | 75.79 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_WEST_0.36 | N/A | 2.171 | No | 57.95 | 57.95 | 57.95 | 270.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.694 | 1.351 | 113.68 | 200.61 | 113.68 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.36 | N/A | 2.171 | No | 86.92 | 86.92 | 86.92 | 0.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.694 | 1.351 | 75.79 | 133.74 | 75.79 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_EAST_0.36 | N/A | 2.171 | No | 57.95 | 57.95 | 57.95 | 90.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.694 | 1.351 | 113.68 | 200.61 | 113.68 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.36 | N/A | 2.171 | No | 86.92 | 86.92 | 86.92 | 180.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.694 | 1.351 | 75.79 | 133.74 | 75.79 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_WEST_0.36 | N/A | 2.171 | No | 57.95 | 57.95 | 57.95 | 270.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.339 | 1.115 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.339 | 1.115 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.339 | 1.115 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.339 | 1.115 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.260 | 1.060 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.260 | 1.060 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.260 | 1.060 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.260 | 1.060 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.694 | 1.351 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.694 | 1.351 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.694 | 1.351 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.694 | 1.351 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.419 | 0.394 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 1.5244275008E-003 | 1.3779584362E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 3.2065267742E-003 | 3.0510702090E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 1.8952761453E-002 | 1.1827367006E-002 | Pass | Pass | 0.4859363059 | 0.4932995494 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 7.1901655070E-002 | 8.6713160964E-002 | Pass | Pass | 0.8741235618 | 1.4203244554 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 2.7926236535E-002 | 2.0209009678E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 5.1089938386E-002 | 5.8589347187E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 8.3801024038E-002 | 8.7844755793E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 4.0306845488E-002 | 3.5712845121E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.6448690840 | 0.5790721634 | Pass | Pass | 0.7113388060 | 0.6131029056 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.5670729189 | 0.6043768880 | Pass | Pass | 0.7401873142 | 0.6741318829 | Pass | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.4363477464 | 0.5206109169 | Pass | Pass | 7.1183368856 | 63.4717703490 | Pass | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.5570105887 | 0.5745679134 | Pass | Pass | 0.7432848997 | 0.6760115184 | Pass | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.8541620596 | 0.7419026930 | Pass | Pass | 0.6658858997 | 0.5858124633 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.7685567635 | 0.7843651848 | Pass | Pass | 0.6869841275 | 0.6106380013 | Pass | Pass |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.6193962294 | 0.6954695849 | Pass | Pass | 0.9030426176 | 1.7192187851 | Pass | Pass |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.7712561137 | 0.7884095620 | Pass | Pass | 0.6952455600 | 0.6175171393 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 9.8365052701E-003 | 6.5841931496E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 9.4714098470E-002 | 6.0845066172E-002 | Pass | Pass | 0.4888764262 | 0.4880077487 | Pass | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.1795239032 | 0.1364595483 | Pass | Pass | 0.5041738029 | 0.4959766586 | Pass | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 7.7966250106E-003 | 3.5117912283E-002 | Pass | Pass | 0.6894088679 | 3.5006419731 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 9.6725776257E-003 | 7.9668935412E-003 | Pass | Pass | 3.9038962358E-003 | 4.3700280452E-003 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 1.4788464402E-002 | 1.1215955252E-002 | Pass | Pass | 5.7453834229E-003 | 6.2157641296E-003 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 1.2617979501E-005 | 2.1585885112E-005 | Pass | Pass | 7.3784597941E-005 | 1.1160446637E-004 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:39
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 7057.54 | 224.26 | 0.00 | 14673.12 | 21704.43 | 43659.34 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:39
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -10.70 | 0.00 | -10.70 | Wetbulb [C] | 7.50 | 320.00 |
NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 32.10 | 7.40 | 23.10 | Wetbulb [C] | 5.60 | 230.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 172.00 | 59 | |||
Feb | 49.00 | 37 | |||
Mar | 40.00 | 38 | |||
Apr | 70.00 | 48 | |||
May | 70.00 | 36 | |||
Jun | 25.00 | 15 | |||
Jul | 64.00 | 20 | |||
Aug | 2.00 | 4 | |||
Sep | 73.00 | 32 | |||
Oct | 7.00 | 8 | |||
Nov | 88.00 | 34 | |||
Dec | 62.00 | 39 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:39
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.399 | 0.419 | 118.87 | 118.87 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.399 | 0.419 | 139.09 | 139.09 | 180.00 | 90.00 | S |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.399 | 0.419 | 139.09 | 139.09 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.115 | 1.339 | 200.61 | 105.88 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.115 | 1.339 | 133.74 | 71.89 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.115 | 1.339 | 200.61 | 105.88 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.115 | 1.339 | 133.74 | 71.89 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.060 | 1.260 | 2006.06 | 1136.85 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 1.060 | 1.260 | 1337.37 | 757.90 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.060 | 1.260 | 2006.06 | 1136.85 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 1.060 | 1.260 | 1337.37 | 757.90 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.351 | 1.694 | 200.61 | 113.68 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.351 | 1.694 | 133.74 | 75.79 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.351 | 1.694 | 200.61 | 113.68 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.351 | 1.694 | 133.74 | 75.79 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.115 | 1.339 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.115 | 1.339 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.115 | 1.339 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.115 | 1.339 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.060 | 1.260 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 1.060 | 1.260 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.060 | 1.260 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 1.060 | 1.260 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.351 | 1.694 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.351 | 1.694 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.351 | 1.694 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.351 | 1.694 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.182 | 0.186 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.399 | 0.419 | 39.22 | 39.22 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.399 | 0.419 | 39.22 | 39.22 | 180.00 | 90.00 | S |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.399 | 0.419 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 270.00 | 90.00 | W |
BASEMENT_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 2779.43 | 2779.43 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 2076.77 | 2076.77 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 419.30 | 419.30 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 2076.82 | 2076.82 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 0.00 | 180.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.35 | 250.35 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 225.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 135.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.41 | 313.41 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
INT-PER3S-NE-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
INT-PER3S-NE | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.42 | 313.42 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
GROUNDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
iz-DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 0.00 | 180.00 | |
MIDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 35631.06 | 35631.06 | 180.00 | 0.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_BOT_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_BOT_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_MID_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
DATACENTER_MID_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
DATACENTER_MID_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 362.03 | 362.03 | 0.00 | 180.00 | |
DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 180.00 | 0.00 | |
DATACENTER_TOP_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_TOP_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_TOP_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 783.68 | 783.68 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 419.35 | 419.35 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 135.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.08 | 63.08 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 180.00 | 0.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 7126.21 | 0.00 | 90.00 | N | ||
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 50646.53 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.26 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.50 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.35 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.48 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.3822_SHGC_NORTH_0.36 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.171 | 0.361 | 0.361 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.3822_SHGC_NORTH_0.36 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.171 | 0.361 | 0.361 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.3822_SHGC_NORTH_0.36 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.171 | 0.361 | 0.361 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.3822_SHGC_NORTH_0.36 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.171 | 0.361 | 0.361 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.3822_SHGC_NORTH_0.36 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.171 | 0.361 | 0.361 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.3822_SHGC_EAST_0.36 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.171 | 0.361 | 0.361 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.3822_SHGC_EAST_0.36 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.171 | 0.361 | 0.361 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.3822_SHGC_EAST_0.36 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.171 | 0.361 | 0.361 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.3822_SHGC_SOUTH_0.36 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.171 | 0.361 | 0.361 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.3822_SHGC_SOUTH_0.36 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.171 | 0.361 | 0.361 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.3822_SHGC_SOUTH_0.36 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.171 | 0.361 | 0.361 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.3822_SHGC_SOUTH_0.36 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.171 | 0.361 | 0.361 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.3822_SHGC_SOUTH_0.36 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.171 | 0.361 | 0.361 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.3822_SHGC_WEST_0.36 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.171 | 0.361 | 0.361 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.3822_SHGC_WEST_0.36 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.171 | 0.361 | 0.361 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.3822_SHGC_WEST_0.36 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.171 | 0.361 | 0.361 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.3822_SHGC_NORTH_0.36 | 86.92 | 0.00 | 0.00 | 86.92 | 869.21 | 2.171 | 0.361 | 0.361 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.3822_SHGC_EAST_0.36 | 57.95 | 0.00 | 0.00 | 57.95 | 579.48 | 2.171 | 0.361 | 0.361 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.3822_SHGC_SOUTH_0.36 | 86.92 | 0.00 | 0.00 | 86.92 | 869.21 | 2.171 | 0.361 | 0.361 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.3822_SHGC_WEST_0.36 | 57.95 | 0.00 | 0.00 | 57.95 | 579.48 | 2.171 | 0.361 | 0.361 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.3822_SHGC_NORTH_0.36 | 86.92 | 0.00 | 0.00 | 86.92 | 86.92 | 2.171 | 0.361 | 0.361 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.3822_SHGC_EAST_0.36 | 57.95 | 0.00 | 0.00 | 57.95 | 57.95 | 2.171 | 0.361 | 0.361 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.3822_SHGC_SOUTH_0.36 | 86.92 | 0.00 | 0.00 | 86.92 | 86.92 | 2.171 | 0.361 | 0.361 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.3822_SHGC_WEST_0.36 | 57.95 | 0.00 | 0.00 | 57.95 | 57.95 | 2.171 | 0.361 | 0.361 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 3476.85 | 2.171 | 0.361 | 0.361 | |||||||||||||||||
North Total or Average | 1043.06 | 2.171 | 0.361 | 0.361 | |||||||||||||||||
Non-North Total or Average | 2433.80 | 2.171 | 0.361 | 0.361 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:39
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:39
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 7.6202 | 2779.43 | 21179.74 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 44.71 | 0.0000 | Y | 177.74 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 7.6202 | 2496.12 | 19020.89 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 44.71 | 0.0000 | Y | 159.62 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 7.6202 | 24961.20 | 190208.95 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 44.71 | 0.0000 | Y | 1596.24 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 7.6202 | 2496.12 | 19020.89 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 44.71 | 0.0000 | Y | 159.62 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 7.6202 | 313.41 | 2388.26 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 30.98 | 0.0000 | Y | 13.89 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 7.6202 | 201.98 | 1539.09 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 30.96 | 0.0000 | Y | 8.95 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 7.6202 | 313.42 | 2388.32 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 30.77 | 0.0000 | Y | 13.80 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 7.6202 | 201.98 | 1539.09 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 30.81 | 0.0000 | Y | 8.90 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 7.6202 | 3134.13 | 23882.63 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 31.01 | 0.0000 | Y | 139.03 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 7.6202 | 2019.75 | 15390.88 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 30.97 | 0.0000 | Y | 89.49 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 7.6202 | 3134.20 | 23883.15 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 30.79 | 0.0000 | Y | 138.04 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 7.6202 | 2019.75 | 15390.88 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 30.82 | 0.0000 | Y | 89.05 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 7.6202 | 313.41 | 2388.26 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 31.01 | 0.0000 | Y | 13.90 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 7.6202 | 201.98 | 1539.09 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 30.97 | 0.0000 | Y | 8.95 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 7.6202 | 313.42 | 2388.32 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 30.79 | 0.0000 | Y | 13.80 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 7.6202 | 201.98 | 1539.09 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 30.82 | 0.0000 | Y | 8.91 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GENERAL | 7.6202 | 783.68 | 5971.78 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 44.71 | 0.0000 | Y | 50.12 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | DATACENTER_BOT_ZN_6 | GENERAL | 12.5114 | 36.20 | 452.95 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 4.64 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | DATACENTER_MID_ZN_6 | GENERAL | 12.5114 | 362.03 | 4529.48 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 46.40 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | DATACENTER_TOP_ZN_6 | GENERAL | 12.5114 | 36.20 | 452.95 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 4.64 |
Interior Lighting Total | 7.6661 | 46320.38 | 355094.67 | 857.30 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2388.32 | 921.17 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 2388.32 | 0.00 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1539.09 | 593.63 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1539.09 | 0.00 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2388.26 | 921.15 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 2388.26 | 0.00 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1539.09 | 593.63 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1539.09 | 0.00 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2388.32 | 921.17 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 2388.32 | 0.00 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1539.09 | 593.63 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1539.09 | 0.00 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2388.26 | 921.15 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 2388.26 | 0.00 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1539.09 | 593.63 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1539.09 | 0.00 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2388.32 | 921.17 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 2388.32 | 0.00 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1539.09 | 593.63 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1539.09 | 0.00 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2388.26 | 921.15 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 2388.26 | 0.00 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1539.09 | 593.63 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1539.09 | 0.00 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 9973.05 | AstronomicalClock | - | 42.43 | 42.43 | 79.44 | |
EXTERIOR_LIGHTS_B | 27638.03 | AstronomicalClock | - | 83.64 | 71.28 | 369.80 | |
Exterior Lighting Total | 37611.08 | 449.24 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:39
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 2796302.70 | |||||
HEATSYS1 BOILER | Boiler:HotWater | 2810999.16 | 0.81 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:ReformulatedEIR | 1417827.83 | 6.28 | 1357043.73 | 5.98 | 6.84 | 23.33 |
COOLSYS1 CHILLER2 | Chiller:Electric:ReformulatedEIR | 1417827.83 | 6.28 | 1357043.73 | 5.98 | 6.84 | 23.33 |
CENTRAL TOWER | FluidCooler:TwoSpeed | 582060.00 | |||||
CENTRAL BOILER | Boiler:HotWater | 534724.26 | 0.80 | ||||
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 1682223.24 | |||||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 1682223.24 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | 229200.72 | 244431.25 | 166932.50 | 77498.75 | 0.68 | - | 25391.95 | 257.54 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | 2231858.92 | 2321644.02 | 1577540.74 | 744103.28 | 0.68 | - | 241744.39 | 2451.91 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | 228877.65 | 245551.89 | 167886.16 | 77665.73 | 0.68 | - | 25510.38 | 258.74 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | 112810.89 | 129663.06 | 90516.25 | 39146.82 | 0.70 | - | 13187.83 | 133.76 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 430959.38 | 311115.05 | 119844.34 | 0.72 | 0.00 | |||
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9507.01 | 6877.70 | 2629.31 | 0.72 | 0.00 | |||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 90854.16 | 65670.26 | 25183.90 | 0.72 | 0.00 | |||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9256.47 | 6692.41 | 2564.06 | 0.72 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 20089.51 | 19048.34 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 508268.08 | 481462.57 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 92710.99 | 87852.81 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 16065.01 | 15221.19 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 10980.27 | 10403.40 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 17706.24 | 16775.96 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 8694.95 | 8235.14 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 271829.17 | 257524.30 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 178600.17 | 169200.88 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 269201.03 | 255034.76 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 173446.66 | 164319.03 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 34830.21 | 32996.29 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 22799.52 | 21599.00 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 34513.29 | 32696.08 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 22497.72 | 21313.10 | - |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | 69798.50 | 50927.45 | - |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | 717380.55 | 511629.54 | - |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | 70617.11 | 51479.24 | - |
CAV_BAS HEATING COIL | Coil:Heating:Water | 270970.20 | 211120.40 | - |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 430959.38 | 0.00 | |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9507.01 | 0.00 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 90854.16 | 0.00 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9256.47 | 0.00 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | 20749.82 | 1.00 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | 958.56 | 1.00 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | 9585.56 | 1.00 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | 958.56 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 9.25 | 21119.54 | 2283.73 | 1.00 | 1.12 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 86.39 | 197298.14 | 2283.73 | 1.00 | 1.07 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 9.32 | 21291.54 | 2283.73 | 1.00 | 1.11 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 |
CAV_BAS FAN | Fan:ConstantVolume | 0.60 | 1018.41 | 5.28 | 8953.22 | 1695.65 | 1.00 | 1.16 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 0.61 | 1018.41 | 21.30 | 35314.70 | 1657.97 | 1.00 | 1.13 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 |
AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.47 | 529.04 | 1120.11 | 1.00 | 1.63 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 4.51 | 5047.61 | 1120.11 | 1.00 | 1.16 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.46 | 514.52 | 1120.11 | 1.00 | 1.65 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 133527.72 | 0.119235 | 24569.99 | 206062.94 | 0.90 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.024592 | 7405.98 | 301156.09 | 0.90 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 92445.74 | 0.119235 | 17010.64 | 142664.32 | 0.90 | General |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.013239 | 3376.53 | 255050.01 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 3168.45 | 0.000440 | 5.96 | 13540.37 | 0.30 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 180718.98 | 0.140326 | 42263.16 | 301178.23 | 0.90 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.50 | 0.08 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:39
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 73318.86 | 73318.86 | 26.38 | 5.280 | 5.280 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00898 | 26.62 | 0.01411 | 1.200 | 0.00 |
CORE_BOTTOM | 77948.18 | 77948.18 | 31.23 | 5.613 | 5.613 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00890 | 26.62 | 0.01411 | 1.078 | 0.00 |
CORE_MID | 732804.18 | 732804.18 | 293.58 | 52.758 | 52.758 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00893 | 26.62 | 0.01411 | 10.778 | 0.00 |
CORE_TOP | 74603.57 | 74603.57 | 29.89 | 5.372 | 5.372 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00892 | 26.62 | 0.01411 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 12859.32 | 12859.32 | 41.03 | 0.935 | 0.935 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 24.00 | 0.00897 | 32.10 | 0.01412 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 14329.31 | 14329.31 | 70.95 | 1.042 | 1.042 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:50:00 | 24.00 | 24.00 | 0.00878 | 27.80 | 0.01411 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 17391.46 | 17391.46 | 55.49 | 1.264 | 1.264 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 24.00 | 24.00 | 0.00885 | 31.73 | 0.01412 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 17915.92 | 17915.92 | 88.70 | 1.302 | 1.302 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 24.00 | 24.00 | 0.00872 | 31.26 | 0.01412 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 121634.60 | 121634.60 | 388.10 | 8.843 | 8.843 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 24.00 | 0.00922 | 32.10 | 0.01412 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 150524.30 | 150524.30 | 745.26 | 10.943 | 10.943 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 24.00 | 24.00 | 0.00890 | 28.24 | 0.01411 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 169466.74 | 169466.74 | 540.70 | 12.320 | 12.320 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 | 24.00 | 24.00 | 0.00903 | 31.79 | 0.01412 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 157123.96 | 157123.96 | 777.94 | 11.423 | 11.423 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 24.00 | 24.00 | 0.00888 | 31.16 | 0.01412 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 14002.82 | 14002.82 | 44.68 | 1.018 | 1.018 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 24.00 | 0.00921 | 32.10 | 0.01412 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 15435.42 | 15435.42 | 76.42 | 1.122 | 1.122 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 24.00 | 24.00 | 0.00894 | 28.45 | 0.01411 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 18673.39 | 18673.39 | 59.58 | 1.358 | 1.358 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 24.00 | 24.00 | 0.00905 | 31.92 | 0.01412 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 16945.88 | 16945.88 | 83.90 | 1.232 | 1.232 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 24.00 | 24.00 | 0.00890 | 31.26 | 0.01412 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 8238.00 | 8238.00 | 227.55 | 0.472 | 0.472 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 27.00 | 27.00 | 0.00859 | 29.58 | 0.01412 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 78598.84 | 78598.84 | 2171.07 | 4.506 | 4.506 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 27.00 | 27.00 | 0.00859 | 29.58 | 0.01412 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 8011.82 | 8011.82 | 221.30 | 0.459 | 0.459 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 27.00 | 27.00 | 0.00859 | 29.77 | 0.01412 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 371512.59 | 371512.59 | 474.06 | 21.300 | 21.300 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 27.00 | 27.00 | 0.00854 | 25.37 | 0.01411 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 21.00 | 23.50 | 0.00150 | -10.70 | 0.00150 | 1.200 | 0.00 |
CORE_BOTTOM | 1101.61 | 1101.61 | 0.44 | 0.047 | 1.078 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00174 | -10.70 | 0.00150 | 1.078 | 0.00 |
CORE_MID | 319779.23 | 319779.23 | 128.11 | 13.514 | 13.514 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -10.70 | 0.00150 | 10.778 | 0.00 |
CORE_TOP | 64925.78 | 64925.78 | 26.01 | 2.761 | 2.761 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -10.70 | 0.00150 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 11251.77 | 11251.77 | 35.90 | 0.479 | 0.479 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00720 | -10.70 | 0.00150 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 7689.61 | 7689.61 | 38.07 | 0.328 | 0.328 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00726 | -10.70 | 0.00150 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 12398.79 | 12398.79 | 39.56 | 0.528 | 0.528 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00733 | -10.70 | 0.00150 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 6079.90 | 6079.90 | 30.10 | 0.259 | 0.259 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00690 | -10.70 | 0.00150 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 190303.59 | 190303.59 | 607.20 | 8.117 | 8.117 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00717 | -10.70 | 0.00150 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 125034.85 | 125034.85 | 619.06 | 5.333 | 5.333 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00716 | -10.70 | 0.00150 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 188465.87 | 188465.87 | 601.32 | 8.039 | 8.039 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00716 | -10.70 | 0.00150 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 121431.05 | 121431.05 | 601.22 | 5.179 | 5.179 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00714 | -10.70 | 0.00150 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 24380.82 | 24380.82 | 77.79 | 1.040 | 1.040 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00720 | -10.70 | 0.00150 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 15959.52 | 15959.52 | 79.02 | 0.681 | 0.681 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 20.99 | 0.00718 | -10.70 | 0.00150 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 24159.19 | 24159.19 | 77.08 | 1.031 | 1.031 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00719 | -10.70 | 0.00150 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 15748.44 | 15748.44 | 77.97 | 0.672 | 0.672 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 20.99 | 0.00717 | -10.70 | 0.00150 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | 18.00 | 25.14 | 0.00654 | -10.70 | 0.00150 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | 18.00 | 22.66 | 0.00200 | -10.70 | 0.00150 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | 18.00 | 20.77 | 0.00199 | -10.70 | 0.00150 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 03:50:00 | 18.00 | 27.00 | 0.00850 | -10.70 | 0.00150 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV_BOT WITH REHEAT | 9.25 | 9.25 | 2.67 | 2.67 | 9.2478 | 2.8695 | 9.2478 | 0.3103 | 0.3000 |
VAV_MID WITH REHEAT | 86.39 | 86.39 | 40.18 | 40.18 | 86.3930 | 40.1821 | 86.3930 | 0.4651 | 0.3000 |
VAV_TOP WITH REHEAT | 9.32 | 9.32 | 6.19 | 6.19 | 9.3232 | 6.1854 | 9.3232 | 0.6634 | 0.3000 |
CAV_BAS | 5.28 | 5.28 | 1.20 | 1.20 | 5.2801 | 5.2801 | 5.2801 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.30 | 21.30 | 0.34 | 0.34 | 21.2999 | 21.2997 | 21.2999 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.47 | 0.47 | 0.02 | 0.02 | 0.4723 | 0.4723 | 0.4723 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 4.51 | 4.51 | 0.16 | 0.16 | 4.5064 | 4.5064 | 4.5064 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.46 | 0.46 | 0.02 | 0.02 | 0.4593 | 0.4593 | 0.4593 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 20089.510 | 20089.510 | 1.908549 | 0.00017575 | 406.822 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 20089.51 | 20089.51 | 1.908549 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00173684 | 11.3356 | 1101.61 | 0.00 | 20163.40 | 20163.40 |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 508268.085 | 508268.085 | 18.728978 | 0.00444655 | 12344.871 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 508268.08 | 508268.08 | 18.728978 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 319779.23 | 0.00 | 509908.34 | 509908.34 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 92710.988 | 92710.988 | 2.760845 | 0.00081108 | 2447.389 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 92710.99 | 92710.99 | 2.760845 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 64925.78 | 0.00 | 93032.10 | 93032.10 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 16065.005 | 16065.005 | 0.479133 | 0.00014054 | 423.788 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 16065.01 | 16065.01 | 0.479133 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00719854 | 46.5817 | 11251.77 | 0.00 | 16118.51 | 16118.51 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 10980.270 | 10980.270 | 0.327529 | 0.00009606 | 289.636 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 10980.27 | 10980.27 | 0.327529 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00725512 | 46.9432 | 7689.61 | 0.00 | 11016.71 | 11016.71 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 17706.236 | 17706.236 | 0.528177 | 0.00015490 | 467.044 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 17706.24 | 17706.24 | 0.528177 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00733066 | 47.4256 | 12398.79 | 0.00 | 17764.93 | 17764.93 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 8694.950 | 8694.950 | 0.260472 | 0.00007607 | 228.907 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8694.95 | 8694.95 | 0.260472 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00690186 | 44.6844 | 6079.90 | 0.00 | 8720.88 | 8720.88 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 271829.169 | 271829.169 | 8.117165 | 0.00237808 | 7166.706 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 271829.17 | 271829.17 | 8.117165 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00716866 | 46.3943 | 190303.59 | 0.00 | 272705.53 | 272705.53 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 178600.166 | 178600.166 | 5.333432 | 0.00156247 | 4708.665 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 178600.17 | 178600.17 | 5.333432 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00715893 | 46.3323 | 125034.85 | 0.00 | 179175.37 | 179175.37 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 269201.030 | 269201.030 | 8.038578 | 0.00235509 | 7097.459 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 269201.03 | 269201.03 | 8.038578 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00716121 | 46.3466 | 188465.87 | 0.00 | 270069.23 | 270069.23 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 173446.656 | 173446.656 | 5.179371 | 0.00151739 | 4572.863 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 173446.66 | 173446.66 | 5.179371 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00713611 | 46.1863 | 121431.05 | 0.00 | 174005.74 | 174005.74 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 34830.214 | 34830.214 | 1.040444 | 0.00030471 | 918.141 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 34830.21 | 34733.25 | 1.040444 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00719576 | 46.5697 | 24380.82 | 0.00 | 34941.43 | 34941.43 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 22799.515 | 22799.515 | 0.681083 | 0.00019946 | 600.998 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 22799.52 | 22799.52 | 0.681083 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 20.99 | 0.00718277 | 46.4870 | 15959.52 | 0.00 | 22872.26 | 22872.26 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 34513.288 | 34513.288 | 1.030967 | 0.00030194 | 909.790 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 34513.29 | 34513.29 | 1.030967 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00718925 | 46.5281 | 24159.19 | 0.00 | 34623.52 | 34623.52 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 22497.715 | 22497.715 | 0.672064 | 0.00019682 | 593.044 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 22497.72 | 22497.72 | 0.672064 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 20.99 | 0.00717354 | 46.4280 | 15748.44 | 0.00 | 22569.51 | 22569.51 |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 229200.723 | -999.000 | 9.247836 | 0.00975073 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 229200.72 | 173008.65 | 9.247836 | 26.33 | 18.75 | 0.01041667 | 10.95 | 10.95 | 0.00850000 | 32.10 | 0.01411964 | 23.13 | 27.4463 | 24.00 | 0.00891647 | 47.9479 | 121103.82 | 0.00 | 229507.08 | 167073.30 |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 69798.502 | 69798.502 | 2.774351 | 0.00061063 | 1119.886 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 69798.50 | 69798.50 | 2.774351 | -8.00 | -8.21 | 0.00179941 | 12.80 | 11.59 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 91.4877 | 21.00 | 0.00723482 | 46.8114 | 34602.79 | 0.00 | 61585.54 | 61585.54 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 2231858.924 | -999.000 | 86.393017 | 0.09494844 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 2231858.92 | 1640683.65 | 86.393017 | 26.58 | 19.02 | 0.01066108 | 10.95 | 10.95 | 0.00850000 | 32.10 | 0.01411964 | 23.13 | 29.3796 | 24.00 | 0.00904527 | 48.6318 | 1096515.53 | 0.00 | 2234964.44 | 1590148.74 |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 717380.549 | 717380.549 | 25.917905 | 0.00627596 | 11389.177 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 717380.55 | 717380.55 | 25.917905 | -10.09 | -10.09 | 0.00162101 | 12.80 | 11.59 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 97.9321 | 19.36 | 0.00673517 | 48.2504 | 452087.97 | 0.00 | 618605.12 | 618605.12 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 228877.652 | -999.000 | 9.323152 | 0.00973698 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 228877.65 | 172927.70 | 9.323152 | 26.20 | 18.69 | 0.01039257 | 10.95 | 10.95 | 0.00850000 | 32.10 | 0.01411964 | 23.13 | 27.2246 | 24.00 | 0.00899831 | 48.3831 | 128250.11 | 0.00 | 229181.57 | 166915.00 |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 70617.113 | 70617.113 | 2.796946 | 0.00061779 | 1132.483 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:20:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 70617.11 | 70617.11 | 2.796946 | -8.08 | -8.08 | 0.00202180 | 12.80 | 11.59 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 90.7486 | 17.60 | 0.00668894 | 53.5319 | 50531.78 | 0.00 | 62256.55 | 62256.55 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 112810.891 | -999.000 | 5.280095 | 0.00479924 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 112810.89 | 85881.69 | 5.280095 | 24.70 | 18.00 | 0.01014776 | 11.42 | 11.42 | 0.00850000 | 27.09 | 0.01411064 | 21.71 | 22.7298 | 24.00 | 0.00897685 | 48.2675 | 72388.71 | 0.00 | 112976.12 | 83034.10 |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | CAV_BAS | 270970.198 | 270970.198 | 5.280095 | 0.00237057 | 5947.014 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 270970.20 | 270970.20 | 5.280095 | -2.43 | -5.10 | 0.00150390 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 22.7298 | 23.62 | 0.00150390 | 8.3740 | 0.00 | 0.00 | 222940.97 | 222940.97 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 430959.384 | 311115.047 | 21.299925 | 0.01055417 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 | 403378.75 | 395698.35 | -999.0 | 28.48 | 18.04 | 0.00863100 | 12.80 | 12.09 | 0.00850000 | 32.10 | 0.01411964 | 23.13 | -999.0000 | 27.00 | 0.00854230 | 38.4643 | 371069.83 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9507.008 | 6877.699 | 0.472311 | 0.00023283 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 8890.19 | 8538.47 | -999.0 | 28.04 | 18.00 | 0.00877081 | 12.80 | 12.09 | 0.00850000 | 29.77 | 0.01411544 | 22.48 | -999.0000 | 27.00 | 0.00858780 | 38.6641 | 8235.01 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 90854.157 | 65670.262 | 4.506359 | 0.00222501 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 84982.06 | 81465.46 | -999.0 | 28.03 | 18.01 | 0.00878376 | 12.80 | 12.09 | 0.00850000 | 29.58 | 0.01411511 | 22.43 | -999.0000 | 27.00 | 0.00859217 | 38.6837 | 78598.84 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9256.470 | 6692.409 | 0.459345 | 0.00022669 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 8657.54 | 8305.96 | -999.0 | 28.04 | 18.01 | 0.00877833 | 12.80 | 12.09 | 0.00850000 | 29.77 | 0.01411544 | 22.48 | -999.0000 | 27.00 | 0.00859030 | 38.6753 | 8011.82 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 430959.384 | 430959.384 | 21.299925 | 0.01055417 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 430959.38 | 430959.38 | 21.299925 | -10.70 | -10.70 | 0.00150390 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 1.5887 | 27.00 | 0.00850000 | 38.2706 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9507.008 | 9507.008 | 0.472311 | 0.00023283 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9507.01 | 9507.01 | 0.472311 | -10.70 | -10.70 | 0.00150390 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 3.3098 | 25.77 | 0.00654062 | 31.7584 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 90854.157 | 90854.157 | 4.506359 | 0.00222501 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 90854.16 | 90854.16 | 4.506359 | -10.70 | -10.70 | 0.00150390 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 3.4690 | 23.83 | 0.00199518 | 10.9586 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9256.470 | 9256.470 | 0.459345 | 0.00022669 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9256.47 | 9256.47 | 0.459345 | -10.70 | -10.70 | 0.00150390 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 3.4032 | 22.74 | 0.00199484 | 11.7052 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 20749.821 | 20749.821 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 20749.82 | 20749.82 | 21.299925 | -0.17 | -0.17 | 0.00838885 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 1.5887 | 27.00 | 0.00850000 | 38.2706 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BOT | 958.556 | 958.556 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 958.56 | 958.56 | 0.472311 | -0.35 | -0.35 | 0.00637392 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 3.3098 | 25.77 | 0.00654062 | 31.7584 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER MID | 9585.558 | 9585.558 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9585.56 | 9585.56 | 4.506359 | -0.37 | -3.04 | 0.00197814 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 3.4690 | 23.83 | 0.00199518 | 10.9586 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER TOP | 958.556 | 958.556 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 958.56 | 958.56 | 0.459345 | -0.36 | -3.03 | 0.00197813 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 3.4032 | 22.74 | 0.00199484 | 11.7052 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 09:04:39
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 20089.510 | 20089.510 | 1.908549 | 0.00017575 | 406.822 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 24.58933829 | 54.44 | 82.22 | 27.78 | 2867571.63 | 0.7006 | 0.714675 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 20089.51 | 20089.51 | 1.0000 | 2.29712040 | 1.908549 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.17573387 | 60.00 | 32.22 | 27.78 | 0.000 | 20089.51 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.93 | 0.00173684 | 21.00 | 0.00173684 | 11.3356 | 1101.61 | 0.00 | 20163.40 | 20163.40 | 2.29712040 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 21.41 | 15.00 | 0.00800000 | 41837.5 | |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 508268.085 | 508268.085 | 18.728978 | 0.00444655 | 12344.871 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 24.58933829 | 54.44 | 82.22 | 27.78 | 2867571.63 | 17.7247 | 18.081403 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 508268.08 | 508268.08 | 1.0000 | 22.54210447 | 18.728978 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 4.44609734 | 60.00 | 32.22 | 27.78 | 0.000 | 508268.08 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.87 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 319779.23 | 0.00 | 509908.34 | 509908.34 | 22.54210447 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 34.98 | 19.65 | 0.00800000 | 55680.1 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 92710.988 | 92710.988 | 2.760845 | 0.00081108 | 2447.389 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 24.58933829 | 54.44 | 82.22 | 27.78 | 2867571.63 | 3.2331 | 3.298151 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 92710.99 | 92710.99 | 1.0000 | 3.32293912 | 2.760845 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.81099343 | 60.00 | 32.22 | 27.78 | 0.000 | 92710.99 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.91 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 64925.78 | 0.00 | 93032.10 | 93032.10 | 3.32293912 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.26 | 21.26 | 0.00800000 | 61056.8 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 16065.005 | 16065.005 | 0.479133 | 0.00014054 | 423.788 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 24.58933829 | 54.44 | 82.22 | 27.78 | 2867571.63 | 0.5602 | 0.571505 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 16065.01 | 16065.01 | 1.0000 | 0.57668156 | 0.479133 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.14052934 | 60.00 | 32.22 | 27.78 | 0.000 | 16065.01 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00719854 | 21.00 | 0.00719854 | 46.5817 | 11251.77 | 0.00 | 16118.51 | 16118.51 | 0.57668156 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.21 | 21.24 | 0.00800000 | 61010.3 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10980.270 | 10980.270 | 0.327529 | 0.00009606 | 289.636 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 24.58933829 | 54.44 | 82.22 | 27.78 | 2867571.63 | 0.3829 | 0.390618 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 10980.27 | 10980.27 | 1.0000 | 0.39421194 | 0.327529 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.09605040 | 60.00 | 32.22 | 27.78 | 0.000 | 10980.27 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00725512 | 21.00 | 0.00725512 | 46.9432 | 7689.61 | 0.00 | 11016.71 | 11016.71 | 0.39421194 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.21 | 21.24 | 0.00800000 | 61006.0 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 17706.236 | 17706.236 | 0.528177 | 0.00015490 | 467.044 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 24.58933829 | 54.44 | 82.22 | 27.78 | 2867571.63 | 0.6175 | 0.629891 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 17706.24 | 17706.24 | 1.0000 | 0.63571123 | 0.528177 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.15488607 | 60.00 | 32.22 | 27.78 | 0.000 | 17706.24 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00733066 | 21.00 | 0.00733066 | 47.4256 | 12398.79 | 0.00 | 17764.93 | 17764.93 | 0.63571123 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 61004.8 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8694.950 | 8694.950 | 0.260472 | 0.00007607 | 228.907 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 24.58933829 | 54.44 | 82.22 | 27.78 | 2867571.63 | 0.3032 | 0.309319 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 8694.95 | 8694.95 | 1.0000 | 0.31350266 | 0.260472 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.07605946 | 60.00 | 32.22 | 27.78 | 0.000 | 8694.95 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.91 | 0.00690186 | 21.00 | 0.00690186 | 44.6844 | 6079.90 | 0.00 | 8720.88 | 8720.88 | 0.31350266 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.08 | 21.21 | 0.00800000 | 60877.4 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 271829.169 | 271829.169 | 8.117165 | 0.00237808 | 7166.706 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 24.58933829 | 54.44 | 82.22 | 27.78 | 2867571.63 | 9.4794 | 9.670197 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 271829.17 | 271829.17 | 1.0000 | 9.76977888 | 8.117165 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 2.37783756 | 60.00 | 32.22 | 27.78 | 0.000 | 271829.17 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00716866 | 21.00 | 0.00716866 | 46.3943 | 190303.59 | 0.00 | 272705.53 | 272705.53 | 9.76977888 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60973.0 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 178600.166 | 178600.166 | 5.333432 | 0.00156247 | 4708.665 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 24.58933829 | 54.44 | 82.22 | 27.78 | 2867571.63 | 6.2283 | 6.353619 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 178600.17 | 178600.17 | 1.0000 | 6.41929211 | 5.333432 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 1.56231278 | 60.00 | 32.22 | 27.78 | 0.000 | 178600.17 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.94 | 0.00715893 | 21.00 | 0.00715893 | 46.3323 | 125034.85 | 0.00 | 179175.37 | 179175.37 | 6.41929211 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60971.8 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 269201.030 | 269201.030 | 8.038578 | 0.00235509 | 7097.459 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 24.58933829 | 54.44 | 82.22 | 27.78 | 2867571.63 | 9.3878 | 9.576703 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 269201.03 | 269201.03 | 1.0000 | 9.67519240 | 8.038578 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 2.35484780 | 60.00 | 32.22 | 27.78 | 0.000 | 269201.03 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00716121 | 21.00 | 0.00716121 | 46.3466 | 188465.87 | 0.00 | 270069.23 | 270069.23 | 9.67519240 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60973.4 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 173446.656 | 173446.656 | 5.179371 | 0.00151739 | 4572.863 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 24.58933829 | 54.44 | 82.22 | 27.78 | 2867571.63 | 6.0486 | 6.170285 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 173446.66 | 173446.66 | 1.0000 | 6.23386437 | 5.179371 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 1.51723222 | 60.00 | 32.22 | 27.78 | 0.000 | 173446.66 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.94 | 0.00713611 | 21.00 | 0.00713611 | 46.1863 | 121431.05 | 0.00 | 174005.74 | 174005.74 | 6.23386437 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60972.8 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 34830.214 | 34830.214 | 1.040444 | 0.00030471 | 918.141 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 24.58933829 | 54.44 | 82.22 | 27.78 | 2867571.63 | 1.2146 | 1.239069 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 34830.21 | 34733.25 | 1.0000 | 1.25227323 | 1.040444 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.30467883 | 60.00 | 32.22 | 27.78 | 0.000 | 34830.21 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.94 | 0.00719576 | 21.00 | 0.00719576 | 46.5697 | 24380.82 | 0.00 | 34941.43 | 34941.43 | 1.25227323 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.16 | 21.23 | 0.00800000 | 60962.2 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 22799.515 | 22799.515 | 0.681083 | 0.00019946 | 600.998 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 24.58933829 | 54.44 | 82.22 | 27.78 | 2867571.63 | 0.7951 | 0.811082 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 22799.52 | 22799.52 | 1.0000 | 0.81974863 | 0.681083 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.19943976 | 60.00 | 32.22 | 27.78 | 0.000 | 22799.52 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.94 | 0.00718277 | 20.99 | 0.00718277 | 46.4870 | 15959.52 | 0.00 | 22872.26 | 22872.26 | 0.81974863 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.16 | 21.23 | 0.00800000 | 60961.4 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 34513.288 | 34513.288 | 1.030967 | 0.00030194 | 909.790 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 24.58933829 | 54.44 | 82.22 | 27.78 | 2867571.63 | 1.2036 | 1.227794 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 34513.29 | 34513.29 | 1.0000 | 1.24086727 | 1.030967 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.30190650 | 60.00 | 32.22 | 27.78 | 0.000 | 34513.29 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.94 | 0.00718925 | 21.00 | 0.00718925 | 46.5281 | 24159.19 | 0.00 | 34623.52 | 34623.52 | 1.24086727 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.16 | 21.23 | 0.00800000 | 60962.5 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 22497.715 | 22497.715 | 0.672064 | 0.00019682 | 593.044 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 24.58933829 | 54.44 | 82.22 | 27.78 | 2867571.63 | 0.7846 | 0.800346 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 22497.72 | 22497.72 | 1.0000 | 0.80889230 | 0.672064 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.19679975 | 60.00 | 32.22 | 27.78 | 0.000 | 22497.72 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.94 | 0.00717354 | 20.99 | 0.00717354 | 46.4280 | 15748.44 | 0.00 | 22569.51 | 22569.51 | 0.80889230 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.16 | 21.23 | 0.00800000 | 60961.6 | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 229200.723 | -999.000 | 9.247836 | 0.00975073 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.2041 | 1004.8586 | 1.2036 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 9.247836 | 11.13064917 | 4197.9300 | 999.8980 | 119.22322388 | 12.27 | 6.67 | 5.60 | 2802748.19 | 8.1777 | 8.177714 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 229200.72 | 173008.65 | 1.0000 | 11.13064917 | 9.247836 | 26.33 | 18.75 | 0.01041667 | 53023.2 | 10.95 | 10.95 | 0.00850000 | 32431.4 | 9.74973394 | 6.67 | 12.27 | 5.60 | 21119.541 | 208081.18 | 32.10 | 0.01411964 | 23.13 | 2.53819000 | 27.4463 | 24.00 | 0.00891647 | 24.00 | 0.00891647 | 47.9479 | 121103.82 | 0.00 | 229507.08 | 167073.30 | 11.13064917 | 26.33 | 18.76 | 0.01041667 | 53023.2 | 11.68 | 11.32 | 0.00819314 | 32403.9 | |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 69798.502 | 69798.502 | 2.774351 | 0.00061063 | 1119.886 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 9.247836 | 11.13064917 | 4197.9300 | 999.8980 | 24.58933829 | 54.44 | 82.22 | 27.78 | 2867571.63 | 2.4341 | 2.483050 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 69798.50 | 69798.50 | 1.0000 | 3.33919475 | 2.774351 | -8.00 | -8.21 | 0.00179941 | -3567.0 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 0.61056545 | 60.00 | 32.22 | 27.78 | 0.000 | 69798.50 | -10.70 | 0.00150390 | -10.70 | 2.53819000 | 91.4877 | 21.00 | 0.00497549 | 21.00 | 0.00723482 | 46.8114 | 34602.79 | 0.00 | 61585.54 | 61585.54 | 3.33919475 | 2.80 | -1.50 | 0.00179941 | 7323.1 | 21.09 | 8.54 | 0.00179941 | 25766.4 | |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 2231858.924 | -999.000 | 86.393017 | 0.09494844 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.6584 | 1004.8586 | 1.2036 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 86.393017 | 103.98220154 | 4197.9300 | 999.8980 | 119.22322388 | 12.27 | 6.67 | 5.60 | 2802748.19 | 79.6311 | 79.631090 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 2231858.92 | 1640683.65 | 1.0000 | 103.98220154 | 86.393017 | 26.58 | 19.02 | 0.01066108 | 53896.1 | 10.95 | 10.95 | 0.00850000 | 32432.2 | 94.93875229 | 6.67 | 12.27 | 5.60 | 197298.135 | 2034560.79 | 32.10 | 0.01411964 | 23.13 | 25.38195000 | 29.3796 | 24.00 | 0.00904527 | 24.00 | 0.00904527 | 48.6318 | 1096515.53 | 0.00 | 2234964.44 | 1590148.74 | 103.98220154 | 26.58 | 19.03 | 0.01066108 | 53896.1 | 11.65 | 11.32 | 0.00820282 | 32402.3 | |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 717380.549 | 717380.549 | 25.917905 | 0.00627596 | 11389.177 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 86.393017 | 103.98220154 | 4197.9300 | 999.8980 | 24.58933829 | 54.44 | 82.22 | 27.78 | 2867571.63 | 25.0170 | 25.520483 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 717380.55 | 717380.55 | 1.0000 | 31.19466046 | 25.917905 | -10.09 | -10.09 | 0.00162101 | -6110.9 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 6.27531778 | 60.00 | 32.22 | 27.78 | 0.000 | 717380.55 | -10.70 | 0.00150390 | -10.70 | 25.38195000 | 97.9321 | 19.01 | 0.00716748 | 19.36 | 0.00673517 | 48.2504 | 452087.97 | 0.00 | 618605.12 | 618605.12 | 31.19466046 | 2.80 | -1.78 | 0.00162101 | 6876.0 | 22.48 | 8.97 | 0.00162101 | 26706.5 | |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 228877.652 | -999.000 | 9.323152 | 0.00973698 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.1593 | 1004.8586 | 1.2036 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 9.323152 | 11.22129892 | 4197.9300 | 999.8980 | 119.22322388 | 12.27 | 6.67 | 5.60 | 2802748.19 | 8.1662 | 8.166187 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | Sensible | 228877.65 | 172927.70 | 1.0000 | 11.22129892 | 9.323152 | 26.20 | 18.69 | 0.01039257 | 52828.0 | 10.95 | 10.95 | 0.00850000 | 32431.3 | 9.73599115 | 6.67 | 12.27 | 5.60 | 21291.541 | 207586.11 | 32.10 | 0.01411964 | 23.13 | 2.53819000 | 27.2246 | 24.00 | 0.00899831 | 24.00 | 0.00899831 | 48.3831 | 128250.11 | 0.00 | 229181.57 | 166915.00 | 11.22129892 | 26.20 | 18.70 | 0.01039257 | 52828.0 | 11.68 | 11.32 | 0.00819291 | 32404.2 | |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 70617.113 | 70617.113 | 2.796946 | 0.00061779 | 1132.483 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 9.323152 | 11.22129892 | 4197.9300 | 999.8980 | 24.58933829 | 54.44 | 82.22 | 27.78 | 2867571.63 | 2.4626 | 2.512171 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:20:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 70617.11 | 70617.11 | 1.0000 | 3.36638968 | 2.796946 | -8.08 | -8.08 | 0.00202180 | -3088.7 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 0.61772629 | 60.00 | 32.22 | 27.78 | 0.000 | 70617.11 | -10.70 | 0.00150390 | -10.70 | 2.53819000 | 90.7486 | 17.67 | 0.00710204 | 17.60 | 0.00668894 | 53.5319 | 50531.78 | 0.00 | 62256.55 | 62256.55 | 3.36638968 | 2.80 | -1.15 | 0.00202180 | 7880.5 | 21.14 | 8.81 | 0.00202180 | 26374.0 | |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 112810.891 | -999.000 | 5.280095 | 0.00479924 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.7042 | 1004.8586 | 1.2036 | CAV_BAS FAN | Fan:ConstantVolume | 5.280095 | 6.35509641 | 4197.9300 | 999.8980 | 119.22322388 | 12.27 | 6.67 | 5.60 | 2802748.19 | 4.0250 | 4.025010 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 112810.89 | 85881.69 | 1.0000 | 6.35509641 | 5.280095 | 24.70 | 18.00 | 0.01014776 | 50668.8 | 11.42 | 11.42 | 0.00850000 | 32917.6 | 4.79874650 | 6.67 | 12.27 | 5.60 | 8953.217 | 103857.67 | 27.09 | 0.01411064 | 21.71 | 1.20015641 | 22.7298 | 24.00 | 0.00897685 | 24.00 | 0.00897685 | 48.2675 | 72388.71 | 0.00 | 112976.12 | 83034.10 | 6.35509641 | 24.70 | 18.01 | 0.01014776 | 50668.8 | 11.94 | 11.52 | 0.00828044 | 32891.6 | |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 270970.198 | 270970.198 | 5.280095 | 0.00237057 | 5947.014 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | CAV_BAS FAN | Fan:ConstantVolume | 5.280095 | 6.35509641 | 4197.9300 | 999.8980 | 24.58933829 | 54.44 | 82.22 | 27.78 | 2867571.63 | 9.4495 | 9.639640 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 270970.20 | 270970.20 | 1.0000 | 6.35509641 | 5.280095 | -2.43 | -5.10 | 0.00150390 | 1310.5 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 2.37032367 | 60.00 | 32.22 | 27.78 | 0.000 | 270970.20 | -10.70 | 0.00150390 | -10.70 | 1.20015641 | 22.7298 | 0.00 | 0.00150390 | 23.62 | 0.00150390 | 8.3740 | 0.00 | 0.00 | 222940.97 | 222940.97 | 6.35509641 | 12.80 | 4.04 | 0.00150390 | 16658.9 | 47.61 | 18.58 | 0.00150390 | 51739.6 | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 430959.384 | 311115.047 | 21.299925 | 0.01055417 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.8846 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 | Sensible | 403378.75 | 395698.35 | 0.9360 | -999.0 | -999.0 | 28.48 | 18.04 | 0.00863100 | 50660.0 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 403378.75 | 32.10 | 0.01411964 | 23.13 | 0.33839277 | -999.0000 | 27.00 | 0.00854230 | 27.00 | 0.00854230 | 38.4643 | 371069.83 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9507.008 | 6877.699 | 0.472311 | 0.00023283 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1021.1445 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | Sensible | 8890.19 | 8538.47 | 0.9351 | -999.0 | -999.0 | 28.04 | 18.00 | 0.00877081 | 50564.8 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8890.19 | 29.77 | 0.01411544 | 22.48 | 0.01563234 | -999.0000 | 27.00 | 0.00858780 | 27.00 | 0.00858780 | 38.6641 | 8235.01 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 90854.157 | 65670.262 | 4.506359 | 0.00222501 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1021.1686 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | Sensible | 84982.06 | 81465.46 | 0.9354 | -999.0 | -999.0 | 28.03 | 18.01 | 0.00878376 | 50595.7 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 84982.06 | 29.58 | 0.01411511 | 22.43 | 0.15632344 | -999.0000 | 27.00 | 0.00859217 | 27.00 | 0.00859217 | 38.6837 | 78598.84 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9256.470 | 6692.409 | 0.459345 | 0.00022669 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1021.1585 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | Sensible | 8657.54 | 8305.96 | 0.9353 | -999.0 | -999.0 | 28.04 | 18.01 | 0.00877833 | 50586.6 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8657.54 | 29.77 | 0.01411544 | 22.48 | 0.01563234 | -999.0000 | 27.00 | 0.00859030 | 27.00 | 0.00859030 | 38.6753 | 8011.82 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 430959.384 | 430959.384 | 21.299925 | 0.01055417 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 430959.38 | 430959.38 | 1.0000 | 25.63648259 | 21.299925 | -10.70 | -10.70 | 0.00150390 | -7020.5 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 430959.38 | -10.70 | 0.00150390 | -10.70 | 0.33839277 | 1.5887 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 38.2706 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9507.008 | 9507.008 | 0.472311 | 0.00023283 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 9507.01 | 9507.01 | 1.0000 | 0.56847161 | 0.472311 | -10.70 | -10.70 | 0.00150390 | -7020.5 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9507.01 | -10.70 | 0.00150390 | -10.70 | 0.01563234 | 3.3098 | 0.00 | 0.00654062 | 25.77 | 0.00654062 | 31.7584 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 90854.157 | 90854.157 | 4.506359 | 0.00222501 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 90854.16 | 90854.16 | 1.0000 | 5.42383146 | 4.506359 | -10.70 | -10.70 | 0.00150390 | -7020.5 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 90854.16 | -10.70 | 0.00150390 | -10.70 | 0.15632344 | 3.4690 | 0.00 | 0.00199518 | 23.83 | 0.00199518 | 10.9586 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9256.470 | 9256.470 | 0.459345 | 0.00022669 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 9256.47 | 9256.47 | 1.0000 | 0.55286559 | 0.459345 | -10.70 | -10.70 | 0.00150390 | -7020.5 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9256.47 | -10.70 | 0.00150390 | -10.70 | 0.01563234 | 3.4032 | 0.00 | 0.00199484 | 22.74 | 0.00199484 | 11.7052 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 20749.821 | 20749.821 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 21.299925 | 25.63648259 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 20749.82 | 20749.82 | 1.0000 | 25.63648259 | 21.299925 | -0.17 | -0.17 | 0.00838885 | 20806.6 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20749.82 | -10.70 | 0.00150390 | -10.70 | 0.33839277 | 1.5887 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 38.2706 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 958.556 | 958.556 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.472311 | 0.56847161 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 958.56 | 958.56 | 1.0000 | 0.56847161 | 0.472311 | -0.35 | -0.35 | 0.00637392 | 15580.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 958.56 | -10.70 | 0.00150390 | -10.70 | 0.01563234 | 3.3098 | 0.00 | 0.00654062 | 25.77 | 0.00654062 | 31.7584 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9585.558 | 9585.558 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 4.506359 | 5.42383146 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 9585.56 | 9585.56 | 1.0000 | 5.42383146 | 4.506359 | -0.37 | -3.04 | 0.00197814 | 4572.9 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9585.56 | -10.70 | 0.00150390 | -10.70 | 0.15632344 | 3.4690 | 0.00 | 0.00199518 | 23.83 | 0.00199518 | 10.9586 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 958.556 | 958.556 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.459345 | 0.55286559 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 958.56 | 958.56 | 1.0000 | 0.55286559 | 0.459345 | -0.36 | -3.03 | 0.00197813 | 4579.9 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 958.56 | -10.70 | 0.00150390 | -10.70 | 0.01563234 | 3.4032 | 0.00 | 0.00199484 | 22.74 | 0.00199484 | 11.7052 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:39
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 9.25 | - | |||
VAV_MID WITH REHEAT_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 86.39 | - | |||
VAV_TOP WITH REHEAT_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 9.32 | - | |||
CAV_BAS_OA_CONTROLLER | DifferentialEnthalpy | 1.20 | 5.28 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 2931.67 | 1690.00 | 591.33 |
CORE_BOTTOM | 2753.67 | 1272.00 | 0.00 |
CORE_MID | 2309.00 | 2828.00 | 134.83 |
CORE_TOP | 2759.33 | 3323.67 | 741.00 |
PERIMETER_BOT_ZN_3 | 2565.67 | 3031.67 | 346.67 |
PERIMETER_BOT_ZN_2 | 2692.33 | 3000.17 | 398.83 |
PERIMETER_BOT_ZN_1 | 2887.00 | 2588.33 | 396.50 |
PERIMETER_BOT_ZN_4 | 3189.17 | 1998.67 | 348.00 |
PERIMETER_MID_ZN_3 | 3462.83 | 3728.83 | 1713.50 |
PERIMETER_MID_ZN_2 | 2945.67 | 3082.33 | 1356.33 |
PERIMETER_MID_ZN_1 | 3226.83 | 3051.83 | 1027.67 |
PERIMETER_MID_ZN_4 | 3381.33 | 3416.00 | 1314.67 |
PERIMETER_TOP_ZN_3 | 3944.67 | 3920.67 | 2309.17 |
PERIMETER_TOP_ZN_2 | 3936.17 | 3720.83 | 2051.17 |
PERIMETER_TOP_ZN_1 | 3607.67 | 3391.83 | 1575.83 |
PERIMETER_TOP_ZN_4 | 3780.00 | 3661.67 | 1868.17 |
DATACENTER_BOT_ZN_6 | 5910.83 | 928.83 | 928.83 |
DATACENTER_MID_ZN_6 | 5438.17 | 245.17 | 171.17 |
DATACENTER_TOP_ZN_6 | 4912.33 | 619.00 | 375.00 |
DATACENTER_BASEMENT_ZN_6 | 5943.00 | 5609.67 | 5609.67 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5943.00 | 5943.00 | 5939.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 62.83 | 0.00 | 0.83 |
CORE_BOTTOM | 0.00 | 2.33 | 0.00 | 0.00 |
CORE_MID | 2.33 | 0.00 | 1.17 | 0.00 |
CORE_TOP | 8.17 | 0.00 | 1.17 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.67 | 1.33 | 0.00 | 0.67 |
PERIMETER_BOT_ZN_2 | 0.83 | 20.17 | 0.00 | 19.83 |
PERIMETER_BOT_ZN_1 | 1.00 | 31.17 | 0.00 | 28.33 |
PERIMETER_BOT_ZN_4 | 0.33 | 103.50 | 0.00 | 39.00 |
PERIMETER_MID_ZN_3 | 60.83 | 0.00 | 15.50 | 0.00 |
PERIMETER_MID_ZN_2 | 35.17 | 22.67 | 3.00 | 22.50 |
PERIMETER_MID_ZN_1 | 28.17 | 25.67 | 2.67 | 24.67 |
PERIMETER_MID_ZN_4 | 27.17 | 27.00 | 3.33 | 16.50 |
PERIMETER_TOP_ZN_3 | 178.50 | 3.83 | 52.33 | 3.00 |
PERIMETER_TOP_ZN_2 | 118.83 | 30.17 | 24.17 | 29.17 |
PERIMETER_TOP_ZN_1 | 94.67 | 27.17 | 13.33 | 25.33 |
PERIMETER_TOP_ZN_4 | 83.83 | 29.83 | 15.17 | 18.67 |
DATACENTER_BOT_ZN_6 | 0.00 | 7.83 | 0.00 | 7.83 |
DATACENTER_MID_ZN_6 | 0.00 | 7.33 | 0.00 | 7.33 |
DATACENTER_TOP_ZN_6 | 0.00 | 3.33 | 0.00 | 3.33 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 334.33 | 0.00 | 298.17 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 198.83 | 568.00 | 56.00 | 405.67 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:39
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.22 | 149.60 | 6779.02 | 1.094 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.88 | 134.35 | 6849.35 | 0.802 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.88 | 134.35 | 6849.35 | 0.639 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.88 | 134.35 | 6849.35 | 0.622 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 7.02 | 16.87 | 860.00 | 0.755 | 0.055 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.52 | 10.87 | 554.22 | 1.039 | 0.057 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 7.02 | 16.87 | 860.02 | 1.098 | 0.055 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.52 | 10.87 | 554.22 | 1.533 | 0.057 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 7.02 | 16.87 | 860.00 | 0.663 | 0.129 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.95 | 10.87 | 554.22 | 0.956 | 0.142 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 7.02 | 16.87 | 860.02 | 1.014 | 0.129 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.52 | 10.87 | 554.22 | 1.099 | 0.133 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 7.02 | 16.87 | 860.00 | 0.677 | 0.159 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.52 | 10.87 | 554.22 | 1.040 | 0.165 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 7.02 | 16.87 | 860.02 | 1.006 | 0.160 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.52 | 10.87 | 554.22 | 1.123 | 0.165 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.427 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.427 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.427 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.54 | 42.18 | 1911.37 | 0.481 | 0.000 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.22 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.88 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.88 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.88 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 7.02 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.52 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 7.02 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.52 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 7.02 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.95 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 7.02 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.52 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 7.02 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.52 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 7.02 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.52 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.54 | 42.18 | 1911.37 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 09:04:39
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | CAV_BAS | 62.22 | 149.60 | 6779.02 | 2779.43 | 1.2002 | 1.200 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 55.88 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
CORE_MID | VAV_MID WITH REHEAT | 55.88 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 10.778 |
CORE_TOP | VAV_TOP WITH REHEAT | 55.88 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 7.02 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 4.52 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 7.02 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 4.52 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 7.02 | 16.87 | 860.00 | 313.41 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 3.95 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 7.02 | 16.87 | 860.02 | 313.42 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 4.52 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 7.02 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 4.52 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 7.02 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 4.52 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.81 | 1.95 | 99.34 | 36.20 | 0.1563 | 0.156 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 17.54 | 42.18 | 1911.37 | 783.68 | 0.3384 | 0.338 |
Total Facility | 1031.21 | 2493.19 | 126016.35 | 46320.38 | 1.7261 | 158.471 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 45488677.95 | 0.00 | 45488677.95 | 0.00 | 45488677.95 | 37848132.68 | 4010.95 | 1399.75 | 3349.30 | 320.54 |
CORE_BOTTOM | 33978958.79 | 0.00 | 33978958.79 | 0.00 | 33978958.79 | 33990283.35 | 5386.10 | 101.11 | 3272.78 | 331.05 |
CORE_MID | 0.26E+09 | 0.00 | 0.26E+09 | 0.00 | 0.26E+09 | 0.34E+09 | 6433.93 | 241.77 | 2084.30 | 225.97 |
CORE_TOP | 25461877.89 | 0.00 | 25461877.89 | 0.00 | 25461877.89 | 33990283.35 | 6847.91 | 38.58 | 1873.50 | 354.18 |
PERIMETER_BOT_ZN_3 | 4013838.38 | 0.00 | 4013838.38 | 542909.24 | 4556747.62 | 4267819.30 | 5386.81 | 70.34 | 3302.86 | 331.05 |
PERIMETER_BOT_ZN_2 | 3560798.69 | 0.00 | 3560798.69 | 361939.24 | 3922737.94 | 2750345.05 | 3851.00 | 42.45 | 4866.55 | 331.05 |
PERIMETER_BOT_ZN_1 | 5752387.95 | 0.00 | 5752387.95 | 542909.24 | 6295297.19 | 4267912.63 | 4312.60 | 104.38 | 4343.02 | 331.05 |
PERIMETER_BOT_ZN_4 | 5220914.47 | 0.00 | 5220914.47 | 361939.24 | 5582853.72 | 2750345.05 | 3723.36 | 4.89 | 5031.76 | 331.05 |
PERIMETER_MID_ZN_3 | 34233480.55 | 0.00 | 34233480.55 | 1273269.14 | 35506749.70 | 42678193.03 | 5617.06 | 254.33 | 2888.61 | 225.97 |
PERIMETER_MID_ZN_2 | 34213161.99 | 0.00 | 34213161.99 | 848845.52 | 35062007.50 | 27503450.52 | 4102.74 | 11.62 | 4645.63 | 1134.97 |
PERIMETER_MID_ZN_1 | 51851833.58 | 0.00 | 51851833.58 | 1273269.14 | 53125102.72 | 42679126.28 | 4204.29 | 65.45 | 4490.26 | 225.97 |
PERIMETER_MID_ZN_4 | 36487237.25 | 0.00 | 36487237.25 | 848845.52 | 37336082.76 | 27503450.52 | 4082.71 | 5.61 | 4671.68 | 225.97 |
PERIMETER_TOP_ZN_3 | 3486406.56 | 0.00 | 3486406.56 | 1580892.99 | 5067299.55 | 4267819.30 | 4607.30 | 1193.61 | 2959.09 | 354.18 |
PERIMETER_TOP_ZN_2 | 3438899.52 | 0.00 | 3438899.52 | 1053927.94 | 4492827.46 | 2750345.05 | 4161.75 | 7.96 | 4590.29 | 354.18 |
PERIMETER_TOP_ZN_1 | 5140343.53 | 0.00 | 5140343.53 | 1580892.99 | 6721236.52 | 4267912.63 | 4188.27 | 7.32 | 4564.41 | 354.18 |
PERIMETER_TOP_ZN_4 | 3718327.44 | 0.00 | 3718327.44 | 1053927.94 | 4772255.38 | 2750345.05 | 4135.98 | 4.53 | 4619.49 | 354.18 |
DATACENTER_BOT_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2442960.18 | 0.00 | 2442960.18 | 0.00 | 2442960.18 | 4929815.99 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 5288266.81 | 0.00 | 5288266.81 | 0.00 | 5288266.81 | 10671554.30 | 4419.00 | 4341.00 | 0.00 | 0.00 |
Total Facility | 0.44E+10 | 0.00 | 0.44E+10 | 49521632.03 | 0.44E+10 | 0.50E+10 | 7184.22 | 4394.07 | 5202.94 | 1679.99 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 2.0170 | 0.0000 | 2.0170 | 0.0000 | 2.0170 | 1.2002 | 1379.66 | 1397.23 | 3166.11 |
CORE_BOTTOM | 1.4955 | 0.0000 | 1.4955 | 0.0000 | 1.4955 | 1.0778 | 2832.19 | 98.69 | 3012.11 |
CORE_MID | 11.9147 | 0.0000 | 11.9147 | 0.0000 | 11.9147 | 10.7782 | 3693.62 | 241.73 | 2007.66 |
CORE_TOP | 1.1604 | 0.0000 | 1.1604 | 0.0000 | 1.1604 | 1.0778 | 4081.93 | 38.58 | 1822.49 |
PERIMETER_BOT_ZN_3 | 0.1768 | 0.0000 | 0.1768 | 0.0129 | 0.1897 | 0.1353 | 2827.63 | 67.92 | 3047.45 |
PERIMETER_BOT_ZN_2 | 0.1570 | 0.0000 | 0.1570 | 0.0086 | 0.1656 | 0.0872 | 1335.26 | 40.35 | 4567.39 |
PERIMETER_BOT_ZN_1 | 0.2574 | 0.0000 | 0.2574 | 0.0129 | 0.2703 | 0.1353 | 1759.74 | 102.33 | 4080.92 |
PERIMETER_BOT_ZN_4 | 0.2313 | 0.0000 | 0.2313 | 0.0086 | 0.2399 | 0.0872 | 1222.95 | 3.76 | 4716.29 |
PERIMETER_MID_ZN_3 | 1.5544 | 0.0000 | 1.5544 | 0.0303 | 1.5848 | 1.3533 | 2879.96 | 253.97 | 2809.07 |
PERIMETER_MID_ZN_2 | 1.4450 | 0.0000 | 1.4450 | 0.0215 | 1.4665 | 0.8721 | 1368.04 | 6.13 | 3659.83 |
PERIMETER_MID_ZN_1 | 2.3759 | 0.0000 | 2.3759 | 0.0303 | 2.4062 | 1.3533 | 1468.73 | 65.00 | 4409.27 |
PERIMETER_MID_ZN_4 | 1.6612 | 0.0000 | 1.6612 | 0.0202 | 1.6814 | 0.8721 | 1358.30 | 3.79 | 4580.91 |
PERIMETER_TOP_ZN_3 | 0.1589 | 0.0000 | 0.1589 | 0.0377 | 0.1966 | 0.1353 | 1844.78 | 1193.13 | 2905.09 |
PERIMETER_TOP_ZN_2 | 0.1572 | 0.0000 | 0.1572 | 0.0251 | 0.1823 | 0.0872 | 1406.36 | 7.10 | 4529.54 |
PERIMETER_TOP_ZN_1 | 0.2359 | 0.0000 | 0.2359 | 0.0377 | 0.2736 | 0.1353 | 1426.41 | 6.64 | 4509.95 |
PERIMETER_TOP_ZN_4 | 0.1698 | 0.0000 | 0.1698 | 0.0251 | 0.1949 | 0.0872 | 1387.47 | 3.35 | 4552.18 |
DATACENTER_BOT_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.1142 | 0.0000 | 0.1142 | 0.0000 | 0.1142 | 0.1563 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.2472 | 0.0000 | 0.2472 | 0.0000 | 0.2472 | 0.3384 | 1602.00 | 4341.00 | 0.00 |
Total Facility | 197.1415 | 0.0000 | 197.1415 | 1.1927 | 198.3342 | 158.4706 | 4367.22 | 4376.09 | 4781.45 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV_BOT WITH REHEAT | 76098470.79 | 0.00 | 76098470.79 | 48026705.38 | 3743.90 | 5.27 | 5010.83 | 331.05 |
VAV_MID WITH REHEAT | 0.61E+09 | 0.00 | 0.61E+09 | 0.48E+09 | 4071.73 | 9.07 | 4679.21 | 225.97 |
VAV_TOP WITH REHEAT | 59746121.60 | 0.00 | 59746121.60 | 48026705.38 | 4140.14 | 4.88 | 4614.98 | 354.18 |
CAV_BAS | 65896758.45 | 0.00 | 65896758.45 | 37848132.68 | 3934.47 | 3.21 | 4822.31 | 320.54 |
AIRLOOP DATACENTER BASEMENT | 7660799.48 | 0.00 | 7660799.48 | 10671554.30 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER BOT | 353897.20 | 0.00 | 353897.20 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER MID | 3538971.99 | 0.00 | 3538971.99 | 4929815.99 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER TOP | 353897.20 | 0.00 | 353897.20 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV_BOT WITH REHEAT | 3.3581 | 0.0000 | 3.3581 | 1.5229 | 1238.40 | 4.02 | 4700.57 |
VAV_MID WITH REHEAT | 27.6153 | 0.0000 | 27.6153 | 15.2292 | 1349.41 | 5.35 | 4588.24 |
VAV_TOP WITH REHEAT | 2.7265 | 0.0000 | 2.7265 | 1.5229 | 1388.02 | 2.81 | 4552.17 |
CAV_BAS | 2.9219 | 0.0000 | 2.9219 | 1.2002 | 1351.79 | 0.66 | 4590.55 |
AIRLOOP DATACENTER BASEMENT | 0.3581 | 0.0000 | 0.3581 | 0.3384 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER BOT | 0.0165 | 0.0000 | 0.0165 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER MID | 0.1654 | 0.0000 | 0.1654 | 0.1563 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER TOP | 0.0165 | 0.0000 | 0.0165 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV_BOT WITH REHEAT | 0.00 | 0.87 | 3079.62 | 0.00 | 0.00 | 0.00 | 1999.03 | 0.00 | 0.00 | 0.00 |
VAV_MID WITH REHEAT | 0.00 | 0.69 | 2658.52 | 0.00 | 0.00 | 0.00 | 2269.33 | 0.00 | 0.00 | 0.00 |
VAV_TOP WITH REHEAT | 0.00 | 1.17 | 2428.34 | 0.00 | 0.00 | 0.00 | 2665.81 | 0.00 | 0.00 | 0.00 |
CAV_BAS | 0.00 | 1387.89 | 3543.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV_BOT WITH REHEAT | 0.0000 | 0.0000 | 5.5122 | 0.0000 | 0.0000 | 0.0000 | 2.4001 | 0.0000 | 0.0000 | 0.0000 |
VAV_MID WITH REHEAT | 0.0000 | 0.0000 | 45.3740 | 0.0000 | 0.0000 | 0.0000 | 23.6591 | 0.0000 | 0.0000 | 0.0000 |
VAV_TOP WITH REHEAT | 0.0000 | 15.7569 | 4.7911 | 0.0000 | 0.0000 | 0.0000 | 2.3456 | 0.0000 | 0.0000 | 0.0000 |
CAV_BAS | 0.0000 | 1.7397 | 4.6390 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BASEMENT | 0.0000 | 0.4903 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BOT | 0.0000 | 0.0227 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER MID | 0.0000 | 0.2265 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER TOP | 0.0000 | 0.0227 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:39
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 8 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1386 |
Defaulted Fields | 1179 |
Fields with Defaults | 3922 |
Autosized Fields | 333 |
Autosizable Fields | 412 |
Autocalculated Fields | 226 |
Autocalculatable Fields | 473 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 09:04:39
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 27893.64 | 359665.34 | 01-JAN-14:00 | 1959609.74 | 22-AUG-14:40 |
Electricity:Building | 17959.14 | 247233.96 | 01-JAN-08:30 | 1055078.17 | 01-DEC-16:30 |
Electricity:Zone:BASEMENT | 602.14 | 14319.77 | 01-JAN-00:10 | 28977.00 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 17959.14 | 247233.96 | 01-JAN-08:30 | 1055078.17 | 01-DEC-16:30 |
InteriorLights:Electricity | 2745.73 | 13024.70 | 01-JAN-08:30 | 261074.09 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:BASEMENT | 177.74 | 862.23 | 01-JAN-00:10 | 15519.45 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 2745.73 | 13024.70 | 01-JAN-08:30 | 261074.09 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity | 2745.73 | 13024.70 | 01-JAN-08:30 | 261074.09 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 177.74 | 862.23 | 01-JAN-00:10 | 15519.45 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 2745.73 | 13024.70 | 01-JAN-08:30 | 261074.09 | 02-JAN-16:40 |
Electricity:Zone:CORE_BOTTOM | 480.91 | 6817.20 | 01-JAN-00:10 | 32066.15 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 159.62 | 774.34 | 01-JAN-00:10 | 13937.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 159.62 | 774.34 | 01-JAN-00:10 | 13937.56 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 4809.09 | 68171.81 | 01-JAN-00:10 | 320660.81 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 1596.25 | 7743.41 | 01-JAN-00:10 | 139375.61 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 1596.25 | 7743.41 | 01-JAN-00:10 | 139375.61 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 480.91 | 6817.18 | 01-JAN-00:10 | 32066.08 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 159.62 | 774.34 | 01-JAN-00:10 | 13937.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 159.62 | 774.34 | 01-JAN-00:10 | 13937.56 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 54.23 | 818.50 | 01-JAN-08:30 | 4026.32 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 13.89 | 59.73 | 01-JAN-08:30 | 1750.00 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 13.89 | 59.73 | 01-JAN-08:30 | 1750.00 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 34.94 | 527.47 | 01-JAN-07:50 | 2594.71 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 8.95 | 38.49 | 01-JAN-07:50 | 1127.77 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 8.95 | 38.49 | 01-JAN-07:50 | 1127.77 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 54.14 | 818.51 | 01-JAN-07:50 | 4026.39 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 13.80 | 59.73 | 01-JAN-07:50 | 1750.04 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 13.80 | 59.73 | 01-JAN-07:50 | 1750.04 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 34.90 | 527.47 | 01-JAN-08:30 | 2594.70 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 8.90 | 38.49 | 01-JAN-08:30 | 1127.77 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 8.90 | 38.49 | 01-JAN-08:30 | 1127.77 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 542.46 | 8184.99 | 01-JAN-08:30 | 40263.18 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 139.03 | 597.26 | 01-JAN-08:30 | 17500.00 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 139.03 | 597.26 | 01-JAN-08:30 | 17500.00 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 349.47 | 5274.72 | 01-JAN-07:50 | 25947.12 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 89.49 | 384.90 | 01-JAN-07:50 | 11277.66 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 89.49 | 384.90 | 01-JAN-07:50 | 11277.66 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 541.47 | 8185.12 | 01-JAN-08:00 | 40263.91 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 138.04 | 597.27 | 01-JAN-08:00 | 17500.38 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 138.04 | 597.27 | 01-JAN-08:00 | 17500.38 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 349.03 | 5274.69 | 01-JAN-08:30 | 25947.03 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 89.05 | 384.90 | 01-JAN-08:30 | 11277.66 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 89.05 | 384.90 | 01-JAN-08:30 | 11277.66 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 54.25 | 818.50 | 01-JAN-08:30 | 4026.32 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 13.90 | 59.73 | 01-JAN-08:30 | 1750.00 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 13.90 | 59.73 | 01-JAN-08:30 | 1750.00 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 34.95 | 527.47 | 01-JAN-07:50 | 2594.71 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 8.95 | 38.49 | 01-JAN-07:50 | 1127.77 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 8.95 | 38.49 | 01-JAN-07:50 | 1127.77 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 54.15 | 818.51 | 01-JAN-08:00 | 4026.39 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 13.80 | 59.73 | 01-JAN-08:00 | 1750.04 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 13.80 | 59.73 | 01-JAN-08:00 | 1750.04 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 34.90 | 527.47 | 01-JAN-08:30 | 2594.70 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 8.91 | 38.49 | 01-JAN-08:30 | 1127.77 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 8.91 | 38.49 | 01-JAN-08:30 | 1127.77 | 02-JAN-16:40 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7544.97 | 95151.24 | 01-JAN-00:10 | 384008.34 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 50.12 | 243.11 | 01-JAN-00:10 | 4375.82 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 50.12 | 243.11 | 01-JAN-00:10 | 4375.82 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 158.52 | 1971.11 | 01-JAN-00:10 | 8199.53 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 4.64 | 22.51 | 01-JAN-00:10 | 405.10 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 4.64 | 22.51 | 01-JAN-00:10 | 405.10 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1585.20 | 19711.13 | 01-JAN-00:10 | 81995.25 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 46.40 | 225.07 | 01-JAN-00:10 | 4051.03 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 46.40 | 225.07 | 01-JAN-00:10 | 4051.03 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 158.52 | 1971.11 | 01-JAN-00:10 | 8199.53 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 4.64 | 22.51 | 01-JAN-00:10 | 405.10 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 4.64 | 22.51 | 01-JAN-00:10 | 405.10 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 15213.41 | 234209.26 | 01-JAN-00:10 | 794004.08 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 15213.41 | 234209.26 | 01-JAN-00:10 | 794004.08 | 03-APR-07:10 |
MiscPlug:InteriorEquipment:Electricity | 5871.99 | 115917.86 | 01-JAN-00:10 | 320838.49 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 5871.99 | 115917.86 | 01-JAN-00:10 | 320838.49 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 321.29 | 6042.86 | 01-JAN-00:10 | 18128.59 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 321.29 | 6042.86 | 01-JAN-00:10 | 18128.59 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 3212.85 | 60428.40 | 01-JAN-00:10 | 181285.20 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 3212.85 | 60428.40 | 01-JAN-00:10 | 181285.20 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 321.28 | 6042.84 | 01-JAN-00:10 | 18128.52 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 321.28 | 6042.84 | 01-JAN-00:10 | 18128.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 40.34 | 758.77 | 01-JAN-00:10 | 2276.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 40.34 | 758.77 | 01-JAN-00:10 | 2276.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.95 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.95 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 40.34 | 758.78 | 01-JAN-00:10 | 2276.35 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 40.34 | 758.78 | 01-JAN-00:10 | 2276.35 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.94 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.94 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 403.42 | 7587.73 | 01-JAN-00:10 | 22763.18 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 403.42 | 7587.73 | 01-JAN-00:10 | 22763.18 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 259.98 | 4889.82 | 01-JAN-00:10 | 14669.46 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 259.98 | 4889.82 | 01-JAN-00:10 | 14669.46 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 403.43 | 7587.84 | 01-JAN-00:10 | 22763.53 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 403.43 | 7587.84 | 01-JAN-00:10 | 22763.53 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 259.98 | 4889.79 | 01-JAN-00:10 | 14669.36 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 259.98 | 4889.79 | 01-JAN-00:10 | 14669.36 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 40.34 | 758.77 | 01-JAN-00:10 | 2276.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 40.34 | 758.77 | 01-JAN-00:10 | 2276.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.95 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.95 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 40.34 | 758.78 | 01-JAN-00:10 | 2276.35 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 40.34 | 758.78 | 01-JAN-00:10 | 2276.35 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.94 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.94 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
Electricity:Plant | 2708.40 | 5450.30 | 02-JAN-05:20 | 434328.31 | 22-AUG-14:40 |
HeatRejection:Electricity | 1130.44 | 1866.13 | 02-JAN-07:20 | 90459.19 | 09-JUL-08:10 |
General:HeatRejection:Electricity | 1130.44 | 1866.13 | 02-JAN-07:20 | 90459.19 | 09-JUL-08:10 |
Electricity:HVAC | 4922.23 | 72083.80 | 01-JAN-24:00 | 462798.97 | 22-AUG-14:40 |
ExteriorEquipment:Electricity | 1914.38 | 28294.68 | 01-JAN-00:10 | 117200.89 | 03-JAN-08:20 |
Transformer:ExteriorEquipment:Electricity | 59.77 | 1112.61 | 01-JAN-00:10 | 3726.76 | 01-DEC-16:40 |
ElectricityPurchased:Facility | 27893.64 | 359665.34 | 01-JAN-14:00 | 1959609.74 | 22-AUG-14:40 |
ElectricityPurchased:Plant | 27893.64 | 359665.34 | 01-JAN-14:00 | 1959609.74 | 22-AUG-14:40 |
Cogeneration:ElectricityPurchased | 27893.64 | 359665.34 | 01-JAN-14:00 | 1959609.74 | 22-AUG-14:40 |
General:Cogeneration:ElectricityPurchased | 27893.64 | 359665.34 | 01-JAN-14:00 | 1959609.74 | 22-AUG-14:40 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 27893.64 | 359665.34 | 01-JAN-14:00 | 1959609.74 | 22-AUG-14:40 |
ElectricityNet:Plant | 27893.64 | 359665.34 | 01-JAN-14:00 | 1959609.74 | 22-AUG-14:40 |
Cogeneration:ElectricityNet | 27893.64 | 359665.34 | 01-JAN-14:00 | 1959609.74 | 22-AUG-14:40 |
General:Cogeneration:ElectricityNet | 27893.64 | 359665.34 | 01-JAN-14:00 | 1959609.74 | 22-AUG-14:40 |
Fans:Electricity | 2283.57 | 41405.87 | 02-JAN-22:30 | 283348.35 | 22-AUG-14:40 |
General:Fans:Electricity | 2283.57 | 41405.87 | 02-JAN-22:30 | 283348.35 | 22-AUG-14:40 |
ExteriorLights:Electricity | 449.24 | 0.00 | 01-JAN-07:30 | 37611.08 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 449.24 | 0.00 | 01-JAN-07:30 | 37611.08 | 01-JAN-06:10 |
ElevatorLift:ExteriorEquipment:Electricity | 1848.78 | 27144.47 | 01-JAN-00:10 | 113101.96 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 5.83 | 37.60 | 01-JAN-00:10 | 376.00 | 01-JAN-07:10 |
HeatRecovery:Electricity | 48.90 | 0.00 | 01-JAN-00:10 | 5613.48 | 02-JAN-07:10 |
General:HeatRecovery:Electricity | 48.90 | 0.00 | 01-JAN-00:10 | 5613.48 | 02-JAN-07:10 |
Cooling:Electricity | 3472.96 | 26163.57 | 02-JAN-07:20 | 448279.91 | 04-AUG-14:00 |
General:Cooling:Electricity | 3472.96 | 26163.57 | 02-JAN-07:20 | 448279.91 | 04-AUG-14:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Humidifier:Electricity | 14.23 | 0.00 | 01-JAN-00:10 | 6185.89 | 02-JAN-20:00 |
General:Humidifier:Electricity | 14.23 | 0.00 | 01-JAN-00:10 | 6185.89 | 02-JAN-20:00 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Pumps:Electricity | 620.77 | 3376.53 | 01-JAN-00:40 | 75732.46 | 30-AUG-13:50 |
General:Pumps:Electricity | 620.77 | 3376.53 | 01-JAN-00:40 | 75732.46 | 30-AUG-13:50 |
WIRED_LTG_ELECTRICITY | 77.15 | 0.00 | 01-JAN-00:10 | 7336.18 | 02-JAN-16:50 |
WIRED_INT_EQUIP | 5871.99 | 115917.86 | 04-MAR-00:10 | 320838.49 | 03-APR-07:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 1828.42 | 5695.87 | 13-AUG-15:00 | 1752188.17 | 02-JAN-05:10 |
NaturalGas:Plant | 1828.42 | 5695.87 | 13-AUG-15:00 | 1752188.17 | 02-JAN-05:10 |
Heating:NaturalGas | 1121.52 | 0.00 | 01-JAN-00:40 | 1746492.30 | 02-JAN-05:10 |
Boiler:Heating:NaturalGas | 1121.52 | 0.00 | 01-JAN-00:40 | 1746492.30 | 02-JAN-05:10 |
WaterSystems:NaturalGas | 706.90 | 5695.87 | 02-JAN-06:10 | 82525.26 | 08-FEB-12:40 |
Water Heater:WaterSystems:NaturalGas | 706.90 | 5695.87 | 02-JAN-06:10 | 82525.26 | 08-FEB-12:40 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 18841.29 | 130485.59 | 02-JAN-07:20 | 2662047.41 | 22-AUG-14:40 |
PlantLoopCoolingDemand:HVAC | 18841.29 | 130485.59 | 02-JAN-07:20 | 2662047.41 | 22-AUG-14:40 |
CoolingCoils:PlantLoopCoolingDemand | 18841.29 | 130485.59 | 02-JAN-07:20 | 2662047.41 | 22-AUG-14:40 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 7251.98 | 0.00 | 01-JAN-00:10 | 0.00 | 30-AUG-15:50 |
Water:HVAC | 5.29 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-20:00 |
Humidifier:Water | 5.29 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-20:00 |
General:Humidifier:Water | 5.29 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-20:00 |
MainsWater:Facility | 7251.98 | 0.00 | 01-JAN-00:10 | 0.00 | 30-AUG-15:50 |
MainsWater:HVAC | 5.29 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-20:00 |
Humidifier:MainsWater | 5.29 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-20:00 |
General:Humidifier:MainsWater | 5.29 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-20:00 |
Water:Plant | 7246.69 | 0.00 | 01-JAN-00:10 | 0.00 | 30-AUG-15:50 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 7246.69 | 0.00 | 01-JAN-00:10 | 0.00 | 30-AUG-15:50 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatRejection:Water | 4966.52 | 0.00 | 01-JAN-00:10 | 0.00 | 30-AUG-15:50 |
General:HeatRejection:Water | 4966.52 | 0.00 | 01-JAN-00:10 | 0.00 | 30-AUG-15:50 |
HeatRejection:MainsWater | 4966.52 | 0.00 | 01-JAN-00:10 | 0.00 | 30-AUG-15:50 |
General:HeatRejection:MainsWater | 4966.52 | 0.00 | 01-JAN-00:10 | 0.00 | 30-AUG-15:50 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 58429.05 | 209852.27 | 02-JAN-06:00 | 10607950.59 | 22-AUG-14:40 |
EnergyTransfer:Building | 18411.43 | 88478.70 | 28-JAN-18:20 | 1602770.89 | 18-AUG-15:00 |
EnergyTransfer:Zone:BASEMENT | 640.80 | 0.00 | 01-JAN-00:10 | 70094.23 | 13-NOV-06:10 |
Heating:EnergyTransfer | 610.15 | 0.00 | 19-JAN-22:10 | 1374424.63 | 02-JAN-05:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 3.19 | 0.00 | 01-JAN-00:10 | 11793.43 | 12-AUG-16:10 |
General:Heating:EnergyTransfer | 610.15 | 0.00 | 19-JAN-22:10 | 1374424.63 | 02-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 3.19 | 0.00 | 01-JAN-00:10 | 11793.43 | 12-AUG-16:10 |
Cooling:EnergyTransfer | 17801.28 | 84269.82 | 02-JAN-04:40 | 1602770.89 | 18-AUG-15:00 |
Cooling:EnergyTransfer:Zone:BASEMENT | 637.61 | 0.00 | 01-JAN-00:10 | 70094.23 | 13-NOV-06:10 |
General:Cooling:EnergyTransfer | 17801.28 | 84269.82 | 02-JAN-04:40 | 1602770.89 | 18-AUG-15:00 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 637.61 | 0.00 | 01-JAN-00:10 | 70094.23 | 13-NOV-06:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 605.63 | 0.00 | 01-JAN-00:10 | 52350.18 | 14-AUG-09:40 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 605.63 | 0.00 | 01-JAN-00:10 | 52350.18 | 14-AUG-09:40 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 605.63 | 0.00 | 01-JAN-00:10 | 52350.18 | 14-AUG-09:40 |
EnergyTransfer:Zone:CORE_MID | 4285.41 | 0.00 | 01-JAN-00:40 | 482418.23 | 02-JAN-05:30 |
Heating:EnergyTransfer:Zone:CORE_MID | 11.63 | 0.00 | 01-JAN-00:20 | 482418.23 | 02-JAN-05:30 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 11.63 | 0.00 | 01-JAN-00:20 | 482418.23 | 02-JAN-05:30 |
Cooling:EnergyTransfer:Zone:CORE_MID | 4273.77 | 0.00 | 01-JAN-00:40 | 451679.06 | 11-JUL-14:30 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 4273.77 | 0.00 | 01-JAN-00:40 | 451679.06 | 11-JUL-14:30 |
EnergyTransfer:Zone:CORE_TOP | 407.63 | 0.00 | 01-JAN-00:40 | 70289.10 | 02-JAN-05:30 |
Heating:EnergyTransfer:Zone:CORE_TOP | 11.79 | 0.00 | 01-JAN-00:40 | 70289.10 | 02-JAN-05:30 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 11.79 | 0.00 | 01-JAN-00:40 | 70289.10 | 02-JAN-05:30 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 395.85 | 0.00 | 01-JAN-00:10 | 51717.57 | 11-JUL-14:20 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 395.85 | 0.00 | 01-JAN-00:10 | 51717.57 | 11-JUL-14:20 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 71.22 | 0.00 | 01-JAN-00:10 | 10372.95 | 19-JUN-14:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.60 | 0.00 | 01-JAN-00:10 | 8464.87 | 06-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.60 | 0.00 | 01-JAN-00:10 | 8464.87 | 06-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 70.62 | 0.00 | 01-JAN-00:10 | 10372.95 | 19-JUN-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 70.62 | 0.00 | 01-JAN-00:10 | 10372.95 | 19-JUN-14:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 60.51 | 0.00 | 01-JAN-00:10 | 12166.53 | 26-JUN-08:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.41 | 0.00 | 01-JAN-00:10 | 5871.11 | 06-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.41 | 0.00 | 01-JAN-00:10 | 5871.11 | 06-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 60.11 | 0.00 | 01-JAN-00:10 | 12166.53 | 26-JUN-08:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 60.11 | 0.00 | 01-JAN-00:10 | 12166.53 | 26-JUN-08:20 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 100.47 | 0.00 | 01-JAN-00:10 | 17682.17 | 04-OCT-12:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.78 | 0.00 | 01-JAN-00:10 | 10027.91 | 02-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.78 | 0.00 | 01-JAN-00:10 | 10027.91 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 99.69 | 0.00 | 01-JAN-00:10 | 17682.17 | 04-OCT-12:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 99.69 | 0.00 | 01-JAN-00:10 | 17682.17 | 04-OCT-12:20 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 94.99 | 0.00 | 01-JAN-00:10 | 16614.94 | 15-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.06 | 0.00 | 01-JAN-00:10 | 4179.15 | 02-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.06 | 0.00 | 01-JAN-00:10 | 4179.15 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 94.93 | 0.00 | 01-JAN-00:10 | 16614.94 | 15-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 94.93 | 0.00 | 01-JAN-00:10 | 16614.94 | 15-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 597.46 | 0.00 | 01-JAN-00:40 | 128892.13 | 06-FEB-04:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 124.67 | 0.00 | 01-JAN-00:40 | 128892.13 | 06-FEB-04:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 124.67 | 0.00 | 01-JAN-00:40 | 128892.13 | 06-FEB-04:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 472.79 | 0.00 | 01-JAN-00:10 | 96672.52 | 19-JUN-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 472.79 | 0.00 | 01-JAN-00:10 | 96672.52 | 19-JUN-14:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 545.43 | 0.00 | 01-JAN-00:40 | 135515.66 | 06-FEB-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 66.15 | 0.00 | 01-JAN-00:40 | 135515.66 | 06-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 66.15 | 0.00 | 01-JAN-00:40 | 135515.66 | 06-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 479.28 | 0.00 | 01-JAN-00:10 | 128283.74 | 14-JUL-08:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 479.28 | 0.00 | 01-JAN-00:10 | 128283.74 | 14-JUL-08:50 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 875.73 | 0.00 | 01-JAN-00:40 | 177803.15 | 28-SEP-13:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 65.28 | 0.00 | 01-JAN-00:40 | 162913.66 | 02-JAN-05:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 65.28 | 0.00 | 01-JAN-00:40 | 162913.66 | 02-JAN-05:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 810.45 | 0.00 | 01-JAN-00:10 | 177803.15 | 28-SEP-13:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 810.45 | 0.00 | 01-JAN-00:10 | 177803.15 | 28-SEP-13:20 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 583.86 | 0.00 | 01-JAN-00:40 | 139443.55 | 15-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 51.44 | 0.00 | 01-JAN-00:40 | 130261.42 | 06-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 51.44 | 0.00 | 01-JAN-00:40 | 130261.42 | 06-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 532.42 | 0.00 | 01-JAN-00:10 | 139443.55 | 15-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 532.42 | 0.00 | 01-JAN-00:10 | 139443.55 | 15-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 76.04 | 0.00 | 01-JAN-00:40 | 15979.19 | 06-FEB-01:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 30.77 | 0.00 | 01-JAN-00:40 | 15979.19 | 06-FEB-01:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 30.77 | 0.00 | 01-JAN-00:40 | 15979.19 | 06-FEB-01:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 45.26 | 0.00 | 01-JAN-00:10 | 11094.55 | 19-JUN-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 45.26 | 0.00 | 01-JAN-00:10 | 11094.55 | 19-JUN-14:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 62.96 | 0.00 | 01-JAN-00:40 | 15338.64 | 06-FEB-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 16.50 | 0.00 | 01-JAN-00:40 | 15338.64 | 06-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 16.50 | 0.00 | 01-JAN-00:40 | 15338.64 | 06-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 46.46 | 0.00 | 01-JAN-00:10 | 13136.93 | 14-JUL-09:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 46.46 | 0.00 | 01-JAN-00:10 | 13136.93 | 14-JUL-09:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 95.16 | 0.00 | 01-JAN-00:40 | 19314.22 | 06-FEB-04:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 18.60 | 0.00 | 01-JAN-00:40 | 19314.22 | 06-FEB-04:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 18.60 | 0.00 | 01-JAN-00:40 | 19314.22 | 06-FEB-04:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 76.56 | 0.00 | 01-JAN-00:10 | 19085.45 | 28-SEP-13:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 76.56 | 0.00 | 01-JAN-00:10 | 19085.45 | 28-SEP-13:20 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 64.78 | 0.00 | 01-JAN-00:40 | 16357.61 | 06-FEB-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 13.31 | 0.00 | 01-JAN-00:40 | 16357.61 | 06-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 13.31 | 0.00 | 01-JAN-00:40 | 16357.61 | 06-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 51.47 | 0.00 | 01-JAN-00:10 | 14648.77 | 15-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 51.47 | 0.00 | 01-JAN-00:10 | 14648.77 | 15-AUG-16:00 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 57.82 | 0.00 | 01-JAN-00:10 | 9808.16 | 14-AUG-14:50 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 4.10 | 0.00 | 01-JAN-00:10 | 5134.98 | 02-JAN-11:50 |
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 4.10 | 0.00 | 01-JAN-00:10 | 5134.98 | 02-JAN-11:50 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 53.72 | 0.00 | 01-JAN-00:10 | 9808.16 | 14-AUG-14:50 |
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 53.72 | 0.00 | 01-JAN-00:10 | 9808.16 | 14-AUG-14:50 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 497.14 | 0.00 | 01-JAN-00:40 | 186451.43 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 141.68 | 0.00 | 01-JAN-00:40 | 186451.43 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 141.68 | 0.00 | 01-JAN-00:40 | 186451.43 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 355.46 | 0.00 | 01-JAN-00:10 | 78302.56 | 10-JUL-15:30 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 355.46 | 0.00 | 01-JAN-00:10 | 78302.56 | 10-JUL-15:30 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 102.88 | 0.00 | 01-JAN-00:40 | 28502.46 | 06-FEB-05:20 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 43.82 | 0.00 | 01-JAN-00:40 | 28502.46 | 06-FEB-05:20 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 43.82 | 0.00 | 01-JAN-00:40 | 28502.46 | 06-FEB-05:20 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 59.07 | 0.00 | 01-JAN-00:10 | 21693.77 | 19-JUN-13:50 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 59.07 | 0.00 | 01-JAN-00:10 | 21693.77 | 19-JUN-13:50 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 137.02 | 6.42 | 01-JAN-19:40 | 8071.72 | 23-APR-17:50 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.01 | 0.00 | 01-JAN-10:20 | 182.82 | 01-JAN-20:20 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.01 | 0.00 | 01-JAN-10:20 | 182.82 | 01-JAN-20:20 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 137.02 | 0.00 | 01-JAN-00:10 | 8071.72 | 23-APR-17:50 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 137.02 | 0.00 | 01-JAN-00:10 | 8071.72 | 23-APR-17:50 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1178.87 | 5.42 | 24-JAN-02:00 | 76053.88 | 31-AUG-17:30 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 4.57 | 0.00 | 02-JAN-07:10 | 5495.86 | 16-JAN-18:00 |
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 4.57 | 0.00 | 02-JAN-07:10 | 5495.86 | 16-JAN-18:00 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1174.30 | 0.00 | 01-JAN-00:10 | 76053.88 | 31-AUG-17:30 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1174.30 | 0.00 | 01-JAN-00:10 | 76053.88 | 31-AUG-17:30 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 109.10 | 0.41 | 30-JAN-20:10 | 7749.74 | 13-AUG-17:40 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.80 | 0.00 | 02-JAN-07:10 | 578.08 | 29-JAN-17:50 |
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.80 | 0.00 | 02-JAN-07:10 | 578.08 | 29-JAN-17:50 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 108.30 | 0.00 | 01-JAN-00:10 | 7749.74 | 13-AUG-17:40 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 108.30 | 0.00 | 01-JAN-00:10 | 7749.74 | 13-AUG-17:40 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7160.52 | 84259.08 | 02-JAN-05:00 | 369448.28 | 18-AUG-23:10 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7160.52 | 84259.08 | 02-JAN-05:00 | 369448.28 | 18-AUG-23:10 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7160.52 | 84259.08 | 02-JAN-05:00 | 369448.28 | 18-AUG-23:10 |
PlantLoopHeatingDemand:Facility | 1207.67 | 0.00 | 01-JAN-00:40 | 1406554.83 | 02-JAN-06:20 |
PlantLoopHeatingDemand:Plant | 411.41 | 0.00 | 01-JAN-00:10 | 52106.89 | 08-FEB-12:20 |
WaterSystems:PlantLoopHeatingDemand | 411.41 | 0.00 | 01-JAN-00:10 | 52106.89 | 08-FEB-12:20 |
General:WaterSystems:PlantLoopHeatingDemand | 411.41 | 0.00 | 01-JAN-00:10 | 52106.89 | 08-FEB-12:20 |
EnergyTransfer:HVAC | 18509.22 | 119979.39 | 02-JAN-05:20 | 2686687.98 | 04-AUG-14:00 |
HeatingCoils:EnergyTransfer | 796.26 | 0.00 | 01-JAN-00:40 | 1400301.67 | 02-JAN-06:20 |
PlantLoopHeatingDemand:HVAC | 796.26 | 0.00 | 01-JAN-00:40 | 1400301.67 | 02-JAN-06:20 |
HeatingCoils:PlantLoopHeatingDemand | 796.26 | 0.00 | 01-JAN-00:40 | 1400301.67 | 02-JAN-06:20 |
CoolingCoils:EnergyTransfer | 16325.53 | 104322.02 | 02-JAN-07:20 | 2490050.71 | 22-AUG-14:40 |
HeatRecoveryForHeating:EnergyTransfer | 916.94 | 0.00 | 01-JAN-00:10 | 587487.32 | 06-FEB-07:10 |
HeatRecoveryForCooling:EnergyTransfer | 470.49 | 0.00 | 01-JAN-00:10 | 513257.78 | 08-JUL-12:00 |
EnergyTransfer:Plant | 21508.40 | 0.00 | 01-JAN-00:40 | 6437908.63 | 22-AUG-14:40 |
LoopToLoop:EnergyTransfer | 6851.56 | -604.51 | 17-JAN-12:30 | 2026215.67 | 22-AUG-14:40 |
WaterSystems:EnergyTransfer | 411.41 | 0.00 | 01-JAN-00:10 | 52106.89 | 08-FEB-12:20 |
WaterUse:WaterSystems:EnergyTransfer | 411.41 | 0.00 | 01-JAN-00:10 | 52106.89 | 08-FEB-12:20 |
Boilers:EnergyTransfer | 792.24 | 0.00 | 01-JAN-00:40 | 1455697.43 | 02-JAN-05:10 |
Chillers:EnergyTransfer | 6248.00 | 0.00 | 01-JAN-00:10 | 2028449.81 | 22-AUG-14:40 |
HeatRejection:EnergyTransfer | 7205.20 | 0.00 | 01-JAN-00:10 | 2301620.47 | 22-AUG-14:40 |
General:HeatRejection:EnergyTransfer | 7205.20 | 0.00 | 01-JAN-00:10 | 2301620.47 | 22-AUG-14:40 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:39
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 3.188 | -637.611 | 0.000 | 0.000 | 92.852 | 177.742 | 424.397 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -60.568 |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -605.624 | 0.000 | 0.000 | 83.541 | 159.625 | 321.286 | 0.000 | 0.000 | 0.000 | 41.173 | 0.000 | 0.000 | 0.000 | 0.000 | -0.001 |
CORE_MID | 0.000 | 0.000 | 11.634 | -4273.759 | 0.000 | 0.000 | 855.231 | 1596.246 | 3212.845 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -1402.197 |
CORE_TOP | 0.000 | 0.000 | 11.787 | -395.843 | 0.000 | 0.000 | 88.255 | 159.625 | 321.285 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -185.107 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.599 | -70.623 | 0.000 | 0.000 | 10.886 | 13.890 | 40.342 | 23.885 | 0.000 | 0.118 | 35.675 | 0.000 | -46.279 | 0.000 | -8.494 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.405 | -60.107 | 0.000 | 0.000 | 7.023 | 8.946 | 25.998 | 43.864 | 0.000 | 0.083 | 7.764 | 0.000 | -28.380 | 0.000 | -5.596 | 0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 0.775 | -99.693 | 0.000 | 0.000 | 10.755 | 13.797 | 40.343 | 89.678 | 0.000 | 0.112 | 0.001 | 0.000 | -42.069 | 0.000 | -8.547 | -5.150 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.062 | -94.926 | 0.000 | 0.000 | 6.869 | 8.902 | 25.998 | 43.691 | 0.000 | 0.070 | 48.415 | 0.000 | -32.853 | 0.000 | -6.228 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 124.675 | -472.782 | 0.000 | 0.000 | 113.734 | 139.033 | 403.423 | 247.260 | 0.000 | 2.625 | 25.577 | 0.000 | -409.745 | 0.000 | -173.799 | -0.006 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 66.151 | -479.270 | 0.000 | 0.000 | 53.463 | 89.489 | 259.981 | 440.922 | 0.000 | 1.672 | 0.010 | 0.000 | -259.878 | 0.000 | -118.217 | -54.314 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 65.279 | -810.445 | 0.000 | 0.000 | 109.696 | 138.037 | 403.429 | 896.444 | 0.000 | 2.434 | 0.000 | 0.000 | -397.718 | 0.000 | -185.975 | -221.181 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 51.443 | -532.415 | 0.000 | 0.000 | 72.698 | 89.051 | 259.979 | 447.601 | 0.000 | 1.649 | 9.481 | 0.000 | -277.245 | 0.000 | -122.243 | -0.003 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 30.773 | -45.263 | 0.000 | 0.000 | 11.514 | 13.903 | 40.342 | 25.043 | 0.000 | 0.302 | 0.000 | 0.000 | -38.461 | 0.000 | -20.327 | -17.826 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 16.505 | -46.457 | 0.000 | 0.000 | 7.339 | 8.949 | 25.998 | 44.348 | 0.000 | 0.196 | 0.000 | 0.000 | -24.500 | 0.000 | -13.870 | -18.508 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 18.604 | -76.556 | 0.000 | 0.000 | 11.158 | 13.804 | 40.343 | 90.095 | 0.000 | 0.289 | 0.001 | 0.000 | -37.316 | 0.000 | -21.646 | -38.773 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 13.309 | -51.471 | 0.000 | 0.000 | 7.365 | 8.905 | 25.998 | 44.913 | 0.000 | 0.196 | 0.000 | 0.000 | -26.237 | 0.000 | -14.365 | -8.613 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.007 | -137.017 | 0.000 | 0.000 | 0.950 | 4.640 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -22.460 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 4.568 | -1174.300 | 0.000 | 0.000 | 9.512 | 46.396 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -424.981 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 0.801 | -108.300 | 0.000 | 0.000 | 0.954 | 4.640 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -51.975 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | 0.000 | 0.000 | -7160.526 | 0.000 | 0.000 | 20.327 | 50.116 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -404.774 |
GROUNDFLOOR_PLENUM | 4.096 | -53.721 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.197 | 67.673 | 0.000 | 0.000 | 0.000 | -18.245 | 0.000 |
MIDFLOOR_PLENUM | 141.683 | -355.460 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 3.530 | 511.843 | 0.000 | 0.000 | 0.000 | -301.596 | -0.000 |
TOPFLOOR_PLENUM | 43.816 | -59.066 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.283 | 46.599 | 0.000 | 0.000 | 0.000 | -31.632 | -0.000 |
Total Facility | 189.595 | -468.247 | 420.564 | -17332.988 | 0.000 | 0.000 | 1574.122 | 2745.734 | 15213.411 | 2437.742 | 0.000 | 13.756 | 794.213 | 0.000 | -1620.681 | 0.000 | -1050.779 | -2916.438 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 26-DEC-04:01 | 0.00 | 0.00 | 0.00 | -108545.55 | 0.00 | 0.00 | 0.00 | 862.23 | 13457.54 | 0.00 | 0.00 | 0.00 | 94225.78 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 13-NOV-04:02 | 0.00 | 0.00 | 0.00 | -91665.16 | 0.00 | 0.00 | 0.00 | 774.34 | 8057.15 | 0.00 | 0.00 | 0.00 | 82833.67 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 07-AUG-03:02 | 0.00 | 0.00 | 0.00 | -862675.97 | 0.00 | 0.00 | 0.00 | 7743.41 | 80571.20 | 0.00 | 0.00 | 0.00 | 774361.36 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 07-AUG-03:02 | 0.00 | 0.00 | 0.00 | -88961.98 | 0.00 | 0.00 | 0.00 | 774.34 | 8057.12 | 0.00 | 0.00 | 0.00 | 80130.52 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 13-AUG-16:21 | 0.00 | 0.00 | 0.00 | -15991.11 | 0.00 | 0.00 | 43.05 | 59.73 | 758.77 | 2790.82 | 0.00 | 74.63 | 12264.12 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 29-MAY-08:22 | 0.00 | 0.00 | 0.00 | -18181.64 | 0.00 | 0.00 | 22.06 | 38.49 | 488.98 | 14277.01 | 0.00 | 0.00 | 3387.42 | 0.00 | -0.00 | 0.00 | -32.33 | 0.00 |
PERIMETER_BOT_ZN_1 | 13-AUG-13:02 | 0.00 | 0.00 | 0.00 | -23321.16 | 0.00 | 0.00 | 35.98 | 59.73 | 758.78 | 13666.20 | 0.00 | 83.01 | 8717.46 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 13-AUG-16:21 | 0.00 | 0.00 | 0.00 | -25790.51 | 0.00 | 0.00 | 18.49 | 38.49 | 488.98 | 9830.92 | 0.00 | 7.97 | 15405.66 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 10-JUL-03:02 | 0.00 | 0.00 | 0.00 | -138092.49 | 0.00 | 0.00 | 0.00 | 972.26 | 10116.97 | 0.00 | 0.00 | 159.44 | 128853.12 | 0.00 | -2009.30 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 02-JUL-09:01 | 0.00 | 0.00 | 0.00 | -212826.16 | 0.00 | 0.00 | 211.27 | 384.90 | 4889.82 | 131031.12 | 0.00 | 0.00 | 77552.26 | 0.00 | -0.00 | 0.00 | -1243.20 | 0.00 |
PERIMETER_MID_ZN_1 | 04-SEP-11:52 | 0.00 | 0.00 | 0.00 | -237443.99 | 0.00 | 0.00 | 340.93 | 597.27 | 7587.84 | 180224.90 | 0.00 | 0.00 | 50264.47 | 0.00 | -0.00 | 0.00 | -1571.42 | 0.00 |
PERIMETER_MID_ZN_4 | 10-SEP-16:02 | 0.00 | 0.00 | 0.00 | -211602.79 | 0.00 | 0.00 | 220.63 | 384.90 | 4889.79 | 146505.81 | 0.00 | 0.00 | 62893.81 | 0.00 | -0.00 | 0.00 | -3292.14 | 0.00 |
PERIMETER_TOP_ZN_3 | 09-JUL-15:21 | 0.00 | 0.00 | 0.00 | -18156.76 | 0.00 | 0.00 | 41.20 | 59.73 | 758.77 | 4629.91 | 0.00 | 0.00 | 12705.87 | 0.00 | -0.00 | 0.00 | -38.72 | 0.00 |
PERIMETER_TOP_ZN_2 | 29-MAY-08:52 | 0.00 | 0.00 | 0.00 | -21299.15 | 0.00 | 0.00 | 21.60 | 38.49 | 488.98 | 13073.42 | 0.00 | 0.00 | 7812.46 | 0.00 | -0.00 | 0.00 | -135.81 | 0.00 |
PERIMETER_TOP_ZN_1 | 04-SEP-11:52 | 0.00 | 0.00 | 0.00 | -26182.83 | 0.00 | 0.00 | 33.51 | 59.73 | 758.78 | 17944.70 | 0.00 | 0.00 | 7589.57 | 0.00 | -0.00 | 0.00 | -203.46 | 0.00 |
PERIMETER_TOP_ZN_4 | 09-JUL-15:21 | 0.00 | 0.00 | 0.00 | -22939.54 | 0.00 | 0.00 | 21.42 | 38.49 | 488.98 | 9441.54 | 0.00 | 0.00 | 13043.40 | 0.00 | -0.00 | 0.00 | -94.28 | 0.00 |
DATACENTER_BOT_ZN_6 | 23-APR-17:45 | 0.00 | 0.00 | 0.00 | -8071.72 | 0.00 | 0.00 | 0.00 | 22.51 | 7794.42 | 0.00 | 0.00 | 0.00 | 254.79 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 31-AUG-17:30 | 0.00 | 0.00 | 0.00 | -76052.66 | 0.00 | 0.00 | 105.14 | 1350.33 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -3347.04 |
DATACENTER_TOP_ZN_6 | 13-AUG-17:40 | 0.00 | 0.00 | 0.00 | -7750.83 | 0.00 | 0.00 | 0.00 | 22.51 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -66.10 |
DATACENTER_BASEMENT_ZN_6 | 18-AUG-23:15 | 0.00 | 0.00 | 0.00 | -369559.35 | 0.00 | 0.00 | 0.00 | 243.11 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -10316.28 |
GROUNDFLOOR_PLENUM | 14-AUG-05:15 | 0.00 | -13505.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13531.69 | 0.00 | -0.00 | 0.00 | -26.52 | 0.00 |
MIDFLOOR_PLENUM | 07-AUG-05:15 | 0.00 | -95836.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97183.09 | 0.00 | -0.00 | 0.00 | -1347.07 | 0.00 |
TOPFLOOR_PLENUM | 19-JUN-13:50 | 0.00 | -21692.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 274.89 | 21418.01 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 23-AUG-05:02 | 0.00 | -17071.95 | 0.00 | -1962550.06 | 0.00 | 0.00 | 16028.24 | 29009.37 | 623236.89 | 0.00 | 0.00 | 0.00 | 1371234.60 | 0.00 | -56225.88 | 0.00 | -3661.19 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 12-AUG-16:02 | 0.00 | 0.00 | 13017.65 | 0.00 | 0.00 | 0.00 | 520.12 | 862.23 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -27857.55 |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 02-JAN-04:01 | 0.00 | 0.00 | 554995.36 | 0.00 | 0.00 | 0.00 | 0.00 | 7743.41 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -643309.96 |
CORE_TOP | 02-JAN-04:01 | 0.00 | 0.00 | 79287.83 | 0.00 | 0.00 | 0.00 | 0.00 | 774.34 | 8057.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -88119.29 |
PERIMETER_BOT_ZN_3 | 06-FEB-05:01 | 0.00 | 0.00 | 12302.13 | 0.00 | 0.00 | 0.00 | 0.00 | 194.45 | 1011.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5418.45 | 0.00 | -2040.38 | -6049.45 |
PERIMETER_BOT_ZN_2 | 06-FEB-05:01 | 0.00 | 0.00 | 11582.08 | 0.00 | 0.00 | 0.00 | 0.00 | 125.31 | 651.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3511.53 | 0.00 | -1368.56 | -7479.28 |
PERIMETER_BOT_ZN_1 | 02-JAN-04:01 | 0.00 | 0.00 | 17511.71 | 0.00 | 0.00 | 0.00 | 0.00 | 97.23 | 1011.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4725.55 | 0.00 | -621.97 | -13273.13 |
PERIMETER_BOT_ZN_4 | 02-JAN-05:01 | 0.00 | 0.00 | 10002.31 | 0.00 | 0.00 | 0.00 | 0.00 | 125.31 | 651.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3441.23 | 0.00 | -473.08 | -6865.28 |
PERIMETER_MID_ZN_3 | 01-JAN-15:22 | 0.00 | 0.00 | 137567.29 | 0.00 | 0.00 | 0.00 | 896.59 | 700.70 | 7587.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -21644.56 | 0.00 | -27955.20 | -97152.55 |
PERIMETER_MID_ZN_2 | 02-JAN-00:02 | 0.00 | 0.00 | 166334.29 | 0.00 | 0.00 | 0.00 | 0.00 | 626.56 | 6519.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -27679.96 | 0.00 | -28512.61 | -117288.04 |
PERIMETER_MID_ZN_1 | 02-JAN-00:02 | 0.00 | 0.00 | 188171.50 | 0.00 | 0.00 | 0.00 | 0.00 | 972.28 | 10117.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -41959.12 | 0.00 | -42558.63 | -114743.15 |
PERIMETER_MID_ZN_4 | 02-JAN-00:02 | 0.00 | 0.00 | 172071.61 | 0.00 | 0.00 | 0.00 | 0.00 | 626.56 | 6519.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -28809.19 | 0.00 | -28684.12 | -121724.59 |
PERIMETER_TOP_ZN_3 | 06-FEB-01:01 | 0.00 | 0.00 | 16610.41 | 0.00 | 0.00 | 0.00 | 0.00 | 97.23 | 1011.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4621.32 | 0.00 | -6142.66 | -6955.35 |
PERIMETER_TOP_ZN_2 | 06-FEB-01:01 | 0.00 | 0.00 | 17555.94 | 0.00 | 0.00 | 0.00 | 0.00 | 62.66 | 651.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2998.11 | 0.00 | -4172.41 | -11100.05 |
PERIMETER_TOP_ZN_1 | 06-FEB-01:01 | 0.00 | 0.00 | 21268.20 | 0.00 | 0.00 | 0.00 | 0.00 | 97.23 | 1011.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4560.40 | 0.00 | -6266.25 | -11550.50 |
PERIMETER_TOP_ZN_4 | 06-FEB-01:01 | 0.00 | 0.00 | 19040.03 | 0.00 | 0.00 | 0.00 | 0.00 | 62.66 | 651.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3156.65 | 0.00 | -4226.37 | -12371.63 |
DATACENTER_BOT_ZN_6 | 01-JAN-09:58 | 0.00 | 0.00 | 436.15 | 0.00 | 0.00 | 0.00 | 5.26 | 22.51 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2412.52 |
DATACENTER_MID_ZN_6 | 16-JAN-18:00 | 0.00 | 0.00 | 5495.90 | 0.00 | 0.00 | 0.00 | 55.93 | 225.07 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -25262.96 |
DATACENTER_TOP_ZN_6 | 29-JAN-17:50 | 0.00 | 0.00 | 578.08 | 0.00 | 0.00 | 0.00 | 5.66 | 22.51 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2554.85 |
DATACENTER_BASEMENT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 11-DEC-05:01 | 14494.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1339.67 | -13154.85 |
MIDFLOOR_PLENUM | 02-JAN-06:12 | 192323.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -6441.41 | -185882.02 |
TOPFLOOR_PLENUM | 06-FEB-05:10 | 29364.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -7816.39 | -21548.07 |
Total Facility | 02-JAN-05:21 | 47251.24 | 100189.22 | 1350970.60 | -100189.22 | 0.00 | 0.00 | 0.00 | 29009.37 | 268362.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -183997.50 | 0.00 | -94662.55 | -1416933.85 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:39
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 10.1564 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 9.2478 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 96.2860 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 86.3930 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 10.1238 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 9.3232 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 5.2801 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 5.2801 | 0.2273 | 1.0000 | Not calculated | 1.2002 | 0.2273 | ||
AIRLOOP DATACENTER BASEMENT | 21.2997 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 21.2999 | 0.0159 | 1.0000 | Not calculated | 0.3384 | 0.0159 | ||
AIRLOOP DATACENTER BOT | 0.4723 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4723 | 0.0331 | 1.0000 | Not calculated | 0.0156 | 0.0331 | ||
AIRLOOP DATACENTER MID | 4.5064 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.5064 | 0.0347 | 1.0000 | Not calculated | 0.1563 | 0.0347 | ||
AIRLOOP DATACENTER TOP | 0.4593 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4593 | 0.0340 | 1.0000 | Not calculated | 0.0156 | 0.0340 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 5.0782 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.8695 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 48.1430 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 28.0183 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 5.0619 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.9002 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 5.2801 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 5.2801 | 1.0000 | 1.0000 | Not calculated | 1.2002 | 0.2273 | ||
AIRLOOP DATACENTER BASEMENT | 21.2997 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 21.2997 | 1.0000 | 1.0000 | Not calculated | 0.3384 | 0.0159 | ||
AIRLOOP DATACENTER BOT | 0.4723 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4723 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0331 | ||
AIRLOOP DATACENTER MID | 4.5064 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.5064 | 1.0000 | 1.0000 | Not calculated | 0.1563 | 0.0347 | ||
AIRLOOP DATACENTER TOP | 0.4593 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4593 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0340 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.000000 | 149.6021 | 0.000432 | 2779.43 | 1.2002 | 1.0000 | 1.2002 | 1.000 | 1.2002 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.000000 | 19.4861 | 0.000432 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.1814 | 0.000432 | 783.68 | 0.3384 | 1.0000 | 0.3384 | 1.000 | 0.3384 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
CAV_BAS | 0.000000 | 149.60 | 0.000432 | 2779.4266 | 1.2002 | 1.2002 | 1.2002 |
AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.18 | 0.000432 | 783.6794 | 0.3384 | 0.3384 | 0.3384 |
AIRLOOP DATACENTER BOT | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AIRLOOP DATACENTER MID | 0.000000 | 19.49 | 0.000432 | 362.0274 | 0.1563 | 0.1563 | 0.1563 |
AIRLOOP DATACENTER TOP | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.2801 | 5.2801 | 5.2801 | No | 1.2002 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.6134 | 5.6134 | 1.9085 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 52.7577 | 52.7577 | 18.7290 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.3717 | 5.3717 | 1.9123 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9348 | 0.9348 | 0.2393 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0416 | 1.0416 | 0.2083 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2642 | 1.2642 | 0.2528 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3024 | 1.3024 | 0.2605 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 8.8427 | 8.8427 | 2.3522 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 10.9429 | 10.9429 | 2.1886 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 12.3200 | 12.3200 | 2.4640 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 11.4227 | 11.4227 | 2.2845 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0404 | 1.0404 | 0.2455 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1222 | 1.1222 | 0.2244 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3576 | 1.3576 | 0.2715 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2320 | 1.2320 | 0.2464 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4723 | 0.4723 | 0.4723 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.5064 | 4.5064 | 4.5064 | No | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4593 | 0.4593 | 0.4593 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 21.2997 | 21.2997 | 21.2997 | No | 0.3384 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 10.1564 | 9.2478 | 10.1564 | 2.8695 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 96.2860 | 86.3930 | 96.2860 | 28.0183 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 10.1238 | 9.3232 | 10.1238 | 2.9002 | 0.0000 | 1.0000 |
CAV_BAS | 5.2801 | 5.2801 | 5.2801 | 5.2801 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.2997 | 21.2999 | 21.2997 | 21.2997 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4723 | 0.4723 | 0.4723 | 0.4723 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.5064 | 4.5064 | 4.5064 | 4.5064 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4593 | 0.4593 | 0.4593 | 0.4593 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.2801 | 5.2801 | 5.2801 | No | 1.2002 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.8067 | 2.8067 | 1.9085 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 26.3788 | 26.3788 | 18.7290 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.6858 | 2.6858 | 1.9123 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4674 | 0.4674 | 0.2393 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5208 | 0.5208 | 0.2083 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6321 | 0.6321 | 0.2528 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6512 | 0.6512 | 0.2605 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.4214 | 4.4214 | 2.3522 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.4714 | 5.4714 | 2.1886 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.1600 | 6.1600 | 2.4640 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.7113 | 5.7113 | 2.2845 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5202 | 0.5202 | 0.2455 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5611 | 0.5611 | 0.2244 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6788 | 0.6788 | 0.2715 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6160 | 0.6160 | 0.2464 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4723 | 0.4723 | 0.4723 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.5064 | 4.5064 | 4.5064 | No | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4593 | 0.4593 | 0.4593 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 21.2997 | 21.2997 | 21.2997 | No | 0.3384 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 5.0782 | 2.8695 | 2.8695 | 2.8695 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 48.1430 | 28.0183 | 28.0183 | 28.0183 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 5.0619 | 2.9002 | 2.9002 | 2.9002 | 0.0000 | 1.0000 |
CAV_BAS | 5.2801 | 5.2801 | 5.2801 | 5.2801 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.2997 | 21.2997 | 21.2997 | 21.2997 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4723 | 0.4723 | 0.4723 | 0.4723 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.5064 | 4.5064 | 4.5064 | 4.5064 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4593 | 0.4593 | 0.4593 | 0.4593 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:39
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 113.98 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 56.00 |
Number of hours cooling loads not met | 405.67 |
Number of hours not met | 461.67 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 1121.52 | 1746492.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 3472.96 | 448279.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 2745.73 | 261074.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 449.24 | 37611.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5871.99 | 320838.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 59.77 | 3726.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 1848.78 | 113101.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 5.83 | 376.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 2283.57 | 283348.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 620.77 | 75732.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 1130.44 | 90459.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- General | 14.23 | 6185.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 48.90 | 5613.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 706.90 | 82525.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 15213.41 | 27893.64 |
Natural Gas | 0.00 | 1828.42 |
Additional | 0.00 | 0.00 |
Total | 15213.41 | 29722.06 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 59.28 |
Space Heating | 0.00 |
Space Cooling | 74.98 |
Fans (All) | 49.30 |
Service Water Heating | 0.00 |
Receptacle Equipment | 328.44 |
Miscellaneous (All) | 602.19 |
Subtotal | 602.19 |
Natural Gas [MJ/m2] | |
Space Heating | 24.21 |
Service Water Heating | 15.26 |
Miscellaneous (All) | 39.47 |
Subtotal | 39.47 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 9.24 |
Space Heating | 3.77 |
Space Cooling | 11.68 |
Fans (All) | 7.68 |
Service Water Heating | 2.38 |
Receptacle Equipment | 51.19 |
Miscellaneous | 14.06 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2393. | 8760. |
LTG_SCH_DATACENTER | 2921. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4487. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 1565. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:39
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8300.17 | 459.83 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8703.17 | 56.83 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8749.83 | 10.17 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8739.50 | 20.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8750.83 | 9.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8714.00 | 46.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8693.67 | 66.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8269.67 | 490.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8718.83 | 41.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8621.17 | 138.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8594.00 | 166.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8391.50 | 368.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8686.67 | 73.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8592.00 | 168.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8562.17 | 197.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8408.50 | 351.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 6163.33 | 2596.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 6169.17 | 2590.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 6143.50 | 2616.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 5929.17 | 2830.83 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8647.33 | 112.67 | 0.00 | 0.00 | 0.00 |
Min | 5929.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 2830.83 | 0.00 | 0.00 | 0.00 |
Average | 8176.88 | 583.12 | 0.00 | 0.00 | 0.00 |
Sum | 188068.17 | 13411.83 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 367171.67 | 1444.33 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330730.00 | 83.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330811.00 | 2.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330782.00 | 31.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 1304.00 | 964.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 1298.50 | 969.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 1295.83 | 972.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 61114.50 | 42280.50 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 367171.67 | 42280.50 | 0.00 | 0.00 | 0.00 |
Average | 78302.46 | 2032.46 | 0.00 | 0.00 | 0.00 |
Sum | 1800956.50 | 46746.50 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 7066.33 | 1693.67 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8073.67 | 686.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 7916.17 | 843.83 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 7967.33 | 792.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 7908.33 | 851.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8165.83 | 594.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 7820.00 | 940.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 7583.00 | 1177.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 7868.33 | 891.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 7848.67 | 911.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 7745.00 | 1015.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 7736.67 | 1023.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 7879.33 | 880.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 7862.50 | 897.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 7788.83 | 971.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 7783.50 | 976.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 7327.67 | 1432.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 7303.50 | 1456.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 7280.50 | 1479.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 7289.17 | 1470.83 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 7700.83 | 1059.17 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 7762.50 | 997.50 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 7278.67 | 1481.33 | 0.00 | 0.00 | 0.00 |
Min | 7066.33 | 594.17 | 0.00 | 0.00 | 0.00 |
Max | 8165.83 | 1693.67 | 0.00 | 0.00 | 0.00 |
Average | 7693.75 | 1066.25 | 0.00 | 0.00 | 0.00 |
Sum | 176956.33 | 24523.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 352929.00 | 15687.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 329643.00 | 1170.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 329588.00 | 1225.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 329564.00 | 1249.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38915.67 | 9.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18352.50 | 1.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38918.83 | 6.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24908.50 | 0.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38912.00 | 13.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24905.33 | 3.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38916.33 | 8.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24907.83 | 1.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 1464.33 | 803.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 1449.33 | 818.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 1438.33 | 829.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 72951.33 | 30443.67 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 352929.00 | 30443.67 | 0.00 | 0.00 | 0.00 |
Average | 78062.28 | 2272.64 | 0.00 | 0.00 | 0.00 |
Sum | 1795432.33 | 52270.67 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:39
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:39
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 4570.43 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 18354.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 38925.00 | 0.00 |
Average | 0.00 | 0.00 | 16367.35 | 0.00 |
Sum | 0.00 | 0.00 | 376449.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018
For: Environment
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Environment
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4A
For: Environment
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_NEWYORK
For: Environment
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.409779E+11 | 101225.76 | 30-JAN-04:01 | -4.0 | -5.6 | 0.558968E+10 | 7499.27 | 03-JAN-10:09 | -4.0 | -5.6 |
February | 0.397012E+11 | 105817.05 | 21-FEB-04:01 | 1.78 | 1.01 | 0.508141E+10 | 7499.14 | 10-FEB-14:20 | 1.78 | 1.01 |
March | 0.514482E+11 | 103836.54 | 13-MAR-03:01 | 0.50 | -3.0 | 0.612732E+10 | 7499.11 | 27-MAR-09:20 | 11.30 | 11.30 |
April | 0.499466E+11 | 103422.61 | 03-APR-03:01 | 3.22 | 0.25 | 0.544579E+10 | 7499.15 | 07-APR-13:00 | 26.10 | 15.95 |
May | 0.528820E+11 | 103833.81 | 01-MAY-03:02 | 7.45 | 5.14 | 0.589880E+10 | 7499.51 | 25-MAY-09:20 | 16.87 | 13.21 |
June | 0.563452E+11 | 93773.98 | 05-JUN-03:03 | 15.82 | 12.11 | 0.588058E+10 | 7499.24 | 23-JUN-09:00 | 30.00 | 18.39 |
July | 0.572756E+11 | 87613.43 | 11-JUL-03:02 | 20.50 | 15.26 | 0.547276E+10 | 7499.16 | 12-JUL-09:30 | 27.50 | 18.52 |
August | 0.649929E+11 | 89401.06 | 29-AUG-03:02 | 17.12 | 14.13 | 0.613793E+10 | 7499.16 | 09-AUG-09:20 | 17.12 | 14.13 |
September | 0.579250E+11 | 102079.14 | 25-SEP-03:02 | 13.98 | 11.61 | 0.545215E+10 | 7499.25 | 19-SEP-09:20 | 13.98 | 11.61 |
October | 0.604891E+11 | 105803.27 | 16-OCT-03:02 | 8.80 | 7.97 | 0.567087E+10 | 7499.49 | 16-OCT-09:20 | 17.07 | 14.18 |
November | 0.547603E+11 | 105334.30 | 06-NOV-04:03 | 5.00 | 2.82 | 0.561200E+10 | 7499.12 | 09-NOV-14:00 | 13.90 | 12.65 |
December | 0.508665E+11 | 108548.94 | 26-DEC-04:01 | 5.60 | 4.99 | 0.546593E+10 | 7499.08 | 15-DEC-10:09 | 5.60 | 4.99 |
Annual Sum or Average | 0.637610E+12 | 0.678352E+11 | ||||||||
Minimum of Months | 0.397012E+11 | 87613.43 | -4.0 | -5.6 | 0.508141E+10 | 7499.08 | -4.0 | -5.6 | ||
Maximum of Months | 0.649929E+11 | 108548.94 | 20.50 | 15.26 | 0.613793E+10 | 7499.51 | 30.00 | 18.52 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.310825E+11 | 79541.05 | 30-JAN-06:02 | -5.0 | -6.1 | 0.499414E+10 | 6734.75 | 17-JAN-10:20 | -5.0 | -6.1 |
February | 0.314778E+11 | 83923.28 | 21-FEB-05:02 | 2.20 | 1.30 | 0.457221E+10 | 6745.22 | 10-FEB-14:39 | 2.20 | 1.30 |
March | 0.461847E+11 | 84360.62 | 30-MAR-04:02 | 2.20 | 0.99 | 0.549470E+10 | 6747.95 | 13-MAR-09:30 | 2.20 | 0.99 |
April | 0.512925E+11 | 85862.75 | 11-APR-03:02 | 6.60 | 1.81 | 0.488095E+10 | 6734.85 | 26-APR-09:00 | 16.10 | 12.59 |
May | 0.513144E+11 | 87495.28 | 01-MAY-03:02 | 7.45 | 5.14 | 0.528460E+10 | 6842.05 | 30-MAY-13:00 | 29.40 | 16.93 |
June | 0.600587E+11 | 89540.86 | 12-JUN-03:02 | 18.90 | 17.52 | 0.526929E+10 | 6784.86 | 22-JUN-13:20 | 28.87 | 17.36 |
July | 0.675754E+11 | 84373.02 | 01-JUL-03:02 | 20.00 | 19.65 | 0.489208E+10 | 6757.03 | 11-JUL-13:39 | 28.53 | 17.90 |
August | 0.756830E+11 | 84093.86 | 07-AUG-05:04 | 19.40 | 16.74 | 0.549321E+10 | 6736.28 | 25-AUG-13:00 | 26.70 | 15.26 |
September | 0.525194E+11 | 91267.60 | 18-SEP-03:02 | 16.70 | 15.98 | 0.488280E+10 | 6735.66 | 01-SEP-13:00 | 16.70 | 15.98 |
October | 0.524039E+11 | 90327.57 | 23-OCT-03:02 | 14.13 | 11.49 | 0.507871E+10 | 6735.13 | 16-OCT-09:09 | 14.13 | 11.49 |
November | 0.437779E+11 | 91713.54 | 13-NOV-04:02 | 5.60 | 4.34 | 0.503060E+10 | 6746.44 | 22-NOV-14:50 | 1.28 | -2.5 |
December | 0.422548E+11 | 85475.15 | 26-DEC-04:01 | 5.60 | 4.99 | 0.489414E+10 | 6745.39 | 12-DEC-10:20 | 5.60 | 4.99 |
Annual Sum or Average | 0.605625E+12 | 0.607674E+11 | ||||||||
Minimum of Months | 0.310825E+11 | 79541.05 | -5.0 | -6.1 | 0.457221E+10 | 6734.75 | -5.0 | -6.1 | ||
Maximum of Months | 0.756830E+11 | 91713.54 | 20.00 | 19.65 | 0.549470E+10 | 6842.05 | 29.40 | 17.90 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.217881E+11 | 21262.51 | 31-JAN-09:40 | -7.1 | -9.7 | 0.435980E+10 | 6703.15 | 27-JAN-14:00 | -7.1 | -9.7 |
February | 0.218105E+11 | 25464.82 | 04-FEB-17:08 | 0.10 | -1.4 | 0.409389E+10 | 6734.48 | 03-FEB-14:00 | 0.10 | -1.4 |
March | 0.288536E+11 | 70076.28 | 30-MAR-05:02 | 2.20 | 0.86 | 0.530787E+10 | 6784.93 | 16-MAR-13:39 | 2.20 | 0.86 |
April | 0.317254E+11 | 77420.71 | 08-APR-05:02 | 14.32 | 11.97 | 0.480874E+10 | 6734.76 | 26-APR-09:00 | 16.10 | 12.59 |
May | 0.415773E+11 | 77442.54 | 20-MAY-05:02 | 13.30 | 11.39 | 0.526391E+10 | 6735.00 | 25-MAY-09:09 | 16.78 | 13.45 |
June | 0.474372E+11 | 81975.11 | 12-JUN-03:02 | 18.90 | 17.52 | 0.526540E+10 | 6757.97 | 20-JUN-13:39 | 27.03 | 17.79 |
July | 0.491834E+11 | 79698.32 | 12-JUL-03:02 | 21.70 | 19.09 | 0.489154E+10 | 6734.84 | 11-JUL-13:00 | 21.70 | 19.09 |
August | 0.523991E+11 | 86286.94 | 07-AUG-03:02 | 18.80 | 17.42 | 0.549615E+10 | 6740.84 | 25-AUG-13:00 | 26.70 | 15.26 |
September | 0.431044E+11 | 80536.55 | 18-SEP-03:02 | 16.70 | 15.98 | 0.487139E+10 | 6734.94 | 19-SEP-09:09 | 18.58 | 14.06 |
October | 0.381759E+11 | 77929.20 | 05-OCT-04:03 | 15.60 | 14.25 | 0.504799E+10 | 6735.05 | 16-OCT-09:09 | 16.88 | 14.11 |
November | 0.269673E+11 | 73403.98 | 03-NOV-05:02 | 9.22 | 6.42 | 0.483187E+10 | 6742.63 | 15-NOV-10:00 | 7.20 | 4.04 |
December | 0.243551E+11 | 24633.11 | 21-DEC-17:00 | 1.70 | -2.8 | 0.454682E+10 | 6734.52 | 22-DEC-14:00 | 1.70 | -2.0 |
Annual Sum or Average | 0.427377E+12 | 0.587854E+11 | ||||||||
Minimum of Months | 0.217881E+11 | 21262.51 | -7.1 | -9.7 | 0.409389E+10 | 6703.15 | -7.1 | -9.7 | ||
Maximum of Months | 0.523991E+11 | 86286.94 | 21.70 | 19.09 | 0.549615E+10 | 6784.93 | 27.03 | 19.09 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.164177E+11 | 18386.66 | 20-JAN-17:00 | 5.60 | 3.19 | 0.401910E+10 | 6244.49 | 19-JAN-14:00 | 5.60 | 3.19 |
February | 0.156704E+11 | 18461.24 | 24-FEB-17:00 | 6.70 | 1.42 | 0.368101E+10 | 6285.95 | 17-FEB-14:00 | 6.70 | 1.42 |
March | 0.239484E+11 | 29245.72 | 03-MAR-17:00 | 14.00 | 7.84 | 0.481858E+10 | 6734.53 | 29-MAR-13:00 | 7.80 | 5.51 |
April | 0.276354E+11 | 75034.63 | 08-APR-05:02 | 14.32 | 11.97 | 0.458616E+10 | 6734.72 | 07-APR-13:09 | 14.32 | 11.97 |
May | 0.394743E+11 | 81840.28 | 30-MAY-03:02 | 18.22 | 15.08 | 0.520600E+10 | 6823.86 | 30-MAY-13:00 | 29.40 | 16.93 |
June | 0.497909E+11 | 84215.32 | 12-JUN-03:02 | 18.90 | 17.52 | 0.526299E+10 | 6890.82 | 22-JUN-13:30 | 29.15 | 17.46 |
July | 0.539085E+11 | 84498.08 | 24-JUL-03:02 | 22.02 | 21.19 | 0.489657E+10 | 6842.75 | 11-JUL-13:50 | 22.02 | 21.19 |
August | 0.564296E+11 | 88980.59 | 07-AUG-03:02 | 18.80 | 17.42 | 0.549670E+10 | 6734.78 | 23-AUG-13:09 | 25.60 | 17.07 |
September | 0.417954E+11 | 81556.61 | 05-SEP-03:02 | 20.50 | 17.81 | 0.485010E+10 | 6734.90 | 19-SEP-09:09 | 18.58 | 14.06 |
October | 0.324523E+11 | 78239.46 | 06-OCT-05:02 | 19.40 | 18.22 | 0.491152E+10 | 6734.99 | 16-OCT-09:09 | 16.88 | 14.11 |
November | 0.206854E+11 | 29554.38 | 03-NOV-16:00 | 15.00 | 10.26 | 0.435474E+10 | 6734.73 | 09-NOV-14:00 | 13.90 | 12.65 |
December | 0.176372E+11 | 18152.88 | 20-DEC-17:00 | 6.70 | 3.52 | 0.397032E+10 | 6272.40 | 20-DEC-14:00 | 6.70 | 3.52 |
Annual Sum or Average | 0.395846E+12 | 0.560538E+11 | ||||||||
Minimum of Months | 0.156704E+11 | 18152.88 | 5.60 | 1.42 | 0.368101E+10 | 6244.49 | 5.60 | 1.42 | ||
Maximum of Months | 0.564296E+11 | 88980.59 | 22.02 | 21.19 | 0.549670E+10 | 6890.82 | 29.40 | 21.19 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.189118E+10 | 2594.39 | 24-JAN-06:03 | 11.10 | 11.10 | 0.514476E+09 | 789.99 | 20-JAN-14:00 | 11.10 | 11.10 |
February | 0.188585E+10 | 2661.02 | 21-FEB-05:02 | 2.20 | 1.30 | 0.472964E+09 | 805.17 | 24-FEB-14:30 | 8.85 | 2.78 |
March | 0.353645E+10 | 5368.29 | 27-MAR-13:30 | 20.85 | 16.76 | 0.642061E+09 | 845.62 | 06-MAR-14:20 | 20.85 | 16.76 |
April | 0.498773E+10 | 6755.29 | 07-APR-13:40 | 26.30 | 16.10 | 0.598691E+09 | 845.64 | 26-APR-09:00 | 16.10 | 12.59 |
May | 0.652347E+10 | 12709.70 | 30-MAY-05:03 | 18.17 | 14.31 | 0.660711E+09 | 871.97 | 30-MAY-13:00 | 29.40 | 16.93 |
June | 0.961510E+10 | 12222.83 | 12-JUN-05:03 | 18.40 | 17.59 | 0.661996E+09 | 863.69 | 22-JUN-13:20 | 28.87 | 17.36 |
July | 0.115587E+11 | 15480.16 | 04-JUL-16:01 | 25.92 | 18.02 | 0.615673E+09 | 860.22 | 11-JUL-13:39 | 28.53 | 17.90 |
August | 0.122821E+11 | 15993.37 | 13-AUG-16:21 | 29.70 | 20.61 | 0.690411E+09 | 846.03 | 25-AUG-13:00 | 26.70 | 15.26 |
September | 0.691302E+10 | 11727.90 | 02-SEP-05:03 | 22.12 | 16.30 | 0.611309E+09 | 845.87 | 01-SEP-13:00 | 22.12 | 16.30 |
October | 0.535183E+10 | 10056.65 | 23-OCT-05:03 | 13.22 | 10.95 | 0.629102E+09 | 845.66 | 16-OCT-09:09 | 13.22 | 10.95 |
November | 0.324965E+10 | 4446.36 | 03-NOV-13:50 | 17.70 | 10.66 | 0.593256E+09 | 845.64 | 09-NOV-14:00 | 13.90 | 12.65 |
December | 0.282807E+10 | 2849.64 | 05-DEC-05:01 | 6.10 | 4.77 | 0.542546E+09 | 845.60 | 26-DEC-14:09 | 8.80 | 4.42 |
Annual Sum or Average | 0.706232E+11 | 0.723320E+10 | ||||||||
Minimum of Months | 0.188585E+10 | 2594.39 | 2.20 | 1.30 | 0.472964E+09 | 789.99 | 8.80 | 2.78 | ||
Maximum of Months | 0.122821E+11 | 15993.37 | 29.70 | 20.61 | 0.690411E+09 | 871.97 | 29.40 | 17.90 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.162241E+10 | 3010.30 | 19-JAN-09:25 | 6.10 | 3.63 | 0.335425E+09 | 544.94 | 26-JAN-10:09 | 2.38 | -1.0 |
February | 0.169872E+10 | 3977.52 | 22-FEB-09:30 | 0.30 | -3.3 | 0.312039E+09 | 544.95 | 22-FEB-10:39 | 1.67 | -2.5 |
March | 0.330786E+10 | 7167.92 | 29-MAR-08:40 | 5.20 | 2.69 | 0.414074E+09 | 546.34 | 13-MAR-09:30 | 5.20 | 2.69 |
April | 0.456074E+10 | 10541.44 | 23-APR-08:33 | 11.33 | 7.60 | 0.381131E+09 | 544.97 | 26-APR-09:50 | 16.38 | 12.56 |
May | 0.613620E+10 | 18182.90 | 29-MAY-08:22 | 25.00 | 16.74 | 0.424694E+09 | 557.77 | 30-MAY-13:00 | 29.40 | 16.93 |
June | 0.766083E+10 | 17846.79 | 04-JUN-08:13 | 22.57 | 12.59 | 0.426299E+09 | 553.39 | 22-JUN-09:30 | 25.85 | 16.85 |
July | 0.901686E+10 | 18147.23 | 02-JUL-08:32 | 25.20 | 21.54 | 0.396626E+09 | 547.67 | 12-JUL-09:39 | 27.60 | 18.47 |
August | 0.101411E+11 | 17440.45 | 13-AUG-09:02 | 27.98 | 19.16 | 0.444670E+09 | 546.19 | 22-AUG-09:00 | 28.30 | 18.37 |
September | 0.612347E+10 | 18180.11 | 04-SEP-07:23 | 21.70 | 18.19 | 0.393690E+09 | 545.63 | 06-SEP-09:20 | 25.97 | 19.25 |
October | 0.491683E+10 | 8599.91 | 03-OCT-08:40 | 18.33 | 16.58 | 0.405231E+09 | 544.99 | 16-OCT-09:09 | 16.88 | 14.11 |
November | 0.271420E+10 | 5145.63 | 02-NOV-08:50 | 10.82 | 5.71 | 0.378174E+09 | 544.96 | 09-NOV-14:00 | 13.90 | 12.65 |
December | 0.220793E+10 | 3674.70 | 20-DEC-09:25 | 7.20 | 4.58 | 0.341702E+09 | 544.94 | 18-DEC-10:09 | 7.20 | 4.58 |
Annual Sum or Average | 0.601071E+11 | 0.465376E+10 | ||||||||
Minimum of Months | 0.162241E+10 | 3010.30 | 0.30 | -3.3 | 0.312039E+09 | 544.94 | 1.67 | -2.5 | ||
Maximum of Months | 0.101411E+11 | 18182.90 | 27.98 | 21.54 | 0.444670E+09 | 557.77 | 29.40 | 19.25 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.315944E+10 | 10789.31 | 19-JAN-13:30 | 9.40 | 3.94 | 0.553934E+09 | 845.64 | 31-JAN-10:20 | -6.3 | -9.2 |
February | 0.353431E+10 | 11529.95 | 22-FEB-13:20 | 4.27 | -1.2 | 0.519179E+09 | 847.55 | 10-FEB-14:39 | 4.27 | -1.2 |
March | 0.627041E+10 | 14175.04 | 03-MAR-13:15 | 14.60 | 8.23 | 0.651885E+09 | 846.37 | 03-MAR-14:20 | 15.00 | 8.55 |
April | 0.695393E+10 | 16859.92 | 09-APR-13:43 | 19.40 | 15.43 | 0.594470E+09 | 852.92 | 07-APR-13:50 | 19.40 | 15.43 |
May | 0.774040E+10 | 21619.03 | 29-MAY-13:43 | 26.28 | 17.36 | 0.658717E+09 | 897.71 | 30-MAY-13:00 | 29.40 | 16.93 |
June | 0.106235E+11 | 15566.95 | 26-JUN-05:02 | 20.78 | 17.10 | 0.662075E+09 | 869.37 | 22-JUN-13:20 | 20.78 | 17.10 |
July | 0.131112E+11 | 22034.40 | 04-JUL-14:02 | 27.70 | 18.45 | 0.616086E+09 | 870.83 | 11-JUL-13:39 | 28.53 | 17.90 |
August | 0.162768E+11 | 23327.09 | 13-AUG-13:02 | 31.20 | 19.67 | 0.691299E+09 | 857.06 | 30-AUG-13:50 | 28.62 | 15.51 |
September | 0.110590E+11 | 22460.27 | 10-SEP-11:02 | 22.30 | 13.72 | 0.612943E+09 | 874.37 | 01-SEP-13:00 | 22.30 | 13.72 |
October | 0.109664E+11 | 22342.11 | 15-OCT-13:32 | 20.93 | 13.28 | 0.634191E+09 | 859.02 | 04-OCT-13:20 | 20.93 | 13.28 |
November | 0.556914E+10 | 16291.15 | 02-NOV-12:40 | 15.40 | 8.14 | 0.605812E+09 | 846.84 | 22-NOV-14:50 | 1.28 | -2.5 |
December | 0.442962E+10 | 17957.59 | 17-DEC-12:33 | 12.20 | 4.80 | 0.564009E+09 | 845.64 | 19-DEC-10:20 | 6.67 | 3.33 |
Annual Sum or Average | 0.996940E+11 | 0.736460E+10 | ||||||||
Minimum of Months | 0.315944E+10 | 10789.31 | 4.27 | -1.2 | 0.519179E+09 | 845.64 | -6.3 | -9.2 | ||
Maximum of Months | 0.162768E+11 | 23327.09 | 31.20 | 19.67 | 0.691299E+09 | 897.71 | 29.40 | 17.90 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.266098E+10 | 5367.07 | 20-JAN-15:40 | 7.40 | 3.86 | 0.348339E+09 | 544.94 | 20-JAN-14:00 | 7.40 | 3.86 |
February | 0.304200E+10 | 7665.10 | 24-FEB-15:30 | 8.05 | 2.04 | 0.332723E+09 | 546.08 | 10-FEB-14:39 | 8.05 | 2.04 |
March | 0.601064E+10 | 11632.18 | 27-MAR-16:00 | 22.20 | 16.34 | 0.438296E+09 | 544.96 | 27-MAR-09:09 | 22.20 | 16.34 |
April | 0.835523E+10 | 22755.94 | 09-APR-16:22 | 16.65 | 13.97 | 0.395102E+09 | 544.97 | 26-APR-09:50 | 16.38 | 12.56 |
May | 0.782065E+10 | 18788.75 | 29-MAY-14:23 | 25.85 | 17.23 | 0.427370E+09 | 562.74 | 30-MAY-13:00 | 29.40 | 16.93 |
June | 0.114669E+11 | 22960.94 | 18-JUN-16:02 | 25.50 | 22.07 | 0.427751E+09 | 550.93 | 22-JUN-13:20 | 28.87 | 17.36 |
July | 0.139399E+11 | 25612.86 | 04-JUL-16:01 | 25.92 | 18.02 | 0.397995E+09 | 547.31 | 11-JUL-13:00 | 28.90 | 17.83 |
August | 0.168864E+11 | 25797.33 | 13-AUG-16:21 | 29.70 | 20.61 | 0.446417E+09 | 546.51 | 22-AUG-15:09 | 29.90 | 17.46 |
September | 0.813367E+10 | 22066.26 | 10-SEP-15:42 | 23.48 | 13.06 | 0.395316E+09 | 545.56 | 01-SEP-13:00 | 23.48 | 13.06 |
October | 0.760819E+10 | 14656.52 | 23-OCT-05:03 | 13.22 | 10.95 | 0.410167E+09 | 544.99 | 16-OCT-09:09 | 13.22 | 10.95 |
November | 0.468072E+10 | 10871.66 | 09-NOV-06:03 | 9.50 | 9.14 | 0.400383E+09 | 545.98 | 22-NOV-14:50 | 1.28 | -2.5 |
December | 0.432093E+10 | 7507.82 | 18-DEC-15:30 | 5.85 | 2.55 | 0.388010E+09 | 544.95 | 29-DEC-14:00 | 3.90 | 3.16 |
Annual Sum or Average | 0.949262E+11 | 0.480787E+10 | ||||||||
Minimum of Months | 0.266098E+10 | 5367.07 | 5.85 | 2.04 | 0.332723E+09 | 544.94 | 1.28 | -2.5 | ||
Maximum of Months | 0.168864E+11 | 25797.33 | 29.70 | 22.07 | 0.446417E+09 | 562.74 | 29.90 | 17.83 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.324336E+09 | 1830.36 | 20-JAN-17:00 | 5.60 | 3.19 | 0.465378E+09 | 653.21 | 20-JAN-14:00 | 5.60 | 3.19 |
February | 0.346390E+09 | 2714.43 | 04-FEB-17:08 | 0.10 | -1.4 | 0.424173E+09 | 675.20 | 24-FEB-14:00 | 8.30 | 2.27 |
March | 0.162726E+10 | 2369.75 | 27-MAR-16:00 | 22.20 | 16.34 | 0.542520E+09 | 828.92 | 28-MAR-13:00 | 13.30 | 8.41 |
April | 0.272649E+10 | 4963.59 | 07-APR-15:20 | 25.60 | 16.01 | 0.542142E+09 | 845.63 | 06-APR-13:09 | 25.60 | 16.01 |
May | 0.503564E+10 | 10386.10 | 30-MAY-05:03 | 18.17 | 14.31 | 0.647796E+09 | 849.14 | 30-MAY-13:00 | 29.40 | 16.93 |
June | 0.778453E+10 | 11376.34 | 20-JUN-05:02 | 20.78 | 18.13 | 0.661064E+09 | 854.78 | 20-JUN-13:39 | 27.03 | 17.79 |
July | 0.911152E+10 | 13815.51 | 10-JUL-03:02 | 26.10 | 21.76 | 0.615819E+09 | 850.86 | 11-JUL-13:30 | 28.35 | 17.93 |
August | 0.908523E+10 | 12318.14 | 18-AUG-03:02 | 25.50 | 18.51 | 0.690561E+09 | 846.81 | 25-AUG-13:00 | 26.70 | 15.26 |
September | 0.556707E+10 | 10780.97 | 22-SEP-05:03 | 21.70 | 20.52 | 0.605310E+09 | 845.64 | 19-SEP-09:09 | 21.70 | 20.52 |
October | 0.363199E+10 | 5448.73 | 05-OCT-14:00 | 23.30 | 18.86 | 0.597515E+09 | 845.61 | 16-OCT-13:50 | 19.32 | 16.19 |
November | 0.153308E+10 | 2789.43 | 02-NOV-13:20 | 15.77 | 8.37 | 0.502427E+09 | 826.96 | 03-NOV-13:00 | 17.80 | 10.67 |
December | 0.505162E+09 | 1765.47 | 20-DEC-13:40 | 9.80 | 5.81 | 0.451298E+09 | 676.46 | 20-DEC-14:20 | 9.43 | 5.62 |
Annual Sum or Average | 0.472787E+11 | 0.674600E+10 | ||||||||
Minimum of Months | 0.324336E+09 | 1765.47 | 0.10 | -1.4 | 0.424173E+09 | 653.21 | 5.60 | 2.27 | ||
Maximum of Months | 0.911152E+10 | 13815.51 | 26.10 | 21.76 | 0.690561E+09 | 854.78 | 29.40 | 20.52 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.404024E+09 | 2138.81 | 26-JAN-09:25 | 1.40 | -1.6 | 0.221802E+09 | 461.50 | 27-JAN-09:00 | 4.40 | 1.46 |
February | 0.582284E+09 | 2472.69 | 04-FEB-17:08 | 0.10 | -1.4 | 0.203673E+09 | 483.11 | 17-FEB-09:50 | 4.13 | 0.27 |
March | 0.198095E+10 | 5920.93 | 29-MAR-09:00 | 5.60 | 2.98 | 0.271671E+09 | 522.52 | 07-MAR-09:20 | 5.60 | 2.98 |
April | 0.321635E+10 | 9091.63 | 28-APR-08:50 | 15.82 | 8.80 | 0.265384E+09 | 521.23 | 06-APR-12:09 | 15.82 | 8.80 |
May | 0.557290E+10 | 20770.25 | 29-MAY-08:42 | 25.73 | 16.73 | 0.305599E+09 | 537.76 | 30-MAY-10:50 | 28.72 | 17.34 |
June | 0.703955E+10 | 18718.30 | 04-JUN-08:23 | 22.75 | 12.67 | 0.312732E+09 | 526.43 | 26-JUN-07:19 | 23.50 | 18.22 |
July | 0.815524E+10 | 21292.56 | 02-JUL-09:01 | 25.68 | 21.69 | 0.292910E+09 | 535.76 | 11-JUL-14:30 | 28.60 | 17.71 |
August | 0.908529E+10 | 18935.18 | 27-AUG-09:53 | 26.10 | 21.81 | 0.327308E+09 | 529.92 | 22-AUG-15:39 | 26.10 | 21.81 |
September | 0.561062E+10 | 20532.56 | 04-SEP-09:12 | 24.47 | 18.42 | 0.286664E+09 | 521.42 | 06-SEP-08:00 | 25.60 | 19.05 |
October | 0.398374E+10 | 8046.64 | 05-OCT-09:00 | 18.90 | 16.77 | 0.288925E+09 | 521.22 | 16-OCT-08:00 | 16.70 | 14.03 |
November | 0.159094E+10 | 3189.85 | 03-NOV-09:00 | 12.80 | 8.09 | 0.242307E+09 | 521.19 | 03-NOV-10:09 | 13.58 | 8.52 |
December | 0.705637E+09 | 2048.78 | 21-DEC-09:15 | 0.20 | -2.8 | 0.216404E+09 | 483.98 | 20-DEC-09:00 | 0.20 | -2.8 |
Annual Sum or Average | 0.479275E+11 | 0.323538E+10 | ||||||||
Minimum of Months | 0.404024E+09 | 2048.78 | 0.10 | -2.8 | 0.203673E+09 | 461.50 | 0.20 | -2.8 | ||
Maximum of Months | 0.908529E+10 | 21292.56 | 26.10 | 21.81 | 0.327308E+09 | 537.76 | 28.72 | 21.81 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.194156E+10 | 9636.76 | 19-JAN-13:40 | 9.40 | 3.86 | 0.521895E+09 | 845.65 | 05-JAN-14:09 | 9.40 | 3.86 |
February | 0.246599E+10 | 11131.70 | 22-FEB-13:40 | 4.63 | -1.0 | 0.487109E+09 | 858.87 | 09-FEB-14:39 | 4.63 | -1.0 |
March | 0.471666E+10 | 13487.33 | 01-MAR-13:30 | 13.90 | 6.36 | 0.615067E+09 | 852.28 | 07-MAR-10:09 | 7.80 | 3.53 |
April | 0.499425E+10 | 13860.82 | 07-APR-12:40 | 26.33 | 16.06 | 0.569410E+09 | 867.51 | 07-APR-13:50 | 26.20 | 16.03 |
May | 0.666975E+10 | 21438.89 | 29-MAY-12:43 | 27.48 | 17.22 | 0.649787E+09 | 878.92 | 30-MAY-13:00 | 29.40 | 16.93 |
June | 0.898030E+10 | 14925.82 | 08-JUN-05:02 | 19.08 | 17.42 | 0.661115E+09 | 855.92 | 20-JUN-13:39 | 27.03 | 17.79 |
July | 0.107542E+11 | 21969.56 | 30-JUL-13:32 | 27.20 | 24.02 | 0.616344E+09 | 864.59 | 11-JUL-13:30 | 27.20 | 24.02 |
August | 0.134403E+11 | 21882.55 | 20-AUG-12:32 | 27.43 | 15.69 | 0.692040E+09 | 886.24 | 30-AUG-13:00 | 28.90 | 15.47 |
September | 0.103783E+11 | 23745.40 | 04-SEP-11:52 | 26.10 | 17.79 | 0.611021E+09 | 898.95 | 01-SEP-13:00 | 26.10 | 17.79 |
October | 0.992465E+10 | 21877.50 | 15-OCT-14:32 | 20.77 | 13.06 | 0.628294E+09 | 884.28 | 04-OCT-13:30 | 20.77 | 13.06 |
November | 0.416910E+10 | 16594.06 | 02-NOV-13:10 | 15.68 | 8.29 | 0.574106E+09 | 864.15 | 21-NOV-10:00 | 2.20 | 0.17 |
December | 0.261032E+10 | 13902.34 | 15-DEC-12:00 | 2.20 | -1.3 | 0.523958E+09 | 845.66 | 15-DEC-14:09 | 3.98 | 0.25 |
Annual Sum or Average | 0.810454E+11 | 0.715014E+10 | ||||||||
Minimum of Months | 0.194156E+10 | 9636.76 | 2.20 | -1.3 | 0.487109E+09 | 845.65 | 2.20 | -1.0 | ||
Maximum of Months | 0.134403E+11 | 23745.40 | 27.48 | 24.02 | 0.692040E+09 | 898.95 | 29.40 | 24.02 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.643836E+09 | 2393.09 | 20-JAN-16:10 | 6.93 | 3.71 | 0.307105E+09 | 506.41 | 20-JAN-16:10 | 6.93 | 3.71 |
February | 0.792390E+09 | 3448.09 | 22-FEB-16:30 | 3.85 | -0.7 | 0.283411E+09 | 530.24 | 17-FEB-14:00 | 3.85 | -0.7 |
March | 0.252490E+10 | 7749.30 | 29-MAR-16:00 | 7.20 | 4.88 | 0.367607E+09 | 544.94 | 01-MAR-14:00 | 7.20 | 4.88 |
April | 0.370132E+10 | 12552.96 | 09-APR-16:33 | 16.47 | 13.91 | 0.356030E+09 | 544.96 | 10-APR-13:09 | 20.10 | 10.10 |
May | 0.565331E+10 | 15095.03 | 28-MAY-16:03 | 23.43 | 15.49 | 0.415407E+09 | 544.99 | 15-MAY-13:50 | 23.43 | 15.49 |
June | 0.795402E+10 | 20273.71 | 04-JUN-16:22 | 21.65 | 14.55 | 0.426357E+09 | 556.59 | 01-JUN-15:50 | 21.65 | 14.55 |
July | 0.884985E+10 | 20989.66 | 02-JUL-16:21 | 24.70 | 20.69 | 0.397425E+09 | 549.15 | 11-JUL-15:20 | 28.30 | 17.46 |
August | 0.996072E+10 | 20254.30 | 13-AUG-15:52 | 30.00 | 20.46 | 0.445907E+09 | 557.06 | 22-AUG-15:39 | 29.60 | 17.26 |
September | 0.597092E+10 | 21157.38 | 10-SEP-16:02 | 23.22 | 12.85 | 0.389733E+09 | 544.97 | 11-SEP-13:09 | 20.60 | 12.01 |
October | 0.452646E+10 | 10492.44 | 04-OCT-15:30 | 23.35 | 19.12 | 0.388649E+09 | 544.95 | 13-OCT-13:39 | 21.70 | 17.54 |
November | 0.175100E+10 | 5405.39 | 03-NOV-15:30 | 16.10 | 10.65 | 0.329730E+09 | 544.95 | 08-NOV-14:00 | 13.30 | 11.09 |
December | 0.913012E+09 | 2256.62 | 08-DEC-15:40 | 6.30 | 2.04 | 0.299674E+09 | 508.14 | 21-DEC-14:00 | 3.30 | -1.8 |
Annual Sum or Average | 0.532417E+11 | 0.440703E+10 | ||||||||
Minimum of Months | 0.643836E+09 | 2256.62 | 3.85 | -0.7 | 0.283411E+09 | 506.41 | 3.30 | -1.8 | ||
Maximum of Months | 0.996072E+10 | 21157.38 | 30.00 | 20.69 | 0.445907E+09 | 557.06 | 29.60 | 17.54 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.105836E+09 | 1558.17 | 20-JAN-16:00 | 7.20 | 3.80 | 0.463159E+09 | 625.90 | 05-JAN-10:39 | 7.20 | 3.80 |
February | 0.112441E+09 | 1633.69 | 24-FEB-15:30 | 8.05 | 2.04 | 0.420241E+09 | 625.94 | 06-FEB-10:50 | 8.05 | 2.04 |
March | 0.924617E+09 | 2365.76 | 28-MAR-14:10 | 13.22 | 8.42 | 0.522317E+09 | 802.72 | 28-MAR-13:00 | 13.22 | 8.42 |
April | 0.224459E+10 | 5617.14 | 07-APR-15:20 | 25.60 | 16.01 | 0.515174E+09 | 845.63 | 07-APR-13:09 | 25.60 | 16.01 |
May | 0.482444E+10 | 11064.09 | 31-MAY-05:03 | 16.38 | 14.99 | 0.629155E+09 | 857.12 | 30-MAY-13:00 | 16.38 | 14.99 |
June | 0.808143E+10 | 13587.36 | 26-JUN-05:02 | 20.78 | 17.10 | 0.659800E+09 | 859.78 | 22-JUN-13:30 | 20.78 | 17.10 |
July | 0.983077E+10 | 18157.48 | 09-JUL-15:21 | 27.20 | 24.16 | 0.616011E+09 | 855.10 | 11-JUL-13:00 | 28.90 | 17.83 |
August | 0.968552E+10 | 14778.17 | 13-AUG-15:52 | 30.00 | 20.46 | 0.690044E+09 | 845.64 | 09-AUG-13:30 | 30.00 | 20.46 |
September | 0.543371E+10 | 10682.72 | 07-SEP-05:02 | 22.20 | 21.37 | 0.597117E+09 | 845.64 | 11-SEP-13:09 | 20.60 | 12.01 |
October | 0.306645E+10 | 5694.95 | 04-OCT-14:00 | 24.40 | 18.95 | 0.568189E+09 | 845.61 | 16-OCT-13:00 | 19.40 | 16.27 |
November | 0.881335E+09 | 2298.44 | 03-NOV-15:00 | 17.20 | 10.98 | 0.476317E+09 | 780.54 | 03-NOV-13:00 | 17.20 | 10.98 |
December | 72464214.08 | 1505.85 | 09-DEC-17:03 | 4.32 | 1.58 | 0.447495E+09 | 625.90 | 11-DEC-14:09 | 1.10 | -0.6 |
Annual Sum or Average | 0.452636E+11 | 0.660502E+10 | ||||||||
Minimum of Months | 72464214.08 | 1505.85 | 4.32 | 1.58 | 0.420241E+09 | 625.90 | 1.10 | -0.6 | ||
Maximum of Months | 0.983077E+10 | 18157.48 | 30.00 | 24.16 | 0.690044E+09 | 859.78 | 30.00 | 20.46 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.217583E+09 | 1701.50 | 19-JAN-10:20 | 7.80 | 4.36 | 0.299700E+09 | 442.74 | 19-JAN-10:30 | 7.80 | 4.48 |
February | 0.288266E+09 | 1738.90 | 22-FEB-10:15 | 1.13 | -2.8 | 0.273062E+09 | 446.64 | 22-FEB-10:20 | 1.13 | -2.8 |
March | 0.141325E+10 | 4064.03 | 29-MAR-09:50 | 6.52 | 3.33 | 0.357189E+09 | 544.94 | 29-MAR-09:09 | 6.52 | 3.33 |
April | 0.280458E+10 | 8512.42 | 07-APR-09:30 | 20.55 | 13.59 | 0.352722E+09 | 544.97 | 26-APR-09:00 | 16.10 | 12.59 |
May | 0.542945E+10 | 21293.57 | 29-MAY-08:52 | 26.10 | 16.72 | 0.410108E+09 | 552.33 | 30-MAY-13:00 | 29.40 | 16.93 |
June | 0.739838E+10 | 19106.42 | 04-JUN-09:13 | 23.67 | 12.90 | 0.425304E+09 | 549.80 | 22-JUN-13:30 | 29.15 | 17.46 |
July | 0.883395E+10 | 19823.50 | 02-JUL-09:12 | 25.77 | 21.71 | 0.397222E+09 | 552.24 | 11-JUL-13:00 | 28.90 | 17.83 |
August | 0.971007E+10 | 19155.68 | 13-AUG-09:52 | 28.90 | 19.41 | 0.445348E+09 | 560.89 | 22-AUG-09:00 | 28.30 | 18.37 |
September | 0.558540E+10 | 20929.34 | 04-SEP-09:12 | 24.47 | 18.42 | 0.387437E+09 | 545.53 | 06-SEP-09:20 | 25.97 | 19.25 |
October | 0.348883E+10 | 7532.67 | 05-OCT-09:20 | 19.27 | 16.99 | 0.385319E+09 | 544.98 | 16-OCT-09:09 | 16.88 | 14.11 |
November | 0.103823E+10 | 2271.47 | 02-NOV-13:30 | 15.85 | 8.46 | 0.314964E+09 | 530.73 | 03-NOV-09:00 | 13.30 | 8.39 |
December | 0.249841E+09 | 1752.42 | 20-DEC-09:35 | 7.57 | 4.72 | 0.289250E+09 | 449.72 | 20-DEC-10:09 | 8.40 | 5.03 |
Annual Sum or Average | 0.464578E+11 | 0.433762E+10 | ||||||||
Minimum of Months | 0.217583E+09 | 1701.50 | 1.13 | -2.8 | 0.273062E+09 | 442.74 | 1.13 | -2.8 | ||
Maximum of Months | 0.971007E+10 | 21293.57 | 28.90 | 21.71 | 0.445348E+09 | 560.89 | 29.40 | 19.25 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.134379E+10 | 8855.22 | 19-JAN-13:50 | 9.40 | 3.78 | 0.507356E+09 | 845.64 | 30-JAN-14:30 | 2.80 | -1.1 |
February | 0.173311E+10 | 9603.48 | 02-FEB-14:20 | 5.40 | -1.3 | 0.468306E+09 | 845.64 | 10-FEB-14:20 | 2.97 | -0.3 |
March | 0.361066E+10 | 13234.09 | 03-MAR-13:40 | 14.80 | 8.43 | 0.587749E+09 | 845.65 | 01-MAR-14:50 | 14.80 | 8.43 |
April | 0.437662E+10 | 14470.88 | 07-APR-12:40 | 26.33 | 16.06 | 0.545645E+09 | 846.34 | 07-APR-13:20 | 26.50 | 16.25 |
May | 0.650924E+10 | 23794.92 | 29-MAY-12:13 | 28.33 | 17.95 | 0.631875E+09 | 891.73 | 30-MAY-13:00 | 29.40 | 16.93 |
June | 0.935854E+10 | 15172.52 | 08-JUN-05:02 | 19.08 | 17.42 | 0.659344E+09 | 872.31 | 22-JUN-13:30 | 29.15 | 17.46 |
July | 0.115990E+11 | 24299.51 | 30-JUL-13:32 | 27.20 | 24.02 | 0.616294E+09 | 862.78 | 11-JUL-13:00 | 27.20 | 24.02 |
August | 0.142238E+11 | 23858.28 | 13-AUG-12:32 | 30.93 | 19.36 | 0.691357E+09 | 852.16 | 30-AUG-13:30 | 28.05 | 15.56 |
September | 0.102845E+11 | 26184.92 | 04-SEP-11:52 | 26.10 | 17.79 | 0.605119E+09 | 870.51 | 01-SEP-13:50 | 26.10 | 17.79 |
October | 0.883370E+10 | 23637.63 | 15-OCT-13:23 | 20.85 | 13.17 | 0.613206E+09 | 858.74 | 04-OCT-13:30 | 20.85 | 13.17 |
November | 0.307069E+10 | 15345.22 | 02-NOV-13:20 | 15.77 | 8.37 | 0.539867E+09 | 845.76 | 02-NOV-13:00 | 16.10 | 8.71 |
December | 0.161315E+10 | 8256.45 | 21-DEC-13:30 | 3.05 | -1.7 | 0.496024E+09 | 845.64 | 14-DEC-14:09 | 3.05 | -1.7 |
Annual Sum or Average | 0.765569E+11 | 0.696214E+10 | ||||||||
Minimum of Months | 0.134379E+10 | 8256.45 | 3.05 | -1.7 | 0.468306E+09 | 845.64 | 2.80 | -1.7 | ||
Maximum of Months | 0.142238E+11 | 26184.92 | 30.93 | 24.02 | 0.691357E+09 | 891.73 | 29.40 | 24.02 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.394358E+09 | 2304.73 | 20-JAN-16:00 | 7.20 | 3.80 | 0.303192E+09 | 486.19 | 20-JAN-16:10 | 6.93 | 3.71 |
February | 0.494362E+09 | 2628.30 | 22-FEB-16:30 | 3.85 | -0.7 | 0.278821E+09 | 521.16 | 22-FEB-16:40 | 3.67 | -0.7 |
March | 0.190219E+10 | 7250.86 | 29-MAR-16:00 | 7.20 | 4.88 | 0.353966E+09 | 544.94 | 02-MAR-14:00 | 7.20 | 4.88 |
April | 0.329027E+10 | 19177.15 | 09-APR-16:51 | 16.10 | 13.79 | 0.340573E+09 | 544.96 | 10-APR-13:09 | 20.10 | 10.10 |
May | 0.558572E+10 | 17229.03 | 29-MAY-14:13 | 25.93 | 17.30 | 0.403460E+09 | 553.83 | 30-MAY-13:00 | 29.40 | 16.93 |
June | 0.821870E+10 | 21819.86 | 18-JUN-16:02 | 25.50 | 22.07 | 0.425021E+09 | 550.06 | 22-JUN-13:30 | 29.15 | 17.46 |
July | 0.942488E+10 | 22945.55 | 09-JUL-15:21 | 27.20 | 24.16 | 0.397253E+09 | 553.65 | 11-JUL-13:00 | 28.90 | 17.83 |
August | 0.104694E+11 | 21865.13 | 13-AUG-15:52 | 30.00 | 20.46 | 0.445553E+09 | 556.71 | 22-AUG-15:30 | 29.70 | 17.33 |
September | 0.594651E+10 | 22558.35 | 10-SEP-16:52 | 22.80 | 12.70 | 0.384033E+09 | 544.97 | 11-SEP-13:09 | 20.60 | 12.01 |
October | 0.407809E+10 | 10766.02 | 04-OCT-15:30 | 23.35 | 19.12 | 0.372944E+09 | 544.95 | 02-OCT-13:20 | 23.35 | 19.12 |
November | 0.123084E+10 | 4847.76 | 03-NOV-15:30 | 16.10 | 10.65 | 0.314158E+09 | 544.88 | 03-NOV-13:00 | 16.10 | 10.65 |
December | 0.435626E+09 | 2223.96 | 08-DEC-15:40 | 6.30 | 2.04 | 0.292702E+09 | 473.97 | 08-DEC-15:50 | 6.20 | 1.96 |
Annual Sum or Average | 0.514709E+11 | 0.431168E+10 | ||||||||
Minimum of Months | 0.394358E+09 | 2223.96 | 3.85 | -0.7 | 0.278821E+09 | 473.97 | 3.67 | -0.7 | ||
Maximum of Months | 0.104694E+11 | 22945.55 | 30.00 | 24.16 | 0.445553E+09 | 556.71 | 29.70 | 19.12 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.288237E+09 | 3206.76 | 14-JAN-06:01 | -7.8 | -8.5 | 0.00 | 0.00 | 01-JAN-00:10 | -7.8 | -8.5 |
February | 0.341578E+09 | 4721.37 | 06-FEB-05:01 | -13.2 | -14.5 | 0.00 | 0.00 | 01-FEB-00:10 | -13.2 | -14.5 |
March | 0.151849E+10 | 3458.53 | 31-MAR-05:10 | 5.10 | 5.10 | 0.00 | 0.00 | 01-MAR-00:10 | 5.10 | 5.10 |
April | 0.353341E+10 | 8349.65 | 10-APR-05:13 | 15.20 | 13.76 | 0.00 | 0.00 | 01-APR-00:10 | 15.20 | 13.76 |
May | 0.508543E+10 | 12082.22 | 30-MAY-05:15 | 18.53 | 14.51 | 0.00 | 0.00 | 01-MAY-00:10 | 18.53 | 14.51 |
June | 0.800837E+10 | 9709.11 | 12-JUN-05:15 | 18.50 | 17.63 | 0.00 | 0.00 | 01-JUN-00:10 | 18.50 | 17.63 |
July | 0.950605E+10 | 12396.08 | 10-JUL-05:15 | 26.10 | 20.74 | 0.00 | 0.00 | 01-JUL-00:10 | 26.10 | 20.74 |
August | 0.108666E+11 | 13506.91 | 14-AUG-05:15 | 22.57 | 20.98 | 0.00 | 0.00 | 01-AUG-00:10 | 22.57 | 20.98 |
September | 0.660357E+10 | 12389.63 | 05-SEP-05:15 | 20.60 | 18.00 | 0.00 | 0.00 | 01-SEP-00:10 | 20.60 | 18.00 |
October | 0.518235E+10 | 8235.25 | 23-OCT-05:13 | 13.13 | 11.01 | 0.00 | 0.00 | 01-OCT-00:10 | 13.13 | 11.01 |
November | 0.197702E+10 | 5306.24 | 13-NOV-06:15 | 5.77 | 4.71 | 0.00 | 0.00 | 01-NOV-00:10 | 5.77 | 4.71 |
December | 0.810363E+09 | 3401.73 | 18-DEC-06:08 | 0.60 | -1.3 | 0.00 | 0.00 | 01-DEC-00:10 | 0.60 | -1.3 |
Annual Sum or Average | 0.537215E+11 | 0.00 | ||||||||
Minimum of Months | 0.288237E+09 | 3206.76 | -13.2 | -14.5 | 0.00 | 0.00 | -13.2 | -14.5 | ||
Maximum of Months | 0.108666E+11 | 13506.91 | 26.10 | 20.98 | 0.00 | 0.00 | 26.10 | 20.98 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 95633488.82 | 5546.45 | 14-JAN-04:01 | -6.8 | -7.5 | 0.00 | 0.00 | 01-JAN-00:10 | -6.8 | -7.5 |
February | 0.105149E+09 | 6177.63 | 05-FEB-22:51 | -12.2 | -14.0 | 0.00 | 0.00 | 01-FEB-00:10 | -12.2 | -14.0 |
March | 0.408577E+09 | 5201.61 | 13-MAR-04:01 | -0.1 | -3.5 | 0.00 | 0.00 | 01-MAR-00:10 | -0.1 | -3.5 |
April | 0.139014E+10 | 3752.97 | 10-APR-05:10 | 15.10 | 13.73 | 0.00 | 0.00 | 01-APR-00:10 | 15.10 | 13.73 |
May | 0.322065E+10 | 7006.16 | 30-MAY-13:35 | 29.60 | 17.29 | 0.00 | 0.00 | 01-MAY-00:10 | 29.60 | 17.29 |
June | 0.614503E+10 | 7475.25 | 20-JUN-13:30 | 26.95 | 17.82 | 0.00 | 0.00 | 01-JUN-00:10 | 26.95 | 17.82 |
July | 0.747646E+10 | 7977.59 | 11-JUL-14:50 | 28.40 | 17.63 | 0.00 | 0.00 | 01-JUL-00:10 | 28.40 | 17.63 |
August | 0.831204E+10 | 9585.18 | 07-AUG-05:15 | 19.40 | 16.84 | 0.00 | 0.00 | 01-AUG-00:10 | 19.40 | 16.84 |
September | 0.498900E+10 | 9334.56 | 01-SEP-14:15 | 30.93 | 17.38 | 0.00 | 0.00 | 01-SEP-00:10 | 30.93 | 17.38 |
October | 0.275922E+10 | 5063.56 | 05-OCT-05:13 | 15.60 | 14.70 | 0.00 | 0.00 | 01-OCT-00:10 | 15.60 | 14.70 |
November | 0.536853E+09 | 5074.35 | 22-NOV-05:01 | -2.2 | -3.3 | 0.00 | 0.00 | 01-NOV-00:10 | -2.2 | -3.3 |
December | 0.107523E+09 | 6049.39 | 02-DEC-05:01 | 1.10 | -2.4 | 0.00 | 0.00 | 01-DEC-00:10 | 1.10 | -2.4 |
Annual Sum or Average | 0.355463E+11 | 0.00 | ||||||||
Minimum of Months | 95633488.82 | 3752.97 | -12.2 | -14.0 | 0.00 | 0.00 | -12.2 | -14.0 | ||
Maximum of Months | 0.831204E+10 | 9585.18 | 30.93 | 17.82 | 0.00 | 0.00 | 30.93 | 17.82 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | -9.6 | -11.5 | 0.00 | 0.00 | 01-JAN-00:10 | -9.6 | -11.5 |
February | 1000283.73 | 298.64 | 17-FEB-13:00 | 6.70 | 1.56 | 0.00 | 0.00 | 01-FEB-00:10 | 6.70 | 1.56 |
March | 0.582434E+09 | 5014.87 | 03-MAR-14:40 | 15.00 | 8.47 | 0.00 | 0.00 | 01-MAR-00:10 | 15.00 | 8.47 |
April | 0.244079E+10 | 13190.03 | 07-APR-13:30 | 26.40 | 16.17 | 0.00 | 0.00 | 01-APR-00:10 | 26.40 | 16.17 |
May | 0.613902E+10 | 20739.38 | 30-MAY-13:05 | 29.90 | 17.82 | 0.00 | 0.00 | 01-MAY-00:10 | 29.90 | 17.82 |
June | 0.110272E+11 | 21693.77 | 19-JUN-13:50 | 34.50 | 23.73 | 0.00 | 0.00 | 01-JUN-00:10 | 34.50 | 23.73 |
July | 0.136769E+11 | 20420.27 | 10-JUL-14:10 | 32.88 | 20.91 | 0.00 | 0.00 | 01-JUL-00:10 | 32.88 | 20.91 |
August | 0.145591E+11 | 20693.14 | 22-AUG-14:20 | 30.73 | 18.19 | 0.00 | 0.00 | 01-AUG-00:10 | 30.73 | 18.19 |
September | 0.706132E+10 | 17971.21 | 01-SEP-14:00 | 31.10 | 17.34 | 0.00 | 0.00 | 01-SEP-00:10 | 31.10 | 17.34 |
October | 0.336570E+10 | 11076.43 | 04-OCT-14:50 | 23.98 | 19.09 | 0.00 | 0.00 | 01-OCT-00:10 | 23.98 | 19.09 |
November | 0.213177E+09 | 3493.69 | 04-NOV-13:10 | 17.62 | 12.77 | 0.00 | 0.00 | 01-NOV-00:10 | 17.62 | 12.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 | 2.86 | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 | 2.86 |
Annual Sum or Average | 0.590666E+11 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -9.6 | -11.5 | 0.00 | 0.00 | -9.6 | -11.5 | ||
Maximum of Months | 0.145591E+11 | 21693.77 | 34.50 | 23.73 | 0.00 | 0.00 | 34.50 | 23.73 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.235293E+10 | 1934.41 | 20-JAN-16:30 | 6.40 | 3.51 | 95227794.89 | 126.83 | 24-JAN-14:00 | 11.00 | 11.00 |
February | 0.724080E+10 | 3979.31 | 22-FEB-16:50 | 3.48 | -0.7 | 86396473.91 | 126.82 | 22-FEB-10:09 | 3.48 | -0.7 |
March | 0.140437E+11 | 6935.85 | 31-MAR-24:00 | 5.40 | 5.40 | 0.103237E+09 | 126.83 | 27-MAR-13:39 | 5.40 | 5.40 |
April | 0.187468E+11 | 8071.72 | 23-APR-17:45 | 12.38 | 8.83 | 91605457.19 | 126.83 | 17-APR-09:00 | 12.38 | 8.83 |
May | 0.437831E+10 | 3522.82 | 31-MAY-24:00 | 18.50 | 16.73 | 99238219.21 | 126.85 | 31-MAY-13:20 | 18.50 | 16.73 |
June | 0.936771E+10 | 5342.74 | 30-JUN-24:00 | 20.00 | 19.21 | 98973713.06 | 126.86 | 15-JUN-13:00 | 20.00 | 19.21 |
July | 0.147530E+11 | 7222.48 | 31-JUL-23:57 | 23.90 | 22.01 | 91892016.63 | 126.85 | 28-JUL-09:09 | 23.90 | 22.01 |
August | 0.198873E+11 | 7984.20 | 13-AUG-18:12 | 27.80 | 20.19 | 0.103804E+09 | 133.39 | 16-AUG-13:00 | 32.20 | 25.36 |
September | 0.439284E+10 | 3414.15 | 30-SEP-24:00 | 12.60 | 11.96 | 91611012.42 | 126.85 | 05-SEP-13:09 | 12.60 | 11.96 |
October | 0.946356E+10 | 5136.44 | 31-OCT-24:00 | 10.60 | 9.48 | 95237801.29 | 126.85 | 24-OCT-09:00 | 10.60 | 9.48 |
November | 0.135509E+11 | 5843.07 | 03-NOV-16:00 | 15.00 | 10.26 | 94301198.15 | 126.84 | 10-NOV-10:00 | 15.60 | 14.59 |
December | 0.188388E+11 | 7701.48 | 18-DEC-16:00 | 5.60 | 2.49 | 91880795.25 | 126.82 | 21-DEC-10:09 | 0.78 | -2.5 |
Annual Sum or Average | 0.137017E+12 | 0.114340E+10 | ||||||||
Minimum of Months | 0.235293E+10 | 1934.41 | 3.48 | -0.7 | 86396473.91 | 126.82 | 0.78 | -2.5 | ||
Maximum of Months | 0.198873E+11 | 8071.72 | 27.80 | 22.01 | 0.103804E+09 | 133.39 | 32.20 | 25.36 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.486441E+09 | 1540.40 | 20-JAN-16:40 | 6.13 | 3.40 | 93661360.81 | 126.83 | 24-JAN-10:50 | 10.60 | 10.60 |
February | 0.465403E+10 | 3543.81 | 22-FEB-17:00 | 3.30 | -0.7 | 86396479.90 | 126.82 | 22-FEB-10:09 | 3.30 | -0.7 |
March | 0.116481E+11 | 6009.06 | 31-MAR-23:50 | 5.53 | 5.53 | 0.103237E+09 | 126.83 | 06-MAR-14:00 | 5.53 | 5.53 |
April | 0.168177E+11 | 7497.51 | 09-APR-17:30 | 15.55 | 13.44 | 91605513.83 | 126.83 | 17-APR-09:00 | 13.30 | 12.36 |
May | 0.365381E+10 | 3350.89 | 31-MAY-24:00 | 18.50 | 16.73 | 99235508.31 | 126.84 | 31-MAY-09:00 | 18.50 | 16.73 |
June | 0.878403E+10 | 5034.59 | 30-JUN-24:00 | 20.00 | 19.21 | 98972899.66 | 126.86 | 15-JUN-13:00 | 20.00 | 19.21 |
July | 0.140600E+11 | 6968.16 | 31-JUL-23:57 | 23.90 | 22.01 | 91892714.40 | 126.85 | 18-JUL-09:00 | 23.90 | 22.01 |
August | 0.189266E+11 | 7605.39 | 31-AUG-17:30 | 25.30 | 22.17 | 0.103745E+09 | 133.65 | 16-AUG-13:00 | 25.30 | 22.17 |
September | 0.380004E+10 | 3073.88 | 30-SEP-23:40 | 12.87 | 12.13 | 91609132.16 | 126.84 | 01-SEP-09:09 | 12.87 | 12.13 |
October | 0.821584E+10 | 4404.44 | 31-OCT-24:00 | 10.60 | 9.48 | 95237291.86 | 126.85 | 06-OCT-09:50 | 10.60 | 9.48 |
November | 0.109912E+11 | 5470.13 | 03-NOV-16:00 | 15.00 | 10.26 | 94301110.94 | 126.84 | 10-NOV-10:50 | 15.68 | 14.79 |
December | 0.153923E+11 | 7030.62 | 21-DEC-16:10 | 2.62 | -2.3 | 91880825.70 | 126.82 | 21-DEC-10:09 | 2.62 | -2.3 |
Annual Sum or Average | 0.117430E+12 | 0.114178E+10 | ||||||||
Minimum of Months | 0.486441E+09 | 1540.40 | 2.62 | -2.3 | 86396479.90 | 126.82 | 2.62 | -2.3 | ||
Maximum of Months | 0.189266E+11 | 7605.39 | 25.30 | 22.17 | 0.103745E+09 | 133.65 | 25.30 | 22.17 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.226279E+09 | 1423.12 | 19-JAN-16:30 | 8.05 | 2.65 | 91034777.73 | 128.07 | 18-JAN-10:09 | 8.05 | 2.65 |
February | 0.314167E+10 | 3401.59 | 02-FEB-17:00 | 2.80 | -3.1 | 86395831.85 | 126.82 | 22-FEB-10:09 | 0.87 | -3.0 |
March | 0.102025E+11 | 5539.09 | 29-MAR-17:00 | 6.10 | 4.33 | 0.103237E+09 | 126.83 | 06-MAR-14:00 | 6.10 | 4.33 |
April | 0.158588E+11 | 7567.06 | 09-APR-17:30 | 15.55 | 13.44 | 91605557.99 | 126.83 | 17-APR-09:00 | 13.30 | 12.36 |
May | 0.327413E+10 | 3321.63 | 31-MAY-24:00 | 18.50 | 16.73 | 99236564.25 | 126.85 | 31-MAY-13:00 | 18.50 | 16.73 |
June | 0.877704E+10 | 4951.34 | 30-JUN-24:00 | 20.00 | 19.21 | 98973373.17 | 126.86 | 15-JUN-13:00 | 20.00 | 19.21 |
July | 0.141607E+11 | 6971.72 | 31-JUL-23:57 | 23.90 | 22.01 | 91893008.27 | 126.85 | 20-JUL-09:00 | 23.90 | 22.01 |
August | 0.189878E+11 | 7750.83 | 13-AUG-17:40 | 29.07 | 20.11 | 0.103553E+09 | 132.11 | 16-AUG-13:00 | 32.20 | 25.36 |
September | 0.356592E+10 | 2808.19 | 30-SEP-23:20 | 13.13 | 12.30 | 91609330.71 | 126.85 | 06-SEP-13:00 | 13.13 | 12.30 |
October | 0.734514E+10 | 3908.63 | 04-OCT-16:00 | 22.80 | 19.11 | 95237369.40 | 126.85 | 24-OCT-13:00 | 22.20 | 19.22 |
November | 0.934213E+10 | 5434.26 | 03-NOV-16:00 | 15.00 | 10.26 | 94301129.09 | 126.84 | 10-NOV-10:50 | 15.68 | 14.79 |
December | 0.134180E+11 | 6807.94 | 08-DEC-16:10 | 5.92 | 1.77 | 91880834.29 | 126.82 | 21-DEC-10:09 | 0.78 | -2.5 |
Annual Sum or Average | 0.108300E+12 | 0.113896E+10 | ||||||||
Minimum of Months | 0.226279E+09 | 1423.12 | 2.80 | -3.1 | 86395831.85 | 126.82 | 0.78 | -3.0 | ||
Maximum of Months | 0.189878E+11 | 7750.83 | 29.07 | 22.01 | 0.103553E+09 | 132.11 | 32.20 | 25.36 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.234911E+12 | 91147.31 | 20-JAN-17:00 | 5.60 | 3.19 | 0.206164E+10 | 2746.94 | 26-JAN-10:00 | 3.30 | -0.4 |
February | 0.433152E+12 | 182527.00 | 22-FEB-17:00 | 3.30 | -0.7 | 0.187129E+10 | 2749.18 | 13-FEB-10:20 | 3.30 | -0.7 |
March | 0.727771E+12 | 358031.60 | 31-MAR-24:00 | 5.40 | 5.40 | 0.223552E+10 | 2749.46 | 22-MAR-13:09 | 5.40 | 5.40 |
April | 0.941832E+12 | 367103.26 | 10-APR-16:00 | 20.00 | 11.13 | 0.198542E+10 | 2940.86 | 07-APR-13:39 | 20.00 | 11.13 |
May | 0.239862E+12 | 175884.78 | 31-MAY-24:00 | 18.50 | 16.73 | 0.214836E+10 | 2746.52 | 18-MAY-13:00 | 18.50 | 16.73 |
June | 0.469954E+12 | 267492.19 | 30-JUN-24:00 | 20.00 | 19.21 | 0.214255E+10 | 2746.50 | 15-JUN-13:00 | 20.00 | 19.21 |
July | 0.731902E+12 | 359805.13 | 31-JUL-23:57 | 23.90 | 22.01 | 0.198919E+10 | 2745.89 | 18-JUL-09:00 | 23.90 | 22.01 |
August | 0.974914E+12 | 369565.33 | 18-AUG-23:15 | 23.13 | 17.02 | 0.246909E+10 | 3494.74 | 16-AUG-13:00 | 23.13 | 17.02 |
September | 0.235894E+12 | 176249.20 | 30-SEP-24:00 | 12.60 | 11.96 | 0.198339E+10 | 2746.92 | 14-SEP-09:00 | 12.60 | 11.96 |
October | 0.487831E+12 | 267951.31 | 31-OCT-24:00 | 10.60 | 9.48 | 0.206180E+10 | 2747.19 | 26-OCT-13:09 | 10.60 | 9.48 |
November | 0.707543E+12 | 276238.39 | 06-NOV-17:00 | 11.70 | 7.36 | 0.204175E+10 | 2748.22 | 22-NOV-14:09 | 2.02 | -1.8 |
December | 0.974956E+12 | 367311.32 | 18-DEC-17:00 | 3.30 | 0.83 | 0.199010E+10 | 2748.59 | 22-DEC-14:09 | 1.20 | -2.7 |
Annual Sum or Average | 0.716052E+13 | 0.249801E+11 | ||||||||
Minimum of Months | 0.234911E+12 | 91147.31 | 3.30 | -0.7 | 0.187129E+10 | 2745.89 | 1.20 | -2.7 | ||
Maximum of Months | 0.974956E+12 | 369565.33 | 23.90 | 22.01 | 0.246909E+10 | 3494.74 | 23.90 | 22.01 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 68145517.97 | 10425.49 | 24-JAN-05:50 | 10.92 |
February | 58645315.32 | 10340.94 | 21-FEB-04:04 | 1.78 |
March | 0.102354E+09 | 10805.86 | 29-MAR-04:05 | 2.20 |
April | 0.137189E+09 | 10933.91 | 24-APR-03:05 | 7.88 |
May | 0.201060E+09 | 12175.24 | 29-MAY-18:53 | 25.00 |
June | 0.180938E+09 | 10519.03 | 10-JUN-04:07 | 16.28 |
July | 0.355380E+09 | 12639.76 | 25-JUL-03:53 | 23.30 |
August | 0.418096E+09 | 13016.42 | 12-AUG-16:02 | 27.80 |
September | 0.490355E+09 | 12347.72 | 14-SEP-03:53 | 22.20 |
October | 0.594492E+09 | 12695.24 | 25-OCT-03:53 | 17.20 |
November | 0.436900E+09 | 10757.46 | 13-NOV-04:17 | 5.60 |
December | 0.144433E+09 | 10643.15 | 26-DEC-05:15 | 5.77 |
Annual Sum or Average | 0.318799E+10 | |||
Minimum of Months | 58645315.32 | 10340.94 | 1.78 | |
Maximum of Months | 0.594492E+09 | 13016.42 | 27.80 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | -9.6 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -1.1 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -9.6 | |
Maximum of Months | 0.00 | 0.00 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.104757E+10 | 55499.59 | 02-JAN-04:01 | -11.8 |
February | 0.115526E+09 | 45589.40 | 06-FEB-05:01 | -13.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 310385.58 | 3621.17 | 27-NOV-06:01 | 6.78 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 |
Annual Sum or Average | 0.116341E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.2 | |
Maximum of Months | 0.104757E+10 | 55499.59 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.473768E+10 | 79287.91 | 02-JAN-04:01 | -11.8 |
February | 0.329236E+10 | 77752.96 | 06-FEB-04:01 | -13.3 |
March | 0.688874E+09 | 71250.63 | 20-MAR-04:01 | -0.8 |
April | 0.126538E+09 | 67999.26 | 03-APR-04:01 | 2.80 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 1398972.70 | 9326.48 | 30-OCT-05:03 | 11.93 |
November | 0.123151E+10 | 73443.05 | 24-NOV-04:01 | -3.4 |
December | 0.170864E+10 | 73984.87 | 26-DEC-04:01 | 5.60 |
Annual Sum or Average | 0.117870E+11 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.473768E+10 | 79287.91 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.351818E+09 | 12258.32 | 02-JAN-05:01 | -12.1 |
February | 0.246020E+09 | 12301.73 | 06-FEB-05:01 | -13.2 |
March | 107059.90 | 1427.47 | 17-MAR-05:01 | -1.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 877713.76 | 8353.23 | 22-NOV-06:01 | -2.2 |
December | 278709.42 | 3355.85 | 02-DEC-06:01 | 1.10 |
Annual Sum or Average | 0.599101E+09 | |||
Minimum of Months | 0.00 | 0.00 | -13.2 | |
Maximum of Months | 0.351818E+09 | 12301.73 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.242699E+09 | 11519.33 | 02-JAN-05:01 | -12.1 |
February | 0.150112E+09 | 11581.43 | 06-FEB-05:01 | -13.2 |
March | 2345834.58 | 8819.13 | 17-MAR-05:01 | -1.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 3539907.77 | 8860.58 | 22-NOV-06:01 | -2.2 |
December | 6384185.72 | 8775.44 | 02-DEC-06:01 | 1.10 |
Annual Sum or Average | 0.405081E+09 | |||
Minimum of Months | 0.00 | 0.00 | -13.2 | |
Maximum of Months | 0.242699E+09 | 11581.43 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.470033E+09 | 17511.63 | 02-JAN-04:01 | -11.8 |
February | 0.263453E+09 | 16547.15 | 06-FEB-05:01 | -13.2 |
March | 9725512.15 | 13483.84 | 17-MAR-05:01 | -1.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 11704005.16 | 13495.77 | 24-NOV-06:01 | -4.4 |
December | 20123972.10 | 13453.56 | 07-DEC-06:01 | 0.10 |
Annual Sum or Average | 0.775039E+09 | |||
Minimum of Months | 0.00 | 0.00 | -13.2 | |
Maximum of Months | 0.470033E+09 | 17511.63 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 42099436.12 | 10000.62 | 02-JAN-05:01 | -12.1 |
February | 19568103.98 | 9668.38 | 06-FEB-05:01 | -13.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 |
Annual Sum or Average | 61667540.10 | |||
Minimum of Months | 0.00 | 0.00 | -13.2 | |
Maximum of Months | 42099436.12 | 10000.62 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.478531E+10 | 13756.86 | 01-JAN-15:22 | -2.8 |
February | 0.382517E+10 | 13644.49 | 06-FEB-00:51 | -13.3 |
March | 0.799958E+09 | 12243.12 | 13-MAR-03:01 | 0.50 |
April | 0.113947E+09 | 11328.61 | 03-APR-04:01 | 2.80 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 5836668.74 | 10360.56 | 28-OCT-05:02 | 3.90 |
November | 0.856838E+09 | 12731.22 | 24-NOV-04:01 | -3.4 |
December | 0.208036E+10 | 13411.75 | 31-DEC-21:52 | -7.2 |
Annual Sum or Average | 0.124674E+11 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.478531E+10 | 13756.86 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.271862E+10 | 16633.21 | 02-JAN-00:02 | -10.7 |
February | 0.184471E+10 | 16591.55 | 06-FEB-00:51 | -13.3 |
March | 0.381563E+09 | 14742.09 | 13-MAR-03:01 | 0.50 |
April | 65260368.22 | 13534.38 | 03-APR-04:01 | 2.80 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 1710659.77 | 6286.70 | 28-OCT-05:02 | 3.90 |
November | 0.445509E+09 | 15320.60 | 24-NOV-04:01 | -3.4 |
December | 0.115768E+10 | 15976.39 | 31-DEC-21:52 | -7.2 |
Annual Sum or Average | 0.661506E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.271862E+10 | 16633.21 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.286384E+10 | 18816.96 | 02-JAN-00:02 | -10.7 |
February | 0.172736E+10 | 18684.87 | 06-FEB-04:11 | -13.3 |
March | 0.390551E+09 | 16208.02 | 17-MAR-04:01 | -1.6 |
April | 80154219.66 | 15059.62 | 03-APR-04:01 | 2.80 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.373080E+09 | 16256.49 | 24-NOV-05:01 | -4.0 |
December | 0.109284E+10 | 16806.43 | 11-DEC-04:01 | 1.70 |
Annual Sum or Average | 0.652782E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.286384E+10 | 18816.96 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.222264E+10 | 17206.93 | 02-JAN-00:02 | -10.7 |
February | 0.155062E+10 | 17174.80 | 06-FEB-04:11 | -13.3 |
March | 0.232642E+09 | 14787.69 | 13-MAR-04:01 | -0.1 |
April | 30184033.05 | 13261.02 | 03-APR-05:01 | 2.70 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 320197.04 | 2366.57 | 28-OCT-05:02 | 3.90 |
November | 0.333383E+09 | 15415.00 | 24-NOV-04:01 | -3.4 |
December | 0.774440E+09 | 14980.62 | 11-DEC-05:01 | 1.70 |
Annual Sum or Average | 0.514424E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.222264E+10 | 17206.93 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.916142E+10 | 16514.81 | 16-JAN-06:12 | -4.8 |
February | 0.812607E+10 | 16610.30 | 06-FEB-01:01 | -13.3 |
March | 0.294541E+10 | 15610.26 | 13-MAR-03:01 | 0.50 |
April | 0.860403E+09 | 15237.81 | 03-APR-03:01 | 3.22 |
May | 24139727.55 | 12214.02 | 01-MAY-05:03 | 6.28 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 0.239728E+09 | 13394.57 | 28-OCT-04:02 | 4.32 |
November | 0.313709E+10 | 16110.95 | 23-NOV-23:42 | -3.2 |
December | 0.627818E+10 | 16466.04 | 31-DEC-19:52 | -6.1 |
Annual Sum or Average | 0.307724E+11 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.916142E+10 | 16610.30 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.527349E+10 | 17448.91 | 16-JAN-06:12 | -4.8 |
February | 0.420653E+10 | 17555.71 | 06-FEB-01:01 | -13.3 |
March | 0.140951E+10 | 16583.19 | 13-MAR-03:01 | 0.50 |
April | 0.469598E+09 | 15961.03 | 03-APR-03:01 | 3.22 |
May | 11733216.35 | 8874.12 | 01-MAY-05:03 | 6.28 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 0.102206E+09 | 13940.89 | 28-OCT-04:02 | 4.32 |
November | 0.160870E+10 | 16908.47 | 23-NOV-23:42 | -3.2 |
December | 0.342284E+10 | 17373.66 | 31-DEC-19:52 | -6.1 |
Annual Sum or Average | 0.165046E+11 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.527349E+10 | 17555.71 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.608040E+10 | 21267.55 | 16-JAN-06:12 | -4.8 |
February | 0.459700E+10 | 21267.97 | 06-FEB-01:01 | -13.3 |
March | 0.170756E+10 | 20089.11 | 13-MAR-03:01 | 0.50 |
April | 0.653672E+09 | 19075.15 | 03-APR-03:01 | 3.22 |
May | 25306579.09 | 14134.29 | 01-MAY-05:03 | 6.28 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 65703450.02 | 15792.58 | 27-OCT-05:02 | 6.02 |
November | 0.171101E+10 | 19779.71 | 27-NOV-04:01 | 6.60 |
December | 0.376278E+10 | 20945.50 | 31-DEC-19:52 | -6.1 |
Annual Sum or Average | 0.186034E+11 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.608040E+10 | 21267.97 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.457371E+10 | 18955.04 | 02-JAN-00:02 | -10.7 |
February | 0.359368E+10 | 19039.72 | 06-FEB-01:01 | -13.3 |
March | 0.978588E+09 | 17867.61 | 13-MAR-03:01 | 0.50 |
April | 0.277738E+09 | 16090.29 | 22-APR-04:11 | 5.60 |
May | 4121214.69 | 8498.39 | 01-MAY-05:03 | 6.28 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 59897230.95 | 12352.93 | 28-OCT-04:02 | 4.32 |
November | 0.128134E+10 | 17515.95 | 20-NOV-04:01 | 0.60 |
December | 0.253940E+10 | 18567.23 | 31-DEC-21:52 | -7.2 |
Annual Sum or Average | 0.133085E+11 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.457371E+10 | 19039.72 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.166245E+10 | 12857.62 | 18-JAN-06:01 | 7.38 |
February | 0.114428E+10 | 12052.39 | 17-FEB-06:01 | 0.60 |
March | 0.192492E+09 | 13290.12 | 13-MAR-04:01 | -0.1 |
April | 0.187981E+09 | 12790.53 | 03-APR-04:01 | 2.80 |
May | 87998368.20 | 10190.89 | 01-MAY-03:02 | 7.45 |
June | 84423112.62 | 9910.42 | 12-JUN-03:02 | 18.90 |
July | 90934005.86 | 7423.60 | 01-JUL-03:02 | 20.00 |
August | 64959753.08 | 8439.51 | 13-AUG-15:01 | 30.50 |
September | 77782048.99 | 9219.72 | 25-SEP-03:02 | 13.98 |
October | 0.112477E+09 | 10327.69 | 10-OCT-03:02 | 10.60 |
November | 0.145325E+09 | 14110.15 | 24-NOV-05:01 | -4.0 |
December | 0.244912E+09 | 14492.81 | 11-DEC-05:01 | 1.70 |
Annual Sum or Average | 0.409601E+10 | |||
Minimum of Months | 64959753.08 | 7423.60 | -4.0 | |
Maximum of Months | 0.166245E+10 | 14492.81 | 30.50 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.507270E+10 | 19232.34 | 02-JAN-06:12 | -11.7 |
February | 0.322701E+10 | 8754.08 | 06-FEB-06:03 | -12.9 |
March | 0.166080E+10 | 8427.33 | 28-MAR-05:03 | 9.50 |
April | 0.496914E+09 | 8108.39 | 25-APR-05:02 | 9.60 |
May | 62775176.66 | 7996.55 | 03-MAY-05:03 | 11.78 |
June | 47973470.34 | 7311.53 | 12-JUN-03:02 | 18.90 |
July | 59671007.13 | 7189.69 | 21-JUL-03:02 | 24.90 |
August | 50549354.20 | 7227.52 | 02-AUG-03:02 | 25.00 |
September | 65114738.82 | 6845.31 | 18-SEP-03:02 | 16.70 |
October | 77703117.05 | 7243.63 | 10-OCT-05:03 | 9.72 |
November | 0.118444E+10 | 7531.10 | 10-NOV-06:03 | 14.60 |
December | 0.216223E+10 | 6560.61 | 03-DEC-12:53 | 8.30 |
Annual Sum or Average | 0.141679E+11 | |||
Minimum of Months | 47973470.34 | 6560.61 | -12.9 | |
Maximum of Months | 0.507270E+10 | 19232.34 | 25.00 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.119135E+11 | 27892.04 | 02-JAN-05:09 | -12.1 |
February | 0.100049E+11 | 29364.48 | 06-FEB-05:10 | -13.2 |
March | 0.453508E+10 | 21505.04 | 13-MAR-05:12 | -0.6 |
April | 0.187746E+10 | 14941.52 | 10-APR-05:02 | 15.10 |
May | 0.327030E+09 | 16344.12 | 16-MAY-05:02 | 9.18 |
June | 77686886.85 | 13967.31 | 03-JUN-05:03 | 13.48 |
July | 53425410.21 | 10448.69 | 05-JUL-03:02 | 20.10 |
August | 70407620.64 | 10778.42 | 08-AUG-04:03 | 15.50 |
September | 0.196516E+09 | 14667.59 | 29-SEP-05:03 | 11.78 |
October | 0.959540E+09 | 15726.72 | 16-OCT-05:03 | 8.90 |
November | 0.503850E+10 | 23048.09 | 24-NOV-05:12 | -4.1 |
December | 0.876136E+10 | 20736.19 | 11-DEC-05:12 | 1.70 |
Annual Sum or Average | 0.438154E+11 | |||
Minimum of Months | 53425410.21 | 10448.69 | -13.2 | |
Maximum of Months | 0.119135E+11 | 29364.48 | 20.10 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 7167129.88 | 436.15 | 01-JAN-09:58 | -2.2 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -1.1 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 |
Annual Sum or Average | 7167129.88 | |||
Minimum of Months | 0.00 | 0.00 | -2.2 | |
Maximum of Months | 7167129.88 | 436.15 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.456777E+09 | 549.59 | 16-JAN-18:00 | 3.90 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -1.1 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 |
Annual Sum or Average | 0.456777E+09 | |||
Minimum of Months | 0.00 | 0.00 | -1.1 | |
Maximum of Months | 0.456777E+09 | 549.59 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.732349E+09 | 578.08 | 29-JAN-17:50 | 0.18 |
February | 67959135.76 | 525.80 | 05-FEB-23:17 | -12.6 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 849251.02 | 355.74 | 01-MAY-03:55 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 |
Annual Sum or Average | 0.801157E+09 | |||
Minimum of Months | 0.00 | 0.00 | -12.6 | |
Maximum of Months | 0.732349E+09 | 578.08 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | -9.6 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -1.1 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -9.6 | |
Maximum of Months | 0.00 | 0.00 | 23.90 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.148304E+11 | 15519.45 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.134523E+11 | 15519.45 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.159851E+11 | 15519.45 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.142779E+11 | 15519.45 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.154078E+11 | 15519.45 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.153333E+11 | 15519.45 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.143524E+11 | 15519.45 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.159851E+11 | 15519.45 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.142779E+11 | 15519.45 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.148304E+11 | 15519.45 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.146566E+11 | 15519.45 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.143524E+11 | 15519.45 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.177742E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.134523E+11 | 15519.45 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.159851E+11 | 15519.45 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.133188E+11 | 13937.56 | 02-JAN-08:09 | 0.270551E+11 | 18128.59 | 02-JAN-08:09 |
February | 0.120811E+11 | 13937.56 | 01-FEB-08:09 | 0.244881E+11 | 18128.59 | 01-FEB-08:09 |
March | 0.143557E+11 | 13937.56 | 01-MAR-08:09 | 0.280558E+11 | 18128.59 | 01-MAR-08:09 |
April | 0.128226E+11 | 13937.56 | 03-APR-07:10 | 0.261305E+11 | 18128.59 | 03-APR-07:10 |
May | 0.138373E+11 | 13937.56 | 01-MAY-07:10 | 0.275555E+11 | 18128.59 | 01-MAY-07:10 |
June | 0.137704E+11 | 13937.56 | 01-JUN-07:10 | 0.270261E+11 | 18128.59 | 01-JUN-07:10 |
July | 0.128895E+11 | 13937.56 | 03-JUL-07:10 | 0.266527E+11 | 18128.59 | 03-JUL-07:10 |
August | 0.143557E+11 | 13937.56 | 01-AUG-07:10 | 0.280558E+11 | 18128.59 | 01-AUG-07:10 |
September | 0.128226E+11 | 13937.56 | 01-SEP-07:10 | 0.261160E+11 | 18128.59 | 01-SEP-07:10 |
October | 0.133188E+11 | 13937.56 | 02-OCT-07:10 | 0.270624E+11 | 18128.59 | 02-OCT-07:10 |
November | 0.131627E+11 | 13937.56 | 01-NOV-07:10 | 0.264424E+11 | 18128.59 | 01-NOV-07:10 |
December | 0.128895E+11 | 13937.56 | 01-DEC-08:09 | 0.266454E+11 | 18128.59 | 01-DEC-08:09 |
Annual Sum or Average | 0.159625E+12 | 0.321286E+12 | ||||
Minimum of Months | 0.120811E+11 | 13937.56 | 0.244881E+11 | 18128.59 | ||
Maximum of Months | 0.143557E+11 | 13937.56 | 0.280558E+11 | 18128.59 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.133188E+11 | 13937.56 | 02-JAN-08:09 | 0.270550E+11 | 18128.52 | 02-JAN-08:09 |
February | 0.120811E+11 | 13937.56 | 01-FEB-08:09 | 0.244880E+11 | 18128.52 | 01-FEB-08:09 |
March | 0.143557E+11 | 13937.56 | 01-MAR-08:09 | 0.280557E+11 | 18128.52 | 01-MAR-08:09 |
April | 0.128226E+11 | 13937.56 | 03-APR-07:10 | 0.261304E+11 | 18128.52 | 03-APR-07:10 |
May | 0.138373E+11 | 13937.56 | 01-MAY-07:10 | 0.275554E+11 | 18128.52 | 01-MAY-07:10 |
June | 0.137704E+11 | 13937.56 | 01-JUN-07:10 | 0.270260E+11 | 18128.52 | 01-JUN-07:10 |
July | 0.128895E+11 | 13937.56 | 03-JUL-07:10 | 0.266526E+11 | 18128.52 | 03-JUL-07:10 |
August | 0.143557E+11 | 13937.56 | 01-AUG-07:10 | 0.280557E+11 | 18128.52 | 01-AUG-07:10 |
September | 0.128226E+11 | 13937.56 | 01-SEP-07:10 | 0.261159E+11 | 18128.52 | 01-SEP-07:10 |
October | 0.133188E+11 | 13937.56 | 02-OCT-07:10 | 0.270623E+11 | 18128.52 | 02-OCT-07:10 |
November | 0.131627E+11 | 13937.56 | 01-NOV-07:10 | 0.264423E+11 | 18128.52 | 01-NOV-07:10 |
December | 0.128895E+11 | 13937.56 | 01-DEC-08:09 | 0.266453E+11 | 18128.52 | 01-DEC-08:09 |
Annual Sum or Average | 0.159625E+12 | 0.321285E+12 | ||||
Minimum of Months | 0.120811E+11 | 13937.56 | 0.244880E+11 | 18128.52 | ||
Maximum of Months | 0.143557E+11 | 13937.56 | 0.280557E+11 | 18128.52 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.133188E+11 | 13937.56 | 02-JAN-08:09 | 0.270550E+11 | 18128.52 | 02-JAN-08:09 |
February | 0.120811E+11 | 13937.56 | 01-FEB-08:09 | 0.244880E+11 | 18128.52 | 01-FEB-08:09 |
March | 0.143557E+11 | 13937.56 | 01-MAR-08:09 | 0.280557E+11 | 18128.52 | 01-MAR-08:09 |
April | 0.128226E+11 | 13937.56 | 03-APR-07:10 | 0.261304E+11 | 18128.52 | 03-APR-07:10 |
May | 0.138373E+11 | 13937.56 | 01-MAY-07:10 | 0.275554E+11 | 18128.52 | 01-MAY-07:10 |
June | 0.137704E+11 | 13937.56 | 01-JUN-07:10 | 0.270260E+11 | 18128.52 | 01-JUN-07:10 |
July | 0.128895E+11 | 13937.56 | 03-JUL-07:10 | 0.266526E+11 | 18128.52 | 03-JUL-07:10 |
August | 0.143557E+11 | 13937.56 | 01-AUG-07:10 | 0.280557E+11 | 18128.52 | 01-AUG-07:10 |
September | 0.128226E+11 | 13937.56 | 01-SEP-07:10 | 0.261159E+11 | 18128.52 | 01-SEP-07:10 |
October | 0.133188E+11 | 13937.56 | 02-OCT-07:10 | 0.270623E+11 | 18128.52 | 02-OCT-07:10 |
November | 0.131627E+11 | 13937.56 | 01-NOV-07:10 | 0.264423E+11 | 18128.52 | 01-NOV-07:10 |
December | 0.128895E+11 | 13937.56 | 01-DEC-08:09 | 0.266453E+11 | 18128.52 | 01-DEC-08:09 |
Annual Sum or Average | 0.159625E+12 | 0.321285E+12 | ||||
Minimum of Months | 0.120811E+11 | 13937.56 | 0.244880E+11 | 18128.52 | ||
Maximum of Months | 0.143557E+11 | 13937.56 | 0.280557E+11 | 18128.52 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.125601E+10 | 1750.00 | 02-JAN-16:40 | 0.339718E+10 | 2276.32 | 02-JAN-08:09 |
February | 0.108653E+10 | 1633.24 | 01-FEB-16:00 | 0.307485E+10 | 2276.32 | 01-FEB-08:09 |
March | 0.123764E+10 | 1405.53 | 02-MAR-16:00 | 0.352283E+10 | 2276.32 | 01-MAR-08:09 |
April | 0.107705E+10 | 1075.02 | 03-APR-07:10 | 0.328108E+10 | 2276.32 | 03-APR-07:10 |
May | 0.114469E+10 | 1075.02 | 01-MAY-07:10 | 0.346000E+10 | 2276.32 | 01-MAY-07:10 |
June | 0.112873E+10 | 1075.02 | 01-JUN-07:10 | 0.339353E+10 | 2276.32 | 01-JUN-07:10 |
July | 0.106210E+10 | 1075.02 | 03-JUL-07:10 | 0.334664E+10 | 2276.32 | 03-JUL-07:10 |
August | 0.119334E+10 | 1075.02 | 01-AUG-07:10 | 0.352283E+10 | 2276.32 | 01-AUG-07:10 |
September | 0.109024E+10 | 1294.12 | 27-SEP-07:10 | 0.327926E+10 | 2276.32 | 01-SEP-07:10 |
October | 0.116309E+10 | 1487.71 | 31-OCT-15:00 | 0.339809E+10 | 2276.32 | 02-OCT-07:10 |
November | 0.121639E+10 | 1750.00 | 06-NOV-16:49 | 0.332024E+10 | 2276.32 | 01-NOV-07:10 |
December | 0.123376E+10 | 1750.00 | 01-DEC-16:30 | 0.334573E+10 | 2276.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.138896E+11 | 0.403423E+11 | ||||
Minimum of Months | 0.106210E+10 | 1075.02 | 0.307485E+10 | 2276.32 | ||
Maximum of Months | 0.125601E+10 | 1750.00 | 0.352283E+10 | 2276.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.804202E+09 | 1127.77 | 02-JAN-16:40 | 0.218927E+10 | 1466.95 | 02-JAN-08:09 |
February | 0.698040E+09 | 1061.30 | 01-FEB-16:00 | 0.198155E+10 | 1466.95 | 01-FEB-08:09 |
March | 0.797944E+09 | 974.86 | 02-MAR-16:00 | 0.227025E+10 | 1466.95 | 01-MAR-08:09 |
April | 0.695582E+09 | 692.79 | 03-APR-07:10 | 0.211446E+10 | 1466.95 | 03-APR-07:10 |
May | 0.740418E+09 | 692.79 | 01-MAY-07:10 | 0.222976E+10 | 1466.95 | 01-MAY-07:10 |
June | 0.730635E+09 | 692.79 | 01-JUN-07:10 | 0.218692E+10 | 1466.95 | 01-JUN-07:10 |
July | 0.687186E+09 | 692.79 | 03-JUL-07:10 | 0.215670E+10 | 1466.95 | 03-JUL-07:10 |
August | 0.771443E+09 | 692.79 | 01-AUG-07:10 | 0.227025E+10 | 1466.95 | 01-AUG-07:10 |
September | 0.703077E+09 | 692.79 | 01-SEP-07:10 | 0.211328E+10 | 1466.95 | 01-SEP-07:10 |
October | 0.749140E+09 | 965.84 | 31-OCT-15:00 | 0.218986E+10 | 1466.95 | 02-OCT-07:10 |
November | 0.782643E+09 | 1127.77 | 06-NOV-16:49 | 0.213969E+10 | 1466.95 | 01-NOV-07:10 |
December | 0.785576E+09 | 1127.77 | 01-DEC-16:30 | 0.215612E+10 | 1466.95 | 01-DEC-08:09 |
Annual Sum or Average | 0.894589E+10 | 0.259981E+11 | ||||
Minimum of Months | 0.687186E+09 | 692.79 | 0.198155E+10 | 1466.95 | ||
Maximum of Months | 0.804202E+09 | 1127.77 | 0.227025E+10 | 1466.95 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.122940E+10 | 1750.04 | 02-JAN-16:40 | 0.339723E+10 | 2276.35 | 02-JAN-08:09 |
February | 0.107000E+10 | 1624.97 | 15-FEB-16:00 | 0.307490E+10 | 2276.35 | 01-FEB-08:09 |
March | 0.123291E+10 | 1327.90 | 02-MAR-16:00 | 0.352288E+10 | 2276.35 | 01-MAR-08:09 |
April | 0.107845E+10 | 1075.05 | 03-APR-07:10 | 0.328113E+10 | 2276.35 | 03-APR-07:10 |
May | 0.114844E+10 | 1075.05 | 01-MAY-07:10 | 0.346006E+10 | 2276.35 | 01-MAY-07:10 |
June | 0.113347E+10 | 1075.05 | 01-JUN-07:10 | 0.339359E+10 | 2276.35 | 01-JUN-07:10 |
July | 0.106607E+10 | 1075.05 | 03-JUL-07:10 | 0.334669E+10 | 2276.35 | 03-JUL-07:10 |
August | 0.119615E+10 | 1075.05 | 01-AUG-07:10 | 0.352288E+10 | 2276.35 | 01-AUG-07:10 |
September | 0.108863E+10 | 1261.96 | 27-SEP-07:10 | 0.327931E+10 | 2276.35 | 01-SEP-07:10 |
October | 0.115388E+10 | 1451.01 | 31-OCT-15:00 | 0.339814E+10 | 2276.35 | 02-OCT-07:10 |
November | 0.120121E+10 | 1750.04 | 06-NOV-16:49 | 0.332029E+10 | 2276.35 | 01-NOV-07:10 |
December | 0.119793E+10 | 1750.04 | 01-DEC-16:30 | 0.334578E+10 | 2276.35 | 01-DEC-08:09 |
Annual Sum or Average | 0.137965E+11 | 0.403429E+11 | ||||
Minimum of Months | 0.106607E+10 | 1075.05 | 0.307490E+10 | 2276.35 | ||
Maximum of Months | 0.123291E+10 | 1750.04 | 0.352288E+10 | 2276.35 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.796967E+09 | 1127.77 | 02-JAN-16:40 | 0.218926E+10 | 1466.94 | 02-JAN-08:09 |
February | 0.692505E+09 | 1042.73 | 15-FEB-16:00 | 0.198154E+10 | 1466.94 | 01-FEB-08:09 |
March | 0.793991E+09 | 895.58 | 16-MAR-07:10 | 0.227023E+10 | 1466.94 | 01-MAR-08:09 |
April | 0.694811E+09 | 794.98 | 14-APR-07:10 | 0.211444E+10 | 1466.94 | 03-APR-07:10 |
May | 0.737878E+09 | 692.79 | 01-MAY-07:10 | 0.222974E+10 | 1466.94 | 01-MAY-07:10 |
June | 0.727940E+09 | 692.79 | 01-JUN-07:10 | 0.218691E+10 | 1466.94 | 01-JUN-07:10 |
July | 0.685157E+09 | 692.79 | 03-JUL-07:10 | 0.215669E+10 | 1466.94 | 03-JUL-07:10 |
August | 0.769291E+09 | 774.11 | 16-AUG-07:10 | 0.227023E+10 | 1466.94 | 01-AUG-07:10 |
September | 0.702154E+09 | 868.81 | 27-SEP-07:10 | 0.211327E+10 | 1466.94 | 01-SEP-07:10 |
October | 0.744930E+09 | 941.51 | 06-OCT-07:10 | 0.218984E+10 | 1466.94 | 02-OCT-07:10 |
November | 0.775868E+09 | 1127.77 | 06-NOV-16:49 | 0.213967E+10 | 1466.94 | 01-NOV-07:10 |
December | 0.780572E+09 | 1127.77 | 01-DEC-16:30 | 0.215610E+10 | 1466.94 | 01-DEC-08:09 |
Annual Sum or Average | 0.890206E+10 | 0.259979E+11 | ||||
Minimum of Months | 0.685157E+09 | 692.79 | 0.198154E+10 | 1466.94 | ||
Maximum of Months | 0.796967E+09 | 1127.77 | 0.227023E+10 | 1466.94 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.125892E+10 | 1750.00 | 02-JAN-16:40 | 0.339718E+10 | 2276.32 | 02-JAN-08:09 |
February | 0.108831E+10 | 1636.80 | 01-FEB-16:00 | 0.307485E+10 | 2276.32 | 01-FEB-08:09 |
March | 0.123829E+10 | 1415.81 | 02-MAR-16:00 | 0.352283E+10 | 2276.32 | 01-MAR-08:09 |
April | 0.107756E+10 | 1075.02 | 03-APR-07:10 | 0.328108E+10 | 2276.32 | 03-APR-07:10 |
May | 0.114505E+10 | 1075.02 | 01-MAY-07:10 | 0.346000E+10 | 2276.32 | 01-MAY-07:10 |
June | 0.112912E+10 | 1075.02 | 01-JUN-07:10 | 0.339353E+10 | 2276.32 | 01-JUN-07:10 |
July | 0.106248E+10 | 1075.02 | 03-JUL-07:10 | 0.334664E+10 | 2276.32 | 03-JUL-07:10 |
August | 0.119361E+10 | 1075.02 | 01-AUG-07:10 | 0.352283E+10 | 2276.32 | 01-AUG-07:10 |
September | 0.109095E+10 | 1307.46 | 27-SEP-07:10 | 0.327926E+10 | 2276.32 | 01-SEP-07:10 |
October | 0.116409E+10 | 1495.56 | 31-OCT-15:00 | 0.339809E+10 | 2276.32 | 02-OCT-07:10 |
November | 0.121799E+10 | 1750.00 | 06-NOV-16:49 | 0.332024E+10 | 2276.32 | 01-NOV-07:10 |
December | 0.123696E+10 | 1750.00 | 01-DEC-16:30 | 0.334573E+10 | 2276.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.139033E+11 | 0.403423E+11 | ||||
Minimum of Months | 0.106248E+10 | 1075.02 | 0.307485E+10 | 2276.32 | ||
Maximum of Months | 0.125892E+10 | 1750.00 | 0.352283E+10 | 2276.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.804704E+09 | 1127.77 | 02-JAN-16:40 | 0.218927E+10 | 1466.95 | 02-JAN-08:09 |
February | 0.698386E+09 | 1061.85 | 01-FEB-16:00 | 0.198155E+10 | 1466.95 | 01-FEB-08:09 |
March | 0.798111E+09 | 976.04 | 02-MAR-16:00 | 0.227025E+10 | 1466.95 | 01-MAR-08:09 |
April | 0.695759E+09 | 692.79 | 03-APR-07:10 | 0.211446E+10 | 1466.95 | 03-APR-07:10 |
May | 0.740533E+09 | 692.79 | 01-MAY-07:10 | 0.222976E+10 | 1466.95 | 01-MAY-07:10 |
June | 0.730761E+09 | 692.79 | 01-JUN-07:10 | 0.218692E+10 | 1466.95 | 01-JUN-07:10 |
July | 0.687318E+09 | 692.79 | 03-JUL-07:10 | 0.215670E+10 | 1466.95 | 03-JUL-07:10 |
August | 0.771545E+09 | 692.79 | 01-AUG-07:10 | 0.227025E+10 | 1466.95 | 01-AUG-07:10 |
September | 0.703288E+09 | 692.79 | 01-SEP-07:10 | 0.211328E+10 | 1466.95 | 01-SEP-07:10 |
October | 0.749457E+09 | 967.14 | 31-OCT-15:00 | 0.218986E+10 | 1466.95 | 02-OCT-07:10 |
November | 0.782917E+09 | 1127.77 | 06-NOV-16:49 | 0.213969E+10 | 1466.95 | 01-NOV-07:10 |
December | 0.786159E+09 | 1127.77 | 01-DEC-16:30 | 0.215612E+10 | 1466.95 | 01-DEC-08:09 |
Annual Sum or Average | 0.894894E+10 | 0.259981E+11 | ||||
Minimum of Months | 0.687318E+09 | 692.79 | 0.198155E+10 | 1466.95 | ||
Maximum of Months | 0.804704E+09 | 1127.77 | 0.227025E+10 | 1466.95 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123090E+10 | 1750.04 | 02-JAN-16:40 | 0.339723E+10 | 2276.35 | 02-JAN-08:09 |
February | 0.107084E+10 | 1628.89 | 15-FEB-16:00 | 0.307490E+10 | 2276.35 | 01-FEB-08:09 |
March | 0.123214E+10 | 1319.38 | 16-MAR-07:10 | 0.352288E+10 | 2276.35 | 01-MAR-08:09 |
April | 0.107902E+10 | 1075.05 | 03-APR-07:10 | 0.328113E+10 | 2276.35 | 03-APR-07:10 |
May | 0.114883E+10 | 1075.05 | 01-MAY-07:10 | 0.346006E+10 | 2276.35 | 01-MAY-07:10 |
June | 0.113399E+10 | 1075.05 | 01-JUN-07:10 | 0.339359E+10 | 2276.35 | 01-JUN-07:10 |
July | 0.106661E+10 | 1075.05 | 03-JUL-07:10 | 0.334669E+10 | 2276.35 | 03-JUL-07:10 |
August | 0.119653E+10 | 1075.05 | 01-AUG-07:10 | 0.352288E+10 | 2276.35 | 01-AUG-07:10 |
September | 0.108927E+10 | 1276.50 | 27-SEP-07:10 | 0.327931E+10 | 2276.35 | 01-SEP-07:10 |
October | 0.115453E+10 | 1460.67 | 31-OCT-15:00 | 0.339814E+10 | 2276.35 | 02-OCT-07:10 |
November | 0.120189E+10 | 1750.04 | 06-NOV-16:49 | 0.332029E+10 | 2276.35 | 01-NOV-07:10 |
December | 0.119915E+10 | 1750.04 | 01-DEC-16:30 | 0.334578E+10 | 2276.35 | 01-DEC-08:09 |
Annual Sum or Average | 0.138037E+11 | 0.403429E+11 | ||||
Minimum of Months | 0.106661E+10 | 1075.05 | 0.307490E+10 | 2276.35 | ||
Maximum of Months | 0.123214E+10 | 1750.04 | 0.352288E+10 | 2276.35 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.797475E+09 | 1127.77 | 02-JAN-16:40 | 0.218926E+10 | 1466.94 | 02-JAN-08:09 |
February | 0.692851E+09 | 1043.66 | 15-FEB-16:00 | 0.198154E+10 | 1466.94 | 01-FEB-08:09 |
March | 0.794228E+09 | 897.38 | 16-MAR-07:10 | 0.227023E+10 | 1466.94 | 01-MAR-08:09 |
April | 0.694978E+09 | 797.10 | 14-APR-07:10 | 0.211444E+10 | 1466.94 | 03-APR-07:10 |
May | 0.737957E+09 | 692.79 | 01-MAY-07:10 | 0.222974E+10 | 1466.94 | 01-MAY-07:10 |
June | 0.728019E+09 | 692.79 | 01-JUN-07:10 | 0.218691E+10 | 1466.94 | 01-JUN-07:10 |
July | 0.685277E+09 | 692.79 | 03-JUL-07:10 | 0.215669E+10 | 1466.94 | 03-JUL-07:10 |
August | 0.769437E+09 | 776.76 | 16-AUG-07:10 | 0.227023E+10 | 1466.94 | 01-AUG-07:10 |
September | 0.702412E+09 | 870.78 | 27-SEP-07:10 | 0.211327E+10 | 1466.94 | 01-SEP-07:10 |
October | 0.745162E+09 | 942.95 | 06-OCT-07:10 | 0.218984E+10 | 1466.94 | 02-OCT-07:10 |
November | 0.776175E+09 | 1127.77 | 06-NOV-16:49 | 0.213967E+10 | 1466.94 | 01-NOV-07:10 |
December | 0.781167E+09 | 1127.77 | 01-DEC-16:30 | 0.215610E+10 | 1466.94 | 01-DEC-08:09 |
Annual Sum or Average | 0.890514E+10 | 0.259979E+11 | ||||
Minimum of Months | 0.685277E+09 | 692.79 | 0.198154E+10 | 1466.94 | ||
Maximum of Months | 0.797475E+09 | 1127.77 | 0.227023E+10 | 1466.94 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.125888E+10 | 1750.00 | 02-JAN-16:40 | 0.339718E+10 | 2276.32 | 02-JAN-08:09 |
February | 0.108831E+10 | 1636.72 | 01-FEB-16:00 | 0.307485E+10 | 2276.32 | 01-FEB-08:09 |
March | 0.123827E+10 | 1415.71 | 02-MAR-16:00 | 0.352283E+10 | 2276.32 | 01-MAR-08:09 |
April | 0.107755E+10 | 1075.02 | 03-APR-07:10 | 0.328108E+10 | 2276.32 | 03-APR-07:10 |
May | 0.114505E+10 | 1075.02 | 01-MAY-07:10 | 0.346000E+10 | 2276.32 | 01-MAY-07:10 |
June | 0.112911E+10 | 1075.02 | 01-JUN-07:10 | 0.339353E+10 | 2276.32 | 01-JUN-07:10 |
July | 0.106247E+10 | 1075.02 | 03-JUL-07:10 | 0.334664E+10 | 2276.32 | 03-JUL-07:10 |
August | 0.119361E+10 | 1075.02 | 01-AUG-07:10 | 0.352283E+10 | 2276.32 | 01-AUG-07:10 |
September | 0.109095E+10 | 1307.08 | 27-SEP-07:10 | 0.327926E+10 | 2276.32 | 01-SEP-07:10 |
October | 0.116409E+10 | 1495.32 | 31-OCT-15:00 | 0.339809E+10 | 2276.32 | 02-OCT-07:10 |
November | 0.121798E+10 | 1750.00 | 06-NOV-16:49 | 0.332024E+10 | 2276.32 | 01-NOV-07:10 |
December | 0.123696E+10 | 1750.00 | 01-DEC-16:30 | 0.334573E+10 | 2276.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.139032E+11 | 0.403423E+11 | ||||
Minimum of Months | 0.106247E+10 | 1075.02 | 0.307485E+10 | 2276.32 | ||
Maximum of Months | 0.125888E+10 | 1750.00 | 0.352283E+10 | 2276.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.804698E+09 | 1127.77 | 02-JAN-16:40 | 0.218927E+10 | 1466.95 | 02-JAN-08:09 |
February | 0.698388E+09 | 1061.80 | 01-FEB-16:00 | 0.198155E+10 | 1466.95 | 01-FEB-08:09 |
March | 0.798113E+09 | 975.96 | 02-MAR-16:00 | 0.227025E+10 | 1466.95 | 01-MAR-08:09 |
April | 0.695757E+09 | 692.79 | 03-APR-07:10 | 0.211446E+10 | 1466.95 | 03-APR-07:10 |
May | 0.740533E+09 | 692.79 | 01-MAY-07:10 | 0.222976E+10 | 1466.95 | 01-MAY-07:10 |
June | 0.730759E+09 | 692.79 | 01-JUN-07:10 | 0.218692E+10 | 1466.95 | 01-JUN-07:10 |
July | 0.687315E+09 | 692.79 | 03-JUL-07:10 | 0.215670E+10 | 1466.95 | 03-JUL-07:10 |
August | 0.771552E+09 | 692.79 | 01-AUG-07:10 | 0.227025E+10 | 1466.95 | 01-AUG-07:10 |
September | 0.703288E+09 | 692.79 | 01-SEP-07:10 | 0.211328E+10 | 1466.95 | 01-SEP-07:10 |
October | 0.749464E+09 | 966.99 | 31-OCT-15:00 | 0.218986E+10 | 1466.95 | 02-OCT-07:10 |
November | 0.782914E+09 | 1127.77 | 06-NOV-16:49 | 0.213969E+10 | 1466.95 | 01-NOV-07:10 |
December | 0.786163E+09 | 1127.77 | 01-DEC-16:30 | 0.215612E+10 | 1466.95 | 01-DEC-08:09 |
Annual Sum or Average | 0.894894E+10 | 0.259981E+11 | ||||
Minimum of Months | 0.687315E+09 | 692.79 | 0.198155E+10 | 1466.95 | ||
Maximum of Months | 0.804698E+09 | 1127.77 | 0.227025E+10 | 1466.95 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123090E+10 | 1750.04 | 02-JAN-16:40 | 0.339723E+10 | 2276.35 | 02-JAN-08:09 |
February | 0.107084E+10 | 1628.78 | 15-FEB-16:00 | 0.307490E+10 | 2276.35 | 01-FEB-08:09 |
March | 0.123213E+10 | 1319.06 | 16-MAR-07:10 | 0.352288E+10 | 2276.35 | 01-MAR-08:09 |
April | 0.107902E+10 | 1075.05 | 03-APR-07:10 | 0.328113E+10 | 2276.35 | 03-APR-07:10 |
May | 0.114883E+10 | 1075.05 | 01-MAY-07:10 | 0.346006E+10 | 2276.35 | 01-MAY-07:10 |
June | 0.113398E+10 | 1075.05 | 01-JUN-07:10 | 0.339359E+10 | 2276.35 | 01-JUN-07:10 |
July | 0.106658E+10 | 1075.05 | 03-JUL-07:10 | 0.334669E+10 | 2276.35 | 03-JUL-07:10 |
August | 0.119653E+10 | 1075.05 | 01-AUG-07:10 | 0.352288E+10 | 2276.35 | 01-AUG-07:10 |
September | 0.108926E+10 | 1276.12 | 27-SEP-07:10 | 0.327931E+10 | 2276.35 | 01-SEP-07:10 |
October | 0.115453E+10 | 1460.45 | 31-OCT-15:00 | 0.339814E+10 | 2276.35 | 02-OCT-07:10 |
November | 0.120189E+10 | 1750.04 | 06-NOV-16:49 | 0.332029E+10 | 2276.35 | 01-NOV-07:10 |
December | 0.119915E+10 | 1750.04 | 01-DEC-16:30 | 0.334578E+10 | 2276.35 | 01-DEC-08:09 |
Annual Sum or Average | 0.138036E+11 | 0.403429E+11 | ||||
Minimum of Months | 0.106658E+10 | 1075.05 | 0.307490E+10 | 2276.35 | ||
Maximum of Months | 0.123213E+10 | 1750.04 | 0.352288E+10 | 2276.35 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.797433E+09 | 1127.77 | 02-JAN-16:40 | 0.218926E+10 | 1466.94 | 02-JAN-08:09 |
February | 0.692815E+09 | 1043.60 | 15-FEB-16:00 | 0.198154E+10 | 1466.94 | 01-FEB-08:09 |
March | 0.794229E+09 | 897.18 | 16-MAR-07:10 | 0.227023E+10 | 1466.94 | 01-MAR-08:09 |
April | 0.694977E+09 | 796.91 | 14-APR-07:10 | 0.211444E+10 | 1466.94 | 03-APR-07:10 |
May | 0.737958E+09 | 692.79 | 01-MAY-07:10 | 0.222974E+10 | 1466.94 | 01-MAY-07:10 |
June | 0.728018E+09 | 692.79 | 01-JUN-07:10 | 0.218691E+10 | 1466.94 | 01-JUN-07:10 |
July | 0.685279E+09 | 692.79 | 03-JUL-07:10 | 0.215669E+10 | 1466.94 | 03-JUL-07:10 |
August | 0.769441E+09 | 776.43 | 16-AUG-07:10 | 0.227023E+10 | 1466.94 | 01-AUG-07:10 |
September | 0.702411E+09 | 870.55 | 27-SEP-07:10 | 0.211327E+10 | 1466.94 | 01-SEP-07:10 |
October | 0.745162E+09 | 942.77 | 06-OCT-07:10 | 0.218984E+10 | 1466.94 | 02-OCT-07:10 |
November | 0.776176E+09 | 1127.77 | 06-NOV-16:49 | 0.213967E+10 | 1466.94 | 01-NOV-07:10 |
December | 0.781173E+09 | 1127.77 | 01-DEC-16:30 | 0.215610E+10 | 1466.94 | 01-DEC-08:09 |
Annual Sum or Average | 0.890507E+10 | 0.259979E+11 | ||||
Minimum of Months | 0.685279E+09 | 692.79 | 0.198154E+10 | 1466.94 | ||
Maximum of Months | 0.797433E+09 | 1127.77 | 0.227023E+10 | 1466.94 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.387117E+09 | 405.10 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.351144E+09 | 405.10 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.417256E+09 | 405.10 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.372695E+09 | 405.10 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.402187E+09 | 405.10 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.400242E+09 | 405.10 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.374640E+09 | 405.10 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.417256E+09 | 405.10 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.372695E+09 | 405.10 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.387117E+09 | 405.10 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.382580E+09 | 405.10 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.374640E+09 | 405.10 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.463957E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.351144E+09 | 405.10 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.417256E+09 | 405.10 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.387117E+09 | 405.10 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.351144E+09 | 405.10 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.417256E+09 | 405.10 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.372695E+09 | 405.10 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.402187E+09 | 405.10 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.400242E+09 | 405.10 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.374640E+09 | 405.10 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.417256E+09 | 405.10 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.372695E+09 | 405.10 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.387117E+09 | 405.10 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.382580E+09 | 405.10 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.374640E+09 | 405.10 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.463957E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.351144E+09 | 405.10 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.417256E+09 | 405.10 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.387117E+09 | 405.10 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.351144E+09 | 405.10 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.417256E+09 | 405.10 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.372695E+09 | 405.10 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.402187E+09 | 405.10 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.400242E+09 | 405.10 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.374640E+09 | 405.10 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.417256E+09 | 405.10 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.372695E+09 | 405.10 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.387117E+09 | 405.10 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.382580E+09 | 405.10 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.374640E+09 | 405.10 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.463957E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.351144E+09 | 405.10 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.417256E+09 | 405.10 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.418155E+10 | 4375.82 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.379298E+10 | 4375.82 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.450711E+10 | 4375.82 | 01-MAR-08:09 | 0.762947E+12 | 379632.52 | 31-MAR-23:10 |
April | 0.402577E+10 | 4375.82 | 03-APR-07:10 | 0.982982E+12 | 379632.52 | 01-APR-00:10 |
May | 0.434433E+10 | 4375.82 | 01-MAY-07:10 | 0.254544E+12 | 189816.26 | 31-MAY-23:10 |
June | 0.432333E+10 | 4375.82 | 01-JUN-07:10 | 0.492345E+12 | 284724.39 | 30-JUN-23:10 |
July | 0.404678E+10 | 4375.82 | 03-JUL-07:10 | 0.762947E+12 | 379632.52 | 31-JUL-23:10 |
August | 0.450711E+10 | 4375.82 | 01-AUG-07:10 | 0.101578E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.402577E+10 | 4375.82 | 01-SEP-07:10 | 0.246344E+12 | 189816.26 | 30-SEP-23:10 |
October | 0.418155E+10 | 4375.82 | 02-OCT-07:10 | 0.508746E+12 | 284724.39 | 31-OCT-23:10 |
November | 0.413254E+10 | 4375.82 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.404678E+10 | 4375.82 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.501156E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.379298E+10 | 4375.82 | 0.246344E+12 | 94908.13 | ||
Maximum of Months | 0.450711E+10 | 4375.82 | 0.101681E+13 | 379632.52 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.148304E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.134523E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.159851E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.142779E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.154078E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.153333E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.143524E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.159851E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.142779E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.148304E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.146566E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.143524E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.177742E+12 | 0.424397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121482E+11 | 0.134523E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.159851E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.133188E+11 | 0.270551E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.120811E+11 | 0.244881E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.143557E+11 | 0.280558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.128226E+11 | 0.261305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.138373E+11 | 0.275555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.137704E+11 | 0.270261E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.128895E+11 | 0.266527E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.143557E+11 | 0.280558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.128226E+11 | 0.261160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.133188E+11 | 0.270624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.131627E+11 | 0.264424E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.128895E+11 | 0.266454E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.159625E+12 | 0.321286E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.120811E+11 | 0.244881E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.143557E+11 | 0.280558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.133188E+11 | 0.270550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.120811E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.143557E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.128226E+11 | 0.261304E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.138373E+11 | 0.275554E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.137704E+11 | 0.270260E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.128895E+11 | 0.266526E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.143557E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.128226E+11 | 0.261159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.133188E+11 | 0.270623E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.131627E+11 | 0.264423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.128895E+11 | 0.266453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.159625E+12 | 0.321285E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.120811E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.143557E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.133188E+11 | 0.270550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.120811E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.143557E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.128226E+11 | 0.261304E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.138373E+11 | 0.275554E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.137704E+11 | 0.270260E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.128895E+11 | 0.266526E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.143557E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.128226E+11 | 0.261159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.133188E+11 | 0.270623E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.131627E+11 | 0.264423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.128895E+11 | 0.266453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.159625E+12 | 0.321285E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.120811E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.143557E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.125601E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146822E+10 |
February | 0.136985E+10 | 0.108653E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128944E+10 |
March | 0.163685E+10 | 0.123764E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108059E+10 |
April | 0.145243E+10 | 0.107705E+10 | 0.328108E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 503445.29 | 0.724671E+09 |
May | 0.157338E+10 | 0.114469E+10 | 0.346000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2451720.96 | 0.409631E+09 |
June | 0.156900E+10 | 0.112873E+10 | 0.339353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17095056.48 | 0.203270E+09 |
July | 0.145680E+10 | 0.106210E+10 | 0.334664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41619808.60 | 57892889.78 |
August | 0.163685E+10 | 0.119334E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50670018.09 | 77094173.95 |
September | 0.145243E+10 | 0.109024E+10 | 0.327926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5864698.84 | 0.223834E+09 |
October | 0.150991E+10 | 0.116309E+10 | 0.339809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 95394.76 | 0.567994E+09 |
November | 0.149516E+10 | 0.121639E+10 | 0.332024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109061E+10 |
December | 0.145680E+10 | 0.123376E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130090E+10 |
Annual Sum or Average | 0.181194E+11 | 0.138896E+11 | 0.403423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118300E+09 | 0.849414E+10 |
Minimum of Months | 0.136985E+10 | 0.106210E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57892889.78 |
Maximum of Months | 0.163685E+10 | 0.125601E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50670018.09 | 0.146822E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.804202E+09 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.974278E+09 |
February | 0.882782E+09 | 0.698040E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.862549E+09 |
March | 0.105485E+10 | 0.797944E+09 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.711227E+09 |
April | 0.936002E+09 | 0.695582E+09 | 0.211446E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 335608.87 | 0.474484E+09 |
May | 0.101394E+10 | 0.740418E+09 | 0.222976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1286464.60 | 0.273781E+09 |
June | 0.101113E+10 | 0.730635E+09 | 0.218692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11651618.74 | 0.130005E+09 |
July | 0.938820E+09 | 0.687186E+09 | 0.215670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29623575.80 | 31552260.46 |
August | 0.105485E+10 | 0.771443E+09 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35977903.91 | 44530025.91 |
September | 0.936002E+09 | 0.703077E+09 | 0.211328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3857294.14 | 0.150909E+09 |
October | 0.973041E+09 | 0.749140E+09 | 0.218986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63586.01 | 0.378198E+09 |
November | 0.963541E+09 | 0.782643E+09 | 0.213969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.715894E+09 |
December | 0.938820E+09 | 0.785576E+09 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.848280E+09 |
Annual Sum or Average | 0.116768E+11 | 0.894589E+10 | 0.259981E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 82796052.07 | 0.559569E+10 |
Minimum of Months | 0.882782E+09 | 0.687186E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31552260.46 |
Maximum of Months | 0.105485E+10 | 0.804202E+09 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35977903.91 | 0.974278E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.122940E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145778E+10 |
February | 0.136988E+10 | 0.107000E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131391E+10 |
March | 0.163688E+10 | 0.123291E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108067E+10 |
April | 0.145246E+10 | 0.107845E+10 | 0.328113E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 498117.80 | 0.719422E+09 |
May | 0.157341E+10 | 0.114844E+10 | 0.346006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1883772.63 | 0.408907E+09 |
June | 0.156904E+10 | 0.113347E+10 | 0.339359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16077201.79 | 0.204197E+09 |
July | 0.145684E+10 | 0.106607E+10 | 0.334669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39615887.46 | 60683516.46 |
August | 0.163688E+10 | 0.119615E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48371253.45 | 83376724.38 |
September | 0.145246E+10 | 0.108863E+10 | 0.327931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5704137.08 | 0.238315E+09 |
October | 0.150994E+10 | 0.115388E+10 | 0.339814E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 85504.12 | 0.599041E+09 |
November | 0.149520E+10 | 0.120121E+10 | 0.332029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108635E+10 |
December | 0.145684E+10 | 0.119793E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129389E+10 |
Annual Sum or Average | 0.181198E+11 | 0.137965E+11 | 0.403429E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112236E+09 | 0.854654E+10 |
Minimum of Months | 0.136988E+10 | 0.106607E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60683516.46 |
Maximum of Months | 0.163688E+10 | 0.123291E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48371253.45 | 0.145778E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.796967E+09 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102429E+10 |
February | 0.882782E+09 | 0.692505E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.917519E+09 |
March | 0.105485E+10 | 0.793991E+09 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.793742E+09 |
April | 0.936002E+09 | 0.694811E+09 | 0.211444E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 328137.21 | 0.548358E+09 |
May | 0.101394E+10 | 0.737878E+09 | 0.222974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1560069.05 | 0.298540E+09 |
June | 0.101113E+10 | 0.727940E+09 | 0.218691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10415386.31 | 0.160846E+09 |
July | 0.938820E+09 | 0.685157E+09 | 0.215669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24321562.08 | 57840852.58 |
August | 0.105485E+10 | 0.769291E+09 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29301814.36 | 73035914.82 |
September | 0.936002E+09 | 0.702154E+09 | 0.211327E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3831605.72 | 0.170012E+09 |
October | 0.973041E+09 | 0.744930E+09 | 0.218984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63608.04 | 0.422803E+09 |
November | 0.963541E+09 | 0.775868E+09 | 0.213967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.797943E+09 |
December | 0.938820E+09 | 0.780572E+09 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.962742E+09 |
Annual Sum or Average | 0.116768E+11 | 0.890206E+10 | 0.259979E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 69822182.75 | 0.622768E+10 |
Minimum of Months | 0.882782E+09 | 0.685157E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57840852.58 |
Maximum of Months | 0.105485E+10 | 0.796967E+09 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29301814.36 | 0.102429E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.125892E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.301128E+10 |
February | 0.136985E+10 | 0.108831E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.268036E+10 |
March | 0.163685E+10 | 0.123829E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217705E+10 |
April | 0.145243E+10 | 0.107756E+10 | 0.328108E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1110854.42 | 0.146185E+10 |
May | 0.157338E+10 | 0.114505E+10 | 0.346000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6627531.52 | 0.884710E+09 |
June | 0.156900E+10 | 0.112912E+10 | 0.339353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39363339.57 | 0.463599E+09 |
July | 0.145680E+10 | 0.106248E+10 | 0.334664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 91613093.03 | 0.163732E+09 |
August | 0.163685E+10 | 0.119361E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110156E+09 | 0.210613E+09 |
September | 0.145243E+10 | 0.109095E+10 | 0.327926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13442186.47 | 0.479251E+09 |
October | 0.150991E+10 | 0.116409E+10 | 0.339809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 173082.75 | 0.115964E+10 |
November | 0.149516E+10 | 0.121799E+10 | 0.332024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212695E+10 |
December | 0.145680E+10 | 0.123696E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.256091E+10 |
Annual Sum or Average | 0.181194E+11 | 0.139033E+11 | 0.403423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.262486E+09 | 0.173799E+11 |
Minimum of Months | 0.136985E+10 | 0.106248E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163732E+09 |
Maximum of Months | 0.163685E+10 | 0.125892E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110156E+09 | 0.301128E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.804704E+09 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201451E+10 |
February | 0.649041E+09 | 0.698386E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181152E+10 |
March | 0.773965E+09 | 0.798111E+09 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148164E+10 |
April | 0.688021E+09 | 0.695759E+09 | 0.211446E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 735169.11 | 0.101761E+10 |
May | 0.744847E+09 | 0.740533E+09 | 0.222976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2876536.26 | 0.605913E+09 |
June | 0.742030E+09 | 0.730761E+09 | 0.218692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25180801.47 | 0.315355E+09 |
July | 0.690839E+09 | 0.687318E+09 | 0.215670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59072412.56 | 0.112840E+09 |
August | 0.773965E+09 | 0.771545E+09 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70708765.73 | 0.148748E+09 |
September | 0.688021E+09 | 0.703288E+09 | 0.211328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8549665.79 | 0.338959E+09 |
October | 0.715730E+09 | 0.749457E+09 | 0.218986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 115285.96 | 0.807795E+09 |
November | 0.708685E+09 | 0.782917E+09 | 0.213969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144450E+10 |
December | 0.690839E+09 | 0.786159E+09 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172233E+10 |
Annual Sum or Average | 0.858171E+10 | 0.894894E+10 | 0.259981E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167239E+09 | 0.118217E+11 |
Minimum of Months | 0.649041E+09 | 0.687318E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112840E+09 |
Maximum of Months | 0.773965E+09 | 0.804704E+09 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70708765.73 | 0.201451E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.123090E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.312588E+10 |
February | 0.136988E+10 | 0.107084E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.285859E+10 |
March | 0.163688E+10 | 0.123214E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233354E+10 |
April | 0.145246E+10 | 0.107902E+10 | 0.328113E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1082193.39 | 0.155723E+10 |
May | 0.157341E+10 | 0.114883E+10 | 0.346006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4357435.75 | 0.913770E+09 |
June | 0.156904E+10 | 0.113399E+10 | 0.339359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36158703.50 | 0.473901E+09 |
July | 0.145684E+10 | 0.106661E+10 | 0.334669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 86103169.03 | 0.174865E+09 |
August | 0.163688E+10 | 0.119653E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102882E+09 | 0.234415E+09 |
September | 0.145246E+10 | 0.108927E+10 | 0.327931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12666392.19 | 0.543624E+09 |
October | 0.150994E+10 | 0.115453E+10 | 0.339814E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 103521.65 | 0.133903E+10 |
November | 0.149520E+10 | 0.120189E+10 | 0.332029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230243E+10 |
December | 0.145684E+10 | 0.119915E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.274019E+10 |
Annual Sum or Average | 0.181198E+11 | 0.138037E+11 | 0.403429E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.243354E+09 | 0.185975E+11 |
Minimum of Months | 0.136988E+10 | 0.106661E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174865E+09 |
Maximum of Months | 0.163688E+10 | 0.123214E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102882E+09 | 0.312588E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.797475E+09 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205721E+10 |
February | 0.882782E+09 | 0.692851E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184467E+10 |
March | 0.105485E+10 | 0.794228E+09 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154566E+10 |
April | 0.936002E+09 | 0.694978E+09 | 0.211444E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 739105.15 | 0.105257E+10 |
May | 0.101394E+10 | 0.737957E+09 | 0.222974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4012964.28 | 0.633626E+09 |
June | 0.101113E+10 | 0.728019E+09 | 0.218691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24457109.18 | 0.346785E+09 |
July | 0.938820E+09 | 0.685277E+09 | 0.215669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57867822.38 | 0.138926E+09 |
August | 0.105485E+10 | 0.769437E+09 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69014510.27 | 0.170821E+09 |
September | 0.936002E+09 | 0.702412E+09 | 0.211327E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8707292.40 | 0.353203E+09 |
October | 0.973041E+09 | 0.745162E+09 | 0.218984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 115423.07 | 0.842948E+09 |
November | 0.963541E+09 | 0.776175E+09 | 0.213967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146697E+10 |
December | 0.938820E+09 | 0.781167E+09 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177089E+10 |
Annual Sum or Average | 0.116768E+11 | 0.890514E+10 | 0.259979E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164914E+09 | 0.122243E+11 |
Minimum of Months | 0.882782E+09 | 0.685277E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138926E+09 |
Maximum of Months | 0.105485E+10 | 0.797475E+09 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69014510.27 | 0.205721E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.125888E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.362620E+10 |
February | 0.136985E+10 | 0.108831E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.320654E+10 |
March | 0.163685E+10 | 0.123827E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251018E+10 |
April | 0.145243E+10 | 0.107755E+10 | 0.328108E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1310253.39 | 0.165614E+10 |
May | 0.157338E+10 | 0.114505E+10 | 0.346000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6759830.70 | 0.103955E+10 |
June | 0.156900E+10 | 0.112911E+10 | 0.339353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44325626.91 | 0.577383E+09 |
July | 0.145680E+10 | 0.106247E+10 | 0.334664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103976E+09 | 0.217905E+09 |
August | 0.163685E+10 | 0.119361E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130213E+09 | 0.265881E+09 |
September | 0.145243E+10 | 0.109095E+10 | 0.327926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15558888.51 | 0.567127E+09 |
October | 0.150991E+10 | 0.116409E+10 | 0.339809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 160899.82 | 0.129943E+10 |
November | 0.149516E+10 | 0.121798E+10 | 0.332024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238749E+10 |
December | 0.145680E+10 | 0.123696E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.297353E+10 |
Annual Sum or Average | 0.181194E+11 | 0.139032E+11 | 0.403423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.302305E+09 | 0.203273E+11 |
Minimum of Months | 0.136985E+10 | 0.106247E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217905E+09 |
Maximum of Months | 0.163685E+10 | 0.125888E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130213E+09 | 0.362620E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.804698E+09 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242738E+10 |
February | 0.882782E+09 | 0.698388E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216229E+10 |
March | 0.105485E+10 | 0.798113E+09 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170846E+10 |
April | 0.936002E+09 | 0.695757E+09 | 0.211446E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 850331.76 | 0.116614E+10 |
May | 0.101394E+10 | 0.740533E+09 | 0.222976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3328268.80 | 0.720625E+09 |
June | 0.101113E+10 | 0.730759E+09 | 0.218692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29087548.77 | 0.395119E+09 |
July | 0.938820E+09 | 0.687315E+09 | 0.215670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68232329.55 | 0.149802E+09 |
August | 0.105485E+10 | 0.771552E+09 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84223138.41 | 0.188893E+09 |
September | 0.936002E+09 | 0.703288E+09 | 0.211328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10102336.33 | 0.407369E+09 |
October | 0.973041E+09 | 0.749464E+09 | 0.218986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 107230.26 | 0.922501E+09 |
November | 0.963541E+09 | 0.782914E+09 | 0.213969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162285E+10 |
December | 0.938820E+09 | 0.786163E+09 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199862E+10 |
Annual Sum or Average | 0.116768E+11 | 0.894894E+10 | 0.259981E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195931E+09 | 0.138700E+11 |
Minimum of Months | 0.882782E+09 | 0.687315E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149802E+09 |
Maximum of Months | 0.105485E+10 | 0.804698E+09 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84223138.41 | 0.242738E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.123090E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.372027E+10 |
February | 0.136988E+10 | 0.107084E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.336447E+10 |
March | 0.163688E+10 | 0.123213E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.268432E+10 |
April | 0.145246E+10 | 0.107902E+10 | 0.328113E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1274171.22 | 0.177530E+10 |
May | 0.157341E+10 | 0.114883E+10 | 0.346006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5018230.52 | 0.107566E+10 |
June | 0.156904E+10 | 0.113398E+10 | 0.339359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42830009.06 | 0.588042E+09 |
July | 0.145684E+10 | 0.106658E+10 | 0.334669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101217E+09 | 0.228264E+09 |
August | 0.163688E+10 | 0.119653E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123363E+09 | 0.295769E+09 |
September | 0.145246E+10 | 0.108926E+10 | 0.327931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15047560.57 | 0.651163E+09 |
October | 0.150994E+10 | 0.115453E+10 | 0.339814E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 137156.23 | 0.155253E+10 |
November | 0.149520E+10 | 0.120189E+10 | 0.332029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.257022E+10 |
December | 0.145684E+10 | 0.119915E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.314008E+10 |
Annual Sum or Average | 0.181198E+11 | 0.138036E+11 | 0.403429E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288887E+09 | 0.216461E+11 |
Minimum of Months | 0.136988E+10 | 0.106658E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228264E+09 |
Maximum of Months | 0.163688E+10 | 0.123213E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123363E+09 | 0.372027E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.797433E+09 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246061E+10 |
February | 0.882782E+09 | 0.692815E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220320E+10 |
March | 0.105485E+10 | 0.794229E+09 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179596E+10 |
April | 0.936002E+09 | 0.694977E+09 | 0.211444E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 872531.77 | 0.121695E+10 |
May | 0.101394E+10 | 0.737958E+09 | 0.222974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4567106.96 | 0.752115E+09 |
June | 0.101113E+10 | 0.728018E+09 | 0.218691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28948484.75 | 0.429964E+09 |
July | 0.938820E+09 | 0.685279E+09 | 0.215669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68441439.90 | 0.177750E+09 |
August | 0.105485E+10 | 0.769441E+09 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 82996474.87 | 0.214103E+09 |
September | 0.936002E+09 | 0.702411E+09 | 0.211327E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10258575.96 | 0.422921E+09 |
October | 0.973041E+09 | 0.745162E+09 | 0.218984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 107310.36 | 0.972152E+09 |
November | 0.963541E+09 | 0.776176E+09 | 0.213967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166415E+10 |
December | 0.938820E+09 | 0.781173E+09 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205522E+10 |
Annual Sum or Average | 0.116768E+11 | 0.890507E+10 | 0.259979E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196192E+09 | 0.143651E+11 |
Minimum of Months | 0.882782E+09 | 0.685279E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177750E+09 |
Maximum of Months | 0.105485E+10 | 0.797433E+09 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 82996474.87 | 0.246061E+10 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.387117E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.351144E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.417256E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.372695E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.402187E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.400242E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.374640E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.417256E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.372695E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.387117E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.382580E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.374640E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.463957E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.351144E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.417256E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.387117E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.351144E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.417256E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.372695E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.402187E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.400242E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.374640E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.417256E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.372695E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.387117E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.382580E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.374640E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.463957E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.351144E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.417256E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.387117E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.351144E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.417256E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.372695E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.402187E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.400242E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.374640E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.417256E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.372695E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.387117E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.382580E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.374640E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.463957E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.351144E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.417256E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.377547E+10 | 0.418155E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.342526E+10 | 0.379298E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409289E+10 | 0.450711E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363176E+10 | 0.402577E+10 | 0.982982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.393418E+10 | 0.434433E+10 | 0.254544E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.392325E+10 | 0.432333E+10 | 0.492345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.364269E+10 | 0.404678E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.409289E+10 | 0.450711E+10 | 0.101578E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.363176E+10 | 0.402577E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.377547E+10 | 0.418155E+10 | 0.508746E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373861E+10 | 0.413254E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364269E+10 | 0.404678E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453069E+11 | 0.501156E+11 | 0.749486E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.342526E+10 | 0.379298E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.409289E+10 | 0.450711E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.316667E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.279099E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230406E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 677907.87 | 0.153789E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4508646.44 | 0.860409E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28637630.65 | 0.430084E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72206944.74 | 0.131975E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83036159.30 | 0.181626E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7998683.05 | 0.477058E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17130.84 | 0.122311E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233191E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.280962E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197083E+09 | 0.182454E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131975E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83036159.30 | 0.316667E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.507263E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.460890E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.382398E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1378863.11 | 0.256118E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9860519.94 | 0.148804E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52532241.47 | 0.756081E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128922E+09 | 0.242696E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146116E+09 | 0.337426E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14167532.58 | 0.826737E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40056.66 | 0.208584E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.381567E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.454037E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.353017E+09 | 0.301596E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242696E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146116E+09 | 0.507263E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.534927E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.481262E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.399213E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 338521.18 | 0.269474E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3314314.36 | 0.168278E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39482277.37 | 0.917546E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96715867.03 | 0.335862E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131172E+09 | 0.408953E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11597306.12 | 0.929970E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217994E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.379009E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.453793E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.282621E+09 | 0.316318E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.335862E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131172E+09 | 0.534927E+10 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 15519.45 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 15519.45 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 15519.45 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 15519.45 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 15519.45 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 15519.45 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 15519.45 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 15519.45 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 15519.45 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 15519.45 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 15519.45 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 15519.45 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 17832.21 | 15519.45 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 15519.45 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 13937.56 | 02-JAN-08:09 | 18128.59 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 13937.56 | 01-FEB-08:09 | 18128.59 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 13937.56 | 01-MAR-08:09 | 18128.59 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 13937.56 | 03-APR-07:10 | 18128.59 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 13937.56 | 01-MAY-07:10 | 18128.59 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 13937.56 | 01-JUN-07:10 | 18128.59 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 13937.56 | 03-JUL-07:10 | 18128.59 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 13937.56 | 01-AUG-07:10 | 18128.59 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 13937.56 | 01-SEP-07:10 | 18128.59 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 13937.56 | 02-OCT-07:10 | 18128.59 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 13937.56 | 01-NOV-07:10 | 18128.59 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 13937.56 | 01-DEC-08:09 | 18128.59 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 13937.56 | 18128.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 13937.56 | 18128.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 13937.56 | 02-JAN-08:09 | 18128.52 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 13937.56 | 01-FEB-08:09 | 18128.52 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 13937.56 | 01-MAR-08:09 | 18128.52 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 13937.56 | 03-APR-07:10 | 18128.52 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 13937.56 | 01-MAY-07:10 | 18128.52 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 13937.56 | 01-JUN-07:10 | 18128.52 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 13937.56 | 03-JUL-07:10 | 18128.52 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 13937.56 | 01-AUG-07:10 | 18128.52 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 13937.56 | 01-SEP-07:10 | 18128.52 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 13937.56 | 02-OCT-07:10 | 18128.52 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 13937.56 | 01-NOV-07:10 | 18128.52 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 13937.56 | 01-DEC-08:09 | 18128.52 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 13937.56 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 13937.56 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 13937.56 | 02-JAN-08:09 | 18128.52 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 13937.56 | 01-FEB-08:09 | 18128.52 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 13937.56 | 01-MAR-08:09 | 18128.52 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 13937.56 | 03-APR-07:10 | 18128.52 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 13937.56 | 01-MAY-07:10 | 18128.52 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 13937.56 | 01-JUN-07:10 | 18128.52 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 13937.56 | 03-JUL-07:10 | 18128.52 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 13937.56 | 01-AUG-07:10 | 18128.52 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 13937.56 | 01-SEP-07:10 | 18128.52 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 13937.56 | 02-OCT-07:10 | 18128.52 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 13937.56 | 01-NOV-07:10 | 18128.52 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 13937.56 | 01-DEC-08:09 | 18128.52 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 13937.56 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 13937.56 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1750.00 | 02-JAN-16:40 | 2276.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 2475.63 | 31-JAN-01:00 |
February | 2010.79 | 01-FEB-10:09 | 1633.24 | 01-FEB-16:00 | 2276.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2472.69 | 06-FEB-00:51 |
March | 2010.79 | 01-MAR-10:09 | 1405.53 | 02-MAR-16:00 | 2276.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1941.15 | 12-MAR-10:00 |
April | 2010.79 | 03-APR-09:09 | 1075.02 | 03-APR-07:10 | 2276.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.53 | 07-APR-13:00 | 1530.36 | 11-APR-03:53 |
May | 2010.79 | 01-MAY-09:09 | 1075.02 | 01-MAY-07:10 | 2276.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 118.65 | 29-MAY-12:00 | 924.42 | 03-MAY-04:00 |
June | 2010.79 | 01-JUN-09:09 | 1075.02 | 01-JUN-07:10 | 2276.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 198.52 | 19-JUN-21:02 | 522.61 | 02-JUN-22:00 |
July | 2010.79 | 03-JUL-09:09 | 1075.02 | 03-JUL-07:10 | 2276.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 205.52 | 09-JUL-14:00 | 220.59 | 11-JUL-04:50 |
August | 2010.79 | 01-AUG-09:09 | 1075.02 | 01-AUG-07:10 | 2276.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 277.06 | 04-AUG-21:01 | 329.52 | 20-AUG-06:00 |
September | 2010.79 | 01-SEP-09:09 | 1294.12 | 27-SEP-07:10 | 2276.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.01 | 14-SEP-14:00 | 472.43 | 17-SEP-10:00 |
October | 2010.79 | 02-OCT-09:09 | 1487.71 | 31-OCT-15:00 | 2276.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.53 | 25-OCT-11:00 | 1326.91 | 08-OCT-08:00 |
November | 2010.79 | 01-NOV-09:09 | 1750.00 | 06-NOV-16:49 | 2276.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2056.21 | 23-NOV-02:00 |
December | 2010.79 | 01-DEC-10:09 | 1750.00 | 01-DEC-16:30 | 2276.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2664.11 | 31-DEC-21:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 220.59 | |||||
Maximum of Months | 2010.79 | 1750.00 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 277.06 | 2664.11 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1127.77 | 02-JAN-16:40 | 1466.95 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 1649.27 | 31-JAN-01:00 |
February | 1295.83 | 01-FEB-10:09 | 1061.30 | 01-FEB-16:00 | 1466.95 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1720.55 | 05-FEB-08:50 |
March | 1295.83 | 01-MAR-10:09 | 974.86 | 02-MAR-16:00 | 1466.95 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1415.28 | 12-MAR-10:00 |
April | 1295.83 | 03-APR-09:09 | 692.79 | 03-APR-07:10 | 1466.95 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.69 | 07-APR-13:00 | 991.51 | 11-APR-03:53 |
May | 1295.83 | 01-MAY-09:09 | 692.79 | 01-MAY-07:10 | 1466.95 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.00 | 29-MAY-11:50 | 612.86 | 03-MAY-04:00 |
June | 1295.83 | 01-JUN-09:09 | 692.79 | 01-JUN-07:10 | 1466.95 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 132.25 | 19-JUN-21:02 | 345.23 | 02-JUN-22:00 |
July | 1295.83 | 03-JUL-09:09 | 692.79 | 03-JUL-07:10 | 1466.95 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 135.68 | 09-JUL-13:52 | 146.47 | 02-JUL-18:30 |
August | 1295.83 | 01-AUG-09:09 | 692.79 | 01-AUG-07:10 | 1466.95 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 195.62 | 12-AUG-18:53 | 214.92 | 20-AUG-06:10 |
September | 1295.83 | 01-SEP-09:09 | 692.79 | 01-SEP-07:10 | 1466.95 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.34 | 14-SEP-14:00 | 308.64 | 17-SEP-10:00 |
October | 1295.83 | 02-OCT-09:09 | 965.84 | 31-OCT-15:00 | 1466.95 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.02 | 25-OCT-11:00 | 964.52 | 08-OCT-08:00 |
November | 1295.83 | 01-NOV-09:09 | 1127.77 | 06-NOV-16:49 | 1466.95 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1355.40 | 23-NOV-02:00 |
December | 1295.83 | 01-DEC-10:09 | 1127.77 | 01-DEC-16:30 | 1466.95 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1749.98 | 31-DEC-21:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.47 | |||||
Maximum of Months | 1295.83 | 1127.77 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 195.62 | 1749.98 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1750.04 | 02-JAN-16:40 | 2276.35 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 2502.84 | 31-JAN-01:00 |
February | 2010.83 | 01-FEB-10:09 | 1624.97 | 15-FEB-16:00 | 2276.35 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2432.79 | 05-FEB-09:00 |
March | 2010.83 | 01-MAR-10:09 | 1327.90 | 02-MAR-16:00 | 2276.35 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2075.89 | 12-MAR-10:00 |
April | 2010.83 | 03-APR-09:09 | 1075.05 | 03-APR-07:10 | 2276.35 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.44 | 07-APR-13:00 | 1526.98 | 11-APR-03:53 |
May | 2010.83 | 01-MAY-09:09 | 1075.05 | 01-MAY-07:10 | 2276.35 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 88.55 | 29-MAY-11:53 | 918.46 | 03-MAY-04:00 |
June | 2010.83 | 01-JUN-09:09 | 1075.05 | 01-JUN-07:10 | 2276.35 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 197.82 | 19-JUN-21:02 | 527.32 | 02-JUN-22:00 |
July | 2010.83 | 03-JUL-09:09 | 1075.05 | 03-JUL-07:10 | 2276.35 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 198.59 | 09-JUL-13:52 | 229.77 | 02-JUL-18:30 |
August | 2010.83 | 01-AUG-09:09 | 1075.05 | 01-AUG-07:10 | 2276.35 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 276.03 | 04-AUG-21:01 | 334.96 | 20-AUG-06:00 |
September | 2010.83 | 01-SEP-09:09 | 1261.96 | 27-SEP-07:10 | 2276.35 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 76.92 | 14-SEP-14:00 | 482.29 | 30-SEP-24:00 |
October | 2010.83 | 02-OCT-09:09 | 1451.01 | 31-OCT-15:00 | 2276.35 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.48 | 25-OCT-11:00 | 1369.64 | 08-OCT-08:00 |
November | 2010.83 | 01-NOV-09:09 | 1750.04 | 06-NOV-16:49 | 2276.35 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2045.22 | 23-NOV-02:00 |
December | 2010.83 | 01-DEC-10:09 | 1750.04 | 01-DEC-16:30 | 2276.35 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2613.92 | 31-DEC-21:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1075.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 229.77 | |||||
Maximum of Months | 2010.83 | 1750.04 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 276.03 | 2613.92 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1127.77 | 02-JAN-16:40 | 1466.94 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 1720.11 | 31-JAN-01:00 |
February | 1295.83 | 01-FEB-10:09 | 1042.73 | 15-FEB-16:00 | 1466.94 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1731.44 | 05-FEB-08:00 |
March | 1295.83 | 01-MAR-10:09 | 895.58 | 16-MAR-07:10 | 1466.94 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1455.61 | 12-MAR-10:00 |
April | 1295.83 | 03-APR-09:09 | 794.98 | 14-APR-07:10 | 1466.94 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.69 | 07-APR-13:00 | 1142.87 | 11-APR-03:50 |
May | 1295.83 | 01-MAY-09:09 | 692.79 | 01-MAY-07:10 | 1466.94 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 84.26 | 29-MAY-11:50 | 683.73 | 03-MAY-04:00 |
June | 1295.83 | 01-JUN-09:09 | 692.79 | 01-JUN-07:10 | 1466.94 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 126.32 | 19-JUN-21:02 | 409.09 | 02-JUN-22:00 |
July | 1295.83 | 03-JUL-09:09 | 692.79 | 03-JUL-07:10 | 1466.94 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 132.39 | 09-JUL-13:52 | 226.33 | 02-JUL-17:50 |
August | 1295.83 | 01-AUG-09:09 | 774.11 | 16-AUG-07:10 | 1466.94 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 178.94 | 04-AUG-21:01 | 269.92 | 20-AUG-06:00 |
September | 1295.83 | 01-SEP-09:09 | 868.81 | 27-SEP-07:10 | 1466.94 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.34 | 14-SEP-14:00 | 350.08 | 17-SEP-10:00 |
October | 1295.83 | 02-OCT-09:09 | 941.51 | 06-OCT-07:10 | 1466.94 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.02 | 25-OCT-11:00 | 961.94 | 08-OCT-08:00 |
November | 1295.83 | 01-NOV-09:09 | 1127.77 | 06-NOV-16:49 | 1466.94 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1483.44 | 23-NOV-02:00 |
December | 1295.83 | 01-DEC-10:09 | 1127.77 | 01-DEC-16:30 | 1466.94 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1943.78 | 31-DEC-21:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 692.79 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 226.33 | |||||
Maximum of Months | 1295.83 | 1127.77 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 178.94 | 1943.78 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1750.00 | 02-JAN-16:40 | 2276.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 5093.89 | 14-JAN-05:51 |
February | 2010.79 | 01-FEB-10:09 | 1636.80 | 01-FEB-16:00 | 2276.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 5380.31 | 06-FEB-01:00 |
March | 2010.79 | 01-MAR-10:09 | 1415.81 | 02-MAR-16:00 | 2276.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4083.16 | 21-MAR-21:02 |
April | 2010.79 | 03-APR-09:09 | 1075.02 | 03-APR-07:10 | 2276.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.46 | 07-APR-13:00 | 3164.57 | 11-APR-03:53 |
May | 2010.79 | 01-MAY-09:09 | 1075.02 | 01-MAY-07:10 | 2276.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 311.32 | 29-MAY-11:53 | 1867.71 | 03-MAY-04:00 |
June | 2010.79 | 01-JUN-09:09 | 1075.02 | 01-JUN-07:10 | 2276.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 456.70 | 19-JUN-21:02 | 1133.30 | 02-JUN-22:00 |
July | 2010.79 | 03-JUL-09:09 | 1075.02 | 03-JUL-07:10 | 2276.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 500.25 | 09-JUL-14:00 | 506.03 | 11-JUL-04:50 |
August | 2010.79 | 01-AUG-09:09 | 1075.02 | 01-AUG-07:10 | 2276.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 642.84 | 04-AUG-21:01 | 763.37 | 20-AUG-06:00 |
September | 2010.79 | 01-SEP-09:09 | 1307.46 | 27-SEP-07:10 | 2276.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 177.63 | 14-SEP-14:00 | 979.42 | 23-SEP-04:00 |
October | 2010.79 | 02-OCT-09:09 | 1495.56 | 31-OCT-15:00 | 2276.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.29 | 25-OCT-11:00 | 2590.09 | 17-OCT-24:00 |
November | 2010.79 | 01-NOV-09:09 | 1750.00 | 06-NOV-16:49 | 2276.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 4033.96 | 23-NOV-02:00 |
December | 2010.79 | 01-DEC-10:09 | 1750.00 | 01-DEC-16:30 | 2276.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 5347.27 | 31-DEC-21:57 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 506.03 | |||||
Maximum of Months | 2010.79 | 1750.00 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 642.84 | 5380.31 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 1127.77 | 02-JAN-16:40 | 1466.95 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 3421.36 | 14-JAN-05:51 |
February | 1239.33 | 01-FEB-08:09 | 1061.85 | 01-FEB-16:00 | 1466.95 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3586.92 | 06-FEB-01:00 |
March | 1239.33 | 01-MAR-08:09 | 976.04 | 02-MAR-16:00 | 1466.95 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2727.21 | 21-MAR-21:02 |
April | 1239.33 | 03-APR-07:10 | 692.79 | 03-APR-07:10 | 1466.95 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.30 | 07-APR-13:00 | 2122.13 | 11-APR-03:53 |
May | 1239.33 | 01-MAY-07:10 | 692.79 | 01-MAY-07:10 | 1466.95 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 175.38 | 29-MAY-12:08 | 1261.53 | 03-MAY-04:00 |
June | 1239.33 | 01-JUN-07:10 | 692.79 | 01-JUN-07:10 | 1466.95 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 302.53 | 19-JUN-21:02 | 765.79 | 02-JUN-22:00 |
July | 1239.33 | 03-JUL-07:10 | 692.79 | 03-JUL-07:10 | 1466.95 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 338.10 | 09-JUL-13:55 | 362.87 | 02-JUL-19:00 |
August | 1239.33 | 01-AUG-07:10 | 692.79 | 01-AUG-07:10 | 1466.95 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 444.29 | 12-AUG-19:00 | 539.54 | 20-AUG-06:00 |
September | 1239.33 | 01-SEP-07:10 | 692.79 | 01-SEP-07:10 | 1466.95 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 118.41 | 14-SEP-14:00 | 696.87 | 10-SEP-08:00 |
October | 1239.33 | 02-OCT-07:10 | 967.14 | 31-OCT-15:00 | 1466.95 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.85 | 25-OCT-11:00 | 1929.66 | 08-OCT-08:00 |
November | 1239.33 | 01-NOV-07:10 | 1127.77 | 06-NOV-16:49 | 1466.95 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2709.69 | 23-NOV-02:00 |
December | 1239.33 | 01-DEC-08:09 | 1127.77 | 01-DEC-16:30 | 1466.95 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3594.50 | 31-DEC-21:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1239.33 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 362.87 | |||||
Maximum of Months | 1239.33 | 1127.77 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 444.29 | 3594.50 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1750.04 | 02-JAN-16:40 | 2276.35 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 5278.93 | 31-JAN-01:00 |
February | 2010.83 | 01-FEB-10:09 | 1628.89 | 15-FEB-16:00 | 2276.35 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 5380.38 | 06-FEB-00:55 |
March | 2010.83 | 01-MAR-10:09 | 1319.38 | 16-MAR-07:10 | 2276.35 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4146.55 | 12-MAR-10:00 |
April | 2010.83 | 03-APR-09:09 | 1075.05 | 03-APR-07:10 | 2276.35 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.36 | 07-APR-13:00 | 3272.79 | 11-APR-03:53 |
May | 2010.83 | 01-MAY-09:09 | 1075.05 | 01-MAY-07:10 | 2276.35 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 205.97 | 29-MAY-12:05 | 1927.81 | 03-MAY-04:00 |
June | 2010.83 | 01-JUN-09:09 | 1075.05 | 01-JUN-07:10 | 2276.35 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 455.11 | 19-JUN-21:02 | 1153.03 | 02-JUN-22:00 |
July | 2010.83 | 03-JUL-09:09 | 1075.05 | 03-JUL-07:10 | 2276.35 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 478.70 | 09-JUL-13:55 | 527.74 | 02-JUL-19:00 |
August | 2010.83 | 01-AUG-09:09 | 1075.05 | 01-AUG-07:10 | 2276.35 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 640.25 | 04-AUG-21:01 | 801.12 | 20-AUG-05:53 |
September | 2010.83 | 01-SEP-09:09 | 1276.50 | 27-SEP-07:10 | 2276.35 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 177.47 | 14-SEP-14:00 | 1087.47 | 30-SEP-24:00 |
October | 2010.83 | 02-OCT-09:09 | 1460.67 | 31-OCT-15:00 | 2276.35 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.68 | 25-OCT-11:00 | 2857.57 | 08-OCT-08:00 |
November | 2010.83 | 01-NOV-09:09 | 1750.04 | 06-NOV-16:49 | 2276.35 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 4231.06 | 23-NOV-02:00 |
December | 2010.83 | 01-DEC-10:09 | 1750.04 | 01-DEC-16:30 | 2276.35 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 5367.77 | 31-DEC-21:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1075.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 527.74 | |||||
Maximum of Months | 2010.83 | 1750.04 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 640.25 | 5380.38 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1127.77 | 02-JAN-16:40 | 1466.94 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 3427.22 | 14-JAN-05:51 |
February | 1295.83 | 01-FEB-10:09 | 1043.66 | 15-FEB-16:00 | 1466.94 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3586.92 | 06-FEB-00:59 |
March | 1295.83 | 01-MAR-10:09 | 897.38 | 16-MAR-07:10 | 1466.94 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2744.34 | 21-MAR-21:02 |
April | 1295.83 | 03-APR-09:09 | 797.10 | 14-APR-07:10 | 1466.94 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.31 | 07-APR-13:00 | 2222.26 | 11-APR-03:53 |
May | 1295.83 | 01-MAY-09:09 | 692.79 | 01-MAY-07:10 | 1466.94 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 217.88 | 29-MAY-11:47 | 1337.62 | 03-MAY-04:00 |
June | 1295.83 | 01-JUN-09:09 | 692.79 | 01-JUN-07:10 | 1466.94 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 296.56 | 19-JUN-21:02 | 860.17 | 03-JUN-19:00 |
July | 1295.83 | 03-JUL-09:09 | 692.79 | 03-JUL-07:10 | 1466.94 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 330.15 | 09-JUL-13:55 | 491.84 | 02-JUL-17:40 |
August | 1295.83 | 01-AUG-09:09 | 776.76 | 16-AUG-07:10 | 1466.94 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 424.09 | 04-AUG-21:01 | 572.44 | 20-AUG-05:53 |
September | 1295.83 | 01-SEP-09:09 | 870.78 | 27-SEP-07:10 | 1466.94 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 118.42 | 14-SEP-14:00 | 714.07 | 30-SEP-24:00 |
October | 1295.83 | 02-OCT-09:09 | 942.95 | 06-OCT-07:10 | 1466.94 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.86 | 25-OCT-11:00 | 1814.46 | 17-OCT-24:00 |
November | 1295.83 | 01-NOV-09:09 | 1127.77 | 06-NOV-16:49 | 1466.94 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2753.14 | 23-NOV-02:00 |
December | 1295.83 | 01-DEC-10:09 | 1127.77 | 01-DEC-16:30 | 1466.94 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3584.17 | 31-DEC-21:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 692.79 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 491.84 | |||||
Maximum of Months | 1295.83 | 1127.77 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 424.09 | 3586.92 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1750.00 | 02-JAN-16:40 | 2276.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 6198.03 | 14-JAN-06:00 |
February | 2010.79 | 01-FEB-10:09 | 1636.72 | 01-FEB-16:00 | 2276.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 6648.38 | 06-FEB-00:50 |
March | 2010.79 | 01-MAR-10:09 | 1415.71 | 02-MAR-16:00 | 2276.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 5064.70 | 21-MAR-21:02 |
April | 2010.79 | 03-APR-09:09 | 1075.02 | 03-APR-07:10 | 2276.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.04 | 07-APR-13:00 | 3595.51 | 11-APR-03:53 |
May | 2010.79 | 01-MAY-09:09 | 1075.02 | 01-MAY-07:10 | 2276.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 340.37 | 29-MAY-12:00 | 2100.12 | 03-MAY-04:00 |
June | 2010.79 | 01-JUN-09:09 | 1075.02 | 01-JUN-07:10 | 2276.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 548.49 | 19-JUN-21:02 | 1360.65 | 02-JUN-22:00 |
July | 2010.79 | 03-JUL-09:09 | 1075.02 | 03-JUL-07:10 | 2276.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 531.11 | 09-JUL-13:27 | 662.70 | 11-JUL-05:00 |
August | 2010.79 | 01-AUG-09:09 | 1075.02 | 01-AUG-07:10 | 2276.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 783.86 | 04-AUG-21:01 | 897.08 | 20-AUG-05:53 |
September | 2010.79 | 01-SEP-09:09 | 1307.08 | 27-SEP-07:10 | 2276.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 216.83 | 14-SEP-14:00 | 1127.29 | 23-SEP-04:00 |
October | 2010.79 | 02-OCT-09:09 | 1495.32 | 31-OCT-15:00 | 2276.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.85 | 25-OCT-11:00 | 2911.78 | 26-OCT-23:00 |
November | 2010.79 | 01-NOV-09:09 | 1750.00 | 06-NOV-16:49 | 2276.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 4953.47 | 22-NOV-22:02 |
December | 2010.79 | 01-DEC-10:09 | 1750.00 | 01-DEC-16:30 | 2276.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 6670.69 | 31-DEC-22:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 662.70 | |||||
Maximum of Months | 2010.79 | 1750.00 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 783.86 | 6670.69 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1127.77 | 02-JAN-16:40 | 1466.95 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 4330.91 | 14-JAN-05:54 |
February | 1295.83 | 01-FEB-10:09 | 1061.80 | 01-FEB-16:00 | 1466.95 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 4432.41 | 06-FEB-00:46 |
March | 1295.83 | 01-MAR-10:09 | 975.96 | 02-MAR-16:00 | 1466.95 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3381.17 | 21-MAR-21:02 |
April | 1295.83 | 03-APR-09:09 | 692.79 | 03-APR-07:10 | 1466.95 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.69 | 07-APR-13:00 | 2418.96 | 11-APR-03:53 |
May | 1295.83 | 01-MAY-09:09 | 692.79 | 01-MAY-07:10 | 1466.95 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 203.63 | 29-MAY-12:18 | 1428.61 | 03-MAY-04:00 |
June | 1295.83 | 01-JUN-09:09 | 692.79 | 01-JUN-07:10 | 1466.95 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 362.86 | 19-JUN-21:02 | 926.82 | 02-JUN-22:00 |
July | 1295.83 | 03-JUL-09:09 | 692.79 | 03-JUL-07:10 | 1466.95 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 365.47 | 09-JUL-14:04 | 501.94 | 02-JUL-18:30 |
August | 1295.83 | 01-AUG-09:09 | 692.79 | 01-AUG-07:10 | 1466.95 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 536.56 | 12-AUG-19:00 | 635.80 | 20-AUG-06:00 |
September | 1295.83 | 01-SEP-09:09 | 692.79 | 01-SEP-07:10 | 1466.95 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 144.56 | 14-SEP-14:00 | 819.60 | 10-SEP-08:10 |
October | 1295.83 | 02-OCT-09:09 | 966.99 | 31-OCT-15:00 | 1466.95 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.56 | 25-OCT-11:00 | 2000.56 | 08-OCT-08:10 |
November | 1295.83 | 01-NOV-09:09 | 1127.77 | 06-NOV-16:49 | 1466.95 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3304.73 | 22-NOV-22:02 |
December | 1295.83 | 01-DEC-10:09 | 1127.77 | 01-DEC-16:30 | 1466.95 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4447.36 | 31-DEC-21:58 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 501.94 | |||||
Maximum of Months | 1295.83 | 1127.77 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 536.56 | 4447.36 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1750.04 | 02-JAN-16:40 | 2276.35 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 6495.95 | 14-JAN-06:00 |
February | 2010.83 | 01-FEB-10:09 | 1628.78 | 15-FEB-16:00 | 2276.35 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 6648.63 | 06-FEB-00:50 |
March | 2010.83 | 01-MAR-10:09 | 1319.06 | 16-MAR-07:10 | 2276.35 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 5093.12 | 21-MAR-21:02 |
April | 2010.83 | 03-APR-09:09 | 1075.05 | 03-APR-07:10 | 2276.35 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.86 | 07-APR-13:00 | 3740.11 | 11-APR-03:53 |
May | 2010.83 | 01-MAY-09:09 | 1075.05 | 01-MAY-07:10 | 2276.35 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 244.86 | 29-MAY-11:38 | 2183.21 | 03-MAY-04:00 |
June | 2010.83 | 01-JUN-09:09 | 1075.05 | 01-JUN-07:10 | 2276.35 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 546.20 | 19-JUN-21:02 | 1388.82 | 02-JUN-22:00 |
July | 2010.83 | 03-JUL-09:09 | 1075.05 | 03-JUL-07:10 | 2276.35 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 527.22 | 09-JUL-13:46 | 711.12 | 02-JUL-18:30 |
August | 2010.83 | 01-AUG-09:09 | 1075.05 | 01-AUG-07:10 | 2276.35 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 780.29 | 04-AUG-21:01 | 947.72 | 20-AUG-05:53 |
September | 2010.83 | 01-SEP-09:09 | 1276.12 | 27-SEP-07:10 | 2276.35 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 216.59 | 14-SEP-14:00 | 1289.25 | 10-SEP-19:55 |
October | 2010.83 | 02-OCT-09:09 | 1460.45 | 31-OCT-15:00 | 2276.35 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.83 | 25-OCT-11:00 | 3199.43 | 17-OCT-22:00 |
November | 2010.83 | 01-NOV-09:09 | 1750.04 | 06-NOV-16:49 | 2276.35 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 4974.67 | 22-NOV-22:02 |
December | 2010.83 | 01-DEC-10:09 | 1750.04 | 01-DEC-16:30 | 2276.35 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 6670.94 | 31-DEC-22:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1075.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 711.12 | |||||
Maximum of Months | 2010.83 | 1750.04 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 780.29 | 6670.94 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1127.77 | 02-JAN-16:40 | 1466.94 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 4330.88 | 14-JAN-05:59 |
February | 1295.83 | 01-FEB-10:09 | 1043.60 | 15-FEB-16:00 | 1466.94 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 4432.41 | 06-FEB-00:44 |
March | 1295.83 | 01-MAR-10:09 | 897.18 | 16-MAR-07:10 | 1466.94 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3400.60 | 21-MAR-21:02 |
April | 1295.83 | 03-APR-09:09 | 796.91 | 14-APR-07:10 | 1466.94 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.70 | 07-APR-13:00 | 2551.15 | 11-APR-03:53 |
May | 1295.83 | 01-MAY-09:09 | 692.79 | 01-MAY-07:10 | 1466.94 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 253.16 | 29-MAY-12:00 | 1533.58 | 03-MAY-04:00 |
June | 1295.83 | 01-JUN-09:09 | 692.79 | 01-JUN-07:10 | 1466.94 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 355.34 | 19-JUN-21:02 | 1064.02 | 03-JUN-19:00 |
July | 1295.83 | 03-JUL-09:09 | 692.79 | 03-JUL-07:10 | 1466.94 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 356.82 | 09-JUL-13:25 | 660.30 | 02-JUL-17:50 |
August | 1295.83 | 01-AUG-09:09 | 776.43 | 16-AUG-07:10 | 1466.94 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 516.76 | 04-AUG-21:01 | 680.23 | 20-AUG-05:53 |
September | 1295.83 | 01-SEP-09:09 | 870.55 | 27-SEP-07:10 | 1466.94 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 144.55 | 14-SEP-14:00 | 888.01 | 10-SEP-19:55 |
October | 1295.83 | 02-OCT-09:09 | 942.77 | 06-OCT-07:10 | 1466.94 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.57 | 25-OCT-11:00 | 2080.15 | 17-OCT-22:00 |
November | 1295.83 | 01-NOV-09:09 | 1127.77 | 06-NOV-16:49 | 1466.94 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3309.93 | 22-NOV-22:02 |
December | 1295.83 | 01-DEC-10:09 | 1127.77 | 01-DEC-16:30 | 1466.94 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4447.25 | 31-DEC-21:57 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 692.79 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 660.30 | |||||
Maximum of Months | 1295.83 | 1127.77 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 516.76 | 4447.25 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 405.10 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 405.10 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 405.10 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 405.10 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 405.10 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 405.10 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 405.10 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 405.10 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 405.10 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 405.10 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 405.10 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 405.10 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 405.10 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 405.10 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 405.10 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 405.10 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 405.10 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 405.10 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 405.10 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 405.10 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 405.10 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 405.10 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 405.10 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 405.10 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 405.10 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 405.10 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 405.10 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 405.10 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 405.10 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 405.10 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 405.10 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 405.10 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 405.10 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 405.10 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 405.10 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 405.10 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 405.10 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 405.10 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 405.10 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 405.10 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 405.10 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 405.10 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5027.92 | 02-JAN-10:09 | 4375.82 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5027.92 | 01-FEB-10:09 | 4375.82 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5027.92 | 01-MAR-10:09 | 4375.82 | 01-MAR-08:09 | 379632.52 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5027.92 | 03-APR-09:09 | 4375.82 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5027.92 | 01-MAY-09:09 | 4375.82 | 01-MAY-07:10 | 189816.26 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5027.92 | 01-JUN-09:09 | 4375.82 | 01-JUN-07:10 | 284724.39 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5027.92 | 03-JUL-09:09 | 4375.82 | 03-JUL-07:10 | 379632.52 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5027.92 | 01-AUG-09:09 | 4375.82 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5027.92 | 01-SEP-09:09 | 4375.82 | 01-SEP-07:10 | 189816.26 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5027.92 | 02-OCT-09:09 | 4375.82 | 02-OCT-07:10 | 284724.39 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5027.92 | 01-NOV-09:09 | 4375.82 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5027.92 | 01-DEC-10:09 | 4375.82 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5027.92 | 4375.82 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 5027.92 | 4375.82 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 5464.70 | 31-JAN-01:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 5462.07 | 06-FEB-00:51 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4059.60 | 12-MAR-10:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.03 | 07-APR-13:00 | 3345.64 | 11-APR-03:57 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 249.23 | 29-MAY-12:00 | 1983.60 | 03-MAY-04:05 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 328.93 | 19-JUN-21:02 | 1075.78 | 02-JUN-22:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 453.97 | 09-JUL-14:00 | 461.07 | 11-JUL-04:53 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 538.77 | 12-AUG-18:53 | 701.01 | 20-AUG-06:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.37 | 14-SEP-14:00 | 964.48 | 23-SEP-04:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.19 | 25-OCT-11:00 | 2865.98 | 08-OCT-07:55 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 4543.44 | 23-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 5842.85 | 31-DEC-21:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 461.07 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 538.77 | 5842.85 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 9096.34 | 31-JAN-01:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 8938.86 | 05-FEB-08:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 6714.78 | 21-MAR-21:02 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.68 | 07-APR-13:00 | 5744.21 | 11-APR-03:53 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 510.11 | 29-MAY-11:53 | 3348.48 | 03-MAY-04:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 588.81 | 19-JUN-21:02 | 1894.04 | 02-JUN-22:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 818.67 | 09-JUL-14:00 | 837.27 | 11-JUL-04:53 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 960.04 | 12-AUG-19:00 | 1277.94 | 20-AUG-05:53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 243.26 | 14-SEP-14:00 | 1689.80 | 23-SEP-04:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.49 | 25-OCT-11:00 | 4865.17 | 08-OCT-07:55 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 7555.68 | 23-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 9213.68 | 31-DEC-21:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 837.27 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 960.04 | 9213.68 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 9371.91 | 31-JAN-01:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 9032.88 | 06-FEB-00:51 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 7529.82 | 21-MAR-21:02 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.12 | 08-APR-10:00 | 5848.89 | 11-APR-03:53 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 212.87 | 29-MAY-12:00 | 3440.94 | 03-MAY-04:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 668.45 | 19-JUN-21:02 | 1998.44 | 02-JUN-22:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 588.63 | 07-JUL-21:53 | 1059.30 | 02-JUL-18:33 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1071.67 | 12-AUG-19:00 | 1318.50 | 20-AUG-05:53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 240.04 | 14-SEP-14:00 | 1761.36 | 23-SEP-04:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 4754.44 | 17-OCT-24:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 7597.66 | 23-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 9158.34 | 31-DEC-22:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1059.30 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1071.67 | 9371.91 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 101225.76 | 30-JAN-04:01 | 0.00 | 7760.04 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 105817.05 | 21-FEB-04:01 | 0.00 | 6035.59 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 103836.54 | 13-MAR-03:01 | 0.00 | 7760.04 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 103422.61 | 03-APR-03:01 | 0.00 | 6897.82 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 103833.81 | 01-MAY-03:02 | 0.00 | 3448.91 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 93773.98 | 05-JUN-03:03 | 0.00 | 2586.68 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 87613.43 | 11-JUL-03:02 | 0.00 | 4311.14 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 89401.06 | 29-AUG-03:02 | 0.00 | 4311.14 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 102079.14 | 25-SEP-03:02 | 0.00 | 5173.36 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 105803.27 | 16-OCT-03:02 | 0.00 | 4311.14 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 105334.30 | 06-NOV-04:03 | 0.00 | 3448.91 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 108548.94 | 26-DEC-04:01 | 0.00 | 6035.59 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 87613.43 | 0.00 | 2586.68 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 108548.94 | 0.00 | 7760.04 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 79541.05 | 30-JAN-06:02 | 14510.15 | 13938.13 | 72514.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 83923.28 | 21-FEB-05:02 | 0.00 | 9292.09 | 48342.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 84360.62 | 30-MAR-04:02 | 0.00 | 9292.09 | 48342.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 85862.75 | 11-APR-03:02 | 0.00 | 3097.36 | 32228.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 87495.28 | 01-MAY-03:02 | 0.00 | 3097.36 | 32228.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 89540.86 | 12-JUN-03:02 | 0.00 | 3871.70 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 84373.02 | 01-JUL-03:02 | 0.00 | 3871.70 | 30214.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 84093.86 | 07-AUG-05:04 | 8061.19 | 7743.41 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 91267.60 | 18-SEP-03:02 | 0.00 | 3871.70 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 90327.57 | 23-OCT-03:02 | 0.00 | 3871.70 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 91713.54 | 13-NOV-04:02 | 0.00 | 3871.70 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 85475.15 | 26-DEC-04:01 | 0.00 | 5420.38 | 56400.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 79541.05 | 0.00 | 3097.36 | 30214.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 91713.54 | 14510.15 | 13938.13 | 72514.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 21262.51 | 31-JAN-09:40 | 30632.53 | 27875.12 | 36257.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 25464.82 | 04-FEB-17:08 | 4030.60 | 3871.70 | 30214.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 70076.28 | 30-MAR-05:02 | 8061.19 | 7743.41 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 77420.71 | 08-APR-05:02 | 8061.19 | 7743.41 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 77442.54 | 20-MAY-05:02 | 8061.19 | 7743.41 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 81975.11 | 12-JUN-03:02 | 0.00 | 3871.70 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 79698.32 | 12-JUL-03:02 | 0.00 | 3871.70 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 86286.94 | 07-AUG-03:02 | 0.00 | 3871.70 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 80536.55 | 18-SEP-03:02 | 0.00 | 3871.70 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 77929.20 | 05-OCT-04:03 | 0.00 | 6194.72 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 73403.98 | 03-NOV-05:02 | 8061.19 | 7743.41 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 24633.11 | 21-DEC-17:00 | 15316.26 | 13937.56 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 21262.51 | 0.00 | 3871.70 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 86286.94 | 30632.53 | 27875.12 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 18386.66 | 20-JAN-17:00 | 30632.53 | 27875.12 | 36257.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 18461.24 | 24-FEB-17:00 | 15316.26 | 13937.56 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 29245.72 | 03-MAR-17:00 | 15316.26 | 13937.56 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 75034.63 | 08-APR-05:02 | 8061.19 | 7743.41 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 81840.28 | 30-MAY-03:02 | 0.00 | 3871.70 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 84215.32 | 12-JUN-03:02 | 0.00 | 3871.70 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 84498.08 | 24-JUL-03:02 | 0.00 | 3871.70 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 88980.59 | 07-AUG-03:02 | 0.00 | 3871.70 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 81556.61 | 05-SEP-03:02 | 0.00 | 3871.70 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 78239.46 | 06-OCT-05:02 | 8061.19 | 7743.41 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 29554.38 | 03-NOV-16:00 | 15316.26 | 13937.56 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 18152.88 | 20-DEC-17:00 | 15316.26 | 13937.56 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 18152.88 | 0.00 | 3871.70 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 88980.59 | 30632.53 | 27875.12 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2594.39 | 24-JAN-06:03 | 809.73 | 777.81 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 268.33 |
February | 2661.02 | 21-FEB-05:02 | 0.00 | 1166.71 | 6070.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 474.52 |
March | 5368.29 | 27-MAR-13:30 | 2010.79 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.38 |
April | 6755.29 | 07-APR-13:40 | 2010.79 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 27.89 | 0.00 |
May | 12709.70 | 30-MAY-05:03 | 809.73 | 477.81 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.31 |
June | 12222.83 | 12-JUN-05:03 | 809.73 | 659.11 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.39 |
July | 15480.16 | 04-JUL-16:01 | 809.73 | 477.81 | 6070.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.16 |
August | 15993.37 | 13-AUG-16:21 | 809.73 | 477.81 | 6070.18 | 0.00 | 0.00 | 0.00 | 0.00 | 74.63 | 0.00 |
September | 11727.90 | 02-SEP-05:03 | 809.73 | 777.81 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.08 |
October | 10056.65 | 23-OCT-05:03 | 809.73 | 777.81 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.43 |
November | 4446.36 | 03-NOV-13:50 | 2010.79 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.99 |
December | 2849.64 | 05-DEC-05:01 | 0.00 | 1361.17 | 7081.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 350.39 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2594.39 | 0.00 | 477.81 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15993.37 | 2010.79 | 1361.17 | 7081.88 | 0.00 | 0.00 | 0.00 | 0.00 | 74.63 | 474.52 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3010.30 | 19-JAN-09:25 | 2478.65 | 1385.57 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.67 |
February | 3977.52 | 22-FEB-09:30 | 2478.65 | 1385.57 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 205.41 |
March | 7167.92 | 29-MAR-08:40 | 1239.33 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.34 |
April | 10541.44 | 23-APR-08:33 | 195.68 | 115.47 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 338.41 |
May | 18182.90 | 29-MAY-08:22 | 326.14 | 192.45 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.33 |
June | 17846.79 | 04-JUN-08:13 | 260.91 | 153.96 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.54 |
July | 18147.23 | 02-JUL-08:32 | 326.14 | 192.45 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.31 |
August | 17440.45 | 13-AUG-09:02 | 391.37 | 230.94 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 27.08 | 0.00 |
September | 18180.11 | 04-SEP-07:23 | 260.91 | 153.96 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.18 |
October | 8599.91 | 03-OCT-08:40 | 1239.33 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.19 |
November | 5145.63 | 02-NOV-08:50 | 1239.33 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.99 |
December | 3674.70 | 20-DEC-09:25 | 2478.65 | 1385.57 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.41 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3010.30 | 195.68 | 115.47 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18182.90 | 2478.65 | 1385.57 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 27.08 | 338.41 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 10789.31 | 19-JAN-13:30 | 1923.15 | 1075.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 238.78 |
February | 11529.95 | 22-FEB-13:20 | 1923.15 | 1075.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 188.52 |
March | 14175.04 | 03-MAR-13:15 | 3846.30 | 2150.10 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.29 |
April | 16859.92 | 09-APR-13:43 | 404.87 | 238.91 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 297.68 |
May | 21619.03 | 29-MAY-13:43 | 404.87 | 238.91 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.52 |
June | 15566.95 | 26-JUN-05:02 | 1012.19 | 761.07 | 5058.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.80 |
July | 22034.40 | 04-JUL-14:02 | 607.31 | 358.36 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 18.39 | 0.00 |
August | 23327.09 | 13-AUG-13:02 | 607.31 | 358.36 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 83.01 | 0.00 |
September | 22460.27 | 10-SEP-11:02 | 404.87 | 238.91 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 242.27 |
October | 22342.11 | 15-OCT-13:32 | 404.87 | 238.91 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 413.22 |
November | 16291.15 | 02-NOV-12:40 | 1923.15 | 1075.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.41 |
December | 17957.59 | 17-DEC-12:33 | 303.66 | 179.18 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 424.25 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 10789.31 | 303.66 | 179.18 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23327.09 | 3846.30 | 2150.10 | 5058.56 | 0.00 | 0.00 | 0.00 | 0.00 | 83.01 | 424.25 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5367.07 | 20-JAN-15:40 | 1239.33 | 692.79 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.46 |
February | 7665.10 | 24-FEB-15:30 | 1239.33 | 692.79 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 185.05 |
March | 11632.18 | 27-MAR-16:00 | 1239.33 | 692.79 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.47 |
April | 22755.94 | 09-APR-16:22 | 326.14 | 192.45 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168.37 |
May | 18788.75 | 29-MAY-14:23 | 260.91 | 153.96 | 1955.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.40 |
June | 22960.94 | 18-JUN-16:02 | 326.14 | 192.45 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.92 |
July | 25612.86 | 04-JUL-16:01 | 521.82 | 307.92 | 3911.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.87 |
August | 25797.33 | 13-AUG-16:21 | 521.82 | 307.92 | 3911.83 | 0.00 | 0.00 | 0.00 | 0.00 | 7.97 | 0.00 |
September | 22066.26 | 10-SEP-15:42 | 326.14 | 192.45 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.74 |
October | 14656.52 | 23-OCT-05:03 | 521.82 | 501.25 | 2607.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.74 |
November | 10871.66 | 09-NOV-06:03 | 521.82 | 501.25 | 2607.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7507.82 | 18-DEC-15:30 | 1239.33 | 692.79 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.14 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5367.07 | 260.91 | 153.96 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25797.33 | 1239.33 | 692.79 | 3911.83 | 0.00 | 0.00 | 0.00 | 0.00 | 7.97 | 185.05 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1830.36 | 20-JAN-17:00 | 3846.22 | 3500.00 | 4552.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 325.04 |
February | 2714.43 | 04-FEB-17:08 | 506.08 | 448.10 | 3793.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 783.58 |
March | 2369.75 | 27-MAR-16:00 | 1923.11 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.66 |
April | 4963.59 | 07-APR-15:20 | 1923.11 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 41.45 | 0.00 |
May | 10386.10 | 30-MAY-05:03 | 809.73 | 477.81 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.90 |
June | 11376.34 | 20-JUN-05:02 | 1012.16 | 597.26 | 5058.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.54 |
July | 13815.51 | 10-JUL-03:02 | 0.00 | 486.13 | 5058.48 | 0.00 | 0.00 | 0.00 | 0.00 | 15.94 | 0.00 |
August | 12318.14 | 18-AUG-03:02 | 0.00 | 486.13 | 5058.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.73 |
September | 10780.97 | 22-SEP-05:03 | 809.73 | 777.81 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.50 |
October | 5448.73 | 05-OCT-14:00 | 2010.79 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.60 |
November | 2789.43 | 02-NOV-13:20 | 2010.79 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 193.16 |
December | 1765.47 | 20-DEC-13:40 | 1923.11 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 245.95 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1765.47 | 0.00 | 448.10 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13815.51 | 3846.22 | 3500.00 | 5058.48 | 0.00 | 0.00 | 0.00 | 0.00 | 41.45 | 783.58 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2138.81 | 26-JAN-09:25 | 2478.65 | 1385.57 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.54 |
February | 2472.69 | 04-FEB-17:08 | 326.14 | 293.60 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 517.11 |
March | 5920.93 | 29-MAR-09:00 | 1239.33 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 227.72 |
April | 9091.63 | 28-APR-08:50 | 1239.33 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.24 |
May | 20770.25 | 29-MAY-08:42 | 391.37 | 230.94 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.47 |
June | 18718.30 | 04-JUN-08:23 | 260.91 | 153.96 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170.56 |
July | 21292.56 | 02-JUL-09:01 | 456.59 | 269.43 | 3422.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.32 |
August | 18935.18 | 27-AUG-09:53 | 260.91 | 153.96 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.27 |
September | 20532.56 | 04-SEP-09:12 | 391.37 | 230.94 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.24 |
October | 8046.64 | 05-OCT-09:00 | 1239.33 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.14 |
November | 3189.85 | 03-NOV-09:00 | 1239.33 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.01 |
December | 2048.78 | 21-DEC-09:15 | 2478.65 | 1385.57 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 367.83 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2048.78 | 260.91 | 153.96 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.27 | |
Maximum of Months | 21292.56 | 2478.65 | 1385.57 | 3422.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 517.11 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9636.76 | 19-JAN-13:40 | 1923.15 | 1075.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 552.36 |
February | 11131.70 | 22-FEB-13:40 | 1923.15 | 1075.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 418.35 |
March | 13487.33 | 01-MAR-13:30 | 1923.15 | 1075.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 205.12 |
April | 13860.82 | 07-APR-12:40 | 1923.15 | 1075.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 57.08 | 0.00 |
May | 21438.89 | 29-MAY-12:43 | 404.87 | 238.91 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 33.31 | 0.00 |
June | 14925.82 | 08-JUN-05:02 | 1012.19 | 805.11 | 5058.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.61 |
July | 21969.56 | 30-JUL-13:32 | 506.09 | 298.64 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.21 |
August | 21882.55 | 20-AUG-12:32 | 404.87 | 238.91 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.98 |
September | 23745.40 | 04-SEP-11:52 | 607.31 | 358.36 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.14 |
October | 21877.50 | 15-OCT-14:32 | 404.87 | 238.91 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1037.37 |
November | 16594.06 | 02-NOV-13:10 | 2010.83 | 1075.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 228.19 |
December | 13902.34 | 15-DEC-12:00 | 3846.30 | 2150.10 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 562.52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 9636.76 | 404.87 | 238.91 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23745.40 | 3846.30 | 2150.10 | 5058.56 | 0.00 | 0.00 | 0.00 | 0.00 | 57.08 | 1037.37 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2393.09 | 20-JAN-16:10 | 1239.33 | 692.79 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.35 |
February | 3448.09 | 22-FEB-16:30 | 1239.33 | 692.79 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 278.85 |
March | 7749.30 | 29-MAR-16:00 | 1239.33 | 692.79 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 314.09 |
April | 12552.96 | 09-APR-16:33 | 260.91 | 153.96 | 1955.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 349.12 |
May | 15095.03 | 28-MAY-16:03 | 260.91 | 153.96 | 1955.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 173.78 |
June | 20273.71 | 04-JUN-16:22 | 326.14 | 192.45 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 374.42 |
July | 20989.66 | 02-JUL-16:21 | 521.82 | 307.92 | 3911.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 260.42 |
August | 20254.30 | 13-AUG-15:52 | 391.37 | 230.94 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 112.48 | 0.00 |
September | 21157.38 | 10-SEP-16:02 | 391.37 | 230.94 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 329.21 |
October | 10492.44 | 04-OCT-15:30 | 1239.33 | 692.79 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.39 |
November | 5405.39 | 03-NOV-15:30 | 1239.33 | 692.79 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.24 |
December | 2256.62 | 08-DEC-15:40 | 1239.33 | 692.79 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 304.43 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2256.62 | 260.91 | 153.96 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21157.38 | 1239.33 | 692.79 | 3911.83 | 0.00 | 0.00 | 0.00 | 0.00 | 112.48 | 374.42 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1558.17 | 20-JAN-16:00 | 1923.11 | 1301.04 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 239.86 |
February | 1633.69 | 24-FEB-15:30 | 1923.11 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 667.29 |
March | 2365.76 | 28-MAR-14:10 | 1923.11 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 421.74 |
April | 5617.14 | 07-APR-15:20 | 1923.11 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 47.70 | 0.00 |
May | 11064.09 | 31-MAY-05:03 | 809.73 | 477.81 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 13587.36 | 26-JUN-05:02 | 1012.16 | 597.26 | 5058.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.65 |
July | 18157.48 | 09-JUL-15:21 | 708.51 | 418.08 | 5311.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.72 |
August | 14778.17 | 13-AUG-15:52 | 607.30 | 358.36 | 4552.64 | 0.00 | 0.00 | 0.00 | 0.00 | 253.59 | 0.00 |
September | 10682.72 | 07-SEP-05:02 | 1012.16 | 972.26 | 5058.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.71 |
October | 5694.95 | 04-OCT-14:00 | 2010.79 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 3.91 | 0.00 |
November | 2298.44 | 03-NOV-15:00 | 1923.11 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.55 |
December | 1505.85 | 09-DEC-17:03 | 404.87 | 388.90 | 3035.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 246.75 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1505.85 | 404.87 | 358.36 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18157.48 | 2010.79 | 1301.04 | 5311.41 | 0.00 | 0.00 | 0.00 | 0.00 | 253.59 | 667.29 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1701.50 | 19-JAN-10:20 | 1295.83 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 393.61 |
February | 1738.90 | 22-FEB-10:15 | 2591.66 | 1385.57 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 490.14 |
March | 4064.03 | 29-MAR-09:50 | 1295.83 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.36 |
April | 8512.42 | 07-APR-09:30 | 1295.83 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.12 |
May | 21293.57 | 29-MAY-08:52 | 391.37 | 230.94 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.81 |
June | 19106.42 | 04-JUN-09:13 | 260.91 | 153.96 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.20 |
July | 19823.50 | 02-JUL-09:12 | 326.14 | 192.45 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.33 |
August | 19155.68 | 13-AUG-09:52 | 326.14 | 192.45 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 98.59 | 0.00 |
September | 20929.34 | 04-SEP-09:12 | 391.37 | 230.94 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.79 |
October | 7532.67 | 05-OCT-09:20 | 1295.83 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.31 |
November | 2271.47 | 02-NOV-13:30 | 1295.83 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170.23 |
December | 1752.42 | 20-DEC-09:35 | 2478.65 | 1385.57 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.62 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1701.50 | 260.91 | 153.96 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21293.57 | 2591.66 | 1385.57 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 98.59 | 490.14 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8855.22 | 19-JAN-13:50 | 1923.15 | 1075.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 676.10 |
February | 9603.48 | 02-FEB-14:20 | 2010.83 | 1075.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 605.25 |
March | 13234.09 | 03-MAR-13:40 | 3846.30 | 2150.10 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 451.92 |
April | 14470.88 | 07-APR-12:40 | 1923.15 | 1075.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 67.34 | 0.00 |
May | 23794.92 | 29-MAY-12:13 | 404.87 | 238.91 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 117.64 | 0.00 |
June | 15172.52 | 08-JUN-05:02 | 1012.19 | 804.98 | 5058.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.86 |
July | 24299.51 | 30-JUL-13:32 | 506.09 | 298.64 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.45 |
August | 23858.28 | 13-AUG-12:32 | 506.09 | 298.64 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 302.65 | 0.00 |
September | 26184.92 | 04-SEP-11:52 | 607.31 | 358.36 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 203.46 |
October | 23637.63 | 15-OCT-13:23 | 404.87 | 238.91 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1225.29 |
November | 15345.22 | 02-NOV-13:20 | 2010.83 | 1075.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 287.87 |
December | 8256.45 | 21-DEC-13:30 | 1923.15 | 1075.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 614.63 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8256.45 | 404.87 | 238.91 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26184.92 | 3846.30 | 2150.10 | 5058.56 | 0.00 | 0.00 | 0.00 | 0.00 | 302.65 | 1225.29 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2304.73 | 20-JAN-16:00 | 1239.33 | 692.79 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 185.74 |
February | 2628.30 | 22-FEB-16:30 | 1239.33 | 692.79 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 348.08 |
March | 7250.86 | 29-MAR-16:00 | 1239.33 | 692.79 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 392.49 |
April | 19177.15 | 09-APR-16:51 | 456.59 | 269.43 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 324.10 |
May | 17229.03 | 29-MAY-14:13 | 260.91 | 153.96 | 1955.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.09 |
June | 21819.86 | 18-JUN-16:02 | 326.14 | 192.45 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176.69 |
July | 22945.55 | 09-JUL-15:21 | 456.59 | 269.43 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.28 |
August | 21865.13 | 13-AUG-15:52 | 391.37 | 230.94 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 125.16 | 0.00 |
September | 22558.35 | 10-SEP-16:52 | 391.37 | 230.94 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 503.06 |
October | 10766.02 | 04-OCT-15:30 | 1239.33 | 692.79 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.76 |
November | 4847.76 | 03-NOV-15:30 | 1239.33 | 692.79 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.65 |
December | 2223.96 | 08-DEC-15:40 | 1239.33 | 692.79 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 365.29 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2223.96 | 260.91 | 153.96 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22945.55 | 1239.33 | 692.79 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 125.16 | 503.06 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3206.76 | 14-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1153.00 |
February | 4721.37 | 06-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4453.46 |
March | 3458.53 | 31-MAR-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 416.11 |
April | 8349.65 | 10-APR-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 144.80 |
May | 12082.22 | 30-MAY-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.64 |
June | 9709.11 | 12-JUN-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.32 |
July | 12396.08 | 10-JUL-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.79 | 0.00 |
August | 13506.91 | 14-AUG-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.52 |
September | 12389.63 | 05-SEP-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.67 |
October | 8235.25 | 23-OCT-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.89 |
November | 5306.24 | 13-NOV-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 233.69 |
December | 3401.73 | 18-DEC-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 288.19 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 3206.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13506.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.79 | 4453.46 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5546.45 | 14-JAN-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7481.48 |
February | 6177.63 | 05-FEB-22:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8635.09 |
March | 5201.61 | 13-MAR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4685.36 |
April | 3752.97 | 10-APR-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 253.67 |
May | 7006.16 | 30-MAY-13:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 144.55 | 0.00 |
June | 7475.25 | 20-JUN-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.46 | 0.00 |
July | 7977.59 | 11-JUL-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.04 | 0.00 |
August | 9585.18 | 07-AUG-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.71 |
September | 9334.56 | 01-SEP-14:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.24 | 0.00 |
October | 5063.56 | 05-OCT-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 199.40 |
November | 5074.35 | 22-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6050.23 |
December | 6049.39 | 02-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5316.16 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 3752.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9585.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.24 | 8635.09 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6716.81 |
February | 298.64 | 17-FEB-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 488.39 |
March | 5014.87 | 03-MAR-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 701.87 |
April | 13190.03 | 07-APR-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.46 | 0.00 |
May | 20739.38 | 30-MAY-13:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 152.20 | 0.00 |
June | 21693.77 | 19-JUN-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 274.89 | 0.00 |
July | 20420.27 | 10-JUL-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 364.17 | 0.00 |
August | 20693.14 | 22-AUG-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 264.59 | 0.00 |
September | 17971.21 | 01-SEP-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176.60 | 0.00 |
October | 11076.43 | 04-OCT-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.25 |
November | 3493.69 | 04-NOV-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 235.90 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3601.74 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21693.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 364.17 | 6716.81 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1934.41 | 20-JAN-16:30 | 222.14 | 405.10 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3979.31 | 22-FEB-16:50 | 222.14 | 405.10 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6935.85 | 31-MAR-24:00 | 0.00 | 22.51 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8071.72 | 23-APR-17:45 | 0.00 | 45.01 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3522.82 | 31-MAY-24:00 | 0.00 | 22.51 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5342.74 | 30-JUN-24:00 | 0.00 | 22.51 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7222.48 | 31-JUL-23:57 | 0.00 | 67.52 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7984.20 | 13-AUG-18:12 | 0.00 | 135.04 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3414.15 | 30-SEP-24:00 | 0.00 | 22.51 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5136.44 | 31-OCT-24:00 | 0.00 | 22.51 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5843.07 | 03-NOV-16:00 | 222.14 | 405.10 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7701.48 | 18-DEC-16:00 | 222.14 | 405.10 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1934.41 | 0.00 | 22.51 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8071.72 | 222.14 | 405.10 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1540.40 | 20-JAN-16:40 | 222.14 | 405.10 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3543.81 | 22-FEB-17:00 | 222.14 | 405.10 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6009.06 | 31-MAR-23:50 | 0.00 | 22.51 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7497.51 | 09-APR-17:30 | 0.00 | 67.52 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3350.89 | 31-MAY-24:00 | 0.00 | 22.51 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5034.59 | 30-JUN-24:00 | 0.00 | 22.51 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6968.16 | 31-JUL-23:57 | 0.00 | 67.52 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7605.39 | 31-AUG-17:30 | 23.38 | 135.03 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3073.88 | 30-SEP-23:40 | 0.00 | 22.51 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4404.44 | 31-OCT-24:00 | 0.00 | 22.51 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5470.13 | 03-NOV-16:00 | 222.14 | 405.10 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7030.62 | 21-DEC-16:10 | 222.14 | 405.10 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1540.40 | 0.00 | 22.51 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7605.39 | 222.14 | 405.10 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1423.12 | 19-JAN-16:30 | 222.14 | 405.10 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3401.59 | 02-FEB-17:00 | 222.14 | 405.10 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5539.09 | 29-MAR-17:00 | 70.15 | 225.06 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7567.06 | 09-APR-17:30 | 0.00 | 67.52 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3321.63 | 31-MAY-24:00 | 0.00 | 22.51 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4951.34 | 30-JUN-24:00 | 0.00 | 22.51 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6971.72 | 31-JUL-23:57 | 0.00 | 67.52 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7750.83 | 13-AUG-17:40 | 0.00 | 157.55 | 54560.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2808.19 | 30-SEP-23:20 | 0.00 | 22.51 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3908.63 | 04-OCT-16:00 | 222.14 | 405.10 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5434.26 | 03-NOV-16:00 | 222.14 | 405.10 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6807.94 | 08-DEC-16:10 | 222.14 | 405.10 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1423.12 | 0.00 | 22.51 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7750.83 | 222.14 | 405.10 | 54560.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 91147.31 | 20-JAN-17:00 | 9617.36 | 8751.64 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 182527.00 | 22-FEB-17:00 | 4808.68 | 4375.82 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 358031.60 | 31-MAR-24:00 | 0.00 | 243.11 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 367103.26 | 10-APR-16:00 | 4808.68 | 4375.82 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 175884.78 | 31-MAY-24:00 | 0.00 | 243.11 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 267492.19 | 30-JUN-24:00 | 0.00 | 243.11 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 359805.13 | 31-JUL-23:57 | 0.00 | 729.33 | 1138897.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 369565.33 | 18-AUG-23:15 | 0.00 | 486.22 | 759265.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 176249.20 | 30-SEP-24:00 | 0.00 | 243.11 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 267951.31 | 31-OCT-24:00 | 0.00 | 243.11 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 276238.39 | 06-NOV-17:00 | 4808.68 | 4375.82 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 367311.32 | 18-DEC-17:00 | 4808.68 | 4375.82 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 91147.31 | 0.00 | 243.11 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 369565.33 | 9617.36 | 8751.64 | 1138897.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.153971E+13 | 982651.48 | 20-JAN-16:00 | 0.454158E+12 | 1752188.17 | 02-JAN-05:10 |
February | 0.174464E+13 | 1099809.15 | 02-FEB-08:09 | 0.343145E+12 | 1378301.61 | 13-FEB-07:10 |
March | 0.237473E+13 | 1374730.96 | 27-MAR-15:00 | 0.165134E+12 | 739074.78 | 13-MAR-04:10 |
April | 0.271001E+13 | 1802086.15 | 07-APR-14:39 | 0.881354E+11 | 455252.31 | 03-APR-05:10 |
May | 0.175521E+13 | 1457384.89 | 30-MAY-13:50 | 0.610582E+11 | 169729.33 | 30-MAY-14:09 |
June | 0.238328E+13 | 1611494.27 | 22-JUN-13:09 | 0.582724E+11 | 226676.01 | 01-JUN-14:00 |
July | 0.297602E+13 | 1788163.72 | 11-JUL-15:20 | 0.534638E+11 | 124969.40 | 11-JUL-14:09 |
August | 0.342864E+13 | 1959609.74 | 22-AUG-14:39 | 0.588140E+11 | 184133.60 | 22-AUG-15:50 |
September | 0.185088E+13 | 1421538.99 | 01-SEP-13:00 | 0.527741E+11 | 94287.47 | 01-SEP-17:19 |
October | 0.212640E+13 | 1490517.29 | 05-OCT-15:39 | 0.605196E+11 | 277345.56 | 28-OCT-06:10 |
November | 0.229346E+13 | 1335517.90 | 03-NOV-15:09 | 0.156143E+12 | 830105.94 | 24-NOV-07:10 |
December | 0.271065E+13 | 1402668.30 | 26-DEC-08:09 | 0.276802E+12 | 707068.51 | 02-DEC-05:10 |
Annual Sum or Average | 0.278936E+14 | 0.182842E+13 | ||||
Minimum of Months | 0.153971E+13 | 982651.48 | 0.527741E+11 | 94287.47 | ||
Maximum of Months | 0.342864E+13 | 1959609.74 | 0.454158E+12 | 1752188.17 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.232581E+12 | 0.488806E+11 | 0.811612E+12 | 0.162551E+12 | 0.163006E+12 | 0.182597E+11 | 0.00 | 0.835575E+11 | 0.100962E+11 | 0.294498E+10 | 0.622067E+10 | 0.00 | 0.00 |
February | 0.209034E+12 | 0.402025E+11 | 0.102011E+13 | 0.146826E+12 | 0.147299E+12 | 0.187738E+11 | 0.00 | 0.138687E+12 | 0.141941E+11 | 0.344635E+10 | 0.607262E+10 | 0.00 | 0.00 |
March | 0.246521E+12 | 0.390867E+11 | 0.146267E+13 | 0.162740E+12 | 0.167045E+12 | 0.184926E+11 | 0.00 | 0.223567E+12 | 0.480225E+11 | 0.198702E+10 | 0.460342E+10 | 0.00 | 0.00 |
April | 0.219214E+12 | 0.323953E+11 | 0.170311E+13 | 0.157288E+12 | 0.170576E+12 | 0.276576E+11 | 0.00 | 0.300717E+12 | 0.966186E+11 | 0.799627E+09 | 0.164026E+10 | 0.00 | 0.00 |
May | 0.235893E+12 | 0.293732E+11 | 0.820521E+12 | 0.162644E+12 | 0.195787E+12 | 0.557829E+11 | 0.00 | 0.166026E+12 | 0.886415E+11 | 0.168346E+09 | 0.376103E+09 | 0.00 | 0.00 |
June | 0.234365E+12 | 0.263910E+11 | 0.110677E+13 | 0.157466E+12 | 0.225179E+12 | 0.915863E+11 | 0.00 | 0.377883E+12 | 0.158955E+12 | 0.00 | 0.467995E+10 | 0.00 | 0.00 |
July | 0.219588E+12 | 0.279276E+11 | 0.143888E+13 | 0.162465E+12 | 0.243456E+12 | 0.114593E+12 | 0.00 | 0.569254E+12 | 0.192901E+12 | 0.00 | 0.695397E+10 | 0.00 | 0.00 |
August | 0.244941E+12 | 0.313334E+11 | 0.177780E+13 | 0.162739E+12 | 0.259428E+12 | 0.118790E+12 | 0.00 | 0.647992E+12 | 0.179983E+12 | 0.00 | 0.563331E+10 | 0.00 | 0.00 |
September | 0.219676E+12 | 0.354418E+11 | 0.784732E+12 | 0.157287E+12 | 0.202403E+12 | 0.760422E+11 | 0.00 | 0.240298E+12 | 0.132220E+12 | 25735324.77 | 0.275678E+10 | 0.00 | 0.00 |
October | 0.229239E+12 | 0.422686E+11 | 0.112899E+13 | 0.162550E+12 | 0.188540E+12 | 0.461724E+11 | 0.00 | 0.228518E+12 | 0.984992E+11 | 0.670971E+09 | 0.952420E+09 | 0.00 | 0.00 |
November | 0.229077E+12 | 0.458675E+11 | 0.140306E+13 | 0.157362E+12 | 0.159988E+12 | 0.178669E+11 | 0.00 | 0.216648E+12 | 0.591990E+11 | 0.124326E+10 | 0.314486E+10 | 0.00 | 0.00 |
December | 0.225605E+12 | 0.500766E+11 | 0.175516E+13 | 0.162467E+12 | 0.160865E+12 | 0.167531E+11 | 0.00 | 0.279811E+12 | 0.511062E+11 | 0.294180E+10 | 0.586777E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.274573E+13 | 0.449245E+12 | 0.152134E+14 | 0.191438E+13 | 0.228357E+13 | 0.620771E+12 | 0.00 | 0.347296E+13 | 0.113044E+13 | 0.142281E+11 | 0.489021E+11 | 0.00 | 0.00 |
Minimum of Months | 0.209034E+12 | 0.263910E+11 | 0.784732E+12 | 0.146826E+12 | 0.147299E+12 | 0.167531E+11 | 0.00 | 0.835575E+11 | 0.100962E+11 | 0.00 | 0.376103E+09 | 0.00 | 0.00 |
Maximum of Months | 0.246521E+12 | 0.500766E+11 | 0.177780E+13 | 0.162740E+12 | 0.259428E+12 | 0.118790E+12 | 0.00 | 0.647992E+12 | 0.192901E+12 | 0.344635E+10 | 0.695397E+10 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.389126E+12 | 0.00 | 0.650320E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.283696E+12 | 0.00 | 0.594494E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.974369E+11 | 0.00 | 0.676968E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.281275E+11 | 0.00 | 0.600079E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.768000E+09 | 0.00 | 0.602902E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.204979E+10 | 0.00 | 0.562226E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.724880E+09 | 0.00 | 0.527389E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.316626E+10 | 0.00 | 0.556477E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.184119E+09 | 0.00 | 0.525900E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.374196E+10 | 0.00 | 0.567777E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.975378E+11 | 0.00 | 0.586053E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.214962E+12 | 0.00 | 0.618399E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.112152E+13 | 0.00 | 0.706898E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.184119E+09 | 0.00 | 0.525900E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.389126E+12 | 0.00 | 0.676968E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 261074.09 | 02-JAN-16:40 | 37611.08 | 01-JAN-06:10 | 439129.89 | 02-JAN-08:09 | 117200.89 | 03-JAN-08:20 | 102185.66 | 02-JAN-06:19 | 41624.57 | 05-JAN-06:10 | 0.00 | 01-JAN-00:10 |
February | 256360.64 | 15-FEB-16:00 | 37611.08 | 01-FEB-06:10 | 557421.28 | 01-FEB-08:09 | 117194.52 | 28-FEB-08:20 | 91994.68 | 06-FEB-05:10 | 41556.91 | 14-FEB-06:10 | 0.00 | 01-FEB-00:10 |
March | 244593.34 | 02-MAR-16:00 | 37611.08 | 01-MAR-06:10 | 675712.68 | 01-MAR-08:09 | 117195.21 | 16-MAR-07:19 | 116926.71 | 29-MAR-15:20 | 41814.07 | 27-MAR-15:00 | 0.00 | 01-MAR-00:10 |
April | 235684.48 | 14-APR-07:10 | 37611.08 | 01-APR-05:10 | 794004.08 | 03-APR-07:10 | 117190.27 | 14-APR-07:19 | 208522.90 | 07-APR-14:39 | 67180.20 | 07-APR-14:39 | 0.00 | 01-APR-00:10 |
May | 234435.00 | 01-MAY-07:10 | 37611.08 | 01-MAY-18:49 | 439129.89 | 01-MAY-07:10 | 117189.56 | 01-MAY-07:19 | 269639.00 | 30-MAY-13:50 | 69893.45 | 30-MAY-13:00 | 0.00 | 01-MAY-00:10 |
June | 234435.00 | 01-JUN-07:10 | 37611.08 | 01-JUN-19:19 | 557421.28 | 01-JUN-07:10 | 117189.56 | 01-JUN-07:19 | 272897.93 | 22-JUN-13:09 | 70333.84 | 01-JUN-15:30 | 0.00 | 01-JUN-00:10 |
July | 234435.00 | 03-JUL-07:10 | 37611.08 | 01-JUL-19:30 | 675712.68 | 03-JUL-07:10 | 117189.56 | 03-JUL-07:19 | 280421.96 | 11-JUL-14:30 | 66910.26 | 11-JUL-14:30 | 0.00 | 01-JUL-00:10 |
August | 235439.69 | 16-AUG-07:10 | 37611.08 | 01-AUG-19:10 | 794004.08 | 01-AUG-07:10 | 117190.13 | 16-AUG-07:19 | 283348.35 | 22-AUG-14:39 | 75732.46 | 30-AUG-13:50 | 0.00 | 01-AUG-00:10 |
September | 241746.79 | 27-SEP-07:10 | 37611.08 | 01-SEP-05:10 | 439129.89 | 01-SEP-07:10 | 117193.72 | 27-SEP-07:19 | 216968.01 | 01-SEP-13:00 | 74972.30 | 01-SEP-13:00 | 0.00 | 01-SEP-00:10 |
October | 250180.37 | 31-OCT-15:00 | 37611.08 | 01-OCT-05:10 | 557421.28 | 02-OCT-07:10 | 117197.72 | 06-OCT-07:19 | 174441.21 | 05-OCT-15:39 | 69201.80 | 05-OCT-13:09 | 0.00 | 01-OCT-00:10 |
November | 261074.09 | 06-NOV-16:49 | 37611.08 | 01-NOV-05:10 | 675712.68 | 01-NOV-07:10 | 117198.73 | 30-NOV-08:20 | 118611.55 | 03-NOV-13:00 | 41508.27 | 02-NOV-13:30 | 0.00 | 01-NOV-00:10 |
December | 261074.09 | 01-DEC-16:30 | 37611.08 | 01-DEC-06:10 | 794004.08 | 01-DEC-08:09 | 117199.02 | 11-DEC-08:20 | 92135.13 | 21-DEC-13:20 | 41436.03 | 30-DEC-06:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 234435.00 | 37611.08 | 439129.89 | 117189.56 | 91994.68 | 41436.03 | 0.00 | |||||||
Maximum of Months | 261074.09 | 37611.08 | 794004.08 | 117200.89 | 283348.35 | 75732.46 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum} [W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY {Maximum} [W] | HUMIDIFIER:ELECTRICITY {TIMESTAMP} | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 38445.03 | 20-JAN-16:10 | 8666.24 | 24-JAN-11:00 | 6185.89 | 02-JAN-19:00 | 5613.48 | 02-JAN-07:10 | 0.00 | 0.00 |
February | 62385.49 | 17-FEB-14:30 | 16773.12 | 20-FEB-11:00 | 6165.13 | 02-FEB-18:00 | 5613.48 | 01-FEB-07:10 | 0.00 | 0.00 |
March | 188318.48 | 27-MAR-15:00 | 51516.49 | 27-MAR-15:00 | 6031.85 | 22-MAR-17:10 | 5613.48 | 01-MAR-07:10 | 0.00 | 0.00 |
April | 369729.79 | 07-APR-14:39 | 90459.19 | 07-APR-13:30 | 5704.84 | 11-APR-18:00 | 5613.48 | 01-APR-06:10 | 0.00 | 0.00 |
May | 317785.98 | 30-MAY-13:20 | 90459.19 | 30-MAY-07:00 | 3341.87 | 01-MAY-17:00 | 5613.48 | 30-MAY-08:50 | 0.00 | 0.00 |
June | 359416.60 | 23-JUN-09:00 | 90459.19 | 01-JUN-09:00 | 0.00 | 01-JUN-00:10 | 5613.48 | 01-JUN-09:00 | 0.00 | 0.00 |
July | 399312.59 | 20-JUL-14:30 | 90459.19 | 09-JUL-08:09 | 0.00 | 01-JUL-00:10 | 5613.48 | 01-JUL-06:10 | 0.00 | 0.00 |
August | 448279.91 | 04-AUG-13:00 | 90459.19 | 01-AUG-06:19 | 0.00 | 01-AUG-00:10 | 5613.48 | 01-AUG-06:10 | 0.00 | 0.00 |
September | 325948.46 | 01-SEP-13:00 | 90459.19 | 01-SEP-06:30 | 1987.51 | 23-SEP-13:00 | 5613.48 | 01-SEP-06:10 | 0.00 | 0.00 |
October | 316607.46 | 04-OCT-13:39 | 90459.19 | 03-OCT-12:09 | 4834.73 | 28-OCT-16:30 | 5613.48 | 03-OCT-12:20 | 0.00 | 0.00 |
November | 151691.56 | 03-NOV-13:00 | 50029.62 | 10-NOV-07:00 | 4841.10 | 22-NOV-19:00 | 5613.48 | 01-NOV-06:10 | 0.00 | 0.00 |
December | 109011.76 | 18-DEC-14:39 | 44729.82 | 17-DEC-14:00 | 6019.31 | 14-DEC-21:00 | 5613.48 | 01-DEC-07:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 38445.03 | 8666.24 | 0.00 | 5613.48 | 0.00 | 0.00 | ||||
Maximum of Months | 448279.91 | 90459.19 | 6185.89 | 5613.48 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 982651.48 | 20-JAN-16:00 | 261074.09 | 439129.89 | 37611.08 | 83160.37 | 74212.12 | 41368.23 | 0.00 | 38126.85 | 4881.56 |
February | 1099809.15 | 02-FEB-08:09 | 237848.94 | 557421.28 | 0.00 | 117102.48 | 72908.15 | 41370.86 | 0.00 | 59747.85 | 6521.57 |
March | 1374730.96 | 27-MAR-15:00 | 234435.00 | 675712.68 | 0.00 | 83146.17 | 99788.07 | 41814.07 | 0.00 | 188318.48 | 51516.49 |
April | 1802086.15 | 07-APR-14:39 | 234435.00 | 794004.08 | 0.00 | 37754.99 | 208522.90 | 67180.20 | 0.00 | 369729.79 | 90459.19 |
May | 1457384.89 | 30-MAY-13:50 | 234435.00 | 439129.89 | 0.00 | 37754.99 | 269639.00 | 69759.88 | 0.00 | 316206.95 | 90459.19 |
June | 1611494.27 | 22-JUN-13:09 | 234435.00 | 557421.28 | 0.00 | 37754.99 | 272897.93 | 68240.50 | 0.00 | 350285.38 | 90459.19 |
July | 1788163.72 | 11-JUL-15:20 | 234435.00 | 675712.68 | 0.00 | 83146.17 | 263468.43 | 66735.23 | 0.00 | 373271.44 | 90459.19 |
August | 1959609.74 | 22-AUG-14:39 | 234435.00 | 794004.08 | 0.00 | 37754.99 | 283348.35 | 70698.45 | 0.00 | 445167.36 | 90459.19 |
September | 1421538.99 | 01-SEP-13:00 | 234435.00 | 439129.89 | 0.00 | 37754.99 | 216968.01 | 74972.30 | 0.00 | 325948.46 | 90459.19 |
October | 1490517.29 | 05-OCT-15:39 | 234435.00 | 557421.28 | 0.00 | 83146.17 | 174441.21 | 64506.70 | 0.00 | 280494.25 | 90459.19 |
November | 1335517.90 | 03-NOV-15:09 | 234435.00 | 675712.68 | 0.00 | 83146.17 | 116374.49 | 41426.78 | 0.00 | 135045.65 | 49377.12 |
December | 1402668.30 | 26-DEC-08:09 | 241078.59 | 794004.08 | 0.00 | 117103.06 | 74907.66 | 41375.90 | 0.00 | 106016.51 | 25375.78 |
Annual Sum or Average | |||||||||||
Minimum of Months | 982651.48 | 234435.00 | 439129.89 | 0.00 | 37754.99 | 72908.15 | 41368.23 | 0.00 | 38126.85 | 4881.56 | |
Maximum of Months | 1959609.74 | 261074.09 | 794004.08 | 37611.08 | 117103.06 | 283348.35 | 74972.30 | 0.00 | 445167.36 | 90459.19 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 1746492.30 | 02-JAN-05:10 | 0.00 | 82473.33 | 31-JAN-12:39 | 0.00 |
February | 0.00 | 0.00 | 1348630.26 | 13-FEB-07:10 | 0.00 | 82525.26 | 08-FEB-12:39 | 0.00 |
March | 0.00 | 0.00 | 729245.82 | 13-MAR-04:10 | 0.00 | 82276.28 | 01-MAR-12:50 | 0.00 |
April | 0.00 | 0.00 | 439008.57 | 03-APR-04:10 | 0.00 | 80784.35 | 03-APR-11:20 | 0.00 |
May | 0.00 | 0.00 | 128851.66 | 30-MAY-14:09 | 0.00 | 78493.21 | 03-MAY-11:20 | 0.00 |
June | 0.00 | 0.00 | 189079.21 | 01-JUN-15:20 | 0.00 | 75615.45 | 02-JUN-11:39 | 0.00 |
July | 0.00 | 0.00 | 92647.23 | 11-JUL-14:50 | 0.00 | 72658.36 | 06-JUL-11:20 | 0.00 |
August | 0.00 | 0.00 | 148862.32 | 22-AUG-15:50 | 0.00 | 71726.77 | 31-AUG-11:20 | 0.00 |
September | 0.00 | 0.00 | 65293.94 | 01-SEP-17:19 | 0.00 | 73646.05 | 27-SEP-11:39 | 0.00 |
October | 0.00 | 0.00 | 261925.29 | 28-OCT-06:10 | 0.00 | 76694.73 | 31-OCT-11:20 | 0.00 |
November | 0.00 | 0.00 | 801003.29 | 24-NOV-07:10 | 0.00 | 79491.69 | 29-NOV-12:50 | 0.00 |
December | 0.00 | 0.00 | 701372.64 | 02-DEC-05:10 | 0.00 | 81484.90 | 29-DEC-12:39 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 65293.94 | 0.00 | 71726.77 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 1746492.30 | 0.00 | 82525.26 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.61 | 0.00 | 25.61 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.72 | 0.00 | 25.72 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 25.69 | 0.00 | 25.69 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 25.91 | 0.00 | 25.91 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 26.05 | 0.00 | 26.05 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 26.10 | 0.00 | 26.10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 26.16 | 0.00 | 26.16 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 26.43 | 0.17 | 26.39 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 26.79 | 0.00 | 26.79 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 14.17 | 26.95 | 0.50 | 26.96 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 26.84 | 0.17 | 26.85 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 26.14 | 0.00 | 26.14 |
Annual Sum or Average | 0.00 | 0.00 | 62.83 | 26.55 | 0.83 | 26.55 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.61 | 0.00 | 25.61 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 14.17 | 26.95 | 0.50 | 26.96 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.62 | 0.00 | 25.62 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.56 | 0.00 | 25.56 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.58 | 0.00 | 25.58 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.57 | 0.00 | 25.57 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.58 | 0.00 | 25.58 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.62 | 0.00 | 25.62 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.56 | 0.00 | 25.56 |
Annual Sum or Average | 0.00 | 0.00 | 2.33 | 25.59 | 0.00 | 25.59 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.62 | 0.00 | 25.62 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.33 | 19.37 | 1.17 | 19.57 | 0.00 | 19.57 | 0.00 | 19.57 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2.33 | 19.37 | 1.17 | 19.57 | 0.00 | 19.57 | 0.00 | 19.57 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.33 | 19.37 | 1.17 | 19.57 | 0.00 | 19.57 | 0.00 | 19.57 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.17 | 18.81 | 0.83 | 19.00 | 0.00 | 19.00 | 0.00 | 19.00 |
February | 2.17 | 18.73 | 0.33 | 18.94 | 0.00 | 18.94 | 0.00 | 18.94 |
March | 0.33 | 19.16 | 0.00 | 19.16 | 0.00 | 19.16 | 0.00 | 19.16 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.83 | 19.00 | 0.00 | 19.00 | 0.00 | 19.00 | 0.00 | 19.00 |
December | 0.67 | 19.29 | 0.00 | 19.29 | 0.00 | 19.29 | 0.00 | 19.29 |
Annual Sum or Average | 8.17 | 18.86 | 1.17 | 19.01 | 0.00 | 19.01 | 0.00 | 19.01 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4.17 | 19.29 | 0.83 | 19.29 | 0.00 | 19.29 | 0.00 | 19.29 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 18.85 | 0.00 | 18.85 | 0.00 | 18.85 | 0.00 | 18.85 |
February | 0.33 | 18.89 | 0.00 | 18.89 | 0.00 | 18.89 | 0.00 | 18.89 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.85 | 0.00 | 25.85 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 26.75 | 0.67 | 26.98 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.67 | 18.87 | 0.00 | 18.87 | 1.33 | 23.97 | 0.67 | 24.81 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 18.89 | 0.00 | 18.89 | 1.00 | 26.75 | 0.67 | 26.98 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 18.87 | 0.00 | 18.87 | 0.00 | 18.87 | 0.00 | 18.87 |
February | 0.50 | 19.05 | 0.00 | 19.05 | 0.00 | 19.05 | 0.00 | 19.05 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.39 | 1.17 | 27.39 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.77 | 4.83 | 27.77 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.84 | 1.67 | 27.84 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.66 | 4.83 | 27.73 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.62 | 3.67 | 27.62 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.91 | 3.50 | 27.91 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.28 | 0.17 | 27.28 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.83 | 18.98 | 0.00 | 18.98 | 20.17 | 27.37 | 19.83 | 27.56 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 19.05 | 0.00 | 19.05 | 5.17 | 27.91 | 4.83 | 27.91 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.50 | 18.82 | 0.00 | 18.82 | 0.00 | 18.82 | 0.00 | 18.82 |
February | 0.50 | 18.88 | 0.00 | 18.88 | 0.17 | 20.98 | 0.17 | 22.24 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.42 | 0.17 | 27.42 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.13 | 2.33 | 27.13 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.37 | 1.67 | 27.37 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27.42 | 6.50 | 27.49 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 27.34 | 5.00 | 27.54 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 27.81 | 5.83 | 27.88 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.64 | 5.17 | 27.64 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.43 | 1.50 | 27.43 |
Annual Sum or Average | 1.00 | 18.85 | 0.00 | 18.85 | 31.17 | 27.22 | 28.33 | 27.42 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 18.88 | 0.00 | 18.88 | 7.17 | 27.81 | 6.50 | 27.88 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 19.20 | 0.00 | 19.20 | 0.00 | 19.20 | 0.00 | 19.20 |
February | 0.17 | 19.43 | 0.00 | 19.43 | 0.00 | 19.43 | 0.00 | 19.43 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.61 | 0.50 | 27.63 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 27.44 | 4.17 | 27.63 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.78 | 4.17 | 27.79 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 16.33 | 27.06 | 5.00 | 27.29 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 32.17 | 27.28 | 10.67 | 27.46 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 32.83 | 27.22 | 8.83 | 27.36 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 27.53 | 3.50 | 27.73 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.73 | 2.00 | 27.73 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.32 | 0.17 | 27.32 |
Annual Sum or Average | 0.33 | 19.32 | 0.00 | 19.32 | 103.50 | 27.26 | 39.00 | 27.45 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 19.43 | 0.00 | 19.43 | 32.83 | 27.78 | 10.67 | 27.79 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 27.83 | 17.10 | 8.50 | 17.18 | 0.00 | 17.18 | 0.00 | 17.18 |
February | 22.50 | 17.50 | 6.17 | 17.81 | 0.00 | 17.81 | 0.00 | 17.81 |
March | 1.83 | 19.20 | 0.17 | 19.30 | 0.00 | 19.30 | 0.00 | 19.30 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 2.67 | 19.03 | 0.33 | 19.18 | 0.00 | 19.18 | 0.00 | 19.18 |
December | 6.00 | 18.02 | 0.33 | 18.15 | 0.00 | 18.15 | 0.00 | 18.15 |
Annual Sum or Average | 60.83 | 17.49 | 15.50 | 17.63 | 0.00 | 17.63 | 0.00 | 17.63 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 27.83 | 19.20 | 8.50 | 19.30 | 0.00 | 19.30 | 0.00 | 19.30 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 17.00 | 16.18 | 3.00 | 16.00 | 0.00 | 16.00 | 0.00 | 16.00 |
February | 10.17 | 16.84 | 0.00 | 16.84 | 0.00 | 16.84 | 0.00 | 16.84 |
March | 1.33 | 19.06 | 0.00 | 19.06 | 0.00 | 19.06 | 0.00 | 19.06 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.84 | 4.33 | 27.84 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.76 | 2.50 | 27.76 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 27.80 | 7.33 | 27.83 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.79 | 4.17 | 27.79 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.87 | 4.17 | 27.87 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.67 | 18.71 | 0.00 | 18.71 | 0.00 | 18.71 | 0.00 | 18.71 |
December | 5.00 | 18.00 | 0.00 | 18.00 | 0.00 | 18.00 | 0.00 | 18.00 |
Annual Sum or Average | 35.17 | 16.86 | 3.00 | 16.71 | 22.67 | 20.85 | 22.50 | 22.73 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 17.00 | 19.06 | 3.00 | 19.06 | 7.50 | 27.87 | 7.33 | 27.87 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 15.83 | 16.72 | 2.67 | 16.76 | 0.00 | 16.76 | 0.00 | 16.76 |
February | 7.33 | 17.53 | 0.00 | 17.53 | 0.00 | 17.53 | 0.00 | 17.53 |
March | 0.67 | 18.93 | 0.00 | 18.93 | 0.00 | 18.93 | 0.00 | 18.93 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.51 | 1.67 | 27.51 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.34 | 1.00 | 27.34 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.46 | 5.50 | 27.52 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.76 | 4.83 | 27.77 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27.46 | 7.00 | 27.46 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.64 | 4.50 | 27.64 |
November | 1.33 | 19.08 | 0.00 | 19.08 | 0.00 | 19.08 | 0.00 | 19.08 |
December | 3.00 | 18.81 | 0.00 | 18.81 | 0.17 | 19.25 | 0.17 | 19.66 |
Annual Sum or Average | 28.17 | 17.32 | 2.67 | 17.29 | 25.67 | 21.95 | 24.67 | 23.66 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 15.83 | 19.08 | 2.67 | 19.08 | 7.17 | 27.76 | 7.00 | 27.77 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 14.67 | 16.24 | 3.33 | 16.00 | 0.00 | 16.00 | 0.00 | 16.00 |
February | 7.33 | 16.98 | 0.00 | 16.98 | 0.00 | 16.98 | 0.00 | 16.98 |
March | 0.67 | 18.98 | 0.00 | 18.98 | 0.00 | 18.98 | 0.00 | 18.98 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.83 | 0.33 | 27.88 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.57 | 3.00 | 27.58 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.93 | 2.83 | 27.99 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 27.70 | 5.33 | 27.80 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.14 | 2.50 | 27.39 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 28.11 | 2.33 | 28.14 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.41 | 0.17 | 27.41 |
November | 1.17 | 18.93 | 0.00 | 18.93 | 0.00 | 18.93 | 0.00 | 18.93 |
December | 3.33 | 18.23 | 0.00 | 18.23 | 0.00 | 18.23 | 0.00 | 18.23 |
Annual Sum or Average | 27.17 | 16.87 | 3.33 | 16.66 | 27.00 | 21.82 | 16.50 | 23.19 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.00 | 0.00 | 16.00 |
Maximum of Months | 14.67 | 18.98 | 3.33 | 18.98 | 9.00 | 28.11 | 5.33 | 28.14 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 64.33 | 16.35 | 19.50 | 16.49 | 0.00 | 16.49 | 0.00 | 16.49 |
February | 55.17 | 16.56 | 20.33 | 16.77 | 0.00 | 16.77 | 0.00 | 16.77 |
March | 12.00 | 18.19 | 1.83 | 18.38 | 0.00 | 18.38 | 0.00 | 18.38 |
April | 2.17 | 18.80 | 0.17 | 18.92 | 0.00 | 18.92 | 0.00 | 18.92 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.19 | 1.83 | 27.29 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.43 | 1.17 | 27.44 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.33 | 19.36 | 0.00 | 19.36 | 0.00 | 19.36 | 0.00 | 19.36 |
November | 16.83 | 17.20 | 4.00 | 17.29 | 0.00 | 17.29 | 0.00 | 17.29 |
December | 27.67 | 17.05 | 6.50 | 17.05 | 0.00 | 17.05 | 0.00 | 17.05 |
Annual Sum or Average | 178.50 | 16.77 | 52.33 | 16.88 | 3.83 | 17.05 | 3.00 | 17.18 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 64.33 | 19.36 | 20.33 | 19.36 | 2.50 | 27.43 | 1.83 | 27.44 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 44.50 | 15.44 | 11.50 | 15.35 | 0.00 | 15.35 | 0.00 | 15.35 |
February | 33.17 | 15.77 | 8.33 | 15.67 | 0.00 | 15.67 | 0.00 | 15.67 |
March | 8.50 | 17.81 | 0.17 | 17.86 | 0.00 | 17.86 | 0.00 | 17.86 |
April | 1.67 | 18.56 | 0.00 | 18.56 | 0.00 | 18.56 | 0.00 | 18.56 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.76 | 5.33 | 27.76 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.77 | 3.00 | 27.77 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 12.00 | 27.76 | 11.33 | 27.79 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.80 | 5.33 | 27.81 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.84 | 4.17 | 27.84 |
October | 0.17 | 19.38 | 0.00 | 19.38 | 0.00 | 19.38 | 0.00 | 19.38 |
November | 10.33 | 16.68 | 0.83 | 16.54 | 0.00 | 16.54 | 0.00 | 16.54 |
December | 20.50 | 16.37 | 3.33 | 16.13 | 0.00 | 16.13 | 0.00 | 16.13 |
Annual Sum or Average | 118.83 | 16.02 | 24.17 | 15.86 | 30.17 | 17.94 | 29.17 | 19.36 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.35 | 0.00 | 15.35 |
Maximum of Months | 44.50 | 19.38 | 11.50 | 19.38 | 12.00 | 27.84 | 11.33 | 27.84 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 35.83 | 15.94 | 8.17 | 15.88 | 0.00 | 15.88 | 0.00 | 15.88 |
February | 26.83 | 16.41 | 3.50 | 16.47 | 0.00 | 16.47 | 0.00 | 16.47 |
March | 6.00 | 18.37 | 0.17 | 18.42 | 0.00 | 18.42 | 0.00 | 18.42 |
April | 1.67 | 18.67 | 0.00 | 18.67 | 0.00 | 18.67 | 0.00 | 18.67 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.40 | 2.50 | 27.40 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.47 | 2.17 | 27.47 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 27.56 | 8.00 | 27.60 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.91 | 5.17 | 27.92 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 28.11 | 5.33 | 28.14 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.67 | 2.17 | 27.67 |
November | 7.67 | 17.38 | 0.33 | 17.28 | 0.00 | 17.28 | 0.00 | 17.28 |
December | 16.67 | 16.86 | 1.17 | 16.77 | 0.00 | 16.77 | 0.00 | 16.77 |
Annual Sum or Average | 94.67 | 16.55 | 13.33 | 16.49 | 27.17 | 18.75 | 25.33 | 20.17 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.88 | 0.00 | 15.88 |
Maximum of Months | 35.83 | 18.67 | 8.17 | 18.67 | 8.83 | 28.11 | 8.00 | 28.14 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 34.17 | 15.52 | 8.50 | 15.36 | 0.00 | 15.36 | 0.00 | 15.36 |
February | 22.67 | 15.84 | 4.33 | 15.63 | 0.00 | 15.63 | 0.00 | 15.63 |
March | 5.17 | 18.57 | 0.00 | 18.57 | 0.00 | 18.57 | 0.00 | 18.57 |
April | 1.17 | 18.90 | 0.00 | 18.90 | 0.67 | 22.12 | 0.50 | 23.33 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.64 | 3.33 | 27.66 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 28.04 | 3.17 | 28.08 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 27.95 | 5.83 | 28.04 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 27.37 | 3.17 | 27.58 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 28.09 | 2.67 | 28.11 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6.67 | 17.44 | 0.33 | 17.33 | 0.00 | 17.33 | 0.00 | 17.33 |
December | 14.00 | 17.03 | 2.00 | 16.73 | 0.00 | 16.73 | 0.00 | 16.73 |
Annual Sum or Average | 83.83 | 16.25 | 15.17 | 16.00 | 29.83 | 18.74 | 18.67 | 19.92 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 34.17 | 18.90 | 8.50 | 18.90 | 10.17 | 28.09 | 5.83 | 28.11 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 27.68 | 7.83 | 27.68 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 7.83 | 27.68 | 7.83 | 27.68 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 27.68 | 7.83 | 27.68 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 27.68 | 7.33 | 27.68 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 7.33 | 27.68 | 7.33 | 27.68 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 27.68 | 7.33 | 27.68 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.63 | 3.33 | 27.63 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 3.33 | 27.63 | 3.33 | 27.63 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.63 | 3.33 | 27.63 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.75 | 2.33 | 27.75 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 332.00 | 28.62 | 295.83 | 28.65 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 334.33 | 28.61 | 298.17 | 28.65 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 332.00 | 28.62 | 295.83 | 28.65 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 311.50 | 23.84 | 42.83 | 24.02 | 0.00 | 24.02 |
February | 298.50 | 23.86 | 27.33 | 24.06 | 0.00 | 24.06 |
March | 144.00 | 23.99 | 88.67 | 24.57 | 0.00 | 24.57 |
April | 50.17 | 24.01 | 139.00 | 25.06 | 0.00 | 25.06 |
May | 32.00 | 24.00 | 274.50 | 24.73 | 24.83 | 24.68 |
June | 151.17 | 24.79 | 438.00 | 24.57 | 151.17 | 24.61 |
July | 230.17 | 25.23 | 497.00 | 24.79 | 230.17 | 24.90 |
August | 102.33 | 25.21 | 476.50 | 24.64 | 102.33 | 24.72 |
September | 59.00 | 25.21 | 388.83 | 24.74 | 59.00 | 24.80 |
October | 56.00 | 24.32 | 336.17 | 24.77 | 23.83 | 24.77 |
November | 52.83 | 24.00 | 137.00 | 25.28 | 0.00 | 25.28 |
December | 202.33 | 24.00 | 85.83 | 24.69 | 0.00 | 24.69 |
Annual Sum or Average | 1690.00 | 24.31 | 2931.67 | 24.64 | 591.33 | 24.68 |
Minimum of Months | 32.00 | 23.84 | 27.33 | 24.02 | 0.00 | 24.02 |
Maximum of Months | 311.50 | 25.23 | 497.00 | 25.28 | 230.17 | 25.28 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 397.67 | 23.61 | 9.33 | 23.62 | 0.00 | 23.62 |
February | 335.00 | 23.83 | 10.00 | 23.88 | 0.00 | 23.88 |
March | 148.00 | 23.92 | 76.17 | 24.34 | 0.00 | 24.34 |
April | 44.67 | 23.93 | 148.83 | 24.65 | 0.00 | 24.65 |
May | 15.33 | 23.90 | 249.17 | 24.43 | 0.00 | 24.43 |
June | 0.00 | 0.00 | 432.17 | 24.27 | 0.00 | 24.27 |
July | 0.00 | 0.00 | 497.00 | 24.21 | 0.00 | 24.21 |
August | 0.00 | 0.00 | 480.17 | 24.18 | 0.00 | 24.18 |
September | 5.17 | 23.87 | 389.17 | 24.38 | 0.00 | 24.38 |
October | 46.00 | 23.98 | 311.83 | 24.44 | 0.00 | 24.44 |
November | 86.00 | 23.92 | 109.67 | 24.76 | 0.00 | 24.76 |
December | 194.17 | 23.94 | 40.17 | 24.24 | 0.00 | 24.24 |
Annual Sum or Average | 1272.00 | 23.80 | 2753.67 | 24.23 | 0.00 | 24.23 |
Minimum of Months | 0.00 | 0.00 | 9.33 | 23.62 | 0.00 | 23.62 |
Maximum of Months | 397.67 | 23.98 | 497.00 | 24.76 | 0.00 | 24.76 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.91 | 91.00 | 21.62 | 91.00 | 21.41 |
February | 454.00 | 22.41 | 39.33 | 22.28 | 39.33 | 22.18 |
March | 463.67 | 23.30 | 4.83 | 23.31 | 0.00 | 23.31 |
April | 277.33 | 23.45 | 34.17 | 23.58 | 0.00 | 23.58 |
May | 100.50 | 23.68 | 185.83 | 24.07 | 0.00 | 24.07 |
June | 13.00 | 23.68 | 417.83 | 24.21 | 0.00 | 24.21 |
July | 0.00 | 0.00 | 490.17 | 24.22 | 0.00 | 24.22 |
August | 0.00 | 0.00 | 456.00 | 24.25 | 0.00 | 24.25 |
September | 27.00 | 23.59 | 327.83 | 24.23 | 0.00 | 24.23 |
October | 134.83 | 23.75 | 221.17 | 24.05 | 0.00 | 24.05 |
November | 358.67 | 23.10 | 36.33 | 23.23 | 0.00 | 23.23 |
December | 497.00 | 22.79 | 4.50 | 22.77 | 4.50 | 22.76 |
Annual Sum or Average | 2828.00 | 22.85 | 2309.00 | 23.38 | 134.83 | 23.30 |
Minimum of Months | 0.00 | 0.00 | 4.50 | 21.62 | 0.00 | 21.41 |
Maximum of Months | 502.00 | 23.75 | 490.17 | 24.25 | 91.00 | 24.25 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.88 | 215.50 | 20.55 | 215.50 | 20.37 |
February | 454.00 | 21.12 | 205.67 | 20.85 | 205.67 | 20.71 |
March | 501.83 | 22.14 | 53.67 | 21.98 | 53.67 | 21.86 |
April | 365.33 | 22.61 | 47.83 | 22.65 | 17.00 | 22.56 |
May | 177.17 | 23.36 | 145.50 | 23.74 | 0.00 | 23.74 |
June | 10.83 | 23.61 | 416.83 | 24.22 | 0.00 | 24.22 |
July | 0.00 | 0.00 | 497.00 | 24.29 | 0.00 | 24.29 |
August | 0.17 | 27.09 | 458.33 | 24.28 | 0.17 | 24.28 |
September | 69.50 | 23.33 | 313.50 | 24.06 | 0.00 | 24.06 |
October | 274.83 | 22.96 | 160.00 | 23.34 | 5.17 | 23.31 |
November | 471.00 | 21.97 | 80.33 | 21.71 | 78.67 | 21.51 |
December | 497.00 | 21.18 | 165.17 | 20.87 | 165.17 | 20.69 |
Annual Sum or Average | 3323.67 | 21.86 | 2759.33 | 22.43 | 741.00 | 22.17 |
Minimum of Months | 0.00 | 0.00 | 47.83 | 20.55 | 0.00 | 20.37 |
Maximum of Months | 502.00 | 27.09 | 497.00 | 24.29 | 215.50 | 24.29 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.34 | 172.50 | 21.11 | 172.50 | 20.98 |
February | 454.00 | 21.58 | 126.00 | 21.38 | 126.00 | 21.25 |
March | 480.83 | 22.77 | 9.83 | 22.79 | 2.33 | 22.78 |
April | 299.83 | 23.27 | 58.50 | 23.44 | 0.00 | 23.44 |
May | 94.83 | 23.64 | 189.33 | 24.09 | 0.00 | 24.09 |
June | 4.33 | 25.23 | 450.17 | 24.31 | 3.17 | 24.32 |
July | 8.83 | 26.68 | 497.00 | 24.43 | 8.83 | 24.47 |
August | 5.50 | 26.72 | 481.17 | 24.31 | 5.50 | 24.33 |
September | 58.17 | 23.82 | 341.17 | 24.25 | 4.00 | 24.27 |
October | 203.83 | 23.40 | 208.33 | 23.77 | 0.00 | 23.77 |
November | 422.50 | 22.83 | 15.00 | 22.82 | 7.67 | 22.79 |
December | 497.00 | 22.24 | 16.67 | 22.19 | 16.67 | 22.15 |
Annual Sum or Average | 3031.67 | 22.44 | 2565.67 | 23.08 | 346.67 | 22.95 |
Minimum of Months | 4.33 | 21.34 | 9.83 | 21.11 | 0.00 | 20.98 |
Maximum of Months | 502.00 | 26.72 | 497.00 | 24.43 | 172.50 | 24.47 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 500.83 | 21.34 | 154.83 | 21.12 | 154.83 | 20.99 |
February | 449.17 | 21.71 | 100.50 | 21.53 | 100.50 | 21.40 |
March | 435.83 | 22.49 | 16.67 | 22.51 | 8.50 | 22.48 |
April | 285.67 | 22.84 | 95.00 | 23.26 | 1.67 | 23.28 |
May | 116.00 | 23.79 | 252.67 | 24.27 | 15.50 | 24.38 |
June | 14.17 | 26.25 | 459.67 | 24.35 | 12.17 | 24.41 |
July | 30.50 | 26.78 | 497.00 | 24.51 | 30.50 | 24.63 |
August | 16.83 | 26.62 | 485.50 | 24.32 | 16.00 | 24.39 |
September | 69.83 | 24.27 | 365.83 | 24.40 | 20.00 | 24.50 |
October | 182.17 | 23.24 | 215.67 | 23.79 | 2.50 | 23.81 |
November | 407.50 | 22.53 | 22.17 | 22.56 | 9.83 | 22.52 |
December | 491.67 | 21.92 | 26.83 | 21.86 | 26.83 | 21.80 |
Annual Sum or Average | 3000.17 | 22.35 | 2692.33 | 23.10 | 398.83 | 23.03 |
Minimum of Months | 14.17 | 21.34 | 16.67 | 21.12 | 1.67 | 20.99 |
Maximum of Months | 500.83 | 26.78 | 497.00 | 24.51 | 154.83 | 24.63 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 456.17 | 21.51 | 139.50 | 21.24 | 135.83 | 21.05 |
February | 388.00 | 22.01 | 92.67 | 21.86 | 83.00 | 21.68 |
March | 377.67 | 22.65 | 54.50 | 22.72 | 17.17 | 22.65 |
April | 263.00 | 22.96 | 103.33 | 23.39 | 3.17 | 23.40 |
May | 117.17 | 23.57 | 218.67 | 24.12 | 6.00 | 24.17 |
June | 18.17 | 25.70 | 454.83 | 24.38 | 13.00 | 24.44 |
July | 34.83 | 26.79 | 497.00 | 24.59 | 34.83 | 24.72 |
August | 21.17 | 26.93 | 497.00 | 24.45 | 21.17 | 24.55 |
September | 59.00 | 25.03 | 405.00 | 24.54 | 26.50 | 24.66 |
October | 112.67 | 23.80 | 308.33 | 24.30 | 12.00 | 24.37 |
November | 327.00 | 22.69 | 71.83 | 22.89 | 12.17 | 22.82 |
December | 413.50 | 22.20 | 44.33 | 22.21 | 31.67 | 22.11 |
Annual Sum or Average | 2588.33 | 22.58 | 2887.00 | 23.35 | 396.50 | 23.28 |
Minimum of Months | 18.17 | 21.51 | 44.33 | 21.24 | 3.17 | 21.05 |
Maximum of Months | 456.17 | 26.93 | 497.00 | 24.59 | 135.83 | 24.72 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 487.50 | 21.86 | 76.50 | 21.69 | 75.83 | 21.56 |
February | 413.50 | 22.46 | 32.67 | 22.44 | 24.33 | 22.36 |
March | 204.00 | 23.46 | 100.17 | 23.85 | 1.67 | 23.86 |
April | 54.50 | 24.55 | 258.17 | 24.74 | 15.33 | 24.85 |
May | 36.00 | 25.16 | 353.83 | 24.57 | 18.00 | 24.67 |
June | 37.00 | 26.95 | 480.83 | 24.68 | 37.00 | 24.83 |
July | 76.83 | 26.82 | 497.00 | 24.91 | 76.83 | 25.14 |
August | 69.67 | 26.77 | 514.00 | 24.78 | 69.67 | 24.99 |
September | 29.50 | 26.22 | 417.83 | 24.61 | 23.00 | 24.72 |
October | 58.33 | 24.02 | 324.50 | 24.45 | 6.00 | 24.49 |
November | 199.83 | 23.30 | 109.83 | 23.87 | 0.33 | 23.88 |
December | 332.00 | 23.44 | 23.83 | 23.60 | 0.00 | 23.60 |
Annual Sum or Average | 1998.67 | 23.27 | 3189.17 | 24.00 | 348.00 | 24.07 |
Minimum of Months | 29.50 | 21.86 | 23.83 | 21.69 | 0.00 | 21.56 |
Maximum of Months | 487.50 | 26.95 | 514.00 | 24.91 | 76.83 | 25.14 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.09 | 396.33 | 19.98 | 396.33 | 19.93 |
February | 454.00 | 20.27 | 385.00 | 20.21 | 385.00 | 20.18 |
March | 513.33 | 21.11 | 186.67 | 20.91 | 186.67 | 20.79 |
April | 420.67 | 22.02 | 50.50 | 21.94 | 37.67 | 21.81 |
May | 246.83 | 23.18 | 116.17 | 23.51 | 0.00 | 23.51 |
June | 42.00 | 24.83 | 418.33 | 24.30 | 27.67 | 24.36 |
July | 58.17 | 25.87 | 497.00 | 24.57 | 58.17 | 24.70 |
August | 30.33 | 25.87 | 461.00 | 24.43 | 29.17 | 24.51 |
September | 125.83 | 23.27 | 273.67 | 23.90 | 9.67 | 23.92 |
October | 349.67 | 22.43 | 115.17 | 22.67 | 20.17 | 22.58 |
November | 489.00 | 21.15 | 158.00 | 20.87 | 158.00 | 20.70 |
December | 497.00 | 20.37 | 405.00 | 20.30 | 405.00 | 20.27 |
Annual Sum or Average | 3728.83 | 21.37 | 3462.83 | 21.85 | 1713.50 | 21.59 |
Minimum of Months | 30.33 | 20.09 | 50.50 | 19.98 | 0.00 | 19.93 |
Maximum of Months | 513.33 | 25.87 | 497.00 | 24.57 | 405.00 | 24.70 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 20.00 | 331.67 | 19.86 | 331.67 | 19.80 |
February | 385.00 | 20.39 | 288.33 | 20.25 | 288.33 | 20.20 |
March | 422.50 | 21.32 | 112.33 | 21.07 | 112.33 | 20.90 |
April | 302.83 | 22.02 | 76.83 | 22.36 | 18.50 | 22.27 |
May | 188.33 | 23.13 | 150.67 | 23.84 | 13.50 | 23.96 |
June | 37.67 | 25.48 | 362.33 | 24.49 | 27.50 | 24.60 |
July | 76.00 | 26.43 | 421.67 | 24.87 | 76.00 | 25.07 |
August | 40.67 | 26.46 | 408.33 | 24.65 | 39.67 | 24.81 |
September | 115.17 | 23.68 | 264.17 | 24.24 | 25.50 | 24.36 |
October | 251.83 | 22.51 | 112.00 | 22.97 | 6.00 | 22.94 |
November | 413.33 | 21.23 | 120.83 | 20.93 | 120.83 | 20.74 |
December | 422.00 | 20.42 | 296.50 | 20.28 | 296.50 | 20.22 |
Annual Sum or Average | 3082.33 | 21.49 | 2945.67 | 22.08 | 1356.33 | 21.85 |
Minimum of Months | 37.67 | 20.00 | 76.83 | 19.86 | 6.00 | 19.80 |
Maximum of Months | 427.00 | 26.46 | 421.67 | 24.87 | 331.67 | 25.07 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 475.83 | 20.72 | 254.00 | 20.35 | 254.00 | 20.17 |
February | 406.83 | 21.22 | 205.83 | 20.95 | 198.00 | 20.76 |
March | 410.67 | 21.74 | 112.17 | 21.65 | 84.67 | 21.46 |
April | 328.50 | 22.23 | 97.17 | 22.55 | 22.33 | 22.45 |
May | 197.83 | 23.17 | 166.83 | 23.74 | 4.83 | 23.78 |
June | 43.00 | 25.01 | 432.17 | 24.36 | 26.17 | 24.44 |
July | 73.67 | 26.23 | 497.00 | 24.70 | 73.67 | 24.88 |
August | 43.33 | 26.54 | 489.33 | 24.60 | 43.33 | 24.74 |
September | 84.00 | 24.40 | 375.17 | 24.41 | 31.17 | 24.55 |
October | 162.33 | 23.28 | 276.50 | 24.01 | 13.00 | 24.08 |
November | 383.17 | 21.83 | 111.67 | 21.71 | 77.50 | 21.48 |
December | 442.67 | 21.24 | 209.00 | 21.00 | 199.00 | 20.81 |
Annual Sum or Average | 3051.83 | 21.97 | 3226.83 | 22.65 | 1027.67 | 22.45 |
Minimum of Months | 43.00 | 20.72 | 97.17 | 20.35 | 4.83 | 20.17 |
Maximum of Months | 475.83 | 26.54 | 497.00 | 24.70 | 254.00 | 24.88 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.35 | 325.67 | 20.16 | 325.67 | 20.07 |
February | 453.33 | 20.69 | 290.17 | 20.49 | 290.17 | 20.40 |
March | 461.00 | 21.50 | 108.83 | 21.38 | 98.83 | 21.25 |
April | 346.50 | 22.14 | 81.33 | 22.44 | 16.50 | 22.39 |
May | 187.00 | 23.18 | 207.50 | 23.82 | 9.67 | 23.90 |
June | 43.50 | 25.52 | 450.83 | 24.48 | 32.50 | 24.59 |
July | 67.00 | 26.53 | 497.00 | 24.77 | 67.00 | 24.96 |
August | 37.33 | 26.68 | 496.67 | 24.61 | 37.33 | 24.74 |
September | 101.67 | 23.56 | 324.33 | 24.15 | 19.50 | 24.24 |
October | 246.33 | 22.55 | 185.67 | 23.20 | 4.50 | 23.18 |
November | 473.33 | 21.32 | 123.17 | 21.07 | 122.83 | 20.90 |
December | 497.00 | 20.72 | 290.17 | 20.56 | 290.17 | 20.48 |
Annual Sum or Average | 3416.00 | 21.59 | 3381.33 | 22.27 | 1314.67 | 22.05 |
Minimum of Months | 37.33 | 20.35 | 81.33 | 20.16 | 4.50 | 20.07 |
Maximum of Months | 502.00 | 26.68 | 497.00 | 24.77 | 325.67 | 24.96 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.85 | 449.33 | 19.78 | 449.33 | 19.76 |
February | 454.00 | 19.95 | 436.17 | 19.93 | 436.17 | 19.92 |
March | 514.00 | 20.62 | 304.50 | 20.42 | 304.50 | 20.33 |
April | 428.00 | 21.38 | 138.33 | 21.15 | 125.00 | 20.96 |
May | 292.33 | 22.69 | 104.00 | 23.09 | 1.83 | 23.08 |
June | 59.17 | 24.49 | 406.33 | 24.28 | 31.17 | 24.36 |
July | 74.33 | 25.97 | 497.00 | 24.64 | 74.33 | 24.79 |
August | 44.67 | 25.52 | 457.00 | 24.44 | 36.33 | 24.55 |
September | 170.17 | 22.87 | 244.33 | 23.64 | 12.33 | 23.65 |
October | 396.00 | 21.76 | 152.17 | 21.76 | 82.67 | 21.52 |
November | 489.00 | 20.45 | 280.67 | 20.21 | 280.67 | 20.09 |
December | 497.00 | 19.93 | 474.83 | 19.90 | 474.83 | 19.90 |
Annual Sum or Average | 3920.67 | 21.00 | 3944.67 | 21.45 | 2309.17 | 21.18 |
Minimum of Months | 44.67 | 19.85 | 104.00 | 19.78 | 1.83 | 19.76 |
Maximum of Months | 514.00 | 25.97 | 497.00 | 24.64 | 474.83 | 24.79 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.90 | 428.83 | 19.81 | 428.83 | 19.77 |
February | 454.00 | 20.11 | 401.17 | 20.05 | 401.17 | 20.03 |
March | 509.33 | 20.95 | 203.50 | 20.63 | 203.50 | 20.45 |
April | 369.33 | 21.63 | 149.83 | 21.71 | 86.50 | 21.49 |
May | 236.67 | 22.73 | 193.50 | 23.55 | 16.67 | 23.67 |
June | 54.00 | 25.09 | 429.17 | 24.41 | 33.50 | 24.53 |
July | 85.33 | 26.40 | 495.00 | 24.79 | 85.33 | 25.00 |
August | 47.33 | 26.32 | 485.17 | 24.57 | 44.17 | 24.72 |
September | 154.00 | 23.33 | 305.83 | 24.02 | 29.83 | 24.14 |
October | 322.83 | 22.03 | 159.00 | 22.41 | 36.50 | 22.26 |
November | 489.00 | 20.67 | 233.33 | 20.36 | 233.33 | 20.20 |
December | 497.00 | 20.03 | 451.83 | 19.98 | 451.83 | 19.96 |
Annual Sum or Average | 3720.83 | 21.17 | 3936.17 | 21.74 | 2051.17 | 21.48 |
Minimum of Months | 47.33 | 19.90 | 149.83 | 19.81 | 16.67 | 19.77 |
Maximum of Months | 509.33 | 26.40 | 495.00 | 24.79 | 451.83 | 25.00 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 490.67 | 20.38 | 320.83 | 20.04 | 320.83 | 19.89 |
February | 436.00 | 20.78 | 283.00 | 20.44 | 283.00 | 20.29 |
March | 437.00 | 21.15 | 195.67 | 20.89 | 177.00 | 20.67 |
April | 357.00 | 21.62 | 159.17 | 21.72 | 92.67 | 21.49 |
May | 251.67 | 22.67 | 156.00 | 23.33 | 9.50 | 23.38 |
June | 64.00 | 24.46 | 416.83 | 24.32 | 30.33 | 24.41 |
July | 81.17 | 26.17 | 495.50 | 24.72 | 81.17 | 24.89 |
August | 50.17 | 26.18 | 485.33 | 24.58 | 44.33 | 24.74 |
September | 114.67 | 23.70 | 343.67 | 24.22 | 32.33 | 24.35 |
October | 211.17 | 22.50 | 258.00 | 23.34 | 31.83 | 23.27 |
November | 425.83 | 21.10 | 188.17 | 20.81 | 169.33 | 20.57 |
December | 472.50 | 20.64 | 305.50 | 20.33 | 303.50 | 20.18 |
Annual Sum or Average | 3391.83 | 21.50 | 3607.67 | 22.09 | 1575.83 | 21.83 |
Minimum of Months | 50.17 | 20.38 | 156.00 | 20.04 | 9.50 | 19.89 |
Maximum of Months | 490.67 | 26.18 | 495.50 | 24.72 | 320.83 | 24.89 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.05 | 390.50 | 19.90 | 390.50 | 19.84 |
February | 454.00 | 20.32 | 357.83 | 20.17 | 357.83 | 20.12 |
March | 475.17 | 21.03 | 198.50 | 20.80 | 191.50 | 20.65 |
April | 374.50 | 21.61 | 131.33 | 21.75 | 71.83 | 21.56 |
May | 248.67 | 22.77 | 182.50 | 23.48 | 13.00 | 23.58 |
June | 61.67 | 25.00 | 434.33 | 24.44 | 38.00 | 24.57 |
July | 76.33 | 26.47 | 495.33 | 24.78 | 76.33 | 24.98 |
August | 45.00 | 26.38 | 493.83 | 24.60 | 41.33 | 24.75 |
September | 142.00 | 23.12 | 290.67 | 23.92 | 21.83 | 24.02 |
October | 303.50 | 21.96 | 180.00 | 22.42 | 40.83 | 22.25 |
November | 481.83 | 20.72 | 221.00 | 20.44 | 221.00 | 20.29 |
December | 497.00 | 20.24 | 404.17 | 20.13 | 404.17 | 20.09 |
Annual Sum or Average | 3661.67 | 21.24 | 3780.00 | 21.84 | 1868.17 | 21.59 |
Minimum of Months | 45.00 | 20.05 | 131.33 | 19.90 | 13.00 | 19.84 |
Maximum of Months | 502.00 | 26.47 | 495.33 | 24.78 | 404.17 | 24.98 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 469.83 | 27.00 | 0.00 | 27.00 |
February | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
March | 5.67 | 27.00 | 514.00 | 27.00 | 5.67 | 27.00 |
April | 73.17 | 27.00 | 485.00 | 27.00 | 73.17 | 27.00 |
May | 3.67 | 27.00 | 508.00 | 27.00 | 3.67 | 27.00 |
June | 80.33 | 27.00 | 496.00 | 27.00 | 80.33 | 27.00 |
July | 261.17 | 27.00 | 497.00 | 27.00 | 261.17 | 27.00 |
August | 440.33 | 27.05 | 514.00 | 27.05 | 440.33 | 27.05 |
September | 24.17 | 27.00 | 485.00 | 27.00 | 24.17 | 27.00 |
October | 34.50 | 27.00 | 502.00 | 27.00 | 34.50 | 27.00 |
November | 5.83 | 27.00 | 489.00 | 27.00 | 5.83 | 27.00 |
December | 0.00 | 0.00 | 497.00 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 928.83 | 27.02 | 5910.83 | 27.01 | 928.83 | 27.01 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 440.33 | 27.05 | 514.00 | 27.05 | 440.33 | 27.05 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 86.17 | 25.05 | 295.00 | 26.41 | 12.17 | 26.29 |
February | 0.00 | 0.00 | 269.00 | 27.00 | 0.00 | 27.00 |
March | 0.00 | 0.00 | 495.67 | 27.00 | 0.00 | 27.00 |
April | 2.17 | 27.00 | 485.00 | 27.00 | 2.17 | 27.00 |
May | 0.00 | 0.00 | 508.00 | 27.00 | 0.00 | 27.00 |
June | 2.17 | 27.00 | 496.00 | 27.00 | 2.17 | 27.00 |
July | 33.83 | 27.00 | 497.00 | 27.00 | 33.83 | 27.00 |
August | 110.33 | 27.17 | 514.00 | 27.06 | 110.33 | 27.08 |
September | 6.50 | 27.00 | 485.00 | 27.00 | 6.50 | 27.00 |
October | 4.00 | 27.00 | 502.00 | 27.00 | 4.00 | 27.00 |
November | 0.00 | 0.00 | 447.33 | 27.00 | 0.00 | 27.00 |
December | 0.00 | 0.00 | 444.17 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 245.17 | 26.39 | 5438.17 | 26.97 | 171.17 | 26.96 |
Minimum of Months | 0.00 | 0.00 | 269.00 | 26.41 | 0.00 | 26.29 |
Maximum of Months | 110.33 | 27.17 | 514.00 | 27.06 | 110.33 | 27.08 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 191.00 | 24.64 | 210.67 | 25.40 | 41.17 | 25.12 |
February | 55.00 | 27.00 | 156.00 | 27.00 | 0.00 | 27.00 |
March | 0.67 | 27.00 | 431.33 | 27.00 | 0.00 | 27.00 |
April | 6.33 | 27.00 | 469.83 | 27.00 | 6.33 | 27.00 |
May | 3.67 | 27.00 | 508.00 | 27.00 | 3.67 | 27.00 |
June | 33.50 | 27.00 | 496.00 | 27.00 | 33.50 | 27.00 |
July | 100.17 | 27.00 | 497.00 | 27.00 | 100.17 | 27.00 |
August | 169.00 | 27.07 | 514.00 | 27.03 | 169.00 | 27.04 |
September | 14.33 | 27.00 | 485.00 | 27.00 | 14.33 | 27.00 |
October | 6.83 | 27.00 | 474.33 | 27.00 | 6.83 | 27.00 |
November | 10.17 | 27.00 | 395.83 | 27.00 | 0.00 | 27.00 |
December | 28.33 | 27.00 | 274.33 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 619.00 | 26.29 | 4912.33 | 26.89 | 375.00 | 26.87 |
Minimum of Months | 0.67 | 24.64 | 156.00 | 25.40 | 0.00 | 25.12 |
Maximum of Months | 191.00 | 27.07 | 514.00 | 27.03 | 169.00 | 27.04 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 168.67 | 27.00 | 502.00 | 27.00 | 168.67 | 27.00 |
February | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
March | 514.00 | 27.00 | 514.00 | 27.00 | 514.00 | 27.00 |
April | 485.00 | 27.01 | 485.00 | 27.01 | 485.00 | 27.01 |
May | 508.00 | 27.00 | 508.00 | 27.00 | 508.00 | 27.00 |
June | 496.00 | 27.00 | 496.00 | 27.00 | 496.00 | 27.00 |
July | 497.00 | 27.00 | 497.00 | 27.00 | 497.00 | 27.00 |
August | 514.00 | 28.02 | 514.00 | 28.02 | 514.00 | 28.02 |
September | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
October | 502.00 | 27.00 | 502.00 | 27.00 | 502.00 | 27.00 |
November | 489.00 | 27.00 | 489.00 | 27.00 | 489.00 | 27.00 |
December | 497.00 | 27.01 | 497.00 | 27.01 | 497.00 | 27.01 |
Annual Sum or Average | 5609.67 | 27.10 | 5943.00 | 27.09 | 5609.67 | 27.10 |
Minimum of Months | 168.67 | 27.00 | 454.00 | 27.00 | 168.67 | 27.00 |
Maximum of Months | 514.00 | 28.02 | 514.00 | 28.02 | 514.00 | 28.02 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.99970 | 20.72905 | 0.69140 | 15.24593 |
February | 454.00000 | 27.00000 | 17.41129 | 0.72365 | 16.13479 |
March | 514.00000 | 27.00004 | 24.54627 | 0.86951 | 21.07395 |
April | 485.00000 | 27.00003 | 29.77106 | 0.96624 | 24.81504 |
May | 508.00000 | 27.00045 | 34.25256 | 0.25376 | 6.42203 |
June | 496.00000 | 27.00144 | 38.07483 | 0.36121 | 7.77419 |
July | 497.00000 | 27.00110 | 39.19636 | 0.42296 | 8.77965 |
August | 514.00000 | 27.04241 | 38.46187 | 0.48461 | 10.01698 |
September | 485.00000 | 27.00060 | 37.70496 | 0.29925 | 6.97149 |
October | 502.00000 | 27.00069 | 31.71066 | 0.93786 | 23.72332 |
November | 489.00000 | 27.00007 | 27.01815 | 0.88656 | 21.73647 |
December | 497.00000 | 26.99999 | 20.17986 | 0.83938 | 19.93474 |
Annual Sum or Average | 5943.00000 | 27.00401 | 30.00989 | 0.64365 | 15.19494 |
Minimum of Months | 454.00000 | 26.99970 | 17.41129 | 0.25376 | 6.42203 |
Maximum of Months | 514.00000 | 27.04241 | 39.19636 | 0.96624 | 24.81504 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.62558 | 20.84880 | 0.48204 | 11.30248 |
February | 454.00000 | 27.00000 | 17.40914 | 0.56692 | 11.90078 |
March | 514.00000 | 27.00003 | 24.53094 | 0.71754 | 16.02677 |
April | 485.00000 | 27.00003 | 29.73603 | 0.82321 | 19.48423 |
May | 508.00000 | 27.00025 | 34.32985 | 0.17634 | 5.79068 |
June | 496.00000 | 27.00138 | 38.11991 | 0.28392 | 6.75348 |
July | 497.00000 | 27.00114 | 39.22083 | 0.33083 | 7.33562 |
August | 514.00000 | 27.03713 | 38.45932 | 0.36756 | 7.93357 |
September | 485.00000 | 27.00042 | 37.83195 | 0.22974 | 6.25930 |
October | 502.00000 | 27.00066 | 31.71887 | 0.84860 | 20.42897 |
November | 489.00000 | 27.00006 | 26.99860 | 0.72191 | 16.22368 |
December | 497.00000 | 26.99999 | 20.16658 | 0.63180 | 13.49202 |
Annual Sum or Average | 5943.00000 | 26.97192 | 30.03619 | 0.51416 | 11.89794 |
Minimum of Months | 454.00000 | 26.62558 | 17.40914 | 0.17634 | 5.79068 |
Maximum of Months | 514.00000 | 27.03713 | 39.22083 | 0.84860 | 20.42897 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.01956 | 21.27676 | 0.31632 | 10.04319 |
February | 454.00000 | 27.00005 | 17.40702 | 0.50103 | 10.49260 |
March | 514.00000 | 27.00004 | 24.54509 | 0.65505 | 14.32366 |
April | 485.00000 | 27.00004 | 29.75293 | 0.77730 | 18.09355 |
May | 508.00000 | 27.00031 | 34.41500 | 0.15534 | 5.79623 |
June | 496.00000 | 27.00142 | 38.12581 | 0.29293 | 6.92907 |
July | 497.00000 | 27.00117 | 39.22828 | 0.35141 | 7.67842 |
August | 514.00000 | 27.02219 | 38.48396 | 0.37853 | 8.14695 |
September | 485.00000 | 27.00043 | 37.86720 | 0.21641 | 6.25702 |
October | 502.00000 | 27.00066 | 31.76558 | 0.80742 | 19.16506 |
November | 489.00000 | 27.00006 | 27.02031 | 0.64783 | 14.16472 |
December | 497.00000 | 27.00000 | 20.17199 | 0.55098 | 11.55704 |
Annual Sum or Average | 5943.00000 | 26.91945 | 30.09437 | 0.47018 | 11.04728 |
Minimum of Months | 454.00000 | 26.01956 | 17.40702 | 0.15534 | 5.79623 |
Maximum of Months | 514.00000 | 27.02219 | 39.22828 | 0.80742 | 19.16506 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00071 | 30.96693 | 1.01472 | 26.76942 |
February | 454.00000 | 27.00458 | 30.19475 | 1.18156 | 34.35935 |
March | 514.00000 | 27.00454 | 30.86757 | 1.35648 | 43.21357 |
April | 485.00000 | 27.00886 | 32.72327 | 1.51487 | 51.71122 |
May | 508.00000 | 27.00115 | 34.76151 | 0.50927 | 10.46890 |
June | 496.00000 | 27.00177 | 37.70167 | 0.77461 | 17.66597 |
July | 497.00000 | 27.00113 | 38.88508 | 0.99566 | 25.95307 |
August | 514.00000 | 28.02354 | 37.74792 | 1.48183 | 49.99003 |
September | 485.00000 | 27.00189 | 37.23299 | 0.59229 | 12.42102 |
October | 502.00000 | 27.00182 | 34.54840 | 1.29274 | 39.91231 |
November | 489.00000 | 27.00335 | 31.62904 | 1.39096 | 45.03753 |
December | 497.00000 | 27.00781 | 30.27393 | 1.49697 | 50.73674 |
Annual Sum or Average | 5943.00000 | 27.09163 | 33.98818 | 1.13370 | 34.04053 |
Minimum of Months | 454.00000 | 27.00071 | 30.19475 | 0.50927 | 10.46890 |
Maximum of Months | 514.00000 | 28.02354 | 38.88508 | 1.51487 | 51.71122 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.15434 | 22.09410 | 0.25150 | 6.78144 |
February | 454.00000 | 24.26260 | 17.78349 | 0.25371 | 6.81823 |
March | 514.00000 | 24.34119 | 25.17798 | 0.33937 | 7.76848 |
April | 485.00000 | 24.44549 | 31.32855 | 0.41069 | 9.05072 |
May | 508.00000 | 24.45293 | 40.66802 | -0.3821 | 8.87597 |
June | 496.00000 | 24.43611 | 55.99032 | -0.2620 | 7.40624 |
July | 497.00000 | 24.58780 | 61.55023 | -0.1693 | 7.01400 |
August | 514.00000 | 24.47468 | 55.81498 | -0.2321 | 7.35000 |
September | 485.00000 | 24.53789 | 49.72913 | -0.2652 | 7.80546 |
October | 502.00000 | 24.58367 | 40.83262 | 0.52710 | 11.67501 |
November | 489.00000 | 24.54212 | 27.34979 | 0.41277 | 9.20391 |
December | 497.00000 | 24.49257 | 19.82143 | 0.33804 | 7.85534 |
Annual Sum or Average | 5943.00000 | 24.44329 | 37.49833 | 0.09984 | 8.14067 |
Minimum of Months | 454.00000 | 24.15434 | 17.78349 | -0.3821 | 6.78144 |
Maximum of Months | 514.00000 | 24.58780 | 61.55023 | 0.52710 | 11.67501 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.75537 | 26.98230 | 0.17753 | 6.07305 |
February | 454.00000 | 24.02860 | 21.01433 | 0.21317 | 6.22474 |
March | 514.00000 | 24.23885 | 26.96551 | 0.33321 | 7.60530 |
April | 485.00000 | 24.29181 | 32.67376 | 0.40399 | 8.76051 |
May | 508.00000 | 24.24752 | 41.61149 | -0.4150 | 9.08152 |
June | 496.00000 | 24.23814 | 51.82908 | -0.3208 | 7.50043 |
July | 497.00000 | 24.20976 | 55.47642 | -0.2911 | 6.93776 |
August | 514.00000 | 24.17198 | 51.70184 | -0.3145 | 7.23556 |
September | 485.00000 | 24.31800 | 48.06509 | -0.3343 | 7.91188 |
October | 502.00000 | 24.36178 | 40.29542 | 0.47822 | 10.30224 |
November | 489.00000 | 24.40849 | 29.69087 | 0.39194 | 8.79298 |
December | 497.00000 | 24.28707 | 22.24576 | 0.30481 | 7.18143 |
Annual Sum or Average | 5943.00000 | 24.21357 | 37.50629 | 0.05012 | 7.80942 |
Minimum of Months | 454.00000 | 23.75537 | 21.01433 | -0.4150 | 6.07305 |
Maximum of Months | 514.00000 | 24.40849 | 55.47642 | 0.47822 | 10.30224 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.90912 | 28.27207 | -0.2965 | 9.25482 |
February | 454.00000 | 22.41110 | 23.46341 | -0.1967 | 6.90251 |
March | 514.00000 | 23.37603 | 30.18395 | 0.09763 | 5.78645 |
April | 485.00000 | 23.75909 | 35.07565 | 0.24322 | 6.75659 |
May | 508.00000 | 24.04938 | 42.47038 | -0.5094 | 10.86887 |
June | 496.00000 | 24.18483 | 52.50778 | -0.3686 | 8.20651 |
July | 497.00000 | 24.21573 | 56.27238 | -0.3264 | 7.52926 |
August | 514.00000 | 24.22620 | 52.49264 | -0.3440 | 7.87784 |
September | 485.00000 | 24.17511 | 48.67846 | -0.4088 | 8.97085 |
October | 502.00000 | 24.03774 | 41.67668 | 0.37525 | 8.48383 |
November | 489.00000 | 23.40990 | 33.27548 | 0.12617 | 6.47819 |
December | 497.00000 | 22.79314 | 26.49974 | -0.0805 | 5.82702 |
Annual Sum or Average | 5943.00000 | 23.55363 | 39.35915 | -0.1411 | 7.75492 |
Minimum of Months | 454.00000 | 21.90912 | 23.46341 | -0.5094 | 5.78645 |
Maximum of Months | 514.00000 | 24.22620 | 56.27238 | 0.37525 | 10.86887 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.87706 | 29.96459 | -0.5633 | 14.84307 |
February | 454.00000 | 21.12079 | 24.76126 | -0.5305 | 12.98252 |
March | 514.00000 | 22.18254 | 32.47707 | -0.1989 | 7.43599 |
April | 485.00000 | 22.98216 | 37.08097 | 0.05161 | 6.97747 |
May | 508.00000 | 23.84519 | 43.30954 | -0.5802 | 12.97129 |
June | 496.00000 | 24.19296 | 52.40553 | -0.3540 | 8.04143 |
July | 497.00000 | 24.29052 | 55.77075 | -0.2836 | 7.08177 |
August | 514.00000 | 24.24806 | 52.20435 | -0.3211 | 7.61377 |
September | 485.00000 | 24.04301 | 49.30115 | -0.4531 | 10.03051 |
October | 502.00000 | 23.43749 | 43.60441 | 0.22426 | 7.76991 |
November | 489.00000 | 22.03950 | 36.04160 | -0.2185 | 8.45435 |
December | 497.00000 | 21.17759 | 28.99790 | -0.4871 | 11.91556 |
Annual Sum or Average | 5943.00000 | 22.88328 | 40.60972 | -0.3085 | 9.65574 |
Minimum of Months | 454.00000 | 20.87706 | 24.76126 | -0.5802 | 6.97747 |
Maximum of Months | 514.00000 | 24.29052 | 55.77075 | 0.22426 | 14.84307 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.33805 | 26.77439 | -0.4250 | 10.28420 |
February | 454.00000 | 21.58013 | 21.41213 | -0.3939 | 9.38964 |
March | 514.00000 | 22.85439 | 28.29039 | -0.0271 | 6.07320 |
April | 485.00000 | 23.60130 | 33.25466 | 0.20735 | 6.74254 |
May | 508.00000 | 24.07145 | 41.26217 | -0.4913 | 10.72687 |
June | 496.00000 | 24.27798 | 51.33333 | -0.2845 | 7.19086 |
July | 497.00000 | 24.39083 | 54.84450 | -0.1910 | 6.50149 |
August | 514.00000 | 24.26021 | 50.95397 | -0.2596 | 6.92516 |
September | 485.00000 | 24.18650 | 48.06415 | -0.3917 | 8.93200 |
October | 502.00000 | 23.81077 | 40.52551 | 0.31562 | 8.04834 |
November | 489.00000 | 23.00819 | 30.81996 | 0.02435 | 6.38313 |
December | 497.00000 | 22.24150 | 23.78261 | -0.2099 | 6.68643 |
Annual Sum or Average | 5943.00000 | 23.31373 | 37.73314 | -0.1764 | 7.81437 |
Minimum of Months | 454.00000 | 21.33805 | 21.41213 | -0.4913 | 6.07320 |
Maximum of Months | 514.00000 | 24.39083 | 54.84450 | 0.31562 | 10.72687 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.34423 | 26.42230 | -0.4149 | 10.08026 |
February | 454.00000 | 21.74486 | 20.86629 | -0.3435 | 8.80684 |
March | 514.00000 | 22.73482 | 27.96661 | -0.0298 | 6.41630 |
April | 485.00000 | 23.41709 | 33.20701 | 0.19867 | 7.55574 |
May | 508.00000 | 24.09182 | 40.98981 | -0.4228 | 10.64735 |
June | 496.00000 | 24.25936 | 51.22290 | -0.2501 | 7.18024 |
July | 497.00000 | 24.37070 | 54.67307 | -0.1579 | 6.75089 |
August | 514.00000 | 24.21891 | 50.81430 | -0.2149 | 6.80207 |
September | 485.00000 | 24.23079 | 47.65369 | -0.3234 | 8.89971 |
October | 502.00000 | 23.80303 | 40.21541 | 0.34898 | 8.80348 |
November | 489.00000 | 22.80136 | 30.74085 | -0.0070 | 6.60103 |
December | 497.00000 | 21.94765 | 23.68073 | -0.2679 | 7.47885 |
Annual Sum or Average | 5943.00000 | 23.25777 | 37.49617 | -0.1564 | 7.99654 |
Minimum of Months | 454.00000 | 21.34423 | 20.86629 | -0.4228 | 6.41630 |
Maximum of Months | 514.00000 | 24.37070 | 54.67307 | 0.34898 | 10.64735 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.75449 | 26.10812 | -0.3159 | 10.19595 |
February | 454.00000 | 22.36630 | 20.32285 | -0.1919 | 8.58435 |
March | 514.00000 | 23.02630 | 27.44105 | 0.04807 | 6.79782 |
April | 485.00000 | 23.54706 | 33.00319 | 0.22265 | 7.77031 |
May | 508.00000 | 24.05643 | 41.22641 | -0.4717 | 11.06801 |
June | 496.00000 | 24.30252 | 51.16818 | -0.2580 | 7.18114 |
July | 497.00000 | 24.43290 | 54.52523 | -0.1484 | 6.62299 |
August | 514.00000 | 24.33289 | 50.43818 | -0.1629 | 6.50037 |
September | 485.00000 | 24.35038 | 47.26257 | -0.2518 | 8.02608 |
October | 502.00000 | 24.19433 | 39.12641 | 0.48330 | 11.34283 |
November | 489.00000 | 23.19551 | 30.03541 | 0.09913 | 7.23809 |
December | 497.00000 | 22.57485 | 23.03522 | -0.1136 | 7.63921 |
Annual Sum or Average | 5943.00000 | 23.51904 | 37.10086 | -0.0884 | 8.24809 |
Minimum of Months | 454.00000 | 21.75449 | 20.32285 | -0.4717 | 6.50037 |
Maximum of Months | 514.00000 | 24.43290 | 54.52523 | 0.48330 | 11.34283 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.92662 | 25.20861 | -0.2546 | 7.95594 |
February | 454.00000 | 22.64582 | 19.44996 | -0.1039 | 6.83633 |
March | 514.00000 | 23.94962 | 25.52709 | 0.29945 | 7.68291 |
April | 485.00000 | 24.40193 | 30.89617 | 0.49690 | 11.21192 |
May | 508.00000 | 24.32573 | 40.20595 | -0.2994 | 8.19663 |
June | 496.00000 | 24.49255 | 50.16542 | -0.0707 | 6.57757 |
July | 497.00000 | 24.61589 | 53.48573 | 0.04266 | 6.88803 |
August | 514.00000 | 24.51140 | 49.65831 | 0.03892 | 6.52107 |
September | 485.00000 | 24.41465 | 46.91856 | -0.2055 | 7.38215 |
October | 502.00000 | 24.34679 | 38.75215 | 0.52665 | 11.81982 |
November | 489.00000 | 23.94243 | 28.28490 | 0.29163 | 7.83605 |
December | 497.00000 | 23.76821 | 20.91079 | 0.18778 | 6.37501 |
Annual Sum or Average | 5943.00000 | 23.95356 | 35.91403 | 0.07986 | 7.94212 |
Minimum of Months | 454.00000 | 21.92662 | 19.44996 | -0.2994 | 6.37501 |
Maximum of Months | 514.00000 | 24.61589 | 53.48573 | 0.52665 | 11.81982 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.08812 | 28.33172 | -0.8033 | 21.22662 |
February | 454.00000 | 20.27437 | 22.85651 | -0.7787 | 19.73761 |
March | 514.00000 | 21.11824 | 31.46645 | -0.4603 | 10.87375 |
April | 485.00000 | 22.28480 | 36.30857 | -0.1205 | 7.52409 |
May | 508.00000 | 23.64544 | 42.71134 | -0.6534 | 15.34127 |
June | 496.00000 | 24.19888 | 52.83049 | -0.3306 | 7.85843 |
July | 497.00000 | 24.42006 | 57.18987 | -0.1997 | 6.79309 |
August | 514.00000 | 24.29475 | 52.66338 | -0.2822 | 7.41658 |
September | 485.00000 | 23.88803 | 49.40014 | -0.5097 | 11.62224 |
October | 502.00000 | 22.87715 | 42.95286 | 0.08436 | 7.44981 |
November | 489.00000 | 21.14930 | 34.70208 | -0.4364 | 11.32391 |
December | 497.00000 | 20.36884 | 27.23735 | -0.7069 | 16.90967 |
Annual Sum or Average | 5943.00000 | 22.40045 | 40.01415 | -0.4310 | 11.95565 |
Minimum of Months | 454.00000 | 20.08812 | 22.85651 | -0.8033 | 6.79309 |
Maximum of Months | 514.00000 | 24.42006 | 57.18987 | 0.08436 | 21.22662 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 20.00487 | 27.30061 | -0.8066 | 21.60935 |
February | 385.00000 | 20.38942 | 21.64626 | -0.7238 | 18.15943 |
March | 433.00000 | 21.38817 | 30.09018 | -0.3735 | 9.97369 |
April | 410.00000 | 22.64444 | 34.71043 | -0.0070 | 8.08845 |
May | 430.00000 | 23.76265 | 41.80065 | -0.5494 | 14.76326 |
June | 418.00000 | 24.29239 | 52.20793 | -0.2546 | 7.79066 |
July | 422.00000 | 24.58473 | 56.34461 | -0.0979 | 7.25220 |
August | 433.00000 | 24.44164 | 51.93182 | -0.1624 | 7.01490 |
September | 410.00000 | 24.05504 | 48.53384 | -0.4000 | 11.02052 |
October | 427.00000 | 23.13451 | 41.30781 | 0.17410 | 7.85014 |
November | 417.00000 | 21.24991 | 33.55884 | -0.3955 | 10.79944 |
December | 422.00000 | 20.41888 | 26.18407 | -0.6793 | 16.18546 |
Annual Sum or Average | 5034.00000 | 22.54399 | 38.91411 | -0.3542 | 11.67264 |
Minimum of Months | 385.00000 | 20.00487 | 21.64626 | -0.8066 | 7.01490 |
Maximum of Months | 433.00000 | 24.58473 | 56.34461 | 0.17410 | 21.60935 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.89634 | 27.18009 | -0.5540 | 16.30932 |
February | 454.00000 | 21.55212 | 21.31054 | -0.4072 | 12.74398 |
March | 514.00000 | 22.20625 | 29.32219 | -0.1536 | 8.52945 |
April | 485.00000 | 22.87878 | 34.66464 | 0.05255 | 8.04455 |
May | 508.00000 | 23.78597 | 42.13418 | -0.5726 | 13.96789 |
June | 496.00000 | 24.24047 | 52.55255 | -0.2934 | 7.74997 |
July | 497.00000 | 24.47610 | 56.67223 | -0.1497 | 6.89371 |
August | 514.00000 | 24.40313 | 51.85412 | -0.1638 | 6.80498 |
September | 485.00000 | 24.23197 | 47.90305 | -0.2964 | 8.98841 |
October | 502.00000 | 23.94047 | 39.80592 | 0.41965 | 10.83509 |
November | 489.00000 | 22.31111 | 32.29554 | -0.1145 | 8.80001 |
December | 497.00000 | 21.59812 | 25.50888 | -0.3666 | 11.68130 |
Annual Sum or Average | 5943.00000 | 23.05473 | 38.56279 | -0.2158 | 10.10092 |
Minimum of Months | 454.00000 | 20.89634 | 21.31054 | -0.5726 | 6.80498 |
Maximum of Months | 514.00000 | 24.47610 | 56.67223 | 0.41965 | 16.30932 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.35456 | 27.46118 | -0.7067 | 18.22263 |
February | 454.00000 | 20.69439 | 21.93095 | -0.6382 | 15.98798 |
March | 514.00000 | 21.76519 | 29.76391 | -0.2664 | 8.74652 |
April | 485.00000 | 22.72593 | 34.76148 | 0.02971 | 7.91131 |
May | 508.00000 | 23.79930 | 41.93165 | -0.5255 | 13.23366 |
June | 496.00000 | 24.32084 | 51.94771 | -0.2043 | 7.28079 |
July | 497.00000 | 24.53250 | 56.08122 | -0.0814 | 6.94622 |
August | 514.00000 | 24.43432 | 51.69111 | -0.1212 | 6.67695 |
September | 485.00000 | 24.02617 | 48.47920 | -0.3872 | 10.22120 |
October | 502.00000 | 23.30787 | 41.30438 | 0.23472 | 8.45873 |
November | 489.00000 | 21.40625 | 33.61361 | -0.3501 | 9.88193 |
December | 497.00000 | 20.71938 | 26.21848 | -0.5929 | 13.71313 |
Annual Sum or Average | 5943.00000 | 22.68991 | 38.89011 | -0.2985 | 10.56847 |
Minimum of Months | 454.00000 | 20.35456 | 21.93095 | -0.7067 | 6.67695 |
Maximum of Months | 514.00000 | 24.53250 | 56.08122 | 0.23472 | 18.22263 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.84562 | 28.93174 | -0.9097 | 25.53843 |
February | 454.00000 | 19.94813 | 23.59798 | -0.9133 | 25.15149 |
March | 514.00000 | 20.62204 | 32.55118 | -0.6196 | 15.30908 |
April | 485.00000 | 21.68990 | 37.63319 | -0.2794 | 10.16300 |
May | 508.00000 | 23.29678 | 43.70464 | -0.7693 | 20.26838 |
June | 496.00000 | 24.15727 | 53.06966 | -0.3331 | 8.25592 |
July | 497.00000 | 24.44391 | 57.15662 | -0.1724 | 6.86539 |
August | 514.00000 | 24.28096 | 52.66718 | -0.2717 | 7.52623 |
September | 485.00000 | 23.66781 | 50.25862 | -0.5813 | 14.27998 |
October | 502.00000 | 22.20633 | 44.59808 | -0.0830 | 9.28416 |
November | 489.00000 | 20.45498 | 36.38701 | -0.6427 | 16.64087 |
December | 497.00000 | 19.92889 | 28.44604 | -0.8729 | 23.67387 |
Annual Sum or Average | 5943.00000 | 22.06254 | 40.87456 | -0.5348 | 15.17728 |
Minimum of Months | 454.00000 | 19.84562 | 23.59798 | -0.9133 | 6.86539 |
Maximum of Months | 514.00000 | 24.44391 | 57.15662 | -0.0830 | 25.53843 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.89939 | 28.50018 | -0.8735 | 24.31135 |
February | 454.00000 | 20.11488 | 23.05743 | -0.8349 | 22.15138 |
March | 514.00000 | 20.98027 | 31.60446 | -0.4989 | 13.26249 |
April | 485.00000 | 22.24142 | 35.95377 | -0.1150 | 9.39225 |
May | 508.00000 | 23.52073 | 42.73735 | -0.6190 | 17.65968 |
June | 496.00000 | 24.22072 | 52.45766 | -0.2478 | 7.81682 |
July | 497.00000 | 24.50783 | 56.20650 | -0.0827 | 7.15422 |
August | 514.00000 | 24.36662 | 51.79468 | -0.1463 | 6.85948 |
September | 485.00000 | 23.88218 | 49.14728 | -0.4416 | 12.34222 |
October | 502.00000 | 22.72896 | 42.85848 | 0.07669 | 8.76333 |
November | 489.00000 | 20.67145 | 35.53216 | -0.5659 | 15.04880 |
December | 497.00000 | 20.03130 | 27.90362 | -0.8246 | 21.84657 |
Annual Sum or Average | 5943.00000 | 22.28103 | 39.93586 | -0.4283 | 13.82545 |
Minimum of Months | 454.00000 | 19.89939 | 23.05743 | -0.8735 | 6.85948 |
Maximum of Months | 514.00000 | 24.50783 | 56.20650 | 0.07669 | 24.31135 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.45944 | 28.00972 | -0.6973 | 20.54122 |
February | 454.00000 | 20.90710 | 22.33026 | -0.6007 | 17.49281 |
March | 514.00000 | 21.57578 | 30.65385 | -0.3352 | 11.92976 |
April | 485.00000 | 22.29557 | 36.02292 | -0.1021 | 9.74300 |
May | 508.00000 | 23.43327 | 43.15087 | -0.6881 | 18.74265 |
June | 496.00000 | 24.17692 | 52.83667 | -0.3017 | 8.28114 |
July | 497.00000 | 24.47338 | 56.70721 | -0.1298 | 7.01129 |
August | 514.00000 | 24.38411 | 51.88193 | -0.1529 | 6.94081 |
September | 485.00000 | 24.05304 | 48.64230 | -0.3534 | 10.83102 |
October | 502.00000 | 23.48715 | 40.98864 | 0.29861 | 10.57238 |
November | 489.00000 | 21.47675 | 34.17662 | -0.3437 | 12.41425 |
December | 497.00000 | 20.82240 | 27.07902 | -0.5955 | 17.25942 |
Annual Sum or Average | 5943.00000 | 22.64268 | 39.49906 | -0.3319 | 12.61997 |
Minimum of Months | 454.00000 | 20.45944 | 22.33026 | -0.6973 | 6.94081 |
Maximum of Months | 514.00000 | 24.47338 | 56.70721 | 0.29861 | 20.54122 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.04897 | 28.16270 | -0.8216 | 22.50306 |
February | 454.00000 | 20.31749 | 22.74631 | -0.7714 | 20.47723 |
March | 514.00000 | 21.25321 | 30.86449 | -0.4176 | 11.81905 |
April | 485.00000 | 22.19930 | 35.96542 | -0.1085 | 9.43450 |
May | 508.00000 | 23.46849 | 42.84480 | -0.6319 | 17.48441 |
June | 496.00000 | 24.25973 | 52.22271 | -0.2117 | 7.75518 |
July | 497.00000 | 24.52008 | 56.14021 | -0.0650 | 7.13194 |
August | 514.00000 | 24.41397 | 51.71253 | -0.1117 | 6.80965 |
September | 485.00000 | 23.81603 | 49.27202 | -0.4529 | 12.47494 |
October | 502.00000 | 22.76809 | 42.64456 | 0.09922 | 9.06355 |
November | 489.00000 | 20.76413 | 35.17054 | -0.5343 | 13.99867 |
December | 497.00000 | 20.23541 | 27.43487 | -0.7559 | 19.30424 |
Annual Sum or Average | 5943.00000 | 22.35582 | 39.72062 | -0.3958 | 13.13429 |
Minimum of Months | 454.00000 | 20.04897 | 22.74631 | -0.8216 | 6.80965 |
Maximum of Months | 514.00000 | 24.52008 | 56.14021 | 0.09922 | 22.50306 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.810076E+09 | 4632.17 | 24-JAN-06:03 | 67.03 | 0.368948E+10 | 0.00 | 0.449955E+10 | 0.41 | 4.56 | 06-JAN-06:50 | 0.00 | 0.00 |
February | 0.937033E+09 | 3768.46 | 17-FEB-09:30 | 77.32 | 0.426735E+10 | 0.00 | 0.520438E+10 | 0.52 | 4.56 | 09-FEB-21:20 | 0.00 | 0.00 |
March | 0.241973E+10 | 80051.69 | 27-MAR-16:00 | 68.94 | 0.126289E+11 | 0.00 | 0.150486E+11 | 0.43 | 6.78 | 27-MAR-16:00 | 0.00 | 0.00 |
April | 0.180848E+11 | 110015.78 | 07-APR-14:20 | 135.96 | 0.103834E+12 | 0.00 | 0.121919E+12 | 0.96 | 7.29 | 07-APR-15:30 | 0.00 | 0.00 |
May | 0.596177E+11 | 131958.21 | 30-MAY-13:15 | 330.43 | 0.356517E+12 | 0.00 | 0.416134E+12 | 2.41 | 7.42 | 30-MAY-11:10 | 0.00 | 0.00 |
June | 0.142394E+12 | 179170.27 | 17-JUN-05:04 | 528.25 | 0.944768E+12 | 0.00 | 0.108716E+13 | 4.57 | 7.77 | 13-JUN-05:04 | 0.00 | 0.00 |
July | 0.180463E+12 | 199082.35 | 20-JUL-05:02 | 647.04 | 0.117370E+13 | 0.00 | 0.135416E+13 | 5.26 | 7.69 | 05-JUL-05:03 | 0.00 | 0.00 |
August | 0.174883E+12 | 180098.04 | 01-AUG-05:03 | 679.10 | 0.113856E+13 | 0.00 | 0.131344E+13 | 5.43 | 7.73 | 07-AUG-05:04 | 0.00 | 0.00 |
September | 0.108219E+12 | 192398.58 | 07-SEP-05:04 | 443.41 | 0.696628E+12 | 0.00 | 0.804847E+12 | 3.68 | 7.70 | 13-SEP-05:03 | 0.00 | 0.00 |
October | 0.512151E+11 | 116939.11 | 05-OCT-13:10 | 254.47 | 0.318574E+12 | 0.00 | 0.369789E+12 | 1.93 | 7.54 | 06-OCT-05:04 | 0.00 | 0.00 |
November | 0.297206E+10 | 57498.63 | 10-NOV-06:03 | 66.51 | 0.134455E+11 | 0.00 | 0.164175E+11 | 0.42 | 5.90 | 10-NOV-06:03 | 0.00 | 0.00 |
December | 0.690872E+09 | 4167.26 | 15-DEC-11:20 | 56.22 | 0.314682E+10 | 0.00 | 0.383770E+10 | 0.34 | 4.56 | 21-DEC-08:00 | 0.00 | 0.00 |
Annual Sum or Average | 0.742707E+12 | 3354.68 | 0.476975E+13 | 0.00 | 0.551246E+13 | 2.21 | 0.00 | 0.00 | ||||
Minimum of Months | 0.690872E+09 | 3768.46 | 56.22 | 0.314682E+10 | 0.00 | 0.383770E+10 | 0.34 | 4.56 | 0.00 | 0.00 | ||
Maximum of Months | 0.180463E+12 | 199082.35 | 679.10 | 0.117370E+13 | 0.00 | 0.135416E+13 | 5.43 | 7.77 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.365394E+09 | 107313.10 | 07-APR-14:40 | 1.00 | 0.261571E+10 | 0.00 | 0.298110E+10 | 0.01 | 7.28 | 07-APR-14:40 | 0.00 | 0.00 |
May | 0.534167E+10 | 131958.21 | 30-MAY-13:15 | 13.75 | 0.380827E+11 | 0.00 | 0.434243E+11 | 0.13 | 7.42 | 30-MAY-11:10 | 0.00 | 0.00 |
June | 0.390614E+11 | 179170.27 | 17-JUN-05:04 | 100.02 | 0.272999E+12 | 0.00 | 0.312061E+12 | 0.97 | 7.77 | 13-JUN-05:04 | 0.00 | 0.00 |
July | 0.703233E+11 | 199082.35 | 20-JUL-05:02 | 174.07 | 0.478245E+12 | 0.00 | 0.548568E+12 | 1.59 | 7.69 | 05-JUL-05:03 | 0.00 | 0.00 |
August | 0.690577E+11 | 180098.04 | 01-AUG-05:03 | 169.16 | 0.472707E+12 | 0.00 | 0.541764E+12 | 1.56 | 7.73 | 07-AUG-05:04 | 0.00 | 0.00 |
September | 0.232071E+11 | 192398.58 | 07-SEP-05:04 | 59.48 | 0.161886E+12 | 0.00 | 0.185093E+12 | 0.58 | 7.70 | 13-SEP-05:03 | 0.00 | 0.00 |
October | 0.713301E+10 | 116939.11 | 05-OCT-13:10 | 18.57 | 0.517096E+11 | 0.00 | 0.588426E+11 | 0.18 | 7.54 | 06-OCT-05:04 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.214490E+12 | 536.04 | 0.147824E+13 | 0.00 | 0.169273E+13 | 0.42 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.703233E+11 | 199082.35 | 174.07 | 0.478245E+12 | 0.00 | 0.548568E+12 | 1.59 | 7.77 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: CENTRAL TOWER
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.100962E+11 | 744.00 | 8666.24 | 24-JAN-12:00 | 176742.47 | 20-JAN-16:20 | 21.53 | 18.33 | 14.10 |
February | 0.141941E+11 | 672.00 | 16774.46 | 20-FEB-12:00 | 320279.96 | 20-FEB-16:30 | 24.39 | 18.33 | 14.10 |
March | 0.479879E+11 | 744.00 | 49248.27 | 02-MAR-15:40 | 584211.57 | 31-MAR-24:00 | 27.51 | 18.41 | 14.10 |
April | 0.962244E+11 | 720.00 | 49248.27 | 05-APR-10:40 | 664819.87 | 07-APR-17:20 | 31.56 | 19.48 | 14.10 |
May | 0.851541E+11 | 744.00 | 49248.27 | 01-MAY-10:50 | 334515.31 | 31-MAY-23:40 | 23.51 | 19.69 | 14.10 |
June | 0.127032E+12 | 720.00 | 49248.27 | 01-JUN-00:10 | 477885.10 | 30-JUN-24:00 | 31.83 | 24.77 | 14.10 |
July | 0.131907E+12 | 744.00 | 49248.27 | 01-JUL-00:10 | 641338.07 | 31-JUL-24:00 | 39.78 | 29.51 | 14.10 |
August | 0.131907E+12 | 744.00 | 49248.27 | 01-AUG-00:03 | 703039.27 | 04-AUG-21:01 | 43.66 | 30.54 | 14.10 |
September | 0.114586E+12 | 720.00 | 49248.27 | 01-SEP-00:03 | 319238.85 | 30-SEP-24:00 | 26.20 | 22.18 | 14.10 |
October | 0.925861E+11 | 744.00 | 49248.27 | 02-OCT-08:15 | 450597.70 | 31-OCT-24:00 | 26.31 | 19.64 | 14.10 |
November | 0.591886E+11 | 720.00 | 49248.27 | 01-NOV-14:00 | 480280.80 | 03-NOV-15:10 | 27.54 | 18.41 | 14.10 |
December | 0.511062E+11 | 744.00 | 44729.82 | 17-DEC-15:00 | 598082.20 | 17-DEC-16:07 | 30.11 | 18.33 | 14.10 |
Annual Sum or Average | 0.961968E+12 | 8760.00 | 29.54 | 21.50 | 14.10 | ||||
Minimum of Months | 0.100962E+11 | 672.00 | 8666.24 | 176742.47 | 21.53 | 18.33 | 14.10 | ||
Maximum of Months | 0.131907E+12 | 744.00 | 49248.27 | 703039.27 | 43.66 | 30.54 | 14.10 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 271881.48 | 04-JAN-09:00 | 20.94 | 20.93 | 1.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 271919.63 | 14-FEB-21:30 | 20.97 | 20.96 | 1.02 |
March | 34647684.99 | 7.75 | 2268.21 | 27-MAR-16:00 | 634193.55 | 27-MAR-16:00 | 21.05 | 21.03 | 1.58 |
April | 0.319977E+09 | 78.29 | 20605.46 | 07-APR-13:00 | 1233782.64 | 07-APR-14:40 | 21.20 | 21.03 | 10.09 |
May | 0.259728E+10 | 251.13 | 20605.46 | 18-MAY-10:00 | 1259938.94 | 30-MAY-08:00 | 21.74 | 21.17 | 28.45 |
June | 0.241197E+11 | 496.54 | 20605.46 | 01-JUN-09:40 | 1151950.12 | 22-JUN-09:40 | 23.83 | 22.30 | 50.40 |
July | 0.442502E+11 | 644.88 | 20605.46 | 01-JUL-03:02 | 1254591.60 | 24-JUL-05:04 | 25.61 | 23.79 | 59.27 |
August | 0.334766E+11 | 641.27 | 20605.46 | 01-AUG-00:03 | 1522181.08 | 30-AUG-14:20 | 24.76 | 22.94 | 60.96 |
September | 0.128083E+11 | 400.34 | 20605.46 | 01-SEP-03:02 | 1165948.69 | 18-SEP-14:10 | 23.10 | 21.97 | 42.00 |
October | 0.458784E+10 | 213.05 | 20605.46 | 02-OCT-13:00 | 1081645.18 | 05-OCT-11:00 | 21.76 | 21.24 | 22.61 |
November | 10405156.34 | 15.03 | 781.35 | 10-NOV-08:00 | 336963.55 | 03-NOV-14:00 | 21.01 | 20.98 | 2.80 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 271868.23 | 13-DEC-07:50 | 20.94 | 20.93 | 0.79 |
Annual Sum or Average | 0.122205E+12 | 2748.29 | 22.25 | 21.61 | 23.57 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 271868.23 | 20.94 | 20.93 | 0.79 | ||
Maximum of Months | 0.442502E+11 | 644.88 | 20605.46 | 1522181.08 | 25.61 | 23.79 | 60.96 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 20.94 | 20.94 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 20.97 | 20.97 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 21.05 | 21.05 | 0.00 |
April | 74179650.24 | 1.00 | 20605.46 | 07-APR-13:30 | 1233782.64 | 07-APR-14:40 | 21.20 | 21.20 | 0.10 |
May | 0.890156E+09 | 12.00 | 20605.46 | 30-MAY-08:00 | 1259938.94 | 30-MAY-08:00 | 21.74 | 21.69 | 1.13 |
June | 0.780308E+10 | 105.19 | 20605.46 | 01-JUN-10:00 | 1151950.12 | 22-JUN-09:40 | 23.83 | 23.39 | 10.12 |
July | 0.167443E+11 | 225.73 | 20605.46 | 01-JUL-05:04 | 1254591.60 | 24-JUL-05:04 | 25.61 | 24.71 | 19.72 |
August | 0.146002E+11 | 199.79 | 20605.46 | 01-AUG-05:03 | 1440385.34 | 30-AUG-15:50 | 24.76 | 23.93 | 17.17 |
September | 0.482621E+10 | 65.06 | 20605.46 | 01-SEP-05:03 | 1101244.52 | 01-SEP-14:00 | 23.10 | 22.83 | 6.30 |
October | 0.132534E+10 | 17.87 | 20605.46 | 03-OCT-12:10 | 1081645.18 | 05-OCT-11:00 | 21.76 | 21.69 | 1.68 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 21.01 | 21.01 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 20.94 | 20.94 | 0.00 |
Annual Sum or Average | 0.462635E+11 | 626.63 | 22.25 | 22.04 | 4.73 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 20.94 | 20.94 | 0.00 | ||
Maximum of Months | 0.167443E+11 | 225.73 | 20605.46 | 1440385.34 | 25.61 | 24.71 | 19.72 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.284193E+12 | 0.00 | 553.25 | 1833185.28 | 09-JAN-05:01 | 0.00 | 31.62 | 67.75 | 0.60 | 0.00 | 0.04 | 0.65 | 09-JAN-05:01 |
February | 0.202509E+12 | 0.00 | 479.23 | 1699049.81 | 13-FEB-05:11 | 0.00 | 31.92 | 66.37 | 0.47 | 0.00 | 0.03 | 0.60 | 13-FEB-05:11 |
March | 0.664779E+11 | 0.00 | 376.19 | 1253412.36 | 07-MAR-06:02 | 0.00 | 25.52 | 52.18 | 0.13 | 0.00 | 0.01 | 0.45 | 07-MAR-06:02 |
April | 0.185320E+11 | 0.00 | 164.08 | 1181952.09 | 03-APR-05:01 | 0.00 | 24.90 | 37.40 | 0.03 | 0.00 | 0.00 | 0.42 | 03-APR-05:01 |
May | 0.492059E+09 | 0.00 | 19.24 | 115315.28 | 30-MAY-14:10 | 0.00 | 24.20 | 25.63 | 0.00 | 0.00 | 0.00 | 0.04 | 30-MAY-14:10 |
June | 0.132684E+10 | 0.00 | 13.89 | 140880.44 | 01-JUN-14:50 | 0.00 | 50.78 | 51.47 | 0.00 | 0.00 | 0.00 | 0.05 | 01-JUN-14:50 |
July | 0.483977E+09 | 0.00 | 8.44 | 61771.96 | 11-JUL-16:20 | 0.00 | 46.03 | 46.37 | 0.00 | 0.00 | 0.00 | 0.02 | 11-JUL-16:20 |
August | 0.205652E+10 | 0.00 | 23.08 | 104413.73 | 22-AUG-15:50 | 0.00 | 45.45 | 46.35 | 0.01 | 0.00 | 0.00 | 0.04 | 22-AUG-15:50 |
September | 0.118703E+09 | 0.00 | 3.75 | 41833.98 | 01-SEP-17:20 | 0.00 | 43.36 | 43.54 | 0.00 | 0.00 | 0.00 | 0.01 | 01-SEP-17:20 |
October | 0.242339E+10 | 0.00 | 68.34 | 548427.29 | 28-OCT-05:02 | 0.00 | 31.33 | 36.12 | 0.00 | 0.00 | 0.00 | 0.20 | 28-OCT-05:02 |
November | 0.666224E+11 | 0.00 | 335.07 | 1285962.51 | 27-NOV-06:01 | 0.00 | 26.21 | 50.62 | 0.13 | 0.00 | 0.01 | 0.46 | 27-NOV-06:01 |
December | 0.147002E+12 | 0.00 | 482.68 | 1271144.51 | 26-DEC-05:01 | 0.00 | 27.13 | 61.34 | 0.27 | 0.00 | 0.02 | 0.45 | 26-DEC-05:01 |
Annual Sum or Average | 0.792237E+12 | 0.00 | 2527.25 | 0.00 | 34.03 | 48.65 | 0.14 | 0.00 | 0.01 | ||||
Minimum of Months | 0.118703E+09 | 0.00 | 3.75 | 41833.98 | 0.00 | 24.20 | 25.63 | 0.00 | 0.00 | 0.00 | 0.01 | ||
Maximum of Months | 0.284193E+12 | 0.00 | 553.25 | 1833185.28 | 0.00 | 50.78 | 67.75 | 0.60 | 0.00 | 0.04 | 0.65 |
Report: BoilerReportMonthly
For: CENTRAL BOILER
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 21.53 | 21.53 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 24.39 | 24.39 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 27.51 | 27.51 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 31.56 | 31.56 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 23.51 | 23.51 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 31.83 | 31.83 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 39.78 | 39.78 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 43.66 | 43.66 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 26.20 | 26.20 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 26.31 | 26.31 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 27.54 | 27.54 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 30.11 | 30.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 29.54 | 29.54 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.53 | 21.53 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.66 | 43.66 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 18841006.08 | 0.00 | 36.58 | 18841006.08 | 0.00 | 0.00 | 0.00 | 0.00 | 4419.47 | 19-JAN-08:30 | 4419.47 | 19-JAN-08:30 | 0.00 | 0.00 | 0.00 |
February | 16076007.78 | 0.00 | 35.24 | 16076007.78 | 0.00 | 0.00 | 0.00 | 0.00 | 2775.79 | 02-FEB-08:10 | 2775.79 | 02-FEB-08:10 | 0.00 | 0.00 | 0.00 |
March | 0.114333E+10 | 0.00 | 36.31 | 0.110759E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64484.72 | 27-MAR-16:00 | 64484.72 | 27-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.119550E+11 | 0.00 | 114.26 | 0.119493E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 116677.73 | 07-APR-15:00 | 116677.73 | 07-APR-15:00 | 0.00 | 0.00 | 0.00 |
May | 0.354743E+11 | 0.00 | 314.96 | 0.316231E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 173874.24 | 30-MAY-13:30 | 173874.24 | 30-MAY-13:30 | 0.00 | 0.00 | 0.00 |
June | 0.120795E+12 | 0.00 | 515.69 | 0.986641E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 209170.36 | 19-JUN-05:03 | 174706.23 | 22-JUN-15:03 | 0.00 | 0.00 | 0.00 |
July | 0.166254E+12 | 0.00 | 612.75 | 0.138266E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 218371.39 | 10-JUL-05:02 | 162495.21 | 12-JUL-11:00 | 0.00 | 0.00 | 0.00 |
August | 0.170332E+12 | 0.00 | 650.69 | 0.150198E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 217988.29 | 03-AUG-05:03 | 199747.65 | 22-AUG-15:05 | 0.00 | 0.00 | 0.00 |
September | 0.797612E+11 | 0.00 | 425.54 | 0.683656E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 211319.70 | 07-SEP-05:02 | 173281.93 | 01-SEP-13:50 | 0.00 | 0.00 | 0.00 |
October | 0.378106E+11 | 0.00 | 244.80 | 0.284025E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 153356.62 | 06-OCT-05:02 | 97163.23 | 04-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.110735E+10 | 0.00 | 37.64 | 0.101617E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59452.13 | 10-NOV-06:03 | 28266.42 | 03-NOV-14:00 | 0.00 | 0.00 | 0.00 |
December | 11156552.39 | 0.00 | 21.58 | 11156552.39 | 0.00 | 0.00 | 0.00 | 0.00 | 4328.34 | 13-DEC-08:10 | 4328.34 | 13-DEC-08:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.624678E+12 | 0.00 | 3046.05 | 0.529638E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 11156552.39 | 0.00 | 21.58 | 11156552.39 | 0.00 | 0.00 | 0.00 | 0.00 | 2775.79 | 2775.79 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.170332E+12 | 0.00 | 650.69 | 0.150198E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 218371.39 | 199747.65 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 50727843.69 | 0.00 | 35.14 | 50727843.69 | 0.00 | 0.00 | 0.00 | 0.00 | 7138.87 | 17-JAN-12:40 | 7138.87 | 17-JAN-12:40 | 0.00 | 0.00 | 0.00 |
February | 4552358.87 | 0.00 | 49.64 | 4552358.87 | 0.00 | 0.00 | 0.00 | 0.00 | 243.98 | 28-FEB-14:20 | 243.98 | 28-FEB-14:20 | 0.00 | 0.00 | 0.00 |
March | 0.652141E+10 | 0.00 | 35.25 | 0.649186E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 393420.99 | 27-MAR-16:00 | 393420.99 | 27-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.786206E+11 | 0.00 | 98.85 | 0.786083E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 974438.23 | 07-APR-14:20 | 974438.23 | 07-APR-14:20 | 0.00 | 0.00 | 0.00 |
May | 0.298317E+12 | 0.00 | 306.40 | 0.266452E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1515081.45 | 30-MAY-10:40 | 1515081.45 | 30-MAY-10:40 | 0.00 | 0.00 | 0.00 |
June | 0.100096E+13 | 0.00 | 453.37 | 0.792011E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2113855.96 | 19-JUN-05:03 | 1654306.99 | 01-JUN-15:10 | 0.00 | 0.00 | 0.00 |
July | 0.132677E+13 | 0.00 | 484.64 | 0.103970E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2397433.49 | 21-JUL-03:02 | 1515823.80 | 11-JUL-14:25 | 0.00 | 0.00 | 0.00 |
August | 0.129637E+13 | 0.00 | 490.75 | 0.110260E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2361522.35 | 04-AUG-03:02 | 1589152.03 | 22-AUG-14:25 | 0.00 | 0.00 | 0.00 |
September | 0.690689E+12 | 0.00 | 401.58 | 0.580703E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2090670.53 | 07-SEP-05:02 | 1800057.64 | 01-SEP-14:15 | 0.00 | 0.00 | 0.00 |
October | 0.294965E+12 | 0.00 | 234.72 | 0.220688E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1403688.23 | 06-OCT-05:02 | 839596.80 | 04-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.783271E+10 | 0.00 | 40.57 | 0.734693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 485257.63 | 10-NOV-06:03 | 194980.86 | 03-NOV-14:00 | 0.00 | 0.00 | 0.00 |
December | 15505479.75 | 0.00 | 18.22 | 15505479.75 | 0.00 | 0.00 | 0.00 | 0.00 | 7041.37 | 13-DEC-10:00 | 7041.37 | 13-DEC-10:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.500112E+13 | 0.00 | 2649.14 | 0.409467E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 4552358.87 | 0.00 | 18.22 | 4552358.87 | 0.00 | 0.00 | 0.00 | 0.00 | 243.98 | 243.98 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.132677E+13 | 0.00 | 490.75 | 0.110260E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2397433.49 | 1800057.64 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 17100433.12 | 0.00 | 39.94 | 17100433.12 | 0.00 | 0.00 | 0.00 | 0.00 | 881.79 | 15-JAN-10:40 | 881.79 | 15-JAN-10:40 | 0.00 | 0.00 | 0.00 |
February | 11946115.34 | 0.00 | 33.52 | 11946115.34 | 0.00 | 0.00 | 0.00 | 0.00 | 1062.38 | 09-FEB-04:42 | 1062.38 | 09-FEB-04:42 | 0.00 | 0.00 | 0.00 |
March | 0.596599E+09 | 0.00 | 50.86 | 0.595262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 32239.90 | 27-MAR-16:00 | 32239.90 | 27-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.801909E+10 | 0.00 | 110.29 | 0.801801E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 101937.01 | 07-APR-14:00 | 101937.01 | 07-APR-14:00 | 0.00 | 0.00 | 0.00 |
May | 0.313793E+11 | 0.00 | 296.89 | 0.283432E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 185343.32 | 30-MAY-13:40 | 185343.32 | 30-MAY-13:40 | 0.00 | 0.00 | 0.00 |
June | 0.108731E+12 | 0.00 | 450.46 | 0.872937E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 221180.58 | 19-JUN-05:03 | 178430.01 | 22-JUN-15:10 | 0.00 | 0.00 | 0.00 |
July | 0.148916E+12 | 0.00 | 487.31 | 0.118319E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 259562.49 | 22-JUL-03:02 | 164858.81 | 11-JUL-14:15 | 0.00 | 0.00 | 0.00 |
August | 0.144224E+12 | 0.00 | 493.92 | 0.124012E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 251658.13 | 04-AUG-03:02 | 209279.41 | 22-AUG-14:50 | 0.00 | 0.00 | 0.00 |
September | 0.709912E+11 | 0.00 | 393.44 | 0.597165E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 220235.66 | 07-SEP-05:02 | 177671.17 | 01-SEP-14:10 | 0.00 | 0.00 | 0.00 |
October | 0.277737E+11 | 0.00 | 223.35 | 0.208934E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 135916.00 | 06-OCT-05:02 | 96524.44 | 04-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.601500E+09 | 0.00 | 53.24 | 0.563271E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16145.86 | 03-NOV-14:00 | 16145.86 | 03-NOV-14:00 | 0.00 | 0.00 | 0.00 |
December | 16443966.69 | 0.00 | 38.58 | 16443966.69 | 0.00 | 0.00 | 0.00 | 0.00 | 2566.65 | 25-DEC-08:55 | 2566.65 | 25-DEC-08:55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.541278E+12 | 0.00 | 2671.80 | 0.447800E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 11946115.34 | 0.00 | 33.52 | 11946115.34 | 0.00 | 0.00 | 0.00 | 0.00 | 881.79 | 881.79 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.148916E+12 | 0.00 | 493.92 | 0.124012E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 259562.49 | 209279.41 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 6817986.26 | 0.00 | 0.25 | 3030633.84 | 0.00 | 0.00 | 0.00 | 0.00 | 33639.40 | 24-JAN-06:03 | 14724.61 | 24-JAN-06:03 | 0.00 | 0.00 | 0.00 |
February | 55406.60 | 0.00 | 0.35 | 55406.60 | 0.00 | 0.00 | 0.00 | 0.00 | 66.02 | 11-FEB-09:40 | 66.02 | 11-FEB-09:40 | 0.00 | 0.00 | 0.00 |
March | 0.583547E+09 | 0.00 | 7.44 | 0.583345E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 40317.22 | 27-MAR-16:00 | 40317.22 | 27-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.529742E+10 | 0.00 | 68.11 | 0.527661E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64036.39 | 07-APR-13:50 | 64036.39 | 07-APR-13:50 | 0.00 | 0.00 | 0.00 |
May | 0.156082E+11 | 0.00 | 184.75 | 0.148307E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 95981.71 | 30-MAY-13:50 | 95981.71 | 30-MAY-13:50 | 0.00 | 0.00 | 0.00 |
June | 0.662030E+11 | 0.00 | 389.38 | 0.545677E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 148327.48 | 19-JUN-03:02 | 88087.74 | 12-JUN-03:02 | 0.00 | 0.00 | 0.00 |
July | 0.958121E+11 | 0.00 | 410.10 | 0.741709E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 146004.82 | 10-JUL-03:02 | 88070.85 | 12-JUL-03:02 | 0.00 | 0.00 | 0.00 |
August | 0.964099E+11 | 0.00 | 444.70 | 0.796964E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 137621.43 | 03-AUG-03:02 | 105247.17 | 13-AUG-15:48 | 0.00 | 0.00 | 0.00 |
September | 0.500455E+11 | 0.00 | 338.97 | 0.432785E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 130636.23 | 07-SEP-03:02 | 98538.06 | 01-SEP-14:00 | 0.00 | 0.00 | 0.00 |
October | 0.191459E+11 | 0.00 | 181.15 | 0.158261E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 101894.32 | 06-OCT-05:04 | 60581.29 | 04-OCT-13:00 | 0.00 | 0.00 | 0.00 |
November | 0.140696E+09 | 0.00 | 6.42 | 0.129357E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 57945.93 | 10-NOV-06:03 | 22991.59 | 10-NOV-06:03 | 0.00 | 0.00 | 0.00 |
December | 11741.56 | 0.00 | 0.67 | 11741.56 | 0.00 | 0.00 | 0.00 | 0.00 | 16.20 | 30-DEC-14:50 | 16.20 | 30-DEC-14:50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.349253E+12 | 0.00 | 2032.30 | 0.288363E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 11741.56 | 0.00 | 0.25 | 11741.56 | 0.00 | 0.00 | 0.00 | 0.00 | 16.20 | 16.20 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.964099E+11 | 0.00 | 444.70 | 0.796964E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 148327.48 | 105247.17 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.316612E+12 | 0.794855E+11 | 744.00 | 0.316485E+12 | 0.127274E+09 | 0.00 | 0.33 | 20-JAN-22:03 | 0.28 | 02-JAN-07:10 | 123808.53 | 20-JAN-22:03 | 123808.53 | 20-JAN-22:03 | 2524.82 | 24-JAN-15:20 | 31033.47 | 20-JAN-22:03 | 0.00 |
February | 0.506080E+12 | 0.120902E+12 | 672.00 | 0.506080E+12 | -0.0 | 0.00 | 0.55 | 21-FEB-22:03 | 0.51 | 06-FEB-07:05 | 215251.88 | 21-FEB-22:03 | 215251.88 | 21-FEB-22:03 | 0.00 | 12-FEB-17:15 | 51241.46 | 21-FEB-22:03 | 0.00 |
March | 0.810809E+12 | 0.185577E+12 | 744.00 | 0.810603E+12 | 0.206335E+09 | 0.00 | 0.92 | 31-MAR-24:00 | 0.72 | 31-MAR-17:10 | 393346.31 | 31-MAR-24:00 | 393346.31 | 31-MAR-24:00 | 5536.34 | 27-MAR-14:55 | 88699.95 | 27-MAR-16:00 | 0.00 |
April | 0.102580E+13 | 0.233198E+12 | 720.00 | 0.102539E+13 | 0.413586E+09 | 0.00 | 1.00 | 07-APR-11:40 | 0.36 | 30-APR-24:00 | 403559.36 | 27-APR-15:50 | 400844.88 | 07-APR-17:20 | 5595.91 | 27-APR-16:00 | 128313.93 | 07-APR-13:00 | 0.00 |
May | 0.331621E+12 | 0.858120E+11 | 744.00 | 0.329084E+12 | 0.253745E+10 | 0.00 | 0.54 | 31-MAY-23:20 | 0.31 | 20-MAY-07:00 | 212637.67 | 31-MAY-24:00 | 211203.06 | 31-MAY-24:00 | 7360.07 | 19-MAY-15:00 | 55389.79 | 31-MAY-23:20 | 0.00 |
June | 0.567339E+12 | 0.161615E+12 | 720.00 | 0.559347E+12 | 0.799257E+10 | 0.00 | 0.76 | 30-JUN-24:00 | 0.53 | 02-JUN-06:20 | 303183.36 | 30-JUN-24:00 | 302807.28 | 30-JUN-24:00 | 13261.44 | 15-JUN-14:00 | 96316.75 | 19-JUN-12:00 | 0.00 |
July | 0.837339E+12 | 0.260251E+12 | 744.00 | 0.826238E+12 | 0.111017E+11 | 0.00 | 0.98 | 31-JUL-24:00 | 0.76 | 01-JUL-00:10 | 395119.84 | 31-JUL-23:57 | 395119.84 | 31-JUL-23:57 | 13742.72 | 20-JUL-15:00 | 124646.44 | 07-JUL-12:00 | 0.00 |
August | 0.107599E+13 | 0.328715E+12 | 744.00 | 0.106841E+13 | 0.758046E+10 | 0.00 | 1.00 | 01-AUG-06:50 | 0.38 | 31-AUG-24:00 | 412547.07 | 18-AUG-19:00 | 405353.74 | 18-AUG-23:15 | 13691.41 | 03-AUG-16:10 | 147754.14 | 24-AUG-16:00 | 0.00 |
September | 0.329990E+12 | 0.915860E+11 | 720.00 | 0.324406E+12 | 0.558389E+10 | 0.00 | 0.53 | 30-SEP-24:00 | 0.31 | 30-SEP-06:10 | 211563.91 | 30-SEP-24:00 | 211563.91 | 30-SEP-24:00 | 10757.63 | 07-SEP-15:00 | 50688.34 | 01-SEP-13:45 | 0.00 |
October | 0.580454E+12 | 0.142098E+12 | 744.00 | 0.576521E+12 | 0.393300E+10 | 0.00 | 0.73 | 31-OCT-24:00 | 0.53 | 21-OCT-06:40 | 303266.01 | 31-OCT-24:00 | 303266.01 | 31-OCT-24:00 | 8394.54 | 06-OCT-09:30 | 69789.14 | 25-OCT-11:00 | 0.00 |
November | 0.789920E+12 | 0.180137E+12 | 720.00 | 0.789535E+12 | 0.384728E+09 | 0.00 | 0.77 | 03-NOV-14:00 | 0.72 | 01-NOV-06:10 | 312108.26 | 10-NOV-10:30 | 308644.49 | 06-NOV-22:03 | 6514.91 | 10-NOV-08:55 | 78764.74 | 03-NOV-14:00 | 0.00 |
December | 0.105746E+13 | 0.233462E+12 | 744.00 | 0.105746E+13 | -0.0 | 0.00 | 0.95 | 29-DEC-22:02 | 0.92 | 04-DEC-17:10 | 400230.39 | 14-DEC-22:02 | 400230.39 | 14-DEC-22:02 | 0.00 | 09-DEC-02:70 | 88238.34 | 29-DEC-22:02 | 0.00 |
Annual Sum or Average | 0.822941E+13 | 0.210284E+13 | 8760.00 | 0.818955E+13 | 0.398610E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.316612E+12 | 0.794855E+11 | 672.00 | 0.316485E+12 | -0.0 | 0.00 | 0.33 | 0.28 | 123808.53 | 123808.53 | 0.00 | 31033.47 | 0.00 | ||||||
Maximum of Months | 0.107599E+13 | 0.328715E+12 | 744.00 | 0.106841E+13 | 0.111017E+11 | 0.00 | 1.00 | 0.92 | 412547.07 | 405353.74 | 13742.72 | 147754.14 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.316061E+10 | 0.856909E+09 | 742.56 | 0.315541E+10 | 5200752.43 | 0.00 | 0.28 | 29-JAN-16:35 | 0.00 | 01-JAN-09:45 | 2147.11 | 29-JAN-16:35 | 2147.11 | 29-JAN-16:35 | 100.05 | 24-JAN-15:20 | 544.21 | 29-JAN-16:35 | 0.00 |
February | 0.793589E+10 | 0.201398E+10 | 672.00 | 0.793589E+10 | 0.00 | 0.00 | 0.53 | 20-FEB-16:25 | 0.28 | 06-FEB-07:05 | 4209.56 | 20-FEB-16:25 | 4209.56 | 20-FEB-16:25 | 0.00 | 05-FEB-20:18 | 1030.10 | 20-FEB-16:25 | 0.00 |
March | 0.149250E+11 | 0.347374E+10 | 744.00 | 0.149138E+11 | 11191680.16 | 0.00 | 0.82 | 31-MAR-24:00 | 0.58 | 01-MAR-07:05 | 7464.89 | 31-MAR-24:00 | 7464.89 | 31-MAR-24:00 | 216.96 | 27-MAR-14:50 | 1744.10 | 27-MAR-17:00 | 0.00 |
April | 0.197704E+11 | 0.448305E+10 | 720.00 | 0.197483E+11 | 22070246.97 | 0.00 | 0.95 | 16-APR-17:13 | 0.31 | 30-APR-24:00 | 8611.00 | 09-APR-17:23 | 8600.75 | 23-APR-17:45 | 218.46 | 27-APR-16:00 | 2550.59 | 07-APR-17:00 | 0.00 |
May | 0.564674E+10 | 0.145213E+10 | 744.00 | 0.554719E+10 | 99551586.46 | 0.00 | 0.48 | 31-MAY-23:30 | 0.19 | 04-MAY-07:00 | 4105.21 | 31-MAY-24:00 | 4052.12 | 31-MAY-24:00 | 286.23 | 18-MAY-15:30 | 1045.21 | 31-MAY-23:20 | 0.00 |
June | 0.109641E+11 | 0.305994E+10 | 720.00 | 0.106400E+11 | 0.324140E+09 | 0.00 | 0.68 | 30-JUN-24:00 | 0.44 | 02-JUN-06:30 | 5890.06 | 30-JUN-24:00 | 5871.80 | 30-JUN-24:00 | 532.49 | 15-JUN-14:00 | 1923.45 | 19-JUN-12:10 | 0.00 |
July | 0.166377E+11 | 0.505883E+10 | 744.00 | 0.161583E+11 | 0.479417E+09 | 0.00 | 0.89 | 31-JUL-24:00 | 0.68 | 01-JUL-06:10 | 7751.52 | 31-JUL-23:57 | 7751.52 | 31-JUL-23:57 | 606.92 | 20-JUL-15:00 | 2485.80 | 07-JUL-12:10 | 0.00 |
August | 0.216639E+11 | 0.655661E+10 | 744.00 | 0.212921E+11 | 0.371739E+09 | 0.00 | 1.00 | 01-AUG-12:10 | 0.32 | 31-AUG-24:00 | 8840.82 | 31-AUG-17:50 | 8524.74 | 13-AUG-18:12 | 612.70 | 03-AUG-15:00 | 3125.19 | 24-AUG-16:00 | 0.00 |
September | 0.583540E+10 | 0.159879E+10 | 720.00 | 0.562444E+10 | 0.210960E+09 | 0.00 | 0.46 | 30-SEP-24:00 | 0.20 | 30-SEP-07:00 | 3943.19 | 30-SEP-24:00 | 3943.19 | 30-SEP-24:00 | 445.26 | 07-SEP-15:00 | 990.30 | 14-SEP-14:00 | 0.00 |
October | 0.107610E+11 | 0.263014E+10 | 744.00 | 0.106068E+11 | 0.154151E+09 | 0.00 | 0.63 | 31-OCT-24:00 | 0.41 | 28-OCT-06:55 | 5667.09 | 31-OCT-24:00 | 5665.49 | 31-OCT-24:00 | 340.98 | 05-OCT-16:00 | 1363.66 | 04-OCT-16:00 | 0.00 |
November | 0.144972E+11 | 0.333604E+10 | 720.00 | 0.144789E+11 | 18273082.94 | 0.00 | 0.72 | 23-NOV-15:55 | 0.59 | 21-NOV-07:10 | 6142.42 | 03-NOV-16:00 | 6142.42 | 03-NOV-16:00 | 258.12 | 10-NOV-08:55 | 1501.74 | 03-NOV-14:00 | 0.00 |
December | 0.196917E+11 | 0.450548E+10 | 744.00 | 0.196917E+11 | -0.0 | 0.00 | 0.94 | 03-DEC-15:43 | 0.79 | 30-DEC-08:00 | 8036.54 | 25-DEC-16:10 | 8036.54 | 25-DEC-16:10 | 0.00 | 01-DEC-20:30 | 1842.65 | 03-DEC-15:43 | 0.00 |
Annual Sum or Average | 0.151490E+12 | 0.390256E+11 | 8758.56 | 0.149793E+12 | 0.169669E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.316061E+10 | 0.856909E+09 | 672.00 | 0.315541E+10 | -0.0 | 0.00 | 0.28 | 0.00 | 2147.11 | 2147.11 | 0.00 | 544.21 | 0.00 | ||||||
Maximum of Months | 0.216639E+11 | 0.655661E+10 | 744.00 | 0.212921E+11 | 0.479417E+09 | 0.00 | 1.00 | 0.79 | 8840.82 | 8600.75 | 612.70 | 3125.19 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.781669E+10 | 0.231994E+10 | 481.50 | 0.777888E+10 | 37808153.02 | 0.00 | 0.23 | 20-JAN-16:30 | 0.00 | 01-JAN-00:01 | 16519.59 | 20-JAN-16:30 | 16519.59 | 20-JAN-16:30 | 824.58 | 24-JAN-15:20 | 4307.64 | 20-JAN-16:30 | 0.00 |
February | 0.529047E+11 | 0.138335E+11 | 672.00 | 0.529047E+11 | -0.0 | 0.00 | 0.48 | 02-FEB-16:50 | 0.10 | 06-FEB-07:05 | 35982.61 | 22-FEB-17:00 | 35982.61 | 22-FEB-17:00 | 0.00 | 01-FEB-13:20 | 8965.85 | 02-FEB-16:50 | 0.00 |
March | 0.124645E+12 | 0.294524E+11 | 744.00 | 0.124533E+12 | 0.112781E+09 | 0.00 | 0.75 | 31-MAR-23:50 | 0.47 | 01-MAR-07:05 | 65138.24 | 31-MAR-23:50 | 65138.24 | 31-MAR-23:50 | 2150.82 | 27-MAR-14:50 | 16234.17 | 27-MAR-17:00 | 0.00 |
April | 0.177787E+12 | 0.406914E+11 | 720.00 | 0.177563E+12 | 0.223595E+09 | 0.00 | 0.94 | 07-APR-16:00 | 0.21 | 30-APR-24:00 | 80207.72 | 09-APR-17:23 | 80022.84 | 09-APR-17:27 | 2167.88 | 27-APR-16:00 | 24240.52 | 07-APR-17:00 | 0.00 |
May | 0.485466E+11 | 0.126196E+11 | 744.00 | 0.475759E+11 | 0.970669E+09 | 0.00 | 0.48 | 31-MAY-23:40 | 0.14 | 01-MAY-06:05 | 39103.47 | 31-MAY-24:00 | 38559.15 | 31-MAY-24:00 | 2820.27 | 18-MAY-15:30 | 9955.56 | 31-MAY-23:20 | 0.00 |
June | 0.103151E+12 | 0.288533E+11 | 720.00 | 0.999335E+11 | 0.321771E+10 | 0.00 | 0.67 | 30-JUN-24:00 | 0.42 | 03-JUN-07:00 | 55578.33 | 30-JUN-24:00 | 55393.76 | 30-JUN-24:00 | 5283.43 | 15-JUN-14:00 | 18385.15 | 19-JUN-12:10 | 0.00 |
July | 0.158782E+12 | 0.482828E+11 | 744.00 | 0.154003E+12 | 0.477982E+10 | 0.00 | 0.90 | 31-JUL-24:00 | 0.67 | 01-JUL-06:10 | 74729.25 | 31-JUL-23:57 | 74729.25 | 31-JUL-23:57 | 6049.36 | 20-JUL-15:00 | 23802.77 | 07-JUL-12:10 | 0.00 |
August | 0.206384E+12 | 0.624876E+11 | 744.00 | 0.202665E+12 | 0.371818E+10 | 0.00 | 1.00 | 01-AUG-12:10 | 0.29 | 31-AUG-24:00 | 84451.84 | 31-AUG-17:40 | 80940.40 | 15-AUG-18:00 | 6126.07 | 03-AUG-15:00 | 29865.46 | 24-AUG-16:00 | 0.00 |
September | 0.517526E+11 | 0.143027E+11 | 720.00 | 0.496863E+11 | 0.206630E+10 | 0.00 | 0.44 | 30-SEP-23:40 | 0.16 | 30-SEP-07:00 | 35786.41 | 30-SEP-23:40 | 35786.41 | 30-SEP-23:40 | 4412.54 | 07-SEP-15:00 | 9397.26 | 14-SEP-14:00 | 0.00 |
October | 0.944614E+11 | 0.232982E+11 | 744.00 | 0.929407E+11 | 0.152072E+10 | 0.00 | 0.58 | 31-OCT-24:00 | 0.34 | 28-OCT-06:55 | 49116.36 | 31-OCT-24:00 | 49092.17 | 31-OCT-24:00 | 3386.98 | 24-OCT-16:00 | 12930.56 | 04-OCT-16:00 | 0.00 |
November | 0.118746E+12 | 0.277698E+11 | 720.00 | 0.118564E+12 | 0.181816E+09 | 0.00 | 0.69 | 02-NOV-15:40 | 0.44 | 24-NOV-07:10 | 57451.97 | 03-NOV-16:00 | 57451.97 | 03-NOV-16:00 | 2552.63 | 10-NOV-10:30 | 14031.70 | 03-NOV-14:00 | 0.00 |
December | 0.161803E+12 | 0.377734E+11 | 744.00 | 0.161803E+12 | -0.0 | 0.00 | 0.87 | 21-DEC-16:10 | 0.60 | 31-DEC-23:53 | 71210.37 | 08-DEC-16:10 | 71210.37 | 08-DEC-16:10 | 0.00 | 07-DEC-02:25 | 16270.51 | 21-DEC-16:10 | 0.00 |
Annual Sum or Average | 0.130678E+13 | 0.341685E+12 | 8497.50 | 0.128995E+13 | 0.168294E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.781669E+10 | 0.231994E+10 | 481.50 | 0.777888E+10 | -0.0 | 0.00 | 0.23 | 0.00 | 16519.59 | 16519.59 | 0.00 | 4307.64 | 0.00 | ||||||
Maximum of Months | 0.206384E+12 | 0.624876E+11 | 744.00 | 0.202665E+12 | 0.477982E+10 | 0.00 | 1.00 | 0.67 | 84451.84 | 80940.40 | 6126.07 | 29865.46 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.280669E+09 | 85111568.41 | 199.47 | 0.277886E+09 | 2783332.87 | 0.00 | 0.21 | 19-JAN-16:30 | 0.00 | 01-JAN-00:01 | 1578.37 | 19-JAN-16:20 | 1578.37 | 19-JAN-16:20 | 73.24 | 24-JAN-15:20 | 407.88 | 19-JAN-16:20 | 0.00 |
February | 0.373381E+10 | 0.999694E+09 | 653.77 | 0.373381E+10 | 0.00 | 0.00 | 0.46 | 02-FEB-16:50 | 0.00 | 05-FEB-03:02 | 3477.88 | 17-FEB-17:00 | 3477.88 | 17-FEB-17:00 | 0.00 | 28-FEB-18:10 | 871.69 | 02-FEB-16:50 | 0.00 |
March | 0.110449E+11 | 0.264475E+10 | 744.00 | 0.110339E+11 | 11012180.08 | 0.00 | 0.71 | 27-MAR-17:00 | 0.34 | 13-MAR-03:17 | 5944.52 | 31-MAR-23:20 | 5944.52 | 31-MAR-23:20 | 215.56 | 27-MAR-14:50 | 1616.62 | 27-MAR-17:00 | 0.00 |
April | 0.168449E+11 | 0.389446E+10 | 720.00 | 0.168228E+11 | 22152140.63 | 0.00 | 0.94 | 07-APR-16:00 | 0.12 | 30-APR-24:00 | 8100.14 | 09-APR-17:23 | 8081.60 | 09-APR-17:27 | 217.01 | 27-APR-16:00 | 2457.28 | 07-APR-17:00 | 0.00 |
May | 0.449874E+10 | 0.118277E+10 | 743.75 | 0.440322E+10 | 95517455.85 | 0.00 | 0.47 | 31-MAY-23:30 | 0.00 | 01-MAY-03:55 | 3891.39 | 31-MAY-24:00 | 3836.43 | 31-MAY-24:00 | 282.64 | 18-MAY-15:30 | 993.44 | 31-MAY-23:20 | 0.00 |
June | 0.103334E+11 | 0.289886E+10 | 720.00 | 0.100117E+11 | 0.321703E+09 | 0.00 | 0.65 | 30-JUN-24:00 | 0.38 | 03-JUN-06:50 | 5484.75 | 30-JUN-24:00 | 5465.88 | 30-JUN-24:00 | 530.62 | 15-JUN-14:00 | 1880.90 | 19-JUN-12:10 | 0.00 |
July | 0.160051E+11 | 0.487496E+10 | 744.00 | 0.155271E+11 | 0.477926E+09 | 0.00 | 0.89 | 31-JUL-24:00 | 0.65 | 01-JUL-06:10 | 7486.24 | 31-JUL-23:57 | 7486.24 | 31-JUL-23:57 | 606.12 | 20-JUL-15:00 | 2415.06 | 07-JUL-12:10 | 0.00 |
August | 0.207263E+11 | 0.629227E+10 | 744.00 | 0.203545E+11 | 0.371829E+09 | 0.00 | 1.00 | 01-AUG-12:30 | 0.28 | 31-AUG-24:00 | 8582.06 | 31-AUG-17:10 | 8266.25 | 13-AUG-17:42 | 614.27 | 03-AUG-15:00 | 3042.28 | 24-AUG-16:00 | 0.00 |
September | 0.496566E+10 | 0.138439E+10 | 720.00 | 0.475987E+10 | 0.205787E+09 | 0.00 | 0.41 | 30-SEP-23:20 | 0.11 | 24-SEP-06:50 | 3322.70 | 30-SEP-23:20 | 3322.70 | 30-SEP-23:20 | 444.83 | 07-SEP-15:00 | 968.97 | 14-SEP-14:00 | 0.00 |
October | 0.860050E+10 | 0.214371E+10 | 744.00 | 0.844951E+10 | 0.150984E+09 | 0.00 | 0.56 | 04-OCT-16:00 | 0.24 | 29-OCT-07:30 | 4660.74 | 04-OCT-16:00 | 4392.60 | 31-OCT-23:30 | 338.64 | 24-OCT-16:00 | 1313.93 | 04-OCT-16:00 | 0.00 |
November | 0.102506E+11 | 0.243326E+10 | 720.00 | 0.102327E+11 | 17906902.45 | 0.00 | 0.68 | 02-NOV-15:30 | 0.28 | 24-NOV-04:03 | 5719.09 | 03-NOV-16:00 | 5719.09 | 03-NOV-16:00 | 254.97 | 10-NOV-10:30 | 1390.43 | 03-NOV-14:10 | 0.00 |
December | 0.142322E+11 | 0.337935E+10 | 744.00 | 0.142322E+11 | -0.0 | 0.00 | 0.83 | 21-DEC-16:00 | 0.45 | 31-DEC-23:55 | 6920.97 | 08-DEC-16:10 | 6920.97 | 08-DEC-16:10 | 0.00 | 26-DEC-04:55 | 1582.46 | 21-DEC-16:00 | 0.00 |
Annual Sum or Average | 0.121517E+12 | 0.322136E+11 | 8196.99 | 0.119839E+12 | 0.167760E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.280669E+09 | 85111568.41 | 199.47 | 0.277886E+09 | -0.0 | 0.00 | 0.21 | 0.00 | 1578.37 | 1578.37 | 0.00 | 407.88 | 0.00 | ||||||
Maximum of Months | 0.207263E+11 | 0.629227E+10 | 744.00 | 0.203545E+11 | 0.477926E+09 | 0.00 | 1.00 | 0.65 | 8582.06 | 8266.25 | 614.27 | 3042.28 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 87.62 | 0.00 | 87.62 | 1.90 | 559.19 | 0.00 | 0.00 | 0.00 |
February | 119.91 | 0.00 | 119.91 | 6.48 | 578.59 | 0.00 | 0.00 | 0.00 |
March | 166.28 | 0.00 | 166.28 | 46.29 | 399.23 | 0.00 | 0.00 | 0.00 |
April | 199.73 | 0.57 | 199.16 | 111.82 | 284.60 | 0.00 | 0.00 | 0.00 |
May | 264.98 | 8.83 | 256.15 | 241.87 | 163.72 | 0.00 | 0.00 | 0.00 |
June | 281.00 | 15.10 | 265.91 | 347.98 | 86.93 | 0.00 | 0.00 | 0.00 |
July | 271.56 | 9.82 | 261.74 | 389.46 | 46.26 | 0.00 | 0.00 | 0.00 |
August | 240.59 | 2.86 | 237.73 | 339.33 | 63.83 | 0.00 | 0.00 | 0.00 |
September | 181.37 | 0.03 | 181.33 | 191.55 | 136.55 | 0.00 | 0.00 | 0.00 |
October | 156.96 | 0.00 | 156.96 | 107.03 | 257.39 | 0.00 | 0.00 | 0.00 |
November | 110.09 | 0.00 | 110.09 | 21.32 | 417.25 | 0.00 | 0.00 | 0.00 |
December | 76.43 | 0.00 | 76.43 | 0.88 | 548.03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 180.06 | 3.12 | 176.94 | 151.48 | 293.50 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 76.43 | 0.00 | 76.43 | 0.88 | 46.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 281.00 | 15.10 | 265.91 | 389.46 | 578.59 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 87.62 | 0.00 | 87.62 | 1.90 | 559.19 | 0.00 | 0.00 | 0.00 |
February | 119.91 | 0.00 | 119.91 | 6.48 | 578.59 | 0.00 | 0.00 | 0.00 |
March | 166.28 | 0.00 | 166.28 | 46.29 | 399.23 | 0.00 | 0.00 | 0.00 |
April | 199.73 | 0.57 | 199.16 | 111.81 | 284.60 | 0.00 | 0.00 | 0.00 |
May | 264.97 | 8.83 | 256.14 | 241.86 | 163.72 | 0.00 | 0.00 | 0.00 |
June | 281.00 | 15.10 | 265.90 | 347.97 | 86.93 | 0.00 | 0.00 | 0.00 |
July | 271.56 | 9.82 | 261.74 | 389.46 | 46.26 | 0.00 | 0.00 | 0.00 |
August | 240.59 | 2.86 | 237.73 | 339.32 | 63.83 | 0.00 | 0.00 | 0.00 |
September | 181.36 | 0.03 | 181.33 | 191.55 | 136.55 | 0.00 | 0.00 | 0.00 |
October | 156.96 | 0.00 | 156.96 | 107.03 | 257.39 | 0.00 | 0.00 | 0.00 |
November | 110.09 | 0.00 | 110.09 | 21.32 | 417.25 | 0.00 | 0.00 | 0.00 |
December | 76.43 | 0.00 | 76.43 | 0.88 | 548.03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 180.05 | 3.12 | 176.94 | 151.48 | 293.50 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 76.43 | 0.00 | 76.43 | 0.88 | 46.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 281.00 | 15.10 | 265.90 | 389.46 | 578.59 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 87.62 | 0.00 | 87.62 | 1.90 | 559.19 | 0.00 | 0.00 | 0.00 |
February | 119.91 | 0.00 | 119.91 | 6.48 | 578.59 | 0.00 | 0.00 | 0.00 |
March | 166.28 | 0.00 | 166.28 | 46.29 | 399.23 | 0.00 | 0.00 | 0.00 |
April | 199.73 | 0.57 | 199.16 | 111.82 | 284.60 | 0.00 | 0.00 | 0.00 |
May | 264.97 | 8.83 | 256.15 | 241.86 | 163.72 | 0.00 | 0.00 | 0.00 |
June | 281.00 | 15.10 | 265.90 | 347.97 | 86.93 | 0.00 | 0.00 | 0.00 |
July | 271.56 | 9.82 | 261.74 | 389.46 | 46.26 | 0.00 | 0.00 | 0.00 |
August | 240.59 | 2.86 | 237.73 | 339.33 | 63.83 | 0.00 | 0.00 | 0.00 |
September | 181.37 | 0.03 | 181.33 | 191.55 | 136.55 | 0.00 | 0.00 | 0.00 |
October | 156.96 | 0.00 | 156.96 | 107.03 | 257.39 | 0.00 | 0.00 | 0.00 |
November | 110.09 | 0.00 | 110.09 | 21.32 | 417.25 | 0.00 | 0.00 | 0.00 |
December | 76.43 | 0.00 | 76.43 | 0.88 | 548.03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 180.05 | 3.12 | 176.94 | 151.48 | 293.50 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 76.43 | 0.00 | 76.43 | 0.88 | 46.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 281.00 | 15.10 | 265.90 | 389.46 | 578.59 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 87.62 | 0.00 | 87.62 | 1.90 | 559.19 | 0.00 | 0.00 | 0.00 |
February | 119.91 | 0.00 | 119.91 | 6.48 | 578.59 | 0.00 | 0.00 | 0.00 |
March | 166.28 | 0.00 | 166.28 | 46.29 | 399.23 | 0.00 | 0.00 | 0.00 |
April | 199.73 | 0.57 | 199.16 | 111.81 | 284.60 | 0.00 | 0.00 | 0.00 |
May | 264.97 | 8.83 | 256.14 | 241.86 | 163.72 | 0.00 | 0.00 | 0.00 |
June | 281.00 | 15.10 | 265.90 | 347.97 | 86.93 | 0.00 | 0.00 | 0.00 |
July | 271.56 | 9.82 | 261.74 | 389.46 | 46.26 | 0.00 | 0.00 | 0.00 |
August | 240.59 | 2.86 | 237.73 | 339.32 | 63.83 | 0.00 | 0.00 | 0.00 |
September | 181.36 | 0.03 | 181.33 | 191.55 | 136.55 | 0.00 | 0.00 | 0.00 |
October | 156.96 | 0.00 | 156.96 | 107.03 | 257.39 | 0.00 | 0.00 | 0.00 |
November | 110.09 | 0.00 | 110.09 | 21.32 | 417.25 | 0.00 | 0.00 | 0.00 |
December | 76.43 | 0.00 | 76.43 | 0.88 | 548.03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 180.05 | 3.12 | 176.94 | 151.48 | 293.50 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 76.43 | 0.00 | 76.43 | 0.88 | 46.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 281.00 | 15.10 | 265.90 | 389.46 | 578.59 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 87.62 | 0.00 | 87.62 | 1.90 | 559.17 | 0.00 | 0.00 | 0.00 |
February | 119.90 | 0.00 | 119.90 | 6.48 | 578.57 | 0.00 | 0.00 | 0.00 |
March | 166.27 | 0.00 | 166.27 | 46.29 | 399.21 | 0.00 | 0.00 | 0.00 |
April | 199.72 | 0.57 | 199.15 | 111.81 | 284.59 | 0.00 | 0.00 | 0.00 |
May | 264.96 | 8.83 | 256.13 | 241.85 | 163.72 | 0.00 | 0.00 | 0.00 |
June | 280.99 | 15.10 | 265.89 | 347.96 | 86.93 | 0.00 | 0.00 | 0.00 |
July | 271.55 | 9.82 | 261.73 | 389.44 | 46.26 | 0.00 | 0.00 | 0.00 |
August | 240.58 | 2.86 | 237.72 | 339.31 | 63.83 | 0.00 | 0.00 | 0.00 |
September | 181.36 | 0.03 | 181.32 | 191.54 | 136.55 | 0.00 | 0.00 | 0.00 |
October | 156.95 | 0.00 | 156.95 | 107.03 | 257.38 | 0.00 | 0.00 | 0.00 |
November | 110.09 | 0.00 | 110.09 | 21.31 | 417.23 | 0.00 | 0.00 | 0.00 |
December | 76.43 | 0.00 | 76.43 | 0.88 | 548.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 180.05 | 3.12 | 176.93 | 151.47 | 293.49 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 76.43 | 0.00 | 76.43 | 0.88 | 46.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 280.99 | 15.10 | 265.89 | 389.44 | 578.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 203.37 | 81.54 | 121.84 | 116.22 | 571.95 | 0.00 | 0.00 | 0.00 |
February | 315.39 | 147.13 | 168.26 | 209.03 | 571.71 | 0.00 | 0.00 | 0.00 |
March | 402.34 | 171.12 | 231.22 | 340.01 | 414.24 | 0.00 | 0.00 | 0.00 |
April | 482.83 | 211.50 | 271.34 | 480.67 | 292.54 | 0.00 | 0.00 | 0.00 |
May | 585.58 | 234.03 | 351.54 | 677.26 | 182.63 | 0.00 | 0.00 | 0.00 |
June | 542.70 | 196.46 | 346.25 | 714.80 | 95.28 | 0.00 | 0.00 | 0.00 |
July | 545.08 | 196.71 | 348.37 | 782.17 | 47.33 | 0.00 | 0.00 | 0.00 |
August | 613.77 | 276.75 | 337.02 | 874.97 | 65.10 | 0.00 | 0.00 | 0.00 |
September | 457.76 | 205.38 | 252.38 | 572.79 | 144.27 | 0.00 | 0.00 | 0.00 |
October | 414.99 | 188.09 | 226.90 | 455.71 | 270.39 | 0.00 | 0.00 | 0.00 |
November | 256.64 | 98.55 | 158.09 | 193.39 | 420.24 | 0.00 | 0.00 | 0.00 |
December | 199.94 | 93.88 | 106.06 | 125.43 | 542.35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 419.03 | 175.29 | 243.74 | 463.64 | 299.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 199.94 | 81.54 | 106.06 | 116.22 | 47.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 613.77 | 276.75 | 351.54 | 874.97 | 571.95 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 203.37 | 81.54 | 121.84 | 116.22 | 571.95 | 0.00 | 0.00 | 0.00 |
February | 315.39 | 147.13 | 168.26 | 209.03 | 571.71 | 0.00 | 0.00 | 0.00 |
March | 402.34 | 171.12 | 231.22 | 340.01 | 414.24 | 0.00 | 0.00 | 0.00 |
April | 482.83 | 211.50 | 271.34 | 480.67 | 292.54 | 0.00 | 0.00 | 0.00 |
May | 585.58 | 234.03 | 351.54 | 677.26 | 182.63 | 0.00 | 0.00 | 0.00 |
June | 542.70 | 196.46 | 346.25 | 714.80 | 95.28 | 0.00 | 0.00 | 0.00 |
July | 545.08 | 196.71 | 348.37 | 782.17 | 47.33 | 0.00 | 0.00 | 0.00 |
August | 613.77 | 276.75 | 337.02 | 874.97 | 65.10 | 0.00 | 0.00 | 0.00 |
September | 457.76 | 205.38 | 252.38 | 572.79 | 144.27 | 0.00 | 0.00 | 0.00 |
October | 414.99 | 188.09 | 226.90 | 455.71 | 270.39 | 0.00 | 0.00 | 0.00 |
November | 256.64 | 98.55 | 158.09 | 193.39 | 420.24 | 0.00 | 0.00 | 0.00 |
December | 199.94 | 93.88 | 106.06 | 125.43 | 542.35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 419.03 | 175.29 | 243.74 | 463.64 | 299.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 199.94 | 81.54 | 106.06 | 116.22 | 47.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 613.77 | 276.75 | 351.54 | 874.97 | 571.95 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 203.37 | 81.54 | 121.84 | 116.22 | 571.94 | 0.00 | 0.00 | 0.00 |
February | 315.38 | 147.13 | 168.26 | 209.03 | 571.70 | 0.00 | 0.00 | 0.00 |
March | 402.33 | 171.11 | 231.22 | 340.01 | 414.23 | 0.00 | 0.00 | 0.00 |
April | 482.82 | 211.49 | 271.33 | 480.67 | 292.54 | 0.00 | 0.00 | 0.00 |
May | 585.57 | 234.03 | 351.54 | 677.25 | 182.63 | 0.00 | 0.00 | 0.00 |
June | 542.69 | 196.45 | 346.24 | 714.78 | 95.28 | 0.00 | 0.00 | 0.00 |
July | 545.07 | 196.70 | 348.37 | 782.15 | 47.33 | 0.00 | 0.00 | 0.00 |
August | 613.76 | 276.75 | 337.02 | 874.96 | 65.09 | 0.00 | 0.00 | 0.00 |
September | 457.75 | 205.37 | 252.37 | 572.78 | 144.27 | 0.00 | 0.00 | 0.00 |
October | 414.98 | 188.08 | 226.90 | 455.71 | 270.38 | 0.00 | 0.00 | 0.00 |
November | 256.63 | 98.55 | 158.08 | 193.39 | 420.23 | 0.00 | 0.00 | 0.00 |
December | 199.93 | 93.88 | 106.06 | 125.43 | 542.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 419.02 | 175.29 | 243.73 | 463.63 | 299.97 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 199.93 | 81.54 | 106.06 | 116.22 | 47.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 613.76 | 276.75 | 351.54 | 874.96 | 571.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 453.29 | 296.81 | 156.47 | 439.66 | 480.75 | 0.00 | 0.00 | 0.00 |
February | 597.87 | 395.74 | 202.13 | 590.48 | 487.36 | 0.00 | 0.00 | 0.00 |
March | 539.39 | 299.37 | 240.02 | 566.10 | 370.27 | 0.00 | 0.00 | 0.00 |
April | 418.55 | 165.51 | 253.04 | 452.57 | 280.25 | 0.00 | 0.00 | 0.00 |
May | 366.80 | 76.51 | 290.29 | 425.24 | 173.56 | 0.00 | 0.00 | 0.00 |
June | 344.23 | 52.62 | 291.61 | 465.56 | 93.10 | 0.00 | 0.00 | 0.00 |
July | 360.82 | 62.67 | 298.15 | 543.67 | 48.30 | 0.00 | 0.00 | 0.00 |
August | 481.84 | 178.72 | 303.12 | 730.75 | 68.95 | 0.00 | 0.00 | 0.00 |
September | 522.80 | 270.41 | 252.39 | 700.63 | 138.94 | 0.00 | 0.00 | 0.00 |
October | 716.19 | 449.10 | 267.09 | 891.45 | 250.85 | 0.00 | 0.00 | 0.00 |
November | 496.62 | 298.24 | 198.38 | 521.21 | 367.53 | 0.00 | 0.00 | 0.00 |
December | 491.29 | 348.79 | 142.51 | 495.30 | 457.08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 481.93 | 240.43 | 241.50 | 568.74 | 266.80 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 344.23 | 52.62 | 142.51 | 425.24 | 48.30 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 716.19 | 449.10 | 303.12 | 891.45 | 487.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 453.28 | 296.81 | 156.47 | 439.66 | 480.75 | 0.00 | 0.00 | 0.00 |
February | 597.86 | 395.74 | 202.13 | 590.48 | 487.36 | 0.00 | 0.00 | 0.00 |
March | 539.39 | 299.37 | 240.02 | 566.09 | 370.27 | 0.00 | 0.00 | 0.00 |
April | 418.55 | 165.50 | 253.04 | 452.57 | 280.25 | 0.00 | 0.00 | 0.00 |
May | 366.80 | 76.51 | 290.29 | 425.23 | 173.56 | 0.00 | 0.00 | 0.00 |
June | 344.23 | 52.62 | 291.61 | 465.55 | 93.10 | 0.00 | 0.00 | 0.00 |
July | 360.82 | 62.67 | 298.15 | 543.66 | 48.29 | 0.00 | 0.00 | 0.00 |
August | 481.83 | 178.72 | 303.11 | 730.75 | 68.95 | 0.00 | 0.00 | 0.00 |
September | 522.80 | 270.41 | 252.39 | 700.63 | 138.94 | 0.00 | 0.00 | 0.00 |
October | 716.19 | 449.10 | 267.09 | 891.45 | 250.85 | 0.00 | 0.00 | 0.00 |
November | 496.61 | 298.24 | 198.37 | 521.20 | 367.53 | 0.00 | 0.00 | 0.00 |
December | 491.29 | 348.78 | 142.51 | 495.29 | 457.08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 481.93 | 240.42 | 241.50 | 568.73 | 266.80 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 344.23 | 52.62 | 142.51 | 425.23 | 48.29 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 716.19 | 449.10 | 303.11 | 891.45 | 487.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 453.29 | 296.81 | 156.47 | 439.66 | 480.75 | 0.00 | 0.00 | 0.00 |
February | 597.87 | 395.74 | 202.13 | 590.48 | 487.36 | 0.00 | 0.00 | 0.00 |
March | 539.39 | 299.37 | 240.02 | 566.10 | 370.27 | 0.00 | 0.00 | 0.00 |
April | 418.55 | 165.51 | 253.04 | 452.57 | 280.25 | 0.00 | 0.00 | 0.00 |
May | 366.80 | 76.51 | 290.29 | 425.24 | 173.56 | 0.00 | 0.00 | 0.00 |
June | 344.23 | 52.62 | 291.61 | 465.56 | 93.10 | 0.00 | 0.00 | 0.00 |
July | 360.82 | 62.67 | 298.15 | 543.67 | 48.30 | 0.00 | 0.00 | 0.00 |
August | 481.84 | 178.72 | 303.12 | 730.75 | 68.95 | 0.00 | 0.00 | 0.00 |
September | 522.80 | 270.41 | 252.39 | 700.63 | 138.94 | 0.00 | 0.00 | 0.00 |
October | 716.19 | 449.10 | 267.09 | 891.45 | 250.85 | 0.00 | 0.00 | 0.00 |
November | 496.62 | 298.24 | 198.38 | 521.21 | 367.53 | 0.00 | 0.00 | 0.00 |
December | 491.29 | 348.79 | 142.51 | 495.30 | 457.08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 481.93 | 240.43 | 241.50 | 568.74 | 266.80 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 344.23 | 52.62 | 142.51 | 425.24 | 48.30 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 716.19 | 449.10 | 303.12 | 891.45 | 487.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 453.28 | 296.81 | 156.47 | 439.66 | 480.75 | 0.00 | 0.00 | 0.00 |
February | 597.86 | 395.74 | 202.13 | 590.48 | 487.36 | 0.00 | 0.00 | 0.00 |
March | 539.39 | 299.37 | 240.02 | 566.09 | 370.27 | 0.00 | 0.00 | 0.00 |
April | 418.55 | 165.50 | 253.04 | 452.57 | 280.25 | 0.00 | 0.00 | 0.00 |
May | 366.80 | 76.51 | 290.29 | 425.23 | 173.56 | 0.00 | 0.00 | 0.00 |
June | 344.23 | 52.62 | 291.61 | 465.55 | 93.10 | 0.00 | 0.00 | 0.00 |
July | 360.82 | 62.67 | 298.15 | 543.66 | 48.29 | 0.00 | 0.00 | 0.00 |
August | 481.83 | 178.72 | 303.11 | 730.75 | 68.95 | 0.00 | 0.00 | 0.00 |
September | 522.80 | 270.41 | 252.39 | 700.63 | 138.94 | 0.00 | 0.00 | 0.00 |
October | 716.19 | 449.10 | 267.09 | 891.45 | 250.85 | 0.00 | 0.00 | 0.00 |
November | 496.61 | 298.24 | 198.37 | 521.20 | 367.53 | 0.00 | 0.00 | 0.00 |
December | 491.29 | 348.78 | 142.51 | 495.29 | 457.08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 481.93 | 240.42 | 241.50 | 568.73 | 266.80 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 344.23 | 52.62 | 142.51 | 425.23 | 48.29 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 716.19 | 449.10 | 303.11 | 891.45 | 487.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 453.27 | 296.80 | 156.47 | 439.64 | 480.73 | 0.00 | 0.00 | 0.00 |
February | 597.84 | 395.72 | 202.12 | 590.46 | 487.34 | 0.00 | 0.00 | 0.00 |
March | 539.37 | 299.36 | 240.01 | 566.07 | 370.26 | 0.00 | 0.00 | 0.00 |
April | 418.53 | 165.50 | 253.03 | 452.55 | 280.24 | 0.00 | 0.00 | 0.00 |
May | 366.78 | 76.50 | 290.28 | 425.22 | 173.56 | 0.00 | 0.00 | 0.00 |
June | 344.21 | 52.62 | 291.60 | 465.53 | 93.09 | 0.00 | 0.00 | 0.00 |
July | 360.81 | 62.67 | 298.13 | 543.64 | 48.29 | 0.00 | 0.00 | 0.00 |
August | 481.81 | 178.71 | 303.10 | 730.72 | 68.95 | 0.00 | 0.00 | 0.00 |
September | 522.78 | 270.40 | 252.38 | 700.60 | 138.94 | 0.00 | 0.00 | 0.00 |
October | 716.16 | 449.08 | 267.08 | 891.41 | 250.84 | 0.00 | 0.00 | 0.00 |
November | 496.59 | 298.23 | 198.37 | 521.18 | 367.51 | 0.00 | 0.00 | 0.00 |
December | 491.27 | 348.77 | 142.50 | 495.28 | 457.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 481.91 | 240.41 | 241.49 | 568.71 | 266.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 344.21 | 52.62 | 142.50 | 425.22 | 48.29 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 716.16 | 449.08 | 303.10 | 891.41 | 487.34 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 200.78 | 82.24 | 118.54 | 114.07 | 616.37 | 0.00 | 0.00 | 0.00 |
February | 296.07 | 130.04 | 166.04 | 188.24 | 641.94 | 0.00 | 0.00 | 0.00 |
March | 437.19 | 201.84 | 235.35 | 370.03 | 466.25 | 0.00 | 0.00 | 0.00 |
April | 477.82 | 204.45 | 273.38 | 462.32 | 355.75 | 0.00 | 0.00 | 0.00 |
May | 556.62 | 211.38 | 345.24 | 636.17 | 206.67 | 0.00 | 0.00 | 0.00 |
June | 609.20 | 245.71 | 363.49 | 794.96 | 120.11 | 0.00 | 0.00 | 0.00 |
July | 570.55 | 214.85 | 355.70 | 799.53 | 71.90 | 0.00 | 0.00 | 0.00 |
August | 631.18 | 292.20 | 338.99 | 883.60 | 98.95 | 0.00 | 0.00 | 0.00 |
September | 448.09 | 195.81 | 252.28 | 559.13 | 168.47 | 0.00 | 0.00 | 0.00 |
October | 444.25 | 216.03 | 228.22 | 487.46 | 310.34 | 0.00 | 0.00 | 0.00 |
November | 208.62 | 60.29 | 148.33 | 121.42 | 491.52 | 0.00 | 0.00 | 0.00 |
December | 185.56 | 80.29 | 105.27 | 101.30 | 639.17 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 423.05 | 178.34 | 244.71 | 461.82 | 347.26 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 185.56 | 60.29 | 105.27 | 101.30 | 71.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 631.18 | 292.20 | 363.49 | 883.60 | 641.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 200.78 | 82.24 | 118.54 | 114.07 | 616.37 | 0.00 | 0.00 | 0.00 |
February | 296.07 | 130.04 | 166.04 | 188.24 | 641.94 | 0.00 | 0.00 | 0.00 |
March | 437.19 | 201.84 | 235.35 | 370.03 | 466.25 | 0.00 | 0.00 | 0.00 |
April | 477.82 | 204.45 | 273.38 | 462.32 | 355.75 | 0.00 | 0.00 | 0.00 |
May | 556.62 | 211.38 | 345.24 | 636.17 | 206.67 | 0.00 | 0.00 | 0.00 |
June | 609.20 | 245.71 | 363.49 | 794.96 | 120.11 | 0.00 | 0.00 | 0.00 |
July | 570.55 | 214.85 | 355.70 | 799.53 | 71.90 | 0.00 | 0.00 | 0.00 |
August | 631.18 | 292.20 | 338.99 | 883.60 | 98.95 | 0.00 | 0.00 | 0.00 |
September | 448.09 | 195.81 | 252.28 | 559.13 | 168.47 | 0.00 | 0.00 | 0.00 |
October | 444.25 | 216.03 | 228.22 | 487.46 | 310.34 | 0.00 | 0.00 | 0.00 |
November | 208.62 | 60.29 | 148.33 | 121.42 | 491.52 | 0.00 | 0.00 | 0.00 |
December | 185.56 | 80.29 | 105.27 | 101.30 | 639.17 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 423.05 | 178.34 | 244.71 | 461.82 | 347.26 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 185.56 | 60.29 | 105.27 | 101.30 | 71.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 631.18 | 292.20 | 363.49 | 883.60 | 641.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 200.77 | 82.24 | 118.53 | 114.07 | 616.35 | 0.00 | 0.00 | 0.00 |
February | 296.07 | 130.03 | 166.03 | 188.24 | 641.93 | 0.00 | 0.00 | 0.00 |
March | 437.18 | 201.83 | 235.35 | 370.03 | 466.24 | 0.00 | 0.00 | 0.00 |
April | 477.82 | 204.45 | 273.37 | 462.31 | 355.74 | 0.00 | 0.00 | 0.00 |
May | 556.61 | 211.38 | 345.23 | 636.15 | 206.66 | 0.00 | 0.00 | 0.00 |
June | 609.19 | 245.70 | 363.49 | 794.95 | 120.11 | 0.00 | 0.00 | 0.00 |
July | 570.54 | 214.85 | 355.69 | 799.51 | 71.90 | 0.00 | 0.00 | 0.00 |
August | 631.17 | 292.19 | 338.98 | 883.59 | 98.95 | 0.00 | 0.00 | 0.00 |
September | 448.08 | 195.81 | 252.27 | 559.12 | 168.47 | 0.00 | 0.00 | 0.00 |
October | 444.24 | 216.02 | 228.22 | 487.45 | 310.33 | 0.00 | 0.00 | 0.00 |
November | 208.61 | 60.29 | 148.32 | 121.42 | 491.51 | 0.00 | 0.00 | 0.00 |
December | 185.56 | 80.29 | 105.27 | 101.30 | 639.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 423.04 | 178.33 | 244.71 | 461.81 | 347.25 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 185.56 | 60.29 | 105.27 | 101.30 | 71.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 631.17 | 292.19 | 363.49 | 883.59 | 641.93 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 438.12 | 0.00 | 438.12 | 25.36 | 2481.94 | 0.00 | 0.00 | 0.00 |
February | 599.54 | 0.00 | 599.54 | 52.82 | 2590.17 | 0.00 | 0.00 | 0.00 |
March | 831.42 | 0.00 | 831.42 | 291.00 | 1734.30 | 0.00 | 0.00 | 0.00 |
April | 998.65 | 2.84 | 995.80 | 622.43 | 1241.02 | 0.00 | 0.00 | 0.00 |
May | 1324.88 | 44.15 | 1280.74 | 1233.61 | 767.78 | 0.00 | 0.00 | 0.00 |
June | 1405.02 | 75.50 | 1329.53 | 1746.18 | 418.59 | 0.00 | 0.00 | 0.00 |
July | 1357.82 | 49.10 | 1308.72 | 1952.20 | 232.43 | 0.00 | 0.00 | 0.00 |
August | 1202.96 | 14.32 | 1188.65 | 1710.28 | 315.94 | 0.00 | 0.00 | 0.00 |
September | 906.83 | 0.17 | 906.66 | 974.24 | 635.85 | 0.00 | 0.00 | 0.00 |
October | 784.80 | 0.00 | 784.80 | 577.50 | 1154.12 | 0.00 | 0.00 | 0.00 |
November | 550.46 | 0.00 | 550.46 | 147.95 | 1770.64 | 0.00 | 0.00 | 0.00 |
December | 382.15 | 0.00 | 382.15 | 15.76 | 2337.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 900.28 | 15.59 | 884.69 | 784.06 | 1299.29 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 382.15 | 0.00 | 382.15 | 15.76 | 232.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1405.02 | 75.50 | 1329.53 | 1952.20 | 2590.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 610.12 | 244.61 | 365.51 | 371.60 | 1539.55 | 0.00 | 0.00 | 0.00 |
February | 946.16 | 441.38 | 504.77 | 655.39 | 1559.03 | 0.00 | 0.00 | 0.00 |
March | 1207.00 | 513.35 | 693.66 | 1044.07 | 1121.93 | 0.00 | 0.00 | 0.00 |
April | 1448.49 | 634.48 | 814.00 | 1455.57 | 809.60 | 0.00 | 0.00 | 0.00 |
May | 1756.71 | 702.09 | 1054.62 | 2026.83 | 523.96 | 0.00 | 0.00 | 0.00 |
June | 1628.10 | 589.36 | 1038.74 | 2129.81 | 287.12 | 0.00 | 0.00 | 0.00 |
July | 1635.23 | 590.11 | 1045.11 | 2327.91 | 159.22 | 0.00 | 0.00 | 0.00 |
August | 1841.30 | 830.24 | 1011.06 | 2604.96 | 216.28 | 0.00 | 0.00 | 0.00 |
September | 1373.25 | 616.13 | 757.13 | 1712.60 | 415.98 | 0.00 | 0.00 | 0.00 |
October | 1244.96 | 564.26 | 680.70 | 1376.60 | 755.88 | 0.00 | 0.00 | 0.00 |
November | 769.91 | 295.65 | 474.26 | 611.25 | 1111.20 | 0.00 | 0.00 | 0.00 |
December | 599.80 | 281.63 | 318.17 | 399.59 | 1438.50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1257.08 | 525.87 | 731.21 | 1398.15 | 824.07 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 599.80 | 244.61 | 318.17 | 371.60 | 159.22 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1841.30 | 830.24 | 1054.62 | 2604.96 | 1559.03 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2266.47 | 1484.10 | 782.37 | 2213.12 | 2249.33 | 0.00 | 0.00 | 0.00 |
February | 2989.40 | 1978.74 | 1010.66 | 2961.75 | 2309.82 | 0.00 | 0.00 | 0.00 |
March | 2697.00 | 1496.88 | 1200.12 | 2831.91 | 1735.10 | 0.00 | 0.00 | 0.00 |
April | 2092.78 | 827.55 | 1265.23 | 2270.85 | 1308.95 | 0.00 | 0.00 | 0.00 |
May | 1834.01 | 382.55 | 1451.47 | 2119.98 | 837.65 | 0.00 | 0.00 | 0.00 |
June | 1721.16 | 263.10 | 1458.07 | 2320.01 | 453.92 | 0.00 | 0.00 | 0.00 |
July | 1804.13 | 313.38 | 1490.75 | 2711.43 | 244.28 | 0.00 | 0.00 | 0.00 |
August | 2409.21 | 893.62 | 1515.59 | 3643.16 | 348.63 | 0.00 | 0.00 | 0.00 |
September | 2614.04 | 1352.09 | 1261.95 | 3484.70 | 678.01 | 0.00 | 0.00 | 0.00 |
October | 3581.02 | 2245.55 | 1335.46 | 4430.93 | 1217.18 | 0.00 | 0.00 | 0.00 |
November | 2483.13 | 1491.24 | 991.89 | 2619.50 | 1708.37 | 0.00 | 0.00 | 0.00 |
December | 2456.52 | 1743.96 | 712.55 | 2493.64 | 2115.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2409.69 | 1202.15 | 1207.54 | 2842.60 | 1261.15 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1721.16 | 263.10 | 712.55 | 2119.98 | 244.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3581.02 | 2245.55 | 1515.59 | 4430.93 | 2309.82 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 602.32 | 246.71 | 355.61 | 366.29 | 1612.39 | 0.00 | 0.00 | 0.00 |
February | 888.21 | 390.10 | 498.10 | 600.56 | 1669.19 | 0.00 | 0.00 | 0.00 |
March | 1311.55 | 605.50 | 706.04 | 1166.35 | 1158.34 | 0.00 | 0.00 | 0.00 |
April | 1433.46 | 613.34 | 820.12 | 1448.48 | 870.48 | 0.00 | 0.00 | 0.00 |
May | 1669.83 | 634.14 | 1035.70 | 1927.68 | 565.37 | 0.00 | 0.00 | 0.00 |
June | 1827.58 | 737.12 | 1090.47 | 2398.13 | 322.82 | 0.00 | 0.00 | 0.00 |
July | 1711.63 | 644.55 | 1067.08 | 2421.79 | 186.16 | 0.00 | 0.00 | 0.00 |
August | 1893.53 | 876.58 | 1016.95 | 2682.66 | 251.85 | 0.00 | 0.00 | 0.00 |
September | 1344.25 | 587.44 | 756.82 | 1692.81 | 453.61 | 0.00 | 0.00 | 0.00 |
October | 1332.73 | 648.07 | 684.65 | 1497.31 | 809.59 | 0.00 | 0.00 | 0.00 |
November | 625.84 | 180.87 | 444.97 | 414.83 | 1177.95 | 0.00 | 0.00 | 0.00 |
December | 556.68 | 240.88 | 315.80 | 344.81 | 1526.04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1269.12 | 535.00 | 734.12 | 1419.33 | 879.14 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 556.68 | 180.87 | 315.80 | 344.81 | 186.16 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1893.53 | 876.58 | 1090.47 | 2682.66 | 1669.19 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 438.12 | 0.00 | 438.12 | 30.19 | 2377.85 | 0.00 | 0.00 | 0.00 |
February | 599.54 | 0.00 | 599.54 | 63.78 | 2455.36 | 0.00 | 0.00 | 0.00 |
March | 831.42 | 0.00 | 831.42 | 316.04 | 1603.60 | 0.00 | 0.00 | 0.00 |
April | 998.65 | 2.84 | 995.80 | 657.54 | 1141.86 | 0.00 | 0.00 | 0.00 |
May | 1324.88 | 44.15 | 1280.74 | 1250.03 | 730.29 | 0.00 | 0.00 | 0.00 |
June | 1405.02 | 75.50 | 1329.53 | 1732.71 | 416.41 | 0.00 | 0.00 | 0.00 |
July | 1357.82 | 49.10 | 1308.72 | 1929.15 | 240.63 | 0.00 | 0.00 | 0.00 |
August | 1202.96 | 14.32 | 1188.65 | 1694.99 | 318.39 | 0.00 | 0.00 | 0.00 |
September | 906.83 | 0.17 | 906.66 | 978.76 | 607.22 | 0.00 | 0.00 | 0.00 |
October | 784.80 | 0.00 | 784.80 | 613.29 | 1056.52 | 0.00 | 0.00 | 0.00 |
November | 550.46 | 0.00 | 550.46 | 179.06 | 1607.22 | 0.00 | 0.00 | 0.00 |
December | 382.15 | 0.00 | 382.15 | 25.02 | 2163.84 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 900.28 | 15.59 | 884.69 | 794.10 | 1219.61 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 382.15 | 0.00 | 382.15 | 25.02 | 240.63 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1405.02 | 75.50 | 1329.53 | 1929.15 | 2455.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 610.12 | 244.61 | 365.51 | 379.69 | 1474.15 | 0.00 | 0.00 | 0.00 |
February | 946.16 | 441.38 | 504.77 | 673.00 | 1476.25 | 0.00 | 0.00 | 0.00 |
March | 1207.00 | 513.35 | 693.66 | 1066.43 | 1040.36 | 0.00 | 0.00 | 0.00 |
April | 1448.49 | 634.48 | 814.00 | 1477.32 | 754.14 | 0.00 | 0.00 | 0.00 |
May | 1756.71 | 702.09 | 1054.62 | 2030.82 | 503.33 | 0.00 | 0.00 | 0.00 |
June | 1628.10 | 589.36 | 1038.74 | 2118.64 | 287.32 | 0.00 | 0.00 | 0.00 |
July | 1635.23 | 590.11 | 1045.11 | 2311.75 | 165.30 | 0.00 | 0.00 | 0.00 |
August | 1841.30 | 830.24 | 1011.06 | 2591.52 | 219.04 | 0.00 | 0.00 | 0.00 |
September | 1373.25 | 616.13 | 757.13 | 1712.03 | 402.06 | 0.00 | 0.00 | 0.00 |
October | 1244.96 | 564.26 | 680.70 | 1396.57 | 702.31 | 0.00 | 0.00 | 0.00 |
November | 769.91 | 295.65 | 474.26 | 640.39 | 1013.94 | 0.00 | 0.00 | 0.00 |
December | 599.80 | 281.63 | 318.17 | 416.41 | 1331.04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1257.08 | 525.87 | 731.21 | 1406.26 | 776.88 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 599.80 | 244.61 | 318.17 | 379.69 | 165.30 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1841.30 | 830.24 | 1054.62 | 2591.52 | 1476.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2266.47 | 1484.10 | 782.37 | 2232.79 | 2137.37 | 0.00 | 0.00 | 0.00 |
February | 2989.40 | 1978.74 | 1010.66 | 2998.26 | 2170.53 | 0.00 | 0.00 | 0.00 |
March | 2697.00 | 1496.88 | 1200.12 | 2861.70 | 1602.87 | 0.00 | 0.00 | 0.00 |
April | 2092.78 | 827.55 | 1265.23 | 2300.34 | 1211.82 | 0.00 | 0.00 | 0.00 |
May | 1834.01 | 382.55 | 1451.47 | 2129.47 | 797.47 | 0.00 | 0.00 | 0.00 |
June | 1721.16 | 263.10 | 1458.07 | 2304.93 | 451.08 | 0.00 | 0.00 | 0.00 |
July | 1804.13 | 313.38 | 1490.75 | 2688.25 | 251.93 | 0.00 | 0.00 | 0.00 |
August | 2409.21 | 893.62 | 1515.59 | 3623.24 | 351.88 | 0.00 | 0.00 | 0.00 |
September | 2614.04 | 1352.09 | 1261.95 | 3481.60 | 655.16 | 0.00 | 0.00 | 0.00 |
October | 3581.02 | 2245.55 | 1335.46 | 4449.32 | 1139.02 | 0.00 | 0.00 | 0.00 |
November | 2483.13 | 1491.24 | 991.89 | 2667.27 | 1553.03 | 0.00 | 0.00 | 0.00 |
December | 2456.52 | 1743.96 | 712.55 | 2537.34 | 1945.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2409.69 | 1202.15 | 1207.54 | 2856.88 | 1183.29 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1721.16 | 263.10 | 712.55 | 2129.47 | 251.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3581.02 | 2245.55 | 1515.59 | 4449.32 | 2170.53 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 602.32 | 246.71 | 355.61 | 372.11 | 1541.93 | 0.00 | 0.00 | 0.00 |
February | 888.21 | 390.10 | 498.10 | 609.51 | 1588.99 | 0.00 | 0.00 | 0.00 |
March | 1311.55 | 605.50 | 706.04 | 1181.83 | 1082.19 | 0.00 | 0.00 | 0.00 |
April | 1433.46 | 613.34 | 820.12 | 1464.88 | 813.64 | 0.00 | 0.00 | 0.00 |
May | 1669.83 | 634.14 | 1035.70 | 1932.65 | 542.03 | 0.00 | 0.00 | 0.00 |
June | 1827.58 | 737.12 | 1090.47 | 2386.53 | 321.03 | 0.00 | 0.00 | 0.00 |
July | 1711.63 | 644.55 | 1067.08 | 2406.28 | 189.96 | 0.00 | 0.00 | 0.00 |
August | 1893.53 | 876.58 | 1016.95 | 2670.00 | 253.44 | 0.00 | 0.00 | 0.00 |
September | 1344.25 | 587.44 | 756.82 | 1692.78 | 437.85 | 0.00 | 0.00 | 0.00 |
October | 1332.73 | 648.07 | 684.65 | 1513.04 | 756.70 | 0.00 | 0.00 | 0.00 |
November | 625.84 | 180.87 | 444.97 | 435.14 | 1084.92 | 0.00 | 0.00 | 0.00 |
December | 556.68 | 240.88 | 315.80 | 355.60 | 1422.65 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1269.12 | 535.00 | 734.12 | 1424.17 | 831.97 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 556.68 | 180.87 | 315.80 | 355.60 | 189.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1893.53 | 876.58 | 1090.47 | 2670.00 | 1588.99 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.234690E+09 | 0.00 | 0.234690E+09 | 5092119.17 | 0.149774E+10 |
February | 0.290084E+09 | 0.00 | 0.290084E+09 | 15675961.70 | 0.139973E+10 |
March | 0.445374E+09 | 0.00 | 0.445374E+09 | 0.123986E+09 | 0.106930E+10 |
April | 0.517698E+09 | 1472482.96 | 0.516225E+09 | 0.289831E+09 | 0.737683E+09 |
May | 0.709714E+09 | 23647927.09 | 0.686066E+09 | 0.647813E+09 | 0.438521E+09 |
June | 0.728364E+09 | 39137814.08 | 0.689226E+09 | 0.901954E+09 | 0.225320E+09 |
July | 0.727357E+09 | 26303484.01 | 0.701053E+09 | 0.104314E+10 | 0.123897E+09 |
August | 0.644404E+09 | 7669258.95 | 0.636735E+09 | 0.908855E+09 | 0.170973E+09 |
September | 0.470103E+09 | 88030.64 | 0.470015E+09 | 0.496507E+09 | 0.353948E+09 |
October | 0.420402E+09 | 0.00 | 0.420402E+09 | 0.286681E+09 | 0.689391E+09 |
November | 0.285359E+09 | 0.00 | 0.285359E+09 | 55252258.30 | 0.108151E+10 |
December | 0.204712E+09 | 0.00 | 0.204712E+09 | 2369643.28 | 0.146784E+10 |
Annual Sum or Average | 0.567826E+10 | 98318997.72 | 0.557994E+10 | 0.477715E+10 | 0.925585E+10 |
Minimum of Months | 0.204712E+09 | 0.00 | 0.204712E+09 | 2369643.28 | 0.123897E+09 |
Maximum of Months | 0.728364E+09 | 39137814.08 | 0.701053E+09 | 0.104314E+10 | 0.149774E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.234687E+09 | 0.00 | 0.234687E+09 | 5091374.01 | 0.149774E+10 |
February | 0.290079E+09 | 0.00 | 0.290079E+09 | 15674869.74 | 0.139973E+10 |
March | 0.445367E+09 | 0.00 | 0.445367E+09 | 0.123981E+09 | 0.106930E+10 |
April | 0.517691E+09 | 1472450.59 | 0.516218E+09 | 0.289824E+09 | 0.737684E+09 |
May | 0.709704E+09 | 23647407.21 | 0.686056E+09 | 0.647800E+09 | 0.438520E+09 |
June | 0.728354E+09 | 39136953.68 | 0.689217E+09 | 0.901940E+09 | 0.225319E+09 |
July | 0.727346E+09 | 26302905.75 | 0.701043E+09 | 0.104312E+10 | 0.123896E+09 |
August | 0.644396E+09 | 7669090.35 | 0.636726E+09 | 0.908845E+09 | 0.170972E+09 |
September | 0.470097E+09 | 88028.70 | 0.470009E+09 | 0.496499E+09 | 0.353946E+09 |
October | 0.420396E+09 | 0.00 | 0.420396E+09 | 0.286675E+09 | 0.689390E+09 |
November | 0.285355E+09 | 0.00 | 0.285355E+09 | 55249775.91 | 0.108151E+10 |
December | 0.204709E+09 | 0.00 | 0.204709E+09 | 2369319.48 | 0.146784E+10 |
Annual Sum or Average | 0.567818E+10 | 98316836.30 | 0.557986E+10 | 0.477707E+10 | 0.925585E+10 |
Minimum of Months | 0.204709E+09 | 0.00 | 0.204709E+09 | 2369319.48 | 0.123896E+09 |
Maximum of Months | 0.728354E+09 | 39136953.68 | 0.701043E+09 | 0.104312E+10 | 0.149774E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.234688E+09 | 0.00 | 0.234688E+09 | 5091622.40 | 0.149774E+10 |
February | 0.290081E+09 | 0.00 | 0.290081E+09 | 15675233.73 | 0.139973E+10 |
March | 0.445369E+09 | 0.00 | 0.445369E+09 | 0.123983E+09 | 0.106930E+10 |
April | 0.517693E+09 | 1472461.38 | 0.516221E+09 | 0.289827E+09 | 0.737684E+09 |
May | 0.709707E+09 | 23647580.50 | 0.686060E+09 | 0.647804E+09 | 0.438520E+09 |
June | 0.728357E+09 | 39137240.48 | 0.689220E+09 | 0.901945E+09 | 0.225320E+09 |
July | 0.727350E+09 | 26303098.50 | 0.701047E+09 | 0.104313E+10 | 0.123897E+09 |
August | 0.644398E+09 | 7669146.55 | 0.636729E+09 | 0.908848E+09 | 0.170972E+09 |
September | 0.470099E+09 | 88029.35 | 0.470011E+09 | 0.496502E+09 | 0.353947E+09 |
October | 0.420398E+09 | 0.00 | 0.420398E+09 | 0.286677E+09 | 0.689390E+09 |
November | 0.285356E+09 | 0.00 | 0.285356E+09 | 55250603.38 | 0.108151E+10 |
December | 0.204710E+09 | 0.00 | 0.204710E+09 | 2369427.41 | 0.146784E+10 |
Annual Sum or Average | 0.567821E+10 | 98317556.77 | 0.557989E+10 | 0.477710E+10 | 0.925585E+10 |
Minimum of Months | 0.204710E+09 | 0.00 | 0.204710E+09 | 2369427.41 | 0.123897E+09 |
Maximum of Months | 0.728357E+09 | 39137240.48 | 0.701047E+09 | 0.104313E+10 | 0.149774E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.234687E+09 | 0.00 | 0.234687E+09 | 5091374.01 | 0.149774E+10 |
February | 0.290079E+09 | 0.00 | 0.290079E+09 | 15674869.74 | 0.139973E+10 |
March | 0.445367E+09 | 0.00 | 0.445367E+09 | 0.123981E+09 | 0.106930E+10 |
April | 0.517691E+09 | 1472450.59 | 0.516218E+09 | 0.289824E+09 | 0.737684E+09 |
May | 0.709704E+09 | 23647407.21 | 0.686056E+09 | 0.647800E+09 | 0.438520E+09 |
June | 0.728354E+09 | 39136953.68 | 0.689217E+09 | 0.901940E+09 | 0.225319E+09 |
July | 0.727346E+09 | 26302905.75 | 0.701043E+09 | 0.104312E+10 | 0.123896E+09 |
August | 0.644396E+09 | 7669090.35 | 0.636726E+09 | 0.908845E+09 | 0.170972E+09 |
September | 0.470097E+09 | 88028.70 | 0.470009E+09 | 0.496499E+09 | 0.353946E+09 |
October | 0.420396E+09 | 0.00 | 0.420396E+09 | 0.286675E+09 | 0.689390E+09 |
November | 0.285355E+09 | 0.00 | 0.285355E+09 | 55249775.91 | 0.108151E+10 |
December | 0.204709E+09 | 0.00 | 0.204709E+09 | 2369319.48 | 0.146784E+10 |
Annual Sum or Average | 0.567818E+10 | 98316836.30 | 0.557986E+10 | 0.477707E+10 | 0.925585E+10 |
Minimum of Months | 0.204709E+09 | 0.00 | 0.204709E+09 | 2369319.48 | 0.123896E+09 |
Maximum of Months | 0.728354E+09 | 39136953.68 | 0.701043E+09 | 0.104312E+10 | 0.149774E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.234678E+09 | 0.00 | 0.234678E+09 | 5091292.99 | 0.149768E+10 |
February | 0.290068E+09 | 0.00 | 0.290068E+09 | 15674419.96 | 0.139967E+10 |
March | 0.445350E+09 | 0.00 | 0.445350E+09 | 0.123977E+09 | 0.106925E+10 |
April | 0.517671E+09 | 1472396.64 | 0.516199E+09 | 0.289814E+09 | 0.737654E+09 |
May | 0.709677E+09 | 23646540.76 | 0.686030E+09 | 0.647776E+09 | 0.438503E+09 |
June | 0.728326E+09 | 39135519.68 | 0.689191E+09 | 0.901906E+09 | 0.225310E+09 |
July | 0.727319E+09 | 26301942.00 | 0.701017E+09 | 0.104308E+10 | 0.123892E+09 |
August | 0.644371E+09 | 7668809.36 | 0.636702E+09 | 0.908810E+09 | 0.170965E+09 |
September | 0.470079E+09 | 88025.48 | 0.469991E+09 | 0.496480E+09 | 0.353932E+09 |
October | 0.420380E+09 | 0.00 | 0.420380E+09 | 0.286664E+09 | 0.689362E+09 |
November | 0.285344E+09 | 0.00 | 0.285344E+09 | 55247962.82 | 0.108147E+10 |
December | 0.204702E+09 | 0.00 | 0.204702E+09 | 2369277.95 | 0.146778E+10 |
Annual Sum or Average | 0.567796E+10 | 98313233.92 | 0.557965E+10 | 0.477689E+10 | 0.925547E+10 |
Minimum of Months | 0.204702E+09 | 0.00 | 0.204702E+09 | 2369277.95 | 0.123892E+09 |
Maximum of Months | 0.728326E+09 | 39135519.68 | 0.701017E+09 | 0.104308E+10 | 0.149768E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.544717E+09 | 0.218387E+09 | 0.326329E+09 | 0.311289E+09 | 0.153192E+10 |
February | 0.762989E+09 | 0.355935E+09 | 0.407054E+09 | 0.505692E+09 | 0.138309E+10 |
March | 0.107762E+10 | 0.458320E+09 | 0.619302E+09 | 0.910693E+09 | 0.110950E+10 |
April | 0.125150E+10 | 0.548198E+09 | 0.703307E+09 | 0.124591E+10 | 0.758268E+09 |
May | 0.156841E+10 | 0.626830E+09 | 0.941577E+09 | 0.181398E+10 | 0.489163E+09 |
June | 0.140669E+10 | 0.509212E+09 | 0.897479E+09 | 0.185275E+10 | 0.246966E+09 |
July | 0.145994E+10 | 0.526858E+09 | 0.933087E+09 | 0.209496E+10 | 0.126768E+09 |
August | 0.164393E+10 | 0.741250E+09 | 0.902684E+09 | 0.234353E+10 | 0.174352E+09 |
September | 0.118650E+10 | 0.532338E+09 | 0.654166E+09 | 0.148468E+10 | 0.373949E+09 |
October | 0.111151E+10 | 0.503774E+09 | 0.607735E+09 | 0.122058E+10 | 0.724211E+09 |
November | 0.665209E+09 | 0.255447E+09 | 0.409762E+09 | 0.501270E+09 | 0.108926E+10 |
December | 0.535510E+09 | 0.251443E+09 | 0.284067E+09 | 0.335945E+09 | 0.145263E+10 |
Annual Sum or Average | 0.132145E+11 | 0.552799E+10 | 0.768655E+10 | 0.146213E+11 | 0.946007E+10 |
Minimum of Months | 0.535510E+09 | 0.218387E+09 | 0.284067E+09 | 0.311289E+09 | 0.126768E+09 |
Maximum of Months | 0.164393E+10 | 0.741250E+09 | 0.941577E+09 | 0.234353E+10 | 0.153192E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.544717E+09 | 0.218387E+09 | 0.326329E+09 | 0.311289E+09 | 0.153192E+10 |
February | 0.762989E+09 | 0.355935E+09 | 0.407054E+09 | 0.505692E+09 | 0.138309E+10 |
March | 0.107762E+10 | 0.458320E+09 | 0.619302E+09 | 0.910693E+09 | 0.110950E+10 |
April | 0.125150E+10 | 0.548198E+09 | 0.703307E+09 | 0.124591E+10 | 0.758268E+09 |
May | 0.156841E+10 | 0.626830E+09 | 0.941577E+09 | 0.181398E+10 | 0.489163E+09 |
June | 0.140669E+10 | 0.509212E+09 | 0.897479E+09 | 0.185275E+10 | 0.246966E+09 |
July | 0.145994E+10 | 0.526858E+09 | 0.933087E+09 | 0.209496E+10 | 0.126768E+09 |
August | 0.164393E+10 | 0.741250E+09 | 0.902684E+09 | 0.234353E+10 | 0.174352E+09 |
September | 0.118650E+10 | 0.532338E+09 | 0.654166E+09 | 0.148468E+10 | 0.373949E+09 |
October | 0.111151E+10 | 0.503774E+09 | 0.607735E+09 | 0.122058E+10 | 0.724211E+09 |
November | 0.665209E+09 | 0.255447E+09 | 0.409762E+09 | 0.501270E+09 | 0.108926E+10 |
December | 0.535510E+09 | 0.251443E+09 | 0.284067E+09 | 0.335945E+09 | 0.145263E+10 |
Annual Sum or Average | 0.132145E+11 | 0.552799E+10 | 0.768655E+10 | 0.146213E+11 | 0.946007E+10 |
Minimum of Months | 0.535510E+09 | 0.218387E+09 | 0.284067E+09 | 0.311289E+09 | 0.126768E+09 |
Maximum of Months | 0.164393E+10 | 0.741250E+09 | 0.941577E+09 | 0.234353E+10 | 0.153192E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.544707E+09 | 0.218383E+09 | 0.326323E+09 | 0.311283E+09 | 0.153189E+10 |
February | 0.762975E+09 | 0.355928E+09 | 0.407047E+09 | 0.505682E+09 | 0.138307E+10 |
March | 0.107760E+10 | 0.458312E+09 | 0.619291E+09 | 0.910676E+09 | 0.110948E+10 |
April | 0.125148E+10 | 0.548188E+09 | 0.703294E+09 | 0.124588E+10 | 0.758254E+09 |
May | 0.156838E+10 | 0.626818E+09 | 0.941560E+09 | 0.181394E+10 | 0.489155E+09 |
June | 0.140667E+10 | 0.509203E+09 | 0.897462E+09 | 0.185272E+10 | 0.246961E+09 |
July | 0.145992E+10 | 0.526848E+09 | 0.933070E+09 | 0.209492E+10 | 0.126765E+09 |
August | 0.164390E+10 | 0.741236E+09 | 0.902667E+09 | 0.234349E+10 | 0.174349E+09 |
September | 0.118648E+10 | 0.532328E+09 | 0.654154E+09 | 0.148465E+10 | 0.373942E+09 |
October | 0.111149E+10 | 0.503764E+09 | 0.607724E+09 | 0.122056E+10 | 0.724198E+09 |
November | 0.665196E+09 | 0.255442E+09 | 0.409754E+09 | 0.501260E+09 | 0.108924E+10 |
December | 0.535500E+09 | 0.251438E+09 | 0.284062E+09 | 0.335939E+09 | 0.145260E+10 |
Annual Sum or Average | 0.132143E+11 | 0.552789E+10 | 0.768641E+10 | 0.146210E+11 | 0.945990E+10 |
Minimum of Months | 0.535500E+09 | 0.218383E+09 | 0.284062E+09 | 0.311283E+09 | 0.126765E+09 |
Maximum of Months | 0.164390E+10 | 0.741236E+09 | 0.941560E+09 | 0.234349E+10 | 0.153189E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.121408E+10 | 0.794987E+09 | 0.419094E+09 | 0.117760E+10 | 0.128765E+10 |
February | 0.144636E+10 | 0.957373E+09 | 0.488991E+09 | 0.142849E+10 | 0.117903E+10 |
March | 0.144471E+10 | 0.801834E+09 | 0.642872E+09 | 0.151624E+10 | 0.991738E+09 |
April | 0.108488E+10 | 0.428992E+09 | 0.655888E+09 | 0.117306E+10 | 0.726409E+09 |
May | 0.982430E+09 | 0.204918E+09 | 0.777512E+09 | 0.113895E+10 | 0.464876E+09 |
June | 0.892241E+09 | 0.136387E+09 | 0.755854E+09 | 0.120672E+10 | 0.241303E+09 |
July | 0.966422E+09 | 0.167866E+09 | 0.798556E+09 | 0.145616E+10 | 0.129354E+09 |
August | 0.129055E+10 | 0.478682E+09 | 0.811865E+09 | 0.195725E+10 | 0.184672E+09 |
September | 0.135510E+10 | 0.700908E+09 | 0.654188E+09 | 0.181604E+10 | 0.360144E+09 |
October | 0.191824E+10 | 0.120287E+10 | 0.715370E+09 | 0.238767E+10 | 0.671884E+09 |
November | 0.128723E+10 | 0.773041E+09 | 0.514188E+09 | 0.135096E+10 | 0.952635E+09 |
December | 0.131588E+10 | 0.934186E+09 | 0.381695E+09 | 0.132661E+10 | 0.122425E+10 |
Annual Sum or Average | 0.151981E+11 | 0.758205E+10 | 0.761607E+10 | 0.179357E+11 | 0.841394E+10 |
Minimum of Months | 0.892241E+09 | 0.136387E+09 | 0.381695E+09 | 0.113895E+10 | 0.129354E+09 |
Maximum of Months | 0.191824E+10 | 0.120287E+10 | 0.811865E+09 | 0.238767E+10 | 0.128765E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.121407E+10 | 0.794981E+09 | 0.419092E+09 | 0.117758E+10 | 0.128765E+10 |
February | 0.144635E+10 | 0.957366E+09 | 0.488988E+09 | 0.142848E+10 | 0.117903E+10 |
March | 0.144470E+10 | 0.801828E+09 | 0.642868E+09 | 0.151622E+10 | 0.991738E+09 |
April | 0.108487E+10 | 0.428989E+09 | 0.655885E+09 | 0.117305E+10 | 0.726409E+09 |
May | 0.982425E+09 | 0.204916E+09 | 0.777508E+09 | 0.113894E+10 | 0.464875E+09 |
June | 0.892236E+09 | 0.136386E+09 | 0.755850E+09 | 0.120671E+10 | 0.241303E+09 |
July | 0.966416E+09 | 0.167865E+09 | 0.798552E+09 | 0.145615E+10 | 0.129353E+09 |
August | 0.129054E+10 | 0.478679E+09 | 0.811861E+09 | 0.195724E+10 | 0.184672E+09 |
September | 0.135509E+10 | 0.700903E+09 | 0.654185E+09 | 0.181602E+10 | 0.360143E+09 |
October | 0.191823E+10 | 0.120286E+10 | 0.715366E+09 | 0.238765E+10 | 0.671883E+09 |
November | 0.128722E+10 | 0.773035E+09 | 0.514185E+09 | 0.135095E+10 | 0.952635E+09 |
December | 0.131587E+10 | 0.934180E+09 | 0.381693E+09 | 0.132660E+10 | 0.122425E+10 |
Annual Sum or Average | 0.151980E+11 | 0.758199E+10 | 0.761603E+10 | 0.179356E+11 | 0.841393E+10 |
Minimum of Months | 0.892236E+09 | 0.136386E+09 | 0.381693E+09 | 0.113894E+10 | 0.129353E+09 |
Maximum of Months | 0.191823E+10 | 0.120286E+10 | 0.811861E+09 | 0.238765E+10 | 0.128765E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.121408E+10 | 0.794987E+09 | 0.419094E+09 | 0.117760E+10 | 0.128765E+10 |
February | 0.144636E+10 | 0.957373E+09 | 0.488991E+09 | 0.142849E+10 | 0.117903E+10 |
March | 0.144471E+10 | 0.801834E+09 | 0.642872E+09 | 0.151624E+10 | 0.991738E+09 |
April | 0.108488E+10 | 0.428992E+09 | 0.655888E+09 | 0.117306E+10 | 0.726409E+09 |
May | 0.982430E+09 | 0.204918E+09 | 0.777512E+09 | 0.113895E+10 | 0.464876E+09 |
June | 0.892241E+09 | 0.136387E+09 | 0.755854E+09 | 0.120672E+10 | 0.241303E+09 |
July | 0.966422E+09 | 0.167866E+09 | 0.798556E+09 | 0.145616E+10 | 0.129354E+09 |
August | 0.129055E+10 | 0.478682E+09 | 0.811865E+09 | 0.195725E+10 | 0.184672E+09 |
September | 0.135510E+10 | 0.700908E+09 | 0.654188E+09 | 0.181604E+10 | 0.360144E+09 |
October | 0.191824E+10 | 0.120287E+10 | 0.715370E+09 | 0.238767E+10 | 0.671884E+09 |
November | 0.128723E+10 | 0.773041E+09 | 0.514188E+09 | 0.135096E+10 | 0.952635E+09 |
December | 0.131588E+10 | 0.934186E+09 | 0.381695E+09 | 0.132661E+10 | 0.122425E+10 |
Annual Sum or Average | 0.151981E+11 | 0.758205E+10 | 0.761607E+10 | 0.179357E+11 | 0.841394E+10 |
Minimum of Months | 0.892241E+09 | 0.136387E+09 | 0.381695E+09 | 0.113895E+10 | 0.129354E+09 |
Maximum of Months | 0.191824E+10 | 0.120287E+10 | 0.811865E+09 | 0.238767E+10 | 0.128765E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.121407E+10 | 0.794981E+09 | 0.419092E+09 | 0.117758E+10 | 0.128765E+10 |
February | 0.144635E+10 | 0.957366E+09 | 0.488988E+09 | 0.142848E+10 | 0.117903E+10 |
March | 0.144470E+10 | 0.801828E+09 | 0.642868E+09 | 0.151622E+10 | 0.991738E+09 |
April | 0.108487E+10 | 0.428989E+09 | 0.655885E+09 | 0.117305E+10 | 0.726409E+09 |
May | 0.982425E+09 | 0.204916E+09 | 0.777508E+09 | 0.113894E+10 | 0.464875E+09 |
June | 0.892236E+09 | 0.136386E+09 | 0.755850E+09 | 0.120671E+10 | 0.241303E+09 |
July | 0.966416E+09 | 0.167865E+09 | 0.798552E+09 | 0.145615E+10 | 0.129353E+09 |
August | 0.129054E+10 | 0.478679E+09 | 0.811861E+09 | 0.195724E+10 | 0.184672E+09 |
September | 0.135509E+10 | 0.700903E+09 | 0.654185E+09 | 0.181602E+10 | 0.360143E+09 |
October | 0.191823E+10 | 0.120286E+10 | 0.715366E+09 | 0.238765E+10 | 0.671883E+09 |
November | 0.128722E+10 | 0.773035E+09 | 0.514185E+09 | 0.135095E+10 | 0.952635E+09 |
December | 0.131587E+10 | 0.934180E+09 | 0.381693E+09 | 0.132660E+10 | 0.122425E+10 |
Annual Sum or Average | 0.151980E+11 | 0.758199E+10 | 0.761603E+10 | 0.179356E+11 | 0.841393E+10 |
Minimum of Months | 0.892236E+09 | 0.136386E+09 | 0.381693E+09 | 0.113894E+10 | 0.129353E+09 |
Maximum of Months | 0.191823E+10 | 0.120286E+10 | 0.811861E+09 | 0.238765E+10 | 0.128765E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.121403E+10 | 0.794952E+09 | 0.419076E+09 | 0.117754E+10 | 0.128760E+10 |
February | 0.144630E+10 | 0.957331E+09 | 0.488970E+09 | 0.142843E+10 | 0.117898E+10 |
March | 0.144464E+10 | 0.801799E+09 | 0.642844E+09 | 0.151617E+10 | 0.991698E+09 |
April | 0.108483E+10 | 0.428973E+09 | 0.655860E+09 | 0.117301E+10 | 0.726379E+09 |
May | 0.982388E+09 | 0.204909E+09 | 0.777479E+09 | 0.113890E+10 | 0.464857E+09 |
June | 0.892203E+09 | 0.136381E+09 | 0.755822E+09 | 0.120667E+10 | 0.241293E+09 |
July | 0.966380E+09 | 0.167858E+09 | 0.798522E+09 | 0.145609E+10 | 0.129348E+09 |
August | 0.129049E+10 | 0.478661E+09 | 0.811830E+09 | 0.195717E+10 | 0.184665E+09 |
September | 0.135504E+10 | 0.700878E+09 | 0.654160E+09 | 0.181596E+10 | 0.360129E+09 |
October | 0.191816E+10 | 0.120282E+10 | 0.715339E+09 | 0.238757E+10 | 0.671856E+09 |
November | 0.128717E+10 | 0.773007E+09 | 0.514166E+09 | 0.135090E+10 | 0.952597E+09 |
December | 0.131582E+10 | 0.934145E+09 | 0.381678E+09 | 0.132655E+10 | 0.122420E+10 |
Annual Sum or Average | 0.151975E+11 | 0.758171E+10 | 0.761575E+10 | 0.179350E+11 | 0.841360E+10 |
Minimum of Months | 0.892203E+09 | 0.136381E+09 | 0.381678E+09 | 0.113890E+10 | 0.129348E+09 |
Maximum of Months | 0.191816E+10 | 0.120282E+10 | 0.811830E+09 | 0.238757E+10 | 0.128760E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.537757E+09 | 0.220267E+09 | 0.317490E+09 | 0.305529E+09 | 0.165087E+10 |
February | 0.716257E+09 | 0.314583E+09 | 0.401674E+09 | 0.455392E+09 | 0.155298E+10 |
March | 0.117096E+10 | 0.540600E+09 | 0.630360E+09 | 0.991099E+09 | 0.124879E+10 |
April | 0.123852E+10 | 0.529931E+09 | 0.708590E+09 | 0.119832E+10 | 0.922102E+09 |
May | 0.149084E+10 | 0.566164E+09 | 0.924679E+09 | 0.170390E+10 | 0.553541E+09 |
June | 0.157905E+10 | 0.636875E+09 | 0.942173E+09 | 0.206054E+10 | 0.311324E+09 |
July | 0.152816E+10 | 0.575458E+09 | 0.952701E+09 | 0.214146E+10 | 0.192581E+09 |
August | 0.169056E+10 | 0.782618E+09 | 0.907941E+09 | 0.236664E+10 | 0.265030E+09 |
September | 0.116145E+10 | 0.507550E+09 | 0.653898E+09 | 0.144926E+10 | 0.436678E+09 |
October | 0.118987E+10 | 0.578606E+09 | 0.611266E+09 | 0.130560E+10 | 0.831210E+09 |
November | 0.540735E+09 | 0.156276E+09 | 0.384459E+09 | 0.314726E+09 | 0.127402E+10 |
December | 0.497005E+09 | 0.215056E+09 | 0.281950E+09 | 0.271319E+09 | 0.171194E+10 |
Annual Sum or Average | 0.133412E+11 | 0.562398E+10 | 0.771718E+10 | 0.145638E+11 | 0.109511E+11 |
Minimum of Months | 0.497005E+09 | 0.156276E+09 | 0.281950E+09 | 0.271319E+09 | 0.192581E+09 |
Maximum of Months | 0.169056E+10 | 0.782618E+09 | 0.952701E+09 | 0.236664E+10 | 0.171194E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.537757E+09 | 0.220267E+09 | 0.317490E+09 | 0.305529E+09 | 0.165087E+10 |
February | 0.716257E+09 | 0.314583E+09 | 0.401674E+09 | 0.455392E+09 | 0.155298E+10 |
March | 0.117096E+10 | 0.540600E+09 | 0.630360E+09 | 0.991099E+09 | 0.124879E+10 |
April | 0.123852E+10 | 0.529931E+09 | 0.708590E+09 | 0.119832E+10 | 0.922102E+09 |
May | 0.149084E+10 | 0.566164E+09 | 0.924679E+09 | 0.170390E+10 | 0.553541E+09 |
June | 0.157905E+10 | 0.636875E+09 | 0.942173E+09 | 0.206054E+10 | 0.311324E+09 |
July | 0.152816E+10 | 0.575458E+09 | 0.952701E+09 | 0.214146E+10 | 0.192581E+09 |
August | 0.169056E+10 | 0.782618E+09 | 0.907941E+09 | 0.236664E+10 | 0.265030E+09 |
September | 0.116145E+10 | 0.507550E+09 | 0.653898E+09 | 0.144926E+10 | 0.436678E+09 |
October | 0.118987E+10 | 0.578606E+09 | 0.611266E+09 | 0.130560E+10 | 0.831210E+09 |
November | 0.540735E+09 | 0.156276E+09 | 0.384459E+09 | 0.314726E+09 | 0.127402E+10 |
December | 0.497005E+09 | 0.215056E+09 | 0.281950E+09 | 0.271319E+09 | 0.171194E+10 |
Annual Sum or Average | 0.133412E+11 | 0.562398E+10 | 0.771718E+10 | 0.145638E+11 | 0.109511E+11 |
Minimum of Months | 0.497005E+09 | 0.156276E+09 | 0.281950E+09 | 0.271319E+09 | 0.192581E+09 |
Maximum of Months | 0.169056E+10 | 0.782618E+09 | 0.952701E+09 | 0.236664E+10 | 0.171194E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.537747E+09 | 0.220263E+09 | 0.317484E+09 | 0.305523E+09 | 0.165084E+10 |
February | 0.716244E+09 | 0.314577E+09 | 0.401667E+09 | 0.455384E+09 | 0.155295E+10 |
March | 0.117094E+10 | 0.540590E+09 | 0.630348E+09 | 0.991081E+09 | 0.124877E+10 |
April | 0.123850E+10 | 0.529922E+09 | 0.708577E+09 | 0.119830E+10 | 0.922086E+09 |
May | 0.149082E+10 | 0.566154E+09 | 0.924662E+09 | 0.170387E+10 | 0.553531E+09 |
June | 0.157902E+10 | 0.636864E+09 | 0.942155E+09 | 0.206051E+10 | 0.311318E+09 |
July | 0.152813E+10 | 0.575447E+09 | 0.952684E+09 | 0.214142E+10 | 0.192578E+09 |
August | 0.169053E+10 | 0.782604E+09 | 0.907925E+09 | 0.236660E+10 | 0.265025E+09 |
September | 0.116143E+10 | 0.507541E+09 | 0.653886E+09 | 0.144923E+10 | 0.436670E+09 |
October | 0.118985E+10 | 0.578595E+09 | 0.611255E+09 | 0.130558E+10 | 0.831195E+09 |
November | 0.540725E+09 | 0.156273E+09 | 0.384452E+09 | 0.314721E+09 | 0.127399E+10 |
December | 0.496996E+09 | 0.215052E+09 | 0.281944E+09 | 0.271314E+09 | 0.171191E+10 |
Annual Sum or Average | 0.133409E+11 | 0.562388E+10 | 0.771704E+10 | 0.145635E+11 | 0.109509E+11 |
Minimum of Months | 0.496996E+09 | 0.156273E+09 | 0.281944E+09 | 0.271314E+09 | 0.192578E+09 |
Maximum of Months | 0.169053E+10 | 0.782604E+09 | 0.952684E+09 | 0.236660E+10 | 0.171191E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.117345E+10 | 0.00 | 0.117345E+10 | 67923433.42 | 0.664763E+10 |
February | 0.145042E+10 | 0.00 | 0.145042E+10 | 0.127786E+09 | 0.626614E+10 |
March | 0.222687E+10 | 0.00 | 0.222687E+10 | 0.779424E+09 | 0.464515E+10 |
April | 0.258849E+10 | 7362461.72 | 0.258113E+10 | 0.161335E+10 | 0.321672E+10 |
May | 0.354857E+10 | 0.118240E+09 | 0.343033E+10 | 0.330411E+10 | 0.205643E+10 |
June | 0.364182E+10 | 0.195690E+09 | 0.344613E+10 | 0.452610E+10 | 0.108499E+10 |
July | 0.363678E+10 | 0.131518E+09 | 0.350527E+10 | 0.522878E+10 | 0.622554E+09 |
August | 0.322202E+10 | 38346539.14 | 0.318367E+10 | 0.458080E+10 | 0.846226E+09 |
September | 0.235051E+10 | 440156.01 | 0.235007E+10 | 0.252522E+10 | 0.164813E+10 |
October | 0.210201E+10 | 0.00 | 0.210201E+10 | 0.154679E+10 | 0.309120E+10 |
November | 0.142680E+10 | 0.00 | 0.142680E+10 | 0.383484E+09 | 0.458951E+10 |
December | 0.102356E+10 | 0.00 | 0.102356E+10 | 42209004.86 | 0.625982E+10 |
Annual Sum or Average | 0.283913E+11 | 0.491598E+09 | 0.278997E+11 | 0.247260E+11 | 0.409745E+11 |
Minimum of Months | 0.102356E+10 | 0.00 | 0.102356E+10 | 42209004.86 | 0.622554E+09 |
Maximum of Months | 0.364182E+10 | 0.195690E+09 | 0.350527E+10 | 0.522878E+10 | 0.664763E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163413E+10 | 0.655155E+09 | 0.978978E+09 | 0.995293E+09 | 0.412353E+10 |
February | 0.228894E+10 | 0.106779E+10 | 0.122115E+10 | 0.158552E+10 | 0.377161E+10 |
March | 0.323283E+10 | 0.137495E+10 | 0.185789E+10 | 0.279643E+10 | 0.300498E+10 |
April | 0.375448E+10 | 0.164458E+10 | 0.210990E+10 | 0.377284E+10 | 0.209849E+10 |
May | 0.470517E+10 | 0.188047E+10 | 0.282470E+10 | 0.542867E+10 | 0.140337E+10 |
June | 0.422003E+10 | 0.152762E+10 | 0.269241E+10 | 0.552048E+10 | 0.744209E+09 |
July | 0.437979E+10 | 0.158056E+10 | 0.279923E+10 | 0.623507E+10 | 0.426451E+09 |
August | 0.493175E+10 | 0.222373E+10 | 0.270802E+10 | 0.697712E+10 | 0.579282E+09 |
September | 0.355948E+10 | 0.159700E+10 | 0.196248E+10 | 0.443907E+10 | 0.107822E+10 |
October | 0.333449E+10 | 0.151131E+10 | 0.182319E+10 | 0.368710E+10 | 0.202454E+10 |
November | 0.199561E+10 | 0.766333E+09 | 0.122927E+10 | 0.158436E+10 | 0.288022E+10 |
December | 0.160651E+10 | 0.754320E+09 | 0.852193E+09 | 0.107026E+10 | 0.385287E+10 |
Annual Sum or Average | 0.396432E+11 | 0.165838E+11 | 0.230594E+11 | 0.440922E+11 | 0.259878E+11 |
Minimum of Months | 0.160651E+10 | 0.655155E+09 | 0.852193E+09 | 0.995293E+09 | 0.426451E+09 |
Maximum of Months | 0.493175E+10 | 0.222373E+10 | 0.282470E+10 | 0.697712E+10 | 0.412353E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.607052E+10 | 0.397502E+10 | 0.209550E+10 | 0.592763E+10 | 0.602459E+10 |
February | 0.723196E+10 | 0.478697E+10 | 0.244499E+10 | 0.716508E+10 | 0.558791E+10 |
March | 0.722365E+10 | 0.400925E+10 | 0.321440E+10 | 0.758500E+10 | 0.464729E+10 |
April | 0.542448E+10 | 0.214500E+10 | 0.327948E+10 | 0.588605E+10 | 0.339279E+10 |
May | 0.491221E+10 | 0.102461E+10 | 0.388760E+10 | 0.567815E+10 | 0.224355E+10 |
June | 0.446126E+10 | 0.681949E+09 | 0.377931E+10 | 0.601347E+10 | 0.117655E+10 |
July | 0.483217E+10 | 0.839346E+09 | 0.399282E+10 | 0.726228E+10 | 0.654267E+09 |
August | 0.645283E+10 | 0.239346E+10 | 0.405937E+10 | 0.975784E+10 | 0.933769E+09 |
September | 0.677560E+10 | 0.350462E+10 | 0.327098E+10 | 0.903235E+10 | 0.175741E+10 |
October | 0.959139E+10 | 0.601449E+10 | 0.357690E+10 | 0.118678E+11 | 0.326009E+10 |
November | 0.643627E+10 | 0.386529E+10 | 0.257098E+10 | 0.678975E+10 | 0.442809E+10 |
December | 0.657953E+10 | 0.467103E+10 | 0.190850E+10 | 0.667897E+10 | 0.566544E+10 |
Annual Sum or Average | 0.759919E+11 | 0.379110E+11 | 0.380808E+11 | 0.896444E+11 | 0.397718E+11 |
Minimum of Months | 0.446126E+10 | 0.681949E+09 | 0.190850E+10 | 0.567815E+10 | 0.654267E+09 |
Maximum of Months | 0.959139E+10 | 0.601449E+10 | 0.405937E+10 | 0.118678E+11 | 0.602459E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.161325E+10 | 0.660794E+09 | 0.952460E+09 | 0.981058E+09 | 0.431862E+10 |
February | 0.214875E+10 | 0.943739E+09 | 0.120501E+10 | 0.145286E+10 | 0.403810E+10 |
March | 0.351285E+10 | 0.162178E+10 | 0.189106E+10 | 0.312394E+10 | 0.310251E+10 |
April | 0.371553E+10 | 0.158978E+10 | 0.212575E+10 | 0.375447E+10 | 0.225629E+10 |
May | 0.447248E+10 | 0.169848E+10 | 0.277401E+10 | 0.516310E+10 | 0.151428E+10 |
June | 0.473710E+10 | 0.191061E+10 | 0.282649E+10 | 0.621595E+10 | 0.836751E+09 |
July | 0.458443E+10 | 0.172636E+10 | 0.285807E+10 | 0.648653E+10 | 0.498604E+09 |
August | 0.507163E+10 | 0.234783E+10 | 0.272380E+10 | 0.718523E+10 | 0.674563E+09 |
September | 0.348431E+10 | 0.152263E+10 | 0.196167E+10 | 0.438777E+10 | 0.117576E+10 |
October | 0.356958E+10 | 0.173580E+10 | 0.183378E+10 | 0.401039E+10 | 0.216842E+10 |
November | 0.162219E+10 | 0.468824E+09 | 0.115336E+10 | 0.107523E+10 | 0.305325E+10 |
December | 0.149100E+10 | 0.645160E+09 | 0.845840E+09 | 0.923540E+09 | 0.408734E+10 |
Annual Sum or Average | 0.400231E+11 | 0.168718E+11 | 0.231513E+11 | 0.447601E+11 | 0.277245E+11 |
Minimum of Months | 0.149100E+10 | 0.468824E+09 | 0.845840E+09 | 0.923540E+09 | 0.498604E+09 |
Maximum of Months | 0.507163E+10 | 0.234783E+10 | 0.285807E+10 | 0.718523E+10 | 0.431862E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.117345E+10 | 0.00 | 0.117345E+10 | 80854585.16 | 0.636884E+10 |
February | 0.145042E+10 | 0.00 | 0.145042E+10 | 0.154306E+09 | 0.594000E+10 |
March | 0.222687E+10 | 0.00 | 0.222687E+10 | 0.846491E+09 | 0.429507E+10 |
April | 0.258849E+10 | 7362461.72 | 0.258113E+10 | 0.170435E+10 | 0.295970E+10 |
May | 0.354857E+10 | 0.118240E+09 | 0.343033E+10 | 0.334807E+10 | 0.195602E+10 |
June | 0.364182E+10 | 0.195690E+09 | 0.344613E+10 | 0.449119E+10 | 0.107934E+10 |
July | 0.363678E+10 | 0.131518E+09 | 0.350527E+10 | 0.516703E+10 | 0.644501E+09 |
August | 0.322202E+10 | 38346539.14 | 0.318367E+10 | 0.453986E+10 | 0.852765E+09 |
September | 0.235051E+10 | 440156.01 | 0.235007E+10 | 0.253696E+10 | 0.157391E+10 |
October | 0.210201E+10 | 0.00 | 0.210201E+10 | 0.164263E+10 | 0.282977E+10 |
November | 0.142680E+10 | 0.00 | 0.142680E+10 | 0.464116E+09 | 0.416592E+10 |
December | 0.102356E+10 | 0.00 | 0.102356E+10 | 67020251.34 | 0.579564E+10 |
Annual Sum or Average | 0.283913E+11 | 0.491598E+09 | 0.278997E+11 | 0.250429E+11 | 0.384615E+11 |
Minimum of Months | 0.102356E+10 | 0.00 | 0.102356E+10 | 67020251.34 | 0.644501E+09 |
Maximum of Months | 0.364182E+10 | 0.195690E+09 | 0.350527E+10 | 0.516703E+10 | 0.636884E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163413E+10 | 0.655155E+09 | 0.978978E+09 | 0.101695E+10 | 0.394835E+10 |
February | 0.228894E+10 | 0.106779E+10 | 0.122115E+10 | 0.162812E+10 | 0.357134E+10 |
March | 0.323283E+10 | 0.137495E+10 | 0.185789E+10 | 0.285632E+10 | 0.278651E+10 |
April | 0.375448E+10 | 0.164458E+10 | 0.210990E+10 | 0.382922E+10 | 0.195473E+10 |
May | 0.470517E+10 | 0.188047E+10 | 0.282470E+10 | 0.543934E+10 | 0.134812E+10 |
June | 0.422003E+10 | 0.152762E+10 | 0.269241E+10 | 0.549152E+10 | 0.744735E+09 |
July | 0.437979E+10 | 0.158056E+10 | 0.279923E+10 | 0.619180E+10 | 0.442735E+09 |
August | 0.493175E+10 | 0.222373E+10 | 0.270802E+10 | 0.694113E+10 | 0.586690E+09 |
September | 0.355948E+10 | 0.159700E+10 | 0.196248E+10 | 0.443757E+10 | 0.104214E+10 |
October | 0.333449E+10 | 0.151131E+10 | 0.182319E+10 | 0.374056E+10 | 0.188108E+10 |
November | 0.199561E+10 | 0.766333E+09 | 0.122927E+10 | 0.165989E+10 | 0.262813E+10 |
December | 0.160651E+10 | 0.754320E+09 | 0.852193E+09 | 0.111531E+10 | 0.356505E+10 |
Annual Sum or Average | 0.396432E+11 | 0.165838E+11 | 0.230594E+11 | 0.443477E+11 | 0.244996E+11 |
Minimum of Months | 0.160651E+10 | 0.655155E+09 | 0.852193E+09 | 0.101695E+10 | 0.442735E+09 |
Maximum of Months | 0.493175E+10 | 0.222373E+10 | 0.282470E+10 | 0.694113E+10 | 0.394835E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.607052E+10 | 0.397502E+10 | 0.209550E+10 | 0.598031E+10 | 0.572473E+10 |
February | 0.723196E+10 | 0.478697E+10 | 0.244499E+10 | 0.725339E+10 | 0.525095E+10 |
March | 0.722365E+10 | 0.400925E+10 | 0.321440E+10 | 0.766478E+10 | 0.429313E+10 |
April | 0.542448E+10 | 0.214500E+10 | 0.327948E+10 | 0.596249E+10 | 0.314103E+10 |
May | 0.491221E+10 | 0.102461E+10 | 0.388760E+10 | 0.570358E+10 | 0.213595E+10 |
June | 0.446126E+10 | 0.681949E+09 | 0.377931E+10 | 0.597437E+10 | 0.116920E+10 |
July | 0.483217E+10 | 0.839346E+09 | 0.399282E+10 | 0.720020E+10 | 0.674780E+09 |
August | 0.645283E+10 | 0.239346E+10 | 0.405937E+10 | 0.970449E+10 | 0.942462E+09 |
September | 0.677560E+10 | 0.350462E+10 | 0.327098E+10 | 0.902430E+10 | 0.169817E+10 |
October | 0.959139E+10 | 0.601449E+10 | 0.357690E+10 | 0.119171E+11 | 0.305075E+10 |
November | 0.643627E+10 | 0.386529E+10 | 0.257098E+10 | 0.691356E+10 | 0.402546E+10 |
December | 0.657953E+10 | 0.467103E+10 | 0.190850E+10 | 0.679602E+10 | 0.520976E+10 |
Annual Sum or Average | 0.759919E+11 | 0.379110E+11 | 0.380808E+11 | 0.900945E+11 | 0.373164E+11 |
Minimum of Months | 0.446126E+10 | 0.681949E+09 | 0.190850E+10 | 0.570358E+10 | 0.674780E+09 |
Maximum of Months | 0.959139E+10 | 0.601449E+10 | 0.405937E+10 | 0.119171E+11 | 0.572473E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.161325E+10 | 0.660794E+09 | 0.952460E+09 | 0.996651E+09 | 0.412991E+10 |
February | 0.214875E+10 | 0.943739E+09 | 0.120501E+10 | 0.147453E+10 | 0.384409E+10 |
March | 0.351285E+10 | 0.162178E+10 | 0.189106E+10 | 0.316542E+10 | 0.289853E+10 |
April | 0.371553E+10 | 0.158978E+10 | 0.212575E+10 | 0.379698E+10 | 0.210896E+10 |
May | 0.447248E+10 | 0.169848E+10 | 0.277401E+10 | 0.517642E+10 | 0.145177E+10 |
June | 0.473710E+10 | 0.191061E+10 | 0.282649E+10 | 0.618588E+10 | 0.832104E+09 |
July | 0.458443E+10 | 0.172636E+10 | 0.285807E+10 | 0.644498E+10 | 0.508780E+09 |
August | 0.507163E+10 | 0.234783E+10 | 0.272380E+10 | 0.715133E+10 | 0.678803E+09 |
September | 0.348431E+10 | 0.152263E+10 | 0.196167E+10 | 0.438768E+10 | 0.113491E+10 |
October | 0.356958E+10 | 0.173580E+10 | 0.183378E+10 | 0.405252E+10 | 0.202676E+10 |
November | 0.162219E+10 | 0.468824E+09 | 0.115336E+10 | 0.112787E+10 | 0.281211E+10 |
December | 0.149100E+10 | 0.645160E+09 | 0.845840E+09 | 0.952442E+09 | 0.381043E+10 |
Annual Sum or Average | 0.400231E+11 | 0.168718E+11 | 0.231513E+11 | 0.449127E+11 | 0.262372E+11 |
Minimum of Months | 0.149100E+10 | 0.468824E+09 | 0.845840E+09 | 0.952442E+09 | 0.508780E+09 |
Maximum of Months | 0.507163E+10 | 0.234783E+10 | 0.285807E+10 | 0.715133E+10 | 0.412991E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 9.50 | 2795.94 | 438.11 | 0.00 | 438.11 | 0.00 | 0.00 |
February | 32.40 | 2892.93 | 599.53 | 0.00 | 599.53 | 0.00 | 0.00 |
March | 231.45 | 1996.13 | 831.40 | 0.00 | 831.40 | 0.00 | 0.00 |
April | 559.07 | 1422.99 | 998.63 | 2.84 | 995.79 | 0.00 | 0.00 |
May | 1209.30 | 818.62 | 1324.86 | 44.14 | 1280.72 | 0.00 | 0.00 |
June | 1739.85 | 434.64 | 1405.00 | 75.50 | 1329.50 | 0.00 | 0.00 |
July | 1947.28 | 231.29 | 1357.79 | 49.10 | 1308.69 | 0.00 | 0.00 |
August | 1696.61 | 319.17 | 1202.94 | 14.32 | 1188.63 | 0.00 | 0.00 |
September | 957.75 | 682.76 | 906.82 | 0.17 | 906.65 | 0.00 | 0.00 |
October | 535.16 | 1286.93 | 784.79 | 0.00 | 784.79 | 0.00 | 0.00 |
November | 106.58 | 2086.24 | 550.45 | 0.00 | 550.45 | 0.00 | 0.00 |
December | 4.42 | 2740.11 | 382.15 | 0.00 | 382.15 | 0.00 | 0.00 |
Annual Sum or Average | 757.40 | 1467.49 | 900.27 | 15.59 | 884.68 | 0.00 | 0.00 |
Minimum of Months | 4.42 | 231.29 | 382.15 | 0.00 | 382.15 | 0.00 | 0.00 |
Maximum of Months | 1947.28 | 2892.93 | 1405.00 | 75.50 | 1329.50 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 348.66 | 1715.85 | 610.12 | 244.61 | 365.51 | 0.00 | 0.00 |
February | 627.09 | 1715.13 | 946.16 | 441.38 | 504.78 | 0.00 | 0.00 |
March | 1020.03 | 1242.71 | 1207.01 | 513.35 | 693.66 | 0.00 | 0.00 |
April | 1442.01 | 877.62 | 1448.49 | 634.48 | 814.01 | 0.00 | 0.00 |
May | 2031.77 | 547.89 | 1756.72 | 702.09 | 1054.63 | 0.00 | 0.00 |
June | 2144.38 | 285.84 | 1628.10 | 589.36 | 1038.74 | 0.00 | 0.00 |
July | 2346.49 | 141.99 | 1635.23 | 590.11 | 1045.12 | 0.00 | 0.00 |
August | 2624.90 | 195.29 | 1841.31 | 830.25 | 1011.06 | 0.00 | 0.00 |
September | 1718.37 | 432.81 | 1373.26 | 616.13 | 757.13 | 0.00 | 0.00 |
October | 1367.13 | 811.16 | 1244.96 | 564.26 | 680.70 | 0.00 | 0.00 |
November | 580.17 | 1260.71 | 769.91 | 295.65 | 474.26 | 0.00 | 0.00 |
December | 376.28 | 1627.04 | 599.81 | 281.63 | 318.17 | 0.00 | 0.00 |
Annual Sum or Average | 1390.90 | 899.93 | 1257.08 | 525.87 | 731.21 | 0.00 | 0.00 |
Minimum of Months | 348.66 | 141.99 | 599.81 | 244.61 | 318.17 | 0.00 | 0.00 |
Maximum of Months | 2624.90 | 1715.85 | 1841.31 | 830.25 | 1054.63 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2198.29 | 2403.74 | 2266.40 | 1484.05 | 782.35 | 0.00 | 0.00 |
February | 2952.37 | 2436.80 | 2989.31 | 1978.68 | 1010.63 | 0.00 | 0.00 |
March | 2830.45 | 1851.35 | 2696.93 | 1496.83 | 1200.09 | 0.00 | 0.00 |
April | 2262.82 | 1401.24 | 2092.72 | 827.52 | 1265.20 | 0.00 | 0.00 |
May | 2126.15 | 867.82 | 1833.97 | 382.53 | 1451.43 | 0.00 | 0.00 |
June | 2327.75 | 465.47 | 1721.13 | 263.09 | 1458.04 | 0.00 | 0.00 |
July | 2718.30 | 241.47 | 1804.08 | 313.37 | 1490.72 | 0.00 | 0.00 |
August | 3653.73 | 344.74 | 2409.15 | 893.59 | 1515.56 | 0.00 | 0.00 |
September | 3503.12 | 694.72 | 2613.97 | 1352.04 | 1261.92 | 0.00 | 0.00 |
October | 4457.22 | 1254.25 | 3580.91 | 2245.48 | 1335.43 | 0.00 | 0.00 |
November | 2606.00 | 1837.63 | 2483.05 | 1491.19 | 991.86 | 0.00 | 0.00 |
December | 2476.46 | 2285.39 | 2456.44 | 1743.91 | 712.54 | 0.00 | 0.00 |
Annual Sum or Average | 2843.66 | 1334.01 | 2409.62 | 1202.11 | 1207.51 | 0.00 | 0.00 |
Minimum of Months | 2126.15 | 241.47 | 1721.13 | 263.09 | 712.54 | 0.00 | 0.00 |
Maximum of Months | 4457.22 | 2436.80 | 3580.91 | 2245.48 | 1515.56 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 342.21 | 1849.09 | 602.32 | 246.71 | 355.61 | 0.00 | 0.00 |
February | 564.72 | 1925.81 | 888.21 | 390.11 | 498.10 | 0.00 | 0.00 |
March | 1110.10 | 1398.73 | 1311.55 | 605.51 | 706.04 | 0.00 | 0.00 |
April | 1386.94 | 1067.24 | 1433.46 | 613.34 | 820.12 | 0.00 | 0.00 |
May | 1908.48 | 620.00 | 1669.84 | 634.14 | 1035.70 | 0.00 | 0.00 |
June | 2384.87 | 360.33 | 1827.59 | 737.12 | 1090.47 | 0.00 | 0.00 |
July | 2398.57 | 215.70 | 1711.64 | 644.55 | 1067.09 | 0.00 | 0.00 |
August | 2650.80 | 296.85 | 1893.54 | 876.58 | 1016.95 | 0.00 | 0.00 |
September | 1677.37 | 505.41 | 1344.26 | 587.44 | 756.82 | 0.00 | 0.00 |
October | 1462.36 | 931.01 | 1332.73 | 648.08 | 684.66 | 0.00 | 0.00 |
November | 364.26 | 1474.55 | 625.85 | 180.87 | 444.97 | 0.00 | 0.00 |
December | 303.89 | 1917.49 | 556.68 | 240.88 | 315.80 | 0.00 | 0.00 |
Annual Sum or Average | 1385.44 | 1041.76 | 1269.13 | 535.00 | 734.13 | 0.00 | 0.00 |
Minimum of Months | 303.89 | 215.70 | 556.68 | 180.87 | 315.80 | 0.00 | 0.00 |
Maximum of Months | 2650.80 | 1925.81 | 1893.54 | 876.58 | 1090.47 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 25.36 | 2481.94 | 438.12 | 0.00 | 438.12 | 0.00 | 0.00 |
February | 52.82 | 2590.17 | 599.54 | 0.00 | 599.54 | 0.00 | 0.00 |
March | 291.00 | 1734.30 | 831.42 | 0.00 | 831.42 | 0.00 | 0.00 |
April | 622.43 | 1241.02 | 998.65 | 2.84 | 995.80 | 0.00 | 0.00 |
May | 1233.61 | 767.78 | 1324.88 | 44.15 | 1280.74 | 0.00 | 0.00 |
June | 1746.18 | 418.59 | 1405.02 | 75.50 | 1329.53 | 0.00 | 0.00 |
July | 1952.20 | 232.43 | 1357.82 | 49.10 | 1308.72 | 0.00 | 0.00 |
August | 1710.28 | 315.94 | 1202.96 | 14.32 | 1188.65 | 0.00 | 0.00 |
September | 974.24 | 635.85 | 906.83 | 0.17 | 906.66 | 0.00 | 0.00 |
October | 577.50 | 1154.12 | 784.80 | 0.00 | 784.80 | 0.00 | 0.00 |
November | 147.95 | 1770.64 | 550.46 | 0.00 | 550.46 | 0.00 | 0.00 |
December | 15.76 | 2337.15 | 382.15 | 0.00 | 382.15 | 0.00 | 0.00 |
Annual Sum or Average | 784.06 | 1299.29 | 900.28 | 15.59 | 884.69 | 0.00 | 0.00 |
Minimum of Months | 15.76 | 232.43 | 382.15 | 0.00 | 382.15 | 0.00 | 0.00 |
Maximum of Months | 1952.20 | 2590.17 | 1405.02 | 75.50 | 1329.53 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 371.60 | 1539.55 | 610.12 | 244.61 | 365.51 | 0.00 | 0.00 |
February | 655.39 | 1559.03 | 946.16 | 441.38 | 504.77 | 0.00 | 0.00 |
March | 1044.07 | 1121.93 | 1207.00 | 513.35 | 693.66 | 0.00 | 0.00 |
April | 1455.57 | 809.60 | 1448.49 | 634.48 | 814.00 | 0.00 | 0.00 |
May | 2026.83 | 523.96 | 1756.71 | 702.09 | 1054.62 | 0.00 | 0.00 |
June | 2129.81 | 287.12 | 1628.10 | 589.36 | 1038.74 | 0.00 | 0.00 |
July | 2327.91 | 159.22 | 1635.23 | 590.11 | 1045.11 | 0.00 | 0.00 |
August | 2604.96 | 216.28 | 1841.30 | 830.24 | 1011.06 | 0.00 | 0.00 |
September | 1712.60 | 415.98 | 1373.25 | 616.13 | 757.13 | 0.00 | 0.00 |
October | 1376.60 | 755.88 | 1244.96 | 564.26 | 680.70 | 0.00 | 0.00 |
November | 611.25 | 1111.20 | 769.91 | 295.65 | 474.26 | 0.00 | 0.00 |
December | 399.59 | 1438.50 | 599.80 | 281.63 | 318.17 | 0.00 | 0.00 |
Annual Sum or Average | 1398.15 | 824.07 | 1257.08 | 525.87 | 731.21 | 0.00 | 0.00 |
Minimum of Months | 371.60 | 159.22 | 599.80 | 244.61 | 318.17 | 0.00 | 0.00 |
Maximum of Months | 2604.96 | 1559.03 | 1841.30 | 830.24 | 1054.62 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2213.12 | 2249.33 | 2266.47 | 1484.10 | 782.37 | 0.00 | 0.00 |
February | 2961.75 | 2309.82 | 2989.40 | 1978.74 | 1010.66 | 0.00 | 0.00 |
March | 2831.91 | 1735.10 | 2697.00 | 1496.88 | 1200.12 | 0.00 | 0.00 |
April | 2270.85 | 1308.95 | 2092.78 | 827.55 | 1265.23 | 0.00 | 0.00 |
May | 2119.98 | 837.65 | 1834.01 | 382.55 | 1451.47 | 0.00 | 0.00 |
June | 2320.01 | 453.92 | 1721.16 | 263.10 | 1458.07 | 0.00 | 0.00 |
July | 2711.43 | 244.28 | 1804.13 | 313.38 | 1490.75 | 0.00 | 0.00 |
August | 3643.16 | 348.63 | 2409.21 | 893.62 | 1515.59 | 0.00 | 0.00 |
September | 3484.70 | 678.01 | 2614.04 | 1352.09 | 1261.95 | 0.00 | 0.00 |
October | 4430.93 | 1217.18 | 3581.02 | 2245.55 | 1335.46 | 0.00 | 0.00 |
November | 2619.50 | 1708.37 | 2483.13 | 1491.24 | 991.89 | 0.00 | 0.00 |
December | 2493.64 | 2115.23 | 2456.52 | 1743.96 | 712.55 | 0.00 | 0.00 |
Annual Sum or Average | 2842.60 | 1261.15 | 2409.69 | 1202.15 | 1207.54 | 0.00 | 0.00 |
Minimum of Months | 2119.98 | 244.28 | 1721.16 | 263.10 | 712.55 | 0.00 | 0.00 |
Maximum of Months | 4430.93 | 2309.82 | 3581.02 | 2245.55 | 1515.59 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 366.29 | 1612.39 | 602.32 | 246.71 | 355.61 | 0.00 | 0.00 |
February | 600.56 | 1669.19 | 888.21 | 390.10 | 498.10 | 0.00 | 0.00 |
March | 1166.35 | 1158.34 | 1311.55 | 605.50 | 706.04 | 0.00 | 0.00 |
April | 1448.48 | 870.48 | 1433.46 | 613.34 | 820.12 | 0.00 | 0.00 |
May | 1927.68 | 565.37 | 1669.83 | 634.14 | 1035.70 | 0.00 | 0.00 |
June | 2398.13 | 322.82 | 1827.58 | 737.12 | 1090.47 | 0.00 | 0.00 |
July | 2421.79 | 186.16 | 1711.63 | 644.55 | 1067.08 | 0.00 | 0.00 |
August | 2682.66 | 251.85 | 1893.53 | 876.58 | 1016.95 | 0.00 | 0.00 |
September | 1692.81 | 453.61 | 1344.25 | 587.44 | 756.82 | 0.00 | 0.00 |
October | 1497.31 | 809.59 | 1332.73 | 648.07 | 684.65 | 0.00 | 0.00 |
November | 414.83 | 1177.95 | 625.84 | 180.87 | 444.97 | 0.00 | 0.00 |
December | 344.81 | 1526.04 | 556.68 | 240.88 | 315.80 | 0.00 | 0.00 |
Annual Sum or Average | 1419.33 | 879.14 | 1269.12 | 535.00 | 734.12 | 0.00 | 0.00 |
Minimum of Months | 344.81 | 186.16 | 556.68 | 180.87 | 315.80 | 0.00 | 0.00 |
Maximum of Months | 2682.66 | 1669.19 | 1893.53 | 876.58 | 1090.47 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 30.19 | 2377.85 | 438.12 | 0.00 | 438.12 | 0.00 | 0.00 |
February | 63.78 | 2455.36 | 599.54 | 0.00 | 599.54 | 0.00 | 0.00 |
March | 316.04 | 1603.60 | 831.42 | 0.00 | 831.42 | 0.00 | 0.00 |
April | 657.54 | 1141.86 | 998.65 | 2.84 | 995.80 | 0.00 | 0.00 |
May | 1250.03 | 730.29 | 1324.88 | 44.15 | 1280.74 | 0.00 | 0.00 |
June | 1732.71 | 416.41 | 1405.02 | 75.50 | 1329.53 | 0.00 | 0.00 |
July | 1929.15 | 240.63 | 1357.82 | 49.10 | 1308.72 | 0.00 | 0.00 |
August | 1694.99 | 318.39 | 1202.96 | 14.32 | 1188.65 | 0.00 | 0.00 |
September | 978.76 | 607.22 | 906.83 | 0.17 | 906.66 | 0.00 | 0.00 |
October | 613.29 | 1056.52 | 784.80 | 0.00 | 784.80 | 0.00 | 0.00 |
November | 179.06 | 1607.22 | 550.46 | 0.00 | 550.46 | 0.00 | 0.00 |
December | 25.02 | 2163.84 | 382.15 | 0.00 | 382.15 | 0.00 | 0.00 |
Annual Sum or Average | 794.10 | 1219.61 | 900.28 | 15.59 | 884.69 | 0.00 | 0.00 |
Minimum of Months | 25.02 | 240.63 | 382.15 | 0.00 | 382.15 | 0.00 | 0.00 |
Maximum of Months | 1929.15 | 2455.36 | 1405.02 | 75.50 | 1329.53 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 379.69 | 1474.15 | 610.12 | 244.61 | 365.51 | 0.00 | 0.00 |
February | 673.00 | 1476.25 | 946.16 | 441.38 | 504.77 | 0.00 | 0.00 |
March | 1066.43 | 1040.36 | 1207.00 | 513.35 | 693.66 | 0.00 | 0.00 |
April | 1477.32 | 754.14 | 1448.49 | 634.48 | 814.00 | 0.00 | 0.00 |
May | 2030.82 | 503.33 | 1756.71 | 702.09 | 1054.62 | 0.00 | 0.00 |
June | 2118.64 | 287.32 | 1628.10 | 589.36 | 1038.74 | 0.00 | 0.00 |
July | 2311.75 | 165.30 | 1635.23 | 590.11 | 1045.11 | 0.00 | 0.00 |
August | 2591.52 | 219.04 | 1841.30 | 830.24 | 1011.06 | 0.00 | 0.00 |
September | 1712.03 | 402.06 | 1373.25 | 616.13 | 757.13 | 0.00 | 0.00 |
October | 1396.57 | 702.31 | 1244.96 | 564.26 | 680.70 | 0.00 | 0.00 |
November | 640.39 | 1013.94 | 769.91 | 295.65 | 474.26 | 0.00 | 0.00 |
December | 416.41 | 1331.04 | 599.80 | 281.63 | 318.17 | 0.00 | 0.00 |
Annual Sum or Average | 1406.26 | 776.88 | 1257.08 | 525.87 | 731.21 | 0.00 | 0.00 |
Minimum of Months | 379.69 | 165.30 | 599.80 | 244.61 | 318.17 | 0.00 | 0.00 |
Maximum of Months | 2591.52 | 1476.25 | 1841.30 | 830.24 | 1054.62 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2232.79 | 2137.37 | 2266.47 | 1484.10 | 782.37 | 0.00 | 0.00 |
February | 2998.26 | 2170.53 | 2989.40 | 1978.74 | 1010.66 | 0.00 | 0.00 |
March | 2861.70 | 1602.87 | 2697.00 | 1496.88 | 1200.12 | 0.00 | 0.00 |
April | 2300.34 | 1211.82 | 2092.78 | 827.55 | 1265.23 | 0.00 | 0.00 |
May | 2129.47 | 797.47 | 1834.01 | 382.55 | 1451.47 | 0.00 | 0.00 |
June | 2304.93 | 451.08 | 1721.16 | 263.10 | 1458.07 | 0.00 | 0.00 |
July | 2688.25 | 251.93 | 1804.13 | 313.38 | 1490.75 | 0.00 | 0.00 |
August | 3623.24 | 351.88 | 2409.21 | 893.62 | 1515.59 | 0.00 | 0.00 |
September | 3481.60 | 655.16 | 2614.04 | 1352.09 | 1261.95 | 0.00 | 0.00 |
October | 4449.32 | 1139.02 | 3581.02 | 2245.55 | 1335.46 | 0.00 | 0.00 |
November | 2667.27 | 1553.03 | 2483.13 | 1491.24 | 991.89 | 0.00 | 0.00 |
December | 2537.34 | 1945.10 | 2456.52 | 1743.96 | 712.55 | 0.00 | 0.00 |
Annual Sum or Average | 2856.88 | 1183.29 | 2409.69 | 1202.15 | 1207.54 | 0.00 | 0.00 |
Minimum of Months | 2129.47 | 251.93 | 1721.16 | 263.10 | 712.55 | 0.00 | 0.00 |
Maximum of Months | 4449.32 | 2170.53 | 3581.02 | 2245.55 | 1515.59 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 372.11 | 1541.93 | 602.32 | 246.71 | 355.61 | 0.00 | 0.00 |
February | 609.51 | 1588.99 | 888.21 | 390.10 | 498.10 | 0.00 | 0.00 |
March | 1181.83 | 1082.19 | 1311.55 | 605.50 | 706.04 | 0.00 | 0.00 |
April | 1464.88 | 813.64 | 1433.46 | 613.34 | 820.12 | 0.00 | 0.00 |
May | 1932.65 | 542.03 | 1669.83 | 634.14 | 1035.70 | 0.00 | 0.00 |
June | 2386.53 | 321.03 | 1827.58 | 737.12 | 1090.47 | 0.00 | 0.00 |
July | 2406.28 | 189.96 | 1711.63 | 644.55 | 1067.08 | 0.00 | 0.00 |
August | 2670.00 | 253.44 | 1893.53 | 876.58 | 1016.95 | 0.00 | 0.00 |
September | 1692.78 | 437.85 | 1344.25 | 587.44 | 756.82 | 0.00 | 0.00 |
October | 1513.04 | 756.70 | 1332.73 | 648.07 | 684.65 | 0.00 | 0.00 |
November | 435.14 | 1084.92 | 625.84 | 180.87 | 444.97 | 0.00 | 0.00 |
December | 355.60 | 1422.65 | 556.68 | 240.88 | 315.80 | 0.00 | 0.00 |
Annual Sum or Average | 1424.17 | 831.97 | 1269.12 | 535.00 | 734.12 | 0.00 | 0.00 |
Minimum of Months | 355.60 | 189.96 | 556.68 | 180.87 | 315.80 | 0.00 | 0.00 |
Maximum of Months | 2670.00 | 1588.99 | 1893.53 | 876.58 | 1090.47 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 25457782.57 | 0.748865E+10 | 0.117343E+10 | 0.00 | 0.117343E+10 | 0.00 | 0.00 |
February | 78375354.88 | 0.699859E+10 | 0.145039E+10 | 0.00 | 0.145039E+10 | 0.00 | 0.00 |
March | 0.619907E+09 | 0.534645E+10 | 0.222683E+10 | 0.00 | 0.222683E+10 | 0.00 | 0.00 |
April | 0.144912E+10 | 0.368839E+10 | 0.258844E+10 | 7362242.16 | 0.258108E+10 | 0.00 | 0.00 |
May | 0.323899E+10 | 0.219258E+10 | 0.354851E+10 | 0.118237E+09 | 0.343027E+10 | 0.00 | 0.00 |
June | 0.450969E+10 | 0.112659E+10 | 0.364175E+10 | 0.195684E+09 | 0.344607E+10 | 0.00 | 0.00 |
July | 0.521560E+10 | 0.619479E+09 | 0.363672E+10 | 0.131514E+09 | 0.350520E+10 | 0.00 | 0.00 |
August | 0.454420E+10 | 0.854854E+09 | 0.322196E+10 | 38345395.57 | 0.318362E+10 | 0.00 | 0.00 |
September | 0.248249E+10 | 0.176972E+10 | 0.235047E+10 | 440142.88 | 0.235003E+10 | 0.00 | 0.00 |
October | 0.143337E+10 | 0.344692E+10 | 0.210197E+10 | 0.00 | 0.210197E+10 | 0.00 | 0.00 |
November | 0.276250E+09 | 0.540752E+10 | 0.142677E+10 | 0.00 | 0.142677E+10 | 0.00 | 0.00 |
December | 11846987.61 | 0.733912E+10 | 0.102354E+10 | 0.00 | 0.102354E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.238853E+11 | 0.462789E+11 | 0.283908E+11 | 0.491583E+09 | 0.278992E+11 | 0.00 | 0.00 |
Minimum of Months | 11846987.61 | 0.619479E+09 | 0.102354E+10 | 0.00 | 0.102354E+10 | 0.00 | 0.00 |
Maximum of Months | 0.521560E+10 | 0.748865E+10 | 0.364175E+10 | 0.195684E+09 | 0.350520E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.933860E+09 | 0.459574E+10 | 0.163414E+10 | 0.655158E+09 | 0.978982E+09 | 0.00 | 0.00 |
February | 0.151707E+10 | 0.414925E+10 | 0.228895E+10 | 0.106780E+10 | 0.122116E+10 | 0.00 | 0.00 |
March | 0.273206E+10 | 0.332848E+10 | 0.323285E+10 | 0.137495E+10 | 0.185790E+10 | 0.00 | 0.00 |
April | 0.373770E+10 | 0.227479E+10 | 0.375449E+10 | 0.164458E+10 | 0.210991E+10 | 0.00 | 0.00 |
May | 0.544190E+10 | 0.146748E+10 | 0.470519E+10 | 0.188048E+10 | 0.282471E+10 | 0.00 | 0.00 |
June | 0.555823E+10 | 0.740892E+09 | 0.422005E+10 | 0.152763E+10 | 0.269242E+10 | 0.00 | 0.00 |
July | 0.628485E+10 | 0.380300E+09 | 0.437981E+10 | 0.158056E+10 | 0.279924E+10 | 0.00 | 0.00 |
August | 0.703054E+10 | 0.523053E+09 | 0.493177E+10 | 0.222373E+10 | 0.270803E+10 | 0.00 | 0.00 |
September | 0.445402E+10 | 0.112184E+10 | 0.355949E+10 | 0.159700E+10 | 0.196249E+10 | 0.00 | 0.00 |
October | 0.366173E+10 | 0.217262E+10 | 0.333451E+10 | 0.151131E+10 | 0.182319E+10 | 0.00 | 0.00 |
November | 0.150380E+10 | 0.326775E+10 | 0.199561E+10 | 0.766336E+09 | 0.122928E+10 | 0.00 | 0.00 |
December | 0.100783E+10 | 0.435785E+10 | 0.160652E+10 | 0.754323E+09 | 0.852197E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.438636E+11 | 0.283800E+11 | 0.396434E+11 | 0.165839E+11 | 0.230595E+11 | 0.00 | 0.00 |
Minimum of Months | 0.933860E+09 | 0.380300E+09 | 0.160652E+10 | 0.655158E+09 | 0.852197E+09 | 0.00 | 0.00 |
Maximum of Months | 0.703054E+10 | 0.459574E+10 | 0.493177E+10 | 0.222373E+10 | 0.282471E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.588790E+10 | 0.643818E+10 | 0.607034E+10 | 0.397489E+10 | 0.209545E+10 | 0.00 | 0.00 |
February | 0.714238E+10 | 0.589510E+10 | 0.723174E+10 | 0.478681E+10 | 0.244493E+10 | 0.00 | 0.00 |
March | 0.758109E+10 | 0.495865E+10 | 0.722345E+10 | 0.400912E+10 | 0.321432E+10 | 0.00 | 0.00 |
April | 0.586523E+10 | 0.363201E+10 | 0.542434E+10 | 0.214493E+10 | 0.327941E+10 | 0.00 | 0.00 |
May | 0.569469E+10 | 0.232436E+10 | 0.491210E+10 | 0.102458E+10 | 0.388752E+10 | 0.00 | 0.00 |
June | 0.603353E+10 | 0.120651E+10 | 0.446116E+10 | 0.681927E+09 | 0.377923E+10 | 0.00 | 0.00 |
July | 0.728070E+10 | 0.646762E+09 | 0.483206E+10 | 0.839319E+09 | 0.399274E+10 | 0.00 | 0.00 |
August | 0.978615E+10 | 0.923353E+09 | 0.645266E+10 | 0.239338E+10 | 0.405928E+10 | 0.00 | 0.00 |
September | 0.908008E+10 | 0.180070E+10 | 0.677541E+10 | 0.350450E+10 | 0.327091E+10 | 0.00 | 0.00 |
October | 0.119382E+11 | 0.335939E+10 | 0.959111E+10 | 0.601430E+10 | 0.357681E+10 | 0.00 | 0.00 |
November | 0.675474E+10 | 0.476314E+10 | 0.643607E+10 | 0.386516E+10 | 0.257091E+10 | 0.00 | 0.00 |
December | 0.663296E+10 | 0.612118E+10 | 0.657933E+10 | 0.467088E+10 | 0.190845E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.896776E+11 | 0.420693E+11 | 0.759898E+11 | 0.379098E+11 | 0.380800E+11 | 0.00 | 0.00 |
Minimum of Months | 0.569469E+10 | 0.646762E+09 | 0.446116E+10 | 0.681927E+09 | 0.190845E+10 | 0.00 | 0.00 |
Maximum of Months | 0.119382E+11 | 0.643818E+10 | 0.959111E+10 | 0.601430E+10 | 0.405928E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.916580E+09 | 0.495259E+10 | 0.161326E+10 | 0.660796E+09 | 0.952464E+09 | 0.00 | 0.00 |
February | 0.136617E+10 | 0.465892E+10 | 0.214876E+10 | 0.943743E+09 | 0.120502E+10 | 0.00 | 0.00 |
March | 0.297328E+10 | 0.374636E+10 | 0.351286E+10 | 0.162179E+10 | 0.189107E+10 | 0.00 | 0.00 |
April | 0.359494E+10 | 0.276629E+10 | 0.371554E+10 | 0.158978E+10 | 0.212576E+10 | 0.00 | 0.00 |
May | 0.511168E+10 | 0.166061E+10 | 0.447250E+10 | 0.169848E+10 | 0.277402E+10 | 0.00 | 0.00 |
June | 0.618159E+10 | 0.933965E+09 | 0.473712E+10 | 0.191061E+10 | 0.282650E+10 | 0.00 | 0.00 |
July | 0.642434E+10 | 0.577741E+09 | 0.458445E+10 | 0.172636E+10 | 0.285809E+10 | 0.00 | 0.00 |
August | 0.709989E+10 | 0.795085E+09 | 0.507165E+10 | 0.234784E+10 | 0.272381E+10 | 0.00 | 0.00 |
September | 0.434774E+10 | 0.131002E+10 | 0.348432E+10 | 0.152264E+10 | 0.196168E+10 | 0.00 | 0.00 |
October | 0.391679E+10 | 0.249361E+10 | 0.356959E+10 | 0.173581E+10 | 0.183379E+10 | 0.00 | 0.00 |
November | 0.944174E+09 | 0.382202E+10 | 0.162219E+10 | 0.468826E+09 | 0.115337E+10 | 0.00 | 0.00 |
December | 0.813952E+09 | 0.513579E+10 | 0.149101E+10 | 0.645163E+09 | 0.845843E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.436911E+11 | 0.328530E+11 | 0.400232E+11 | 0.168718E+11 | 0.231514E+11 | 0.00 | 0.00 |
Minimum of Months | 0.813952E+09 | 0.577741E+09 | 0.149101E+10 | 0.468826E+09 | 0.845843E+09 | 0.00 | 0.00 |
Maximum of Months | 0.709989E+10 | 0.513579E+10 | 0.507165E+10 | 0.234784E+10 | 0.285809E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 67923433.42 | 0.664763E+10 | 0.117345E+10 | 0.00 | 0.117345E+10 | 0.00 | 0.00 |
February | 0.127786E+09 | 0.626614E+10 | 0.145042E+10 | 0.00 | 0.145042E+10 | 0.00 | 0.00 |
March | 0.779424E+09 | 0.464515E+10 | 0.222687E+10 | 0.00 | 0.222687E+10 | 0.00 | 0.00 |
April | 0.161335E+10 | 0.321672E+10 | 0.258849E+10 | 7362461.72 | 0.258113E+10 | 0.00 | 0.00 |
May | 0.330411E+10 | 0.205643E+10 | 0.354857E+10 | 0.118240E+09 | 0.343033E+10 | 0.00 | 0.00 |
June | 0.452610E+10 | 0.108499E+10 | 0.364182E+10 | 0.195690E+09 | 0.344613E+10 | 0.00 | 0.00 |
July | 0.522878E+10 | 0.622554E+09 | 0.363678E+10 | 0.131518E+09 | 0.350527E+10 | 0.00 | 0.00 |
August | 0.458080E+10 | 0.846226E+09 | 0.322202E+10 | 38346539.14 | 0.318367E+10 | 0.00 | 0.00 |
September | 0.252522E+10 | 0.164813E+10 | 0.235051E+10 | 440156.01 | 0.235007E+10 | 0.00 | 0.00 |
October | 0.154679E+10 | 0.309120E+10 | 0.210201E+10 | 0.00 | 0.210201E+10 | 0.00 | 0.00 |
November | 0.383484E+09 | 0.458951E+10 | 0.142680E+10 | 0.00 | 0.142680E+10 | 0.00 | 0.00 |
December | 42209004.86 | 0.625982E+10 | 0.102356E+10 | 0.00 | 0.102356E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.247260E+11 | 0.409745E+11 | 0.283913E+11 | 0.491598E+09 | 0.278997E+11 | 0.00 | 0.00 |
Minimum of Months | 42209004.86 | 0.622554E+09 | 0.102356E+10 | 0.00 | 0.102356E+10 | 0.00 | 0.00 |
Maximum of Months | 0.522878E+10 | 0.664763E+10 | 0.364182E+10 | 0.195690E+09 | 0.350527E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.995293E+09 | 0.412353E+10 | 0.163413E+10 | 0.655155E+09 | 0.978978E+09 | 0.00 | 0.00 |
February | 0.158552E+10 | 0.377161E+10 | 0.228894E+10 | 0.106779E+10 | 0.122115E+10 | 0.00 | 0.00 |
March | 0.279643E+10 | 0.300498E+10 | 0.323283E+10 | 0.137495E+10 | 0.185789E+10 | 0.00 | 0.00 |
April | 0.377284E+10 | 0.209849E+10 | 0.375448E+10 | 0.164458E+10 | 0.210990E+10 | 0.00 | 0.00 |
May | 0.542867E+10 | 0.140337E+10 | 0.470517E+10 | 0.188047E+10 | 0.282470E+10 | 0.00 | 0.00 |
June | 0.552048E+10 | 0.744209E+09 | 0.422003E+10 | 0.152762E+10 | 0.269241E+10 | 0.00 | 0.00 |
July | 0.623507E+10 | 0.426451E+09 | 0.437979E+10 | 0.158056E+10 | 0.279923E+10 | 0.00 | 0.00 |
August | 0.697712E+10 | 0.579282E+09 | 0.493175E+10 | 0.222373E+10 | 0.270802E+10 | 0.00 | 0.00 |
September | 0.443907E+10 | 0.107822E+10 | 0.355948E+10 | 0.159700E+10 | 0.196248E+10 | 0.00 | 0.00 |
October | 0.368710E+10 | 0.202454E+10 | 0.333449E+10 | 0.151131E+10 | 0.182319E+10 | 0.00 | 0.00 |
November | 0.158436E+10 | 0.288022E+10 | 0.199561E+10 | 0.766333E+09 | 0.122927E+10 | 0.00 | 0.00 |
December | 0.107026E+10 | 0.385287E+10 | 0.160651E+10 | 0.754320E+09 | 0.852193E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.440922E+11 | 0.259878E+11 | 0.396432E+11 | 0.165838E+11 | 0.230594E+11 | 0.00 | 0.00 |
Minimum of Months | 0.995293E+09 | 0.426451E+09 | 0.160651E+10 | 0.655155E+09 | 0.852193E+09 | 0.00 | 0.00 |
Maximum of Months | 0.697712E+10 | 0.412353E+10 | 0.493175E+10 | 0.222373E+10 | 0.282470E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.592763E+10 | 0.602459E+10 | 0.607052E+10 | 0.397502E+10 | 0.209550E+10 | 0.00 | 0.00 |
February | 0.716508E+10 | 0.558791E+10 | 0.723196E+10 | 0.478697E+10 | 0.244499E+10 | 0.00 | 0.00 |
March | 0.758500E+10 | 0.464729E+10 | 0.722365E+10 | 0.400925E+10 | 0.321440E+10 | 0.00 | 0.00 |
April | 0.588605E+10 | 0.339279E+10 | 0.542448E+10 | 0.214500E+10 | 0.327948E+10 | 0.00 | 0.00 |
May | 0.567815E+10 | 0.224355E+10 | 0.491221E+10 | 0.102461E+10 | 0.388760E+10 | 0.00 | 0.00 |
June | 0.601347E+10 | 0.117655E+10 | 0.446126E+10 | 0.681949E+09 | 0.377931E+10 | 0.00 | 0.00 |
July | 0.726228E+10 | 0.654267E+09 | 0.483217E+10 | 0.839346E+09 | 0.399282E+10 | 0.00 | 0.00 |
August | 0.975784E+10 | 0.933769E+09 | 0.645283E+10 | 0.239346E+10 | 0.405937E+10 | 0.00 | 0.00 |
September | 0.903235E+10 | 0.175741E+10 | 0.677560E+10 | 0.350462E+10 | 0.327098E+10 | 0.00 | 0.00 |
October | 0.118678E+11 | 0.326009E+10 | 0.959139E+10 | 0.601449E+10 | 0.357690E+10 | 0.00 | 0.00 |
November | 0.678975E+10 | 0.442809E+10 | 0.643627E+10 | 0.386529E+10 | 0.257098E+10 | 0.00 | 0.00 |
December | 0.667897E+10 | 0.566544E+10 | 0.657953E+10 | 0.467103E+10 | 0.190850E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.896444E+11 | 0.397718E+11 | 0.759919E+11 | 0.379110E+11 | 0.380808E+11 | 0.00 | 0.00 |
Minimum of Months | 0.567815E+10 | 0.654267E+09 | 0.446126E+10 | 0.681949E+09 | 0.190850E+10 | 0.00 | 0.00 |
Maximum of Months | 0.118678E+11 | 0.602459E+10 | 0.959139E+10 | 0.601449E+10 | 0.405937E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.981058E+09 | 0.431862E+10 | 0.161325E+10 | 0.660794E+09 | 0.952460E+09 | 0.00 | 0.00 |
February | 0.145286E+10 | 0.403810E+10 | 0.214875E+10 | 0.943739E+09 | 0.120501E+10 | 0.00 | 0.00 |
March | 0.312394E+10 | 0.310251E+10 | 0.351285E+10 | 0.162178E+10 | 0.189106E+10 | 0.00 | 0.00 |
April | 0.375447E+10 | 0.225629E+10 | 0.371553E+10 | 0.158978E+10 | 0.212575E+10 | 0.00 | 0.00 |
May | 0.516310E+10 | 0.151428E+10 | 0.447248E+10 | 0.169848E+10 | 0.277401E+10 | 0.00 | 0.00 |
June | 0.621595E+10 | 0.836751E+09 | 0.473710E+10 | 0.191061E+10 | 0.282649E+10 | 0.00 | 0.00 |
July | 0.648653E+10 | 0.498604E+09 | 0.458443E+10 | 0.172636E+10 | 0.285807E+10 | 0.00 | 0.00 |
August | 0.718523E+10 | 0.674563E+09 | 0.507163E+10 | 0.234783E+10 | 0.272380E+10 | 0.00 | 0.00 |
September | 0.438777E+10 | 0.117576E+10 | 0.348431E+10 | 0.152263E+10 | 0.196167E+10 | 0.00 | 0.00 |
October | 0.401039E+10 | 0.216842E+10 | 0.356958E+10 | 0.173580E+10 | 0.183378E+10 | 0.00 | 0.00 |
November | 0.107523E+10 | 0.305325E+10 | 0.162219E+10 | 0.468824E+09 | 0.115336E+10 | 0.00 | 0.00 |
December | 0.923540E+09 | 0.408734E+10 | 0.149100E+10 | 0.645160E+09 | 0.845840E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.447601E+11 | 0.277245E+11 | 0.400231E+11 | 0.168718E+11 | 0.231513E+11 | 0.00 | 0.00 |
Minimum of Months | 0.923540E+09 | 0.498604E+09 | 0.149100E+10 | 0.468824E+09 | 0.845840E+09 | 0.00 | 0.00 |
Maximum of Months | 0.718523E+10 | 0.431862E+10 | 0.507163E+10 | 0.234783E+10 | 0.285807E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 80854585.16 | 0.636884E+10 | 0.117345E+10 | 0.00 | 0.117345E+10 | 0.00 | 0.00 |
February | 0.154306E+09 | 0.594000E+10 | 0.145042E+10 | 0.00 | 0.145042E+10 | 0.00 | 0.00 |
March | 0.846491E+09 | 0.429507E+10 | 0.222687E+10 | 0.00 | 0.222687E+10 | 0.00 | 0.00 |
April | 0.170435E+10 | 0.295970E+10 | 0.258849E+10 | 7362461.72 | 0.258113E+10 | 0.00 | 0.00 |
May | 0.334807E+10 | 0.195602E+10 | 0.354857E+10 | 0.118240E+09 | 0.343033E+10 | 0.00 | 0.00 |
June | 0.449119E+10 | 0.107934E+10 | 0.364182E+10 | 0.195690E+09 | 0.344613E+10 | 0.00 | 0.00 |
July | 0.516703E+10 | 0.644501E+09 | 0.363678E+10 | 0.131518E+09 | 0.350527E+10 | 0.00 | 0.00 |
August | 0.453986E+10 | 0.852765E+09 | 0.322202E+10 | 38346539.14 | 0.318367E+10 | 0.00 | 0.00 |
September | 0.253696E+10 | 0.157391E+10 | 0.235051E+10 | 440156.01 | 0.235007E+10 | 0.00 | 0.00 |
October | 0.164263E+10 | 0.282977E+10 | 0.210201E+10 | 0.00 | 0.210201E+10 | 0.00 | 0.00 |
November | 0.464116E+09 | 0.416592E+10 | 0.142680E+10 | 0.00 | 0.142680E+10 | 0.00 | 0.00 |
December | 67020251.34 | 0.579564E+10 | 0.102356E+10 | 0.00 | 0.102356E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.250429E+11 | 0.384615E+11 | 0.283913E+11 | 0.491598E+09 | 0.278997E+11 | 0.00 | 0.00 |
Minimum of Months | 67020251.34 | 0.644501E+09 | 0.102356E+10 | 0.00 | 0.102356E+10 | 0.00 | 0.00 |
Maximum of Months | 0.516703E+10 | 0.636884E+10 | 0.364182E+10 | 0.195690E+09 | 0.350527E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.101695E+10 | 0.394835E+10 | 0.163413E+10 | 0.655155E+09 | 0.978978E+09 | 0.00 | 0.00 |
February | 0.162812E+10 | 0.357134E+10 | 0.228894E+10 | 0.106779E+10 | 0.122115E+10 | 0.00 | 0.00 |
March | 0.285632E+10 | 0.278651E+10 | 0.323283E+10 | 0.137495E+10 | 0.185789E+10 | 0.00 | 0.00 |
April | 0.382922E+10 | 0.195473E+10 | 0.375448E+10 | 0.164458E+10 | 0.210990E+10 | 0.00 | 0.00 |
May | 0.543934E+10 | 0.134812E+10 | 0.470517E+10 | 0.188047E+10 | 0.282470E+10 | 0.00 | 0.00 |
June | 0.549152E+10 | 0.744735E+09 | 0.422003E+10 | 0.152762E+10 | 0.269241E+10 | 0.00 | 0.00 |
July | 0.619180E+10 | 0.442735E+09 | 0.437979E+10 | 0.158056E+10 | 0.279923E+10 | 0.00 | 0.00 |
August | 0.694113E+10 | 0.586690E+09 | 0.493175E+10 | 0.222373E+10 | 0.270802E+10 | 0.00 | 0.00 |
September | 0.443757E+10 | 0.104214E+10 | 0.355948E+10 | 0.159700E+10 | 0.196248E+10 | 0.00 | 0.00 |
October | 0.374056E+10 | 0.188108E+10 | 0.333449E+10 | 0.151131E+10 | 0.182319E+10 | 0.00 | 0.00 |
November | 0.165989E+10 | 0.262813E+10 | 0.199561E+10 | 0.766333E+09 | 0.122927E+10 | 0.00 | 0.00 |
December | 0.111531E+10 | 0.356505E+10 | 0.160651E+10 | 0.754320E+09 | 0.852193E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.443477E+11 | 0.244996E+11 | 0.396432E+11 | 0.165838E+11 | 0.230594E+11 | 0.00 | 0.00 |
Minimum of Months | 0.101695E+10 | 0.442735E+09 | 0.160651E+10 | 0.655155E+09 | 0.852193E+09 | 0.00 | 0.00 |
Maximum of Months | 0.694113E+10 | 0.394835E+10 | 0.493175E+10 | 0.222373E+10 | 0.282470E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.598031E+10 | 0.572473E+10 | 0.607052E+10 | 0.397502E+10 | 0.209550E+10 | 0.00 | 0.00 |
February | 0.725339E+10 | 0.525095E+10 | 0.723196E+10 | 0.478697E+10 | 0.244499E+10 | 0.00 | 0.00 |
March | 0.766478E+10 | 0.429313E+10 | 0.722365E+10 | 0.400925E+10 | 0.321440E+10 | 0.00 | 0.00 |
April | 0.596249E+10 | 0.314103E+10 | 0.542448E+10 | 0.214500E+10 | 0.327948E+10 | 0.00 | 0.00 |
May | 0.570358E+10 | 0.213595E+10 | 0.491221E+10 | 0.102461E+10 | 0.388760E+10 | 0.00 | 0.00 |
June | 0.597437E+10 | 0.116920E+10 | 0.446126E+10 | 0.681949E+09 | 0.377931E+10 | 0.00 | 0.00 |
July | 0.720020E+10 | 0.674780E+09 | 0.483217E+10 | 0.839346E+09 | 0.399282E+10 | 0.00 | 0.00 |
August | 0.970449E+10 | 0.942462E+09 | 0.645283E+10 | 0.239346E+10 | 0.405937E+10 | 0.00 | 0.00 |
September | 0.902430E+10 | 0.169817E+10 | 0.677560E+10 | 0.350462E+10 | 0.327098E+10 | 0.00 | 0.00 |
October | 0.119171E+11 | 0.305075E+10 | 0.959139E+10 | 0.601449E+10 | 0.357690E+10 | 0.00 | 0.00 |
November | 0.691356E+10 | 0.402546E+10 | 0.643627E+10 | 0.386529E+10 | 0.257098E+10 | 0.00 | 0.00 |
December | 0.679602E+10 | 0.520976E+10 | 0.657953E+10 | 0.467103E+10 | 0.190850E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.900945E+11 | 0.373164E+11 | 0.759919E+11 | 0.379110E+11 | 0.380808E+11 | 0.00 | 0.00 |
Minimum of Months | 0.570358E+10 | 0.674780E+09 | 0.446126E+10 | 0.681949E+09 | 0.190850E+10 | 0.00 | 0.00 |
Maximum of Months | 0.119171E+11 | 0.572473E+10 | 0.959139E+10 | 0.601449E+10 | 0.405937E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.996651E+09 | 0.412991E+10 | 0.161325E+10 | 0.660794E+09 | 0.952460E+09 | 0.00 | 0.00 |
February | 0.147453E+10 | 0.384409E+10 | 0.214875E+10 | 0.943739E+09 | 0.120501E+10 | 0.00 | 0.00 |
March | 0.316542E+10 | 0.289853E+10 | 0.351285E+10 | 0.162178E+10 | 0.189106E+10 | 0.00 | 0.00 |
April | 0.379698E+10 | 0.210896E+10 | 0.371553E+10 | 0.158978E+10 | 0.212575E+10 | 0.00 | 0.00 |
May | 0.517642E+10 | 0.145177E+10 | 0.447248E+10 | 0.169848E+10 | 0.277401E+10 | 0.00 | 0.00 |
June | 0.618588E+10 | 0.832104E+09 | 0.473710E+10 | 0.191061E+10 | 0.282649E+10 | 0.00 | 0.00 |
July | 0.644498E+10 | 0.508780E+09 | 0.458443E+10 | 0.172636E+10 | 0.285807E+10 | 0.00 | 0.00 |
August | 0.715133E+10 | 0.678803E+09 | 0.507163E+10 | 0.234783E+10 | 0.272380E+10 | 0.00 | 0.00 |
September | 0.438768E+10 | 0.113491E+10 | 0.348431E+10 | 0.152263E+10 | 0.196167E+10 | 0.00 | 0.00 |
October | 0.405252E+10 | 0.202676E+10 | 0.356958E+10 | 0.173580E+10 | 0.183378E+10 | 0.00 | 0.00 |
November | 0.112787E+10 | 0.281211E+10 | 0.162219E+10 | 0.468824E+09 | 0.115336E+10 | 0.00 | 0.00 |
December | 0.952442E+09 | 0.381043E+10 | 0.149100E+10 | 0.645160E+09 | 0.845840E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.449127E+11 | 0.262372E+11 | 0.400231E+11 | 0.168718E+11 | 0.231513E+11 | 0.00 | 0.00 |
Minimum of Months | 0.952442E+09 | 0.508780E+09 | 0.149100E+10 | 0.468824E+09 | 0.845840E+09 | 0.00 | 0.00 |
Maximum of Months | 0.715133E+10 | 0.412991E+10 | 0.507163E+10 | 0.234783E+10 | 0.285807E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 1.17 | -0.7 | -4.4 | 5.65 | -10.4 | 36.91 | 88.07 | 0.05 |
February | -0.2 | -2.6 | -7.5 | 5.07 | -13.4 | 46.98 | 136.68 | 0.04 |
March | 5.59 | 3.43 | 0.29 | 5.58 | -4.1 | 68.24 | 153.73 | 0.03 |
April | 10.94 | 8.00 | 4.75 | 4.99 | 0.53 | 82.64 | 161.98 | 0.05 |
May | 16.05 | 12.31 | 9.14 | 4.42 | 7.77 | 109.28 | 173.60 | 0.03 |
June | 21.71 | 18.08 | 15.84 | 4.92 | 13.23 | 112.36 | 186.51 | 0.01 |
July | 25.05 | 21.76 | 20.26 | 4.06 | 17.39 | 114.46 | 172.96 | 0.02 |
August | 24.79 | 19.84 | 17.14 | 4.19 | 14.42 | 95.56 | 226.16 | 0.00 |
September | 19.96 | 15.96 | 13.24 | 3.91 | 10.59 | 73.65 | 166.08 | 0.03 |
October | 14.02 | 11.03 | 7.95 | 4.86 | 2.64 | 61.34 | 179.75 | 0.00 |
November | 7.31 | 4.98 | 2.14 | 5.60 | -4.0 | 48.23 | 90.71 | 0.03 |
December | 3.33 | 0.91 | -2.8 | 5.64 | -8.5 | 30.23 | 98.59 | 0.04 |
Annual Sum or Average | 12.55 | 9.49 | 6.43 | 4.91 | 2.28 | 73.48 | 153.05 | 0.03 |
Minimum of Months | -0.2 | -2.6 | -7.5 | 3.91 | -13.4 | 30.23 | 88.07 | 0.00 |
Maximum of Months | 25.05 | 21.76 | 20.26 | 5.65 | 17.39 | 114.46 | 226.16 | 0.05 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.20 | 24-JAN-12:20 | 11.81 | 11.50 | 1.00 | 8.15 | 93.67 | 0.00 |
February | 10.00 | 20-FEB-11:00 | 4.36 | -3.3 | 2.60 | -3.9 | 151.50 | 540.00 |
March | 22.20 | 27-MAR-15:00 | 16.34 | 12.80 | 6.70 | 11.65 | 136.50 | 590.00 |
April | 26.70 | 07-APR-12:00 | 16.40 | 9.40 | 6.20 | 11.65 | 179.00 | 713.50 |
May | 30.00 | 30-MAY-12:00 | 18.00 | 10.60 | 5.20 | 17.39 | 233.50 | 730.00 |
June | 36.70 | 19-JUN-11:00 | 24.28 | 19.40 | 5.20 | 24.83 | 185.00 | 771.50 |
July | 33.90 | 07-JUL-11:00 | 23.31 | 18.90 | 3.60 | 23.82 | 331.00 | 570.00 |
August | 33.90 | 24-AUG-14:00 | 20.23 | 12.80 | 8.80 | 21.61 | 240.00 | 432.00 |
September | 31.10 | 01-SEP-13:00 | 17.34 | 8.30 | 4.60 | 18.46 | 182.00 | 662.00 |
October | 25.00 | 04-OCT-12:00 | 18.54 | 15.00 | 5.20 | 11.27 | 171.50 | 695.00 |
November | 17.80 | 04-NOV-12:20 | 12.57 | 8.50 | 3.60 | 6.15 | 182.50 | 595.67 |
December | 12.20 | 17-DEC-12:20 | 4.65 | -6.1 | 4.27 | -4.7 | 53.17 | 801.67 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.00 | 4.36 | -6.1 | 1.00 | -4.7 | 53.17 | 0.00 | |
Maximum of Months | 36.70 | 24.28 | 19.40 | 8.80 | 24.83 | 331.00 | 801.67 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -12.2 | 02-JAN-04:00 | -13.6 | -19.4 | 2.60 | -30.7 | 0.00 | 0.00 |
February | -13.9 | 06-FEB-02:00 | -15.3 | -22.8 | 7.20 | -34.1 | 0.00 | 0.00 |
March | -5.0 | 23-MAR-03:00 | -7.6 | -14.4 | 1.50 | -23.9 | 0.00 | 0.00 |
April | 2.20 | 01-APR-03:00 | 0.57 | -1.7 | 3.10 | -6.6 | 0.00 | 0.00 |
May | 6.10 | 01-MAY-04:00 | 4.33 | 2.20 | 3.60 | -9.7 | 25.50 | 0.00 |
June | 13.30 | 03-JUN-02:00 | 9.35 | 5.60 | 4.60 | -2.1 | 0.00 | 0.00 |
July | 18.30 | 02-JUL-02:00 | 17.54 | 17.20 | 0.00 | 5.33 | 0.00 | 0.00 |
August | 15.00 | 08-AUG-04:00 | 12.47 | 10.60 | 3.10 | 3.06 | 0.00 | 0.00 |
September | 10.00 | 24-SEP-05:00 | 8.56 | 7.20 | 2.60 | -3.4 | 18.50 | 158.50 |
October | 2.20 | 09-OCT-03:00 | 1.71 | 1.10 | 0.00 | -13.7 | 0.00 | 0.00 |
November | -4.4 | 24-NOV-05:00 | -6.2 | -10.0 | 1.50 | -19.7 | 0.00 | 0.00 |
December | -8.3 | 31-DEC-23:00 | -10.6 | -18.9 | 9.30 | -26.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -13.9 | -15.3 | -22.8 | 0.00 | -34.1 | 0.00 | 0.00 | |
Maximum of Months | 18.30 | 17.54 | 17.20 | 9.30 | 5.33 | 25.50 | 158.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 11.93 | 24-JAN-11:00 | 12.20 | 11.70 | 1.50 | 8.15 | 103.00 | 0.00 |
February | 6.67 | 28-FEB-09:00 | 7.20 | 6.10 | 4.10 | 2.01 | 101.50 | 0.00 |
March | 16.99 | 27-MAR-12:00 | 20.60 | 15.00 | 3.60 | 10.50 | 295.50 | 565.50 |
April | 17.70 | 09-APR-10:00 | 21.70 | 15.60 | 4.10 | 14.84 | 244.50 | 281.50 |
May | 20.43 | 31-MAY-12:00 | 26.10 | 17.80 | 4.10 | 17.03 | 214.00 | 772.00 |
June | 24.96 | 15-JUN-11:00 | 31.10 | 22.80 | 5.20 | 22.47 | 380.00 | 460.00 |
July | 26.10 | 08-JUL-11:00 | 32.20 | 23.90 | 5.20 | 22.47 | 354.00 | 501.50 |
August | 25.84 | 03-AUG-13:00 | 30.00 | 24.40 | 6.20 | 20.57 | 298.00 | 500.00 |
September | 23.57 | 07-SEP-13:00 | 27.20 | 22.20 | 6.20 | 15.02 | 148.00 | 730.50 |
October | 19.76 | 25-OCT-10:00 | 25.00 | 17.20 | 7.70 | 14.84 | 189.00 | 308.50 |
November | 16.10 | 10-NOV-07:00 | 16.10 | 16.10 | 8.20 | 12.98 | 71.50 | 0.00 |
December | 10.26 | 25-DEC-08:00 | 10.60 | 10.00 | 3.60 | 6.15 | 43.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.67 | 7.20 | 6.10 | 1.50 | 2.01 | 43.00 | 0.00 | |
Maximum of Months | 26.10 | 32.20 | 24.40 | 8.20 | 22.47 | 380.00 | 772.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 11.70 | 18-JAN-15:00 | 12.20 | 11.93 | 14.90 | 8.15 | 22.00 | 2.00 |
February | 6.10 | 28-FEB-10:20 | 7.03 | 6.58 | 3.43 | 1.87 | 109.83 | 0.00 |
March | 15.00 | 27-MAR-12:20 | 18.00 | 16.18 | 3.93 | 10.11 | 271.83 | 611.17 |
April | 15.60 | 09-APR-10:00 | 21.70 | 17.70 | 4.10 | 14.84 | 244.50 | 281.50 |
May | 18.00 | 18-MAY-09:00 | 18.00 | 18.00 | 4.60 | 15.39 | 265.50 | 12.00 |
June | 22.80 | 15-JUN-11:00 | 31.10 | 24.96 | 5.20 | 22.47 | 380.00 | 460.00 |
July | 24.40 | 09-JUL-07:00 | 27.20 | 25.17 | 2.10 | 15.39 | 195.00 | 504.00 |
August | 25.00 | 03-AUG-19:00 | 26.10 | 25.32 | 5.70 | 19.35 | 0.00 | 0.00 |
September | 22.20 | 07-SEP-13:00 | 27.20 | 23.57 | 6.20 | 15.02 | 148.00 | 730.50 |
October | 18.30 | 05-OCT-18:00 | 19.40 | 18.62 | 7.70 | 6.55 | 0.00 | 0.00 |
November | 16.10 | 10-NOV-07:00 | 16.10 | 16.10 | 8.20 | 12.98 | 71.50 | 0.00 |
December | 10.00 | 25-DEC-08:00 | 10.60 | 10.26 | 3.60 | 6.15 | 43.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.10 | 7.03 | 6.58 | 2.10 | 1.87 | 0.00 | 0.00 | |
Maximum of Months | 25.00 | 31.10 | 25.32 | 14.90 | 22.47 | 380.00 | 730.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 10.03 | 13.58 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 9.54 | 21.42 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 10.65 | 30.29 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 13.15 | 37.02 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 16.36 | 45.86 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 19.42 | 49.74 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 21.50 | 48.12 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 22.05 | 49.54 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 20.89 | 34.71 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 18.36 | 29.93 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 15.14 | 17.00 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 12.10 | 12.41 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 15.80 | 32.53 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 9.54 | 12.41 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 22.05 | 49.74 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.400213E+11 | -0.389835E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.103779E+10 | 58.98 | 0.00 | 0.00 |
February | 0.367126E+11 | -0.357798E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -932800943.3 | 58.97 | 0.00 | 0.00 |
March | 0.421638E+11 | -0.411338E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102991E+10 | 58.97 | 0.00 | 0.00 |
April | 0.363754E+11 | -0.353826E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -992821672.5 | 58.98 | 0.00 | 0.00 |
May | 0.362000E+11 | -0.351743E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102565E+10 | 58.97 | 0.00 | 0.00 |
June | 0.333262E+11 | -0.323337E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -992485768.9 | 58.98 | 0.00 | 0.00 |
July | 0.301402E+11 | -0.291203E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101988E+10 | 58.98 | 0.00 | 0.00 |
August | 0.324649E+11 | -0.314413E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102367E+10 | 58.98 | 0.00 | 0.00 |
September | 0.304119E+11 | -0.294234E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -988467184.3 | 58.97 | 0.00 | 0.00 |
October | 0.333860E+11 | -0.323660E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101998E+10 | 58.97 | 0.00 | 0.00 |
November | 0.352379E+11 | -0.342486E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -989280199.0 | 58.98 | 0.00 | 0.00 |
December | 0.374546E+11 | -0.364306E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102401E+10 | 58.97 | 0.00 | 0.00 |
Annual Sum or Average | 0.423895E+12 | -0.411818E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.120768E+11 | 58.97 | 0.00 | 0.00 |
Minimum of Months | 0.301402E+11 | -0.411338E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.103779E+10 | 58.97 | 0.00 | 0.00 |
Maximum of Months | 0.421638E+11 | -0.291203E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -932800943.3 | 58.98 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.64 | 0.61 | 01-JAN-07:49 | 5412.94 | 32.85 | 169.00 | 226.00 | 2818.79 | 33.17 | 182.17 | 185.33 |
February | 216.00 | 0.63 | 0.61 | 01-FEB-07:40 | 8003.29 | 36.15 | 203.17 | 249.83 | 1659.65 | 27.10 | 179.33 | 224.50 |
March | 275.00 | 0.64 | 0.61 | 01-MAR-06:00 | 2858.04 | 22.65 | 90.17 | 309.50 | 1204.34 | 21.16 | 149.00 | 255.00 |
April | 261.17 | 0.63 | 0.61 | 01-APR-06:19 | 1624.56 | 17.47 | 0.00 | 328.17 | 936.92 | 20.45 | 109.33 | 278.33 |
May | 372.00 | 0.64 | 0.61 | 01-MAY-05:40 | 1432.11 | 17.34 | 0.00 | 380.17 | 788.81 | 20.25 | 157.33 | 318.50 |
June | 351.83 | 0.63 | 0.61 | 01-JUN-05:19 | 1363.28 | 17.26 | 0.00 | 368.33 | 763.77 | 20.26 | 135.00 | 318.17 |
July | 365.17 | 0.63 | 0.61 | 01-JUL-05:30 | 1507.66 | 17.58 | 0.00 | 375.33 | 824.66 | 20.57 | 176.67 | 323.00 |
August | 389.17 | 0.64 | 0.61 | 01-AUG-05:00 | 1658.02 | 17.58 | 0.00 | 360.50 | 940.20 | 20.53 | 185.50 | 320.33 |
September | 285.33 | 0.63 | 0.61 | 01-SEP-06:10 | 3140.82 | 19.98 | 29.50 | 312.33 | 1109.81 | 20.85 | 146.83 | 272.50 |
October | 305.50 | 0.63 | 0.61 | 01-OCT-14:39 | 8762.56 | 35.02 | 278.50 | 299.17 | 1558.74 | 22.93 | 241.17 | 276.33 |
November | 240.83 | 0.63 | 0.61 | 01-NOV-06:00 | 5455.65 | 33.83 | 217.00 | 248.83 | 1805.64 | 28.52 | 213.83 | 222.50 |
December | 211.17 | 0.64 | 0.61 | 01-DEC-07:40 | 5060.23 | 33.64 | 178.83 | 230.17 | 4634.15 | 37.63 | 197.67 | 198.17 |
Annual Sum or Average | 3472.67 | 0.63 | 3508.15 | 23.78 | 1166.17 | 3688.33 | 1420.29 | 23.49 | 2073.83 | 3192.67 | ||
Minimum of Months | 199.50 | 0.63 | 0.61 | 1363.28 | 17.26 | 0.00 | 226.00 | 763.77 | 20.25 | 109.33 | 185.33 | |
Maximum of Months | 389.17 | 0.64 | 0.61 | 8762.56 | 36.15 | 278.50 | 380.17 | 4634.15 | 37.63 | 241.17 | 323.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.65 | 0.61 | 01-JAN-07:49 | 1616.17 | 19.15 | 60.33 | 202.00 | 856.60 | 18.50 | 40.00 | 136.00 |
February | 216.00 | 0.64 | 0.61 | 01-FEB-07:40 | 2184.95 | 19.32 | 61.33 | 229.67 | 1339.44 | 20.64 | 58.50 | 177.50 |
March | 275.00 | 0.65 | 0.61 | 01-MAR-06:49 | 2303.55 | 17.27 | 56.67 | 300.67 | 1320.74 | 17.15 | 38.50 | 227.33 |
April | 261.17 | 0.63 | 0.61 | 01-APR-05:00 | 3207.42 | 15.80 | 38.83 | 326.33 | 1184.93 | 14.54 | 0.00 | 273.00 |
May | 372.00 | 0.64 | 0.61 | 01-MAY-05:40 | 2523.34 | 13.38 | 0.00 | 382.83 | 1387.95 | 14.60 | 0.00 | 323.50 |
June | 351.83 | 0.63 | 0.61 | 01-JUN-04:00 | 2318.97 | 13.36 | 0.00 | 372.83 | 1263.45 | 14.63 | 0.00 | 333.50 |
July | 365.17 | 0.63 | 0.61 | 01-JUL-04:00 | 2324.94 | 13.78 | 1.83 | 382.00 | 1268.28 | 14.94 | 0.00 | 334.17 |
August | 389.17 | 0.64 | 0.61 | 01-AUG-05:40 | 3200.07 | 16.02 | 57.67 | 359.67 | 1287.99 | 14.81 | 0.00 | 327.00 |
September | 285.33 | 0.64 | 0.61 | 01-SEP-05:49 | 2645.30 | 17.54 | 61.33 | 308.00 | 1158.05 | 15.20 | 5.50 | 260.33 |
October | 305.50 | 0.64 | 0.61 | 01-OCT-14:39 | 2384.23 | 18.88 | 74.17 | 279.83 | 1283.71 | 18.73 | 50.17 | 240.00 |
November | 240.83 | 0.64 | 0.61 | 01-NOV-06:49 | 1511.88 | 17.82 | 52.00 | 230.67 | 830.60 | 18.82 | 46.17 | 174.50 |
December | 211.17 | 0.66 | 0.61 | 01-DEC-07:40 | 1493.45 | 18.86 | 64.17 | 196.83 | 898.54 | 20.24 | 59.00 | 123.17 |
Annual Sum or Average | 3472.67 | 0.64 | 2383.50 | 16.37 | 528.33 | 3571.33 | 1200.94 | 16.51 | 297.83 | 2930.00 | ||
Minimum of Months | 199.50 | 0.63 | 0.61 | 1493.45 | 13.36 | 0.00 | 196.83 | 830.60 | 14.54 | 0.00 | 123.17 | |
Maximum of Months | 389.17 | 0.66 | 0.61 | 3207.42 | 19.32 | 74.17 | 382.83 | 1387.95 | 20.64 | 59.00 | 334.17 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.66 | 0.61 | 01-JAN-08:30 | 497.40 | 0.00 | 0.00 | 175.67 | 303.69 | 0.00 | 0.00 | 71.67 |
February | 216.00 | 0.65 | 0.61 | 01-FEB-08:30 | 535.18 | 0.00 | 0.00 | 208.33 | 348.56 | 0.00 | 0.00 | 117.50 |
March | 275.00 | 0.65 | 0.61 | 01-MAR-07:10 | 715.40 | 0.00 | 0.00 | 296.33 | 445.15 | 0.00 | 0.00 | 198.00 |
April | 261.17 | 0.63 | 0.61 | 01-APR-06:19 | 805.23 | 0.00 | 0.00 | 332.67 | 502.72 | 0.00 | 0.00 | 256.17 |
May | 372.00 | 0.63 | 0.61 | 01-MAY-05:40 | 1048.62 | 0.00 | 0.00 | 393.83 | 597.21 | 0.00 | 0.00 | 332.00 |
June | 351.83 | 0.62 | 0.61 | 01-JUN-04:00 | 1177.00 | 0.00 | 0.00 | 390.83 | 646.75 | 0.00 | 0.00 | 351.50 |
July | 365.17 | 0.62 | 0.61 | 01-JUL-04:00 | 1164.95 | 0.00 | 0.00 | 395.83 | 645.43 | 0.00 | 0.00 | 348.00 |
August | 389.17 | 0.63 | 0.61 | 01-AUG-05:49 | 952.05 | 0.00 | 0.00 | 371.50 | 571.82 | 0.00 | 0.00 | 329.67 |
September | 285.33 | 0.64 | 0.61 | 01-SEP-06:10 | 736.72 | 0.00 | 0.00 | 304.50 | 465.23 | 0.00 | 0.00 | 228.00 |
October | 305.50 | 0.64 | 0.61 | 01-OCT-14:39 | 663.30 | 0.00 | 0.00 | 275.67 | 430.43 | 0.00 | 0.00 | 206.67 |
November | 240.83 | 0.65 | 0.61 | 01-NOV-07:19 | 557.23 | 0.00 | 0.00 | 213.67 | 332.28 | 0.00 | 0.00 | 107.67 |
December | 211.17 | 0.68 | 0.61 | 01-DEC-08:20 | 398.81 | 0.00 | 0.00 | 155.83 | 252.27 | 0.00 | 0.00 | 34.67 |
Annual Sum or Average | 3472.67 | 0.64 | 821.63 | 0.00 | 0.00 | 3514.67 | 488.11 | 0.00 | 0.00 | 2581.50 | ||
Minimum of Months | 199.50 | 0.62 | 0.61 | 398.81 | 0.00 | 0.00 | 155.83 | 252.27 | 0.00 | 0.00 | 34.67 | |
Maximum of Months | 389.17 | 0.68 | 0.61 | 1177.00 | 0.00 | 0.00 | 395.83 | 646.75 | 0.00 | 0.00 | 351.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.65 | 0.61 | 01-JAN-08:30 | 1547.48 | 19.01 | 57.17 | 205.00 | 902.44 | 20.31 | 52.17 | 138.00 |
February | 216.00 | 0.64 | 0.61 | 01-FEB-08:39 | 1790.46 | 18.80 | 56.17 | 228.83 | 910.04 | 18.30 | 36.17 | 173.50 |
March | 275.00 | 0.64 | 0.61 | 01-MAR-07:19 | 2483.05 | 18.35 | 69.67 | 304.50 | 1459.11 | 18.06 | 47.50 | 237.33 |
April | 261.17 | 0.64 | 0.61 | 01-APR-07:19 | 3016.20 | 15.58 | 36.00 | 324.83 | 1154.12 | 14.50 | 0.00 | 275.50 |
May | 372.00 | 0.63 | 0.61 | 01-MAY-05:00 | 2783.95 | 13.44 | 0.00 | 382.83 | 1205.73 | 14.77 | 1.83 | 325.67 |
June | 351.83 | 0.63 | 0.61 | 01-JUN-05:40 | 2620.36 | 13.55 | 0.00 | 378.00 | 1431.61 | 16.94 | 43.00 | 323.17 |
July | 365.17 | 0.63 | 0.61 | 01-JUL-05:40 | 2464.92 | 13.89 | 3.50 | 382.00 | 1329.62 | 14.98 | 0.00 | 330.00 |
August | 389.17 | 0.64 | 0.61 | 01-AUG-05:00 | 3261.84 | 15.87 | 54.33 | 360.17 | 1385.52 | 14.81 | 0.00 | 327.83 |
September | 285.33 | 0.64 | 0.61 | 01-SEP-06:30 | 2514.00 | 16.34 | 45.67 | 307.67 | 1354.43 | 15.32 | 5.50 | 261.00 |
October | 305.50 | 0.63 | 0.61 | 01-OCT-14:39 | 2672.05 | 19.63 | 83.50 | 292.83 | 1139.83 | 19.22 | 53.17 | 256.00 |
November | 240.83 | 0.64 | 0.61 | 01-NOV-07:19 | 1353.31 | 18.87 | 68.00 | 233.33 | 700.68 | 18.31 | 43.50 | 170.17 |
December | 211.17 | 0.66 | 0.61 | 01-DEC-08:30 | 1273.61 | 19.09 | 67.33 | 198.50 | 677.65 | 18.21 | 43.67 | 125.67 |
Annual Sum or Average | 3472.67 | 0.64 | 2425.11 | 16.48 | 541.33 | 3598.50 | 1181.44 | 16.69 | 326.50 | 2943.83 | ||
Minimum of Months | 199.50 | 0.63 | 0.61 | 1273.61 | 13.44 | 0.00 | 198.50 | 677.65 | 14.50 | 0.00 | 125.67 | |
Maximum of Months | 389.17 | 0.66 | 0.61 | 3261.84 | 19.63 | 83.50 | 382.83 | 1459.11 | 20.31 | 53.17 | 330.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.64 | 0.61 | 01-JAN-07:00 | 5366.84 | 31.74 | 169.00 | 224.50 | 2858.54 | 31.31 | 143.83 | 186.33 |
February | 216.00 | 0.63 | 0.61 | 01-FEB-07:40 | 7968.37 | 35.58 | 202.50 | 248.50 | 1709.88 | 23.29 | 80.00 | 225.50 |
March | 275.00 | 0.64 | 0.61 | 01-MAR-06:00 | 2869.51 | 18.16 | 89.67 | 311.67 | 1248.86 | 16.89 | 4.33 | 258.33 |
April | 261.17 | 0.64 | 0.61 | 01-APR-06:19 | 1603.13 | 11.66 | 0.00 | 326.17 | 970.84 | 16.52 | 0.00 | 279.83 |
May | 372.00 | 0.64 | 0.61 | 01-MAY-05:40 | 1404.22 | 11.71 | 0.00 | 378.83 | 812.95 | 16.40 | 0.00 | 325.00 |
June | 351.83 | 0.63 | 0.61 | 01-JUN-05:30 | 1337.01 | 11.68 | 0.00 | 366.33 | 786.80 | 16.45 | 0.00 | 321.17 |
July | 365.17 | 0.63 | 0.61 | 01-JUL-05:30 | 1476.18 | 11.86 | 0.00 | 373.50 | 848.84 | 16.63 | 0.00 | 324.67 |
August | 389.17 | 0.64 | 0.61 | 01-AUG-05:00 | 1631.40 | 12.04 | 0.00 | 358.50 | 971.69 | 16.78 | 0.00 | 322.33 |
September | 285.33 | 0.64 | 0.61 | 01-SEP-06:10 | 3115.37 | 14.58 | 29.50 | 311.00 | 1151.37 | 16.66 | 0.00 | 274.00 |
October | 305.50 | 0.63 | 0.61 | 01-OCT-14:39 | 8720.04 | 34.31 | 278.17 | 298.67 | 1683.09 | 18.70 | 19.33 | 277.33 |
November | 240.83 | 0.63 | 0.61 | 01-NOV-06:00 | 5384.43 | 32.62 | 213.50 | 247.50 | 2227.31 | 27.48 | 136.83 | 224.00 |
December | 211.17 | 0.64 | 0.61 | 01-DEC-07:40 | 4834.34 | 29.38 | 155.00 | 227.83 | 4670.08 | 36.83 | 195.67 | 199.17 |
Annual Sum or Average | 3472.67 | 0.63 | 3466.17 | 19.65 | 1137.33 | 3673.00 | 1488.55 | 20.04 | 580.00 | 3217.67 | ||
Minimum of Months | 199.50 | 0.63 | 0.61 | 1337.01 | 11.66 | 0.00 | 224.50 | 786.80 | 16.40 | 0.00 | 186.33 | |
Maximum of Months | 389.17 | 0.64 | 0.61 | 8720.04 | 35.58 | 278.17 | 378.83 | 4670.08 | 36.83 | 195.67 | 325.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.65 | 0.61 | 01-JAN-07:49 | 1609.90 | 17.20 | 60.33 | 201.33 | 875.16 | 16.44 | 40.00 | 138.67 |
February | 216.00 | 0.64 | 0.61 | 01-FEB-07:40 | 2180.36 | 17.15 | 61.33 | 228.83 | 1363.99 | 18.84 | 58.50 | 181.33 |
March | 275.00 | 0.65 | 0.61 | 01-MAR-06:49 | 2306.52 | 14.97 | 56.83 | 300.00 | 1349.76 | 15.10 | 38.50 | 231.17 |
April | 261.17 | 0.63 | 0.61 | 01-APR-06:10 | 3210.86 | 12.98 | 38.83 | 324.83 | 1219.34 | 11.97 | 0.00 | 276.83 |
May | 372.00 | 0.64 | 0.61 | 01-MAY-05:40 | 2497.31 | 10.00 | 0.00 | 382.00 | 1420.07 | 12.23 | 0.00 | 328.17 |
June | 351.83 | 0.63 | 0.61 | 01-JUN-04:00 | 2212.92 | 10.01 | 0.00 | 372.33 | 1295.48 | 12.31 | 0.00 | 336.00 |
July | 365.17 | 0.63 | 0.61 | 01-JUL-04:00 | 2306.18 | 10.39 | 1.83 | 381.33 | 1300.94 | 12.56 | 0.00 | 337.83 |
August | 389.17 | 0.64 | 0.61 | 01-AUG-05:40 | 3193.06 | 13.31 | 57.67 | 359.33 | 1321.63 | 12.35 | 0.00 | 330.67 |
September | 285.33 | 0.64 | 0.61 | 01-SEP-05:49 | 2650.70 | 15.09 | 61.33 | 306.00 | 1190.93 | 12.65 | 5.50 | 263.50 |
October | 305.50 | 0.64 | 0.61 | 01-OCT-14:39 | 2376.94 | 16.65 | 74.17 | 279.17 | 1312.93 | 16.58 | 50.17 | 243.67 |
November | 240.83 | 0.64 | 0.61 | 01-NOV-06:49 | 1504.57 | 15.35 | 52.00 | 229.50 | 850.71 | 16.64 | 46.17 | 177.50 |
December | 211.17 | 0.66 | 0.61 | 01-DEC-07:40 | 1491.21 | 16.87 | 64.17 | 196.33 | 915.43 | 18.44 | 59.33 | 127.67 |
Annual Sum or Average | 3472.67 | 0.64 | 2366.22 | 13.68 | 528.50 | 3561.00 | 1230.01 | 14.25 | 298.17 | 2973.00 | ||
Minimum of Months | 199.50 | 0.63 | 0.61 | 1491.21 | 10.00 | 0.00 | 196.33 | 850.71 | 11.97 | 0.00 | 127.67 | |
Maximum of Months | 389.17 | 0.66 | 0.61 | 3210.86 | 17.20 | 74.17 | 382.00 | 1420.07 | 18.84 | 59.33 | 337.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.66 | 0.61 | 01-JAN-08:30 | 485.63 | 0.00 | 0.00 | 169.83 | 311.14 | 0.00 | 0.00 | 77.50 |
February | 216.00 | 0.65 | 0.61 | 01-FEB-08:30 | 524.38 | 0.00 | 0.00 | 205.50 | 357.73 | 0.00 | 0.00 | 123.00 |
March | 275.00 | 0.65 | 0.61 | 01-MAR-07:10 | 702.31 | 0.00 | 0.00 | 294.83 | 457.82 | 0.00 | 0.00 | 202.00 |
April | 261.17 | 0.63 | 0.61 | 01-APR-06:19 | 792.63 | 0.00 | 0.00 | 331.00 | 517.75 | 0.00 | 0.00 | 262.83 |
May | 372.00 | 0.63 | 0.61 | 01-MAY-05:40 | 1029.81 | 0.00 | 0.00 | 392.50 | 614.94 | 0.00 | 0.00 | 335.83 |
June | 351.83 | 0.63 | 0.61 | 01-JUN-04:00 | 1158.39 | 0.00 | 0.00 | 388.83 | 673.49 | 0.00 | 0.00 | 357.83 |
July | 365.17 | 0.62 | 0.61 | 01-JUL-04:00 | 1145.11 | 0.00 | 0.00 | 393.50 | 664.00 | 0.00 | 0.00 | 350.17 |
August | 389.17 | 0.63 | 0.61 | 01-AUG-05:49 | 936.52 | 0.00 | 0.00 | 370.33 | 588.45 | 0.00 | 0.00 | 332.17 |
September | 285.33 | 0.64 | 0.61 | 01-SEP-06:10 | 724.28 | 0.00 | 0.00 | 302.17 | 478.73 | 0.00 | 0.00 | 233.67 |
October | 305.50 | 0.64 | 0.61 | 01-OCT-14:39 | 649.56 | 0.00 | 0.00 | 273.50 | 441.55 | 0.00 | 0.00 | 211.50 |
November | 240.83 | 0.65 | 0.61 | 01-NOV-07:19 | 544.44 | 0.00 | 0.00 | 210.17 | 340.65 | 0.00 | 0.00 | 113.67 |
December | 211.17 | 0.68 | 0.61 | 01-DEC-08:30 | 389.14 | 0.00 | 0.00 | 150.17 | 258.23 | 0.00 | 0.00 | 41.83 |
Annual Sum or Average | 3472.67 | 0.64 | 806.86 | 0.00 | 0.00 | 3482.33 | 502.70 | 0.00 | 0.00 | 2642.00 | ||
Minimum of Months | 199.50 | 0.62 | 0.61 | 389.14 | 0.00 | 0.00 | 150.17 | 258.23 | 0.00 | 0.00 | 41.83 | |
Maximum of Months | 389.17 | 0.68 | 0.61 | 1158.39 | 0.00 | 0.00 | 393.50 | 673.49 | 0.00 | 0.00 | 357.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.65 | 0.61 | 01-JAN-08:30 | 1529.81 | 16.85 | 56.17 | 203.50 | 920.45 | 18.42 | 52.33 | 141.00 |
February | 216.00 | 0.64 | 0.61 | 01-FEB-08:39 | 1568.81 | 14.13 | 37.00 | 228.00 | 934.77 | 16.11 | 36.17 | 178.00 |
March | 275.00 | 0.64 | 0.61 | 01-MAR-07:19 | 2480.50 | 16.04 | 68.67 | 303.83 | 1489.52 | 16.01 | 47.67 | 239.33 |
April | 261.17 | 0.64 | 0.61 | 01-APR-07:19 | 2805.74 | 12.74 | 36.00 | 324.17 | 1187.68 | 11.96 | 0.00 | 278.83 |
May | 372.00 | 0.63 | 0.61 | 01-MAY-05:00 | 2766.14 | 10.05 | 0.00 | 382.50 | 1237.24 | 12.40 | 1.83 | 330.67 |
June | 351.83 | 0.63 | 0.61 | 01-JUN-05:40 | 2597.59 | 10.08 | 0.00 | 377.33 | 1467.95 | 14.96 | 43.00 | 326.33 |
July | 365.17 | 0.63 | 0.61 | 01-JUL-05:40 | 2444.31 | 10.48 | 3.50 | 381.00 | 1363.34 | 12.58 | 0.00 | 333.83 |
August | 389.17 | 0.64 | 0.61 | 01-AUG-05:00 | 3255.84 | 13.11 | 54.33 | 359.83 | 1419.94 | 12.34 | 0.00 | 329.50 |
September | 285.33 | 0.64 | 0.61 | 01-SEP-06:30 | 2517.22 | 13.64 | 45.67 | 305.67 | 1385.53 | 12.79 | 5.50 | 264.67 |
October | 305.50 | 0.63 | 0.61 | 01-OCT-14:39 | 2668.25 | 17.42 | 83.50 | 292.17 | 1169.29 | 17.05 | 53.17 | 258.00 |
November | 240.83 | 0.64 | 0.61 | 01-NOV-07:19 | 1332.24 | 16.40 | 64.83 | 232.83 | 717.63 | 16.11 | 43.50 | 173.33 |
December | 211.17 | 0.66 | 0.61 | 01-DEC-08:30 | 1101.46 | 14.43 | 45.67 | 196.67 | 693.98 | 16.17 | 43.67 | 129.67 |
Annual Sum or Average | 3472.67 | 0.64 | 2375.23 | 13.41 | 495.33 | 3587.50 | 1210.72 | 14.43 | 326.83 | 2983.17 | ||
Minimum of Months | 199.50 | 0.63 | 0.61 | 1101.46 | 10.05 | 0.00 | 196.67 | 693.98 | 11.96 | 0.00 | 129.67 | |
Maximum of Months | 389.17 | 0.66 | 0.61 | 3255.84 | 17.42 | 83.50 | 382.50 | 1489.52 | 18.42 | 53.17 | 333.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.64 | 0.61 | 01-JAN-07:00 | 5365.46 | 31.72 | 169.00 | 224.50 | 2859.86 | 31.30 | 143.83 | 186.33 |
February | 216.00 | 0.63 | 0.61 | 01-FEB-07:40 | 7967.46 | 35.56 | 202.50 | 248.50 | 1711.28 | 23.27 | 80.00 | 225.83 |
March | 275.00 | 0.64 | 0.61 | 01-MAR-06:00 | 2870.01 | 18.13 | 89.67 | 311.67 | 1250.21 | 16.87 | 4.33 | 258.50 |
April | 261.17 | 0.64 | 0.61 | 01-APR-06:19 | 1603.79 | 11.62 | 0.00 | 326.17 | 971.85 | 16.51 | 0.00 | 279.83 |
May | 372.00 | 0.64 | 0.61 | 01-MAY-05:40 | 1404.91 | 11.67 | 0.00 | 379.00 | 813.90 | 16.38 | 0.00 | 325.17 |
June | 351.83 | 0.63 | 0.61 | 01-JUN-05:30 | 1337.60 | 11.64 | 0.00 | 366.33 | 787.66 | 16.43 | 0.00 | 321.50 |
July | 365.17 | 0.63 | 0.61 | 01-JUL-05:30 | 1476.94 | 11.82 | 0.00 | 373.67 | 849.83 | 16.61 | 0.00 | 325.17 |
August | 389.17 | 0.64 | 0.61 | 01-AUG-05:00 | 1632.11 | 12.00 | 0.00 | 358.50 | 972.73 | 16.76 | 0.00 | 322.33 |
September | 285.33 | 0.64 | 0.61 | 01-SEP-06:10 | 3116.04 | 14.54 | 29.50 | 311.00 | 1152.60 | 16.64 | 0.00 | 274.00 |
October | 305.50 | 0.63 | 0.61 | 01-OCT-14:39 | 8719.66 | 34.30 | 278.17 | 298.67 | 1684.75 | 18.68 | 19.33 | 277.33 |
November | 240.83 | 0.63 | 0.61 | 01-NOV-06:00 | 5383.21 | 32.61 | 213.50 | 247.50 | 2228.86 | 27.47 | 136.83 | 224.00 |
December | 211.17 | 0.64 | 0.61 | 01-DEC-07:40 | 4804.08 | 28.97 | 152.00 | 227.67 | 4671.09 | 36.83 | 195.67 | 199.17 |
Annual Sum or Average | 3472.67 | 0.63 | 3464.52 | 19.60 | 1134.33 | 3673.17 | 1489.72 | 20.02 | 580.00 | 3219.17 | ||
Minimum of Months | 199.50 | 0.63 | 0.61 | 1337.60 | 11.62 | 0.00 | 224.50 | 787.66 | 16.38 | 0.00 | 186.33 | |
Maximum of Months | 389.17 | 0.64 | 0.61 | 8719.66 | 35.56 | 278.17 | 379.00 | 4671.09 | 36.83 | 195.67 | 325.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.65 | 0.61 | 01-JAN-07:49 | 1609.46 | 17.19 | 60.33 | 201.33 | 875.71 | 16.43 | 40.00 | 138.67 |
February | 216.00 | 0.64 | 0.61 | 01-FEB-07:40 | 2179.79 | 17.14 | 61.33 | 228.67 | 1364.53 | 18.83 | 58.50 | 181.67 |
March | 275.00 | 0.65 | 0.61 | 01-MAR-06:49 | 2305.87 | 14.96 | 56.83 | 300.00 | 1350.52 | 15.09 | 38.50 | 231.17 |
April | 261.17 | 0.63 | 0.61 | 01-APR-06:10 | 3210.59 | 12.96 | 38.83 | 324.83 | 1220.17 | 11.96 | 0.00 | 277.33 |
May | 372.00 | 0.64 | 0.61 | 01-MAY-05:40 | 2497.32 | 9.99 | 0.00 | 382.00 | 1421.08 | 12.22 | 0.00 | 328.33 |
June | 351.83 | 0.63 | 0.61 | 01-JUN-04:00 | 2212.91 | 9.99 | 0.00 | 372.33 | 1296.41 | 12.30 | 0.00 | 336.00 |
July | 365.17 | 0.63 | 0.61 | 01-JUL-04:00 | 2306.33 | 10.38 | 1.83 | 381.33 | 1302.00 | 12.55 | 0.00 | 337.83 |
August | 389.17 | 0.64 | 0.61 | 01-AUG-05:40 | 3192.93 | 13.30 | 57.67 | 359.33 | 1322.58 | 12.34 | 0.00 | 330.67 |
September | 285.33 | 0.64 | 0.61 | 01-SEP-05:49 | 2650.32 | 15.07 | 61.33 | 305.83 | 1191.71 | 12.64 | 5.50 | 263.50 |
October | 305.50 | 0.64 | 0.61 | 01-OCT-14:39 | 2376.23 | 16.64 | 74.17 | 279.17 | 1313.65 | 16.57 | 50.17 | 243.67 |
November | 240.83 | 0.64 | 0.61 | 01-NOV-06:49 | 1504.20 | 15.34 | 52.00 | 229.33 | 848.68 | 16.46 | 44.83 | 177.17 |
December | 211.17 | 0.66 | 0.61 | 01-DEC-07:40 | 1490.77 | 16.86 | 64.17 | 196.33 | 835.44 | 16.14 | 42.67 | 125.33 |
Annual Sum or Average | 3472.67 | 0.64 | 2365.94 | 13.67 | 528.50 | 3560.50 | 1225.74 | 14.09 | 280.17 | 2971.33 | ||
Minimum of Months | 199.50 | 0.63 | 0.61 | 1490.77 | 9.99 | 0.00 | 196.33 | 835.44 | 11.96 | 0.00 | 125.33 | |
Maximum of Months | 389.17 | 0.66 | 0.61 | 3210.59 | 17.19 | 74.17 | 382.00 | 1421.08 | 18.83 | 58.50 | 337.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.66 | 0.61 | 01-JAN-08:30 | 485.52 | 0.00 | 0.00 | 170.00 | 311.41 | 0.00 | 0.00 | 77.83 |
February | 216.00 | 0.65 | 0.61 | 01-FEB-08:30 | 524.13 | 0.00 | 0.00 | 205.67 | 357.96 | 0.00 | 0.00 | 123.17 |
March | 275.00 | 0.65 | 0.61 | 01-MAR-07:10 | 702.18 | 0.00 | 0.00 | 294.83 | 458.19 | 0.00 | 0.00 | 202.17 |
April | 261.17 | 0.63 | 0.61 | 01-APR-06:19 | 792.47 | 0.00 | 0.00 | 331.00 | 518.15 | 0.00 | 0.00 | 263.00 |
May | 372.00 | 0.63 | 0.61 | 01-MAY-05:40 | 1029.87 | 0.00 | 0.00 | 392.50 | 615.56 | 0.00 | 0.00 | 336.00 |
June | 351.83 | 0.63 | 0.61 | 01-JUN-04:00 | 1158.42 | 0.00 | 0.00 | 388.83 | 674.12 | 0.00 | 0.00 | 358.00 |
July | 365.17 | 0.62 | 0.61 | 01-JUL-04:00 | 1145.18 | 0.00 | 0.00 | 393.50 | 664.65 | 0.00 | 0.00 | 350.17 |
August | 389.17 | 0.63 | 0.61 | 01-AUG-05:49 | 936.38 | 0.00 | 0.00 | 370.33 | 588.93 | 0.00 | 0.00 | 332.17 |
September | 285.33 | 0.64 | 0.61 | 01-SEP-06:10 | 724.11 | 0.00 | 0.00 | 302.33 | 479.09 | 0.00 | 0.00 | 234.17 |
October | 305.50 | 0.64 | 0.61 | 01-OCT-14:39 | 649.25 | 0.00 | 0.00 | 273.50 | 441.84 | 0.00 | 0.00 | 211.67 |
November | 240.83 | 0.65 | 0.61 | 01-NOV-07:19 | 544.38 | 0.00 | 0.00 | 210.17 | 340.97 | 0.00 | 0.00 | 113.83 |
December | 211.17 | 0.68 | 0.61 | 01-DEC-08:30 | 388.98 | 0.00 | 0.00 | 150.00 | 258.42 | 0.00 | 0.00 | 42.00 |
Annual Sum or Average | 3472.67 | 0.64 | 806.76 | 0.00 | 0.00 | 3482.67 | 503.13 | 0.00 | 0.00 | 2644.17 | ||
Minimum of Months | 199.50 | 0.62 | 0.61 | 388.98 | 0.00 | 0.00 | 150.00 | 258.42 | 0.00 | 0.00 | 42.00 | |
Maximum of Months | 389.17 | 0.68 | 0.61 | 1158.42 | 0.00 | 0.00 | 393.50 | 674.12 | 0.00 | 0.00 | 358.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.65 | 0.61 | 01-JAN-08:30 | 1529.39 | 16.84 | 56.17 | 203.83 | 844.57 | 16.21 | 36.83 | 138.50 |
February | 216.00 | 0.64 | 0.61 | 01-FEB-08:39 | 1568.29 | 14.11 | 37.00 | 228.00 | 935.34 | 16.11 | 36.17 | 178.00 |
March | 275.00 | 0.64 | 0.61 | 01-MAR-07:19 | 2479.85 | 16.03 | 68.67 | 303.83 | 1490.29 | 16.00 | 47.67 | 239.83 |
April | 261.17 | 0.64 | 0.61 | 01-APR-07:19 | 2805.39 | 12.73 | 36.00 | 324.17 | 1188.52 | 11.95 | 0.00 | 278.83 |
May | 372.00 | 0.63 | 0.61 | 01-MAY-05:00 | 2766.20 | 10.03 | 0.00 | 382.50 | 1238.23 | 12.39 | 1.83 | 330.67 |
June | 351.83 | 0.63 | 0.61 | 01-JUN-05:40 | 2597.56 | 10.07 | 0.00 | 377.33 | 1469.07 | 14.95 | 43.00 | 326.50 |
July | 365.17 | 0.63 | 0.61 | 01-JUL-05:49 | 2444.44 | 10.47 | 3.50 | 381.00 | 1364.44 | 12.57 | 0.00 | 334.17 |
August | 389.17 | 0.64 | 0.61 | 01-AUG-05:00 | 3255.72 | 13.10 | 54.33 | 359.83 | 1420.88 | 12.33 | 0.00 | 329.50 |
September | 285.33 | 0.64 | 0.61 | 01-SEP-06:30 | 2516.81 | 13.62 | 45.67 | 305.50 | 1386.34 | 12.78 | 5.50 | 264.83 |
October | 305.50 | 0.63 | 0.61 | 01-OCT-14:39 | 2667.49 | 17.41 | 83.50 | 292.00 | 1170.03 | 17.04 | 53.17 | 258.00 |
November | 240.83 | 0.64 | 0.61 | 01-NOV-07:19 | 1332.00 | 16.39 | 64.83 | 232.83 | 718.26 | 16.11 | 43.50 | 173.33 |
December | 211.17 | 0.66 | 0.61 | 01-DEC-08:30 | 1101.06 | 14.42 | 45.67 | 196.50 | 694.38 | 16.16 | 43.67 | 129.67 |
Annual Sum or Average | 3472.67 | 0.64 | 2374.95 | 13.40 | 495.33 | 3587.33 | 1207.16 | 14.29 | 311.33 | 2981.83 | ||
Minimum of Months | 199.50 | 0.63 | 0.61 | 1101.06 | 10.03 | 0.00 | 196.50 | 694.38 | 11.95 | 0.00 | 129.67 | |
Maximum of Months | 389.17 | 0.66 | 0.61 | 3255.72 | 17.41 | 83.50 | 382.50 | 1490.29 | 17.04 | 53.17 | 334.17 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.225549E+09 | 26903.76 | 30-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.334247E+09 | 36097.44 | 13-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.304603E+09 | 25564.96 | 23-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 52170126.04 | 11101.34 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 9988412.96 | 10037.71 | 30-MAY-13:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.107357E+09 | 13471.24 | 22-JUN-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 35833800.26 | 8161.29 | 11-JUL-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.129561E+09 | 14630.30 | 24-AUG-18:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 10587846.38 | 8306.57 | 01-SEP-17:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 12548123.97 | 7695.81 | 28-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.168077E+09 | 25239.18 | 24-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.411799E+09 | 25796.01 | 22-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.180232E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 9988412.96 | 7695.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.411799E+09 | 36097.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.925650E+09 | 15073.28 | 30-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.672608E+09 | 15124.91 | 03-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 8579536.41 | 3646.88 | 17-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 18164270.88 | 11695.54 | 22-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 10385148.87 | 5576.37 | 02-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.163539E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.925650E+09 | 15124.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.773533E+09 | 13680.23 | 30-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.519049E+09 | 13773.81 | 03-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 59239250.06 | 13563.94 | 17-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 106441.27 | 50.64 | 22-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 44277494.56 | 13595.53 | 22-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.173687E+09 | 13522.49 | 07-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.156989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.773533E+09 | 13773.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.991201E+09 | 19260.83 | 26-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.625895E+09 | 19342.41 | 15-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 77434954.76 | 19112.77 | 13-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 124979.93 | 202.61 | 22-APR-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 61450014.08 | 19279.15 | 24-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.183669E+09 | 19035.95 | 07-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.193978E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.991201E+09 | 19342.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.309749E+09 | 12582.53 | 02-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 99596850.74 | 12566.08 | 06-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.409346E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.309749E+09 | 12582.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.185308E+11 | 305673.20 | 30-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.145417E+11 | 415877.62 | 13-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.865365E+10 | 282465.67 | 23-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.170644E+10 | 133402.02 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.114491E+09 | 85246.79 | 30-MAY-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.112838E+10 | 150605.20 | 01-JUN-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.377969E+09 | 85429.96 | 11-JUL-16:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.182212E+10 | 114511.09 | 22-AUG-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.149381E+09 | 54164.17 | 01-SEP-17:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.234257E+09 | 95708.03 | 28-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.501667E+10 | 296145.53 | 24-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.125837E+11 | 285292.59 | 22-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.648595E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.114491E+09 | 54164.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.185308E+11 | 415877.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.247827E+11 | 580508.74 | 02-JAN-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.539277E+10 | 579868.59 | 13-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.228662E+09 | 157538.90 | 27-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.159856E+09 | 75955.71 | 26-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.305640E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.247827E+11 | 580508.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.683041E+11 | 132404.03 | 18-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.561124E+11 | 132080.45 | 16-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.173092E+11 | 143276.91 | 30-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.379876E+10 | 143302.39 | 14-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.518620E+09 | 143675.75 | 28-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.168034E+11 | 142448.13 | 13-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.379096E+11 | 132453.51 | 01-DEC-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.200756E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.683041E+11 | 143675.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.447950E+11 | 163439.39 | 09-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.324003E+11 | 162963.76 | 16-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.102191E+11 | 173931.69 | 31-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.324731E+10 | 162538.10 | 21-APR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.287964E+09 | 88232.73 | 28-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.109804E+11 | 173152.07 | 13-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.253482E+11 | 163437.30 | 26-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.127278E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.447950E+11 | 173931.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.418119E+11 | 184196.06 | 23-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.268752E+11 | 183795.24 | 28-FEB-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.802622E+10 | 198287.61 | 31-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.267796E+10 | 183225.89 | 22-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 22630413.26 | 5576.41 | 28-OCT-06:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.760860E+10 | 191565.76 | 13-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.198230E+11 | 183731.78 | 11-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.106846E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.418119E+11 | 198287.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.385415E+11 | 170677.07 | 09-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.287390E+11 | 169737.36 | 13-FEB-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.735276E+10 | 169450.04 | 13-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.183863E+10 | 168601.52 | 03-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.204357E+09 | 45000.19 | 28-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.975337E+10 | 169997.51 | 27-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.206937E+11 | 170007.56 | 11-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.107123E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.385415E+11 | 170677.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.164776E+10 | 35947.83 | 30-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121225E+10 | 46230.27 | 13-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.282101E+09 | 33518.65 | 23-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 98128921.20 | 17682.30 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 31905434.60 | 12873.43 | 30-MAY-13:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 64024185.51 | 14282.95 | 01-JUN-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 46715621.23 | 7142.57 | 11-JUL-16:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 93737170.25 | 18641.35 | 25-AUG-14:47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6797665.66 | 4443.80 | 01-SEP-14:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 38320061.20 | 14120.23 | 28-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.239970E+09 | 34207.08 | 24-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.431640E+09 | 34042.07 | 22-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.419335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 6797665.66 | 4443.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.164776E+10 | 46230.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.103424E+11 | 80499.06 | 23-JAN-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.803644E+10 | 80156.79 | 21-FEB-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.219844E+10 | 80061.85 | 20-MAR-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.548041E+09 | 80136.87 | 03-APR-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 33760246.49 | 21820.24 | 30-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.332992E+10 | 80442.95 | 27-NOV-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.591622E+10 | 80346.40 | 26-DEC-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.304052E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.103424E+11 | 80499.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.116892E+11 | 15618.76 | 24-JAN-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.104360E+11 | 15589.43 | 28-FEB-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.473516E+10 | 15651.49 | 06-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.156505E+10 | 15574.17 | 03-APR-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 72442418.64 | 15505.50 | 01-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 760708.46 | 188.03 | 30-SEP-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.521547E+09 | 15524.73 | 10-OCT-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.468870E+10 | 15642.37 | 27-NOV-05:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.871402E+10 | 15630.43 | 26-DEC-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.424228E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.116892E+11 | 15651.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.733241E+10 | 16810.61 | 24-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.600102E+10 | 16772.38 | 04-FEB-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.258689E+10 | 16837.61 | 06-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.101195E+10 | 16743.81 | 14-APR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 48984570.32 | 11340.79 | 01-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 352502.87 | 244.86 | 30-SEP-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.262017E+09 | 16594.06 | 28-OCT-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.280475E+10 | 16785.02 | 27-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.536117E+10 | 16781.97 | 01-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.254095E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.733241E+10 | 16837.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.806802E+10 | 20351.07 | 23-JAN-05:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.617287E+10 | 20343.90 | 28-FEB-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.286969E+10 | 20400.20 | 06-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.127622E+10 | 20281.00 | 22-APR-04:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 77491871.42 | 18064.34 | 01-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.189481E+09 | 20108.14 | 27-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.268697E+10 | 20401.71 | 27-NOV-05:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.540560E+10 | 20369.77 | 26-DEC-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.267463E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.806802E+10 | 20401.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.666014E+10 | 18381.07 | 12-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.540033E+10 | 18402.47 | 28-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.215756E+10 | 18335.87 | 13-MAR-04:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.796808E+09 | 18367.34 | 22-APR-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 41713049.22 | 10864.55 | 01-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.229354E+09 | 15003.37 | 28-OCT-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.251271E+10 | 18369.88 | 22-NOV-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.450516E+10 | 18414.91 | 01-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.223038E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.666014E+10 | 18414.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS HEATING COIL
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT HEATING COIL
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT HEATING COIL
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID HEATING COIL
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP HEATING COIL
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID_SUPPHEATCOIL
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 18841006.08 | 18841006.08 | 4419.47 | 19-JAN-08:30 | 4419.47 | 0.00 |
February | 0.00 | 0.00 | 16076007.78 | 16076007.78 | 2775.79 | 02-FEB-08:10 | 2775.79 | 0.00 |
March | 0.00 | 0.00 | 0.114333E+10 | 0.110759E+10 | 64484.72 | 27-MAR-16:00 | 64484.72 | 0.02 |
April | 0.00 | 0.00 | 0.119550E+11 | 0.119493E+11 | 116677.73 | 07-APR-15:00 | 116677.73 | 0.09 |
May | 0.00 | 0.00 | 0.354743E+11 | 0.316231E+11 | 173874.24 | 30-MAY-13:30 | 173874.24 | 0.23 |
June | 0.00 | 0.00 | 0.120795E+12 | 0.986641E+11 | 209170.36 | 19-JUN-05:03 | 145809.67 | 0.66 |
July | 0.00 | 0.00 | 0.166254E+12 | 0.138266E+12 | 218371.39 | 10-JUL-05:02 | 156084.20 | 0.82 |
August | 0.00 | 0.00 | 0.170332E+12 | 0.150198E+12 | 217988.29 | 03-AUG-05:03 | 153701.02 | 0.84 |
September | 0.00 | 0.00 | 0.797612E+11 | 0.683656E+11 | 211319.70 | 07-SEP-05:02 | 148966.65 | 0.51 |
October | 0.00 | 0.00 | 0.378106E+11 | 0.284025E+11 | 153356.62 | 06-OCT-05:02 | 65678.85 | 0.28 |
November | 0.00 | 0.00 | 0.110735E+10 | 0.101617E+10 | 59452.13 | 10-NOV-06:03 | 23174.92 | 0.02 |
December | 0.00 | 0.00 | 11156552.39 | 11156552.39 | 4328.34 | 13-DEC-08:10 | 4328.34 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.624678E+12 | 0.529638E+12 | 0.29 | |||
Minimum of Months | 0.00 | 0.00 | 11156552.39 | 11156552.39 | 2775.79 | 2775.79 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.170332E+12 | 0.150198E+12 | 218371.39 | 173874.24 | 0.84 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 50727843.69 | 50727843.69 | 7138.87 | 17-JAN-12:40 | 7138.87 | 0.00 |
February | 0.00 | 0.00 | 4552358.87 | 4552358.87 | 243.98 | 28-FEB-14:20 | 243.98 | 0.00 |
March | 0.00 | 0.00 | 0.652141E+10 | 0.649186E+10 | 393420.99 | 27-MAR-16:00 | 393420.99 | 0.02 |
April | 0.00 | 0.00 | 0.786206E+11 | 0.786083E+11 | 974438.23 | 07-APR-14:20 | 974438.23 | 0.07 |
May | 0.00 | 0.00 | 0.298317E+12 | 0.266452E+12 | 1515081.45 | 30-MAY-10:40 | 1515081.45 | 0.22 |
June | 0.00 | 0.00 | 0.100096E+13 | 0.792011E+12 | 2113855.96 | 19-JUN-05:03 | 1364635.72 | 0.58 |
July | 0.00 | 0.00 | 0.132677E+13 | 0.103970E+13 | 2397433.49 | 21-JUL-03:02 | 1407957.95 | 0.65 |
August | 0.00 | 0.00 | 0.129637E+13 | 0.110260E+13 | 2361522.35 | 04-AUG-03:02 | 1402163.86 | 0.63 |
September | 0.00 | 0.00 | 0.690689E+12 | 0.580703E+12 | 2090670.53 | 07-SEP-05:02 | 1377656.10 | 0.48 |
October | 0.00 | 0.00 | 0.294965E+12 | 0.220688E+12 | 1403688.23 | 06-OCT-05:02 | 600920.96 | 0.27 |
November | 0.00 | 0.00 | 0.783271E+10 | 0.734693E+10 | 485257.63 | 10-NOV-06:03 | 188247.70 | 0.02 |
December | 0.00 | 0.00 | 15505479.75 | 15505479.75 | 7041.37 | 13-DEC-10:00 | 7041.37 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.500112E+13 | 0.409467E+13 | 0.25 | |||
Minimum of Months | 0.00 | 0.00 | 4552358.87 | 4552358.87 | 243.98 | 243.98 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.132677E+13 | 0.110260E+13 | 2397433.49 | 1515081.45 | 0.65 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 17100433.12 | 17100433.12 | 881.79 | 15-JAN-10:40 | 881.79 | 0.00 |
February | 0.00 | 0.00 | 11946115.34 | 11946115.34 | 1062.38 | 09-FEB-04:42 | 1062.38 | 0.00 |
March | 0.00 | 0.00 | 0.596599E+09 | 0.595262E+09 | 32239.90 | 27-MAR-16:00 | 32239.90 | 0.02 |
April | 0.00 | 0.00 | 0.801909E+10 | 0.801801E+10 | 101937.01 | 07-APR-14:00 | 101937.01 | 0.07 |
May | 0.00 | 0.00 | 0.313793E+11 | 0.283432E+11 | 185343.32 | 30-MAY-13:40 | 185343.32 | 0.21 |
June | 0.00 | 0.00 | 0.108731E+12 | 0.872937E+11 | 221180.58 | 19-JUN-05:03 | 142529.43 | 0.57 |
July | 0.00 | 0.00 | 0.148916E+12 | 0.118319E+12 | 259562.49 | 22-JUL-03:02 | 129541.70 | 0.65 |
August | 0.00 | 0.00 | 0.144224E+12 | 0.124012E+12 | 251658.13 | 04-AUG-03:02 | 145969.37 | 0.63 |
September | 0.00 | 0.00 | 0.709912E+11 | 0.597165E+11 | 220235.66 | 07-SEP-05:02 | 140336.99 | 0.47 |
October | 0.00 | 0.00 | 0.277737E+11 | 0.208934E+11 | 135916.00 | 06-OCT-05:02 | 58206.30 | 0.26 |
November | 0.00 | 0.00 | 0.601500E+09 | 0.563271E+09 | 16145.86 | 03-NOV-14:00 | 16145.86 | 0.01 |
December | 0.00 | 0.00 | 16443966.69 | 16443966.69 | 2566.65 | 25-DEC-08:55 | 2566.65 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.541278E+12 | 0.447800E+12 | 0.24 | |||
Minimum of Months | 0.00 | 0.00 | 11946115.34 | 11946115.34 | 881.79 | 881.79 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.148916E+12 | 0.124012E+12 | 259562.49 | 185343.32 | 0.65 |
Report: CoilReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 6817986.26 | 3030633.84 | 33639.40 | 24-JAN-06:03 | 14724.61 | 0.00 |
February | 0.00 | 0.00 | 55406.60 | 55406.60 | 66.02 | 11-FEB-09:40 | 66.02 | 0.00 |
March | 0.00 | 0.00 | 0.583547E+09 | 0.583345E+09 | 40317.22 | 27-MAR-16:00 | 40317.22 | 0.01 |
April | 0.00 | 0.00 | 0.529742E+10 | 0.527661E+10 | 64036.39 | 07-APR-13:50 | 64036.39 | 0.05 |
May | 0.00 | 0.00 | 0.156082E+11 | 0.148307E+11 | 95981.71 | 30-MAY-13:50 | 95981.71 | 0.12 |
June | 0.00 | 0.00 | 0.662030E+11 | 0.545677E+11 | 148327.48 | 19-JUN-03:02 | 81791.99 | 0.51 |
July | 0.00 | 0.00 | 0.958121E+11 | 0.741709E+11 | 146004.82 | 10-JUL-03:02 | 84286.38 | 0.55 |
August | 0.00 | 0.00 | 0.964099E+11 | 0.796964E+11 | 137621.43 | 03-AUG-03:02 | 84416.04 | 0.57 |
September | 0.00 | 0.00 | 0.500455E+11 | 0.432785E+11 | 130636.23 | 07-SEP-03:02 | 81980.79 | 0.42 |
October | 0.00 | 0.00 | 0.191459E+11 | 0.158261E+11 | 101894.32 | 06-OCT-05:04 | 43743.01 | 0.22 |
November | 0.00 | 0.00 | 0.140696E+09 | 0.129357E+09 | 57945.93 | 10-NOV-06:03 | 22991.59 | 0.00 |
December | 0.00 | 0.00 | 11741.56 | 11741.56 | 16.20 | 30-DEC-14:50 | 16.20 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.349253E+12 | 0.288363E+12 | 0.21 | |||
Minimum of Months | 0.00 | 0.00 | 11741.56 | 11741.56 | 16.20 | 16.20 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.964099E+11 | 0.796964E+11 | 148327.48 | 95981.71 | 0.57 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.316612E+12 | 0.316485E+12 | 123808.53 | 20-JAN-22:03 | 123808.53 | 0.00 |
February | 0.00 | 0.00 | 0.506080E+12 | 0.506080E+12 | 215251.88 | 21-FEB-22:03 | 215251.88 | 0.00 |
March | 0.00 | 0.00 | 0.810809E+12 | 0.810603E+12 | 393346.31 | 31-MAR-24:00 | 393346.31 | 0.00 |
April | 0.00 | 0.00 | 0.102580E+13 | 0.102539E+13 | 403559.36 | 27-APR-15:50 | 398075.68 | 0.00 |
May | 0.00 | 0.00 | 0.331621E+12 | 0.329084E+12 | 212637.67 | 31-MAY-24:00 | 211203.06 | 0.00 |
June | 0.00 | 0.00 | 0.567339E+12 | 0.559347E+12 | 303183.36 | 30-JUN-24:00 | 302807.28 | 0.00 |
July | 0.00 | 0.00 | 0.837339E+12 | 0.826238E+12 | 395119.84 | 31-JUL-23:57 | 395119.84 | 0.00 |
August | 0.00 | 0.00 | 0.107599E+13 | 0.106841E+13 | 412547.07 | 18-AUG-19:00 | 402892.07 | 0.00 |
September | 0.00 | 0.00 | 0.329990E+12 | 0.324406E+12 | 211563.91 | 30-SEP-24:00 | 211563.91 | 0.00 |
October | 0.00 | 0.00 | 0.580454E+12 | 0.576521E+12 | 303266.01 | 31-OCT-24:00 | 303266.01 | 0.00 |
November | 0.00 | 0.00 | 0.789920E+12 | 0.789535E+12 | 312108.26 | 10-NOV-10:30 | 305926.48 | 0.00 |
December | 0.00 | 0.00 | 0.105746E+13 | 0.105746E+13 | 400230.39 | 14-DEC-22:02 | 400230.39 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.822941E+13 | 0.818955E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.316612E+12 | 0.316485E+12 | 123808.53 | 123808.53 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.107599E+13 | 0.106841E+13 | 412547.07 | 402892.07 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.316061E+10 | 0.315541E+10 | 2147.11 | 29-JAN-16:35 | 2147.11 | 0.00 |
February | 0.00 | 0.00 | 0.793589E+10 | 0.793589E+10 | 4209.56 | 20-FEB-16:25 | 4209.56 | 0.00 |
March | 0.00 | 0.00 | 0.149250E+11 | 0.149138E+11 | 7464.89 | 31-MAR-24:00 | 7464.89 | 0.00 |
April | 0.00 | 0.00 | 0.197704E+11 | 0.197483E+11 | 8611.00 | 09-APR-17:23 | 8592.19 | 0.00 |
May | 0.00 | 0.00 | 0.564674E+10 | 0.554719E+10 | 4105.21 | 31-MAY-24:00 | 4052.12 | 0.00 |
June | 0.00 | 0.00 | 0.109641E+11 | 0.106400E+11 | 5890.06 | 30-JUN-24:00 | 5871.80 | 0.00 |
July | 0.00 | 0.00 | 0.166377E+11 | 0.161583E+11 | 7751.52 | 31-JUL-23:57 | 7751.52 | 0.00 |
August | 0.00 | 0.00 | 0.216639E+11 | 0.212921E+11 | 8840.82 | 31-AUG-17:50 | 8483.60 | 0.00 |
September | 0.00 | 0.00 | 0.583540E+10 | 0.562444E+10 | 3943.19 | 30-SEP-24:00 | 3943.19 | 0.00 |
October | 0.00 | 0.00 | 0.107610E+11 | 0.106068E+11 | 5667.09 | 31-OCT-24:00 | 5665.49 | 0.00 |
November | 0.00 | 0.00 | 0.144972E+11 | 0.144789E+11 | 6142.42 | 03-NOV-16:00 | 6142.42 | 0.00 |
December | 0.00 | 0.00 | 0.196917E+11 | 0.196917E+11 | 8036.54 | 25-DEC-16:10 | 8036.54 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.151490E+12 | 0.149793E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.316061E+10 | 0.315541E+10 | 2147.11 | 2147.11 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.216639E+11 | 0.212921E+11 | 8840.82 | 8592.19 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.781669E+10 | 0.777888E+10 | 16519.59 | 20-JAN-16:30 | 16519.59 | 0.00 |
February | 0.00 | 0.00 | 0.529047E+11 | 0.529047E+11 | 35982.61 | 22-FEB-17:00 | 35982.61 | 0.00 |
March | 0.00 | 0.00 | 0.124645E+12 | 0.124533E+12 | 65138.24 | 31-MAR-23:50 | 65138.24 | 0.00 |
April | 0.00 | 0.00 | 0.177787E+12 | 0.177563E+12 | 80207.72 | 09-APR-17:23 | 80022.79 | 0.00 |
May | 0.00 | 0.00 | 0.485466E+11 | 0.475759E+11 | 39103.47 | 31-MAY-24:00 | 38559.15 | 0.00 |
June | 0.00 | 0.00 | 0.103151E+12 | 0.999335E+11 | 55578.33 | 30-JUN-24:00 | 55393.76 | 0.00 |
July | 0.00 | 0.00 | 0.158782E+12 | 0.154003E+12 | 74729.25 | 31-JUL-23:57 | 74729.25 | 0.00 |
August | 0.00 | 0.00 | 0.206384E+12 | 0.202665E+12 | 84451.84 | 31-AUG-17:40 | 80901.20 | 0.00 |
September | 0.00 | 0.00 | 0.517526E+11 | 0.496863E+11 | 35786.41 | 30-SEP-23:40 | 35786.41 | 0.00 |
October | 0.00 | 0.00 | 0.944614E+11 | 0.929407E+11 | 49116.36 | 31-OCT-24:00 | 49092.17 | 0.00 |
November | 0.00 | 0.00 | 0.118746E+12 | 0.118564E+12 | 57451.97 | 03-NOV-16:00 | 57451.97 | 0.00 |
December | 0.00 | 0.00 | 0.161803E+12 | 0.161803E+12 | 71210.37 | 08-DEC-16:10 | 71210.37 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.130678E+13 | 0.128995E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.781669E+10 | 0.777888E+10 | 16519.59 | 16519.59 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.206384E+12 | 0.202665E+12 | 84451.84 | 80901.20 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.280669E+09 | 0.277886E+09 | 1578.37 | 19-JAN-16:20 | 1578.37 | 0.00 |
February | 0.00 | 0.00 | 0.373381E+10 | 0.373381E+10 | 3477.88 | 17-FEB-17:00 | 3477.88 | 0.00 |
March | 0.00 | 0.00 | 0.110449E+11 | 0.110339E+11 | 5944.52 | 31-MAR-23:20 | 5944.52 | 0.00 |
April | 0.00 | 0.00 | 0.168449E+11 | 0.168228E+11 | 8100.14 | 09-APR-17:23 | 8081.59 | 0.00 |
May | 0.00 | 0.00 | 0.449874E+10 | 0.440322E+10 | 3891.39 | 31-MAY-24:00 | 3836.43 | 0.00 |
June | 0.00 | 0.00 | 0.103334E+11 | 0.100117E+11 | 5484.75 | 30-JUN-24:00 | 5465.88 | 0.00 |
July | 0.00 | 0.00 | 0.160051E+11 | 0.155271E+11 | 7486.24 | 31-JUL-23:57 | 7486.24 | 0.00 |
August | 0.00 | 0.00 | 0.207263E+11 | 0.203545E+11 | 8582.06 | 31-AUG-17:10 | 8198.27 | 0.00 |
September | 0.00 | 0.00 | 0.496566E+10 | 0.475987E+10 | 3322.70 | 30-SEP-23:20 | 3322.70 | 0.00 |
October | 0.00 | 0.00 | 0.860050E+10 | 0.844951E+10 | 4660.74 | 04-OCT-16:00 | 4344.30 | 0.00 |
November | 0.00 | 0.00 | 0.102506E+11 | 0.102327E+11 | 5719.09 | 03-NOV-16:00 | 5719.09 | 0.00 |
December | 0.00 | 0.00 | 0.142322E+11 | 0.142322E+11 | 6920.97 | 08-DEC-16:10 | 6920.97 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.121517E+12 | 0.119839E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.280669E+09 | 0.277886E+09 | 1578.37 | 1578.37 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.207263E+11 | 0.203545E+11 | 8582.06 | 8198.27 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 106105.41 | 1833185.28 | 09-JAN-05:01 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 83709.07 | 1699049.81 | 13-FEB-05:11 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 24820.01 | 1253412.36 | 07-MAR-06:02 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7149.68 | 1181952.09 | 03-APR-05:01 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 183.71 | 115315.28 | 30-MAY-14:10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 511.90 | 140880.44 | 01-JUN-14:50 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 180.70 | 61771.96 | 11-JUL-16:20 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 767.82 | 104413.73 | 22-AUG-15:50 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 45.80 | 41833.98 | 01-SEP-17:20 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 904.79 | 548427.29 | 28-OCT-05:02 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25703.08 | 1285962.51 | 27-NOV-06:01 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 54884.21 | 1271144.51 | 26-DEC-05:01 |
Annual Sum or Average | 0.00 | 25121.68 | ||||
Minimum of Months | 0.00 | 0.00 | 45.80 | 41833.98 | ||
Maximum of Months | 0.00 | 0.00 | 106105.41 | 1833185.28 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 2742.69 | 41987.23 | 24-JAN-06:03 | 0.00 | 0.00 | 01-JAN-00:01 |
February | 3510.05 | 31142.94 | 09-FEB-13:10 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 9375.07 | 1080294.11 | 27-MAR-16:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 79772.35 | 1602500.79 | 07-APR-14:20 | 1.04 | 10159.02 | 08-APR-03:02 |
May | 265164.88 | 1953237.31 | 30-MAY-13:15 | 115.41 | 281628.67 | 21-MAY-06:43 |
June | 726840.26 | 2702360.10 | 17-JUN-05:04 | 2.82 | 35427.86 | 05-JUN-01:12 |
July | 874315.65 | 3042866.78 | 24-JUL-05:04 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 848142.72 | 2626657.47 | 01-AUG-05:03 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 535781.52 | 2802368.72 | 07-SEP-05:04 | 9.32 | 84476.35 | 11-SEP-03:02 |
October | 237026.46 | 1717397.35 | 05-OCT-13:10 | 6.30 | 39048.13 | 22-OCT-21:03 |
November | 10328.29 | 674997.41 | 10-NOV-06:03 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 2331.89 | 37794.13 | 15-DEC-11:20 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 301622.01 | 11.42 | ||||
Minimum of Months | 2331.89 | 31142.94 | 0.00 | 0.00 | ||
Maximum of Months | 874315.65 | 3042866.78 | 115.41 | 281628.67 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 9.49 | 44848.52 | 24-JAN-06:03 | 0.00 | 0.00 | 01-JAN-00:01 |
February | 5.76 | 987.50 | 09-FEB-13:10 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 4139.52 | 676809.51 | 27-MAR-16:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 50370.96 | 1589602.15 | 07-APR-14:40 | 0.00 | 0.00 | 01-APR-00:10 |
May | 175362.53 | 2036214.53 | 30-MAY-13:15 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 591399.63 | 4082642.50 | 27-JUN-05:02 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 716843.76 | 4169953.02 | 24-JUL-05:02 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 708275.83 | 4031801.49 | 14-AUG-05:02 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 415973.95 | 4083687.27 | 07-SEP-05:02 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 186041.97 | 3097743.33 | 06-OCT-05:02 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 4879.19 | 1124000.47 | 10-NOV-06:03 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 23.37 | 7006.41 | 13-DEC-10:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 239425.93 | 0.00 | ||||
Minimum of Months | 5.76 | 987.50 | 0.00 | 0.00 | ||
Maximum of Months | 716843.76 | 4169953.02 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 156828.69 | 176742.47 | 20-JAN-16:20 | 0.00 | 0.00 | 01-JAN-00:01 |
February | 297605.34 | 320279.96 | 20-FEB-16:30 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 452282.06 | 897583.64 | 27-MAR-16:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 654469.41 | 1359812.72 | 07-APR-13:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 254457.31 | 892221.28 | 30-MAY-13:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 668650.99 | 1510727.95 | 19-JUN-12:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 1069504.03 | 1585903.71 | 07-JUL-12:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 1268037.69 | 1777267.91 | 24-AUG-16:00 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 388023.44 | 965621.24 | 01-SEP-14:00 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 392926.86 | 854053.20 | 04-OCT-13:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 453743.55 | 655842.85 | 03-NOV-14:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 581746.58 | 598082.20 | 17-DEC-16:07 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 555421.51 | 0.00 | ||||
Minimum of Months | 156828.69 | 176742.47 | 0.00 | 0.00 | ||
Maximum of Months | 1268037.69 | 1777267.91 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 15962.24 | 53799.88 | 31-JAN-13:00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 16193.60 | 53874.81 | 09-FEB-13:00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 16763.29 | 53456.28 | 01-MAR-12:20 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15062.79 | 51248.39 | 03-APR-11:40 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14544.33 | 48331.83 | 01-MAY-11:20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13888.90 | 44836.21 | 01-JUN-11:40 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 12288.09 | 41926.21 | 03-JUL-11:40 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 13151.15 | 40982.77 | 31-AUG-11:40 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 12771.92 | 42847.30 | 29-SEP-11:20 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 13502.36 | 46142.96 | 31-OCT-11:40 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14628.84 | 49520.12 | 30-NOV-13:00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 15014.84 | 52220.11 | 29-DEC-13:00 |
Annual Sum or Average | 0.00 | 14471.26 | ||||
Minimum of Months | 0.00 | 0.00 | 12288.09 | 40982.77 | ||
Maximum of Months | 0.00 | 0.00 | 16763.29 | 53874.81 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 148.09 | 32501.51 | 04-JAN-09:00 | 3603.66 | 171740.92 | 10-JAN-10:30 |
February | 142.52 | 33248.82 | 14-FEB-21:30 | 4309.72 | 170631.98 | 07-FEB-13:30 |
March | 4157.01 | 634193.55 | 27-MAR-16:00 | 2991.59 | 160447.51 | 16-MAR-13:10 |
April | 50750.39 | 2578234.17 | 07-APR-14:40 | 1731.46 | 134835.52 | 04-APR-09:00 |
May | 195160.50 | 3412561.13 | 31-MAY-13:30 | 918.31 | 94636.67 | 13-MAY-10:30 |
June | 975023.78 | 5500317.06 | 15-JUN-12:10 | 232.48 | 59848.38 | 09-JUN-06:10 |
July | 1781012.58 | 6060086.24 | 20-JUL-13:10 | 1.18 | 5276.84 | 11-JUL-03:00 |
August | 1524004.51 | 6392153.19 | 02-AUG-13:40 | 220.66 | 40037.63 | 29-AUG-03:45 |
September | 626118.62 | 4895482.25 | 07-SEP-14:00 | 283.91 | 79906.24 | 23-SEP-11:30 |
October | 202471.36 | 3079811.55 | 25-OCT-10:20 | 526.73 | 100618.19 | 26-OCT-11:50 |
November | 5125.21 | 336963.55 | 03-NOV-14:00 | 2412.94 | 152943.66 | 29-NOV-07:20 |
December | 98.16 | 32241.91 | 13-DEC-07:50 | 3068.50 | 171177.79 | 22-DEC-10:10 |
Annual Sum or Average | 451049.72 | 1676.02 | ||||
Minimum of Months | 98.16 | 32241.91 | 1.18 | 5276.84 | ||
Maximum of Months | 1781012.58 | 6392153.19 | 4309.72 | 171740.92 |
Report: FanReportMonthly
For: CAV_BAS FAN
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.127455E+11 | 0.74 | 8953.22 | 02-JAN-06:01 | 1.39 |
February | 0.117914E+11 | 0.76 | 8953.22 | 01-FEB-05:01 | 1.40 |
March | 0.142060E+11 | 0.82 | 8953.22 | 01-MAR-05:01 | 1.39 |
April | 0.132029E+11 | 0.79 | 8953.22 | 01-APR-04:01 | 1.39 |
May | 0.140503E+11 | 0.81 | 8953.22 | 01-MAY-03:02 | 1.39 |
June | 0.141291E+11 | 0.84 | 8953.22 | 01-JUN-03:02 | 1.38 |
July | 0.138260E+11 | 0.79 | 8953.22 | 01-JUL-03:02 | 1.38 |
August | 0.153191E+11 | 0.88 | 8953.22 | 01-AUG-03:02 | 1.38 |
September | 0.143894E+11 | 0.85 | 8953.22 | 01-SEP-03:02 | 1.38 |
October | 0.145526E+11 | 0.84 | 8953.22 | 01-OCT-21:20 | 1.38 |
November | 0.138265E+11 | 0.83 | 8953.22 | 01-NOV-03:10 | 1.38 |
December | 0.131822E+11 | 0.77 | 8953.22 | 01-DEC-04:50 | 1.39 |
Annual Sum or Average | 0.165221E+12 | 0.81 | |||
Minimum of Months | 0.117914E+11 | 0.74 | 8953.22 | 1.38 | |
Maximum of Months | 0.153191E+11 | 0.88 | 8953.22 | 1.40 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.321762E+10 | 0.30 | 13680.45 | 31-JAN-06:01 | 1.43 |
February | 0.332505E+10 | 0.32 | 11963.21 | 04-FEB-06:01 | 1.31 |
March | 0.567218E+10 | 0.40 | 11038.72 | 17-MAR-05:01 | 1.25 |
April | 0.742200E+10 | 0.47 | 19208.50 | 07-APR-14:40 | 1.75 |
May | 0.767479E+10 | 0.47 | 21111.09 | 30-MAY-10:23 | 1.86 |
June | 0.109585E+11 | 0.61 | 21111.09 | 01-JUN-14:20 | 1.86 |
July | 0.129926E+11 | 0.69 | 21111.09 | 10-JUL-05:02 | 1.86 |
August | 0.152963E+11 | 0.77 | 21111.09 | 07-AUG-05:02 | 1.86 |
September | 0.844461E+10 | 0.50 | 21111.09 | 05-SEP-05:02 | 1.86 |
October | 0.797692E+10 | 0.46 | 18323.26 | 23-OCT-05:03 | 1.70 |
November | 0.525252E+10 | 0.37 | 11527.02 | 22-NOV-06:01 | 1.28 |
December | 0.469038E+10 | 0.35 | 11038.72 | 02-DEC-06:01 | 1.25 |
Annual Sum or Average | 0.929234E+11 | 0.48 | |||
Minimum of Months | 0.321762E+10 | 0.30 | 11038.72 | 1.25 | |
Maximum of Months | 0.152963E+11 | 0.77 | 21111.09 | 1.86 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.321838E+11 | 0.34 | 45478.13 | 03-JAN-05:12 | 0.78 |
February | 0.285889E+11 | 0.33 | 45478.13 | 06-FEB-05:01 | 0.78 |
March | 0.328917E+11 | 0.32 | 119145.24 | 31-MAR-05:02 | 1.36 |
April | 0.389968E+11 | 0.34 | 128039.12 | 07-APR-14:40 | 1.42 |
May | 0.576550E+11 | 0.41 | 197219.22 | 30-MAY-10:23 | 1.86 |
June | 0.839093E+11 | 0.51 | 197219.22 | 01-JUN-14:37 | 1.86 |
July | 0.951085E+11 | 0.54 | 197219.22 | 03-JUL-05:03 | 1.85 |
August | 0.106209E+12 | 0.58 | 197219.22 | 02-AUG-03:02 | 1.86 |
September | 0.658854E+11 | 0.44 | 197219.22 | 01-SEP-14:15 | 1.86 |
October | 0.507770E+11 | 0.37 | 101891.93 | 05-OCT-15:40 | 1.22 |
November | 0.304954E+11 | 0.30 | 119731.43 | 13-NOV-06:01 | 1.36 |
December | 0.286613E+11 | 0.31 | 38136.91 | 21-DEC-13:20 | 0.71 |
Annual Sum or Average | 0.651362E+12 | 0.40 | |||
Minimum of Months | 0.285889E+11 | 0.30 | 38136.91 | 0.71 | |
Maximum of Months | 0.106209E+12 | 0.58 | 197219.22 | 1.86 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.395796E+10 | 0.40 | 4644.26 | 02-JAN-04:01 | 0.76 |
February | 0.342466E+10 | 0.38 | 4644.26 | 01-FEB-05:01 | 0.76 |
March | 0.337347E+10 | 0.34 | 4644.26 | 06-MAR-05:01 | 0.75 |
April | 0.362985E+10 | 0.32 | 11129.45 | 07-APR-15:20 | 1.24 |
May | 0.550525E+10 | 0.39 | 21283.02 | 30-MAY-10:27 | 1.86 |
June | 0.885780E+10 | 0.50 | 21283.02 | 01-JUN-14:40 | 1.86 |
July | 0.106272E+11 | 0.55 | 21283.02 | 10-JUL-05:02 | 1.86 |
August | 0.117025E+11 | 0.59 | 21283.02 | 04-AUG-05:03 | 1.86 |
September | 0.635927E+10 | 0.41 | 21283.02 | 07-SEP-05:02 | 1.86 |
October | 0.433162E+10 | 0.33 | 11395.47 | 04-OCT-15:50 | 1.25 |
November | 0.308995E+10 | 0.32 | 4644.26 | 06-NOV-06:01 | 0.75 |
December | 0.342981E+10 | 0.35 | 4644.26 | 01-DEC-06:01 | 0.75 |
Annual Sum or Average | 0.682893E+11 | 0.41 | |||
Minimum of Months | 0.308995E+10 | 0.32 | 4644.26 | 0.75 | |
Maximum of Months | 0.117025E+11 | 0.59 | 21283.02 | 1.86 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BASEMENT SUPPLY FAN
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.945869E+11 | 1.35 | 35314.70 | 01-JAN-00:01 | 1.35 |
February | 0.854333E+11 | 1.35 | 35314.70 | 01-FEB-00:10 | 1.35 |
March | 0.945869E+11 | 1.35 | 35314.70 | 01-MAR-00:10 | 1.35 |
April | 0.915357E+11 | 1.35 | 35314.70 | 01-APR-00:10 | 1.35 |
May | 0.945869E+11 | 1.35 | 35314.70 | 01-MAY-00:10 | 1.35 |
June | 0.915357E+11 | 1.35 | 35314.70 | 01-JUN-00:10 | 1.35 |
July | 0.945869E+11 | 1.35 | 35314.70 | 01-JUL-00:10 | 1.35 |
August | 0.945869E+11 | 1.35 | 35314.70 | 01-AUG-00:03 | 1.35 |
September | 0.915357E+11 | 1.35 | 35314.70 | 01-SEP-00:03 | 1.35 |
October | 0.945869E+11 | 1.35 | 35314.70 | 01-OCT-00:10 | 1.35 |
November | 0.915357E+11 | 1.35 | 35314.70 | 01-NOV-00:10 | 1.35 |
December | 0.945869E+11 | 1.35 | 35314.70 | 01-DEC-00:10 | 1.35 |
Annual Sum or Average | 0.111368E+13 | 1.35 | |||
Minimum of Months | 0.854333E+11 | 1.35 | 35314.70 | 1.35 | |
Maximum of Months | 0.945869E+11 | 1.35 | 35314.70 | 1.35 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BOT SUPPLY FAN
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.141698E+10 | 0.92 | 529.04 | 01-JAN-00:01 | 0.92 |
February | 0.127985E+10 | 0.92 | 529.04 | 01-FEB-00:10 | 0.92 |
March | 0.141698E+10 | 0.92 | 529.04 | 01-MAR-00:10 | 0.92 |
April | 0.137127E+10 | 0.92 | 529.04 | 01-APR-00:10 | 0.91 |
May | 0.141698E+10 | 0.91 | 529.04 | 01-MAY-00:10 | 0.91 |
June | 0.137127E+10 | 0.91 | 529.04 | 01-JUN-00:10 | 0.91 |
July | 0.141698E+10 | 0.91 | 529.04 | 01-JUL-00:10 | 0.91 |
August | 0.141698E+10 | 0.91 | 529.04 | 01-AUG-00:03 | 0.91 |
September | 0.137127E+10 | 0.91 | 529.04 | 01-SEP-00:03 | 0.91 |
October | 0.141698E+10 | 0.91 | 529.04 | 01-OCT-00:10 | 0.91 |
November | 0.137127E+10 | 0.92 | 529.04 | 01-NOV-00:10 | 0.91 |
December | 0.141698E+10 | 0.92 | 529.04 | 01-DEC-00:10 | 0.92 |
Annual Sum or Average | 0.166838E+11 | 0.92 | |||
Minimum of Months | 0.127985E+10 | 0.91 | 529.04 | 0.91 | |
Maximum of Months | 0.141698E+10 | 0.92 | 529.04 | 0.92 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER MID SUPPLY FAN
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.135195E+11 | 0.92 | 5047.61 | 01-JAN-00:01 | 0.92 |
February | 0.122112E+11 | 0.92 | 5047.61 | 01-FEB-00:10 | 0.92 |
March | 0.135195E+11 | 0.92 | 5047.61 | 01-MAR-00:10 | 0.92 |
April | 0.130834E+11 | 0.92 | 5047.61 | 01-APR-00:10 | 0.91 |
May | 0.135195E+11 | 0.91 | 5047.61 | 01-MAY-00:10 | 0.91 |
June | 0.130834E+11 | 0.91 | 5047.61 | 01-JUN-00:10 | 0.91 |
July | 0.135195E+11 | 0.91 | 5047.61 | 01-JUL-00:10 | 0.91 |
August | 0.135195E+11 | 0.91 | 5047.61 | 01-AUG-00:03 | 0.91 |
September | 0.130834E+11 | 0.91 | 5047.61 | 01-SEP-00:03 | 0.91 |
October | 0.135195E+11 | 0.91 | 5047.61 | 01-OCT-00:10 | 0.91 |
November | 0.130834E+11 | 0.92 | 5047.61 | 01-NOV-00:10 | 0.91 |
December | 0.135195E+11 | 0.92 | 5047.61 | 01-DEC-00:10 | 0.92 |
Annual Sum or Average | 0.159181E+12 | 0.92 | |||
Minimum of Months | 0.122112E+11 | 0.91 | 5047.61 | 0.91 | |
Maximum of Months | 0.135195E+11 | 0.92 | 5047.61 | 0.92 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER TOP SUPPLY FAN
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.137808E+10 | 0.92 | 514.52 | 01-JAN-00:01 | 0.92 |
February | 0.124472E+10 | 0.92 | 514.52 | 01-FEB-00:10 | 0.92 |
March | 0.137808E+10 | 0.92 | 514.52 | 01-MAR-00:10 | 0.92 |
April | 0.133363E+10 | 0.92 | 514.52 | 01-APR-00:10 | 0.91 |
May | 0.137808E+10 | 0.91 | 514.52 | 01-MAY-00:10 | 0.91 |
June | 0.133363E+10 | 0.91 | 514.52 | 01-JUN-00:10 | 0.91 |
July | 0.137808E+10 | 0.91 | 514.52 | 01-JUL-00:10 | 0.91 |
August | 0.137808E+10 | 0.91 | 514.52 | 01-AUG-00:03 | 0.91 |
September | 0.133363E+10 | 0.91 | 514.52 | 01-SEP-00:03 | 0.91 |
October | 0.137808E+10 | 0.91 | 514.52 | 01-OCT-00:10 | 0.91 |
November | 0.133363E+10 | 0.92 | 514.52 | 01-NOV-00:10 | 0.91 |
December | 0.137808E+10 | 0.92 | 514.52 | 01-DEC-00:10 | 0.92 |
Annual Sum or Average | 0.162258E+11 | 0.92 | |||
Minimum of Months | 0.124472E+10 | 0.91 | 514.52 | 0.91 | |
Maximum of Months | 0.137808E+10 | 0.92 | 514.52 | 0.92 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 38652184.59 | 34786966.13 | 1146.90 | 03-JAN-06:02 | 1032.21 | 1032.21 | 46.50 | 11.28 |
February | 21120784.37 | 19008705.93 | 1062.08 | 06-FEB-05:02 | 955.88 | 955.88 | 49.22 | 10.89 |
March | 4437067.61 | 3993360.85 | 334.39 | 17-MAR-05:01 | 300.95 | 300.95 | 41.78 | 6.48 |
April | 878685.76 | 790817.18 | 323.31 | 03-APR-05:01 | 290.98 | 290.98 | 36.35 | 6.39 |
May | 16750.76 | 15075.68 | 6.27 | 30-MAY-14:10 | 5.64 | 5.64 | 36.96 | 0.65 |
June | 75429.98 | 67886.98 | 9.34 | 01-JUN-14:50 | 8.41 | 8.41 | 40.29 | 0.86 |
July | 27140.61 | 24426.55 | 4.36 | 11-JUL-16:20 | 3.92 | 3.92 | 49.39 | 0.49 |
August | 139151.36 | 125236.22 | 12.67 | 24-AUG-16:50 | 11.40 | 11.40 | 61.44 | 1.05 |
September | 6528.52 | 5875.67 | 2.24 | 01-SEP-17:20 | 2.02 | 2.02 | 44.85 | 0.29 |
October | 84713.07 | 76241.76 | 52.57 | 28-OCT-05:02 | 47.32 | 47.32 | 28.45 | 2.52 |
November | 4605691.77 | 4145122.59 | 436.76 | 27-NOV-06:01 | 393.08 | 393.08 | 38.07 | 7.35 |
December | 9693366.77 | 8724030.10 | 362.62 | 30-DEC-06:01 | 326.36 | 326.36 | 42.13 | 6.73 |
Annual Sum or Average | 79737495.16 | 71763745.65 | ||||||
Minimum of Months | 6528.52 | 5875.67 | 2.24 | 2.02 | 2.02 | 28.45 | 0.29 | |
Maximum of Months | 38652184.59 | 34786966.13 | 1146.90 | 1032.21 | 1032.21 | 61.44 | 11.28 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 20803.34 | 18723.00 | 37.52 | 24-JAN-06:03 | 33.77 | 33.77 | 7.34 | 4.80 |
February | 4875.76 | 4388.18 | 0.36 | 09-FEB-13:10 | 0.32 | 0.32 | 7.50 | 0.08 |
March | 4264293.43 | 3837864.09 | 412.47 | 27-MAR-16:00 | 371.22 | 371.22 | 8.45 | 19.47 |
April | 0.100220E+09 | 90198118.10 | 4697.97 | 07-APR-14:40 | 4228.18 | 4228.18 | 7.20 | 60.50 |
May | 0.353037E+09 | 0.317734E+09 | 7417.48 | 30-MAY-14:00 | 6675.73 | 6675.73 | 6.72 | 73.35 |
June | 0.152161E+10 | 0.136945E+10 | 24714.96 | 08-JUN-05:02 | 22243.46 | 22243.46 | 8.18 | 119.22 |
July | 0.188615E+10 | 0.169754E+10 | 24714.96 | 01-JUL-05:02 | 22243.46 | 22243.46 | 8.08 | 119.22 |
August | 0.233773E+10 | 0.210396E+10 | 24714.96 | 02-AUG-05:03 | 22243.46 | 22243.46 | 7.46 | 119.22 |
September | 0.120296E+10 | 0.108266E+10 | 24714.96 | 07-SEP-05:02 | 22243.46 | 22243.46 | 7.78 | 119.22 |
October | 0.601594E+09 | 0.541434E+09 | 14407.95 | 06-OCT-05:02 | 12967.16 | 12967.16 | 8.14 | 96.23 |
November | 3439517.92 | 3095566.13 | 1390.55 | 10-NOV-06:03 | 1251.50 | 1251.50 | 8.50 | 35.19 |
December | 9540.57 | 8586.51 | 1.10 | 13-DEC-10:00 | 0.99 | 0.99 | 8.45 | 0.25 |
Annual Sum or Average | 0.801104E+10 | 0.720994E+10 | ||||||
Minimum of Months | 4875.76 | 4388.18 | 0.36 | 0.32 | 0.32 | 6.72 | 0.08 | |
Maximum of Months | 0.233773E+10 | 0.210396E+10 | 24714.96 | 22243.46 | 22243.46 | 8.50 | 119.22 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.410455E+10 | 0.369409E+10 | 17010.64 | 02-JAN-07:03 | 15309.57 | 15309.57 | 8.43 | 119.22 |
February | 0.473508E+10 | 0.426157E+10 | 17010.64 | 01-FEB-11:50 | 15309.57 | 15309.57 | 8.43 | 119.22 |
March | 0.422197E+10 | 0.379977E+10 | 17010.64 | 01-MAR-07:05 | 15309.57 | 15309.57 | 8.43 | 119.22 |
April | 0.833072E+10 | 0.749764E+10 | 17010.64 | 01-APR-08:30 | 15309.57 | 15309.57 | 8.43 | 119.22 |
May | 0.202690E+11 | 0.182421E+11 | 17010.64 | 01-MAY-09:30 | 15309.57 | 15309.57 | 8.44 | 119.22 |
June | 0.323541E+11 | 0.291187E+11 | 17010.64 | 01-JUN-03:02 | 15309.57 | 15309.57 | 9.02 | 119.22 |
July | 0.396239E+11 | 0.356615E+11 | 17010.64 | 01-JUL-03:02 | 15309.57 | 15309.57 | 9.59 | 119.22 |
August | 0.415868E+11 | 0.374281E+11 | 17010.64 | 01-AUG-00:03 | 15309.57 | 15309.57 | 7.35 | 119.22 |
September | 0.271714E+11 | 0.244543E+11 | 17010.64 | 01-SEP-00:20 | 15309.57 | 15309.57 | 7.40 | 119.22 |
October | 0.155925E+11 | 0.140332E+11 | 17010.64 | 02-OCT-03:02 | 15309.57 | 15309.57 | 8.57 | 119.22 |
November | 0.407281E+10 | 0.366553E+10 | 17010.64 | 02-NOV-11:00 | 15309.57 | 15309.57 | 8.45 | 119.22 |
December | 0.344283E+10 | 0.309855E+10 | 17010.64 | 01-DEC-06:50 | 15309.57 | 15309.57 | 8.43 | 119.22 |
Annual Sum or Average | 0.205506E+12 | 0.184955E+12 | ||||||
Minimum of Months | 0.344283E+10 | 0.309855E+10 | 17010.64 | 15309.57 | 15309.57 | 7.35 | 119.22 | |
Maximum of Months | 0.415868E+11 | 0.374281E+11 | 17010.64 | 15309.57 | 15309.57 | 9.59 | 119.22 |
Report: PumpReportMonthly
For: PLANT CIRC PUMP
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.904370E+10 | 0.813933E+10 | 3376.53 | 01-JAN-00:01 | 3038.88 | 3038.88 | 21.46 | 14.10 |
February | 0.816850E+10 | 0.735165E+10 | 3376.53 | 01-FEB-00:10 | 3038.88 | 3038.88 | 24.15 | 14.10 |
March | 0.904370E+10 | 0.813933E+10 | 3376.53 | 01-MAR-00:10 | 3038.88 | 3038.88 | 26.94 | 14.10 |
April | 0.875196E+10 | 0.787677E+10 | 3376.53 | 01-APR-00:10 | 3038.88 | 3038.88 | 30.16 | 14.10 |
May | 0.904370E+10 | 0.813933E+10 | 3376.53 | 01-MAY-00:10 | 3038.88 | 3038.88 | 22.37 | 14.10 |
June | 0.875196E+10 | 0.787677E+10 | 3376.53 | 01-JUN-00:10 | 3038.88 | 3038.88 | 28.03 | 14.10 |
July | 0.904370E+10 | 0.813933E+10 | 3376.53 | 01-JUL-00:10 | 3038.88 | 3038.88 | 33.80 | 14.10 |
August | 0.904370E+10 | 0.813933E+10 | 3376.53 | 01-AUG-00:03 | 3038.88 | 3038.88 | 42.35 | 14.10 |
September | 0.875196E+10 | 0.787677E+10 | 3376.53 | 01-SEP-00:03 | 3038.88 | 3038.88 | 29.90 | 14.10 |
October | 0.904370E+10 | 0.813933E+10 | 3376.53 | 01-OCT-00:10 | 3038.88 | 3038.88 | 24.83 | 14.10 |
November | 0.875196E+10 | 0.787677E+10 | 3376.53 | 01-NOV-00:10 | 3038.88 | 3038.88 | 27.48 | 14.10 |
December | 0.904370E+10 | 0.813933E+10 | 3376.53 | 01-DEC-00:10 | 3038.88 | 3038.88 | 29.87 | 14.10 |
Annual Sum or Average | 0.106482E+12 | 0.958340E+11 | ||||||
Minimum of Months | 0.816850E+10 | 0.735165E+10 | 3376.53 | 3038.88 | 3038.88 | 21.46 | 14.10 | |
Maximum of Months | 0.904370E+10 | 0.813933E+10 | 3376.53 | 3038.88 | 3038.88 | 42.35 | 14.10 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 11967951.72 | 3590385.52 | 5.96 | 01-JAN-06:02 | 1.79 | 1.79 | 56.01 | 0.44 |
February | 10809762.85 | 3242928.85 | 5.96 | 01-FEB-06:01 | 1.79 | 1.79 | 56.35 | 0.44 |
March | 11967951.72 | 3590385.52 | 5.96 | 01-MAR-06:03 | 1.79 | 1.79 | 56.23 | 0.44 |
April | 11581888.76 | 3474566.63 | 5.96 | 01-APR-05:02 | 1.79 | 1.79 | 56.22 | 0.44 |
May | 11967951.72 | 3590385.52 | 5.96 | 01-MAY-05:03 | 1.79 | 1.79 | 55.99 | 0.44 |
June | 11581888.76 | 3474566.63 | 5.96 | 01-JUN-05:03 | 1.79 | 1.79 | 56.92 | 0.44 |
July | 11967951.72 | 3590385.52 | 5.96 | 01-JUL-05:02 | 1.79 | 1.79 | 56.05 | 0.44 |
August | 11967951.72 | 3590385.52 | 5.96 | 01-AUG-05:03 | 1.79 | 1.79 | 56.51 | 0.44 |
September | 11581888.76 | 3474566.63 | 5.96 | 01-SEP-05:03 | 1.79 | 1.79 | 56.10 | 0.44 |
October | 11967951.72 | 3590385.52 | 5.96 | 01-OCT-05:10 | 1.79 | 1.79 | 56.55 | 0.44 |
November | 11581888.76 | 3474566.63 | 5.96 | 01-NOV-05:03 | 1.79 | 1.79 | 56.16 | 0.44 |
December | 11967951.72 | 3590385.52 | 5.96 | 01-DEC-06:01 | 1.79 | 1.79 | 55.87 | 0.44 |
Annual Sum or Average | 0.140913E+09 | 42273893.99 | ||||||
Minimum of Months | 10809762.85 | 3242928.85 | 5.96 | 1.79 | 1.79 | 55.87 | 0.44 | |
Maximum of Months | 11967951.72 | 3590385.52 | 5.96 | 1.79 | 1.79 | 56.92 | 0.44 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.506081E+10 | 0.455473E+10 | 20977.38 | 04-JAN-09:00 | 18879.64 | 18879.64 | 21.21 | 69.88 |
February | 0.583828E+10 | 0.525445E+10 | 20977.42 | 14-FEB-21:30 | 18879.68 | 18879.68 | 21.21 | 69.88 |
March | 0.520624E+10 | 0.468562E+10 | 21008.48 | 27-MAR-16:00 | 18907.63 | 18907.63 | 23.27 | 69.88 |
April | 0.104622E+11 | 0.941602E+10 | 42087.52 | 07-APR-14:40 | 37878.77 | 37878.77 | 25.51 | 139.76 |
May | 0.261051E+11 | 0.234946E+11 | 42137.95 | 31-MAY-13:30 | 37924.16 | 37924.16 | 26.94 | 139.76 |
June | 0.489470E+11 | 0.440523E+11 | 42204.00 | 15-JUN-10:10 | 37983.60 | 37983.60 | 28.98 | 139.76 |
July | 0.640275E+11 | 0.576247E+11 | 42204.00 | 05-JUL-16:00 | 37983.60 | 37983.60 | 28.89 | 139.76 |
August | 0.658101E+11 | 0.592291E+11 | 42204.00 | 01-AUG-10:00 | 37983.60 | 37983.60 | 28.94 | 139.76 |
September | 0.389043E+11 | 0.350139E+11 | 42204.00 | 07-SEP-12:40 | 37983.60 | 37983.60 | 28.83 | 139.76 |
October | 0.209225E+11 | 0.188303E+11 | 42117.83 | 25-OCT-10:20 | 37906.04 | 37906.04 | 26.37 | 139.76 |
November | 0.502252E+10 | 0.452026E+10 | 20993.11 | 03-NOV-14:00 | 18893.79 | 18893.79 | 22.25 | 69.88 |
December | 0.424492E+10 | 0.382043E+10 | 20977.36 | 13-DEC-07:50 | 18879.63 | 18879.63 | 21.21 | 69.88 |
Annual Sum or Average | 0.300552E+12 | 0.270496E+12 | ||||||
Minimum of Months | 0.424492E+10 | 0.382043E+10 | 20977.36 | 18879.63 | 18879.63 | 21.21 | 69.88 | |
Maximum of Months | 0.658101E+11 | 0.592291E+11 | 42204.00 | 37983.60 | 37983.60 | 28.98 | 139.76 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 45.07 | 45.07 | 106105.41 | 1833185.28 | 09-JAN-05:01 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 30.01 | 30.01 | 83709.07 | 1699049.81 | 13-FEB-05:11 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.53 | 25.53 | 24820.01 | 1253412.36 | 07-MAR-06:02 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.83 | 20.83 | 7149.68 | 1181952.09 | 03-APR-05:01 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 21.89 | 21.89 | 183.71 | 115315.28 | 30-MAY-14:10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 37.69 | 37.69 | 511.90 | 140880.44 | 01-JUN-14:50 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 43.14 | 43.14 | 180.70 | 61771.96 | 11-JUL-16:20 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 47.28 | 47.28 | 767.82 | 104413.73 | 22-AUG-15:50 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 50.55 | 50.55 | 45.80 | 41833.98 | 01-SEP-17:20 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 42.70 | 42.70 | 904.79 | 548427.29 | 28-OCT-05:02 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.88 | 22.88 | 25703.08 | 1285962.51 | 27-NOV-06:01 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.73 | 23.73 | 54884.21 | 1271144.51 | 26-DEC-05:01 |
Annual Sum or Average | 0.00 | 25121.68 | ||||||
Minimum of Months | 0.00 | 0.00 | 20.83 | 20.83 | 45.80 | 41833.98 | ||
Maximum of Months | 0.00 | 0.00 | 50.55 | 50.55 | 106105.41 | 1833185.28 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 2742.69 | 41987.23 | 24-JAN-06:03 | 8.45 | 8.41 | 0.00 | 0.00 | 01-JAN-00:01 |
February | 3510.05 | 31142.94 | 09-FEB-13:10 | 8.43 | 8.40 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 9375.07 | 1080294.11 | 27-MAR-16:00 | 9.54 | 8.45 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 79772.35 | 1602500.79 | 07-APR-14:20 | 10.02 | 8.11 | 1.04 | 10159.02 | 08-APR-03:02 |
May | 265164.88 | 1953237.31 | 30-MAY-13:15 | 10.61 | 6.70 | 115.41 | 281628.67 | 21-MAY-06:43 |
June | 726840.26 | 2702360.10 | 17-JUN-05:04 | 13.12 | 7.71 | 2.82 | 35427.86 | 05-JUN-01:12 |
July | 874315.65 | 3042866.78 | 24-JUL-05:04 | 13.69 | 8.01 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 848142.72 | 2626657.47 | 01-AUG-05:03 | 12.38 | 7.12 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 535781.52 | 2802368.72 | 07-SEP-05:04 | 12.99 | 7.38 | 9.32 | 84476.35 | 11-SEP-03:02 |
October | 237026.46 | 1717397.35 | 05-OCT-13:10 | 10.71 | 7.27 | 6.30 | 39048.13 | 22-OCT-21:03 |
November | 10328.29 | 674997.41 | 10-NOV-06:03 | 9.72 | 9.04 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 2331.89 | 37794.13 | 15-DEC-11:20 | 8.45 | 8.41 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 301622.01 | 11.42 | ||||||
Minimum of Months | 2331.89 | 31142.94 | 8.43 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 874315.65 | 3042866.78 | 13.69 | 9.04 | 115.41 | 281628.67 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 9.49 | 44848.52 | 24-JAN-06:03 | 8.93 | 8.41 | 0.00 | 0.00 | 01-JAN-00:01 |
February | 5.76 | 987.50 | 09-FEB-13:10 | 9.54 | 8.40 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 4139.52 | 676809.51 | 27-MAR-16:00 | 15.01 | 8.42 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 50370.96 | 1589602.15 | 07-APR-14:40 | 12.97 | 8.12 | 0.00 | 0.00 | 01-APR-00:10 |
May | 175362.53 | 2036214.53 | 30-MAY-13:15 | 13.75 | 6.97 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 591399.63 | 4082642.50 | 27-JUN-05:02 | 14.88 | 7.98 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 716843.76 | 4169953.02 | 24-JUL-05:02 | 15.06 | 8.09 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 708275.83 | 4031801.49 | 14-AUG-05:02 | 14.78 | 7.45 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 415973.95 | 4083687.27 | 07-SEP-05:02 | 14.88 | 7.41 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 186041.97 | 3097743.33 | 06-OCT-05:02 | 14.39 | 7.84 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 4879.19 | 1124000.47 | 10-NOV-06:03 | 14.33 | 8.81 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 23.37 | 7006.41 | 13-DEC-10:00 | 13.41 | 8.40 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 239425.93 | 0.00 | ||||||
Minimum of Months | 5.76 | 987.50 | 8.93 | 6.97 | 0.00 | 0.00 | ||
Maximum of Months | 716843.76 | 4169953.02 | 15.06 | 8.81 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 156828.69 | 176742.47 | 20-JAN-16:20 | 21.94 | 18.33 | 0.00 | 0.00 | 01-JAN-00:01 |
February | 297605.34 | 320279.96 | 20-FEB-16:30 | 24.85 | 18.33 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 452282.06 | 897583.64 | 27-MAR-16:00 | 36.40 | 26.49 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 654469.41 | 1359812.72 | 07-APR-13:00 | 45.47 | 32.43 | 0.00 | 0.00 | 01-APR-00:10 |
May | 254457.31 | 892221.28 | 30-MAY-13:00 | 36.29 | 31.90 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 668650.99 | 1510727.95 | 19-JUN-12:00 | 48.39 | 40.28 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 1069504.03 | 1585903.71 | 07-JUL-12:00 | 49.85 | 38.79 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 1268037.69 | 1777267.91 | 24-AUG-16:00 | 53.53 | 39.94 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 388023.44 | 965621.24 | 01-SEP-14:00 | 37.74 | 33.11 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 392926.86 | 854053.20 | 04-OCT-13:00 | 35.54 | 28.18 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 453743.55 | 655842.85 | 03-NOV-14:00 | 31.59 | 21.94 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 581746.58 | 598082.20 | 17-DEC-16:07 | 30.44 | 18.33 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 555421.51 | 0.00 | ||||||
Minimum of Months | 156828.69 | 176742.47 | 21.94 | 18.33 | 0.00 | 0.00 | ||
Maximum of Months | 1268037.69 | 1777267.91 | 53.53 | 40.28 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 57.09 | 57.09 | 15962.24 | 53799.88 | 31-JAN-13:00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 56.78 | 56.78 | 16193.60 | 53874.81 | 09-FEB-13:00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 56.57 | 56.57 | 16763.29 | 53456.28 | 01-MAR-12:20 |
April | 0.00 | 0.00 | 01-APR-00:10 | 56.80 | 56.80 | 15062.79 | 51248.39 | 03-APR-11:40 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 56.84 | 56.84 | 14544.33 | 48331.83 | 01-MAY-11:20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 57.41 | 57.41 | 13888.90 | 44836.21 | 01-JUN-11:40 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 56.51 | 56.51 | 12288.09 | 41926.21 | 03-JUL-11:40 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 57.02 | 57.02 | 13151.15 | 40982.77 | 31-AUG-11:40 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 56.66 | 56.66 | 12771.92 | 42847.30 | 29-SEP-11:20 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 56.84 | 56.84 | 13502.36 | 46142.96 | 31-OCT-11:40 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 56.75 | 56.75 | 14628.84 | 49520.12 | 30-NOV-13:00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 56.34 | 56.34 | 15014.84 | 52220.11 | 29-DEC-13:00 |
Annual Sum or Average | 0.00 | 14471.26 | ||||||
Minimum of Months | 0.00 | 0.00 | 56.34 | 56.34 | 12288.09 | 40982.77 | ||
Maximum of Months | 0.00 | 0.00 | 57.41 | 57.41 | 16763.29 | 53874.81 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 148.09 | 32501.51 | 04-JAN-09:00 | 21.21 | 20.28 | 3603.66 | 171740.92 | 10-JAN-10:30 |
February | 142.52 | 33248.82 | 14-FEB-21:30 | 21.21 | 20.28 | 4309.72 | 170631.98 | 07-FEB-13:30 |
March | 4157.01 | 634193.55 | 27-MAR-16:00 | 23.27 | 21.10 | 2991.59 | 160447.51 | 16-MAR-13:10 |
April | 50750.39 | 2578234.17 | 07-APR-14:40 | 25.51 | 21.29 | 1731.46 | 134835.52 | 04-APR-09:00 |
May | 195160.50 | 3412561.13 | 31-MAY-13:30 | 26.94 | 23.76 | 918.31 | 94636.67 | 13-MAY-10:30 |
June | 975023.78 | 5500317.06 | 15-JUN-12:10 | 30.52 | 27.36 | 232.48 | 59848.38 | 09-JUN-06:10 |
July | 1781012.58 | 6060086.24 | 20-JUL-13:10 | 31.47 | 28.10 | 1.18 | 5276.84 | 11-JUL-03:00 |
August | 1524004.51 | 6392153.19 | 02-AUG-13:40 | 32.04 | 28.51 | 220.66 | 40037.63 | 29-AUG-03:45 |
September | 626118.62 | 4895482.25 | 07-SEP-14:00 | 29.48 | 26.32 | 283.91 | 79906.24 | 23-SEP-11:30 |
October | 202471.36 | 3079811.55 | 25-OCT-10:20 | 26.37 | 23.15 | 526.73 | 100618.19 | 26-OCT-11:50 |
November | 5125.21 | 336963.55 | 03-NOV-14:00 | 22.25 | 21.10 | 2412.94 | 152943.66 | 29-NOV-07:20 |
December | 98.16 | 32241.91 | 13-DEC-07:50 | 21.21 | 20.28 | 3068.50 | 171177.79 | 22-DEC-10:10 |
Annual Sum or Average | 451049.72 | 1676.02 | ||||||
Minimum of Months | 98.16 | 32241.91 | 21.21 | 20.28 | 1.18 | 5276.84 | ||
Maximum of Months | 1781012.58 | 6392153.19 | 32.04 | 28.51 | 4309.72 | 171740.92 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.322568E+10 | 0.00 | 18841006.08 | 0.321762E+10 | 0.00 | 0.00 |
February | 0.225140E+10 | 0.00 | 16076007.78 | 0.332505E+10 | 0.00 | 0.00 |
March | 0.449857E+09 | 0.00 | 0.114333E+10 | 0.567218E+10 | 0.00 | 0.00 |
April | 52401547.24 | 0.00 | 0.119550E+11 | 0.742200E+10 | 0.00 | 0.00 |
May | 9988412.96 | 0.00 | 0.354743E+11 | 0.767479E+10 | 0.00 | 0.00 |
June | 0.107357E+09 | 0.00 | 0.120795E+12 | 0.109585E+11 | 0.00 | 0.00 |
July | 35833800.26 | 0.00 | 0.166254E+12 | 0.129926E+11 | 0.00 | 0.00 |
August | 0.129561E+09 | 0.00 | 0.170332E+12 | 0.152963E+11 | 0.00 | 0.00 |
September | 10587846.38 | 0.00 | 0.797612E+11 | 0.844461E+10 | 0.00 | 0.00 |
October | 12548123.97 | 0.00 | 0.378106E+11 | 0.797692E+10 | 0.00 | 0.00 |
November | 0.291969E+09 | 0.00 | 0.110735E+10 | 0.525252E+10 | 0.00 | 0.00 |
December | 0.779541E+09 | 0.00 | 11156552.39 | 0.469038E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.735672E+10 | 0.00 | 0.624678E+12 | 0.929234E+11 | 0.00 | 0.00 |
Minimum of Months | 9988412.96 | 0.00 | 11156552.39 | 0.321762E+10 | 0.00 | 0.00 |
Maximum of Months | 0.322568E+10 | 0.00 | 0.170332E+12 | 0.152963E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.236766E+12 | 0.00 | 50727843.69 | 0.321838E+11 | 0.00 | 0.00 |
February | 0.164061E+12 | 0.00 | 4552358.87 | 0.285889E+11 | 0.00 | 0.00 |
March | 0.515609E+11 | 0.00 | 0.652141E+10 | 0.328917E+11 | 0.00 | 0.00 |
April | 0.132691E+11 | 0.00 | 0.786206E+11 | 0.389968E+11 | 0.00 | 0.00 |
May | 0.114491E+09 | 0.00 | 0.298317E+12 | 0.576550E+11 | 0.00 | 0.00 |
June | 0.112838E+10 | 0.00 | 0.100096E+13 | 0.839093E+11 | 0.00 | 0.00 |
July | 0.377969E+09 | 0.00 | 0.132677E+13 | 0.951085E+11 | 0.00 | 0.00 |
August | 0.182212E+10 | 0.00 | 0.129637E+13 | 0.106209E+12 | 0.00 | 0.00 |
September | 0.149381E+09 | 0.00 | 0.690689E+12 | 0.658854E+11 | 0.00 | 0.00 |
October | 0.126783E+10 | 0.00 | 0.294965E+12 | 0.507770E+11 | 0.00 | 0.00 |
November | 0.503911E+11 | 0.00 | 0.783271E+10 | 0.304954E+11 | 0.00 | 0.00 |
December | 0.116518E+12 | 0.00 | 15505479.75 | 0.286613E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.637427E+12 | 0.00 | 0.500112E+13 | 0.651362E+12 | 0.00 | 0.00 |
Minimum of Months | 0.114491E+09 | 0.00 | 4552358.87 | 0.285889E+11 | 0.00 | 0.00 |
Maximum of Months | 0.236766E+12 | 0.00 | 0.132677E+13 | 0.106209E+12 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.457399E+11 | 0.00 | 17100433.12 | 0.395796E+10 | 0.00 | 0.00 |
February | 0.372589E+11 | 0.00 | 11946115.34 | 0.342466E+10 | 0.00 | 0.00 |
March | 0.148298E+11 | 0.00 | 0.596599E+09 | 0.337347E+10 | 0.00 | 0.00 |
April | 0.529619E+10 | 0.00 | 0.801909E+10 | 0.362985E+10 | 0.00 | 0.00 |
May | 0.272537E+09 | 0.00 | 0.313793E+11 | 0.550525E+10 | 0.00 | 0.00 |
June | 64024185.51 | 0.00 | 0.108731E+12 | 0.885780E+10 | 0.00 | 0.00 |
July | 46715621.23 | 0.00 | 0.148916E+12 | 0.106272E+11 | 0.00 | 0.00 |
August | 93737170.25 | 0.00 | 0.144224E+12 | 0.117025E+11 | 0.00 | 0.00 |
September | 7910876.99 | 0.00 | 0.709912E+11 | 0.635927E+10 | 0.00 | 0.00 |
October | 0.127448E+10 | 0.00 | 0.277737E+11 | 0.433162E+10 | 0.00 | 0.00 |
November | 0.162630E+11 | 0.00 | 0.601500E+09 | 0.308995E+10 | 0.00 | 0.00 |
December | 0.303338E+11 | 0.00 | 16443966.69 | 0.342981E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.151481E+12 | 0.00 | 0.541278E+12 | 0.682893E+11 | 0.00 | 0.00 |
Minimum of Months | 7910876.99 | 0.00 | 11946115.34 | 0.308995E+10 | 0.00 | 0.00 |
Maximum of Months | 0.457399E+11 | 0.00 | 0.148916E+12 | 0.117025E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 6817986.26 | 0.127455E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 55406.60 | 0.117914E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.583547E+09 | 0.142060E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.529742E+10 | 0.132029E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.156082E+11 | 0.140503E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.662030E+11 | 0.141291E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.958121E+11 | 0.138260E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.964099E+11 | 0.153191E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.500455E+11 | 0.143894E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.191459E+11 | 0.145526E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.140696E+09 | 0.138265E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 11741.56 | 0.131822E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.349253E+12 | 0.165221E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 11741.56 | 0.117914E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.964099E+11 | 0.153191E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.396097E+12 | 0.177017E+12 | 0.00 | 1.10 |
February | 0.00 | 0.00 | 0.626983E+12 | 0.209782E+12 | 0.00 | 1.28 |
March | 0.00 | 0.00 | 0.996386E+12 | 0.282151E+12 | 0.00 | 0.74 |
April | 0.00 | 0.00 | 0.125900E+13 | 0.325533E+12 | 0.00 | 0.30 |
May | 0.00 | 0.00 | 0.417433E+12 | 0.180567E+12 | 0.00 | 0.06 |
June | 0.00 | 0.00 | 0.728954E+12 | 0.253151E+12 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.109759E+13 | 0.354838E+12 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.140470E+13 | 0.423302E+12 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.421576E+12 | 0.183147E+12 | 0.00 | 0.01 |
October | 0.00 | 0.00 | 0.722551E+12 | 0.237355E+12 | 0.00 | 0.25 |
November | 0.00 | 0.00 | 0.970057E+12 | 0.272916E+12 | 0.00 | 0.46 |
December | 0.00 | 0.00 | 0.129092E+13 | 0.330991E+12 | 0.00 | 1.09 |
Annual Sum or Average | 0.00 | 0.00 | 0.103322E+14 | 0.323075E+13 | 0.00 | 5.29 |
Minimum of Months | 0.00 | 0.00 | 0.396097E+12 | 0.177017E+12 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.140470E+13 | 0.423302E+12 | 0.00 | 1.28 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.401752E+10 | 0.227389E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.994988E+10 | 0.329384E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.183988E+11 | 0.489072E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.242534E+11 | 0.585432E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.709887E+10 | 0.286911E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.140240E+11 | 0.443121E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.216966E+11 | 0.647581E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.282205E+11 | 0.797359E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.743419E+10 | 0.297006E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.133911E+11 | 0.404712E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.178332E+11 | 0.470732E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.241972E+11 | 0.592246E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.190515E+12 | 0.557094E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.401752E+10 | 0.227389E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.282205E+11 | 0.797359E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.101366E+11 | 0.158395E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.667382E+11 | 0.260447E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.154098E+12 | 0.429719E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.218478E+12 | 0.537748E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.611662E+11 | 0.261391E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.132004E+12 | 0.419367E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.207065E+12 | 0.618024E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.268871E+12 | 0.760071E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.660553E+11 | 0.273861E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.117760E+12 | 0.368178E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.146515E+12 | 0.408532E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.199576E+12 | 0.512929E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.164846E+13 | 0.500866E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.101366E+11 | 0.158395E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.268871E+12 | 0.760071E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.365781E+09 | 0.146319E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.473350E+10 | 0.224441E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.136897E+11 | 0.402283E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.207394E+11 | 0.522808E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.568150E+10 | 0.256085E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.132322E+11 | 0.423248E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.208800E+11 | 0.625304E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.270186E+11 | 0.767035E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.635005E+10 | 0.271801E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.107442E+11 | 0.352179E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.126838E+11 | 0.376689E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.176116E+11 | 0.475743E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.153730E+12 | 0.484394E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.365781E+09 | 0.146319E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.270186E+11 | 0.767035E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.321762E+10 | 18841006.08 | 0.322568E+10 | 0.182695E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.332505E+10 | 16076007.78 | 0.225140E+10 | 0.166638E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.567218E+10 | 0.114333E+10 | 0.449857E+09 | 0.481813E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.742200E+10 | 0.119550E+11 | 52401547.24 | 0.488048E+09 | 12219509.69 | 0.00 | 0.00 | 0.00 |
May | 0.767479E+10 | 0.354743E+11 | 9988412.96 | 0.00 | 0.260178E+09 | 0.00 | 0.00 | 0.00 |
June | 0.109585E+11 | 0.120795E+12 | 0.107357E+09 | 0.00 | 0.407412E+10 | 0.00 | 0.00 | 0.00 |
July | 0.129926E+11 | 0.166254E+12 | 35833800.26 | 0.00 | 0.165496E+11 | 0.00 | 0.00 | 0.00 |
August | 0.152963E+11 | 0.170332E+12 | 0.129561E+09 | 0.00 | 0.163643E+11 | 0.00 | 0.00 | 0.00 |
September | 0.844461E+10 | 0.797612E+11 | 10587846.38 | 0.00 | 0.225720E+10 | 0.00 | 0.00 | 0.00 |
October | 0.797692E+10 | 0.378106E+11 | 12548123.97 | 57880580.23 | 32262931.19 | 0.00 | 0.00 | 0.00 |
November | 0.525252E+10 | 0.110735E+10 | 0.291969E+09 | 0.282121E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.469038E+10 | 11156552.39 | 0.779541E+09 | 0.670440E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.929234E+11 | 0.624678E+12 | 0.735672E+10 | 0.498229E+11 | 0.395499E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.321762E+10 | 11156552.39 | 9988412.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.152963E+11 | 0.170332E+12 | 0.322568E+10 | 0.182695E+11 | 0.165496E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.321838E+11 | 50727843.69 | 0.236766E+12 | 0.218466E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.285889E+11 | 4598398.06 | 0.164061E+12 | 0.219398E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.328917E+11 | 0.652141E+10 | 0.515609E+11 | 0.100407E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.389968E+11 | 0.786206E+11 | 0.132691E+11 | 0.147317E+11 | 0.151201E+09 | 0.00 | 0.00 | 0.00 |
May | 0.576550E+11 | 0.298317E+12 | 0.114491E+09 | 30467670.68 | 0.260390E+10 | 0.00 | 0.00 | 0.00 |
June | 0.839093E+11 | 0.100096E+13 | 0.112838E+10 | 0.00 | 0.407854E+11 | 0.00 | 0.00 | 0.00 |
July | 0.951085E+11 | 0.132677E+13 | 0.377969E+09 | 0.00 | 0.164911E+12 | 0.00 | 0.00 | 0.00 |
August | 0.106209E+12 | 0.129637E+13 | 0.182212E+10 | 0.00 | 0.163477E+12 | 0.00 | 0.00 | 0.00 |
September | 0.658854E+11 | 0.690689E+12 | 0.149381E+09 | 0.00 | 0.232607E+11 | 0.00 | 0.00 | 0.00 |
October | 0.507770E+11 | 0.294965E+12 | 0.126783E+10 | 0.165772E+10 | 0.400481E+09 | 0.00 | 0.00 | 0.00 |
November | 0.304954E+11 | 0.783271E+10 | 0.503911E+11 | 0.634059E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.286613E+11 | 15505479.75 | 0.116518E+12 | 0.154430E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.651362E+12 | 0.500112E+13 | 0.637427E+12 | 0.772526E+12 | 0.395590E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.285889E+11 | 4598398.06 | 0.114491E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.106209E+12 | 0.132677E+13 | 0.236766E+12 | 0.219398E+12 | 0.164911E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.395796E+10 | 17100433.12 | 0.457399E+11 | 0.252456E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.342466E+10 | 11946115.34 | 0.372589E+11 | 0.250676E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.337347E+10 | 0.596599E+09 | 0.148298E+11 | 0.128970E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.362985E+10 | 0.801909E+10 | 0.529619E+10 | 0.276442E+10 | 3539211.18 | 0.00 | 0.00 | 0.00 |
May | 0.550525E+10 | 0.313793E+11 | 0.272537E+09 | 22983738.08 | 0.179293E+09 | 0.00 | 0.00 | 0.00 |
June | 0.885780E+10 | 0.108731E+12 | 64024185.51 | 0.00 | 0.339595E+10 | 0.00 | 0.00 | 0.00 |
July | 0.106272E+11 | 0.148916E+12 | 46715621.23 | 0.00 | 0.148584E+11 | 0.00 | 0.00 | 0.00 |
August | 0.117025E+11 | 0.144224E+12 | 93737170.25 | 0.00 | 0.150674E+11 | 0.00 | 0.00 | 0.00 |
September | 0.635927E+10 | 0.709912E+11 | 7910876.99 | 0.00 | 0.184598E+10 | 0.00 | 0.00 | 0.00 |
October | 0.433162E+10 | 0.277737E+11 | 0.127448E+10 | 0.473075E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.308995E+10 | 0.601500E+09 | 0.162630E+11 | 0.843917E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.342981E+10 | 16443966.69 | 0.303338E+11 | 0.196799E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.682893E+11 | 0.541278E+12 | 0.151481E+12 | 0.945897E+11 | 0.353506E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.308995E+10 | 11946115.34 | 7910876.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.117025E+11 | 0.148916E+12 | 0.457399E+11 | 0.252456E+11 | 0.150674E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.127455E+11 | 6817986.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.117914E+11 | 55406.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.142060E+11 | 0.583547E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.132029E+11 | 0.529742E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.140503E+11 | 0.156082E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.141291E+11 | 0.662030E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.138260E+11 | 0.958121E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.153191E+11 | 0.964099E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.143894E+11 | 0.500455E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.145526E+11 | 0.191459E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.138265E+11 | 0.140696E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.131822E+11 | 11741.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.165221E+12 | 0.349253E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.117914E+11 | 11741.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.153191E+11 | 0.964099E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.945869E+11 | 0.316612E+12 | 0.00 | 0.00 | 0.00 | 0.293178E+10 | 0.00 | 0.00 |
February | 0.854333E+11 | 0.506080E+12 | 0.00 | 0.00 | 0.00 | 0.343091E+10 | 0.00 | 0.00 |
March | 0.945869E+11 | 0.810809E+12 | 0.00 | 0.00 | 0.00 | 0.197811E+10 | 0.00 | 0.00 |
April | 0.915357E+11 | 0.102580E+13 | 0.00 | 0.00 | 0.00 | 0.796044E+09 | 0.00 | 0.00 |
May | 0.945869E+11 | 0.331621E+12 | 0.00 | 0.00 | 0.00 | 0.167591E+09 | 0.00 | 0.00 |
June | 0.915357E+11 | 0.567339E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.945869E+11 | 0.837339E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.945869E+11 | 0.107599E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.915357E+11 | 0.329990E+12 | 0.00 | 0.00 | 0.00 | 25619998.77 | 0.00 | 0.00 |
October | 0.945869E+11 | 0.580454E+12 | 0.00 | 0.00 | 0.00 | 0.667964E+09 | 0.00 | 0.00 |
November | 0.915357E+11 | 0.789920E+12 | 0.00 | 0.00 | 0.00 | 0.123769E+10 | 0.00 | 0.00 |
December | 0.945869E+11 | 0.105746E+13 | 0.00 | 0.00 | 0.00 | 0.292862E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.111368E+13 | 0.822941E+13 | 0.00 | 0.00 | 0.00 | 0.141643E+11 | 0.00 | 0.00 |
Minimum of Months | 0.854333E+11 | 0.316612E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.945869E+11 | 0.107599E+13 | 0.00 | 0.00 | 0.00 | 0.343091E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.141698E+10 | 0.316061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.127985E+10 | 0.793589E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.141698E+10 | 0.149250E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.137127E+10 | 0.197704E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.141698E+10 | 0.564674E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.137127E+10 | 0.109641E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.141698E+10 | 0.166377E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.141698E+10 | 0.216639E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.137127E+10 | 0.583540E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.141698E+10 | 0.107610E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.137127E+10 | 0.144972E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.141698E+10 | 0.196917E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.166838E+11 | 0.151490E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.127985E+10 | 0.316061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.141698E+10 | 0.216639E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.135195E+11 | 0.781669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.122112E+11 | 0.529047E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.135195E+11 | 0.124645E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.130834E+11 | 0.177787E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.135195E+11 | 0.485466E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.130834E+11 | 0.103151E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.135195E+11 | 0.158782E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.135195E+11 | 0.206384E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.130834E+11 | 0.517526E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.135195E+11 | 0.944614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.130834E+11 | 0.118746E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.135195E+11 | 0.161803E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.159181E+12 | 0.130678E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.122112E+11 | 0.781669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.135195E+11 | 0.206384E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.137808E+10 | 0.280669E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.124472E+10 | 0.373381E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.137808E+10 | 0.110449E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.133363E+10 | 0.168449E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.137808E+10 | 0.449874E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.133363E+10 | 0.103334E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.137808E+10 | 0.160051E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.137808E+10 | 0.207263E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.133363E+10 | 0.496566E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.137808E+10 | 0.860050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.133363E+10 | 0.102506E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.137808E+10 | 0.142322E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.162258E+11 | 0.121517E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.124472E+10 | 0.280669E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.137808E+10 | 0.207263E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.321762E+10 | 0.322568E+10 | 18841006.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.332505E+10 | 0.225140E+10 | 16076007.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.567218E+10 | 0.449857E+09 | 0.114333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.742200E+10 | 52401547.24 | 0.119550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.767479E+10 | 9988412.96 | 0.354743E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.109585E+11 | 0.107357E+09 | 0.120795E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129926E+11 | 35833800.26 | 0.166254E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.152963E+11 | 0.129561E+09 | 0.170332E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.844461E+10 | 10587846.38 | 0.797612E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.797692E+10 | 12548123.97 | 0.378106E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.525252E+10 | 0.291969E+09 | 0.110735E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.469038E+10 | 0.779541E+09 | 11156552.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.929234E+11 | 0.735672E+10 | 0.624678E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.321762E+10 | 9988412.96 | 11156552.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.152963E+11 | 0.322568E+10 | 0.170332E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.321838E+11 | 0.236766E+12 | 50727843.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.285889E+11 | 0.164061E+12 | 4552358.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.328917E+11 | 0.515609E+11 | 0.652141E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.389968E+11 | 0.132691E+11 | 0.786206E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.576550E+11 | 0.114491E+09 | 0.298317E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.839093E+11 | 0.112838E+10 | 0.100096E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.951085E+11 | 0.377969E+09 | 0.132677E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.106209E+12 | 0.182212E+10 | 0.129637E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.658854E+11 | 0.149381E+09 | 0.690689E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.507770E+11 | 0.126783E+10 | 0.294965E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.304954E+11 | 0.503911E+11 | 0.783271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.286613E+11 | 0.116518E+12 | 15505479.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.651362E+12 | 0.637427E+12 | 0.500112E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.285889E+11 | 0.114491E+09 | 4552358.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.106209E+12 | 0.236766E+12 | 0.132677E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.395796E+10 | 0.457399E+11 | 17100433.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.342466E+10 | 0.372589E+11 | 11946115.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.337347E+10 | 0.148298E+11 | 0.596599E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.362985E+10 | 0.529619E+10 | 0.801909E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.550525E+10 | 0.272537E+09 | 0.313793E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.885780E+10 | 64024185.51 | 0.108731E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.106272E+11 | 46715621.23 | 0.148916E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.117025E+11 | 93737170.25 | 0.144224E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.635927E+10 | 7910876.99 | 0.709912E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.433162E+10 | 0.127448E+10 | 0.277737E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.308995E+10 | 0.162630E+11 | 0.601500E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.342981E+10 | 0.303338E+11 | 16443966.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.682893E+11 | 0.151481E+12 | 0.541278E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.308995E+10 | 7910876.99 | 11946115.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.117025E+11 | 0.457399E+11 | 0.148916E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.127455E+11 | 0.00 | 6817986.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.117914E+11 | 0.00 | 55406.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.142060E+11 | 0.00 | 0.583547E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.132029E+11 | 0.00 | 0.529742E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.140503E+11 | 0.00 | 0.156082E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.141291E+11 | 0.00 | 0.662030E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.138260E+11 | 0.00 | 0.958121E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.153191E+11 | 0.00 | 0.964099E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.143894E+11 | 0.00 | 0.500455E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.145526E+11 | 0.00 | 0.191459E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.138265E+11 | 0.00 | 0.140696E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.131822E+11 | 0.00 | 11741.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.165221E+12 | 0.00 | 0.349253E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.117914E+11 | 0.00 | 11741.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.153191E+11 | 0.00 | 0.964099E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.945869E+11 | 0.00 | 0.396097E+12 | 0.00 | 0.794855E+11 | 0.00 | 0.00 | 0.00 | 0.294498E+10 | 0.00 | 0.00 | 0.00 |
February | 0.854333E+11 | 0.00 | 0.626983E+12 | 0.00 | 0.120902E+12 | 0.00 | 0.00 | 0.00 | 0.344635E+10 | 0.00 | 0.00 | 0.00 |
March | 0.945869E+11 | 0.00 | 0.996386E+12 | 0.00 | 0.185577E+12 | 0.00 | 0.00 | 0.00 | 0.198702E+10 | 0.00 | 0.00 | 0.00 |
April | 0.915357E+11 | 0.00 | 0.125900E+13 | 0.00 | 0.233198E+12 | 0.00 | 0.00 | 0.00 | 0.799627E+09 | 0.00 | 0.00 | 0.00 |
May | 0.945869E+11 | 0.00 | 0.417433E+12 | 0.00 | 0.858120E+11 | 0.00 | 0.00 | 0.00 | 0.168346E+09 | 0.00 | 0.00 | 0.00 |
June | 0.915357E+11 | 0.00 | 0.728954E+12 | 0.00 | 0.161615E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.945869E+11 | 0.00 | 0.109759E+13 | 0.00 | 0.260251E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.945869E+11 | 0.00 | 0.140470E+13 | 0.00 | 0.328715E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.915357E+11 | 0.00 | 0.421576E+12 | 0.00 | 0.915860E+11 | 0.00 | 0.00 | 0.00 | 25735324.77 | 0.00 | 0.00 | 0.00 |
October | 0.945869E+11 | 0.00 | 0.722551E+12 | 0.00 | 0.142098E+12 | 0.00 | 0.00 | 0.00 | 0.670971E+09 | 0.00 | 0.00 | 0.00 |
November | 0.915357E+11 | 0.00 | 0.970057E+12 | 0.00 | 0.180137E+12 | 0.00 | 0.00 | 0.00 | 0.124326E+10 | 0.00 | 0.00 | 0.00 |
December | 0.945869E+11 | 0.00 | 0.129092E+13 | 0.00 | 0.233462E+12 | 0.00 | 0.00 | 0.00 | 0.294180E+10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.111368E+13 | 0.00 | 0.103322E+14 | 0.00 | 0.210284E+13 | 0.00 | 0.00 | 0.00 | 0.142281E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.854333E+11 | 0.00 | 0.396097E+12 | 0.00 | 0.794855E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.945869E+11 | 0.00 | 0.140470E+13 | 0.00 | 0.328715E+12 | 0.00 | 0.00 | 0.00 | 0.344635E+10 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.141698E+10 | 0.00 | 0.401752E+10 | 0.00 | 0.856909E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.127985E+10 | 0.00 | 0.994988E+10 | 0.00 | 0.201398E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.141698E+10 | 0.00 | 0.183988E+11 | 0.00 | 0.347374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.137127E+10 | 0.00 | 0.242534E+11 | 0.00 | 0.448305E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.141698E+10 | 0.00 | 0.709887E+10 | 0.00 | 0.145213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.137127E+10 | 0.00 | 0.140240E+11 | 0.00 | 0.305994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.141698E+10 | 0.00 | 0.216966E+11 | 0.00 | 0.505883E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.141698E+10 | 0.00 | 0.282205E+11 | 0.00 | 0.655661E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.137127E+10 | 0.00 | 0.743419E+10 | 0.00 | 0.159879E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.141698E+10 | 0.00 | 0.133911E+11 | 0.00 | 0.263014E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.137127E+10 | 0.00 | 0.178332E+11 | 0.00 | 0.333604E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.141698E+10 | 0.00 | 0.241972E+11 | 0.00 | 0.450548E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.166838E+11 | 0.00 | 0.190515E+12 | 0.00 | 0.390256E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.127985E+10 | 0.00 | 0.401752E+10 | 0.00 | 0.856909E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.141698E+10 | 0.00 | 0.282205E+11 | 0.00 | 0.655661E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.135195E+11 | 0.00 | 0.101366E+11 | 0.00 | 0.231994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.122112E+11 | 0.00 | 0.667382E+11 | 0.00 | 0.138335E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.135195E+11 | 0.00 | 0.154098E+12 | 0.00 | 0.294524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.130834E+11 | 0.00 | 0.218478E+12 | 0.00 | 0.406914E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.135195E+11 | 0.00 | 0.611662E+11 | 0.00 | 0.126196E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.130834E+11 | 0.00 | 0.132004E+12 | 0.00 | 0.288533E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.135195E+11 | 0.00 | 0.207065E+12 | 0.00 | 0.482828E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.135195E+11 | 0.00 | 0.268871E+12 | 0.00 | 0.624876E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.130834E+11 | 0.00 | 0.660553E+11 | 0.00 | 0.143027E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.135195E+11 | 0.00 | 0.117760E+12 | 0.00 | 0.232982E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.130834E+11 | 0.00 | 0.146515E+12 | 0.00 | 0.277698E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.135195E+11 | 0.00 | 0.199576E+12 | 0.00 | 0.377734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.159181E+12 | 0.00 | 0.164846E+13 | 0.00 | 0.341685E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.122112E+11 | 0.00 | 0.101366E+11 | 0.00 | 0.231994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.135195E+11 | 0.00 | 0.268871E+12 | 0.00 | 0.624876E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.137808E+10 | 0.00 | 0.365781E+09 | 0.00 | 85111568.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.124472E+10 | 0.00 | 0.473350E+10 | 0.00 | 0.999694E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.137808E+10 | 0.00 | 0.136897E+11 | 0.00 | 0.264475E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.133363E+10 | 0.00 | 0.207394E+11 | 0.00 | 0.389446E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.137808E+10 | 0.00 | 0.568150E+10 | 0.00 | 0.118277E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.133363E+10 | 0.00 | 0.132322E+11 | 0.00 | 0.289886E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.137808E+10 | 0.00 | 0.208800E+11 | 0.00 | 0.487496E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.137808E+10 | 0.00 | 0.270186E+11 | 0.00 | 0.629227E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.133363E+10 | 0.00 | 0.635005E+10 | 0.00 | 0.138439E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.137808E+10 | 0.00 | 0.107442E+11 | 0.00 | 0.214371E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.133363E+10 | 0.00 | 0.126838E+11 | 0.00 | 0.243326E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.137808E+10 | 0.00 | 0.176116E+11 | 0.00 | 0.337935E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.162258E+11 | 0.00 | 0.153730E+12 | 0.00 | 0.322136E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.124472E+10 | 0.00 | 0.365781E+09 | 0.00 | 85111568.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.137808E+10 | 0.00 | 0.270186E+11 | 0.00 | 0.629227E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.758624E+10 | 0.00 | 0.00 | 71145072.67 | 0.00 | 0.00 | 0.519523E+11 | 0.00 | 0.43 |
February | 0.381697E+10 | 0.00 | 0.00 | 74159341.04 | 0.00 | 0.00 | 0.526262E+11 | 0.00 | 0.42 |
March | 0.401887E+09 | 0.00 | 0.00 | 0.112727E+09 | 0.00 | 0.00 | 0.706967E+11 | 0.00 | 0.67 |
April | 0.400116E+09 | 16220266.99 | 0.00 | 99815874.72 | 0.00 | 0.00 | 0.627847E+11 | 0.00 | 0.90 |
May | 0.174981E+09 | 0.218822E+09 | 0.00 | 98459272.32 | 0.00 | 0.00 | 0.569852E+11 | 0.00 | 1.26 |
June | 0.115865E+09 | 0.647842E+10 | 0.00 | 53953888.96 | 37371031.08 | 0.00 | 0.162808E+11 | 0.00 | 0.94 |
July | 45486452.05 | 0.206652E+11 | 0.00 | 10566091.35 | 0.127667E+09 | 0.00 | 0.115222E+10 | 0.00 | 0.38 |
August | 91170682.94 | 0.173534E+11 | 0.00 | 41069769.39 | 0.149685E+09 | 0.00 | 0.703104E+10 | 0.00 | 0.71 |
September | 0.227076E+09 | 0.435937E+10 | 0.00 | 82519386.04 | 4290041.45 | 0.00 | 0.315844E+11 | 0.00 | 1.12 |
October | 0.444300E+09 | 0.180841E+09 | 0.00 | 0.120467E+09 | 0.00 | 0.00 | 0.607418E+11 | 0.00 | 1.21 |
November | 0.438305E+09 | 0.00 | 0.00 | 0.121642E+09 | 0.00 | 0.00 | 0.734308E+11 | 0.00 | 0.80 |
December | 0.587309E+09 | 0.00 | 0.00 | 0.117449E+09 | 0.00 | 0.00 | 0.687487E+11 | 0.00 | 0.53 |
Annual Sum or Average | 0.143297E+11 | 0.492723E+11 | 0.00 | 0.100397E+10 | 0.319013E+09 | 0.00 | 0.554015E+12 | 0.00 | 0.78 |
Minimum of Months | 45486452.05 | 0.00 | 0.00 | 10566091.35 | 0.00 | 0.00 | 0.115222E+10 | 0.00 | 0.38 |
Maximum of Months | 0.758624E+10 | 0.206652E+11 | 0.00 | 0.121642E+09 | 0.149685E+09 | 0.00 | 0.734308E+11 | 0.00 | 1.26 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.103036E+11 | 0.00 | 0.00 | 36632078.56 | 0.00 | 0.00 | 0.258013E+11 | 0.00 | 0.33 |
February | 0.604292E+10 | 0.00 | 0.00 | 45586363.08 | 0.00 | 0.00 | 0.305939E+11 | 0.00 | 0.35 |
March | 0.221471E+10 | 0.00 | 0.00 | 89620348.68 | 0.00 | 0.00 | 0.533570E+11 | 0.00 | 0.53 |
April | 0.567086E+10 | 17080016.32 | 0.00 | 84608467.49 | 0.00 | 0.00 | 0.507311E+11 | 0.00 | 0.78 |
May | 0.345530E+10 | 0.148699E+09 | 0.00 | 81135613.60 | 0.00 | 0.00 | 0.404807E+11 | 0.00 | 0.90 |
June | 0.223142E+10 | 0.496402E+10 | 0.00 | 35580307.70 | 0.102514E+09 | 0.00 | 0.888484E+10 | 0.00 | 0.63 |
July | 0.265286E+09 | 0.978551E+10 | 0.00 | 2315131.29 | 0.173492E+09 | 0.00 | 0.291615E+09 | 0.00 | 0.28 |
August | 0.292786E+10 | 0.659614E+10 | 0.00 | 29270500.48 | 0.142369E+09 | 0.00 | 0.430649E+10 | 0.00 | 0.60 |
September | 0.266477E+10 | 0.317641E+10 | 0.00 | 54815900.95 | 32902389.30 | 0.00 | 0.201067E+11 | 0.00 | 0.72 |
October | 0.444478E+10 | 0.437703E+09 | 0.00 | 84837207.81 | 0.00 | 0.00 | 0.395410E+11 | 0.00 | 0.82 |
November | 0.174765E+10 | 0.00 | 0.00 | 85006397.49 | 0.00 | 0.00 | 0.518032E+11 | 0.00 | 0.58 |
December | 0.233019E+10 | 0.00 | 0.00 | 82731888.53 | 0.00 | 0.00 | 0.483123E+11 | 0.00 | 0.41 |
Annual Sum or Average | 0.442994E+11 | 0.251256E+11 | 0.00 | 0.712140E+09 | 0.451278E+09 | 0.00 | 0.374210E+12 | 0.00 | 0.58 |
Minimum of Months | 0.265286E+09 | 0.00 | 0.00 | 2315131.29 | 0.00 | 0.00 | 0.291615E+09 | 0.00 | 0.28 |
Maximum of Months | 0.103036E+11 | 0.978551E+10 | 0.00 | 89620348.68 | 0.173492E+09 | 0.00 | 0.533570E+11 | 0.00 | 0.90 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.231777E+12 | 0.00 | 0.00 | 13279297.30 | 0.00 | 0.714048E+10 | 0.223371E+11 | 0.00 | 0.30 |
February | 0.211990E+12 | 0.00 | 0.00 | 33193138.60 | 0.00 | 0.170713E+10 | 0.395838E+11 | 0.00 | 0.30 |
March | 0.160482E+12 | 0.00 | 0.00 | 0.220120E+09 | 0.00 | 0.00 | 0.178863E+12 | 0.00 | 0.36 |
April | 0.921484E+11 | 57284945.76 | 0.00 | 0.371894E+09 | 0.00 | 0.00 | 0.252285E+12 | 0.00 | 0.49 |
May | 0.371101E+11 | 0.125135E+10 | 0.00 | 0.562791E+09 | 0.00 | 0.00 | 0.310350E+12 | 0.00 | 0.73 |
June | 0.101081E+11 | 0.467360E+11 | 0.00 | 0.304883E+09 | 0.977898E+09 | 0.00 | 0.744865E+11 | 0.00 | 0.54 |
July | 0.948505E+09 | 0.945846E+11 | 0.00 | 20398023.23 | 0.170427E+10 | 0.00 | 0.288309E+10 | 0.00 | 0.27 |
August | 0.800075E+10 | 0.617760E+11 | 0.00 | 0.275328E+09 | 0.133726E+10 | 0.00 | 0.389188E+11 | 0.00 | 0.48 |
September | 0.227969E+11 | 0.308408E+11 | 0.00 | 0.405587E+09 | 0.338498E+09 | 0.00 | 0.156174E+12 | 0.00 | 0.60 |
October | 0.483620E+11 | 0.411899E+10 | 0.00 | 0.499693E+09 | 0.00 | 0.00 | 0.261323E+12 | 0.00 | 0.61 |
November | 0.137191E+12 | 0.00 | 0.00 | 0.235577E+09 | 0.00 | 11999871.28 | 0.183937E+12 | 0.00 | 0.39 |
December | 0.206005E+12 | 0.00 | 0.00 | 73755451.98 | 0.00 | 0.00 | 0.797121E+11 | 0.00 | 0.30 |
Annual Sum or Average | 0.116692E+13 | 0.239365E+12 | 0.00 | 0.301650E+10 | 0.435792E+10 | 0.885961E+10 | 0.160085E+13 | 0.00 | 0.45 |
Minimum of Months | 0.948505E+09 | 0.00 | 0.00 | 13279297.30 | 0.00 | 0.00 | 0.288309E+10 | 0.00 | 0.27 |
Maximum of Months | 0.231777E+12 | 0.945846E+11 | 0.00 | 0.562791E+09 | 0.170427E+10 | 0.714048E+10 | 0.310350E+12 | 0.00 | 0.73 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.186345E+11 | 0.00 | 0.00 | 1736.23 | 0.00 | 0.201053E+10 | 83937269.18 | 0.00 | 0.28 |
February | 0.174017E+11 | 0.00 | 0.00 | 24866.88 | 0.00 | 0.169207E+10 | 0.231420E+09 | 0.00 | 0.28 |
March | 0.222701E+11 | 0.00 | 0.00 | 4631660.03 | 0.00 | 0.461010E+09 | 0.571839E+10 | 0.00 | 0.35 |
April | 0.139669E+11 | 490248.16 | 0.00 | 21544173.89 | 0.00 | 88226067.16 | 0.158473E+11 | 0.00 | 0.46 |
May | 0.837418E+10 | 0.130636E+09 | 0.00 | 43558412.88 | 0.00 | 0.00 | 0.244804E+11 | 0.00 | 0.71 |
June | 0.108464E+10 | 0.459258E+10 | 0.00 | 30059342.14 | 94646060.85 | 0.00 | 0.773716E+10 | 0.00 | 0.55 |
July | 0.164764E+09 | 0.965358E+10 | 0.00 | 2719066.32 | 0.171347E+09 | 0.00 | 0.285974E+09 | 0.00 | 0.28 |
August | 0.684872E+09 | 0.622548E+10 | 0.00 | 27812181.43 | 0.141914E+09 | 0.00 | 0.396544E+10 | 0.00 | 0.51 |
September | 0.419673E+10 | 0.308897E+10 | 0.00 | 31617127.74 | 29566262.05 | 0.00 | 0.122174E+11 | 0.00 | 0.58 |
October | 0.100611E+11 | 0.276995E+09 | 0.00 | 28927975.24 | 0.00 | 1485475.58 | 0.152256E+11 | 0.00 | 0.54 |
November | 0.195420E+11 | 0.00 | 0.00 | 4414433.04 | 0.00 | 0.638217E+09 | 0.474943E+10 | 0.00 | 0.34 |
December | 0.203175E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132528E+10 | 0.00 | 0.00 | 0.29 |
Annual Sum or Average | 0.136699E+12 | 0.239687E+11 | 0.00 | 0.195311E+09 | 0.437474E+09 | 0.621682E+10 | 0.905424E+11 | 0.00 | 0.43 |
Minimum of Months | 0.164764E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.222701E+11 | 0.965358E+10 | 0.00 | 43558412.88 | 0.171347E+09 | 0.201053E+10 | 0.244804E+11 | 0.00 | 0.71 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.320349E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.622361E+09 | 0.00 | 0.00 | 0.28 |
February | 0.317100E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421034E+09 | 0.00 | 0.00 | 0.27 |
March | 0.336336E+10 | 0.00 | 0.00 | 1637480.21 | 0.00 | 276327.98 | 0.148073E+10 | 0.00 | 0.37 |
April | 0.227843E+10 | 2546784.38 | 0.00 | 4834359.58 | 0.00 | 0.00 | 0.328465E+10 | 0.00 | 0.65 |
May | 0.100410E+10 | 27241074.84 | 0.00 | 7940360.08 | 0.00 | 0.00 | 0.422222E+10 | 0.00 | 0.91 |
June | 0.313490E+09 | 0.880600E+09 | 0.00 | 4849736.63 | 12853908.43 | 0.00 | 0.122017E+10 | 0.00 | 0.78 |
July | 33945859.45 | 0.180030E+10 | 0.00 | 437166.39 | 21753652.64 | 0.00 | 46821825.04 | 0.00 | 0.41 |
August | 0.383509E+09 | 0.121613E+10 | 0.00 | 4141202.30 | 17851163.50 | 0.00 | 0.570367E+09 | 0.00 | 0.75 |
September | 0.624392E+09 | 0.467309E+09 | 0.00 | 5106724.48 | 4125524.57 | 0.00 | 0.197076E+10 | 0.00 | 0.73 |
October | 0.157814E+10 | 60175034.82 | 0.00 | 5402555.10 | 0.00 | 0.00 | 0.274407E+10 | 0.00 | 0.68 |
November | 0.275494E+10 | 0.00 | 0.00 | 1849594.53 | 0.00 | 969797.09 | 0.170214E+10 | 0.00 | 0.39 |
December | 0.393385E+10 | 0.00 | 0.00 | 145214.41 | 0.00 | 514011.32 | 0.282301E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.226426E+11 | 0.445430E+10 | 0.00 | 36344393.72 | 56584249.14 | 0.104516E+10 | 0.175242E+11 | 0.00 | 0.54 |
Minimum of Months | 33945859.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.393385E+10 | 0.180030E+10 | 0.00 | 7940360.08 | 21753652.64 | 0.622361E+09 | 0.422222E+10 | 0.00 | 0.91 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.270508E+10 | 0.00 | 0.00 | 145929.28 | 0.00 | 0.511320E+09 | 0.120205E+09 | 0.00 | 0.38 |
February | 0.263310E+10 | 0.00 | 0.00 | 250933.74 | 0.00 | 0.347305E+09 | 0.170983E+09 | 0.00 | 0.37 |
March | 0.263232E+10 | 0.00 | 0.00 | 2646406.89 | 0.00 | 18297581.51 | 0.199875E+10 | 0.00 | 0.54 |
April | 0.216230E+10 | 1864866.20 | 0.00 | 4859770.05 | 0.00 | 0.00 | 0.309185E+10 | 0.00 | 0.94 |
May | 0.944485E+09 | 24299351.41 | 0.00 | 8377053.60 | 0.00 | 0.00 | 0.409402E+10 | 0.00 | 1.32 |
June | 0.273697E+09 | 0.632611E+09 | 0.00 | 4305244.67 | 11189978.34 | 0.00 | 0.120426E+10 | 0.00 | 1.01 |
July | 31543859.56 | 0.130769E+10 | 0.00 | 410828.76 | 18937656.45 | 0.00 | 50941829.22 | 0.00 | 0.50 |
August | 0.337409E+09 | 0.934403E+09 | 0.00 | 3610866.68 | 15540342.00 | 0.00 | 0.579798E+09 | 0.00 | 0.99 |
September | 0.566668E+09 | 0.355255E+09 | 0.00 | 5411395.58 | 5338139.28 | 0.00 | 0.194484E+10 | 0.00 | 1.02 |
October | 0.143426E+10 | 47347768.40 | 0.00 | 5243613.14 | 0.00 | 0.00 | 0.269369E+10 | 0.00 | 0.98 |
November | 0.256789E+10 | 0.00 | 0.00 | 1595791.98 | 0.00 | 14539752.90 | 0.130515E+10 | 0.00 | 0.52 |
December | 0.336481E+10 | 0.00 | 0.00 | 314757.82 | 0.00 | 31490717.55 | 0.300565E+09 | 0.00 | 0.38 |
Annual Sum or Average | 0.196536E+11 | 0.330347E+10 | 0.00 | 37172592.21 | 51006116.07 | 0.922952E+09 | 0.175551E+11 | 0.00 | 0.75 |
Minimum of Months | 31543859.56 | 0.00 | 0.00 | 145929.28 | 0.00 | 0.00 | 50941829.22 | 0.00 | 0.37 |
Maximum of Months | 0.336481E+10 | 0.130769E+10 | 0.00 | 8377053.60 | 18937656.45 | 0.511320E+09 | 0.409402E+10 | 0.00 | 1.32 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.252283E+10 | 0.00 | 0.00 | 2805158.62 | 0.00 | 0.579872E+09 | 0.200734E+10 | 0.00 | 0.37 |
February | 0.224413E+10 | 0.00 | 0.00 | 3677785.45 | 0.00 | 0.371543E+09 | 0.261578E+10 | 0.00 | 0.39 |
March | 0.266445E+10 | 0.00 | 0.00 | 7567964.83 | 0.00 | 45870660.21 | 0.556601E+10 | 0.00 | 0.66 |
April | 0.236231E+10 | 4453253.93 | 0.00 | 8034491.30 | 0.00 | 0.00 | 0.514505E+10 | 0.00 | 0.93 |
May | 0.128429E+10 | 34235705.69 | 0.00 | 9421504.82 | 0.00 | 0.00 | 0.475005E+10 | 0.00 | 1.07 |
June | 0.354244E+09 | 0.976115E+09 | 0.00 | 5192588.35 | 13581299.55 | 0.00 | 0.128274E+10 | 0.00 | 0.86 |
July | 34422850.63 | 0.201217E+10 | 0.00 | 643263.98 | 22984672.29 | 0.00 | 48031573.48 | 0.00 | 0.47 |
August | 0.395787E+09 | 0.157805E+10 | 0.00 | 6131265.33 | 18861344.80 | 0.00 | 0.730791E+09 | 0.00 | 0.99 |
September | 0.545652E+09 | 0.642024E+09 | 0.00 | 11921588.28 | 4358984.30 | 0.00 | 0.350191E+10 | 0.00 | 1.17 |
October | 0.100579E+10 | 0.145167E+09 | 0.00 | 15472352.28 | 0.00 | 0.00 | 0.727026E+10 | 0.00 | 1.35 |
November | 0.215856E+10 | 0.00 | 0.00 | 6924496.38 | 0.00 | 30567760.61 | 0.509650E+10 | 0.00 | 0.67 |
December | 0.290369E+10 | 0.00 | 0.00 | 4709423.68 | 0.00 | 73643786.57 | 0.327358E+10 | 0.00 | 0.41 |
Annual Sum or Average | 0.184761E+11 | 0.539222E+10 | 0.00 | 82501883.30 | 59786300.94 | 0.110150E+10 | 0.412880E+11 | 0.00 | 0.78 |
Minimum of Months | 34422850.63 | 0.00 | 0.00 | 643263.98 | 0.00 | 0.00 | 48031573.48 | 0.00 | 0.37 |
Maximum of Months | 0.290369E+10 | 0.201217E+10 | 0.00 | 15472352.28 | 22984672.29 | 0.579872E+09 | 0.727026E+10 | 0.00 | 1.35 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.361168E+10 | 0.00 | 0.00 | 513138.27 | 0.00 | 0.137243E+09 | 0.504676E+09 | 0.00 | 0.48 |
February | 0.282315E+10 | 0.00 | 0.00 | 1455668.94 | 0.00 | 43870189.57 | 0.137152E+10 | 0.00 | 0.50 |
March | 0.110339E+10 | 0.00 | 0.00 | 8495631.35 | 0.00 | 0.00 | 0.626244E+10 | 0.00 | 0.90 |
April | 0.635075E+09 | 4920091.59 | 0.00 | 14195191.65 | 0.00 | 0.00 | 0.815792E+10 | 0.00 | 1.63 |
May | 0.550419E+09 | 32546692.97 | 0.00 | 11370805.13 | 0.00 | 0.00 | 0.564546E+10 | 0.00 | 1.66 |
June | 0.213134E+09 | 0.104045E+10 | 0.00 | 6975104.38 | 10477031.55 | 0.00 | 0.160511E+10 | 0.00 | 1.44 |
July | 20291273.91 | 0.213545E+10 | 0.00 | 1321722.82 | 12411319.95 | 0.00 | 69923188.95 | 0.00 | 0.76 |
August | 0.197600E+09 | 0.167331E+10 | 0.00 | 8008093.92 | 8991116.72 | 0.00 | 0.104477E+10 | 0.00 | 1.59 |
September | 0.375034E+09 | 0.533503E+09 | 0.00 | 7946327.92 | 3699083.72 | 0.00 | 0.263861E+10 | 0.00 | 1.33 |
October | 0.719135E+09 | 90603966.99 | 0.00 | 10701744.58 | 0.00 | 0.00 | 0.515325E+10 | 0.00 | 1.47 |
November | 0.122095E+10 | 0.00 | 0.00 | 6006162.29 | 0.00 | 0.00 | 0.465869E+10 | 0.00 | 0.82 |
December | 0.165102E+10 | 0.00 | 0.00 | 4502839.29 | 0.00 | 0.00 | 0.375033E+10 | 0.00 | 0.55 |
Annual Sum or Average | 0.131209E+11 | 0.551078E+10 | 0.00 | 81492430.54 | 35578551.94 | 0.181113E+09 | 0.408627E+11 | 0.00 | 1.10 |
Minimum of Months | 20291273.91 | 0.00 | 0.00 | 513138.27 | 0.00 | 0.00 | 69923188.95 | 0.00 | 0.48 |
Maximum of Months | 0.361168E+10 | 0.213545E+10 | 0.00 | 14195191.65 | 12411319.95 | 0.137243E+09 | 0.815792E+10 | 0.00 | 1.66 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.835971E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258545E+11 | 0.00 | 0.00 | 0.31 |
February | 0.857080E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.244547E+11 | 0.00 | 0.00 | 0.31 |
March | 0.294545E+11 | 0.00 | 0.00 | 264731.85 | 0.00 | 0.101922E+11 | 0.482392E+09 | 0.00 | 0.34 |
April | 0.283408E+11 | 8117065.72 | 0.00 | 12241985.73 | 0.00 | 0.204431E+10 | 0.689295E+10 | 0.00 | 0.43 |
May | 0.157576E+11 | 0.242735E+09 | 0.00 | 47233388.50 | 0.00 | 0.00 | 0.238674E+11 | 0.00 | 0.70 |
June | 0.184455E+10 | 0.848878E+10 | 0.00 | 38128691.95 | 0.122814E+09 | 0.00 | 0.968414E+10 | 0.00 | 0.68 |
July | 0.124002E+09 | 0.182571E+11 | 0.00 | 3271665.20 | 0.214038E+09 | 0.00 | 0.454255E+09 | 0.00 | 0.42 |
August | 0.121342E+10 | 0.121469E+11 | 0.00 | 35384985.31 | 0.167946E+09 | 0.00 | 0.480396E+10 | 0.00 | 0.63 |
September | 0.926747E+10 | 0.447073E+10 | 0.00 | 32199971.06 | 54740012.07 | 0.00 | 0.109494E+11 | 0.00 | 0.59 |
October | 0.232249E+11 | 0.535251E+09 | 0.00 | 17582399.16 | 115070.53 | 0.189539E+09 | 0.809688E+10 | 0.00 | 0.51 |
November | 0.265997E+11 | 0.00 | 0.00 | 203218.89 | 0.00 | 0.944129E+10 | 0.297988E+09 | 0.00 | 0.34 |
December | 0.143259E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216391E+11 | 0.00 | 0.00 | 0.29 |
Annual Sum or Average | 0.167083E+12 | 0.441496E+11 | 0.00 | 0.186511E+09 | 0.559652E+09 | 0.938157E+11 | 0.655294E+11 | 0.00 | 0.46 |
Minimum of Months | 0.124002E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.294545E+11 | 0.182571E+11 | 0.00 | 47233388.50 | 0.214038E+09 | 0.258545E+11 | 0.238674E+11 | 0.00 | 0.70 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.103402E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206275E+11 | 0.00 | 0.00 | 0.43 |
February | 0.129373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170201E+11 | 0.00 | 0.00 | 0.43 |
March | 0.261784E+11 | 0.00 | 0.00 | 6456924.96 | 0.00 | 0.583564E+10 | 0.626471E+10 | 0.00 | 0.50 |
April | 0.201923E+11 | 7663826.55 | 0.00 | 30268479.17 | 0.00 | 0.171939E+10 | 0.187930E+11 | 0.00 | 0.75 |
May | 0.140836E+11 | 0.236441E+09 | 0.00 | 64473760.96 | 0.00 | 0.00 | 0.308616E+11 | 0.00 | 1.20 |
June | 0.150641E+10 | 0.677692E+10 | 0.00 | 42225236.05 | 0.145105E+09 | 0.00 | 0.117129E+11 | 0.00 | 1.01 |
July | 0.112374E+09 | 0.152469E+11 | 0.00 | 4270799.46 | 0.199152E+09 | 0.00 | 0.603848E+09 | 0.00 | 0.58 |
August | 0.100118E+10 | 0.111670E+11 | 0.00 | 42197212.30 | 0.156266E+09 | 0.00 | 0.639830E+10 | 0.00 | 1.00 |
September | 0.742589E+10 | 0.365294E+10 | 0.00 | 44801918.33 | 0.194848E+09 | 0.00 | 0.148559E+11 | 0.00 | 0.94 |
October | 0.160932E+11 | 0.490034E+09 | 0.00 | 32830188.53 | 0.00 | 0.142340E+09 | 0.168355E+11 | 0.00 | 0.84 |
November | 0.245685E+11 | 0.00 | 0.00 | 2410263.58 | 0.00 | 0.645706E+10 | 0.280699E+10 | 0.00 | 0.49 |
December | 0.166639E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166566E+11 | 0.00 | 0.00 | 0.42 |
Annual Sum or Average | 0.151103E+12 | 0.375779E+11 | 0.00 | 0.269935E+09 | 0.695371E+09 | 0.684586E+11 | 0.109133E+12 | 0.00 | 0.72 |
Minimum of Months | 0.112374E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 0.261784E+11 | 0.152469E+11 | 0.00 | 64473760.96 | 0.199152E+09 | 0.206275E+11 | 0.308616E+11 | 0.00 | 1.20 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.151749E+11 | 0.00 | 0.00 | 17419002.38 | 0.00 | 0.140247E+11 | 0.113733E+11 | 0.00 | 0.36 |
February | 0.153969E+11 | 0.00 | 0.00 | 24755094.42 | 0.00 | 0.113316E+11 | 0.164279E+11 | 0.00 | 0.39 |
March | 0.228659E+11 | 0.00 | 0.00 | 53701076.31 | 0.00 | 0.478289E+10 | 0.376436E+11 | 0.00 | 0.57 |
April | 0.206828E+11 | 20073907.90 | 0.00 | 55339153.63 | 0.00 | 0.176636E+10 | 0.332212E+11 | 0.00 | 0.71 |
May | 0.148797E+11 | 0.315734E+09 | 0.00 | 72261624.21 | 0.00 | 0.00 | 0.358113E+11 | 0.00 | 0.92 |
June | 0.240766E+10 | 0.968326E+10 | 0.00 | 43373076.78 | 0.128653E+09 | 0.00 | 0.107329E+11 | 0.00 | 0.78 |
July | 0.129671E+09 | 0.210280E+11 | 0.00 | 5007557.42 | 0.224215E+09 | 0.00 | 0.456195E+09 | 0.00 | 0.49 |
August | 0.112909E+10 | 0.168920E+11 | 0.00 | 61169747.95 | 0.175931E+09 | 0.00 | 0.685047E+10 | 0.00 | 0.92 |
September | 0.632569E+10 | 0.673662E+10 | 0.00 | 0.110239E+09 | 60114899.65 | 0.00 | 0.297603E+11 | 0.00 | 1.10 |
October | 0.955017E+10 | 0.166994E+10 | 0.00 | 0.134980E+09 | 0.00 | 0.00 | 0.616638E+11 | 0.00 | 1.22 |
November | 0.192905E+11 | 0.00 | 0.00 | 47842873.66 | 0.00 | 0.408019E+10 | 0.338613E+11 | 0.00 | 0.57 |
December | 0.182789E+11 | 0.00 | 0.00 | 24254825.66 | 0.00 | 0.113845E+11 | 0.162584E+11 | 0.00 | 0.37 |
Annual Sum or Average | 0.146112E+12 | 0.563456E+11 | 0.00 | 0.650343E+09 | 0.588914E+09 | 0.473702E+11 | 0.294061E+12 | 0.00 | 0.70 |
Minimum of Months | 0.129671E+09 | 0.00 | 0.00 | 5007557.42 | 0.00 | 0.00 | 0.456195E+09 | 0.00 | 0.36 |
Maximum of Months | 0.228659E+11 | 0.210280E+11 | 0.00 | 0.134980E+09 | 0.224215E+09 | 0.140247E+11 | 0.616638E+11 | 0.00 | 1.22 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.143455E+11 | 0.00 | 0.00 | 152109.07 | 0.00 | 0.174492E+11 | 0.362497E+09 | 0.00 | 0.45 |
February | 0.151149E+11 | 0.00 | 0.00 | 1644582.96 | 0.00 | 0.148207E+11 | 0.136720E+10 | 0.00 | 0.45 |
March | 0.277659E+11 | 0.00 | 0.00 | 14372104.63 | 0.00 | 0.438709E+10 | 0.104826E+11 | 0.00 | 0.57 |
April | 0.224414E+11 | 11502833.28 | 0.00 | 35168332.89 | 0.00 | 0.102208E+10 | 0.203920E+11 | 0.00 | 0.83 |
May | 0.131792E+11 | 0.286583E+09 | 0.00 | 62452894.16 | 0.00 | 0.00 | 0.306183E+11 | 0.00 | 1.22 |
June | 0.172946E+10 | 0.864290E+10 | 0.00 | 40461185.17 | 90286967.49 | 0.00 | 0.979858E+10 | 0.00 | 1.07 |
July | 0.108561E+09 | 0.173729E+11 | 0.00 | 5312621.61 | 0.127621E+09 | 0.00 | 0.355505E+09 | 0.00 | 0.62 |
August | 0.101973E+10 | 0.133415E+11 | 0.00 | 42376720.10 | 0.127425E+09 | 0.00 | 0.484614E+10 | 0.00 | 1.07 |
September | 0.770817E+10 | 0.464911E+10 | 0.00 | 47057076.04 | 55718047.67 | 0.00 | 0.138463E+11 | 0.00 | 0.99 |
October | 0.177154E+11 | 0.802344E+09 | 0.00 | 36587900.37 | 0.00 | 7567963.80 | 0.179408E+11 | 0.00 | 0.93 |
November | 0.262458E+11 | 0.00 | 0.00 | 3937183.01 | 0.00 | 0.598951E+10 | 0.359879E+10 | 0.00 | 0.53 |
December | 0.211340E+11 | 0.00 | 0.00 | 116191.98 | 0.00 | 0.132522E+11 | 0.315118E+09 | 0.00 | 0.44 |
Annual Sum or Average | 0.168508E+12 | 0.451068E+11 | 0.00 | 0.289639E+09 | 0.401052E+09 | 0.569284E+11 | 0.113924E+12 | 0.00 | 0.77 |
Minimum of Months | 0.108561E+09 | 0.00 | 0.00 | 116191.98 | 0.00 | 0.00 | 0.315118E+09 | 0.00 | 0.44 |
Maximum of Months | 0.277659E+11 | 0.173729E+11 | 0.00 | 62452894.16 | 0.127621E+09 | 0.174492E+11 | 0.306183E+11 | 0.00 | 1.22 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.368314E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251905E+10 | 0.00 | 0.00 | 0.32 |
February | 0.379347E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234758E+10 | 0.00 | 0.00 | 0.32 |
March | 0.188627E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179002E+10 | 0.00 | 0.00 | 0.36 |
April | 0.233121E+10 | 63959.81 | 0.00 | 1106645.35 | 0.00 | 0.629852E+09 | 0.623213E+09 | 0.00 | 0.44 |
May | 0.190535E+10 | 24310380.02 | 0.00 | 3953329.85 | 0.00 | 32861423.37 | 0.201398E+10 | 0.00 | 0.71 |
June | 0.254935E+09 | 0.811233E+09 | 0.00 | 3936002.88 | 12279479.95 | 0.00 | 0.976158E+09 | 0.00 | 0.69 |
July | 17694705.23 | 0.181484E+10 | 0.00 | 543982.54 | 22001385.53 | 0.00 | 49779173.81 | 0.00 | 0.42 |
August | 0.148076E+09 | 0.119388E+10 | 0.00 | 3608870.47 | 18806025.27 | 0.00 | 0.482964E+09 | 0.00 | 0.66 |
September | 0.975349E+09 | 0.429073E+09 | 0.00 | 2686288.58 | 18116427.45 | 0.00 | 0.955941E+09 | 0.00 | 0.59 |
October | 0.212766E+10 | 34357768.28 | 0.00 | 1192126.12 | 399735.90 | 0.218092E+09 | 0.540683E+09 | 0.00 | 0.49 |
November | 0.170503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152346E+10 | 0.00 | 0.00 | 0.35 |
December | 0.283968E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.264231E+10 | 0.00 | 0.00 | 0.31 |
Annual Sum or Average | 0.123832E+11 | 0.430775E+10 | 0.00 | 17027245.80 | 71603054.09 | 0.117032E+11 | 0.564272E+10 | 0.00 | 0.47 |
Minimum of Months | 17694705.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
Maximum of Months | 0.233121E+10 | 0.181484E+10 | 0.00 | 3953329.85 | 22001385.53 | 0.264231E+10 | 0.201398E+10 | 0.00 | 0.71 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.539463E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195423E+10 | 0.00 | 0.00 | 0.42 |
February | 0.699195E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162055E+10 | 0.00 | 0.00 | 0.42 |
March | 0.198263E+10 | 0.00 | 0.00 | 257583.14 | 0.00 | 0.103611E+10 | 0.317959E+09 | 0.00 | 0.50 |
April | 0.166716E+10 | 69665.57 | 0.00 | 2641590.23 | 0.00 | 0.478489E+09 | 0.162218E+10 | 0.00 | 0.74 |
May | 0.146557E+10 | 23391754.73 | 0.00 | 6736334.30 | 0.00 | 19569220.17 | 0.296105E+10 | 0.00 | 1.21 |
June | 0.147551E+09 | 0.656241E+09 | 0.00 | 4573540.39 | 22264917.47 | 0.00 | 0.124476E+10 | 0.00 | 1.03 |
July | 14680534.53 | 0.153242E+10 | 0.00 | 723193.78 | 20109697.12 | 0.00 | 68369855.31 | 0.00 | 0.60 |
August | 98096348.88 | 0.111571E+10 | 0.00 | 4560112.59 | 16655383.64 | 0.00 | 0.674015E+09 | 0.00 | 1.07 |
September | 0.683616E+09 | 0.364857E+09 | 0.00 | 4487785.65 | 28159986.92 | 0.00 | 0.143353E+10 | 0.00 | 0.94 |
October | 0.149303E+10 | 33652413.12 | 0.00 | 2636416.56 | 64631.88 | 0.105875E+09 | 0.127942E+10 | 0.00 | 0.80 |
November | 0.183839E+10 | 0.00 | 0.00 | 33536.75 | 0.00 | 0.997010E+09 | 70468445.68 | 0.00 | 0.49 |
December | 0.790900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178977E+10 | 0.00 | 0.00 | 0.42 |
Annual Sum or Average | 0.114203E+11 | 0.372634E+10 | 0.00 | 26650093.39 | 87254617.03 | 0.800160E+10 | 0.967175E+10 | 0.00 | 0.72 |
Minimum of Months | 14680534.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 0.198263E+10 | 0.153242E+10 | 0.00 | 6736334.30 | 28159986.92 | 0.195423E+10 | 0.296105E+10 | 0.00 | 1.21 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.987160E+09 | 0.00 | 0.00 | 1006066.52 | 0.00 | 0.167482E+10 | 0.665871E+09 | 0.00 | 0.35 |
February | 0.104519E+10 | 0.00 | 0.00 | 1542723.13 | 0.00 | 0.126098E+10 | 0.101680E+10 | 0.00 | 0.37 |
March | 0.180295E+10 | 0.00 | 0.00 | 3938828.83 | 0.00 | 0.960408E+09 | 0.298897E+10 | 0.00 | 0.54 |
April | 0.181356E+10 | 179818.59 | 0.00 | 4849529.83 | 0.00 | 0.555404E+09 | 0.304855E+10 | 0.00 | 0.71 |
May | 0.186788E+10 | 31143432.63 | 0.00 | 6951267.86 | 0.00 | 34671613.19 | 0.334236E+10 | 0.00 | 0.94 |
June | 0.307191E+09 | 0.911558E+09 | 0.00 | 4642782.87 | 16486812.06 | 0.00 | 0.115635E+10 | 0.00 | 0.80 |
July | 15994634.13 | 0.206808E+10 | 0.00 | 997646.12 | 26562423.20 | 0.00 | 59293751.96 | 0.00 | 0.49 |
August | 0.138822E+09 | 0.163525E+10 | 0.00 | 6523622.75 | 20149274.82 | 0.00 | 0.757274E+09 | 0.00 | 0.98 |
September | 0.699250E+09 | 0.653987E+09 | 0.00 | 11776129.43 | 13902039.44 | 0.00 | 0.299596E+10 | 0.00 | 1.11 |
October | 0.102050E+10 | 0.107937E+09 | 0.00 | 11471181.05 | 0.00 | 87301309.75 | 0.539462E+10 | 0.00 | 1.16 |
November | 0.171031E+10 | 0.00 | 0.00 | 2921965.22 | 0.00 | 0.815912E+09 | 0.211406E+10 | 0.00 | 0.52 |
December | 0.120250E+10 | 0.00 | 0.00 | 1156979.09 | 0.00 | 0.148086E+10 | 0.743318E+09 | 0.00 | 0.35 |
Annual Sum or Average | 0.126113E+11 | 0.540813E+10 | 0.00 | 57778722.70 | 77100549.53 | 0.687036E+10 | 0.242834E+11 | 0.00 | 0.70 |
Minimum of Months | 15994634.13 | 0.00 | 0.00 | 997646.12 | 0.00 | 0.00 | 59293751.96 | 0.00 | 0.35 |
Maximum of Months | 0.186788E+10 | 0.206808E+10 | 0.00 | 11776129.43 | 26562423.20 | 0.167482E+10 | 0.539462E+10 | 0.00 | 1.16 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.893477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181275E+10 | 0.00 | 0.00 | 0.46 |
February | 0.909593E+09 | 0.00 | 0.00 | 76936.37 | 0.00 | 0.151446E+10 | 95774529.34 | 0.00 | 0.46 |
March | 0.214973E+10 | 0.00 | 0.00 | 1083172.48 | 0.00 | 0.827312E+09 | 0.908309E+09 | 0.00 | 0.58 |
April | 0.203719E+10 | 65086.59 | 0.00 | 3190715.02 | 0.00 | 0.350767E+09 | 0.192455E+10 | 0.00 | 0.84 |
May | 0.166690E+10 | 27616957.70 | 0.00 | 5964595.20 | 0.00 | 14497437.90 | 0.288822E+10 | 0.00 | 1.25 |
June | 0.223725E+09 | 0.805620E+09 | 0.00 | 4535011.56 | 9980053.10 | 0.00 | 0.104166E+10 | 0.00 | 1.09 |
July | 12684342.94 | 0.169623E+10 | 0.00 | 1295023.74 | 15405086.75 | 0.00 | 49973185.52 | 0.00 | 0.62 |
August | 0.116456E+09 | 0.127918E+10 | 0.00 | 4309537.76 | 13882226.99 | 0.00 | 0.509148E+09 | 0.00 | 1.11 |
September | 0.843566E+09 | 0.448792E+09 | 0.00 | 4717514.49 | 14838234.25 | 0.00 | 0.132777E+10 | 0.00 | 1.01 |
October | 0.173708E+10 | 53357363.22 | 0.00 | 2989867.98 | 0.00 | 0.102641E+09 | 0.151039E+10 | 0.00 | 0.91 |
November | 0.204292E+10 | 0.00 | 0.00 | 205279.23 | 0.00 | 0.964218E+09 | 0.196076E+09 | 0.00 | 0.54 |
December | 0.104087E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176408E+10 | 0.00 | 0.00 | 0.46 |
Annual Sum or Average | 0.136742E+11 | 0.431087E+10 | 0.00 | 28367653.83 | 54105601.08 | 0.735072E+10 | 0.104519E+11 | 0.00 | 0.78 |
Minimum of Months | 12684342.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.46 |
Maximum of Months | 0.214973E+10 | 0.169623E+10 | 0.00 | 5964595.20 | 15405086.75 | 0.181275E+10 | 0.288822E+10 | 0.00 | 1.25 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 928767.74 | 0.00 | 0.00 | 2548389.29 | 0.00 | 0.00 | 0.697246E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 6765420.85 | 0.00 | 0.00 | 0.660260E+09 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 13907060.00 | 0.00 | 0.00 | 0.624831E+09 | 0.00 | 0.30 |
April | 0.00 | 0.00 | 0.00 | 16413998.41 | 0.00 | 0.00 | 0.424898E+09 | 0.00 | 0.29 |
May | 0.00 | 4443004.17 | 0.00 | 3689020.81 | 0.00 | 0.00 | 0.257041E+09 | 0.00 | 0.29 |
June | 0.00 | 0.147525E+09 | 0.00 | 2580700.21 | 0.00 | 0.00 | 44292751.82 | 0.00 | 0.31 |
July | 0.00 | 0.359779E+09 | 0.00 | 331570.78 | 0.00 | 0.00 | 958267.14 | 0.00 | 0.28 |
August | 0.00 | 0.282954E+09 | 0.00 | 4310272.59 | 0.00 | 0.00 | 21205370.26 | 0.00 | 0.31 |
September | 0.00 | 75536524.52 | 0.00 | 2252683.69 | 0.00 | 0.00 | 0.116260E+09 | 0.00 | 0.29 |
October | 0.00 | 11913462.35 | 0.00 | 6629981.76 | 0.00 | 0.00 | 0.239041E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 11975914.29 | 0.00 | 0.00 | 0.512738E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 16661145.05 | 0.00 | 0.00 | 0.639744E+09 | 0.00 | 0.28 |
Annual Sum or Average | 928767.74 | 0.882151E+09 | 0.00 | 88066157.74 | 0.00 | 0.00 | 0.423852E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 331570.78 | 0.00 | 0.00 | 958267.14 | 0.00 | 0.28 |
Maximum of Months | 928767.74 | 0.359779E+09 | 0.00 | 16661145.05 | 0.00 | 0.00 | 0.697246E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.197226E+10 | 0.00 | 0.00 | 7818002.69 | 0.00 | 0.00 | 0.496743E+10 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 49080490.09 | 0.00 | 0.00 | 0.662234E+10 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 0.119306E+09 | 0.00 | 0.00 | 0.626681E+10 | 0.00 | 0.30 |
April | 0.00 | 0.00 | 0.00 | 0.149805E+09 | 0.00 | 0.00 | 0.425915E+10 | 0.00 | 0.29 |
May | 0.00 | 43058339.57 | 0.00 | 31921218.59 | 0.00 | 0.00 | 0.259013E+10 | 0.00 | 0.29 |
June | 0.00 | 0.146576E+10 | 0.00 | 24386674.46 | 0.00 | 0.00 | 0.443876E+09 | 0.00 | 0.31 |
July | 0.00 | 0.359146E+10 | 0.00 | 3176855.36 | 0.00 | 0.00 | 9649135.25 | 0.00 | 0.28 |
August | 0.00 | 0.283111E+10 | 0.00 | 41127527.53 | 0.00 | 0.00 | 0.212641E+09 | 0.00 | 0.31 |
September | 0.00 | 0.740382E+09 | 0.00 | 19682708.70 | 0.00 | 0.00 | 0.117228E+10 | 0.00 | 0.29 |
October | 0.00 | 0.115847E+09 | 0.00 | 59280850.24 | 0.00 | 0.00 | 0.239947E+10 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 0.101386E+09 | 0.00 | 0.00 | 0.514453E+10 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 0.141788E+09 | 0.00 | 0.00 | 0.642181E+10 | 0.00 | 0.28 |
Annual Sum or Average | 0.197226E+10 | 0.878762E+10 | 0.00 | 0.748760E+09 | 0.00 | 0.00 | 0.405101E+11 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 3176855.36 | 0.00 | 0.00 | 9649135.25 | 0.00 | 0.28 |
Maximum of Months | 0.197226E+10 | 0.359146E+10 | 0.00 | 0.149805E+09 | 0.00 | 0.00 | 0.662234E+10 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.410085E+09 | 0.00 | 0.00 | 363919.27 | 0.00 | 0.00 | 0.273845E+09 | 0.00 | 0.28 |
February | 279064.10 | 0.00 | 0.00 | 4077054.60 | 0.00 | 0.00 | 0.662689E+09 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 10981158.33 | 0.00 | 0.00 | 0.627833E+09 | 0.00 | 0.30 |
April | 0.00 | 0.00 | 0.00 | 14425740.99 | 0.00 | 0.00 | 0.426687E+09 | 0.00 | 0.29 |
May | 1738873.44 | 4347020.22 | 0.00 | 2972764.01 | 0.00 | 0.00 | 0.258804E+09 | 0.00 | 0.29 |
June | 0.00 | 0.146582E+09 | 0.00 | 2449750.39 | 0.00 | 0.00 | 44432597.84 | 0.00 | 0.31 |
July | 0.00 | 0.359076E+09 | 0.00 | 319384.13 | 0.00 | 0.00 | 966851.06 | 0.00 | 0.28 |
August | 0.00 | 0.283993E+09 | 0.00 | 4127838.46 | 0.00 | 0.00 | 21300581.97 | 0.00 | 0.31 |
September | 0.00 | 74094298.53 | 0.00 | 1854532.29 | 0.00 | 0.00 | 0.117803E+09 | 0.00 | 0.29 |
October | 0.00 | 11478911.16 | 0.00 | 5482554.00 | 0.00 | 0.00 | 0.240929E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 9176464.23 | 0.00 | 0.00 | 0.515693E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 13087659.81 | 0.00 | 0.00 | 0.643291E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.412103E+09 | 0.879571E+09 | 0.00 | 69318820.51 | 0.00 | 0.00 | 0.383427E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 319384.13 | 0.00 | 0.00 | 966851.06 | 0.00 | 0.28 |
Maximum of Months | 0.410085E+09 | 0.359076E+09 | 0.00 | 14425740.99 | 0.00 | 0.00 | 0.662689E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.211049E+09 | 0.00 | 0.00 | 0.177198E+11 | 0.00 | 0.32 |
February | 0.00 | 0.00 | 0.00 | 0.390352E+09 | 0.00 | 0.00 | 0.174080E+11 | 0.00 | 0.32 |
March | 0.00 | 0.00 | 0.00 | 0.713227E+09 | 0.00 | 0.00 | 0.150425E+11 | 0.00 | 0.34 |
April | 0.00 | 0.00 | 0.00 | 0.822981E+09 | 0.00 | 0.00 | 0.960518E+10 | 0.00 | 0.32 |
May | 0.00 | 0.136557E+09 | 0.00 | 0.192800E+09 | 0.00 | 0.00 | 0.552586E+10 | 0.00 | 0.33 |
June | 0.00 | 0.340254E+10 | 0.00 | 0.124444E+09 | 0.00 | 0.00 | 0.917716E+09 | 0.00 | 0.34 |
July | 0.00 | 0.796100E+10 | 0.00 | 14179609.08 | 0.00 | 0.00 | 15855041.49 | 0.00 | 0.31 |
August | 0.00 | 0.507180E+10 | 0.00 | 0.236593E+09 | 0.00 | 0.00 | 0.504309E+09 | 0.00 | 0.35 |
September | 0.00 | 0.188931E+10 | 0.00 | 0.119408E+09 | 0.00 | 0.00 | 0.245092E+10 | 0.00 | 0.32 |
October | 0.00 | 0.303644E+09 | 0.00 | 0.330732E+09 | 0.00 | 0.00 | 0.563743E+10 | 0.00 | 0.32 |
November | 0.00 | 0.00 | 0.00 | 0.620083E+09 | 0.00 | 0.00 | 0.119145E+11 | 0.00 | 0.32 |
December | 0.00 | 0.00 | 0.00 | 0.855994E+09 | 0.00 | 0.00 | 0.161238E+11 | 0.00 | 0.32 |
Annual Sum or Average | 0.00 | 0.187648E+11 | 0.00 | 0.463184E+10 | 0.00 | 0.00 | 0.102866E+12 | 0.00 | 0.33 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 14179609.08 | 0.00 | 0.00 | 15855041.49 | 0.00 | 0.31 |
Maximum of Months | 0.00 | 0.796100E+10 | 0.00 | 0.855994E+09 | 0.00 | 0.00 | 0.177198E+11 | 0.00 | 0.35 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 09:04:39
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.252855E+12 | 0.441479E+11 | 0.00 | 0.145282E+13 | 0.544519E+12 |
February | 0.399891E+12 | 0.398302E+11 | 0.00 | 0.148917E+13 | 0.824512E+12 |
March | 0.661306E+12 | 0.324567E+11 | 0.00 | 0.183654E+13 | 0.129742E+13 |
April | 0.703586E+12 | 0.213707E+11 | 0.00 | 0.183283E+13 | 0.179287E+13 |
May | 0.890318E+12 | 0.123025E+11 | 0.00 | 0.176715E+13 | 0.107780E+13 |
June | 0.868351E+12 | 0.223477E+09 | 0.00 | 0.398317E+12 | 0.255325E+13 |
July | 0.847990E+12 | -0.111996E+11 | 0.00 | -0.399890E+12 | 0.358993E+13 |
August | 0.813583E+12 | -0.557004E+10 | 0.00 | -0.383380E+11 | 0.390681E+13 |
September | 0.577559E+12 | 0.468213E+10 | 0.00 | 0.971992E+12 | 0.170834E+13 |
October | 0.552731E+12 | 0.167491E+11 | 0.00 | 0.187651E+13 | 0.144890E+13 |
November | 0.280212E+12 | 0.314101E+11 | 0.00 | 0.182057E+13 | 0.127523E+13 |
December | 0.209156E+12 | 0.378559E+11 | 0.00 | 0.166544E+13 | 0.168483E+13 |
Annual Sum or Average | 0.705754E+13 | 0.224259E+12 | 0.00 | 0.146731E+14 | 0.217044E+14 |
Minimum of Months | 0.209156E+12 | -0.111996E+11 | 0.00 | -0.399890E+12 | 0.544519E+12 |
Maximum of Months | 0.890318E+12 | 0.441479E+11 | 0.00 | 0.187651E+13 | 0.390681E+13 |