Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:04
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** Tampa-MacDill AFB FL USA TMY3 WMO#=747880
Simulation Timestamp: 2023-10-16 09:04:59
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:59
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 31644.45 | 683.16 | 683.16 |
Net Site Energy | 31644.45 | 683.16 | 683.16 |
Total Source Energy | 98876.74 | 2134.63 | 2134.63 |
Net Source Energy | 98876.74 | 2134.63 | 2134.63 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 48.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 5101.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 2740.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 447.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 15213.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1914.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2510.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1113.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 1896.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11132.31 |
Humidification | 1.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.57 |
Heat Recovery | 60.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 595.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 31000.55 | 643.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13413.05 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 48.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 5101.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 2740.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 447.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5871.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 59.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 1848.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 5.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 2510.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 1113.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 1896.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11132.31 |
Humidification | General | 1.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.57 |
Heat Recovery | General | 60.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Water Heater | 0.00 | 595.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 48.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 5101.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 2740.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 447.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 15213.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 1914.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 2510.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 1113.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 1896.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11132.31 |
Humidification | Unassigned | 1.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.57 |
Heat Recovery | Unassigned | 60.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 595.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 68.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 229.37 | 13.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
Other | 371.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 669.26 | 13.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 68.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 229.37 | 13.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
Other | 371.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 669.26 | 13.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 31000.553 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 31000.553 | 100.00 |
Total On-Site and Utility Electric Sources | 31000.553 | 100.00 |
Total Electricity End Uses | 31000.553 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 2232.72 | 98.55 |
Air to Air Heat Recovery for Heating | 32.93 | 1.45 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 2265.64 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 13413.05 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 13413.05 | 100.00 |
Total Water End Uses | 13413.05 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 1.50 |
Time Setpoint Not Met During Occupied Cooling | 754.67 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5943.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_TAMPA
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| HEATSYS1 BOILER | CENTRAL BOILER |DXReportMonthly
| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |FanReportMonthly
| CAV_BAS FAN | VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:59
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:04 |
RunPeriod | RUNPERIOD 1 |
Weather File | Tampa-MacDill AFB FL USA TMY3 WMO#=747880 |
Latitude [deg] | 27.85 |
Longitude [deg] | -82.5 |
Elevation [m] | 8.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 3476.85 | 1043.06 | 695.37 | 1043.06 | 695.37 |
Gross Window-Wall Ratio [%] | 28.54 | 28.54 | 28.54 | 28.54 | 28.54 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 3476.85 | 1043.06 | 695.37 | 1043.06 | 695.37 |
Gross Window-Wall Ratio [%] | 28.54 | 28.54 | 28.54 | 28.54 | 28.54 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 7.6202 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.6202 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.6202 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.6202 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 7.6202 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 7.6202 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 7.6202 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 7.6202 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 86.92 | 86.92 | 7.6202 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 57.95 | 57.95 | 7.6202 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 86.92 | 86.92 | 7.6202 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 57.95 | 57.95 | 7.6202 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 7.6202 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 7.6202 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 7.6202 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 7.6202 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.5114 | 18.58 | 215.2992 |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.5114 | 18.58 | 215.2992 |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.5114 | 18.58 | 215.2992 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 7.6202 | 18.58 | 484.4232 |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 3476.85 | 3476.85 | 7.6661 | 18.58 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 3476.85 | 3476.85 | 7.6661 | 18.58 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 2779.43 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 7.6202 | 18.58 | 4.8418 | |
CORE_BOTTOM | 2496.12 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 7.6202 | 18.58 | 8.0697 | |
CORE_MID | 2496.12 | Yes | Yes | 10.00 | CORE_MID | GENERAL | CORE_MID | 7.6202 | 18.58 | 8.0696 | |
CORE_TOP | 2496.12 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 7.6202 | 18.58 | 8.0696 | |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 7.6202 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 7.6202 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 7.6202 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 7.6202 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 7.6202 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 7.6202 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 7.6202 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 7.6202 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 7.6202 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 7.6202 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 7.6202 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 7.6202 | 18.58 | 8.0699 | |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | GROUNDFLOOR_PLENUM | GENERAL | GROUNDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 10.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_BOT_ZN_6 | GENERAL | DATACENTER_BOT_ZN_6 | 12.5114 | 18.58 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 10.00 | DATACENTER_MID_ZN_6 | GENERAL | DATACENTER_MID_ZN_6 | 12.5114 | 18.58 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_TOP_ZN_6 | GENERAL | DATACENTER_TOP_ZN_6 | 12.5114 | 18.58 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1.00 | DATACENTER_BASEMENT_ZN_6 | GENERAL | DATACENTER_BASEMENT_ZN_6 | 7.6202 | 18.58 | 484.4232 | |
Total | 46320.38 | 7.6661 | 9.29 | 17.8789 | |||||||
Conditioned Total | 46320.38 | 7.6661 | 9.29 | 17.8789 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 42757.27 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 46320.38 | 46320.38 | 0.00 | 42757.27 | 2.3561 | 60.38 | 10.8345 |
Total | 46320.38 | 46320.38 | 0.00 | 42757.27 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:59
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 03-AUG-15:20 | 21-DEC-07:10 | - | - | - | - | - | - | - | - | - | - | 13-JUN-15:09 |
Heating | 0.00 | 467400.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 443007.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 234435.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 794004.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 83146.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 200875.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 70372.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 93886.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 5613.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 28401.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1925340.49 | 495802.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 467400.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 443007.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 234435.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 320838.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 3711.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 79171.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 263.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 200875.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 70372.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 93886.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 5613.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 28401.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:59
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 52.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 16157.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 8680.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 1416.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 48180.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 6062.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 7951.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 3527.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 6006.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 4.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 190.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 645.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 98178.75 | 697.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 1.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 348.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 187.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 30.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1040.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 130.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 171.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 76.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 129.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 4.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 13.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2119.56 | 15.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 1.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 348.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 187.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 30.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1040.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 130.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 171.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 76.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 129.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 4.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 13.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2119.56 | 15.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:59
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
BASEMENT DIRECT AIR | 5.48 |
DATACENTER_BOT_ZN_6 DIRECT AIR | 0.465681 |
DATACENTER_MID_ZN_6 DIRECT AIR | 4.43 |
DATACENTER_TOP_ZN_6 DIRECT AIR | 0.451387 |
DATACENTER_BASEMENT_ZN_6 DIRECT AIR | 21.33 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 5.64 | 0.337300 | 0.335000 | 1.89 | 0.899466 | 0.500000 | 0.001130 | 0.000166 | 1.89 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 52.80 | 0.360250 | 0.349000 | 18.43 | 0.960666 | 0.500000 | 0.001058 | 0.003224 | 18.43 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 5.23 | 0.363666 | 0.361000 | 1.89 | 0.969775 | 0.500000 | 0.001048 | 0.000540 | 1.89 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.908251 | 0.262946 | 0.261000 | 0.237053 | 0.701188 | 0.500000 | 0.001449 | 0.000049 | 0.237053 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.929224 | 0.165628 | 0.200000 | 0.185845 | 0.441673 | 0.500000 | 0.002300 | 0.000038 | 0.185845 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.10 | 0.217235 | 0.216000 | 0.237468 | 0.579293 | 0.500000 | 0.001754 | 0.000064 | 0.237468 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 1.20 | 0.128667 | 0.200000 | 0.239230 | 0.343112 | 0.500000 | 0.002961 | 0.000030 | 0.239230 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 8.42 | 0.283510 | 0.275000 | 2.32 | 0.756026 | 0.500000 | 0.001344 | 0.001293 | 4.41 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 9.49 | 0.162210 | 0.200000 | 1.90 | 0.432560 | 0.500000 | 0.002349 | 0.000863 | 2.94 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 10.35 | 0.230798 | 0.224000 | 2.32 | 0.615461 | 0.500000 | 0.001651 | 0.001285 | 4.38 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 10.05 | 0.153077 | 0.200000 | 2.01 | 0.408207 | 0.500000 | 0.002489 | 0.000766 | 2.61 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.967470 | 0.246851 | 0.245000 | 0.237030 | 0.658268 | 0.500000 | 0.001543 | 0.000173 | 0.589819 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.969264 | 0.158786 | 0.200000 | 0.193853 | 0.423428 | 0.500000 | 0.002399 | 0.000114 | 0.389472 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.16 | 0.206721 | 0.205000 | 0.236838 | 0.551255 | 0.500000 | 0.001843 | 0.000172 | 0.586603 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.09 | 0.141130 | 0.200000 | 0.218104 | 0.376347 | 0.500000 | 0.002700 | 0.000107 | 0.364566 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 19004.94 | 0.000166 | 383.12 |
CORE_MID VAV BOX REHEAT COIL | 368521.24 | 0.003224 | 8236.55 |
CORE_TOP VAV BOX REHEAT COIL | 61690.93 | 0.000540 | 1609.03 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 5654.10 | 0.000049 | 132.03 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 4326.48 | 0.000038 | 100.36 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 7343.12 | 0.000064 | 187.12 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 3453.00 | 0.000030 | 72.73 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 147829.41 | 0.001293 | 3900.55 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 98605.52 | 0.000863 | 2601.67 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 146866.25 | 0.001285 | 3875.16 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 87523.00 | 0.000766 | 2309.53 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 19765.21 | 0.000173 | 521.35 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 13050.70 | 0.000114 | 344.23 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 19657.69 | 0.000172 | 518.52 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 12217.78 | 0.000107 | 322.28 |
VAV_BOT WITH REHEAT HEATING COIL | 26182.45 | 0.000229 | 452.91 |
VAV_MID WITH REHEAT HEATING COIL | 246020.64 | 0.002152 | 4252.08 |
VAV_TOP WITH REHEAT HEATING COIL | 23750.39 | 0.000208 | 412.95 |
CAV_BAS HEATING COIL | 258285.90 | 0.002260 | 5860.88 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT | 4.89 | 2.79 | 9.77 | 2.79 | 8.94 | 8.94 | 0.300000 | 0.311872 | 8.94 |
VAV_MID WITH REHEAT | 45.56 | 26.97 | 91.11 | 26.97 | 82.72 | 82.72 | 0.300000 | 0.326035 | 82.72 |
VAV_TOP WITH REHEAT | 4.71 | 2.77 | 9.41 | 3.74 | 8.94 | 8.94 | 0.300000 | 0.418601 | 8.94 |
CAV_BAS | 5.48 | 5.48 | 5.48 | 5.48 | 5.48 | 5.48 | 1.00 | 1.00 | 5.48 |
AIRLOOP DATACENTER BASEMENT | 21.33 | 21.33 | 21.33 | 21.33 | 21.33 | 21.33 | 1.00 | 0.999990 | 21.33 |
AIRLOOP DATACENTER BOT | 0.465681 | 0.465681 | 0.465681 | 0.465681 | 0.465681 | 0.465681 | 1.00 | 1.00 | 0.465681 |
AIRLOOP DATACENTER MID | 4.43 | 4.43 | 4.43 | 4.43 | 4.43 | 4.43 | 1.00 | 1.00 | 4.43 |
AIRLOOP DATACENTER TOP | 0.451387 | 0.451387 | 0.451387 | 0.451387 | 0.451387 | 0.451387 | 1.00 | 1.00 | 0.451387 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 8.94 | |
VAV_MID WITH REHEAT_OA_CONTROLLER | 82.72 | |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 8.94 | |
CAV_BAS_OA_CONTROLLER | 5.48 | 1.20 |
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | 21.33 | 0.338393 |
AIRLOOP DATACENTER BOT_OA_CONTROLLER | 0.465681 | 0.015632 |
AIRLOOP DATACENTER MID_OA_CONTROLLER | 4.43 | 0.156323 |
AIRLOOP DATACENTER TOP_OA_CONTROLLER | 0.451387 | 0.015632 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT OA HEAT RECOVERY | 2.54 |
VAV_MID WITH REHEAT OA HEAT RECOVERY | 25.38 |
VAV_TOP WITH REHEAT OA HEAT RECOVERY | 2.54 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT COOLING COIL | 26.93 | 6.67 | 11.05 | 0.011175 | 0.008500 | 247829.88 | 0.010543 | 8.94 |
VAV_MID WITH REHEAT COOLING COIL | 27.29 | 6.67 | 11.05 | 0.011535 | 0.008500 | 2420734.69 | 0.102984 | 82.72 |
VAV_TOP WITH REHEAT COOLING COIL | 26.82 | 6.67 | 11.05 | 0.011143 | 0.008500 | 245566.35 | 0.010447 | 8.94 |
CAV_BAS COOLING COIL | 25.00 | 6.67 | 11.42 | 0.010624 | 0.008500 | 127008.98 | 0.005403 | 5.48 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 8.94 |
VAV_MID WITH REHEAT FAN | 82.72 |
VAV_TOP WITH REHEAT FAN | 8.94 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.010543 | 0.000045 |
VAV_BOT WITH REHEAT_HEATC_CONTROLLER | 0.000229 | |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.102984 | 0.000005 |
VAV_MID WITH REHEAT_HEATC_CONTROLLER | 0.002152 | |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.010447 | 0.000046 |
VAV_TOP WITH REHEAT_HEATC_CONTROLLER | 0.000208 | |
CAV_BAS_COOLC_CONTROLLER | 0.005403 | 0.000088 |
CAV_BAS_HEATC_CONTROLLER | 0.002260 |
Design Size Maximum Flow Rate [m3/s] | |
CAV_BAS FAN | 5.48 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Total Cooling Capacity [W] | Design Size Rated Sensible Cooling Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | 21.33 | 434337.82 | 312325.51 | 0.010637 |
AIRLOOP DATACENTER BOT COOLING COIL | 0.465681 | 9501.30 | 6820.69 | 0.000233 |
AIRLOOP DATACENTER MID COOLING COIL | 4.43 | 90544.49 | 64905.21 | 0.002217 |
AIRLOOP DATACENTER TOP COOLING COIL | 0.451387 | 9227.99 | 6617.53 | 0.000226 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | 21.33 | 21.33 | 21.33 | 21.33 | 434337.82 | 434337.82 | 14482.89 | 1.00 |
AIRLOOP DATACENTER BOT DXAC HEAT PUMP | 0.465681 | 0.465681 | 0.465681 | 0.465681 | 9501.30 | 9501.30 | 669.05 | 1.00 |
AIRLOOP DATACENTER MID DXAC HEAT PUMP | 4.43 | 4.43 | 4.43 | 4.43 | 90544.49 | 90544.49 | 6690.49 | 1.00 |
AIRLOOP DATACENTER TOP DXAC HEAT PUMP | 0.451387 | 0.451387 | 0.451387 | 0.451387 | 9227.99 | 9227.99 | 669.05 | 1.00 |
Design Size Maximum Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | 21.33 |
AIRLOOP DATACENTER BOT SUPPLY FAN | 0.465681 |
AIRLOOP DATACENTER MID SUPPLY FAN | 4.43 |
AIRLOOP DATACENTER TOP SUPPLY FAN | 0.451387 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Heating Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | 21.33 | 434337.82 | 0.010637 |
AIRLOOP DATACENTER BOT HEATING COIL | 0.465681 | 9501.30 | 0.000233 |
AIRLOOP DATACENTER MID HEATING COIL | 4.43 | 90544.49 | 0.002217 |
AIRLOOP DATACENTER TOP HEATING COIL | 0.451387 | 9227.99 | 0.000226 |
Design Size Nominal Capacity [W] | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | 14482.89 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | 669.05 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | 6690.49 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | 669.05 |
Design Size Nominal Capacity Volume [m3/s] | User-Specified Nominal Capacity Volume [m3/s] | Design Size Rated Power [W] | User-Specified Rated Power [W] | |
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | 0.000080 | 0.000037 | 96450.70 | 100000.00 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.129377 | 26659.83 | |
HEATSYS1 PUMP | 0.013733 | 4135.73 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.129377 | 15.53 |
HEATSYS1 | 0.013733 | 1.65 |
COOLSYS1_SUPPLY | 0.129377 | 15.53 |
SINGLE WATER PLANT LOOP | 0.013313 | 1.60 |
SWHSYS1 | 0.000440 | 0.052800 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.129377 | 0.129377 | 543060.70 | 5.60 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 1569748.75 | 1569748.75 | 0.013733 |
CENTRAL BOILER | 548382.01 | 537788.84 | 0.013313 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP | 0.129377 | 18457.50 |
PLANT CIRC PUMP | 0.013313 | 3395.48 |
SWHSYS1 PUMP | 0.000440 | 5.96 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Water Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.129377 | 0.065210 | 1536592.25 | 1543939.29 | 0.076404 |
COOLSYS1 CHILLER2 | 0.129377 | 0.065210 | 1536592.25 | 1543939.29 | 0.076404 |
Design Water Flow Rate [m3/s] | Air Flow Rate at High Fan Speed [m3/s] | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | Air Flow Rate at Low Fan Speed [m3/s] | Fan Power at Low Fan Speed [W] | U-factor Times Area Value at Low Fan Speed [W/C] | |
CENTRAL TOWER | 0.013313 | 139666.47 | 59194.70 | 69833.23 | 7879.72 | 21407.40 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000440 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.152808 | 18.34 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.152808 | 46022.34 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 58.79 | 1831858.06 | 11.76 | 228982.26 |
TOWERWATERSYS COOLTOWER 2 | 58.79 | 1831858.06 | 11.76 | 228982.26 |
Design Water Flow Rate [m3/s] Equipment # 47 | |
WSHPPLANT OPERATION SCHEME | 0.079360 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:59
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:59
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:59
VersionVersion ID | |
1 | 22.1.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 24.20 | 18.90 | 15.70 | 13.60 | 15.50 | 17.10 | 21.20 | 26.90 | 27.60 | 27.90 | 27.40 | 26.20 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Tampa-MacDill AFB FL USA TMY3 WMO#=747880 | 27.85 | -82.52 | -5.00 | 8.00 | 101229 | 1.2032 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 21.85 | 14.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 105.88 | 86.92 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 71.89 | 57.95 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 105.88 | 86.92 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 71.89 | 57.95 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 7.620 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 12.462 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 12.511 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 227.811 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 12.511 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 227.811 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 12.511 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 227.811 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 18.579 | 5.382E-002 | 7.620 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 492.043 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DATACENTER_BOT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | DATACENTER_MID_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | DATACENTER_TOP_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | DATACENTER_BASEMENT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 42.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 42 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_OFFICE | BASEMENT | 2779.43 | 149.6 | 21179.739 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 21179.739 |
2 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 2496.12 | 134.4 | 19020.895 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 19020.895 |
3 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 2496.12 | 134.4 | 19020.895 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 19020.895 |
4 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 2496.12 | 134.4 | 19020.895 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 19020.895 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2388.263 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2388.263 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1539.088 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1539.088 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2388.315 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2388.315 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1539.088 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1539.088 |
9 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2388.263 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2388.263 |
10 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1539.088 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1539.088 |
11 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2388.315 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2388.315 |
12 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1539.088 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1539.088 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2388.263 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2388.263 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1539.088 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1539.088 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2388.315 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2388.315 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1539.088 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1539.088 |
17 | DATACENTER_BASEMENT_LIGHTS | LTG_SCH_OFFICE | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 5971.780 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5971.780 |
18 | DATACENTER_BOT_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 452.948 | 12.511 | 232.447 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 452.948 |
19 | DATACENTER_MID_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 452.948 | 12.511 | 232.447 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 452.948 |
20 | DATACENTER_TOP_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 452.948 | 12.511 | 232.447 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 452.948 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 379632.522 | 484.423 | 9000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.464 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
9 | NONRES_EXT_WALL_GRD | 20 | 3 | 9 | 0.167 | 1.743 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | NONRES_EXT_WALL_MID | 21 | 3 | 9 | 0.167 | 1.656 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | NONRES_EXT_WALL_TOP | 22 | 3 | 9 | 0.167 | 2.135 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | BASEMENT_WALL_EAST_CFACTOR | 39 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_SOUTH_CFACTOR | 40 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BASEMENT_WALL_NORTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 42 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 43 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 44 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2887 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4064 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4365 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3009 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
32 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
33 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
34 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
35 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.4637404 | 3.4637404 | 3.4637404 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
47 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
48 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
49 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
50 | 9 | 0.76055735E-15 | 0.55973061E-16 | -0.11090261E-09 | -0.43371185E-17 |
51 | 8 | 0.16390423E-07 | 0.22068143E-12 | 0.31740643E-03 | -0.18636477E-09 |
52 | 7 | -0.10429999E-01 | 0.12271718E-07 | -0.20474149E-01 | 0.11859286E-03 |
53 | 6 | 0.35611320 | 0.43955117E-05 | 0.42991281 | -0.41673803E-02 |
54 | 5 | -4.7098961 | 0.16827687E-03 | -4.1162358 | 0.57223947E-01 |
55 | 4 | 30.875684 | 0.14076848E-02 | 20.167480 | -0.39388153 |
56 | 3 | -106.69740 | 0.31291265E-02 | -53.106522 | 1.4497707 |
57 | 2 | 192.63914 | 0.17911574E-02 | 75.570394 | -2.8293896 |
58 | 1 | -169.50392 | 0.19431750E-03 | -54.592911 | 2.7164834 |
59 | 0 | 57.057407 | 0.11257899E-05 | 15.674734 | |
60 | 9 | 0.11474244E-14 | 0.54197419E-16 | -0.11508650E-09 | -0.49945851E-17 |
61 | 8 | 0.16984416E-07 | 0.21156325E-12 | 0.32425024E-03 | -0.19311866E-09 |
62 | 7 | -0.10636353E-01 | 0.11664670E-07 | -0.20772028E-01 | 0.12093918E-03 |
63 | 6 | 0.36172330 | 0.41637772E-05 | 0.43474562 | -0.42335086E-02 |
64 | 5 | -4.7646824 | 0.15893927E-03 | -4.1535939 | 0.57903236E-01 |
65 | 4 | 31.118254 | 0.13261305E-02 | 20.314042 | -0.39710182 |
66 | 3 | -107.21418 | 0.29411649E-02 | -53.396504 | 1.4572354 |
67 | 2 | 193.15212 | 0.16802168E-02 | 75.835339 | -2.8375342 |
68 | 1 | -169.69371 | 0.18194848E-03 | -54.668081 | 2.7198097 |
69 | 0 | 57.057407 | 0.10520719E-05 | 15.660794 | |
70 | 9 | 0.66246833E-15 | 0.57738042E-16 | -0.92036509E-10 | -0.27018983E-17 |
71 | 8 | 0.13701644E-07 | 0.25726543E-12 | 0.28527343E-03 | -0.15579243E-09 |
72 | 7 | -0.94571194E-02 | 0.14940887E-07 | -0.19068097E-01 | 0.10753086E-03 |
73 | 6 | 0.32965778 | 0.54453531E-05 | 0.40701455 | -0.38555430E-02 |
74 | 5 | -4.4514676 | 0.21157254E-03 | -3.9387765 | 0.54019785E-01 |
75 | 4 | 29.731016 | 0.17930056E-02 | 19.470280 | -0.37868589 |
76 | 3 | -104.25747 | 0.40308508E-02 | -51.726693 | 1.4145289 |
77 | 2 | 190.21562 | 0.23301583E-02 | 74.311741 | -2.7909129 |
78 | 1 | -168.60668 | 0.25508611E-03 | -54.239505 | 2.7007581 |
79 | 0 | 57.057407 | 0.14924561E-05 | 15.743350 | |
80 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
81 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
82 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
83 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
84 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
85 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
86 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
87 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
88 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
89 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
90 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
91 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
92 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
93 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
94 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
95 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
96 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
97 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
98 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
99 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
100 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
101 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
102 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
103 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
104 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
105 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
106 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
107 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
108 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
109 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
110 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
111 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
112 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
113 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
114 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
115 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
116 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
117 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
118 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
119 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
120 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
121 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
122 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
123 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
124 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
125 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
126 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
127 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.5047_SHGC_EAST_0.25 | 35 | 1 | VerySmooth | 2.869 | 2.869 | 1.000 | 0.251 | ||
2 | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | 36 | 1 | VerySmooth | 2.869 | 2.869 | 1.000 | 0.251 | ||
3 | WINDOW_U_0.5047_SHGC_WEST_0.25 | 37 | 1 | VerySmooth | 2.869 | 2.869 | 1.000 | 0.251 | ||
4 | WINDOW_U_0.5047_SHGC_NORTH_0.25 | 38 | 1 | VerySmooth | 2.869 | 2.869 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 1.90891E-002 | 0.16139 | 0.61055 | 0.61055 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.10708 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 1.90891E-002 | 0.16139 | 0.61055 | 0.61055 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.10708 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 1.90891E-002 | 0.16139 | 0.61055 | 0.61055 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.10708 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 1.90891E-002 | 0.16139 | 0.61055 | 0.61055 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.10708 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_BOT_ZN_3 | 5 | 0 |
2 | PERIMETER_BOT_ZN_2 | 3 | 0 |
3 | PERIMETER_BOT_ZN_1 | 5 | 0 |
4 | PERIMETER_BOT_ZN_4 | 3 | 0 |
5 | PERIMETER_MID_ZN_3 | 1 | 0 |
6 | PERIMETER_MID_ZN_2 | 1 | 0 |
7 | PERIMETER_MID_ZN_1 | 1 | 0 |
8 | PERIMETER_MID_ZN_4 | 1 | 0 |
9 | PERIMETER_TOP_ZN_3 | 1 | 0 |
10 | PERIMETER_TOP_ZN_2 | 1 | 0 |
11 | PERIMETER_TOP_ZN_1 | 1 | 0 |
12 | PERIMETER_TOP_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_BOT_ZN_3 | 0 | |
2 | PERIMETER_BOT_ZN_2 | 0 | |
3 | PERIMETER_BOT_ZN_1 | 0 | |
4 | PERIMETER_BOT_ZN_4 | 0 | |
5 | PERIMETER_MID_ZN_3 | 0 | |
6 | PERIMETER_MID_ZN_2 | 0 | |
7 | PERIMETER_MID_ZN_1 | 0 | |
8 | PERIMETER_MID_ZN_4 | 0 | |
9 | PERIMETER_TOP_ZN_3 | 0 | |
10 | PERIMETER_TOP_ZN_2 | 0 | |
11 | PERIMETER_TOP_ZN_1 | 0 | |
12 | PERIMETER_TOP_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 1.1356 | 87921.3 | 0.496 | 7.5104E-002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 4.384E-005 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.6254E-003 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.6265E-003 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.7661E-003 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.7670E-003 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.1309E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.1315E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.2447E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.2452E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.6512E-003 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.7229E-003 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.7871E-003 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.8468E-003 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.1472E-003 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.1952E-003 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.2574E-003 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.2891E-003 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.2727E-002 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.0291E-002 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.0494E-002 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.2035E-002 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.9708E-002 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.2098E-002 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.6042E-002 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 9.1095E-003 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.6579E-003 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.7555E-003 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.7943E-003 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.8820E-003 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.1538E-003 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.2204E-003 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.2577E-003 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.2900E-003 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.6253E-003 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.6267E-003 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.7661E-003 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.7672E-003 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.1309E-003 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.1317E-003 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.2447E-003 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.2451E-003 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.8368E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.9662E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.7256E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.8595E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.5577E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.6254E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.1302E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.1521E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.4075E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.6441E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.2729E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.5117E-002 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.4408E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.3988E-002 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.6787E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 9.9865E-003 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.8074E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.8584E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.6892E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.7267E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.5378E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.5542E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.1303E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.1525E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.2173E-003 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2185E-003 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.0474E-003 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.0484E-003 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 9.3115E-004 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 9.3188E-004 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.2447E-003 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2452E-003 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.2446E-003 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3113E-003 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.0699E-003 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1233E-003 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 9.4925E-004 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 9.8862E-004 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.2577E-003 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2900E-003 |
81 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.8942E-002 |
82 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.0694E-002 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.4825E-002 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 8.1954E-003 |
85 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.4675E-002 |
86 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 5.8147E-003 |
87 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.6042E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 9.1067E-003 |
89 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.2422E-003 |
90 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3084E-003 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.0669E-003 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1173E-003 |
93 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 9.4412E-004 |
94 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 9.7295E-004 |
95 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.2574E-003 |
96 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2891E-003 |
97 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.2172E-003 |
98 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2184E-003 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.0473E-003 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.0482E-003 |
101 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 9.3105E-004 |
102 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 9.3158E-004 |
103 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.2447E-003 |
104 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2451E-003 |
105 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.3332E-003 |
106 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.3869E-003 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.1155E-003 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.1543E-003 |
109 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.0937E-003 |
110 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.1081E-003 |
111 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.1303E-003 |
112 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.1525E-003 |
113 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.4812E-002 |
114 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.2955E-002 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.1647E-002 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.0967E-002 |
117 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.5251E-002 |
118 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.0492E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.6787E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 9.9865E-003 |
121 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.3553E-003 |
122 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.4510E-003 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.1434E-003 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.2365E-003 |
125 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.1120E-003 |
126 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.1695E-003 |
127 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.1302E-003 |
128 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.1521E-003 |
129 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 7.3410E-002 |
130 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 4.1344E-002 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 7.9692E-002 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 4.3683E-002 |
133 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 6.3222E-002 |
134 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 3.1272E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 3.0133E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 1.4574E-002 |
137 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.9035E-002 |
138 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.2699E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.7576E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.1160E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.9026E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.9643E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.0820E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.4729E-002 |
145 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.2861E-002 |
146 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.5883E-002 |
147 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 1.8361E-002 |
148 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.2694E-002 |
149 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 1.8134E-002 |
150 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 9.9391E-003 |
151 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.0133E-002 |
152 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.4571E-002 |
153 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 2.8977E-002 |
154 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.8133E-002 |
155 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 2.5522E-002 |
156 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.5701E-002 |
157 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 2.9157E-002 |
158 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.5175E-002 |
159 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.0820E-002 |
160 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.4729E-002 |
161 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 7.3413E-002 |
162 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 4.1409E-002 |
163 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 7.9711E-002 |
164 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 4.3759E-002 |
165 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 6.3264E-002 |
166 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 3.1337E-002 |
167 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 3.0168E-002 |
168 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 1.4602E-002 |
169 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.9027E-002 |
170 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.2722E-002 |
171 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.7578E-002 |
172 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.1183E-002 |
173 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.9047E-002 |
174 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.9678E-002 |
175 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.0854E-002 |
176 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.4757E-002 |
177 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.2836E-002 |
178 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.5890E-002 |
179 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 1.8344E-002 |
180 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.2700E-002 |
181 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 1.8144E-002 |
182 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 9.9535E-003 |
183 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.0168E-002 |
184 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.4599E-002 |
185 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 2.8960E-002 |
186 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.8147E-002 |
187 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 2.5513E-002 |
188 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.5714E-002 |
189 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 2.9171E-002 |
190 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.5200E-002 |
191 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.0854E-002 |
192 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.4757E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 76041.58315 | 76041.58315 | 5.47886 | 5.47886 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 28.05400 | 1.65254E-002 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20016 | 00:10:00 | 4.60000 | 5.25715E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 | |
3 | CORE_BOTTOM | Cooling | 78274.25347 | 78274.25347 | 5.63903 | 5.63903 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 28.05400 | 1.65254E-002 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
4 | CORE_BOTTOM | Heating | 0.00000 | 0.00000 | 0.00000 | 1.07782 | 00:10:00 | 4.60000 | 5.25715E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 | |
5 | CORE_MID | Cooling | 733090.74824 | 733090.74824 | 52.79794 | 52.79794 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 28.05400 | 1.65254E-002 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
6 | CORE_MID | Heating | 183142.69633 | 183142.69633 | 7.67434 | 10.77825 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
7 | CORE_TOP | Cooling | 72622.80178 | 72622.80178 | 5.23020 | 5.23020 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 28.05400 | 1.65254E-002 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
8 | CORE_TOP | Heating | 42695.79090 | 42695.79090 | 1.81005 | 1.81005 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 12489.88707 | 12489.88707 | 0.90825 | 0.90825 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 33.90000 | 1.65364E-002 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 3273.41376 | 3273.41376 | 0.13793 | 0.13793 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 12778.37453 | 12778.37453 | 0.92922 | 0.92922 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:40:00 | 30.45033 | 1.65299E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 2459.77317 | 2459.77317 | 0.10391 | 0.10391 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 15118.40346 | 15118.40346 | 1.09939 | 1.09939 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 33.76833 | 1.65361E-002 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 4957.07671 | 4957.07671 | 0.21006 | 0.21006 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 16449.13132 | 16449.13132 | 1.19615 | 1.19615 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 32.79400 | 1.65343E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 1052.25000 | 1052.25000 | 4.46141E-002 | 8.72129E-002 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
17 | PERIMETER_MID_ZN_3 | Cooling | 115832.27826 | 115832.27826 | 8.42372 | 8.42372 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 33.90000 | 1.65364E-002 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 103514.34719 | 103514.34719 | 4.40836 | 4.40836 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 130468.12308 | 130468.12308 | 9.48802 | 9.48802 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:50:00 | 30.67417 | 1.65303E-002 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 69043.46998 | 69043.46998 | 2.94069 | 2.94069 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 142290.72837 | 142290.72837 | 10.34783 | 10.34783 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 33.83417 | 1.65363E-002 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 102840.94518 | 102840.94518 | 4.37957 | 4.37957 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 138251.92159 | 138251.92159 | 10.05406 | 10.05406 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | 32.66233 | 1.65340E-002 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 61294.69647 | 61294.69647 | 2.60952 | 2.60952 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 13303.12849 | 13303.12849 | 0.96747 | 0.96747 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 33.82100 | 1.65362E-002 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 13834.64805 | 13834.64805 | 0.58982 | 0.58982 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 13327.86167 | 13327.86167 | 0.96926 | 0.96926 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:10:00 | 31.09550 | 1.65311E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 9134.59591 | 9134.59591 | 0.38947 | 0.38947 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 15886.01902 | 15886.01902 | 1.15531 | 1.15531 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 33.90000 | 1.65364E-002 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 13759.49424 | 13759.49424 | 0.58660 | 0.58660 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 14995.22512 | 14995.22512 | 1.09052 | 1.09052 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 32.79400 | 1.65343E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 8552.35816 | 8552.35816 | 0.36457 | 0.36457 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 8120.36112 | 8120.36112 | 0.46568 | 0.46568 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:20:00 | 26.05267 | 1.65216E-002 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | 00:10:00 | 4.60000 | 5.25715E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 | |
35 | DATACENTER_MID_ZN_6 | Cooling | 77163.21473 | 77163.21473 | 4.42564 | 4.42564 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 31.21400 | 1.65313E-002 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15632 | 00:10:00 | 4.60000 | 5.25715E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 | |
37 | DATACENTER_TOP_ZN_6 | Cooling | 7870.19515 | 7870.19515 | 0.45139 | 0.45139 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 31.21400 | 1.65313E-002 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | 00:10:00 | 4.60000 | 5.25715E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 | |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 371959.72717 | 371959.72717 | 21.33288 | 21.33288 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 07:00:00 | 26.71100 | 1.65229E-002 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33839 | 00:10:00 | 4.60000 | 5.25715E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV_BOT WITH REHEAT | Cooling | Sensible | 146314.48 | 8.94172 | 8.94172 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
2 | VAV_BOT WITH REHEAT | Heating | Sensible | 16030.11 | 1.61693 | 1.61693 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
3 | VAV_MID WITH REHEAT | Cooling | Sensible | 1336440.30 | 82.71906 | 82.71906 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
4 | VAV_MID WITH REHEAT | Heating | Sensible | 249001.53 | 25.11640 | 25.11640 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
5 | VAV_TOP WITH REHEAT | Cooling | Sensible | 150861.96 | 8.93574 | 8.93574 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
6 | VAV_TOP WITH REHEAT | Heating | Sensible | 25149.12 | 3.74052 | 3.74052 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
7 | CAV_BAS | Cooling | Sensible | 80481.36 | 5.47886 | 5.47886 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
8 | CAV_BAS | Heating | Sensible | 51365.55 | 1.20016 | 1.20016 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
9 | AIRLOOP DATACENTER BASEMENT | Cooling | Sensible | 368539.76 | 21.33310 | 21.33310 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
10 | AIRLOOP DATACENTER BASEMENT | Heating | Sensible | 14482.89 | 0.33839 | 0.33839 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
11 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 8069.30 | 0.46568 | 0.46568 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
12 | AIRLOOP DATACENTER BOT | Heating | Sensible | 669.05 | 1.56323E-002 | 1.56323E-002 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
13 | AIRLOOP DATACENTER MID | Cooling | Sensible | 76766.78 | 4.42564 | 4.42564 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
14 | AIRLOOP DATACENTER MID | Heating | Sensible | 6690.49 | 0.15632 | 0.15632 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
15 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 7831.26 | 0.45139 | 0.45139 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
16 | AIRLOOP DATACENTER TOP | Heating | Sensible | 669.05 | 1.56323E-002 | 1.56323E-002 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | BASEMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 5.47886 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.63903 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.33730 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.33500 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.88908 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.89947 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.12956E-003 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.66263E-004 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.88908 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
13 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 19004.93673 |
14 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.66263E-004 |
15 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 383.12461 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 52.79794 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.36025 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.34900 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 18.42648 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.96067 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.05760E-003 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.22398E-003 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 18.42648 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
27 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 368521.24448 |
28 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.22398E-003 |
29 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 8236.54941 |
30 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.23020 |
31 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.36367 |
32 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.36100 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.88810 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.96978 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.04767E-003 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.39699E-004 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.88810 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
40 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
41 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 61690.92905 |
42 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.39699E-004 |
43 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1609.03079 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.90825 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.26295 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.26100 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.23705 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.70119 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.44897E-003 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.94645E-005 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.23705 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
55 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 5654.09781 |
56 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.94645E-005 |
57 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 132.02861 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.92922 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16563 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.18584 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.44167 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.30034E-003 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.78499E-005 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.18584 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
69 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 4326.47754 |
70 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.78499E-005 |
71 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 100.35627 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.09939 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.21723 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.21600 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.23747 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.57929 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.75386E-003 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.42408E-005 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.23747 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
83 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7343.11521 |
84 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.42408E-005 |
85 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 187.12359 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.19615 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12867 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.23923 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.34311 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.96113E-003 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.02084E-005 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.23923 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
97 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 3453.00346 |
98 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.02084E-005 |
99 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 72.72870 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 8.42372 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.28351 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.27500 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.31652 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.75603 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.34387E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.29328E-003 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 4.40836 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 147829.41000 |
112 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.29328E-003 |
113 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 3900.55004 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 9.48802 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16221 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.89760 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.43256 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.34881E-003 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.62644E-004 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.94069 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
124 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
125 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 98605.52248 |
126 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.62644E-004 |
127 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2601.66588 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 10.34783 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.23080 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.22400 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.31791 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.61546 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.65080E-003 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.28485E-003 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 4.37957 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
138 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
139 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 146866.25488 |
140 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.28485E-003 |
141 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 3875.16332 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 10.05406 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15308 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.01081 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.40821 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.48894E-003 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.65689E-004 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.60952 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
152 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
153 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 87523.00276 |
154 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.65689E-004 |
155 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2309.52518 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.96747 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.24685 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.24500 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.23703 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.65827 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.54344E-003 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.72915E-004 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.58982 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
166 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
167 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 19765.20623 |
168 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.72915E-004 |
169 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 521.34882 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.96926 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15879 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.19385 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.42343 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.39946E-003 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.14173E-004 |
178 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.38947 |
179 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
180 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
181 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 13050.69875 |
182 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.14173E-004 |
183 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 344.23061 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.15531 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20672 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20500 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.23684 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.55126 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.84307E-003 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.71974E-004 |
192 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.58660 |
193 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
194 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
195 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 19657.69134 |
196 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.71974E-004 |
197 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 518.51591 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.09052 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14113 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.21810 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.37635 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.69964E-003 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.06886E-004 |
206 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.36457 |
207 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
208 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
209 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12217.77503 |
210 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.06886E-004 |
211 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 322.28105 |
212 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BOT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.46568 |
213 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_MID_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.42564 |
214 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_TOP_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.45139 |
215 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BASEMENT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 21.33288 |
216 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.88602 |
217 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.78867 |
218 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 9.77205 |
219 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 2.78867 |
220 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 8.94172 |
221 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 8.94172 |
222 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
223 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.31187 |
224 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 45.55579 |
225 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 26.96933 |
226 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 91.11158 |
227 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 26.96933 |
228 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 82.71906 |
229 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 82.71906 |
230 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
231 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.32604 |
232 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.70638 |
233 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.77393 |
234 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 9.41276 |
235 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 3.74052 |
236 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 8.93574 |
237 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 8.93574 |
238 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
239 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.41860 |
240 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.47886 |
241 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 5.47886 |
242 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.47886 |
243 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 5.47886 |
244 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.47886 |
245 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 5.47886 |
246 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
247 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
248 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 21.33288 |
249 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 21.33288 |
250 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 21.33288 |
251 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Heating Design Air Flow Rate [m3/s] | 21.33288 |
252 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Cooling Design Air Flow Rate [m3/s] | 21.33310 |
253 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Main Design Air Flow Rate [m3/s] | 21.33310 |
254 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | User Heating Air Flow Ratio [] | 1.00000 |
255 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Calculated Heating Air Flow Ratio [] | 0.99999 |
256 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.46568 |
257 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.46568 |
258 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.46568 |
259 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.46568 |
260 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.46568 |
261 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.46568 |
262 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
263 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
264 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.42564 |
265 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.42564 |
266 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.42564 |
267 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 4.42564 |
268 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.42564 |
269 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.42564 |
270 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
271 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
272 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.45139 |
273 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.45139 |
274 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.45139 |
275 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.45139 |
276 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.45139 |
277 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.45139 |
278 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
279 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
280 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 8.94172 |
281 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 82.71906 |
282 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 8.93574 |
283 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 5.47886 |
284 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Design Supply Air Flow Rate [m3/s] | 21.33310 |
285 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.46568 |
286 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 4.42564 |
287 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.45139 |
288 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 8.94172 |
289 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_BOT WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.53819 |
290 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.93365 |
291 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
292 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.04880 |
293 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.11747E-002 |
294 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
295 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 247829.88187 |
296 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.05433E-002 |
297 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 8.94172 |
298 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 26182.45066 |
299 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.29055E-004 |
300 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 452.91327 |
301 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 8.94172 |
302 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.05433E-002 |
303 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 4.51654E-005 |
304 | Controller:WaterCoil | VAV_BOT WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.29055E-004 |
305 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 82.71906 |
306 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_MID WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 25.38195 |
307 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 27.29353 |
308 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
309 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.04995 |
310 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.15349E-002 |
311 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
312 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 2420734.69453 |
313 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 0.10298 |
314 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 82.71906 |
315 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 246020.64182 |
316 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.15230E-003 |
317 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 4252.08254 |
318 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 82.71906 |
319 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 0.10298 |
320 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 4.62394E-006 |
321 | Controller:WaterCoil | VAV_MID WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.15230E-003 |
322 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 8.93574 |
323 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_TOP WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.53819 |
324 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.82250 |
325 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
326 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.04870 |
327 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.11429E-002 |
328 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
329 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 245566.35331 |
330 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 1.04470E-002 |
331 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 8.93574 |
332 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 23750.38579 |
333 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.07779E-004 |
334 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 412.95426 |
335 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 8.93574 |
336 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.04470E-002 |
337 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 4.55817E-005 |
338 | Controller:WaterCoil | VAV_TOP WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.07779E-004 |
339 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.47886 |
340 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.20016 |
341 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.00074 |
342 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
343 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.42450 |
344 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.06240E-002 |
345 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
346 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Coil Load [W] | 127008.98187 |
347 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 5.40326E-003 |
348 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 5.47886 |
349 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Rated Capacity [W] | 258285.90198 |
350 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.25960E-003 |
351 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 5860.87899 |
352 | Fan:ConstantVolume | CAV_BAS FAN | Design Size Maximum Flow Rate [m3/s] | 5.47886 |
353 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.40326E-003 |
354 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 8.81303E-005 |
355 | Controller:WaterCoil | CAV_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.25960E-003 |
356 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 21.33310 |
357 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.33839 |
358 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 21.33310 |
359 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 434337.81672 |
360 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 312325.50573 |
361 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.06369E-002 |
362 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 21.33310 |
363 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 21.33310 |
364 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 21.33310 |
365 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 21.33310 |
366 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 434337.81672 |
367 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 434337.81672 |
368 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 14482.88751 |
369 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
370 | Fan:OnOff | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 21.33310 |
371 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 21.33310 |
372 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Heating Capacity [W] | 434337.81672 |
373 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.06369E-002 |
374 | Coil:Heating:Electric | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 14482.88751 |
375 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Nominal Capacity Volume [m3/s] | 8.01492E-005 |
376 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Nominal Capacity Volume [m3/s] | 3.72000E-005 |
377 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Rated Power [W] | 96450.69782 |
378 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Rated Power [W] | 100000.00000 |
379 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.46568 |
380 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
381 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.46568 |
382 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9501.30473 |
383 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6820.68720 |
384 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.32686E-004 |
385 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.46568 |
386 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.46568 |
387 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.46568 |
388 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.46568 |
389 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9501.30473 |
390 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9501.30473 |
391 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 669.04940 |
392 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
393 | Fan:OnOff | AIRLOOP DATACENTER BOT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.46568 |
394 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.46568 |
395 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Heating Capacity [W] | 9501.30473 |
396 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.32686E-004 |
397 | Coil:Heating:Electric | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 669.04940 |
398 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.42564 |
399 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.15632 |
400 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.42564 |
401 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 90544.48627 |
402 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 64905.21163 |
403 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.21743E-003 |
404 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 4.42564 |
405 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 4.42564 |
406 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 4.42564 |
407 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 4.42564 |
408 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Heating Capacity [W] | 90544.48627 |
409 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 90544.48627 |
410 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 6690.49404 |
411 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
412 | Fan:OnOff | AIRLOOP DATACENTER MID SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 4.42564 |
413 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.42564 |
414 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Heating Capacity [W] | 90544.48627 |
415 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.21743E-003 |
416 | Coil:Heating:Electric | AIRLOOP DATACENTER MID_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 6690.49404 |
417 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.45139 |
418 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
419 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.45139 |
420 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9227.99310 |
421 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6617.52579 |
422 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.25993E-004 |
423 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.45139 |
424 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.45139 |
425 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.45139 |
426 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.45139 |
427 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9227.99310 |
428 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9227.99310 |
429 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 669.04940 |
430 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
431 | Fan:OnOff | AIRLOOP DATACENTER TOP SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.45139 |
432 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.45139 |
433 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Heating Capacity [W] | 9227.99310 |
434 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.25993E-004 |
435 | Coil:Heating:Electric | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 669.04940 |
436 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 0.12938 |
437 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 26659.82968 |
438 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 0.12938 |
439 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 15.52525 |
440 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 0.12938 |
441 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 0.12938 |
442 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 543060.69850 |
443 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 5.60000 |
444 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 1.37328E-002 |
445 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 1.64794 |
446 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 1.37328E-002 |
447 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 4135.73038 |
448 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
449 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 1569748.74601 |
450 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 1569748.75000 |
451 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 1.37328E-002 |
452 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 0.12938 |
453 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 15.52525 |
454 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 0.12938 |
455 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 18457.49939 |
456 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 0.12938 |
457 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 6.52100E-002 |
458 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1536592.24705 |
459 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1543939.29500 |
460 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Water Flow Rate [m3/s] | 7.64038E-002 |
461 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 0.12938 |
462 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 6.52100E-002 |
463 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 1536592.24705 |
464 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 1543939.29500 |
465 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Water Flow Rate [m3/s] | 7.64038E-002 |
466 | PlantLoop | SINGLE WATER PLANT LOOP | Maximum Loop Flow Rate [m3/s] | 1.33130E-002 |
467 | PlantLoop | SINGLE WATER PLANT LOOP | Plant Loop Volume [m3] | 1.59756 |
468 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Flow Rate [m3/s] | 1.33130E-002 |
469 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Power Consumption [W] | 3395.48410 |
470 | FluidCooler:TwoSpeed | CENTRAL TOWER | Design Water Flow Rate [m3/s] | 1.33130E-002 |
471 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at High Fan Speed [m3/s] | 139666.46671 |
472 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | 59194.70296 |
473 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at Low Fan Speed [m3/s] | 69833.23335 |
474 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fan Power at Low Fan Speed [W] | 7879.72339 |
475 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at Low Fan Speed [W/C] | 21407.39688 |
476 | Boiler:HotWater | CENTRAL BOILER | Design Size Nominal Capacity [W] | 548382.00728 |
477 | Boiler:HotWater | CENTRAL BOILER | User-Specified Nominal Capacity [W] | 537788.84000 |
478 | Boiler:HotWater | CENTRAL BOILER | Design Size Design Water Flow Rate [m3/s] | 1.33130E-002 |
479 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
480 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
481 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
482 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 5.95776 |
483 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
484 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 0.15281 |
485 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 18.33692 |
486 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 0.15281 |
487 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 46022.34362 |
488 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 58.79022 |
489 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 1831858.06222 |
490 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 11.75804 |
491 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 228982.25778 |
492 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 58.79022 |
493 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 1831858.06222 |
494 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 11.75804 |
495 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 228982.25778 |
496 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 7.93600E-002 |
497 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 7.93600E-002 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 18020.38 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 349236.22 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 58416.50 |
4 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 5356.82 |
5 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 4099.13 |
6 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 6953.99 |
7 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 3273.46 |
8 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 140070.62 |
9 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 93429.65 |
10 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 139158.19 |
11 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 82930.64 |
12 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 18726.72 |
13 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 12364.94 |
14 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 18624.88 |
15 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 11575.92 |
16 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | 22237.61 |
17 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | 208610.62 |
18 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | 20368.63 |
19 | Coil:Heating:Water | CAV_BAS HEATING COIL | 209415.47 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | 246350.29 | 166037.70 | 80312.59 | 0.67 | 25674.37 | 260.40 |
2 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | 2324475.12 | 1557559.90 | 766915.21 | 0.67 | 243261.58 | 2467.29 |
3 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | 245446.72 | 165579.17 | 79867.55 | 0.67 | 25572.17 | 259.37 |
4 | Coil:Cooling:Water | CAV_BAS COOLING COIL | 139490.03 | 96230.52 | 43259.51 | 0.69 | 14218.79 | 144.21 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | 6.84 | 23.33 |
2 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | 6.84 | 23.33 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.743 | 1.382 | 105.88 | 200.61 | 105.88 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_NORTH_0.25 | N/A | 2.869 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_NORTH_0.25 | N/A | 2.869 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_NORTH_0.25 | N/A | 2.869 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_NORTH_0.25 | N/A | 2.869 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_NORTH_0.25 | N/A | 2.869 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.743 | 1.382 | 71.89 | 133.74 | 71.89 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_EAST_0.25 | N/A | 2.869 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_EAST_0.25 | N/A | 2.869 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_EAST_0.25 | N/A | 2.869 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.743 | 1.382 | 105.88 | 200.61 | 105.88 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | N/A | 2.869 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | N/A | 2.869 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | N/A | 2.869 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | N/A | 2.869 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | N/A | 2.869 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.743 | 1.382 | 71.89 | 133.74 | 71.89 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_WEST_0.25 | N/A | 2.869 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_WEST_0.25 | N/A | 2.869 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_WEST_0.25 | N/A | 2.869 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.656 | 1.327 | 113.68 | 200.61 | 113.68 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_NORTH_0.25 | N/A | 2.869 | No | 86.92 | 86.92 | 86.92 | 0.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.656 | 1.327 | 75.79 | 133.74 | 75.79 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_EAST_0.25 | N/A | 2.869 | No | 57.95 | 57.95 | 57.95 | 90.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.656 | 1.327 | 113.68 | 200.61 | 113.68 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | N/A | 2.869 | No | 86.92 | 86.92 | 86.92 | 180.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.656 | 1.327 | 75.79 | 133.74 | 75.79 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_WEST_0.25 | N/A | 2.869 | No | 57.95 | 57.95 | 57.95 | 270.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 2.135 | 1.618 | 113.68 | 200.61 | 113.68 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_NORTH_0.25 | N/A | 2.869 | No | 86.92 | 86.92 | 86.92 | 0.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 2.135 | 1.618 | 75.79 | 133.74 | 75.79 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_EAST_0.25 | N/A | 2.869 | No | 57.95 | 57.95 | 57.95 | 90.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 2.135 | 1.618 | 113.68 | 200.61 | 113.68 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | N/A | 2.869 | No | 86.92 | 86.92 | 86.92 | 180.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 2.135 | 1.618 | 75.79 | 133.74 | 75.79 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.5047_SHGC_WEST_0.25 | N/A | 2.869 | No | 57.95 | 57.95 | 57.95 | 270.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.743 | 1.382 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.743 | 1.382 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.743 | 1.382 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.743 | 1.382 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.656 | 1.327 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.656 | 1.327 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.656 | 1.327 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.656 | 1.327 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 2.135 | 1.618 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 2.135 | 1.618 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 2.135 | 1.618 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 2.135 | 1.618 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 0.2137772604 | 0.2138114317 | Pass | Pass | 0.6983254466 | 0.6635844730 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 0.2779531181 | 0.2448828691 | Pass | Pass | 0.2948710649 | 0.4528436479 | Pass | Pass |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 0.1607523704 | 0.2008086195 | Pass | Pass | 0.2332335304 | 0.4215222089 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 0.1453835253 | 0.1967262428 | Pass | Pass | 0.2245773836 | 0.4149793043 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.2232170369 | 0.2075386451 | Pass | Pass | 0.2940590136 | 0.4524296115 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2943537134 | 0.2786977093 | Pass | Pass | 0.2957214022 | 0.4527831682 | Pass | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.4108400743 | 0.5199614057 | Pass | Pass | 0.3347059714 | 0.4999660248 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.3847274494 | 0.3836479870 | Pass | Pass | 0.3012588087 | 0.4518471448 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1363666115 | 0.1691947869 | Pass | Pass | 0.2318251869 | 0.4203152299 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2094990881 | 0.2363970741 | Pass | Pass | 0.2335652425 | 0.4224965040 | Pass | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.3448620155 | 0.5076044814 | Pass | Pass | 0.2814064208 | 0.4925364547 | Pass | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.2115586731 | 0.2891746034 | Pass | Pass | 0.2335338066 | 0.4195373098 | Pass | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1290791877 | 0.1688626524 | Pass | Pass | 0.2239731635 | 0.4137517113 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1994223504 | 0.2263827315 | Pass | Pass | 0.2257532957 | 0.4159830524 | Pass | Pass |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.3451102564 | 0.5262533203 | Pass | Pass | 0.2714273401 | 0.4917846578 | Pass | Pass |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.2090554843 | 0.2878429613 | Pass | Pass | 0.2253725342 | 0.4130166603 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 5.3516382014E-002 | 4.5836656463E-002 | Pass | Pass | 0.5233926237 | 2.3266375629 | Pass | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 4.2245890431E-002 | 4.6117621775E-002 | Pass | Pass | 0.7844715080 | 6.0825273154 | Pass | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 6.2256133760E-002 | 6.5623035030E-002 | Pass | Pass | 0.2473076538 | 0.4570897443 | Pass | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 7.4109437117E-006 | 8.4931035236E-006 | Pass | Pass | 3.1287125972E-003 | 3.6623397606E-003 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 6.9957677153E-006 | 8.2933606108E-006 | Pass | Pass | 4.0133893296E-003 | 4.3557143232E-003 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 6.7761443669E-006 | 8.1529628763E-006 | Pass | Pass | 6.3040276873E-003 | 4.7267348112E-003 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 1.0303987002E-005 | 1.4372986124E-005 | Pass | Pass | 4.6808360229E-005 | 1.0617894138E-004 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:59
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 5988.10 | -31.9 | 0.00 | 3638.66 | 32326.33 | 41921.20 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:59
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 4.60 | 0.00 | 4.60 | Wetbulb [C] | 2.50 | 10.00 |
TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 33.90 | 7.90 | 25.10 | Wetbulb [C] | 3.10 | 270.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 66.00 | 12 | |||
Feb | 66.00 | 22 | |||
Mar | 126.00 | 32 | |||
Apr | 206.00 | 19 | |||
May | 144.00 | 46 | |||
Jun | 99.00 | 30 | |||
Jul | 192.00 | 52 | |||
Aug | 240.00 | 34 | |||
Sep | 310.00 | 44 | |||
Oct | 34.00 | 10 | |||
Nov | 63.00 | 12 | |||
Dec | 35.00 | 24 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:59
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.845 | 0.940 | 118.87 | 118.87 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 139.09 | 139.09 | 180.00 | 90.00 | S |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 139.09 | 139.09 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.382 | 1.743 | 200.61 | 105.88 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.382 | 1.743 | 133.74 | 71.89 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.382 | 1.743 | 200.61 | 105.88 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.382 | 1.743 | 133.74 | 71.89 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.327 | 1.656 | 2006.06 | 1136.85 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 1.327 | 1.656 | 1337.37 | 757.90 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.327 | 1.656 | 2006.06 | 1136.85 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 1.327 | 1.656 | 1337.37 | 757.90 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.618 | 2.135 | 200.61 | 113.68 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.618 | 2.135 | 133.74 | 75.79 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.618 | 2.135 | 200.61 | 113.68 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.618 | 2.135 | 133.74 | 75.79 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.382 | 1.743 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.382 | 1.743 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.382 | 1.743 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.382 | 1.743 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.327 | 1.656 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 1.327 | 1.656 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.327 | 1.656 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 1.327 | 1.656 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.618 | 2.135 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.618 | 2.135 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.618 | 2.135 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.618 | 2.135 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 39.22 | 39.22 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 39.22 | 39.22 | 180.00 | 90.00 | S |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.845 | 0.940 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 270.00 | 90.00 | W |
BASEMENT_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 2779.43 | 2779.43 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 2076.77 | 2076.77 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 419.30 | 419.30 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 2076.82 | 2076.82 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 0.00 | 180.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.35 | 250.35 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 225.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 135.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.41 | 313.41 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
INT-PER3S-NE-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
INT-PER3S-NE | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.42 | 313.42 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
GROUNDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
iz-DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 0.00 | 180.00 | |
MIDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 35631.06 | 35631.06 | 180.00 | 0.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_BOT_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_BOT_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_MID_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
DATACENTER_MID_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
DATACENTER_MID_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 362.03 | 362.03 | 0.00 | 180.00 | |
DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 180.00 | 0.00 | |
DATACENTER_TOP_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_TOP_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_TOP_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 783.68 | 783.68 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 419.35 | 419.35 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 135.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.08 | 63.08 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 180.00 | 0.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 7126.21 | 0.00 | 90.00 | N | ||
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 50646.53 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.26 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.50 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.35 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.48 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.5047_SHGC_NORTH_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.5047_SHGC_NORTH_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.5047_SHGC_NORTH_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.5047_SHGC_NORTH_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.5047_SHGC_NORTH_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.5047_SHGC_EAST_0.25 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.5047_SHGC_EAST_0.25 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.5047_SHGC_EAST_0.25 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.5047_SHGC_WEST_0.25 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.5047_SHGC_WEST_0.25 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.5047_SHGC_WEST_0.25 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.869 | 0.251 | 0.251 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.5047_SHGC_NORTH_0.25 | 86.92 | 0.00 | 0.00 | 86.92 | 869.21 | 2.869 | 0.251 | 0.251 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.5047_SHGC_EAST_0.25 | 57.95 | 0.00 | 0.00 | 57.95 | 579.48 | 2.869 | 0.251 | 0.251 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | 86.92 | 0.00 | 0.00 | 86.92 | 869.21 | 2.869 | 0.251 | 0.251 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.5047_SHGC_WEST_0.25 | 57.95 | 0.00 | 0.00 | 57.95 | 579.48 | 2.869 | 0.251 | 0.251 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.5047_SHGC_NORTH_0.25 | 86.92 | 0.00 | 0.00 | 86.92 | 86.92 | 2.869 | 0.251 | 0.251 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.5047_SHGC_EAST_0.25 | 57.95 | 0.00 | 0.00 | 57.95 | 57.95 | 2.869 | 0.251 | 0.251 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.5047_SHGC_SOUTH_0.25 | 86.92 | 0.00 | 0.00 | 86.92 | 86.92 | 2.869 | 0.251 | 0.251 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.5047_SHGC_WEST_0.25 | 57.95 | 0.00 | 0.00 | 57.95 | 57.95 | 2.869 | 0.251 | 0.251 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 3476.85 | 2.869 | 0.251 | 0.251 | |||||||||||||||||
North Total or Average | 1043.06 | 2.869 | 0.251 | 0.251 | |||||||||||||||||
Non-North Total or Average | 2433.80 | 2.869 | 0.251 | 0.251 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:59
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:59
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 7.6202 | 2779.43 | 21179.74 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 44.71 | 0.0000 | Y | 177.74 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 7.6202 | 2496.12 | 19020.89 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 44.71 | 0.0000 | Y | 159.62 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 7.6202 | 24961.20 | 190208.95 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 44.71 | 0.0000 | Y | 1596.24 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 7.6202 | 2496.12 | 19020.89 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 44.71 | 0.0000 | Y | 159.62 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 7.6202 | 313.41 | 2388.26 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 30.71 | 0.0000 | Y | 13.77 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 7.6202 | 201.98 | 1539.09 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 30.65 | 0.0000 | Y | 8.86 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 7.6202 | 313.42 | 2388.32 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 30.46 | 0.0000 | Y | 13.66 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 7.6202 | 201.98 | 1539.09 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 30.64 | 0.0000 | Y | 8.85 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 7.6202 | 3134.13 | 23882.63 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 30.75 | 0.0000 | Y | 137.84 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 7.6202 | 2019.75 | 15390.88 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 30.66 | 0.0000 | Y | 88.58 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 7.6202 | 3134.20 | 23883.15 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 30.48 | 0.0000 | Y | 136.65 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 7.6202 | 2019.75 | 15390.88 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 30.66 | 0.0000 | Y | 88.58 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 7.6202 | 313.41 | 2388.26 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 30.75 | 0.0000 | Y | 13.78 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 7.6202 | 201.98 | 1539.09 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 30.66 | 0.0000 | Y | 8.86 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 7.6202 | 313.42 | 2388.32 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 30.48 | 0.0000 | Y | 13.67 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 7.6202 | 201.98 | 1539.09 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 30.66 | 0.0000 | Y | 8.86 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GENERAL | 7.6202 | 783.68 | 5971.78 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 44.71 | 0.0000 | Y | 50.12 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | DATACENTER_BOT_ZN_6 | GENERAL | 12.5114 | 36.20 | 452.95 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 4.64 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | DATACENTER_MID_ZN_6 | GENERAL | 12.5114 | 362.03 | 4529.48 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 46.40 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | DATACENTER_TOP_ZN_6 | GENERAL | 12.5114 | 36.20 | 452.95 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 4.64 |
Interior Lighting Total | 7.6661 | 46320.38 | 355094.67 | 856.11 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2388.32 | 921.17 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 2388.32 | 0.00 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1539.09 | 593.63 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1539.09 | 0.00 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2388.26 | 921.15 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 2388.26 | 0.00 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1539.09 | 593.63 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1539.09 | 0.00 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2388.32 | 921.17 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 2388.32 | 0.00 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1539.09 | 593.63 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1539.09 | 0.00 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2388.26 | 921.15 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 2388.26 | 0.00 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1539.09 | 593.63 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1539.09 | 0.00 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2388.32 | 921.17 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 2388.32 | 0.00 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1539.09 | 593.63 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1539.09 | 0.00 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2388.26 | 921.15 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 2388.26 | 0.00 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1539.09 | 593.63 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1539.09 | 0.00 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 9973.05 | AstronomicalClock | - | 41.73 | 41.73 | 78.11 | |
EXTERIOR_LIGHTS_B | 27638.03 | AstronomicalClock | - | 83.73 | 71.13 | 369.00 | |
Exterior Lighting Total | 37611.08 | 447.11 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:59
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 3034146.19 | |||||
HEATSYS1 BOILER | Boiler:HotWater | 1569748.75 | 0.81 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:ReformulatedEIR | 1543939.29 | 6.28 | 1477742.28 | 5.98 | 6.84 | 23.33 |
COOLSYS1 CHILLER2 | Chiller:Electric:ReformulatedEIR | 1543939.29 | 6.28 | 1477742.28 | 5.98 | 6.84 | 23.33 |
CENTRAL TOWER | FluidCooler:TwoSpeed | 582060.00 | |||||
CENTRAL BOILER | Boiler:HotWater | 537788.84 | 0.80 | ||||
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 1831858.06 | |||||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 1831858.06 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | 247829.88 | 246350.29 | 166037.70 | 80312.59 | 0.67 | - | 25674.37 | 260.40 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | 2420734.69 | 2324475.12 | 1557559.90 | 766915.21 | 0.67 | - | 243261.58 | 2467.29 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | 245566.35 | 245446.72 | 165579.17 | 79867.55 | 0.67 | - | 25572.17 | 259.37 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | 127008.98 | 139490.03 | 96230.52 | 43259.51 | 0.69 | - | 14218.79 | 144.21 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 434337.82 | 312325.51 | 122012.31 | 0.72 | 0.00 | |||
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9501.30 | 6820.69 | 2680.62 | 0.72 | 0.00 | |||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 90544.49 | 64905.21 | 25639.27 | 0.72 | 0.00 | |||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9227.99 | 6617.53 | 2610.47 | 0.72 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 19004.94 | 18020.38 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 368521.24 | 349236.22 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 61690.93 | 58416.50 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 5654.10 | 5356.82 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 4326.48 | 4099.13 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 7343.12 | 6953.99 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 3453.00 | 3273.46 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 147829.41 | 140070.62 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 98605.52 | 93429.65 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 146866.25 | 139158.19 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 87523.00 | 82930.64 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 19765.21 | 18726.72 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 13050.70 | 12364.94 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 19657.69 | 18624.88 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 12217.78 | 11575.92 | - |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | 26182.45 | 22237.61 | - |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | 246020.64 | 208610.62 | - |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | 23750.39 | 20368.63 | - |
CAV_BAS HEATING COIL | Coil:Heating:Water | 258285.90 | 209415.47 | - |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 434337.82 | 0.00 | |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9501.30 | 0.00 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 90544.49 | 0.00 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9227.99 | 0.00 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | 14482.89 | 1.00 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | 669.05 | 1.00 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | 6690.49 | 1.00 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | 669.05 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 8.94 | 19322.59 | 2160.95 | 1.00 | 1.12 | General | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 82.72 | 178751.49 | 2160.95 | 1.00 | 1.08 | General | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 8.94 | 19309.67 | 2160.95 | 1.00 | 1.12 | General | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:40:00 |
CAV_BAS FAN | Fan:ConstantVolume | 0.60 | 1018.41 | 5.48 | 9290.26 | 1695.65 | 1.00 | 1.16 | General | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 0.61 | 1018.41 | 21.33 | 35369.70 | 1657.97 | 1.00 | 1.13 | General | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 07:10:00 |
AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.47 | 521.61 | 1120.11 | 1.00 | 1.64 | General | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 4.43 | 4957.19 | 1120.11 | 1.00 | 1.16 | General | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.45 | 505.60 | 1120.11 | 1.00 | 1.65 | General | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 133527.72 | 0.129377 | 26659.83 | 206062.94 | 0.90 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.013733 | 4135.73 | 301156.09 | 0.90 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 92445.74 | 0.129377 | 18457.50 | 142664.32 | 0.90 | General |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.013313 | 3395.48 | 255050.01 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 3168.45 | 0.000440 | 5.96 | 13540.37 | 0.30 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 180718.98 | 0.152808 | 46022.34 | 301178.23 | 0.90 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.50 | 0.08 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:59
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 76041.58 | 76041.58 | 27.36 | 5.479 | 5.479 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00896 | 28.05 | 0.01653 | 1.200 | 0.00 |
CORE_BOTTOM | 78274.25 | 78274.25 | 31.36 | 5.639 | 5.639 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00890 | 28.05 | 0.01653 | 1.078 | 0.00 |
CORE_MID | 733090.75 | 733090.75 | 293.69 | 52.798 | 52.798 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00893 | 28.05 | 0.01653 | 10.778 | 0.00 |
CORE_TOP | 72622.80 | 72622.80 | 29.09 | 5.230 | 5.230 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00893 | 28.05 | 0.01653 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 12489.89 | 12489.89 | 39.85 | 0.908 | 0.908 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 24.00 | 24.00 | 0.00895 | 33.90 | 0.01654 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 12778.37 | 12778.37 | 63.27 | 0.929 | 0.929 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:40:00 | 24.00 | 24.00 | 0.00879 | 30.45 | 0.01653 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 15118.40 | 15118.40 | 48.24 | 1.099 | 1.099 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 24.00 | 24.00 | 0.00887 | 33.77 | 0.01654 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 16449.13 | 16449.13 | 81.44 | 1.196 | 1.196 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 24.00 | 24.00 | 0.00872 | 32.79 | 0.01653 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 115832.28 | 115832.28 | 369.58 | 8.424 | 8.424 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 24.00 | 24.00 | 0.00918 | 33.90 | 0.01654 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 130468.12 | 130468.12 | 645.96 | 9.488 | 9.488 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:50:00 | 24.00 | 24.00 | 0.00891 | 30.67 | 0.01653 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 142290.73 | 142290.73 | 453.99 | 10.348 | 10.348 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 24.00 | 24.00 | 0.00906 | 33.83 | 0.01654 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 138251.92 | 138251.92 | 684.50 | 10.054 | 10.054 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | 24.00 | 24.00 | 0.00888 | 32.66 | 0.01653 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 13303.13 | 13303.13 | 42.45 | 0.967 | 0.967 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 24.00 | 24.00 | 0.00917 | 33.82 | 0.01654 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 13327.86 | 13327.86 | 65.99 | 0.969 | 0.969 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:10:00 | 24.00 | 24.00 | 0.00895 | 31.10 | 0.01653 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 15886.02 | 15886.02 | 50.69 | 1.155 | 1.155 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 24.00 | 24.00 | 0.00906 | 33.90 | 0.01654 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 14995.23 | 14995.23 | 74.24 | 1.091 | 1.091 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 24.00 | 24.00 | 0.00890 | 32.79 | 0.01653 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 8120.36 | 8120.36 | 224.30 | 0.466 | 0.466 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:20:00 | 27.00 | 27.00 | 0.00850 | 26.05 | 0.01652 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 77163.21 | 77163.21 | 2131.42 | 4.426 | 4.426 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 27.00 | 27.00 | 0.00859 | 31.21 | 0.01653 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 7870.20 | 7870.20 | 217.39 | 0.451 | 0.451 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 27.00 | 27.00 | 0.00859 | 31.21 | 0.01653 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 371959.73 | 371959.73 | 474.63 | 21.333 | 21.333 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 07:00:00 | 27.00 | 27.00 | 0.00854 | 26.71 | 0.01652 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | 00:10:00 | 15.60 | 25.28 | 0.00526 | 4.60 | 0.00526 | 1.200 | 0.00 | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.000 | 1.078 | 00:10:00 | 15.60 | 22.87 | 0.00526 | 4.60 | 0.00526 | 1.078 | 0.00 | |
CORE_MID | 183142.70 | 183142.70 | 73.37 | 7.674 | 10.778 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 4.60 | 0.00526 | 10.778 | 0.00 |
CORE_TOP | 42695.79 | 42695.79 | 17.10 | 1.810 | 1.810 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 4.60 | 0.00526 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 3273.41 | 3273.41 | 10.44 | 0.138 | 0.138 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00711 | 4.60 | 0.00526 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 2459.77 | 2459.77 | 12.18 | 0.104 | 0.104 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00720 | 4.60 | 0.00526 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 4957.08 | 4957.08 | 15.82 | 0.210 | 0.210 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00738 | 4.60 | 0.00526 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 1052.25 | 1052.25 | 5.21 | 0.045 | 0.087 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00668 | 4.60 | 0.00526 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 103514.35 | 103514.35 | 330.28 | 4.408 | 4.408 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00764 | 4.60 | 0.00526 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 69043.47 | 69043.47 | 341.84 | 2.941 | 2.941 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00766 | 4.60 | 0.00526 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 102840.95 | 102840.95 | 328.13 | 4.380 | 4.380 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00764 | 4.60 | 0.00526 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 61294.70 | 61294.70 | 303.48 | 2.610 | 2.610 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00757 | 4.60 | 0.00526 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 13834.65 | 13834.65 | 44.14 | 0.590 | 0.590 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00776 | 4.60 | 0.00526 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 9134.60 | 9134.60 | 45.23 | 0.389 | 0.389 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00776 | 4.60 | 0.00526 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 13759.49 | 13759.49 | 43.90 | 0.587 | 0.587 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00776 | 4.60 | 0.00526 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 8552.36 | 8552.36 | 42.34 | 0.365 | 0.365 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00773 | 4.60 | 0.00526 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | 00:10:00 | 18.00 | 27.00 | 0.00850 | 4.60 | 0.00526 | 0.016 | 0.00 | |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | 00:10:00 | 18.00 | 24.95 | 0.00797 | 4.60 | 0.00526 | 0.156 | 0.00 | |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | 00:10:00 | 18.00 | 24.02 | 0.00549 | 4.60 | 0.00526 | 0.016 | 0.00 | |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | 00:10:00 | 18.00 | 27.00 | 0.00850 | 4.60 | 0.00526 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV_BOT WITH REHEAT | 8.94 | 8.94 | 1.62 | 1.62 | 8.9417 | 2.7887 | 8.9417 | 0.3119 | 0.3000 |
VAV_MID WITH REHEAT | 82.72 | 82.72 | 25.12 | 25.12 | 82.7191 | 26.9693 | 82.7191 | 0.3260 | 0.3000 |
VAV_TOP WITH REHEAT | 8.94 | 8.94 | 3.74 | 3.74 | 8.9357 | 3.7405 | 8.9357 | 0.4186 | 0.3000 |
CAV_BAS | 5.48 | 5.48 | 1.20 | 1.20 | 5.4789 | 5.4789 | 5.4789 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.33 | 21.33 | 0.34 | 0.34 | 21.3331 | 21.3329 | 21.3331 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.47 | 0.47 | 0.02 | 0.02 | 0.4657 | 0.4657 | 0.4657 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 4.43 | 4.43 | 0.16 | 0.16 | 4.4256 | 4.4256 | 4.4256 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.45 | 0.45 | 0.02 | 0.02 | 0.4514 | 0.4514 | 0.4514 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 19004.937 | 19004.937 | 1.889076 | 0.00016626 | 383.125 | 1/21 00:10:00 | 1/21 00:10:00 | 19004.94 | 19004.94 | 1.889076 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00800000 | 51.6744 | 0.00 | 0.00 | 19075.01 | 19075.01 | ||
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 368521.244 | 368521.244 | 18.426480 | 0.00322398 | 8236.549 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 368521.24 | 368521.24 | 18.426480 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00800000 | 51.6744 | 183142.70 | 0.00 | 369784.63 | 369784.63 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 61690.929 | 61690.929 | 1.888102 | 0.00053970 | 1609.031 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 61690.93 | 61690.93 | 1.888102 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00800000 | 51.6744 | 42695.79 | 0.00 | 61879.53 | 61879.53 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 5654.098 | 5654.098 | 0.237053 | 0.00004946 | 132.029 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 5654.10 | 5654.10 | 0.237053 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00710692 | 45.9738 | 3273.41 | 0.00 | 5672.69 | 5672.69 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 4326.478 | 4326.478 | 0.185845 | 0.00003785 | 100.356 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4326.48 | 4326.48 | 0.185845 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00719888 | 46.5621 | 2459.77 | 0.00 | 4340.76 | 4340.76 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 7343.115 | 7343.115 | 0.237468 | 0.00006424 | 187.124 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 7343.12 | 7343.12 | 0.237468 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00738152 | 47.7294 | 4957.08 | 0.00 | 7365.78 | 7365.78 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 3453.003 | 3453.003 | 0.239230 | 0.00003021 | 72.729 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 3453.00 | 3453.00 | 0.239230 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00667577 | 43.2134 | 1052.25 | 0.00 | 3465.48 | 3465.48 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 147829.410 | 147829.410 | 4.408361 | 0.00129328 | 3900.550 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 147829.41 | 147829.41 | 4.408361 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00764445 | 49.4092 | 103514.35 | 0.00 | 148328.09 | 148328.09 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 98605.522 | 98605.522 | 2.940693 | 0.00086264 | 2601.666 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 98605.52 | 98605.52 | 2.940693 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00765689 | 49.4886 | 69043.47 | 0.00 | 98937.52 | 98937.52 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 146866.255 | 146866.255 | 4.379573 | 0.00128485 | 3875.163 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 146866.25 | 146866.25 | 4.379573 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00764032 | 49.3828 | 102840.95 | 0.00 | 147361.87 | 147361.87 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 87523.003 | 87523.003 | 2.609522 | 0.00076569 | 2309.525 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 87523.00 | 87523.00 | 2.609522 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00757209 | 48.9476 | 61294.70 | 0.00 | 87819.60 | 87819.60 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 19765.206 | 19765.206 | 0.589819 | 0.00017291 | 521.349 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 19765.21 | 19765.21 | 0.589819 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00775967 | 50.1441 | 13834.65 | 0.00 | 19830.69 | 19830.69 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 13050.699 | 13050.699 | 0.389472 | 0.00011417 | 344.231 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 13050.70 | 13050.70 | 0.389472 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00776160 | 50.1565 | 9134.60 | 0.00 | 13093.87 | 13093.87 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 19657.691 | 19657.691 | 0.586603 | 0.00017197 | 518.516 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 19657.69 | 19657.69 | 0.586603 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00775753 | 50.1305 | 13759.49 | 0.00 | 19722.84 | 19722.84 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 12217.775 | 12217.775 | 0.364566 | 0.00010689 | 322.281 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12217.78 | 12217.78 | 0.364566 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00772955 | 49.9521 | 8552.36 | 0.00 | 12258.34 | 12258.34 |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 247829.882 | -999.000 | 8.941724 | 0.01054326 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 247829.88 | 172633.37 | 8.941724 | 26.93 | 19.52 | 0.01117472 | 11.05 | 11.05 | 0.00850000 | 33.90 | 0.01653638 | 25.13 | 28.3859 | 24.00 | 0.00891574 | 47.9268 | 117750.75 | 0.00 | 248209.30 | 168596.78 |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 26182.451 | 26182.451 | 2.682517 | 0.00022906 | 452.913 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 26182.45 | 26182.45 | 2.682517 | 4.73 | 4.71 | 0.00529132 | 12.80 | 11.59 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 94.6197 | 21.96 | 0.00617385 | 37.7135 | 11742.51 | 0.00 | 26920.67 | 26920.67 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 2420734.695 | -999.000 | 82.719065 | 0.10298365 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 2420734.69 | 1632276.66 | 82.719065 | 27.29 | 19.91 | 0.01153489 | 11.05 | 11.05 | 0.00850000 | 33.90 | 0.01653638 | 25.13 | 30.6845 | 24.00 | 0.00904016 | 48.5870 | 1048802.15 | 0.00 | 2423637.37 | 1599968.41 |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 246020.642 | 246020.642 | 24.815719 | 0.00215230 | 4252.083 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 246020.64 | 246020.64 | 24.815719 | 4.60 | 4.60 | 0.00525715 | 12.80 | 11.59 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 102.2817 | 21.00 | 0.00776067 | 50.1499 | 519836.16 | 0.00 | 252541.00 | 252541.00 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 245566.353 | -999.000 | 8.935743 | 0.01044696 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:40:00 | 245566.35 | 171304.97 | 8.935743 | 26.82 | 19.47 | 0.01114288 | 11.05 | 11.05 | 0.00850000 | 33.90 | 0.01653638 | 25.13 | 28.4049 | 24.00 | 0.00899056 | 48.3245 | 122368.39 | 0.00 | 245939.19 | 167231.14 |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 23750.386 | 23750.386 | 2.680723 | 0.00020778 | 412.954 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 23750.39 | 23750.39 | 2.680723 | 5.47 | 5.23 | 0.00539518 | 12.80 | 11.59 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 94.6830 | 21.00 | 0.00785329 | 50.7399 | 59135.00 | 0.00 | 24658.51 | 24658.51 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 127008.982 | -999.000 | 5.478862 | 0.00540326 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 127008.98 | 91034.07 | 5.478862 | 25.00 | 18.47 | 0.01062400 | 11.42 | 11.42 | 0.00850000 | 28.55 | 0.01652632 | 23.72 | 21.9052 | 24.00 | 0.00895956 | 48.1587 | 75031.25 | 0.00 | 127162.48 | 88610.75 |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | CAV_BAS | 258285.902 | 258285.902 | 5.478862 | 0.00225960 | 5860.879 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 258285.90 | 258285.90 | 5.478862 | 1.01 | 1.01 | 0.00525715 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 21.9052 | 25.28 | 0.00525715 | 26.3315 | 0.00 | 0.00 | 221550.43 | 221550.43 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 434337.817 | 312325.506 | 21.333099 | 0.01063691 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 07:10:00 | 406947.05 | 397013.16 | -999.0 | 28.51 | 18.07 | 0.00866922 | 12.80 | 12.09 | 0.00850000 | 33.90 | 0.01653638 | 25.13 | -999.0000 | 27.00 | 0.00854225 | 38.4505 | 371459.76 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9501.305 | 6820.687 | 0.465681 | 0.00023269 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:20:00 | 8904.61 | 8448.66 | -999.0 | 28.09 | 18.08 | 0.00885599 | 12.80 | 12.09 | 0.00850000 | 31.21 | 0.01653132 | 24.43 | -999.0000 | 27.00 | 0.00858924 | 38.6568 | 8115.11 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 90544.486 | 64905.212 | 4.425639 | 0.00221743 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 84897.54 | 80341.80 | -999.0 | 28.09 | 18.10 | 0.00887421 | 12.80 | 12.09 | 0.00850000 | 31.21 | 0.01653132 | 24.43 | -999.0000 | 27.00 | 0.00859384 | 38.6775 | 77163.21 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9227.993 | 6617.526 | 0.451387 | 0.00022599 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:30:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 8651.41 | 8195.83 | -999.0 | 28.10 | 18.09 | 0.00886692 | 12.80 | 12.09 | 0.00850000 | 31.41 | 0.01653169 | 24.48 | -999.0000 | 27.00 | 0.00859193 | 38.6689 | 7869.54 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 434337.817 | 434337.817 | 21.333099 | 0.01063691 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 434337.82 | 434337.82 | 21.333099 | 4.60 | 4.60 | 0.00525715 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 1.5862 | 27.00 | 0.00850000 | 38.2570 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9501.305 | 9501.305 | 0.465681 | 0.00023269 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9501.30 | 9501.30 | 0.465681 | 4.60 | 4.60 | 0.00525715 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 3.3569 | 27.00 | 0.00850000 | 38.2570 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 90544.486 | 90544.486 | 4.425639 | 0.00221743 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 90544.49 | 90544.49 | 4.425639 | 4.60 | 4.60 | 0.00525715 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 3.5322 | 24.95 | 0.00796561 | 40.5098 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9227.993 | 9227.993 | 0.451387 | 0.00022599 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9227.99 | 9227.99 | 0.451387 | 4.60 | 4.60 | 0.00525715 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 3.4632 | 24.02 | 0.00548951 | 29.6249 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 14482.888 | 14482.888 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 14482.89 | 14482.89 | 21.333099 | 0.07 | 0.07 | 0.00844856 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 1.5862 | 27.00 | 0.00850000 | 38.2570 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BOT | 669.049 | 669.049 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 669.05 | 669.05 | 0.465681 | 0.15 | 0.15 | 0.00839114 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 3.3569 | 27.00 | 0.00850000 | 38.2570 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER MID | 6690.494 | 6690.494 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 6690.49 | 6690.49 | 4.425639 | 0.16 | 0.16 | 0.00786994 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 3.5322 | 24.95 | 0.00796561 | 40.5098 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER TOP | 669.049 | 669.049 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 669.05 | 669.05 | 0.451387 | 0.16 | 0.16 | 0.00548147 | 40.00 | 21.17 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 3.4632 | 24.02 | 0.00548951 | 29.6249 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 09:04:59
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 19004.937 | 19004.937 | 1.889076 | 0.00016626 | 383.125 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.73144592 | 54.44 | 82.22 | 27.78 | 1601340.56 | 1.1868 | 1.210699 | 1/21 00:10:00 | unknown | unknown | 1/21 00:10:00 | Sensible | 19004.94 | 19004.94 | 1.0000 | 2.27287324 | 1.889076 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.16624652 | 60.00 | 32.22 | 27.78 | 0.000 | 19004.94 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 51.6744 | 0.00 | 0.00 | 19075.01 | 19075.01 | 2.27287324 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 21.03 | 14.86 | 0.00800000 | 41452.3 | |||
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 368521.244 | 368521.244 | 18.426480 | 0.00322398 | 8236.549 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.73144592 | 54.44 | 82.22 | 27.78 | 1601340.56 | 23.0133 | 23.476448 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 368521.24 | 368521.24 | 1.0000 | 22.17013120 | 18.426480 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 3.22365573 | 60.00 | 32.22 | 27.78 | 0.000 | 368521.24 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.57 | 0.00800000 | 21.00 | 0.00800000 | 51.6744 | 183142.70 | 0.00 | 369784.63 | 369784.63 | 22.17013120 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 29.16 | 17.75 | 0.00800000 | 49739.2 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 61690.929 | 61690.929 | 1.888102 | 0.00053970 | 1609.031 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.73144592 | 54.44 | 82.22 | 27.78 | 1601340.56 | 3.8525 | 3.929987 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 61690.93 | 61690.93 | 1.0000 | 2.27170139 | 1.888102 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.53964410 | 60.00 | 32.22 | 27.78 | 0.000 | 61690.93 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.86 | 0.00800000 | 21.00 | 0.00800000 | 51.6744 | 42695.79 | 0.00 | 61879.53 | 61879.53 | 2.27170139 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 39.51 | 21.04 | 0.00800000 | 60299.1 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5654.098 | 5654.098 | 0.237053 | 0.00004946 | 132.029 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.73144592 | 54.44 | 82.22 | 27.78 | 1601340.56 | 0.3531 | 0.360191 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 5654.10 | 5654.10 | 1.0000 | 0.28521482 | 0.237053 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.04945947 | 60.00 | 32.22 | 27.78 | 0.000 | 5654.10 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.87 | 0.00710692 | 21.00 | 0.00710692 | 45.9738 | 3273.41 | 0.00 | 5672.69 | 5672.69 | 0.28521482 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.30 | 18.80 | 0.00800000 | 52949.0 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4326.478 | 4326.478 | 0.185845 | 0.00003785 | 100.356 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.73144592 | 54.44 | 82.22 | 27.78 | 1601340.56 | 0.2702 | 0.275616 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 4326.48 | 4326.48 | 1.0000 | 0.22360230 | 0.185845 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.03784605 | 60.00 | 32.22 | 27.78 | 0.000 | 4326.48 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.87 | 0.00719888 | 21.00 | 0.00719888 | 46.5621 | 2459.77 | 0.00 | 4340.76 | 4340.76 | 0.22360230 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 31.84 | 18.64 | 0.00800000 | 52472.7 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7343.115 | 7343.115 | 0.237468 | 0.00006424 | 187.124 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.73144592 | 54.44 | 82.22 | 27.78 | 1601340.56 | 0.4586 | 0.467789 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 7343.12 | 7343.12 | 1.0000 | 0.28571408 | 0.237468 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.06423422 | 60.00 | 32.22 | 27.78 | 0.000 | 7343.12 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.86 | 0.00738152 | 21.00 | 0.00738152 | 47.7294 | 4957.08 | 0.00 | 7365.78 | 7365.78 | 0.28571408 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 38.08 | 20.61 | 0.00800000 | 58840.1 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3453.003 | 3453.003 | 0.239230 | 0.00003021 | 72.729 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.73144592 | 54.44 | 82.22 | 27.78 | 1601340.56 | 0.2156 | 0.219972 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 3453.00 | 3453.00 | 1.0000 | 0.28783346 | 0.239230 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.03020530 | 60.00 | 32.22 | 27.78 | 0.000 | 3453.00 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.91 | 0.00667577 | 21.00 | 0.00667577 | 43.2134 | 1052.25 | 0.00 | 3465.48 | 3465.48 | 0.28783346 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 24.61 | 16.17 | 0.00800000 | 45099.7 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 147829.410 | 147829.410 | 4.408361 | 0.00129328 | 3900.550 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.73144592 | 54.44 | 82.22 | 27.78 | 1601340.56 | 9.2316 | 9.417393 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 147829.41 | 147829.41 | 1.0000 | 5.30399358 | 4.408361 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 1.29314424 | 60.00 | 32.22 | 27.78 | 0.000 | 147829.41 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.91 | 0.00764445 | 21.00 | 0.00764445 | 49.4092 | 103514.35 | 0.00 | 148328.09 | 148328.09 | 5.30399358 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.22 | 21.25 | 0.00800000 | 61025.2 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 98605.522 | 98605.522 | 2.940693 | 0.00086264 | 2601.666 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.73144592 | 54.44 | 82.22 | 27.78 | 1601340.56 | 6.1577 | 6.281612 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 98605.52 | 98605.52 | 1.0000 | 3.53814431 | 2.940693 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.86255613 | 60.00 | 32.22 | 27.78 | 0.000 | 98605.52 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.91 | 0.00765689 | 21.00 | 0.00765689 | 49.4886 | 69043.47 | 0.00 | 98937.52 | 98937.52 | 3.53814431 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.22 | 21.25 | 0.00800000 | 61022.9 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 146866.255 | 146866.255 | 4.379573 | 0.00128485 | 3875.163 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.73144592 | 54.44 | 82.22 | 27.78 | 1601340.56 | 9.1715 | 9.356036 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 146866.25 | 146866.25 | 1.0000 | 5.26935745 | 4.379573 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 1.28471900 | 60.00 | 32.22 | 27.78 | 0.000 | 146866.25 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.91 | 0.00764032 | 21.00 | 0.00764032 | 49.3828 | 102840.95 | 0.00 | 147361.87 | 147361.87 | 5.26935745 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.23 | 21.25 | 0.00800000 | 61025.6 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 87523.003 | 87523.003 | 2.609522 | 0.00076569 | 2309.525 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.73144592 | 54.44 | 82.22 | 27.78 | 1601340.56 | 5.4656 | 5.575606 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 87523.00 | 87523.00 | 1.0000 | 3.13969091 | 2.609522 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.76561130 | 60.00 | 32.22 | 27.78 | 0.000 | 87523.00 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.91 | 0.00757209 | 21.00 | 0.00757209 | 48.9476 | 61294.70 | 0.00 | 87819.60 | 87819.60 | 3.13969091 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.23 | 21.25 | 0.00800000 | 61030.6 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 19765.206 | 19765.206 | 0.589819 | 0.00017291 | 521.349 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.73144592 | 54.44 | 82.22 | 27.78 | 1601340.56 | 1.2343 | 1.259132 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 19765.21 | 19765.21 | 1.0000 | 0.70965110 | 0.589819 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.17289701 | 60.00 | 32.22 | 27.78 | 0.000 | 19765.21 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.95 | 0.00775967 | 21.00 | 0.00775967 | 50.1441 | 13834.65 | 0.00 | 19830.69 | 19830.69 | 0.70965110 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 61004.1 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13050.699 | 13050.699 | 0.389472 | 0.00011417 | 344.231 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.73144592 | 54.44 | 82.22 | 27.78 | 1601340.56 | 0.8150 | 0.831388 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 13050.70 | 13050.70 | 1.0000 | 0.46859974 | 0.389472 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.11416156 | 60.00 | 32.22 | 27.78 | 0.000 | 13050.70 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.95 | 0.00776160 | 21.00 | 0.00776160 | 50.1565 | 9134.60 | 0.00 | 13093.87 | 13093.87 | 0.46859974 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 61002.4 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 19657.691 | 19657.691 | 0.586603 | 0.00017197 | 518.516 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.73144592 | 54.44 | 82.22 | 27.78 | 1601340.56 | 1.2276 | 1.252283 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 19657.69 | 19657.69 | 1.0000 | 0.70578189 | 0.586603 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.17195652 | 60.00 | 32.22 | 27.78 | 0.000 | 19657.69 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.95 | 0.00775753 | 21.00 | 0.00775753 | 50.1305 | 13759.49 | 0.00 | 19722.84 | 19722.84 | 0.70578189 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 61004.5 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12217.775 | 12217.775 | 0.364566 | 0.00010689 | 322.281 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 13.73144592 | 54.44 | 82.22 | 27.78 | 1601340.56 | 0.7630 | 0.778327 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 12217.78 | 12217.78 | 1.0000 | 0.43863325 | 0.364566 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 0.10687552 | 60.00 | 32.22 | 27.78 | 0.000 | 12217.78 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.95 | 0.00772955 | 21.00 | 0.00772955 | 49.9521 | 8552.36 | 0.00 | 12258.34 | 12258.34 | 0.43863325 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.21 | 21.24 | 0.00800000 | 61006.5 | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 247829.882 | -999.000 | 8.941724 | 0.01054326 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.6133 | 1004.8586 | 1.2032 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 8.941724 | 10.75838654 | 4197.9300 | 999.8980 | 129.36392424 | 12.27 | 6.67 | 5.60 | 3041139.91 | 8.1492 | 8.149243 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | Sensible | 247829.88 | 172633.37 | 1.0000 | 10.75838654 | 8.941724 | 26.93 | 19.52 | 0.01117472 | 55570.8 | 11.05 | 11.05 | 0.00850000 | 32534.9 | 10.54218056 | 6.67 | 12.27 | 5.60 | 19322.590 | 228507.29 | 33.90 | 0.01653638 | 25.13 | 2.53819000 | 28.3859 | 24.00 | 0.00891574 | 24.00 | 0.00891574 | 47.9268 | 117750.75 | 0.00 | 248209.30 | 168596.78 | 10.75838654 | 26.93 | 19.54 | 0.01117472 | 55570.8 | 11.65 | 11.36 | 0.00824123 | 32499.6 | |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 26182.451 | 26182.451 | 2.682517 | 0.00022906 | 452.913 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 8.941724 | 10.75838654 | 4197.9300 | 999.8980 | 13.73144592 | 54.44 | 82.22 | 27.78 | 1601340.56 | 1.6350 | 1.667939 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 26182.45 | 26182.45 | 1.0000 | 3.22751596 | 2.682517 | 4.73 | 4.71 | 0.00529132 | 18029.6 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 0.22903213 | 60.00 | 32.22 | 27.78 | 0.000 | 26182.45 | 4.60 | 0.00525715 | 4.60 | 2.53819000 | 94.6197 | 6.96 | 0.00589222 | 21.96 | 0.00617385 | 37.7135 | 11742.51 | 0.00 | 26920.67 | 26920.67 | 3.22751596 | 2.80 | 2.80 | 0.00529132 | 16074.4 | 11.02 | 7.85 | 0.00529132 | 24415.3 | |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 2420734.695 | -999.000 | 82.719065 | 0.10298365 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.2828 | 1004.8586 | 1.2032 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 82.719065 | 99.52484064 | 4197.9300 | 999.8980 | 129.36392424 | 12.27 | 6.67 | 5.60 | 3041139.91 | 79.5996 | 79.599583 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | Sensible | 2420734.69 | 1632276.66 | 1.0000 | 99.52484064 | 82.719065 | 27.29 | 19.91 | 0.01153489 | 56858.9 | 11.05 | 11.05 | 0.00850000 | 32536.0 | 102.97314452 | 6.67 | 12.27 | 5.60 | 178751.494 | 2241983.20 | 33.90 | 0.01653638 | 25.13 | 25.38195000 | 30.6845 | 24.00 | 0.00904016 | 24.00 | 0.00904016 | 48.5870 | 1048802.15 | 0.00 | 2423637.37 | 1599968.41 | 99.52484064 | 27.29 | 19.92 | 0.01153489 | 56858.9 | 11.63 | 11.36 | 0.00825409 | 32506.9 | |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 246020.642 | 246020.642 | 24.815719 | 0.00215230 | 4252.083 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 82.719065 | 99.52484064 | 4197.9300 | 999.8980 | 13.73144592 | 54.44 | 82.22 | 27.78 | 1601340.56 | 15.3634 | 15.672613 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 246020.64 | 246020.64 | 1.0000 | 29.85745219 | 24.815719 | 4.60 | 4.60 | 0.00525715 | 17815.0 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 2.15207634 | 60.00 | 32.22 | 27.78 | 0.000 | 246020.64 | 4.60 | 0.00525715 | 4.60 | 25.38195000 | 102.2817 | 20.76 | 0.00779025 | 21.00 | 0.00776067 | 50.1499 | 519836.16 | 0.00 | 252541.00 | 252541.00 | 29.85745219 | 2.80 | 2.80 | 0.00525715 | 15988.7 | 11.14 | 7.87 | 0.00525715 | 24447.0 | |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 245566.353 | -999.000 | 8.935743 | 0.01044696 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.5541 | 1004.8586 | 1.2032 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 8.935743 | 10.75119035 | 4197.9300 | 999.8980 | 129.36392424 | 12.27 | 6.67 | 5.60 | 3041139.91 | 8.0748 | 8.074813 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:40:00 | Sensible | 245566.35 | 171304.97 | 1.0000 | 10.75119035 | 8.935743 | 26.82 | 19.47 | 0.01114288 | 55375.6 | 11.05 | 11.05 | 0.00850000 | 32534.8 | 10.44589465 | 6.67 | 12.27 | 5.60 | 19309.665 | 226256.69 | 33.90 | 0.01653638 | 25.13 | 2.53819000 | 28.4049 | 24.00 | 0.00899056 | 24.00 | 0.00899056 | 48.3245 | 122368.39 | 0.00 | 245939.19 | 167231.14 | 10.75119035 | 26.82 | 19.48 | 0.01114288 | 55375.6 | 11.66 | 11.36 | 0.00824078 | 32500.1 | |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 23750.386 | 23750.386 | 2.680723 | 0.00020778 | 412.954 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 8.935743 | 10.75119035 | 4197.9300 | 999.8980 | 13.73144592 | 54.44 | 82.22 | 27.78 | 1601340.56 | 1.4832 | 1.513006 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 23750.39 | 23750.39 | 1.0000 | 3.22535710 | 2.680723 | 5.47 | 5.23 | 0.00539518 | 19046.4 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 0.20775754 | 60.00 | 32.22 | 27.78 | 0.000 | 23750.39 | 4.60 | 0.00525715 | 4.60 | 2.53819000 | 94.6830 | 21.00 | 0.00785329 | 21.00 | 0.00785329 | 50.7399 | 59135.00 | 0.00 | 24658.51 | 24658.51 | 3.22535710 | 2.80 | 2.80 | 0.00539518 | 16334.7 | 10.33 | 7.64 | 0.00539518 | 23979.9 | |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 127008.982 | -999.000 | 5.478862 | 0.00540326 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.5895 | 1004.8586 | 1.2032 | CAV_BAS FAN | Fan:ConstantVolume | 5.478862 | 6.59198528 | 4197.9300 | 999.8980 | 129.36392424 | 12.27 | 6.67 | 5.60 | 3041139.91 | 4.1764 | 4.176361 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | Sensible | 127008.98 | 91034.07 | 1.0000 | 6.59198528 | 5.478862 | 25.00 | 18.47 | 0.01062400 | 52185.5 | 11.42 | 11.42 | 0.00850000 | 32918.3 | 5.40270451 | 6.67 | 12.27 | 5.60 | 9290.256 | 117718.73 | 28.55 | 0.01652632 | 23.72 | 1.20015641 | 21.9052 | 24.00 | 0.00895956 | 24.00 | 0.00895956 | 48.1587 | 75031.25 | 0.00 | 127162.48 | 88610.75 | 6.59198528 | 25.00 | 18.48 | 0.01062400 | 52185.5 | 11.88 | 11.52 | 0.00830604 | 32895.0 | |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 258285.902 | 258285.902 | 5.478862 | 0.00225960 | 5860.879 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | CAV_BAS FAN | Fan:ConstantVolume | 5.478862 | 6.59198528 | 4197.9300 | 999.8980 | 13.73144592 | 54.44 | 82.22 | 27.78 | 1601340.56 | 16.1294 | 16.453965 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 258285.90 | 258285.90 | 1.0000 | 6.59198528 | 5.478862 | 1.01 | 1.01 | 0.00525715 | 14170.2 | 40.00 | 21.17 | 0.00800000 | 60796.0 | 2.25936724 | 60.00 | 32.22 | 27.78 | 0.000 | 258285.90 | 4.60 | 0.00525715 | 4.60 | 1.20015641 | 21.9052 | 0.00 | 0.00525715 | 25.28 | 0.00525715 | 26.3315 | 0.00 | 0.00 | 221550.43 | 221550.43 | 6.59198528 | 12.80 | 8.65 | 0.00525715 | 26134.9 | 45.93 | 20.95 | 0.00525715 | 59743.9 | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 434337.817 | 312325.506 | 21.333099 | 0.01063691 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.9556 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 07:10:00 | Sensible | 406947.05 | 397013.16 | 0.9369 | -999.0 | -999.0 | 28.51 | 18.07 | 0.00866922 | 50787.4 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 406947.05 | 33.90 | 0.01653638 | 25.13 | 0.33839277 | -999.0000 | 27.00 | 0.00854225 | 27.00 | 0.00854225 | 38.4505 | 371459.76 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9501.305 | 6820.687 | 0.465681 | 0.00023269 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1021.3028 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:20:00 | Sensible | 8904.61 | 8448.66 | 0.9372 | -999.0 | -999.0 | 28.09 | 18.08 | 0.00885599 | 50833.6 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8904.61 | 31.21 | 0.01653132 | 24.43 | 0.01563234 | -999.0000 | 27.00 | 0.00858924 | 27.00 | 0.00858924 | 38.6568 | 8115.11 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 90544.486 | 64905.212 | 4.425639 | 0.00221743 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1021.3367 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | Sensible | 84897.54 | 80341.80 | 0.9376 | -999.0 | -999.0 | 28.09 | 18.10 | 0.00887421 | 50887.5 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 84897.54 | 31.21 | 0.01653132 | 24.43 | 0.15632344 | -999.0000 | 27.00 | 0.00859384 | 27.00 | 0.00859384 | 38.6775 | 77163.21 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9227.993 | 6617.526 | 0.451387 | 0.00022599 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1021.3232 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:30:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:30:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | Sensible | 8651.41 | 8195.83 | 0.9375 | -999.0 | -999.0 | 28.10 | 18.09 | 0.00886692 | 50873.0 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8651.41 | 31.41 | 0.01653169 | 24.48 | 0.01563234 | -999.0000 | 27.00 | 0.00859193 | 27.00 | 0.00859193 | 38.6689 | 7869.54 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 434337.817 | 434337.817 | 21.333099 | 0.01063691 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 434337.82 | 434337.82 | 1.0000 | 25.66727840 | 21.333099 | 4.60 | 4.60 | 0.00525715 | 17815.0 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 434337.82 | 4.60 | 0.00525715 | 4.60 | 0.33839277 | 1.5862 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 38.2570 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9501.305 | 9501.305 | 0.465681 | 0.00023269 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 9501.30 | 9501.30 | 1.0000 | 0.56029140 | 0.465681 | 4.60 | 4.60 | 0.00525715 | 17815.0 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9501.30 | 4.60 | 0.00525715 | 4.60 | 0.01563234 | 3.3569 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 38.2570 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 90544.486 | 90544.486 | 4.425639 | 0.00221743 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 90544.49 | 90544.49 | 1.0000 | 5.32478286 | 4.425639 | 4.60 | 4.60 | 0.00525715 | 17815.0 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 90544.49 | 4.60 | 0.00525715 | 4.60 | 0.15632344 | 3.5322 | 0.00 | 0.00796561 | 24.95 | 0.00796561 | 40.5098 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9227.993 | 9227.993 | 0.451387 | 0.00022599 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 9227.99 | 9227.99 | 1.0000 | 0.54309410 | 0.451387 | 4.60 | 4.60 | 0.00525715 | 17815.0 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9227.99 | 4.60 | 0.00525715 | 4.60 | 0.01563234 | 3.4632 | 0.00 | 0.00548951 | 24.02 | 0.00548951 | 29.6249 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 14482.888 | 14482.888 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 21.333099 | 25.66727840 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 14482.89 | 14482.89 | 1.0000 | 25.66727840 | 21.333099 | 0.07 | 0.07 | 0.00844856 | 21203.8 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14482.89 | 4.60 | 0.00525715 | 4.60 | 0.33839277 | 1.5862 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 38.2570 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 669.049 | 669.049 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.465681 | 0.56029140 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 669.05 | 669.05 | 1.0000 | 0.56029140 | 0.465681 | 0.15 | 0.15 | 0.00839114 | 21143.3 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 669.05 | 4.60 | 0.00525715 | 4.60 | 0.01563234 | 3.3569 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 38.2570 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 6690.494 | 6690.494 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 4.425639 | 5.32478286 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 6690.49 | 6690.49 | 1.0000 | 5.32478286 | 4.425639 | 0.16 | 0.16 | 0.00786994 | 19847.9 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6690.49 | 4.60 | 0.00525715 | 4.60 | 0.15632344 | 3.5322 | 0.00 | 0.00796561 | 24.95 | 0.00796561 | 40.5098 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 669.049 | 669.049 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.451387 | 0.54309410 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 669.05 | 669.05 | 1.0000 | 0.54309410 | 0.451387 | 0.16 | 0.16 | 0.00548147 | 13870.5 | 40.00 | 21.17 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 669.05 | 4.60 | 0.00525715 | 4.60 | 0.01563234 | 3.4632 | 0.00 | 0.00548951 | 24.02 | 0.00548951 | 29.6249 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:59
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 8.94 | - | |||
VAV_MID WITH REHEAT_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 82.72 | - | |||
VAV_TOP WITH REHEAT_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 8.94 | - | |||
CAV_BAS_OA_CONTROLLER | DifferentialEnthalpy | 1.20 | 5.48 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 4934.67 | 1918.83 | 1852.83 |
CORE_BOTTOM | 4916.50 | 93.67 | 0.33 |
CORE_MID | 4470.83 | 664.33 | 0.00 |
CORE_TOP | 4275.83 | 1228.00 | 36.17 |
PERIMETER_BOT_ZN_3 | 4402.17 | 1159.00 | 107.50 |
PERIMETER_BOT_ZN_2 | 4440.50 | 1160.50 | 245.83 |
PERIMETER_BOT_ZN_1 | 4867.67 | 812.50 | 297.67 |
PERIMETER_BOT_ZN_4 | 5097.17 | 862.17 | 528.00 |
PERIMETER_MID_ZN_3 | 3968.00 | 2047.83 | 439.50 |
PERIMETER_MID_ZN_2 | 3497.00 | 1648.17 | 472.17 |
PERIMETER_MID_ZN_1 | 4674.83 | 1229.00 | 487.33 |
PERIMETER_MID_ZN_4 | 4352.83 | 1623.67 | 440.83 |
PERIMETER_TOP_ZN_3 | 4103.00 | 2327.17 | 776.67 |
PERIMETER_TOP_ZN_2 | 4195.83 | 2035.33 | 647.33 |
PERIMETER_TOP_ZN_1 | 4580.50 | 1519.33 | 612.67 |
PERIMETER_TOP_ZN_4 | 4304.67 | 1925.17 | 621.00 |
DATACENTER_BOT_ZN_6 | 5943.00 | 1603.17 | 1603.17 |
DATACENTER_MID_ZN_6 | 5940.67 | 138.33 | 138.33 |
DATACENTER_TOP_ZN_6 | 5890.83 | 394.67 | 383.17 |
DATACENTER_BASEMENT_ZN_6 | 5943.00 | 5943.00 | 5943.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5943.00 | 5943.00 | 5943.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 77.00 | 0.00 | 3.17 |
CORE_BOTTOM | 0.00 | 4.17 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.17 | 0.00 | 0.00 |
CORE_TOP | 0.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 8.17 | 0.00 | 1.33 |
PERIMETER_BOT_ZN_2 | 0.00 | 34.67 | 0.00 | 31.83 |
PERIMETER_BOT_ZN_1 | 0.00 | 66.33 | 0.00 | 54.33 |
PERIMETER_BOT_ZN_4 | 0.00 | 235.67 | 0.00 | 75.67 |
PERIMETER_MID_ZN_3 | 0.00 | 1.67 | 0.00 | 0.50 |
PERIMETER_MID_ZN_2 | 0.00 | 47.83 | 0.00 | 44.83 |
PERIMETER_MID_ZN_1 | 0.00 | 52.33 | 0.00 | 46.83 |
PERIMETER_MID_ZN_4 | 0.00 | 59.33 | 0.00 | 27.83 |
PERIMETER_TOP_ZN_3 | 6.00 | 26.17 | 1.50 | 17.33 |
PERIMETER_TOP_ZN_2 | 3.33 | 70.50 | 0.17 | 57.67 |
PERIMETER_TOP_ZN_1 | 1.83 | 72.83 | 0.00 | 55.67 |
PERIMETER_TOP_ZN_4 | 1.83 | 71.67 | 0.00 | 34.50 |
DATACENTER_BOT_ZN_6 | 0.00 | 48.67 | 0.00 | 48.67 |
DATACENTER_MID_ZN_6 | 0.00 | 53.33 | 0.00 | 53.33 |
DATACENTER_TOP_ZN_6 | 0.00 | 27.17 | 0.00 | 27.17 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 640.50 | 0.00 | 560.33 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 6.00 | 1067.00 | 1.50 | 754.67 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:59
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.43 | 149.60 | 6779.02 | 0.986 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 56.07 | 134.35 | 6849.35 | 0.685 | 0.000 | 0.000 | 0.000 |
CORE_MID | 56.07 | 134.35 | 6849.35 | 0.582 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 56.07 | 134.35 | 6849.35 | 0.544 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 7.04 | 16.87 | 860.00 | 0.672 | 0.034 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.54 | 10.87 | 554.22 | 0.838 | 0.035 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 7.04 | 16.87 | 860.02 | 0.991 | 0.034 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.54 | 10.87 | 554.22 | 1.338 | 0.035 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 7.04 | 16.87 | 860.00 | 0.618 | 0.079 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.97 | 10.87 | 554.22 | 0.784 | 0.087 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 7.04 | 16.87 | 860.02 | 0.948 | 0.079 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.54 | 10.87 | 554.22 | 0.918 | 0.082 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 7.04 | 16.87 | 860.00 | 0.607 | 0.098 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.54 | 10.87 | 554.22 | 0.835 | 0.102 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 7.04 | 16.87 | 860.02 | 0.898 | 0.098 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.54 | 10.87 | 554.22 | 0.903 | 0.102 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.427 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.427 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.427 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.60 | 42.18 | 1911.37 | 0.481 | 0.000 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.43 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 56.07 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 56.07 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 56.07 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 7.04 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.54 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 7.04 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.54 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 7.04 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.97 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 7.04 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.54 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 7.04 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.54 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 7.04 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.54 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.60 | 42.18 | 1911.37 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 09:04:59
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | CAV_BAS | 62.43 | 149.60 | 6779.02 | 2779.43 | 1.2002 | 1.200 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 56.07 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
CORE_MID | VAV_MID WITH REHEAT | 56.07 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 10.778 |
CORE_TOP | VAV_TOP WITH REHEAT | 56.07 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 7.04 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 4.54 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 7.04 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 4.54 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 7.04 | 16.87 | 860.00 | 313.41 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 3.97 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 7.04 | 16.87 | 860.02 | 313.42 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 4.54 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 7.04 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 4.54 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 7.04 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 4.54 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.81 | 1.95 | 99.34 | 36.20 | 0.1563 | 0.156 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 17.60 | 42.18 | 1911.37 | 783.68 | 0.3384 | 0.338 |
Total Facility | 1034.72 | 2493.19 | 126016.35 | 46320.38 | 1.7261 | 158.471 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 41242949.08 | 0.00 | 41242949.08 | 0.00 | 41242949.08 | 37848132.68 | 4061.63 | 2807.70 | 1890.66 | 279.57 |
CORE_BOTTOM | 29007425.90 | 0.00 | 29007425.90 | 0.00 | 29007425.90 | 33990283.35 | 6650.01 | 66.62 | 2043.37 | 260.44 |
CORE_MID | 0.24E+09 | 0.00 | 0.24E+09 | 0.00 | 0.24E+09 | 0.34E+09 | 6884.13 | 157.07 | 1718.80 | 57.31 |
CORE_TOP | 21909880.07 | 0.00 | 21909880.07 | 0.00 | 21909880.07 | 33990283.35 | 6997.90 | 220.17 | 1541.93 | 53.44 |
PERIMETER_BOT_ZN_3 | 3562426.67 | 0.00 | 3562426.67 | 328931.10 | 3891357.77 | 4267819.30 | 4504.54 | 103.84 | 4151.61 | 260.44 |
PERIMETER_BOT_ZN_2 | 2857984.58 | 0.00 | 2857984.58 | 219287.25 | 3077271.83 | 2750345.05 | 4207.53 | 54.47 | 4498.00 | 260.44 |
PERIMETER_BOT_ZN_1 | 5161264.68 | 0.00 | 5161264.68 | 328931.10 | 5490195.77 | 4267912.63 | 4114.47 | 52.34 | 4593.19 | 260.44 |
PERIMETER_BOT_ZN_4 | 4533338.36 | 0.00 | 4533338.36 | 219287.25 | 4752625.61 | 2750345.05 | 3905.14 | 0.17 | 4854.69 | 260.44 |
PERIMETER_MID_ZN_3 | 31343744.06 | 0.00 | 31343744.06 | 771421.61 | 32115165.67 | 42678193.03 | 4815.45 | 168.19 | 3776.36 | 57.31 |
PERIMETER_MID_ZN_2 | 27674715.71 | 0.00 | 27674715.71 | 514280.72 | 28188996.44 | 27503450.52 | 4235.93 | 17.25 | 4506.82 | 966.31 |
PERIMETER_MID_ZN_1 | 47911853.13 | 0.00 | 47911853.13 | 771421.61 | 48683274.74 | 42679126.28 | 4318.35 | 137.60 | 4304.05 | 57.31 |
PERIMETER_MID_ZN_4 | 29998114.40 | 0.00 | 29998114.40 | 514280.72 | 30512395.13 | 27503450.52 | 4187.78 | 3.53 | 4568.68 | 57.31 |
PERIMETER_TOP_ZN_3 | 3063840.16 | 0.00 | 3063840.16 | 957784.80 | 4021624.96 | 4267819.30 | 4909.01 | 221.47 | 3629.52 | 53.44 |
PERIMETER_TOP_ZN_2 | 2713892.85 | 0.00 | 2713892.85 | 638522.76 | 3352415.62 | 2750345.05 | 4275.69 | 12.33 | 4471.99 | 53.44 |
PERIMETER_TOP_ZN_1 | 4519844.20 | 0.00 | 4519844.20 | 957784.80 | 5477629.00 | 4267912.63 | 4435.09 | 184.92 | 4139.99 | 53.44 |
PERIMETER_TOP_ZN_4 | 2938320.15 | 0.00 | 2938320.15 | 638522.76 | 3576842.91 | 2750345.05 | 4248.09 | 2.50 | 4509.41 | 53.44 |
DATACENTER_BOT_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2442960.18 | 0.00 | 2442960.18 | 0.00 | 2442960.18 | 4929815.99 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 5288266.81 | 0.00 | 5288266.81 | 0.00 | 5288266.81 | 10671554.30 | 4419.00 | 4341.00 | 0.00 | 0.00 |
Total Facility | 0.39E+10 | 0.00 | 0.39E+10 | 30003098.57 | 0.39E+10 | 0.50E+10 | 7433.97 | 4358.71 | 5001.69 | 1336.25 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 1.8166 | 0.0000 | 1.8166 | 0.0000 | 1.8166 | 1.2002 | 1441.32 | 2805.78 | 1695.89 |
CORE_BOTTOM | 1.2761 | 0.0000 | 1.2761 | 0.0000 | 1.2761 | 1.0778 | 4074.68 | 65.27 | 1803.05 |
CORE_MID | 10.8425 | 0.0000 | 10.8425 | 0.0000 | 10.8425 | 10.7782 | 4118.96 | 157.07 | 1666.97 |
CORE_TOP | 1.0141 | 0.0000 | 1.0141 | 0.0000 | 1.0141 | 1.0778 | 4201.74 | 220.12 | 1521.15 |
PERIMETER_BOT_ZN_3 | 0.1572 | 0.0000 | 0.1572 | 0.0079 | 0.1651 | 0.1353 | 1926.96 | 102.38 | 3913.67 |
PERIMETER_BOT_ZN_2 | 0.1263 | 0.0000 | 0.1263 | 0.0053 | 0.1315 | 0.0872 | 1645.17 | 54.07 | 4243.77 |
PERIMETER_BOT_ZN_1 | 0.2318 | 0.0000 | 0.2318 | 0.0079 | 0.2397 | 0.1353 | 1537.13 | 50.73 | 4355.14 |
PERIMETER_BOT_ZN_4 | 0.2016 | 0.0000 | 0.2016 | 0.0053 | 0.2069 | 0.0872 | 1348.58 | 0.17 | 4594.26 |
PERIMETER_MID_ZN_3 | 1.4449 | 0.0000 | 1.4449 | 0.0185 | 1.4633 | 1.3533 | 2050.11 | 168.19 | 3724.70 |
PERIMETER_MID_ZN_2 | 1.1817 | 0.0000 | 1.1817 | 0.0131 | 1.1948 | 0.8721 | 1443.78 | 12.27 | 3577.95 |
PERIMETER_MID_ZN_1 | 2.2185 | 0.0000 | 2.2185 | 0.0185 | 2.2370 | 1.3533 | 1552.89 | 137.60 | 4252.51 |
PERIMETER_MID_ZN_4 | 1.3840 | 0.0000 | 1.3840 | 0.0123 | 1.3963 | 0.8721 | 1425.21 | 3.53 | 4514.25 |
PERIMETER_TOP_ZN_3 | 0.1420 | 0.0000 | 0.1420 | 0.0229 | 0.1649 | 0.1353 | 2114.36 | 221.39 | 3607.24 |
PERIMETER_TOP_ZN_2 | 0.1259 | 0.0000 | 0.1259 | 0.0153 | 0.1412 | 0.0872 | 1482.69 | 11.45 | 4448.86 |
PERIMETER_TOP_ZN_1 | 0.2100 | 0.0000 | 0.2100 | 0.0229 | 0.2329 | 0.1353 | 1639.26 | 184.87 | 4118.87 |
PERIMETER_TOP_ZN_4 | 0.1362 | 0.0000 | 0.1362 | 0.0153 | 0.1515 | 0.0872 | 1457.16 | 2.29 | 4483.54 |
DATACENTER_BOT_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.1142 | 0.0000 | 0.1142 | 0.0000 | 0.1142 | 0.1563 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.2472 | 0.0000 | 0.2472 | 0.0000 | 0.2472 | 0.3384 | 1602.00 | 4341.00 | 0.00 |
Total Facility | 177.5652 | 0.0000 | 177.5652 | 0.7263 | 178.2916 | 158.4706 | 4616.97 | 4353.20 | 4635.13 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV_BOT WITH REHEAT | 65320344.90 | 0.00 | 65320344.90 | 48026705.38 | 3905.14 | 0.94 | 4853.92 | 260.44 |
VAV_MID WITH REHEAT | 0.54E+09 | 0.00 | 0.54E+09 | 0.48E+09 | 4174.66 | 2.36 | 4582.98 | 57.31 |
VAV_TOP WITH REHEAT | 50876716.33 | 0.00 | 50876716.33 | 48026705.38 | 4236.54 | 1.92 | 4521.55 | 53.44 |
CAV_BAS | 59703729.48 | 0.00 | 59703729.48 | 37848132.68 | 4021.96 | 2.04 | 4736.00 | 279.57 |
AIRLOOP DATACENTER BASEMENT | 7655350.99 | 0.00 | 7655350.99 | 10671554.30 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER BOT | 353645.50 | 0.00 | 353645.50 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER MID | 3536455.01 | 0.00 | 3536455.01 | 4929815.99 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER TOP | 353645.50 | 0.00 | 353645.50 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV_BOT WITH REHEAT | 2.8852 | 0.0000 | 2.8852 | 1.5229 | 1348.58 | 0.67 | 4593.76 |
VAV_MID WITH REHEAT | 24.8511 | 0.0000 | 24.8511 | 15.2292 | 1412.40 | 2.15 | 4528.45 |
VAV_TOP WITH REHEAT | 2.3567 | 0.0000 | 2.3567 | 1.5229 | 1447.63 | 0.82 | 4494.55 |
CAV_BAS | 2.6298 | 0.0000 | 2.6298 | 1.2002 | 1436.27 | 0.42 | 4506.31 |
AIRLOOP DATACENTER BASEMENT | 0.3578 | 0.0000 | 0.3578 | 0.3384 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER BOT | 0.0165 | 0.0000 | 0.0165 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER MID | 0.1653 | 0.0000 | 0.1653 | 0.1563 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER TOP | 0.0165 | 0.0000 | 0.0165 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV_BOT WITH REHEAT | 0.00 | 0.00 | 1938.50 | 0.00 | 0.00 | 0.00 | 2916.36 | 0.00 | 0.00 | 0.00 |
VAV_MID WITH REHEAT | 0.00 | 0.03 | 1651.09 | 0.00 | 0.00 | 0.00 | 2942.11 | 0.00 | 0.00 | 0.00 |
VAV_TOP WITH REHEAT | 0.00 | 0.03 | 1529.29 | 0.00 | 0.00 | 0.00 | 3048.17 | 0.00 | 0.00 | 0.00 |
CAV_BAS | 0.00 | 2805.42 | 1985.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV_BOT WITH REHEAT | 0.0000 | 0.0000 | 6.1214 | 0.0000 | 0.0000 | 0.0000 | 2.3577 | 0.0000 | 0.0000 | 0.0000 |
VAV_MID WITH REHEAT | 0.0000 | 0.0000 | 48.4655 | 0.0000 | 0.0000 | 0.0000 | 23.9567 | 0.0000 | 0.0000 | 0.0000 |
VAV_TOP WITH REHEAT | 0.0000 | 0.0000 | 4.6000 | 0.0000 | 0.0000 | 0.0000 | 2.3690 | 0.0000 | 0.0000 | 0.0000 |
CAV_BAS | 0.0000 | 1.7376 | 6.3041 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BASEMENT | 0.0000 | 0.4900 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BOT | 0.0000 | 0.0226 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER MID | 0.0000 | 0.2263 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER TOP | 0.0000 | 0.0226 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:59
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 8 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1386 |
Defaulted Fields | 1179 |
Fields with Defaults | 3922 |
Autosized Fields | 333 |
Autosizable Fields | 412 |
Autocalculated Fields | 226 |
Autocalculatable Fields | 473 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 09:04:59
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 31000.55 | 370259.68 | 22-JAN-10:10 | 1925340.49 | 03-AUG-15:20 |
Electricity:Building | 17954.39 | 247233.96 | 01-JAN-08:50 | 1049209.74 | 12-DEC-08:10 |
Electricity:Zone:BASEMENT | 602.14 | 14319.77 | 01-JAN-00:10 | 28977.00 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 17954.39 | 247233.96 | 01-JAN-08:50 | 1049209.74 | 12-DEC-08:10 |
InteriorLights:Electricity | 2740.98 | 13024.70 | 01-JAN-08:50 | 255624.72 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:BASEMENT | 177.74 | 862.23 | 01-JAN-00:10 | 15519.45 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 2740.98 | 13024.70 | 01-JAN-08:50 | 255624.72 | 25-OCT-07:10 |
LightsWired:InteriorLights:Electricity | 2740.98 | 13024.70 | 01-JAN-08:50 | 255624.72 | 25-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 177.74 | 862.23 | 01-JAN-00:10 | 15519.45 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 2740.98 | 13024.70 | 01-JAN-08:50 | 255624.72 | 25-OCT-07:10 |
Electricity:Zone:CORE_BOTTOM | 480.91 | 6817.20 | 01-JAN-00:10 | 32066.15 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 159.62 | 774.34 | 01-JAN-00:10 | 13937.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 159.62 | 774.34 | 01-JAN-00:10 | 13937.56 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 4809.09 | 68171.81 | 01-JAN-00:10 | 320660.81 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 1596.25 | 7743.41 | 01-JAN-00:10 | 139375.61 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 1596.25 | 7743.41 | 01-JAN-00:10 | 139375.61 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 480.91 | 6817.18 | 01-JAN-00:10 | 32066.08 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 159.62 | 774.34 | 01-JAN-00:10 | 13937.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 159.62 | 774.34 | 01-JAN-00:10 | 13937.56 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 54.11 | 818.50 | 01-JAN-08:50 | 3890.83 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 13.77 | 59.73 | 01-JAN-08:50 | 1614.51 | 25-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 13.77 | 59.73 | 01-JAN-08:50 | 1614.51 | 25-OCT-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 34.85 | 527.47 | 01-JAN-07:50 | 2491.03 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 8.86 | 38.49 | 01-JAN-07:50 | 1024.08 | 25-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 8.86 | 38.49 | 01-JAN-07:50 | 1024.08 | 25-OCT-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 54.00 | 818.51 | 01-JAN-08:00 | 3882.56 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 13.66 | 59.73 | 01-JAN-08:00 | 1606.21 | 25-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 13.66 | 59.73 | 01-JAN-08:00 | 1606.21 | 25-OCT-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 34.85 | 527.47 | 01-JAN-08:50 | 2514.29 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 8.85 | 38.49 | 01-JAN-08:50 | 1047.35 | 25-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 8.85 | 38.49 | 01-JAN-08:50 | 1047.35 | 25-OCT-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 541.26 | 8184.99 | 01-JAN-08:50 | 38947.98 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 137.84 | 597.26 | 01-JAN-08:50 | 16184.80 | 25-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 137.84 | 597.26 | 01-JAN-08:50 | 16184.80 | 25-OCT-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 348.57 | 5274.72 | 01-JAN-07:50 | 24923.19 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 88.59 | 384.90 | 01-JAN-07:50 | 10253.73 | 25-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 88.59 | 384.90 | 01-JAN-07:50 | 10253.73 | 25-OCT-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 540.08 | 8185.12 | 01-JAN-08:00 | 38868.83 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 136.65 | 597.27 | 01-JAN-08:00 | 16105.31 | 25-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 136.65 | 597.27 | 01-JAN-08:00 | 16105.31 | 25-OCT-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 348.56 | 5274.69 | 01-JAN-08:50 | 25148.89 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 88.58 | 384.90 | 01-JAN-08:50 | 10479.53 | 25-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 88.58 | 384.90 | 01-JAN-08:50 | 10479.53 | 25-OCT-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 54.13 | 818.50 | 01-JAN-08:50 | 3894.67 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 13.78 | 59.73 | 01-JAN-08:50 | 1618.36 | 25-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 13.78 | 59.73 | 01-JAN-08:50 | 1618.36 | 25-OCT-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 34.86 | 527.47 | 01-JAN-07:50 | 2492.26 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 8.86 | 38.49 | 01-JAN-07:50 | 1025.32 | 25-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 8.86 | 38.49 | 01-JAN-07:50 | 1025.32 | 25-OCT-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 54.01 | 818.51 | 01-JAN-08:00 | 3886.76 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 13.67 | 59.73 | 01-JAN-08:00 | 1610.41 | 25-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 13.67 | 59.73 | 01-JAN-08:00 | 1610.41 | 25-OCT-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 34.86 | 527.47 | 01-JAN-08:50 | 2514.81 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 8.86 | 38.49 | 01-JAN-08:50 | 1047.88 | 25-OCT-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 8.86 | 38.49 | 01-JAN-08:50 | 1047.88 | 25-OCT-07:10 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7544.97 | 95151.24 | 01-JAN-00:10 | 384008.34 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 50.12 | 243.11 | 01-JAN-00:10 | 4375.82 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 50.12 | 243.11 | 01-JAN-00:10 | 4375.82 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 158.52 | 1971.11 | 01-JAN-00:10 | 8199.53 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 4.64 | 22.51 | 01-JAN-00:10 | 405.10 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 4.64 | 22.51 | 01-JAN-00:10 | 405.10 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1585.20 | 19711.13 | 01-JAN-00:10 | 81995.25 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 46.40 | 225.07 | 01-JAN-00:10 | 4051.03 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 46.40 | 225.07 | 01-JAN-00:10 | 4051.03 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 158.52 | 1971.11 | 01-JAN-00:10 | 8199.53 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 4.64 | 22.51 | 01-JAN-00:10 | 405.10 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 4.64 | 22.51 | 01-JAN-00:10 | 405.10 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 15213.41 | 234209.26 | 01-JAN-00:10 | 794004.08 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 15213.41 | 234209.26 | 01-JAN-00:10 | 794004.08 | 03-APR-07:10 |
MiscPlug:InteriorEquipment:Electricity | 5871.99 | 115917.86 | 01-JAN-00:10 | 320838.49 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 5871.99 | 115917.86 | 01-JAN-00:10 | 320838.49 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 321.29 | 6042.86 | 01-JAN-00:10 | 18128.59 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 321.29 | 6042.86 | 01-JAN-00:10 | 18128.59 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 3212.85 | 60428.40 | 01-JAN-00:10 | 181285.20 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 3212.85 | 60428.40 | 01-JAN-00:10 | 181285.20 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 321.28 | 6042.84 | 01-JAN-00:10 | 18128.52 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 321.28 | 6042.84 | 01-JAN-00:10 | 18128.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 40.34 | 758.77 | 01-JAN-00:10 | 2276.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 40.34 | 758.77 | 01-JAN-00:10 | 2276.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.95 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.95 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 40.34 | 758.78 | 01-JAN-00:10 | 2276.35 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 40.34 | 758.78 | 01-JAN-00:10 | 2276.35 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.94 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.94 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 403.42 | 7587.73 | 01-JAN-00:10 | 22763.18 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 403.42 | 7587.73 | 01-JAN-00:10 | 22763.18 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 259.98 | 4889.82 | 01-JAN-00:10 | 14669.46 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 259.98 | 4889.82 | 01-JAN-00:10 | 14669.46 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 403.43 | 7587.84 | 01-JAN-00:10 | 22763.53 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 403.43 | 7587.84 | 01-JAN-00:10 | 22763.53 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 259.98 | 4889.79 | 01-JAN-00:10 | 14669.36 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 259.98 | 4889.79 | 01-JAN-00:10 | 14669.36 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 40.34 | 758.77 | 01-JAN-00:10 | 2276.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 40.34 | 758.77 | 01-JAN-00:10 | 2276.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.95 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.95 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 40.34 | 758.78 | 01-JAN-00:10 | 2276.35 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 40.34 | 758.78 | 01-JAN-00:10 | 2276.35 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.94 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.94 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
Electricity:Plant | 5139.72 | 6988.29 | 05-JAN-08:00 | 448410.02 | 24-OCT-13:30 |
HeatRejection:Electricity | 1896.49 | 3256.62 | 05-JAN-08:00 | 93886.47 | 18-JAN-15:00 |
General:HeatRejection:Electricity | 1896.49 | 3256.62 | 05-JAN-08:00 | 93886.47 | 18-JAN-15:00 |
Electricity:HVAC | 5604.72 | 76371.97 | 22-JAN-08:30 | 431440.41 | 18-APR-14:30 |
ExteriorEquipment:Electricity | 1914.38 | 28294.68 | 01-JAN-00:10 | 117201.62 | 25-OCT-07:20 |
Transformer:ExteriorEquipment:Electricity | 59.77 | 1112.61 | 01-JAN-00:10 | 3723.66 | 25-OCT-07:20 |
ElectricityPurchased:Facility | 31000.55 | 370259.68 | 22-JAN-10:10 | 1925340.49 | 03-AUG-15:20 |
ElectricityPurchased:Plant | 31000.55 | 370259.68 | 22-JAN-10:10 | 1925340.49 | 03-AUG-15:20 |
Cogeneration:ElectricityPurchased | 31000.55 | 370259.68 | 22-JAN-10:10 | 1925340.49 | 03-AUG-15:20 |
General:Cogeneration:ElectricityPurchased | 31000.55 | 370259.68 | 22-JAN-10:10 | 1925340.49 | 03-AUG-15:20 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 31000.55 | 370259.68 | 22-JAN-10:10 | 1925340.49 | 03-AUG-15:20 |
ElectricityNet:Plant | 31000.55 | 370259.68 | 22-JAN-10:10 | 1925340.49 | 03-AUG-15:20 |
Cogeneration:ElectricityNet | 31000.55 | 370259.68 | 22-JAN-10:10 | 1925340.49 | 03-AUG-15:20 |
General:Cogeneration:ElectricityNet | 31000.55 | 370259.68 | 22-JAN-10:10 | 1925340.49 | 03-AUG-15:20 |
Fans:Electricity | 2510.59 | 41354.11 | 03-JAN-01:40 | 261005.24 | 18-APR-14:40 |
General:Fans:Electricity | 2510.59 | 41354.11 | 03-JAN-01:40 | 261005.24 | 18-APR-14:40 |
ExteriorLights:Electricity | 447.11 | 0.00 | 01-JAN-07:30 | 37611.08 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 447.11 | 0.00 | 01-JAN-07:30 | 37611.08 | 01-JAN-06:10 |
ElevatorLift:ExteriorEquipment:Electricity | 1848.78 | 27144.47 | 01-JAN-00:10 | 113101.96 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 5.83 | 37.60 | 01-JAN-00:10 | 376.00 | 01-JAN-07:10 |
HeatRecovery:Electricity | 60.30 | 0.00 | 01-JAN-00:10 | 5613.48 | 02-JAN-10:50 |
General:HeatRecovery:Electricity | 60.30 | 0.00 | 01-JAN-00:10 | 5613.48 | 02-JAN-10:50 |
Cooling:Electricity | 5101.82 | 30632.58 | 05-JAN-08:00 | 443337.10 | 03-AUG-15:30 |
General:Cooling:Electricity | 5101.82 | 30632.58 | 05-JAN-08:00 | 443337.10 | 03-AUG-15:30 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Humidifier:Electricity | 1.54 | 0.00 | 01-JAN-00:10 | 4283.79 | 08-MAR-22:00 |
General:Humidifier:Electricity | 1.54 | 0.00 | 01-JAN-00:10 | 4283.79 | 08-MAR-22:00 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Pumps:Electricity | 1113.93 | 3395.48 | 01-JAN-01:00 | 73611.76 | 11-OCT-14:30 |
General:Pumps:Electricity | 1113.93 | 3395.48 | 01-JAN-01:00 | 73611.76 | 11-OCT-14:30 |
WIRED_LTG_ELECTRICITY | 77.02 | 0.00 | 01-JAN-00:10 | 7183.05 | 25-OCT-07:20 |
WIRED_INT_EQUIP | 5871.99 | 115917.86 | 04-MAR-00:10 | 320838.49 | 03-APR-07:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 643.90 | 5695.87 | 01-JAN-00:10 | 495802.30 | 21-DEC-07:10 |
NaturalGas:Plant | 643.90 | 5695.87 | 01-JAN-00:10 | 495802.30 | 21-DEC-07:10 |
Heating:NaturalGas | 48.57 | 0.00 | 01-JAN-00:10 | 467400.92 | 21-DEC-07:10 |
Boiler:Heating:NaturalGas | 48.57 | 0.00 | 01-JAN-00:10 | 467400.92 | 21-DEC-07:10 |
WaterSystems:NaturalGas | 595.33 | 5695.87 | 01-JAN-00:10 | 73397.75 | 25-JAN-12:20 |
Water Heater:WaterSystems:NaturalGas | 595.33 | 5695.87 | 01-JAN-00:10 | 73397.75 | 25-JAN-12:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 27682.44 | 150405.05 | 05-JAN-08:00 | 2391599.86 | 14-AUG-13:30 |
PlantLoopCoolingDemand:HVAC | 27682.44 | 150405.05 | 05-JAN-08:00 | 2391599.86 | 14-AUG-13:30 |
CoolingCoils:PlantLoopCoolingDemand | 27682.44 | 150405.05 | 05-JAN-08:00 | 2391599.86 | 14-AUG-13:30 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 13413.05 | 0.00 | 01-JAN-00:10 | 0.00 | 13-JUN-15:10 |
Water:HVAC | 0.57 | 0.00 | 01-JAN-00:10 | 0.00 | 08-MAR-22:00 |
Humidifier:Water | 0.57 | 0.00 | 01-JAN-00:10 | 0.00 | 08-MAR-22:00 |
General:Humidifier:Water | 0.57 | 0.00 | 01-JAN-00:10 | 0.00 | 08-MAR-22:00 |
MainsWater:Facility | 13413.05 | 0.00 | 01-JAN-00:10 | 0.00 | 13-JUN-15:10 |
MainsWater:HVAC | 0.57 | 0.00 | 01-JAN-00:10 | 0.00 | 08-MAR-22:00 |
Humidifier:MainsWater | 0.57 | 0.00 | 01-JAN-00:10 | 0.00 | 08-MAR-22:00 |
General:Humidifier:MainsWater | 0.57 | 0.00 | 01-JAN-00:10 | 0.00 | 08-MAR-22:00 |
Water:Plant | 13412.48 | 0.00 | 01-JAN-00:10 | 0.00 | 13-JUN-15:10 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 13412.48 | 0.00 | 01-JAN-00:10 | 0.00 | 13-JUN-15:10 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatRejection:Water | 11132.31 | 0.00 | 01-JAN-00:10 | 0.00 | 13-JUN-15:00 |
General:HeatRejection:Water | 11132.31 | 0.00 | 01-JAN-00:10 | 0.00 | 13-JUN-15:00 |
HeatRejection:MainsWater | 11132.31 | 0.00 | 01-JAN-00:10 | 0.00 | 13-JUN-15:00 |
General:HeatRejection:MainsWater | 11132.31 | 0.00 | 01-JAN-00:10 | 0.00 | 13-JUN-15:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 93542.36 | 228686.34 | 22-JAN-06:00 | 9643553.02 | 24-OCT-13:30 |
EnergyTransfer:Building | 21096.02 | 93871.03 | 22-JAN-08:20 | 1561106.62 | 30-AUG-16:00 |
EnergyTransfer:Zone:BASEMENT | 711.74 | 0.00 | 01-JAN-00:10 | 75518.68 | 13-NOV-06:10 |
Heating:EnergyTransfer | 31.34 | 0.00 | 01-JAN-00:10 | 220247.47 | 06-FEB-06:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 4.94 | 0.00 | 01-JAN-00:10 | 23436.72 | 22-JUL-16:10 |
General:Heating:EnergyTransfer | 31.34 | 0.00 | 01-JAN-00:10 | 220247.47 | 06-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 4.94 | 0.00 | 01-JAN-00:10 | 23436.72 | 22-JUL-16:10 |
Cooling:EnergyTransfer | 21064.68 | 93358.64 | 22-JAN-08:20 | 1561106.62 | 30-AUG-16:00 |
Cooling:EnergyTransfer:Zone:BASEMENT | 706.80 | 0.00 | 01-JAN-00:10 | 75518.68 | 13-NOV-06:10 |
General:Cooling:EnergyTransfer | 21064.68 | 93358.64 | 22-JAN-08:20 | 1561106.62 | 30-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 706.80 | 0.00 | 01-JAN-00:10 | 75518.68 | 13-NOV-06:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 724.45 | 0.00 | 01-JAN-00:10 | 52916.76 | 21-AUG-09:20 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 724.45 | 0.00 | 01-JAN-00:10 | 52916.76 | 21-AUG-09:20 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 724.45 | 0.00 | 01-JAN-00:10 | 52916.76 | 21-AUG-09:20 |
EnergyTransfer:Zone:CORE_MID | 5377.21 | 0.00 | 01-JAN-00:10 | 474978.64 | 18-APR-13:50 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 5377.21 | 0.00 | 01-JAN-00:10 | 474978.64 | 18-APR-13:50 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 5377.21 | 0.00 | 01-JAN-00:10 | 474978.64 | 18-APR-13:50 |
EnergyTransfer:Zone:CORE_TOP | 540.84 | 0.00 | 01-JAN-00:10 | 50160.73 | 18-APR-14:40 |
Heating:EnergyTransfer:Zone:CORE_TOP | 0.22 | 0.00 | 01-JAN-00:10 | 34926.64 | 06-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 0.22 | 0.00 | 01-JAN-00:10 | 34926.64 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 540.62 | 0.00 | 01-JAN-00:10 | 50160.73 | 18-APR-14:40 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 540.62 | 0.00 | 01-JAN-00:10 | 50160.73 | 18-APR-14:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 101.84 | 0.00 | 01-JAN-00:10 | 11201.63 | 21-AUG-14:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 101.84 | 0.00 | 01-JAN-00:10 | 11201.63 | 21-AUG-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 101.84 | 0.00 | 01-JAN-00:10 | 11201.63 | 21-AUG-14:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 79.20 | 0.00 | 01-JAN-00:10 | 10281.61 | 11-SEP-09:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 79.20 | 0.00 | 01-JAN-00:10 | 10281.61 | 11-SEP-09:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 79.20 | 0.00 | 01-JAN-00:10 | 10281.61 | 11-SEP-09:20 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 131.65 | 0.00 | 01-JAN-00:10 | 15887.02 | 06-NOV-13:40 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 131.65 | 0.00 | 01-JAN-00:10 | 15887.02 | 06-NOV-13:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 131.65 | 0.00 | 01-JAN-00:10 | 15887.02 | 06-NOV-13:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 122.40 | 0.00 | 01-JAN-00:10 | 15177.23 | 30-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 122.40 | 0.00 | 01-JAN-00:10 | 15177.23 | 30-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 122.40 | 0.00 | 01-JAN-00:10 | 15177.23 | 30-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 784.04 | 0.00 | 01-JAN-00:10 | 98148.33 | 21-AUG-14:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 2.63 | 0.00 | 01-JAN-00:10 | 54126.40 | 06-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 2.63 | 0.00 | 01-JAN-00:10 | 54126.40 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 781.40 | 0.00 | 01-JAN-00:10 | 98148.33 | 21-AUG-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 781.40 | 0.00 | 01-JAN-00:10 | 98148.33 | 21-AUG-14:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 689.28 | 0.00 | 01-JAN-00:10 | 103775.36 | 03-MAY-09:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 1.07 | 0.00 | 01-JAN-00:10 | 30977.83 | 06-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 1.07 | 0.00 | 01-JAN-00:10 | 30977.83 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 688.21 | 0.00 | 01-JAN-00:10 | 103775.36 | 03-MAY-09:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 688.21 | 0.00 | 01-JAN-00:10 | 103775.36 | 03-MAY-09:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1102.65 | 0.00 | 01-JAN-00:10 | 152819.53 | 06-NOV-13:50 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.34 | 0.00 | 01-JAN-00:10 | 30241.18 | 06-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.34 | 0.00 | 01-JAN-00:10 | 30241.18 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1102.31 | 0.00 | 01-JAN-00:10 | 152819.53 | 06-NOV-13:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1102.31 | 0.00 | 01-JAN-00:10 | 152819.53 | 06-NOV-13:50 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 738.44 | 0.00 | 01-JAN-00:10 | 119556.50 | 30-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.41 | 0.00 | 01-JAN-00:10 | 23735.83 | 06-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.41 | 0.00 | 01-JAN-00:10 | 23735.83 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 738.03 | 0.00 | 01-JAN-00:10 | 119556.50 | 30-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 738.03 | 0.00 | 01-JAN-00:10 | 119556.50 | 30-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 82.72 | 0.00 | 01-JAN-00:10 | 12331.18 | 06-FEB-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 2.42 | 0.00 | 01-JAN-00:10 | 12331.18 | 06-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 2.42 | 0.00 | 01-JAN-00:10 | 12331.18 | 06-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 80.31 | 0.00 | 01-JAN-00:10 | 10769.58 | 21-AUG-14:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 80.31 | 0.00 | 01-JAN-00:10 | 10769.58 | 21-AUG-14:40 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 72.86 | 0.00 | 01-JAN-00:10 | 10632.88 | 03-MAY-09:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 1.02 | 0.00 | 01-JAN-00:10 | 8759.23 | 06-FEB-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 1.02 | 0.00 | 01-JAN-00:10 | 8759.23 | 06-FEB-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 71.85 | 0.00 | 01-JAN-00:10 | 10632.88 | 03-MAY-09:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 71.85 | 0.00 | 01-JAN-00:10 | 10632.88 | 03-MAY-09:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 112.12 | 0.00 | 01-JAN-00:10 | 16629.89 | 06-NOV-14:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.83 | 0.00 | 01-JAN-00:10 | 9884.04 | 06-FEB-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.83 | 0.00 | 01-JAN-00:10 | 9884.04 | 06-FEB-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 111.29 | 0.00 | 01-JAN-00:10 | 16629.89 | 06-NOV-14:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 111.29 | 0.00 | 01-JAN-00:10 | 16629.89 | 06-NOV-14:20 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 76.80 | 0.00 | 01-JAN-00:10 | 12720.95 | 30-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.68 | 0.00 | 01-JAN-00:10 | 6342.86 | 06-FEB-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.68 | 0.00 | 01-JAN-00:10 | 6342.86 | 06-FEB-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 76.12 | 0.00 | 01-JAN-00:10 | 12720.95 | 30-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 76.12 | 0.00 | 01-JAN-00:10 | 12720.95 | 30-AUG-16:00 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 93.54 | 0.00 | 01-JAN-00:10 | 10272.89 | 10-OCT-05:20 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 1.00 | 0.00 | 01-JAN-00:10 | 4150.48 | 31-DEC-11:10 |
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 1.00 | 0.00 | 01-JAN-00:10 | 4150.48 | 31-DEC-11:10 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 92.54 | 0.00 | 01-JAN-00:10 | 10272.89 | 10-OCT-05:20 |
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 92.54 | 0.00 | 01-JAN-00:10 | 10272.89 | 10-OCT-05:20 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 681.61 | 0.00 | 01-JAN-00:10 | 81198.10 | 22-MAY-05:20 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 8.90 | 0.00 | 01-JAN-00:10 | 28591.24 | 20-FEB-13:30 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 8.90 | 0.00 | 01-JAN-00:10 | 28591.24 | 20-FEB-13:30 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 672.71 | 0.00 | 01-JAN-00:10 | 81198.10 | 22-MAY-05:20 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 672.71 | 0.00 | 01-JAN-00:10 | 81198.10 | 22-MAY-05:20 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 112.66 | 0.00 | 01-JAN-00:10 | 20443.99 | 07-JUL-14:30 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 6.80 | 0.00 | 01-JAN-00:10 | 13965.29 | 06-FEB-06:20 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 6.80 | 0.00 | 01-JAN-00:10 | 13965.29 | 06-FEB-06:20 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 105.86 | 0.00 | 01-JAN-00:10 | 20443.99 | 07-JUL-14:30 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 105.86 | 0.00 | 01-JAN-00:10 | 20443.99 | 07-JUL-14:30 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 142.25 | 1046.44 | 05-JAN-08:00 | 7906.36 | 16-APR-18:10 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 142.25 | 1046.44 | 05-JAN-08:00 | 7906.36 | 16-APR-18:10 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 142.25 | 1046.44 | 05-JAN-08:00 | 7906.36 | 16-APR-18:10 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1314.92 | 3801.76 | 10-JAN-06:30 | 74571.13 | 16-APR-18:10 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1314.92 | 3801.76 | 10-JAN-06:30 | 74571.13 | 16-APR-18:10 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1314.92 | 3801.76 | 10-JAN-06:30 | 74571.13 | 16-APR-18:10 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 128.44 | 2.61 | 10-JAN-09:30 | 7640.94 | 23-APR-18:10 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.09 | 0.00 | 01-JAN-00:10 | 520.41 | 22-JAN-06:30 |
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.09 | 0.00 | 01-JAN-00:10 | 520.41 | 22-JAN-06:30 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 128.35 | 0.00 | 04-JAN-04:40 | 7640.94 | 23-APR-18:10 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 128.35 | 0.00 | 04-JAN-04:40 | 7640.94 | 23-APR-18:10 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7174.36 | 88095.99 | 22-JAN-06:00 | 369889.36 | 09-AUG-21:10 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7174.36 | 88095.99 | 22-JAN-06:00 | 369889.36 | 09-AUG-21:10 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7174.36 | 88095.99 | 22-JAN-06:00 | 369889.36 | 09-AUG-21:10 |
PlantLoopHeatingDemand:Facility | 355.29 | 0.00 | 01-JAN-00:10 | 372655.06 | 21-DEC-07:10 |
PlantLoopHeatingDemand:Plant | 321.87 | 0.00 | 01-JAN-00:10 | 40639.77 | 23-JAN-12:20 |
WaterSystems:PlantLoopHeatingDemand | 321.87 | 0.00 | 01-JAN-00:10 | 40639.77 | 23-JAN-12:20 |
General:WaterSystems:PlantLoopHeatingDemand | 321.87 | 0.00 | 01-JAN-00:10 | 40639.77 | 23-JAN-12:20 |
EnergyTransfer:HVAC | 27008.98 | 131497.36 | 27-JAN-22:00 | 2665135.32 | 07-AUG-13:00 |
HeatingCoils:EnergyTransfer | 33.42 | 0.00 | 01-JAN-00:10 | 359420.23 | 21-DEC-07:10 |
PlantLoopHeatingDemand:HVAC | 33.42 | 0.00 | 01-JAN-00:10 | 359420.23 | 21-DEC-07:10 |
HeatingCoils:PlantLoopHeatingDemand | 33.42 | 0.00 | 01-JAN-00:10 | 359420.23 | 21-DEC-07:10 |
CoolingCoils:EnergyTransfer | 24709.92 | 119772.48 | 05-JAN-08:00 | 2229849.36 | 07-AUG-14:40 |
HeatRecoveryForHeating:EnergyTransfer | 32.93 | 0.00 | 01-JAN-00:10 | 240675.94 | 20-DEC-08:00 |
HeatRecoveryForCooling:EnergyTransfer | 2232.72 | 0.00 | 01-JAN-00:10 | 599444.45 | 22-JUL-16:00 |
EnergyTransfer:Plant | 45437.36 | 0.00 | 01-JAN-00:10 | 5791331.88 | 11-OCT-14:30 |
LoopToLoop:EnergyTransfer | 15476.02 | 0.00 | 01-JAN-00:10 | 1896461.94 | 22-MAY-05:10 |
WaterSystems:EnergyTransfer | 321.87 | 0.00 | 01-JAN-00:10 | 40639.77 | 23-JAN-12:20 |
WaterUse:WaterSystems:EnergyTransfer | 321.87 | 0.00 | 01-JAN-00:10 | 40639.77 | 23-JAN-12:20 |
Boilers:EnergyTransfer | 32.93 | 0.00 | 01-JAN-00:10 | 387855.82 | 21-DEC-07:10 |
Chillers:EnergyTransfer | 13738.62 | 0.00 | 01-JAN-00:10 | 1838412.30 | 11-OCT-14:30 |
HeatRejection:EnergyTransfer | 15867.92 | 0.00 | 01-JAN-00:10 | 2108853.97 | 24-OCT-13:30 |
General:HeatRejection:EnergyTransfer | 15867.92 | 0.00 | 01-JAN-00:10 | 2108853.97 | 24-OCT-13:30 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:59
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 4.940 | -706.802 | 0.000 | 0.000 | 92.680 | 177.742 | 424.397 | 0.000 | 0.000 | 0.000 | 7.043 | 0.000 | 0.000 | 0.000 | 0.000 | -0.001 |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -724.446 | 0.000 | 0.000 | 83.427 | 159.625 | 321.286 | 0.000 | 0.000 | 0.000 | 160.108 | 0.000 | 0.000 | 0.000 | 0.000 | -0.003 |
CORE_MID | 0.000 | 0.000 | 0.000 | -5377.198 | 0.000 | 0.000 | 835.911 | 1596.246 | 3212.845 | 0.000 | 0.000 | 0.000 | 0.031 | 0.000 | 0.000 | 0.000 | 0.000 | -267.804 |
CORE_TOP | 0.000 | 0.000 | 0.221 | -540.619 | 0.000 | 0.000 | 84.325 | 159.625 | 321.285 | 0.000 | 0.000 | 0.000 | 0.013 | 0.000 | 0.000 | 0.000 | 0.000 | -24.837 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.000 | -101.837 | 0.000 | 0.000 | 10.542 | 13.768 | 40.342 | 31.360 | 0.000 | 0.383 | 32.655 | 0.000 | -25.390 | 0.000 | -1.824 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.000 | -79.199 | 0.000 | 0.000 | 6.782 | 8.855 | 25.998 | 45.647 | 0.000 | 0.259 | 8.234 | 0.000 | -15.368 | 0.000 | -1.207 | -0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 0.000 | -131.646 | 0.000 | 0.000 | 10.491 | 13.656 | 40.343 | 78.636 | 0.000 | 0.364 | 14.232 | 0.000 | -24.122 | 0.000 | -1.953 | -0.001 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.000 | -122.405 | 0.000 | 0.000 | 6.749 | 8.854 | 25.998 | 43.553 | 0.000 | 0.225 | 57.874 | 0.000 | -19.399 | 0.000 | -1.448 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 2.634 | -781.391 | 0.000 | 0.000 | 107.319 | 137.840 | 403.423 | 320.990 | 0.000 | 8.624 | 70.130 | 0.000 | -231.084 | 0.000 | -38.484 | 0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 1.068 | -688.198 | 0.000 | 0.000 | 50.318 | 88.585 | 259.981 | 454.433 | 0.000 | 5.372 | 4.761 | 0.000 | -148.938 | 0.000 | -27.382 | -0.000 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 0.336 | -1102.292 | 0.000 | 0.000 | 105.267 | 136.651 | 403.429 | 784.014 | 0.000 | 8.023 | 0.031 | 0.000 | -235.956 | 0.000 | -45.104 | -54.368 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 0.414 | -738.021 | 0.000 | 0.000 | 68.627 | 88.577 | 259.979 | 445.742 | 0.000 | 5.285 | 63.651 | 0.000 | -165.233 | 0.000 | -29.021 | -0.000 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 2.416 | -80.305 | 0.000 | 0.000 | 10.849 | 13.784 | 40.342 | 31.962 | 0.000 | 1.001 | 6.261 | 0.000 | -21.869 | 0.000 | -4.442 | -0.000 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 1.016 | -71.844 | 0.000 | 0.000 | 6.902 | 8.859 | 25.998 | 45.364 | 0.000 | 0.630 | 0.525 | 0.000 | -14.259 | 0.000 | -3.190 | -0.001 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 0.829 | -111.288 | 0.000 | 0.000 | 10.598 | 13.665 | 40.343 | 78.172 | 0.000 | 0.937 | 0.002 | 0.000 | -22.732 | 0.000 | -5.313 | -5.212 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 0.680 | -76.118 | 0.000 | 0.000 | 6.934 | 8.858 | 25.998 | 44.416 | 0.000 | 0.632 | 7.838 | 0.000 | -15.831 | 0.000 | -3.406 | -0.001 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.000 | -142.250 | 0.000 | 0.000 | 0.948 | 4.640 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -17.218 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 0.000 | -1314.926 | 0.000 | 0.000 | 9.482 | 46.396 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -279.757 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 0.087 | -128.349 | 0.000 | 0.000 | 0.949 | 4.640 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -31.207 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | 0.000 | 0.000 | -7174.374 | 0.000 | 0.000 | 20.106 | 50.116 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -390.704 |
GROUNDFLOOR_PLENUM | 1.004 | -92.536 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.675 | 94.896 | 0.000 | 0.000 | 0.000 | -4.038 | 0.000 |
MIDFLOOR_PLENUM | 8.899 | -672.704 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 12.200 | 720.684 | 0.000 | 0.000 | 0.000 | -69.079 | 0.000 |
TOPFLOOR_PLENUM | 6.799 | -105.859 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.066 | 105.261 | 0.000 | 0.000 | 0.000 | -7.266 | -0.001 |
Total Facility | 16.702 | -871.100 | 14.642 | -20193.508 | 0.000 | 0.000 | 1529.205 | 2740.978 | 15213.411 | 2404.288 | 0.000 | 45.676 | 1354.229 | 0.000 | -940.182 | 0.000 | -243.159 | -1071.116 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 20-MAR-03:02 | 0.00 | 0.00 | 0.00 | -110471.10 | 0.00 | 0.00 | 0.00 | 862.23 | 13457.54 | 0.00 | 0.00 | 0.00 | 96151.33 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 18-DEC-04:02 | 0.00 | 0.00 | 0.00 | -92273.06 | 0.00 | 0.00 | 0.00 | 774.34 | 8057.15 | 0.00 | 0.00 | 0.00 | 83441.57 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 01-MAY-03:02 | 0.00 | 0.00 | 0.00 | -805825.92 | 0.00 | 0.00 | 0.00 | 7743.41 | 80571.20 | 0.00 | 0.00 | 0.00 | 717511.31 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 01-MAY-03:02 | 0.00 | 0.00 | 0.00 | -80133.20 | 0.00 | 0.00 | 0.00 | 774.34 | 8057.12 | 0.00 | 0.00 | 0.00 | 71301.74 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 21-AUG-03:02 | 0.00 | 0.00 | 0.00 | -14199.66 | 0.00 | 0.00 | 0.00 | 97.23 | 1011.70 | 0.00 | 0.00 | 10.13 | 13552.06 | 0.00 | -471.45 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 07-MAY-09:22 | 0.00 | 0.00 | 0.00 | -16840.93 | 0.00 | 0.00 | 24.23 | 38.49 | 488.98 | 9992.70 | 0.00 | 31.43 | 6265.10 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 11-NOV-13:22 | 0.00 | 0.00 | 0.00 | -20999.58 | 0.00 | 0.00 | 35.60 | 59.73 | 758.78 | 15348.75 | 0.00 | 0.00 | 4859.77 | 0.00 | -0.00 | 0.00 | -63.05 | 0.00 |
PERIMETER_BOT_ZN_4 | 03-SEP-15:51 | 0.00 | 0.00 | 0.00 | -22562.17 | 0.00 | 0.00 | 21.44 | 38.49 | 488.98 | 10689.44 | 0.00 | 80.93 | 11242.89 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 25-JUN-16:31 | 0.00 | 0.00 | 0.00 | -144609.24 | 0.00 | 0.00 | 429.99 | 597.26 | 7587.73 | 42183.33 | 0.00 | 1128.34 | 92682.60 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 29-MAY-08:42 | 0.00 | 0.00 | 0.00 | -180212.66 | 0.00 | 0.00 | 224.81 | 384.90 | 4889.82 | 109977.31 | 0.00 | 0.00 | 64836.59 | 0.00 | -0.00 | 0.00 | -100.77 | 0.00 |
PERIMETER_MID_ZN_1 | 01-JAN-14:11 | 0.00 | 0.00 | 0.00 | -206661.78 | 0.00 | 0.00 | 331.83 | 597.27 | 7587.84 | 154558.06 | 0.00 | 0.00 | 44575.45 | 0.00 | -0.00 | 0.00 | -988.69 | 0.00 |
PERIMETER_MID_ZN_4 | 11-JUN-17:11 | 0.00 | 0.00 | 0.00 | -191349.64 | 0.00 | 0.00 | 0.00 | 384.90 | 4889.79 | 89581.99 | 0.00 | 1127.91 | 95365.06 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 25-JUN-16:31 | 0.00 | 0.00 | 0.00 | -17180.45 | 0.00 | 0.00 | 40.43 | 59.73 | 758.77 | 4069.28 | 0.00 | 125.07 | 12127.17 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 29-MAY-08:42 | 0.00 | 0.00 | 0.00 | -18540.35 | 0.00 | 0.00 | 22.05 | 38.49 | 488.98 | 10935.72 | 0.00 | 0.00 | 7071.33 | 0.00 | -0.00 | 0.00 | -16.23 | 0.00 |
PERIMETER_TOP_ZN_1 | 01-JAN-15:02 | 0.00 | 0.00 | 0.00 | -22569.38 | 0.00 | 0.00 | 33.85 | 59.73 | 758.78 | 12285.57 | 0.00 | 0.00 | 9594.41 | 0.00 | -0.00 | 0.00 | -162.96 | 0.00 |
PERIMETER_TOP_ZN_4 | 29-MAY-16:01 | 0.00 | 0.00 | 0.00 | -21246.60 | 0.00 | 0.00 | 20.06 | 38.49 | 488.98 | 11035.28 | 0.00 | 103.63 | 9560.16 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 16-APR-18:02 | 0.00 | 0.00 | 0.00 | -7906.33 | 0.00 | 0.00 | 0.00 | 22.51 | 7794.42 | 0.00 | 0.00 | 0.00 | 89.40 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 16-APR-18:02 | 0.00 | 0.00 | 0.00 | -74570.87 | 0.00 | 0.00 | 0.00 | 225.07 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -3598.42 |
DATACENTER_TOP_ZN_6 | 23-APR-18:03 | 0.00 | 0.00 | 0.00 | -7640.92 | 0.00 | 0.00 | 0.00 | 22.51 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -176.01 |
DATACENTER_BASEMENT_ZN_6 | 09-AUG-21:13 | 0.00 | 0.00 | 0.00 | -371121.41 | 0.00 | 0.00 | 114.68 | 486.22 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -9112.02 |
GROUNDFLOOR_PLENUM | 10-OCT-05:15 | 0.00 | -14016.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14077.56 | 0.00 | -0.00 | 0.00 | -61.37 | 0.00 |
MIDFLOOR_PLENUM | 22-MAY-05:13 | 0.00 | -127032.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 309.53 | 126723.14 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 07-JUL-14:30 | 0.00 | -20443.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.49 | 20330.55 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 21-AUG-05:02 | 0.00 | -49783.94 | 0.00 | -1909826.22 | 0.00 | 0.00 | 15652.28 | 29009.37 | 623236.89 | 0.00 | 0.00 | 330.32 | 1303994.63 | 0.00 | -12613.33 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 22-JUL-16:02 | 0.00 | 0.00 | 25013.68 | 0.00 | 0.00 | 0.00 | 520.12 | 862.23 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -39853.57 |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 06-FEB-05:01 | 0.00 | 0.00 | 58718.54 | 0.00 | 0.00 | 0.00 | 0.00 | 1548.68 | 8057.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -68324.34 |
PERIMETER_BOT_ZN_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 06-FEB-05:01 | 0.00 | 0.00 | 108109.81 | 0.00 | 0.00 | 0.00 | 0.00 | 1944.52 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -33808.85 | 0.00 | -4628.60 | -81733.86 |
PERIMETER_MID_ZN_2 | 06-FEB-05:01 | 0.00 | 0.00 | 94711.65 | 0.00 | 0.00 | 0.00 | 0.00 | 1253.13 | 6519.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -23321.03 | 0.00 | -3219.58 | -75943.93 |
PERIMETER_MID_ZN_1 | 21-DEC-06:01 | 0.00 | 0.00 | 120985.99 | 0.00 | 0.00 | 0.00 | 1461.00 | 1944.57 | 10117.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -42986.85 | 0.00 | -2358.10 | -89163.73 |
PERIMETER_MID_ZN_4 | 21-DEC-06:01 | 0.00 | 0.00 | 83051.21 | 0.00 | 0.00 | 0.00 | 941.49 | 1253.13 | 6519.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -28369.19 | 0.00 | -1571.37 | -61824.98 |
PERIMETER_TOP_ZN_3 | 05-FEB-07:43 | 0.00 | 0.00 | 14470.80 | 0.00 | 0.00 | 0.00 | 88.34 | 86.93 | 758.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3782.50 | 0.00 | -2221.26 | -9401.08 |
PERIMETER_TOP_ZN_2 | 06-FEB-04:01 | 0.00 | 0.00 | 13460.87 | 0.00 | 0.00 | 0.00 | 0.00 | 62.66 | 651.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1827.58 | 0.00 | -349.47 | -11998.46 |
PERIMETER_TOP_ZN_1 | 06-FEB-04:01 | 0.00 | 0.00 | 15923.27 | 0.00 | 0.00 | 0.00 | 0.00 | 97.23 | 1011.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2961.61 | 0.00 | -570.76 | -13499.85 |
PERIMETER_TOP_ZN_4 | 06-FEB-04:01 | 0.00 | 0.00 | 12850.81 | 0.00 | 0.00 | 0.00 | 0.00 | 62.66 | 651.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2029.68 | 0.00 | -384.93 | -11150.84 |
DATACENTER_BOT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 10-JAN-04:45 | 0.00 | 0.00 | 523.18 | 0.00 | 0.00 | 0.00 | 0.00 | 22.51 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2494.30 |
DATACENTER_BASEMENT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 21-DEC-05:01 | 10890.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -816.72 | -10073.94 |
MIDFLOOR_PLENUM | 22-MAY-03:02 | 76717.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -220.14 | -76497.70 |
TOPFLOOR_PLENUM | 09-NOV-06:02 | 17407.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -483.32 | -16924.09 |
Total Facility | 06-FEB-06:01 | -571785.36 | 553093.32 | 499569.19 | -553093.32 | 0.00 | 0.00 | 19239.26 | 29009.37 | 386654.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -144741.17 | 0.00 | -7038.43 | -210906.96 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:59
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 9.7720 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 8.9417 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 91.1116 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 82.7191 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 9.4128 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 8.9357 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 5.4789 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 5.4789 | 0.2191 | 1.0000 | Not calculated | 1.2002 | 0.2191 | ||
AIRLOOP DATACENTER BASEMENT | 21.3329 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 21.3331 | 0.0159 | 1.0000 | Not calculated | 0.3384 | 0.0159 | ||
AIRLOOP DATACENTER BOT | 0.4657 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4657 | 0.0336 | 1.0000 | Not calculated | 0.0156 | 0.0336 | ||
AIRLOOP DATACENTER MID | 4.4256 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.4256 | 0.0353 | 1.0000 | Not calculated | 0.1563 | 0.0353 | ||
AIRLOOP DATACENTER TOP | 0.4514 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4514 | 0.0346 | 1.0000 | Not calculated | 0.0156 | 0.0346 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 4.8860 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.7887 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 45.5558 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 26.9693 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 4.7064 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.7739 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 5.4789 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 5.4789 | 1.0000 | 1.0000 | Not calculated | 1.2002 | 0.2191 | ||
AIRLOOP DATACENTER BASEMENT | 21.3329 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 21.3329 | 1.0000 | 1.0000 | Not calculated | 0.3384 | 0.0159 | ||
AIRLOOP DATACENTER BOT | 0.4657 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4657 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0336 | ||
AIRLOOP DATACENTER MID | 4.4256 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.4256 | 1.0000 | 1.0000 | Not calculated | 0.1563 | 0.0353 | ||
AIRLOOP DATACENTER TOP | 0.4514 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4514 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0346 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.000000 | 149.6021 | 0.000432 | 2779.43 | 1.2002 | 1.0000 | 1.2002 | 1.000 | 1.2002 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.000000 | 19.4861 | 0.000432 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.1814 | 0.000432 | 783.68 | 0.3384 | 1.0000 | 0.3384 | 1.000 | 0.3384 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
CAV_BAS | 0.000000 | 149.60 | 0.000432 | 2779.4266 | 1.2002 | 1.2002 | 1.2002 |
AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.18 | 0.000432 | 783.6794 | 0.3384 | 0.3384 | 0.3384 |
AIRLOOP DATACENTER BOT | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AIRLOOP DATACENTER MID | 0.000000 | 19.49 | 0.000432 | 362.0274 | 0.1563 | 0.1563 | 0.1563 |
AIRLOOP DATACENTER TOP | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.4789 | 5.4789 | 5.4789 | No | 1.2002 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.6390 | 5.6390 | 1.8891 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 52.7979 | 52.7979 | 18.4265 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.2302 | 5.2302 | 1.8881 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9083 | 0.9083 | 0.2371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9292 | 0.9292 | 0.1858 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0994 | 1.0994 | 0.2375 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1961 | 1.1961 | 0.2392 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 8.4237 | 8.4237 | 2.3165 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 9.4880 | 9.4880 | 1.8976 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 10.3478 | 10.3478 | 2.3179 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 10.0541 | 10.0541 | 2.0108 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9675 | 0.9675 | 0.2370 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9693 | 0.9693 | 0.1939 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1553 | 1.1553 | 0.2368 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0905 | 1.0905 | 0.2181 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4657 | 0.4657 | 0.4657 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.4256 | 4.4256 | 4.4256 | No | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4514 | 0.4514 | 0.4514 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 21.3329 | 21.3329 | 21.3329 | No | 0.3384 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 9.7720 | 8.9417 | 9.7720 | 2.7887 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 91.1116 | 82.7191 | 91.1116 | 26.9693 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 9.4128 | 8.9357 | 9.4128 | 2.7739 | 0.0000 | 1.0000 |
CAV_BAS | 5.4789 | 5.4789 | 5.4789 | 5.4789 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.3329 | 21.3331 | 21.3329 | 21.3329 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4657 | 0.4657 | 0.4657 | 0.4657 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.4256 | 4.4256 | 4.4256 | 4.4256 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4514 | 0.4514 | 0.4514 | 0.4514 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.4789 | 5.4789 | 5.4789 | No | 1.2002 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.8195 | 2.8195 | 1.8891 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 26.3990 | 26.3990 | 18.4265 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.6151 | 2.6151 | 1.8881 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4541 | 0.4541 | 0.2371 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4646 | 0.4646 | 0.1858 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5497 | 0.5497 | 0.2375 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5981 | 0.5981 | 0.2392 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.2119 | 4.2119 | 2.3165 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.7440 | 4.7440 | 1.8976 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.1739 | 5.1739 | 2.3179 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.0270 | 5.0270 | 2.0108 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4837 | 0.4837 | 0.2370 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4846 | 0.4846 | 0.1939 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5777 | 0.5777 | 0.2368 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5453 | 0.5453 | 0.2181 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4657 | 0.4657 | 0.4657 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.4256 | 4.4256 | 4.4256 | No | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4514 | 0.4514 | 0.4514 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 21.3329 | 21.3329 | 21.3329 | No | 0.3384 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 4.8860 | 2.7887 | 2.7887 | 2.7887 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 45.5558 | 26.9693 | 26.9693 | 26.9693 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 4.7064 | 2.7739 | 2.7739 | 2.7739 | 0.0000 | 1.0000 |
CAV_BAS | 5.4789 | 5.4789 | 5.4789 | 5.4789 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.3329 | 21.3329 | 21.3329 | 21.3329 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4657 | 0.4657 | 0.4657 | 0.4657 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.4256 | 4.4256 | 4.4256 | 4.4256 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4514 | 0.4514 | 0.4514 | 0.4514 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:59
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Tampa-MacDill AFB FL USA TMY3 WMO#=747880 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 113.98 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 1.50 |
Number of hours cooling loads not met | 754.67 |
Number of hours not met | 756.17 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 48.57 | 467400.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 5101.82 | 443337.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 2740.98 | 255624.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 447.11 | 37611.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5871.99 | 320838.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 59.77 | 3723.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 1848.78 | 113101.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 5.83 | 376.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 2510.59 | 261005.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 1113.93 | 73611.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 1896.49 | 93886.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- General | 1.54 | 4283.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 60.30 | 5613.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 595.33 | 73397.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 15213.41 | 31000.55 |
Natural Gas | 0.00 | 643.90 |
Additional | 0.00 | 0.00 |
Total | 15213.41 | 31644.45 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 59.17 |
Space Heating | 0.00 |
Space Cooling | 110.14 |
Fans (All) | 54.20 |
Service Water Heating | 0.00 |
Receptacle Equipment | 328.44 |
Miscellaneous (All) | 669.26 |
Subtotal | 669.26 |
Natural Gas [MJ/m2] | |
Space Heating | 1.05 |
Service Water Heating | 12.85 |
Miscellaneous (All) | 13.90 |
Subtotal | 13.90 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 8.66 |
Space Heating | 0.15 |
Space Cooling | 16.12 |
Fans (All) | 7.93 |
Service Water Heating | 1.88 |
Receptacle Equipment | 48.08 |
Miscellaneous | 17.17 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2393. | 8760. |
LTG_SCH_DATACENTER | 2921. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4487. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 1565. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:59
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 7478.83 | 1281.17 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8695.83 | 64.17 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8759.50 | 0.50 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8754.17 | 5.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8707.50 | 52.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8621.67 | 138.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8537.00 | 223.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 7562.00 | 1198.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8564.00 | 196.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8266.00 | 494.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8238.33 | 521.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 7811.50 | 948.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8427.83 | 332.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8139.50 | 620.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8109.17 | 650.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 7817.83 | 942.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 3499.33 | 5260.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 3607.83 | 5152.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 3559.67 | 5200.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 2825.83 | 5934.17 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8444.00 | 316.00 | 0.00 | 0.00 | 0.00 |
Min | 2825.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 5934.17 | 0.00 | 0.00 | 0.00 |
Average | 7475.97 | 1284.03 | 0.00 | 0.00 | 0.00 |
Sum | 171947.33 | 29532.67 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 364798.67 | 3817.33 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330727.00 | 86.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330809.00 | 4.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 525.00 | 1743.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 523.50 | 1744.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 516.00 | 1752.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 24521.33 | 78873.67 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 364798.67 | 78873.67 | 0.00 | 0.00 | 0.00 |
Average | 76507.93 | 3826.98 | 0.00 | 0.00 | 0.00 |
Sum | 1759682.50 | 88020.50 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 4144.67 | 4615.33 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 7146.83 | 1613.17 | 0.00 | 0.00 | 0.00 |
CORE_MID | 6812.83 | 1947.17 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 6686.33 | 2073.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 6520.17 | 2239.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 6874.33 | 1885.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 6235.83 | 2524.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 5875.67 | 2884.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 6385.33 | 2374.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 6279.33 | 2480.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 6035.00 | 2725.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 6111.50 | 2648.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 6395.00 | 2365.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 6300.50 | 2459.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 6057.17 | 2702.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 6155.83 | 2604.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 5749.33 | 3010.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 5757.17 | 3002.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 5732.00 | 3028.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 5241.33 | 3518.67 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 5936.67 | 2823.33 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 5647.50 | 3112.50 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 4450.83 | 4309.17 | 0.00 | 0.00 | 0.00 |
Min | 4144.67 | 1613.17 | 0.00 | 0.00 | 0.00 |
Max | 7146.83 | 4615.33 | 0.00 | 0.00 | 0.00 |
Average | 6023.09 | 2736.91 | 0.00 | 0.00 | 0.00 |
Sum | 138531.17 | 62948.83 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 287829.83 | 80786.17 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 327853.00 | 2960.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 327707.00 | 3106.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 325783.00 | 5030.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38894.83 | 30.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18340.50 | 13.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38902.50 | 22.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24900.67 | 8.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38851.50 | 73.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24889.83 | 19.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38867.50 | 57.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24897.00 | 12.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 726.67 | 1541.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 722.67 | 1545.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 712.83 | 1555.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 37014.83 | 66380.17 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 327853.00 | 80786.17 | 0.00 | 0.00 | 0.00 |
Average | 73241.83 | 7093.08 | 0.00 | 0.00 | 0.00 |
Sum | 1684562.17 | 163140.83 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:59
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:59
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 4570.43 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 18354.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 38925.00 | 0.00 |
Average | 0.00 | 0.00 | 16367.35 | 0.00 |
Sum | 0.00 | 0.00 | 376449.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018
For: Environment
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Environment
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2A
For: Environment
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_TAMPA
For: Environment
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.572 |
February | 15.490 |
March | 17.074 |
April | 21.231 |
May | 26.899 |
June | 27.606 |
July | 27.937 |
August | 27.434 |
September | 26.232 |
October | 24.234 |
November | 18.911 |
December | 15.677 |
Annual Sum or Average | 21.892 |
Minimum of Months | 13.572 |
Maximum of Months | 27.937 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.569420E+11 | 106684.89 | 23-JAN-04:03 | 8.00 | 6.50 | 0.566824E+10 | 7499.42 | 12-JAN-10:09 | 8.00 | 6.50 |
February | 0.497781E+11 | 109574.77 | 13-FEB-04:03 | 6.38 | 2.53 | 0.514041E+10 | 7499.11 | 09-FEB-10:00 | 6.38 | 2.53 |
March | 0.571125E+11 | 110548.58 | 20-MAR-03:02 | 12.55 | 8.37 | 0.613292E+10 | 7499.70 | 23-MAR-09:20 | 16.97 | 14.65 |
April | 0.526144E+11 | 106601.17 | 10-APR-03:02 | 13.30 | 9.00 | 0.544938E+10 | 7499.32 | 12-APR-09:20 | 21.23 | 16.81 |
May | 0.566859E+11 | 78461.54 | 30-MAY-03:02 | 25.60 | 23.91 | 0.590206E+10 | 7498.83 | 26-MAY-09:20 | 25.60 | 23.91 |
June | 0.568225E+11 | 79393.90 | 07-JUN-03:02 | 21.10 | 18.25 | 0.588158E+10 | 7498.83 | 29-JUN-09:20 | 29.63 | 25.44 |
July | 0.591844E+11 | 77787.42 | 18-JUL-03:02 | 24.40 | 22.88 | 0.547440E+10 | 7498.82 | 14-JUL-09:20 | 24.40 | 22.88 |
August | 0.688889E+11 | 80747.66 | 28-AUG-03:02 | 26.27 | 23.76 | 0.613929E+10 | 7498.78 | 25-AUG-13:20 | 26.27 | 23.76 |
September | 0.611075E+11 | 81548.92 | 05-SEP-03:02 | 22.62 | 22.62 | 0.545382E+10 | 7498.81 | 14-SEP-13:20 | 28.13 | 24.89 |
October | 0.644411E+11 | 97505.74 | 28-OCT-05:02 | 10.00 | 5.56 | 0.567324E+10 | 7499.09 | 17-OCT-13:20 | 10.00 | 5.56 |
November | 0.625421E+11 | 109129.27 | 24-NOV-04:02 | 10.03 | 8.79 | 0.561732E+10 | 7504.26 | 10-NOV-10:09 | 10.03 | 8.79 |
December | 0.606785E+11 | 109257.88 | 18-DEC-04:02 | 3.17 | -0.2 | 0.547420E+10 | 7499.56 | 08-DEC-10:00 | 3.17 | -0.2 |
Annual Sum or Average | 0.706798E+12 | 0.680069E+11 | ||||||||
Minimum of Months | 0.497781E+11 | 77787.42 | 3.17 | -0.2 | 0.514041E+10 | 7498.78 | 3.17 | -0.2 | ||
Maximum of Months | 0.688889E+11 | 110548.58 | 26.27 | 23.91 | 0.613929E+10 | 7504.26 | 29.63 | 25.44 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.470816E+11 | 88919.37 | 17-JAN-04:03 | 16.83 | 16.83 | 0.507408E+10 | 6734.83 | 05-JAN-14:09 | 16.83 | 16.83 |
February | 0.456065E+11 | 90725.95 | 21-FEB-04:02 | 17.30 | 17.30 | 0.460572E+10 | 6734.91 | 28-FEB-14:30 | 25.00 | 20.38 |
March | 0.579824E+11 | 91701.52 | 20-MAR-03:02 | 12.55 | 8.37 | 0.549901E+10 | 6735.29 | 23-MAR-09:09 | 16.78 | 14.63 |
April | 0.633986E+11 | 87699.10 | 10-APR-03:02 | 13.30 | 9.00 | 0.488009E+10 | 6907.87 | 18-APR-13:00 | 27.70 | 15.13 |
May | 0.601381E+11 | 84254.60 | 23-MAY-03:02 | 24.90 | 23.43 | 0.528552E+10 | 6734.57 | 03-MAY-09:00 | 24.90 | 23.43 |
June | 0.648408E+11 | 85752.99 | 07-JUN-03:02 | 21.10 | 18.25 | 0.526557E+10 | 6734.56 | 01-JUN-13:09 | 21.10 | 18.25 |
July | 0.695588E+11 | 80350.40 | 10-JUL-05:04 | 24.60 | 23.27 | 0.489204E+10 | 6734.62 | 24-JUL-13:00 | 27.20 | 23.27 |
August | 0.770628E+11 | 78632.04 | 14-AUG-05:03 | 26.10 | 23.77 | 0.549321E+10 | 6734.57 | 07-AUG-13:00 | 26.10 | 23.77 |
September | 0.586029E+11 | 85164.06 | 08-SEP-03:02 | 22.85 | 22.73 | 0.488019E+10 | 6734.54 | 07-SEP-13:00 | 22.85 | 22.73 |
October | 0.632841E+11 | 90148.84 | 30-OCT-03:02 | 17.00 | 14.54 | 0.507613E+10 | 6734.80 | 18-OCT-09:30 | 17.00 | 14.54 |
November | 0.586188E+11 | 91445.26 | 27-NOV-04:02 | 14.30 | 13.51 | 0.502954E+10 | 6734.81 | 21-NOV-14:00 | 14.30 | 13.51 |
December | 0.582709E+11 | 92293.82 | 18-DEC-04:02 | 3.17 | -0.2 | 0.490020E+10 | 6735.00 | 08-DEC-10:30 | 3.17 | -0.2 |
Annual Sum or Average | 0.724446E+12 | 0.608813E+11 | ||||||||
Minimum of Months | 0.456065E+11 | 78632.04 | 3.17 | -0.2 | 0.460572E+10 | 6734.54 | 3.17 | -0.2 | ||
Maximum of Months | 0.770628E+11 | 92293.82 | 26.10 | 23.77 | 0.549901E+10 | 6907.87 | 27.70 | 23.77 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.356287E+11 | 78052.20 | 20-JAN-05:03 | 17.00 | 17.00 | 0.503255E+10 | 6734.80 | 05-JAN-14:09 | 17.00 | 17.00 |
February | 0.336796E+11 | 77514.36 | 11-FEB-06:02 | 13.30 | 12.93 | 0.457323E+10 | 6734.93 | 28-FEB-14:50 | 25.00 | 20.38 |
March | 0.414467E+11 | 80458.51 | 20-MAR-03:02 | 12.55 | 8.37 | 0.547351E+10 | 6735.25 | 23-MAR-09:09 | 16.78 | 14.63 |
April | 0.427854E+11 | 78916.00 | 19-APR-04:03 | 17.45 | 15.97 | 0.487837E+10 | 6783.36 | 18-APR-13:50 | 17.45 | 15.97 |
May | 0.515058E+11 | 80602.55 | 01-MAY-03:02 | 25.27 | 22.91 | 0.528290E+10 | 6734.60 | 03-MAY-09:20 | 27.93 | 21.46 |
June | 0.518089E+11 | 78502.25 | 01-JUN-03:02 | 21.95 | 21.06 | 0.526606E+10 | 6734.61 | 01-JUN-13:09 | 23.90 | 20.94 |
July | 0.513479E+11 | 74015.48 | 12-JUL-05:04 | 23.90 | 23.16 | 0.489060E+10 | 6734.58 | 20-JUL-13:00 | 28.90 | 23.37 |
August | 0.535479E+11 | 77602.18 | 01-AUG-05:04 | 23.90 | 22.91 | 0.549510E+10 | 6734.60 | 25-AUG-13:09 | 27.80 | 24.45 |
September | 0.484379E+11 | 78237.43 | 20-SEP-03:02 | 22.38 | 21.02 | 0.487454E+10 | 6734.57 | 15-SEP-13:09 | 22.38 | 21.02 |
October | 0.486279E+11 | 80219.90 | 17-OCT-03:02 | 18.08 | 14.23 | 0.507084E+10 | 6734.82 | 17-OCT-13:09 | 22.17 | 15.50 |
November | 0.414274E+11 | 77840.09 | 25-NOV-06:02 | 15.00 | 14.01 | 0.501336E+10 | 6734.84 | 13-NOV-14:09 | 15.00 | 14.01 |
December | 0.374773E+11 | 78680.80 | 14-DEC-05:03 | 20.00 | 20.00 | 0.486631E+10 | 6735.02 | 08-DEC-10:39 | 20.00 | 20.00 |
Annual Sum or Average | 0.537721E+12 | 0.607174E+11 | ||||||||
Minimum of Months | 0.336796E+11 | 74015.48 | 12.55 | 8.37 | 0.457323E+10 | 6734.57 | 15.00 | 14.01 | ||
Maximum of Months | 0.535479E+11 | 80602.55 | 25.27 | 23.16 | 0.549510E+10 | 6783.36 | 28.90 | 24.45 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.294304E+11 | 74775.42 | 19-JAN-06:03 | 18.83 | 18.83 | 0.477951E+10 | 6734.55 | 27-JAN-14:00 | 18.00 | 12.42 |
February | 0.298614E+11 | 76885.92 | 01-FEB-06:02 | 16.10 | 16.10 | 0.442479E+10 | 6734.79 | 28-FEB-14:39 | 25.00 | 20.38 |
March | 0.375237E+11 | 77094.14 | 01-MAR-06:02 | 15.52 | 13.84 | 0.536269E+10 | 6734.69 | 24-MAR-09:09 | 19.03 | 14.07 |
April | 0.426611E+11 | 78292.76 | 24-APR-03:02 | 20.18 | 20.07 | 0.486449E+10 | 6734.90 | 10-APR-13:00 | 20.18 | 20.07 |
May | 0.563427E+11 | 80152.36 | 01-MAY-03:02 | 25.27 | 22.91 | 0.528633E+10 | 6734.55 | 26-MAY-13:09 | 26.97 | 24.64 |
June | 0.578197E+11 | 79249.67 | 06-JUN-03:02 | 23.22 | 21.76 | 0.526952E+10 | 6734.58 | 01-JUN-13:09 | 23.22 | 21.76 |
July | 0.575473E+11 | 76312.70 | 01-JUL-03:02 | 24.57 | 23.11 | 0.489597E+10 | 6734.56 | 03-JUL-13:09 | 31.70 | 25.89 |
August | 0.591441E+11 | 77973.53 | 29-AUG-03:02 | 23.43 | 23.01 | 0.549830E+10 | 6734.55 | 22-AUG-13:09 | 23.43 | 23.01 |
September | 0.514912E+11 | 77884.07 | 06-SEP-03:02 | 24.70 | 23.43 | 0.487860E+10 | 6734.56 | 07-SEP-13:00 | 24.40 | 22.88 |
October | 0.501442E+11 | 79028.84 | 10-OCT-03:02 | 22.00 | 19.94 | 0.506319E+10 | 6734.80 | 17-OCT-13:09 | 22.17 | 15.50 |
November | 0.371959E+11 | 77976.40 | 08-NOV-05:03 | 19.90 | 19.21 | 0.495855E+10 | 6734.76 | 13-NOV-14:09 | 23.30 | 17.20 |
December | 0.314597E+11 | 72963.56 | 14-DEC-06:03 | 20.00 | 20.00 | 0.470123E+10 | 6734.94 | 08-DEC-10:39 | 20.00 | 20.00 |
Annual Sum or Average | 0.540621E+12 | 0.599832E+11 | ||||||||
Minimum of Months | 0.294304E+11 | 72963.56 | 15.52 | 13.84 | 0.442479E+10 | 6734.55 | 18.00 | 12.42 | ||
Maximum of Months | 0.591441E+11 | 80152.36 | 25.27 | 23.43 | 0.549830E+10 | 6734.94 | 31.70 | 25.89 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.421638E+10 | 11905.46 | 02-JAN-06:02 | 16.00 | 15.39 | 0.607240E+09 | 845.61 | 27-JAN-14:00 | 18.00 | 12.42 |
February | 0.453334E+10 | 9750.23 | 28-FEB-06:02 | 18.38 | 17.90 | 0.564171E+09 | 845.65 | 28-FEB-14:30 | 25.00 | 20.38 |
March | 0.616173E+10 | 11152.39 | 27-MAR-05:02 | 19.82 | 18.59 | 0.680469E+09 | 845.66 | 23-MAR-09:20 | 19.82 | 18.59 |
April | 0.844622E+10 | 11604.08 | 07-APR-05:02 | 19.90 | 18.48 | 0.611715E+09 | 867.02 | 18-APR-13:00 | 27.70 | 15.13 |
May | 0.104987E+11 | 12459.10 | 30-MAY-03:02 | 25.60 | 23.91 | 0.664749E+09 | 845.85 | 16-MAY-13:50 | 25.60 | 23.91 |
June | 0.118384E+11 | 12109.64 | 26-JUN-04:03 | 25.00 | 23.68 | 0.662453E+09 | 845.88 | 05-JUN-13:50 | 25.00 | 23.68 |
July | 0.123646E+11 | 14172.33 | 23-JUL-13:02 | 33.80 | 26.10 | 0.616098E+09 | 846.04 | 20-JUL-13:39 | 33.80 | 26.10 |
August | 0.131176E+11 | 14203.20 | 21-AUG-03:02 | 26.27 | 23.88 | 0.690890E+09 | 847.19 | 22-AUG-13:00 | 32.20 | 25.17 |
September | 0.937261E+10 | 12573.31 | 06-SEP-03:02 | 24.70 | 23.43 | 0.613737E+09 | 845.60 | 07-SEP-13:50 | 25.23 | 23.17 |
October | 0.927859E+10 | 12129.56 | 23-OCT-04:53 | 25.00 | 24.24 | 0.637003E+09 | 845.64 | 17-OCT-13:09 | 25.00 | 24.24 |
November | 0.643720E+10 | 11503.38 | 02-NOV-05:02 | 23.38 | 22.55 | 0.627318E+09 | 845.64 | 21-NOV-14:00 | 22.20 | 15.14 |
December | 0.557238E+10 | 11324.74 | 12-DEC-06:02 | 20.17 | 20.17 | 0.601406E+09 | 845.65 | 08-DEC-10:30 | 20.17 | 20.17 |
Annual Sum or Average | 0.101838E+12 | 0.757725E+10 | ||||||||
Minimum of Months | 0.421638E+10 | 9750.23 | 16.00 | 15.39 | 0.564171E+09 | 845.60 | 18.00 | 12.42 | ||
Maximum of Months | 0.131176E+11 | 14203.20 | 33.80 | 26.10 | 0.690890E+09 | 867.02 | 33.80 | 26.10 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.356431E+10 | 8255.62 | 01-JAN-09:53 | 20.00 | 16.19 | 0.400961E+09 | 544.96 | 11-JAN-10:09 | 14.67 | 12.06 |
February | 0.380890E+10 | 7986.17 | 26-FEB-10:43 | 24.25 | 19.98 | 0.367356E+09 | 544.97 | 28-FEB-14:30 | 25.00 | 20.38 |
March | 0.525892E+10 | 12168.71 | 26-MAR-09:02 | 23.67 | 19.70 | 0.438459E+09 | 545.01 | 23-MAR-09:09 | 23.67 | 19.70 |
April | 0.678647E+10 | 16376.50 | 23-APR-09:13 | 24.97 | 20.75 | 0.393717E+09 | 553.78 | 18-APR-13:00 | 24.97 | 20.75 |
May | 0.851861E+10 | 16847.88 | 07-MAY-09:22 | 29.15 | 23.43 | 0.428685E+09 | 545.31 | 03-MAY-09:50 | 29.15 | 23.43 |
June | 0.908089E+10 | 11043.27 | 29-JUN-05:02 | 25.18 | 24.55 | 0.426924E+09 | 545.27 | 12-JUN-09:00 | 25.18 | 24.55 |
July | 0.925006E+10 | 16752.61 | 23-JUL-09:02 | 29.68 | 25.89 | 0.397007E+09 | 545.11 | 20-JUL-09:00 | 29.68 | 25.89 |
August | 0.932142E+10 | 15075.14 | 27-AUG-10:23 | 30.00 | 24.51 | 0.445024E+09 | 544.94 | 25-AUG-13:09 | 30.00 | 24.51 |
September | 0.721812E+10 | 16821.18 | 24-SEP-09:32 | 29.03 | 25.00 | 0.395802E+09 | 545.42 | 11-SEP-09:00 | 29.03 | 25.00 |
October | 0.724939E+10 | 16327.62 | 09-OCT-08:53 | 27.10 | 22.26 | 0.410607E+09 | 544.96 | 18-OCT-09:30 | 21.50 | 17.07 |
November | 0.504968E+10 | 10432.73 | 11-NOV-09:23 | 24.40 | 21.68 | 0.404641E+09 | 544.96 | 27-NOV-14:09 | 25.82 | 17.52 |
December | 0.409322E+10 | 5661.18 | 10-DEC-09:43 | 23.33 | 19.53 | 0.385475E+09 | 544.98 | 08-DEC-10:30 | 23.33 | 19.53 |
Annual Sum or Average | 0.792000E+11 | 0.489466E+10 | ||||||||
Minimum of Months | 0.356431E+10 | 5661.18 | 20.00 | 16.19 | 0.367356E+09 | 544.94 | 14.67 | 12.06 | ||
Maximum of Months | 0.932142E+10 | 16847.88 | 30.00 | 25.89 | 0.445024E+09 | 553.78 | 30.00 | 25.89 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.854832E+10 | 19949.38 | 01-JAN-13:52 | 26.00 | 17.88 | 0.629397E+09 | 858.25 | 19-JAN-14:20 | 25.00 | 21.54 |
February | 0.836133E+10 | 19818.23 | 26-FEB-14:43 | 26.18 | 20.05 | 0.573604E+09 | 859.02 | 27-FEB-14:20 | 25.70 | 20.08 |
March | 0.873218E+10 | 19176.97 | 26-MAR-13:43 | 29.90 | 19.94 | 0.682435E+09 | 846.00 | 29-MAR-13:00 | 25.00 | 21.11 |
April | 0.990174E+10 | 13692.53 | 29-APR-05:02 | 23.20 | 21.68 | 0.612383E+09 | 890.74 | 18-APR-13:00 | 23.20 | 21.68 |
May | 0.107338E+11 | 14347.00 | 01-MAY-05:02 | 25.92 | 23.71 | 0.664813E+09 | 845.63 | 31-MAY-13:09 | 23.27 | 21.49 |
June | 0.114975E+11 | 14419.25 | 26-JUN-04:03 | 25.00 | 23.68 | 0.662385E+09 | 845.63 | 01-JUN-13:09 | 25.00 | 23.68 |
July | 0.122664E+11 | 15979.21 | 23-JUL-13:02 | 33.80 | 26.10 | 0.616063E+09 | 845.63 | 24-JUL-13:00 | 27.20 | 23.27 |
August | 0.141650E+11 | 18809.56 | 27-AUG-13:02 | 33.17 | 23.64 | 0.691143E+09 | 845.92 | 31-AUG-13:00 | 31.60 | 25.03 |
September | 0.113831E+11 | 19654.20 | 03-SEP-15:12 | 32.53 | 24.63 | 0.614518E+09 | 845.97 | 12-SEP-13:20 | 31.60 | 24.10 |
October | 0.137808E+11 | 19856.92 | 08-OCT-11:43 | 30.83 | 25.74 | 0.639079E+09 | 858.57 | 10-OCT-13:09 | 31.00 | 22.17 |
November | 0.116855E+11 | 21006.21 | 11-NOV-13:22 | 26.35 | 22.79 | 0.632516E+09 | 890.01 | 06-NOV-14:09 | 26.35 | 22.79 |
December | 0.105907E+11 | 19838.54 | 10-DEC-13:42 | 27.00 | 20.22 | 0.610516E+09 | 867.09 | 15-DEC-14:30 | 29.00 | 21.83 |
Annual Sum or Average | 0.131646E+12 | 0.762885E+10 | ||||||||
Minimum of Months | 0.836133E+10 | 13692.53 | 23.20 | 17.88 | 0.573604E+09 | 845.63 | 23.20 | 20.08 | ||
Maximum of Months | 0.141650E+11 | 21006.21 | 33.80 | 26.10 | 0.691143E+09 | 890.74 | 31.60 | 25.03 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.524480E+10 | 16714.11 | 16-JAN-15:53 | 25.00 | 17.90 | 0.400997E+09 | 544.96 | 05-JAN-14:20 | 25.00 | 17.90 |
February | 0.621088E+10 | 19228.16 | 26-FEB-15:23 | 25.80 | 20.01 | 0.370703E+09 | 544.99 | 28-FEB-14:30 | 25.00 | 20.38 |
March | 0.876754E+10 | 19527.38 | 26-MAR-14:23 | 26.90 | 20.14 | 0.445002E+09 | 545.00 | 23-MAR-09:09 | 26.90 | 20.14 |
April | 0.121067E+11 | 21178.71 | 23-APR-16:32 | 27.37 | 21.80 | 0.396549E+09 | 561.01 | 18-APR-14:00 | 27.37 | 21.80 |
May | 0.103241E+11 | 21240.88 | 28-MAY-16:21 | 32.50 | 24.77 | 0.429025E+09 | 544.94 | 03-MAY-09:00 | 32.50 | 24.77 |
June | 0.123043E+11 | 20992.23 | 11-JUN-16:42 | 33.12 | 21.82 | 0.427701E+09 | 544.94 | 01-JUN-13:09 | 33.12 | 21.82 |
July | 0.135345E+11 | 20719.03 | 16-JUL-15:52 | 31.70 | 25.48 | 0.397981E+09 | 544.95 | 24-JUL-13:00 | 27.20 | 23.27 |
August | 0.160425E+11 | 20763.98 | 06-AUG-16:22 | 25.00 | 22.52 | 0.446385E+09 | 544.95 | 07-AUG-13:00 | 24.00 | 22.63 |
September | 0.960117E+10 | 22571.25 | 03-SEP-15:51 | 32.20 | 24.61 | 0.396266E+09 | 544.94 | 07-SEP-13:50 | 25.23 | 23.17 |
October | 0.107658E+11 | 21487.10 | 22-OCT-15:52 | 28.90 | 23.86 | 0.412118E+09 | 544.96 | 17-OCT-13:09 | 28.90 | 23.86 |
November | 0.882539E+10 | 21584.90 | 11-NOV-15:22 | 26.35 | 22.93 | 0.407812E+09 | 544.98 | 27-NOV-14:09 | 25.82 | 17.52 |
December | 0.867725E+10 | 19820.40 | 10-DEC-15:42 | 27.17 | 20.20 | 0.397140E+09 | 544.98 | 08-DEC-10:30 | 27.17 | 20.20 |
Annual Sum or Average | 0.122405E+12 | 0.492768E+10 | ||||||||
Minimum of Months | 0.524480E+10 | 16714.11 | 25.00 | 17.90 | 0.370703E+09 | 544.94 | 24.00 | 17.52 | ||
Maximum of Months | 0.160425E+11 | 22571.25 | 33.12 | 25.48 | 0.446385E+09 | 561.01 | 33.12 | 24.77 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.287946E+10 | 5208.97 | 31-JAN-14:40 | 25.00 | 21.54 | 0.558308E+09 | 845.60 | 02-JAN-14:50 | 25.00 | 21.54 |
February | 0.313250E+10 | 5437.44 | 28-FEB-15:00 | 25.00 | 20.38 | 0.532062E+09 | 845.64 | 28-FEB-14:50 | 25.00 | 20.38 |
March | 0.409000E+10 | 9249.26 | 27-MAR-05:02 | 19.82 | 18.59 | 0.648010E+09 | 845.62 | 15-MAR-13:09 | 19.82 | 18.59 |
April | 0.557779E+10 | 10168.52 | 29-APR-05:02 | 23.20 | 21.68 | 0.606309E+09 | 851.80 | 18-APR-13:50 | 23.20 | 21.68 |
May | 0.938808E+10 | 14098.03 | 29-MAY-16:01 | 32.43 | 23.42 | 0.664703E+09 | 845.79 | 16-MAY-13:50 | 32.43 | 23.42 |
June | 0.101685E+11 | 14463.46 | 25-JUN-16:31 | 32.40 | 24.97 | 0.662719E+09 | 845.76 | 05-JUN-13:39 | 32.40 | 24.97 |
July | 0.100117E+11 | 13185.16 | 03-JUL-03:02 | 28.03 | 25.04 | 0.616356E+09 | 845.86 | 20-JUL-13:00 | 28.90 | 23.37 |
August | 0.994140E+10 | 13192.26 | 21-AUG-03:02 | 26.27 | 23.88 | 0.691288E+09 | 845.83 | 14-AUG-13:50 | 26.27 | 23.88 |
September | 0.799543E+10 | 11478.23 | 11-SEP-05:03 | 25.42 | 23.91 | 0.613411E+09 | 845.60 | 07-SEP-13:39 | 25.42 | 23.91 |
October | 0.727557E+10 | 14273.06 | 08-OCT-14:52 | 31.00 | 25.74 | 0.634183E+09 | 845.64 | 17-OCT-13:09 | 22.17 | 15.50 |
November | 0.434089E+10 | 10587.25 | 01-NOV-05:03 | 22.62 | 22.36 | 0.607593E+09 | 845.62 | 21-NOV-14:00 | 22.20 | 15.14 |
December | 0.333913E+10 | 10121.05 | 15-DEC-06:02 | 21.00 | 21.00 | 0.552526E+09 | 845.61 | 14-DEC-14:39 | 21.00 | 21.00 |
Annual Sum or Average | 0.781404E+11 | 0.738747E+10 | ||||||||
Minimum of Months | 0.287946E+10 | 5208.97 | 19.82 | 18.59 | 0.532062E+09 | 845.60 | 19.82 | 15.14 | ||
Maximum of Months | 0.101685E+11 | 14463.46 | 32.43 | 25.74 | 0.691288E+09 | 851.80 | 32.43 | 24.97 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.266650E+10 | 6396.73 | 19-JAN-10:00 | 23.00 | 20.89 | 0.279069E+09 | 521.20 | 19-JAN-16:00 | 24.00 | 20.62 |
February | 0.300592E+10 | 6835.02 | 27-FEB-10:00 | 21.10 | 19.21 | 0.261109E+09 | 521.22 | 09-FEB-11:09 | 21.10 | 19.21 |
March | 0.419942E+10 | 10696.95 | 26-MAR-09:43 | 25.13 | 20.13 | 0.313302E+09 | 521.24 | 23-MAR-08:00 | 25.13 | 20.13 |
April | 0.559309E+10 | 17342.48 | 23-APR-09:32 | 25.53 | 20.92 | 0.289116E+09 | 523.19 | 18-APR-14:00 | 25.53 | 20.92 |
May | 0.822051E+10 | 18026.50 | 29-MAY-08:42 | 27.62 | 23.19 | 0.315710E+09 | 521.21 | 03-MAY-08:00 | 27.62 | 23.19 |
June | 0.857205E+10 | 16781.62 | 11-JUN-08:32 | 26.87 | 20.94 | 0.314190E+09 | 521.32 | 28-JUN-10:30 | 31.40 | 24.40 |
July | 0.842053E+10 | 16754.31 | 30-JUL-09:02 | 29.50 | 25.11 | 0.293319E+09 | 521.63 | 20-JUL-10:30 | 29.50 | 25.11 |
August | 0.824259E+10 | 16631.63 | 27-AUG-10:23 | 30.00 | 24.51 | 0.327648E+09 | 521.20 | 29-AUG-14:20 | 30.87 | 23.97 |
September | 0.666116E+10 | 16594.00 | 10-SEP-09:42 | 33.73 | 27.29 | 0.291439E+09 | 521.20 | 07-SEP-14:20 | 33.73 | 27.29 |
October | 0.638727E+10 | 16009.14 | 08-OCT-14:52 | 31.00 | 25.74 | 0.301586E+09 | 521.22 | 17-OCT-12:20 | 21.33 | 14.79 |
November | 0.397458E+10 | 9791.74 | 02-NOV-05:02 | 23.38 | 22.55 | 0.294188E+09 | 521.21 | 21-NOV-15:20 | 21.83 | 15.14 |
December | 0.287740E+10 | 5974.59 | 15-DEC-06:02 | 21.00 | 21.00 | 0.269262E+09 | 521.21 | 01-DEC-11:09 | 21.00 | 21.00 |
Annual Sum or Average | 0.688210E+11 | 0.354994E+10 | ||||||||
Minimum of Months | 0.266650E+10 | 5974.59 | 21.00 | 19.21 | 0.261109E+09 | 521.20 | 21.00 | 14.79 | ||
Maximum of Months | 0.857205E+10 | 18026.50 | 33.73 | 27.29 | 0.327648E+09 | 523.19 | 33.73 | 27.29 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.759863E+10 | 20670.25 | 01-JAN-14:11 | 25.67 | 18.12 | 0.622666E+09 | 884.91 | 19-JAN-14:39 | 25.00 | 21.54 |
February | 0.726445E+10 | 19317.52 | 26-FEB-13:42 | 26.52 | 19.51 | 0.567975E+09 | 876.94 | 27-FEB-14:39 | 25.90 | 20.26 |
March | 0.685394E+10 | 18022.03 | 26-MAR-13:43 | 29.90 | 19.94 | 0.670800E+09 | 845.84 | 06-MAR-14:50 | 29.90 | 19.94 |
April | 0.722567E+10 | 13865.96 | 23-APR-15:32 | 28.07 | 21.86 | 0.609787E+09 | 865.35 | 18-APR-13:50 | 28.07 | 21.86 |
May | 0.963564E+10 | 17008.33 | 29-MAY-16:01 | 32.43 | 23.42 | 0.664772E+09 | 845.62 | 03-MAY-09:20 | 32.43 | 23.42 |
June | 0.979700E+10 | 17435.51 | 25-JUN-15:51 | 32.80 | 24.12 | 0.662572E+09 | 845.62 | 12-JUN-13:09 | 32.80 | 24.12 |
July | 0.992573E+10 | 15255.13 | 20-JUL-03:02 | 26.70 | 24.39 | 0.616277E+09 | 845.62 | 20-JUL-13:00 | 28.90 | 23.37 |
August | 0.110951E+11 | 17675.59 | 27-AUG-13:02 | 33.17 | 23.64 | 0.691606E+09 | 845.80 | 31-AUG-13:00 | 31.60 | 25.03 |
September | 0.101942E+11 | 18443.03 | 17-SEP-14:22 | 31.60 | 26.01 | 0.614389E+09 | 845.81 | 12-SEP-13:39 | 31.60 | 26.01 |
October | 0.122323E+11 | 19513.53 | 08-OCT-14:52 | 31.00 | 25.74 | 0.639199E+09 | 876.25 | 13-OCT-13:50 | 32.87 | 23.24 |
November | 0.994987E+10 | 19448.05 | 05-NOV-13:32 | 27.20 | 20.74 | 0.631181E+09 | 911.73 | 06-NOV-14:09 | 28.30 | 21.03 |
December | 0.845852E+10 | 20198.37 | 10-DEC-12:42 | 27.00 | 20.34 | 0.601869E+09 | 879.99 | 15-DEC-14:39 | 29.00 | 21.74 |
Annual Sum or Average | 0.110231E+12 | 0.759309E+10 | ||||||||
Minimum of Months | 0.685394E+10 | 13865.96 | 25.67 | 18.12 | 0.567975E+09 | 845.62 | 25.00 | 19.94 | ||
Maximum of Months | 0.122323E+11 | 20670.25 | 33.17 | 26.01 | 0.691606E+09 | 911.73 | 32.87 | 26.01 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.316809E+10 | 13871.29 | 01-JAN-15:32 | 25.00 | 18.55 | 0.373965E+09 | 544.94 | 02-JAN-14:50 | 26.83 | 18.62 |
February | 0.353744E+10 | 17306.88 | 26-FEB-17:03 | 24.22 | 19.76 | 0.351774E+09 | 544.97 | 28-FEB-14:50 | 25.00 | 20.38 |
March | 0.443169E+10 | 12330.72 | 27-MAR-05:02 | 19.82 | 18.59 | 0.424135E+09 | 544.95 | 24-MAR-09:50 | 19.82 | 18.59 |
April | 0.610923E+10 | 18710.30 | 23-APR-16:52 | 27.20 | 21.71 | 0.393509E+09 | 548.69 | 18-APR-13:30 | 27.20 | 21.71 |
May | 0.808852E+10 | 19114.55 | 29-MAY-16:01 | 32.43 | 23.42 | 0.428743E+09 | 544.94 | 03-MAY-09:20 | 32.43 | 23.42 |
June | 0.870965E+10 | 19141.24 | 11-JUN-17:11 | 32.93 | 21.75 | 0.427481E+09 | 544.94 | 12-JUN-09:20 | 29.07 | 22.55 |
July | 0.844149E+10 | 16408.38 | 16-JUL-15:52 | 31.70 | 25.48 | 0.397636E+09 | 544.94 | 20-JUL-13:00 | 28.90 | 23.37 |
August | 0.890172E+10 | 15568.64 | 21-AUG-03:02 | 26.27 | 23.88 | 0.446001E+09 | 544.94 | 25-AUG-13:09 | 27.80 | 24.45 |
September | 0.715455E+10 | 18481.81 | 17-SEP-15:42 | 32.10 | 25.59 | 0.395769E+09 | 544.94 | 07-SEP-13:39 | 32.10 | 25.59 |
October | 0.704165E+10 | 18334.73 | 08-OCT-16:12 | 30.33 | 25.03 | 0.410119E+09 | 544.96 | 17-OCT-13:09 | 22.17 | 15.50 |
November | 0.452532E+10 | 12341.82 | 05-NOV-15:32 | 27.20 | 19.72 | 0.396804E+09 | 544.96 | 21-NOV-14:00 | 22.20 | 15.14 |
December | 0.369359E+10 | 17173.28 | 10-DEC-15:22 | 27.50 | 20.13 | 0.368216E+09 | 544.95 | 14-DEC-14:39 | 27.67 | 22.98 |
Annual Sum or Average | 0.738029E+11 | 0.481415E+10 | ||||||||
Minimum of Months | 0.316809E+10 | 12330.72 | 19.82 | 18.55 | 0.351774E+09 | 544.94 | 19.82 | 15.14 | ||
Maximum of Months | 0.890172E+10 | 19141.24 | 32.93 | 25.59 | 0.446001E+09 | 548.69 | 32.43 | 25.59 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.221614E+10 | 5478.47 | 31-JAN-15:00 | 25.00 | 21.54 | 0.533050E+09 | 845.60 | 02-JAN-14:00 | 25.00 | 21.54 |
February | 0.272501E+10 | 5753.84 | 22-FEB-14:30 | 25.55 | 20.41 | 0.514102E+09 | 845.63 | 28-FEB-14:39 | 25.00 | 20.38 |
March | 0.379669E+10 | 8266.40 | 27-MAR-05:02 | 19.82 | 18.59 | 0.625155E+09 | 845.61 | 15-MAR-13:50 | 19.82 | 18.59 |
April | 0.562746E+10 | 11860.74 | 29-APR-05:02 | 23.20 | 21.68 | 0.599637E+09 | 845.64 | 12-APR-13:30 | 23.20 | 21.68 |
May | 0.101436E+11 | 16997.61 | 29-MAY-16:01 | 32.43 | 23.42 | 0.664919E+09 | 845.73 | 16-MAY-13:50 | 32.43 | 23.42 |
June | 0.111431E+11 | 17184.13 | 25-JUN-16:31 | 32.40 | 24.97 | 0.662904E+09 | 845.60 | 12-JUN-13:09 | 32.40 | 24.97 |
July | 0.110335E+11 | 16506.11 | 02-JUL-17:03 | 29.90 | 25.00 | 0.616713E+09 | 846.17 | 20-JUL-13:39 | 30.57 | 24.32 |
August | 0.108293E+11 | 16294.45 | 27-AUG-16:12 | 33.33 | 24.08 | 0.691464E+09 | 845.97 | 21-AUG-13:20 | 33.33 | 24.08 |
September | 0.847257E+10 | 16408.81 | 17-SEP-15:42 | 32.10 | 25.59 | 0.613465E+09 | 845.61 | 07-SEP-13:00 | 32.10 | 25.59 |
October | 0.754256E+10 | 16909.88 | 08-OCT-14:52 | 31.00 | 25.74 | 0.630941E+09 | 845.64 | 17-OCT-13:09 | 22.17 | 15.50 |
November | 0.400143E+10 | 12237.82 | 02-NOV-05:02 | 23.38 | 22.55 | 0.589903E+09 | 845.63 | 21-NOV-14:00 | 22.20 | 15.14 |
December | 0.277534E+10 | 6360.99 | 15-DEC-15:00 | 29.00 | 21.56 | 0.528145E+09 | 845.61 | 14-DEC-14:39 | 29.00 | 21.56 |
Annual Sum or Average | 0.803066E+11 | 0.727040E+10 | ||||||||
Minimum of Months | 0.221614E+10 | 5478.47 | 19.82 | 18.59 | 0.514102E+09 | 845.60 | 19.82 | 15.14 | ||
Maximum of Months | 0.111431E+11 | 17184.13 | 33.33 | 25.74 | 0.691464E+09 | 846.17 | 33.33 | 25.59 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.230210E+10 | 6126.19 | 19-JAN-10:20 | 23.57 | 21.08 | 0.363271E+09 | 544.94 | 02-JAN-10:09 | 23.57 | 21.08 |
February | 0.275892E+10 | 6651.82 | 27-FEB-10:30 | 21.90 | 19.28 | 0.346756E+09 | 544.96 | 28-FEB-14:39 | 25.00 | 20.38 |
March | 0.399937E+10 | 9620.83 | 27-MAR-05:02 | 19.82 | 18.59 | 0.420055E+09 | 545.00 | 23-MAR-09:09 | 19.82 | 18.59 |
April | 0.575005E+10 | 17028.12 | 23-APR-11:02 | 26.70 | 20.26 | 0.391681E+09 | 544.98 | 12-APR-13:30 | 26.70 | 20.26 |
May | 0.894686E+10 | 18545.74 | 29-MAY-08:42 | 27.62 | 23.19 | 0.428911E+09 | 545.31 | 03-MAY-09:00 | 27.62 | 23.19 |
June | 0.945390E+10 | 17141.03 | 11-JUN-08:32 | 26.87 | 20.94 | 0.427430E+09 | 545.23 | 13-JUN-09:20 | 29.60 | 24.10 |
July | 0.936872E+10 | 17923.63 | 23-JUL-09:02 | 29.68 | 25.89 | 0.397722E+09 | 545.23 | 07-JUL-09:00 | 29.68 | 25.89 |
August | 0.907681E+10 | 17072.57 | 27-AUG-10:13 | 30.00 | 24.62 | 0.445808E+09 | 545.08 | 10-AUG-09:00 | 30.00 | 24.62 |
September | 0.718654E+10 | 17116.62 | 10-SEP-09:42 | 33.73 | 27.29 | 0.395664E+09 | 545.33 | 11-SEP-09:00 | 28.80 | 24.74 |
October | 0.674101E+10 | 16827.65 | 08-OCT-14:52 | 31.00 | 25.74 | 0.408299E+09 | 544.96 | 18-OCT-09:50 | 22.50 | 17.62 |
November | 0.375316E+10 | 9879.80 | 02-NOV-05:02 | 23.38 | 22.55 | 0.395459E+09 | 544.96 | 21-NOV-14:00 | 22.20 | 15.14 |
December | 0.250856E+10 | 4897.81 | 16-DEC-10:10 | 24.33 | 21.30 | 0.354106E+09 | 544.98 | 08-DEC-10:39 | 24.33 | 21.30 |
Annual Sum or Average | 0.718460E+11 | 0.477516E+10 | ||||||||
Minimum of Months | 0.230210E+10 | 4897.81 | 19.82 | 18.59 | 0.346756E+09 | 544.94 | 19.82 | 15.14 | ||
Maximum of Months | 0.945390E+10 | 18545.74 | 33.73 | 27.29 | 0.445808E+09 | 545.33 | 30.00 | 25.89 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.635802E+10 | 22582.53 | 01-JAN-15:02 | 25.00 | 18.55 | 0.607190E+09 | 860.99 | 19-JAN-14:50 | 25.00 | 21.54 |
February | 0.658472E+10 | 21361.69 | 26-FEB-13:52 | 26.60 | 19.72 | 0.556547E+09 | 855.51 | 27-FEB-14:39 | 25.90 | 20.26 |
March | 0.643290E+10 | 17332.89 | 05-MAR-13:33 | 27.70 | 18.32 | 0.654003E+09 | 845.89 | 06-MAR-14:50 | 26.18 | 21.15 |
April | 0.730673E+10 | 18208.64 | 23-APR-15:01 | 28.62 | 21.65 | 0.604942E+09 | 845.68 | 12-APR-13:30 | 28.62 | 21.65 |
May | 0.104099E+11 | 20140.95 | 29-MAY-16:01 | 32.43 | 23.42 | 0.664958E+09 | 845.62 | 31-MAY-13:09 | 23.27 | 21.49 |
June | 0.107478E+11 | 20181.35 | 25-JUN-15:51 | 32.80 | 24.12 | 0.662760E+09 | 845.62 | 12-JUN-13:09 | 32.80 | 24.12 |
July | 0.109323E+11 | 18875.07 | 23-JUL-13:02 | 33.80 | 26.10 | 0.616605E+09 | 845.62 | 14-JUL-13:20 | 33.80 | 26.10 |
August | 0.120695E+11 | 19872.62 | 27-AUG-12:53 | 33.00 | 23.68 | 0.691741E+09 | 845.88 | 31-AUG-13:00 | 31.60 | 25.03 |
September | 0.108395E+11 | 20821.25 | 17-SEP-14:22 | 31.60 | 26.01 | 0.614405E+09 | 845.98 | 19-SEP-13:20 | 28.87 | 24.26 |
October | 0.126754E+11 | 22252.80 | 08-OCT-14:52 | 31.00 | 25.74 | 0.637126E+09 | 861.96 | 13-OCT-13:00 | 33.00 | 23.24 |
November | 0.939724E+10 | 22413.15 | 11-NOV-14:02 | 26.18 | 22.88 | 0.624962E+09 | 887.57 | 06-NOV-14:20 | 26.18 | 22.88 |
December | 0.753593E+10 | 22516.71 | 10-DEC-12:52 | 27.00 | 20.22 | 0.586121E+09 | 856.85 | 15-DEC-14:39 | 29.00 | 21.74 |
Annual Sum or Average | 0.111290E+12 | 0.752136E+10 | ||||||||
Minimum of Months | 0.635802E+10 | 17332.89 | 25.00 | 18.32 | 0.556547E+09 | 845.62 | 23.27 | 20.26 | ||
Maximum of Months | 0.126754E+11 | 22582.53 | 33.80 | 26.10 | 0.691741E+09 | 887.57 | 33.80 | 26.10 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.275138E+10 | 9251.06 | 01-JAN-17:03 | 23.33 | 19.19 | 0.358704E+09 | 544.94 | 02-JAN-14:50 | 26.83 | 18.62 |
February | 0.328908E+10 | 15223.43 | 26-FEB-17:12 | 24.03 | 19.67 | 0.341052E+09 | 544.96 | 28-FEB-14:39 | 25.00 | 20.38 |
March | 0.426678E+10 | 13101.05 | 27-MAR-05:02 | 19.82 | 18.59 | 0.409763E+09 | 544.94 | 15-MAR-13:39 | 19.82 | 18.59 |
April | 0.620931E+10 | 19355.22 | 23-APR-17:01 | 26.92 | 21.65 | 0.389769E+09 | 544.98 | 12-APR-13:30 | 26.92 | 21.65 |
May | 0.869581E+10 | 21253.96 | 29-MAY-16:01 | 32.43 | 23.42 | 0.428744E+09 | 544.94 | 31-MAY-13:09 | 23.27 | 21.49 |
June | 0.947028E+10 | 21132.71 | 11-JUN-17:11 | 32.93 | 21.75 | 0.427485E+09 | 544.94 | 12-JUN-13:09 | 31.78 | 20.56 |
July | 0.924908E+10 | 19132.36 | 30-JUL-16:52 | 27.20 | 24.74 | 0.397677E+09 | 544.94 | 14-JUL-13:09 | 27.20 | 24.74 |
August | 0.961146E+10 | 17648.68 | 27-AUG-16:12 | 33.33 | 24.08 | 0.446020E+09 | 544.94 | 25-AUG-13:09 | 33.33 | 24.08 |
September | 0.759574E+10 | 20236.31 | 17-SEP-15:42 | 32.10 | 25.59 | 0.395569E+09 | 544.94 | 07-SEP-13:00 | 32.10 | 25.59 |
October | 0.732783E+10 | 20213.05 | 08-OCT-16:12 | 30.33 | 25.03 | 0.408183E+09 | 544.96 | 17-OCT-13:09 | 22.17 | 15.50 |
November | 0.433667E+10 | 17809.92 | 11-NOV-15:22 | 26.35 | 22.93 | 0.386901E+09 | 544.96 | 21-NOV-14:00 | 22.20 | 15.14 |
December | 0.331590E+10 | 18918.04 | 10-DEC-16:12 | 26.33 | 20.05 | 0.353111E+09 | 544.95 | 14-DEC-14:39 | 27.67 | 22.98 |
Annual Sum or Average | 0.761193E+11 | 0.474298E+10 | ||||||||
Minimum of Months | 0.275138E+10 | 9251.06 | 19.82 | 18.59 | 0.341052E+09 | 544.94 | 19.82 | 15.14 | ||
Maximum of Months | 0.961146E+10 | 21253.96 | 33.33 | 25.59 | 0.446020E+09 | 544.98 | 33.33 | 25.59 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.387755E+10 | 11952.62 | 02-JAN-06:15 | 16.00 | 15.39 | 0.00 | 0.00 | 01-JAN-00:10 | 16.00 | 15.39 |
February | 0.430433E+10 | 8690.61 | 27-FEB-06:15 | 17.70 | 17.70 | 0.00 | 0.00 | 01-FEB-00:10 | 17.70 | 17.70 |
March | 0.567338E+10 | 9503.76 | 27-MAR-05:15 | 19.73 | 18.53 | 0.00 | 0.00 | 01-MAR-00:10 | 19.73 | 18.53 |
April | 0.735718E+10 | 8564.63 | 24-APR-05:15 | 20.17 | 20.05 | 0.00 | 0.00 | 01-APR-00:10 | 20.17 | 20.05 |
May | 0.924257E+10 | 13943.61 | 22-MAY-05:13 | 26.10 | 22.55 | 0.00 | 0.00 | 01-MAY-00:10 | 26.10 | 22.55 |
June | 0.997463E+10 | 9890.61 | 12-JUN-05:15 | 23.70 | 21.42 | 0.00 | 0.00 | 01-JUN-00:10 | 23.70 | 21.42 |
July | 0.105501E+11 | 13585.21 | 24-JUL-05:15 | 26.83 | 24.96 | 0.00 | 0.00 | 01-JUL-00:10 | 26.83 | 24.96 |
August | 0.116539E+11 | 13830.48 | 28-AUG-05:15 | 25.33 | 23.69 | 0.00 | 0.00 | 01-AUG-00:10 | 25.33 | 23.69 |
September | 0.875982E+10 | 13759.94 | 05-SEP-05:15 | 22.80 | 22.80 | 0.00 | 0.00 | 01-SEP-00:10 | 22.80 | 22.80 |
October | 0.906198E+10 | 14017.82 | 10-OCT-05:15 | 21.97 | 20.04 | 0.00 | 0.00 | 01-OCT-00:10 | 21.97 | 20.04 |
November | 0.668095E+10 | 9779.61 | 06-NOV-06:15 | 18.80 | 17.70 | 0.00 | 0.00 | 01-NOV-00:10 | 18.80 | 17.70 |
December | 0.540021E+10 | 9113.80 | 11-DEC-06:15 | 20.67 | 20.21 | 0.00 | 0.00 | 01-DEC-00:10 | 20.67 | 20.21 |
Annual Sum or Average | 0.925366E+11 | 0.00 | ||||||||
Minimum of Months | 0.387755E+10 | 8564.63 | 16.00 | 15.39 | 0.00 | 0.00 | 16.00 | 15.39 | ||
Maximum of Months | 0.116539E+11 | 14017.82 | 26.83 | 24.96 | 0.00 | 0.00 | 26.83 | 24.96 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.205626E+10 | 6891.05 | 02-JAN-06:15 | 16.00 | 15.39 | 0.00 | 0.00 | 01-JAN-00:10 | 16.00 | 15.39 |
February | 0.242079E+10 | 5175.24 | 24-FEB-06:13 | 14.60 | 14.60 | 0.00 | 0.00 | 01-FEB-00:10 | 14.60 | 14.60 |
March | 0.332932E+10 | 5778.22 | 01-MAR-06:13 | 15.53 | 13.91 | 0.00 | 0.00 | 01-MAR-00:10 | 15.53 | 13.91 |
April | 0.496999E+10 | 6430.65 | 28-APR-15:20 | 32.93 | 23.96 | 0.00 | 0.00 | 01-APR-00:10 | 32.93 | 23.96 |
May | 0.804588E+10 | 12706.03 | 22-MAY-05:13 | 26.10 | 22.55 | 0.00 | 0.00 | 01-MAY-00:10 | 26.10 | 22.55 |
June | 0.834218E+10 | 8560.51 | 23-JUN-05:02 | 25.60 | 23.86 | 0.00 | 0.00 | 01-JUN-00:10 | 25.60 | 23.86 |
July | 0.832922E+10 | 8011.97 | 31-JUL-05:13 | 24.40 | 23.27 | 0.00 | 0.00 | 01-JUL-00:10 | 24.40 | 23.27 |
August | 0.866537E+10 | 8964.87 | 28-AUG-05:02 | 25.67 | 23.79 | 0.00 | 0.00 | 01-AUG-00:10 | 25.67 | 23.79 |
September | 0.721044E+10 | 8556.71 | 05-SEP-05:15 | 22.80 | 22.80 | 0.00 | 0.00 | 01-SEP-00:10 | 22.80 | 22.80 |
October | 0.700211E+10 | 9605.40 | 10-OCT-05:15 | 21.97 | 20.04 | 0.00 | 0.00 | 01-OCT-00:10 | 21.97 | 20.04 |
November | 0.405458E+10 | 6676.58 | 04-NOV-05:15 | 20.57 | 20.00 | 0.00 | 0.00 | 01-NOV-00:10 | 20.57 | 20.00 |
December | 0.284487E+10 | 5782.50 | 15-DEC-06:15 | 21.00 | 21.00 | 0.00 | 0.00 | 01-DEC-00:10 | 21.00 | 21.00 |
Annual Sum or Average | 0.672710E+11 | 0.00 | ||||||||
Minimum of Months | 0.205626E+10 | 5175.24 | 14.60 | 13.91 | 0.00 | 0.00 | 14.60 | 13.91 | ||
Maximum of Months | 0.866537E+10 | 12706.03 | 32.93 | 23.96 | 0.00 | 0.00 | 32.93 | 23.96 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.209665E+10 | 9748.93 | 19-JAN-15:00 | 25.00 | 21.54 | 0.00 | 0.00 | 01-JAN-00:10 | 25.00 | 21.54 |
February | 0.327521E+10 | 11609.51 | 24-FEB-15:00 | 25.50 | 20.83 | 0.00 | 0.00 | 01-FEB-00:10 | 25.50 | 20.83 |
March | 0.471593E+10 | 12987.63 | 06-MAR-15:00 | 26.10 | 21.05 | 0.00 | 0.00 | 01-MAR-00:10 | 26.10 | 21.05 |
April | 0.825277E+10 | 18175.10 | 28-APR-15:00 | 33.30 | 23.06 | 0.00 | 0.00 | 01-APR-00:10 | 33.30 | 23.06 |
May | 0.137456E+11 | 19299.57 | 10-MAY-14:40 | 32.80 | 23.17 | 0.00 | 0.00 | 01-MAY-00:10 | 32.80 | 23.17 |
June | 0.152682E+11 | 20243.21 | 28-JUN-14:00 | 33.90 | 26.45 | 0.00 | 0.00 | 01-JUN-00:10 | 33.90 | 26.45 |
July | 0.146116E+11 | 20443.99 | 07-JUL-14:30 | 34.45 | 24.41 | 0.00 | 0.00 | 01-JUL-00:10 | 34.45 | 24.41 |
August | 0.147212E+11 | 19533.00 | 10-AUG-14:00 | 32.70 | 25.03 | 0.00 | 0.00 | 01-AUG-00:10 | 32.70 | 25.03 |
September | 0.111470E+11 | 17594.43 | 01-SEP-15:10 | 31.38 | 24.60 | 0.00 | 0.00 | 01-SEP-00:10 | 31.38 | 24.60 |
October | 0.103807E+11 | 16472.91 | 05-OCT-15:40 | 32.67 | 23.68 | 0.00 | 0.00 | 01-OCT-00:10 | 32.67 | 23.68 |
November | 0.477868E+10 | 13018.03 | 02-NOV-14:00 | 29.40 | 24.47 | 0.00 | 0.00 | 01-NOV-00:10 | 29.40 | 24.47 |
December | 0.286747E+10 | 11020.87 | 15-DEC-15:00 | 29.00 | 21.56 | 0.00 | 0.00 | 01-DEC-00:10 | 29.00 | 21.56 |
Annual Sum or Average | 0.105861E+12 | 0.00 | ||||||||
Minimum of Months | 0.209665E+10 | 9748.93 | 25.00 | 20.83 | 0.00 | 0.00 | 25.00 | 20.83 | ||
Maximum of Months | 0.152682E+11 | 20443.99 | 34.45 | 26.45 | 0.00 | 0.00 | 34.45 | 26.45 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.402286E+10 | 2052.06 | 01-JAN-17:27 | 22.00 | 18.79 | 95232581.71 | 126.85 | 12-JAN-14:00 | 19.00 | 15.91 |
February | 0.839474E+10 | 4115.35 | 26-FEB-17:42 | 23.48 | 19.39 | 86406041.54 | 126.85 | 28-FEB-10:00 | 22.20 | 19.62 |
March | 0.144437E+11 | 7197.45 | 31-MAR-24:00 | 20.70 | 19.78 | 0.103242E+09 | 126.84 | 07-MAR-10:09 | 20.70 | 19.78 |
April | 0.189954E+11 | 7906.36 | 16-APR-18:10 | 18.43 | 13.27 | 91654201.66 | 129.29 | 28-APR-13:00 | 32.70 | 23.02 |
May | 0.462645E+10 | 3491.61 | 31-MAY-24:00 | 23.00 | 21.40 | 99236232.38 | 126.85 | 08-MAY-13:00 | 23.00 | 21.40 |
June | 0.935289E+10 | 5345.11 | 30-JUN-23:57 | 25.10 | 23.16 | 98982601.12 | 126.87 | 19-JUN-09:09 | 25.10 | 23.16 |
July | 0.147288E+11 | 7222.33 | 31-JUL-23:57 | 25.20 | 23.65 | 91894438.39 | 126.85 | 14-JUL-09:20 | 25.20 | 23.65 |
August | 0.198424E+11 | 7789.06 | 06-AUG-18:00 | 25.00 | 23.59 | 0.105052E+09 | 136.33 | 28-AUG-13:00 | 33.00 | 25.67 |
September | 0.450423E+10 | 3520.03 | 30-SEP-24:00 | 22.30 | 21.22 | 91606025.36 | 126.82 | 22-SEP-09:09 | 22.30 | 21.22 |
October | 0.968260E+10 | 5366.73 | 31-OCT-24:00 | 21.60 | 20.90 | 95249542.69 | 126.88 | 24-OCT-09:30 | 21.60 | 20.90 |
November | 0.141309E+11 | 5953.60 | 06-NOV-17:00 | 26.60 | 19.72 | 94307121.14 | 126.85 | 01-NOV-09:20 | 26.60 | 19.72 |
December | 0.195249E+11 | 7830.98 | 10-DEC-16:54 | 25.00 | 19.63 | 91882435.98 | 126.83 | 28-DEC-10:09 | 18.33 | 18.33 |
Annual Sum or Average | 0.142250E+12 | 0.114475E+10 | ||||||||
Minimum of Months | 0.402286E+10 | 2052.06 | 18.43 | 13.27 | 86406041.54 | 126.82 | 18.33 | 15.91 | ||
Maximum of Months | 0.198424E+11 | 7906.36 | 26.60 | 23.65 | 0.105052E+09 | 136.33 | 33.00 | 25.67 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.288993E+10 | 1855.74 | 18-JAN-17:00 | 22.00 | 19.94 | 95231305.39 | 126.84 | 02-JAN-10:50 | 22.00 | 19.94 |
February | 0.727985E+10 | 3774.27 | 26-FEB-17:54 | 23.30 | 19.29 | 86405408.59 | 126.85 | 24-FEB-14:00 | 23.30 | 19.29 |
March | 0.132181E+11 | 6775.73 | 31-MAR-24:00 | 20.70 | 19.78 | 0.103242E+09 | 126.84 | 07-MAR-14:00 | 20.70 | 19.78 |
April | 0.180191E+11 | 7457.11 | 16-APR-18:10 | 18.43 | 13.27 | 91666820.86 | 130.27 | 28-APR-13:00 | 32.70 | 23.02 |
May | 0.430312E+10 | 3304.87 | 31-MAY-24:00 | 23.00 | 21.40 | 99234505.64 | 126.85 | 03-MAY-13:00 | 23.00 | 21.40 |
June | 0.889764E+10 | 5202.21 | 30-JUN-23:57 | 25.10 | 23.16 | 98981196.38 | 126.86 | 19-JUN-09:09 | 25.10 | 23.16 |
July | 0.140306E+11 | 6956.68 | 31-JUL-23:57 | 25.20 | 23.65 | 91894988.33 | 126.85 | 31-JUL-13:00 | 25.20 | 23.65 |
August | 0.188162E+11 | 7262.04 | 06-AUG-18:10 | 25.00 | 23.59 | 0.105139E+09 | 135.91 | 28-AUG-13:00 | 33.00 | 25.67 |
September | 0.410087E+10 | 3312.39 | 30-SEP-24:00 | 22.30 | 21.22 | 91605454.09 | 126.82 | 05-SEP-13:39 | 22.30 | 21.22 |
October | 0.904887E+10 | 5025.17 | 31-OCT-24:00 | 21.60 | 20.90 | 95248447.57 | 126.87 | 24-OCT-09:20 | 21.60 | 20.90 |
November | 0.130149E+11 | 5638.16 | 06-NOV-17:00 | 26.60 | 19.72 | 94306956.43 | 126.84 | 01-NOV-09:00 | 26.60 | 19.72 |
December | 0.178731E+11 | 7368.55 | 15-DEC-17:00 | 28.00 | 21.24 | 91882307.51 | 126.83 | 28-DEC-10:09 | 18.33 | 18.33 |
Annual Sum or Average | 0.131492E+12 | 0.114484E+10 | ||||||||
Minimum of Months | 0.288993E+10 | 1855.74 | 18.43 | 13.27 | 86405408.59 | 126.82 | 18.33 | 18.33 | ||
Maximum of Months | 0.188162E+11 | 7457.11 | 28.00 | 23.65 | 0.105139E+09 | 135.91 | 33.00 | 25.67 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.191250E+10 | 1905.45 | 19-JAN-17:00 | 24.00 | 20.62 | 95152088.18 | 126.84 | 02-JAN-14:09 | 24.00 | 20.62 |
February | 0.651988E+10 | 3796.23 | 26-FEB-17:42 | 23.48 | 19.39 | 86405574.66 | 126.85 | 24-FEB-14:00 | 23.48 | 19.39 |
March | 0.126758E+11 | 6671.83 | 31-MAR-24:00 | 20.70 | 19.78 | 0.103242E+09 | 126.85 | 07-MAR-14:00 | 20.70 | 19.78 |
April | 0.178941E+11 | 7640.94 | 23-APR-18:08 | 25.13 | 21.19 | 91645258.59 | 128.54 | 28-APR-13:00 | 32.70 | 23.02 |
May | 0.440921E+10 | 3268.37 | 31-MAY-24:00 | 23.00 | 21.40 | 99235595.90 | 126.85 | 08-MAY-13:00 | 23.00 | 21.40 |
June | 0.901576E+10 | 5231.75 | 30-JUN-23:57 | 25.10 | 23.16 | 98982517.33 | 126.87 | 01-JUN-13:09 | 25.10 | 23.16 |
July | 0.141630E+11 | 6940.03 | 31-JUL-23:57 | 25.20 | 23.65 | 91895686.84 | 126.85 | 31-JUL-13:00 | 25.20 | 23.65 |
August | 0.189362E+11 | 7506.99 | 06-AUG-17:40 | 25.33 | 23.69 | 0.104404E+09 | 134.41 | 28-AUG-13:00 | 33.00 | 25.67 |
September | 0.418582E+10 | 3354.81 | 30-SEP-24:00 | 22.30 | 21.22 | 91605555.65 | 126.82 | 05-SEP-13:39 | 22.30 | 21.22 |
October | 0.899440E+10 | 4967.20 | 31-OCT-24:00 | 21.60 | 20.90 | 95249176.71 | 126.87 | 24-OCT-13:00 | 21.60 | 20.90 |
November | 0.125636E+11 | 5697.61 | 06-NOV-17:00 | 26.60 | 19.72 | 94307275.39 | 126.85 | 01-NOV-09:00 | 26.60 | 19.72 |
December | 0.170788E+11 | 7431.07 | 15-DEC-17:00 | 28.00 | 21.24 | 91882643.81 | 126.83 | 28-DEC-14:20 | 19.33 | 19.33 |
Annual Sum or Average | 0.128349E+12 | 0.114401E+10 | ||||||||
Minimum of Months | 0.191250E+10 | 1905.45 | 20.70 | 19.39 | 86405574.66 | 126.82 | 19.33 | 19.33 | ||
Maximum of Months | 0.189362E+11 | 7640.94 | 28.00 | 23.69 | 0.104404E+09 | 134.41 | 33.00 | 25.67 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.240798E+12 | 92998.12 | 02-JAN-17:00 | 26.00 | 18.38 | 0.206180E+10 | 2746.99 | 10-JAN-10:09 | 7.33 | 2.79 |
February | 0.436995E+12 | 183714.69 | 27-FEB-17:00 | 24.40 | 20.28 | 0.187059E+10 | 2747.74 | 13-FEB-14:09 | 24.40 | 20.28 |
March | 0.728776E+12 | 358582.23 | 31-MAR-24:00 | 20.70 | 19.78 | 0.223496E+10 | 2747.57 | 09-MAR-10:09 | 20.70 | 19.78 |
April | 0.940594E+12 | 367523.33 | 28-APR-21:02 | 23.82 | 23.08 | 0.204340E+10 | 3335.60 | 28-APR-13:00 | 23.82 | 23.08 |
May | 0.240801E+12 | 175679.32 | 31-MAY-24:00 | 23.00 | 21.40 | 0.214903E+10 | 2747.22 | 22-MAY-13:00 | 23.00 | 21.40 |
June | 0.469290E+12 | 267329.23 | 30-JUN-23:57 | 25.10 | 23.16 | 0.214280E+10 | 2746.58 | 01-JUN-13:09 | 25.10 | 23.16 |
July | 0.731501E+12 | 359638.50 | 31-JUL-23:53 | 25.20 | 23.65 | 0.198925E+10 | 2745.93 | 12-JUL-13:30 | 25.20 | 23.65 |
August | 0.972797E+12 | 371126.47 | 09-AUG-21:13 | 23.27 | 22.90 | 0.260630E+10 | 3584.01 | 28-AUG-13:00 | 33.00 | 25.67 |
September | 0.236881E+12 | 176634.57 | 30-SEP-24:00 | 22.30 | 21.22 | 0.198397E+10 | 2747.19 | 18-SEP-13:00 | 22.30 | 21.22 |
October | 0.488655E+12 | 268703.72 | 31-OCT-24:00 | 21.60 | 20.90 | 0.206196E+10 | 2746.76 | 24-OCT-09:30 | 21.60 | 20.90 |
November | 0.709669E+12 | 276635.21 | 06-NOV-17:00 | 26.60 | 19.72 | 0.204148E+10 | 2746.47 | 22-NOV-14:50 | 19.32 | 9.14 |
December | 0.977605E+12 | 368064.53 | 26-DEC-17:00 | 12.70 | 5.60 | 0.201565E+10 | 3142.64 | 13-DEC-14:00 | 12.70 | 5.60 |
Annual Sum or Average | 0.717436E+13 | 0.252012E+11 | ||||||||
Minimum of Months | 0.236881E+12 | 92998.12 | 12.70 | 5.60 | 0.187059E+10 | 2745.93 | 7.33 | 2.79 | ||
Maximum of Months | 0.977605E+12 | 371126.47 | 26.60 | 23.65 | 0.260630E+10 | 3584.01 | 33.00 | 25.67 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.389851E+09 | 11609.52 | 09-JAN-04:07 | 8.83 |
February | 0.282664E+09 | 12651.45 | 20-FEB-18:13 | 19.93 |
March | 0.226493E+09 | 12330.33 | 22-MAR-03:13 | 9.43 |
April | 0.248526E+09 | 16624.09 | 22-APR-16:02 | 30.08 |
May | 0.383351E+09 | 18580.83 | 27-MAY-16:02 | 31.60 |
June | 0.361605E+09 | 21787.33 | 10-JUN-16:02 | 33.72 |
July | 0.530143E+09 | 25011.20 | 22-JUL-16:02 | 35.92 |
August | 0.456420E+09 | 19357.65 | 26-AUG-16:02 | 32.10 |
September | 0.591552E+09 | 24685.01 | 09-SEP-16:02 | 35.73 |
October | 0.514719E+09 | 18693.11 | 07-OCT-16:02 | 31.58 |
November | 0.464543E+09 | 13228.58 | 02-NOV-03:53 | 23.60 |
December | 0.489818E+09 | 12975.48 | 10-DEC-15:22 | 27.50 |
Annual Sum or Average | 0.493969E+10 | |||
Minimum of Months | 0.226493E+09 | 11609.52 | 8.83 | |
Maximum of Months | 0.591552E+09 | 25011.20 | 35.92 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 17.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 14.12 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 17.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 14.12 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 21849803.10 | 52384.39 | 23-JAN-06:02 | 6.83 |
February | 0.186428E+09 | 58718.53 | 06-FEB-05:01 | 3.03 |
March | 11027137.54 | 51132.42 | 13-MAR-05:03 | 6.68 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 2085987.25 | 21990.12 | 21-DEC-06:01 | 0.83 |
Annual Sum or Average | 0.221391E+09 | |||
Minimum of Months | 0.00 | 0.00 | 0.83 | |
Maximum of Months | 0.186428E+09 | 58718.53 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 17.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 14.12 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 17.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 14.12 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 17.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 14.12 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 17.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 14.12 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.107683E+09 | 10436.38 | 10-JAN-05:01 | 1.33 |
February | 65417805.82 | 10811.09 | 06-FEB-05:01 | 3.03 |
March | 27542948.81 | 9817.05 | 09-MAR-06:02 | 1.10 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 62759350.60 | 10493.39 | 21-DEC-05:01 | 0.17 |
Annual Sum or Average | 0.263403E+09 | |||
Minimum of Months | 0.00 | 0.00 | 0.17 | |
Maximum of Months | 0.107683E+09 | 10811.09 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 38985844.95 | 8888.37 | 10-JAN-06:02 | 3.00 |
February | 22879517.62 | 9471.34 | 06-FEB-05:01 | 3.03 |
March | 11525654.74 | 6652.82 | 11-MAR-06:03 | 6.60 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 33392040.76 | 9306.93 | 21-DEC-05:01 | 0.17 |
Annual Sum or Average | 0.106783E+09 | |||
Minimum of Months | 0.00 | 0.00 | 0.17 | |
Maximum of Months | 38985844.95 | 9471.34 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 8318441.49 | 11917.56 | 10-JAN-06:02 | 3.00 |
February | 6025746.43 | 12066.74 | 06-FEB-06:01 | 2.88 |
March | 2041047.71 | 4715.90 | 11-MAR-06:03 | 6.60 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 17237014.54 | 12098.54 | 21-DEC-06:01 | 0.83 |
Annual Sum or Average | 33622250.17 | |||
Minimum of Months | 0.00 | 0.00 | 0.83 | |
Maximum of Months | 17237014.54 | 12098.54 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 16909615.47 | 8199.59 | 10-JAN-06:02 | 3.00 |
February | 10029344.91 | 8292.87 | 06-FEB-06:01 | 2.88 |
March | 419126.84 | 2464.63 | 11-MAR-06:03 | 6.60 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 14074296.98 | 8305.06 | 21-DEC-06:01 | 0.83 |
Annual Sum or Average | 41432384.19 | |||
Minimum of Months | 0.00 | 0.00 | 0.83 | |
Maximum of Months | 16909615.47 | 8305.06 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.926120E+09 | 13200.75 | 23-JAN-04:03 | 8.00 |
February | 0.566121E+09 | 14470.85 | 05-FEB-07:43 | -3.4 |
March | 0.326631E+09 | 12737.03 | 13-MAR-04:01 | 7.05 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 39581504.96 | 11659.82 | 16-NOV-06:02 | 9.40 |
December | 0.557823E+09 | 12911.10 | 20-DEC-05:01 | 4.67 |
Annual Sum or Average | 0.241628E+10 | |||
Minimum of Months | 0.00 | 0.00 | -3.4 | |
Maximum of Months | 0.926120E+09 | 14470.85 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.364885E+09 | 12048.77 | 05-JAN-05:01 | 0.83 |
February | 0.206928E+09 | 13460.88 | 06-FEB-04:01 | 3.35 |
March | 0.167155E+09 | 11626.80 | 10-MAR-05:02 | 5.83 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 8134511.06 | 10442.54 | 16-NOV-06:02 | 9.40 |
December | 0.269070E+09 | 12070.29 | 21-DEC-05:01 | 0.17 |
Annual Sum or Average | 0.101617E+10 | |||
Minimum of Months | 0.00 | 0.00 | 0.17 | |
Maximum of Months | 0.364885E+09 | 13460.88 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.272133E+09 | 14887.21 | 10-JAN-05:01 | 1.33 |
February | 0.181105E+09 | 15923.28 | 06-FEB-04:01 | 3.35 |
March | 0.191874E+09 | 14342.89 | 11-MAR-05:02 | 7.27 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 7835.57 | 65.30 | 16-NOV-06:04 | 9.40 |
December | 0.184191E+09 | 15116.44 | 21-DEC-05:01 | 0.17 |
Annual Sum or Average | 0.829312E+09 | |||
Minimum of Months | 0.00 | 0.00 | 0.17 | |
Maximum of Months | 0.272133E+09 | 15923.28 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.279142E+09 | 12065.80 | 10-JAN-05:01 | 1.33 |
February | 0.159980E+09 | 12850.81 | 06-FEB-04:01 | 3.35 |
March | 95548271.55 | 10993.00 | 10-MAR-05:02 | 5.83 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 1528477.85 | 3916.14 | 16-NOV-06:02 | 9.40 |
December | 0.143403E+09 | 12123.78 | 21-DEC-05:01 | 0.17 |
Annual Sum or Average | 0.679602E+09 | |||
Minimum of Months | 0.00 | 0.00 | 0.17 | |
Maximum of Months | 0.279142E+09 | 12850.81 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 89445357.58 | 10306.08 | 23-JAN-05:01 | 7.83 |
February | 77436961.55 | 10861.04 | 06-FEB-05:01 | 3.03 |
March | 0.104277E+09 | 10037.05 | 20-MAR-03:02 | 12.55 |
April | 0.111668E+09 | 9737.59 | 10-APR-03:02 | 13.30 |
May | 55285840.82 | 7917.31 | 24-MAY-03:02 | 25.00 |
June | 48222977.10 | 6880.22 | 07-JUN-03:02 | 21.10 |
July | 53549778.41 | 4529.07 | 23-JUL-13:02 | 33.80 |
August | 43739654.01 | 5152.79 | 06-AUG-11:43 | 31.00 |
September | 57354031.08 | 7480.34 | 21-SEP-03:02 | 22.70 |
October | 84147969.14 | 9944.23 | 30-OCT-03:02 | 17.00 |
November | 0.119486E+09 | 10143.13 | 27-NOV-04:02 | 14.30 |
December | 0.158977E+09 | 10890.41 | 21-DEC-05:01 | 0.17 |
Annual Sum or Average | 0.100359E+10 | |||
Minimum of Months | 43739654.01 | 4529.07 | 0.17 | |
Maximum of Months | 0.158977E+09 | 10890.41 | 33.80 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.180705E+09 | 7497.43 | 13-JAN-06:02 | 7.17 |
February | 0.150863E+09 | 7496.93 | 08-FEB-06:02 | 12.10 |
March | 0.113174E+09 | 7399.92 | 20-MAR-03:02 | 12.55 |
April | 39986892.57 | 6611.21 | 10-APR-03:02 | 13.30 |
May | 45947907.20 | 7673.22 | 22-MAY-03:02 | 26.10 |
June | 36771598.36 | 6819.18 | 28-JUN-03:02 | 27.20 |
July | 34262649.31 | 6819.34 | 27-JUL-03:02 | 25.50 |
August | 34539193.02 | 7009.73 | 10-AUG-03:02 | 26.45 |
September | 43326147.10 | 6542.75 | 07-SEP-03:02 | 25.60 |
October | 50494804.84 | 6594.46 | 25-OCT-03:02 | 26.17 |
November | 56063098.23 | 6050.12 | 14-NOV-05:03 | 15.50 |
December | 0.103755E+09 | 7406.21 | 22-DEC-06:03 | 10.00 |
Annual Sum or Average | 0.889890E+09 | |||
Minimum of Months | 34262649.31 | 6050.12 | 7.17 | |
Maximum of Months | 0.180705E+09 | 7673.22 | 27.20 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.193236E+10 | 17053.78 | 03-JAN-06:02 | 2.83 |
February | 0.121520E+10 | 17365.35 | 06-FEB-06:13 | 3.07 |
March | 0.110324E+10 | 16504.86 | 20-MAR-05:03 | 12.10 |
April | 0.238997E+09 | 16222.49 | 11-APR-05:03 | 10.63 |
May | 48414437.68 | 9513.99 | 15-MAY-03:02 | 24.22 |
June | 38421408.56 | 8691.48 | 07-JUN-04:03 | 21.10 |
July | 34245329.08 | 7680.51 | 21-JUL-03:02 | 25.60 |
August | 33892079.89 | 7389.26 | 30-AUG-03:02 | 25.32 |
September | 43186885.11 | 8359.77 | 18-SEP-03:02 | 25.00 |
October | 0.141477E+09 | 13632.79 | 18-OCT-05:03 | 15.17 |
November | 0.478803E+09 | 17405.42 | 09-NOV-06:02 | 10.42 |
December | 0.149097E+10 | 15832.96 | 01-DEC-06:02 | 11.00 |
Annual Sum or Average | 0.679921E+10 | |||
Minimum of Months | 33892079.89 | 7389.26 | 2.83 | |
Maximum of Months | 0.193236E+10 | 17405.42 | 25.60 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 17.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 14.12 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 17.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 14.12 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 87168840.80 | 523.18 | 10-JAN-04:45 | 1.17 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 |
Annual Sum or Average | 87168840.80 | |||
Minimum of Months | 0.00 | 0.00 | 1.17 | |
Maximum of Months | 87168840.80 | 523.18 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 17.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 14.12 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.148304E+11 | 15519.45 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.134523E+11 | 15519.45 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.159851E+11 | 15519.45 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.142779E+11 | 15519.45 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.154078E+11 | 15519.45 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.153333E+11 | 15519.45 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.143524E+11 | 15519.45 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.159851E+11 | 15519.45 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.142779E+11 | 15519.45 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.148304E+11 | 15519.45 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.146566E+11 | 15519.45 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.143524E+11 | 15519.45 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.177742E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.134523E+11 | 15519.45 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.159851E+11 | 15519.45 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.133188E+11 | 13937.56 | 02-JAN-08:09 | 0.270551E+11 | 18128.59 | 02-JAN-08:09 |
February | 0.120811E+11 | 13937.56 | 01-FEB-08:09 | 0.244881E+11 | 18128.59 | 01-FEB-08:09 |
March | 0.143557E+11 | 13937.56 | 01-MAR-08:09 | 0.280558E+11 | 18128.59 | 01-MAR-08:09 |
April | 0.128226E+11 | 13937.56 | 03-APR-07:10 | 0.261305E+11 | 18128.59 | 03-APR-07:10 |
May | 0.138373E+11 | 13937.56 | 01-MAY-07:10 | 0.275555E+11 | 18128.59 | 01-MAY-07:10 |
June | 0.137704E+11 | 13937.56 | 01-JUN-07:10 | 0.270261E+11 | 18128.59 | 01-JUN-07:10 |
July | 0.128895E+11 | 13937.56 | 03-JUL-07:10 | 0.266527E+11 | 18128.59 | 03-JUL-07:10 |
August | 0.143557E+11 | 13937.56 | 01-AUG-07:10 | 0.280558E+11 | 18128.59 | 01-AUG-07:10 |
September | 0.128226E+11 | 13937.56 | 01-SEP-07:10 | 0.261160E+11 | 18128.59 | 01-SEP-07:10 |
October | 0.133188E+11 | 13937.56 | 02-OCT-07:10 | 0.270624E+11 | 18128.59 | 02-OCT-07:10 |
November | 0.131627E+11 | 13937.56 | 01-NOV-07:10 | 0.264424E+11 | 18128.59 | 01-NOV-07:10 |
December | 0.128895E+11 | 13937.56 | 01-DEC-08:09 | 0.266454E+11 | 18128.59 | 01-DEC-08:09 |
Annual Sum or Average | 0.159625E+12 | 0.321286E+12 | ||||
Minimum of Months | 0.120811E+11 | 13937.56 | 0.244881E+11 | 18128.59 | ||
Maximum of Months | 0.143557E+11 | 13937.56 | 0.280558E+11 | 18128.59 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.133188E+11 | 13937.56 | 02-JAN-08:09 | 0.270550E+11 | 18128.52 | 02-JAN-08:09 |
February | 0.120811E+11 | 13937.56 | 01-FEB-08:09 | 0.244880E+11 | 18128.52 | 01-FEB-08:09 |
March | 0.143557E+11 | 13937.56 | 01-MAR-08:09 | 0.280557E+11 | 18128.52 | 01-MAR-08:09 |
April | 0.128226E+11 | 13937.56 | 03-APR-07:10 | 0.261304E+11 | 18128.52 | 03-APR-07:10 |
May | 0.138373E+11 | 13937.56 | 01-MAY-07:10 | 0.275554E+11 | 18128.52 | 01-MAY-07:10 |
June | 0.137704E+11 | 13937.56 | 01-JUN-07:10 | 0.270260E+11 | 18128.52 | 01-JUN-07:10 |
July | 0.128895E+11 | 13937.56 | 03-JUL-07:10 | 0.266526E+11 | 18128.52 | 03-JUL-07:10 |
August | 0.143557E+11 | 13937.56 | 01-AUG-07:10 | 0.280557E+11 | 18128.52 | 01-AUG-07:10 |
September | 0.128226E+11 | 13937.56 | 01-SEP-07:10 | 0.261159E+11 | 18128.52 | 01-SEP-07:10 |
October | 0.133188E+11 | 13937.56 | 02-OCT-07:10 | 0.270623E+11 | 18128.52 | 02-OCT-07:10 |
November | 0.131627E+11 | 13937.56 | 01-NOV-07:10 | 0.264423E+11 | 18128.52 | 01-NOV-07:10 |
December | 0.128895E+11 | 13937.56 | 01-DEC-08:09 | 0.266453E+11 | 18128.52 | 01-DEC-08:09 |
Annual Sum or Average | 0.159625E+12 | 0.321285E+12 | ||||
Minimum of Months | 0.120811E+11 | 13937.56 | 0.244880E+11 | 18128.52 | ||
Maximum of Months | 0.143557E+11 | 13937.56 | 0.280557E+11 | 18128.52 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.133188E+11 | 13937.56 | 02-JAN-08:09 | 0.270550E+11 | 18128.52 | 02-JAN-08:09 |
February | 0.120811E+11 | 13937.56 | 01-FEB-08:09 | 0.244880E+11 | 18128.52 | 01-FEB-08:09 |
March | 0.143557E+11 | 13937.56 | 01-MAR-08:09 | 0.280557E+11 | 18128.52 | 01-MAR-08:09 |
April | 0.128226E+11 | 13937.56 | 03-APR-07:10 | 0.261304E+11 | 18128.52 | 03-APR-07:10 |
May | 0.138373E+11 | 13937.56 | 01-MAY-07:10 | 0.275554E+11 | 18128.52 | 01-MAY-07:10 |
June | 0.137704E+11 | 13937.56 | 01-JUN-07:10 | 0.270260E+11 | 18128.52 | 01-JUN-07:10 |
July | 0.128895E+11 | 13937.56 | 03-JUL-07:10 | 0.266526E+11 | 18128.52 | 03-JUL-07:10 |
August | 0.143557E+11 | 13937.56 | 01-AUG-07:10 | 0.280557E+11 | 18128.52 | 01-AUG-07:10 |
September | 0.128226E+11 | 13937.56 | 01-SEP-07:10 | 0.261159E+11 | 18128.52 | 01-SEP-07:10 |
October | 0.133188E+11 | 13937.56 | 02-OCT-07:10 | 0.270623E+11 | 18128.52 | 02-OCT-07:10 |
November | 0.131627E+11 | 13937.56 | 01-NOV-07:10 | 0.264423E+11 | 18128.52 | 01-NOV-07:10 |
December | 0.128895E+11 | 13937.56 | 01-DEC-08:09 | 0.266453E+11 | 18128.52 | 01-DEC-08:09 |
Annual Sum or Average | 0.159625E+12 | 0.321285E+12 | ||||
Minimum of Months | 0.120811E+11 | 13937.56 | 0.244880E+11 | 18128.52 | ||
Maximum of Months | 0.143557E+11 | 13937.56 | 0.280557E+11 | 18128.52 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.120204E+10 | 1525.96 | 31-JAN-08:09 | 0.339718E+10 | 2276.32 | 02-JAN-08:09 |
February | 0.106348E+10 | 1561.87 | 01-FEB-08:09 | 0.307485E+10 | 2276.32 | 01-FEB-08:09 |
March | 0.123594E+10 | 1477.64 | 27-MAR-07:10 | 0.352283E+10 | 2276.32 | 01-MAR-08:09 |
April | 0.108831E+10 | 1504.27 | 14-APR-07:10 | 0.328108E+10 | 2276.32 | 03-APR-07:10 |
May | 0.115157E+10 | 1243.87 | 23-MAY-07:30 | 0.346000E+10 | 2276.32 | 01-MAY-07:10 |
June | 0.113758E+10 | 1075.02 | 01-JUN-07:10 | 0.339353E+10 | 2276.32 | 01-JUN-07:10 |
July | 0.107202E+10 | 1075.02 | 03-JUL-07:10 | 0.334664E+10 | 2276.32 | 03-JUL-07:10 |
August | 0.120389E+10 | 1276.27 | 21-AUG-07:10 | 0.352283E+10 | 2276.32 | 01-AUG-07:10 |
September | 0.109492E+10 | 1474.55 | 26-SEP-07:10 | 0.327926E+10 | 2276.32 | 01-SEP-07:10 |
October | 0.115663E+10 | 1614.51 | 25-OCT-07:10 | 0.339809E+10 | 2276.32 | 02-OCT-07:10 |
November | 0.118464E+10 | 1570.75 | 01-NOV-07:10 | 0.332024E+10 | 2276.32 | 01-NOV-07:10 |
December | 0.117701E+10 | 1604.50 | 12-DEC-08:09 | 0.334573E+10 | 2276.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.137680E+11 | 0.403423E+11 | ||||
Minimum of Months | 0.106348E+10 | 1075.02 | 0.307485E+10 | 2276.32 | ||
Maximum of Months | 0.123594E+10 | 1614.51 | 0.352283E+10 | 2276.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.766708E+09 | 964.48 | 04-JAN-16:00 | 0.218927E+10 | 1466.95 | 02-JAN-08:09 |
February | 0.681522E+09 | 981.55 | 01-FEB-08:09 | 0.198155E+10 | 1466.95 | 01-FEB-08:09 |
March | 0.792549E+09 | 906.86 | 27-MAR-07:10 | 0.227025E+10 | 1466.95 | 01-MAR-08:09 |
April | 0.701629E+09 | 944.30 | 14-APR-07:10 | 0.211446E+10 | 1466.95 | 03-APR-07:10 |
May | 0.744864E+09 | 802.12 | 30-MAY-15:30 | 0.222976E+10 | 1466.95 | 01-MAY-07:10 |
June | 0.737295E+09 | 692.79 | 01-JUN-07:10 | 0.218692E+10 | 1466.95 | 01-JUN-07:10 |
July | 0.693308E+09 | 692.79 | 03-JUL-07:10 | 0.215670E+10 | 1466.95 | 03-JUL-07:10 |
August | 0.777390E+09 | 692.79 | 01-AUG-07:10 | 0.227025E+10 | 1466.95 | 01-AUG-07:10 |
September | 0.705544E+09 | 902.72 | 26-SEP-07:10 | 0.211328E+10 | 1466.95 | 01-SEP-07:10 |
October | 0.743134E+09 | 1024.08 | 25-OCT-07:10 | 0.218986E+10 | 1466.95 | 02-OCT-07:10 |
November | 0.758148E+09 | 1020.12 | 21-NOV-16:00 | 0.213969E+10 | 1466.95 | 01-NOV-07:10 |
December | 0.753024E+09 | 1024.01 | 12-DEC-08:09 | 0.215612E+10 | 1466.95 | 01-DEC-08:09 |
Annual Sum or Average | 0.885511E+10 | 0.259981E+11 | ||||
Minimum of Months | 0.681522E+09 | 692.79 | 0.198155E+10 | 1466.95 | ||
Maximum of Months | 0.792549E+09 | 1024.08 | 0.227025E+10 | 1466.95 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.116670E+10 | 1493.99 | 31-JAN-08:09 | 0.339723E+10 | 2276.35 | 02-JAN-08:09 |
February | 0.104529E+10 | 1541.87 | 01-FEB-08:09 | 0.307490E+10 | 2276.35 | 01-FEB-08:09 |
March | 0.122724E+10 | 1466.75 | 27-MAR-07:10 | 0.352288E+10 | 2276.35 | 01-MAR-08:09 |
April | 0.109022E+10 | 1508.53 | 14-APR-07:10 | 0.328113E+10 | 2276.35 | 03-APR-07:10 |
May | 0.115830E+10 | 1279.30 | 23-MAY-07:19 | 0.346006E+10 | 2276.35 | 01-MAY-07:10 |
June | 0.114551E+10 | 1075.05 | 01-JUN-07:10 | 0.339359E+10 | 2276.35 | 01-JUN-07:10 |
July | 0.107745E+10 | 1216.90 | 14-JUL-07:10 | 0.334669E+10 | 2276.35 | 03-JUL-07:10 |
August | 0.120708E+10 | 1315.84 | 21-AUG-07:10 | 0.352288E+10 | 2276.35 | 01-AUG-07:10 |
September | 0.109361E+10 | 1471.26 | 26-SEP-07:10 | 0.327931E+10 | 2276.35 | 01-SEP-07:10 |
October | 0.114754E+10 | 1606.21 | 25-OCT-07:10 | 0.339814E+10 | 2276.35 | 02-OCT-07:10 |
November | 0.115278E+10 | 1537.51 | 21-NOV-16:00 | 0.332029E+10 | 2276.35 | 01-NOV-07:10 |
December | 0.114392E+10 | 1592.83 | 12-DEC-08:09 | 0.334578E+10 | 2276.35 | 01-DEC-08:09 |
Annual Sum or Average | 0.136556E+11 | 0.403429E+11 | ||||
Minimum of Months | 0.104529E+10 | 1075.05 | 0.307490E+10 | 2276.35 | ||
Maximum of Months | 0.122724E+10 | 1606.21 | 0.352288E+10 | 2276.35 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.763255E+09 | 994.16 | 31-JAN-08:09 | 0.218926E+10 | 1466.94 | 02-JAN-08:09 |
February | 0.680797E+09 | 1013.27 | 01-FEB-08:09 | 0.198154E+10 | 1466.94 | 01-FEB-08:09 |
March | 0.798371E+09 | 979.22 | 13-MAR-07:10 | 0.227023E+10 | 1466.94 | 01-MAR-08:09 |
April | 0.705034E+09 | 987.18 | 14-APR-07:10 | 0.211444E+10 | 1466.94 | 03-APR-07:10 |
May | 0.746777E+09 | 880.96 | 24-MAY-07:19 | 0.222974E+10 | 1466.94 | 01-MAY-07:10 |
June | 0.736966E+09 | 806.15 | 08-JUN-07:10 | 0.218691E+10 | 1466.94 | 01-JUN-07:10 |
July | 0.693853E+09 | 840.50 | 14-JUL-07:10 | 0.215669E+10 | 1466.94 | 03-JUL-07:10 |
August | 0.779455E+09 | 932.17 | 23-AUG-07:10 | 0.227023E+10 | 1466.94 | 01-AUG-07:10 |
September | 0.709726E+09 | 978.74 | 26-SEP-07:10 | 0.211327E+10 | 1466.94 | 01-SEP-07:10 |
October | 0.745265E+09 | 1047.35 | 25-OCT-07:10 | 0.218984E+10 | 1466.94 | 02-OCT-07:10 |
November | 0.750901E+09 | 1028.27 | 01-NOV-07:10 | 0.213967E+10 | 1466.94 | 01-NOV-07:10 |
December | 0.743145E+09 | 1035.42 | 12-DEC-08:09 | 0.215610E+10 | 1466.94 | 01-DEC-08:09 |
Annual Sum or Average | 0.885355E+10 | 0.259979E+11 | ||||
Minimum of Months | 0.680797E+09 | 806.15 | 0.198154E+10 | 1466.94 | ||
Maximum of Months | 0.798371E+09 | 1047.35 | 0.227023E+10 | 1466.94 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.120479E+10 | 1532.38 | 31-JAN-08:09 | 0.339718E+10 | 2276.32 | 02-JAN-08:09 |
February | 0.106505E+10 | 1567.29 | 01-FEB-08:09 | 0.307485E+10 | 2276.32 | 01-FEB-08:09 |
March | 0.123742E+10 | 1485.74 | 27-MAR-07:10 | 0.352283E+10 | 2276.32 | 01-MAR-08:09 |
April | 0.108886E+10 | 1511.49 | 14-APR-07:10 | 0.328108E+10 | 2276.32 | 03-APR-07:10 |
May | 0.115212E+10 | 1258.37 | 23-MAY-07:30 | 0.346000E+10 | 2276.32 | 01-MAY-07:10 |
June | 0.113803E+10 | 1075.02 | 01-JUN-07:10 | 0.339353E+10 | 2276.32 | 01-JUN-07:10 |
July | 0.107254E+10 | 1075.02 | 03-JUL-07:10 | 0.334664E+10 | 2276.32 | 03-JUL-07:10 |
August | 0.120457E+10 | 1290.21 | 21-AUG-07:10 | 0.352283E+10 | 2276.32 | 01-AUG-07:10 |
September | 0.109571E+10 | 1482.63 | 26-SEP-07:10 | 0.327926E+10 | 2276.32 | 01-SEP-07:10 |
October | 0.115779E+10 | 1618.48 | 25-OCT-07:10 | 0.339809E+10 | 2276.32 | 02-OCT-07:10 |
November | 0.118683E+10 | 1575.96 | 01-NOV-07:10 | 0.332024E+10 | 2276.32 | 01-NOV-07:10 |
December | 0.118026E+10 | 1608.72 | 12-DEC-08:09 | 0.334573E+10 | 2276.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.137840E+11 | 0.403423E+11 | ||||
Minimum of Months | 0.106505E+10 | 1075.02 | 0.307485E+10 | 2276.32 | ||
Maximum of Months | 0.123742E+10 | 1618.48 | 0.352283E+10 | 2276.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.767014E+09 | 967.16 | 04-JAN-16:00 | 0.218927E+10 | 1466.95 | 02-JAN-08:09 |
February | 0.681866E+09 | 983.28 | 01-FEB-08:09 | 0.198155E+10 | 1466.95 | 01-FEB-08:09 |
March | 0.792801E+09 | 910.38 | 27-MAR-07:10 | 0.227025E+10 | 1466.95 | 01-MAR-08:09 |
April | 0.701849E+09 | 946.98 | 14-APR-07:10 | 0.211446E+10 | 1466.95 | 03-APR-07:10 |
May | 0.745063E+09 | 802.93 | 30-MAY-15:30 | 0.222976E+10 | 1466.95 | 01-MAY-07:10 |
June | 0.737501E+09 | 692.79 | 01-JUN-07:10 | 0.218692E+10 | 1466.95 | 01-JUN-07:10 |
July | 0.693493E+09 | 692.79 | 03-JUL-07:10 | 0.215670E+10 | 1466.95 | 03-JUL-07:10 |
August | 0.777547E+09 | 692.79 | 01-AUG-07:10 | 0.227025E+10 | 1466.95 | 01-AUG-07:10 |
September | 0.705781E+09 | 906.63 | 26-SEP-07:10 | 0.211328E+10 | 1466.95 | 01-SEP-07:10 |
October | 0.743436E+09 | 1025.37 | 25-OCT-07:10 | 0.218986E+10 | 1466.95 | 02-OCT-07:10 |
November | 0.758636E+09 | 1020.96 | 21-NOV-16:00 | 0.213969E+10 | 1466.95 | 01-NOV-07:10 |
December | 0.753544E+09 | 1025.04 | 12-DEC-08:09 | 0.215612E+10 | 1466.95 | 01-DEC-08:09 |
Annual Sum or Average | 0.885853E+10 | 0.259981E+11 | ||||
Minimum of Months | 0.681866E+09 | 692.79 | 0.198155E+10 | 1466.95 | ||
Maximum of Months | 0.792801E+09 | 1025.37 | 0.227025E+10 | 1466.95 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.116698E+10 | 1501.73 | 31-JAN-08:09 | 0.339723E+10 | 2276.35 | 02-JAN-08:09 |
February | 0.104565E+10 | 1548.12 | 01-FEB-08:09 | 0.307490E+10 | 2276.35 | 01-FEB-08:09 |
March | 0.122793E+10 | 1475.31 | 27-MAR-07:10 | 0.352288E+10 | 2276.35 | 01-MAR-08:09 |
April | 0.109097E+10 | 1515.58 | 14-APR-07:10 | 0.328113E+10 | 2276.35 | 03-APR-07:10 |
May | 0.115908E+10 | 1292.50 | 23-MAY-07:19 | 0.346006E+10 | 2276.35 | 01-MAY-07:10 |
June | 0.114622E+10 | 1075.05 | 01-JUN-07:10 | 0.339359E+10 | 2276.35 | 01-JUN-07:10 |
July | 0.107810E+10 | 1231.65 | 14-JUL-07:10 | 0.334669E+10 | 2276.35 | 03-JUL-07:10 |
August | 0.120792E+10 | 1328.20 | 21-AUG-07:10 | 0.352288E+10 | 2276.35 | 01-AUG-07:10 |
September | 0.109413E+10 | 1479.46 | 26-SEP-07:10 | 0.327931E+10 | 2276.35 | 01-SEP-07:10 |
October | 0.114833E+10 | 1610.53 | 25-OCT-07:10 | 0.339814E+10 | 2276.35 | 02-OCT-07:10 |
November | 0.115465E+10 | 1544.28 | 21-NOV-16:00 | 0.332029E+10 | 2276.35 | 01-NOV-07:10 |
December | 0.114514E+10 | 1597.59 | 12-DEC-08:09 | 0.334578E+10 | 2276.35 | 01-DEC-08:09 |
Annual Sum or Average | 0.136651E+11 | 0.403429E+11 | ||||
Minimum of Months | 0.104565E+10 | 1075.05 | 0.307490E+10 | 2276.35 | ||
Maximum of Months | 0.122793E+10 | 1610.53 | 0.352288E+10 | 2276.35 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.763666E+09 | 995.18 | 31-JAN-08:09 | 0.218926E+10 | 1466.94 | 02-JAN-08:09 |
February | 0.681145E+09 | 1014.13 | 01-FEB-08:09 | 0.198154E+10 | 1466.94 | 01-FEB-08:09 |
March | 0.798827E+09 | 982.49 | 13-MAR-07:10 | 0.227023E+10 | 1466.94 | 01-MAR-08:09 |
April | 0.705414E+09 | 988.22 | 14-APR-07:10 | 0.211444E+10 | 1466.94 | 03-APR-07:10 |
May | 0.747044E+09 | 882.49 | 24-MAY-07:10 | 0.222974E+10 | 1466.94 | 01-MAY-07:10 |
June | 0.737198E+09 | 809.54 | 08-JUN-07:10 | 0.218691E+10 | 1466.94 | 01-JUN-07:10 |
July | 0.694042E+09 | 842.63 | 14-JUL-07:10 | 0.215669E+10 | 1466.94 | 03-JUL-07:10 |
August | 0.779708E+09 | 933.98 | 23-AUG-07:10 | 0.227023E+10 | 1466.94 | 01-AUG-07:10 |
September | 0.709997E+09 | 979.85 | 26-SEP-07:10 | 0.211327E+10 | 1466.94 | 01-SEP-07:10 |
October | 0.745661E+09 | 1047.95 | 25-OCT-07:10 | 0.218984E+10 | 1466.94 | 02-OCT-07:10 |
November | 0.751503E+09 | 1029.08 | 01-NOV-07:10 | 0.213967E+10 | 1466.94 | 01-NOV-07:10 |
December | 0.743465E+09 | 1036.12 | 12-DEC-08:09 | 0.215610E+10 | 1466.94 | 01-DEC-08:09 |
Annual Sum or Average | 0.885767E+10 | 0.259979E+11 | ||||
Minimum of Months | 0.681145E+09 | 809.54 | 0.198154E+10 | 1466.94 | ||
Maximum of Months | 0.798827E+09 | 1047.95 | 0.227023E+10 | 1466.94 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.120489E+10 | 1532.18 | 31-JAN-08:09 | 0.339718E+10 | 2276.32 | 02-JAN-08:09 |
February | 0.106506E+10 | 1567.12 | 01-FEB-08:09 | 0.307485E+10 | 2276.32 | 01-FEB-08:09 |
March | 0.123743E+10 | 1485.53 | 27-MAR-07:10 | 0.352283E+10 | 2276.32 | 01-MAR-08:09 |
April | 0.108886E+10 | 1511.27 | 14-APR-07:10 | 0.328108E+10 | 2276.32 | 03-APR-07:10 |
May | 0.115214E+10 | 1257.95 | 23-MAY-07:30 | 0.346000E+10 | 2276.32 | 01-MAY-07:10 |
June | 0.113803E+10 | 1075.02 | 01-JUN-07:10 | 0.339353E+10 | 2276.32 | 01-JUN-07:10 |
July | 0.107254E+10 | 1075.02 | 03-JUL-07:10 | 0.334664E+10 | 2276.32 | 03-JUL-07:10 |
August | 0.120457E+10 | 1289.92 | 21-AUG-07:10 | 0.352283E+10 | 2276.32 | 01-AUG-07:10 |
September | 0.109571E+10 | 1482.42 | 26-SEP-07:10 | 0.327926E+10 | 2276.32 | 01-SEP-07:10 |
October | 0.115779E+10 | 1618.36 | 25-OCT-07:10 | 0.339809E+10 | 2276.32 | 02-OCT-07:10 |
November | 0.118686E+10 | 1575.84 | 01-NOV-07:10 | 0.332024E+10 | 2276.32 | 01-NOV-07:10 |
December | 0.118021E+10 | 1608.57 | 12-DEC-08:09 | 0.334573E+10 | 2276.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.137841E+11 | 0.403423E+11 | ||||
Minimum of Months | 0.106506E+10 | 1075.02 | 0.307485E+10 | 2276.32 | ||
Maximum of Months | 0.123743E+10 | 1618.36 | 0.352283E+10 | 2276.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.767035E+09 | 967.35 | 04-JAN-16:00 | 0.218927E+10 | 1466.95 | 02-JAN-08:09 |
February | 0.681879E+09 | 983.20 | 01-FEB-08:09 | 0.198155E+10 | 1466.95 | 01-FEB-08:09 |
March | 0.792807E+09 | 910.31 | 27-MAR-07:10 | 0.227025E+10 | 1466.95 | 01-MAR-08:09 |
April | 0.701864E+09 | 946.87 | 14-APR-07:10 | 0.211446E+10 | 1466.95 | 03-APR-07:10 |
May | 0.745062E+09 | 802.83 | 30-MAY-15:30 | 0.222976E+10 | 1466.95 | 01-MAY-07:10 |
June | 0.737499E+09 | 692.79 | 01-JUN-07:10 | 0.218692E+10 | 1466.95 | 01-JUN-07:10 |
July | 0.693476E+09 | 692.79 | 03-JUL-07:10 | 0.215670E+10 | 1466.95 | 03-JUL-07:10 |
August | 0.777547E+09 | 692.79 | 01-AUG-07:10 | 0.227025E+10 | 1466.95 | 01-AUG-07:10 |
September | 0.705780E+09 | 906.55 | 26-SEP-07:10 | 0.211328E+10 | 1466.95 | 01-SEP-07:10 |
October | 0.743439E+09 | 1025.32 | 25-OCT-07:10 | 0.218986E+10 | 1466.95 | 02-OCT-07:10 |
November | 0.758653E+09 | 1020.87 | 21-NOV-16:00 | 0.213969E+10 | 1466.95 | 01-NOV-07:10 |
December | 0.753522E+09 | 1024.95 | 12-DEC-08:09 | 0.215612E+10 | 1466.95 | 01-DEC-08:09 |
Annual Sum or Average | 0.885856E+10 | 0.259981E+11 | ||||
Minimum of Months | 0.681879E+09 | 692.79 | 0.198155E+10 | 1466.95 | ||
Maximum of Months | 0.792807E+09 | 1025.32 | 0.227025E+10 | 1466.95 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.116698E+10 | 1501.54 | 31-JAN-08:09 | 0.339723E+10 | 2276.35 | 02-JAN-08:09 |
February | 0.104565E+10 | 1547.95 | 01-FEB-08:09 | 0.307490E+10 | 2276.35 | 01-FEB-08:09 |
March | 0.122794E+10 | 1475.11 | 27-MAR-07:10 | 0.352288E+10 | 2276.35 | 01-MAR-08:09 |
April | 0.109096E+10 | 1515.36 | 14-APR-07:10 | 0.328113E+10 | 2276.35 | 03-APR-07:10 |
May | 0.115908E+10 | 1292.11 | 23-MAY-07:19 | 0.346006E+10 | 2276.35 | 01-MAY-07:10 |
June | 0.114624E+10 | 1075.05 | 01-JUN-07:10 | 0.339359E+10 | 2276.35 | 01-JUN-07:10 |
July | 0.107809E+10 | 1231.28 | 14-JUL-07:10 | 0.334669E+10 | 2276.35 | 03-JUL-07:10 |
August | 0.120791E+10 | 1327.90 | 21-AUG-07:10 | 0.352288E+10 | 2276.35 | 01-AUG-07:10 |
September | 0.109412E+10 | 1479.25 | 26-SEP-07:10 | 0.327931E+10 | 2276.35 | 01-SEP-07:10 |
October | 0.114833E+10 | 1610.41 | 25-OCT-07:10 | 0.339814E+10 | 2276.35 | 02-OCT-07:10 |
November | 0.115466E+10 | 1544.14 | 21-NOV-16:00 | 0.332029E+10 | 2276.35 | 01-NOV-07:10 |
December | 0.114514E+10 | 1597.44 | 12-DEC-08:09 | 0.334578E+10 | 2276.35 | 01-DEC-08:09 |
Annual Sum or Average | 0.136651E+11 | 0.403429E+11 | ||||
Minimum of Months | 0.104565E+10 | 1075.05 | 0.307490E+10 | 2276.35 | ||
Maximum of Months | 0.122794E+10 | 1610.41 | 0.352288E+10 | 2276.35 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.763685E+09 | 995.06 | 31-JAN-08:09 | 0.218926E+10 | 1466.94 | 02-JAN-08:09 |
February | 0.681196E+09 | 1014.02 | 01-FEB-08:09 | 0.198154E+10 | 1466.94 | 01-FEB-08:09 |
March | 0.798839E+09 | 982.68 | 13-MAR-07:10 | 0.227023E+10 | 1466.94 | 01-MAR-08:09 |
April | 0.705422E+09 | 988.08 | 14-APR-07:10 | 0.211444E+10 | 1466.94 | 03-APR-07:10 |
May | 0.747045E+09 | 882.37 | 24-MAY-07:10 | 0.222974E+10 | 1466.94 | 01-MAY-07:10 |
June | 0.737200E+09 | 809.89 | 08-JUN-07:10 | 0.218691E+10 | 1466.94 | 01-JUN-07:10 |
July | 0.694040E+09 | 842.40 | 14-JUL-07:10 | 0.215669E+10 | 1466.94 | 03-JUL-07:10 |
August | 0.779707E+09 | 933.96 | 23-AUG-07:10 | 0.227023E+10 | 1466.94 | 01-AUG-07:10 |
September | 0.709994E+09 | 979.71 | 26-SEP-07:10 | 0.211327E+10 | 1466.94 | 01-SEP-07:10 |
October | 0.745663E+09 | 1047.88 | 25-OCT-07:10 | 0.218984E+10 | 1466.94 | 02-OCT-07:10 |
November | 0.751516E+09 | 1029.01 | 01-NOV-07:10 | 0.213967E+10 | 1466.94 | 01-NOV-07:10 |
December | 0.743472E+09 | 1036.02 | 12-DEC-08:09 | 0.215610E+10 | 1466.94 | 01-DEC-08:09 |
Annual Sum or Average | 0.885778E+10 | 0.259979E+11 | ||||
Minimum of Months | 0.681196E+09 | 809.89 | 0.198154E+10 | 1466.94 | ||
Maximum of Months | 0.798839E+09 | 1047.88 | 0.227023E+10 | 1466.94 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.387117E+09 | 405.10 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.351144E+09 | 405.10 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.417256E+09 | 405.10 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.372695E+09 | 405.10 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.402187E+09 | 405.10 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.400242E+09 | 405.10 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.374640E+09 | 405.10 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.417256E+09 | 405.10 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.372695E+09 | 405.10 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.387117E+09 | 405.10 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.382580E+09 | 405.10 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.374640E+09 | 405.10 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.463957E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.351144E+09 | 405.10 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.417256E+09 | 405.10 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.387117E+09 | 405.10 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.351144E+09 | 405.10 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.417256E+09 | 405.10 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.372695E+09 | 405.10 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.402187E+09 | 405.10 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.400242E+09 | 405.10 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.374640E+09 | 405.10 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.417256E+09 | 405.10 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.372695E+09 | 405.10 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.387117E+09 | 405.10 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.382580E+09 | 405.10 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.374640E+09 | 405.10 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.463957E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.351144E+09 | 405.10 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.417256E+09 | 405.10 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.387117E+09 | 405.10 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.351144E+09 | 405.10 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.417256E+09 | 405.10 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.372695E+09 | 405.10 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.402187E+09 | 405.10 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.400242E+09 | 405.10 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.374640E+09 | 405.10 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.417256E+09 | 405.10 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.372695E+09 | 405.10 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.387117E+09 | 405.10 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.382580E+09 | 405.10 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.374640E+09 | 405.10 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.463957E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.351144E+09 | 405.10 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.417256E+09 | 405.10 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.418155E+10 | 4375.82 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.379298E+10 | 4375.82 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.450711E+10 | 4375.82 | 01-MAR-08:09 | 0.762947E+12 | 379632.52 | 31-MAR-23:10 |
April | 0.402577E+10 | 4375.82 | 03-APR-07:10 | 0.982982E+12 | 379632.52 | 01-APR-00:10 |
May | 0.434433E+10 | 4375.82 | 01-MAY-07:10 | 0.254544E+12 | 189816.26 | 31-MAY-23:10 |
June | 0.432333E+10 | 4375.82 | 01-JUN-07:10 | 0.492345E+12 | 284724.39 | 30-JUN-23:10 |
July | 0.404678E+10 | 4375.82 | 03-JUL-07:10 | 0.762947E+12 | 379632.52 | 31-JUL-23:10 |
August | 0.450711E+10 | 4375.82 | 01-AUG-07:10 | 0.101578E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.402577E+10 | 4375.82 | 01-SEP-07:10 | 0.246344E+12 | 189816.26 | 30-SEP-23:10 |
October | 0.418155E+10 | 4375.82 | 02-OCT-07:10 | 0.508746E+12 | 284724.39 | 31-OCT-23:10 |
November | 0.413254E+10 | 4375.82 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.404678E+10 | 4375.82 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.501156E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.379298E+10 | 4375.82 | 0.246344E+12 | 94908.13 | ||
Maximum of Months | 0.450711E+10 | 4375.82 | 0.101681E+13 | 379632.52 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.148304E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.134523E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.159851E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.142779E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.154078E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.153333E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.143524E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.159851E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.142779E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.148304E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.146566E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.143524E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.177742E+12 | 0.424397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121482E+11 | 0.134523E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.159851E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.133188E+11 | 0.270551E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.120811E+11 | 0.244881E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.143557E+11 | 0.280558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.128226E+11 | 0.261305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.138373E+11 | 0.275555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.137704E+11 | 0.270261E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.128895E+11 | 0.266527E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.143557E+11 | 0.280558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.128226E+11 | 0.261160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.133188E+11 | 0.270624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.131627E+11 | 0.264424E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.128895E+11 | 0.266454E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.159625E+12 | 0.321286E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.120811E+11 | 0.244881E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.143557E+11 | 0.280558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.133188E+11 | 0.270550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.120811E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.143557E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.128226E+11 | 0.261304E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.138373E+11 | 0.275554E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.137704E+11 | 0.270260E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.128895E+11 | 0.266526E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.143557E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.128226E+11 | 0.261159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.133188E+11 | 0.270623E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.131627E+11 | 0.264423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.128895E+11 | 0.266453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.159625E+12 | 0.321285E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.120811E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.143557E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.133188E+11 | 0.270550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.120811E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.143557E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.128226E+11 | 0.261304E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.138373E+11 | 0.275554E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.137704E+11 | 0.270260E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.128895E+11 | 0.266526E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.143557E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.128226E+11 | 0.261159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.133188E+11 | 0.270623E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.131627E+11 | 0.264423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.128895E+11 | 0.266453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.159625E+12 | 0.321285E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.120811E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.143557E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.120204E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 974161.34 | 0.375169E+09 |
February | 0.136985E+10 | 0.106348E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1921699.49 | 0.291296E+09 |
March | 0.163685E+10 | 0.123594E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5951757.09 | 0.305302E+09 |
April | 0.145243E+10 | 0.108831E+10 | 0.328108E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12543804.67 | 0.128619E+09 |
May | 0.157338E+10 | 0.115157E+10 | 0.346000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53549439.09 | 19246284.17 |
June | 0.156900E+10 | 0.113758E+10 | 0.339353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49977927.57 | 11948972.17 |
July | 0.145680E+10 | 0.107202E+10 | 0.334664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 71341319.32 | 2894365.39 |
August | 0.163685E+10 | 0.120389E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69467745.92 | 12923222.95 |
September | 0.145243E+10 | 0.109492E+10 | 0.327926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60316856.77 | 32441257.98 |
October | 0.150991E+10 | 0.115663E+10 | 0.339809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48859971.58 | 0.109399E+09 |
November | 0.149516E+10 | 0.118464E+10 | 0.332024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5177065.44 | 0.193813E+09 |
December | 0.145680E+10 | 0.117701E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3359680.51 | 0.341095E+09 |
Annual Sum or Average | 0.181194E+11 | 0.137680E+11 | 0.403423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.383441E+09 | 0.182415E+10 |
Minimum of Months | 0.136985E+10 | 0.106348E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 974161.34 | 2894365.39 |
Maximum of Months | 0.163685E+10 | 0.123594E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 71341319.32 | 0.375169E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.766708E+09 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 549070.00 | 0.255973E+09 |
February | 0.882782E+09 | 0.681522E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1171627.62 | 0.196977E+09 |
March | 0.105485E+10 | 0.792549E+09 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3547424.65 | 0.202162E+09 |
April | 0.936002E+09 | 0.701629E+09 | 0.211446E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8375031.05 | 83373641.87 |
May | 0.101394E+10 | 0.744864E+09 | 0.222976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35120518.58 | 12534009.69 |
June | 0.101113E+10 | 0.737295E+09 | 0.218692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34088494.32 | 6796704.99 |
July | 0.938820E+09 | 0.693308E+09 | 0.215670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50171084.46 | 1286581.58 |
August | 0.105485E+10 | 0.777390E+09 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49809547.81 | 5779293.91 |
September | 0.936002E+09 | 0.705544E+09 | 0.211328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38812840.27 | 20977691.77 |
October | 0.973041E+09 | 0.743134E+09 | 0.218986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31662502.53 | 71285483.66 |
November | 0.963541E+09 | 0.758148E+09 | 0.213969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3220874.71 | 0.128968E+09 |
December | 0.938820E+09 | 0.753024E+09 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2125436.72 | 0.221250E+09 |
Annual Sum or Average | 0.116768E+11 | 0.885511E+10 | 0.259981E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258654E+09 | 0.120736E+10 |
Minimum of Months | 0.882782E+09 | 0.681522E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 549070.00 | 1286581.58 |
Maximum of Months | 0.105485E+10 | 0.792549E+09 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50171084.46 | 0.255973E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.116670E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 646326.54 | 0.406076E+09 |
February | 0.136988E+10 | 0.104529E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1505366.13 | 0.310251E+09 |
March | 0.163688E+10 | 0.122724E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4619351.13 | 0.312857E+09 |
April | 0.145246E+10 | 0.109022E+10 | 0.328113E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11346228.08 | 0.133595E+09 |
May | 0.157341E+10 | 0.115830E+10 | 0.346006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53153281.28 | 19501705.95 |
June | 0.156904E+10 | 0.114551E+10 | 0.339359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50484432.79 | 11684805.54 |
July | 0.145684E+10 | 0.107745E+10 | 0.334669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 71345453.03 | 2945049.45 |
August | 0.163688E+10 | 0.120708E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67694736.07 | 13842605.76 |
September | 0.145246E+10 | 0.109361E+10 | 0.327931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55283859.02 | 36551894.76 |
October | 0.150994E+10 | 0.114754E+10 | 0.339814E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41535091.46 | 0.127190E+09 |
November | 0.149520E+10 | 0.115278E+10 | 0.332029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4062273.64 | 0.213157E+09 |
December | 0.145684E+10 | 0.114392E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2627015.42 | 0.365604E+09 |
Annual Sum or Average | 0.181198E+11 | 0.136556E+11 | 0.403429E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.364303E+09 | 0.195326E+10 |
Minimum of Months | 0.136988E+10 | 0.104529E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 646326.54 | 2945049.45 |
Maximum of Months | 0.163688E+10 | 0.122724E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 71345453.03 | 0.406076E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.763255E+09 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 488738.48 | 0.275048E+09 |
February | 0.882782E+09 | 0.680797E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1051079.53 | 0.219534E+09 |
March | 0.105485E+10 | 0.798371E+09 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3192466.83 | 0.236287E+09 |
April | 0.936002E+09 | 0.705034E+09 | 0.211444E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6841098.56 | 0.110037E+09 |
May | 0.101394E+10 | 0.746777E+09 | 0.222974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33671834.80 | 20140208.85 |
June | 0.101113E+10 | 0.736966E+09 | 0.218691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30019315.94 | 13709422.98 |
July | 0.938820E+09 | 0.693853E+09 | 0.215669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40246142.41 | 6145390.78 |
August | 0.105485E+10 | 0.779455E+09 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39580037.62 | 20221112.52 |
September | 0.936002E+09 | 0.709726E+09 | 0.211327E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36714561.84 | 30521968.28 |
October | 0.973041E+09 | 0.745265E+09 | 0.218984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28293582.44 | 94100481.20 |
November | 0.963541E+09 | 0.750901E+09 | 0.213967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2807817.76 | 0.152905E+09 |
December | 0.938820E+09 | 0.743145E+09 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1799612.96 | 0.269114E+09 |
Annual Sum or Average | 0.116768E+11 | 0.885355E+10 | 0.259979E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224706E+09 | 0.144776E+10 |
Minimum of Months | 0.882782E+09 | 0.680797E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 488738.48 | 6145390.78 |
Maximum of Months | 0.105485E+10 | 0.798371E+09 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40246142.41 | 0.275048E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.120479E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4448082.49 | 0.761386E+09 |
February | 0.136985E+10 | 0.106505E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5804147.70 | 0.585739E+09 |
March | 0.163685E+10 | 0.123742E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16455130.57 | 0.635373E+09 |
April | 0.145243E+10 | 0.108886E+10 | 0.328108E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29045569.87 | 0.291214E+09 |
May | 0.157338E+10 | 0.115212E+10 | 0.346000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119009E+09 | 52609521.04 |
June | 0.156900E+10 | 0.113803E+10 | 0.339353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109291E+09 | 39609051.98 |
July | 0.145680E+10 | 0.107254E+10 | 0.334664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153591E+09 | 17101076.31 |
August | 0.163685E+10 | 0.120457E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149488E+09 | 51788699.24 |
September | 0.145243E+10 | 0.109571E+10 | 0.327926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138119E+09 | 78781674.45 |
October | 0.150991E+10 | 0.115779E+10 | 0.339809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112585E+09 | 0.246803E+09 |
November | 0.149516E+10 | 0.118683E+10 | 0.332024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14656280.32 | 0.401139E+09 |
December | 0.145680E+10 | 0.118026E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9893478.65 | 0.686839E+09 |
Annual Sum or Average | 0.181194E+11 | 0.137840E+11 | 0.403423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.862384E+09 | 0.384838E+10 |
Minimum of Months | 0.136985E+10 | 0.106505E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4448082.49 | 17101076.31 |
Maximum of Months | 0.163685E+10 | 0.123742E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153591E+09 | 0.761386E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.767014E+09 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1575387.72 | 0.541079E+09 |
February | 0.649041E+09 | 0.681866E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2877929.32 | 0.417141E+09 |
March | 0.773965E+09 | 0.792801E+09 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7894946.02 | 0.448751E+09 |
April | 0.688021E+09 | 0.701849E+09 | 0.211446E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17682546.12 | 0.210961E+09 |
May | 0.744847E+09 | 0.745063E+09 | 0.222976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75095513.63 | 39204555.10 |
June | 0.742030E+09 | 0.737501E+09 | 0.218692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 71409726.09 | 28303762.68 |
July | 0.690839E+09 | 0.693493E+09 | 0.215670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 98217113.83 | 13665038.41 |
August | 0.773965E+09 | 0.777547E+09 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 96829241.67 | 37592015.30 |
September | 0.688021E+09 | 0.705781E+09 | 0.211328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 85731844.59 | 57149953.01 |
October | 0.715730E+09 | 0.743436E+09 | 0.218986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67559050.99 | 0.177395E+09 |
November | 0.708685E+09 | 0.758636E+09 | 0.213969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7397771.34 | 0.288394E+09 |
December | 0.690839E+09 | 0.753544E+09 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4908674.25 | 0.478611E+09 |
Annual Sum or Average | 0.858171E+10 | 0.885853E+10 | 0.259981E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.537180E+09 | 0.273825E+10 |
Minimum of Months | 0.649041E+09 | 0.681866E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1575387.72 | 13665038.41 |
Maximum of Months | 0.773965E+09 | 0.792801E+09 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 98217113.83 | 0.541079E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.116698E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1227508.23 | 0.921348E+09 |
February | 0.136988E+10 | 0.104565E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3246596.79 | 0.693118E+09 |
March | 0.163688E+10 | 0.122793E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10182470.50 | 0.694737E+09 |
April | 0.145246E+10 | 0.109097E+10 | 0.328113E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25909459.06 | 0.316644E+09 |
May | 0.157341E+10 | 0.115908E+10 | 0.346006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118622E+09 | 53532424.13 |
June | 0.156904E+10 | 0.114622E+10 | 0.339359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111450E+09 | 38132014.39 |
July | 0.145684E+10 | 0.107810E+10 | 0.334669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154879E+09 | 16756390.42 |
August | 0.163688E+10 | 0.120792E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145446E+09 | 55658366.87 |
September | 0.145246E+10 | 0.109413E+10 | 0.327931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124368E+09 | 92808362.69 |
October | 0.150994E+10 | 0.114833E+10 | 0.339814E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 92249178.65 | 0.313285E+09 |
November | 0.149520E+10 | 0.115465E+10 | 0.332029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8955093.77 | 0.488879E+09 |
December | 0.145684E+10 | 0.114514E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5812238.77 | 0.825546E+09 |
Annual Sum or Average | 0.181198E+11 | 0.136651E+11 | 0.403429E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.802348E+09 | 0.451044E+10 |
Minimum of Months | 0.136988E+10 | 0.104565E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1227508.23 | 16756390.42 |
Maximum of Months | 0.163688E+10 | 0.122793E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154879E+09 | 0.921348E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.763666E+09 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1582889.58 | 0.559223E+09 |
February | 0.882782E+09 | 0.681145E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2766428.34 | 0.429307E+09 |
March | 0.105485E+10 | 0.798827E+09 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8773075.64 | 0.462709E+09 |
April | 0.936002E+09 | 0.705414E+09 | 0.211444E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16002039.32 | 0.228453E+09 |
May | 0.101394E+10 | 0.747044E+09 | 0.222974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76347307.22 | 45522098.53 |
June | 0.101113E+10 | 0.737198E+09 | 0.218691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68984337.45 | 35391388.40 |
July | 0.938820E+09 | 0.694042E+09 | 0.215669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 95109090.46 | 18778687.34 |
August | 0.105485E+10 | 0.779708E+09 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 94580140.01 | 48552032.83 |
September | 0.936002E+09 | 0.709997E+09 | 0.211327E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84146588.75 | 67037038.56 |
October | 0.973041E+09 | 0.745661E+09 | 0.218984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67466756.98 | 0.199664E+09 |
November | 0.963541E+09 | 0.751503E+09 | 0.213967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7699429.82 | 0.298351E+09 |
December | 0.938820E+09 | 0.743465E+09 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5030779.47 | 0.509061E+09 |
Annual Sum or Average | 0.116768E+11 | 0.885767E+10 | 0.259979E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.528489E+09 | 0.290205E+10 |
Minimum of Months | 0.882782E+09 | 0.681145E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1582889.58 | 18778687.34 |
Maximum of Months | 0.105485E+10 | 0.798827E+09 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 95109090.46 | 0.559223E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.120489E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7124180.21 | 0.849127E+09 |
February | 0.136985E+10 | 0.106506E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7720923.37 | 0.652873E+09 |
March | 0.163685E+10 | 0.123743E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19439840.86 | 0.732220E+09 |
April | 0.145243E+10 | 0.108886E+10 | 0.328108E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33049585.49 | 0.349322E+09 |
May | 0.157338E+10 | 0.115214E+10 | 0.346000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138917E+09 | 71274894.11 |
June | 0.156900E+10 | 0.113803E+10 | 0.339353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127935E+09 | 54275388.23 |
July | 0.145680E+10 | 0.107254E+10 | 0.334664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174672E+09 | 25687395.55 |
August | 0.163685E+10 | 0.120457E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174986E+09 | 69910712.59 |
September | 0.145243E+10 | 0.109571E+10 | 0.327926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157492E+09 | 0.104441E+09 |
October | 0.150991E+10 | 0.115779E+10 | 0.339809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128565E+09 | 0.296083E+09 |
November | 0.149516E+10 | 0.118686E+10 | 0.332024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17719653.91 | 0.459338E+09 |
December | 0.145680E+10 | 0.118021E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13414787.99 | 0.777718E+09 |
Annual Sum or Average | 0.181194E+11 | 0.137841E+11 | 0.403423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100104E+10 | 0.444227E+10 |
Minimum of Months | 0.136985E+10 | 0.106506E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7124180.21 | 25687395.55 |
Maximum of Months | 0.163685E+10 | 0.123743E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174986E+09 | 0.849127E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.767035E+09 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2413020.69 | 0.606798E+09 |
February | 0.882782E+09 | 0.681879E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3434814.44 | 0.467456E+09 |
March | 0.105485E+10 | 0.792807E+09 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8917658.49 | 0.524865E+09 |
April | 0.936002E+09 | 0.701864E+09 | 0.211446E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20190029.00 | 0.256364E+09 |
May | 0.101394E+10 | 0.745062E+09 | 0.222976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 89264052.01 | 52410847.19 |
June | 0.101113E+10 | 0.737499E+09 | 0.218692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84239476.96 | 38535369.62 |
July | 0.938820E+09 | 0.693476E+09 | 0.215670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113623E+09 | 19724702.02 |
August | 0.105485E+10 | 0.777547E+09 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114485E+09 | 50340854.41 |
September | 0.936002E+09 | 0.705780E+09 | 0.211328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100070E+09 | 75436027.77 |
October | 0.973041E+09 | 0.743439E+09 | 0.218986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78793789.22 | 0.214519E+09 |
November | 0.963541E+09 | 0.758653E+09 | 0.213969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8483792.10 | 0.336962E+09 |
December | 0.938820E+09 | 0.753522E+09 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5974341.10 | 0.546402E+09 |
Annual Sum or Average | 0.116768E+11 | 0.885856E+10 | 0.259981E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.629890E+09 | 0.318981E+10 |
Minimum of Months | 0.882782E+09 | 0.681879E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2413020.69 | 19724702.02 |
Maximum of Months | 0.105485E+10 | 0.792807E+09 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114485E+09 | 0.606798E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.116698E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1453228.26 | 0.105780E+10 |
February | 0.136988E+10 | 0.104565E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3767432.52 | 0.785850E+09 |
March | 0.163688E+10 | 0.122794E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11881572.49 | 0.811434E+09 |
April | 0.145246E+10 | 0.109096E+10 | 0.328113E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29678866.01 | 0.383323E+09 |
May | 0.157341E+10 | 0.115908E+10 | 0.346006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138744E+09 | 72530632.77 |
June | 0.156904E+10 | 0.114624E+10 | 0.339359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129941E+09 | 52491431.21 |
July | 0.145684E+10 | 0.107809E+10 | 0.334669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176414E+09 | 25144358.98 |
August | 0.163688E+10 | 0.120791E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171510E+09 | 75107001.06 |
September | 0.145246E+10 | 0.109412E+10 | 0.327931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146266E+09 | 0.122645E+09 |
October | 0.150994E+10 | 0.114833E+10 | 0.339814E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109530E+09 | 0.385110E+09 |
November | 0.149520E+10 | 0.115466E+10 | 0.332029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10767721.50 | 0.582516E+09 |
December | 0.145684E+10 | 0.114514E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6896469.22 | 0.958832E+09 |
Annual Sum or Average | 0.181198E+11 | 0.136651E+11 | 0.403429E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.936850E+09 | 0.531278E+10 |
Minimum of Months | 0.136988E+10 | 0.104565E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1453228.26 | 25144358.98 |
Maximum of Months | 0.163688E+10 | 0.122794E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176414E+09 | 0.105780E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.763685E+09 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2268054.90 | 0.639381E+09 |
February | 0.882782E+09 | 0.681196E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3366380.00 | 0.489028E+09 |
March | 0.105485E+10 | 0.798839E+09 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10499933.05 | 0.541874E+09 |
April | 0.936002E+09 | 0.705422E+09 | 0.211444E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18970839.01 | 0.276669E+09 |
May | 0.101394E+10 | 0.747045E+09 | 0.222974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 91678204.14 | 58977943.17 |
June | 0.101113E+10 | 0.737200E+09 | 0.218691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 82919143.89 | 46350694.09 |
July | 0.938820E+09 | 0.694040E+09 | 0.215669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112768E+09 | 24916743.96 |
August | 0.105485E+10 | 0.779707E+09 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113350E+09 | 63058548.28 |
September | 0.936002E+09 | 0.709994E+09 | 0.211327E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100468E+09 | 86265376.53 |
October | 0.973041E+09 | 0.745663E+09 | 0.218984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 80051193.22 | 0.241770E+09 |
November | 0.963541E+09 | 0.751516E+09 | 0.213967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9424909.19 | 0.349874E+09 |
December | 0.938820E+09 | 0.743472E+09 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6353001.42 | 0.587914E+09 |
Annual Sum or Average | 0.116768E+11 | 0.885778E+10 | 0.259979E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.632118E+09 | 0.340608E+10 |
Minimum of Months | 0.882782E+09 | 0.681196E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2268054.90 | 24916743.96 |
Maximum of Months | 0.105485E+10 | 0.798839E+09 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113350E+09 | 0.639381E+09 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.387117E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.351144E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.417256E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.372695E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.402187E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.400242E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.374640E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.417256E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.372695E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.387117E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.382580E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.374640E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.463957E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.351144E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.417256E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.387117E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.351144E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.417256E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.372695E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.402187E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.400242E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.374640E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.417256E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.372695E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.387117E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.382580E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.374640E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.463957E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.351144E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.417256E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.387117E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.351144E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.417256E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.372695E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.402187E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.400242E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.374640E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.417256E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.372695E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.387117E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.382580E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.374640E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.463957E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.351144E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.417256E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.377547E+10 | 0.418155E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.342526E+10 | 0.379298E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409289E+10 | 0.450711E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363176E+10 | 0.402577E+10 | 0.982982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.393418E+10 | 0.434433E+10 | 0.254544E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.392325E+10 | 0.432333E+10 | 0.492345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.364269E+10 | 0.404678E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.409289E+10 | 0.450711E+10 | 0.101578E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.363176E+10 | 0.402577E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.377547E+10 | 0.418155E+10 | 0.508746E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373861E+10 | 0.413254E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364269E+10 | 0.404678E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453069E+11 | 0.501156E+11 | 0.749486E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.342526E+10 | 0.379298E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.409289E+10 | 0.450711E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 756616.99 | 0.831277E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2105378.49 | 0.642694E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8465324.97 | 0.663163E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19872015.22 | 0.287452E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96284671.94 | 36334020.21 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89668350.85 | 27884009.65 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133522E+09 | 8964353.71 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121910E+09 | 37255899.35 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107992E+09 | 69111371.37 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82794927.72 | 0.250326E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7146446.06 | 0.430944E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4675997.62 | 0.752936E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.675194E+09 | 0.403834E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 756616.99 | 8964353.71 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133522E+09 | 0.831277E+09 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2457497.91 | 0.141169E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4751408.35 | 0.108941E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18121804.62 | 0.113401E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36170905.58 | 0.504331E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171254E+09 | 66827058.93 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157965E+09 | 53479403.91 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239734E+09 | 17590643.05 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216997E+09 | 72785163.98 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198877E+09 | 0.120467E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149844E+09 | 0.435246E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14385621.44 | 0.736413E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9451998.33 | 0.126568E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122001E+10 | 0.690793E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2457497.91 | 17590643.05 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239734E+09 | 0.141169E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1339814.18 | 0.141611E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1887338.76 | 0.109397E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9655160.32 | 0.120211E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24535461.27 | 0.576125E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150044E+09 | 91778973.87 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144173E+09 | 69147311.57 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209851E+09 | 29863348.02 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203402E+09 | 94892426.91 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182470E+09 | 0.148711E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121525E+09 | 0.483314E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10035417.17 | 0.767395E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6972336.08 | 0.129296E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106589E+10 | 0.726638E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1339814.18 | 29863348.02 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209851E+09 | 0.141611E+10 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 15519.45 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 15519.45 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 15519.45 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 15519.45 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 15519.45 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 15519.45 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 15519.45 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 15519.45 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 15519.45 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 15519.45 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 15519.45 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 15519.45 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 17832.21 | 15519.45 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 15519.45 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 13937.56 | 02-JAN-08:09 | 18128.59 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 13937.56 | 01-FEB-08:09 | 18128.59 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 13937.56 | 01-MAR-08:09 | 18128.59 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 13937.56 | 03-APR-07:10 | 18128.59 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 13937.56 | 01-MAY-07:10 | 18128.59 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 13937.56 | 01-JUN-07:10 | 18128.59 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 13937.56 | 03-JUL-07:10 | 18128.59 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 13937.56 | 01-AUG-07:10 | 18128.59 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 13937.56 | 01-SEP-07:10 | 18128.59 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 13937.56 | 02-OCT-07:10 | 18128.59 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 13937.56 | 01-NOV-07:10 | 18128.59 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 13937.56 | 01-DEC-08:09 | 18128.59 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 13937.56 | 18128.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 13937.56 | 18128.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 13937.56 | 02-JAN-08:09 | 18128.52 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 13937.56 | 01-FEB-08:09 | 18128.52 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 13937.56 | 01-MAR-08:09 | 18128.52 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 13937.56 | 03-APR-07:10 | 18128.52 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 13937.56 | 01-MAY-07:10 | 18128.52 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 13937.56 | 01-JUN-07:10 | 18128.52 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 13937.56 | 03-JUL-07:10 | 18128.52 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 13937.56 | 01-AUG-07:10 | 18128.52 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 13937.56 | 01-SEP-07:10 | 18128.52 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 13937.56 | 02-OCT-07:10 | 18128.52 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 13937.56 | 01-NOV-07:10 | 18128.52 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 13937.56 | 01-DEC-08:09 | 18128.52 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 13937.56 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 13937.56 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 13937.56 | 02-JAN-08:09 | 18128.52 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 13937.56 | 01-FEB-08:09 | 18128.52 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 13937.56 | 01-MAR-08:09 | 18128.52 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 13937.56 | 03-APR-07:10 | 18128.52 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 13937.56 | 01-MAY-07:10 | 18128.52 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 13937.56 | 01-JUN-07:10 | 18128.52 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 13937.56 | 03-JUL-07:10 | 18128.52 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 13937.56 | 01-AUG-07:10 | 18128.52 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 13937.56 | 01-SEP-07:10 | 18128.52 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 13937.56 | 02-OCT-07:10 | 18128.52 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 13937.56 | 01-NOV-07:10 | 18128.52 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 13937.56 | 01-DEC-08:09 | 18128.52 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 13937.56 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 13937.56 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1525.96 | 31-JAN-08:09 | 2276.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 46.24 | 16-JAN-15:00 | 698.19 | 09-JAN-05:00 |
February | 2010.79 | 01-FEB-10:09 | 1561.87 | 01-FEB-08:09 | 2276.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 49.90 | 02-FEB-13:00 | 978.72 | 05-FEB-08:00 |
March | 2010.79 | 01-MAR-10:09 | 1477.64 | 27-MAR-07:10 | 2276.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 98.99 | 05-MAR-12:53 | 846.44 | 20-MAR-22:00 |
April | 2010.79 | 03-APR-09:09 | 1504.27 | 14-APR-07:10 | 2276.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 151.52 | 29-APR-17:02 | 518.20 | 01-APR-21:00 |
May | 2010.79 | 01-MAY-09:09 | 1243.87 | 23-MAY-07:30 | 2276.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 231.51 | 21-MAY-13:53 | 109.60 | 09-MAY-02:00 |
June | 2010.79 | 01-JUN-09:09 | 1075.02 | 01-JUN-07:10 | 2276.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 267.85 | 10-JUN-17:02 | 157.66 | 06-JUN-22:00 |
July | 2010.79 | 03-JUL-09:09 | 1075.02 | 03-JUL-07:10 | 2276.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 233.11 | 22-JUL-18:50 | 92.62 | 30-JUL-11:00 |
August | 2010.79 | 01-AUG-09:09 | 1276.27 | 21-AUG-07:10 | 2276.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 329.70 | 20-AUG-14:00 | 191.82 | 25-AUG-24:00 |
September | 2010.79 | 01-SEP-09:09 | 1474.55 | 26-SEP-07:10 | 2276.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 320.63 | 09-SEP-17:02 | 198.99 | 05-SEP-03:00 |
October | 2010.79 | 02-OCT-09:09 | 1614.51 | 25-OCT-07:10 | 2276.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 368.55 | 09-OCT-14:00 | 420.55 | 29-OCT-02:00 |
November | 2010.79 | 01-NOV-09:09 | 1570.75 | 01-NOV-07:10 | 2276.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 62.66 | 05-NOV-13:10 | 602.79 | 12-NOV-08:00 |
December | 2010.79 | 01-DEC-10:09 | 1604.50 | 12-DEC-08:09 | 2276.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 58.01 | 10-DEC-15:10 | 911.51 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 46.24 | 92.62 | |||||
Maximum of Months | 2010.79 | 1614.51 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 368.55 | 978.72 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 964.48 | 04-JAN-16:00 | 1466.95 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 24.82 | 16-JAN-15:00 | 463.20 | 22-JAN-08:00 |
February | 1295.83 | 01-FEB-10:09 | 981.55 | 01-FEB-08:09 | 1466.95 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 33.27 | 02-FEB-13:00 | 682.79 | 05-FEB-10:00 |
March | 1295.83 | 01-MAR-10:09 | 906.86 | 27-MAR-07:10 | 1466.95 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 57.14 | 05-MAR-13:00 | 557.34 | 20-MAR-22:00 |
April | 1295.83 | 03-APR-09:09 | 944.30 | 14-APR-07:10 | 1466.95 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 105.57 | 29-APR-17:02 | 335.10 | 01-APR-21:00 |
May | 1295.83 | 01-MAY-09:09 | 802.12 | 30-MAY-15:30 | 1466.95 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 171.81 | 21-MAY-13:53 | 75.13 | 14-MAY-12:10 |
June | 1295.83 | 01-JUN-09:09 | 692.79 | 01-JUN-07:10 | 1466.95 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 187.98 | 10-JUN-17:02 | 100.47 | 06-JUN-22:00 |
July | 1295.83 | 03-JUL-09:09 | 692.79 | 03-JUL-07:10 | 1466.95 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 164.82 | 22-JUL-18:50 | 88.66 | 30-JUL-11:00 |
August | 1295.83 | 01-AUG-09:09 | 692.79 | 01-AUG-07:10 | 1466.95 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 222.80 | 20-AUG-14:00 | 117.72 | 25-AUG-24:00 |
September | 1295.83 | 01-SEP-09:09 | 902.72 | 26-SEP-07:10 | 1466.95 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 216.84 | 09-SEP-22:53 | 130.97 | 05-SEP-03:00 |
October | 1295.83 | 02-OCT-09:09 | 1024.08 | 25-OCT-07:10 | 1466.95 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 237.46 | 09-OCT-13:40 | 277.39 | 29-OCT-02:00 |
November | 1295.83 | 01-NOV-09:09 | 1020.12 | 21-NOV-16:00 | 1466.95 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.49 | 05-NOV-13:10 | 451.88 | 12-NOV-08:30 |
December | 1295.83 | 01-DEC-10:09 | 1024.01 | 12-DEC-08:09 | 1466.95 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 38.68 | 10-DEC-15:10 | 587.06 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 24.82 | 75.13 | |||||
Maximum of Months | 1295.83 | 1024.08 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 237.46 | 682.79 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1493.99 | 31-JAN-08:09 | 2276.35 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 18.32 | 19-JAN-12:10 | 721.06 | 26-JAN-03:00 |
February | 2010.83 | 01-FEB-10:09 | 1541.87 | 01-FEB-08:09 | 2276.35 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 49.90 | 02-FEB-13:00 | 974.68 | 05-FEB-08:00 |
March | 2010.83 | 01-MAR-10:09 | 1466.75 | 27-MAR-07:10 | 2276.35 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 70.79 | 26-MAR-13:48 | 857.71 | 20-MAR-22:00 |
April | 2010.83 | 03-APR-09:09 | 1508.53 | 14-APR-07:10 | 2276.35 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 133.25 | 29-APR-17:02 | 526.89 | 01-APR-21:00 |
May | 2010.83 | 01-MAY-09:09 | 1279.30 | 23-MAY-07:19 | 2276.35 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 228.31 | 21-MAY-13:53 | 110.27 | 09-MAY-02:00 |
June | 2010.83 | 01-JUN-09:09 | 1075.05 | 01-JUN-07:10 | 2276.35 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 275.78 | 10-JUN-17:02 | 156.68 | 06-JUN-22:00 |
July | 2010.83 | 03-JUL-09:09 | 1216.90 | 14-JUL-07:10 | 2276.35 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 237.07 | 22-JUL-18:50 | 100.00 | 30-JUL-11:00 |
August | 2010.83 | 01-AUG-09:09 | 1315.84 | 21-AUG-07:10 | 2276.35 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 325.24 | 20-AUG-14:00 | 195.07 | 25-AUG-24:00 |
September | 2010.83 | 01-SEP-09:09 | 1471.26 | 26-SEP-07:10 | 2276.35 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 304.72 | 09-SEP-17:02 | 212.48 | 05-SEP-03:00 |
October | 2010.83 | 02-OCT-09:09 | 1606.21 | 25-OCT-07:10 | 2276.35 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 341.60 | 09-OCT-14:00 | 441.31 | 29-OCT-02:00 |
November | 2010.83 | 01-NOV-09:09 | 1537.51 | 21-NOV-16:00 | 2276.35 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.10 | 07-NOV-13:00 | 656.35 | 12-NOV-08:10 |
December | 2010.83 | 01-DEC-10:09 | 1592.83 | 12-DEC-08:09 | 2276.35 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 36.30 | 13-DEC-14:00 | 899.22 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1075.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 18.32 | 100.00 | |||||
Maximum of Months | 2010.83 | 1606.21 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 341.60 | 974.68 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 994.16 | 31-JAN-08:09 | 1466.94 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 12.22 | 19-JAN-12:10 | 501.19 | 26-JAN-03:00 |
February | 1295.83 | 01-FEB-10:09 | 1013.27 | 01-FEB-08:09 | 1466.94 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 33.27 | 02-FEB-13:00 | 692.41 | 05-FEB-07:55 |
March | 1295.83 | 01-MAR-10:09 | 979.22 | 13-MAR-07:10 | 1466.94 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 53.97 | 26-MAR-13:48 | 628.99 | 20-MAR-22:00 |
April | 1295.83 | 03-APR-09:09 | 987.18 | 14-APR-07:10 | 1466.94 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.24 | 29-APR-17:07 | 427.75 | 01-APR-21:00 |
May | 1295.83 | 01-MAY-09:09 | 880.96 | 24-MAY-07:19 | 1466.94 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 158.40 | 21-MAY-13:53 | 96.23 | 09-MAY-02:00 |
June | 1295.83 | 01-JUN-09:09 | 806.15 | 08-JUN-07:10 | 1466.94 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 162.78 | 10-JUN-17:08 | 147.06 | 06-JUN-22:00 |
July | 1295.83 | 03-JUL-09:09 | 840.50 | 14-JUL-07:10 | 1466.94 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 137.12 | 16-JUL-15:14 | 94.88 | 30-JUL-11:00 |
August | 1295.83 | 01-AUG-09:09 | 932.17 | 23-AUG-07:10 | 1466.94 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 210.19 | 20-AUG-14:00 | 177.29 | 25-AUG-24:00 |
September | 1295.83 | 01-SEP-09:09 | 978.74 | 26-SEP-07:10 | 1466.94 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 196.43 | 09-SEP-17:08 | 153.06 | 13-SEP-02:50 |
October | 1295.83 | 02-OCT-09:09 | 1047.35 | 25-OCT-07:10 | 1466.94 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 230.45 | 09-OCT-13:36 | 328.67 | 29-OCT-02:00 |
November | 1295.83 | 01-NOV-09:09 | 1028.27 | 01-NOV-07:10 | 1466.94 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.82 | 07-NOV-13:00 | 443.74 | 12-NOV-08:00 |
December | 1295.83 | 01-DEC-10:09 | 1035.42 | 12-DEC-08:09 | 1466.94 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 24.20 | 13-DEC-14:00 | 694.56 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 806.15 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 12.22 | 94.88 | |||||
Maximum of Months | 1295.83 | 1047.35 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 230.45 | 694.56 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1532.38 | 31-JAN-08:09 | 2276.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 173.59 | 16-JAN-15:00 | 1453.54 | 21-JAN-05:55 |
February | 2010.79 | 01-FEB-10:09 | 1567.29 | 01-FEB-08:09 | 2276.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 207.59 | 20-FEB-14:53 | 1978.03 | 05-FEB-07:55 |
March | 2010.79 | 01-MAR-10:09 | 1485.74 | 27-MAR-07:10 | 2276.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 306.42 | 05-MAR-12:43 | 1780.29 | 20-MAR-22:00 |
April | 2010.79 | 03-APR-09:09 | 1511.49 | 14-APR-07:10 | 2276.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 382.90 | 29-APR-17:02 | 1051.03 | 01-APR-21:00 |
May | 2010.79 | 01-MAY-09:09 | 1258.37 | 23-MAY-07:30 | 2276.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 496.42 | 07-MAY-13:53 | 233.90 | 09-MAY-02:00 |
June | 2010.79 | 01-JUN-09:09 | 1075.02 | 01-JUN-07:10 | 2276.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 632.00 | 10-JUN-17:02 | 324.29 | 06-JUN-22:00 |
July | 2010.79 | 03-JUL-09:09 | 1075.02 | 03-JUL-07:10 | 2276.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 545.60 | 22-JUL-18:50 | 208.13 | 30-JUL-11:00 |
August | 2010.79 | 01-AUG-09:09 | 1290.21 | 21-AUG-07:10 | 2276.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 725.46 | 20-AUG-14:00 | 465.54 | 25-AUG-23:53 |
September | 2010.79 | 01-SEP-09:09 | 1482.63 | 26-SEP-07:10 | 2276.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 751.83 | 09-SEP-17:02 | 480.87 | 05-SEP-02:55 |
October | 2010.79 | 02-OCT-09:09 | 1618.48 | 25-OCT-07:10 | 2276.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 848.78 | 09-OCT-14:00 | 840.97 | 29-OCT-02:00 |
November | 2010.79 | 01-NOV-09:09 | 1575.96 | 01-NOV-07:10 | 2276.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 204.47 | 05-NOV-13:00 | 1259.20 | 12-NOV-06:55 |
December | 2010.79 | 01-DEC-10:09 | 1608.72 | 12-DEC-08:09 | 2276.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 181.85 | 10-DEC-14:50 | 1792.49 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 173.59 | 208.13 | |||||
Maximum of Months | 2010.79 | 1618.48 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 848.78 | 1978.03 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 967.16 | 04-JAN-16:00 | 1466.95 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 87.34 | 16-JAN-15:00 | 966.54 | 21-JAN-05:55 |
February | 1239.33 | 01-FEB-08:09 | 983.28 | 01-FEB-08:09 | 1466.95 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 113.35 | 20-FEB-14:53 | 1403.18 | 05-FEB-08:00 |
March | 1239.33 | 01-MAR-08:09 | 910.38 | 27-MAR-07:10 | 1466.95 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 133.20 | 05-MAR-13:10 | 1209.40 | 20-MAR-22:00 |
April | 1239.33 | 03-APR-07:10 | 946.98 | 14-APR-07:10 | 1466.95 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 240.07 | 29-APR-17:02 | 723.68 | 01-APR-21:00 |
May | 1239.33 | 01-MAY-07:10 | 802.93 | 30-MAY-15:30 | 1466.95 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 316.60 | 21-MAY-13:40 | 198.65 | 14-MAY-12:10 |
June | 1239.33 | 01-JUN-07:10 | 692.79 | 01-JUN-07:10 | 1466.95 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 431.09 | 10-JUN-17:02 | 222.58 | 06-JUN-22:00 |
July | 1239.33 | 03-JUL-07:10 | 692.79 | 03-JUL-07:10 | 1466.95 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 362.53 | 22-JUL-18:50 | 243.53 | 30-JUL-11:00 |
August | 1239.33 | 01-AUG-07:10 | 692.79 | 01-AUG-07:10 | 1466.95 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 483.53 | 20-AUG-14:00 | 319.81 | 25-AUG-23:53 |
September | 1239.33 | 01-SEP-07:10 | 906.63 | 26-SEP-07:10 | 1466.95 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 502.97 | 09-SEP-17:02 | 338.48 | 05-SEP-02:55 |
October | 1239.33 | 02-OCT-07:10 | 1025.37 | 25-OCT-07:10 | 1466.95 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 585.73 | 09-OCT-13:56 | 580.48 | 29-OCT-02:00 |
November | 1239.33 | 01-NOV-07:10 | 1020.96 | 21-NOV-16:00 | 1466.95 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 97.80 | 05-NOV-13:00 | 974.64 | 12-NOV-08:40 |
December | 1239.33 | 01-DEC-08:09 | 1025.04 | 12-DEC-08:09 | 1466.95 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 91.43 | 10-DEC-14:55 | 1201.14 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1239.33 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 87.34 | 198.65 | |||||
Maximum of Months | 1239.33 | 1025.37 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 585.73 | 1403.18 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1501.73 | 31-JAN-08:09 | 2276.35 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 38.49 | 19-JAN-12:10 | 1583.02 | 26-JAN-03:00 |
February | 2010.83 | 01-FEB-10:09 | 1548.12 | 01-FEB-08:09 | 2276.35 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 114.07 | 02-FEB-13:00 | 2105.80 | 05-FEB-08:00 |
March | 2010.83 | 01-MAR-10:09 | 1475.31 | 27-MAR-07:10 | 2276.35 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 161.33 | 26-MAR-13:48 | 1862.17 | 20-MAR-22:00 |
April | 2010.83 | 03-APR-09:09 | 1515.58 | 14-APR-07:10 | 2276.35 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 330.72 | 29-APR-17:02 | 1113.00 | 01-APR-21:00 |
May | 2010.83 | 01-MAY-09:09 | 1292.50 | 23-MAY-07:19 | 2276.35 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 465.46 | 07-MAY-13:53 | 240.96 | 09-MAY-02:00 |
June | 2010.83 | 01-JUN-09:09 | 1075.05 | 01-JUN-07:10 | 2276.35 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 650.69 | 10-JUN-17:02 | 325.83 | 06-JUN-22:00 |
July | 2010.83 | 03-JUL-09:09 | 1231.65 | 14-JUL-07:10 | 2276.35 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 558.40 | 22-JUL-18:50 | 216.70 | 30-JUL-11:00 |
August | 2010.83 | 01-AUG-09:09 | 1328.20 | 21-AUG-07:10 | 2276.35 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 725.31 | 20-AUG-14:00 | 478.22 | 25-AUG-23:53 |
September | 2010.83 | 01-SEP-09:09 | 1479.46 | 26-SEP-07:10 | 2276.35 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 709.26 | 09-SEP-17:02 | 519.82 | 05-SEP-02:55 |
October | 2010.83 | 02-OCT-09:09 | 1610.53 | 25-OCT-07:10 | 2276.35 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 780.85 | 09-OCT-14:00 | 972.95 | 29-OCT-02:00 |
November | 2010.83 | 01-NOV-09:09 | 1544.28 | 21-NOV-16:00 | 2276.35 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.05 | 07-NOV-13:00 | 1431.70 | 12-NOV-08:00 |
December | 2010.83 | 01-DEC-10:09 | 1597.59 | 12-DEC-08:09 | 2276.35 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 83.27 | 13-DEC-14:00 | 1889.38 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1075.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 38.49 | 216.70 | |||||
Maximum of Months | 2010.83 | 1610.53 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 780.85 | 2105.80 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 995.18 | 31-JAN-08:09 | 1466.94 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 60.11 | 16-JAN-13:00 | 998.79 | 26-JAN-03:00 |
February | 1295.83 | 01-FEB-10:09 | 1014.13 | 01-FEB-08:09 | 1466.94 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 76.05 | 02-FEB-13:00 | 1350.26 | 05-FEB-07:55 |
March | 1295.83 | 01-MAR-10:09 | 982.49 | 13-MAR-07:10 | 1466.94 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 178.65 | 05-MAR-12:43 | 1254.75 | 20-MAR-22:00 |
April | 1295.83 | 03-APR-09:09 | 988.22 | 14-APR-07:10 | 1466.94 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 138.05 | 29-APR-17:07 | 791.53 | 01-APR-17:55 |
May | 1295.83 | 01-MAY-09:09 | 882.49 | 24-MAY-07:10 | 1466.94 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 321.36 | 21-MAY-14:00 | 202.27 | 06-MAY-20:00 |
June | 1295.83 | 01-JUN-09:09 | 809.54 | 08-JUN-07:10 | 1466.94 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 373.96 | 10-JUN-17:08 | 256.54 | 06-JUN-22:00 |
July | 1295.83 | 03-JUL-09:09 | 842.63 | 14-JUL-07:10 | 1466.94 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 328.29 | 16-JUL-13:00 | 176.83 | 31-JUL-02:70 |
August | 1295.83 | 01-AUG-09:09 | 933.98 | 23-AUG-07:10 | 1466.94 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 483.54 | 20-AUG-14:00 | 353.86 | 25-AUG-23:53 |
September | 1295.83 | 01-SEP-09:09 | 979.85 | 26-SEP-07:10 | 1466.94 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 455.01 | 09-SEP-17:08 | 354.48 | 05-SEP-02:55 |
October | 1295.83 | 02-OCT-09:09 | 1047.95 | 25-OCT-07:10 | 1466.94 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 568.91 | 09-OCT-13:56 | 628.33 | 29-OCT-02:00 |
November | 1295.83 | 01-NOV-09:09 | 1029.08 | 01-NOV-07:10 | 1466.94 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 116.60 | 05-NOV-13:00 | 885.36 | 12-NOV-06:55 |
December | 1295.83 | 01-DEC-10:09 | 1036.12 | 12-DEC-08:09 | 1466.94 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 87.44 | 10-DEC-11:30 | 1245.24 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 809.54 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 60.11 | 176.83 | |||||
Maximum of Months | 1295.83 | 1047.95 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 568.91 | 1350.26 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1532.18 | 31-JAN-08:09 | 2276.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 233.02 | 16-JAN-15:00 | 1790.90 | 21-JAN-06:00 |
February | 2010.79 | 01-FEB-10:09 | 1567.12 | 01-FEB-08:09 | 2276.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 232.96 | 20-FEB-14:43 | 2289.82 | 05-FEB-08:00 |
March | 2010.79 | 01-MAR-10:09 | 1485.53 | 27-MAR-07:10 | 2276.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 382.00 | 05-MAR-12:33 | 2078.79 | 20-MAR-22:00 |
April | 2010.79 | 03-APR-09:09 | 1511.27 | 14-APR-07:10 | 2276.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 413.14 | 29-APR-17:02 | 1264.86 | 01-APR-17:55 |
May | 2010.79 | 01-MAY-09:09 | 1257.95 | 23-MAY-07:30 | 2276.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 599.35 | 07-MAY-13:53 | 297.91 | 09-MAY-02:00 |
June | 2010.79 | 01-JUN-09:09 | 1075.02 | 01-JUN-07:10 | 2276.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 721.55 | 10-JUN-17:02 | 413.45 | 06-JUN-21:20 |
July | 2010.79 | 03-JUL-09:09 | 1075.02 | 03-JUL-07:10 | 2276.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 580.46 | 16-JUL-15:16 | 317.09 | 30-JUL-10:53 |
August | 2010.79 | 01-AUG-09:09 | 1289.92 | 21-AUG-07:10 | 2276.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 886.90 | 20-AUG-14:00 | 570.34 | 25-AUG-23:53 |
September | 2010.79 | 01-SEP-09:09 | 1482.42 | 26-SEP-07:10 | 2276.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 886.78 | 09-SEP-17:02 | 635.48 | 05-SEP-02:55 |
October | 2010.79 | 02-OCT-09:09 | 1618.36 | 25-OCT-07:10 | 2276.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1030.75 | 09-OCT-13:56 | 908.66 | 29-OCT-02:00 |
November | 2010.79 | 01-NOV-09:09 | 1575.84 | 01-NOV-07:10 | 2276.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 234.19 | 05-NOV-13:00 | 1485.87 | 12-NOV-06:55 |
December | 2010.79 | 01-DEC-10:09 | 1608.57 | 12-DEC-08:09 | 2276.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 213.11 | 10-DEC-15:00 | 1945.37 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 213.11 | 297.91 | |||||
Maximum of Months | 2010.79 | 1618.36 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 1030.75 | 2289.82 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 967.35 | 04-JAN-16:00 | 1466.95 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 115.47 | 16-JAN-15:00 | 1193.97 | 21-JAN-05:55 |
February | 1295.83 | 01-FEB-10:09 | 983.20 | 01-FEB-08:09 | 1466.95 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 111.31 | 20-FEB-15:10 | 1526.89 | 05-FEB-07:55 |
March | 1295.83 | 01-MAR-10:09 | 910.31 | 27-MAR-07:10 | 1466.95 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 156.10 | 05-MAR-13:00 | 1426.17 | 20-MAR-22:00 |
April | 1295.83 | 03-APR-09:09 | 946.87 | 14-APR-07:10 | 1466.95 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 254.13 | 29-APR-17:02 | 880.53 | 01-APR-17:55 |
May | 1295.83 | 01-MAY-09:09 | 802.83 | 30-MAY-15:30 | 1466.95 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 418.23 | 21-MAY-13:53 | 271.04 | 14-MAY-12:10 |
June | 1295.83 | 01-JUN-09:09 | 692.79 | 01-JUN-07:10 | 1466.95 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 491.70 | 10-JUN-17:02 | 284.21 | 06-JUN-21:20 |
July | 1295.83 | 03-JUL-09:09 | 692.79 | 03-JUL-07:10 | 1466.95 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 404.18 | 16-JUL-15:16 | 234.45 | 30-JUL-10:50 |
August | 1295.83 | 01-AUG-09:09 | 692.79 | 01-AUG-07:10 | 1466.95 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 591.25 | 20-AUG-14:00 | 392.86 | 25-AUG-23:53 |
September | 1295.83 | 01-SEP-09:09 | 906.55 | 26-SEP-07:10 | 1466.95 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 592.52 | 09-SEP-17:02 | 441.83 | 05-SEP-02:55 |
October | 1295.83 | 02-OCT-09:09 | 1025.32 | 25-OCT-07:10 | 1466.95 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 718.74 | 09-OCT-13:56 | 632.88 | 29-OCT-02:00 |
November | 1295.83 | 01-NOV-09:09 | 1020.87 | 21-NOV-16:00 | 1466.95 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 108.65 | 05-NOV-13:00 | 1142.20 | 12-NOV-08:40 |
December | 1295.83 | 01-DEC-10:09 | 1024.95 | 12-DEC-08:09 | 1466.95 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 113.18 | 10-DEC-15:00 | 1309.12 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 108.65 | 234.45 | |||||
Maximum of Months | 1295.83 | 1025.32 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 718.74 | 1526.89 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1501.54 | 31-JAN-08:09 | 2276.35 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 47.10 | 19-JAN-12:00 | 1790.93 | 21-JAN-05:55 |
February | 2010.83 | 01-FEB-10:09 | 1547.95 | 01-FEB-08:09 | 2276.35 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 137.94 | 02-FEB-13:00 | 2290.08 | 05-FEB-07:55 |
March | 2010.83 | 01-MAR-10:09 | 1475.11 | 27-MAR-07:10 | 2276.35 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 200.12 | 26-MAR-13:57 | 2198.28 | 20-MAR-22:00 |
April | 2010.83 | 03-APR-09:09 | 1515.36 | 14-APR-07:10 | 2276.35 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 344.76 | 29-APR-17:02 | 1360.44 | 01-APR-17:55 |
May | 2010.83 | 01-MAY-09:09 | 1292.11 | 23-MAY-07:19 | 2276.35 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 588.76 | 07-MAY-13:53 | 306.99 | 09-MAY-02:00 |
June | 2010.83 | 01-JUN-09:09 | 1075.05 | 01-JUN-07:10 | 2276.35 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 743.06 | 10-JUN-17:02 | 415.93 | 06-JUN-21:20 |
July | 2010.83 | 03-JUL-09:09 | 1231.28 | 14-JUL-07:10 | 2276.35 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 579.96 | 22-JUL-18:50 | 324.57 | 30-JUL-10:53 |
August | 2010.83 | 01-AUG-09:09 | 1327.90 | 21-AUG-07:10 | 2276.35 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 886.89 | 20-AUG-14:00 | 587.27 | 25-AUG-23:53 |
September | 2010.83 | 01-SEP-09:09 | 1479.25 | 26-SEP-07:10 | 2276.35 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 833.45 | 09-SEP-17:10 | 679.30 | 05-SEP-02:55 |
October | 2010.83 | 02-OCT-09:09 | 1610.41 | 25-OCT-07:10 | 2276.35 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 944.29 | 09-OCT-14:00 | 1093.62 | 29-OCT-02:00 |
November | 2010.83 | 01-NOV-09:09 | 1544.14 | 21-NOV-16:00 | 2276.35 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 107.05 | 07-NOV-13:00 | 1776.03 | 12-NOV-11:00 |
December | 2010.83 | 01-DEC-10:09 | 1597.44 | 12-DEC-08:09 | 2276.35 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 101.07 | 13-DEC-14:00 | 2044.23 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1075.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 47.10 | 306.99 | |||||
Maximum of Months | 2010.83 | 1610.41 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 944.29 | 2290.08 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 995.06 | 31-JAN-08:09 | 1466.94 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 95.79 | 16-JAN-13:23 | 1194.02 | 21-JAN-05:55 |
February | 1295.83 | 01-FEB-10:09 | 1014.02 | 01-FEB-08:09 | 1466.94 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 91.96 | 02-FEB-13:00 | 1526.72 | 05-FEB-07:55 |
March | 1295.83 | 01-MAR-10:09 | 982.68 | 13-MAR-07:10 | 1466.94 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 220.83 | 05-MAR-12:33 | 1478.82 | 20-MAR-22:00 |
April | 1295.83 | 03-APR-09:09 | 988.08 | 14-APR-07:10 | 1466.94 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 162.87 | 29-APR-17:07 | 969.61 | 01-APR-17:55 |
May | 1295.83 | 01-MAY-09:09 | 882.37 | 24-MAY-07:10 | 1466.94 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 435.83 | 21-MAY-13:53 | 241.56 | 06-MAY-19:50 |
June | 1295.83 | 01-JUN-09:09 | 809.89 | 08-JUN-07:10 | 1466.94 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 456.51 | 10-JUN-17:08 | 326.80 | 06-JUN-21:20 |
July | 1295.83 | 03-JUL-09:09 | 842.40 | 14-JUL-07:10 | 1466.94 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 400.17 | 02-JUL-11:50 | 235.62 | 31-JUL-02:00 |
August | 1295.83 | 01-AUG-09:09 | 933.96 | 23-AUG-07:10 | 1466.94 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 591.27 | 20-AUG-14:00 | 436.26 | 25-AUG-23:53 |
September | 1295.83 | 01-SEP-09:09 | 979.71 | 26-SEP-07:10 | 1466.94 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 558.90 | 09-SEP-17:08 | 456.11 | 05-SEP-02:55 |
October | 1295.83 | 02-OCT-09:09 | 1047.88 | 25-OCT-07:10 | 1466.94 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 705.55 | 09-OCT-13:56 | 706.81 | 29-OCT-02:00 |
November | 1295.83 | 01-NOV-09:09 | 1029.01 | 01-NOV-07:10 | 1466.94 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 129.73 | 05-NOV-13:00 | 1048.89 | 12-NOV-06:55 |
December | 1295.83 | 01-DEC-10:09 | 1036.02 | 12-DEC-08:09 | 1466.94 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 122.02 | 10-DEC-11:00 | 1373.02 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 809.89 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 91.96 | 235.62 | |||||
Maximum of Months | 1295.83 | 1047.88 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 705.55 | 1526.72 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 405.10 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 405.10 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 405.10 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 405.10 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 405.10 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 405.10 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 405.10 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 405.10 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 405.10 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 405.10 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 405.10 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 405.10 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 405.10 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 405.10 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 405.10 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 405.10 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 405.10 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 405.10 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 405.10 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 405.10 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 405.10 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 405.10 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 405.10 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 405.10 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 405.10 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 405.10 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 405.10 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 405.10 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 405.10 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 405.10 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 405.10 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 405.10 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 405.10 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 405.10 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 405.10 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 405.10 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 405.10 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 405.10 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 405.10 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 405.10 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 405.10 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 405.10 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5027.92 | 02-JAN-10:09 | 4375.82 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5027.92 | 01-FEB-10:09 | 4375.82 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5027.92 | 01-MAR-10:09 | 4375.82 | 01-MAR-08:09 | 379632.52 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5027.92 | 03-APR-09:09 | 4375.82 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5027.92 | 01-MAY-09:09 | 4375.82 | 01-MAY-07:10 | 189816.26 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5027.92 | 01-JUN-09:09 | 4375.82 | 01-JUN-07:10 | 284724.39 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5027.92 | 03-JUL-09:09 | 4375.82 | 03-JUL-07:10 | 379632.52 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5027.92 | 01-AUG-09:09 | 4375.82 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5027.92 | 01-SEP-09:09 | 4375.82 | 01-SEP-07:10 | 189816.26 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5027.92 | 02-OCT-09:09 | 4375.82 | 02-OCT-07:10 | 284724.39 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5027.92 | 01-NOV-09:09 | 4375.82 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5027.92 | 01-DEC-10:09 | 4375.82 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5027.92 | 4375.82 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 5027.92 | 4375.82 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.79 | 16-JAN-15:00 | 1530.68 | 26-JAN-03:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.58 | 02-FEB-13:00 | 2190.64 | 05-FEB-07:55 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182.80 | 26-MAR-14:00 | 1851.27 | 20-MAR-22:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 291.21 | 29-APR-17:02 | 1080.59 | 01-APR-21:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 484.22 | 21-MAY-14:00 | 175.27 | 09-MAY-02:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 575.57 | 10-JUN-17:02 | 286.87 | 06-JUN-21:20 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 491.24 | 22-JUL-18:53 | 131.57 | 31-JUL-02:30 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 680.34 | 20-AUG-14:00 | 404.58 | 25-AUG-24:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 653.27 | 09-SEP-17:02 | 386.49 | 05-SEP-03:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 734.97 | 09-OCT-14:00 | 913.07 | 29-OCT-02:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.63 | 05-NOV-12:52 | 1288.85 | 12-NOV-08:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.41 | 10-DEC-14:52 | 2025.10 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.79 | 131.57 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 734.97 | 2190.64 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 178.26 | 16-JAN-15:00 | 2639.72 | 21-JAN-05:55 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.74 | 20-FEB-15:00 | 3785.34 | 05-FEB-07:55 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 382.63 | 05-MAR-12:53 | 3217.16 | 20-MAR-22:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 554.58 | 29-APR-17:02 | 1845.54 | 01-APR-21:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 826.94 | 07-MAY-13:53 | 301.05 | 09-MAY-02:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1046.93 | 10-JUN-17:02 | 514.83 | 06-JUN-21:20 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 911.56 | 22-JUL-18:53 | 237.27 | 31-JUL-03:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1237.37 | 20-AUG-14:00 | 741.21 | 25-AUG-23:53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1188.51 | 09-SEP-17:02 | 666.89 | 05-SEP-03:04 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1329.00 | 09-OCT-14:00 | 1562.18 | 29-OCT-02:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 191.13 | 05-NOV-13:00 | 2223.51 | 12-NOV-06:55 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 197.79 | 10-DEC-15:00 | 3462.36 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.74 | 237.27 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1329.00 | 3785.34 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.25 | 16-JAN-15:00 | 2638.30 | 21-JAN-06:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.17 | 02-FEB-13:00 | 3478.42 | 05-FEB-08:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 284.73 | 26-MAR-14:00 | 3399.01 | 20-MAR-22:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 389.87 | 29-APR-17:02 | 2071.37 | 01-APR-17:55 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 706.33 | 07-MAY-13:55 | 624.68 | 14-MAY-12:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 979.95 | 10-JUN-17:02 | 542.39 | 06-JUN-21:20 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 721.64 | 02-JUL-10:53 | 601.52 | 30-JUL-10:53 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1142.09 | 20-AUG-14:00 | 828.27 | 25-AUG-23:53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1268.77 | 09-SEP-22:53 | 897.32 | 05-SEP-03:04 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 976.64 | 08-OCT-14:00 | 1493.44 | 29-OCT-02:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.47 | 05-NOV-13:00 | 2335.15 | 12-NOV-06:55 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.08 | 10-DEC-15:00 | 3308.44 | 20-DEC-01:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.08 | 542.39 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1268.77 | 3478.42 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 106684.89 | 23-JAN-04:03 | 0.00 | 3448.91 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 109574.77 | 13-FEB-04:03 | 0.00 | 3448.91 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 110548.58 | 20-MAR-03:02 | 0.00 | 5173.36 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 106601.17 | 10-APR-03:02 | 0.00 | 4311.14 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 78461.54 | 30-MAY-03:02 | 0.00 | 4311.14 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 79393.90 | 07-JUN-03:02 | 0.00 | 4311.14 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 77787.42 | 18-JUL-03:02 | 0.00 | 4311.14 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 80747.66 | 28-AUG-03:02 | 0.00 | 5173.36 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 81548.92 | 05-SEP-03:02 | 0.00 | 4311.14 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 97505.74 | 28-OCT-05:02 | 8976.13 | 8622.27 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 109129.27 | 24-NOV-04:02 | 0.00 | 4311.14 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 109257.88 | 18-DEC-04:02 | 0.00 | 4311.14 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 77787.42 | 0.00 | 3448.91 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 110548.58 | 8976.13 | 8622.27 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 88919.37 | 17-JAN-04:03 | 0.00 | 3097.36 | 32228.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 90725.95 | 21-FEB-04:02 | 0.00 | 3871.70 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 91701.52 | 20-MAR-03:02 | 0.00 | 4646.04 | 48342.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 87699.10 | 10-APR-03:02 | 0.00 | 3871.70 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 84254.60 | 23-MAY-03:02 | 0.00 | 3097.36 | 32228.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 85752.99 | 07-JUN-03:02 | 0.00 | 3871.70 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 80350.40 | 10-JUL-05:04 | 8061.19 | 7743.41 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 78632.04 | 14-AUG-05:03 | 9673.43 | 9292.09 | 48342.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 85164.06 | 08-SEP-03:02 | 0.00 | 3097.36 | 32228.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 90148.84 | 30-OCT-03:02 | 0.00 | 3871.70 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 91445.26 | 27-NOV-04:02 | 0.00 | 3871.70 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 92293.82 | 18-DEC-04:02 | 0.00 | 3871.70 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 78632.04 | 0.00 | 3097.36 | 32228.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 92293.82 | 9673.43 | 9292.09 | 48342.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 78052.20 | 20-JAN-05:03 | 0.00 | 6194.72 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 77514.36 | 11-FEB-06:02 | 8061.19 | 7743.41 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 80458.51 | 20-MAR-03:02 | 0.00 | 4646.04 | 48342.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 78916.00 | 19-APR-04:03 | 0.00 | 6194.72 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 80602.55 | 01-MAY-03:02 | 0.00 | 3097.36 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 78502.25 | 01-JUN-03:02 | 0.00 | 3871.70 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 74015.48 | 12-JUL-05:04 | 8061.19 | 7743.41 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 77602.18 | 01-AUG-05:04 | 8061.19 | 7743.41 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 78237.43 | 20-SEP-03:02 | 0.00 | 3871.70 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 80219.90 | 17-OCT-03:02 | 0.00 | 3871.70 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 77840.09 | 25-NOV-06:02 | 8061.19 | 7743.41 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 78680.80 | 14-DEC-05:03 | 0.00 | 6194.72 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 74015.48 | 0.00 | 3097.36 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 80602.55 | 8061.19 | 7743.41 | 48342.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 74775.42 | 19-JAN-06:03 | 6448.95 | 6194.72 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 76885.92 | 01-FEB-06:02 | 8061.19 | 7743.41 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 77094.14 | 01-MAR-06:02 | 8061.19 | 7743.41 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 78292.76 | 24-APR-03:02 | 0.00 | 3871.70 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 80152.36 | 01-MAY-03:02 | 0.00 | 3097.36 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 79249.67 | 06-JUN-03:02 | 0.00 | 3097.36 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 76312.70 | 01-JUL-03:02 | 0.00 | 3871.70 | 30214.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 77973.53 | 29-AUG-03:02 | 0.00 | 3097.36 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 77884.07 | 06-SEP-03:02 | 0.00 | 3871.70 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 79028.84 | 10-OCT-03:02 | 0.00 | 3871.70 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 77976.40 | 08-NOV-05:03 | 0.00 | 6194.72 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 72963.56 | 14-DEC-06:03 | 6448.95 | 6194.72 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 72963.56 | 0.00 | 3097.36 | 30214.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 80152.36 | 8061.19 | 7743.41 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 11905.46 | 02-JAN-06:02 | 1012.16 | 972.26 | 5058.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.95 |
February | 9750.23 | 28-FEB-06:02 | 1012.16 | 972.26 | 5058.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.28 |
March | 11152.39 | 27-MAR-05:02 | 1012.16 | 972.26 | 5058.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.02 |
April | 11604.08 | 07-APR-05:02 | 1012.16 | 972.26 | 5058.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.09 |
May | 12459.10 | 30-MAY-03:02 | 0.00 | 486.13 | 5058.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.55 |
June | 12109.64 | 26-JUN-04:03 | 0.00 | 777.81 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 14172.33 | 23-JUL-13:02 | 404.87 | 238.90 | 3035.09 | 0.00 | 0.00 | 0.00 | 0.00 | 86.38 | 0.00 |
August | 14203.20 | 21-AUG-03:02 | 0.00 | 583.36 | 6070.18 | 0.00 | 0.00 | 0.00 | 0.00 | 10.13 | 0.00 |
September | 12573.31 | 06-SEP-03:02 | 0.00 | 486.13 | 5058.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.59 |
October | 12129.56 | 23-OCT-04:53 | 0.00 | 777.81 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.25 |
November | 11503.38 | 02-NOV-05:02 | 1012.16 | 972.26 | 5058.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.45 |
December | 11324.74 | 12-DEC-06:02 | 1012.16 | 972.26 | 5058.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.37 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 9750.23 | 0.00 | 238.90 | 3035.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14203.20 | 1012.16 | 972.26 | 6070.18 | 0.00 | 0.00 | 0.00 | 0.00 | 86.38 | 26.59 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8255.62 | 01-JAN-09:53 | 195.68 | 115.47 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.32 |
February | 7986.17 | 26-FEB-10:43 | 195.68 | 115.47 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.93 |
March | 12168.71 | 26-MAR-09:02 | 260.91 | 153.96 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.48 |
April | 16376.50 | 23-APR-09:13 | 260.91 | 153.96 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.28 |
May | 16847.88 | 07-MAY-09:22 | 326.14 | 192.45 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 31.43 | 0.00 |
June | 11043.27 | 29-JUN-05:02 | 652.28 | 626.56 | 3259.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.20 | 0.00 |
July | 16752.61 | 23-JUL-09:02 | 326.14 | 192.45 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 8.54 | 0.00 |
August | 15075.14 | 27-AUG-10:23 | 260.91 | 153.96 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 46.24 | 0.00 |
September | 16821.18 | 24-SEP-09:32 | 326.14 | 192.45 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 17.78 | 0.00 |
October | 16327.62 | 09-OCT-08:53 | 260.91 | 153.96 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.23 |
November | 10432.73 | 11-NOV-09:23 | 195.68 | 115.47 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.50 |
December | 5661.18 | 10-DEC-09:43 | 195.68 | 115.47 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.28 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5661.18 | 195.68 | 115.47 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16847.88 | 652.28 | 626.56 | 3259.88 | 0.00 | 0.00 | 0.00 | 0.00 | 46.24 | 134.32 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 19949.38 | 01-JAN-13:52 | 506.09 | 298.64 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.42 |
February | 19818.23 | 26-FEB-14:43 | 404.87 | 238.91 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.45 |
March | 19176.97 | 26-MAR-13:43 | 404.87 | 238.91 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 56.76 | 0.00 |
April | 13692.53 | 29-APR-05:02 | 1012.19 | 972.28 | 5058.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.97 |
May | 14347.00 | 01-MAY-05:02 | 1012.19 | 972.28 | 5058.56 | 0.00 | 0.00 | 0.00 | 0.00 | 2.28 | 0.00 |
June | 14419.25 | 26-JUN-04:03 | 0.00 | 777.83 | 4046.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 15979.21 | 23-JUL-13:02 | 404.87 | 238.91 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 86.55 | 0.00 |
August | 18809.56 | 27-AUG-13:02 | 404.87 | 238.91 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 135.60 | 0.00 |
September | 19654.20 | 03-SEP-15:12 | 607.31 | 358.36 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 135.87 | 0.00 |
October | 19856.92 | 08-OCT-11:43 | 404.87 | 238.91 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 145.01 | 0.00 |
November | 21006.21 | 11-NOV-13:22 | 607.31 | 358.36 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.05 |
December | 19838.54 | 10-DEC-13:42 | 506.09 | 298.64 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.76 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 13692.53 | 0.00 | 238.91 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21006.21 | 1012.19 | 972.28 | 5058.56 | 0.00 | 0.00 | 0.00 | 0.00 | 145.01 | 63.05 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 16714.11 | 16-JAN-15:53 | 260.91 | 153.96 | 1955.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.17 |
February | 19228.16 | 26-FEB-15:23 | 260.91 | 153.96 | 1955.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.77 |
March | 19527.38 | 26-MAR-14:23 | 260.91 | 153.96 | 1955.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 0.00 |
April | 21178.71 | 23-APR-16:32 | 326.14 | 192.45 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 3.66 | 0.00 |
May | 21240.88 | 28-MAY-16:21 | 456.59 | 269.43 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 80.84 | 0.00 |
June | 20992.23 | 11-JUN-16:42 | 326.14 | 192.45 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 55.85 | 0.00 |
July | 20719.03 | 16-JUL-15:52 | 326.14 | 192.45 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 113.38 | 0.00 |
August | 20763.98 | 06-AUG-16:22 | 326.14 | 192.45 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.08 |
September | 22571.25 | 03-SEP-15:51 | 456.59 | 269.43 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 80.93 | 0.00 |
October | 21487.10 | 22-OCT-15:52 | 326.14 | 192.45 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 15.80 | 0.00 |
November | 21584.90 | 11-NOV-15:22 | 326.14 | 192.45 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.03 |
December | 19820.40 | 10-DEC-15:42 | 326.14 | 192.45 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 3.68 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 16714.11 | 260.91 | 153.96 | 1955.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22571.25 | 456.59 | 269.43 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 113.38 | 31.08 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5208.97 | 31-JAN-14:40 | 2010.79 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 23.12 | 0.00 |
February | 5437.44 | 28-FEB-15:00 | 2010.79 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 24.57 | 0.00 |
March | 9249.26 | 27-MAR-05:02 | 1012.16 | 972.26 | 5058.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.09 |
April | 10168.52 | 29-APR-05:02 | 1012.16 | 972.26 | 5058.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.59 |
May | 14098.03 | 29-MAY-16:01 | 708.51 | 418.08 | 5311.41 | 0.00 | 0.00 | 0.00 | 0.00 | 213.63 | 0.00 |
June | 14463.46 | 25-JUN-16:31 | 708.51 | 418.08 | 5311.41 | 0.00 | 0.00 | 0.00 | 0.00 | 112.83 | 0.00 |
July | 13185.16 | 03-JUL-03:02 | 0.00 | 486.13 | 5058.48 | 0.00 | 0.00 | 0.00 | 0.00 | 153.41 | 0.00 |
August | 13192.26 | 21-AUG-03:02 | 0.00 | 583.36 | 6070.18 | 0.00 | 0.00 | 0.00 | 0.00 | 12.78 | 0.00 |
September | 11478.23 | 11-SEP-05:03 | 809.73 | 777.81 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 9.99 | 0.00 |
October | 14273.06 | 08-OCT-14:52 | 607.30 | 358.36 | 4552.64 | 0.00 | 0.00 | 0.00 | 0.00 | 485.06 | 0.00 |
November | 10587.25 | 01-NOV-05:03 | 809.73 | 777.81 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.25 |
December | 10121.05 | 15-DEC-06:02 | 1012.16 | 972.26 | 5058.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.60 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5208.97 | 0.00 | 358.36 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14463.46 | 2010.79 | 1075.02 | 6070.18 | 0.00 | 0.00 | 0.00 | 0.00 | 485.06 | 54.09 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6396.73 | 19-JAN-10:00 | 1239.33 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.86 |
February | 6835.02 | 27-FEB-10:00 | 1239.33 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.26 |
March | 10696.95 | 26-MAR-09:43 | 195.68 | 115.47 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.17 |
April | 17342.48 | 23-APR-09:32 | 326.14 | 192.45 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.00 |
May | 18026.50 | 29-MAY-08:42 | 391.37 | 230.94 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.08 |
June | 16781.62 | 11-JUN-08:32 | 260.91 | 153.96 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.05 |
July | 16754.31 | 30-JUL-09:02 | 260.91 | 153.96 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 108.61 | 0.00 |
August | 16631.63 | 27-AUG-10:23 | 260.91 | 153.96 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 97.36 | 0.00 |
September | 16594.00 | 10-SEP-09:42 | 326.14 | 192.45 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 274.19 | 0.00 |
October | 16009.14 | 08-OCT-14:52 | 391.37 | 230.94 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 326.44 | 0.00 |
November | 9791.74 | 02-NOV-05:02 | 652.28 | 626.56 | 3259.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.65 |
December | 5974.59 | 15-DEC-06:02 | 652.28 | 626.56 | 3259.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.67 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5974.59 | 195.68 | 115.47 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18026.50 | 1239.33 | 692.79 | 3259.88 | 0.00 | 0.00 | 0.00 | 0.00 | 326.44 | 75.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 20670.25 | 01-JAN-14:11 | 708.53 | 418.09 | 5311.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.87 |
February | 19317.52 | 26-FEB-13:42 | 506.09 | 298.64 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.62 |
March | 18022.03 | 26-MAR-13:43 | 404.87 | 238.91 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 131.64 | 0.00 |
April | 13865.96 | 23-APR-15:32 | 506.09 | 298.64 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 98.13 | 0.00 |
May | 17008.33 | 29-MAY-16:01 | 708.53 | 418.09 | 5311.49 | 0.00 | 0.00 | 0.00 | 0.00 | 215.00 | 0.00 |
June | 17435.51 | 25-JUN-15:51 | 708.53 | 418.09 | 5311.49 | 0.00 | 0.00 | 0.00 | 0.00 | 95.25 | 0.00 |
July | 15255.13 | 20-JUL-03:02 | 0.00 | 486.14 | 5058.56 | 0.00 | 0.00 | 0.00 | 0.00 | 16.13 | 0.00 |
August | 17675.59 | 27-AUG-13:02 | 404.87 | 238.91 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 317.92 | 0.00 |
September | 18443.03 | 17-SEP-14:22 | 506.09 | 298.64 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 273.91 | 0.00 |
October | 19513.53 | 08-OCT-14:52 | 607.31 | 358.36 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 296.58 | 0.00 |
November | 19448.05 | 05-NOV-13:32 | 506.09 | 298.64 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.87 |
December | 20198.37 | 10-DEC-12:42 | 607.31 | 358.36 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 13865.96 | 0.00 | 238.91 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20670.25 | 708.53 | 486.14 | 5311.49 | 0.00 | 0.00 | 0.00 | 0.00 | 317.92 | 98.87 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 13871.29 | 01-JAN-15:32 | 391.37 | 230.94 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.90 |
February | 17306.88 | 26-FEB-17:03 | 260.91 | 153.96 | 1955.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.25 |
March | 12330.72 | 27-MAR-05:02 | 652.28 | 626.56 | 3259.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.29 |
April | 18710.30 | 23-APR-16:52 | 391.37 | 230.94 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.73 |
May | 19114.55 | 29-MAY-16:01 | 456.59 | 269.43 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 95.05 | 0.00 |
June | 19141.24 | 11-JUN-17:11 | 0.00 | 269.43 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 112.79 | 0.00 |
July | 16408.38 | 16-JUL-15:52 | 326.14 | 192.45 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 264.12 | 0.00 |
August | 15568.64 | 21-AUG-03:02 | 0.00 | 375.94 | 3911.83 | 0.00 | 0.00 | 0.00 | 0.00 | 12.21 | 0.00 |
September | 18481.81 | 17-SEP-15:42 | 391.37 | 230.94 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 243.53 | 0.00 |
October | 18334.73 | 08-OCT-16:12 | 391.37 | 230.94 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 214.48 | 0.00 |
November | 12341.82 | 05-NOV-15:32 | 391.37 | 230.94 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 7.48 | 0.00 |
December | 17173.28 | 10-DEC-15:22 | 391.37 | 230.94 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 20.23 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 12330.72 | 0.00 | 153.96 | 1955.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19141.24 | 652.28 | 626.56 | 3911.83 | 0.00 | 0.00 | 0.00 | 0.00 | 264.12 | 75.25 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5478.47 | 31-JAN-15:00 | 2010.79 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 25.20 | 0.00 |
February | 5753.84 | 22-FEB-14:30 | 2010.79 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 13.81 | 0.00 |
March | 8266.40 | 27-MAR-05:02 | 1012.16 | 972.26 | 5058.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.37 |
April | 11860.74 | 29-APR-05:02 | 1012.16 | 972.26 | 5058.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.23 |
May | 16997.61 | 29-MAY-16:01 | 708.51 | 418.08 | 5311.41 | 0.00 | 0.00 | 0.00 | 0.00 | 229.79 | 0.00 |
June | 17184.13 | 25-JUN-16:31 | 708.51 | 418.08 | 5311.41 | 0.00 | 0.00 | 0.00 | 0.00 | 125.07 | 0.00 |
July | 16506.11 | 02-JUL-17:03 | 0.00 | 238.90 | 3035.09 | 0.00 | 0.00 | 0.00 | 0.00 | 259.49 | 0.00 |
August | 16294.45 | 27-AUG-16:12 | 607.30 | 358.36 | 4552.64 | 0.00 | 0.00 | 0.00 | 0.00 | 625.09 | 0.00 |
September | 16408.81 | 17-SEP-15:42 | 607.30 | 358.36 | 4552.64 | 0.00 | 0.00 | 0.00 | 0.00 | 554.18 | 0.00 |
October | 16909.88 | 08-OCT-14:52 | 607.30 | 358.36 | 4552.64 | 0.00 | 0.00 | 0.00 | 0.00 | 525.96 | 0.00 |
November | 12237.82 | 02-NOV-05:02 | 1012.16 | 972.26 | 5058.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.07 |
December | 6360.99 | 15-DEC-15:00 | 2010.79 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 64.02 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5478.47 | 0.00 | 238.90 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17184.13 | 2010.79 | 1075.02 | 5311.41 | 0.00 | 0.00 | 0.00 | 0.00 | 625.09 | 68.37 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6126.19 | 19-JAN-10:20 | 1295.83 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.53 |
February | 6651.82 | 27-FEB-10:30 | 1295.83 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.66 |
March | 9620.83 | 27-MAR-05:02 | 652.28 | 626.56 | 3259.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.07 |
April | 17028.12 | 23-APR-11:02 | 260.91 | 153.96 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.62 |
May | 18545.74 | 29-MAY-08:42 | 391.37 | 230.94 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.23 |
June | 17141.03 | 11-JUN-08:32 | 260.91 | 153.96 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.48 |
July | 17923.63 | 23-JUL-09:02 | 326.14 | 192.45 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 18.79 | 0.00 |
August | 17072.57 | 27-AUG-10:13 | 260.91 | 153.96 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 118.50 | 0.00 |
September | 17116.62 | 10-SEP-09:42 | 326.14 | 192.45 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 326.42 | 0.00 |
October | 16827.65 | 08-OCT-14:52 | 391.37 | 230.94 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 358.47 | 0.00 |
November | 9879.80 | 02-NOV-05:02 | 652.28 | 626.56 | 3259.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.86 |
December | 4897.81 | 16-DEC-10:10 | 409.21 | 230.93 | 814.97 | 0.00 | 0.00 | 0.00 | 0.00 | 1.12 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4897.81 | 260.91 | 153.96 | 814.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18545.74 | 1295.83 | 692.79 | 3259.88 | 0.00 | 0.00 | 0.00 | 0.00 | 358.47 | 46.07 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 22582.53 | 01-JAN-15:02 | 607.31 | 358.36 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.96 |
February | 21361.69 | 26-FEB-13:52 | 506.09 | 298.64 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.53 |
March | 17332.89 | 05-MAR-13:33 | 303.66 | 179.18 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 57.89 | 0.00 |
April | 18208.64 | 23-APR-15:01 | 708.53 | 418.09 | 5311.49 | 0.00 | 0.00 | 0.00 | 0.00 | 171.20 | 0.00 |
May | 20140.95 | 29-MAY-16:01 | 708.53 | 418.09 | 5311.49 | 0.00 | 0.00 | 0.00 | 0.00 | 234.97 | 0.00 |
June | 20181.35 | 25-JUN-15:51 | 708.53 | 418.09 | 5311.49 | 0.00 | 0.00 | 0.00 | 0.00 | 106.56 | 0.00 |
July | 18875.07 | 23-JUL-13:02 | 404.87 | 238.91 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 243.57 | 0.00 |
August | 19872.62 | 27-AUG-12:53 | 404.87 | 238.91 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 364.22 | 0.00 |
September | 20821.25 | 17-SEP-14:22 | 506.09 | 298.64 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 306.16 | 0.00 |
October | 22252.80 | 08-OCT-14:52 | 607.31 | 358.36 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 308.25 | 0.00 |
November | 22413.15 | 11-NOV-14:02 | 607.31 | 358.36 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 217.82 |
December | 22516.71 | 10-DEC-12:52 | 607.31 | 358.36 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.36 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 17332.89 | 303.66 | 179.18 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22582.53 | 708.53 | 418.09 | 5311.49 | 0.00 | 0.00 | 0.00 | 0.00 | 364.22 | 217.82 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9251.06 | 01-JAN-17:03 | 260.91 | 153.96 | 1955.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.79 |
February | 15223.43 | 26-FEB-17:12 | 391.37 | 230.94 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.61 |
March | 13101.05 | 27-MAR-05:02 | 652.28 | 626.56 | 3259.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.65 |
April | 19355.22 | 23-APR-17:01 | 0.00 | 269.43 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.17 |
May | 21253.96 | 29-MAY-16:01 | 456.59 | 269.43 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 103.63 | 0.00 |
June | 21132.71 | 11-JUN-17:11 | 0.00 | 269.43 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 125.88 | 0.00 |
July | 19132.36 | 30-JUL-16:52 | 326.14 | 192.45 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.17 |
August | 17648.68 | 27-AUG-16:12 | 391.37 | 230.94 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 412.18 | 0.00 |
September | 20236.31 | 17-SEP-15:42 | 391.37 | 230.94 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 272.37 | 0.00 |
October | 20213.05 | 08-OCT-16:12 | 391.37 | 230.94 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 226.77 | 0.00 |
November | 17809.92 | 11-NOV-15:22 | 326.14 | 192.45 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.23 |
December | 18918.04 | 10-DEC-16:12 | 391.37 | 230.94 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.64 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 9251.06 | 0.00 | 153.96 | 1955.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21253.96 | 652.28 | 626.56 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 412.18 | 96.61 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 11952.62 | 02-JAN-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.75 |
February | 8690.61 | 27-FEB-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 9503.76 | 27-MAR-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.96 |
April | 8564.63 | 24-APR-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.04 |
May | 13943.61 | 22-MAY-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.36 | 0.00 |
June | 9890.61 | 12-JUN-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.51 |
July | 13585.21 | 24-JUL-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.95 | 0.00 |
August | 13830.48 | 28-AUG-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.99 |
September | 13759.94 | 05-SEP-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.91 |
October | 14017.82 | 10-OCT-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.37 |
November | 9779.61 | 06-NOV-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.68 |
December | 9113.80 | 11-DEC-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.84 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 8564.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14017.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.36 | 61.37 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6891.05 | 02-JAN-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.60 |
February | 5175.24 | 24-FEB-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5778.22 | 01-MAR-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 233.49 |
April | 6430.65 | 28-APR-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 198.65 | 0.00 |
May | 12706.03 | 22-MAY-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.95 | 0.00 |
June | 8560.51 | 23-JUN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.35 | 0.00 |
July | 8011.97 | 31-JUL-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.47 |
August | 8964.87 | 28-AUG-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.85 | 0.00 |
September | 8556.71 | 05-SEP-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.73 |
October | 9605.40 | 10-OCT-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.55 |
November | 6676.58 | 04-NOV-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.34 |
December | 5782.50 | 15-DEC-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.88 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 5175.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12706.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 198.65 | 233.49 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9748.93 | 19-JAN-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.09 |
February | 11609.51 | 24-FEB-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.23 |
March | 12987.63 | 06-MAR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.08 | 0.00 |
April | 18175.10 | 28-APR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 227.16 | 0.00 |
May | 19299.57 | 10-MAY-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.90 | 0.00 |
June | 20243.21 | 28-JUN-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.60 | 0.00 |
July | 20443.99 | 07-JUL-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.49 | 0.00 |
August | 19533.00 | 10-AUG-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.91 | 0.00 |
September | 17594.43 | 01-SEP-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.14 | 0.00 |
October | 16472.91 | 05-OCT-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.92 | 0.00 |
November | 13018.03 | 02-NOV-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.30 | 0.00 |
December | 11020.87 | 15-DEC-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.96 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 9748.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20443.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 227.16 | 36.09 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 2052.06 | 01-JAN-17:27 | 35.07 | 67.52 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4115.35 | 26-FEB-17:42 | 46.77 | 90.03 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7197.45 | 31-MAR-24:00 | 0.00 | 22.51 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7906.36 | 16-APR-18:10 | 0.00 | 112.53 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3491.61 | 31-MAY-24:00 | 0.00 | 22.51 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5345.11 | 30-JUN-23:57 | 0.00 | 67.52 | 17537.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7222.33 | 31-JUL-23:57 | 0.00 | 67.52 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7789.06 | 06-AUG-18:00 | 0.00 | 90.03 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3520.03 | 30-SEP-24:00 | 0.00 | 22.51 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5366.73 | 31-OCT-24:00 | 0.00 | 22.51 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5953.60 | 06-NOV-17:00 | 222.14 | 405.10 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7830.98 | 10-DEC-16:54 | 58.46 | 112.53 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 2052.06 | 0.00 | 22.51 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7906.36 | 222.14 | 405.10 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1855.74 | 18-JAN-17:00 | 222.14 | 405.10 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3774.27 | 26-FEB-17:54 | 58.46 | 112.53 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6775.73 | 31-MAR-24:00 | 0.00 | 22.51 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7457.11 | 16-APR-18:10 | 0.00 | 112.53 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3304.87 | 31-MAY-24:00 | 0.00 | 22.51 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5202.21 | 30-JUN-23:57 | 0.00 | 67.52 | 17537.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6956.68 | 31-JUL-23:57 | 0.00 | 67.52 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7262.04 | 06-AUG-18:10 | 0.00 | 45.01 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3312.39 | 30-SEP-24:00 | 0.00 | 22.51 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5025.17 | 31-OCT-24:00 | 0.00 | 22.51 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5638.16 | 06-NOV-17:00 | 222.14 | 405.10 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7368.55 | 15-DEC-17:00 | 222.14 | 405.10 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1855.74 | 0.00 | 22.51 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7457.11 | 222.14 | 405.10 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1905.45 | 19-JAN-17:00 | 222.14 | 405.10 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3796.23 | 26-FEB-17:42 | 46.77 | 90.03 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6671.83 | 31-MAR-24:00 | 0.00 | 22.51 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7640.94 | 23-APR-18:08 | 0.00 | 90.03 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3268.37 | 31-MAY-24:00 | 0.00 | 22.51 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5231.75 | 30-JUN-23:57 | 0.00 | 67.52 | 17537.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6940.03 | 31-JUL-23:57 | 0.00 | 67.52 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7506.99 | 06-AUG-17:40 | 0.00 | 135.04 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3354.81 | 30-SEP-24:00 | 0.00 | 22.51 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4967.20 | 31-OCT-24:00 | 0.00 | 22.51 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5697.61 | 06-NOV-17:00 | 222.14 | 405.10 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7431.07 | 15-DEC-17:00 | 222.14 | 405.10 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1905.45 | 0.00 | 22.51 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7640.94 | 222.14 | 405.10 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 92998.12 | 02-JAN-17:00 | 4808.68 | 4375.82 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 183714.69 | 27-FEB-17:00 | 4808.68 | 4375.82 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 358582.23 | 31-MAR-24:00 | 0.00 | 243.11 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 367523.33 | 28-APR-21:02 | 1518.53 | 2917.33 | 2277795.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 175679.32 | 31-MAY-24:00 | 0.00 | 243.11 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 267329.23 | 30-JUN-23:57 | 0.00 | 729.33 | 854173.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 359638.50 | 31-JUL-23:53 | 0.00 | 729.33 | 1138897.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 371126.47 | 09-AUG-21:13 | 1518.53 | 2917.33 | 2277795.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 176634.57 | 30-SEP-24:00 | 0.00 | 243.11 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 268703.72 | 31-OCT-24:00 | 0.00 | 243.11 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 276635.21 | 06-NOV-17:00 | 4808.68 | 4375.82 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 368064.53 | 26-DEC-17:00 | 4808.68 | 4375.82 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 92998.12 | 0.00 | 243.11 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 371126.47 | 4808.68 | 4375.82 | 2277795.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.169750E+13 | 1345079.74 | 31-JAN-16:19 | 0.725824E+11 | 432689.59 | 05-JAN-07:10 |
February | 0.196418E+13 | 1515298.59 | 28-FEB-16:10 | 0.587335E+11 | 426078.39 | 06-FEB-07:10 |
March | 0.264295E+13 | 1678944.96 | 06-MAR-16:19 | 0.639663E+11 | 346886.28 | 09-MAR-07:10 |
April | 0.306537E+13 | 1901572.29 | 28-APR-15:09 | 0.494398E+11 | 102122.93 | 18-APR-14:30 |
May | 0.220616E+13 | 1438105.25 | 17-MAY-15:50 | 0.493999E+11 | 66573.75 | 02-MAY-11:50 |
June | 0.259850E+13 | 1608137.44 | 28-JUN-15:20 | 0.465482E+11 | 62646.36 | 05-JUN-11:30 |
July | 0.306872E+13 | 1772619.75 | 18-JUL-15:20 | 0.446472E+11 | 60186.17 | 06-JUL-11:50 |
August | 0.355094E+13 | 1925340.49 | 03-AUG-15:20 | 0.476434E+11 | 61272.35 | 28-AUG-11:30 |
September | 0.210608E+13 | 1440386.78 | 06-SEP-15:30 | 0.456884E+11 | 64604.33 | 29-SEP-11:30 |
October | 0.251466E+13 | 1591812.26 | 06-OCT-15:00 | 0.494216E+11 | 67824.40 | 26-OCT-11:50 |
November | 0.261891E+13 | 1690341.90 | 03-NOV-15:00 | 0.509044E+11 | 108639.75 | 27-NOV-14:20 |
December | 0.296660E+13 | 1834878.73 | 12-DEC-16:30 | 0.649260E+11 | 495802.30 | 21-DEC-07:10 |
Annual Sum or Average | 0.310006E+14 | 0.643901E+12 | ||||
Minimum of Months | 0.169750E+13 | 1345079.74 | 0.446472E+11 | 60186.17 | ||
Maximum of Months | 0.355094E+13 | 1925340.49 | 0.725824E+11 | 495802.30 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.230309E+12 | 0.445478E+11 | 0.811612E+12 | 0.162550E+12 | 0.175919E+12 | 0.463976E+11 | 0.00 | 0.150440E+12 | 0.727784E+11 | 0.502569E+09 | 0.244205E+10 | 0.00 | 0.00 |
February | 0.208114E+12 | 0.379910E+11 | 0.102011E+13 | 0.146826E+12 | 0.163671E+12 | 0.551294E+11 | 0.00 | 0.230157E+12 | 0.995200E+11 | 0.351114E+09 | 0.231275E+10 | 0.00 | 0.00 |
March | 0.246449E+12 | 0.386805E+11 | 0.146267E+13 | 0.162740E+12 | 0.191131E+12 | 0.664477E+11 | 0.00 | 0.344906E+12 | 0.126810E+12 | 0.227752E+09 | 0.289038E+10 | 0.00 | 0.00 |
April | 0.219690E+12 | 0.341555E+11 | 0.170311E+13 | 0.157288E+12 | 0.201569E+12 | 0.957589E+11 | 0.00 | 0.498945E+12 | 0.150544E+12 | 62952719.63 | 0.424323E+10 | 0.00 | 0.00 |
May | 0.236263E+12 | 0.323392E+11 | 0.820521E+12 | 0.162644E+12 | 0.239326E+12 | 0.112129E+12 | 0.00 | 0.401429E+12 | 0.193955E+12 | 0.00 | 0.755798E+10 | 0.00 | 0.00 |
June | 0.234810E+12 | 0.296873E+11 | 0.110677E+13 | 0.157466E+12 | 0.240092E+12 | 0.119605E+12 | 0.00 | 0.506234E+12 | 0.196270E+12 | 0.00 | 0.755798E+10 | 0.00 | 0.00 |
July | 0.220025E+12 | 0.315268E+11 | 0.143888E+13 | 0.162465E+12 | 0.238938E+12 | 0.128437E+12 | 0.00 | 0.630543E+12 | 0.210730E+12 | 0.00 | 0.717402E+10 | 0.00 | 0.00 |
August | 0.245403E+12 | 0.339189E+11 | 0.177780E+13 | 0.162740E+12 | 0.251643E+12 | 0.133354E+12 | 0.00 | 0.727707E+12 | 0.210514E+12 | 0.00 | 0.786111E+10 | 0.00 | 0.00 |
September | 0.219913E+12 | 0.360511E+11 | 0.784732E+12 | 0.157287E+12 | 0.220528E+12 | 0.107567E+12 | 0.00 | 0.383003E+12 | 0.189823E+12 | 0.00 | 0.717402E+10 | 0.00 | 0.00 |
October | 0.229023E+12 | 0.406889E+11 | 0.112899E+13 | 0.162550E+12 | 0.218979E+12 | 0.107033E+12 | 0.00 | 0.442420E+12 | 0.179253E+12 | 53688292.87 | 0.566287E+10 | 0.00 | 0.00 |
November | 0.227547E+12 | 0.422343E+11 | 0.140306E+13 | 0.157361E+12 | 0.187993E+12 | 0.797311E+11 | 0.00 | 0.380846E+12 | 0.137432E+12 | 80917418.96 | 0.262430E+10 | 0.00 | 0.00 |
December | 0.223432E+12 | 0.452925E+11 | 0.175516E+13 | 0.162466E+12 | 0.180798E+12 | 0.623430E+11 | 0.00 | 0.405186E+12 | 0.128862E+12 | 0.257510E+09 | 0.280281E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.274098E+13 | 0.447114E+12 | 0.152134E+14 | 0.191438E+13 | 0.251059E+13 | 0.111393E+13 | 0.00 | 0.510182E+13 | 0.189649E+13 | 0.153650E+10 | 0.603035E+11 | 0.00 | 0.00 |
Minimum of Months | 0.208114E+12 | 0.296873E+11 | 0.784732E+12 | 0.146826E+12 | 0.163671E+12 | 0.463976E+11 | 0.00 | 0.150440E+12 | 0.727784E+11 | 0.00 | 0.231275E+10 | 0.00 | 0.00 |
Maximum of Months | 0.246449E+12 | 0.452925E+11 | 0.177780E+13 | 0.162740E+12 | 0.251643E+12 | 0.133354E+12 | 0.00 | 0.727707E+12 | 0.210730E+12 | 0.502569E+09 | 0.786111E+10 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.179037E+11 | 0.00 | 0.546788E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.942274E+10 | 0.00 | 0.493107E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.852877E+10 | 0.00 | 0.554375E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.342146E+09 | 0.00 | 0.490977E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.493999E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.465482E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.446472E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.476434E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.456884E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 11781611.69 | 0.00 | 0.494098E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.294006E+09 | 0.00 | 0.506104E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.120646E+11 | 0.00 | 0.528614E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.485677E+11 | 0.00 | 0.595333E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.446472E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.179037E+11 | 0.00 | 0.554375E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 251691.20 | 31-JAN-08:09 | 37611.08 | 01-JAN-06:10 | 439129.89 | 02-JAN-08:09 | 117199.38 | 31-JAN-08:20 | 151013.44 | 02-JAN-13:39 | 72022.64 | 19-JAN-15:20 | 0.00 | 01-JAN-00:10 |
February | 253346.39 | 01-FEB-08:09 | 37611.08 | 01-FEB-06:10 | 557421.28 | 01-FEB-08:09 | 117200.32 | 01-FEB-08:20 | 163054.74 | 28-FEB-16:40 | 72381.17 | 27-FEB-11:00 | 0.00 | 01-FEB-00:10 |
March | 250193.82 | 27-MAR-07:10 | 37611.08 | 01-MAR-06:10 | 675712.68 | 01-MAR-08:09 | 117198.53 | 27-MAR-07:19 | 190186.15 | 24-MAR-14:50 | 70038.08 | 07-MAR-14:50 | 0.00 | 01-MAR-00:10 |
April | 251535.70 | 14-APR-07:10 | 37611.08 | 01-APR-05:10 | 794004.08 | 03-APR-07:10 | 117199.29 | 14-APR-07:19 | 261005.24 | 18-APR-14:39 | 70385.95 | 19-APR-13:00 | 0.00 | 01-APR-00:10 |
May | 241221.90 | 23-MAY-07:19 | 37611.08 | 01-MAY-05:10 | 439129.89 | 01-MAY-07:10 | 117193.42 | 23-MAY-07:30 | 202263.60 | 04-MAY-15:00 | 70211.44 | 16-MAY-13:39 | 0.00 | 01-MAY-00:10 |
June | 235832.96 | 08-JUN-07:10 | 37611.08 | 01-JUN-05:10 | 557421.28 | 01-JUN-07:10 | 117190.36 | 08-JUN-07:19 | 202723.19 | 13-JUN-15:30 | 70354.74 | 13-JUN-15:00 | 0.00 | 01-JUN-00:10 |
July | 238094.86 | 14-JUL-07:10 | 37611.08 | 01-JUL-05:10 | 675712.68 | 03-JUL-07:10 | 117191.64 | 14-JUL-07:19 | 202061.93 | 06-JUL-14:50 | 70380.47 | 12-JUL-15:30 | 0.00 | 01-JUL-00:10 |
August | 242522.88 | 21-AUG-07:10 | 37611.08 | 01-AUG-05:10 | 794004.08 | 01-AUG-07:10 | 117194.16 | 21-AUG-07:19 | 207541.00 | 29-AUG-15:50 | 71132.90 | 30-AUG-13:00 | 0.00 | 01-AUG-00:10 |
September | 250168.11 | 26-SEP-07:10 | 37611.08 | 01-SEP-05:10 | 439129.89 | 01-SEP-07:10 | 117198.51 | 26-SEP-07:19 | 203884.10 | 06-SEP-15:39 | 71016.10 | 01-SEP-14:20 | 0.00 | 01-SEP-00:10 |
October | 255624.72 | 25-OCT-07:10 | 37611.08 | 01-OCT-05:10 | 557421.28 | 02-OCT-07:10 | 117201.62 | 25-OCT-07:19 | 189733.25 | 12-OCT-15:39 | 73611.76 | 11-OCT-14:30 | 0.00 | 01-OCT-00:10 |
November | 253389.50 | 21-NOV-16:00 | 37611.08 | 01-NOV-05:10 | 675712.68 | 01-NOV-07:10 | 117200.24 | 01-NOV-07:19 | 168707.40 | 07-NOV-16:49 | 73100.78 | 02-NOV-13:09 | 0.00 | 01-NOV-00:10 |
December | 255205.66 | 12-DEC-08:09 | 37611.08 | 01-DEC-06:10 | 794004.08 | 01-DEC-08:09 | 117201.38 | 12-DEC-08:20 | 164332.06 | 14-DEC-16:49 | 72643.67 | 14-DEC-13:30 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 235832.96 | 37611.08 | 439129.89 | 117190.36 | 151013.44 | 70038.08 | 0.00 | |||||||
Maximum of Months | 255624.72 | 37611.08 | 794004.08 | 117201.62 | 261005.24 | 73611.76 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum} [W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY {Maximum} [W] | HUMIDIFIER:ELECTRICITY {TIMESTAMP} | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 292652.70 | 19-JAN-10:50 | 93886.47 | 18-JAN-14:00 | 4027.77 | 21-JAN-12:00 | 5613.48 | 02-JAN-10:50 | 0.00 | 0.00 |
February | 335464.94 | 24-FEB-13:09 | 93886.47 | 02-FEB-13:20 | 4043.93 | 16-FEB-21:00 | 5613.48 | 01-FEB-13:09 | 0.00 | 0.00 |
March | 363761.01 | 30-MAR-12:50 | 93886.47 | 06-MAR-09:50 | 4283.79 | 08-MAR-21:00 | 5613.48 | 04-MAR-16:10 | 0.00 | 0.00 |
April | 429723.76 | 28-APR-13:00 | 93886.47 | 14-APR-10:20 | 3733.87 | 11-APR-16:10 | 5613.48 | 01-APR-06:10 | 0.00 | 0.00 |
May | 323490.16 | 24-MAY-12:50 | 93886.47 | 01-MAY-06:40 | 0.00 | 01-MAY-00:10 | 5613.48 | 01-MAY-06:10 | 0.00 | 0.00 |
June | 370001.79 | 28-JUN-14:30 | 93886.47 | 01-JUN-06:30 | 0.00 | 01-JUN-00:10 | 5613.48 | 01-JUN-06:10 | 0.00 | 0.00 |
July | 418240.31 | 18-JUL-14:00 | 93886.47 | 01-JUL-07:10 | 0.00 | 01-JUL-00:10 | 5613.48 | 01-JUL-06:10 | 0.00 | 0.00 |
August | 443337.10 | 03-AUG-15:30 | 93886.47 | 01-AUG-07:40 | 0.00 | 01-AUG-00:10 | 5613.48 | 01-AUG-06:10 | 0.00 | 0.00 |
September | 328692.50 | 18-SEP-13:00 | 93886.47 | 01-SEP-06:10 | 0.00 | 01-SEP-00:10 | 5613.48 | 01-SEP-06:10 | 0.00 | 0.00 |
October | 388160.81 | 24-OCT-13:30 | 93886.47 | 02-OCT-09:50 | 2510.90 | 27-OCT-16:10 | 5613.48 | 02-OCT-09:39 | 0.00 | 0.00 |
November | 408552.39 | 02-NOV-13:09 | 93886.47 | 01-NOV-08:20 | 2664.89 | 22-NOV-18:10 | 5613.48 | 01-NOV-06:10 | 0.00 | 0.00 |
December | 424241.47 | 14-DEC-13:30 | 93886.47 | 11-DEC-10:20 | 3466.80 | 20-DEC-20:00 | 5613.48 | 02-DEC-13:30 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 292652.70 | 93886.47 | 0.00 | 5613.48 | 0.00 | 0.00 | ||||
Maximum of Months | 443337.10 | 93886.47 | 4283.79 | 5613.48 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 1345079.74 | 31-JAN-16:19 | 234435.00 | 439129.89 | 0.00 | 83146.17 | 141319.63 | 69642.79 | 0.00 | 277906.31 | 93886.47 |
February | 1515298.59 | 28-FEB-16:10 | 234435.00 | 557421.28 | 0.00 | 83146.17 | 157497.68 | 69838.04 | 0.00 | 313460.46 | 93886.47 |
March | 1678944.96 | 06-MAR-16:19 | 234435.00 | 675712.68 | 0.00 | 83146.17 | 168028.38 | 69528.22 | 0.00 | 348594.55 | 93886.47 |
April | 1901572.29 | 28-APR-15:09 | 234435.00 | 794004.08 | 0.00 | 83146.17 | 199677.44 | 69841.90 | 0.00 | 420967.75 | 93886.47 |
May | 1438105.25 | 17-MAY-15:50 | 234435.00 | 439129.89 | 0.00 | 83146.17 | 197371.06 | 70210.26 | 0.00 | 314312.92 | 93886.47 |
June | 1608137.44 | 28-JUN-15:20 | 234435.00 | 557421.28 | 0.00 | 83146.17 | 198039.28 | 70104.54 | 0.00 | 365491.21 | 93886.47 |
July | 1772619.75 | 18-JUL-15:20 | 234435.00 | 675712.68 | 0.00 | 83146.17 | 192274.85 | 70345.78 | 0.00 | 417205.31 | 93886.47 |
August | 1925340.49 | 03-AUG-15:20 | 234435.00 | 794004.08 | 0.00 | 83146.17 | 200875.52 | 70372.68 | 0.00 | 443007.08 | 93886.47 |
September | 1440386.78 | 06-SEP-15:30 | 234435.00 | 439129.89 | 0.00 | 83146.17 | 199517.21 | 70175.62 | 0.00 | 314482.93 | 93886.47 |
October | 1591812.26 | 06-OCT-15:00 | 234435.00 | 557421.28 | 0.00 | 83146.17 | 181965.06 | 70479.63 | 0.00 | 364865.16 | 93886.47 |
November | 1690341.90 | 03-NOV-15:00 | 234435.00 | 675712.68 | 0.00 | 83146.17 | 156403.94 | 70076.68 | 0.00 | 371067.47 | 93886.47 |
December | 1834878.73 | 12-DEC-16:30 | 239586.09 | 794004.08 | 0.00 | 83148.47 | 156386.94 | 69959.91 | 0.00 | 392293.29 | 93886.47 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1345079.74 | 234435.00 | 439129.89 | 0.00 | 83146.17 | 141319.63 | 69528.22 | 0.00 | 277906.31 | 93886.47 | |
Maximum of Months | 1925340.49 | 239586.09 | 794004.08 | 0.00 | 83148.47 | 200875.52 | 70479.63 | 0.00 | 443007.08 | 93886.47 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 404211.18 | 05-JAN-07:10 | 0.00 | 73397.75 | 25-JAN-12:20 | 0.00 |
February | 0.00 | 0.00 | 397592.43 | 06-FEB-07:10 | 0.00 | 73298.50 | 02-FEB-12:50 | 0.00 |
March | 0.00 | 0.00 | 341190.41 | 09-MAR-07:10 | 0.00 | 72048.76 | 06-MAR-12:00 | 0.00 |
April | 0.00 | 0.00 | 70880.51 | 18-APR-14:30 | 0.00 | 69029.66 | 04-APR-11:20 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 66573.75 | 02-MAY-11:50 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 62646.36 | 05-JUN-11:30 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 60186.17 | 06-JUL-11:50 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 61272.35 | 28-AUG-11:30 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 64604.33 | 29-SEP-11:30 | 0.00 |
October | 0.00 | 0.00 | 1704.83 | 28-OCT-06:40 | 0.00 | 67824.40 | 26-OCT-11:50 | 0.00 |
November | 0.00 | 0.00 | 68819.76 | 27-NOV-14:20 | 0.00 | 71170.87 | 29-NOV-12:50 | 0.00 |
December | 0.00 | 0.00 | 467400.92 | 21-DEC-07:10 | 0.00 | 72673.47 | 28-DEC-12:30 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 60186.17 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 467400.92 | 0.00 | 73397.75 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 26.42 | 0.50 | 26.47 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 26.43 | 0.67 | 26.53 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 26.13 | 0.00 | 26.13 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 25.95 | 0.00 | 25.95 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 26.26 | 0.17 | 26.20 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 26.11 | 0.00 | 26.11 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 26.43 | 0.17 | 26.39 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 26.05 | 0.17 | 26.08 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 26.61 | 0.00 | 26.61 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 26.61 | 0.17 | 26.62 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 26.75 | 0.67 | 26.80 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 | 26.72 | 0.67 | 26.77 |
Annual Sum or Average | 0.00 | 0.00 | 77.00 | 26.46 | 3.17 | 26.49 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 25.95 | 0.00 | 25.95 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 | 26.75 | 0.67 | 26.80 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.58 | 0.00 | 25.58 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.58 | 0.00 | 25.58 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.59 | 0.00 | 25.59 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 25.60 | 0.00 | 25.60 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.56 | 0.00 | 25.56 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.67 | 0.00 | 25.67 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 25.58 | 0.00 | 25.58 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 25.63 | 0.00 | 25.63 |
Annual Sum or Average | 0.00 | 0.00 | 4.17 | 25.60 | 0.00 | 25.60 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 25.67 | 0.00 | 25.67 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.56 | 0.00 | 25.56 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.17 | 25.56 | 0.00 | 25.56 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.56 | 0.00 | 25.56 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.17 | 19.34 | 0.00 | 19.34 | 0.00 | 19.34 | 0.00 | 19.34 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | 19.34 | 0.00 | 19.34 | 0.00 | 19.34 | 0.00 | 19.34 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 19.34 | 0.00 | 19.34 | 0.00 | 19.34 | 0.00 | 19.34 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 25.67 | 0.00 | 25.67 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.61 | 0.00 | 25.61 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 26.37 | 1.00 | 26.60 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 25.98 | 0.33 | 26.13 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.62 | 0.00 | 25.62 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.63 | 0.00 | 25.63 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 8.17 | 26.07 | 1.33 | 26.25 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 26.37 | 1.00 | 26.60 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.27 | 0.50 | 27.27 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.39 | 0.83 | 27.39 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.68 | 1.17 | 27.68 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 27.57 | 7.17 | 27.63 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.62 | 2.67 | 27.62 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 27.40 | 5.67 | 27.52 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 26.99 | 2.67 | 27.21 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27.56 | 6.83 | 27.61 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.58 | 3.67 | 27.58 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.37 | 0.67 | 27.37 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 34.67 | 27.47 | 31.83 | 27.54 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 27.68 | 7.17 | 27.68 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 27.76 | 6.17 | 27.76 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.65 | 2.83 | 27.65 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.50 | 2.33 | 27.50 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 26.88 | 1.00 | 26.88 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 26.01 | 0.17 | 26.22 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.62 | 0.00 | 25.62 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 26.38 | 1.33 | 26.65 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 26.81 | 4.67 | 27.04 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 27.39 | 7.83 | 27.51 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 13.67 | 27.48 | 10.50 | 27.62 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 27.50 | 10.33 | 27.50 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 27.82 | 7.17 | 27.84 |
Annual Sum or Average | 0.00 | 0.00 | 66.33 | 27.37 | 54.33 | 27.49 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.62 | 0.00 | 25.62 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 13.67 | 27.82 | 10.50 | 27.84 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.66 | 1.33 | 27.66 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.16 | 2.17 | 27.39 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 27.00 | 3.33 | 27.21 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 25.67 | 27.02 | 7.00 | 27.16 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 16.67 | 26.91 | 5.00 | 27.12 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 25.33 | 27.00 | 6.33 | 27.17 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 39.50 | 27.29 | 13.50 | 27.42 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 51.50 | 27.42 | 12.17 | 27.51 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 16.50 | 27.04 | 5.67 | 27.27 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 22.33 | 27.02 | 8.33 | 27.24 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 12.17 | 26.98 | 5.00 | 27.24 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 11.33 | 27.16 | 5.83 | 27.37 |
Annual Sum or Average | 0.00 | 0.00 | 235.67 | 27.15 | 75.67 | 27.32 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 26.91 | 1.33 | 27.12 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 51.50 | 27.66 | 13.50 | 27.66 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.69 | 0.00 | 25.69 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 26.42 | 0.17 | 26.70 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.61 | 0.00 | 25.61 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 26.45 | 0.33 | 26.73 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 1.67 | 26.11 | 0.50 | 26.38 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 26.45 | 0.33 | 26.73 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.47 | 0.50 | 27.47 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.88 | 1.17 | 27.88 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 27.65 | 8.33 | 27.71 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27.50 | 6.83 | 27.53 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 27.55 | 9.00 | 27.60 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 27.42 | 6.00 | 27.49 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 27.73 | 7.67 | 27.73 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.60 | 5.17 | 27.60 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.31 | 0.17 | 27.31 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 47.83 | 27.58 | 44.83 | 27.62 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 27.88 | 9.00 | 27.88 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.80 | 5.67 | 27.80 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.77 | 2.00 | 27.77 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.45 | 1.83 | 27.45 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 26.50 | 0.17 | 26.76 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.59 | 0.00 | 25.59 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 26.94 | 2.50 | 27.13 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 27.50 | 7.50 | 27.58 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 12.00 | 27.60 | 9.67 | 27.72 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 11.67 | 27.01 | 11.50 | 27.01 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.86 | 6.00 | 27.86 |
Annual Sum or Average | 0.00 | 0.00 | 52.33 | 27.44 | 46.83 | 27.50 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 12.00 | 27.86 | 11.50 | 27.86 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.31 | 0.17 | 27.31 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.82 | 0.50 | 27.82 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.57 | 0.83 | 27.57 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.75 | 1.67 | 27.78 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 27.40 | 3.17 | 27.56 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 27.12 | 3.17 | 27.33 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 13.17 | 27.05 | 5.33 | 27.23 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 26.74 | 3.67 | 26.99 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 27.54 | 3.83 | 27.72 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.63 | 4.00 | 27.72 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.49 | 1.00 | 27.49 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.49 | 0.50 | 27.49 |
Annual Sum or Average | 0.00 | 0.00 | 59.33 | 27.24 | 27.83 | 27.42 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.74 | 0.17 | 26.99 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 13.17 | 27.82 | 5.33 | 27.82 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.00 | 18.99 | 0.00 | 18.99 | 0.00 | 18.99 | 0.00 | 18.99 |
February | 2.83 | 17.33 | 1.50 | 17.10 | 0.00 | 17.10 | 0.00 | 17.10 |
March | 0.67 | 19.33 | 0.00 | 19.33 | 0.00 | 19.33 | 0.00 | 19.33 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.22 | 2.50 | 27.31 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.32 | 2.33 | 27.38 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 27.22 | 5.67 | 27.31 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.18 | 3.17 | 27.29 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.38 | 2.17 | 27.43 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.42 | 1.50 | 27.42 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.50 | 18.72 | 0.00 | 18.72 | 0.00 | 18.72 | 0.00 | 18.72 |
Annual Sum or Average | 6.00 | 18.22 | 1.50 | 17.91 | 26.17 | 25.18 | 17.33 | 25.95 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.83 | 19.33 | 1.50 | 19.33 | 9.00 | 27.42 | 5.67 | 27.43 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.50 | 18.98 | 0.00 | 18.98 | 0.00 | 18.98 | 0.00 | 18.98 |
February | 0.83 | 17.48 | 0.17 | 17.05 | 0.00 | 17.05 | 0.00 | 17.05 |
March | 0.50 | 19.40 | 0.00 | 19.40 | 0.50 | 23.37 | 0.50 | 24.70 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.68 | 2.33 | 27.68 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 27.74 | 8.50 | 27.84 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 27.62 | 7.50 | 27.69 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 17.17 | 27.59 | 13.33 | 27.67 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 27.52 | 8.00 | 27.61 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 | 27.75 | 10.83 | 27.79 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 27.65 | 6.67 | 27.65 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.50 | 18.77 | 0.00 | 18.77 | 0.00 | 18.77 | 0.00 | 18.77 |
Annual Sum or Average | 3.33 | 18.64 | 0.17 | 18.46 | 70.50 | 27.21 | 57.67 | 27.46 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.50 | 19.40 | 0.17 | 19.40 | 17.17 | 27.75 | 13.33 | 27.84 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.00 | 19.32 | 0.00 | 19.32 | 3.67 | 26.07 | 3.67 | 26.88 |
February | 0.33 | 18.65 | 0.00 | 18.65 | 1.67 | 26.30 | 1.67 | 27.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.50 | 2.00 | 27.50 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.42 | 1.00 | 27.42 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.29 | 3.67 | 27.37 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.26 | 2.50 | 27.33 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 27.21 | 6.33 | 27.31 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 27.30 | 5.50 | 27.41 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 12.83 | 27.57 | 8.67 | 27.69 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 13.33 | 27.67 | 9.17 | 27.83 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 27.72 | 7.17 | 27.73 |
December | 0.50 | 19.11 | 0.00 | 19.11 | 4.50 | 27.06 | 4.33 | 27.48 |
Annual Sum or Average | 1.83 | 19.14 | 0.00 | 19.14 | 72.83 | 27.33 | 55.67 | 27.51 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 26.07 | 1.00 | 26.88 |
Maximum of Months | 1.00 | 19.32 | 0.00 | 19.32 | 13.33 | 27.72 | 9.17 | 27.83 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.00 | 19.11 | 0.00 | 19.11 | 0.17 | 20.28 | 0.17 | 21.16 |
February | 0.33 | 18.65 | 0.00 | 18.65 | 0.67 | 24.68 | 0.67 | 25.88 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.58 | 1.00 | 27.58 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.83 | 1.67 | 27.88 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 27.72 | 3.67 | 27.83 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 27.42 | 3.67 | 27.60 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 17.67 | 27.30 | 7.83 | 27.46 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 27.03 | 4.33 | 27.26 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 27.69 | 5.33 | 27.83 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 27.71 | 4.67 | 27.82 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.53 | 1.00 | 27.53 |
December | 0.50 | 19.07 | 0.00 | 19.07 | 0.50 | 23.35 | 0.50 | 24.77 |
Annual Sum or Average | 1.83 | 19.02 | 0.00 | 19.02 | 71.67 | 27.25 | 34.50 | 27.47 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 20.28 | 0.17 | 21.16 |
Maximum of Months | 1.00 | 19.11 | 0.00 | 19.11 | 17.67 | 27.83 | 7.83 | 27.88 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.62 | 1.00 | 27.62 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 47.67 | 27.74 | 47.67 | 27.74 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 48.67 | 27.73 | 48.67 | 27.73 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 47.67 | 27.74 | 47.67 | 27.74 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.66 | 1.67 | 27.66 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 51.67 | 27.74 | 51.67 | 27.74 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 53.33 | 27.74 | 53.33 | 27.74 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 51.67 | 27.74 | 51.67 | 27.74 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.61 | 0.67 | 27.61 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 26.50 | 27.72 | 26.50 | 27.72 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 27.17 | 27.71 | 27.17 | 27.71 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 26.50 | 27.72 | 26.50 | 27.72 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 105.83 | 28.15 | 104.50 | 28.15 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 493.83 | 28.88 | 415.00 | 28.95 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 40.83 | 28.03 | 40.83 | 28.03 |
Annual Sum or Average | 0.00 | 0.00 | 640.50 | 28.70 | 560.33 | 28.75 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 493.83 | 28.88 | 415.00 | 28.95 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 56.83 | 24.52 | 238.50 | 25.01 | 39.50 | 24.98 |
February | 90.50 | 24.58 | 311.17 | 24.70 | 70.00 | 24.70 |
March | 106.17 | 24.57 | 311.50 | 24.63 | 82.00 | 24.65 |
April | 172.83 | 24.75 | 430.17 | 24.62 | 172.83 | 24.65 |
May | 292.50 | 24.87 | 508.00 | 24.63 | 292.50 | 24.70 |
June | 252.00 | 24.85 | 496.00 | 24.58 | 252.00 | 24.65 |
July | 245.33 | 25.23 | 497.00 | 24.82 | 245.33 | 24.92 |
August | 180.33 | 25.28 | 514.00 | 24.70 | 180.33 | 24.82 |
September | 219.50 | 25.19 | 485.00 | 24.76 | 219.50 | 24.86 |
October | 165.67 | 25.47 | 452.50 | 24.89 | 165.67 | 25.02 |
November | 75.00 | 25.34 | 381.00 | 24.88 | 75.00 | 24.95 |
December | 62.17 | 24.99 | 309.83 | 24.97 | 58.17 | 24.98 |
Annual Sum or Average | 1918.83 | 25.01 | 4934.67 | 24.74 | 1852.83 | 24.81 |
Minimum of Months | 56.83 | 24.52 | 238.50 | 24.58 | 39.50 | 24.65 |
Maximum of Months | 292.50 | 25.47 | 514.00 | 25.01 | 292.50 | 25.02 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 45.67 | 23.90 | 215.33 | 24.52 | 0.33 | 24.53 |
February | 24.50 | 23.91 | 306.67 | 24.40 | 0.00 | 24.40 |
March | 15.50 | 23.88 | 317.67 | 24.41 | 0.00 | 24.41 |
April | 0.00 | 0.00 | 433.17 | 24.28 | 0.00 | 24.28 |
May | 0.00 | 0.00 | 508.00 | 24.26 | 0.00 | 24.26 |
June | 0.00 | 0.00 | 496.00 | 24.17 | 0.00 | 24.17 |
July | 0.00 | 0.00 | 497.00 | 24.21 | 0.00 | 24.21 |
August | 0.00 | 0.00 | 514.00 | 24.17 | 0.00 | 24.17 |
September | 0.00 | 0.00 | 485.00 | 24.27 | 0.00 | 24.27 |
October | 0.00 | 0.00 | 451.83 | 24.35 | 0.00 | 24.35 |
November | 0.00 | 0.00 | 380.33 | 24.46 | 0.00 | 24.46 |
December | 8.00 | 23.98 | 311.50 | 24.53 | 0.00 | 24.53 |
Annual Sum or Average | 93.67 | 23.91 | 4916.50 | 24.31 | 0.33 | 24.31 |
Minimum of Months | 0.00 | 0.00 | 215.33 | 24.17 | 0.00 | 24.17 |
Maximum of Months | 45.67 | 23.98 | 514.00 | 24.53 | 0.33 | 24.53 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 216.67 | 23.59 | 140.67 | 23.84 | 0.00 | 23.84 |
February | 123.33 | 23.62 | 229.00 | 24.00 | 0.00 | 24.00 |
March | 119.50 | 23.63 | 249.17 | 24.06 | 0.00 | 24.06 |
April | 5.83 | 23.95 | 405.33 | 24.31 | 0.00 | 24.31 |
May | 0.00 | 0.00 | 506.67 | 24.23 | 0.00 | 24.23 |
June | 0.00 | 0.00 | 495.83 | 24.19 | 0.00 | 24.19 |
July | 0.00 | 0.00 | 496.17 | 24.20 | 0.00 | 24.20 |
August | 0.00 | 0.00 | 514.00 | 24.21 | 0.00 | 24.21 |
September | 0.00 | 0.00 | 481.33 | 24.18 | 0.00 | 24.18 |
October | 14.83 | 23.72 | 439.50 | 24.27 | 0.00 | 24.27 |
November | 46.17 | 23.72 | 303.83 | 24.22 | 0.00 | 24.22 |
December | 138.00 | 23.55 | 209.33 | 24.00 | 0.00 | 24.00 |
Annual Sum or Average | 664.33 | 23.61 | 4470.83 | 24.16 | 0.00 | 24.16 |
Minimum of Months | 0.00 | 0.00 | 140.67 | 23.84 | 0.00 | 23.84 |
Maximum of Months | 216.67 | 23.95 | 514.00 | 24.31 | 0.00 | 24.31 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 351.17 | 22.66 | 122.83 | 22.99 | 7.00 | 22.95 |
February | 206.50 | 22.60 | 197.00 | 23.16 | 19.00 | 23.04 |
March | 191.17 | 22.95 | 234.33 | 23.58 | 5.83 | 23.53 |
April | 30.33 | 23.47 | 381.50 | 24.21 | 0.00 | 24.21 |
May | 0.00 | 0.00 | 508.00 | 24.28 | 0.00 | 24.28 |
June | 0.00 | 0.00 | 496.00 | 24.25 | 0.00 | 24.25 |
July | 0.00 | 0.00 | 497.00 | 24.28 | 0.00 | 24.28 |
August | 0.00 | 0.00 | 514.00 | 24.26 | 0.00 | 24.26 |
September | 0.00 | 0.00 | 485.00 | 24.25 | 0.00 | 24.25 |
October | 39.00 | 23.31 | 427.17 | 24.23 | 0.00 | 24.23 |
November | 148.67 | 23.32 | 247.83 | 23.85 | 0.00 | 23.85 |
December | 261.17 | 22.82 | 165.17 | 23.30 | 4.33 | 23.28 |
Annual Sum or Average | 1228.00 | 22.85 | 4275.83 | 23.91 | 36.17 | 23.89 |
Minimum of Months | 0.00 | 0.00 | 122.83 | 22.99 | 0.00 | 22.95 |
Maximum of Months | 351.17 | 23.47 | 514.00 | 24.28 | 19.00 | 24.28 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 320.67 | 22.84 | 137.00 | 23.25 | 0.00 | 23.25 |
February | 184.67 | 22.94 | 211.17 | 23.56 | 4.17 | 23.53 |
March | 185.67 | 23.29 | 241.67 | 23.83 | 0.00 | 23.83 |
April | 25.67 | 23.72 | 404.17 | 24.19 | 0.00 | 24.19 |
May | 19.83 | 26.15 | 508.00 | 24.47 | 19.83 | 24.53 |
June | 4.67 | 26.69 | 496.00 | 24.37 | 4.67 | 24.39 |
July | 23.83 | 26.66 | 497.00 | 24.56 | 23.83 | 24.65 |
August | 15.50 | 26.67 | 514.00 | 24.38 | 15.50 | 24.45 |
September | 20.67 | 26.12 | 485.00 | 24.47 | 20.67 | 24.54 |
October | 48.33 | 24.57 | 437.83 | 24.41 | 18.83 | 24.47 |
November | 106.17 | 23.61 | 269.83 | 24.06 | 0.00 | 24.06 |
December | 203.33 | 23.19 | 200.50 | 23.70 | 0.00 | 23.70 |
Annual Sum or Average | 1159.00 | 23.41 | 4402.17 | 24.14 | 107.50 | 24.17 |
Minimum of Months | 4.67 | 22.84 | 137.00 | 23.25 | 0.00 | 23.25 |
Maximum of Months | 320.67 | 26.69 | 514.00 | 24.56 | 23.83 | 24.65 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 265.50 | 22.98 | 148.83 | 23.51 | 3.00 | 23.53 |
February | 163.33 | 23.04 | 215.67 | 23.72 | 3.00 | 23.72 |
March | 163.00 | 23.07 | 251.50 | 23.84 | 4.17 | 23.87 |
April | 32.17 | 24.03 | 395.33 | 24.22 | 6.00 | 24.26 |
May | 49.50 | 26.63 | 508.00 | 24.65 | 49.50 | 24.81 |
June | 25.33 | 26.72 | 496.00 | 24.47 | 25.33 | 24.57 |
July | 44.17 | 26.71 | 497.00 | 24.63 | 44.17 | 24.79 |
August | 24.33 | 26.69 | 514.00 | 24.39 | 24.33 | 24.49 |
September | 49.67 | 26.69 | 485.00 | 24.66 | 49.67 | 24.84 |
October | 55.00 | 25.31 | 436.50 | 24.53 | 33.33 | 24.66 |
November | 89.83 | 23.49 | 298.17 | 24.15 | 2.83 | 24.17 |
December | 198.67 | 22.88 | 194.50 | 23.56 | 0.50 | 23.56 |
Annual Sum or Average | 1160.50 | 23.78 | 4440.50 | 24.25 | 245.83 | 24.35 |
Minimum of Months | 24.33 | 22.88 | 148.83 | 23.51 | 0.50 | 23.53 |
Maximum of Months | 265.50 | 26.72 | 514.00 | 24.66 | 49.67 | 24.84 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 173.83 | 23.58 | 222.67 | 24.18 | 21.50 | 24.32 |
February | 101.50 | 23.47 | 294.33 | 24.16 | 13.83 | 24.21 |
March | 135.17 | 23.34 | 289.50 | 24.05 | 10.17 | 24.12 |
April | 21.00 | 24.33 | 409.33 | 24.31 | 4.83 | 24.34 |
May | 28.33 | 26.25 | 508.00 | 24.50 | 28.33 | 24.59 |
June | 7.00 | 26.64 | 496.00 | 24.37 | 7.00 | 24.40 |
July | 29.17 | 26.65 | 497.00 | 24.57 | 29.17 | 24.68 |
August | 25.33 | 26.76 | 514.00 | 24.46 | 25.33 | 24.56 |
September | 48.67 | 26.69 | 485.00 | 24.69 | 48.67 | 24.86 |
October | 61.83 | 26.29 | 458.33 | 24.77 | 52.33 | 24.96 |
November | 56.83 | 25.44 | 393.83 | 24.69 | 30.67 | 24.84 |
December | 123.83 | 23.94 | 299.67 | 24.43 | 25.83 | 24.58 |
Annual Sum or Average | 812.50 | 24.45 | 4867.67 | 24.45 | 297.67 | 24.56 |
Minimum of Months | 7.00 | 23.34 | 222.67 | 24.05 | 4.83 | 24.12 |
Maximum of Months | 173.83 | 26.76 | 514.00 | 24.77 | 52.33 | 24.96 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 199.67 | 23.29 | 212.67 | 23.93 | 6.00 | 23.97 |
February | 83.00 | 23.75 | 311.33 | 24.36 | 9.33 | 24.42 |
March | 57.00 | 24.69 | 364.17 | 24.58 | 19.67 | 24.68 |
April | 49.67 | 26.85 | 467.33 | 24.81 | 49.67 | 24.99 |
May | 46.83 | 26.82 | 508.00 | 24.71 | 46.83 | 24.88 |
June | 54.33 | 26.82 | 496.00 | 24.72 | 54.33 | 24.91 |
July | 88.67 | 26.79 | 497.00 | 24.96 | 88.67 | 25.20 |
August | 88.50 | 26.77 | 514.00 | 24.86 | 88.50 | 25.10 |
September | 50.67 | 26.78 | 485.00 | 24.76 | 50.67 | 24.93 |
October | 58.50 | 26.67 | 470.83 | 24.85 | 54.83 | 25.04 |
November | 31.67 | 26.55 | 423.17 | 24.76 | 27.33 | 24.88 |
December | 53.67 | 25.61 | 347.67 | 24.89 | 32.17 | 25.04 |
Annual Sum or Average | 862.17 | 25.46 | 5097.17 | 24.71 | 528.00 | 24.88 |
Minimum of Months | 31.67 | 23.29 | 212.67 | 23.93 | 6.00 | 23.97 |
Maximum of Months | 199.67 | 26.85 | 514.00 | 24.96 | 88.67 | 25.20 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 396.33 | 21.82 | 112.00 | 22.07 | 38.33 | 21.99 |
February | 292.33 | 22.06 | 143.17 | 22.44 | 28.33 | 22.28 |
March | 288.33 | 22.48 | 169.33 | 22.96 | 13.83 | 22.88 |
April | 97.50 | 23.61 | 326.00 | 24.08 | 12.67 | 24.12 |
May | 49.50 | 25.82 | 508.00 | 24.53 | 49.50 | 24.63 |
June | 32.67 | 26.21 | 496.00 | 24.50 | 32.67 | 24.60 |
July | 63.67 | 26.19 | 497.00 | 24.68 | 63.67 | 24.84 |
August | 55.33 | 26.02 | 514.00 | 24.53 | 55.33 | 24.66 |
September | 70.50 | 25.63 | 485.00 | 24.52 | 70.50 | 24.65 |
October | 104.33 | 24.29 | 407.83 | 24.35 | 48.00 | 24.47 |
November | 247.83 | 22.83 | 181.67 | 23.37 | 5.17 | 23.38 |
December | 349.50 | 22.13 | 128.00 | 22.53 | 21.50 | 22.48 |
Annual Sum or Average | 2047.83 | 22.88 | 3968.00 | 23.77 | 439.50 | 23.83 |
Minimum of Months | 32.67 | 21.82 | 112.00 | 22.07 | 5.17 | 21.99 |
Maximum of Months | 396.33 | 26.21 | 514.00 | 24.68 | 70.50 | 24.84 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 314.83 | 22.26 | 95.50 | 22.64 | 15.83 | 22.60 |
February | 210.00 | 22.37 | 130.17 | 22.89 | 17.33 | 22.78 |
March | 201.00 | 22.60 | 183.00 | 23.39 | 10.33 | 23.38 |
April | 60.67 | 24.24 | 311.17 | 24.42 | 22.17 | 24.52 |
May | 68.83 | 26.51 | 430.00 | 24.85 | 68.83 | 25.05 |
June | 50.33 | 26.61 | 417.33 | 24.75 | 50.33 | 24.93 |
July | 71.17 | 26.66 | 422.00 | 24.95 | 71.17 | 25.17 |
August | 62.33 | 26.44 | 433.00 | 24.75 | 62.33 | 24.94 |
September | 75.00 | 26.29 | 409.00 | 24.81 | 75.00 | 25.01 |
October | 95.50 | 24.98 | 349.83 | 24.67 | 55.17 | 24.86 |
November | 165.83 | 23.14 | 193.00 | 23.81 | 7.00 | 23.85 |
December | 272.67 | 22.36 | 123.00 | 22.85 | 16.67 | 22.82 |
Annual Sum or Average | 1648.17 | 23.49 | 3497.00 | 24.15 | 472.17 | 24.29 |
Minimum of Months | 50.33 | 22.26 | 95.50 | 22.64 | 7.00 | 22.60 |
Maximum of Months | 314.83 | 26.66 | 433.00 | 24.95 | 75.00 | 25.17 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 209.17 | 23.20 | 206.67 | 23.89 | 28.50 | 24.03 |
February | 137.17 | 22.97 | 259.33 | 23.83 | 18.00 | 23.82 |
March | 184.67 | 22.84 | 251.00 | 23.65 | 12.33 | 23.67 |
April | 60.50 | 24.04 | 373.67 | 24.30 | 16.17 | 24.36 |
May | 55.83 | 25.88 | 508.00 | 24.55 | 55.83 | 24.67 |
June | 31.83 | 26.10 | 496.00 | 24.47 | 31.83 | 24.57 |
July | 63.50 | 26.18 | 497.00 | 24.67 | 63.50 | 24.82 |
August | 59.33 | 26.23 | 514.00 | 24.60 | 59.33 | 24.75 |
September | 76.50 | 26.23 | 485.00 | 24.72 | 76.50 | 24.90 |
October | 86.33 | 25.83 | 452.00 | 24.78 | 64.00 | 24.98 |
November | 88.67 | 24.60 | 356.83 | 24.58 | 32.83 | 24.74 |
December | 175.50 | 23.32 | 275.33 | 24.09 | 28.50 | 24.22 |
Annual Sum or Average | 1229.00 | 24.15 | 4674.83 | 24.38 | 487.33 | 24.52 |
Minimum of Months | 31.83 | 22.84 | 206.67 | 23.65 | 12.33 | 23.67 |
Maximum of Months | 209.17 | 26.23 | 514.00 | 24.78 | 76.50 | 24.98 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 329.00 | 22.26 | 134.67 | 22.75 | 17.33 | 22.72 |
February | 213.67 | 22.36 | 201.83 | 23.10 | 17.83 | 23.01 |
March | 208.83 | 22.66 | 242.33 | 23.48 | 12.00 | 23.48 |
April | 57.67 | 24.64 | 392.67 | 24.46 | 22.00 | 24.56 |
May | 54.00 | 26.29 | 508.00 | 24.65 | 54.00 | 24.79 |
June | 43.83 | 26.65 | 496.00 | 24.65 | 43.83 | 24.80 |
July | 72.50 | 26.53 | 497.00 | 24.82 | 72.50 | 25.01 |
August | 58.83 | 26.55 | 514.00 | 24.68 | 58.83 | 24.85 |
September | 70.50 | 26.19 | 485.00 | 24.68 | 70.50 | 24.85 |
October | 84.17 | 25.14 | 439.00 | 24.59 | 51.83 | 24.75 |
November | 163.50 | 23.19 | 256.17 | 23.86 | 9.17 | 23.91 |
December | 267.17 | 22.45 | 186.17 | 23.18 | 11.00 | 23.18 |
Annual Sum or Average | 1623.67 | 23.45 | 4352.83 | 24.14 | 440.83 | 24.26 |
Minimum of Months | 43.83 | 22.26 | 134.67 | 22.75 | 9.17 | 22.72 |
Maximum of Months | 329.00 | 26.65 | 514.00 | 24.82 | 72.50 | 25.01 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 422.67 | 21.32 | 189.33 | 21.38 | 131.33 | 21.22 |
February | 326.17 | 21.62 | 169.50 | 21.77 | 82.00 | 21.52 |
March | 319.50 | 22.02 | 195.00 | 22.41 | 54.00 | 22.20 |
April | 141.00 | 23.21 | 301.67 | 23.90 | 13.17 | 23.94 |
May | 66.33 | 26.03 | 508.00 | 24.61 | 66.33 | 24.76 |
June | 46.00 | 26.38 | 494.83 | 24.58 | 46.00 | 24.73 |
July | 68.17 | 26.43 | 497.00 | 24.76 | 68.17 | 24.94 |
August | 66.17 | 26.12 | 514.00 | 24.59 | 66.17 | 24.75 |
September | 82.83 | 25.73 | 483.83 | 24.59 | 82.83 | 24.73 |
October | 124.00 | 24.00 | 399.67 | 24.30 | 54.33 | 24.44 |
November | 290.50 | 22.37 | 170.67 | 22.90 | 23.67 | 22.86 |
December | 373.83 | 21.61 | 179.50 | 21.87 | 88.67 | 21.72 |
Annual Sum or Average | 2327.17 | 22.57 | 4103.00 | 23.48 | 776.67 | 23.47 |
Minimum of Months | 46.00 | 21.32 | 169.50 | 21.38 | 13.17 | 21.22 |
Maximum of Months | 422.67 | 26.43 | 514.00 | 24.76 | 131.33 | 24.94 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 392.17 | 21.74 | 148.50 | 21.93 | 71.00 | 21.77 |
February | 271.83 | 21.93 | 160.83 | 22.31 | 41.83 | 22.08 |
March | 248.33 | 22.23 | 243.50 | 22.99 | 41.50 | 22.86 |
April | 90.83 | 23.69 | 360.67 | 24.23 | 23.00 | 24.32 |
May | 72.83 | 26.49 | 508.00 | 24.75 | 72.83 | 24.94 |
June | 55.17 | 26.66 | 494.50 | 24.68 | 55.17 | 24.86 |
July | 73.67 | 26.74 | 497.00 | 24.87 | 73.67 | 25.08 |
August | 66.50 | 26.46 | 514.00 | 24.67 | 66.50 | 24.86 |
September | 82.00 | 26.25 | 482.83 | 24.73 | 82.00 | 24.92 |
October | 121.00 | 24.58 | 414.00 | 24.52 | 61.67 | 24.72 |
November | 216.67 | 22.79 | 208.83 | 23.50 | 8.50 | 23.52 |
December | 344.33 | 21.92 | 163.17 | 22.34 | 49.67 | 22.21 |
Annual Sum or Average | 2035.33 | 23.04 | 4195.83 | 23.85 | 647.33 | 23.92 |
Minimum of Months | 55.17 | 21.74 | 148.50 | 21.93 | 8.50 | 21.77 |
Maximum of Months | 392.17 | 26.74 | 514.00 | 24.87 | 82.00 | 25.08 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 256.33 | 22.55 | 199.83 | 23.17 | 52.83 | 23.14 |
February | 184.00 | 22.35 | 248.17 | 23.25 | 34.33 | 23.13 |
March | 221.83 | 22.38 | 255.00 | 23.14 | 42.50 | 23.02 |
April | 96.33 | 23.56 | 347.17 | 24.17 | 18.50 | 24.24 |
May | 67.17 | 26.02 | 508.00 | 24.61 | 67.17 | 24.76 |
June | 45.00 | 26.29 | 494.83 | 24.56 | 45.00 | 24.69 |
July | 67.17 | 26.39 | 497.00 | 24.74 | 67.17 | 24.92 |
August | 65.17 | 26.25 | 514.00 | 24.63 | 65.17 | 24.79 |
September | 83.67 | 26.18 | 484.17 | 24.74 | 83.67 | 24.92 |
October | 96.33 | 25.46 | 446.83 | 24.73 | 66.00 | 24.94 |
November | 120.50 | 23.74 | 326.00 | 24.33 | 27.50 | 24.46 |
December | 215.83 | 22.66 | 259.50 | 23.55 | 42.83 | 23.56 |
Annual Sum or Average | 1519.33 | 23.65 | 4580.50 | 24.19 | 612.67 | 24.28 |
Minimum of Months | 45.00 | 22.35 | 199.83 | 23.14 | 18.50 | 23.02 |
Maximum of Months | 256.33 | 26.39 | 514.00 | 24.74 | 83.67 | 24.94 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 366.00 | 21.75 | 164.17 | 22.09 | 67.17 | 21.96 |
February | 258.50 | 21.92 | 197.33 | 22.51 | 45.50 | 22.31 |
March | 249.83 | 22.20 | 238.67 | 22.97 | 35.83 | 22.85 |
April | 89.67 | 23.88 | 364.83 | 24.31 | 23.17 | 24.42 |
May | 62.50 | 26.27 | 508.00 | 24.67 | 62.50 | 24.83 |
June | 52.50 | 26.66 | 495.00 | 24.69 | 52.50 | 24.86 |
July | 80.17 | 26.60 | 497.00 | 24.87 | 80.17 | 25.08 |
August | 66.83 | 26.60 | 514.00 | 24.72 | 66.83 | 24.91 |
September | 77.33 | 26.16 | 482.83 | 24.70 | 77.33 | 24.87 |
October | 100.83 | 24.76 | 428.50 | 24.54 | 57.17 | 24.71 |
November | 215.67 | 22.70 | 223.17 | 23.49 | 11.67 | 23.54 |
December | 305.33 | 21.95 | 191.17 | 22.59 | 41.17 | 22.50 |
Annual Sum or Average | 1925.17 | 23.05 | 4304.67 | 23.90 | 621.00 | 23.98 |
Minimum of Months | 52.50 | 21.75 | 164.17 | 22.09 | 11.67 | 21.96 |
Maximum of Months | 366.00 | 26.66 | 514.00 | 24.87 | 80.17 | 25.08 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.50 | 27.00 | 502.00 | 27.00 | 4.50 | 27.00 |
February | 15.83 | 27.00 | 454.00 | 27.00 | 15.83 | 27.00 |
March | 59.00 | 27.00 | 514.00 | 27.00 | 59.00 | 27.00 |
April | 262.17 | 27.01 | 485.00 | 27.01 | 262.17 | 27.01 |
May | 11.83 | 27.00 | 508.00 | 27.00 | 11.83 | 27.00 |
June | 109.00 | 27.00 | 496.00 | 27.00 | 109.00 | 27.00 |
July | 271.17 | 27.00 | 497.00 | 27.00 | 271.17 | 27.00 |
August | 484.17 | 27.14 | 514.00 | 27.14 | 484.17 | 27.14 |
September | 37.17 | 27.00 | 485.00 | 27.00 | 37.17 | 27.00 |
October | 98.17 | 27.00 | 502.00 | 27.00 | 98.17 | 27.00 |
November | 95.50 | 27.00 | 489.00 | 27.00 | 95.50 | 27.00 |
December | 154.67 | 27.00 | 497.00 | 27.00 | 154.67 | 27.00 |
Annual Sum or Average | 1603.17 | 27.04 | 5943.00 | 27.02 | 1603.17 | 27.02 |
Minimum of Months | 4.50 | 27.00 | 454.00 | 27.00 | 4.50 | 27.00 |
Maximum of Months | 484.17 | 27.14 | 514.00 | 27.14 | 484.17 | 27.14 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 502.00 | 27.00 | 0.00 | 27.00 |
February | 0.00 | 0.00 | 451.67 | 27.00 | 0.00 | 27.00 |
March | 0.00 | 0.00 | 514.00 | 27.00 | 0.00 | 27.00 |
April | 6.83 | 27.31 | 485.00 | 27.01 | 6.83 | 27.01 |
May | 0.00 | 0.00 | 508.00 | 27.00 | 0.00 | 27.00 |
June | 0.00 | 0.00 | 496.00 | 27.00 | 0.00 | 27.00 |
July | 1.17 | 27.00 | 497.00 | 27.00 | 1.17 | 27.00 |
August | 123.67 | 27.52 | 514.00 | 27.21 | 123.67 | 27.26 |
September | 0.00 | 0.00 | 485.00 | 27.00 | 0.00 | 27.00 |
October | 0.50 | 27.00 | 502.00 | 27.00 | 0.50 | 27.00 |
November | 1.50 | 27.00 | 489.00 | 27.00 | 1.50 | 27.00 |
December | 4.67 | 27.00 | 497.00 | 27.00 | 4.67 | 27.00 |
Annual Sum or Average | 138.33 | 27.48 | 5940.67 | 27.02 | 138.33 | 27.03 |
Minimum of Months | 0.00 | 0.00 | 451.67 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 123.67 | 27.52 | 514.00 | 27.21 | 123.67 | 27.26 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 5.50 | 26.19 | 481.17 | 26.99 | 0.00 | 26.99 |
February | 7.67 | 27.00 | 436.33 | 27.00 | 1.67 | 27.00 |
March | 1.33 | 27.00 | 507.00 | 27.00 | 1.33 | 27.00 |
April | 39.83 | 27.04 | 485.00 | 27.01 | 39.83 | 27.01 |
May | 15.33 | 27.00 | 508.00 | 27.00 | 15.33 | 27.00 |
June | 37.67 | 27.00 | 496.00 | 27.00 | 37.67 | 27.00 |
July | 76.50 | 27.00 | 497.00 | 27.00 | 76.50 | 27.00 |
August | 144.50 | 27.29 | 514.00 | 27.13 | 144.50 | 27.16 |
September | 19.17 | 27.00 | 485.00 | 27.00 | 19.17 | 27.00 |
October | 31.33 | 27.00 | 502.00 | 27.00 | 31.33 | 27.00 |
November | 6.67 | 27.00 | 489.00 | 27.00 | 6.67 | 27.00 |
December | 9.17 | 27.00 | 490.33 | 27.00 | 9.17 | 27.00 |
Annual Sum or Average | 394.67 | 27.10 | 5890.83 | 27.01 | 383.17 | 27.02 |
Minimum of Months | 1.33 | 26.19 | 436.33 | 26.99 | 0.00 | 26.99 |
Maximum of Months | 144.50 | 27.29 | 514.00 | 27.13 | 144.50 | 27.16 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 27.00 | 502.00 | 27.00 | 502.00 | 27.00 |
February | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
March | 514.00 | 27.00 | 514.00 | 27.00 | 514.00 | 27.00 |
April | 485.00 | 27.28 | 485.00 | 27.28 | 485.00 | 27.28 |
May | 508.00 | 27.00 | 508.00 | 27.00 | 508.00 | 27.00 |
June | 496.00 | 27.00 | 496.00 | 27.00 | 496.00 | 27.00 |
July | 497.00 | 27.00 | 497.00 | 27.00 | 497.00 | 27.00 |
August | 514.00 | 28.68 | 514.00 | 28.68 | 514.00 | 28.68 |
September | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
October | 502.00 | 27.00 | 502.00 | 27.00 | 502.00 | 27.00 |
November | 489.00 | 27.00 | 489.00 | 27.00 | 489.00 | 27.00 |
December | 497.00 | 27.11 | 497.00 | 27.11 | 497.00 | 27.11 |
Annual Sum or Average | 5943.00 | 27.18 | 5943.00 | 27.18 | 5943.00 | 27.18 |
Minimum of Months | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
Maximum of Months | 514.00 | 28.68 | 514.00 | 28.68 | 514.00 | 28.68 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00021 | 32.41350 | 0.88576 | 21.69884 |
February | 454.00000 | 27.00094 | 33.67847 | 0.94033 | 23.79517 |
March | 514.00000 | 27.00055 | 33.95099 | 0.97846 | 25.29395 |
April | 485.00000 | 27.00401 | 36.63871 | 1.04973 | 28.29059 |
May | 508.00000 | 27.00035 | 42.22260 | 0.34470 | 7.51351 |
June | 496.00000 | 27.00234 | 40.64782 | 0.38074 | 8.05580 |
July | 497.00000 | 27.00136 | 39.91345 | 0.42335 | 8.77134 |
August | 514.00000 | 27.13143 | 39.22418 | 0.50720 | 10.54353 |
September | 485.00000 | 27.00020 | 42.61318 | 0.35024 | 7.59969 |
October | 502.00000 | 27.00182 | 38.51082 | 1.01328 | 26.72956 |
November | 489.00000 | 27.00064 | 35.55206 | 1.00702 | 26.46487 |
December | 497.00000 | 27.00017 | 33.55634 | 1.00908 | 26.57764 |
Annual Sum or Average | 5943.00000 | 27.01241 | 37.43111 | 0.73888 | 18.38526 |
Minimum of Months | 454.00000 | 27.00017 | 32.41350 | 0.34470 | 7.51351 |
Maximum of Months | 514.00000 | 27.13143 | 42.61318 | 1.04973 | 28.29059 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00013 | 32.49914 | 0.81196 | 19.09821 |
February | 454.00000 | 27.00089 | 33.69464 | 0.85348 | 20.58534 |
March | 514.00000 | 27.00052 | 33.92015 | 0.88319 | 21.60031 |
April | 485.00000 | 27.00493 | 36.59214 | 0.96089 | 24.55059 |
May | 508.00000 | 27.00020 | 42.42097 | 0.29973 | 6.91244 |
June | 496.00000 | 27.00223 | 40.71039 | 0.31380 | 7.08656 |
July | 497.00000 | 27.00137 | 39.92894 | 0.32967 | 7.29590 |
August | 514.00000 | 27.13538 | 39.21660 | 0.38270 | 8.22749 |
September | 485.00000 | 27.00012 | 42.90302 | 0.29615 | 6.87511 |
October | 502.00000 | 27.00173 | 38.56250 | 0.95540 | 24.35020 |
November | 489.00000 | 27.00062 | 35.52266 | 0.91219 | 22.65342 |
December | 497.00000 | 27.00015 | 33.50296 | 0.88044 | 21.51456 |
Annual Sum or Average | 5943.00000 | 27.01277 | 37.47707 | 0.65462 | 15.84260 |
Minimum of Months | 454.00000 | 27.00012 | 32.49914 | 0.29615 | 6.87511 |
Maximum of Months | 514.00000 | 27.13538 | 42.90302 | 0.96089 | 24.55059 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.98190 | 32.59388 | 0.75799 | 17.51511 |
February | 454.00000 | 27.00091 | 33.74378 | 0.81610 | 19.46089 |
March | 514.00000 | 27.00054 | 33.95035 | 0.85753 | 20.78953 |
April | 485.00000 | 27.00337 | 36.62199 | 0.95777 | 24.46916 |
May | 508.00000 | 27.00029 | 42.34730 | 0.31743 | 7.17538 |
June | 496.00000 | 27.00235 | 40.69575 | 0.33611 | 7.42565 |
July | 497.00000 | 27.00144 | 39.94094 | 0.35313 | 7.66684 |
August | 514.00000 | 27.08406 | 39.27249 | 0.38980 | 8.34344 |
September | 485.00000 | 27.00013 | 42.84248 | 0.30988 | 7.08539 |
October | 502.00000 | 27.00180 | 38.57039 | 0.95755 | 24.49548 |
November | 489.00000 | 27.00065 | 35.55727 | 0.88872 | 21.83742 |
December | 497.00000 | 27.00018 | 33.53799 | 0.83869 | 20.13356 |
Annual Sum or Average | 5943.00000 | 27.00670 | 37.49369 | 0.64656 | 15.48484 |
Minimum of Months | 454.00000 | 26.98190 | 32.59388 | 0.30988 | 7.08539 |
Maximum of Months | 514.00000 | 27.08406 | 42.84248 | 0.95777 | 24.49548 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00147 | 33.86132 | 1.11351 | 31.16488 |
February | 454.00000 | 27.00198 | 35.11065 | 1.26539 | 38.52176 |
March | 514.00000 | 27.00110 | 34.92304 | 1.39888 | 45.46222 |
April | 485.00000 | 27.28110 | 36.96329 | 1.60259 | 56.42752 |
May | 508.00000 | 27.00415 | 40.24930 | 0.57261 | 11.91178 |
June | 496.00000 | 27.00292 | 39.76167 | 0.78324 | 17.94614 |
July | 497.00000 | 27.00140 | 39.51757 | 0.99621 | 25.97541 |
August | 514.00000 | 28.67645 | 37.90373 | 1.67252 | 59.87193 |
September | 485.00000 | 27.00466 | 40.29943 | 0.63296 | 13.46116 |
October | 502.00000 | 27.00238 | 38.15307 | 1.33036 | 41.85149 |
November | 489.00000 | 27.00083 | 36.20186 | 1.44770 | 48.07347 |
December | 497.00000 | 27.10578 | 34.73743 | 1.57762 | 55.10554 |
Annual Sum or Average | 5943.00000 | 27.17851 | 37.31663 | 1.19986 | 37.17626 |
Minimum of Months | 454.00000 | 27.00083 | 33.86132 | 0.57261 | 11.91178 |
Maximum of Months | 514.00000 | 28.67645 | 40.29943 | 1.67252 | 59.87193 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.54671 | 38.18362 | 0.49384 | 11.02254 |
February | 454.00000 | 24.51620 | 46.34240 | 0.54038 | 11.91955 |
March | 514.00000 | 24.41071 | 45.26981 | 0.51038 | 11.20576 |
April | 485.00000 | 24.49827 | 56.87606 | 0.61121 | 13.56156 |
May | 508.00000 | 24.49899 | 64.73033 | -0.1810 | 6.93540 |
June | 496.00000 | 24.44874 | 64.03564 | -0.1981 | 6.83931 |
July | 497.00000 | 24.61111 | 63.18433 | -0.1452 | 7.05813 |
August | 514.00000 | 24.49222 | 61.29135 | -0.1765 | 6.95829 |
September | 485.00000 | 24.56440 | 62.30023 | -0.1572 | 7.04431 |
October | 502.00000 | 24.61702 | 56.81991 | 0.65920 | 15.24040 |
November | 489.00000 | 24.61877 | 47.67094 | 0.59119 | 13.22669 |
December | 497.00000 | 24.60778 | 42.78921 | 0.54912 | 12.33580 |
Annual Sum or Average | 5943.00000 | 24.53550 | 54.16941 | 0.25502 | 10.25539 |
Minimum of Months | 454.00000 | 24.41071 | 38.18362 | -0.1981 | 6.83931 |
Maximum of Months | 514.00000 | 24.61877 | 64.73033 | 0.65920 | 15.24040 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.30075 | 38.97513 | 0.44179 | 9.58816 |
February | 454.00000 | 24.33140 | 44.76451 | 0.49717 | 10.66179 |
March | 514.00000 | 24.27491 | 43.43484 | 0.48479 | 10.32531 |
April | 485.00000 | 24.24760 | 51.53518 | 0.54803 | 11.50887 |
May | 508.00000 | 24.25985 | 56.47276 | -0.2837 | 7.00206 |
June | 496.00000 | 24.17402 | 56.36455 | -0.3014 | 7.03896 |
July | 497.00000 | 24.21364 | 55.96302 | -0.2828 | 6.83435 |
August | 514.00000 | 24.16945 | 55.63178 | -0.2826 | 6.79611 |
September | 485.00000 | 24.26775 | 56.35077 | -0.2785 | 6.95308 |
October | 502.00000 | 24.31499 | 51.78926 | 0.56618 | 12.02418 |
November | 489.00000 | 24.37220 | 46.12676 | 0.53644 | 11.43997 |
December | 497.00000 | 24.35232 | 42.00858 | 0.49827 | 10.66120 |
Annual Sum or Average | 5943.00000 | 24.27251 | 49.97890 | 0.17537 | 9.21792 |
Minimum of Months | 454.00000 | 24.16945 | 38.97513 | -0.3014 | 6.79611 |
Maximum of Months | 514.00000 | 24.37220 | 56.47276 | 0.56618 | 12.02418 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.92671 | 40.64003 | 0.33273 | 7.81563 |
February | 454.00000 | 24.00102 | 46.40708 | 0.39572 | 8.86018 |
March | 514.00000 | 24.04934 | 45.06183 | 0.40651 | 8.96703 |
April | 485.00000 | 24.25622 | 52.88796 | 0.52201 | 11.02287 |
May | 508.00000 | 24.22646 | 56.87572 | -0.3154 | 7.38111 |
June | 496.00000 | 24.19414 | 56.79335 | -0.3248 | 7.44603 |
July | 497.00000 | 24.19492 | 56.90178 | -0.3262 | 7.48390 |
August | 514.00000 | 24.21115 | 56.81749 | -0.3180 | 7.39956 |
September | 485.00000 | 24.17964 | 57.11658 | -0.3315 | 7.55879 |
October | 502.00000 | 24.24775 | 52.48829 | 0.52801 | 11.14361 |
November | 489.00000 | 24.15968 | 47.51265 | 0.45820 | 9.72926 |
December | 497.00000 | 24.00896 | 44.10363 | 0.38477 | 8.65959 |
Annual Sum or Average | 5943.00000 | 24.13866 | 51.15819 | 0.11468 | 8.61322 |
Minimum of Months | 454.00000 | 23.92671 | 40.64003 | -0.3315 | 7.38111 |
Maximum of Months | 514.00000 | 24.25622 | 57.11658 | 0.52801 | 11.14361 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.07753 | 43.20244 | 0.11965 | 7.19394 |
February | 454.00000 | 23.35964 | 48.47232 | 0.23876 | 8.64696 |
March | 514.00000 | 23.68420 | 46.37174 | 0.31398 | 8.66960 |
April | 485.00000 | 24.17537 | 53.13120 | 0.50535 | 10.70555 |
May | 508.00000 | 24.28138 | 56.46810 | -0.2803 | 7.04573 |
June | 496.00000 | 24.25005 | 56.25120 | -0.2856 | 7.02468 |
July | 497.00000 | 24.28449 | 56.31608 | -0.2775 | 6.95394 |
August | 514.00000 | 24.26390 | 56.41985 | -0.2833 | 7.05485 |
September | 485.00000 | 24.25172 | 56.83629 | -0.2961 | 7.16199 |
October | 502.00000 | 24.21486 | 52.77321 | 0.52672 | 11.36503 |
November | 489.00000 | 23.87115 | 48.80230 | 0.38346 | 8.72564 |
December | 497.00000 | 23.41670 | 46.31229 | 0.23359 | 7.85470 |
Annual Sum or Average | 5943.00000 | 23.93101 | 51.79410 | 0.07265 | 8.19126 |
Minimum of Months | 454.00000 | 23.07753 | 43.20244 | -0.2961 | 6.95394 |
Maximum of Months | 514.00000 | 24.28449 | 56.83629 | 0.52672 | 11.36503 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.31598 | 40.99646 | 0.17746 | 7.31759 |
February | 454.00000 | 23.63181 | 45.24975 | 0.29649 | 8.42785 |
March | 514.00000 | 23.85456 | 43.75975 | 0.35134 | 8.68380 |
April | 485.00000 | 24.17095 | 51.09188 | 0.51573 | 10.86700 |
May | 508.00000 | 24.40181 | 56.07869 | -0.1974 | 6.62369 |
June | 496.00000 | 24.34729 | 55.30359 | -0.1947 | 6.42501 |
July | 497.00000 | 24.45532 | 55.15037 | -0.1561 | 6.50604 |
August | 514.00000 | 24.31481 | 54.98476 | -0.1972 | 6.46764 |
September | 485.00000 | 24.40016 | 56.32911 | -0.2124 | 6.83545 |
October | 502.00000 | 24.32356 | 51.80951 | 0.57120 | 12.48167 |
November | 489.00000 | 24.05014 | 46.38462 | 0.42619 | 9.35928 |
December | 497.00000 | 23.75597 | 43.22927 | 0.31571 | 8.18978 |
Annual Sum or Average | 5943.00000 | 24.08781 | 50.05572 | 0.13927 | 8.17283 |
Minimum of Months | 454.00000 | 23.31598 | 40.99646 | -0.2124 | 6.42501 |
Maximum of Months | 514.00000 | 24.45532 | 56.32911 | 0.57120 | 12.48167 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.56860 | 40.00187 | 0.25553 | 8.11723 |
February | 454.00000 | 23.75243 | 44.69326 | 0.34765 | 9.04020 |
March | 514.00000 | 23.84211 | 43.41294 | 0.37806 | 9.54427 |
April | 485.00000 | 24.14270 | 50.91785 | 0.53840 | 11.58571 |
May | 508.00000 | 24.45561 | 55.56468 | -0.1324 | 6.73283 |
June | 496.00000 | 24.35400 | 55.07623 | -0.1544 | 6.40282 |
July | 497.00000 | 24.44885 | 54.94722 | -0.1257 | 6.62379 |
August | 514.00000 | 24.27838 | 54.99383 | -0.1880 | 6.53060 |
September | 485.00000 | 24.45741 | 55.78466 | -0.1611 | 7.07509 |
October | 502.00000 | 24.35091 | 51.38151 | 0.60189 | 13.50043 |
November | 489.00000 | 24.09060 | 45.99861 | 0.45733 | 10.18780 |
December | 497.00000 | 23.63548 | 43.24553 | 0.30149 | 8.36570 |
Annual Sum or Average | 5943.00000 | 24.11668 | 49.69490 | 0.17433 | 8.63150 |
Minimum of Months | 454.00000 | 23.56860 | 40.00187 | -0.1880 | 6.40282 |
Maximum of Months | 514.00000 | 24.45741 | 55.78466 | 0.60189 | 13.50043 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.01902 | 38.55234 | 0.40084 | 10.38912 |
February | 454.00000 | 24.09881 | 43.52520 | 0.46340 | 11.24708 |
March | 514.00000 | 23.99104 | 42.98641 | 0.41881 | 10.22793 |
April | 485.00000 | 24.25174 | 50.70929 | 0.55536 | 11.90499 |
May | 508.00000 | 24.40681 | 56.03572 | -0.1916 | 6.64007 |
June | 496.00000 | 24.33618 | 55.36845 | -0.2055 | 6.52109 |
July | 497.00000 | 24.45001 | 55.16753 | -0.1601 | 6.56443 |
August | 514.00000 | 24.34251 | 54.78656 | -0.1691 | 6.41336 |
September | 485.00000 | 24.49041 | 55.73352 | -0.1423 | 6.92916 |
October | 502.00000 | 24.51598 | 50.70851 | 0.67655 | 15.69262 |
November | 489.00000 | 24.45813 | 44.71325 | 0.59623 | 13.54148 |
December | 497.00000 | 24.21807 | 41.41676 | 0.49340 | 11.96372 |
Annual Sum or Average | 5943.00000 | 24.29855 | 49.17475 | 0.22511 | 9.81412 |
Minimum of Months | 454.00000 | 23.99104 | 38.55234 | -0.2055 | 6.41336 |
Maximum of Months | 514.00000 | 24.51598 | 56.03572 | 0.67655 | 15.69262 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.91264 | 38.78650 | 0.36886 | 9.42369 |
February | 454.00000 | 24.26583 | 43.02766 | 0.51884 | 12.05090 |
March | 514.00000 | 24.37589 | 41.74364 | 0.56633 | 12.84613 |
April | 485.00000 | 24.56991 | 49.36623 | 0.73474 | 17.22217 |
May | 508.00000 | 24.51687 | 55.18050 | -0.0671 | 6.46412 |
June | 496.00000 | 24.49413 | 54.41449 | -0.0281 | 6.38716 |
July | 497.00000 | 24.63463 | 53.98552 | 0.03592 | 6.83471 |
August | 514.00000 | 24.52915 | 53.68246 | 0.05144 | 6.58094 |
September | 485.00000 | 24.54423 | 55.18542 | -0.0683 | 6.73052 |
October | 502.00000 | 24.58179 | 50.32530 | 0.71896 | 16.87053 |
November | 489.00000 | 24.54309 | 44.37242 | 0.63563 | 14.39234 |
December | 497.00000 | 24.53564 | 40.41717 | 0.59564 | 13.71650 |
Annual Sum or Average | 5943.00000 | 24.45925 | 48.40363 | 0.33638 | 10.76510 |
Minimum of Months | 454.00000 | 23.91264 | 38.78650 | -0.0683 | 6.38716 |
Maximum of Months | 514.00000 | 24.63463 | 55.18542 | 0.73474 | 17.22217 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.26338 | 44.15995 | -0.0800 | 7.76974 |
February | 454.00000 | 22.72474 | 47.94750 | 0.07013 | 8.53143 |
March | 514.00000 | 23.15562 | 46.17857 | 0.17080 | 8.00898 |
April | 485.00000 | 23.99988 | 53.10251 | 0.45389 | 9.99933 |
May | 508.00000 | 24.40066 | 57.48575 | -0.2074 | 6.79071 |
June | 496.00000 | 24.39007 | 56.49383 | -0.1981 | 6.67194 |
July | 497.00000 | 24.48754 | 57.35949 | -0.1639 | 6.79679 |
August | 514.00000 | 24.37284 | 57.55178 | -0.2089 | 6.81239 |
September | 485.00000 | 24.36246 | 58.47213 | -0.2357 | 7.03598 |
October | 502.00000 | 24.18607 | 54.04951 | 0.52987 | 11.95971 |
November | 489.00000 | 23.41723 | 48.85046 | 0.26011 | 7.78337 |
December | 497.00000 | 22.67013 | 47.01680 | 0.04705 | 7.65306 |
Annual Sum or Average | 5943.00000 | 23.70880 | 52.41242 | 0.03524 | 7.97651 |
Minimum of Months | 454.00000 | 22.26338 | 44.15995 | -0.2357 | 6.67194 |
Maximum of Months | 514.00000 | 24.48754 | 58.47213 | 0.52987 | 11.95971 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 22.76311 | 42.45182 | 0.05459 | 7.63674 |
February | 385.00000 | 23.13417 | 46.10579 | 0.18502 | 8.53813 |
March | 433.00000 | 23.46599 | 44.41118 | 0.27018 | 9.23977 |
April | 410.00000 | 24.23394 | 51.85764 | 0.54051 | 12.10244 |
May | 430.00000 | 24.58285 | 56.60341 | -0.1033 | 7.12647 |
June | 418.00000 | 24.52578 | 55.81284 | -0.1154 | 6.77393 |
July | 422.00000 | 24.66248 | 56.50021 | -0.0697 | 7.23043 |
August | 433.00000 | 24.50687 | 56.90351 | -0.1311 | 6.91489 |
September | 410.00000 | 24.53829 | 57.45870 | -0.1472 | 7.51762 |
October | 427.00000 | 24.38127 | 53.22000 | 0.60074 | 14.16586 |
November | 417.00000 | 23.78515 | 47.16576 | 0.36732 | 9.17930 |
December | 422.00000 | 22.97037 | 45.68563 | 0.13112 | 8.11518 |
Annual Sum or Average | 5034.00000 | 23.96664 | 51.20209 | 0.13090 | 8.70790 |
Minimum of Months | 385.00000 | 22.76311 | 42.45182 | -0.1472 | 6.77393 |
Maximum of Months | 433.00000 | 24.66248 | 57.45870 | 0.60074 | 14.16586 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.79181 | 39.69618 | 0.34449 | 10.10038 |
February | 454.00000 | 23.85395 | 44.40423 | 0.39758 | 10.81330 |
March | 514.00000 | 23.69844 | 44.21151 | 0.33657 | 9.66585 |
April | 485.00000 | 24.18943 | 52.20917 | 0.52212 | 11.43790 |
May | 508.00000 | 24.40605 | 57.42988 | -0.2011 | 6.78535 |
June | 496.00000 | 24.37008 | 56.61313 | -0.2125 | 6.73814 |
July | 497.00000 | 24.47664 | 57.40690 | -0.1695 | 6.81739 |
August | 514.00000 | 24.40635 | 57.24085 | -0.1759 | 6.72384 |
September | 485.00000 | 24.47639 | 57.51309 | -0.1537 | 7.10825 |
October | 502.00000 | 24.50055 | 52.15490 | 0.66886 | 15.74279 |
November | 489.00000 | 24.34243 | 45.43569 | 0.55561 | 12.85119 |
December | 497.00000 | 23.95797 | 42.99025 | 0.41971 | 11.41044 |
Annual Sum or Average | 5943.00000 | 24.20706 | 50.64791 | 0.19165 | 9.66418 |
Minimum of Months | 454.00000 | 23.69844 | 39.69618 | -0.2125 | 6.72384 |
Maximum of Months | 514.00000 | 24.50055 | 57.51309 | 0.66886 | 15.74279 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.89419 | 41.96979 | 0.09834 | 7.98574 |
February | 454.00000 | 23.28023 | 45.87295 | 0.23818 | 9.48735 |
March | 514.00000 | 23.54646 | 44.54210 | 0.30189 | 9.35257 |
April | 485.00000 | 24.28762 | 51.68888 | 0.57596 | 12.91090 |
May | 508.00000 | 24.47166 | 56.78720 | -0.1298 | 6.67249 |
June | 496.00000 | 24.46806 | 55.84734 | -0.1150 | 6.64914 |
July | 497.00000 | 24.57102 | 56.50887 | -0.0842 | 6.87621 |
August | 514.00000 | 24.46554 | 56.61751 | -0.1109 | 6.61120 |
September | 485.00000 | 24.46182 | 57.37317 | -0.1465 | 7.00754 |
October | 502.00000 | 24.36982 | 52.76330 | 0.61921 | 14.27318 |
November | 489.00000 | 23.82496 | 47.06934 | 0.39410 | 9.56275 |
December | 497.00000 | 23.24860 | 44.84962 | 0.21703 | 8.67779 |
Annual Sum or Average | 5943.00000 | 23.99494 | 51.02031 | 0.15321 | 8.82402 |
Minimum of Months | 454.00000 | 22.89419 | 41.96979 | -0.1465 | 6.61120 |
Maximum of Months | 514.00000 | 24.57102 | 57.37317 | 0.61921 | 14.27318 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.72349 | 45.90755 | -0.2322 | 9.96799 |
February | 454.00000 | 22.26167 | 49.54705 | -0.0523 | 10.11290 |
March | 514.00000 | 22.77569 | 47.16787 | 0.07295 | 8.94561 |
April | 485.00000 | 23.85007 | 53.49753 | 0.42159 | 9.87485 |
May | 508.00000 | 24.42619 | 57.40154 | -0.1813 | 6.81849 |
June | 496.00000 | 24.41619 | 56.24551 | -0.1685 | 6.68289 |
July | 497.00000 | 24.53388 | 57.14610 | -0.1281 | 6.96600 |
August | 514.00000 | 24.39813 | 57.51547 | -0.1820 | 6.84097 |
September | 485.00000 | 24.38955 | 58.67727 | -0.2124 | 7.19772 |
October | 502.00000 | 24.11306 | 54.63940 | 0.52052 | 12.38664 |
November | 489.00000 | 23.03227 | 50.04808 | 0.16481 | 7.95960 |
December | 497.00000 | 22.18961 | 48.83554 | -0.0828 | 8.96533 |
Annual Sum or Average | 5943.00000 | 23.51735 | 53.06833 | -0.0056 | 8.54727 |
Minimum of Months | 454.00000 | 21.72349 | 45.90755 | -0.2322 | 6.68289 |
Maximum of Months | 514.00000 | 24.53388 | 58.67727 | 0.52052 | 12.38664 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.24239 | 44.19161 | -0.0815 | 8.70090 |
February | 454.00000 | 22.75181 | 47.77018 | 0.09369 | 9.58912 |
March | 514.00000 | 23.23193 | 45.41108 | 0.21545 | 9.83652 |
April | 485.00000 | 24.09389 | 52.10946 | 0.52533 | 11.94185 |
May | 508.00000 | 24.50154 | 56.48833 | -0.0907 | 6.97103 |
June | 496.00000 | 24.45991 | 55.59954 | -0.0925 | 6.62989 |
July | 497.00000 | 24.58744 | 56.26228 | -0.0511 | 7.17754 |
August | 514.00000 | 24.44162 | 56.74092 | -0.1128 | 6.78284 |
September | 485.00000 | 24.46203 | 57.56032 | -0.1387 | 7.48055 |
October | 502.00000 | 24.25097 | 53.44791 | 0.58970 | 14.23291 |
November | 489.00000 | 23.53391 | 48.16560 | 0.30984 | 8.90015 |
December | 497.00000 | 22.58701 | 47.33867 | 0.03078 | 8.76822 |
Annual Sum or Average | 5943.00000 | 23.76838 | 51.77768 | 0.09883 | 8.90718 |
Minimum of Months | 454.00000 | 22.24239 | 44.19161 | -0.1387 | 6.62989 |
Maximum of Months | 514.00000 | 24.58744 | 57.56032 | 0.58970 | 14.23291 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.35785 | 41.26345 | 0.21958 | 9.99579 |
February | 454.00000 | 23.45883 | 45.74942 | 0.29298 | 11.10319 |
March | 514.00000 | 23.38413 | 45.13779 | 0.25454 | 10.10262 |
April | 485.00000 | 24.06455 | 52.55133 | 0.49624 | 11.27923 |
May | 508.00000 | 24.42808 | 57.35867 | -0.1758 | 6.81271 |
June | 496.00000 | 24.39730 | 56.36670 | -0.1828 | 6.73191 |
July | 497.00000 | 24.52054 | 57.20073 | -0.1346 | 6.97653 |
August | 514.00000 | 24.42575 | 57.21021 | -0.1501 | 6.76707 |
September | 485.00000 | 24.48538 | 57.74959 | -0.1340 | 7.29147 |
October | 502.00000 | 24.44400 | 52.66137 | 0.66511 | 16.00929 |
November | 489.00000 | 24.14361 | 46.16584 | 0.50138 | 12.27730 |
December | 497.00000 | 23.57774 | 44.55123 | 0.31577 | 11.23723 |
Annual Sum or Average | 5943.00000 | 24.06014 | 51.19724 | 0.16183 | 9.69694 |
Minimum of Months | 454.00000 | 23.35785 | 41.26345 | -0.1828 | 6.73191 |
Maximum of Months | 514.00000 | 24.52054 | 57.74959 | 0.66511 | 16.00929 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.37851 | 43.56076 | -0.0396 | 8.98026 |
February | 454.00000 | 22.84774 | 47.32127 | 0.12892 | 10.26888 |
March | 514.00000 | 23.18313 | 45.48319 | 0.21212 | 9.72875 |
April | 485.00000 | 24.15028 | 52.01589 | 0.54799 | 12.65398 |
May | 508.00000 | 24.47560 | 56.74992 | -0.1101 | 6.73342 |
June | 496.00000 | 24.47476 | 55.66406 | -0.0913 | 6.71207 |
July | 497.00000 | 24.58687 | 56.36454 | -0.0585 | 7.05571 |
August | 514.00000 | 24.47546 | 56.59178 | -0.0891 | 6.70117 |
September | 485.00000 | 24.45602 | 57.61561 | -0.1325 | 7.19964 |
October | 502.00000 | 24.29247 | 53.29945 | 0.61028 | 14.48982 |
November | 489.00000 | 23.48697 | 48.06857 | 0.31239 | 9.24579 |
December | 497.00000 | 22.78814 | 46.51001 | 0.09860 | 9.13957 |
Annual Sum or Average | 5943.00000 | 23.80546 | 51.62679 | 0.11462 | 9.05907 |
Minimum of Months | 454.00000 | 22.37851 | 43.56076 | -0.1325 | 6.70117 |
Maximum of Months | 514.00000 | 24.58687 | 57.61561 | 0.61028 | 14.48982 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.493740E+11 | 121397.73 | 19-JAN-10:50 | 241.27 | 0.299688E+12 | 0.00 | 0.349062E+12 | 1.78 | 7.54 | 19-JAN-06:03 | 0.00 | 0.00 |
February | 0.659877E+11 | 121685.67 | 24-FEB-13:10 | 303.18 | 0.410166E+12 | 0.00 | 0.476154E+12 | 2.55 | 7.52 | 28-FEB-06:02 | 0.00 | 0.00 |
March | 0.831328E+11 | 151976.61 | 07-MAR-06:04 | 373.95 | 0.527083E+12 | 0.00 | 0.610215E+12 | 2.88 | 7.72 | 27-MAR-05:04 | 0.00 | 0.00 |
April | 0.130919E+12 | 172874.55 | 29-APR-05:02 | 552.73 | 0.844256E+12 | 0.00 | 0.975175E+12 | 4.47 | 7.79 | 14-APR-05:04 | 0.00 | 0.00 |
May | 0.193945E+12 | 220288.16 | 24-MAY-05:03 | 575.33 | 0.126510E+13 | 0.00 | 0.145905E+13 | 4.83 | 7.64 | 17-MAY-05:03 | 0.00 | 0.00 |
June | 0.198666E+12 | 194350.28 | 29-JUN-05:02 | 626.02 | 0.127202E+13 | 0.00 | 0.147069E+13 | 5.24 | 7.69 | 08-JUN-05:02 | 0.00 | 0.00 |
July | 0.209246E+12 | 218476.13 | 31-JUL-05:04 | 678.07 | 0.130879E+13 | 0.00 | 0.151804E+13 | 5.32 | 7.39 | 17-JUL-05:02 | 0.00 | 0.00 |
August | 0.210491E+12 | 201022.27 | 01-AUG-05:04 | 696.96 | 0.133789E+13 | 0.00 | 0.154838E+13 | 5.51 | 7.52 | 17-AUG-05:02 | 0.00 | 0.00 |
September | 0.188506E+12 | 208490.59 | 12-SEP-05:02 | 558.20 | 0.122160E+13 | 0.00 | 0.141011E+13 | 4.83 | 7.72 | 22-SEP-05:02 | 0.00 | 0.00 |
October | 0.167602E+12 | 210125.99 | 25-OCT-05:02 | 567.44 | 0.107501E+13 | 0.00 | 0.124261E+13 | 4.56 | 7.69 | 03-OCT-05:02 | 0.00 | 0.00 |
November | 0.104293E+12 | 181705.25 | 02-NOV-05:02 | 444.21 | 0.659003E+12 | 0.00 | 0.763297E+12 | 3.54 | 7.75 | 08-NOV-06:04 | 0.00 | 0.00 |
December | 0.720656E+11 | 183059.78 | 15-DEC-06:04 | 340.09 | 0.453448E+12 | 0.00 | 0.525514E+12 | 2.56 | 7.78 | 14-DEC-06:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.167423E+13 | 5957.46 | 0.106741E+14 | 0.00 | 0.123483E+14 | 4.01 | 0.00 | 0.00 | ||||
Minimum of Months | 0.493740E+11 | 121397.73 | 241.27 | 0.299688E+12 | 0.00 | 0.349062E+12 | 1.78 | 7.39 | 0.00 | 0.00 | ||
Maximum of Months | 0.210491E+12 | 220288.16 | 696.96 | 0.133789E+13 | 0.00 | 0.154838E+13 | 5.51 | 7.79 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.247809E+10 | 121397.73 | 19-JAN-10:50 | 6.04 | 0.174406E+11 | 0.00 | 0.199187E+11 | 0.06 | 7.54 | 19-JAN-06:03 | 0.00 | 0.00 |
February | 0.535638E+10 | 121685.67 | 24-FEB-13:10 | 13.18 | 0.380766E+11 | 0.00 | 0.434330E+11 | 0.14 | 7.52 | 28-FEB-06:02 | 0.00 | 0.00 |
March | 0.394873E+10 | 151976.61 | 07-MAR-06:04 | 9.57 | 0.275343E+11 | 0.00 | 0.314830E+11 | 0.09 | 7.72 | 27-MAR-05:04 | 0.00 | 0.00 |
April | 0.123459E+11 | 172874.55 | 29-APR-05:02 | 29.39 | 0.855380E+11 | 0.00 | 0.978839E+11 | 0.28 | 7.79 | 14-APR-05:04 | 0.00 | 0.00 |
May | 0.666471E+11 | 220288.16 | 24-MAY-05:03 | 154.28 | 0.452499E+12 | 0.00 | 0.519146E+12 | 1.41 | 7.64 | 17-MAY-05:03 | 0.00 | 0.00 |
June | 0.711357E+11 | 194350.28 | 29-JUN-05:02 | 162.78 | 0.476925E+12 | 0.00 | 0.548061E+12 | 1.52 | 7.69 | 08-JUN-05:02 | 0.00 | 0.00 |
July | 0.734434E+11 | 218476.13 | 31-JUL-05:04 | 166.19 | 0.486224E+12 | 0.00 | 0.559667E+12 | 1.48 | 7.39 | 17-JUL-05:02 | 0.00 | 0.00 |
August | 0.828367E+11 | 201022.27 | 01-AUG-05:04 | 188.64 | 0.551777E+12 | 0.00 | 0.634614E+12 | 1.69 | 7.52 | 17-AUG-05:02 | 0.00 | 0.00 |
September | 0.597492E+11 | 208490.59 | 12-SEP-05:02 | 138.10 | 0.403211E+12 | 0.00 | 0.462960E+12 | 1.29 | 7.72 | 22-SEP-05:02 | 0.00 | 0.00 |
October | 0.523297E+11 | 210125.99 | 25-OCT-05:02 | 119.89 | 0.354909E+12 | 0.00 | 0.407238E+12 | 1.09 | 7.69 | 03-OCT-05:02 | 0.00 | 0.00 |
November | 0.162195E+11 | 181705.25 | 02-NOV-05:02 | 37.41 | 0.111134E+12 | 0.00 | 0.127354E+12 | 0.36 | 7.75 | 08-NOV-06:04 | 0.00 | 0.00 |
December | 0.857686E+10 | 183059.78 | 15-DEC-06:04 | 20.23 | 0.592970E+11 | 0.00 | 0.678738E+11 | 0.19 | 7.78 | 14-DEC-06:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.455067E+12 | 1045.70 | 0.306457E+13 | 0.00 | 0.351963E+13 | 0.80 | 0.00 | 0.00 | ||||
Minimum of Months | 0.247809E+10 | 121397.73 | 6.04 | 0.174406E+11 | 0.00 | 0.199187E+11 | 0.06 | 7.39 | 0.00 | 0.00 | ||
Maximum of Months | 0.828367E+11 | 220288.16 | 188.64 | 0.551777E+12 | 0.00 | 0.634614E+12 | 1.69 | 7.79 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: CENTRAL TOWER
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.672863E+11 | 744.00 | 49248.27 | 01-JAN-00:05 | 227032.29 | 31-JAN-16:20 | 23.28 | 19.57 | 14.18 |
February | 0.920280E+11 | 672.00 | 49248.27 | 01-FEB-00:10 | 380509.02 | 24-FEB-14:20 | 27.42 | 20.76 | 14.18 |
March | 0.116885E+12 | 744.00 | 49248.27 | 01-MAR-00:10 | 624442.19 | 31-MAR-24:00 | 32.12 | 22.53 | 14.18 |
April | 0.127346E+12 | 720.00 | 49248.27 | 01-APR-00:10 | 706303.92 | 28-APR-17:20 | 39.64 | 26.90 | 14.18 |
May | 0.131907E+12 | 744.00 | 49248.27 | 01-MAY-00:05 | 343014.06 | 31-MAY-23:40 | 33.12 | 28.80 | 14.18 |
June | 0.127652E+12 | 720.00 | 49248.27 | 01-JUN-00:10 | 495852.93 | 30-JUN-23:43 | 38.28 | 30.88 | 14.18 |
July | 0.131907E+12 | 744.00 | 49248.27 | 01-JUL-00:03 | 648110.58 | 31-JUL-23:53 | 43.05 | 32.59 | 14.18 |
August | 0.131907E+12 | 744.00 | 49248.27 | 01-AUG-00:03 | 712405.50 | 06-AUG-15:31 | 46.69 | 33.39 | 14.18 |
September | 0.127652E+12 | 720.00 | 49248.27 | 01-SEP-00:05 | 342735.80 | 30-SEP-23:50 | 32.49 | 28.14 | 14.18 |
October | 0.129909E+12 | 744.00 | 49248.27 | 01-OCT-00:10 | 483716.75 | 31-OCT-24:00 | 34.73 | 27.51 | 14.18 |
November | 0.120732E+12 | 720.00 | 49248.27 | 01-NOV-00:10 | 552738.27 | 01-NOV-14:20 | 33.51 | 23.75 | 14.18 |
December | 0.117204E+12 | 744.00 | 49248.27 | 01-DEC-00:10 | 687667.28 | 13-DEC-17:10 | 34.99 | 22.62 | 14.18 |
Annual Sum or Average | 0.142241E+13 | 8760.00 | 34.99 | 26.49 | 14.18 | ||||
Minimum of Months | 0.672863E+11 | 672.00 | 49248.27 | 227032.29 | 23.28 | 19.57 | 14.18 | ||
Maximum of Months | 0.131907E+12 | 744.00 | 49248.27 | 712405.50 | 46.69 | 33.39 | 14.18 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.499659E+10 | 176.28 | 22319.10 | 02-JAN-10:40 | 1202221.34 | 02-JAN-13:30 | 21.61 | 21.16 | 21.49 |
February | 0.647430E+10 | 242.24 | 22319.10 | 01-FEB-13:00 | 1164302.07 | 27-FEB-09:50 | 22.00 | 21.33 | 31.36 |
March | 0.915374E+10 | 293.26 | 22319.10 | 06-MAR-06:04 | 1329907.79 | 24-MAR-16:00 | 22.08 | 21.30 | 34.52 |
April | 0.203082E+11 | 472.38 | 22319.10 | 01-APR-04:03 | 1421570.61 | 18-APR-14:15 | 22.94 | 21.66 | 55.14 |
May | 0.455160E+11 | 575.33 | 22319.10 | 01-MAY-01:07 | 1361955.28 | 22-MAY-05:05 | 26.01 | 24.24 | 57.75 |
June | 0.488779E+11 | 625.91 | 22319.10 | 01-JUN-03:02 | 1289408.92 | 08-JUN-05:04 | 26.35 | 24.49 | 63.05 |
July | 0.544825E+11 | 678.07 | 22319.10 | 01-JUL-00:03 | 1428077.42 | 31-JUL-05:04 | 27.32 | 25.48 | 63.97 |
August | 0.549568E+11 | 695.12 | 22319.10 | 01-AUG-00:10 | 1167900.29 | 29-AUG-05:03 | 26.71 | 24.83 | 67.51 |
September | 0.444077E+11 | 558.20 | 22319.10 | 01-SEP-00:05 | 1324031.10 | 05-SEP-05:04 | 26.57 | 24.80 | 56.06 |
October | 0.343425E+11 | 539.79 | 22319.10 | 02-OCT-09:20 | 1353980.04 | 11-OCT-05:04 | 24.92 | 23.38 | 54.51 |
November | 0.131339E+11 | 360.72 | 22319.10 | 01-NOV-00:53 | 1220823.05 | 08-NOV-06:04 | 22.68 | 21.69 | 43.09 |
December | 0.995309E+10 | 261.54 | 22319.10 | 08-DEC-11:10 | 1183432.82 | 08-DEC-12:00 | 22.01 | 21.35 | 31.24 |
Annual Sum or Average | 0.346603E+12 | 5478.85 | 24.28 | 22.99 | 48.38 | ||||
Minimum of Months | 0.499659E+10 | 176.28 | 22319.10 | 1164302.07 | 21.61 | 21.16 | 21.49 | ||
Maximum of Months | 0.549568E+11 | 695.12 | 22319.10 | 1428077.42 | 27.32 | 25.48 | 67.51 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.495484E+09 | 6.17 | 22319.10 | 18-JAN-15:00 | 1033424.11 | 19-JAN-10:50 | 21.61 | 21.58 | 0.63 |
February | 0.101775E+10 | 12.67 | 22319.10 | 02-FEB-13:20 | 1020541.85 | 28-FEB-13:20 | 22.00 | 21.94 | 1.43 |
March | 0.771348E+09 | 9.60 | 22319.10 | 06-MAR-06:04 | 1229808.57 | 27-MAR-05:04 | 22.08 | 22.04 | 0.98 |
April | 0.288918E+10 | 36.04 | 22319.10 | 07-APR-05:04 | 1421570.61 | 18-APR-14:15 | 22.94 | 22.80 | 3.76 |
May | 0.165328E+11 | 205.76 | 22319.10 | 01-MAY-03:02 | 1361955.28 | 22-MAY-05:05 | 26.01 | 25.21 | 19.94 |
June | 0.197411E+11 | 245.69 | 22319.10 | 01-JUN-03:02 | 1289408.92 | 08-JUN-05:04 | 26.35 | 25.37 | 22.84 |
July | 0.243405E+11 | 302.94 | 22319.10 | 01-JUL-03:02 | 1428077.42 | 31-JUL-05:04 | 27.32 | 26.20 | 25.61 |
August | 0.236502E+11 | 294.34 | 22319.10 | 01-AUG-05:02 | 1167900.29 | 29-AUG-05:03 | 26.71 | 25.60 | 26.34 |
September | 0.177636E+11 | 221.08 | 22319.10 | 01-SEP-03:02 | 1324031.10 | 05-SEP-05:04 | 26.57 | 25.73 | 20.42 |
October | 0.150020E+11 | 186.71 | 22319.10 | 02-OCT-09:50 | 1353980.04 | 11-OCT-05:04 | 24.92 | 24.21 | 16.40 |
November | 0.356592E+10 | 44.38 | 22319.10 | 01-NOV-04:03 | 1220823.05 | 08-NOV-06:04 | 22.68 | 22.49 | 4.50 |
December | 0.170473E+10 | 21.22 | 22319.10 | 11-DEC-10:20 | 1156703.20 | 15-DEC-06:04 | 22.01 | 21.92 | 2.17 |
Annual Sum or Average | 0.127475E+12 | 1586.59 | 24.28 | 23.77 | 12.16 | ||||
Minimum of Months | 0.495484E+09 | 6.17 | 22319.10 | 1020541.85 | 21.61 | 21.58 | 0.63 | ||
Maximum of Months | 0.243405E+11 | 302.94 | 22319.10 | 1428077.42 | 27.32 | 26.20 | 26.34 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.121505E+11 | 0.00 | 173.51 | 835681.10 | 10-JAN-06:02 | 0.00 | 32.58 | 44.23 | 0.02 | 0.00 | 0.00 | 0.53 | 10-JAN-06:02 |
February | 0.649651E+10 | 0.00 | 90.70 | 846264.83 | 06-FEB-06:01 | 0.00 | 26.00 | 32.77 | 0.01 | 0.00 | 0.00 | 0.54 | 06-FEB-06:01 |
March | 0.562852E+10 | 0.00 | 65.11 | 580033.84 | 11-MAR-06:03 | 0.00 | 29.81 | 34.41 | 0.01 | 0.00 | 0.00 | 0.37 | 11-MAR-06:03 |
April | 0.223118E+09 | 0.00 | 9.42 | 45413.30 | 18-APR-14:30 | 0.00 | 49.38 | 49.80 | 0.00 | 0.00 | 0.00 | 0.03 | 18-APR-14:30 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 58.89 | 58.89 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 58.89 | 58.89 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 58.89 | 58.89 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 58.89 | 58.89 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 58.89 | 58.89 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 7548505.89 | 0.00 | 4.33 | 1092.29 | 28-OCT-06:40 | 0.00 | 58.44 | 58.57 | 0.00 | 0.00 | 0.00 | 0.00 | 28-OCT-06:40 |
November | 0.189057E+09 | 0.00 | 21.94 | 44092.98 | 27-NOV-14:20 | 0.00 | 45.66 | 46.78 | 0.00 | 0.00 | 0.00 | 0.03 | 27-NOV-14:20 |
December | 0.823094E+10 | 0.00 | 123.16 | 852257.95 | 21-DEC-06:01 | 0.00 | 27.01 | 35.71 | 0.01 | 0.00 | 0.00 | 0.54 | 21-DEC-06:01 |
Annual Sum or Average | 0.329262E+11 | 0.00 | 488.17 | 0.00 | 47.05 | 49.82 | 0.01 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.00 | 32.77 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.121505E+11 | 0.00 | 173.51 | 852257.95 | 0.00 | 58.89 | 58.89 | 0.02 | 0.00 | 0.00 | 0.54 |
Report: BoilerReportMonthly
For: CENTRAL BOILER
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 23.28 | 23.28 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 27.42 | 27.42 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 32.12 | 32.12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 39.64 | 39.64 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 33.12 | 33.12 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 38.28 | 38.28 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 43.05 | 43.05 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 46.69 | 46.69 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 32.49 | 32.49 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 34.73 | 34.73 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 33.51 | 33.51 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 34.99 | 34.99 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 34.99 | 34.99 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.28 | 23.28 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.69 | 46.69 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.342391E+11 | 0.00 | 218.17 | 0.265937E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 168799.79 | 19-JAN-06:03 | 116493.73 | 19-JAN-06:03 | 0.00 | 0.00 | 0.00 |
February | 0.488738E+11 | 0.00 | 283.99 | 0.366752E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 180386.99 | 28-FEB-06:02 | 98737.65 | 27-FEB-16:20 | 0.00 | 0.00 | 0.00 |
March | 0.651581E+11 | 0.00 | 359.62 | 0.542407E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 208959.66 | 07-MAR-06:02 | 150596.70 | 06-MAR-06:02 | 0.00 | 0.00 | 0.00 |
April | 0.109851E+12 | 0.00 | 537.65 | 0.928891E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 206446.93 | 29-APR-05:02 | 147285.91 | 18-APR-13:55 | 0.00 | 0.00 | 0.00 |
May | 0.150401E+12 | 0.00 | 540.49 | 0.122674E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 232449.88 | 24-MAY-03:02 | 154576.84 | 30-MAY-05:02 | 0.00 | 0.00 | 0.00 |
June | 0.162738E+12 | 0.00 | 588.26 | 0.134790E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 220574.81 | 28-JUN-05:02 | 153773.02 | 28-JUN-05:02 | 0.00 | 0.00 | 0.00 |
July | 0.176160E+12 | 0.00 | 632.74 | 0.143564E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 223397.89 | 03-JUL-05:02 | 159961.74 | 24-JUL-05:04 | 0.00 | 0.00 | 0.00 |
August | 0.193773E+12 | 0.00 | 657.63 | 0.159654E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 224764.42 | 21-AUG-05:03 | 158800.86 | 21-AUG-05:03 | 0.00 | 0.00 | 0.00 |
September | 0.149166E+12 | 0.00 | 524.48 | 0.115876E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 229700.99 | 05-SEP-03:02 | 153305.26 | 11-SEP-05:03 | 0.00 | 0.00 | 0.00 |
October | 0.137372E+12 | 0.00 | 535.84 | 0.113254E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 221490.55 | 06-OCT-05:02 | 154122.79 | 10-OCT-05:03 | 0.00 | 0.00 | 0.00 |
November | 0.805258E+11 | 0.00 | 423.09 | 0.678669E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 208890.27 | 02-NOV-05:02 | 146522.41 | 02-NOV-05:02 | 0.00 | 0.00 | 0.00 |
December | 0.590780E+11 | 0.00 | 317.73 | 0.483666E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 208236.56 | 16-DEC-06:02 | 144691.07 | 12-DEC-06:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.136734E+13 | 0.00 | 5619.68 | 0.111644E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.342391E+11 | 0.00 | 218.17 | 0.265937E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 168799.79 | 98737.65 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.193773E+12 | 0.00 | 657.63 | 0.159654E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 232449.88 | 159961.74 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.267454E+12 | 0.00 | 207.32 | 0.202814E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1454570.34 | 19-JAN-06:03 | 902346.59 | 02-JAN-15:10 | 0.00 | 0.00 | 0.00 |
February | 0.378432E+12 | 0.00 | 265.66 | 0.278911E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1515309.23 | 28-FEB-06:02 | 826335.64 | 27-FEB-16:20 | 0.00 | 0.00 | 0.00 |
March | 0.479486E+12 | 0.00 | 315.29 | 0.384419E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2053829.77 | 07-MAR-06:02 | 1309335.07 | 07-MAR-06:02 | 0.00 | 0.00 | 0.00 |
April | 0.794848E+12 | 0.00 | 409.30 | 0.645535E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2047377.13 | 26-APR-05:03 | 1353741.78 | 24-APR-05:03 | 0.00 | 0.00 | 0.00 |
May | 0.135751E+13 | 0.00 | 494.89 | 0.106824E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2591312.84 | 22-MAY-03:02 | 1410317.62 | 01-MAY-05:02 | 0.00 | 0.00 | 0.00 |
June | 0.139215E+13 | 0.00 | 504.49 | 0.110351E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2177070.60 | 19-JUN-03:02 | 1431312.10 | 28-JUN-05:02 | 0.00 | 0.00 | 0.00 |
July | 0.143176E+13 | 0.00 | 520.44 | 0.108864E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2254851.86 | 26-JUL-05:03 | 1434920.18 | 05-JUL-05:02 | 0.00 | 0.00 | 0.00 |
August | 0.148707E+13 | 0.00 | 515.82 | 0.113376E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2404068.81 | 15-AUG-03:02 | 1416564.29 | 21-AUG-05:02 | 0.00 | 0.00 | 0.00 |
September | 0.131486E+13 | 0.00 | 481.53 | 0.967551E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2751506.84 | 05-SEP-03:02 | 1423298.66 | 01-SEP-05:03 | 0.00 | 0.00 | 0.00 |
October | 0.113814E+13 | 0.00 | 458.70 | 0.887973E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2282805.22 | 07-OCT-03:02 | 1419532.00 | 10-OCT-03:02 | 0.00 | 0.00 | 0.00 |
November | 0.606307E+12 | 0.00 | 373.33 | 0.491463E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2124444.42 | 01-NOV-05:03 | 1357596.17 | 04-NOV-05:03 | 0.00 | 0.00 | 0.00 |
December | 0.412523E+12 | 0.00 | 258.12 | 0.317558E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2076060.99 | 15-DEC-06:02 | 1325051.51 | 15-DEC-06:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.110606E+14 | 0.00 | 4804.89 | 0.857037E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.267454E+12 | 0.00 | 207.32 | 0.202814E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1454570.34 | 826335.64 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.148707E+13 | 0.00 | 520.44 | 0.113376E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2751506.84 | 1434920.18 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.257704E+11 | 0.00 | 202.19 | 0.192649E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 143803.00 | 19-JAN-06:03 | 89372.11 | 19-JAN-15:50 | 0.00 | 0.00 | 0.00 |
February | 0.378887E+11 | 0.00 | 260.53 | 0.281386E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 139287.12 | 28-FEB-06:02 | 96002.11 | 27-FEB-15:50 | 0.00 | 0.00 | 0.00 |
March | 0.493188E+11 | 0.00 | 307.61 | 0.395297E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 195943.60 | 27-MAR-05:02 | 125380.04 | 30-MAR-05:03 | 0.00 | 0.00 | 0.00 |
April | 0.847841E+11 | 0.00 | 404.28 | 0.696855E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 220697.29 | 29-APR-05:02 | 140539.13 | 29-APR-05:02 | 0.00 | 0.00 | 0.00 |
May | 0.150982E+12 | 0.00 | 504.10 | 0.120857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 265803.82 | 22-MAY-03:02 | 153948.02 | 22-MAY-03:02 | 0.00 | 0.00 | 0.00 |
June | 0.157677E+12 | 0.00 | 514.80 | 0.127809E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 243274.61 | 30-JUN-03:02 | 155107.09 | 21-JUN-03:02 | 0.00 | 0.00 | 0.00 |
July | 0.162030E+12 | 0.00 | 534.63 | 0.126017E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 251496.59 | 26-JUL-03:02 | 153917.38 | 26-JUL-03:02 | 0.00 | 0.00 | 0.00 |
August | 0.165969E+12 | 0.00 | 529.55 | 0.129198E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 259936.57 | 11-AUG-03:02 | 153441.95 | 23-AUG-03:02 | 0.00 | 0.00 | 0.00 |
September | 0.142064E+12 | 0.00 | 485.39 | 0.106046E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 296074.12 | 05-SEP-03:02 | 152072.83 | 07-SEP-03:02 | 0.00 | 0.00 | 0.00 |
October | 0.122309E+12 | 0.00 | 459.64 | 0.966161E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 256083.09 | 25-OCT-03:02 | 153030.58 | 25-OCT-03:02 | 0.00 | 0.00 | 0.00 |
November | 0.594080E+11 | 0.00 | 364.91 | 0.482725E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 218228.23 | 02-NOV-05:02 | 140363.44 | 02-NOV-05:02 | 0.00 | 0.00 | 0.00 |
December | 0.397464E+11 | 0.00 | 251.64 | 0.302889E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 183256.79 | 15-DEC-06:02 | 113090.48 | 15-DEC-06:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.119795E+13 | 0.00 | 4819.27 | 0.941723E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.257704E+11 | 0.00 | 202.19 | 0.192649E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 139287.12 | 89372.11 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.165969E+12 | 0.00 | 534.63 | 0.129198E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 296074.12 | 155107.09 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.218968E+11 | 0.00 | 150.82 | 0.169084E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 119639.89 | 01-JAN-16:12 | 98091.48 | 01-JAN-16:12 | 0.00 | 0.00 | 0.00 |
February | 0.263542E+11 | 0.00 | 199.37 | 0.215636E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 109905.30 | 03-FEB-06:03 | 97462.06 | 21-FEB-04:02 | 0.00 | 0.00 | 0.00 |
March | 0.354979E+11 | 0.00 | 239.76 | 0.300986E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 139139.19 | 07-MAR-04:03 | 93382.55 | 06-MAR-05:23 | 0.00 | 0.00 | 0.00 |
April | 0.562278E+11 | 0.00 | 350.29 | 0.488070E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 141680.75 | 29-APR-04:03 | 87614.99 | 24-APR-03:04 | 0.00 | 0.00 | 0.00 |
May | 0.103677E+12 | 0.00 | 438.17 | 0.800205E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 173131.55 | 22-MAY-03:02 | 91011.86 | 30-MAY-03:02 | 0.00 | 0.00 | 0.00 |
June | 0.108815E+12 | 0.00 | 429.98 | 0.815867E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 172825.55 | 19-JUN-03:02 | 91753.22 | 12-JUN-03:02 | 0.00 | 0.00 | 0.00 |
July | 0.117942E+12 | 0.00 | 429.38 | 0.834478E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 160889.34 | 17-JUL-03:02 | 90979.62 | 18-JUL-03:02 | 0.00 | 0.00 | 0.00 |
August | 0.130714E+12 | 0.00 | 476.88 | 0.949890E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 169304.83 | 06-AUG-14:12 | 93931.14 | 21-AUG-00:53 | 0.00 | 0.00 | 0.00 |
September | 0.110906E+12 | 0.00 | 445.55 | 0.810925E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 169974.94 | 17-SEP-14:20 | 94109.91 | 05-SEP-03:02 | 0.00 | 0.00 | 0.00 |
October | 0.953928E+11 | 0.00 | 419.04 | 0.734004E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 168365.14 | 08-OCT-14:58 | 95306.42 | 01-OCT-15:22 | 0.00 | 0.00 | 0.00 |
November | 0.523303E+11 | 0.00 | 308.20 | 0.433700E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 143605.32 | 03-NOV-03:02 | 94017.72 | 05-NOV-15:30 | 0.00 | 0.00 | 0.00 |
December | 0.342941E+11 | 0.00 | 208.44 | 0.277316E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 137277.76 | 10-DEC-15:20 | 95889.66 | 10-DEC-15:20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.894049E+12 | 0.00 | 4095.88 | 0.683016E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.218968E+11 | 0.00 | 150.82 | 0.169084E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 109905.30 | 87614.99 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.130714E+12 | 0.00 | 476.88 | 0.949890E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 173131.55 | 98091.48 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.331718E+12 | 0.857884E+11 | 744.00 | 0.329000E+12 | 0.271843E+10 | 0.00 | 0.37 | 19-JAN-12:00 | 0.31 | 21-JAN-07:10 | 136409.24 | 31-JAN-16:40 | 128368.54 | 02-JAN-15:00 | 9993.42 | 31-JAN-17:00 | 44156.01 | 02-JAN-15:00 | 0.00 |
February | 0.522753E+12 | 0.132873E+12 | 672.00 | 0.517891E+12 | 0.486193E+10 | 0.00 | 0.60 | 24-FEB-13:50 | 0.52 | 13-FEB-07:20 | 227508.79 | 24-FEB-16:50 | 218743.41 | 24-FEB-13:10 | 9718.32 | 24-FEB-17:10 | 76378.79 | 02-FEB-13:10 | 0.00 |
March | 0.823430E+12 | 0.212843E+12 | 744.00 | 0.818567E+12 | 0.486294E+10 | 0.00 | 0.95 | 31-MAR-24:00 | 0.72 | 15-MAR-07:00 | 393952.00 | 31-MAR-24:00 | 393952.00 | 31-MAR-24:00 | 11308.23 | 07-MAR-15:00 | 111275.29 | 30-MAR-13:00 | 0.00 |
April | 0.103628E+13 | 0.290624E+12 | 720.00 | 0.103012E+13 | 0.616229E+10 | 0.00 | 1.00 | 03-APR-13:30 | 0.37 | 30-APR-23:55 | 422269.30 | 28-APR-18:00 | 404198.58 | 18-APR-16:50 | 18479.12 | 28-APR-18:00 | 147537.14 | 28-APR-15:00 | 0.00 |
May | 0.349000E+12 | 0.116550E+12 | 744.00 | 0.336384E+12 | 0.126161E+11 | 0.00 | 0.56 | 31-MAY-23:20 | 0.34 | 07-MAY-01:00 | 212762.30 | 31-MAY-23:10 | 211053.36 | 31-MAY-24:00 | 14568.64 | 23-MAY-16:00 | 63138.09 | 31-MAY-23:20 | 0.00 |
June | 0.576229E+12 | 0.193659E+12 | 720.00 | 0.562358E+12 | 0.138713E+11 | 0.00 | 0.78 | 30-JUN-23:35 | 0.55 | 01-JUN-05:00 | 302726.56 | 30-JUN-23:03 | 302698.94 | 30-JUN-23:57 | 17736.67 | 29-JUN-15:00 | 94851.73 | 30-JUN-23:20 | 0.00 |
July | 0.842408E+12 | 0.284092E+12 | 744.00 | 0.827501E+12 | 0.149065E+11 | 0.00 | 0.99 | 31-JUL-23:23 | 0.78 | 01-JUL-01:30 | 395008.21 | 31-JUL-23:53 | 395008.21 | 31-JUL-23:53 | 16618.81 | 12-JUL-12:50 | 134005.95 | 21-JUL-16:00 | 0.00 |
August | 0.108075E+13 | 0.352864E+12 | 744.00 | 0.106732E+13 | 0.134305E+11 | 0.00 | 1.00 | 01-AUG-06:40 | 0.39 | 31-AUG-24:00 | 424437.60 | 07-AUG-14:00 | 410412.81 | 06-AUG-15:55 | 20710.88 | 07-AUG-14:00 | 155030.22 | 30-AUG-16:00 | 0.00 |
September | 0.342098E+12 | 0.111896E+12 | 720.00 | 0.328554E+12 | 0.135440E+11 | 0.00 | 0.55 | 30-SEP-23:20 | 0.34 | 22-SEP-06:10 | 213274.21 | 30-SEP-24:00 | 212005.73 | 30-SEP-24:00 | 14066.39 | 18-SEP-10:40 | 62453.15 | 30-SEP-23:20 | 0.00 |
October | 0.593623E+12 | 0.183038E+12 | 744.00 | 0.582774E+12 | 0.108490E+11 | 0.00 | 0.76 | 31-OCT-24:00 | 0.53 | 17-OCT-07:00 | 304073.58 | 31-OCT-24:00 | 304073.58 | 31-OCT-24:00 | 15961.13 | 24-OCT-09:00 | 91339.71 | 05-OCT-15:00 | 0.00 |
November | 0.804250E+12 | 0.214475E+12 | 720.00 | 0.798245E+12 | 0.600517E+10 | 0.00 | 0.84 | 02-NOV-13:10 | 0.72 | 15-NOV-07:10 | 324540.11 | 03-NOV-16:00 | 312644.47 | 03-NOV-14:00 | 12829.72 | 03-NOV-16:10 | 114382.62 | 02-NOV-13:00 | 0.00 |
December | 0.107079E+13 | 0.267171E+12 | 744.00 | 0.106704E+13 | 0.374641E+10 | 0.00 | 1.00 | 07-DEC-13:20 | 0.91 | 18-DEC-07:20 | 416142.25 | 13-DEC-18:00 | 403726.83 | 13-DEC-18:00 | 13034.76 | 11-DEC-15:10 | 138753.65 | 13-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.837333E+13 | 0.244587E+13 | 8760.00 | 0.826575E+13 | 0.107575E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.331718E+12 | 0.857884E+11 | 672.00 | 0.328554E+12 | 0.271843E+10 | 0.00 | 0.37 | 0.31 | 136409.24 | 128368.54 | 9718.32 | 44156.01 | 0.00 | ||||||
Maximum of Months | 0.108075E+13 | 0.352864E+12 | 744.00 | 0.106732E+13 | 0.149065E+11 | 0.00 | 1.00 | 0.91 | 424437.60 | 410412.81 | 20710.88 | 155030.22 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.522595E+10 | 0.135569E+10 | 744.00 | 0.511722E+10 | 0.108729E+09 | 0.00 | 0.34 | 19-JAN-17:00 | 0.15 | 05-JAN-08:00 | 2815.04 | 19-JAN-17:00 | 2573.79 | 01-JAN-17:30 | 400.79 | 31-JAN-17:00 | 829.76 | 02-JAN-15:00 | 0.00 |
February | 0.963334E+10 | 0.242875E+10 | 672.00 | 0.944020E+10 | 0.193142E+09 | 0.00 | 0.57 | 27-FEB-17:00 | 0.39 | 17-FEB-07:10 | 4743.07 | 27-FEB-17:00 | 4636.94 | 26-FEB-17:47 | 398.40 | 24-FEB-17:00 | 1475.09 | 02-FEB-13:10 | 0.00 |
March | 0.158168E+11 | 0.403685E+10 | 744.00 | 0.156121E+11 | 0.204692E+09 | 0.00 | 0.87 | 31-MAR-24:00 | 0.60 | 11-MAR-18:00 | 7719.06 | 31-MAR-24:00 | 7719.06 | 31-MAR-24:00 | 481.49 | 07-MAR-15:00 | 2204.21 | 30-MAR-13:00 | 0.00 |
April | 0.205463E+11 | 0.567964E+10 | 720.00 | 0.202581E+11 | 0.288232E+09 | 0.00 | 1.00 | 21-APR-16:00 | 0.31 | 30-APR-23:55 | 8661.28 | 28-APR-17:20 | 8427.98 | 16-APR-18:06 | 556.82 | 28-APR-17:30 | 3096.05 | 28-APR-15:00 | 0.00 |
May | 0.656738E+10 | 0.213719E+10 | 744.00 | 0.606268E+10 | 0.504705E+09 | 0.00 | 0.50 | 31-MAY-23:20 | 0.26 | 13-MAY-06:10 | 4098.04 | 31-MAY-23:10 | 4013.58 | 31-MAY-24:00 | 555.62 | 23-MAY-16:00 | 1187.25 | 31-MAY-23:20 | 0.00 |
June | 0.113496E+11 | 0.371859E+10 | 720.00 | 0.107689E+11 | 0.580682E+09 | 0.00 | 0.70 | 30-JUN-23:43 | 0.48 | 01-JUN-06:00 | 5880.12 | 30-JUN-23:43 | 5866.74 | 30-JUN-23:57 | 686.13 | 29-JUN-15:00 | 1869.01 | 29-JUN-14:00 | 0.00 |
July | 0.168360E+11 | 0.554200E+10 | 744.00 | 0.161843E+11 | 0.651725E+09 | 0.00 | 0.90 | 31-JUL-23:45 | 0.70 | 11-JUL-21:20 | 7743.94 | 31-JUL-23:57 | 7743.94 | 31-JUL-23:57 | 666.48 | 12-JUL-10:00 | 2734.19 | 21-JUL-16:00 | 0.00 |
August | 0.219447E+11 | 0.711090E+10 | 744.00 | 0.212887E+11 | 0.655960E+09 | 0.00 | 1.00 | 01-AUG-09:40 | 0.33 | 31-AUG-24:00 | 8920.93 | 07-AUG-13:50 | 8310.67 | 06-AUG-17:55 | 741.27 | 07-AUG-13:40 | 3253.07 | 30-AUG-16:00 | 0.00 |
September | 0.639852E+10 | 0.203724E+10 | 720.00 | 0.585585E+10 | 0.542676E+09 | 0.00 | 0.49 | 30-SEP-24:00 | 0.26 | 28-SEP-06:10 | 4072.46 | 30-SEP-24:00 | 4041.72 | 30-SEP-24:00 | 585.39 | 18-SEP-14:30 | 1169.12 | 30-SEP-23:20 | 0.00 |
October | 0.115026E+11 | 0.347400E+10 | 744.00 | 0.110511E+11 | 0.451561E+09 | 0.00 | 0.69 | 31-OCT-24:00 | 0.43 | 28-OCT-07:00 | 5896.72 | 31-OCT-24:00 | 5888.35 | 31-OCT-24:00 | 685.51 | 24-OCT-14:10 | 1840.31 | 05-OCT-15:00 | 0.00 |
November | 0.155902E+11 | 0.409321E+10 | 720.00 | 0.153395E+11 | 0.250694E+09 | 0.00 | 0.80 | 02-NOV-16:00 | 0.62 | 15-NOV-07:10 | 6812.59 | 07-NOV-16:40 | 6469.19 | 06-NOV-17:00 | 560.94 | 01-NOV-11:00 | 2285.07 | 01-NOV-14:00 | 0.00 |
December | 0.208571E+11 | 0.514964E+10 | 744.00 | 0.206805E+11 | 0.176594E+09 | 0.00 | 1.00 | 15-DEC-16:40 | 0.78 | 20-DEC-07:20 | 8752.63 | 14-DEC-17:00 | 8352.59 | 10-DEC-16:54 | 565.24 | 12-DEC-15:00 | 2895.89 | 13-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.162269E+12 | 0.467637E+11 | 8760.00 | 0.157659E+12 | 0.460939E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.522595E+10 | 0.135569E+10 | 672.00 | 0.511722E+10 | 0.108729E+09 | 0.00 | 0.34 | 0.15 | 2815.04 | 2573.79 | 398.40 | 829.76 | 0.00 | ||||||
Maximum of Months | 0.219447E+11 | 0.711090E+10 | 744.00 | 0.212887E+11 | 0.655960E+09 | 0.00 | 1.00 | 0.78 | 8920.93 | 8427.98 | 741.27 | 3253.07 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.402077E+11 | 0.106336E+11 | 744.00 | 0.391491E+11 | 0.105860E+10 | 0.00 | 0.34 | 19-JAN-17:00 | 0.07 | 10-JAN-07:10 | 26479.92 | 19-JAN-17:00 | 22891.68 | 19-JAN-17:00 | 3954.27 | 31-JAN-17:00 | 7741.99 | 19-JAN-16:50 | 0.00 |
February | 0.845363E+11 | 0.215230E+11 | 672.00 | 0.826269E+11 | 0.190945E+10 | 0.00 | 0.56 | 27-FEB-17:00 | 0.30 | 06-FEB-07:10 | 45068.26 | 27-FEB-17:00 | 42699.93 | 26-FEB-17:54 | 3960.27 | 24-FEB-17:00 | 13904.43 | 02-FEB-13:10 | 0.00 |
March | 0.145211E+12 | 0.373124E+11 | 744.00 | 0.143172E+12 | 0.203927E+10 | 0.00 | 0.87 | 31-MAR-24:00 | 0.52 | 13-MAR-06:55 | 72714.50 | 31-MAR-24:00 | 72714.50 | 31-MAR-24:00 | 4800.87 | 07-MAR-15:00 | 21090.65 | 30-MAR-13:00 | 0.00 |
April | 0.195032E+12 | 0.539815E+11 | 720.00 | 0.192146E+12 | 0.288524E+10 | 0.00 | 1.00 | 21-APR-16:00 | 0.29 | 30-APR-23:55 | 82671.37 | 28-APR-17:20 | 79528.48 | 16-APR-18:06 | 5549.13 | 28-APR-17:30 | 29508.13 | 28-APR-15:00 | 0.00 |
May | 0.616944E+11 | 0.200938E+11 | 744.00 | 0.566988E+11 | 0.499564E+10 | 0.00 | 0.49 | 31-MAY-23:20 | 0.25 | 13-MAY-06:10 | 38933.34 | 31-MAY-23:10 | 38009.77 | 31-MAY-24:00 | 5486.69 | 23-MAY-16:00 | 11274.55 | 31-MAY-23:20 | 0.00 |
June | 0.108247E+12 | 0.354574E+11 | 720.00 | 0.102466E+12 | 0.578103E+10 | 0.00 | 0.72 | 30-JUN-23:53 | 0.47 | 07-JUN-06:10 | 57115.28 | 30-JUN-23:53 | 56979.50 | 30-JUN-23:57 | 6809.05 | 29-JUN-15:00 | 17923.87 | 29-JUN-14:00 | 0.00 |
July | 0.160671E+12 | 0.528726E+11 | 744.00 | 0.154167E+12 | 0.650356E+10 | 0.00 | 0.91 | 31-JUL-23:53 | 0.69 | 11-JUL-21:20 | 74523.99 | 31-JUL-23:57 | 74523.99 | 31-JUL-23:57 | 6657.80 | 12-JUL-10:00 | 26150.61 | 21-JUL-16:00 | 0.00 |
August | 0.208488E+12 | 0.675803E+11 | 744.00 | 0.201930E+12 | 0.655838E+10 | 0.00 | 1.00 | 01-AUG-09:10 | 0.30 | 31-AUG-24:00 | 84741.14 | 07-AUG-13:50 | 77816.05 | 03-AUG-18:00 | 7368.24 | 07-AUG-13:40 | 31001.50 | 30-AUG-16:00 | 0.00 |
September | 0.592091E+11 | 0.188865E+11 | 720.00 | 0.538525E+11 | 0.535660E+10 | 0.00 | 0.49 | 30-SEP-24:00 | 0.24 | 28-SEP-06:10 | 38398.57 | 30-SEP-24:00 | 38082.00 | 30-SEP-24:00 | 5824.50 | 18-SEP-14:30 | 11026.43 | 30-SEP-23:20 | 0.00 |
October | 0.107970E+12 | 0.327005E+11 | 744.00 | 0.103480E+12 | 0.448989E+10 | 0.00 | 0.68 | 31-OCT-24:00 | 0.39 | 28-OCT-07:00 | 55315.74 | 31-OCT-24:00 | 55208.91 | 31-OCT-24:00 | 6830.37 | 24-OCT-14:10 | 17577.05 | 05-OCT-15:00 | 0.00 |
November | 0.144059E+12 | 0.380433E+11 | 720.00 | 0.141564E+12 | 0.249463E+10 | 0.00 | 0.80 | 02-NOV-15:00 | 0.57 | 15-NOV-07:10 | 64978.12 | 07-NOV-16:40 | 61278.67 | 06-NOV-17:00 | 5606.36 | 01-NOV-11:00 | 21887.17 | 01-NOV-14:00 | 0.00 |
December | 0.191363E+12 | 0.476051E+11 | 744.00 | 0.189594E+12 | 0.176981E+10 | 0.00 | 1.00 | 15-DEC-17:00 | 0.72 | 20-DEC-07:10 | 83141.25 | 14-DEC-17:00 | 78843.23 | 15-DEC-17:00 | 5640.65 | 12-DEC-15:00 | 27575.24 | 13-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.150669E+13 | 0.436690E+12 | 8760.00 | 0.146085E+13 | 0.458421E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.402077E+11 | 0.106336E+11 | 672.00 | 0.391491E+11 | 0.105860E+10 | 0.00 | 0.34 | 0.07 | 26479.92 | 22891.68 | 3954.27 | 7741.99 | 0.00 | ||||||
Maximum of Months | 0.208488E+12 | 0.675803E+11 | 744.00 | 0.201930E+12 | 0.655838E+10 | 0.00 | 1.00 | 0.72 | 84741.14 | 79528.48 | 7368.24 | 31001.50 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.298188E+10 | 0.809863E+09 | 706.41 | 0.287757E+10 | 0.104307E+09 | 0.00 | 0.34 | 19-JAN-17:00 | 0.00 | 04-JAN-07:10 | 2716.01 | 19-JAN-17:00 | 2356.05 | 19-JAN-17:00 | 398.52 | 31-JAN-17:00 | 796.31 | 19-JAN-16:00 | 0.00 |
February | 0.771631E+10 | 0.198835E+10 | 672.00 | 0.752664E+10 | 0.189672E+09 | 0.00 | 0.56 | 27-FEB-17:00 | 0.10 | 05-FEB-08:50 | 4565.92 | 27-FEB-17:00 | 4301.81 | 26-FEB-17:47 | 396.52 | 24-FEB-17:00 | 1408.86 | 02-FEB-13:40 | 0.00 |
March | 0.140046E+11 | 0.363163E+10 | 744.00 | 0.138013E+11 | 0.203249E+09 | 0.00 | 0.84 | 31-MAR-24:00 | 0.39 | 12-MAR-08:00 | 7177.44 | 31-MAR-24:00 | 7177.44 | 31-MAR-24:00 | 480.12 | 07-MAR-15:00 | 2129.33 | 30-MAR-13:00 | 0.00 |
April | 0.194033E+11 | 0.539456E+10 | 720.00 | 0.191153E+11 | 0.288026E+09 | 0.00 | 1.00 | 28-APR-12:40 | 0.29 | 30-APR-23:55 | 8367.72 | 28-APR-17:20 | 8146.55 | 23-APR-18:08 | 548.50 | 28-APR-17:30 | 3006.78 | 28-APR-15:00 | 0.00 |
May | 0.630387E+10 | 0.205537E+10 | 744.00 | 0.580248E+10 | 0.501390E+09 | 0.00 | 0.48 | 31-MAY-23:20 | 0.25 | 13-MAY-06:10 | 3872.97 | 31-MAY-23:10 | 3774.38 | 31-MAY-24:00 | 553.98 | 23-MAY-16:00 | 1123.87 | 31-MAY-23:20 | 0.00 |
June | 0.109690E+11 | 0.359719E+10 | 720.00 | 0.103903E+11 | 0.578689E+09 | 0.00 | 0.71 | 30-JUN-23:53 | 0.45 | 07-JUN-06:10 | 5751.01 | 30-JUN-23:53 | 5737.37 | 30-JUN-23:57 | 684.14 | 29-JUN-15:00 | 1829.65 | 29-JUN-14:00 | 0.00 |
July | 0.162259E+11 | 0.534739E+10 | 744.00 | 0.155756E+11 | 0.650263E+09 | 0.00 | 0.90 | 31-JUL-23:53 | 0.68 | 15-JUL-06:00 | 7445.64 | 31-JUL-23:57 | 7445.64 | 31-JUL-23:57 | 666.59 | 12-JUL-10:00 | 2663.54 | 21-JUL-16:00 | 0.00 |
August | 0.209977E+11 | 0.682412E+10 | 744.00 | 0.203413E+11 | 0.656396E+09 | 0.00 | 1.00 | 01-AUG-10:30 | 0.29 | 31-AUG-24:00 | 8559.26 | 14-AUG-16:00 | 8019.34 | 27-AUG-17:23 | 736.46 | 07-AUG-13:40 | 3159.05 | 30-AUG-16:00 | 0.00 |
September | 0.603300E+10 | 0.192771E+10 | 720.00 | 0.549586E+10 | 0.537146E+09 | 0.00 | 0.49 | 30-SEP-23:30 | 0.23 | 28-SEP-06:10 | 3891.55 | 30-SEP-24:00 | 3860.50 | 30-SEP-24:00 | 582.78 | 18-SEP-14:40 | 1138.71 | 09-SEP-17:00 | 0.00 |
October | 0.107689E+11 | 0.327579E+10 | 744.00 | 0.103200E+11 | 0.448904E+09 | 0.00 | 0.66 | 31-OCT-24:00 | 0.32 | 28-OCT-07:00 | 5484.20 | 31-OCT-24:00 | 5472.80 | 31-OCT-24:00 | 684.19 | 24-OCT-14:10 | 1793.19 | 05-OCT-15:00 | 0.00 |
November | 0.139793E+11 | 0.372249E+10 | 720.00 | 0.137308E+11 | 0.248512E+09 | 0.00 | 0.80 | 02-NOV-15:10 | 0.50 | 16-NOV-07:10 | 6558.31 | 07-NOV-16:40 | 6197.21 | 06-NOV-17:00 | 560.83 | 01-NOV-11:00 | 2209.82 | 01-NOV-14:00 | 0.00 |
December | 0.183680E+11 | 0.461828E+10 | 744.00 | 0.181916E+11 | 0.176411E+09 | 0.00 | 0.99 | 15-DEC-17:00 | 0.62 | 20-DEC-07:10 | 8371.61 | 14-DEC-17:00 | 7958.07 | 15-DEC-17:00 | 563.85 | 12-DEC-15:00 | 2775.87 | 13-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.147752E+12 | 0.431927E+11 | 8722.41 | 0.143169E+12 | 0.458296E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.298188E+10 | 0.809863E+09 | 672.00 | 0.287757E+10 | 0.104307E+09 | 0.00 | 0.34 | 0.00 | 2716.01 | 2356.05 | 396.52 | 796.31 | 0.00 | ||||||
Maximum of Months | 0.209977E+11 | 0.682412E+10 | 744.00 | 0.203413E+11 | 0.656396E+09 | 0.00 | 1.00 | 0.68 | 8559.26 | 8146.55 | 736.46 | 3159.05 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.36 | 0.00 | 83.36 | 50.27 | 365.65 | 0.00 | 0.00 | 0.00 |
February | 98.34 | 0.00 | 98.34 | 71.65 | 310.43 | 0.00 | 0.00 | 0.00 |
March | 114.09 | 0.00 | 114.09 | 108.45 | 263.45 | 0.00 | 0.00 | 0.00 |
April | 134.65 | 0.55 | 134.10 | 180.28 | 157.19 | 0.00 | 0.00 | 0.00 |
May | 152.52 | 5.58 | 146.94 | 314.74 | 42.85 | 0.00 | 0.00 | 0.00 |
June | 173.44 | 12.01 | 161.43 | 372.91 | 35.47 | 0.00 | 0.00 | 0.00 |
July | 168.32 | 6.41 | 161.90 | 357.36 | 23.90 | 0.00 | 0.00 | 0.00 |
August | 150.73 | 1.19 | 149.54 | 321.78 | 34.44 | 0.00 | 0.00 | 0.00 |
September | 130.20 | 0.01 | 130.19 | 256.09 | 51.57 | 0.00 | 0.00 | 0.00 |
October | 113.14 | 0.00 | 113.14 | 203.94 | 98.91 | 0.00 | 0.00 | 0.00 |
November | 85.89 | 0.00 | 85.89 | 85.00 | 235.88 | 0.00 | 0.00 | 0.00 |
December | 77.49 | 0.00 | 77.49 | 55.07 | 321.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.64 | 2.15 | 121.49 | 198.89 | 161.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 77.49 | 0.00 | 77.49 | 50.27 | 23.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 173.44 | 12.01 | 161.90 | 372.91 | 365.65 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.36 | 0.00 | 83.36 | 50.27 | 365.65 | 0.00 | 0.00 | 0.00 |
February | 98.34 | 0.00 | 98.34 | 71.65 | 310.43 | 0.00 | 0.00 | 0.00 |
March | 114.09 | 0.00 | 114.09 | 108.45 | 263.45 | 0.00 | 0.00 | 0.00 |
April | 134.65 | 0.55 | 134.09 | 180.28 | 157.19 | 0.00 | 0.00 | 0.00 |
May | 152.51 | 5.58 | 146.94 | 314.73 | 42.85 | 0.00 | 0.00 | 0.00 |
June | 173.44 | 12.01 | 161.43 | 372.91 | 35.47 | 0.00 | 0.00 | 0.00 |
July | 168.31 | 6.41 | 161.90 | 357.36 | 23.89 | 0.00 | 0.00 | 0.00 |
August | 150.73 | 1.19 | 149.54 | 321.77 | 34.44 | 0.00 | 0.00 | 0.00 |
September | 130.19 | 0.01 | 130.18 | 256.09 | 51.57 | 0.00 | 0.00 | 0.00 |
October | 113.14 | 0.00 | 113.14 | 203.94 | 98.91 | 0.00 | 0.00 | 0.00 |
November | 85.89 | 0.00 | 85.89 | 84.99 | 235.88 | 0.00 | 0.00 | 0.00 |
December | 77.49 | 0.00 | 77.49 | 55.07 | 321.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.64 | 2.15 | 121.48 | 198.89 | 161.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 77.49 | 0.00 | 77.49 | 50.27 | 23.89 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 173.44 | 12.01 | 161.90 | 372.91 | 365.65 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.36 | 0.00 | 83.36 | 50.27 | 365.65 | 0.00 | 0.00 | 0.00 |
February | 98.34 | 0.00 | 98.34 | 71.65 | 310.43 | 0.00 | 0.00 | 0.00 |
March | 114.09 | 0.00 | 114.09 | 108.45 | 263.45 | 0.00 | 0.00 | 0.00 |
April | 134.65 | 0.55 | 134.10 | 180.28 | 157.19 | 0.00 | 0.00 | 0.00 |
May | 152.51 | 5.58 | 146.94 | 314.74 | 42.85 | 0.00 | 0.00 | 0.00 |
June | 173.44 | 12.01 | 161.43 | 372.91 | 35.47 | 0.00 | 0.00 | 0.00 |
July | 168.31 | 6.41 | 161.90 | 357.36 | 23.90 | 0.00 | 0.00 | 0.00 |
August | 150.73 | 1.19 | 149.54 | 321.77 | 34.44 | 0.00 | 0.00 | 0.00 |
September | 130.20 | 0.01 | 130.19 | 256.09 | 51.57 | 0.00 | 0.00 | 0.00 |
October | 113.14 | 0.00 | 113.14 | 203.94 | 98.91 | 0.00 | 0.00 | 0.00 |
November | 85.89 | 0.00 | 85.89 | 84.99 | 235.88 | 0.00 | 0.00 | 0.00 |
December | 77.49 | 0.00 | 77.49 | 55.07 | 321.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.64 | 2.15 | 121.48 | 198.89 | 161.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 77.49 | 0.00 | 77.49 | 50.27 | 23.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 173.44 | 12.01 | 161.90 | 372.91 | 365.65 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.36 | 0.00 | 83.36 | 50.27 | 365.65 | 0.00 | 0.00 | 0.00 |
February | 98.34 | 0.00 | 98.34 | 71.65 | 310.43 | 0.00 | 0.00 | 0.00 |
March | 114.09 | 0.00 | 114.09 | 108.45 | 263.45 | 0.00 | 0.00 | 0.00 |
April | 134.65 | 0.55 | 134.09 | 180.28 | 157.19 | 0.00 | 0.00 | 0.00 |
May | 152.51 | 5.58 | 146.94 | 314.73 | 42.85 | 0.00 | 0.00 | 0.00 |
June | 173.44 | 12.01 | 161.43 | 372.91 | 35.47 | 0.00 | 0.00 | 0.00 |
July | 168.31 | 6.41 | 161.90 | 357.36 | 23.89 | 0.00 | 0.00 | 0.00 |
August | 150.73 | 1.19 | 149.54 | 321.77 | 34.44 | 0.00 | 0.00 | 0.00 |
September | 130.19 | 0.01 | 130.18 | 256.09 | 51.57 | 0.00 | 0.00 | 0.00 |
October | 113.14 | 0.00 | 113.14 | 203.94 | 98.91 | 0.00 | 0.00 | 0.00 |
November | 85.89 | 0.00 | 85.89 | 84.99 | 235.88 | 0.00 | 0.00 | 0.00 |
December | 77.49 | 0.00 | 77.49 | 55.07 | 321.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.64 | 2.15 | 121.48 | 198.89 | 161.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 77.49 | 0.00 | 77.49 | 50.27 | 23.89 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 173.44 | 12.01 | 161.90 | 372.91 | 365.65 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.36 | 0.00 | 83.36 | 50.26 | 365.64 | 0.00 | 0.00 | 0.00 |
February | 98.34 | 0.00 | 98.34 | 71.64 | 310.42 | 0.00 | 0.00 | 0.00 |
March | 114.08 | 0.00 | 114.08 | 108.44 | 263.44 | 0.00 | 0.00 | 0.00 |
April | 134.64 | 0.55 | 134.09 | 180.28 | 157.18 | 0.00 | 0.00 | 0.00 |
May | 152.51 | 5.58 | 146.93 | 314.72 | 42.85 | 0.00 | 0.00 | 0.00 |
June | 173.43 | 12.01 | 161.43 | 372.89 | 35.47 | 0.00 | 0.00 | 0.00 |
July | 168.31 | 6.41 | 161.89 | 357.34 | 23.89 | 0.00 | 0.00 | 0.00 |
August | 150.72 | 1.19 | 149.54 | 321.76 | 34.44 | 0.00 | 0.00 | 0.00 |
September | 130.19 | 0.01 | 130.18 | 256.08 | 51.56 | 0.00 | 0.00 | 0.00 |
October | 113.13 | 0.00 | 113.13 | 203.93 | 98.90 | 0.00 | 0.00 | 0.00 |
November | 85.89 | 0.00 | 85.89 | 84.99 | 235.87 | 0.00 | 0.00 | 0.00 |
December | 77.49 | 0.00 | 77.49 | 55.07 | 321.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 123.63 | 2.15 | 121.48 | 198.88 | 161.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 77.49 | 0.00 | 77.49 | 50.26 | 23.89 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 173.43 | 12.01 | 161.89 | 372.89 | 365.64 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 238.37 | 121.38 | 116.99 | 269.33 | 369.40 | 0.00 | 0.00 | 0.00 |
February | 265.44 | 128.15 | 137.29 | 320.89 | 311.32 | 0.00 | 0.00 | 0.00 |
March | 312.24 | 150.59 | 161.66 | 417.02 | 264.59 | 0.00 | 0.00 | 0.00 |
April | 342.65 | 154.97 | 187.68 | 529.80 | 161.38 | 0.00 | 0.00 | 0.00 |
May | 353.18 | 153.15 | 200.03 | 664.16 | 46.78 | 0.00 | 0.00 | 0.00 |
June | 358.18 | 142.05 | 216.14 | 699.31 | 36.50 | 0.00 | 0.00 | 0.00 |
July | 345.34 | 126.38 | 218.96 | 675.29 | 22.35 | 0.00 | 0.00 | 0.00 |
August | 318.22 | 109.41 | 208.81 | 623.25 | 32.03 | 0.00 | 0.00 | 0.00 |
September | 281.88 | 96.91 | 184.97 | 523.19 | 55.44 | 0.00 | 0.00 | 0.00 |
October | 278.56 | 117.55 | 161.01 | 489.41 | 102.27 | 0.00 | 0.00 | 0.00 |
November | 246.62 | 125.81 | 120.81 | 337.01 | 235.12 | 0.00 | 0.00 | 0.00 |
December | 194.18 | 87.96 | 106.22 | 230.69 | 321.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 294.67 | 126.13 | 168.54 | 482.49 | 162.44 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 194.18 | 87.96 | 106.22 | 230.69 | 22.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 358.18 | 154.97 | 218.96 | 699.31 | 369.40 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 238.37 | 121.38 | 116.99 | 269.33 | 369.40 | 0.00 | 0.00 | 0.00 |
February | 265.44 | 128.15 | 137.29 | 320.89 | 311.32 | 0.00 | 0.00 | 0.00 |
March | 312.24 | 150.59 | 161.66 | 417.02 | 264.59 | 0.00 | 0.00 | 0.00 |
April | 342.65 | 154.97 | 187.68 | 529.80 | 161.38 | 0.00 | 0.00 | 0.00 |
May | 353.18 | 153.15 | 200.03 | 664.16 | 46.78 | 0.00 | 0.00 | 0.00 |
June | 358.18 | 142.05 | 216.14 | 699.31 | 36.50 | 0.00 | 0.00 | 0.00 |
July | 345.34 | 126.38 | 218.96 | 675.29 | 22.35 | 0.00 | 0.00 | 0.00 |
August | 318.22 | 109.41 | 208.81 | 623.25 | 32.03 | 0.00 | 0.00 | 0.00 |
September | 281.88 | 96.91 | 184.97 | 523.19 | 55.44 | 0.00 | 0.00 | 0.00 |
October | 278.56 | 117.55 | 161.01 | 489.41 | 102.27 | 0.00 | 0.00 | 0.00 |
November | 246.62 | 125.81 | 120.81 | 337.01 | 235.12 | 0.00 | 0.00 | 0.00 |
December | 194.18 | 87.96 | 106.22 | 230.69 | 321.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 294.67 | 126.13 | 168.54 | 482.49 | 162.44 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 194.18 | 87.96 | 106.22 | 230.69 | 22.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 358.18 | 154.97 | 218.96 | 699.31 | 369.40 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 238.37 | 121.38 | 116.99 | 269.32 | 369.39 | 0.00 | 0.00 | 0.00 |
February | 265.43 | 128.14 | 137.29 | 320.88 | 311.31 | 0.00 | 0.00 | 0.00 |
March | 312.24 | 150.58 | 161.65 | 417.02 | 264.58 | 0.00 | 0.00 | 0.00 |
April | 342.64 | 154.97 | 187.67 | 529.79 | 161.37 | 0.00 | 0.00 | 0.00 |
May | 353.17 | 153.14 | 200.03 | 664.15 | 46.78 | 0.00 | 0.00 | 0.00 |
June | 358.18 | 142.04 | 216.13 | 699.30 | 36.50 | 0.00 | 0.00 | 0.00 |
July | 345.33 | 126.37 | 218.96 | 675.28 | 22.35 | 0.00 | 0.00 | 0.00 |
August | 318.21 | 109.40 | 208.81 | 623.24 | 32.03 | 0.00 | 0.00 | 0.00 |
September | 281.88 | 96.91 | 184.97 | 523.18 | 55.44 | 0.00 | 0.00 | 0.00 |
October | 278.55 | 117.55 | 161.01 | 489.40 | 102.27 | 0.00 | 0.00 | 0.00 |
November | 246.62 | 125.81 | 120.81 | 337.01 | 235.12 | 0.00 | 0.00 | 0.00 |
December | 194.17 | 87.96 | 106.22 | 230.69 | 321.31 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 294.67 | 126.13 | 168.54 | 482.48 | 162.44 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 194.17 | 87.96 | 106.22 | 230.69 | 22.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 358.18 | 154.97 | 218.96 | 699.30 | 369.39 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 481.83 | 343.63 | 138.20 | 681.14 | 327.79 | 0.00 | 0.00 | 0.00 |
February | 436.99 | 282.86 | 154.13 | 630.55 | 283.45 | 0.00 | 0.00 | 0.00 |
March | 278.98 | 125.91 | 153.08 | 413.19 | 252.18 | 0.00 | 0.00 | 0.00 |
April | 206.78 | 48.45 | 158.33 | 340.45 | 161.55 | 0.00 | 0.00 | 0.00 |
May | 158.00 | 6.71 | 151.28 | 329.81 | 44.66 | 0.00 | 0.00 | 0.00 |
June | 156.07 | 1.45 | 154.62 | 336.89 | 36.88 | 0.00 | 0.00 | 0.00 |
July | 163.38 | 3.00 | 160.38 | 348.65 | 23.75 | 0.00 | 0.00 | 0.00 |
August | 192.21 | 23.07 | 169.14 | 411.45 | 36.88 | 0.00 | 0.00 | 0.00 |
September | 230.62 | 60.78 | 169.84 | 455.73 | 55.69 | 0.00 | 0.00 | 0.00 |
October | 357.81 | 186.38 | 171.43 | 648.01 | 103.70 | 0.00 | 0.00 | 0.00 |
November | 455.33 | 313.50 | 141.83 | 703.02 | 222.00 | 0.00 | 0.00 | 0.00 |
December | 470.80 | 338.11 | 132.70 | 693.26 | 295.52 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 298.34 | 143.77 | 154.57 | 498.71 | 152.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 156.07 | 1.45 | 132.70 | 329.81 | 23.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 481.83 | 343.63 | 171.43 | 703.02 | 327.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 481.82 | 343.62 | 138.20 | 681.13 | 327.79 | 0.00 | 0.00 | 0.00 |
February | 436.99 | 282.85 | 154.13 | 630.55 | 283.45 | 0.00 | 0.00 | 0.00 |
March | 278.98 | 125.90 | 153.08 | 413.18 | 252.18 | 0.00 | 0.00 | 0.00 |
April | 206.78 | 48.45 | 158.33 | 340.45 | 161.55 | 0.00 | 0.00 | 0.00 |
May | 158.00 | 6.71 | 151.28 | 329.81 | 44.66 | 0.00 | 0.00 | 0.00 |
June | 156.07 | 1.45 | 154.62 | 336.89 | 36.88 | 0.00 | 0.00 | 0.00 |
July | 163.38 | 3.00 | 160.38 | 348.65 | 23.75 | 0.00 | 0.00 | 0.00 |
August | 192.21 | 23.07 | 169.14 | 411.45 | 36.88 | 0.00 | 0.00 | 0.00 |
September | 230.62 | 60.78 | 169.84 | 455.73 | 55.69 | 0.00 | 0.00 | 0.00 |
October | 357.81 | 186.38 | 171.42 | 648.01 | 103.70 | 0.00 | 0.00 | 0.00 |
November | 455.33 | 313.50 | 141.83 | 703.02 | 222.00 | 0.00 | 0.00 | 0.00 |
December | 470.80 | 338.10 | 132.70 | 693.25 | 295.51 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 298.34 | 143.77 | 154.57 | 498.71 | 152.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 156.07 | 1.45 | 132.70 | 329.81 | 23.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 481.82 | 343.62 | 171.42 | 703.02 | 327.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 481.83 | 343.63 | 138.20 | 681.14 | 327.79 | 0.00 | 0.00 | 0.00 |
February | 436.99 | 282.86 | 154.13 | 630.55 | 283.45 | 0.00 | 0.00 | 0.00 |
March | 278.98 | 125.91 | 153.08 | 413.19 | 252.18 | 0.00 | 0.00 | 0.00 |
April | 206.78 | 48.45 | 158.33 | 340.45 | 161.55 | 0.00 | 0.00 | 0.00 |
May | 158.00 | 6.71 | 151.28 | 329.81 | 44.66 | 0.00 | 0.00 | 0.00 |
June | 156.07 | 1.45 | 154.62 | 336.89 | 36.88 | 0.00 | 0.00 | 0.00 |
July | 163.38 | 3.00 | 160.38 | 348.65 | 23.75 | 0.00 | 0.00 | 0.00 |
August | 192.21 | 23.07 | 169.14 | 411.45 | 36.88 | 0.00 | 0.00 | 0.00 |
September | 230.62 | 60.78 | 169.84 | 455.73 | 55.69 | 0.00 | 0.00 | 0.00 |
October | 357.81 | 186.38 | 171.43 | 648.01 | 103.70 | 0.00 | 0.00 | 0.00 |
November | 455.33 | 313.50 | 141.83 | 703.02 | 222.00 | 0.00 | 0.00 | 0.00 |
December | 470.80 | 338.11 | 132.70 | 693.26 | 295.52 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 298.34 | 143.77 | 154.57 | 498.71 | 152.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 156.07 | 1.45 | 132.70 | 329.81 | 23.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 481.83 | 343.63 | 171.43 | 703.02 | 327.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 481.82 | 343.62 | 138.20 | 681.13 | 327.79 | 0.00 | 0.00 | 0.00 |
February | 436.99 | 282.85 | 154.13 | 630.55 | 283.45 | 0.00 | 0.00 | 0.00 |
March | 278.98 | 125.90 | 153.08 | 413.18 | 252.18 | 0.00 | 0.00 | 0.00 |
April | 206.78 | 48.45 | 158.33 | 340.45 | 161.55 | 0.00 | 0.00 | 0.00 |
May | 158.00 | 6.71 | 151.28 | 329.81 | 44.66 | 0.00 | 0.00 | 0.00 |
June | 156.07 | 1.45 | 154.62 | 336.89 | 36.88 | 0.00 | 0.00 | 0.00 |
July | 163.38 | 3.00 | 160.38 | 348.65 | 23.75 | 0.00 | 0.00 | 0.00 |
August | 192.21 | 23.07 | 169.14 | 411.45 | 36.88 | 0.00 | 0.00 | 0.00 |
September | 230.62 | 60.78 | 169.84 | 455.73 | 55.69 | 0.00 | 0.00 | 0.00 |
October | 357.81 | 186.38 | 171.42 | 648.01 | 103.70 | 0.00 | 0.00 | 0.00 |
November | 455.33 | 313.50 | 141.83 | 703.02 | 222.00 | 0.00 | 0.00 | 0.00 |
December | 470.80 | 338.10 | 132.70 | 693.25 | 295.51 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 298.34 | 143.77 | 154.57 | 498.71 | 152.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 156.07 | 1.45 | 132.70 | 329.81 | 23.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 481.82 | 343.62 | 171.42 | 703.02 | 327.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 481.81 | 343.61 | 138.20 | 681.11 | 327.78 | 0.00 | 0.00 | 0.00 |
February | 436.97 | 282.84 | 154.13 | 630.53 | 283.44 | 0.00 | 0.00 | 0.00 |
March | 278.97 | 125.90 | 153.07 | 413.17 | 252.17 | 0.00 | 0.00 | 0.00 |
April | 206.77 | 48.45 | 158.32 | 340.44 | 161.55 | 0.00 | 0.00 | 0.00 |
May | 157.99 | 6.71 | 151.27 | 329.80 | 44.65 | 0.00 | 0.00 | 0.00 |
June | 156.07 | 1.45 | 154.61 | 336.88 | 36.88 | 0.00 | 0.00 | 0.00 |
July | 163.38 | 3.00 | 160.37 | 348.64 | 23.75 | 0.00 | 0.00 | 0.00 |
August | 192.20 | 23.07 | 169.13 | 411.43 | 36.88 | 0.00 | 0.00 | 0.00 |
September | 230.61 | 60.78 | 169.84 | 455.71 | 55.68 | 0.00 | 0.00 | 0.00 |
October | 357.79 | 186.38 | 171.42 | 647.98 | 103.70 | 0.00 | 0.00 | 0.00 |
November | 455.31 | 313.49 | 141.83 | 702.99 | 221.99 | 0.00 | 0.00 | 0.00 |
December | 470.78 | 338.09 | 132.69 | 693.23 | 295.50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 298.33 | 143.77 | 154.56 | 498.69 | 152.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 156.07 | 1.45 | 132.69 | 329.80 | 23.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 481.81 | 343.61 | 171.42 | 702.99 | 327.78 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 253.55 | 137.10 | 116.44 | 307.07 | 416.30 | 0.00 | 0.00 | 0.00 |
February | 287.07 | 145.30 | 141.77 | 360.22 | 368.95 | 0.00 | 0.00 | 0.00 |
March | 282.94 | 125.25 | 157.69 | 369.63 | 326.85 | 0.00 | 0.00 | 0.00 |
April | 351.42 | 161.66 | 189.76 | 530.96 | 214.39 | 0.00 | 0.00 | 0.00 |
May | 292.25 | 95.20 | 197.05 | 556.30 | 64.91 | 0.00 | 0.00 | 0.00 |
June | 324.65 | 113.84 | 210.81 | 627.94 | 59.78 | 0.00 | 0.00 | 0.00 |
July | 296.35 | 82.20 | 214.14 | 568.00 | 47.14 | 0.00 | 0.00 | 0.00 |
August | 299.64 | 91.73 | 207.92 | 570.96 | 68.94 | 0.00 | 0.00 | 0.00 |
September | 275.92 | 94.65 | 181.27 | 508.02 | 75.10 | 0.00 | 0.00 | 0.00 |
October | 282.49 | 122.06 | 160.43 | 493.18 | 135.33 | 0.00 | 0.00 | 0.00 |
November | 242.12 | 121.68 | 120.44 | 336.14 | 296.15 | 0.00 | 0.00 | 0.00 |
December | 232.90 | 123.85 | 109.05 | 291.31 | 396.99 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 284.95 | 117.60 | 167.35 | 460.35 | 205.05 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 232.90 | 82.20 | 109.05 | 291.31 | 47.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 351.42 | 161.66 | 214.14 | 627.94 | 416.30 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 253.55 | 137.10 | 116.44 | 307.07 | 416.30 | 0.00 | 0.00 | 0.00 |
February | 287.07 | 145.30 | 141.77 | 360.22 | 368.95 | 0.00 | 0.00 | 0.00 |
March | 282.94 | 125.25 | 157.69 | 369.63 | 326.85 | 0.00 | 0.00 | 0.00 |
April | 351.42 | 161.66 | 189.76 | 530.96 | 214.39 | 0.00 | 0.00 | 0.00 |
May | 292.25 | 95.20 | 197.05 | 556.30 | 64.91 | 0.00 | 0.00 | 0.00 |
June | 324.65 | 113.84 | 210.81 | 627.94 | 59.78 | 0.00 | 0.00 | 0.00 |
July | 296.35 | 82.20 | 214.14 | 568.00 | 47.14 | 0.00 | 0.00 | 0.00 |
August | 299.64 | 91.73 | 207.92 | 570.96 | 68.94 | 0.00 | 0.00 | 0.00 |
September | 275.92 | 94.65 | 181.27 | 508.02 | 75.10 | 0.00 | 0.00 | 0.00 |
October | 282.49 | 122.06 | 160.43 | 493.18 | 135.33 | 0.00 | 0.00 | 0.00 |
November | 242.12 | 121.68 | 120.44 | 336.14 | 296.15 | 0.00 | 0.00 | 0.00 |
December | 232.90 | 123.85 | 109.05 | 291.31 | 396.99 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 284.95 | 117.60 | 167.35 | 460.35 | 205.05 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 232.90 | 82.20 | 109.05 | 291.31 | 47.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 351.42 | 161.66 | 214.14 | 627.94 | 416.30 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 253.54 | 137.10 | 116.44 | 307.06 | 416.29 | 0.00 | 0.00 | 0.00 |
February | 287.07 | 145.30 | 141.77 | 360.22 | 368.94 | 0.00 | 0.00 | 0.00 |
March | 282.93 | 125.25 | 157.69 | 369.62 | 326.84 | 0.00 | 0.00 | 0.00 |
April | 351.41 | 161.66 | 189.76 | 530.95 | 214.39 | 0.00 | 0.00 | 0.00 |
May | 292.24 | 95.20 | 197.04 | 556.29 | 64.91 | 0.00 | 0.00 | 0.00 |
June | 324.65 | 113.84 | 210.81 | 627.92 | 59.77 | 0.00 | 0.00 | 0.00 |
July | 296.34 | 82.20 | 214.14 | 567.99 | 47.14 | 0.00 | 0.00 | 0.00 |
August | 299.64 | 91.72 | 207.92 | 570.95 | 68.93 | 0.00 | 0.00 | 0.00 |
September | 275.92 | 94.65 | 181.26 | 508.01 | 75.10 | 0.00 | 0.00 | 0.00 |
October | 282.48 | 122.06 | 160.42 | 493.17 | 135.33 | 0.00 | 0.00 | 0.00 |
November | 242.12 | 121.68 | 120.44 | 336.14 | 296.15 | 0.00 | 0.00 | 0.00 |
December | 232.90 | 123.85 | 109.05 | 291.31 | 396.98 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 284.94 | 117.59 | 167.35 | 460.34 | 205.05 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 232.90 | 82.20 | 109.05 | 291.31 | 47.14 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 351.41 | 161.66 | 214.14 | 627.92 | 416.29 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 416.80 | 0.00 | 416.80 | 293.93 | 1642.49 | 0.00 | 0.00 | 0.00 |
February | 491.72 | 0.00 | 491.72 | 398.73 | 1383.59 | 0.00 | 0.00 | 0.00 |
March | 570.44 | 0.00 | 570.44 | 578.48 | 1193.27 | 0.00 | 0.00 | 0.00 |
April | 673.25 | 2.76 | 670.48 | 921.19 | 747.13 | 0.00 | 0.00 | 0.00 |
May | 762.58 | 27.89 | 734.69 | 1576.91 | 214.44 | 0.00 | 0.00 | 0.00 |
June | 867.22 | 60.05 | 807.17 | 1868.73 | 184.97 | 0.00 | 0.00 | 0.00 |
July | 841.58 | 32.06 | 809.51 | 1797.92 | 122.32 | 0.00 | 0.00 | 0.00 |
August | 753.65 | 5.93 | 747.72 | 1627.92 | 171.62 | 0.00 | 0.00 | 0.00 |
September | 650.98 | 0.05 | 650.93 | 1289.25 | 245.14 | 0.00 | 0.00 | 0.00 |
October | 565.69 | 0.00 | 565.69 | 1036.84 | 464.67 | 0.00 | 0.00 | 0.00 |
November | 429.45 | 0.00 | 429.45 | 460.39 | 1055.88 | 0.00 | 0.00 | 0.00 |
December | 387.46 | 0.00 | 387.46 | 319.11 | 1408.12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 618.19 | 10.76 | 607.43 | 1017.85 | 732.76 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 387.46 | 0.00 | 387.46 | 293.93 | 122.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 867.22 | 60.05 | 809.51 | 1868.73 | 1642.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 715.11 | 364.14 | 350.98 | 824.03 | 1028.59 | 0.00 | 0.00 | 0.00 |
February | 796.30 | 384.43 | 411.87 | 975.73 | 871.99 | 0.00 | 0.00 | 0.00 |
March | 936.72 | 451.75 | 484.96 | 1249.90 | 759.35 | 0.00 | 0.00 | 0.00 |
April | 1027.94 | 464.91 | 563.03 | 1572.02 | 497.68 | 0.00 | 0.00 | 0.00 |
May | 1059.53 | 459.43 | 600.10 | 1972.62 | 150.63 | 0.00 | 0.00 | 0.00 |
June | 1074.54 | 426.13 | 648.41 | 2078.93 | 128.63 | 0.00 | 0.00 | 0.00 |
July | 1036.01 | 379.12 | 656.88 | 2005.72 | 85.50 | 0.00 | 0.00 | 0.00 |
August | 954.65 | 328.22 | 626.43 | 1851.46 | 119.85 | 0.00 | 0.00 | 0.00 |
September | 845.64 | 290.73 | 554.91 | 1557.52 | 169.60 | 0.00 | 0.00 | 0.00 |
October | 835.67 | 352.65 | 483.02 | 1455.45 | 308.97 | 0.00 | 0.00 | 0.00 |
November | 739.86 | 377.43 | 362.43 | 1012.80 | 673.47 | 0.00 | 0.00 | 0.00 |
December | 582.53 | 263.87 | 318.66 | 705.54 | 898.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 884.01 | 378.40 | 505.61 | 1441.00 | 472.28 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 582.53 | 263.87 | 318.66 | 705.54 | 85.50 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1074.54 | 464.91 | 656.88 | 2078.93 | 1028.59 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2409.18 | 1718.17 | 691.02 | 3376.14 | 1609.27 | 0.00 | 0.00 | 0.00 |
February | 2184.99 | 1414.31 | 770.68 | 3132.70 | 1379.42 | 0.00 | 0.00 | 0.00 |
March | 1394.95 | 629.54 | 765.41 | 2058.88 | 1211.05 | 0.00 | 0.00 | 0.00 |
April | 1033.92 | 242.27 | 791.64 | 1700.91 | 792.14 | 0.00 | 0.00 | 0.00 |
May | 789.99 | 33.57 | 756.41 | 1650.91 | 223.53 | 0.00 | 0.00 | 0.00 |
June | 780.37 | 7.27 | 773.10 | 1691.93 | 189.67 | 0.00 | 0.00 | 0.00 |
July | 816.92 | 15.01 | 801.91 | 1756.49 | 119.71 | 0.00 | 0.00 | 0.00 |
August | 961.07 | 115.36 | 845.71 | 2066.89 | 186.22 | 0.00 | 0.00 | 0.00 |
September | 1153.12 | 303.90 | 849.22 | 2270.37 | 274.06 | 0.00 | 0.00 | 0.00 |
October | 1789.07 | 931.94 | 857.14 | 3219.47 | 517.98 | 0.00 | 0.00 | 0.00 |
November | 2276.71 | 1567.54 | 709.17 | 3495.49 | 1086.56 | 0.00 | 0.00 | 0.00 |
December | 2354.07 | 1690.56 | 663.50 | 3450.17 | 1429.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1491.72 | 718.87 | 772.84 | 2486.09 | 748.21 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 780.37 | 7.27 | 663.50 | 1650.91 | 119.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2409.18 | 1718.17 | 857.14 | 3495.49 | 1609.27 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 760.64 | 411.31 | 349.33 | 949.75 | 1112.97 | 0.00 | 0.00 | 0.00 |
February | 861.21 | 435.89 | 425.32 | 1117.34 | 956.24 | 0.00 | 0.00 | 0.00 |
March | 848.81 | 375.75 | 473.06 | 1145.82 | 832.33 | 0.00 | 0.00 | 0.00 |
April | 1054.25 | 484.97 | 569.27 | 1629.46 | 555.77 | 0.00 | 0.00 | 0.00 |
May | 876.73 | 285.60 | 591.13 | 1681.08 | 176.31 | 0.00 | 0.00 | 0.00 |
June | 973.95 | 341.51 | 632.43 | 1905.65 | 156.39 | 0.00 | 0.00 | 0.00 |
July | 889.03 | 246.60 | 642.43 | 1742.77 | 107.42 | 0.00 | 0.00 | 0.00 |
August | 898.92 | 275.17 | 623.75 | 1763.70 | 149.01 | 0.00 | 0.00 | 0.00 |
September | 827.76 | 283.96 | 543.80 | 1536.82 | 196.09 | 0.00 | 0.00 | 0.00 |
October | 847.45 | 366.17 | 481.28 | 1503.40 | 353.22 | 0.00 | 0.00 | 0.00 |
November | 726.37 | 365.04 | 361.32 | 1048.26 | 748.47 | 0.00 | 0.00 | 0.00 |
December | 698.70 | 371.56 | 327.14 | 923.61 | 970.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 854.83 | 352.79 | 502.04 | 1413.44 | 523.95 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 698.70 | 246.60 | 327.14 | 923.61 | 107.42 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1054.25 | 484.97 | 642.43 | 1905.65 | 1112.97 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 416.80 | 0.00 | 416.80 | 323.53 | 1504.56 | 0.00 | 0.00 | 0.00 |
February | 491.72 | 0.00 | 491.72 | 421.39 | 1273.08 | 0.00 | 0.00 | 0.00 |
March | 570.44 | 0.00 | 570.44 | 593.90 | 1118.65 | 0.00 | 0.00 | 0.00 |
April | 673.25 | 2.76 | 670.48 | 917.83 | 726.90 | 0.00 | 0.00 | 0.00 |
May | 762.58 | 27.89 | 734.69 | 1550.94 | 226.68 | 0.00 | 0.00 | 0.00 |
June | 867.22 | 60.05 | 807.17 | 1839.20 | 198.34 | 0.00 | 0.00 | 0.00 |
July | 841.58 | 32.06 | 809.51 | 1764.14 | 136.10 | 0.00 | 0.00 | 0.00 |
August | 753.65 | 5.93 | 747.72 | 1600.98 | 182.50 | 0.00 | 0.00 | 0.00 |
September | 650.98 | 0.05 | 650.93 | 1264.00 | 256.05 | 0.00 | 0.00 | 0.00 |
October | 565.69 | 0.00 | 565.69 | 1025.22 | 457.06 | 0.00 | 0.00 | 0.00 |
November | 429.45 | 0.00 | 429.45 | 477.05 | 983.10 | 0.00 | 0.00 | 0.00 |
December | 387.46 | 0.00 | 387.46 | 340.97 | 1294.77 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 618.19 | 10.76 | 607.43 | 1013.51 | 693.45 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 387.46 | 0.00 | 387.46 | 323.53 | 136.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 867.22 | 60.05 | 809.51 | 1839.20 | 1504.56 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 715.11 | 364.14 | 350.98 | 855.19 | 949.08 | 0.00 | 0.00 | 0.00 |
February | 796.30 | 384.43 | 411.87 | 997.57 | 810.34 | 0.00 | 0.00 | 0.00 |
March | 936.72 | 451.75 | 484.96 | 1257.62 | 722.07 | 0.00 | 0.00 | 0.00 |
April | 1027.94 | 464.91 | 563.03 | 1565.93 | 490.29 | 0.00 | 0.00 | 0.00 |
May | 1059.53 | 459.43 | 600.10 | 1952.59 | 158.78 | 0.00 | 0.00 | 0.00 |
June | 1074.54 | 426.13 | 648.41 | 2057.54 | 138.13 | 0.00 | 0.00 | 0.00 |
July | 1036.01 | 379.12 | 656.88 | 1982.24 | 94.77 | 0.00 | 0.00 | 0.00 |
August | 954.65 | 328.22 | 626.43 | 1831.47 | 127.20 | 0.00 | 0.00 | 0.00 |
September | 845.64 | 290.73 | 554.91 | 1539.62 | 177.08 | 0.00 | 0.00 | 0.00 |
October | 835.67 | 352.65 | 483.02 | 1445.22 | 306.13 | 0.00 | 0.00 | 0.00 |
November | 739.86 | 377.43 | 362.43 | 1023.60 | 639.16 | 0.00 | 0.00 | 0.00 |
December | 582.53 | 263.87 | 318.66 | 724.50 | 835.87 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 884.01 | 378.40 | 505.61 | 1438.48 | 452.17 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 582.53 | 263.87 | 318.66 | 724.50 | 94.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1074.54 | 464.91 | 656.88 | 2057.54 | 949.08 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2409.18 | 1718.17 | 691.02 | 3405.84 | 1505.21 | 0.00 | 0.00 | 0.00 |
February | 2184.99 | 1414.31 | 770.68 | 3156.76 | 1294.27 | 0.00 | 0.00 | 0.00 |
March | 1394.95 | 629.54 | 765.41 | 2067.38 | 1149.08 | 0.00 | 0.00 | 0.00 |
April | 1033.92 | 242.27 | 791.64 | 1691.90 | 775.82 | 0.00 | 0.00 | 0.00 |
May | 789.99 | 33.57 | 756.41 | 1624.75 | 236.10 | 0.00 | 0.00 | 0.00 |
June | 780.37 | 7.27 | 773.10 | 1663.62 | 204.08 | 0.00 | 0.00 | 0.00 |
July | 816.92 | 15.01 | 801.91 | 1721.83 | 133.27 | 0.00 | 0.00 | 0.00 |
August | 961.07 | 115.36 | 845.71 | 2038.77 | 198.10 | 0.00 | 0.00 | 0.00 |
September | 1153.12 | 303.90 | 849.22 | 2244.48 | 285.72 | 0.00 | 0.00 | 0.00 |
October | 1789.07 | 931.94 | 857.14 | 3200.89 | 516.39 | 0.00 | 0.00 | 0.00 |
November | 2276.71 | 1567.54 | 709.17 | 3500.59 | 1044.47 | 0.00 | 0.00 | 0.00 |
December | 2354.07 | 1690.56 | 663.50 | 3468.17 | 1344.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1491.72 | 718.87 | 772.84 | 2478.80 | 720.82 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 780.37 | 7.27 | 663.50 | 1624.75 | 133.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2409.18 | 1718.17 | 857.14 | 3500.59 | 1505.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 760.64 | 411.31 | 349.33 | 965.67 | 1037.21 | 0.00 | 0.00 | 0.00 |
February | 861.21 | 435.89 | 425.32 | 1127.83 | 895.50 | 0.00 | 0.00 | 0.00 |
March | 848.81 | 375.75 | 473.06 | 1150.53 | 789.69 | 0.00 | 0.00 | 0.00 |
April | 1054.25 | 484.97 | 569.27 | 1621.68 | 544.55 | 0.00 | 0.00 | 0.00 |
May | 876.73 | 285.60 | 591.13 | 1664.45 | 182.76 | 0.00 | 0.00 | 0.00 |
June | 973.95 | 341.51 | 632.43 | 1886.73 | 163.47 | 0.00 | 0.00 | 0.00 |
July | 889.03 | 246.60 | 642.43 | 1722.04 | 113.73 | 0.00 | 0.00 | 0.00 |
August | 898.92 | 275.17 | 623.75 | 1745.94 | 154.97 | 0.00 | 0.00 | 0.00 |
September | 827.76 | 283.96 | 543.80 | 1521.59 | 201.68 | 0.00 | 0.00 | 0.00 |
October | 847.45 | 366.17 | 481.28 | 1493.94 | 349.39 | 0.00 | 0.00 | 0.00 |
November | 726.37 | 365.04 | 361.32 | 1054.17 | 709.56 | 0.00 | 0.00 | 0.00 |
December | 698.70 | 371.56 | 327.14 | 934.01 | 907.02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 854.83 | 352.79 | 502.04 | 1408.43 | 502.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 698.70 | 246.60 | 327.14 | 934.01 | 113.73 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1054.25 | 484.97 | 642.43 | 1886.73 | 1037.21 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.223271E+09 | 0.00 | 0.223271E+09 | 0.134637E+09 | 0.979361E+09 |
February | 0.237915E+09 | 0.00 | 0.237915E+09 | 0.173332E+09 | 0.750993E+09 |
March | 0.305574E+09 | 0.00 | 0.305574E+09 | 0.290464E+09 | 0.705629E+09 |
April | 0.349011E+09 | 1432452.17 | 0.347579E+09 | 0.467297E+09 | 0.407428E+09 |
May | 0.408498E+09 | 14941839.27 | 0.393557E+09 | 0.842992E+09 | 0.114763E+09 |
June | 0.449564E+09 | 31128636.17 | 0.418436E+09 | 0.966582E+09 | 91947773.30 |
July | 0.450816E+09 | 17175142.31 | 0.433641E+09 | 0.957158E+09 | 64001331.13 |
August | 0.403714E+09 | 3175239.04 | 0.400538E+09 | 0.861844E+09 | 92244014.98 |
September | 0.337469E+09 | 25991.58 | 0.337443E+09 | 0.663790E+09 | 0.133660E+09 |
October | 0.303029E+09 | 0.00 | 0.303029E+09 | 0.546233E+09 | 0.264912E+09 |
November | 0.222627E+09 | 0.00 | 0.222627E+09 | 0.220309E+09 | 0.611392E+09 |
December | 0.207556E+09 | 0.00 | 0.207556E+09 | 0.147495E+09 | 0.861724E+09 |
Annual Sum or Average | 0.389904E+10 | 67879300.53 | 0.383116E+10 | 0.627213E+10 | 0.507806E+10 |
Minimum of Months | 0.207556E+09 | 0.00 | 0.207556E+09 | 0.134637E+09 | 64001331.13 |
Maximum of Months | 0.450816E+09 | 31128636.17 | 0.433641E+09 | 0.966582E+09 | 0.979361E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.223268E+09 | 0.00 | 0.223268E+09 | 0.134635E+09 | 0.979360E+09 |
February | 0.237912E+09 | 0.00 | 0.237912E+09 | 0.173330E+09 | 0.750991E+09 |
March | 0.305570E+09 | 0.00 | 0.305570E+09 | 0.290460E+09 | 0.705628E+09 |
April | 0.349007E+09 | 1432420.68 | 0.347574E+09 | 0.467292E+09 | 0.407426E+09 |
May | 0.408493E+09 | 14941510.79 | 0.393551E+09 | 0.842984E+09 | 0.114762E+09 |
June | 0.449558E+09 | 31127951.84 | 0.418430E+09 | 0.966572E+09 | 91946389.67 |
July | 0.450809E+09 | 17174764.73 | 0.433634E+09 | 0.957147E+09 | 64000018.18 |
August | 0.403708E+09 | 3175169.23 | 0.400533E+09 | 0.861836E+09 | 92242641.50 |
September | 0.337464E+09 | 25991.01 | 0.337438E+09 | 0.663783E+09 | 0.133659E+09 |
October | 0.303025E+09 | 0.00 | 0.303025E+09 | 0.546228E+09 | 0.264911E+09 |
November | 0.222624E+09 | 0.00 | 0.222624E+09 | 0.220306E+09 | 0.611390E+09 |
December | 0.207553E+09 | 0.00 | 0.207553E+09 | 0.147493E+09 | 0.861723E+09 |
Annual Sum or Average | 0.389899E+10 | 67877808.28 | 0.383111E+10 | 0.627206E+10 | 0.507804E+10 |
Minimum of Months | 0.207553E+09 | 0.00 | 0.207553E+09 | 0.134635E+09 | 64000018.18 |
Maximum of Months | 0.450809E+09 | 31127951.84 | 0.433634E+09 | 0.966572E+09 | 0.979360E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.223269E+09 | 0.00 | 0.223269E+09 | 0.134635E+09 | 0.979360E+09 |
February | 0.237913E+09 | 0.00 | 0.237913E+09 | 0.173331E+09 | 0.750992E+09 |
March | 0.305571E+09 | 0.00 | 0.305571E+09 | 0.290461E+09 | 0.705628E+09 |
April | 0.349008E+09 | 1432431.18 | 0.347576E+09 | 0.467294E+09 | 0.407427E+09 |
May | 0.408494E+09 | 14941620.28 | 0.393553E+09 | 0.842987E+09 | 0.114762E+09 |
June | 0.449560E+09 | 31128179.95 | 0.418432E+09 | 0.966575E+09 | 91946850.88 |
July | 0.450811E+09 | 17174890.59 | 0.433636E+09 | 0.957151E+09 | 64000455.84 |
August | 0.403710E+09 | 3175192.50 | 0.400535E+09 | 0.861839E+09 | 92243099.32 |
September | 0.337466E+09 | 25991.20 | 0.337440E+09 | 0.663785E+09 | 0.133659E+09 |
October | 0.303026E+09 | 0.00 | 0.303026E+09 | 0.546230E+09 | 0.264911E+09 |
November | 0.222625E+09 | 0.00 | 0.222625E+09 | 0.220307E+09 | 0.611391E+09 |
December | 0.207554E+09 | 0.00 | 0.207554E+09 | 0.147494E+09 | 0.861723E+09 |
Annual Sum or Average | 0.389901E+10 | 67878305.70 | 0.383113E+10 | 0.627209E+10 | 0.507804E+10 |
Minimum of Months | 0.207554E+09 | 0.00 | 0.207554E+09 | 0.134635E+09 | 64000455.84 |
Maximum of Months | 0.450811E+09 | 31128179.95 | 0.433636E+09 | 0.966575E+09 | 0.979360E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.223268E+09 | 0.00 | 0.223268E+09 | 0.134635E+09 | 0.979360E+09 |
February | 0.237912E+09 | 0.00 | 0.237912E+09 | 0.173330E+09 | 0.750991E+09 |
March | 0.305570E+09 | 0.00 | 0.305570E+09 | 0.290460E+09 | 0.705628E+09 |
April | 0.349007E+09 | 1432420.68 | 0.347574E+09 | 0.467292E+09 | 0.407426E+09 |
May | 0.408493E+09 | 14941510.79 | 0.393551E+09 | 0.842984E+09 | 0.114762E+09 |
June | 0.449558E+09 | 31127951.84 | 0.418430E+09 | 0.966572E+09 | 91946389.67 |
July | 0.450809E+09 | 17174764.73 | 0.433634E+09 | 0.957147E+09 | 64000018.18 |
August | 0.403708E+09 | 3175169.23 | 0.400533E+09 | 0.861836E+09 | 92242641.50 |
September | 0.337464E+09 | 25991.01 | 0.337438E+09 | 0.663783E+09 | 0.133659E+09 |
October | 0.303025E+09 | 0.00 | 0.303025E+09 | 0.546228E+09 | 0.264911E+09 |
November | 0.222624E+09 | 0.00 | 0.222624E+09 | 0.220306E+09 | 0.611390E+09 |
December | 0.207553E+09 | 0.00 | 0.207553E+09 | 0.147493E+09 | 0.861723E+09 |
Annual Sum or Average | 0.389899E+10 | 67877808.28 | 0.383111E+10 | 0.627206E+10 | 0.507804E+10 |
Minimum of Months | 0.207553E+09 | 0.00 | 0.207553E+09 | 0.134635E+09 | 64000018.18 |
Maximum of Months | 0.450809E+09 | 31127951.84 | 0.433634E+09 | 0.966572E+09 | 0.979360E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.223260E+09 | 0.00 | 0.223260E+09 | 0.134630E+09 | 0.979320E+09 |
February | 0.237903E+09 | 0.00 | 0.237903E+09 | 0.173323E+09 | 0.750961E+09 |
March | 0.305558E+09 | 0.00 | 0.305558E+09 | 0.290449E+09 | 0.705600E+09 |
April | 0.348993E+09 | 1432368.20 | 0.347561E+09 | 0.467274E+09 | 0.407410E+09 |
May | 0.408477E+09 | 14940963.33 | 0.393536E+09 | 0.842951E+09 | 0.114757E+09 |
June | 0.449541E+09 | 31126811.29 | 0.418414E+09 | 0.966535E+09 | 91942914.42 |
July | 0.450792E+09 | 17174135.44 | 0.433618E+09 | 0.957111E+09 | 63997657.52 |
August | 0.403693E+09 | 3175052.89 | 0.400517E+09 | 0.861802E+09 | 92239152.62 |
September | 0.337451E+09 | 25990.05 | 0.337425E+09 | 0.663757E+09 | 0.133654E+09 |
October | 0.303013E+09 | 0.00 | 0.303013E+09 | 0.546207E+09 | 0.264900E+09 |
November | 0.222615E+09 | 0.00 | 0.222615E+09 | 0.220298E+09 | 0.611366E+09 |
December | 0.207545E+09 | 0.00 | 0.207545E+09 | 0.147488E+09 | 0.861688E+09 |
Annual Sum or Average | 0.389884E+10 | 67875321.21 | 0.383097E+10 | 0.627182E+10 | 0.507784E+10 |
Minimum of Months | 0.207545E+09 | 0.00 | 0.207545E+09 | 0.134630E+09 | 63997657.52 |
Maximum of Months | 0.450792E+09 | 31126811.29 | 0.433618E+09 | 0.966535E+09 | 0.979320E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.638461E+09 | 0.325107E+09 | 0.313354E+09 | 0.721368E+09 | 0.989398E+09 |
February | 0.642146E+09 | 0.310011E+09 | 0.332135E+09 | 0.776294E+09 | 0.753137E+09 |
March | 0.836308E+09 | 0.403329E+09 | 0.432980E+09 | 0.111695E+10 | 0.708667E+09 |
April | 0.888146E+09 | 0.401684E+09 | 0.486462E+09 | 0.137324E+10 | 0.418287E+09 |
May | 0.945954E+09 | 0.410184E+09 | 0.535770E+09 | 0.177889E+10 | 0.125299E+09 |
June | 0.928410E+09 | 0.368182E+09 | 0.560228E+09 | 0.181262E+10 | 94609742.59 |
July | 0.924957E+09 | 0.338484E+09 | 0.586473E+09 | 0.180870E+10 | 59856402.48 |
August | 0.852319E+09 | 0.293034E+09 | 0.559285E+09 | 0.166932E+10 | 85779608.05 |
September | 0.730643E+09 | 0.251193E+09 | 0.479451E+09 | 0.135611E+10 | 0.143707E+09 |
October | 0.746094E+09 | 0.314849E+09 | 0.431244E+09 | 0.131083E+10 | 0.273928E+09 |
November | 0.639250E+09 | 0.326106E+09 | 0.313143E+09 | 0.873540E+09 | 0.609434E+09 |
December | 0.520086E+09 | 0.235587E+09 | 0.284498E+09 | 0.617887E+09 | 0.860616E+09 |
Annual Sum or Average | 0.929277E+10 | 0.397775E+10 | 0.531502E+10 | 0.152157E+11 | 0.512272E+10 |
Minimum of Months | 0.520086E+09 | 0.235587E+09 | 0.284498E+09 | 0.617887E+09 | 59856402.48 |
Maximum of Months | 0.945954E+09 | 0.410184E+09 | 0.586473E+09 | 0.181262E+10 | 0.989398E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.638461E+09 | 0.325107E+09 | 0.313354E+09 | 0.721368E+09 | 0.989398E+09 |
February | 0.642146E+09 | 0.310011E+09 | 0.332135E+09 | 0.776294E+09 | 0.753137E+09 |
March | 0.836308E+09 | 0.403329E+09 | 0.432980E+09 | 0.111695E+10 | 0.708667E+09 |
April | 0.888146E+09 | 0.401684E+09 | 0.486462E+09 | 0.137324E+10 | 0.418287E+09 |
May | 0.945954E+09 | 0.410184E+09 | 0.535770E+09 | 0.177889E+10 | 0.125299E+09 |
June | 0.928410E+09 | 0.368182E+09 | 0.560228E+09 | 0.181262E+10 | 94609742.59 |
July | 0.924957E+09 | 0.338484E+09 | 0.586473E+09 | 0.180870E+10 | 59856402.48 |
August | 0.852319E+09 | 0.293034E+09 | 0.559285E+09 | 0.166932E+10 | 85779608.05 |
September | 0.730643E+09 | 0.251193E+09 | 0.479451E+09 | 0.135611E+10 | 0.143707E+09 |
October | 0.746094E+09 | 0.314849E+09 | 0.431244E+09 | 0.131083E+10 | 0.273928E+09 |
November | 0.639250E+09 | 0.326106E+09 | 0.313143E+09 | 0.873540E+09 | 0.609434E+09 |
December | 0.520086E+09 | 0.235587E+09 | 0.284498E+09 | 0.617887E+09 | 0.860616E+09 |
Annual Sum or Average | 0.929277E+10 | 0.397775E+10 | 0.531502E+10 | 0.152157E+11 | 0.512272E+10 |
Minimum of Months | 0.520086E+09 | 0.235587E+09 | 0.284498E+09 | 0.617887E+09 | 59856402.48 |
Maximum of Months | 0.945954E+09 | 0.410184E+09 | 0.586473E+09 | 0.181262E+10 | 0.989398E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.638450E+09 | 0.325101E+09 | 0.313349E+09 | 0.721355E+09 | 0.989380E+09 |
February | 0.642135E+09 | 0.310006E+09 | 0.332129E+09 | 0.776280E+09 | 0.753124E+09 |
March | 0.836293E+09 | 0.403321E+09 | 0.432972E+09 | 0.111693E+10 | 0.708654E+09 |
April | 0.888130E+09 | 0.401677E+09 | 0.486453E+09 | 0.137321E+10 | 0.418280E+09 |
May | 0.945937E+09 | 0.410176E+09 | 0.535761E+09 | 0.177886E+10 | 0.125296E+09 |
June | 0.928393E+09 | 0.368175E+09 | 0.560218E+09 | 0.181259E+10 | 94608013.86 |
July | 0.924940E+09 | 0.338478E+09 | 0.586462E+09 | 0.180867E+10 | 59855308.77 |
August | 0.852304E+09 | 0.293029E+09 | 0.559275E+09 | 0.166929E+10 | 85778040.67 |
September | 0.730630E+09 | 0.251188E+09 | 0.479442E+09 | 0.135609E+10 | 0.143704E+09 |
October | 0.746080E+09 | 0.314843E+09 | 0.431237E+09 | 0.131080E+10 | 0.273923E+09 |
November | 0.639238E+09 | 0.326100E+09 | 0.313138E+09 | 0.873524E+09 | 0.609422E+09 |
December | 0.520076E+09 | 0.235583E+09 | 0.284493E+09 | 0.617876E+09 | 0.860600E+09 |
Annual Sum or Average | 0.929260E+10 | 0.397768E+10 | 0.531493E+10 | 0.152155E+11 | 0.512262E+10 |
Minimum of Months | 0.520076E+09 | 0.235583E+09 | 0.284493E+09 | 0.617876E+09 | 59855308.77 |
Maximum of Months | 0.945937E+09 | 0.410176E+09 | 0.586462E+09 | 0.181259E+10 | 0.989380E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.129053E+10 | 0.920368E+09 | 0.370159E+09 | 0.182435E+10 | 0.877959E+09 |
February | 0.105717E+10 | 0.684285E+09 | 0.372883E+09 | 0.152543E+10 | 0.685728E+09 |
March | 0.747233E+09 | 0.337225E+09 | 0.410008E+09 | 0.110668E+10 | 0.675433E+09 |
April | 0.535976E+09 | 0.125591E+09 | 0.410385E+09 | 0.882456E+09 | 0.418749E+09 |
May | 0.423176E+09 | 17984196.22 | 0.405192E+09 | 0.883365E+09 | 0.119606E+09 |
June | 0.404542E+09 | 3770670.32 | 0.400771E+09 | 0.873226E+09 | 95591703.47 |
July | 0.437605E+09 | 8043046.48 | 0.429562E+09 | 0.933824E+09 | 63617911.30 |
August | 0.514818E+09 | 61793137.02 | 0.453025E+09 | 0.110202E+10 | 98780825.48 |
September | 0.597768E+09 | 0.157536E+09 | 0.440232E+09 | 0.118125E+10 | 0.144340E+09 |
October | 0.958355E+09 | 0.499210E+09 | 0.459145E+09 | 0.173564E+10 | 0.277758E+09 |
November | 0.118023E+10 | 0.812596E+09 | 0.367630E+09 | 0.182223E+10 | 0.575413E+09 |
December | 0.126100E+10 | 0.905582E+09 | 0.355420E+09 | 0.185682E+10 | 0.791508E+09 |
Annual Sum or Average | 0.940840E+10 | 0.453399E+10 | 0.487441E+10 | 0.157273E+11 | 0.482449E+10 |
Minimum of Months | 0.404542E+09 | 3770670.32 | 0.355420E+09 | 0.873226E+09 | 63617911.30 |
Maximum of Months | 0.129053E+10 | 0.920368E+09 | 0.459145E+09 | 0.185682E+10 | 0.877959E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.129052E+10 | 0.920361E+09 | 0.370157E+09 | 0.182434E+10 | 0.877958E+09 |
February | 0.105716E+10 | 0.684280E+09 | 0.372881E+09 | 0.152542E+10 | 0.685728E+09 |
March | 0.747229E+09 | 0.337223E+09 | 0.410006E+09 | 0.110667E+10 | 0.675433E+09 |
April | 0.535973E+09 | 0.125590E+09 | 0.410383E+09 | 0.882451E+09 | 0.418749E+09 |
May | 0.423174E+09 | 17984064.43 | 0.405190E+09 | 0.883362E+09 | 0.119606E+09 |
June | 0.404540E+09 | 3770642.69 | 0.400769E+09 | 0.873223E+09 | 95591215.25 |
July | 0.437603E+09 | 8042987.54 | 0.429560E+09 | 0.933820E+09 | 63617485.32 |
August | 0.514816E+09 | 61792684.20 | 0.453023E+09 | 0.110202E+10 | 98780350.78 |
September | 0.597765E+09 | 0.157535E+09 | 0.440230E+09 | 0.118124E+10 | 0.144339E+09 |
October | 0.958349E+09 | 0.499207E+09 | 0.459142E+09 | 0.173563E+10 | 0.277758E+09 |
November | 0.118022E+10 | 0.812590E+09 | 0.367628E+09 | 0.182222E+10 | 0.575413E+09 |
December | 0.126099E+10 | 0.905576E+09 | 0.355418E+09 | 0.185680E+10 | 0.791507E+09 |
Annual Sum or Average | 0.940834E+10 | 0.453395E+10 | 0.487439E+10 | 0.157272E+11 | 0.482448E+10 |
Minimum of Months | 0.404540E+09 | 3770642.69 | 0.355418E+09 | 0.873223E+09 | 63617485.32 |
Maximum of Months | 0.129052E+10 | 0.920361E+09 | 0.459142E+09 | 0.185680E+10 | 0.877958E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.129053E+10 | 0.920368E+09 | 0.370159E+09 | 0.182435E+10 | 0.877959E+09 |
February | 0.105717E+10 | 0.684285E+09 | 0.372883E+09 | 0.152543E+10 | 0.685728E+09 |
March | 0.747233E+09 | 0.337225E+09 | 0.410008E+09 | 0.110668E+10 | 0.675433E+09 |
April | 0.535976E+09 | 0.125591E+09 | 0.410385E+09 | 0.882456E+09 | 0.418749E+09 |
May | 0.423176E+09 | 17984196.22 | 0.405192E+09 | 0.883365E+09 | 0.119606E+09 |
June | 0.404542E+09 | 3770670.32 | 0.400771E+09 | 0.873226E+09 | 95591703.47 |
July | 0.437605E+09 | 8043046.48 | 0.429562E+09 | 0.933824E+09 | 63617911.30 |
August | 0.514818E+09 | 61793137.02 | 0.453025E+09 | 0.110202E+10 | 98780825.48 |
September | 0.597768E+09 | 0.157536E+09 | 0.440232E+09 | 0.118125E+10 | 0.144340E+09 |
October | 0.958355E+09 | 0.499210E+09 | 0.459145E+09 | 0.173564E+10 | 0.277758E+09 |
November | 0.118023E+10 | 0.812596E+09 | 0.367630E+09 | 0.182223E+10 | 0.575413E+09 |
December | 0.126100E+10 | 0.905582E+09 | 0.355420E+09 | 0.185682E+10 | 0.791508E+09 |
Annual Sum or Average | 0.940840E+10 | 0.453399E+10 | 0.487441E+10 | 0.157273E+11 | 0.482449E+10 |
Minimum of Months | 0.404542E+09 | 3770670.32 | 0.355420E+09 | 0.873226E+09 | 63617911.30 |
Maximum of Months | 0.129053E+10 | 0.920368E+09 | 0.459145E+09 | 0.185682E+10 | 0.877959E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.129052E+10 | 0.920361E+09 | 0.370157E+09 | 0.182434E+10 | 0.877958E+09 |
February | 0.105716E+10 | 0.684280E+09 | 0.372881E+09 | 0.152542E+10 | 0.685728E+09 |
March | 0.747229E+09 | 0.337223E+09 | 0.410006E+09 | 0.110667E+10 | 0.675433E+09 |
April | 0.535973E+09 | 0.125590E+09 | 0.410383E+09 | 0.882451E+09 | 0.418749E+09 |
May | 0.423174E+09 | 17984064.43 | 0.405190E+09 | 0.883362E+09 | 0.119606E+09 |
June | 0.404540E+09 | 3770642.69 | 0.400769E+09 | 0.873223E+09 | 95591215.25 |
July | 0.437603E+09 | 8042987.54 | 0.429560E+09 | 0.933820E+09 | 63617485.32 |
August | 0.514816E+09 | 61792684.20 | 0.453023E+09 | 0.110202E+10 | 98780350.78 |
September | 0.597765E+09 | 0.157535E+09 | 0.440230E+09 | 0.118124E+10 | 0.144339E+09 |
October | 0.958349E+09 | 0.499207E+09 | 0.459142E+09 | 0.173563E+10 | 0.277758E+09 |
November | 0.118022E+10 | 0.812590E+09 | 0.367628E+09 | 0.182222E+10 | 0.575413E+09 |
December | 0.126099E+10 | 0.905576E+09 | 0.355418E+09 | 0.185680E+10 | 0.791507E+09 |
Annual Sum or Average | 0.940834E+10 | 0.453395E+10 | 0.487439E+10 | 0.157272E+11 | 0.482448E+10 |
Minimum of Months | 0.404540E+09 | 3770642.69 | 0.355418E+09 | 0.873223E+09 | 63617485.32 |
Maximum of Months | 0.129052E+10 | 0.920361E+09 | 0.459142E+09 | 0.185680E+10 | 0.877958E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.129047E+10 | 0.920327E+09 | 0.370144E+09 | 0.182427E+10 | 0.877923E+09 |
February | 0.105712E+10 | 0.684255E+09 | 0.372867E+09 | 0.152537E+10 | 0.685700E+09 |
March | 0.747201E+09 | 0.337211E+09 | 0.409990E+09 | 0.110663E+10 | 0.675406E+09 |
April | 0.535953E+09 | 0.125586E+09 | 0.410367E+09 | 0.882418E+09 | 0.418732E+09 |
May | 0.423158E+09 | 17983405.49 | 0.405175E+09 | 0.883327E+09 | 0.119601E+09 |
June | 0.404524E+09 | 3770504.53 | 0.400754E+09 | 0.873189E+09 | 95587606.60 |
July | 0.437587E+09 | 8042692.84 | 0.429544E+09 | 0.933784E+09 | 63615134.24 |
August | 0.514796E+09 | 61790420.09 | 0.453006E+09 | 0.110198E+10 | 98776606.82 |
September | 0.597743E+09 | 0.157529E+09 | 0.440213E+09 | 0.118120E+10 | 0.144334E+09 |
October | 0.958314E+09 | 0.499188E+09 | 0.459125E+09 | 0.173556E+10 | 0.277747E+09 |
November | 0.118017E+10 | 0.812560E+09 | 0.367614E+09 | 0.182215E+10 | 0.575390E+09 |
December | 0.126095E+10 | 0.905542E+09 | 0.355404E+09 | 0.185673E+10 | 0.791476E+09 |
Annual Sum or Average | 0.940799E+10 | 0.453379E+10 | 0.487420E+10 | 0.157266E+11 | 0.482429E+10 |
Minimum of Months | 0.404524E+09 | 3770504.53 | 0.355404E+09 | 0.873189E+09 | 63615134.24 |
Maximum of Months | 0.129047E+10 | 0.920327E+09 | 0.459125E+09 | 0.185673E+10 | 0.877923E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.679104E+09 | 0.367222E+09 | 0.311882E+09 | 0.822446E+09 | 0.111501E+10 |
February | 0.694487E+09 | 0.351506E+09 | 0.342981E+09 | 0.871455E+09 | 0.892566E+09 |
March | 0.757826E+09 | 0.335471E+09 | 0.422355E+09 | 0.990017E+09 | 0.875424E+09 |
April | 0.910877E+09 | 0.419021E+09 | 0.491856E+09 | 0.137625E+10 | 0.555699E+09 |
May | 0.782752E+09 | 0.254983E+09 | 0.527769E+09 | 0.148999E+10 | 0.173855E+09 |
June | 0.841498E+09 | 0.295069E+09 | 0.546429E+09 | 0.162761E+10 | 0.154939E+09 |
July | 0.793735E+09 | 0.220170E+09 | 0.573565E+09 | 0.152132E+10 | 0.126253E+09 |
August | 0.802566E+09 | 0.245676E+09 | 0.556890E+09 | 0.152926E+10 | 0.184637E+09 |
September | 0.715188E+09 | 0.245344E+09 | 0.469844E+09 | 0.131679E+10 | 0.194659E+09 |
October | 0.756612E+09 | 0.326924E+09 | 0.429688E+09 | 0.132094E+10 | 0.362469E+09 |
November | 0.627587E+09 | 0.315400E+09 | 0.312187E+09 | 0.871284E+09 | 0.767622E+09 |
December | 0.623808E+09 | 0.331732E+09 | 0.292075E+09 | 0.780256E+09 | 0.106329E+10 |
Annual Sum or Average | 0.898604E+10 | 0.370852E+10 | 0.527752E+10 | 0.145176E+11 | 0.646642E+10 |
Minimum of Months | 0.623808E+09 | 0.220170E+09 | 0.292075E+09 | 0.780256E+09 | 0.126253E+09 |
Maximum of Months | 0.910877E+09 | 0.419021E+09 | 0.573565E+09 | 0.162761E+10 | 0.111501E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.679104E+09 | 0.367222E+09 | 0.311882E+09 | 0.822446E+09 | 0.111501E+10 |
February | 0.694487E+09 | 0.351506E+09 | 0.342981E+09 | 0.871455E+09 | 0.892566E+09 |
March | 0.757826E+09 | 0.335471E+09 | 0.422355E+09 | 0.990017E+09 | 0.875424E+09 |
April | 0.910877E+09 | 0.419021E+09 | 0.491856E+09 | 0.137625E+10 | 0.555699E+09 |
May | 0.782752E+09 | 0.254983E+09 | 0.527769E+09 | 0.148999E+10 | 0.173855E+09 |
June | 0.841498E+09 | 0.295069E+09 | 0.546429E+09 | 0.162761E+10 | 0.154939E+09 |
July | 0.793735E+09 | 0.220170E+09 | 0.573565E+09 | 0.152132E+10 | 0.126253E+09 |
August | 0.802566E+09 | 0.245676E+09 | 0.556890E+09 | 0.152926E+10 | 0.184637E+09 |
September | 0.715188E+09 | 0.245344E+09 | 0.469844E+09 | 0.131679E+10 | 0.194659E+09 |
October | 0.756612E+09 | 0.326924E+09 | 0.429688E+09 | 0.132094E+10 | 0.362469E+09 |
November | 0.627587E+09 | 0.315400E+09 | 0.312187E+09 | 0.871284E+09 | 0.767622E+09 |
December | 0.623808E+09 | 0.331732E+09 | 0.292075E+09 | 0.780256E+09 | 0.106329E+10 |
Annual Sum or Average | 0.898604E+10 | 0.370852E+10 | 0.527752E+10 | 0.145176E+11 | 0.646642E+10 |
Minimum of Months | 0.623808E+09 | 0.220170E+09 | 0.292075E+09 | 0.780256E+09 | 0.126253E+09 |
Maximum of Months | 0.910877E+09 | 0.419021E+09 | 0.573565E+09 | 0.162761E+10 | 0.111501E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.679091E+09 | 0.367215E+09 | 0.311876E+09 | 0.822431E+09 | 0.111499E+10 |
February | 0.694475E+09 | 0.351500E+09 | 0.342975E+09 | 0.871439E+09 | 0.892549E+09 |
March | 0.757812E+09 | 0.335464E+09 | 0.422348E+09 | 0.989999E+09 | 0.875408E+09 |
April | 0.910860E+09 | 0.419013E+09 | 0.491847E+09 | 0.137622E+10 | 0.555688E+09 |
May | 0.782738E+09 | 0.254978E+09 | 0.527759E+09 | 0.148997E+10 | 0.173852E+09 |
June | 0.841483E+09 | 0.295063E+09 | 0.546419E+09 | 0.162758E+10 | 0.154936E+09 |
July | 0.793720E+09 | 0.220166E+09 | 0.573554E+09 | 0.152130E+10 | 0.126250E+09 |
August | 0.802552E+09 | 0.245672E+09 | 0.556880E+09 | 0.152923E+10 | 0.184634E+09 |
September | 0.715175E+09 | 0.245339E+09 | 0.469836E+09 | 0.131677E+10 | 0.194656E+09 |
October | 0.756598E+09 | 0.326918E+09 | 0.429680E+09 | 0.132091E+10 | 0.362463E+09 |
November | 0.627576E+09 | 0.315394E+09 | 0.312181E+09 | 0.871268E+09 | 0.767608E+09 |
December | 0.623796E+09 | 0.331726E+09 | 0.292070E+09 | 0.780242E+09 | 0.106327E+10 |
Annual Sum or Average | 0.898588E+10 | 0.370845E+10 | 0.527743E+10 | 0.145174E+11 | 0.646630E+10 |
Minimum of Months | 0.623796E+09 | 0.220166E+09 | 0.292070E+09 | 0.780242E+09 | 0.126250E+09 |
Maximum of Months | 0.910860E+09 | 0.419013E+09 | 0.573554E+09 | 0.162758E+10 | 0.111499E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.111635E+10 | 0.00 | 0.111635E+10 | 0.787268E+09 | 0.439925E+10 |
February | 0.118957E+10 | 0.00 | 0.118957E+10 | 0.964611E+09 | 0.334717E+10 |
March | 0.152787E+10 | 0.00 | 0.152787E+10 | 0.154939E+10 | 0.319606E+10 |
April | 0.174505E+10 | 7162306.50 | 0.173789E+10 | 0.238773E+10 | 0.193656E+10 |
May | 0.204249E+10 | 74709672.45 | 0.196778E+10 | 0.422360E+10 | 0.574348E+09 |
June | 0.224782E+10 | 0.155644E+09 | 0.209218E+10 | 0.484376E+10 | 0.479434E+09 |
July | 0.225408E+10 | 85876258.80 | 0.216820E+10 | 0.481554E+10 | 0.327610E+09 |
August | 0.201857E+10 | 15876296.36 | 0.200269E+10 | 0.436022E+10 | 0.459679E+09 |
September | 0.168734E+10 | 129958.71 | 0.168721E+10 | 0.334174E+10 | 0.635404E+09 |
October | 0.151514E+10 | 0.00 | 0.151514E+10 | 0.277708E+10 | 0.124458E+10 |
November | 0.111313E+10 | 0.00 | 0.111313E+10 | 0.119332E+10 | 0.273684E+10 |
December | 0.103778E+10 | 0.00 | 0.103778E+10 | 0.854705E+09 | 0.377150E+10 |
Annual Sum or Average | 0.194952E+11 | 0.339399E+09 | 0.191558E+11 | 0.320990E+11 | 0.231084E+11 |
Minimum of Months | 0.103778E+10 | 0.00 | 0.103778E+10 | 0.787268E+09 | 0.327610E+09 |
Maximum of Months | 0.225408E+10 | 0.155644E+09 | 0.216820E+10 | 0.484376E+10 | 0.439925E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.191536E+10 | 0.975310E+09 | 0.940054E+09 | 0.220709E+10 | 0.275498E+10 |
February | 0.192642E+10 | 0.930024E+09 | 0.996395E+09 | 0.236048E+10 | 0.210951E+10 |
March | 0.250890E+10 | 0.120997E+10 | 0.129893E+10 | 0.334774E+10 | 0.203383E+10 |
April | 0.266441E+10 | 0.120504E+10 | 0.145937E+10 | 0.407467E+10 | 0.128999E+10 |
May | 0.283783E+10 | 0.123054E+10 | 0.160729E+10 | 0.528348E+10 | 0.403450E+09 |
June | 0.278520E+10 | 0.110453E+10 | 0.168067E+10 | 0.538859E+10 | 0.333404E+09 |
July | 0.277484E+10 | 0.101544E+10 | 0.175940E+10 | 0.537211E+10 | 0.229001E+09 |
August | 0.255693E+10 | 0.879093E+09 | 0.167784E+10 | 0.495894E+10 | 0.321015E+09 |
September | 0.219191E+10 | 0.753571E+09 | 0.143834E+10 | 0.403709E+10 | 0.439605E+09 |
October | 0.223826E+10 | 0.944538E+09 | 0.129372E+10 | 0.389826E+10 | 0.827550E+09 |
November | 0.191773E+10 | 0.978309E+09 | 0.939421E+09 | 0.262518E+10 | 0.174564E+10 |
December | 0.156024E+10 | 0.706755E+09 | 0.853486E+09 | 0.188971E+10 | 0.240581E+10 |
Annual Sum or Average | 0.278780E+11 | 0.119331E+11 | 0.159449E+11 | 0.454433E+11 | 0.148938E+11 |
Minimum of Months | 0.156024E+10 | 0.706755E+09 | 0.853486E+09 | 0.188971E+10 | 0.229001E+09 |
Maximum of Months | 0.283783E+10 | 0.123054E+10 | 0.175940E+10 | 0.538859E+10 | 0.275498E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.645276E+10 | 0.460194E+10 | 0.185082E+10 | 0.904264E+10 | 0.431028E+10 |
February | 0.528594E+10 | 0.342150E+10 | 0.186444E+10 | 0.757862E+10 | 0.333709E+10 |
March | 0.373623E+10 | 0.168616E+10 | 0.205006E+10 | 0.551450E+10 | 0.324369E+10 |
April | 0.267991E+10 | 0.627970E+09 | 0.205194E+10 | 0.440876E+10 | 0.205322E+10 |
May | 0.211590E+10 | 89922872.05 | 0.202598E+10 | 0.442181E+10 | 0.598691E+09 |
June | 0.202273E+10 | 18853748.06 | 0.200387E+10 | 0.438548E+10 | 0.491633E+09 |
July | 0.218805E+10 | 40216078.06 | 0.214783E+10 | 0.470457E+10 | 0.320626E+09 |
August | 0.257412E+10 | 0.308972E+09 | 0.226515E+10 | 0.553595E+10 | 0.498782E+09 |
September | 0.298889E+10 | 0.787698E+09 | 0.220119E+10 | 0.588479E+10 | 0.710375E+09 |
October | 0.479186E+10 | 0.249610E+10 | 0.229575E+10 | 0.862303E+10 | 0.138736E+10 |
November | 0.590124E+10 | 0.406306E+10 | 0.183817E+10 | 0.906031E+10 | 0.281637E+10 |
December | 0.630513E+10 | 0.452801E+10 | 0.177712E+10 | 0.924092E+10 | 0.382745E+10 |
Annual Sum or Average | 0.470427E+11 | 0.226704E+11 | 0.243723E+11 | 0.784014E+11 | 0.235956E+11 |
Minimum of Months | 0.202273E+10 | 18853748.06 | 0.177712E+10 | 0.438548E+10 | 0.320626E+09 |
Maximum of Months | 0.645276E+10 | 0.460194E+10 | 0.229575E+10 | 0.924092E+10 | 0.431028E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.203729E+10 | 0.110165E+10 | 0.935636E+09 | 0.254380E+10 | 0.298098E+10 |
February | 0.208344E+10 | 0.105451E+10 | 0.102893E+10 | 0.270308E+10 | 0.231334E+10 |
March | 0.227345E+10 | 0.100640E+10 | 0.126705E+10 | 0.306895E+10 | 0.222931E+10 |
April | 0.273260E+10 | 0.125705E+10 | 0.147555E+10 | 0.422356E+10 | 0.144055E+10 |
May | 0.234823E+10 | 0.764941E+09 | 0.158329E+10 | 0.450260E+10 | 0.472226E+09 |
June | 0.252447E+10 | 0.885198E+09 | 0.163927E+10 | 0.493945E+10 | 0.405355E+09 |
July | 0.238118E+10 | 0.660502E+09 | 0.172068E+10 | 0.466783E+10 | 0.287709E+09 |
August | 0.240767E+10 | 0.737022E+09 | 0.167065E+10 | 0.472389E+10 | 0.399109E+09 |
September | 0.214554E+10 | 0.736024E+09 | 0.140952E+10 | 0.398343E+10 | 0.508277E+09 |
October | 0.226981E+10 | 0.980761E+09 | 0.128905E+10 | 0.402671E+10 | 0.946052E+09 |
November | 0.188274E+10 | 0.946191E+09 | 0.936552E+09 | 0.271709E+10 | 0.194004E+10 |
December | 0.187140E+10 | 0.995187E+09 | 0.876217E+09 | 0.247380E+10 | 0.260036E+10 |
Annual Sum or Average | 0.269578E+11 | 0.111254E+11 | 0.158324E+11 | 0.445742E+11 | 0.165233E+11 |
Minimum of Months | 0.187140E+10 | 0.660502E+09 | 0.876217E+09 | 0.247380E+10 | 0.287709E+09 |
Maximum of Months | 0.273260E+10 | 0.125705E+10 | 0.172068E+10 | 0.493945E+10 | 0.298098E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.111635E+10 | 0.00 | 0.111635E+10 | 0.866551E+09 | 0.402982E+10 |
February | 0.118957E+10 | 0.00 | 0.118957E+10 | 0.101943E+10 | 0.307984E+10 |
March | 0.152787E+10 | 0.00 | 0.152787E+10 | 0.159070E+10 | 0.299619E+10 |
April | 0.174505E+10 | 7162306.50 | 0.173789E+10 | 0.237902E+10 | 0.188412E+10 |
May | 0.204249E+10 | 74709672.45 | 0.196778E+10 | 0.415405E+10 | 0.607128E+09 |
June | 0.224782E+10 | 0.155644E+09 | 0.209218E+10 | 0.476720E+10 | 0.514104E+09 |
July | 0.225408E+10 | 85876258.80 | 0.216820E+10 | 0.472508E+10 | 0.364535E+09 |
August | 0.201857E+10 | 15876296.36 | 0.200269E+10 | 0.428808E+10 | 0.488797E+09 |
September | 0.168734E+10 | 129958.71 | 0.168721E+10 | 0.327629E+10 | 0.663694E+09 |
October | 0.151514E+10 | 0.00 | 0.151514E+10 | 0.274595E+10 | 0.122420E+10 |
November | 0.111313E+10 | 0.00 | 0.111313E+10 | 0.123652E+10 | 0.254819E+10 |
December | 0.103778E+10 | 0.00 | 0.103778E+10 | 0.913261E+09 | 0.346790E+10 |
Annual Sum or Average | 0.194952E+11 | 0.339399E+09 | 0.191558E+11 | 0.319621E+11 | 0.218685E+11 |
Minimum of Months | 0.103778E+10 | 0.00 | 0.103778E+10 | 0.866551E+09 | 0.364535E+09 |
Maximum of Months | 0.225408E+10 | 0.155644E+09 | 0.216820E+10 | 0.476720E+10 | 0.402982E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.191536E+10 | 0.975310E+09 | 0.940054E+09 | 0.229053E+10 | 0.254201E+10 |
February | 0.192642E+10 | 0.930024E+09 | 0.996395E+09 | 0.241332E+10 | 0.196037E+10 |
March | 0.250890E+10 | 0.120997E+10 | 0.129893E+10 | 0.336841E+10 | 0.193399E+10 |
April | 0.266441E+10 | 0.120504E+10 | 0.145937E+10 | 0.405888E+10 | 0.127084E+10 |
May | 0.283783E+10 | 0.123054E+10 | 0.160729E+10 | 0.522983E+10 | 0.425281E+09 |
June | 0.278520E+10 | 0.110453E+10 | 0.168067E+10 | 0.533314E+10 | 0.358044E+09 |
July | 0.277484E+10 | 0.101544E+10 | 0.175940E+10 | 0.530922E+10 | 0.253832E+09 |
August | 0.255693E+10 | 0.879093E+09 | 0.167784E+10 | 0.490541E+10 | 0.340691E+09 |
September | 0.219191E+10 | 0.753571E+09 | 0.143834E+10 | 0.399069E+10 | 0.458994E+09 |
October | 0.223826E+10 | 0.944538E+09 | 0.129372E+10 | 0.387088E+10 | 0.819931E+09 |
November | 0.191773E+10 | 0.978309E+09 | 0.939421E+09 | 0.265317E+10 | 0.165671E+10 |
December | 0.156024E+10 | 0.706755E+09 | 0.853486E+09 | 0.194049E+10 | 0.223879E+10 |
Annual Sum or Average | 0.278780E+11 | 0.119331E+11 | 0.159449E+11 | 0.453640E+11 | 0.142595E+11 |
Minimum of Months | 0.156024E+10 | 0.706755E+09 | 0.853486E+09 | 0.194049E+10 | 0.253832E+09 |
Maximum of Months | 0.283783E+10 | 0.123054E+10 | 0.175940E+10 | 0.533314E+10 | 0.254201E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.645276E+10 | 0.460194E+10 | 0.185082E+10 | 0.912220E+10 | 0.403156E+10 |
February | 0.528594E+10 | 0.342150E+10 | 0.186444E+10 | 0.763683E+10 | 0.313111E+10 |
March | 0.373623E+10 | 0.168616E+10 | 0.205006E+10 | 0.553727E+10 | 0.307770E+10 |
April | 0.267991E+10 | 0.627970E+09 | 0.205194E+10 | 0.438539E+10 | 0.201093E+10 |
May | 0.211590E+10 | 89922872.05 | 0.202598E+10 | 0.435173E+10 | 0.632373E+09 |
June | 0.202273E+10 | 18853748.06 | 0.200387E+10 | 0.431211E+10 | 0.528963E+09 |
July | 0.218805E+10 | 40216078.06 | 0.214783E+10 | 0.461174E+10 | 0.356953E+09 |
August | 0.257412E+10 | 0.308972E+09 | 0.226515E+10 | 0.546063E+10 | 0.530579E+09 |
September | 0.298889E+10 | 0.787698E+09 | 0.220119E+10 | 0.581768E+10 | 0.740574E+09 |
October | 0.479186E+10 | 0.249610E+10 | 0.229575E+10 | 0.857325E+10 | 0.138310E+10 |
November | 0.590124E+10 | 0.406306E+10 | 0.183817E+10 | 0.907352E+10 | 0.270728E+10 |
December | 0.630513E+10 | 0.452801E+10 | 0.177712E+10 | 0.928915E+10 | 0.360078E+10 |
Annual Sum or Average | 0.470427E+11 | 0.226704E+11 | 0.243723E+11 | 0.781715E+11 | 0.227319E+11 |
Minimum of Months | 0.202273E+10 | 18853748.06 | 0.177712E+10 | 0.431211E+10 | 0.356953E+09 |
Maximum of Months | 0.645276E+10 | 0.460194E+10 | 0.229575E+10 | 0.928915E+10 | 0.403156E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.203729E+10 | 0.110165E+10 | 0.935636E+09 | 0.258644E+10 | 0.277807E+10 |
February | 0.208344E+10 | 0.105451E+10 | 0.102893E+10 | 0.272846E+10 | 0.216638E+10 |
March | 0.227345E+10 | 0.100640E+10 | 0.126705E+10 | 0.308158E+10 | 0.211511E+10 |
April | 0.273260E+10 | 0.125705E+10 | 0.147555E+10 | 0.420340E+10 | 0.141148E+10 |
May | 0.234823E+10 | 0.764941E+09 | 0.158329E+10 | 0.445807E+10 | 0.489515E+09 |
June | 0.252447E+10 | 0.885198E+09 | 0.163927E+10 | 0.489041E+10 | 0.423720E+09 |
July | 0.238118E+10 | 0.660502E+09 | 0.172068E+10 | 0.461230E+10 | 0.304613E+09 |
August | 0.240767E+10 | 0.737022E+09 | 0.167065E+10 | 0.467633E+10 | 0.415078E+09 |
September | 0.214554E+10 | 0.736024E+09 | 0.140952E+10 | 0.394396E+10 | 0.522755E+09 |
October | 0.226981E+10 | 0.980761E+09 | 0.128905E+10 | 0.400137E+10 | 0.935806E+09 |
November | 0.188274E+10 | 0.946191E+09 | 0.936552E+09 | 0.273241E+10 | 0.183919E+10 |
December | 0.187140E+10 | 0.995187E+09 | 0.876217E+09 | 0.250166E+10 | 0.242937E+10 |
Annual Sum or Average | 0.269578E+11 | 0.111254E+11 | 0.158324E+11 | 0.444164E+11 | 0.158311E+11 |
Minimum of Months | 0.187140E+10 | 0.660502E+09 | 0.876217E+09 | 0.250166E+10 | 0.304613E+09 |
Maximum of Months | 0.273260E+10 | 0.125705E+10 | 0.172068E+10 | 0.489041E+10 | 0.277807E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 251.33 | 1828.24 | 416.79 | 0.00 | 416.79 | 0.00 | 0.00 |
February | 358.24 | 1552.14 | 491.71 | 0.00 | 491.71 | 0.00 | 0.00 |
March | 542.22 | 1317.25 | 570.43 | 0.00 | 570.43 | 0.00 | 0.00 |
April | 901.41 | 785.92 | 673.24 | 2.76 | 670.47 | 0.00 | 0.00 |
May | 1573.66 | 214.23 | 762.57 | 27.89 | 734.67 | 0.00 | 0.00 |
June | 1864.52 | 177.37 | 867.20 | 60.05 | 807.15 | 0.00 | 0.00 |
July | 1786.78 | 119.47 | 841.56 | 32.06 | 809.50 | 0.00 | 0.00 |
August | 1608.85 | 172.20 | 753.63 | 5.93 | 747.71 | 0.00 | 0.00 |
September | 1280.44 | 257.83 | 650.97 | 0.05 | 650.92 | 0.00 | 0.00 |
October | 1019.69 | 494.53 | 565.68 | 0.00 | 565.68 | 0.00 | 0.00 |
November | 424.97 | 1179.37 | 429.44 | 0.00 | 429.44 | 0.00 | 0.00 |
December | 275.34 | 1608.64 | 387.46 | 0.00 | 387.46 | 0.00 | 0.00 |
Annual Sum or Average | 994.42 | 805.11 | 618.18 | 10.76 | 607.42 | 0.00 | 0.00 |
Minimum of Months | 251.33 | 119.47 | 387.46 | 0.00 | 387.46 | 0.00 | 0.00 |
Maximum of Months | 1864.52 | 1828.24 | 867.20 | 60.05 | 809.50 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 807.98 | 1108.19 | 715.12 | 364.14 | 350.98 | 0.00 | 0.00 |
February | 962.66 | 933.94 | 796.31 | 384.44 | 411.87 | 0.00 | 0.00 |
March | 1251.06 | 793.75 | 936.72 | 451.75 | 484.97 | 0.00 | 0.00 |
April | 1589.39 | 484.13 | 1027.94 | 464.91 | 563.03 | 0.00 | 0.00 |
May | 1992.47 | 140.34 | 1059.53 | 459.43 | 600.10 | 0.00 | 0.00 |
June | 2097.93 | 109.50 | 1074.54 | 426.13 | 648.41 | 0.00 | 0.00 |
July | 2025.86 | 67.04 | 1036.01 | 379.12 | 656.89 | 0.00 | 0.00 |
August | 1869.75 | 96.08 | 954.65 | 328.22 | 626.44 | 0.00 | 0.00 |
September | 1569.57 | 166.33 | 845.65 | 290.73 | 554.92 | 0.00 | 0.00 |
October | 1468.21 | 306.82 | 835.67 | 352.65 | 483.02 | 0.00 | 0.00 |
November | 1011.04 | 705.36 | 739.87 | 377.44 | 362.43 | 0.00 | 0.00 |
December | 692.07 | 963.95 | 582.53 | 263.87 | 318.66 | 0.00 | 0.00 |
Annual Sum or Average | 1447.46 | 487.32 | 884.01 | 378.40 | 505.61 | 0.00 | 0.00 |
Minimum of Months | 692.07 | 67.04 | 582.53 | 263.87 | 318.66 | 0.00 | 0.00 |
Maximum of Months | 2097.93 | 1108.19 | 1074.54 | 464.91 | 656.89 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3405.64 | 1638.95 | 2409.11 | 1718.11 | 691.00 | 0.00 | 0.00 |
February | 3152.73 | 1417.25 | 2184.93 | 1414.26 | 770.67 | 0.00 | 0.00 |
March | 2065.91 | 1260.88 | 1394.91 | 629.52 | 765.39 | 0.00 | 0.00 |
April | 1702.25 | 807.77 | 1033.89 | 242.26 | 791.63 | 0.00 | 0.00 |
May | 1649.04 | 223.28 | 789.97 | 33.57 | 756.40 | 0.00 | 0.00 |
June | 1684.45 | 184.40 | 780.36 | 7.27 | 773.08 | 0.00 | 0.00 |
July | 1743.23 | 118.76 | 816.91 | 15.01 | 801.89 | 0.00 | 0.00 |
August | 2057.22 | 184.40 | 961.05 | 115.35 | 845.69 | 0.00 | 0.00 |
September | 2278.61 | 278.43 | 1153.09 | 303.89 | 849.20 | 0.00 | 0.00 |
October | 3240.03 | 518.51 | 1789.02 | 931.91 | 857.12 | 0.00 | 0.00 |
November | 3515.07 | 1109.97 | 2276.64 | 1567.49 | 709.16 | 0.00 | 0.00 |
December | 3466.24 | 1477.56 | 2353.99 | 1690.51 | 663.49 | 0.00 | 0.00 |
Annual Sum or Average | 2493.52 | 764.91 | 1491.68 | 718.85 | 772.82 | 0.00 | 0.00 |
Minimum of Months | 1649.04 | 118.76 | 780.36 | 7.27 | 663.49 | 0.00 | 0.00 |
Maximum of Months | 3515.07 | 1638.95 | 2409.11 | 1718.11 | 857.12 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 921.19 | 1248.88 | 760.64 | 411.31 | 349.33 | 0.00 | 0.00 |
February | 1080.67 | 1106.85 | 861.21 | 435.89 | 425.32 | 0.00 | 0.00 |
March | 1108.88 | 980.53 | 848.81 | 375.75 | 473.07 | 0.00 | 0.00 |
April | 1592.87 | 643.17 | 1054.25 | 484.97 | 569.27 | 0.00 | 0.00 |
May | 1668.89 | 194.73 | 876.73 | 285.60 | 591.14 | 0.00 | 0.00 |
June | 1883.79 | 179.33 | 973.95 | 341.51 | 632.44 | 0.00 | 0.00 |
July | 1703.98 | 141.41 | 889.03 | 246.60 | 642.43 | 0.00 | 0.00 |
August | 1712.87 | 206.81 | 898.93 | 275.17 | 623.75 | 0.00 | 0.00 |
September | 1524.05 | 225.30 | 827.76 | 283.96 | 543.80 | 0.00 | 0.00 |
October | 1479.54 | 405.99 | 847.45 | 366.18 | 481.28 | 0.00 | 0.00 |
November | 1008.42 | 888.45 | 726.37 | 365.04 | 361.33 | 0.00 | 0.00 |
December | 873.94 | 1190.95 | 698.71 | 371.56 | 327.14 | 0.00 | 0.00 |
Annual Sum or Average | 1381.04 | 615.14 | 854.83 | 352.79 | 502.04 | 0.00 | 0.00 |
Minimum of Months | 873.94 | 141.41 | 698.71 | 246.60 | 327.14 | 0.00 | 0.00 |
Maximum of Months | 1883.79 | 1248.88 | 1054.25 | 484.97 | 642.43 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 293.93 | 1642.49 | 416.80 | 0.00 | 416.80 | 0.00 | 0.00 |
February | 398.73 | 1383.59 | 491.72 | 0.00 | 491.72 | 0.00 | 0.00 |
March | 578.48 | 1193.27 | 570.44 | 0.00 | 570.44 | 0.00 | 0.00 |
April | 921.19 | 747.13 | 673.25 | 2.76 | 670.48 | 0.00 | 0.00 |
May | 1576.91 | 214.44 | 762.58 | 27.89 | 734.69 | 0.00 | 0.00 |
June | 1868.73 | 184.97 | 867.22 | 60.05 | 807.17 | 0.00 | 0.00 |
July | 1797.92 | 122.32 | 841.58 | 32.06 | 809.51 | 0.00 | 0.00 |
August | 1627.92 | 171.62 | 753.65 | 5.93 | 747.72 | 0.00 | 0.00 |
September | 1289.25 | 245.14 | 650.98 | 0.05 | 650.93 | 0.00 | 0.00 |
October | 1036.84 | 464.67 | 565.69 | 0.00 | 565.69 | 0.00 | 0.00 |
November | 460.39 | 1055.88 | 429.45 | 0.00 | 429.45 | 0.00 | 0.00 |
December | 319.11 | 1408.12 | 387.46 | 0.00 | 387.46 | 0.00 | 0.00 |
Annual Sum or Average | 1017.85 | 732.76 | 618.19 | 10.76 | 607.43 | 0.00 | 0.00 |
Minimum of Months | 293.93 | 122.32 | 387.46 | 0.00 | 387.46 | 0.00 | 0.00 |
Maximum of Months | 1868.73 | 1642.49 | 867.22 | 60.05 | 809.51 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 824.03 | 1028.59 | 715.11 | 364.14 | 350.98 | 0.00 | 0.00 |
February | 975.73 | 871.99 | 796.30 | 384.43 | 411.87 | 0.00 | 0.00 |
March | 1249.90 | 759.35 | 936.72 | 451.75 | 484.96 | 0.00 | 0.00 |
April | 1572.02 | 497.68 | 1027.94 | 464.91 | 563.03 | 0.00 | 0.00 |
May | 1972.62 | 150.63 | 1059.53 | 459.43 | 600.10 | 0.00 | 0.00 |
June | 2078.93 | 128.63 | 1074.54 | 426.13 | 648.41 | 0.00 | 0.00 |
July | 2005.72 | 85.50 | 1036.01 | 379.12 | 656.88 | 0.00 | 0.00 |
August | 1851.46 | 119.85 | 954.65 | 328.22 | 626.43 | 0.00 | 0.00 |
September | 1557.52 | 169.60 | 845.64 | 290.73 | 554.91 | 0.00 | 0.00 |
October | 1455.45 | 308.97 | 835.67 | 352.65 | 483.02 | 0.00 | 0.00 |
November | 1012.80 | 673.47 | 739.86 | 377.43 | 362.43 | 0.00 | 0.00 |
December | 705.54 | 898.23 | 582.53 | 263.87 | 318.66 | 0.00 | 0.00 |
Annual Sum or Average | 1441.00 | 472.28 | 884.01 | 378.40 | 505.61 | 0.00 | 0.00 |
Minimum of Months | 705.54 | 85.50 | 582.53 | 263.87 | 318.66 | 0.00 | 0.00 |
Maximum of Months | 2078.93 | 1028.59 | 1074.54 | 464.91 | 656.88 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3376.14 | 1609.27 | 2409.18 | 1718.17 | 691.02 | 0.00 | 0.00 |
February | 3132.70 | 1379.42 | 2184.99 | 1414.31 | 770.68 | 0.00 | 0.00 |
March | 2058.88 | 1211.05 | 1394.95 | 629.54 | 765.41 | 0.00 | 0.00 |
April | 1700.91 | 792.14 | 1033.92 | 242.27 | 791.64 | 0.00 | 0.00 |
May | 1650.91 | 223.53 | 789.99 | 33.57 | 756.41 | 0.00 | 0.00 |
June | 1691.93 | 189.67 | 780.37 | 7.27 | 773.10 | 0.00 | 0.00 |
July | 1756.49 | 119.71 | 816.92 | 15.01 | 801.91 | 0.00 | 0.00 |
August | 2066.89 | 186.22 | 961.07 | 115.36 | 845.71 | 0.00 | 0.00 |
September | 2270.37 | 274.06 | 1153.12 | 303.90 | 849.22 | 0.00 | 0.00 |
October | 3219.47 | 517.98 | 1789.07 | 931.94 | 857.14 | 0.00 | 0.00 |
November | 3495.49 | 1086.56 | 2276.71 | 1567.54 | 709.17 | 0.00 | 0.00 |
December | 3450.17 | 1429.01 | 2354.07 | 1690.56 | 663.50 | 0.00 | 0.00 |
Annual Sum or Average | 2486.09 | 748.21 | 1491.72 | 718.87 | 772.84 | 0.00 | 0.00 |
Minimum of Months | 1650.91 | 119.71 | 780.37 | 7.27 | 663.50 | 0.00 | 0.00 |
Maximum of Months | 3495.49 | 1609.27 | 2409.18 | 1718.17 | 857.14 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 949.75 | 1112.97 | 760.64 | 411.31 | 349.33 | 0.00 | 0.00 |
February | 1117.34 | 956.24 | 861.21 | 435.89 | 425.32 | 0.00 | 0.00 |
March | 1145.82 | 832.33 | 848.81 | 375.75 | 473.06 | 0.00 | 0.00 |
April | 1629.46 | 555.77 | 1054.25 | 484.97 | 569.27 | 0.00 | 0.00 |
May | 1681.08 | 176.31 | 876.73 | 285.60 | 591.13 | 0.00 | 0.00 |
June | 1905.65 | 156.39 | 973.95 | 341.51 | 632.43 | 0.00 | 0.00 |
July | 1742.77 | 107.42 | 889.03 | 246.60 | 642.43 | 0.00 | 0.00 |
August | 1763.70 | 149.01 | 898.92 | 275.17 | 623.75 | 0.00 | 0.00 |
September | 1536.82 | 196.09 | 827.76 | 283.96 | 543.80 | 0.00 | 0.00 |
October | 1503.40 | 353.22 | 847.45 | 366.17 | 481.28 | 0.00 | 0.00 |
November | 1048.26 | 748.47 | 726.37 | 365.04 | 361.32 | 0.00 | 0.00 |
December | 923.61 | 970.86 | 698.70 | 371.56 | 327.14 | 0.00 | 0.00 |
Annual Sum or Average | 1413.44 | 523.95 | 854.83 | 352.79 | 502.04 | 0.00 | 0.00 |
Minimum of Months | 923.61 | 107.42 | 698.70 | 246.60 | 327.14 | 0.00 | 0.00 |
Maximum of Months | 1905.65 | 1112.97 | 1054.25 | 484.97 | 642.43 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 323.53 | 1504.56 | 416.80 | 0.00 | 416.80 | 0.00 | 0.00 |
February | 421.39 | 1273.08 | 491.72 | 0.00 | 491.72 | 0.00 | 0.00 |
March | 593.90 | 1118.65 | 570.44 | 0.00 | 570.44 | 0.00 | 0.00 |
April | 917.83 | 726.90 | 673.25 | 2.76 | 670.48 | 0.00 | 0.00 |
May | 1550.94 | 226.68 | 762.58 | 27.89 | 734.69 | 0.00 | 0.00 |
June | 1839.20 | 198.34 | 867.22 | 60.05 | 807.17 | 0.00 | 0.00 |
July | 1764.14 | 136.10 | 841.58 | 32.06 | 809.51 | 0.00 | 0.00 |
August | 1600.98 | 182.50 | 753.65 | 5.93 | 747.72 | 0.00 | 0.00 |
September | 1264.00 | 256.05 | 650.98 | 0.05 | 650.93 | 0.00 | 0.00 |
October | 1025.22 | 457.06 | 565.69 | 0.00 | 565.69 | 0.00 | 0.00 |
November | 477.05 | 983.10 | 429.45 | 0.00 | 429.45 | 0.00 | 0.00 |
December | 340.97 | 1294.77 | 387.46 | 0.00 | 387.46 | 0.00 | 0.00 |
Annual Sum or Average | 1013.51 | 693.45 | 618.19 | 10.76 | 607.43 | 0.00 | 0.00 |
Minimum of Months | 323.53 | 136.10 | 387.46 | 0.00 | 387.46 | 0.00 | 0.00 |
Maximum of Months | 1839.20 | 1504.56 | 867.22 | 60.05 | 809.51 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 855.19 | 949.08 | 715.11 | 364.14 | 350.98 | 0.00 | 0.00 |
February | 997.57 | 810.34 | 796.30 | 384.43 | 411.87 | 0.00 | 0.00 |
March | 1257.62 | 722.07 | 936.72 | 451.75 | 484.96 | 0.00 | 0.00 |
April | 1565.93 | 490.29 | 1027.94 | 464.91 | 563.03 | 0.00 | 0.00 |
May | 1952.59 | 158.78 | 1059.53 | 459.43 | 600.10 | 0.00 | 0.00 |
June | 2057.54 | 138.13 | 1074.54 | 426.13 | 648.41 | 0.00 | 0.00 |
July | 1982.24 | 94.77 | 1036.01 | 379.12 | 656.88 | 0.00 | 0.00 |
August | 1831.47 | 127.20 | 954.65 | 328.22 | 626.43 | 0.00 | 0.00 |
September | 1539.62 | 177.08 | 845.64 | 290.73 | 554.91 | 0.00 | 0.00 |
October | 1445.22 | 306.13 | 835.67 | 352.65 | 483.02 | 0.00 | 0.00 |
November | 1023.60 | 639.16 | 739.86 | 377.43 | 362.43 | 0.00 | 0.00 |
December | 724.50 | 835.87 | 582.53 | 263.87 | 318.66 | 0.00 | 0.00 |
Annual Sum or Average | 1438.48 | 452.17 | 884.01 | 378.40 | 505.61 | 0.00 | 0.00 |
Minimum of Months | 724.50 | 94.77 | 582.53 | 263.87 | 318.66 | 0.00 | 0.00 |
Maximum of Months | 2057.54 | 949.08 | 1074.54 | 464.91 | 656.88 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3405.84 | 1505.21 | 2409.18 | 1718.17 | 691.02 | 0.00 | 0.00 |
February | 3156.76 | 1294.27 | 2184.99 | 1414.31 | 770.68 | 0.00 | 0.00 |
March | 2067.38 | 1149.08 | 1394.95 | 629.54 | 765.41 | 0.00 | 0.00 |
April | 1691.90 | 775.82 | 1033.92 | 242.27 | 791.64 | 0.00 | 0.00 |
May | 1624.75 | 236.10 | 789.99 | 33.57 | 756.41 | 0.00 | 0.00 |
June | 1663.62 | 204.08 | 780.37 | 7.27 | 773.10 | 0.00 | 0.00 |
July | 1721.83 | 133.27 | 816.92 | 15.01 | 801.91 | 0.00 | 0.00 |
August | 2038.77 | 198.10 | 961.07 | 115.36 | 845.71 | 0.00 | 0.00 |
September | 2244.48 | 285.72 | 1153.12 | 303.90 | 849.22 | 0.00 | 0.00 |
October | 3200.89 | 516.39 | 1789.07 | 931.94 | 857.14 | 0.00 | 0.00 |
November | 3500.59 | 1044.47 | 2276.71 | 1567.54 | 709.17 | 0.00 | 0.00 |
December | 3468.17 | 1344.38 | 2354.07 | 1690.56 | 663.50 | 0.00 | 0.00 |
Annual Sum or Average | 2478.80 | 720.82 | 1491.72 | 718.87 | 772.84 | 0.00 | 0.00 |
Minimum of Months | 1624.75 | 133.27 | 780.37 | 7.27 | 663.50 | 0.00 | 0.00 |
Maximum of Months | 3500.59 | 1505.21 | 2409.18 | 1718.17 | 857.14 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 965.67 | 1037.21 | 760.64 | 411.31 | 349.33 | 0.00 | 0.00 |
February | 1127.83 | 895.50 | 861.21 | 435.89 | 425.32 | 0.00 | 0.00 |
March | 1150.53 | 789.69 | 848.81 | 375.75 | 473.06 | 0.00 | 0.00 |
April | 1621.68 | 544.55 | 1054.25 | 484.97 | 569.27 | 0.00 | 0.00 |
May | 1664.45 | 182.76 | 876.73 | 285.60 | 591.13 | 0.00 | 0.00 |
June | 1886.73 | 163.47 | 973.95 | 341.51 | 632.43 | 0.00 | 0.00 |
July | 1722.04 | 113.73 | 889.03 | 246.60 | 642.43 | 0.00 | 0.00 |
August | 1745.94 | 154.97 | 898.92 | 275.17 | 623.75 | 0.00 | 0.00 |
September | 1521.59 | 201.68 | 827.76 | 283.96 | 543.80 | 0.00 | 0.00 |
October | 1493.94 | 349.39 | 847.45 | 366.17 | 481.28 | 0.00 | 0.00 |
November | 1054.17 | 709.56 | 726.37 | 365.04 | 361.32 | 0.00 | 0.00 |
December | 934.01 | 907.02 | 698.70 | 371.56 | 327.14 | 0.00 | 0.00 |
Annual Sum or Average | 1408.43 | 502.00 | 854.83 | 352.79 | 502.04 | 0.00 | 0.00 |
Minimum of Months | 934.01 | 113.73 | 698.70 | 246.60 | 327.14 | 0.00 | 0.00 |
Maximum of Months | 1886.73 | 1037.21 | 1054.25 | 484.97 | 642.43 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.673171E+09 | 0.489676E+10 | 0.111634E+10 | 0.00 | 0.111634E+10 | 0.00 | 0.00 |
February | 0.866645E+09 | 0.375493E+10 | 0.118956E+10 | 0.00 | 0.118956E+10 | 0.00 | 0.00 |
March | 0.145229E+10 | 0.352811E+10 | 0.152784E+10 | 0.00 | 0.152784E+10 | 0.00 | 0.00 |
April | 0.233645E+10 | 0.203712E+10 | 0.174503E+10 | 7162092.90 | 0.173786E+10 | 0.00 | 0.00 |
May | 0.421490E+10 | 0.573806E+09 | 0.204246E+10 | 74707444.46 | 0.196775E+10 | 0.00 | 0.00 |
June | 0.483284E+10 | 0.459730E+09 | 0.224778E+10 | 0.155640E+09 | 0.209214E+10 | 0.00 | 0.00 |
July | 0.478571E+10 | 0.319999E+09 | 0.225404E+10 | 85873697.81 | 0.216816E+10 | 0.00 | 0.00 |
August | 0.430916E+10 | 0.461212E+09 | 0.201853E+10 | 15875822.90 | 0.200266E+10 | 0.00 | 0.00 |
September | 0.331890E+10 | 0.668291E+09 | 0.168731E+10 | 129954.84 | 0.168718E+10 | 0.00 | 0.00 |
October | 0.273112E+10 | 0.132455E+10 | 0.151512E+10 | 0.00 | 0.151512E+10 | 0.00 | 0.00 |
November | 0.110153E+10 | 0.305693E+10 | 0.111311E+10 | 0.00 | 0.111311E+10 | 0.00 | 0.00 |
December | 0.737464E+09 | 0.430858E+10 | 0.103776E+10 | 0.00 | 0.103776E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.313602E+11 | 0.253900E+11 | 0.194949E+11 | 0.339389E+09 | 0.191555E+11 | 0.00 | 0.00 |
Minimum of Months | 0.673171E+09 | 0.319999E+09 | 0.103776E+10 | 0.00 | 0.103776E+10 | 0.00 | 0.00 |
Maximum of Months | 0.483284E+10 | 0.489676E+10 | 0.225404E+10 | 0.155640E+09 | 0.216816E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.216409E+10 | 0.296818E+10 | 0.191537E+10 | 0.975314E+09 | 0.940057E+09 | 0.00 | 0.00 |
February | 0.232887E+10 | 0.225940E+10 | 0.192643E+10 | 0.930028E+09 | 0.996399E+09 | 0.00 | 0.00 |
March | 0.335084E+10 | 0.212599E+10 | 0.250891E+10 | 0.120998E+10 | 0.129893E+10 | 0.00 | 0.00 |
April | 0.411969E+10 | 0.125485E+10 | 0.266442E+10 | 0.120504E+10 | 0.145938E+10 | 0.00 | 0.00 |
May | 0.533663E+10 | 0.375893E+09 | 0.283785E+10 | 0.123054E+10 | 0.160730E+10 | 0.00 | 0.00 |
June | 0.543784E+10 | 0.283827E+09 | 0.278521E+10 | 0.110454E+10 | 0.168067E+10 | 0.00 | 0.00 |
July | 0.542606E+10 | 0.179568E+09 | 0.277485E+10 | 0.101545E+10 | 0.175941E+10 | 0.00 | 0.00 |
August | 0.500793E+10 | 0.257337E+09 | 0.255694E+10 | 0.879096E+09 | 0.167785E+10 | 0.00 | 0.00 |
September | 0.406831E+10 | 0.431117E+09 | 0.219192E+10 | 0.753574E+09 | 0.143834E+10 | 0.00 | 0.00 |
October | 0.393246E+10 | 0.821779E+09 | 0.223827E+10 | 0.944542E+09 | 0.129373E+10 | 0.00 | 0.00 |
November | 0.262060E+10 | 0.182829E+10 | 0.191774E+10 | 0.978313E+09 | 0.939424E+09 | 0.00 | 0.00 |
December | 0.185365E+10 | 0.258183E+10 | 0.156025E+10 | 0.706758E+09 | 0.853490E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.456470E+11 | 0.153681E+11 | 0.278782E+11 | 0.119332E+11 | 0.159450E+11 | 0.00 | 0.00 |
Minimum of Months | 0.185365E+10 | 0.179568E+09 | 0.156025E+10 | 0.706758E+09 | 0.853490E+09 | 0.00 | 0.00 |
Maximum of Months | 0.543784E+10 | 0.296818E+10 | 0.283785E+10 | 0.123054E+10 | 0.175941E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.912166E+10 | 0.438976E+10 | 0.645256E+10 | 0.460178E+10 | 0.185078E+10 | 0.00 | 0.00 |
February | 0.762708E+10 | 0.342861E+10 | 0.528578E+10 | 0.342138E+10 | 0.186440E+10 | 0.00 | 0.00 |
March | 0.553334E+10 | 0.337714E+10 | 0.373613E+10 | 0.168611E+10 | 0.205002E+10 | 0.00 | 0.00 |
April | 0.441223E+10 | 0.209373E+10 | 0.267985E+10 | 0.627949E+09 | 0.205190E+10 | 0.00 | 0.00 |
May | 0.441678E+10 | 0.598026E+09 | 0.211586E+10 | 89919926.79 | 0.202594E+10 | 0.00 | 0.00 |
June | 0.436609E+10 | 0.477953E+09 | 0.202269E+10 | 18853130.54 | 0.200383E+10 | 0.00 | 0.00 |
July | 0.466907E+10 | 0.318086E+09 | 0.218800E+10 | 40214760.86 | 0.214779E+10 | 0.00 | 0.00 |
August | 0.551007E+10 | 0.493899E+09 | 0.257406E+10 | 0.308962E+09 | 0.226510E+10 | 0.00 | 0.00 |
September | 0.590617E+10 | 0.721691E+09 | 0.298881E+10 | 0.787672E+09 | 0.220114E+10 | 0.00 | 0.00 |
October | 0.867809E+10 | 0.138878E+10 | 0.479172E+10 | 0.249602E+10 | 0.229570E+10 | 0.00 | 0.00 |
November | 0.911106E+10 | 0.287704E+10 | 0.590106E+10 | 0.406293E+10 | 0.183813E+10 | 0.00 | 0.00 |
December | 0.928397E+10 | 0.395751E+10 | 0.630494E+10 | 0.452786E+10 | 0.177708E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.786356E+11 | 0.241222E+11 | 0.470415E+11 | 0.226697E+11 | 0.243718E+11 | 0.00 | 0.00 |
Minimum of Months | 0.436609E+10 | 0.318086E+09 | 0.202269E+10 | 18853130.54 | 0.177708E+10 | 0.00 | 0.00 |
Maximum of Months | 0.928397E+10 | 0.438976E+10 | 0.645256E+10 | 0.460178E+10 | 0.229570E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.246732E+10 | 0.334501E+10 | 0.203730E+10 | 0.110166E+10 | 0.935640E+09 | 0.00 | 0.00 |
February | 0.261435E+10 | 0.267768E+10 | 0.208345E+10 | 0.105451E+10 | 0.102894E+10 | 0.00 | 0.00 |
March | 0.297003E+10 | 0.262626E+10 | 0.227346E+10 | 0.100641E+10 | 0.126706E+10 | 0.00 | 0.00 |
April | 0.412871E+10 | 0.166709E+10 | 0.273261E+10 | 0.125705E+10 | 0.147556E+10 | 0.00 | 0.00 |
May | 0.446995E+10 | 0.521562E+09 | 0.234824E+10 | 0.764944E+09 | 0.158330E+10 | 0.00 | 0.00 |
June | 0.488280E+10 | 0.464814E+09 | 0.252448E+10 | 0.885201E+09 | 0.163928E+10 | 0.00 | 0.00 |
July | 0.456394E+10 | 0.378755E+09 | 0.238119E+10 | 0.660505E+09 | 0.172068E+10 | 0.00 | 0.00 |
August | 0.458774E+10 | 0.553909E+09 | 0.240768E+10 | 0.737025E+09 | 0.167066E+10 | 0.00 | 0.00 |
September | 0.395035E+10 | 0.583974E+09 | 0.214555E+10 | 0.736027E+09 | 0.140952E+10 | 0.00 | 0.00 |
October | 0.396279E+10 | 0.108740E+10 | 0.226982E+10 | 0.980765E+09 | 0.128906E+10 | 0.00 | 0.00 |
November | 0.261384E+10 | 0.230285E+10 | 0.188275E+10 | 0.946195E+09 | 0.936555E+09 | 0.00 | 0.00 |
December | 0.234075E+10 | 0.318985E+10 | 0.187141E+10 | 0.995191E+09 | 0.876220E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.435526E+11 | 0.193992E+11 | 0.269580E+11 | 0.111255E+11 | 0.158325E+11 | 0.00 | 0.00 |
Minimum of Months | 0.234075E+10 | 0.378755E+09 | 0.187141E+10 | 0.660505E+09 | 0.876220E+09 | 0.00 | 0.00 |
Maximum of Months | 0.488280E+10 | 0.334501E+10 | 0.273261E+10 | 0.125705E+10 | 0.172068E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.787268E+09 | 0.439925E+10 | 0.111635E+10 | 0.00 | 0.111635E+10 | 0.00 | 0.00 |
February | 0.964611E+09 | 0.334717E+10 | 0.118957E+10 | 0.00 | 0.118957E+10 | 0.00 | 0.00 |
March | 0.154939E+10 | 0.319606E+10 | 0.152787E+10 | 0.00 | 0.152787E+10 | 0.00 | 0.00 |
April | 0.238773E+10 | 0.193656E+10 | 0.174505E+10 | 7162306.50 | 0.173789E+10 | 0.00 | 0.00 |
May | 0.422360E+10 | 0.574348E+09 | 0.204249E+10 | 74709672.45 | 0.196778E+10 | 0.00 | 0.00 |
June | 0.484376E+10 | 0.479434E+09 | 0.224782E+10 | 0.155644E+09 | 0.209218E+10 | 0.00 | 0.00 |
July | 0.481554E+10 | 0.327610E+09 | 0.225408E+10 | 85876258.80 | 0.216820E+10 | 0.00 | 0.00 |
August | 0.436022E+10 | 0.459679E+09 | 0.201857E+10 | 15876296.36 | 0.200269E+10 | 0.00 | 0.00 |
September | 0.334174E+10 | 0.635404E+09 | 0.168734E+10 | 129958.71 | 0.168721E+10 | 0.00 | 0.00 |
October | 0.277708E+10 | 0.124458E+10 | 0.151514E+10 | 0.00 | 0.151514E+10 | 0.00 | 0.00 |
November | 0.119332E+10 | 0.273684E+10 | 0.111313E+10 | 0.00 | 0.111313E+10 | 0.00 | 0.00 |
December | 0.854705E+09 | 0.377150E+10 | 0.103778E+10 | 0.00 | 0.103778E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.320990E+11 | 0.231084E+11 | 0.194952E+11 | 0.339399E+09 | 0.191558E+11 | 0.00 | 0.00 |
Minimum of Months | 0.787268E+09 | 0.327610E+09 | 0.103778E+10 | 0.00 | 0.103778E+10 | 0.00 | 0.00 |
Maximum of Months | 0.484376E+10 | 0.439925E+10 | 0.225408E+10 | 0.155644E+09 | 0.216820E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.220709E+10 | 0.275498E+10 | 0.191536E+10 | 0.975310E+09 | 0.940054E+09 | 0.00 | 0.00 |
February | 0.236048E+10 | 0.210951E+10 | 0.192642E+10 | 0.930024E+09 | 0.996395E+09 | 0.00 | 0.00 |
March | 0.334774E+10 | 0.203383E+10 | 0.250890E+10 | 0.120997E+10 | 0.129893E+10 | 0.00 | 0.00 |
April | 0.407467E+10 | 0.128999E+10 | 0.266441E+10 | 0.120504E+10 | 0.145937E+10 | 0.00 | 0.00 |
May | 0.528348E+10 | 0.403450E+09 | 0.283783E+10 | 0.123054E+10 | 0.160729E+10 | 0.00 | 0.00 |
June | 0.538859E+10 | 0.333404E+09 | 0.278520E+10 | 0.110453E+10 | 0.168067E+10 | 0.00 | 0.00 |
July | 0.537211E+10 | 0.229001E+09 | 0.277484E+10 | 0.101544E+10 | 0.175940E+10 | 0.00 | 0.00 |
August | 0.495894E+10 | 0.321015E+09 | 0.255693E+10 | 0.879093E+09 | 0.167784E+10 | 0.00 | 0.00 |
September | 0.403709E+10 | 0.439605E+09 | 0.219191E+10 | 0.753571E+09 | 0.143834E+10 | 0.00 | 0.00 |
October | 0.389826E+10 | 0.827550E+09 | 0.223826E+10 | 0.944538E+09 | 0.129372E+10 | 0.00 | 0.00 |
November | 0.262518E+10 | 0.174564E+10 | 0.191773E+10 | 0.978309E+09 | 0.939421E+09 | 0.00 | 0.00 |
December | 0.188971E+10 | 0.240581E+10 | 0.156024E+10 | 0.706755E+09 | 0.853486E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.454433E+11 | 0.148938E+11 | 0.278780E+11 | 0.119331E+11 | 0.159449E+11 | 0.00 | 0.00 |
Minimum of Months | 0.188971E+10 | 0.229001E+09 | 0.156024E+10 | 0.706755E+09 | 0.853486E+09 | 0.00 | 0.00 |
Maximum of Months | 0.538859E+10 | 0.275498E+10 | 0.283783E+10 | 0.123054E+10 | 0.175940E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.904264E+10 | 0.431028E+10 | 0.645276E+10 | 0.460194E+10 | 0.185082E+10 | 0.00 | 0.00 |
February | 0.757862E+10 | 0.333709E+10 | 0.528594E+10 | 0.342150E+10 | 0.186444E+10 | 0.00 | 0.00 |
March | 0.551450E+10 | 0.324369E+10 | 0.373623E+10 | 0.168616E+10 | 0.205006E+10 | 0.00 | 0.00 |
April | 0.440876E+10 | 0.205322E+10 | 0.267991E+10 | 0.627970E+09 | 0.205194E+10 | 0.00 | 0.00 |
May | 0.442181E+10 | 0.598691E+09 | 0.211590E+10 | 89922872.05 | 0.202598E+10 | 0.00 | 0.00 |
June | 0.438548E+10 | 0.491633E+09 | 0.202273E+10 | 18853748.06 | 0.200387E+10 | 0.00 | 0.00 |
July | 0.470457E+10 | 0.320626E+09 | 0.218805E+10 | 40216078.06 | 0.214783E+10 | 0.00 | 0.00 |
August | 0.553595E+10 | 0.498782E+09 | 0.257412E+10 | 0.308972E+09 | 0.226515E+10 | 0.00 | 0.00 |
September | 0.588479E+10 | 0.710375E+09 | 0.298889E+10 | 0.787698E+09 | 0.220119E+10 | 0.00 | 0.00 |
October | 0.862303E+10 | 0.138736E+10 | 0.479186E+10 | 0.249610E+10 | 0.229575E+10 | 0.00 | 0.00 |
November | 0.906031E+10 | 0.281637E+10 | 0.590124E+10 | 0.406306E+10 | 0.183817E+10 | 0.00 | 0.00 |
December | 0.924092E+10 | 0.382745E+10 | 0.630513E+10 | 0.452801E+10 | 0.177712E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.784014E+11 | 0.235956E+11 | 0.470427E+11 | 0.226704E+11 | 0.243723E+11 | 0.00 | 0.00 |
Minimum of Months | 0.438548E+10 | 0.320626E+09 | 0.202273E+10 | 18853748.06 | 0.177712E+10 | 0.00 | 0.00 |
Maximum of Months | 0.924092E+10 | 0.431028E+10 | 0.645276E+10 | 0.460194E+10 | 0.229575E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.254380E+10 | 0.298098E+10 | 0.203729E+10 | 0.110165E+10 | 0.935636E+09 | 0.00 | 0.00 |
February | 0.270308E+10 | 0.231334E+10 | 0.208344E+10 | 0.105451E+10 | 0.102893E+10 | 0.00 | 0.00 |
March | 0.306895E+10 | 0.222931E+10 | 0.227345E+10 | 0.100640E+10 | 0.126705E+10 | 0.00 | 0.00 |
April | 0.422356E+10 | 0.144055E+10 | 0.273260E+10 | 0.125705E+10 | 0.147555E+10 | 0.00 | 0.00 |
May | 0.450260E+10 | 0.472226E+09 | 0.234823E+10 | 0.764941E+09 | 0.158329E+10 | 0.00 | 0.00 |
June | 0.493945E+10 | 0.405355E+09 | 0.252447E+10 | 0.885198E+09 | 0.163927E+10 | 0.00 | 0.00 |
July | 0.466783E+10 | 0.287709E+09 | 0.238118E+10 | 0.660502E+09 | 0.172068E+10 | 0.00 | 0.00 |
August | 0.472389E+10 | 0.399109E+09 | 0.240767E+10 | 0.737022E+09 | 0.167065E+10 | 0.00 | 0.00 |
September | 0.398343E+10 | 0.508277E+09 | 0.214554E+10 | 0.736024E+09 | 0.140952E+10 | 0.00 | 0.00 |
October | 0.402671E+10 | 0.946052E+09 | 0.226981E+10 | 0.980761E+09 | 0.128905E+10 | 0.00 | 0.00 |
November | 0.271709E+10 | 0.194004E+10 | 0.188274E+10 | 0.946191E+09 | 0.936552E+09 | 0.00 | 0.00 |
December | 0.247380E+10 | 0.260036E+10 | 0.187140E+10 | 0.995187E+09 | 0.876217E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.445742E+11 | 0.165233E+11 | 0.269578E+11 | 0.111254E+11 | 0.158324E+11 | 0.00 | 0.00 |
Minimum of Months | 0.247380E+10 | 0.287709E+09 | 0.187140E+10 | 0.660502E+09 | 0.876217E+09 | 0.00 | 0.00 |
Maximum of Months | 0.493945E+10 | 0.298098E+10 | 0.273260E+10 | 0.125705E+10 | 0.172068E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.866551E+09 | 0.402982E+10 | 0.111635E+10 | 0.00 | 0.111635E+10 | 0.00 | 0.00 |
February | 0.101943E+10 | 0.307984E+10 | 0.118957E+10 | 0.00 | 0.118957E+10 | 0.00 | 0.00 |
March | 0.159070E+10 | 0.299619E+10 | 0.152787E+10 | 0.00 | 0.152787E+10 | 0.00 | 0.00 |
April | 0.237902E+10 | 0.188412E+10 | 0.174505E+10 | 7162306.50 | 0.173789E+10 | 0.00 | 0.00 |
May | 0.415405E+10 | 0.607128E+09 | 0.204249E+10 | 74709672.45 | 0.196778E+10 | 0.00 | 0.00 |
June | 0.476720E+10 | 0.514104E+09 | 0.224782E+10 | 0.155644E+09 | 0.209218E+10 | 0.00 | 0.00 |
July | 0.472508E+10 | 0.364535E+09 | 0.225408E+10 | 85876258.80 | 0.216820E+10 | 0.00 | 0.00 |
August | 0.428808E+10 | 0.488797E+09 | 0.201857E+10 | 15876296.36 | 0.200269E+10 | 0.00 | 0.00 |
September | 0.327629E+10 | 0.663694E+09 | 0.168734E+10 | 129958.71 | 0.168721E+10 | 0.00 | 0.00 |
October | 0.274595E+10 | 0.122420E+10 | 0.151514E+10 | 0.00 | 0.151514E+10 | 0.00 | 0.00 |
November | 0.123652E+10 | 0.254819E+10 | 0.111313E+10 | 0.00 | 0.111313E+10 | 0.00 | 0.00 |
December | 0.913261E+09 | 0.346790E+10 | 0.103778E+10 | 0.00 | 0.103778E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.319621E+11 | 0.218685E+11 | 0.194952E+11 | 0.339399E+09 | 0.191558E+11 | 0.00 | 0.00 |
Minimum of Months | 0.866551E+09 | 0.364535E+09 | 0.103778E+10 | 0.00 | 0.103778E+10 | 0.00 | 0.00 |
Maximum of Months | 0.476720E+10 | 0.402982E+10 | 0.225408E+10 | 0.155644E+09 | 0.216820E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.229053E+10 | 0.254201E+10 | 0.191536E+10 | 0.975310E+09 | 0.940054E+09 | 0.00 | 0.00 |
February | 0.241332E+10 | 0.196037E+10 | 0.192642E+10 | 0.930024E+09 | 0.996395E+09 | 0.00 | 0.00 |
March | 0.336841E+10 | 0.193399E+10 | 0.250890E+10 | 0.120997E+10 | 0.129893E+10 | 0.00 | 0.00 |
April | 0.405888E+10 | 0.127084E+10 | 0.266441E+10 | 0.120504E+10 | 0.145937E+10 | 0.00 | 0.00 |
May | 0.522983E+10 | 0.425281E+09 | 0.283783E+10 | 0.123054E+10 | 0.160729E+10 | 0.00 | 0.00 |
June | 0.533314E+10 | 0.358044E+09 | 0.278520E+10 | 0.110453E+10 | 0.168067E+10 | 0.00 | 0.00 |
July | 0.530922E+10 | 0.253832E+09 | 0.277484E+10 | 0.101544E+10 | 0.175940E+10 | 0.00 | 0.00 |
August | 0.490541E+10 | 0.340691E+09 | 0.255693E+10 | 0.879093E+09 | 0.167784E+10 | 0.00 | 0.00 |
September | 0.399069E+10 | 0.458994E+09 | 0.219191E+10 | 0.753571E+09 | 0.143834E+10 | 0.00 | 0.00 |
October | 0.387088E+10 | 0.819931E+09 | 0.223826E+10 | 0.944538E+09 | 0.129372E+10 | 0.00 | 0.00 |
November | 0.265317E+10 | 0.165671E+10 | 0.191773E+10 | 0.978309E+09 | 0.939421E+09 | 0.00 | 0.00 |
December | 0.194049E+10 | 0.223879E+10 | 0.156024E+10 | 0.706755E+09 | 0.853486E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.453640E+11 | 0.142595E+11 | 0.278780E+11 | 0.119331E+11 | 0.159449E+11 | 0.00 | 0.00 |
Minimum of Months | 0.194049E+10 | 0.253832E+09 | 0.156024E+10 | 0.706755E+09 | 0.853486E+09 | 0.00 | 0.00 |
Maximum of Months | 0.533314E+10 | 0.254201E+10 | 0.283783E+10 | 0.123054E+10 | 0.175940E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.912220E+10 | 0.403156E+10 | 0.645276E+10 | 0.460194E+10 | 0.185082E+10 | 0.00 | 0.00 |
February | 0.763683E+10 | 0.313111E+10 | 0.528594E+10 | 0.342150E+10 | 0.186444E+10 | 0.00 | 0.00 |
March | 0.553727E+10 | 0.307770E+10 | 0.373623E+10 | 0.168616E+10 | 0.205006E+10 | 0.00 | 0.00 |
April | 0.438539E+10 | 0.201093E+10 | 0.267991E+10 | 0.627970E+09 | 0.205194E+10 | 0.00 | 0.00 |
May | 0.435173E+10 | 0.632373E+09 | 0.211590E+10 | 89922872.05 | 0.202598E+10 | 0.00 | 0.00 |
June | 0.431211E+10 | 0.528963E+09 | 0.202273E+10 | 18853748.06 | 0.200387E+10 | 0.00 | 0.00 |
July | 0.461174E+10 | 0.356953E+09 | 0.218805E+10 | 40216078.06 | 0.214783E+10 | 0.00 | 0.00 |
August | 0.546063E+10 | 0.530579E+09 | 0.257412E+10 | 0.308972E+09 | 0.226515E+10 | 0.00 | 0.00 |
September | 0.581768E+10 | 0.740574E+09 | 0.298889E+10 | 0.787698E+09 | 0.220119E+10 | 0.00 | 0.00 |
October | 0.857325E+10 | 0.138310E+10 | 0.479186E+10 | 0.249610E+10 | 0.229575E+10 | 0.00 | 0.00 |
November | 0.907352E+10 | 0.270728E+10 | 0.590124E+10 | 0.406306E+10 | 0.183817E+10 | 0.00 | 0.00 |
December | 0.928915E+10 | 0.360078E+10 | 0.630513E+10 | 0.452801E+10 | 0.177712E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.781715E+11 | 0.227319E+11 | 0.470427E+11 | 0.226704E+11 | 0.243723E+11 | 0.00 | 0.00 |
Minimum of Months | 0.431211E+10 | 0.356953E+09 | 0.202273E+10 | 18853748.06 | 0.177712E+10 | 0.00 | 0.00 |
Maximum of Months | 0.928915E+10 | 0.403156E+10 | 0.645276E+10 | 0.460194E+10 | 0.229575E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.258644E+10 | 0.277807E+10 | 0.203729E+10 | 0.110165E+10 | 0.935636E+09 | 0.00 | 0.00 |
February | 0.272846E+10 | 0.216638E+10 | 0.208344E+10 | 0.105451E+10 | 0.102893E+10 | 0.00 | 0.00 |
March | 0.308158E+10 | 0.211511E+10 | 0.227345E+10 | 0.100640E+10 | 0.126705E+10 | 0.00 | 0.00 |
April | 0.420340E+10 | 0.141148E+10 | 0.273260E+10 | 0.125705E+10 | 0.147555E+10 | 0.00 | 0.00 |
May | 0.445807E+10 | 0.489515E+09 | 0.234823E+10 | 0.764941E+09 | 0.158329E+10 | 0.00 | 0.00 |
June | 0.489041E+10 | 0.423720E+09 | 0.252447E+10 | 0.885198E+09 | 0.163927E+10 | 0.00 | 0.00 |
July | 0.461230E+10 | 0.304613E+09 | 0.238118E+10 | 0.660502E+09 | 0.172068E+10 | 0.00 | 0.00 |
August | 0.467633E+10 | 0.415078E+09 | 0.240767E+10 | 0.737022E+09 | 0.167065E+10 | 0.00 | 0.00 |
September | 0.394396E+10 | 0.522755E+09 | 0.214554E+10 | 0.736024E+09 | 0.140952E+10 | 0.00 | 0.00 |
October | 0.400137E+10 | 0.935806E+09 | 0.226981E+10 | 0.980761E+09 | 0.128905E+10 | 0.00 | 0.00 |
November | 0.273241E+10 | 0.183919E+10 | 0.188274E+10 | 0.946191E+09 | 0.936552E+09 | 0.00 | 0.00 |
December | 0.250166E+10 | 0.242937E+10 | 0.187140E+10 | 0.995187E+09 | 0.876217E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.444164E+11 | 0.158311E+11 | 0.269578E+11 | 0.111254E+11 | 0.158324E+11 | 0.00 | 0.00 |
Minimum of Months | 0.250166E+10 | 0.304613E+09 | 0.187140E+10 | 0.660502E+09 | 0.876217E+09 | 0.00 | 0.00 |
Maximum of Months | 0.489041E+10 | 0.277807E+10 | 0.273260E+10 | 0.125705E+10 | 0.172068E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 13.57 | 11.02 | 8.64 | 3.24 | 3.13 | 48.31 | 209.17 | 0.01 |
February | 15.49 | 12.82 | 10.40 | 2.82 | 4.36 | 58.07 | 218.23 | 0.02 |
March | 17.07 | 13.58 | 10.72 | 3.68 | 7.24 | 76.61 | 186.08 | 0.03 |
April | 21.23 | 17.54 | 15.23 | 2.65 | 11.47 | 90.28 | 216.86 | 0.02 |
May | 26.90 | 22.82 | 21.10 | 3.11 | 19.64 | 106.10 | 173.47 | 0.04 |
June | 27.61 | 23.37 | 21.62 | 2.44 | 19.77 | 115.40 | 187.69 | 0.03 |
July | 27.94 | 24.58 | 23.34 | 2.53 | 20.70 | 123.49 | 154.05 | 0.05 |
August | 27.43 | 23.90 | 22.52 | 3.20 | 20.40 | 118.51 | 145.78 | 0.03 |
September | 26.23 | 23.37 | 22.24 | 3.39 | 19.02 | 101.73 | 135.58 | 0.05 |
October | 24.23 | 20.47 | 18.40 | 4.11 | 16.60 | 78.24 | 178.15 | 0.01 |
November | 18.91 | 15.31 | 12.62 | 2.63 | 7.99 | 49.56 | 205.43 | 0.01 |
December | 15.68 | 12.88 | 10.53 | 3.17 | 6.01 | 45.08 | 191.18 | 0.02 |
Annual Sum or Average | 21.89 | 18.50 | 16.48 | 3.09 | 13.08 | 84.44 | 183.16 | 0.03 |
Minimum of Months | 13.57 | 11.02 | 8.64 | 2.44 | 3.13 | 45.08 | 135.58 | 0.01 |
Maximum of Months | 27.94 | 24.58 | 23.34 | 4.11 | 20.70 | 123.49 | 218.23 | 0.05 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 27.00 | 02-JAN-14:00 | 18.67 | 14.00 | 1.50 | 17.75 | 146.50 | 0.00 |
February | 28.30 | 02-FEB-12:00 | 20.78 | 17.20 | 6.60 | 17.93 | 127.50 | 748.50 |
March | 30.00 | 26-MAR-13:00 | 19.88 | 14.40 | 3.00 | 19.52 | 288.50 | 548.00 |
April | 33.30 | 28-APR-14:00 | 23.06 | 18.80 | 4.10 | 23.15 | 150.50 | 762.50 |
May | 33.90 | 07-MAY-13:00 | 23.76 | 19.40 | 4.10 | 23.15 | 287.50 | 507.50 |
June | 35.00 | 14-JUN-13:00 | 23.95 | 19.40 | 2.10 | 24.16 | 194.50 | 712.50 |
July | 36.10 | 21-JUL-15:00 | 25.96 | 22.20 | 1.50 | 26.65 | 216.00 | 245.00 |
August | 36.30 | 30-AUG-15:00 | 23.74 | 18.50 | 2.40 | 25.33 | 116.00 | 698.50 |
September | 36.40 | 09-SEP-16:00 | 26.65 | 23.40 | 4.40 | 26.48 | 114.00 | 401.50 |
October | 34.00 | 05-OCT-14:00 | 24.05 | 20.00 | 2.60 | 29.55 | 169.50 | 606.00 |
November | 30.00 | 01-NOV-13:00 | 25.01 | 23.30 | 2.00 | 26.48 | 216.50 | 118.00 |
December | 30.00 | 13-DEC-14:00 | 21.84 | 18.00 | 3.10 | 20.92 | 101.50 | 682.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 27.00 | 18.67 | 14.00 | 1.50 | 17.75 | 101.50 | 0.00 | |
Maximum of Months | 36.40 | 26.65 | 23.40 | 6.60 | 29.55 | 288.50 | 762.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 0.00 | 05-JAN-05:00 | -0.0 | -0.0 | 2.10 | -16.0 | 0.00 | 0.00 |
February | -3.4 | 05-FEB-07:10 | -5.4 | -9.4 | 4.68 | -21.3 | 0.00 | 0.00 |
March | 1.10 | 09-MAR-05:00 | -2.1 | -7.3 | 3.60 | -14.4 | 0.00 | 0.00 |
April | 8.30 | 11-APR-05:00 | 6.95 | 5.50 | 0.00 | -6.9 | 0.00 | 0.00 |
May | 21.10 | 07-MAY-00:00 | 19.58 | 18.90 | 0.00 | 11.46 | 0.00 | 0.00 |
June | 20.60 | 07-JUN-01:00 | 18.00 | 16.70 | 3.60 | 10.50 | 0.00 | 0.00 |
July | 22.20 | 11-JUL-19:00 | 21.37 | 21.10 | 2.10 | 20.22 | 0.00 | 0.00 |
August | 20.20 | 25-AUG-23:00 | 20.20 | 20.20 | 5.30 | 11.84 | 0.00 | 0.00 |
September | 19.20 | 07-SEP-17:00 | 19.20 | 19.20 | 2.50 | 16.85 | 35.00 | 7.00 |
October | 10.00 | 28-OCT-04:00 | 5.56 | 0.00 | 3.60 | -0.1 | 0.00 | 0.00 |
November | 7.20 | 12-NOV-07:49 | 4.12 | 0.18 | 4.60 | -9.0 | 36.00 | 517.00 |
December | 0.00 | 21-DEC-04:00 | -0.9 | -2.0 | 2.10 | -16.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -3.4 | -5.4 | -9.4 | 0.00 | -21.3 | 0.00 | 0.00 | |
Maximum of Months | 22.20 | 21.37 | 21.10 | 5.30 | 20.22 | 36.00 | 517.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 22.11 | 31-JAN-12:00 | 25.00 | 21.00 | 5.70 | 20.92 | 336.50 | 96.00 |
February | 21.49 | 24-FEB-12:00 | 27.70 | 18.80 | 4.10 | 17.75 | 165.00 | 746.50 |
March | 22.77 | 30-MAR-12:00 | 29.40 | 20.00 | 2.50 | 27.14 | 340.00 | 0.00 |
April | 25.55 | 28-APR-15:00 | 32.20 | 23.30 | 3.60 | 22.47 | 156.00 | 575.50 |
May | 25.84 | 27-MAY-13:00 | 31.70 | 23.90 | 3.10 | 22.13 | 168.50 | 735.50 |
June | 26.52 | 29-JUN-16:00 | 29.40 | 25.60 | 1.50 | 26.32 | 164.00 | 36.00 |
July | 27.17 | 22-JUL-10:00 | 32.20 | 25.60 | 2.10 | 21.96 | 191.00 | 719.50 |
August | 27.24 | 07-AUG-12:00 | 31.00 | 26.00 | 3.10 | 27.95 | 473.00 | 200.00 |
September | 27.79 | 10-SEP-12:00 | 35.00 | 25.50 | 2.90 | 24.66 | 239.50 | 662.00 |
October | 28.18 | 07-OCT-07:00 | 29.00 | 28.00 | 2.60 | 21.09 | 95.00 | 500.50 |
November | 25.01 | 01-NOV-13:00 | 30.00 | 23.30 | 2.00 | 26.48 | 216.50 | 118.00 |
December | 24.12 | 12-DEC-13:00 | 27.00 | 23.00 | 2.10 | 19.17 | 160.50 | 599.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 21.49 | 25.00 | 18.80 | 1.50 | 17.75 | 95.00 | 0.00 | |
Maximum of Months | 28.18 | 35.00 | 28.00 | 5.70 | 27.95 | 473.00 | 746.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 21.00 | 31-JAN-12:00 | 25.00 | 22.11 | 5.70 | 20.92 | 336.50 | 96.00 |
February | 20.20 | 02-FEB-22:00 | 21.50 | 20.56 | 4.80 | 14.65 | 0.00 | 0.00 |
March | 21.10 | 07-MAR-08:00 | 23.30 | 21.69 | 2.00 | 13.91 | 126.00 | 566.50 |
April | 23.30 | 28-APR-15:00 | 32.20 | 25.55 | 3.60 | 22.47 | 156.00 | 575.50 |
May | 24.40 | 26-MAY-08:20 | 27.07 | 25.09 | 3.10 | 23.71 | 252.67 | 47.33 |
June | 25.60 | 29-JUN-14:00 | 27.20 | 26.00 | 5.10 | 24.16 | 335.00 | 238.00 |
July | 25.60 | 02-JUL-05:00 | 26.10 | 25.71 | 2.60 | 19.52 | 30.50 | 8.50 |
August | 26.60 | 09-AUG-18:00 | 26.60 | 26.60 | 1.90 | 19.52 | 26.00 | 23.00 |
September | 25.50 | 10-SEP-12:00 | 35.00 | 27.79 | 2.90 | 24.66 | 239.50 | 662.00 |
October | 28.00 | 07-OCT-07:00 | 29.00 | 28.18 | 2.60 | 21.09 | 95.00 | 500.50 |
November | 23.80 | 01-NOV-10:00 | 26.10 | 24.39 | 2.00 | 22.64 | 228.50 | 113.00 |
December | 23.00 | 12-DEC-13:00 | 27.00 | 24.12 | 2.10 | 19.17 | 160.50 | 599.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.20 | 21.50 | 20.56 | 1.90 | 13.91 | 0.00 | 0.00 | |
Maximum of Months | 28.00 | 35.00 | 28.18 | 5.70 | 24.66 | 336.50 | 662.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 20.46 | 29.60 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 20.78 | 36.65 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 22.23 | 38.94 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 24.49 | 49.11 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 26.95 | 46.95 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 28.93 | 51.71 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 29.89 | 48.43 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 29.58 | 45.50 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 28.08 | 39.22 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 25.80 | 37.51 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 23.35 | 31.26 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 21.40 | 27.18 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 25.18 | 40.17 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 20.46 | 27.18 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 29.89 | 51.71 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.316941E+11 | -0.306723E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102181E+10 | 58.98 | 0.00 | 0.00 |
February | 0.285705E+11 | -0.276466E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -923821343.2 | 58.97 | 0.00 | 0.00 |
March | 0.322990E+11 | -0.312722E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102675E+10 | 58.98 | 0.00 | 0.00 |
April | 0.276058E+11 | -0.266158E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -989956834.6 | 58.96 | 0.00 | 0.00 |
May | 0.274494E+11 | -0.264264E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102308E+10 | 58.97 | 0.00 | 0.00 |
June | 0.255533E+11 | -0.245617E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -991542835.9 | 58.97 | 0.00 | 0.00 |
July | 0.236217E+11 | -0.226027E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101895E+10 | 58.97 | 0.00 | 0.00 |
August | 0.260438E+11 | -0.250211E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102267E+10 | 58.97 | 0.00 | 0.00 |
September | 0.248604E+11 | -0.238729E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -987477863.9 | 58.97 | 0.00 | 0.00 |
October | 0.274556E+11 | -0.264370E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101858E+10 | 58.97 | 0.00 | 0.00 |
November | 0.288190E+11 | -0.278328E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -986211668.9 | 58.98 | 0.00 | 0.00 |
December | 0.302298E+11 | -0.292107E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101904E+10 | 58.97 | 0.00 | 0.00 |
Annual Sum or Average | 0.334202E+12 | -0.322172E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.120299E+11 | 58.97 | 0.00 | 0.00 |
Minimum of Months | 0.236217E+11 | -0.312722E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.102675E+10 | 58.96 | 0.00 | 0.00 |
Maximum of Months | 0.322990E+11 | -0.226027E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -923821343.2 | 58.98 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.64 | 0.61 | 01-JAN-07:00 | 6725.53 | 34.61 | 279.17 | 288.50 | 1112.85 | 25.01 | 167.17 | 270.67 |
February | 295.50 | 0.63 | 0.61 | 01-FEB-11:39 | 2777.54 | 26.53 | 165.17 | 272.50 | 953.61 | 21.96 | 106.50 | 257.17 |
March | 296.00 | 0.64 | 0.61 | 02-MAR-12:39 | 1216.55 | 16.86 | 0.00 | 306.50 | 703.80 | 19.77 | 50.00 | 258.17 |
April | 347.33 | 0.65 | 0.61 | 01-APR-07:30 | 965.20 | 16.00 | 0.00 | 309.50 | 553.46 | 18.85 | 19.83 | 258.83 |
May | 353.67 | 0.64 | 0.61 | 01-MAY-06:00 | 864.11 | 16.13 | 0.00 | 332.17 | 484.50 | 19.05 | 5.50 | 266.67 |
June | 394.00 | 0.64 | 0.61 | 01-JUN-06:40 | 819.52 | 15.75 | 0.00 | 332.50 | 462.56 | 18.67 | 1.67 | 266.83 |
July | 390.00 | 0.64 | 0.61 | 01-JUL-06:40 | 910.33 | 16.19 | 0.00 | 345.00 | 496.97 | 19.09 | 10.17 | 279.50 |
August | 380.83 | 0.64 | 0.61 | 01-AUG-06:00 | 1062.71 | 16.59 | 0.00 | 335.00 | 567.17 | 19.44 | 36.50 | 281.67 |
September | 342.17 | 0.64 | 0.61 | 01-SEP-06:00 | 1257.42 | 16.96 | 3.67 | 305.83 | 658.05 | 19.70 | 93.33 | 261.17 |
October | 330.00 | 0.63 | 0.61 | 01-OCT-06:00 | 2251.76 | 21.48 | 80.50 | 307.17 | 887.59 | 20.92 | 144.50 | 271.17 |
November | 308.00 | 0.63 | 0.61 | 01-NOV-07:49 | 6845.52 | 35.40 | 293.83 | 282.17 | 1061.02 | 22.98 | 131.33 | 262.00 |
December | 282.83 | 0.64 | 0.61 | 01-DEC-07:49 | 6828.55 | 35.14 | 260.50 | 275.83 | 1454.25 | 26.98 | 168.17 | 258.83 |
Annual Sum or Average | 4027.67 | 0.64 | 2528.61 | 21.68 | 1082.83 | 3692.67 | 755.76 | 20.82 | 934.67 | 3192.67 | ||
Minimum of Months | 282.83 | 0.63 | 0.61 | 819.52 | 15.75 | 0.00 | 272.50 | 462.56 | 18.67 | 1.67 | 257.17 | |
Maximum of Months | 394.00 | 0.65 | 0.61 | 6845.52 | 35.40 | 293.83 | 345.00 | 1454.25 | 26.98 | 168.17 | 281.67 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.66 | 0.61 | 01-JAN-07:49 | 1570.43 | 17.11 | 81.17 | 238.00 | 804.55 | 16.51 | 53.33 | 174.67 |
February | 295.50 | 0.65 | 0.61 | 01-FEB-11:39 | 1735.06 | 16.85 | 71.67 | 237.17 | 943.11 | 17.88 | 62.00 | 191.67 |
March | 296.00 | 0.64 | 0.61 | 02-MAR-12:39 | 1821.33 | 15.09 | 48.50 | 294.50 | 927.00 | 13.45 | 0.00 | 230.50 |
April | 347.33 | 0.65 | 0.61 | 01-APR-07:10 | 1850.45 | 11.54 | 0.00 | 305.67 | 993.99 | 12.90 | 0.00 | 259.17 |
May | 353.67 | 0.64 | 0.61 | 01-MAY-06:40 | 2070.86 | 12.21 | 0.00 | 339.67 | 817.13 | 13.38 | 0.00 | 278.17 |
June | 394.00 | 0.64 | 0.61 | 01-JUN-06:10 | 1935.40 | 12.24 | 0.00 | 340.33 | 772.01 | 13.31 | 0.00 | 282.50 |
July | 390.00 | 0.64 | 0.61 | 01-JUL-06:10 | 1808.71 | 12.61 | 0.00 | 347.50 | 765.15 | 13.57 | 0.00 | 285.00 |
August | 380.83 | 0.64 | 0.61 | 01-AUG-06:49 | 1669.00 | 12.58 | 0.00 | 331.17 | 873.34 | 13.63 | 0.00 | 280.33 |
September | 342.17 | 0.65 | 0.61 | 01-SEP-06:49 | 1599.61 | 12.78 | 5.67 | 296.00 | 815.11 | 13.84 | 3.67 | 246.33 |
October | 330.00 | 0.64 | 0.61 | 01-OCT-06:49 | 1662.53 | 17.16 | 75.33 | 283.50 | 828.56 | 16.73 | 46.50 | 238.17 |
November | 308.00 | 0.65 | 0.61 | 01-NOV-07:49 | 1267.09 | 15.62 | 56.83 | 236.67 | 703.99 | 17.00 | 53.33 | 189.67 |
December | 282.83 | 0.66 | 0.61 | 01-DEC-07:49 | 1486.68 | 17.38 | 75.50 | 225.83 | 804.50 | 17.87 | 59.67 | 166.67 |
Annual Sum or Average | 4027.67 | 0.64 | 1718.08 | 14.23 | 414.67 | 3476.00 | 835.83 | 14.85 | 278.50 | 2822.83 | ||
Minimum of Months | 282.83 | 0.64 | 0.61 | 1267.09 | 11.54 | 0.00 | 225.83 | 703.99 | 12.90 | 0.00 | 166.67 | |
Maximum of Months | 394.00 | 0.66 | 0.61 | 2070.86 | 17.38 | 81.17 | 347.50 | 993.99 | 17.88 | 62.00 | 285.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.67 | 0.61 | 01-JAN-08:50 | 401.73 | 0.00 | 0.00 | 194.67 | 265.47 | 0.00 | 0.00 | 54.00 |
February | 295.50 | 0.66 | 0.61 | 01-FEB-11:39 | 463.81 | 0.00 | 0.00 | 215.83 | 307.40 | 0.00 | 0.00 | 112.33 |
March | 296.00 | 0.65 | 0.61 | 02-MAR-12:39 | 548.39 | 0.00 | 0.00 | 282.00 | 348.93 | 0.00 | 0.00 | 156.67 |
April | 347.33 | 0.64 | 0.61 | 01-APR-07:30 | 658.81 | 0.00 | 0.00 | 313.83 | 404.02 | 0.00 | 0.00 | 241.00 |
May | 353.67 | 0.63 | 0.61 | 01-MAY-06:49 | 816.33 | 0.00 | 0.00 | 353.83 | 473.31 | 0.00 | 0.00 | 294.50 |
June | 394.00 | 0.63 | 0.61 | 01-JUN-06:19 | 955.82 | 0.00 | 0.00 | 362.67 | 501.73 | 0.00 | 0.00 | 314.50 |
July | 390.00 | 0.63 | 0.61 | 01-JUL-06:19 | 937.83 | 0.00 | 0.00 | 364.00 | 507.07 | 0.00 | 0.00 | 313.67 |
August | 380.83 | 0.64 | 0.61 | 01-AUG-06:49 | 818.64 | 0.00 | 0.00 | 342.50 | 459.36 | 0.00 | 0.00 | 286.83 |
September | 342.17 | 0.64 | 0.61 | 01-SEP-06:00 | 682.19 | 0.00 | 0.00 | 301.17 | 392.86 | 0.00 | 0.00 | 215.33 |
October | 330.00 | 0.64 | 0.61 | 01-OCT-07:19 | 578.23 | 0.00 | 0.00 | 278.83 | 357.92 | 0.00 | 0.00 | 188.83 |
November | 308.00 | 0.67 | 0.61 | 01-NOV-08:30 | 412.00 | 0.00 | 0.00 | 199.17 | 274.04 | 0.00 | 0.00 | 60.83 |
December | 282.83 | 0.67 | 0.61 | 01-DEC-08:30 | 400.84 | 0.00 | 0.00 | 190.83 | 266.93 | 0.00 | 0.00 | 41.33 |
Annual Sum or Average | 4027.67 | 0.65 | 660.18 | 0.00 | 0.00 | 3399.33 | 388.87 | 0.00 | 0.00 | 2279.83 | ||
Minimum of Months | 282.83 | 0.63 | 0.61 | 400.84 | 0.00 | 0.00 | 190.83 | 265.47 | 0.00 | 0.00 | 41.33 | |
Maximum of Months | 394.00 | 0.67 | 0.61 | 955.82 | 0.00 | 0.00 | 364.00 | 507.07 | 0.00 | 0.00 | 314.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.66 | 0.61 | 01-JAN-08:50 | 1770.46 | 17.54 | 83.67 | 245.33 | 1037.37 | 19.07 | 80.17 | 183.33 |
February | 295.50 | 0.65 | 0.61 | 01-FEB-11:39 | 1614.34 | 17.58 | 77.83 | 245.33 | 819.79 | 16.87 | 50.00 | 200.00 |
March | 296.00 | 0.64 | 0.61 | 02-MAR-12:39 | 1730.22 | 14.65 | 45.33 | 289.33 | 868.44 | 13.30 | 0.00 | 222.67 |
April | 347.33 | 0.65 | 0.61 | 01-APR-07:49 | 1946.70 | 11.63 | 0.00 | 305.83 | 1034.14 | 13.01 | 0.00 | 263.83 |
May | 353.67 | 0.64 | 0.61 | 01-MAY-07:30 | 1596.40 | 12.25 | 0.00 | 334.50 | 694.13 | 13.43 | 0.00 | 276.17 |
June | 394.00 | 0.64 | 0.61 | 01-JUN-06:00 | 1749.52 | 12.18 | 0.00 | 340.00 | 705.11 | 13.25 | 0.00 | 283.33 |
July | 390.00 | 0.64 | 0.61 | 01-JUL-06:49 | 1604.45 | 12.57 | 0.00 | 347.83 | 681.70 | 13.54 | 0.00 | 286.17 |
August | 380.83 | 0.64 | 0.61 | 01-AUG-07:10 | 1623.29 | 12.66 | 0.00 | 332.00 | 727.02 | 13.72 | 0.00 | 279.67 |
September | 342.17 | 0.64 | 0.61 | 01-SEP-07:30 | 1512.31 | 12.71 | 5.50 | 296.83 | 752.68 | 13.65 | 0.00 | 246.17 |
October | 330.00 | 0.63 | 0.61 | 01-OCT-07:40 | 1919.38 | 17.75 | 83.17 | 287.50 | 788.94 | 15.12 | 9.67 | 241.17 |
November | 308.00 | 0.65 | 0.61 | 01-NOV-08:00 | 1563.10 | 17.26 | 79.50 | 241.33 | 849.15 | 17.83 | 63.17 | 186.50 |
December | 282.83 | 0.65 | 0.61 | 01-DEC-08:39 | 1678.16 | 18.69 | 84.83 | 243.33 | 870.32 | 18.13 | 58.83 | 173.33 |
Annual Sum or Average | 4027.67 | 0.64 | 1691.86 | 14.56 | 459.83 | 3509.17 | 811.62 | 14.91 | 261.83 | 2842.33 | ||
Minimum of Months | 282.83 | 0.63 | 0.61 | 1512.31 | 11.63 | 0.00 | 241.33 | 681.70 | 13.01 | 0.00 | 173.33 | |
Maximum of Months | 394.00 | 0.66 | 0.61 | 1946.70 | 18.69 | 84.83 | 347.83 | 1037.37 | 19.07 | 80.17 | 286.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.64 | 0.61 | 01-JAN-07:00 | 6715.41 | 33.93 | 278.83 | 287.50 | 1153.68 | 20.87 | 92.17 | 271.67 |
February | 295.50 | 0.63 | 0.61 | 01-FEB-11:39 | 2765.80 | 23.22 | 165.17 | 272.17 | 991.05 | 17.78 | 36.33 | 259.17 |
March | 296.00 | 0.64 | 0.61 | 02-MAR-12:39 | 1203.26 | 11.02 | 0.00 | 305.33 | 730.22 | 15.94 | 0.00 | 260.33 |
April | 347.33 | 0.65 | 0.61 | 01-APR-07:30 | 950.87 | 10.58 | 0.00 | 308.00 | 571.62 | 15.28 | 0.00 | 262.67 |
May | 353.67 | 0.64 | 0.61 | 01-MAY-06:00 | 847.82 | 10.58 | 0.00 | 330.33 | 498.52 | 15.36 | 0.00 | 270.50 |
June | 394.00 | 0.64 | 0.61 | 01-JUN-06:40 | 804.00 | 10.25 | 0.00 | 331.17 | 475.89 | 14.98 | 0.00 | 272.17 |
July | 390.00 | 0.64 | 0.61 | 01-JUL-06:40 | 891.79 | 10.51 | 0.00 | 343.17 | 510.94 | 15.22 | 0.00 | 283.83 |
August | 380.83 | 0.64 | 0.61 | 01-AUG-06:00 | 1040.46 | 10.90 | 0.00 | 332.83 | 583.31 | 15.56 | 0.00 | 285.67 |
September | 342.17 | 0.64 | 0.61 | 01-SEP-06:00 | 1229.60 | 11.18 | 3.67 | 304.67 | 677.24 | 15.65 | 0.00 | 263.00 |
October | 330.00 | 0.63 | 0.61 | 01-OCT-06:00 | 2220.90 | 16.37 | 77.17 | 306.00 | 922.87 | 16.97 | 10.33 | 273.50 |
November | 308.00 | 0.64 | 0.61 | 01-NOV-07:49 | 6795.94 | 33.52 | 279.00 | 278.00 | 1130.95 | 20.67 | 90.83 | 269.33 |
December | 282.83 | 0.64 | 0.61 | 01-DEC-07:00 | 6770.31 | 33.17 | 248.83 | 272.33 | 1496.40 | 23.18 | 110.83 | 259.50 |
Annual Sum or Average | 4027.67 | 0.64 | 2505.15 | 17.18 | 1052.67 | 3671.50 | 783.37 | 17.07 | 340.50 | 3231.33 | ||
Minimum of Months | 282.83 | 0.63 | 0.61 | 804.00 | 10.25 | 0.00 | 272.17 | 475.89 | 14.98 | 0.00 | 259.17 | |
Maximum of Months | 394.00 | 0.65 | 0.61 | 6795.94 | 33.93 | 279.00 | 343.17 | 1496.40 | 23.18 | 110.83 | 285.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.66 | 0.61 | 01-JAN-07:49 | 1569.52 | 15.14 | 81.33 | 237.67 | 823.65 | 14.63 | 53.33 | 180.33 |
February | 295.50 | 0.65 | 0.61 | 01-FEB-11:39 | 1735.37 | 14.66 | 71.67 | 236.67 | 964.76 | 16.13 | 62.17 | 197.17 |
March | 296.00 | 0.64 | 0.61 | 02-MAR-12:39 | 1610.91 | 12.38 | 48.50 | 294.17 | 954.27 | 10.91 | 0.00 | 237.00 |
April | 347.33 | 0.65 | 0.61 | 01-APR-07:10 | 1841.50 | 8.21 | 0.00 | 304.17 | 1017.92 | 10.57 | 0.00 | 263.33 |
May | 353.67 | 0.64 | 0.61 | 01-MAY-06:40 | 2053.78 | 8.71 | 0.00 | 339.50 | 842.86 | 11.07 | 0.00 | 284.33 |
June | 394.00 | 0.64 | 0.61 | 01-JUN-06:10 | 1845.87 | 8.87 | 0.00 | 338.83 | 795.42 | 11.13 | 0.00 | 287.83 |
July | 390.00 | 0.64 | 0.61 | 01-JUL-06:19 | 1793.54 | 9.21 | 0.00 | 346.17 | 788.13 | 11.36 | 0.00 | 288.83 |
August | 380.83 | 0.64 | 0.61 | 01-AUG-06:49 | 1650.87 | 9.24 | 0.00 | 330.33 | 895.03 | 11.35 | 0.00 | 284.83 |
September | 342.17 | 0.65 | 0.61 | 01-SEP-06:49 | 1594.91 | 9.53 | 5.67 | 295.33 | 836.03 | 11.47 | 3.67 | 251.83 |
October | 330.00 | 0.64 | 0.61 | 01-OCT-06:49 | 1663.17 | 14.85 | 75.33 | 282.50 | 850.23 | 14.68 | 47.17 | 242.83 |
November | 308.00 | 0.65 | 0.61 | 01-NOV-07:49 | 1265.60 | 13.15 | 56.83 | 236.17 | 723.64 | 15.06 | 53.67 | 195.83 |
December | 282.83 | 0.66 | 0.61 | 01-DEC-07:49 | 1484.76 | 15.39 | 75.50 | 224.83 | 822.29 | 16.08 | 59.67 | 172.33 |
Annual Sum or Average | 4027.67 | 0.65 | 1687.76 | 11.36 | 414.83 | 3466.33 | 858.08 | 12.70 | 279.67 | 2886.50 | ||
Minimum of Months | 282.83 | 0.64 | 0.61 | 1265.60 | 8.21 | 0.00 | 224.83 | 723.64 | 10.57 | 0.00 | 172.33 | |
Maximum of Months | 394.00 | 0.66 | 0.61 | 2053.78 | 15.39 | 81.33 | 346.17 | 1017.92 | 16.13 | 62.17 | 288.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.68 | 0.61 | 01-JAN-08:50 | 394.77 | 0.00 | 0.00 | 188.67 | 273.00 | 0.00 | 0.00 | 66.67 |
February | 295.50 | 0.66 | 0.61 | 01-FEB-11:39 | 456.51 | 0.00 | 0.00 | 212.50 | 316.41 | 0.00 | 0.00 | 123.50 |
March | 296.00 | 0.65 | 0.61 | 02-MAR-12:39 | 540.47 | 0.00 | 0.00 | 279.00 | 359.63 | 0.00 | 0.00 | 171.67 |
April | 347.33 | 0.65 | 0.61 | 01-APR-07:30 | 649.19 | 0.00 | 0.00 | 312.33 | 416.45 | 0.00 | 0.00 | 248.83 |
May | 353.67 | 0.63 | 0.61 | 01-MAY-06:49 | 802.24 | 0.00 | 0.00 | 353.00 | 482.99 | 0.00 | 0.00 | 294.17 |
June | 394.00 | 0.63 | 0.61 | 01-JUN-06:19 | 940.17 | 0.00 | 0.00 | 361.83 | 524.98 | 0.00 | 0.00 | 324.83 |
July | 390.00 | 0.63 | 0.61 | 01-JUL-06:19 | 920.50 | 0.00 | 0.00 | 363.50 | 521.26 | 0.00 | 0.00 | 318.83 |
August | 380.83 | 0.64 | 0.61 | 01-AUG-06:00 | 803.20 | 0.00 | 0.00 | 340.67 | 472.29 | 0.00 | 0.00 | 290.33 |
September | 342.17 | 0.64 | 0.61 | 01-SEP-06:00 | 669.84 | 0.00 | 0.00 | 299.50 | 404.10 | 0.00 | 0.00 | 222.00 |
October | 330.00 | 0.64 | 0.61 | 01-OCT-07:19 | 568.07 | 0.00 | 0.00 | 277.00 | 368.10 | 0.00 | 0.00 | 196.17 |
November | 308.00 | 0.67 | 0.61 | 01-NOV-08:39 | 405.04 | 0.00 | 0.00 | 196.00 | 281.85 | 0.00 | 0.00 | 76.67 |
December | 282.83 | 0.67 | 0.61 | 01-DEC-08:30 | 393.46 | 0.00 | 0.00 | 185.00 | 274.26 | 0.00 | 0.00 | 52.83 |
Annual Sum or Average | 4027.67 | 0.65 | 648.87 | 0.00 | 0.00 | 3369.00 | 400.59 | 0.00 | 0.00 | 2386.50 | ||
Minimum of Months | 282.83 | 0.63 | 0.61 | 393.46 | 0.00 | 0.00 | 185.00 | 273.00 | 0.00 | 0.00 | 52.83 | |
Maximum of Months | 394.00 | 0.68 | 0.61 | 940.17 | 0.00 | 0.00 | 363.50 | 524.98 | 0.00 | 0.00 | 324.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.66 | 0.61 | 01-JAN-08:50 | 1762.94 | 15.44 | 82.67 | 244.67 | 1057.80 | 17.45 | 80.50 | 189.83 |
February | 295.50 | 0.65 | 0.61 | 01-FEB-11:39 | 1419.40 | 12.88 | 51.33 | 244.83 | 842.88 | 14.93 | 50.00 | 206.00 |
March | 296.00 | 0.64 | 0.61 | 02-MAR-12:39 | 1739.41 | 11.96 | 45.33 | 288.50 | 892.13 | 10.82 | 0.00 | 230.50 |
April | 347.33 | 0.65 | 0.61 | 01-APR-07:49 | 1935.96 | 8.28 | 0.00 | 305.50 | 1058.38 | 10.66 | 0.00 | 267.33 |
May | 353.67 | 0.64 | 0.61 | 01-MAY-07:30 | 1580.02 | 8.87 | 0.00 | 333.33 | 715.56 | 11.18 | 0.00 | 281.33 |
June | 394.00 | 0.64 | 0.61 | 01-JUN-06:00 | 1680.71 | 8.88 | 0.00 | 338.67 | 726.96 | 11.09 | 0.00 | 289.17 |
July | 390.00 | 0.64 | 0.61 | 01-JUL-06:49 | 1553.76 | 9.25 | 0.00 | 345.83 | 702.30 | 11.37 | 0.00 | 290.67 |
August | 380.83 | 0.64 | 0.61 | 01-AUG-07:10 | 1606.16 | 9.34 | 0.00 | 330.83 | 748.15 | 11.45 | 0.00 | 283.17 |
September | 342.17 | 0.64 | 0.61 | 01-SEP-07:30 | 1507.40 | 9.46 | 5.50 | 295.83 | 773.12 | 11.24 | 0.00 | 249.33 |
October | 330.00 | 0.63 | 0.61 | 01-OCT-07:40 | 1919.71 | 15.47 | 83.17 | 286.83 | 803.01 | 12.37 | 7.00 | 244.00 |
November | 308.00 | 0.65 | 0.61 | 01-NOV-08:00 | 1562.19 | 15.14 | 79.50 | 240.83 | 820.92 | 14.67 | 50.67 | 189.17 |
December | 282.83 | 0.65 | 0.61 | 01-DEC-08:39 | 1678.88 | 16.75 | 84.83 | 242.17 | 880.38 | 15.90 | 55.83 | 178.67 |
Annual Sum or Average | 4027.67 | 0.64 | 1661.62 | 11.55 | 432.33 | 3497.83 | 828.16 | 12.60 | 244.00 | 2899.17 | ||
Minimum of Months | 282.83 | 0.63 | 0.61 | 1419.40 | 8.28 | 0.00 | 240.83 | 702.30 | 10.66 | 0.00 | 178.67 | |
Maximum of Months | 394.00 | 0.66 | 0.61 | 1935.96 | 16.75 | 84.83 | 345.83 | 1058.38 | 17.45 | 80.50 | 290.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.64 | 0.61 | 01-JAN-07:00 | 6715.08 | 33.91 | 278.83 | 287.50 | 1154.60 | 20.86 | 92.17 | 271.67 |
February | 295.50 | 0.63 | 0.61 | 01-FEB-11:39 | 2766.12 | 23.19 | 165.17 | 272.17 | 991.94 | 17.76 | 36.33 | 259.17 |
March | 296.00 | 0.64 | 0.61 | 02-MAR-12:39 | 1203.75 | 10.98 | 0.00 | 305.33 | 730.97 | 15.92 | 0.00 | 260.33 |
April | 347.33 | 0.65 | 0.61 | 01-APR-07:30 | 951.24 | 10.54 | 0.00 | 308.00 | 572.21 | 15.26 | 0.00 | 262.67 |
May | 353.67 | 0.64 | 0.61 | 01-MAY-06:00 | 848.16 | 10.54 | 0.00 | 330.33 | 499.06 | 15.34 | 0.00 | 270.67 |
June | 394.00 | 0.64 | 0.61 | 01-JUN-06:40 | 804.31 | 10.21 | 0.00 | 331.17 | 476.40 | 14.97 | 0.00 | 272.50 |
July | 390.00 | 0.64 | 0.61 | 01-JUL-06:40 | 892.24 | 10.47 | 0.00 | 343.17 | 511.53 | 15.20 | 0.00 | 284.17 |
August | 380.83 | 0.64 | 0.61 | 01-AUG-06:00 | 1041.08 | 10.86 | 0.00 | 332.83 | 584.04 | 15.54 | 0.00 | 286.00 |
September | 342.17 | 0.64 | 0.61 | 01-SEP-06:00 | 1230.38 | 11.14 | 3.67 | 304.67 | 678.14 | 15.63 | 0.00 | 263.00 |
October | 330.00 | 0.63 | 0.61 | 01-OCT-06:00 | 2221.55 | 16.34 | 77.17 | 305.83 | 923.94 | 16.95 | 10.33 | 273.50 |
November | 308.00 | 0.64 | 0.61 | 01-NOV-07:49 | 6795.90 | 33.51 | 279.00 | 278.00 | 1131.88 | 20.66 | 90.83 | 269.33 |
December | 282.83 | 0.64 | 0.61 | 01-DEC-07:00 | 6769.81 | 33.16 | 248.83 | 272.33 | 1497.38 | 23.17 | 110.83 | 259.50 |
Annual Sum or Average | 4027.67 | 0.64 | 2505.46 | 17.15 | 1052.67 | 3671.33 | 784.14 | 17.06 | 340.50 | 3232.50 | ||
Minimum of Months | 282.83 | 0.63 | 0.61 | 804.31 | 10.21 | 0.00 | 272.17 | 476.40 | 14.97 | 0.00 | 259.17 | |
Maximum of Months | 394.00 | 0.65 | 0.61 | 6795.90 | 33.91 | 279.00 | 343.17 | 1497.38 | 23.17 | 110.83 | 286.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.66 | 0.61 | 01-JAN-07:49 | 1569.18 | 15.13 | 81.33 | 237.67 | 824.05 | 14.62 | 53.33 | 180.33 |
February | 295.50 | 0.65 | 0.61 | 01-FEB-11:39 | 1735.03 | 14.65 | 71.67 | 236.67 | 965.24 | 16.12 | 62.17 | 197.17 |
March | 296.00 | 0.64 | 0.61 | 02-MAR-12:39 | 1610.54 | 12.37 | 48.50 | 294.00 | 954.87 | 10.90 | 0.00 | 237.00 |
April | 347.33 | 0.65 | 0.61 | 01-APR-07:10 | 1841.47 | 8.20 | 0.00 | 304.17 | 1018.53 | 10.56 | 0.00 | 263.67 |
May | 353.67 | 0.64 | 0.61 | 01-MAY-06:40 | 2053.78 | 8.70 | 0.00 | 339.50 | 843.58 | 11.06 | 0.00 | 284.83 |
June | 394.00 | 0.64 | 0.61 | 01-JUN-06:10 | 1845.97 | 8.86 | 0.00 | 338.83 | 796.17 | 11.12 | 0.00 | 287.83 |
July | 390.00 | 0.64 | 0.61 | 01-JUL-06:19 | 1793.78 | 9.20 | 0.00 | 346.17 | 788.96 | 11.35 | 0.00 | 289.00 |
August | 380.83 | 0.64 | 0.61 | 01-AUG-06:49 | 1651.16 | 9.23 | 0.00 | 330.33 | 889.70 | 11.34 | 0.00 | 284.50 |
September | 342.17 | 0.65 | 0.61 | 01-SEP-06:49 | 1595.14 | 9.52 | 5.67 | 295.33 | 811.72 | 11.46 | 3.67 | 249.33 |
October | 330.00 | 0.64 | 0.61 | 01-OCT-06:49 | 1662.88 | 14.84 | 75.33 | 282.67 | 850.90 | 14.68 | 47.17 | 242.83 |
November | 308.00 | 0.65 | 0.61 | 01-NOV-07:49 | 1265.25 | 13.13 | 56.83 | 236.17 | 724.07 | 15.06 | 53.67 | 196.00 |
December | 282.83 | 0.66 | 0.61 | 01-DEC-07:49 | 1484.44 | 15.38 | 75.50 | 224.50 | 822.68 | 16.07 | 59.67 | 172.50 |
Annual Sum or Average | 4027.67 | 0.65 | 1687.69 | 11.35 | 414.83 | 3466.00 | 856.00 | 12.70 | 279.67 | 2885.00 | ||
Minimum of Months | 282.83 | 0.64 | 0.61 | 1265.25 | 8.20 | 0.00 | 224.50 | 724.07 | 10.56 | 0.00 | 172.50 | |
Maximum of Months | 394.00 | 0.66 | 0.61 | 2053.78 | 15.38 | 81.33 | 346.17 | 1018.53 | 16.12 | 62.17 | 289.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.68 | 0.61 | 01-JAN-08:50 | 394.60 | 0.00 | 0.00 | 188.83 | 273.17 | 0.00 | 0.00 | 66.83 |
February | 295.50 | 0.66 | 0.61 | 01-FEB-11:39 | 456.32 | 0.00 | 0.00 | 212.50 | 316.60 | 0.00 | 0.00 | 123.67 |
March | 296.00 | 0.65 | 0.61 | 02-MAR-12:39 | 540.36 | 0.00 | 0.00 | 279.00 | 359.89 | 0.00 | 0.00 | 172.00 |
April | 347.33 | 0.65 | 0.61 | 01-APR-07:30 | 649.16 | 0.00 | 0.00 | 312.33 | 416.80 | 0.00 | 0.00 | 249.33 |
May | 353.67 | 0.63 | 0.61 | 01-MAY-06:49 | 802.39 | 0.00 | 0.00 | 353.00 | 483.49 | 0.00 | 0.00 | 294.33 |
June | 394.00 | 0.63 | 0.61 | 01-JUN-06:19 | 940.41 | 0.00 | 0.00 | 361.83 | 525.54 | 0.00 | 0.00 | 325.17 |
July | 390.00 | 0.63 | 0.61 | 01-JUL-06:19 | 920.81 | 0.00 | 0.00 | 363.33 | 521.86 | 0.00 | 0.00 | 319.17 |
August | 380.83 | 0.64 | 0.61 | 01-AUG-06:00 | 803.43 | 0.00 | 0.00 | 340.67 | 472.82 | 0.00 | 0.00 | 290.83 |
September | 342.17 | 0.64 | 0.61 | 01-SEP-06:00 | 669.95 | 0.00 | 0.00 | 299.50 | 404.52 | 0.00 | 0.00 | 222.67 |
October | 330.00 | 0.64 | 0.61 | 01-OCT-07:19 | 567.98 | 0.00 | 0.00 | 277.00 | 368.40 | 0.00 | 0.00 | 196.50 |
November | 308.00 | 0.67 | 0.61 | 01-NOV-08:39 | 404.85 | 0.00 | 0.00 | 196.00 | 282.02 | 0.00 | 0.00 | 76.67 |
December | 282.83 | 0.67 | 0.61 | 01-DEC-08:30 | 393.27 | 0.00 | 0.00 | 184.83 | 274.42 | 0.00 | 0.00 | 53.00 |
Annual Sum or Average | 4027.67 | 0.65 | 648.89 | 0.00 | 0.00 | 3368.83 | 400.95 | 0.00 | 0.00 | 2390.17 | ||
Minimum of Months | 282.83 | 0.63 | 0.61 | 393.27 | 0.00 | 0.00 | 184.83 | 273.17 | 0.00 | 0.00 | 53.00 | |
Maximum of Months | 394.00 | 0.68 | 0.61 | 940.41 | 0.00 | 0.00 | 363.33 | 525.54 | 0.00 | 0.00 | 325.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.66 | 0.61 | 01-JAN-08:50 | 1762.61 | 15.43 | 82.67 | 244.67 | 1058.19 | 17.44 | 80.50 | 189.83 |
February | 295.50 | 0.65 | 0.61 | 01-FEB-11:39 | 1418.97 | 12.87 | 51.33 | 244.67 | 843.36 | 14.92 | 50.00 | 206.17 |
March | 296.00 | 0.64 | 0.61 | 02-MAR-12:39 | 1739.17 | 11.94 | 45.33 | 288.00 | 892.68 | 10.81 | 0.00 | 230.50 |
April | 347.33 | 0.65 | 0.61 | 01-APR-07:49 | 1935.91 | 8.27 | 0.00 | 305.50 | 1059.02 | 10.65 | 0.00 | 267.50 |
May | 353.67 | 0.64 | 0.61 | 01-MAY-07:30 | 1580.16 | 8.85 | 0.00 | 333.33 | 881.93 | 11.18 | 0.00 | 281.50 |
June | 394.00 | 0.64 | 0.61 | 01-JUN-06:00 | 1680.88 | 8.86 | 0.00 | 338.50 | 727.67 | 11.09 | 0.00 | 289.33 |
July | 390.00 | 0.64 | 0.61 | 01-JUL-06:49 | 1554.11 | 9.24 | 0.00 | 345.83 | 710.05 | 11.36 | 0.00 | 290.67 |
August | 380.83 | 0.64 | 0.61 | 01-AUG-07:10 | 1606.49 | 9.32 | 0.00 | 330.83 | 864.27 | 11.44 | 0.00 | 283.50 |
September | 342.17 | 0.64 | 0.61 | 01-SEP-07:30 | 1507.59 | 9.45 | 5.50 | 295.50 | 773.87 | 11.23 | 0.00 | 249.67 |
October | 330.00 | 0.63 | 0.61 | 01-OCT-07:40 | 1919.49 | 15.46 | 83.17 | 286.83 | 803.67 | 12.36 | 7.00 | 244.17 |
November | 308.00 | 0.65 | 0.61 | 01-NOV-08:00 | 1561.84 | 15.13 | 79.50 | 240.83 | 821.33 | 14.67 | 50.67 | 189.33 |
December | 282.83 | 0.65 | 0.61 | 01-DEC-08:39 | 1678.52 | 16.74 | 84.83 | 242.17 | 880.77 | 15.89 | 55.83 | 178.83 |
Annual Sum or Average | 4027.67 | 0.64 | 1661.58 | 11.54 | 432.33 | 3496.67 | 854.90 | 12.59 | 244.00 | 2901.00 | ||
Minimum of Months | 282.83 | 0.63 | 0.61 | 1418.97 | 8.27 | 0.00 | 240.83 | 710.05 | 10.65 | 0.00 | 178.83 | |
Maximum of Months | 394.00 | 0.66 | 0.61 | 1935.91 | 16.74 | 84.83 | 345.83 | 1059.02 | 17.44 | 80.50 | 290.67 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 73616678.49 | 14292.01 | 05-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 34311161.85 | 13105.10 | 17-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 26985485.57 | 12386.10 | 09-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 45546390.94 | 15646.13 | 18-APR-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 240.64 | 0.25 | 27-OCT-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 3342.80 | 14.57 | 05-NOV-16:27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 31006491.88 | 14684.33 | 21-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.211470E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 73616678.49 | 15646.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 1247208.14 | 314.94 | 05-JAN-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1247208.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1247208.14 | 314.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 2893907.14 | 810.79 | 05-JAN-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 58743.04 | 97.91 | 06-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6906973.45 | 1828.68 | 21-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 9859623.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6906973.45 | 1828.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 376650.20 | 484.24 | 21-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 424832.96 | 346.69 | 06-FEB-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1229523.18 | 538.83 | 20-DEC-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2031006.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1229523.18 | 538.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.160286E+10 | 165263.11 | 04-JAN-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.781001E+09 | 150964.81 | 17-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.631684E+09 | 150058.89 | 09-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.118713E+09 | 52316.77 | 18-APR-14:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1960.52 | 3.27 | 17-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 26889846.40 | 18590.95 | 27-NOV-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.108309E+10 | 174130.95 | 21-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.424424E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.160286E+10 | 174130.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.365185E+10 | 138362.26 | 04-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.183058E+10 | 136868.50 | 17-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.124294E+10 | 138329.67 | 09-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 18542076.21 | 9071.59 | 16-NOV-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.221914E+10 | 136043.31 | 23-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.896305E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.365185E+10 | 138362.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.153425E+10 | 121392.01 | 05-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.689780E+09 | 117558.40 | 06-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.846056E+09 | 88687.96 | 11-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 2060122.62 | 2704.56 | 16-NOV-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129239E+10 | 120131.52 | 20-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.436455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.153425E+10 | 121392.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.435735E+09 | 150830.02 | 10-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.241320E+09 | 150855.54 | 06-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.592079E+09 | 65145.39 | 11-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.526566E+09 | 154237.29 | 20-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.179570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.592079E+09 | 154237.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.120659E+10 | 115954.71 | 05-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.556624E+09 | 112183.05 | 06-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.524121E+09 | 40252.86 | 11-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.629063E+09 | 114739.15 | 20-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.291640E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.120659E+10 | 115954.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.128761E+09 | 21393.84 | 05-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 50788732.52 | 19804.16 | 17-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 43773498.48 | 19868.95 | 09-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 10379427.72 | 3416.92 | 18-APR-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 247329.35 | 148.48 | 28-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5787500.76 | 5152.16 | 15-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 69263721.09 | 22713.15 | 21-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.309001E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.128761E+09 | 22713.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.200109E+09 | 67620.34 | 23-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.351065E+09 | 68600.34 | 06-FEB-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.136800E+09 | 67370.36 | 13-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 53527624.84 | 34286.47 | 21-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.741502E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.351065E+09 | 68600.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.171152E+10 | 14512.01 | 23-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.955808E+09 | 14439.26 | 06-FEB-06:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.594658E+09 | 14448.74 | 13-MAR-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 2600002.75 | 485.88 | 03-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 12526897.90 | 1290.10 | 28-OCT-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.116399E+09 | 14406.84 | 24-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.108454E+10 | 14453.25 | 05-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.447805E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.171152E+10 | 14512.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.698628E+09 | 13854.68 | 05-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.384120E+09 | 13800.49 | 06-FEB-05:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.337092E+09 | 13722.30 | 10-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5513041.28 | 989.64 | 28-OCT-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 39120330.47 | 13528.79 | 16-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.578284E+09 | 13854.72 | 21-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.204276E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.698628E+09 | 13854.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.505116E+09 | 17223.05 | 09-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.314837E+09 | 17190.14 | 06-FEB-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.369572E+09 | 17201.29 | 13-MAR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 264006.07 | 211.27 | 28-OCT-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6205328.53 | 1631.59 | 16-NOV-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364691E+09 | 17193.78 | 30-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.156069E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.505116E+09 | 17223.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.697370E+09 | 14134.12 | 05-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.363108E+09 | 14088.37 | 06-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.262433E+09 | 13950.99 | 09-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 2015415.22 | 394.37 | 28-OCT-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 30235777.77 | 5346.06 | 16-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.426811E+09 | 14165.34 | 21-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.178197E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.697370E+09 | 14165.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS HEATING COIL
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT HEATING COIL
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT HEATING COIL
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID HEATING COIL
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP HEATING COIL
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID_SUPPHEATCOIL
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.342391E+11 | 0.265937E+11 | 168799.79 | 19-JAN-06:03 | 116493.73 | 0.23 |
February | 0.00 | 0.00 | 0.488738E+11 | 0.366752E+11 | 180386.99 | 28-FEB-06:02 | 72370.12 | 0.38 |
March | 0.00 | 0.00 | 0.651581E+11 | 0.542407E+11 | 208959.66 | 07-MAR-06:02 | 145354.89 | 0.38 |
April | 0.00 | 0.00 | 0.109851E+12 | 0.928891E+11 | 206446.93 | 29-APR-05:02 | 144850.01 | 0.69 |
May | 0.00 | 0.00 | 0.150401E+12 | 0.122674E+12 | 232449.88 | 24-MAY-03:02 | 142643.92 | 0.73 |
June | 0.00 | 0.00 | 0.162738E+12 | 0.134790E+12 | 220574.81 | 28-JUN-05:02 | 153773.02 | 0.82 |
July | 0.00 | 0.00 | 0.176160E+12 | 0.143564E+12 | 223397.89 | 03-JUL-05:02 | 153972.99 | 0.85 |
August | 0.00 | 0.00 | 0.193773E+12 | 0.159654E+12 | 224764.42 | 21-AUG-05:03 | 158800.86 | 0.88 |
September | 0.00 | 0.00 | 0.149166E+12 | 0.115876E+12 | 229700.99 | 05-SEP-03:02 | 150011.52 | 0.73 |
October | 0.00 | 0.00 | 0.137372E+12 | 0.113254E+12 | 221490.55 | 06-OCT-05:02 | 150186.54 | 0.67 |
November | 0.00 | 0.00 | 0.805258E+11 | 0.678669E+11 | 208890.27 | 02-NOV-05:02 | 146522.41 | 0.50 |
December | 0.00 | 0.00 | 0.590780E+11 | 0.483666E+11 | 208236.56 | 16-DEC-06:02 | 144651.25 | 0.36 |
Annual Sum or Average | 0.00 | 0.00 | 0.136734E+13 | 0.111644E+13 | 0.60 | |||
Minimum of Months | 0.00 | 0.00 | 0.342391E+11 | 0.265937E+11 | 168799.79 | 72370.12 | 0.23 | |
Maximum of Months | 0.00 | 0.00 | 0.193773E+12 | 0.159654E+12 | 232449.88 | 158800.86 | 0.88 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.267454E+12 | 0.202814E+12 | 1454570.34 | 19-JAN-06:03 | 529668.76 | 0.21 |
February | 0.00 | 0.00 | 0.378432E+12 | 0.278911E+12 | 1515309.23 | 28-FEB-06:02 | 607455.15 | 0.35 |
March | 0.00 | 0.00 | 0.479486E+12 | 0.384419E+12 | 2053829.77 | 07-MAR-06:02 | 1309335.07 | 0.33 |
April | 0.00 | 0.00 | 0.794848E+12 | 0.645535E+12 | 2047377.13 | 26-APR-05:03 | 1346779.57 | 0.51 |
May | 0.00 | 0.00 | 0.135751E+13 | 0.106824E+13 | 2591312.84 | 22-MAY-03:02 | 1384820.44 | 0.67 |
June | 0.00 | 0.00 | 0.139215E+13 | 0.110351E+13 | 2177070.60 | 19-JUN-03:02 | 1391219.91 | 0.70 |
July | 0.00 | 0.00 | 0.143176E+13 | 0.108864E+13 | 2254851.86 | 26-JUL-05:03 | 1398748.05 | 0.70 |
August | 0.00 | 0.00 | 0.148707E+13 | 0.113376E+13 | 2404068.81 | 15-AUG-03:02 | 1387955.00 | 0.69 |
September | 0.00 | 0.00 | 0.131486E+13 | 0.967551E+12 | 2751506.84 | 05-SEP-03:02 | 1318266.43 | 0.67 |
October | 0.00 | 0.00 | 0.113814E+13 | 0.887973E+12 | 2282805.22 | 07-OCT-03:02 | 1383667.02 | 0.57 |
November | 0.00 | 0.00 | 0.606307E+12 | 0.491463E+12 | 2124444.42 | 01-NOV-05:03 | 1341207.78 | 0.43 |
December | 0.00 | 0.00 | 0.412523E+12 | 0.317558E+12 | 2076060.99 | 15-DEC-06:02 | 1325051.51 | 0.28 |
Annual Sum or Average | 0.00 | 0.00 | 0.110606E+14 | 0.857037E+13 | 0.51 | |||
Minimum of Months | 0.00 | 0.00 | 0.267454E+12 | 0.202814E+12 | 1454570.34 | 529668.76 | 0.21 | |
Maximum of Months | 0.00 | 0.00 | 0.148707E+13 | 0.113376E+13 | 2751506.84 | 1398748.05 | 0.70 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.257704E+11 | 0.192649E+11 | 143803.00 | 19-JAN-06:03 | 87545.09 | 0.20 |
February | 0.00 | 0.00 | 0.378887E+11 | 0.281386E+11 | 139287.12 | 28-FEB-06:02 | 55756.47 | 0.34 |
March | 0.00 | 0.00 | 0.493188E+11 | 0.395297E+11 | 195943.60 | 27-MAR-05:02 | 85343.94 | 0.32 |
April | 0.00 | 0.00 | 0.847841E+11 | 0.696855E+11 | 220697.29 | 29-APR-05:02 | 140539.13 | 0.50 |
May | 0.00 | 0.00 | 0.150982E+12 | 0.120857E+12 | 265803.82 | 22-MAY-03:02 | 153948.02 | 0.68 |
June | 0.00 | 0.00 | 0.157677E+12 | 0.127809E+12 | 243274.61 | 30-JUN-03:02 | 152399.39 | 0.71 |
July | 0.00 | 0.00 | 0.162030E+12 | 0.126017E+12 | 251496.59 | 26-JUL-03:02 | 153917.38 | 0.72 |
August | 0.00 | 0.00 | 0.165969E+12 | 0.129198E+12 | 259936.57 | 11-AUG-03:02 | 147958.41 | 0.71 |
September | 0.00 | 0.00 | 0.142064E+12 | 0.106046E+12 | 296074.12 | 05-SEP-03:02 | 140557.56 | 0.67 |
October | 0.00 | 0.00 | 0.122309E+12 | 0.966161E+11 | 256083.09 | 25-OCT-03:02 | 153030.58 | 0.57 |
November | 0.00 | 0.00 | 0.594080E+11 | 0.482725E+11 | 218228.23 | 02-NOV-05:02 | 140363.44 | 0.42 |
December | 0.00 | 0.00 | 0.397464E+11 | 0.302889E+11 | 183256.79 | 15-DEC-06:02 | 113090.48 | 0.27 |
Annual Sum or Average | 0.00 | 0.00 | 0.119795E+13 | 0.941723E+12 | 0.51 | |||
Minimum of Months | 0.00 | 0.00 | 0.257704E+11 | 0.192649E+11 | 139287.12 | 55756.47 | 0.20 | |
Maximum of Months | 0.00 | 0.00 | 0.165969E+12 | 0.129198E+12 | 296074.12 | 153948.02 | 0.72 |
Report: CoilReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.218968E+11 | 0.169084E+11 | 119639.89 | 01-JAN-16:12 | 98091.48 | 0.16 |
February | 0.00 | 0.00 | 0.263542E+11 | 0.215636E+11 | 109905.30 | 03-FEB-06:03 | 42174.88 | 0.27 |
March | 0.00 | 0.00 | 0.354979E+11 | 0.300986E+11 | 139139.19 | 07-MAR-04:03 | 86073.13 | 0.25 |
April | 0.00 | 0.00 | 0.562278E+11 | 0.488070E+11 | 141680.75 | 29-APR-04:03 | 83502.45 | 0.44 |
May | 0.00 | 0.00 | 0.103677E+12 | 0.800205E+11 | 173131.55 | 22-MAY-03:02 | 79669.10 | 0.59 |
June | 0.00 | 0.00 | 0.108815E+12 | 0.815867E+11 | 172825.55 | 19-JUN-03:02 | 87580.28 | 0.60 |
July | 0.00 | 0.00 | 0.117942E+12 | 0.834478E+11 | 160889.34 | 17-JUL-03:02 | 87119.64 | 0.58 |
August | 0.00 | 0.00 | 0.130714E+12 | 0.949890E+11 | 169304.83 | 06-AUG-14:12 | 87136.56 | 0.64 |
September | 0.00 | 0.00 | 0.110906E+12 | 0.810925E+11 | 169974.94 | 17-SEP-14:20 | 85360.28 | 0.62 |
October | 0.00 | 0.00 | 0.953928E+11 | 0.734004E+11 | 168365.14 | 08-OCT-14:58 | 86783.60 | 0.52 |
November | 0.00 | 0.00 | 0.523303E+11 | 0.433700E+11 | 143605.32 | 03-NOV-03:02 | 87453.91 | 0.37 |
December | 0.00 | 0.00 | 0.342941E+11 | 0.277316E+11 | 137277.76 | 10-DEC-15:20 | 95889.66 | 0.24 |
Annual Sum or Average | 0.00 | 0.00 | 0.894049E+12 | 0.683016E+12 | 0.44 | |||
Minimum of Months | 0.00 | 0.00 | 0.218968E+11 | 0.169084E+11 | 109905.30 | 42174.88 | 0.16 | |
Maximum of Months | 0.00 | 0.00 | 0.130714E+12 | 0.949890E+11 | 173131.55 | 98091.48 | 0.64 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.331718E+12 | 0.329000E+12 | 136409.24 | 31-JAN-16:40 | 126594.14 | 0.00 |
February | 0.00 | 0.00 | 0.522753E+12 | 0.517891E+12 | 227508.79 | 24-FEB-16:50 | 217934.04 | 0.00 |
March | 0.00 | 0.00 | 0.823430E+12 | 0.818567E+12 | 393952.00 | 31-MAR-24:00 | 393952.00 | 0.00 |
April | 0.00 | 0.00 | 0.103628E+13 | 0.103012E+13 | 422269.30 | 28-APR-18:00 | 403790.18 | 0.00 |
May | 0.00 | 0.00 | 0.349000E+12 | 0.336384E+12 | 212762.30 | 31-MAY-23:10 | 210450.49 | 0.00 |
June | 0.00 | 0.00 | 0.576229E+12 | 0.562358E+12 | 302726.56 | 30-JUN-23:03 | 302021.96 | 0.00 |
July | 0.00 | 0.00 | 0.842408E+12 | 0.827501E+12 | 395008.21 | 31-JUL-23:53 | 395008.21 | 0.00 |
August | 0.00 | 0.00 | 0.108075E+13 | 0.106732E+13 | 424437.60 | 07-AUG-14:00 | 403726.71 | 0.00 |
September | 0.00 | 0.00 | 0.342098E+12 | 0.328554E+12 | 213274.21 | 30-SEP-24:00 | 212005.73 | 0.00 |
October | 0.00 | 0.00 | 0.593623E+12 | 0.582774E+12 | 304073.58 | 31-OCT-24:00 | 304073.58 | 0.00 |
November | 0.00 | 0.00 | 0.804250E+12 | 0.798245E+12 | 324540.11 | 03-NOV-16:00 | 311897.23 | 0.00 |
December | 0.00 | 0.00 | 0.107079E+13 | 0.106704E+13 | 416142.25 | 13-DEC-18:00 | 403726.83 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.837333E+13 | 0.826575E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.331718E+12 | 0.328554E+12 | 136409.24 | 126594.14 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.108075E+13 | 0.106732E+13 | 424437.60 | 403790.18 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.522595E+10 | 0.511722E+10 | 2815.04 | 19-JAN-17:00 | 2453.19 | 0.00 |
February | 0.00 | 0.00 | 0.963334E+10 | 0.944020E+10 | 4743.07 | 27-FEB-17:00 | 4382.47 | 0.00 |
March | 0.00 | 0.00 | 0.158168E+11 | 0.156121E+11 | 7719.06 | 31-MAR-24:00 | 7719.06 | 0.00 |
April | 0.00 | 0.00 | 0.205463E+11 | 0.202581E+11 | 8661.28 | 28-APR-17:20 | 8122.95 | 0.00 |
May | 0.00 | 0.00 | 0.656738E+10 | 0.606268E+10 | 4098.04 | 31-MAY-23:10 | 3955.32 | 0.00 |
June | 0.00 | 0.00 | 0.113496E+11 | 0.107689E+11 | 5880.12 | 30-JUN-23:43 | 5866.48 | 0.00 |
July | 0.00 | 0.00 | 0.168360E+11 | 0.161843E+11 | 7743.94 | 31-JUL-23:57 | 7743.94 | 0.00 |
August | 0.00 | 0.00 | 0.219447E+11 | 0.212887E+11 | 8920.93 | 07-AUG-13:50 | 8181.00 | 0.00 |
September | 0.00 | 0.00 | 0.639852E+10 | 0.585585E+10 | 4072.46 | 30-SEP-24:00 | 4041.72 | 0.00 |
October | 0.00 | 0.00 | 0.115026E+11 | 0.110511E+11 | 5896.72 | 31-OCT-24:00 | 5888.35 | 0.00 |
November | 0.00 | 0.00 | 0.155902E+11 | 0.153395E+11 | 6812.59 | 07-NOV-16:40 | 6277.34 | 0.00 |
December | 0.00 | 0.00 | 0.208571E+11 | 0.206805E+11 | 8752.63 | 14-DEC-17:00 | 8285.41 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.162269E+12 | 0.157659E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.522595E+10 | 0.511722E+10 | 2815.04 | 2453.19 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.219447E+11 | 0.212887E+11 | 8920.93 | 8285.41 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.402077E+11 | 0.391491E+11 | 26479.92 | 19-JAN-17:00 | 22891.68 | 0.00 |
February | 0.00 | 0.00 | 0.845363E+11 | 0.826269E+11 | 45068.26 | 27-FEB-17:00 | 41487.15 | 0.00 |
March | 0.00 | 0.00 | 0.145211E+12 | 0.143172E+12 | 72714.50 | 31-MAR-24:00 | 72714.50 | 0.00 |
April | 0.00 | 0.00 | 0.195032E+12 | 0.192146E+12 | 82671.37 | 28-APR-17:20 | 77324.51 | 0.00 |
May | 0.00 | 0.00 | 0.616944E+11 | 0.566988E+11 | 38933.34 | 31-MAY-23:10 | 37406.82 | 0.00 |
June | 0.00 | 0.00 | 0.108247E+12 | 0.102466E+12 | 57115.28 | 30-JUN-23:53 | 56979.32 | 0.00 |
July | 0.00 | 0.00 | 0.160671E+12 | 0.154167E+12 | 74523.99 | 31-JUL-23:57 | 74523.99 | 0.00 |
August | 0.00 | 0.00 | 0.208488E+12 | 0.201930E+12 | 84741.14 | 07-AUG-13:50 | 77382.41 | 0.00 |
September | 0.00 | 0.00 | 0.592091E+11 | 0.538525E+11 | 38398.57 | 30-SEP-24:00 | 38082.00 | 0.00 |
October | 0.00 | 0.00 | 0.107970E+12 | 0.103480E+12 | 55315.74 | 31-OCT-24:00 | 55208.91 | 0.00 |
November | 0.00 | 0.00 | 0.144059E+12 | 0.141564E+12 | 64978.12 | 07-NOV-16:40 | 59646.44 | 0.00 |
December | 0.00 | 0.00 | 0.191363E+12 | 0.189594E+12 | 83141.25 | 14-DEC-17:00 | 78477.30 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.150669E+13 | 0.146085E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.402077E+11 | 0.391491E+11 | 26479.92 | 22891.68 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.208488E+12 | 0.201930E+12 | 84741.14 | 78477.30 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.298188E+10 | 0.287757E+10 | 2716.01 | 19-JAN-17:00 | 2356.05 | 0.00 |
February | 0.00 | 0.00 | 0.771631E+10 | 0.752664E+10 | 4565.92 | 27-FEB-17:00 | 4207.69 | 0.00 |
March | 0.00 | 0.00 | 0.140046E+11 | 0.138013E+11 | 7177.44 | 31-MAR-24:00 | 7177.44 | 0.00 |
April | 0.00 | 0.00 | 0.194033E+11 | 0.191153E+11 | 8367.72 | 28-APR-17:20 | 7829.91 | 0.00 |
May | 0.00 | 0.00 | 0.630387E+10 | 0.580248E+10 | 3872.97 | 31-MAY-23:10 | 3719.37 | 0.00 |
June | 0.00 | 0.00 | 0.109690E+11 | 0.103903E+11 | 5751.01 | 30-JUN-23:53 | 5737.35 | 0.00 |
July | 0.00 | 0.00 | 0.162259E+11 | 0.155756E+11 | 7445.64 | 31-JUL-23:57 | 7445.64 | 0.00 |
August | 0.00 | 0.00 | 0.209977E+11 | 0.203413E+11 | 8559.26 | 14-AUG-16:00 | 7894.47 | 0.00 |
September | 0.00 | 0.00 | 0.603300E+10 | 0.549586E+10 | 3891.55 | 30-SEP-24:00 | 3860.50 | 0.00 |
October | 0.00 | 0.00 | 0.107689E+11 | 0.103200E+11 | 5484.20 | 31-OCT-24:00 | 5472.80 | 0.00 |
November | 0.00 | 0.00 | 0.139793E+11 | 0.137308E+11 | 6558.31 | 07-NOV-16:40 | 6024.84 | 0.00 |
December | 0.00 | 0.00 | 0.183680E+11 | 0.181916E+11 | 8371.61 | 14-DEC-17:00 | 7905.30 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.147752E+12 | 0.143169E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.298188E+10 | 0.287757E+10 | 2716.01 | 2356.05 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.209977E+11 | 0.203413E+11 | 8559.26 | 7905.30 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 4536.50 | 835681.10 | 10-JAN-06:02 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 2685.40 | 846264.83 | 06-FEB-06:01 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 2101.45 | 580033.84 | 11-MAR-06:03 |
April | 0.00 | 0.00 | 01-APR-00:10 | 86.08 | 45413.30 | 18-APR-14:30 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 2.82 | 1092.29 | 28-OCT-06:40 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 72.94 | 44092.98 | 27-NOV-14:20 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 3073.08 | 852257.95 | 21-DEC-06:01 |
Annual Sum or Average | 0.00 | 1044.08 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 4536.50 | 852257.95 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 222199.35 | 1776720.36 | 19-JAN-06:03 | 0.97 | 17378.04 | 01-JAN-05:23 |
February | 336658.15 | 1712163.92 | 24-FEB-13:10 | 1.00 | 12086.88 | 26-FEB-09:23 |
March | 390658.08 | 2302650.67 | 07-MAR-06:04 | 34.33 | 183171.99 | 19-MAR-08:13 |
April | 647032.32 | 2593334.71 | 29-APR-05:02 | 0.05 | 781.84 | 09-APR-23:33 |
May | 940377.28 | 3141983.77 | 24-MAY-05:03 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 977051.04 | 2843070.04 | 08-JUN-05:04 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 972937.46 | 3289953.98 | 31-JUL-05:04 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 994884.68 | 2901200.29 | 01-AUG-05:04 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 938046.35 | 2963436.30 | 13-SEP-05:03 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 798755.53 | 3032100.65 | 20-OCT-05:04 | 2.46 | 28471.76 | 29-OCT-19:33 |
November | 505261.07 | 2678073.48 | 02-NOV-05:02 | 15.81 | 84048.06 | 19-NOV-18:53 |
December | 336297.72 | 2756609.21 | 15-DEC-06:04 | 4.69 | 44427.22 | 31-DEC-21:13 |
Annual Sum or Average | 673390.59 | 4.98 | ||||
Minimum of Months | 222199.35 | 1712163.92 | 0.00 | 0.00 | ||
Maximum of Months | 994884.68 | 3289953.98 | 34.33 | 183171.99 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 159967.97 | 3193301.15 | 19-JAN-06:03 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 251897.80 | 3482738.19 | 28-FEB-06:02 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 283276.52 | 4125445.37 | 07-MAR-06:02 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 476826.81 | 4130577.91 | 29-APR-05:02 | 0.00 | 0.00 | 01-APR-00:10 |
May | 748842.17 | 4362661.83 | 10-MAY-05:02 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 785753.50 | 4230109.91 | 08-JUN-05:02 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 774027.55 | 4281972.98 | 31-JUL-05:02 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 813379.75 | 4341884.70 | 07-AUG-05:02 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 750530.31 | 4710341.63 | 05-SEP-03:02 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 633304.96 | 4343121.36 | 11-OCT-05:02 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 372531.03 | 4193746.16 | 02-NOV-05:02 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 248841.98 | 4262561.13 | 15-DEC-06:02 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 526392.48 | 0.00 | ||||
Minimum of Months | 159967.97 | 3193301.15 | 0.00 | 0.00 | ||
Maximum of Months | 813379.75 | 4710341.63 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 244437.57 | 744419.59 | 02-JAN-15:00 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 450640.28 | 1035948.96 | 02-FEB-13:10 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 687278.79 | 1336119.03 | 30-MAR-13:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 1069279.24 | 1758685.33 | 28-APR-15:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 737325.01 | 1101891.63 | 18-MAY-16:00 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 999142.31 | 1425474.56 | 14-JUN-14:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 1243310.74 | 1739962.02 | 21-JUL-16:00 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 1431570.18 | 1911302.02 | 30-AUG-16:10 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 705062.85 | 1264988.73 | 09-SEP-17:00 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 819014.29 | 1376855.99 | 05-OCT-15:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 757228.59 | 1382792.26 | 02-NOV-13:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 832637.59 | 1575232.05 | 13-DEC-15:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 833978.40 | 0.00 | ||||
Minimum of Months | 244437.57 | 744419.59 | 0.00 | 0.00 | ||
Maximum of Months | 1431570.18 | 1911302.02 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 12872.40 | 42424.01 | 25-JAN-12:40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 12848.26 | 42362.61 | 01-FEB-12:30 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 13094.26 | 41421.46 | 01-MAR-12:50 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11687.11 | 39162.13 | 03-APR-12:00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 11287.80 | 36776.47 | 01-MAY-11:20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 10898.83 | 34320.97 | 01-JUN-11:40 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 9869.12 | 32682.26 | 03-JUL-11:40 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 10767.89 | 33345.93 | 31-AUG-11:40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 10638.63 | 35304.02 | 29-SEP-11:50 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 11291.04 | 38011.11 | 31-OCT-11:40 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12157.86 | 40419.46 | 30-NOV-12:30 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12325.05 | 41967.03 | 29-DEC-12:50 |
Annual Sum or Average | 0.00 | 11638.24 | ||||
Minimum of Months | 0.00 | 0.00 | 9869.12 | 32682.26 | ||
Maximum of Months | 0.00 | 0.00 | 13094.26 | 42424.01 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 180137.24 | 3674544.78 | 19-JAN-12:00 | 1943.88 | 190590.83 | 21-JAN-11:30 |
February | 272230.40 | 3580410.81 | 24-FEB-13:20 | 1130.59 | 181561.35 | 17-FEB-07:50 |
March | 334616.96 | 4098203.56 | 07-MAR-11:30 | 1586.49 | 188773.57 | 09-MAR-11:00 |
April | 664928.68 | 5615019.25 | 28-APR-16:00 | 793.97 | 132029.93 | 10-APR-08:20 |
May | 1864149.01 | 6067390.26 | 24-MAY-05:05 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 2175860.82 | 6239731.25 | 28-JUN-14:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 2554553.19 | 6519640.34 | 12-JUL-10:10 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 2467901.48 | 6453960.77 | 14-AUG-11:00 | 0.44 | 3948.61 | 20-AUG-04:40 |
September | 1987138.32 | 6451798.07 | 18-SEP-14:00 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 1497200.70 | 6692347.80 | 24-OCT-13:30 | 334.79 | 119709.13 | 27-OCT-17:50 |
November | 590867.10 | 5428491.22 | 01-NOV-14:00 | 1535.17 | 154065.82 | 22-NOV-09:50 |
December | 350792.14 | 5083777.27 | 12-DEC-14:20 | 1759.05 | 182682.84 | 20-DEC-15:30 |
Annual Sum or Average | 1251825.12 | 755.88 | ||||
Minimum of Months | 180137.24 | 3580410.81 | 0.00 | 0.00 | ||
Maximum of Months | 2554553.19 | 6692347.80 | 1943.88 | 190590.83 |
Report: FanReportMonthly
For: CAV_BAS FAN
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.151143E+11 | 0.84 | 9290.26 | 01-JAN-00:20 | 1.37 |
February | 0.132172E+11 | 0.81 | 9290.26 | 01-FEB-04:03 | 1.38 |
March | 0.151784E+11 | 0.84 | 9290.26 | 01-MAR-04:03 | 1.38 |
April | 0.138852E+11 | 0.79 | 9290.26 | 01-APR-03:02 | 1.38 |
May | 0.149819E+11 | 0.83 | 9290.26 | 01-MAY-03:02 | 1.38 |
June | 0.146433E+11 | 0.83 | 9290.26 | 01-JUN-03:02 | 1.38 |
July | 0.147184E+11 | 0.81 | 9290.26 | 01-JUL-03:02 | 1.38 |
August | 0.162706E+11 | 0.90 | 9290.26 | 01-AUG-03:03 | 1.38 |
September | 0.153983E+11 | 0.88 | 9290.26 | 01-SEP-03:02 | 1.38 |
October | 0.158403E+11 | 0.88 | 9290.26 | 01-OCT-13:16 | 1.37 |
November | 0.153407E+11 | 0.88 | 9290.26 | 01-NOV-03:05 | 1.37 |
December | 0.153907E+11 | 0.86 | 9290.26 | 01-DEC-04:03 | 1.39 |
Annual Sum or Average | 0.179979E+12 | 0.85 | |||
Minimum of Months | 0.132172E+11 | 0.79 | 9290.26 | 1.37 | |
Maximum of Months | 0.162706E+11 | 0.90 | 9290.26 | 1.39 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.592536E+10 | 0.39 | 19314.86 | 02-JAN-06:02 | 1.76 |
February | 0.620593E+10 | 0.43 | 19254.93 | 27-FEB-06:02 | 1.76 |
March | 0.839646E+10 | 0.50 | 19314.86 | 27-MAR-05:02 | 1.76 |
April | 0.102676E+11 | 0.60 | 19314.86 | 18-APR-12:05 | 1.76 |
May | 0.105108E+11 | 0.58 | 19314.86 | 01-MAY-05:02 | 1.76 |
June | 0.117660E+11 | 0.66 | 19314.86 | 08-JUN-05:02 | 1.76 |
July | 0.125788E+11 | 0.68 | 19314.86 | 06-JUL-05:03 | 1.76 |
August | 0.150613E+11 | 0.76 | 19314.86 | 02-AUG-05:02 | 1.76 |
September | 0.980537E+10 | 0.57 | 19314.86 | 05-SEP-03:02 | 1.76 |
October | 0.101668E+11 | 0.57 | 19314.86 | 03-OCT-05:02 | 1.76 |
November | 0.857445E+10 | 0.51 | 19314.86 | 02-NOV-05:02 | 1.76 |
December | 0.781333E+10 | 0.48 | 19314.86 | 12-DEC-06:02 | 1.76 |
Annual Sum or Average | 0.117072E+12 | 0.56 | |||
Minimum of Months | 0.592536E+10 | 0.39 | 19254.93 | 1.76 | |
Maximum of Months | 0.150613E+11 | 0.76 | 19314.86 | 1.76 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.406986E+11 | 0.33 | 128434.74 | 02-JAN-06:02 | 1.43 |
February | 0.404960E+11 | 0.35 | 140524.93 | 28-FEB-06:02 | 1.51 |
March | 0.521199E+11 | 0.39 | 178679.99 | 27-MAR-05:02 | 1.76 |
April | 0.639477E+11 | 0.43 | 178679.99 | 18-APR-14:40 | 1.77 |
May | 0.928688E+11 | 0.54 | 178679.99 | 01-MAY-05:02 | 1.76 |
June | 0.956132E+11 | 0.57 | 178679.99 | 01-JUN-05:03 | 1.76 |
July | 0.905658E+11 | 0.54 | 178679.99 | 03-JUL-05:02 | 1.76 |
August | 0.985827E+11 | 0.57 | 178679.99 | 01-AUG-05:02 | 1.76 |
September | 0.797594E+11 | 0.51 | 178679.99 | 01-SEP-05:03 | 1.76 |
October | 0.744310E+11 | 0.47 | 178679.99 | 05-OCT-03:02 | 1.76 |
November | 0.522700E+11 | 0.39 | 178679.99 | 01-NOV-05:03 | 1.76 |
December | 0.431209E+11 | 0.34 | 178679.99 | 15-DEC-06:02 | 1.76 |
Annual Sum or Average | 0.824474E+12 | 0.45 | |||
Minimum of Months | 0.404960E+11 | 0.33 | 128434.74 | 1.43 | |
Maximum of Months | 0.985827E+11 | 0.57 | 178679.99 | 1.77 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.341808E+10 | 0.31 | 10153.34 | 02-JAN-06:02 | 1.17 |
February | 0.370760E+10 | 0.33 | 12319.46 | 27-FEB-06:02 | 1.32 |
March | 0.467302E+10 | 0.36 | 18520.59 | 27-MAR-05:02 | 1.71 |
April | 0.627882E+10 | 0.41 | 19301.94 | 18-APR-14:20 | 1.77 |
May | 0.102022E+11 | 0.55 | 19301.94 | 04-MAY-05:02 | 1.76 |
June | 0.108801E+11 | 0.59 | 19301.94 | 12-JUN-05:02 | 1.76 |
July | 0.103120E+11 | 0.57 | 19301.94 | 01-JUL-05:03 | 1.76 |
August | 0.109654E+11 | 0.58 | 19301.94 | 01-AUG-05:02 | 1.76 |
September | 0.837518E+10 | 0.50 | 19301.94 | 01-SEP-05:03 | 1.76 |
October | 0.777843E+10 | 0.46 | 19301.94 | 06-OCT-05:02 | 1.76 |
November | 0.461798E+10 | 0.35 | 19301.94 | 02-NOV-05:02 | 1.76 |
December | 0.371020E+10 | 0.31 | 11396.30 | 15-DEC-06:02 | 1.26 |
Annual Sum or Average | 0.849189E+11 | 0.44 | |||
Minimum of Months | 0.341808E+10 | 0.31 | 10153.34 | 1.17 | |
Maximum of Months | 0.109654E+11 | 0.59 | 19301.94 | 1.77 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BASEMENT SUPPLY FAN
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.947342E+11 | 1.35 | 35369.70 | 01-JAN-00:10 | 1.35 |
February | 0.855664E+11 | 1.35 | 35369.70 | 01-FEB-00:10 | 1.35 |
March | 0.947342E+11 | 1.35 | 35369.70 | 01-MAR-00:10 | 1.35 |
April | 0.916783E+11 | 1.35 | 35369.70 | 01-APR-00:10 | 1.35 |
May | 0.947342E+11 | 1.35 | 35369.70 | 01-MAY-00:05 | 1.35 |
June | 0.916783E+11 | 1.35 | 35369.70 | 01-JUN-00:10 | 1.35 |
July | 0.947342E+11 | 1.35 | 35369.70 | 01-JUL-00:03 | 1.35 |
August | 0.947342E+11 | 1.35 | 35369.70 | 01-AUG-00:03 | 1.35 |
September | 0.916783E+11 | 1.35 | 35369.70 | 01-SEP-00:10 | 1.35 |
October | 0.947342E+11 | 1.35 | 35369.70 | 01-OCT-00:10 | 1.35 |
November | 0.916783E+11 | 1.35 | 35369.70 | 01-NOV-00:10 | 1.35 |
December | 0.947342E+11 | 1.35 | 35369.70 | 01-DEC-00:10 | 1.35 |
Annual Sum or Average | 0.111542E+13 | 1.35 | |||
Minimum of Months | 0.855664E+11 | 1.35 | 35369.70 | 1.35 | |
Maximum of Months | 0.947342E+11 | 1.35 | 35369.70 | 1.35 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BOT SUPPLY FAN
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.139709E+10 | 0.91 | 521.61 | 01-JAN-00:05 | 0.91 |
February | 0.126188E+10 | 0.91 | 521.61 | 01-FEB-00:10 | 0.91 |
March | 0.139709E+10 | 0.91 | 521.61 | 01-MAR-00:10 | 0.91 |
April | 0.135202E+10 | 0.91 | 521.61 | 01-APR-00:10 | 0.91 |
May | 0.139709E+10 | 0.91 | 521.61 | 01-MAY-00:10 | 0.91 |
June | 0.135202E+10 | 0.91 | 521.61 | 01-JUN-00:10 | 0.91 |
July | 0.139709E+10 | 0.91 | 521.61 | 01-JUL-00:03 | 0.91 |
August | 0.139709E+10 | 0.91 | 521.61 | 01-AUG-00:03 | 0.91 |
September | 0.135202E+10 | 0.91 | 521.61 | 01-SEP-00:05 | 0.91 |
October | 0.139709E+10 | 0.91 | 521.61 | 01-OCT-00:20 | 0.91 |
November | 0.135202E+10 | 0.91 | 521.61 | 01-NOV-00:10 | 0.91 |
December | 0.139709E+10 | 0.91 | 521.61 | 01-DEC-00:10 | 0.91 |
Annual Sum or Average | 0.164496E+11 | 0.91 | |||
Minimum of Months | 0.126188E+10 | 0.91 | 521.61 | 0.91 | |
Maximum of Months | 0.139709E+10 | 0.91 | 521.61 | 0.91 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER MID SUPPLY FAN
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.132773E+11 | 0.91 | 4957.19 | 01-JAN-00:05 | 0.91 |
February | 0.119924E+11 | 0.91 | 4957.19 | 01-FEB-00:10 | 0.91 |
March | 0.132773E+11 | 0.91 | 4957.19 | 01-MAR-00:10 | 0.91 |
April | 0.128490E+11 | 0.91 | 4957.19 | 01-APR-00:10 | 0.91 |
May | 0.132773E+11 | 0.91 | 4957.19 | 01-MAY-00:05 | 0.91 |
June | 0.128490E+11 | 0.91 | 4957.19 | 01-JUN-00:10 | 0.91 |
July | 0.132773E+11 | 0.91 | 4957.19 | 01-JUL-00:03 | 0.91 |
August | 0.132773E+11 | 0.91 | 4957.19 | 01-AUG-00:03 | 0.91 |
September | 0.128490E+11 | 0.91 | 4957.19 | 01-SEP-00:05 | 0.91 |
October | 0.132773E+11 | 0.91 | 4957.19 | 01-OCT-00:10 | 0.91 |
November | 0.128490E+11 | 0.91 | 4957.19 | 01-NOV-00:10 | 0.91 |
December | 0.132773E+11 | 0.91 | 4957.19 | 01-DEC-00:10 | 0.91 |
Annual Sum or Average | 0.156330E+12 | 0.91 | |||
Minimum of Months | 0.119924E+11 | 0.91 | 4957.19 | 0.91 | |
Maximum of Months | 0.132773E+11 | 0.91 | 4957.19 | 0.91 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER TOP SUPPLY FAN
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.135421E+10 | 0.91 | 505.60 | 01-JAN-00:05 | 0.91 |
February | 0.122315E+10 | 0.91 | 505.60 | 01-FEB-00:10 | 0.91 |
March | 0.135421E+10 | 0.91 | 505.60 | 01-MAR-00:10 | 0.91 |
April | 0.131052E+10 | 0.91 | 505.60 | 01-APR-00:10 | 0.91 |
May | 0.135421E+10 | 0.91 | 505.60 | 01-MAY-00:05 | 0.91 |
June | 0.131052E+10 | 0.91 | 505.60 | 01-JUN-00:10 | 0.91 |
July | 0.135421E+10 | 0.91 | 505.60 | 01-JUL-00:03 | 0.91 |
August | 0.135421E+10 | 0.91 | 505.60 | 01-AUG-00:03 | 0.91 |
September | 0.131052E+10 | 0.91 | 505.60 | 01-SEP-00:10 | 0.91 |
October | 0.135421E+10 | 0.91 | 505.60 | 01-OCT-00:10 | 0.91 |
November | 0.131052E+10 | 0.91 | 505.60 | 01-NOV-00:10 | 0.91 |
December | 0.135421E+10 | 0.91 | 505.60 | 01-DEC-00:10 | 0.91 |
Annual Sum or Average | 0.159447E+11 | 0.91 | |||
Minimum of Months | 0.122315E+10 | 0.91 | 505.60 | 0.91 | |
Maximum of Months | 0.135421E+10 | 0.91 | 505.60 | 0.91 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 55649384.98 | 50084446.48 | 2669.34 | 10-JAN-06:02 | 2402.41 | 2402.41 | 36.06 | 4.49 |
February | 30888926.61 | 27800033.95 | 2793.81 | 06-FEB-06:01 | 2514.43 | 2514.43 | 39.74 | 4.95 |
March | 24487271.51 | 22038544.36 | 2117.72 | 11-MAR-06:03 | 1905.94 | 1905.94 | 33.79 | 3.00 |
April | 1735457.38 | 1561911.65 | 331.83 | 18-APR-15:00 | 298.64 | 298.64 | 55.69 | 0.35 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 58.89 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 58.89 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 58.89 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 58.89 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 58.89 | 0.00 |
October | 79966.15 | 71969.54 | 11.46 | 28-OCT-06:40 | 10.32 | 10.32 | 56.80 | 0.01 |
November | 1187226.51 | 1068503.86 | 259.01 | 16-NOV-06:02 | 233.11 | 233.11 | 43.33 | 0.27 |
December | 36508158.26 | 32857342.44 | 2705.52 | 20-DEC-06:02 | 2434.97 | 2434.97 | 37.45 | 4.62 |
Annual Sum or Average | 0.150536E+09 | 0.135483E+09 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.79 | 0.00 | |
Maximum of Months | 55649384.98 | 50084446.48 | 2793.81 | 2514.43 | 2514.43 | 58.89 | 4.95 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.332519E+09 | 0.299267E+09 | 13035.71 | 19-JAN-06:03 | 11732.14 | 11732.14 | 8.26 | 97.03 |
February | 0.556023E+09 | 0.500421E+09 | 17249.40 | 28-FEB-06:02 | 15524.46 | 15524.46 | 8.25 | 108.61 |
March | 0.571491E+09 | 0.514342E+09 | 26817.12 | 27-MAR-05:02 | 24135.41 | 24135.41 | 8.08 | 129.36 |
April | 0.955206E+09 | 0.859686E+09 | 26817.12 | 24-APR-05:03 | 24135.41 | 24135.41 | 8.07 | 129.36 |
May | 0.187000E+10 | 0.168300E+10 | 26817.12 | 04-MAY-05:02 | 24135.41 | 24135.41 | 7.71 | 129.36 |
June | 0.189859E+10 | 0.170873E+10 | 26817.12 | 01-JUN-05:03 | 24135.41 | 24135.41 | 7.80 | 129.36 |
July | 0.189812E+10 | 0.170831E+10 | 26817.12 | 03-JUL-05:02 | 24135.41 | 24135.41 | 7.29 | 129.36 |
August | 0.211437E+10 | 0.190293E+10 | 26817.12 | 01-AUG-05:02 | 24135.41 | 24135.41 | 7.52 | 129.36 |
September | 0.180486E+10 | 0.162437E+10 | 26817.12 | 05-SEP-05:02 | 24135.41 | 24135.41 | 8.07 | 129.36 |
October | 0.190060E+10 | 0.171054E+10 | 26817.12 | 10-OCT-05:03 | 24135.41 | 24135.41 | 7.81 | 129.36 |
November | 0.996723E+09 | 0.897050E+09 | 26817.12 | 02-NOV-05:02 | 24135.41 | 24135.41 | 7.80 | 129.36 |
December | 0.621114E+09 | 0.559002E+09 | 25814.34 | 15-DEC-06:02 | 23232.91 | 23232.91 | 7.90 | 127.43 |
Annual Sum or Average | 0.155196E+11 | 0.139677E+11 | ||||||
Minimum of Months | 0.332519E+09 | 0.299267E+09 | 13035.71 | 11732.14 | 11732.14 | 7.29 | 97.03 | |
Maximum of Months | 0.211437E+10 | 0.190293E+10 | 26817.12 | 24135.41 | 24135.41 | 8.26 | 129.36 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.160346E+11 | 0.144311E+11 | 18457.50 | 01-JAN-00:23 | 16611.75 | 16611.75 | 8.22 | 129.36 |
February | 0.201493E+11 | 0.181344E+11 | 18457.50 | 01-FEB-04:03 | 16611.75 | 16611.75 | 9.21 | 129.36 |
March | 0.248665E+11 | 0.223798E+11 | 18457.50 | 01-MAR-04:03 | 16611.75 | 16611.75 | 9.19 | 129.36 |
April | 0.367297E+11 | 0.330567E+11 | 18457.50 | 01-APR-03:02 | 16611.75 | 16611.75 | 9.35 | 129.36 |
May | 0.382292E+11 | 0.344063E+11 | 18457.50 | 01-MAY-00:05 | 16611.75 | 16611.75 | 7.54 | 129.36 |
June | 0.415971E+11 | 0.374374E+11 | 18457.50 | 01-JUN-03:02 | 16611.75 | 16611.75 | 11.26 | 129.36 |
July | 0.450560E+11 | 0.405504E+11 | 18457.50 | 01-JUL-00:03 | 16611.75 | 16611.75 | 7.15 | 129.36 |
August | 0.463108E+11 | 0.416797E+11 | 18457.50 | 01-AUG-00:10 | 16611.75 | 16611.75 | 7.13 | 129.36 |
September | 0.370909E+11 | 0.333818E+11 | 18457.50 | 01-SEP-00:05 | 16611.75 | 16611.75 | 7.17 | 129.36 |
October | 0.377111E+11 | 0.339400E+11 | 18457.50 | 01-OCT-07:33 | 16611.75 | 16611.75 | 8.50 | 129.36 |
November | 0.295383E+11 | 0.265844E+11 | 18457.50 | 01-NOV-00:53 | 16611.75 | 16611.75 | 8.73 | 129.36 |
December | 0.226055E+11 | 0.203449E+11 | 18457.50 | 01-DEC-04:03 | 16611.75 | 16611.75 | 8.46 | 129.36 |
Annual Sum or Average | 0.395919E+12 | 0.356327E+12 | ||||||
Minimum of Months | 0.160346E+11 | 0.144311E+11 | 18457.50 | 16611.75 | 16611.75 | 7.13 | 129.36 | |
Maximum of Months | 0.463108E+11 | 0.416797E+11 | 18457.50 | 16611.75 | 16611.75 | 11.26 | 129.36 |
Report: PumpReportMonthly
For: PLANT CIRC PUMP
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.909446E+10 | 0.818502E+10 | 3395.48 | 01-JAN-00:05 | 3055.94 | 3055.94 | 22.61 | 14.18 |
February | 0.821436E+10 | 0.739292E+10 | 3395.48 | 01-FEB-00:10 | 3055.94 | 3055.94 | 27.13 | 14.18 |
March | 0.909446E+10 | 0.818502E+10 | 3395.48 | 01-MAR-00:10 | 3055.94 | 3055.94 | 30.56 | 14.18 |
April | 0.880109E+10 | 0.792099E+10 | 3395.48 | 01-APR-00:10 | 3055.94 | 3055.94 | 38.71 | 14.18 |
May | 0.909446E+10 | 0.818502E+10 | 3395.48 | 01-MAY-00:05 | 3055.94 | 3055.94 | 28.63 | 14.18 |
June | 0.880109E+10 | 0.792099E+10 | 3395.48 | 01-JUN-00:10 | 3055.94 | 3055.94 | 32.83 | 14.18 |
July | 0.909446E+10 | 0.818502E+10 | 3395.48 | 01-JUL-00:03 | 3055.94 | 3055.94 | 39.34 | 14.18 |
August | 0.909446E+10 | 0.818502E+10 | 3395.48 | 01-AUG-00:03 | 3055.94 | 3055.94 | 43.77 | 14.18 |
September | 0.880109E+10 | 0.792099E+10 | 3395.48 | 01-SEP-00:05 | 3055.94 | 3055.94 | 31.49 | 14.18 |
October | 0.909446E+10 | 0.818502E+10 | 3395.48 | 01-OCT-00:10 | 3055.94 | 3055.94 | 32.07 | 14.18 |
November | 0.880109E+10 | 0.792099E+10 | 3395.48 | 01-NOV-00:10 | 3055.94 | 3055.94 | 35.60 | 14.18 |
December | 0.909446E+10 | 0.818502E+10 | 3395.48 | 01-DEC-00:10 | 3055.94 | 3055.94 | 30.82 | 14.18 |
Annual Sum or Average | 0.107080E+12 | 0.963720E+11 | ||||||
Minimum of Months | 0.821436E+10 | 0.739292E+10 | 3395.48 | 3055.94 | 3055.94 | 22.61 | 14.18 | |
Maximum of Months | 0.909446E+10 | 0.818502E+10 | 3395.48 | 3055.94 | 3055.94 | 43.77 | 14.18 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 11967951.72 | 3590385.52 | 5.96 | 01-JAN-06:05 | 1.79 | 1.79 | 56.23 | 0.44 |
February | 10809762.85 | 3242928.85 | 5.96 | 01-FEB-06:02 | 1.79 | 1.79 | 56.30 | 0.44 |
March | 11967951.72 | 3590385.52 | 5.96 | 01-MAR-06:02 | 1.79 | 1.79 | 56.42 | 0.44 |
April | 11581888.76 | 3474566.63 | 5.96 | 01-APR-05:03 | 1.79 | 1.79 | 57.16 | 0.44 |
May | 11967951.72 | 3590385.52 | 5.96 | 01-MAY-05:02 | 1.79 | 1.79 | 57.03 | 0.44 |
June | 11581888.76 | 3474566.63 | 5.96 | 01-JUN-05:03 | 1.79 | 1.79 | 57.04 | 0.44 |
July | 11967951.72 | 3590385.52 | 5.96 | 01-JUL-05:03 | 1.79 | 1.79 | 56.90 | 0.44 |
August | 11967951.72 | 3590385.52 | 5.96 | 01-AUG-05:02 | 1.79 | 1.79 | 56.57 | 0.44 |
September | 11581888.76 | 3474566.63 | 5.96 | 01-SEP-05:03 | 1.79 | 1.79 | 56.93 | 0.44 |
October | 11967951.72 | 3590385.52 | 5.96 | 01-OCT-05:10 | 1.79 | 1.79 | 56.63 | 0.44 |
November | 11581888.76 | 3474566.63 | 5.96 | 01-NOV-05:03 | 1.79 | 1.79 | 57.12 | 0.44 |
December | 11967951.72 | 3590385.52 | 5.96 | 01-DEC-06:02 | 1.79 | 1.79 | 56.58 | 0.44 |
Annual Sum or Average | 0.140913E+09 | 42273893.99 | ||||||
Minimum of Months | 10809762.85 | 3242928.85 | 5.96 | 1.79 | 1.79 | 56.23 | 0.44 | |
Maximum of Months | 11967951.72 | 3590385.52 | 5.96 | 1.79 | 1.79 | 57.16 | 0.44 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.208684E+11 | 0.187816E+11 | 45883.48 | 19-JAN-12:00 | 41295.13 | 41295.13 | 26.88 | 152.19 |
February | 0.261680E+11 | 0.235512E+11 | 45877.79 | 24-FEB-13:20 | 41290.01 | 41290.01 | 26.73 | 152.19 |
March | 0.318788E+11 | 0.286909E+11 | 45909.13 | 07-MAR-11:30 | 41318.22 | 41318.22 | 27.54 | 152.19 |
April | 0.492596E+11 | 0.443336E+11 | 45957.91 | 28-APR-15:40 | 41362.12 | 41362.12 | 29.16 | 152.19 |
May | 0.629230E+11 | 0.566307E+11 | 45957.91 | 01-MAY-05:04 | 41362.12 | 41362.12 | 28.94 | 152.19 |
June | 0.672962E+11 | 0.605666E+11 | 45957.91 | 01-JUN-11:30 | 41362.12 | 41362.12 | 28.94 | 152.19 |
July | 0.723766E+11 | 0.651390E+11 | 45957.91 | 03-JUL-05:04 | 41362.12 | 41362.12 | 28.94 | 152.19 |
August | 0.758219E+11 | 0.682397E+11 | 45957.91 | 01-AUG-08:70 | 41362.12 | 41362.12 | 28.94 | 152.19 |
September | 0.598585E+11 | 0.538727E+11 | 45957.91 | 01-SEP-07:40 | 41362.12 | 41362.12 | 29.14 | 152.19 |
October | 0.583151E+11 | 0.524836E+11 | 45957.91 | 05-OCT-08:50 | 41362.12 | 41362.12 | 28.87 | 152.19 |
November | 0.403822E+11 | 0.363440E+11 | 45957.91 | 01-NOV-12:10 | 41362.12 | 41362.12 | 29.07 | 152.19 |
December | 0.299735E+11 | 0.269762E+11 | 45957.91 | 12-DEC-14:10 | 41362.12 | 41362.12 | 28.93 | 152.19 |
Annual Sum or Average | 0.595122E+12 | 0.535610E+12 | ||||||
Minimum of Months | 0.208684E+11 | 0.187816E+11 | 45877.79 | 41290.01 | 41290.01 | 26.73 | 152.19 | |
Maximum of Months | 0.758219E+11 | 0.682397E+11 | 45957.91 | 41362.12 | 41362.12 | 29.16 | 152.19 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 79.40 | 79.40 | 4536.50 | 835681.10 | 10-JAN-06:02 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 23.87 | 23.87 | 2685.40 | 846264.83 | 06-FEB-06:01 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 24.51 | 24.51 | 2101.45 | 580033.84 | 11-MAR-06:03 |
April | 0.00 | 0.00 | 01-APR-00:10 | 44.84 | 44.84 | 86.08 | 45413.30 | 18-APR-14:30 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 58.89 | 58.89 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 58.89 | 58.89 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 58.89 | 58.89 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 58.89 | 58.89 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 58.89 | 58.89 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 58.89 | 58.89 | 2.82 | 1092.29 | 28-OCT-06:40 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 55.16 | 55.16 | 72.94 | 44092.98 | 27-NOV-14:20 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 39.44 | 39.44 | 3073.08 | 852257.95 | 21-DEC-06:01 |
Annual Sum or Average | 0.00 | 1044.08 | ||||||
Minimum of Months | 0.00 | 0.00 | 23.87 | 23.87 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 79.40 | 79.40 | 4536.50 | 852257.95 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 222199.35 | 1776720.36 | 19-JAN-06:03 | 11.16 | 7.88 | 0.97 | 17378.04 | 01-JAN-05:23 |
February | 336658.15 | 1712163.92 | 24-FEB-13:10 | 9.86 | 6.70 | 1.00 | 12086.88 | 26-FEB-09:23 |
March | 390658.08 | 2302650.67 | 07-MAR-06:04 | 11.79 | 7.54 | 34.33 | 183171.99 | 19-MAR-08:13 |
April | 647032.32 | 2593334.71 | 29-APR-05:02 | 12.01 | 7.23 | 0.05 | 781.84 | 09-APR-23:33 |
May | 940377.28 | 3141983.77 | 24-MAY-05:03 | 12.76 | 7.06 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 977051.04 | 2843070.04 | 08-JUN-05:04 | 12.62 | 7.38 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 972937.46 | 3289953.98 | 31-JUL-05:04 | 13.12 | 7.42 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 994884.68 | 2901200.29 | 01-AUG-05:04 | 12.48 | 7.12 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 938046.35 | 2963436.30 | 13-SEP-05:03 | 12.69 | 7.22 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 798755.53 | 3032100.65 | 20-OCT-05:04 | 13.01 | 7.41 | 2.46 | 28471.76 | 29-OCT-19:33 |
November | 505261.07 | 2678073.48 | 02-NOV-05:02 | 12.14 | 7.20 | 15.81 | 84048.06 | 19-NOV-18:53 |
December | 336297.72 | 2756609.21 | 15-DEC-06:04 | 12.65 | 7.56 | 4.69 | 44427.22 | 31-DEC-21:13 |
Annual Sum or Average | 673390.59 | 4.98 | ||||||
Minimum of Months | 222199.35 | 1712163.92 | 9.86 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 994884.68 | 3289953.98 | 13.12 | 7.88 | 34.33 | 183171.99 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 159967.97 | 3193301.15 | 19-JAN-06:03 | 14.56 | 7.93 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 251897.80 | 3482738.19 | 28-FEB-06:02 | 14.36 | 7.99 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 283276.52 | 4125445.37 | 07-MAR-06:02 | 14.44 | 7.58 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 476826.81 | 4130577.91 | 29-APR-05:02 | 14.77 | 7.57 | 0.00 | 0.00 | 01-APR-00:10 |
May | 748842.17 | 4362661.83 | 10-MAY-05:02 | 14.76 | 7.54 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 785753.50 | 4230109.91 | 08-JUN-05:02 | 14.51 | 7.62 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 774027.55 | 4281972.98 | 31-JUL-05:02 | 14.61 | 7.49 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 813379.75 | 4341884.70 | 07-AUG-05:02 | 14.72 | 7.22 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 750530.31 | 4710341.63 | 05-SEP-03:02 | 15.50 | 7.34 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 633304.96 | 4343121.36 | 11-OCT-05:02 | 14.72 | 7.67 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 372531.03 | 4193746.16 | 02-NOV-05:02 | 14.45 | 7.62 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 248841.98 | 4262561.13 | 15-DEC-06:02 | 14.69 | 7.62 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 526392.48 | 0.00 | ||||||
Minimum of Months | 159967.97 | 3193301.15 | 14.36 | 7.22 | 0.00 | 0.00 | ||
Maximum of Months | 813379.75 | 4710341.63 | 15.50 | 7.99 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 244437.57 | 744419.59 | 02-JAN-15:00 | 33.28 | 28.91 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 450640.28 | 1035948.96 | 02-FEB-13:10 | 39.02 | 31.52 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 687278.79 | 1336119.03 | 30-MAR-13:00 | 44.86 | 34.17 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 1069279.24 | 1758685.33 | 28-APR-15:00 | 52.99 | 39.43 | 0.00 | 0.00 | 01-APR-00:10 |
May | 737325.01 | 1101891.63 | 18-MAY-16:00 | 40.30 | 35.45 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 999142.31 | 1425474.56 | 14-JUN-14:00 | 46.59 | 38.58 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 1243310.74 | 1739962.02 | 21-JUL-16:00 | 52.63 | 41.25 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 1431570.18 | 1911302.02 | 30-AUG-16:10 | 55.89 | 42.26 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 705062.85 | 1264988.73 | 09-SEP-17:00 | 43.48 | 38.58 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 819014.29 | 1376855.99 | 05-OCT-15:00 | 45.65 | 37.60 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 757228.59 | 1382792.26 | 02-NOV-13:00 | 45.76 | 34.87 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 832637.59 | 1575232.05 | 13-DEC-15:00 | 49.47 | 36.04 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 833978.40 | 0.00 | ||||||
Minimum of Months | 244437.57 | 744419.59 | 33.28 | 28.91 | 0.00 | 0.00 | ||
Maximum of Months | 1431570.18 | 1911302.02 | 55.89 | 42.26 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 57.91 | 57.91 | 12872.40 | 42424.01 | 25-JAN-12:40 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 56.87 | 56.87 | 12848.26 | 42362.61 | 01-FEB-12:30 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 56.87 | 56.87 | 13094.26 | 41421.46 | 01-MAR-12:50 |
April | 0.00 | 0.00 | 01-APR-00:10 | 57.31 | 57.31 | 11687.11 | 39162.13 | 03-APR-12:00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 57.55 | 57.55 | 11287.80 | 36776.47 | 01-MAY-11:20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 57.44 | 57.44 | 10898.83 | 34320.97 | 01-JUN-11:40 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 57.23 | 57.23 | 9869.12 | 32682.26 | 03-JUL-11:40 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 56.89 | 56.89 | 10767.89 | 33345.93 | 31-AUG-11:40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 57.31 | 57.31 | 10638.63 | 35304.02 | 29-SEP-11:50 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 57.36 | 57.36 | 11291.04 | 38011.11 | 31-OCT-11:40 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 57.58 | 57.58 | 12157.86 | 40419.46 | 30-NOV-12:30 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 57.01 | 57.01 | 12325.05 | 41967.03 | 29-DEC-12:50 |
Annual Sum or Average | 0.00 | 11638.24 | ||||||
Minimum of Months | 0.00 | 0.00 | 56.87 | 56.87 | 9869.12 | 32682.26 | ||
Maximum of Months | 0.00 | 0.00 | 57.91 | 57.91 | 13094.26 | 42424.01 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 180137.24 | 3674544.78 | 19-JAN-12:00 | 26.88 | 23.82 | 1943.88 | 190590.83 | 21-JAN-11:30 |
February | 272230.40 | 3580410.81 | 24-FEB-13:20 | 26.73 | 23.55 | 1130.59 | 181561.35 | 17-FEB-07:50 |
March | 334616.96 | 4098203.56 | 07-MAR-11:30 | 27.54 | 24.41 | 1586.49 | 188773.57 | 09-MAR-11:00 |
April | 664928.68 | 5615019.25 | 28-APR-16:00 | 29.93 | 26.99 | 793.97 | 132029.93 | 10-APR-08:20 |
May | 1864149.01 | 6067390.26 | 24-MAY-05:05 | 30.64 | 26.49 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 2175860.82 | 6239731.25 | 28-JUN-14:00 | 30.91 | 27.87 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 2554553.19 | 6519640.34 | 12-JUL-10:10 | 31.35 | 28.15 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 2467901.48 | 6453960.77 | 14-AUG-11:00 | 31.25 | 28.09 | 0.44 | 3948.61 | 20-AUG-04:40 |
September | 1987138.32 | 6451798.07 | 18-SEP-14:00 | 31.24 | 28.09 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 1497200.70 | 6692347.80 | 24-OCT-13:30 | 31.62 | 28.24 | 334.79 | 119709.13 | 27-OCT-17:50 |
November | 590867.10 | 5428491.22 | 01-NOV-14:00 | 29.63 | 26.58 | 1535.17 | 154065.82 | 22-NOV-09:50 |
December | 350792.14 | 5083777.27 | 12-DEC-14:20 | 29.09 | 25.85 | 1759.05 | 182682.84 | 20-DEC-15:30 |
Annual Sum or Average | 1251825.12 | 755.88 | ||||||
Minimum of Months | 180137.24 | 3580410.81 | 26.73 | 23.55 | 0.00 | 0.00 | ||
Maximum of Months | 2554553.19 | 6692347.80 | 31.62 | 28.24 | 1943.88 | 190590.83 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 78134443.96 | 0.00 | 0.342391E+11 | 0.592536E+10 | 0.00 | 0.00 |
February | 34794737.85 | 0.00 | 0.488738E+11 | 0.620593E+10 | 0.00 | 0.00 |
March | 26985485.57 | 0.00 | 0.651581E+11 | 0.839646E+10 | 0.00 | 0.00 |
April | 45546390.94 | 0.00 | 0.109851E+12 | 0.102676E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.150401E+12 | 0.105108E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.162738E+12 | 0.117660E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.176160E+12 | 0.125788E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.193773E+12 | 0.150613E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.149166E+12 | 0.980537E+10 | 0.00 | 0.00 |
October | 240.64 | 0.00 | 0.137372E+12 | 0.101668E+11 | 0.00 | 0.00 |
November | 3342.80 | 0.00 | 0.805258E+11 | 0.857445E+10 | 0.00 | 0.00 |
December | 39142988.51 | 0.00 | 0.590780E+11 | 0.781333E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.224608E+09 | 0.00 | 0.136734E+13 | 0.117072E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.342391E+11 | 0.592536E+10 | 0.00 | 0.00 |
Maximum of Months | 78134443.96 | 0.00 | 0.193773E+12 | 0.150613E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.843129E+10 | 0.00 | 0.267454E+12 | 0.406986E+11 | 0.00 | 0.00 |
February | 0.409931E+10 | 0.00 | 0.378432E+12 | 0.404960E+11 | 0.00 | 0.00 |
March | 0.383688E+10 | 0.00 | 0.479486E+12 | 0.521199E+11 | 0.00 | 0.00 |
April | 0.118713E+09 | 0.00 | 0.794848E+12 | 0.639477E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.135751E+13 | 0.928688E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.139215E+13 | 0.956132E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.143176E+13 | 0.905658E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.148707E+13 | 0.985827E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.131486E+13 | 0.797594E+11 | 0.00 | 0.00 |
October | 1960.52 | 0.00 | 0.113814E+13 | 0.744310E+11 | 0.00 | 0.00 |
November | 47492045.22 | 0.00 | 0.606307E+12 | 0.522700E+11 | 0.00 | 0.00 |
December | 0.575025E+10 | 0.00 | 0.412523E+12 | 0.431209E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.222839E+11 | 0.00 | 0.110606E+14 | 0.824474E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.267454E+12 | 0.404960E+11 | 0.00 | 0.00 |
Maximum of Months | 0.843129E+10 | 0.00 | 0.148707E+13 | 0.985827E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.394150E+10 | 0.00 | 0.257704E+11 | 0.341808E+10 | 0.00 | 0.00 |
February | 0.241973E+10 | 0.00 | 0.378887E+11 | 0.370760E+10 | 0.00 | 0.00 |
March | 0.174433E+10 | 0.00 | 0.493188E+11 | 0.467302E+10 | 0.00 | 0.00 |
April | 12979430.47 | 0.00 | 0.847841E+11 | 0.627882E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.150982E+12 | 0.102022E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.157677E+12 | 0.108801E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.162030E+12 | 0.103120E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.165969E+12 | 0.109654E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.142064E+12 | 0.837518E+10 | 0.00 | 0.00 |
October | 20566689.82 | 0.00 | 0.122309E+12 | 0.777843E+10 | 0.00 | 0.00 |
November | 0.197748E+09 | 0.00 | 0.594080E+11 | 0.461798E+10 | 0.00 | 0.00 |
December | 0.257711E+10 | 0.00 | 0.397464E+11 | 0.371020E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.109140E+11 | 0.00 | 0.119795E+13 | 0.849189E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.257704E+11 | 0.341808E+10 | 0.00 | 0.00 |
Maximum of Months | 0.394150E+10 | 0.00 | 0.165969E+12 | 0.109654E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.218968E+11 | 0.151143E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.263542E+11 | 0.132172E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.354979E+11 | 0.151784E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.562278E+11 | 0.138852E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.103677E+12 | 0.149819E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.108815E+12 | 0.146433E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.117942E+12 | 0.147184E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.130714E+12 | 0.162706E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.110906E+12 | 0.153983E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.953928E+11 | 0.158403E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.523303E+11 | 0.153407E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.342941E+11 | 0.153907E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.894049E+12 | 0.179979E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.218968E+11 | 0.132172E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.130714E+12 | 0.162706E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.417507E+12 | 0.181025E+12 | 0.00 | 0.19 |
February | 0.00 | 0.00 | 0.655626E+12 | 0.218791E+12 | 0.00 | 0.13 |
March | 0.00 | 0.00 | 0.103627E+13 | 0.307805E+12 | 0.00 | 0.08 |
April | 0.00 | 0.00 | 0.132691E+13 | 0.382366E+12 | 0.00 | 0.02 |
May | 0.00 | 0.00 | 0.465550E+12 | 0.211284E+12 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.769888E+12 | 0.285338E+12 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.112650E+13 | 0.378826E+12 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.143361E+13 | 0.447598E+12 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.453994E+12 | 0.203575E+12 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.776661E+12 | 0.277826E+12 | 0.00 | 0.02 |
November | 0.00 | 0.00 | 0.101872E+13 | 0.306234E+12 | 0.00 | 0.03 |
December | 0.00 | 0.00 | 0.133796E+13 | 0.362163E+12 | 0.00 | 0.10 |
Annual Sum or Average | 0.00 | 0.00 | 0.108192E+14 | 0.356283E+13 | 0.00 | 0.57 |
Minimum of Months | 0.00 | 0.00 | 0.417507E+12 | 0.181025E+12 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.143361E+13 | 0.447598E+12 | 0.00 | 0.19 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.658165E+10 | 0.275278E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.120621E+11 | 0.369063E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.198537E+11 | 0.543394E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.262259E+11 | 0.703166E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.870458E+10 | 0.353428E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.150682E+11 | 0.507061E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.223780E+11 | 0.693909E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.290556E+11 | 0.850799E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.843577E+10 | 0.338926E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.149766E+11 | 0.487109E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.196834E+11 | 0.544522E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.260067E+11 | 0.654672E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.209032E+12 | 0.632133E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.658165E+10 | 0.275278E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.290556E+11 | 0.850799E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.508414E+11 | 0.239110E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.106059E+12 | 0.335154E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.182524E+12 | 0.505897E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.249013E+12 | 0.668306E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.817882E+11 | 0.333711E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.143704E+12 | 0.483064E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.213543E+12 | 0.661499E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.276068E+12 | 0.808577E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.780957E+11 | 0.317356E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.140670E+12 | 0.459778E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.182102E+12 | 0.508923E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.238969E+12 | 0.608825E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.194338E+13 | 0.593020E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.508414E+11 | 0.239110E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.276068E+12 | 0.808577E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.379174E+10 | 0.216407E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.970467E+10 | 0.321151E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.176362E+11 | 0.498583E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.247979E+11 | 0.670508E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.835925E+10 | 0.340958E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.145662E+11 | 0.490771E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.215733E+11 | 0.670160E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.278218E+11 | 0.817832E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.796071E+10 | 0.323823E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.140447E+11 | 0.462999E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.177018E+11 | 0.503301E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.229863E+11 | 0.597249E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.190944E+12 | 0.591374E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.379174E+10 | 0.216407E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.278218E+11 | 0.817832E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.592536E+10 | 0.342391E+11 | 78134443.96 | 0.579760E+09 | 0.622798E+09 | 0.00 | 0.00 | 0.00 |
February | 0.620593E+10 | 0.488738E+11 | 34794737.85 | 0.227691E+09 | 0.108677E+10 | 0.00 | 0.00 | 0.00 |
March | 0.839646E+10 | 0.651581E+11 | 26985485.57 | 0.135627E+09 | 0.200521E+10 | 0.00 | 0.00 | 0.00 |
April | 0.102676E+11 | 0.109851E+12 | 45546390.94 | 0.00 | 0.550623E+10 | 0.00 | 0.00 | 0.00 |
May | 0.105108E+11 | 0.150401E+12 | 0.00 | 0.00 | 0.255005E+11 | 0.00 | 0.00 | 0.00 |
June | 0.117660E+11 | 0.162738E+12 | 0.00 | 0.00 | 0.315630E+11 | 0.00 | 0.00 | 0.00 |
July | 0.125788E+11 | 0.176160E+12 | 0.00 | 0.00 | 0.353239E+11 | 0.00 | 0.00 | 0.00 |
August | 0.150613E+11 | 0.193773E+12 | 0.00 | 0.00 | 0.346446E+11 | 0.00 | 0.00 | 0.00 |
September | 0.980537E+10 | 0.149166E+12 | 0.00 | 0.00 | 0.227554E+11 | 0.00 | 0.00 | 0.00 |
October | 0.101668E+11 | 0.137372E+12 | 240.64 | 0.00 | 0.198112E+11 | 0.00 | 0.00 | 0.00 |
November | 0.857445E+10 | 0.805258E+11 | 3342.80 | 0.00 | 0.496281E+10 | 0.00 | 0.00 | 0.00 |
December | 0.781333E+10 | 0.590780E+11 | 39142988.51 | 0.229344E+09 | 0.259094E+10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.117072E+12 | 0.136734E+13 | 0.224608E+09 | 0.117242E+10 | 0.186373E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.592536E+10 | 0.342391E+11 | 0.00 | 0.00 | 0.622798E+09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.150613E+11 | 0.193773E+12 | 78134443.96 | 0.579760E+09 | 0.353239E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.406986E+11 | 0.267454E+12 | 0.843129E+10 | 0.105883E+11 | 0.642394E+10 | 0.00 | 0.00 | 0.00 |
February | 0.404960E+11 | 0.378432E+12 | 0.409931E+10 | 0.557734E+10 | 0.116439E+11 | 0.00 | 0.00 | 0.00 |
March | 0.521199E+11 | 0.479486E+12 | 0.383688E+10 | 0.333129E+10 | 0.201811E+11 | 0.00 | 0.00 | 0.00 |
April | 0.639477E+11 | 0.794848E+12 | 0.118713E+09 | 0.00 | 0.535308E+11 | 0.00 | 0.00 | 0.00 |
May | 0.928688E+11 | 0.135751E+13 | 0.00 | 0.00 | 0.255419E+12 | 0.00 | 0.00 | 0.00 |
June | 0.956132E+11 | 0.139215E+13 | 0.00 | 0.00 | 0.316946E+12 | 0.00 | 0.00 | 0.00 |
July | 0.905658E+11 | 0.143176E+13 | 0.00 | 0.00 | 0.354932E+12 | 0.00 | 0.00 | 0.00 |
August | 0.985827E+11 | 0.148707E+13 | 0.00 | 0.00 | 0.344565E+12 | 0.00 | 0.00 | 0.00 |
September | 0.797594E+11 | 0.131486E+13 | 0.00 | 0.00 | 0.229375E+12 | 0.00 | 0.00 | 0.00 |
October | 0.744310E+11 | 0.113814E+13 | 1960.52 | 0.00 | 0.199853E+12 | 0.00 | 0.00 | 0.00 |
November | 0.522700E+11 | 0.606307E+12 | 47492045.22 | 47338405.56 | 0.500533E+11 | 0.00 | 0.00 | 0.00 |
December | 0.431209E+11 | 0.412523E+12 | 0.575025E+10 | 0.683158E+10 | 0.261556E+11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.824474E+12 | 0.110606E+14 | 0.222839E+11 | 0.263759E+11 | 0.186908E+13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.404960E+11 | 0.267454E+12 | 0.00 | 0.00 | 0.642394E+10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.985827E+11 | 0.148707E+13 | 0.843129E+10 | 0.105883E+11 | 0.354932E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.341808E+10 | 0.257704E+11 | 0.394150E+10 | 0.212490E+10 | 0.154330E+09 | 0.00 | 0.00 | 0.00 |
February | 0.370760E+10 | 0.378887E+11 | 0.241973E+10 | 0.108240E+10 | 0.516296E+09 | 0.00 | 0.00 | 0.00 |
March | 0.467302E+10 | 0.493188E+11 | 0.174433E+10 | 0.720139E+09 | 0.151549E+10 | 0.00 | 0.00 | 0.00 |
April | 0.627882E+10 | 0.847841E+11 | 12979430.47 | 517937.45 | 0.466142E+10 | 0.00 | 0.00 | 0.00 |
May | 0.102022E+11 | 0.150982E+12 | 0.00 | 0.00 | 0.245808E+11 | 0.00 | 0.00 | 0.00 |
June | 0.108801E+11 | 0.157677E+12 | 0.00 | 0.00 | 0.304655E+11 | 0.00 | 0.00 | 0.00 |
July | 0.103120E+11 | 0.162030E+12 | 0.00 | 0.00 | 0.340201E+11 | 0.00 | 0.00 | 0.00 |
August | 0.109654E+11 | 0.165969E+12 | 0.00 | 0.00 | 0.332634E+11 | 0.00 | 0.00 | 0.00 |
September | 0.837518E+10 | 0.142064E+12 | 0.00 | 0.00 | 0.220680E+11 | 0.00 | 0.00 | 0.00 |
October | 0.777843E+10 | 0.122309E+12 | 20566689.82 | 2977314.11 | 0.190876E+11 | 0.00 | 0.00 | 0.00 |
November | 0.461798E+10 | 0.594080E+11 | 0.197748E+09 | 45416986.13 | 0.473784E+10 | 0.00 | 0.00 | 0.00 |
December | 0.371020E+10 | 0.397464E+11 | 0.257711E+10 | 0.140474E+10 | 0.219213E+10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.849189E+11 | 0.119795E+13 | 0.109140E+11 | 0.538108E+10 | 0.177263E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.341808E+10 | 0.257704E+11 | 0.00 | 0.00 | 0.154330E+09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.109654E+11 | 0.165969E+12 | 0.394150E+10 | 0.212490E+10 | 0.340201E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.151143E+11 | 0.218968E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.132172E+11 | 0.263542E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.151784E+11 | 0.354979E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.138852E+11 | 0.562278E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.149819E+11 | 0.103677E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.146433E+11 | 0.108815E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.147184E+11 | 0.117942E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.162706E+11 | 0.130714E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.153983E+11 | 0.110906E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.158403E+11 | 0.953928E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.153407E+11 | 0.523303E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.153907E+11 | 0.342941E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.179979E+12 | 0.894049E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.132172E+11 | 0.218968E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.162706E+11 | 0.130714E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.947342E+11 | 0.331718E+12 | 0.00 | 0.00 | 0.00 | 0.500317E+09 | 0.00 | 0.00 |
February | 0.855664E+11 | 0.522753E+12 | 0.00 | 0.00 | 0.00 | 0.349540E+09 | 0.00 | 0.00 |
March | 0.947342E+11 | 0.823430E+12 | 0.00 | 0.00 | 0.00 | 0.226732E+09 | 0.00 | 0.00 |
April | 0.916783E+11 | 0.103628E+13 | 0.00 | 0.00 | 0.00 | 62670613.80 | 0.00 | 0.00 |
May | 0.947342E+11 | 0.349000E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.916783E+11 | 0.576229E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.947342E+11 | 0.842408E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.947342E+11 | 0.108075E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.916783E+11 | 0.342098E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.947342E+11 | 0.593623E+12 | 0.00 | 0.00 | 0.00 | 53447703.09 | 0.00 | 0.00 |
November | 0.916783E+11 | 0.804250E+12 | 0.00 | 0.00 | 0.00 | 80554809.11 | 0.00 | 0.00 |
December | 0.947342E+11 | 0.107079E+13 | 0.00 | 0.00 | 0.00 | 0.256356E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.111542E+13 | 0.837333E+13 | 0.00 | 0.00 | 0.00 | 0.152962E+10 | 0.00 | 0.00 |
Minimum of Months | 0.855664E+11 | 0.331718E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.947342E+11 | 0.108075E+13 | 0.00 | 0.00 | 0.00 | 0.500317E+09 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.139709E+10 | 0.522595E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.126188E+10 | 0.963334E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.139709E+10 | 0.158168E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.135202E+10 | 0.205463E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139709E+10 | 0.656738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.135202E+10 | 0.113496E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.139709E+10 | 0.168360E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.139709E+10 | 0.219447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.135202E+10 | 0.639852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.139709E+10 | 0.115026E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.135202E+10 | 0.155902E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.139709E+10 | 0.208571E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.164496E+11 | 0.162269E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.126188E+10 | 0.522595E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.139709E+10 | 0.219447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.132773E+11 | 0.402077E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.119924E+11 | 0.845363E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.132773E+11 | 0.145211E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128490E+11 | 0.195032E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.132773E+11 | 0.616944E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.128490E+11 | 0.108247E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.132773E+11 | 0.160671E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.132773E+11 | 0.208488E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128490E+11 | 0.592091E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.132773E+11 | 0.107970E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.128490E+11 | 0.144059E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.132773E+11 | 0.191363E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.156330E+12 | 0.150669E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.119924E+11 | 0.402077E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.132773E+11 | 0.208488E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.135421E+10 | 0.298188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.122315E+10 | 0.771631E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.135421E+10 | 0.140046E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.131052E+10 | 0.194033E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.135421E+10 | 0.630387E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.131052E+10 | 0.109690E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.135421E+10 | 0.162259E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.135421E+10 | 0.209977E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.131052E+10 | 0.603300E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.135421E+10 | 0.107689E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.131052E+10 | 0.139793E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.135421E+10 | 0.183680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.159447E+11 | 0.147752E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.122315E+10 | 0.298188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.135421E+10 | 0.209977E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.592536E+10 | 78134443.96 | 0.342391E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.620593E+10 | 34794737.85 | 0.488738E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.839646E+10 | 26985485.57 | 0.651581E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.102676E+11 | 45546390.94 | 0.109851E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.105108E+11 | 0.00 | 0.150401E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.117660E+11 | 0.00 | 0.162738E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.125788E+11 | 0.00 | 0.176160E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.150613E+11 | 0.00 | 0.193773E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.980537E+10 | 0.00 | 0.149166E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.101668E+11 | 240.64 | 0.137372E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.857445E+10 | 3342.80 | 0.805258E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.781333E+10 | 39142988.51 | 0.590780E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.117072E+12 | 0.224608E+09 | 0.136734E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.592536E+10 | 0.00 | 0.342391E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.150613E+11 | 78134443.96 | 0.193773E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.406986E+11 | 0.843129E+10 | 0.267454E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.404960E+11 | 0.409931E+10 | 0.378432E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.521199E+11 | 0.383688E+10 | 0.479486E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.639477E+11 | 0.118713E+09 | 0.794848E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.928688E+11 | 0.00 | 0.135751E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.956132E+11 | 0.00 | 0.139215E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.905658E+11 | 0.00 | 0.143176E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.985827E+11 | 0.00 | 0.148707E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.797594E+11 | 0.00 | 0.131486E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.744310E+11 | 1960.52 | 0.113814E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.522700E+11 | 47492045.22 | 0.606307E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.431209E+11 | 0.575025E+10 | 0.412523E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.824474E+12 | 0.222839E+11 | 0.110606E+14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.404960E+11 | 0.00 | 0.267454E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.985827E+11 | 0.843129E+10 | 0.148707E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.341808E+10 | 0.394150E+10 | 0.257704E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.370760E+10 | 0.241973E+10 | 0.378887E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.467302E+10 | 0.174433E+10 | 0.493188E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.627882E+10 | 12979430.47 | 0.847841E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.102022E+11 | 0.00 | 0.150982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.108801E+11 | 0.00 | 0.157677E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.103120E+11 | 0.00 | 0.162030E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.109654E+11 | 0.00 | 0.165969E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.837518E+10 | 0.00 | 0.142064E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.777843E+10 | 20566689.82 | 0.122309E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.461798E+10 | 0.197748E+09 | 0.594080E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.371020E+10 | 0.257711E+10 | 0.397464E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.849189E+11 | 0.109140E+11 | 0.119795E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.341808E+10 | 0.00 | 0.257704E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.109654E+11 | 0.394150E+10 | 0.165969E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.151143E+11 | 0.00 | 0.218968E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.132172E+11 | 0.00 | 0.263542E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.151784E+11 | 0.00 | 0.354979E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.138852E+11 | 0.00 | 0.562278E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.149819E+11 | 0.00 | 0.103677E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.146433E+11 | 0.00 | 0.108815E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.147184E+11 | 0.00 | 0.117942E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.162706E+11 | 0.00 | 0.130714E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.153983E+11 | 0.00 | 0.110906E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.158403E+11 | 0.00 | 0.953928E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.153407E+11 | 0.00 | 0.523303E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.153907E+11 | 0.00 | 0.342941E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.179979E+12 | 0.00 | 0.894049E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.132172E+11 | 0.00 | 0.218968E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.162706E+11 | 0.00 | 0.130714E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.947342E+11 | 0.00 | 0.417507E+12 | 0.00 | 0.857884E+11 | 0.00 | 0.00 | 0.00 | 0.502569E+09 | 0.00 | 0.00 | 0.00 |
February | 0.855664E+11 | 0.00 | 0.655626E+12 | 0.00 | 0.132873E+12 | 0.00 | 0.00 | 0.00 | 0.351114E+09 | 0.00 | 0.00 | 0.00 |
March | 0.947342E+11 | 0.00 | 0.103627E+13 | 0.00 | 0.212843E+12 | 0.00 | 0.00 | 0.00 | 0.227752E+09 | 0.00 | 0.00 | 0.00 |
April | 0.916783E+11 | 0.00 | 0.132691E+13 | 0.00 | 0.290624E+12 | 0.00 | 0.00 | 0.00 | 62952719.63 | 0.00 | 0.00 | 0.00 |
May | 0.947342E+11 | 0.00 | 0.465550E+12 | 0.00 | 0.116550E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.916783E+11 | 0.00 | 0.769888E+12 | 0.00 | 0.193659E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.947342E+11 | 0.00 | 0.112650E+13 | 0.00 | 0.284092E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.947342E+11 | 0.00 | 0.143361E+13 | 0.00 | 0.352864E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.916783E+11 | 0.00 | 0.453994E+12 | 0.00 | 0.111896E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.947342E+11 | 0.00 | 0.776661E+12 | 0.00 | 0.183038E+12 | 0.00 | 0.00 | 0.00 | 53688292.87 | 0.00 | 0.00 | 0.00 |
November | 0.916783E+11 | 0.00 | 0.101872E+13 | 0.00 | 0.214475E+12 | 0.00 | 0.00 | 0.00 | 80917418.96 | 0.00 | 0.00 | 0.00 |
December | 0.947342E+11 | 0.00 | 0.133796E+13 | 0.00 | 0.267171E+12 | 0.00 | 0.00 | 0.00 | 0.257510E+09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.111542E+13 | 0.00 | 0.108192E+14 | 0.00 | 0.244587E+13 | 0.00 | 0.00 | 0.00 | 0.153650E+10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.855664E+11 | 0.00 | 0.417507E+12 | 0.00 | 0.857884E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.947342E+11 | 0.00 | 0.143361E+13 | 0.00 | 0.352864E+12 | 0.00 | 0.00 | 0.00 | 0.502569E+09 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.139709E+10 | 0.00 | 0.658165E+10 | 0.00 | 0.135569E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.126188E+10 | 0.00 | 0.120621E+11 | 0.00 | 0.242875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.139709E+10 | 0.00 | 0.198537E+11 | 0.00 | 0.403685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.135202E+10 | 0.00 | 0.262259E+11 | 0.00 | 0.567964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139709E+10 | 0.00 | 0.870458E+10 | 0.00 | 0.213719E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.135202E+10 | 0.00 | 0.150682E+11 | 0.00 | 0.371859E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.139709E+10 | 0.00 | 0.223780E+11 | 0.00 | 0.554200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.139709E+10 | 0.00 | 0.290556E+11 | 0.00 | 0.711090E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.135202E+10 | 0.00 | 0.843577E+10 | 0.00 | 0.203724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.139709E+10 | 0.00 | 0.149766E+11 | 0.00 | 0.347400E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.135202E+10 | 0.00 | 0.196834E+11 | 0.00 | 0.409321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.139709E+10 | 0.00 | 0.260067E+11 | 0.00 | 0.514964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.164496E+11 | 0.00 | 0.209032E+12 | 0.00 | 0.467637E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.126188E+10 | 0.00 | 0.658165E+10 | 0.00 | 0.135569E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.139709E+10 | 0.00 | 0.290556E+11 | 0.00 | 0.711090E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.132773E+11 | 0.00 | 0.508414E+11 | 0.00 | 0.106336E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.119924E+11 | 0.00 | 0.106059E+12 | 0.00 | 0.215230E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.132773E+11 | 0.00 | 0.182524E+12 | 0.00 | 0.373124E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128490E+11 | 0.00 | 0.249013E+12 | 0.00 | 0.539815E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.132773E+11 | 0.00 | 0.817882E+11 | 0.00 | 0.200938E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.128490E+11 | 0.00 | 0.143704E+12 | 0.00 | 0.354574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.132773E+11 | 0.00 | 0.213543E+12 | 0.00 | 0.528726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.132773E+11 | 0.00 | 0.276068E+12 | 0.00 | 0.675803E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128490E+11 | 0.00 | 0.780957E+11 | 0.00 | 0.188865E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.132773E+11 | 0.00 | 0.140670E+12 | 0.00 | 0.327005E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.128490E+11 | 0.00 | 0.182102E+12 | 0.00 | 0.380433E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.132773E+11 | 0.00 | 0.238969E+12 | 0.00 | 0.476051E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.156330E+12 | 0.00 | 0.194338E+13 | 0.00 | 0.436690E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.119924E+11 | 0.00 | 0.508414E+11 | 0.00 | 0.106336E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.132773E+11 | 0.00 | 0.276068E+12 | 0.00 | 0.675803E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.135421E+10 | 0.00 | 0.379174E+10 | 0.00 | 0.809863E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.122315E+10 | 0.00 | 0.970467E+10 | 0.00 | 0.198835E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.135421E+10 | 0.00 | 0.176362E+11 | 0.00 | 0.363163E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.131052E+10 | 0.00 | 0.247979E+11 | 0.00 | 0.539456E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.135421E+10 | 0.00 | 0.835925E+10 | 0.00 | 0.205537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.131052E+10 | 0.00 | 0.145662E+11 | 0.00 | 0.359719E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.135421E+10 | 0.00 | 0.215733E+11 | 0.00 | 0.534739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.135421E+10 | 0.00 | 0.278218E+11 | 0.00 | 0.682412E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.131052E+10 | 0.00 | 0.796071E+10 | 0.00 | 0.192771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.135421E+10 | 0.00 | 0.140447E+11 | 0.00 | 0.327579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.131052E+10 | 0.00 | 0.177018E+11 | 0.00 | 0.372249E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.135421E+10 | 0.00 | 0.229863E+11 | 0.00 | 0.461828E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.159447E+11 | 0.00 | 0.190944E+12 | 0.00 | 0.431927E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.122315E+10 | 0.00 | 0.379174E+10 | 0.00 | 0.809863E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.135421E+10 | 0.00 | 0.278218E+11 | 0.00 | 0.682412E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.294843E+09 | 0.156221E+10 | 0.00 | 0.102668E+09 | 0.00 | 0.00 | 0.566564E+11 | 0.00 | 0.98 |
February | 0.225278E+09 | 0.158565E+10 | 0.00 | 80431359.77 | 3899243.67 | 0.00 | 0.429519E+11 | 0.00 | 1.07 |
March | 0.140611E+09 | 0.323684E+10 | 0.00 | 85931506.76 | 7394895.87 | 0.00 | 0.458338E+11 | 0.00 | 1.08 |
April | 0.139339E+09 | 0.568647E+10 | 0.00 | 57897958.13 | 73823185.45 | 0.00 | 0.209665E+11 | 0.00 | 0.94 |
May | 2177251.66 | 0.263903E+11 | 0.00 | 1477259.60 | 0.151749E+09 | 0.00 | 50393268.98 | 0.00 | 0.34 |
June | 3262071.92 | 0.319195E+11 | 0.00 | 2272378.28 | 0.210620E+09 | 0.00 | 0.151259E+09 | 0.00 | 0.36 |
July | 0.00 | 0.387442E+11 | 0.00 | 0.00 | 0.409581E+09 | 0.00 | 0.00 | 0.00 | 0.31 |
August | 0.00 | 0.396452E+11 | 0.00 | 155258.92 | 0.234963E+09 | 0.00 | 11290501.41 | 0.00 | 0.34 |
September | 1371945.20 | 0.294477E+11 | 0.00 | 1564247.73 | 0.294490E+09 | 0.00 | 0.136254E+09 | 0.00 | 0.34 |
October | 0.130875E+09 | 0.222595E+11 | 0.00 | 39048133.73 | 0.231871E+09 | 0.00 | 0.125914E+11 | 0.00 | 0.68 |
November | 0.241434E+09 | 0.663252E+10 | 0.00 | 93823836.95 | 8365468.69 | 0.00 | 0.373023E+11 | 0.00 | 1.14 |
December | 0.326302E+09 | 0.422008E+10 | 0.00 | 97015428.70 | 11211159.27 | 0.00 | 0.507271E+11 | 0.00 | 0.96 |
Annual Sum or Average | 0.150549E+10 | 0.211330E+12 | 0.00 | 0.562285E+09 | 0.163797E+10 | 0.00 | 0.267379E+12 | 0.00 | 0.71 |
Minimum of Months | 0.00 | 0.156221E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
Maximum of Months | 0.326302E+09 | 0.396452E+11 | 0.00 | 0.102668E+09 | 0.409581E+09 | 0.00 | 0.566564E+11 | 0.00 | 1.14 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.216531E+10 | 0.129778E+10 | 0.00 | 65802497.98 | 0.00 | 0.00 | 0.365343E+11 | 0.00 | 0.63 |
February | 0.223284E+10 | 0.139639E+10 | 0.00 | 59722707.64 | 10060613.65 | 0.00 | 0.262459E+11 | 0.00 | 0.69 |
March | 0.259117E+10 | 0.247915E+10 | 0.00 | 68360700.38 | 46531758.95 | 0.00 | 0.328359E+11 | 0.00 | 0.76 |
April | 0.521991E+10 | 0.404203E+10 | 0.00 | 38832363.57 | 41815637.12 | 0.00 | 0.117190E+11 | 0.00 | 0.69 |
May | 0.00 | 0.106809E+11 | 0.00 | 0.00 | 0.109595E+09 | 0.00 | 0.00 | 0.00 | 0.26 |
June | 25371720.04 | 0.113848E+11 | 0.00 | 129713.15 | 0.115919E+09 | 0.00 | 2255272.27 | 0.00 | 0.26 |
July | 0.00 | 0.135739E+11 | 0.00 | 0.00 | 0.212657E+09 | 0.00 | 0.00 | 0.00 | 0.24 |
August | 58250652.66 | 0.140694E+11 | 0.00 | 0.00 | 0.139004E+09 | 0.00 | 0.00 | 0.00 | 0.27 |
September | 0.00 | 0.131766E+11 | 0.00 | 0.00 | 0.230498E+09 | 0.00 | 0.00 | 0.00 | 0.26 |
October | 0.110263E+10 | 0.860759E+10 | 0.00 | 22515527.59 | 0.145309E+09 | 0.00 | 0.790051E+10 | 0.00 | 0.43 |
November | 0.366004E+10 | 0.368868E+10 | 0.00 | 62902178.60 | 32021022.64 | 0.00 | 0.242554E+11 | 0.00 | 0.78 |
December | 0.417318E+10 | 0.312440E+10 | 0.00 | 66988301.28 | 45722884.09 | 0.00 | 0.350252E+11 | 0.00 | 0.68 |
Annual Sum or Average | 0.212287E+11 | 0.875218E+11 | 0.00 | 0.385254E+09 | 0.112914E+10 | 0.00 | 0.174519E+12 | 0.00 | 0.49 |
Minimum of Months | 0.00 | 0.129778E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.24 |
Maximum of Months | 0.521991E+10 | 0.140694E+11 | 0.00 | 68360700.38 | 0.230498E+09 | 0.00 | 0.365343E+11 | 0.00 | 0.78 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.643631E+11 | 0.120606E+11 | 0.00 | 0.359167E+09 | 0.00 | 0.00 | 0.224751E+12 | 0.00 | 0.50 |
February | 0.350357E+11 | 0.128570E+11 | 0.00 | 0.341813E+09 | 96467075.04 | 0.00 | 0.168170E+12 | 0.00 | 0.53 |
March | 0.265324E+11 | 0.226701E+11 | 0.00 | 0.430078E+09 | 0.748571E+09 | 0.00 | 0.223812E+12 | 0.00 | 0.57 |
April | 0.137313E+11 | 0.381975E+11 | 0.00 | 0.313727E+09 | 0.415253E+09 | 0.00 | 0.907754E+11 | 0.00 | 0.51 |
May | 0.00 | 0.105561E+12 | 0.00 | 0.00 | 0.109275E+10 | 0.00 | 0.00 | 0.00 | 0.26 |
June | 0.163701E+09 | 0.112591E+12 | 0.00 | 4348758.31 | 0.115859E+10 | 0.00 | 46491242.35 | 0.00 | 0.27 |
July | 0.00 | 0.133000E+12 | 0.00 | 0.00 | 0.213051E+10 | 0.00 | 0.00 | 0.00 | 0.24 |
August | 0.00 | 0.136241E+12 | 0.00 | 0.00 | 0.128488E+10 | 0.00 | 0.00 | 0.00 | 0.27 |
September | 0.00 | 0.129016E+12 | 0.00 | 0.00 | 0.223000E+10 | 0.00 | 0.00 | 0.00 | 0.26 |
October | 0.786834E+10 | 0.846052E+11 | 0.00 | 0.167964E+09 | 0.145199E+10 | 0.00 | 0.615518E+11 | 0.00 | 0.38 |
November | 0.212389E+11 | 0.356595E+11 | 0.00 | 0.401447E+09 | 0.326357E+09 | 0.00 | 0.167630E+12 | 0.00 | 0.58 |
December | 0.452938E+11 | 0.290139E+11 | 0.00 | 0.342754E+09 | 0.979951E+09 | 0.00 | 0.199784E+12 | 0.00 | 0.47 |
Annual Sum or Average | 0.214227E+12 | 0.851473E+12 | 0.00 | 0.236130E+10 | 0.119153E+11 | 0.00 | 0.113652E+13 | 0.00 | 0.40 |
Minimum of Months | 0.00 | 0.120606E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.24 |
Maximum of Months | 0.643631E+11 | 0.136241E+12 | 0.00 | 0.430078E+09 | 0.223000E+10 | 0.00 | 0.224751E+12 | 0.00 | 0.58 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.125170E+11 | 0.125632E+10 | 0.00 | 13057530.60 | 52426210.54 | 31285411.96 | 0.951765E+10 | 0.00 | 0.43 |
February | 0.721584E+10 | 0.131532E+10 | 0.00 | 17297986.31 | 33920142.90 | 72838448.51 | 0.901699E+10 | 0.00 | 0.47 |
March | 0.637784E+10 | 0.236849E+10 | 0.00 | 25172792.99 | 46944772.37 | 9565311.94 | 0.137725E+11 | 0.00 | 0.51 |
April | 0.172190E+10 | 0.378956E+10 | 0.00 | 24650542.65 | 45079647.12 | 0.00 | 0.726650E+10 | 0.00 | 0.48 |
May | 0.00 | 0.103987E+11 | 0.00 | 0.00 | 0.110753E+09 | 0.00 | 0.00 | 0.00 | 0.26 |
June | 4874384.35 | 0.110911E+11 | 0.00 | 333223.49 | 0.111340E+09 | 0.00 | 2531420.13 | 0.00 | 0.26 |
July | 0.00 | 0.131946E+11 | 0.00 | 0.00 | 0.264556E+09 | 0.00 | 0.00 | 0.00 | 0.24 |
August | 0.00 | 0.133644E+11 | 0.00 | 0.00 | 0.171705E+09 | 0.00 | 0.00 | 0.00 | 0.27 |
September | 0.00 | 0.127175E+11 | 0.00 | 0.00 | 0.226776E+09 | 0.00 | 0.00 | 0.00 | 0.26 |
October | 0.114616E+10 | 0.815973E+10 | 0.00 | 13491908.54 | 0.142337E+09 | 0.00 | 0.465009E+10 | 0.00 | 0.37 |
November | 0.509633E+10 | 0.339497E+10 | 0.00 | 24174547.54 | 71533771.49 | 0.00 | 0.103237E+11 | 0.00 | 0.52 |
December | 0.100787E+11 | 0.287028E+10 | 0.00 | 12397629.62 | 66852893.03 | 1314971.86 | 0.800285E+10 | 0.00 | 0.41 |
Annual Sum or Average | 0.441586E+11 | 0.839209E+11 | 0.00 | 0.130576E+09 | 0.134422E+10 | 0.115004E+09 | 0.625528E+11 | 0.00 | 0.37 |
Minimum of Months | 0.00 | 0.125632E+10 | 0.00 | 0.00 | 33920142.90 | 0.00 | 0.00 | 0.00 | 0.24 |
Maximum of Months | 0.125170E+11 | 0.133644E+11 | 0.00 | 25172792.99 | 0.264556E+09 | 72838448.51 | 0.137725E+11 | 0.00 | 0.52 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.231288E+10 | 0.159733E+09 | 0.00 | 1500153.10 | 0.00 | 0.00 | 0.105398E+10 | 0.00 | 0.46 |
February | 0.142479E+10 | 0.182227E+09 | 0.00 | 2538188.81 | 1262470.80 | 0.00 | 0.116795E+10 | 0.00 | 0.54 |
March | 0.136886E+10 | 0.352986E+09 | 0.00 | 3588273.40 | 5839105.74 | 0.00 | 0.181768E+10 | 0.00 | 0.61 |
April | 0.808924E+09 | 0.623594E+09 | 0.00 | 3602656.09 | 5247296.30 | 0.00 | 0.103732E+10 | 0.00 | 0.68 |
May | 0.00 | 0.196842E+10 | 0.00 | 0.00 | 13752734.94 | 0.00 | 0.00 | 0.00 | 0.38 |
June | 3237466.89 | 0.227811E+10 | 0.00 | 3117.28 | 14546208.71 | 0.00 | 79166.71 | 0.00 | 0.42 |
July | 0.00 | 0.265511E+10 | 0.00 | 0.00 | 26685600.88 | 0.00 | 0.00 | 0.00 | 0.37 |
August | 7309668.24 | 0.256170E+10 | 0.00 | 0.00 | 17443166.60 | 0.00 | 0.00 | 0.00 | 0.39 |
September | 0.00 | 0.218726E+10 | 0.00 | 0.00 | 28924440.03 | 0.00 | 0.00 | 0.00 | 0.34 |
October | 0.279130E+09 | 0.144981E+10 | 0.00 | 1885933.16 | 18234339.70 | 0.00 | 0.669477E+09 | 0.00 | 0.47 |
November | 0.984686E+09 | 0.509907E+09 | 0.00 | 4081382.28 | 4018204.80 | 0.00 | 0.163106E+10 | 0.00 | 0.64 |
December | 0.187843E+10 | 0.403760E+09 | 0.00 | 2298667.85 | 5737602.90 | 0.00 | 0.135277E+10 | 0.00 | 0.50 |
Annual Sum or Average | 0.906823E+10 | 0.153326E+11 | 0.00 | 19498371.99 | 0.141691E+09 | 0.00 | 0.873032E+10 | 0.00 | 0.48 |
Minimum of Months | 0.00 | 0.159733E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.34 |
Maximum of Months | 0.231288E+10 | 0.265511E+10 | 0.00 | 4081382.28 | 28924440.03 | 0.00 | 0.181768E+10 | 0.00 | 0.68 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.130643E+10 | 0.120080E+09 | 0.00 | 2294894.24 | 790885.51 | 0.00 | 0.161425E+10 | 0.00 | 0.60 |
February | 0.986404E+09 | 0.140503E+09 | 0.00 | 2601165.82 | 989750.02 | 0.00 | 0.126597E+10 | 0.00 | 0.71 |
March | 0.107627E+10 | 0.269656E+09 | 0.00 | 3550459.95 | 6957834.22 | 0.00 | 0.176028E+10 | 0.00 | 0.84 |
April | 0.679854E+09 | 0.478346E+09 | 0.00 | 2973903.54 | 5004246.48 | 0.00 | 0.981182E+09 | 0.00 | 0.88 |
May | 0.00 | 0.156300E+10 | 0.00 | 0.00 | 10781849.14 | 0.00 | 0.00 | 0.00 | 0.48 |
June | 2602613.47 | 0.172568E+10 | 0.00 | 0.00 | 11403915.56 | 0.00 | 0.00 | 0.00 | 0.49 |
July | 0.00 | 0.197123E+10 | 0.00 | 0.00 | 20920938.58 | 0.00 | 0.00 | 0.00 | 0.43 |
August | 5730623.08 | 0.178475E+10 | 0.00 | 0.00 | 13675068.39 | 0.00 | 0.00 | 0.00 | 0.42 |
September | 0.00 | 0.163506E+10 | 0.00 | 0.00 | 22676140.44 | 0.00 | 0.00 | 0.00 | 0.40 |
October | 0.219604E+09 | 0.110663E+10 | 0.00 | 1541298.30 | 14295331.13 | 0.00 | 0.543583E+09 | 0.00 | 0.57 |
November | 0.839862E+09 | 0.362736E+09 | 0.00 | 3341739.08 | 3150186.36 | 0.00 | 0.141157E+10 | 0.00 | 0.80 |
December | 0.157405E+10 | 0.246938E+09 | 0.00 | 1930139.32 | 7464066.22 | 0.00 | 0.110562E+10 | 0.00 | 0.61 |
Annual Sum or Average | 0.669080E+10 | 0.114046E+11 | 0.00 | 18233600.24 | 0.118110E+09 | 0.00 | 0.868247E+10 | 0.00 | 0.60 |
Minimum of Months | 0.00 | 0.120080E+09 | 0.00 | 0.00 | 790885.51 | 0.00 | 0.00 | 0.00 | 0.40 |
Maximum of Months | 0.157405E+10 | 0.197123E+10 | 0.00 | 3550459.95 | 22676140.44 | 0.00 | 0.176028E+10 | 0.00 | 0.88 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.110108E+10 | 0.271342E+09 | 0.00 | 10579293.86 | 0.00 | 0.00 | 0.553334E+10 | 0.00 | 0.94 |
February | 0.816444E+09 | 0.358026E+09 | 0.00 | 7528306.78 | 1264680.74 | 0.00 | 0.348807E+10 | 0.00 | 0.94 |
March | 0.113674E+10 | 0.484761E+09 | 0.00 | 6574725.11 | 5849327.02 | 0.00 | 0.310946E+10 | 0.00 | 0.88 |
April | 0.793591E+09 | 0.735354E+09 | 0.00 | 4380486.13 | 5256481.63 | 0.00 | 0.123164E+10 | 0.00 | 0.79 |
May | 0.00 | 0.199545E+10 | 0.00 | 0.00 | 13776808.93 | 0.00 | 0.00 | 0.00 | 0.39 |
June | 3243134.04 | 0.219353E+10 | 0.00 | 2535.00 | 14571671.66 | 0.00 | 79893.02 | 0.00 | 0.40 |
July | 0.00 | 0.262142E+10 | 0.00 | 0.00 | 26732313.69 | 0.00 | 0.00 | 0.00 | 0.37 |
August | 7322463.72 | 0.277065E+10 | 0.00 | 0.00 | 17473700.65 | 0.00 | 0.00 | 0.00 | 0.42 |
September | 0.00 | 0.265075E+10 | 0.00 | 0.00 | 28975071.90 | 0.00 | 0.00 | 0.00 | 0.42 |
October | 0.194038E+09 | 0.210207E+10 | 0.00 | 3541094.53 | 15394254.57 | 0.00 | 0.110209E+10 | 0.00 | 0.70 |
November | 0.540748E+09 | 0.827477E+09 | 0.00 | 11785343.76 | 4025238.62 | 0.00 | 0.410811E+10 | 0.00 | 1.17 |
December | 0.110637E+10 | 0.655597E+09 | 0.00 | 10255178.25 | 5747646.50 | 0.00 | 0.477396E+10 | 0.00 | 0.98 |
Annual Sum or Average | 0.569958E+10 | 0.176664E+11 | 0.00 | 54646963.42 | 0.139067E+09 | 0.00 | 0.233468E+11 | 0.00 | 0.70 |
Minimum of Months | 0.00 | 0.271342E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 |
Maximum of Months | 0.113674E+10 | 0.277065E+10 | 0.00 | 11785343.76 | 28975071.90 | 0.00 | 0.553334E+10 | 0.00 | 1.17 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.143801E+10 | 0.190439E+09 | 0.00 | 4124543.78 | 0.00 | 0.00 | 0.261917E+10 | 0.00 | 0.88 |
February | 0.595650E+09 | 0.242414E+09 | 0.00 | 6142063.15 | 194898.94 | 0.00 | 0.274294E+10 | 0.00 | 1.12 |
March | 0.461888E+09 | 0.448384E+09 | 0.00 | 8861673.49 | 2962655.49 | 0.00 | 0.409334E+10 | 0.00 | 1.39 |
April | 0.393986E+09 | 0.897782E+09 | 0.00 | 8886650.00 | 885290.06 | 0.00 | 0.221549E+10 | 0.00 | 1.51 |
May | 0.00 | 0.190415E+10 | 0.00 | 0.00 | 10527361.98 | 0.00 | 0.00 | 0.00 | 0.58 |
June | 2364817.68 | 0.230667E+10 | 0.00 | 43921.67 | 4362501.01 | 0.00 | 1231916.50 | 0.00 | 0.67 |
July | 0.00 | 0.284310E+10 | 0.00 | 0.00 | 7078995.34 | 0.00 | 0.00 | 0.00 | 0.62 |
August | 0.00 | 0.311060E+10 | 0.00 | 33128.52 | 4288592.34 | 0.00 | 7482000.07 | 0.00 | 0.73 |
September | 0.00 | 0.221345E+10 | 0.00 | 0.00 | 18432236.30 | 0.00 | 0.00 | 0.00 | 0.54 |
October | 0.123596E+09 | 0.161654E+10 | 0.00 | 3136373.24 | 13491183.58 | 0.00 | 0.103278E+10 | 0.00 | 0.86 |
November | 0.418723E+09 | 0.648276E+09 | 0.00 | 8795392.76 | 1077982.32 | 0.00 | 0.320383E+10 | 0.00 | 1.37 |
December | 0.499331E+09 | 0.567455E+09 | 0.00 | 8747097.77 | 5790281.45 | 0.00 | 0.434632E+10 | 0.00 | 1.20 |
Annual Sum or Average | 0.393355E+10 | 0.169893E+11 | 0.00 | 48770844.38 | 69091978.81 | 0.00 | 0.202626E+11 | 0.00 | 0.95 |
Minimum of Months | 0.00 | 0.190439E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.54 |
Maximum of Months | 0.143801E+10 | 0.311060E+10 | 0.00 | 8886650.00 | 18432236.30 | 0.00 | 0.434632E+10 | 0.00 | 1.51 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.244271E+11 | 0.121826E+10 | 0.00 | 2634565.42 | 0.190172E+09 | 0.261359E+10 | 0.182704E+10 | 0.00 | 0.41 |
February | 0.164610E+11 | 0.151918E+10 | 0.00 | 5674478.41 | 57409523.56 | 0.107739E+10 | 0.289950E+10 | 0.00 | 0.44 |
March | 0.179516E+11 | 0.294616E+10 | 0.00 | 10193427.74 | 0.201571E+09 | 0.894865E+09 | 0.485219E+10 | 0.00 | 0.46 |
April | 0.567048E+10 | 0.578415E+10 | 0.00 | 18969701.91 | 0.107209E+09 | 0.00 | 0.500772E+10 | 0.00 | 0.49 |
May | 0.00 | 0.200696E+11 | 0.00 | 0.00 | 0.137377E+09 | 0.00 | 0.00 | 0.00 | 0.40 |
June | 22681844.76 | 0.238103E+11 | 0.00 | 131398.87 | 0.145654E+09 | 0.00 | 336693.09 | 0.00 | 0.45 |
July | 0.00 | 0.280017E+11 | 0.00 | 0.00 | 0.267841E+09 | 0.00 | 0.00 | 0.00 | 0.41 |
August | 0.00 | 0.265448E+11 | 0.00 | 0.00 | 0.161532E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
September | 0.00 | 0.218217E+11 | 0.00 | 0.00 | 0.280348E+09 | 0.00 | 0.00 | 0.00 | 0.35 |
October | 0.340507E+10 | 0.145128E+11 | 0.00 | 11562497.04 | 0.202252E+09 | 0.00 | 0.382261E+10 | 0.00 | 0.42 |
November | 0.138693E+11 | 0.473630E+10 | 0.00 | 13141709.16 | 87979136.82 | 0.00 | 0.485616E+10 | 0.00 | 0.48 |
December | 0.220678E+11 | 0.333689E+10 | 0.00 | 1555776.44 | 0.269435E+09 | 0.147261E+10 | 0.837301E+09 | 0.00 | 0.39 |
Annual Sum or Average | 0.103875E+12 | 0.154302E+12 | 0.00 | 63863554.99 | 0.210878E+10 | 0.605846E+10 | 0.241029E+11 | 0.00 | 0.42 |
Minimum of Months | 0.00 | 0.121826E+10 | 0.00 | 0.00 | 57409523.56 | 0.00 | 0.00 | 0.00 | 0.35 |
Maximum of Months | 0.244271E+11 | 0.280017E+11 | 0.00 | 18969701.91 | 0.280348E+09 | 0.261359E+10 | 0.500772E+10 | 0.00 | 0.49 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.164809E+11 | 0.106202E+10 | 0.00 | 6468156.74 | 0.127077E+09 | 0.123173E+10 | 0.627036E+10 | 0.00 | 0.52 |
February | 0.106112E+11 | 0.138591E+10 | 0.00 | 13002362.46 | 37731022.94 | 0.426570E+09 | 0.669131E+10 | 0.00 | 0.61 |
March | 0.116823E+11 | 0.282017E+10 | 0.00 | 24438372.61 | 0.122450E+09 | 0.664513E+09 | 0.103818E+11 | 0.00 | 0.73 |
April | 0.370321E+10 | 0.554139E+10 | 0.00 | 26417039.67 | 78835623.35 | 0.00 | 0.825614E+10 | 0.00 | 0.78 |
May | 0.00 | 0.171011E+11 | 0.00 | 0.00 | 0.112534E+09 | 0.00 | 0.00 | 0.00 | 0.53 |
June | 18580079.77 | 0.197075E+11 | 0.00 | 78552.12 | 0.119314E+09 | 0.00 | 256531.72 | 0.00 | 0.57 |
July | 0.00 | 0.234504E+11 | 0.00 | 0.00 | 0.219405E+09 | 0.00 | 0.00 | 0.00 | 0.52 |
August | 0.00 | 0.217413E+11 | 0.00 | 0.00 | 0.132321E+09 | 0.00 | 0.00 | 0.00 | 0.53 |
September | 0.00 | 0.177701E+11 | 0.00 | 0.00 | 0.229650E+09 | 0.00 | 0.00 | 0.00 | 0.45 |
October | 0.238684E+10 | 0.124266E+11 | 0.00 | 12400655.44 | 0.159549E+09 | 0.00 | 0.400712E+10 | 0.00 | 0.57 |
November | 0.826977E+10 | 0.395016E+10 | 0.00 | 21421922.74 | 0.125171E+09 | 0.00 | 0.882946E+10 | 0.00 | 0.67 |
December | 0.154029E+11 | 0.248430E+10 | 0.00 | 6829877.04 | 0.297461E+09 | 0.866863E+09 | 0.422584E+10 | 0.00 | 0.50 |
Annual Sum or Average | 0.685557E+11 | 0.129441E+12 | 0.00 | 0.111057E+09 | 0.176150E+10 | 0.318968E+10 | 0.486623E+11 | 0.00 | 0.58 |
Minimum of Months | 0.00 | 0.106202E+10 | 0.00 | 0.00 | 37731022.94 | 0.00 | 0.00 | 0.00 | 0.45 |
Maximum of Months | 0.164809E+11 | 0.234504E+11 | 0.00 | 26417039.67 | 0.297461E+09 | 0.123173E+10 | 0.103818E+11 | 0.00 | 0.78 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.104733E+11 | 0.279461E+10 | 0.00 | 92869806.47 | 11766040.89 | 0.420832E+09 | 0.467883E+11 | 0.00 | 0.86 |
February | 0.779081E+10 | 0.381752E+10 | 0.00 | 59999146.70 | 11428227.43 | 0.148281E+09 | 0.273381E+11 | 0.00 | 0.84 |
March | 0.120168E+11 | 0.477682E+10 | 0.00 | 47985002.35 | 60605653.49 | 0.196228E+09 | 0.208426E+11 | 0.00 | 0.74 |
April | 0.415881E+10 | 0.730639E+10 | 0.00 | 31639252.03 | 94444573.03 | 0.00 | 0.866901E+10 | 0.00 | 0.63 |
May | 0.00 | 0.204221E+11 | 0.00 | 0.00 | 0.137460E+09 | 0.00 | 0.00 | 0.00 | 0.41 |
June | 22695479.32 | 0.227668E+11 | 0.00 | 134634.02 | 0.145742E+09 | 0.00 | 435324.14 | 0.00 | 0.43 |
July | 0.00 | 0.276543E+11 | 0.00 | 0.00 | 0.268002E+09 | 0.00 | 0.00 | 0.00 | 0.40 |
August | 0.00 | 0.295268E+11 | 0.00 | 0.00 | 0.161629E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
September | 0.00 | 0.277230E+11 | 0.00 | 0.00 | 0.280517E+09 | 0.00 | 0.00 | 0.00 | 0.45 |
October | 0.197865E+10 | 0.228185E+11 | 0.00 | 29687653.66 | 0.153116E+09 | 0.00 | 0.876520E+10 | 0.00 | 0.70 |
November | 0.448823E+10 | 0.899409E+10 | 0.00 | 99412343.07 | 40564482.03 | 0.00 | 0.330591E+11 | 0.00 | 1.05 |
December | 0.100799E+11 | 0.696628E+10 | 0.00 | 80513050.23 | 52393708.17 | 0.378088E+09 | 0.347283E+11 | 0.00 | 0.84 |
Annual Sum or Average | 0.510092E+11 | 0.185567E+12 | 0.00 | 0.442241E+09 | 0.141767E+10 | 0.114343E+10 | 0.180191E+12 | 0.00 | 0.65 |
Minimum of Months | 0.00 | 0.279461E+10 | 0.00 | 0.00 | 11428227.43 | 0.00 | 0.00 | 0.00 | 0.40 |
Maximum of Months | 0.120168E+11 | 0.295268E+11 | 0.00 | 99412343.07 | 0.280517E+09 | 0.420832E+09 | 0.467883E+11 | 0.00 | 1.05 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.178373E+11 | 0.149405E+10 | 0.00 | 12863843.35 | 33551757.54 | 0.857749E+09 | 0.833026E+10 | 0.00 | 0.60 |
February | 0.114681E+11 | 0.189248E+10 | 0.00 | 16927847.28 | 11845718.09 | 0.334277E+09 | 0.758687E+10 | 0.00 | 0.69 |
March | 0.127285E+11 | 0.298838E+10 | 0.00 | 24603014.10 | 57016330.04 | 28674461.69 | 0.112177E+11 | 0.00 | 0.77 |
April | 0.272420E+10 | 0.643834E+10 | 0.00 | 30994991.41 | 58292097.71 | 0.00 | 0.810487E+10 | 0.00 | 0.82 |
May | 0.00 | 0.169574E+11 | 0.00 | 0.00 | 0.105137E+09 | 0.00 | 0.00 | 0.00 | 0.53 |
June | 17961882.62 | 0.199024E+11 | 0.00 | 162659.71 | 66593242.83 | 0.00 | 2143485.59 | 0.00 | 0.59 |
July | 0.00 | 0.234452E+11 | 0.00 | 0.00 | 0.115717E+09 | 0.00 | 0.00 | 0.00 | 0.53 |
August | 0.00 | 0.238818E+11 | 0.00 | 0.00 | 0.103316E+09 | 0.00 | 0.00 | 0.00 | 0.59 |
September | 0.00 | 0.192745E+11 | 0.00 | 0.00 | 0.181303E+09 | 0.00 | 0.00 | 0.00 | 0.49 |
October | 0.232445E+10 | 0.134803E+11 | 0.00 | 14603043.40 | 0.119882E+09 | 0.00 | 0.443897E+10 | 0.00 | 0.63 |
November | 0.930447E+10 | 0.472977E+10 | 0.00 | 23341693.03 | 27778783.60 | 0.00 | 0.893131E+10 | 0.00 | 0.76 |
December | 0.168796E+11 | 0.364643E+10 | 0.00 | 11257742.70 | 45764374.36 | 0.393018E+09 | 0.539117E+10 | 0.00 | 0.60 |
Annual Sum or Average | 0.732844E+11 | 0.138131E+12 | 0.00 | 0.134755E+09 | 0.926198E+09 | 0.161372E+10 | 0.540033E+11 | 0.00 | 0.63 |
Minimum of Months | 0.00 | 0.149405E+10 | 0.00 | 0.00 | 11845718.09 | 0.00 | 0.00 | 0.00 | 0.49 |
Maximum of Months | 0.178373E+11 | 0.238818E+11 | 0.00 | 30994991.41 | 0.181303E+09 | 0.857749E+09 | 0.112177E+11 | 0.00 | 0.82 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.181438E+10 | 0.127072E+09 | 0.00 | 144631.31 | 26526125.75 | 0.711863E+09 | 74951204.38 | 0.00 | 0.40 |
February | 0.128356E+10 | 0.148065E+09 | 0.00 | 321536.23 | 14238526.74 | 0.377445E+09 | 0.177067E+09 | 0.00 | 0.42 |
March | 0.165532E+10 | 0.284195E+09 | 0.00 | 661331.58 | 34445733.16 | 0.249419E+09 | 0.277203E+09 | 0.00 | 0.45 |
April | 0.538771E+09 | 0.555928E+09 | 0.00 | 1690521.38 | 19065865.21 | 0.00 | 0.442122E+09 | 0.00 | 0.48 |
May | 0.00 | 0.194580E+10 | 0.00 | 0.00 | 13903747.28 | 0.00 | 0.00 | 0.00 | 0.39 |
June | 795245.20 | 0.227648E+10 | 0.00 | 10156.54 | 15463323.14 | 0.00 | 9473.89 | 0.00 | 0.43 |
July | 0.00 | 0.269503E+10 | 0.00 | 0.00 | 33212112.56 | 0.00 | 0.00 | 0.00 | 0.39 |
August | 0.00 | 0.255652E+10 | 0.00 | 0.00 | 21555709.82 | 0.00 | 0.00 | 0.00 | 0.41 |
September | 0.00 | 0.213079E+10 | 0.00 | 0.00 | 30527715.48 | 0.00 | 0.00 | 0.00 | 0.35 |
October | 0.321630E+09 | 0.138847E+10 | 0.00 | 1002537.19 | 21599212.30 | 0.00 | 0.314022E+09 | 0.00 | 0.41 |
November | 0.127377E+10 | 0.417113E+09 | 1356474.06 | 913075.98 | 41489630.51 | 40517188.25 | 0.361402E+09 | 3920.38 | 0.46 |
December | 0.160482E+10 | 0.297382E+09 | 243593.85 | 70935.59 | 55467870.07 | 0.520276E+09 | 37146241.80 | 2998.65 | 0.38 |
Annual Sum or Average | 0.849305E+10 | 0.148228E+11 | 1600067.91 | 4814725.79 | 0.327496E+09 | 0.189952E+10 | 0.168392E+10 | 6919.03 | 0.42 |
Minimum of Months | 0.00 | 0.127072E+09 | 0.00 | 0.00 | 13903747.28 | 0.00 | 0.00 | 0.00 | 0.35 |
Maximum of Months | 0.181438E+10 | 0.269503E+10 | 1356474.06 | 1690521.38 | 55467870.07 | 0.711863E+09 | 0.442122E+09 | 3920.38 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.165722E+10 | 0.119597E+09 | 0.00 | 219619.20 | 15517990.67 | 0.269478E+09 | 0.194196E+09 | 0.00 | 0.52 |
February | 0.101915E+10 | 0.144142E+09 | 0.00 | 874650.92 | 7403987.45 | 0.122479E+09 | 0.419812E+09 | 0.00 | 0.59 |
March | 0.996096E+09 | 0.289362E+09 | 0.00 | 2105140.05 | 18101682.61 | 0.144527E+09 | 0.875952E+09 | 0.00 | 0.70 |
April | 0.299272E+09 | 0.545053E+09 | 0.00 | 2606021.54 | 11571305.13 | 0.00 | 0.808864E+09 | 0.00 | 0.78 |
May | 0.00 | 0.167669E+10 | 0.00 | 0.00 | 11371044.83 | 0.00 | 0.00 | 0.00 | 0.52 |
June | 580948.58 | 0.190585E+10 | 0.00 | 6334.10 | 12878975.03 | 0.00 | 75098.70 | 0.00 | 0.56 |
July | 0.00 | 0.228154E+10 | 0.00 | 0.00 | 24277801.69 | 0.00 | 0.00 | 0.00 | 0.51 |
August | 0.00 | 0.212401E+10 | 0.00 | 0.00 | 17629128.15 | 0.00 | 0.00 | 0.00 | 0.53 |
September | 0.00 | 0.175872E+10 | 0.00 | 0.00 | 30868391.54 | 0.00 | 0.00 | 0.00 | 0.45 |
October | 0.223878E+09 | 0.120976E+10 | 0.00 | 1185224.22 | 17036076.09 | 0.00 | 0.342906E+09 | 0.00 | 0.57 |
November | 0.761467E+09 | 0.372744E+09 | 0.00 | 1658562.05 | 28774039.54 | 13045512.51 | 0.703362E+09 | 0.00 | 0.64 |
December | 0.133978E+10 | 0.236941E+09 | 0.00 | 361851.15 | 45530756.24 | 0.272763E+09 | 0.164803E+09 | 0.00 | 0.49 |
Annual Sum or Average | 0.629744E+10 | 0.126644E+11 | 0.00 | 9017403.22 | 0.240961E+09 | 0.822293E+09 | 0.350997E+10 | 0.00 | 0.57 |
Minimum of Months | 0.00 | 0.119597E+09 | 0.00 | 0.00 | 7403987.45 | 0.00 | 0.00 | 0.00 | 0.45 |
Maximum of Months | 0.165722E+10 | 0.228154E+10 | 0.00 | 2606021.54 | 45530756.24 | 0.272763E+09 | 0.875952E+09 | 0.00 | 0.78 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.882401E+09 | 0.317877E+09 | 0.00 | 7558440.09 | 4500544.85 | 0.206552E+09 | 0.350554E+10 | 0.00 | 0.75 |
February | 0.723924E+09 | 0.391791E+09 | 0.00 | 4699842.41 | 1425432.40 | 0.110905E+09 | 0.216795E+10 | 0.00 | 0.76 |
March | 0.107844E+10 | 0.472536E+09 | 0.00 | 4080860.31 | 13648290.41 | 0.143708E+09 | 0.179425E+10 | 0.00 | 0.70 |
April | 0.417017E+09 | 0.698123E+09 | 0.00 | 2990483.47 | 14890473.91 | 0.00 | 0.799304E+09 | 0.00 | 0.62 |
May | 0.00 | 0.197699E+10 | 0.00 | 0.00 | 13892465.47 | 0.00 | 0.00 | 0.00 | 0.40 |
June | 709768.39 | 0.217859E+10 | 0.00 | 10843.18 | 15894574.91 | 0.00 | 94524.29 | 0.00 | 0.41 |
July | 0.00 | 0.265822E+10 | 0.00 | 0.00 | 33185163.49 | 0.00 | 0.00 | 0.00 | 0.39 |
August | 0.00 | 0.283149E+10 | 0.00 | 0.00 | 21538219.03 | 0.00 | 0.00 | 0.00 | 0.45 |
September | 0.00 | 0.269012E+10 | 0.00 | 0.00 | 26503740.12 | 0.00 | 0.00 | 0.00 | 0.44 |
October | 0.198963E+09 | 0.216302E+10 | 0.00 | 2968782.45 | 14544047.79 | 0.00 | 0.750720E+09 | 0.00 | 0.68 |
November | 0.454467E+09 | 0.847354E+09 | 0.00 | 8421404.60 | 8114729.06 | 149694.76 | 0.295575E+10 | 0.00 | 0.99 |
December | 0.947909E+09 | 0.659562E+09 | 0.00 | 6236878.57 | 17359928.32 | 0.131350E+09 | 0.268231E+10 | 0.00 | 0.78 |
Annual Sum or Average | 0.470383E+10 | 0.178857E+11 | 0.00 | 36967535.08 | 0.185498E+09 | 0.592664E+09 | 0.146559E+11 | 0.00 | 0.61 |
Minimum of Months | 0.00 | 0.317877E+09 | 0.00 | 0.00 | 1425432.40 | 0.00 | 0.00 | 0.00 | 0.39 |
Maximum of Months | 0.107844E+10 | 0.283149E+10 | 0.00 | 8421404.60 | 33185163.49 | 0.206552E+09 | 0.350554E+10 | 0.00 | 0.99 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.159503E+10 | 0.159715E+09 | 0.00 | 810080.97 | 9410611.45 | 0.310597E+09 | 0.576542E+09 | 0.00 | 0.61 |
February | 0.104065E+10 | 0.193410E+09 | 0.00 | 1192129.07 | 3442341.55 | 0.150890E+09 | 0.608632E+09 | 0.00 | 0.68 |
March | 0.125836E+10 | 0.291992E+09 | 0.00 | 2056970.25 | 13707123.34 | 0.119423E+09 | 0.940374E+09 | 0.00 | 0.77 |
April | 0.325693E+09 | 0.615493E+09 | 0.00 | 2762305.63 | 8718335.93 | 0.00 | 0.722337E+09 | 0.00 | 0.81 |
May | 0.00 | 0.162269E+10 | 0.00 | 0.00 | 9276654.48 | 0.00 | 0.00 | 0.00 | 0.51 |
June | 653625.76 | 0.186665E+10 | 0.00 | 14199.36 | 5518383.19 | 0.00 | 98341.21 | 0.00 | 0.56 |
July | 0.00 | 0.221937E+10 | 0.00 | 0.00 | 12266853.32 | 0.00 | 0.00 | 0.00 | 0.50 |
August | 0.00 | 0.226070E+10 | 0.00 | 0.00 | 12908024.60 | 0.00 | 0.00 | 0.00 | 0.56 |
September | 0.00 | 0.186421E+10 | 0.00 | 0.00 | 23839593.06 | 0.00 | 0.00 | 0.00 | 0.47 |
October | 0.237326E+09 | 0.127365E+10 | 0.00 | 1439498.47 | 13302449.74 | 0.00 | 0.384740E+09 | 0.00 | 0.62 |
November | 0.979667E+09 | 0.437517E+09 | 0.00 | 1826425.59 | 15553036.70 | 7044191.72 | 0.727576E+09 | 0.00 | 0.74 |
December | 0.148456E+10 | 0.340356E+09 | 0.00 | 795931.30 | 23754407.76 | 0.201694E+09 | 0.397005E+09 | 0.00 | 0.60 |
Annual Sum or Average | 0.692193E+10 | 0.131457E+11 | 0.00 | 10897540.64 | 0.151698E+09 | 0.789648E+09 | 0.435731E+10 | 0.00 | 0.62 |
Minimum of Months | 0.00 | 0.159715E+09 | 0.00 | 0.00 | 3442341.55 | 0.00 | 0.00 | 0.00 | 0.47 |
Maximum of Months | 0.159503E+10 | 0.226070E+10 | 0.00 | 2762305.63 | 23839593.06 | 0.310597E+09 | 0.940374E+09 | 0.00 | 0.81 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 31171110.80 | 0.00 | 2676190.27 | 0.00 | 0.00 | 0.326026E+09 | 0.00 | 0.28 |
February | 0.00 | 48201917.42 | 0.00 | 4432491.84 | 0.00 | 0.00 | 0.176014E+09 | 0.00 | 0.29 |
March | 0.00 | 83138210.77 | 0.00 | 8577087.26 | 0.00 | 0.00 | 0.220159E+09 | 0.00 | 0.31 |
April | 0.00 | 0.159000E+09 | 0.00 | 4903372.94 | 0.00 | 0.00 | 50695113.11 | 0.00 | 0.29 |
May | 0.00 | 0.422331E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
June | 0.00 | 0.519274E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
July | 0.00 | 0.601281E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
August | 0.00 | 0.604596E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
September | 0.00 | 0.427770E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
October | 0.00 | 0.348255E+09 | 0.00 | 1535060.49 | 0.00 | 0.00 | 45155846.69 | 0.00 | 0.28 |
November | 0.00 | 0.123660E+09 | 0.00 | 6759912.08 | 0.00 | 0.00 | 0.125931E+09 | 0.00 | 0.28 |
December | 0.00 | 90330746.47 | 0.00 | 10864818.43 | 0.00 | 0.00 | 0.241486E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.00 | 0.345901E+10 | 0.00 | 39748933.31 | 0.00 | 0.00 | 0.118547E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 31171110.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.00 | 0.604596E+09 | 0.00 | 10864818.43 | 0.00 | 0.00 | 0.326026E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.298280E+09 | 0.00 | 20055692.85 | 0.00 | 0.00 | 0.327033E+10 | 0.00 | 0.28 |
February | 0.00 | 0.476950E+09 | 0.00 | 38924448.20 | 0.00 | 0.00 | 0.176508E+10 | 0.00 | 0.29 |
March | 0.00 | 0.830311E+09 | 0.00 | 78470903.54 | 0.00 | 0.00 | 0.220448E+10 | 0.00 | 0.31 |
April | 0.00 | 0.159201E+10 | 0.00 | 46416107.14 | 0.00 | 0.00 | 0.507103E+09 | 0.00 | 0.29 |
May | 0.00 | 0.418739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
June | 0.00 | 0.517955E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
July | 0.00 | 0.600688E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
August | 0.00 | 0.604095E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
September | 0.00 | 0.422804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
October | 0.00 | 0.347029E+10 | 0.00 | 14130169.21 | 0.00 | 0.00 | 0.451595E+09 | 0.00 | 0.28 |
November | 0.00 | 0.123506E+10 | 0.00 | 62451922.37 | 0.00 | 0.00 | 0.126096E+10 | 0.00 | 0.28 |
December | 0.00 | 0.903810E+09 | 0.00 | 99561346.15 | 0.00 | 0.00 | 0.241800E+10 | 0.00 | 0.28 |
Annual Sum or Average | 0.00 | 0.344495E+11 | 0.00 | 0.360011E+09 | 0.00 | 0.00 | 0.118775E+11 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.298280E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.00 | 0.604095E+10 | 0.00 | 99561346.15 | 0.00 | 0.00 | 0.327033E+10 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 36794530.98 | 29611974.49 | 0.00 | 1369048.12 | 0.00 | 0.00 | 0.291432E+09 | 0.00 | 0.28 |
February | 0.00 | 47466476.53 | 0.00 | 3532054.14 | 0.00 | 0.00 | 0.177339E+09 | 0.00 | 0.29 |
March | 0.00 | 82849716.23 | 0.00 | 7487902.22 | 0.00 | 0.00 | 0.221113E+09 | 0.00 | 0.31 |
April | 0.00 | 0.159005E+09 | 0.00 | 4594099.33 | 0.00 | 0.00 | 50883005.36 | 0.00 | 0.29 |
May | 0.00 | 0.420131E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
June | 0.00 | 0.518287E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
July | 0.00 | 0.600553E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
August | 0.00 | 0.607391E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
September | 0.00 | 0.423949E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
October | 0.00 | 0.347038E+09 | 0.00 | 1358214.89 | 0.00 | 0.00 | 45296830.17 | 0.00 | 0.28 |
November | 0.00 | 0.123285E+09 | 0.00 | 6023839.28 | 0.00 | 0.00 | 0.126597E+09 | 0.00 | 0.28 |
December | 0.00 | 90167365.16 | 0.00 | 9468698.47 | 0.00 | 0.00 | 0.242604E+09 | 0.00 | 0.28 |
Annual Sum or Average | 36794530.98 | 0.344973E+10 | 0.00 | 33833856.45 | 0.00 | 0.00 | 0.115527E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 29611974.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 36794530.98 | 0.607391E+09 | 0.00 | 9468698.47 | 0.00 | 0.00 | 0.291432E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.823293E+09 | 0.00 | 0.159213E+09 | 0.00 | 0.00 | 0.745830E+10 | 0.00 | 0.32 |
February | 0.00 | 0.111714E+10 | 0.00 | 0.223179E+09 | 0.00 | 0.00 | 0.404521E+10 | 0.00 | 0.32 |
March | 0.00 | 0.182904E+10 | 0.00 | 0.431959E+09 | 0.00 | 0.00 | 0.482783E+10 | 0.00 | 0.34 |
April | 0.00 | 0.308023E+10 | 0.00 | 0.239291E+09 | 0.00 | 0.00 | 0.108909E+10 | 0.00 | 0.32 |
May | 0.00 | 0.994081E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 |
June | 0.00 | 0.116372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.34 |
July | 0.00 | 0.132427E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
August | 0.00 | 0.112334E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
September | 0.00 | 0.101546E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 |
October | 0.00 | 0.783394E+10 | 0.00 | 78074821.39 | 0.00 | 0.00 | 0.101473E+10 | 0.00 | 0.32 |
November | 0.00 | 0.272192E+10 | 0.00 | 0.337924E+09 | 0.00 | 0.00 | 0.269382E+10 | 0.00 | 0.32 |
December | 0.00 | 0.182197E+10 | 0.00 | 0.544572E+09 | 0.00 | 0.00 | 0.526009E+10 | 0.00 | 0.31 |
Annual Sum or Average | 0.00 | 0.754363E+11 | 0.00 | 0.201421E+10 | 0.00 | 0.00 | 0.263891E+11 | 0.00 | 0.33 |
Minimum of Months | 0.00 | 0.823293E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
Maximum of Months | 0.00 | 0.132427E+11 | 0.00 | 0.544572E+09 | 0.00 | 0.00 | 0.745830E+10 | 0.00 | 0.35 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 09:04:59
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.431339E+12 | 0.103534E+11 | 0.00 | 0.147288E+13 | 0.967846E+12 |
February | 0.459024E+12 | 0.816866E+10 | 0.00 | 0.123101E+13 | 0.146220E+13 |
March | 0.524105E+12 | 0.789550E+10 | 0.00 | 0.123364E+13 | 0.210218E+13 |
April | 0.578944E+12 | 0.144821E+10 | 0.00 | 0.669908E+12 | 0.298023E+13 |
May | 0.574997E+12 | -0.110683E+11 | 0.00 | -0.564678E+12 | 0.289061E+13 |
June | 0.571216E+12 | -0.880602E+10 | 0.00 | -0.661765E+12 | 0.331308E+13 |
July | 0.590954E+12 | -0.158830E+11 | 0.00 | -0.769809E+12 | 0.383340E+13 |
August | 0.545171E+12 | -0.148966E+11 | 0.00 | -0.750264E+12 | 0.433691E+13 |
September | 0.473773E+12 | -0.142917E+11 | 0.00 | -0.581536E+12 | 0.275191E+13 |
October | 0.477881E+12 | -0.809111E+10 | 0.00 | -0.210959E+11 | 0.290752E+13 |
November | 0.373525E+12 | 0.439422E+10 | 0.00 | 0.105978E+13 | 0.235378E+13 |
December | 0.387172E+12 | 0.888376E+10 | 0.00 | 0.132037E+13 | 0.242660E+13 |
Annual Sum or Average | 0.598810E+13 | -0.318930E+11 | 0.00 | 0.363843E+13 | 0.323263E+14 |
Minimum of Months | 0.373525E+12 | -0.158830E+11 | 0.00 | -0.769809E+12 | 0.967846E+12 |
Maximum of Months | 0.590954E+12 | 0.103534E+11 | 0.00 | 0.147288E+13 | 0.433691E+13 |